Uponor
T-38 24v Programmable Room Thermostat
T-38 Operating Buttons
T-38 Programmable Room Thermostat
Button Description
Parameter and Mode Settings Menu To enter the parameter and mode settings menu: 1. Press and hold the OK button for three seconds to enter the settings menu.
The OK button is used to: The first menu, CLK (clock), is displayed Enter and exit the settings menu Confirm a setting
2. Press the + button repeatedly to reach the other menus.
Select comfort or economy mode
The menus are presented in the following order:
The minus and plus sign buttons are used to: Set the temperature setpoint
CLK (clock) PRG (programming) HOL (holiday mode) MOD (regulation choices) BAL (balancing mode) T 째C (temperature set point) CAL (calibration) OFF (standby mode)
Toggle between comfort and economy modes Modify settings in the settings menus
3. Press the - button to run the menu sequence in Opposite order.
Enter and exit the lock mode (press and hold simultaneous for 3 seconds)
4. Press and hold the OK button for three seconds to exit the settings menu.
john.ashford@uponor.com 2012
Page 1 of 7
T-38 Operating Buttons
Power-up
Run Mode ( Continued )
At power-up the thermostat designation, T-38, and the software version is shown for three seconds.
Example:
Then the thermostat enters into run mode.. Example:
In the example above the following is displayed:
• System works in heating mode • Room temperature is 22.3 °C • System works in comfort mode
Run Mode Run mode display description
• System works in auto-balancing mode, heating demand is on
In run mode the screen displays the following:
• Today is Thursday
• Room temperature in degrees Celsius
• Time is 15:47
• Heating or cooling icon depending on system working mode
Changing Temperature Setpolnt
• ECO or comfort mode icon depending on system working mode
To adjust the temperature setpolnt of the current mode from the run mode screen:
• Heating/Cooling demand icon if a demand is present
1. Press the + or - button once. The screen shows the current setpolnt flashing.
• Standby icon if the system is set in standby mode
2. Press the + or - button repeatedly to adjust the Setpolnt temperature.
• Holiday mode icon and remaining days if system is set in holiday mode • Lock mode icon if the thermostat is set in lock mode
When the new setpolnt is set, the screen returns to run mode after a few seconds, showing the room temperature.
• Manual override icon if the system is set in forced comfort or ECO mode • If a connected floor sensor is faulty, this is indicated by a flashing star to the left of the displayed room temperature • (T-38 only) Weekday and time
john.ashford@uponor.com 2012
Page 2 of 7
T-38 Operating Buttons
Setting forced ECO or comfort mode
CLK – Clock Settings T-38
To set the system in forced ECO or comfort mode:
The clock menu is used to set date and time.
1. Press the OK button. The house icon starts flashing.
To set the clock parameters:
2. Press the + or - button to change from comfort to ECO mode or the other way around.
1. Press and hold the OK key for 3 seconds. The screen displays CLK (clock). 2. Press OK to enter the clock menu.
3. Press the OK button. The screen returns to run mode displaying the selected ECO or comfort mode and the manual
The screen displays YR (year) and four digits designating the year are blinking.
override icon.
3. Press the + and - buttons to change the setting.
To remove forced mode:
4. Press OK to confirm the setting. The screen displays MTH (month) and two digits designating the month are blinking.
1. Press and hold the OK key for 3 seconds. 5. Press the + and - buttons to change the setting. The manual override icon
disappears and
the system returns to the mode, ECO or Comfort, as defined by the programming.
6. Press OK to confirm the setting. The screen displays DAY (day) and two digits designating the date are blinking. 7. Press the + and - buttons to change the setting.
Parameter and Mode Settings Menu To enter the parameter and mode settings menu: 1. Press and hold the OK button for three seconds to enter the settings menu.
8. Press OK to confirm the setting. The screen displays TME (time) and either 24:H or AM/PM 12:H, designating the time format are blinking. 9. Press the + and - buttons to change the setting.
• T-38: The first menu, CLK (clock), is displayed 2. Press the + button repeatedly to reach the other menus. The menus are presented in the following order:
10. Press OK to confirm the setting. The screen displays TME (time) and four digits designating the time are blinking. 11. Press the + and - buttons to change the setting:
Uponor Thermostat T-38
• Press once and the time setting increments with a 1
• CLK (clock) • PRG (programming) • HOL (holiday mode) • MOD (regulation choices) • BAL (balancing mode) • T °C (temperature setpoint) • CAL (calibration) • OFF (standby mode)
minute step.
• Press continuously and the time setting increments with 1 minute steps, after a few seconds increments are made with 10 minute steps and then 1 hour steps.
12. Press OK to confirm the setting.
3. Press the -button to run the menu sequence in opposite order.
The screen displays S/W (summer-winter time).
4. Press and hold the OK button for three seconds to exit the settings menu.
john.ashford@uponor.com 2012
Continued
Page 3 of 7
T-38 Operating Buttons
CLK – Clock Settings T-38
There are three choices: 1
Continued
2
3
4
5
6
7
Monday till Friday, default setting
Two alternatives are selectable: • S/W and OK displayed: Automatic change of summer winter time activated
1
2
3
4
5
6
7
Monday till Saturday
• S/W only displayed: Automatic change of summer winter time deactivated 1 Example:
2
3
4
5
6
7
Monday till Sunday
Automatic summer-winter time changes elected.
3. Press OK to confirm the setting. The digital clock starts flashing. 4. Press and hold the OK key for 3 seconds to select the default schedule. The diagram below shows the default schedule for Monday till Friday or Monday till Saturday programming groups.
13. Press OK to confirm the setting. The next diagram shows the default schedule for Monday till Sunday programming group.
PRG – Programming The programming menu is used to adjust the settings for comfort and economy modes. To change the programming: 1. When PRG is displayed, press OK to enter the menu.
5. Press the + and - buttons to modify the default clock setting: • Press once and the time setting increments with a 1 minute step. • Press continuously and the time setting increments with 1 minute steps, after a few seconds increments are made with 10 minute steps and then 1 hour steps. • Set the clock to the time for the first comfort/economy changeover. 6. Press the OK key to change between comfort and economy mode at the desired time. Continue to the next comfort/economy changeover with the + button. Up to 5 changes in 24 hours are permitted.
The group of days flashes (day numbers with frames) john.ashford@uponor.com 2012
Continued
Page 4 of 5
T-38 Operating Buttons
PRG – Programming
HOL – Holiday Mode T-38
Continued If the group Monday till Saturday was selected, then 1
2
3
4
5
6
7
Sunday is displayed. If the group Monday till Sunday was selected, then the screen displays the next menu, 8. Press and hold the OK key for 3 seconds to select the default schedule.
The holiday mode menu is used to set a temperature setpoint that is used for a defined period when the house is empty. Entering holiday mode 1. When HOL is displayed, press OK to enter the menu. The screen displays the following: Heating
or cooling
Holiday suitcase
icon depending on mode icon
Ambient temperature
Empty house
icon flashing
9. Press the + and - buttons to modify the default clock setting:
1 d flashing, designating the number of days the holiday mode is active
• Press once and the time setting increments with a 1minute step.
2. Press the + and - buttons to set the number of days the holiday mode shall be active.
• Press continuously and the time setting increments with 1 minute steps, after a few seconds increments are made with 10 minute steps and then 1 hour steps.
3. Press OK to confirm the setting.
• Set the clock to the time for the first comfort/ economy changeover.
4. Press the + and - buttons to change the holiday mode temperature setpoint.
10. Press the OK key to change between comfort and economy mode at the desired time.
Default setting: 18 °C
Continue to the next comfort/economy changeover with the + button. Up to 5 changes in 24 hours are permitted. 11. Continue stepping the clock until midnight is passed. The screen displays the next menu, HOL.
The holiday mode temperature setpoint and the empty house icon are flashing.
Setting range: 10 – 30 °C 5. Press OK to confirm the setting. The screen enters run mode. The thermostat starts to countdown the days when holiday mode is active. The holiday mode ends automatically at 00:00 the day 0. Exiting holiday mode 1. Press and hold the OK button for three seconds. The holiday mode is cancelled and the run mode is entered.
john.ashford@uponor.com 2012
Page 5 of 7
T-38 Operating Buttons
MOD – Regulation Choices
BAL – Balancing Mode
The regulation choices menu is used to set the regulation mode of the thermostat.
The balancing mode menu is used to select between manual and auto-balancing.
1. When MOD is displayed, press OK to enter the menu.
The auto-balance function removes the need for manual balancing of the manifold at installation.
The screen displays one of the following:
The principle for automatic balancing is that the energy required by each loop is distributed in pulses.
• RT – room sensor regulation • RFT – room sensor regulation with floor sensor limitation • RS – remote sensor regulation 2. Press the + or - button to change the setting.
The length of the pulses in each loop is calculated from the actual heat demand of the room. 1. When BAL is displayed, press OK to enter the menu.
3. Press OK to confirm the setting. The screen displays one of the following: If RT or RS regulation mode is selected, the next menu is displayed, see section If RFT regulation mode is selected, the next regulation setting, is displayed.
• MAN – manual balancing • AB – automatic balancing 2. Press the + or - button to change the setting.
4. (Heating mode only) 3. Press OK to confirm the setting The symbol (heating mode) and MAX is displayed (maximum floor temperature limitation). 4.1. Press OK to display the limitation temperature. 4.2. Press the + and - buttons to change the setting. Default setting: 26 °C Setting range: 20 – 35 °C
The menu for comfort and economy mode temperatures is used to set the setpoint temperature in comfort mode and the setback temperature in economy mode. The settings will apply to the mode the system is set to work in, heating or cooling.
4.3. Press OK to confirm the setting. 5. (Heating and cooling modes) The heating or cooling icon and MIN is displayed (low floor temperature limitation). 5.1. Press OK to display the limitation temperature. 5.2. Press the + and - buttons to change the setting. Default setting: 20 °C Setting range: 10 – 35 °C
T°C – Comfort and economy mode temperatures (T-38 only)
The default comfort and economy settings are used unless the user changes a setpoint from the run mode screen. In that case the latest setpoint setting will be applied. Adjusted settings are saved in the thermostat. 1. When T °C is displayed, press OK to enter the menu.
Press OK to confirm the setting
The screen displays the setpoint temperature and the comfort icon. Continued
john.ashford@uponor.com 2012
Page 6 of 7
T-38 Operating Buttons
OFF – Standby Mode
T°C – Comfort and economy mode temperatures (T-38 only)
In standby mode, the regulation of the room temperature is disabled, but thermostat still displays the current room temperature.
Continue 2. Press the + or -button to change the setting.
Entering standby mode Default setting, heating mode: 21 °C Default setting, cooling mode: 26 °C
1. Press OK to confirm the standby mode.
Setting range: 5 -30 °C Setting accuracy: 0.5 °C
The standby icon and the room temperature is displayed.
3. Press OK to confirm the setting.
Exiting standby mode
The screen displays the economy setpoint temperature and the ECO icon.
1. Press and hold OK for three seconds.
4. Press the + or - button to change the setting.
The thermostat name and software version are displayed for two seconds. Then the thermostat enters run mode.
Default setting, heating mode: 17 °C Default setting, cooling mode: 30 °C
Lock Mode
Setting range: 5 - 30 °C Setting accuracy: 0.5 °C
The three operating buttons can be locked to prevent unintentional use.
5. Press OK to confirm the setting.
Entering lock mode
CAL – Calibration The calibration menu is used to adjust the temperature sensor in the thermostat. 1. When CAL is displayed, press OK to enter the menu.
The lock icon appears. Other displayed Information remains and the thermostat operates as set-up. Exiting lock mode
The room temperature is displayed. 2. Press the + and - buttons to change the setting in 0.1 °C steps. Setting range: -3 °C to +3 °C
1. Press and hold the + and - buttons simultaneously for three seconds.
1. Press and hold the + and - buttons simultaneously for three seconds. The lock
icon disappears.
3. Press OK to confirm the setting.
john.ashford@uponor.com 2012
Page 7 of 7