Guide to the Wiring Regulations 17th Edition IEE Wiring Regulations (BS 7671: 2008) Darrell Locke IEng MIEE ACIBSE Electrical Contractors’ Association
in association with
Extracts from BS 7671: 2008 have been kindly provided by the Institution of Engineering and Technology (IET) and extracts from other standards have been reproduced with permission from British Standards Institution (BSI). Information and copies of standards are available from BSI at http://www.bsonline.bsi-global.com
John Wiley & Sons, Ltd
Guide to the Wiring Regulations
Guide to the Wiring Regulations 17th Edition IEE Wiring Regulations (BS 7671: 2008) Darrell Locke IEng MIEE ACIBSE Electrical Contractors’ Association
in association with
Extracts from BS 7671: 2008 have been kindly provided by the Institution of Engineering and Technology (IET) and extracts from other standards have been reproduced with permission from British Standards Institution (BSI). Information and copies of standards are available from BSI at http://www.bsonline.bsi-global.com
John Wiley & Sons, Ltd
Copyright © 2008 John Wiley & Sons Ltd, The Atrium, Southern Gate, Chichester, West Sussex PO19 8SQ , England Telephone (+44) 1243 779777 Email (for orders and customer service enquiries): cs-books@wiley.co.uk Visit our Home Page on www.wiley.com All Rights Reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, scanning or otherwise, except under the terms of the Copyright, Designs and Patents Act 1988 or under the terms of a licence issued by the Copyright Licensing Agency Ltd, 90 Tottenham Court Road, London W1T 4LP, UK, without the permission in writing of the Publisher. Requests to the Publisher should be addressed to the Permissions Department, John Wiley & Sons Ltd, The Atrium, Southern Gate, Chichester, West Sussex PO19 8SQ , England, or emailed to permreq@wiley.co.uk, or faxed to (+44) 1243 770620. Designations used by companies to distinguish their products are often claimed as trademarks. All brand names and product names used in this book are trade names, service marks, trademarks or registered trademarks of their respective owners. The Publisher is not associated with any product or vendor mentioned in this book. This publication is designed to provide accurate and authoritative information in regard to the subject matter covered. It is sold on the understanding that the Publisher is not engaged in rendering professional services. If professional advice or other expert assistance is required, the services of a competent professional should be sought. ECA is the trademark of the Electrical Contractors’ Association. The ECA is the UK’s largest and leading trade association representing electrical, electronic, installation engineering and building services companies. Website www.eca.co.uk Whilst every care has been taken to ensure the accuracy of the information in this book, neither the author or the ECA can accept liability for any inaccuracies or omissions arising from the information provided. SELECT are Scotland’s trade association for the electrical, electronics and communications systems industry. Website www.select.org.uk Other Wiley Editorial Offices John Wiley & Sons Inc., 111 River Street, Hoboken, NJ 07030, USA Jossey-Bass, 989 Market Street, San Francisco, CA 94103-1741, USA Wiley-VCH Verlag GmbH, Boschstr. 12, D-69469 Weinheim, Germany John Wiley & Sons Australia Ltd, 42 McDougall Street, Milton, Queensland 4064, Australia John Wiley & Sons (Asia) Pte Ltd, 2 Clementi Loop #02-01, Jin Xing Distripark, Singapore 129809 John Wiley & Sons Canada Ltd, 6045 Freemont Blvd, Mississauga, ONT, L5R 4J3 Wiley also publishes its books in a variety of electronic formats. Some content that appears in print may not be available in electronic books. Library of Congress Cataloging-in-Publication Data is available British Library Cataloguing in Publication Data A catalogue record for this book is available from the British Library ISBN 978-0-470-51685-0 (PB) Typeset in 11/13 pt Baskerville by Sparks, Oxford – www.sparks.co.uk Printed and bound in Italy by Printer Trento This book is printed on acid-free paper responsibly manufactured from sustainable forestry in which at least two trees are planted for each one used for paper production.
Contents
Contents Foreword by Giuliano Digilio
xi
Preface
xiii
Acknowledgements
xvii
Chapter A – BS 7671: 2008 – Introduction and Overview A 1 Introduction to BS 7671: 2008 A 2 Plan and layout of BS 7671: 2008 A 3 Overview of major changes
1 1 4 5
Chapter B – Legal Relationship and General Requirements of BS 7671: 2008 B 1 Legal requirements and relationship B 1.1 Key UK legislation B 1.2 The Electricity at Work Regulations 1989 (EWR 1989) B 1.3 The Electricity Safety, Quality and Continuity Regulations 2002 (as amended) B 1.4 The Electricity Act 1984 (as amended) B 1.5 The Building Act 1984, The Building Regulations and Part P B 1.6 The Electromagnetic Compatibility Regulations 2005 (EMC) B 1.7 Tort and negligence B 2 The role of Standards B 3 Part 3 of BS 7671: 2008 – assessment of general characteristics Chapter C – Circuitry and Related Parts of BS 7671: 2008 C 1 Introduction C 2 Design procedure overview C 3 Load assessment
11 11 11 12 13 14 14 16 16 17 19 21 21 22 23
v
Contents
C 4
C 5
C 6
C 7 C 8 C 9
C 10 C 11
C 3.1 Principles and definitions C 3.2 Maximum demand assessment C 3.3 Diversity Circuit design C 4.1 Introduction C 4.2 Protection against overcurrent in general C 4.3 Overload protection C 4.4 Fault protection C 4.5 Voltage drop C 4.6 Disconnection and electric shock Submains C 5.1 Diversity C 5.2 Distribution circuit (submain) selection C 5.3 Armouring as a cpc C 5.4 Automatic disconnection for submains Discrimination co-ordination C 6.1 Principles and system co-ordination C 6.2 Fuse-to-fuse discrimination C 6.3 Circuit breaker to circuit breaker discrimination C 6.4 Circuit breaker to fuse discrimination Parallel cables C 7.1 General and 7671 requirements C 7.2 Unequal current sharing Harmonics C 8.1 Requirements C 8.2 Harmonic assessment Standard final circuit designs C 9.1 Introduction and scope C 9.2 Standard domestic circuits C 9.3 All-purpose standard final circuits RCDs and circuitry C 10.1 Introduction, increased use of RCDs C 10.2 Consumer unit arrangements for RCDs Ring and radial final circuits C 11.1 Introduction C 11.2 Ring final circuits C 11.3 Radial final circuits
Chapter D – Selection and Erection – Equipment D 1 Introduction and fundamentals D 2 Compliance with Standards D 3 Identification of conductors
vi
23 26 28 30 30 32 32 46 49 55 64 64 64 65 67 67 67 69 70 71 72 72 73 73 73 74 74 74 77 79 83 83 84 87 87 87 89 91 91 92 93
Contents
D 3.1 Principle of required identification (514.3.1) D 3.2 Identification by colour D 3.3 Identification by marking D 3.4 Additions and alterations – identification D 3.5 Interface marking D 3.6 d.c. identification D 4 EMC and prevention of mutual detrimental influences D 4.1 Introduction D 4.2 EMC directive and BS 7671 D 4.3 EMC cable separation – power, IT, data and control cables D 4.4 Cable management and EMC D 5 Wiring systems D 5.1 The choice of wiring systems D 5.2 Circulating currents and eddy currents in single-core installations D 5.3 Electrical connections and joints D 5.4 Wiring systems – minimizing spread of fire D 5.5 Proximity to other services D 6 Circuit breakers D 6.1 General D 6.2 Operation and characteristics D 6.3 Ambient temperature de-rating D 7 Residual current devices D 7.1 BS 7671 applications D 7.2 Operation and BS 7671 requirements D 7.3 Unwanted RCD tripping and discrimination D 7.4 d.c. issues for RCDs D 7.5 TT installations and RCDs D 8 Other equipment D 8.1 Isolation and switching D 8.2 Consumer units for domestic installations D 8.3 Overvoltage, undervoltage and electromagnetic disturbances D 8.4 Surge protective devices D 8.5 Insulation monitoring devices (IMDs) D 8.6 Residual current monitors (RCMs) D 9 Generating sets D 10 Rotating machines D 11 Plugs and socket outlets D 12 Electrode water heaters and electrode boilers D 13 Heating conductors D 14 Lighting and luminaires D 15 Safety services
vii
94 95 97 97 98 98 101 101 101 102 105 106 106 110 112 117 119 119 119 120 124 125 125 127 128 130 130 132 132 132 132 133 135 135 137 138 139 140 141 141 144
Contents
D 15.1 Introduction D 15.2 Classification of break times D 15.3 Safety sources D 15.4 Circuits for safety services D 16 Ingress protection (IP), external influences D 16.1 General D 16.2 Equipment applications and examples
144 144 145 146 146 146 149
Chapter E – Earthing and Bonding E 1 Introduction E 2 Earthing arrangements E 3 General requirements of earthing and bonding E 4 Protective conductors E 4.1 General E 4.2 Physical types of protective conductor E 4.3 Sizing protective conductors E 4.4 Protective conductors up to 16 mm2 E 4.5 Earthing conductor E 5 Armoured cables as protective conductors E 5.1 General E 5.2 ERA report on current sharing between armouring and cpc E 5.3 ECA advice and recommendations E 6 Protective equipotential bonding E 6.1 Purpose of protective equipotential bonding E 6.2 BS 7671 requirements E 6.3 Bonding solutions for the modern installation E 6.4 Sizing protective bonding conductors E 6.5 Domestic protective equipotential bonding layouts E 6.6 Supplementary equipotential bonding E 7 High earth leakage installations
151 151 153 159 162 162 162 164 165 167 167 167 168 169 169 169 170 170 177 178 178 183
Chapter F – Inspection, Testing and Certification (Part 6) F 1 Introduction F 1.1 Inspection and testing – an integrated procedure F 2 Visual inspection F 3 Testing F 3.1 Introduction – pass and fail nature F 3.2 Required tests F 3.3 Continuity testing F 3.4 Ring continuity F 3.5 Insulation testing F 3.6 Polarity testing
185 185 185 186 188 188 188 189 193 196 200
viii
Contents
F 3.7 Earth fault loop impedance (ELI) testing F 3.8 Prospective fault current testing F 3.9 Testing RCDs and other functional tests F 3.10 Verification of voltage drop F 4 Certification paperwork F 4.1 Introduction, various certificates and schedules F 4.2 Overview of certificates and schedules F 4.3 Completing the paperwork
201 205 206 208 208 208 208 209
Chapter G – Special Locations G 1 Introduction: Purpose and principles G 1.1 Introduction G 1.2 Purpose and principles G 1.3 Particular requirements and numbering G 2 Locations containing a bath or shower (701) G 2.1 Introduction and risks G 2.2 Zone concept G 2.3 Electric shock requirements G 2.4 Equipment selection and erection G 3 Swimming pools and other basins (702) G 3.1 Introduction and risks G 3.2 Zone concept G 3.3 Requirements and guidance G 4 Agricultural and horticultural premises (705) G 4.1 Introduction, purpose and principles G 4.2 Requirements and guidance G 5 Caravan parks and camping parks (708) G 5.1 Introduction, purpose and principles G 5.2 Requirements and guidance G 6 Exhibitions, shows and stands (711) G 6.1 Introduction and risks G 6.2 Requirements and guidance G 7 Solar photovoltaic (PV) power supply systems (712) G 7.1 Introduction, principles and terminology G 7.2 Requirements G 7.3 Notes and guidance G 8 Mobile or transportable units (717) G 8.1 Scope and application G 8.2 Requirements G 8.3 Notes and guidance G 9 Floor and ceiling heating systems (753) G 9.1 Introduction
219 219 219 220 221 221 221 222 226 227 228 228 229 232 234 235 235 239 239 240 243 244 244 246 246 249 249 253 253 254 254 256 256
ix
Contents
G 9.2 Requirements G 9.3 Notes and guidance
256 257
Appendices Appendix 1 – Standards and bibliography Appendix 2 – Popular cables: current rating tables from BS 7671: 2008 Appendix 4 Appendix 3 – Limiting earth fault loop impedance tables from BS 7671: 2008 Appendix 4 – Cable data-resistance, impedance and ‘R1 + R2’ values Appendix 5 – Fuse I 2t characteristics
261 262
Index
277
x
267 270 272 276
Foreword
Foreword by Giuliano Digilio
Head of Technical Services, Electrical Contractors’ Association (ECA) The IEE Wiring Regulations and more lately BS 7671 have always been important for electrical contractors and for installation designers, and they are a key factor in the implementation of electrical safety within the UK and indeed overseas. The IEE Wiring Regulations go back to the end of the 19th century, almost to the time of the very first electrical installation within the UK. The ECA is fully committed to the development of standards for the national BS 7671 committee as well as corresponding work in both the European Committee for Electrotechnical Standardisation (CENELEC) and the International Electrotechnical Commission (IEC). This includes a considerable amount of work in the preparation for BS7671: 2008. I am pleased that you have purchased the ECA Guide to the Wiring Regulations and I trust that this quality publication will aid to enhance the understanding and knowledge within the electrical industry for both electrical contractors and electrical designers.
xi
Preface
Preface This book discusses the requirements of BS 7671: 2008, also known as the IEE Wiring Regulations 17th Edition, published during January 2008. The aim of the guide is to provide an explanation of the theory and reasons behind the Regulations, their meaning and the intent of their drafting. The book provides advice and guidance, demystifying the ‘requirements’ wherever possible. Practical and original solutions have been provided, which are often not found in other industry guidance. The guide is a valuable resource for all users of BS 7671 including apprentices, electricians who perhaps want to ‘dig a bit deeper’ into the background of the Regulations, together with electrical technicians, installation engineers and design engineers. Most individuals who have any involvement with BS 7671 will find the book of considerable help and benefit in their everyday work. To derive use and benefit from the book it is assumed that readers have knowledge of electrical installation engineering to a basic level. However, ‘defined scope’ installers and those at similar levels will also gain from working through the book thanks to its clear diagrams. Given these prerequisites, the book can be used as a learning text for the 17th Edition Wiring Regulations as long as readers have a copy of the Standard itself. Indeed, a copy of BS 7671: 2008 is required as a reference document when using this book, and readers should at least familiarize themselves with the terminology and definitions used in the basic Standard. Guide to the Wiring Regulations is intended to be read on a chapter-by-chapter basis by those involved at the level of designing and constructing installations. This is something that is not easy to achieve with books on this subject as accessing the basic Standard itself can be quite daunting and heavy going.
xiii
Preface
A particular emphasis or expansion has been made to those subjects that are often confused by readers of BS 7671. In this respect the text does not wander off to discuss ancillary subjects; the text stays focused on providing an understanding of those concepts demanded of BS 7671 so that design and installation decisions can be made by readers. The book’s coverage is comprehensive, and all Parts of the Regulations have been addressed within the topic lead chapters. Design aspects have been included as they are integral to installations. Often, individuals or organizations consider themselves to be either pure designers or pure installers. However, even by the act of an ‘installer’ in selecting equipment that was unspecified by the designer, e.g. selecting cables or other equipment, an element of design is being carried out. The same concept is true of domestic installers who select ‘standard designs’ but perhaps feel that they do not design. These individuals are considered to be designers even where the design is not calculated for each installation. The adoption of a ‘standard design’ or a ‘standard cable size’ by the installer is in fact design by the installer. The book is arranged into topic lead chapters, at the heart of which are Chapters C (Circuitry) and D (Selection and Erection of Equipment). Although the titles of these chapters seem simple enough, they are comprehensive and encompass about 70% of the Regulations. Most requirements of the Regulations have been condensed and summarized using tables aided by clear, simple diagrams. Some tables seem quite long but they are still very condensed compared with the regulations that they summarize. As an example, the new Section 559 in BS 7671 includes 44 regulations, but these are summarized in a 15-row table. The nature of the Regulations is that they must state all facts. However, the repetition of the most basic information in the guide was not considered beneficial; for example, where the regulation is written in the following style: ‘cables shall be large enough for the anticipated current’ This type of regulation is either not expanded upon in the guide or it is explained as follows: ‘cables shall be 6 mm2 minimum’. The book includes five printed appendices and further appendices are available as downloads from the companion website. Appendices that have been included on the Companion Website were either considered to be non-essential for most readers,
xiv
Preface
or were items that may be subject to change at a future date. The Companion Website can be found at: http://www.wiley.com/go/eca_wiringregulations Although more experienced readers may wish to jump to Chapter C, the introductory Chapters A and B are worth spending some time on. Within these chapters, the legal standing of BS 7671: 2008 is discussed together with its relationship with key UK law in the area of electrical installations. The general requirements of BS 7671: 2008 are also summarized within these chapters.
xv
Acknowledgements
Acknowledgements I would like to thank my wife Julie and my children for their patience, particularly throughout 2007, when much of the drafting of this book took place. I also give particular thanks to Paul Cook, former staff member of IET, for his assistance with the Circuitry and Earthing and Bonding chapters, and to Leon Markwell, also former IET staff member, for his help with the Special Locations chapter. I also thank James O’Neil, Director of Engineering of NG Bailey Limited, and Phil MacDonald, Principal Project Electrical Design Engineer of Shepherd Engineering Services, for acting as general readers, and Ken Morton, HM Principal Electrical Inspector, Health & Safety Executive, for his comments on Chapter B. With thanks to David Thompson for the book design concept and for his creation of the illustrations. Finally, I also wish to thank Simone Taylor, Nicky Skinner and their colleagues at the Wiley office, Chichester. Darrell Locke, October 2007
xvii
BS 7671: Introduction and Overview
A
BS 7671: 2008 – Introduction and Overview A 1
Introduction to BS 7671: 2008 BS 7671: 2008 was published during January 2008 as a significant new Edition of this fundamental Standard. BRITISH STANDARD
BS 7671:2008
Requirements for Electrical Installations
IEE Wiring Regulations Seventeenth Edition
© The Institution of Engineering and Technology and BSI NO COPYING IN ANY FORM WITHOUT WRITTEN PERMISSION
British Standards
Although the document is a British Standard, it is also known as (and jointly labelled as) the IEE Wiring Regulations 17th Edition; this is for copyright reasons. In spite of the fact that the IEE changed to the IET in 2006, the IET has maintained the brand of IEE, mainly for use in its Wiring Regulations documents and products. Indeed, the IEE logo appears on the front cover and the IET logo inside the front cover. Throughout this book, BS 7671: 2008 is referred to as BS 7671: 2008, or variously as BS 7671, the Wiring Regulations, the Regulations, the 17th edition or the Standard, depending upon the particular context. In essence, BS 7671: 2008 is virtually a European document. In fact, two parent documents as parts of the corresponding IEC standard have been used or adapted.
Guide to the Wiring Regulations: 17th Edition IEE Wiring Regulations (BS 7671: 2008) Darrell Locke © 2008 John Wiley & Sons Ltd
1
A
Guide to the Wiring Regulations
STANDARDS BODY
STANDARD (INSTALLATION)
World IEC
IEC 60364
European CENELEC
HD 60384
National JPEL/64
BS7671: 2008
Figure A 1.1 Installation standards at world, European and national levels.
Both IEC and CENELEC have ‘wiring regulation’ standards or rules for electrical installations. The general structure of IEC, CENELEC and BS 7671 is illustrated in Figure A 1.1. Many parts of the document originate in CENELEC in a ‘harmonized document’ (HD). The parent document is known as HD 60384 and comprises virtually all parts of the installation standard. Within BS 7671: 2008 there are now only a few regulations that are truly ‘UK only’, although some of the CENELEC parts of HD 60384 have been modified, cut or expanded for BS 7671. Some of the appendices of BS 7671 are homegrown. The Wiring Regulations committee has also used certain parts of the corresponding IEC document (IEC 60364) modified or virtually unmodified. A list of the parts of the corresponding CENELEC parts of HD 60384 used in BS 7671: 2008 is shown in Table A 1.1.
A
2
BS 7671: Introduction and Overview Table A 1.1 Corresponding parts of CENELEC HD 60384 used in BS 7671: 2008. CENELEC part
Issue date
Title
BS 7671 reference
prHD 60364–1
2007
Fundamental principles, assessment of general characteristics, definitions
Part 1, Part 2 (in part), Part 3
HD 384.4.41 S2/A1
2002
Protection against electric shock
Chapter 41
HD 384.4.42 S1 A2
1994
Protection against thermal effects
Chapter 42
HD 384.4.482 S1
1997
Protection against fire where particular risks or danger exist
Chapter 42
HD 384.4.43 S2
2001
Protection against overcurrent
Chapter 43
HD 384.4.473 A1
1980
Application of measures for protection against overcurrent
Chapter 43
HD 384.4.443 S1
2000
Protection against overvoltages
Section 443
prHD 60364–5-51
2003
Selection and erection of equipment – common rules
Chapter 51
HD 384.4.43 S2
2001
Protection against overcurrent
Chapter 53
prHD 60364–5-54
2004
Earthing arrangements, protective conductors and protective bonding conductors
Chapter 54
HD 384.7.714 S1
2000
Outdoor lighting installations
Section 559
HD 60364–7-715
2005
Extra-low voltage lighting installations
Section 559
HD 384.6.61 S2
2003
Initial verification
Part 6, Appendix 14
HD 60364–7-701
2007
Locations containing a bath or shower
Section 701
HD 384.7.702 S2
2002
Swimming pools and other basins
Section 702
HD 384.7.703
2005
Rooms and cabins containing sauna heaters
Section 703
HD 60364–7-704
2007
Construction and demolition site installations
Section 704
HD 60364–7-705
2007
Agricultural and horticultural premises
Section 705
HD 60364–7-706
2007
Conducting locations with restricted movement
Section 706
HD 384.7.708
2005
Caravan parks, camping parks and similar locations
Section 708
prHD 60364–7-709
2007
Marinas and similar locations
Section 709
HD 384.7.711
2003
Exhibitions, shows and stands
Section 711
HD 60364–7-712
2005
Solar photovoltaic (PV) power supply systems
Section 712
HD 60364–7-715
2005
Extra-low voltage lighting installations
Section 559
HD 60364–7-717
2004
Mobile or transportable units
Section 717
prHD 60364–7-721
200X
Electrical installations in caravans and motor caravans
Section 721
prHD 60364–7-740
2006
Temporary electrical installations for structures, amusement Section 740 devices and booths at fairgrounds, amusement parks and circuses
3
A
Guide to the Wiring Regulations
A 2
Plan and layout of BS 7671: 2008 Most users will not need to concern themselves with the correct terminology for groups of regulations and chapters etc., but an explanation of this has been added for completeness. Let us look at a single Regulation 411.3.2.1 and provide a diagram of the structure. Taking the first three digits, these relate as follows: Part 4
411
Section 411
Chapter 41 The remaining numbers make up the group, sub-set and regulation, but really only the group is of any significance: Group
Regulation
411 . 3 . 2 . 1
Sub-set There are seven parts to BS 7671: 2008 as follows:
A
Part
Contents
1
Scope, Object and Fundamental Principles
2
Definitions
3
Assessment of General Characteristics
4
Protection for Safety
5
Selection and Erection of Equipment
6
Inspection and Testing
7
Special Installation or Locations
4
BS 7671: Introduction and Overview
A 3
Overview of major changes There is not much of the document which remains unchanged compared with the 16th Edition; many changes were due to formal incorporation of CENELEC drafts required to achieve harmonization. This section gives an overview of technical changes that will manifest a change in practice or will be something that you should be aware of. As stated in the preface the subject of BS 7671 can be heavy going and this part of the book has been kept as short as possible. Readers may wish to skip this part of the book and start with the two key chapters, C and D. The following overview notes have been included, and are listed in what is considered to be an ‘order of significance’. Chapter 41 Protection against electric shock Revision of Chapter 41 is probably the most significant revision made for the 17th Edition. The whole structure of the chapter has been modified. The familiar terms used in the 16th Edition of ‘direct contact’ and ‘indirect contact’ have been replaced with ‘basic protection’ and ‘fault protection’ respectively. This terminology change by itself had ramifications in many other parts of the Regulations and these brought about logistical modifications. The various measures are termed ‘protective measures’. The structure of Chapter 41 was accordingly modified. Basic protection (insulation and enclosures) was considered something that designers and installers did not actually ‘consider’ and was shunted towards the rear of the chapter. The extremely rare measures of ‘placing out of reach’, ‘obstacles’, ‘non-conducting location’, ‘earth-free local equipotential bonding’ and ‘electrical separation’ were shunted further to the rear of the chapter. Thus, the main reading in the front end of Chapter 41 is about automatic disconnection. There have been changes to disconnection times. There are no ‘mixed’ disconnection times and disconnection times have been introduced for TT installations. As protection in TT installations will virtually always require an RCD, the reduced disconnection times in the 17th Edition are easily achieved (0.2 s for final circuits). A very significant new Regulation (411.3.3) requires a 30 mA RCD for socket-outlet circuits that are intended for use by ordinary persons. With a few exceptions, this
5
A
Guide to the Wiring Regulations
No Basic Protection
With Basic Protection (Enclosure)
L
L
N
N
E
E
No Basic Protection
With Fault Protection
L
L
N
N
E
E
L
Figure A 3.1  Basic protection and fault protection.
means all domestic installations. Commercial installations will generally remain exempt, as in most such situations individuals will have received instruction. Guidance on the structure, disconnection times and the use of RCDs is given in Chapter C of this book. Bathrooms 701 The 17th Edition goes the extra mile on harmonization with CENELEC for bathroom installations.
A
6
BS 7671: Introduction and Overview
The 16th Edition introduced the concept of ‘Zones’ to the regulations for bathrooms but fell short of harmonization with Europe in one key area: socket outlets in bathrooms. Section 701 now aligns with the European ethos; there is no Zone 3. Thus, outside Zone 2, which is 600 mm from the bath or shower, only the ‘general rules’ of the regulations apply and any equipment is allowed, although socket outlets have a special distance specified and must be at least 3 m from the boundary of Zone 1. All bathroom circuits now require a 30 mA RCD and a UK modification negates the need for supplementary bonding. Tables and methods of cable current-carrying capacity (Appendix 4 of BS 7671) The whole of the front end of this appendix has been modified for the 17th Edition. The modifications include the following:
•• ••
Overhaul of the installation methods and reference installation methods. New installation methods for cables in domestic style insulated cavity floors and lofts. ‘Rating’ factors for cables buried in the ground. Extensive additional rating factors for cables in free air (called correction factors in the 16th Edition).
Swimming pools (702) For the 17th Edition, the scope of section 702 now includes the basins of fountains and areas in natural waters including the sea and lakes, where they are specifically designated as swimming areas. Lighting and luminaires A completely new section for the 17th Edition is section 559 ‘Luminaires and Lighting Installations’, which totals six pages of text and some 44 new regulations. The new section deals with interior and exterior lighting installations and also applies to highway power supplies and street furniture. The section specifies such regulations as: ‘luminaire through wiring can only be used where the luminaire is specifically designed for this’, ‘heat specification of terminal wiring’, and others of a similar nature.
7
A
Guide to the Wiring Regulations
Inspection and testing Under this heading a new requirement is that the insulation resistance of conductors is tested to the cpc with the cpc connected to the earthing arrangement. New appendix with current-carrying capacity of busbars A new appendix has been added giving information on current-carrying capacity and voltage drop of busbars and powertrack. Chapter 56 Safety services This chapter has been modified and specifies ‘break times’ for standby systems. It sets regulations for such subjects as circuitry under fault conditions, parallel operation, and specifies the life of certain critical back-up batteries. High earth leakage currents Correctly termed ‘high protective conductor currents’. The former section 607 has been incorporated into Chapter 54 with some limited removal of ambiguous regulations. High voltage to low voltage faults A new section for the 17th Edition, but this not particularly significant for installers or designers. The section is only relevant for ‘private’ HV-LV substations, and even then the corresponding HV standards will need to be followed. Read Chapter D for a fuller explanation. Voltage drop Whilst in essence the basic requirements of the regulations on voltage drop have not changed, a new appendix suggests maximum voltage drops for both utility and private supplies. These voltage drops are separated into suggested limits for lighting and other circuits. Atmospheric and switching overvoltages There are a few pages of regulations on this subject, but there is not much of significance unless you have overhead distribution cables within your installation. Surge protective devices Although not required, there are regulations for installing surge protective devices (SPDs). Insulation monitoring devices (IMDs) and residual current monitors (RCMs) Similarly, although optional, there are regulations for installing these devices.
A
8
BS 7671: Introduction and Overview
RCMs in particular are becoming more widely specified, and there is guidance on this subject provided in Chapter D of this book. Caravan and camping parks (708) The main modification for the 17th Edition is that pitch socket-outlets are to be individually protected by a 30 mA RCD. New special installations or locations The following Special Installations sections are new to the 17th Edition:
•• •• •• •
709 Marinas 711 Exhibitions, shows and stands 712 Solar photovoltaic (PV) power supply systems 717 Mobile or transportable units 721 Electrical installations in caravans and motor caravans 740 Temporary electrical installations for structures, amusements and booths at fairgrounds 753 Floor and ceiling heating systems.
9
A
Legal Relationship and General Requirements of BS 7671: 2008
B
Legal Relationship and General Requirements of BS 7671: 2008
Introduction It is important to recognize that, for electrical designers and installers, there are legal responsibilities that must be both known and implemented whilst carrying out electrical installation or electrical design work. This chapter provides information and guidance on key UK legislation relevant to electrical installations. It also provides guidance on some contractual obligations relating to designs and installations. The chapter is neither a full legal guide nor a full contractual guide to requirements but provides a short overview. The chapter finishes with notes on the assessment of general characteristics (i.e. Part 3 of BS 7671: 2008).
B 1
Legal requirements and relationship
B 1.1
Key UK legislation Legislation can be in the form of an Act of Parliament (e.g. The Health & Safety at Work etc. Act 1974) or a Statutory Instrument (e.g. The Electricity at Work Regulations 1989). Acts are primary legislation and Statutory Instruments are secondary legislation made under a specific Act – in the case of the Electricity at Work Regulations, these were made under the Health & Safety at Work Act. Failing to comply with requirements of an Act of Parliament or a Statutory Instrument is a breach of criminal law and may result in a prosecution.
11
B
Guide to the Wiring Regulations
The following legislation is considered key and relevant to the electrical technical aspects of electrical designs and electrical installations:
•• ••
The Electricity at Work Regulations 1989 The Electricity Safety, Quality and Continuity Regulations 2000 (as amended 2006) The Electricity Act 1984 The Building Acts 1984 & 2000 (These apply to England and Wales only and implement the Building Regulations for England and Wales including Approved Document Part P (Electrical Safety – Dwellings). The Building (Scotland) Act 2003 (This applies in Scotland only and implements the Building (Scotland) Regulations 2004. The Electromagnetic Compatibility Regulations 2006 Tort
• •• B 1.2
The Electricity at Work Regulations 1989 (EWR 1989) The EWR 1989 is one of the most important pieces of legislation that an electrical designer or electrical contractor must be familiar with. You should know the content of this document as well as know of its existence. The EWR 1989 covers the safety of people, including employees, involved in all aspects of electrical and electronic systems in the UK. This includes selfemployed electricians working in domestic installations; all ‘electrical personnel’ in commercial installations and construction sites; and for commercial installations the end users. It also includes any person undertaking any work activity on or near electrical equipment. All electrical equipment and systems are encompassed by the legislation, from a battery to the national super grid at 400 kV. The legislation covers design, operation, isolation, maintenance, workspace and lighting equipment. There are Regulations on precautions for working on equipment made dead and on work on, or near, live conductors. There are also requirements for persons undertaking work to be competent to prevent danger and injury. Compliance with EWR 1989 is therefore a fundamental requirement for any organization, and it is recommended that organizations have in place a system of training to ensure compliance with the Regulations. Guidance on EWR 1989 is available from the Health & Safety Executive (publication HSR 25 – Memorandum of guidance on the Electricity at Work Regulations 1989). It is recommended that organizations
B
12
Legal Relationship and General Requirements of BS 7671: 2008
purchase this and implement the guidance provided; it contains the text of the Act as well as HSE guidance on how to achieve the statutory requirements. The document details and availability are as follows: HSE’s ‘Memorandum of Guidance on the Electricity at Work Regulations 1989 – HSR 25’ ISBN 9780717662289 (50 pages, available from HSE Books and is referenced HSR25) As well as having a copy of HSR 25, organizations must provide adequate training for all staff that work on or near electrical installations. To supplement this, a dead working policy should ideally be formalized together with a live working policy for those contractors that carry out live work. In respect of the ‘making dead or live’ working aspects of EWR 1989, the following document is also very useful, if not essential. HSG 85 Electricity at Work – Safe Working Practices ISBN 0717621642 This document expands upon detail of policy and procedures for safe working practices for people who work on or near electrical equipment. It includes guidance on the following:
•• •• •
assessing safe working practices; deciding to work dead or live; actions common to both dead and live working; working dead; and working live.
B 1.3
The Electricity Safety, Quality and Continuity Regulations 2002 (as amended) These statutory Regulations are primarily intended for distribution network operators (DNOs), setting statutory limits for voltage and frequency. The Regulations state that PME supplies cannot be used to supply installations supplying caravans or boats. Also, DNOs can take the option not to provide an
13
B
Guide to the Wiring Regulations
earth to installations that they feel are inappropriate. This will possibly be the case on some farms, building sites and petrol filling stations. For all installations, DNOs will have to take a view on the safety of an installation and will use BS 7671: 2008 for this. If the DNO feels that an installation is unsafe, they can refuse to provide a supply or, if connected, disconnect the supply.
B 1.4
The Electricity Act 1984 (as amended) This Act is primarily aimed at distribution network operators and (more recently) meter operators. However, there is a relevant point for installation designers and contractors to note: the Act gives the DNO or meter operator the right to position intakes where they see fit and where they feel appropriate for a given installation.
B 1.5
The Building Act 1984, The Building Regulations and Part P The Building Act 1984 refers only to England and Wales. This book does not cover all the technical requirements relating to the Building Regulations. There are numerous guides and books on this subject including one produced by the ECA and the NICEIC. However, Part P of the Building Regulations, on the subject of electrical safety within dwellings, is summarized in this section. Legal standing of Part P The Building Regulations are made under the main Act of Parliament, the Building Act 1984. The Building Act is the primary legislation and itself refers to the Building Regulations 2000 with its various Parts on structure, means of escape, spread of fire, ventilation, heat loss and, of course, electrical safety. The Building Regulations 2000 are statutory and a breach of the Regulations in itself is an offence under criminal law. As mentioned earlier, statutory instruments such as the Building Regulations must be complied with, otherwise a breach may result in a prosecution. For guidance, and to specify a recognized way of complying with the individual parts of the Building Regulations, the CLG (Communities for Local Government) produces ‘Approved Documents’ on each part of the Building Regulations. It is important to recognize that the Approved Documents themselves are not statutory. This is demonstrated in Figure B 1.1.
B
14
Legal Relationship and General Requirements of BS 7671: 2008
LEGAL STANDING
DOCUMENT Statutory Act
The Building Act 1984
Legal Act
The Statutory Instruments
Statutory Instruments: The Building Regulations 2000 and amendments
Effectively legal
Guidance
Building Regulations Approved Documents
ODPM/ CLG Guidance
Figure B 1.1 Relationship of Building Act, Statutory Instruments and Approved Documents.
The wording of the ‘Statutory Instrument’ and hence the legal requirement of Part P is given in Table B 1.1. Table B 1.1 Statutory Instrument relating to Part P of the Building Regulations. Requirement
Limits on application
PART P ELECTRICAL SAFETY Design, installation, inspection and testing P1 Reasonable provision shall be made in the design, installation, inspection and testing of electrical installations in order to protect persons from fire or injury. Provision of information P2 Sufficient information shall be provided so that persons wishing to operate, maintain or alter an electrical installation can do so with reasonable safety.
The requirements of this Part apply only to electrical installations that are intended to operate at low or extra-low voltage and are in a dwelling; in the common parts of a building serving one or more dwellings, but excluding power supplies to lifts; in a building that receives its electricity from a source located within or shared with a dwelling; and in a garden or in or on land associated with a building where the electricity is from a source located within or shared with a dwelling.
15
B
Guide to the Wiring Regulations
B 1.6
The Electromagnetic Compatibility Regulations 2005 (EMC) Information on EMC and duties under the EMC directive and BS 7671: 2008 are provided in Chapter D section D 4.
B 1.7
Tort and negligence This section is included, not to scare, but to provide information on this ‘common law’ duty. Tort The English legal system recognizes two forms of ‘wrongs’. The first is what we call ‘criminal’ and may be punished by a fine, imprisonment or both. Commonly we think of murder, but this act stemmed from an infringement of society’s moral code, i.e. it was morally wrong to deprive someone of their life. These moral codes were identified and legislated for, initially by the overlords, then monarchs, and ultimately by Parliament. The Health & Safety at Work etc. Act 1974 is Parliamentenacted law and, as such, creates a criminal obligation upon any transgressor. The second is called ‘civil’ or ‘common’ law, colloquially known as ‘judge-made law’ because the rules and principles have been created in the courts of the land, enshrined by what is termed ‘the law of precedent’; that is, unless overturned by a superior court, the ruling establishes the law and binds judges in any subsequent cases. The civil law is concerned with providing restitution of rights, obligations or finances in the event of some form of dispute, termed a breach. Civil law governs both the circumstances where there is an intention to form a relationship, by creation of a legally binding agreement – we call this the law of contract – and where a relationship may exist but where no contract is present, which we call the law of torts. Tort may thus be considered liability where there is no contract. Torts include negligence, nuisance, defamation and trespass, to name but a few. It is possible to owe a duty in both tort and criminal law. However, if an action is successfully pursued in a criminal court, the ‘beyond reasonable doubt’ burden of proof being considerably higher than the civil determination of ‘viewed against the balance of probabilities’, means that the civil liability is taken as having been established. It is the function of the criminal compensation board to establish the level of civil damages due to a ‘common’ infringement of rights, having established a criminal liability.
B
16
Legal Relationship and General Requirements of BS 7671: 2008
In tort there is a need to establish a relationship. The landmark case is Donoghue v Stevenson (1932), wherein a friend of Donoghue purchased for her a bottle of ginger beer, found to contain a partially decomposed snail. Donoghue then successfully established that the manufacturer owed her a ‘duty of care’ under the tort of negligence, and hence was in a relationship, even though ‘she’ had no direct contractual relationship with the manufacturer of her own. This ‘neighbour’ principle is important as it establishes whether a duty of care is owed or not. The question follows: Who is my neighbour? Well, the answer is anyone who it is foreseeable to be likely to be affected by your actions. You can see that liability in tort is therefore very wide, and the rules governing its implementation are extremely complex. Seventy years on, the courts are still grappling with the principles and extent of this law. To some extent this is why ‘collateral warranties’ are called for, because rather than rely on the tort of negligence, parties in a collateral warranty agreement can instead sue for a breach of contract. The level of damages may be similar or higher and it is easier to prove a breach under contract law. We ignore ‘pure economic loss’ and the newly enacted Rights of Third Parties Act. Negligence If you negligently design a system or provide a service, and as a result it causes death or personal injury, or causes damage to other property, then you can be held liable for these losses under the tort of negligence. Making a mistake, or getting something wrong, is not being negligent. Being negligent is where you are found to have performed at a level less than would have been expected by a ‘reasonable man’ whilst undertaking a task, where you had held yourself out as being competent to undertake that task. Thus, if you hold yourself out as being competent to design a lighting system, offer advice concerning that system, and others rely on that advice and install what is subsequently found to be deficient, then irrespective of payment, you may still be held financially liable. It is for this reason that services designers and contractors are strongly advised to insure themselves with professional indemnity insurance.
B 2
The role of Standards Definition of Standards Standards, including international, European and British Standards, are documents to bring about simplification, interchangeability, terminology, methodology, specification or codified practice.
17
B
Guide to the Wiring Regulations
A Standard is defined as: ‘A document established by consumers and approved by a recognized body that provides for common and repeated use, rules, guidelines or characterization for activities or their results, aimed at the achievement of the optimum degree in a given context.’ (This was taken from IEC Guide 2, 1996) Standards are (or should be) written by industry by consensus where consensus is defined as: ‘General agreement, characterized by the absence of sustained opposition or substantial opposition by any important part of the concerned interests and by a process that involves seeking to take into account the views of all parties concerned and to reconcile any conflicting arguments.’ Legal standing of Standards Standards are described or implicated by statute. Standards are voluntary codes of rules, and are not law nor are they legally enforceable. Indeed, individuals may take a view to ignore a particular standard. However, some standards are boosted to an elevated status by being referred to either directly or indirectly in statutes. Depending upon the wording, this can make the standards themselves have a quasilegal status. Again, though, there is a caveat. A good way to explain this further is to look at how BS 7671 is referred to in some legal documents. BS 7671 and the Electricity at Work Regulations 1989 (EWR) It is important to recognize that the wording of the EWR makes no mention of BS 7671. The HSE’s Memorandum of Guidance (HSR 25) states that: ‘BS7671 is a code of practice which is widely recognized and accepted in the UK and compliance with it is likely to achieve compliance with relevant aspects of the 1989 (EWR) Regulations.’ BS 7671: 2001 in Part P of the Building Regulations 2000 In a similar fashion, BS 7671 is not mentioned in the primary legislation, which simply states that ‘the installation shall be designed and installed in order to protect persons from fire or injury’. It is Approved Document P (which itself is guidance) that mentions BS 7671. This states ‘In the Secretary of State’s view, the (Part P) requirements will be met by adherence to the ‘Fundamental Principles’ for achieving safety given in BS
B
18
Legal Relationship and General Requirements of BS 7671: 2008
7671: 2001 Chapter 13’. This will need updating to read correctly for BS 7671: 2008. Standards implied or prescribed by contract Standards are often prescribed by a contract on a definite item (stated) or by a general contract term similar to ‘shall comply with all relevant codes and standards’. Assuming the standard is relevant or if it is listed, then compliance with the Standard becomes binding under the UK law of contract.
B 3
Part 3 of BS 7671: 2008 – assessment of general characteristics Part 3 of BS 7671, totalling only four pages, sets requirements for an overall assessment of an electrical installation. It is intended that the requirements of Part 3 be considered prior to the design of an installation in compliance with other Parts of BS 7671. This works for some of the regulations in Part 3, but some are really repetitive of the general requirements given in Parts 4 or 5. The requirements are summarized in Table B 3.1 in just five paragraphs. The regulation numbers have been omitted here for clarity and due to the fact that the requirements are so general.
Table B 3.1 Requirements of Part 3 of BS 7671: 2008. Requirement of Regulations
Notes and advice
The installation shall be assessed for purpose, external influence, compatibility, maintainability, continuity of service and recognized safety services The characteristics of voltage, current, frequency, prospective fault current, earth fault loop impedance (ELI), maximum demand and protective device at the origin shall be determined
This can be done by inspection, by enquiry, measurement, calculation and applies to all sources of supply. Safety supplies shall be assessed separately and the requirements of these are in Chapter 56 of BS 7671; see Chapter D
Installations shall be suitably divided up to avoid danger, minimize inconvenience in the event of a fault, reduce the possibility of unwanted tripping of RCDs, mitigate the effects of electromagnetic interference, and ensure effective isolation Continuity of supply for the intended use and life of the installation shall be considered
These requirements are discussed with recommendations made in Chapter C
Final circuits shall be connected to separate protective devices at distribution boards Compatibility and EMC shall be considered
See Chapters C and D
19
B
Circuitry and Related Parts of BS 7671: 2008
C
Circuitry and Related Parts of BS 7671: 2008 C 1
Introduction This chapter provides information and guidance on circuitry aspects of BS 7671: 2008 and includes a significant amount of regulations associated with circuits. For example, ‘protection against electric shock’ aspects are included. Like other chapters, the structure is topic led and can be read in page order. The chapter guides you through what you need to design and install circuits to BS 7671: 2008 and applies to significantly large installations. It does not cater for very large or complex installations with, for example, interconnecting busbars, and such complexity is outside the scope of this book. There is a certain amount of overlap with Chapter D, and these two chapters should both be read prior to undertaking design or installation. Lastly, in this chapter, unlike other chapters, there are not numerous references to individual regulation numbers. This is due to the fact that most of the circuitry aspects are covered by relatively few regulations in BS 7671: 2008, the importance of which cannot be overstated. Extensive background knowledge and understanding is required to comply with these regulations and this chapter guides readers through all relevant aspects needed.
21
C
Guide to the Wiring Regulations
C 2
Design procedure overview The procedure of carrying out an electrical system design of an installation can be quite involved and often a number of drafts and subsequent adjustments are necessary. The following flow diagram shows the logical order of steps in the design process.
Identify and quantify loads
Visualise, sketch system and consider physical position of main switchgear, risers etc
Final circuit design using ‘nominal’ parameters for volt drop
Maximum demand
Design and size protection of conductors of sub-mains check discrimination with final circuits if necessary
Design and size protection of conductors of main switchgear and co-ordinate with size of incoming supply
By studying this flow chart it should be obvious that a certain number of iterations with adjustments will be required, as a system is rarely designed without a certain amount of to and fro.
C
22
Circuitry and Related Parts of BS 7671: 2008
The contents of this chapter will need full consideration and, when carrying out a design in practice, adjustments will be necessary at various stages of the process. Discrimination between all upstream and downstream protective devices may be required for convenience or continuity of supply to essential equipment, but this may make the electrical system over-designed (much too large for its designed use) and thus carry a cost burden (see C 6.1). To provide for a cost-effective and efficient design it helps if the main incoming supply point is close to the load centre of the installation, and hence discussions with the electricity distributor should be started at an early stage. It is not essential that the main distribution board(s) are positioned close to the intake point, and their position has an effect on voltage drop on the whole installation including the submain cables. This point of ‘positioning’ is also true of final circuit distribution boards which need to be carefully considered in terms of voltage drop in large installations with highly loaded final circuits. The concept of how to achieve this will become clearer when this chapter has been read.
C 3
Load assessment
C 3.1
Principles and definitions The subject of load assessment often comes down to experience, and there is no substitute for this. Many installations have major identifiable loads. In commercial premises these usually include air-conditioning with chillers, heater banks, compressors and motors of all types as well as lifts, lighting and user ‘final’ equipment loads usually served by socket outlets. A ‘newer’ load is the electrical supply to ‘data storage’ facilities (data centres). Although beyond the scope of this book, data centres require vast amounts of power, but between a large purpose-built data centre and an installation with a few PCs there are installations with small and medium data storage or server rooms. These have notable electrical power and cooling loads, and these loads should be considered.
23
C
Guide to the Wiring Regulations
Interestingly on this subject, whilst traditional loads such as lighting have become more efficient, overall supply demand has increased due to computing and data processing loads. So, how is an installation’s electrical load quantified and estimated? Firstly, it is important to clarify the terms used, as some of these are not defined in BS 7671. Connected load Connected load (or total connected load) is taken to be the sum of all loads in the installation. Care is needed in specifying this load; diversity (See section C3.3) cannot be used but duty cycle (cyclic load) considerations may need to be included. Duty cycle For a device or piece of equipment used intermittently, this is the cycle of starting, operating and stopping. Also included is the time interval that elapses during such a cycle. Alternatively expressed, for a device or piece of equipment used intermittently it is the ratio of its operating time to its rest time, or to total time. Crest factor In a periodically varying function (such as that of a.c.) this is the ratio of the peak amplitude to the RMS amplitude. Some may know this definition as ‘load factor’, and is not the same as duty cycle. Both terms are further explained with the aid of an example. This example would be needed for cyclic loads (533.2.1) evaluation. Consider an installation with two motors of the same type installed in different applications. One motor is used in a supply air fan, the other in a passenger lift application. Both motors have a 20 kW motor with a full load running current of 35 amps and a starting current of 175 A. The lift is in a busy, frequently visited building, particularly busy between 9.00 am and 9.30 am.
C
24
Circuitry and Related Parts of BS 7671: 2008
Current
Key
Fan Motor Lift Motor
175A Starting Current Load Factor = 175 =5 35
100A
35A Running Current
9.00am
9.30am
Time
Figure C 3.1 Starting and running currents of lift motor and fan motor between 9.00 am and 9.30 am.
The duty cycle and crest factor for both motors is shown in Figure C 3.1. Figure C 3.1 shows that both motors have the same crest factor but very different duty cycles. The fan’s duty cycle can be taken as unity (1) and its starting current ignored in terms of heating effect on the supply switchgear and cables. The starting
25
C
Guide to the Wiring Regulations
current of the lift motor, however, needs consideration, as there are 15 starting occasions in 30 min. If the starting time was 30 s, the duty cycle would be 0.5 × 15 = 0.25 30 indicating that the motor was in starting mode for 25% of its time. From this information, the heating effect of the duty cycle can be calculated using the fact that the heating effect is proportional to I 2Rt. Thus, the equivalent continuous current is Iequivalent = √i12R1t1 + i22R2t2 = √352 × 0.75 + 1752 × 0.25 = 93 A
This result demonstrates the significance of duty cycle of the cyclic lift motor load compared with the steady load of the fan. The lift motor supply would need to be rated at 100 A, and the fan motor supply at 50 A (for the lift motor running current of 35 A). It should be noted that in practice the lift motor starting current will not be on for 30 s, this figure being exaggerated to emphasize the point. Maximum demand Maximum demand (or maximum power demand) is the highest rate at which power is consumed. Alternatively expressed, it is the highest average rate at which electrical power is consumed. In calculating the maximum demand in an installation, diversity can be applied (311.1). To apply these definitions to an installation still requires appropriate experience and usually a lack of such experience leads to an overdesigned electrical distribution system. The author has attended many installations with 500% or greater overcapacity with all the client’s equipment connected and running.
C 3.2
Maximum demand assessment Maximum demand is sometimes expressed as: maximum demand (kVA) = connected load × diversity Diversity is discussed in section C 3.3.
C
26
Circuitry and Related Parts of BS 7671: 2008
There are two methods for calculating maximum demand, as follows:
• •
A summation of individual connected loads with application of diversity factors. Comparison with table of ‘norms’ for similar installations.
In practice, a combination of these two methods is often utilized. For example, major plant loads are calculated with duty cycle and diversity applied and this is added to the ‘norm’ watts per square metre for general areas of the installation. For assessment by adding individual loads there are nearly always differences between the rated power expressed by the manufacturer, and the actual currents drawn. This can be true despite checking catalogues and data sheets as well as rating plates and this contributes to overdesign. More often than not, actual connected loads are 50–70% of the quoted value. The watts per square metre method can be used to produce an overall maximum demand estimate, alongside information on known loads, or it can be used solely to produce an estimate. The watts per square metre method involves comparing the installation type and size with a watts per square metre ‘normal’ table. Good in theory, but where does the table come from? There have been limited central studies of this type of ‘norm’ in the UK, although consulting design firms and larger contractors collect their own data. CIBSE (the Chartered Institution of Building Services Engineers) does publish a certain amount of such data in its journal, but this information is connected load and not actual running load. BSRIA (www.bsria.co.uk) also publishes some guidance on this subject. Table C 3.1 provides an assessment of load and would equate to the maximum demand estimate. The table can be used for generic designs while noting that it is an ‘average-norm’ table, and if you have significant loads not found in the average office the table will be inaccurate. Medium-sized data centres are excluded from this table.
27
C
Guide to the Wiring Regulations Table C 3.1 Typical load assessment for commercial offices.
C 3.3
Office size
Load no air-conditioning (W/m2)
Load with air-conditioning (W/m2)
Small office Up to 2000 m2
70
120
Medium office 2000 m2 to 10 000 m2
60
110
Large office Over 10 000 m2
55
100
Diversity 311.1 Diversity should be taken into account when assessing the maximum demand of an installation (311.1). Diversity is the engineering principle that in any given installation, some of the connected loads will not be running at the same time instant as other loads. This principle can be further broken down into two types of load as follows: A Loads that, due to the law of averages, will not be on at the same time. B Loads that, due to fact, will not be on at the same time. Examples of type A include instantaneous electric showers in a multiple block of flats, lift supplies in general and motors for building services. Examples of type B include electrical heating loads and electrical cooling loads; obviously, while it is possible to run both together, the fact is that they do not. There are many examples of both types of load. In attempting to make an assessment of diversity, there is no substitute for knowledge and experience. The extent of knowledge and experience needed must match the type of installation being assessed. It should be recognized that diversity can be applied in a number of ways as follows:
•• ••
for items on a final circuit (except socket outlets); between similar final circuits, i.e. assume one circuit is 100%, the other 0% or x%; between sub-distribution boards or submain cables; and at each main distribution board.
C
28
Circuitry and Related Parts of BS 7671: 2008
Table C 3.2 indicates some suggested diversity factors for average circumstances and can only be used by those with suitable experience and knowledge of the type of installation being assessed. It should also be noted that many engineers, technicians and electricians are inclined to significantly overestimate loadings – perhaps to play safe – and this leads to an overdesigned electrical system. It is more skilful to produce an ample design with capacity built-in, but which is not grossly overdesigned. An interesting point to note here is the supply utility’s figures for domestic supplies; they use a figure for domestic maximum demand of about 2 kW as an average consumer load. This figure says much about diversity when applied correctly. It should be noted that Table C 3.2 may differ from other published data on the subject; it is felt that Table C 3.2 is realistic, subject to the constraints given above on experience. Table C 3.2 Some suggested diversity factors. Item
Diversity factor
Notes
Lighting in small office and similar, up to 2000 m2
0.7
0.6 with daylight control
Lighting in medium office and similar, 2000 m2 to 10 000 m2
0.8
0.7 with daylight control
Lighting in large office and similar, over 10 000 m2
0.85
0.7 with daylight control
Retail store lighting
0.9
Space heating in small office and similar, up to 2000 m2
0.8
Capacity of system and 24 hour cycle to be considered for thermal capacity; adjust as necessary
Space heating in medium office and similar, 2000 m2 to 10 000 m2
0.7
Capacity of system and 24 hour cycle to be considered for thermal capacity; adjust as necessary
Space heating in large office and similar, over 10 000 m2
0.6
Capacity of system and 24 hour cycle to be considered for thermal capacity; adjust as necessary
Socket outlets – all commercial general purpose office, all sizes
Use W/m2
More appropriate to use the overall table figures in Table C 3.1
29
C
Guide to the Wiring Regulations
C 4
Circuit design
C 4.1
Introduction This section explains how to carry out cable sizing manually. Modern cable sizing software programs can be quite sophisticated and, for most projects, save considerable time. However, as engineers you must know if the inputs you are making, as well as the outputs that you are receiving, are correct. In this section, the design procedure common to all circuits is considered. With reference to BS 7671, there are four separate subject areas that will determine the cable size as follows:
Thermal Capacity under fault 43
Overload 43
Cable Size
Voltage Drop 525
Disconnection Time 41
These factors are considered and discussed in this chapter. Readers should note that ultimately only one of these factors will, at any point and for a particular circumstance, determine the cable size. Experience and some rules of thumb given in this chapter may, for example, lead you to carry out a voltage drop check in preference to one of the other sizing factors. In order to visualize the cable sizing process, Figure C 4.1 provides a flow chart of the process showing the order of stages.
C
30
Circuitry and Related Parts of BS 7671: 2008
KEY Select cable type and installation method
Book Reference Stage
D5
Is overload protection required
C1
C 4.3.4
Yes
Establish Ca
Check Voltage drop
C 4.3.5
C4.5
Calculate design current Ib
C 4.3.2
Select protective device rating
C 4.3.1
Establish Cg
C 4.3.4
Calculate It
C 4.3.3
Check size for short circuit
Establish Ci & Cf where applicable C 4.3.5
C4.4
Check size for disconnection times
C4.6
FINAL CABLE SIZE
Figure C 4.1  Cable sizing stage diagram.
31
C
Guide to the Wiring Regulations
C 4.2
Protection against overcurrent in general Protection against overcurrent as defined in BS 7671: 2008 includes overload and fault currents: Overcurrent 43
Overload 433
Faults 434
Overcurrent in a sound circuit
Current in an abnormal or unintended path
It should be noted that an earth fault current in terms of BS 7671: 2008 is simply known as a fault current; but this can cause confusion, and the term earth fault current is used in this book. The earth fault current requirements specified in Chapter 54 of BS 7671 are in essence the same as the short circuit requirements specified in Chapter 43, and aspects of protective conductor sizing are therefore included in this part of the book.
C 4.3
Overload protection C 4.3.1 Fundamentals There are circumstances where overload protection is not required – usually where the continuity of the supply is critical compared with the implications of not providing overload protection. These are discussed later. For most circuits overload protection is required, and this protection should become second nature to installation engineers. A basic requirement given in 433.1 is that circuits should be arranged so that small overloads for long durations are ‘unlikely to occur’. What is meant by small overloads are those that will not be detected by the protective device. For MCBs this would be somewhere between 1 and 1.45 of the rated current of the device (see D 6.2).
C
32
Circuitry and Related Parts of BS 7671: 2008
Problems arising from not complying with this regulation are rare (cables are usually oversized) and only an error in obtaining an accurate current rating would cause difficulties. Another fundamental requirement of 433.1.1 is that: Ib ≤ In ≤ Iz where Ib is the design current of the circuit, In is the nominal current or current setting of the protective device, Iz is the current-carrying capacity of the conductor in the particular installation conditions. Pictorially represented this requirement is as follows:
In e.g. 32A
Ib
Iz e.g. 36A
Protective Device
e.g. 28A
Load
cable
Devices will operate if the current exceeds the fusing or tripping current I2 for a time greater than the conventional fusing or tripping time. Fusing, non-fusing and conventional times are given for common devices in Table C 4.1.
Table C 4.1 Fusing and non-fusing currents and conventional fusing times. Device type
Rated current In (A)
Non-fusing or nontripping current I1 (A)
Fusing or tripping current I2 (A)
Conventional fusing or tripping time (h)
MCBs to BS EN 60898
≤ 63 ≥ 63
1.13 In 1.13 In
1.45 In 1.45 In
1 2
BS 88 fuse
<16 16 < In ≤ 63 63 < In ≤ 160 160 ≤ In ≤ 400 400 < In
1.25 In for 1 h 1.25 In for 1 h 1.25 In for 2 h 1.25 In for 3 h 1.25 In for 4 h
1.6 In 1.6 In 1.6 In 1.6 In 1.6 In
1 1 2 3 4
BS 1361
5 < In ≤ 45 60 < In ≤ 100
1.5 In 1.5 In
4 4
33
C
Guide to the Wiring Regulations
Overcurrent devices will not operate if the overcurrent is of short duration (except for circuit breakers where the overcurrent exceeds the instantaneous operating current). C 4.3.2 Design current Ib In order to determine a correct individual cable size it is important to obtain or calculate an accurate circuit design current. This may not be critical for short or lightly loaded circuits, but becomes critical when sizing heavily loaded circuits with long cable runs of, say, over 75 m. At longer circuit lengths, voltage drop requirements can lead to cable sizes significantly larger than the base size. In order to minimize this in calculations, an accurate design current Ib can be key in ensuring a good design. The basic formulae to apply to obtain a design current are as follows: Single-phase equipment, I = Three-phase, I1 =
kW × 1000 (amps), V × pf
kW × 1000 (amps), √3 V1 × pf
where: V is the nominal phase voltage to earth, also denoted by U0 Vl is the line voltage, also denoted by U pf is the power factor Il is the line current in a three-phase system. C 4.3.3 Installed cable sizing While carrying out cable sizing to BS 7671, or indeed for cable sizing in general, it helps to bear in mind the following principles:
••
An insulated cable size is only limited by its type of insulation. For a given insulation, the rating depends upon both load current and the rate of heat dissipated by the cable to its immediate environment.
The basic sizing principle is as follows:
C
34
Circuitry and Related Parts of BS 7671: 2008
First select an appropriate protective rating, larger than the design current (step 1). Next the initial, tabulated cable size (It) is obtained by using the protective device rating and correcting for ambient temperature, grouping factor and, where applicable, correction factors for thermal insulation and rewirable fuses (step 2). It =
In Ca Cg Ci Cc
(Equation 1)
where: It is the tabulated current-carrying capacity from Appendix 4 of BS 7671 C denotes a correction factor as follows: Ca is ambient temperature; see Appendix C Table 4B1 (cables in air) or 4B2/4B3 (cables in ground) Cg is grouping; see Appendix C Table 4C1 to 4C5 Ci is for conductors totally surrounded by thermal insulation. Although not given in Appendix 4 this factor is 0.5 (523.6.6). It should be noted that some 17th Edition tables include a certain amount of thermal insulation and where these are used no further correction should be made. For example, new Table 4D5, included due to ECA suggestion, includes thermal insulation for cables in loft-roof spaces, and the Ci correction should not be used as it is already in the It value. Cc is for semi-enclosed fuses to BS 3036. A cable with tabulated current-carrying capacity (Iz) is then selected such to exceed the It (step 3). The procedure can be depicted as in Figure C 4.2.
35
C
Guide to the Wiring Regulations
Step 1- select In Ib Protective Device
In e.g.32A Step 2 It
In Ca Cg Ci Cc e.g.36A
Ib
e.g. 28A
Iz e.g.36A Step 3 Iz from cable data Iz It
Figure C 4.2â&#x20AC;&#x201A; Diagram of conductor size design method.
Current rating tables for some common cables are found in Appendix 2 of this guide. Correction factors are discussed in sections C 4.3.4 and C 4.3.5. On completion of obtaining an installed current rating for the relevant cable size, it is then further checked for voltage drop, thermal withstand under fault conditions and size for earth fault loop impedance. These are discussed later in the chapter. As the factors for thermal insulation and fusing (semi-enclosed) are not used all that often, Equation 1 becomes: It =
In Ca Cg
(Equation 2)
The various correction factors are now discussed. C 4.3.4 Grouping factors Firstly, caution has to be exercised when applying grouping factors; very large cable sizes can result unless careful consideration of realistic design currents is made before a grouping factor is applied.
C
36
Circuitry and Related Parts of BS 7671: 2008
BS 7671: 2008 Appendix 4 includes revised information for grouping factors calculations. A new table of grouping factors for buried cables has been added (Table 4C2 reproduced below). Also new is a method for calculating the grouping factor for circuits where cables are of different sizes, as follows: F=
1 √n
where F is the group rating factor and n is the number of circuits. This formula will give a lower group factor than BS 7671 Tables 4C1 to 4C5 as these tables assume that cables in the group are of the same size. An overriding point to note before the grouping factor tables are given is the note 523.5 in BS 7671, which states that where a cable is known to carry 30% or less of its grouped rating, it can be ignored for the purposes of grouping. This is invaluable and should be utilized for BS 7671: 2008 calculations. The procedure for applying grouping factors is either to use the factor from BS 7671 Tables 4C1 to 4C2 or to use the following method: Compare the formula:
√
It = In2 + 0.48Ib2
( 1 C– C ) 2
2
g
g
(Equation 3)
with It =
Ib Cg
(Equation 4)
using the larger value. This method can only be used where the circuits within a group are not expected to be simultaneously overloaded. For circuits that are not fully loaded, the use of this (Equation 3) method produces a lower It than the grouping factor method using tables 4C1 to 4C5 from BS 7671. The procedures are summarized as:
37
C
Guide to the Wiring Regulations
1.0 Cg=0.9
0.9
Cg=0.8
0.8
Cg=0.7
0.7 Correction Factor to be applied to In Ca Cg
Cg=0.6
0.6
Cg=0.5
0.5
Cg=0.4
0.4
Cg=0.3
0.3
No Correction Factor possible
Cg=0.2
0.2
Cg=0.1
0.1 0 0
0.1
0.2
0.3
0.4
0.5 Ib In
0.6
0.7
0.8
0.9
1.0
Figure C 4.3 Reduction formula for circuits not fully loaded. Source: adapted from Electrical Installation Calculations, Third Edition, ECA 2002.
• •
if a quick sizing method is required, use BS 7671 Tables 4C1 to 4C5 and equations 2 or 3 and do no more; or calculate It using Equations 3 and 4, using the larger It value.
As both Cg and Ib/In are both known, to make life even easier and to save application of the second bullet point above, which can be tiresome, the ‘look-up’ table in Figure C 4.3 can be used instead and applied to Equations 1 or 2 (but not where the protective device is a semi-enclosed fuse). The following tables of grouping factors are reproduced from BS 7671: 2008.
C
38
Circuitry and Related Parts of BS 7671: 2008
Table 4C1â&#x20AC;&#x201A; Rating factors for one circuit or one multicore cable or for a group of circuits, or a group of multicore cables, to be used with current-carrying capacities of Tables 4D1A to 4J4A Arrangement (cables touching)
Number of circuits or multicore cables 1
2
3
4
5
6
7
8
9
12
16
20
To be used with current-carrying capacities, reference
Bunched in air, on a surface, embedded or enclosed
1.00
0.80
0.70
0.65
0.60
0.57
0.54
0.52
0.50
0.45
0.41
0.38
Methods A to F
Single layer on wall or floor
1.00
0.85
0.79
0.75
0.73
0.72
0.72
0.71
0.70
0.70
0.70
0.70
Method C
Single layer multicore on a perforated horizontal or vertical cable tray systems
1.00
0.88
0.82
0.77
0.75
0.73
0.73
0.72
0.72
0.72
0.72
0.72
Methods E and F
Single layer multicore on cable ladder systems or cleats, etc.
1.00
0.87
0.82
0.80
0.80
0.79
0.79
0.78
0.78
0.78
0.78
0.78
NOTE 1: These factors are applicable to uniform groups of cables, equally loaded. NOTE 2: Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no rating factor need be applied. NOTE 3: The same factors are applied to: - groups of two or three single-core cables; - multicore cables. NOTE 4: If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and the corresponding factor is applied to the tables for two loaded conductors for the two-core cables, and to the tables for three loaded conductors for the three-core cables. NOTE 5: If a group consists of n single-core cables it may either be considered as n/2 circuits of two loaded conductors or n/3 circuits of three loaded conductors. NOTE 6: The values given have been averaged over the range of conductor sizes and types of installation included in Tables 4D1A to 4J4A; the overall accuracy of tabulated values is within 5%. NOTE 7: For some installations and for other methods not provided for in the above table, it may be appropriate to use factors calculated for specific cases; see for example Tables 4C4 and 4C5. NOTE 8: When cables having differing conductor operating temperature are grouped together, the current rating is to be based upon the lowest operating temperature of any cable in the group. NOTE 9: If, due to known operating conditions, a cable is expected to carry not more than 30% of its grouped rating, it may be ignored for the purpose of obtaining the rating factor for the rest of the group. For example, a group of N loaded cables would normally require a group reduction factor of Cg applied to the tabulated It. However, if M cables in the group carry loads which are not greater than 0.3 CgIt amperes the other cables can be sized by using the group rating factor corresponding to (Nâ&#x20AC;&#x2018;M) cables.
39
C
Guide to the Wiring Regulations
Table 4C2 Rating factors for more than one circuit, cables laid directly in the ground – Reference Method D in Tables 4D1A to 4J4A single-core or multicore cables Number of circuits
Cable to cable clearance (α) Nil (cables touching)
One cable diameter
0.125 m
0.25 m
0.5 m
2
0.75
0.80
0.85
0.90
0.90
3
0.65
0.70
0.75
0.80
0.85
4
0.60
0.60
0.70
0.75
0.80
5
0.55
0.55
0.65
0.70
0.80
6
0.50
0.55
0.60
0.70
0.80
Multicore cables
Į Į
Į Į
Single-core cables
Į Į
Į Į
NOTE 1: Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 K.m/W. These are average values for the range of cable sizes and types quoted for Tables 4D1A to 4J4A. The process of averaging, together with rounding off, can result in some cases in errors of up to ±10%. (Where more precise values are required they may be calculated by methods given in BS 7769 (BS IEC 60287).) NOTE 2: In case of a thermal resistivity lower than 2.5 K.m/W the correction factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).
C
40
Circuitry and Related Parts of BS 7671: 2008
Table 4C3 Rating factors for more than one circuit, cables laid in ducts in the ground – Reference Method D in Tables 4D1A to 4J4A (i) Multicore cables in single-way ducts Number of cables
Duct to duct clearance (α) Nil (ducts touching)
0.25 m
0.5 m
1.0 m
2
0.85
0.90
0.95
0.95
3
0.75
0.85
0.90
0.95
4
0.70
0.80
0.85
0.90
5
0.65
0.80
0.85
0.90
6
0.60
0.80
0.80
0.90
Multicore cables
Į
Į
NOTE 1: Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 K.m/W. They are average values for the range of cable sizes and types quoted for Tables 4D1A to 4J4A. The process of averaging, together with rounding off, can result in some cases in errors of up to ±10%. (Where more precise values are required they may be calculated by methods given in BS 7769 (BS IEC 60287).) NOTE 2: In case of a thermal resistivity lower than 2.5 K.m/W the correction factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287). (ii) Single-core cables in non-ferrous single-way ducts Number of cables
Duct to duct clearance (α) Nil (ducts touching)
0.25 m
0.5 m
1.0 m
2
0.80
0.90
0.90
0.95
3
0.70
0.80
0.85
0.90
4
0.65
0.75
0.80
0.90
5
0.60
0.70
0.80
0.90
6
0.60
0.70
0.80
0.90
Single-core cables
Į
Į
NOTE 1: Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 K.m/W. Į and types quoted for Tables 4D1A to They Įare average values for the range of cable sizes 4J4A. The process of averaging, together with rounding off, can result in some cases in errors of up to ±10%. (Where more precise values are required they may be calculated by methods given in BS 7769 (BS IEC 60287).) NOTE 2: In case of a thermal resistivity lower than 2.5 K.m/W the correction factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).
41
C
Guide to the Wiring Regulations
Table 4C4 Rating factors for groups of more than one multicore cable, to be applied to reference currentcarrying capacities for multicore cables in free air – Reference Method E in Tables 4D1A to 4J4A Installation method in Table 4A2
Number Number of cables per tray or ladder of trays 2 3 4 6 9 or ladders 1
Perforated cable tray systems (Note 3)
1 2 3 6
1.00 1.00 1.00
See item 4 of Table 4C1 0.87 0.80 0.77 0.73 0.86 0.79 0.76 0.71 0.84 0.77 0.73 0.68
0.68 0.66 0.64
1 2 3
1.00 1.00 1.00
1.00 0.99 0.98
— — —
1 2
1.00
See item 4 of Table 4C1 0.88 0.81 0.76 0.71
0.70
1 2
1.00 1.00
0.91 0.91
0.89 0.88
0.88 0.87
0.87 0.85
— —
1 2 3 6
0.97 0.97 0.97 0.97
0.84 0.83 0.82 0.81
0.78 0.76 0.75 0.73
0.75 0.72 0.71 0.69
0.71 0.68 0.66 0.63
0.68 0.63 0.61 0.58
31
Touching
300 mm 20 mm 300 mm 20 mm 300 mm 20 mm 300 mm Spaced 20 mm 300 mm 20 mm De De
De De
Vertical perforated cable tray systems (Note 4)
31
0.98 0.96 0.95
0.95 0.92 0.91
0.91 0.87 0.85
De
20 mm 20 mm 20 mm 20 mm Touching 20 mm 225 mm 225 mm 225 mm 225 mm 225 mm
Spaced
225 mm De 225 mm De 225 mm De 225 mm 225 mm
Unperforated cable tray systems
30
De De
Touching
300 mm 20 mm 300 mm 20 mm 300 mm 20 mm 300 mm 20 mm 300 mm 20 mm (Continued.)
C
42
20 mm 20 mm 300 mm 300 mm 20 mm 20 mm 300 mm 20 mm 300 mm 300 mm De De De De De
De De
225 mm 225 mm
Circuitry and Related Parts of BS 7671: 2008
Table 4C4 (Continued.) Installation method in Table 4A2
300300 mmmm
20 mm 20 mm Cable ladder systems, cleats, wire mesh tray, etc. (Note 3)
32 33 34
Touching
20 mm 20 mm
Number Number of cables per tray or ladder of trays 2 3 4 6 9 or ladders 1 1 2 3 6
1.00 1.00 1.00
See item 4 of Table 4C1 0.86 0.80 0.78 0.76 0.85 0.79 0.76 0.73 0.84 0.77 0.73 0.68
0.73 0.70 0.64
1 2 3
1.00 1.00 1.00
1.00 0.99 0.98
— — —
300300 mmmm
Spaced
De De
1.00 0.98 0.97
1.00 0.97 0.96
1.00 0.96 0.93
20 mm 20 mm NOTE 1: Values given are averages for the cable types and range of conductor sizes considered in Tables 4D1A to 4J4A. The spread of values is generally less than 5%. NOTE 2: Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other. Values for such installations may be significantly lower and must be determined by an appropriate method. NOTE 3: Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the factors should be reduced. NOTE 4: Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back to back. For closer spacing the factors should be reduced.
Table 4C5 Rating factors for groups of one or more circuits of single-core cables to be applied to reference currentcarrying capacity for one circuit of single-core cables in free air – Reference Method F in Tables 4D1A to 4J4A Installation method in Table 4A2
Perforated cable tray systems (Note 3)
31
Touching
Number of trays or ladders
Number of threephase circuits per tray or ladder
Use as a multiplier to rating for
1
2
3
1 2 3
0.98 0.96 0.95
0.91 0.87 0.85
0.87 0.81 0.78
Three cables in horizontal formation
1 2
0.96 0.95
0.86 0.84
— —
Three cables in vertical formation
300 mm 300 mm 20 mm20 mm Vertical perforated cable tray systems (Note 4)
31
Touching
225 mm 225 mm
(Continued.)
43
C
300mm mm 300 300 300mm mm
Guide to the Wiring Regulations 20mm mm 20 2020 mm mm
Table 4C5 (Continued.) Installation method in Table 4A2
Number of trays or ladders
225 mm 225 mm 225 mm 225 mm
Cable ladder systems, cleats, wire mesh tray, etc. (Note 3)
Perforated cable tray systems (Note 3)
32 33 34
Touching
Number of threephase circuits per tray or ladder
Use as a multiplier to rating for
1
2
3
1 2 3
1.00 0.98 0.97
0.97 0.93 0.90
0.96 0.89 0.86
Three cables in horizontal formation
1 2 3
1.00 0.97 0.96
0.98 0.93 0.92
0.96 0.89 0.86
Three cables in trefoil formation
1 2
1.00 1.00
0.91 0.90
0.89 0.86
1 2 3
1.00 0.97 0.96
1.00 0.95 0.94
1.00 0.93 0.90
300mm mm 300 300 300mm mm
31
20mm mm 20 2020 mm mm 2De 2D e 2D e e DD e 2D Dee De 300mm mm 300 300 300mm mm 20mm mm 20 2020 mm mm
Vertical perforated cable tray systems (Note 4)
Cable ladder systems, cleats, wire mesh tray, etc. (Note 3)
31
Spaced 2De 2D ee 2D2D e
225mm mm 225 225 mm 225 mm
32 33 34
2De 2D ee 2D 2D e
DDD eee De
e DDD eD ee
300mm mm 300 300 300mm mm 20mm mm 20 2020 mm mm
NOTE 1: Values given are averages for the cable types and range of conductor sizes considered in Tables 4D1A to 4J4A. The spread of values is generally less than 5%. NOTE 2: Factors apply to single layer groups of cables (or trefoil groups) as shown above and do not apply when cables are installed in more than one layer touching each other. Values for such installations may be significantly lower and must be determined by an appropriate method. NOTE 3: Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the factors should be reduced. NOTE 4: Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back to back. For closer spacing the factors should be reduced. NOTE 5: For circuits having more than one cable in parallel per phase, each three-phase set of conductors is to be considered as a circuit for the purpose of this table.
C
44
Circuitry and Related Parts of BS 7671: 2008
4.3.5 Other correction factors As well as grouping factors, correction factors for ambient temperature (Ca), total surround by thermal insulation factor (Ci ) and semi-enclosed fuse factor (Cc ), which is 0.725) need to be used where appropriate. Ambient temperature Ca This is a factor for ambient temperature of the installation where the cables are run. The tabulated cable current ratings in Appendix 4 of BS 7671 are based upon a 30°C ambient temperature for general cables and 20°C around ambient temperature for cables buried in the ground. Tables 4B1 and 4B2 of Appendix 4 of BS 7671 give the relevant factors to be used, including the new correction factors for cables buried in the ground. Where there are mixed installation temperatures in a cable length it is best to use the higher temperature (alternatively, larger cables can be installed for that portion). Thermal insulation Ci A careful application of this factor is required, as many of the cable rating tables (4D to 4F) already allow for some thermal insulation. This factor (Ci = 0.5) is to be used where an appropriate cable installation method is not available (533.6.6). It must be applied to the ‘in free air’ rating of the cable type. Semi-enclosed fuse factor Cc This factor, equal to 0.725, should be used where the protective device is a semienclosed (rewirable) fuse. C 4.3.6 Omission of overload protection There are examples of circuits or equipment where it is recognized by BS 7671 that overload protection is not required or perhaps not desired. The first of these is not utilized as much as it could be, and is for circuits with loads not likely to cause an overload (433.3.1). An example would be a circuit supplying a fixed water heater, but this regulation applies to many fixed loads. Fault current protection is still a requirement and must be provided. The other category of loads for which overload protection need not be provided is where disconnection could cause danger, such as sprinkler pump supplies, lifting electromagnets, safety supplies in general (may not apply to all of them) and others. It is noted that supply cut-out fuses are allowed to be utilized for overload protection of the main supply cables (433.3.1).
45
C
Guide to the Wiring Regulations
C 4.4
Fault protection C 4.4.1 General and omissions BS 7671 has new terminology for fault protection. Fault currents now include all faults, i.e. those between live conductors as well as earth faults. The term ‘short circuit current’ is not used within Section 434 although it still appears in part 2 – definitions (it was used in the 16th Edition). There are two aspects of protection against fault currents: the protection of the cables, covered in this part, and the protection of and selection of equipment (fault rating), which is dealt with in Chapter D. C 4.4.2 Fault protection requirements For protection against short circuit, the overcurrent device must be able to:
••
withstand the short circuit current (device breaking capacity); and disconnect sufficiently quickly to prevent damage to the cables.
The fault currents to be considered include faults between line conductors and earth, line conductor and neutral, and line-to-line conductors. The highest fault currents will arise with three-phase line conductors shorting together and to earth. The BS 7671 requirements for fault protection are summarized in Table C 4.2.
Table C 4.2 Fault protection requirements. Requirement
Regulation number
Fault current shall be determined at every position
434.1
Devices capable of withstanding fault levels
434.5.1
Disconnection times are to protect heat rise in cables1
434.5.2
Separate overload and fault devices to be co-ordinated
435.2
Note 1: Perhaps one of the most significant regulations here is in relation to achieving compliance with 434.5.2, which states that if overload protection (Ib ≤ In ≤ Iz) is achieved then this will provide fault protection (435.1).
C
46
Circuitry and Related Parts of BS 7671: 2008
C 4.4.3 Determination of fault current The Regulations (434.1) require that the fault current be determined at every relevant point. For small and medium installations with LV utility supplies, this is satisfied by determination of the fault currents at the incomer. The DNO will supply this information and usually quote a maximum fault current of 16 kA. This is a theoretical maximum that is rarely found in practice. This level of fault will mean that MCBs (60898 devices, see Chapter D) will need to be rated at 16 kA. Whilst it is possible to purchase 16 kA devices, they are usually double width and often more expensive than the 3, 6, 9 or 10 kA devices. A solution here is to measure the incoming fault currents or loop impedances, and use these values. For installations with private transformers, calculations are required, and this is outside the scope of this book. Generally, fault levels of 15–20 kA exist in the close vicinity of main switchgear, and a careful consideration of MCB fault rating must be made for local distribution boards. C 4.4.4 Fault capacity of devices Table C 4.3 summarizes fault capacities of relevant devices. For most domestic installations the prospective fault current is unlikely to exceed 6 kA, up to which value the Icn and Ics values are the same. The short-circuit capacity of devices to BS EN 60947–2 is specified by the individual manufacturer. C 4.4.5 Circuits without overload protection Where the overcurrent device does not provide overload protection, the cable size must be checked for short-circuit (thermal) withstand. This confirms that the circuit energy let through by the protective device does not cause a damaging heat rise in the cable. The calculation uses the ‘adiabatic’ equation given in Regulation 434.5.2 as follows: t=
k 2S 2 I 2
(Equation 5)
where: t is the duration in seconds S is the cross-sectional area of conductor in mm2
47
C
Guide to the Wiring Regulations
Table C 4.3 Fault ratings of common devices. Device type
Fault current capacity (kA)
Circuit-breakers to BS EN 60898 and BS EN 61009 1
1
Icn Ics 1.5 (1.5) 3.0 (3.0) 4.5 (4.5) 6 (6.0) (7.5) 16
Circuit-breakers to BS EN 60947–2
Varies, specified by manufacturer
Cartridge fuse to BS 1361 type I Type II
16.5 33.0
General purpose fuse to BS 88 Part 2.1 Part 6
50 at 400 V 16.5 at 230 V 80.0 at 400 V
Semi-enclosed fuse to BS 3036 with category of duty
S1A-1 S2A-2 S4A-4
Circuit-breakers to BS 3871
M1–1 M1.5–1.5 M3–3 M4.5–4.5 M6–6 M9–9
Note 1: Two rated short-circuit ratings are defined in BS EN 60898 and BS EN 61009: Icn is the rated short-circuit capacity (marked on the device), Ics is the service short-circuit capacity. The difference between the two is the condition of the circuit breaker after manufacturer’s testing. Icn is the maximum fault current the breaker can interrupt safely, although the breaker may no longer be usable. Ics is the maximum fault current the breaker can interrupt safely without loss of performance. The Icn value is normally marked on the device in a rectangle, e.g. 6000 For the majority of applications the prospective fault current at the terminals of the circuit-breaker should not exceed this value.
I is the effective short-circuit current in amperes, due account being taken of the current limiting effect of the circuit impedances k is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures. It should be noted that in this application of Equation 5, the disconnection time should not be taken as 5 s, but is taken from the time-current characteristic for the
C
48
Circuitry and Related Parts of BS 7671: 2008
Table C 4.4 k values for use in adiabatic equation. 70° PVC
90° XLPE
MICC
(thermoplastic)
(thermosetting)
Served
Bare
Copper conductor
k = 115
k = 100
k = 115
k = 115
Aluminium conductor
k = 76
k = 66
N/A
N/A
protective device. Alternatively, some manufacturers provide I 2t values that can be used. For copper and aluminium cables up to 300 mm2, k is given in Table C 4.4; the full list for other materials is found in the Regulations. The adiabatic equation (Equation 5) can be used to find a tripping time that will not overheat the cable being used. It is then compared with the actual tripping time for the protective device at the fault current level found in the device time/current curves. This can be a little confusing and it can be easier to calculate the minimum size required using a transposed adiabatic equation as follows: S=
I √t , noting that S comes out in mm2. k
It should be noted that where the initial cable size has been adjusted following a thermal withstand check, further iterations may be necessary as the new size itself affects the prospective fault current. It is worth noting that the factors in Table 43.1 of BS 7671 are based on the circuit conductor running at its maximum operating temperature. Designers should take account of this when the adiabatic calculation yields a cable size ‘just over’ a standard available size. It is suggested that where this is in the order of 5% to 10%, the smaller size be used.
C 4.5
Voltage drop C 4.5.1 7671 requirements Section 525 of BS 7671: 2008 contains four regulations specifying that the voltage at the terminals of equipment is:
••
suitable for that specified in the equipment product standard; or for equipment without a standard, suitable for safe functioning.
49
C
Guide to the Wiring Regulations
Table C 4.5 Appendix12 voltage drop specification. Type of supply
Voltage drop lighting
Voltage drop other
From DNO
3%
5%
Private supply
6%
8%
A new Appendix (12) is included in BS7671: 2008 for consumers’ installations which, if followed, is ‘deemed to comply’ with voltage drop design requirements of the Regulations. This is summarized in Table C 4.5. It is recognized in the body of Section 525 and Appendix 12 that high inrush currents may cause higher voltage drop levels, and reference to equipment product standards is made. In essence this does not change the basic requirement that equipment must work! C 4.5.2 System design values For domestic installations, voltage drop is quite simple and rarely needs a design or further consideration. In commercial and industrial installations, voltage drop design will depend upon the nature of the supply. If the supply is to the Electricity Safety, Quality and Continuity Regulations 2002, the supply voltage can vary between statutory limits of +10% to –6%. As such, the voltage drops in Table C 4.5 are recommended with the caveat that voltage can be lower if the equipment standard allows. For private transformers the subject is more complicated, as the voltage regulation of the transformer is now under the control of you, the designer. The secondary terminal voltage of the transformer will largely depend upon the magnitude of the total load at any instant. Generally it is good practice to simulate the values of statutory voltage limits found in the Electricity, Safety, Quality and Continuity Regulations. The current limits are nominal voltage +10% to –6%. Thus for a large installation, a system of main and sub voltage drops may be required to be set, to achieve a ‘system’ design. A simple system view of this is given in Figure C 4.4. A guide to installation voltage drop limits is 6% with an 8% maximum. Often it can be useful to apply values in stages in a system, and popular values are 2% to 3% for submains coupled with 4% or 3% for final circuits.
C
50
Circuitry and Related Parts of BS 7671: 2008
Final Circuit Equipment
Minimum Voltage here 400V - 6%
X
Intermediate Voltage Drop Point: This may be set to say 2.5% of supply
X
X
X
X
X
X X
X
X
X
X
X No load voltage max 400V +10%
X
X
X X
X X
X
Transformer 11000V / 400V
Figure C 4.4â&#x20AC;&#x201A; System voltage drops.
51
C
Guide to the Wiring Regulations
C 4.5.3 Definition and simple calculation of voltage drop An accurate estimation of the circuit design current is decisive in calculating an accurate voltage drop. For submains, diversity will need to be considered with a slightly different approach than when applying diversity for cable sizing. Whilst short time overload currents will not cause problems to a system, voltage dips below a certain value may cause equipment to stop or malfunction. Therefore a more rigorous approach to individual submain diversity is required. An ‘overall’ diversity factor, however, may be equal to that used for the maximum demand estimate. The definition of voltage drop is the voltage difference between any two points of a circuit or conductor, due to the flow of current. Voltage drop information for installation cables is given in BS 7671 Appendix 4 tables expressed in millivolts for a current of one amp for one metre of the cable. Hence: Voltage drop (V) =
tabulated voltage drop × design current (A) × length 1000
The tabulated ratings are also denoted as ‘(mV/A/m)’ ratings and the above equation can be expressed as follows: v.d. (V) =
(mV/A/m) × L × Ib 1000
or can be rearranged to find a limiting circuit length: Length (m) =
permitted v.d. (V) × 1000 (mV/A/m) × Ib
C 4.5.4 Correction for conductor temperature These equations and the (mV/A/m) values in Appendix 4 of BS 7671 are based upon fully loaded circuits, a rare circumstance in practice. The values of (mV/A/m) given in the Appendix 4 tables are at the maximum conductor operating temperature of, say, 70°C or 90°C, and these temperatures are only reached when the conductor is carrying its full load. At lower loads, the temperature and the resistance of the cable are lower. The difference can be significant – up to 20%. Thus for lightly loaded circuits this can reduce the tabulated rating (mV/A/m) by up to 20%.
C
52
Circuitry and Related Parts of BS 7671: 2008
The conductor temperature correction factor, Ct, is worked out using the following:
(
Ct =
)
Ib2 (t – 30) It2 p 230 + tp
230 + tp – Ca2 Cg2 –
where tp is the rated maximum conductor operating temperature Ib is design current of the circuit
G F E
0.98
D
C
A
1.00
B
It is the tabulated current rating of the cable.
Ib In
=0.9
B
0.96
Ib =0.8 In
0.94
Reduction Factor to tabulated mV/A/m
A
C
0.92
Ib =0.7 In
0.90
D
0.88
Ib =0.6 In
E
0.86
Ib =0.5 In
0.84
F
0.82
Ib =0.4 In
0.80
G Ib =0.3 In
0.78 0.76 0.74 0.72 0.70 0
10
40 20 30 o Ambient Temperature C
50
60
Figure C 4.5 Reduction factors for thermoplastic cables (PVC). Source: adapted from Electrical Installation Calculations, Third Edition, ECA 2002.
53
C
F G
E
D
C
A
1.00
B
Guide to the Wiring Regulations
0.98 0.96
A
0.94
Ib In
B
0.92
Ib =0.8 In
0.90 Reduction Factor to tabulated mV/A/m
C
0.88
Ib In
0.86
D
=0.7
Ib =0.6 In
0.84
E Ib In
0.82 0.80
F
0.78
Ib In
=0.5
=0.4
G
0.76
Ib In
0.74 0.72 0.70 0
10
20
30
40
50
60
70
80
90
o
Ambient Temperature C Figure C 4.6 Reduction factors for thermosetting cables (XLPE). Source: adapted from Electrical Installation Calculations, Third Edition, ECA 2002.
Again, manual calculations can be tedious, and the graphs in Figures C 4.5 and C 4.6 provide a quick and convenient way of avoiding them. The graphs can be used to correct tabulated (mV/A/m) values and can be applied to all cables under 16 mm2 and to the tabulated resistive component, (mV/A/m)r, for larger cables. To use the graphs, select an Ib/In line, and find the reduction factor F at the appropriate installation ambient temperature and a corresponding reduction factor. This factor is multiplied by either the tabulated (mV/A/m) value for cables up to 16 mm2 or by the resistive (mV/A/m)r component for cables of 25 mm2 and over. C 4.5.5 Correction for load power factor and temperature For larger cables above 25 mm2 where the load power factor is known, a more accurate estimation can be made of voltage drop allowing slightly greater cable
C
=0.9
54
=0.3
Circuitry and Related Parts of BS 7671: 2008
length or perhaps reduced size in marginal cases. The voltage drop is calculated using the formula: Voltage drop =
L × Ib [C cos f (mV/A/m)r + sin f (mV/A/m)x] 1000 t
where (mV/A/m)r is the tabulated value of resistive element of voltage drop in mV per amp per metre from the cable rating tables of Appendix 4 of BS 7671 (mV/A/m)x is the tabulated value of inductive element of voltage drop in mV per amp per metre from the cable rating tables of Appendix 4 f is the power factor of the load For cables of 25 mm2 and greater, the voltage drop is given both as an impedance (mV/A/m)z and as a complex impedance with a resistive element (mV/A/m)r and inductive element (mV/A/m)x as follows: (mV/A/m)z = √(mV/A/m)r2 + (mV/A/m)x2 Example calculations are provided in Appendix 10.
C 4.6
Disconnection and electric shock C 4.6.1 Introduction and protective measures A significant change for BS 7671: 2008 is the introduction of new terminology within the new Chapter 41. The previously very familiar terms ‘direct contact’ and ‘indirect contact’ are replaced by the terms ‘basic protection’ and ‘fault protection’ respectively; these terms in themselves introduce no technical changes. As well as terminology changes, the whole of Chapter 41 has been revised. It is important to become familiar with the structure of the chapter, and this is depicted in Figure C 4.7. It can be seen that ‘basic protection’ measures have been shunted to the end of the chapter. This is sensible, as almost without exception we do not consider these; they are so fundamental as to be ‘automatically’ included. The ‘basic protection’ protective measure is achieved by selecting equipment complying with relevant product standards. The new terms ‘basic protection’ and ‘fault protection’ are illustrated in Figure C 4.8.
55
C
Guide to the Wiring Regulations Protective Measure
=
+
Basic Protection
Insulation of live parts
Fault Protection
416
or
or Barriers or enclosures
Automatic Disconnection
411
ELV
414
Separation
413
Double Insulation
412
or
416
or
Figure C 4.7 Structure and ‘protective measures’ of Chapter 41 for general application.
No Basic Protection No Basic Protection L L
L L
N N E
N N E
E
E
L L
No Basic Protection No Basic Protection
N N E
N N E
E
E
Figure C 4.8 Basic protection and fault protection.
C
L L
56
With Basic Protection (Enclosure) With Basic Protection (Enclosure)
With Fault protection With Fault protection
L L
Circuitry and Related Parts of BS 7671: 2008
The second structural arrangement of Chapter 41 to note is that the measures other than automatic disconnection or ‘other measures’, i.e. Obstacles and Out of Reach (417), Non-conducting Locations (418) and Earth-free Local Equipotential Bonding (418.2) have been relegated to the rear of the chapter. As these methods are rarely used they have been discussed in Appendix 13. C 4.6.2 Automatic disconnection of supply The ‘protective measure – automatic disconnection of supply’ is the standard method used in most applications and almost by default. This measure makes up the bulk of Chapter 41 totalling some 40 regulations. Although the whole of Chapter 41 has been revised, highlights of automatic disconnection include reduced disconnection times (compared with the 16th Edition) and an increased use of RCDs, both explained in this part of the book. Chapter 41 first sets down the main requirements for automatic disconnection, followed by specifics for TN, TT and IT systems. To comply with the ‘protective measure’, the following are required: 1 basic protection; and 2 protective earthing and protective equipotential bonding (see Chapter E); and 3 automatic disconnection in the event of a fault. Automatic disconnection requires disconnection within the time given by Table 41.1 of BS 7671. For nominal line-to-earth voltages U0 of 230 V, as in the UK, the requirements are given in Table C 4.6. Table C 4.6 Maximum disconnection times for U0 230 V. System
Final circuits disconnection time (s)
Distribution circuits disconnection time (s)
TN a.c.
0.4
5
TN d.c.
5
5
TT a.c.
0.2
1
TT d.c.
0.4
1
57
C
Guide to the Wiring Regulations These disconnection times are achieved by limiting the earth fault loop impedance Zs such that
Zs â&#x2030;¤
U0 Ia
where U0 is the voltage to earth (normally 230â&#x20AC;&#x2030;V) Ia is the current in amperes causing the automatic operation of the disconnecting device within the time specified in the table
Zs is the total earth fault loop impedance (ELI) in ohms of the fault loop, comprising the source impedance Ze, the line conductor up to the point of the fault Z1 and the protective conductor within the installation Z2 between the point of the fault and the source, or Zs = Ze + (Z1 + Z2) Earth fault loop impedance calculations conventionally assume a fault of negligible impedance. Figures C 4.9 and C 4.10 show the path of earth fault current for TN-C-S and TT systems and the components that make up the impedance of the earth fault loop. For TT systems Zs includes the resistance of the installation cables (Z1 and Z2), the installation earth electrode (Za), the supply distribution cable and the supply earth electrode (Zd). Maximum design earth fault loop impedance values for common devices are given in Tables 41.2, 41.3, 41.4 of BS 7671: 2008 and are reproduced in Appendix 3 of this book. Within this book, in order to distinguish the BS 7671 tabulated design earth fault loop impedance values from measured values, design earth fault loop impedance values have been given the symbol Z41 (note: this symbol does not appear in BS 7671).
C
58
59
Figure C 4.9â&#x20AC;&#x201A; Path of earth fault loop impedance TN-C-S system.
Supply Network
Path of earth fault current
(Ze)
(Ze)
Supply Terminals
Z2
Z1
Installation
Distribution Board
Equipment
Circuitry and Related Parts of BS 7671: 2008
C
C
60 Supply Network
Supply Terminals
Z2
Z1
Installation
Distribution Board
Za Installation Earth Electrode
Figure C 4.10â&#x20AC;&#x201A; Path of earth fault loop impedance TT system.
Zd
Path of earth fault current
Equipment
Guide to the Wiring Regulations
Circuitry and Related Parts of BS 7671: 2008
Therefore, to achieve the required disconnection times:
Z41 > Zs and Z41 > Ze + (Z1 + Z2) where
Z41 is the design ELI from Chapter 41 Zs is the total earth fault loop impedance Ze is the impedance of the source or sources. For conductor sizes 16 mm2 and less, reactance is not a factor and resistance can be used, and the equation becomes:
Z41 > Ze + (R1 + R2) where R1 is the resistance of the line conductor, up to the point of the fault R2 is the resistance of the protective conductor. An alternative way of expressing this is by calculating the maximum length of a circuit and using the following formula: Lâ&#x2030;¤
Z41 â&#x20AC;&#x201C; Ze R1 + R2
where R1 is the resistance in ohms per metre of the line conductor R2 is the resistance in ohms per metre of the protective conductor
Ze, the impedance of the supply, is either measured, determined from the supply company, or if domestic can be assumed to be as in Table C 4.7.
61
C
Guide to the Wiring Regulations
Table C 4.7 Ze for utility supplies. Type of system
External earth fault loop impedance Ze (Ω)
TN-C-S
0.35
TN-S
0.8
TT
21
C 4.6.3 TT installations A disconnection time of 0.2 s for TT installations has been introduced in the 17th Edition. This makes the use of an RCD or circuit breaker with a residual element virtually essential. For most installations, the installation earth electrode value Za (see Figure C 4.10) is large compared with the other factors contributing to earth fault loop impedance (supply and installation cables and supply earthing, Zd). For simplicity, therefore, the following formula is used:
Za < Z41 RCD where Z41 RCD is the maximum value of loop impedance from Table C 4.8. When an RCD is used for shock protection it is necessary to provide short circuit protection between line conductors and neutral by an overcurrent device. Table C 4.8 TT maximum ELI values RCD rated residual operating current (mA)
Maximum values of earth fault loop impedance Z41 RCD (Ω)
30
15331
100
4601
300
153
500
100
An earth electrode value of greater than 200 W is considered by some to be unstable; others use a figure of 100 W. However, for single vertical rod electrodes, depth is an important factor and a 2.4 m deep electrode with initial resistance of, say, 300 W will be more stable than a shallow 1.2 m rod with an initial resistance of, say, 100 W. Thus the effects of freezing and drying out can be all but eliminated in the UK by installing 2.4 m deep electrodes. 1
C
62
Circuitry and Related Parts of BS 7671: 2008
C 4.6.4 ELI adjustment The design values of maximum earth fault loop impedance (ELI) given in BS 7671 Tables 41.2, 41.3 and 41.4 cannot be directly compared to measured values. Measured values of ELI need to be adjusted to take account of the fact that when measured they are not at maximum operating temperature. While this point is discussed in Chapter F of this book, the necessary compensation step often gets missed; the design engineer thinks the tester will do a compensation and vice versa. A new appendix, Appendix 14, has been included in the 17th Edition, and this suggests a compensation value of 0.8 applied as follows:
Zmeasured ≤ 0.8 Z41 Although this guidance and the values in BS 7671 Tables 41.2, 41.3 and 41.4 set figures for maximum ELI, we should not get paranoid if the odd circuit slightly exceeds these values. C 4.6.5 Irrelevant ELI specification A common source of misunderstanding is that of either specifying or measuring values of ELI where the circuit also has an RCD fitted. ELI measurement under these circumstances is a futile exercise. The circuit will have been checked for continuity, and this is all that is needed together with, of course, functional checks of the RCD. This criterion satisfies requirements for automatic disconnection. The subject is somewhat confused by the inclusion of RCBOs in BS 7671 Table 41.3 and for clarification, circuits with RCBOs do not need to meet the specified ELI values. Functional checks for RCDs are covered in Chapter F. C 4.6.6 RCD supplementary protection A completely new requirement in Chapter 41 is Regulation 411.3.3, which specifies RCDs for socket-outlet circuits intended for use by ordinary persons. A point to stress here is that the ‘additional protection’ is not optional; it is now a fundamental requirement of Chapter 41. The wording of this regulation is reproduced below, and guidance on its interpretation is given under the selection and erection part of RCDs, Section D 7.1.
63
C
Guide to the Wiring Regulations
411.3.3 Additional Protection In a.c. systems, additional protection by means of an RCD in accordance with Regulation 415.1 shall be provided for: (i) socket-outlets with a rated current not exceeding 20 A that are for use by ordinary persons and are intended for general use, and (ii) mobile equipment with a current rating not exceeding 32 A for use outdoors. An exception is permitted for: (a) socket-outlets for use under the supervision of skilled or instructed persons, e.g. in some commercial or industrial locations, or (b) a specific labelled or otherwise suitably identified socket-outlet provided for connection of a particular item of equipment. Note 1: See also Regulations 314.1(iv) and 531.2.4 concerning the avoidance of unwanted tripping. Note 2: The requirements of Regulation 411.3.3 do not apply to FELV systems according to Regulation 411.7 or reduced low voltage systems according to Regulation 411.8.
In the context of this Regulation, RCD is a 30 mA RCD.
C 5
Submains
C 5.1
Diversity Getting a design that achieves function, economics and future capacity is important for most installations and in achieving this an accurate estimate of design current is key. General notes on diversity and load profiles were given in Section C 3.
C 5.2
Distribution circuit (submain) selection Distribution circuits are normally selected from the following cables and wiring systems:
C
64
Circuitry and Related Parts of BS 7671: 2008
Table C 5.1 Comparison of distribution systems. Distributor system
Disadvantages
Advantages
Unarmoured cables with or without cable tray
Risk of damage
Quick to install
Armoured cables
Large sizes require support to supporting structures
Good mechanical protection, good fire withstand
Mineral insulated cables
Need installation skills, may need protection from voltage surges
Robust, good fire withstand
Single insulated in conduit or trunking
Limited current carrying capacity
Good mechanical protection, easy rewiring
Busbar trunking
Not easily adapted
Easy to alter tap-offs
•• ••
busbar trunking; single insulated cables in trunking or conduit; steel wire armoured cables; mineral insulated cables.
The most suitable can be selected with assistance from Table C 5.1, which generally highlights the particular advantages and disadvantages of the systems. Of course, regional material and labour costs will have to be factored into this decision of wiring system.
C 5.3
Armouring as a cpc Software design packages may propose that a supplementary protective conductor be run in parallel with an armoured cable. This is usually proposed to reduce the loop impedance such that disconnection will occur within the required five seconds. If possible, designers should manually check the calculation at this point. The armouring of cables can and should be used as a protective conductor. All protective conductors are required either to:
•
comply with the adiabatic equation of Regulation 543.1.3,
•
I 2t S = √ , or k
meet the cross-sectional area requirements of Table 54.7.
65
C
Guide to the Wiring Regulations
The calculated size virtually always produces a smaller conductor size (see Chapter E). In 2007, the ECA commissioned the Electrical Research Association (ERA) to carry out an investigation into the merits or not of running additional cpcs externally to armoured cables. The report included a comparison of the fault current withstand of the armour of cables to BS 5467, using the k values given in Chapter 54 of BS 7671. It showed that for all cables except 120 mm2 and 400 mm2 2-core cables, the fault currentwithstand of the armour was greater than the fault current required to operate a BS 88 fuse within 5 s. The 120 mm2 cable was within a few per cent of passing, and should be used unless it is intended to run the cable at full current-carrying capacity. Also, calculation of the current sharing between the armour and an external cpc showed that if a small external cpc was run in parallel with the armour of a large cable there is a risk that the fault current withstand of the external cpc will be exceeded. Because of this it is recommended that the cross-sectional area of the external cpc should not be less than a quarter of that of the line conductors. More details of the findings from this report are discussed in Chapter E, Section E5, and a full copy of the report is included in Appendix 16. The following guidance is recommended:
•
Use all armoured cables as a cpc without the need for a thermal withstand check with the exception of 400 mm2 2-core. Note: The 120 mm2 cable was within a few per cent of the size required (required I 2t – 33 062 500, actual 33 800 000 after 5 s) and should be used without calculation unless it is intended to run the cable at full current-carrying capacity. It is very difficult to load a cable of this size at its full current-carrying capacity for a continuously long period. Where calculation software specifies external cpcs for ELI reduction, use a cpc size of at least 25% of the phase size (perhaps after manually checking calculations). Manually check ELI calculations where they specify a small external cable cpc.
• • C
66
Circuitry and Related Parts of BS 7671: 2008
Table C 5.2 Distribution circuit disconnection times.
C 5.4
System
Disconnection time for distribution circuits (s)
TN
5
TT
1
Automatic disconnection for submains The disconnection times allowed for distribution circuits and for any circuit, other than a final circuit not exceeding 32 A, are given in Table C 5.2.
C 6
Discrimination co-ordination
C 6.1
Principles and system co-ordination Section 536 of BS 7671: 2008 details requirements for protective device co-ordination. An overall ‘system’ design view has to be taken on discrimination and co-ordination as otherwise this can lead to uneconomic schemes. For some installations, depending upon the number of protective devices between final circuit and incomer protection, it may be an expensive luxury to design for full discrimination. Consider Figure C 6.1, which illustrates this point; a final circuit distribution board has a socket outlet protected by a 32 A circuit breaker. As can be seen, by using a 2:1 discrimination rule to achieve full discrimination, a 2000 A main protective device is required and we have not considered any loads! This demonstrates that, for many installations, whole system discrimination is not justified unless there are life-critical constraints. Regulation 536.1 states that discrimination should be considered to prevent danger and where required for proper functioning of the installation. Chapter 36 gives an example of life-support systems where discrimination should be considered. There is a fair bit of judgement to be made. Take Figure C 6.1 again – let’s say the final circuit board was for a multi-million pound dealer unit. It would be reasonable for circuit breaker A to discriminate with circuit breaker B, but the discrimination between circuit breakers C and D may still be regarded as a luxury. We all know that despite the turnover of the client, there would be a limit to what they would pay for the electrical installation.
67
C
Guide to the Wiring Regulations
Socket Outlet Breaker A 32 A X
Breaker C
X
Final Distribution Board
X X
125 A X
X X
X X
Riser
63 A
250 A X
Breaker B
X
X X
X
X X
Breaker D
X
500 A
Riser 1000 A X
X
2000 A Incomer
Figure C 6.1â&#x20AC;&#x201A; System discrimination.
There are many options and combinations that can assist; for example, in Figure C 6.1 the final circuit breaker (A) could be 16 or 20â&#x20AC;&#x2030;A, or circuit breaker C may be omitted. In order to carry out an accurate discrimination study, fault current magnitudes are required at every protective device position.
C
68
Circuitry and Related Parts of BS 7671: 2008
C 6.2
Fuse-to-fuse discrimination Fuses are relatively simple to consider when establishing discrimination co-ordination. As a rule of thumb, an upstream circuit breaker will always discriminate with a downstream fuse of half its rating. This applies for all currents of both overload magnitude and for fault currents. Fuses have characteristics described as follows:
• •
Pre-arcing I 2t is the energy required to take the fuse element to the point where it starts to melt. Total operating I 2t is the total energy until the arc is quenched.
This information is widely available from product standards, manufacturers and is included in Appendix 5 of this book. Discrimination is achieved if the pre-arcing I 2t of the upstream device is less than the total operating I 2t of the downstream device; this is illustrated for some common BS 88 fuses in Figure C 6.2.
2
Total Operating I t 2
Pre - Arcing I t
2
It
50
63
80
100
125
Fuse Rating - Amps Figure C 6.2 Typical fuse I2t characteristics.
69
C
Guide to the Wiring Regulations
It can be seen that by studying the I 2t characteristics that the 80 A fuse discriminates with the 125 A fuse (but not with the 100 A fuse). Fuses to BS 88 and BS 1361 have relatively very high fault ratings and will be able to interrupt all short circuit currents in the installation, with no need for cascading (see Section C 6.3).
C 6.3
Circuit breaker to circuit breaker discrimination Unlike fuses, circuit breakers cannot always rely on the upstream/downstream ratio of 2:1 for guaranteed discrimination. The 2:1 ratio generally holds true for the thermal trip mechanism but does not always apply to the magnetic trip mechanism (see D5 for explanation of mechanisms). The normal method of manual co-ordination is by plotting the relevant protective device characteristics onto the same time-current graph paper. Due to scaling this is carried out on log-log paper; the graph in Figure C 6.3 shows two circuit breakers and the ‘zone’ where discrimination may not be achieved.
C2 C1 Discrimination in this area to be confirmed by manufacturer
Time
Current Figure C 6.3 Discrimination between two circuit breakers.
C
70
Circuitry and Related Parts of BS 7671: 2008
The zone indicated in Figure C 6.3 indicates an area where discrimination can only be achieved by carrying out tests and thus only manufacturers can confirm discrimination between circuit breakers in this zone. Discrimination in this area is a subject vaguely addressed by some manufacturers and, for critical applications mentioned in C 6.1, confirmation by the manufacturer is strongly recommended. Sometimes this subject is confused with cascading, a circumstance where downstream circuit breakers are ‘backed-up’ by circuit breakers. This technique should not be a substitute for a system discrimination co-ordination. Where cascading is used, the upstream breaker must have sufficient short-circuit breaking capacity to interrupt the fault, and the downstream breaker must be able to handle the through fault currents sufficiently long enough for the upstream breaker to operate.
C 6.4
Circuit breaker to fuse discrimination At certain fault levels, fuses operate quicker than circuit breakers. Although now always readily available, the use of fuses is often to assist with achieving a system discrimination scheme. Figure C 6.4 shows circuit breaker and fuse characteristics and indicates the faster operating time at high fault currents (no values have been put on the figure as this is a general trend). The principle outlined in Figure C 6.4 is the same as used for back-up protection, where a downstream circuit breaker is not rated for the prospective fault current at the point where it is installed. Take point X in the figure; larger fault currents will be interrupted by the fuse, smaller fault currents will be interrupted by the circuit breaker. Thus point X should be at a current less than the fault rating of the circuit breaker. Manufacturers’ data should be considered in co-ordinating for back-up protection.
71
C
Guide to the Wiring Regulations
Circuit breaker Fuse total operating Fuse prearcing
Time
Point X Current
Figure C 6.4 Circuit breaker and fuse operating characteristics.
C 7
Parallel cables
C 7.1
General and 7671 requirements The use of parallel cables is often made for reasons of cost as, for a given current, two or more cables run in parallel may be more economic than a single larger one. The other reason to use two or more cables in parallel is for ease of running and the logistics of termination. Sometimes switchgear may simply not have the space in the termination area for a single cable over a certain size. BS 7671 requirements for cables run in parallel are summarized in Table C 7.1. Table C 7.1 Requirements for cables in parallel.
C
Requirement
Regulation
No branch circuits allowed
433.4
Iz total = Iz1 + Iz2 … etc.
433.4.1
Unequal size conductors require careful consideration (see C 7.2)
433.4.2
Fault protection shall be at supply end
434.4
Shall have equal current sharing or calculated appropriately
523.8
72
Circuitry and Related Parts of BS 7671: 2008
It should be noted that ring circuits are not considered to be parallel cables. The requirements of Table C 7.1 and hence the Regulations are satisfied by selecting cables of exactly the same type, construction and installation, in which case the total current-carrying capacity is the sum of the individual currentcarrying capacities. It should be noted that grouping factors are applicable to parallel cables.
C 7.2
Unequal current sharing The general rules, summarized in Table C 7.1, apply to most applications for cables run in parallel with equal impedance. This is achieved if all the factors that affect the current-carrying capacity of the cables are the same, i.e. type, length, construction and installation method. It is assumed by this criterion that the impedances will be within 10% of each other and current sharing is taken to be equal. Where this is not the case, it is possible to calculate and design the unequal current sharing based upon the different impedances, and methods for this are included in Appendix 10 of BS 7671: 2008. Discussion of this is outside the scope of this book.
C 8
Harmonics
C 8.1
Requirements BS 7671: 2008 primarily concerns itself with harmonics in respect of appropriate sizing of the neutral conductor, and the requirements are summarized in Table C 8.1.
Table C 8.1â&#x20AC;&#x201A; Requirements for harmonic assessment for neutral conductor. Requirement
Regulation
Notes
Balanced polyphase circuits require no action
523.6.1
Neutral in unbalanced polyphase circuits to be sized for highest line current
523.6.2
This is usually done as a matter of course
For harmonic content > 15% reduced size neutral shall not be used
523.6.3
This is usually done as a matter of course
For high harmonic content further consideration is to be made
523.6.3
73
C
Guide to the Wiring Regulations
Table C 8.2 Rating factors for triple harmonic currents in four-core and five-core cables.
1
C 8.2
Third harmonic content of line current1 (%)
Rating factor Size selection is based on line current
Size selection is based on neutral current
0–15
1.0
—
15–33
0.86
—
33–45
—
0.86
> 45
—
1.0
Expressed as % of THD.
Harmonic assessment Coupled with Regulation 523.6.3, BS 7671: 2008 provides an informative Appendix (11) on cable de-rating for installations with high harmonic currents. Most modern installations contain equipment that causes harmonic currents; for example, equipment with switched mode power supplies found in personal computers, photocopiers, printers, fluorescent lighting and motor drives. The summation of these harmonic currents can cause an overload in the neutral conductor. Table C 8.2, extracted from Appendix 11 of BS 7671, provides de-rating factors for balanced three-phase loads and should be applied to 4- and 5-core cables. It can be seen that a de-rating factor of 0.86 will cover neutral undersizing and perhaps may be used for loads like micro and small data centres and communications rooms. This de-rating should be used in conjunction with the general cable sizing philosophy given in Sections C 3 and C 4. Appendix 11 of BS 7671: 2008 gives further methods for harmonic de-rating factors for higher harmonic frequencies, but these are outside the scope of this book.
C 9
Standard final circuit designs
C 9.1
Introduction and scope This section provides ‘standard’ designs for some common final circuits. The designs provide circuit type, protective device and most importantly a maximum circuit length. Many of us use these standard designs, as it is time-consuming to
C
74
Circuitry and Related Parts of BS 7671: 2008
design every final circuit from first principles. Standard circuit designs are usually used for common circuits, particularly domestic circuits. The designs in this Section C 9.3 can be used in commercial and industrial installation designs for final circuits where the eath fault loop impedance at the local distribution board does not exceed the standard values given below. The tables have been calculated using particular parameters as follows: External earth fault loop impedances Those used by the UK supply industry are as follows:
•• •
0.35 Ω for PME supplies; 0.80 Ω for TN-S supplies; 21 Ω for TT supplies.
Where RCDs are used, the tables in this section have been calculated so that the earth fault loop impedance values comply with the limiting values for overcurrent devices in Chapter 41. This gives maximum lengths, which are generally recommended, but considerably longer lengths are possible. Cable types and installation methods The standard circuit tables have assumed flat twin and earth cable to BS 6400 with reduced cpc size and installed as Table 4A2 of BS 7671 with current rating taken from Table 4D5 of BS 7671 (see Table C 9.1): Table C 9.1 Flat twin and earth cable installation methods, adapted from Table 4D5 of BS 7671. Reference method A
Examples
Description
Rating of 2.5 mm2 cable
Enclosed in conduit in an insulated wall
20
(Continued.)
75
C
Guide to the Wiring Regulations
Table C 9.1 (Continued.) Reference method
Examples
Description
Rating of 2.5 mm2 cable
C
Clipped direct
27
Method 100
Installation methods for flat twin and earth cable clipped direct to a wooden joist above a plasterboard ceiling with a minimum U value of 0.1 W/m2K and with thermal insulation not exceeding 100 mm in thickness
21
Method 101
Installation methods for flat twin and earth cable clipped direct to a wooden joist above a plasterboard ceiling with a minimum U value of 0.1 W/m2K and with thermal insulation exceeding 100 mm in thickness
17
Method 102
Installation methods for flat twin and earth cable in a stud wall with thermal insulation with a minimum U value of 0.1 W/m2K with the cable touching the inner wall surface
21
Method 103
Installation methods for flat twin and earth cable in a stud wall with thermal insulation with a minimum U value of 0.1 W/m2K with the cable not touching the inner wall surface
13.5
with a current rating factor of 0.5 in accordance with Regulation 523.7
Note that Table 4D5 was expanded for BS 7671: 2008, and confirms that in many cases cables installed in particular circumstances with thermal insulation (methods 100, 101 and 102) show a significantly better current rating as compared with the ‘totally surrounded method’ (method 103).
C
76
Circuitry and Related Parts of BS 7671: 2008
C 9.2
Standard domestic circuits The following tables are based on a voltage drop of 5% generally and lighting circuit voltage drop of 3%.
Table C 9.2 Standard domestic final circuit lengths type B circuit breakers. Type B circuit breaker and RCBO (to BS EN 60898 or 61009) Type of circuit
Cable csa pvc/pvc (mm2)
Circuit breaker rating (A)
Maximum length for TN-C-S PME (m)
Maximum length for TN-S (m)
Installation method
MCB
RCD or RCBO
MCB
RCD or RCBO
Ring 13 A socket outlet
2.5/1.5
32
note 1
106
note 1
106
Radial 13 A socket outlets
2.5/1.5
20
40
40
40
40
Cooker (oven and hob)
6/2.5
32
53
53
50
53
Oven (no hob) up to 3 kW
2.5/1.5
16
55
55
55
55
Immersion heater
2.5/1.5
16
55
55
55
55
Shower to 30 A (7.2 kW)
6/2.5
32
note 1
53
note 1
50
Shower to 40 A (9.6 kW)
10/4
40
note 1
66
note 1
66
A, C, 100, 102; see note 1
Storage heater
2.5/1.5
16
51
51
51
51
All
Fixed lighting (excl. switch drops)
1.5/1.0
10
53
53
53
53
A, C, 100, 102; see note 1
All
Note 1: If the cable is installed as per installation methods 101 or 103 a larger csa cable is required or thermosetting cable per 4E3A. Note 2: RCD (or RCBO) required.
Table C 9.3 Standard domestic final circuit lengths type C circuit breakers. Type C circuit breaker and RCBO (to BS EN 60898 or 61009) Type of circuit
Cable csa pvc/pvc (mm2)
Circuit breaker rating (A)
Maximum length for TN-C-S PME (m)
Maximum length for TN-S (m)
MCB
RCD or RCBO
MCB
RCD or RCBO
Ring 13 A socket outlet
2.5/1.5
32
63
82
NP
NP
Radial 13 A socket outlets
2.5/1.5
20
34
40
14
19
Cooker (oven and hob)
6/2.5
32
29
49
NP
NP
Installation method
A, C, 100, 102; see note 1
(Continued.)
77
C
Guide to the Wiring Regulations
Table C 9.3 (Continued.) Type C circuit breaker and RCBO (to BS EN 60898 or 61009) Type of circuit
Cable csa pvc/pvc (mm2)
Circuit breaker rating (A)
Maximum length for TN-C-S PME (m)
Maximum length for TN-S (m)
MCB
RCD or RCBO
MCB
RCD or RCBO
Oven (no hob)
2.5/1.5
16
46
55
27
35
-
Immersion heater
2.5/1.5
16
46
55
27
35
Shower to 30 A (7.2 kW)
6/2.5
32
49
NP
NP
A, C, 100, 102; see note 1
51
NP
NP
All
note 2 Shower to 40 A (9.6 kW)
10/4
40
Installation method
note 2 Storage radiator
2.5/1.5
16
46
51
21
35
Fixed lighting (excl. switch drops)
1.5/1.0
6
53
53
53
53
Note 1: If the cable is installed as per installation methods 101 or 103 a larger csa cable is required or thermosetting cable per 4E3A. Note 2: RCD (or RCBO) required. Note 3: NP means not permitted.
Table C 9.4 Standard domestic final circuit lengths cartridge fuses BS 1361. Cartridge fuses BS 1361 Type of circuit
Cable csa pvc/pvc (mm2)
Fuse rating (A)
Maximum length for TN-C-S PME (m)
Maximum length for TN-S (m)
MCB
RCD or RCBO
MCB
RCD or RCBO
Ring 13 A socket outlet
2.5/1.5
30
note 2
111
note 2
111
Radial 13 A socket outlets
2.5/1.5
20
40
40
40
40
Cooker (oven and hob)
6/2.5
30
53
53
28
53
Oven (no hob)
2.5/1.5
15
32
32
32
32
Immersion heater
2.5/1.5
15
32
32
32
32
Shower to 30 A (7.2 kW)
6/2.5
30
note 2
53
note 2
53
Shower to 40 A (9.6 kW)
10/4
45
note 2
66
note 2
66
Storage radiator
2.5/1.5
15
30
30
30
30
Fixed lighting (excl. switch drops)
1.5/1.0
5
53
53
53
53
Installation method
A, C, 100, 102, see note 1
All
Note 1: If the cable is installed as per installation methods 101 or 103 a larger csa cable is required or thermosetting cable per 4E3A. Note 2: RCD (or RCBO) required. Note 3: NP means not permitted.
C
78
Circuitry and Related Parts of BS 7671: 2008
Table C 9.5 Standard domestic final circuit lengths rewirable fuses (semi-enclosed) BS 3036. Rewirable fuses (semi-enclosed) BS 3036 Type of circuit
Cable csa Fuse pvc/pvc rating (mm2) (A)
30
Maximum length for TN-C-S PME (m)
Maximum length for TN-S (m)
MCB
RCD or RCBO
MCB
note 2
111
Ring 13 A socket outlet; note 1
2.5/1.5
Radial 13 A socket outlets
2.5/1.5 4.0/1.5
20 20
NP 68
NP 68
Cooker (oven and hob)
6/2.5
30
53
Oven (no hob)
1.5/1.0
15
Immersion heater
1.5/1.0
Shower to 30 A (7.2 kW)
Installation method
RCD or RCBO 111
A, C, 100, 102; see note 1
NP 68
NP 68
C
53
53
53
30
30
30
30
15
30
30
30
30
6/2.5
30
note 2
55
note 2
53
Shower to 40 A (9.6 kW)
10/4
45
66
66
66
66
Storage radiator
2.5/1.5
15
51
51
51
51
Fixed lighting (excl. switch drops); note 2
1.0/1.0 1.5/1.0
5 5
35 53
35 53
35 53
35 53
note 2
All
A, C, 100, 102; see note 1
All
Note 1: If the cable is installed as per installation methods 101 or 103 a larger csa cable is required or thermosetting cable per 4E3A. Note 2: RCD (or RCBO) required. Note 3: NP means not permitted.
C 9.3
All-purpose standard final circuits The following tables are based on a voltage drop of 5%. Circuits are suitable for the installation reference methods listed in the tables. Voltage drop limitations are calculated for the most onerous installation reference method listed for the cable/ overcurrent device combination. The load assumed is the rating of the overcurrent device. Some values of maximum length in the tables have the notation(s), indicating that the length is limited by earth fault loop impedance. If you have an external loop impedance lower that that used in the table then longer lengths are possible.
79
C
Guide to the Wiring Regulations
Table C 9.6 All-purpose 5 A to 16 A radial final circuits using insulated 70°C thermoplastic (pvc) insulated and sheathed flat cable having copper conductors. Protective device
Cable size (mm2)
Permitted installation reference methods
Maximum length (m) Zs ≤ 0.8 Ω TN-S
Zs ≤ 0.35 Ω TN-C-S
Rating (A)
Type
5
BS 1361 BS 3036
1.0/1.0
103,101,A,100,102,C
56 56
56 56
5
BS 1361 BS 3036
1.5/1.0
103,101,A,100,102,C
88 88
88 88
6
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
1.0/1.0
46 46 46 25 (s)
46 46 46 36 (s)
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
1.5/1.0
72 72 72 30 (s)
72 72 72 43 (s)
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
1.0/1.0
26 24 24 8
26 24 24 18
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
1.5/1.0
39 39 39 9
39 39 39 22
15
BS 1361 BS 3036
1.0/1.0
C NP
17 NP (ol)
17 NP (ol)
15
BS 1361 BS 3036
1.5/1.0
100,102,C NP
26 NP (ol)
26 NP (ol)
15
BS 1361 BS 3036
2.5/1.5
101,A,100,102,C 100,102,C
43 45
43 45
15
BS 1361 BS 3036
4.0/1.5
103,101,A,100,102,C 101,A,100,102,C
72 75
72 75
16
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
1.0/1.0
C C
16 16 14 (s) NP (s)
16 16 16 8 (s)
16
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
1.5/1.0
100,102,C 100,102,C
24 24 17s NP (s)
24 24 24 10 (s)
6
10
10
103,101,A,100,102,C
103,101,A,100,102,C
101,A,100,102,C
103,101,A,100,102,C
(Continued.)
C
80
Circuitry and Related Parts of BS 7671: 2008
Table C 9.6 (Continued.) Protective device
Cable size (mm2)
Permitted installation reference methods
Maximum length (m) Zs ≤ 0.8 Ω TN-S
Zs ≤ 0.35 Ω TN-C-S
Rating (A)
Type
16
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
2.5/1.5
101,A,100,102,C 101,A,100,102,C
40 40 27s NP (s)
40 40 40 15 (s)
16
BS EN 60269–2,BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
4.0/1.5
103,101,A,100,102,C 103,101,A,100,102,C
66 66 31 (s) NP (s)
66 66 54 (s) 18 (s)
Key: NP, not permitted. ol, cable/device/load combination not allowed in any of the installation conditions. s, limited by earth fault loop impedance Zs.
Table C 9.7 All-purpose 20 A to 32 A radial final circuits using insulated 70°C thermoplastic (pvc) insulated and sheathed flat cable having copper conductors. Protective device
Cable size (mm2)
Permitted installation reference methods
Maximum length (m) Zs ≤ 0.8 Ω TN-S
Zs ≤ 0.35 Ω TN-C-S
A,100,102,C A,100,102,C NP A,100,102,C
31 31 NP (ol) 31 14 (s) NP (s)
31 31 NP (ol) 31 31 9 (s)
4.0/1.5
101,A,100,102,C 101,A,100,102,C C 101,A,100,102,C
48 (s) 44 (s) 48s 53 17s NP (s)
53 53 57 53 39 (s) 11 (s)
6.0/2.5
103,101,A,100,102,C 103,101,A,100,102,C
77 (s) 71 (s) 77 (s) 81 27 (s) NP (s)
81 81 85 81 63 (s) 17 (s)
Rating (A)
Type
20
BS EN 60269–2, BS 88–6 BS 1361 BS 3036 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
2.5/1.5
20
BS EN 60269–2,BS 88–6 BS 1361 BS 3036 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
20
BS EN 60269–2, BS 88–6 BS 1361 BS 3036 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
(Continued.)
81
C
Guide to the Wiring Regulations
Table C 9.7 (Continued.) Protective device
Cable size (mm2)
Permitted installation reference methods
Zs ≤ 0.8 Ω TN-S
Zs ≤ 0.35 Ω TN-C-S
C C
26 26 5 (s) NP (s)
26 26 24 (s) 4 (s)
4.0/1.5
A,100,102,C A,100,102,C
31 (s) 42 5 (s) NP (s)
42 42 28 (s) 4 (s)
BS EN 60269–2, BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
6.0/2.5
101, A,100,102,C 101, A,100,102,C
50 (s) 64 9 (s) NP (s)
64 64 45 (s) 8 (s)
30
BS 1361 BS 3036
4.0/1.5
C NP
17s NP (ol)
36 NP (ol)
30
BS 1361 BS 3036
6.0/2.5
A,100,102,C C
27 (s) 23 (s)
53 57
30
BS 1361 BS 3036
10/4.0
101, A,100,102,C A,100,102,C
45 (s) 37 (s)
90 93
32
BS EN 60269–2, BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
4.0/1.5
C C
11 (s) 31 (s) NP (s) NP (s)
33 33 18 (s) NP (s)
32
BS EN 60269–2, BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
6.0/2.5
A,100,102,C A,100,102,C
19 (s) 49 NP (s) NP (s)
49 49 29 (s) 1 (s)
Rating (A)
Type
25
BS EN 60269–2, BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
2.5/1.5
25
BS EN 60269–2, BS 88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
25
Key: NP, not permitted. ol, cable/device/load combination not allowed in any of the installation conditions. s, limited by earth fault loop impedance Zs.
C
Maximum length (m)
82
Circuitry and Related Parts of BS 7671: 2008
Table C 9.8 Ring final circuits using insulated 70°C thermoplastic (pvc) insulated and sheathed flat cable having copper conductors. Protective device
Cable size (mm2)
Rating (A)
Type
30
BS 1361 BS 3036
2.5/1.5
30
BS 1361 BS 3036
4.0/1.5
32
BSEN 60269–2,BS88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
2.5/1.5
BSEN 60269–2,BS88–6 MCB and RCBO Type B MCB and RCBO Type C MCB and RCBO Type D
4.0/1.5
32
Permitted installation reference methods
Maximum length m Zs ≤ 0.8 Ω TN-S
Zs ≤ 0.35 Ω TN-C-S
A,100,102,C
59 (s) 49 (s)
111 111
101,A,100,102,C
183 69
183 159
106 106 NP (s) NP (s)
106 106 63 1
176 176 NP (s) NP (s)
176 176 33 4
A,100,102,C
101,A,100,102,C
Key: NP, not permitted. ol, cable/device/load combination not allowed in any of the installation conditions. s, limited by earth fault loop impedance Zs.
C 10 RCDs and circuitry C 10.1 Introduction, increased use of RCDs Chapter D discusses the selection of RCDs and their increased specification in BS 7671: 2008 compared with previous editions. The increased use of RCDs includes the following:
• •• •
All socket-outlet circuits accessible to ordinary or non-instructed persons* (411.3.3). All circuits within a bathroom (701.411.3.3). Concealed cables either less than 50 mm deep, in installations not intended to be under the supervision of a skilled or instructed person*, not mechanically protected or protected by earthed metal and not run in the ‘safe zones’ *. Concealed cables within metal partitions, in installations not intended to be under the supervision of a skilled or instructed person*, not mechanically protected or protected by earthed metal and accessible to ordinary or noninstructed persons*.
83
C
Guide to the Wiring Regulations
• • •
Generally where disconnection times cannot be achieved with an overcurrent device. Most TT installations, usually required to achieve a disconnection time of 0.2 s. Other special locations, including swimming pools and caravan parks.
*The subject of providing RCDs for ordinary persons is covered in D 7.1, which should be read in conjunction with this section. They are now required for most domestic socket-outlet circuits as well as some commercial and industrial socketoutlet circuits, and this section of the book details how to arrange the circuitry aspects of RCDs in order to maintain compliance with the Regulations.
C 10.2 Consumer unit arrangements for RCDs Every installation shall be divided into circuits as necessary to:
•• • • ••
avoid hazards and minimize inconvenience in the event of a fault; facilitate safe inspection, testing and maintenance; take account of danger that may arise from circuit failure such as a lighting circuit; reduce the possibility of unwanted tripping of RCDs, due to excessive protective conductor currents produced by equipment in normal operation; mitigate the effects of electromagnetic interference; and prevent the indirect energizing of a circuit intended to be isolated.
There are various ways of arranging RCDs in consumer units; an obvious but expensive option is to use RCBOs for every circuit. Short of this, the figures in this section show some useful arrangements. Figure C 10.1 shows a split load consumer unit with single 30 mA RCD. This would be used in both TN-S and TN-C-S systems and provide compliance with the ‘Additional Protection’ requirements of Chapter 41. Figure C 10.2 shows an installation wholly protected with RCDs, a 100 mA main switch RCD incorporating a time delay and a secondary 30 mA RCD. This is suitable for TN-S and TN-C-S installations, and TT installations (with an insulated consumer unit).
C
84
85
Non RCD
30 mA RCD
30 mA
30mA Protected
All other Socket outlets Bathroom circuits
Figure C 10.1 ‘Split load’ consumer unit with single 30 mA RCD suitable for TN-S and TN-C-S systems.
Standard main switch
Supply
Lighting Smoke Alarm Cooker Central Heating Freezer socket
Circuitry and Related Parts of BS 7671: 2008
C
C
86 100mA
100mA Protected
30mA RCD
30mA
30mA Protected
All other Socket outlets Bathroom circuits
Figure C 10.2â&#x20AC;&#x201A; Consumer unit with main switch time-delayed RCD and secondary RCD suitable for TN-S, TN-C-S and TT systems.
Main Switch with100mA S-type time delay RCD
Supply
Lighting Cooker Central Heating Freezer socket
Guide to the Wiring Regulations
Circuitry and Related Parts of BS 7671: 2008
C 11 Ring and radial final circuits C 11.1 Introduction BS 7671: 2008 provides some basic guidance on ring and radial final circuits. This information is included within Appendix 15 of BS 7671: 2008, the diagrams of which are reproduced in this section with kind permission of the IET.
C 11.2 Ring final circuits Rings must comply with Regulation 433.1.4, which is as follows: 433.1.4 Accessories to BS 1363 may be supplied through a ring final circuit, with or without unfused spurs, protected by a 30 A or 32 A protective device complying with BS 88–2.2, BS 88–6, BS 1361, BS 3036, BS EN 60898, BS EN 60947–2 or BS EN 61009–1 (RCBO). The circuit shall be wired with copper conductors having line and neutral conductors with a minimum cross-sectional area of 2.5 mm2 except for two-core mineral insulated cables complying with BS EN 60702–1, for which the minimum cross-sectional area is 1.5 mm2. Such circuits are deemed to meet the requirements of Regulation 433.1.1 if the current-carrying capacity (Iz) of the cable is not less than 20 A and if, under the intended conditions of use, the load current in any part of the circuit is unlikely to exceed for long periods the current-carrying capacity (Iz) of the cable. Recommendations on how to achieve this are as follows, noting that this advice may differ from that in Appendix 15 of BS767: 2008:
•• •
For commercial and industrial installations radials are preferred. Large fixed loads (2 kW and above) should not be connected near the ‘ends’ of a 32 A ring. Kitchen appliances should preferably be supplied via dedicated radials or rings.
Figure C 11.1 is based upon that in Appendix 15 of BS 7671: 2008.
87
C
Guide to the Wiring Regulations
2.5mm 2
2.5mm 2
Unfused spur An unfused spur should feed one single or one twin socket-outlet only. An unfused spur may be connected to the origin of the circuit in the distribution board. 2.5mm 2
1.5mm2
A ring final circuit starts and finishes at the distribution board, where it is connected to a 30A or 32A overcurrent protective device. Note: Consideration must be given to the need for additional protection by an RCD in accordance with Regulation 411.3.3 and Regulations 522.6.6 to 522.6.8
1.5mm2
Spur using an FCU not connected directly to the ring The number of socket-outlets supplied from a fused connection unit is dependent upon the load characteristics, having taken diversity into account.
2.5mm 2 conductors forming the ring
BS 1363 socket-outlet
1.5mm2
Spur using an FCU connected directly to the ring The number of socket-outlets supplied from a fused connection unit is dependent upon the load characteristics, having taken diversity into account.
Fused connection unit (FCU) supplying fixed equipment
Fixed equipment 2.5mm 2
Figure C 11.1â&#x20AC;&#x201A; Ring final circuit information diagram.
C
88
1.5mm2
Circuitry and Related Parts of BS 7671: 2008
C 11.3 Radial final circuits Figure C 11.2 is based upon that in Appendix 15 of BS 7671:2008.
20A Radial 20A All live conductors 2.5 mm2
BS 1363 socket-outlet
32A Radial 30/32A Live conductors 4.0 mm 2
BS 1363 socket-outlet
Unfused spur An unfused spur run in 2.5 mm 2 cable should feed one single or one twin socket-outlet only. An unfused spur may be connected to the origin of the circuit in the consumer unit.
2.5 mm
2
Spur circuit using an FCU The number of socket-outlets supplied from a fused connection unit is dependent upon the load characteristics having taken diversity into account.
1.5 mm 2
Figure C 11.2â&#x20AC;&#x201A; Radial final circuit information diagram.
89
C
Selection and Erection â&#x20AC;&#x201C; Equipment
D
Selection and Erection â&#x20AC;&#x201C; Equipment D 1
Introduction and fundamentals This chapter on selection and erection of equipment discusses and provides guidance and solutions on what essentially is an equipment area of BS 7671: 2008, and includes a sizeable amount of the Regulations. Consistent with the general philosophy of this book, all areas are amply covered with particular practical guidance on more difficult or contentious areas. The selection of equipment generally is a very important aspect for the designer, but often understated is that the installer selects equipment. In this case the installer is carrying out part-design, and installers should obtain selection advice from their designer unless contracted to do otherwise. The term equipment, as the BS 7671 definition makes clear, relates to all equipment to be utilized in an electrical installation. So as to be clear as to what is included, the BS 7671 definition of electrical equipment is repeated in the box below. Electrical equipment (abbr: equipment). Any item for such purposes as generation, conversion, transmission, distribution or utilization of electrical energy, such as machines, transformers, apparatus, measuring instruments, protective devices, wiring systems, accessories, appliances and luminaires. Fundamental requirements for selecting all equipment It is important to note that the selection and erection requirements of the 17th Edition do not in general repeat requirements within the product standards to which the equipment is made. Instead, BS 7671 addresses equipment so far as selection and equipment within the installation is concerned (Regulation 113.1). When selecting equipment, the following must be considered:
91
D
Guide to the Wiring Regulations
•• ••
compliance with the appropriate product standards; suitability for the anticipated operational conditions; suitability for the anticipated external influences; provision for adequate accessibility for maintenance.
D 2
Compliance with Standards One of the most fundamental rules of the 17th Edition is that equipment shall comply with an acceptable and current equipment Standard. Most equipment will have a specific British Standard or BS EN written for it, and these standards would need to be used for specifying or selecting equipment. However, for many reasons, it may not be possible or desirable to select equipment to an appropriate BS or BS EN Standard, and in these cases alternatives are permissible. In the author’s experience this route is not uncommon as often nonEuropean equipment is more viable; an example here is the prefabricated wiring systems made to IEC or USA Standards. In cases such as this there are two routes to compliance and the flow diagram below provides some further guidance. Firstly, equipment to a foreign national Standard which is based on the corresponding IEC Standard may be used provided that, as the 17th Edition requires: ‘the designer confirms that it provides at least the same degree of safety as equivalent British Standard equipment’. In practice this exercise will usually approach the impossible and, in many cases, a sensible view has to be taken. Some will find this judgement to be unacceptable but it is your responsibility, if you are the designer; you may wish to use only BS EN equipment. Another route applies where you wish to use equipment not covered by a Standard, or where it is used outside of scope, and here the designer must confirm its safety to the 17th Edition. This option is at least achievable. A diagram of how to select a product standard in relation to Section 511 is given in Figure D 2.1. It should now be obvious that selection of equipment is very much dependent upon knowledge of the equipment Standards and, from this aspect, the BSI website is invaluable. This book includes a list of some relevant BS and BS EN standards in Appendix 1.
D
92
Selection and Erection – Equipment
Visualize & formalize specification and functional requirements
Look for BS EN Standard www.bsi-global.com
No
If no BS EN or alternative check IEC standards www.iec.ch
Foreign National standard based upon an IEC standard and check for safety to BS 7671
Yes BS EN product
BS product
Other In many cases other equipment standards need to be used and you need to confirm safety of BS 7671 is maintained Examples: UL USA/Underwriters Laboratory www.ul.com DEFSTAN UK MOD Standards www.dstan.mod.uk IEEE USA Institute of Electrical and Electronic Engineers www.standards.ieee.org CSA Canadian Standards Association - www.csa.ca
No product standard found 1. Look again; there probably is 2. A competent person needs to take a view and record as departure 3. Use alternative equipment
Figure D 2.1 Selection of equipment – Standards flow diagram.
D 3
Identification of conductors Introduction Harmonized cable colours were introduced into BS 7671 in the 2004 Amendment, and transitional arrangements were made. The 17th Edition makes no changes to the regulations on cable identification or to Appendix 7 of BS 7671, which provides details of interfaces with existing installations.
93
D
Guide to the Wiring Regulations
D 3.1
Principle of required identification (514.3.1) It is most important to understand the principle behind the drafting of the 17th Edition in respect of cable identification. Cable cores shall be identifiable at their terminations either by colour or by alphanumeric characters. While this has not changed from the 16th Edition it is worth discussing the principles. It is noted that cores should preferably be identifiable throughout their length. For many applications coloured cables, either single- or multicore, will be used and these cables are obviously identified throughout their length. However, in many other applications installers will need to make use of this Regulation (514.3.1) for overmarking at terminations. The principles and applications of identification are now discussed with the use of diagrams. Figure D 3.1 shows the principle of identification where colours are used, i.e. marking by colour at all terminations and preferably throughout the length. In Figure D 3.1 marking throughout the length is not used and single core cables have been used. It should be noted that the colour of the cables originally used is not important and overmarking by tape or similar takes precedence. Building on this principle, Figure D 3.2 shows the principle of identification where alphanumeric identification is used. It is perhaps more obvious now that marking throughout the length is not necessary. It should be noted that the colour of the cables originally used is not important and overmarking takes precedence. This principle holds whatever the colour of cores of the original cable, and applies at terminations by coloured tapes or by characters.
Termination
Termination
Figure D 3.1â&#x20AC;&#x201A; Principle of colour identification.
D
94
Selection and Erection – Equipment
LI
L1
L2
L2
L3
L3
N
N E
E
Termination
Termination
Figure D 3.2 Principle of identification by characters.
In summary, an important principle is established in that, wherever marking at terminations by either tapes, lettering or numbering is used, the original cable colours must be ignored; this can be against your gut feeling but you must get used to it! Common examples and applications where identification is only practised at terminations include the following:
•• ••
Multicore cables with more than five cores. MICC cables. Control applications wired in single-core conductors. Applications where coloured cable is not available, including connections to large generators or transformers, where often only black cable is available.
It should now be established that installers may wish to use any single cable colour, or combination of colours, and overmark at terminations, and this is not considered a lesser option. For green-and-yellow conductors in multicore cables, overmarking in another colour at terminations is permitted. Overmarking at terminations is prohibited for single-core green-and-yellow conductors. The general principles are now discussed further and some applications are included.
D 3.2
Identification by colour Where colour is used to comply with the method of identification, Table 51 from BS 7671: 2008 gives the colour options.
95
D
Guide to the Wiring Regulations Table 51 Identification of conductors (from BS 7671: 2008). Function
Alphanumeric
Colour
Protective conductor
Green-and-yellow
Functional earthing conductor
Cream
a.c. power circuit
3
Line of single-phase circuit
L
Brown
Neutral of single- or three-phase circuit
N
Blue
Line 1 of three-phase circuit
L1
Brown
Line 2 of three-phase circuit
L2
Black
Line 3 of three-phase circuit
L3
Grey
Positive of two-wire circuit
L+
Brown
Negative of two-wire circuit
L–
Grey
L+
Brown
M
Blue
M
Blue
L–
Grey
Outer positive of two-wire circuit derived from three-wire system
L+
Brown
Outer negative of two-wire circuit derived from three-wire system
L
Grey
Positive of three-wire circuit
L+
Brown
M
Blue
L–
Grey
Line conductor
L
Brown, Black, Red, Orange, Yellow, Violet, Grey, White, Pink, Turquoise
Neutral or mid-wire 2
N or M
Blue
Two-wire unearthed d.c. power circuit
Two-wire earthed d.c. power circuit Positive (of negative earthed) circuit Negative (of negative earthed) circuit Positive (of positive earthed) circuit
4
4
Negative (of positive earthed) circuit Three-wire d.c. power circuit
Mid-wire of three-wire circuit
1,4
Negative of three-wire circuit Control circuits, ELV and other applications
Only the middle wire of three-wire circuits may be earthed. An earthed PELV conductor is blue. 3 Power circuits include lighting circuits. 4 M identifies either the middle wire of a three-wire d.c. circuit, or the earthed conductor of a two-wire earthed d.c. circuit. 1 2
Following the principles of the Regulations, it should be stressed that the alphanumeric column was added to Table 51 for reference and if the colour option is used, these are not required.
D
96
Selection and Erection – Equipment
Control circuits, ELV and other applications It should be noted that in the last part of Table 51 ‘Control circuits, ELV and other applications’ the use of other cable colours is allowed for these particular applications. This can be for any application where the general standard power colours are not preferred. An example of where this would be used would be a lock-stop button control cable, where it is desired to use, say, violet as a colour. It should be noted that additional termination marking (by colour or characters) would not be necessary (the information relating to violet as a colour for the lockstop cable would normally be contained on schedules or schematic diagrams).
D 3.3
Identification by marking Colour identification does not have to be used, and of course sometimes cannot be used, for example when using MICC cables. In these cases, or where the designer or installer simply does not prefer colour, identification by marking at terminations is used. Section 514 of BS 7671: 2008 allows you the flexibility to select an identification system that works for you and the application. This may either be the alphanumeric identification of Table 51 or can be by numbering (514.5.4). Numbering may be the preferred method of identification; for example, multicore armoured termination kits. Take a 27-core armoured cable. The cores are numbered from 0 to 26; in the installation, a number of these may be used for neutrals and others used for earths (514.5.4 states that the number 0 should be used for the neutral). They are all coloured black. Normally, to satisfy other parts of BS 7671, a suitable wiring diagram or equivalent will be required, indicating the use of the numbers (unless there is no possibility of confusion).
D 3.4
Additions and alterations – identification Where pre-2004 harmonized cable colours (generally red, yellow, blue and black) and harmonized colours (generally brown, black, grey and blue) are used in the same installation, the following label must be applied at the relevant distribution boards or items of switchgear as appropriate. CAUTION: This installation has wiring colours to two versions of BS 7671. Great care should be taken before undertaking extension, alteration or repair that all conductors are correctly identified. It should be noted that this label need not be applied at all other points on circuits, only at the point of the circuits most likely to be used for isolation in the future, most commonly the distribution boards or items of switchgear.
97
D
Guide to the Wiring Regulations
D 3.5
Interface marking When harmonized cable colours were introduced into BS 7671 in the 2004 Amendment, a new Appendix 7 was included detailing best practice for marking between pre-harmonized and harmonized colours. This appendix is reproduced in the 17th Edition. The 17th Edition requires that termination overmarking is applied â&#x20AC;&#x2DC;except where there is no possibility of confusionâ&#x20AC;&#x2122; at interfaces (the interface is the joint between pre-harmonized and harmonized). In practice, the installer will need to learn the principle and apply it accordingly, but no marking is required for most single-phase correctly coloured interfaces â&#x20AC;&#x201C; see Figure D 3.3. For three-phase applications, Appendix 7 of BS 7671 suggests applying L1, L2, L3 and N at interfaces, again, where there is no possibility of confusion. The requirements are illustrated for some typical three-phase installation interfaces. There are examples when interface marking will not be required, but the decision is for the installer, and if you are uncomfortable with interpretation it is recommended that you always apply the interface marking. However, there are of course applications where interface marking is not required, as per the Figure D 3.4.
D 3.6
d.c. identification d.c. colour or alphanumeric identification is given in Table 51 within the 17th Edition, and both the colours and alphanumeric specified have caused some heartache since they were introduced in the 2004 Amendment. Many engineers feel that the d.c. colours specified in the 17th Edition are inappropriate; this is a classic area where, if it is felt that existing practice of colours is less confusing, a departure is made with an appropriate note recorded on the completion certificate.
D
98
99
Figure D 3.3 Typical extension interface marking.
Existing Switchgear e.g. Busbar
New L2 load
New L1 load
Not Required
Not Required
At Switchgear
At Switchgear
At Switchgear
Mark browns with L1, L2,L3 & Neutral conductor with N at load and preferably at switchgear
NOTES: All single core circuits like these ‘tap-offs’ shall be in Brown phase conductors (applies to main, sub-main & final circuits), where colour is used.
New L3 load
New three phase load
At Switchgear
General Warning Label Required
Not Required
Interface Marking Required
Selection and Erection – Equipment
D
D
100
Figure D 3.4 New installation interface identification.
Existing Switchgear e.g. Busbar
New L2 load
New L1 load
Not Required
Not Required
Browns to be marked L1,L2,L3
NOTES: All single core circuits like these ‘tap-offs’ shall be in Brown phase conductors (applies to main, sub-main & final circuits), where colour is used.
New L3 load
New three phase load
Not Required
Interface Marking
Guide to the Wiring Regulations
Selection and Erection – Equipment
D 4
EMC and prevention of mutual detrimental influences
D 4.1
Introduction The Wiring Regulations have for a number of years included basic regulations for electromagnetic compatibility (EMC), regulations about separating system voltages and also regulations about the rather cumbersome title of ‘preventing mutual detrimental influences’. These topics are all discussed in this section as many of the recommendations overlap. BS 7671: 2008 has a number of regulations to take note of as follows:
••
Section 528 – proximity to other cables, equipment. Part 515 EMC.
Let’s first look at proximity; Regulation 528.2 requires that ELV and LV circuits shall not be in the same containment unless insulated for the highest voltage present. This applies to cables on cable tray as well as within conduit, trunking and ducting. Of course, this insulation requirement is not required where compartments physically separate the cables.
D 4.2
EMC directive and BS 7671 Previously, the EMC directive did not specifically mention installations, but the recent revision to the directive now states installations are not exempt from the legislation. This section provides brief guidance on complying with the EMC directive and EMC requirements of BS 7671: 2008. The directive and official guidance indicates that best practice is followed, and cites HD 60384, the European harmonization document upon which BS 7671: 2008 is based. Regulation 515.3 states that equipment shall be chosen with suitable immunity and emission levels. The EMC directive Regulations and various guidance documents can be found on the DTI website, and this also provides links for supporting informative EMC documents as well as a link to the EU Commission website. All main documents and guides on these sites were, at the time of writing, free of charge. So, what is the impact and what advice can be provided to installation designers and installers? Three key points of action are required:
101
D
Guide to the Wiring Regulations
1 Equipment should preferably be to BS EN standards. Immunity and emission are written into standards and, irrespective of this, manufacturers have an obligation to manufacture to the EU EMC levels. If you need to use equipment to a different standard it is a good idea to obtain confirmation that equivalent immunity and emission has been achieved. It is important to note that it is the EU retailer who has the duty to confirm this (e.g. the importer). This is not always as difficult as it sounds, as Standards like the USA’s FCC rules are both stringent and well documented. 2 Design and install circuits and equipment to ‘best practice’. This means to BS 7671 and other recommended guides. At the time of writing, a new section (444) was being drafted by the Wiring Regulations committee and is likely to include new regulations and some guidance on this subject. 3 Formalize documentation. It is perhaps even more important now to formalize the storage of the project’s technical design and installation information. By completing these three actions, designers and installers will have fulfilled their duties under the EMC directive as well as BS 7671: 2008.
D 4.3
EMC cable separation – power, IT, data and control cables General Firstly it must be stated that the majority of power installations installed to BS 7671 will exhibit no EMC problems between the power system and ‘sensitive’ data type installation. Indeed, it is interesting to note that many data IT installation EMC problems have been discovered to be infringements of BS 7671, particularly poor earthing. In spite of this, the following guidance is recommended where ‘sensitive’ equipment is installed (‘sensitive’ equipment means IT data and communications equipment). Some of the recommendations will have to be balanced against cost and performance. When the requirements for the segregation of sensitive equipment and cables are being considered for an installation, more design and installation information can be found in the series of Standards BS EN 50310, BS EN 50173 and BS EN 50174 Part 1–3. Recommendations – cable separation for sensitive equipment The following optional solutions may be considered to mitigate the effects of EMC on sensitive equipment:
D
102
Selection and Erection – Equipment
•• ••
separate power transformers as Figure D 4.1; size neutral for unbalanced load and triple harmonic currents1; balance loads; in extreme cases, oversizing the power transformer to lower the source impedance.
1
The subject of harmonic assessments is covered in Chapter C.
Composite Transformer
Power Distribution Equipment Sensitive Equipment
Arrangement A - Not recommended
Power Distribution Equipment
Sensitive Equipment
Arrangement B - Recommended
Figure D 4.1 Segregated distribution transformers for sensitive equipment installations.
103
D
Guide to the Wiring Regulations
The following points are also recommended to prevent the electricity distribution systems adversely influencing sensitive equipment. There will be practical limits to most of the options, and compromises will often be necessary: 1 A physical distance-based separation between potential sources of interference, e.g. lifts, power transformers, variable speed drives, high current busbars or HV equipment. 2 Metal pipes such as water, gas, heating and cables should enter the building at the same location as the electrical power cable and be connected to the main equipotential bonding system at this point. 3 A common route through the building for power and signal cables will avoid large inductive loops formed by different cabling systems. 4 The necessary separation between power and information technology cables by distance or by screening should be provided. Separation distances are found in Table D 4.1. 5 Power and information technology cables should cross over at right angles. 6 Power cabling systems that use single-core conductors should ideally be enclosed in earthed metallic enclosures or conduits. The separation distances given in Table D 4.1 are for backbone cabling from end to end. However, for horizontal cabling where the final circuit length is less than 35 metres no separation is required in the case of screened cabling.
Table D 4.1 Recommended cable separation distances. Type of installation
Minimum separation distance Without divider or non-metallic divider¹
Aluminium divider
Steel divider
Unscreened power cable and unscreened IT cable
200 mm
100 mm
50 mm
Unscreened power cable and screened IT cable²
50 mm
20 mm
5 mm
Screened power cable and unscreened IT cable
30 mm
10 mm
2 mm
Screened power cable and screened IT cable²
0 mm
0 mm
Separation by distance or by screening
1 It is assumed that in case of metallic divider, the design of the cable management system will achieve a screening attenuation related to the material used for the divider. 2 The screened IT cables shall comply with EN 50288 series.
D
104
Selection and Erection â&#x20AC;&#x201C; Equipment
Cable 2
Cable 1
Cabinet
Outlet
L If length L
35m, no separation is required
Figure D 4.2â&#x20AC;&#x201A; Schematic of length and required separation recommendations.
For lengths greater than 35 metres, the separation shall apply to the full length, excluding the final 15 metres before it is attached to the outlet (see Figure D 4.2).
D 4.4
Cable management and EMC Some metallic cable management products offer an improved protection from electromagnetic emissions (EMI). Plastic cable management systems can also offer some protection but are only recommended where the system has a low emission level, or where optical fibre cabling is used. Figure D 4.3 illustrates recommended cable layouts within cable management products. Where metallic system components are used, the shape (flat, U-shape, tube, etc.) will determine the characteristic impedance of the cable management system. Enclosed shapes, by reducing the common mode coupling, offer the best profile.
105
D
Guide to the Wiring Regulations
Not recommended
Preferred- Best Power cabling
Auxiliary
Correct
IT cabling
Power cabling
Sensitive circuits
Auxiliary circuits (e.g. fire alarm, door opener) IT cabling Sensitive circuits (e.g. for measurement or instrumentation)
Figure D 4.3â&#x20AC;&#x201A; Cable separation within cable management systems.
D 5
Wiring systems
D 5.1
The choice of wiring systems The choice of wiring system will depend on a number of factors that the installation designer will need to consider, depending on the particular type of installation, its use, the environment and also any economic constraints. In order to achieve compliance with BS 7671, it is important to select a type of wiring system complying with the appropriate product standard, as previously mentioned in Section D 2.
D
106
Selection and Erection – Equipment
The selection of an appropriate wiring system can be represented as a balancing act between specification, cost and time, as depicted in the balance triangle below:
Spec’/Quality
t flic
Co nf lic
t
n Co
Cable Type
Cost
Conflict
Time (Speed)
The balance of any one of the three selection parameters is in conflict with the other two, and in selecting any one cable type, compromises will need to be made. Maintenance considerations are not shown on this diagram but should be considered under the specification parameter. The complex criteria of specification will be very much affected by environmental factors and the use by operators. With this in mind, the following points will need to be considered in the specification parameter:
•• •• •• ••
type of installation, domestic/commercial/industrial and impact protection; temperature of installation and local heat sources; effects of dust and water; effects of chemicals, fumes and gases; animals including vermin; movement and mechanical vibrations; corrosion including electrolytic corrosion; other environmental factors including wind, seismic effects, solar radiation, hygiene and mould growth.
This list is not exhaustive, and experience and knowledge are key factors in selecting the wiring system.
107
D
Guide to the Wiring Regulations
A key 17th Edition regulation in cable selection is the mechanical protection, or impact protection, as required under the 522.6 group of regulations. A concealed cable installed within 50 mm of the surface of a building fabric (shallow) needs careful consideration as listed in 522.6.5, 522.6.6, 522.6.7 and 522.6.8. The principle of these regulations is as follows:
••
the running of concealed cables in zones ‘deemed to be safe’; or, mechanical protection or ‘earthed metallic’ protection.
The permitted cable zones are indicated in Figure D 5.1. Two additional regulations have been added in BS 7671: 2008 to the 522.6 ‘concealed cable protection’ group of regulations as follows:
•
522.6.7 requires a 30 mA RCD for cables less than 50 mm deep run in the ‘safe zones’ where the installation is not intended to be under the supervision of a skilled or instructed person, and where the cable is not mechanically protected or not within earthed metallic enclosures. 522.6.8 requires a 30 mA RCD for cables of any depth concealed within metal partitions where the installation is not under the supervision of a skilled or instructed person, and is not mechanically protected, run in zones or within earthed metallic enclosures.
•
Generally, these applications ‘not under the supervision of a skilled or instructed person’ include domestic installations and parts of an installation where members of the public may use socket outlets (e.g. internet cafés). To save repetition, for interpretation on where to use RCDs and the extent to which instructed or skilled persons are included, see Section D 7.1. To comply with 522.6 it should be noted that not all cables have to be installed in ‘heavy-duty conduit’. As an example, cables to BS 8436, which are soft or semirigid cables incorporating an aluminium screen, can provide a solution. This relatively new cable has a screen that is in contact with a bare cpc, negating the need for special ‘earthing’ glands, and may be a solution in some cases. Where unsheathed cables are to be used, the ‘earthed metallic’ enclosures include:
•• ••
steel conduit; flexible steel conduit; steel trunking; steel underfloor trunking.
D
108
Zone
Figure D 5.1 Cable ‘safe’ zones.
Key
150 mm
150 mm
Cables run here are not in zone
Selection and Erection – Equipment
109
D
Guide to the Wiring Regulations
D 5.2
Circulating currents and eddy currents in single-core installations Regulations 521.5.2 and 523.10 give requirements concerning ferrous enclosures and single-core armoured cables with respect to eddy currents and circulating currents. While 521.5.2 stipulates that steel wire armoured cables shall not be used with a.c. circuits there are other pitfalls in selecting alternative cables. Single-conductor non-ferrous metal sheathed or armoured cables need careful consideration due to the problems of sheath currents and eddy currents. Circulating (sheath) currents Circulating or sheath currents flow in the metal sheaths or armour of single-core cables. All single-core metallic-sheathed cables have a sheath current induced by the a.c. magnetic field surrounding each conductor. The metallic sheaths and armoured cables are often earth-connected to equipment at both ends, providing a closed circuit path through metal gland plates, enclosures and other metallic paths where sheath currents are permitted to flow, as shown in Figure D 5.2. Induced sheath currents cause a heating effect and temperature rise in metal sheaths or armour of single-conductor cables. This is transferred to the cable insulation and,
Sheath / Circulating Current
Figure D 5.2â&#x20AC;&#x201A; Circulating sheath current.
D
110
Selection and Erection – Equipment
depending on the general circuit loading, this additional heat may cause the cable to suffer premature insulation damage. There is no recognized method for an exact calculation of the heating effect of sheath currents and the following options are advised: Mitigating sheath (circulating) currents – option A De-rate the single-conductor cable current rating by a factor of up to 50%. This will have cost and termination constraints, i.e. you may simply not be able to terminate the cable. These cables are often transformer or generator final connections and sizing should be rechecked; it is a fact that in many installations power cables never achieve anything approaching their operating temperature due to overdesign. There are many installations where single core cables are bonded (earthed) at both ends and problems virtually never exist. This is particularly true of the main cables between transformer and switchgear, which in many installations only ever reach a small fraction of their rated current. Whilst this advice may seem perhaps a bit open, ultimately an engineering judgement is required. Mitigating sheath (circulating) currents – option B A second option is providing isolation of the metallic sheath or armour from earth at one end of the cable. This is often achieved by cable termination with a non-metallic gland plate. This is sometimes known as single point bonding. Separate earth cables will be required to maintain the system earthing. To ensure that metallic sheaths or armour are isolated from earthed metal, cables will almost certainly need a non-metallic outer sheath covering. This will ensure that sheath currents will not flow spuriously due to contact with metallic parts such as cable trays, racks or structural steel. Due to the possibility that isolation is not always maintained, option A might be preferred. If this method is being used, it is recommended to limit the longitudinal voltage to 25 volts for corrosion and safety reasons. This is estimated using the following rule of thumb: For trefoil cables, voltage = 0.05 mV/A/m. For flat formation, voltage = 0.125 mV/A/m.
Eddy currents The same magnetic fields that surround single-conductor cables can also produce eddy currents in the steel enclosures, which completely surround the cables.
111
D
Guide to the Wiring Regulations
Magnetic Flux
Eddy Current Flow
Current Flow
Current Flow
Figure D 5.3â&#x20AC;&#x201A; Eddy current in a metallic gland plate.
Figure D 5.3 shows how and where eddy currents are created at a metallic gland plate. Eddy currents can overheat iron or steel cabinets, locknuts or bushings or any ferrous metal that completely encircles the single-conductor cables. This presents no problem in multi-Âconductor cables, where the magnetic fields tend to cancel each other out. For single-core cables, it is recommended that these cables enter metal enclosures through a non-ferrous plate (e.g. aluminium). Any connectors, glands and similar that completely surround the conductors must be of nonferrous materials. Slotting the equipment enclosure between the cable openings was considered an acceptable way to reduce the effects of eddy currents, but is no longer common practice (some feel that the practice of slotting weakens equipment).
D 5.3
Electrical connections and joints D 5.3.1 General A typical installation comprises a multitude of joints and connections, both in conductors and in wiring containment systems. As is seen from reading other chapters of this book, the soundness of connections is crucial, and loose or
D
112
Selection and Erection – Equipment
partially loose connections can cause all sorts of problems, including overheating and possibly fire. It is imperative that such connections are made in such a way as to provide for durable electrical continuity and low resistance. It is important that connections in both live conductors (phase and neutral) exhibit adequate mechanical strength and continuity to allow the current-using equipment of the circuit concerned to function as intended. For protective conductors it is perhaps just as important that such connections are soundly made, because poor connections will remain undetected until the time of a possible earth fault. The correct tightness of connections is essential to avoid particular risks from fire or other harmful thermal effects, such as:
• ••
Excessive temperature developed in a high resistance connection when it carries current (e.g. load current or short-circuit current). Arcs or high temperature particles emitted from a loose connection. Poor connections giving rise to the risk of electric shock due to a malfunction of the protective measure of fault protection. A high resistance or open circuit in a protective conductor affecting the earth fault loop impedance may prevent automatic disconnection. Subsequent contact of a person or livestock with an exposed-conductive-part could be hazardous.
For the above considerations, BS 7671 makes a number of requirements concerning the construction of electrical connections and the workmanship necessary in carrying out such connections. All connections between conductors and between conductors and other equipment, such as current-using equipment, accessories or switchgear, are required to provide for durable electrical continuity and adequate mechanical strength (Regulation 526.1). When selecting a suitable connection, BS 7671 requires the designer to take account of a number of factors (taken directly from Regulation 526.2), as appropriate:
•• •• •
the material of the conductor and its insulation; the number and shape of the wires forming the conductor; the cross-sectional area of the conductor; the number of conductors to be connected together; the temperature attained at the terminals in normal service such that the effectiveness of the insulation of the conductors connected to them is not impaired;
113
D
Guide to the Wiring Regulations
• •
the provision of adequate locking arrangements in situations subject to vibration or thermal cycling; where a soldered connection is used the design shall take account of creep, mechanical stress and temperature rise under fault conditions.
Equipment may come with the following lettering on connection terminals:
•• •
‘R’ signifies that the terminal is suitable to accept only a rigid conductor. ‘F’ signifies that the terminal is suitable to accept only a flexible conductor. ‘S’ or ‘Sol’ signifies that the terminal is suitable to accept only a solid conductor.
Terminals without these markings are suitable to accept cables of any type. D 5.3.2 Compression joints Compression joints and connections are used extensively to make connections for terminating small copper conductors, and for large copper and aluminium conductors. The use of compression tools generally provides a simple and quick way of making terminations compared with other methods. However, to make a satisfactory termination with a compression tool, care must be taken to select the correct tool so as to:
••
match the lug (or other connector) to the conductor; and match the compression tool to the lug.
Generally, is it better to choose a lug and compression tool from the same manufacturer and range to ensure compatibility. The matching of cable diameter to lug size is critical and careful inspection of manufacturers’ compatibility data is required as the cable overall diameters can vary. Where the lug and conductor are not compatible, or where the lug and compression tool do not match or are of different manufacture, problems may occur. In the case of a lug and conductor mismatch, attempts to solve the problem by, for example, ‘filling’ the lug with additional copper strands is not acceptable. D 5.3.3 Galvanic (electrolytic) corrosion between metals Where certain dissimilar metals are placed in contact with each other, precautions should be taken to prevent galvanic (also called electrolytic or dissimilar metal) corrosion.
D
114
Selection and Erection – Equipment
There are two conditions that cause this corrosion and both need to exist for it to take place. Firstly, there have to be two different metals present, and these need to have different atomic properties; this is quantified by the metals’ anodic indices. Table D 5.2 shows the anodic indices for metals used in electrical installation engineering. Secondly, there must be an electrical conductive path between the metals. The amount of conduction depends upon water or humidity content as well as chemical presence. To make things a little easier, Table D 5.1 details recommended maximum differences in anodic indices for different environments. Table D 5.1 is used with anodic indices of metals specified in electrical installation engineering, given in Table D 5.2.
Table D 5.1 Recommended anodic difference for certain environments. Environment type
Recommended maximum difference in anodic index (V)
Typical example environments
Normal indoor
0.51
All heated non-damp buildings, air conditioned buildings, humidity controlled buildings and structures
Unheated buildings
0.25
Non-humidity controlled warehouses, unheated buildings such as churches and barns, etc.
Outdoor and harsh installations
0.15
Outdoor installations, ‘salty’ indoor environments, high humidity or moisture
1 Note that the figure of 0.5 for indoor installations is a design value and there are many installations with metals coupled with anodic differences of 0.7 and 1.0 that show no signs of corrosion after many years of service.
Table D 5.2 Anodic index of common metals. Metals
Anodic index (V)
Nickel
0.30
Copper, silver solder
0.35
Brass, bronze
0.35
Chromium
0.5
Tin, lead tin solder
0.65
Iron and steels
0.85
Aluminium
0.9
Zinc
1.25
115
D
Guide to the Wiring Regulations
A remedy for making a connection is often plating the metal. For example, as can be seen, copper can be mated indoors with steel or tin (difference of 0.5V and 0.3V respectively). If aluminium needs to be connected indoors to brass or copper, the anodic difference is 0.55; a solution is to ‘tin’ either the brass or copper which reduces the anodic difference to 0.25. D 5.3.4 Accessibility of connections Every connection between conductors, and between a conductor and an item of current-using equipment, is required to be accessible. This is required in order that inspection, testing and maintenance work can be undertaken during the lifetime of the installation. However, there are certain exceptions permitted by Regulation 526–3 where this requirement can be relaxed, such as:
•• ••
a compound-filled or encapsulated joint; a connection between a cold tail and a heating element (e.g. a ceiling and floor heating system, a pipe trace-heating system); a joint made by welding, soldering, brazing or compression tool; a joint forming part of the equipment complying with the appropriate product standard.
D 5.3.5 Temperature of connections Generally, the temperature of connections is not normally an issue where good workmanship and good materials are used. However, there are some circumstances where the temperature attained is of concern. For example, this would be the case of a connection of a conductor insulated with PVC (70°C) to a busbar which is rated for a maximum operating temperature of 90°C, and which is to operate at that temperature. Without measures to address the problem, the insulation will be impaired (Regulation 526.4). A solution would be to strip back the insulation to a point where the temperature of 70°C is not exceeded. Depending on the temperature gradient, the stripping back of, say, 150 mm of the PVC insulation and replacing it with suitable heat-resisting insulation would solve the problem. For connections to luminaires, a new section has been added to BS 7671: 2008, Section 559, see D 14. D 5.3.6 Enclosures of connections of live conductors Connections and joints in live conductors (and in a PEN conductor) are required to be made within one of the enclosures (or a combination of) identified in Regulation 526.5 as follows:
D
116
Selection and Erection – Equipment
•• •
a suitable accessory complying with the appropriate product standard; an equipment enclosure complying with the appropriate product standard; an enclosure partially formed or completed with building material which is non-combustible when tested to BS 476–4.
An enclosure used to contain connections or joints is required to exhibit adequate mechanical protection and be suitable for the external influences likely to be present (Regulation 526.7). Also, the connections are required not to be subjected to any appreciable mechanical strain, i.e. the conductors must be fixed in the vicinity of the enclosure (Regulation 526.6). Additionally, cores of insulated-only conductors, including those of stripped-back sheathed cables, are required to be contained within the enclosure (Regulation 526.9). D 5.3.7 Connections – Multi, fine and very fine wire Regulation group 526.8 is new for BS 7671: 2008. It requires special treatment of connections of multiwire, fine wire and very fine wire conductors and requires that suitable terminals be used or the conductor ends be suitably treated. Regulation 526.8.2 prohibits the soldering of fine wire conductor ends where screw terminals are used. Soldered conductor ends on fine wire and very fine wire conductors are not permitted (Regulation 526.8.3) where relative movement can be expected between soldered and non-soldered parts of the conductor.
D 5.4
Wiring systems – minimizing spread of fire Section 527 deals with minimizing the spread of fire and calls for the wiring systems to be installed such that the building structure is not compromised in terms of performance and fire safety. D 5.4.1 Cable specification The key regulation in Section 527 is 527.1.3, which states that cables should comply with BS EN 60332–1-2. Tests on electric and optical fibre cables under fire conditions. Test for vertical flame propagation for a single insulated wire or cable. Procedure for 1 kW pre-mixed flame. Cables manufactured to this standard (the ‘flame test’ standard) are considered to be suitable for installation without any special precautions.
117
D
Guide to the Wiring Regulations
It should be noted that all BS EN installation cables comply with this standard except butyl rubber flexes and hence these can only be used in short lengths. Alternatively, cables not complying with BS EN 60332–1-2 can be used in cable management products; these should be to one of the following standards:
••
BS EN 61386 Conduit systems for cable management. General requirements. BS EN 500854: Cable trunking and ducting systems for electrical installations.
D 5.4.2 Sealing building penetrations Regulation group 527.2 requires that penetrations made in building fabric should be made good with a material that maintains the fire rating of the surrounding fabric. Furthermore, internal fire sealing is required for metal and non-metal cable containment systems; the only exception is internal sealing of 25 mm diameter and smaller conduits. This requirement has proven to be most costly for organizations that did not price accordingly, so beware. Similarly, sealing which has been disturbed by any alteration work is required to be reinstated as soon as practicable. Under fire conditions, the toxic effects of PVC have long been acknowledged as problematic when considering the effective escape of persons from buildings. The importance of the selection of PVC on an installation is outside the scope of this book as it will depend upon the view of the local authority. However, with the increasing availability of low smoke, halogen-free (LSHF) cables, the designer can choose to limit PVC or not use it at all. Bulk PVC cable installations should not be used in designated fire escape zones. It should be noted that BS 7671: 2008 uses the term ‘thermoplastic’ instead of PVC and ‘thermosetting’ generally for LSHF cables. Examples of cables with low emission of smoke and corrosive gases under fire conditions are the following:
•• ••
non-sheathed single-core thermosetting insulated; armoured thermosetting insulated; elastomer insulated (types C and D only), armoured and non-armoured; mineral insulated (except those served PVC overall) with fittings to BS 6081.
D
118
Selection and Erection – Equipment
Some less common types of cable are given below:
• •• •• •
impregnated paper-insulated aluminium-sheathed (CONSAC) to BS 5593 (often used for PME power supplies); PVC insulated cables for switchgear to BS 6231 (used for switchgear); impregnated paper-insulated lead-sheathed to BS 6480 (used for HV supplies); rubber insulated flexible to BS 6708 (for use in mines and quarries); rubber insulated cables and cords to BS 6726 (used for festoon and temporary supplies); flexible cables to BS 6977 (used for lift installations).
Cables manufactured to other recognized Standards, provided they meet an equivalent degree of safety.
D 5.5
Proximity to other services Section 558 of the Regulations includes a few regulations on the subject of proximity to other services and is covered in this book under Section D 4.
D 6
Circuit breakers
D 6.1
General There is a certain overlap in this chapter with circuit breakers mentioned in Chapter C, which covers the selection of circuit protective devices to co-ordinate with cable sizes. This section reviews the other selection aspects of circuit breakers as well as their operation, and should be read in conjunction with Chapter C. There are many types of circuit breaker available, the most common being the thermal magnetic circuit breaker. The three types of circuit breaker in use are BS EN 60898, BS EN 61009 and BS EN 60947. The 60898 devices generally replace the miniature circuit breaker (MCB). ‘Miniature circuit breaker’ is a deprecated term and these devices should all be called ‘circuit breaker’. To avoid confusion these are referred to in parts of this book either as MCBs or occasionally as ‘60898 devices’.
119
D
Guide to the Wiring Regulations
• •
BS EN 60898: Circuit breakers for overcurrent protection for household and similar installations. These are available in ratings from 6 A to 125 A. They have three different magnetic sensitivities, described in D 6.2 below. BS EN 61009: Residual current circuit breakers with integral overcurrent protection for household and similar uses. These are combined circuit breakers/residual circuit breakers, known as RCBOs. They are generally available in the same range as 60898 devices, with the same overcurrent sensitivities as 60898 devices and residual sensitivities as RCDs. BS EN 60947 circuit breakers replace what were known as MCCBs and air circuit breakers.
•
Most circuit breakers are available in one-, two-, three- and four-pole variations. The two-, three- and four-pole are all additionally available with neutral overload sensing. The basic, important requirement for the co-ordination of circuit breakers with cables and load current, as explained in some detail in Chapter C, is given by the formula: Ib ≤ In ≤ Iz
D 6.2
Operation and characteristics An MCB is a thermo-magnetic device, meaning that it has two methods of circuit interruption. A thermal mechanism, usually a bi-metallic strip, provides protection against moderate overcurrent. The heating action of the current causes the bi-metallic strip to curve and break circuit contact. This method is complemented by a solenoid designed to respond to larger currents. A diagram of an MCB is shown in Figure D 6.1. It should be apparent that the thermal trip has a slow response time and the solenoid trip has a rapid response time. When combined, these devices provide quite a sophisticated protection characteristic profile. The two characteristics are now described.
D
120
Selection and Erection – Equipment
Cable Terminal
Contact
Arc Chamber
Operating Handle
Din Rail Mounting
Coil Assembly
Cable Terminal
Bi-Metal Thermo Element
Figure D 6.1 Internal view of an MCB.
121
D
Guide to the Wiring Regulations
Table D 6.1 BS EN 60898 device thermal characteristics. Current
Desired result
1.13 In
Must not trip within 1 h
1.45 In ≤ 63A
Must trip within 1 h
1.45 x In, > 63A
Must trip within 2 h
2.55 In ≤ 32A
Must trip between 1 and 60 s
2.55 In, > 32A
Must trip between 1 and 120 s
Thermal characteristic The thermal, bi-metallic characteristic is summarized in Table D 6.1. A further co-ordination of the requirement is that of Regulation 433.1.1 (iii) which is: I2 ≤ 1.45 × Iz where I2 is the current that causes operation of the device. By studying Table D 6.1, it can be seen that this requirement is built into the product standard for BS EN 60898 devices and is effectively the calibration of the bi-metallic strip. Magnetic characteristic The maximum rated current available for MCBs is 125 A, and these BS EN 60898 devices are available with different magnetic sensitivities, denoted with a prefix B, C or D accordingly. The different magnetic characteristics of BS EN 60898 circuit breakers are provided in Appendix 3 of BS 7671: 2008, but to illustrate the differences in the magnetic characteristics, Figure D 6.2 shows a comparison of B, C and D types for devices of the same basic rating. A 32 A circuit breaker with type C sensitivity is denoted C32, and it is a requirement of the equipment standard to apply this marking to the device. The stated B, C or D sensitivities each have a minimum current that causes operation, and this is conventionally taken to be operation within 0.1 second; this is conventionally termed instantaneous operation or instantaneous tripping. This minimum time convention is due to the mechanics of the circuit breaker, which will always require a certain minimum time, regardless of current for the trip mechanism to open. This instantaneous tripping time of 0.1 second can be a problem where two devices are required to discriminate, and this is also explained in Chapter C.
D
122
Selection and Erection – Equipment Time(s)
Type B Type C Type D
100
10
1.0
0.1
10
640
160
0.01 50
100
320
1000 Current (A)
Min’ Instantaneous Tripping Current Figure D 6.2 32 A MCB sensitivity characteristics comparison.
Figure D 6.2 shows that in order to achieve instantaneous tripping or tripping at 0.1 s, a 32 A type B breaker requires 160 A, a type C breaker 320 A and a type D breaker 640 A.
123
D
Guide to the Wiring Regulations
Table D 6.2 Circuit breaker (BS EN 60898) selection for inrush current applications. Type
Manufactured magnetic trip setting (× In)
Typical applications
B
3 to 5
General domestic and resistive loads
C
5 to 10
Small motors (a few kW), small transformers fluorescent lighting and most inductive loads
D
10 to 20
DOL motors, large star delta motors, lowpressure sodium discharge lighting, larger transformers, welding machine supplies
Below these threshold currents the thermal mechanism is dominant, and has the same characteristic for all three devices. The magnetic characteristics determine the sensitivity type. Equipment connected or likely to be connected to the circuit must be assessed in terms of likely peak or inrush current (533.2.1). Inrush current is the current that a load draws when the supply is switched on. Values can range from being insignificant (a few times the normal current), 5 to10 times normal current for iron core transformers (e.g. conventional ballastfluorescent luminaires) and up to 20 times normal current for much modern electronic equipment, including the power supplies found in user equipment. While short-lived (often the peak current is a few milliseconds), this can cause circuit breakers to trip, but assessing the likelihood of a circuit breaker tripping is complicated. Table D 6.2 recommends circuit breaker types for typical inrush current applications. Separately to inrush current, load peak current also needs to be considered. Peak current in respect of circuit breaker selection is a term used to describe a peak within the normal operation of a cyclic or time varying load. Part C 3.1 of this book has more information and an example of a cyclic load calculation. If you have loads with significant cyclic peaks you need to confirm that the circuit breaker will not trip. This can be confirmed by studying the circuit breaker characteristic curve, but confirmation with the manufacturer may be necessary.
D 6.3
Ambient temperature de-rating Both BS EN 60898 and BS EN 60947 provide details of de-rating factors for using circuit breakers in ambient temperatures greater that 30°C.
D
124
Selection and Erection – Equipment
In installations where you encounter such temperatures it is best to consult the standards or manufacturers’ data, but the following give an indication of correction factors for 60898 devices up to 100A:
•• •
40°C de-rating factor of 0.85 50°C de-rating factor of 0.75 60°C de-rating factor of 0.65.
Some manufacturers also provide de-rating factors for groups of circuit breakers mounted next to each other where they are all fully loaded. A typical de-rating in such examples would be 0.85, but in practice it is very rare to see such loadings, particularly on more than one circuit.
D 7
Residual current devices
D 7.1
BS 7671 applications BS 7671: 2008 requires the fitting of RCDs as additional protection in more applications compared with the previous editions. RCDs, with a rated operating current of 30 mA, are now required in the following situations:
• •• •
All socket-outlet circuits accessible to ordinary or non-instructed persons (411.3.3). All circuits within a bathroom (701.411.3.3). Concealed cables either less than 50 mm deep, in installations not intended to be under the supervision of a skilled or instructed person, not mechanically protected or protected by earthed metal and not run in the ‘safe zones’. Concealed cables within metal partitions, in installations not intended to be under the supervision of a skilled or instructed person, not mechanically protected or protected by earthed metal and accessible to ordinary or noninstructed persons. Generally where disconnection times cannot be achieved with an overcurrent device. Most TT installations, usually required to achieve a disconnection time of 0.2 s. Other special locations including caravan parks.
• • •
One of the most significant changes in the 17th Edition is the requirement for RCDs to be applied to all socket-outlet circuits accessible to ordinary persons. It is quite important to get the principle of Regulation 411.3.3 clear.
125
D
Guide to the Wiring Regulations
411.3.3 Additional Protection In a.c. systems, additional protection by means of an RCD in accordance with Regulation 415.1 shall be provided for: (i) socket-outlets with a rated current not exceeding 20 A that are for use by ordinary persons and are intended for general use, and (ii) mobile equipment with a current rating not exceeding 32 A for use outdoors. An exception is permitted for: (a) socket outlets for use under the supervision of skilled or instructed persons, e.g. in some commercial or industrial locations, or (b) a specific labelled or otherwise suitably identified socket-outlet provided for connection of a particular item of equipment. Note 1: See also Regulations 314.1(iv) and 531.2.4 concerning the avoidance of unwanted tripping. Note 2: The requirements of Regulation 411.3.3 do not apply to FELV systems according to Regulation 411.7 or reduced low voltage systems according to Regulation 411.8.
Let’s break down the requirement and also describe ordinary, skilled and instructed persons. An ordinary person is a person who is neither skilled nor instructed. A skilled person is one with technical knowledge or sufficient experience to enable him or her to avoid dangers which electricity may create. An instructed person is one adequately advised or supervised by a skilled person to enable him/her to avoid dangers which electricity may create. Applying this to Regulation 433.1.1 (and elements of 522.6.7 and 522.6.8): Domestic installations always involve ordinary persons, and RCDs are required to all socket-outlet circuits. Exceptions can be made for socket outlets for specific purposes, a common example of which would be a domestic freezer circuit. To comply with the spirit some of these socket outlets may need labelling depending upon their location.
D
126
Selection and Erection – Equipment
Commercial installations where individuals are employed come under the Electricity at Work Regulations 1989 (EWR). This is also true of a single employee workplace whatever the nature of the business. EWR requires a safe system of working, and this means that someone in every installation will need to control activities; the operational requirements of installations are made in BS EN 50110: 2004–1: Operation of Electrical Installations. When this requirement is combined with the requirement under EWR for the workplace equipment to be safe and maintained, there is no requirement for employees in the workplace to have socket outlets with additional RCD protection. The designer must assume this to be the case. Falling outside of these two cases are the commercial installations with socket outlets that members of the public can use. These would not be socket outlets in the lobby of a commercial installation, where it is reasonable to assume they will not be used by visitors, but would include, say, socket outlets in internet cafés for plugging in laptops. The designer has options and will need to liaise with the client over supervising or providing instruction to such users or fitting RCDs to socket outlets.
D 7.2
Operation and BS 7671 requirements Operation Residual current devices monitor the instantaneous current flowing along the line and neutral conductors in a circuit by means of a sensitive coil. The coil or ‘core’ measures the instantaneous resulting sum of these currents. When an earth fault or earth leakage is present on a circuit, a small ‘imbalance’ is set up in the detection coil and, at a certain level, causes a trip of the circuit breaker mechanism. A diagrammatic representation of this is shown in Figure D 7.1.
Electrical Equipment (Metal cased)
Supply
Fault L N N E
E
To trip mechanism
Figure D 7.1 Representation of an RCD.
127
D
Guide to the Wiring Regulations
Requirements The requirements for RCDs are set out in Regulation group 531.2 and are summarized in Table D 7.1. Table D 7.1 Requirements for RCDs. Reg No
Requirement
531.2.1
Capable of disconnecting all the line conductors of the circuit at the same time
531.2.2
Magnetic circuit to enclose all live conductors and protective conductor to be outside the magnetic circuit
531.2.3
Residual operating current to comply with the requirements of Section 411 (automatic disconnection)
531.2.4
Selected so any expected protective conductor current will be unlikely to cause unnecessary tripping of the device
531.2.5
Not be considered sufficient for fault protection even if the rated residual operating current does not exceed 30 mA
531.2.6
Where powered from an independent auxiliary source must be fail safe
531.2.7
Not be impaired by magnetic fields caused by other equipment
531.2.8
Where used for fault protection separately from an overcurrent device, must be capable of withstanding thermal and mechanical stresses
531.2.9
Where discrimination is necessary to prevent danger, device characteristics are required so discrimination is achieved
531.2.10
For ordinary persons it shall not be possible to modify or adjust the setting of the device without a tool or key
Most of the above requirements will be achieved automatically as they are incorporated within the relevant product standards. This is not so for the requirements for ‘unwanted tripping’ or discrimination, and these are now discussed.
D 7.3
Unwanted RCD tripping and discrimination Unwanted tripping In order to avoid unwanted tripping, the most important factor of influence is the circuit arrangement. Most modern individual pieces of equipment on a circuit create some amount of earth leakage current and these currents add in the circuit’s protective earth conductor. There is, therefore, a circuit limit to the quantity of connected equipment in terms of the total circuit earth leakage. In order to reduce the risk of unwanted tripping, the circuit should be designed so that the circuit runs with a standing earth leakage of less than 25 % of the rated residual operating current of the RCD.
D
128
Selection and Erection – Equipment
Two common sources of equipment earth leakage are as follows: 1 Earth leakage caused by power supplies, particularly switched mode power supplies. These are used in a considerable amount of modern equipment including computers and televisions, photocopiers etc. A rule of thumb figure of 1 mA leakage per device is recommended for assessment. 2 Heating elements found in washing machines, dishwashers and cookers. A rule of thumb is 3 mA for appliances up to 3 kW and 6 mA for appliances up to 6 kW. For speculative designs and socket-outlet circuits the designer needs to take a view on likely equipment the user will operate. Generally to achieve compliance with Section 543.7 (high protective conductor currents), a maximum of 10 double socket outlets per circuit is recommended. Example: a 30 mA RCD circuit with eight PCs, two televisions and a 3 kW dishwasher (a rather strange mix, granted, but this could be a single RCD in a consumer unit). Based upon the above rules of thumb, the earth leakage would be in the order of 13 mA. Under most circumstances, the RCD would not trip even though this exceeds a good design value of 25%. However, if someone now used a domestic kettle in the circuit, the earth leakage may trip the RCD. This example should serve to illustrate the principle of RCD selection and its effect on circuit design. There are many other factors that may either contribute to or cause unwanted tripping, including inrush currents (see Section D 6.2 for explanation), mains factors such as noise, loose connections, poor insulation of cables of connected equipment and radio frequency interference. There are other causes of unwanted tripping. A relatively rare problem, but one that is worth mentioning, is unwanted tripping that is caused by microwave emissions from mobile cell phones. This can be an issue and exposes a loophole in standardization. It is a valid reason in itself not to install RCDs on safetyof-life critical circuits, along with suitable comments made on the completion certificate. RCD discrimination In order to achieve discrimination between two series-connected residual current devices where required to comply with Regulation 531.2.9, it will be necessary to use a time-delayed residual current device at the upstream position. This will
129
D
Guide to the Wiring Regulations
permit the downstream residual current device to respond to an earth fault on its downstream side and avoid operation of the upstream device.
D 7.4
d.c. issues for RCDs The selection of RCDs in respect of load d.c. components is an issue that is often overlooked by designers. RCDs are classified according to their response to d.c. signals as follows:
•
Type AC This class of device generally only detect sinusoidal alternating residual currents. They may not detect non-sinusoidal, non-alternating residual components. These non-sinusoidal currents are present in many items of equipment, e.g. virtually all equipment with a switched mode power supply will have a d.c. component, as do battery chargers and X-ray machines etc. Type A This class of device will detect residual current of both a.c. and pulsating d.c. and are known as d.c. sensitive RCDs. They cannot be used on steady d.c. loads. Type B This type will detect a.c., pulsating d.c. and steady d.c. residual currents.
• •
RCDs are required to be marked with their type and Table D 7.2 shows the markings and provides selection criteria.
D 7.5
TT installations and RCDs In a TT system the earth fault loop impedance is not usually sufficiently low to facilitate the operation of an overcurrent protective device within the required disconnection time. This is even more the case in BS 7671: 2008 as the disconnection time for TT installations is 0.2 s compared with the 0.4 s required in the previous edition. Where an RCD is used for fault protection, the product of the rated residual current and the sum of the resistances of the installation earth electrode and protective conductors connecting it to exposed-conductive-parts (RA) is required to be not greater than 50 V (Regulation 411.5.3). However, it is also recommended that an earth electrode resistance, where possible, should not exceed 200 Ω (411.5.3 note 2). This is good general advice but is a simplification, as a deep earth electrode, say 4 m deep with resistance of 400 Ω, will be more stable than a 1.2 m electrode with resistance of 50 Ω. For rod electrodes it is vertical depth that should be encouraged.
D
130
Selection and Erection – Equipment
Supply
Sinusoidal A.C.
Form of Residual Current
Recommended type of symbol AC B A
Suddenly applied
Slowly rising
Pulsating D.C.
Suddenly applied
Slowly rising
Smooth D.C.
Figure D 7.2 RCD d.c. selection criteria.
In a TT installation, where a single RCD protects the whole installation, it is essential that the device is placed at the origin of the installation (i.e. adjacent to the electricity meter). The connections and any switchgear between the RCD and the electricity supplier’s meter is required to meet the requirements for protection by the use of Class II equipment or equivalent insulation (531.4.1).
131
D
Guide to the Wiring Regulations
D 8
Other equipment There are a number of regulations grouped under Section 530 listed as protection, isolation, switching, control and monitoring. This section lists the most relevant points; most others do not need commenting on.
D 8.1
Isolation and switching The ECA has always found it disappointing that the subject of isolation and switching was so convoluted to the point that there was a separate IEE guidance note specifically on the subject. A new Table 53 within Chapter 53 answers many questions posed by designers or installers.
D 8.2
Consumer units for domestic installations BS EN 60898 circuit breakers installed in domestic consumer units would not generally comply with Regulation 432.1 where a breaking capacity of 16 kA is quoted. However, a consumer unit that complies with the conditional short-circuit test as described in Annex ZA of BS EN 60439–3 will meet the requirements of the Regulations as compliance with 434.5 is achieved. This means that where a service cut-out fuse to BS 1361 with a rating of maximum 100 A is fitted the switchgear will be safe. This is stated here merely from a specification point of view.
D 8.3
Overvoltage, undervoltage and electromagnetic disturbances Chapter 44 affects the selection of equipment. The chapter has been extensively modified, for the 17th Edition gives requirements for protection against voltage disturbances and electromagnetic disturbances. It considers these disturbances for both internal and externally created disturbances, and is divided into four sections; two are ‘blanks’ for BS 7671: 2008 as follows:
•• • •
Section 441: Reserved for future use. Section 442: Protection of LV installations against HV faults. Section 443: Protection against overvoltages of atmospheric origin or due to switching. Section 444: Measures against electromagnetic influences. At the time of publication this section was being developed by the Wiring Regulations committee and will be published in a future amendment.
D
132
Selection and Erection – Equipment
D 8.3.1 HV – LV faults The new Section 442 sets regulations for installations for supplies taken at high voltage or for where a substation is located on the property of the installation. Section 442 specifies a maximum ‘stress voltage’, which is a fault voltage appearing on the LV earthing system with respect to the local earth potential. However, installations that receive their LV supply from a utility provider do not need to consider this section. Thus, Section 442 can be ignored unless you are installing a private substation. In these cases reference to IEC 61936–1 Power Installations Exceeding 1 kV a.c. will provide methods of complying with the HV/LV co-ordination aspects. D 8.3.2 Atmospheric and switching overvoltages Like many parts of the Regulations, there is often confusion when reading a section, only to discover later that most of the text is not applicable. Section 443 is a classic case of this and is explained as follows:
•
No action will be required for UK installations as installations will be in areas where thunderstorms occur less than 25 days per year.
It is noted that equipment will need to have voltage impulse withstand levels as specified in Table 44.3, but all equipment to BS EN standards will comply with this. For installations overseas in areas of high lightning strike locations, surge protection is required (alternatively a risk assessment may be carried out). D 8.3.3 Undervoltage Although not new, the regulations under Section 445 required an undervoltage detection relay with appropriate resetting for installations where a sudden re-energized state could lead to danger. Common examples of these installations are machinery workshops and similar plants, and there are various standards to consider, the subject of which is outside the scope of this book.
D 8.4
Surge protective devices Although not required in the UK by Section 443 (see Section D 8.3.2), surge protective devices (SPDs) may optionally be specified. If you are the designer you may feel that they add a certain security to an installation. SPD selection and installation comes down to a few simple rules, summarized as follows:
133
D
Guide to the Wiring Regulations
•• •
Choose SPDs complying with IEC 61643 series. In TN-C-S installations connect device between line conductors and earth. In TN-S and TT installations connect device between line conductors and both neutral and earth.
Figures D 8.1, D 8.2 and D 8.3 show typical SPD connections in mains positions of various supply earthing arrangements.
Incoming Supply Terminals
Main Distribution Board
Supply L
L
N
N
SPD Device
E
Figure D 8.1 Connection of SPD in TN-C-S system (PME).
Incoming Supply Terminals Supply
Main Distribution Board
L
L
N
N E
Installation Earth Electrode Figure D 8.2 Connection of SPD in TT system.
D
134
SPD Device
Selection and Erection – Equipment
Incoming Supply Terminals
Main Distribution Board
Supply L
L
N
N
E
E
SPD Device
Figure D 8.3 Connection of SPD in TN-S system.
The length of conductors connecting the SPDs is a factor that should be controlled due to the magnitude of both current and voltage when the devices operate, and it is recommended that connecting tails are limited to a length of 0.5 m.
D 8.5
Insulation monitoring devices (IMDs) Most of BS 7671: 2008’s rules (538.1) for insulation monitoring devices (IMDs) cover their use in IT systems (e.g. for first fault conditions). This is a rare and specialist area and is beyond the scope of this book. Some limited information can be found in BS EN 61557–8.
D 8.6
Residual current monitors (RCMs) Still a relatively rare device, the residual current monitor (RCM) is similar to RCDs (see D 7.2), but instead of tripping a circuit, monitoring is provided. The monitoring can be visual or, at a pre-determined value of residual current, it can create an audible signal or a signal for remote monitoring. RCMs are useful devices in main distribution panels, and in this configuration monitor several circuits at once. In a larger installation a three-phase RCM device positioned in the main distribution board will be extremely useful. These devices can be widely used and Figure D 8.4 indicates examples of where RCMs are used in mains, riser and final distribution board positions.
135
D
Guide to the Wiring Regulations
Floor RCM
Single phase shown for clarity
PE
N
L
Main panel RCM
Riser RCM
N Figure D 8.4â&#x20AC;&#x201A; Application examples of residual current monitors.
D
136
L1
L2
L3
Selection and Erection – Equipment
The following pattern has been experienced by the author in several large installations (load of a few MW) and has been provided here for information for those wishing to use the devices for the first time:
• • • •
When setting the RCM, a general standing residual current will be established; this may involve considerable fault finding for faults previously undetected. At certain times the residual current will probably suddenly go high; this will often be due to equipment faults, particularly neutral earth faults which remain undetected by overcurrent devices. For tracing faults, isolation of sub-boards is the easiest method, but is subject to isolation of large parts of the installation. Where this is not possible the use of clamp-on earth leakage current probe testers will be necessary. For tracing faults, user equipment should be subjected to its daily or weekly cyclic run mode.
To serve as an example: a 2 MW installation may have 4 A of ‘normal’ residual current, fluctuating most days between 3 and 5 A. Suddenly the earth leakage current rises to about 15 A. This may be attributed to a neutral earth fault, present on a lighting circuit or similar. For smaller installations, some limited information on the devices can be found in BS EN 62020: Electrical accessories – Residual current monitors for household and similar uses (RCMs).
D 9
Generating sets Section 551 was introduced in the 2001 edition of BS 7671 and has only had limited modification for the 17th Edition. It is key to recognize the definition of ‘generating set’ within the scope of Section 551, as it applies to more than just ‘diesel’ generators. ‘Generating set’ applies to any power source other than the incoming or main supply, including:
•• ••
combustion engines e.g. diesel sets; electromotive generators e.g. wind turbines, water mill turbines; photovoltaic cells; electrochemical accumulators e.g. battery back-up cells.
The key regulations of this section are as in Table D 9.1.
137
D
Guide to the Wiring Regulations
Table D 9.1 Requirements for ‘generating sets’. Voltage/frequency shall not cause damage or danger
551.2.3
RCDs in circuit remain effective
551.4.2
Fault protection (disconnection times) of system must work with various combinations of supply
551.4
Standby supplies to have separate earth independent from mains
551.4.2
Non-permanent sets to have 30 mA RCD
551.4.4.2
The most common non-compliance item here is the requirement to provide an independent earth. However, it is very often easy to comply with this regulation. For most installations the use of structural steel and similar extraneous-conductiveparts can be utilized to form a suitable earth system. Although some checking with Chapter 54 of BS 7671 is required (see Chapter E) often the existing main bonding elements and conductors can be utilized and are more than adequately sized for the purpose.
D 10 Rotating machines Regulation group 552 addresses rotating machines and makes a number of requirements that are unique to motor circuits, and are in addition to the general requirements, which also have to be met. Motors of 370 W or more are required to have a device for protection against overload (552.1.2) except where they are part of equipment complying with an appropriate British Standard. Stand-alone motors will normally have a motor starter incorporating an overcurrent device. Motors with frequent starting and stopping will need a careful rating selection due to the cumulative effect of the high starting current, and manufacturers’ data should be considered here. As well as the motor itself, such frequent starting will have an effect on the supply cables and other electrical equipment, which should be de-rated. There is no guidance for such de-rating as the permutations are quite varied, and will have to be considered individually – see the example in Section C 3.1. Motor control is addressed by Regulation 537.5.4. Where the restarting of a motor after a mains failure could cause danger, a means is required (usually a relay) to prevent the automatic restarting of the motor on re-energization (537.5.4.1).
D
138
Selection and Erection – Equipment
Regulation 537.5.4.3, whilst not new, is not always complied with and states that where the direction of rotation is a factor relating to safety, measures to prevent the reversal shall be taken. This effectively means supply phase rotation sensing at or near the motor with associated automatic isolation should phase reversal occur.
D 11 Plugs and socket outlets Regulation group 553 sets out the requirements for plugs, socket outlets and cable couplers in terms of applicable product standards, other particular requirements relating to pin configuration and the need for every socket outlet for household use to be shuttered. Except for the connection of clocks, electric shavers and other circuits having special characteristics (see Regulation 553.1.5), the only acceptable types of socket outlet for low voltage applications are:
•• ••
13 A plugs and socket outlets to British Standard BS 1363 for a.c. only; 2, 5, 15, 30 A fused or non-fused plugs, and socket outlets to BS 546; 5, 15, 30 A fused or non-fused plugs, and socket outlets to BS 196; 16, 32, 63, 125 A plugs and socket outlets (industrial type) to BS EN 60309–2.
There are many applications where you may wish, or indeed need, to specify or use a plug and socket not listed above. These will generally be ‘no-load’ makeor-break devices, and are fine for applications where skilled or instructed persons operate. The mounting height of a socket outlet above floor level, or above a work surface, should minimize the risk of accessory or cord damage (553.1.6). Although not specified as a distance in the Regulations, a height of approximately 150 mm above the floor or work surface is recommended as a minimum. For installations in domestic premises, Part M of the Building Regulations stipulates mounting heights for electrical equipment including socket outlets (see also BS 8300: Design of buildings and their approaches to meet the needs of disabled people. Code of practice). There has been some confusion with the interpretation of these requirements since their publication. Generally, for both dwellings and ‘visitor’ areas in commercial installations, electrical accessories should be mounted at a height of between 450 mm and 1200 mm above finished floor level. The basis of these criteria is to avoid problems for disabled persons that may visit a building. It is
139
D
Guide to the Wiring Regulations
not a design brief for a dedicated installation for disabled persons; these are quite different. Finally on socket outlets, Regulation 553.1.7 requires that a sufficient number of socket outlets be provided so that long flexible cords are avoided. This should be pointed out to clients as part of your design briefing. Cable couplers Excepting for SELV and Class II circuits, cable couplers are required to be nonreversible and have provision for a protective conductor. Acceptable cable couplers include those complying with the following British Standards:
•• ••
BS 196; BS EN 60309–2; BS 4491; BS 6991.
It should go without saying that the connector (female part) of the coupler is fitted to the end of the cable remote from the supply.
D 12 Electrode water heaters and electrode boilers Regulation group 554.1 sets out the requirements for electrode water heaters and boilers, which are summarized as follows:
•• •• • •
Connected only to an a.c. supply; Supply controlled by a linked circuit breaker; Overcurrent protective device fitted in each conductor feeding an electrode; Shell of electrode to be earthed; Where the heater is three-phase, the shell of the heater is required to be connected to the neutral conductor; Heaters are required to incorporate (or be provided with) an automatic device to prevent a dangerous rise in temperature.
Generally, all heaters with immersed heating elements are required to have an automatic device to prevent a dangerous rise in temperature. Most of these requirements are built in to the BS and BS EN product standards.
D
140
Selection and Erection – Equipment
D 13 Heating conductors With an increase in the specification of underfloor heating, the Regulations remain surprisingly sparse in this area. The best advice in selecting either underfloor heating cables or external buried heating cables is to select products with recognized product standards and to follow the manufacturers’ installation guides. There are no regulations in the group 554–06 which specify anything that would not be included in the product Standards.
D 14 Lighting and luminaires A completely new section for the 17th Edition is Section 559 ‘Luminaires and Lighting Installations’. The new section deals with interior and exterior lighting installations and also applies to highway power supplies and street furniture. The following items are excluded from Section 559:
•• •
distributors’ equipment as defined in the ESQCR 20021; HV signs supplied at LV, for example neon tubes; signs and luminous discharge tube installations operating from a no-load rated output voltage exceeding 1 kV but not exceeding 10 kV.
1
The Electricity Safety, Quality and Continuity Regulations 2002.
Table D 14.1 summarizes the requirements. Although this table looks fairly long, it covers all the regulations in Section 559 and, consistent with the general spirit of this book, only regulations that are not obvious are included and subsequently explained. For high voltage signs, see BS 559 Specification for design, construction and installation of signs and the BS EN 50107 series Signs and luminous discharge tube installations operating from a no-load rated output voltage exceeding 1 kV but not exceeding 10 kV.
141
D
Guide to the Wiring Regulations
Table D 14.1 Lighting and luminaire requirements. Track lighting shall comply with BS EN 60570
559.4
Heat of lamps on surrounding material shall be considered
559.5.1
Max. lighting circuit size of 16 amp (ES and BC lampholders)
559.6.1.6
Outer screw of ES lampholder must connect to neutral (except for E14 & E27 to BS EN 60238)
559.6.1.8
Through wiring only permitted if luminaire designed for it
559.6.2.1
Temperature rating if marked on luminaire gives heat withstand of cable; see Figure D 14.1
559.6.2.2
3-phase lighting circuits with common neutral shall have linked circuit breaker
559.6.2.3
Stroboscopic effects to be considered in areas with rotating machines (a stroboscopic effect can give the perception that moving objects are stationary when in fact they are moving)
559.9
Earth-free equipotential bonding not to be used
559.10.2
SELV transformers to be to BS EN 61558–2-6
559.11.3.1
1
ELV electronic convertor to be to BS EN 61347–2-2
2
559.11.3.2
SELV bare live conductor systems shall comply with BS EN 60598–2-23 or shall monitor and disconnect within 0.3 s, fail-safe
559.11.4.1 and 559.11.4.2
ELV flexes minimum 1.0 mm2 max. length 3 m
559.11.5.2
ELV flexes minimum 4.0 mm for luminaires suspended by the flex
559.11.5.2
Highway street furniture access door to be accessible only with key or tool or be 2.5 m above ground
559.10.3.1
Highway street furniture lamps to be 2.8 m high or behind barrier
559.10.3.1
Highway street furniture adjacent metal does not require bonding
559.10.3.1
Highway street furniture may use fuse carrier as isolator
559.10.6.1
Highway street furniture disconnection time is 5 seconds
559.10.3.3
2
and 2 Requirement only applies where SELV is being used as a protective measure. Often installers use SELV equipment but install it to 230 volt standards and this requirement will not apply (e.g. most ELV downlighter installations).
1
As well as ‘throwing the book’ at you with quite a few new regulations to study and digest, there is some helpful information in Section 559, mainly the markings found on some luminaires; this information originates in BS EN 60598–1: 2004 Luminaires and is given in Figure D 14.1.
D
142
Selection and Erection â&#x20AC;&#x201C; Equipment
SYMBOL
MEANING Class II Rated maximum ambient temperature
ta ..... C COOL BEAM
Warning against the use of cool-beam lamps
m
Minimum distance from lighted objects (metres)
F
Luminaire suitable for direct mounting on normally flammable surfaces
F
Luminaire suitable for direct mounting on non-combustible surfaces only
F
Luminaire suitable for direct mounting in/on normally flammable surfaces when thermally insulating material may cover the luminaire Use of heat-resistant supply cables, interconnecting cables or external wiring
t ..... C
Luminaire designed for use with bowl mirror lamps
Rough service luminaire
E
Luminaire for use with high pressure sodium lamps that require an external ignitor (to the lamp)
I
Luminaire for use with high pressure sodium lamps having an external starting device
(Rectangular) or
Replace any cracked protective shield
(Round)
Luminaire designed for use with self-shielded tungsten halogen lamps only
Figure D 14.1â&#x20AC;&#x201A; Luminaire markings from BS EN 60598.
143
D
Guide to the Wiring Regulations
D 15 Safety services D 15.1 Introduction Chapter 56 of BS 7671: 2008 entitled ‘Safety Services’ covers some basic selection and erection aspects of supplies intended for safety services. A safety service is defined as an electrical system provided to protect or warn persons in the event of a hazard, or essential to their evacuation. Chapter 56 sets some fundamental requirements only, and there will be considerable overlap with other safety service related standards in both design and installation issues. Most of the chapter provides basic rules about standby supplies where used for safety services. The requirements of the chapter again have been broken down into tables, one for equipment selection and erection and the other for circuits. Obvious regulations have not been included.
D 15.2 Classification of break times For an automatic safety service, the classification of changeover durations is summarized in Table D 15.1.
Table D 15.1 Classification of changeover durations for safety supplies. Classification
Duration ‘D’ of changeover (s)
Break description
No-break
Zero
An automatic supply which can ensure a continuous supply within specified conditions
Very short break
D ≤ 0.15
Changeover within stated duration
Short break
0.15 ≤ D ≤ 0.5
Changeover within stated duration
Lighting break
0.5 ≤ D ≤ 5
Changeover within stated duration
Medium break
5 ≤ D ≤ 15
Changeover within stated duration
Long break
15 ≤ D
Changeover within stated duration
Note: In order to maintain the specified operation, essential items of equipment for safety services are required to be compatible with the changeover duration as indicated above.
D
144
Selection and Erection â&#x20AC;&#x201C; Equipment
D 15.3 Safety sources There are a number of requirements peculiar to safety sources, these being summarized in Table D 15.2.
Table D 15.2â&#x20AC;&#x201A; Summary of requirements for sources for safety services. Type
Regulation
Requirement
Sources
560.6.2
Source to be accessible only to skilled persons or instructed persons
560.6.4
Independent supply feeders by distribution network operator (DNO) not allowed unless DNO confirms feeders unlikely to suffer simultaneous failure
560.6.6
Source may be used for purposes other than safety services if service is not impaired A fault occurring in other than a circuit for purposes of safety services is required not to interrupt any circuit for safety services To achieve above, automatic load shedding will often be required
Non-parallel sources
560.6.7
Precautions required to prevent parallel operation
Parallel sources
560.6.8
The parallel operation of independent sources usually requires the authorization of the distributor
560.6.8.1
Protection against fault current and against electric shock is required to be ensured where the installation is supplied separately by either of the two sources or by both in parallel
Central power supply sources
560.6.9
The batteries are required to be vented or valve-regulated type Minimum design life of the batteries to be 10 years
Low power supply sources
560.6.10
The batteries may be of gastight or valve-regulated maintenance-free type Minimum design life of the batteries is required to be 5 years
UPS
560.6.11
UPS must be able to operate protective devices
Generator supply sources
560.6.12
Must comply with BS 7698â&#x20AC;&#x201C;12: 1998
145
D
Guide to the Wiring Regulations
D 15.4 Circuits for safety services Circuits for safety services are subject to additional requirements, which are summarized in Table D 15.3. Table D 15.3 Additional requirements for circuits for safety services. Regulation
Additional requirement/comment
560.7.1
To be independent of other circuits If routed in fire risk areas, fire rating required
560.7.2
Routing through fire risk areas should be avoided where practicable, if not possible fire rating required
560.7.3
Overload protection may be omitted where the loss of supply may cause a greater hazard (indication required e.g. visual or audible)
560.7.4
Overcurrent protective devices to be co-ordinated so as to achieve discrimination
560.7.5
Switchgear and control gear accessible only to skilled persons or instructed persons
560.7.8
Circuits for safety services not to be installed in lift shafts or other flue-like openings
560.7.11
All current-using equipment to be listed, together with rated currents and starting currents and time. This information may be included in the circuit diagrams
560.8.1
Fire rated cables to be to BS EN 50362, BS EN 50200, BS EN 60332–1-2
560.8.2
Where applicable control bus must comply with above (all circuit requirements)
D 16 Ingress protection (IP), external influences D 16.1 General Regulation 512.2 requires that equipment is suitable for the external influence that it will be subjected to when installed. A large ‘matrix’ type table of external influences with letter designations is included in Appendix 5 of BS 7671: 2008, running to 13 pages. This can be confusing to use and is largely used by technical committees.
D
146
Selection and Erection – Equipment
The influence of objects and water is the main criterion that needs to be considered; other criteria, like ambient temperature, are best found from studying manufacturers’ data. The European Standard BS EN 60529: Degrees of protection provided by enclosures (IP Code) is a ‘standard for standards’ document and provides information about the degrees of protection that can be expected of equipment when allocated with a particular IP Code. ‘Standard for standards’ means that the document is intended for use by equipment manufacturers and equipment standards committees. The IP code provides an indication of the protection the equipment will afford in terms of access to hazardous parts, such as live or moving parts, ingress of foreign objects such as tools, dirt, and liquids such as water. Exact confirmation on particular performance should always be made with the manufacturer. The arrangement of the IP code is made up of four characters, some of which are optional. The arrangement of the code is as follows: IP- International Protection
1ST Numeral protection against solid objects 0 to 6 or X
IP
6
2ND Numeral protection against water 0 to 8 or X
7
3RD Letter-optional access to live parts A, B, C or D
H
C
4TH Letter-optional supplementary information H, M, S or W
147
D
Guide to the Wiring Regulations
Now the code is established, the protection levels can be understood and these are often only specified using the first two characters, as follows:
1 ST Numeral Solid Objects
0 1 2 3 4 5 6
No protection 50mm Back of hand 12.5mm Finger 2.5mmTool 1.0mm Wire Dust protected Dust tight
0 1 2 3 4 5 6 7 8
No protection Drips-vertical Drips 15 degrees Spraying Splashing Jets Powerful Jets Temporary immersion Continuous immersion
IP67
2 ND Numeral Water
Optional Characters Sometimes, albeit rarely, the optional characters three and/or four may be used as follows: 3 RD Character A B C D IP67 AH
Back of hand Finger Tool Wire
4 TH Character H High voltage apparatus M Motion during water test S Stationary during water test W Weather conditions
D
148
Selection and Erection – Equipment
D 16.2 Equipment applications and examples Sometimes, particularly in specifications, one of the first or second characters is not specified and an ‘X’ is used, e.g. ‘IP2X’. Perhaps a little more confusing is where the two designations are used for water. Generally, the higher the numerals of the IP code, the higher the protection level. This is not true where jets of water are concerned. Equipment to IPX8, for example, is totally immersible in water but may not necessarily be suitable for jets (IPX5) or high-pressure jets (IPX6). Equipment that is suitable for both environments will thus require a dual marking of IPX6/IPX8 meaning protected against powerful jets and able to be immersed. Table D 16.1 applies to water jets and immersion.
Table D 16.1 Water jets and immersion. Enclosure passes tests for: Water jets second characteristic numeral
Temporary or continuous immersion second characteristic
Designation and marking
Range of application
5 6 5 6 — —
7 7 8 8 7 8
IPX5/IPX7 IPX6/IPX7 IPX5/IPX8 IPX6/IPX8 IPX7 IPX8
Versatile Versatile Versatile Versatile Restricted Restricted
It can be seen that equipment with the single designation IPX7 or IPX8 has restricted applications or use.
149
D
Guide to the Wiring Regulations
Finally, the following symbols are not listed in BS EN 60529 but may be encountered; an equivalent of the IP code is given below and this will not always be reproduced on the equipment.
Drip Proof
(IPX2)
Rain Proof
(IPX3)
Splash Proof
(IPX4)
Jet Proof
(IPX5)
Immersion Proof
D
150
(IPX8)
Earthing and Bonding
E
Earthing and Bonding E 1
Introduction The subject of earthing and bonding in terms of installation power supplies and BS 7671 is not a highly complicated subject. BS 7671: 2008 comprises just nine pages of regulations on the subject, but there is probably more text written on this subject than any other. This chapter focuses on BS 7671 requirements and solutions, and covers all that most readers will need. Supplementary information on earth electrodes is included in Appendix 12, as it is not relevant for many installations. The interaction of the facets of an earthing system, which includes protective equipotential bonding, together with references to sections of this book, is represented in Figure E 1.1.
151
E
E
152
E5 CPCs
E3
E4
Earthing Conductors
Protective Conductors
E4
E4
E3
Protective Earthing and Bonding System
Figure E 1.1â&#x20AC;&#x201A; Protective earthing and protective equipotential bonding interactions.
Armoured Cables
General Requirements
E2
Earthing Arrangements
E3
E6
Earth Electrodes
Protective Equipotential Bonding Conductors
Main Earthing Terminal
Depicts book section
E4
Guide to the Wiring Regulations
Earthing and Bonding
E 2
Earthing arrangements BS 7671: 2008 defines or lists the types of system earthing in Part 2 – (definitions) and these are also defined in BS 7430: 1998. As the system earthing arrangement is such an important component, the earthing arrangements are explained here. The possible earthing arrangements and hierarchy are shown in Figure E 2.1.
Earthing Arrangement
Earthed Neutral Systems (TN)
TN-C
TN-S
TT Independent Earths
IT Isolated
TN-C-S
Figure E 2.1 Earthing arrangement hierarchy.
The system earthing arrangements are depicted by a code of letters. The first two explain the source and installation arrangement as explained in Figure E 2.2. Two additional letters classify a sub-arrangement of TN systems and relate to the combination of neutral and earth conductor. This is also detailed in Figure E 2.2. The earthing arrangements are further explained with diagrams of both the supply and installation of typical connections, as shown in Figures E 2.3–E 2.8.
153
E
Guide to the Wiring Regulations
2 nd Letter
1st Letter
Connection of exposed - conductive parts to earth
Source
T I
Earthed
+
OR Isolated
Neutral N ViaOR T Independently Earthed
AND 3rd and 4 letters th
FOR TN SYSTEMS ONLY
Defines the Combination of Neutral and Earth Conductors
Separate S OR Combined C OR Combined in Supply, CS Separate in Installation Figure E 2.2â&#x20AC;&#x201A; Earthing arrangement lettering code.
E
154
Earthing and Bonding
TN-C Combined N/E conductor used throughout
L1
L
L2 L3 N
Equipment PEN
Supply Cables
Supply
N
Consumer Terminals
PEN
Installation
Figure E 2.3â&#x20AC;&#x201A; TN-C system earthing.
TN-S Separate neutral and earth throughout
L1
L
L2 L3
Equipment N
N
E
Supply
Supply Cables
Consumer Terminals
Installation
Figure E 2.4â&#x20AC;&#x201A; TN-S system earthing.
155
E
Guide to the Wiring Regulations
TN-C-S (PME) Combined N/E in supply, separate in installation PME Variant: Multiple earths in supply (Protective Multiple Earthing)
L1
L
L2 L3
Equipment N
N
E
Supply Cables
Supply
Consumer Terminals
Installation
Figure E 2.5â&#x20AC;&#x201A; TN-C-S system earthing with PME.
TN-C-S (PNB) PNB Variant Single point of N/E Bonding Protective Neutral Bonding e.g. at switchpanel L1
L
L2 L3
Equipment N E
N
Installation Figure E 2.6â&#x20AC;&#x201A; TN-C-S system earthing with PNB.
E
156
Earthing and Bonding
TT Source and installation earth-separate
L1
L
L2 L3
Equipment N E
N
Supply Cables
Supply
Consumer Terminals
Installation
Figure E 2.7â&#x20AC;&#x201A; TT system earthing.
IT Source neutral unearthed or earthed via a high impedance
L1
L2 L3
Equipment
N Alternative positions for high impedance earth
Supply
Supply Cables
Consumer Terminals
Installation
Figure E 2.8â&#x20AC;&#x201A; IT system earthing.
157
E
Guide to the Wiring Regulations
Some relevant points to note about the various systems are now considered.
• •
TN-C This system is only used in the UK by utilities and usually includes earthed sheath return wiring (ESRW) or earthed concentric wiring. TN-S A true TN-S earthing system has the neutral-earth point at the source or right at the transformer. In practice this is rare and these systems are considered to be TN-C-S PNB (see Figures E 2.6 and E 2.9).
•
TN-C-S (PME) PME systems are used by the utility DNOs (distribution network operators) in most modern networks, mainly for economy and safety. A Government licence is required to own and operate this type of system.
•
TN-C-S (PNB) Figure E 2.6 is something that should be studied, as it is a variation of a TN-C-S system known as PNB, meaning protective neutral bonding. This variation of a TN-C-S system is not defined in BS 7671 but is defined in BS 7430: 1998. The electrical utility companies commonly use this PNB terminology, although it is not so common with electrical contractors or consulting engineers. The TN-C-S PNB system is often used to describe the earthing arrangement in installations with on-site transformers; whilst some describe these arrangements as TN-S they are very close to the TN-C-S PNB system of Figure E 2.6, depending upon the position of the neutral earth link. A typical arrangement for an on-site transformer with the neutral earth link made in the main switchgear is shown in Figure E 2.9.
L
L2
L1
N L3
Connection A E
Transformer
Main Switchgear
Figure E 2.9 Earthing arrangement for on-site substation.
E
158
Point of neutral source earthing
Earthing and Bonding
• •
‘Connection A’ in Figure E 2.9 should be considered as a combined neutral and earth conductor. This PNB arrangement is typical for most installations with an on-site transformer. The point of neutral system earthing is at one place within the main LV panel.
TT In this system the source earth is independent of the installation earth, and hence for the latter there needs to be some form of earth electrode system. IT The source is either not earthed or earthed through a high impedance. A local IT ‘system’ can be created within a system but by considering Figure E 2.8, it can be seen that isolation of the local fabric is required and this can be difficult to achieve.
E 3
General requirements of earthing and bonding The general requirements of BS 7671 for earthing are summarized in Table E 3.1.
Table E 3.1 General earthing requirements of BS 7671. Requirement
Regulation
TN-S systems shall be directly connected to earthed point of source
542.1.2
TN-C-S systems shall be directly connected to earthed point of source via distributor’s earth terminal
542.1.3
TT and IT systems shall be via earthing conductor to an earth electrode
542.1.4
Earth impedance shall be such that protective measure function is as designed
542.1.6 (i)
Conductors shall be adequately sized and robust
542.1.6 (ii) & (iii)
Different interconnected installations shall have adequately sized conductors for maximum fault current
542.1.8
159
E
Guide to the Wiring Regulations
Chapter 41 ‘Protection against electric shock’, restructured and with new definitions for BS 7671: 2008, is described in Chapter C. The measures of complying with the requirements of Chapter 41 are called ‘protective measures’. The protective measures for general application are:
•• ••
automatic disconnection of supply; double or reinforced installation; electrical separation; extra-low voltage provided by SELV or PELV.
The protective measure ‘automatic disconnection of supply’ is by far the most common and makes specific requirements for both protective earthing and protective bonding. Again, whilst covered by Chapter C, we need to briefly review the requirements of the protective measure in order to establish earthing and bonding requirements. The basis of the measure is as follows.
• •
Basic protection (protection against direct contact) is protection from contact with live parts provided by basic insulation, or by barriers or enclosures. Fault protection (protection against indirect contact) is provided by protective earthing, protective equipotential bonding and automatic disconnection in case of fault. In the event of a fault between a live conductor and an exposed-conductivepart of equipment, sufficient fault current flows to operate (trip or fuse) the overcurrent protection.
For the protective measure to work, protective conductors are required to connect all exposed-conductive-parts (of equipment) to the earthing terminal. This is protective earthing and includes circuit protective conductors and the earthing conductor. To reduce shock voltages (touch voltages during a fault), and to provide protection in the event of an open circuit in the PEN conductor of a PME supply, protective equipotential bonding is also required. This requirement is fundamental to the automatic disconnection protective measure of Chapter 41. A simple installation with both circuit protective conductors and protective bonding conductors is shown in Figure E 3.1.
E
160
Supply
9
6 7 8 9 10
7
3
8
1 4
Installation
2
5
Equipment
Exposed-Conductive-Part (Steel Column) Earthing Conductor Earth Electrode PEN Conductor Point of Source Earthing
Figure E 3.1â&#x20AC;&#x201A; Various earthing and bonding conductors and components.
10
N
L2 L3
L1
KEY 1 CPC 2 Exposed-Conductive-Part 3 Main Earthing Terminal 4 Protective Bonding Conductor 5 Exposed-Conductive-Part (Water Pipe)
4 6
Earthing and Bonding
161
E
Guide to the Wiring Regulations
E 4
Protective conductors
E 4.1
General Protective earthing requires exposed-conductive-parts (of electrical equipment, likely to become live in the event of a fault) to be connected (by protective conductors) to the main earthing terminal of the electrical installation. In the event of a fault, sufficient current will flow around the earth fault loop to cause the operation of the fault protective device (fuse, circuit breaker or RCD) and disconnect the fault. Protective bonding conductors reduce the magnitude of voltages during fault conditions. It should be remembered that the following are all types of protective conductor:
•• •
circuit protective conductors (cpc); protective bonding conductors; earthing conductors.
It is important to establish and use the correct terminology; earthing conductors are often confused with cpcs. Earthing conductors are explained in E 4.5.
E 4.2
Physical types of protective conductor BS 7671 recognizes that virtually any metallic conductive part can be used as a protective conductor, and this means as a cpc, a protective bonding conductor or an earthing conductor. Table E 4.1 details metallic conductors and other metallic parts that can be used and provides guidance to their application. It is strongly recommended that what could be described as ‘natural’ components be used as protective conductors. Often these elements exist as a matter of course, e.g. a metal pipe for another service. These items usually provide a much better solution than running extra green and yellow copper cable for protective conductors. The following solutions are recommended:
E
162
Earthing and Bonding Table E 4.1 Recommended types of protective conductor. Conductor
Recommended for use as cpc
Recommended Recommended for use as bonding for use as earthing conductor conductor
Notes
Single core cable
✓
✓
✓
Conductor in cable
✓
✓
✗
If less than 10 mm2, shall be copper
Insulated or bare cable in enclosure with live conductors
✓
✓
✓
Fixed insulated conductor
✓
✓
✓
Fixed bare conductor
✓
✓
✓
Cable sheaths or armouring
✓
✓
Possible
Metal conduit, trunking and ducting
✓
✓
✗
Metal tray
Possible
✓
✗
Possible with consideration
Metal support systems
✗
✓ see note
✗
Structural metal
Possible
✓ see note
✓
For use, continuity and size to be assured and precautions taken against removal
Metal water and service pipes, HVAC services and general metalwork
✗
✓ see note
✓
cpc should be run in close proximity to line conductors. EMC reduction is better when run in enclosure or cable. If less than 10 mm2 shall be copper Possible with consideration
•• • •
Always use metal conduit or trunking as a cpc where it is installed. If cable tray or ladder rack is used to support cables use it as a main bonding conductor. Utilize as much of other services and constructional material as possible for bonding. Utilize the structural steel for bonding.
Section E 6.3 provides more information on utilizing these solutions.
163
E
Guide to the Wiring Regulations
E 4.3
Sizing protective conductors In order to prevent overheating of the protective conductor during a fault, the crosssectional area of a protective conductor(s) shall be not less than that determined by the adiabatic formula as follows: S=
I √t √I 2t , or alternatively arranged as S = k k
where: S is the nominal cross-sectional area of conductor in mm2. I is the value of fault current in amperes (rms for a.c.) for a fault of negligible impedance. t is the operating time of the disconnecting device in seconds, corresponding to the fault current. It is found from the protective device characteristic curve. k is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures, see Tables 54.2 to 54.6 of BS 7671. It should be noted that where the initial cable size has been adjusted following a thermal withstand check, further iterations may be necessary as the new size itself affects the prospective fault current. Alternatively, the minimum cross-sectional area of a protective conductor can be determined by selection from Table 54.7 of BS 7671 (as below), but this virtually always yields a larger cable. Table 54.7 of BS 7671 Minimum CSA of protective conductor in relation to the crosssectional area of associated line conductor. Cross-sectional area of line conductor S (mm2)
If the protective conductor is of the same material as the line conductor (mm2)
If the protective conductor is not the same material as the line conductor (mm2)
S ≤ 16
S
k1/k2 × S
16 ≤ S < 35
16
k1/k2 × 16
S > 35
S/2
k1/k2 × S/2
k1 is the value of k for the line conductor, selected from Table 43.1 in Chapter 43 according to the materials of both conductor and insulation. k2 is the value of k for the protective conductor, selected from Tables 54.2 to 54.6 as applicable.
E
164
Earthing and Bonding
It should be noted that bonding conductors should not be sized using this method; it applies to cpcs and earthing conductors (see 543.1.1). For sizing of protective bonding conductors, see E6.
E 4.4
Protective conductors up to 16 mm2 The sizing of protective conductors depends upon only two factors: a size for disconnection times and a size for thermal capacity under fault conditions. Instead of calculating the size of protective conductor for all combinations, the tables provided in this section give maximum earth fault loop impedance values for a number of protective device and protective conductor combinations. When fuses to BS 1361, BS 88, or BS 3036 are used, this sets a maximum limit on the earth fault loop impedance. Tables E 4.2 to E 4.5 inclusive give maximum test earth fault loop impedances allowed for particular fuse and protective conductor Table E 4.2 BS 3036 fuse maximum ELI values in ohms. BS 3036 fuse maximum ELI values (W) Protective conductor size (mm2)
Fuse rating 5 A
15 A
20 A
30 A
45 A
1.0
7.7
2.1
1.4
NP
NP
1.5
7.7
2.1
1.4
0.9
NP
2.5
7.7
2.1
1.4
0.9
0.5
4.0 to 16
7.7
2.1
1.4
0.9
0.5
Notes: NP: protective conductor/fuse combination not permitted. A value of k of 115 from Table 54.3 of BS 7671 is used. This is suitable for PVC-insulated and sheathed cables to Table 5 of BS 6004.
Table E 4.3 BS 88 fuse maximum ELI values in ohms. BS 88 fuse maximum ELI values (W) Protective conductor size (mm2)
Fuse rating 6 A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
1.0
6.87
4.12
2.18
1.43
1.16
0.66
NP
NP
1.5
6.87
4.12
2.18
1.43
1.16
0.84
0.64
NP
2.5 to16
6.87
4.12
2.18
1.43
1.16
0.84
0.66
0.49
Notes: NP indicates protective conductor/fuse combination not permitted. A value of k of 115 from Table 54.3 of BS 7671 is used. This is suitable for PVC-insulated and sheathed cables to Table 5 of BS 6004.
165
E
Guide to the Wiring Regulations
Table E 4.4 BS 1361 fuse maximum ELI values in ohms. BS 1361 fuse maximum ELI values (W) Protective conductor size (mm2)
Fuse rating 5 A
15 A
20 A
30 A
45 A
1.0
8.43
2.65
1.37
0.77
NP
1.5
8.43
2.65
1.37
0.93
NP
2.5
8.43
2.65
1.37
0.93
0.51
4.0
8.43
2.65
1.37
0.93
0.68
6.0 to 16
8.43
2.65
1.37
0.93
0.77
Notes: NP indicates protective conductor/fuse combination not permitted. A value of k of 115 from Table 54.3 of BS 7671 is used. This is suitable for PVC-insulated and sheathed cables to Table 5 of BS 6004.
combinations. When the protective conductor is small the limiting factor is the adiabatic equation. For larger sizes of protective conductor the limiting factor is the shock protection requirement. When circuit breakers are used to protect the circuit, because shock protection requirements require that circuit breakers operate instantaneously in the event of a fault, the most practical approach is to set a minimum protective conductor size for each type and rating of circuit breaker. For completeness in Table E 4.5 below, the maximum test loop impedance is included and these values ensure instantaneous operation (0.1 s) of the circuit breaker.
Table E 4.5 Cable size and maximum ELI values for BS EN 60898 circuit breakers. Circuit breaker type B
C
D
E
Device rating A 6
10
16
20
25
32
40
50
63
80
100
Min cable size (mm2)
1
1
1
1
1
1
1
1
1.5
1.5
1.5
Max ELI (Ω)
6.2
3.7
2.3
1.9
1.5
1.2
0.93
0.74
0.59
0.46
0.37
Min cable size (mm2)
1
1
1
1
1
1
1
1.5
1.5
2.5
2.5
Max ELI (Ω)
3.1
1.9
1.2
0.93
0.71
0.58
0.46
0.37
0.29
0.23
0.18
Min cable size (mm2)
1
1
1.5
1.5
2.5
2.5
4
4
6
6
10
Max ELI (Ω)
1.6
0.93
0.58
0.46
0.37
0.29
0.23
0.18
0.15
0.12
0.09
166
Earthing and Bonding
E 4.5
Earthing conductor The earthing conductor connects the system earth bar or main earthing terminal (MET) to the system means of earthing (see Figures E 3.1 and E 6.5). It is sized as for other protective conductors, namely either by the adiabatic equation: I t S= √ k or by using Table 54.7 of BS 7671; this is explained in Section E 4.3. For PME installations the size of the earthing conductor must be no less than the sizes in Table E 4.6. Table E 4.6 PME (TN-C-S) minimum earthing conductor sizes. PME (TN-C-S) main protective bonding conductor sizes (mm2) Supply neutral conductor size (mm2)
Earthing conductor min. size (mm2)
25
35
50
70
95
120
150
Over 150
10
10
16
25
25
35
35
50
Note: Electricity utility distributors may require a minimum size of earthing conductor at the origin of the supply of 16 mm2 copper or greater for TN-C-S (PME) supplies.
E 5
Armoured cables as protective conductors
E 5.1
General It has been common practice in the United Kingdom to use the armouring of steel wire armoured cables as the protective conductor. This practice complies with BS 7671 and is most desirable for a number of reasons. Armouring provides a lowimpedance, robust, protective earthing system and will greatly assist any potential EMC issues compared with the practice of running external cpcs. Checking that the armouring is of sufficient cross-sectional area is complicated by the armouring being of a different material (steel) to that of the conductor (copper or aluminium). It is also complicated by the cross-sectional area for some two- and three-core cables being less than that given by Table 54.7. In the past,
167
E
Guide to the Wiring Regulations
various organizations have suggested that certain cable configurations and sizes are insufficient for compliance with BS 7671. However, the remedy of the suggested undersized armour was to run an external cable cpc in the vicinity of the cable. This subject itself posed unanswered problems of the current sharing between the armour and the external cpc. It was thought that current sharing under fault conditions would not be in line with the respective impedances due to the magnetic field interaction of the armour. There was no recognized method of approximating this current sharing. Due to this, during 2007 ECA sponsored research on this subject by the cables division of the Electrical Research Association (ERA). The report is included in Appendix 16 and its conclusions are given below.
E 5.2
ERA report on current sharing between armouring and cpc Conclusions Prior to carrying out the test work described above it was thought that the proportion of any earth fault current carried by an external cpc, run in parallel with the armour of a cable, would be less than that predicted from the ratio of the armour and cpc resistance. The test work has shown that this is not the case and that using the resistance ratio will give a reasonable estimate of the current carried by the external cpc. Comparison of the fault current withstand of the armour of cables to BS 5467, using the k values given in Chapter 54 of BS 7671, has shown that for all cables except the 120Â mm2 and 400Â mm2 2-core cables the fault current withstand of the armour is greater than the fault current required to operate a BS 88 fuse. Thus a supplementary external cpc is generally not required to increase the fault current withstand of an armoured cable. A supplementary external cpc would only be required if the earth fault loop impedance needed to be reduced to meet the values tabulated in Chapter 41 of BS 7671. This could be the case for a long cable run where protection against indirect contact was achieved by automatic disconnection of the supply and the use of a residual current device was not appropriate. (Continued.)
E
168
Earthing and Bonding
(Continued.)
Empirical equations have been derived for calculating the prospective fault current where an external cpc is installed in parallel with steel wire armour. Empirical equations have also been derived for calculating the current sharing between the armour and the external cpc. Calculation of the current sharing between the armour and an external cpc has shown that if a small external cpc is run in parallel with the armour of a large cable there is a risk that the fault current withstand of the external cpc will be exceeded. Because of this it is recommended that the cross-sectional area of the external cpc should not be less than a quarter of that of the line conductor.
E 5.3
ECA advice and recommendations The ECA recommends the following:
• •
Use all armoured cables as a cpc without the need for a thermal withstand check, with the exception of 400 mm2 2-core. Note: The 120 mm2 cable was within a few per cent of the size required (required I2t of 33 062 500, actual 33 800 000 after 5 seconds) and should be used without calculation unless it is intended to run the cable at full currentcarrying capacity. It is very difficult to load a cable of this size at its full currentcarrying capacity for a continuously long period. Where calculation software specifies external cpcs for ELI reduction, use a cpc size of at least 25% of the line conductor csa (perhaps after manually checking calculations). Manually check ELI calculations where software specifies small external cable cpcs.
• • E 6
Protective equipotential bonding
E 6.1
Purpose of protective equipotential bonding This section discusses main equipotential bonding. The purpose of protective equipotential bonding is to:
••
reduce shock voltages in the event of a fault; and reinforce the connection with the earth of the installation.
169
E
Guide to the Wiring Regulations
E 6.2
BS 7671 requirements In every installation, protective bonding conductors are required to connect the protective earthing terminal to extraneous-conductive-parts including to the earthing system (via the main earthing terminal). Chapter 41 has a different list of suggested items to bond than does Chapter 54 but both should be used. The comprehensive list is as follows:
•• •• •• •
circuit protective conductors; water installation pipes; gas installation pipes; other installation pipework and ducting; exposed, metallic structural parts of the building; functional earthing conductors where used; lightning protection system (LPS) in accordance with BS EN 623051.
1
At the time of drafting, BS EN 62305 was under modification to state that this bond was the responsibility of the LPS contractor in terms of both sizing and installation.
E 6.3
Bonding solutions for the modern installation The question still remains as to how to carry out bonding in a modern installation. Historically, after publication of the 15th Edition of the IEE Wiring Regulations in 1981, the industry went through what can only be described as a ridiculous period of practice. It was common to bond all exposed metalwork, including such items as metal window frames, individual metal floor or ceiling tiles and cross bonding to virtually everything. If consulting engineers did not insist on the practice, then the installation contractor did! The modern trend is now well away from this, but the question remains of what to do about continuity of, say, the structural steel, or air conditioning ductwork systems. The solution advocated by the ECA for many years now is provided in this section.
E
170
Earthing and Bonding
Commercial and industrial installations Take one bonding conductor to each of the items in the list given in Section E 6.2.
â&#x20AC;˘
Thatâ&#x20AC;&#x2122;s it! See Figures E 6.1 to E 6.4 and accompanying notes. Using constructional elements for bonding Figure E 6.1 shows a typical commercial or industrial structure. There is a metal superstructure either with steel beams and columns, or steel reinforced concrete. There are many interconnected star and parallel metallic and conductive parts. Many of these are not shown on the diagram, but consider the amount of services and their support metalwork for the ductwork, water pipework, gas piping, external cladding, false floor, false ceiling, lifts and, of course, the electrical services. There really is no need for any green and yellow cable at all. Continuity tests on this metalwork virtually always indicate a continuity approaching zero ohms. The best solution for main protective equipotential bonding is that indicated in Figure E 6.4, but often the solutions shown in Figures E 6.1 or E 6.2 are installed. The figures now follow. Figure E 6.1 shows a typical solution which involves running separate bonding conductors to the extraneous-conductive-parts. This is unnecessary. Figure E6.2 shows a typical solution which involves running separate bonding conductors to the extraneous-conductive-parts but now installed on metal cable tray or ladder rack. This is often undertaken whether or not the tray or ladder rack was installed for power cables. Figure E 6.3 shows a much better and more economic solution, where the cable tray or ladder rack has been used as a protective conductor. Figure E 6.4 shows the best solution for most installations of this nature. The building structure has been used as a protective conductor. The cable tray is not shown on this diagram as it may have been installed for just a few cables, which have now been clipped directly to the structure. Unfortunately, this technique is under-utilized, mainly due to custom and practice. If the diagrams are considered again, it is obvious that the structure and metal services will form part of the bonding network whether you like it or not.
171
E
Guide to the Wiring Regulations
KEY 1 2 3 4 5 6 7 9
Main electrical switchpanel Main earthing terminal Bond to structure Bond to gas pipe system Bond to waterpipe system Bond to A/C ductwork Boiler Cable tray or ladder rack
6 5 4
9
7
1 2
3
Figure E 6.1â&#x20AC;&#x201A; Protective equipotential bonding â&#x20AC;&#x201C; via multiple cables.
E
172
Earthing and Bonding
KEY 1 2 3 4 5 6 7 9
Main electrical switchpanel Main earthing terminal Bond to structure Bond to gas pipe system Bond to waterpipe system Bond to A/C ductwork Boiler Cable tray or ladder rack
5
4
6
7 9
1 2
3
Figure E 6.2â&#x20AC;&#x201A; Protective equipotential bonding â&#x20AC;&#x201C; via multiple cables run on cable tray.
173
E
Guide to the Wiring Regulations
KEY 1 2 3 4 5 6 7 8
Main electrical switchpanel Main earthing terminal Bond to structure Bond to gas pipe system Bond to waterpipe system Bond to A/C ductwork Boiler Bond to tray or ladder rack (or similar) for use as protective conductor 9 Cable tray or ladder rack
5
9
6 4
7
8 1 2
3
Figure E 6.3â&#x20AC;&#x201A; Protective equipotential bonding â&#x20AC;&#x201C; utilizing cable tray as protective conductor.
E
174
Earthing and Bonding
KEY 1 2 3 4 5 6 7
Main electrical switchpanel Main earthing terminal Bond to structure Bond to gas pipe system Bond to waterpipe system Bond to A/C ductwork Boiler
5 4
6 7
1 2
3
Figure E 6.4â&#x20AC;&#x201A; Protective equipotential bonding â&#x20AC;&#x201C; utilizing structure as protective conductor.
175
E
Guide to the Wiring Regulations
Domestic installations Take one bond to incoming metallic water and gas pipes. If there is a metallically piped central heating system, bond it in one location. This is not necessary where any metallic pipe, bonded elsewhere (e.g. metallic water pipe), is connected and tests satisfactorily for continuity. If the structure is metallic, take a bond to one location; this is not necessary for intermediate metallic stud partitions or individual metal beams and the like. The central heating system will probably not need a cable bond connection if connected by metallic gas or water pipes which have themselves been bonded (see Figure E 6.5).
•• • •
Structural beam - do not bond CH Radiator plumbed in plastic pipe
CH Radiator plumbed in metal pipe
Main bond required if incoming services are plastic Earthing Conductor
CH Boiler
MET Gas
Water Bond to incoming metal services only
Figure E 6.5 Protective equipotential bonding – in a domestic installation.
E
176
Earthing and Bonding
Figure E 6.5 shows a typical domestic dwelling, and main protective bonding requirements. The radiator served via plastic pipe does not require a bond. The radiator served via metal pipes will need a bond if the boiler is not itself bonded. However, it would be better practice to bond the boiler or a pipe close to the boiler.
E 6.4
Sizing protective bonding conductors The sizing of bonding conductors can get confusing when reading Chapter 54 of BS 7671. This is due to the fact that the suggested minimum sizes relate to the size of the line and earthing conductor for TN-S supplies, and the supply neutral conductor for TN-C-S (PME) supplies. Tables E 6.1 and E 6.2 provide an easy look up for main protective bonding conductor sizes.
Table E 6.1 TN-S, PNB, TT main protective bonding conductor sizes. Line conductor size (mm2) 25
35
50
70
95
120
150
185
240
300
400
500
600
Earthing conductor min. size (mm2)
16
16
25
35
50
70
95
95
120
150
240
300
300
Bonding conductor min. size (mm2)
10
10
16
16
25
25
25
25
25
25
25
25
25
Notes: Smaller sizes are possible by using S = (I√t)/k to calculate earthing conductor size; main bonding is half the size of this up to a maximum of 25 mm2. A minimum conductor size of 6 mm2 shall be used and conductors of 10 mm2 or less shall be copper. For conductors of other material, the material must be sized to achieve the equivalent conductance of the copper of the relevant size. See Appendices for data. IT system earthing conductors may be sized using this table.
Table E 6.2 PME (TN-C-S) main protective bonding conductor sizes. Supply neutral conductor size – mm2 25
35
50
70
95
120
150
Over 150
Earthing conductor min. size (mm )
10
10
16
25
25
35
35
50
Bonding conductor min. size (mm )
10
10
16
25
25
35
35
50
2
2
Note: Electricity utility distributors may require a minimum size of earthing conductor at the origin of the supply of 16 mm2 copper or greater for TN-C-S (PME) supplies.
177
E
Guide to the Wiring Regulations
E 6.5
Domestic protective equipotential bonding layouts This section provides diagrams of typical protective equipotential bonding layouts. It has been added to provide further guidance on typical layouts of bonding conductors, and also assists with recognizing earthing arrangements. Many other layouts are, of course, possible. Figure E 6.6 shows the main earthing terminal connected via the earthing conductor to the utility cut-out stud terminal (TN-C-S). Figure E 6.7 shows the main earthing terminal connected via the earthing conductor to the sheath of the utility supply cable (TN-S). Figure E 6.8 shows the main earthing terminal connected via the earthing conductor to the installation earth electrode (TT). The earthing conductor in a TT installation may only need to be 6 mm2 although it is shown as 16 mm2 in this diagram.
E 6.6
Supplementary equipotential bonding Chapter 41 of BS 7671: 2008 lists two additional measures intended to supplement the main protective measures for protection against electric shock. The additional measures are RDCs and supplementary equipotential bonding. The subject of RCDs is covered in this book in Chapters C and D. Supplementary bonding is additional protection to fault protection, and may be required where the disconnection times of Table 41.1 of BS 7671 cannot be achieved. However, the use of supplementary bonding does not exclude the need to disconnect the supply for other reasons, for example, for protection against overcurrent. Supplementary bonding may also be required for special locations such as:
•• ••
locations with a bath or shower 701.415.2; swimming pools and other basins 702 .411.3.3; locations with livestock 705.415.2.1; conducting locations with restricted movement 706.410.3.10 (iii).
It should be noted that there is no requirement in BS 7671 to install supplementary bonding in kitchens.
E
178
16 mm 2
1
Figure E 6.6â&#x20AC;&#x201A; Typical TN-C-S protective equipotential bonding layout.
6
9 9999 9
KEY 1 Earthing conductor 2 CPCs 3 Main protective bonding conductor 4 Metal water pipe 5 Metal gas pipe 6 Cut-out earth terminal 7 Main earthing terminal 2
16 mm
2
1
7
10 mm 2
3
3
10 mm 2
4
5
Earthing and Bonding
179
E
E
180
Figure E 6.7â&#x20AC;&#x201A; Typical TN-S protective equipotential bonding layout.
6
9 9999 9
KEY 1 Earthing conductor 2 CPCs 3 Main protective bonding conductor 4 Metal water pipe 5 Metal gas pipe 6 Service cable TN-S earth 7 Main earthing terminal 2
16 mm
2
16 mm 2
1
1
7
10 mm 2
3
3
10 mm 2
4
5
Guide to the Wiring Regulations
Figure E 6.8â&#x20AC;&#x201A; Typical TT protective equipotential bonding layout.
Cut-out
9 9999 9
KEY 1 Earthing conductor 2 CPCs 3 Main protective bonding conductor 4 Metal water pipe 5 Metal gas pipe 6 Earth rod 7 Main earthing terminal 2
6
16 mm
2
1
16 mm 2
1 7
10 mm 2
3
3
10 mm
4
2
5
Earthing and Bonding
181
E
Guide to the Wiring Regulations
The sizes of supplementary bonding conductors are summarized in Table E 6.3 for cables not mechanically protected, which is the usual case. For completeness, Table E 6.4 is for cables which are mechanically protected, i.e. run in conduit, trunking or similar.
Table E 6.3 Supplementary bonding conductor sizes – unprotected cables. Circuit conductor size (mm2)
Exposed to exposedconductive-parts (mm2)
Exposed to extraneousconductive-parts (mm2)
Extraneous to extraneousconductive-parts (mm2)
1.0
4
4
4
1.5
4
4
4
2.5
4
4
4
4
4
4
4
6
6
4
4
10
10
6
4
16
16
10
4
Note: If one of the extraneous-conductive-parts is connected to an exposed-conductive-part, the bond must be no smaller than that required for bonds between exposed-conductive-parts.
Table E 6.4 Supplementary bonding conductor sizes – protected cables. Circuit conductor size (mm2)
Exposed to exposedconductive-parts (mm2)
Exposed to extraneousconductive-parts (mm2)
Extraneous to extraneousconductive-parts (mm2)
1
1
1
2.5
1.5
1
1
2.5
2.5
2.5
1.5
2.5
4
4
2.5
2.5
6
6
4
2.5
10
10
6
2.5
16
16
10
2.5
Note: If one of the extraneous-conductive-parts is connected to an exposed-conductive-part, the bond must be no smaller than that required for bonds between exposed-conductive-parts.
E
182
Earthing and Bonding
E 7
High earth leakage installations The subject of circuits or equipment with high earth leakage currents was covered in a Special Installations section (607) in previous versions of BS 7671. This section was deleted in the international IEC document and for BS 7671: 2008 the requirements are contained within Chapter 54, Section 543.7. The designer of the installation needs to assess whether the equipment circuit is likely to carry earth leakage current. It is recommended to use a figure of 1 mA earth leakage per workstation outlet for personal computers. The requirements are summarized in Table E 7.1 for circuits and Table E 7.2 for individual items of equipment. The option of using earth monitoring has not been included as it is a rather specialist area and very rarely used. Table E 7.1 Requirements for circuits with collective leakage exceeding 10 mA. Requirement
Regulation
Comments
Circuits shall have dual cpc terminated separately at supply and outlets, or
543.7.1.3
Applies to ring socket-outlet circuits
Circuits shall have a 4 mm2 copper cpc, or
543.7.1.3
Circuits shall have a 10 mm cpc
543.7.1.3
‘Spur’- off rings to be duplicated
543.7.2.1
2
Table E 7.2 Requirements for individual items of equipment with leakage exceeding 3.5 mA. Requirement
Regulation
Items of equipment with leakage between 3.5 mA and 10 mA: hard wire or connect via ‘industrial’ plug and socket to BS EN 60309–2
543.7.1.1
Items of equipment with leakage of 10 mA and above: hard wire or connect via ‘industrial’ plug and socket to BS EN 60309–2 with cpc of 2.5 mm2, or 4 mm2 if >16 A
543.7.1.2
183
E
Inspection, Testing and Certification (Part 6)
F
Inspection, Testing and Certification (Part 6) F 1
Introduction Part 6 of BS 7671: 2008 is entitled ‘Inspection and Testing’ but covers the subjects of certification and reporting as well as inspection and testing. The Part comprises three chapters as follows;
•• •
61 Initial Verification; 62 Periodic Inspection and Testing; 63 Certification and Reporting.
The subject of Periodic Inspection and Testing is discussed in Appendix 15 of this book as many organizations do not undertake such work, which is generally regarded as a little more ‘specialist’. Chapter F therefore discusses and provides explanation and guidance on the inspection, testing and certification of new installations, including alterations and additions. The main part of the chapter addresses the ‘initial verification’ of the Regulations and confirmation that the installation meets the requirements of the Regulations.
F 1.1
Inspection and testing – an integrated procedure The activities of carrying out visual inspection and of then carrying out testing should be considered as complementary procedures. These procedures should not be considered to be separate functions carried out by separate individuals or
185
F
Guide to the Wiring Regulations
organizations; this is particularly true of the inspection confirmation part of the inspection and testing. To illustrate this point: in general there would be little point in carrying out a continuity test on a cable if it had been found that some of its connection terminals were loose. The defect would need to be remedied before the test was conducted. Another aspect to consider are the stages of inspection and stages of testing for larger installations. For many such installations the inspection is formally carried out at the end of the constructional element of the electrical installation process; often a separate ‘test’ electrician or engineer undertakes this task. However, the amount of visual inspection undertaken during the electrical construction stage is often very significant. Most electricians check visual elements like polarity, tightness of connections, and indeed many of the items required under the visual inspection element of inspection and testing (see Section F 2 below). These visual checks are done as a matter of course, but often the ‘test engineer’ completes the visual inspection separately and often without consultation with the installation electricians. It is suggested that this ‘inspection’ facet of the inspection and testing process is more efficient, and generally better, if carried out ‘inherently’ by the installers. Of course, there are exceptions; a particular example is where semi-skilled labour is being utilized for installation. It is suggested, for larger organizations, that a system be created that allows the installer to confirm facts about the visual inspection. Table F 2.1 suggests items that can and should be carried out during the electrical construction procedure.
F 2
Visual inspection The visual inspection part of the initial verification is the process of assessing the installation prior to testing. Regulation 611.2 specifies the purpose of the visual inspection, summarized as follows:
•• •
equipment complies with a product standard (see Section D 2); equipment is correctly selected and erected (see Chapter D); equipment is not damaged.
Table F 2.1 summarizes the requirements for the inspection part of the initial verification. To be consistent with the restructured Chapter 41 (see Chapter C) the protective measures like ‘placing out of reach’, and similar, have been removed from this table, as they are not considered at the installation stage. The table has been
F
186
Inspection, Testing and Certification (Part 6)
constructed with a ‘should have an automatic tick’ column. This column indicates facets that should be automatically inspected by the installer. For example, how can an installer install a cable if he does not know the designer’s specified cable size? As a further example, the installer should not be terminating cables if he does not know BS 7671 aspects relating to the tightness of connections; thus, he should be inspecting this part of the work. This column should be inherently carried out by the installing operative, completed on the inspection checklist paperwork and passed to the ‘test engineer’ if this is a separate individual.
Table F 2.1 Visual inspection requirements of BS 7671: 2008. Inspection
Should have automatic tick
At ‘installed’ stage
Confirmed separately at final ‘testing’ stage
Erection methods
✓
✓
Not required
Conductor terminations
✓
✓
Not required
Identification (colour/labelling of cables)
✓
✓
Not required
Installation of cables (mechanical protection, 522 etc.)
✓
✓
Not required
Cable size as design specification
✓
✓
Not required
✓
Not required
Building sealing around cables and trunking etc. Presence of means of earthing
✓
✓
Not required
Presence of protective conductors, cpcs and bonding
✓
✓
Not required
Isolation
✓
✓
Not required
Warning notices
✓
✓
Not required
Diagrams
✓
✓
Equipment to standards, and IP
✓
✓
Not required
✓
Spot checks may be useful
Detrimental influences
Notes
Spot checks may be useful
Spot checks may be useful
Adequate access to switchgear
✓
✓
Not required
Spot checks may be useful
Overcurrent devices correctly sized as specified
✓
✓
Not required
Spot checks may be useful
Presence of RCD protection where required
✓
✓
Not required
Spot checks may be useful
✓
Check
Undervoltage devices where required
187
F
Guide to the Wiring Regulations
The detail of inspection to this table is covered in the other chapters of this book, and is not expanded upon here with the exception of some labelling and warning notices; for these, refer to BS 7671: 2008 directly. It should be apparent that if an organization employs separate ‘inspection and test engineers’, much of the inspection work should be a conversation and completing paperwork exercise with the test engineer. This exercise is better if the inspection paperwork originates with the designer and is passed on to the test engineer. In these situations it should not be the function of the ‘test engineer’ to repeat inspections of items confirmed by the installers; this is not a requirement of the Regulations.
F 3
Testing
F 3.1
Introduction – pass and fail nature This section discusses methods for achieving the physical testing requirements of BS 7671. It should be noted that, in some books and advice, too much emphasis is placed on particulars of test methods, often in areas that are not important and do not make any difference to the safety of an installation. It should be remembered that, of the seven ‘everyday’ tests required by BS 7671, five are really pass/fail tests. Also, the test methods suggested by industry guidance and manufacturers’ literature are just that – guidance. Other methods can and will produce satisfactory results and may be used; and this is, of course, true of this part of this book.
F 3.2
Required tests The tests required by Part 7 of BS 7671: 2008 fall into two categories:
• •
The seven ‘everyday’ tests. These are regularly and continually used by installers and are described in this section of the book. Additional tests that may be used occasionally. They would include, for example, testing the insulation of an IT ‘floor structure’. These are discussed in Appendix 14.
The ‘everyday tests’ required by Part 6 of BS 7671: 2008 have been required in the Regulations for a considerable number of years. The Regulations and guidance
F
188
Inspection, Testing and Certification (Part 6)
DEAD Continuity + Rings
DEAD AND /OR ALIVE
Insulation Resistance Polarity
LIVE ELI Fault Current Measurement RCDTests
Figure F 3.1 ‘Everyday tests’ order and state of energization.
have suggested an order of tests based on safety and logic. The suggested order is to carry out at least two tests prior to energization (cpc continuity and insulation resistance, with the possible addition of polarity checks) and the remainder to be carried out after energization. A diagram of the seven ‘everyday tests’ and the suggested order of tests is given in Figure F 3.1. Working to the suggested order of tests is recommended, but you should bear in mind that some tests will require disconnection of the circuit’s neutral; the exact order should not be cast in stone, although the dead tests should certainly be completed prior to energization for safety reasons.
F 3.3
Continuity testing This is the first suggested test as it is important for the safety of the circuit, and it helps confirm a reference for the remainder of the tests. Continuity testing is carried out on all protective conductors including cpcs, main and supplementary protective bonding conductors.
189
F
Guide to the Wiring Regulations
The test is carried out with a low d.c. voltage continuity tester, and this may detect loose and unsound connections; other instruments may be used. It is important to establish the path of the conductor that is being measured, as often there will be parallel paths in circuit. This is virtually always the case in commercial and industrial installations where parallel metalwork has a significant bearing on readings. Consider the luminaire circuit in Figure F 3.2 installed in a typical commercial installation. The figure shows a luminaire mounted with a substantial metal fixing to the structure. There are numerous earth return paths back to the source earth point including the cable cpc, trunking, metal supports, the cable ladder rack and the superstructure of the building. It is unrealistic to disconnect the luminaire from these to test for continuity. Even if the luminaire had an ‘insulated’ cable supply, unlikely in this environment, the cpc would need to be disconnected at every luminaire on the circuit in order that the cable cpc be tested correctly. This would defeat the object, as the connections are the most vulnerable parts of the circuit. Thus, the only test possible is to test for continuity of the luminaire, including the multiple parallel return paths. In effect, the reading is confirming that the equipment under test is earthed and, with this test, it is possible that a cable cpc is open circuit. Some do not like this situation and it is one of the reasons that the ECA would recommend using metallic trunking or metallic conduit as a cpc and not a cable cpc within these systems. This brings us to the two popular methods for continuity testing, namely: 1 ‘wandering lead’ method; 2 utilization of circuit cable by ‘shorting’. Wandering lead method The author, mainly for the reasons given above concerning parallel returns, prefers this method. Figure F 3.2 shows a ‘wandering lead’ continuity test. You will notice by studying the figure that the cpc has not been removed from the earth terminal at the distribution board. This is due to the fact that there are parallel metallic earth return paths and removal of this conductor will not change this. Once set up, testing using the ‘wandering lead’ method is quick and simple. Metalwork in the vicinity of the equipment under test can be quickly checked (often all that is needed is a piece of timber with cable and spike!). Extraneousconductive-parts can be checked using the same method.
F
190
Inspection, Testing and Certification (Part 6)
Continuity of CPC by ‘Wandering Lead’
E
Wandering lead
0.1
8
Meter
ESSENTIALS CPC Test
Connected to earth terminal at DB* At all points
Readings Relate to resistance of copper or steel* usually less than 1 ohm * See notes
Figure F 3.2 Continuity of cpc by ‘wandering lead’ method.
It is recommended that this method be used for commercial installations with parallel earth return paths. Also, the recording of a resistance value for each circuit is rather pointless, as parallel paths do not fall neatly into ‘circuits’. Instead, all equipment relevant to a distribution board is tested and the following recorded on the test sheet relating to the distribution board: ‘All circuits tested for continuity maximum reading 1.2 ohms (luminaire director’s office)’ As for readings, many tests using this method will show readings approaching zero or typically less than one or two ohms.
191
F
Guide to the Wiring Regulations
Utilizing the circuit cable and R1 + R2 method The second method involves using the circuit cable and shorting or linking it out at one end as shown in Figure F 3.3.
Continuity using circuit cable
L
E
0.2
1
Link Cable Meter
ESSENTIALS CPC
Connected to earth in DB*
Test
At all points
Readings Relate to resistance of copper or steel* usually less than 1 ohm * See notes
Figure F 3.3â&#x20AC;&#x201A; Continuity of cpc by circuit cable method.
F
192
Inspection, Testing and Certification (Part 6)
The method is simple enough, and if the line conductor is used, this method can be used to record the circuit’s R1 + R2 value. However, the comments made in the ‘wandering lead’ method about parallel metallic return paths also apply to this method, and therefore in virtually all commercial and industrial applications this test only measures R1 plus a value of a parallel multi-connected return path. It is therefore a little misleading to record results for this method as a circuit’s R1 + R2 value without a cautionary note on the test sheet. When compared with the ‘wandering lead’ method, this test method is slow to repeat at all outlets on a particular circuit (except for socket outlets) as it involves access to equipment terminals. The method does find favour with some, and can be used to establish a circuit’s earth fault loop impedance value as discussed later.
F 3.4
Ring continuity The continuity of ring final circuits is something that is a little more involved. Methods have evolved over the years to establish whether the rings are indeed wired as ring circuits, and not ‘shorted’ forming a ‘figure of eight’ layout and similar. Whether the 17th Edition requires this test is questionable. The best advice here is not to use ring circuits for commercial and industrial installations. For completeness and where ring final circuits are used, the following continuity tests are recommended. It should be noted that the stage 3 tests involving using the circuits cpc will suffer from the problem of parallel multi-metallic return paths as mentioned in Section F 3.3, and unless circuit wiring, socket outlets and accessory boxes are insulated from earth this test stage should not be used.
193
F
Guide to the Wiring Regulations
STAGE 1
L
E
L
N
0.6
N
E
1.0 0.6
Figure F 3.4aâ&#x20AC;&#x201A; Continuity of ring final circuits, stage 1.
Stage 1 â&#x20AC;&#x201C; open loop resistances Measure the end-to-end resistance of each conductor, R1 (line), Rn (neutral) and R2 (cpc) respectively as indicated in Figure F 3.4a. An open circuit result would suggest either the incorrect conductors have been selected or the circuit is incorrectly terminated. As phase and neutral conductors will be of the same cross-sectional area, the resistance values obtained for both conductors should be similar. Where twin and earth cables to BS 6004 are used, and the cross-sectional area of the cpc is reduced in comparison with the live conductors, the resistance of R2 will be comparatively higher than that of the phase and neutral loops.
F
194
Inspection, Testing and Certification (Part 6)
STAGE 2
L
E
N
L
E
N
0.3
Meter
Figure F 3.4bâ&#x20AC;&#x201A; Continuity of ring final circuits, stage 2.
Stage 2 â&#x20AC;&#x201C; interconnected L-N With phase and neutral interconnected as Figure F 3.4b, measure resistance between phase and neutral conductors at each socket outlet using a continuity tester or similar instrument. If the ring is not interconnected the measurements taken on the ring circuit will be similar. The measurements obtained will be approximately one quarter of the resistance of the sum of the open loop resistances from stage 1, that is (R1 + Rn)/4.
195
F
Guide to the Wiring Regulations
STAGE 3
L
N
E
L
N
E
0.4
Meter
Figure F 3.4câ&#x20AC;&#x201A; Continuity of ring final circuits, stage 3.
Stage 3 â&#x20AC;&#x201C; interconnected L-cpc (for all insulated systems) With phase and cpc interconnected as Figure F 3.4c, measure resistance between phase and cpc conductors at each socket outlet using a continuity tester or similar instrument. If the ring is not interconnected the measurements taken on the ring circuit will be similar. The measurements obtained will be approximately one quarter of the resistance of the sum of the open loop resistances from stage 1, that is (R1 + R2)/4.
F 3.5
Insulation testing Insulation testing is fundamental and will be used as cables are being installed. On completion of the circuit and before energization, the circuit insulation is again checked. The tests show faults or shorts as well as low insulation caused by moisture and similar. Electrical equipment and appliances such as controlgear and lamps should be disconnected prior to testing. Many such devices if left in-circuit would
F
196
Inspection, Testing and Certification (Part 6)
show as an insulation failure; also, sensitive electronic equipment such as dimmer switches and electronic ballasts could be damaged in the test. Insulation resistance is measured between:
••
live conductors, including the neutral; live conductors and the protective conductor connected to the earthing arrangement.
It should be noted that Regulation 612.3.1 states that insulation testing is to be made between the live and protective conductors with the protective conductors connected to the earthing arrangement. This is an additional requirement compared with previous editions of the Standard where, for example, cable could be tested to its cpc and then terminated. This procedure may catch you out as you may not be accustomed to carrying it out – so please note. The basic method of insulation testing is shown in Figures F 3.5 and F 3.6.
Insulation Resistance
Equipment Disconnected
ESSENTIALS
22
0M
Tests
with CPC connected to each system
Test
between all live conductors to neutral and to earth
Readings should be approximately tens of M (min 2 M )
Meter
MCB open
Figure F 3.5 Insulation testing.
197
F
Guide to the Wiring Regulations
Insulation - Industrial Application
Note: L3 ommitted for clarity Steel Conduit
17
Meter
Starter (open)
3M
N L1 L 2 L 3
L L1 N E 2
Supply DB Figure F 3.6â&#x20AC;&#x201A; Insulation testing of motor circuit.
F
198
Inspection, Testing and Certification (Part 6)
Table F 3.1 Minimum value of insulation resistance – normal circuits. Circuit nominal voltage (V)
Test voltage d.c. (V)
Minimum insulation resistance (MW)
Normal LV circuits up to 500 V
500
≥ 1.0
Normal LV circuits up to 500 V where it is difficult to disconnect sensitive equipment
250
≥ 1.0
Table F 3.2 Minimum value of insulation resistance SELV, PELV and circuits above 500 V. Circuit nominal voltage (V) SELV and PELV Above 500 V
Test voltage d.c. (V)
Minimum insulation resistance (MW)
250
≥ 0.5
1000
≥ 1.0
The minimum values of insulation resistance are given in Table 61 of BS 7671: 2008 reproduced here in Table F 3.1 for normal circuits. This minimum value of 1 MW is an increase from the 0.5 MW of the 16th Edition. For most new circuits values would be way in excess of this, usually approaching the maximum scale on the meter. Lesser used, Table F 3.2 gives minimum insulation resistance values for other circuits. Perhaps an underused technique is that of carrying out insulation testing on groups of circuits together as shown in Figure F 3.7, and it is recommended that this is limited to 50 outlets per test.
199
F
Guide to the Wiring Regulations
ESSENTIALS
35
2M
OFF
Up to 50 outlets in final circuits can be tested together as demonstrated here
500 V
Meter
Figure F 3.7 Insulation test of a group of circuits.
F 3.6
Polarity testing Polarity testing is very easy to carry out. There are a few methods and all of the following are acceptable:
•• •• •
visual checks where coloured cables are used; checks as part of the continuity testing using shorted out cable; neon and similar voltage probes; multimeters; indicators on ELI testers and similar.
F
200
Inspection, Testing and Certification (Part 6)
Of all of these the visual check is usually the easiest, and this test is one that is best carried out by the person installing and terminating cables, rather than by the â&#x20AC;&#x2DC;test engineerâ&#x20AC;&#x2122;. Regulation 612.6 requires that every fuse and single-pole control and protective device is connected in the line conductor only. It also requires a check that E14 and E27 lampholders, not to BS EN 60238, have the outer or screwed contacts connected to the neutral conductor; but this does not apply to new installations, as new lampholders should be BS EN 60238 type. Phase rotation The correct phasing of three-phase circuits must of course be checked. For all subcircuits this is usually completed by cable identification and shorting out cables as appropriate. For transformers, generators and the incoming mains LV supply, a phase rotation meter should be used to check for correct phase rotation (Regulation 612.12); follow equipment manufacturersâ&#x20AC;&#x2122; instructions.
F 3.7
Earth fault loop impedance (ELI) testing Earth fault loop impedance is required to be checked at various places throughout the installation, and generally at every point where a protective device is installed. For final circuits, there are two alternative methods of determining the earth fault loop impedance: 1 Direct measurement of total ELI. 2 Measurement of the circuit R1 + R2 value and addition to the ZDB (earth fault loop impedance at the local distribution board). Method 2 is not favoured, as explained in Section F 3.3, but if used the general procedure in this section for ELI measurement is followed, and this is added to the circuit R1 + R2 value, measured as described in Section F 3.3. F 3.7.1 External earth fault loop impedance (Ze) Measurement of external ELI is necessary in LV supplies to confirm the supply earth condition. External ELI is measured live at the intake position, or close to it, with the means of earthing disconnected from the installation and the loop tester connected to it as illustrated in Figure F 3.8. The supply to the installation will need to be isolated. Care should be taken that the installation main equipotential bonding is in place, or that the test is carried out under controlled conditions. The test current on some ELI meters may make exposed-conductive-parts and extraneous-conductive-parts rise in potential in relation to true earth, presenting a
201
F
Guide to the Wiring Regulations
Main Switchgear Supply Terminals L
0.2
N
8
MET
Meter L-E
Supply Network
Installation Network
Figure F 3.8 Measurement of external earth fault loop impedance.
potential hazard to persons or livestock. If main equipotential bonding is in place the potential should be no more than a few volts. Figure F 3.8 is a typical arrangement; in this case for a TN-C-S PME supply. Note that all loop testers illustrated in this book are two lead meters. Three lead loop meters usually perform the same task as two lead units if the neutral and earth leads are connected together, but you should confirm this by consulting the manufacturer’s data. Also note that the connection point of the live supply to the meter is not critical to the result. For UK low-voltage supplies the values should be no more than in Table F 3.3.
Table F 3.3 Maximum external ELI values.
F
Type of system
External earth fault loop impedance Ze (W)
TN-C-S
0.35
TN-S
0.8
TT
21
202
Inspection, Testing and Certification (Part 6)
Substations It should be noted that where a transformer is installed on-site, the use of a ‘contractors’ ELI meter is inappropriate. Small values of resistance cannot be measured on conventional ELI instruments. Confirmation of impedances and d.c. resistance can only accurately be made by calculation and inspection or by the use of ‘milli-ohmmeters’ utilizing four lead connections. Both methods are outside the scope of this book. Conventional ELI meters can be very inaccurate at resolutions below 0.1 ohm. Even at readings of 0.2 and similar a digit ± fluctuation has to be applied, and this should be borne in mind when reading the meter at low values (you may have a negative ELI value!). F 3.7.2 Testing for total earth fault loop impedance (Zs) As mentioned in Section C, earth fault loop impedance may be required at various points throughout the installation and will generally need to be measured at every level of protective device. For confirmation of final circuit disconnection times where RCDs are not installed, measured total earth fault loop impedance is usually required for all circuits.
Zs may be carried out by direct measurement at the extremity of a circuit. Alternatively, Zs may be collectively measured using the components in the following formula: Zs = ZDB + (R1 + R2) where:
ZDB is the earth fault loop impedance at the distribution board supplying the final circuit; (R1 + R2) is the circuit measured line-cpc loop resistance (see Section F 3.3). Whilst carrying out Zs testing, both the main equipotential bonding and the means of earthing are left connected. This advice was given by the ECA for a number of years in order to maintain consistency between Zs results when carrying out periodic testing and testing new installations. When carrying out periodic testing, disconnection of earthing and bonding is simply not practicable. The ECA advice was adopted by the IET.
203
F
Guide to the Wiring Regulations
This does mean that in some installations Zs values measured directly will be less than those measured using the collectively measured Zs = ZDB + (R1 + R2) formula. When comparing the results of measured earth fault loop impedance values with design values, this possible discrepancy should be remembered, as should the matter of possible parallel metallic earth return paths. The physical measurement of ELI is generally as shown in Figure F 3.9, and it should be remembered that RCDs in circuit will trip unless the test instrument has a facility to block unwanted tripping. Some ELI testers can test at such small current levels that they are below the threshold of tripping. Alternatively, the RCD must be linked-out of the circuit. The measured values of Zs should be less than the values given in Chapter 41 of BS 7671: 2008 Tables 41.2, 41.3, 41.4 and 41.5, which are reproduced in Appendix 3. It should be noted that the limiting ELI values given in these tables are design values and should be de-rated by a factor of 0.8.
SUPPLY
Supply Terminals
Distribution Board
L N E
1.2
9
LOOP
Meter L-E
Figure F 3.9â&#x20AC;&#x201A; Measurement of total ELI (Zs).
F
204
INSTALLATION
Inspection, Testing and Certification (Part 6)
F 3.8
Prospective fault current testing Regulation 612.11 requires that the prospective fault current, IPF , under both short-circuit and earth fault conditions, be measured, calculated or determined by another method, at the origin and at other relevant points in the installation. For domestic and LV supplies the utility values can be used and measurement is not required (the utility value is a maximum of 16 kA). Fault current measurement, however, is quite easy to measure for modest fault levels. Most earth fault loop impedance meters double as fault current measuring devices, capable of measuring phase-neutral prospective fault current as well as earth fault current. Figure F 3.10 shows measurement at two positions within an installation.
SUPPLY
Supply Terminals
Distribution Board
INSTALLATION L N E
8.6
4.1
KA
LOOP
Meter
PSCC
KA
LOOP
Meter
PSCC
Figure F 3.10 Measurement of prospective fault current.
205
F
Guide to the Wiring Regulations
Bear in mind that these instruments simply measure the loop impedance and, by Ohm’s law, calculate the fault current. This will give an overestimate of fault current as the fault will have a low power factor, not taken into consideration by the ELI meter. Some test instruments are capable of measuring line-to-line fault current. These work by measuring the line-to-line loop impedance. If these instruments are not used the three-phase fault current is approximated as twice the single-phase level.
F 3.9
Testing RCDs and other functional tests Regulation 612.13.2 requires that switchgear and control gear assemblies, controls and interlocks be functionally tested to check that they work as required. This is part of the commissioning of the electrical installation and not part of the subject of this book. RCD testing RCDs should have their functionality tested by operating the integrated ‘trip’ button. BS 7671: 2008 only requires operating time testing of RCDs where fault protection is provided by an RCD. Where final circuits have overcurrent protection by a fuse or MCB, here are a couple of options:
• •
either test the RCD and rely on this to achieve the disconnection time (usually within 0.4 s); or test the circuit for Zs and if compliant with the tables in Chapter 41, RCD testing is not essential.
In similar fashion to other daring statements in this book, some may be uncomfortable with this suggestion, but you should consider that RCDs are a manufactured ‘type-tested’ device; we do not routinely test the operating characteristics of MCBs. RCD testing itself is relatively simple in terms of using your test instrument connected on the load side of the RCD; Figure F 3.11 shows a typical RCD test. Interpreting results, especially with time-delayed RCDs, can be a little confusing. Table F 3.4 summarizes the maximum RCD trip times for comparison with measured results and includes minimum trip times for time-delayed RCDs.
F
206
Inspection, Testing and Certification (Part 6)
Supply Terminals
SUPPLY
RCD
INSTALLATION
L N E
27m
s
RCD
Meter 30 mA
Figure F 3.11 Testing RCD trip operating times.
Table F 3.4 Trip times for RCDs. RCD type
Sensitivity (mA)
Test current 1 × Dn (mA)
Trip time (ms)
Test current 5 × Dn (mA)
Trip time (ms)
General
10
10
200 max
50
40 max
30
30
150
100
100
500
300
300
1500
500
500
2500
100
100
130 min 500 max
500
40 min 150 max
300
300
130 min 500 max
1500
40 min 150 max
500
500
130 min 500 max
2500
40 min 150 max
Delay type S
Note: Testing should include a 50% no trip test
207
F
Guide to the Wiring Regulations
F 3.10 Verification of voltage drop Notes have been included on this subject because it appears in Part 6 of BS 7671: 2008 and gives rise to some confusion. Regulation 612.14 gives two methods for checking voltage drop, either by measuring a circuit’s impedance or by checking design criteria. The regulation only suggests doing this where it is necessary to verify compliance with the voltage drop requirements. In practice, this will mean where there is a voltage drop problem. The single most important factor that will affect voltage drop under running conditions is the running current, of both the circuit and the whole installation.
F 4
Certification paperwork
F 4.1
Introduction, various certificates and schedules Part 6 of BS 7671: 2008 requires various certificates and schedules to be issued on completion of the installation as follows:
•• •
a completion certificate; or periodic report form where undertaken; and accompanying either of these, results of inspection and test.
This chapter provides in Section F 4.2 a brief overview of the various certificates and accompanying schedules, and a line-by-line brief of how to complete the various forms, in Section F 4.3. Section F 4.3 describes typical certificates and forms and A4 versions of these are available in Appendix 17. The models suggested are as in BS 7671: 2008 with ECA graphics applied.
F 4.2
Overview of certificates and schedules Electrical installation certificate (BS 7671: 2008) This certificate should be used for new installations including alterations and additions. The certificate requires signatures for the three different aspects of design, construction, inspection and test. The certificate should be accompanied by the appropriate schedules of inspections and test results.
F
208
Inspection, Testing and Certification (Part 6)
Single signatory electrical installation certificate (BS 7671: 2008) This is a certificate complying fully with BS 7671: 2008 and is used where one individual or organization has been responsible for the all the aspects of design, construction, inspection and testing. The form is combined with a test schedule comprising a maximum of 18 circuits and a schedule of inspections. Minor electrical installation works certificate (BS 7671: 2008) For certification of installation work that does not include the introduction of new circuits, e.g. the addition of a socket outlet or lighting point to an existing circuit. Schedule of test results This schedule includes all the relevant information from the ‘everyday tests’ described in Section F 3. Schedule of inspections This form is used by the person carrying out the visual inspection and confirms the visual inspections undertaken. Periodic inspection report for an electrical installation (BS 7671: 2008) This is discussed in Appendix 15.
F 4.3
Completing the paperwork This section has been added for completeness and may be skipped by some readers. F 4.3.1 Electrical installation certificate (BS 7671: 2008) ELECTRICAL INSTALLATION CERTIFICATE (BS 7671: 2008) This form meets the model requirements of BS 7671: 2008
PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION CERTIFICATE
EI
Designer (No.1)
Name: ............................................................................. Company: ......................................................................................... Address: ......................................................................................................................................................................................
© Copyright The Electrical Contractors’ Association, The Electrical Contractors’ Association of Scotland.
........................................................................................ Postcode: ................................ Tel No: ...........................................
This certificate is not valid if the number has been defaced or altered.
Designer (No.2) (if applicable)
Name: ............................................................................. Company: ......................................................................................... Address: ......................................................................................................................................................................................
DETAILS OF THE CLIENT
........................................................................................ Postcode: ................................ Tel No: ...........................................
.....................................................................................................................................................................................................................................
Constructor
Name: ............................................................................. Company: ......................................................................................... Address: ......................................................................................................................................................................................
INSTALLATION ADDRESS
........................................................................................ Postcode: ................................ Tel No: ...........................................
.....................................................................................................................................................................................................................................
Inspector
.....................................................................................................................................................................................................................................
DESCRIPTION AND EXTENT OF THE INSTALLATION
Name: ............................................................................. Company: ......................................................................................... Address: ...................................................................................................................................................................................... ........................................................................................ Postcode: ................................ Tel No: ...........................................
Tick boxes as appropriate
Description of installation
�
New installation
Earthing arrangement
Addition to an Extent of installation covered by this Certificate:
existing installation
�
TN-C TN-S
Alteration to an (Use continuation sheet if necessary)
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
existing installation
�
FOR DESIGN
TN-C-S TT IT
I/We being the person(s) responsible for the design of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out that design hereby CERTIFY that the design work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Details of departures from BS 7671: 2008 (Regulations 120.3, 120.4): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the DESIGN of the installation: **(Where there is mutual responsibility for the design) Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Designer No. 1 Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Designer No. 2**
� � � � � �
Alternative Source of supply (to be detailed on attached schedules)
Number and Type of Live Conductors a.c. 1-phase, 2 wire 2-phase, 3 wire 3-phase, 3 wire 3-phase, 4 wire
� � � � �
d.c. 2-pole 3-pole other
Tick boxes and enter details as appropriate
Nature of Supply Parameters
� � � �
Nominal voltage, U/Uo(1) ............................. V
Supply Protective Device Characteristics
Nominal frequency, f(1) ............................... Hz
Type ........................
Prospective fault current, Ipf .................... kA (2)
External loop impedance, Ze(2) ................... 1
Method of Fault Protection
Means of Earthing
Automatic Disconnection (See 411)
Distributor’s facility
�
Installation earth electode
�
�
OTHER ...............................
Tick boxes and enter details as appropriate
Maximum Demand Maximum demand (load) ....................................................................Amps/Phase Details of installation Earth Electrode (where applicable) Type (e.g. rod(s), tape etc) Location Electrode resistance to Earth ...........................................
..................................
........................................... 1
Main Protective Conductors
FOR CONSTRUCTION I/We being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that the construction work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Details of departures from BS 7671: 2008 (Regulations 120.3, 120.4):
Earthing Conductor Main equipotential bonding conductors To incoming water service To lightning protection
material ....................... material .......................
� �
To incoming gas service To other incoming service(s)
csa .......................mm2 csa .......................mm2
� �
To incoming oil service
�
To structural steel
�
(state details ..............................................................................)
Main Switch or Circuit-breaker
The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the CONSTRUCTION of the installation: Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Constructor
Type and No. of poles ......................................
Current rating ............................. A
Location .............................................................
Fuse rating or setting ................. A
Voltage rating .................................................V
FOR INSPECTION & TESTING
Rated residual operating current ........................... mA and operating time of ................... ms
I/We being the person(s) responsible for the inspection & testing of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection & testing hereby CERTIFY that the construction work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Details of departures from BS 7671: 2008 (Regulations 120.3, 120.2):
COMMENTS ON EXISTING INSTALLATION
(applicable only when an RCD is suitable and is used as a main circuit-breaker)
(in case of an alteration or addition see Section 743)
..................................................................................................................................................................................................................................... ..................................................................................................................................................................................................................................... ..................................................................................................................................................................................................................................... .....................................................................................................................................................................................................................................
The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the INSPECTION AND TEST of the installation:
COMMENTS ON EXISTING INSTALLATION
Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Inspector
NEXT INSPECTION
The attached Schedules are part of this document and this Certificate is valid only when they are attached to it. .....................Schedules of Inspection and.....................Schedules of Test Results are attached.
I/We recommend that the installation should be re-inspected after an interval of not more than ..................................... months/years 09/07
Nominal current rating .................. A
(Note (1) by enquiry, (2) by enquiry or by measurement)
PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE
Page 1 of
(Enter quantities of schedules attached).
09/07
Page 2 of
(For A4 versions, see Appendix 17.)
209
F
Guide to the Wiring Regulations
Details of the client Insert client’s name and title. Installation address Insert address of installation. Description and extent of installation Describe the extent and limitation of the certificated work. Tick, as appropriate, the box for either new installation, addition to an existing installation or alteration to an existing installation. Design, Construction, Inspection & Testing The appropriate sections should be completed and signed by competent personnel authorized by those responsible for the work of design, construction, inspection and testing respectively. The relevant amendment date of BS 7671 must be added. Any departures from BS 7671 must be indicated. Next inspection Add the appropriate recommended date of next inspection – see Section F 4.3.6. Particulars of signatories To be completed by the organizations responsible for each aspect of design, construction, inspection and test. Supply characteristics and earthing arrangements Earthing arrangement Add tick to the appropriate box noting the (external) supply characteristic. Number and type of live conductors Tick appropriate box(es). Nature of supply parameters The nominal supply voltage between phases (U ), the voltage to earth (Uo) and the frequency must be added after confirmation by the supply company. The prospective fault current, being the larger of the short-circuit current and the earth fault current, shall be recorded – this is determined either by enquiry, measurement or calculation. The external earth fault loop impedance, Ze, shall be recorded and is determined either by enquiry, measurement or by calculation.
F
210
Inspection, Testing and Certification (Part 6)
Supply protective device characteristic Type – add type of supply protective device. Also add the protective device current rating. Particulars referred to in the certificate Method of fault protection Either tick EEBADOS (Earthed Equipotential Bonding and Automatic Disconnection of Supply) or, if this method is not used, enter ‘see attached’ in space provided and include the necessary details with the certificate. Means of earthing Tick appropriate box – see Chapter E. Maximum demand The maximum demand is the designer’s estimation of the maximum load demand of the installation expressed in kVA or amps per phase and takes into account diversity. Further guidance on this subject can be found in Chapter C of this book. F 4.3.2 Single signatory electrical installation certificate (BS 7671: 2008) SI
Electrical Installation Certificate BS 7671: 2008 - Single Signatory
SUB-MAIN (WHERE APPLICABLE)
BS 7671: 2008 Requirements for Electrical Installations (17th Edition IEE Wiring Regulations) © Copyright The Electrical Contractors’ Association,
(For use in certification of AC installations only)
This certificate is not valid if the number has been defaced or altered.
DETAILS OF CLIENT
CIRCUIT
REF
New Installation ........�
PROTECTION ...........Amps
Zdb ........................... Ohms
PROSPECTIVE FAULT CURRENT .............................................................. kA
INSTALLED CIRCUIT DETAILS OVERCURRENT DISC DEVICE SHORTTIME CIRCUIT CAPACITY........kA
INSTALLATION ADDRESS:
DESCRIPTION AND EXTENT OF INSTALLATION COVERED BY THIS CERTIFICATE
DISTRIBUTION BOARD REF: ........................... LOCATION ......................................................................................................................
TYPE .........................SIZE.................mm2
A
DESCRIPTION B
TEST RESULTS CONDUCTORS
R1 + R2 Ω
Ph - Ph Ω
CONTINUITY
N-N Ω
CPC - CPC Ω
L-L MΩ
INSULATION RESISTANCE
L-E MΩ
P O L A R I T Y
H
J
K
L
M
N
P
RING
TYPE
RATING AMPS
INSTALLED REF METHOD
C
D
E*
SIZE LIVE CPC mm2 mm2
F
G
EARTH FAULT
RCD
LOOP TRIP IMPEDANCE TIME OTHER Zs AT 1∆n FUNCTION ms Ω TESTS
R
S
T
REMARKS V
Addition .....................� Alteration ...................� FOR DESIGN, CONSTRUCTION, INSPECTION & TESTING
Name .................................................................................................................
I/We, being the person responsible for the Design, Construction, Inspection & Testing of the electrical installation (as indicated by my signature below), particulars of which are described above, having exercised reasonable skill and care when carrying out the Design, Construction, Inspection & Testing, hereby CERTIFY that the said work for which I/we have been responsible is to the best of my knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Departures and comments on existing installation:- .................................................................................... ........................................................................................................................................................................... ........................................................................................................................................................................... ...........................................................................................................................................................................
for ..................................................................................................................... ........................................................................................................................... ........................................................................................................................... Position ................................................................ ............................................................................... ............................................................................... I/We recommend that the installation be further inspected and tested after an interval of not more than ............................. years.
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS Voltage .................V
Prospective Fault
Frequency ..........Hz
Current ................................kA Earth Fault Loop Impedance Ze ................Ohms
Number and Type of Live Conductors
� ...........2 No. 1-Phase � ...........3 No. 3-Phase � ...........4 No. 3-Phase
PARTICULARS OF INSTALLATION REFERRED TO IN THIS CERTIFICATE Method of fault protection: Earthed equipotential � bonding and automatic � disconnection of supply
Supply Protection Type ................................. Current Rating ..........................A
Earthing Arrangements TN-S TN-C-S TT Other ...........................
� � �
Main Switch
Maximum Demand
Location ...........................................................................
.......................................... Amps Per Phase
Type ................................................... RCD 1∆n .........mA
� or Details of Earth
Type .................................................................. Location ............................................................ Resistance ...............................................Ohms COMMENTS ON INSTALLATION:
Main Protective Conductors Earthing
Rating ................................................ Amps (Per Phase)
RCD Time Delay ..........................................................ms
Supply Earth Electrode
Bonding
� Copper CSA ..........mm2 � Steel � Aluminium � Copper CSA ..........mm2 � Steel � Aluminium
09/07
TEST INSTRUMENTS USED INSTRUMENT
TYPE
SERIAL No.
ACCURACY VERIFIED
COMPANY: .........................................................
Connections � Verified
SIGNED: .............................................................. * Denotes optional information only
SHEET 1 OF ____
TESTER DETAILS NAME: ................................................................
Connections � Verified
DATE: .................................................................
09/07
SHEET 2 OF ____
(For A4 versions, see Appendix 17.)
Certificate overview Where design, construction and inspection and testing are the responsibility of one person or organization, this single signatory certificate can be used and fully complies with BS 7671: 2008. It also combines a test sheet and can be used for an installation of up to 18 circuits of any current rating. Details of client Insert client’s name and title.
211
F
Guide to the Wiring Regulations
Installation address Insert address of installation. Description and extent of installation Briefly describe the installation and describe the extent and limitation of the certificated work. Tick, as appropriate, the box for either new installation, addition to an existing installation or alteration to an existing installation. Design, construction, inspection and testing This section should be completed and signed by the individual responsible for the work of design, construction, inspection and testing of the installation. The relevant BS 7671 amendment date should be added. Next inspection Add the appropriate recommended date of next inspection â&#x20AC;&#x201C; see Section F 4.3.6. Supply characteristics and earthing arrangements Voltage Add supply voltage to earth (Uo) and supply frequency in Hz. The prospective fault current must be recorded, and is the larger of the short-circuit current and earth fault current established by enquiry or measurement. The external earth fault loop impedance Ze shall be recorded and may be measured or determined by enquiry. Number and type of live conductors Tick appropriate box(es). Supply protection Type â&#x20AC;&#x201C; add type of supply protective device. Also add the protective device current rating. Earthing arrangement Tick appropriate box noting the (external) supply characteristic. Supply earth and earth electrode Where there is an electricity company earth, tick the box. If there is a private earth electrode system, provide details here.
F
212
Inspection, Testing and Certification (Part 6)
Particulars of installation referred to in this certificate Method of fault protection The certificate can only be used for normal ADOS (Automatic Disconnection of Supply) and this method has been pre-ticked to indicate this. Maximum demand The maximum demand is the designerâ&#x20AC;&#x2122;s estimation of the maximum load demand of the installation expressed in kVA or amps per phase and takes into account diversity. Further guidance on this subject can be found in Chapter C. Main switch or circuit breaker Complete all entries. Main protective conductors Complete as necessary. Submain Add details of submain where applicable. Distribution board Add details â&#x20AC;&#x201C; Zs and prospective fault current are measured (or calculated) at the distribution board. Note: do not add external readings. Installed circuit details A Add circuit reference. B Describe circuit briefly, i.e. ring, socket outlets. Top of columns C & D Add short circuit breaking capacity of overcurrent device as follows: BS
Type
Typical breaking capacity (kA)
BS 88
HRC cartridge fuse
80
BS 3036
Rewireable
2
BS 1361
Household cartridge fuse
16.5
BS EN 60898
Circuit breaker
3, 6, 9, or 16
C Add type of protection device. For fuse add BS number, for circuit breaker add sensitivity type B, C or D. D Add current rating of protective device. E Optional column. Add installed reference method from Appendix 4 of BS 7671.
213
F
Guide to the Wiring Regulations
F Add line and neutral conductor size where they are the same. If reduced neutral add to remarks column. G Add cpc size. Optionally, for armoured cables, add cross-sectional area of armour in mm2. If not SWA add material type. H Continuity. Add maximum value obtained from method used to check continuity of cpc at all points on circuit and delete R1 + R2 or R2 as appropriate, depending upon method used. Optionally, this column may be ticked. Where the circuit is a ring the (R1 + R2) value must be inserted into column H and will be the (R1 + R2) on the ring with the phase and cpc cross-connected at the board. See Section F 3.4. J, K & L ring continuity only J Add open phase/phase resistance. K Add open neutral/neutral resistance. L Add open cpc/cpc resistance. Insulation resistance M Test between phase conductors and phase to neutral and record the minimum. N Test phase to earth and neutral to earth either together or separately and record the minimum. P Polarity. Tick when polarity at all points has been checked. R Earth fault loop impedance. Either add Ze at incomer (distribution board) to the (R1 + R2) value or measure at remote part of circuit. Record the maximum value measured. Functional tests S Check RCD trip time at normal rate current setting only. T Tick this column after functional checks are made including: assemblies, switchgear/control gear, drives, controls and interlocks to show they are properly mounted, adjusted and installed in accordance with BS 7671: 2008. Other comments Add relevant comments. Test instruments used Add details of all instruments used whilst testing.
F
214
Inspection, Testing and Certification (Part 6)
F 4.3.3 Minor electrical installation works certificate (BS 7671: 2008) MINOR ELECTRICAL INSTALLATION WORKS CERTIFICATE (BS 7671: 2008) To be used only for the completion and inspection certification of electrical installation work which does not include a new circuit.
MW
© Copyright The Electrical Contractors’ Association This certificate is not valid if the number has been defaced or altered.
PART 1: DESCRIPTION OF MINOR WORKS 1. Description of the minor works 2. Location/Address 3. Date minor works completed 4. Details of departures, if any, from BS 7671: 2008
PART 2: INSTALLATION DETAILS
� TN-S � �
TT
�
1. System earthing arrangements (where known)
TN-C-S
2. Method of fault protection
EEBADS OTHER ........................................................................ (411) Type ...................................................... Rating ........................................A
3. Protective device for the modified circuit
Comments on existing installation, including adequacy of earthing and bonding arrangements: (see Regulation 131.8)
PART 3: ESSENTIAL TESTS Earth continuity satisfactory
�
Insulation resistance: Phase/neutral ................................................... M1
(Where practical)
Phase/earth ...................................................... M1 Neutral/earth ................................................... M1 Earth fault loop impedance ........................................................... 1 Polarity satisfactory
�
RCD operation (if applicable).
Rated residual operating current ....................... mA and operating time of ....................... ms
INSTRUMENTS USED Manufacturer
Type
Serial Number
Date Accuracy Verified
PART 4: DECLARATION I/We CERTIFY that the said works do not impair the safety of the existing installation, that the said works have been designed, constructed, inspected and tested in accordance with BS 7671: 2008 (IEE Wiring Regulations), and that the said works, to the best of my/our knowledge and belief, at the time of my/our inspection, compiled with BS 7671: 2008 except as detailed in part 1. Name: ....................................................................................................
Signature: ............................................................................................
For and on behalf of: ...........................................................................
Position: ...............................................................................................
Address: ................................................................................................ ................................................................................................................ ................................................................................................................
Date: ....................................................................................................
09/07
(For A4 version, see Appendix 17.)
This certificate is fully compliant with BS 7671: 2008 when used for the certification of electrical work which does not include a new circuit (e.g. circuit extensions). It should not be used for a consumer unit change. Description of minor works Complete as necessary. Installation details 1 System earthing arrangements – tick appropriate box. 2 Tick boxes or describe other methods as appropriate. 3 Add BS and type of protective device and list its rating. Add any relevant comments. Essential tests Complete these minimum essential tests including the installation phase to neutral test only where practical. Instruments used List all instruments used while testing. Declaration Sign as necessary.
215
F
Guide to the Wiring Regulations
F 4.3.4 Schedule of test results T
SCHEDULE OF TEST RESULTS © Copyright The Electrical Contractors’ Association The Electrical Contractors’ Association of Scotland SUB-MAIN
PROJECT:
JOB No:
DISTRIBUTION BOARD
TESTER DETAILS
TYPE: ..........................
REF: ................. LOCATION: .....................................................................................
SIZE: ................... mm2
Zdb: ................. OHMS: ....................................
PROTECTION: .............
PFC: ................. kA (Prospective Fault Current)
COMPANY: ................................................. SIGNED: ...................................................... DATE: .........................................................
INSTALLED CIRCUIT DETAILS CIRCUIT
REF
No OF POINTS SERVED
DESCRIPTION
A
B
OVERCURRENT DISC DEVICE SHORTTIME CIRCUIT CAPACITY........kA
W*
NAME: ........................................................
TEST RESULTS CONDUCTORS:
R1 + R2 Ω
Ph - Ph Ω
CONTINUITY
N-N Ω
CPC - CPC Ω
L-L MΩ
L-E MΩ
P O L A R I T Y
H
J
K
L
M
N
P
TYPE:.........................
TYPE
RATING AMPS
INSTALLED REF METHOD
C
D
E*
SIZE LIVE CPC mm2 mm2
F
G
INSULATION RESISTANCE
RING
COMMENTS ON INSTALLATION:
EARTH FAULT
RCD
LOOP TRIP IMPEDANCE TIME OTHER Zs AT 1∆n FUNCTION ms Ω TESTS
R
S
T
REMARKS V
TEST INSTRUMENTS USED INSTRUMENT
TYPE
SERIAL No.
ACCURACY VERIFIED
* Denotes optional information only 09/07
SHEET 3 OF 3
(For A4 version, see Appendix 17.)
Project Add details. Job no. Optional, for your company use. Submain Add details where applicable. Distribution board Add details – Zs and prospective fault current are measured (or calculated) at the distribution board. Installed circuit details A Add circuit reference. B Describe circuit briefly, i.e. ring, socket outlets. Top of columns C & D Add short circuit breaking capacity of overcurrent device as follows: BS
Type
Typical breaking capacity (kA)
BS 88
HRC cartridge fuse
80
BS 3036
Rewireable
BS 1361
Houshold cartridge fuse
16.5
BS EN 60898
Circuit breaker
3, 6, 9, or 16
2
C Add type of protection device. For fuse add BS Number, for circuit breaker add sensitivity type B, C or D. D Add current rating of protective device.
F
216
Inspection, Testing and Certification (Part 6)
E Optional column Add installed reference method from Appendix 4 of BS 7671. F Add line and neutral conductor size where they are the same. If reduced neutral add to remarks column. G Add cpc size. Optionally, for armoured cables, add cross-sectional area of armour in mm2. If not SWA add material type. H Continuity. Add maximum value obtained from method used to check continuity of cpc at all points on circuit and delete (R1 + R2) or R2, as appropriate, depending upon method used. Optionally, this column may be ticked. Where the circuit is a ring the (R1 + R2) value must be inserted into column H and will be the (R1 + R2) on the ring with the phase and cpc cross-connected at the board. See Section F 3.4. Ring continuity only J Add open phase/phase resistance. K Add open neutral/neutral resistance. L Add open cpc/cpc resistance. Insulation resistance M Test between phase conductors and phase to neutral and record the minimum. N Test phase to earth and neutral to earth either together or separately and record the minimum. P Polarity. Tick when polarity at all points has been checked. R Earth fault loop impedance. Either add Ze at incomer (distribution board) to the (R1 + R2) value or measure at remote part of circuit. Record the maximum value measured. Functional tests S Check RCD trip time at normal rate current setting only. T Tick this column after functional checks are made including: assemblies, switchgear/control gear, drives, controls and interlocks to show they are properly mounted, adjusted and installed in accordance with BS 7671: 2008. V Add any relevant remarks to each circuit. Other comments Add relevant comments to section. Test instruments used Add details of all instruments used whilst testing.
217
F
Guide to the Wiring Regulations
F 4.3.5 Schedule of inspections SCHEDULE OF INSPECTIONS (BS 7671: 2008)
I
PROJECT:
JOB No:
INSPECTED BY:
DATE:
Notes: � to indicate an inspection has been carried out and the result is satisfactory � to indicate an inspection has been carried out and the result is unsatisfactory N/A to indicate an inspection is not applicable LIM to indicate that, exceptionally, a limitation agreed with the person ordering the work prevented the inspection being carried out
Methods of protection against electric shock Both basic and fault protection: (i)
SELV
(ii)
PELV
(iii) Double insulation (iv)
Reinforced insulation
Basic protection (i)
Insulation of live parts Barriers or enclosures
Proximity of non-electrical services and other influences
(b)
Segregation of Band I and Band II circuits or use of Band II insulation
(c)
(b) (c)
(iii) Obstacles Placing out of reach
Fault protection: (i)
(a)
(d)
Presence of diagrams, instructions, circuit charts and similar information Presence of danger notices and other warning notices Labelling of protective devices, switches and terminals Identification of conductors
Cables and conductors Selection of conductors for current-carrying capacity and voltage drop
Automatic disconnection of supply: Presence of earthing conductor
Erection methods
Presence of circuit protective conductors
Routing of cables in prescribed zones
Presence of protective bonding conductors
Cables incorporating earthed armour or sheath, or run within an earthed wiring system, or otherwise adequately protected against nails, screws and the like
Presence of supplementary bonding conductors Presence of earthing arrangements for combined protective and functional purposes
Additional protection provided by 30 mA RCD for cables in concealed walls (where required in premises not under the supervision of a skilled or instructed person)
Presence of adequate arrangements for alternative source(s), where applicable FELV
Connection of conductors
Choice and setting of protective and monitoring devices (for fault and/or overcurrent protection)
(ii)
Non-conducting location:
(iii)
Earth-free equipotential bonding:
(iv)
Electrical Separation:
Absence of protective conductors
Presence of earth-free equipotential bonding
Presence of fire barriers, suitable seals and protection against thermal effects
General Presence and correct location of appropriate devices for isolation and switching Adequacy of access to switchgear and other equipment Particular protective measures for special installations and locations
Provided for one item of current-using equipment
Connection of single-pole devices for protection or switching in line conductors only
Provided for more than one item of currentusing equipment
Correct connection of accessories and equipment
Additional protection:
09/07
Segregation of safety circuits
Identification (a)
(ii)
(iv)
Prevention of mutual detrimental influence
Presence of undervoltage protective devices
Presence of residual current devices(s)
Selection of equipment and protective measures appropriate to external influences
Presence of supplementary bonding conductors
Selection of appropriate functional switching devices
© Copyright The Electrical Contractors’ Association
Page ___ of ___
(For A4 version, see Appendix 17.)
Simply insert a tick into the appropriate box indicating the inspections made. Add a ‘N/A’ to the box where the inspection is not applicable. You may feel it is appropriate to insert ‘LIM’ (for limitation) into a box where the inspection type is limited to certain areas. If this is the case, you should create your own ‘LIM’ legend on the schedule. The schedule should be used with an associated Electrical Installation Certificate or Periodic Inspection Report. F 4.3.6 Recommended frequencies of next inspection The frequencies of ‘next’ inspection are shown in Table F 4.1 and reproduced from IEE Guidance Note 3. Table F 4.1 Recommended initial frequencies of electrical installation inspections.
1 2
F
Type of installation
Maximum period between inspections and testing as necessary
Domestic
Change of occupancy/10 years
All commercial i.e. shops, offices, hospitals and labs etc.
Change of occupancy/5 years
Industrial
3 years
Places subject to entertainment licence
1 (note 2)
1,2
Public swimming pools, caravan parks
1 year
1,2
See also Electricity at Work Regulations 1989. This is normally a requirement of local licensing organizations.
218
Reference (see notes below)
1
Special Locations
G
Special Locations G 1
Introduction: Purpose and principles
G 1.1
Introduction Part 7 of BS 7671: 2008 makes specific references to electrical installations in areas defined as ‘Special Installations or Locations’. As well as having to comply with the general requirements of BS 7671, some further requirements or restrictions apply to installations in these special locations. The term ‘special’ therefore means application of particular requirements in addition to the general rules of BS 7671 within Parts 1 to 6. BS 7671 introduces some six new ‘Part 7’ special locations making a total of 14 in all, and the complete list is shown in Figure G 1.1. The provision of special locations sections has increased in IEC over the years, and it may be argued that in some cases they are not really ‘special’, but they have been accepted internationally. Some of the special locations in BS 7671: 2008 locations are not discussed in this book, as most designers and contractors do not get involved with them. Figure G 1.1 shows the Part 7s discussed in this book and those that are not. Some requirements have been removed from those provided in the 16th Edition, for example, Section 607 ‘High protective conductor currents’ and Section 611 ‘Installation of highways power supplies, street furniture and street located equipment’; these sections have both been incorporated into the general rules, i.e. 543.7 and 559.10, respectively, of the 17th Edition.
219
G
Guide to the Wiring Regulations
Special Locations Included in this book 701 Bathrooms
702 Swimming Pools
705 Agricultural and Horticultural
708 Caravan Parks
711 Exhibitions, Shows and Stands
712 PV Cells
717 Mobile or Transportable Units
753 Floor and Ceiling Heating Units
Not included in this book 703 Saunas
704 Construction Sites
706 Restricted Movement
709 Marinas
721 Within Caravans
740 Fairgrounds
Figure G 1.1 Part 7 sections showing those discussed in this book.
G 1.2
Purpose and principles In general, such ‘Special Installations or Locations’ listed in BS 7671 involve increased risks and/or harsher conditions compared with those catered for by the general parts (Parts 1–6). Risk here is risk of danger as defined in part 2 of the Regulations:
• • • •
Onerous site conditions that may impair the effectiveness of the electrical or environmental protective measures. Increased risk of contact with earthed metalwork, usually extraneousconductive-parts. Water or condensation giving reduced body resistance and better electrical contact. Absence of shoes or clothing (e.g. bathing or swimming) and therefore a greater opportunity to make contact with live parts or earthed metalwork, or actual contact with Earth itself.
G
220
Special Locations
The requirements for such locations have been developed by continual assessment of such risks, and the application of protective and environmental measures seen to be necessary to reduce the foreseen risks. Designers and installers must assess the environment, use and risks at the locations for which they are designing and constructing installations, and make provisions accordingly – a high level of competence and relevant experience is required. Designers and installers must also comply with the requirements of legislation and relevant building regulations. Installations must be properly verified and commissioned, with initial inspection and testing as required by Part 6 of BS 7671. All installations must be properly maintained and periodically inspected and tested, depending on their age, application and condition. An assessment of the expected maintenance that an installation will receive should be made as part of the design process, and if necessary the design and materials selected should be amended accordingly.
G 1.3
Particular requirements and numbering It is the case that Part 7s are intended to supplement or modify the general requirements of Parts 1–6. In line with this is new numbering, which is meant to highlight the particular requirements; this uses the Part 7 numbering followed by the ‘general rules’ clause. An example from 701 (bathrooms) is as follows: 701.41 Protection for safety: protection against electric shock 701.410.1 General requirements 701.410.3.5 The protective measures of obstacles and placing out of reach (Section 417) are not permitted. Regulation 410.3.5 in Part 4 of the Standard has been modified for this Part 7 Regulation 701.410.3.5 above.
G 2
Locations containing a bath or shower (701)
G 2.1
Introduction and risks Bathroom installation regulations have perhaps always been somewhat contentious and have undergone a number of changes in requirements in the last ten years. The requirements have again changed in the 17th Edition of BS 7671 and indeed have
221
G
Guide to the Wiring Regulations
become simpler. This part now harmonizes with the corresponding CENELEC part, and introduces some significant changes for the UK. In a bathroom or shower room the increased risks are from exposed wet skin (with a lower contact resistance), the splashing and ingress of water, and the usual close proximity of earthed metalwork. There may also be further risks due to disability or infirmity. Medical locations are not considered in detail, and such medical locations as birthing pools need special provisions outside the scope of this document.
G 2.2
Zone concept The concept of zones was introduced into BS 7671 for the 2001 edition and allowed different rules to be applied to different areas. The concept of zones remains in BS 7671: 2008 but Zone 3 has been removed. This is one of the most significant regulation changes in the whole document; without a Zone 3, there are no specific rules for Zone 3 and only the general rules apply. Hence, equipment can be installed at the boundary of Zone 2. The zones provide a means of controlling the location type and environmental rating of electrical equipment installed in a bathroom. They are only a guide and, regardless of this, the installation must be properly designed to take into account all foreseen risks in the design of a bathroom within a particular building. The Regulations actually apply to ‘locations containing a fixed bath or shower’, and this can therefore include bedrooms, changing facilities in workshops or sports clubs, etc. These will require different design solutions from those for a domestic bathroom, and in all cases full consultation with the client’s advisers and equipment manufacturers is essential. Unfortunately, not all electrical equipment or accessories have IP ratings, but manufacturers will be able to provide guidance in the selection and application of their products. The zones are specified in regulations and are summarized as follows:
•• •
Zone 0 is the bath or shower tray. Zone 1 can be considered to be the area where the individual is bathing or showering, or the area where shower water is likely to be directly sprayed. Zone 2 is the area beyond Zone 1, extending by a further 600 mm.
The layout of the zones is illustrated in Figures G 2.1 and G 2.2 for a number of bathroom and shower room arrangements. Other layouts such as bedrooms with shower cubicles, changing rooms and the like must be considered; the concepts of the zones should be extended accordingly.
G
222
Special Locations
Key Zone 0 Zone 1 Zone 2
Generally the bath or shower tray Generally where the individual will be bathing/showering Generally outside Zone 1 extending a further 600 mm
s = thickness of partition y = radial distance from water outlet
Window recess Zone 2
Window recess Zone 2
Zone1
Zone1
Zone 2
Zone 2
Zone 0
Window recess Zone 2
Zone 0
Zone 2
Zone 1
s (0.6-s) m
b. Bath tub with permanently fixed partition
a. Bath tub
Zone 0
0.6 m
Window recess Zone 2
0.6 m
Zone 0
Zone 2
Zone 2
Zone1
0.6 m s (0.6-s)
d. Shower basin with permanently fixed partition
c. Shower basin
Figure G 2.1â&#x20AC;&#x201A; Bathroom zone dimensions plans (aâ&#x20AC;&#x201C;d). (Continued.) f. Shower, without basin, but with permanent fixed partition
e. Shower, without basin
Fixed water outlet 1.20 m
Fixed water outlet x
x
y s
(1.2-y-s) m
223
G
(0.6-s)
c. Shower basin Guide to the Wiring Regulations
d. Shower basin with permanently fixed partition
f. Shower, without basin, but with permanent fixed partition
e. Shower, without basin
Fixed water outlet
Fixed water outlet
x
x
y
1.20 m
s
Zone 1 Zone 2
Zone 1 Zone 2
(1.2-y-s) m
1.20 m
Figure G 2.1 (Continued.) Bathroom zone dimensions plans (e–f).
Key Zone 0
Generally the bath or shower tray
Zone 1
Generally where the individual will be bathing/showering
Zone 2
Generally outside Zone 1 extending a further 600 mm
s = thickness of partition y = radial distance from water outlet a. Bath tub Ceiling Outside Zones Window Recess Zone 2 Outside Zones Zone 1
Zone 2
2.25 m
* 0.60 m
c. Shower basin Recess above ceiling Figure G 2.2 Bathroom zone dimensions elevations (a). (Continued.) Luminaire Ceiling Outside Zones
G
224
Special Locations
* 0.60 m
c. Shower basin Recess above ceiling
Luminaire
Ceiling Outside Zones
Outside Zones Zone 1
Zone 0
Zone 2
2.25 m
* 0.60 m
f. Shower without basin, but with permanent fixed partition Section x-x, see Fig. F2.1 (f) Ceiling Outside Zones
Outside Zones
10 m
Zone 1
Zone 1
Zone 0
Zone 0
2.25 m
Permanent partition * Zone 1 if the space is accessible without the use of a tool. Spaces under the bath accessible only with the use of a tool are outside the zones.
Figure G 2.2â&#x20AC;&#x201A; (Continued.)
For electrical provisions the general requirements of BS 7671 apply, but the extra provisions in Section 701 must supplement these. Obviously, not all the protective measures for installations are applicable in bathrooms; the protective measures for obstacles, placing out of reach, non-conductive locations and earth-free equipotential bonding are not permitted, and it is not difficult to see why.
225
G
Guide to the Wiring Regulations
Table G 2.1 Bathroom electric shock requirements.
G 2.3
Requirement
Regulation
All circuits to have 30 mA RCD
701.411.3.3
Socket outlets to be 3 m from the outer limit of Zone 1 (except SELV)
701.512.3
Where main equipotential bonding is used in the installation, no local supplementary bonding is required
701.415.2
Obstacles and Out Of Reach are not permitted
701.410.3.5
Non-conducting location and earth-free local equipotential bonding are not permitted
701.410.3.6
Electrical separation can only be used for single items
701.413
For SELV and PELV basic protection must be used
701.414.4.5
Electric shock requirements The requirements in addition to the general rules are summarized in Table G 2.1. Perhaps the most significant change in this section in the 17th Edition is the fact that there are only regulations for Zones 1 and 2. Outside of Zone 2 the general rules of the Standard apply, but in reality virtually any equipment can now be installed outside Zone 2. The only caveat concerns socket outlets, where Regulation 701.512.3 prohibits them within 3m of the outer limit of Zone 1 (unless they are SELV). Some individuals will feel uncomfortable installing socket outlets even under these conditions (and despite the fact that they will be RCD protected, see below). All circuits supplying the bathroom are now to be provided with additional protection by the use of an RCD with a rated residual operating current not exceeding 30 mA. However, where this is provided, supplementary equipotential bonding is not required. The use of RCDs on all circuits, including lighting circuits, may cause some problems initially (e.g. with possible increased risk of hazards if lights go out unexpectedly). These can be overcome relatively easily with some planning; e.g. the bathroom on a separate lighting circuit or two lighting circuits for the bathroom and surrounding rooms. Protection by electrical separation may be used, but this is a difficult concept to achieve in practice and is usually only provided as a shaver socket outlet; however, the supply to such an outlet will still require RCD protection.
G
226
Special Locations
Separated extra low voltage (SELV) systems may be installed, but again these are difficult to achieve in practice, and need to be maintained and controlled by a competent person. Protected extra low voltage (PELV) systems are more common but again difficult to achieve in practice and must be properly designed and specified, so such systems are rarely utilized. The requirements of the 17th Edition of BS 7671 are not retrospective. This edition, however, now allows that supplementary equipotential bonding is not required in bathrooms provided that each circuit in the bathroom is provided with additional protection by an RCD sensitivity not exceeding 30 mA. This will be the preferred solution in new developments, but there are many existing dwellings and other locations with bath and shower facilities that already have supplementary equipotential bonding, and when bathrooms are modified or refurbished it may be more economic to extend or modify this rather than rewire and install RCDs.
G 2.4
Equipment selection and erection The equipment requirements of Section 701 are summarized in Table G 2.2, and the requirements fall into two types of regulation – ingress protection and suitability as regards switches and accessories.
Table G 2.2 Bathroom equipment selection and erection requirements. Requirement
Regulation
Equipment in Zone 0 shall be IP X7
701.512.2
Equipment in Zones 1 and 2 shall be IP X4
701.512.2
Equipment exposed to cleaning jets to be at least IP X5
701.512.2
In Zone 0, no switchgear or accessories allowed
701.512.3
In Zone 0, only 12 V current-using equipment complying with a relevant Standard is allowed
701.55
In Zone 1, only 12 V SELV switchgear or accessories allowed
701.512.3
In Zone 1, only whirlpool units, electric showers, shower pumps, ventilation equipment, towel rails, water heaters, luminaires and 25 V SELV or PELV equipment is allowed
701.55
In Zone 2, SELV switches and socket outlets and shaver supply socket outlets to BS EN 61558–2-5 are the only allowed switchgear or accessories
701.512.3
Notes
Particular requirements exist for IP and water jets; see D 16.2
227
G
Guide to the Wiring Regulations
The general principle of this group of regulations is that unsuitable electrical equipment must be inaccessible to persons in the bath or shower (when they are in the bath or shower, Zone 1). This is deemed to be outside Zone 2. This ‘inaccessibility’ principle extends to electrical equipment generally, and only switches using insulated linkages or pull cords to operate BS 3676 devices, or specially designed controls to BS 3456 (instantaneous water heaters), are permitted within the zones. It is accepted, however, that a shaver supply unit with a BS EN 61558–2–5 transformer may be installed, as may switches supplied by SELV where the nominal voltage does not exceed 12 V rms. Fixed equipment within the 2.5 m zone must be selected and erected according to foreseen risks, and its likely duty. The likelihood is for splashing water to be present, and this requires an IP rating dependent on its location in the room. Power showers can generate penetrating jets of water, and may require a minimum of IPX5 equipment. BS 7671 does not actually prohibit the use of Class I fixed equipment for outside of Zone 2, but luminaires to be fixed within these areas should preferably be either totally enclosed, or if of Type B22, should be fitted with a BS 5042 (Home Office) shield. In general, those responsible for selection and erection of equipment will find that Class II devices more readily satisfy the requirements of bathrooms. With the increased use of pumped water in bathrooms for spa-baths, power showers, etc. there is a need, on occasion, to provide for motive power within the area of the bath. In order to protect against direct and indirect contact, supplies for such equipment must be by SELV with the nominal voltage not exceeding 12 V rms. Where it is necessary to mount the SELV source within the bath enclosure, then it may only be accessible by means of a tool. The reason for this is concerned with the now familiar definition of a skilled person, i.e. it is assumed that persons using a tool to access the SELV source under a bath will be sufficiently informed and skilled to avoid danger and that the circuit will be dead and isolated before work is commenced.
G 3
Swimming pools and other basins (702)
G 3.1
Introduction and risks BS 7671: 2008 maintains the next Special Location in Part 7 as ‘Swimming Pools and Other Basins’. The ‘other basins’ is important as the section applies to the
G
228
Special Locations
basins of fountains and to areas in natural waters including the sea and lakes, where they are specifically designated as swimming areas. Swimming pools and basins pose similar risks to bathrooms, in that people are generally unclothed and body contact resistance is low. One major difference to keep in mind, however, is that generally there are several people in the pool area and usually only one person in the bathroom. Some fountain basins are likely or even expected, to be occupied, and as such they should be treated as swimming pools as far as BS 7671 is concerned. Often a risk assessment will need to be carried out to assess whether fountains need to be treated as fountains or as swimming pools.
G 3.2
Zone concept Again, the swimming pool or fountain basin is first divided into zones in order that regulatory requirements can be prescribed for each zone. The zones for swimming pools are shown in Figures G 3.1 and G 3.2 (pools above and below ground).
Key Zone 0 Zone 0 Zone 1 Zone 1 due to diver 1.5 m
Zone 2
1.5 m
2.5 m
Zone 1
2.5 m
1.5 m
2.0 m
2.5 m
Zone 0
2.0 m
1.5 m
Zone 0
Figure G 3.1â&#x20AC;&#x201A; Swimming pool zones.
229
G
Guide to the Wiring Regulations
Key Zone 0 Zone 0 Zone 1 Zone 1 due to diver Zone 2
2.5 m h
2.5 m h
1.5 m
2.0 m
2.0 m
1.5 m
NOTE: The dimensions are measured taking account of walls and fixed partitions
Figure G 3.2â&#x20AC;&#x201A; Swimming pool zones â&#x20AC;&#x201C; raised pool.
Also, for fixed partitions the zone plan in Figure G 3.3 will be useful. For fountains, there is no Zone 2 as it is unlikely that persons will be unclothed in public fountains. The zones for fountains are given in Figure G 3.4.
G
230
Special Locations
r3
r1
1.5
Zone 2
2.0
Zone 1
Dimensions in metres r1= 2 r2= r1-(s1+s2) r3= 3.5 r4= r3-(s1+s2) r5= r3 -(s3+s4)
r2 r4
s1
Zone 0
r4
r1
r1 s3
r3
r2 s4
s2 r5
Figure G 3.3 Swimming pool zones – from various fixed partitions.
Key 1.5 m
Zone 0
2.0 m 1.5 m
Zone 1 Zone 0 Air spray below waterjets and waterfalls to be considered as zone 0
2.0 m
2.0 m 2.5 m 2.5 m
2.5 m 2.5 m
2.0 m
Basin 2.5 m
Pool Figure G 3.4 Fountain zones.
231
G
Guide to the Wiring Regulations
G 3.3
Requirements and guidance The requirements additional to the general rules are summarized in Tables G 3.1 and G 3.2.
Table G 3.1 Swimming pool and fountain electric shock requirements. Swimming pool or fountain
Requirement
Regulation
Both
All extraneous-conductive-parts in Zones 0, 1 and 2 (except for fountains) to be supplementary bonded
702.411.3.3
Both
For SELV and PELV basic protection must be used
702.414.4.5
Only SELV up to 12 V a.c. or 30 V d.c. can be used as a protective measure in Zone 0 in swimming pools
702.410.3.4.1
Swimming pools Swimming pools
Only SELV up to 25 V a.c. or 60 V d.c. can be used as a protective measure in Zone 1 in swimming pools
702.410.3.4.1
Swimming pools
Protective measure in Zone 2 in swimming pool can be SELV, RCD automatic disconnection or ‘single item electrical separation’
702.410.3.4.3
Fountains
Protective measure in Zones 0 and 1 in fountains can be SELV, RCD automatic disconnection or ‘single item’ electrical separation
702.410.3.4.2
Table G 3.2 Swimming pool and fountain equipment selection and erection requirements.
G
Swimming pool or fountain
Requirement
Regulation
Both
Equipment in Zone 0 shall be IP X8
702.512.2
Both
Equipment in Zone 1 shall be IP X4
702.512.2
Both
Equipment exposed to cleaning jets to be at least IP X5
702.512.2
Both
Surface metallic wiring sheaths or conduits, or those less than 50 mm deep shall be connected to the local supplementary bonding
702.522.21
Both
In Zones 0 and 1, no switchgear is permitted
702.53
Both
In Zones 0 and 1, no socket outlet is permitted
702.53
Swimming pool
In Zones 0 and 1, only equipment designed for a swimming pool can be used
702.55.1
Swimming pool
In Zones 0 and 1, floor heating unit is allowed if it is SELV, RCD protected and covered with earthed metal grid
702.55.1
Both
Luminaires shall comply with BS EN 60598–2-18
702.55.2 702.55.3
232
Notes
Particular requirements exist for IP and water jets, see D 16.2
Special Locations
Table G 3.2 (Continued.) Swimming pool or fountain
Requirement
Regulation
Swimming pools
Zone 1 pool equipment (pumps etc.) shall be in a Class II enclosure, only accessible with a tool and have 25 V a.c SELV (60 V d.c.) or electrical separation
702.55.4
Swimming pools
For swimming pools without a Zone 2, luminaires can be installed in Zone 1 and do not need to be 12 V SELV, but must be RCD protected and at least 2 m above floor
702.55.4
Notes
To further assist with the tables, the following notes have also been included for extra clarification and guidance. Apart from underfloor heating there is no specific requirement for a metallic grid in the floor (this was deleted by amendment of the 16th Edition). Connections to the protective conductors of exposed-conductive-parts may be made locally to the equipment or at a local distribution board or control panel, depending on the installation design. Extraneous-conductive-parts are conductive parts not forming part of the electrical installation and liable to introduce an electric potential, including the electric potential of a local earth. For Section 702 this means a potential from outside Zones 0, 1 and 2 into these Zones. Such parts may include the following:
•• •• •
metallic pipelines for fresh water, waste water, gas, heating, climate and other; metallic parts of building construction; metallic parts of the basin construction; reinforcement of non-insulating floors; reinforcement of concrete basins.
Floors made of individual concrete tiles whose reinforcement is fully encapsulated within the tile and not accessible without damaging the tile, need not be included in supplementary equipotential bonding. Concrete tiles without metallic reinforcement, tile coverings as well as topsoil (e.g. lawn) need not be included in supplementary equipotential bonding. The following conductive parts are not regarded as extraneous-conductive-parts provided that they cannot introduce a potential to Zones 0, 1 and 2; they need not be included in supplementary equipotential bonding:
233
G
Guide to the Wiring Regulations
•• •• •• •• •
basin ladders; basin barriers; diving structures, ladders; handrails and handholds on the rim of the basin; grid covers including the mounting frames of overflow pipes; window frames; door frames; starting blocks; other similar items.
For fountain basins, cables run to supply lighting equipment in Zone 0 are to be run outside the basin as much as possible, and take the shortest practicable route in Zone 0 to the equipment. Cables must be suitable for total continuous immersion and type H07RN8-F is recommended. If it is possible for people to get into the basin, cables should not be installed. Socket outlets are not permitted in Zones 0 or 1 of a swimming pool area, and are normally only permissible in Zone 2 if they are supplied either by SELV, the source being installed outside the zones, or by the application of electrical separation; again the transformer being outside the zones, or protected by a 30 mA RCD. Pool cleaning equipment at mains voltage or special equipment should only be brought into the pool area when it is empty of swimmers, and supplied from sockets outside the zones.
G 4
Adrian Peacock/Getty Images/Digital Vision
Agricultural and horticultural premises (705)
G
234
Special Locations
G 4.1
Introduction, purpose and principles BS 7671: 2008 includes this Section 7 for fixed electrical installations inside and outside agricultural and horticultural buildings, including locations where animals are kept. It does not apply to residences or other locations such as shops, workshops or storage areas in agricultural premises. These locations are characterized by arduous conditions, and people usually working in a wet or damp environment, both indoors and outdoors. An increased risk of damage to the electrical installation and an increased risk of personal danger can come from a number of factors, including:
•• •• •
the use, possibly widespread, of chemical cleaners and fertilizers; behaviour and nature of animals (stock and vermin); agricultural machinery; frequent wet and damp conditions; lower body resistance of livestock.
It should be noted that danger, including the risk from electric shock, particularly applies to livestock. In places where livestock is kept, there is a greater risk of electric shock to them due to their lower body resistance and more intimate contact with the general mass of earth. It can often be seen in milking parlours that cows will not pass from one place to another where they sense a small potential difference between their front and rear legs.
G 4.2
Requirements and guidance The requirements of the section are summarized in Table G 4.1. As well as Table G 4.1 the following notes and guidance are provided. As applies generally to special location areas, protection by the use of obstacles, placing out of reach, non-conducting locations or earth-free equipotential bonding is not allowed in agriculture/horticulture due to the extra risks involved in such wet and exposed locations, as operators are usually non-technical staff (ordinary persons). Wiring systems and electrical equipment and accessories must be suitable for the location and environment of their use. Arduous conditions including animal housing, cleaning chemicals, wash down with hoses, vermin, physical impact damage
235
G
Guide to the Wiring Regulations
Table G 4.1 Agricultural and horticultural installation requirements. Requirement
Regulation
Final socket-outlet circuits with socket outlets up to 32 A require a 30 mA RCD
705.411.1
Final socket-outlet circuits with socket outlets above 32 A require a 100 mA RCD
705.411.1
All other circuits require an RCD not exceeding 300 mA
705.411.1
For SELV and PELV basic protection must be used
705.414.4
Where livestock is kept, supplementary bonding shall connect exposed and extraneous-conductive-parts; this includes floor reinforcing Copper conductors to be 4 mm2 minimum, steel bonding to be galvanized and minimum of 8 mm diameter or 30 x 3 mm section
705.415.2.1 705.544.2
Where welfare of animals is affected by loss of supply (e.g. food, water, ventilation or lighting systems) a standby supply shall be installed and separate final circuits shall be used. Alternatively for ventilation systems, monitoring and alarms can be used
705.560.6
Ventilation supply circuits shall be designed to achieve discrimination
705.560.6
Electrical heaters for livestock shall be to BS EN 60335–2-71
705.422.6
All equipment to have IP minimum of IP44
705.512.2
Obstacles and Out Of Reach are not permitted
705.410.3.5
Non-conducting location and earth-free local equipotential bonding are not permitted
705.410.3.6
etc. are all possible, and the selection and erection of systems and equipment must provide proper protection and safety. All electrical equipment should have physical protection to withstand wash down and the use of chemical cleaning agents, and will require special considerations against corrosion. High impact plastic materials may be better than metals, but these cannot be considered to be a Class II installation. Generally, the best physical protection will be provided by careful placement of outlets and controls in areas where they are not likely to be subject to damage or impact. Electrical equipment must be protected against the ingress of both solid particles and water, depending upon its location, and BS 7671 recommends a minimum rating of IP44 under normal conditions; equipment not so rated should be enclosed
G
236
Special Locations
within an enclosure rated to at least IP44. This may, however, not be practical for all items, such as sensors or controls, and other alternatives, such as locating these in safer areas (if possible) may be necessary. IP44 is really a general minimum, and an environmental assessment must be made at the design stage and equipment selected accordingly. It must be noted that IP ratings are not ‘all inclusive’ and their application to various environments must be considered. For example, IPX8 may be suitable for total immersion, but it may not be suitable for water jets and areas being hosed down (see D 16.2). In areas with no specific risk, e.g. residential areas, offices, shops and similar locations belonging to agricultural and horticultural locations, a normal residential level of protection should be adequate, but if there is any extra risk, e.g. the practice of using extension leads into other areas (which should be avoided), further provisions may be necessary. Special consideration must be given to earthing and bonding to ensure its integrity, and stranded conductors are recommended, especially in areas where vibration is likely to be experienced. Earthing and protective bonding conductors must also be protected against damage and corrosion, and BS 7671 suggests minimum cross-sectional areas of conductors of various materials (see Chapter E). The reduced disconnection time of 0.2 s of the 16th Edition has been deleted for the 17th Edition, and there is now no difference between the special locations disconnection time requirements and those specified in Chapter 41. Again, the use of RCDs is seen as a positive safety benefit, but the designer must consider the possible consequences of loss of electrical supply to farm buildings or systems that may provide life support for animals or other safety services. Indeed, the requirements for agricultural and horticultural installations in the 17th Edition call for the consideration of supply security and possible standby supplies for animal life-support or comfort systems. The general requirements of Part 4 of BS 7671 apply, and in all circuits, whatever the type of earthing system, 30 mA RCDs (to the requirements of Regulation 415.1.1) are to be provided for all socket-outlet circuits up to and including 32 A socket outlets, and a 100 mA RCD (again, to the performance requirements of Regulation 415.1.1) must be provided for circuits with socket outlets over 32 A.
237
G
Guide to the Wiring Regulations
Key 1. Silo 2. Gate or door or metal partition 3. Metal associated with milking 4. Feeding trough 5. Floor mesh 6. Steel construction elements 7. Earth bar
1
3
7
2
5 4 6
6
Figure G 4.1â&#x20AC;&#x201A; Required earth bonding in milking parlour and similar.
In livestock locations all exposed-conductive-parts and extraneous-conductive-parts that are accessible to livestock must be connected together with supplementary equipotential bonding. Figure G 4.1 gives an illustration of the requirement. Where a metal grid is installed in the floor, or there are extraneous-conductive-parts in or on the floor, e.g. structural steel components, or cattle pens with â&#x20AC;&#x2DC;cast inâ&#x20AC;&#x2122; items embedded in the concrete, or concrete reinforcing, they must be connected to the supplementary equipotential bonding. The illustrations in Figure G 4.1 are only for general guidance and other suitable bonding arrangements are quite acceptable. If a bonded metal grid cannot be laid in the floor of animal houses during construction or refurbishment, it is recommended that a TN-C-S (PME) electricity supply is not used. A TN-S supply is preferred. If a TN-C-S supply is offered or is the only type available, it is recommended that a separate local earth electrode be installed.
G
238
Electrical Earth
Special Locations
Fire has always been a significant risk in agricultural and horticultural buildings, with the amount of flammable materials used and stored in them. A lot of fires are put down to ‘electrical faults’ and, although the use of RCDs cannot be guaranteed to prevent the risk of electrically ignited fires, correctly selected RCD protection can reduce electrical fires caused by earth leakage current ignition. For fire protection purposes, an RCD with a rated residual operating current not exceeding 300 mA is advised, and a lower operating current may be appropriate depending on the installation and loads supplied. Lastly, if electric fences are installed, details of operation and maintenance should be provided to the user of the installation.
G 5
Caravan parks and camping parks (708)
G 5.1
Introduction, purpose and principles The 17th Edition has two separate sections concerning caravans, Section 708 covering caravan parks (and including camping parks) and a new Section 721 covering caravans and motor caravans. The latter, Section 721, is not included within this book as it is concerned with the internal wiring within caravans. Section 708 does not apply to installations for mobile homes and similar and its scope is for ‘caravan parks/camping parks’ as defined in the Standard, as follows: Caravan park/camping park: Area of land that contains two or more caravan pitches and/or tents. Whereas a caravan is defined as: Caravan: A trailer leisure accommodation vehicle, used for touring, designed to meet the requirements for the construction and use of road vehicles. Caravan parks are laid out with ‘caravan pitches’ in the form of spaces to accommodate the caravans, and the layout will depend on the shape, topography and nature of the site. Most sites are laid out with the caravans in a regular arrangement to maximize the space, as parks are commercial enterprises. Others have trees, etc. and other features that make the park attractive and these need to be accommodated.
239
G
Guide to the Wiring Regulations
Caravans are for touring, and can travel throughout Europe, and farther, so their electrical installation may have to accommodate the different electrical practices of various countries, thus Section 721 requires the provision of a 30 mA RCD to the requirements of Regulation 415.1.1 to be provided within UK caravans.
G 5.2
Requirements and guidance The requirements of BS 7671 are summarized in Table G 5.1. The park provides an electricity supply at each pitch, and generally these supplies are provided by the use of a 16 A SP&N ‘industrial’ socket outlet to BS EN 60309–2. Some larger supplies may exist for very large caravans, but generally these would not be touring types. As usual with special locations the protective measures of obstacles, placing out of reach, non-conducting location and earth-free equipotential bonding are not allowed as the parks and caravans are used by ordinary persons, and the installations cannot be under effective supervision at all times. The electricity supply to a caravan park must be a TN-S supply to the caravan pitches. A TN-C-S supply is not acceptable as the common problems with a broken or lost neutral could make the metal frame and skin of a caravan live with respect to the general mass of earth, and this would be potentially dangerous for anyone Table G 5.1 Caravan and camping park requirements.
G
Requirement
Regulation
TN-C-S arrangements are not permitted
708.411.4
Equipment to be minimum of IP 44
708.512.2
Overhead cables to be minimum of 6 m where vehicles are used and 3.5 m elsewhere
708.521.1.2
Supply point at pitch is to be a maximum of 20 m from caravan inlet
708.530.3
Pitch socket outlets to be provided with at least one outlet, minimum 16 A, IP44, BS EN 60529 type and located between 0.5 and 1.5 m high
708.553.1.8 708.553.1.9 708.553.1.10 708.553.1.11
Each pitch socket outlet to be provided with overcurrent protection and 30 mA RCD
708.553.1.12 708.553.1.13
Obstacles and Out Of Reach are not permitted
708.410.3.5
Non-conducting location and earth-free local equipotential bonding are not permitted
708.410.3.6
240
Special Locations
touching earth and the caravan at the same time. A TN-C-S system is allowable, however, in fixed buildings on the park, offices, shops, clubhouse, stores etc. and these can be treated as any other building. Two common methods are used for installations with supplies with a TN-C-S PME incomer. The first is to break the PME at the distribution board that supplies the caravan pitches. The second, more popular, method is to break the PME supply at the pitch outlets. In both cases ‘breaking’ is normally carried out by terminating the earth cable sheath or similar on an insulated enclosure. As parks are usually in exposed locations, particular care must be taken in selecting wiring systems and equipment, and further mechanical protection may be required for some applications. Generally pitch socket outlets should be IP44 if they are enclosed or protected from the elements, and higher IP ratings will be necessary if they are exposed. Impact protection must be considered, and it may be necessary to protect exposed cables with conduit or steel channel. The 17th Edition advises mechanical stress protection to AG3 (high severity) of Appendix 5 of BS 7671 but this does not give any practical advice as to what would be required. Cables should be run round the site underground, but this may not be possible in all locations due to soil depth. The recommended minimum depth of cable burial is 600 mm, but where this cannot be achieved, mechanical protection must be provided if there is any likelihood of cable damage. Cables should be run round the edge of pitch locations or along road verges to reduce the possibility of damage caused by digging in pitch areas, or pegs or spikes used for awnings or tents. Overhead conductors should only be considered where buried cables are not practical, and they should be high enough over roadways, or kept away from traffic routes to prevent damage from tall vehicles or caravans, as well as aerials, chimneys and other projections that may be on caravans. Overhead conductor supporting poles should also be located away from vehicle routes to avoid possible impact and damage. Each caravan or tent pitch should be supplied with a conveniently located socket outlet to allow the caravan to connect easily and safely with its standard flexible connector. In regularly laid-out parks, each group of perhaps four pitches would have a power supply location centrally located, but with irregularly laid-out parks this will not be so. Each socket outlet shall have individual overcurrent protection and a 30 mA RCD.
241
G
Guide to the Wiring Regulations
Site supply
Plug
Socket-outlet
View of pins
View of socket tubes Line conductor (e.g.L1)
Neutral conductor (N)
Neutral conductor (N)
Protective conductor (PE)
View of terminals
View of contact tubes
Light Blue Line Neutral conductor conductor (N) (e.g.L1)
Line Neutral conductor conductor (e.g.L1) (N)
Green-yellow Protective conductor (PE)
Line conductor (e.g.L1)
Line conductor (e.g.L1)
Green - yellow Protective conductor (PE)
View of pins
View of terminals
Protective conductor (PE)
Neutral Line conductor conductor (N) (e.g.L1)
Green-yellow Protective conductor (PE)
Connection device
Connector
Figure G 5.1â&#x20AC;&#x201A; Caravan pitch outlet, extension lead and inlet.
G
242
Light Blue Neutral conductor (N)
Protective conductor (PE)
Line Light Blue conductor Neutral conductor (N) (e.g.L1)
Protective conductor (PE)
View of terminals
Caravan inlet
Special Locations
The 16th Edition of BS 7671 allowed up to three socket outlets to be supplied from one circuit and RCD, but the 17th Edition now requires each outlet to have its own RCD, to prevent interruption to other supplies by a faulty caravan. RCDs are to comply with the requirements of Regulation 415.1.1 and must be multi-pole. Socket outlets should be fixed between 500 mm and 1500 mm from the ground to allow easy access and prevent damage from equipment or the elements. In cases where flooding may be expected, this height should be increased. The 16th Edition allowed socket outlets to be between 800 mm and 1500 mm from the ground, but this change in minimum dimension does not make installations carried out to the 16th Edition in any way unsafe, and the Regulations are not retrospective. This must be remembered during safety inspections. The further provision of RCDs in the 17th Edition has the same effect and does not affect safety. Figure G 5.1 is adapted from a diagram in BS 7671: 2008 and shows a pitch outlet, extension lead and caravan inlet.
G 6
© Masterfile (Royalty-Free Division)
Exhibitions, shows and stands (711)
243
G
Guide to the Wiring Regulations
G 6.1
Introduction and risks Section 711 of the special locations requirements applies to temporary exhibitions and shows, and the stands and exhibition equipment used in them. The section should not be applied to permanent exhibitions and shows, or to the permanent fixed installations of exhibition halls or show grounds that accommodate the exhibition. Vehicles or caravans that are used as prefabricated exhibition stands are included in this section. The major risks are unsafe electrical work carried out by people who are not competent, giving rise to danger of fire and electric shock, and most exhibition and show organizers will require an electrical installation certificate for each standâ&#x20AC;&#x2122;s electrical installation before they will allow its connection to the local supply. Organizers also usually require the inspection and testing and certification of all electrical equipment (e.g. lighting, sound systems etc.) that is to be used. Major events are set up by professional engineering staff, and the use of pre-engineered stage components and systems is well established. Many smaller shows, however, may be provided for by local electrical contractors, and in very small shows the DIYer may be tempted to do his own work, with all the problems that may provide! The environmental conditions must be properly assessed, and can range from agriculture shows in open fields, with attendant livestock, to exhibitions in regularly used purpose-built halls. The protective measures of obstacles or placing out of reach are not permitted, as they cannot be successfully managed, and nonconductive locations or earth-free local equipotential bonding are not permitted, as they are not under the continuous control of a competent person. Generally, electrical systems should be as simple and robust as possible, and modular installation systems with plug and socket outlet connections have been developed to go with prefabricated modular stand constructions.
G 6.2
Requirements and guidance The requirements of 711 are summarized in Table G 6.1. Regulation 711.521 requires the selection of cables assuming the installation contains no fire alarm system in the building accommodating the exhibition or show. This requirement is not really practical as (apart from small private buildings such as school halls) all buildings open to the public in the UK will be subject to prior inspection by the local authority for licensing, and adequate fire alarm and emergency escape provisions are required for licensing. Even if this is not the case
G
244
Special Locations
Table G 6.1 Requirements for exhibitions, shows and stands. Requirement
Regulation
A cable supplying a temporary exhibition, show or stand shall be additionally 711.410.3.4 protected with a 300 mA RCD and shall discriminate with final circuits Obstacles and Out Of Reach not permitted Non-conducting location and earth-free local equipotential bonding not permitted
711.410.3.5 and 711.410.3.6
Structural metal of stand, caravan, wagon or container to be main bonded
711.411.3.1.2
Socket-outlet circuits up to 32 A and lighting circuits to have 30 mA RCD (excludes emergency lighting)
711.411.3.3
Where SELV and PELV are used, basic protection shall be provided
711.414.4.5
Cables shall be at least 1.5 mm
711.52
2
Notes For RCD discrimination see Section D 7.3
Butyl flex not to be used where no fire alarm is present
711.52
See text following table
Joints in cables shall only be made for connection into circuits
711.526.1
In-line joints should not be used
Joint system to be at least IPX4
711.526.1
Separate units require isolators
711.537.2.3
All motors shall have isolators located adjacent to them
711.55.4.1
Adequate quantity of socket outlets shall be provided
711.55.7
A visible switch shall be provided for signs, lamps or exhibit circuits
711.559.4.7
Installation shall be inspected and tested after each assembly
711.6
(as explained in the selection of cables section under Section D 5.4.1), the only BS EN cables that do not comply with BS EN 60332–1–2 are butyl flexes. All supply cables are required to be protected against damage by an RCD with a rated residual operating current that does not exceed 300 mA, and all final circuits on the stand are to be protected by 30 mA RCD. This includes socket outlets rated up to and including 32 A. BS 7671, however, excludes emergency lighting circuits, but generally emergency lighting will be provided elsewhere in a building or show as part of the overall emergency escape policy and will not be a part of the stand (unless it is a very large stand with internal rooms or partitions), and emergency lighting will usually be of the self-contained type, so this exclusion is not relevant. Installation methods must take into account the access of members of the public in relatively large numbers, and the fact that these persons generally will be more interested in the exhibition or show than anything else, and so cables must be run in safe locations away from damage, trip hazards and wear from users (e.g. foot
245
G
Guide to the Wiring Regulations
or vehicle traffic), and armoured cables or other protection should be used where there is expected to be any risk of damage. It is desirable that switchgear and control gear is not accessible to the general public and should be enclosed in lockable cabinets or similar. Most exhibition halls and shows have specific licensing and inspection requirements or rules for exhibitors, e.g. the Amusement Devices Inspection Procedures Scheme (ADIPS). This was introduced by the industry with HSE support, and provides for third party safety inspections for entertainment and amusement devices and rides. Current approval documentation from such an inspection may need to be shown to the organizers, along with electrical installation and electrical equipment inspection and testing certification.
G 7
Solar photovoltaic (PV) power supply systems (712)
G 7.1
Introduction, principles and terminology BS 7671 includes Section 712, which, to give it its full title, is ‘Solar Photovoltaic (PV) Power Supply Systems’. The purpose for inclusion of this new section in BS 7671 is only concerned with safety. In this section of the book, terms used to describe the subject are PV cells (individual cells), PV strings (a circuit arrangement of PV cells), PV arrays (a general term for a collection of cells, possibly comprising a number of PV strings) and PV system (the cells or arrays, their control and connection); the terms are generally expanded upon and illustrated in this section. A PV system is a collection of interconnected PV cells that turn sunlight directly into electrical energy, and consequently needs to be installed outside (usually at roof level); so any external electrical work has to be suitable for the environment and correctly IP rated. PV arrays and equipment must conform with the relevant equipment Standards, i.e. BS EN 61215. PV arrays are just one of several sources of sustainable energy (e.g. wind turbines), and all have similar connection requirements to run in parallel with the Regional Electricity Companies’ mains supply. The Department of Trade and Industry (DTI) has published a guidance document on the installation and connection of such sources (Photovoltaics in Buildings, 2nd Edition printed 2006 {URN 06/1972}), and this provides detailed information on installation requirements.
G
246
Adobe Stock Photos
Special Locations
247
G
Guide to the Wiring Regulations
PV arrays produce electricity at a voltage dependent upon the physical characteristics of the array and its construction, and the series and parallel interconnection of PV cells within an array. These are all set during the manufacturing process and the electrical contractor only has to install the system to the manufacturer’s details. As the PV array is a source of energy, it is effectively live at all times and cannot be isolated (like a battery). The array output voltage is dependent on the array construction and the load current, and needs to be provided by the manufacturer’s designer. When on load, like any source, the terminal voltage can fall to zero at high load, but will recover when the load is removed. Figure G 7.1 shows the no-load current-voltage characteristic of a typical PV cell, and Figure G 7.2 shows a typical loaded power–voltage characteristic. Typical No-Load Characteristic 2,500 2,000
Current (mA)
1,500 1,000 500 0
0
0.1
0.2
0.3
0.4
0.5
0.6
0.5
0.6
d.c. cell voltage (V) Figure G 7.1 Typical PV cell no-load current-voltage characteristic.
Typical Loaded Characteristic 2,500 2,000
Power (mW)
1,500 1,000 500 0
0
0.1
0.2
0.3
0.4
d.c. cell voltage (V) Figure G 7.2 Typical PV cell on-load power–voltage characteristic.
G
248
Special Locations
Table G 7.1 PV system requirements. Requirement
1
G 7.2
Regulation
PV a.c. supply to be connected to supply side of protective device
712.411.3.2.1.1
RCD required and shall be type B to IEC 60775
712.411.3.2.1.2
1
Class II is preferred on d.c. side of cell
712.412
Overload protection may be omitted from the PV array string if the cable currentcarrying capacity is rated to at least 1.25 of the short circuit current. Short circuit current protection must be provided at connection to the mains
712.433.1 712.434.1
Isolation for maintenance on d.c. and a.c. sides to be provided
712.537.2.1.1
All junction boxes to carry label warning about energization after loss of mains
712.537.2.2.5.1
Protective bonding conductors to be run in close contact with d.c. and a.c. PV system cables
712.54.
RCD not required where the PV construction is not able to feed the d.c. fault.
Requirements The requirements of BS 7671 are summarized in Table G 7.1.
G 7.3
Notes and guidance It is required to provide an isolator in a suitable location on the d.c. output from the array, and it must be noted that the cables from the array to this isolator will always be live, and must be of a suitable construction to withstand thermal and mechanical damage. The general method of installation is outlined in Figure G 7.3, but PV arrays are at present specially manufactured items, usually supplied as a complete system with the converter and specialist installation in a ‘package’. There are mandatory requirements concerning parallel connection of ‘generators’ before installations can be interconnected with the supply network. Section 551 of BS 7671 has general regulations on these connections (see 551 and Section D 9 of this book). The permission of the local distribution network operator (DNO, formerly known as REC) must be obtained, and this is a relatively simple, formal process for small domestic systems up to 5 kW, but the process becomes considerably more complex for larger commercial projects.
249
G
Guide to the Wiring Regulations
Meter 9 9999 9
PV Overcurrent Device
RCD
AC isolator
PV System Control
Convertor
DC Isolator
PV Array Figure G 7.3â&#x20AC;&#x201A; Typical PV system, showing array and control and isolation.
G
250
Special Locations
To aid designers and installers the DNOs have issued Engineering Recommendations to assist in designing and specifying systems correctly for their approval. Recommendation G83/1 is for PV systems up to 5â&#x20AC;&#x2030;kW, and G59/1 covers PV and other systems above 5â&#x20AC;&#x2030;kW. These documents can be purchased from the Energy Networks Association. Protection by the use of Class II (double insulated) or equivalent insulation is advised for the d.c. system from the array, but it is permitted to earth the d.c. side at one point if there is at least separation with the use of basic insulation between the d.c. and a.c. sides. All equipment used on the d.c. side must be suitable for d.c. voltages and currents, equipment approved to normal a.c. standards will not be suitable (especially switchgear), and the designer should clarify standards and performance requirements with equipment manufacturers. PV arrays must be installed by competent persons to an approved design, and planning and building regulations approvals may be required. As they are fixed to the outside of a building they will be subject to all environmental conditions including storms and high winds, so the construction and weather sealing must be sound. The installation must also be accessible for any repair or maintenance, although with no moving parts this should be minimal. The arrays are to be installed to allow adequate ventilation to prevent any heat build-up, especially to electrical equipment and components. Depending on the design of the arrays, overcurrent protection may not be necessary on the d.c. side cables as there is a limit to the current output of the array. ISC STC is the short circuit current of a PV module or array under standard test conditions, and VOC STC is the open circuit voltage under standard test conditions of an unloaded PV module or array on the d.c. side of the system. If the continuous current-carrying capacity of any d.c. cable at any point is at least 1.25 ISC STC with any de-rating factors taken into account, overcurrent protection is not required. Short circuit protection, however, must be provided at the connection to the a.c. mains for the a.c. side supply cable, in accordance with the normal requirements of Part 4 of BS 7671, to prevent damage from an a.c. side fault (see Figure G 7.3).
251
G
Guide to the Wiring Regulations
PV String: PV Cells in series to generate required output voltage String Cables
String Cables
Main DC Cable Figure G 7.4â&#x20AC;&#x201A; PV string arrangement.
Cables shall be of a type selected to be suitable for their environment and conditions of use, and suitable for the expected equipment temperatures (DTI guidance suggests 80°C rated cables should be considered). Cables must also be installed to minimize the possible risks of damage and faults, and further protection or armoured cabling may be necessary. Plug and socket connectors, specific to PV systems, are commonly fitted to module cables by the manufacturer. Such connectors provide a secure, durable and effective electrical contact. They also simplify and increase the safety of installation works. They are recommended in particular for any installation being performed by a non-PV specialist, for example, a PV array being installed by a roofer.
G
252
Special Locations
G 8
Mobile or transportable units (717)
G 8.1
Scope and application New for the 17th Edition, this is perhaps the most unusual section of the special locations, as it covers a wide range of units from specialist broadcast vehicles to simple skid-mounted units. Generally all such units are prefabricated to specific user specifications and technical standards, and the general electrical consulting engineer or electrical contractor will have little to do with their construction. You may now ask why this section has been included within the book. Although the design of the units is carried out by manufacturers, questions concerning connection to the units, or their inspection, are ones that are frequently put to electrical contractors. The scope of the section states that the ‘units’ are intended to mean either a mobile vehicle unit or a transportable unit; for example, a container. It cites examples as: technical and facilities vehicles for the entertainment industry, medical services, advertising, fire fighting, workshops/offices and transportable catering units. It then lists exclusions such as generating sets, marinas and pleasure craft, mobile machinery to BS EN 60204–1 (Safety of Machinery). Thus the whole application of Section 717 is confused, as it could be applied to a collection of temporary site buildings, or Portakabins® used as wards for the local NHS hospital. Whilst some of the measures in this section would be suitable, such constructions would not normally be expected to be ‘special locations’ and the normal installation requirements of Parts 1 to 5 of BS 7671 would be adequate. This book, therefore, limits itself to specialist mobile units; even this is not easy to define but would include, for example, outside broadcast mobile vehicles. To throw some advice at those of you who are a little lost, perhaps a solution would be to consider the requirements given in Section G 8.2; there is not a vast quantity and they are not particularly difficult to apply. One option open therefore would be, if in doubt, to apply the requirements anyway.
253
G
Guide to the Wiring Regulations
Table G 8.1 Mobile or transportable units system requirements Requirement
Regulation
Automatic disconnection shall be by an RCD
717.411.1
Socket outlets to be 30 mA protected (unless they are SELV, PELV or by electrical separation)
717.415
Accessible metal parts like the chassis shall be main bonded, using finely stranded conductors
717.411.3.1.2
TN-C-S (PME) shall not be used
717.411.4
Unit supply cables to be flexible to BS 7919 or equivalent, minimum 2.5 mm and shall enter the unit via an insulating sleeve or enclosure
717.52.1
Unit supply connectors to be BS EN 60309–2, insulated to IP44
717.55.1
Electrical equipment not to be run in gas storage area except gas-supply control
717.528.3.5
Unit to have an electrical rating plate, indicating earthing arrangement, voltage, phases and maximum power
717.514
Obstacles and Out Of Reach are not permitted
717.417
Non-conducting location or earth free local equipotential bonding are not permitted
717.418
Alternatively, an IT supply can be used, with insulation monitoring, and RCD to disconnect if the isolating transformer fails
717.411.6.2
2
G 8.2
Requirements The requirements of Section 717 are summarized in Table G 8.1; some of these requirements are items that should or can only be undertaken at the manufacturing stage.
G 8.3
Notes and guidance Generally for such units a TN-C-S supply system is not allowable, due to the possible dangers associated with a broken or disconnected neutral making the earth a part of the circuit, and the need to properly control and maintain such a supply system; not easily practical in most ‘temporary’ locations. The integrity of earthing and bonding connections is obviously of considerable concern in such mobile units, where vibration can be a considerable problem, and the Regulations require that all accessible metalwork parts of the unit are to be connected through a finely stranded protective bonding conductor to the main earthing terminal of the unit. A note to Regulation 717.411.3.1.2 suggests that cable types H05V-K and H07V-K to BS 6004 are appropriate stranded cable types. Generally, however, as discussed previously, such mobile or transportable units are designed by specialists for special applications and any earthing and
G
254
Special Locations
bonding connections should be carried out by the contractor to the instructions of the equipment designer. Generally, the protective measure of automatic disconnection of the supply is achieved by the use of an RCD. Some specialist units such as broadcast vehicles do not use RCDs on their earthing system, as the sudden interruption of supply could not be tolerated. These installations are always under the control of competent persons during operation, and the earth current is closely monitored. Small units may be operated more practically as an IT system (isolated from earth). The ‘first fault’ will not cause operation of any protective device, but the unit should be constructed and operated to minimize the likelihood of any such fault. BS 7671 however, allows IT systems to be provided only by either the use of an insulation monitoring device or by the use of simple electrical separation. Simple separation must itself provide for the use of an insulation monitoring device providing automatic disconnection at first fault, or the use of a 30 mA RCD complying with Regulation 415.1.1 of BS 7671 (30 mA). As with all special locations there is increased risk of danger if the installation is not properly designed, constructed and commissioned, and then properly operated and maintained by competent persons. As such units will usually be used outside, and be subject to continual movement and handling, the electrical equipment must be suitably rated, environmentally protected, of good quality and be to relevant British or equivalent Standards. Cables for internal wiring of units may be PVC insulated single-core to BS 6004 installed in conduit; but if there is any possibility of vibration, all-insulated conductors, or even flexible stranded conductors, should be used. Cables for connecting the unit to the supply must be of flexible type, and suitable for their environment and method of use. Such cables should be protected if there is any likelihood of damage (e.g. foot or vehicle traffic) and protected from any abrasion. BS 7671 recommends that flexible H05RN-F or H07RN-F cable of a minimum 2.5 mm2 cross-sectional area be used, but this may need to be increased for reasons of voltage drop. Plugs and socket outlets are to be industrial type to BS EN 60309–2, insulated construction only, and be suitably IP rated to a minimum of IP44 outside. The plug-top shall be on the unit.
255
G
Guide to the Wiring Regulations
Finally, Section 717 includes two drawings of internal wiring arrangements for mobile units; these diagrams are most confusing and do not greatly extend the reader’s knowledge.
G 9
Floor and ceiling heating systems (753)
G 9.1
Introduction Section 753 ‘Floor and Ceiling Heating Systems’ is new to BS 7671: 2008. Readers may wonder whether this is Section 753 or 53rd in the series of Part 7s. The answer is that within IEC, there are many Part 7s either drafted or planned. Electric floor and ceiling heating systems are mainly used in domestic and similar installations and are usually buried in the building fabric. The main risks of such systems are overheating and physical damage after installation, as the systems are not visible but buried at a shallow depth.
G 9.2
Requirements Again the requirements have been summarized in a Table, G 9.1.
Table G 9.1 Floor and ceiling heating requirements.
G
Requirement
Regulation
Automatic disconnection shall be by a 30 mA RCD
753.411.3.2
Heating units (cables, tape or panels) that are not manufactured with a conductive covering or mesh shall be protected with a metal mesh or grid with spacing of not more than 30 mm
753.411.3.2
A maximum temperature of 80°C operating temperature shall be achieved by design, installation or by sensing. Floor areas shall have a lower temperature for skin comfort (say 35°C)
753.424.1.1 753.423
Heating cables shall be to BS 6351 and flexible sheet panels to BS EN 60335–2-96
753.511
Heating units (cables, type of panels) for floor installation shall be to IPX7
753.512.2.5
Information shall be given to the user of the installation (see Section G 9.3)
753.514
256
Special Locations
G 9.3
Notes and guidance Systems are to be protected by a 30 mA RCD. If heaters do not have an integral conductive covering or sheath (an exposed-conductive-part), a conductive covering with a spacing of not more than 30 mm (e.g. a grid or mesh) is to be provided at installation as an exposed-conductive-part over the heating system. See also Regulation 701.753 for bathrooms. A grid or mesh will not provide full mechanical protection against physical damage from nails, screws and the like, but is intended to provide a conductive path to earth, and not physical protection in its own right. A Class II heating system (or of equivalent construction) is also to be provided with additional protection by using a 30 mA RCD. Unfortunately, RCDs can be subject to unwanted tripping, and so the load on each RCD should be limited to ensure that any leakage current is limited to levels that will not cause unwanted operation of the RCD. A maximum circuit load of 7.5 kW for single-phase loads or 13 kW for three-phase loads are suggested in Section 753. All such heating systems must be installed in accordance with manufacturers’ instructions, and the possible temperature of connections and the local ambient temperatures must be considered in any installation. It is required that the installer (or designer) provides a record drawing for each heating system installed showing its location, area, rating details and, indeed, far more information than will ever actually be provided, in most cases. The complete list of information to be provided is given below. A description of the heating system shall be provided by the installer of the heating system to the owner of the building or his/her agent upon completion of the installation. The description shall contain at least the following information: a) Description of the construction of the heating system, which must include the installation depth of the heating units. b) Location diagram with information concerning: the distribution of the heating circuits and their rated power;
•
257
G
Guide to the Wiring Regulations
••
the position of the heating units in each room; conditions which have been taken into account when installing the heating units, for example, heating-free areas, complementary heating zones, unheated areas for fixing means penetrating into the floor covering. c) Data on the control equipment used, with relevant circuit diagrams and the dimensioned position of floor temperature and weather conditions sensors, if any. d) Data on the type of heating units and their maximum operating temperature. The installer shall inform the owner that the description of the heating system includes all necessary information, for example, for repair work. The installer shall provide the owner with a description of the heating system including all necessary information, for example, to permit repair work. In addition, the installer shall provide instructions for use of the heating installation. The designer/installer of the heating system shall hand over an appropriate number of instructions for use to the owner or his/her agent upon completion. One copy of the instructions for use shall be permanently fixed in or near each relevant distribution board. The instructions for use shall include at least the following information: a) Description of the heating system and its function. b) Operation of the heating installation in the first heating period in the case of a new building, for example, regarding drying out. c) Operation of the control equipment for the heating system in the dwelling area and the complementary heating zones as well, if any. d) Information on restrictions on placing of furniture or similar. Information provided to the owner shall cover the restrictions, if any, including: whether additional floor coverings are permitted, for example, carpets with a thickness of >10 mm may lead to higher floor temperatures which can adversely affect the performance of the heating system; where pieces of furniture solidly covering the floor and/or built-in cupboards may be placed on heating-free areas; where furniture, such as carpets, seating and rest furniture with pelmets, which in part do not solidly cover the floor, may not be placed in complementary heating zones, if any.
• • •
G
258
Special Locations
e) Information on restrictions on placing of furniture or similar. f) In the case of ceiling heating systems, restrictions regarding the height of furniture. Cupboards of room height may be placed only below the area of ceiling where no heating elements are installed. g) Dimensioned position of complementary heating zones and placing areas. h) Statement that, in the case of thermal floor and ceiling heating systems, no fixing shall be made into the floor and ceiling respectively. Excluded from this requirement are unheated areas. Alternatives shall be given, where applicable. References British Standards Institution (1958) BS 3036: 1958 Specification. Semi-enclosed electric fuses (rating up to 100 amperes and 240 volts to earth) London: BSI British Standards Institution (1971) BS 1361: 1971 Specification for cartridge fuses for a.c. circuits in domestic and similar premises London: BSI British Standards Institution (1979) PD 6484: 1979 Commentary on corrosion at bimetallic contacts and its alleviation London: BSI British Standards Institution (1988) BS 88 part 1: 1988 Cartridge fuses for voltages up to and including 1000 V a.c. and 1500 V d.c. London: BSI British Standards Institution (1998) BS 7430: 1998 Code of Practice for Earthing London: BSI British Standards Institution (2003) BS EN 60898 part 1: 2003 Specification for circuit-breakers for overcurrent protection for household and similar installations London: BSI British Standards Institution (2008) BS 7671: 2008 Requirements for Electrical Installations â&#x20AC;&#x201C; IEE Wiring Regulations Seventeenth Edition London: BSI Coates, M. and Jenkins, B. D. (2003) Electrical Installation Calculations 3rd ed. Oxford: Blackwell Science Ltd Kaplan, S. M. (2004) Wiley Electrical And Electronics Engineering Dictionary Hoboken: John Wiley & Sons
259
G
Appendices
Appendices Appendices 1–5 are contained within this chapter; Appendices 10–17 are available via the Companion Website (see below for details). 1 Standards and bibliography 2 Popular cables current rating tables from BS 7671: 2008 Appendix 4 4E1A 4E4A and 4D5A (samples only) 3 Limiting earth fault loop impedance tables from BS 7671: 2008 4 Cable data-resistance, impedance and R1 + R2 values 5 Fuse I 2t characteristics The following appendices are included on the Companion Website available at http://www.wiley.com/go/eca_wiringregulations 10 11 12 13 14 15 16 17 18
Example cable sizing calculations Impedances of conduits and trunking Earth electrodes and earth electrode testing Notes on Out of Reach/Obstacles/Non-conducting Location/Earth-free Local Equipotential Bonding (see 4.6.1) Additional ‘occasional’ tests that may be required Notes on periodic inspection and testing Electrical Research Association (ERA) report on armoured cables with external cpcs A4 sample versions of ECA BS 7671: 2008 certificates and forms Building Standards in Scotland
261
Guide to the Wiring Regulations
1
Appendix 1 – Standards and bibliography
Standards The following list of standards may be used or encountered when undertaking electrical installation work. This list is not expected to be used other than as a look-up table when a standard number is quoted and only a fraction of these standards were used when writing this book. The following table does not include the date of the standard, merely the title. The BSI’s website for ‘standards on line’ is an excellent database and tool for searching standards. It is available to search free of charge for viewing the title of standards and is accessed via http://www.bsonline.bsi-global.com Standard no.
Title
BS 31
Specification. Steel conduit and fittings for electrical wiring
BS 67
Specification for ceiling roses
BS 881
Cartridge fuses for voltages up to and including 1000 V a.c. and 1500 V d.c.
BS 196
Specification for protected-type non-reversible plugs, socket-outlets, cable couplers and appliance couplers with earthing contacts for single-phase a.c. circuits up to 250 volts
BS 4761
Fire tests on building materials and structure
BS 546
Specification. Two-pole and earthing pin plugs, socket outlets and socket outlet adaptors
BS 559
Specification for electric signs and high voltage luminous discharge tube installations
BS 646
Specification. Cartridge fuse links (rated up to 5 amperes) for a.c. and d.c. service
BS 731
Flexible steel conduit for cable protection and flexible steel tubing to enclose flexible drives
BS 731–1
Flexible steel conduit and adaptors for the protection of electric cables
BS 951
Specification for clamps for earthing and bonding purposes
BS 1361
Specification for cartridge fuses for a.c. circuits in domestic and similar premises
BS 1362
Specification for general purpose fuse links for domestic and similar purposes (primarily for use in plugs)
BS 13631
13 A plugs, socket outlets, connection units and adaptors
BS 3036
Specification. Semi-enclosed electric fuses (rating up to 100 amperes and 240 volts to earth)
BS 35351
Isolating transformers and safety isolating transformers; to be jointly read with the BS EN 61558 series of standards
BS 3676
Switches for household and similar fixed electrical installations
BS 4066
1
1
Tests on electric cables under fire conditions
262
Appendices Standard no.
Title
BS 4363
Specification for distribution assemblies for electricity supplies for construction and building sites
BS 4444
Guide to electrical earth monitoring and protective conductor proving
BS 45531
Specification for 600/1000 V single-phase split concentric electric cables
BS 4568
Specification for steel conduit and fittings with metric threads of ISO form for electrical installations
BS 4568
Steel conduit, bends and couplers
BS 4573
Specification for 2-pin reversible plugs and shaver socket outlets
BS 4607
Non-metallic conduits and fittings for electrical installations
BS 46781
Cable trunking
BS 4727
Glossary of electrotechnical, power, telecommunications, electronics, lighting and colour terms
BS 5042
Specification for bayonet lampholders (replaced by BS EN 61184)
BS 5266
Emergency lighting
BS 5345
Electrical apparatus for explosive gas atmospheres (replaced in part by BS EN 60079) and BS EN 50014: 1998 Electrical apparatus for potentially explosive atmospheres
BS 5467
Specification for 600/1000 V and 1900/3300 V armoured electric cables having thermosetting insulation
BS 5518
Specification for electronic variable control switches (dimmer switches) for tungsten filament lighting
BS 56551
Lifts and service lifts
BS 5733
Specification for general requirements for electrical accessories
BS 5839
1
Fire detection and alarm systems for buildings
BS 6004
2000 Electric cables. PVC insulated, non-armoured cables for voltages up to and including 450/750 V, for electric power, lighting and internal wiring
BS 6141
Specification for insulated cables and flexible cords for use in high temperature zones
BS 62071
Mineral insulated cables with a rated voltage not exceeding 750 V
BS 6346
Specification for 600/1000 V and 1900/3000 V armoured cables having PVC insulation
BS 6351
Electric surface heating
BS 63511
Specification for electric surface heating devices etc.
BS 6423
Code of practice for maintenance of electrical switchgear and control gear for voltages up to and including 1â&#x20AC;&#x2030;kV
BS 64581
Fire hazard testing for electrotechnical products
BS 6500
Electric cables. Flexible cords rated up to 300/500 V, for use with appliances and equipment intended for domestic, office and similar environments
BS 6651
Code of practice for protection of structures against lightning
BS 6701
Code of practice for installation of apparatus intended for connection to certain telecommunications systems
263
1
Guide to the Wiring Regulations Standard no.
Title
BS 6724
Specification for 600/1000 V and 1900/3300 V armoured cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire
BS 6883
Elastomer insulated cables for fixed wiring in ships and on mobile and fixed offshore units
BS 6907
Electrical installations for open cast mines and quarries
BS 6972
Specification for general requirements for luminaire supporting couplers for domestic, light industrial and commercial use
BS 6991
Specification for 6/10 amp two pole weather-resistant couplers for household, commercial and light industrial equipment
BS 7001
Specification for interchangeability and safety of a standardized luminaire supporting coupler (to be read in conjunction with BS 6972)
BS 7071
Specification for portable residual current devices
BS 7211
Specification for thermosetting insulated cables with low emission of smoke and corrosive gases when affected by fire
BS 7288
Specification for socket outlets incorporating residual current devices (SRCDs)
BS 7375
Code of practice for distribution of electricity on construction and building sites
BS 7430
Code of practice for earthing
BS 7454
Method for calculation of thermally permissible short-circuit currents taking into account nonadiabatic heating effects
BS 76291
Specification for 300/500 V fire-resistant electric cables having low emission of smoke and corrosive gases when affected by fire
BS 7697
Nominal voltages for low voltage public electricity supply systems
BS 7769
1
Electric cables, Calculation of current rating
BS 7822
1
Insulation coordination for equipment within low voltage systems
BS 7846
Electric cables. 600/1000 V armoured fire resistant electric cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire
BS 7889
Specification for 600/1000 V single-core unarmoured electric cables having thermosetting insulation
BS 7895
Specification for bayonet lampholders with enhanced safety
BS 7919
Electric cables. Flexible cables rated up to 450/750 V, for use with appliances and equipment intended for industrial and similar environments
BS 8436
300/500 V screened electric cables having low emission of smoke and corrosive gases when affected by fire, for use in thin partitions and building voids
BS EN 16481 BS EN 50110
1
Leisure accommodation vehicles. 12 V direct current extra low voltage electrical installations 1
Operation of electrical installations
BS EN 50014
Electrical apparatus for potentially explosive atmospheres
BS EN 50081
Electromagnetic compatibility. Generic emission standard
264
Appendices Standard no.
Title
BS EN 50082
Electromagnetic compatibility. Generic immunity standard. (Partially replaced by BS EN 61000â&#x20AC;&#x201C;6-2: 1999)
BS EN 500851
Specification for cable trunking and ducting systems for electrical installations
BS EN 50086
Specification for conduit systems for electrical installations
1
BS EN 50265
Common test methods for cables under fire conditions. Test for resistance to vertical flame propagation for a single insulated conductor or cable
BS EN 502651
Tests for resistance to vertical flame propagation for a single insulated conductor or cable
BS EN 50281
Electrical apparatus for use in the presence of combustible dust
BS EN 50310
Application of equipotential bonding and earthing in buildings with information technology equipment
BS EN 600791
Electrical apparatus for potentially explosive gas atmospheres
BS EN 60238
Specification for Edison screw lampholders
BS EN 60269
1
Low voltage fuses
BS EN 60309
1
Plugs, socket outlets and couplers for industrial purposes.
BS EN 60335
1
Household appliances (many parts, about a hundred)
BS EN 60423
Conduits for electrical purposes. Outside diameters of conduits for electrical installations and threads for conduits and fittings (replaces BS 6053)
BS EN 604391
Specification for low voltage switchgear and control gear assemblies
BS EN 60445
Basic and safety principles for man-machine interface, marking and identification. Identification of equipment terminals and of terminations of certain designated conductors, including general rules for an alphanumeric system
BS EN 60446
Basic and safety principles for the man-machine interface, marking and identification. Identification of conductors by colours or numerals
BS EN 60529
Specification for degrees of protection provided by enclosures (IP code)
BS EN 60570
Electrical supply track systems for luminaires
BS EN 60598
Luminaires
BS EN 60598â&#x20AC;&#x201C;2-24
Luminaires with limited surface temperature
BS EN 60617
Graphical symbols for diagrams
BS EN 606691
Switches for household and similar fixed electrical equipment
BS EN 607021
Mineral insulated cables and their terminations with a rated voltage not exceeding 750 V
BS EN 60742
Isolating transformers and safety isolating transformers
BS EN 60898
Specification for circuit-breakers for overcurrent protection for household and similar installations
BS EN 609471
Specification for low voltage switchgear and control gear
BS EN 609471
Switches, disconnectors, switch-disconnectors and fuse-combination units
265
1
Guide to the Wiring Regulations Standard no.
Title
BS EN 60950
Specification for safety of information technology equipment including electrical business equipment
BS EN 610081
Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs)
BS EN 61009
Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs)
BS EN 610111
Electric fence energizers. Safety requirements for mains operated electric fence energizers
BS EN 61184
Bayonet lampholders
BS EN 61386
Conduit system for cable management. General requirements
Note 1: Contains various parts
Bibliography and further reading Readers may find the following publications useful as additional reading.
•• •
IEE Guidance Notes 1 to 8 inclusive IEE Commentary on BS 7671: 2001 Cooper Development Agency (CDA), various publications on harmonics, also mirrored to some extent by BSRIA. See websites for details: www.cda.org.uk www.bsria.co.uk
1
••
266
Three tables are included here, BS 6004 PVC thermosetting flat twin and earth, XLPE thermosetting single-core and XLPE thermosetting armoured. These tables are not complete and have been added to make this book, particularly Chapter C, readable. For complete tables, please refer to BS 7671: 2008.
Appendix 2 – Popular cables: current rating tables from BS 7671: 2008 Appendix 4
2
(A)
13
27
57
1
(mm2)
1
4
16
46
22
10.5
(A)
3
Reference Method 101 (above a plasterboard ceiling covered by thermal insulation exceeding 100 mm in thickness)
63
27
13
(A)
4
Reference Method 102# (in a stud wall with thermal insulation with cable touching the inner wall surface)
42.5
17.5
8
(A)
5
Reference Method 103# (in a stud wall with thermal insulation with cable not touching the inner wall surface)
85
37
16
(A)
6
Reference Method C* (clipped direct)
57
26
11.5
(A)
7
Reference Method A* (enclosed in conduit in an insulated wall)
2.8
11
44
(mV/A/m)
8
Voltage drop (per ampere per metre)
Ambient temperature: 30°C Conductor operating temperature: 70°C
A* For full installation method refer to Table 4A2 Installation Method 2 but for Twin flat and earth cable B* For full installation method refer to Table 4A2 Installation Method 20 but for Twin flat and earth cable 100# For full installation method refer to Table 4A2 Installation Method 100 101# For full installation method refer to Table 4A2 Installation Method 101 102# For full installation method refer to Table 4A2 Installation Method 102 103# For full installation method refer to Table 4A2 Installation Method 103 Wherever practicable, a cable is to be fixed in a position such that it will not be covered with thermal insulation. Regulation 523.7, BS 5803-5: Appendix C: Avoidance of overheating of electric cables, Building Regulations Approved document B and Thermal insulation: avoiding risks, BR 262, BRE, 2001 refer.
Reference Method 100 (above a plasterboard ceiling covered by thermal insulation not exceeding 100 mm in thickness)
Conductor crosssectional area
Current-carrying capacity (A)
Samples from Table 4 D5A 70°C thermoplastic insulated and sheathed flat cable with protective conductor (copper conductors).
Table 4C5 Rating factors for groups of one or more circuits of single-core cables to be applied to reference current-carrying capacity for one circuit of single-core cables in free air – Reference Method F in Tables 4D1A to 4J4A.
2
Appendices
267
2
2
268
2
(A)
9
158
278
486
(mm2)
1.5
50
120
300
435
249
141
17
(A)
3
603
354
198
23
(A)
4
514
312
175
20
(A)
5
3 or 4 cables, threephase a.c.
2 cables, singlephase a.c. or d.c.
2 cables, singlephase a.c. or d.c.
3 or 4 cables, threephase a.c.
(enclosed in conduit on a wall or in trunking, etc.)
(enclosed in conduit in thermally insulating wall, etc.)
1
Conductor crosssectional area
Current-carrying capacity (A)
743
413
228
25
(A)
6
2 cables, singlephase a.c. or d.c. flat and touching
681
379
209
23
(A)
7
3 or 4 cables, threephase a.c. flat and touching or trefoil
(clipped direct)
783
437
242
—
(A)
8
736
400
216
—
(A)
9
3 cables, threephase a.c. flat
703
383
207
—
(A)
10
3 cables, threephase a.c trefoil
902
500
275
—
(A)
11
Horizontal
833
454
246
—
(A)
12
Vertical
2 cables, singlephase a.c. or d.c. or 3 cables threephase a.c. flat
Spaced by one cable diameter
Touching
2 cables, singlephase a.c. or d.c. flat
(in free air)
(in free air or on a perforated cable tray etc horizontal or vertical, etc.)
Ambient temperature: 30°C Conductor operating temperature: 90°C
Samples from Table 4 E1A Single-core 90°C thermosetting insulated cables, unarmoured, with or without sheath (copper conductors).
Guide to the Wiring Regulations
2 (A) 62 146 219 515
(mm2)
6
25
50
185
441
187
124
53
(A)
3
539
228
152
66
(A)
4
463
197
131
56
(A)
5
1 three- or 1 fourcore cable, threephase a.c.
1 two-core cable, single-phase a.c. or d.c.
1 two-core cable, single-phase a.c. or d.c.
1 three- or 1 fourcore cable, threephase a.c.
(in free air or on a perforated cable tray etc, horizontal or vertical)
(clipped direct)
1
Conductor crosssectional area
Current-carrying capacity (A)
343
164
116
53
(A)
6
1 two-core cable, single-phase a.c. or d.c.
281
135
96
44
(A)
7
1 three- or 1 fourcore cable, threephase a.c.
(direct in ground or in ducting in ground, in or around buildings)
Air ambient temperature: 30°C Ground ambient temperature: 20°C Conductor operating temperature: 90°C
Samples from Table 4 E4A Multicore 90°C armoured thermosetting insulated cables (copper conductors).
Appendices
269
2
Guide to the Wiring Regulations
3
Appendix 3 – Limiting earth fault loop impedance tables from BS 7671: 2008
Table 41.2 Maximum earth fault loop impedance (Zs) for fuses, for 0.4 s disconnection time with U0 of 230 V (see Regulation 411.4.6). (a) General purpose (gG) fuses to BS 88–2.2 and BS 88–6 Rating (A)
6
10
16
20
25
32
Zs (W)
8.52
5.11
2.70
1.77
1.44
1.04
(b) Fuses to BS 1361 Rating (A)
5
15
20
30
Zs (W)
10.45
3.28
1.70
1.15
(c) Fuses to BS 3036
(d) Fuses to BS 1362
Rating (A)
5
15
20
30
Rating (A)
3
13
Zs (W)
9.58
2.55
1.77
1.09
Zs (W)
16.4
2.42
NOTE: The circuit loop impedances given in the table should not be exceeded when the conductors are at their normal operating temperature. If the conductors are at a different temperature when tested, the reading should be adjusted accordingly.
Table 41.3 Maximum earth fault loop impedance (Zs) for circuit breakers with U0 of 230 V, for instantaneous operation giving compliance with the 0.4 s disconnection time of Regulation 411.3.2.2 and 5 s disconnection time of Regulation 411.3.2.3. (a) Type B circuit breakers to BS EN 60898 and the overcurrent characteristics of RCBOs to BS EN 61009 Rating (A) Zs (W)
3
6
10
7.67 15.33
16
20
2.87 4.60
25
32
1.84 2.30
40
50
1.15 1.44
63
80
0.73 0.92
100
125
0.46 0.57
In 46/In
0.37
(b) Type C circuit breakers to BS EN 60898 and the overcurrent characteristics of RCBOs to BS EN 61009 Rating (A)
6
Zs (W)
3.83
10
16
20
1.44 2.30
25
32
0.92 1.15
40
50
0.57 0.72
63
80
0.36 0.46
100
125
0.23 0.29
In 23/In
0.18
(c) Type D circuit breakers to BS EN 60898 and the overcurrent characteristics of RCBOs to BS EN 61009 Rating (A)
6
Zs (W)
1.92
10
16
20
0.72 1.15
25
32
0.46 0.57
40
50
0.29 0.36
63
80
0.18 0.23
100
125
0.11 0.14
In 11.5/In
0.09
NOTE: The circuit loop impedances given in the table should not be exceeded when the conductors are at their normal operating temperature. If the conductors are at a different temperature when tested, the reading should be adjusted accordingly.
3
270
Appendices
Table 41.4 Maximum earth fault loop impedance (Zs) for fuses, for 5 s disconnection time with U0 of 230 V (see Regulation 411.4.8). (a) General purpose (gG) fuses to BS 88–2.2 and BS 88–6 Rating (A)
6
10
16
20
25
32
40
50
Zs (W)
13.5
7.42
4.18
2.91
2.30
1.84
1.35
1.04
Rating (A)
63
80
100
125
160
200
Zs (W)
0.82
0.57
0.42
0.33
0.25
0.19
(b) Fuses to BS 1361 Rating (A)
5
15
20
30
45
60
80
100
Zs (W)
16.4
5.00
2.80
1.84
0.96
0.70
0.50
0.36
(c) Fuses to BS 3036 Rating (A)
5
15
20
30
45
60
100
Zs (W)
17.7
5.35
3.83
2.64
1.59
1.12
0.53
(d) Fuses to BS 1362 Rating (A)
3
13
Zs (W)
23.2
3.83
NOTE: The circuit loop impedances given in the table should not be exceeded when the conductors are at their normal operating temperature. If the conductors are at a different temperature when tested, the reading should be adjusted accordingly.
271
3
Guide to the Wiring Regulations
4
Appendix 4 – Cable data-resistance, impedance and ‘R1 + R2’ values Table 4.1 Resistance of copper cables at 20°C. Conductor nominal cross-sectional area (mm2)
Maximum resistance of copper conductors at 20°C (W/km)
0.5
36
0.75
24.5
1
18.1
1.5
12.1
2.5
7.41
4
4.61
6
3.08
10
1.83
16
1.15
25
0.727
35
0.524
50
0.387
70
0.268
95
0.193
120
0.153
150
0.124
185
0.0991
240
0.0754
300
0.0601
400
0.0470
500
0.0366
630
0.0221
1000
0.0176
2000
0.0090
Notes: Values are for stranded conductors but solid conductors are nearly identical. Taken from BS 6360: 1991.
4
272
Appendices Table 4.2 Values of R1 + R2 for cables using wire for cpc at 20°C. Conductor nominal crosssectional area (mm2)
Maximum resistance of copper conductors at 20°C (W/km)
1.5
24.2
2.5
14.82
4
9.22
6
6.16
10
3.66
16
2.30
25
1.454
35
1.048
50
0.774
70
0.536
95
0.386
120
0.306
150
Generally at these sizes a cable cpc is not used. If needed, R1 + R2 can be worked out from Table 4.1
185 240 300 400 500 630 1000 2000
Notes: Values are for stranded conductors but solid conductors are nearly identical. Taken from BS 6360: 1991.
Table 4.3 Values of R1 + R2 for twin and earth cables to BS 6004 at 20°C. Cable size (mm2)
Size of CPC
R1 + R2 (W/km)
50 m value of R1 + R2 50 m run (W)
1.5
1
30.2
1.51
2.5
1.5
19.51
0.98
4
1.5
16.71
0.84
6
2.5
10.49
0.52
10
4
6.44
0.32
16
6
4.23
0.211
273
4
Guide to the Wiring Regulations Table 4.4 Resistance data for armoured cables at 20°C (copper conductors). Nominal CSA of conductor (mm2)
R1 resistance (W/km)
Armour resistance steel wire 2-core (W/km)
3-core (W/km)
4-core (W/km)
5-core (W/km)
1.5
12.1
10.2
9.5
8.8
8.2
2.5
7.41
8.8
8.2
7.7
6.8
4
4.61
7.9
7.5
6.8
6.2
6
3.08
7.0
6.7
4.3
3.9
10
1.83
6.0
4.0
3.7
3.4
16
1.15
3.7
3.5
3.1
2.2
25
0.727
3.7
2.5
2.3
1.8
35
0.524
2.6
2.3
2.0
1.6
50
0.387
2.3
2.0
1.8
1.1
70
0.268
2.0
1.8
1.2
0.94
95
0.193
1.4
1.3
1.1
—
120
0.153
1.3
1.2
0.76
—
150
0.124
1.2
0.78
0.68
—
185
0.099
0.82
0.71
0.61
—
240
0.075
0.73
0.63
0.54
—
300
0.060
0.67
0.58
0.49
—
400
0.047
0.59
0.52
0.35
—
Note 1: Data is adapted from BS 5467 for XLPE shaped conductors but other conductor shapes and PVC cables have negligible differences.
Table 4.5 R1 + R2 data for armoured cables at 20°C, copper conductors.
4
Nominal CSA of conductor (mm2)
R1 + R2 values using armour steel wire 2- core R1 + R2 (W/km)
4- core R1 + R2 (W/km)
1.5
22.3
20.9
2.5
16.21
15.11
4
12.51
11.41
6
10.08
7.38
10
7.83
5.53
16
4.85
4.25
25
4.43
2.93
35
3.12
2.52
274
Appendices Nominal CSA of conductor (mm2)
R1 + R2 values using armour steel wire 2- core R1 + R2 (W/km)
4- core R1 + R2 (W/km)
50
2.69
2.19
70
2.27
1.47
95
1.59
1.29
120
1.45
0.91
150
1.33
0.80
185
0.92
0.71
Note 1: Data is adapted from BS 5467 for XLPE shaped conductors but other conductor shapes and PVC cables have negligible differences.
Table 4.6 Correction factors for temperature of copper and steel. Temperature of component
Correction factor for copper
Correction factor for steel
20
1.000
1.000
25
1.020
1.025
30
1.039
1.050
35
1.059
1.075
40
1.079
1.100
45
1.098
1.125
50
1.118
1.150
55
1.138
1.175
60
1.157
1.200
65
1.177
1.225
70
1.197
1.250
75
1.216
1.275
80
1.236
1.300
85
1.256
1.325
90
1.275
1.350
95
1.295
1.375
100
1.314
1.400
105
1.334
1.425
275
4
276
7
4
2
10
10
10
3
10
5
6
10
10
10
10 8
2
Ampere 2 seconds
5
2
4
6
10
16
20
25
32
35
40
50
Pre-Arcing I2t
Total Operating I2t
63
80
200 250
Fuse Rating
100 125 160
315 365 400
With a prospective current up to 80kA, 0.15 p.f. at 415 Volts
450 500 560
2-1250 Amp
630 670 710 750 800 1000 1250
Discrimination between fuse-links is achieved when the total I2t of the minor fuse-link does not exceed the pre-arcing I2t of the major fuse-link
Type T
The following fuse Iâ&#x20AC;&#x2030;2t characteristics have been adapted from information formerly produced by GEC switchgear.
Appendix 5 â&#x20AC;&#x201C; Fuse I2t characteristics
I t Characteristics
5
Guide to the Wiring Regulations
Index
Index agricultural premises 234–9 guidance 235–9 principles 235 purpose 235 requirements 235–9 alterations/additions, identification, conductors 97 ambient temperature de-rating, circuit breakers 125 armoured cables earthing/bonding 167–9 ECA recommendations 169 ERA report 168–9 protective conductors 167–9 sub-mains 65–6 XLPE thermosetting 266–9 atmospheric and switching overvoltages 133 automatic disconnection circuitry design 57–62 ELI 57–63 sub-mains 67 TN-C-S systems 57–63 TT systems 57–63 basic protection earthing/bonding 160 electric shock 5–6, 55–7, 160 basins/swimming pools see swimming pools/ basins bath/shower locations 221–8 electric shock requirements 226–7 equipment selection/erection 227–8 RCDs 226–7 risks 221–2 zone concept 222–6
bonding see earthing/bonding; protective bonding break times classification, safety services 144 BS 6004 PVC thermosetting flat twin and earth cables 266–9 BS 7671: 2008 changes, overview 5–9 introduction 1–3 layout 4 origins 2–3 overview 5–9 plan 4 Building Act 1984 14–15 Building Regulations and Part P 14–15, 18–19 cable couplers 140 cable data resistance impedance and R1 + R2 values 272–5 cable management cable separation 105–6 EMC 105–6 cable separation cable management 105–6 data/control cables 102–5 EMC 102–5 IT cables 102–5 power cables 102–5 sensitive equipment 102–5 cable size circuitry design 30–1 overload protection 34–6 cable specification, fire minimizing 117–19 cable types/installation, standard final circuit designs 75–6
277
Index cables see also wiring systems armoured 65–6, 167–9 BS 6004 PVC thermosetting flat twin and earth 266–9 current carrying capacity 30 current rating tables 266–9 protective bonding 171–5 rating tables 266–9 underfloor heating 141 XLPE thermosetting armoured 266–9 XLPE thermosetting single core 266–9 caravan/camping parks 239–43 guidance 240–3 principles 239–40 purpose 239–40 requirements 240–3 ceiling heating see floor/ceiling heating CENELEC HD 60384, corresponding parts 2–3 certification see also inspection/testing/certification electrical installation certificate (BS 7671: 2008) 208–11 minor electrical installation works certificate (BS 7671: 2008) 209, 215 overview 208–9 paperwork 208–18 periodic inspection report for an electrical installation (BS 7671: 2001) 209 schedule of inspections 209, 218 schedule of test results 209, 216–17 single signatory electrical installation certificate (BS 7671: 2008) 209, 211–14 changes, overview, BS 7671: 2008 5–9 circuit breaker to circuit breaker discrimination 70–1 circuit breaker to fuse discrimination 71, 72 circuit breakers 119–25 ambient temperature de-rating 125 characteristics 120–4 domestic circuits 77–9 magnetic characteristic 122–4 operation 120–4 sensitivity characteristics 122–4 thermal characteristic 122 types 119–20 circuit cable method, continuity testing 192–3 circuitry 21–89
278
design procedure 22–3 discrimination coordination 67–71, 72 harmonics 73–4 load assessment 23–9 parallel cables 71–3 RCDs 83–6 ring final circuits 87–8 safety services 146 standard final circuit designs 74–83 sub-mains 64–7 system discrimination 67–71 circuitry design 30–64 automatic disconnection 57–63 cable size 30–1 design procedure 22–3 disconnection/electric shock 55–64 ELI 57–63 fault protection 46–9 overcurrent protection 32 overload protection 32–45 standard final circuit designs 74–83 voltage drop 49–55 circulating currents, wiring systems 110–12 colour identification, conductors 93–7 commercial installations protective bonding 171–5 RCDs 127 compression joints, electrical connections 114 conductor temperature correction, voltage drop 52–5 conductors alterations/additions, identification 97 characters identification 95 colour identification 93–7 control circuits, ELV and other applications 96, 97 DC identification 96, 98 earthing conductor 167 enclosures 116–17 heating conductors 141 identification 93–100 interface marking 98–100 marking identification 97 protective conductors 160–7 connected load, load assessment 24 connections, electrical see electrical connections consumer unit arrangements, RCDs 84–6 consumer units, domestic installations 132 continuity testing 189–93
Index circuit cable method 192–3 R1 + R2 method 192–3 wandering lead method 190–1 control circuits, ELV and other applications, conductors 96, 97 corrosion, galvanic (electrolytic), joints 114–16 crest factor, load assessment 24–6 current rating tables, cables 266–9 data/control cables, cable separation 102–5 DC identification, conductors 96, 98 DC issues, RCDs 130, 131 design, circuitry see circuitry design design current Ib, overload protection 34 design procedure, circuitry 22–3 determination of fault current, fault protection 47 disconnection, automatic, circuitry design 57–63 disconnection/electric shock, circuitry design 55–64 discrimination coordination circuit breaker to circuit breaker discrimination 70–1 circuit breaker to fuse discrimination 71, 72 circuitry 67–71, 72 fuse-to-fuse discrimination 69–70 discrimination, RCDs 129–30 distribution circuits, sub-mains 64–5 diversity load assessment 28–9 sub-mains 64 domestic circuits circuit breakers 77–9 fuses 77–9 standard final circuit designs 77–9 domestic installations consumer units 132 protective bonding 176–7 RCDs 126 domestic layouts, protective bonding 178–82 duty cycle, load assessment 24 earth fault loop impedance (ELI) adjustment 63 automatic disconnection 57–63 circuitry design 57–63
external (Ze) ELI, standard final circuit designs 75–6 external (Ze), testing 201–3 irrelevant specification 63 limiting tables 270–1 testing 201–4 total ELI 203–4 earthing/bonding 151–83 armoured cables 167–9 basic protection 160 earthing arrangements 153–9 earthing conductor 167 fault protection 160 general requirements 159–61 hierarchy 153 high earth leakage installations 183 IT systems 157–9 lettering code 154 protective bonding 151–2, 160–1, 169–82 protective conductors 160–7 TN-C-S systems 155–9 TT systems 157–9 ECA recommendations, armoured cables 169 eddy currents, wiring systems 111–12 electric shock basic protection 55–7, 160 disconnection/electric shock, circuitry design 55–64 fault protection 55–7 electric shock requirements bath/shower locations 226–7 RCDs 226–7 electrical connections see also joints accessibility 116 compression joints 114 corrosion 114–16 enclosures 116–17 fine wire 117 galvanic (electrolytic) corrosion 114–16 joints 112–17 multi-wire 117 temperature 116 very fine wire 117 wiring systems 112–17 electrical installation certificate (BS 7671: 2008), certification 208–11 Electricity Act 1984 (as amended) 14
279
Index Electricity at Work Regulations 1989 (EWR 1989) 12–13, 18 Electricity Safety Quality and Continuity Regulations 2000 (as amended) 13 electrode boilers 140 electrolytic (galvanic) corrosion, joints 114–16 electromagnetic compatibility (EMC) 101–6 cable management 105–6 cable separation 102–5 directive 101–2 Electromagnetic Compatibility Regulations 2006 (EMC) 16 electromagnetic disturbances 132–3 ELI see earth fault loop impedance EMC see electromagnetic compatibility; Electromagnetic Compatibility Regulations 2006 enclosures electrical connections 116–17 live conductors 116–17 equipment compliance with Standards 92–3 selection requirements 91–3 equipotential protective bonding see protective bonding ERA report, armoured cables 168–9 EWR 1989 see Electricity at Work Regulations 1989 exhibitions 243–6 guidance 244–6 requirements 244–6 risks 244 external (Ze) earth fault loop impedance (ELI) standard final circuit designs 75–6 testing 201–3 fault protection circuitry design 46–9 determination of fault current 47 earthing/bonding 160 electric shock 5–6, 55–7 fault capacity of devices 47 fault ratings 47–9 omissions 46 overload protection 47–9 requirements 46 terminology 46 fine wire electrical connections 117 fire minimizing
280
cable specification 117–19 PVC insulation 118–19 sealing building penetrations 118–19 wiring systems 117–19 floor/ceiling heating 141, 256–9 guidance 257–9 notes 257–9 requirements 256 frequency of inspections 218 fuse I2t characteristics 275–6 fuse-to-fuse discrimination 69–70 fuses, domestic circuits 77–9 galvanic (electrolytic) corrosion, joints 114–16 general requirements, BS 7671: 2008 11–19 generating sets 137–8 grouping factors, overload protection 36–44 harmonics assessment 74 circuitry 73–4 requirements 73–4 heating conductors 141 high earth leakage installations, earthing/ bonding 183 horticultural premises 234–9 principles 235 purpose 235 HV-LV faults 133 identification, conductors 93–100 alterations/additions 97 characters identification 95 colour identification 93–7 DC identification 96, 98 interface marking 98–100 marking identification 97 principles 94–5 IMDs see insulation monitoring devices industrial installations see also commercial installations protective bonding 171–5 ingress protection (IP) 146–50 equipment applications 149–50 examples 149–50 external influences 146–50 inspection/testing/certification (part 6) 185–217 frequency of inspections 218
Index schedule of inspections 209, 218 testing 188–208 visual inspection 186–8 insulation fire minimizing 118–19 PVC insulation 118–19 testing 196–200 wiring systems 118–19 insulation monitoring devices (IMDs) 133 interconnected L-CPC, ring continuity 196 interconnected L-N, ring continuity 195 interface marking, conductors 98–100 IP see ingress protection isolation and switching 132 IT cables, cable separation 102–5 IT systems, earthing/bonding 157–9 joints see also electrical connections compression 114 corrosion 114–16 galvanic (electrolytic) corrosion 114–16 wiring systems 112–17 layout, BS 7671: 2008 4 legal relationship, BS 7671: 2008 11–19 legal requirements and relationship, legislation, key UK 11–17 legal standing, Standards 18 lettering code, earthing/bonding 154 lighting/luminaires 7, 141–3 markings, BS EN 60598 143 live conductors, enclosures 116–17 load assessment circuitry 23–9 connected load 24 crest factor 24–6 definitions 23–6 diversity 28–9 duty cycle 24 load factor 24–6 maximum demand 26–8 principles 23–6 load factor, load assessment 24–6 load power factor correction, voltage drop 54–5 locations, special see special locations luminaires/lighting 141–3 markings, BS EN 60598 143 LV-HV faults 133
MCB (miniature circuit breakers) see circuit breakers magnetic characteristic, circuit breakers 122–4 marking identification, conductors 97 markings, BS EN 60598, luminaires/lighting 143 maximum demand, load assessment 26–8 miniature circuit breakers (MCB) see circuit breakers minor electrical installation works certificate (BS 7671: 2008), certification 209, 215 mobile units 253–6 application 253 guidance 254–6 notes 254–6 requirements 254 scope 253 modern installations, protective bonding 170–7 multi-wire electrical connections 117 negligence 17 open loop resistances, ring continuity 193–4 origins, BS 7671: 2008 2–3 overcurrent protection, circuitry design 32 overload protection cable size 34–6 circuitry design 32–45 design current Ib 34 fault protection 47–9 fundamentals 32–4 grouping factors 36–44 lack of 47–9 rating factors 36–44 overvoltage 132–3 parallel cables circuitry 71–3 general and 7671 requirements 71–3 unequal current sharing 73 part 3, BS 7671: 2008 19 Part P, Building Regulations and Part P 14–15, 18–19 periodic inspection report for an electrical installation (BS 7671: 2001), certification 209 periodic testing, safety services 146–7 phase rotation, polarity testing 201
281
Index photovoltaic (PV) power supply systems (712) see solar photovoltaic (PV) power supply systems (712) plan, BS 7671: 2008 4 plugs/socket outlets 139–40 polarity testing 200–1 phase rotation 201 power cables, cable separation 102–5 protection automatic disconnection 57–62 disconnection/electric shock, circuitry design 55–64 IP 146–50 overcurrent protection 32 overload see overload protection protection, electric shock basic protection 55–7 fault protection 55–7 protective bonding bonding solutions 170–7 BS 7671 requirements 170 commercial installations 171–5 constructional elements 171–5 domestic installations 176–7 domestic layouts 178–82 earthing/bonding 151–2, 160–1, 169–82 industrial installations 171–5 modern installations 170–7 purpose 169 sizing 177 TN-C-S systems 178–82 TT systems 178–82 protective conductors 160–7 armoured cables 167–9 earthing/bonding 160–7 earthing conductor 167 physical types 162–3 sizing 164–6 up to 16mm2 165–6 PV cells see solar photovoltaic (PV) power supply systems (712) PVC insulation fire minimizing 118–19 wiring systems 118–19 R1 + R2 method, continuity testing 192–3 R1 + R2 values, cable data resistance impedance and 272–5 radial final circuits, circuitry 89
282
rating factors, overload protection 36–44 rating tables, cables 266–9 RCDs see residual current devices RCMs see residual current monitors (the) Regulations see BS 7671: 2008 residual current devices (RCDs) 125–31, 135–7 bath/shower locations 226–7 BS 7671 applications 125–7 BS 7671 requirements 128 circuitry 83–6 commercial installations 127 consumer unit arrangements 84–6 DC issues 130, 131 discrimination 129–30 domestic installations 126 electric shock requirements 226–7 functional tests 206–7 increased use 83–4 operation 127 socket outlets 125–7 supplementary protection 63–4 testing 206–7 TT installations 130–1 unwanted tripping 128–9 residual current monitors (RCMs) 135–7 resistance impedance and R1 + R2 values, cable data 272–5 ring continuity interconnected L-CPC 196 interconnected L-N 195 open loop resistances 193–4 testing 193–6 ring final circuits, circuitry 87–8 rotating machines 138–9 safety services 144–7 break times classification 144 circuitry 146 periodic testing 146–7 safety sources 145 testing, periodic 146–7 verification 146–7 schedule of inspections, certification 209, 218 schedule of test results, certification 209, 216–17 sealing building penetrations, fire minimizing 118–19 sensitive equipment, cable separation 102–5 sensitivity characteristics, circuit breakers 122–4
Index sheath currents, wiring systems 110–12 shock, electric see electric shock shower/bath locations see bath/shower locations shows see exhibitions single-core installations circulating currents 110–12 eddy currents 111–12 sheath currents 110–12 single signatory electrical installation certificate (BS 7671: 2008), certification 209, 211–14 sizing protective bonding 177 protective conductors 164–6 socket outlets/plugs 139–40 socket outlets, RCDs 125–7 solar photovoltaic (PV) power supply systems (712) 246–52 guidance 249–52 notes 249–52 principles 246–8 requirements 249 terminology 246–8 SPDs see surge protection devices special locations 219–59 additional requirements 221 agricultural premises 234–9 basins/swimming pools 221–8 bath/shower locations 221–8 caravan/camping parks 239–43 exhibitions 243–6 horticultural premises 234–9 mobile units 253–6 numbering 221 principles 219–21 purpose 219–21 shows 243–6 solar photovoltaic (PV) power supply systems (712) 246–52 stands, exhibition 243–6 swimming pools/basins 228–34 transportable units 253–6 (the) Standard see BS 7671: 2008 standard final circuit designs all-purpose standard final circuits 79–83 cable types/installation 75–6 domestic circuits 77–9 external earth fault loop impedances 75–6
scope 74–6 Standards 17–19, 262–6 bibliography 266 compliance with 92–3 defining 17–18 legal standing 18 role 17–19 stands, exhibition see exhibitions sub-mains armoured cables 65–6 automatic disconnection 67 circuitry 64–7 distribution circuits 64–5 diversity 64 surge protection devices (SPDs) 133–5 swimming pools/basins 228–34 guidance 232–4 requirements 232–4 zone concept 229–31 switching and atmospheric overvoltages 133 switching and isolation 132 system discrimination, circuitry 67–71 temperature ambient temperature de-rating, circuit breakers 125 electrical connections 116 temperature correction, conductor, voltage drop 52–5 testing see also inspection/testing/certification circuit cable method 192–3 continuity testing 189–93 ELI 201–4 functional tests 206–7 inspection/testing/certification (part 6) 188–208 insulation 196–200 pass/fail 188 polarity 200–1 prospective fault current 205–6 RCDs 206–7 required tests 188–9 ring continuity 193–6 safety services 146–7 voltage drop 208 wandering lead method 190–1 thermal characteristic, circuit breakers 122
283
Index TN-C-S systems automatic disconnection 57–63 earthing/bonding 155–9 protective bonding 178–82 tort 16–17 transportable units 253–6 application 253 guidance 254–6 notes 254–6 requirements 254 scope 253 tripping, unwanted, RCDs 128–9 TT installations, RCDs 130–1 TT systems automatic disconnection 57–63 earthing/bonding 157–9 protective bonding 178–82 underfloor heating see floor/ceiling heating undervoltage 132–3 unwanted tripping, RCDs 128–9 very fine wire electrical connections 117 visual inspection, inspection/testing/ certification (part 6) 186–8 voltage drop calculating 52 circuitry design 49–55 conductor temperature correction 52–5 defining 52
284
load power factor correction 54–5 requirements 49–50 system design values 50–1 temperature correction, conductor 52–5 testing 208 verification 208 wandering lead method, continuity testing 190–1 water heaters 140 (the) Wiring Regulations see BS 7671: 2008 wiring systems 106–19 see also cables choosing 106–9 circulating currents 110–12 eddy currents 111–12 electrical connections 112–17 fire minimizing 117–19 PVC insulation 118–19 ‘safe’ zones 108–9 selecting 106–9 sheath currents 110–12 single-core installations 110–12 XLPE thermosetting armoured cables 266–9 XLPE thermosetting single core cables 266–9 zone concept bath/shower locations 222–6 swimming pools/basins 229–31
Appendices
10 10.1
Appendix 10 Introduction This appendix gives two examples of cable sizing calculations in order to explain Chapter C of the book. Example one has been chosen to illustrate many of the techniques required or suggested in Chapter C, hence itâ&#x20AC;&#x2122;s length. Example two is a little more straightforward. Generally the procedure of Chapter C section C 4.1 will be followed as indicated on Figure C 4.1. For those that wish to find explanations to each stage of the calculation process, blue graphics have been included referring to the section numbers of Chapter C of the book.
Figure C 4.1 Cable sizing stage diagram
1
10
Guide to the Wiring Regulations
10.2
Example 1 Consider a 50 kW, 3 phase load at 0.8 power factor. The load is to be supplied by a cable to be run underground for 50 m and clipped to cable tray for a further 50 m together with 6 other similar cables. Overload protection is to be provided by a BS 88 fuse. The route length is 100 m and Ze is given as 0.15 ohms. The thermal resistivity of the soil along the underground part of the route has been confirmed as less than 2.5 K.m/W. It is assumed that the grouped cables may be subject to simultaneous overload (note however that this is an unlikely situation). 10.2.1 Selection of cable type and installation method
As the cable is to be laid underground a steel wire armoured cable (with copper conductors) is to be used. For half the route the cable is grouped with 6 other similar cables on a horizontal perforated cable tray otherwise run underground in a duct. Overload protection is required. 10.2.2 Calculate design current Ib
Using the equation in C 4.3.2 kW × 1000 (amps) and hence, √3 V1 × pf 50 Ib = × 1000 (amps) = 90.2 A √3 × 400 × 0.8 Ib =
10
2
Appendices
where: Ib is the design current of the circuit, (also for 3 phase denoted Il the line current) Vl is the line voltage also denoted U p.f. is the power factor cos θ kW is the load power in kilowatts 10.2.3 Select protective device rating
Where overload protection is to be provided: In ≥ Ib where: ≥ greater or equal to Ib is the design current of the circuit In is the nominal current or current setting of the protective device The smallest protective device greater than 90.2 A is a 100 A overcurrent device BS 88 fuse; thus is selected at In = 100 A. 10.2.4 Establish Ca, Gg, Ci & Cc
As the cable has mixed installation methods the options are to carry out these
3
10
Guide to the Wiring Regulations
calculations for both the buried portion and the portion run on tray and use the more onerous. However, from a quick glance at the various tables, the grouping factor or the cable with six other cables will be limiting and is used here. C a is correction factor for ambient temperature, (Tables 4B1 and 4B2 of BS 7671: 2008), No ambient temperature is given as is typically the case in practice as the assumption of a 30째C ambient is usual. This is higher than is likely, and is conservative for cable selection purposes. Hence from Table 4B1 of BS 7671: 2008 Ca = 1 C g is correction factor for grouping (Table 4C of BS 7671: 2008) From Table 4C1 (page 39 of this book) for a group of 7 cables single layer multicore on a perforated cable tray, Cg = 0.73 C i is correction factor for conductors surrounded by thermal insulation The cables are not surrounded by insulation so Ci =1 C c is a correction factor for the installation conditions (Table 4B3) and for use when overload protection is being provided by overcurrent devices with fusing factors greater than 1.45 e.g. Cc = 0.725 for semi-enclosed fuses to BS 3036. The fuse is BS 88 and the cable is not laid underground in this section of the cable route so Cc = 1 10.2.5 Calculate It
This calculation is based on the more onerous portion of the cable grouped on a cable tray. From section C 4.3.3,
10
4
Appendices
It ≥
In 100 and hence, It ≥ ≥ 137 A. Ca Cg Ci Cc 1 × 0.73 × 1 × 1
From Table 4D4A of BS 7671: 2008, column 7, the smallest cable suitable is a 70 mm2 four core cable; note the lowest rating of the two installed conditions has to be used and in this case, column 7 has a rating of 143 amps. 10.2.6 Check size for volt drop
Two calculations need to be carried out as the temperature of the cable will be different in each portion i) For the part of the cable route where the cable is clipped to cable tray with 6 other cables C ×(mV/A/m) × L × Ib Voltage drop in line to line voltage = t 1000 (see C 4.5.3 and C 4.5.4 of this book and the equation from paragraph 6.2 of Appendix 4 to BS 7671: 2008). Where: (mV/A/m)3p is the tabulated value of voltage drop in mV per amp per metre from the cable rating tables of Appendix 4 of BS 7671 for a three phase cable L is the length of the circuit cable in metres Ib is design current of the circuit A
(
Ct =
)
Ib2 (t – 30) It2 p 230 + tp
230 + tp – Ca2 Cg2 –
Where: tp is the rated conductor operating temperature from the rating table Ib is design current of the circuit
5
10
Guide to the Wiring Regulations
It is the tabulated current rating of the cable From Table 4D4B column 4, the (mV/A/m)3p is as follows: r = 0.55, x = 0.14, z = 0.57 For simplicity using z = 0.57,
(
230 + 70 – 12 × 0.732 – Ct =
)
902 (70 – 30) 2072
= 0.95 230 + 70 0.95 × 0.57 × 50 × 90.2 = 2.44 volts Voltage dropon tray = 1000
This may now be reduced using the consideration of load power factor and temperature, see C 4.5.5 L Ib [C cos φ (mV/A/m)r + sin φ (mV/A/m)x] 1000 t 50 × 90.2 [(0.97 × 0.55 × 0.8) + (0.6 × 0.140)] Voltage dropon tray (reduced) = 1000 = 2.30 volts Voltage dropon tray (reduced) =
Thus by using the ‘power factor’ voltage drop correction, the voltage drop has been reduced by some 40%. ii) For the part of the cable route where the cable is run underground For the underground section Ct is given by:
(
)
902 (70 – 30) 1432 Ct = = 0.920 230 + 70 L Ib [C cos φ (mV/A/m)r + sin φ (mV/A/m)x] Voltage dropunderground = 1000 t 50 × 90.2 [(0.920 × 0.55 × 0.8) + (0.6 × 0.140)] Voltage dropunderground = 1000 = 2.20 volts 230 + 70 – 12 × 12 –
Now combining the voltage drop for the portion on the tray and that for the buried cable Total voltage drop = 2.30 + 2.20 = 4.50 V
10
6
Appendices
This is voltage drop in the line voltage, so percentage voltage drop is % voltage drop =
4.50 Ă&#x2014; 100 = 1.13%, which is acceptable. 400
Graphical estimation of the correction to voltage drop for conductor temperature as per section C 4.5.4 of the book Manual calculations of Ct can be tedious and the graph in Figure C 4.5 provides a quick and convenient way of avoiding them. The graph can be used to correct tabulated (mV/A/m) values and can be applied to all cables under 16 mm2 and to the tabulated resistive component, (mV/A/m)r, for larger cables. The graph is accurate where grouping factor is one and, for the buried cable portion, Cg, Ci and Cc are = 1. Thus, figure C 4.5, gives a reduction factor (equivalent to Ct) of 0.9; this is the same as the value calculated in (ii) above.
Figure C 4.5 Reduction factors for thermoplastic cables (PVC)
7
10
Guide to the Wiring Regulations
10.2.7 Check for short circuit
As Ib ≤ In ≤ Iz the phase conductors and neutral do not need a separate check for thermal withstand, see section C 4.4.2 of the book and regulation 434.5.2. For the protective conductors, this does not need checking, see ECA recommendations C 5.3 of the book. For completeness however, calculations based on BS 7671: 2008 are now provided. i)
the adiabatic equation of regulation 543 I 2t S ≥ √ , or k
ii) meet the cross-sectional area requirements of Table 54.7. The minimum size arising from these can be used; this will virtually always be by the adiabatic equation. where: S is the nominal cross-sectional area of the conductor in mm2. I is the value in amperes (rms for ac) of fault current for a fault of negligible impedance t is the operating time of the disconnecting device in seconds corresponding to the fault current I amperes. k is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures, see Table 54. (i) Size using the adiabatic equation The fault current, If , is required and this is used to find a disconnection time using the protective device time current characteristic curve.
10
8
Appendices
The fault current (in this case an earth fault current) is first calculated using the earth fault loop impedance. Strictly speaking calculations need to be carried out at the upstream and downstream ends of the cable but for illustration purposes, both will be carried out here (often a high loop impedance and lower fault current can let through more energy). At distribution board outgoing terminals assuming a fault U If = 0 Ze Note Ze here is the earth fault loop impedance at the distribution board, in our simplified example it is also the external ELI. If =
230 = 1533 amps, 0.15
and from graph Figure 3.3B of BS 7671: 2008, disconnection time, t = 0.1 seconds. Note this figure would be lower if the British Standard or manufacturers data were used and the disconnection time would be 0.04 seconds, but we will proceed with 0.1 seconds. k from Table 54.4 is 51. I 2t √15332 0.1 = ≥ 9.5 mm2 S≥ √ k 51 At load assuming a fault U If = 0 Zs Note Zs here is the total earth fault loop impedance at the load end of the radial circuit. Using Table 4.5 of Appendix 4 of this book, the cable loop impedance, to be added to the external loop impedance is R1 + R2 (ohms per km) × L 2.19 × 100 = = 0.219 ohms 1000 1000 Total ELI, Zs = Ze + (R1 + R2) = 0.15 + 0.219 = 0.369 ohms. If =
230 = 623 amps, 0.369
and from graph Figure 3.3B of BS 7671: 2008, disconnection time, t = 2.8 seconds.
9
10
Guide to the Wiring Regulations
I 2t √6232 2.8 = ≥ 20.4 mm2 S≥ √ k 51 From Table 10.1, it can be seen that a 50 mm2 4-core armoured cable, the csa of the armouring is 122 mm2. (i) Size using Table 54.7, then Minimum area of protective conductor ≥
k1 S × k2 2
from Table 54.2 of BS 7671: 2008 Minimum area of protective conductor ≥
115 70 × ≥ 78.9 mm2 51 2
Table 10.1 Gross cross-sectional area of armour wires for two-core, three-core and fourcore 600/1000 V cables having steel-wire armour to BS 6436 Cross-sectional area of round armour wires
Nominal area of conductor 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
10
10
Cables with stranded copper conductors
Cables with solid aluminium conductors
2 -core (mm2)
3-core (mm2)
4-core (mm2)
4-core (reduced neutral) (mm2)
2 -core (mm2)
3-core (mm2)
4-core (mm2)
15 17 21 24 41 46 60 66 74 84 122 131 144 201 225 250 279
16 19 23 36 44 50 66 74 84 119 138 150 211 230 260 289 319
17 20 35 40 49 72 76 84 122 138 160 220 240 265 299 333 467
76 82 94 135 157 215 235 260 289 323 452
42 54 58 66 74 109 -
46 62 68 78 113 128 138 191 215 240 265 -
66 70 78 113 128 147 201 220 245 274 304 -
Appendices
10.2.8 Check for disconnection times
To check disconnection times you need to confirm that the total circuit earth fault loop impedance, ELI is less than that required by Chapter 41 of the regulations. We have designated the design ELI as Z41. So, Zs ≤ Z41 From Table 41.4 of BS 7671: 2008 or from Appendix 3 of this book, the maximum design ELI, Z41 ≤ 0.42 ohms.
Zs = Ze + L (r1 + r2) where:
Ze is the impedance in ohms of the source r1 is the resistance in ohms per metre of the line conductor r2 is the resistance in ohms per metre of the protective conductor L is the length of the cable in metres The value of r1 + r2 for steel wire armoured cables are given in tables in Appendix 4, Table 4.5 and for a 50 mm2 four core cable neglecting reactance and correction for temperature, is r1 + r2 =
1.47 × 100 = 0.147 ohms, 1000
and the total ELI = 0.15 + 0.147 = 0.297 ohms. Therefore the actual designed ELI is less than the 0.42 Ω given in Table 41.4 of BS 7671: 2008. It is noted that these values have been calculated using resistances of copper at 20°C, and an allowance has to be made for the final temperature of the conductors.
11
10
Guide to the Wiring Regulations
The new Appendix 14 of BS 7671: 2008 suggests a correction factor of 0.8. This however does not take into account that the cable will not be at its maximum operating temperature. A quick estimate of the reduction effect of this can be made using Figure C 4.5 of this book, but using Ib , Iz where Iz is the tabulated current carrying capacity. Thus, using BS 7671: 2008 correction factor, the maximum ELI is 0.42 + 0.8 = 0.336 and the cable ELI is within this value.
10.3
Example 2 This example is a radial circuit supplying luminaires of length 40 m. The circuit cable to be enclosed in 50 mm by 50 mm trunking with 8 other single phase circuits. The load Ib is estimated to be 10 A and a 20 A type B circuit breaker is to be used to avoid unwanted tripping on switch due to inrush. The client has required a protective conductor to be run in the trunking Ze is 0.4 ohm. 10.3.1 Cable type and installation method
Single core 70째C thermoplastic insulated cable without sheath enclosed in trunking is selected. 10.3.2 Calculate design current Ib
Ib = 10 A
10
12
Appendices
10.3.3 Calculate protective device rating
To avoid unwanted tripping the device rating is selected to be 20 A, In = 20 A 10.3.4 Establish Ca, Gg, Ci & Cc
C a is the rating factor for ambient temperature, (Table 4B1 of BS 7671), No ambient temperature is given, as is typically the case in practice. The assumption of a 30°C ambient is usual and is conservative for cable selection purposes. Hence from Table 4B1 of BS 7671: 2008 Ca = 1 Cg is the rating factor for grouping BS 7671: 2008 Appendix 4 includes revised information for grouping factors calculations. This includes a new table of grouping factors for buried cables. It also includes a new generic method for calculating grouping factors for circuits with different size as follows: F=
1 √n
where F is the group reduction factor and n is the number of circuits. Using F =
1 1 = = 0.33 √n √9
13
10
Guide to the Wiring Regulations
10.3.5 Calculate It
This would require a cable of tabulated rating Using Equation 2 given in C 4.3.3: It ≥
In (Equation 2) Ca Cg
Note that for many examples, the thermal insulation (Ci) and semi-enclosed fuse factor (Cc) are not used and have been ignored here. Thus, It ≥
In 20 ≥ ≥ 60 Ca Cg 1 × 0.333 × 1 × 1
These formulae will give a lower group factor than BS 7671 tables 4C1 to 4C5 as these tables assume that cables in the group are of the same size (and requiring a higher It). Table 4C1 (see C 4.33.4 of this book) gives a grouping factor = 0.5 It ≥
20 ≥ 40 (amps) 1 × 0.5 × 1 × 1
The procedure (see section C 4.3.4 in this book) for applying grouping factors is to use either the factor from BS 7671 Tables 4C1 to 4C2 or use the following method: Compare the formulae
√
It ≥ In2 + 0.48Ib2 with It ≥
10
Ib (Equation 4) Cg
14
2
( 1 C– C ) (Equation 3) g
2
g
Appendices
using the larger value (note these equation numbers are from this book, Chapter C). In our example Equation 3 is It ≥
√
1 – 0.52 202 1 2 + 0.48 × 10 = 23.3 amps 0.52 1 × 1 12
(
)
and Equation 4 is It ≥
10 ≥ 20 amps. 0.5
Thus an It equal or greater than 23.3 amps is to be selected. From Table 4D1A a 2.5 mm2 cable is adequate. In summary, for circuits that are not fully loaded, the use of this (Equation 4) method produces a lower It than the grouping factor method using Tables 4C1 to 4C5 from BS 7671. In summary the procedures are summarised as:
• •
If a quick size method is required use BS 7671 Tables 4C1 to 4C5 and Equation 2, In It ≤ Ca Cg and do no more or, Calculate It using Equation 4 and Equation 3, using the larger It value.
To make life even easier and to save application of the second bullet point above which can be tiresome, the following look up table in Figure C 4.3 can be used instead and applied to Equation 2 (do not use where the protective device is a semi-enclosed fuse).
15
10
Guide to the Wiring Regulations
Figure C 4.3 Reduction formulae for circuits not fully loaded
Applying the table to the last example Ib 10 = = 0.5 In 20 Cg is 0.5 and Figure C 4.3, the reduction factor that can be used with Equation 2 is approximately 0.58. This would give a cable It It ≥
In 20 × 0.58 ≥ 23.2 amps × Figure C 4.3 factor ≥ Ca Cg 0.5
You can see the speed of using Figure C4.3 and the result is very close to the longer calculation above.
10
16
Appendices
10.3.6 Check size for volt drop
Using the simple volt drop calculation for 2.5 mm2 cable of length 60 m with a load Ib of 10A, from Table 4E1B (mV/A/m) is 16mV/A/m Voltage drop =
(mV/A/m) × L × Ib 15 × 40 × 10 = = 6 volts 1000 1000
The suggested 3% limit, in light of other values, of 230 V is 6.9 V, so this voltage drop may be acceptable. 10.3.7 Check for disconnection times
To check disconnection times we need to confirm that:
Zs ≤ Z41.4 From Table 41.3 of BS 7671: 2008 Z41 = 2.3 ohms
Zs = Ze + L (r1 + r2) Where:
Ze is the impedance in ohms of the source r1 is the resistance in ohms per metre of the line conductor r2 is the resistance in ohms per metre of the protective conductor L is the length of the cable in metres From Table 4.2 of this book (Appendix 4), for 2.5 mm2 line and protective conductor
17
10
Guide to the Wiring Regulations
r1 + r2 at 20°C is 14.82 mΩ/m. Hence Zs = Ze + L (r1 + r2) = 0.4 +
14.82 × 40 = 0.99 ohms 1000
Correcting for conductor temperature of 70°C (see Table 4.6, Appendix 4 of this book), correction factor = 1.197 Thus the ELI will be 1.2 ohms which is less than that required by Chapter 41. 10.3.8 Check for short circuit withstand
Not necessary no reduced area protective conductors used.
10
18
Appendices
11
Appendix 11 – Impedances of conduits and trunking Table 11.1 Impedance of steel conduit at 20°C Heavy Gauge Typical impedance (Note 3) Nominal conduit size (mm)
Resistance r (Note 1) (mΩ/m)
Reactance x (Note 1) (mΩ/m)
16
3.3
3.3
20
2.4
2.4
25
1.6
1.6
32
1.4
1.4
Light gauge Typical impedance (Note 3) Nominal conduit size (mm)
Resistance r (Note 1) (mΩ/m)
Reactance x (Note 1) (mΩ/m)
16
4.5
4.7
20
3.7
3.7
25
2.1
2.1
32
1.5
1.5
Notes: 1 Typical values are taken at fault currents greater than 100A. When If is less than 100A, the tabulated impedances should be doubled. 2 When touch voltages on the conduit are being determined the product of current and resistance (r) gives a good approximation. 3 The above values are at 20°C but may be assumed to be independent of temperature and are used for design and verification.
19
11
Guide to the Wiring Regulations Table 11.2 Impedance of steel trunking to BS 4678 (Note 2) Typical impedance at 20°C Size (mm x mm)
Resistance r (mΩ/m)
Reactance x (mΩ/m)
50 x 37
2.96
2.96
50 x 50
2.44
2.44
75 x 50
1.75
1.75
75 x 75
1.37
1.37
100 x 50
1.52
1.52
100 x 75
1.21
1.21
100 x 100
0.87
0.87
150 x 50
1.05
1.05
150 x 75
0.87
0.87
150 x 100
0.81
0.81
150 x 150
0.52
0.52
Notes: 1 When determining touch voltages on the trunking, the product of current and resistance (r) gives a good approximation. 2 The above values may be assumed to be independent of temperature and are used for design and verification.
Table 11.3 Impedance of steel cable under floor trunking to BS 4678 Part 2 (Note 2) Typical impedance at 20°C Size (mm x mm)
Resistance r (mΩ/m)
Reactance x (mΩ/m)
75 x 25
1.28
1.28
75 x 37.5
1.16
1.16
100 x 25
1.08
1.08
100 x 37.5
0.99
0.99
150 x 25
0.74
0.74
150 x 37.5
0.69
0.69
225 x 25
0.52
0.52
225 x 37.5
0.49
0.49
Notes: 1 When determining touch voltages on the ducting, the product of current and resistance (r) gives a good approximation. 2 The above values are at 20°C, but may be assumed to be independent of temperature and are used for design and verification.
11
20
Appendices
12 12.1
Appendix 12 – Earth Electrodes And Earth Electrode Testing Introduction This appendix provides guidance and background information an earth electrode testing and some limited information on earth electrode design and improvement. It is not intended to cover the design of large complex earth systems, soil resistivity tests or test methods such as the clamp-voltage earth testers (e.g. the ‘attached rod’ and similar methods). More information on these subjects can be found in BS 7430 (for electrode design, earth design, soil resistivity testing) and various manufacturers for various testing instruments using clamps. This appendix has been based on information kindly provided by Megger.
12.2
Earth resistance Broadly speaking, ‘earth resistance’ is the resistance of soil to the passage of electric current. Actually, the earth is a relatively poor conductor of electricity compared to normal conductors like copper wire. But, if the area of a path for current is large enough, resistance can be quite low and the earth can be a good conductor. It is the earth’s abundance and availability that make it an indispensable component of a properly functioning electrical system. Earth resistance is measured in two ways for two important fields of use: 1. Determining effectiveness of ‘ground’ grids and connections that are used with electrical systems to protect personnel and equipment. 2. Prospecting for good (low resistance) ‘ground’ locations, or obtaining measured resistance values that can give specific information about what lies some distance below the earth’s surface (such as depth to bed rock).
12.3
Nature of an earth electrode Resistance to current through an earth electrode actually has three components:
•• •
Resistance of the electrode itself and connections to it. Contact resistance between the electrode and the soil adjacent to it. Resistance of the surrounding earth.
21
12
Guide to the Wiring Regulations
Electrode Resistance Rods, pipes, masses of metal, structures, and other devices are commonly used for earth connections. These are usually of sufficient size or cross section that their resistance is a negligible part of the total resistance. Electrode-earth contact resistance This is much less than you might think. If the electrode is free from paint or grease, and the earth is packed firmly, contact resistance is negligible. Rust on an iron electrode has little or no effect; the iron oxide is readily soaked with water and has less resistance than most soils. But if an iron pipe has rusted through, the part below the break is not effective as a part of the earth electrode.
Figure 12.1 Interface of earth and electrode
Resistance of surrounding earth An electrode driven into earth of uniform resistivity radiates current in all directions. Think of the electrode as being surrounded by shells of earth, all of equal thickness (see Figure 12.1). The earth shell nearest the electrode naturally has the smallest surface area and so offers the greatest resistance. The next earth shell is somewhat larger in area and offers less resistance. Finally, a distance from the electrode will be reached where inclusion of additional earth shells does not add significantly to the resistance of the earth surrounding the electrode.
12
22
Appendices
12.4
Basic test method for earth resistance The resistance to earth of any system of electrodes theoretically can be calculated from formulas based upon the general resistance formula: R=
Ď L A
where Ď is the resistivity of the earth in ohm-cm L is the length of the conducting path A is the cross-sectional area of the path The theory behind resistance measurement gets quite involved but is simplified by assuming that the earthâ&#x20AC;&#x2122;s resistivity is uniform throughout the entire soil volume under consideration. The earth tester generates an ac signal, which is fed into the system under test. The instrument then checks the status of the circuits for good connection and noise. If either of these variables is out of specification then the operator is informed. Having checked that the conditions for test are met, the instrument automatically steps through its measurement ranges to find the optimum signal to apply. Measuring the current flowing and the voltage generated the instrument calculates and displays the system or electrode resistance. There are three basic test methods as noted below. The first two are shown schematically in Figures 12.2 and 12.3. 1. Fall of potential method, or three-terminal test. 2. Dead earth method (two-point test).
12.5
Fall of potential method 12.5.1 Introduction and method This three-terminal test is the method that can be carried out with three or four terminal earth testers. Although four terminals are necessary for resistivity measurements, the use of either three of four terminals is largely optional for testing the resistance of an installed electrode. The use of three terminals is more convenient because it requires only one lead to be connected.
23
12
Guide to the Wiring Regulations
Figure 12.2 Fall of potential method
With a three-terminal instrument, connect X to the earth electrode. With a four-terminal tester, P1 and C1 terminals on the instrument are ‘jumpered’ and connected to the earth electrode under test. The driven reference rod C should be placed as far from the earth electrode as practical; this distance may be limited by the length of extension wire available, or the geography of the surroundings. Leads should be separated and ‘snaked’, not run close and parallel to each other, to eliminate mutual inductance. Potentialreference rod P is then driven in at a number of points roughly on a straight line between the earth electrode and C. 12.5.2 Simplified analysis for fall-of-potential test This reading with P at 50% of the distance from the earth electrode to C is noted as R1. Reference probe P is then moved to a location 40% of the distance to C. The reading at this point is noted as R2. A third reading, R3, is made with P at a 60% distance. The average of R1, R2 and R3 is calculated as RA. You determine the maximum deviation from the average by finding the greatest difference between individual readings and the average. If 1.2 times this percentage is less than your desired test accuracy, RA can be used as the test result. An example of this technique is as follows: R1 = 58 Ω, R2 = 55 Ω, R3 = 59 Ω RA = 58 + 55 + 59 = 57.3 Ω
12
24
Appendices
RA – R2 = 57.3 – 55 = 4.0% 4.0% × 1.2 = 4.8% If your desired accuracy was 5%, 57.3 Ω (RA) could be used as the result. This is usually more than accurate for most applications. If the result is not within the required accuracy, probe C has to be placed farther away and the tests repeated. There are many variations on the fall of potential method. For example, resistance readings are logged for each of the points. A curve of resistance vs. distance is then drawn. Correct earth resistance is read from the curve for the distance that is about 62% of the total distance from the earth electrode to C. The detail of further analysis of these methods is outside the scope of this book. 12.5.3 Lazy spikes The problem with three or four electrode methods is often the ability to drive test electrodes. The latest designs of digital earth testers can operate with very high temporary spike resistances and still give reliable and accurate results. Because the current and voltage are measured separately, it enables electrode measurements to be carried out with test spike resistances up to 400 kΩ. However, in urban situations, tests can be carried out using street furniture such as sign posts, metal fences and bollards. Where this is not possible, results have been obtained by laying the temporary electrodes on a wet patch of concrete. Coiled metal chains or metallized ground mats, with water poured over them, make an even better electrode because they conform more intimately to the earth’s surface than does a rigid spike. This technique has led to measured values of ‘spike’ of less than 10 kΩ, well inside the maximum value that will cause an error to the reading. With modern instruments, any problem with the temporary spikes will usually be indicated on the display to show that a reading may not be valid. A more suitable position for the spike may have to be used such as along the gap between paving stones, a crack in concrete, or in a nearby puddle. As long as warning indicators do not appear, sufficient contact has been made and a reliable test may be performed.
12.6
Dead earth method When using a four-terminal instrument, P1 and C1 terminals connect to the earth electrode under test; P2 and C2 terminals connect to an all-metallic metal system (e.g. a water pipe system). The water system could be any suitable metal structure
25
12
Guide to the Wiring Regulations
or similar.With a three-terminal instrument, connect X to the earth electrode, P and C to the pipe system, see Figure 12.3. If the water system is extensive (covering a large area), its resistance should be low and is usually much less than one ohm. You can then take the instrument reading as being the resistance of the electrode under test.
Figure 12.3 Dead earth (two-electrode) method
The dead earth method is the simplest way to make an earth resistance test. With this method, resistance of two electrodes in series is measured (the driven rod and the water system). It is, however important to note the limitations to this test method as follows:
â&#x20AC;˘ â&#x20AC;˘â&#x20AC;˘
The dead earth metal (e.g. water pipe) system must be extensive enough to have a negligible resistance The dead earth metal (e.g. water pipe) system must be metallic throughout The earth electrode under test must be far enough away from the dead earth (e.g. water pipe) system to be outside its sphere of influence.
In some locations, your earth electrode may be so close to the dead earth system (e.g. water pipe system) that you cannot separate the two by the required distance for measurement by the two-terminal method. Under these circumstances, you can connect to the water pipe system and obtain a suitable earth electrode.
12
26
Appendices
12.7
How to improve earth resistance When you find that your earth electrode resistance is not low enough, there are several ways you can improve it as follows
•• •
Lengthen the earth electrode in the earth. Use multiple rods. Treat the soil.
12.7.1 Effect of rod depth As you might suspect, driving a longer rod deeper into the earth, materially decreases its resistance. In general, doubling the rod length reduces resistance by about 40%. The curve of Figure 12.4 shows this effect.
Figure 12.4 Effect of vertical depth on resistance to earth
27
12
Guide to the Wiring Regulations
The subject of stability of single, vertical earth electrodes often causes confusion. The depth of a vertical rod is the decisive factor for stability as the effects of drying out or freezing effect the upper part of the rod most significantly. Therefore a 3 m rod with installed resistance of say 300 ohms will be more stable than a 1.2 m rod with resistance of say 100 ohms. 12.7.2 Use of multiple rods Two well-spaced rods driven into the earth provide parallel paths. They are, in effect, two resistances in parallel. The rule for two resistances in parallel does not apply exactly; that is, the resultant resistance is not one-half the individual rod resistances (assuming they are of the same size and depth). Actually, the reduction for two equal resistance rods is about 40%. If three rods are used, the reduction is 60%; if four, 66% as shown in Figure 12.5.
Figure 12.5 Effect of rod spacing on overall resistance
When you use multiple rods, they must be spaced further apart than the length of their immersion.
12
28
Appendices
12.7.3 Treatment of the soil Chemical treatment of soil is a good way to improve earth electrode resistance when you cannot drive deeper ground rods because of hard underlying rock, for example. It is beyond the scope of this book to recommend the best treatment chemicals for all situations. One popular approach is to backfill around the electrode with a specialized conductive concrete. A number of these products, like bentonite, are available on the market. This subject does become specialist and it is worth discussing treatment with a specialist earthing design or installation organisation.
29
12
Guide to the Wiring Regulations
13 13.1
Appendix 13 – Notes on ‘out of reach’ and ‘obstacles’ Introduction In the restructured Chapter 41 of BS 7671: 2008, the methods of protection against electric shock (other than automatic disconnection) that are not commonly used are shunted towards the rear of the Chapter. This appendix provides guidance on these methods including: Out of reach, obstacles, and non-conducting locations, earth free local equipotential bonding and electrical separation.
13.2
Out of reach or providing obstacles The method is a protective measure for basic protection only and can only be used where skilled or instructed persons are present. This is important as some feel that as utilities use overhead lines then placing out of reach can be used in areas accessible to lay persons. This is not true. The measures are basic protection only and fault protection requires separate consideration. The regulations themselves do not require much detailed consideration, the basic principles are:
••
Obstacles shall prevent unintentional contact with live parts or Live parts shall be placed out of arms reach
Arms reach is defined but it is quite obvious and a diagram is not reproduced – if you are working to limits that mean placing conductors at arms reach a study of Chapter 41 section 417 will be required.
13.3
Non-conducting location This method is quite specialist and usually involves creating an isolated area or room with the fabric isolated from earth (being the local general mass of earth and the system earth). The protective measure is perhaps more applicable to specialist testing labs and similar. As well as isolating the room and constructional fabric from earth,
13
30
Appendices
equipment exposed-conductive-parts must effectively be insulated, as persons must not be able to contact any two of such parts.
1.4 Earth free local equipotential bonding Again this is a specialist application only to be used where other methods will not be suitable. For example, a medical location may require the use of this application and although the medical equipment used is outside the scope of BS 7671, the installation may be specified to be earth free local equipotential bonding. It can be seen that this method is arguably easier to achieve than a non-conducting location and hence its more frequent use.
13.5
Electrical separation and electrical separation of more than one item of equipment This method is perhaps a bit more common in application. It involves the use of an isolation transformer which breaks the touch current earth return path to the mains supply. The method may be used to supply more than one item of equipment (e.g. in labs or schools) but most special locations restrict the application to supplying just a single item of equipment in the special location. The requirements are summarised in Table 13.1. Table 13.1 Requirements for electrical separation Requirement
Regulation
Separated circuit voltage shall not exceed 500 V
413.3.2
Live parts or separated shall not be connected to Earth or to PE conductor
413.3.3
Flexible cables to be visible throughout their length
413.3.4
Separated wiring systems recommended for supply and separated circuits
413.3.5
Exposed conductive parts of separated circuit equipment shall not be connected to Earth or PE conductors
413.3.6
For more than one item supplied by separation, warning notice instructing not to bond or connect to earth shall be affixed (see 514.13.2)
418.3
For more than one item supplied by separation, exposed conductive parts shall be connected together using insulated cable.
418.3.4
For more than one item supplied by separation, maximum circuit length is 500 m
418.3.8
31
13
Guide to the Wiring Regulations
14 14.1
Appendix 14 – ‘Occasional’ tests that may be required Introduction To supplement the tests detailed in Chapter F of the book the following tests are outlined in this appendix:
•• •• 14.2
SELV and PELV tests Site applied insulation Electrical separation tests Non-conducting locations tests
SELV and PELV tests Where SELV is used and it is the method of protection against electric shock, some additional testing is necessary. These tests are not required where SELV is used and equipment complies with ‘230 volt’ rules i.e. full insulation and the other basic rules. These tests shall also be used for PELV systems. The tests are as follows: For SELV and PELV
•
Test between the ELV live conductors and any other live conductors in the same containment at 500 V
And additionally for SELV
•
Test for insulation at 250 V between live parts and primary Earth (connected to the PE conductor)
Minimum insulation shall be 1 MΩ
14.3
Site Applied Insulation Where insulation has been applied on-site to equipment in accordance with regulation 421.2.1.3, an ‘enhanced’ insulation test should be carried out. This does not apply to assemblies of equipment-manufactured off-site but constructed on-site, even where these are insulation kits used as part of this process. The test is for un-insulated conductive parts that have been used and insulated on-site by the installation designer or installer. The test procedure is carried out using higher voltage insulation tester, also commonly known as either a flash tester or high pot tester.
14
32
Appendices
It is best if the voltage and procedure for test is replicated from an appropriate British standard. Failing this tests should be carried out as follows (between live parts and live parts and equipment earth not connected to the system earthing):
•• •
test with installation 500 V insulation tester and if greater than 2 MΩ test at 1000 ac 50 Hz, increasing to test at 1500 V ac 50 Hz for 1 minute
No flashovers or breakdowns shall occur during this period. A earth leakage will be present depending upon the size and nature of the components. Generally this should be in the order of a few milliamps.
14.4
Electrical separation tests Where electrical separation is used as a protective measure, a test to confirm the separation is required as follows:
• • •
Test at 500 V between live parts of the separated circuit and earth connected to the system PE conductor if available and, Test at 500 V between live parts of the separated circuit and supply live conductors and, Test at 500 V between live parts of the separated circuit and live conductors of other circuits in a common enclosure.
In all cases, the insulation resistance for nominal voltage to earth circuits of 230 volts, shall not be less than 1 MΩ.
14.5
Non-conducting location tests Where a non-conducting location has been set up and constructed, the isolation must be checked by testing. This is listed in BS 7671: 2008 as ‘insulation resistance/ impedance of floors and walls’, see regulation 612.5.1. The test procedure for this construction must be carried out in at least three places and is as follows:
•• •
test with installation 500 V insulation tester and if greater than 1 MΩ, test at 1000 V ac 50 Hz, increasing to test at 2000 V ac 50 Hz for 1 minute.
The latter test shall not pass a leakage current of 1 mA.
33
14
Guide to the Wiring Regulations
15 15.1
Appendix 15 â&#x20AC;&#x201C; Notes on periodic inspecting and testing Introduction scope and statutory requirements After an electrical installation is constructed, commissioned and put into service it must be maintained to keep it in a safe condition. The statutory requirements for health and safety at work are covered by the Health and Safety at Work etc. Act 1974, and through this act the Electricity at Work Regulations 1989 (EWR) provides the basic statutory framework for electrical safety in the workplace (but they do not apply to domestic installations). The EWR are not voltage dependant and cover all electrical systems from battery operated torches to the national grid. There are some terms that are central to the understanding of these requirements, and for ease of reference they are listed below. Most are from the EWR, but some are supplemented by Part 2 of BS 7671: 2008 and are as follows: Duty holder A person on whom statutory or other duties are imposed by statutory regulations or other (usually contractual) requirements. (The duty holder may or may not be a â&#x20AC;&#x2DC;competent personâ&#x20AC;&#x2122;). Competent person A person who possesses sufficient technical knowledge and experience for the nature of the electrical work undertaken, and is able at all times to prevent danger, and where appropriate injury, to themselves and others. Danger Risk of injury. Injury Death or personal injury from electrical shock, electric burn, electrical explosion or arcing, or from fire or explosion initiated by electrical energy, where any such death or injury is associated with the generation, provision, transmission, transformation, rectification, conversion, conduction, distribution, control, storage, measurement or use of electrical energy. System An electrical system in which all the electrical equipment is, or may be, electrically connected to a common source of electrical energy, and includes such source and such equipment. (It includes all the electrical installations, switchgear, luminaires, equipment, accessories, fittings, appliances and controls etc.).
15
34
Appendices
Electrical equipment Any item for such purposes as generation, conversion, transmission, distribution or utilisation of electrical energy, such as machines, transformers, apparatus, measuring instruments, protective devices, wiring systems, accessories, appliances and luminaires. Regulation 4(2) of the Electricity at Work Regulations requires: ‘As may be necessary to prevent danger, all systems shall be maintained so as to prevent, so far as is reasonably practicable, such danger.’ Someone must be responsible for an electrical installation. For a domestic installation, this is the householder and for an electrical installation at a place of work, the responsible person is usually a nominated person (the duty holder). Often no one is specifically nominated, but someone must have control (e.g. the office manager or other manager who gets an electrical contractor in to do some work) and this person or these persons will assume the position, usually by default, and the law will presume that they are duty holders. It is for the installation duty holder to decide, by a risk assessment, as to what danger can arise and what maintenance is required to prevent danger. The statutory obligation to maintain at work arises only if danger would otherwise result, although there is the practical reason to maintain to keep a building in good condition. The quantity and frequency of statutory maintenance should be sufficient to prevent danger so far as is reasonably practicable. There is no statutory duty to maintain in a domestic environment, but insurers may not pay claims if they can show that an installation was not safe.
15.2
BS 7671: 2008 requirements On the electrical installation certificate of a new installation advice is given for the time period at which the installation should have its first periodic inspection and test. This is based on the considered advice from a number of parties, as identified in Chapter 34 of BS 7671: 2008 which states:
• •• •
An assessment is to be made of the frequency and quality of maintenance of the reasonable expectation of the installation The responsible person shall be consulted Periodic inspection and testing as well as maintenance and repairs shall be considered The assessment shall consider the effectiveness of the protective measures
35
15
Guide to the Wiring Regulations
15.3
Information and records Before any periodic inspection and testing work can be undertaken (or even priced), the scope of the installation and the required work must be identified. There should be several existing sources of information about the electrical installation, but if necessary the inspector must survey the building and identify the installation arrangement and circuits before any meaningful inspection and testing work can be undertaken. 15.3.1 Operation and maintenance documents When commissioned and set to work operation and maintenance documentation, including record drawings and an electrical installation certificate is issued for a new installation. BS 7671: 2008 lists the information that should be available in section 514 and these amount to circuit diagrams. For most commercial installations a single line diagram is usually essential. Statutory legislation including the Construction Design and Management Regulations 1994 (revised 2007) and the Building Regulations (England and Wales) require adequate health and safety, operation and maintenance, and record drawings documents be provided by the installer. In essence the information that should be available should allow the safe and proper operation and maintenance of the building and its services. These health and safety requirements do not apply to domestic installations, which are usually a lot simpler, but the Building Regulations and NHBC guidance still require adequate records, and the requirements of section 514 of BS 7671: 2008 still apply. The new Home Information Packs may also contain a Home Condition Report as an optional document, which will give details about the physical condition of a dwelling. At the time or writing, it was not clear if this report would contain electrical information, but if it does sellers, buyers and lenders will be able to rely on it as an accurate document. An electrical installation certificate must accompany each new work in a commercial building and if it is â&#x20AC;&#x2DC;notifiableâ&#x20AC;&#x2122; (see 15.3.2 below), the required CDM Health & Safety file, as well as general Operation & Maintenance and record information. The CDM H&S file must be retained by the building owner, for the life of the building, and thus this provides a valuable source of information for building modifications and inspections. Unfortunately, this information is not always available when required!
15
36
Appendices
15.3.2 Health and safety files The CDM Health and Safety Files are the means by which health and safety information is recorded and kept for future use at the end of a construction project. The Construction (Design & Management) Regulations 1994 and 2007 require that the file includes adequate information about any aspect of the structure or materials used which might affect the health or safety of anyone carrying out construction, maintenance, cleaning or demolition work or of anyone who may be affected by such work. The file will contain information necessary for future construction, maintenance, refurbishment or demolition to be carried out safely, and is retained by the client or any future owner of the property. (Where a client gets non-notifiable work done, and a health and safety file already exists for the premises, it should be updated if necessary). The file should be a useful and valuable document for the client and any persons with a professional interest in the building, and since 1994 should provide the required information on the building. Work undertaken by a local authority or a domestic householder is exempt from the CDM Regulations. For any notifiable project under the CDM Regulations (defined as projects where the production stage on site will exceed 30 days or 500 person days) a health and safety file must be prepared at the completion of the works and retained by the owner of the works. When the project is finished and the health and safety file has been handed over by the planning supervisor, the client should keep it available for those who need to use it. Usually this will include maintenance contractors, the planning supervisor and contractors preparing or carrying out future construction work. Its purpose is to provide the end user with information about the risks that have to be managed during maintenance, repair, renovation or demolition. This file must be made available to anyone doing any future work on the structure. Guidance to the regulations recommends that the file include:
• •• ••
‘record’ or ‘as built’ drawings and plans used and produced throughout the construction process; the design criteria; general details of the construction methods and materials used; details of the equipment and maintenance facilities within the structure; maintenance procedures and requirements for the structure;
37
15
Guide to the Wiring Regulations
â&#x20AC;˘ â&#x20AC;˘
manuals produced by specialist contractors and suppliers which outline operating and maintenance procedures and schedules for plant and equipment installed as part of the structure; details of the location and nature of utilities and services, including emergency and fire-fighting systems.
Ideally, the health and safety file should be kept available for inspection on the premises to which it relates. It may be useful to store the health and safety file so that it is in two parts. One part will be more relevant for day-to-day use, e.g. operational and maintenance manuals. The other part will be for longer-term use, e.g. drawings that will only be required when major alteration work is carried out. The health and safety file could be stored electronically but it should be easily accessible in whatever form it is stored, and for a big project the documentation could run to many volumes but the system must be searchable. Over the course of time an installation will be modified, extended or perhaps parts replaced due to changes in use of parts of the building. O&M documentation and drawings must be kept up to date or supplemented as the building changes over time, or it will be useless.
15.4
Competence of personnel The individual(s) carrying out the electrical inspection and testing must be competent and experienced in electrical installation work, and especially in the type of installation being inspected and tested. The subject of competence is complicated but it is important to realise that periodic inspecting and testing is an area often underestimated in terms of an individualâ&#x20AC;&#x2122;s competence. Although outside the scope of this book, the subject of quoting for and the forming of a contract for an inspection and test can be quite involved. For simple installations, a City and Guilds 2392 qualification is usually accepted as the required technical standard for electrical operatives carrying out inspection and testing work to the requirements of BS 7671: 2008. Often for larger commercial installations, electrical technicians or electrical engineers should be employed. It should perhaps be remembered that the competence should be at a level where the quantity of tests and samples as in Tables 15.2 and 15.3 to be applied can be routinely considered by the individual.
15
38
Appendices
15.5
Basic principles of periodic inspecting and testing The following principles should be noted relevant to a BS 7671 periodic inspecting and test:
•• •
The periodic inspection and test forms a condition report for the installation The periodic inspection and test is not intended to cover 100% (indeed this would almost always be impractical if not impossible). Thus sampling will be required the nature of which will need to be set by the person carrying out the periodic inspection and test. The inspection and test method should follow the principles highlighted in the latest Edition of BS 7671. However, many installations will not have been installed to this latest standard. This will generally not be a problem as it was safe at the time of installation. Comments or recommendations on any ‘upgrades’ can be provided but these comments should be separated from any issues that make the installation unsafe (often, this will not be due to an issue with a previous Edition of BS 7671). This is an example where the experience of the individual(s) is important.
Generally, inspection and testing is carried out as a prerequisite to any maintenance to establish the condition of electrical systems. There is no specific required frequency for periodic inspection and testing, and it depends solely on the age, use and condition of the system, and to assess its suitability for continued use. Guidance on inspection periods is given in Table 15.1 but it must be understood that the periods proposed are suggested maximum periods, and each installation will be different and must be considered individually on its merits. Table 15.1 Recommended Initial Inspection Frequencies of Electrical Installation Type of installation
Maximum period between inspections and testing as necessary
Domestic
Change of occupancy/10 years
All Commercial i.e. shops offices, hospitals and labs, etc.
Change of occupancy/5 years
Industrial
3 years
Places subject to entertainment licence
1 year
1,2
Public swimming pools, caravan parks
1 year
1,2
Notes: 1 2
Reference (see notes below)
1
See also Electricity at work Regulations 1989 This is normally a requirement of local licensing organisations
39
15
Guide to the Wiring Regulations
If the duty holder is continuously aware of the condition of the system there is no need for any formal inspection and testing regime. The frequency of periodic inspection and testing of an installation must be determined having regard to the type of system, its use and operation, the frequency and quality of maintenance and the external influences to which it is subjected. Not all parts of the system may require the same frequency of inspection and testing. BS 7671: 2008 Chapter 62 gives guidance on the requirements for periodic inspection and testing of fixed electrical installations. It advises that periodic inspection testing of an electrical installation should be carried out to determine, so far as is reasonably practicable, whether the installation is in a satisfactory condition for continued service. The statement so far as is reasonably practicable must be clarified, and attempts to bring a balance against the time, trouble, cost and physical difficulty of doing something and the risk to safety of not doing it. If these resources are so disproportionate to the risk that it would be unreasonable to expect any employer to have to incur them to prevent it, the employer is not obliged to do so unless there is a specific requirement that he does. Some EWR requirements are â&#x20AC;&#x2DC;absoluteâ&#x20AC;&#x2122; and must be complied with regardless of cost (e.g. providing an earth connection), but some can be compared to cost and maintenance is an example of where costs must be considered. A duty holder should identify all the circumstances in which persons could be at risk whilst at work, and all the circumstances in which anyone else could be at risk as a result of anything done in his work, and determine the level of resource that is needed to manage each risk effectively taking account of the level of risk. Only by directing and applying a level and effectiveness of resource that is commensurate with the risk can the employer perform his general duties so far as is reasonably practicable. The greater the risk, the more likely it is that it is reasonable to go to very substantial expense, trouble and invention to reduce it. But if the consequences and extent of a risk are small, insistence on great expense would not be considered reasonable. It is important to remember that the judgment is an objective one and the size or financial positions of the employer are immaterial.
Inspection of an installation and electrical equipment comprising careful scrutiny should be carried out with dismantling as required, together with appropriate tests as discussed in the other sections. It must be realised however that to disassemble or disconnect something already in service for
15
40
Appendices
physical inspection or testing always carries with it the risk of introducing new faults to the equipment during this work. The scope of the periodic inspection and test, should be set by a competent person. This is usually the duty holder, although he can ‘sub-contract’ this duty. The scope should take into account availability of records and the use, condition and nature of the installation. This inspection and testing should provide, so far as is reasonably practicable, for:
• • • • 15.6
the safety of persons and livestock against the effects of electric shock and burns protecting against damage to property by fire and heat arising from an installation defect, and confirming that the installation is not damaged or deteriorated so as to impair safety, and the identification of installation defects and non-compliance with the requirements of the Regulation which may give rise to danger.
Establishing sample and scope of inspection and test Sampling of both the visual inspecting and testing facets of the inspection and test is key and this is where experience counts. Inspection and testing is a complex process and time consuming and costly to do fully, and some proposals are always made to reduce the work, but one must ensure that in consequence the installation safety is not reduced. The person inspecting and testing the installation will provide a report on the condition of the installation and its safety and suitability for continued use. The installation owner and users are usually not technical, and will rely on the conclusions of the report so it is vital that the inspection and testing is properly carried out. Samples should be selected to be representative of installation and will thus be dependent upon records. The sample size may need regular adjustment throughout the process. The samples must be representative and chosen by experience, judging each installation on its merits. It can be argued that large well maintained buildings (e.g. offices etc.) would have the scope for reduced sample sizes over other less wellmaintained buildings. Samples tables are provided for in this appendix for visual inspections as well as physical tests but the following summary applies:
41
15
Guide to the Wiring Regulations
• ••
Sampling criteria depends on size, age, complexity, condition of records and frequency of routine maintenance. Small domestic installations will tend to a fuller sampling approach Large installations will have to implement a low sample approach
Generally, samples of less than 10% are not recommended. For very large installations where it is established that the installation is consistent by say, inspection of records or similar, the sample size may be reduced below 10%.
15.7
The visual inspection Often, the value of the visual inspection facet of the inspection and test is undervalued but it usually depicts a much better indication about the condition of an installation than the testing facet. As discussed previously, the inspector must be very experienced in working on the type of installation being inspected. Precautions must be taken to ensure that inspection and testing does not cause danger to persons or livestock and does not cause damage to property and system even if the circuit or equipment is defective. During the inspection any damage, deterioration, defects, dangerous conditions which may give rise to danger, and any non-compliance with the requirements of the current edition of the IEE Regulations, together with any limitations of the inspection shall be recorded. The inspector must utilise all of the senses (sight, touch, smell etc.) to form a judgment of the condition of various parts of the installation, and must make an opinion of the condition, use and suitability for future safe use of the installation including:
•• •• •• •• •
Safety Wear and tear Corrosion Damage Excessive loading (overloading) Age of equipment External influences Suitability Heat, temperature and burning
The sampling provided in Table 15.2 is recommended but needs to be set by a competent person
15
42
Appendices Table 15.2 Range samples for visual inspection Visual inpection
Suggested minimum sample (see note 1)
Check for single line diagram
100%, i.e. it/they must be present
Signs of overheating, aging, check tightness.
Main switchgear outside inspection
100%
Signs of overheating, aging, check tightness.
Internal sections and cable terminations
100%
Signs of overheating, aging, check tightness.
Internal inspection of circuit breaker connections and control sections (large switchgear)
100% small installations 10% large installations
Signs of overheating, aging, check tightness.
Sub-main swtichgear
Ideally 100% of connections reducing to 10% of connections. This may need reducing for very large installations.
Signs of overheating, aging, check tightness.
Final circuit distribution boards
Ideally 100% of connections reducing to 10% of connections. This may need reducing for very large installations.
Signs of overheating, aging, check tightness.
Final circuits joints in cables
Sample circuits of 10%
Signs of overheating, aging, check tightness.
Final circuits accessories
Samples on above
Damage, signs of overheating
Main equipotential bonding
100%
Presence
Typical checks
Note 1. Although generally samples of 10% are not recommended, for very large installations where it is established that the installation is consistent by say inspection of records, the sample size may be reduced.
Overheating is a common problem, whether caused by overloading, poor ventilation or whatever, and an inspection must pay particular attention to signs of overheating and identify their possible causes. Many installations are now surveyed with infrared thermographic cameras, which can provide a useful non invasive aid to inspection, especially in installations that cannot be easily switched off (e.g. computer facilities), but care must be taken to understand the results obtained. Not all electrical equipment is thermally â&#x20AC;&#x2DC;transparentâ&#x20AC;&#x2122;, and if thermographic pictures are used over time to look at possible changes in an installation one must ensure that pictures are taken with the same loads, environment and circumstances.
43
15
Guide to the Wiring Regulations
Depending on the type of building, especially if it has areas in it accessible to the general public (school, hospital etc.), it may be necessary (or at least wise) to carry out regular inspections of the accessible electrical equipment and accessories outside the formal periodic inspection and testing programme.
15.8
The testing Testing should be considered to supplement the visual inspection part of the periodic inspection and test process. This section provides an overview of samples and general notes on testing. The test methods detailed in Chapter F of the book can all generally be used with necessary modifications. This section provides an overview of samples and general notes on testing. 15.8.1 Sample sizes Testing in a periodic inspection and test programme is different from that at the commissioning of a new installation as one may well be working in an occupied building and it may not be possible to isolate all the electrical systems, or carry out all the tests (e.g. there may be local flammable products stored that cannot be moved). Any limitations on the testing must be clearly identified in the report. Although generally samples of 10% are not recommended, for very large installations where it is established that the installation is consistent by say, inspection of records or from the visual inspection, the sample size may be reduced. 15.8.2 Preparation Precautions must be taken to ensure that inspection and testing does not cause danger to persons or livestock and does not cause damage to property and system even if the circuit or equipment is defective. Safety is particularly important â&#x20AC;&#x201C; especially safety of the public in an occupied building. Switchrooms, risers, distribution boards etc. are normally kept locked, and when work access is required safety barriers and warning signs must be put up at the workplace to keep people away from electrical equipment.
15
44
Appendices Table 15.3 Testing to be carried out where practicable on existing installations Test (note 1)
Recommendations
Earth fault loop impedance
At the following positions: • Origin of the installation • Distribution boards (may be sampled see note 2) • Accessible socket-outlets and extremity of radial circuits (may be sampled see note 1)
Protective conductors continuity
•
Bonding conductors continuity
• Main bonding conductors • All necessary supplementary bonding conductors (may be sampled see note 2)
Insulation resistance
If tests are to be made: • Between live conductors and Earth at all final distribution boards (may be sampled see note 2)
Earth electrode resistance
Test each earth rod or group of rods separately, with the test links removed, and with the installation isolated from the supply source
Functional tests RCDs Circuit-breakers, isolators and switching devices
Tests as required by Regulation 713–13–01, followed by operation of the functional test button (may be sampled see note 2) Manual operation to prove that the devices disconnect the supply (may be sampled see note 2)
Polarity (note 4)
At the following positions: • Origin of the installation • Distribution boards • Accessible socket-outlets • Extremity of radial circuits
Ring circuit continuity (note 4)
Where there are proper records of previous tests, this test may not be necessary. This test should be carried out where inspection/documentation indicate that there may have been changes made to the ring final circuit (may be sampled see note 2)
Accessible exposed-conductive-parts of current-using equipment and accessories (requires sampling see notes 2 & 3)
Notes: 1 The person carrying out the testing is required to decide which of the above tests are appropriate by using their experience and knowledge of the installation being inspected and tested and by consulting any available records. 2 Where sampling is applied, the percentage used is at the discretion of the tester, see section 15.6. Generally samples of less than 10% are not recommended. For very large installations where it is established that the installation is consistent by say, inspection of records or from the visual inspection, the sample size may be reduced below 10%. 3 The earth fault loop impedance test may be used to confirm the continuity of protective conductors. 4 These tests will often not be required if appropriate records for the existing installation are confirmed.
Generally, live working is not safe and is not allowed unless it can be justified by unusual circumstances (see the EAWR). Some testing must be done live, (e.g. earth loop impedance) but that does not mean the tester or occupiers should be exposed to any risk, and work must be properly planned to ensure that equipment can be isolated so that there is no access to live parts.
45
15
Guide to the Wiring Regulations
15.8.3 Tests The test methods detailed in Chapter F of this book can all be generally applied to a periodic test. The individual performing the tests must be aware of the results expected to be obtained and able to interpret them and decide on their adequacy. Knowledge and experience is required in applying the tests and interpreting the results. Insulation resistance in an old installation is unlikely to equal the high values of a new installation, but it must still be adequate. It is not practice to carry out this test between live and testing between neutral and earth is nearly always impractical. With some electronic equipment in circuits it may not be possible to carry out a full insulation resistance test as the equipment may be damaged and tests will often need to be carried out at 250 V and noted on the test paperwork. If the duty holder is continuously aware of the condition of the system there is perhaps no need for any formal periodic inspection and testing regime. In the case of a system under effective supervision in normal use, BS 7671: 2008 allows that periodic inspection and testing may be replaced by an adequate regime of continuous monitoring and maintenance of the installation by competent skilled persons. Full records must be kept for the installation and all works to show that appropriate maintenance management procedures have been followed at all times. There is however no specific guidance as to what this requires, but the duty holder must be able to show that the installation complies at all times with the requirements of the EAWR. Some installations cannot easily be switched off, and so inspection and testing can be rather limited, and ways have been proposed to continuously monitor such installations to identify possible faults before they interfere with the operation of the installation. Infra-red thermography has already been mentioned, and it can prove very useful so long as the installation is designed to accommodate it (thermally transparent switchgear etc.), and the information gathered is properly understood. Another method gaining popularity is to continuously measure earth leakage current. This is generally very small but relatively stable, and it can be monitored at several points in an installation and any changes may signify impending equipment breakdown that can be attended to before it happens.
15
46
Appendices
15.9
Electrical equipment As discussed at the beginning of this appendix, electrical equipment is defined as any item for the generation, conversion, transmission, distribution or utilisation of electrical energy, and as such covers fixed wiring as well as appliances. The EWR cover safety requirements for all electrical systems and equipment used at work, regardless of voltage levels, and it must be understood that the requirements for periodic inspection and testing apply to the fixed installation only. The installation duty holder should be notified of the fact that the ‘clients’ equipment, for example portable and transportable equipment, is not included in a BS 7671 periodic report. This is quite clear for equipment supplied via a plug and socket outlet. However, for other equipment such items as luminaires, chillers, electric motors and boilers etc., the subject is not so clear. Whilst these all fall within the EAW requirements they do present a problem. It is recommended to visually inspect such equipment in the course of the periodic inspection and test process and to highlight any equipment that requires a fuller inspection. In similar fashion, sampling will need to be applied to this process. The IET Code of Practice for the In-service Inspection and Testing of Electrical Equipment gives guidance on the inspection and testing of electrical equipment.
15.10
Reports Following a periodic inspection and testing a Periodic Inspection Report, together with a schedule of inspections and a schedule of test result is to be produced by the person or company carrying out the inspection and testing works. A copy of the ECA Periodic Inspection Report, taken from BS 7671: 2008 is provided in Appendix 17. BS 7671: 2008 suggests that the report is to be ‘given to the person ordering the inspection’. This is rather literal, and realistically the report and schedules must be received by someone in authority (e.g. the duty holder) who is able to do something about any dangers or safety problems identified in the report. The schedules of inspection results and test results will record the result of the appropriate inspections and test carried out. Copies of reports and schedules and records of maintenance works including test results should preferably be kept throughout the working life of an electrical system, and this will enable the condition of the equipment and the effectiveness of maintenance policies to be monitored. Without effective monitoring duty holders cannot be certain that the requirement for maintenance has been complied with.
47
15
Guide to the Wiring Regulations
There is a section on the report ‘extent and limitations’ which identifies and describes the parts or areas of an installation covered by a report, and any limitations on the work carried out, e.g. lack of access to certain parts or unable to isolate some equipment for testing. The periodic report is to be completed by an experienced and competent person who was involved in the inspection and testing work, and in the report there is a space to indicate when it is advised that the next periodic inspection and test should be undertaken. This gives a continuity of advice from the guidance on the initial electrical installation certificate as to when inspection and testing of an installation should be undertaken. The most important part of the report is the observations and recommendations section, which identifies any dangers and remedial work required. The requirements are given a coding or categorisation from 1 to 4:
•• ••
Code 1 – Requires urgent attention Code 2 – Requires improvement Code 3 – Requires further investigation Code 4 – Does not comply with BS 7671: 2008
Only one code should be given to each observation. If more than one code could be applied, only the most serious recommendation should be given. Where an immediate danger is observed Code 1 must be used. Where one or more observations are given a Code 1 recommendation the overall assessment of the installation must be stated to be unsatisfactory. Code 3 indicates that the inspector was unable to reach a conclusion about a certain aspect of the installation, or that the observation was outside the agreed extent or limitations of the inspection, but has come to the inspector’s attention during the inspection and testing. Code 4 indicates items that have been identified as not complying with the requirements of BS 7671: 2008, but that the item is not of any danger. It is entirely a matter for the competent operative doing the inspection and testing to decide on the recommendation code to be given to any fault or observation. The operative’s own judgment as a competent person should not be influenced by his employer or the client or their requirements. The persons signing the report are responsible for its content.
15
48
Appendices
15.11
Repairs and maintenance Installations and equipment must be maintained for safety, long life and efficient performance, and regular inspection and testing and condition monitoring is a necessary part of such maintenance. BS 7671: 2008 is not really concerned with maintenance or energy efficient operation, but such things are now a part of everyday life. As noted above a periodic inspection and test may identify dangers and faults in an electrical installation and these must be repaired in a reasonable time. Any Code 1 items should be seen to immediately they are found, to minimise possible dangers, and if not it can be argued that an inspector could immediately disconnect the supply to that item due to the possible danger. The presence of any Code 2 items is also unacceptable and these should be attended to as soon as realistically possible. Code 3 items may require further work by the inspector and a way forward should be agreed. Code 4 items may not need any action as long as persons are aware of them, but they could be attended to when any new work is being carried out. Generally upon receipt of a report it is advisable to set a programme to ensure that all the Code 1, 2 and 3 items are resolved in an acceptable period, and to have the inspector return to check that they have been completed satisfactorily. Maintenance policies and provisions vary widely depending on the equipment or system, and outcomes required, and such details cannot be discussed here, but must be fully understood by the operational staff.
49
15
Guide to the Wiring Regulations
16
Appendix 16 â&#x20AC;&#x201C; Electrical Research Association Report (ERA) report on armoured cables with external CPCs The attached report was commissioned by the ECA and is copyright of the ERA. It can be used to assist readers assessing the merits of installing externally run CPCs with armoured cables.
16
50
ECA
Guide to the Wiring Regulations
Appendix 16
ERA Business Unit:
Engineering Consultancy Services
Report Title:
Use of External CPCs with Armoured Cables
Author(s):
M W Coates
Client:
Electrical Contractors Association
ERA Report Number:
2007-0334
ERA Project Number:
7M0288301
Report Version:
Final Report
Document Control:
Commercial-in-Confidence
ERA Report Checked by:
Approved by:
Mr B Knox Principal Engineer
Dr A Friday Head of Materials and Design May 07 Ref. R:\Projects (7 series)\7M - Materials Design & Consultancy\7M0288301 ECA\ECA Report V3.doc
PURPOSE OF DISTRIBUTION: This document is distributed to Electrical Contractors Association for the sole purpose of commercial and technical use. Rights to copy or distribute this document are only granted for the stated purpose. The document may not otherwise be used or distributed without the prior written permission of ERA Technology Limited.
ECA
©
Guide to the Wiring Regulations
Appendix 16
Copyright ERA Technology Limited 2007 All Rights Reserved No part of this document may be copied or otherwise reproduced without the prior written permission of ERA Technology Limited. If received electronically, recipient is permitted to make such copies as are necessary to: view the document on a computer system; comply with a reasonable corporate computer data protection and backup policy and produce one paper copy for personal use.
Distribution List ECA Project File Information Centre
(1) (1) (1)
DOCUMENT CONTROL Distribution of this document by the recipient(s) is authorised in accordance with the following commercial restrictive markings: Commercial-in-confidence : No distribution or disclosure outside of the recipient’s organisation is permitted without the prior written permission of ERA Technology Limited. Distributed-in-confidence : Distribution of the document shall be in accordance with the document distribution list and no further distribution or disclosure shall be allowed without the prior written permission of ERA Copied or otherwise reproduced with theTechnology prior permission in writing of ERA Technology Ltd. Such Limited. written permission must also be obtained before any part of this document is stored in an electronic system Recipient-in-confidence of whatever nature. : ERA Technology Limited distributes this document to the recipient on the condition that no further distribution or disclosure by the recipient shall be allowed. Where specified the document may only be used in accordance with the ‘Purpose of Distribution’ notice displayed on the cover page. For the purpose of these conditions, the recipient’s organisation shall not include parent or subsidiary organisations. Permission to disclose within recipient’s organisation does not extend to allowing access to the document via Internet, Intranet or other web-based computer systems. Commercial restrictive markings are as contained in page header blocks. If no restrictive markings are shown, the document may be distributed freely in whole, without alteration, subject to Copyright. ERA Technology Ltd Cleeve Road Leatherhead Surrey KT22 7SA UK Tel : +44 (0) 1372 367000 No part of this document may be photocopied or otherwise reproduced Fax: +44 (0) 1372 367099without the prior permission in writing of ERA Technology Ltd. Such written permission must also be obtained before any part of E-mail: info@era.co.uk
this document is stored in an electronic system of whatever nature. Read more about ERA Technology on our Internet page at: http://www.era.co.uk/
© ERA Technology Ltd
3 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Summary For some years it has become common practice to run separate circuit protective conductors, cpcs, in parallel with the armour of steel wire armoured low voltage cables. It is intended that these external cpcs would carry a proportion of the fault current and hence increase the fault current withstand of the earth return path. An external cpc will also reduce the total impedance of the circuit protective conductor, armour and external cpc in parallel. This report contains details of tests carried out on two sizes of armoured cable to measure the current sharing that is achieved between the armour and the external cpc. Prior to carrying out this test work it was thought that the proportion of any earth fault current carried by the external cpc would be less than that predicted from the ratio of the armour and cpc resistance. The test work has shown that this is not the case and that using the resistance ratio will give a reasonable estimate of the current carried by the external cpc. Comparison of the fault current withstand of the armour of cables to BS 5467, using the k values given in Chapter 54 of BS 7671, has shown that for all cables except the 120 mm² and 400 mm² 2-core cables the fault current withstand of the armour is greater than the fault current required to operate a BS 88 fuse within 5 seconds. Thus a supplementary external cpc is generally not required to increase the fault current withstand of an armoured cable. A supplementary external cpc would only be required if the earth fault loop impedance needed to be reduced to meet the values tabulated in Chapter 41 of BS 7671. This could be the case for a long cable run where protection against indirect contact was achieved by automatic disconnection of the supply and the use of a residual current device was not appropriate. Empirical equations have been derived for calculating the prospective fault current where an external cpc is installed in parallel with steel wire armour. Empirical equations have also been derived for calculating the current sharing between the armour and the external cpc. Calculation of the current sharing between the armour and an external cpc has shown that if a small external cpc is run in parallel with the armour of a large cable there is a risk that the fault current withstand of the external cpc will be exceeded. Because of this it is recommended that the cross-sectional area of the external cpc should not be less than a quarter of that of the line conductors.
© ERA Technology Ltd
4 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
This page is intentionally left blank
Š ERA Technology Ltd
5 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Contents Page No.
1.
Introduction
7
2.
Test work
7
2.1
Methodology
7
2.2
Test arrangement
7
2.3
Test procedure
8
3.
Results
9
4.
Requirements of BS 7671
12
5.
Analysis
17
5.1
Initial Analysis
17
5.2
Impedance calculations
18
5.3
Further analysis
22
6.
Fault current withstand of cpc
26
7.
Proposed equations
28
8.
Conclusions
29
Š ERA Technology Ltd
6 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Tables List Page No. Table 1
Test results for 185 mm² cable.........................................................................9
Table 2
Test results for 95 mm² cable .........................................................................10
Table 3
Measured resistances.....................................................................................11
Table 4
Armour requirements from Table 54G............................................................12
Table 5
Two-core cable, in Air .....................................................................................14
Table 6
Three-core cable, In Air ..................................................................................15
Table 7
Comparison of measured and calculated currents ........................................17
Table 8
Calculated impedances for 185 mm² cable....................................................19
Table 9
Calculated impedances for 95 mm² cable......................................................20
Table 10
Resistance ratios ............................................................................................21
Table 11
CPC reactance................................................................................................21
Table 12
Calculated fault currents .................................................................................24
Table 13
Calculated armour fault currents ....................................................................25
Table 14
Minimum size of external cpc .........................................................................27
Figures List Page No. Figure 1
Test arrangement...............................................................................................8
© ERA Technology Ltd
7 of 30
ECA
1.
Guide to the Wiring Regulations
Appendix 16
Introduction
For some years it has become common practice to run separate circuit protective conductors, cpcs, in parallel with the armour of steel wire armoured low voltage cables. It is intended that these external cpcs would carry a proportion of the fault current and reduce the total impedance of the circuit protective conductor, armour and external cpc in parallel. It is also intended that the addition of an external cpc would increase the fault current withstand of the earth return path. One of the difficulties with this arrangement it that there is not a recognised method for calculating the current sharing between the steel wire armour and the external cpc. Limited theoretical studies, based on the armour being a complete steel tube, have indicated that the impedance of the external cpc will be high and the current would not be expected to be shared on the basis of the ratio of the resistance of the two paths. Because of the uncertainty in the current sharing ECA asked ERA to carry out a limited number of tests to measure the current sharing between the armour and an external cpc on 2 sizes of cable. This report contains details of the tests carried out.
2.
Test work
2.1
Methodology
Because it was expected that the reactance of the armour and external cpc would have a significant effect on the current sharing testing was carried out on larger sizes of cable where the reactive component of the impedance would be significant relative to the resistive component. The cables chosen for the tests were 95 mm² and 185 mm² 4-core armoured cables. The external cpcs used were 4 mm², 25 mm², 50 mm² and 95 mm². The cables were subjected to earth fault currents in the range of approximately 1000 A to 3000 A and the current in the phase conductor armour and external cpc recorded. The fault duration used was 0.4 seconds so that the heating effect of the fault current was small. This would minimise the effect of change of resistance with temperature on the current sharing.
2.2
Test arrangement
Each cable sample was about 7 m long. The armour was terminated in brass cable glands with approximately 1 m long tails at each end. Two brass earthing tags were fitted at each gland to minimise the risk of overheating the tags. The external cpc was bolted to the earthing tag at each end of the cable sample and tied to the cable at intervals along its length. At one end of the cable one phase conductor was also bolted to the earthing tag to form the earth fault. At the other end of the cable the phase conductor and the earthing tag were connected across the output terminals of a short-circuit transformer.
© ERA Technology Ltd
8 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Current probes were fitted around the phase conductor, the external cpc and the earthing tag at one end inside the connection to the external cpc. These current probes were used to monitor the total fault current, the current in the external cpc and the current in the armour. A sketch of the test circuit is shown in Fig. 1.
Transformer
External cpc Current probes
Cable sample Figure 1
Test arrangement
In addition to the current probes potential taps were fitted to measure the voltage across the output terminals of the short-circuit transformer and the voltage drop in the armour/cpc conductor. The voltage measurement leads were run away from the test sample at right angles to it before being run to the measuring instrument to minimise any induced voltage in the measurement leads.
2.3
Test procedure
The initial tests were carried out on the 185 mm² cable fitted with a 95 mm² external cpc in parallel with the armour. Prior to completely assembling the test circuit the dc resistance of the armour and the external cpc were measured individually. The circuit was then subjected to an earth fault of about 1000 A and the 3 currents and two voltages recorded on a transient recorder. The recorded traces were analysed to determine the magnitude and phase displacement, relative to the phase conductor current, of each trace, the relative displacement was recorded in milliseconds. The test was then repeated with a higher fault current. These two tests were then repeated on the 185 mm² cable with a 50 mm² and then a 25 mm² external cpc. The final tests on the 185 mm² cable were carried out with one of the cores of the cable connected in parallel with the armour in place of the external cpc. This series of tests was then repeated on the 95 mm² cable with the same range of additional cpcs. A limited number of additional tests were carried out on the 95 mm² cable with a 4 mm² external cpc.
© ERA Technology Ltd
9 of 30
ECA
3.
Guide to the Wiring Regulations
Appendix 16
Results
The recorded currents and phase displacements relative to the phase conductor current, in milliseconds, for the 185 mm² and 95 mm² cables are given in Tables 1 and 2. The measured resistance of the various conductors is given in Table 3 converted into mΩ/m. Table 1 Parameter
Test results for 185 mm² cable Measured Phase Measured Phase r.m.s value, displacement, r.m.s value, displacement, shot 1 ms shot 2 ms 185 mm² 4-core cable with 95 mm² external cpc
Total current, A
1902
0
2906
0
Armour current, A
905
-1.03
1358
-1.37
CPC current, A
1107
0.82
1874
0.91
Armour voltage, V
1.35
-1.13
2.31
-1.13
Total voltage, V
4.62
2.96
7.18
3
185 mm² 4-core cable with 50 mm² external cpc Total current, A
1846
0
2825
0
Armour current, A
993
-0.65
1510
-0.72
CPC current, A
923
0.81
1485
0.64
Armour voltage, V
1.91
-0.55
3.02
-0.77
Total voltage, V
5.02
2.72
7.58
2.68
185 mm² 4-core cable with 25 mm² external cpc Total current, A
1754
0
2574
0
Armour current, A
1039
-0.35
1648
-0.35
CPC current, A
700
0.58
1050
0.30
Armour voltage, V
2.40
-0.35
3.81
-0.58
Total voltage, V
5.07
2.3
7.41
2.22
185 mm² 4-core cable with 185 mm² internal cpc Total current, A
2372
0
3458
0
Armour current, A
583
-1.41
951
-1.43
CPC current, A
1853
0.30
2740
0.27
Armour voltage, V
1.87
-1.74
2.68
-1.68
Total voltage, V
4.73
2.33
6.79
2.31
© ERA Technology Ltd
10 of 30
ECA
Guide to the Wiring Regulations
Table 2 Parameter
Appendix 16
Test results for 95 mm² cable
Measured Phase r.m.s value, displacement, shot 1 ms
Measured r.m.s value, shot 2
Phase displacement, ms
95 mm² 4-core cable with 95 mm² external cpc Total current, A
1626
0
3239
0
Armour current, A
562
-1.68
1085
-1.71
CPC current, A
1220
0.62
2623
0.64
Armour voltage, V
1.41
-1.25
3.02
-1.27
Total voltage, V
5.98
2.83
12.23
3.03
95 mm² 4-core cable with 50 mm² external cpc Total current, A
1496
0
2970
0
Armour current, A
633
-1.03
1202
-1.03
CPC current, A
958
0.67
2082
0.55
Armour voltage, V
1.91
-0.63
3.83
-0.73
Total voltage, V
5.74
2.54
11.2
2.46
95 mm² 4-core cable with 25 mm² external cpc Total current, A
1312
0
2599
0
Armour current, A
689
-0.3
1329
-0.42
CPC current, A
702
0.5
1419
0.47
Armour voltage, V
2.56
-0.3
5.15
-0.31
Total voltage, V
5.19
1.8
10.35
1.87
95 mm² 4-core cable with 4 mm² external cpc Total current, A
662
0
389
0
Armour current, A
556
0
300
0
CPC current, A
110
0
71
0
Armour voltage, V
1.52
-0.2
0.91
-0.22
Total voltage, V
4.09
1.6
2.47
1.54
© ERA Technology Ltd
11 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Table 2 continued 95 mm² 4-core cable with 95 mm² internal cpc Total current, A
1697
0
3285
0
Armour current, A
477
-1.11
983
-1.0
CPC current, A
1326
0.19
2592
0.3
Armour voltage, V
1.98
-1.12
3.96
-1.0
Total voltage, V
4.67
1.56
9.26
1.67
Table 3
Measured resistances Component
Resistance, mΩ/m
4 mm² cpc
4.517
25 mm² cpc
0.657
50 mm² cpc
0.344
95 mm² cpc
0.174
95 mm² cable armour
0.832
95 mm² cable conductor
0.192
185 mm² cable armour
0.487
185 mm² cable conductor
0.0968
A review of the recorded current traces did not reveal any reduction in the current over the duration of the fault. This suggests the there was no significant change in resistance during the fault. This indicates that there was no significant temperature rise over the short duration of the fault at the fault currents used.
© ERA Technology Ltd
12 of 30
ECA
4.
Guide to the Wiring Regulations
Appendix 16
Requirements of BS 7671
There are a number of requirements in BS 7671 that relate to the cross-sectional area of cable armour. However the fundamental requirements are those in Chapter 41 relating to earth fault loop impedance and those in Chapter 54 relating to fault current withstand. The requirements in Chapter 54 give two methods for calculating the size of the protective conductor. The method covered by Regulation 543-01-04 and Table 54G bases the size of the cpc on the size of the phase conductor, multiplied by a factor relating to material properties. Minimum armour cross-sectional areas determined by this approach are given in Table 4 for 2 and 3 core cables having thermosetting insulation (XLPE). Table 4
Armour requirements from Table 54G
Nominal Nominal Nominal Armour size cable size, armour size, armour size, required mm2 mm2 mm2 from Table 54G 2-Core
3-Core
1
3
4
5
1.5
15
16
4.7
2.5
17
19
7.8
4
19
20
12.4
6
22
23
18.7
10
26
39
31.1
16
42
45
49.7
25
42
62
49.7
35
60
68
54.4
50
68
78
77.7
70
80
90
108.8
95
113
128
147.7
120
125
141
186.5
150
138
201
233.2
185
191
220
287.6
240
215
250
373
Š ERA Technology Ltd
13 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
300
235
269
466.3
400
265
304
621.7
The values highlighted in Red are those where the armour appears to be inadequate. From Table 4 it is clear that using the approach given in Regulation 543-01-04 leads to the conclusion that the cable armour will be inadequate in many cases. However the second approach offered by Regulation 543-01-03 is more rigorous and leads to a very different conclusion. The second method involves the calculation of the fault loop impedance, prospective fault current and disconnection time so that the fault energy, I2t, can be determined. The cpc is then selected so that the fault energy is less than the withstand capacity of the armour, k2S2. Since, in most cases, calculations should be carried out to demonstrate that the disconnection time is acceptable the additional calculations needed for the second method are not very great. The following tables give the results of calculations using the second approach. The comparisons are based on cables to BS 5467. The armour wire sizes on BS 6346, BS 6724 and BS 5467 cables are effectively the same. Because cables to BS 5467 and BS 6724 have a higher operating temperature than cables to BS 6346 the initial temperature used in calculating the k factors given in BS 7671 is higher. This leads to a lower k factor and hence a lower withstand capacity. Also the current ratings of cables to BS 5467 are higher than those of cables to BS 6346 and hence the rating of the protective device may be higher. Because of this the results for cables to BS 5467 or BS 6724 are the worse case. For these calculations it has been assumed that overload and fault current protection is provided by a BS 88 fuse. The fuse characteristics have been taken from the 15th edition of the IEE Wiring Regulations because this edition provided characteristics for a greater range of fuse sizes than those given in BS 7671. The fuse size selected is the largest size that is consistent with the tabulated single circuit rating of the cable.
Š ERA Technology Ltd
14 of 30
ECA
Guide to the Wiring Regulations
Table 5
Appendix 16
Two-core cable, in Air
Nominal Tabulated Fuse size Nominal cable current for armour size, mm2 rating size, mm2 It > In In Air
Armour withstand k2S2
I2t
I2t
from fuse from fuse curves, for 5 curves, for sec. 0.4 sec.
1
2
3
4
5
6
7
1.5
29
25
15
476100
50000
10240
2.5
39
32
17
611524
78125
19360
4
52
50
19
763876
242000
57760
6
66
63
22
1024144
392000
100000
10
90
80
26
1430416
800000
219040
16
115
100
42
3732624
1512500
384160
25
152
125
42
3732624
2380500
676000
35
188
160
60
7617600
4050000
1156000
50
228
200
68
9784384
7200000
1936000
70
291
250
80
13542400
9800000
3136000
95
354
315
113
27019204
22050000
5476000
120
410
400
125
33062500
33800000
9604000
150
472
400
138
40297104
33800000
9604000
185
539
500
191
77193796
61250000
17956000
240
636
630
215
97812100
92450000
29584000
300
732
630
235
116856100
92450000
29584000
400 847 800 265 148596100 231200000 The values highlighted in Red are those where the armour is inadequate.
67600000
The results given in Table 5 show that the armour is inadequate in only 2 cases. These cases are where the fault loop impedance is such that the maximum disconnection time of 5 seconds is only just achieved. The I²t values given in column 7, for a disconnection time of 0.4 seconds, show that the fuse characteristics are such that a reduced fault loop impedance, leading to a higher fault current results in a lower I²t.. For the 400 mm2 cable further calculations have shown that the armour would be suitable for use as a cpc if the fault duration did not exceed 2 seconds.
© ERA Technology Ltd
15 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Similar calculations have been carried out for 2-core armoured cables where the fuse size has been selected on the basis of the ‘clipped direct’ current rating. Because these ratings are lower the fuse size is lower in some cases. This reduces the I²t and the cable armour was found to be adequate in all cases. The results for similar calculations based on a 3-core cable are shown in Table 6. In this case the fuse size has been selected based on the 3-phase current rating of the cable. Table 6
Three-core cable, In Air
Nominal Tabulated Fuse size Nominal cable current for armour size, mm2 rating size, mm2 It > In In Air
Armour withstand k2S2
I2t from fuse curves, for 5 sec.
1
2
6
3
5
8
1.5
25
25
16
541696
50000
2.5
33
32
19
763876
78125
4
44
40
20
846400
144500
6
56
50
23
1119364
242000
10
78
63
39
3218436
392000
16
99
80
45
4284900
800000
25
131
125
62
8133904
2380500
35
162
160
68
9784384
4050000
50
197
160
78
12873744
4050000
70
251
250
90
17139600
9800000
95
304
250
128
34668544
9800000
120
353
315
141
42068196
22050000
150
406
400
201
85488516
33800000
185
463
400
220
102414400
33800000
240
546
500
250
132250000
61250000
300
628
500
269
153115876
61250000
400
728
630
304
195552256
92450000
© ERA Technology Ltd
16 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
The results given in Table 6 show that the armour of a 3-core cable has sufficient fault current withstand capacity in all cases, where overload and earth fault current protection is provided by a BS 88 fuse. Because the cross-sectional area of the armour on a 4-core cable will be greater than that on a 3-core cable of the same conductor size it is clear that the armour of a 4-core cable will also be adequate. The comparison of the two methods, given in BS 7671, for checking the fault withstand capacity of a cpc has shown that the simple method given in Table 54G gives a very pessimistic result for cable armour. Because of this the method given in Regulation 543-0103 should be used. Use of this method will usually demonstrate that the cable armour meets the requirements of Chapter 54 of BS 7671 where the protective device is a BS 88 fuse. Limited calculations using let through energy data for Type C mcbs and RCOBs to BS EN 61009 provided by one manufacturer has shown that the armour fault current withstand is also adequate where protection is provided by these devices.
Š ERA Technology Ltd
17 of 30
ECA
Guide to the Wiring Regulations
5.
Analysis
5.1
Initial Analysis
Appendix 16
The currents that would be expected in the external cpc and the armour, if the current sharing was based on the ratio of the resistances, were calculated. These currents are compared with the measured currents in Table 7. The calculated currents are based on the total measured currents and do not take any account of the measured phase displacements. Table 7
Comparison of measured and calculated currents
Cable arrangement
185 mm² cable + 95 mm² external cpc
185 mm² cable + 50 mm² external cpc
185 mm² cable + 25 mm² external cpc
185 mm² cable + 185 mm² internal cpc
95 mm² cable + 95 mm² external cpc
95 mm² cable + 50 mm² external cpc
95 mm² cable + 25 mm² external cpc
95 mm² cable + 4 mm² external cpc
95 mm² cable + 95 mm² internal cpc
Armour
External cpc
Measured
Calculated
Measured
Calculated
905
484
1107
1418
1358
739
1874
2167
993
739
923
1107
1510
1131
1485
1694
1039
979
700
774
1648
1437
1050
1137
583
491
1853
1881
951
716
2740
2742
562
281
1220
1345
1085
560
2623
2679
633
437
958
1058
1202
868
2082
2102
689
578
702
733
1329
1146
1419
1453
556
550
110
112
300
323
71
66
477
402
1326
1295
983
779
2592
2506
© ERA Technology Ltd
18 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Prior to carrying out the tests it was expected that the current carried by the external cpc would be very much less than that calculated from the resistance ratio. This is because previous estimates had been made based on the assumption that the armour would act like a closed steel tube. If this was the case the reactance of the external cpc would be very high and this would result in high impedance in the external cpc. The test results have shown that this is not the case. In all bar one of the tests with an external cpc the measured armour current was greater than that calculated from the resistance ratio. The one exception was one of the tests on the 95 mm² cable with the 4 mm² cpc. Similarly the measured current in the external cpc was less than that calculated from the resistance ratio except for one test with the 95 mm² cable and the 4 mm² cpc. In the tests where one core of the cable was connected in parallel with the armour, internal cpc, the calculated current in the cpc was close to the measured current and the calculated armour current was less than that in the armour. That the sum of the calculated currents is less than the sum of the measured currents is expected because no account of the relative phase angles in the calculation.
5.2
Impedance calculations
Further analysis was carried out by calculating the resistive and reactive components of the phase conductor, armour and cpc impedances. These calculations were carried out by calculating the phase angles of the measured currents and voltage, relative to the phase conductor current, from the measured phase displacements measured in milliseconds. The complex impedance of the armour and the cpcs were calculated by dividing the complex armour voltage by the complex armour and cpc currents. The phase conductor impedance was calculated by loop impedance from the total current and total voltage and subtracting the impedance of the parallel combination of the armour and cpc. The results of these calculations expressed in mΩ/m, are given in Tables 8 & 9.
© ERA Technology Ltd
19 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Table 8
Calculated impedances for 185 mm² cable
Condition
R + j x calculated impedances, mΩ/m Armour
cpc
Conductor
185 mm² 4-core cable with 95 mm² external cpc Measured d.c.
0.487
0.174
0.097
Shot 1
0.268 – j 0.008
0.179 – j 0.126
0.103 + j 0.240
Shot 2
0.306 + j 0.023
0.178 – j 0.133
0.100 + j 0.223
185 mm² 4-core cable with 50 mm² external cpc Measured d.c.
0.487
0.344
0.097
Shot 1
0.345 + j 0.011
0.339 – j 0.154
0.101 + j 0.240
Shot 2
0.360 – j 0.006
0.331 – j 0.157
0.100 + j 0.245
185 mm² 4-core cable with 25 mm² external cpc Measured d.c.
0.487
0.657
0.097
Shot 1
0.416 + j 0.000
0.592 – j 0.178
0.098 + j 0.231
Shot 2
0.416 – j 0.030
0.629 – j 0.179
0.099 + j 0.241
185 mm² 4-core cable with 185 mm² internal cpc Measured d.c.
0.487
0.097
0.097
Shot 1
0.576- j 0.060
0.111 – j 0.083
0.117 + j 0.184
Shot 2
0.506 – j 0.040
0.110 – j 0.077
0.117 + j 0.175
© ERA Technology Ltd
20 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
Table 9
Calculated impedances for 95 mm² cable
Condition
R + j x Calculated impedances, mΩ/m Armour
cpc
Conductor
95 mm² 4-core cable with 95 mm² external cpc Measured d.c.
0.832
0.174
0.192
Shot 1
0.485 + j 0.066
0.188 – j 0.125
0.206 + j 0.272
Shot 2
0.538 + j 0.075
0.185 – j 0.127
0.188 + j 0.272
95 mm² 4-core cable with 50 mm² external cpc Measured d.c.
0.832
0.344
0.192
Shot 1
0.583 + j 0.074
0.356 – j 0.154
0.196 + j 0.257
Shot 2
0.619 + j 0.058
0.330 – j 0.140
0.202 + j 0.269
95 mm² 4-core cable with 25 mm² external cpc Measured d.c.
0.832
0.657
0.192
Shot 1
0.725 + j 0.000
0.689 – j 0.177
0.194 + j 0.269
Shot 2
0.755 + j 0.026
0.687 – j 0.172
0.186 + j 0.260
95 mm² 4-core cable with 95 mm² internal cpc Measured d.c.
0.832
0.192
0.192
Shot 1
0.810 – j 0.003
0.199 - j 0.087
0.204 + j 0.166
Shot 2
0.785 + j 0.000
0.204 – j 0.088
0.204 + j 0.179
For both cables where an external cpc was used it is noted that the calculated resistive component of the impedance of the cpc and the conductor is close to the measured d.c. value. However the calculated resistive component of the armour is less than the measured value and increases with decreasing sizes of external cpc. In all cases the reactive component of the armour is small in comparison with the resistive component. Where an external cpc is used the reactive component of the conductor impedance is of a similar order of magnitude to the value of 0.30 mΩ/m recommended in IET Guidance note No 6 and ERA Report 84-0067 as the reactance to be used when calculating the earth fault loop impedance of an armoured cable. The reactive component of the impedance of the external cpc increases with decreasing cross-sectional area of the external cpc but appears not to be significantly influenced by the size of the armoured cable.
© ERA Technology Ltd
21 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
The ratio of the average calculated armour resistance to the measured armour resistance for both cables is given in Table 10. Table 10 Cross-sectional area of external cpc
Resistance ratios Armour resistance ratio 185 mm² cable
95 mm² cable
95 mm²
0.59
0.61
50 mm²
0.71
0.72
25 mm²
0.85
0.89
Internal cpc
1.11
0.96
These results suggest that the apparent reduction in armour resistance is a function of the cross-sectional area of the external cpc rather than a function of the cross-sectional area of the armoured cable. The comparison of the reactive component of the impedance of the external cpcs also indicates that this reactance is a function of the cross-sectional area of the cpc rather than a function of the cross-sectional area of the armoured cable. The average of the calculated reactance from each shot is tabulated below. Table 11 Cross-sectional area of external cpc
CPC reactance CPC reactance, mΩ/m 185 mm² cable
95 mm² cable
95 mm²
-0.130
-0.126
50 mm²
-0.156
-0.147
25 mm²
-0.178
-0.175
Internal cpc
-0.080
-0.088
© ERA Technology Ltd
22 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
The above analysis indicates that for calculation of the earth fault loop impedance of armoured cables with an external cpc two parameters are required in addition to the resistance of the armour and the external cpc. These factors are: 1.
A reduction factor for armour resistance that is independent of the cross-sectional area of the armoured cable.
2.
An impedance value for the external cpc that is independent of the cross-sectional area of the armoured cable.
An empirical equation for the reduction factor, Far, for the armour resistance has been derived by curve fitting the ratios given in Table 10. The resulting equation is: Far =
2.7744 S
+ 0.3143
Where S is the cross sectional area of the external cpc. Similarly the following empirical equation as been derived for the apparent reactance of the external cpc, Xcpc. X cpc =
5.3
0.4974 S
+ 0.0776
Further analysis
The initial analysis was aimed at analysing the test results to determine appropriate resistance and reactance values for the fault circuit to match the test results. It was clear that any calculation method derived from the initial analysis would result in an unwieldy set of equations. The further analysis has been based on reviewing the required parameters and revisiting the existing methods of calculation. When designing a circuit with a separate cpc in parallel with the steel wire armour of a cable there is a need to calculate the earth fault loop impedance in order to determine the magnitude of the fault current so that the disconnection time can be found. There is also a need to calculate the proportion of the fault current that will be carried by each parallel leg of the circuit, the armour and the external cpc. These currents, together with the disconnection times, are used to check whether the fault energy, I²t, is less than the withstand level of the armour and the cpc. The IET guidance note No 6 gives the impedance, ZL, of the earth loop formed by an armoured cable as:
Š ERA Technology Ltd
23 of 30
ECA
Guide to the Wiring Regulations
ZL =
(R + R ) + (X 2
1
p
1
Appendix 16
)
+Xp 2
Where:
(R + R )= R 1
(X
1
p
c
+ 1.1 R a and
0.3 L ) 1000
+Xp =
Rc = resistance of the line conductor, Ω Ra = resistance of the armour, Ω L = conductor length, m These equations were used to calculate the prospective fault current for the arrangements tested, based on the measured applied voltage. The value of Ra used in the calculations was taken as the resistance of the armour, RA, in parallel with the resistance of the external cpc, Rcpc. Ra =
1 1 1 + 1.1 R A Rcpc
The results of these calculations did not give a good fit with the measured total fault current. The above equations were then adjusted to provide a better fit. The reactance value of 0.3 mΩ/m had been derived from previous test work to take account of the effect of the armour on the reactance of the fault loop. As the initial analysis of the test results indicated that the total impedance of the circuit was higher than 0.3 this value was increased in stages to determine whether a reasonable fit could be achieved.. The prospective fault currents for an impedance value of 0.4 mΩ/m were calculated from the following equations: V If = m Zf
Where Vm = Measured total voltage, Tables 1 & 2 Zf =L
(R
c
) (
)
+ Rp 2 + Xc + X p 2
© ERA Technology Ltd
24 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
L = conductor length Rc = measured phase conductor resistance Rp =
(X
1
1 1 1 + 1.1 R A Rcpc 0.4 L ) 1000
+Xp =
The prospective fault currents obtained from these calculations are compared with the measured values in Table 12 below. Table 12
Calculated fault currents
Cable arrangement
First shot Measured
Calculated
Second shot Measured
Calculated
185 mm² cable + 95 mm² external cpc
1902
1748 (-8%)
2906
2717 (-7%)
185 mm² cable + 50 mm² external cpc
1846
1730 (-6%)
2825
2613 (-8%)
185 mm² cable + 25 mm² external cpc
1754
1571 (-10%)
2574
2296 (-11%)
95 mm² cable + 95 mm² external cpc
1626
1909 (21%)
3239
3905 (21%)
95 mm² cable + 50 mm² external cpc
1496
1612 (8%)
2970
3144 (6%)
95 mm² cable + 25 mm² external cpc
1312
1247 (-5%)
2599
2487 (-4%)
95 mm² cable + 4 mm² external cpc
389
409 (5%)
662
677 (2%)
The values given in () are the percentage differences between the measured and calculated values. Except for the calculated value for the 95 mm² cable with the 95 mm² external cpc all of the calculated values are considered to be sufficiently close to the measured values to be used when calculating prospective fault currents. As it is considered extremely unlikely that an external cpc having an equal size to the line conductor would be used the large difference between the values for the 95 mm² cable + 95 mm² external cpc can be ignored. The second factor to be considered is the current sharing between the parallel armour and external cpc paths.
© ERA Technology Ltd
25 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
The values given in Table 4 indicate that it is reasonable to calculate the proportion of the current carried by the external cpc on the basis of resistance rations. Thus the current in the external cpc, Icpc, can be given by: 1.1 R A I cpc = I f 1.1 R A + Rcpc
(
)
The values given in Table 4 also show that calculating the armour current on the basis of resistance ratios results in an armour current that is lower than the measured value. Because of this calculation of the armour currents have been carried out on the basis is half of the circuit reactance, 0.2 mΩ/m, being attributed to the external cpc and the armour resistance being reduced by a factor of 0.7. This gives the following equation for the armour current:
IA = I f
(0.7 R
2 Rcpc + 0.2 2 A
)
+ Rcpc 2 + 0.2 2
The armour currents calculated using this equation are given in Table 13. Table 13
Calculated armour fault currents
Cable arrangement
First shot Measured
Calculated
Second shot Measured
Calculated
185 mm² cable + 95 mm² external cpc
905
863 (-5%)
1358
1318 (-3%)
185 mm² cable + 50 mm² external cpc
993
984 (-1%)
1510
1506 (<1%)
185 mm² cable + 25 mm² external cpc
1039
1146 (10%)
1648
1682 (2%)
95 mm² cable + 95 mm² external cpc
562
514 (-9%)
1085
1024 (-6%)
95 mm² cable + 50 mm² external cpc
633
592 (-6%)
1202
1176 (-2%)
95 mm² cable + 25 mm² external cpc
689
686 (<1%)
1329
1359 (2%)
95 mm² cable + 4 mm² external cpc
300
341 (14%)
5556
580 (4%)
The values given in () are the percentage differences between the measured and calculated values.
© ERA Technology Ltd
26 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
The calculated values given in Table 13 above are considered to be sufficiently accurate for use in checking the fault current withstand of the cable armour.
6.
Fault current withstand of cpc
The comparisons of armour fault current withstand and fault energy given in Tables 5 & 6 indicate that the armour of a 120 mm² 2-core XLPE insulated cable is not sufficient to withstand the fault current required to operate a 400 A BS 88 fuse in 5 seconds. Thus this is a situation where an external cpc might be used. This cable size has been used as an example to investigate the effect of running a small external cpc in parallel with a much larger cable. The equations given in 5.3 above have been used to calculate the proportion of the fault current that would be carried by a 4 mm² external cpc run in parallel with the armour of a 120 mm² 2-core cable. The circuit length has been selected so that the total fault current is equal to the current required to operate a 400 A fuse in 5 seconds, 2600 A. The calculated armour and external cpc currents are 2170 A and 580 A respectively. The current carried by the armour is less that the maximum 5 second withstand current of the armour but the current carried by the external cpc is greater than its 5 second withstand current of 256 A. Thus the 4 mm² external cpc is not acceptable. As the size of the external cpc is increased then the proportion of the fault current that it carries will increase. Further calculations have shown that the minimum acceptable size of the external cpc in this case is 35 mm². Further calculations have been carried out to determine the minimum acceptable size for the external cpc. The calculated I²t values given in Table 5 show that, for the BS 88 fuse characteristics given in the Wiring Regulations, the I²t increases with increasing disconnection time. Because of this the calculations have been based on the current required to operate a BS 88 fuse in 5 seconds. For a given size of cable and external cpc the proportion the fault current carried by the external cpc will be greatest for the highest armour resistance. Because the armour resistance of a 2-core cable is higher than that of a 3 or 4 core cable the calculations have been based on 2-core cables. The fuse sizes have been selected on the same basis as for the calculations for Table 5. The minimum acceptable size for the external cpc is that having a 5 second fault current withstand greater than the calculated fault current to be carried by the cpc. The minimum calculated sizes are given in column 4 of Table 14. From these calculated results it is suggested that the minimum size of the external cpc should not be less than on quarter of the size of the line conductor of the cable (S/4). These values are given in column 5 of Table 14. For most cases the sizes given in column 5 of Table 14 are equal to or greater than those in column 4. The one exception is the 6 mm² cable where the calculations indicate that a 2.5 mm² external cpc would be required and the S/4 rule gives 1.5 mm². In this case the calculations show that the fault current withstand of the 1.5 mm² external cpc is 101 A and the proportion if the fault current it is expected to carry is 107 A. There are a number of
© ERA Technology Ltd
27 of 30
ECA
Guide to the Wiring Regulations
Appendix 16
conservative assumptions in these calculations including: there are no other parallel earth return paths, the use of the fuse characteristics in BS 7671and the assumed initial temperature of the external cpc (75°C). Of these the effect of the assumed initial temperature of the cpc is the easiest to asses. A temperature of 75°C was selected because the external cpc is expected to be touching the sheath of the main cable. For an XLPE insulated cable operating with a conductor temperature of 90 °C the expected sheath temperature is of the order of 75 °C. If the initial temperature of the 1.5 mm² external cpc is assumed to be 60 °C or lower then its 5 second fault current withstand is ≥ 107 A. Because of this the S/4 rule is considered acceptable. Table 14
Minimum size of external cpc
Nominal Tabulated Fuse size Minimum Size from cable current for external S/4 size, mm2 rating cpc mm² It > In mm² In Air 1
2
3
4
5
1.5
29
25
1.5
1.5
2.5
39
32
1.5
1.5
4
52
50
1.5
1.5
6
66
63
2.5
1.5
10
90
80
2.5
2.5
16
115
100
4
4
25
152
125
6
10
35
188
160
10
10
50
228
200
16
16
70
291
250
16
25
95
354
315
25
25
120
410
400
35
35
150
472
400
35
50
185
539
500
35
50
240
636
630
50
70
300
732
630
50
95
400
847
800
95
120
© ERA Technology Ltd
28 of 30
ECA
Guide to the Wiring Regulations
7.
Appendix 16
Proposed equations
If an external cpc is to be installed in parallel with steel wire armour the prospective fault current, If, should be calculated from the following equations. These equations have been derived from those given in IET Guidance Note No 6 and those derived above. If =
((R
U0
s
) + (X 2
+ R1 + R p
s
+ X1 + X p
)) 2
Where: Rs and Xs are the resistance and reactance of the supply,
(R + R )= R 1
(X
1
p
c
+
1 1 1 1.1 + R a Rcpc
0.4 L ) 1000
+Xp =
Rc = resistance of the line conductor, 立 Ra = dc resistance of the armour adjusted to the appropriate operating temperature, 立 Rcpc = resistance of the external cpc, 立 L = conductor length, m Where the above equations are used it will be necessary to calculate the proportion of the fault current carried by the external cpc to determine whether the fault current withstand of the external cpc is adequate. The proportion of the fault current carried by the armour, Ia, and the external cpc, Icpc, can be calculated from the following equations.
Ia = I f
(1.1R
2 Rcpc + 0.2 2 a
)
+ Rcpc 2 + 0.2 2
1.1 R a I cpc = I f 1.1 R a + Rcpc
(
)
息 ERA Technology Ltd
29 of 30
ECA
8.
Guide to the Wiring Regulations
Appendix 16
Conclusions
Prior to carrying out the test work described above it was thought that the proportion of any earth fault current carried by an external cpc, run in parallel with the armour of a cable, would be less than that predicted from the ratio of the armour and cpc resistance. The test work has shown that this is not the case and that using the resistance ratio will give a reasonable estimate of the current carried by the external cpc. Comparison of the fault current withstand of the armour of cables to BS 5467, using the k values given in Chapter 54 of BS 7671, has shown that for all cables except the 120 mm² and 400 mm² 2-core cables the fault current withstand of the armour is greater than the fault current required to operate a BS 88 fuse. Thus a supplementary external cpc is generally not required to increase the fault current withstand of an armoured cable. A supplementary external cpc would only be required if the earth fault loop impedance needed to be reduced to meet the values tabulated in Chapter 41 of BS 7671. This could be the case for a long cable run where protection against indirect contact was achieved by automatic disconnection of the supply and the use of a residual current device was not appropriate. Empirical equations have been derived for calculating the prospective fault current where an external cpc is installed in parallel with steel wire armour. Empirical equations have also been derived for calculating the current sharing between the armour and the external cpc. Calculation of the current sharing between the armour and an external cpc has shown that if a small external cpc is run in parallel with the armour of a large cable there is a risk that the fault current withstand of the external cpc will be exceeded. Because of this it is recommended that the cross-sectional area of the external cpc should not be less than a quarter of that of the line conductor.
© ERA Technology Ltd
30 of 30
Appendices
17
Appendix 17 â&#x20AC;&#x201C; A4 samples of ECA BS 7671: 2008 certificates The following pages are a single file (eight pages including this page) of the ECA certificates. These should only be used by ECA members; both member and nonmember versions are available to purchase from the ECA.
51
17
ELECTRICAL INSTALLATION CERTIFICATE (BS 7671: 2008) This form meets the model requirements of BS 7671: 2008
EI
© Copyright The Electrical Contractors’ Association, The Electrical Contractors’ Association of Scotland. This certificate is not valid if the number has been defaced or altered.
DETAILS OF THE CLIENT .....................................................................................................................................................................................................................................
INSTALLATION ADDRESS .....................................................................................................................................................................................................................................
DESCRIPTION AND EXTENT OF THE INSTALLATION Description of installation
e
..................................................................................................................................................................................................................................... Tick boxes as appropriate
❑
New installation Addition to an existing installation
pl
Extent of installation covered by this Certificate:
Alteration to an
(Use continuation sheet if necessary)
FOR DESIGN
existing installation
❑ ❑
m
I/We being the person(s) responsible for the design of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out that design hereby CERTIFY that the design work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Details of departures from BS 7671: 2008 (Regulations 120.3, 120.4): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the DESIGN of the installation: **(Where there is mutual responsibility for the design)
Sa
Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Designer No. 1 Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Designer No. 2**
FOR CONSTRUCTION
I/We being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that the construction work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Details of departures from BS 7671: 2008 (Regulations 120.3, 120.4): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the CONSTRUCTION of the installation: Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Constructor
FOR INSPECTION & TESTING I/We being the person(s) responsible for the inspection & testing of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection & testing hereby CERTIFY that the construction work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows: Details of departures from BS 7671: 2008 (Regulations 120.3, 120.2): The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate. For the INSPECTION AND TEST of the installation: Signature: .............................................. Date: ......................... Name (IN BLOCK LETTERS): ................................................. Inspector
NEXT INSPECTION I/We recommend that the installation should be re-inspected after an interval of not more than ..................................... months/years 09/07
Page 1 of
PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION CERTIFICATE Designer (No.1)
Name: ............................................................................. Company: ......................................................................................... Address: ...................................................................................................................................................................................... ........................................................................................ Postcode: ................................ Tel No: ...........................................
Designer (No.2) (if applicable)
Name: ............................................................................. Company: ......................................................................................... Address: ...................................................................................................................................................................................... ........................................................................................ Postcode: ................................ Tel No: ...........................................
Constructor
Name: ............................................................................. Company: ......................................................................................... Address: ...................................................................................................................................................................................... ........................................................................................ Postcode: ................................ Tel No: ...........................................
Inspector
Name: ............................................................................. Company: .........................................................................................
e
Address: ...................................................................................................................................................................................... ........................................................................................ Postcode: ................................ Tel No: ...........................................
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
TN-S TN-C-S TT IT
❑ ❑ ❑ ❑ ❑ ❑
Alternative Source of supply (to be detailed on attached schedules)
a.c. 1-phase, 2 wire 2-phase, 3 wire 3-phase, 3 wire
❑ ❑ ❑ ❑ ❑
d.c.
Nature of Supply Parameters
❑ ❑ ❑ ❑
Nominal voltage, U/Uo(1) ............................. V
Supply Protective Device Characteristics
Nominal frequency, f(1) ............................... Hz
Type ........................
pl
TN-C
Number and Type of Live Conductors
2-pole 3-pole other
Prospective fault current, Ipf(2) .................... kA External loop impedance, Ze(2) ................... Ω
m
Earthing arrangement
3-phase, 4 wire
Tick boxes and enter details as appropriate
Method of Fault Protection Automatic Disconnection (See 411)
❑
Means of Earthing
Distributor’s facility
❑
Installation earth electode
❑
Tick boxes and enter details as appropriate
Maximum Demand
Maximum demand (load) ....................................................................Amps/Phase Details of installation Earth Electrode (where applicable) Type (e.g. rod(s), tape etc) Location Electrode resistance to Earth
Sa
OTHER ...............................
rating .................. A
(Note (1) by enquiry, (2) by enquiry or by measurement)
PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE
Nominal current
...........................................
..................................
........................................... Ω
Main Protective Conductors
Earthing Conductor
material .......................
csa .......................mm2
Main equipotential bonding conductors To incoming water service
material .......................
csa .......................mm2
To lightning protection
❑ ❑
To incoming gas service To other incoming service(s)
❑ ❑
To incoming oil service
❑
To structural steel
❑
(state details ..............................................................................)
Main Switch or Circuit-breaker
Type and No. of poles ......................................
Current rating ............................. A
Location .............................................................
Fuse rating or setting ................. A
Voltage rating .................................................V
Rated residual operating current ........................... mA and operating time of ................... ms
COMMENTS ON EXISTING INSTALLATION
(applicable only when an RCD is suitable and is used as a main circuit-breaker)
(in case of an alteration or addition see Section 743)
..................................................................................................................................................................................................................................... ..................................................................................................................................................................................................................................... ..................................................................................................................................................................................................................................... .....................................................................................................................................................................................................................................
COMMENTS ON EXISTING INSTALLATION The attached Schedules are part of this document and this Certificate is valid only when they are attached to it. .....................Schedules of Inspection and.....................Schedules of Test Results are attached. (Enter quantities of schedules attached).
09/07
Page 2 of
Sa
m
INSTALLATION ADDRESS:
Current ................................kA
Frequency ..........Hz
Number and Type of Live Conductors ❑ ...........2 No. 1-Phase ❑ ...........3 No. 3-Phase ❑ ...........4 No. 3-Phase
09/07
Method of fault protection: Earthed equipotential ✓ bonding and automatic ❑ disconnection of supply
.......................................... Amps Per Phase
Maximum Demand
for .....................................................................................................................
Main Switch
Current Rating ..........................A
Supply Protection Type .................................
RCD Time Delay ..........................................................ms
Type ................................................... RCD 1∆n .........mA
Rating ................................................ Amps (Per Phase) Bonding
Earthing
❑ ❑ ❑ ❑ ❑ ❑
❑ or Details of Earth
CSA ..........mm2
CSA ..........mm2
Main Protective Conductors
SHEET 1 OF ____
Connections ❑ Verified
Connections ❑ Verified
Resistance ...............................................Ohms
Location ............................................................
Type ..................................................................
Supply Earth Electrode
Copper Steel Aluminium Copper Steel Aluminium
Earthing Arrangements ❑ TN-S ❑ TN-C-S ❑ TT Other ...........................
I/We recommend that the installation be further inspected and tested after an interval of not more than ............................. years.
e
...............................................................................
...............................................................................
Position ................................................................
...........................................................................................................................
...........................................................................................................................
Location ...........................................................................
PARTICULARS OF INSTALLATION REFERRED TO IN THIS CERTIFICATE
Impedance Ze ................Ohms
Earth Fault Loop
Prospective Fault
Voltage .................V
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
...........................................................................................................................................................................
...........................................................................................................................................................................
...........................................................................................................................................................................
Departures and comments on existing installation:- ....................................................................................
Alteration ...................❑
Addition .....................❑
New Installation ........❑
This certificate is not valid if the number has been defaced or altered.
SI
BS 7671: 2008 Requirements for Electrical Installations (17th Edition IEE Wiring Regulations) © Copyright The Electrical Contractors’ Association,
Name .................................................................................................................
pl
I/We, being the person responsible for the Design, Construction, Inspection & Testing of the electrical installation (as indicated by my signature below), particulars of which are described above, having exercised reasonable skill and care when carrying out the Design, Construction, Inspection & Testing, hereby CERTIFY that the said work for which I/we have been responsible is to the best of my knowledge and belief in accordance with BS 7671: 2008 except for the departures, if any, detailed as follows:
FOR DESIGN, CONSTRUCTION, INSPECTION & TESTING
DESCRIPTION AND EXTENT OF INSTALLATION COVERED BY THIS CERTIFICATE
DETAILS OF CLIENT
(For use in certification of AC installations only)
Electrical Installation Certificate BS 7671: 2008 - Single Signatory
DESCRIPTION
B
09/07
* Denotes optional information only
COMMENTS ON INSTALLATION:
A
REF
CIRCUIT
Sa
D
RATING AMPS CPC mm2
E*
F
G
DATE: .................................................................
SIGNED: ..............................................................
COMPANY: .........................................................
J
Ph - Ph Ω
K
N-N Ω
RING
CONTINUITY
INSTRUMENT
M
L-L MΩ
N
L-E MΩ
P
P O L A R I T Y
TYPE
RCD
R
SERIAL No.
S
V
REMARKS
SHEET 2 OF ____
ACCURACY VERIFIED
T
LOOP TRIP IMPEDANCE TIME OTHER Zs AT 1∆n FUNCTION ms Ω TESTS
EARTH FAULT
TEST INSTRUMENTS USED
e
L
CPC - CPC Ω
INSULATION RESISTANCE
TEST RESULTS
PROSPECTIVE FAULT CURRENT .............................................................. kA
pl
H
R1 + R2 Ω
m
LIVE mm2
SIZE
CONDUCTORS
Zdb ........................... Ohms
NAME: ................................................................
TESTER DETAILS
C
TYPE
OVERCURRENT DISC DEVICE SHORTTIME CIRCUIT CAPACITY........kA
DISTRIBUTION BOARD REF: ........................... LOCATION ......................................................................................................................
INSTALLED REF METHOD
PROTECTION ...........Amps
INSTALLED CIRCUIT DETAILS
TYPE .........................SIZE.................mm2
SUB-MAIN (WHERE APPLICABLE)
MINOR ELECTRICAL INSTALLATION WORKS CERTIFICATE (BS 7671: 2008) To be used only for the completion and inspection certification of electrical installation work which does not include a new circuit.
MW
© Copyright The Electrical Contractors’ Association This certificate is not valid if the number has been defaced or altered.
PART 1: DESCRIPTION OF MINOR WORKS 1. Description of the minor works 2. Location/Address 3. Date minor works completed
1. System earthing arrangements (where known) 2. Method of fault protection
pl
PART 2: INSTALLATION DETAILS
e
4. Details of departures, if any, from BS 7671: 2008
❑ TN-S ❑ EEBADS ❑ TN-C-S
TT
❑
OTHER ........................................................................ (411) Type ...................................................... Rating ........................................A
3. Protective device for the modified circuit
m
Comments on existing installation, including adequacy of earthing and bonding arrangements: (see Regulation 131.8)
PART 3: ESSENTIAL TESTS Earth continuity satisfactory
❑
Sa
Insulation resistance:
Phase/neutral ................................................... MΩ
(Where practical)
Phase/earth ...................................................... MΩ Neutral/earth ................................................... MΩ
Earth fault loop impedance ........................................................... Ω Polarity satisfactory
❑
RCD operation (if applicable).
Rated residual operating current ....................... mA and operating time of ....................... ms
INSTRUMENTS USED Manufacturer
Type
Serial Number
Date Accuracy Verified
PART 4: DECLARATION I/We CERTIFY that the said works do not impair the safety of the existing installation, that the said works have been designed, constructed, inspected and tested in accordance with BS 7671: 2008 (IEE Wiring Regulations), and that the said works, to the best of my/our knowledge and belief, at the time of my/our inspection, compiled with BS 7671: 2008 except as detailed in part 1. Name: ....................................................................................................
Signature: ............................................................................................
For and on behalf of: ...........................................................................
Position: ...............................................................................................
Address: ................................................................................................ ................................................................................................................ ................................................................................................................ 09/07
Date: ....................................................................................................
DESCRIPTION
B
* Denotes optional information only
09/07
Sa
W*
No OF POINTS SERVED
C
TYPE
D
RATING AMPS
OVERCURRENT DISC DEVICE SHORTTIME CIRCUIT CAPACITY........kA
F
LIVE mm2
G
CPC mm2
SIZE
K
N-N Ω
INSTRUMENT
J
Ph - Ph Ω
RING
L
M
L-L MΩ
P
P O L A R I T Y
R
TYPE
SERIAL No.
S
V
REMARKS
SHEET 3 OF 3
ACCURACY VERIFIED
T
LOOP TRIP IMPEDANCE TIME OTHER Zs AT 1∆n FUNCTION ms Ω TESTS
EARTH FAULT
RCD
DATE: .........................................................
SIGNED: ......................................................
COMPANY: .................................................
TEST INSTRUMENTS USED
N
L-E MΩ
INSULATION RESISTANCE
e
pl
H
R1 + R2 Ω
m
E*
INSTALLED REF METHOD
TYPE:.........................
CONDUCTORS:
CPC - CPC Ω
PFC: ................. kA (Prospective Fault Current)
PROTECTION: .............
CONTINUITY
Zdb: ................. OHMS: ....................................
SIZE: ................... mm2
TESTER DETAILS NAME: ........................................................
T
TEST RESULTS
REF: ................. LOCATION: .....................................................................................
DISTRIBUTION BOARD
TYPE: ..........................
SUB-MAIN
INSTALLED CIRCUIT DETAILS
COMMENTS ON INSTALLATION:
A
REF
CIRCUIT
JOB No:
PROJECT:
© Copyright The Electrical Contractors’ Association The Electrical Contractors’ Association of Scotland
SCHEDULE OF TEST RESULTS
SCHEDULE OF INSPECTIONS (BS 7671: 2008)
I
PROJECT:
JOB No:
INSPECTED BY:
DATE:
Notes: ✓ to indicate an inspection has been carried out and the result is satisfactory ✗ to indicate an inspection has been carried out and the result is unsatisfactory N/A to indicate an inspection is not applicable LIM to indicate that, exceptionally, a limitation agreed with the person ordering the work prevented the inspection being carried out
Prevention of mutual detrimental influence (a)
Both basic and fault protection: SELV
(ii)
PELV
(b) (c)
(iii) Double insulation (iv)
Reinforced insulation
Basic protection (i)
Insulation of live parts
(ii)
Barriers or enclosures
(iv)
Placing out of reach
Fault protection:
Presence of diagrams, instructions, circuit charts and similar information
(b)
Presence of danger notices and other warning notices
(c)
Labelling of protective devices, switches and terminals
(d)
Identification of conductors
Cables and conductors
Erection methods
Presence of circuit protective conductors
Routing of cables in prescribed zones
Presence of protective bonding conductors
Cables incorporating earthed armour or sheath, or run within an earthed wiring system, or otherwise adequately protected against nails, screws and the like
Presence of earthing arrangements for combined protective and functional purposes
Additional protection provided by 30 mA RCD for cables in concealed walls (where required in premises not under the supervision of a skilled or instructed person)
Presence of adequate arrangements for alternative source(s), where applicable FELV
Connection of conductors
Choice and setting of protective and monitoring devices (for fault and/or overcurrent protection)
Non-conducting location:
Absence of protective conductors
(iii)
Earth-free equipotential bonding: Presence of earth-free equipotential bonding
(iv)
Electrical Separation:
Presence of fire barriers, suitable seals and protection against thermal effects
General Presence and correct location of appropriate devices for isolation and switching Adequacy of access to switchgear and other equipment Particular protective measures for special installations and locations
Provided for one item of current-using equipment
Connection of single-pole devices for protection or switching in line conductors only
Provided for more than one item of currentusing equipment
Correct connection of accessories and equipment
Additional protection:
09/07
Selection of conductors for current-carrying capacity and voltage drop
Presence of earthing conductor
Presence of supplementary bonding conductors
(ii)
Segregation of safety circuits
(a)
Automatic disconnection of supply:
Sa
(i)
Segregation of Band I and Band II circuits or use of Band II insulation
Identification
m
(iii) Obstacles
Proximity of non-electrical services and other influences
pl
(i)
e
Methods of protection against electric shock
Presence of undervoltage protective devices
Presence of residual current devices(s)
Selection of equipment and protective measures appropriate to external influences
Presence of supplementary bonding conductors
Selection of appropriate functional switching devices
© Copyright The Electrical Contractors’ Association
Page ___ of ___
Guide to the Wiring Regulations
18 18.1
Appendix 18 – Building standards in Scotland Building regulations The Building Regulations 2000 are not applicable in Scotland where the Building (Scotland) Regulations 2004 apply. Compliance with these Regulations can be achieved by complying with the mandatory Scottish Building Standards. Guidance on how to achieve compliance with these Standards is given in two Scottish Building Standards technical handbooks (domestic and non-domestic). These handbooks contain recommendations for electrical installations including the following:
•• •• •• • 18.2
Compliance with BS 7671: 2001 Minimum number of socket-outlets in dwellings Minimum number of lighting points in dwellings Minimum illumination levels in common areas of domestic buildings e.g. blocks of flats Minimum mounting heights of switches and socket-outlets etc. Separate switching for concealed socket-outlets e.g. behind white goods in kitchens etc. Conservation of fuel and power in both domestic and non-domestic buildings
Certification Scheme Under the Building Scotland Act 2003 a new certification scheme was introduced for work that is the subject of a building warrant. The electrical installation is required to be certified by an Approved Certifier of Construction under a scheme operated by an Approved Body (Contractor). Approved Bodies and Approved Certifiers are required to meet the criteria for a Certification Scheme operated by a Scheme Provider. Details of this scheme can be obtained at www.sbsa.gov.uk
18
52