St. Francis Building

Page 1

DOCUMENT PACKAGE

PATIENT ROOM ADDITION FIT UP

ISSUED:

AUGUST 13, 2013

PACKAGE:

CONSTRUCTION ISSUE RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

FRANCISCAN HEALTHCARE ST. FRANCIS BUILDING 9TH LEVEL LA CROSSE, WISCONSIN

- BRICK EXPANSION JOINT - BOARD - BUILDING - BLOCK - BEAM - BOTTOM - BRICK - BASEMENT - BOLT - BUILT-UP ROOFING

CAB CAT CB CBD CBU CEM CER CG CH CHAN CI CIP CJ CL CLG CLR CMU CNTR CO COL COMPART CONC COND CONN CONT CONTR COORD CORR CT CTR CTSK CW

- CABINET - CATEGORY - CATCH BASIN - CHALK BOARD - CEMENTITIOUS BACKER UNIT - CEMENT - CERAMIC - CORNER GUARD - CHILLER - CHANNEL - CAST IRON - CAST-IN-PLACE - CONTROL JOINT / CONSTRUCTION JOINT - CENTER LINE - CEILING - CLEAR - CONCRETE MASONRY UNIT - COUNTER - CLEANOUT - COLUMN - COMPARTMENT - CONCRETE - CONDITION - CONNECTION - CONTINUOUS - CONTRACTOR - COORDINATE - CORRIDOR - CERAMIC TILE / COOLING TOWER - CENTER - COUNTER SUNK - COLD WATER (PIPING)

D DA DBL DEG DEMO DEPT DET DF DIA DIFF DIM DIS DISP DMPF DMT DN DO DP DPTN DR DRN DS DW DWG DWR

- DEEP, DEPTH - DISABLED - DOUBLE - DEGREE - DEMOLITION - DEPARTMENT - DETAIL - DRINKING FOUNTAIN - DIAMETER - DIFFUSER - DIMENSION - DISABLED - DISPENSER - DAMPPROOFING - DEMOUNTABLE - DOWN - DOOR OPENING - DIMENSION POINT - DEMOUNTABLE PARTITION - DOOR - DRAIN - DOWNSPOUT - DISHWASHER - DRAWING - DRAWER

(E) E EA EB EIFS EFS EJ EL ELEC ELEV EMERG ENCLO EP EQ EQUIP ESCAL EWC EXH EXP EXIST EXT

- EXISTING - EAST - EACH - EXPANSION BOLT - EXTERIOR INSULATION AND FINISH SYSTEM - EXTERIOR FINISH SYSTEM - EXPANSION JOINT - ELEVATION - ELECTRICAL - ELEVATOR - EMERGENCY - ENCLOSURE - ELECTRICAL PANELBOARD - EQUAL - EQUIPMENT - ESCALATOR - ELECTRICAL WATER COOLER - EXHAUST - EXPANSION - EXISTING - EXTERIOR

FA FB FC FD FDC FND FE FEC FF&E FFEL FH FHC FIN FIXT FL FLASH FLUOR FO FP FPG FR FT FRTW FTG FURN FURR FWC FWP

- FIRE ALARM - FACE BRICK - FACE - FLOOR DRAIN - FIRE DEPARTMENT CONNECTION - FOUNDATION - FIRE EXTINGUISHER - FIRE EXTINGUISHER CABINET - FURNITURE, FINISHES & EQUIPMENT - FINISH FLOOR ELEVATION - FLAT HEAD - FIRE HOSE CABINET - FINISH - FIXTURE - FLOOR - FLASHING - FLUORESCENT - FACE OF - FIRE PROTECTION - FIREPROOFING - FRAME - FEET - FIRE RETARDANT TREATED WOOD - FOOTING - FURNITURE - FURRING - FABRIC WALLCOVERING - FABRIC WRAPPED PANEL

- GROUND - GAUGE / GAGE - GALVANIZED - GRAB BAR - GENERAL CONTRACT(OR) - GLASS FIBER REINFORCED CONCRETE - GLASS FIBER REINFORCED GYPSUM - GLASS - GRADE - GROUND - GYPSUM WALLBOARD

H HB HC HCP HDW HDWD

- HIGH / HEIGHT - HOSE BIB - HOLLOW CORE - HANDICAPPED - HARDWARE - HARDWOOD

HS HM HNDRL HO HORIZ HPT HRC HR HT HVAC HW HYDR

- HEAT STRENGTHEND (GLASS) - HOLLOW METAL (STEEL FRAME) - HANDRAIL - HOLD-OPEN - HORIZONTAL - HIGH POINT - HOSE REEL CABINET - HOUR - HEIGHT - HEATING, VENTILATION, AIR CONDITIONING - HOT WATER - HYDRAULIC

ID IN INCAND INCL INFO INSUL INT INTERM INV IPS IRMA

- INSIDE DIAMETER - INCH - INCANDESCENT - INCLUDED / INCLUDING - INFORMATION - INSULATION - INTERIOR - INTERMEDIATE - INVERT - INTERNATIONAL PIPE STANDARD - INVERTED ROOF MEMBRANE ASSEMBLY

JAN JC JST JT

- JANITOR - JANITOR'S CLOSET - JOIST - JOINT

K KPL KG KIT KO

- KIP (1000 LBF) - KICK PLATE - KILOGRAM - KITCHEN - KNOCKOUT

L LAB LDG LAM LAV LB LF LKR LLH LLV LN LT LPT

- LONG OR LITER (METRIC DOCS) - LABORATORY - LANDING - LAMINATE / LAMINATION - LAVATORY - POUND - LINEAR FOOT - LOCKER - LONG LEG HORIZONTAL - LONG LEG VERTICAL - LINE - LIGHT - LOW POINT

M MACH MAINT MAS MATL MAX MB MBL MDF MEP MDO MECH MEMB MET MEZZ MFR MH MIN MISC MM MO MS MTD MTG MTL MULL

- METER - MACHINE - MAINTENANCE - MASONRY - MATERIAL - MAXIMUM - MACHINE BOLT - MARBLE - MEDIUM DENSITY FIBERBOARD - MECHANICAL, ELECTRICAL, PLUMBING - MEDIUM DENSITY OVERLAY PLYWOOD - MECHANICAL - MEMBRANE - METAL - MEZZANINE - MANUFACTURER - MANHOLE - MINIMUM - MISCELLANEOUS - MILLIMETER - MASONRY OPENING - MACHINE SCREW - MOUNTED - MOUNTING - METAL - MULLION

N NA NC NIC NO NOM NTS

- NORTH - NOT APPLICABLE - NOISE CRITERIA - NOT IN CONTRACT - NUMBER - NOMINAL - NOT TO SCALE

OA OC OCEW OD OFCI OFOI OFF OH OPH OPNG OPP OPPHD ORD OUTS OVHD

- OUTSIDE AIR - ON CENTER - ON CENTER EACH WAY - OUTSIDE DIAMETER/DIMENSION - OWNER FURNISHED, CONTR INSTALLED - OWNER FURNISHED, OWNER INSTALLED - OFFICE - OVER HEAD - OPPOSITE HAND - OPENING - OPPOSITE - OPPOSITE HAND - OVERFLOW ROOF DRAIN - OUTSIDE - OVERHEAD

P PAV PARTN PATD PBD PC PDF PERF PERIM PERP PF PL PLAM PLAS PLBG PLF PLYWD PNL POL PR PREFAB PROJ PSF PT PTD PTN PTR Q QTY

\\minfs02.rsparch.internal\RSPUsers$\jandring\Documents\SF09CENTRAL_jandring.rvt 8/9/2013 10:22:33 AM

- PAINT - PAVING - PARTITION - PAPER TOWEL DISPENSER - PARTICLEBOARD - PRECAST CONCRETE - POWER DRIVEN FASTENER - PERFORATED - PERIMETER - PERPENDICULAR - POINT OF INTERSECTION - PLATE - PLASTIC LAMINATE - PLASTER - PLUMBING - POUNDS PER LINEAR FOOT - PLYWOOD - PANEL - POLISHED - PAIR - PREFABRICATED - PROJECT - POUNDS PER SQUARE FOOT - POINT - PAINTED - PARTITION - PAPER TOWEL RECEPTACLE - QUARRY TILE - QUANTITY

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

(R) R RA RAD RB RCP RD RECOM RECPT REC REF REFL REFR REG REINF REL REM REQ RESIL REV RM RO RTD RTG RWL

- RELOCATED - RADIUS OR RISER (PIPING) - RETURN AIR - RADIUS - RESILIENT BASE - REFLECTED CEILING PLAN - ROOF DRAIN - RECOMMENDED - RECEPTACLE - RECESSED - REFERENCE - REFLECTED / REFLECTIVE / REFLECT - REFRIGERATOR - REGISTER - REINFORCED / REINFORCING - RELOCATE - REMOVABLE - REQUIRE / REQUIRED - RESILIENT - REVISION / REVISED - ROOM - ROUGH OPENING - RATED - RATING - RAIN WATER LEADER

S SA SAN

- SOUTH - SUPPLY AIR - SANITARY

SC - SOLID CORE SCHED - SCHEDULE SD - STORM DRAIN / SOAP DISPENSER SECT - SECTION STS - SELF TAP METAL SCREW SF - SQUARE FEET/FOOT SH - SPRINKLER HEAD SHT - SHEET SHR - SHOWER SIM - SIMILAR SM - SHEET METAL OR SQUARE METER SND - SANITARY NAPKIN DISPENSER SP - STANDPIPE SPEC - SPECIFICATION SPR - SPRINKLER SPKR - SPEAKER SQ - SQUARE SSE - STRUCTURE SLAB ELEVATION SST - STAINLESS STEEL SSK - SERVICE SINK STA - STATION STD - STANDARD STL - STEEL STLJST - STEEL JOIST STOR - STORAGE STRG - STRINGER STRL - STRUCTURAL STRUC - STRUCTURAL SUBCAT- SUBCATEGORY SUSP - SUSPENDED SYMM - SYMMETRICAL SYS - SYSTEM

SHEET INDEX DRAWINGS

OWNER

ARCHITECT

MECH/ELEC ENGINEERS

Mayo Health System -Franciscan Skemp Facilities Project Services 700 West Avenue South LaCrosse, WI 54601

RSP Architects, Ltd. 320 South Broadway, Suite B Rochester, MN 55904 Phone: 507/285-6569 Fax: 612/677-7499

MEP Associates, LLC 2900 43rd Street NW, Suite 100 Rochester, MN 55901 Phone: 507/281-1632 Fax: 507/281-6328

Dennis Havlik, Construction Supervisor Phone: 608/392-4869 Email: havlik.dennis@mayo.edu

ISSUES CONSTRUCTION ISSUE 08/13/13

BEJ BD BLDG BLK BM BOT BRK BSMT BT BUR

PROJECT TEAM G GA GALV GB GC GRC GRG GL GR GRD GYPBD

ISSUE KEY: 1 ISSUED (WITH SIGNATURE) 2 REVISED AND RE-ISSUED (WITH SIGNATURE) 3 NOT FOR CONSTRUCTION - REFERENCE ONLY 4 RE-ISSUED FROM A PRIOR BID PACK - NO REVISIONS

Stephen Fautsch, Principal Phone: 612/677-7175 Email: Steve.Fautsch@rsparch.com

Mechanical Contact:

Luke Johnson Phone: 507/281-1632 Email: Lukej@mepassociates.com

Jasen Andring, Project Captain Phone: 507/292-8664 Email: jasen.andring@rsparch.com

Electrical Contact:

Kerry Hayden Phone: 507/281-1632 Email: Kerryh@mepassociates.com

SHEET NO. NAME G000 COVER SHEET G109 NINTH LEVEL LIFE SAFETY PLAN

Certification

3 3

A109 A209 A301 A901

NINTH LEVEL DEMOLITION PLAN AND FLOOR PLAN NINTH LEVEL REFLECTED CEILING PLAN DOOR SCHEDULE AND PARTITIONS TYPES DETAILS AND INTERIOR ELEVATIONS

3 3 3 3

I109

NINTH LEVEL FINISH PLAN

3

P001

PLUMBING SYMBOLS, ABBREVIATIONS, GENERAL NOTES, DETAILS AND SCHEDULES PARTIAL NINTH LEVEL PLUMBING PLAN

3

3

M109

MECHANICAL SYMBOLS, ABBREVIATIONS, GENERAL NOTES AND SCHEDULES PARTIAL NINTH LEVEL MECHANICAL HVAC PLAN

3

E001 ED209 E209 E309

ELECTRICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES PARTIAL NINTH LEVEL ELECTRICAL DEMOLITION PLAN PARTIAL NINTH LEVEL ELECTRICAL LIGHTING AND POWER PLAN PARTIAL NINTH LEVEL ELECTRICAL SIGNAL PLAN

3 3 3 3

Signature:

KEY PLAN

P109 M001

UP

STEPHEN J. FAUTSCH

Registration Number: A-11366 Date:

Registration Expiration: 7/31/14

8/13/13

Project For

3

DN

Franciscan Healthcare St. Francis Building Ninth Level

ICE

REF

WO W

PATIENT ROOM ADDITION FIT UP

REF ICE

PIL LO W T UB WO W

T&G T TB TC TCONC TEL TEMP TER TGB THK THRES THRU TKBD TMPD TO TOS TOSTL TP TPD TRACT TV TW TYP

- TONGUE AND GROOVE - TREAD / THERMOSTAT - TOWEL BAR - TOP OF CURB - TOP OF CONCRETE - TELEPHONE OR TELECOM - TEMPERATURE - TERRAZZO - TOGGLE BOLT - THICKNESS - THRESHOLD - THROUGH - TACKBOARD - TEMPERED - TOP OF (SEE OTHER WORD) - TOP OF SLAB, TOP OF STRUCTURE - TOP OF STEEL - TOP OF PAVEMENT - TOILET PAPER DISPENSER - TRACTION - TELEVISION - TOP OF WALL - TYPICAL

UNFIN UON UR

- UNFINISHED - UNLESS OTHERWISE NOTED - URINAL

VAC VCT VERT VEST VIF VR VT VWC

- VENTILATION AND AIR CONDITIONING - VINYL COMPOSITION TILE - VERTICAL - VESTIBULE - VERIFY IN FIELD - VAPOR RETARDER - VINYL TILE - VINYL WALL COVERING

W/ W WC WD WDS WDW W/O WP WPM WPT WR WS WSCT WT WW

- WITH - WIDE, WIDTH/WEST - WATER CLOSET - WOOD - WOOD SCREW - WINDOW - WITHOUT - WATERPROOFING - WATERPROOF MEMBRANE - WORK POINT - WATER RESISTENT/REPELLANT - WEATHERSTRIPPING - WAINSCOT - WEIGHT - WALL TO WALL

UP

DN

UP

DN

CLE AN LIN EN

MED CA RT

PEDS CRASH CART

WO W

PYXIS

PYXIS

WO W

PYXIS

CODE ANALYSIS

REF.

- ANCHOR BOLT - AIR CONDITIONING - ACCESSIBLE - ACOUSTICAL - AREA DRAIN - ADDITIONAL - ADJUSTABLE - ABOVE FINISH FLOOR - AGGREGATE - ALTERNATE - ALUMINUM - ANCHOR - ANODIZED - ACOUSTICAL PANEL CEILING - APPROVED - APPROXIMATE - ARCHITECTURAL - ACOUTSTICAL TILE CEILING - AUTOMATIC - AUDIO VISUAL

FUTURE PYXIS FUTURE PYXIS

Means of Egress – Chapter 10 Occupant Load Table1004.1.1 – Institutional Areas – Sleeping Areas -= 120 GSF per occupant Total Occupants for the 9th Floor: 302 occupants

Applicable codes

· · · ·

2011 Wisconsin Commercial Building Code 2009 International Building Code 2009 International Fire Code ICC/ANSI Standard A117.1 - 2003 2011 NFPA 70

Common Path of Travel Section 1014.3 Common path of egress travel distance shall not exceed 75 feet.

Use and Occupancy – Chapter 3 Occupancy: Section 308 – Institutional Group I Building Occupancy: Group I-2, Hospitals

AREA OF WORK

Exit Access Travel Distance Table 1016.1 I-2 Occupancy allows 200 feet maximum exit access travel distance with sprinkler system.

Special Detailed Requirements Based on Use and Occupancy – Chapter 4 Section 407 – Group I-2

DN

UP

General Building Heights and Areas – Chapter 5 Table 503 - Height and Number of Stories: Height Requirement: Unlimited Actual: Not known

Corridor Fire-Resistance Rating Table 1018.1 – Corridor Fire-Resistance Rating Required Fire-Resistance Rating: 0 hours Dead Ends Section 1018.4 Distance shall not exceed 20 feet

Stories Requirement: Unlimited Actual: 11 stories Type of Construction – Chapter 6 Construction Type: Assumed Type 1-A – No existing code information available

1

Fire Protection System Chapter 9 Existing Building is provided with Automatic Sprinkler System and Fire Alarm System consistent with the requirements of Chapter 9 throughout the entire facility.

NINTH LEVEL KEY PLAN 1" = 20'-0"

DRAWING SYMBOLS

ARCHITECTURAL

1

0

ROOM NAME REVISION REFERENCE

0

COLUMN OR GRID LINE - EXISTING

A101

ELEVATION TAG SINGLE VIEW

101

A101

2

ELEVATION TAG MULTIPLE VIEW

PARTITION TAG

1 A101

DETAIL TAG

SIM MATCH LINE

MATCH LINE

12

SEE X/XXX

T.O. FOOTING Name Elevation EL. = 96'-0" EL. = 100'-0"

2045.002.03

Drawn By

BCS

Checked By

JHA

Date

08/13/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2012. All rights reserved.

Revisions No.

Date

Description

VIEW NAME 1/8" = 1'-0"

DRAWING TITLE

1 A101

1 A101

ELEVATION / LEVEL TAG NORTH ARROW

SPOT ELEVATION

NORTH NORTH

SIM

WALL SECTION TAG

ROOM TAG

(ROOM AREA)

XX

KEYNOTE

23 1t

WINDOW TAG

234

EQUIPMENT TAG

101

DOOR TAG ELECTRICAL

PT-1 VB-1 SV-2

SIM

(WALL FINISH) (BASE FINISH) (FLOOR FINISH)

FINISH TAG ALL SURFACES

BUILDING SECTION TAG

VB-1 SV-2

1 A101 SIM

PLUMBING / MECHANICAL / FIRE PROTECTION

(ROOM NAME) (ROOM NUMBER)

150 SF

1

COLUMN OR GRID LINE - NEW

0

Exit Access Table 1021.1 – Minimum Number of Exits for Occupant Load Required: 1-500 Occupants require 2 exits minimum Provided: 4 exits provided

Project No.

STAMPS AND APPROVALS 1

0

Key Plan

Egress Width Table 1005.1 9th Floor Required: 302 occupants x 0.2 = 60 inches Provided: 4 exit doors = 140 inches

Building Description: The existing building is an 11 story hospital with the 9th floor being the highest floor occupied by patients. This remodeling project is occurring on the 9th floor which is 36,240 GSF.

XXXX

AB AC ACC ACOUS AD ADD ADJ AFF AGGR ALT ALUM ANCH ANNO APC APPD APPROX ARCH ATC AUTO AV

Consultants

ENLARGED PLAN OR DETAIL REFERENCE

CPT-01

CPT-02

FINISH TAG WITH EXTENT OF FINISH

FINISH TRANSITION

COVER SHEET

G000


Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


DEMOLITION PLAN GENERAL NOTES:

DEMOLITION PLAN LEGEND:

1. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS. THE INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS. PYXIS

PYXIS

PYXIS

1.7

1.6

1.3

1.3

1.3

1.4

EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED

3. LOUD DEMOLITION WORK (i.e. CONCRETE REMOVAL) SHALL BE COORDINATED WITH THE BUILDING MANAGER TO MINIMIZE DISRUPTION TO BUILDING OCCUPANTS.

1.7

1.3

EXISTING DOOR AND FRAME TO REMAIN

2. FIRE SAFETY MUST BE MAINTAINED FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS, SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. IMMEDIATELY NOTIFY BUILDING SECURITY AND BUILDING MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY.

1.7

1.5

EXISTING PARTITION TO REMAIN

4. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND/OR REPAIRING ANY DAMAGE CAUSED BY HIM OR HIS SUBCONTRACTORS TO EXISTING CONSTRUCTION IN ELEVATOR LOBBIES, PUBLIC CORRIDORS OR RESTROOMS. REFINISH TO MATCH EXISTING ADJACENT FINISH, OR AS NOTED HEREIN.

ROOM NAME

5. ALL DIMENSIONS TO EXISTING ELEMENTS ARE FOR REFERENCE ONLY AND SHOULD BE FIELD VERIFIED.

2.1

6. THE INTENT OF THIS DEMOLITION IS TO PROVIDE A CLEAN AND CLEAR AREA FOR NEW CONSTRUCTION AND FINISHES.

1.8

1i

"OUT"

EXISTING DOOR AND FRAME TO BE REMOVED

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

ROOM TAG

Consultants

KEYNOTE EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE

EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK. AREA N.I.C.

1.1 Certification

1.2

KEYNOTES - DEMOLITION PLAN 1.1

SHELL SPACE 9-00

1.8

EXISTING ELECTRICAL PANEL TO BE REMOVED AND RELOCATED PRIOR TO START OF PROJECT. EXISTING FIRE ALARM TO BE REMOVED AND RELOCATED PRIOR TO START OF PROJECT. REMOVE EXISTING WALL CONSTRUCTION TO ACCOMODATE NEW CONSTRUCTION - SEE FLOOR PLAN FOR DIMENSIONS NEW DOOR OPENING - SEE FLOOR PLAN FOR LOCATION REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE AND GRID. REMOVE EXISTING SHEET VINYL FLOORING AND COVED BASE. NO WORK IN THIS AREA. EXISTING PLUMBING OR HYDRONIC PIPING TO REMAIN.

1.2

WORK RM. 9-03H

1.3

1.7

1.4 1.5 1.6 1.7 1.8

Signature:

STEPHEN J. FAUTSCH

Registration Number: A-11366 Date:

Registration Expiration: 7/31/14

8/13/13

Project For

2

NINTH LEVEL DEMOLITION PLAN 1/4" = 1'-0"

NORTH

FLOOR PLAN GENERAL NOTES

FLOOR PLAN LEGEND:

1. ALL EXPOSED PIPING AND CONDUIT SHALL BE PAINTED TO MATCH THE ADJACENT SURFACE.

EXISTING PARTITION TO REMAIN

2. ALL PLAN DIMENSIONS LOCATING INTERIOR WALLS ARE TO: a: FACE OF EXISTING WALL SYSTEM UNLESS NOTED OTHERWISE. b: FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE. c: CENTERLINE OF BUILDING GRID.

Franciscan Healthcare St. Francis Building Ninth Level PATIENT ROOM ADDITION FIT UP

EXISTING DOOR AND FRAME TO REMAIN

NEW PARTITON 3. SEE LIFE SAFETY PLANS, SHEETS FOR ALL RATED PARTITION LOCATIONS. PYXIS

PYXIS

PYXIS

4. EXISTING PENETRATIONS IN RATED PARTITIONS AND THRU FLOOR ASSEMBLIES TO BE FIRESTOPPED & SEALED. NEW MECHANICAL / ELECTRICAL PENETRATIONS TO BE FIRESTOPPED & SEALED. ALL SUBCONTRACTORS TO USE THE SAME FIRESTOPPING SYSTEM.

9-00B

5. SEE SHEET A301 FOR PARTITION TYPES

2.6

2.6

9-00B

5"

D2

4' - 9" V.I.F.

A1

4 1/4"

3' - 8"

3"

C1

2.10

2.9

3' - 6"

4 1/4"

C31-PL

A901

9-00A

4 1/4"

6 A901 8

1' - 2 3/4"

F1

2' - 10 1/2"

PATIENT ROOM 9-01

13

PATIENT ROOM 9-02

2.3

12' - 11 1/2"

2.2

G1

2.5

3"

2' - 4"

11

A901

F1

SIM.

9-02C

TYP

1

12

13

A901 SIM.

4' - 9 1/2"

2.3

9

5" 2' - 0"

F1

2.2

6 3/4"

TYP

Checked By

JHA 08/13/13

Revisions

2.6

No. 2.1

WORK RM

2.2 2.3 2.4

13' - 5 1/2" 2.5

3"

2.5

2.7

2.6 2.7 2.8 2.9 2.10

3"

2.7

D2

Date

Description

KEYNOTES - FLOOR PLAN

3' - 3"

3" 2' - 9 1/2"

D2

BCS

© Copyright RSP Architects 2012. All rights reserved.

9-03H

3' - 0"

2.7

Drawn By

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

2.4

16

3" 2.7

NEW PARTITION AS SCHEDULED

2045.002.03

Date

4 1/4"

2.7

5 A301

6 A301

D2

2.7

3' - 7"

3" 2.7

3' - 6 7/8"

D2

1

DOOR TAG

10 2.1

D2 D2

SPECIALITY EQUIPMENT TAG

D3

15

15

A901

1i

E1

14

+/-

2.5

D2

3"

9-01A

A

AREA N.I.C.

1' - 7"

14

2.4

G1

14' - 7"

2.7

2' - 2"

16

2.3

9-02A

5"

6' - 11 1/2"

2.4

2.2

2.1

9-01A

1/4" 5"

7

6 1/4"

E1

5

9-02

4 1/4"

10 1/4"

4

2.9

TOILET

11

EQUIPMENT TAG

101

E1

B1

1' - 9"

12

3

9-01

F1

F1

A1

11' - 6 1/4"

D3

C1

COUNTERTOP TAG

Project No.

TOILET

A901

4 1/4"

9-00A

2

9

A1

ROOM TAG

1i

2.1

8 3/4"

6' - 8"

11' - 6 1/4"

9-00

10' - 2"

5"

7. GENERAL CONTRACTOR TO COORDINATE INSTALLATION OF NEW ACOUSTICAL CEILING SYSTEMS WITH EXISTING BULKHEADS, SOFFITS AND OBSTRUCTIONS. VERIFY CONDITIONS WITH CM PRIOR TO INSTALLATION.

D2

11' - 6 1/4"

PATIENT ROOM

2.8

6' - 0 3/4"

5" 3' - 6"

2.1 10

2.1

E1

4 1/4"

4' - 10"

8 3/4"

D3

A1

4 3/4"

D3

1

3"

D2

B1

E1

9-00

TOILET

1' - 8"

2.10

1' - 9"

7 TYP A301 F1 6' - 6" 4 1/4"

E2

3"

Key Plan

KEYNOTE

2.1 2.1

3"

4' - 10"

ROOM NAME

6. NOTE: SOME OPENINGS REQUIRED TO BE PATCHED MAY EXIST ABOVE EXISTING ACOUSTICAL LAY IN CEILINGS. WHERE APPLICABLE, REMOVE CEILINGS AS NECCESSARY FOR PATCHING OF WALL AND REINSTALL UPON COMPLETION OF WORK.

2.6

LINEN HOLDING 7' - 6"

NEW DOOR, REFER TO DOOR SCHEDULE

D2

FACE OF NEW WALL TO BE ALIGNED WITH FACE OF EXISTING WALL. CENTERLINE OF HEAD WALL, HOSPITAL BED, AND PATIENT LIFT. CENTERLINE OF PATIENT LIFT. LIKO PATIENT LIFT - FLOOR SUPPORTED TRAVERSE STYLE (MODEL 250-550 LBS.) - LIFT SUPPLIER/INSTALLER TO PROVIDE ALL REQUIRED STRUCTURAL SUPPORTS REQUIRED - COORDINATE ALL OPTIONS WITH CONSTRUCTION MANAGER. HILROM HEADWALL SYSTEM - REGAL SERIES SURFACE MOUNTED 19" FLATWALL (INPRO - APPLEWOOD 0537) - COORDINATE ALL OPTIONS WITH CONSTRUCTION MANAGER. NO WORK IN THIS AREA. INSTALL NEW 5/8" GYPSUM BOARD OVER EXISTING STEEL STUDS. SHOWER PLAN AND ELEVATIONS - SEE DETAIL SH1/A901 SHOWER PLAN AND ELEVATIONS - SEE DETAIL SH4/A901 FULL HEIGHT PLASTIC LAMINATE NURSE SERVER CABINET COORDINATE EXACT SIZE WITH CM.

3 A301 TYP

NINTH LEVEL FLOOR PLAN 1/4" = 1'-0"

NORTH

NINTH LEVEL DEMOLITION PLAN AND FLOOR PLAN

A109 \\minfs02.rsparch.internal\RSPUsers$\jandring\Documents\SF09CENTRAL_jandring.rvt 8/9/2013 10:22:30 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


REFLECTED CEILING PLAN GENERAL NOTES: 1. GENERAL CONTRACTOR TO COORDINATE ALL WORK OF ALL TRADES INVOLVED IN THE CEILING WORK TO INSURE CLEARANCES FOR FIXTURES, DUCTS, PIPING, CEILING SUSPENSION SYSTEMS, ETC. NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED ON ARCHITECTS DRAWINGS. 2. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL PLUMBING, MECHANICAL DUCTS, STRUCTURAL ELEMENTS AND ANY OTHER APPLICABLE ITEMS. INSTALL NEW PLUMBING, MECHANICAL FANS, DUCTS, CONDUITS, AND OTHER RELATED ITEMS SO AS NOT TO CONFLICT WITH LUMINARIES.

2

3. VERIFY ALL RECESS DEPTHS OF FIXTURES AGAINST A.C. DUCTS, PIPES, BEAMS, ETC. BEFORE ORDERING FIXTURES. SUBMIT SHOP DRAWINGS OF ALL FIXTURES TO ARCHITECT AND ENGINEER FOR APPROVAL. 4. REMOVE ALL OBSTRUCTIONS FROM CEILING, INCLUDING ABANDONED CONDUITS, WIRES, DUCK WORK, ETC. NOT SCHEDULED FOR REUSE.

2

6. REFER TO ENGINEERING DRAWINGS FOR ALL LIFE SAFETY DEVICES REQUIRED BY CODE AND ALL EMERGENCY LIGHT FIXTURES. ARCHITECTURAL DRAWINGS SHALL GOVERN LOCATION OF THESE DEVICES.

2

OS 1

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

5. ALL SPECIFIC INFORMATION CONCERNING INSTALLATION OF VARIOUS ABOVE-CEILING ELEMENTS ARE TO BE FOUND IN HVAC, PLUMBING, FIRE PROTECTION, ELECTRICAL AND LIGHTING DRAWINGS. REFER TO ENGINEERING DRAWINGS FOR FULL WORK SCOPE ON DIFFUSERS, RETURNS, SPRINKLERS, LIGHT SWITCHES, THERMOSTATS, FIRE ALARMS, STROBES, ETC.

Consultants

7. NOTIFY ARCHITECT OF ANY CONFLICTS OF LIGHT FIXTURE LOCATIONS WITH MAIN CEILING GRID RUNNERS, DUCTS, STRUCTURES, HVAC AND/OR ELECTRICAL CONDUIT, PRIOR TO FRAMING FOR LIGHTS. ANY DISCREPANCIES BETWEEN ARCHITECT'S CEILING GRID LOCATION AND ACTUAL FIELD CONDITIONS ARE TO BE CLARIFIED WITH THE ARCHITECT PRIOR TO FRAMING.

4

4

8. INSTALL LIGHT FIXTURES WITH PROTECTIVE FILM OR SIMILAR COVER OVER LOUVER, LENS, BAFFLE, AND THE LIKE, TO AVOID FIXTURE SOILING OR DAMAGE. FIXTURES SHALL BE KEPT CLEAN AND AS NEW. LAMPS SHALL BE NEW AT PROJECT COMPLETION.

4

9. SWITCHES, THERMOSTATS, STROBES AND OTHER ELECTRICAL DEVICES ARE TO ALIGN ALONG THEIR CENTERLINE, WHEN DEVICES OCCUR IN THE PROXIMITY OF WALL OUTLETS. ALIGN OUTLETS WITH DEVICES ABOVE. 10. LIGHT FIXTURES, EXIT SIGNS, SPRINKLERS AND OTHER CEILING ELEMENTS SHALL BE LOCATED IN CENTER OF INDIVIDUAL CEILING TILE, U.N.O. OS

11. ALL SOFFITS AND CEILING HEIGHTS ARE DIMENSIONED FROM TOP OF FINISHED FLOOR TO BOTTOM OF GYB. BD. OR CEILING TILE AND SHALL ALLOW FOR THICKNESS OF ALL FLOOR FINISHES.

OS

5

1

12. FIRE SAFETY MUST BE MAINTAIN FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STARS, ALARMS, SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. NOTIFY BUILDING FACILITIES MANAGER OF DAMAGED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY.

5

OS 5

13. REMOVAL OF ANY EQUIPMENT, CABLING SWITCHES, AND CONDUIT PERTAINING TO DATA/COMMUNICATIONS AND TELEPHONE SHALL BE VERIFIED WITH TELEPHONE COMPANIES, SERVICE OWNER OR TENANT DATA/COMMUNICATIONS REPRESENTATIVE AS REQUIRED TO PREVENT NEW CONSTRUCTION DELAYS.

1

1

Certification

3

3

REFLECTED CEILING PLAN LEGEND 2

SD SD

SD

SPRINKLER HEAD

3

LIGHT FIXTURE - SEE ELECTRICAL

Signature:

EXIT LIGHT

Registration Number: A-11366

LIGHT FIXTURE - SEE ELECTRICAL V

SD

A

OC

4 A301

STEPHEN J. FAUTSCH

SPEAKER

Date:

Registration Expiration: 7/31/14

8/13/13

DIFFUSER - SEE MECHANICAL

Project For

SMOKE DETECTOR

LINEAR DIFFUSER - SEE MECHANICAL

FIRE ALARM

OCCUPANCY SENSOR

EXHAUST AIR GRILLE - SEE MECHANICAL

TYP NEW SUSP. CEILING TILE AND GRID SYSTEM RETURN AIR GRILLE - SEE MECHANICAL

1

EXISTING SUSP. CEILING TILE AND GRID SYSTEM TO REMAIN

NINTH LEVEL REFLECTED CEILING PLAN

Franciscan Healthcare St. Francis Building Ninth Level

RADIANT PANEL - SEE MECHANICAL

1/4" = 1'-0"

NORTH

PATIENT ROOM ADDITION FIT UP

KEYNOTES - REFLECTED CEILING PLAN 1 2 3 4 PYXIS

PYXIS

PYXIS

NEW (2x2) SUSPENDED ACOUSTICAL CEILING SYSTEM (ACT-1) AT 8'-0" A.F.F. NO WORK IN THIS AREA. DASHED LINE INDICATES PATH OF CURTAIN TRACK. NEW (2x2) SUSPENDED ACOUSTICAL CEILING SYSTEM, EXTENDED FROM EXISTING SUSPENDED ACOUSTICAL CEILING SYSTEM IN ADJACENT CORRIDOR. NEW (2x2) SUSPENDED ACOUSTICAL CEILING SYSTEM (ACT-2) AT 8'-0" A.F.F.

5

Key Plan

TAG LINEN HOLDING

A.18 A.24 A.30 A.36 A.42 A.65 B

9-00B

A.18

A.18

I

I

I

I

A.24 L

PATIENT ROOM

A.65

9-00

TOILET A.42

E

B

C

I A.36

A.24 D

H PATIENT ROOM

9-01

C

C

22" x 30" MIRROR

3

D

SOAP DISPENSER

3

E F G H I

PAPER TOWEL DISPENSER SHARPS CONTAINTER GLOVE DISPENSER HAND SANITIZER EMERGENCY NURSE CALL

3 3 3 3 6

J.1 J.2 K L

48" x 36" PATIENT INFORMATION WHITEBOARD 36" x 36" PATIENT INFORMATION WHITEBOARD PERSONAL PROTECTIVE EQUIPMENT CABINET S.S. SHELF

2 1 3 3

9-01A, 9-01B 9-01A, 9-01B 9-00A 9-00A 9-00A 9-00A 9-00A, 9-01A, 9-02A 9-00A, 9-01A, 9-02A 9-00A, 9-01A, 9-02A 9-00, 9-01, 9-02 9-00, 9-01, 9-02 9-00, 9-01, 9-02 9-00, 9-01, 9-02 9-00A, 9-01A, 9-02A 9-01, 9-02 9-00 9-00, 9-01, 9-02 9-00, 9-01, 9-02

INSTALLED BY

CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER

MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

CONSTRUCTION MANAGER

MANUFACTURE

CONTRACTOR

CONSTRUCTION MANAGER

MANUFACTURE

CONTRACTOR

CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER

MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER

MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

REMARKS

Project No.

2045.002.03

Drawn By

BCS

Checked By

JHA

Date

08/13/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2012. All rights reserved.

KEYNOTES - EQUIPMENT/FURNITURE PLAN

L

F

1 2

F J.1

2 4 2 1 1 1 3

E

9-02

L

J.2

QTY

B

G

H PATIENT ROOM

E

D

9-02A

G

C

F

TOILET

9-01A

D

H

9-00A

I

K

A.24

G

A.30

K TOILET

B

K A.30

A.24

DESCRIPTION 18" GRAB BAR 24" GRAB BAR 30" GRAB BAR 36" GRAB BAR 42" GRAB BAR 65" GRAB BAR TOILET PAPER DISPENSER

SPECIALTY EQUIPMENT SCHEDULE TO ROOM ORDERED BY SUPPLIED BY

FURNITURE TO BE PROVIDED BY OWNER. WARDROBE CLOSETS TO BE PROVIDED BY OWNER.

Revisions No.

Date

Description

J.1

WORK RM 9-03H

1

1

2

2

1

2

1

1 1

1 1

1

2

1

1

1

NINTH LEVEL REFLECTED CEILING PLAN

NINTH LEVEL EQUIPMENT/FURNITURE PLAN 1/4" = 1'-0"

NORTH

A209 \\minfs02.rsparch.internal\RSPUsers$\jandring\Documents\SF09CENTRAL_jandring.rvt 8/9/2013 10:22:30 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


DOOR SCHEDULE W 3' - 6" 3' - 6" 3' - 6" 3' - 6" 3' - 6" 3' - 6" 3' - 6"

H 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0"

TYPE F F F F F F F

MATL. WD WD WD WD WD WD WD

DOOR TYPES

FRAME TYPES

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

SEE SCHED

SEE SCHED

2"

3' - 0"

PAIR No No No No No No No

TYPE F1 F1 F1 F1 F1 F1 F1

MATL. HM HM HM HM HM HM HM

FRAME HEAD 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301

JAMB 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301

SILL -

SPECS. RATING HDWR. 45 MIN. H2 H3 45 MIN. H1 45 MIN. H2 H3 45 MIN. H2 H3

COMMENTS 4 7/8" 4 7/8"

H1

2"

2"

2 PAIR BUTTS STORE ROOM FUNCTION LOCKSET SURFACE CLOSER WALL STOP SMOKE GASKET KICK PLATE

7/16"

3/8" 7/16"

5 3/4"

NOTE: NO DOOR AT SIM CONDITION

F1

1

HOLLOW METAL FRAME

DOUBLE STUDS AT JAMBS (TYPICAL)

HOLLOW METAL FRAME

DOOR - SEE SCHEDULE

F - FLUSH

JAMB ANCHORS 3 PER JAMB

5/8"

2"

2 PAIR BUTTS HOSPITAL/PRIVACY LOCKSET OVERHEAD STOP

HEADER BY STEEL STUD SUPPLIER

5/8"

H3

7'-0"

SEE SCHEDULE

2 PAIR BUTTS PASSAGE FUNCTION LATCHSET WALL STOP SMOKE GASKET

7/16"

Consultants

7/16"

H2

3/8"

3/8"

3/8"

7'-0"

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

HARDWARE GROUPS:

3' - 0"

SEE SCHEDULE

SEE PLANS FOR PARTITION TYPE

SEE PLANS FOR PARTITION TYPE

2"

NO. 9-00 9-00A 9-00B 9-01 9-01A 9-02 9-02C

DOOR T 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4"

DOOR - SEE SCHEDULE

5 3/4"

NOTE: NO DOOR AT SIM CONDITION

TYPICAL DOOR HEAD DETAIL

2

3" = 1'-0"

TYPICAL DOOR JAMB DETAIL 3" = 1'-0" Certification

EXISTING EXTERIOR STONE SILL BELOW EXISTING VISION GLAZING EXISTING EXTERIOR STONE SYSTEM EXISTING EXTERIOR WALL INSULATION SYSTEM

EXISTING ALUMINUM WINDOW FRAME SYSTEM

Signature:

STEPHEN J. FAUTSCH

Registration Number: A-11366

1/2" SEALANT JOINT

Date:

Registration Expiration: 7/31/14

8/13/13

NEW FIRE TREATED 2X WOOD BLOCKING AS REQUIRED EXISTING 4" STRUCTURAL STEEL STUDS 5/8" GYPSUM BOARD

Project For

EXISTING 2X WOOD BLOCKING

EXISTING 4" STRUCTURAL STEEL STUDS 5/8" GYPSUM BOARD EXISTING SPANDREL GLAZING 1/2" SEALANT JOINT EXISTING ALUMINUM WINDOW FRAME SYSTEM

1/2"

4 5/8"

5/8"

3

WINDOW MULLION FINISH DETAIL

4

1 1/2" = 1'-0"

4 5/8"

WINDOW HEAD FINISH DETAIL 1 1/2" = 1'-0"

WALL TILE

WALL TILE

5/8" MOISTURE RESISTANT TILE BACKER BOARD

EXISTING REINFORCED CONCRETE SLAB

SHOWER PAN MEMBRANE, EXTEND UP WALL

EXISTING FIRESTOPPING AT FLOOR BELOW

FLOOR TILE

EXISTING 2X WOOD BLOCKING

FLOOR DRAIN FIRE STOP AROUND DRAIN LINE FLOOR TILE

EXISTING 4" STRUCTURAL STEEL STUDS EXISTING 2X WOOD BLOCKING

5/8" GYPSUM BOARD

5/8" GYPSUM BOARD

EXISTING EXTERIOR WALL INSULATION SYSTEM

1/2" SEALANT JOINT

EXISTING EXTERIOR STONE SYSTEM

EXISTING ALUMINUM WINDOW FRAME SYSTEM

4 5/8"

WINDOW SILL FINISH DETAIL

6

1 1/2" = 1'-0"

3/4"

EXISTING 4" STRUCTURAL STEEL STUDS

PATIENT ROOM ADDITION FIT UP

3/4" FIRE TREATED PLYWOOD

SHOWER PAN MEMBRANE, EXTEND UP WALL

3/4" FIRE TREATED PLYWOOD

1/2" SEALANT JOINT 1/2" SOLID SURFACE SILL

MORTAR FILL

5/8" MOISTURE RESISTANT TILE BACKER BOARD

EXISTING EXTERIOR STONE SYSTEM EXISTING EXTERIOR WALL INSULATION SYSTEM

EXISTING ALUMINUM WINDOW FRAME SYSTEM

5

WALL FRAMING - SEE FLOOR PLAN FOR PARTITION TYPES

WALL FRAMING - SEE FLOOR PLAN FOR PARTITION TYPES

1/2"

Franciscan Healthcare St. Francis Building Ninth Level

EDGE OF SHOWER TO START FLOOR SLOPE - SEE FLOOR PLAN

8"

4"

Key Plan

PROVIDE BLOCK-OUT IN SLAB TO ALLOW SLOPED FILL TO DRAIN VARIES

6"

1/2"

1' - 0"

MORTAR FILL

VARIES

WINDOW JAMB FINISH DETAIL

7

1 1/2" = 1'-0"

SHOWER BASIN DETAIL 1 1/2" = 1'-0"

Project No.

2045.002.03

Drawn By

BCS

Checked By

JHA

Date

PARTITION TYPES - STEEL STUD

08/13/13

SCALE: 1" = 1'-0"

TYPE A- FULL HEIGHT (1 HOUR RATED)

TYPE C - FULL HEIGHT SHAFT WALL (1 HOUR RATED) DESCRIPTION:

TYPE E - PARTIAL HEIGHT (TERMINATE AT 4" ABOVE CEILING)

DESCRIPTION:

DESCRIPTION:

5/8" MOISTURE RESISTANT TILE BACKER BOARD EXTEND TO FINISHED CEILING

5/8" TYPE 'X' GYPSUM BOARD

5/8" TYPE 'X' GYPSUM BOARD

METAL STUD AT 16" O.C.

© Copyright RSP Architects 2012. All rights reserved.

5/8" GYPSUM BOARD

Revisions

METAL STUD AT 16" O.C.

C-H SHAFT WALL STUDS AT 16" O.C.

METAL STUD AT 16" O.C.

5/8" GYPSUM BOARD

DESCRIPTION:

1" GYPSUM LINER PANEL

5/8" TYPE 'X' GYPSUM BOARD

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

TYPE G - FULL HEIGHT

WETSIDE

PTN TYPE

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

A1

3 5/8"

4 7/8"

U465

1 HR

STC RATING W/O W/ INSUL INSUL 40

NOTES

49

TYPE B - FULL HEIGHT (1 HOUR RATED)

PTN TYPE

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

C1

2 1/2"

3 1/8"

U438

1 HR

STC RATING W/O W/ INSUL INSUL

NOTES

TYPE D - FURRING (TERMINATE AT 4" ABOVE CEILING) DESCRIPTION: 5/8" TYPE 'X' GYPSUM BOARD METAL STUD AT 16" O.C.

No.

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

E1

3 5/8"

4 1/4"

NA

NA

40

49

E2

2 1/2"

3 1/8"

NA

NA

40

49

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

B1

3 5/8"

4 7/8"

U465

1 HR

STC RATING W/O W/ INSUL INSUL 40

49

PTN TYPE

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

G1

3 5/8"

4 7/8"

NA

NA

STC RATING W/O W/ INSUL INSUL 40

49

Description

NOTES

SEE DETAILS 1/A303, 2/A303, & 3/A303.

TYPE L - INFILL TO MATCH EXISTING

DESCRIPTION:

DESCRIPTION:

DESCRIPTION:

5/8" GYPSUM BOARD

5/8" GYPSUM BOARD

MATCH EXISTING ADJACENT WALL CONSTRUCTION SEE LIFE SAFETY PLANS FOR RATINGS

METAL STUD AT 16" O.C.

NOTES

NOTES

TYPE F - FULL HEIGHT (TERMINATE AT 4" ABOVE CEILING)

METAL STUD AT 16" O.C. ACOUSTIC SOUND BATT INSULATION

WETSIDE

5/8" MOISTURE RESISTANT TILE BACKER BOARD (WETSIDE) - EXTEND TO DECK

PTN TYPE

STC RATING W/O W/ INSUL INSUL

PTN TYPE

Date

5/8" MOISTURE RESISTANT TILE BACKER BOARD (WETSIDE) - EXTEND TO 4" ABOVE FINISHED CEILING

PTN TYPE

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

D3

3 5/8"

4 1/4"

NA

NA

D2

2 1/2"

3 1/8"

NA

NA

D1

1 5/8"

2 1/4"

NA

NA

STC RATING W/O W/ INSUL INSUL

NOTES

PTN TYPE

STUD WIDTH

PTN WIDTH

UL DESIGN

FIRE RATING

F1

3 5/8"

4 7/8"

NA

NA

STC RATING W/O W/ INSUL INSUL 40

NOTES

PTN TYPE:

STUD WIDTH:

PTN WIDTH:

UL DESIGN:

FIRE RATING:

STC: W/O W/ INSUL INSUL

NOTES:

49

DOOR SCHEDULE AND PARTITIONS TYPES

A301 \\minfs02.rsparch.internal\RSPUsers$\jandring\Documents\SF09CENTRAL_jandring.rvt 8/9/2013 10:22:31 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


5

3' - 6"

C

1

1

7

7

D

E

1

C

A.30

2

2 3

2

2

1/4" = 1'-0"

2

3

3

A.65

I

TOILET 9-00A1 - SOUTH

1

I

TOILET 9-00A1 - WEST

3

1/4" = 1'-0"

4' - 0"

A.65

J.2

4

6' - 6"

6' - 0"

A.30

E

2' - 10"

B

A.65

4' - 0"

4' - 0"

A.36

6' - 6"

6' - 6"

I

4 5/32"

A.30

2' - 10"

6"

A.42

L

1

TOILET 9-00A1 - NORTH

A.42

K B

6

6

A.36

TOILET 9-00A1 - EAST

4

1/4" = 1'-0"

3

6' - 6"

A.30

PATIENT ROOM 9-00A - SOUTH

5

1/4" = 1'-0"

6

1/4" = 1'-0"

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

PATIENT ROOM 9-00A - WEST 1/4" = 1'-0"

Consultants

D

I

A.24

I

6"

1

2

3

A.24

B

2' - 10"

6

I

4' - 0"

6' - 0"

4' - 0"

6

2' - 10"

H

C

A.24

6' - 6"

4

K

D

1

A.18

6' - 6"

F

8

E

B

E

L

3' - 6"

A.18

1

1

C G

A.24

6' - 6"

7

7

2

A.18

3

3

3

2

2 Certification

PATIENT ROOM 9-00A - NORTH

7

PATIENT ROOM 9-00A - EAST

8

1/4" = 1'-0"

9

1/4" = 1'-0"

TOILET 9-00B1 AND 9-00C1 - FIXTURE WALL

10

1/4" = 1'-0"

7

7

7

TOILET 9-00B1 AND 9-00C1 - SHOWER WALL

11

1/4" = 1'-0"

TOILET 9-00B1 AND 9-00C1 - MIRROR WALL 1/4" = 1'-0"

1 2 3

L J.1 K

K

4

6' - 6"

F

4 5

4

6 7 8

H

6

PATIENT ROOM 9-00B AND 9-00C CORRIDOR WALL

14

1/4" = 1'-0"

15

1/4" = 1'-0"

STANDARD ADA SHOWER DIMENSIONS (BASED ON 2003 ICC/ANSI GUIDELINES)

CEILING LINE

6"

PATIENT ROOM 9-00B AND 9-00C - T.V. WALL

16

1/4" = 1'-0"

CEILING LINE

6"

Date:

CEILING LINE

Franciscan Healthcare St. Francis Building Ninth Level

1' - 6"

PATIENT ROOM ADDITION FIT UP

SH5 G021 SH7

SHOWER CONTROL AREA

3' - 0"

SH6

CURTAIN ROD

Key Plan

2' - 0"

1' - 9"

6"

6' - 6"

6' - 8"

6"

10"

1' - 4"

6"

48"x36" CLEAR FLOOR SPACE

(SEE PLAN) 2' - 10"

6"

Project No.

1' - 6"

1' - 6"

2' - 10"

2' - 0"

2' - 10"

2' - 10"

2' - 10"

4' - 0"

6" 60"x36" CLEAR FLOOR SPACE (MIN.)

8/13/13

Project For

CEILING LINE

1' - 6" (SIDE WALL)

2' - 0"

SH2

Registration Expiration: 7/31/14

1/4" = 1'-0"

6"

6"

CURTAIN ROD

(SIDE WALL)

(SIDE WALL)

M IN .

SH3

STEPHEN J. FAUTSCH

Registration Number: A-11366

(BACK WALL)

6"

(BACK WALL)

3' - 6"

Signature:

PATIENT ROOM 9-00B AND 9-00C EXTERIOR WALL

CEILING LINE

3' - 6"

6"

SH2 A921 (SIM)

CERAMIC TILE BULLNOSED EDGE. CERAMIC TILE BASE - SEE ROOM FINISH SHEDULE. PROVIDE SHOWER PAN MEMBRANE IN ENITE ROOM, EXTEND UP WALL - SEE DETAIL X/AX. WARDROBE CABINET PROVIDED BY OWNER AND INSTALLED BY CONTRACTOR. FLAT SCREEN MONITOR AND MOUNTING BASE - PROVIDE BLOCKING FOR MOUNTING BASE AS SCHEDULED - SEE ROOM FINISH SCHEDULE PATIENT LIFT SYSTEM - SEE FLOOR PLAN HEAD WALL SYSTEM - SEE FLOOR PLAN

INFORMATION HERE IS FOR REFERENCE ONLY. ANY DIMENSIONS, NOTES, TEXT OR FINISHES ON ARCHITECTURAL PLANS OVERRIDES THE INFORMATION FOUND ON THIS SHEET.

SCALE: 1/2" = 1'-0"

6' - 6"

6

(SIDE WALL)

13

6

6

PATIENT ROOM 9-00B AND 9-00C - HEAD WALL

1/4" = 1'-0"

KEYNOTES - ELEVATIONS

G

L

TOILET 9-00B1 AND 9-00C1 - EXIT WALL

7

5 5

8

12

2045.002.03

Drawn By

BCS

Checked By

JHA

Date

SH1 36x78 ROLL-IN SHOWER

SH2 SIDE WALL ELEVATION

SH3 BACK WALL ELEVATION

SH4 36x42 ACCESSIBLE SHOWER

SH5 SIDE WALL ELEVATION

SH6 BACK WALL ELEVATION

08/13/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

SH7 SIDE WALL ELEVATION

© Copyright RSP Architects 2012. All rights reserved.

Revisions No.

ACCESSORY MOUNTING DIAGRAM FOR MINIMUM ADA GUIDELINES

Date

Description

INFORMATION HERE IS FOR REFERENCE ONLY. ANY DIMENSIONS, NOTES, TEXT OR FINISHES ON ARCHITECTURAL PLANS OVERRIDES THE INFORMATION FOUND ON THIS SHEET.

SCALE: 1/2" = 1'-0"

NOTE: REFER TO TOILET PLAN LAYOUT FOR GRAB BAR DIMENSIONS AND LAYOUT

1' - 0"

42" 3' -MIN. 6"

MAX.

CL

GRAB BAR HEIGHT

B

TOILET TISSUE DISPENSER

C

FRAMED MIRROR

D

SOAP DISPENSER

E

PAPER TOWEL DISPENSER

48" MAX.

1'-5"

18" MAX.

17" - 19"

2' - 10"

4' - 0"

48" MAX.

(3'-6" AT COUNTER)

4'-0" MAX. TO DISP. SLOT

TO SPOUT

36" - 48"

3'-4"

MEASURED TO BOTTOM OF VIEWING SURFACE

A

3'-4" MAX AT LAVATORY 2'-11" MAX AT FLOOR

30" - 33"

33" - 36"

7" - 9"

F

SHARPS CONTAINER

G

GLOVE DISPENSER

H

HAND SANITIZER

I

EMERGENCY NURSE CALL

K

TOILET SEAT HEIGHT

DETAILS AND INTERIOR ELEVATIONS L

SHOWER SEAT