SEC_SES301 manual

Page 1

SES301 Temperature Sensor – Z-Wave

Installation Instructions 1


SES301 SES301 is a battery-powered temperature sensor that uses Z-Wave速 technology low-power radio signals to transmit temperature data to a Controller. This product can be included and operated in any ZWave network with other Z-Wave certified devices from other manufacturers and/or other applications. All constantly powered nodes within the network will act as repeaters for the SES301, which will help to increase network reliability.

2


Installation and commissioning 1. Install the two AAA batteries supplied with the unit, taking care to observe the polarity markings. 2. To include the SES301 onto a network. Put the Controller in Include mode by pressing the button inside the unit for 2 seconds as shown in the diagram below. The Controller will show when the unit is linked. Button for Inclusion / Exclusion

3. Choose the position where the unit is to be mounted. Avoid locations alongside or behind large metal surfaces that could interfere with the low-power radio signals between the unit and the Controller. 3


4. The SES301 should be mounted on an internal wall, around 1.5 m above floor level and in a position away from draughts, direct heat and sunlight. 5. Make sure that there will be sufficient space around the unit to allow easy access to the two retaining screws on the base of the wall plate. 6. Fit the wall plate to the wall and then fit the SES301 on to the wall plate. Secure it in position by tightening the two captive screws. If the unit needs to be excluded from a network, put the Controller in Exclusion mode and press the button on SES301 for more than 2 second. The Controller indicates when the process is completed. 4


The device classes supported are given below. Z-Wave Device Classes Implemented Device Class Generic

Multilevel sensor

Specific

Routing Multilevel sensor

Basic

Routing Slave

Command Classes Supported

Description

Manufacturer Specific

Secure Manufacturer ID

Version

Provides the version number of the

Multilevel Sensor

Supports Multilevel Sensor GET and

software Multilevel Sensor REPORT. The report carries the measured temperature as a 2byte signed number (in 째C or 째F) with a precision of 1 decimal place. The report can be requested (or sent unsolicited) to the nodes in Group 1. 5


Battery Level

Supports GET and REPORT, for battery level in the range 0-100%. Low Battery Warning is reported (with parameter = 0xFF) to the nodes in Group 2 if the battery voltage is less than 2.5 volts.

Wake Up(Ver 2)

Wake Up Capabilities Report, supports wake up intervals in steps of 10s, with a default setting to 24 hrs, any received out of range wake up interval will be ignored.

Basic

Mapped to the Multilevel Sensor Command Class as follows: o Basic SET: Not Supported o Basic GET: Multilevel Sensor Get o Basic REPORT: Multilevel Sensor Report

Association

Two association groups are supported: Group 1 - Nodes to receive unsolicited multilevel sensor report. Group 2 - Nodes to receive unsolicited low battery warnings report. Each group contains a maximum of 4 nodes conti...

6


Configuration

Two single-byte configurations are supported for the temperature sensor functionality 1. Configuration Parameter Number 1, temperature scale: a. 0 to 127 (0x00-0x7F) = Celsius b. - 1 2 8 t o - 1 ( 0 x 8 0 - 0 x F F ) = Fahrenheit c. Default value is 0 2. Configuration Parameter Number 2, delta temperature: a. Can set in the range 1 to 100, in 0.1 degree steps b. Default value is 10 (1.0 ºC).

Note:

To preserve battery life in a wider system, it is recommended that minimum default values are set for the following parameters: Ÿ Wake up Interval: 15 Minutes (min) Ÿ Temperature Report: Δ0.5°C (min) and/or Wake up (15 Mins)

7


Note: All command classes are version 1 unless otherwise stated. Technical Information Dimensions (WxHxD)

86 x 86 x 30 mm Power supply

Measurement accuracy

±0.5 °C

Transmitter frequency

868 Mhz

Pollution control degree

2

Design standard

EN 60730-2-9

Enclosure protection

Ip30

Operating range

0 °C to +40 °C

Enclosure material

Flame-retardant thermoplastic

2 x AAA alkaline cells

Cewe Instrument AB Box 1006 611 31 Nyköping Tel: +46 8 600 80 60 Email: info@securetogether.eu Web Site: www.securetogether.eu Part Number P84268 Issue Number 3


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.