porch,shep

Page 1

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360

Bill & Kim Sheppard

2644 Woodwin Road Doraville, Georgia 30360

Austin Foster, C.R.- Owner Joe Bryant, C.L.C. - Project Manager Jenny Burger - Design Manager & C.A.D. Technician

Date: Signature:

- . ) /

Date:

DESIGN MANAGER & CAD TECHNICIAN

770-234-0911 www.constructionahead.net

Signature:

Index of Architectural Drawings Sheet # Sheet # 13 Sandy Springs Notes 1 Title Page 2 Existing Porch Slab Floor Plan 14 15 3 New Porch Floor Plan 4 Fireplace Detail 5 Porch Elevation 6 Arch Detail 7 Elevation Fireplace 8 Footing Detail 9 Pneumatic Lift Detail for Picture Frame 10 Ceiling Framing 11 Roof Framing 12 Site & Survey Plan

770-234-0911 www.constructionahead.net

Home: 404-8743-0447

)* +,* % PRESIDENT & OWNER

(Porch Addition)

405 Winfield Glen Ct NE Atlanta, GA 30342

! " " $ %&'( (

#

!


20' SET BACK

11'-11"

Existing Concrete Patio

24'-1"

Existing Sheppard Plan

Scale: 5/16" = 1' - 0" ! " "

$ %&'( (

#

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


2889

Cover Existing Concrete Slab with Tennesee Blue-Stone. InstallStanding Seam Metal Roof. Tongue and Groove Coffered Ceiling. 8"x8" Coffered Ceiling Beams Extend Slab 2'-4" Deep Radius & Cover with Tennesse Blue Stone

6'-9"

6'-9" Cut Existing Slab Under 10"x10" Column Areas and Construct 24"x24"x12" Footings to Support the Columns.

770-234-0911 www.constructionahead.net

Construct 16" Tall Hearth with Fireplace covered with stoneHeatilator Gas Logs42" Direct Vent-Novus NDV4236 Leave 1" Minium Between Fire Box and Wall. Install Vent on Top of Fire Box with 90 Degree Elbow Exiting to Right Wall. Please Read Heatilator's Installation Instructions.

Date:

Date: Signature:

Arch

DESIGN MANAGER & CAD TECHNICIAN

Arch

Arch

- . ) /

6'-9"

WP

Signature:

Arch

Sconce

)* +,* % PRESIDENT & OWNER

Roof Ridge Top Height Conndecting to House 174" from Slab12" Roof Overhang

10" x 111" Square Columns-Installed 6'-9" apartWrap Bottom Perimeter with 8" Tall Base Moulding. Wrap Top of Column with 5" TALL Crown.

Columns Installed 2" in from Slab Edge

Ceiling Fans Include Light Kits Lower Fan Height Blade no Lower than 84"

Ceiling Height: 144"

5'-3/4"

2'-4"

11'-0"

WP

5"

CURVED BUILT-IN STONE PLANTER18" TALLX16"DEEP

SE TB AC K

Extend Radius Slab & Cover With Tennessee Blue Stone

WP

Arch

20 '

4'-0"

5'-3/4"

Free Standing Grill

4'-6" WP

1'-0"

5'-0" 11'-9"

CURVED BUILT-IN STONE PLANTER18" TALLX16"DEEP

Existing GAS

WP

1'-4"

Bib (no kink)

4'-0" HB

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360

24'-0"

19'-7"

! " " $ %&'( (

Scale: 5/16" = 1' - 0"

#


Scale: 3/4" = 1' - 0"

)* +,* % PRESIDENT & OWNER

$ %&'( (

! " "

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360

770-234-0911 www.constructionahead.net

#

Date:

Signature:

DESIGN MANAGER & CAD TECHNICIAN

- . ) /

Date:

Signature:

16" TALL CURVED HEARTH-

1'-4"

1'-7"

6" 10" 1 ' -5 " Construct 16" Tall Hearth with " Fireplace covered with stone-6 3' Heatilator Gas Logs" 42" Direct Vent-Novus NDV4236 -8 " 1' 5" 1 Grill Leave 1" Minium Between -1 11 1' Vent Fire Box and Wall. " Install Vent on Top of Fire Box with 90 Degree Elbow Exiting to Right Wall. Please Read Heatilator's Installation Instructions.

6'-9"

10"


10'-0" Install New Slab Covered with Tennesse Blue Stone

Install New Stone Planters

1'-6" 4'-0" Existing Brick

Install Tennesse Blue Stone Over Existing Slab

Porch Elevation

9"

2'-9"

9'-3"

6" Tall Crown Moulding

DESIGN MANAGER & CAD TECHNICIAN

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360

770-234-0911 www.constructionahead.net

#

$ %&'( (

! " "

- . ) /

Date:

Signature:

Date:

Signature:

5" Tall Crown Moulding

12'-0" 14'-6"

10" x111" Columns

)* +,* % PRESIDENT & OWNER

6"

1'-4"

Scale: 1/4" = 1' - 0"

Build Gas Fireplace & 8" Tall Base Moulding Cover with Stone

7'-3"


1'-0"

Roof Over-Hang

8"x8"x Coffered Ceiling Beam Painted White

2x4's 12" O.C.

8"x3/4" Siding Used to Forn Underside of Arch 1/4" Reveal

0

#

$ %&'( (

! " "

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360

770-234-0911 www.constructionahead.net

Standing Seam Metal Roof to Match Bay Window Roof Tongue & Groove Ceiling Painted White 2x8's

8" 2x8's

10"

DESIGN MANAGER & CAD TECHNICIAN

- . ) /

Date:

Signature:

Date:

Signature:

5/8" HardyBoard

Two 2x8's Stacked Vertically with Horiontal 2x8's Above & Below

10"x111" Column

Scale: 3/4" = 1' - 0"

)* +,* % PRESIDENT & OWNER

6" 5"

Arch Detail

2'-9"

3"

8"

From Ceiling to Arch Top

1'-5"

5'-1"


Stone Mantle

2'-6"

Frame

4'-0"

5"

2'-10" 5'-0" 5'-9"

Construct TV Box with 1/2" Thick Material.

TV Dimensions: 31 1/4" Wide x 22" Tall x 4 1/2" Deep

Scale: 3/4" = 1' - 0"

1'-4"

Cut-Out: 39" x 28" x 9"

69" A.F.F.

3'-6" 6"

12'-0" ! " "

$ %&'( (

#

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


Scale: 1" = 1' - 0" ! " "

$ %&'( (

#

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


Pneumatic Lift System NOT to Scale ! " "

$ %&'( (

#

1

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


12'-4"

4'-6"

Blocking for Tongue & Groove Ceiling

25'-3"

2"x8" Ceiling Joist 16" OC

Sheppard Ceiling Framing Plan

Scale: 3/8" = 1' - 0"

7'-9"

! " "

$ %&'( (

#

!

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


1 13/16" Roof Pitch 174" Ridge Height from Slab 144" Ceiling Height 12" Roof OverhangInstall Standing Seam Metal Roof to Match Bay Window Roof. Tongue and Groove Coffered Ceiling.

25'-7"

25'-2"

12'-4"

Sheppard Roof Framing

8" Deep Arches 12" Roof Overhang

$ %&'( (

! " "

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360

770-234-0911 www.constructionahead.net

#

!!

Date:

Signature:

DESIGN MANAGER & CAD TECHNICIAN

- . ) /

Date:

Signature:

13" 14' 45°

2"x10" Hips 2"x6" Rafters 16" O.C. 5/8" CDX Plywood for Roof Sheathing 2x8 Ceiling Joist

Scale: 3/8" = 1' - 0"

)* +,* % PRESIDENT & OWNER

12'-8" 4"


Extend Patio Slab and Cover with Stone- 281 SqFt Install Porch Roof Over Existing Slab. 230 SqFt. TOTAL: 511 Square Feet Tree Save

Silt Fence

! " "

$ %&'( (

#

!

Area of Construction

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


2007 SANDY SPRINGS GA RESIDENTIAL CODE COMPLIANCE NOTES REV. 0 “SANDY SPRINGS, GA RESIDENTIAL CODE COMPLIANCE NOTESâ€? Reflecting the 2006 IRC with Georgia State Amendments (Effective January 01, 2007): • Governing Building Codes: All construction shall comply with the City of Sandy Springs Code of Ordinances, Chapter 9, Article 1, Section 1. The governing code is the 2006 International Residential Code with 2007 GEORGIA STATE Amendments. Unless indicated otherwise, code references contained herein are to the 2006 IRC with GEORGIA STATE Amendments. • Manufacturer’s installation instructions, as required by this code, shall be available on the job site at the time of inspection (R106.1.2). • Exterior wall, bottom sill plates, shall be pressure treated or equal, and shall bear/extend minimum 8 inches above finish grade. (R319.1). • All exits to be operable from the inside without the use of a key or special knowledge (R310.1.4 and 311.4.4). • Doors leading into the house from the garage shall be 1 3/8â€? thick solid core, honey comb core steel door, solid wood or 20 minute firerated door. (R309.1). • IRC R309.2 (amended): Provide 1/2 inch gypsum board applied to the garage side for separation from garage for attic and residence. Garages beneath habitable rooms shall be separated from all habitable rooms by not less than 5/8â€? Type X gyp board or equivalent. Where the separation is a floor-ceiling assembly, the structure supporting the separation shall also be protected by not less than 1/2 inch gypsum board or equivalent. DCA amendments allow installation of an automatic sprinkler system for protection in garage in lieu of separation (2007). • Provide roof attic ventilation per R806.1. • Lumber shall bear an approved grading stamp (R502.1 and 319.1). • Fire blocking shall comply with (R602.8) and be maximum 10 ft. O.C., horizontal or vertical. • Floor-ceiling assemblies with a concealed space in excess of 1000 square feet shall have draft stops installed that divide the concealed space into approximately equal areas (R502.1.2). Draft-stopping material shall comply with (R502.12.1). • Walls and soffits of enclosed usable space under interior stairways shall be protected on the enclosed side by minimum ½â€? gypsum board. (R311.2.2) • Gypsum board applied to a ceiling with water-based texturing, shall be 1/2â€? when framing members are 16â€? o.c. or 5/8â€? when framing members are 24â€? o.c. or use labeled 1/2â€? sag-resistant gypsum ceiling board. (Table R702.3.5 (d)). • Shower area walls shall be finished with a smooth, hard non-absorbent surface, such as adhesive application of ceramic tile, to a height of not less than 72 inches above the floor (R307.2). When gypsum wallboard is used as a base for tile or wall panels, water-resistant gypsum wallboard shall be used. Water-resistant gypsum board shall not be used over a vapor retarder, in areas of high humidity or on ceilings where the frame spacing exceeds 12 inches on center for ½ gypsum, and 16 inches on center for 5/8 gypsum. (R702.3.8). Cement, fiber-cement and glass mat gypsum backers in compliance with ASTM C 1288, C 1325, or C 1178 shall be used for wall tile in tub and shower areas and wall panels in shower areas. (R702.4.2) • Plumbing fixtures shall comply with the following conservation requirements: o Water closets-Tank type = 1.6 gal. /flush. o Shower heads- 2.75 gal. /minute. o Faucets- 3.0 gal. /minute, provide aerator. • Provide an expansion tank or check valve for the water heater if a backflow preventer is or will be installed on the water line or at the meter. (IPC607.3). • Showers and tub-shower combinations shall be provided with individual control valves of the pressure balance or thermostatic mixing valve type. (IPC 424.3) • Domestic dishwashing machines connected to a disposer shall have the discharge installed as high as possible, but not lower than 2â€? above the flood rim of the sink. (IPC 802.1.6) • Provide minimum clearances from centerline of water closets to finished wall, cabinets, and other plumbing fixtures. (R307.1) • The clothes dryer shall be provided with a 4-inch diameter exhaust duct to the exterior and shall not exceed a total length of 25 feet, unless an engineered duct system is provided. (M1502.6) The duct shall terminate not less than 3 feet from a property line or from openings into a building (Table R302.1, R303.4 and R303.5). • Provide outside combustion air for fireplaces located in bedrooms. (M1701.4) • Provide required elevation, for mechanical equipment’s ignition source, water heaters and appliances if placed in garage or room with direct access to garage of 18 inches above the floor. (M1307.3). • Provide combustion air and provide high and low vent sizes for gas fuel appliances located in confined spaces. (M1702.2, and M1703.2) • Location of smoke detectors shall comply with IRC 313. • Provide IC-rated recessed light fixtures installed in insulated ceilings. (NEC 110.3(B), 41.66(B)). • Fixtures located in damp or wet locations shall be “listedâ€? to be suitable for such location. (NEC 410.4) • Provide GFCI protection for receptacles within 6’ of all lavatories, sinks and basins. (NEC 210.8) • All kitchen counter receptacles shall be GFCI protected. (NEC 210.8(6) 2007 SANDY SPRINGS GA RESIDENTIAL CODE COMPLIANCE NOTES REV. 0 • Provide GFCI protected receptacles at all exterior, bathroom and garage locations. (NEC 210.8 & 210.52.) • Provide a wall mounted GFCI protected receptacle outlet within 36â€? of a bathroom or powder room lavatory. (NEC 210.52(D)) • All circuits supplying receptacle outlets in bedrooms shall be AFCI (Arc-Fault Circuit Interrupter) protected. (NEC 210.12) • Receptacle outlets shall be installed so that no point along the floor line in any wall space is more than 6 feet, measured horizontally, from an outlet in that space, including any wall space 2 feet or more in width. (NEC 210.52 (A)) • Bathroom receptacle outlets shall be supplied by at least one 20-ampere branch circuit. Such circuits shall have no other outlets. (NEC 210.52 (D)) • Provide a separate 20-ampere branch circuit to the laundry. (NEC 210.11(C), 210.23 (A), 210.50 (C), 210.52(F & G), 220.14(J)) • Provide a minimum of two 20-amp small appliance branch circuits for the kitchen/dining/breakfast. (NEC 210.11(C)(1), 210.52(B)(1), 220.14(J)) • The two or more 20-ampere small appliance branch circuits shall have no other outlets, except the receptacle installed solely for electric supply to an electrical clock in the kitchen/dining/breakfast areas or receptacles for supplemental equipment and lighting for gas-fired ranges, ovens, or counter-mounted units. (NEC 210.52 (B)(3)) • Receptacle outlets for ranges and clothes dryers shall be a 3-pole with ground type. Four-wire, grounding-type flexible cords will be required for connection of ranges and clothes dryers. The bonding jumper shall not be connected between the neutral terminal and the frame of the appliance. (NEC 250.140 & 250.142) • Provide bonding to the water piping, gas and metal building systems. (Minimum #4 for 200-amp service). (NEC 250.50, 250.104 & 250.52) • All metal piping systems, metal parts of electrical equipment, and pump motors associated with the hydro massage tub shall be bonded together using a copper bonding jumper, insulated, covered, or bare, not smaller than No. 8 solid. Metal parts of listed equipment incorporating an approved system of double insulation and providing a means for grounding internal non-accessible, non-currentcarrying metal parts shall not be bonded. (NEC 680.62) • For new windows, windows being replaced or windows affected by modifications elsewhere they shall be compliant with IRC R310: “Basements with habitable spaces and every sleeping room shall have at least one openable emergency escape and rescue window or exterior door opening for emergency escape and rescue. When openings are provided . . . . they shall have a sill height of not more than 44 inches above finished floor. Where a door opening having a threshold below the adjacent ground elevation serves as an emergency escape and rescue opening and is provided with a bulkhead enclosure, the bulkhead enclosure shall comply with R310.3. The net clear opening dimensions required by this section shall be obtained by the normal operation of the window or door opening from the inside. Escape and rescue window openings with a finished sill height below the adjacent ground elevation shall be provided with a window well in accordance with R310.1. Minimum escape and rescue opening dimension shall be a net clear opening of 5.7 square feet, except at grade floor where the net clear opening shall be a minimum of 5 square feet. R310.1.2 Minimum net clear opening height shall be 24 inches.â€? R310.1.3 Minimum net clear opening width shall be 20 inches. R310.1.4 Emergency escape and rescue openings shall be operational from the inside of room without the use of keys or tools. • Provide mechanical exhaust ventilation for bathrooms, water closet rooms, laundry room, and kitchen, ducted direct to outside. (R303.4 to R303.5) • The soil load-bearing capacity shall be presumed to be 2,000 psf max., unless a Geotechnical Investigation, properly stamped by a Professional Engineer registered in the State of Georgia, substantiates the noted bearing capacity (Table R401.4.1). • The wood floor system drawings, stamped/noted as reviewed by DPoR, must be available on site PRIOR to erecting. A floor framing drawing using the floor system nomenclature is required (R502.8.2). • Pressure treated wood in contact or close proximity to metal, including fasteners. With the removal of CCA treated lumber, most of the lumber available locally is treated with ACQ and CBA treatments. These treatments are more than twice as corrosive as CCA. Sandy Springs Building Inspectors will look for connectors and fasteners that are hot-dipped zinc-coated galvanized steel in accordance with ASTM A153, stainless steel, silicon bronze or copper (with exceptions) in contact with pressure treated wood (R319.3). • Foundation drainage will be in accordance with Section R-405 of IRC. • All foundation walls of below grade space which may be occupied shall be waterproofed to allow for future use as habitable space (i.e. finished basement). The membranes shall extend from the edge of the footing to the finished grade (R-406.1). Note method of waterproofing to be used on basement walls. Exception: Poured concrete foundation walls require dampproofing only (R406.2). • If pre-engineered wood trusses are used in floor framing, provide truss drawings which identify member sizes to be used. Wood trusses shall be designed in accordance with approved engineering practice (Sec. R-502.11). If manufactured trusses are to be used, the truss supplier’s detailed drawings for the project shall be available at the job site, prior to erection. • If pre-engineered wood trusses are used in roof framing, provide truss drawings. Wood trusses shall be designed in accordance with approved engineering practice (Sec. R-802.10). If manufactured trusses are to be used, the truss supplier’s detailed drawings for the project shall be available at the job site, prior to erection.

! " "

$ %&'( (

#

!

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


! " "

$ %&'( (

#

!

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


! " "

$ %&'( (

#

!

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


! " "

$ %&'( (

#

!0

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


! " "

$ %&'( (

#

!

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360


! " "

$ %&'( (

#

!

)* +,* % PRESIDENT & OWNER Signature:

- . ) /

Date: DESIGN MANAGER & CAD TECHNICIAN 770-234-0911 www.constructionahead.net

Signature:

Date:

2644 WOODWIN ROAD DORAVILLE, GEORGIA 30360