BS 5308 Part 1 Type 2 multipairs instrumentation cables

Page 1

ADDISON PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC PVC Outer Sheath Tinned Copper Drain Wire AL/HDPE Tape PVC Inner Sheath PE Insulation Plain Annealed Copper Aluminium/polyester Tape Galvanized Steel Wire Armour

APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.

STANDARDS Basic design to BS 5308 Part 1 Type 2

FIRE PERFORMANCE EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE Flame Retardance (Single Vertical 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test)** CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test)** CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING 300/500V

CABLE CONSTRUCTION Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228. Insulation: PE compound.

2

Caledonian


Caledonian

NON-IS & IS Instrumentation Cables

www.caledonian-cables.co.uk

www.caledonian-tech.net

Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm Binder tape: PETP transparent tape Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm². Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound Amouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: NON-IS Cable: Black IS Cable: Blue

Physical AND THERMAL PROPERTIES Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter

Electrical PROPERTIES Conductor Area Size

mm2

1.0

1.5

2.5

Conductor Stranding

No. x mm

1 x 1.13

7 x 0.53

7 x 0.67

Conductor Resistance Max

ohm/km

18.2

12.3

7.58

Insulation Resistance Min

MΩ/km

500

500

500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen)

pF/250m

Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)

pF/m

75

85

85

Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs)

pF/m

115

120

120

μH/ohm

25

40

65

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen Rated Voltage Max

250

V

1000

V

1000

V

300/500

300/500

300/500

ADDISON

3


ADDISON CONSTRUCTION PARAMETERS RE-2Y(St)MSYSWAY Nominal Cable Code

Insulation Thickness mm

RE-2Y(St)MSYSWAY 1×2×1.0

0.6

RE-2Y(St)MSYSWAY 1×2×1.5

0.6

RE-2Y(St)MSYSWAY 1×2×2.5

0.6

RE-2Y(St)MSYSWAY 2×2×1.0

0.6

RE-2Y(St)MSYSWAY 2×2×1.5

0.6

RE-2Y(St)MSYSWAY 5×2×1.0

0.6

RE-2Y(St)MSYSWAY 5×2×2.5

0.6

RE-2Y(St)MSYSWAY 10×2×1.0

0.6

RE-2Y(St)MSYSWAY 10×2×2.5

0.6

RE-2Y(St)MSYSWAY 12×2×1.0

0.6

RE-2Y(St)MSYSWAY 12×2×2.5

0.6

RE-2Y(St)MSYSWAY 20×2×1.0

0.6

RE-2Y(St)MSYSWAY 20×2×2.5

0.6

Nominal

Nominal

Inner

Outer

Sheath

Sheath

Thickness

Thickness

mm

mm

Note : Other conductor sizes & core configurations are available upon request. 300/500V

Rated Voltage

4

N BS 5308

Standard

Caledonian

Reduced Fire Propagation** Flame Retardancy** NF C32-070-2.2(C1) NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1 IEC60332-3-24/EN50266-2-4

Nominal Overall Diameter mm

Approx. Weight

kg/km


Caledonian

NON-IS & IS Instrumentation Cables

www.caledonian-cables.co.uk

www.caledonian-tech.net

PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

PVC Outer Sheath Tinned Copper Drain Wire AL/HDPE Tape PVC Inner Sheath PE Insulation Plain Annealed Copper Aluminium/polyester Tape Galvanized Steel Wire Armour

APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.

STANDARDS Basic design to BS 5308 Part 1 Type 2

FIRE PERFORMANCE EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE Flame Retardance (Single Vertical 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test)** CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test)** CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING 300/500V

CABLE CONSTRUCTION Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228. Insulation: PE compound.

ADDISON

5


ADDISON Triple: Three conductors twisted to form a triple. Binder tape: PETP transparent tape Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm². Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound Amouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: NON-IS Cable: Black IS Cable: Blue

Physical AND THERMAL PROPERTIES Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter

Electrical PROPERTIES Conductor Area Size

mm2

1.0

1.5

2.5

Conductor Stranding

No. x mm

1 x 1.13

7 x 0.53

7 x 0.67

Conductor Resistance Max

ohm/km

18.2

12.3

7.58

Insulation Resistance Min

MΩ/km

500

500

500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen)

pF/250m

Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)

pF/m

75

85

85

Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs)

pF/m

115

120

120

μH/ohm

25

40

65

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen Rated Voltage Max

6

Caledonian

250

V

1000

V

1000

V

300/500

300/500

300/500


Caledonian

NON-IS & IS Instrumentation Cables

www.caledonian-cables.co.uk

www.caledonian-tech.net

CONSTRUCTION PARAMETERS RE-2Y(St)MSYSWAY Nominal Cable Code

Insulation Thickness mm

RE-2Y(St)MSYSWAY 7×3×1.0

0.6

RE-2Y(St)MSYSWAY 10×3×1.5

0.6

RE-2Y(St)MSYSWAY 20×3×2.5

0.6

Nominal

Nominal

Inner

Outer

Sheath

Sheath

Thickness

Thickness

mm

mm

Nominal Overall Diameter mm

Approx. Weight

kg/km

Note : Other conductor sizes & core configurations are available upon request. 300/500V

Rated Voltage

N BS 5308

Standard

Reduced Fire Propagation** Flame Retardancy** NF C32-070-2.2(C1) NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1 IEC60332-3-24/EN50266-2-4

ADDISON

7


ADDISON Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipairs) RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

PVC Inner Sheath Aluminum/Polyester Tape With Tinned Copper Drain Wire Mica Tape+PE Insulation Plain Annealed Copper AL/HDPE Tape

Galvanized Steel Wire Armour PVC Outer Sheath

APPLICATION The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.

STANDARDS Basic design to BS 5308

FIRE PERFORMANCE Circuit Integrity Circuit Integrity with mechanical shock Circuit Integrity with mechanical shock & water spray System Circuit Integrity

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) EN 50200(PH30); CEI 20-36/4-0 EN 50200 annex E DIN 4102-12, E30 depending on lay system

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; Flame Retardance (Single Vertical VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test) CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test) CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; Halogen Free CEI 20-37/2-1 ; BS 6425-1*

8

Caledonian


Caledonian

NON-IS & IS Instrumentation Cables

www.caledonian-cables.co.uk

www.caledonian-tech.net

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

CABLE CONSTRUCTION Conductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2. Insulation: Mica glass tape covered by PE compound. Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm Overall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire. Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound. Armouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

VOLTAGE RATING 300/500 V

COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: Orange (other colours on request)

Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 10 x Overall Diameter

Electrical PROPERTIES Conductor Area Size Conductor Stranding

mm2

1.0

No. x mm 1 x 1.13

1.5

2.5

4.0

7 x 0.53

7 x 0.67

7 x 0.85

Conductor Resistance Max

ohm/km

18.2

12.3

7.58

Insulation Resistance Min

MΩ/km

500

500

500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen) Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)

pF/250m pF/m

250 75

85

85

ADDISON

9


ADDISON Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs) Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen

pF/m

115

120

120

μH/ohm

25

40

65

Rated Voltage Max

V

1000

V

1000

V

300/500

300/500

300/500

300/500

CONSTRUCTION PARAMETERS RE-m2Y(St)MSYSWAY Nominal Cable Code

Insulation Thickness mm

RE-m2Y(St)MSYSWAY 5×2×1.0

0.6

RE-m2Y(St)MSYSWAY 5×2×1.5

0.6

RE-m2Y(St)MSYSWAY 5×2×2.5

0.6

RE-m2Y(St)MSYSWAY 5×2×4.0

0.6

RE-m2Y(St)MSYSWAY 10×2×1.5

0.6

RE-m2Y(St)MSYSWAY 10×2×2.5

0.6

RE-m2Y(St)MSYSWAY 10×2×4.0

0.6

RE-m2Y(St)MSYSWAY 20×2×1.5

0.6

Nominal

Nominal

Inner

Outer

Sheath

Sheath

Thickness mm

Thickness mm

Note : Other conductor sizes & core configurations are available upon request. 300/500V

Rated Voltage

N BS 5308

Standard

W

E

Circuit Integrity Flame Retardancy Reduced Fire Propagation IEC 60331/BS 6387 NF C32-070-2.2(C1) NF C32-070-2.1(C2) EN 50200 NF C32-070-2.3(CR1) IEC60332-3-24/EN50266-2-4 IEC60332-1-2/EN50265-2-1

Zero

Low Toxicity NES 02-713/NF C 20-454

10

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Caledonian

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073

Halogen Free IEC60754-1 EN50267-2-1

W

E

Functional Integrity DIN 4102-12

Nominal Overall Diameter mm

Approx. Weight kg/km


Caledonian

NON-IS & IS Instrumentation Cables

www.caledonian-cables.co.uk

www.caledonian-tech.net

Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple) RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

PVC Inner Sheath Aluminum/Polyester Tape With Tinned Copper Drain Wire Mica Tape+PE Insulation Plain Annealed Copper AL/HDPE Tape

Galvanized Steel Wire Armour PVC Outer Sheath

APPLICATION The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.

STANDARDS Basic design to BS 5308

FIRE PERFORMANCE Circuit Integrity Circuit Integrity with mechanical shock Circuit Integrity with mechanical shock & water spray System Circuit Integrity

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) EN 50200(PH30); CEI 20-36/4-0 EN 50200 annex E DIN 4102-12, E30 depending on lay system

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; Flame Retardance (Single Vertical VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test) CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test) CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; Halogen Free CEI 20-37/2-1 ; BS 6425-1*

ADDISON

11


ADDISON No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

CABLE CONSTRUCTION Conductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2. Insulation: Mica glass tape covered by PE compound. Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm Overall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire. Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound. Armouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

VOLTAGE RATING 300/500 V

COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: Orange (other colours on request)

Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 10 x Overall Diameter

Electrical PROPERTIES Conductor Area Size Conductor Stranding

1.0

No. x mm 1 x 1.13

1.5

2.5

4.0

7 x 0.53

7 x 0.67

7 x 0.85

Conductor Resistance Max

ohm/km

18.2

12.3

7.58

Insulation Resistance Min

MΩ/km

500

500

500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen)

12

mm2

Caledonian

pF/250m

250


Caledonian

NON-IS & IS Instrumentation Cables

www.caledonian-cables.co.uk

www.caledonian-tech.net

Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)

pF/m

75

85

85

Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs)

pF/m

115

120

120

μH/ohm

25

40

65

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen Rated Voltage Max

V

1000

V

1000

V

300/500

300/500

300/500

300/500

CONSTRUCTION PARAMETERS RE-m2Y(St)MSYSWAY Nominal Cable Code

Insulation Thickness mm

RE-m2Y(St)MSYSWAY 1×3×1.5

0.6

RE-m2Y(St)MSYSWAY 1×3×2.5

0.6

RE-m2Y(St)MSYSWAY 7×3×1.5

0.6

RE-m2Y(St)MSYSWAY 7×3×2.5

0.6

RE-m2Y(St)MSYSWAY 12×3×1.5

0.6

Nominal

Nominal

Inner

Outer

Sheath

Sheath

Thickness

Thickness

mm

mm

Nominal Overall Diameter mm

Approx. Weight kg/km

Note : Other conductor sizes & core configurations are available upon request. 300/500V

Rated Voltage

N BS 5308

Standard

W

E

Circuit Integrity Flame Retardancy Reduced Fire Propagation IEC 60331/BS 6387 NF C32-070-2.2(C1) NF C32-070-2.1(C2) EN 50200 NF C32-070-2.3(CR1) IEC60332-3-24/EN50266-2-4 IEC60332-1-2/EN50265-2-1

Zero

Low Toxicity NES 02-713/NF C 20-454

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073

Halogen Free IEC60754-1 EN50267-2-1

W

E

Functional Integrity DIN 4102-12

ADDISON

13


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.