ADDISON PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC PVC Outer Sheath Tinned Copper Drain Wire AL/HDPE Tape PVC Inner Sheath PE Insulation Plain Annealed Copper Aluminium/polyester Tape Galvanized Steel Wire Armour
APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.
STANDARDS Basic design to BS 5308 Part 1 Type 2
FIRE PERFORMANCE EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE Flame Retardance (Single Vertical 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test)** CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test)** CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING 300/500V
CABLE CONSTRUCTION Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228. Insulation: PE compound.
2
Caledonian
Caledonian
NON-IS & IS Instrumentation Cables
www.caledonian-cables.co.uk
www.caledonian-tech.net
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm Binder tape: PETP transparent tape Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm². Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound Amouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: NON-IS Cable: Black IS Cable: Blue
Physical AND THERMAL PROPERTIES Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter
Electrical PROPERTIES Conductor Area Size
mm2
1.0
1.5
2.5
Conductor Stranding
No. x mm
1 x 1.13
7 x 0.53
7 x 0.67
Conductor Resistance Max
ohm/km
18.2
12.3
7.58
Insulation Resistance Min
MΩ/km
500
500
500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen)
pF/250m
Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)
pF/m
75
85
85
Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs)
pF/m
115
120
120
μH/ohm
25
40
65
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen Rated Voltage Max
250
V
1000
V
1000
V
300/500
300/500
300/500
ADDISON
3
ADDISON CONSTRUCTION PARAMETERS RE-2Y(St)MSYSWAY Nominal Cable Code
Insulation Thickness mm
RE-2Y(St)MSYSWAY 1×2×1.0
0.6
RE-2Y(St)MSYSWAY 1×2×1.5
0.6
RE-2Y(St)MSYSWAY 1×2×2.5
0.6
RE-2Y(St)MSYSWAY 2×2×1.0
0.6
RE-2Y(St)MSYSWAY 2×2×1.5
0.6
RE-2Y(St)MSYSWAY 5×2×1.0
0.6
RE-2Y(St)MSYSWAY 5×2×2.5
0.6
RE-2Y(St)MSYSWAY 10×2×1.0
0.6
RE-2Y(St)MSYSWAY 10×2×2.5
0.6
RE-2Y(St)MSYSWAY 12×2×1.0
0.6
RE-2Y(St)MSYSWAY 12×2×2.5
0.6
RE-2Y(St)MSYSWAY 20×2×1.0
0.6
RE-2Y(St)MSYSWAY 20×2×2.5
0.6
Nominal
Nominal
Inner
Outer
Sheath
Sheath
Thickness
Thickness
mm
mm
Note : Other conductor sizes & core configurations are available upon request. 300/500V
Rated Voltage
4
N BS 5308
Standard
Caledonian
Reduced Fire Propagation** Flame Retardancy** NF C32-070-2.2(C1) NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1 IEC60332-3-24/EN50266-2-4
Nominal Overall Diameter mm
Approx. Weight
kg/km
Caledonian
NON-IS & IS Instrumentation Cables
www.caledonian-cables.co.uk
www.caledonian-tech.net
PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
PVC Outer Sheath Tinned Copper Drain Wire AL/HDPE Tape PVC Inner Sheath PE Insulation Plain Annealed Copper Aluminium/polyester Tape Galvanized Steel Wire Armour
APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.
STANDARDS Basic design to BS 5308 Part 1 Type 2
FIRE PERFORMANCE EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE Flame Retardance (Single Vertical 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test)** CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test)** CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING 300/500V
CABLE CONSTRUCTION Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228. Insulation: PE compound.
ADDISON
5
ADDISON Triple: Three conductors twisted to form a triple. Binder tape: PETP transparent tape Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm². Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound Amouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: NON-IS Cable: Black IS Cable: Blue
Physical AND THERMAL PROPERTIES Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter
Electrical PROPERTIES Conductor Area Size
mm2
1.0
1.5
2.5
Conductor Stranding
No. x mm
1 x 1.13
7 x 0.53
7 x 0.67
Conductor Resistance Max
ohm/km
18.2
12.3
7.58
Insulation Resistance Min
MΩ/km
500
500
500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen)
pF/250m
Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)
pF/m
75
85
85
Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs)
pF/m
115
120
120
μH/ohm
25
40
65
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen Rated Voltage Max
6
Caledonian
250
V
1000
V
1000
V
300/500
300/500
300/500
Caledonian
NON-IS & IS Instrumentation Cables
www.caledonian-cables.co.uk
www.caledonian-tech.net
CONSTRUCTION PARAMETERS RE-2Y(St)MSYSWAY Nominal Cable Code
Insulation Thickness mm
RE-2Y(St)MSYSWAY 7×3×1.0
0.6
RE-2Y(St)MSYSWAY 10×3×1.5
0.6
RE-2Y(St)MSYSWAY 20×3×2.5
0.6
Nominal
Nominal
Inner
Outer
Sheath
Sheath
Thickness
Thickness
mm
mm
Nominal Overall Diameter mm
Approx. Weight
kg/km
Note : Other conductor sizes & core configurations are available upon request. 300/500V
Rated Voltage
N BS 5308
Standard
Reduced Fire Propagation** Flame Retardancy** NF C32-070-2.2(C1) NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1 IEC60332-3-24/EN50266-2-4
ADDISON
7
ADDISON Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipairs) RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
PVC Inner Sheath Aluminum/Polyester Tape With Tinned Copper Drain Wire Mica Tape+PE Insulation Plain Annealed Copper AL/HDPE Tape
Galvanized Steel Wire Armour PVC Outer Sheath
APPLICATION The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.
STANDARDS Basic design to BS 5308
FIRE PERFORMANCE Circuit Integrity Circuit Integrity with mechanical shock Circuit Integrity with mechanical shock & water spray System Circuit Integrity
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) EN 50200(PH30); CEI 20-36/4-0 EN 50200 annex E DIN 4102-12, E30 depending on lay system
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; Flame Retardance (Single Vertical VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test) CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test) CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; Halogen Free CEI 20-37/2-1 ; BS 6425-1*
8
Caledonian
Caledonian
NON-IS & IS Instrumentation Cables
www.caledonian-cables.co.uk
www.caledonian-tech.net
No Corrosive Gas Emission
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases
NES 02-713; NF C 20-454
Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTION Conductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2. Insulation: Mica glass tape covered by PE compound. Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm Overall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire. Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound. Armouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
VOLTAGE RATING 300/500 V
COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: Orange (other colours on request)
Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 10 x Overall Diameter
Electrical PROPERTIES Conductor Area Size Conductor Stranding
mm2
1.0
No. x mm 1 x 1.13
1.5
2.5
4.0
7 x 0.53
7 x 0.67
7 x 0.85
Conductor Resistance Max
ohm/km
18.2
12.3
7.58
Insulation Resistance Min
MΩ/km
500
500
500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen) Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)
pF/250m pF/m
250 75
85
85
ADDISON
9
ADDISON Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs) Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen
pF/m
115
120
120
μH/ohm
25
40
65
Rated Voltage Max
V
1000
V
1000
V
300/500
300/500
300/500
300/500
CONSTRUCTION PARAMETERS RE-m2Y(St)MSYSWAY Nominal Cable Code
Insulation Thickness mm
RE-m2Y(St)MSYSWAY 5×2×1.0
0.6
RE-m2Y(St)MSYSWAY 5×2×1.5
0.6
RE-m2Y(St)MSYSWAY 5×2×2.5
0.6
RE-m2Y(St)MSYSWAY 5×2×4.0
0.6
RE-m2Y(St)MSYSWAY 10×2×1.5
0.6
RE-m2Y(St)MSYSWAY 10×2×2.5
0.6
RE-m2Y(St)MSYSWAY 10×2×4.0
0.6
RE-m2Y(St)MSYSWAY 20×2×1.5
0.6
Nominal
Nominal
Inner
Outer
Sheath
Sheath
Thickness mm
Thickness mm
Note : Other conductor sizes & core configurations are available upon request. 300/500V
Rated Voltage
N BS 5308
Standard
W
E
Circuit Integrity Flame Retardancy Reduced Fire Propagation IEC 60331/BS 6387 NF C32-070-2.2(C1) NF C32-070-2.1(C2) EN 50200 NF C32-070-2.3(CR1) IEC60332-3-24/EN50266-2-4 IEC60332-1-2/EN50265-2-1
Zero
Low Toxicity NES 02-713/NF C 20-454
10
Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074
Caledonian
Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073
Halogen Free IEC60754-1 EN50267-2-1
W
E
Functional Integrity DIN 4102-12
Nominal Overall Diameter mm
Approx. Weight kg/km
Caledonian
NON-IS & IS Instrumentation Cables
www.caledonian-cables.co.uk
www.caledonian-tech.net
Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple) RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
PVC Inner Sheath Aluminum/Polyester Tape With Tinned Copper Drain Wire Mica Tape+PE Insulation Plain Annealed Copper AL/HDPE Tape
Galvanized Steel Wire Armour PVC Outer Sheath
APPLICATION The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.
STANDARDS Basic design to BS 5308
FIRE PERFORMANCE Circuit Integrity Circuit Integrity with mechanical shock Circuit Integrity with mechanical shock & water spray System Circuit Integrity
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) EN 50200(PH30); CEI 20-36/4-0 EN 50200 annex E DIN 4102-12, E30 depending on lay system
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; Flame Retardance (Single Vertical VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test) CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test) CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; Halogen Free CEI 20-37/2-1 ; BS 6425-1*
ADDISON
11
ADDISON No Corrosive Gas Emission
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases
NES 02-713; NF C 20-454
Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTION Conductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2. Insulation: Mica glass tape covered by PE compound. Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm Overall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire. Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound. Armouring: Galvanized steel wire armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
VOLTAGE RATING 300/500 V
COLOUR CODE Insulation Colour: See Technical Information Outer Sheath: Orange (other colours on request)
Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 10 x Overall Diameter
Electrical PROPERTIES Conductor Area Size Conductor Stranding
1.0
No. x mm 1 x 1.13
1.5
2.5
4.0
7 x 0.53
7 x 0.67
7 x 0.85
Conductor Resistance Max
ohm/km
18.2
12.3
7.58
Insulation Resistance Min
MΩ/km
500
500
500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen)
12
mm2
Caledonian
pF/250m
250
Caledonian
NON-IS & IS Instrumentation Cables
www.caledonian-cables.co.uk
www.caledonian-tech.net
Max. Mutual Capacitance @ 1 Khz for non Os or Os Cables (Except 1 Pair and 2 Pairs)
pF/m
75
85
85
Max. Mutual Capacitance @ 1 Khz for Is/ Os Cables (Include 1 Pair and 2 Pairs)
pF/m
115
120
120
μH/ohm
25
40
65
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) Core To Core Test Voltage Core To Screen Rated Voltage Max
V
1000
V
1000
V
300/500
300/500
300/500
300/500
CONSTRUCTION PARAMETERS RE-m2Y(St)MSYSWAY Nominal Cable Code
Insulation Thickness mm
RE-m2Y(St)MSYSWAY 1×3×1.5
0.6
RE-m2Y(St)MSYSWAY 1×3×2.5
0.6
RE-m2Y(St)MSYSWAY 7×3×1.5
0.6
RE-m2Y(St)MSYSWAY 7×3×2.5
0.6
RE-m2Y(St)MSYSWAY 12×3×1.5
0.6
Nominal
Nominal
Inner
Outer
Sheath
Sheath
Thickness
Thickness
mm
mm
Nominal Overall Diameter mm
Approx. Weight kg/km
Note : Other conductor sizes & core configurations are available upon request. 300/500V
Rated Voltage
N BS 5308
Standard
W
E
Circuit Integrity Flame Retardancy Reduced Fire Propagation IEC 60331/BS 6387 NF C32-070-2.2(C1) NF C32-070-2.1(C2) EN 50200 NF C32-070-2.3(CR1) IEC60332-3-24/EN50266-2-4 IEC60332-1-2/EN50265-2-1
Zero
Low Toxicity NES 02-713/NF C 20-454
Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074
Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073
Halogen Free IEC60754-1 EN50267-2-1
W
E
Functional Integrity DIN 4102-12
ADDISON