Caledonian
CPMS (Car Park Management System)
Communication Cable FFX200 05mROZ1-R/F 3P0.75
FFX200 05mROZ1-R 3P0.75 (CU/MGT+XLPE/OSCR/LSZH 3×2×0.75mmsq 300/500V class 2) FFX200 05mROZ1-F 3P0.75 (CU/MGT+XLPE/OSCR/LSZH 3×2×0.75mmsq 300/500V class 5)
m o
LSZH Outer Sheath Mica+XLPE Insulation
c . s e l b a
Plain Annealed Copper
AL/Polyester Tape With Tinned Copper Drain Wire
APPLICATIONS
c rt
The cables are single pair stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.
o p r i a . w
STANDARDS Basic design
BS 7629
Halogen Free
IEC 60754-1
No corrosive gas emission
IEC 60754-2
Minimum Smoke Emission
IEC 61034-1/2
Reduced Fire Propagation
IEC 60332-3C / NF C 32070-2.2 (C1)
Flame Retardance
IEC 60332-1 / NF C 32-070-2.1 (C2)
Fire Resistance
IEC 60331 / NF C 32070-2.3(CR1)
w w
VOLTAGE RATING 300/500V
CABLE CONSTRUCTION Conductors: Plain annealed copper wire, stranded according to EN 60228 class 2 or class 5. Insulation: Mica glass tape covered by extruded cross-linked XLPE compound. Cable elements: Insulated cores are twisted to form pairs. Cabling: Pairs are cabled together. Overall screen: Aluminum/polyester tape with copper drain wire.
ADDISON
39
ADDISON Outer sheath: Thermoplastic LSZH compound. COLOUR CODE Insulation Colour: According to IEC 60189-2 (other colour code on request). Sheath Colour: Colour red (other colours on request). Electrical PROPERTIES Dielectric test:
2000 V r.m.s. x 5’ (core/core)
Insulation resistance
1000 MΩ x km (at 20°C)
Short circuit temperature
250°C
m o
c . s e l b a
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter CONSTRUCTION PARAMETERS FFX200 05mROZ1-R 3P0.75 FFX200 05mROZ1-F 3P0.75 Nominal Number & No.of Cross Nominal pair Sectional Diameter of Area Strands
3
Approx. Weight
No/mm
mm
mm
mm
kg/km
0.75
7/0.37
0.6
1.0
11.5
126
0.75
24/0.2
0.6
1.0
11.5
126
Standard
Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4
40
Nominal Overall Diameter
mm2
N w w BS 7629-1
Nominal Sheath Thickness
o p r i a . w
3
c rt
Nominal Insulation Thickness
Caledonian
Zero
Halogen Free IEC60754-1/ EN50267-2-1
Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1
Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074
Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)
Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073
Caledonian ULV Cables -CPMS (Car Park Management System) www.airport-cables.com
enquiry@airport-cables.com
Caledonian
CPMS (Car Park Management System) Talk-back Cable FFX200 05mROZ1-R/F 2G1.0 FFX200 05mROZ1-R 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 2) FFX200 05mROZ1-F 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 5)
LSZH Outer Sheath Plain Annealed Copper
m o
Mica+XLPE Insulation
c . s e l b a
AL/Polyester Tape With Tinned Copper Drain Wire
APPLICATIONS
The cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.
o p r i a . w
STANDARDS
c rt
Basic design
BS 7629
Halogen Free
IEC 60754-1
No corrosive gas emission
IEC 60754-2
Minimum Smoke Emission
IEC 61034-1/2
Reduced Fire Propagation
IEC 60332-3C / NF C 32070-2.2 (C1)
Flame Retardance
IEC 60332-1 / NF C 32-070-2.1 (C2)
Fire Resistance
IEC 60331 / NF C 32070-2.3(CR1)
w w
VOLTAGE RATING 300/500V
CABLE CONSTRUCTION Conductors: Plain annealed copper wire, stranded according to EN 60228 class 2 or class 5. Insulation: Mica glass tape covered by extruded cross-linked XLPE compound. Cable elements: Insulated cores are twisted to form pairs. Cabling: Pairs are cabled together. Overall screen: Aluminum/polyester tape with copper drain wire.
ADDISON
41
ADDISON Outer sheath: Thermoplastic LSZH compound. COLOUR CODE Insulation Colour: According to IEC 60189-2 (other colour code on request). Sheath Colour: Colour red (other colours on request). Electrical PROPERTIES Dielectric test:
2000 V r.m.s. x 5’ (core/core)
Insulation resistance
1000 MΩ x km (at 20°C)
Short circuit temperature
250°C
m o
c . s e l b a
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter CONSTRUCTION PARAMETERS FFX200 05mROZ1-R 2G1.0 FFX200 05mROZ1-F 2G1.0
o p r i a . w
No.of core
2 2
Nominal Cross Sectional Area
w wN BS 7629-1
mm2 1.0 1.0
Standard
Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4
42
Caledonian
Number & Nominal Diameter of Strands No/mm 7/0.44 32/0.2
c rt Nominal Insulation Thickness
Nominal Sheath Thickness
Nominal Overall Diameter
mm 0.6 0.6
mm 0.9 0.9
mm 7.2 7.2
Zero
Halogen Free IEC60754-1
Flame Retardance IEC60332-1-2 /NF C32-070-2.1(C2)
Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074
Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)
Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073
Approx. Weight kg/km 64 64
Caledonian ULV-Current Cables Carrying Capacities and Voltage Drop www.airport-cables.com
enquiry@airport-cables.com
Caledonian
Current Carrying Capacities And Voltage Drop Conductor Operating Temperature : 90째C Ambient Temperature : 30째C Current-Carrying Capacities (Amp) Conductor crosssectional area
Reference Reference Method Reference Method 12 (free air) Method 3 Reference Method 4 (enclosed (enclosed in Reference Method 1 11 (on a perforated in conduit conduit on a wall (clipped direct) cable tray, horizontal Horizontal Vertical flat in thermally Trefoil or in trunking or vertical) flat spaced spaced insulating wall etc) etc)
2 cables, singlephase a.c. or d.c.
1 mm2 1.0 1.5 2.5
2 A 13 18 24
2 2 cables, 3 or 4 2 cables, 3 or 4 cables, cables, single cables, single3 or 4 single- 3 or 4 phase 3-phase -phase 3-phase cables, cables, a.c. flat a.c. or a.c. flat a.c. or 3-phase 3-phase phase d.c. or and d.c. flat and a.c. a.c. a.c. or and touching flat and touching d.c touching or trefoil touching or trefoil
3 A 17 23
4 A 22 30
5 A 19 26
6 A 15 25 34
o p r i a . w
Voltage Drop (Per Amp Per Meter)
1 mm
2
2.5
8 A -
9 A -
10 A -
11 A -
12 A -
3 or 4 cables, 3-phase a.c. Ref. Methods 1 and Ref. Methods 3 Ref. Methods 1, 11 and 4 (enclosed 11 and 12 (in in conduit etc, (Flat and touching) trefoil) in or on a wall)
2
3
4
5
6
7
mV/A/m
mV/A/m
mV/A/m
mV/A/m
mV/A/m
mV/A/m
46 31
46 31
27
27
27
27
19
19
16
16
16
16
w w 1.0 1.5
m o
c . s e l b a
7 A 23 31
c rt
2 cables, single-phase a.c. Nominal Ref. Methods 3 Ref. Methods 1 Cross 2 cables and 4 (enclosed and 11 (clipped Section d.c. in conduit etc, direct or on trays Area in or on a wall) touching)
2 cables, 2 cables, singlesingle3 cables, phase phase a.c. trefoil a.c. or or d.c. or d.c. or 3 3-phase 3 cables a.c. cables three three phase phase
ADDISON
43