EIB cable 2y(st)h

Page 1

ADDISON PE Insulation, LSZH Outer Sheath European Installation Bus(EIB) Cables EIB 2Y(St)H 2x2x0.8

LSZH Outer Sheath PE Insulation Solid Copper Conductor

Overall AL/Polyester Tape With Tinned Copper Drain Wire

APPLICATION EIB installation consists of sensors and actuators. The E.I.B. concept allows intergration of Building Management Systems (B.M.S.) over one common system. Lighting, blinds, heating and ventilation can be automatically controlled through the E.I.B cable. This dramatically reduces the cabling required in a modern building. To meet European standards this cable is LSZH throughout. They can be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun.

STANDARDS Basic design to European Standard EN 50090

FIRE PERFORMANCE EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE Flame Retardance (Single Vertical 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test) CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test) CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

4

Caledonian

www.caledonian-cables.co.uk

www.addison-cables.com


Caledonian

European Installation Bus(EIB) Cables

CABLE CONSTRUCTION Type/Cable Construction Inner Conductor Conductor Insulation Insulation Colour Stranding Element Screen Drain Wire Outer Sheath

1 Quad Plain copper conductors 0.8mm PE White, yellow, red, black Cores twisted into a quad Aluminium/polyester foil screen Solid copper LSZH

2 Pair Plain copper conductors 0.8mm PE White/yellow, red/black Cores twisted into pairs, pairs laid up Aluminium/polyester foil screen Stranded tinned copper LSZH

cOLOUR Code Insulation Colour: Pair1: Red/Black; Pair2: White/Yellow Sheath Colour: Green

Electrical Properties Test Voltage

4000V

Working Voltage

Max.150V

Conductor resistance

37.0 Ohm/km @ 20°C

Insulation resistance

1000MΩhms*km @ 20°C

Mutual capacitance@800Hz

60nF/km max

Unbalanced capacitance

300pF/100m max

ADDISON

5


ADDISON TECHNICAL DATA: Approx.Weight (kg/km)

62

57

Nominal diameter(mm)

6.1

6.1

Min. Bending Radius (Laying)

10 x OD mm

10 x OD mm

Operating temperature, min

-20째C(fixed)

-5째C (installation)

Operating temperature, max

+70째C(fixed)

+50째C (installation)

150V

N EN 50090

Rated Voltage

Standard

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

Zero

Low Toxicity NES 02-713/NF C 20-454

6

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Caledonian

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073

www.caledonian-cables.co.uk

Halogen Free IEC60754-1 EN50267-2-1

www.addison-cables.com


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.