h(st)h LSZH Insulation, LSZH Outer Sheath European Installation Bus(EIB) Cables

Page 1

Caledonian

European Installation Bus(EIB) Cables

LSZH Insulation, LSZH Outer Sheath European Installation Bus(EIB) Cables EIB H(St)H 2x2x0.8

LSZH Outer Sheath LSZH Insulation Solid Copper Conductor

Overall AL/Polyester Tape With Tinned Copper Drain Wire

APPLICATION EIB installation consists of sensors and actuators. The E.I.B. concept allows intergration of Building Management Systems (B.M.S.) over one common system. Lighting, blinds, heating and ventilation can be automatically controlled through the E.I.B cable. This dramatically reduces the cabling required in a modern building. To meet European standards this cable is LSZH throughout. They can be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun.

STANDARDS Basic design to European Standard EN 50090

FIRE PERFORMANCE EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE Flame Retardance (Single Vertical 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); Wire Test) CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; (Vertically-mounted bundled wires VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); & cable test) CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

ADDISON

11


ADDISON CABLE CONSTRUCTION Type/Cable Construction Conductor Conductor Insulation Insulation Colour Stranding Element Screen

1 Quad Plain copper conductors 0.8mm LSZH White,yellow,red,black Cores twisted into a quad Aluminium/polyester foil screen Solid copper LSZH

Drain Wire Outer Sheath

2 Pair Plain copper conductors 0.8mm LSZH White/yellow, red/black Cores twisted into pairs, pairs laid up Aluminium/polyester foil screen Stranded tinned copper LSZH

cOLOUR Code Insulation Colour: Pair1: Red/Black; Pair2: White/Yellow Sheath Colour: Green

Electrical Properties

12

Test Voltage

4000V

Working Voltage

Max.150V

Conductor resistance

37.0 Ohm/km @ 20°C

Insulation resistance

100MΩhms*km @ 20°C

Mutual capacitance@800Hz

100nF/km max

Unbalanced capacitance

300pF/100m max

Caledonian

www.caledonian-cables.co.uk

www.addison-cables.com


Caledonian

European Installation Bus(EIB) Cables

TECHNICAL DATA: Approx.Weight (kg/km)

62

57

Nominal diameter(mm)

6.1

6.1

Min. Bending Radius (Laying)

10 x OD mm

10 x OD mm

Operating temperature, min

-20째C(fixed)

-5째C (installation)

Operating temperature, max

+70째C(fixed)

+50째C (installation)

150V

Rated Voltage

N EN 50090

Standard

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

Zero

Low Toxicity NES 02-713/NF C 20-454

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073

Halogen Free IEC60754-1 EN50267-2-1