Caledonian Airport Cables Fire alarm system

Page 1

Caledonian ULV Cables www.airport-cables.com

-FAS (Fire Alarm System)

enquiry@airport-cables.com

Caledonian

FAS (Fire Alarm System)

Detector Cable , FFX200 05SZ1-R/F 1P1.5 FFX200 05SZ1-R 1P1.5 (CU/SR/LSZH 1×2×1.5mmsq 300/500V class 2) FFX200 05SZ1-F 1P1.5 (CU/SR/LSZH 1×2×1.5mmsq 300/500V class 5)

Silicone Rubber Insulation

LSZH Outer Sheath

APPLICATIONS

m o

c . s e l b a Plain Annealed Copper

c rt

The cables are single pair stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.

o p r i a . w

STANDARDS Basic design

BS 7629-1

Halogen Free

IEC 60754-1

No corrosive gas emission

IEC 60754-2

Minimum Smoke Emission

IEC 61034/1/2

Reduced Fire Propagation

IEC 60332-3C / NF C 32-070-2.2 (C1)

Flame Retardance

IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance

IEC 60331 / BS 5839-1 Clause 26 2d / NF C 32070-2.3(CR1)

w w

VOLTAGE RATING 300/500V

CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5. Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1

ADDISON

3


ADDISON Twisting: Cores are twisted into pairs with varying lay length to minimize crosstalk Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1. Electrical PROPERTIES Dielectric test:

2000 V r.m.s. x 5’ (core/core)

Insulation resistance

300 MΩ x km (at 20°C)

Short circuit temperature

350°C

m o

Physical AND THERMAL PROPERTIES

c . s e l b a

Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter CONSTRUCTION PARAMETERS FFX200 05SZ1-R 1P1.5 FFX200 05SZ1-F 1P1.5 No.of pair x

Nominal Cross Sectional Area

Number & Nominal Diameter of Strands No/mm

Nominal Sheath Thickness

Nominal Overall Diameter

Approx. Weight

mm

mm

mm

kg/km

0.5

0.5

7.0

60

0.5

0.5

7.0

60

o p r i a . N w w w mm

2

1

1.5

7/0.53

1

1.5

30/0.25

c rt

Nominal Insulation Thickness

BS 7629-1

Zero

Standard

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

4

Caledonian

Halogen Free IEC60754-1

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

No Corrosive Gas Emission IEC60754-2

Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073


Caledonian ULV Cables www.airport-cables.com

-FAS (Fire Alarm System)

enquiry@airport-cables.com

Caledonian

FAS (Fire Alarm System)

Fire Communication Cable, FFX200 05SZ1-R/F 1P1.5 FFX200 05SZ1-R 1P1.5 (CU/SR/LSZH 1×2×1.5mmsq 300/500V class 2) FFX200 05SZ1-F 1P1.5 (CU/SR/LSZH 1×2×1.5mmsq 300/500V class 5)

Silicone Rubber Insulation

LSZH Outer Sheath

APPLICATIONS

m o

c . s e l b a Plain Annealed Copper

c rt

The cables are single pair stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.

o p r i a . w

STANDARDS Basic design

BS 7629-1

Halogen Free

IEC 60754-1

No corrosive gas emission

IEC 60754-2

Minimum Smoke Emission

IEC 61034/1/2

Reduced Fire Propagation

IEC 60332-3C / NF C 32-070-2.2 (C1)

Flame Retardance

IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance

IEC 60331 / BS 5839-1 Clause 26 2d / NF C 32070-2.3(CR1)

w w

VOLTAGE RATING 300/500V

CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5. Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1

ADDISON

5


ADDISON Twisting: Cores are twisted into pairs with varying lay length to minimize crosstalk Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1. Electrical PROPERTIES Dielectric test:

2000 V r.m.s. x 5’ (core/core)

Insulation resistance

300 MΩ x km (at 20°C)

Short circuit temperature

350°C

m o

Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter

c . s e l b a

CONSTRUCTION PARAMETERS FFX200 05SZ1-R 1P1.5 FFX200 05SZ1-F 1P1.5

mm2

Number & Nominal Diameter of Strands No/mm

1

1.5

7/0.53

1

1.5

30/0.25

No.of pair x

Nominal Cross Sectional Area

c rt

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Overall Diameter

Approx. Weight

mm

mm

mm

kg/km

0.5

0.5

7.0

60

0.5

0.5

7.0

60

o p r i Nw.a w w BS 7629-1

Zero

Standard

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

6

Caledonian

Halogen Free IEC60754-1/ EN50267-2-1

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073


Caledonian ULV Cables www.airport-cables.com

-FAS (Fire Alarm System)

enquiry@airport-cables.com

Caledonian

FAS (Fire Alarm System) Sounder Cable FFX200 05SZ1-R/F 2G1.5 FFX200 05SZ1-R 2G1.5 (CU/SR/LSZH 2×1.5mmsq 300/500V class 2) FFX200 05SZ1-F 2G1.5 (CU/SR/LSZH 2×1.5mmsq 300/500V class 5)

Silicone Rubber Insulation

m o

Plain Annealed Copper

c . s e l b a LSZH Outer Sheath

APPLICATIONS

The cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.

o p r i a . w

STANDARDS

c rt

Basic design

BS 7629-1

Halogen Free

IEC 60754-1

No corrosive gas emission

IEC 60754-2

w w

Minimum Smoke Emission

IEC 61034/1/2

Reduced Fire Propagation

IEC 60332-3C / NF C 32070-2.2 (C1)

Flame Retardance

IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance

IEC 60331 / BS 5839-1 Clause 26 2d / NF C 32070-2.3(CR1)

VOLTAGE RATING 300/500V

CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5. Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.

ADDISON

7


ADDISON Electrical PROPERTIES Dielectric test:

2000 V r.m.s. x 5’ (core/core)

Insulation resistance

300 MΩ x km (at 20°C)

Short circuit temperature

350°C

Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter

FFX200 05SZ1-R 2G1.5 FFX200 05SZ1-F 2G1.5 Nominal Cross No.of core Sectional Area mm2

Number & Nominal Diameter of Strands No/mm

2

1.5

7/0.53

2

1.5

30/0.25

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Overall Diameter

Approx.Weight

mm

mm

mm

kg/km

0.5

7.0

70

0.5

7.0

70

o N irp a . w w w BS 7629-1

Zero

Standard

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

8

Caledonian

Halogen Free IEC60754-1

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

m o

c . s e l b a

CONSTRUCTION PARAMETERS

c rt 0.5

0.5

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073


Caledonian ULV Cables www.airport-cables.com

-FAS (Fire Alarm System)

enquiry@airport-cables.com

Caledonian

FAS (Fire Alarm System)

Control Cable FFX200 05SZ1-R/F 2G2.5 FFX200 05SZ1-R 2G2.5 (CU/SR/LSZH 2×2.5mmsq 300/500V class 2) FFX200 05SZ1-F 2G2.5 (CU/SR/LSZH 2×2.5mmsq 300/500V class 5)

m o

Plain Annealed Copper Silicone Rubber Insulation

c . s e l b a LSZH Outer Sheath

APPLICATIONS

c rt

The cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. The cables are designed specially for fire alarm systems where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground.

o p r i a . w

STANDARDS Basic design

BS 7629-1

Halogen Free

IEC 60754-1

No corrosive gas emission

IEC 60754-2

Minimum Smoke Emission

IEC 61034-1/2

Reduced Fire Propagation

IEC 60332-3C / NF C 32070-2.2 (C1)

Flame Retardance

IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance

IEC 60331 / BS 5839-1 Clause 26 2d / NF C 32070-2.3(CR1)

w w

VOLTAGE RATING 300/500V

CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5. Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1. Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.

ADDISON

9


ADDISON Electrical PROPERTIES Dielectric test:

2000 V r.m.s. x 5’ (core/core)

Insulation resistance

300 MΩ x km (at 20°C)

Short circuit temperature

350°C

Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter

FFX200 05SZ1-R 2G2.5 FFX200 05SZ1-F 2G2.5 Nominal Cross No.of core Sectional Area mm2

Number & Nominal Diameter of Strands No/mm

o p r N .ai w w w 2 2

2.5 2.5

7/0.67 50/0.25

BS 7629-1

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Overall Diameter

Approx. Weight

mm

mm

mm

kg/km

1.0 1.0

9.0 9.0

105 105

c rt 0.8 0.8

Zero

Standard

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

10

Caledonian

Halogen Free IEC60754-1

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

m o

c . s e l b a

CONSTRUCTION PARAMETERS

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073


Caledonian ULV Cables www.airport-cables.com

-FAS (Fire Alarm System)

enquiry@airport-cables.com

Caledonian

FAS (Fire Alarm System)

RS485 Data Cable RE-02Y(St)H 1P18A RE-02Y(St)H 1P18A (CU/PE/OSCR/LSZH 1Ă—2Ă—18AWG)

LSZH Outer Sheath Fireproof tape

m o

Stranded Tinned Copper

c . s e l b a

PE Insulation

Overall AL/Polyester Tape With Tinned Copper Drain Wire

APPLICATIONS

c rt

The cables are designed for RS485 data connections. This cable combines low capacitance insulation with one of the highest levels of screening to provide high speed, interference free, data transmission where continued functionality is required during a fire situation.

o p r i a . w

STANDARDS Basic design

EIA/TIA 485

Halogen Free

IEC 60754-1

No corrosive gas emission

IEC 60754-2

Minimum Smoke Emission

IEC 61034-1/2

Reduced Fire Propagation

IEC 60332-3C / NF C 32070-2.2 (C1)

Flame Retardance

IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance

IEC 60331-23 / NF C 32-070-2.3(CR1)

w w

CABLE CONSTRUCTION Conductors: tinned annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5. Insulation: Solid or foam PE compound Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Overall screen: Aluminum/ polyester tape with tinned copper drain wire. Fire Barrier: Fireproof Tape. Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.

ADDISON

11


ADDISON Electrical Properties Dielectric test

1000 V r.m.s. for 5’ (core-core) 1000 V r.m.s. for 5’ (core-screen)

Impedance

120Ω

Capacitance

45 nF/km conductor to conductor 90 nF/km conductor to shield

m o

Physical AND THERMAL PROPERTIES

c . s e l b a

Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter CONSTRUCTION PARAMETERS RE-02Y(ST)H 1P18A

c rt

AWG

Number & Nominal Diameter of Strands No/mm

1

18

7/0.404

1.15

1.2

10.5

100

1

18

16/0.254

1.15

1.2

10.5

100

No.of pair ×

Wire Gange

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Overall Diameter

Approx.Weight

mm

mm

mm

kg/km

o p r i Nw.a w w EIA/TIA 485

Zero

Standard

Reduced Fire Propagation NF C32-070-2.2(C1) IEC60332-3-24 EN50266-2-4

12

Caledonian

Halogen Free IEC60754-1

Flame Retardancy NF C32-070-2.1(C2) IEC60332-1-2/EN50265-2-1

Low Corrosivity IEC60754-2 EN50267-2-2/3 NF C 32-074

Fire Resistance IEC 60331 /NF C 32070-2.3(CR1)

Low Smoke Emission IEC 61034-1&2 EN 50268-1&2/NF C32-073