Ratings and dimensions Rated voltage Rated power-frequency withstand voltage
TE AID TE
Rated lightning impulse withstand voltage
The values in the table refer to IEC standards, unless explicit reference to ANSI is made; for missing ANSI ratings, refer to C37.32
Ur (kV) Ud (kV)
Ud (kV)
Up (kVp)
AID Up (kVp) Rated switching impulse withstand voltage
72.5
123
145
170
140
230
275
325
395
460
380
160
265
315
375
460
530
435
1050
1050
325 (IEC)
245
950 (IEC)
300
550
650
750
375
630
750
860
1050
1200
350 (ANSI)
900 (ANSI)
TE
Us (kVp)
-
-
-
-
-
-
AID
Us (kVp)
-
-
-
-
-
-
1050 (+170) 850 700 (+245)
TE: To Earth AID: Across the Isolating Distance Ir (A) Ik (kA) Ip (kAp)
Rated short-time withstand current Rated peak withstand current Dimensions (mm)
A B C D E F G
IEC ANSI IEC ANSI
up to 4000 IEC / ANSI (depending on rated voltage) up to 75 / 3s (depending on rated current) up to 190 (depending on rated current) 1280 770 762 970 962 900 170 4 ø18
1780 1220 1143 1420 1343 1400 170 4 ø18
2200 1500 1372 1720 15912 1800 270 4 ø18
Reliability and maintenance
2200 1700 1575 1920 1795 1800 270 4 ø18
2880 2100 2032 2370 2302 2300 270 4 ø18
3200 2300 2337 2570 2607 2800 270 270 8 ø18
3200 2300 2337 2570 2607 2800 270 270 8 ø18
A
Due to lifetime greased (or self-lubricated) hinges and to self-wiping contacts, the maintenance of the TCB is ensured by its motion. The use of corrosion-free (or coated) materials for all components ensures exceptional reliability for many years of service. The mechanical endurance performance exceeds IEC standard requirements..
B
C
F E
Optional devices
For operation under severe ice conditions (up to 20 mm), ice shields are available for protection of the equipment (where needed).
COELME Via G. Galilei, 1/2 - 30036 Santa Maria di Sala (VE) - Italia Tel.: +39 041 486022 - Fax: +39 041 486909 E-Mail: contact@coelme-egic.com, www.coelme-egic.com
40 x
The integrated earthing switch can also be fitted with an optional induced current switching device, compliant with IEC 62271-102.
x
35
30
20
Upon request, the disconnector can be equipped with a bus-transfer current switching device, compliant with IEC 62271-102.
D
y
y
Egic 60b, rue L. et R. Desgrand - 69625 Villeurbanne CEDEX - France Tel.: +33 4 72 66 20 70 - Fax: +33 4 72 39 08 65 E-Mail: contact@coelme-egic.com, www.coelme-egic.com
TCB-en-C/E - 01/2019 - Due to product and standards evolution, characteristics and dimensions shown might change.
Rated continuous current