VSV_25-36KV_EN_2013.pdf

Page 1

COSTRUZIONI ELETTROMECCANICHE - SPA

VSV 25-36 kV Catenary switcher

Group


We know how Our range of switchers is designed to ensure the best performances and reliability, which are the result of our 60-year-old experience in the field of high voltage.

The VSV Catenary switcher The VSV is an outdoor switch. It is expressly designed to meet the needs of 25-36 kV railway lines requiring high-performance equipment as well as modern and reliable technologies. The VSV is composed of a sealed enclosure filled with inert gas where a vacuum interrupter is located. This device is operated by a magnetic actuator which is connected to it without any outside mechanical transmission rods. The VSV’s strengths are its versatility and weather resistance, which make its installation possible also in harsh environmental conditions, with no need for adjustments or final calibrations. Its simplicity, compactness and robustness make it easy to be installed as well as able to operate regularly, in the years, under maintenance-free conditions. Pursuant to the most recent environmental laws on the use of sulphur hexafluoride, the VSV uses inert gas (SF6 or N2) only to guarantee the dielectric features, thus avoiding emissions of burnt gases during operations.

Optional devices The VSV can be supplied either in unipolar or bipolar version. Additionally, a disconnector can be provided – upon request – for open circuit to be made visible. Upon request, the VSV can also be provided with a specific relay to control the automatic opening of the equipment in the event of voltage failure in the power circuit of the control cabinet.

Reliability and maintenance The VSV is designed to be maintenance-free. The use of a high-quality vacuum interrupter ensures the constancy of performance in time. The use of stainless material (or made so thanks to proper protective coatings) in the manufacturing of all components, the presence of a magnetic actuator and of few moving parts, the absence of external transmission rods ensure an excellent level of reliability of the VSV for many years of operation.


Construction features

1

The VSV is composed of either one or two (if bipolar) poles connected to the same control cabinet through a shielded cable. Each pole includes a vacuum interrupter and a magnetic actuator. The former is manufactured using high-quality material and advanced technology, which allow for short operation times and ensure the long life of the equipment. The latter, which is bistable, is warranted for more than 30,000 operation cycles.

1 2 3 4 5 6 7 8 9 10

Upper terminal Vacuum interrupter Hollow insulator Lower terminal Insulating driving shaft Connector Emergency manual operation device Position sensor Magnetic actuator Position indicator

2 3 4

5

The porcelain insulators ensure an excellent dielectric withstand, also in case of high levels of pollution. Upon request, the VSV can be provided with composite insulators. The control cabinet serves as interface between the control room and the VSV. It is provided with lockable door and allows for the following operations:

6

â– Remote electrical operations and monitoring of the equipment via an alarm signal. â– Local electrical operations.

7

Each pole is also equipped with a lever device for manual emergency operations: it allows opening and closing operations also without power supply to the control cabinet.

8 9

10

885

885

500

500 16

187.5

45 45 17.5

1283 9Ă˜16

17.5

646

2042

3000<H<6000

497

319

from 280 to 400 1000

from 280 to 400

125

45 45

616


Ratings The values in the table refer to IEC standards.

25 to 36 kV

Insulation level

kV rms, 50Hz 1min

95

kV peak, 1.2/50

250

Rated current

A

up to 1600

Breaking capacity

kA

20

Making capacity

kA

20

Short time current Ambient temperature

kA rms, -1s

12.5

°C

-33 +40

Rated operating sequence

CO

Operating times

Minimum mechanical and electrical endurance

opening, ms

<70

closing, ms

<100

cycles

10.000

50/60 Hz, Vac Supply voltage Control cabinet (-20 ÷ + 30%)

127 230 48

Vdc

110 220

Current consuption

PO

charging, Amax

3

standby, mA

12

Electrical diagram legend PO Opening push-button PC Closing push-button MEC 1 PCB controller Signalling auxiliary relay: open XO XC Signalling auxiliary relay: closed LO Signalling lamp: open LC Signalling lamp: closed PKT Alarm contact NT Counter RA Anti-condensation resistance

PC

Position signalling contact: closed

Alimentation (ac ou dc) + -

Position signalling contact: open 230 Vca

XC LO LC XO RA +t°

NT

PKT MEC 1

COELME Via G. Galilei, 1/2 - 30036 Santa Maria di Sala (VE) - Italia Tel.: +39 041 486022 - Fax: +39 041 486909 E-Mail: contact@coelme-egic.com, www.coelme-egic.com

EGIC 60b, rue L. et R. Desgrand - 69625 Villeurbanne CEDEX - France Tel.: +33 4 72 66 20 70 - Fax: +33 4 72 39 08 65 E-Mail: contact@coelme-egic.com, www.coelme-egic.com

VSV-en-C/E - 12/2013 - Due to product and standards evolution, characteristics and dimensions are likely to change.