IQ DP-4000 Category
Modbus TCP Register
Description
Register Count
Type ID Units
System ID
1032 1064 1096 1128 1605 18172
Vendor Name Model Name Display Name Device Type Field Replaceable Unit Energy Concentrator Configuration
32 32 32 32 1 125
ASCII ASCII ASCII ASCII UINT16 ASCII
7222 7264
Peak Demand Forward Watts Peak Demand Reverse Watts
2 2
FLOAT FLOAT
7305
Peak Demand Lagging VARs
2
FLOAT
7347
Peak Demand Leading VARs
2
FLOAT
watts watts volt-amperesreactive volt-amperesreactive
3048
Device Online Status
1
UINT16
no-units
Offline(3);Online(4)
3000
Status
1
UINT16
no-units
Off(0);Ready(1);Alarm 1(2);Alarm 2(3)
no-units
Normal(0);RAM Failure(1);ROM Failure(2);A/D Converter Error(3);EEPROM Failure(4);Deadman Timer Error(5);Loss of Phase Current(6);Phase Reversal(7);Phase Unbalance(8);Loss of Phase Voltage(9);Under Voltage(10);Over Voltage(11);INCOM Initiated(12);Unknown(13)
Energy Concentrator Parameters
Status
Meters
Eaton Corporation
3001
Status Reason
1
UINT16
4002 4004 4006 4010 4012
Vab Vbc Vca Van Vbn
2 2 2 2 2
FLOAT FLOAT FLOAT FLOAT FLOAT
f/w 3.11
Writable
Possible Values
no-units no-units no-units no-units no-units no-units
volts volts volts volts volts
4/14/2010
Category
Eaton Corporation
Modbus TCP Register
Description
Register Count
Type ID Units
4014 5002 5004 5006 5014 5016 5018 5250 5252 5254 6006 6070 6134
Vcn Ia Ib Ic Peak Demand Ia Peak Demand Ib Peak Demand Ic Demand Ia Demand Ib Demand Ic Real Power Apparent Power Reactive Power
2 2 2 2 2 2 2 2 2 2 2 2 2
FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT
6218 6220 7004 7006 7008
PF Displacement PF Apparent Forward Real Energy Reverse Real Energy Net Real Energy
2 2 2 2 2
FLOAT FLOAT FLOAT FLOAT FLOAT
7010
Leading Reactive Energy
2
FLOAT
volt-amperereactive-hours
7012
Lagging Reactive Energy
2
FLOAT
volt-amperereactive-hours
7014
Net Reactive Energy
2
FLOAT
7016 7023 7220 7262
Apparent Energy Demand Watts Demand Forward Watts Demand Reverse Watts
2 2 2 2
FLOAT FLOAT FLOAT FLOAT
7029
Demand VARs
2
FLOAT
7303
Demand Lagging VARs
2
FLOAT
f/w 3.11
Writable
Possible Values
volts amperes amperes amperes amperes amperes amperes amperes amperes amperes watts volt-amperes volt-amperesreactive power-factor power-factor watt-hours watt-hours watt-hours
volt-amperereactive-hours volt-amperehours watts watts watts volt-amperesreactive volt-amperesreactive
4/14/2010
Category
Eaton Corporation
Modbus TCP Register
Description
Register Count
Type ID Units
7345 7035 7040
Demand Leading VARs Demand VAs Peak Demand Watts
2 2 2
FLOAT FLOAT FLOAT
7045 7050
Peak Demand VARs Peak Demand VAs
2 2
FLOAT FLOAT
7628 7679 9436 9438 9440 8148 8150 8152 8154 8156 8158 9328 9336 9330 9338 9332 9340 9373 9385 9375 9387 9377 9389 9379 9391 9381 9393 9383 9395
Total Reactive Energy Total Real Energy Percent THD Ia Percent THD Ib Percent THD Ic Percent THD Vab Percent THD Vbc Percent THD Vca Percent THD Van Percent THD Vbn Percent THD Vcn Min Percent THD Ia Max Percent THD Ia Min Percent THD Ib Max Percent THD Ib Min Percent THD Ic Max Percent THD Ic Min Percent THD Vab Max Percent THD Vab Min Percent THD Vbc Max Percent THD Vbc Min Percent THD Vca Max Percent THD Vca Min Percent THD Van Max Percent THD Van Min Percent THD Vbn Max Percent THD Vbn Min Percent THD Vcn Max Percent THD Vcn
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT FLOAT
f/w 3.11
Writable
Possible Values
volt-amperesreactive volt-amperes watts volt-amperesreactive volt-amperes volt-amperereactive-hours watt-hours percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent percent
4/14/2010
Category
Alarms
Controls
Modbus TCP Register
Description
Register Count
Type ID Units
11000
Frequency
2
FLOAT
hertz
13548 13555
Alarm Active Trip Event
1 1
UINT16 UINT16
no-units
False(0);True(1)
no-units
False(0);True(1)
2203 2204 2205 2206 2207
Reset Alarm 2 Reset Alarm 1 Reset Peak Demand Watts Reset Energy Reset Timestamped Event Buffer Reset (Synchronize) Demand Watts and Demand Current Window
1 1 1 1 1
BOOL BOOL BOOL BOOL BOOL
no-units no-units
1 1 1 1 1 1 1 1 1
BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL
2208 2209 2210 2227 2228 2222 2224 2225 2226
Eaton Corporation
Save Energy Request Reset Peak Demand Currents Reset Min/Max Current %THD Reset Min/Max Voltage %THD Advance Time-Stamped Event Buffer Reset INCOM Slave Interface Statistics Reset Product Specific Statistics Ack Energy Reset
f/w 3.11
no-units no-units no-units no-units no-units no-units no-units no-units no-units no-units no-units no-units
Writable
Possible Values
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
4/14/2010