Bear Claw Design Guide Lightweight Rear Ventilated Rain Screen (TO BE USED IN CONJUNCTION WITH DESIGN GUIDE SYSTEM2)
ENGINEERED ASSEMBLIES 1-866-591-7021 info@engineeredassemblies.com
E A T c L i p ™ RV R S Wa l l S y s t e m
INTRODUCTION We are pleased to provide you thermal and structural testing and analysis for TClip; Thermally Broken Subsystem for use with a variety of facades fibre cement, solid phenolic, Assemblies ceramic, wood This manualincluding: provides information on the Engineered Inc. veneer, porcelain, etc. BearClaw system & methodology, for lightweight, thermally broken, façade substructures and panel products. INTRODUCTION This guide provides thermal and structural analysis of Engineered Assemblies’ TClip; Thermally Broken Subsystem. The TClip system supports a variety of façade panels. The main purpose of this guide is to create a better understanding of the performance capabilities and benefits of TClip. DISCLAIMER Referuse to the “Quick References” section of this guideoffor a breakdown The of this information shows your acceptance these terms. of performance details and system drawings. System drawings 1, 2 The information is intended to provide background information on and 3 (pgs. 8-10) detail Engineered Assemblies Hidden Fastening Façade system. products provided by Engineered Assemblies Inc. although Engineered Assemblies Inc. makes reasonable efforts to present DISCLAIMER information which is up to date and accurate. Engineered Assemblies The use of this information shows your acceptance of these terms. Inc. no representation to the adequacy, accuracy The makes information is intended or to warranty provide as background information on completeness or correctness of envelope such information, does it warrant Engineered Assemblies building systems;nor specifically TClip; Thermally Broken Subsystem with reference to the Hidden Fastener or represent that the information provided is complete in every respect. System. Engineered assemblies inc. shall not have liability resulting from the use of the information the absence of any specific information, Although Engineeredprovided, Assemblies Inc. makes reasonable efforts to present information whichoristechnical up to date and Engineered the possible interruptions errors of accurate. this information and/or Assemblies Inc. makes no representation or warranty as to the the content herein. adequacy, accuracy completeness or correctness of such information, nor does it warrant or represent that the information provided is complete in every respect. Your Engineered Assemblies Inc. Team Engineered Assemblies Inc. shall not have liability resulting from the use of the information provided, the absence of any specific information, the possible interruptions or technical errors of this information and/or the content herein.
brilliant buildings Your Engineered Assemblies Inc. Team
page 5 FEB2016
E A T c L i p ™ RV R S Wa l l S y s t e m
Engineered Assemblies (EA) BearClaw Executive Summary In response to the rapidly increasing demand for lightweight, high performance, rear hung Façade systems, EA has designed the BearClaw The system is comprised of aluminum cleats and Rails connected to vertical subgirts (framing members). The cleats are designed to attach to cladding products through the use of synthetic polymer bonding agents by Dynamic Bond, undercut anchor or blind fastener. Structural Performance The BearClaw is engineered to accommodate façade panels generally 8-1 3 mm in thickness and up to 35kg/m2. When used in conjunction with SYSTEM2,vertical framing members are required. The vertical framing members are attached back to horizontal framing members.The horizontal framing member attaches to the TcLip™ S2 and can be adjusted to plumb out the structure. The spacing of the horizontal framing is adjustable to suite the design loads imposed on the system. *Note: This guide is to be used in conjunction with ‘RVRS SYSTEM2 Design Guide’. Use of the BearClaw system may require training and certification in the use of Dynamic Bond. Data on Dynamic Bond performance and testing available upon request. Contact Engineered Assemblies for more information on this matter.
page 6 FEB2016
For further information please visit: www.engineeredassemblies.com
brilliant buildings
ENGINEERED ASSEMBLIES
TABLE OF CONTENTS
INTRODUCTION TABLE OF CONTENTS 6mm THK. PORCELAIN w/ DYNAMIC BOND
8mm THK. FRC w/ DYNAMIC BOND
8mm THK. PHENOLIC w/ DYNAMIC BOND
10mm THK. PHENOLIC w/ BLIND FASTENER
12mm THK. FRC w/ UNDERCUT ANCHOR
PART SPECIFICATIONS FOR ENGINEERED ASSEMBLIES WALL SYSTEM PANEL INSTALLATION INSTRUCTIONS
(BEAR CLAW) ENGINEERED ASSEMBLIES
6mm THICK PORCELAIN TILE w/ DYNAMIC BOND
(BEAR CLAW) ENGINEERED ASSEMBLIES
6mm THICK PORCELAIN TILE W/ DYNAMIC BOND 163 25 VENTING PLENUM
102 [4"] INSULATION
1
23
100
35
12
4
38
13
30
12
6
16
12
26
15 35
18
25 12 12
4
12
35
12
4
75
10
19
8
12
31
51
38
10
4
47
50
SECTION DETAIL
(BEAR CLAW) ENGINEERED ASSEMBLIES
6mm THICK PORCELAIN TILE W/ DYNAMIC BOND
400 MAX C.C. TCLIP
600 MAX C.C. VERTICAL HATBAR 19
40
10
8
25
19
19
10
150 DYNAMIC BOND
10
300 MAX CUT TO SUIT BC-B/BC-M CONTINUOUS
PLAN DETAIL
40
19
10
150 DYNAMIC BOND
25
8
(BEAR CLAW) ENGINEERED ASSEMBLIES
8mm THICK FRC w/ DYNAMIC BOND
(BEAR CLAW) ENGINEERED ASSEMBLIES
8mm THICK FRC W/ DYNAMIC BOND 165 25 VENTING PLENUM
102 [4"] INSULATION
1
23
100
35
12
4
38
13
30
12
8
16
12
26
15 35
18
25 12 12
4
12
35
12
4
75
10
19
8
12
31
51
38
10
4
47
50
SECTION DETAIL
(BEAR CLAW) ENGINEERED ASSEMBLIES
8mm THICK FRC W/ DYNAMIC BOND
400 MAX C.C. TCLIP
600 MAX C.C. VERTICAL HATBAR 19
40
10
8
25
19
19
10
150 DYNAMIC BOND & CLIP
PLAN DETAIL
40
10
300 MAX
19
10
150 DYNAMIC BOND & CLIP
25
8
(BEAR CLAW) ENGINEERED ASSEMBLIES
8mm THICK PHENOLIC w/ DYNAMIC BOND
(BEAR CLAW) ENGINEERED ASSEMBLIES
8mm THICK PHENOLIC W/ DYNAMIC BOND 165 25 VENTING PLENUM
102 [4"] INSULATION
1
23
100
35
12
4
38
13
30
12
8
16
12
26
15 35
18
25 12 12
4
12
35
12
4
75
10
19
8
12
31
51
38
10
4
47
50
SECTION DETAIL
(BEAR CLAW) ENGINEERED ASSEMBLIES
8mm THICK PHENOLIC W/ DYNAMIC BOND
400 MAX C.C. TCLIP
600 MAX C.C. VERTICAL HATBAR 19
40
10
8
25
19
19
10
150 DYNAMIC BOND & CLIP
PLAN DETAIL
40
10
300 MAX
19
10
150 DYNAMIC BOND & CLIP
25
8
(BEAR CLAW) ENGINEERED ASSEMBLIES
10mm THICK PHENOLIC w/ DYNAMIC BOND
(BEAR CLAW) ENGINEERED ASSEMBLIES
10mm THICK PHENOLIC W/ BLIND FASTENER 167 30
25 VENTING PLENUM
102 [4"] INSULATION
1
38
13
10
16
23
50
7
47
1
100
8
2
31
10
26
75
35
18
15
8
19
38
10
51
8
2
1
7
SECTION DETAIL
(BEAR CLAW) ENGINEERED ASSEMBLIES
10mm THICK PHENOLIC W/ BLIND FASTENER
400 MAX C.C. TCLIP
600 MAX C.C. VERTICAL HATBAR 19
25
7
12
1
26
7
2 8
12
600 MAX C.C. BEAR CLAW CLIP SPACING
19
10
12
26 50mm BEAR CLAW
50mm BEAR CLAW
PLAN DETAIL
40
10
1
10
8
10
19
8
40
12
2
19
25
8
(BEAR CLAW) ENGINEERED ASSEMBLIES
12mm THICK FRC w/ DYNAMIC BOND
(BEAR CLAW) ENGINEERED ASSEMBLIES
12mm THICK FRC W/ UNDERCUT ANCHOR 169 30
25 VENTING PLENUM
102 [4"] INSULATION
1
38
13
12
16
23
9.5
100
2.5
47
50 31
10
26
75
35
18
15
8
19
38
10
51
2.5
9.5
SECTION DETAIL
(BEAR CLAW) ENGINEERED ASSEMBLIES
12mm THICK FRC W/ UNDERCUT ANCHOR
400 MAX C.C. TCLIP
600 MAX C.C. VERTICAL HATBAR 19
40
19
10
40
10
19
10
2.5
9.5
10
19
8
25
50mm BEAR CLAW
50mm BEAR CLAW 600 MAX C.C. BEAR CLAW CLIP SPACING
PLAN DETAIL
25
8
ENGINEERED ASSEMBLIES
PART SPECIFICATIONS FOR ENGINEERED ASSEMBLIES WALL SYSTEMS
E.A.I. STANDARD WALL SYSTEM
GENERAL NOTES
ENGINEERED ASSEMBLIES
PART SPECIFICATIONS FOR ENGINEERED ASSEMBLIES WALL SYSTEMS
ENGINEERED ASSEMBLIES
PANEL INSTALLATION INSTRUCTIONS 8mm FRC W/ DYNAMIC BOND
ENGINEERED ASSEMBLIES
PANEL INSTALLATION INSTRUCTIONS 8mm PHENOLIC W/ DYNAMIC BOND
ENGINEERED ASSEMBLIES
PANEL INSTALLATION INSTRUCTIONS 6mm PORCELAIN W/ DYNAMIC BOND
ENGINEERED ASSEMBLIES
PANEL INSTALLATION INSTRUCTIONS 10mm PHENOLIC W/ BLIND FASTENER
ENGINEERED ASSEMBLIES
PANEL INSTALLATION INSTRUCTIONS 12mm FRC W/ UNDERCUT ANCHOR