CONTROL PANEL INTERIOR

The optional control panel has a twelve-lamp moni­ toring system. The following describes each lamp function.

Generator AC Voltage Regulator

The solid-state regulator (VRAS-2) controls AC out­ put voltage from the generator at a predetermi:ied level regardless of load. Voltage reguiation is plus or minus three percent from no load to full load. Ran­ dom voltage variation is p!us or minus one percent for constant loads.

• RUN (green) lamp comes on when both starter circuits are opened after unit starting. • PRE LO OIL PRES (yellow) indicates engine oil pressure is marginally low.

Engine Control Module

:: PRE H! ENG TEMP (yellow) indicates engine temperature is marginally high.

Electronic and relay components of the er.gine mor:i­ torlng circuit are on a circuit.board assembly. Sensor inputs (Figure 2) are connected by the wiring har:iess to plug connectors on the board. The cont:c: �oduie provides the following functions of unit protection.

• LO Oll PRES (red) indicates engine has shut down because of critically low oil pressure. • HI ENG TEMP (red) indicates engine has shut down because of critically high temperature.

• Overcrank- limits engine cranking to 75 seconds. If engine fails to start, the module lights a fault lamp and opens the cranking circuit. The cycle cranking option allows three 15-second cranking cycles with two 15-second rest periods on the 12-lamp control.

• OVERSPEED (red) indicates engine has shut down because of excessive speed. • OVERCRANK (red) indicates the starter has been locked out because of excessive cranking time.

• Overspeed - shuts down the engine immediately if overspeed occurs and lights a fault lamp. The sen­ sor switch is mounted in the end bell on the gener­ ator shaft. It is factory adjusted to shut down 60 hertz units at 2200 ± 100 r/min, 50 hertz units at 1900 ± 100 r/min.

• FAULT 1 (red) an undedicated fault. May be factory programmed as a shutdown or non-shutdown, and as a timed or non-timed fault. (Normally set for timed shutdown). • FAULT 2 (red) S ame features as Fault 1 (Normally set for timed shutdown).

• Low Oil Pressure - shuts down the engine imme­ diately if oil pressure drops below 14 psi (97 kPa) and lights a fault lamp. The fault is time delayed about 10 seconds foliowing starter disconnect and inhibited during cranking. The delay allows oi: pressure to rise to normal before the electronic control module monitors this system.

• LOW ENG TEMP (yellow) engine temperature is marginally low for starting. Indicates inoperative coolant heater. • LO FUEL (yellow) indicates fuel supply is margi­ nally low.

A pre-low oil pressure sensor and lamp (used with optional 12-lamp system) provides an alarm that oil pressure is marginally low (20 psi/138 kPa or less). The cause should be found and corrected as soon

• SWITCH OFF (flashing red) indicates generator set is not in automatic start operation mode.