STANDARD DCS SYMAL‐FUSE™ SIZES COMMON SIZE
CONTAINMENT PIPE
SDR
WALL
CARRIER PIPE
SDR
WALL
ANULAR SPACE
MUST BE BETWEEN 80% AND 120%
3 X 1 3 X 1 1/4 3 X 1 1/2 4 X 2 4 X 2 6 X 3 6 X 3 6 X 4 8 X 4 10 X 6 12 X 8 14 X 10 16 X 10 18 X 12 18 X 14 20 X 14 20 X 16 22 X 16 22 X 18 24 X 18 26 X 20 28 X 22 30 X 24 32 X 24
3.5 3.5 3.5 4.5 4.5 6.625 6.625 6.625 8.625 10.75 12.75 14 16 18 18 20 20 22 22 24 26 28 30 32
17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 15.5 17 15.5 17 17 15.5 15.5 17
0.206 0.206 0.206 0.265 0.265 0.390 0.390 0.390 0.507 0.632 0.750 0.824 0.941 1.059 1.059 1.176 1.290 1.294 1.419 1.412 1.529 1.806 1.935 1.882
1.315 1.66 1.9 2.375 2.375 3.5 3.5 4.5 4.5 6.625 8.625 10.75 10.75 12.75 14 14 16 16 18 18 20 22 24 24
7 9 9 9 11 9 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11
0.188 0.184 0.211 0.264 0.216 0.389 0.318 0.409 0.409 0.602 0.784 0.977 0.977 1.159 1.273 1.273 1.455 1.455 1.636 1.636 1.818 2.000 2.182 2.182
0.887 0.714 0.594 0.798 0.798 1.173 1.173 0.673 1.555 1.430 1.313 0.801 1.684 1.566 0.941 1.824 0.710 1.706 0.581 1.588 1.471 1.194 1.065 2.118
91% 90% 103% 100% 82% 100% 82% 105% 81% 95% 105% 119% 104% 109% 120% 108% 113% 112% 115% 116% 119% 111% 113% 116%
WHEN USING A SIMULTANEOUSLY FUSED DUAL CONTAINMENT SYSTEM, IT IS VERY IMPORTANT THAT PIPE WALL THICKNESS OF EACH PIPE IS WITHIN A 20% RANGE OF EACH OTHER TO MAINTAIN A HEAT AND PRESSURE RELATIONSHIP AS WELL AS BEING ASSURED THE BLIND FUSION (THE INTERNAL CARRIER PIPE) IS BEING HEATED AND WELED PROPERLY. NOTE THAT AS THE CARRIER PIPE SDR BECOMES THICKER OR THINNER, THE SAME CAN BE ACCOMPLISHED WITH THE CONTAINMENT PIPE. AS AN EXAMPLE 14" SDR 32.5 AND 10" SDR 26 WOULD BE TWO PIPES THAT COULD BE SIMAL‐FUSED USING THESE PARAMETERS AS THEIR WALL THICKNESSES ARE WITHIN 4% OF EACH OTHER. PLEASE CHECK WITH HCF ON ANY QUESTIONS. 14 X 10
14 32.5 0.431 10.75 26 0.413 1.194 96% COPYRIGHT 2019 HIGH COUNTRY FUSION, A DIVISION OF CONSOLIDATED PIPE & SUPPLY CO, INC. www.HighCountryFusion.com 800‐780‐6330