Sheet Metal Connectors, Inc. SPECIFICATIONS FOR
DOUBLE WALL SPIRAL PIPE AND FITTINGS
MINNEAPOLIS, MN 5850 Main Street N.E. Minneapolis, MN 55432 LOCALLY CALL: 763-572-0000 TOLL FREE: 1-800-328-1966 FAX: 763-572-1100
ROCKFORD, IL 5601 Sandy Hollow Road Rockford, IL 61109 LOCALLY CALL: 815-874-4600 TOLL FREE: 1-866-504-4600 FAX: 815-874-9979
Corporate Headquarters
SHEET METAL CONNECTORS, INC. 5850 MAIN STREET N.E. • MINNEAPOLIS, MINNESOTA 55432 Toll Free: 800-328-1966 Local: 763-572-0000 Fax: 763-572-1100 www.smcduct.com
Manufacturing Facilities 5850 Main Street N.E. Minneapolis, MN 55432 LOCAL: 763-572-0000 TOLL FREE: 1-800-328-1966 FAX: 763-572-1100
5601 Sandy Hollow Road Rockford, IL 61109 LOCAL: 815-874-4600 TOLL FREE: 1-866-504-4600 FAX: 815-874-9979
Sheet Metal Connectors, Inc. is proud to be a member or affiliated with the following associations;
Sheet Metal Workers’ International Association Washington, DC
Sheet Metal Air Conditioning Contractors’ National Association Chantilly, VA
SPIDA Spiral Duct Manufacturers Association Irmo, SC
SMACNA Testing & Research Institute Chantilly, VA
1
Double-Wall Round Spiral Pipe & Fittings Sheet Metal Connectors, Inc. (SMC) Double Wall Pipe and Fittings with E-Z Flange and Barrel Clamp or Standard Slip Connection Sheet Metal Connectors, Inc. double wall round spiral duct and fittings are one part of our complete line of HVAC products. Double wall round spiral duct has two different types of applications: • Acoustical double wall for noise control • Thermal double wall duct for temperature control SMC double wall round spiral pipe and fittings are manufactured with an E-Z Flange with Barrel Clamp, E-Z Flange Jr. with Barrel Clamp or standard slip construction. All sizes shall be listed using inside dimensions.
5"
Lateral section of 4-ply pressure-proof spiral seam. 5"
Lateral section of grooved seam with optional corrugated grooves. 5
Optional culvert groove.
Acoustical Double Wall
Standard acoustical double wall is for noise control. Constructed of a perforated inner shell surrounded by a layer of insulation and covered by a solid outer shell. The perforated inner shell has 3/32” diameter holes staggered at 3/16” on center for a clear open area of 23%.
Solid Outer Shell DIAMETER 5” - 96” 5” - 96” 5” - 96” 5” - 60” 5” - 60”
MATERIAL Galvanized Paint Grip PVS* Aluminum Stainless Steel
THICKNESS 26 - 14 gauge 24 - 18 gauge 24 - 16 gauge .032 - .063 24 - 18 gauge
ASTM A-653 A-653 A-653 B-316 A-240
TYPE G60-G90 A60 4 x 1, 4 x 4 3003 H-14 304 or 316
LENGTH 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard
THICKNESS 24 - 22 gauge
ASTM A-653
TYPE G60-G90
LENGTH 1’ – 20’, 10’ Standard
*PVS specification book available
Perforated Inner Shell DIAMETER 3” - 94”
MATERIAL Galvanized
*Special order perforated available in other materials - consult factory
Thermal Double Wall Standard thermal double wall is for temperature control. Constructed of a solid shell surrounded by a layer of insulation and covered by a solid outer shell.
Solid Outer and Inner Shell DIAMETER 3” - 96” 3” - 96” 3” - 96” 3” - 60” 3” - 60”
MATERIAL Galvanized Paint Grip PVS* Aluminum Stainless Steel
THICKNESS 26 - 14 gauge 24 - 18 gauge 24 - 16 gauge .032 - .063 24 - 18 gauge
ASTM A-653 A-653 A-653 B-316 A-240
TYPE G60-G90 A60 4 x 1, 4 x 4 3003 H-14 304 or 316
LENGTH 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard 1’ – 20’, 10’ Standard
*PVS specification book available
Note: SMACNA Testing and Research Institute verified that Sheet Metal Connectors, Inc. shop standards comply with the 1995-2nd edition of the SMACNA HVAC Duct Construction Standards.
SHEET METAL CONNECTORS, INC. MARCH 2004
2
Double-Wall Connections Double Wall E-Z Flange Jr. with Barrel Clamp - 6” to 24” Diameter The Double Wall E-Z Flange Jr. is a 5/8” flange turned out 90° on the outer shell. A 1-3/8” angle flange is inserted into the inner shell. The two flanges are then tack welded together creating a double wall E-Z Flange Jr. This double wall E-Z Flange Jr. can be shipped in sets or factory installed. A set consists of two double wall E-Z Flange Jr. and one barrel clamp. For field installation the installer attaches the double wall E-Z Flange Jr., applies a gasket on one flange, mates the two double wall E-Z Flange Jr. together and attaches the barrel clamp. For field cuts a 5/8” double wall flange sleeve is available, cut the spiral pipe to the measured length and apply the sleeve.
Spot Weld
5/8" Flange Turned 90° on Spiral
1 3/8" Insulation
1 3/8"
Double Wall E-Z Flange with Barrel Clamp - 26” to 96” Diameter The double wall E-Z Flange with Barrel Clamp can be shipped in sets or factory installed. A set consists of two double wall E-Z Flanges and one barrel clamp. For field installation the installer attaches the double wall E-Z Flange to the pipe and fittings. Next the installer applies the gasket to one flange, mates the two double wall flanges together and attaches the barrel clamp. Sheet Metal Connectors also installs double wall E-Z Flanges. Flanges are spot welded and internally sealed on all ends of the spiral pipe and fittings.
5/8" 1 1/2"
Tack Weld
1 1/2" 1 3/8"
1 3/8"
Double Wall Standard Spiral Pipe Connector Pipe to Pipe connections are made by using a double wall fitting size coupling that slips inside the mating pipe sections, as shown. A stop bead runs around the middle of the coupling to center the coupling in the connection. Secure the connections by installing sheet metal screws through the outer shell of the duct, 1/2” from the stop bead.
SHEET METAL CONNECTORS, INC.
Spot Weld
Insulation
1"
2"
2"
B
A
11/2"
4 3/8"
3
Sheet Metal Connectors Double Wall Fittings Sheet Metal Connectors, Inc. double wall duct has a complete line of compatible fittings. Fittings can be fabricated with standing seam, elbow lock or welded seam construction. Double wall fittings can be fabricated to desired length and many different configurations. All sizes shall be listed using inside dimensions.
Elbow Lock Seam
All fittings can be manufactured with: • E-Z Flange Jr. with Barrel Clamp - 6” to 24” Diameter • E-Z Flange with Barrel Clamp - 26” to 96” Diameter • Double Wall Couplings
Standing Seam
Insulation
Butt Weld Seam
SMC double wall round spiral duct is a dependable, erosion resistant alternative to lined round spiral duct, providing improved protection for insulation exposed to the airstream. In double wall round spiral duct a metal inner liner insures that high airflow velocities cannot separate insulation by pulling away from the duct’s outer wall and creating erosion or airflow problems. SMC constructs each piece with an inner shell (perforated or solid) surrounded by a layer of insulation and covered by a solid outer shell. The insulation is used in both acoustical and thermal duct systems. SMC solves air quality problems caused by bacteria and other contaminants that can embed in fibrous materials, which can be a health hazard in environments such as schools, hospitals, laboratories, and food or pharmaceutical plants. In cases where additional erosion or contamination protection is desired for such an environment, we can provide a customer specified barrier material (mylar) between the insulation and the perforated liner. Standard insulation is 1” thick with 1 1/2 lb. per cubic foot density. See chart below for specifications. Many other thickness’ and densities are available, consult factory. SOUND ABSORPTION COEFFICIENTS (ASTM C 423, Type A Mounting) 1/3 Octave Band Center Frequency (cycles/sec.) Type
125
250
500
1000
2000 4000 NRC
1” - 1 1/2 # Cu. Ft.
.09
.31
.55
.72
.86
.93
.60
2” - 1 1/2 # Cu. Ft.
.18
.58
.79
1.02
1.06
.99
.85
1” - 3 # Cu. Ft.
.09
.28
.63
.86
.91
.92
.65
Coefficients determined per ASTM E 795 Type A Mounting Note: Pressure classifications are based on SMACNA Second Edition - 1995
THERMAL CONDUCTANCE “C” AND RESISTANCE “R” (ASTM C 177) Product
Mean Temperature 75˚F (24˚) Resistance “R”(2) Conductance “C”(1)
1” - 1 1/2 # Cu. Ft.
.28 (1.59)
3.6
2” - 1 1/2 # Cu. Ft.
.14
7.1 (1.26)
1” - 3 # Cu. Ft.
(.80)
.24 (1.36)
4.2
(.36)
(.73)
1 The lower the value, the better the performance. 2 The higher the value, the better the performance.
Specification Compliance SMC standard insulation meets the requirements of the following codes and specifications: NFPA 90A and NFPA 90B NAIMA Standard AHC-101 ASTM C 1071 Type 1 Replaces HH-I-545B Type 1
SHEET METAL CONNECTORS, INC.
4 Single Wall Weight and Gauge Chart
Positive Pressure Bursting Pressure various gauges of spiral tubing
Diam.
26 Gauge lbs./ft.
24 Gauge lbs./ft.
22 Gauge lbs./ft.
20 Gauge lbs./ft.
18 Gauge lbs./ft.
16 Gauge lbs./ft.
3” 4” 5” 6” 7” 8” 9” 10” 11” 12” 13” 14” 15” 16” 17” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36” 38” 40” 42” 44” 46” 48” 50” 52” 54” 56” 58” 60”
0.8 1.1 1.4 1.6 1.9 2.1 2.4 2.6 2.9 3.2 3.5 3.8 4.1 4.4 4.6 4.9 5.5 6.0 6.5 7.1 7.6 8.2 8.7 9.3 9.8 10.4 10.9 11.5 12.0 12.5 13.1 13.6 14.2 14.7 15.3 15.8 16.4
1.1 1.4 1.7 2.0 2.4 2.8 3.1 3.4 3.8 4.1 4.5 4.8 5.1 5.5 5.8 6.1 6.8 7.5 8.2 9.0 9.7 10.4 11.1 11.8 12.5 13.2 13.9 14.6 15.3 16.0 16.7 17.4 18.1 18.8 19.5 20.2 20.9
1.3 1.7 2.1 2.5 2.9 3.3 3.8 4.2 4.6 5.0 5.4 5.8 6.2 6.6 7.1 7.5 8.3 9.1 9.9 10.8 11.6 12.4 13.3 14.1 14.9 16.1 16.9 17.7 18.6 19.5 20.3 21.2 22.0 22.9 23.7 24.5 25.4
1.5 2.0 2.5 3.0 3.4 3.9 4.4 4.9 5.4 5.9 6.4 6.9 7.4 7.8 8.3 8.8 9.8 10.8 11.7 12.7 13.7 14.6 15.6 16.6 17.6 18.5 19.5 20.5 21.5 22.5 23.4 24.5 25.9 26.9 27.9 28.9 29.9
3.2 3.9 4.6 5.2 5.9 6.5 7.1 7.8 8.5 9.1 9.8 10.4 11.1 11.7 13.0 14.3 15.6 16.9 18.2 19.5 20.8 22.0 23.3 24.6 25.9 27.2 28.5 29.8 31.1 32.4 33.7 34.8 36.3 37.4 38.9
4.0 4.5 5.6 6.3 7.2 7.9 8.7 9.5 10.2 11.1 11.9 12.7 13.4 14.2 15.8 17.4 19.0 20.6 22.2 23.8 25.4 26.9 28.5 30.1 31.7 33.3 34.9 36.4 38.0 39.6 41.3 42.9 44.5 46.0 47.3
Standard gauges in boxed area, weights may vary slightly.
To calculate weight of Double Wall Spiral: (Weight of Inner Shell) + (Weight of Outer Shell) = Lbs./Ft. Example: 10’ - 0” of 20”Ø Double Wall 20”Ø I.D. 24 Gauge = 6.8 lbs./ft. x 10’ = 68# 22”Ø O.D. 22 Gauge = 9.1 lbs./ft. x 10’ = 91# Weight = 159# Less Insulation
Diam.
3” 4” 5” 6” 7” 8” 9” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36” 38” 40” 42” 44” 46” 48” 50”
26 Gauge
24 Gauge
22 Gauge
20 Gauge
18 Gauge
420 308 238 199 169 145 127 113 93 76 68
535 392 303 252 216 186 161 144 118 100 86 75 66 60
650 475 369 308 262 224 196 177 145 120 103 91 81 72 66 61 55 51 47
765 560 435 363 309 264 230 208 171 142 122 104 96 85 78 72 65 60 56 52 48 45 42 39
995 728 566 473 403 344 299 271 223 185 162 136 125 111 101 94 85 78 73 68 65 59 55 51 47 44 41 39
1 PSI = 27.678 H20 All tube diameters in inches. All pressure in PSI.
Internal Pressure Collapsing Pressure various gauges of spiral tubing Diam.
6” 8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36” 38” 40” 42” 44” 46” 48” 50” 60”
26 Gauge
220.4 69.2 34.6 22.0 15.3 11.0 9.0 7.8 7.2 5.5 5.1 4.7 4.3
24 Gauge
22 Gauge
121.2 110.6 55.1 38.5 27.5 20.8 16.5 14.1 11.8 9.8 8.6 8.2 6.6
691.7 249.2 110.6 105.1 53.9 38.5 30.3 24.8 20.8 18.1 15.3 13.7
5.5
11.0
4.3
9.8 9.0
.036 PSI = 1 inch H20
20 Gauge
1107.0 456.6 236.2 149.6 99.6 72.0 55.5 44.0 35.8 30.3 26.3 22.0 20.4 17.7 16.5 15.3 13.7 12.5 11.8 11.0
18 Gauge
16 Gauge
2767.7 1383.8 664.1 332.2 221.2 155.1 110.6 88.5 69.2 58.2 48.4 42.9 37.4 33.0 29.1 26.3 23.6 22.0 19.2 14.9
5258.6 2214.1 1245.6 692.1 387.4 290.5 243.7 166.1 128.7 103.9 85.8 72.0 62.2 53.9 47.2 41.3 37.4 34.6 24.8
Internal negative pressure in inches of water. These tables are given only as a courtesy. Sheet Metal Connectors is not responsible for any results listed on these charts.
5
Double Wall Pipe & Fittings Double Wall 90˚ Elbow with E-Z Flange and Barrel Clamp Inside dimensions to be listed Standard Throats 8” Thru 18” 8” Throat 20” Thru 40” 10” Throat 42” Thru 60” 20” Throat
Double Wall 45˚ Angle with E-Z Flange and Barrel Clamp Inside dimensions to be listed Standard Throats 8” Thru 18” 8” Throat 20” Thru 40” 10” Throat 42” Thru 60” 20” Throat
SHEET METAL CONNECTORS, INC.
6
Double Wall Pipe and Fitting C
Double Wall 90˚ Tee with E-Z Flange and Barrel Clamp
6"
4"
A
B
Inside dimensions to be listed A,B,C C+8
4"
C
Double Wall 45˚ Lateral with E-Z Flange and Barrel Clamp
3"
6" A
Inside dimensions to be listed A, B, C C + 2 x 1.414 + 9”=Length
B
LENGTH
1” or 2” Internal Insulation
Double Wall Pipe with E-Z Flange and Barrel Clamp Inside dimensions to be listed
Many Other Fittings Are Available, Please Consult Factory
SHEET METAL CONNECTORS, INC.
7
DP1010 WATER BASED DUCT SEALANT - Gray A smooth, water based, premium quality, U.L. 181 Classified, high velocity duct sealant for commercial and residential use. Available in 1/12 gallon tubes, 1 gallon pail, or 5 gallon pail. Recommended Uses: • Sealing metal joints on air duct where a smooth finish is desired • Sealing connections on flexible duct or fiberglass ductboard • Intended for use on duct systems which do not exceed 15 inches water column pressure
DP1090 SOLVENT BASED DUCT SEALANT A premium quality UL Classified high velocity duct sealant, for commerical use. Recommended Uses: • DP1090 is formulated for sealing low, medium and high-pressure metal duct systems in commerical and industrial applications • DP1090 is intended for use on duct systems which do not exceed 15 inches water column pressure • DP1090 is ideal for sealing rectangular, round, oval and metal flexible ducts.
DP2501 WATER BASED DUCT LINER ADHESIVE - Clear A water based, premium quality U.L. Classified duct liner adhesive. DP 2501 is specifically formulated for roller and low pressure spray applications. Available in 5 gallon pails, 54 gallon drum Recommended Uses: • Bonding fibrous duct liner installation to galvanized ductwork • Sealing cut edges of fiberglass insulation • Bonding kraft backed foil coverings to fiberglass and urethane flat stock or pipe insulation • Bonding multiple layers of fibrous insulation board
DP2502 WATER BASED DUCT LINER ADHESIVE - Clear A water based, premium quality U.L. Classified duct liner adhesive. DP 2502 is a higher viscosity version of DP 2501. DP 2502 is specifically formulated for spray, brush, and roller applications. Available in 5 gallon pails, 54 gallon drum Recommended Uses: • Bonding fibrous duct liner installation to galvanized ductwork • Sealing cut edges of fiberglass insulation • Bonding kraft backed foil coverings to fiberglass and urethane flat stock or pipe insulation • Bonding multiple layers of fibrous insulation board
DP 2590 SOLVENT BASED SPRAY ADHESIVE A premium quality, solvent based, fast drying, non-flammable, pressure sensitive insulation adhesive. DP 2590 is supplied in a convenient spray system which is both portable and cost effective. Available in 12# canister or 40# canister. Pro spray gun and 12’ hose sold separately. Recommended Uses: • Bonding fiberglass duct liner to galvanized steel, stainless steel and aluminum HVAC duct • Bonding fiberglass insulation to the exterior of galvanized steel, stainless steel and aluminum HVAC duct • Sealing and bonding laps in HVAC duct insulation • Adhering kraft backed foil and foil jacketing to urethane foam
DP 77 INDUSTRIAL SPRAY ADHESIVE Solvent based industrial strength aerosol duct liner spray adhesive. Available in 12 oz. spray cans. Recommended Uses: • Bonding galvanized metal, wood, fiberglass, foam rubber, cardboard, textiles, cloth and plastics
DP 2” CHIP BRUSH DUCT TAPE Product Number 557 Printed 229 339 Printed 330
Description Application Premium performance duct tape specifically engineered for flex duct systems. Meets UL 181B-FX & UL 723 Heavy duty contractor grade duct tape with extra thick adhesive for conformability Meets UL 723 Dead-soft aluminum foil backed duct tape for fiberglass duct systems. UL 181 A-P approved All-weather duct tape, working temperature range of -35°F to 260°F, plain dead soft aluminum foil, extremely conformable.
Colors
Adhesive
Total Thickness mils (mm)
Tensile Strength lbs/in (kg/cm)
Adhesion To Steel ozs/in (g/cm)
Grey
Natural Rubber
14.0 (0.36)
45 (8.01)
50 (560)
Grey
Natural Rubber
12.0 (0.30)
25 (4.45)
70 (784)
Silver
Acrylic
4.4 (0.11)
25 (4.45)
72 (806)
Silver
Acrylic
3.5 (0.08)
20 (3.56)
45 (504)
SHEET METAL CONNECTORS, INC.