1 minute read

RES Technical Corner by Brett Eliasz, PE

Technical Corner

For the article this month we will look at an approved method to determine clearances for oil filled transformers from a building and other transformers using FM Global requirements and the first letter of the 4-letter cooling class of the transformer. Note: transformers to be installed outside.

The following table shows the required clearances:

1. Determine if you have a FM approved transformer by getting the nameplate data and contacting the transformer manufacturer. (May be difficult-and forced to assume non-approved transformer).

2. Determine what type of oil you have by looking at the 4-letter cooling class code on the nameplate-

First Letterusually an “O” indicating an oil flash point less than 300 C-not a FM approved oil-will catch on fire faster. Otherwise, a “K” indicating an oil flash point of greater than 300 C-FM approved oil-will catch on fire slower.

3. Determine the gallons of oil in the transformer by looking at the nameplate-

4. Determine if the building exterior walls are Non-combustible, combustible or 2 hour fire rated: A. By asking an Architect (recommended) OR B. Use Informative Annex E of the 2017 NEC OR C. See footnote #1 in the table above.

The following table shows the required clearances between oil filled transformers:

Hopefully this article finds you well and can be used as a reference for your project needs. If anyone would like to contribute to the Rochester Engineer and add an article or would like to request information on a specific topic (not limited to Electrical) just email me at beliasz@bergmannpc.com. As always, any comments are appreciated…! Thank you for reading.

Brett Eliasz, P.E., LEED AP BD+C , RES Director

This article is from: