GRENTON ANALOG IN/OUT 0-10 V MUL-046-T-17
IN/OUT ANALOG MODULE FOR ASSEMBLY IN DIN RAIL
The in/out analog module for assembly in DIN rail expands the possibilities of the system and ensures support for popular communication standards used in automation: 0-10 V and 1-Wire.
PROPERTIES • • • •
features four inputs and four outputs 0-10 V fully configurable – the user can set input sensitivity, range of supported values, value scalar and inertias for input possible to connect any sensor operating in the 1-Wire standard possible to connect any sensor or receiver operating in the 0-10 V standard to the system
WIRING DIAGRAM
Sensor 0-10 V
Receiver 0-10 V
DS1820, DS18B20, etc. VDD DQ GND
1...16 UTP cable, max. 50 m
1W GND
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS OF 0-10 V OUTPUTS CHARACTERISTICS Value
Current output value (0.0 – 10.0 V)
ScaledValue
Current value multiplied by scalar
Scale
Output value scalar
Ramp
Time of output value increment (ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error. Range: 0.0 – 10.0 V
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error. Range: 0.0 – 10.0 V
METHODS SetValue
Sets output value (0.0 – 10.0 V)
SetScaledValue
Sets output value taking into account the scalar
SetScale
Sets scalar value
SetRamp
Sets increments for output value
SetMin
Sets MinValue
SetMax
Sets MaxValue
Hold
Reduces or increases the output value using a ramp specified in the parameter. If the ramp parameter is not specified, the default ramp is used
Switch
Switches output state to an opposite state. If time > 0, after a specified period it restores the previous state. The second parameter (ramp) is optional
SwitchOn
Sets output value to MaxValue (default 10.0 V). The first parameter is the time of switching (how long it is to be switched for). The second parameter (ramp) is optional
SwitchOff
Sets output value to MinValue (default 0.0 V). The first parameter is the time of switching (how long it is to be switched for). The second parameter (ramp) is optional
EVENTS OnChangeValue
Event from changing the output value (when SetValue is requested)
OnLowerValue
Event occurring when the set value is lower than the previous value
OnRiseValue
Event occurring when the set value is higher than the previous value
OnOutRange
Event occurring with an attempt to exceed the permissible range (MinValue .. MaxValue). (The set value is cut down to this range)
OnSwitchOn
Event occuring when MaxValue (default 10.0 V) is set at output
OnSwitchOff
Event occuring when MinValue (default 0.0 V) is set at output
CONFIGURATION PARAMETERS OF 0-10 V INPUTS CHARACTERISTICS Value
Current output value taking into account the scalar
Value%
Current percentage input value of the maximum value (MaxValue characteristic)
Scale
Input scalar – parameter which is used for multiplying the input value during reading
Sensitivity
Sensitivity – minimum change of input state when the OnChangeValue, OnLowerValue or OnRaiseValue event is generated
Inertia
Input inertia value
MinValue
Minimum value of the Value characteristic after exceeding which the OnOutRange event is generated
MaxValue
Maximum value of the Value characteristic after exceeding which the OnOutRange event is generated
METHODS SetScale
Sets scalar value (float)
SetSensitivity
Sets input sensitivity value
SetInertia
Sets input inertia value
SetMin
Sets MinValue
SetMax
Sets MaxValue
EVENTS OnChangeValue
Event resulting from changing input state
OnLowerValue
Event occurs when a value lower than the value from the last reading appears at input
OnRiseValue
Event occurs when a value higher than the value from the last reading appears at input
OnOutRange
Event resulting from exceeding the permissible range (MinValue .. MaxValue)
OnSwitchOn
Event occurs when the input value reaches MaxValue
OnSwitchOff
Event occurs when the input value reaches MinValue
CONFIGURATION PARAMETERS OF 1-WIRE SENSORS CHARACTERISTICS Value
Input value
Threshold
Hysteresis size (accuracy 0.1°C or 0.1%) specifying the sensitivity with which the following events are generated: OnChange, OnLower, OnRaise
Sensitivity
Time (in ms) for which the sampled values are averaged
MinValue
Minimum value of the Value characteristic after exceeding which the OnOutRange event is generated
MaxValue
Maximum value of the Value characteristic after exceeding which the OnOutRange event is generated
EVENTS OnChange
Event resulting from changing input state
OnRise
Event resulting from exceeding the upper threshold of hysteresis
OnLower
Event resulting from exceeding the lower threshold of hysteresis
OnOutOfRange
Event resulting from exceeding estabilished range (MinValue .. MaxValue)
TECHNICAL SPECIFICATION DC power supply
5V
max. current input
8.39 mA
weight
90 g
dimensions (H/W/D)
58/71/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
4
operating temperature range
0 to +40°C v. 1.1
GRENTON ANALOG IN/OUT 0-10 V MUL-067-T-17
IN/OUT ANALOGUE MODULE FOR FLUSH-MOUNT ASSEMBLY The in/out analogue module for flush-mount assembly expands the possibilities of the system and ensures support for popular communication standards used in automation: 0-10 V and 1-Wire.
PROPERTIES • • • •
features two inputs and two outputs (0-10 V) fully configurable – the user can set input sensitivity, range of supported values, value scalar and inertias for input it is possible to connect any sensor operating in the 1-Wire standard it is possible to connect any sensor or receiver operating in the 0-10 V standard to the system
WIRING DIAGRAM TF-Bus
TF-Bus
DS1820, DS18B20, etc. Receiver 0-10 V
VDD DQ GND
Sensor 0-10 V
UTP cable, max. 50 m 1...16
1W GND
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS OF 0-10 V OUTPUTS CHARACTERISTICS Value
Current output value (0.0 – 10.0 V)
ScaledValue
Current value multiplied by scalar
Scale
Output value scalar
Ramp
Time of output value increment (ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error. Range: 0.0 – 10.0 V
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error. Range: 0.0 – 10.0 V
METHODS SetValue
Sets output value (0.0 – 10.0 V)
SetScale
Sets scalar value
SetRamp
Sets increments for output value
SetMinValue
Sets MinValue
SetMaxValue
Sets MaxValue
Hold
Reduces or increases the output value using a ramp specified in the parameter. If the ramp parameter is not specified, the default ramp is used
Switch
Switches output state to an opposite state. If time > 0 after a specified period it restores the previous state. The second parameter (ramp) is optional
SwitchOn
Sets output value to MaxValue (default 10.0 V). The first parameter is the time of switching (how long it is to be switched for). The second parameter (ramp) is optional
SwitchOff
Sets output value to MinValue (default 0.0 V). The first parameter is the time of switching (how long it is to be switched for). The second parameter (ramp) is optional
EVENTS OnChangeValue
Event from changing output value (when SetValue is requested)
OnLowerValue
Event occurring when the set value is lower than the previous value
OnRiseValue
Event occurring when the set value is higher than the previous value
OnOutRange
Event occurring with an attempt to exceed the permissible range (MinValue - MaxValue). (The set value is cut down to this range)
OnSwitchOn
Event occuring when MaxValue (default 10.0 V) is set at output
OnSwitchOff
Event occuring when MinValue (default 0.0 V) is set at output
CONFIGURATION PARAMETERS OF 0-10 V INPUTS CHARACTERISTICS Value
Current input value taking into account the scalar
Value%
Current percentage input value of the maximum value (MaxValue characteristic)
Scale
Input scalar – parameter which is used for multiplying the input value during reading
Sensitivity
Sensitivity – minimum change of input state when the OnChangeValue, OnLowerValue or OnRaiseValue event is generated
Inertia
Input inertia value
MinValue
Minimum value of the Value characteristic after exceeding which the OnOutOfRange event is generated
MaxValue
Maximum value of the Value characteristic after exceeding which the OnOutOfRange event is generated
METHODS SetScale
Sets scalar value (float)
SetSensitivity
Sets input sensitivity value
SetInertia
Sets input inertia value
SetMin
Sets MinValue
SetMax
Sets MaxValue
EVENTS OnChangeValue
Event resulting from changing the input state
OnLowerValue
Event occurs when a value lower than the value from the last reading appears at input
OnRiseValue
Event occurs when a value higher than the value from the last reading appears at input
OnOutRange
Event resulting from exceeding the permissible range (MinValue - MaxValue)
OnSwitchOn
Event occurs when the input value reaches MaxValue
OnSwitchOff
Event occurs when the input value reaches MinValue
CONFIGURATION PARAMETERS OF 1-WIRE SENSORS CHARACTERISTICS Value
Input value
Threshold
Hysteresis size (accuracy 0.1°C or 0.1%) specifying the sensitivity when the following events are generated: OnChange, OnLower, OnRaise
MinValue
Minimum value of the Value characteristic after exceeding which the OnOutOfRange event is generated
MaxValue
Maximum value of the Value characteristic after exceeding which the OnOutOfRange event is generated
EVENTS OnChange
Event resulting from changing input state
OnRise
Event resulting from exceeding the upper threshold of hysteresis
OnLower
Event resulting from exceeding the lower threshold of hysteresis
OnOutOfRange
Event resulting from exceeding allowed range
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
8.39 mA
weight
38 g
dimensions (H/W/D)
52/57/21 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C v. 1.1
GRENTON CLU Z-Wave CLU-022-E-02
COMMON LOGIC UNIT FOR DIN RAIL ASSEMBLY The Common Logic Unit (CLU) module for DIN rail assembly, with Z-Wave wireless communication controller, executes the function of processing logic and storing the configuration. The CLU constitutes the basis for every system. The CLU module also ensures communication with IOM modules via a local busbar. It expands the communication possibilities of the GRENTON system with a wireless network.
PROPERTIES • • • • • • • • • • •
stores system configuration completes all calculations enables connection with the system features a built-in switch and two RJ45 ports allows you to connect 48 modules (or 128 inputs/outputs) to the system busbar executes the functionality of cloud computing (distributed computing) allows you to connect the system to the internet stores created scripts/scenes enables you to create virtual CLU objects (timers, calendars, schedules, PID controllers etc.) enables you to connect the system to any wireless device operating with the use of Z-Wave features a built-in busbar supply unit with 1000 mA capacity
WIRING DIAGRAM
12 - 24 VDC
Ethernet Switch 2 x RJ45
TF-Bus
Power Jack 12 – 24 VDC LEDs
TF-Bus
TF-Bus
RS232 service port
LED – status indication No supply
CLU in Z-Wave module removal mode - red diode blink in 200 ms intervals
Green diode blink every 500 ms – system ok
Confirmation of adding Z-Wave module green diode lights constantly for 1 second, then green and red diods blink three times in 200 ms intervals
Configuration error – system not configured or no communication with IOM module CLU in Z-Wave module discovery mode - green diode blink in 200 ms intervals
Confirmation of removing Z-Wave module - red and green diodes blink three times in 200 ms intevals, then red diode goes off and green diode blink in 500 ms interval
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Uptime
Time of device operation since last reset (in seconds)
Log
Internal device log
State
Device state
Date
Current date
Time
Current time (hh:mm:dd)
Day
Number of the current day of the month
Month
Current number of the month
Year
Current number of the year
DayOfWeek
Current day of the week (0 = Sunday)
Hour
Current hour (no minutes or seconds)
Minute
Current number of minutes from last full hour
UnixTime
Current Unix time
FirmwareVersion
Software version
METHODS NAME
DESCRIPTION
AddToLog
Adds a new entry to the internal log
ClearLog
Deletes the contents of the internal device log
SetDateTime
Sets date and time
StartZWaveDiscovery
Initiates Z-Wave module discovery mode (if time = 0 then only to the first added node)
StopZWaveDiscovery
Stops Z-Wave module discovery mode
EVENTS NAME
DESCRIPTION
OnInit
Event occurring once during device initialization
TECHNICAL SPECIFICATIONS DC supply
12 - 24 V
average current input
112 mA
max. current input
250 mA
Z-Wave frequency
868 MHz
weight
106 g
dimensions (H/W/D)
58/71/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
4
operating temperature range
0 to +40°C
built-in busbar supply unit
1000 mA
v. 1.1
GRENTON DIGITAL IN INP-018-T-16
DIGITAL INPUT MODULE FOR ASSEMBLY ON DIN RAIL Digital input module allows you to connect any digital input with the system.
PROPERTIES • • • • •
enables you to connect six independent binary inputs enables you to connect two 230 V inputs inputs are fully configurable operates in two modes: monostable and bistable differentiates a click in monostable mode: short press, long press, and hold button
WIRING DIAGRAM L
~230 V
N
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input mode as 0 or 1
Inertion
Minimum interval in milliseconds which has to pass between presses of a button so that it is interpreted as a new pressing activity
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds after which, when pressing and holding a button, the OnHold event occurs
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device, Pulse - measurement counted when the input state is high
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time; Pulse - consumption value per one pulse
METHODS NAME
DESCRIPTION
SetInertion
Sets Inertion value
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at input
OnSwitchOff
Occurs when the low state is set at input
OnShortPress
Occurs after pressing the button for 500 ms - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval Value
OnClick
Occurs after pressing the button for less than 500 ms
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
6.3 mA
weight
94 g
dimensions (H/W/D)
58/71/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
4
operating temperature range
O to +40°C
v. 1.1
GRENTON DIGITAL IN INP-029-T-16
DIGITAL INPUT MODULE FOR FLUSH-MOUNT ASSEMBLY Digital input module allows you to connect any digital input with the system.
PROPERTIES • • • • • •
enables you to connect four independent binary inputs enables you to connect two 230 V inputs inputs are fully configurable operates in two modes: monostable and bistable differentiates a click in monostable mode, short press, long press, and hold button recommended installation in a P80 flush or in a flush with side pocket
WIRING DIAGRAM
TF-Bus
~230 V
TF-Bus
L N
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input mode as 0 or 1
Inertion
Minimum interval in milliseconds which has to pass between presses of a button so that it is interpreted as a new pressing activity
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds, after which when pressing and holding a button, the OnHold event occurs
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device, Pulse - measurement counted when the input state is high
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time; Pulse - consumption value per one pulse
METHODS NAME
DESCRIPTION
SetInertion
Sets Inertion value
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at input
OnSwitchOff
Occurs when the low state is set at input
OnShortPress
Occurs after pressing the button for 500 - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval Value
OnCLick
Occurs after pressing the button for less than 500 ms
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
4.7 mA
weight
38 g
dimensions (H/W/D)
52/57/21 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
v. 1.1
GRENTON DIGITAL IN Z-Wave INP-038-Z-04
WIRELESS DIGITAL INPUT MODULE FOR FLUSH-MOUNT ASSEMBLY Wireless digital input module for flush-mount assembly allows you to connect any input with the system.
PROPERTIES • • • • • • •
enables you to connect four 230 V inputs inputs are fully configurable small size – fits into a P60 box under the ancillary equipment each input can carry out up to seven independent functions each function can request up to four events simultaneously operates with 230 V supply communicates with other wireless modules using a mesh network
WIRING DIAGRAM
~230 V
L N
MODULE INSTALLATION Connect the module according to the diagram above, and then add the Z-Wave module to CLU controller. To do this, follow these steps: 1. Press the “Link” button located on the CLU module (green LED blinks in 200 ms intervals). 2. Press the button located on the added Z-Wave module. If the module was added correctly, it will be signalled by three blinks of green and red LEDs on the CLU. After physically pairing the module with CLU, perform system configuration. In order to do so, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open a new project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input mode as 0 or 1
Inertion
Minimum interval in milliseconds which has to pass between presses of a button so that it is interpreted as a new pressing task
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds after which, when pressing and holding a button, the OnHold event occurs
METHODS NAME
DESCRIPTION
SetInertion
Sets Inertion value
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at input
OnSwitchOff
Occurs when the low state is set at input
OnShortPress
Occurs after pressing the button for 500 - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval Value
OnClick
Occurs after pressing the button for less than 500 ms
TECHNICAL SPECIFICATIONS AC supply
230 V
average current input
2 mA
max. current input
3 mA
Z-Wave frequency
868 MHz
weight
27 g
dimensions (H/W/D)
19/45/36 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
v. 1.1
GRENTON DIMMER Z-Wave DIM-041-Z-01
WIRELESS UNIVERSAL DIMMER MODULE FOR FLUSH-MOUNT ASSEMBLY Universal dimmer module enables smooth control of the light intensity level.
PROPERTIES • • • • • • • •
allows you to connect a lighting circuit with a total output of 350 W each of the dimmer responses (dimming, illuminating, activating, etc.) can generate up to 6 events and each event can execute up to 4 functions simultaneously enables you to define the maximum and minimum values for the lighting circuit features two 230 V inputs inputs are fully configurable small size – fits into a P60 box under the ancillary equipment operates with 230 V supply communicates with other wireless modules using a mesh network
WIRING DIAGRAM
~230 V
L N
~230 V
L N
MODULE INSTALLATION Connect the module according to the above diagram and connect the Z-Wave module with CLU Z-Wave controller. To do this: 1. Use the „Link” button on CLU module (green diode blinks in 200 ms intervals) 2. Use the linking button on Z-Wave module. Correct linking the module will be confirmed with a triple blinking of the both diodes on CLU. After physical addition of the module start a configuration. In order to do so, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Specifies the current output value (0.0 - 1.0)
RampTime
Delay value when changing illumination (in ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error. Range: 0.0 - 1.0
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error. Range: 0.0 - 1.0
METHODS NAME
DESCRIPTION
SetValue
Sets output value (0.0 - 1.0)
SetRampTime
Determines the time of output value increment (ms)
SetMinValue
Setting the minimum value which can be adopted by an output. Attempting to set a lower value will generate an error. Range: 0.0 - 1.0
SetMaxValue
Setting the maximum value which can be adopted by an output. Attempting to set a higher value will generate an error. Range: 0.0 - 1.0
Hold
Executes the function of illuminating/dimming
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds) The second parameter is the ramp (time of value increments) which is optional. If this parameter is not specified, the default ramp is used
SwitchOn
Sets output value to 1. The first parameter is the time of switching (how long it is to be switched for). The second parameter is the ramp (time of value increments) which is optional.
SwitchOff
Sets output value to 0. The first parameter is the time of switching (how long it is to be switched for). The second parameter is the ramp (time of value increments) which is optional.
EVENTS NAME
DESCRIPTION
OnChange
Event resulting from changing the output state
OnLowerValue
Event occurring when the set value is lower than the current value
OnRaiseValue
Event occurring when the set value is higher than the current value
OnOutOfRange
Event occurring when setting a value which is higher than the MaxValue or lower than the MinValue
OnSwitchOn
Event occurring when the output value is changed from 0 to a value higher than 0
OnSwitchOff
Event occurring when 0 is set at the output
INPUT PROPERTIES CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input mode as 0 or 1
Inertion
Minimum interval in milliseconds which has to pass between presses of a button so that it is interpreted as a new pressing activity
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds after which, when pressing and holding a button, the OnHold event occurs
METHODS NAME
DESCRIPTION
SetInertion
Sets Inertion value
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at the input
OnSwitchOff
Occurs when the low state is set at the input
OnShortPress
Occurs after pressing the button for 500 - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval Value
OnClick
Occurs after pressing the button for less than 500 ms
TECHNICAL SPECIFICATIONS AC supply
230 V
average current input
2 mA
max. current input
3 mA
Z-Wave frequency
868 MHz
weight
37 g
dimensions (H/W/D)
19/45/36
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
maximum load
350 W v. 1.1
GRENTON DIMMER
DIM-021-T-01
UNIVERSAL DIMMER MODULE FOR DIN RAIL ASSEMBLY Universal dimmer module for DIN rail assembly enables smooth control of the light intensity level.
PROPERTIES • • • • •
fully configurable enables the following functions: dimming, continuous activation, and specific-time activation controlled increment time enables you to connect a lighting circuit with a total output of 690 W enables you to define the maximum and minimum values for the lighting circuit
WIRING DIAGRAM ~230 V
L N Bulb
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Specifies the current output value (0.0 - 1.0)
RampTime
Delay value when changing illumination (in ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error. Range 0.0 - 1.0
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error. Range 0.0 - 1.0
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time
METHODS NAME
DESCRIPTION
SetValue
Sets output value (0.0 - 1.0)
SetRampTime
Determines the time of output value increment (ms)
SetMinValue
Setting the minimum value which can be adopted by an output. Attempting to set a lower value will generate an error. Range: 0.0 - 1.0
SetMaxValue
Setting the maximum value which can be adopted by an output. Attempting to set a higher value will generate an error. Range: 0.0 - 1.0
Hold
Executes the function of illuminating/dimming
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds) The second parameter is the ramp (time of value increments which is optional. If this parameter is not specified, the default ramp is used
SwitchOn
Sets output value to 1. The first parameter is the time of switching (how long it is to be switched for). The second parameter is the ramp (time of value increments) which is optional.
SwitchOff
Sets output value to 0. The first parameter is the time of switching (how long it is to be switched for). The second parameter is the ramp (time of value increments) which is optional.
EVENTS NAME
DESCRIPTION
OnChange
Event resulting from changing the output state
OnLowerValue
Event occurring when the set value is lower than the current value
OnRaiseValue
Event occurring when the set value is higher than the current value
OnOutOfRange
Event occurring when setting a value which is higher than the MaxValue or lower than the MinValue
OnSwitchOn
Event occurring when the output value is changed from 0 to a value higher than 0
OnSwitchOff
Event occurring when 0 is set at the output
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
8.39 mA
weight
104 g
dimensions (H/W/D)
58/36/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
2
operating temperature range
O to +40°C
maximum load
690 W
v. 1.2
GRENTON DIMMER
DIM-031-T-01
UNIVERSAL DIMMER MODULE FOR FLUSH-MOUNT ASSEMBLY Universal dimmer module for flush-mount assembly enables smooth control of the light intensity level.
PROPERTIES • • • • •
allows you to connect a lighting circuit with an output of 1x 350 W or 2x 250 W small size – fits into a P60 box under the ancillary equipment enables the following functions: dimming, continuous activation, and specific-time activation controlled increment time enables you to define the maximum and minimum values for the lighting circuit
WIRING DIAGRAM TF-Bus
TF-Bus
Bulb
~230 V
Bulb
L N
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Specifies the current output value (0.0 - 1.0)
RampTime
Delay value when changing illumination (in ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error. Range: 0.0 - 1.0
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error. Range: 0.0 - 1.0
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time
METHODS NAME
DESCRIPTION
SetValue
Sets output value (0.0 - 1.0)
SetRampTime
Determines the time of output value increment (ms)
SetMinValue
Setting the minimum value which can be adopted by an output. Attempting to set a lower value will generate an error. Range: 0.0 - 1.0
SetMaxValue
Setting the maximum value which can be adopted by an output. Attempting to set a higher value will generate an error. Range: 0.0 - 1.0
Hold
Executes the function of illuminating/dimming
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds) The second parameter is the ramp (time of value increments) which is optional. If this parameter is not specified, the default ramp is used
SwitchOn
Sets output value to 1. The first parameter is the time of switching (how long it is to be switched for). The second parameter is the ramp (time of value increments) which is optional.
SwitchOff
Sets output value to 0. The first parameter is the time of switching (how long it is to be switched for). The second parameter is the ramp (time of value increments) which is optional.
EVENTS NAME
DESCRIPTION
OnChange
Event resulting from changing the output state
OnLowerValue
Event occurring when the set value is lower than the current value
OnRaiseValue
Event occurring when the set value is higher than the current value
OnOutOfRange
Event occurring when setting a value which is higher than the MaxValue or lower than the MinValue
OnSwitchOn
Event occurring when the output value is changed from 0 to a value higher than 0
OnSwitchOff
Event occurring when 0 is set at the output
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
8.39 mA
weight
30 g
dimensions (H/W/D)
52/57/21 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
maximum load
1x 350 W or 2x 250 W
v. 1.1
GRENTON GATE ALARM INT-013-E-01
UNIVERSAL GATE MODULE FOR DIN RAIL ASSEMBLY
Module for integration with external devices and systems. Gate ALARM enables integration with Satel alarm system.
PROPERTIES • enables the service of up to 60 objects, such as zone, input, output, register • transmits information about the slave systems to the CLU enabling creating complex logic in the Grenton supervisory system • allows to create simple event-based configuration TECHNICAL SPECIFICATION power options
DC supply
12 - 24 V
TF-Bus
5V
max. current input for 12 V
80 mA
max. current input for 24 V
50 mA
weight
80 g
dimensions (H/W/D)
52/57/21 mm
operating temperature range
0 to +45°C
WIRING DIAGRAM
GND
12 - 24 VDC
LED diodes
GATE ALARM
Ethernet 8P8C **
TF-Bus *
TF-Bus *
Reset
*) The device can be alternatively powered by means of the TF-Bus connector that provides 5 VDC power supply. However, it is recommended to use external 12 - 24 VDC supplies as it improves the stability of the system. The device works as a TF-Bus relay so it can be easily installed in the middle of other Grenton modules. **) The GATE module communicates with the CLU unit via the Ethernet network/interface (8P8C Ethernet connector, so-called RJ-45). In order for the system to operate correctly the CLU device(s), the GATE ALARM module as well as the ETH interface of the Alarm device have to be connected to the same ethernet network. LED - status indication: No supply Green diode blinks - system OK Slave device reports an error Error or no configuration
ADDITIONAL INFORMATION Full instruction, technical specification and declaration of conformity are available on the website: www.grenton.com The general Warranty Terms & Conditions are available on the manufacturer’s website at: www.grenton.pl/gwarancja
v. 1.0
GRENTON GATE MODBUS INT-011-E-01
UNIVERSAL GATE MODULE FOR DIN RAIL ASSEMBLY
Module for integration with external devices and systems. Gate MODBUS enables integrations with every device supporting MODBUS RTU.
PROPERTIES • possibility to control any Modbus-based devices by means of a mobile application • great integration flexibility thanks to the support for simultaneous communication with various devices, which may also use different transmission parameters • reliable ethernet communication with the Grenton CLU unit
TECHNICAL SPECIFICATION power options
DC supply
12 - 24 V
TF-Bus
5V
max. current input for 12 V
80 mA
max. current input for 24 V
50 mA
weight
80 g
dimensions (H/W/D)
52/57/21 mm
operating temperature range
0 to +45°C
Modbus physical layer
RS-485
TECHNICAL SPECIFICATION
TERM Modbus termination **
12 - 24 VDC
TERM
ON OFF
LED diodes
Modbus B
GND
Modbus A
GATE MODBUS
Ethernet 8P8C TF-Bus *
TF-Bus *
Reset
*) The device can be alternatively powered by means of the TF-Bus connector that provides 5 VDC power supply. However, it is recommended to use external 12 - 24 VDC supplies as it improves the stability of the system. The device works as a TF-Bus relay so it can be easily installed in the middle of other Grenton modules. **) If the GATE MODBUS is located at a physical end of the bus (Modbus), a terminator jumper should be placed in the ON position. For correct operation of the Modbus, termination is required at both ends.
LED - status indication: No supply Green diode blinks - system OK Slave device reports an error Error or no configuration
ADDITIONAL INFORMATION Full instruction, technical specification and declaration of conformity are available on the website: www.grenton.com The general Warranty Terms & Conditions are available on the manufacturer’s website at: www.grenton.pl/gwarancja
v. 1.0
GRENTON GSM MUL-036-T-06
GSM COMMUNICATION MODULE FOR DIN RAIL ASSEMBLY The GSM communication module enables bidirectional connection of the user with the system using a mobile telephone network.
PROPERTIES • • •
sends information and receives requests “Ask” function – if any events occur, a text message is sent with a request for response enables you to divert a voice call to a mobile telephone
WIRING DIAGRAM
12 - 24 V LEDs
LED – status indication: Green diode flashes every 500 ms – no errors in the module, correct reception Red diode flashes every 500 ms – no reception Red diode is illuminated continuously – module not connected Red diode flashes ever 200 ms – no SIM card or card error Green diode flashes every 200 ms, for t = time – the module sent an enquiry with the Ask function and is awaiting response; t = time for awaiting response
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Inbox
Inbox containing the last text message received. Does not apply to Y/N text messages sent in response to queries made using the Ask() method
Outbox
Outbox containing the outgoing buffer
AccessList
List of numbers which can be used for sending requests, e.g. 555555555;666666666; A semi-colon must be included at the end!
ScriptList
List of scripts (scenes) which can be requested by text messages. List format: script1;script2;script3; etc. In practice, this will look as follows: waterplants;switchonboiler;switchoffboiler; A semi-colon must be included at the end!
Password
Password which must be included in a text message sent to the address of the gateway (if PassMandatory is set to 1)
PassMandatory
If set to 0, password is not required. If set to 1, password is required.
ConfirmMessage
A confirmation text message. If defined, it will be sent after each correct activation of a script whose name was sent via a text message
RefuseMessage
A refusal text message. If defined, it will be sent after each correct activation of a script whose name was sent via a text message
SignalLevel
Mobile network signal level in the range of 0 - 32
AskConfirm
Text specifying the form of a confirmation message for the Ask() method, e.g. “y”, “yes”
AskRefuse
Text specifying the form of a refusal message for the Ask() method, e.g. “n”, “no”
PIN
PIN code of SIM card
METHODS NAME
DESCRIPTION
ClearInbox
Clears the incoming buffer (inbox). The incoming buffer is cleared automatically when a new text message is received. This does not apply to text messages with Y/N confirmations.
ClearOutbox
Clears outgoing buffer (outbox)
AddToOutbox
Adds text to outgoing buffer (outbox)
SendOutboxTo
Sends outbox content to the specified number
Ask
A method which sends an enquiry to a telephone number. It returns 1 if the user received the message with a confirmation response and 0 if the response was a refusal or if the user did not respond in the required time (timeout). Parameters: Ask (tel. number; enquiry; timeout in s). At the end of the enquiry, the following text form is always added: [AskConfirm/AskRefuse] so for instance: [Y/N] or [yes/no].
Call
Calls the specified number. The method returns 1 if the connection is established or 0 when there is no connection
Drop
Drops the voice call
EVENTS NAME
DESCRIPTION
OnReceive
Occurs immediately after receiving a text message.
OnSend
The user can read an Inbox characteristic to check the text message content
OnStatus
Occurs immediately after sending a text message
OnCall
Occurs immediately after receiving a text message with the status command
OnScript
Occurs when a voice call is answered (only AccessList number calls are answered – the remainder are rejected)
TEXT MESSAGE COMMANDS NAME
DESCRIPTION
“Help” or “password:Help”
If the number is included on the AccessList (if created) and when the password is correct (if required), it returns a list of the available scripts (ScriptList characteristic)
“Status” or “password:Status”
Generates the OnStatus event
Name of script with or without password
When the user sends the following text message to the number of the gateway: lamp1, the OnScript event will be generated when the following conditions are met: - no password is required; - the number is on the AccessList (AccessList characteristic); - “lamp1” is on the list of available scripts (ScriptList characteristic). If the password is required, the text message should be as follows: “password:lamp1”, so the command must be preceded by the password. A colon, semi-colon, comma, period or slash can be used as the separator (i.e. any non-letter character).
TECHNICAL SPECIFICATIONS DC supply
12 – 24 V
average current input (with 12V)
17 mA
max. current input (with 12V)
1000 mA
weight
72 g
dimensions (H/W/D)
58/36/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
2
operating temperature range
0 to +40°C
NOTE: When you use an audio track, use the long antenna (GSM antenna).
v. 1.1
GRENTON LED RGB RGB-028-T-01
LED RGB LIGHTING CONTROL MODULE FOR DIN RAIL ASSEMBLY
LED RGB lighting control module for DIN rail assembly enables smooth and full control of decorative lighting using LED RGB technology.
PROPERTIES • • • • • •
dimming function – allows it to operate as a three-channel dimmer full freedom when setting the color: RGB or HSV model 16.8 million colors enables you to adjust both the saturation and hue smooth transition when changing color, saturation, and intensity nables you to set the ramp (transition time) for transitions between colors, saturation, and intensity of light
WIRING DIAGRAM COM
12/24 VDC
12/24 VDC COM
LED Red LED Green
LED 3 LED 2
LED Blue
LED 1
TF-Bus
TF-Bus
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Brightness value (range: 0 - 1)
Hue
Color hue value as per the HSV model (0 - 360)
Saturation
Color saturation value (0 - 1)
RValue
R component value (0 - 255) – Red
GValue
G component value (0 - 255) – Green
BValue
B component value (0 - 255) – Blue
#RGB
Color value as per the RGB model “#RRGGBB” (specified in HEX)
RampTime
Time value of increment of color and brightness (ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error.
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error.
RCorrection
White correction – channel R (0 - 10.000), default 10.000
GCorrection
White correction – channel G (0 - 10.000), default 8.333
BCorrection
White correction – channel B (0 - 10.000), default 8.333
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time
METHODS NAME
DESCRIPTION
SetValue
Sets output value (0 - 1)
SetHue
Sets hue value (0 - 360)
SetSaturation
Sets saturation value (0 - 1)
SetRValue
Sets R component value (0 - 255)
SetGValue
Sets G component value (0 - 255)
SetBValue
Sets B component value (0 - 255
Set#RGB
Sets RGB value using the “#RRGGBB” string
HoldValue
Executes illumination/dimming function
HoldHue
Executes smooth hue transition
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds) The second parameter is the ramp (time of value increments) which is optional. If this parameter is not specified, the default ramp is used
SwitchOn
Sets output value to MaxValue
SwitchOff
Sets output value to MinValue
SetRampTime
Sets value of increment of color and input (ms)
SetMax
Sets MaxValue
SetMin
Sets MinValue
EVENTS NAME
DESCRIPTION
OnChange
Event occurring when changing the output state
OnSwitchOn
Event occurring when the output state is changed from = 0 to > 0
OnSwitchOff
Event occurring when “0” is set at the output
OnRaiseValueSet
Event occurring when the set value is higher than the current value
OnLowerValueSet
Event occurring when the set value is lower than the current value
OnOutOfRange
Event occurring when setting a value which is higher than the maximum value or lower than the minimum value
TECHNICAL SPECIFICATION DC supply
5V
max. current input
8.39 mA
weight
90 g
dimensions (H/W/D)
58/71/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
2
operating temperature range
O to +40°C
maximum load
16 A - total for all channels v. 1.1
GRENTON LED RGB RGB-042-T-16
LED RGB LIGHTING CONTROL MODULE FOR FLUSH-MOUNT ASSEMBLY
LED RGB lighting control module for flush-mount assembly enables smooth and full control of decorative lighting using LED RGB technology.
PROPERTIES • • • • • •
dimming function – allows it to operate as a three-channel dimmer full freedom when setting the color: RGB or HSV model 16.8 million colors enables you to adjust both the saturation and hue smooth transition when changing color, saturation, and intensity enables you to set the ramp (transition time) for transitions between colors, saturation, and intensity of light
WIRING DIAGRAM
TF-Bus
TF-Bus
TF-Bus
TF-Bus
LED 3 LED 2
LED Blue LED Green LED Red COM
LED 1 COM
12/24 VDC
12/24 VDC
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Brightness value (range: 0 - 1)
Hue
Color hue value as per the HSV model (0 - 360)
Saturation
Color saturation value (0 - 1)
RValue
R component value (0 - 255) – Red
GValue
G component value (0 - 255) – Green
BValue
B component value (0 - 255) – Blue
#RGB
Color value as per the RGB model “#RRGGBB” (specified in HEX)
RampTime
Time value of increment of color and brightness (ms)
MinValue
Minimum value which Value can adopt. Attempting to set a lower value will generate an error.
MaxValue
Maximum value which Value can adopt. Attempting to set a higher value will generate an error.
RCorrection
White correction – channel R (0 - 10,000), default 10,000
GCorrection
White correction – channel G (0 - 10,000), default 8,333
BCorrection
White correction – channel B (0 - 10,000), default 8,333
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time
METHODS NAME
DESCRIPTION
SetValue
Sets output value (0 - 1)
SetHue
Sets hue value (0 - 360)
SetSaturation
Sets saturation value (0 - 1)
SetRValue
Sets R component value (0 - 255)
SetGValue
Sets G component value (0 - 255)
SetBValue
Sets B component value (0 -255)
Set#RGB
Sets RGB value using the “#RRGGBB” string
HoldValue
Executes illumination/dimming function
HoldHue
Executes smooth hue transition
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds) The second parameter is the ramp (time of value increments) which is optional. If this parameter is not specified, the default ramp is used
SwitchOn
Sets output value to MaxValue
SwitchOff
Sets output value to MinValue
SetRampTime
Sets value of increment of color and input (ms)
SetMax
Sets MaxValue
SetMin
Sets MinValue
EVENTS NAME
DESCRIPTION
OnChange
Event occurring when changing the output state
OnSwitchOn
Event occurring when the output state is changed from = 0 to > 0
OnSwitchOff
Event occurring when “0” is set at the output
OnRaiseValueSet
Event occurring when the set value is higher than the current value
OnLowerValueSet
Event occurring when the set value is lower than the current value
OnOutOfRange
Event occurring when setting a value which is higher than the maximum value or lower than the minimum value
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
4.7 mA
weight
38 g
dimensions (H/W/D)
52/57/21 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
0 to +40°C
maximum load
10 A - total for all channels
v. 1.1
GRENTON RELAYx2 REL-019-T-01
RELAY OUTPUT MODULE FOR DIN RAIL ASSEMBLY The relay output module allows you to switch any electrical device without the need to use additional control relays.
PROPERTIES • • • •
two relay outputs enables you to connect a direct load up to 3.6 kVA per channel enables the following functions: switching, continuous activation, and specific-time activation signals output state with a diode
WIRING DIAGRAM L
~230 V
N
Receiver NO
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns 1 for output set at “On” and 0 for output set at “Off”
StatisticState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time;
METHODS NAME
DESCRIPTION
SetValue
Sets output value to 1 or 0
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds)
SwitchOn
Sets output value to 1
SwitchOff
Sets output value to 0
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the state takes place (regardless of the value)
OnSwitchOn
Occurs when “On” is set at output
OnSwitchOff
Occurs when “Off” is set at output
TECHNICAL SPECIFICATIONS DC supply
5V
average current input
4.18 mA
max. current input
112 mA
contact arrangement
2x NO
weight
82 g
dimensions (H/W/D)
58/36/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
2
operating temperature range
O to +40°C
maximum load
3600 VA per channel
v. 1.1
GRENTON RELAYx2 REL-030-T-01
RELAY OUTPUT MODULE FOR FLUSH-MOUNT ASSEMBLY The relay output module for flushmount assembly allows you to switch any electrical device without the need to use additional control relays.
PROPERTIES • • •
two relay outputs enables you to connect a direct load up to 1.8 kVA per channel enables the following functions: switching, continuous activation, and specific-time activation
WIRING DIAGRAM TF-Bus
TF-Bus
NO
Receiver
~230 V
L N
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns 1 for output set at “On” and 0 for output set at “Off”
StatlstlcState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
l.oad
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time
METHODS NAME
DESCRIPTION
SetValue
Sets output value to 1 or 0
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds)
SwitchOn
Sets output value to 1
SwitchOff
Sets output value to 0
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the state takes place (regardless of the value)
OnSwitchOn
Occurs when “On” is set at output
OnSwitchOff
Occurs when “Off” is set at output
TECHNICAL SPECIFICATIONS DC supply
5V
average current input
4.18 mA
max. current input
112 mA
contact arrangement
2x NO
weight
46 g
dimensions (H/W/D)
52/57/21 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
maximum load
1,800 VA per channel
v. 1.1
GRENTON RELAYx2 Z-Wave REL-039-Z-07
WIRELESS 230 V OUTPUT MODULE FOR FLUSH-MOUNT ASSEMBLY
Wireless 230 V output module for flush-mount assembly allows you to switch any electrical device without the need to use additional control relays.
PROPERTIES • • • • • • • •
two 230 V outputs enables you to connect a direct load up to 1,800 VA per channel enables the following functions: switching, continuous activation, and specific-time activation allows you to connect two 230 V inputs inputs are fully configurable small size – fits into a P60 box under the ancillary equipment operates with 230 V supply communicates with other wireless modules using a mesh network
WIRING DIAGRAM
Receiver
~230 V
L N
MODULE INSTALLATION Connect the module according to the diagram above, and then add the Z-Wave module to CLU controller. To do this, follow these steps: 1. Use the „Link” button on CLU module (green diode blinks in 200 ms intervals) 2. Use the linking button on Z-Wave module. Correct linking the module will be confirmed with a triple blinking of the both diodes on CLU. After physical addition of the module start a configuration. In order to do so, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open a new project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns 1 for output set at “On” and 0 for output set at “Off”
METHODS NAME
DESCRIPTION
SetValue
Set soutputvaluetolorO
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds)
SwitchOn
Sets output value to 1
SwitchOff
Sets output value to 0
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the state takes place (regardless of the value)
OnSwitchOn
Occurs when “On” is set at output
OnSwitchOff
Occurs when “Off” is set at output
INPUT PROPERTIES CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input state as 0 or 1
Inertion
Minimum interval in milliseconds which has to pass between presses of a button so that it is interpreted as a new pressing activity
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds after which, when pressing and holding a button, the OnHold event occurs
METHODS NAME
DESCRIPTION
SetInertion
Sets Inertion value
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at the input
OnSwitchOff
Occurs when the low state is set at the input
OnShortPress
Occurs after pressing the button for 500 - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval Value
OnClick
Occurs after pressing the button for less than 500 ms
TECHNICAL SPECIFICATIONS AC supply
230 V
average current input
2 mA
max. current input
6 mA
Z-Wave frequency
868 MHz
weight
35 g
dimensions (H/W/D)
19/45/36 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
maximum load
1,800 VA per channel v. 1.1
GRENTON RELAYx4 REL-020-T-11
RELAY OUTPUT MODULE FOR DIN RAIL ASSEMBLY The relay output module allows you to switch any electrical device without the need to use additional control relays.
PROPERTIES • • • •
four relay outputs enables you to connect a direct load up to 3.6 kVA per channel enables the following functions: switching, continuous activation, and specific-time activation signals output state with a diode
WIRING DIAGRAM L
~230 V
N
Receiver NO
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
Value
Returns 1 for output set at “On” and 0 for output set at “Off”
StatlstlcState
Measurement type. Off - turned off; Continuous - Load measurement throughout the machine cycle/Load measurement over the entire life cycle of the device
Load
Multiplier of measured value. For StatisticState: Continous - consumption value per unit time
METHODS NAME
DESCRIPTION
SetValue
Sets output value to 1 or 0
Switch
Changes the output value from 0 to 1 or from 1 to 0. The first parameter is the time of change: - 0 – switches output to continuous mode - num – switches output for a time specified by a parameter (in milliseconds)
SwitchOn
Sets output value to 1
SwitchOff
Sets output value to 0
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the state takes place (regardless of the value)
OnSwitchOn
Occurs when “On” is set at output
OnSwitchOff
Occurs when “Off” is set at output
TECHNICAL SPECIFICATIONS DC supply
5V
average current input
4.16 mA
max. current input
220 mA
contact arrangement
4x NO
weight
146 g
dimensions (H/W/D)
58/71/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
4
operating temperature range
O to +40°C
maximum load
3,600 VA per channel
v. 1.1
GRENTON ROLLER SHUTTER RSH-045-T-06
ROLLER SHUTTER CONTROL MODULE FOR DIN RAIL ASSEMBLY The roller shutter control module for DIN rail assembly allows you to control any roller shutter drive.
PROPERTIES • • •
equipped with two control contacts (up/down, left/right) for installation in electrical switch rooms allows you to control drives with a maximum capacity of 3.6 kW
WIRING DIAGRAM L
~230 V
N M
TF-Bus
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
M1
State of M1 relay (moving downwards)
M2
State of M2 relay (moving upwards)
State
Device state. 0 - no movement, 1 - moving downwards, 2 - moving upwards
MaxTime
Default Time parameter value. Maximum movement time
METHODS NAME
DESCRIPTION
Up
Roller Shutter Up or Stop if moving. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Down
Roller Shutter Down or Stop if moving. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Start
Roller Shutter Up if the preceding motion was Down or Roller Shutter Down if the preceding motion was Up. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Stop
Stop if moving
Hold
Hold with direction change
HoldUp
Hold always up
HoldDown
Hold always down
EVENTS NAME
DESCRIPTION
OnChange
Occurs when changing the state of any of the outputs
OnUp
Occurs when changing the Stop state to the Up state
OnDown
Occurs when changing the Stop state to the Down state
OnStart
Occurs when Start is requested
OnStop
Occurs when Stop is requested
TECHNICAL SPECIFICATIONS DC supply
5V
average current input
4.18 mA
max. current input
112 mA
weight
82 g
dimensions (H/W/D)
58/36/90 mm
max. connection wire section
≤ 2.5 mm2
size [DIN]
2
operating temperature range
0 to +40°C
maximum load
3,600 VA per channel
v. 1.1
GRENTON ROLLER SHUTTER RSH-044-T-02
ROLLER SHUTTER CONTROL MODULE FOR FLUSH-MOUNT ASSEMBLY
The roller shutter control module for flush-mount assembly allows you to control any roller shutter drive.
PROPERTIES • • •
equipped with two control contacts (up/down, left/right) small size – fits into a P60 box under the ancillary equipment allows you to control drives with a maximum capacity 1.8 kVA
WIRING DIAGRAM TF-Bus
TF-Bus
M
~230 V
L N
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
M1
State of M1 relay
M2
State of M2 relay
State
Device state. 0 - no movement, 1 - moving downwards, 2 - moving upwards
MaxTime
Default Time parameter value. Maximum movement time
METHODS NAME
DESCRIPTION
Up
Roller Shutter Up or Stop if moving. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Down
Roller Shutter Down or Stop if moving. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Start
Roller Shutter Up if the preceding motion was Down or Roller Shutter Down if the preceding motion was Up. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Stop
Stop if moving
Hold
Hold with direction change
HoldUp
Hold always up
HoldDown
Hold always down
EVENTS NAME
DESCRIPTION
OnChange
Occurs when changing the state of any of the outputs
OnUp
Occurs when changing the Stop state to the Up state
OnDown
Occurs when changing the Stop state to the Down state
OnStart
Occurs when Start is requested
OnStop
Occurs when Stop is requested
TECHNICAL SPECIFICATIONS DC supply
5V
average current input
4.18 mA
max. current input
112 mA
weight
46 g
dimensions (H/W/D)
52/57/21 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
0 to +40°C
maximum load
1,800 VA
v. 1.1
GRENTON ROLLER SHUTTER Z-Wave RSH-040-Z-02
WIRELESS ROLLER SHUTTER CONTROL MODULE FOR FLUSH-MOUNT ASSEMBLY The wireless roller shutter control module for flush-mount assembly allows you to control any roller shutter drive.
PROPERTIES • • • • • •
equipped with two control contacts (up/down, left/right) two 230 V outputs inputs are fully configurable small size – fits into a P60 box under the ancillary equipment operates with 230 V supply communicates with other wireless modules using a mesh network
0
WIRING DIAGRAM
M
~230 V
L N
MODULE INSTALLATION Connect the module according to the diagram above, and then add the Z-Wave module to CLU controller. To do this, follow these steps: 1. Use the „Link” button on CLU module (green diode blinks in 200 ms intervals). 2. Use the linking button on Z-Wave module. Correct linking the module will be confirmed with a triple blinking of the both diodes on CLU. After physical addition of the module start a configuration. In order to do so, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open a new project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
CONFIGURATION PARAMETERS CHARACTERISTICS NAME
DESCRIPTION
M1
State of M1 relay
M2
State of M2 relay
State
Output state: 0 – stopped, 1 – moving up, 2 – moving down
MaxTime
Default value for the Time parameter, if “0” was entered
METHODS NAME
DESCRIPTION
Up
Roller Shutter Up or Stop if moving. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Down
Roller Shutter Down or Stop if moving. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Start
Roller Shutter Up if the preceding motion was Down or Roller Shutter Down if the preceding motion was Up. Parameter Time: - 0 - output is active for the time specified in MaxTime - number - output is active for specified time
Stop
Stop if moving
Hold
Hold with direction change
HoldUp
Hold always up
HoldDown
Hold always down
EVENTS NAME
DESCRIPTION
OnChange
Occurs when changing the state of any of the outputs
OnUp
Occurs when changing the Stop state to the Up state
OnDown
Occurs when changing the Stop state to the Down state
OnStart
Occurs when Start is requested
OnStop
Occurs when Stop is requested
INPUT PROPERTIES CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input state as 0 or 1
Inertion
Minimum interval in milliseconds which has to pass between presses of a button so that it is interpreted as a new pressing activity
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds after which, when pressing and holding a button, the OnHold event occurs
METHODS NAME
DESCRIPTION
SetInertion
Sets Inertion value
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at the input
OnSwitchOff
Occurs when the low state is set at the input
OnShortPress
Occurs after pressing the button for 500 - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval Value
OnClick
Occurs after pressing the button for less than 500 ms
TECHNICAL SPECIFICATIONS AC supply
230 V
average current input
2 mA
max. current input
3 mA
Z-Wave frequency
868 MHz
contact arrangement
2x NO
weight
35 g
dimensions (H/W/D)
19/45/36 mm
max. connection wire section
≤ 1.5 mm2
operating temperature range
O to +40°C
maximum load
1,800 VA v. 1.1
GRENTON SMART PANEL SPS-001-T-01
FOUR CAPACITIVE BUTTONS TOUCH PANEL WITH THE OLED DISPLAY AND HAND GESTURE CONTROL
Replacing traditional wall switches, Smart Panel allows to control not only the light, but also any device in a smart home. The Panel provides information from sensors, system parameters or its functional data. The versatile and intuitive control interface make it easy and quick to control an individual device or a whole home.
PROPERTIES • smart design matching every interior • four touch buttons, executing up to four independent functions • each button can signal corectness of activation or errors: ShowOk and ShowError • OLED screen • sound signals • proximity sensor and hand gesture control • temperature and light sensors • unlimited functionality - wide programming possibility TECHNICAL SPECIFICATION DC supply
5 - 24 V
average current input in a standby mode for 5 V
20 mA
max. current input for 5 V
80 mA
weight
120 g
dimmensions (H/W/D)
surface part: 80/80/10 mm concealed part: Ø 50 mm/h : 22 mm
operating temperature range
0 - 45°C (without condesantion)
microSD CARD INSTALLATION The card should be installed with the power supply turned off! 1
2
3
4 A
B
WIRING DIAGRAM 1
2
flush box
fastening ring
3
TF-Bus
4
click!
push
flush box
ADDITIONAL INFORMATION Full instruction, technical specification and declaration of conformity are available on the website: www.grenton.pl The general Warranty Terms & Conditions are available on the manufacturer’s website at: www.grenton.pl/gwarancja
v. 1.3
GRENTON TOUCH PANEL TPA-02X-T-0X
TOUCH PANEL
The touch panel replaces traditional light switches.
PROPERTIES • • • • •
two versions: four buttons or eight buttons each button can execute up to four independent functions features a built-in temperature sensor each button can signal correctness of activation or errors: ShowOK and ShowError functions available in different colors
WIRING DIAGRAM 1
2
3
click!
TF-Bus
MODULE INSTALLATION Connect the module according to the above diagram. After connecting the module with other modules in the system, add the module to system configuration using TF-Bus. In order to do this, follow these steps: 1. Connect the CLU module using the ETHERNET port to the computer on which the GRENTON OBJECT MANAGER configuration program is installed. 2. Open existing project or create a new one in GRENTON OBJECT MANAGER program. 3. Run the CLU DISCOVERY procedure.
4. Add found modules to the project.
BUTTON PROPERTIES CHARACTERISTICS NAME
DESCRIPTION
Value
Returns input state as 0 or 1
Mode
Returns the selected mode of button action (0 – monostable, 1 – bistable, 2 – locked). In locked mode, the diode is illuminated in continuous red light.
HoldDelay
Time in milliseconds after which, when pressing and holding a button, the OnHold event occurs
HoldInterval
Cyclical interval in milliseconds after which, when pressing and holding a button, the OnHold event occurs
METHODS NAME
DESCRIPTION
SetMode
Sets the mode of button action (0 – monostable, 1 – bistable, 2 – locked). In locked mode, the diode is illuminated in continuous red light.
SetHoldDelay
Sets HoldDelay value
SetHoldInterval
Sets HoldInterval value
ShowError
Causes the red diode on the button to flash for 2 seconds (frequency 500 ms). The green diode on the button is off
ShowOK
Causes the green diode on the button to flash for 2 seconds (frequency 500 ms). The red diode on the button is off
LedSwitchOn
Activates the green diode on the button
LedSwitchOff
Deactivates the green diode on the button
EVENTS NAME
DESCRIPTION
OnChange
Occurs when a change in the input state takes place (regardless of the value)
OnSwitchOn
Occurs when the high state is set at input
OnSwitchOff
Occurs when the low state is set at input
OnShortPress
Occurs after pressing the button for 500 - 2000 ms
OnLongPress
Occurs after pressing the button for two seconds
OnHold
Occurs for the first time after HoldDelay time passes and then cyclically every HoldInterval value
OnClick
Occurs after pressing the button for less than 500 ms
SENSOR PROPERTIES CHARACTERISTICS NAME
DESCRIPTION
Threshold
Hysteresis size (accuracy 0.1°C or 0.1%) specifying the sensitivity when the following events are generated: OnChange, OnLower, OnRaise
Sensitivity
Time (in ms) for which the sampled values are averaged
MinValue
Minimum value of the Value characteristic after exceeding which the OnOutOfRange event is generated
MaxValue
Maximum value of the Value characteristic after exceeding which the OnOutOfRange event is generated
Value
Input value: for temperature sensor from 0.0 to 6553.5 (°C), for light sensor 0 - 100
EVENTS NAME
DESCRIPTION
OnChange
Event resulting from changing input state
OnRise
Event resulting from exceeding the upper threshold of hysteresis
OnLower
Event resulting from exceeding the lower threshold of hysteresis
OnOutOfRange
Event resulting from exceeding any range
TECHNICAL SPECIFICATIONS DC supply
5V
max. current input
36.3 mA
weight
200 g
dimensions (H/W/D)
160/80/18 mm
operating temperature range
O to +40°C
v. 1.1