13858 selkirk drive harnek singh

Page 1

4' [1.22m] REAR SETBACK

4'-7" [1.40m]

42'-8" [13.00m]

6'-1014" [2.09m]

51'-113 4" [15.84m]

20' [6.10m]

BUILDING - INTERIOR DESIGNERS

25'-10 1/2"

25' [7.62m] REAR SETBACK

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

75'-2" [22.90m] BLDG DEPTH

CLIENT:

8' [2.43m] REAR SETBACK

UDC DESIGN CENTER LTD

25'-1012" [7.89m]

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

31'-10" [9.70m] FRONT SETBACK

Site Plan

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

1/8" = 1'-0"

V01

SHEET NO:

A 1/6


A A1 69'-8" 20'

22'-8" 4'-8"

6'

4'-10"

1'-7"

1'-7"

5'-3"

4'

21'-9"

4050RS

3016FX 3070FX

12'-9" 3'-7"

3070FX 3016FX

3050RS

3'-8"

2680

2680

5'-6"

d/w

2'-10"

3016FX 3070FX

8'-11"

3050RS

2680 6080

UP

3'-2"

2680

5050RS

6'-8"

3'-6"

section-1

utility

2650FX

3980

16080 9'-11"

48'

3080

8'-8"

Double Door Refrigerator 2

Tub-Shower 2

48'

21080

26'-10"

2080

BUILDING - INTERIOR DESIGNERS

SMOKE ALARM & CARBON MONOXIDE (CO) ALARM

7'-10"

S CO

7'-10"

5'-6" 2'-2"

2680

5'-5"

Farm Sink in Stand

3070FX

3080

2680

21080

2680

1'-8"

2650FX

2680 2680

S CO

EXTENT OF SUITE30 MIN. FIRE RATED FOR WALLS AND CLG.

3070FX

6050RS

SMOKE ALARM & CARBON MONOXIDE (CO) ALARM

FIRE RATED, SOLID CORE, WEATHER STRIPPED, SELF CLOSING DOOR

5'-5"

6'-3"

20'-10"

S

5'

5068

2680

4'-7"

5'

FIRE RATED DOOR

S

13'-5"

3070FX

FIRE RATED DOOR

2680

EXTENT OF SUITE30 MIN. FIRE RATED FOR WALLS AND CLG.

2680

2'-7"

2680 3016RS

3040RS

4040RS

3080

18'-4"

4'-2"

2'-8"

2'-8"

4040RS

9'-9"

6'-6"

4'-8"

2580

7'-8"

4'-9"

5'-8"

3030RS

9'-9"

3080

UDC DESIGN CENTER LTD

2'-8"

2060FX

7'-4"

2060FX

12'-8"

4'-7"

27'

4'-8"

19'-9"

5'-4"

22'

75'-1"

A A1

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

MAIN FLOOR

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

V01

SHEET NO:

A

2/6


A A1 47'-11" 20'-2" 3'

27'-9" 3'

14'-2"

18'-2"

2'-2"

7'-5"

3040RS

12'-4"

5440RS

4'-2" 14'-10" 10'-8"

3068

4368 3'-4"

48'

5016RS

3'

section-1

DN Tub-Shower 2

4040FX

2'-8" 2'-10"

21068

2668

21068

SKY LIGHT

2'-6"

2268 2668

21068

S

2668

4040FX

Tub-Shower 2

S

5068

45'-11"

10'-4"

7'-8"

Rect (medium) [48]

8'-5"

2668

BUILDING - INTERIOR DESIGNERS

2668 S

21068 2668

S

5068

15'-5"

20'-10"

20'-9"

2668

2668

4568 3040RS 3016RS

3016RS

4040RS

6040RS

UDC DESIGN CENTER LTD

0"

3040RS S

6'

5'-10" 11'-10"

2'-4"

5'-2"

5'-2"

2'-9"

2'-7"

12'-8"

5'-4"

2'-8"

2'-5" 5'-1"

6'-6"

6'-6" 13'

47'-11"

A A1

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

TOP FLOOR

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

1/4"=1'-0"

V01

SHEET NO:

A

3/6


6'-05 8" [1.84m]

ROOF RIDGE LVL. 111.64

1 12 8

6'-05 8" [1.84m]

MEAN ROOF LVL. 109.80

4030FX

3

9'-03 4" [2.76m]

27'-8" [8.43m]

2

SECOND FLOOR LVL. 105.20

5016RS

MATERIAL SPECIFICATIONS 4030FX

11'-13 8" [3.39m]

6016FX

3016FX

3016FX

3016FX

4 6 3070FX

5050RS 3070FX

3070FX

3070FX

3070FX

6080

3070FX

1.

ASPHALT SHINGLE 40 YRS - IKO CAMBRIDGE, DUAL BLACK

2.

BUILT-IN GUTTER - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT

3.

1 x 4 OVER 2" X 10" FASCIA BOARD

4.

4" OR 6" WINDOW AND DOOR TRIM

5.

STUCCO

6.

ALUMINUM FRAMED WINDOW AND PATIO DOOR

7.

WOODEN EXTERIOR DOOR

8. 9.

STONE HARDY PANEL

10.

SHINGLES

MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38

6'-05 8" [1.84m]

ROOF RIDGE LVL. 111.64

FRONT ELEVATION SCALE:1/8"-1'

12 8

6'-05 8" [1.84m]

MEAN ROOF LVL. 109.80

SECOND FLOOR LVL. 105.20

9'-03 4" [2.76m]

U/S CEILING LVL. 107.96

27'-8" [8.43m]

3016RS

4040RS

4.5

3016RS 4.5

6040RS

16

24

LEFT ELEVATION TOTAL AREA: 1219 SQ. FT. [113 SQ.M] DISTANCE TO PROPERTY LINE: 8' (2.43 M) ≈ 4M MAX. ALLOWABLE UNPROTECTED AREA @ 12.0% = 146.28 SQ. FT. PROPOSED UNPROTECTED AREA: 8.0% = 106.5 SQ. FT

LEFT ELEVATION

11'-13 8" [3.39m]

BUILDING - INTERIOR DESIGNERS

UDC DESIGN CENTER LTD

U/S CEILING LVL. 107.96

3016RS

4.5 3030RS

4040RS

3040RS 16

4040RS 12

9

16

3068

2568

MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38

SCALE:1/8"-1'

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

FRONT & LEFT ELEVATION

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

1/4"=1'-0"

V01

SHEET NO:

A

4/6


6'-05 8" [1.84m]

ROOF RIDGE LVL. 111.64

12 8

6'-05 8" [1.84m]

MEAN ROOF LVL. 109.80

9'-03 4" [2.76m]

4030FX 5440RS

4040FX

5040RS

3068

11'-13 8" [3.39m]

27'-8" [8.43m]

SECOND FLOOR LVL. 105.20

3040RS

3040RS

2640FX

2640FX

6040RS

3068

MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38

6'-05 8" [1.84m]

ROOF RIDGE LVL. 111.64

REAR ELEVATION

12 8

SCALE:1/8"-1'

6'-05 8" [1.84m]

MEAN ROOF LVL. 109.80

TOTAL AREA: 786 SQ. FT. = 73 SQ.M DISTANCE TO PROPERTY LINE: 4' - 0" = 1.2M MAX. ALLOWABLE UNPROTECTED AREA @ 7.0% = 60 SQ. FT. PROPOSED UNPROTECTED AREA: = 73 SQ. FT

2040SH

2040SH 8

8

11'-13 8" [3.39m]

RIGHT ELEVATION

SECOND FLOOR LVL. 105.20

9'-03 4" [2.76m]

U/S CEILING LVL. 107.96

27'-8" [8.43m]

BUILDING - INTERIOR DESIGNERS

UDC DESIGN CENTER LTD

U/S CEILING LVL. 107.96

4050RS 2060FX 12

2060FX 12

20

MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38

RIGHT ELEVATION SCALE:1/8"-1'

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

REAR & RIGHT ELEVATION

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

1/4"=1'-0"

V01

SHEET NO:

A

5/6


6'-05 8" [1.84m]

ROOF RIDGE LVL. 111.64

DUROID ROOF BUILDING PAPER ON 12" PLYWOOD ENG.TRUSSES @24" O/C R-40 BATT INSULATION 6 MIL POLY V.B. (LAPPED JOINTS,SEAL ELECT. OUTLETS) (WARM SIDE) 5 8" GYPSUM BOARD BUFFLES 2" CLEAR FROM TOP

12 8

1 MEAN ROOF LVL. 109.80 6'-05 8" [1.84m]

ATTIC ATTIC VENTILATION AS PER BUILDINGCODE A/300 OF INSULATED CEILING AREA MIN. 25% OF VENTING @TOP & 25% @ BOTTOM

2

9'-03 4" [2.76m]

27'-8" [8.43m]

SECOND FLOOR LVL. 105.20

4 5068

21068

5

4

11'-13 8" [3.39m]

3

2650FX

NET BACKFILL HT.

A

B

LESS THAN 7'-6"

0"

0"

7'-6" TO 8'-0"

18"

20"

8'-1" TO 9'-0"

14"

20"

9'-1" TO 10'-0"

12"

20"

NOTE: 1. REBAR TO BE 230 MPa MINIMUM. 2. CONCRETE TO BE 20 MPa MINIMUM. 3. BACKFILL NOT TO EXCEED 20 KN/ cubic METER

5 8" ANCHOR BOLT @ 48" o.c. (MAX. OF 1 PLATE UNDER JOIST.)

FLOOR JOIST

W1(C): -38mm(112")X 89mm(321") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD

5

8" TYPE "X" GYPSUM BOARD ON BOTH SIDES CONTINUOUS TO UNDERSIDE OF FLOOR SHEATHING (HATCHED AREA)

1

HORIZONTAL STEEL = 'B' (LAP JOINTS 18" MINIMUM) APPLY DAMPROOFING AS REQ. BY N.B.C. SECT.9-13

NET BACKFILL HEIGHT

MAX. COVER 2"

F.R.R WALL DETAIL

4" CONC. SLAB ON 6 MIL. POLY. V.B. ON 6" COMPACTED GRANULAR FILL

3

5

8" TYPE "X" GYPSUM BOARD AGAINST SEPARATION WALL

-METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm (58") TYPE X GYPSUM BOARD

15M @ 15" o.c.

DETAIL AT 'A'

ON PLAN

8"

5

EAVES:

- 5 8" TYPE "X" GYPSUM BOARD (FIN. AS PER OWNER)

6

4

EXTERIOR WALLS (2 hr FRR): - STUCCO ON WIREMESH - METAL LATH - 19MM (3/4") AIR SPACE / @ 16" O.C. - 15# BREATHER TYPE BUILDING PAPER - 15 32" SHEATHING - 2 x 6 STUDS @ 16" O.C. - R-20 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.

F.R.R. CEILING DETAIL

2-15M CONT.

BASEMENT FLOOR: - FINISH FLOOR: TO OWNERS SPEC'S - 0'-6" CONC. SLAB - 10 GA 6 x 6 WIRE MESH - 6 MIL. POLY. V.B. - R-10 RIGID INSULATION - MIN. 12" COMPACTED GRANULAR FILL

INTERIOR PARTITIONS ( 1 hr FRR): - 1/2" GYPSUM BOARD (BOTH SIDES) - 2 x 4 STUDS @ 16" O.C. - INSUALTED CAVITY

F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(112")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(58") TYPE X GYPSUM BOARD

MAIN AND UPPER FLOOR (1 hr FRR): - FINISH FLOOR: TO OWNERS SPEC'S - P.T. 2x10 @16 o.c. JOISTS AS PER MANUFACTURERS SPECS - 11/2"th. CONCRETE TOPPING - R-40 SPRAT FOAM INSULATION

- BUILT-IN GUTTER - 2 x 12 FASCIA BOARD - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT

SUBFLOOR

NOTCH OUT 12" TYPE "X" GYPSUM BOARD FOR FLOOR JOISTS

ROOF: - ROOF FINISH: 210 # ASPHALT SHINGLES ROOF - STARTER STRIP - 716" OSB SHEATHING c/w. H. CLIPS - PREFAB. ENG. TRUSSES @ 24" O.C. - R-50 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.

2

VERTICAL STEEL = 'A' (ALTERNATE HOOKS)

4"Ø PERIMETER DRAIN TILE WITH DRAIN ROCKS

SECTIONAL DETAILS AND SPECIFICATIONS:

W1(C): -38mm(112")X 89mm(321") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD

30 MIN. F.R.R. ASSEMBLY DETAIL

212" RIGID INSULATION (N.I.C.) TO BELOW FROSTLINE OR 2x4 FURRED WALL w/ R12 F.G. BATT INSUL. (N.I.C.) WHERE INDICATED

24"

A

EXTERIOR WALL CONSTRUCTION

GARAGE SLAB OR FINISHED GRADE

8" REINFORCED CONCRETE FOUNDATION WALL

2680

7

TYPICAL FLOOR CONSTRUCTION

2" FROM GARAGE SLAB OR SIDEWALK 8" MIN. FROM FINISH GRADE

TYP.CELLAR FLR. ASSEMBLY GYPSUM BOARD FLR. JOINTS @ 16" o.c. AS ER STRUC. ENG. 5 " T&G PLYWOOD SUBFLOOR 8 RADIANT HEATING PIPES ON WIRE MESH 1- 12" LIGHT WEIGHT CONC. TOPPING FLOOR FINISH 1" 2

6

F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(85") TYPE X GYPSUM BOARD

SUPPORTED WALL (10M BAR)

2650FX

2680

MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38

AS NOTED

BUILDING - INTERIOR DESIGNERS

UDC DESIGN CENTER LTD

U/S CEILING LVL. 107.96

7

FOUNDATION WALLS: - 2 x 6 SILL PLATE - 8" CONC. FOUNDATION WALL - 2 COATS OF ASHPALT EMULSION TO EXTERIOR FACE - 2 - 15M T & B, 10M @16" O.C E/W.1.F UP TO GRADE

INTERNAL INSULATED WALL - 2" AIR SPACE - 2 x 4 SPF # 2 STUDS @ 24" O.C. (U.N.O.) - R-14 BATT. INSULATION - 6 MIL. POLY. V.B. - C/W TUCK TAPE JOINTS - 1/2" DRYWALL

AS NOTED ON PLAN

SUPPORTED WALL SECTION

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

SECTION AND DETAIL

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

1/4"=1'-0"

V01

SHEET NO:

A

6/6


BUILDING - INTERIOR DESIGNERS

UDC DESIGN CENTER LTD

∙

UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

ENERGY DETAIL

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

N.T.S.

V01

SHEET NO:

D1


GRID

HEADER

EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.) 1/2"CONTROL JOINT FLOOR FINISH ON C/W CAULK AND ROD CONCRETE TOPPING

MIN. 3/8" GAP BETWEEN WINDOW & 1X2 STRAPPING

EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

4" ADHERED FLASHING MEMBRANE

INTERIOR

100 mm (4")

FLOOR FINISH ON CONCRETE TOPPING

SHEATHING PAPER BEHIND FLASHING AND INTO WINDOW OPENING INSECT SCREEN

MIN. 2% SLOPE TO DRAIN SEALANT JOINT AT VENT DUCT TO HOUSEWRAP (A.B.)

2"CONTINUOUS FLANGE AT PERIMETER OF HOOD

STUD @ 16" O.C

2"

2

SEALANT OR GASKET (A.B.) BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED

1 MIN 2"

BLDG. PAPER

4.06

23.03

EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY

3.99

22.61

0.68

4.11

23.29

ADHERED MEMBRANE FLASHING TO LAP 100mm (4") OVER SHEATHING PAPER BELOW

ROOF ASSEMBLY COMPONENTS (W/ ASPHALT SHINGLES) 1 ROOFING SHINGLES 2 POLYTHENE V.B 5 ″ (15.88 MM) OSB SHEATHING 3 8 4 2 x 10 JOISTS W/ R50 BATT @ 24″ O.C. 5 POLYETHYLENE 6 1/2″ (12.7 MM) GYPSUM BOARD 7 INTERIOR AIR FILM

RSI 0.077 0.00 0.136 8.8 0.00 0.08 0.12

R 0.44 0.00 0.77 50.0 0.00 0.45 0.68

SEALANT OR GASKET JOINT AT POLYETHYLENE (A.B. & V.B.) TO PLATE (A.B.)

2X10 FLOOR JOISTS

SEAL POLYETHYLENE (V.B.) TO SHEATHING PAPER (A.B.)

EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY

9.21

50.34

FLOOR ASSEMBLY OVER UNHEATED SPACE 1 EXTERIOR AIR FILM 2 FLOOR FINISHES (3 4" HARDWOOD) 3 POLYETHYLENE 4 512" CONC. SLAB 5 R-28 INSULATION 9 NATURAL GRADE

RSI 0.03 0.12 0.00 0.15 4.99 0.00

R 0.17 0.68 0.00 0.83 28.00 0.00

EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY

5.29

29.68

TRIPLE GLAZED WINDOWS & DOORS LOW E, DOUBLE GLAZED (6mm GAP), TEMPERED GLASS εn = 0.1, AIR FILLED WITH VINYL OR FIBRE GLASS FRAME

USI

U

1.4

0.246

SEPERATION AIR SPACE

EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY

1 MIN.

RSI R 0.03 0.17 0.035 0.20 1.06 6.00 0.00 0.00 0.11 0.62 2.55 14.49 0.00 0.00 0.08 0.45 0.00 0.00 0.12 0.68 .12

1" 2

2a

2 SEALANT OR GASKET (A.B.)

EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY

12mm (1/2")

SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.)

1X2 STRAPPING

VALUES ADOPTED FROM CANADIAN WOOD COUNCIL

PREFINISHED METAL FLASHING C/W END DAMS TO EXTEND 1" PAST END OF WINDOW FRAME

VENTED ALUMINUM SOFFIT PANELS EFFECTIVE RSI - 4.06 SEAL SHEATHING PAPER (A.B.) TO WINDOW FRAME REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

VALUES ADOPTED FROM CANADIAN WOOD COUNCIL

1.5" SILL PLATE

BUILDING - INTERIOR DESIGNERS

EXTERIOR STUCCO CLADDING

- HEAVY- DUTY POLYVINYL CHLORIDE (PVC )

INTERIOR

AIR SPACE W/ 1x2 TREATED WOOD STRAPPING SCREWED THROUGH INSULATION

THERMOPLASTIC WATER PROOFING MEMBRANES ARE OVERLAPPED AND HEAT FUSED ( APPLICATION CODE :CGSB -37-GP-55M)

SEALANT OR GASKET POLYETHYLENE TO PLATE (A.B.)

FLASHING & COUNTER FLASHING

SEALANT OR GASKET (A.B.)

ASPHALT IMPREGNATED PAPER

INSECT SCREEN - NO DAMPERS

EFFECTIVE RSI VALUE = 6.06 ROOFING SHINGLES (M.B.) WATERPROOF ROOF MEMBRANE (M.B.) FOR EAVE PROTECTION 5/8" OSB ROOF SHEATHING W/ H CLIPS WOOD ROOF FRAMING R-50 BATT INSULATION POLYETHYLENE (A.B. & V.B.) GYPSUM BOARD

GRID

1/2″ (12.7 MM) PLYWOOD SHEATHING

2 X 2 BLOCKING AT BOTH ENDS OF VENT 11/2" CONT. VENT

POLYETHYLENE VAPOR BARRIER

ADHERE SUBFLOOR TO HEADER (A.B.) FLOOR FINISH ON CONCRETE TOPPING

EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING

EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 (RSI-1.06)

1/2″ (12.7 MM) GYPSUM BOARD

MIN. 2% SLOPE TO DRAIN

2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. SLOPED SUB-SILL FRAMING

SEALANT OR GASKET (A.B.) REFER TO W-1 FOR EXTERNAL WALL ASSEMBLY DETAIL

INSULATION GUARD

POLYETHYLENE (V.B. AND A.B.) SEALANT OR GASKET (A.B.)

EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

GASKET (A.B.)

BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED

LAP POLYETHYLENE AND SEAL TO ADHERED MEMBRANE (A.B. AND V.B.)

W-1

SEALANT AND BACKER ROD JOINT AT WINDOW FRAME TO MEMBRANE (A.B. AND M.B.) SEALANT FILLET JOINT PREFINISHED METAL DRIP FLASHING

SEALANT BETWEEN POLYETHYLENE AND HOUSEWRAP (A.B.) FLOOR FINISH ON CONCRETE TOPPING

INTERMITTENT 1/8" P.T. SHIM BEHIND WINDOW FLANGE TO CREATE DRAINAGE PATH (ALTERNATELY DRILL HOLES OR SLOTS THROUGH WINDOW FLANGES TO TO ALLOW FOR DRAINAGE)

HOUSEWRAP AT HEADER (A.B.)

BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED GYPSUM BOARD

BATT INSULATION POLYETHYLENE (V.B.) STAPLED IN PLACE

25mm (1")

ADHERED MEMBRANE FLASHING (M.B.) SILL GASKET (A.B.)

2" MIN.

FILTER CLOTH

CEMENT OR ACRYLIC STUCCO PARGING

SEE 'FLASHING-BEST PRACTICE GUIDE' FOR ADDITIONAL ROOF FLASHING DETAILS

DAMP PROOFING / VAP. BARRIER EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

8" CONC. FOUNDATION WALL

FINISHED GRADE

4" EXTRUDED POLYSTYRENE R-5/in. 1" 2

REFER TO W-2/A-501 FOR FND WALL ASSEMBLY DETAIL

DRYWALL FINISH

912"

INSECT SCREEN

VENTED ALUMINUM SOFFIT PANELS

FLOOR OVER UNHEATED SPACE EFFECTIVE RSI 2.06

512"

CEMENT OR ACRYLIC STUCCO PARGING

8" MINIMUM

SHEATHING PAPER TO LAP OVER ADHERED MEMBRANE FLASHING

EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

SEAL HOUSEWRAP (A.B.) TO FRAMING

CONTINUE EAVE PROTECTION 12" BEYOND INSIDE FACE OF WALL

ADHERED MEMBRANE FLASHING TO EXTEND 4" AND LAP OVER SHEATHING PAPER

INTERIOR

1/2"

UDC DESIGN CENTER LTD

ROD AND SEALANT

4" FLANGE

25.4mm (1")

R 0.17 0.62 6.00 0.00 0.62 14.49 0.00 0.45 0.00 0.68

WALL ASSEMBLY COMPONENTS (W/ STUCCO CLADDING) 1 EXTERIOR AIR FILM 3 " STUCCO FIN. 2 4 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER2 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM

SHEATHING PAPER TO LAP METAL FLASHING

ROD AND SEALANT 1

RSI 0.03 0.11 1.06 0.00 0.11 2.55 0.00 0.08 0.00 0.12

VALUES ADOPTED FROM CANADIAN WOOD COUNCIL

4" FLANGE 6

WALL ASSEMBLY COMPONENTS (W/ NINYL CLADDING) 1 EXTERIOR AIR FILM 2 VINYL SIDING (NO AIR SPACE) 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM

EXTERIOR

4"

EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6

RSI / R VALUE CALCULATIONS FOR ASSEMBLIES

EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING

COMPLETE W/ 4" EXTRUDED POLYSTYRENE FOAM BOARD INSUL. R-5/in.

WOOD FRAMING (STUDS OR STRAPPING)

W-2 UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM

CLIENT:

SHEET TITLE:

HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14

BLOCK 5 NORTH RANGE 2 WEST PLAN 17137

GENERAL DETAIL

DRAWN BY:

G.S.B.

PROJECT NO.

CHECKED BY:

B.M.

1278

DATE:

JUNE. 2017

FILE NO.

SCALE:

N.T.S.

V01

SHEET NO:

D2