4' [1.22m] REAR SETBACK
4'-7" [1.40m]
42'-8" [13.00m]
6'-1014" [2.09m]
51'-113 4" [15.84m]
20' [6.10m]
BUILDING - INTERIOR DESIGNERS
25'-10 1/2"
25' [7.62m] REAR SETBACK
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
75'-2" [22.90m] BLDG DEPTH
CLIENT:
8' [2.43m] REAR SETBACK
UDC DESIGN CENTER LTD
25'-1012" [7.89m]
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
31'-10" [9.70m] FRONT SETBACK
Site Plan
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/8" = 1'-0"
V01
SHEET NO:
A 1/6
A A1 69'-8" 20'
22'-8" 4'-8"
6'
4'-10"
1'-7"
1'-7"
5'-3"
4'
21'-9"
4050RS
3016FX 3070FX
12'-9" 3'-7"
3070FX 3016FX
3050RS
3'-8"
2680
2680
5'-6"
d/w
2'-10"
3016FX 3070FX
8'-11"
3050RS
2680 6080
UP
3'-2"
2680
5050RS
6'-8"
3'-6"
section-1
utility
2650FX
3980
16080 9'-11"
48'
3080
8'-8"
Double Door Refrigerator 2
Tub-Shower 2
48'
21080
26'-10"
2080
BUILDING - INTERIOR DESIGNERS
SMOKE ALARM & CARBON MONOXIDE (CO) ALARM
7'-10"
S CO
7'-10"
5'-6" 2'-2"
2680
5'-5"
Farm Sink in Stand
3070FX
3080
2680
21080
2680
1'-8"
2650FX
2680 2680
S CO
EXTENT OF SUITE30 MIN. FIRE RATED FOR WALLS AND CLG.
3070FX
6050RS
SMOKE ALARM & CARBON MONOXIDE (CO) ALARM
FIRE RATED, SOLID CORE, WEATHER STRIPPED, SELF CLOSING DOOR
5'-5"
6'-3"
20'-10"
S
5'
5068
2680
4'-7"
5'
FIRE RATED DOOR
S
13'-5"
3070FX
FIRE RATED DOOR
2680
EXTENT OF SUITE30 MIN. FIRE RATED FOR WALLS AND CLG.
2680
2'-7"
2680 3016RS
3040RS
4040RS
3080
18'-4"
4'-2"
2'-8"
2'-8"
4040RS
9'-9"
6'-6"
4'-8"
2580
7'-8"
4'-9"
5'-8"
3030RS
9'-9"
3080
UDC DESIGN CENTER LTD
2'-8"
2060FX
7'-4"
2060FX
12'-8"
4'-7"
27'
4'-8"
19'-9"
5'-4"
22'
75'-1"
A A1
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
MAIN FLOOR
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
V01
SHEET NO:
A
2/6
A A1 47'-11" 20'-2" 3'
27'-9" 3'
14'-2"
18'-2"
2'-2"
7'-5"
3040RS
12'-4"
5440RS
4'-2" 14'-10" 10'-8"
3068
4368 3'-4"
48'
5016RS
3'
section-1
DN Tub-Shower 2
4040FX
2'-8" 2'-10"
21068
2668
21068
SKY LIGHT
2'-6"
2268 2668
21068
S
2668
4040FX
Tub-Shower 2
S
5068
45'-11"
10'-4"
7'-8"
Rect (medium) [48]
8'-5"
2668
BUILDING - INTERIOR DESIGNERS
2668 S
21068 2668
S
5068
15'-5"
20'-10"
20'-9"
2668
2668
4568 3040RS 3016RS
3016RS
4040RS
6040RS
UDC DESIGN CENTER LTD
0"
3040RS S
6'
5'-10" 11'-10"
2'-4"
5'-2"
5'-2"
2'-9"
2'-7"
12'-8"
5'-4"
2'-8"
2'-5" 5'-1"
6'-6"
6'-6" 13'
47'-11"
A A1
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
TOP FLOOR
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
SHEET NO:
A
3/6
6'-05 8" [1.84m]
ROOF RIDGE LVL. 111.64
1 12 8
6'-05 8" [1.84m]
MEAN ROOF LVL. 109.80
4030FX
3
9'-03 4" [2.76m]
27'-8" [8.43m]
2
SECOND FLOOR LVL. 105.20
5016RS
MATERIAL SPECIFICATIONS 4030FX
11'-13 8" [3.39m]
6016FX
3016FX
3016FX
3016FX
4 6 3070FX
5050RS 3070FX
3070FX
3070FX
3070FX
6080
3070FX
1.
ASPHALT SHINGLE 40 YRS - IKO CAMBRIDGE, DUAL BLACK
2.
BUILT-IN GUTTER - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
3.
1 x 4 OVER 2" X 10" FASCIA BOARD
4.
4" OR 6" WINDOW AND DOOR TRIM
5.
STUCCO
6.
ALUMINUM FRAMED WINDOW AND PATIO DOOR
7.
WOODEN EXTERIOR DOOR
8. 9.
STONE HARDY PANEL
10.
SHINGLES
MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38
6'-05 8" [1.84m]
ROOF RIDGE LVL. 111.64
FRONT ELEVATION SCALE:1/8"-1'
12 8
6'-05 8" [1.84m]
MEAN ROOF LVL. 109.80
SECOND FLOOR LVL. 105.20
9'-03 4" [2.76m]
U/S CEILING LVL. 107.96
27'-8" [8.43m]
3016RS
4040RS
4.5
3016RS 4.5
6040RS
16
24
LEFT ELEVATION TOTAL AREA: 1219 SQ. FT. [113 SQ.M] DISTANCE TO PROPERTY LINE: 8' (2.43 M) ≈ 4M MAX. ALLOWABLE UNPROTECTED AREA @ 12.0% = 146.28 SQ. FT. PROPOSED UNPROTECTED AREA: 8.0% = 106.5 SQ. FT
LEFT ELEVATION
11'-13 8" [3.39m]
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
U/S CEILING LVL. 107.96
3016RS
4.5 3030RS
4040RS
3040RS 16
4040RS 12
9
16
3068
2568
MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38
SCALE:1/8"-1'
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
FRONT & LEFT ELEVATION
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
SHEET NO:
A
4/6
6'-05 8" [1.84m]
ROOF RIDGE LVL. 111.64
12 8
6'-05 8" [1.84m]
MEAN ROOF LVL. 109.80
9'-03 4" [2.76m]
4030FX 5440RS
4040FX
5040RS
3068
11'-13 8" [3.39m]
27'-8" [8.43m]
SECOND FLOOR LVL. 105.20
3040RS
3040RS
2640FX
2640FX
6040RS
3068
MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38
6'-05 8" [1.84m]
ROOF RIDGE LVL. 111.64
REAR ELEVATION
12 8
SCALE:1/8"-1'
6'-05 8" [1.84m]
MEAN ROOF LVL. 109.80
TOTAL AREA: 786 SQ. FT. = 73 SQ.M DISTANCE TO PROPERTY LINE: 4' - 0" = 1.2M MAX. ALLOWABLE UNPROTECTED AREA @ 7.0% = 60 SQ. FT. PROPOSED UNPROTECTED AREA: = 73 SQ. FT
2040SH
2040SH 8
8
11'-13 8" [3.39m]
RIGHT ELEVATION
SECOND FLOOR LVL. 105.20
9'-03 4" [2.76m]
U/S CEILING LVL. 107.96
27'-8" [8.43m]
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
U/S CEILING LVL. 107.96
4050RS 2060FX 12
2060FX 12
20
MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38
RIGHT ELEVATION SCALE:1/8"-1'
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
REAR & RIGHT ELEVATION
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
SHEET NO:
A
5/6
6'-05 8" [1.84m]
ROOF RIDGE LVL. 111.64
DUROID ROOF BUILDING PAPER ON 12" PLYWOOD ENG.TRUSSES @24" O/C R-40 BATT INSULATION 6 MIL POLY V.B. (LAPPED JOINTS,SEAL ELECT. OUTLETS) (WARM SIDE) 5 8" GYPSUM BOARD BUFFLES 2" CLEAR FROM TOP
12 8
1 MEAN ROOF LVL. 109.80 6'-05 8" [1.84m]
ATTIC ATTIC VENTILATION AS PER BUILDINGCODE A/300 OF INSULATED CEILING AREA MIN. 25% OF VENTING @TOP & 25% @ BOTTOM
2
9'-03 4" [2.76m]
27'-8" [8.43m]
SECOND FLOOR LVL. 105.20
4 5068
21068
5
4
11'-13 8" [3.39m]
3
2650FX
NET BACKFILL HT.
A
B
LESS THAN 7'-6"
0"
0"
7'-6" TO 8'-0"
18"
20"
8'-1" TO 9'-0"
14"
20"
9'-1" TO 10'-0"
12"
20"
NOTE: 1. REBAR TO BE 230 MPa MINIMUM. 2. CONCRETE TO BE 20 MPa MINIMUM. 3. BACKFILL NOT TO EXCEED 20 KN/ cubic METER
5 8" ANCHOR BOLT @ 48" o.c. (MAX. OF 1 PLATE UNDER JOIST.)
FLOOR JOIST
W1(C): -38mm(112")X 89mm(321") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
5
8" TYPE "X" GYPSUM BOARD ON BOTH SIDES CONTINUOUS TO UNDERSIDE OF FLOOR SHEATHING (HATCHED AREA)
1
HORIZONTAL STEEL = 'B' (LAP JOINTS 18" MINIMUM) APPLY DAMPROOFING AS REQ. BY N.B.C. SECT.9-13
NET BACKFILL HEIGHT
MAX. COVER 2"
F.R.R WALL DETAIL
4" CONC. SLAB ON 6 MIL. POLY. V.B. ON 6" COMPACTED GRANULAR FILL
3
5
8" TYPE "X" GYPSUM BOARD AGAINST SEPARATION WALL
-METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm (58") TYPE X GYPSUM BOARD
15M @ 15" o.c.
DETAIL AT 'A'
ON PLAN
8"
5
EAVES:
- 5 8" TYPE "X" GYPSUM BOARD (FIN. AS PER OWNER)
6
4
EXTERIOR WALLS (2 hr FRR): - STUCCO ON WIREMESH - METAL LATH - 19MM (3/4") AIR SPACE / @ 16" O.C. - 15# BREATHER TYPE BUILDING PAPER - 15 32" SHEATHING - 2 x 6 STUDS @ 16" O.C. - R-20 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
F.R.R. CEILING DETAIL
2-15M CONT.
BASEMENT FLOOR: - FINISH FLOOR: TO OWNERS SPEC'S - 0'-6" CONC. SLAB - 10 GA 6 x 6 WIRE MESH - 6 MIL. POLY. V.B. - R-10 RIGID INSULATION - MIN. 12" COMPACTED GRANULAR FILL
INTERIOR PARTITIONS ( 1 hr FRR): - 1/2" GYPSUM BOARD (BOTH SIDES) - 2 x 4 STUDS @ 16" O.C. - INSUALTED CAVITY
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(112")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(58") TYPE X GYPSUM BOARD
MAIN AND UPPER FLOOR (1 hr FRR): - FINISH FLOOR: TO OWNERS SPEC'S - P.T. 2x10 @16 o.c. JOISTS AS PER MANUFACTURERS SPECS - 11/2"th. CONCRETE TOPPING - R-40 SPRAT FOAM INSULATION
- BUILT-IN GUTTER - 2 x 12 FASCIA BOARD - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
SUBFLOOR
NOTCH OUT 12" TYPE "X" GYPSUM BOARD FOR FLOOR JOISTS
ROOF: - ROOF FINISH: 210 # ASPHALT SHINGLES ROOF - STARTER STRIP - 716" OSB SHEATHING c/w. H. CLIPS - PREFAB. ENG. TRUSSES @ 24" O.C. - R-50 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
2
VERTICAL STEEL = 'A' (ALTERNATE HOOKS)
4"Ø PERIMETER DRAIN TILE WITH DRAIN ROCKS
SECTIONAL DETAILS AND SPECIFICATIONS:
W1(C): -38mm(112")X 89mm(321") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
30 MIN. F.R.R. ASSEMBLY DETAIL
212" RIGID INSULATION (N.I.C.) TO BELOW FROSTLINE OR 2x4 FURRED WALL w/ R12 F.G. BATT INSUL. (N.I.C.) WHERE INDICATED
24"
A
EXTERIOR WALL CONSTRUCTION
GARAGE SLAB OR FINISHED GRADE
8" REINFORCED CONCRETE FOUNDATION WALL
2680
7
TYPICAL FLOOR CONSTRUCTION
2" FROM GARAGE SLAB OR SIDEWALK 8" MIN. FROM FINISH GRADE
TYP.CELLAR FLR. ASSEMBLY GYPSUM BOARD FLR. JOINTS @ 16" o.c. AS ER STRUC. ENG. 5 " T&G PLYWOOD SUBFLOOR 8 RADIANT HEATING PIPES ON WIRE MESH 1- 12" LIGHT WEIGHT CONC. TOPPING FLOOR FINISH 1" 2
6
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(85") TYPE X GYPSUM BOARD
SUPPORTED WALL (10M BAR)
2650FX
2680
MAIN FL. LVL. 101.81 AVE. GRADE. LVL. 101.38
AS NOTED
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
U/S CEILING LVL. 107.96
7
FOUNDATION WALLS: - 2 x 6 SILL PLATE - 8" CONC. FOUNDATION WALL - 2 COATS OF ASHPALT EMULSION TO EXTERIOR FACE - 2 - 15M T & B, 10M @16" O.C E/W.1.F UP TO GRADE
INTERNAL INSULATED WALL - 2" AIR SPACE - 2 x 4 SPF # 2 STUDS @ 24" O.C. (U.N.O.) - R-14 BATT. INSULATION - 6 MIL. POLY. V.B. - C/W TUCK TAPE JOINTS - 1/2" DRYWALL
AS NOTED ON PLAN
SUPPORTED WALL SECTION
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
SECTION AND DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
SHEET NO:
A
6/6
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
∙
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
ENERGY DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
N.T.S.
V01
SHEET NO:
D1
GRID
HEADER
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.) 1/2"CONTROL JOINT FLOOR FINISH ON C/W CAULK AND ROD CONCRETE TOPPING
MIN. 3/8" GAP BETWEEN WINDOW & 1X2 STRAPPING
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
4" ADHERED FLASHING MEMBRANE
INTERIOR
100 mm (4")
FLOOR FINISH ON CONCRETE TOPPING
SHEATHING PAPER BEHIND FLASHING AND INTO WINDOW OPENING INSECT SCREEN
MIN. 2% SLOPE TO DRAIN SEALANT JOINT AT VENT DUCT TO HOUSEWRAP (A.B.)
2"CONTINUOUS FLANGE AT PERIMETER OF HOOD
STUD @ 16" O.C
2"
2
SEALANT OR GASKET (A.B.) BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED
1 MIN 2"
BLDG. PAPER
4.06
23.03
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
3.99
22.61
0.68
4.11
23.29
ADHERED MEMBRANE FLASHING TO LAP 100mm (4") OVER SHEATHING PAPER BELOW
ROOF ASSEMBLY COMPONENTS (W/ ASPHALT SHINGLES) 1 ROOFING SHINGLES 2 POLYTHENE V.B 5 ″ (15.88 MM) OSB SHEATHING 3 8 4 2 x 10 JOISTS W/ R50 BATT @ 24″ O.C. 5 POLYETHYLENE 6 1/2″ (12.7 MM) GYPSUM BOARD 7 INTERIOR AIR FILM
RSI 0.077 0.00 0.136 8.8 0.00 0.08 0.12
R 0.44 0.00 0.77 50.0 0.00 0.45 0.68
SEALANT OR GASKET JOINT AT POLYETHYLENE (A.B. & V.B.) TO PLATE (A.B.)
2X10 FLOOR JOISTS
SEAL POLYETHYLENE (V.B.) TO SHEATHING PAPER (A.B.)
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
9.21
50.34
FLOOR ASSEMBLY OVER UNHEATED SPACE 1 EXTERIOR AIR FILM 2 FLOOR FINISHES (3 4" HARDWOOD) 3 POLYETHYLENE 4 512" CONC. SLAB 5 R-28 INSULATION 9 NATURAL GRADE
RSI 0.03 0.12 0.00 0.15 4.99 0.00
R 0.17 0.68 0.00 0.83 28.00 0.00
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
5.29
29.68
TRIPLE GLAZED WINDOWS & DOORS LOW E, DOUBLE GLAZED (6mm GAP), TEMPERED GLASS εn = 0.1, AIR FILLED WITH VINYL OR FIBRE GLASS FRAME
USI
U
1.4
0.246
SEPERATION AIR SPACE
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
1 MIN.
RSI R 0.03 0.17 0.035 0.20 1.06 6.00 0.00 0.00 0.11 0.62 2.55 14.49 0.00 0.00 0.08 0.45 0.00 0.00 0.12 0.68 .12
1" 2
2a
2 SEALANT OR GASKET (A.B.)
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
12mm (1/2")
SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.)
1X2 STRAPPING
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
PREFINISHED METAL FLASHING C/W END DAMS TO EXTEND 1" PAST END OF WINDOW FRAME
VENTED ALUMINUM SOFFIT PANELS EFFECTIVE RSI - 4.06 SEAL SHEATHING PAPER (A.B.) TO WINDOW FRAME REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
1.5" SILL PLATE
BUILDING - INTERIOR DESIGNERS
EXTERIOR STUCCO CLADDING
- HEAVY- DUTY POLYVINYL CHLORIDE (PVC )
INTERIOR
AIR SPACE W/ 1x2 TREATED WOOD STRAPPING SCREWED THROUGH INSULATION
THERMOPLASTIC WATER PROOFING MEMBRANES ARE OVERLAPPED AND HEAT FUSED ( APPLICATION CODE :CGSB -37-GP-55M)
SEALANT OR GASKET POLYETHYLENE TO PLATE (A.B.)
FLASHING & COUNTER FLASHING
SEALANT OR GASKET (A.B.)
ASPHALT IMPREGNATED PAPER
INSECT SCREEN - NO DAMPERS
EFFECTIVE RSI VALUE = 6.06 ROOFING SHINGLES (M.B.) WATERPROOF ROOF MEMBRANE (M.B.) FOR EAVE PROTECTION 5/8" OSB ROOF SHEATHING W/ H CLIPS WOOD ROOF FRAMING R-50 BATT INSULATION POLYETHYLENE (A.B. & V.B.) GYPSUM BOARD
GRID
1/2″ (12.7 MM) PLYWOOD SHEATHING
2 X 2 BLOCKING AT BOTH ENDS OF VENT 11/2" CONT. VENT
POLYETHYLENE VAPOR BARRIER
ADHERE SUBFLOOR TO HEADER (A.B.) FLOOR FINISH ON CONCRETE TOPPING
EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING
EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 (RSI-1.06)
1/2″ (12.7 MM) GYPSUM BOARD
MIN. 2% SLOPE TO DRAIN
2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. SLOPED SUB-SILL FRAMING
SEALANT OR GASKET (A.B.) REFER TO W-1 FOR EXTERNAL WALL ASSEMBLY DETAIL
INSULATION GUARD
POLYETHYLENE (V.B. AND A.B.) SEALANT OR GASKET (A.B.)
EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
GASKET (A.B.)
BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED
LAP POLYETHYLENE AND SEAL TO ADHERED MEMBRANE (A.B. AND V.B.)
W-1
SEALANT AND BACKER ROD JOINT AT WINDOW FRAME TO MEMBRANE (A.B. AND M.B.) SEALANT FILLET JOINT PREFINISHED METAL DRIP FLASHING
SEALANT BETWEEN POLYETHYLENE AND HOUSEWRAP (A.B.) FLOOR FINISH ON CONCRETE TOPPING
INTERMITTENT 1/8" P.T. SHIM BEHIND WINDOW FLANGE TO CREATE DRAINAGE PATH (ALTERNATELY DRILL HOLES OR SLOTS THROUGH WINDOW FLANGES TO TO ALLOW FOR DRAINAGE)
HOUSEWRAP AT HEADER (A.B.)
BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED GYPSUM BOARD
BATT INSULATION POLYETHYLENE (V.B.) STAPLED IN PLACE
25mm (1")
ADHERED MEMBRANE FLASHING (M.B.) SILL GASKET (A.B.)
2" MIN.
FILTER CLOTH
CEMENT OR ACRYLIC STUCCO PARGING
SEE 'FLASHING-BEST PRACTICE GUIDE' FOR ADDITIONAL ROOF FLASHING DETAILS
DAMP PROOFING / VAP. BARRIER EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
8" CONC. FOUNDATION WALL
FINISHED GRADE
4" EXTRUDED POLYSTYRENE R-5/in. 1" 2
REFER TO W-2/A-501 FOR FND WALL ASSEMBLY DETAIL
DRYWALL FINISH
912"
INSECT SCREEN
VENTED ALUMINUM SOFFIT PANELS
FLOOR OVER UNHEATED SPACE EFFECTIVE RSI 2.06
512"
CEMENT OR ACRYLIC STUCCO PARGING
8" MINIMUM
SHEATHING PAPER TO LAP OVER ADHERED MEMBRANE FLASHING
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
SEAL HOUSEWRAP (A.B.) TO FRAMING
CONTINUE EAVE PROTECTION 12" BEYOND INSIDE FACE OF WALL
ADHERED MEMBRANE FLASHING TO EXTEND 4" AND LAP OVER SHEATHING PAPER
INTERIOR
1/2"
UDC DESIGN CENTER LTD
ROD AND SEALANT
4" FLANGE
25.4mm (1")
R 0.17 0.62 6.00 0.00 0.62 14.49 0.00 0.45 0.00 0.68
WALL ASSEMBLY COMPONENTS (W/ STUCCO CLADDING) 1 EXTERIOR AIR FILM 3 " STUCCO FIN. 2 4 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER2 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM
SHEATHING PAPER TO LAP METAL FLASHING
ROD AND SEALANT 1
RSI 0.03 0.11 1.06 0.00 0.11 2.55 0.00 0.08 0.00 0.12
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
4" FLANGE 6
WALL ASSEMBLY COMPONENTS (W/ NINYL CLADDING) 1 EXTERIOR AIR FILM 2 VINYL SIDING (NO AIR SPACE) 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM
EXTERIOR
4"
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
RSI / R VALUE CALCULATIONS FOR ASSEMBLIES
EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING
COMPLETE W/ 4" EXTRUDED POLYSTYRENE FOAM BOARD INSUL. R-5/in.
WOOD FRAMING (STUDS OR STRAPPING)
W-2 UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
HARNEK SINGH PROJECT: CIVIC ADDRESS:13858 SELKIRK DRIVE SURREY, BC LEGAL DESCRIPTION: LOT #6 SECTION 14
BLOCK 5 NORTH RANGE 2 WEST PLAN 17137
GENERAL DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JUNE. 2017
FILE NO.
SCALE:
N.T.S.
V01
SHEET NO:
D2