25'-2" [7.68m]
77' [23.47m] BLDG DEPTH
48'-10" [14.89m]
27'-1" [8.26m] REAR SETBACK
9'-8" [2.95m]
BUILDING - INTERIOR DESIGNERS
SUMP
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
30'-11" [9.42m]
48'-1" [14.64m]
6' [1.83m] SIDE SETBACK
18' [5.49m] FRONT SETBACK
UDC DESIGN CENTER LTD
6'-83 4" [2.05m] SIDE SETBACK
to be removed
SHEET TITLE:
Site Plan
to be removed
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/8" = 1'-0"
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A 1/5
40'-6" 24'-5"
16'-1" 4'-7"
11'-10"
8'-0"
3030RS
3'-10" 3'-7"
6'-8"
3080FX
14'-4"
3'-10"
3080FX 3080FX
2668
3030RS
3'-0"
2668
4'-8" 4" 2'-0" 9'-2"
4'-1" 6040RS
2668
Elongated Toilet
5'-1"
2668
5'-1" 2'-8"
4'-6"
7'-10"
10'-5"
3070FX
21'-0"
Dryer (curved) 22" w/ Gas Upflow [22 1/2W28 5/8D] Medium Elec WH
5068
6'-6"
Elongated Toilet
2668
4068
Elevation 5
9'-5"
5'-0"
1468
Tub-Shower 2
5'-6"
5030RS
3016RS
5040RS
6040RS
3068
3030RS
3'-8"
2630RS
A1 A
FIRE RATED, SOLID CORE, WEATHER STRIPPED, SELF CLOSING DOOR
5'-0"
2668 S
SMOKE ALARM & CARBON MONOXIDE (CO) ALARM
3070FX
2468
E5
2668
Bottom Mount Refrigerator 3 S CO
5'-6"
3068 Dryer (curved) Apron Front Sink [24 13/16W]
9'-11"
2668
S
3070FX
9'-0"
3068
5'-4"
FIRE RATED WALL
FIRE RATED DOOR
3'-8"
5'-0"
3'-6"
2668
FIRE RATED WALL
3'-8"
31168
3040RS
2668
Electric Range
11'-5"
3068
13'-8"
21'-9"
16080
3'-2"
56'-8"
2668
3040RS
5'-0"
5068
9'-9"
A1 A
53'-0"
3'-8"
2668
6'-5"
35'-8"
9'-5"
DN
UP E6
3068
Elevation 6
LINE OF DECK ABOVE 31'-8"
6068
8'-8"
1'-6"
2668
BUILDING - INTERIOR DESIGNERS
4'-9"
Dishwasher
5"
SMOKE ALARM & CARBON MONOXIDE (CO) ALARM
WH
3068
UDC DESIGN CENTER LTD
7'-8"
4'-8"
3'-1"
3040RS S CO
5'-3"
5'-3"
3'-9"
4'-5"
18'-8"
3'-7"
4'-10"
2'-9" 3'-5"
8'-6"
2'-8"
4'-8"
5'-5"
4'-8" 9'-4"
2'-4"
1'-6" 1'-8" 2'-4"
3'-2"
4'-3"
19'-8" 22'-0"
77'-0"
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
main floor plan
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
TOWNSHIP 1 NEW WESTMINSTER SCALE:
V01
SHEET NO:
A 2/5
49'-0" 11'-9"
15'-0"
12'-3"
2668
14'-5"
3068
10'-0"
E6
Elevation 6
3'-9" 2668
2'-9" 13'-6"
Elongated Toilet
4040RS
3'-0"
Tub-Shower 2
4068
4068
Tub-Shower 2
Elongated Toilet
6034RS
2030SH
8'-4"
4'-0"
6'-5"
5'-8"
16'-1"
6031RS
A1 A
2668
5'-8"
2668
5'-8"
A1 A
S
16'-0"
6'-0"
S
2'-6"
3040RS
2668
5068 5068
3040RS
21068
21068
5068
4'-4"
11'-2"
4'-8" 4020RS
2668
17'-3"
2668 S
51'-8"
5068
2668
2'-4"
6'-4"
W
51'-8"
D
BUILDING - INTERIOR DESIGNERS
DN
S
10'-1"
5068
6040RS
13'-4"
2668
24'-6"
2668
UDC DESIGN CENTER LTD
10'-8"
8'-4"
6'-8" 12'-4"
2'-8"
2'-8"
5'-4"
7'-3"
8'-0" 15'-3"
49'-0"
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
uppper floor plan
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A 3/5
ROOF RIDGE LVL. 112.45
ROOF RIDGE LVL. 112.45 6'-67 8" [2.00m]
6'-67 8" [2.00m]
1
MEAN ROOF LVL. 110.45
MEAN ROOF LVL. 110.45
U/S CEILING LVL. 108.45
10 3
U/S CEILING LVL. 108.45
2
9'-03 4" [2.76m]
9'-03 4" [2.76m]
8
8 4020RS 3040RS
6
4030FX
3040RS
10
SECOND FLOOR LVL. 105.69
4
3070FX
3070FX
3080FX
3080FX
3080FX
6040RS
3070FX
2'-87 8" [0.83m]
MAIN FL. LVL. 102.30
6
8
8
MAIN FL. LVL. 102.30
AVE. GRADE. LVL. 101.47
RIGHT ELEVATION TOTAL AREA: 856.6 SQ. FT. = 79.5 SQ.M DISTANCE TO PROPERTY LINE: 6' - 8" = 2M MAX. ALLOWABLE UNPROTECTED AREA @ 9.0% = 77.09 SQ. FT. PROPOSED UNPROTECTED AREA: = 77SQ. FT
3040RS
2'-8 8" [0.83m]
8
7
29'-6" [8.99m]
8
11'-13 8" [3.39m]
29'-6" [8.99m]
10
11'-13 8" [3.39m]
10
SECOND FLOOR LVL. 105.69
AVE. GRADE. LVL. 101.47
RIGHT ELEVATION SCALE:1/4"-1'
FRONT ELEVATION SCALE:1/4"-1' MATERIAL SPECIFICATIONS 1.
ASPHALT SHINGLE 40 YRS - IKO CAMBRIDGE, DUAL BLACK
2.
BUILT-IN GUTTER - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
3.
1 x 4 OVER 2" X 10" FASCIA BOARD
4.
4" OR 6" WINDOW AND DOOR TRIM
5.
STUCCO
6.
ALUMINUM FRAMED WINDOW AND PATIO DOOR
7.
WOODEN EXTERIOR DOOR
8. STONE 9. CEDAR 10. SHINGLES
6'-67 8" [2.00m]
ROOF RIDGE LVL. 112.45 6'-67 8" [2.00m]
ROOF RIDGE LVL. 112.45
6040RS
9'-03 4" [2.76m]
U/S CEILING LVL. 108.45
9'-03 4" [2.76m]
U/S CEILING LVL. 108.45
4040RS
TOTAL AREA: 1106.5 SQ. FT. [102.80SQ.M] DISTANCE TO PROPERTY LINE: 6' (1.82 M) ≈ 2.0M MAX. ALLOWABLE UNPROTECTED AREA @ 8.0% = 88.52 SQ. FT. PROPOSED UNPROTECTED AREA: 8.0% = 87.5 SQ. FT
MAIN FL. LVL. 102.30
3016RS 3030RS
5030RS 6040RS
2630RS
5040RS
2'-8 8" [0.83m]
3040RS
2'-87 8" [0.83m]
3040RS
7
29'-6" [8.99m] 3030RS
11'-13 8" [3.39m]
3030RS
AVE. GRADE. LVL. 101.47
2'-518" [0.74m]
AVE. GRADE. LVL. 101.47
LEFT ELEVATION
6031RS
6034RS
2030SH
SECOND FLOOR LVL. 105.69 29'-6" [8.99m]
SECOND FLOOR LVL. 105.69
MAIN FL. LVL. 102.30
6'-67 8" [2.00m]
MEAN ROOF LVL. 110.45 6'-67 8" [2.00m]
MEAN ROOF LVL. 110.45
11'-13 8" [3.39m]
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
6'-67 8" [2.00m]
6'-67 8" [2.00m]
10
REAR ELEVATION
LEFT ELEVATION
SCALE:1/4"-1'
SCALE:1/4"-1'
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
ELEVATIONS
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/8" = 1'-0"
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A 4/5
6'-67 8" [2.00m]
ROOF RIDGE LVL. 112.45
DUROID ROOF BUILDING PAPER ON 12" PLYWOOD ENG.TRUSSES @24" O/C R-40 BATT INSULATION 6 MIL POLY V.B. (LAPPED JOINTS,SEAL ELECT. OUTLETS) (WARM SIDE) 5 8" GYPSUM BOARD BUFFLES 2" CLEAR FROM TOP
6'-67 8" [2.00m]
MEAN ROOF LVL. 110.45
9'-03 4" [2.76m]
3040RS
TYP.CELLAR FLR. ASSEMBLY GYPSUM BOARD FLR. JOINTS @ 16" o.c. AS ER STRUC. ENG. 5 " T&G PLYWOOD SUBFLOOR 8 RADIANT HEATING PIPES ON WIRE MESH 1- 12" LIGHT WEIGHT CONC. TOPPING FLOOR FINISH 1" 2
2'-87 8" [0.83m]
MAIN FL. LVL. 102.30
11'-13 8" [3.39m]
29'-6" [8.99m]
SECOND FLOOR LVL. 105.69
AVE. GRADE. LVL. 101.47
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(58") TYPE X GYPSUM BOARD
SUPPORTED WALL (10M BAR)
SECTION A-1 SCALE:1/4"-1'
NET BACKFILL HT.
A
B
LESS THAN 7'-6"
0"
0"
7'-6" TO 8'-0"
18"
20"
8'-1" TO 9'-0"
14"
20"
9'-1" TO 10'-0"
12"
20"
5
NOTE: 1. REBAR TO BE 230 MPa MINIMUM. 2. CONCRETE TO BE 20 MPa MINIMUM. 3. BACKFILL NOT TO EXCEED 20 KN/ cubic METER
ANCHOR BOLT @ 48" o.c. (MAX. OF 1 PLATE UNDER JOIST.)
8"
TYPICAL FLOOR CONSTRUCTION
2" FROM GARAGE SLAB OR SIDEWALK 8" MIN. FROM FINISH GRADE GARAGE SLAB OR FINISHED GRADE
W1(C): -38mm(121")X 89mm(312") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
VERTICAL STEEL = 'A' (ALTERNATE HOOKS) MAX. COVER 2" HORIZONTAL STEEL = 'B' (LAP JOINTS 18" MINIMUM) APPLY DAMPROOFING AS REQ. BY N.B.C. SECT.9-13
NET BACKFILL HEIGHT
2 2" RIGID INSULATION (N.I.C.) TO BELOW FROSTLINE OR 2x4 FURRED WALL w/ R12 F.G. BATT INSUL. (N.I.C.) WHERE INDICATED
5
8" TYPE "X" GYPSUM BOARD ON BOTH SIDES CONTINUOUS TO UNDERSIDE OF FLOOR SHEATHING (HATCHED AREA)
W1(C): -38mm(121")X 89mm(312") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
NOTCH OUT 21" TYPE "X" GYPSUM BOARD FOR FLOOR JOISTS
5
8" TYPE "X" GYPSUM BOARD AGAINST SEPARATION WALL
-METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm (85") TYPE X GYPSUM BOARD
15M @ 15" o.c.
4"Ø PERIMETER DRAIN TILE WITH DRAIN ROCKS
ON PLAN
8"
DETAIL AT 'A'
1
5
ROOF: - ROOF FINISH: 210 # ASPHALT SHINGLES ROOF - STARTER STRIP - 716" OSB SHEATHING c/w. H. CLIPS - PREFAB. ENG. TRUSSES @ 24" O.C. - R-50 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
F.R.R WALL DETAIL 2
- 5 8" TYPE "X" GYPSUM BOARD (FIN. AS PER OWNER)
6
EAVES:
3
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(85") TYPE X GYPSUM BOARD
F.R.R. CEILING DETAIL
BASEMENT FLOOR: - FINISH FLOOR: TO OWNERS SPEC'S - 0'-6" CONC. SLAB - 10 GA 6 x 6 WIRE MESH - 6 MIL. POLY. V.B. - R-10 RIGID INSULATION - MIN. 12" COMPACTED GRANULAR FILL
INTERIOR PARTITIONS ( 1 hr FRR): 7
- 1/2" GYPSUM BOARD (BOTH SIDES) - 2 x 4 STUDS @ 16" O.C. - INSUALTED CAVITY
4
MAIN AND UPPER FLOOR (1 hr FRR): - FINISH FLOOR: TO OWNERS SPEC'S - P.T. 2x10 @16 o.c. JOISTS AS PER MANUFACTURERS SPECS - 11/2"th. CONCRETE TOPPING - R-40 SPRAT FOAM INSULATION
- BUILT-IN GUTTER - 2 x 12 FASCIA BOARD - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
SUBFLOOR
4" CONC. SLAB ON 6 MIL. POLY. V.B. ON 6" COMPACTED GRANULAR FILL
8" REINFORCED CONCRETE FOUNDATION WALL
SUPPORTED WALL SECTION
SECTIONAL DETAILS AND SPECIFICATIONS:
FLOOR JOIST
30 MIN. F.R.R. ASSEMBLY DETAIL
1
24"
A
EXTERIOR WALL CONSTRUCTION
AS NOTED
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
U/S CEILING LVL. 108.45
EXTERIOR WALLS (2 hr FRR): - STUCCO ON WIREMESH - METAL LATH - 19MM (3/4") AIR SPACE / @ 16" O.C. - 15# BREATHER TYPE BUILDING PAPER - 15 32" SHEATHING - 2 x 6 STUDS @ 16" O.C. - R-20 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
FOUNDATION WALLS: - 2 x 6 SILL PLATE - 8" CONC. FOUNDATION WALL - 2 COATS OF ASHPALT EMULSION TO EXTERIOR FACE - 2 - 15M T & B, 10M @16" O.C E/W.1.F UP TO GRADE
INTERNAL INSULATED WALL - 2" AIR SPACE - 2 x 4 SPF # 2 STUDS @ 24" O.C. (U.N.O.) - R-14 BATT. INSULATION - 6 MIL. POLY. V.B. - C/W TUCK TAPE JOINTS - 1/2" DRYWALL
2-15M CONT. AS NOTED ON PLAN
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
SECTION AND DETAILS
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A 5/5
6'-67 8" [2.00m]
ROOF RIDGE LVL. 112.45
9'-03 4" [2.76m]
U/S CEILING LVL. 108.45
3040RS
5
11'-13 8" [3.39m]
4 3
5 9'-05 8" [2.76m]
6'-4" [1.93m]
MAIN FL. LVL. 102.30 AVE. GRADE. LVL. 101.47
93 8" [0.24m]
29'-6" [8.99m]
SECOND FLOOR LVL. 105.69
7 TYP.CELLAR FLR. ASSEMBLY GYPSUM BOARD FLR. JOINTS @ 16" o.c. AS ER STRUC. ENG. 5 " T&G PLYWOOD SUBFLOOR 8 RADIANT HEATING PIPES ON WIRE MESH 1- 12" LIGHT WEIGHT CONC. TOPPING FLOOR FINISH 1" 2
7 6
BSMT. FL. LVL. 99.54
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(58") TYPE X GYPSUM BOARD
SUPPORTED WALL (10M BAR)
SECTION A-1 SCALE:1/4"-1'
NET BACKFILL HT.
A
B
LESS THAN 7'-6"
0"
0"
7'-6" TO 8'-0"
18"
20"
8'-1" TO 9'-0"
14"
20"
9'-1" TO 10'-0"
12"
20"
5
NOTE: 1. REBAR TO BE 230 MPa MINIMUM. 2. CONCRETE TO BE 20 MPa MINIMUM. 3. BACKFILL NOT TO EXCEED 20 KN/ cubic METER
ANCHOR BOLT @ 48" o.c. (MAX. OF 1 PLATE UNDER JOIST.)
8"
TYPICAL FLOOR CONSTRUCTION
2" FROM GARAGE SLAB OR SIDEWALK 8" MIN. FROM FINISH GRADE GARAGE SLAB OR FINISHED GRADE
W1(C): -38mm(121")X 89mm(312") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
VERTICAL STEEL = 'A' (ALTERNATE HOOKS) MAX. COVER 2" HORIZONTAL STEEL = 'B' (LAP JOINTS 18" MINIMUM) APPLY DAMPROOFING AS REQ. BY N.B.C. SECT.9-13
NET BACKFILL HEIGHT
2 2" RIGID INSULATION (N.I.C.) TO BELOW FROSTLINE OR 2x4 FURRED WALL w/ R12 F.G. BATT INSUL. (N.I.C.) WHERE INDICATED
5
8" TYPE "X" GYPSUM BOARD ON BOTH SIDES CONTINUOUS TO UNDERSIDE OF FLOOR SHEATHING (HATCHED AREA)
W1(C): -38mm(121")X 89mm(312") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
NOTCH OUT 21" TYPE "X" GYPSUM BOARD FOR FLOOR JOISTS
5
8" TYPE "X" GYPSUM BOARD AGAINST SEPARATION WALL
-METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm (85") TYPE X GYPSUM BOARD
15M @ 15" o.c.
4"Ø PERIMETER DRAIN TILE WITH DRAIN ROCKS
ON PLAN
8"
DETAIL AT 'A'
1
5
ROOF: - ROOF FINISH: 210 # ASPHALT SHINGLES ROOF - STARTER STRIP - 716" OSB SHEATHING c/w. H. CLIPS - PREFAB. ENG. TRUSSES @ 24" O.C. - R-50 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
F.R.R WALL DETAIL 2
- 5 8" TYPE "X" GYPSUM BOARD (FIN. AS PER OWNER)
6
EAVES:
3
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(85") TYPE X GYPSUM BOARD
F.R.R. CEILING DETAIL
BASEMENT FLOOR: - FINISH FLOOR: TO OWNERS SPEC'S - 0'-6" CONC. SLAB - 10 GA 6 x 6 WIRE MESH - 6 MIL. POLY. V.B. - R-10 RIGID INSULATION - MIN. 12" COMPACTED GRANULAR FILL
INTERIOR PARTITIONS ( 1 hr FRR): 7
- 1/2" GYPSUM BOARD (BOTH SIDES) - 2 x 4 STUDS @ 16" O.C. - INSUALTED CAVITY
4
MAIN AND UPPER FLOOR (1 hr FRR): - FINISH FLOOR: TO OWNERS SPEC'S - P.T. 2x10 @16 o.c. JOISTS AS PER MANUFACTURERS SPECS - 11/2"th. CONCRETE TOPPING - R-40 SPRAT FOAM INSULATION
- BUILT-IN GUTTER - 2 x 12 FASCIA BOARD - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
SUBFLOOR
4" CONC. SLAB ON 6 MIL. POLY. V.B. ON 6" COMPACTED GRANULAR FILL
8" REINFORCED CONCRETE FOUNDATION WALL
SUPPORTED WALL SECTION
SECTIONAL DETAILS AND SPECIFICATIONS:
FLOOR JOIST
30 MIN. F.R.R. ASSEMBLY DETAIL
1
24"
A
EXTERIOR WALL CONSTRUCTION
AS NOTED
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
12 7
6'-67 8" [2.00m]
MEAN ROOF LVL. 110.45
DUROID ROOF BUILDING PAPER ON 12" PLYWOOD ENG.TRUSSES @24" O/C R-40 BATT INSULATION 6 MIL POLY V.B. (LAPPED JOINTS,SEAL ELECT. OUTLETS) (WARM SIDE) 5 8" GYPSUM BOARD BUFFLES 2" CLEAR FROM TOP
EXTERIOR WALLS (2 hr FRR): - STUCCO ON WIREMESH - METAL LATH - 19MM (3/4") AIR SPACE / @ 16" O.C. - 15# BREATHER TYPE BUILDING PAPER - 15 32" SHEATHING - 2 x 6 STUDS @ 16" O.C. - R-20 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
FOUNDATION WALLS: - 2 x 6 SILL PLATE - 8" CONC. FOUNDATION WALL - 2 COATS OF ASHPALT EMULSION TO EXTERIOR FACE - 2 - 15M T & B, 10M @16" O.C E/W.1.F UP TO GRADE
INTERNAL INSULATED WALL - 2" AIR SPACE - 2 x 4 SPF # 2 STUDS @ 24" O.C. (U.N.O.) - R-14 BATT. INSULATION - 6 MIL. POLY. V.B. - C/W TUCK TAPE JOINTS - 1/2" DRYWALL
2-15M CONT. AS NOTED ON PLAN
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
SECTION AND DETAILS
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A6
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
∙
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
ENERGY DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
N.T.S.
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A7
GRID
GRID GRID
HEADER
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.) 1/2"CONTROL JOINT FLOOR FINISH ON C/W CAULK AND ROD CONCRETE TOPPING
MIN. 3/8" GAP BETWEEN WINDOW & 1X2 STRAPPING
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
4" ADHERED FLASHING MEMBRANE
INTERIOR
100 mm (4")
FLOOR FINISH ON CONCRETE TOPPING
SHEATHING PAPER BEHIND FLASHING AND INTO WINDOW OPENING INSECT SCREEN
MIN. 2% SLOPE TO DRAIN SEALANT JOINT AT VENT DUCT TO HOUSEWRAP (A.B.)
2"CONTINUOUS FLANGE AT PERIMETER OF HOOD
STUD @ 16" O.C
2"
2
SEALANT OR GASKET (A.B.) BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED
1 MIN 2"
BLDG. PAPER
4.06
23.03
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
3.99
22.61
0.68
4.11
23.29
ADHERED MEMBRANE FLASHING TO LAP 100mm (4") OVER SHEATHING PAPER BELOW
ROOF ASSEMBLY COMPONENTS (W/ ASPHALT SHINGLES) 1 ROOFING SHINGLES 2 POLYTHENE V.B 5 ″ (15.88 MM) OSB SHEATHING 3 8 4 2 x 10 JOISTS W/ R50 BATT @ 24″ O.C. 5 POLYETHYLENE 6 1/2″ (12.7 MM) GYPSUM BOARD 7 INTERIOR AIR FILM
RSI 0.077 0.00 0.136 8.8 0.00 0.08 0.12
R 0.44 0.00 0.77 50.0 0.00 0.45 0.68
SEALANT OR GASKET JOINT AT POLYETHYLENE (A.B. & V.B.) TO PLATE (A.B.)
2X10 FLOOR JOISTS
SEAL POLYETHYLENE (V.B.) TO SHEATHING PAPER (A.B.)
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
9.21
50.34
FLOOR ASSEMBLY OVER UNHEATED SPACE 1 EXTERIOR AIR FILM 2 FLOOR FINISHES (3 4" HARDWOOD) 3 POLYETHYLENE 4 512" CONC. SLAB 5 R-28 INSULATION 9 NATURAL GRADE
RSI 0.03 0.12 0.00 0.15 4.99 0.00
R 0.17 0.68 0.00 0.83 28.00 0.00
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
5.29
29.68
TRIPLE GLAZED WINDOWS & DOORS LOW E, DOUBLE GLAZED (6mm GAP), TEMPERED GLASS εn = 0.1, AIR FILLED WITH VINYL OR FIBRE GLASS FRAME
USI
U
1.4
0.246
SEPERATION AIR SPACE
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
1 MIN.
RSI R 0.03 0.17 0.035 0.20 1.06 6.00 0.00 0.00 0.11 0.62 2.55 14.49 0.00 0.00 0.08 0.45 0.00 0.00 0.12 0.68 .12
1" 2
2a
2 SEALANT OR GASKET (A.B.)
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
12mm (1/2")
SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.)
1X2 STRAPPING
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
PREFINISHED METAL FLASHING C/W END DAMS TO EXTEND 1" PAST END OF WINDOW FRAME
VENTED ALUMINUM SOFFIT PANELS EFFECTIVE RSI - 4.06 SEAL SHEATHING PAPER (A.B.) TO WINDOW FRAME REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
1.5" SILL PLATE
BUILDING - INTERIOR DESIGNERS
EXTERIOR STUCCO CLADDING
- HEAVY- DUTY POLYVINYL CHLORIDE (PVC )
AIR SPACE W/ 1x2 TREATED WOOD STRAPPING SCREWED THROUGH INSULATION
THERMOPLASTIC WATER PROOFING MEMBRANES ARE OVERLAPPED AND HEAT FUSED
INTERIOR
( APPLICATION CODE :CGSB -37-GP-55M) SEALANT OR GASKET POLYETHYLENE TO PLATE (A.B.)
FLASHING & COUNTER FLASHING
SEALANT OR GASKET (A.B.)
ASPHALT IMPREGNATED PAPER
INSECT SCREEN - NO DAMPERS
EFFECTIVE RSI VALUE = 6.06 ROOFING SHINGLES (M.B.) WATERPROOF ROOF MEMBRANE (M.B.) FOR EAVE PROTECTION 5/8" OSB ROOF SHEATHING W/ H CLIPS WOOD ROOF FRAMING R-50 BATT INSULATION POLYETHYLENE (A.B. & V.B.) GYPSUM BOARD
GRID
1/2″ (12.7 MM) PLYWOOD SHEATHING
2 X 2 BLOCKING AT BOTH ENDS OF VENT 11/2" CONT. VENT
POLYETHYLENE VAPOR BARRIER
ADHERE SUBFLOOR TO HEADER (A.B.)
1/2″ (12.7 MM) GYPSUM BOARD
MIN. 2% SLOPE TO DRAIN
FLOOR FINISH ON CONCRETE TOPPING
EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING
EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 (RSI-1.06)
2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. SLOPED SUB-SILL FRAMING
SEALANT OR GASKET (A.B.) REFER TO W-1 FOR EXTERNAL WALL ASSEMBLY DETAIL
INSULATION GUARD
POLYETHYLENE (V.B. AND A.B.) SEALANT OR GASKET (A.B.)
EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
GASKET (A.B.)
BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED
LAP POLYETHYLENE AND SEAL TO ADHERED MEMBRANE (A.B. AND V.B.)
W-1
SEALANT AND BACKER ROD JOINT AT WINDOW FRAME TO MEMBRANE (A.B. AND M.B.) SEALANT FILLET JOINT PREFINISHED METAL DRIP FLASHING
SEALANT BETWEEN POLYETHYLENE AND HOUSEWRAP (A.B.) FLOOR FINISH ON CONCRETE TOPPING
INTERMITTENT 1/8" P.T. SHIM BEHIND WINDOW FLANGE TO CREATE DRAINAGE PATH (ALTERNATELY DRILL HOLES OR SLOTS THROUGH WINDOW FLANGES TO TO ALLOW FOR DRAINAGE)
HOUSEWRAP AT HEADER (A.B.)
BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED GYPSUM BOARD
BATT INSULATION POLYETHYLENE (V.B.) STAPLED IN PLACE
25mm (1")
ADHERED MEMBRANE FLASHING (M.B.) SILL GASKET (A.B.)
2" MIN.
FILTER CLOTH
VENTED ALUMINUM SOFFIT PANELS
SEE 'FLASHING-BEST PRACTICE GUIDE' FOR ADDITIONAL ROOF FLASHING DETAILS
FLOOR OVER UNHEATED SPACE EFFECTIVE RSI 2.06 DAMP PROOFING / VAP. BARRIER
FINISHED GRADE
4" EXTRUDED POLYSTYRENE R-5/in. 1" 2
COMPLETE W/ 4" EXTRUDED POLYSTYRENE FOAM BOARD INSUL. R-5/in.
CEMENT OR ACRYLIC STUCCO PARGING
DRYWALL FINISH
912"
REFER TO W-2/A-501 FOR FND WALL ASSEMBLY DETAIL
INSECT SCREEN
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
8" CONC. FOUNDATION WALL
512"
CEMENT OR ACRYLIC STUCCO PARGING
8" MINIMUM
SHEATHING PAPER TO LAP OVER ADHERED MEMBRANE FLASHING
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
SEAL HOUSEWRAP (A.B.) TO FRAMING
CONTINUE EAVE PROTECTION 12" BEYOND INSIDE FACE OF WALL
ADHERED MEMBRANE FLASHING TO EXTEND 4" AND LAP OVER SHEATHING PAPER
INTERIOR
1/2"
UDC DESIGN CENTER LTD
ROD AND SEALANT
4" FLANGE
25.4mm (1")
R 0.17 0.62 6.00 0.00 0.62 14.49 0.00 0.45 0.00 0.68
WALL ASSEMBLY COMPONENTS (W/ STUCCO CLADDING) 1 EXTERIOR AIR FILM 3 " STUCCO FIN. 2 4 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER2 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM
SHEATHING PAPER TO LAP METAL FLASHING
ROD AND SEALANT 1
RSI 0.03 0.11 1.06 0.00 0.11 2.55 0.00 0.08 0.00 0.12
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
4" FLANGE 6
WALL ASSEMBLY COMPONENTS (W/ NINYL CLADDING) 1 EXTERIOR AIR FILM 2 VINYL SIDING (NO AIR SPACE) 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM
EXTERIOR
4"
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
RSI / R VALUE CALCULATIONS FOR ASSEMBLIES
EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING
WOOD FRAMING (STUDS OR STRAPPING)
W-2 UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT: BUILDER: YARED AFEWORK 604 - 290 - 7272 yared.a@alairhomes.com
DR. OLU
PROJECT: CIVIC ADDRESS:15493 18 AVE SOUTH SURREY, BC LEGAL DESCRIPTION: LOT #9 SECTION 14 DISTRICT PLAN 13376
SHEET TITLE:
GENERAL DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1281
DATE:
JUNE. 2017
FILE NO.
SCALE:
N.T.S.
V01
TOWNSHIP 1 NEW WESTMINSTER
SHEET NO:
A8