Dimmer and covers
For your safety
Wiring Examples (1)
DALI DT6, DT8 TC Rotary Dimmer
(2)
(3)
(4)
Risk of death and fire due to electrical voltage of 230 V.
Operating instructions E Series 046PDP 38301
Dim me r
-046
eter tentiom DALI po White Power nable DT8 Tu , 92mA T6 ID For DAL DALI ECGs ax. 46 m r Fo
°C
~ +50 ta: 0 °C tc: 70
V~
/240 230 AC 0Hz 50/6
L e in Mad
N
DA+
5mm
F92002
DA-
1. Work on the 230V supply system may only be performed by authorized electricians! 2. Disconnect the mains power supply prior to installation and/or disassembly! 3. Please read the mounting instructions carefully and keep them for future use. 4. Additional user information and information about planning is available at www.Kinglumi.com
Control location 1
Control location 1
L
AC Mains N DA+ DA-
*
L N DA+ DA-
L N DA+ DA-
(3)Nut
Dimensions
E-mail: sales@kinglumi.com Tel: +86-755-29516789
AC Mains N DA+ DA-
1. Dimming Turn the rotary knob either clockwise or anticlockwise:the connected lamps are dimmed brighter or darker. Turn slowly = Brightness change small Turn quickly = Brightness change great The rotary knob does not have a limit stop!
(5)
* If you have technical questions, please contact.
L
Operation
(1)Dimmer (2) Frame
046PDPE Series F92002-04638301
a Chin
Master Mode Max 46 DALI Devices One master dimmer connected to AC and DALI (active power supply) and up to three additional slave dimmers connected to DALI only (inactive power supply).
Master Mode Max 92 DALI Devices Two master dimmers connected to AC and DALI (active power supply) and up to two additional slave dimmers connected to DALI only (inactive power supply).
(4) Rotary knob (5) Screw terminals
(2) ,(4)Not included
Wiring
Unit:mm
The flush-mounted dimmer must only be installed in flush mounted boxes according to DIN 49073-1 or suitable surface mounted housings. Only be installed in dry interior rooms. Observe the currently valid regulations.
Φ4 10
Control location 2
Control location 2
Support both Master mode(powered by AC mains), and Slave mode(powered by DALI bus). 1. AC power input should only be connected if the dimmer is used as a Master. 2. Wiring cross section Max. 2.5 mm.2 3. Total length power cable Max. 300 m. 4. Total length of DALI bus cable Max. 300 m.
DALI DT6 / DT8 TC DA Device
DALI DT6 / DT8 TC DA Device L N DA+ DA-
DA
L N DA+ DA-
DA
2. Colour temperature tuning Turn the rotary knob either clockwise or anticlockwise: The connected lamps are tuning color cooler (increase colour temperature ) or warmer (reduce colour temperature ). Turn slowly = Colour change small Turn quickly = Colour change great Only works with the DALI DT8 tc devices. The rotary knob does not have a limit stop!
* *
18
1.2 Min
Rev: A1
26.6
4 5mm
2 Max 2.5mm2
<300m
DA
DALI DT6 / DT8 TC Device
Control location 3
All rights reserved. The information in this document is subject to change without notice. L N DA+DA-
Technical data
Intended use
Input voltage
230-240VAC, 50/60Hz
Max power
3W
Control interface
DA+, DA-
Output voltage
10-16.5V
1. Switching 2. Dimming 3. Colour temperature tuning(for DALI DT8 only) 4. Memory
70.8 60 Φ3.5
To utilize the lowest possible dim level (0.1%) please make sure that the drivers used in the installation support dimming down to 0.1%.
*
4mA
Standby power
Typ. 0.3W
No load pwer
Typ. 0.5W
Color temperature tuning range
2000K ~ 10000K
Working temp.
ta: 0 ~ +50°C, tc: 70°C
DALI-mode
DT6, DT8 tunable white
Dimming range
0.1 % – 100 %
Mains surge capability (between L – N)
0.5 kV
Operating life
50,000 cycles
Warranty
5 years
Φ72.5
50
Environment!
2 79 .
.5
Control location 4
dimmer has memory and will store the *lastThebrightness & color temperature or saved DALI DT6 / DT8 TC DA Device
AC Mains N DA+ DA-
Control location 2
Φ4.2 Consider the protection of the environment! Used electric and electronic devices must not be disposed of with domestic waste.
84
DA
switch-on brightness.
DA
L N DA+ DA-
Φ4
The Dimmer is designed for a life-time stated above under reference conditions and with a failure probability of less than 10%. The relation of tc to ta temperature depends on the installation conditions.
L
C
3. Switching Press the rotary knob: the connected lamps are switched-on or off.
L N DA+DA-
Φ60
52.25
DALI current draw
Control location 1
70.8
Max load @ Ta=25°C 46 DALI ECGs / 92mA
Slave Mode using external DALI Power Supply Slave dimmers connected to DALI only (inactive power supply). DALI-power supplied by external system. Number of DALI-devices depending on the limitation the external control system. Each connected dimmer draws 4 mA from the DALI bus.
W
DALI DT6 / DT8 TC DA Device
DA
Commissioning DALI DT6 / DT8 TC DA Device
L N DA+ DA-
DA
The device contains valuable raw materials which can be recycled. Therefore, dispose of the device at the appropriate collecting depot. DALI DT6 / DT8 TC DA Device DA
1. Save switch-on brightness If the lighting is not always to be switched on with the same brightness, then this can be saved as a switch on brightness. (1).Switch on light. (2).Set required switch-on brightness. (3).Press the rotary knob for longer than 10 seconds. The lighting briefly switches off-on-off and then on. The switch-on brightness is saved.
4. Activate dimming mode & tuning mode Double click(press <0.5s) the rotary knob to switch between dimming mode and tuning mode. The dimmer is default in dimming mode *unless activate to tuning mode, and will return to dimming mode if no tuning over 30s.
2 times 0.5S 2. Delete switch-on brightness (1).Switch the light off. (2).Press the rotary knob for longer than 10 seconds. The lighting briefly switches on-off and then on. The switch-on brightness has been deleted.
ww cw