Innovative. Integrated. Simple. Energy Saving Lighting Controls
Product Catalog VACANCY & OCCUPANCY SENSORS DAYLIGHTING CONTROLS LIGHTING CONTROL PANELS WIRELESS LIGHTING CONTROLS EMERGENCY LIGHTING CONTROLS
2
Table of Contents Go to specific section by clicking on the product category. Hubbell Building Automation
4-7
Hubbell Building Automation
4
HBA Energy Conservation
6
Support, Service and Quotes
7
Vacancy & Occupancy Sensors
8-65
10-19
LightHAWK2TM
20-27
OMNI
TM TM
OMNI-BP
28-35
LightOWLTM
36-41
42-45
IWSZP Sensors
TD300 Timer
46-47
Low Voltage Switches
48
HBA Tracker
49
Power Packs and Relays
50-56 57
Accessories
Indoor/Outdoor Sensors
WASP2TM
58-65 59-61
Dimming WASP
WASP Lens Options
TM
62-64 65
Daylighting Controls
65-97
ZONE5TM
66-77
DLC Controls
78-83
Luxstat
84-97
Lighting Control Panels
98-151
LX Networked Lighting Controls
100-137
CX Commercial Lighting Controls
138-151
Wireless Lighting Controls
152-211
®
wiHUBB
153-174
wiSTARTM
175-189
wiSCAPE
190-211
TM
Emergency Lighting Controls
212-219
® Registered trademarks of Hubbell Building Automation, Inc. (HBA), MYTECH Corporation and Unenco. TM Trademarks of Hubbell Building Automation, Inc. LightOWL, LightHAWK, The OMNI, wiSTAR, Daylight Tracker, IntelliDAPT, HBA WASP2, wiHUBB, Zone5, and CX are registered trademarks of Hubbell Building Automation, Inc. Other product and company names mentioned herein may be the trademarks of their respective owners. Printed in the United States of America. ©Copyright 2014, Hubbell Building Automation, Inc. Hubbell Building Automation, Inc. products are protected under the following United States of American Patents: 6,222,191; 439,853; 435, 798; 430,056; 430,055; 6,078,253; 5,986,357; 404,326; 404,325; 401,175; and 5,640,143. Specifications Subject to Change Without Notification. Product photography throughout the Hubbell Building Automation product catalog, by Jesse Knish Photography – Austin, Texas USA.
Hubbell Building Automation Hubbell Building Automation is the leading developer of groundbreaking technologies in wireless lighting controls, LED and fluorescent controls, occupancy|vacancy sensors and lighting control panels. With over 30 years of lighting control experience, HBA provides complete energy-saving solutions. All HBA products come with a five-year limited warranty.
PAGE 4
A Name You Can Trust – Hubbell Hubbell Building Automation, a subsidiary of Hubbell Incorporated (A Delaware Corporation), manufactures a complete suite of energy-saving lighting control solutions. Founded in 1888 by Harvey Hubbell II, Hubbell Inc. has been a long-time contributor to new product design and manufacturing innovation. In 1896, Hubbell invented the world’s first lighting control device: the pull chain switch. More than 100 years later, Hubbell Building Automation (HBA), headquartered in Austin, Texas, continues a tradition of innovation with the development of a vast array of energy-saving lighting controls.
Innovative Vacancy/Occupancy Sensors
Wireless Lighting Controls need
Hubbell Building Automation proudly offers wiHUBB®,
adjustments throughout the year as seasons change, when
wiSTARTM and wiSCAPETM indoor and outdoor wireless
airflow is modified, or if furniture layout or occupancy
lighting controls. While installation of wired systems is often
patterns change. When these sensors are not constantly
complicated and costly, Hubbell Building Automation’s
monitored and adjusted, energy savings objectives are not
wireless lighting controls feature a future-proof design
met.
including a self-healing wireless mesh network. Many
Traditional
vacancy
and
occupancy
sensors
wireless-enabled fixtures are available through our family of In response to this need, HBA introduced the industry’s
quality brands under the umbrella of Hubbell Lighting.
first self-adapting sensor. HBA’s patented IntelliDAPT
®
technology is the key to maximizing energy savings—
Wireless lighting controls allow for individual fixture control
from open offices to the manufacturing floor, digital
without needing to know how the circuit is wired or having
microprocessor technology makes all sensor adjustment
to pull control wires to each fixture location.
decisions. Smart software monitors the controlled area and makes sensitivity and timer adjustments automatically. Vacancy and occupancy sensors with IntelliDAPT provide maintenance-free “install-and-forget” operations. Integrated Networked Lighting Controls Hubbell Building Automation’s innovative CX Commercial Lighting Control Panel offers expanded programming options to increase energy conservation, and can save up to 50% in labor and materials when used in place of conventional time clock and contactor combinations. The LX Series Lighting Control Panels deliver networked lighting controls with rich functionality, an easy-to-use graphical user interface for local and remote system management, and unmatched integration support for other building systems and network protocols.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 5
Energy Conservation Hubbell Building Automation offers a broad range of vacancy and occupancy sensors and lighting controls that meet the latest energy efficiency codes and standards. Energy conservation has become a significant global movement, with nations, states, and local municipalities creating new codes and standards of efficiency for both commercial and residential buildings. These codes and standards include: •
LEED® (Leadership in Energy and Environmental Design) certification in new and renovated facilities through the U.S. Green Building Council (USGBC) promotes sustainable building design.
•
California Energy Commission’s (CEC) Title 24 program enforces stringent standards and regulations to reduce energy consumption, including automatic lighting control and shut-off .
•
ASHRAE/IESNA 90.1 energy efficiency code requires interior lighting in all buildings to be controlled with automatic devices.
•
Backed by HBA Service and Support
IECC® (International Energy Conservation Code) compliance requires automatic shut-off of lighting which is
HBA Occupancy Sensors are backed by Hubbell Building
now adopted by most states in some form.
support including:
As energy concerns increase, the “greening” of commercial and
Automation’s sustainability initiative and superior service with
•
residential buildings will continue through stringent standards and energy conservation initiatives like the EPA’s ENERGY STAR
savings •
program, or the 2030 Challenge which aims to reduce energy use by 50% before 2030.
Valuable online ROI worksheet for calculating energy Product selection guide for choosing the right HBA Occupancy Sensor and technology
•
Online specification assistance through AutoCAD drawings, templates and documentation
HBA Lighting controls Play a Key Role
•
In the U.S., lighting consumes 22% of electricity and represents $40 billion a year in energy costs. In a typical office building,
for a significant return on investment (ROI).
design
assistance
for
deploying
vacancy/ occupancy sensors in a variety of applications •
where lighting accounts for 35 to 45% of energy use, HBA Lighting Controls have the potential to reduce wasted lighting by 13 to 90%
Comprehensive Highly
knowledgeable
network
of
specification
professionals and trained, dedicated sales staff •
A commitment to safeguard the environment through environmental stewardship, innovative products and efficient operations
For more information about Hubbell Building Automation’s sustainability initiative and access to our complete suite of online tools, visit our website at www.hubbell-automation.com.
Pa g e 6
hubbell-automation.com
Support, Service and Quotations Hubbell Building Automation provides thorough answers to your questions and ensures the best service.
Contact Information Telephone — Austin, TX USA 512.450.1100
HBA’s Service and Support groups are available daily from 8am to 5pm CST. Customer Service
Get a personalized level of service: • Detailed product knowledge • Fast and accurate order entry • Timely order acknowledgments • Order management from initial ordering to shipping
Telephone — Toll-Free 888.698.3242 Fax — Orders Only 512.450.0864 Fax — General 512.450.1215
Technical Services
Fax — Toll-Free Customer Service 877.783.9201
HBA’s technical services include quotations, factory-certified occupancy sensor layouts, technical phone support, application support, and technical documentation.
Corporate Website hubbell-automation.com
Quotations
HBA’s Quotations Group coordinates with the Technical Services Group to provide detailed drawings and accurate quotations, working with you to ensure all needs of your project are fulfilled. Get detailed submittal packages, necessary product documentation and project-specific information.
Technical Drawing Submittal hba-cad@hubbell-automation.com
Factory-Certified Layouts
We guarantee the type and placement of each control on every drawing. Send electronic AutoCAD files and we’ll create a factory-certified, competitive layout with a detailed Bill of Materials.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 7
Vacancy & Occupancy Sensors
Pa g e 8
Control Energy Costs Most Reliable Motion Sensing Technologies A sensor is only as good as it’s proper use and placement. Different applications require different sensor technologies to provide you with the best sensor coverage and performance. Hubbell Building Automation's motion sensors are available with the most reliable indoor motion sensor technologies currently available: Passive Infrared (PIR), Ultrasonic (US), and Dual Technology.
Passive Infrared Technology
Ultrasonic Technology
Dual Technology
Passive infrared sensors provide the best
Ultrasonic sensors provide the best solution
Dual technology sensors combine passive
solution for major motion detection. These
for detecting minor motion such as typing,
infrared and ultrasonic technologies for
sensors use a specially designed lens to
reading, and writing. These sensors emit a
maximum reliability. Both technologies
divide the space into separate zones. When
safe, inaudible sound wave into the control
must detect occupancy to activate lighting,
a person crosses between these zones, the
space. Minor movements cause frequency
and only one technology is required to
sensor detects occupancy. Passive infrared
shifts in the emitted waves which are detected
keep lighting on. Dual technology sensors
sensors are perfect for small, enclosed
by the senor. Because ultrasonic sensors are
are the best solution for most applications.
spaces with frequent occupant movement.
volumetric and do not require a clear line of sight, they are ideal for hallways or restrooms with stalls.
The Right Technology for the Right Application IntelliDAPTŽ is HBA's patented self-adapting sensor technology that enables automatic sensitivity and timing adjustments for true install-and-forget operation. IntelliDAPT technology comes standard in HBA’s OMNI, LightOWL and LightHAWK sensors and switches. It works in conjunction with Passive Infrared, Ultrasonic and Dual technology to maximize energy savings.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax orders ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 9
LightHAWK2TM Dual Technology Wall Switch Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
LOW
24 VDC
VOLTAGE
120 277
347
VAC
VAC
With a coverage area of up to 1,000 square feet and 180° of detection, the LightHAWK2TM Dual Technology Wall Switch Sensor combines ultrasonic (US) and passive infrared (PIR) technologies for unequaled motion detection. By far the most versatile and widely used sensor in the LightHAWK2 product line, this sensor can be used in a large number of applications,and won’t leave users waving their hands in the dark. LHMT sensors feature Hubbell Building Automation’s patented IntelliDAPTTM technology, which makes all the sensor adjustment decisions automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. With selectable operating modes—auto on/off or manual on/auto off—and a builtLHMTS1
in photosensor for automatic daylight harvesting, LHMT sensors are the most capable choice in today’s marketplace.
PRODUCT FEATURES
DAYLIGHT HARVESTING
OCCUPANCY SENSING
IntelliDAPT
• Digital dual technology: (US) and (PIR) sensors • IntelliDAPT self-adaptive technology—no manual adjustment required 1.8”
• 1 or 2 relay models for single-level switching or bi-level switching • Occupancy (auto-on) and Vacancy (manual-on) operating modes • Available with or without Neutral • 1,000 square-foot, 180° coverage area • RhinoTuff™ vandal resistant lens • Dual 120/277VAC operation • No minimum load requirement
Fits Standard Decorator Style Wallplate (sold separately)
RhinoTuffTM Vandal Resistant Lens 4.2”
On/Off Button
• Zero Arc Point Switching • Five-year limited warranty
Ultrasonic Sensor
Galvanized Steel Mounting Strap
2.1” LHMTD2
Pa g e 10
hubbell-automation.com
Dual Load Wiring With Neutral
Single Load Wiring Without Neutral
General Specifications IntelliDAPT Technology
Self-adjusting timer Self-adjusting Ultrasonic (US) and passive infrared (PIR) sensitivity Automatic false-on/false-off corrections No manual adjustments required
Time Delay
Auto mode: 4–30 minutes; self-adjusts based on occupancy Fixed mode: 4, 8, 15, and 30 minutes Test mode: 5 seconds
Ultrasonic (US) Output
40kHz output
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical RhinoTuff lens
Photocell
Natural light override range: 10–500 foot-candles
Coverage
1,000 square-foot, 180° coverage area
Power Requirements
120/277VAC; 50/60Hz 347VAC; 50/60Hz 24VDC (requires UVPP)
Electrical Ratings
120VAC: 800W Incandescent; 1,000W Fluorescent; 1/6 HP 277VAC: 1,800W Fluorescent; 1/6 HP 347VAC; 1,500W Fluorescent; 1/6 HP
Minimum Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Impact-resistant lens Color-coded leads are 6” long Wrap-around galvanized steel mounting strap
Dimensions
4.2”H x 1.8”D x 2.1”W; .37” extension
Weight
2.9 oz
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (standard switch box) Decorator-style wall plate sold separately
Warranty
Five-year limited
Ordering Information
LHMTS
model LightHAWK2™ Dual Technology Single Relay
LHMTD LightHAWK2™ Dual Technology Dual Relay
NOTE: * † -
buttons 0 1* 2†
G N 24V G347 N347
wiring Ground (120/277V) Neutral (120/277V) Low Voltage Ground (347V) Neutral (347V)
WH IV LA GY BK
color White Ivory Light Almond Gray Black
Mode Blank Switchable Vacancy or Occupancy Mode M Vacancy Mode Only
Only available with LightHAWK2™ Dual Technology Single Relay. Only available with LightHAWK2™ Dual Technology Dual Relay. Wall switch plates are sold separately. Low voltage sensors require a power pack that is sold separately. See wiring diagram on specification sheet.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 11
LightHAWK2TM Ultrasonic Wall Switch Sensor
TITLE
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
LOW
120 277
24 24 CEC
VDC
347
VAC
VOLTAGE
VAC
The LightHAWK2TM Ultrasonic Wall Switch Sensor uses ultrasonic (US) technology for detecting minor movement in areas with line-of-sight obstacles such as cubicles and stalls. Because ultrasonic technology is volumetric in nature, its coverage pattern can adapt itself to fill oddly shaped spaces such as alcoves, recesses, and nooks. This sensor has a coverage area of up to 400 square feet and 180° of detection. This sensor includes HBA patented IntelliDAPT® technology. LHUS sensors feature Hubbell Building Automation’s patented IntelliDAPTTM technology, which makes all the sensor adjustment decisions automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. With selectable operating modes—automatic ON/OFF or manual ON/automatic LHUSS1
OFF—and a built-in photosensor for automatic daylight harvesting, the LHUS sensors are the most capable choice in today’s market place.
PRODUCT FEATURES
DAYLIGHT HARVESTING
OCCUPANCY SENSING
IntelliDAPT
• Digital Ultrasonic (US) sensor 1.8”
• IntelliDAPT self-adaptive technology—no manual adjustment required • 1 or 2 relay models for single-level switching or bi-level switching control • Occupancy (auto-on) and Vacancy (manual-on) operating modes • Available with or without Neutral
Photo Cell/ LED Indicator
• 1,000 square-foot, 180° coverage area • Dual 120/277VAC operation • No minimum load requirement 4.2”
• Zero Arc Point Switching
On/Off Button
• Five-year warranty Fits Standard Decorator Style Wallplate (sold separately)
Ultrasonic Sensor Galvanized Steel Mounting Strap
2.1”
LHUSD2
Pa g e 12
hubbell-automation.com
Dual Load Wiring With Neutral
Single Load Wiring Without Neutral
General Specifications IntelliDAPT Technology
Self-adjusting timer Self-adjusting ultrasonic (US) sensitivity Automatic false-on/false-off corrections No manual adjustments required
Time Delay
Auto mode: 4–30 minutes; self-adjusts based on occupancy Fixed mode: 4, 8, 15, and 30 minutes Test mode: 5 seconds
Ultrasonic (US) Output
40kHz output
Photocell
Natural light override range: 10–500 foot-candles
Coverage
400 square-foot, 180° coverage area
Power Requirements
120/277VAC; 50/60Hz 347VAC; 50/60Hz 24VDC (requires UVPP)
Electrical Ratings
120VAC: 800W Incandescent; 1,000W Fluorescent; 1/6 HP 277VAC: 1,800W Fluorescent; 1/6 HP 347VAC; 1,500W Fluorescent; 1/6 HP
Minimum Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Color-coded leads are 6” long Wrap-around galvanized steel mounting strap
Dimensions Weight
4.2”H x 1.8”D x 2.1”W; .37” extension 2.9 oz
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (standard switch box) Decorator-style wall plate sold separately
Warranty
Five-year limited
Ordering Information
LHUSS LHUSD
model LightHAWK2™ Ultrasonic Single Relay LightHAWK2™ Ultrasonic Dual Relay
buttons 0 1* 2†
G N 24V G347 N347
wiring Ground (120/277V) Neutral (120/277V) Low Voltage Ground (347V) Neutral (347V)
WH IV LA GY BK
color White Ivory Light Almond Gray Black
Mode Blank Switchable Vacancy or Occupancy Mode M Vacancy Mode Only
NOTE: * Only available with LightHAWK2™ Ultrasonic Single Relay. † Only available with LightHAWK2™ Ultrasonic Dual Relay. - Wall switch plates are sold separately. - Low voltage sensors require a power pack that is sold separately. See wiring diagram on specification sheet.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 13
LightHAWK2TM Passive Infrared Wall Switch Sensor
TITLE
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
LOW
120 277
24 24 CEC
VDC
347
VAC
VOLTAGE
VAC
The LightHAWK2™ Passive Infrared Wall Switch Sensor uses passive infrared (PIR) technology to detect motion. The most affordable of the motion detecting technologies, this sensor type is ideal for detecting large motion in areas with an unobstructed view of the sensor. This sensor has a coverage area of up to 1,000 square feet and 180° of detection. LHIR sensors feature Hubbell Building Automation’s patented IntelliDAPTTM technology, which makes all the sensor adjustment decisions automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. With selectable operating modes — automatic ON/OFF or manual ON/automatic OFF — and a built-in photosensor for automatic daylight harvesting, LHIR sensors LHIRS1
are the best choice in today’s market place.
PRODUCT FEATURES
DAYLIGHT HARVESTING
OCCUPANCY SENSING
IntelliDAPT
• Digital passive infrared (PIR) sensor • IntelliDAPT self-adaptive technology—no manual adjustment required
1.8”
• 1 or 2 relay models for single-level switching or bi-level switching control • Occupancy (auto-on) and Vacancy (manual-on) operating modes • Available with or without Neutral
RhinoTuffTM Vandal Resistant Lens
• 1,000 square-foot, 180° coverage area • RhinoTuff™ vandal resistant lens • Dual 120/277VAC operation
4.2”
On/Off Button
• No minimum load requirement • Zero Arc Point Switching • Five-year warranty
Fits Standard Decorator Style Wallplate (sold separately)
Photo Cell/ LED Indicator Galvanized Steel Mounting Strap
2.1”
LHIRD2
Pa g e 14
hubbell-automation.com
Dual Load Wiring With Neutral
Single Load Wiring Without Neutral
IR Motion
General Specifications IntelliDAPT Technology
Self-adjusting timer Self-adjusting passive infrared (PIR) sensitivity Automatic false-on/false-off corrections No manual adjustments required
Time Delay
Auto mode: 4–30 minutes; self-adjusts based on occupancy Fixed mode: 4, 8, 15, and 30 minutes Test mode: 5 seconds
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical RhinoTuff lens
Photocell
Natural light override range: 10–500 foot-candles
Coverage
1,000 square-foot, 180° coverage area
Power Requirements
120-277VAC; 50/60Hz 347VAC; 50/60Hz 24VDC (requires UVPP)
Electrical Ratings
120VAC: 800W Incandescent; 1,000W Fluorescent; 1/6 HP 277VAC: 1,800W Fluorescent; 1/6 HP 347VAC; 1,500W Fluorescent; 1/6 HP
Minimum Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Impact-resistant lens Color-coded leads are 6” long Wrap-around galvanized steel mounting strap
Dimensions Weigh
4.2”H x 1.8”D x 2.1”W; .37” extension 2.9 oz
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (standard switch box) Decorator-style wall plate sold separately
Warranty
Five-year limited
Ordering Information
LHIRS LHIRD
model LightHAWK2™ Passive Infrared Single Relay LightHAWK2™ Passive Infrared Dual Relay
buttons 0 1* 2†
G N 24V G347 N347
wiring Ground (120/277V) Neutral (120/277V) Low Voltage Ground (347V) Neutral (347V)
WH IV LA GY BK
color White Ivory Light Almond Gray Black
Mode Blank Switchable Vacancy or Occupancy Mode M Vacancy Mode Only
NOTE: * Only available with LightHAWK2™ Passive Infrared Single Relay † Only available with LightHAWK2™ Passive Infrared Dual Relay - Wall switch plates are sold separately. - Low voltage sensors require a power pack that is sold separately. See wiring diagram on specification sheet.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 15
LightHAWK2TM Night Light PIR Wall Switch Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
120 277 VAC
Whether used for code compliance or for mere convenience, the LightHAWK2™ Night Light Wall Switch Sensor combines passive infrared (PIR) technology with the added safety and comfort of a night light. Ideal for use in the hospitality industry, this sensor has a coverage area of up to 1,000 square feet and 180° of detection and is ready to use anywhere a little extra light would make all the difference. LHIR sensors feature Hubbell Building Automation’s patented IntelliDAPTTM technology, which makes all the sensor adjustment decisions automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. With selectable operating modes — automatic ON/OFF or manual ON/automatic OFF — and a built-in photosensor for automatic daylight harvesting, LHN-IR sensors LHN-IRS1
are the best choice in today’s market place.
PRODUCT FEATURES
DAYLIGHT HARVESTING
OCCUPANCY SENSING
IntelliDAPT
• Digital passive infrared (PIR) sensor • IntelliDAPT self-adaptive technology—no manual adjustment required
1.8”
• 1 or 2 relay models for single-level switching or bi-level switching • Occupancy (auto-on) and Vacancy (manual-on) operating modes • Night Light mounted under lens • 1,000 square-foot, 180° coverage area
Night Light Behind RhinoTuffTM Vandal Resistant Lens
• RhinoTuff™ vandal resistant lens • Dual 120/277 VAC operation • No minimum load requirement
4.2”
• Zero Arc Point Switching • Five-year limited warranty
On/Off Button Fits Standard Decorator Style Wallplate (sold separately)
Photo Cell/ LED Indicator
2.1”
Pa g e 16
Galvanized Steel Mounting Strap
hubbell-automation.com
Single Relay Wiring Without Neutral
IR Motion
General Specifications IntelliDAPT Technology
Self-adjusting timer Self-adjusting passive infrared (PIR) sensitivity Automatic false-on/false-off corrections No manual adjustments required
Time Delay
Auto mode: 4–30 minutes; self-adjusts based on occupancy Fixed mode: 4, 8, 15, and 30 minutes Test mode: 5 seconds
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical RhinoTuff lens
Photocell
Natural light override range: 10–500 foot-candles
Coverage
1,000 square-foot, 180° coverage area
Power Requirements
120/277VAC; 50/60Hz
Electrical Ratings
120VAC: 800W Incandescent; 1,000W Fluorescent; 1/6 HP 277VAC: 1,800W Fluorescent; 1/6 HP
Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Impact-resistant lens Color-coded leads are 6” long Wrap-around galvanized steel mounting strap
Dimensions Weight
4.2”H x 1.8”D x 2.1”W; .37” extension 2.9 oz
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (standard switch box) Decorator-style wall plate sold separately
Warranty
Five-year limited
Ordering Information LHN-IRS
LHN-IRS
model LightHAWK2™ Night Light Passive Infrared Single Relay
NOTE: - Wall switch plates are sold separately.
1 buttons 1
wiring N Neutral (120/277V) N347 Neutral (347V)
WH IV LA GY BK
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
color White Ivory Light Almond Gray Black
Mode Blank Switchable Vacancy or Occupancy Mode M Vacancy Mode Only
Pa g e 17
LightHAWK2TM Dimming Wall Switch Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
120 277 VAC
The LightHAWK2™ Dimming Wall Switch Sensor combines passive infrared (PIR) technology with the additional energy savings of 0-10V dimming. The user can set the occupied level to a predetermined level or set the sensor to activate to the last-used dimming level. With ON/OFF and Dimming Control, the user can easily adjust the light level for their area. This sensor has a coverage area of up to 1,000 square feet and 180° of detection. LHIR sensors feature Hubbell Building Automation’s patented IntelliDAPTTM technology, which makes all the sensor adjustment decisions automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. With selectable operating modes — automatic ON/OFF or manual ON/automatic OFF, occupancy on to predetermined dimming level go to last dimming setting LHD-IRS3
upon occupancy — and a built-in photosensor for automatic daylight harvesting, LHD-IR sensors are the best choice in today’s market place.
PRODUCT FEATURES DAYLIGHT HARVESTING
OCCUPANCY SENSING
IntelliDAPT
• All-digital passive infrared (PIR) sensor •
0-10V dimming capabilities
1.8”
• IntelliDAPT self-adaptive technology—no manual adjustment required • 1 relay model for single-level switching • Occupancy (auto-on) and Vacancy (manual-on) operating modes • Available with or without Neutral
RhinoTuffTM Vandal Resistant Lens
• 1,000 square-foot, 180° coverage area • RhinoTuff™ vandal resistant lens 4.2”
• Dual 120/277V or 347V operation
On/Off Button
• No minimum load requirement • Zero Arc Point Switching • Five-year warranty
Fits Standard Decorator Style Wallplate (sold separately)
Lower Button Photo Cell/ LED Indicator
2.1”
Pa g e 18
Raise Button
Galvanized Steel Mounting Strap
hubbell-automation.com
Single Relay Wiring
IR Motion
General Specifications IntelliDAPT Technology
Self-adjusting timer Self-adjusting passive infrared (PIR) sensitivity Automatic false-on/false-off corrections No manual adjustments required
Time Delay
Auto mode: 4–30 minutes; self-adjusts based on occupancy Fixed mode: 4, 8, 15, and 30 minutes Test mode: 5 seconds
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical RhinoTuff lens
Dimming
0-10V, Sink up to 30mA
Photocell
Natural light override range: 10–500 foot-candles
Coverage
1,000 square-foot, 180° coverage area
Power Requirements
120-277VAC; 50/60Hz
Electrical Ratings
120-277VAC: 800W Incandescent; 1,000W Fluorescent; 1/6 HP
Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Impact-resistant lens Color-coded leads are 6” long Wrap-around galvanized steel mounting strap
Dimensions
4.2”H x 1.8”D x 2.1”W; .37” extension
Weight
2.9 oz
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (standard switch box) Decorator-style wall plate sold separately
Warranty
Five-year limited
Ordering Information LHD-IRS
LHD-IRS
model LightHAWK2™ Dimming Passive Infrared Single Relay
3 buttons 3
N N347
wiring Neutral (120/277V) Neutral (347V)
WH IV LA GY BK
color White Ivory Light Almond Gray Black
Mode Blank Switchable Vacancy or Occupancy Mode M Vacancy Mode Only
NOTE: - Wall switch plates are sold separately.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 19
OMNITM Low Voltage Dual Technology Ultrasonic and PIR
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
24 VDC
VOLTAGE
The OMNIDT combines ultrasonic (US) and passive infrared (PIR) technologies to turn lighting on and off based on occupancy. This dual technology provides accurate turn-ons while virtually eliminating false-offs. This sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, Intellidapt software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
OMNIDT2000
PRODUCT FEATURES
OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology - no manual adjustment
required PIR Sensor
• All-digital dual technology (ultrasonic [US] and
passive infrared [PIR]) sensor
1.5”
• Non-volatile memory for sensor settings • 500–2,000 square-foot coverage area (depending on model)
Ultrasonic Sensor
• Optional relay and photocell control • Optional Quick to Install (QTI) connector • UL and cUL listed • California Title 24 compliant
4.5”
• Five-year limited warranty
Pa g e 2 0
hubbell-automation.com
22'
22'
23'
32'
32' 23'
22'
23'
12'
12'
12'
23' 32'
16' 23'
45' 64'
US Minor Motion
IR Minor Motion
US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
US Major Motion
IR Major Motion
OMNIDT500
OMNIDT1000
US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
OMNIDT2000
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared thresholds Automatic false-on/false-off corrections
LED Lamp
Red - infrared motion Green - ultrasonic detection
Timer Timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Ultrasonic (US) Output
OMNIDT500: 40kHz output OMNIDT1000 and OMNIDT2000: 32kHz
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24VDC; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0 to 1,000 lux)
Coverage
500 sq ft; 180° coverage 1000 sq ft; 180° coverage 2000 sq ft, 360° coverage
Power Requirements
24V, 33mA (uses UVPP and MP- Series power pack- not included)
Output
24V active high-logic control signal with short circuit protection and optional dry contact (see RP options)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C)
Relative humidity (non-condensing): 0% to 95%
Construction
Casing- rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors
Color-coded leads are 6” long
Dimensions
4.5”DIA, 1.5”H
Weight
5.0 oz
Color
Off-white
Mounting Mounting base provided Recommended mounting height: 8ft with a max mounting height of 12ft. Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information omni model omni
DT technology DT Dual Technology
coverage 500 500 sq. ft. 1000 1,000 sq. ft. 2000 2,000 sq. ft.
Relay / Photocell option
RP Blank
Relay & Photocell No Option
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI Blank
QTI Quick to Install No QTI
Pa g e 2 1
OMNITM Low Voltage Ultrasonic Ceiling Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
LOW
24 VDC
VOLTAGE
The OMNIUS uses ultrasonic (US) technology to turn lighting on and off based on occupancy. Designed specifically for both areas with obstructions (e.g. columns, cubicles, stalls, and filing cabinets) and areas with long periods of minor-motion activity (e.g. typing), this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget OMNIUS500
operation.
PRODUCT FEATURES OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology - no manual adjustment required • Superior all-digital ultrasonic (US) minor motion detection • Non-volatile memory for sensor settings • 500–2,000 square-foot coverage area
1.5” Ultrasonic Sensor
(depending on model) • Optional relay and photocell control • Optional Quick to Install (QTI) connector
• UL and cUL listed • California Title 24 compliant • Five-year limited warranty
Pa g e 2 2
4.5”
hubbell-automation.com
32'
23'
23'
16’
32' 23'
45' 64'
32' 23'
16' 23'
Minor Motion
Minor Motion
Major Motion
Major Motion
US 500 Range
Minor Motion Major Motion
US 1000 Range
US 2000 Range
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting ultrasonic thresholds Automatic false-on/false-off corrections
LED Lamp
Green - ultrasonic motion
Timer Timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Ultrasonic (US) Output
OMNIUS500: 40kHz output OMNIUS1000 and OMNIUS2000: 32kHz output
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24VDC; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0–1,000 lux)
Coverage
500–2,000 square feet (depending on model)
Power Requirements
24V, 33mA (uses UVPP and MP- Series power pack- not included)
Output
24V active high-logic control signal with short circuit protection and optional dry contact (see RP options)
24V active high-logic control signal with short circuit protection
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing - rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors Color-coded leads are 6” long
Dimensions
4.5”DIA, 1.5”H
Weight
8.2 oz
Color
Off-white
Mounting Mounting base provided
Recommended mounting height: 8ft with a max mounting height of 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information omni model omni
US technology us Ultrasonic
coverage 500 500 sq. ft. 1000 1,000 sq. ft. 2000 2,000 sq. ft.
Relay / Photocell option RP Relay & Photocell Blank No Option
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI QTI Blank
Quick to Install No QTI
Pa g e 2 3
OMNITM Low Voltage Passive Infrared Ceiling Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
24 VDC
VOLTAGE
The OMNIIR uses passive infrared (PIR) technology to turn lighting on and off based on occupancy. Designed specifically for areas with long-range major-motion activity, this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
OMNIIR
PRODUCT FEATURES
OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology—no manual adjustment required • All-digital passive infrared (PIR) sensor • Non-volatile memory for sensor settings
PIR Sensor
• 450 - 1,500 square-foot coverage area (depending on model) • Optional relay and photocell control
1.5”
• Optional Quick to Install (QTI) connector • UL and cUL listed • California Title 24 compliant • Five-year limited warranty
4.5”
Pa g e 2 4
hubbell-automation.com
6'
12'
12'
22'
Minor Motion
Minor Motion
Major Motion
Major Motion
OMNI IR Range
OMNI IRL Range
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared thresholds Automatic false-on/false-off corrections
LED Lamp
Red - infrared motion
Timer Timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24VDC; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0–1,000 lux)
Coverage
450 - 1,500 square feet
Power Requirements
24V, 33mA (uses UVPP and MP- Series power pack- not included)
Output
24V active high-logic control signal with short circuit protection and optional dry contact (see RP options)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing - rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors Color-coded leads are 6” long
Dimensions
4.5”DIA, 1.5”H
Weight
5.0 oz
Color Off-white Mounting
Mounting base provided
Recommended mounting height: 8ft with a max mounting height of 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
omni Model omni
ir Technology IR
Passive Infrared
Coverage L Blank
Long Range IR, 1,500 sq. ft. 450 sq. ft.
Relay / Photocell option RP Blank
Relay & Photocell No Option
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI QTI Blank
Quick to Install No QTI
Pa g e 2 5
OMNITM Low Voltage Dual Technology Acoustic and PIR
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
24 VDC
VOLTAGE
The OMNIDIA combines passive infrared (PIR) and acoustic (sound-activated) technologies to turn lighting systems on and off based on occupancy. The OMNIDIA features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
OMNIDIA
PRODUCT FEATURES
OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology—no manual adjustment required • All-digital dual technology (acoustic and passive infrared [PIR]) sensor • Non-volatile memory for sensor settings
PIR Sensor
• 450 square-foot coverage • Optional relay and photocell control
1.5”
• Optional Quick to Install (QTI) connector • UL and cUL listed • California Title 24 compliant • Five-year limited warranty
4.5”
Pa g e 2 6
hubbell-automation.com
6' 12' 6' 12'
Minor Motion Major Motion
Minor Motion Major Motion
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared thresholds Automatic false-on/false-off corrections
LED Lamp
Red - infrared motion Green - acoustic detection
Timer Timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24V; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0–1,000 lux)
Coverage
450 square feet
Power Requirements
24V, 33mA (uses UVPP and MP- Series power pack- not included)
Output
24V active high-logic control signal with short circuit protection and optional dry contact (see RP options)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C)
Relative humidity (non-condensing): 0% to 95%
Construction Casing—rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors
Color-coded leads are 6” long
Dimensions
4.5”DIA, 1.5”H
Weight
5.0 oz
Color
Off-white
Mounting
Mounting base provided
Recommended mounting height: 8ft with a max mounting height of 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information OMNI model OMNI
DIA technology DIA Dual Technology Acoustic & Passive Infrared
Relay/Photocell option RP Relay & Photocell Blank No Option
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI Blank
QTI Quick to Install No QTI
Pa g e 2 7
OMNI-BPTM Line Voltage Dual Technology
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
120 277 VAC
The OMNIDTBP1277 line voltage ceiling sensor combines ultrasonic (US) and passive infrared (PIR) technologies to turn lighting on and off based on occupancy. This dual technology provides accurate turn-ons while virtually eliminating falseoffs. This sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. OMNIDT2000BP1277
PRODUCT FEATURES
OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology - no manual adjustment required •
All-digital dual technology (ultrasonic [US] and passive infrared [PIR]) sensor
4.5”
• Non-volatile memory for sensor settings • 500–2,000 square-foot coverage area (depending on model)
PIR Sensor
• Self-contained power supply • Universal voltage (100-277VAC; 50/60 Hz)
Ultrasonic Sensor
• UL and cUL listed • California Title 24 compliant • Five-year warranty
Power Supply
3.4” 1.95” 2.5”
Pa g e 2 8
hubbell-automation.com
22'
32' 22' 23'
22' 23'
12'
32' 23'
12'
12'
23' 23'
45' 64'
32'
US Minor Motion
IR Minor Motion
US Minor Motion
IR Minor Motion
US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
US Major Motion
IR Major Motion
US Major Motion
IR Major Motion
DT 500 Range
DT 1000 Range
DT 2000 Range
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting ultrasonic and passive infrared thresholds Automatic false-on/false-off corrections
LED Lamp Timer Timeout
Red—infrared motion Green—ultrasonic motion Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Ultrasonic (US) Output
OMNIDT500: 40kHz output OMNIDT1000 and OMNIDT2000: 32kHz
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
Coverage
500 sq ft; 180° coverage 1000 sq ft: 180° coverage 2000 sq ft; 180° coverage
Power Requirements
100/277VAC; 50/60Hz Single phase only
Output
24VDC active high-logic control signal with short circuit protection
Relay Contact Rating
20A: 120VAC Incandescent 20A: 120 or 277VAC Magnetic Ballast 16A: 120 or 277VAC Electronic Ballast 1HP: 120VAC Motor Load 3/4HP: 277VAC Motor Load
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing—rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors Color-coded leads are 6” long
Dimensions
4.5”DIA, 3.4”H
Weight
8.2 oz (232g)
Color
Off-white
Mounting
Mounting using a 3 inch mud ring attached to 4 inch square electrical box Recommended MAX mounting height: 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
OMNIDT500BP1277
model Line Voltage Ultrasonic and PIR Ceiling Sensor 500 Sq Ft coverage
OMNIDT1000BP1277
Line Voltage Ultrasonic and PIR Ceiling Sensor 1000 Sq Ft coverage
OMNIDT2000BP1277
Line Voltage Ultrasonic and PIR Ceiling Sensor 2000 Sq Ft coverage
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 9
OMNI-BPTM Line Voltage Ultrasonic Ceiling Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
120 277 VAC
The OMNIUSBP1277 line voltage ceiling sensor uses ultrasonic (US) technology to turn lighting on and off based on occupancy. Designed specifically for both areas with obstructions (e.g. columns, cubicles, stalls, and filing cabinets) and areas with long periods of minor-motion activity (e.g. typing), this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. OMNIUS500BP1277
PRODUCT FEATURES OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology—no manual adjustment required • Superior all-digital ultrasonic (US) minor motion detection
4.5”
• Non-volatile memory for sensor settings • 500–2,000 square-foot coverage area (depending on model) • Self-contained power supply
Ultrasonic Sensor
• Universal voltage (100-277VAC; 50/60 Hz) • UL and cUL listed • California Title 24 compliant
3.4” Power Supply
• Five-year warranty
1.95”
2.5”
Pa g e 3 0
hubbell-automation.com
32'
23'
32' 23'
23'
32' 23'
23' Minor Motion
Minor Motion
Major Motion
Major Motion
US 500 Range
US 1000 Range
45' 64' Minor Motion Major Motion
US 2000 Range
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting ultrasonic thresholds Automatic false-on/false-off corrections
LED Lamp
Green—ultrasonic motion
Timer Timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy)
Test mode: 8 seconds (for an easy check at installation)
Ultrasonic (US) Output
OMNIUS500: 40kHz output OMNIUS1000 and OMNIUS2000: 32kHz output
Coverage
500–2,000 square feet (depending on model)
Power Requirements
100/277VAC; 50/60Hz Single phase only
Output
24VDC active high-logic control signal with short circuit protection
Relay Contact Rating
20A: 120VAC Incandescent 20A: 120 or 277VAC Magnetic Ballast 16A: 120 or 277VAC Electronic Ballast 1HP: 120VAC Motor Load
3/4HP: 277VAC Motor Load
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C)
Relative humidity (non-condensing): 0% to 95%
Construction
Casing - rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors Color-coded leads are 6” long
Dimensions
4.5”DIA, 3.4”H
Weight
8.2 oz
Color
Off-white
Mounting Mounting using a 3 inch mud ring attached to 4 inch square electrical box Recommended MAX mounting height: 12ft. Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
OMNIUS500BP1277
model Line Voltage Ultrasonic Ceiling Sensor 500 Sq Ft coverage
OMNIUS1000BP1277
Line Voltage Ultrasonic Ceiling Sensor 1000 Sq Ft coverage
OMNIUS2000BP1277
Line Voltage Ultrasonic Ceiling Sensor 2000 Sq Ft coverage
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 3 1
OMNI-BPTM Line Voltage Passive Infrared Ceiling Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
120 277 VAC
The OMNIIRBP line voltage ceiling sensor uses passive infrared (PIR) technology to turn lighting on and off based on occupancy. Designed specifically for areas with long-range major-motion activity, this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
OMNIIRBP1277
PRODUCT FEATURES
OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology—no manual adjustment required
4.5”
• All-digital passive infrared [PIR]) sensor
Passive Infrared Sensor
• Non-volatile memory for sensor settings • 450–1,500 square-foot coverage area (depending on model) • Self-contained power supply • Universal voltage (100-277VAC; 50/60 Hz) • UL and cUL listed • California Title 24 compliant
3.4” Power Supply
• Five-year warranty
1.95” 2.5”
Pa g e 3 2
hubbell-automation.com
6'
12'
12'
22'
Minor Motion
Minor Motion
Major Motion
Major Motion
OMNI IR Range
OMNI IRL Range
General Specifications IntelliDAPT
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared thresholds
Automatic false-on/false-off corrections
LED lamp
Red—infrared motion
Timer timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
Coverage
450–1,500 square feet (depending on model)
Power Requirements
100-277VAC; 50/60Hz Single phase only
Output
24VDC active high-logic control signal with short circuit protection
Relay Contact Rating
20A: 120VAC Incandescent 20A: 120 or 277VAC Magnetic Ballast 16A: 120 or 277VAC Electronic Ballast 1HP: 120VAC Motor Load
3/4HP: 277VAC Motor Load
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C)
Relative humidity (non-condensing): 0% to 95%
Construction
Casing—rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors
Color-coded leads are 6” long
Dimensions
4.5”DIA, 3.4”H
Weight
8.2 oz
Color
Off-white
Mounting
Mounting base provided Recommended MAX mounting height: 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
OMNIIRBP1277 OMNIIRLBP1277
model Line Voltage Passive Infrared Ceiling Sensor 450 Sq Ft coverage Line Voltage Passive Infrared Ceiling Sensor 1500 Sq Ft coverage
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 3 3
OMNI-BPTM Line Voltage Dual Technology Acoustic and Passive Infrared
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Ceiling Mount OCCUPANCY SENSORS
120 277 VAC
The OMNIDIABP line voltage ceiling sensor combines passive infrared (PIR) and acoustic (sound-activated) technologies to turn lighting systems on and off based on occupancy. The OMNIDIABP features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
OMNIDIABP1277
PRODUCT FEATURES
OCCUPANCY SENSING
• IntelliDAPT self-adaptive technology—no manual adjustment required
IntelliDAPT
4.5”
• All-digital dual technology (acoustic and passive infrared [PIR]) sensor
Passive Infrared Sensor
• Non-volatile memory for sensor settings • 450 square-foot coverage • Self-contained power supply • Universal voltage (100-277VAC; 50/60 Hz) • UL and cUL listed
3.4” Power Supply
• California Title 24 compliant • Five-year warranty
1.95” 2.5”
Pa g e 3 4
hubbell-automation.com
DIA Range
6' 12' Minor Motion Major Motion
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared thresholds
Automatic false-on/false-off corrections
LED Lamp
Red—infrared motion Green- acoustic detection
Timer Timeout
Automatic mode: 8–30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
Coverage
450 square feet
Power Requirements
100-277VAC; 50/60Hz Single phase only
Output 24VDC active high-logic control signal with short circuit protection Relay Contact Rating
20A: 120VAC Incandescent 20A: 120 or 277VAC Magnetic Ballast 16A: 120 or 277VAC Electronic Ballast 1HP: 120VAC Motor Load
3/4HP: 277VAC Motor Load
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C)
Relative humidity (non-condensing): 0% to 95%
Construction Casing—rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors
Color-coded leads are 6” long
Dimensions
4.5”DIA, 3.4”H
Weight
8.2 oz
Color
Off-white
Mounting Mounting base provided
Recommended MAX mounting height: 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information OMNIDIABP1277 OMNIDIABP1277
model Line Voltage Dual Technology Acoustic and Passive Infrared Ceiling Sensor 450 Sq Ft coverage
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 3 5
LightOWLTM Dual Technology Ultrasonic and Passive Infrared Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
CEILING AND WALL MOUNT OCCUPANCY SENSORS
24 VDC
VOLTAGE
The LightOWLTM Dual Technology Ultrasonic and Passive Infrared Sensor combines ultrasonic (US) and passive infrared (PIR) technologies to turn lighting on and off based on occupancy. Designed specifically for areas where ceiling sensors are not appropriate, this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
LODT
PRODUCT FEATURES
OCCUPANCY SENSING
IntelliDAPT
• IntelliDAPT self-adaptive technology—no manual adjustment required 3.63”
• All-digital dual technology passive infrared (PIR) and ultrasonic (US) sensor • Non-volatile memory for sensor settings • 1,600 square-foot coverage area
Ultrasonic Sensor
• Optional relay and photocell control • Optional Quick-to-Install (QTI) connector • UL and cUL listed • California Title 24 compliant
6.58”
PIR Sensor
• Five-year limited warranty
3.72”
Pa g e 3 6
hubbell-automation.com
40' 32' 23'
20'
23' 32' US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared and acoustic thresholds Automatic false-on/false-off corrections
LED Lamp
Red - infrared motion Green - ultrasonic detection
Timer Timeout
Automatic mode: 8–30 minutes (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
Ultrasonic (US) Output
Operating frequency: 32kHz
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24VDC; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0–1,000 lux)
Factory set at 3,000 lux (disable photocell)
Coverage
1,600 square feet
Power Requirements
24VDC, 33 mA (uses UVPP and MP-Series power pack—not included)
Output
24VDC active high-logic control signal with short circuit protection and optional dry contact (see: RP Option)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing – Rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) Color-coded leads are 6” long
Dimensions
6.58”H x 3.63”W x 3.72”D
Weight
5.0 oz
Color Off-white Mounting
Mounting base provided Recommended MAX mounting height: 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information lo model LO
dT
DT
technology Dual Technology Ultrasonic and Passive Infrared
Relay / Photocell option RP Relay Photocell Blank No Relay Photocell
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI Blank
QTI Quick to Install No QTI
Pa g e 3 7
LightOWLTM Passive Infrared Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
CEILING AND WALL MOUNT OCCUPANCY SENSORS
24 VDC
VOLTAGE
The LightOWLTM Passive Infrared Sensor sensor uses passive infrared (PIR) technology to turn lighting on and off based on occupancy. Designed specifically for areas with long-range major-motion activity, this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
LOIR
PRODUCT FEATURES
OCCUPANCY SENSING
• IntelliDAPT self-adaptive technology—no manual adjustment required
IntelliDAPT
3.63”
• All-digital dual technology passive infrared [PIR] sensor • Non-volatile memory for sensor settings • 1,600 square-foot coverage area
High Impact Plastic Casing
• Optional relay and photocell control • Optional Quick-to-Install (QTI) connector • UL and cUL listed • California Title 24 compliant
6.58”
PIR Sensor
• Five-year limited warranty
3.72”
Pa g e 3 8
hubbell-automation.com
40' 20'
IR Minor Motion
IR Major Motion
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared and acoustic thresholds Automatic false-on/false-off corrections
LED Lamp
Red - infrared motion
Timer Timeout
Automatic mode: 8–30 minutes (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24 VDC; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0–1,000 lux) Factory set at 3,000 lux (disable photocell)
Coverage
1,600 square feet
Power Requirements
24VDC, 33 mA (uses UVPP and MP-Series power pack—not included)
Output
24VDC active high-logic control signal with short circuit protection and optional dry contact (see: RP Option)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing – Rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) Color-coded leads are 6” long
Dimensions
6.58”H x 3.63”W x 3.72”D
Weight
5.0 oz
Color Off-white Mounting
Mounting base provided Recommended MAX mounting height: 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information lo model LO
IRWV technology IRWV IRHB
Passive Infrared Wide View Passive Infrared High Bay
Relay / Photocell option RP Relay Photocell Blank No Relay Photocell
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI QTI Blank
Quick to Install No QTI
Pa g e 3 9
LightOWLTM Dual Technology Passive Infrared and Acoustic Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
CEILING AND WALL MOUNT OCCUPANCY SENSORS
24 VDC
VOLTAGE
r
The LightOWLTM Dual Technology Passive Infrared and Acoustic Sensor combines passive infrared (PIR) and acoustic (sound-activated) technologies to turn lighting on and off based on occupancy. This sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
LODIA
PRODUCT FEATURES OCCUPANCY SENSING
•
IntelliDAPT
IntelliDAPT self-adaptive technology—no manual adjustment required 3.63”
• All-digital dual technology (passive infrared [PIR] and acoustic) sensor • Non-volatile memory for sensor settings • 1,600 square-foot coverage area
High Impact Plastic Casing
• Optional relay and photocell control • Optional Quick-to-Install (QTI) connector • UL and cUL listed • California Title 24 compliant
6.58”
PIR Sensor
• Five-year limited warranty
Acoustic Located Behind Cover 3.72”
Pa g e 4 0
hubbell-automation.com
40' 32' 23'
20'
23' 32' US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared and acoustic thresholds Automatic false-on/false-off corrections
LED Lamp
Red—infrared motion Green—acoustic detection
Timer Timeout
Automatic mode: 8–30 minutes (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
RP Option
Relay and photocell included Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24VDC; three-wire isolated relay Photocell: adjustable natural-light override ranges from 0 to 100 foot-candles (0–1,000 lux)
Coverage
1,600 square feet
Power Requirements
24VDC, 33 mA (uses UVPP and MP-Series power pack—not included)
Output
24VDC active high-logic control signal with short circuit protection and optional dry contact (see: RP Option)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction
Casing – Rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors Color-coded leads are 6” long
Dimensions
6.58”H x 3.63”W x 3.72”D
Weight
5.0 oz
Color Off-white Mounting
Mounting base provided Recommended MAX mounting height: 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information LO model LO
DIA technology DIA Passive Infrared and Acoustic
Relay / Photocell option RP Relay Photocell Blank No Relay Photocell
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
QTI Blank
QTI Quick to Install No QTI
Pa g e 41
Manual On/ Auto OFF Passive Infrared Wall Switch Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
120 277 VAC
The IWSZPM is a Title 24 compliant, manual-on, passive infrared (PIR) wall switch vacancy sensor that provides excellent energy savings and reliable motion detection. The sensor’s low-profile casing design provides the perfect wall switch for residential areas, such as bathrooms, garages, laundry rooms and utility rooms. The IWSZPM’s manual-on/automatic-off operation meets Title 24 guidelines for residential lighting, which requires a person to manually turn on lighting and the sensor to automatically turn off lighting during vacancy.
IWSZPM
PRODUCT FEATURES •
Zero Arc Point Switching
•
No minimum load requirement
•
Adjustable time delay and sensitivity
•
Walk test indicator
•
Dual 120/277VAC operation
•
UL and cUL listed
•
Title 24 compliant
•
Five-year limited warranty
OCCUPANCY SENSING
2.75”
PIR Sensor 4.5”
Manual On Button
1.65”
Pa g e 4 2
hubbell-automation.com
Line Black 35' (10.8m)
Black
Ground (Green)
Ground (Green)
Red
16' (4.9m)
4.0' (1.2m)
Red Load
15ϒ 15ϒ
floor
Neutral
35' (10.8m)
General Specifications Timer Timeout
Fully adjustable from 30 seconds to 30 minutes
Sensitivity
Fully adjustable from 20% to 100%
Passive Infrared
Multi-segment IR Fresnel lens
Coverage
900 sq. ft., 180 degrees
Power Requirements
120 or 277VAC, 60 Hz
Electrical Ratings
120VAC: 800W Incandescent, 1000W Fluorescent, 1/6 HP
277VAC: 1800W Fluorescent, 1/6 HP
Load Requirements
No minimum load
Operating Environment
Indoor use only Operating temperature: 32o to 122o F (0o to 50o C) 0% to 95% relative humidity, non-condensing
Construction
Housing – high-impact, injection-molded plastic Color-coded leads are 6” long
Dimensions
4.5”H x 2.75”W x 1.625”D
Weight
2.9 oz
Color
White, Ivory
Mounting
Single gang NEMA style switch box, decorator style wall plate included
Certifications
UL and cUL Listed
Warranty
Five-year limited
Ordering Information IWSZP model IWSZP
m
M
control Manual On/Auto Off
W I
color White Ivory
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 4 3
Automatic Passive Infrared Wall Switch Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WALL SWITCH OCCUPANCY SENSORS
120 277 VAC
The IWSZP3P is an automatic passive infrared wall switch occupancy sensor that provides excellent energy savings as well as reliable motion detection. The sensor's low profile housing design provides the perfect wall switch for applications including private offices, conference rooms, break rooms, lounges and storage areas. When a person enters the sensor’s field of view, the IWSZP3P will automatically switch “ON” available lighting. The sensor will automatcially switch OFF lighting after a specific time period of no occupancy.
IWSZP3P
PRODUCT FEATURES •
Zero Arc Point Switching
•
No minimum load requirement
•
Adjustable time delay and sensitivity
•
Built-in photocell
•
Walk test indicator
•
Dual 120/277VAC operation
•
UL and cUL listed
•
Five-year limited warranty
OCCUPANCY SENSING
2.75”
PIR Sensor 4.5”
1.65”
Pa g e 4 4
hubbell-automation.com
Line Black 35' (10.8m)
Black
Ground (Green)
Ground (Green)
Red
16' (4.9m)
4.0' (1.2m)
Red Load
15ϒ 15ϒ
floor
Neutral
35' (10.8m)
General Specifications Timer Timeout
Fully adjustable from 30 seconds to 30 minutes
Sensitivity
Fully adjustable from 20% to 100%
Passive Infrared
Multi-segment IR Fresnel lens
Photocell
Adjustable ambient light override ranges from approximately 5 foot-candles (50 lux) to 200 foot-candles (2000 lux)
Coverage
900 sq. ft., 180 degrees
Power Requirements
120 or 277VAC, 60 Hz
Electrical Ratings
120VAC: 800W Incandescent, 1000W Fluorescent, 1/6 HP
277VAC: 1800W Fluorescent, 1/6 HP
Load Requirements
No minimum load
Operating environment
Indoor use only Operating temperature: 32o to 122o F (0o to 50o C) 0% to 95% relative humidity, non-condensing
Construction
Housing – high-impact, injection-molded plastic Color-coded leads are 6” long
Dimensions
4.5”H x 2.75”W x 1.625”D
Weight
2.9 oz
Color
White, Ivory
Mounting
Single gang NEMA style switch box, decorator style wall plate included
Certifications
UL and cUL Listed
Warranty
Five-year limited
Ordering Information IWSZP model IWSZP
3P control 3P Auto On/Auto Off
W I
color White Ivory
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 4 5
Digital Programmable Timer
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Power Packs and Relays
120 277 VAC
With its aesthetically pleasing features, the TD300 combines style with functionality as it provides energy saving control of incandescent, LED and fluorescent lighting, as well as certain motor loads such as fans, hot tub heaters and circulating pumps.
The timer offers two presets for energy code compliance – two hour timing for Title 24 and IECC and 4 hour timing for ASHRAE 90.1. A timed override allows lights and HVAC (heating, ventilating and air conditioning) to remain on for a specified amount of time for after-hours cleaning crews. The TD300 is easy to install and can replace any wall switch.
TD300
PRODUCT FEATURES •
Supports multiple timer intervals
•
Energy code presets for Title 24, IECC, and ASHRAE 90.1
•
Visual and audible turnoff warning
•
3 Way and Multiple Way Switching
•
No Neutral Required
•
No Load Requirement
•
Dip switch control of features
•
Zero Arc Point Switching
•
UL and cUL listed
•
Five-year limited warranty
2.75”
Display
4.5” Manual On Button
1.65”
Pa g e 4 6
hubbell-automation.com
General Specifications Power Requirements
120/230/277VAC; 50/60Hz
Electrical Ratings 120VAC - 15A Resistive - 10A Ballast - 1200W LED Lamp Driver - 8A Tungsten - 1/4HP Motor - 360VA Pilot Duty 277VAC - 15A Resistive - 15A Resistive - 10A Ballast Load Requirements
None
Operating Environment
Indoor use only Operating environment: 32° - 122°F (0°-50°C) Relative humidity (non-condensing): 0%-95%
Construction
Casing – high impact injection-molded plastic Wall plate locks access to DIP switches for tamper resistance
Display
Backlit LED
Dimensions
4.5”H x 2.75”W x 1.625”D
Weight
2.9 oz
Color White Mounting
Single-gang NEMA-style switch box (average switch box) Decorator wall plate sold separately
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information W
TD300 model TD300
W
control White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 47
Low Voltage Switches
TITLE
COMPLIANT
CALIFORNIA
LVS SERIES
LOW
24 24 CEC
VDC
VOLTAGE
Hubbell Building Automation’s Low Voltage Wall Switches are designed for virtually any indoor area. The soft contours of its architecturally pleasing design fit easily into any décor. Switches are available in both momentary or latching versions and feature multiple button configurations making them the perfect switch solution for use with HBA’s Lighting Control Panels.
LVSM1NP
LVSM1PL
PRODUCT FEATURES • Attractive, architecturally pleasing design
• Mounts to standard single-gang box
• Momentary or latching versions available
• Title 24 compliant when used as part of compliant system
• 1-4 buttons with or without LED
• Five-year limited warranty
General Specifications Electrical Ratings
Each switch: 100mA @ 30VDC Max Each pilot LED: 18-30VDC, internal 2.2kohm, ½ Watt resistor
Configurations
1 - 4 buttons, with or without pilot LED Momentary or latching (sustained)
Operating Environment
Indoor use only Operating temperature: 32° to 122°F (0° to 50°C) Relative humidity (non-condensing): 10% to 90%
Construction
Housing – Rugged, high-impact, injection-molded plastic Color-coded leads
Dimensions
1.88”W x 4.25”H x 1.56”D
Weight
3.0 oz
Color
White, Ivory, Light Almond, Gray
Mounting
Single-gang NEMA-style switch box (average switch box) Decorator-style wall plate not included
Warranty
Five-year limited
Ordering Information LVS Sensor model LVS
Pa g e 4 8
SENSOR type M Momentary L Latching
NUMBER OF BUTTONs 1 2 3 4
pilot PL w/ Pilot LEDS NP No Pilot
color WH White IV Ivory LA Light Almond G Gray
hubbell-automation.com
HBA Tracker Occupancy and Light Level Data Logger
The Hubbell Building Automation (HBA) Tracker is an occupancy and light level data logger that records room occupancy, lighting, and daylight patterns for easy verification of potential savings by installing HBA occupancy sensors and daylight harvesting products. The HBA Tracker’s robust reporting tools take the guesswork out of energy audits. Data is collected once per minute to ensure accurate payback analysis. Smart software averages similar area types for full building analysis. The light weight sensor easily mounts via strong magnet for easy set-up. The unit connects to a PC via included USB cord. The intuitive software includes a variety of reports customizable to the space. LL-200
PRODUCT FEATURES • Digital passive infrared (PIR) sensor with daylight sensor
• PC based software included
• No wiring required
• Windows XP / Windows 7
• Reusable magnetic mounting
• User set inputs for accurate reporting
• User replaceable 9V battery
• Downloadable reports available in PDF and CVS File versions
• Easily connects to computer (PC) via USB Cable
• Five-year warranty
General Specifications Power Requirements
Powered by 9 Volt battery (included)
Passive Infrared
Dual element pyrometer and spherical Fresnel lens
Daylight Sensor
Range: 30 – 2500FC
Operating Environment
Indoor use only; Operating temperature: 32° to 149°F (0° to 65°C)
Dimensions
4.0”DIA x 1.5”H
Weight
7 oz.
Relative humidity (non-condensing):
0% to 95%
Warranty
Five-year limited
Ordering Information LL-200 LL-200
model Tracker and Occupancy and Light Level Data Logger
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 4 9
Universal Voltage Power Packs
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Power Packs and Relays
LOW
24 VDC
VOLTAGE
The Universal Voltage Power Pack (UVPP) is a self-contained transformer and relay designed for low-voltage 24VDC occupancy sensors. The power pack supports and automatically detects the line-voltage input within the 100–277VAC range. This eliminates the need for voltage-specific power packs. The Universal Voltage Power Pack with Manual ON/OFF control (UVPPM) provides a unique solution for lighting applications where users require both manual ON/OFF control as well as automatic OFF control. Both power packs are capable of switching 20A loads and feature Zero Arc Point Switching, minimizing relay-contact wear from high inrush loads. A single power pack can power either 4 sensors or 3 sensors and the MPSA auxiliary relay for multiple circuits. The power packs are plenum rated and easily mount inside or outside of a junction box or inside a fixture. UVPP
PRODUCT FEATURES 2.33”
• Universal voltage: 100–277VAC; 50/60Hz • Automatic voltage detection • Electrical load switching capability: maximum of 20 Amps • Regulated 24VDC current; 150mA output •
Zero Arc Point Switching
• Plenum rated • Mounts: inside or outside a junction box; inside a fixture • Available with exclusive Quick-to-Install (QTI) connector
3.69”
• Companion auxiliary relay device available (MPSA) • UL and cUL listed • Five-year limited warranty
1.36” UVPPM
Pa g e 5 0
hubbell-automation.com
UVPP Wiring Diagram
UVPPM Wiring Diagram
and is powered by 24VDC supplied by UVPP or UVPPM
General Specification Power Requirements
100–277VAC; 50/60Hz
Output (UVPP/UPPM)
24VDC; 150mA nominal, isolated, and regulated
Relay Contact Rating
20A: 120VAC Incandescent 20A: 120 or 277VAC Ballast 1HP: 120 or 277VAC Motor Load
Plenum Rated
Complies with requirements for use in a plenum area Plenum rated for external junction box mounting
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Dimensions
3.69”L x 2.33”W x 1.36”D
Weight
15 oz.
Color Black Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
model uvpp uvppqti MPSA UVPPM
Universal Voltage Power Pack Universal Voltage Power Pack with QTI Connector Auxiliary Relay Device Universal Voltage Power Pack with Manual ON/OFF Control
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 51
MP347A Power Pack
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Power Packs and Relays
347 VAC
The MP347A is a self-contained transformer and relay (an ON/OFF switch controlled by a circuit) designed for low-voltage 24VDC occupancy sensors. This power pack is capable of switching 15A loads and feature Zero Arc Point Switching, minimizing relay-contact wear from high inrush loads. A single power pack can power either 3 sensors or 2 sensors and the MPSA auxiliary relay for multiple circuits. The power packs are plenum rated and easily mount inside or outside of a junction box or inside a fluorescent ballast cavity.
MP347A
PRODUCT FEATURES • Plenum rated
2.33”
• Self-contained transformer and relay • 347VAC, 60Hz • Regulated 24 VDC current; 100 mA output • Easily mounts inside or outside a junction box • Optional Quick To Install (QTI) connector • Companion auxiliary relay device available • UL and cUL listed
3.69”
• Five-year limited warranty
1.36”
Pa g e 5 2
hubbell-automation.com
General Specifications Power Requirements
347VAC @ 60Hz
Output
24VDC; 100 mA nominal, full-wave rectified, and filtered
Relay Contact Rating
15A: 347VAC Incandescent
15A: 347VAC Ballast
Construction
High-impact UL 94-5V plastic
Plenum Rated
Complies with requirements for use in a plenum area Plenum rated for external junction box mounting
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Dimensions
3.69”L x 2.33”W x 1.36”D
Weight
15 oz.
Color Black Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
model MP347A MPSA
347VAC Power Pack Auxiliary Relay Device
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 5 3
Line Voltage Auxiliary Relays Power Packs and Relays
120 277 VAC
Hubbell Building Automation’s Enclosed 10 Amp SPDT Relays from Functional Devices, Inc. provide an isolated N.O. / N.C. contact that can be used to integrate low voltage sensors to other building automation systems. The coil contained in these relays can be powered by more than one voltage. An externally visible LED indicates the status of the coil of the relay.
RRISPDTC
General Specifications
Pa g e 5 4
# Relays & Contact Type
One (1) SPDT Continuous Duty Coil
Expected Relay Life
10 million cycles minimum mechanical
Gold Flash
Yes
Contact Ratings
10 Amp resistive @ 120-277VAC
10 Amp resistive @ 28VDC
480 VA Pilot Duty @ 240-277VAC
480 VA Ballast @ 277VAC
600 Watt Tungsten @ 120VAC N/O
240 Watt Tungsten @ 120VAC N.C.
1/3 HP for N/O @ 120-240VAC
1/6 HP for N/O @ 120-240VAC
1/4 HP for N/O @ 277VAC
1/8 HP for N/C @ 277VAC
Coil Current
30 mA @ 10VAC
12 mA @ 10VDC
32 mA @ 12VAC
14 mA @ 12VDC
42 mA @ 24VAC
16 mA @ 24VDC
50 mA @ 30VAC
18 mA @ 30VDC
25 mA @ 120VAC
Coil Voltage Input
RR1SPDTC120: 10-30VAC/DC, 120VAC; 50-60Hz
RR1SPDTC277: 10-30VAC/DC, 208-277VAC; 50-60Hz
Operating Environment
-30° to 140°F
Housing Rating
Plenum, NEMA 1
Wires
16”, 600V Rated
Certifications
UL and cUL Listed, UL916, UL864
Warranty
Five-year limited
hubbell-automation.com
Ordering Information
model RR1SPDTC120 RR1SPDTC277
Enclosed Relay 10 Amp SPDT with 10-30VAC/DC/120VAC Coil Enclosed Relay 10 Amp SPDT with 10-30VAC/DC/208-277VAC Coil
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 5 5
Line Voltage Auxiliary Relays Power Packs and Relays
120 277 VAC
Hubbell Building Automation’s remote relay units (RRU) are used to switch additional lighting or other control circuits. Designed to work with line voltage sensors, the RRU provides 20 amp switching capacity and features a Normally Open (N/O) isolated contact.
RRU
PRODUCT FEATURES • 120 or 277VAC models available • 20 Amp switching capacity • N.O. isolated contact • UL and cUL listed • Five-year warranty
General Specifications Electrical Ratings
RRU120 – 2400 watts @ 120VAC 50/60 Hz, 1 HP RRU277 – 5000 watts @ 277VAC 50/60 Hz, 1.5 HP
Operating Environment
Indoor use only
Dimensions Weight
2.75”W x 4.5”L x 1.10”D 3.0 oz.
Color White Certifications
UL and cUL Listed
Warranty
Five years
Ordering Information
model rru120 rru277
Pa g e 5 6
Auxiliary Relay for 120V Line Voltage Sensors Auxiliary Relay for 277V Line Voltage Sensors
hubbell-automation.com
Ceiling and Wall Mount Occupancy Sensor Accessories Sensor accessories ACAK (Shown with LightOWL mounting arm.) ACAK — Acoustic Ceiling Mounting Kit For ceiling and wall mount sensors used with acoustic ceiling tile. ACAK uses integral cutting teeth for quicker installation. Color: White. LMRA — LightOWL Mud Ring ADAPTER A LightOWL goof ring for covering oversized holes. Color: White. LMRA OPE – OMNI Protective Enclosure The OPE is a NEMA Type 4X enclosure specifically designed for use with HBA’s OMNIIR ceiling mount occupancy sensor. Designed to provide protection from foreign materials and water, the enclosure is acceptable for use in a variety of environments including applications in OPE
the pharmaceutical and food pre-paration industries. Size: 6.5”DIA, 2”H Color: White. HCRA — Hard Ceiling Raceway Adapter For OMNI™ sensors.
The HCRA is compatible with Hubbell™ and
Wiremold™ raceway. The HCRA has knockout raceway holes for quick and clean installation. Color: White. WGWS – Wall mount wire guard for wall switches,
HCRA
6.25”H x 4.0”W x 2.25”D WGOMNI – Ceiling mount guard for OMNI sensors, 7.0”W x 3.25”D (circular guard) Wire guards are heavy-duty coated wire guards for sensors to protect from destructive strikes. Mounting clips are included. Color: White. WGLO – Wall mount wire guard for LightOWL sensors, 7.0”H x 5.75”W x 4.5”D
Ordering Information
ACAK LMRA
color Acoustic Ceiling Mount Kit LightOWL Mud Ring Adapter
HCRA
Hard Ceiling Adapter
OPE
Omni Protective Enclosure
WGWS
Wire Guard for Wall Switches
WGLO
Wire Guard for LightOWL sensors
WGOMNI
WGWS
WGOMNI
WGLO
Wire Guard for Omni Sensors
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 5 7
Occupancy Sensors for High Mount and Outdoor Use
Reduce energy consumption, maximize illumination performance, and meet optimal operating costs and lighting code standards with HUbbell Building Automation’s WASP2 and Dimming WASP. HBA’s WASP Occupancy/ Motion sensors takes the sting out of meeting energy codes while maximizing the energy savings available from LED lighting. WASP sensors provide occupancy sensing and daylight harvesting for indoor and outdoor lighting applications. Depending on the WASP2 or Dimming WASP model chosen, sensors may be configured to turn lights off or go to preset dimmed settings to provide optimal safety and security while still providing energy savings for the user. The WASP sensors are ideal for a variety of applications such as parking garages, area/site lighting, pathways, warehouses, storage areas, stairwells and more.
Occupancy Sensing
Flexibility
The HBA WASP2 and Dimming WASP are intelligent Passive Infrared
The WASP2 and Dimming WASP support mounting heights from 18
(PIR) occupancy sensors. The occupancy sensing feature maximizes
to 45 feet and feature multiple outputs and mounting options for
energy savings by respectively allowing for smart switching or
versatility. The sensor is available in one-relay, two relay, 24VDC,
dimming depending on code or application requirements.
120/277/347VAC, 208/240VAC, 480VAC, and low voltage versions. Surface and end-mount versions increase installation flexibility.
COMPLIANCE These specialty sensors meet the latest energy efficiency codes and
LENS OPTIONS
standards, including ASHRAE/IESNA 90.1 and CEC’s Title 24, and can
The WASP2 and Dimming WASP lines also offers different lenses
provide LEED (Leadership in Energy and Environmental Design) points
with versatile masking options providing customized coverage for
in categories including Sustainable Sites, Energy and Atmosphere,
your space. These options include: High Mount, Low Mount, 360°
Indoor Environmental Quality and Innovative Design Process.
Coverage, 180° Coverage, Aisle Patterns, and Half Aisle Patterns.
Daylight Harvesting The WASP2 and Dimming WASP can decrease energy consumption by utilizing daylight harvesting. These sensors have an integral photocell which allows for even more energy savings during daylight hours by turning off lights when there is sufficient natural light.
Pa g e 5 8
hubbell-automation.com
HBA WASP2TM Occupancy Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Specialty Occupancy Sensors and Controllers
RATED
IP 65
WATER-DUST RESISTANT
The HBA WASP2 Indoor/Outdoor Occupancy Sensor is specifically designed for ON/OFF control of high bay fixtures in warehouse, distribution centers and similar facilities. The WASP2 sensor is also available for low mount applications when using the appropriate lens. The sensor is available in end mount and surface mount versions with either single or dual outputs. All WASP2 sensors feature a daylight sensor which can be used to increase energy savings by turning off lights when there is sufficient natural light detected. These sensors also have a unique feature known as Smart Cycling™ which ensures even lamp burn time within multi lamp flourescent fixture. Using the “Smart Cycling” End Mount WASP2 Sensor with lens option
feature, the amount of time each lamp is burned is maintained and kept balanced.
PRODUCT FEATURES
OCCUPANCY SENSING
DAYLIGHT HARVESTING
SMART CYCLING
• Digital Passive Infrared (PIR) sensor • Supported mounting heights: • High mount lens: Up to 30 ft outdoors; 45 ft indoors • Low mount lens: Up to 16 ft indoors/outdoors Interchangeable Lens Options
• Multiple (single and dual) output versions • Unique Smart Cycling™ for improved lamp life • End mount and surface mount versions • Interchangeable high/low area detection lens options
High Impact Plastic Design
1.5”
• Low voltage and line voltage models available • Daylight sensor for daylight harvesting applications • Low temperature/water-tight/indoor-outdoor versions • IP65 Rated version available • UL and cUL listed
4.0”
• Five-year limited warranty
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 5 9
Sensor Lens Coverage and Detection Patterns When Mounted at 8ft with Low Mount Lens
Sensor Lens Coverage and Detection Patterns When Mounted at 30ft and 45ft with Standard Lens
General Specifications Power Requirements
Line Voltage sensors: 120/277/347VAC, 208/240VAC, 480VAC, 60 Hz Low Voltage sensors: 24VDC (uses UVPP or MP-Series power pack – not included)
Load Ratings (Line Voltage Sensors)
120VAC: 0-800W ballast or 0-600W tungsten, 60Hz 277VAC: 0-1200W ballast 347VAC: 0-1500W ballast 208/240VAC: 0-1200W ballast 480VAC: 0-2400W ballast ¼ HP motor load @ 120VAC, 1/6HP @ 347VAC
Output (Low Voltage Sensors)
24VDC active high-logic control signal Relay: N/O + N/C contacts; 500mA rated @ 24VDC; three wire isolated relay
User Interface
(1) Twelve pin DIP switch
Timer Timeouts
Primary: 8-second test mode - 4, 8, 16 and 30 minute timeouts Secondary: Can be disabled (switches off with primary timer) - 30, 60 and 90 minute timeouts
Passive Infrared
Dual element pyrometer and spherical Fresnel lens designed for robust detection of a walking person.
(When used with program start ballast, a 1-2 second delay from occupancy detection to lamp turn-on may be experienced.)
Daylight Sensor
Range: 30 – 2500FC End mount sensor: Downward and upward looking daylight sensors (Direction selectable via DIP switch) Surface mount sensor: Downward looking daylight sensor only
Interchangeable Lens Options
Lens options: (Lenses sold separately – not included with sensor module) Low Mount/High Mount Indoor/Outdoor Coverage: 360°, 180°, Aisle, Half Aisle
Operating Environment
Standard version: Indoor use only; Operating temperature: 32° to 149°F (0° to 65°C); Relative humidity (non-condensing): 0% to 95% Low-temperature/Water-tight/Indoor-Outdoor version: Operating temperature: -40° to 149°F (-40° to 65°C)
Construction
Sensor Module and Lens Assembly – high impact, injection-molded plastic
Dimensions Weight
4.0”DIA, 1.5”H 7 oz.
Color
White, Black and Gray
Mounting
End mount sensor: Mounts directly to end of fixture through extended ½” chase nipple For deeper body fixtures, an optional Extender Adapter (available separately) positions the sensor flush or below the bottom of the reflector for a full field-of-view. Surface mount sensor: Mounts directly to fixture or j-box via (2) 1.25” stainless steel screws and locking nuts
Certifications
Conforms to UL STD 508, UL STD 244A Conforms to IP65 (Low-temperature/Water-tight version)
Warranty
Five-year limited
Pa g e 6 0
hubbell-automation.com
120/277/347VAC WASP2 Wiring Diagram
208/240 & 480VAC WASP2 Wiring Diagram
24V WASP2 Wiring Diagram
Ordering Information WSP SENSOR model
WSP
EM SM
MOUNTING End Mount Surface Mount
INPUT VOLTAGE 24V 24VDC (Low Voltage) UNV 120/277/347VAC UNV2R 120/277/347VAC (2 Outputs) 208 208/240VAC 480 480VAC
Blank LWO
LOW-TEMP/ Water Tight Standard Version Low-Temp/Water Tight/ Indoor/Outdoor
Blank BK GY
color White Black Gray
Example: WSP EM UNV LWO – Wasp End Mount Sensor, 120-347VAC, Low Temp/Water Tight, White
For available lens options and ordering information, reference the WASP2 Occupancy Sensor Lens Specification Sheet. Accessory The Optional WSPADAPTOR2 offset adaptor can be used to improve the field of view for fixture mounted sensors where the geometry of the fixture might otherwise interfere with the sensor’s performance. The adapter snaps into a standard 1/2” knockout on the end of the fixture and provides several mounting position choices for the sensor.
Ordering Information WSPADAPTOR2 Model WSPADAPTOR2
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 61
HBA Dimming WASPTM
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Occupancy Sensors and Controllers
RATED
IP 65
WATER-DUST RESISTANT
The HBA Dimming WASP Indoor/Outdoor Occupancy Sensor is specifically designed to provide 0-10V (Class 1) control of dimmable fixtures. Easy to use DIP switches allow the user to set unoccupied and occupied dimming levels. The sensor is available in end mount and surface mount versions in both line and low voltage options. Interchangeable twist-on lenses eliminate need for field masking. All Dimming WASP sensors feature a daylight sensor for ON/OFF control of fixtures when there is sufficient natural light. The gasketed design of the enclosure makes it impervious to dust and able to withstand water ingress making it an ideal sensor for outdoor and wet locations including those End Mount Dimming WASP Sensor with lens
with temperatures as low as - 40°F to 149°F (-40°C to 65°C).
PRODUCT FEATURES
OCCUPANCY SENSING
0-10V DIMMING
DAYLIGHT HARVESTING
• Digital Passive Infrared (PIR) sensor • Supported mounting heights: • High mount lens: Up to 30 ft outdoors; 45 ft indoors
Interchangeable Lens Options
• Low mount lens: Up to16 ft indoors/outdoors • Controls 0-10V dimmable ballasts; 0-10V LED drivers • User controlled dimming presets
High Impact Plastic Design
1.5”
• Daylight sensor for daylight harvesting applications • End mount and surface mount versions • Interchangeable high/low area detection lens options • Low voltage and line voltage models available • Low temperature/water-tight/indoor-outdoor versions
4.0”
• Available in White, Black and Gray • IP65 Rated version available • UL and cUL listed • Five-year limited warranty
Pa g e 6 2
hubbell-automation.com
Sensor Lens Coverage and Detection Patterns When Mounted at 30ft and 45ft with Standard Lens
Sensor Lens Coverage and Detection Patterns When Mounted at 8ft with Low Mount Lens
General Specifications Power Requirements
Line Voltage sensors: 120/277/347VAC, 208/240VAC, 480VAC, 50/60Hz
Low Voltage sensors: 24VDC (uses UVPP or MP-series power pack – not included)
Load Ratings
120VAC: 0-800W ballast or 0-600W tungsten, 60Hz
(Line Voltage Sensors)
277VAC: 0-1200W ballast
347VAC: 0-1500W ballast
208/240VAC: 0-1200W ballast
480VAC: 0-2400W ballast
¼ HP motor load @ 120VAC, 1/6 HP @ 347VAC
0-10V Dimming
Capable of sinking up to 30mA
Output (Low Voltage Sensors)
24VDC active high-logic control signal
Relay: N/O + N/C contacts; 500mA rated @ 24VDC
User Interface
Twelve pin DIP switch for initial choice of functionality
Timer Timeouts
8-second test mode – 1, 5, 10 and 15 minute timeouts
Dimming Presets
Unoccupied: 70%, 60%, 50%, 20%
Full Off Timer Delay
Enabled: After 60 minutes in the Unoccupied low level state, sensor will turn lighting off
Disabled: Sensor will maintain low level setting when there is no occupancy
Passive Infrared
Dual element pyrometer and spherical Fresnel lens designed for robust detection of walking person
(When used with program start ballasts, a 1-2 second delay from occupancy detection to lamp turn-on may occur)
Daylight Sensor
Range: 1 to 50FC or 5 to 500FC
End mount sensor: Downward and upward facing daylight sensor (direction selectable via DIP switch)
Surface mount sensor: Downward facing daylight sensor only
Interchangeable Lens Options and Coverage
Lens options: (Lenses sold separately – not included with sensor module)
Low Mount/High Mount
Indoor/Outdoor
Coverage: 360°, 180°, Aisle, Half Aisle
Operating Environment
Indoor/outdoor use
Operating temperature: - 40°F to 149°F (-40°C to 65°C)
Construction
Sensor Module and Lens Assembly: high-impact, injection-molded plastic
Dimensions
4.0”DIA, 1.5”H
Weight
7 oz.
Color
White, Black, Gray
Mounting
End mount sensor: 1/2” chase nipple
Optional extender adapter (available separately)
Surface mount sensor: Mounts directly via (2) 1.25” stainless screws and locking nuts
Certifications
Conforms to UL STD 508, UL STD 244A
Conforms to IP65 ( low-temp, water tight/indoor/outdoor versions)
Warranty
Five-year limited
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 6 3
208/240 & 480VAC Dimming WASP Wiring Diagram
120/277/347VAC Dimming WASP Wiring Diagram
24V Dimming WASP Wiring Diagram
Ordering Information D
WSP SENSOR model
WSP
EM SM
MOUNTING End Mount Surface Mount
24V UNV 208 480
INPUT VOLTAGE 24VDC (Low Voltage) 120/277/347VAC 208/240VAC 480VAC
outdoor rating /LOWTEMP Blank Indoor
Dimming option D 0-10V Dimming
LWO Low-Temp/Water Tight/ Indoor/Outdoor
color Blank White BK Black GY Gray
Example: WSPEMUNVLWO-D-BK – Wasp End Mount Sensor, 120-347VAC, Low Temp/Water Tight, 0-10 Dimming, Black
For available lens options and ordering information, reference the WASP2 Occupancy Sensor Lens Specification Sheet. Accessory The Optional WSPADAPTOR2 offset adaptor can be used to improve the field of view for fixture mounted sensors where the geometry of the fixture might otherwise interfere with the sensor’s performance. The adapter snaps into a standard 1/2” knockout on the end of the fixture and provides several mounting position choices for the sensor.
Ordering Information WSPADAPTOR2 Model WSPADAPTOR2
Pa g e 6 4
hubbell-automation.com
HBA WASP2TM Occupancy Sensor Lens Options
TITLE
24 CEC
COMPLIANT
CALIFORNIA
High Bay Occupancy Sensors and Controllers
RATED
IP 65
WATER-DUST RESISTANT
The HBA WASP2TM and Dimming WASP family of occupancy sensors offers a variety of interchangeable lenses with versatile masking options providing customized coverage for your space. These options include: High Mount, Low Mount, 360째 Coverage, 180째 Coverage, Aisle Patterns, and Half Aisle Patterns.
Ordering Information WSP MODEL
WSP
L360 L180 LH LHA
COVERAGE 360째 Area Lens 180째 Area Lens Aisle Lens Half Aisle Lens
Blank LM
Mounting High Mount Low Mount
Environment Blank LWO
Indoor Low-Temp/Water-Tight/Outdoor
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
WH BK GY
color White Black Gray
Pa g e 6 5
Daylighting Controls
Pa g e 6 6
Let the Sun Be Your Guiding Light
™
HBA introduces the Zone5 Daylight Harvesting System, which combines all three daylighting approaches and controls tailored to the specific and demanding needs of daylight harvesting applications. Daylighting controls like HBA’s Zone5 Harvesting System impact budgets by harnessing the sun’s power to reduce energy consumption. HBA’s solutions for daylighting control include dimming, stepped dimming, and switching systems. Dimming systems continuously adjust light output by signaling dimming ballasts, and stepped dimming offers the advantages of full-range dimming without the expense of dimming ballasts. Lamps are either fully turned off or partially turned off, depending on natural light levels. Switching systems turn lighting OFF or ON in accordance with available natural light. With a lower initial cost than dimming systems, switching systems are most often recommended for warehouses, storage areas, atrium, lobbies and parking facilities, where non-stationary tasks are performed.
Save Money
Intuitive, easy-to-use LCD menu
Cut lighting costs by up to 75%. Master Off and Row Off functions
The two-line LCD interface is intuitive, easy-to-use and interactive.
can contribute to additional energy savings when users turn the
The interface allows users to quickly change system settings or
lights off ahead of the occupancy sensor detecting that the room
monitor system diagnostics in real time.
is empty.
Flexibility Save time
All Zone5 switches can be ganged together to form custom switch
Zone5 controls are plug-and-play, eliminating wiring labor costs.
stations, maximizing flexibility in multi-use rooms. Color-coded plug-and-play jumper cables are available to be ordered
User-friendly programming
separately, making installation effortless.
SD Card interface provides a simple way to commission, log, verify and update the Zone5 system. Control parameters can be copied to the card from one Zone5 Control Module to another, email from specifier or Zone5 PC-based template builder.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax orders ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 67
HBA Zone5 Control Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHT HARVESTING CONTROLS
120 277 VAC
The HBA Zone5 Daylight Harvesting System features specialized controls tailored to the specific and demanding needs of daylight harvesting applications. The HBA Zone5 Control Module (ZCM) is the central controller of the system. It accurately analyzes and interprets signals from Zone5 plug and play components, including occupancy sensors, daylight sensors and low voltage switches to control both General and A/V lighting. The ZCM supports up to 4 zones of lighting that can be individually programmed for either daylight switching, stepped dimming or continuous dimming. A fifth zone for standard ON/OFF control of whiteboard lighting is also supported. The Zone5 Control Module features an intuitive menu driven LCD user interface to program system settings, view system/device status, and perform system diagnostics and testing. The ZCM features an SD card interface that can be used to save system settings and copy them to another controller, cutting down on the time required to commission multiple systems. Each Zone5 input device is equipped Z5-CM
with color coded plug and play connectors which snap into the corresponding port on the ZCM.
PRODUCT FEATURES
DAYLIGHT HARVESTING
•
Supports up to five zones of lighting control
•
Daylight switching, stepped dimming or continuous dimming – per zone for four zones
0-10V DIMMING
Lighting Control Switch Ports
•
Controls both General and A/V lighting
•
Whiteboard lighting control
•
Intuitive menu-driven LCD user interface
•
Seamless integration with Zone5 sensors and lighting control switches
•
SD card interface for saving and loading system settings
•
Event logging
•
Contractor-friendly, color coded plug and play installation
•
UL and cUL listed
•
Five-year warranty
Master/ Row Control Ports 12”
Dimming Control Ports
Occupancy Sensor Ports Daylight Sensor Ports
15”
4”
Pa g e 6 8
hubbell-automation.com
Option Board
Dry Contact Terminal
Terminal Block LCD Display
SD Card Interface General Specifications User Interface Daylight Harvesting Options
2-line LCD display 4 navigational buttons SD Card interface – used for system settings, logging and firmware updates For each zone Switched Stepped dimming Full range dimming None (Not Daylight Harvested)
Color Coded Low Voltage Ports
Uses standard RJ45 connectors Plenum rated, low voltage system cabling (sold separately) Blue – lighting control Yellow – master and row control Orange - 0-10V dimming White – occupancy sensor Green – daylight sensor
Demand Response
Dry contact input
Electrical
Each Zone (1-4) 1 relay: general lighting 1 relay: A/V lighting Dimming: 0-10V, capable of controlling up to 50 low voltage, 2-wire, 0-10V dimming ballasts Additional relay for whiteboard lighting Switched output per relay 15A tungsten (120v only,) 20A magnetic ballast, 16A electronic ballast Maximum combined output not to exceed 20A
Dimension
4”W x 12”H x 15”D
Weight
20.75 lbs
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
Z5-CM
Z5-CM
Model Zone5 Control Module
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 6 9
HBA Zone5 Ceiling and Wall Mount Occupancy Sensors
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
DAYLIGHT HARVESTING CONTROLS
24 VDC
VOLTAGE
The HBA Zone5 Ceiling Mount and Wall Mount Occupancy Sensors combine ultrasonic (US) and passive infrared (PIR) technologies to turn lighting on and PIR Sensor
off based on occupancy. This dual technology provides accurate turn-ons while virtually eliminating false-offs.
Ultrasonic Sensors
These sensors feature Hubbell Building Automation’s patented IntelliDAPT® technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors
1.5” 4.5”
with IntelliDAPT provide a maintenance-free install-and-forget operation.
Z5-OS-OMDT2000RP
PRODUCT FEATURES
OCCUPANCY SENSING
•
Occupancy Sensors for Zone5 Daylight Harvesting System
•
IntelliDAPT self-adaptive technology – no manual adjustment required
•
All-digital dual technology (ultrasonic [US] and passive infrared [PIR]) sensors
•
Non-volatile memory for sensor settings
•
1,600 and 2,000 square-foot coverage area
•
Form C relay with N/O + N/C outputs
•
Color coded, plug and play installation
•
UL and cUL listed
•
Five-year limited warranty
DAYLIGHT HARVESTING
IntelliDAPT
3.63”
PIR Sensor
6.58”
Ultrasonic Sensors
3.72”
Z5-OS-LODTRP
Pa g e 7 0
hubbell-automation.com
32' 23'
22'
40'
32' 23'
20'
20' 23' 32'
12' 23' 32'
US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
40'
32' 23'
20'
32' 23'
23' 32' 45' 64' US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
Z5-OS-OMNIDT2000RP Range Diagram
US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
Z5-OS-LODTRP Range Diagrams
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting ultrasonic and passive infrared thresholds Automatic false-on/ false-off corrections
LED Lamp
Red – infrared motion Green – ultrasonic motion
Timer Timeout
Automatic mode: 8 – 30 min. (self adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Ultrasonic (US) Output
Operating frequency: 32 kHz
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
Form C Relay
Relay: N/O + N/C contacts; SPDT; 500 mA rated @ 24VDC; three-wire isolated relay
Coverage
Ceiling mount sensor: 2,000 square feet Wall mount sensor: 1,600 square feet
Power Requirements
24VDC, 33mA Power and 24VDC active high-logic output control signal provided through plenum rated CAT5 plug-and-play cable (ordered separately)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 5%
Construction
Casing – rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UV-945VA) flame class rating, UV inhibitors
OMDT2000RP Dimensions
4.5” diameter, 1.5” height (114 mm diameter, 38mm height)
Weight
5.0 oz (142g)
LODTPRP Dimensions
6.58”H x 3.63”W x 3.72”D
Weight
5.0 oz (142g)
Color Off-white Mounting
Mounting base provided
Recommended mounting height: 8ft with a max mounting height of 12ft.
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
Z5-OS-OMDT2000RP Z5-OS-LODTRP
Model Zone5 Occupancy Sensor, Ceiling Mount, PIR and Ultrasonic, Form C Relay, 2000 Sq. Ft. Zone5 Occupancy Sensor, Wall Mount, PIR and Ultrasonic, Form C Relay, 1600 Sq. Ft. CAT5 Cable Sold Separately
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 71
HBA Zone5 Low Voltage Wall Switches
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
24 VDC
VOLTAGE
The HBA Zone5 Low Voltage Wall Switches provide manual control of the HBA Zone5 Daylight Harvesting System. The Zone5 system consists of two types of switches – Lighting Control Switches and Master/Row Control Switches. The Lighting Control Switches include a General – A/V switch that enables users to switch between General Lighting and Audio Visual Lighting, a General – A/V lighting dimming switch that raises and lowers light levels in both modes, a whiteboard lighting switch that can control up to two independent whiteboard lights, and a Study Time switch that provides uninterrupted lighting during periods of low activity. The Master/Row Control Switches include a Master ON/OFF switch Z5-SW-GAV
Z5-SW-ST
that turns all lighting ON or OFF, and individual Row (1 – 4) ON/OFF switches that control each row of lighting individually. All Zone5 switches are color coded and provide CAT5 plug and play installation to the Zone5 Control Module
PRODUCT FEATURES •
Supports up to 4 zones of lighting control
•
Attractive, architecturally pleasing design
•
General – A/V lighting control with optional dimming control
•
Whiteboard lighting control
•
Master and individual row ON/OFF control
•
Color-coded, plug and play installation
•
All switches mount to standard single or multi-gang wall boxes
•
Multi-gang wall plates available
•
Five-year warranty
1.6”
Fits Standard Decorator Style Wallplate (sold separately)
On/Off Switches
4.2”
1.4” Z5-SW-MC
Pa g e 7 2
hubbell-automation.com
General Specifications Power Requirements
Each switch: 100mA @ 30VDC Max – Provided by Zone5 low voltage color coded plug and play cable (ordered separately) Master/Row control switches: Use with yellow cable Lighting Control Switches: Use with blue cable
Operating Environment
Indoor use only Operating temperature: 32°to 122°F (0° to 50°C) Relative humidity (non-condensing): 10% to 90%
Construction
Housing – Rugged, high-impact, injection-molded plastic
Dimensions
4.2”H x 1.6”E x 1.4”D
Weight
1.6 oz
Color
White
Mounting
Switches may be mounted individually in a single gang switch box or ganged together in a multi-gang switch box NOTE: When ganging multiple switches make sure the switches are of the same color-coded type. Decorator-style wall plates available separately
Warranty
Five-year limited
Ordering Information
LIGHTING CONTROL SWITCHES AND CABLES Z5-SW-GAV Zone5 General - A/V Mode Switch, White Z5-SW-AVD Zone5 General - A/V Dimming Switch, White Z5-SW-ST Zone5 Study Time Switch, White Z5-SW-WB Zone5 Whiteboard Switch, White CAT5-50F-BL Zone5 Cable for Lighting Control Switches, 50ft, Blue CAT5-100F-BL Zone5 Cable for Lighting Control Switches, 100ft, Blue CAT5-3IN-BL Zone5 Jumper Cable for Lighting Control Switches, 3 inches, Blue
MASTER/ROW CONTROL SWITCHES AND CABLES Z5-SW-MC Zone5 Master ON/OFF Switch, White Z5-SW-RCR1 Zone5 Row 1 Control Switch, White Z5-SW-RCR2 Zone5 Row 2 Control Switch, White Z5-SW-RCR3 Zone5 Row 3 Control Switch, White Z5-SW-RCR4 Zone5 Row 4 Control Switch, White CAT5-50F-YL Zone5 Cable for Master/Row Control Switches, 50ft, Yellow CAT5-100F-YL Zone5 Cable for Master/Row Control Switches, 100ft, Yellow CAT5-3IN-YL Zone5 Cable for Master/Row Control Switches, 3 inches, Yellow
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
WALL SWITCH PLATES Z5-WP-1G-WH Zone5 Wall Switch Plate, Decorator Style, 1-gang, White Z5-WP-2G-WH Zone5 Wall Switch Plate, Decorator Style, 2-gang, White Z5-WP-3G-WH Zone5 Wall Switch Plate, Decorator Style, 3-gang, White Z5-WP-4G-WH Zone5 Wall Switch Plate, Decorator Style, 4-gang, White Z5-WP-5G-WH Zone5 Wall Switch Plate, Decorator Style, 5-gang, White
Pa g e 7 3
RJ45 Adapter and CAT5 System Cables DAYLIGHTING CONTROLS
LOW
24 VDC
VOLTAGE
Hubbell Building Automation’s RJ45 Adapter and CAT5 system cables are designed to be used with HBA low voltage occupancy and daylight sensors. The adapter replaces the Quick-To-Install™ (QTI) connectors previously used by the wiHUBB® and Zone5™ occupancy and daylight sensors and enables devices to connect to HBA control modules (e.g. wiHUBB Smart Pack, Zone5 Control Module, etc) using standard CAT5 cable. RJ45Adapter
PRODUCT FEATURES • • •
Supports Zone5 occupancy and daylight sensors Plenum rated Five-year limited warranty
General Specifications Electrical
4 Terminal Connections - Red: +24V - Blue: Occupancy Sensor Input - Yellow: Photocell/Daylight Sensor Input - Black: Common Class 2 device Max Cable Length Supported: 300-ft from device to control module
Plenum Rated
Complies with requirements for use in a plenum area
Construction
Material: SABIC NORYL HS2000X
Dimensions Weight
2.168”L x 1.093”W x 0.995”H 0.8 oz
Color Gray Mounting
Adapter may be mounted using a zip-tie (not included) or with a #8 or #10 mounting screw (not included)
Warranty
Five-year limited
Pa g e 74
hubbell-automation.com
Ordering Information RJ45 Adapter
model/DESCRIPTION RJ45ADAPTER RJ45ADAPTER-10 RJ45ADAPTER-50
RJ45 Adapter for wiHUBB & Zone5 Occupancy and Daylight Sensors RJ45 Adapter for wiHUBB & Zone5 Occupancy and Daylight Sensors - 10 Pack RJ45 Adapter for wiHUBB & Zone5 Occupancy and Daylight Sensors - 50 Pack
CAT5 System Cables
model/DESCRIPTION CAT5-3IN-BL
CAT5 Jumper Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 3in, Blue
CAT5-10F-BL
CAT5 Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 10ft, Blue
CAT5-50F-BL
CAT5 Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 50ft, Blue
CAT5-100F-BL
CAT5 Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 100ft, Blue
CAT5-10F-WH
CAT5 Cable for wiHUBB & Zone5 Occupancy & WASP2 Sensors, Plenum Rated, 10ft, White
CAT5-50F-WH
CAT5 Cable for wiHUBB & Zone5 Occupancy & WASP2 Sensors, Plenum Rated, 50ft, White
CAT5-100F-WH
CAT5 Cable for wiHUBB & Zone5 Occupancy & WASP2 Sensors, Plenum Rated, 100ft, White
CAT5-10F-GN
CAT5 Cable for wiHUBB & Zone5 Daylight Sensors, Plenum Rated, 10ft, Green
CAT5-50F-GN
CAT5 Cable for wiHUBB & Zone5 Daylight Sensors, Plenum Rated, 50ft, Green
CAT5-100F-GN
CAT5 Cable for wiHUBB & Zone5 Daylight Sensors, Plenum Rated, 100ft, Green
CAT5-3IN-YL
CAT5 Jumper Cable for Zone5 Master/Row Control Switches, Plenum Rated, 3in, Yellow
CAT5-50F-YL
CAT5 Cable for Zone5 Master/Row Control Switches, 50ft, Yellow
CAT5-100F-YL
CAT5 Cable for Zone5 Master/Row Control Switches, 100ft, Yellow
Special Notes: 1. When cutting CAT5 cable to specific lengths, the cable pin out is as follows: Pin No. 1 2 3 4 5 6 7 8
Wire Color WHITE with ORANGE STRIPE ORANGE WHITE with GREEN STRIPE BLUE WHITE with BLUE STRIPE GREEN WHITE with BROWN STRIPE BROWN
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 7 5
HBA Zone5 Daylight Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
DAYLIGHT HARVESTING CONTROLS
24 VDC
VOLTAGE
The HBA Zone5 Daylight Sensor provides the necessary daylight-level information to the Zone5 Control Module (ZCM). Using a photodiode element, this sensor continuously measures daylight levels and sends the information to the ZCM for daylight harvesting with lighting in the General (GEN) lighting mode. The daylight sensor supports multiple foot-candle ranges which can be used in normal, skylight or atrium lighting applications.
Z5-DS
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Indoor daylight sensor for Zone5 Daylight Harvesting System • Architecturally attractive design • Open loop operation • Foot-candle range: 3-6,000FC • Mounts vertically or horizontally • Color coded, plug-and-play installation • UL and cUL listed • Five-Year Warranty
General Specifications Electrical
Three jumper-selectable foot-candle ranges: 3-300fc; 30-3,000fc; 60-6,000fc 24VDC Power provided through plenum rated CAT5 plug and play cable (ordered separately)
Construction
Protective hard plastic cover and housing
Dimension
2”DIA, 1.2”H
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information Z5-DS Z5-DS
Pa g e 76
Model Zone5 Daylight Sensor
hubbell-automation.com
ZONE5 System Architecture
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 7 7
Continuous Dimming Control DAYLIGHTING CONTROLS
LOW
24 VDC
VOLTAGE
Hubbell Building Automation’s DLC7 is the ideal system for providing continuous closed loop dimming control for 2-wire 0 -10V dimming ballasts and LED dimmable drivers based on natural daylight. This control maintains constant, undisturbed, light levels during peak use times. Through continuous monitoring of ambient light levels, the DLC7 dims the associated lighting fixtures to a user’s predefined foot-candle setting. The DLC7 dimming photocell provides precise control of the actual amount of lighting on the work surface (e.g. desktop, floor) within its field of view. Measured light levels are converted into a linear, proportional, analog voltage that controls the ballast or LED driver dimming range. This achieves maximum energy savings by efficiently blending natural and artificial light to DLC7
maintain a comfortable visual environment. The sensor head adjustment sets the maximum output of the controlled ballast or LED driver. The sensor also provides a short and long delay. The short delay provides faster sensor response. The long delay slows the sensor response and maintains a more stable signal to the ballast or LED driver, accomodating for brief changes in light due to passing clouds.
PRODUCT FEATURES
DAYLIGHT HARVESTING
0-10V DIMMING
• Controls 2-wire 0 -10V dimming ballasts and LED drivers • Light-sensitivity range of 0–500FC • Selectable 3- or 8-second dimming rate • Multiple calibration options • Low-profile design • Five-year limited warranty
Commisioning Port 1.23”
2.00”
Pa g e 7 8
hubbell-automation.com
General Specifications Accuracy
+/-1% @ 70°F (21°C); Derated to +/-5% when above 120°F or below 50°F (18° to 49°C)
Operating Environment
-13°F to 140°F (-11°C to 60°C)
Sensitivity Ranges
0–500FC
Adjustment Range
10–140FC
Input Voltage
10V (supplied by ballast or LED driver)
Current
Sink up to 25mA
Output Voltage
1V (light) - 10 V (dark)
Wire Leads
22 gauge Gray and violet to the Advance ballast White-green 2-wire loop cut for 10-second delay. Leave intact for 20-second delay to ballast
Sensor Type
Blue enhanced photodiode
Dimensions Weight
Base diameter: 2.00” Sensor diameter: 1.29” Height: 1.23” 1.2 oz.
Mounting
Mounting hole: 3/8” Mounting medium: 3M™ double adhesive tape
Construction
Sensor housing meets flame-retardant requirements of UL standard 94HB
Certifications
ETL/UL 916
Warranty
Five-year limited
Ordering Information dlc7
dlc7
Model Continuous Dimming Control
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 7 9
Daylighting Control Photocell Sensors
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
LOW
24 VDC
VOLTAGE
Correct orientation shown
Hubbell Building Automation’s daylighting control photocell sensors (DLCPCI, DLCPCO, DLCPCA and DLCPCS) provide indoor, outdoor, or skylight control of lighting circuits based on natural daylight. The DLCPC sensors and controller are 2.00”
able to provide coverage for any application. The DLCPC sensors are used in different locations in and around a building. Indoor sensors are used in offices and classrooms. Outdoor sensors detect light for sign and site illumination control. Atrium sensors measure light in lobbies. Skylight sensors read the ambient light 2.00”
available in warehouse skylights.
DLCPCI
Each sensor has a different range and focus of the light being measured. The sensor sensitivity is adjustable. Model measurements ranges include 750, 2,500 2.50”
or 7,500FC. The indoor sensor has a flat Frensal lens that looks downward in a 60-degree cone of referance to measure acutal light on the work surface. The outdoor sensor is enclosed in a weatherproof housing with a visor for shading and
1.75”
lens protection. The Atrium and Skylight sensors both use diffusing dome lenses to provide a 180-degree angle of photodiode reposnse.
DLCPCO
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Multiple sensor options available • Interfaces with Energy Management Systems • Five-year limited warranty
2.75”
1.75”
DLCPCA
Pa g e 8 0
DLCPCS
hubbell-automation.com
General Specifications Accuracy
+/-1% at 70°F (21°C Derated to +/-5% at 120°F or at) F (-18°C to 49°C)
Operating Temperature
13°F to 140°F (-11°C to 60°C)
Sensor Type
Blue-enhanced photo diode
Sensor Ranges
Housing Minimum Adjustable Maximum DLCPCI Indoor 50-750FC DLCPCO Outdoor 50-750FC DLCPCA Atrium 200-2,500FC DLCPCS Skylight 1,000-7,500FC
Input Voltage
24VDC
Output Voltage
10V full output
Output Offset
0VDC or 1VDC - total darkness
Wiring
Three conductors 18-gauge standard cable Red: Pos. DC input Black: DC common Yellow: Output to EMS
Certifications
ETL/UL 916 Listed Title 24 Listed RoHS compliant
Warranty
Five-year limited
Ordering Information
Model DLCPCI DLCPCO DLCPCA DLCPCS
Indoor Photocell Sensor, 50 - 750FC Outdoor Photocell Sensor, 50 - 750FC Atrium Photocell Sensor, 200 - 2500FC Skylight Photocell Sensor, 1000 - 7500FC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 8 1
Photocell Controller
TITLE
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
LOW
24 24 CEC
VDC
VOLTAGE
Hubbell Building Automation’s DLCPCC is the ideal system for providing indoor, outdoor, or skylight control of lighting circuits based on daylight. The DLCPCC lighting controller automatically switches a dry contact in response to changes in natural light levels. The DLCPCC provides a maintained single pole, double throw “Form C” relay output to drive electrically-held contactors or relays, or inputs to Building Automation Systems. The low voltage controller requires a remotely mounted photoconductive (PC) sensor (sold separately). The DLCPCC continuously compares the remote sensor’s signal against the LOW and HIGH light level set points. When the sensor detects decreasing light levels that corresponds with the LOW set point, the lights are switched ON. Conversely, as light levels increase and the sensor’s signal matches the HIGH set point, the lights DLCPCC
are switched OFF. The LOW and HIGH set points are separated by a “deadband.” This prevents the DLCPCC from switching light levels between set points, thus eliminating nuisance or intermittent changes.
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Adjustable on/off set points • Dual power unit input: 24VAC or 24VDC • Flexible control options • Input time delay • Two set points available for separate on and off levels • Five-year limited warranty
4.75”
1.5” 2.5”
Pa g e 8 2
hubbell-automation.com
General Specifications Accuracy
+/- 1 percent at 70°F (21°C) Derated +/- 5 percent above 120°F or below 0°F (49°F / -18°C)
Sensor Type
CD S Photoconductive 2 wire
Power Requirements
24VAC or 24VDC standard
Dead Band
Adjustable: 5-95%
Indicators
Red High and Low LEDs
Input Delay
Standard 30-second sensor (removable for adjustment)
Control Inputs
Photoconductive Sensor Calibration / Simulator (for optional DLCSIMM)
Output
Standard form C SPDT relay 10A resistive
Operating environment
Operating Temp: -13°F to 140°F (-11°C to 60°C) Indoor use only
Construction
Sensor is mounted on a wall switch faceplate
Dimensions
4.75”h x 2.5”w x 1.5”D
Color White Warranty
Five-year limited
Ordering Information DLCPCC Model DLCPCC
Photocell Controller
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 8 3
Luxstat Dimming Control Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
LOW
24 VDC
VOLTAGE
Using a unique Open Loop control algorithm, the Luxstat Dimming Control Module by Servodan provides continuous dimming daylight harvesting control to an area. The lights dim when there is enough daylight, and they brighten when there is not enough daylight. Instead of measuring the light already inside an area, this module measures the amount of daylight entering an area. During installation, lighting levels (without artificial lighting) are measured at task height for each of the 3 zones. The controller adjusts each of the zones independently to maintain the desired lighting levels within each space while taking advantage of available natural daylight. The Luxstat Dimming Control Module is part of a daylight harvesting system that includes the Luxstat Light Sensor and the Luxstat Power Pack. This control module can work with occupancy sensors and manual wall switches to LUXSTATDCM
provide a diverse lighting solution for classrooms and meeting rooms.
PRODUCT FEATURES
DAYLIGHT HARVESTING
•
Open Loop continuous dimming daylight harvesting control
•
Pushbutton programming
•
Automated setup
•
LCD display provides “Real Time” light-level readings
•
5 pre-programmed applications
•
Continuous dimming control—choose from 1, 2, or 3 zones
•
Individual adjustment for each channel of control
•
Compatible with 2-wire 0 - 10V dimming ballast or LED drivers
•
Integration with occupancy sensors and manual override controls
•
DIN rail mounting
•
Title 24 compliant
•
UL and cUL listed
•
Five-year limited warranty
Pa g e 8 4
0-10V DIMMING
2.75”
Display 3.54” Navigation Buttons
2.36”
hubbell-automation.com
General Specifications Electrical
Class 2
Supply Voltage
LUXSTATPP Power Pack: 24 VDC
Operation
Control output voltage to ballasts: 0–10V
Programmable Features
Minimum output setting: 0–4V Maximum output setting: 6–10V Fade and ramp rate: 5–60 seconds Cut off delay: 0–20 minutes or infinity Maximum sink: 50mA per channel Maximum source: 3mA per channel Maximum ballasts: 50 per channel
Dimensions
3.54”H x 2.75”W x 2.36”D
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information LUXSTATDCM model LUXSTATDCM
Luxstat Dimming Control Module, 24V DC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 8 5
Luxstat ON/OFF Control Module
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
24 VDC
VOLTAGE
The Luxstat ON/OFF Control Module by Servodan provides multilevel ON/OFF daylight harvesting control by using a unique Open Loop control algorithm. The lights turn off when there is enough daylight, and they turn on when there is not enough daylight. Instead of measuring the light already inside of an area, this module measures the amount of daylight entering an area. During installation, lighting levels (without artificial lighting) are measured at task height for each of the 3 zones. When daylight is adequate, the controller switches lighting off. When daylight is below the desired level, the control module switches lighting back on. The ON and OFF delays for each channel are individually adjustable. The Luxstat ON/OFF Control Module is part of a daylight harvesting system that includes the Luxstat Light Sensor and the Luxstat Power Pack. The control module can work with occupancy sensors and manual wall switches to provide a diverse lighting solution for classrooms and meeting rooms. LUXSTATOCM
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Open Loop ON/OFF daylight harvesting control • Pushbutton programming with automated setup
2.75”
• LCD display provides “Real Time” light level readings • 5 pre-programmed applications—fit most applications without complicated setup • Multilevel switching—choose from 1, 2, or 3 zones • Individual adjustment for each channel of control • Adjustable ON and OFF delays • Integration with occupancy sensors and manual override controls
Display 3.54”
• DIN rail mounting
Navigation Buttons
• Title 24 compliant • UL and cUL listed
2.36”
• Five-year limited warranty
Pa g e 8 6
hubbell-automation.com
General Specifications Electrical
Class 2
Supply Voltage
LUXSTATPP Power Pack: 24VDC
Programmable Features
Photocell range: 3–6000FC Set point range: 5–60 foot-candles Programmable deadband: 10%–80% Adjustable ON delay: 5–60 seconds Adjustable OFF delay: 3–60 minutes Load shed set point: 5–60FC
Dimensions
3.5”H x 2.8”W x 2.5”D
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information LUXSTATOCM model LUXSTATOCM
Luxstat On/Off Control Module, 24V DC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 8 7
Luxstat Power Pack
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
120 277 VAC
LOW
24 VDC
VOLTAGE
The Luxstat Power Pack by Servodan powers the Luxstat ON/OFF Control Module and the Luxstat Dimming Control Module. It supplies low-voltage power to the control modules via a quick connect cable and has 3 normally open relays (ON/ OFF switches controlled by a circuit) to switch line voltage in response to signals from the connected controller. Additionally, the power pack has an automatically resetting fuse. If the current drawn from the power pack exceeds the specifications, the +24VDC output and the LED will turn off. When the problem and the primary power are removed, the power pack will restore power. LUXSTATPP
PRODUCT FEATURES • Provide power to operate Luxstat daylight harvesting control modules • 3 individually controlled relays for ON/OFF control 2.76”
• 120/230/277VAC transformer • Quick connect to Luxstat daylight harvesting control modules • DIN rail mounting • UL listed • California Title 24 Compliant • Five-year limited warranty
3.57”
2.36”
Pa g e 8 8
hubbell-automation.com
General Specifications Voltage
120/277VAC, 50/60 Hz—single phase
Secondary Power
1,000 mA @ 24VDC
Relays
3 normally open relays (620 A @ 120 or 277VAC)
Dimensions
2.76”W x 3.57”H x 2.36”D
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information LUXSTATPP
LUXSTATPP
Model Luxstat Power Pack for Luxstat Control Modules
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 8 9
Luxstat Single Zone On/Off Control Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
120 277 VAC
The Luxstat Single Zone ON/OFF Control Module by Servodan provides single zone ON/OFF Daylight Harvesting control utilizing a unique Open Loop control algorithm. Instead of measuring the light inside of the space the control module measures the amount of daylight entering the space. During installation, lighting levels, without artificial lighting, are measured at task height for the zone to be controlled. The level is then input into the control module. The photocell measures daylight and transmits this data to the Luxstat Single Zone ON/OFF Control Module. When daylight is adequate, the controller switches lights off. When daylight diminishes below the desired set point, the control module switches lighting back on. The OFF delay for the zone is adjustable. LUXSTATOCM1Z
The Luxstat Single Zone ON/OFF Control Module is part of a Daylight Harvesting system that includes the Luxstat Light Sensor. The control module can also integrate with occupancy sensors and manual control wall switches .
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Open Loop ON/OFF Daylight Harvesting control • Pushbutton programming
2.81”
• LCD display provides Real Time light level readings • 3 to 3000FC Range • Single-zone switching • Adjustable OFF delay Display
• Integration with occupancy sensors and manual override controls • DIN rail mounting
3.54” Navigation Buttons
• UL listed • California Title 24 Compliant • Five-year limited warranty 2.5”
Pa g e 9 0
hubbell-automation.com
General Specifications Electrical (Input)
LUXSTATOCMIZ120: 120VAC LUXSTATOCMIZ277: 277VAC Load: Max 40mA Power Consumption: Approximately 2W Signal from Light Sensor: 0-10V
Electrical (Output) Relay Contact: N/O, 10mA Load: Incandescent Lamps – 1200W Fluorescent – 620VA Halogen Incandescent – 500W Secondary Voltage: 24VDC Performance
FC Range: 0.3 – 30FC; 3-300FC; 30-3000FC Setting Range: 0.3-27FC; 3-270FC; 30-2700FC OFF Delay: 0-60 minutes
Operating Environment
Temperature range: 41°F to 122°F (+5°C to +50°C)
Dimensions
3.54”H x 2.81.”W x 2.5”D
Mounting
DIN Rail
Accessories
IndoorLight Sensor – LUXSTATLS Outdoor Light Sensor - LUXSTATLSO LUXSTAT 1-Button Momentary Switch - LUXSTATSW1WH or LUXSTATSW1IV
Certifications
UL and CE Listed
Warranty
Five-year limited
Ordering Information
LUXSTATOCM1Z120 LUXSTATOCM1Z277
Model Luxstat Single Zone On/Off Control Module 120VAC Luxstat Single Zone On/Off Control Module 277VAC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 9 1
Luxstat Day/Night Control Module with Clock
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
120 277 VAC
The Luxstat Day/Night Control Module by Servodan provides single zone ON/OFF daylight harvesting control utilizing a unique Open Loop control algorithm. In the evening, when daylight diminishes below the desired ON set point, the control module switches lighting on. In the morning, when daylight reaches the desired OFF set point, lighting is switched off. The controller’s integrated clock function switches off lighting completely during a pre-defined period. Switching off lighting during the late evening/early morning means more energy savings. The controller also features pushbutton programming for easy system setup and configuration.
LUXSTATDNCM
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Open Loop ON/OFF daylight harvesting control • Integrated clock for night blocking
1.37”
• Pushbutton programming • DIN rail mounting • UL listed • California Title 24 Compliant • Five-year limited warranty
Display 3.54” Navigation Buttons
2.36”
Pa g e 9 2
hubbell-automation.com
PIR
Lux NPN
0-10V
1
B
2
12
36-080
CC
4
3
45
1
2
3
B
Minilux Control
Lux Lux range on
Off delay Test
AppI n
Out
Mode
Set +
Test
Set -
1
23
D1
23
D
L N
General Specifications Electrical (Input)
LUXSTATDNCM120: 120VAC LUXSTATDNCM277: 277VAC Load: Max 40mA Power Consumption: Approximately 2W Signal from Light Sensor: 0-10V
Electrical (Output) Relay Contact: N/O, m10A Load: Incandescent Lamps – 1200W Fluorescent – 620VA Halogen Incandescent – 500W Secondary Voltage: 24VDC Performance
Fc Range: 0.3 – 30FC Adjustment range for Fc on: 1 – 30FC
Adjustment Range for FC off:
Minimum: 10% of Fc on, but not less than 0.3FC Maximum: 70% of Fc on but not more than 9FC Tolerance of Fc range: +-10% Backup for clock: > 2 hours, when the unit has been connected at least 5 minutes
Operating Environment
Temperature range: 41°F to 122°F (+5°C to +50°C)
Dimensions
3.54”H x 1.37”W x 2.36”D
Mounting
DIN Rail
Accessories
Outdoor Light Sensor – LUXSTATLSO Indoor Light Sensor - LUXSTATLS
Certifications
UL and CE Listed
Warranty
Five-year limited
Ordering Information
LUXSTATDNCM120 LUXSTATDNCM277
Model Luxstat Day/Night Control Module with Clock, 120VAC, DIN Rail Mount Luxstat Day/Night Control Module with Clock, 277VAC, DIN Rail Mount
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 9 3
Luxstat Light Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
24 VDC
VOLTAGE
The Luxstat Light Sensor by Servodan provides the necessary daylight-level information to the Luxstat daylight harvesting control modules. Using a photodiode element, this sensor continuously measures daylight levels and sends the information to the selected Luxstat daylight harvesting control module. In order to operate as a true Open Loop controller, the sensor must be positioned to see only daylight (no artificial light). You select the applicable foot-candle range by using a jumper beneath the front cover.
LUXSTATLS
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Daylight sensor for Luxstat Daylight Harvesting System • Architecturally attractive design • Indoor and outdoor versions • Open loop operation • Foot-candle range: 3-6,000FC • Mounts vertically or horizontally • UL and cUL listed • California Title 24 Compliant • Five-year limited warranty
1.2” 2”
Pa g e 9 4
hubbell-automation.com
Lux
Light sensor
0-10V
1
2
3
45º
Luxstat Control
A B
17 23
45
68
91
01
11
2
30º
A 17 23
78-050
45
68
91
01 11 2
B
30º
Luxstat Control DIM
General Specifications Electrical
Four jumper-selectable foot-candle ranges: .03-30FC; 3-300FC; 30-3,000FC; 60-6,000FC 24VDC Low Voltage Class 2 Device 3-conductor 22 AWG twisted cable—equal to Belden 8443
Construction
Protective hard plastic cover and housing
Dimension
2” diameter x 1.2” height (50.8 diameter x 30.5mm height)
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
LUXSTATLS LUXSTATLSo
Model Luxstat Light Sensor - Indoor Luxstat Light Sensor - Outdoor
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 9 5
Low Voltage Wall Switches for Luxstat
TITLE
24 CEC
COMPLIANT
CALIFORNIA
DAYLIGHTING CONTROLS
LOW
24 VDC
VOLTAGE
Hubbell Building Automation’s Low Voltage Wall Switches for Luxstat provides manual control of the Luxstat Daylight Harvesting Control Modules. The 4-button switch allows occupants to override the automatic daylight control and provides manual ON/OFF and dimming control. The 2-Button Auto/Manual Wall Switch allows occupants to override the automatic daylight control and provides manual ON/OFF control. The 2-Button Dimming Wall Switch provides manual dimming control. The 1-Button Momentary Wall Switch provides manual ON/OFF control.
LUXSTATSW4WH
LUXSTAT2DIM
PRODUCT FEATURES •
Attractive, architecturally pleasing design
•
Multiple button configurations available
•
Manual ON/OFF control
•
Low voltage operation; Class 2 device
•
Mounts to standard single-gang box
•
Five-year warranty
1.6”
Fits Standard Decorator Style Wallplate (sold separately)
Auto Switch
4.2”
Dimming Switches
Manual Switch
1.4”
Pa g e 9 6
hubbell-automation.com
General Specifications Power Requirements
Each switch: 100mA @ 30VDC Max Each pilot LED: 18-30VDC, internal 2.2kohm, ½ Watt resistor
Operating Environment
Indoor use only Operating temperature: 32°to 122°F (0° to 50°C) Relative humidity (non-condensing): 10% to 90%
Construction
Housing – Rugged, high-impact, injection-molded plastic
Dimensions
4.2”H x 1.6” W x 1.4” D
Weight
1.6 oz
Color Mounting
White, Ivory Single gang NEMA-style switch box Decorator-style wall plates available separately
Warranty
Five-year limited
Ordering Information
model LUXSTATSW4 LUXSTATSW2 AUTO LUXSTATSW2 DIM LUXSTAT SW1
Wh iv
color White Ivory
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 9 7
Lighting Control Panels
Pa g e 9 8
hubbell-automation.com
Seamless Networked Lighting
Interior and exterior lighting can account for 40% of all energy costs on a property. Recover as much as 25-50% of that cost in the first six months of implementing HBA’s LX networked lighting control system. LX is a network of expandable and modular relay panels, sensors and switches. Take control of your lighting near or far with its intuitive programming interface, touchscreen tablet and remote access via LAN and Internet. Connect to any point on the topology-free, polarity-insensitive, 2-wire LON communication network with our LonMark® certified architecture. Install sensors and switches “plug-and-play” for endless possibilities in control and savings.
Save Time
Improve the ease of lighting control
LX control panels are simple to install and use. The LX series
•
Unique hand-held touchscreen GUI
utilizes LonMark® certified architecture so sensors and
•
Robust and reliable 20Amp
switches can be installed plug-and-play by connecting to
mechanically-latching relays
any point on the topology-free, polarity-insensitive 2-wire
•
Multiple size enclosures available
communication network.
(4, 8, 16, 32, and 48 relays)
•
Powered, topology-free, polarity-insensitive,
Flexibility
2-wire communication
The LX networked lighting controls use a hand-held
•
LonMark® certified
touchscreen GUI interface that keeps up with the constant
•
Seamless integration with major building
progression of lighting control systems.
protocols, such as LON, BACnet® and
MODBUS® •
Feature-rich scheduling functions
•
365-day time clock
•
Automatic daylight savings time and leap year
compensation •
Built-in astronomical time clock for sunrise and
sunset programming
F a x oorders r d e r s ( 512 ) 4)5 40 5- 00 8- 06 84 6 4| h| u hbubbebl le- al lu- at ou m t iaotni o . cno. cmo m ( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax ( 512 t oam
Pa g e 9 9
LX Lighting Control Panels
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
120 347 VAC
The LX Series Network Lighting Control Panels are the core of the LX system providing programmable switching control of the project’s lighting circuits. Multiple panels are equal peers on the network and can have relays controlled individually or in groups by any input, schedule, preset or Building Automation System.
PRODUCT FEATURES NETWORK
• Unique hand-held touchscreen graphical user interface (GUI) (Order Separately) • Robust and reliable 20 Amp mechanically latching relays • Multiple size enclosures available (4, 8, 16, 32, and 48 relays) • Topology-free, polarity-insensitive, 2-wire communication • LonMark ® certified • Feature-rich scheduling functions • 365-day time clock • Automatic Daylight Savings Time and leap year compensation • Built-in astronomical time clock for sunrise and sunset programming • Five-year limited warranty
Pa g e 10 0
hubbell-automation.com
General Specifications Programming and Configuration
Programmable via the LX Touch Tablet or LX JENEsys™
Physical
NEMA 1 enclosure, surface or recessed Pre-drilled mounting holes for easy mounting either to the uni-strut framing or directly to wall, KO’s provided on top and bottom Removable interior assembly 4, 8, 16, 32, and 48 relay enclosures with hinged locking door
Electrical
120/277/347VAC multi-tap transformer 120, 277, and 347VAC 20 Amp Single Pole Relays
208, 240, and 480VAC 20 Amp Double Pole Relays
Operating Environment
Location: interior space Operating temperature: 0° to 50°C (32° to 112°F) Relative humidity (non-condensing): 10%–90%
Certifications
UL and cUL listed (UL 508, 916 and UL 924) LonMark 3.3 Certified
Warranty
Five-year limited
Ordering Information lxin model LXIN LX Relay Panel Interiors
Relay capacity 4 8 16 32 48
Number of Single Pole Relays 00-48 (Depending on Size)
*NOTE: Number of poles cannot exceed the relay panel size. Example: A LX Series Relay Panel is comprised of 2 separate part numbers, 1 for the interior and 1 for the enclosure — they must be the same size.
lxEn model LXEN LX Relay Panel Enclosure
Number of Double Pole Relays 00-24 (Depending on Size)
size 4 8 16 32 48
trim F Flush S Surface
Example: 32 Relay Interior with 4 Single Pole Relays and 4 Double Pole Relays: LXIN32 04 04 Enclosure to complete specifications - LXEN325
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 10 1
LX Relays LX SERIES NETWORKED LIGHTING CONTROLS
120 347 VAC
480 VAC
LXRL1
The heart of any lighting control system is the relay. With today’s new high in-rush lighting loads and demanding inductive switching requirements, only the most robust relays are capable of keeping up with the demands placed upon them. LX Relays are recognized as the industry’s most robust and reliable relays on the market today. With a 2,000 Amp in-rush current and 14,000 Amp short circuit current, our relays are built to last.
LXRL2
PRODUCT FEATURES NETWORK
•
Robust and reliable mechanically latching relay
•
Suitable for high in-rush loads up to 2,000 Amps
•
14,000 Amp SCCR @277VAC
•
120, 277 & 347VAC Single Pole
•
208, 240 & 480VAC Double Pole
•
Built-in manual override lever & ON/OFF indicator
•
UL Listed
•
Five-year limited warranty
3.75”
0.9” 2.3”
3.75”
1.9”
Pa g e 10 2
hubbell-automation.com
General Specifications Physical
Mechanically-held latching relay Mounts in LX panel to supplied mounting bracket Built-in manual override lever & ON/OFF indicator on each relay Tool-less insertion and removal of relay
Electrical
UL Endurance Test 60k Operations at 20A, 300VAC 14,000 Amp short circuit current @277VAC* 20 Amp Single Pole – 120, 277 & 347VAC 20 Amp Double Pole – 208, 240 & 480VAC ½HP@110-125VAC, 1 ½HP@220-277VAC
Operating Environment
Location: Interior space Operating temperature: 0° to 50°C (32° to 122°F) Relative Humidity: 10% to 90% non-condensing
Dimensions
Single Pole: 3.75”L x 0.9”W x 2.3”D Double Pole: 3.75”L x 1.9”W x 2.3”D
Certifications
UL & cUL Listed (UL 508)
Warranty
Five-year limited
*Applicable to Single Pole Relay only.
Ordering Information
LXRL1
LX Relay, Single Pole, 120/277/347VAC
LXRL2
LX Relay, Double Pole, 120/277/347VAC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 10 3
LXBC Breaker Control Panels
TITLE
24
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
120 277
480
VAC
VAC
The LXBC Breaker Control Panel provides the opportunity to combine controlled and non-controlled loads into a single, fully functional branch circuit panel board. The LXBC integrates seamlessly into the LX Lighting Control Network and can be used as a stand-alone LX control panel or combined in a network with other LX and/or LXBC panels.
NOTE: Touch Screen Graphic User Interface (GUI) not included. Order Separately.
PRODUCT FEATURES NETWORK
20”
• Unique, hand-held touch screen graphical user interface (GUI) (Order Separately) • Robust and reliable 20 and 30 Amp mechanically latching circuit breaker/relays • Multiple size enclosures available (12, 18, 30, and 42 spaces)
Touchscreen Interface
• 100 AMP, 225 AMP or 400 AMP bussing Main Lugs or Main Circuit Breaker • 120/208V, 3PH, 4W or 277/480V, 3PH, 4W • Topology-free, polarity-insensitive, 2-wire communication
Breakers/ Breaker Relays
• LonMark ® certified 57”
• Feature-rich scheduling functions • 365-day time clock • Automatic Daylight Savings Time and leap year compensation • Built-in astronomical time clock for sunrise and sunset programming • Five-year warranty
5.75”
Pa g e 10 4
hubbell-automation.com
General Specifications Programming and Configuration
Programmable via the LX Touch Tablet
Physical
NEMA 1 enclosure, surface or flush mount NEMA 3 enclosure, surface or flush mount KOs provided on top and bottom 12, 18, 30, and 42 space enclosures with hinged locking door
Electrical
120VAC input control voltage at terminal block 15 Amp, 20 Amp and 30 Amp 1-pole and 2-pole Circuit Breaker/Relays Non-Control circuit breakers 15A – 100A, 1,2, and 3-pole 100 AMP, 225 AMP or 400 AMP Lugs Only or Main Circuit Breaker, CU/AL Lugs Bottom Feed only, Top Feed is not available. 120/208V, 3PH, 4W or 277/480V, 3PH, 4W system voltage, 14KAIC @277/480V, 65KAIC Series Rated with main CB
Operating Environment for NEMA 1 Rated Equipment
Location: interior space Operating temperature: 0° to 50° C (32° to 112° F) Relative humidity (non-condensing): 10% to 90%
Certifications
UL listed (UL 916) LonMark 3.3 Certified
Warranty
Five-year limited
Dimensions
D
W
H
400 amp
57"
20"
5.75"
69"
20"
5.75"
Ordering Information LXBC model LXBC LX Breaker Control Panel
B system voltage 1 120/208, 3 Phase, 4 Wire 2 277/480, 3 Phase, 4 Wire
Mains IL 100 Amp Main Lugs Only IC 100 Amp Main Circuit Breaker 2L 225 Amp Main Lugs Only 2C 225 Amp Main Circuit Breaker 4L 400 Amp Main Lugs Only 4C 400 Amp Main Circuit Breaker
H
FEED B Bottom Feed Only (Top Feed is not available)
Relay spaces 12 12 Spaces 18 18 Spaces 30 30 Spaces 42 42 Spaces NOTE: 42 space is available in 225A and 400A main size only.
communications H HBA LX-Lon
enclosure 1S NEMA 1 Surface 1F NEMA 1 Flush 3S NEMA 3 Surface 3F NEMA 3 Flush
Example: Panel, Controlled Circuit Breaker/Relays, and Non-Controlled Breakers must be ordered as separate line items: 1 ea LXBC11CB30H1S 100A Main Circuit Breaker, 120/208V, 3 Phase, 4 wire, 30 Space, NEMA 1 Surface, Bottom Feed, CU/AL Lugs 18 ea LXBR120C – 20A, 1P, Controlled Circuit Breaker/Relays (18 ea) 12 ea LXBR120N – 20A, 1P, Non-Controlled Circuit breakers (12 ea)
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 10 5
LXBR Circuit Relays and Circuit Breakers
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
120 277 VAC
480 VAC
The LXBR Circuit Breaker/Relays and Circuit Breakers are the heart of the LX Breaker Control Panel Series. The use of a combination LXBC Lighting control panel can save space by providing controlled and non-controlled loads in any combination. LXBR Circuit Breaker/Relays communicate seamlessly with the LX Lighting Control System to provide both control and branch circuit protection for the project’s lighting loads.
1-Pole
3-Pole
Non-controlled Circuit Breakers
PRODUCT FEATURES NETWORK
• Robust and reliable 20 and 30 Amp mechanically- latching Circuit Breaker/Relays • Circuit Breaker/Relays are available in 1-pole, 120/277V and 2-pole, 480V • Non-controlled Circuit Breakers are available in 1-pole to 120/277V and 2-pole or 3-pole, 480V • All devices are rated for switching duty (SWD) • 14,000 Amp interrupting capacity (AIC) • Built-in ON/OFF indicator lever • Five-year limited warranty
Controlled Circuit Breaker/Relay 1-Pole shown (2-Pole also available)
Pa g e 10 6
hubbell-automation.com
General Specifications Physical
Mechanically-held latching circuit breaker/relay or non-controlled circuit breaker Mounts in LXBC panel bus with bolt into pre-drilled and tapped hole Built-in ON/OFF indicator lever on each circuit breaker/relay Power to panel must be disconnected for insertion and removal of devices
Electrical
600VAC 20 Amp and 30 Amp Single and Double Pole Circuit Breaker/Relays Non-Control circuit breakers 15A – 100A, 1,2, and 3-pole 14KAIC @277/480V, 65KAIC Series Rated with main CB Circuit Breaker Relays – Maximum duty cycle of 6 Open/Close cycles per minute
Operating Environment for
Location: interior space
NEMA 1 Rated Equipment
Operating temperature: 0° to 50° C (32° to 112° F) Relative humidity (non-condensing): 10% to 90%
Certifications
UL listed (UL 489)
Warranty
Five-year limited
Ordering Information LXBR model LXBR LX Breaker Relay or Breaker
No. Of poles 1 1-Pole 2 2-Pole 3 3-Pole
amp rating 15 15 Amp 20 20 Amp 30 30 Amp 40 40 Amp 50 50 Amp 60 60 Amp 70 70 Amp 90 90 Amp 100 100 Amp
control C Controlled N Non-Controlled NOTE: Controlled Breaker/ Relays are available in 15A, 20A and 30A 1-Pole and 2-Pole ONLY.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 10 7
Touch Tablet Graphical User Interface
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
The LXTB Touch Tablet Graphical User Interface provides easy-to-use intuitive access to the LX System programming. The Tablet allows the user to program the system, view status of devices and relays, and make changes to the system while connected. The LXTB is not required to be connected to the LX System for all functionality to occur, rather it only displays activity such as clock time to the user. The LX system program allows for user access to be define in the tablet, or facility managers can simply control access to the tablet for system security. LXTB
PRODUCT FEATURES NETWORK
• Portable hand-held touch screen
• High-contrast backlit LCD screen
• Graphical user interface (GUI)
• Programmable security codes
• Context-sensitive help
• Five-year limited warranty
• Quarter VGA display (320 x 240 pixels)
General Specifications Programming and Configuration
Device used to program the functionality of other LX lighting control system devices Can program security codes
Physical
Hand-held device Quarter VGA display (320 x 240 pixels)
Electrical
5VDC power—supplied from the LX panel
Operating Environment
Location: interior space Operating temperature: 0° to 50°C (32° to 122°F) Relative humidity (non-condensing): 10% to 90%
Dimensions
7.5”W x 6”H x 1”D
Warranty
Five-year limited
Ordering Information LXTB
model LXTB LX Touch Screen Tablet
Pa g e 10 8
hubbell-automation.com
LX Terminator
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
Hubbell Building Automation’s LX Terminator ensures the correct operation of the LX Series’ free topology (FT), twisted-pair communication networks. On an FT network, each LX Series network segment needs to correctly terminate so that network signals do not reflect back to the segment. The LX Terminator absorbs these network signals and provides a low-cost solution for terminating network segments. The LX Terminator is not required for link power (LP) networks. LXTERMINATOR
PRODUCT FEATURES NETWORK
• LX network segment terminator • DIN Rail Mounting • Five-year limited warranty
General Specifications Network Interface
Screw terminal connector
Operating Environment
32°to 140°F (0° to 60°C)
Relative humidity (non-condensing): 5% to 95%
Warranty
Five-year limited
Ordering Information lxTERMINATOR model LXTERMINATOR LX Free Topology Bus Terminator
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 10 9
LXBASM Building Automation ProtoNode LX SERIES NETWORKED LIGHTING CONTROLS
The Hubbell Building Automation ProtoNode is an external, high performance, low cost Building Automation multi-protocol gateway for providing control and access to Hubbell Building Automation’s LX Network Lighting Control Panel system. The device provides protocol translation between LX systems and BAS/BMS services using BACnet®, Metasys® N2 by JCI, and Modbus. ProtoNode is designed to be used in facilities that need to quickly and easily enable their LX Lighting Control Panels and Devices to interface with other protocols. The ProtoNode device is pre-configured with LX system protocol interface and allows the user to field select BAS system protocols including Modbus RTU, Modbus TCP, BACnet/IP, BACnet MS/TP or JCI Metasys N2OPEN.
PRODUCT FEATURES NETWORK
• Web browser based integration programming 3.25”
• Device is field selectable for specific BAS protocol • Sophisticated user account/password manager • Integrates LX lighting control systems and Building Automation Systems (BAS) • Supports BACnet®, Metasys® N2 by JCI, Modbus™ and LonWorks® protocols • Automatically generates all required control points and documentation for integration with the selected protocol • Five-year limited warranty
4.52”
1.6”
Pa g e 110
hubbell-automation.com
General Specifications Supported Serial (RS-485) Protocols
BACnet MS/TP Modbus RTU
Supported Ethernet Protocols
BACnet IP Modbus TCP/IP JCI Metasys® N2OPEN
Supported Electrical Connections
(1) 6 pin Phoenix Connector (1) RS-485 +/- Ground port Power +/- Frame Ground port (1) Ethernet -10/100 Ethernet port (1) FTT-10 LonWorks® port (LonWorks® Version)
Power Requirements
9-30 VDC or 12-24VAC Current draw @ 12V = 240 mA
Operating Environment
Indoor use only -40°C to 75°C (-40°F to 167°F) Relative humidity (non-condensing): 5% to 90%
Dimensions
4.52”L x 3.25”W x 1.60”H
Approvals
BACnet Testing Labs (BTL) B-ASC LonMark 3.4 Certified TUV approved to UL 916 standard and CSA C22-2 RoHS Compliant OPC Self Certified to Compliance CE Mark
Warranty
Five-year limited
Ordering Information LXBASM LXBASM
Model LX Building Automation Interface, Universal Control with Power Supply
Metasys® is a registered trademark of Johnson Controls, Inc. LonWorks® is a registered trademark of Echelon Corp. BACnet® is a registered trademark of ASHRAE
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 111
LX JENEsysTM
TITLE
24
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
LX JENEsys provides a simple and easy-to-use interface to the LX Networked Lighting Control System via Personal Computer. The LX JENEsys allows any PC with an Internet Explorer compatible browser to interface with the LX JENEsys lighting control system through a built-in web server. The LX JENEsys provides an easy-to-use and highly intuitive graphical user interface (GUI). System users can easily program, monitor, and control (locally or remotely) all the functions of the LX lighting controls system conveniently from their PC—all without installing software. LXJNSYS
PRODUCT FEATURES
• Real-time programming and monitoring of the LX lighting control system through your PC
NETWORK
• No software required—built-in web server provides connection via any Internet Explorer®-compatible browser • Graphical User Interface (GUI) makes programming both intuitive and simple • Local or remote access via the local network or Internet • Can connect multiple users at once • Sophisticated user account/password manager
6.25”
• Powered by the revolutionary NiagaraAX Framework® • Five-year warranty
4.82”
2.43”
Pa g e 112
hubbell-automation.com
Ordering Information
LXJNSYS
LXJNSYS2LON
model LX JENEsys Controller with Management Software, LON Network Module and Power Supply N LX JENEsys Controller with Management Software, LON Integration Support, LON Network Modules and Power Supply
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 113
LX Switch Station LX SERIES NETWORKED LIGHTING CONTROLS
LX Switch Stations are designed for virtually any area. The soft contours of its architecturally-pleasing design fit easily into any décor. Each switch can be individually programmed to control a single relay, group of relays, or preset scene. In addition to flexible switch functionality, LX Switch Stations can be programmed to be active only during a specific time window. This function allows the switch station to be automatically secured when they are not being used, which eliminates LXSW1
LXSW4
LXSW2
LXSW5
LXSW3
the need for lockout key switches and locking covers.
LXSW6
PRODUCT FEATURES NETWORK
• Attractive, architecturally-pleasing design • Flexible programming of switch functionality • Programmable active and inactive times • Topology-free, polarity-insensitive, 2-wire communication • FT-10 and LPT-10 versions available • LonMark ® certified • 1–6 buttons with or without pilot
4.13”
• Mounts to standard single-gang box • Five-year limited warranty
1.13” 1.13”
Pa g e 114
hubbell-automation.com
g up, installing, and
Figure 2: Switch Station Controls Diagram
wer off at service panel ergized electrical
Power Indicator LED (reference Switch Station Controls Diagram) is lit. 5. Program Switch Station button controls and lighting system functionality as described in the Programming Switch Station Functions Section. Figure 1: Wiring Diagram
cordance with e following instruc-
The Switch Statio located under the Switch Station Co to address 001 pri Station on the net address. Address address 001. For Station on the net Address dial settin
To set the Switch tion facia (front c a small blade scre the Facia Remova Remove the facia dials as shown in appropriate dial(s tor points to the a address as delinea the most significa least significant d 001 is set by Dial
eginning installation.
amaged.
ugh-in wall switch work leads as necesCommunication n the communication
Assigning Switch
(FT Version only) n as shown in the
e Switch Station’s on Controls Diagram)
Assigning Switch Station Network Address The Switch Station network address is set via three rotary dials General Specifications located under the Switch Station facia (face cover) as shown in the ighting system funcSwitch Station Controls Diagram. Each Switch Station is factory set Network FTT-10 witch Station Functions to addressInterface 001 prior to shipping. For LX-only networks, each Switchor LPT-10 Station on the network will need to be assigned a unique network Programming and Configuration Programmable over a network using the LX Touch Tablet or any other LX programming device address. Addresses must be assigned in sequential order starting with address 001. For LonWorks Open System Networks, each Switch Physical Injection-molded switch plate and switches Mode. Station on the network must be programmed for LonMARK Fits standard (Decorator style) wall switch plates (not included) Address dial settings have no effect in LonMARK Mode. Mounts to standard electrical gang box To set the Switch Station Address, carefully remove the Switch Sta- version: powered from Link Power Module Electrical LPT-10 Insert version: 24 volts AC or DC; .5Amps required tion facia (front cover) to gain access to the address controls.FTT-10 a small blade screwdriver into the facia catch release as shown in Operating Environment Location: the Facia Removal Diagram and gently snap it loose at the top edge. interior space rotary temperature: 0° to 50°C (32° to 122°F) Remove the facia along with any buttons that obscure the three Operating the humidity (non-condensing): 10% to 90% dials as shown in the Switch Station Controls Diagram. Rotate Relative appropriate dial(s) with the small, blade screwdriver till the indicaDimensions 4.13”H tor points to the appropriate number. Assign each Switch Station its x 1.13”D x 1.13”W address as delineated in the project plans as applicable. Dial1–6 “A”buttons sets Capacities the most significant digit of the network address and Dial “C” sets the Certifications LonMark 3.3 certified least significant digit of the network address. For example, address 001 is set by Dial A = “0”, Dial B = “0” and Dial C = “1”. Warranty Five-year limited
Ordering Information LXSW model LXSW
No. of Buttons 1 2 3 4 5 6
Network interface LP Link Power LPT-10 FT FTT-10 24V AC or DC
color W I
White Ivory
Example: White 4 Button FT Switch Station: LXSW4FTW
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 115
Keyed Switch Station
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
The LX Keyed Switch Station is designed for use in virtually any space that requires restricted access to switch functionality. The stainless steel faceplate and secure barrel-style locking mechanism provide significant tamper and vandal deterrence. The switch can be individually programmed to control a single relay or group of relays. In addition to flexible programming of switch functionality, LX Keyed Switch Stations can be programmed to be active only during a specific time window, allowing the switch station to be automatically disabled when they are not required. This provides a second layer of access control.
LXKEY
PRODUCT FEATURES NETWORK
• Stainless steel face plate with barrel-lock mechanism and pilot light • Flexible programming of switch functionality • Programmable Active & Inactive times • Topology-Free, Polarity-Insensitive, 2-wire communication • Mounts in standard single-gang box • Five-year limited warranty
4.5”
4.13”
1.13” 1.13” 2.75”
Pa g e 116
hubbell-automation.com
9601 Dessau Road • Building One • Suite 100 Austin, Texas 78754 512-450-1100 • 512-450-1215 Fax www.hubbell-automation.com
in the Assigning Switch Sta-
ect LON Network leads to the iagram, Figure 1. h on switch station cover to wn in Figure 2. The connecn either direction. stainless steel cover and the e time. verify that the Switch Station hen the key is turned to the
Figure 1: Wiring Diagram
Overview These instructions provide guidelines for setting up, installing, and programming the LX Keyed Switch Station. Precautions • RISK OF ELECTRICAL SHOCK. Turn power off at service panel before beginning installation. Never wire energized electrical components. • For installation by a licensed electrician in accordance with National and/or local Electrical Codes and the following instructions. • Indoor use only. • Read and understand all instructions before beginning installation. • USE COPPER CONDUCTOR ONLY. • NOTICE: Do not install if product appears damaged.
ls and lighting system funcg Switch Station Functions
Installation 1. Prepare the installation site as necessary. Rough-in wall switch boxes and route LON Network leads as necessary. Reference Open System Architecture Communication Network Section for additional information on the communication network requirements. 2. Assign Network Address as described in the Assigning Switch Station Network Address Section. 3. With the Link Power supply off, connect LON Network leads to the Figure 2: Keyed Switch Station Controls Diagram Switch Station as shown in the Wiring Diagram, Figure 1. Figure 1: Wiring Diagram 4. Attach wire connector from key switch on switch station cover to the connector on the circuit board as shown in Figure 2. The connecGeneral Specifications tor is not polarized and can be inserted in either direction. 5. Use the supplied screws to attach the stainless steel cover and the device in the wall switch box atLPT-10 the same time. Network Interface 6. Apply Link Power to the system and verify that the Switch Station Programming and Configuration Programmed over is powered. The green LED will light when the keynetwork is turnedusing to thethe LX Touch Tablet or any other LX programming device ON position. Stainless steel faceplate 7. Program Switch Station button controls and lighting system funcBarrel-style locking switch mechanism tionality as described in the Programming Switch Station Functions Mounts to standard electrical gang box Section. LPT-10: Powered from Link Power Module
Physical Electrical Dimensions
Switch Station: 4.13”H x 1.13”W x 1.13”D Face Plate: 4.5”H x 2.75”W
Operating Environment
Location: Interior space Operating temperature: 0° to 50°C (32° to 122°F) Relative Humidity: 10% to 90% non-condensing
Warranty
Five-year limited
Ordering Information lxKEY model LXKEY1
Figure 2: Keyed Switch Station Controls Diagram
LP Network interface LP
color Blank Stainless Steel2
NOTES: 1. LXKEY is available with 1 keyswitch only and "LP" Link Power only. 2. LXKEY available in Stainless Steel only (not available in white or ivory).
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 117
LXOMNI™ Dual Technology Occupancy Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
24 VDC
VOLTAGE
The LX Occupancy Sensor is a LonMark ® certified device that represents the state-of-the-art in sensor technology, combining both ultrasonic (US) and passive infrared (PIR) technologies for unequaled occupancy detection and false trip immunity. Both FT-10 and LPT-10 versions are available. The LX Occupancy Sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
LXOMDT2000
PRODUCT FEATURES NETWORK
•
FT-10 and LPT-10 versions available
•
Topology-free, polarity-insensitive, 2-wire communication
•
IntelliDAPT self-adaptive technology - no manual adjustment required
•
All-digital dual technology (ultrasonic [US] and passive infrared [PIR]) sensor
•
Non-volatile memory for sensor settings
•
2,000 square-foot coverage area (depending on model)
•
UL and cUL listed
•
California Title 24 compliant
•
LonMark® certified
•
Five-year limited warranty
OCCUPANCY SENSING
IntelliDAPT
PIR Sensor Ultrasonic Sensor
1.5”
4.5”
Pa g e 118
hubbell-automation.com
22'
12'
32' 23'
45' 64' US Minor Motion
IR Minor Motion
US Major Motion
IR Major Motion
General Specifications Network Interface
FTT-10 or LPT-10
IntelliDAPT Technology Auto reset from test setting Self-adjusting timer Self-adjusting passive infrared thresholds Automatic false-on/false-off corrections LED Lamp Red- infrared motion Green- ultrasonic detection Time Delay Automatic mode: 8–30 min. (self-adjusts based on occupancy) Manual mode: 2-30 min. Test mode: 8 seconds (for an easy check at installation) Ultrasonic (US) Output
32kHz
Passive Infrared (PIR)
Dual-element pyrometer and 12-element cylindrical rugged lens
Programming and Configuration
LX mode- programed over network using LX Touch Tabley, JENEsysTM
Coverage 2,000 square feet Power Requirements
LP Version requires 42VDC, (Provided by the LXLPM2) ; FT Version requires 24VDC, (Provided by the LXPWRSPLY)
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Construction Casing- rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UL-945VA) flame class rating, UV inhibitors
Color-coded leads are 6” long Dimensions 4.5”DIA x 1.5”H Weight 5.0 oz Color Off-white Mounting Mounting base provided Recommended MAX mounting height: 8ft with a max mounting height of 12ft Certifications
LonMark 3.3 certified
UL and cUL listed Warranty Five-year limited
Ordering Information lx
OMDT 2000
model LX
DEVICE TYPE OMDT 2000
NETWORK INTERFACE LP FT
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 119
LX Photo Sensor and Control Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
The LX Photo Sensor and Control Module provides a convenient method of turning lighting circuits on and off in response to natural light. With 6 individually programmable on and off set points, this device can control multiple lighting circuits to respond to different natural lighting levels. This eliminates the need for multiple photosensors. Real-time photometric information is transmitted over the LX network and displays on either the LX tablet (or another programming device connected to the network). Each of the 6 set points can be programmed to control a single relay, group of relays, or preset
LXPSCM
scene. For added control, the LX Photo Sensor Control Module can be programmed to be active or inactive during a specific time window.
LXPSPCO
LXPSPCI
LXPCPCS
PRODUCT FEATURES NETWORK
DAYLIGHT HARVESTING
• Turns lighting on and off based on available natural light • Network-based photosensor control module • Real-time foot-candle levels transmitted over a network on demand to a tablet • 3 available sensor heads - Indoor, Outdoor, and Skylight/Atrium • 0-1,000 foot-candle range with 1 foot-candle resolution • 6 programmable on and off set points
3.75”
• Programmable active and inactive times • Topology-free, polarity-insensitive, 2-wire communication • FT-10 and LPT-10 versions available • LonMark ® certified
1.5” 6.25”
• Mounts to standard DIN Rail • Five-year limited warranty
Pa g e 12 0
hubbell-automation.com
General Specifications Network Interface
FTT-10 or LPT-10
Programmable Functionality
Each on and off set point can be programmed to control a single relay, group of relays, or preset scene Active and inactive times
Programming
Programmable over a network using the LX Touch Tablet
Capacities
6 programmable on and off set points with adjustable deadband
Photocell Ranges
0–1,000 foot-candle range with 1 foot-candle resolution
Electrical
LXPSCMLP: Powered from the Link Power network LXPSCMFT: 16–30 Volts AC or DC; .5 Amps required
Operating Environment
Indoor use only (Except LXPSPCO) Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Dimensions
6.25”L x 3.75”H x 1.5”W
Weight
6.0 oz.
Color
Photo Sensor Control Module—black Photo Sensor Photocells—white
Mounting
Mounts to a 35mm DIN rail
Certifications
LonMark 3.3 certified
Warranty
Five-year limited
Ordering Information Control Module lxPS
CM
model
DEVICE TYPE
NETWORK INTERFACE
LXps
CM
LP FT
NOTE: 1. LXPSCM Photo Sensor Control Module Support only one (1) Photo Sensor head. Photo Sensor head is ordered separately.
Photo Sensor lxpsp model
LXps
pCI pCO pCS
DEVICE TYPE Photocell Indoor Photocell Outdoor Photocell Skylight / Atrium LonWorks ® is a registered trademark of Echelon Corporation. LonMark ® is a registered trademark of LonMark International.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 12 1
LX Dry Contact Interface Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
The LX Dry Contact Interface Module provides a simple method of incorporating standard dry contact inputs into the LX lighting control system. This device can incorporate dry contact closures from building automation, fire, and security alarm systems. It can also incorporate virtually any dry contact device (momentary or maintained). Each of the 6 available inputs can be individually programmed to control a single relay, group of relays, or preset scene. For added control, the LX Dry Contact Input LXDCIMFT
Module can be programmed to be active or inactive during specific time windows.
PRODUCT FEATURES NETWORK
• Programmable interface for dry contact devices • Flexible programming of switch functionality • 6 individual dry contact inputs with or without pilots 24V Supply Input
• Accommodates 2- and 3-wire devices (momentary or maintained) • Programmable active and inactive times • Topology-free, polarity-insensitive, 2-wire communication
3.75”
• LonMark ® certified Contact Input Ports
• Mounts to standard DIN rail • Five-year limited warranty 6.25”
PA G E 12 2
hubbell-automation.com
LON Network Interface
24V DC Power Supply Use LXPWRSLPY
Use 2, 3, or 4-conductor, 20AWG non-shielded cable as appropriate. 1000ft. maximum length.
General Specifications Network Interface
FTT-10
Programmable Functionality Maintained contact switch input: - toggle, on only, off only Momentary contact switch input: - push button toggle, on only, off only Preset Timed on Programming
Programmable over a network using the LX Touch Tablet
Capacities
Maximum of 6 momentary or maintained switches (2- or 3-wire)
Electrical
16–30 Volts AC or DC; .5 Amps required
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
Dimensions
6.25”L x 3.75”H x 1.5”W
Weight
6.0 oz
Color Black Mounting
Mounts to a 35mm DIN rail
Certifications
LonMark 3.3 certified
Warranty
Five-year limited
Ordering Information lx model LX
DCIM DEVICE TYPE DCIM1
FT NETWORK INTERFACE FT
NOTE: 1. FT only.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 12 3
LX Line V Automatic Line Voltage Switches
TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
120 277 VAC
The Hubbell Building Automation Line V Automatic Line Voltage Switches provide feature cost effective lighting control for maximum energy savings. The switches operate based on timed blink patterns from the LX Panels to activate internal relays ON, OFF or override an impending OFF schedule for user selectable periods of 30, 60, 90, or 120 minutes. The LX Panels are designed to control the relay timed blinks to allow for a single relay to signal multiple Line V switches to perform the desired functions. The 1-Relay version has standard capability to be wired to addition switches for 3-way and 4-way operation on a single zone. The 2-Relay version allows for bi-level LINEVAS1BUNVWH
LINEVAS2BUNVWH
switching within a single zone. Signal ON can be selected for 1 or 2 relays.
PRODUCT FEATURES • Two switch configurations – 1-Relay and 2-relay • 1-Relay model controls a single zone or can be connected for 3-way and 4-way operation • 2-Relay model provides single circuit input for dual level area control • Switches are controlled ON or OFF from the LX Panel using OFF intervals from a single relay • Allows for retrofit of standard line voltage toggle switches for automatic schedule ON/OFF control • Blink warning allows user to initiate override of 30, 60, 90, or 120 minutes and
4.29”
cancel OFF event • Switches operate without the need for a neutral connection • Dual 120/277VAC operation • No minimum load requirement • Zero Arc Point Switching • ETL, UL, and cUL listed
1.8” 2.1”
• California Title 24 compliant • Five-year limited warranty
Pa g e 12 4
hubbell-automation.com
General Specifications Programming and Configuration
Programmable via DIP switches mounted on door All control functions are issued at the switch
Relays Configurations
1-Relay – Single Zone OR 3-Way/4-Way operation 2-Relays – Single circuit input for Bi-Level Control
Power Requirements
120/277VAC; 50/60Hz
Electrical Ratings
120VAC: 5.0 Amps Tungsten; 10.0 Amps Fluorescent; 1/3 HP 277VAC: 10.0 Amps Fluorescent; 1/6 HP
Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32°–104°F (0°–40°C) Relative humidity (non-condensing): 0%–95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Color-coded leads are 6” long
Dimensions
4.2”H x 1.8”D x 2.1”W; .37” extension
Weight
2.9 oz.
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (average switch box) Decorator-style wall plate not included
Certifications
ETL, UL, and cUL listed
Warranty
Five-year limited
Ordering Information
model/DESCRIPTION LINEVAS1BUNVBK LINEVAS1BUNVGY LINEVAS1BUNVIV LINEVAS1BUNVLA LINEVAS1BUNVWH LINEVAS2BUNVBK LINEVAS2BUNVGY LINEVAS2BUNVIV LINEVAS2BUNVLA LINEVAS2BUNVWH
Line V Line V Line V Line V Line V Line V Line V Line V Line V Line V
120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic
Switch, 1-Button, Single Relay, Single or 3-Way Black Switch, 1-Button, Single Relay, Single or 3-Way Gray Switch, 1-Button, Single Relay, Single or 3-Way Ivory Switch, 1-Button, Single Relay, Single or 3-Way Light Almond Switch, 1-Button, Single Relay, Single or 3-Way White Switch, 2-Button, Dual Relay, Single Black Switch, 2-Button, Dual Relay, Single Gray Switch, 2-Button, Dual Relay, Single Ivory Switch, 2-Button, Dual Relay, Single Light Almond Switch, 2-Button, Dual Relay, Single White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 12 5
LX Link Power Module TITLE
24 CEC
COMPLIANT
CALIFORNIA
LX SERIES NETWORKED LIGHTING CONTROLS
120 VAC
Hubbell Building Automation’s LX Link Power Module is a self-contained power supply that provides operating power to LX Series twisted-pair communication networks. This module powers a multitude of device types, such as LX switch stations, LX occupancy sensors, and LX photosensor control modules. The device’s versatility enables it to support a variety of network topologies, including Star and T-configurations.
LXLPM2
PRODUCT FEATURES NETWORK
• Power supply for LX Series Link Power-based devices • Short-circuit and overcurrent monitoring • Bus termination by switch • DIN rail mount • Five-year limited warranty 3.54”
4.96”
Pa g e 12 6
hubbell-automation.com
General Specifications Power Supply
Rated input voltage: 120VAC (85-132V) Rated frequency: 50/60 Hz Rated input current: 0.7A
Output to Bus
Output voltage: 41.5V; +/-2.2% Residual ripple: <80mV at 10 kHz (200mV at f>200kHz) Output current: 1A (supports approximately 56 LX Series devices)
(For larger networks, an additional LX Link Power Module and
LX Router/Repeater Module can be added to expand the LX network)
Overload protection: typical at 1.6A; permanent short circuit proof with pulsing “try of restart”
Connectors
Screw terminal
Operating Environment
Indoor use only Operating temperature: 32° to 104°F (0° to 40°C) Relative humidity (non-condensing): 0% to 95%
EMC
Emission: EN61,000-6-3; class B; EN50090-2-2 Immunity: EN61,000-4-2/3/4/5/6; class A
Dimensions
4.96”L x 2.28”W x 3.54”H
Warranty
Five-year limited
Ordering Information lxLPM2
model LXLPM2
LX Link Power Module
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 12 7
LX Router/Repeater Module LX SERIES NETWORKED LIGHTING CONTROLS
Hubbell Building Automation’s LX Router/Repeater Module interconnects multiple LX Series communication-network segments and refreshes the network signal from one segment to the next thus increasing the maximum transmission distance. This module is required for networks where either the network wire length exceeds the maximum limit (1,500 feet) or there are more than 56 devices per segment. With the LX Router/Repeater Module, two independentlypowered network segments can share their information while maintaining each segment’s power system separately.
LXRRM
PRODUCT FEATURES NETWORK
• Repeater for LX Series networks • Screw terminal wiring connections • 16–30VAC or VDC operation • LonMark™ certified • UL listed • Five-year limited warranty
6.3”
1.0” 3.9”
Pa g e 12 8
hubbell-automation.com
General Specifications Processor
2 Neuron 3150® Chips; 10MHz
Service Function
Recessed service switch and service (wink) LED. Dual tear-off bar code Neuron ID self-adhesive tag
Channel Type
TP/FT-10 to TP/FT-10
Input Power
16–30VAC or DC @ 24VA Requires a separate power supply (the LXPWRSPLY)
Mounting
DIN Rail
Operating Environment
-40° to 185°F (-40° to 85°C) Relative humidity (non-condensing): 10% to 95%
Dimensions
3.9”L x 6.3”H x 1.0”W
Certifications
UL 916; FCC A; CE Mark
Warranty
Five-year limited
Ordering Information LXRRM
LXRRM
model LX Repeater
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 12 9
LX Power Supply LX SERIES NETWORKED LIGHTING CONTROLS
LOW
120 24 VAC VDC
VOLTAGE
Hubbell Building Automation’s LX Power Supply provides power to free topology(FT)-based LX Series devices. The 30W, single-output, Class 2, DIN rail power supply can power LX switch stations, LX occupancy sensors, LX photosensor control modules, and LX dry contact interface modules. This power supply also features an LED indicator for power-on status and short-circuit, overload, and overvoltage protection support.
LXPWRSPLY
PRODUCT FEATURES NETWORK
• Universal AC input 120VAC (100–240V); line and neutral single phase only • DIN rail mountable: TS35/7.5; TS35/15 • Protection: short circuit, overload, and over-voltage • LED indicator for power on • UL listed • Five-year limited warranty
3.5”
2.5” 3.0”
Pa g e 13 0
hubbell-automation.com
General Specifications AC Input Voltage Range
120VAC (100–240V), 50-60HZ Line and Neutral Single Phase only
Output
24V; 0–1.5A
Tolerance +/-1% Efficiency 83% DC Adjustment Range
Rated output voltage: +/-10%
Overload Protection
105% to 160% constant current limiting; auto-recovery
Over-voltage Protection
Rated output voltage: 115% to 135%
Setup; Rise; Hold-up Time
100ms, 70ms, 100ms at full load and 132VAC
Withstand Voltage I/P-O/P:3KVAC Connection I/P: 2 poles O/P: 4 poles screw DIN terminal Dimensions
3.0”L x 3.5”H x 2.5”W
Operating Environment
-4° to 22°F (-20°to 50°C) @100% load 140° F (60° C) @ 80% load
Certifications
UL60950-1; TUV EN60950-1
EMC
EN55022 class B; EN61,000-3-2,3; EN61,000-6-2; EN61,000- 4-2,3,4,5,6,8,11; ENV50204; EN61204-3
Warranty
Five-year limited
Ordering Information lxPWRSPLY model LXPWRSPLY LX Power Supply
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 13 1
LX Enclosure for DIN Rail Modules LX SERIES NETWORKED LIGHTING CONTROLS
Hubbell Building Automation’s LX Enclosure for DIN Rail Modules is designed to enclose our DIN rail-mountable devices and power supplies. The surface-mount metal enclosure is NEMA 1 rated and is suitable for dry indoor locations, such as electrical rooms and closets. The enclosure also comes with a screw-mount cover and 2 DIN rails that can be mounted in multiple ways.
LXENDM
PRODUCT FEATURES • NEMA 1 rated metal enclosure • Screw-mount cover • Includes 2 DIN rails
General Specifications Dimensions
12”H x 15”L x 4”W
Weight
11 lbs.
NEMA 1 Rated
Provides a degree of protection for people against contact with the enclosed devices Provides a degree of protection for the enclosed devices against falling dirt
Warranty
Five-year limited
Ordering Information lxENDM
LXENDM
Pa g e 13 2
model LX Enclosure for DIN Rail Device Modules
hubbell-automation.com
Panel Wire Way Divider Accessory Kit LX SERIES NETWORKED LIGHTING CONTROLS
Hubbell Building Automation’s LXWRDV Panel Wire Way Divider Accessory Kit provides the ability to place a physical barrier in the line voltage wire’s way to separate different voltages or sources. This accessory is field-installed and ordered separately. Each kit includes two code-gauge steel divider plates and mounting hard-ware. Dividers are easily installed between relays and therefore do not consume any relay spaces.
PRODUCT FEATURES • Provides physical code-gauge steel separation between different voltages or sources that share the same relay panel • Field-installed
• Fits between relates – no loss of relay spaces • For use with LX Series Lighting Control Panels (Except 4 relay LX panels)
• Can be mounted at any location
General Specifications Each Kit Includes:
2 ea - Wire Way Divider Plates 2 ea - Stainless Steel mounting Screws Installation Instructions
Operating Environment
Indoor use only
Dimensions
4.25”W x 3.25”L
Weight
3.0 oz.
Color
ANSI 61 Gray Polyester Powder Coat
Certifications
For use with LX Series UL and cUL Listed LXIN and LXEN network lighting control panels (except LXEN04)
Warranty
Five-year limited
Ordering Information lxWRDV
lxwrdv
model Wire Way Divider Kit for LX Series Relay Panels
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 13 3
Riser Rated Belden 8471 Cable LX SERIES NETWORKED LIGHTING CONTROLS
Hubbell Building Automation’s LX network cable is used to interconnect LX
PVC Jacket (Unsheilded)
Panels, LX Devices and LX Accessories for a complete communications network. All devices that communicate on the LX Network are connected with the same
BELDEN 8471
type of twisted pair cable. Both power and data are carried over the same two wires. The LX System is wired as a topology-free, polarity-insensitive network. HBA supplied LX Network Cables assure proper network communications and should be specified and installed on all LX System projects.
Twisted Pair #16 Tinned Copper Conductors, PVC Insulation
PRODUCT FEATURES • Interconnects LX Lighting Control Panels and LX network devices • Cable carries both power and data in a single twisted pair • Belden #8471 - twisted pair #16 tinned copper • Single cable type connects to all types of LX network devices • Echelon Guideline Compliant for LON networks • Available in 100 ft and 500 ft reels • Riser Rated • Connects to terminal blocks or with twist on connectors • UL and cUL Listed • One-year limited warranty
LX SYSTEM NETWORK CABLE REQUIREMENTS Hubbell Building Automation’s LX Lighting Control System requires the use of Belden #8471 cable for Riser Rated applications OR Windy City Wire #104500 for Plenum Rated applications. These are the ONLY cables that can be used for network wiring with the LX System. The use of substitute cables based on similar physical characteristics is not allowed and will VOID any HBA warranty for the LX system or any LX component connected to the substitute cable.
Pa g e 13 4
hubbell-automation.com
General Specifications Description
1 pair - 16 AWG stranded tinned copper conductors, PVC Insulation, unshielded twisted pair (UTP), PVC jacket
Shielding Unshielded Overall Nominal Diameter
0.274 inches
Plenum Rating
Not Plenum Rated
Operating Temperature Range
-20°C to +80°C (Indoor use only)
Maximum Pulling Tension
61 lbs
Minimum Bend Radius
5.1 inches
Color
Pair Color - Black/White, Outer Jacket - Gray
Certifications
NEC (UL) CMG, CEC/C (UL) CMG,
Flame Test
UL Flame Test – UL1685 FT4 Loading, C (UL) Flame Test FT4
Warranty
One-year limited
Ordering Information
LX8471CBL100* LX8471CBL500*
model LX Cable Belden 8471 Riser Rated 100 ft Reel LX Cable Belden 8471 Riser Rated 500 ft Reel
*All sales are final, no returns are allowed.
INSTALLATION NOTES 1.
DO NOT exceed 1500 feet of cable OR connect more than 56 devices per network segment.
2.
Each network segment using LP style devices requires an LXLPM2 Link Power Module for device power. Each additional segment requires an additional LXLPM2 Link Power Module and an LXRRM Repeater for data transmission between segments.
3.
Each network segment existing of panels only or that use FT style devices only require termination with LXTERMINATOR instead of LXLPM2 Link Power Module.
4.
Run cable and connect network with the shortest distances possible. The most efficient network is wired similar to branch circuit outlets.
5.
When using twist-on wire connectors with network cable use no more than three wires per connector.
6.
The use of T-taps to minimize cable length is encouraged. Daisy chain topology is allowed, but most often increases overall cable length.
7.
DO NOT homerun all devices individually, or leave spare cable at ceiling mounted devices. If devices need to be relocated, cables can be extended with twist-on wire connectors.
8.
DO NOT mix plenum and NON-plenum cables on the same segment.
9. Keep 12” minimum from line voltage, do nut run in the same raceway with line voltage.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 13 5
Plenum Rated Windy City Wire 104500 Cable LX SERIES NETWORKED LIGHTING CONTROLS
Hubbell Building Automation’s LX network cable is used to interconnect LX Panels, LX Devices and LX Accessories for a complete communications network. All devices that communicate on the LX Network are connected with the same type of single twisted pair cable. Both power and data are carried over the same two wires. The LX System is wired as a topology-free, polarity-insensitive network. HBA supplied LX Network Cables assure proper network communications and should be specified and installed on all LX System projects.
PRODUCT FEATURES • Interconnects LX Lighting Control Panels and LX network devices • Cable carries both power and data in a single twisted pair • Windy City Wire #104500 - twisted pair #16 tinned copper • Single cable type connects to all types of LX network devices • Echelon Guideline Compliant for LON networks • Available in 100 ft and 500 ft reels • Plenum Rated • Connects to terminal blocks or with twist on connectors • UL and cUL Listed • One-year limited warranty
LX SYSTEM NETWORK CABLE REQUIREMENTS Hubbell Building Automation’s LX Lighting Control System requires the use of Belden #8471 cable for Riser Rated applications OR Windy City Wire #104500 for Plenum Rated applications. These are the ONLY cables that can be used for network wiring with the LX System. The use of substitute cables based on similar physical characteristics is not allowed and will VOID any HBA warranty for the LX system or any LX component connected to the substitute cable.
Pa g e 13 6
hubbell-automation.com
General Specifications Description
1 pair - 16 AWG stranded tinned copper conductors, PVC Insulation, unshielded twisted pair (UTP), PVC jacket
Shielding Unshielded Overall Nominal Diameter
0.182 inches
Plenum Rating
Plenum Rated
Operating Temperature Range
0°C to +75°C (Indoor use only)
Maximum Pulling Tension
61 lbs
Minimum Bend Radius
5.1 inches
Color
Pair Color - Black/White, Outer Jacket - White
Certifications
NEC (UL) Subject 444 Type CL2P/CMP, CSA (cUL)
Flame Test
NFPA 262 Steiner Tunnel Test
Warranty
One-year limited
Ordering Information
model LX104500CBL100* LX Cable Windy City 104500 Plenum Rated 100 ft Reel LX104500CBL500* LX Cable Windy City 104500 Plenum Rated 500 ft Reel *All sales are final, no returns are allowed.
INSTALLATION NOTES 1.
DO NOT exceed 1500 feet of cable OR connect more than 56 devices per network segment.
2.
Each network segment using LP style devices requires an LXLPM2 Link Power Module for device power. Each additional segment requires an additional LXLPM2 Link Power Module and an LXRRM Repeater for data transmission between segments.
3.
Each network segment existing of panels only or that use FT style devices only require termination with LXTERMINATOR instead of LXLPM2 Link Power Module.
4.
Run cable and connect network with the shortest distances possible. The most efficient network is wired similar to branch circuit outlets.
5.
When using twist-on wire connectors with network cable use no more than three wires per connector.
6.
The use of T-taps to minimize cable length is encouraged. Daisy chain topology is allowed, but most often increases overall cable length.
7.
DO NOT homerun all devices individually, or leave spare cable at ceiling mounted devices. If devices need to be relocated, cables can be extended with twist-on wire connectors.
8.
DO NOT mix plenum and NON-plenum cables on the same segment.
9. Keep 12” minimum from line voltage, do nut run in the same raceway with line voltage.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 13 7
Affordable Switching and Dimming CX Panels provide feature rich and cost effective lighting control for maximum energy savings. You can save up to 50% in labor and materials when used in place of conventional time clock and contactor combinations. The use of the Astronomical Clock in place of roof mounted photocells increases cost savings, lowers maintenance, and improves reliability. SAVE TIME
Lower Cost
•
Compact single enclosure includes relays,
•
Can save up to 50% in parts and labor cost over
control functions and input terminals for low
conventional time clock and contactor systems.
voltage devices.
•
Lowers energy consumption with expanded
•
All inputs are software assignable to any HBA
programming options.
low voltage input device including switches,
•
Astronomical clock eliminates the need for roof
motion sensors, and photocells.
mounted photocells.
•
Low voltage devices connect directly to panel
•
Pre-programmed scenarios offer a wide variety
without any ancillary parts such as power packs.
of options to maximize energy savings for each
•
LCD user interface incorporates easy to follow
possible control zone.
intuitive programming tools.
Increase Control
Save Energy
•
Sunrise/sunset controls provided using internal
•
HBA CX Panels meet ASHRAE 90.1, IEEC and
astronomical clock.
California (CEC) Title 24 energy codes.
•
Scenarios offer many easy to use control
•
CX Panels contribute to LEED certification
combinations.
requirements.
•
Priorities and masking allow for personalized
•
Allows multiple low voltage inputs from HBA
control solutions.
switches, motion sensors, and photocells to
•
Dimming option for most 0-10V ballasts and
enhance energy savings for scenarios such as
LED drivers
manual switch ON and automatic motion sensor
OFF control.
Pa g e 13 8
hubbell-automation.com
The CX Series panels are self-contained lighting control systems. All inputs are low voltage and hard-wired to terminal blocks in the panel. Input power supply is multi-tapped or universal for typical service voltages. Line voltage terminals are located with generous space for easy connection.
CX 8-Relay Panel Interior
Auxiliary Inputs
Dry Contact Outputs Individual Mounted Relay Card
CX Dimming Card
Auxiliary Input Features • Provisions for multiple device control of a single relay or group. • Scenarios program allows for easy mapping of auxiliary inputs.
Dry Contact Output Features
CX Dimming Card Features
Relay Card Features
• Normally open or normally closed output. • Momentary or maintained. • Allows for interconnection to other building functions such as security, fire alarm, or building management system.
• Full range dimming with preset dimming levels. • Ramp Up, Fade Down, Minimum Dim Level. • Max Dim Level (Demand Response System Settings) • Operates with 0-10V dimmable ballasts. • Provides manual and automatic control of dimming levels. • 8 Dimming channels per card. • Works with CAT5 switches.
• 1-pole and 2-pole relays fit in the same sized space. • Relay self-identifies once installed. • Available 20A/1P N/O, 20A/2P N/O or N/C and 30A/1P latching. • 14K SCCR for 20A/1P N/O, 20A/2P N/O or N/C. • 18K SCCR for 30A/1P latching.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 13 9
CX Lighting Control Panels
TITLE
24 CEC
COMPLIANT
CALIFORNIA
CX COMMERCIAL LIGHTING CONTROL PANELS
120 277 VAC
The Hubbell Building Automation CX Commercial Lighting Control Panels provide
CX16 and CX24 16- and 24-Relay Panels
feature-rich and cost-effective lighting control for maximum energy savings. The LCD User interface is located in the door and utilizes simple and intuitive CX04 and CX08 4- and 8-Relay Panels
scrolling menus to program, check status or update the panel. The easy-to-use Pre-Programmed Scenarios Menu makes project commissioning simple and fast. The CX Panels can save up to 50% in labor and materials when used in place of conventional time clock and contactor combinations. The use of the astronomical clock instead of roof-mounted photocells increases cost savings, lowers maintenance, and improves reliability.
PRODUCT FEATURES • Four Relay panel sizes – 4, 8, 16 and 24 relay spaces • Relays – 20A/1P, N/O, 20A/2P, N/O (14K SSCR) and 30A/1P latching (18K SCCR) • Optional 0-10V Dimming • LCD user interface with keypad • 365 day programming with 64 schedules • Astronomical and real time clock • 6 programmable dry contact inputs for 4 relay panel 12 Programmable dry contact inputs for 8 relay panel 20 Programmable dry contact inputs for 16 relay panel 30 programmable dry contact inputs for 24 relay panel • Selectable pre-programmed scenarios • Programmable inputs accept low voltage switches, photocells, or motion sensors •
Two low voltage dry contact output relays on 8, 16 and 24 relay panel
• Program uploads via removable SD memory card • Listed to UL916, UL924 and cUL • Five -year limited warranty
Pa g e 14 0
hubbell-automation.com
CX04 and CX08 4- and 8-Relay Panels 14.5” W x 17”H x 4” D
CX16 and CX24 16- and 24-Relay Panels 20” W x 24”H x 4” D
General Specifications Programming and Configuration
Programmable via user interface mounted on door Fully programmable by users with door closed and locked Stand Alone, Master, or Secondary Panels. One Master and one Secondary may be connected as a system
Physical
NEMA 1 surface enclosure Pre-drilled mounting holes for mounting to wall, KOs provided on top and bottom 4/8 relay and 16/24 relay enclosures with hinged locking door
Electrical Input
120/208/240/277VAC for 4/8 size 120-277VAC Universal for 16/24 size Standard 120/277/347 Optional
Operating Environment
Location: NEMA 1 interior space Operating temperature: 0° to 50°C (32° to 112°F) Relative humidity (non-condensing): 10% to 90%
Certifications
Listed to UL916, UL924 and cUL
Warranty
Five-years limited
Ordering Information CX model CX CX Lighting Control Panel
S
Spaces 04 4 Relay Spaces 08 8 Relay Spaces 16 16 Relay Spaces 24 24 Relay Spaces
Input voltage 2 120/277V Universal
Enclosure S NEMA 1 Surface
3 347/480V
NOTES: 1. Required for CX04 Series Panels. Not Available for CX08, CX16, CX 24 2. Not available for CX04.
Relay Quantity 00 No Relays Spaces Only 04 4 Relays Installed 08 8 Relays Installed 16 16 Relays Installed 24 24 Relays Installed
Relay type SP Space Only 2N 20A Electrically Held N/O 120-277V 3L Latching 120-277347V TN 20A Electrically Held N/O 208480V
Options N Stand Alone Panel M Master Panel S Secondary Panel (Note 4 & 5)
3. 2-Pole relays take the same amount of space as 1-Pole relays. 4. Installed relays must be all of the same type. Relay Type TC and 2C not available in fully populate panels 5. “00” option has no relays, all must be ordered separately and installed in the field. 6. Secondary panel includes (2) master/secondary panel interface cards.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 141
CX Relays CX LIGHTING CONTROL PANELS
The CX Panels have four types of available CXR relays. Each relay is individually board-mounted and can be installed in any combination in the panel. Relays are offered in a variety of types and ratings to meet any project requirements. Types include electrically-held normally open (N/O), electrically-held normally closed (N/C), and latching. Ratings are 20A/1P 20A/2P, and 30A/1P. Pre-Configured Panels are available with relays of the same type. Combinations of any relay type must be ordered CXRTN & CXRTC 20A/2P Relays
separately and field installed into Space Only standard panels.
PRODUCT FEATURES • Relays are mounted to individual relay cards • Four types of relays – 20A/1P, N/O and 20A/2P, N/O, N/C (14K SCCR) and 30A 1P latching (18K SCCR) • Smart Relay card self-identifies type automatically to panel
CXR2N 20A/1P Relay
• Each relay includes 1 programmable input for low voltage switches, photocells, or motion sensors • Panels are ordered fully populated with the same relay type or with space only for field installation of relay combinations • Relay cards include a plugging connector to panel motherboard and a single screw to secure it to the panel enclosure • Relay cards include a manual override control button and LED status indication • Listed to UL916 standard, UL924 and Canadian cUL • Five-year warranty
Pa g e 14 2
5.5” 1.625”
CXR3L 30A/1P Relay
hubbell-automation.com
General Specifications Physical
Mounts inside NEMA 1 surface panel enclosure Pre-drilled mounting hole for securing relay cards Individual relay cards – 1P and 2P are equal in size
Operating Environment
Location: interior space Operating temperature: 0°–50°C (32°–112°F) Relative humidity (non-condensing): 10%–90%
Certifications
Certified to UL 916, UL 924 and cUL
Warranty
Five-year limited
Relay Specifications
Characteristics Type
Load Ratings
Poles
CXR2N- Elec Held , N.O
1
CXR3L- Latching
1
CXRTN - Elect Held, N.O. CXRTC - Elec Held, N.C.
2 2
VAC 120 227 120 277 347 480 † 480 †
Tungsten 15A NA 20A NA NA NA NA
Flour. Ballast * 16A 16A 30A 30A 20A 20A 20A
HID Ballast 20A 20A 30A 30A 20A 20A 20A
Motor Rating 1 HP 3/4 HP 1 HP NA NA 2 HP 2HP
SCCR Rating 14K Amps 18K Amps 14K Amps 14K Amps
* Electronic Flourescent Ballast Rating is 16A † Suitable for use at 208V, 240V and 480V
Ordering Information CXR model CXR
2N 3L TN TC
Relay type 20A 1-Pole Electrically Held N.O. 120-277V 14KSCCR @ 277VAC 30A 1-Pole Latching 120-277-347V 18KSCCR @ 277VAC, 14KSCCR @ 347VAC 20A 2-Pole Electrically Held N.O. 480V 14KSCCR @ 480VAC 20A 2-Pole Electrically Held N.C. 480V 14KSCCR @ 480VAC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 14 3
CX Dimming Option Card
TITLE
24 CEC
COMPLIANT
CALIFORNIA
CX LIGHTING CONTROL PANELS
The CX Dimming Option Card provides 0-10V dimming through any HBA CX Lighting Control Panel. This provides a low cost solution for lighting control challenges such as more stringent energy codes, demand response requirements, and LEED qualification while providing additional energy saving capabilities through the use of full range dimming. The CX Dimming Option Card provides 0-10V dimming control for LED electronic dimming drivers and fluorescent electronic dimming ballasts. The Dimming Channels may be configured to work in concert with Photo Cells, Occupancy Sensors and Schedules in addition to manual Raise Lower Switches.
CXDIMCONTRBD
PRODUCT FEATURES • Full range dimming with Preset dimming levels
• Upgrade option to Existing and New CX Panels
• Ramp Up, Fade Down, Minimum Dim Level
• 8 Dimming Channels per card
• Max Dim Level (Demand Response System Settings)
• Works with Zone5 Switches
• Operates with 0-10V drivers and dimmable ballasts
• Five-year warranty
• Provides manual and automatic control of dimming levels
General Specifications Power Requirements
Low Voltage via CX Panel Option Port
Output (Low Voltage Sensors)
Eight 0-10V Dimming Channels 0-10V Screw terminals. #16 solid or stranded copper wire. 0-10V output 30mA per channel Four RJ45 Connections for discrete RJ45 Zone 5 Switches
Panel Dimming Option Card Capacity
CX04/CX08 CX16
1 CX Dimming Option Card Up to 2 CX Dimming Options Cards
CX24
Up to 3 CX Dimming Option Cards
User Interface
LCD Color Display via CX Panel Supports Zone 5 RJ45 Switches
Warranty
Five-year limited
Ordering Information CXDIMCONTRBD model CXDIMCONTRBD CX Panel 8-Channel Dimming Controller Option Board
Pa g e 14 4
hubbell-automation.com
CX Low Voltage Switches
TITLE
COMPLIANT
CALIFORNIA
CX LIGHTING CONTROL PANELS
LOW
24 24 CEC
VDC
VOLTAGE
Hubbell Building Automation’s CX Low Voltage Wall Switches are designed for virtually any area. The soft contours of its architecturally pleasing design fit easily into any décor. Switches are available in both momentary and latching versions and feature multiple button configurations making them the perfect switch solution for use with HBA’s CX Commercial Lighting Control Panels.
LVSM1NP
LVSM1PL
PRODUCT FEATURES • Attractive, architecturally pleasing design
• Mounts to standard single-gang box
• Momentary and latching versions available
• Title 24 compliant when used as part of compliant system
• 1-4 buttons with or without LED
• Five-year limited warranty
General Specifications Electrical Ratings
Each switch: 100mA @ 30VDC Max Each pilot LED: 18-30VDC, internal 2.2kohm, ½ Watt resistor
Configurations
1 - 4 buttons, with or without pilot LED Momentary or latching (sustained)
Operating Environment
Indoor use only Operating temperature: 32° to 122°F (0° to 50°C) Relative humidity (non-condensing): 10% to 90%
Construction
Housing – Rugged, high-impact, injection-molded plastic Color-coded leads
Dimensions
1.88”W x 4.25”H x 1.56”D
Weight
3.0 oz
Color
White, Ivory, Light Almond, Gray
Mounting
Single-gang NEMA-style switch box (average switch box) Decorator-style wall plate not included
Warranty
Five-year limited
Ordering Information LVS model LVS
Switch type M Momentary L Latching
NUMBER OF BUTTONs 1 2 3 4
pilot PL w/ Pilot LEDS NP No Pilot
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
color WH White IV Ivory LA Light Almond G Gray
Pa g e 14 5
CX Light Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
CX LIGHTING CONTROL PANELS
24 VDC
VOLTAGE
The CX Light Sensor by Servodan provides the necessary daylight-level information to the CX Panel System. Using a photodiode element, this sensor continuously measures daylight levels and sends the information to the selected Luxstat daylight harvesting control module. In order to operate as a true Open Loop controller, the sensor must be positioned to see only daylight (no artificial light). You select the applicable foot-candle range by using a jumper beneath the front cover.
LUXSTATLS
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Daylight sensor for CX Panel Systems • Architecturally attractive design • Indoor and outdoor versions • Open loop operation • Foot-candle range: 3-6,000 fc • Mounts vertically or horizontally • UL and cUL listed • California Title 24 Compliant • Five-year limited warranty
1.2” 2”
Pa g e 14 6
hubbell-automation.com
45º
30º
30º
General Specifications Electrical
Four jumper-selectable foot-candle ranges: .03-30FC; 3-300FC; 30-3,000FC; 60-6,000FC 24VDC Low Votage Class 2 Device 3-conductor 22 AWG twisted cable—equal to Belden 8443
Construction
Protective hard plastic cover and housing
Dimension
2”DIA x 1.2”H
Weight
0.5 oz
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
LUXSTATLS LUXSTATLSo
Model Luxstat Light Sensor - Indoor Luxstat Light Sensor - Outdoor
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 147
CX Line V Automatic Line Voltage Switches
TITLE
24 CEC
COMPLIANT
CALIFORNIA
CX LIGHTING CONTROL PANELS
120 277 VAC
The Hubbell Building Automation Line V Automatic Line Voltage Switches provide feature cost effective lighting control for maximum energy savings. The switches operate based on timed blink patterns from the CX or LX Panels to activate internal relays ON, OFF or override an impending OFF schedule for user selectable periods of 30, 60, 90, or 120 minutes. The CX or LX Panels are designed to control the relay timed blinks to allow for a single relay to signal multiple Line V switches to perform the desired functions. The 1-Relay version has standard capability to be wired to addition switches for 3-way and 4-way operation on a single zone. The 2-Relay version allows for bi-level LINEVAS1BUNVWH
LINEVAS2BUNVWH
switching within a single zone. Signal ON can be selected for 1 or 2 relays.
PRODUCT FEATURES • Two switch configurations – 1-Relay and 2-relay • 1-Relay model controls a single zone or can be connected for 3-way and 4-way operation • 2-Relay model provides single circuit input for dual level area control • Switches are controlled ON or OFF from the CX Panel using OFF intervals from a single relay • Allows for retrofit of standard line voltage toggle switches for automatic schedule ON/OFF control • Blink warning allows user to initiate override of 30, 60, 90, or 120 minutes and
4.29”
cancel OFF event • Switches operate without the need for a neutral connection • Dual 120/277VAC operation • No minimum load requirement • Zero Arc Point Switching • ETL, UL, and cUL listed
1.8”
2.1”
• California Title 24 compliant • Five-year limited warranty
Pa g e 14 8
hubbell-automation.com
General Specifications Programming and Configuration
Programmable via DIP switches mounted on door All control functions are issued at the switch
Relays Configurations
1-Relay – Single Zone OR 3-Way/4-Way operation 2-Relays – Single circuit input for Bi-Level Control
Power Requirements
120/277VAC; 50/60Hz
Electrical Ratings
120VAC: 5.0 Amps Tungsten; 10.0 Amps Fluoresent; 1/3 HP 277VAC: 10.0 Amps Fluorescent; 1/6 HP
Load Requirements
None
Operating Environment
Indoor use only Operating temperature: 32°–104°F (0°–40°C) Relative humidity (non-condensing): 0%–95%
Construction
Casing—high-impact injection-molded plastic (UL-94-5V) Color-coded leads are 6” long
Dimensions
4.2”L x 1.8”D x 2.1”W; .37” extension
Weight
2.9 oz.
Color
White; Ivory; Light Almond; Gray; Black
Mounting
Single-gang NEMA-style switch box (average switch box) Decorator-style wall plate not included
Certifications
ETL, UL, and cUL listed
Warranty
Five-year limited
Ordering Information
model/DESCRIPTION LINEVAS1BUNVBK LINEVAS1BUNVGY LINEVAS1BUNVIV LINEVAS1BUNVLA LINEVAS1BUNVWH LINEVAS2BUNVBK LINEVAS2BUNVGY LINEVAS2BUNVIV LINEVAS2BUNVLA LINEVAS2BUNVWH
Line V Line V Line V Line V Line V Line V Line V Line V Line V Line V
120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic 120-277VAC Automatic
Switch, 1-Button, Single Relay, Single or 3-Way Black Switch, 1-Button, Single Relay, Single or 3-Way Gray Switch, 1-Button, Single Relay, Single or 3-Way Ivory Switch, 1-Button, Single Relay, Single or 3-Way Light Almond Switch, 1-Button, Single Relay, Single or 3-Way White Switch, 2-Button, Dual Relay, Single Black Switch, 2-Button, Dual Relay, Single Gray Switch, 2-Button, Dual Relay, Single Ivory Switch, 2-Button, Dual Relay, Single Light Almond Switch, 2-Button, Dual Relay, Single White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 14 9
CX Occupancy Sensors
TITLE
24 CEC
COMPLIANT
CALIFORNIA
CX LIGHTING CONTROL PANELS
120 277 VAC
The OMNI line of occupancy and vacancy sensors are available in Ultrasonic, Infrared and Multi-Tech (combines ultrasonic (US) and passive infrared (PIR)) to turn lighting on and off based on occupancy. This family of sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, Intellidapt software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
OMNIDT2000
The LightOWLTM Dual Technology Ultrasonic and Passive Infrared Sensor combines ultrasonic (US) and passive infrared (PIR) technologies to turn lighting on and off based on occupancy. Designed specifically for areas where ceiling sensors are not appropriate, this sensor features Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustments automatically. Throughout the product’s lifespan, IntelliDAPT software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation.
LODT
Ordering Information Consult the Occupancy/Vacancy Section for detailed specifications, application guidelines and product ordering.
Pa g e 15 0
hubbell-automation.com
CX Lighting Control Switches
TITLE
24 CEC
COMPLIANT
CALIFORNIA
CX LIGHTING CONTROL PANELS
LOW
24 VDC
VOLTAGE
1.6”
The HBA CX Lighting Control Switches provide manual control. The system consists of two types of switches – a Dimming Control Switch and a Master On/ Off Control Switch. The Dimmning Control switches enables users to raise and lowers light levels. The Master/Row Control switches turn all lighting ON or OFF.
4.2”
1.4” Z5-SW-MC
PRODUCT FEATURES •
Attractive, architecturally pleasing design
•
Raise/ Lower Dimming control
•
Master ON/OFF control
•
Mount to standard single or multi-gang wall boxes
•
Five-year warranty
Ordering Information
LIGHTING CONTROL SWITCHES AND CABLES Z5-SW-AVD CX Dimming Switch, White Z5-SW-MC CX Master On/Off Switch, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 151
Wireless Lighting Controls
Pa g e 15 2
Wireless Comes to Light®
The wiHUBB® Distributed Lighting Control system wirelessly controls indoor and outdoor applications including area/site lighting, parking garage lighting, and interior facility lighting. It is simple to install and configure, and provides a wireless network that can grow and change with your building’s needs. While installation of wired systems can be complicated and expensive, wiHUBB is simple to use, requiring minimal installation time and wiring costs. wiHUBB’s future proof design features a self-organizing and self-healing wireless mesh network.
Intuitive Network Technology Intelligent SmartPORTS
•
Peer-to-peer: All devices are peers and act as
repeaters, forwarding messages to ensure
•
Plug-and-play support for wiHUBB occupancy
message delivery
sensors, daylight sensors and switch stations.
•
Self-organizing: Network automatically builds
•
Automatically and intelligently provides the most
energy-efficient operation
itself •
Self-healing: Messages automatically reroute
around failed nodes
Network Protocol •
SNAP (Synapse Network Appliance Protocol)
Security •
Wired: HTTPS/SSL – The wiHUBB Access Point
connects the client browser and wiHUBB network
using Secure Socket Layer (SSL) protocol, the
standard for web security authentication.
Radio Frequency •
902-928 MHz (robust and reliable) ISM band. FCC
Part 14 Certified
•
Spread Spectrum Frequency Hopping
•
Supported distance between wireless devices:
100 meters
® WIRELESS COMES TO LIGHT® ( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax orders ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 15 3
wiHUBB® Access Point
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
®
120 VAC
WIRELESS COMES TO LIGHT®
Hubbell Building Automation’s wiHUBB® Access Point is a user friendly, webbased device for commissioning and managing up to 100 devices within the wiHUBB wireless mesh network. The wiHUBB Access Point’s integrated web server provides access to the wiHUBB network using any standard web browser – no special client side PC software required. The intuitive and easy to use Graphical User Interface (GUI) provides building owners and facility managers with the ability to schedule and control individual wiHUBB-enabled devices or groups of devices.
WIH-AP
PRODUCT FEATURES WIRELESS
• Web-based commissioning and monitoring of the wiHUBB lighting control system 902 - 928MHz Frequency Antenna
• Integrated web server provides connection via standard web browsers • Easy system access from the local network or Internet • Intuitive and easy-to-use Graphical User Interface (GUI) • Ability to schedule wiHUBB-enabled devices or groups of devices via standard or astronomical time functions • Provides On/Off and dimming control of wiHUBB-enabled devices and groups of devices • View power consumption from each device • Robust & reliable 900Mhz wireless self-organizing and self-healing
5”
mesh network • FCC certified • Five-year limited warranty
7.5”
Pa g e 15 4
hubbell-automation.com
Device Settings
General Specifications wiHUBB Network Size
Supports up to 100 wiHUBB devices. For larger network use wiHUBB Access Point 2.0 (WIH-AP2)
Power Requirements
120VAC - Plug-in power adapter included
RF Frequency
902 - 928MHz Wireless Peer-To-Peer, Self-Organizing and Self-Healing Mesh Network Spread Spectrum Frequency Hopping
RF Range
Supported distance between wireless devices: 100 meters (328 feet) Maximum Transmission Output Power: +20 dBm Maximum Receive Sensitivity: -118 dBm
Operating Environment
Operating Temperature: 0°C to 40°C (32°F to 104°F) Relative humidity (non-condensing): 0 to 95%
Construction
Housing: Flame retardant ABS plastic, UL flame rating of 94-5VA
Dimensions
5.00”L x 7.50”W x 1.75”H
Weight 6oz Color Black Mounting
Surface or Wall Mount
Patents
Patent(s) Pending
Certifications
FCC Certified IC Approved
Warranty
Five-year limited
Ordering Information WIH-AP model / Description WIH-AP
wiHUBB Access Point
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 15 5
wiHUBB® Access Point 2.0
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
®
120
WIRELESS COMES TO LIGHT®
VAC
Hubbell Building Automation’s wiHUBB® Access Point 2.0 is a user friendly, webbased device for commissioning and managing hundreds of devices within the wiHUBB wireless mesh network. The wiHUBB Access Point’s integrated web server provides access to the wiHUBB network using any standard web browser – no special client side PC software required. The intuitive and easy to use Graphical User Interface (GUI) provides building owners and facility managers with the ability to schedule and control individual wiHUBB-enabled devices or groups of devices.
WIH-AP2
WIRELESS
PRODUCT FEATURES • Web-based commissioning and management of the wiHUBB system
902 - 928MHz Frequency Antenna
• Integrated web server provides connection via standard web browsers 7.5”
• Easy system access from the local network or Internet • Intuitive and easy to use Graphical User Interface (GUI) • Ability to schedule wiHUBB-enabled devices or groups
8.26”
of devices • Provides On/Off and dimming control of wiHUBB-enabled devices and groups of devices
2.44”
120VAC Power Adapter
• View power consumption from each device • Robust & reliable 900Mhz wireless self-organizing and self-healing mesh network
Ethernet Ports
• FCC certified
Pa g e 15 6
hubbell-automation.com
Device Settings
General Specifications wiHUBB Network Size
Supports over 100 wiHUBB devices
Power Requirements
120VAC - Plug-in power adapter included
RF Frequency
902 - 928MHz Wireless Peer-To-Peer, Self-Organizing and Self-Healing Mesh Network Spread Spectrum Frequency Hopping
RF Range
Supported distance between wireless devices: 100 meters (328 feet) Maximum Transmission Output Power: +20 dBm Maximum Receive Sensitivity: -118 dBm
Operating Environment
Operating Temperature: 0°C to 40°C (32°F to 104°F) Relative humidity (non-condensing): 0 to 95%
Construction
Housing: Metal enclosure
Dimensions
Size: 8.26”L x 7.55”W x 2.44”H
Weight
3lb 6oz
Color Black Patents
Patent(s) Pending
Certifications
FCC Certified
IC Approved
Warranty
Five-year limited
Ordering Information WIH-AP2
WIH-AP2
model wiHUBB Access Point 2.0
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 15 7
wiHUBB® Smart Pack
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
®
120 277
WIRELESS COMES TO LIGHT®
VAC
Hubbell Building Automation’s wiHUBB® Smart Pack is a self-contained intelligent wireless power pack. It contains either one or two independently controlled outputs. The two output version can be used for High/Low or alternate circuit switching. An optional 0-10VDC output is also available for full range dimming control of dimmable ballasts and LED drivers. Each wiHUBB Smart Pack can control one or more circuits and can be individually controlled or grouped with other wiHUBB devices. The wiHUBB Smart Pack also features SmartPORT technology that provides plugand-play support for wiHUBB occupancy sensors and manual control switches. When devices are plugged into the SmartPORTs, the Smart Pack automatically and WIH-SP-2RD-1277
intelligently responds to the devices to provide the most energy-efficient operation. The wiHUBB Smart Pack communicates via 900MHz radio frequency to other devices within the wiHUBB wireless self-organizing and self-healing mesh network.
PRODUCT FEATURES WIRELESS
•
Single or dual relay versions for On/Off or High/Low control
•
Optional 0 – 10V interface for full range dimming control
•
Plug-and-play support for wiHUBB occupancy sensors,daylight
0-10V DIMMING
sensors and switch stations •
Device intelligently and automatically responds to sensors and switches in the most energy- efficient manner
•
Schedules are held in the devices themselves – no need for a master scheduling device
•
Retains data during power outages
•
Robust & reliable 900MHz wireless self-organizing and self-healing mesh network
•
Future-proof design – firmware updateable over the air
•
FCC certified
•
Five-year limited warranty
900MHZ Radio Antenna
3.85”
1.3”
5.75” Plug and Play SmartPORTs
Pa g e 15 8
hubbell-automation.com
General Specifications Electrical Ratings Input: 120/277VAC, 20A Max, 60Hz Output*: 20A, Tungsten, 120VAC only 20A, Magnetic Ballast 16A, Electronic Ballast 1 H.P. Motor @120V, 3/4 H.P. @277V *For (2) relay models the maximum combined output of both relays: 20A
Low Voltage Ports:
Class 2 24VDC, 150mA MAX (all outputs combined)
Optional Dimming Interface
0-10V, 30mA output For use with low-voltage, two-wire dimming ballast and LED drivers.
RF Frequency
902 - 928MHz Wireless Peer-To-Peer, Self-Organizing and Self-Healing Mesh Network Spread Spectrum Frequency Hopping
RF Range
Supported distance between wireless devices: 100 meters (328 feet) Maximum Transmission Output Power: +20 dBm Maximum Receive Sensitivity: -118 dBm
Operating Environment
Operating Temperature: 0°C to 40°C Relative humidity (non-condensing): 0 to 95%
Construction
Housing: GSM UL Rated 94 HB Plastic
Plenum Rated
Complies with requirements for use in a plenum area Plenum rated for external junction box mounting
Dimensions
5.75”L x 3.85”W x 1.30”H
Weight
4 oz
Color Gray Mounting
Mounts directly to an external junction box through an extended ½” chase nipple.
Patents
Patent(s) Pending
Certifications
Conforms with UL916 and Certified to CAN/CSA C22.2 No. 205-M1983 FCC Certified IC Approved
Warranty
Five-year limited
Ordering Information WIH-sp model WIH-sp
1277 Output 1R 1RD 2R 2RD
1 SPST Output 1 SPST Output, 0-10VDC Dimming Output 2 SPST Outputs 2 SPST Outputs, 0-10VDC Dimming Output
input voltage 120/2777VAC 1277
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 15 9
wiHUBB® Ceiling Mount and Wall Mount Sensors
TITLE
24 CEC
®
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
WIRELESS COMES TO LIGHT®
Hubbell Building Automation’s wiHUBB® Ceiling Mount and Wall Mount Occupancy Sensors employ passive infrared, ultrasonic, and acoustic sensing technologies to turn lighting on and off based on occupancy. These sensors represent the state-of-the-art in sensor technology and are designed to provide accurate turn-on while virtually eliminating false-offs. The sensors feature Hubbell Building Automation’s patented IntelliDAPT® technology, which makes all the sensor adjustments automatically. Throughout the
WIH-OS-OMDT2
product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install and forget operation. All wiHUBB Occupancy Sensors provide plug-and-play integration with the wiHUBB Smart Pack.
WIH-OS-LODT
PRODUCT FEATURES
OCCUPANCY SENSING
•
IntelliDAPT® self-adaptive technology – no manual adjustment required
•
All-digital dual technology (ultrasonic [US] and passive infrared [PIR]) sensor
•
Non-volatile memory for sensor settings
•
500 to 2,000 square-foot coverage area (based on model)
•
Optional Isolated Form C relay with N/O + N/C outputs
•
Plug and play integration with wiHUBB Smart Pack
•
UL and cUL listed
•
Five-year limited warranty
Pa g e 16 0
IntelliDAPT
hubbell-automation.com
General Specifications IntelliDAPT Technology
Auto reset from test setting Self-adjusting timer Self-adjusting ultrasonic and passive infrared thresholds Automatic false-on, false-off corrections
LED Indicators
Red: motion detected by Passive Infrared sensing technology Green: motion detected by Ultrasonic sensing technology
Timer Timeout
Automatic mode: 8-30 min. (self-adjusts based on occupancy) Test mode: 8 seconds (for an easy check at installation)
Ultrasonic Output
Maximum amount of radiation output allowed: 115dB @ 1 ft. from source Frequency: 32.768kHz or 40kHz (based on model)
Passive Infrared
Dual element pyrometer and 12 element cylindrical rugged lens
Form C Relay
Relay: NO + NC contacts, SPDT, 500 mA rated @ 24VDC, three wire, isolated relay
Coverage
Ceiling mount sensor: 500 sq. ft. (Major motion) / 250 sq. ft. (Minor motion) to 2000 sq. ft. (Major motion) / 1000 sq. ft. (Minor motion) –(based on model) Wall mount sensor: 1600 sq. ft. (Major motion) / 800 sq. ft. (Minor motion)
Power Requirements
Powered by wiHUBB Smart Pack SmartPORT using plenum rated CAT5 cables (ordered separately)
Operating Environment
Indoor use only Operating Temperature: 0°C to +40°C Relative humidity (non-condensing): 0 to 95%
Construction
Casing – rugged, high-impact, injection-molded plastic KJB ABS Cycolac (UV-945VA) flame class rating, UV inhibitors
Color
Off White
Mounting
Mounting base provided Recommended MAX mounting height: 12 ft.
Patents
U.S. Patents: 6151529, 5946209, 5699243, 5640143, 6415205, 6078253, D404326, 6222191, 5986357, 6759954 Patent(s) Pending
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information WIH-OS
model WIH-OS
SENSOR TYPE OMDT2 OMDT2R OMDT1 OMDT1R OMDT5 OMDT5R OMUS2 OMUS2R OMUS1 OMUS1R OMUS5 OMUS5R OMIR OMIRR OMIRL OMIRLR OMDIA OMDIAR LODT LODTR LOIRWV LOIRWVR LOIRHB LOIRHBR LODIA LODIAR
Ceiling Mount, PIR and Ultrasonic, 2000 Sq. Ft. Ceiling Mount, PIR and Ultrasonic, 2000 Sq. Ft., Form C Relay Ceiling Mount, PIR and Ultrasonic, 1000 Sq. Ft. Ceiling Mount, PIR and Ultrasonic, 1000 Sq. Ft., Form C Relay Ceiling Mount, PIR and Ultrasonic, 500 Sq. Ft. Ceiling Mount, PIR and Ultrasonic, 500 Sq. Ft., Form C Relay Ceiling Mount, Ultrasonic, 2000 Sq. Ft. Ceiling Mount, Ultrasonic, 2000 Sq. Ft., Form C Relay Ceiling Mount, Ultrasonic, 1000 Sq. Ft. Ceiling Mount, Ultrasonic, 1000 Sq. Ft., Form C Relay Ceiling Mount, Ultrasonic, 500 Sq. Ft. Ceiling Mount, Ultrasonic, 500 Sq. Ft., Form C Relay Ceiling Mount, Passive Infrared, 450 Sq. Ft. Ceiling Mount, Passive Infrared, 450 Sq. Ft., Form C Relay Ceiling Mount, Passive Infrared, 1500 Sq. Ft. Ceiling Mount, Passive Infrared, 1500 Sq. Ft., Form C Relay Ceiling Mount, PIR and Acoustic, 450 Sq. Ft. Ceiling Mount, PIR and Acoustic, 450 Sq. Ft., Form C Relay Wall Mount, PIR and Ultrasonic, 1600 Sq. Ft. Wall Mount, PIR and Ultrasonic, 1600 Sq. Ft., Form C Relay Wall Mount, Passive Infrared, 2500 Sq. Ft. Wall Mount, Passive Infrared, 2500 Sq. Ft., Form C Relay Wall Mount, Passive Infrared, 50’ at 30’ Height Wall Mount, Passive Infrared, 50’ at 30’ Height, Form C Relay Wall Mount, PIR and Acoustic, 1600 Sq. Ft. Wall Mount, PIR and Acoustic, 1600 Sq. Ft., Form C Relay
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 161
wiHUBB® Switch Stations WIRELESS LIGHTING CONTROLS
®
LOW
24 VDC
WIRELESS COMES TO LIGHT®
VOLTAGE
Hubbell Building Automation’s wiHUBB® Switch Stations provide manual control of the wiHUBB System. The wiHUBB Switch Stations include an On/Off switch, a High/Low/Off switch for multiple level lighting control, an On/Raise/Lower/ Off switch, a 4-button Preset switch for scene control, a General–A/V switch that enables users to switch between General Lighting and Audio/Visual Lighting, a Raise/Lower dimmer switch and a Timed On switch. All wiHUBB Switch Stations WIH-SW-HLO
WIH-SW-ORLO
WIH-SW-GAV
WIH-SW-RL
provide plug-and-play integration with the wiHUBB Smart Pack.
WIH-SW-PRESET
WIH-SW-TO
PRODUCT FEATURES •
Attractive, architecturally-pleasing decorator style design
•
Multiple switch options available
•
All switches mount to standard single or multi-gang wall boxes
•
Plug-and-play integration with wiHUBB Smart Pack
•
Five-year limited warranty
1.6”
Fits Standard Decorator Style Wallplate (sold separately)
On/Off Switches
4.2”
1.4” WIH-SW-OO
Pa g e 16 2
hubbell-automation.com
General Specifications Power Requirements
Powered by wiHUBB Smart Pack SmartPORT using plenum rated CAT5 cables (ordered separately)
Operating Environment
Indoor use only Operating Temperature: 0°C to 40°C Relative humidity (non-condensing): 0 to 95%
Construction
Housing – Rugged, high impact, injection molded plastic
Dimensions
4.2”L x 1.6”W x 1.4”D
Weight
1.6 oz
Color
White, Ivory, Light Almond, Gray, and Black
Mounting
Switches may be mounted individually in a single gang switch box or ganged together in a multi-gang switch box Decorator-style wall plates available separately
Patents
Patent(s) Pending
Warranty
Five-year limited
Ordering Information WIH-sw model WIH-sw
Switch type OO HLO ORLO PRESET GAV RL TO
On/Off Switch High/Low/Off Switch On/Raise/Lower/Off Switch Preset/Scene Switch (4-button) General – A/V Mode Switch Raise/Lower Switch Timed On Switch
color wh IV LA GY BK
White Ivory Light Almond Gray Black
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 16 3
wiHUBB® In-Fixture Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
120 277 VAC
®
347
WIRELESS COMES TO LIGHT®
VAC
Hubbell Building Automation’s wiHUBB® In-Fixture Module (IFM) is a self-contained intelligent wireless control module. It contains either one or two independentlycontrolled outputs. The two-output version can be used for High/Low or alternate ballast switching.
WIH-IM-1RDFF-1277
An optional 0-10V output is also available for full-range dimming control of dimmable ballasts and LED drivers. Each wiHUBB IFM can control one or more fixtures and can be individually controlled or grouped with other wiHUBB devices. The wiHUBB IFM communicates via 900MHz radio frequency to other devices within the wiHUBB wireless self-organizing and self-healing mesh network.
PRODUCT FEATURES
WIRELESS
0-10V DIMMING
• Single or dual relay versions for On/Off or High/Low control • Optional 0 – 10V interface for full range dimming control • Device intelligently and automatically responds to sensors and switches in the most energy-efficient manner • Schedules are held in the devices themselves – no need for a master scheduling device
1.27”
• Monitors, measures, and records energy consumption and runtime data
1.08”
• Retains data during power outages • Robust & reliable 900MHz wireless self-organizing and self-healing mesh network
4.5” 5.5”
• Future-proof design – firmware updateable over the air • Multiple antenna options available • FCC certified • Five-year limited warranty
Pa g e 16 4
hubbell-automation.com
General Specifications Electrical Ratings (-1277 version) Input: 120-277VAC, 10A Max, 60Hz Output: 10A, Tungsten, 120VAC only 10A, Magnetic Ballast 5A, Electronic Ballast (max each relay) ¼ H.P. Motor, 120 & 277VAC For (2) relay models the maximum combined output of both relays: 10A Electrical Ratings (-347 version) Input: 347VAC, 10A Max, 60Hz Output: 10A, Ballast For (2) relay models the maximum combined output of both relays: 10A Optional Dimming Interface
0-10V, 30mA output for use with low-voltage, two-wire dimming ballast and LED drivers.
RF Frequency
902 - 928MHz Wireless Peer-To-Peer, Self-Organizing and Self-Healing Mesh Network Spread Spectrum Frequency Hopping
RF Range
Supported distance between wireless devices: 100 meters (328 feet) Maximum Transmission Output Power: +20 dBm Maximum Receive Sensitivity: -118 dBm
Operating Environment
Operating Temperature: -40°C to +90°C Relative humidity (non-condensing): 0 to 95%
Construction
Housing: GSM UL Rated 94 HB Plastic
Dimensions
5.50”L x 1.27”W x 1.08”H
Weight
4 oz
Color Gray Mounting
Mounts inside fixture ballast cavity or housing Optional mounting adaptor available (p/n WIH-IM-ADAPTER) for external junction box mounting
Certifications
Conforms with UL916 and Certified to CAN/CSA C22.2 No. 205-M1983 FCC Certified IC Approved
Warranty
Five-year limited
Ordering Information WIH-IM model WIH-IM
Output 1RA 1RDA 1RF 1RDF 2RA 2RDA 2RF 2RDF
1 SPST Output, Articulating Antenna 1 SPST Output, 0-10VDC Dimming Output, Articulating Antenna 1 SPST Output, Fixed Antenna with 24” Extension Cable 1 SPST Output, 0-10VDC Dimming Output, Fixed Antenna with 24” Extension Cable 2 SPST Outputs, Articulating Antenna 2 SPST Outputs, 0-10VDC Dimming Output, Articulating Antenna 2 SPST Outputs, Fixed Antenna with 24” Extension Cable 2 SPST Outputs, 0-10VDC Dimming Output, Fixed Antenna with 24” Extension Cable
input voltage 1277 120/277VAC 347 347VAC
Accessory WIH-IM model WIH-IM
Adapter
Adapter
Accessory In-Fixture Module J-Box Mounting Adapter
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 16 5
wiHUBB® ON-FIXTURE MODULE
TITLE
24 CEC
120 347
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
®
480
VAC
VAC
WIRELESS COMES TO LIGHT®
Hubbell Building Automation’s wiHUBB® On-Fixture Module (OFM) is a selfcontained intelligent wireless control module that provides On/Off lighting control for outdoor fixtures. Each OFM contains an integrated daylight sensor that can be used to turn lighting ON or OFF based on the amount of natural light available. Each wiHUBB OnFixture Module can be individually controlled or grouped with other wiHUBB devices. The wiHUBB OFM communicates via 900MHz radio frequency to other devices within the wiHUBB wireless self-organizing and self-healing mesh network.
WIH-OM-UNV
PRODUCT FEATURES WIRELESS
• On/Off outdoor lighting control • Compatible with all lighting loads including LED drivers • Integrated daylight sensor
3.50”
• Schedules are held in the devices themselves – UV Stabilized Material
master scheduling device not necessary • Retains device settings during power outages • Robust & reliable 900MHz wireless self-organizing
902 - 928MHz Frequency Antenna
2.275”
Photocell
and self-healing mesh network • FCC certified • Five-year limited warranty
Twist Lock Plug
Pa g e 16 6
hubbell-automation.com
General Specifications Electrical Ratings
Input: - WIH-OM-UNV:120-347VAC, 50/60Hz - WIH-OM-480: 480VAC, 50/60Hz Output: 20A, Tungsten, Magnetic and Electronic Ballast
RF Frequency
902 - 928MHz Wireless Peer-To-Peer, Self-Organizing and Self-Healing Mesh Network Spread Spectrum Frequency Hopping
RF Range
Supported distance between wireless devices: 100 meters (328 feet) Maximum Transmission Output Power: +20 dBm Maximum Receive Sensitivity: -118 dBm
Daylight Sensor
ON Level: 1 FC to 5 FC (Default: 5FC) OFF Level: 4 FC to 15 FC (Default: 8FC) ON/OFF Delay Times: 0-120 secs (Default: 60 secs)
Operating Environment
Operating Temperature: -40°C to +90°C (-40°F to +194°F)
Construction
Housing: GSM UL Rated 94 HB Plastic
Dimensions Weight
3.50”DIA x 2.275”H 4 oz
Color
Smoked Plastic Housing
Mounting
Standard twist lock photo-sensor receptacle
Patents
Patent(s) Pending
Certifications
Conforms with UL916 and Certified to CAN/CSA C22.2 No. 61010-1-04 FCC Certified IC Approved
Warranty
Five-year limited
Ordering Information WIH-OM model
WIH-OM
UNV 480
input voltage 120-347VAC, 50/60Hz 480VAC, 50/60HZ
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 167
wiHUBB® Building Automation System Gateway Interface
TITLE
24 CEC
®
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
WIRELESS COMES TO LIGHT®
Hubbell Building Automation’s wiHUBB® Building Automation System (BAS) Gateway Interface is an external, high performance, low cost, multi-protocol gateway for providing control and access from building automation systems to HBA’s wiHUBB Wireless Lighting Control System. The device provides protocol translation between wiHUBB and BAS devices using BACnet®, Metasys® N2 by JCI, and Modbus™. The wiHUBB BAS Gateway is based on the industry leading FieldServer Technologies™ ProtoCessor ProtoNode technology and is preconfigured with the wiHUBB system protocol interface.
WIH-BAS-M
PRODUCT FEATURES • Web browser based programming
3.25”
• Intuitive and easy to use Graphical User Interface (GUI) • Device is field selectable for specific BAS protocol • Sophisticated user account/password manager • Integrates wiHUBB lighting control systems and Building Automation Systems (BAS) • Supports BACnet®, Metasys® N2 by JCI, Modbus™ and LonWorks® protocols • Automatically generates all required control points and documentation for integration with the selected protocol
4.52”
• Five-year limited warranty
Ethernet Port
1.6”
Pa g e 16 8
hubbell-automation.com
BAS Integration
Ethernet Port 24 VDC Power WIH-BAS
LXPWRSPLY Power Supply
Mount all components inside HBA p/n LXENDM DIN rail enclosure. (LXENDM is ordered separately)
General Specifications Supported wiHUBB® Access Point
Access Point 2.0 required (Ordered Separately)
Supported Serial (RS-485) Protocols Supported Ethernet Protocols
BACnet MS/TP Modbus RTU BACnet IP Modbus TCP/IP
JCI Metasys® N2OPEN
Supported Electrical Connections
(1) 6 pin Phoenix Connector (1) RS-485 +/- Ground port Power +/- Frame Ground port (1) Ethernet -10/100 Ethernet port
(1) FTT-10 LonWorks® port (LonWorks® Version) Power Requirements
9-30 VDC or 12-24VAC
Current draw @ 12V = 240 mA
Operating environment
Indoor use only -40°C to 75°C (-40°F to 167°F) Relative humidity (non-condensing): 5% to 90%
Dimensions
4.52”L x 3.25”W x 1.60”H
Approvals
BACnet Testing Labs (BTL) B-ASC LonMark 3.4 Certified – WIH-BAS-L Version TUV approved to UL 916 standard and CSA C22-2 RoHS Compliant DNP3 Conformance Tested OPC Self Certified to Compliance CE & FCC Approved
Warranty
Five-year limited
Ordering Information WIH-BAS model WIH-BAS
M
L
model wiHUBB Building Automation System Gateway Interface for Multi-Protocols - BACNET, Modbus, N2 wiHUBB Building Automation System Gateway Interface for LonWorks®
Metasys® is a registered trademark of Johnson Controls, Inc. LonWorks® is a registered trademark of Echelon Corp. BACnet® is a registered trademark of ASHRAE
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 16 9
wiHUBB® Antennas and Cables WIRELESS LIGHTING CONTROLS
® WIRELESS COMES TO LIGHT®
Hubbell Building Automation’s wiHUBB® Antennas are designed to be used with the wiHUBB In-Fixture Module and wiHUBB Smart Pack. The wiHUBB Articulating Antenna and the wiHUBB Fixed Antenna-HW are ½-wave center-fed DIPole antennas. The Articulating Antenna’s base allows the antenna to tilt 90 degrees and rotate 360 degrees. The Articulating Antenna and Fixed Antenna-HW’s internal counterpoise eliminates external ground plane dependence and maximizes performance. The wiHUBB Fixed Antenna is a ¼-wave center-fed monopole antenna that utilizes a helical element to greatly reduce the physical length of the antenna housing. WIH-AT-FA
PRODUCT FEATURES • Multiple antenna options available • Excellent performance • Omni-directional pattern • Fully weatherized • Rugged and damage-resistant • Five-year limited warranty
WIH-AT-FA
WIH-AT-AA WIH-AT-FA-HW
Pa g e 17 0
hubbell-automation.com
General Specifications Antenna Type Center Frequency
Dipole – No ground plane required: WIH-AT-AA, WIH-AT-FA-HW Monopole – Requires an external proximity ground plane for proper operation: WIH-AT-FA. NOTE: 4”x4” ground plane centered around the antenna base recommended.
916MHz
Wavelength ½-wave: WIH-AT-AA, WIH-AT-FA-HW ¼-wave: WIH-AT-FA Voltage Standard Wave Ration (VSWR)
<2.0 typical at center: WIH-AT-AA <1.9 typical at center: WIH-AT-FA-HW, WIH-AT-FA
Impedance
50 ohms
Connector RP-SMA Dimensions
WIH-AT-AA: 5.59”H x 0.32”W with 90° tilt and 360° rotation WIH-AT-FA: 2.00”H x 0.31”W WIH-AT-FA-HW: 4.72”H x 0.32”W
Color Black Warranty
Five-year limited
Ordering Information Antennas WIH-AT model WIH-AT
aa FA FA-36 FA-48 FA-HW
Articulating Antenna, Dipole – No Ground Plane Required, 5.59” H with 90° Bend Fixed Antenna, Monopole – Requires Ground Plane, 2.00” H, with 24” cable & mounting hardware Fixed Antenna, Monopole – Requires Ground Plane, 2.00” H, with 36” cable & mounting hardware Fixed Antenna, Monopole – Requires Ground Plane, 2.00” H, with 48” cable & mounting hardware Fixed Antenna, Dipole – No Ground Plane Required, 4.72” H
Antenna Cables WIH-AT model WIH-AT
TYPE CAB24IN CAB36IN CAB48IN
Antenna Cable, 24” cable (Includes mounting hardware) Antenna Cable, 36” cable (Includes mounting hardware) Antenna Cable, 48” cable (Includes mounting hardware)
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 171
RJ45 Adapter and CAT5 System Cables WIRELESS LIGHTING CONTROLS
LOW
®
24
WIRELESS COMES TO LIGHT®
VDC
VOLTAGE
Hubbell Building Automation’s RJ45 Adapter and CAT5 system cables are designed to be used with HBA low voltage occupancy and daylight sensors. The adapter replaces the QuickTo-Install™ (QTI) connectors previously used by the wiHUBB® and Zone5™ occupancy and daylight sensors and enables devices to connect to HBA control modules (e.g. wiHUBB Smart Pack, Zone5 Control Module, etc) using standard CAT5 cable.
RJ45Adapter
PRODUCT FEATURES • • •
Supports wiHUBB and Zone5 occupancy and daylight sensors Plenum rated Five-year limited warranty
General Specifications Electrical
4 Terminal Connections
- Red: +24V
- Blue: Occupancy Sensor Input
- Yellow: Photocell/Daylight Sensor Input
- Black: Common
Class 2 device
Max Cable Length Supported: 300-ft from device to control module
Plenum Rated
Complies with requirements for use in a plenum area
Construction
Material: SABIC NORYL HS2000X
Dimensions
2.168”L x 1.093”W x 0.995”H
Weight
0.8 oz
Color Gray Mounting
Adapter may be mounted using a zip-tie (not included) or with a #8 or #10 mounting screw (not included)
Warranty
Five-year limited
Pa g e 17 2
hubbell-automation.com
Ordering Information RJ45 Adapter
model/DESCRIPTION RJ45ADAPTER RJ45ADAPTER-10 RJ45ADAPTER-50
RJ45 Adapter RJ45 Adapter - 10 Pack RJ45 Adapter - 50 Pack
CAT5 System Cables
model CAT5-3IN-BL CAT5-10F-BL CAT5-50F-BL CAT5-100F-BL CAT5-10F-WH CAT5-50F-WH CAT5-100F-WH CAT5-10F-GN CAT5-50F-GN CAT5-100F-GN CAT5-3IN-YL CAT5-50F-YL CAT5-100F-YL
CAT5 Jumper Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 3in, Blue CAT5 Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 10ft, Blue CAT5 Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 50ft, Blue CAT5 Cable for wiHUBB & Zone5 Lighting Control Switches, Plenum Rated, 100ft, Blue CAT5 Cable for wiHUBB & Zone5 Occupancy & WASP2 Sensors, Plenum Rated, 10ft, White CAT5 Cable for wiHUBB & Zone5 Occupancy & WASP2 Sensors, Plenum Rated, 50ft, White CAT5 Cable for wiHUBB & Zone5 Occupancy & WASP2 Sensors, Plenum Rated, 100ft, White CAT5 Cable for wiHUBB & Zone5 Daylight Sensors, Plenum Rated, 10ft, Green CAT5 Cable for wiHUBB & Zone5 Daylight Sensors, Plenum Rated, 50ft, Green CAT5 Cable for wiHUBB & Zone5 Daylight Sensors, Plenum Rated, 100ft, Green CAT5 Jumper Cable for Zone5 Master/Row Control Switches, Plenum Rated, 3in, Yellow CAT5 Cable for Zone5 Master/Row Control Switches, 50ft, Yellow CAT5 Cable for Zone5 Master/Row Control Switches, 100ft, Yellow
Special Notes: 1. When cutting CAT5 cable to specific lengths, the cable pin out is as follows: Pin No. 1 2 3 4 5 6 7 8
Wire Color WHITE with ORANGE STRIPE ORANGE WHITE with GREEN STRIPE BLUE WHITE with BLUE STRIPE GREEN WHITE with BROWN STRIPE BROWN
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 17 3
wiHUBB® Daylight Sensors
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
®
TESTED & APPROVED
IP 54
WIRELESS COMES TO LIGHT®
WATER-DUST RESISTANT
Hubbell Building Automation’s wiHUBB® Daylight Sensors provide the necessary daylight-level information to the wiHUBB network. Using a photodiode element, the daylight sensor continuously measures daylight levels and sends the information to the network devices which then perform daylight switching or dimming functionality based on the amount of natural light in the area.
WIH-DS
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Indoor and Outdoor models available
• Mounts vertically or horizontally
• Architecturally attractive design
• Color coded, plug-and-play integration with wiHUBB Smart Pack
• Open loop operation
• UL and cUL listed
• Foot-candle range: 3-6,000fc
• Five-year limited warranty
General Specifications Electrical
Four jumper-selectable foot candle ranges: 0.3-30fc; 3-300fc; 30-3,000fc; 60-6,000fc
Powered by wiHUBB Smart Pack SmartPORT using plenum rated CAT5 cables (ordered separately)
Operating Environment
WIH-DS: Indoor use only. Operating Temperature: 0°C to +40°C
WIH-DS-O: Outdoor Use - IP54. Operating Temperature: -40°C to +50°C
Construction
Protective hard plastic cover and housing
Dimensions
2”D x 1.2”H
Certifications
UL and cUL listed
Warranty
Five-year limited
Ordering Information
model / Description WIH-DS wiHUBB Daylight Sensor WIH-DS-O wiHUBB Daylight Sensor for Outdoors
Pa g e 174
hubbell-automation.com
TM
Seamless Area Lighting
wiSTARâ&#x201E;˘ is a wireless, self-powered lighting control system designed for stand-alone, indoor applications such as offices, conference rooms, break rooms, classrooms and much more. From retrofitting older structures to designing new buildings, wiSTAR is a simple way to ensure flexibility, energy savings, and cost reductions to almost any space.
No Batteries Utilizing the EnOcean Technology Platform, wiSTAR devices harvest energy from their surroundings â&#x20AC;&#x201C; tiny changes in movement or light are all that is needed. The wall switches use the linear motion of the button push to create the power needed to send a signal to operate the lights. Sensors have tiny solar cells that convert light into the power they need to do the same thing. These solar cells work off of any light source and the converted energy is stored for operation during times with no light.
No Wires wiSTAR devices are self-powered and require no wires to operate. These devices can be freely positioned making for versatile layouts. Compared to a wired solution, buildings can be planned, constructed and operated with greater flexibility and at a lower cost.
No Worries With wireless technology, wiSTAR installs easily into existing buildings without the need to completely rewire the space. This makes wiSTAR ideal for adding lighting controls to areas that have traditionally been difficult to retrofit, including historical buildings.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax orders ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 17 5
wiSTARtm In-line Switch Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
TM
120 277 VAC
A simple solution for wireless control of lighting and appliances. Hubbell Building Automation’s wiSTAR™ In-line Switch Module uses radio frequency technology to communicate with other wiSTAR products and provides an amazingly simple solution for control of lighting and other electrical loads. The module’s compact size enables flexible installation inside of or next to electrical boxes and fixtures so it can be easily wired out of sight using standard wiring practices. Simply link the module to a wiSTAR occupancy sensor, switch or light sensor and experience levels of efficiency and convenience that can only be achieved through wireless controls.
WIS-ISM
PRODUCT FEATURES WIRELESS
• Switches lighting or other electrical loads On/Off • Installs inside or mounts to electrical box using threaded connector • Easily links with wireless sensors and switches
Compact Casing
• Five-year limited warranty
Device Configuration and Manual Control Buttons with LEDs
2.78”
1.1”
Pa g e 176
1.65”
hubbell-automation.com
General Specifications Power Supply
120/277VAC, 50/60Hz
Maximum Load
General Purpose – 16A @ 120/277VAC Resistive – 16A @ 120/277VAC Tungsten – 960W @ 120VAC Ballast - 600W @ 120VAC
Motor Load Rating - ½ HP @ 120VAC
Power Consumption
1.1W @ full load, 500mW quiescent
Inputs/Outputs
Flying-lead style power input wires 1 normally open relay 1 switched output wire Radio Frequency (RF) transceiver 2 Buttons with LEDs for device configuration and manual control
RF Communications
EnOcean 902 MHz
Transmission Range
80ft. (25m)
Dimensions
2.78”H x 1.65”W x 1.1”D
Weight
3.2 oz.
Mounting Install inside standard electrical box Connect to electrical box and fixutes using 1/2” threaded nipple Environment
Indoor use only 32° to 131° F (0° to 55° C) 20% to 95% relative humidity (non-condensing)
Agency Compliance
Conforms to UL Std. 244A and 1472 Certified to CAN/CSA Std. C22.2 NO 184 FCC: SZV-STM300U IC: 5713A-STM300U
Warranty
Five-year limited
Interoperable Products / EEPs (EnOcean Equipment Profiles)
Product Name (EEP #) Rocker Pad Switch (F6-02-02) Key Card Switch (F6-04-01) Window handle (F6-10-00) 1BS Single Input Contact (D5-00-01) Temperature Sensor, 0° to 40° C (A5-02-05) Occupancy Sensor (A5-07-01) Contact, single input (A5-30-01) Central Gateway (A5-38-08)
Ordering Information WIS-ISM-WH
model WIS-ISM-WH
wiSTAR In-line Switch Module, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 17 7
wiSTARtm Plug-in Switch Module
TITLE
24 CEC
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
TM
120 VAC
A simple solution for wireless control through any standard outlet. Controlling lamps and electronics in any room is simple when you use Hubbell Building Automation’s wiSTAR™ Plug-In Switch Module. The module uses radio frequency technology to communicate wirelessly with other wiSTAR devices and provides convenient control of lighting and electronic appliances. Simply plug the module into any standard outlet and then plug the lamp or other electronic device into the receptacle on the opposite end. Link the module to a wiSTAR switch or occupancy sensor for convenient wireless control.
WIS-PSM
PRODUCT FEATURES WIRELESS
• Provides switching of plug-in electrical loads • Communicates with other devices to enable energy savings • Plugs into any standard outlet, no wiring required • Easily links with wireless sensors and switches • Five-year limited warranty 4.09”
Device Configuration and Manual Control Buttons with LEDs 1.26”
1.85”
Pa g e 17 8
hubbell-automation.com
General Specifications Power Supply
120VAC, 50/60Hz
Power Consumption
1.1W @ full load, 500mW quiescent
Inputs/Outputs
Standard male plug for power input Standard female plug for controlled output 1 normally open relay Input for accessory tabletop rocker pad Radio Frequency (RF) transceiver 2 Buttons with LEDs for device configuration and manual control
Maximum Load
General Purpose – 15A @ 120VAC Resistive – 15A @ 120VAC Tungsten – 960W @ 120VAC Ballast - 600W @ 120VAC Motor Load Rating - ½ HP @ 120VAC
RF Communications
EnOcean 902 MHz
Transmission Range
80ft. (25m)
Dimensions
4.09”H x 1.85”W x 1.26”D
Weight
12.3oz. (348g)
Cord Lengths
Plug cord: 3ft. (91.4cm)
Outlet cord: 1 ft. (30.5cm)
Mounting
Free standing, or mounts to wall using included mounting plate
Environment
Indoor use only 32° to 131° F (0° to 55° C) 5% to 95% relative humidity (non-condensing)
Agency Compliance
Conforms to UL Std. 244A and 1472 Certified to CAN/CSA Std. C22.2 No. 184 FCC: SZV-STM300U IC: 5713A-STM300U
Warranty
Five-year limited
Interoperable Products / EEPs (EnOcean Equipment Profiles)
Product Name (EEP #) Rocker Pad Switch (F6-02-02) Key Card Switch (F6-04-01) Window handle (F6-10-00) 1BS Single Input Contact (D5-00-01) Temperature Sensor, 0° to 40° C (A5-02-05) Occupancy Sensor (A5-07-01) Contact, single input (A5-30-01) Central Gateway (A5-38-08)
Ordering Information WIS-PSM-WH
model WIS-PSM-WH
wiSTAR Plug-In Switch Module, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 17 9
wiSTARtm Light Sensor
TITLE
24 CEC
TM
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
Hubbell Building Automation’s wiSTAR™ Wireless Light Sensor has built-in solar cells that draw on available ambient light to power itself and can operate for up to 7 days in total darkness. Batteries are not required for continuous operation. The Light Sensor is designed to operate in closed loop applications for light levels from 0 to 94.8 footcandles (0 to 1020 LUX). This is a revolutionary product for daylight harvesting applications to meet energy saving initiatives. Optimally place the sensor in the desired lighted space, pair it with a receiver for load control and your installation is complete. The selfpowered wireless light sensor design also overcomes the placement and coverage challenges of traditional light sensors. They may be mounted wherever needed WIS-DSM
without moving or installing new wiring or conduit.
PRODUCT FEATURES WIRELESS
DAYLIGHT HARVESTING
NO BATTERIES OR POWER REQUIRED
• Daylight Harvesting with both switched and dimmed capabilities • Self-Powered & Self-Charging • No Batteries or External Power Required • Quick Charge Time to Operation • Up to 7 days of Stored Power • Five-year limited warranty
Pa g e 18 0
Solar Cells
hubbell-automation.com
General Specifications Frequency
902 MHz
Photocell
0 to 94.8FC (0 to 1020 LUX)
Transmission Interval
Upon > 20FC (200LUX) changes
Minimum Light Required
4FC (40 LUX)
Solar Cell Operating Range
4 to 100FC (40 to 1000 LUX)
Minimum Charge Time to Begin Operation
1 minute @ 20FC (200 LUX)
Full Charge Time
~8 hours @ 100FC (1000 LUX)
Maintain Charge Time
3 hours per 24 hours @ 20FC (200 LUX)
Operation Life at Full Charge
7 Days
Optional Battery Life
10 Years
Operating Temperature Range
32°F to 104°F (0°C to 40°C)
Storage Temperature Range
-4°F to 158°F (-20°C to 70°C)
Relative Humidity
0% to 95%, non-condensing
Usage
Indoor use only
Mounting Height
8-12 feet
Warranty
Five-year limited
Ordering Information WIS-DSM-WH
model WIS-DSM-WH
wiSTAR Daylight Sensor Module, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 18 1
wiSTARtm Ceiling Mounted Occupancy Sensor
TITLE
24 CEC
TM
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
Saving energy without sacrificing comfort can be effortless with occupancy based controls. Hubbell Building Automation’s wiSTAR™ Ceiling Mounted Occupancy Sensor enables a new level of energy saving control for rooms, hallways and other common areas. The occupancy sensor uses radio frequency technology to communicate wirelessly with other wiSTAR devices to turn off lights and electrical loads when a space has been unoccupied for a set period of time. Because the sensor is wireless there is no need to run additional wiring and installation can be completed in a matter of minutes. The sensor is self-powered by harvesting light energy, eliminating the need for periodic battery changes. The clean, contemporary styling makes the sensor an attractive addition to any décor. WIS-OSC
PRODUCT FEATURES WIRELESS
OCCUPANCY SENSING
NO BATTERIES OR POWER REQUIRED
• Sends messages to other devices when motion is detected • Harvests light energy to power the sensor Integrated Solar Cells
• Mounts easily on any ceiling or material • Works with other sensors for enhanced occupancy tracking • Built-in tests to confirm operation • Alternate power supply options for extreme low light conditions • Five-year limited warranty
PIR Motion Sensor
6.5”
1.47” 2.36”
Pa g e 18 2
hubbell-automation.com
10’
0 0-1’
Top view of sensor coverage based on 10ft mounting height
3.1’ 4.6’
7.5’ 9.3’ 10.9’ 13.’ 14.2’ 16.8’
Side view of sensor coverage based on 10ft mounting height
General Specifications Power Supply
Indoor light energy harvesting (Optional supplemental battery or 2-wire connector for external power or remote solar cell)
RF Communications
EnOcean 902 MHz
Transmission Range
80ft. (25m)
Motion Detection Range
40ft. (25m) diameter
Minimum Operating Light
50 lux (for auto-off only)
Startup Charge Times (from empty)
Linking = 4 min @ 100 lux 1.5 min @200 lux Motion Transmission = 6 min @ 100 lux 3.5 min @ 200 lux Note: Bright light or battery can be temporarily used to shorten initial startup charge times
Charge Time to Full
9 hrs @ 200 lux
Sustaining Charge Time
3 hours per 24 hours @ 200 lux
Motion Transmission Interval
60 - 300 seconds (based on real-time charge rate) 60 sec @ 200 lux - 300 sec @ 50 lux
Heartbeat Transmission Interval
120 - 600 seconds (based on real-time charge rate) 120 sec @ 200 lux - 600 sec @ 50 lux
Operating Life in Darkness
48 hours (after full charge)
EnOcean Equipment Profile (EEP)
A05-07-02
Dimensions
6.5”H x 2.36”W x 1.47” D
Mounting Height
7 - 10 feet (recommended)
Agency Compliance
FCC: SZV-EOSC05 IC: 5713-EOSC05
Warranty
Five-year limited
Interoperable Products / EEPs
Product Name (EEP #)
(EnOcean Equipment Profiles)
Rocker Pad Switch (F6-02-02) Key Card Switch (F6-04-01) Window handle (F6-10-00) 1BS Single Input Contact (D5-00-01) Temperature Sensor, 0 - 40° C (A5-02-05) Occupancy Sensor (A5-07-01) Contact, single input (A5-30-01) Central Gateway (A5-38-08)
Ordering Information WIS-OSC-WH
model WIS-OSC-WH
wiSTAR Occupancy Sensor - Ceiling Mount, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 18 3
wiSTARtm Wall Mounted Occupancy Sensor
TITLE
24 CEC
TM
COMPLIANT
CALIFORNIA
WIRELESS LIGHTING CONTROLS
Saving energy without sacrificing comfort can be effortless with occupancy based controls. Hubbell Building Automation’s wiSTAR™ Wall-Mounted Occupancy Sensors are wireless and self-powered making them one of the most cost-effective ways to control energy-use in unoccupied rooms. They can be installed in minutes because there are no additional wires to run and they require no batteries so ongoing maintenance costs are eliminated. The sensor harvests solar energy from indoor light and uses radio frequency technology to communicate wirelessly with other wiSTAR devices, turning off lights and electrical loads when it detects that a space has been unoccupied for a set period of time. The wall-mounted occupancy sensors feature clean contemporary styling, making them an attractive addition that’s sure to compliment any décor. WIS-OSW
PRODUCT FEATURES WIRELESS
OCCUPANCY SENSING
NO BATTERIES OR POWER REQUIRED
• Sends messages to other devices when motion is detected • Harvests light energy to power the sensor Integrated Solar Cells
• Mounts flush on wall or in a corner • Works with other sensors for enhanced occupancy tracking • Interchangeable lenses for tailored sensor coverage • Built-in tests to confirm operation • Alternate power supply options for extreme low light conditions • Five-year limited warranty 5.83”
PIR Motion Sensor
1.8”
Pa g e 18 4
2.52”
hubbell-automation.com
Wide Angle Coverage
Top View
Long Range Coverage
33ft (10m)
Top View
77° 16ft
16ft (5m)
21.5°
8ft 0
14°6
.5°
29° center line
0 8ft
16ft (5m)
16ft 33ft (10m)
Side View
6.8ft
Side View 6.8ft
(2.1m)
(2.1m)
6ft
15ft
(1.2m) (4.6m)
25ft
(7.6m)
50ft
(15.2m)
3ft
(1m)
7ft
(2.2m)
10ft
(3m)
35ft
(10.7m)
60ft
(18.3m)
100ft
(30.5m)
General Specifications Power Supply
Indoor light energy harvesting (Optional supplemental battery or 2-wire connector for external power or remote solar cell)
RF Communications
EnOcean 902 MHz
Transmission Range
80ft. (25m)
Motion Detection Range
50ft. wide angle lens / 100ft. long range lens
Minimum Operating Light
50 lux (for auto-off only)
Startup Charge Times (from empty)
Linking = 4 min @ 100 lux
1.5 min @200 lux Motion Transmission = 6 min @ 100 lux 3.5 min @ 200 lux Light/Walk Test Modes + 5.5 hrs @ 200 lux
Note: Bright light or battery can be temporarily used to shorten initial startup charge times Charge Time to Full
9 hrs @ 200 lux
Sustaining Charge Time
3 hours per 24 hours @ 200 lux
Motion Transmission Interval
60 - 300 seconds (based on real-time charge rate) 60 sec @ 200 lux - 300 sec @ 50 lux
Heartbeat Transmission Interval
120 - 600 seconds (based on real-time charge rate) 120 sec @ 200 lux - 600 sec @ 50 lux
Operating Life in Darkness
48 hours (after full charge)
EnOcean Equipment Profile (EEP)
A05-07-02
Dimensions
5.83”H x 2.52”W x 1.8”D
Mounting Height
6 - 8 feet (recommended)
Agency Compliance
FCC: SZV-EOSC05 IC: 5713-EOSC05
Warranty
Five-year limited
Inter-operable Products / EEPs
Product Name (EEP #)
(EnOcean Equipment Profiles)
Rocker Pad Switch (F6-02-02) Key Card Switch (F6-04-01) Window handle (F6-10-00) 1BS Single Input Contact (D5-00-01) Temperature Sensor, 0 to 40° C (A5-02-05) Occupancy Sensor (A5-07-01) Contact, single input (A5-30-01)
Central Gateway (A5-38-08)
Ordering Information WIS-OSW-WH
model WIS-OSW-WH
wiSTAR Occupancy Sensor - Wall Mount, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 18 5
wiSTARtm Key Card Switch WIRELESS LIGHTING CONTROLS
TM
Take the first step toward significant energy savings. Hubbell Building Automation’s wiSTAR™ Key Card Switch is one of the simplest, most economical ways to save energy through occupancy based control of lighting, HVAC and miscellaneous electric loads. The switch is self-powered and the simple act of inserting or removing the card generates enough kinetic energy to send a wireless signal to other wiSTAR devices within the room. To operate the switch, guests simply insert their key card in the slot when they enter the room and then remove it when they leave. The key card switch is wireless and can be installed in minutes without having to drill into the wall or run additional wiring. The switch features a clean contemporary styling, making it an attractive addition that’s sure to compliment any décor.
WIS-KCS
PRODUCT FEATURES WIRELESS
NO BATTERIES OR POWER REQUIRED
• Determines occupancy based on guest room key being inserted or removed • Harvests kinetic energy from the card action - no batteries • Installs easily in new or existing rooms - no wiring • Transmits room occupancy status wirelessly Key Card Slot
• Five-year limited warranty
4.72”
0.43”
Pa g e 18 6
3.8”
hubbell-automation.com
General Specifications Power Supply
Mechanical energy harvesting (power is generated by the motion of key card moving in or out)
Inputs/Outputs
Slot for standard hotel key card (2.125” W x 3.375” H x 0.034” D) Radio Frequency (RF) transmitter
RF Communications
EnOcean 902 MHz
Transmission Range
80ft. (25m)
RF Transmission
On key card insertion or removal
EEP (EnOcean Equipment Profile)
F6-04-01
Installation
Surface mounted on wall (using included mounting screws)
Dimensions
4.72”H x 3.8”W x .43”D
Weight
3.5 oz. (99 g)
Environment
Indoor use only 32° to 131° F (0° to 55° C) 5% to 95% relative humidity (non-condensing)
Agency Compliance
FCC: SZV-PTM33XU IC: 5713A-PTM33XU
Warranty
Five-year limited
Interoperable Products / EEPs
Product Name (EEP #)
(EnOcean Equipment Profiles)
Rocker Pad Switch (F6-02-02) Key Card Switch (F6-04-01) Window handle (F6-10-00) 1BS Single Input Contact (D5-00-01) Temperature Sensor, 0 to 40° C (A5-02-05) Occupancy Sensor (A5-07-01) Contact, single input (A5-30-01)
Central Gateway (A5-38-08)
Ordering Information WIS-KCS-WH
model WIS-KCS-WH
wiSTAR Key Card Switch, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 18 7
wiSTARtm Wall Switches WIRELESS LIGHTING CONTROLS
TM
Self-powered wireless controls are simple to install. Hubbell Building Automation’s wiSTAR™ Single and Double Rocker Switches use EnOcean energy harvesting technology to communicate wirelessly with other wireless devices and provide convenient control of lighting, temperature and miscellaneous electric loads. The rocker switches are self-powered and never require batteries. The action of pressing the rocker generates enough energy to send a wireless signal to other wiSTAR devices. Use them in conjunction with sensors and controls to maximize efficiency and provide a level of comfort and convenience you cannot achieve with traditional switches. The rocker switches feature a clean contemporary styling, WIS-DRP
making them an attractive addition that’s sure to compliment any décor.
WIS-SRP
PRODUCT FEATURES WIRELESS
NO BATTERIES OR POWER REQUIRED
• User interface for controlling lighting loads • Harvests energy from linear motion - no batteries 4.52”
• Transmits unique RF message each time pressed or released •
3.21”
Five-year limited warranty
Mechanical Energy Harvesting 1 or 2 Button Rocker Switches
4.9”
EnOcean 902MHz Frequency
0.72”
0.74”
WIS-DRP
Pa g e 18 8
WIS-SRP
hubbell-automation.com
General Specifications Power Supply
Mechanical Energy Harvesting (power is generated by the motion of pressing the switch)
Inputs/Outputs
1 or 2 button rocker switch options Radio Frequency (RF) transmitter
RF Communications
EnOcean 902 MHz
Transmission Range
80ft. (25m)
RF Transmission
On press and release of rocker button
EEP (EnOcean Equipment Profile)
F6-02-02
Dimensions
Single: 4.95”H x 3.21”W x 0.74”D Double: 4.95”H x 4.52”W x 0.72”D
Weight
Single: 3.98oz. Double: 5.3oz.
Mounting
Surface mounted on wall (using included mounting screws) Can also be flush mounted by optional use of electrical wall box or low-voltage ring
Environment
Indoor use only 32° to 131° F (0° to 55° C) 5% to 95% relative humidity (non-condensing)
Agency Compliance
FCC: SZV-PTM210U IC: 5713A-PTM210U
Warranty
Five-year limited
Inter-operable Products / EEPs
Product Name (EEP #)
(EnOcean Equipment Profiles)
Rocker Pad Switch (F6-02-02) Key Card Switch (F6-04-01) Window handle (F6-10-00) 1BS Single Input Contact (D5-00-01) Temperature Sensor, 0 - 40° C (A5-02-05) Occupancy Sensor (A5-07-01) Contact, single input (A5-30-01) Central Gateway (A5-38-08)
Ordering Information
model WIS-SRP-WH
wiSTAR Single Rocker Pad, 902MHz, White
WIS-DRP-WH
wiSTAR Double Rocker Pad, 902MHz, White
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 18 9
Smart Street Lighting
wiSCAPETM uses a combination of fixture modules and gateways to create a wireless street lighting controls solution. wiSCAPE components are adaptable to ALL fixture types and ALL voltages in new and retrofit street lighting environments. These components create a secure peer-to-peer, self-organizing and self-healing mesh network infrastructure that allows for distances of 300ft or 1,000ft between devices*. wiSCAPE allows users to manage, monitor, and meter individual fixtures or groups of fixtures over-the-air with the click of a mouse. *Dependant on choice of module.
wiSCAPE Gateways
wiSCAPE Fixture Modules
wiSCAPE Gateways are used to combine up to 1000 wiSCAPE
•
Dry contact inputs for low voltage devices.
Fixture Modules into a single wireless network. Although each
•
Dry contact output for driving external contactors.
Fixture Module is functionally autonomous, the Gateway also
•
0-10V output control for Pre-set levels, Ramp speed (Up-Down), Smooth transition, Minimum and Maximum Dimming levels, Minimum On-time before dimming, and Demand/ Response load shedding settings.
•
Unlimited number of schedules based on Sunrise/Sunset, Time of Day, Day of Week, Predefined periods and Holidays.
•
Real latitude and longitude location information.
•
Unique serial number bar code.
•
Works with all lighting fixtures types including: • LED, • Induction, • MH-HPS-LPS • Incandescent • Halogen, and Plasma.
acts as an access point through which the modules can be managed, monitored, and metered through wiSCAPE View™ software.
Three Server Options There are three ways to host wiSCAPE on a server: 1.
Local PC tied directly to the Gateway(s).
2.
Local PC connected to remote Gateway(s) via the Internet.
3.
Cloud based server connected to remote Gateway(s) via the Internet.
Pa g e 19 0
wiSCAPETM is a Wireless Street Lighting Controls Solution that enables utilities and municipalities to manage, monitor and meter each individual streetlight throughout the city.
wiSCAPE performs every function municipal engineers and control electricians are looking for:
wiSCAPE Reduces the Overall Amount of Energy Used by Street Lights One of the best ways to save energy from street lighting is to dim or switch fixtures off when they are not needed. wiSCAPE offers a variety of features to facilitate this: Photocells, Light Sensors, Standard Time Clock, Astronomical Time Clock Lights can be dimmed* or switched based on daylight levels, time schedules and/or sunrise and sunset. For example, streetlights could be turned on 15 minutes before sunset, dimmed to 50% at 11 p.m., set to full at 5 a.m., and turn off 15 minutes after sunrise.
wiSCAPE Allows for Streamlined and economical Street Lighting Networks Keeping city fixtures in working order is costly. Oftentimes, maintenance departments are unaware of an outage until they get a call or incur the cost of sending maintenance crews out each night to visually identify lamp failures. Alarms and Notifications wiSCAPE can be set to trigger alarm notifications for streetlight problems such as burned lamps, over/under voltage, and cycling. Not only does wiSCAPE report the exact problem fixture and fixture location (GPS), the system also gives the information needed for maintenance crews to prioritize repairs and schedule the most efficient repair routes.
wiSCAPE Lights Streets Based on Activity Level Some street locations have such random use at night that trying to set light levels based on a schedule is nearly impossible. Motion Sensors Motion sensors would allow each individual streetlight to dim* or switch on or off based upon whether motion is detected from either a vehicle or a pedestrian.
wiSCAPE Assists in Minimizing Light Pollution Light pollution is an issue that’s gaining greater attention across the country as more and more cities are passing Dark Sky legislation. Dimming, Scheduling, and Motion Control wiSCAPE allows for control down to the granularity of a single fixture and can utilize a combined strategy of dimming*, scheduling, and motion control to dim or turn lights off when they are not needed.
wiSCAPE Enables Municipalities to Pay For Actual Energy Consumed Because streetlights are not always metered, cities are often charged a tariff per streetlight currently installed. While this method is rarely accurate due to fixtures requiring maintenance at any given time, it’s difficult to prove exactly how much energy was really consumed. Monitoring and Metering wiSCAPE allows the city to monitor and meter each fixture’s energy use and create an energy usage report for an individual fixture, a zone or the entire city.
wiSCAPE Is Affordable to Install The cost of the fix is always a concern as municipalities and utilities have limited budgets to work with. Wireless and Modular Whether cities choose to retrofit existing fixtures or go with something new, wiSCAPE modules are compatible with all types of lighting fixtures and aren’t limited to any specific fixture manufacturer. The wireless technology allows for a cost effective installation, eliminating the need for trenching and wiring – practices that can make controls an expensive solution. Due to the modular nature of wiSCAPE, additional fixtures and streets can be added to the system at any time or as funds become available.
*Dimming solutions are only available when used with a 0-10V dimmable fixture.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax orders ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 19 1
wiSCAPE™ Gateway WIRELESS STREET LIGHTING CONTROLS
120 VAC
RATED
IP 66
WATER-DUST RESISTANT
Hubbell Building Automation's wiSCAPE™ Gateway is used to combine up to 1000 wiSCAPE Fixture Modules into a single wireless network. Although each Fixture Module is functionally autonomous, the Gateway acts as an access point through which the modules can be managed, monitored and metered through wiSCAPE View™ software. Using the robust 2.4GHz ISM (Industrial, Scientific and Medical) radio band, the wiSCAPE Gateway's wireless control technology adapts easily to complex automation situations for quick, simple and economical commissioning and operation.
WIR-GATEWAY
PRODUCT FEATURES
WIRELESS
•
Scales to any network size
•
Solid-state disks withstand temperature, shock and vibrations
•
Surge protected
•
Module/Gateway ratio:1000 modules per Gateway
•
Fail-safe operation- defaults to photocell control
•
Gateways are in NEMA 4X (IP66) cabinets
•
Data storage supports up to six months of rolling data storage
•
128-bit AES encryption
14”
12” 6”
Pa g e 19 2
hubbell-automation.com
General Specifications Voltage
120-240VAC; 50/60Hz
Power consumption 18 watts
Fused supply
5 amps
Surge protection
190 Joules (10,000 surge current rating measured using industry standard 8/20 µSec wave)
50/60 HZ, Consumption: max 26 VA
Ambient temperature range
-400F to 1850F (-400C to 850C)
Relative Humidity
Up to 99% non-condensing (fully waterproof enclosure NEMA 4x)
Dimensions
12”L x 14”W x 6”H
Construction
Compression molded fiberglass reinforced polyester construction with flush, solid/opaque cover IP66 Rated
Certifications
FCC/IC Certified, RoHS Compliant
Warranty
Five-year limited warranty
Ordering Information WIR-GATEWAY model WIR-GATEWAY
Blank CM
Modem None
Cellular Modem
Accessory
Stepdown Transformer
WIR-STPDNXFMR-277 wiSCAPE Gateway 277V to 120V Stepdown WIR-STPDNXFMR-347 wiSCAPE Gateway 347V to 120V Stepdown
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 19 3
wiSCAPE™ Fixture Module WIRELESS STREET LIGHTING CONTROLS
120, 208 277, 347 VAC
Hubbell Building Automation's wiSCAPE™ Fixture Module is a bidirectional wireless RF device that allows an individual fixture to be managed, monitored and metered. The wiSCAPE Module can switch loads of up to 3 Amps and is available for the following voltages: 120, 208, 277 and 347VAC. Built-in 0-10V outputs also allow fixtures to be dimmed. The Fixture Module works with all fixture types including: LED, Induction, MH-HPS-LPS, Incandescent, Halogen and Plasma. Digital and analog inputs and outputs make sending and receiving signals from additional control devices simple and easy. wiSCAPE Fixture Modules communicates wirelessly over a robust 2.4GHz ISM (Industrial, Scientific and Medical) certified radio signal. The wiSCAPE Fixture Module drastically simplifies control and automation of projects, especially in retrofit environments and challenges the legacy world of wired-systems. wiSCAPE wireless control technology adapts easily to complex automation situations for WIR-RM
quick, simple and economical commissioning.
PRODUCT FEATURES 0-10V DIMMING
•
Inputs for low-voltage switch, motion and photo sensor
•
Outputs 0-10V for dimming ballasts (Sink+Source)
•
Dry contact output for driving external contactors
•
Bidirectional wireless RF Mesh communications
•
Individual addresses providing unique serial numbers
•
Can work as a fully autonomous system, or remotely managed from a central
WIRELESS
system. No central panel required •
Multi-level grouping and multiple scenarios
•
Adjustable minimum and maximum dimming levels
•
Programmable state after blackout, with peak shaving options
•
Blink warning and override before scheduled lights off
•
Both locally and remotely controllable with status and metering reporting
•
Smart daylight harvesting and motion sensing functions, with occupied and
1.52” .86” 4.75” 2.65”
unoccupied levels including a lamp saver function •
Demand response (load shedding) and emergency mode ready
Pa g e 19 4
hubbell-automation.com
General Specifications Voltage
120, 208-240, 277, 347; 50/60Hz Less than 2 watts standby consumption
Maximum Load Amperage
3 amps
Phase-cut Dimming
Continuous retroactive trailing-edge
Output Status Monitoring
Standard feature
Power Metering
Amperage - Voltage - Power (2% accuracy), Power Factor, Cumulative Energy - Burn-time counters
Options
Hi-Lo: Control for HID (Core & Coil) Dual-capacitors
0-10V Dimming
For all types of 0-10V drivers & ballasts requiring either to be sunk (up to 200mA) or sourced (20mA standalone or higher w/ext. source)
Standard Inputs
3 Digital: ex: Motion sensor and switch top/bottom buttons (max : 48V) + 1 Analog 0-10V
Additional Outputs
2 Digital (Open-collector up to 48Vâ&#x20AC;&#x201D;max: 20 mA total)
Standard Radio
Up to 300 ft between modules
Long Range Radio
Up to 1000 ft between modules
Ambient Temperature Range
-400F to 1850F (-400C to +850C)
Relative Humidity
0% to 100% non-condensing (fully waterproof packaging option)
Certifications
ETL 3192455, UL508 & CSA C22.2 No.14 U.S. FCC Part 15.247 : OUR-XBEE / OUR-XBEE UL94V-0 Flame retardant ABS or Epoxy molding
Warranty
Five-year limited
Ordering Information
model wiSCAPE Wireless Relay - Standard Range WIR-RML wiSCAPE Wireless Relay - Long Range
WIR-RMS
24 120 208 277 347
Voltage 24VAC* 120VAC 208/240VAC 277VAC 347VAC
Input/Output Blank None IO Input/ Output
Enclosure Blank None N4 NEMA 4
* Requires Power Pack/ Includes IO Option
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 19 5
wiSCAPETM 480V Fixture Module WIRELESS Street lighting CONTROLS
480 VAC
Hubbell Building Automation's wiSCAPE™ Fixture Module is a bidirectional wireless RF device that allows an individual fixture to be managed, monitored and metered. The wiSCAPE Module can switch loads of up to 6 Amps and is available for 480VAC. Built-in 0-10V outputs also allow fixtures to be dimmed. The Fixture Module works with all fixture types including: LED, Induction, MH-HPS-LPS, Incandescent, Halogen and Plasma. Digital and analog inputs and outputs make sending and receiving signals from additional control devices simple and easy. wiSCAPE Fixture Modules communicate wirelessly over a robust 2.4GHz ISM (Industrial, Scientific and Medical) certified meshed radio signal. The wiSCAPE Fixture Module drastically simplifies control and automation of projects, especially in retrofit environments and challenges the legacy world of wired-systems. wiSCAPE wireless control technology adapts easily to complex automation situations for quick, simple and economical commissioning. WIR-RM 480
PRODUCT FEATURES 0-10V DIMMING
•
Inputs for low-voltage switches, motion and photo sensors
•
Outputs 0-10V for dimming ballasts (Sink+Source)
•
Dry contact output for driving external contactors
•
Bidirectional wireless RF Mesh communications
•
Individual addresses of unique serial numbers
•
Can work as a fully autonomous system, or remotely managed from a central
WIRELESS
system. No central panel required 3.35”
•
Multi-level grouping and multiple scenarios
•
Adjustable minimum and maximum dimming levels
•
Programmable state after blackout, with peak shaving options
•
Blink warning and override before scheduled lights off
•
Both locally and remotely controllable with status and metering reporting
•
Smart daylight harvesting and motion sensing functions, with occupied and
6.3”
unoccupied levels including a lamp saver function •
Demand response (load shedding) and emergency mode ready 3.15”
Pa g e 19 6
hubbell-automation.com
General Specifications Voltage
480V; 60Hz Less than 2 watts standby consumption
Maximum Load Amperage
6 amps
Phase-cut Dimming
Continuous retroactive trailing-edge
Output Status Monitoring
Standard feature
Power Metering
Amperage - Voltage - Power (2% accuracy), PF, Cum. Energy - Burn-time counters
Options
Hi-Lo: Control for HID (Core & Coil) Dual-capacitors
0-10V Dimming
For all types of 0-10V drivers & ballasts requiring either to be sunk (up to 200mA) or sourced (20mA standalone or higher w/ext. source)
Standard Inputs
3 Digital: ex: Motion sensor and switch top/bottom buttons (max : 48V) + 1 Analog 0-10V
Additional Outputs
2 Digital (Open-collector up to 48Vâ&#x20AC;&#x201D;max: 20 mA total)
Standard Radio
Up to 300 ft between modules
Long Range Radio
Up to 1000 ft between modules
Ambient Temperature Range
-400F to 1850F (-400C to +850C)
Relative Humidity
0% to 100% non-condensing (fully waterproof packaging option)
Certifications
ETL 3192455, UL508 & CSA C22.2 No.14 U.S. FCC Part 15.247 : OUR-XBEE / OUR-XBEE UL94V-0 Flame retardant ABS or Epoxy molding
Warranty
Five-year limited
Ordering Information
model wiSCAPE Wireless Relay - Standard WIR-RML wiSCAPE Wireless Relay - Long Range
WIR-RMS
480
480
IO
Voltage 480VAC
Input/Output IO Input/ Output
N4
N4
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Enclosure Nema 4
Pa g e 19 7
wiSCAPE™ PLC WIRELESS STREET LIGHTING CONTROLS
120 347 VAC
RATED
IP 66
WATER-DUST RESISTANT
Hubbell Building Automation's wiSCAPE™ PLC is a communication interface between the wiSCAPE Keypad and the wiSCAPE Wireless Street Lighting Controls which allows for the activation of sophisticated lighting scenarios.
WIR-PLC
PRODUCT FEATURES WIRELESS
•
Weatherproof NEMA 4 IP66 enclosure.
•
Can be wired up to 75’ from the wiSCAPE Keypad
•
Communicates wirelessly with wiSCAPE Fixture Modules.
8”
8” 4”
Pa g e 19 8
hubbell-automation.com
General Specifications XB RF mesh Signal
2.4GHz – 802.15.4 ISM
Supply Voltage
120, 208, 240, 277 or 347 VAC
PLC Central Carrier Frequency
262kHz
Operating Temperature
-4°F to 122°F (-20°C to +50°C)
Construction
Rugged design enabling installation in a weatherproof NEMA 4 enclosure
Dimensions
8”L x 8”W x 4”H
Warranty
Five-year limited
Ordering Information WIR-PLC model WIR-PLC
120 208 277 347
Voltage 120 VAC 208/240VAC 277VAC 347VAC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 19 9
wiSCAPE™ Software Suite WIRELESS STREET LIGHTING CONTROLS
wiSCAPE™ Wireless Street Lighting Controls offers a suite of software to manage, monitor, and meter your wireless street lighting network.
wiSCAPE View™ Graphical System Management Software Hubbell Building Automation's wiSCAPE View™ is an intuitive software platform that can configure, manage, monitor and meter a wiSCAPE Lighting Control System, all in one easy to use software platform. Using wiSCAPE View the user is able to remotely access multiple wiSCAPE Gateways individually from one location. • Secured multi-concurrent users login and tractability
• Software Configuration of modules
• Module configuration and control
• Scheduling
• Creation/Editing of the user-defined library of Scenarios - Commands
• Zone Design (Virtual assignment of Relays to Zones)
- Groups - Schedules
• Power Monitoring
• Database management • Historical data logging of power use, data acquisition modules (pulse counters, analog and digital sensors and instruments) and history of commands and scenarios
General Specifications Data storage: Operating System: Operating System: Desktop Browser and Settings (Active X, registry settings, etc.) and Operating System: Reporting Tools:
MySQL database Windows Server 64-bit User Desktops, Tablets or Laptops Any browser, no special setting
Exports to Excel and CSV Formats
wiSCAPE Enterprise™ Software Hubbell Building Automation's wiSCAPE Enterprise™ is an add on module to wiSCAPE View that allows the user to conveniently combine all of their Gateways into a single database. wiSCAPE Enterprise allows single sign-on and access to all installed Gateways and provides all of the functionality of wiSCAPE View.
Pa g e 2 0 0
hubbell-automation.com
wiSCAPE BACnet Software Module Hubbell Building Automation's wiSCAPE BACnet software module allows easy interfacing of wiSCAPE control system and modules with the Building Automation Systems BACnet. BACnet was chosen as the integration platform, for integrating with traditional building automating systems, while promoting the use of intelligent addressable wireless controls & sensors that do not require dedicated control wiring, making it ideal for both new and retrofit projects.
wiSCAPE APP HBA offers a web based Graphical User interface for IPOD®, IPAD®, IPHONE®, Android™, Blackberry® or any other Smartphone with a browser. The wiSCAPE-APP provides control of wiSCAPE devices including: •
Wireless intelligent relays
•
Wireless RF controls
•
BACnet objects
•
Preconfigured Scenarios
• The interface is web based so it doesn’t require any installation on the client device and is always up to date, reducing maintenance and support cost to a minimum. • Being linked to the same SQL database as the wiSCAPE Building Automation System, changes are immediately reflected on all clients connected.
General Specifications APP Requirements:
wiSCAPE View software. Server running Microsoft IIS Internet or local area network connection
IPOD®, IPAD®, and IPHONE® are registered trademarks of Apple Inc., registered in the U.S. and other countries. Android™ is a trademark of Google Inc. BlackBerry® is the property of Research In Motion Limited and are registered and/or used in the U.S. and countries around the world. Used under licence from Research In Motion Limited.
Ordering Information WIR-SS
WIR-SS
model wiSCAPE Software Suite
Software VIEW ENTERPRISE BACNET APP
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 0 1
wiSCAPETM Gateway Cellular Modem WIRELESS STREET LIGHTING CONTROLS
The wiSCAPE Gateway Cellular Modem is a secure Ethernet gateway ideal for customers requiring 24/7 broadband connectivity. With simple installation and configuration requirements, the Gateway Cellular Modem is designed to handle robust, fixed applications requiring broadband communication speeds and bandwidth.
WIR-MOD-GPRS
PRODUCT FEATURES •
Persistent 3G Network
•
Connectivity
•
Low Power Consumption
•
Compact Size for Easy Integration
•
Rugged Aluminum Case
•
Remote Management and Configuration
•
Five-year limited
WIRELESS
3.7”
1.1”
3”
Pa g e 2 0 2
hubbell-automation.com
General Specifications Security
IPsec VPN GRE Tunneling Events Reporting Engine Routing Protocols Highly Configurable
Technology
HSUPA with fallback to: HSDPA, UMTS, EDGE, GPRS, GSM EV-DO Rev. A with fallback to: CDMA, EV-DO Rev. 0, CDMA 1x, CDMA IS-95
Bands
Tri-Band UMTS/HSDPA/HSUPA, 850, 1900, 2100 MHz Quad-Band GPRS/EDGE, 850, 900, 1800, 1900 MHz Dual-Band EV-DO Rev. A, 800, 1900 MHz
Quad-Band UMTS/HSDPA/HSUPA, 850, 900, 1900, 2100 MHz
Host Interfaces
Ethernet: 10/100 BASE-T RJ-45 USB Type B5 Pin Mini
Antenna Connections
Cellular - 50 Ohm SMA Receive Diversity 50 Ohm SMA
I/O Ports
2
LED Indicators Network Signal Activity Power Operating Temperature
-22°F to 158°F (-30° to +70°C)
Storage Temperature
-40°F to 185°F (-40° to +85°C)
Dimensions
3.0”W x 1.1”H x 3.7”L
Weight
7.1 oz
Certifications FCC RoHS PTCRB CE Warranty
Five-year limited
Ordering Information WIR-MOD-GPRS model WIR-MOD-GPRS
GPRS Cell Modem add-on option for wiSCAPE Gateways
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 0 3
wiSCAPETM Modem WIRELESS STREET LIGHTING CONTROLS
The wiSCAPE™ Modem allows the user to wirelessly connect their notebook or desktop PC to the wiSCAPE wireless street lighting system via their computer’s USB port. The wiSCAPE Modem allows the user to remotely manage, monitor, and meter their wiSCAPE System through wiSCAPE View™ software on their computer.
WIR-MODEM
PRODUCT FEATURES •
Low Power Consumption
•
Compact Size for Easy Integration
•
Rugged Case
•
Remote Management and Configuration
•
Five-year limited
WIRELESS
2.25”
1.5”
Pa g e 2 0 4
hubbell-automation.com
General Specifications
Operating Voltages
Powered from USB port
Connector Type
USB 2.0 Type B
Communication Type
Wireless RF MESH 2.4GHz – 802.15.4 ISM FCC compliant (FCC ID: OUR-XBEE)
Range
RF Mesh : 300 ft per hop
LED Indicators
Green = Power OK Yellow = Transmitting Red = Receiving
Dimensions
4”L x 2.25”W x 1.5”H
Warranty
Five-year limited
Ordering Information WIR-MODEM model WIR-MODEM
wiSCAPE Modem with USB Connection
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 0 5
wiSCAPETM Photo Sensor
TITLE
24 CEC
LOW
COMPLIANT
CALIFORNIA
Wireless Street Lighting Controls
24 VDC
VOLTAGE
Hubbell Building Automation’s wiSCAPETM Photo Sensor provides the necessary daylight-level information to the wiSCAPE Fixture Modules. Using a photodiode element, this sensor continuously measures daylight levels and sends the information to the module. The applicable foot-candle range is selected by using a jumper beneath the front cover.
DLCPCO
PRODUCT FEATURES
DAYLIGHT HARVESTING
• Interfaces with Energy Management Systems • Foot-candle range: 50 - 750FC • Mounts horizontally • UL and cUL listed • California Title 24 Compliant • Five-year limited warranty
1.35”
1.85”
Correct orientation shown
Pa g e 2 0 6
hubbell-automation.com
General Specifications Accuracy
+/-1% at 70°F (21°C Derated to +/-5% at 120°F or at) F (-18°C to 49°C)
Operating Temperature
13°F to 140°F (-11°C to 60°C)
Sensor Type
Blue-enhanced photo diode
Sensor Ranges
50-750FC
Input Voltage
24VDC
Output Voltage
10V full output
Output Offset
0VDC or 1VDC - total darkness
Wiring
Three conductors 18-gauge standard cable Red: Pos. DC input Black: DC common Yellow: Output to EMS
Certifications
ETL/UL 916 Listed Title 24 Listed RoHS compliant
Warranty
Five-year limited
Ordering Information DLCPCO
DLCPCO
Model Outdoor Photocell Sensor, 50 - 750FC
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 0 7
wiSCAPE™ Keypad WIRELESS STREET LIGHTING CONTROLS
LOW
24 VDC
VOLTAGE
The wiSCAPE™ Keypad is designed to be integrated with wiSCAPE Wireless Street Lighting Controls. The compact and versatile design features 6 buttons, each capable of being programmed to activate sophisticated lighting scenarios. In conjunction with wiSCAPE enabled fixtures, a scenario could include a single fixture or entire groups of fixtures. As with all wiSCAPE Fixture Modules, the keypad is configured through wiSCAPE View™ software. Once configured, the keypad will not require the presence of a computer or central controller on the network.
WIR-KP
PRODUCT FEATURES •
6 programmable buttons for a total of 6 possible scenarios
•
Low power consumption
•
Sends any user-programmable commands to an unlimited number
•
LED Feedback on each button
of receivers
•
Reprogrammable over the air
•
Compact design to be easily installed in standard electrical boxes
•
Five-year limited warranty
•
Fits standard Decorator Style wallplate (sold separately)
General Specifications Operating Voltage
15-30VDC
Mounting
Standard single gang electrical box
Dimensions
1.6”W x 4.0”H x 1.7”D
Other Requirements:
Requires appropriate wiSCAPE PLC for system operation
Ordering Information WIR-SW-KP6-WH
WIR-SW-KP6-WH
Pa g e 2 0 8
model wiSCAPE Keypad
hubbell-automation.com
wiSCAPE WASP2TM Motion Sensor
TITLE
24 CEC
COMPLIANT
CALIFORNIA
Wireless Street Lighting Controls
RATED
IP 65
WATER-DUST RESISTANT
Hubbell Building Automation’s wiSCAPETM WASP2TM Motion Sensor is specifically designed for ON/OFF control of street lighting. The motion sensor is also available for low-mount applications when using the appropriate lens. The sensor is available in end-mount and surface-mount versions with either single or dual outputs.
End Mount wiSCAPE WASP2 Sensor with Lens option
PRODUCT FEATURES
OCCUPANCY SENSING
DAYLIGHT HARVESTING
SMART CYCLING
• Digital Passive Infrared (PIR) sensor • Supported maximum mounting heights: • High mount lens: up to 30 ft outdoors; 45 ft indoors •
Interchangeable Lens Options
Multiple (single and dual) output versions
• Unique Smart Cycling™ for improved lamp life High Impact Plastic Design
• End-mount and surface-mount versions • Withstands low temperature and conforms to IP65 water-tight
1.5”
standards • UL and cUL listed • Five-year limited warranty 4.0”
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 0 9
Sensor Lens Coverage and Detection Patterns When Mounted at 8ft with Low Mount Lens
Sensor Lens Coverage and Detection Patterns When Mounted at 30ft
General Specifications Power Requirements
Low Voltage sensors: 24VDC
User Interface
(1) Twelve pin DIP switch
Time Delay
Primary: 8-second test mode - 4, 8, 16 and 30 minute timeouts Secondary: Can be disabled (switches off with primary timer) - 30, 60 and 90 minute timeouts
Passive Infrared
Dual element pyrometer and spherical Fresnel lens designed for robust detection of a walking person.
When used with program start ballast, a 1-2 second delay from occupancy detection to lamp turn-on may be experienced.)
Daylight Sensor
Range: 30 – 2500FC End mount sensor: Downward and upward looking daylight sensors (Direction selectable via DIP switch) Surface mount sensor: Downward looking daylight sensor only
Interchangeable Lens Options
Lens options: (Lenses sold separately – not included with sensor module) Low Mount/High Mount Indoor/Outdoor Coverage: 360°, 180°, Aisle, Half Aisle
Operating Environment
Relative humidity (non-condensing): 0% to 95% Low-temperature/Water-tight/Indoor-Outdoor version: -40° to 149°F (-40° to 65°C)
Construction
Sensor Module and Lens Assembly – high impact, injection-molded plastic
Dimensions
4.0”DIA x 1.5”H
Weight
7 oz.
Color
White, Black and Gray
Mounting
End mount sensor: Mounts directly to end of fixture through extended ½” chase nipple For deeper body fixtures, an optional Extender Adapter (available separately) positions the sensor flush or below the bottom of the reflector for a full field-of-view. Surface mount sensor: Mounts directly to fixture or j-box via (2) 1.25” stainless steel screws and locking nuts
Certifications
Conforms to UL STD 508, UL STD 244A Conforms to IP65 (Low-temperature/Water-tight version)
Warranty
Five-year limited
Pa g e 2 10
hubbell-automation.com
Ordering Information WSP WSP SENSOR model WSP
24V MOUNTING EM - End Mount SM - Surface Mount
INPUT VOLTAGE 24V - 24VDC (Low Voltage)
LOW-TEMP/ Water Tight LWO - Low-Temp/Water Tight/ Indoor/Outdoor
color Blank - White BK - Black GY - Gray
Example: WSP EM 24V LWO â&#x20AC;&#x201C; Wasp End Mount Sensor, 24V, Low Temp/Water Tight, White
For appropriate lens options please reference WASP2 Occupancy Sensor Lens Specification Sheet.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 11
Emergency Lighting Bypass Controls
Pa g e 2 12
Providing Safety and Savings
Emergency lighting is a critical component when laying out a lighting system. The system requirements are defined by local codes which determine the amount of emergency lighting required to meet minimum lighting levels during a loss of power. How these levels are attained is dependent on the design of the lighting system. Hubbell Building Automationâ&#x20AC;&#x2122;s emergency lighting bypass lighting controls offer several options for emergency lighting applications. All HBA products are specifically UL listed and labeled for use in emergency lighting.
( 8 8 8 ) 6 9 8 - 3 2 4 2 | Fax orders ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 13
UL924 Enclosed 20 AMP Bypass Shunt Relay
TITLE
24
120 277
COMPLIANT
CALIFORNIA
EMERGENCY LIGHTING BYPASS CONTROLS
VAC
Hubbell Building Automation’s enclosed 20 Amp electrically held UL 924 Bypass Shunt Relays provide an isolated normally closed contact that can be used to provide bypass shunt to power emergency egress lighting directly from the emergency generator source. The coil in these relays is powered by a normal power supply. When the loss of commercial power occurs, the contact returns to its normally closed state and bypasses control to the emergency egress lighting. These fixtures will remain connected directly to generator emergency source until transfer back
UL924SR
to normal power occurs.
PRODUCT FEATURES • 20 Amp 120/277VAC Relay • N/C isolated contacts • UL listed • No minimum load requirement • Five-year limited warranty
1.75”
3.75”
Pa g e 2 14
hubbell-automation.com
General Specifications # Relays & Contact Type
One (1) SPST Continuous Duty Electrically Held Coil
Contact Ratings
1500 VA Tungsten @ 120VAC 20 Amp Ballast @ 120/277VAC 2 HP @ 277VAC 1 HP @ 120VAC
Coil Current
0.06 A @ 120VAC 0.06 A @ 277VAC
Coil Voltage Input
UL924SR1: 120VAC; 60Hz
UL924SR2: 277VAC; 60Hz
Operating Environment
Indoor use only 32° to 140°F Relative humidity (non-condensing): 0% to 95%
Dimensions
3.75”L x 1.75”W x 1.25”H with mounting ears for 1-gang box
Housing Rating
Plenum, NEMA 1
Flame Rating
UL94V-0
Wires
7”, 105° C, 600V Rated
Certifications
UL Listed, UL924
Warranty
Five-year limited
Ordering Information
UL924SR1 UL924SR2
model UL924 N/C Shunt Relay 120/277V, 20A SPST with 120VAC Coil UL924 N/C Shunt Relay 120/277V, 20A SPST with 277VAC Coil
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 15
UL924 Enclosed 20 AMP Bypass Relay with Remote Emergency Control
TITLE
24 CEC
COMPLIANT
CALIFORNIA
EMERGENCY LIGHTING BYPASS CONTROLS
120 277 VAC
Hubbell Building Automation’s enclosed 20 Amp electrically held UL 924 Bypass Relay is specifically designed for projects requiring bypass utilizing an unswitched emergency circuit that is not controlled by a relay in a panel or power pack. The control of the lighting on the emergency circuit is switched ON and OFF based on the normal circuit switching input to the unit. When the loss of commercial power occurs, the contact returns to its normally closed state and bypasses control to the emergency egress lighting.
UL924BRUNV
The unit includes an automatic test function that simulates utility power failure and holds emergency lighting on for 2.5 seconds each time the switched input is turned OFF.
PRODUCT FEATURES
• 20 Amp 120/277VAC Relay • Available with Dual Tap 120VAC or 277VAC Coil • N/C isolated contacts • UL listed • No minimum load requirement
1.75”
• Five-year warranty
3.75”
Pa g e 2 16
1.25”
hubbell-automation.com
General Specifications # Relays & Contact Type
One (1) SPST Continuous Duty Electrically Held Coil
Contact Ratings
1500 VA Tungsten @ 120VAC 20 Amp Ballast @ 120/277VAC 2 HP @ 277VAC 1 HP @ 120VAC
Coil Current
0.06 A @ 120VAC 0.06 A @ 277VAC
Coil Voltage Input
UL924BRUNV: 120 or 277VAC; 60Hz
Operating Environment
Indoor use only 32° to 140°F Relative humidity (non-condensing): 0% to 95%
Dimensions
3.75”L x 1.75”W x 1.25”H with mounting ears for 1-gang box
Housing Rating
Plenum, NEMA 1
Flame Rating
UL94V-0
Wires
7”, 105° C, 600V Rated
Certifications
UL Listed, UL924
Warranty
Five-year limited
Ordering Information UL924BRUNV
model UL924BRUNV
UL924 Emergency Control Relay (Shunt or Bypass) with auto test 120-277VAC Coil
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 17
UL924 Enclosed 20 AMP Automatic Power Transfer Control Relay
TITLE
24 CEC
COMPLIANT
CALIFORNIA
EMERGENCY LIGHTING BYPASS CONTROLS
120 277 VAC
Hubbell Building Automation’s enclosed 20 Amp Emergency Power Transfer Control Relay is a versatile, cost-effective unit, specifically designed for projects requiring hot and neutral switching of the load from normal circuit to emergency circuit or that include the requirement that 0-10V dimming circuits be brought to full brightness during the emergency transfer event. The unit senses loss or voltage drop of the normal utility source and within 1.5 seconds transfers the load including the neutral to the emergency source. When power is restored, the unit transfers the load back to normal utility power within 1.5 seconds. An integral momentary test switch simulates utility power failure and can be activated at any time. Any interruption of normal utility power will automatically transfer designated emergency lights to full bright regardless of current dim level UL924BRLN
or ON/OFF state of the system.
PRODUCT FEATURES • 20 Amp 120/277VAC Relay • N/C isolated contacts • 0-10V Dimming Control to Full upon Transfer • UL listed • No minimum load requirement • Five-year warranty 5.25”
5.25”
Pa g e 2 18
2.25”
hubbell-automation.com
For use with LX, CX Panels, Power Packs and wiHUBB™ Smart Packs. 1
Switched with Normal Load when Normal Power is available. Held ON when Normal Power is not available and Emergency Power is available.
2
Switched with Normal Load when Normal Power is available. Not powered when Normal Power is not available.
General Specifications # Relays & Contact Type
Six (6) SPST Continuous Duty Electrically Held Coil with Time Delay
Contact Ratings
1800 VA Tungsten @ 120VAC 20 Amp Ballast @ 120/277VAC
Coil Current
0.06 A @ 120VAC 0.06 A @ 277VAC
Coil Voltage Input
UL924BRLN1: 120VAC; 60Hz
UL924BRLN2: 277VAC; 60Hz
Operating environment
Indoor use only 32° to 140°F Relative humidity (non-condensing): 0% to 95%
Dimensions
5.125”H x 5.125”W x 2.25”D with mounting holes for 4 11/16” deep box
Housing Rating
Plenum, NEMA 1
Flame Rating
UL94V-0
Wires
7”, 105° C, 600V Rated
Certifications
UL Listed, UL924
Warranty
Five-year limited
Ordering Information
model UL924BRLN1
UL924 Emergency Transfer Control Relay with manual test 120V Coil, 0-10V control
UL924BRLN2
UL924 Emergency Transfer Control Relay with manual test 277V Coil, 0-10V control
( 8 8 8 ) 6 9 8 - 3 2 4 2 | F a x o r d e r s ( 512 ) 4 5 0 - 0 8 6 4 | h u b b e l l - a u t o m a t i o n . c o m
Pa g e 2 19
Index VACANCY & OCCUPANCY SENSORS LightHawk2™—Dual Technology Wall Switch Sensor featuring IntelliDAPT® ........................................................................................................ 10 LightHawk2—Ultrasonic Wall Switch Sensor featuring IntelliDAPT........................................................................................................................... 12 LightHawk2—Passive Infrared Wall Switch Sensor featuring IntelliDAPT................................................................................................................. 14 LightHawk2— Night Light Passive Infrared Wall Switch Sensor featuring IntelliDAPT............................................................................................ 16 LightHawk2— Dimming Passive Infrared Wall Switch Sensor featuring IntelliDAPT............................................................................................... 18 OMNI™ Dual Technology Ultrasonic and Passive Infrared Ceiling Sensor featuring IntelliDAPT ........................................................................... 20 OMNI Ultrasonic Ceiling Sensor featuring IntelliDAPT............................................................................................................................................... 22 OMNI Passive Infrared Ceiling Sensor featuring IntelliDAPT..................................................................................................................................... 24 OMNI Dual Technology Acoustic and Passive Infrared Ceiling Sensor featuring IntelliDAPT .................................................................................. 26 OMNI-BPTM Dual Technology Ultrasonic and Passive Infrared Ceiling Sensor featuring IntelliDAPT ...................................................................... 28 OMNI-BP Ultrasonic Ceiling Sensor featuring IntelliDAPT......................................................................................................................................... 30 OMNI-BP Passive Infrared Ceiling Sensor featuring IntelliDAPT............................................................................................................................... 32 OMNI Dual Technology Acoustic and Passive Infrared Ceiling Sensor featuring IntelliDAPT .................................................................................. 34 LightOWL™ Dual Technology Ultrasonic and PIR Wall Sensor featuring IntelliDAPT............................................................................................ 36 LightOWL Passive Infrared Wall Sensor featuring IntelliDAPT................................................................................................................................... 38 LightOWL Dual Technology Passive Infrared and Acoustic Sensor featuring IntelliDAPT...................................................................................... 40 Manual ON | Automatic OFF Passive Infrared Wall Switch Sensor............................................................................................................................ 42 Automatic Passive Infrared Wall Switch Sensor............................................................................................................................................................ 44 Digital Programmable Timer ........................................................................................................................................................................................ 46 LVS Series Low Voltage Switches................................................................................................................................................................................... 48 HBA Tracker...................................................................................................................................................................................................................... 49 Universal Voltage Power Packs....................................................................................................................................................................................... 50 Universal Voltage Power Pack with Manual ON|OFF Control.................................................................................................................................... 52 RR1 Line Voltage Auxiliary Relays.................................................................................................................................................................................. 54 RRU—Line Voltage Auxiliary Relays............................................................................................................................................................................... 56 Ceiling and Wall Mount Sensor Accessories................................................................................................................................................................ 57 HBA WASP2 Occupancy Sensor.................................................................................................................................................................................... 59 Dimming WASP Occupancy Sensor.............................................................................................................................................................................. 62 WASP Lens Options........................................................................................................................................................................................................ 65
DAYLIGHTING CONTROLS Zone5™ Control Module................................................................................................................................................................................................ 68 Zone5 Ceiling and Wall Mount Occupancy Sensors................................................................................................................................................... 70 Zone5 Low Voltage Wall Switches................................................................................................................................................................................. 72 Zone5 RJ45 Adapter........................................................................................................................................................................................................ 74 Zone5 Daylight Sensor.................................................................................................................................................................................................... 76 DLC7 Continuous Dimming Control............................................................................................................................................................................. 78 Photocell Sensors............................................................................................................................................................................................................ 80 Photocell Controller.......................................................................................................................................................................................................... 82 Luxstat Dimming Control Module................................................................................................................................................................................. 84 Luxstat ON/OFF Control Module.................................................................................................................................................................................. 86 Luxstat Power Pack.......................................................................................................................................................................................................... 88 Luxstat Single Zone ON/OFF Control Module............................................................................................................................................................ 90 Luxstat Day/Night Control Module with Clock............................................................................................................................................................ 92 Luxstat Light Sensor........................................................................................................................................................................................................ 94 Luxstat Low Voltage Wall Switches................................................................................................................................................................................ 96
LIGHTING CONTROL PANELS LX Lighting Control Panels............................................................................................................................................................................................ 100 LX Relays.......................................................................................................................................................................................................................... 102 LX Breaker Control Panels............................................................................................................................................................................................. 104 LX Circuit Relays and Circuit Breakers for LXBC.......................................................................................................................................................... 106 LX Touch Tablet Graphical User Interface.................................................................................................................................................................... 108 LX Terminator.................................................................................................................................................................................................................. 109 LX Building Automation ProtoNode............................................................................................................................................................................ 110
LX JENsys........................................................................................................................................................................................................................ 112 LX Networked Switch Stations...................................................................................................................................................................................... 114 LX Keyed Switch Station................................................................................................................................................................................................ 116 LX Occupancy Sensor featuring IntelliDAPT............................................................................................................................................................... 118 LX Photo Sensor Control Module and Sensors........................................................................................................................................................... 120 LX Dry Contact Interface Module................................................................................................................................................................................. 122 LX Automatic Line Voltage Switches............................................................................................................................................................................ 124 LX Link Power Module.................................................................................................................................................................................................... 126 LX Router Repeater........................................................................................................................................................................................................ 128 LX Power Supply............................................................................................................................................................................................................. 130 LX Enclosure for DIN Rail Modules............................................................................................................................................................................... 132 LX Panel Wire Way Divider Accessory Kit.................................................................................................................................................................... 133 LX Networked Cable|Riser Rated—Riser Rated Belden 8471 Cable........................................................................................................................ 134 LX Networked Cable|Plenum Rated—Plenum Rated Windy city Wire 104500 Cable............................................................................................ 136 CX Series Commercial Lighting Control Panels.......................................................................................................................................................... 140 CX Series Commercial Lighting Control Panel Relays................................................................................................................................................ 142 CX Dimming Option Card............................................................................................................................................................................................. 144 CX Series Low Voltage Switches................................................................................................................................................................................... 145 CX Light Sensor.............................................................................................................................................................................................................. 146 CX Line V Automatic Line Voltage Switches................................................................................................................................................................ 148 CX Occupancy Sensors.................................................................................................................................................................................................. 150
WIRELESS CONTROLS wiHUBB® Access Point.................................................................................................................................................................................................... 154 wiHUBB Access Point 2.0................................................................................................................................................................................................ 156 wiHUBB Smart Pack......................................................................................................................................................................................................... 158 wiHUBB Ceiling and Wall Mount Occupancy Sensors................................................................................................................................................ 160 wiHUBB Switch Stations.................................................................................................................................................................................................. 162 wiHUBB In-Fixture Module............................................................................................................................................................................................. 164 wiHUBB On-Fixture Module........................................................................................................................................................................................... 166 wiHUBB Building Automation System Gateway Interface.......................................................................................................................................... 168 wiHUBB Antennas and Cables....................................................................................................................................................................................... 170 wiHUBB RJ45 Adapter and Cables................................................................................................................................................................................ 172 wiHUBB Daylight Sensors............................................................................................................................................................................................... 174 wiSTAR™ In-Line Switch Module................................................................................................................................................................................... 176 wiSTAR Plug-In Switch Module...................................................................................................................................................................................... 178 wiSTAR Light Sensor........................................................................................................................................................................................................ 180 wiSTAR Ceiling Mount Sensor........................................................................................................................................................................................ 182 wiSTAR Wall Mount Ceiling Sensor............................................................................................................................................................................... 184 wiSTAR Key Card Switch................................................................................................................................................................................................. 186 wiSTAR Wall Switch.......................................................................................................................................................................................................... 188 wiSCAPE™ Gateway....................................................................................................................................................................................................... 192 wiSCAPE Fixture Module................................................................................................................................................................................................ 194 wiSCAPE 480V Fixture Module...................................................................................................................................................................................... 196 wiSCAPE PLC................................................................................................................................................................................................................... 198 wiSCAPE Software Suite................................................................................................................................................................................................. 200 wiSCAPE Cellular Modem.............................................................................................................................................................................................. 202 wiSCAPE Desktop Modem............................................................................................................................................................................................. 204 wiSCAPE Photo Sensor................................................................................................................................................................................................... 206 wiSCAPE Key Pad............................................................................................................................................................................................................ 208 wiSCAPE WASP2 Motion Sensor................................................................................................................................................................................... 209 EMERGENCY BYPASS CONTROLS UL924 Enclosed 20 AMP Bypass Shunt Relay............................................................................................................................................................. 214 UL924 Enclosed 20 AMP Bypass Relay with Remote Emergency Control.............................................................................................................. 216 UL924 Enclosed 20 AMP Automatic Power Transfer Control Relay ........................................................................................................................ 218
701 Millennium Blvd. Greenville, SC 29607 hubbelllighting.com Alera Lighting Architectural Area Lighting Beacon Products Columbia Lighting Compass Life Safety Devine Lighting Dual-Lite Hubbell Building Automation Hubbell Industrial Hubbell Outdoor Kim Lighting Kurt Versen LiteControl Norlux/TRP Prescolite Progress Lighting Security Lighting Systems Spaulding Lighting Sportsliter Solutions Sterner Whiteway
9601 Dessau Road | Building One | Austin, Texas 78754 | 512-450-1100 | 512-450-1215 fax | www. hubbell-automation.com