Government Office Building

Page 1

BROWARD COUNTY ADMINISTRATOR BERTHA HENRY

BOARD OF COUNTY COMMISSIONERS TIM RYAN; MAYOR MARTIN DAVID KIAR, VICE MAYOR MARK D. BOGEN STACY RITTER CHIP LAMARCA LOIS WEXLER BEAM FURR BARBARA SHARIFF DALE V.C. HOLNESS

GOVERNMENT CENTER WEST FOURTH FLOOR INTERIOR RENOVATION 1 N UNIVERSITY DRIVE, PLANTATION, FL 33324

100% CONSTRUCTION DOCUMENTS 02/28/2017


A102 Fourth Floor Plan A103 Fourth Floor Plan Wall Sections and Details

M101 Fourth Floor Mechanical Plan M102 Fourth Floor Mechanical Plan M103 Fourth Floor Mechanical Plan M201 Fourth Floor Mechanical Notes & Details E101

Fourth Floor Electrical Power Plan

E102 E103

Fourth Floor Electrical Power Plan

E202 E203

Fourth Floor Electrical Power Plan Fourth Floor Electrical Lighting Plan Fourth Floor Electrical Lighting Plan Fourth Floor Electrical Lighting Plan

Fourth Floor Electrical Notes & Details FS101 Fourth Floor Fire Sprinkler Plan FS102 Fourth Floor Fire Sprinkler Plan

-

E301

FS103 Fourth Floor Fire Sprinkler Plan LS101 Fourth Floor Life Safety Plan

NOTE:

SCOPE OF WORK FOR PHASE 3A INCLUDES THE DIRECT REPLACEMENT OF INDICATED CUBICAL WORK STATIONS ONLY.

GENERAL NOTES General Notes 1. All work shall be performed in accordance with all codes, rules, regulations and restrictions having jurisdiction on this project.

PHASE 2

PHASE 3 & 3A

2. Work shall include all items indicated on these drawings, unless otherwise noted.

REF

-

1 North University Drive Plantation, FL 33324

A101 Fourth Floor Plan

E201

2/28/2017 Issue For Permit

12/14/2016 Revision

X X X X X X X X X X X X - - X - - X - - X X X X X X X X X

Fourth Floor Interior Renovation

D102 Fourth Floor Demo Plan D103 Fourth Floor Demo Plan

Building Location Plan

-

3321 NW 97 Avenue Sunrise, FL 33351 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

Government Center West

D101 Fourth Floor Demo Plan

1 CS N.T.S.

8/18/2016 Furniture Revision

A010 Cover Sheet - Project Information

A201

-

Drawing has been superseded - Do not use.

Wall Sections and Details

PROJECT LOCATION

7/7/2016 100 Percent

-

Current drawing

1/15/2016 90 Percent

X

11/29/2016 Furniture Electric Rev.

Sheet Index

CODE REFERENCES FLORIDA BUILDING CODE, 5th EDITION (2014) FLORIDA EXISTING CODE, 5th EDITION (2014) NATIONAL ELECTRICAL CODE 2011 NATIONAL FIRE PROTECTION ASSOCIATION 72-2010 NATIONAL FIRE PROTECTION ASSOCIATION 13-2010 FLORIDA FIRE PREVENTION CODE 2012

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

3. The contractor shall verify all dimensions prior to construction. Square one architecture, inc. Shall be notified of any RAMP UP

deviation from the plans prior to construction. Drawings shall not be scaled.

RAMP UP

RAMP UP

No. 1 2 3

BUILDING INFORMATION

MECHANICAL ROOM

Description 90 Percent 100 Percent Issue For Permit

Date 1/15/2016 7/7/2016 2/28/2017

4. The contractor shall acquaint themselves with the site and shall verify all field conditions prior to actual construction. Any deviation from the construction documents discovered at the time shall be reported by the contractor immediately to Square One Architecture, inc.

Existing Construction Type: III

REF

F.B.C. Occupancy: B (Business) Civic administration, office.

VENDINGVENDING MACHINEMACHINE

5. Fire protection design, calculations & data shall be provided by licensed fire protection company.

Level of Alteration: II FE

6. All Material substitutions shall be approved as equal by the Architect

RAMP UP

EXIST'G STAIR

EXIST'G STAIR

7.To maintain clearance for existing sprinkler system, all furniture shall not exceed 18" from bottom of sprinkler heads.

FLORIDA FIRE PREVENTION INFORMATION

OCCUPANT LOAD

FE

NO WORK

PHASE 1

Building Area: The scope of work reconfigures the interior space and does not change the building area.

FFPC & NFPA Occupancy Classification: Assembly

EXIST'G STAIR

Minimum corridor width = 44" Minimum corridor and door width at 0.22" per person: 36" door: 34"x0.22=154 persons. Wall and Ceiling Finish Classification: A or B. Assembly enclosed stairways shall be class A only..

Occupant Load Business: The building occupancy is Business. The scope of work reconfigures the interior space and does not change the occupant load. John Norman Garra Florida Architect AR92545

Code reference: Florida Building Code Section 1004 Occupant Load

COVER SHEET

Floor Finish Classification: I or II. Assembly enclosed stairways shall be class II only.

Date

1 CS

FOURTH FLOOR PHASING PLAN 1

Drawn by

32" = 1'

2-28-2017 Ian Monday

A 010 Scale COPYRIGHT 2016

N.T.S.


DEMO FLOOR PLAN LEGEND # DESCRIPTION

PHASE 2

PHASE 3 & 3A

No work

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP

Concrete Column. Do Not Disturb

RAMP UP

RAMP UP

1 Remove existing partition wall 2 Remove portion of existing partition wall 3 Remove existing window and salvage for reuse Salvage existing furniture to be removed, and relocate in new 4 location. 5 Remove existing door. 6 Remove existing cubical work station during phase 3A only.

MECHANICAL ROOM

Existing partition wall to be removed Existing wall to remain. Do not disturb.

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.Sq-1.net

REF VENDINGVENDING MACHINEMACHINE

NOTES

N

LEGEND

Existing door to be removed

Notes:

RAMP UP

EXIST'G STAIR

Existing door to remain. Do not Disturb. EXIST'G STAIR

PHASE 1

2 D101

Existing cubical workstations to remain until Phase 3A. During Phase 3A cubical workstations shall be removed for direct replacement .

Fourth Floor Demo Key Plan

1

D101 1 " = 1'-0" 32

67/42

67/42

67/24

67/18

67/18

67/24

67/48

67/48

67/18

67/30

67/42

67/48

67/48

67/24

67/18

67/48

67/18 67/60

67/18 67/18

67/48

FE

48

67/18 67/18 67/18

67/18 67/18

67/30

67/18

67/18

67/18

67/18

67/24

36

67/24

42 / 42 /3 6

30 /2

4

/ 67

67/24

67/36

48 48 / 67

67 67 /1

8

67/42

4

8 /1

6 67

/

36

36 36 / 67

30 /

48

36 36 36 / 67

67/42

40/36

40/24

67

67/48

67/48

67/24

67/48

67/24

30/24

36/24

36/24 60

67/30

67/48

67/48

67/36

67/36

67/36

67/36

4 /2

6

67

/3

67 /3

4

John Norman Garra Florida Architect AR92545

FOURTH FLOOR DEMOLITION PLAN

RAMP UP

EXIST'G STAIR

MECHANICAL ROOM

67

6 /3

6

/3 67

67 /

6

36

67

4

30

/3

6

/4 67

/4

8

8

40/36

VENDINGVENDING MACHINEMACHINE

30 /4

8

1 7/

8

67

30 /2 4

67/36

60

60

/2

67 /1 8

67/36 67/36

30 /3 0

36/24 36/24 48/24

67/36

24/24

67/48

4 /2 24

67/24

85/24

67/60

81/60

48

67/18

85/24

67/18

85/24

67/18 67/18

81/60

85/24 85/48

67/18 67/18 67/18

24/24

48

1

67/18

81/18

67/18

85/36

67/48

60/24

67/60

67/60

60

60/24

67/60

60

60/24

67/60

60

60/24

67/18 67/18

67/60 67/30

60/24

67/18

4

4

/2

72

67 36 /3 6

67/24

67/30

67/30

81/60

67/48

67/30

67/24

4 /2

48 /2

TRASH / RECYCLE

4

67 /3 6

67/18 67/18

67/18

/2

36

67 3 6 /3 6

67/18

72

67

48

4 /2

67 /

67/18

1

4

67/48

67/24

67/18 67/48

Date 7/72016 8/182016 2/28/2017

4

4 /2 60

67 60 /6 0

81/18

67/48

67/48

67/48

Description 100 Percent Furniture Revision Issue For Permit

No. 1 2 3

30 /2 24 /2

36

1

67/48

67/36

67/36

67/48

67/48

67/48

67/60

67/42

48

67/24

67/18

85/36

67/48

67/48

81/18 81/18

67/30

0

60/24

67

REF

/3

67/48 48/24

42

67/36

67/48

67/24

67/30

67/30

67/30

67/18

67/48

67/36 60/24

60/24

PHASE 2

67/24

60/24

60

60/24

60/24

67/24

67/48

67/60

48

67/42

60

67/42

48

48 67/48

67/24

48 60/24

67/24

67/24

67/48

67/36 67/18 67/18

67/24

67/48

67/48

67/48

48

67/36

67/48

48

67/42

67/30

67/48

48

67/18

48/24

48

30

48

67/48 67/24

48/24

67/48 67/24

30/24

67/48

24/24

48/24

48

67/48

67/18

67/48

48/24

72/24

67/48

72/24

60/24

60/24

60

48

67/48

67/18

67/36

48/24

67/18

67/48

36/24

67/48

48/24

67/18

36/24

1 North University Drive Plantation, FL 33324

EXIST'G STAIR

Government Center West

Existing furniture to remain. Do not Disturb.

Fourth Floor Interior Renovation

Existing furniture to be removed

Date Drawn by

FE

N

D 101

5

2

D101

RAMP

2-28-2017 Ian Monday

Fourth Floor Partial Demo Plan (Phase 1) 3

16" = 1'-0"

Scale COPYRIGHT 2016

Varies


DEMO FLOOR PLAN LEGEND # DESCRIPTION

LEGEND PHASE 2

PHASE 3 & 3A

No work

N

REF

1 Remove existing partition wall 2 Remove portion of existing partition wall 3 Remove existing window and salvage for reuse Salvage existing furniture to be removed, and relocate in new 4 location. 5 Remove existing door. 6 Remove existing cubical work station during phase 3A only.

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

Concrete Column. Do Not Disturb

RAMP UP RAMP UP

RAMP UP

2

Existing partition wall to be removed

MECHANICAL ROOM

D102

Existing wall to remain. Do not disturb.

VENDINGVENDING MACHINEMACHINE

NOTES

REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.Sq-1.net

Existing door to be removed

Notes:

RAMP UP

Existing door to remain. Do not Disturb.

EXIST'G STAIR

PHASE 1

EXIST'G STAIR

EXIST'G STAIR

Existing cubical workstations to remain until Phase 3A. During Phase 3A cubical workstations shall be removed for direct replacement .

1

Fourth Floor Demo Key Plan

D102 1 " = 1'-0" 32

36 36

BBF

72/24

67/36 67/36

60(4)

36

67/60

72/24

36

67/36 67/36

72/24

36

67/36

67/24

67/24

67/24

67/30

67/48

67/36

67/48

67/48

67/30

BBF

FF 67/18

67/24

67/48

67/24

67/18

67/48

67/48

67/48

67/18 67/18

67/48

72/24

67/18 67/18

30/48

67/48 48

48 67/48

48 30/48

67/36

36

67/36

72/24

36

67/36

67/48

BBF

42/48

67/48

67/48

67/48 48

48 67/48

42/48

42/48

67/24

30/48

67/48 48

48 67/48

30/48

48

30/48

30/48 30/48

48

67/24

48

24/24

30/48

48

24/24

67/48

24/24

67/18

24/24

67/36 GL

30/24

30/48

48

BBF

36/24

67/24

36

30/48

67/18 67/18 67/24

72/24

FF

67/18

60

42/48

60/24

67/18

60/24

42/48

67/18

36

24/24

67/60

48(4)

42/48

30/24

36(4)

42/48

24/24

42/48

30/48

36(2)

24/24

3

42/48

30/48

30/24

30/24

1 North University Drive Plantation, FL 33324

Government Center West

Existing furniture to remain. Do not Disturb.

Fourth Floor Interior Renovation

Existing furniture to be removed

36/24

36/24

30/48

67/36

72/24

48/24

67/48

67/48

36/24

67/36

42/48

3

67/48

67/36 67/48

67/48 BBF

BBF

67/18

36

42/48

67/48

67/48

48/24

48/24

67/48

67/48

67/48

67/24

Date 7/72016 8/18/2016 2/28/2017

67/24 67/18

67/48

67/48

2

Description 100 Percent Furniture Revision Issue For Permit

No. 1 2 3

67/18

48/24

67/48

67/36

60/24

67/36

24/24

48/24

48/24

48/24

48

67/48

48/24

48

67/24

67/18

67/36

36

67/36

48

67/48

48/24

67/18

48

67/36 67/36 67/48

48/24 36/24

67/18

67/30

67/18

67/48

67/48

67/18

67/18

67/48

67/48 67/36

67/30

67/48

67/48

67/48

5

67/24

48

67/30

67/36

67/18

67/24

67/48 48

N Date

Drawn by 67/48

67/18 67/18

67/18 36/24

67/48

2

D102 3 " = 1'-0" 16

FOURTH FLOOR DEMOLITION PLAN

60/24

PHASE 1

Fourth Floor Partial Demo Plan (Phase 2)

60

67/24

67/24

48

67/24

John Norman Garra Florida Architect AR92545

67/48

36/24

60

MECHANICAL ROOM

67/60

67/42

48/24

67/48

67/18 67/18

67/60

67/36

60 60/24

67/36

67/36

67/48

67/48

67/30 67/18

67/30

36/24

RAMP UP

48 67/48

48 67/48

30/48 42/48

RAMP UP

67/48

67/36

67/48 48

67/48 48

RAMP UP

67/36 67/48

67/48 67/36

42/48

67/48

2 48/24 67/48

67/18

48/24

5

67/18

67/18

36

5

67/18

36

30/48

2

67/18

36

2

36

67/48

BBF

30/48

42/48

67/18

48

FF

1

2

5

36

EXISTING FMD SUPERVISOR'S OFFICE

BBF

48/24

BBF

48/24

67/18

1

24/24

30/48

42/48

30/24

48

67/24

48/24

36

36

67/60

30/30

67/48

67/18

2

EXIST'G STAIR

67/48

67/48

30/24

48/24

3

REF

67/36

42/18

67/60 GL

42/48

24/24

48

67/48

1

42/24

67/24

48

67/36

42/48

67/48

67/60

60

60

67/60

42/48

67/48

1

42/48

67/36

67/18

67/48

67/24

48

42/48

67/18

72/24

67/48 48

67/60 GL

48

42/48

60(3)

30

42/48

48(3)

30/24

48

48(3)

30

42/48

67/60

30/24

42/48

67/48

48

30/48

42/48

67/48

48/24

30/48

42/48

30/48

42/48

48 67/48

1

67/42

67/42

2-28-2017 Ian Monday

D 102

67/48

Scale COPYRIGHT 2016

Varies


DEMO FLOOR PLAN LEGEND # DESCRIPTION

LEGEND

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

Concrete Column. Do Not Disturb

RAMP UP RAMP UP

RAMP UP

2

Existing partition wall to be removed

MECHANICAL ROOM

D103

Existing wall to remain. Do not disturb.

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.Sq-1.net

REF VENDINGVENDING MACHINEMACHINE

Existing door to be removed

Notes:

RAMP UP

EXIST'G STAIR

Existing door to remain. Do not Disturb.

PHASE 1

EXIST'G STAIR

Government Center West

EXIST'G STAIR

Existing cubical workstations to remain until Phase 3A. During Phase 3A cubical workstations shall be removed for direct replacement .

1

Fourth Floor Key Plan

42/48

42/48

42/48

42/48

67/48 48 67/48 48

30/48

48 67/48

67/48 48 67/48 48

42/48

42/48

30/48

48 67/48

42/48

48 67/48

42/48

42/48 42/48

48 67/48

30/48 42/48

30/48

42/48

30/48

67/48 48 67/48 48

42/48

42/48

42/48

67/48 48 67/48 48

30/48

48 67/48 48 67/48

42/48

48 67/48

30/48

67/48 67/48

42/48

48

30/48 42/48

48 67/48

30/48

67/48 67/48

42/48

48 48

42/48

30/48

48

30/48

42/48

42/48

30/48

42/48

42/48

30/48

6

42/48

30/48

30/48

6

42/48

30/48

6

30/48

6

30/48

30/48

D103 1 " = 1'-0" 32

1 North University Drive Plantation, FL 33324

Existing furniture to remain. Do not Disturb.

Fourth Floor Interior Renovation

Existing furniture to be removed

30/48 42/48

42/48

6 1

PHASE 2

6

42/48

30/48 48 67/48

48 67/48

30/48 30/48

6

42/48

42/48

67/48 48

6

67/48 48

EXIST'G STAIR

Date 7/72016 8/18/2016 2/28/2017

42/48

30/48

REF

Description 100 Percent Furniture Revision Issue For Permit

No. 1 2 3

42/48 42/48

NOTES

1 Remove existing partition wall 2 Remove portion of existing partition wall 3 Remove existing window and salvage for reuse Salvage existing furniture to be removed, and relocate in new 4 location. 5 Remove existing door. 6 Remove existing cubical work station during phase 3A only.

PHASE 2

PHASE 3 & 3A

No work

N

2

RAMP UP

6

John Norman Garra Florida Architect AR92545

RAMP UP

FOURTH FLOOR DEMOLITION PLAN

N Date

Drawn by

2

D 103

Fourth Floor Partial Demo Plan (Phase 3 & 3A)

D103 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2016

Varies


X

-1 3/4"

-3'-0" x 8'-0"

#

NOTES

2

N

LEGEND

1 Install new partition wall 2 Install salvaged office furniture in new location. 3 Install new direct replacement workstation cubicles during PHASE 3A only.

PHASE 2

PHASE 3 & 3A

No work

REF

Concrete Column. Do Not Disturb New partition wall to be Installed

Notes: 1.Reference RCP lighting & mechanical plans to confirm location of new walls with ceiling grid above. 2.Install all new furniture as per Legend

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

Existing door shall remain. Do not disturb. Flush wood door with wood frame, stained to match existing. Three hinges to match existing interior doors THK: T.M.E. Fin:wood to match existing interior doors.Door hardware: Entry lock with lever handle to meet ADA requirements. Metal door with metal frame, stained to match existing. Three hinges to match existing interior doors. Door shall Metal 3'-0" x 8'-0" 1 3/4" have electronic card reader security lock. THK: T.M.E. Fin:wood to match existing interior doors. 1. Jamb depth shall be verified in field. 2. Doors shall have lever handles to meet ADA requirements. 3. All product substitutions shall be approved as equal by the Architect. 4. Door with access control system shall not be locked from the egress side.

1

-Wood

FLOOR PLAN LEGEND DESCRIPTION

RAMP UP

Existing wall to remain. Do not disturb.

MECHANICAL ROOM

New door to be installed

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.Sq-1.net

Existing door to remain. Do not Disturb. REF

SIZE A

48" x 89"

Fixed window. To match existing

B

36" x 96"

Fixed window. To match existing

NOTES

VENDINGVENDING MACHINEMACHINE

WINDOW SCHEDULE DESCRIPTION

New furniture to be installed RAMP UP

EXIST'G STAIR

New location of salvaged furniture to be installed

1. All exterior windows to remain 2.Windows frame and glazing color shall be selected by Owner and Architect. 3. All glazing at hazardous locations such as tub, shower enclosures, windows, etc., shall comply with Chapter 24 of the F.B.C. 4 Contractor shall verify all jamb thicknesses prior to ordering.

EXIST'G STAIR

PHASE 1

Existing furniture to remain. Do not Disturb.

2 A101

Government Center West

EXIST'G STAIR

Fourth Floor Key Plan

1

X

X

10'-2 1/2"

1

ALIGN NEW WALL WITH EXISTING COLUMN EDGE

A101 1 " = 1'-0" 32

11'-0 1/2"

X

FE

1

A

10'-5"

1

1

1

X

X

X

X

1

Fourth Floor Interior Renovation

New cubical workstations direct replacement - during phase 3A only.

1 North University Drive Plantation, FL 33324

THK FIN

NOTES

# SIZE

DOOR SCHEDULE REMARKS

Description 100 Percent Furniture Revision Issue For Permit

Date 7/72016 8/182016 2/28/2017

1

X

X VENDINGVENDING MACHINEMACHINE

X

MECHANICAL ROOM

X

2

X

X

REF

X

X

1

TRASH / RECYCLE

X

1

X

X X

X

X

1

4'-6"

2'-9 1/2"

PHASE 2

1'-6"

1

No. 1 2 3

EXIST'G STAIR

2

John Norman Garra Florida Architect AR92545

RAMP UP

FOURTH FLOOR PLAN

Date FE

X

X

X

X

X

B

X

Drawn by

2

N

A 101

Fourth Floor Partial Plan (Phase 1)

A101 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2016

Varies


THK FIN

X

-1 3/4"

NOTES

Existing door shall remain. Do not disturb. Flush wood door with wood frame, stained to match existing. Three hinges to match existing interior doors THK: T.M.E. Fin:wood to match existing interior doors.Door hardware: Entry lock with lever handle to meet ADA requirements. Metal door with metal frame, stained to match existing. Three hinges to match existing interior doors. Door shall 3'-0" x 8'-0" 1 3/4" Metal have electronic card reader security lock. THK: T.M.E. Fin:wood to match existing interior doors. 1. Jamb depth shall be verified in field. 2. Doors shall have lever handles to meet ADA requirements. 3. All product substitutions shall be approved as equal by the Architect. 4. Door with access control system shall not be locked from the egress side.

PHASE 2

PHASE 3 & 3A

No work

N

REF

Concrete Column. Do Not Disturb New partition wall to be Installed

Notes: 1.Reference RCP lighting & mechanical plans to confirm location of new walls with ceiling grid above. 2.Install all new furniture as per Legend

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

2

LEGEND

1 Install new partition wall 2 Install salvaged office furniture in new location. 3 Install new direct replacement workstation cubicles during PHASE 3A only.

-Wood

NOTES

1

-3'-0" x 8'-0"

#

FLOOR PLAN LEGEND DESCRIPTION

RAMP UP

Existing wall to remain. Do not disturb.

2 New door to be installed

MECHANICAL ROOM

A102 5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

Existing door to remain. Do not Disturb. REF

SIZE A

48" x 89"

Fixed window. To match existing

B

36" x 96"

Fixed window. To match existing

NOTES

VENDINGVENDING MACHINEMACHINE

WINDOW SCHEDULE DESCRIPTION

New furniture to be installed RAMP UP

EXIST'G STAIR

New location of salvaged furniture to be installed

PHASE 1

EXIST'G STAIR

1. All exterior windows to remain 2.Windows frame and glazing color shall be selected by Owner and Architect. 3. All glazing at hazardous locations such as tub, shower enclosures, windows, etc., shall comply with Chapter 24 of the F.B.C. 4 Contractor shall verify all jamb thicknesses prior to ordering.

Existing furniture to remain. Do not Disturb.

1

Government Center West

EXIST'G STAIR

Fourth Floor Key Plan

A102 1 " = 1'-0" 32 ALIGN NEW WALL WITH EXISTING COLUMN EDGE

ALIGN NEW WALL WITH EXISTING COLUMN EDGE

X ALIGN WITH EXISTING OVERHEAD LIGHT & GRID

EXISTING LIGHT FIXTURE ABOVE

ALIGN

X

1 1

1 2'-1 1/2"

A

2 X

1

X

1

REF

X

NEW RETURN AIR GRILL ABOVE

X

X

3'-3 1/2"

1

A

1

EXISTING FMD SUPERVISOR'S OFFICE

7'-5 3/4"

1

2

9'-5 3/4"

1

Description 100 Percent Furniture Revision Issue For Permit

No. 1 2 3

Date 7/72016 8/182016 2/28/2017

X 1

1

1 11'-2 1/2"

X

X

NEW RETURN AIR GRILL ABOVE

10'-5"

EXISTING LIGHT FIXTURE ABOVE

1 4'-6"

EXIST'G STAIR

12'-10 1/2"

X

X

1 2

A

2

RAMP UP

B

X

RAMP UP

RAMP

ALIGN NEW WALL WITH EXISTING COLUMN EDGE

A

1

1

1

1

X

10'-2 1/2"

10'-5" 1'-6"

1 X

1

1

11'-0 1/2"

5'-0"

2'-9 1/2"

ALIGN NEW WALL WITH EXISTING COLUMN EDGE

2'-9 1/2"

2

2'-8"

ALIGN WITH EXISTING OVERHEAD LIGHT & CEILING GRID

PHASE 3 & 3A

Fourth Floor Interior Renovation

New cubical workstations direct replacement - during phase 3A only.

1 North University Drive Plantation, FL 33324

# SIZE

DOOR SCHEDULE REMARKS

John Norman Garra Florida Architect AR92545

1 1

FOURTH FLOOR PLAN

4'-6"

MECHANICAL ROOM

N Date

X

Drawn by

PHASE 1

2

A 102

Fourth Floor Partial Plan (Phase 2)

A102 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


-1 3/4"

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

Concrete Column. Do Not Disturb RAMP UP

New partition wall to be Installed

Notes: 1.Reference RCP lighting & mechanical plans to confirm location of new walls with ceiling grid above. 2.Install all new furniture as per Legend

RAMP UP

2

Existing wall to remain. Do not disturb.

MECHANICAL ROOM

A103

New door to be installed

B

36" x 96"

Fixed window. To match existing

EXIST'G STAIR

New location of salvaged furniture to be installed

1. All exterior windows to remain 2.Windows frame and glazing color shall be selected by Owner and Architect. 3. All glazing at hazardous locations such as tub, shower enclosures, windows, etc., shall comply with Chapter 24 of the F.B.C. 4 Contractor shall verify all jamb thicknesses prior to ordering.

PHASE 1

Existing furniture to remain. Do not Disturb.

New cubical workstations direct replacement - during phase 3A only. EXIST'G STAIR

1

Government Center West

Fixed window. To match existing

RAMP UP

EXIST'G STAIR

Fourth Floor Key Plan

A103 1 " = 1'-0" 32

X

1

NEW RETURN AIR GRILL ABOVE

5'-2 1/2"

1 12'-4 3/4"

5'-6 1/2"

1

ALIGN NEW WALL WITH EXISTING COLUMN EDGE

X

1

7'-8 3/4"

1 3

3

3

3

X

1 3

2 3

Description 100 Percent Furniture Revision Issue For Permit

No. 1 2 3

PHASE 2

Date 7/72016 8/182016 2/28/2017

X

X

X

X

REF

9'-9 1/2"

48" x 89"

New furniture to be installed

X

1

EXISTING CEILING DIFFUSER ABOVE

EXIST'G STAIR

9'-2 1/2"

A

VENDINGVENDING MACHINEMACHINE

WINDOW SCHEDULE DESCRIPTION

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

REF

Existing door to remain. Do not Disturb.

SIZE

NOTES

1 Install new partition wall 2 Install salvaged office furniture in new location. 3 Install new direct replacement workstation cubicles during PHASE 3A only.

10'-0"

NOTES

Existing door shall remain. Do not disturb. Flush wood door with wood frame, stained to match existing. Three hinges to match existing interior doors THK: T.M.E. Fin:wood to match existing interior doors.Door hardware: Entry lock with lever handle to meet ADA requirements. Metal door with metal frame, stained to match existing. Three hinges to match existing interior doors. Door shall Metal 3'-0" x 8'-0" 1 3/4" have electronic card reader security lock. THK: T.M.E. Fin:wood to match existing interior doors. 1. Jamb depth shall be verified in field. 2. Doors shall have lever handles to meet ADA requirements. 3. All product substitutions shall be approved as equal by the Architect. 4. Door with access control system shall not be locked from the egress side.

REF

RAMP UP

2

-Wood

No work

5'-9"

1

-3'-0" x 8'-0"

PHASE 2

PHASE 3 & 3A

LEGEND

1 North University Drive Plantation, FL 33324

X

#

FLOOR PLAN LEGEND DESCRIPTION

Fourth Floor Interior Renovation

THK FIN

NOTES

# SIZE

DOOR SCHEDULE REMARKS

N

3 3

RAMP UP John Norman Garra Florida Architect AR92545

3

RAMP UP

FOURTH FLOOR PLAN

Date Drawn by

N 2

A 103

Fourth Floor Partial Plan (Phase 3 & 3A)

A103 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


INSTALL NEW 81" THICK STRUCTURAL STEEL PLATE TO ALIGN WITH EXISTING FLOOR SYSTEM. SLICES SHALL BE OVER PEDESTALS ONLY. ALL FASTENERS SHALL BE COUNTER-SUNK AND FLUSH. PEDESTALS SHALL MATCH EXISTING AND BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS @ 24" 0.C.

BOTTOM OF EXISTING CONC. SLAB +10'-0 21 "

+10'-0 "

TOP OF EXISTING RAISED FLOOR 0'-0" -0'-6 21"

EXISTING CONCRETE FLOOR SLAB.

EXISTING STEEL WIRE TO EXISTING STRUCTURE ABOVE.

EXISTING STEEL WIRE TO EXISTING STRUCTURE ABOVE.

EXISTING 6 41" FIBERGLASS BATT INSULATION.

EXISTING 6 41" FIBERGLASS BATT INSULATION.

EXISTING 24" x 24" ACOUSTIC CEILING TILE.

EXISTING 24" x 24" ACOUSTIC CEILING TILE.

BOTTOM OF EXISTING CEILING VARIES

FLOOR DETAIL - WALL TO BE REMOVED

INSTALL NEW CEILING TILE TRACK EACH SIDE OF WALL.

INSTALL DRYWALL CAP.

PORTION OF WALL REMOVED.

WALL DETAIL - WALL REMOVED BETWEEN CEILING GRID2 WALL DETAIL - WALL REMOVED BELOW CEILING GRID A201 3" = 1'-0" 4

1. 2. 3. 4.

See Fire Prevention Information on A010-Cover Sheet. Steel Framing: ClarkDietrich, 25 gauge steel framing or equal. Gypsum Board: National Gypsum, GrindMarX, 4'X8", 5/8" thick or equal. Acoustical Insulation: Owens and Corning, Eco touch Propink fiberglass insulation, R-11, 16"x96" or equal.

*All material substitutions shall be approved as equal by the Architect.

1 North University Drive Plantation, FL 33324

A201 3" = 1'-0" 4

Fourth Floor Interior Renovation

1

PORTION OF WALL REMOVED.

Government Center West

N.T.S.

+8'-2 21 " INSTALL NEW 24" x 24" ACOUSTIC CEILING TILE T.M.E. INSTALL NEW "T" TRACK T.M.E. WITH 12 GA. STEEL WIRE @ 48" O.C. TO EXISTING STRUCTURE ABOVE.

+8'-2 "

INSTALL DRYWALL CAP.

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.Sq-1.net

BOTTOM OF EXISTING CEILING VARIES

1 2

EXISTING PORTION OF WALL TO REMAIN ABOVE CEILING.

INSTALL NEW 4" LONG 25 GA. TOP STEEL TRACK WITH WITH (2) 0.145 DIA. P.A.F.

EXISTING ROOF CONCRETE SLAB

EXISTING ROOF CONCRETE SLAB

BOTTOM OF EXISTING CONC. SLAB

BOTTOM OF EXISTING CONC. SLAB

1 2

+10'-0 21 "

+10'-0 " EXISTING STEEL WIRE TO EXISTING STRUCTURE ABOVE.

EXISTING STEEL WIRE TO EXISTING STRUCTURE ABOVE.

INSTALL NEW 3-5/8" X 1-1/4", 25 GA. STEEL STUD BRACING @ MIN. 48" 0.C. EXISTING 6 41" FIBERGLASS BATT INSULATION.

EXISTING 6 41" FIBERGLASS BATT INSULATION.

INSTALL NEW 6" LONG 25 GA. STEEL BOTTOM TRACK AT WINDOW ROUGH OPENING HEAD.

EXISTING 24" x 24" ACOUSTIC CEILING TILE.

2 3/4"

EXISTING 24" x 24" ACOUSTIC CEILING TILE.

BOTTOM OF EXISTING CEILING VARIES +8'-2 21 "

Description 100 Percent Issue For Permit

No. 1 2

Date 7/7/2016 2/28/2017

BOTTOM OF EXISTING CEILING VARIES +8'-2 21 "

INSTALL NEW 18 GA. TOP STEEL TRACK WITH SHEET METAL SCREWS @ 48" 0.C. MIN. AND INTO EXISTING METAL GRID ONLY. NO FASTENERS SHALL BE INSTALLED IN ACOUSTIC PANELS.

INSTALL NEW Clark Dietrich, 3-5/8" X 1-1/4", 18 GA. STEEL STUDS (OR EQUAL) @ 16" 0.C.

INSTALL NEW ALUMINUM FRAME INTERIOR WINDOW. GLAZING SHALL BE SAFETY GLASS PER F.B.C. CHAPTER 24

INSTALL NEW ACOUSTICAL INSULATION. OWENS AND CORNING, ECOTOUCH PROPINK FIBERGLASS, R-11, 16"x96" (OR EQUAL)

8'-3 1/4"

INSTALL NEW 18 GA. TOP STEEL TRACK WITH SHEET METAL SCREWS @ 48" 0.C. MIN. AND INTO EXISTING METAL GRID ONLY. NO FASTENERS SHALL BE INSTALLED IN ACOUSTIC PANELS.

7'-6" WINDOW

A201

BOTTOM OF EXISTING CONC. SLAB 1 2

TOP OF EXISTING CONC. FLOOR SLAB

8

EXISTING ROOF CONCRETE SLAB

INSTALL NEW 3-5/8" X 1-1/4", 18 GA. STEEL FRAMING BLOCKING INSTALL 0NE (1) LAYER 5/8" THK. GYPSUM BOARD. NATIONAL GYPSUM, GRINDMARX, 4'x8' (OR EQUAL). EACH FACE OF STUD WITH DRYWALL SCREWS ACCORDING TO GA 216-00 "APPLICATIONS & FINISHING OF GYPSUM BOARD".

INSTALL NEW Clark Dietrich, 3-5/8" X 1-1/4", 18 GA. STEEL STUDS (OR EQUAL) @ 16" 0.C. INSTALL 0NE (1) LAYER 5/8" THK. GYPSUM BOARD. NATIONAL GYPSUM, GRINDMARX, 4'x8' (OR EQUAL). EACH FACE OF STUD WITH DRYWALL SCREWS ACCORDING TO GA 216-00 "APPLICATIONS & FINISHING OF GYPSUM BOARD".

INSTALL NEW 18 GA. BOTTOM METAL TRACK WITH 1 4"

DIA.

1 2"

INSTALL NEW 18 GA. BOTTOM METAL TRACK WITH 1 4"

SELF TAPPING METAL SCREWS @ 48" 0.C.

DIA. 21" SELF TAPPING METAL SCREWS @ 48" 0.C.

INSTALL NEW 4" RUBBER COVE BASE T.M.E. EXISTING STEEL RAISED ACCESS FLOOR SYSTEM.

INSTALL NEW 4" RUBBER COVE BASE T.M.E. EXISTING STEEL RAISED ACCESS FLOOR SYSTEM.

TOP OF EXISTING RAISED FLOOR 0'-0"

A201

Wall Section 3

4 " = 1'-0"

SECTIONS & DETAILS TOP OF EXISTING RAISED FLOOR 0'-0"

TOP OF EXISTING CONC. FLOOR SLAB

TOP OF EXISTING CONC. FLOOR SLAB

-0'-6 21"

-0'-6 21"

EXISTING CONCRETE FLOOR SLAB.

3

John Norman Garra Florida Architect AR92545

6 1/2"

EXISTING STEEL RAISED ACCESS FLOOR SYSTEM.

EXISTING ROOF CONCRETE SLAB

Date Drawn by

EXISTING CONCRETE FLOOR SLAB.

4

A201

A 201

Wall Section - Window 3 4 " = 1'-0"

2-28-2017 Ian Monday

Scale COPYRIGHT 2016

Varies


N

PHASE 2

PHASE 3 & 3A REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

RAMP UP

MECHANICAL ROOM

REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

RAMP UP

EXIST'G STAIR

M101

Fourth Floor Mechanical Key Plan

M101 1 " = 1'-0" 32

20x16

470 CFM : 350 CFM

5

NEW CD

14x16

1 North University Drive Plantation, FL 33324

1

2

Fourth Floor Interior Renovation

EXIST'G STAIR

PHASE 1

Government Center West

EXIST'G STAIR

5

NEW RG

6

NEW CD

FE

Description 100 Percent Issue For Permit

No. 1 2

Date 7/7/2016 2/28/2017

EXIST. 20x16 LP DUCT

2

8

4

RELOCATE

PHASE 2

VENDINGVENDING MACHINEMACHINE

John Norman Garra Florida Architect AR92545

EXIST'G STAIR

MECHANICAL ROOM

REF

RAMP UP

FOURTH FLOOR MECHANICAL PLAN Date Drawn by

FE

2-28-2017 Ian Monday

N 2

M 101

Fourth Floor Mechanical Partial Plan (Phase 1)

M101 3 " = 1'-0" 16

Scale COPYRIGHT 2015

Varies


N

PHASE 2

PHASE 3 & 3A REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

RAMP UP

2

MECHANICAL ROOM

M102 REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

RAMP UP

EXIST'G STAIR

1

Fourth Floor Mechanical Key Plan

M102 1 " = 1'-0" 32

400 CFM : 250 CFM

7

1 North University Drive Plantation, FL 33324

Government Center West

EXIST'G STAIR

Fourth Floor Interior Renovation

PHASE 1

EXIST'G STAIR

320 CFM : 225 CFM

7 RELOC ATE

PHASE 3 & 3A

3

6

5

1

NEW CD

5

NEW RG NEW CD

NEW CD

5

7

EXISTING FMD SUPERVISOR'S OFFICE RELOCATE

EXIST'G STAIR

10x16

NEW CD

400 CFM : 115 CFM

6

1 3

6

14x12

6

Date 7/7/2016 2/28/2017

EXIST. 14" LP DUCT

5

REF

Description 100 Percent Issue For Permit

No. 1 2

7

190 CFM : 90 CFM

7

12x12

NEW RG

275 CFM : 150 CFM

7

470 CFM : 390 CFM

NEW RG

RAMP UP

EXIST. 20x16 LP DUCT

RAMP UP

RAMP

6 NEW RG

John Norman Garra Florida Architect AR92545 NEW CD

5

Date

14x16

PHASE 1

Fourth Floor Mechanical Partial Plan (Phase 2)

M102 3 " = 1'-0" 16

N

5

MECHANICAL ROOM

2

FOURTH FLOOR MECHANICAL PLAN

NEW CD

Drawn by

2-28-2017 Ian Monday

470 CFM : 350 CFM

M 102

20x16 Scale COPYRIGHT 2015

Varies


N

PHASE 2

PHASE 3 & 3A REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

RAMP UP

2

MECHANICAL ROOM

M103 REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

RAMP UP

EXIST'G STAIR

1

NEW CD

5

6

Fourth Floor Mechanical Key Plan

M103 1 " = 1'-0" 32

RELOCATE

NEW RG

4

2

A OC

L RE

7

TE

1

1 North University Drive Plantation, FL 33324

EXIST'G STAIR

Fourth Floor Interior Renovation

PHASE 1

Government Center West

EXIST'G STAIR

3 525 CFM : 350 CFM

10x16

PHASE 2 Description 100 Percent Issue For Permit

No. 1 2

NEW RG

Date 7/7/2016 2/28/2017

REF

6 12x12

7 190 CFM : 90 CFM NEW CD

5

EXIST'G STAIR

RAMP UP

RAMP UP

John Norman Garra Florida Architect AR92545

FOURTH FLOOR MECHANICAL PLAN

N Date Drawn by

2

M103

Fourth Floor Mechanical Partial Plan (Phase 3 &3A)

M103 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2016

Varies


HVAC SPECIFICATIONS

MECHANICAL PLAN LEGEND # DESCRIPTION Remove existing ceiling diffuser and salvage for reuse in new location Remove existing return air grill and salvage for reuse in new 2 location 3 Install salvaged ceiling diffuser in new location. Install new flex from existing takeoff to relocated grill if existing flex is not long enough. Do not splice flex. Match existing size.

1

Existing partition wall to be removed

3.Contractor to coordinate Work that straddles multiple phases with Owner.

New door to be installed Existing door to be removed. Existing door to remain. Do not Disturb.

EXISTING LIGHT TO REMAIN. · ·

NEW LOCATION OF SALVAGED LIGHT TO BE INSTALLED

· ·

1 North University Drive Plantation, FL 33324

New partition wall to be Installed

Existing wall to remain. Do not disturb.

2. No PVC, wood or other combustible materials shall be allowed in return air plenum above ceiling.

·

Concrete Column. Do Not Disturb

Fourth Floor Interior Renovation

1.All new partition walls must maintain minimum 12" clearance from upper slab for return air path. Notify Engineer if any new walls in the field will extend to the deck, in order to size transfer openings.

No work

Government Center West

NOTES

4 Install salvaged lay in return grill in new location. Install new ceiling diffuser and connect with new flex duct to 5 existing rigid supply duct Install new lay-in return air grill open to existing air plenum 6 above ceiling. Re-balance airflow as shown, (existing CFM : propsosed 7 CFM). Add balancing damper at takeoff if not present. This room and zone had existing cooling deficiencies at the 8 time of the site visit, to be resolved by owner's maintenance division. Contractor shall perform duct traverse to determine total airflow at existing VAV-8-8 serving this area. Notify Engineer if not within 1925-2225 CFM (2025CFM target) in full cooing. Provide line item bid to recalibrating VAV Box. Also inspect duct serving this particular supply grille.

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SQ-1.net

Description 100 Percent Issue For Permit

No. 1 2

Date 7/7/2016 2/28/2017

½

John Norman Garra Florida Architect AR92545

½

FOURTH FLOOR MECHANICAL NOTES & DETAILS

½

Date Drawn by

½

7-7-2016 Ian Monday

M 201 Scale COPYRIGHT 2016

N.T.S.


No work

1 2

GFCI

Concrete Column. Do Not Disturb New partition wall to be Installed

Existing partition wall to be removed Existing wall to remain. Do not disturb.

8 9

T

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP

RAMP UP

MECHANICAL ROOM

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

7

Existing door to be removed

No electrical power or lighting work in this room. Remove existing receptacle on wall being demolished. Remove existing data jack on wall being demolished. Install new duplex wall receptacle. Install new wall mounted data jack. Install new electrical circuit, J box, and modular furniture base feed harness; make all electrical connections to modular furniture. Provide opening in raised floor system and carpet to accommodate sleeve and wire. Install new electrical card reader security door access lock. Removed existing electrical power whip. Repair hole in raised floor system and patch and repair carpet tile to match existing. Install new data wire and jack, provide opening in raised floor system and carpet to accommodate wire as needed. Connect data jack to modular furniture data system.

REF

New door to be installed

REF

RAMP UP

3 4 5 6

PHASE 2

PHASE 3 & 3A

RAMP UP

EXIST'G STAIR

EXIST'G STAIR

PHASE 1

1. General Contractor shall coordinate exact location of electrical devices with new furniture layout. 2. Electrical Power Base Feed Harness shall feed modular furniture electrical system. Install modular furniture electrical system as per manufacturers written instructions, do not exceed recommended number of circuits or recommended number of duplex receptacles per circuits. Modular furniture electrical system shall accommodate minimum (x2) duplex receptacles per personal cubical.

EXIST'G STAIR

2 E101

3.Contractor shall trace new and existing circuits.

1

Fourth Floor Electrical Key Plan

1

1

6

1

1

EXISTING CEILING MOUNTED RECEPTACLE SERVING PROJECTOR

FE

6 9

9

6

6

8

Date 7/7/2016 12/14/2016 2/28/2017

9

9

9

Description 100 Percent Revision Issue For Permit

No. 1 2 3

9

9

6

8

6

9

6

9

6

4

5

4

4

4

8

FLOOR HOLE ONLY. NO RECEPTACLE.

9 6

11 9

6 9

4

4

9

8

5

6

E101 1 " = 1'-0" 32

Fourth Floor Interior Renovation

CR

Government Center West

NOTES

10 Relocate existing thermostat. 11 Removed existing data whip. Repair hole in raised floor system and patch and repair carpet tile to match existing.

1 North University Drive Plantation, FL 33324

CR

Existing door to remain. Do not Disturb.

N

ELEC. POWER PLAN LEGEND # DESCRIPTION

6

EXIST'G STAIR

TELEPHONE

John Norman Garra Florida Architect AR92545

FOURTH FLOOR ELECTRICAL POWER PLAN

1

RAMP UP

1

1

CR

MECHANICAL ROOM

9

8

VENDINGVENDING MACHINEMACHINE

1

GFCI

GFCI

REF

1

1

1

9

1

6

1

T

T

10

PHASE 2

Date FE

Drawn by

N 2

E 101

Fourth Floor Electrical Power Partial Plan (Phase 1)

E103 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


ELEC. POWER PLAN LEGEND # DESCRIPTION

No work

1 2

GFCI

Concrete Column. Do Not Disturb New partition wall to be Installed

Existing partition wall to be removed Existing wall to remain. Do not disturb.

Existing door to remain. Do not Disturb.

8 9

T

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP

RAMP UP

2

MECHANICAL ROOM

E102

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

7

Existing door to be removed

No electrical power or lighting work in this room. Remove existing receptacle on wall being demolished. Remove existing data jack on wall being demolished. Install new duplex wall receptacle. Install new wall mounted data jack. Install new electrical circuit, J box, and modular furniture base feed harness; make all electrical connections to modular furniture. Provide opening in raised floor system and carpet to accommodate sleeve and wire. Install new electrical card reader security door access lock. Removed existing electrical power whip. Repair hole in raised floor system and patch and repair carpet tile to match existing. Install new data wire and jack, provide opening in raised floor system and carpet to accommodate wire as needed. Connect data jack to modular furniture data system.

REF

New door to be installed

REF

RAMP UP

3 4 5 6

PHASE 2

PHASE 3 & 3A

RAMP UP

EXIST'G STAIR

PHASE 1

EXIST'G STAIR

1. General Contractor shall coordinate exact location of electrical devices with new furniture layout. 2. Electrical Power Base Feed Harness shall feed modular furniture electrical system. Install modular furniture electrical system as per manufacturers written instructions, do not exceed recommended number of circuits or recommended number of duplex receptacles per circuits. Modular furniture electrical system shall accommodate minimum (x2) duplex receptacles per personal cubical.

EXIST'G STAIR

3.Contractor shall trace new and existing circuits.

Fourth Floor Electrical Key Plan 1

1

E102

8

3 2

6

8

8

8

11

3

2

8

32 " = 1'-0"

8

5

8

Fourth Floor Interior Renovation

CR

Government Center West

NOTES

10 Relocate existing thermostat. 11 Removed existing data whip. Repair hole in raised floor system and patch and repair carpet tile to match existing.

9 2

9

2

6

6

2

6

8

8

9

6 8

9

3

2

9

1 North University Drive Plantation, FL 33324

CR

N

8

8

8

8

1

9 9 2

PHASE7 3 & 3A

CR

3 2

CR

2

3 2

5 2

1

4

6

4

4

2

5 4

8

8

8

Date 7/7/2016 12/14/2016 2/28/2017

8

1 2

4

8

2

Description 100 Percent Revision Issue For Permit

No. 1 2 3

5

2

2

4

4

8

8

8

4

EXIST'G STAIR

7

2

3

2 9

8

2 4

REF

8

EXISTING FMD SUPERVISOR'S OFFICE

5

2

5 9

4

6

4

9

4 9

6

1

2

9

6

6

2

RAMP UP

7

CR

CR

7

4

CR

5

T

7 1

RAMP UP

4

RAMP

John Norman Garra Florida Architect AR92545

5 2

6

9

4

4 4

4 5

4

N

MECHANICAL ROOM

Date

1

2

FOURTH FLOOR ELECTRICAL POWER PLAN

9

6

9

Drawn by

PHASE 1

E 102

Fourth Floor Electrical Power Partial Plan (Phase 2)

E102 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


No work

1 2

GFCI

Concrete Column. Do Not Disturb New partition wall to be Installed

Existing partition wall to be removed Existing wall to remain. Do not disturb. New door to be installed

T

8 9

RAMP UP

RAMP UP

2

MECHANICAL ROOM

E103 5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

RAMP UP

EXIST'G STAIR

EXIST'G STAIR

PHASE 1

10 Relocate existing thermostat. 11 Removed existing data whip. Repair hole in raised floor system and patch and repair carpet tile to match existing.

2. Electrical Power Base Feed Harness shall feed modular furniture electrical system. Install modular furniture electrical system as per manufacturers written instructions, do not exceed recommended number of circuits or recommended number of duplex receptacles per circuits. Modular furniture electrical system shall accommodate minimum (x2) duplex receptacles per personal cubical.

EXIST'G STAIR

3.Contractor shall trace new and existing circuits.

1

E103

Fourth Floor Electrical Key Plan 1 32 " = 1'-0"

1 4

8

8 11

4

Fourth Floor Interior Renovation

1. General Contractor shall coordinate exact location of electrical devices with new furniture layout.

Government Center West

CR

NOTES

Existing door to remain. Do not Disturb.

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

REF

7

Existing door to be removed

REF

RAMP UP

3 4 5 6

PHASE 2

PHASE 3 & 3A

No electrical power or lighting work in this room. Remove existing receptacle on wall being demolished. Remove existing data jack on wall being demolished. Install new duplex wall receptacle. Install new wall mounted data jack. Install new electrical circuit, J box, and modular furniture base feed harness; make all electrical connections to modular furniture. Provide opening in raised floor system and carpet to accommodate sleeve and wire. Install new electrical card reader security door access lock. Removed existing electrical power whip. Repair hole in raised floor system and patch and repair carpet tile to match existing. Install new data wire and jack, provide opening in raised floor system and carpet to accommodate wire as needed. Connect data jack to modular furniture data system.

N

2

1 8

1 North University Drive Plantation, FL 33324

CR

ELEC. POWER PLAN LEGEND # DESCRIPTION

6 2

9 9

9

7

2

CR

PHASE 2

REF

1

Description 100 Percent Revision 1 Issue For Permit

No. 1 2 3

Date 7/7/2016 12/14/2016 2/28/2017

1

5 4 4

9

6

EXIST'G STAIR

RAMP UP

6 9 RAMP UP

8

John Norman Garra Florida Architect AR92545

N

FOURTH FLOOR ELECTRICAL POWER PLAN Date Drawn by

2

E 103

Fourth Floor Electrical Power Partial Plan (Phase 3 & 3A)

E103 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


N

PHASE 2

PHASE 3 & 3A

ELEC. LIGHTING PLAN LEGEND # DESCRIPTION

RAMP UP

No electrical power or lighting work in this room. 2 Install new electrical switch with integral dual-tech vacancy sensor; rewire existing lights to serve new dedicated room. 3 Relocate existing light fixture 4 Remove existing light switch on wall to be demolished. 5 Reconnect these lights to be controlled by existing main local switch serving adjacent fixtures in open workspace area.

Concrete Column. Do Not Disturb New partition wall to be Installed

Existing partition wall to be removed

RAMP UP

MECHANICAL ROOM

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

REF VENDINGVENDING MACHINEMACHINE

Existing wall to remain. Do not disturb.

RAMP UP

1

CR

Existing door to be removed Existing door to remain. Do not Disturb.

RAMP UP

Notes:

EXIST'G STAIR

EXIST'G STAIR

PHASE 1

2

EXIST'G STAIR

1

E201

Government Center West

NOTES

New door to be installed

Fourth Floor Electrical Key Plan

J

1

J

1 J

J

J

J

J

J

J

1

J

J

RELOCATE

2

J

J

J

J

3

1

E201 1 " = 1'-0" 32

1 North University Drive Plantation, FL 33324

No work

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

Fourth Floor Interior Renovation

CR

REF

J J

J J

J J

J

J

2

J

J

RELOCATE

J

J

J

J

J

3

FE

Description 100 Percent Issue For Permit

Date 7/7/2016 2/28/2017

J

J

No. 1 2

4HB-14 J J

1

1 CR

1

MECHANICAL ROOM

J

4HB-6

J

J

J

4HB-4

VENDINGVENDING MACHINEMACHINE

J

REF

EXIST'G STAIR

John Norman Garra Florida Architect AR92545

FOURTH FLOOR ELECTRICAL LIGHTING PLAN Date

J

J

1

J

RAMP UP

4HB-11

J

J

1 J

J

1

J

J

1

J J

J

RELOCATE

2

RELOCATE

J

4HB-7

J

J

4

1

3

2

PHASE 2

J

4

J

J

J

4HB-9

J

3

J

RELOCATE

Drawn by

FE

1

N 2

RAMP

E 201

Fourth Floor Electrical Lighting Partial Plan (Phase 1)

E201 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


ELEC. LIGHTING PLAN LEGEND # DESCRIPTION

CR

No work

No electrical power or lighting work in this room. 2 Install new electrical switch with integral dual-tech vacancy sensor; rewire existing lights to serve new dedicated room. 3 Relocate existing light fixture 4 Remove existing light switch on wall to be demolished. 5 Reconnect these lights to be controlled by existing main local switch serving adjacent fixtures in open workspace area.

Concrete Column. Do Not Disturb New partition wall to be Installed Existing wall to remain. Do not disturb.

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

Existing partition wall to be removed

PHASE 2

PHASE 3 & 3A

1

N

RAMP UP

2

MECHANICAL ROOM

E202

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

NOTES

New door to be installed

Existing door to remain. Do not Disturb.

VENDINGVENDING MACHINEMACHINE

Existing door to be removed

Notes:

REF

CR

RAMP UP

EXIST'G STAIR

1

E202

J

32 " = 1'-0"

1

5

4 J

Fourth Floor Electrical Key Plan 1

J

J

J

J

J

J

J

J

J

J

J

J

1 North University Drive Plantation, FL 33324

Government Center West

EXIST'G STAIR

Fourth Floor Interior Renovation

PHASE 1

EXIST'G STAIR

J

4HB-8

1 J

4

PHASE 3 & 3A

J

5

2

CR

J

J

J

CR

J

J

J

J

J

J

J

J

J

4HC-4 J

J

J

CA

R

REF

TE

O EL

3

1

3

2

4

J R

J

J

A OC EL

J

4

4HB-15 J

EXISTING FMD SUPERVISOR'S OFFICE

J

2

J

TE

J

3

CA

CA TE

1

J

J

5

J

J

J

J

J

2

J

1 J J

2

J

RAMP UP

J

4HB-11

4HB-15

J

J

J

1

RAMP UP

RAMP

J

LO

EXIST 4HB-12 PANEL HC4 EXIST PANEL LC4

RE LO

RE

3

Date 7/7/2016 2/28/2017

J

J

EXIST'G STAIR

1

5 TE

Description 100 Percent Issue For Permit

No. 1 2

2

J

2

J

J

John Norman Garra Florida Architect AR92545

J

4HB-9

J

2

Fourth Floor Electrical Lighting Partial Plan (Phase 2)

E202 3 " = 1'-0" 16

3

RELOCATE

3

1

RELOCATE

MECHANICAL ROOM

RELOCATE

N

FOURTH FLOOR ELECTRICAL LIGHTING PLAN Date

3

Drawn by

2-28-2017 Ian Monday

PHASE 1

E 202

J Scale COPYRIGHT 2015

Varies


ELEC. LIGHTING PLAN LEGEND # DESCRIPTION

CR

No work

N

PHASE 2

PHASE 3 & 3A REF

1

No electrical power or lighting work in this room. 2 Install new electrical switch with integral dual-tech vacancy sensor; rewire existing lights to serve new dedicated room. 3 Relocate existing light fixture 4 Remove existing light switch on wall to be demolished. 5 Reconnect these lights to be controlled by existing main local switch serving adjacent fixtures in open workspace area.

Existing wall to remain. Do not disturb.

RAMP UP

2

MECHANICAL ROOM

E203

CR

Existing door to be removed Existing door to remain. Do not Disturb.

VENDINGVENDING MACHINEMACHINE

NOTES

REF

New door to be installed

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

Notes: RAMP UP

EXIST'G STAIR

PHASE 1

Government Center West

EXIST'G STAIR

EXIST'G STAIR

1

E203

Fourth Floor Electrical Key Plan 1 32 " = 1'-0"

J

2

1 J

J

J

LO

3

CA

J

4

RE

J

TE

J

J

J

J

J

J

J

1 North University Drive Plantation, FL 33324

Existing partition wall to be removed

RAMP UP

New partition wall to be Installed

RAMP UP

Fourth Floor Interior Renovation

Concrete Column. Do Not Disturb

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

J

1 J

J

J

4

J CR

J

4HB-1

PHASE 2 J

J

J

J

Description 100 Percent Issue For Permit

No. E1 AT 2 C O

L

RE

REF

Date 7/7/2016 2/28/2017

1 J J

J

1

J

J

J J

RELOCATE

EXIST'G STAIR

3

J

EXIST 4HB-12 PANEL HC4 EXIST PANEL LC4

J

2

RAMP UP

J

J

4HB-3

RAMP UP

4HB-15

John Norman Garra Florida Architect AR92545

J

N

FOURTH FLOOR ELECTRICAL LIGHTING PLAN Date Drawn by

2

E 203

Fourth Floor Electrical Lighting Partial Plan (Phase 3 & 3A)

E203 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


1 North University Drive Plantation, FL 33324

Fourth Floor Interior Renovation

Government Center West

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SQ-1.net

Description 100 Percent Issue For Permit

No. 1 2

Date 7/7/2016 2/28/2017

John Norman Garra Florida Architect AR92545

FOURTH FLOOR ELECTRICAL NOTES & DETAILS Date Drawn by

2-28-2017 Ian Monday

E 301 Scale COPYRIGHT 2016

N.T.S.


# 1 2

N

FIRE SPRINKLER PLAN LEGEND DESCRIPTION

PHASE 2

PHASE 3 & 3A REF

Install new sprinkler head. Remove existing sprinkler head.

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

RAMP UP

MECHANICAL ROOM

REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

RAMP UP

No work

EXIST'G STAIR

Concrete Column. Do Not Disturb

EXIST'G STAIR

PHASE 1

New partition wall to be Installed

Existing wall to remain. Do not disturb. New door to be installed

2

Existing door to remain. Do not Disturb. EXIST'G STAIR

1

FS101

Government Center West

≥

Fourth Floor Fire Sprinkler Key Plan

1

1

2

FS101 1 " = 1'-0" 32

Fourth Floor Interior Renovation

Existing door to be removed.

1 North University Drive Plantation, FL 33324

Existing partition wall to be removed

1

2

1

FE

Description 100 Percent Issue For Permit

Date 7/7/2016 2/28/2017

1

2

1

No. 1 2

PHASE 2

VENDINGVENDING MACHINEMACHINE

John Norman Garra Florida Architect AR92545

EXIST'G STAIR

MECHANICAL ROOM

REF

RAMP UP

FOURTH FLOOR FIRE SPRINKLER PLAN

Date FE

Drawn by

N 2

FS101

Fourth Floor Fire Sprinkler Partial Plan (Phase 1)

FS101 3 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2015

Varies


# 1 2

FIRE SPRINKLER PLAN LEGEND DESCRIPTION

PHASE 2

PHASE 3 & 3A

Install new sprinkler head. Remove existing sprinkler head.

N

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP

RAMP UP

RAMP UP

2

MECHANICAL ROOM

FS102 REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

No work RAMP UP

EXIST'G STAIR

Concrete Column. Do Not Disturb

PHASE 1

EXIST'G STAIR

New partition wall to be Installed Existing partition wall to be removed

New door to be installed

Existing door to remain. Do not Disturb.

≥

1

Government Center West

EXIST'G STAIR

Fourth Floor Fire Sprinkler Key Plan

FS102 1 " = 1'-0" 32

Fourth Floor Interior Renovation

Existing door to be removed.

1 North University Drive Plantation, FL 33324

Existing wall to remain. Do not disturb.

1 1

PHASE 3 & 3A

1

1

Description 100 Percent Issue For Permit

No. 1 2

Date 7/7/2016 2/28/2017

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP RAMP UP

RAMP

John Norman Garra Florida Architect AR92545

1

1

1

FOURTH FLOOR FIRE SPRINKLER PLAN

2

MECHANICAL ROOM

2

N

2

Date Drawn by

2-28-2017 Ian Monday

PHASE 1 2

FS102

Fourth Floor Fire Sprinkler Partial Plan (Phase 2)

FS102 3 " = 1'-0" 16

Scale COPYRIGHT 2015

Varies


#

FIRE SPRINKLER PLAN LEGEND DESCRIPTION

PHASE 2

PHASE 3 & 3A

1 Install new sprinkler head. 2 Remove existing sprinkler head.

N

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

RAMP UP

RAMP UP

RAMP UP

2

MECHANICAL ROOM

FS103 REF

5450 Griffin Rd. -Suite ADavie, FL 33314 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

VENDINGVENDING MACHINEMACHINE

No work

RAMP UP

EXIST'G STAIR

Concrete Column. Do Not Disturb EXIST'G STAIR

New partition wall to be Installed

PHASE 1

Existing partition wall to be removed

New door to be installed

Existing door to remain. Do not Disturb.

≥

Government Center West

EXIST'G STAIR

Fourth Floor Fire Sprinkler Key Plan

1

FS103 1 " = 1'-0" 32

FE

1

1

Fourth Floor Interior Renovation

Existing door to be removed.

1 North University Drive Plantation, FL 33324

Existing wall to remain. Do not disturb.

PHASE 2 Description 100 Percent Issue For Permit

No. 1 2

REF

Date 7/7/2016 2/28/2017

1

EXIST'G STAIR

RAMP UP

RAMP UP John Norman Garra Florida Architect AR92545

N

FOURTH FLOOR FIRE SPRINKLER PLAN

Date Drawn by

2

FS103

Fourth Floor Fire Sprinkler Partial Plan (Phase 3 &3A)

FS103 3 " = 1'-0" 16

2-28-2016 Ian Monday

Scale COPYRIGHT 2015

Varies


LIFE SAFETY GENERAL NOTES

LIFE SAFETY LEGEND

1. There is no change to the number or location of separate means of egress.

No work

2. There is no change in the occupant load.

Concrete Column. Do Not Disturb New partition wall to be Installed Existing wall to remain. Do not disturb. New door to be installed Existing door to remain. Do not Disturb.

New location of office furniture

3321 NW 97 Avenue Sunrise, FL 33351 AA26001846 ::::: 954-861-0852 ::::: www.SquareOneArchitecture.com

REF

EXISTING FMD SUPERVISOR'S OFFICE

EXIST'G STAIR

TRAVEL DISTANCE FROM MOST REMOTE POINT:199' RAMP UP

RAMP UP

RAMP UP

MECHANICAL ROOM

Fourth Floor Interior Renovation

Government Center West

MOST REMOTE POINT

TRASH / RECYCLE

1 North University Drive Plantation, FL 33324

Existing fire rated egress stair. Do not disturb rated enclosure.

REF VENDINGVENDING MACHINEMACHINE

FE

RAMP UP

EXIST'G STAIR

No. 1 2 3

EXIST'G STAIR

Description 100 Percent Furniture Revision Issue For Permit

Date 7/7/2016 8/18/2016 2/28/2017

FE

TRAVEL DISTANCE FROM MOST REMOTE POINT:188' EXIST'G STAIR

John Norman Garra Florida Architect AR92545

FOURTH FLOOR LIFE SAFETY PLAN

N Date

Drawn by

1

LS101

Fourth Floor Fire Life Safety Plan (All Phases)

LS103 1 " = 1'-0" 16

2-28-2017 Ian Monday

Scale COPYRIGHT 2016

1 16"

= 1'


Turn static files into dynamic content formats.

Create a flipbook