International Journal of Engineering Inventions ISSN: 2278-7461, www.ijeijournal.com Volume 1, Issue 8 (October2012) PP: 14-19
A ROBUST PERFORMANCE OF A VOLTAGE SOURCE CONVERTER BASED HIGH VOLTAGE DIRECT CURRENT Nadir Ghanemi 1, Djamel Labed2, 1 ,2
Electrical Laboratory of Constantine, Constantine University, Algeria
Abstract:––In this paper, we presented the modelling of VSC (Voltage Source Converter) of a DC link in the field of Park. A control strategy based on the separation of active and reactive power is proposed. Simulation in Matlab / Simulink system proposed under normal operation and faulty operation allows us to evaluate the performance of a VSC HVDC. Keywords:––VSC, HVDC, decoupled control
I.
INTRODUCTION
The power transmission DC has being historically the first used solution, but the technology of that time did not allow the development of this type of power transmission. The first power transmission system using HVDC (High Voltage Direct Current) was released in 1954 [1], since then research on power transmission DC has started. Nowadays, and following the progress of the field of power electronics, converters based on VSC technology are realized with IGBT (Insulated Gate Bipolar Transistor). These showed many advantages [1], [2] as compared to converters used for the traditional HVDC and are realised with thyristors. In this study, we present a model of the VSC HVDC that will allow us to establish a mathematical model, or a so called control strategy. This model for separating control is used to power the controlled converter VSC. A simulation with Matlab / simulink is performed to highlight the performance of a VSC HVDC.
II.
MODELING OF THE VSC HVDC
The configuration of a single polar VSC [1] is given by "Fig. 1". Rated AC voltages can be expressed by the following formula:
Vcabc V xabc L
diabc rI abc dt
(1)
Our goal is to establish a mathematical model that will be used for the control law. For this, we choose the study in the area of Park, or we will establish a control system called VSC control by powers decoupled.
Fig. 1 VSC HVDC single polar To facilitate the calculation, we used the transformation of Clark. This transformation the following result:
abc dq
The transition from normal reference to real reference Clark is given by "(2)":
1 2 0 0 3 1 2
1 2 3 2 1 2
1 2 a 3 . b 2 1 c 2
(2)
Transformation using the Clark "(1)":
ISSN: 2278-7461
www.ijeijournal.com
P a g e | 14