The

EWAD~C family

Non-inverter

All year round… Inverter A p p l i e d S y s t e m s C ATA LO G U E 2 0 12

… top efficiency, low sound levels and flexible solutions for a wide range of applications

Applied Systems

Catalogue ■

ALL SEASONS PERFECT C MFORT

Free cooling

The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

DAIKIN AIRCONDITIONING CENTRAL EUROPE HandelsgmbH campus 21, Europaring F12/402, A – 2345 Brunn/Gebirge Tel.: +43 / 22 36 / 3 25 57-0, Fax: +43 / 22 36 / 3 25 57-900 e-mail: office@daikin.at, www.daikin-ce.com

Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.euroventcertification.com or using: www.certiflash.com

Daikin products are distributed by:

ECPEN12_02_dace_AS • Copyright Daikin We reserve the right for printing errors and model changes.

Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

2012



TABLE OF CONTENTS Table of contents

1

New products 2012

2

Seosonal efficiency

3

Environmental awareness

116

Daikin solutions to R-22 phase out 118

APPLIED SYSTEMS

NEW

NEW NEW

NEW

NEW

NEW NEW

NEW

CHILLERS Air cooled chillers (Cooling only) EWAQ-ACV3 EWAQ-ACW1 EUWAC-FBZW1 EUWA(N-P-B)-KBZW1 EWAQ-BAWN/BAWP EWAQ-DAYN EWAD-E- EWAD-D- EWAD-BZ EWAD-C- EWAD-CZ EWAD-CF

4 9 10 11 12 13 14 15 16 18 26 28 34 36

Air cooled chillers (Heat pump) EWYQ-ACV3 EWYQ-ACW1 EUWY(N-P-B)-KBZW1 EWYQ-BAWN/BAWP EWYQ-DAYN EWYD-BZ

38 38 39 40 41 42 43

Air cooled condensing units ERQ VRV-AHU ERAD-E-

45 46 48 50

Water cooled chillers EWWP-KBW1N EWWD-J- EWWD-G- EWWD-I- EWWD-H- EWWQ-B-

53 54 56 58 60 62 64

Water cooled centrifugal chillers EWWD-FZXS DWSC, DWDC

66 66 68

Condenserless chillers EWLP-KBW1N EWLD-J- EWLD-G- EWLD-I-

71 72 73 74 75 1

Accessories DICN (Daikin Integrated Chiller Network) EHMC, EKBT (Hydraulic Module, Buffer tank) Dry Coolers & Condensers Cooling Towers

76 76 77 78 78

Ventilation Fan coil units FWC-BT/BF FWF-BT/BF FWC-AT/AF FWF-CT FWB-JT/JF FWB-BT FWT-BT/BF FWL-DT/DF FWM-DT/DF FWD-AT/AF FWV-DT/DF

79 80 81 82 83 84 85 86 87 88 89 90 91

Air Coolers

92

Heat Reclaim Ventilation VAM-FA

93 93

Rooftops UATYQ-CY1 UATYP-AY1

94 94 95

Air handling units

96

Plug And Play VRV-Connection AHU

100

Options & Accessories

107


New products 2012 14/41 Small inverter chiller - EWA/YQ-BA* >> Air cooled chiller with inverter compressor and fan >> High efficiency with leader-of-class ESEER up to 4.75 >> Available both in cooling only and heat pump models >> Wide capacity range from 17 kW up to 75 kW (7 sizes) >> Supplied optionally with factory mounted (standard/high-ESP) pump >> R-410A scroll compressor (1 or 2 circuits)

34 Large air cooled inverter chiller - EWAD-CZ >> Highest partial load efficiency scores in its class (ESEER up to 5.8) >> Large operating range (ambient temperatures from -18°C up to +50°C) >> Multiple sound levels to meet accoustic requirements >> Highest cooling capacity in its class (up to 1,800 kW) >> Extensive option list including fan speed regulation, rapid restart and heat recovery option

36 Free cooling chiller - EWAD-CF >> Air cooled chiller with free cooling system >> High efficiency version, combinable with 3 sound levels >> 11 sizes from 600 kW up to 1,565 kW >> Greater energy savings and reduced CO2 emissions during cold season

62 New flooded Chiller range - EWWD-H>> 11 sizes between 370 and 1,215 kW >> Condenser leaving water up to 50°C as standard >> High temperature kit for condenser leaving water up to 65°C >> Extended with heat pump option

96 D-AHU Professional and D-AHU Easy >> Air flow rates from 500 m³/h up to 124,000 m³/h >> From standard sizes to customized solutions >> Premium Eurovent performances >> Infinitely variable sizes

2


SEASONAL EFFICIENCY With European legislation* pressing energy users to drastically cut energy consumption, improve energy efficiency of buildings and homes, and meet the Commission’s 20/20/20 targets, industry is looking at more appropriate ways to evaluate efficiency. Thus, the new Directive aims at reducing the environmental impact of products in the EU. NOMINAL EFFICIENCY UP FOR IMPROVEMENT Measuring environmental performance is not new to Europe. Such measurements are used to set minimum requirements for manufacturers and to provide consumers with information on air conditioner performance so they can make intelligent choices when purchasing. The measurement method currently in place is that of nominal efficiency, a method, however, with limitations that result in a significant gap between rated and actual performance.

Temperature distribution curve Occurrence

SEASONAL EFFICIENCY IN LINE WITH PART LOAD PERFORMANCE To correct this situation, a more complex measurement for seasonal efficiency is being developed. The major differences between seasonal and nominal calculation are:

35° Temperature

7° Current point for COP Current point for EER Heating Cooling

>> The use of several rating temperatures for cooling and heating instead of one nominal temperature, better reflecting actual performance over an entire season

Annual energy consumption

>> Integration of operation at partial capacity instead of full capacity better estimation of the real-life performance of a unit since the majority

NOMINAL

of systems operate at partial load most of the time

TOTAL

>> Adoption of the seasonal efficiency calculation method will result in a

ESEER - European Seasonal Energy Efficiency Ratio To get a reliable energy analysis of the product annual performances it has been introduced a European Seasonal Energy Efficiency Ratio fully recognized in Europe (ESEER). The European Seasonal Energy Efficiency Ratio is a weighed formula enabling to take into account the variation of EER with the load rate and the variation of air or water inlet condenser temperature. The calculation formula and graph for ESEER is listed below: ESEER = 3% EER100% Load + 33% EER75%Load + 41% EER50%Load + 23% EER25%Load Therefore the ESEER is realistic tool, much better than full load EER, to be used to compare average efficiency of two chillers.

*EPB (Energy Performance of Buildings) Directive 2002/91/EC

3

ESEER parameter Part. load rate 100 75 50 25

Air temperature (°C) 35 30 25 20

Water temperature (°C) Weighting coeffizients 30 3% 26 33% 22 41% 18 23%


Extra low

Reduced

Low

Standard

Sound version High ambient

Premium

High

Standard

Efficiency version Centrifugal

Scroll

Screw

Compressor Swing

Free cooling

Inverter

Refrigerant

Page

General chiller Portfolio Air cooled overview units

INVERTER

Air cooled chillers (Cooling only) EWAQ005-007ACV3

10

R-410A

EWAQ009-011ACV3

10

R-410A

EWAQ-ACW1

11

R-410A

EUWAC-FBZW1

12

EUWA*-KBZW1

R-407C

13

R-407C

EWAQ-BAWN/BAWP

14

R-410A

EWAQ-DAYN

15

R-410A

EWAD-E-

16

R-134a

 

EWAD-D-

18

R-134a

 

    

EWAD-BZ

26

R-134a

 

  

EWAD-C-

28

R-134a

  

  

EWAD-CZ

34

R-134a

  

EWAD-CF

36

R-134a

  

  

Air cooled chillers (Heat pump) EWYQ005-007ACV3

38

R-410A

EWYQ009-011ACV3

38

R-410A

EWYQ-ACW1

39

R-410A

EUWY*-KBZW1

40

R-407C

EWYQ-BAWN/BAWP

41

R-410A

EWYQ-DAYN

42

R-410A

EWYD-BZ

43

R-134a

50

R-134a

 

 

 

Air cooled condensing units ERAD-E-

4


Capacity classes (kW) 0

17.5

200

500

1,000

2,000

5.2~7.1

8.5~11.0

9.0~13.2

11.6~23.8

11.3~55.3

16.8~63.0

80~254

97.9~413

177~622

329~515

619~2,008

635~1,802

602~1,555

0

17.5

200

500

1,000

2,000

500

1,000

2,000

5.2~7.1 5.65~7.75 8.5~11.0 10.0~13.0 9~13.2 11~14 9.1~50.0 11.9~54.0 16.8~63 16.8~63 77~252 88.7~281 248~583 270~615 0

17.5

200

116~488

5


INVERTER

Water cooled chillers (Cooling only & Heating only)

R-134a

 

60

R-134a

 

62

R-134a

 

EWWP-KBW1N

54

R-407C

EWWD-J-

56

R-134a

EWWD-G-

58

EWWD-I-

EWWD-H-

Water cooled chillers (Cooling only) EWWQ-B-

64

R-410A

Water cooled centrifugal chillers EWWD-FZXS

66

R-134a

DWSC DWDC

68

R-134a

 

EWLP-KBW1N

72

R-407C

EWLD-J-

73

R-134a

EWLD-G-

74

R-134a

EWLD-I-

75

R-134a

Condenserless chillers

6

Extra low

Reduced

Low

Standard

Sound version High ambient

Premium

High

Standard

Efficiency version Centrifugal

Scroll

Screw

Compressor Swing

Free cooling

Inverter

Refrigerant

Page

Portfolio Water cooled and Condenserless units


Capacity classes (kW) 0

17.5

200

500

1,000

2,000 9,000

1,000

2,000 9,000

1,000

2,000 9,000

13.0~195 16.6~248 120~570 142~681 166~604 204~712 333~1,510 388.4~1,790 369~1,215 419~1,356 0

17.5

200

500

380~2,152

0

17.5

200

500

114~1,048

300~4,500 600~9,000 0

17.5

200

500

1,000

12.1~62.4

110~530

161~526

328~1,422

7

2,000 9,000


A ir cooled chiller 1

7

3

2

5

4

5

Expansion vessel

t

Chillers

Evaporator

Buffer Tank

To fan coil units

t

t 1 1. 2. 3. 4.

6

5 5. 6. 7. 8.

Temperature sensor Filter Shut-off valve Pump

8

9

11 9. 10. 11. 12.

Pressure port Flow switch Air purge Pressure gauge

10

Balancing valve Drain valve Charging valve Safety valve

H eat recovery chiller 1 Chillers

7

3

2

5

4

5

Expansion vessel

t Buffer Tank Evaporator

12

Heat recovery exchanger

10

13

t 1

1. 2. 3. 4.

t

5

Temperature sensor Filter Shut-off valve Pump

9 8

6

Water Tank

5. 6. 7. 8.

Pressure port Flow switch Air purge Pressure gauge

11 To sanitary use

9. 10. 11. 12.

8

Balancing valve Drain valve Charging valve Safety valve

13. Mixing valve

To fan coil units


Air cooled chillers are most frequently used in the chilled water market. Out of its wide range of chillers in cooling only or heat pump version, with or without integrated hydronic components, DAIKIN always offers you a chiller fitting your application needs.

Daikin has taken great care to match major chiller components and refrigerant combinations to a point where high efficiency ranges of technically advanced and closely optimised air and water cooled units are now widely available for use with R-410A, R-407C and R-134a refrigerants. swing

scroll

screw

Air cooled chillers (Cooling only)

NEW

NEW NEW

EWAQ-ACV3 EWAQ-ACW1 EUWAC-FBZW1 EUWA(N-P-B)-KBZW1 EWAQ-BAWN/BAWP EWAQ-DAYN EWAD-E- EWAD-D- EWAD-BZ EWAD-C- EWAD-CZ EWAD-CF

10 11 12 13 14 15 16 18 26 28 34 36

Air cooled chillers (Heat pump)

NEW

EWYQ-ACV3 EWYQ-ACW1 EUWY(N-P-B)-KBZW1 EWYQ-BAWN/BAWP EWYQ-DAYN EWYD-BZ

38 39 40 41 42 43

9


EWAQ-ACV3

Air cooled mini chiller inverter EWAQ005-011ACV3

Digital controller

›› ›› ›› ›› ›› ›› ›› ››

Inverter technology ensures: continuous match of requested load, excellent part load efficiency (ESEER up to 4.57), significant reduction of starting currents, precise temperature control (evaporator leaving water) Low operating sound level Easy ‘plug and play’ installation Daikin swing (sizes 005-006-007) or scroll compressor (sizes 009-010-011) Integrated hydronics Available options: evaporator heater type (OP10) and high ESP pump up to 90 kPa (OPHP) Single phase power supply and main switch included Wide operating range

Cooling only Capacity class Cooling capacity Power input EER ESEER Dimensions Weight Water heat exchanger

Nom. Cooling

Unit Unit Type Water volume Nominal water flow Air heat exchanger Type Nominal ESP unit Pump Hydraulic components Expansion vessel Fan Air flow rate Fan motor Speed

Nom.

HeightxWidthxDepth

kW kW

005 5.2 1.89 2.75 3.75

006 6.0 2.35 2.55 3.83 805x1,190x360 100

mm kg

007 7.1 2.95 2.41 3.87

009 8.5 2.74 3.11 4.57

010 9.5 3.19 2.98 4.52 1,435x1,418x382 180

011 11.0 3.82 2.88 4.46

Brazed plate Cooling

Cooling Volume Cooling Nom. Cooling Nom. Steps Sound power level Cooling Nom. Sound pressure Cooling Nom. level Night quiet mode Cooling Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Water inlet / outlet Piping connections Water drain Power supply Phase / Frequency / Voltage

l l/min

kPa l m³/min rpm dBA dBA dBA °CDB °CDB

14.9

17.2 Tube type 45.1 6 -

49.4

62 48

1.01 20.4

24.4

27.2

38.3

63 50

Hermetically sealed swing compressor 5~20 10~43 R-410A

kg

1.7

2.95 Electronic expansion valve 1

inch inch Hz / V

G 5/4" (female) -

1" MBSP Hose nipple 1/2" FBSP 1~ / 50 / 230

10

31.5

Hi-XSS 58.0 54.6 49.1 10 96 100 97 780 8 64 51 45 Hermetically sealed scroll compressor 5~22 10~46


EWAQ-ACW1

Air cooled mini chiller inverter EWAQ009-013ACW1

Digital controller

›› ›› ›› ›› ›› ›› ›› ››

Inverter technology ensures: continuous match of requested load, excellent part load efficiency (ESEER up to 4.68), significant reduction of starting currents, precise temperature control (evaporator leaving water) Low operating sound level Easy ‘plug and play’ installation Daikin scroll compressor Integrated hydronics Available options: evaporator heater type (OP10) and high ESP pump up to 90 kPa (OPHP) Three phase power supply and main switch included Wide operating range

Cooling only Capacity class Cooling capacity Power input EER ESEER Dimensions Weight Water heat exchanger

Nom. Cooling

Unit Unit Type Water volume Nominal water flow Air heat exchanger Type Nominal ESP unit Pump Hydraulic components Expansion vessel Fan motor Speed

Nom.

HeightxWidthxDepth

Cooling

Cooling Volume Cooling Nom. Steps Sound power level Cooling Nom. Sound pressure Cooling Nom. level Night quiet mode Cooling Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Water inlet / outlet Power supply Phase / Frequency / Voltage

kW kW

009 9.0 2.96 3.04 4.68

011 11.0 3.82 2.88 4.63 1,435x1,418x382 180 Brazed plate 1.01 31.5 Hi-XSS 49.1 10 780 8

mm kg l l/min kPa l rpm

25.8 56.4

dBA dBA dBA

64 51 45

kg

inch Hz / V

11

37.8 40.9

66 52 46 Hermetically sealed scroll compressor 5~22 10~46 R-410A 2.95 Electronic expansion valve 1 G 5/4" (female) 3N~ / 50 / 400

°CDB °CDB

013 13.2 5.10 2.59 4.52


EUWAC-FBZW1

Air cooled chiller with centrifugal fan EUWAC8FBZW1

μC² SE

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

For indoor installation Optimised for use with R-407C Daikin scroll compressor Standard phase sequence controller Maximum external static pressure (ESP): 150Pa Pressure gauges Standard operation range down to -10°C Regulating switch Water inlet or outlet temperature control Input contacts/available outputs Input: on/off, pump/flow switch Outputs: compressor operation, summary alarm, pump relay contact Compatible with hydraulic module µC² SE DDC controller

Cooling only Capacity class Cooling capacity Capacity steps Power input EER Dimensions Weight

Nom. Cooling

Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Minimum water volume in the system Water flow rate Nom. Nominal water Cooling Heat exchanger pressure drop Model Type Quantity Air heat exchanger Type Fan Air flow rate Nom. Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Evaporator water drain Power supply Phase / Frequency / Voltage

kW % kW mm kg kg l l/min kPa

m³/min dBA

5 11.6

8 18.4 100-0 7.66 2.40 1,290x1,180x630 224 228 Brazed plate 153 53

5.2 2.23 1,345x856x630 164 166 101 33

9.67 2.46 1,395x1,330x630 261 266 212 68

26

42

48

AC70-24

AC70-34 1 Cross fin coil/Hi-X tubes and PE coated waffle louvre fins 109.8 66 Hermetically sealed scroll compressor -10 (OPZL) ~ 21 -10 ~ 43 R-407C Thermostatic expansion valve 1 3.9 FBSP 1 Field installation 3N~ / 50 / 400

AC70-40

70.2 63

°CDB °CDB

kg inch

10 23.8

2.1

Hz / V

12

126 69

4.7


EUWA(N-P-B)-KBZW1

Air cooled chiller EUWA*16KBZW1

μC² SE

›› ›› ›› ›› ›› ›› ›› ›› ››

››

Optimised for use with R-407C Daikin scroll compressor Reduced installation time thanks to integrated pump and;or buffer tank Possibility for a 200l buffer tank Low operating sound level Easy maintenance Main switch Water flow switch 3 different design options available: - EUWAN chiller without integrated hydraulic module ; - EUWAP chiller with integrated hydraulic module (pump, expansion vessel, hydraulic components) ; - EUWAB chiller with integrated hydraulic module (buffer tank, pump, expansion vessel, hydraulic components) µC² SE DDC controller

Cooling only Capacity class Cooling capacity Capacity steps Power input EER Dimensions Weight Water heat exchanger

Air heat exchanger Hydraulic components Fan group Fan group 2 Sound power level Compressor Operation range Refrigerant

Refrigerant circuit Refrigerant circuit 2 Piping connections Power supply

N5

Nom. Cooling

Nom.

HeightxWidthxDepth Unit Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Type Expansion vessel Volume Air flow rate Cooling Nom. Air flow rate Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Control Circuits Quantity Charge Charge Water inlet / outlet Phase / Frequency / Voltage

kW % kW mm kg kg l l/min kPa

l m³/min m³/min dBA

P5 11.3

N10 P10 B10 N12 P12 B12 N16 P16 B16 N20 P20 B20 N24 P24 B24 22.5 26.5 34.6 46.6 55.3 0-100 0-50-100 4.48 7.27 8.64 11.50 14.70 17.90 23.80 2.53 2.46 2.60 2.30 2.35 2.60 2.32 1,230x1,290x734 1,450x1,290x734 1,321x2,580x734 1,541x2,580x734 150 168 180 215 229 241 245 259 271 248 262 274 430 448 460 490 508 520 496 514 526 152 171 239 218 232 300 248 262 330 251 265 335 436 457 525 496 518 545 503 524 592 Brazed plate 1.14 1.615 1.9 2.375 2.964 3.9 4.524 32 51 64 76 99 134 158

N8

24 12 160 (per 2 fans) 67

°CDB °CDB

kg kg inch Hz / V

B5

3.9

P8 19.7

B8

38 -

43

37

22

Cross fin coil/Hi-X tubes and PE coated waffle louvre fins 12 12 12 12 12 170 (per 2 fans) 170 (per 2 fans) 76 78 79 81 Hermetically sealed scroll compressor -10 (OPZL) ~ 25 -15 ~ 43 R-407C Thermostatic expansion valve 1 2 4.6 5.9 6.0 4.6 5.9 4.6 5.9 G 1"1/4 (male) 2" (male) 3N~ / 50 / 400

13

12

6.0 6.0


EWAQ-BAWN/BAWP

Air cooled inverter chiller EWAQ-BA*

BRC21A52

›› ›› ›› ›› ›› ›› ››

High efficiency chiller with leader-of-class ESEER (up to 4.75) Minimal starting currents and short payback times No buffertank required for standard applications Naked or with factory mounted (standard/high-ESP) pump Low sound thanks to inverter compressor / fans EWAQ-BAWN: Naked EWAQ-BAWP: With pump

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Heating Nominal water pressure drop Cooling Total Air heat exchanger Type Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Water inlet / outlet Power supply Phase/Frequency/Voltage

kW % kW

016 16.8

5.57 3.01 4.75

mm kg kg

264 267

l l/min l/min kPa

48 48 20

m³/min dBA

021 21.0

025 25.2

7.25 2.90 4.65 1,684x1,371x774 317 320 1 60 60 30

171

185 78

°CDB °CDB kg

7.6

inch Hz/V

1-1/4

14

032 040 050 31.5 42.0 50.4 Inverter controlled 25 9.25 12.9 14.9 19.0 2.72 2.44 2.82 2.65 4.45 4.00 4.60 4.40 1,684x1,684x774 1,684x2,358x780 397 571 401 577 Brazed plate 2 3 72 90 120 144 72 90 120 144 42 30 42 Hi-XSS 233 370 80 81 Hermetically sealed scroll compressor -10~20 -15~43 R-410A 9.6 15.2 Electronic expansion valve 1 1-1/2 3N~/50/400

064 63.0

26.7 2.36 3.95 1,684x2,980x780 730 738 5 181 181 30 466.0 83

19.2


EWAQ-DAYN

Air cooled chiller, multiple scroll EWAQ130-150DAYN

PCASO

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Optimised for use with R-410A refrigerant Multiple compressors per circuit Reliable and efficient scroll with high EER values High part load efficiency (ESEER) Anti-corrosion treated aluminium coils Low operating sound level Easy 'plug and play' installation Fans protected against abnormal operation (4 - 8 fans depending on unit size) Safety valves in each circuit Electronic circuit breakers Electronic expansion valve True dual plate brazed plate heat exchanger All hydronics can be accessed easily from 3 sides (no surrounding cabinet) Separate switchbox for easy access Compressors and controls at unit side Increased reliability via 2 independent refrigerant circuits (EWAQ130-260DAYN) Double circuit heat exchanger (from >100 kW) Non hermetic filter/dryer Daikin Pcaso controller with user friendly and powerful LCD interface

Cooling only Capacity class Cooling capacity Capacity steps

Power input EER ESEER Dimensions Weight

Nom.

Cooling

kW %

Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Nominal water flow Cooling Nominal water Cooling Total pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping Water inlet / outlet connections Water drain Power supply Phase / Frequency / Voltage

kW

mm kg kg l/min kPa

m³/min rpm dBA

080 80

100 105

180 210 182 209 21/290-25-50-75-100 43/50/570-25-50-75-100 71/79-100 46.6 56.3 64.5 74.6 2.81 2.70 2.82 2.80 4.34 4.22 4.36 4.32 2,311x2,000x2,631 2,311x2,000x3,081 1,500 1,550 1,800 1,850 1,517 1,569 1,825 1,877 Brazed plate 377 436 522 599

0-50-100 26.4 36.2 3.03 2.90 4.12 4.00 2,311x2,000x2,566 1,350 1,400 1,365 1,415 229

301

59

58

150 152

52

49

52

53

Cross fin coil/Hi-Xss tubes and poly ethylene coated waffle fins 800 860 1,290 900 970 88 89 90 Scroll compressor -10 (OPZL) ~ 25 -15 ~ 43 R-410A 19 25 29 28 Electronic expansion valve 2 3" OD 1/2"G 3~ / 50 / 400

780 880 86

°CDB °CDB kg

130 131

33 1

inch inch Hz / V

15

240 260 236 254 22/2840/50/560-25-50-75-100 72/78-100 82.8 94.0 2.85 2.70 4.20 4.00 2,311x2,000x4,850 3,150 3,250 3,189 3,292 677

728

51

47 1,600 900 91

39

3"


EWAD-E-SS

Air cooled chiller, standard efficiency EWAD130,140,160E-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ››

Wide capacity range: 10 sizes to cover a range from 101 to 413 kW (SS), 97.9 to 398kW (SL) One refrigerant circuit with steppless single screw compressor Compact design with brazed plate heat exchanger Large operation range (ambient temperature down to -18°C) Low operating sound level (SL) Water supply down to -15°C Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communication

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight Water heat exchanger

Air heat exchanger Fan Sound power level Sound pressure level Compressor Operation range Refrigerant

Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

kW

HeightxWidthxDepth Unit Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase / Frequency / Voltage

mm kg kg

% kW

l l/s kPa

l/s rpm dBA dBA

100 101

120 121

inch Hz / V

160 163

180 183

210 214

260 256

310 307

360 360

410 413

Stepless 25 38.7 2.61

46.9 2.57

2.93 2,273x1,292x2,165 1,684 1,699

53.4 60.3 2.58 2.70 2.75 2.93 2,273x1,292x3,065 1,861 1,881

12 4.83

15 5.76

17 6.58

24

25

10,922

10,575 91.5 73.5

°CDB °CDB kg

140 138

18

21

20 7.77 24

68.5 71.7 2.67 2.98 2.81 3.02 2,273x1,292x3,965 2,086 2,116 Brazed plate 24 30 8.74 10.22 22

86.7 2.95 3.18

111 133 2.77 2.71 3.05 3.23 2,223x2,236x3,070 2,919 2,963

146 2.84 3.34

25 12.22

30 14.65

44 19.74

21

High efficiency fin and tube type with integral subcooler 16,383 15,863 21,844 21,150 32,767 920 92.3 93.0 94.2 73.7 73.9 75.1 75.0 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 23 28 30 33 46 1 3 3~ / 50 / 400

16

36 17.21

48

45 31,725 94.5 75.3

95.2 76.0

56

60


EWAD-E-SL

Standard efficiency Low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

100 97.9

120 116

inch Hz / V

160 157

180 177

210 209

250 249

300 296

350 345

400 398

Stepless 25 38.8 47.9 2.52 2.42 3.01 2.97 2,273x1,292x2,165 1,784 1,799

53.0 60.6 2.53 2.60 2.85 3.00 2,273x1,292x3,065 1,961 1,981

12 4.68

17 6.40

15 5.54 23

8,372

8,144 89.0 71.0

째CDB 째CDB kg

130 134

18

21

20 7.51

67.8 72.1 2.61 2.89 3.07 3.32 2,273x1,292x3,965 2,186 2,216 Brazed plate 24 30 8.47 9.97 21

20

84.5 2.95 3.55

110 134 2.69 2.58 3.41 3.34 2,223x2,236x3,070 3,029 3,073

150 2.65 3.45

25 11.90

30 14.15

36 16.50

44 19.01

46

45

44

42

High efficiency fin and tube type with integral subcooler 12,558 12,217 16,744 16,289 25,117 715 89.8 90.5 91.7 71.2 71.4 72.6 72.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 23 28 30 33 46 1 3 3~ / 50 / 400

17

24,433 92.0 72.8

92.7 73.5

56

60


EWAD-D-SS

Air cooled chiller, standard efficiency EWAD390D-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ››

Standard efficiency level Standard sound level configuration: condenser fan rotating at 920 rpm, rubber antivibration under compressor (SS) Low sound level configuration: condenser fan rotating at 715/900 rpm, rubber antivibration under compressor, compressor sound enclosure (SL) Stepless single-screw compressor Optimised for use with R-134a Large operation range (ambient temperature down to -18°C) Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communication

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

390 389

440 436

470 466

152 2.56 3.36 2,223x2,234x3,139 2,960 3,090

164 2.66 3.54

167 2.79 3.55

4,030 4,195

4,220

530 532

560 556

580 578

194 2.74

205 2.72 3.56

197 2.93 3.39

3.52 2,223x2,234x4,040 4,230 4,395 Single pass shell & tube 165

4,235

130

165

175

18.60

20.80

22.20

24.00

25.40

26.50

27.60

45.6

37.9

66.5

47.1

52.1

57.4

51.2

32,772 95.8

96.7

76.5

56

139.7

Hz / V

3~ / 50 / 400

18

42,300 98.7

78.5

Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 70 76 82

60

160

High efficiency fin and tube type with integral subcooler 43,694 43,455 43,694 920 96 96.7 98.2 77.0

°CDB °CDB

kg mm

510 502 Stepless 12.5 184 2.73

79.0

87

92


EWAD-D-SL

Standard efficiency Low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

180 184

200 198

81.4 79.7 2.26 2.48 3.00 3.12 2,355x2,234x2,239 2,475 2,470 2,500 Plate to plate 25 30

230 225

250 245

84.5 2.66 3.31

93.4 101 108 2.62 2.58 2.54 3.21 3.26 3.23 2,355x2,234x3,139 2,860 2,960

9.40

10.70

11.70

28.9

21.8

57.8

49.0

15,300

280 275

100

8.80

14,900

22,900 900

300 320 370 400 298 321 370 404 Stepless 12.5 119 123 133 169 2.50 2.60 2.78 2.39 3.20 3.24 3.41 3.65 2,223x2,234x3,139 2,960 4,029 3,090 4,194 Single pass shell & tube 130 165

42

48

50

170

195 2.73 3.77 4,234

165

160

17.70

19.30

21.00

22.80

24.10

25.40

53.9

58.9

59.5

55.2

67.4

47.5

62.1

54.0

48.4

43.4

High efficiency fin and tube type with integral subcooler 22,600 22,300 24,428 94.7

33,489

32,572

97.2

715 94.2

95.7

96.2

77.5

74.5

76.0

76.5

84

86

Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 54 58 66 70

76 139.7

3~ / 50 / 400

19

170 186 203 2.59 2.57 2.49 3.67 3.57 3.67 2,223x2,234x4,040 4,224 4,229 4,394

530 533

15.30

114.3

Hz/V

510 505

14.20

94.3

88.9

480 477

13.10

75.0

36

440 440

12.50

93.7

째CDB 째CDB

kg mm

260 261

82


EWAD-D-SR

Air cooled chiller, standard efficiency EWAD370D-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ››

Standard efficiency level Reduced sound level configuration: condenser fan rotating at 680/715 rpm, rubber antivibration under compressor, compressor sound enclosure (SR) Extra low sound level configuration: condenser fan rotating at 500 rpm, rubber antivibration under compressor, compressor and evaporator sound enclosure (SX) Stepless single-screw compressor Optimised for use with R-134a Large operation range (ambient temperature down to -18°C) Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communication

Standard efficiency Reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

180 177

190 190

84.0 82.7 2.11 2.30 2.89 3.00 2,355x2,234x2,239 2,620 2,650 Plate to plate 25 30

220 219

240 238

85.2 2.57 3.34

94.7 103 111 2.51 2.44 2.38 3.21 3.23 3.16 2,355x2,234x3,139 2,890 3,100

9.10

10.40

11.30

26.9

20.1

55.1

46.6

15,300

mm

270 265

280 310 370 400 278 312 366 404 Stepless 12.5 122 125 138 169 2.28 2.49 2.65 2.39 3.13 3.25 3.42 3.65 2,223x2,234x3,139 3,110 4,040 3,240 4,342 Single pass shell & tube 130 165

100

8.50

14,900

22,900 680

12.00 50.8

12.60

13.30

55.2

89.3

42

48

50

88.9

530 533

170 186 203 2.59 2.57 2.49 3.67 3.57 3.67 2,223x2,234x4,040 4,240 4,542

195 2.73 3.77

165

160

19.30

21.00

22.80

24.10

25.40

52.7

65.1

47.5

62.1

54.0

48.4

43.4

89.7

170

33,489

32,572

92.2

715 90.7

92.2

92.7

72.5

71.0

72.5

73.0

84

86

Semi-hermetic single screw compressor -15~15 -18~48 R-134a 54 58 66 70 2

76 139.7

3~ / 50 / 400

20

510 505

17.40

114.3

Hz / V

480 477

14.90

70.0

36

440 440

High efficiency fin and tube type with integral subcooler 22,600 22,300 24,428

88.7

°CDB °CDB kg

250 252

82


EWAD-D-SX

Standard efficiency Extra low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

210 203

230 231

250 253

79.9 2.54 3.39 2,420x2,234x3,139 3,110 3,200

85.2 2.71 3.63

93.5 2.70 3.52 3,475

90

115

9.70

11.00

12.10

44.7

33.8

38

12,900

270 271

300 310 299 309 Stepless 12.5 104 114 126 136 2.59 2.50 2.37 2.27 3.55 3.44 3.39 3.25 2,420x2,234x4,040 3,425 3,430 3,590 Single pass shell & tube 165 160

370 370

410 413

148 2.49 3.24

169 2.44 3.49

3,560 3,735

4,302 4,472

84.3

173 187 2.60 2.63 3.61 3.58 2,420x2,234x4,940 4,506 4,581 4,676 4,746

175

170

165

14.30

14.70

17.70

19.70

21.50

23.50

38.3

34.9

37.7

40.5

44.5

43.9

50

44.8

25,933

28,625

33,116

65.0 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 60

56 114.3

Hz / V

65

70 139.7

3~ / 50 / 400

21

490 492

13.70

High efficiency fin and tube type with integral subcooler 17,200 26,495 500 84.7

17,900

450 451

12.90

째CDB 째CDB

kg mm

290 286

85.7

86.2

65.5

66.0

76

82


EWAD-D-XS

Air cooled chiller, high efficiency EWAD370D-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ››

High efficiency Standard sound level configuration: condenser fan rotating at 900/920 rpm, rubber antivibration under compressor (XS) Reduced sound level configuration: condenser fan rotating at 680/715 rpm, rubber antivibration under compressor, compressor sound enclosure (XR) Stepless single-screw compressor Optimised for use with R-134a Large operation range (ambient temperature down to -18°C) Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communication

High efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

250 247

280 275

300 302

79.1 3.12 3.56 2,355x2,234x3,138 2,905 3,000

87.1 3.16 3.60

94.1 3.20 3.62

104 113 127 3.15 3.12 3.16 3.85 3.67 3.59 2,355x2,234x4,040 3,235 3,240 3,400 Single pass shell & tube 165 160 15.60 46.1

3,285

95

115

11.80

13.10

14.40

48.1

44.9

48.8

22,300

330 327

380 376 Stepless 12.5 120 3.14 3.58

400 401

470 469

520 524

150 3.12 3.84 2,223x2,234x4,040 3,510 3,780

166 3.15 4.00

16.70

17.90

19.10

22.40

30,600

96.8

25.00

27.40

29.70

50.8

57.6

63.5

47.4

62.9

56.2

37.9

77.5

58

66

76

Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 73 76

22

255

54,616 920 99.2

86

100 168.3

3~ / 50 / 400

620 622

181 194 3.18 3.20 4.01 3.88 2,223x2,234x4,940 4,670 4,685 4,940

79.0

114.3

Hz / V

580 575

270

High efficiency fin and tube type with integral subcooler 29,700 44,000 43,000 43,695 900 97.2 98.7

°CDB °CDB

kg mm

350 351


EWAD-D-XR

High efficiency Reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

240 243

270 272

300 296

320 322

80.6 3.01 3.63 2,355x2,234x3,138 3,005 3,100

87.0 3.12 3.70

95.1 3.11 3.69

106 115 127 3.05 2.99 3.10 3.82 3.71 3.82 2,355x2,234x4,040 3,335 3,340 3,500 Single pass shell & tube 165 160 15.40 44.7

3,385

95

115

11.60

13.00

14.10

46.7

44.0

47.5

370 370 Stepless 12.5 119 3.12 4.01

390 394

460 455

510 512

152 2.99 3.89 2,223x2,234x4,040 3,610 3,880

167

16.40

17.70

18.80

21.70

91.8

24.40

26.80

28.60

49.2

56.2

55.6

44.8

60.4

53.7

36.1

72.5

60

560 561

183 198 3.07 3.03 4.11 3.93 2,223x2,234x4,940 4,770 4,785 5,040 255

41,861

41,864 715 93.7

73.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 80

68 114.3

Hz/V

23

104 168.3

3~ / 50 / 400

600 600

270

High efficiency fin and tube type with integral subcooler 12,500 33,488 680 92.2 93.2

째CDB 째CDB

kg mm

350 345


EWAD-D-HS

Air cooled chiller, high ambient EWAD380D-HS

MicroTech III

›› ›› ›› ›› ›› ›› ››

High ambient Standard sound level configuration: condenser fan rotating at 900/920 rpm, rubber antivibration under compressor Stepless single-screw compressor Optimised for use with R-134a Large operation range (ambient temperature down to -18°C) Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

High ambient Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Fan motor Speed Cooling Nom. Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg l l/s kPa

l/s rpm dBA dBA

200 195

210 208

77.2 75.5 2.52 2.76 3.11 3.26 2,223x2,234x2,239 2,475 2,470 2,500 Plate to plate 25 30

230 234

260 256

83.0

270 274

91.0

97.7 104 2.80 2.78 3.34 3.21 3.30 3.28 2,223x2,234x3,339 2,865 2,870 2,960 2.81

95

310 306

340 380 420 336 381 415 Stepless 12.5 120 127 141 2.80 3.00 2.94 3.25 3.57 3.61 2,223x2,234x4,040 3,185 3,277 3,300 3,447 Single pass shell & tube 115

112 2.73 3.27

90

450 448

480 478

150 2.98

162 2.95

510 514

550 547

175 182 2.94 3.00 3.68 3.66 3.71 2,223x2,234x4,940 3,942 4,356 4,361 4,112 4,526 170

165

590 587

191 3.07 3.79 4,366

160

9.30

9.90

11.10

12.20

13.10

13.80

14.60

16.00

18.20

19.80

21.40

22.80

24.50

26.10

28.00

31.5

23.7

46.1

52.1

53.7

59.3

64.4

58.3

69.9

45.8

52.5

58.0

50.9

55.7

52.6

23,900 22,800

High efficiency fin and tube type with integral subcooler 35,000 34,100 47,900 43,694 42,300 900 96.3 96.7 98.7 96.7

35,900

95.7

77.0

79.0

°CDB °CDB

kg mm

290 289

36

42

44

55

88.9

Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 56 58 66 70 114.3

Hz / V

90

97.7

99.2

99.7

77.5

79.0

79.5

95

100 139.7

3~ / 50 / 400

24

77.0

54,616 920


25


EWAD-BZSS/SL

Air cooled inverter chiller EWAD330,360BZ

PCO2

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

ESEER up to 4.70 (SS/SL) High seasonal efficiency (ESEER up to 5.01) (XS/XL/XR) All models are PED pressure vessel approved Inverter stepless single-screw compressor Optimised for use with R-134a Cooling range: 329-515kW 2 truly independent refrigerant circuits DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops The ability to vary the output power in direct relation to the cooling requirements of the system allows to achieve building comfort conditions much faster at start-up Standard electronic expansion valve Partial and total heat recovery option available Power factor over 0.95 Standard operation range down to -10°C

Standard efficiency Standard/low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (SS) Weight (SL) Water heat exchanger

Air heat exchanger Fan Sound power level (SS) Sound power level (SL) Sound pressure level (SS) Sound pressure level (SL) Compressor Operation range Refrigerant

Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

kW

HeightxWidthxDepth Unit Unit Operation weight Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase / Frequency / Voltage

mm kg kg kg kg

% kW

l l/s kPa

l/s rpm dBA dBA dBA dBA

330 329

360 358

120.0 136 2.74 2.63 4.59 4.60 2,355x2,234x4,381 4,190 4,440 4,340 4,590 271 15.72

17.10

264

60

61

420 423 Stepless 13.5 147 159 2.69 2.66 4.55 4.59 2,355x2,234x5,281 4,590 4,840 4,740 4,990 Single pass shell & tube 256 18.87 20.21 72

67

460 459

490 488

520 515

168 2.73 4.57

181 2.70 4.70 2,355x2,234x6,181 4,990 5,240 5,140 5,390

193 2.67 4.60

21.93

23.32

24.61

78

69

76

248

High efficiency fin and tube type with integral subcooler 40,833 700 103.2 97.3 83.0 77.0 Semi-hermetic single screw compressor -9.5~15 -10~45 R-134a 99 105 114 2 168.3 3~ / 50 / 400

32,667 102.8 96.9

°CDB °CDB kg

400 395

73

mm Hz / V

26

49,000 103.6 98.2 83.5 77.5

118

121


EWAD-BZXS/XL/XR

High efficiency Standard/low/reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (XS)

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Weight (XL) Unit Operation weight Weight (XR) Unit Operation weight Water heat Type exchanger Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level (XS) Cooling Nom. Sound pressure Cooling Nom. level (XS) Sound power level (XL) Cooling Nom. Sound pressure Cooling Nom. level (XL) Sound power level (XR) Cooling Nom. Sound pressure Cooling Nom. level (XR) Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage

kW % kW

mm kg kg kg kg kg kg l l/s kPa

330 329

360 358

118.0 135 2.79 2.65 4.79 4.82 2,355x2,234x4,381 4,190 4,440 4,340 4,590 4,390 4,640 271 15.72

17.10

264

60

61

l/s rpm dBA dBA

32,667

dBA dBA

96.9

dBA dBA

92.9

420 423 Stepless 13 145 157 2.72 2.69 4.78 4.84 2,355x2,234x5,281 4,590 4,840 4,740 4,990 4,790 5,040 Single pass shell & tube 256 18.87 20.21 72

67

460 459

490 488

520 515

165 2.78 4.81

178 2.74 5.01 2,355x2,234x6,181 4,990 5,240 5,140 5,390 5,190 5,440

190 2.71 4.84

21.93

23.32

24.61

78

69

76

248

High efficiency fin and tube type with integral subcooler 40,833 700 103.2

102.8

83.0

77.0

73.0

27

98.2

94.2 73.5

Semi-hermetic single screw compressor -9.5~15 -10~45 R-134a 99 105 114 2 168.3 3~ / 50 / 400

mm Hz / V

103.6

77.5 93.3

73

49,000

83.5 97.3

째CDB 째CDB kg

400 395

118

121


EWAD-C-SS/SL

Air cooled chiller, standard efficiency EWAD-C15C-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Wide capacity range: 15 sizes to cover a range from 647 to 1,922 kW (SS/SL), 16 sizes from 619 to 1,833 kW (SR) Stepless single-screw compressor Large operation range (ambient temperature down to -18°C and up to 46°C) Reduced sound version (SR) All models are PED pressure vessel approved Optimised for use with R-134a 2-3 truly independent refrigerant circuits Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard/low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (SS) Weight (SL) Water heat exchanger

Air heat exchanger Fan Sound power level (SS) Sound pressure level (SS) Sound power level (SL) Sound pressure level (SL) Compressor Operation range Refrigerant

Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water pressure drop Cooling Heat exchanger Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase/Frequency/Voltage

kW % kW

mm kg kg kg kg l l/s kPa l/s rpm dBA dBA dBA dBA °CDB °CDB kg mm Hz/V

650 647

740 744

830 832

910 912

970 967

C12 1,152

C13 H14 1,319 1,418 Stepless

C15 1,538

C16 1,622

C17 1,714

C18 1,802

C19 1,875

C20 1,922

7 402 441 474 551 580 618 665 682 714 2.86 2.99 2.79 2.8 2.77 2.71 2.75 2.69 3.84 4.08 4.07 3.9 3.87 3.78 3.79 3.81 3.77 2,540x2,285 2,540x2,285x8,885 2,540x2,285x11,085 2,540x2,285x11,985 2,540x2,285x6,185 x7,985 5,630 5,740 5,760 6,280 6,560 7,280 7,900 10,320 10,710 10,770 11,240 11,600 5,910 5,990 6,010 6,530 6,810 7,520 8,280 10,730 11,110 11,260 12,110 12,480 5,920 6,030 6,050 6,570 6,850 7,570 8,190 10,770 11,150 11,210 11,680 12,040 6,200 6,280 6,300 6,820 7,100 7,810 8,570 11,170 11,550 11,700 12,560 12,920 Single pass shell & tube 266 251 243 386 408 474 850 30.9 35.56 39.74 43.6 46.21 50.85 55.04 62.9 67.7 73.5 77.51 81.89 86.00 89.50 91.70 73 59 52 61 68 63 72 54 58 59 65 73 36 39 40 High efficiency fin and tube type with integral subcooler 53,444 64,133 74,822 85,510 96,199 106,888 117,577 128,266 920 99.5 100.0 100.9 101.1 101.5 101.7 101.9 103.0 103.2 103.3 103.5 103.7 79.0 79.5 80.4 80.6 80.7 81.1 81.2 81.5 81.9 96.0 96.1 97.5 97.1 97.6 98.1 98.2 99.1 99.5 99.9 101 75.5 75.6 76.5 76.6 76.8 76.9 77 77.2 77.3 77.4 77.9 78 Semi-hermetic single screw compressor -8~15 -18~46 R-134a 128 146 144 162 178 196 260 261 275 305 2 3 168.3 219.1 3~/50/400 221 2.93 3.95

262 2.84 3.87

299 2.78 3.89

318 2.87 3.84

28

12.5 351 2.76 3.8

C11 1,064

378 2.82 3.88 2,540x2,285 x7,085 7,010 7,250 7,300 7,540


EWAD-C-SR

Standard efficiency Reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

620 619

720 715

790 789

880 876

920 922

223 2.77 4.08

272 2.62 3.96

315 2.51 3.98

331 2.65 3.99

12.5 369 2.5 4

5,920 6,200

6,030 6,280

mm kg kg l l/s kPa

l/s rpm dBA dBA

2,540x2,285x6,185 6,050 6,300

6,750 6,820

266

251

mm

C11 1,112

C12 H14 1,270 1,321 Stepless

C13 1,367

C14 1,471

C15 1,556

C14 1,623

C17 1,714

C18 1,795

C19 1,833

7 395 417 457 495 517 576 603 647 702 718 757 2.59 2.67 2.78 2.67 2.64 2.55 2.58 2.51 2.44 2.50 2.42 3.96 4.12 4.00 3.9 3.87 3.9 3.83 3.79 3.82 3.77 2,540x2,285 2,540x2,285 2,540x2,285x8,885 2,540x2,285x10,185 2,540x2,285x11,085 2,540x2,285x11,985 x7,085 x7,985 6,850 7,300 7,570 8,190 10,750 10,770 11,150 11,210 11,680 12,040 7,100 7,540 7,810 8,570 11,170 11,550 11,700 12,560 12,920 Single pass shell & tube 243 386 421 408 474 850

29.57

34.15

37.71

41.83

44.05

48.75

53.11

60.67

63.11

65.32

70.28

74.32

77.57

81.80

85.60

87.50

67

55

47

57

62

58

68

50

54

44

54

60

66

33

36

37

41,006 91.5

92.0

71.0

71.5

High efficiency fin and tube type with integral subcooler 49,207 57,408 65,610 73,811 82,012 90,213 715 92.5 93.0 93.5 93.8 94 94.8 94.9 95.1 95.2 72

72.5

째CDB 째CDB kg

C10 1,020

128

144 2

72.6

72.7

72.9

Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 46 R-134a 162 178 196 260 219.1 3~ / 50 / 400

29

73.1

261

98,417

95.5 73.4

95.9 73.7

275

74

305

3

168.3

Hz / V

73.0

90,216

273


EWAD-C-XS/XL

Air cooled chiller, high efficiency EWAD-C11-C13C-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Wide capacity range: 17 sizes to cover a range from 756 to 2,008 kW (XS/XL), from 736 to 1,959 kW (XR) Stepless single-screw compressor Large operation range (ambient temperature down to -18°C and up to 50°C) All models are PED pressure vessel approved Optimised for use with R-134a 2-3 truly independent refrigerant circuits Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

High efficiency Standard/low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (XS) Weight (XL) Water heat exchanger

Air heat exchanger Fan Fan motor Sound power level (XS) Sound pressure level (XS) Sound power level (XL) Sound pressure level (XL) Compressor Operation range Refrigerant

Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water pressure drop Cooling Heat exchanger Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase/Frequency/Voltage

kW % kW

760 756

830 830

890 889

kg kg kg kg

233 3.25 4.02 2,540x2,285 x6,185 5,990 6,240 6,280 6,520

253 278 3.28 3.2 4.11 4.02 2,540x2,285 x7,085 6,340 6,360 6,580 6,600 6,630 6,650 6,870 6,890

l l/s kPa

251 36.1 80

243 39.67 42.49 56 64

l/s rpm dBA dBA dBA dBA

64,133

74,822

100.2

100.5 79.7 97.4 76.5

mm

96.8 76.3

°CDB °CDB kg mm Hz/V

146

162 168.3

990 C10 C11 C12 C13 H14 H15 C16 C17 C18 C19 C20 C21 C22 1,001 1,074 1,196 1,280 1,349 1,415 1,525 1,596 1,685 1,768 1,858 1,901 1,953 2,008 Stepless 12.5 7 307 338 364 400 411 444 475 504 533 561 590 615 642 672 3.26 3.18 3.29 3.2 3.29 3.19 3.21 3.17 3.16 3.15 3.09 3.04 2.99 4.11 4.05 4.14 4.02 4.28 4.31 4.35 4.17 4.16 4.13 4.12 4.03 4.01 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285x9,785 2,540x2,285x14,685 x7,985 x11,985 x12,885 x13,785 7,190 7,470 8,220 8,240 8,900 11,570 11,900 12,260 12,600 7,600 7,870 8,610 8,630 9,890 12,430 12,760 13,140 13,470 7,480 7,760 8,510 8,530 9,190 12,010 12,350 12,700 13,040 7,880 8,160 8,900 8,920 10,180 12,870 13,200 13,580 13,910 Single pass shell & tube 403 386 979 850 871 850 47.82 51.32 57.13 61.18 64.45 67.50 72.86 76.24 80.48 84.47 88.79 90.77 93.2 95.8 61 69 45 51 71 77 84 62 68 64 37 39 41 43 High efficiency fin and tube type with integral subcooler 128,266 138,954 149,643 160,332 85,510 106,888 920 101.4 101.9 102.4 102.5 103.2 103.5 103.7 103.9 80.2 80.7 80.3 80.4 80.9 80.8 81 98 98.2 98.8 98.9 99.6 100 100.2 100.4 76.9 77.1 76.7 76.8 77.3 77.4 77 77.5 Semi-hermetic single screw compressor -8~15 -18~50 R-134a 182 214 225 248 297 312 328 343 343 2 3 219.1 273 3~/50/400

30


EWAD-C-XR

High efficiency Reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight Water heat exchanger

Air heat exchanger Fan Sound power level Sound pressure level Compressor Operation range Refrigerant

Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water pressure drop Cooling Heat exchanger Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase/Frequency/Voltage

kW % kW

mm kg kg l l/s kPa l/s rpm dBA dBA 째CDB 째CDB kg mm Hz/V

740 736

810 811

870 866

970 974

C10 1,041

C11 1,168

C12 1,247

C13 1,302

H14 1,367

H15 1,468

C16 1,550

C17 1,639

C18 1,722

C19 1,813

C20 1,854

C21 1,902

C22 1,959

12.5 7 254 281 309 343 365 404 415 454 491 513 541 567 595 624 658 692 3.2 3.08 3.15 3.03 3.2 3.08 3.14 3.01 2.99 3.03 3.04 2.97 2.89 2.83 4.36 4.23 4.34 4.24 4.38 4.25 4.33 4.38 4.43 4.26 4.2 4.21 4.2 4.1 4.08 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285x9,785 2,540x2,285x14,685 x7,085 x7,985 x11,985 x12,885 x13,785 6,630 6,650 7,480 7,760 8,510 8,530 9,190 12,010 12,350 12,700 13,040 6,870 6,890 7,880 8,160 8,900 8,920 10,180 12,870 13,200 13,580 13,910 Single pass shell & tube 251 243 403 386 979 850 871 850 35.17 38.74 41.36 46.54 49.76 55.78 59.56 62.21 65.20 70.00 74.07 78.32 82.3 86.61 88.5 90.7 93.5 76 54 61 58 65 43 49 67 73 79 59 65 61 35 37 39 41 High efficiency fin and tube type with integral subcooler 123,021 49,207 57,408 65,610 82,012 82,014 98,414 106,616 114,817 123,018 715 92 92.3 93.5 93.7 94.3 94.5 94.4 94.6 95.3 95.6 95.7 95.9 96.2 96.6 71.5 72.3 72.5 72.2 72.3 72.5 72.9 73 73.3 73.7 Semi-hermetic single screw compressor -8~15 -18~50 R-134a 146 162 182 214 225 248 297 312 328 343 343 2 3 168.3 219.1 273 3~/50/400 235 3.14 4.29 2,540x2,285 x6,185 6,280 6,520

31


EWAD-C-PS/PL

Air cooled chiller, premium efficiency EWAD-C-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Premium efficiency version (PS/PL) Premium efficiency and reduced sound version (PR) Wide capacity range: 9 sizes to cover a range from 821 to 1,562 kW (PS/PL), from 809 to 1,521 kW (PR) Stepless single-screw compressor Large operation range (ambient temperature down to -18°C and up to 52°C) All models are PED pressure vessel approved Optimised for use with R-134a 2 truly independent refrigerant circuits Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Premium efficiency Standard/low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (PS)

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Weight (PL) Unit Operation weight Water heat Type exchanger Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level (PS) Cooling Nom. Sound pressure Cooling Nom. level (PS) Sound power level (PL) Cooling Nom. Sound pressure Cooling Nom. level (PL) Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage

kW % kW

820 821

890 890

980 975

225 3.64 4.44

249 3.58 4.5

274

mm

l l/s kPa

7,530 8,130 7,820 8,420

4.41

7,660 8,700 7,950 8,990

599

301

3.56

2,540x2,285x8,885

kg kg kg kg

C11 1,074

39.22

42.53

1,043 46.6

57

65

30

C12 1,158 Stepless 12.5 330 3.51 4.39

C13 1,279

363 3.52 4.53 4.44 2,540x2,285 2,540x2,285x9,785 x11,085 8,290 8,550 9,390 9,330 9,590 10,380 8,580 8,840 10,380 9,620 9,880 10,670 Single pass shell & tube 1,027 995 51.3 55.31 61.12 61

69

60

C14 1,390

C15 1,474

C16 1,562

396 3.51 4.31

424 3.48 4.33

453 3.45 4.32

2,540x2,285x11,985 9,730 10,720 10,720 11,010

66.41

979 70.30

74.50

73

81

89

High efficiency fin and tube type with integral subcooler 106,888 117,577 128,266 920 101.8 102.3 102.6 102.9

l/s rpm dBA dBA

96,199

79.5

80

80.5

80.4

80.5

80.8

81.1

dBA dBA

98.4

98.8

99.9

99.3

99.6

99.9

100.2

77.2

77.5

77.8

101

76.9

77

°CDB °CDB kg mm Hz / V

204

202

204

219.1

32

77.1

Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 52 R-134a 220 252 2 273 3~ / 50 / 400

128,266 103.2

254

103.5


EWAD-C-PR

Premium efficiency Reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Water heat Type exchanger Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW

810 809

880 875

960 956

C10 1,053

219 3.7 4.63

244 3.58 4.59

272 3.51 4.54

299 3.52 4.59

mm

2,540x2,285x8,885

kg kg l l/s kPa

7,820 8,420

7,950 8,990

38.65

599 41.81

1,043 45.69

56

63

29

l/s rpm dBA dBA

73,811 92.7 71.2

mm

204

C13 1,251

364 3.44 4.53 2,540x2,285 2,540x2,285x9,785 x11,085 8,580 8,840 10,380 9,620 9,880 10,670 Single pass shell & tube 1,027 995 50.3 54.11 59.76 59

66

58

C14 1,359

C15 1,439

C16 1,521

396 3.43 4.51

425 3.39 4.50

457 3.33 4.45

2,540x2,285x11,985 10,720 11,010

64.95

979 68.7

72.6

70

77

84

High efficiency fin and tube type with integral subcooler 82,012 90,213 98,414 715 93.4 93.8 94.1 94.4 71.7 72.0 Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 52 R-134a 204 220 252 2

째CDB 째CDB kg

C11 1,132 Stepless 12.5 330 3.43 4.5

202 219.1

273

Hz / V

3~ / 50 / 400

33

98,417 94.7 72.3

254

95 72.6


EWAD-CZXS/XL

Air cooled inverter chiller, high efficiency EWAD-CZ

MicroTech III

›› ›› ›› ›› ›› ›› ›› ››

ESEER up to 5.76 (XS/XL), 5.79 (XR) Inverter stepless single-screw compressor High efficiency, standard and low sound levels Optimised for use with R-134a Wide operating range Extensive option list (partial and total heat recovery option available) Low starting current MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

High efficiency Standard/low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (XS) Weight (XL) Water heat exchanger

Air heat exchanger Fan Fan motor Sound power level (XS) Sound pressure level (XS) Sound power level (XL) Sound pressure level (XL) Compressor Operation range Refrigerant Refrigerant circuit Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water pressure drop Cooling Heat exchanger Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Circuits Quantity Charge Evaporator water inlet/outlet Phase/Frequency/Voltage

kW % kW

mm kg kg kg kg l l/s kPa l/s rpm dBA dBA dBA dBA °CDB °CDB

kg mm Hz/V

670 672

740 738

830 832

900 902

C10 1,037

C11 1,095 20

C12 1,236 Stepless

C13 1,308

C14 1,450

C15 1,545

C16 1,622

C17 1,709

C18 1,802

13 400 442 488 531 558 611 3.09 2.96 2.97 2.91 2.90 2.95 4.93 4.74 5.02 5.17 5.03 5.76 4.85 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285x6,725 2,540x2,285x7,625 2,540x2,285x8,525 x11,625 x12,525 x13,425 x14,325 x10,325 5,880 6,000 6,620 6,870 7,440 8,570 8,970 9,600 9,940 11,370 12,190 12,920 6,140 6,250 6,860 7,110 7,880 8,960 9,360 9,980 10,320 12,220 13,040 13,790 6,170 6,280 6,900 7,150 7,720 8,850 9,250 9,880 10,220 11,790 12,610 13,340 6,430 6,530 7,140 7,390 8,160 9,240 9,640 10,260 10,600 12,640 13,460 14,210 Single pass shell & tube 263 248 241 441 383 374 850 871 32.00 35.20 39.70 43.00 49.50 52.30 59.00 62.40 69.20 73.70 77.40 81.50 86.00 80 75 55 64 63 69 46 51 61 71 62 68 64 High efficiency fin and tube type with integral subcooler 54,188 65,025 75,863 86,700 108,376 119,213 130,051 129,454 140,143 151,129 900 102.1 102.2 102.5 102.9 103.5 104.1 105.8 106.0 106.2 81.0 81.1 81.2 82.8 82.9 98.6 99.2 99.5 99.9 100.5 101.1 102.8 103.0 103.2 77.5 78.0 78.1 78.2 79.8 79.9 Semi-hermetic single screw compressor -8~15 -18~50 R-134a 2 3 141 161 178 200 235 275 320 327 343 361 168.3 219.1 273 3~/50/400 245 2.74 5.07

235 3.14 5.13

266 3.13 5.20

305 2.96 5.22

34

339 3.06 5.24

375 2.92 5.03


EWAD-CZXR

High efficiency Reduced sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight Water heat exchanger

Air heat exchanger Fan Fan motor Sound power level Sound pressure level Compressor Operation range Refrigerant Refrigerant circuit Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water pressure drop Cooling Heat exchanger Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Circuits Quantity Charge Evaporator water inlet/outlet Phase/Frequency/Voltage

kW % kW

mm kg kg l l/s kPa l/s rpm dBA dBA 째CDB 째CDB

kg mm Hz/V

640 635

700 700

790 789

850 852

980 976

C10 1,031 20

C11 1,170 Stepless

C12 1,235

C13 1,332

C14 1,443

C15 1,545

C16 1,631

C17 1,712

13 408 455 524 589 580 610 631 2.86 2.71 2.55 2.45 2.66 2.67 2.71 5.76 5.41 5.05 5.45 5.60 5.51 5.33 5.19 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285x6,725 2,540x2,285x7,625 2,540x2,285x8,525 x11,625 x12,525 x13,425 x14,325 x10,325 6,170 6,470 7,100 7,360 7,950 9,120 9,530 10,180 10,530 12,150 12,990 13,740 6,430 6,720 7,340 7,600 8,390 9,500 9,920 10,550 10,910 13,000 13,840 14,610 Single pass shell & tube 263 248 241 441 383 374 850 871 30.30 33.40 37.60 40.70 46.60 49.20 55.80 58.9 63.60 68.80 73.70 77.80 81.70 73 69 51 58 57 63 43 47 53 59 57 62 59 High efficiency fin and tube type with integral subcooler 41,536 49,843 58,151 66,458 83,072 99,687 107,994 116,301 700 94.6 95.2 95.5 95.9 96.5 97.1 98.8 99.0 99.2 73.5 74.0 74.1 74.2 75.8 75.9 Semi-hermetic single screw compressor -8~15 -18~50 R-134a 2 3 141 161 178 200 235 275 320 327 343 361 168.3 219.1 273 3~/50/400 260 2.44 5.52

242 2.89 5.71

271 2.91

314 2.71

35

347 2.81 5.79

388 2.65 5.49


EWAD-CFXS/XL

Air cooled free cooling chiller, high efficiency EWAD-CF

MicroTech III

›› ›› ›› ›› ›› ››

Free cooling chiller High efficiency, standard/low (XS/XL) & reduced (XR) sound levels Greater energy savings and reduced CO2 emissions during cold season Wide capacity range: 11 sizes between 602 and 1,476 kW (XR), 640 and 1,555 kW (XS/XL) Wide operating range MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

High efficiency Standard/low sound

Cooling only Capacity class Cooling capacity

Nom.

kW

Mechanical capacity Air temperature for free cooling 100% Capacity control Method Minimum capacity Power input Cooling Nom.

kW °C % kW

EER ESEER Dimensions Weight (XS) Weight (XS) Water heat exchanger

Air heat exchanger Fan Sound power level (XS) Sound pressure level (XS) Sound power level (XL) Sound pressure level (XL) Compressor Operation range Refrigerant

Piping connections Power supply

Unit

HeightxWidthxDepth

Unit Operation weight Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water Cooling Heat exchanger pressure drop Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase/Frequency/Voltage

mm kg kg kg kg l l/s kPa

l/s rpm dBA dBA dBA dBA °CDB °CDB kg mm Hz/V

640 640 (1) / 295 (2) 345 (2) -0.8

770 772 (1) / 365 (2) 407 (2) -0.1

850 852 (1) / 413 (2) 439 (2) 1.2

900 902 (1) / 434 (2) 468 (2) 0.4

257 (1) / 272 (1) / 293 (1) / 324 (1) / 74.3 (2) 87.9 (2) 90.7 (2) 99.8 (2) 2.49 (1) / 2.84 (1) / 2.90 (1) / 2.78 (1) / 8.62 (2) 8.78 (2) 9.4 (2) 9.04 (2) 3.44 3.52 3.78 3.50 2,565x2,480 2,565x2,480 2,565x2,480x7,985 x6,185 x7,085 7,760 8,340 8,900 8,040 8,580 9,140 8,050 8,620 9,190 8,320 8,870 9,430

C10 C11 C12 C13 C14 C15 C16 1,027 (1) / 1,089 (1) / 1,269 (1) / 1,349 (1) / 1,435 (1) / 1,493 (1) / 1,555 (1) / 502 (2) 524 (2) 594 (2) 652 (2) 663 (2) 659 (2) 722 (2) 524 (2) 565 (2) 675 (2) 697 (2) 772 (2) 834 (2) 0.9 0.1 2.9 2.1 1.3 0.7 0.1 Stepless 12.5 360 (1) / 399 (1) / 397 (1) / 439 (1) / 454 (1) / 492 (1) / 530 (1) / 109 (2) 118 (2) 131 (2) 143 (2) 152 (2) 160 (2) 170 (2) 2.85 (1) / 2.73 (1) / 3.19 (1) / 3.08 (1) / 3.16 (1) / 3.04 (1) / 2.93 (1) / 9.43 (2) 9.19 (2) 9.67 (2) 9.45 (2) 9.42 (2) 9.33 (2) 9.16 (2) 3.74 3.54 3.88 3.78 4.01 3.95 3.85 2,565x2,480x8,885

2,565x2,480x10,685

10,160 10,420 11,900 10,560 10,820 12,290 10,450 10,710 12,190 10,850 11,110 12,580 Single pass shell & tube 266 251 243 403 386 27.8 33.5 37.0 39.2 44.6 47.3 55.1 58.6 105 / 172 101 / 198 111 / 245 124 / 272 110 / 259 85 / 128 (2) 90 / 178 (2) 98 / 232 (2) (2) (2) (2) (2) (2) High efficiency fin and tube type with integral subcooler 50,367 60,440 70,513 80,587 920 99.5 100.2 100.5 101.4 101.9 102.4 79.0 (1) 79.7 (1) 80.2 (1) 80.7 (1) 80.3 (1) 96.0 96.8 97.4 98.0 98.2 98.8 75.5 (1) 76.3 (1) 76.5 (1) 76.9 (1) 77.1 (1) 76.7 (1) Asymm single screw -8~15 -20~45 R-134a 128 146 162 182 214 2 168.3 219.1 3~/50/400

(1) Cooling: evaporator 16/10°C, ambient 35°C, unit at full load operation; standard: ISO 3744 (2) Data is calculated at ambient air temperature 5°C, inlet water temperature 16°C.

36

12,540 13,530 12,830 13,820

12,620 13,610 12,910 13,900

12,670 13,660 12,960 13,950

62.4 139 / 305 (2)

979 64.9 150 / 328 (2)

67.6 162 / 354 (2)

95,253 102.5 80.4 (1) 98.9 76.8 (1)

225

248 273


EWAD-CFXR

High efficiency Reduced sound

Cooling only Capacity class Cooling capacity

Nom.

kW

Mechanical capacity Air temperature for free cooling 100% Capacity control Method Minimum capacity Power input Cooling Nom.

kW °C % kW

EER ESEER Dimensions Weight

Unit

HeightxWidthxDepth

Unit Operation weight Water heat Type exchanger Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase/Frequency/Voltage

mm kg kg l l/s kPa l/s rpm dBA dBA °CDB °CDB kg mm Hz/V

600 602 (1) / 270 (2) 332 (2) -2.3

740 739 (1) / 334 (2) 405 (2) -1.9

820 821 (1) / 379 (2) 442 (2) -0.6

870 866 (1) / 409 (2) 457 (2) -1.5

980 981 (1) / 459 (2) 523 (2) -0.9

263 (1) / 278 (1) / 299 (1) / 334 (1) / 70.3 (2) 84.3 (2) 88.4 (2) 95.9 (2) 2.29 (1) / 2.66 (1) / 2.75 (1) / 2.59 (1) / 8.56 (2) 8.77 (2) 9.29 (2) 9.03 (2) 3.59 3.66 3.89 3.62 2,565x2,480 2,565x2,480 2,565x2,480x7,985 x6,185 x7,085 8,050 8,620 9,190 8,320 8,870 9,430

368 (1) / 106 (2) 2.67 (1) / 9.27 (2) 3.83

C10 C11 C12 C13 C14 C15 1,034 (1) / 1,229 (1) / 1,302 (1) / 1,374 (1) / 1,424 (1) / 1,476 (1) / 492 (2) 562 (2) 598 (2) 619 (2) 640 (2) 668 (2) 542 (2) 667 (2) 704 (2) 756 (2) 784 (2) 809 (2) -1.7 0.7 -0.2 -1.1 -1.6 -2.3 Stepless 12.5 412 (1) / 403 (1) / 450 (1) / 466 (1) / 511 (1) / 556 (1) / 112 (2) 127 (2) 141 (2) 146 (2) 154 (2) 161 (2) 2.51 (1) / 3.05 (1) / 2.90 (1) / 2.95 (1) / 2.79 (1) / 2.66 (1) / 9.21 (2) 9.67 (2) 9.22 (2) 9.4 (2) 9.26 (2) 9.15 (2) 3.63 4.13 3.89 4.09 4.02 3.92

2,565x2,480x8,885

2,565x2,480x10,685

10,450 10,710 12,190 12,830 10,850 11,110 12,580 13,820 Single pass shell & tube 266 251 243 403 386 26.2 32.1 35.7 37.6 42.6 44.9 53.4 56.6 59.7 / 225 113 / 248 92 / 219 (2) 103 / 243 128 / 282 76 / 115 (2) 97 / 159 (2) 84 / 167 (2) 93 / 184 (2) 102(2) (2) (2) (2) High efficiency fin and tube type with integral subcooler 38,934 46,721 54,508 62,294 73,010 715 91.5 92.0 92.3 93.5 93.7 94.3 94.5 71.0 (1) 71.5 (1) 72.3 (1) 72.5 (1) 72.2 (1) 72.3 (1) Asymm single screw -8~15 -20~45 R-134a 128 146 162 182 214 225 2 168.3 219.1 3~/50/400

(1) Cooling: evaporator 16/10°C, ambient 35°C, unit at full load operation; standard: ISO 3744 (2) Data is calculated at ambient air temperature 5°C, inlet water temperature 16°C.

37

12,910 13,900

12,960 13,950

979 61.9 137 / 301 (2)

64.1 146 / 321 (2)

94.6 72.5 (1)

248 273


EWYQ-ACV3

Air cooled heat pump mini chiller inverter EWYQ005-011ACV3

Digital controller

›› ›› ›› ›› ›› ›› ›› ››

Inverter technology ensures: continuous match of requested load, excellent part load efficiency (ESEER up to 4.57), significant reduction of starting currents ; precise temperature control (evaporator leaving water) Low operating sound level Easy ‘plug and play’ installation Daikin swing (sizes 005-006-007) or scroll compressor (sizes 009-010-011) Integrated hydronics Available options: evaporator heater type (OP10) and high ESP pump up to 90 kPa (OPHP) Single phase power supply and main switch included Wide operating range

Heating & Cooling Capacity class Cooling capacity Heating capacity Power input EER COP ESEER Dimensions Weight

Nom. Nom. Cooling Heating

Nom. Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Heating Air heat exchanger Type Nominal ESP unit Cooling Pump Hydraulic components Expansion vessel Volume Fan Air flow rate Cooling Nom. Heating Nom. Fan motor Speed Cooling Nom. Heating Nom. Steps Sound power level Cooling Nom. Heating Nom. Sound pressure Cooling Nom. level Heating Nom. Night quiet Cooling mode Heating Compressor Type Operation range Water side Cooling Min.~Max. Heating Min.~Max. Air side Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping Water inlet / outlet connections Water drain Power supply Phase / Frequency / Voltage

kW kW kW kW

005 5.2 5.65 1.89 1.97 2.75 2.87

006 6.0 6.35 2.35 2.24 2.55 2.83 805x1,190x360 100 104

mm kg kg

007 7.1 7.75 2.95 2.83 2.41 2.74

009 8.5 10.0 2.74 2.91 4.37 3.44 4.57

010 9.5 11.5 3.19 3.38 2.98 3.40 4.52 1,435x1,418x382 180 -

011 11.0 13.0 3.82 3.86 2.88 3.37 4.46

Brazed plate l l/min l/min kPa l m³/min m³/min rpm rpm dBA dBA dBA dBA dBA dBA °CDB °CDB °CDB °CDB

17.2 19.5 Tube type 45.1 6 -

14.9 17.5 49.4

62

1.01 27.2 33.0 Hi-XSS 58.0 54.6 10 96 100 90 780 760 8 64 64 51 51 45 42 Hermetically sealed scroll compressor 5~22 25~50 10~46 -15~35

20.4 23.5

24.4 28.7

38.3

63 -

48 48

50 49

Hermetically sealed swing compressor 5~20 25~50 10~43 -15~25 R-410A

kg

1.7

2.95 Electronic expansion valve 1 G 5/4" (female) -

1" MBSP Hose nipple 1/2" FBSP Hz / V

1~ / 50 / 230

38

31.5 37.3 49.1 97


EWYQ-ACW1

Air cooled heat pump mini chiller inverter EWYQ009ACW1

Digital controller

›› ›› ›› ›› ›› ›› ›› ››

Inverter technology ensures: continuous match of requested load, excellent part load efficiency (ESEER up to 4.68), significant reduction of starting currents, precise temperature control (evaporator leaving water) Low operating sound level Easy ‘plug and play’ installation Daikin scroll compressor Integrated hydronics Available options: evaporator heater type (OP10) and high ESP pump up to 90 kPa (OPHP) Three phase power supply and main switch included Wide operating range

Heating & Cooling Capacity class Cooling capacity Heating capacity Power input EER COP ESEER Dimensions Weight Water heat exchanger

Air heat exchanger Pump Hydraulic components Fan motor

Nom. Nom. Cooling Heating

Unit Unit Type Water volume Nominal water flow

Nom. Nom.

HeightxWidthxDepth

Cooling Heating

Type Nominal ESP unit Cooling Expansion vessel Volume Speed Cooling Nom. Heating Nom. Steps Sound power level Cooling Nom. Heating Nom. Sound pressure Cooling Nom. level Heating Nom. Night quiet Cooling mode Heating Compressor Type Operation range Water side Cooling Min.~Max. Heating Min.~Max. Air side Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Water inlet / outlet Power supply Phase / Frequency / Voltage

kW kW kW kW

009 9.0 11.0 2.96 3.23 3.04 3.41 4.68

011 11.0 12.5 3.82 3.70 2.88 3.38 4.63 1,435x1,418x382 180 Brazed plate 1.01 31.5 35.8 Hi-XSS 49.1 10 780 760 8

mm kg l l/min l/min kPa l rpm rpm

25.8 31.5 56.4

dBA dBA dBA dBA dBA dBA

64

013 13.2 14.0 5.10 4.19 2.59 3.34 4.52

37.8 40.1 40.9

66 64

51

52 51

45 42

46 43 Hermetically sealed scroll compressor 5~22 25~50 10~46 -15~35 R-410A 2.95 Electronic expansion valve 1 G 5/4" (female) 3N~ / 50 / 400

°CDB °CDB °CDB °CDB kg

inch Hz / V

39


EUWY(N-P-B)-KBZW1

Air cooled heat pump chiller EUWY*16KBZW1

μC² SE

›› ›› ›› ›› ›› ›› ›› ›› ››

››

Optimised for use with R-407C Daikin scroll compressor Reduced installation time thanks to integrated pump and/or buffer tank Possibility for a 200l buffer tank Low operating sound level Easy maintenance Main switch Water flow switch 3 different design options available: - EUWYN chiller without integrated hydraulic module; - EUWYP chiller with integrated hydraulic module (pump, expansion vessel, hydraulic components); - EUWYB chiller with integrated hydraulic module (buffer tank, pump, expansion vessel, hydraulic components) µC² SE DDC controller

Heating & Cooling Capacity class Cooling capacity Heating capacity Capacity steps Power input EER COP Dimensions Weight Water heat exchanger

Air heat exchanger Hydraulic components Fan group Fan group 2 Sound power level Compressor Operation range

Refrigerant

Refrigerant circuit Refrigerant circuit 2 Piping connections Power supply

N5

Nom. Nom. Cooling Heating

Nom. Nom.

HeightxWidthxDepth Unit Unit Operation weight Type Water volume Nominal water Cooling flow Heating Nominal water Cooling Filter pressure drop Heating Filter Type Expansion vessel Volume Air flow rate Cooling Nom. Air flow rate Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Heating Min.~Max. Air side Cooling Min.~Max. Heating Min.~Max. Type Control Circuits Quantity Charge Charge Water inlet / outlet Phase / Frequency / Voltage

kW kW % kW kW

mm kg kg l l/min l/min kPa kPa l m³/min m³/min dBA °CDB °CDB °CDB °CDB

kg kg inch Hz / V

P5 9,1 9.1 11.9 11,9

B5

N8

P8 17,1 17.1 18.5 18,5

B8

N10 P10 B10 N12 P12 B12 N16 P16 B16 N20 P20 B20 N24 P24 B24 21.0 21,0 25.0 25,0 34.2 34,2 40 50.0 50,0 24.0 24,0 27.0 27,0 37.0 37,0 46 54.0 54,0 0-100 0-50-100 3.77 3,77 7.38 7,38 8.49 8,49 11.3 11,3 14.8 14,8 16.2 16,2 22.6 22,6 4.56 4,56 7.01 7,01 8.98 8,98 10.7 10,7 14.10 14,10 17.3 17,3 21.4 21,4 2.41 2,41 2.32 2,32 2.47 2,47 2.21 2,21 2.3 2,3 2.5 2,5 2.2 2,2 2.61 2,61 2.64 2,64 2.67 2,67 2.52 2,52 2.62 2,62 2.66 2,66 2.52 2,52 1,230x1,290x734 1.230x1.290x734 1,450x1,290x734 1.450x1.290x734 1,321x2,580x734 1.321x2.580x734 1,541x2,580x734 1.541x2.580x734 163 181 193 227 241 253 258 272 284 258 272 284 455 473 485 516 534 546 516 534 546 165 184 252 230 244 312 261 275 343 261 275 343 461 482 550 522 544 612 522 544 612 Brazed plate 1.140 1,140 1.615 1,615 1.900 1,900 2.375 2,375 2.964 2,964 3.900 3,900 4.524 4,524 26 49 60 72 98 115 143 34 53 69 77 106 132 155 10 25 24 33 12 19 17 29 31 38 14 16 22 Cross fin coil/Hi-X tubes and PE coated waffle louvre fins 12 12 12 12 12 12 12 160 (per 2 fans) 170 (per 2 fans) 170 (per 2 fans) 67 76 78 79 81 Hermetically sealed scroll compressor -10(OPZL) ~ 20 35 ~ 50 -15 ~ 43 -10 ~ 21 R-407C Thermostatic expansion valve 1 2 4.6 4,6 4.7 4,7 5.4 5,4 5.1 5,1 5.4 5,4 5.6 5,6 5.1 5,1 5.4 5,4 5.6 5,6 G 1"1/4 (male) 2" male 3N~ / 50 / 400

40


EWYQ-BAWN/BAWP

Air cooled heat pump inverter chiller EWYQ-BA*

BRC21A52

›› ›› ›› ›› ›› ›› ››

High efficiency chiller with leader-of-class ESEER (up to 4.75) Minimal starting currents and short payback times No buffertank required for standard applications Naked or with factory mounted (standard/high-ESP) pump Low sound thanks to inverter compressor / fans EWYQ-BAWN: Naked EWYQ-BAWP: With pump

Heating & Cooling Capacity class Cooling capacity Heating capacity Capacity control Power input EER ESEER COP Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Heating Nominal water pressure drop Cooling Total Air heat exchanger Type Fan Air flow rate Cooling Nom. Heating Nom. Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Heating Min.~Max. Air side Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Water inlet / outlet Power supply Phase/Frequency/Voltage

kW kW % kW kW

016 16.8 16.8

5.57 5.51 3.01 4.75 3.05

mm kg kg

264 267

l l/min l/min kPa

48 48 20

m³/min m³/min dBA

021 21.0 21.0

025 25.2 25.2

7.25 7.09 2.90 4.65 2.96 1,684x1,371x774 317 320 1 60 60 30

171 171

185 185 78

°CDB °CDB °CDB °CDB kg

7.6

inch Hz/V

1-1/4”

41

032 040 050 31.5 42.0 50.4 31.5 42.0 50.4 Inverter controlled 25 9.25 12.9 14.9 19.0 8.87 10.5 14.2 17.8 2.72 2.44 2.82 2.65 4.45 4.00 4.60 4.40 2.84 3.00 2.96 2.83 1,684x1,684x774 1,684x2,358x780 397 571 401 577 Brazed plate 2 3 72 90 120 144 72 90 120 144 42 30 42 Hi-XSS 233 370 233 370 80 81 Hermetically sealed scroll compressor -10~20 25~50 -15~43 -15~35 R-410A 9.6 15.2 Electronic expansion valve 1 1-1/2" 3N~/50/400

064 63.0 63.0

26.7 21.0 2.36 3.95 3.00 1,684x2,980x780 730 738 5 181 181 30 466.0 466 83

19.2


EWYQ-DAYN

Air cooled heat pump chiller, multiple scroll EWYQ130-150DAYN

PCASO

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Optimised for use with R-410A refrigerant Multiple compressors per circuit Reliable and efficient scroll with high EER values High part load efficiency (ESEER) Anti-corrosion treated aluminium coils Low operating sound level Easy 'plug and play' installation Fans protected against abnormal operation (4 - 8 fans depending on unit size) Safety valves in each circuit Electronic circuit breakers Electronic expansion valve True dual plate brazed plate heat exchanger All hydronics can be accessed easily from 3 sides (no surrounding cabinet) Separate switchbox for easy access Compressors and controls at unit side Increased reliability via 2 independent refrigerant circuits (EWYQ130-250DAYN) Double circuit heat exchanger (from >100 kW) Non hermetic filter/dryer Daikin Pcaso controller with user friendly and powerful LCD interface

Heating & Cooling Capacity class Cooling capacity Heating capacity Capacity steps

Power input EER COP ESEER Dimensions Weight Water heat exchanger

Air heat exchanger Fan Sound power level Compressor Operation range

Refrigerant

Refrigerant circuit Refrigerant circuit 2 Piping connections Power supply

Nom. Nom.

Cooling Heating

kW kW %

Nom. Nom.

HeightxWidthxDepth Unit Unit Operation weight Type Nominal water Cooling flow Heating Nominal water Cooling Total pressure drop Heating Total Type Air flow rate Nom. Speed Cooling Nom. Type Water side Cooling Min.~Max. Water side Heating Min.~Max. Air side Cooling Min.~Max. Air side Heating Min.~Max. Type Control Circuits Quantity Charge Charge Water inlet / outlet Water drain Phase / Frequency / Voltage

kW kW

mm kg kg l/min l/min kPa kPa

080 77 87.7

100 100 114

130 136 149

180 210 183 211 199 225.00 21/290-25-50-75-100 43/50/570-25-50-75-100 71/79-100 47.6 55.7 63.8 75.3 49.6 58.8 68.0 77.0 2.86 2.60 2.87 2.80 3.00 2.81 2.93 2.92 4.31 4.07 4.33 4.23 2,311x2,000x2,631 2,311x2,000x3,081 1,550 1,600 1,850 1,900 1,567 1,619 1,875 1,927 Brazed plate, one per unit 390 416 525 605 427 473 570 645 43 38 41 44 51 49 48 50 Cross fin coil/Hi-Xss tubes and poly ethylene coated waffle fins 800 860 1,290 900 970 88 89 90 Scroll compressor -10 (OPZL) ~ 25 25 ~ 50 -15 ~ 43 -10 ~ 21 R-410A Electronic expansion valve 2 22 32 22 32 3" OD 1/2"G 3~ / 50 / 400

0-50-100 26.5 36.2 30.0 38.1 2.91 2.76 2.92 2.99 4.00 3.81 2,311x2,000x2,566 1,400 1,450 1,415 1,465 221 251

287 327 36

47

m³/min rpm dBA

46 780 880 86

°CDB °CDB °CDB °CDB

1 kg kg inch inch Hz / V

33

37 -

42

150 145 165

230 250 231 252 258 281 22/2844/50/560-25-50-75-100 72/78-100 82.2 93.5 84.2 96.6 2.81 2.70 3.06 2.91 4.20 4.00 2,311x2,000x4,850 3,200 3,300 3,239 3,342 662 740 39 48

722 806 38 46 1,600 900 91

39 39 3"


EWYD-BZSS

Air cooled heat pump inverter chiller, standard efficiency, standard sound EWYD250BZSS

PCO2

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Optimised for use with R-134a Cooling range: 254-583kW Heating range: 270-615kW EER range up to 2.83 Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Low starting current No gas boiler required Optimised defrost cycles Optimum ESEER values Partial heat recovery option available PID microprocessor control Power factor up to 0.95 2-3 truly independent refrigerant circuits Standard operation range down to -12 °C

Standard efficiency Standard sound

Heating & Cooling Capacity class Cooling capacity Heating capacity Capacity control Power input EER COP ESEER Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Heating Nominal water Cooling Heat exchanger pressure drop Heating Heat exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Heating Nom. Sound pressure level Cooling Nom. Heating Nom. Compressor Type Operation range Water side Cooling Min.~Max. Water side Heating Min.~Max. Air side Cooling Min.~Max. Air side Heating Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW % kW kW

mm kg kg l l/s l/s kPa kPa

250 254 270

270 273 297

290 292 324

90.3 100 109 90.4 99 107 2.81 2.74 2.69 2.98 2.99 3.03 4.05 4.04 4.01 2,335x2,254x3,547 3,410 3,455 3,500 3,550 3,595 3,640

320 324 333

138 13.03 14.18

13.94 15.49

37

42

48

53

42

49

58

55

100.5 100.5 82.1 82.1

94

410 413 443

440 436 463

460 457 475

510 505 530

161 164 2.83 2.90 4.31

178 176 2.83 3.02

100

mm Hz / V

43

520 522 558

580 583 615

186 184 2.81 3.04

215 205 2.71 3.00 4.05

9

5,015 5,255

4.13 2,335x2,254x6,583 5,495 5,735 5,724 5,964 5,953

240 21.83 22.68

24.11 25.33

24.92 26.65

218 27.87 29.39

229

58

53

57

46

51

61

50

53

65

60

57

65

52

57

66

55

60

71

High efficiency fin and tube type with integral subcooler 42,304 52,880 920 101.2 101.8 101.2 101.8 82.3 82.5 82.3 82.5 Semi-hermetic single screw compressor -8~15 35~55 -10~45 -12°C~20 R-134a 118 121 124 148 177 2 139.7 3~ / 50 / 400

31,728

88

380 382 410 Stepless

13 124 134 142 152 163 124 132 141 155 165 2.74 2.73 2.68 2.72 2.68 2.80 2.87 2.90 2.85 2.81 4.01 4.02 3.94 4.03 4.01 2,335x2,254x4,381 2,335x2,254x5,281 3,870 3,940 4,010 4,390 4,010 4,068 4,138 4,518 Single pass shell & tube 133 128 15.46 16.21 17.42 18.25 19.72 20.81 15.89 16.66 18.11 19.57 21.15 22.14

°CDB °CDB °CDB °CDB kg

370 365 379

116 117 2.79 2.84 4.07

12.12 12.89

l/s rpm dBA dBA dBA dBA

340 339 349

63,456 103.6 103.6 83.7 83.7

183

186 3 219.1


EWYD-BZSL

Air cooled heat pump inverter chiller, standard efficiency, low sound EWYD250BZSL

PCO2

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Optimised for use with R-134a Cooling range: 248-567kW Heating range: 270-615kW EER range up to 2.87 Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Low operating sound level Low starting current No gas boiler required Optimised defrost cycles Optimum ESEER values Partial heat recovery option available PID microprocessor control Power factor up to 0.95 2-3 truly independent refrigerant circuits Standard operation range down to -12°C

Standard efficiency Low sound

Heating & Cooling Capacity class Cooling capacity Heating capacity Capacity control Power input EER COP ESEER Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume Nominal water Cooling flow Heating Nominal water Cooling Heat exchanger pressure drop Heating Heat exchanger Air heat exchanger Type Fan Air flow rate Cooling Nom. Heating Nom. Fan motor Speed Cooling Nom. Heating Nom. Sound power level Cooling Nom. Heating Nom. Sound pressure Cooling Nom. level Heating Nom. Compressor Type Operation range Water side Cooling Min.~Max. Water side Heating Min.~Max. Air side Cooling Min.~Max. Air side Heating Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW % kW kW

mm kg kg l l/s l/s kPa kPa

250 248 270

270 266 297

290 291 324

88.5 98 109 90.4 99 107 2.80 2.70 2.66 2.98 2.99 3.03 4.18 4.16 4.11 2,335x2,254x3,547 3,750 3,795 3,840 3,888 3,933 3,978

320 316 333

138 12.70 14.18

13.89 15.49

36

40

48

51

42

49

58

55

94.0 94.9 75.6 76.5

94

400 403 443

430 425 463

450 448 475

156 164 2.87 2.90 4.31 5,525 5,765

100

mm Hz / V

44

490 493 530

510 510 558

570 567 615

9 174 183 214 176 184 205 2.83 2.79 2.65 3.02 3.04 3.00 4.29 4.23 4.10 2,335x2,254x6,583 6,005 6,245 6,234 6,474 6,463

240 21.39 22.68

23.56 25.33

24.34 26.65

218 27.11 29.39

229

55

50

55

44

48

59

48

51

62

60

57

65

52

57

66

55

60

71

High efficiency fin and tube type with integral subcooler 32,576 40,720 42,304 52,880 715 920 94.7 95.3 96.1 96.7 75.8 76.0 77.2 77.4 Semi-hermetic single screw compressor -8~15 35~55 -10~45 -12°C~20 R-134a 118 121 124 148 177 2 139.7 3 ~/ 50 / 400

24,432 31,728

88

370 372 410 Stepless

13 122 132 142 149 161 124 132 141 155 165 2.72 2.68 2.62 2.71 2.64 2.80 2.87 2.90 2.85 2.81 4.18 4.16 4.13 4.19 4.14 2,335x2,254x4,381 2,335x2,254x5,281 4,210 4,280 4,350 4,730 4,343 4,408 4,478 4,858 Single pass shell & tube 133 128 15.12 15.83 16.98 17.77 19.28 20.30 15.89 16.66 18.11 19.57 21.15 22.14

°CDB °CDB °CDB °CDB kg

360 355 379

113 117 2.79 2.84 4.29

11.83 12.89

l/s l/s rpm rpm dBA dBA dBA dBA

330 331 349

48,864 63,456

97.0 98.4 77.2 78.6

183

186 3 219.1


The Daikin condensing units can be used in a wide variety of air conditioning, refrigeration and ventilation applications.

condensing units ERQ VRV速-AHU ERAD-E-SS ERAD-E-SL

46 48 50 51

PIPING DIAGRAM FOR COMFORT COOLING APPLICATION

Air handling unit

Condensing Unit

1. Switchbox 2. Thermistor line

45


ERQ

›› ›› ›› ›› ›› ›› ›› ›› ››

Heat-pump condensing unit

Highly efficient cooling and heating solution for air handling applications Saves on installation costs – no water piping, freezing protection, chillers or boilers needed to satisfy the fresh air heating and cooling loads Daikin Inverter technology for step-less and efficient capacity control ensuring constant and comfortable supply air temperature Wide capacity regulation range – down to 18% nominal capacity on size 250 Wide operation range – in heating down to -20°C and in cooling up to +43°C ambient temperature Flexible choice of regulations, from plug&play Daikin regulation, to sophisticated external control Wide range of options, such as low noise mode or externally-controlled power input limiting R410A direct expansion system for connection to external air heat exchangers

Expansion valve kit EKEXV

ERQ

Air handling unit

Liquid pipe

Gas pipe

Expansion valve control Thermistors

Daikin communication

Control box EKEQDCB EKEQFCB

Controller (Daikin or External)

46


ERQ

Heat-pump condensing unit

Heat pump ERQ100AV1

OUTDOOR UNITS Nominal Capacity * EER COP Combinable expansion valves Operation range - outdoor ERQ-AV1

Operation range on-coil indoor Sound power level Sound pressure level

ERQ125AW1

Defrost method Dimensions

Weight Refrigerant Piping dimensions

ERQ200~250AW1

Piping length Power supply Recommended fuses

Cooling Heating

kW kW

EKEXV # Cooling Heating Cooling Heating Cooling Heating Cooling Heating

°CDB °CWB °C °C dBA dBA dBA dBA

Height Width Depth

mm mm mm kg

R410A Liquid (OD) mm Gas (OD) mm Maximum m A

Expansion valve kits Nominal heat exchanger capacity* Heat exchanger inner volume Dimensions

EKEXV

Weight Sound pressure level Piping connections

minimum maximum minimum maximum Height Width Depth

In (OD) Out (OD)

kW kW l l mm mm mm kg dBA mm mm

ERQ125AV1

EKEQFCB

Regulation range

Inputs & Outputs

Daikin Remote Controller Dimensions

Weight Power supply

BRC1D52 / BRC1E51A Height mm Width mm Depth mm kg

Options/Accessories Electromechanical cool/heat selector (switch) Fixing box for cool/heat selector Drain pan kit with central drain outlet Daikin Remote Controller Adaptor for ext. monitoring/control External room temperature sensor

KRC19-26 KJB111A KWC26B160 KWC26B280 BRC1D52 / BRC1E51A KRP4A51 KRCS01-1

ERQ125AW1

14 15.5 16 18 3.99 3.42 4.15 3.94 63 ~ 140 80 ~ 140 -5 ~ +46 -20 ~ +15,5 +14 WB ~ +25 WB / +35 DB +10 DB ~ 27 DB 66 67 69 – – – 50 51 53 52 53 55 Reverse cycle, electronically controlled 1.345 900 320 120 4 9.52 9.52 9.52 15.9 15.9 19.1 55 1~ / 230V / 50Hz 32

ERQ200AW1

ERQ250AW1

14 16 3.98 4 63 ~ 140

22.4 28 25 31.5 4.29 3.77 4.5 4.09 100 ~ 250 125 ~ 250 -5 ~ +43 -20 ~ +15 +14 WB ~ +25 WB / +35 DB +10 DB ~ 27 DB 72 78 78 – – – 54 57 58 – – – Reverse cycle, electronically controlled 1.68 1.68 1.68 635 930 930 765 765 765 159 187 240 6.2 7.7 8.4 9.52 9.52 9.52 15.9 19.1 22.2 55 3N~ / 400V / 50Hz 16 25 25

EKEXV63

EKEXV80

EKEXV100

EKEXV125

EKEXV140

EKEXV200

EKEXV250

6.3 7.8

7.9 9.9

10 12.3

12.4 15.4 1.66 8.25 457 270 120 2.9 45 9.52 9.52

15.5 17.6

17.7 24.6

24.7 30.8

EKEQDCB

EKEQFCB

Daikin control Room temperature control [via Remote Controller (accessory) or via External room temperature sensor (accessory)]

Free (External) control 0~10V direct capacity control (5V = maintain capacity, >5V colder air wanted, <5V warmer air wanted)

Return air temperature control (via a supplied thermistor) Setpoint 16 ~ 32°C via Daikin Remote Controller (accessory)

On / Off potential free input Fan Control potential free output (e.g. to stop AHU during hot-start and defrost)

Fixed evaporation / condensation temperature control 0~10V input from external controller Fixed evaporation temperature setting to 5 ~ 12°C Fixed condensation temperature setting to 43 ~ 49°C On / Off potential free input Fan Control potential free output (e.g. to stop AHU during hot-start and defrost)

Operation / Error output possible by accessory (KRP4A51)

Defrost potential free output (e.g. to stop AHU during hot-start and defrost)

CONTROL BOXES Control type Control options

ERQ140AV1

11.2 12.5 3.99 4.56 63 ~ 125

Compressor operation potential free output Error indication potential free output Required for end-user control (order separatelly) Required for commissioning & service (order separatelly) 132 400 200 3.6 3.9 1~ / 230V / 50Hz

ERQ-AV1

ERQ125AW1

ERQ200.250AW1

• •

• • •

• •

EKEQDCB

EKEQFCB

• • •

47


EKEQMCB VRV® air handling applications

›› Integrated air conditioning and air handling solution from one supplier ›› Connect any Air Handling Unit to any VRV® –– Even geothermal-sourced VRV® WIII possible ›› Efficiency of DX system both for cooling and for heating ›› Unique application for Daikin VRV® III Heat Recovery with continuous heating during defrost EKEXV-kit

EKEQMCB

gas pipe liquid pipe F1-F2 other communication

CONTROL BOXES

EKEQMCB

Control type Control options

Daikin control Room temperature control [via Remote Controller (accessory) or via External room temperature sensor (accessory)] Return air temperature control (via a supplied thermistor) Setpoint 16 ~ 32°C via Daikin Remote Controller (accessory) On / Off potential free input Fan Control potential free output (e.g. to stop AHU during defrost) Operation / Error output possible by accessory (KRP4A51)

Regulation range Inputs & Outputs

Daikin Remote Controller Dimensions

BRC1D52 BRC1E51A Height Width Depth

Weight Power supply

Expansion Valve Kits Allowed heat Cooling exchanger (evaporation capacity temp. 6°C) Heating (condensing temp. 46°C) Dimensions Weight Sound pressure level Operation range

Unit Unit Nom. Cooling Heating Operation range - Cooling on coil temperature Heating Refrigerant Type Piping Liquid connections Gas 1 2

Required for end-user control (order separatelly) 132 400 200 3.6 1~ / 230V / 50Hz

mm mm mm kg

Minimum Standard Maximum Minimum Standard Maximum HeightxWidthxDepth

Min./Max. Min./Max. Max. Min.

kW kW kW kW kW kW mm kg dBA °CDB °CWB °CDB °CDB

OD OD

mm mm

EKEXV50 5.0 5.6 6.2 5.6 6.3 7.0

EKEXV63 6.3 7.1 7.8 7.1 8.0 8.8

EKEXV80 7.9 9.0 9.9 8.9 10.0 11.1

6.35 6.35

45% relative humidity The temperature of the air entering the coil in heating mode can be reduced to -5°CDB. Contact your local dealer for more information

48

EKEXV100 EKEXV125 10.0 12.4 11.2 14.0 12.3 15.4 11.2 13.9 12.5 16.0 13.8 17.3 401x215x78 2.9 45 -5.0/46.0 -/351 102 R-410A 9.52 9.52

EKEXV140 15.5 16.0 17.6 17.4 18.0 19.8

EKEXV200 17.7 22.4 24.6 19.9 25.0 27.7

EKEXV250 24.7 28.0 30.8 27.8 31.5 34.7



ERAD-E-SS

Air cooled condensing unit, standard efficiency, standard sound ERAD170,200E-SS

MicroTech III

›› ›› ›› ›› ›› ››

Wide capacity range (121 kW - 488 kW) Single refrigerant circuit with steppless single screw compressor Compact design Large operation range (ambient temperature down to -18°C) Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Air heat exchanger Type Fan Air flow rate Nom. Fan motor Speed Cooling Nom. Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Saturated suction temp. Min-Max Condenser Min-Max Refrigerant Type Charge Circuits Quantity Power supply Phase / Frequency / Voltage

kW % kW mm kg kg l/s rpm dBA dBA

120 121

140 144

170 165

220 219

250 252

310 306

370 370

440 435

490 488

Stepless 25 41.8 51.0 2.90 2.83 2,273x1,292x2,165 1,584 1,617 10,922

10,575 91.5

57.4 65.2 73.7 76.6 92.8 122.0 147.2 160.8 2.87 3.00 2.97 3.28 3.30 3.04 2.96 3.03 2,273x1,292x3,065 2,273x1,292x3,965 2,223x2,236x3,070 1,741 1,936 2,679 1,781 1,981 2,756 High efficiency fin and tube type with integral subcooler 16,383 15,863 21,844 21,150 32,767 31,725 920 92.3 93.0 94.2 94.5 95.2

73.5

73.7

°C °C kg

200 196

17

20

22

Hz / V

50

73.9

75.1

75.0

Semi-hermetic single screw compressor -9~12 -18~48 R-134a 27 29 32 1 3~ / 50 / 400

75.3

45

76.0

54

58


ERAD-E-SL

Air cooled condensing unit, standard efficiency, low sound ERAD160,190E-SL

MicroTech III

›› ›› ›› ›› ›› ›› ››

Low operating sound level Wide capacity range (116 kW - 462 kW) Single refrigerant circuit with steppless single screw compressor Compact design Large operation range (ambient temperature down to -18°C) Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Low sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Air heat exchanger Type Fan Air flow rate Nom. Fan motor Speed Cooling Nom. Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Saturated suction temp. Min-Max Condenser Min-Max Refrigerant Type Charge Circuits Quantity Power supply Phase / Frequency / Voltage

kW % kW mm kg kg l/s rpm dBA dBA

120 116

140 137

160 159

210 209

240 243

300 295

350 352

410 409

460 462

Stepless 25 42.3 52.5 2.74 2.61 2,273x1,292x2,165 1,684 1,717 8,372

8,144 89.0

57.6 66.3 73.9 78.2 91.5 122 150 167 2.75 2.82 2.83 3.11 3.23 2.88 2.73 2.76 2,273x1,292x3,065 2,273x1,292x3,965 2,223x2,236x3,070 1,841 2,036 2,789 1,881 2,081 2,886 High efficiency fin and tube type with integral subcooler 12,558 12,217 16,744 16,289 25,117 24,433 715 89.8 90.5 91.7 92.0 92.7

71.0

71.2

°C °C kg

190 187

17

20

22

Hz / V

51

71.4

72.6

72.5

Semi-hermetic single screw compressor -9~12 -18~48 R-134a 27 29 32 1 3~ / 50 / 400

72.8

45

73.5

54

58


1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13.

Balancing valve Pressure gauge Temperature sensor Drain valve Shut-off valve Charging valve Filter Air purge Safety valve Pressure port Pump Flow switch Bypass valve

water cooled chiller 3 12

2

9

10

8

3

Chillers

Buffer tank

5

Expansion vessel

5

7

Buffer tank

Condenser

6 4

Evaporator

5

11

1

To fan coil units or thermal load

4 6

Expansion vessel

3

11 8

9

13

10

5

7

5

3 12

52

3

1 2

To fan coil units or thermal load

5


Daikin offers you compact water-cooled chiller units which require only very limited space in a machine room. Used for commercial or industrial applications, these chillers generate cold and hot water, which can be used for chilling, heating, or even both at the same time.

water-cooled chillers NEW

NEW NEW NEW

EWWP-KBW1N EWWD-J-SS EWWD-G-SS EWWD-G-XS EWWD-I-SS EWWD-I-XS EWWD-H-XS EWWQ-B-SS EWWQ-B-XS EWWD-FZXS DWSC, DWDC

54 56 58 59 60 61 62 64 65 66 68

53


EWWP-KBW1N

Water cooled chiller EWWP014-035KBW1N

μC² SE

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Standard integrated: main switch, water filter, flow switch, air purge, pressure ports Daikin scroll compressor Optimised for use with R-407C Low operating sound level Low energy consumption Extension possible up to 195kW Compact dimensions and low refrigerant volume Easy installation and maintenance Stainless steel plate heat exchanger Remote cooling or heating selection Water/water heat pump, with water reversibility Compatible with hydraulic module EHMC µC² SE DDC controller pCO3 DDC controller for assembly of 2 or 3 modules

Heating only & Cooling only Capacity class Cooling capacity Nom. Heating capacity Nom. Capacity steps number Power input Cooling Nom. EER HeightxWidthxDepth Dimensions Unit Weight Unit Water heat Type exchanger Minimum water volume in the system evaporator Water flow rate Min. Nom. Max. Water heat Type exchanger Water flow rate Min. condenser Nom. Max. Sound power level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Evaporator water drain Condenser water inlet/outlet Condenser water drain Power supply Phase / Frequency / Voltage

kW kW

014 13.0 16.6

022 21.5 27.3

028 28.0 35.4

035 32.5 41.2

mm kg

1 5.79 7.48 8.75 3.71 3.74 3.71 600x600x600 118 155 165 172

l l/min l/min l/min

62 19 37 75

103 31 62 123

134 40 80 161

155 47 93 186

l/min l/min l/min dBA

24 48 95

39 78 157 64

51 102 203

59 118 237 71

kW

3.61 3.60

°CDB °CDB

kg mm mm Hz / V

1.2

1 2 2.5 FBSP 25 FBSP 25

3.1

045 43.0 54.8

055 065 56.0 65.0 71.4 82.7 2 11.80 15.50 17.60 3.64 3.61 3.69 600x600x1,200 300 320 334

110 120 130 112 121 130 143 154 165 4 23.6 27.3 31.0 33.1 35.2 3.64 3.63 3.61 3.66 3.69 1,200x600x1,200 600 620 640 654 668 Brazed plate 205 268 311 205 268 311 62 80 93 123 142 161 173 186 123 161 186 247 284 321 347 373 247 321 373 493 568 642 694 745 Brazed plate 79 102 118 157 181 205 221 237 157 205 237 314 362 410 442 474 314 410 474 629 724 819 883 948 67 74 71 75 77 Hermetically sealed scroll compressor -10 (OPZL) ~ 25 20 ~ 55 R-407C Thermostatic expansion valve 2 4 4.6 5.6 9.2 10.2 11.2 FBSP 40 2 x 2 x FBSP 38 Field installation FBSP 40 2 x 2 x FBSP 38 Field installation 3N~ / 50 / 400

54

090 86.0 110

100 99.0 126

145 142 181

155 155 198

39.1 3.63

42.8 3.62

920

165 168 214

175 177 226

185 186 237

6 46.5 48.6 50.7 3.61 3.64 3.67 1,800x600x1,200 940 960 974 988

205 204 222 407 444 814 889

195 195 248 52.8 3.69 1.002

268 311 254 267 280 507 533 559 1,015 1,066 1,118

241 482 963

260 283 307 323 339 355 519 567 614 647 679 711 1,038 1,133 1,229 1,293 1,357 1,422 73 76 78 79

6 13.8

14.8 15.8 3 x 2 x FBSP 38 3 x 2 x FBSP 38

16.8


EWWP-KBW1N

Water cooled chiller

EWWP014-035KBW1N

EWWP090-130KBW1N

EWWP145-195KBW1N

1 MODULE (KB-SERIES)

SELECTION TABLE

2 MODULES (KB-SERIES)

3 MODULES (KB-SERIES)

Capacity index

014

022

028

035

045

055

065

090

100

110

120

130

145

155

165

175

185

195

Cooling capacity (kW)

13.0

21.5

28.0

32.5

43.0

56.0

65.0

86.0

99.0

112

121

130

142

155

168

177

186

195

16.6

27.3

35.4

41.2

54.8

71.4

82.7

110

126

143

154

165

181

198

214

226

237

248

1 -

1 -

1 -

1 -

1 -

1 -

1 -

2 1 -

1 1 1 -

2 1 -

1 1 1 -

2 1 -

2 1 1

1 2 1

3 1

2 1 1

1 2 1

3 1

Heating capacity (kW)

UNIT + CONTROL (Factory mounted)

MODULAR UNITS (Controller available as accessory) CONTROL (kit) For example:

EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB2MUW ECB3MUW

for a 121 kW HP system, select : EWWP055KBW1N + EWWP065KBW1N

55


EWWD-J-SS

Water cooled chiller, standard efficiency, standard sound EWWD-J-

MicroTech III

›› ›› ›› ›› ›› ››

Compact design to allow easy indoor installation or retrofit operations Stepless single screw compressor High efficiency at full and partial load Chilled water temperatures down to -10°C on standard unit Optimised for use with R-134a MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Heating only & Cooling only Capacity class Cooling capacity Heating capacity Capacity control Power input EER ESEER COP Dimensions Weight Water heat exchanger Water heat exchanger evaporator Water heat exchanger condenser Sound power level Sound pressure level Compressor Operation range Refrigerant

Piping connections Power supply

120 120 142

140 146 172

150 155 188

180 178 216

210 208 249

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

kW kW

HeightxWidthxDepth Unit Unit Operation weight Type Water volume Nominal water pressure drop Cooling Heat exchanger Type Water flow rate Nom. Nominal water pressure drop Cooling Cooling Nom. Cooling Nom. Type Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Condenser water inlet/outlet Phase/Frequency/Voltage

mm kg kg

1,177 1,211

l kPa

14 15

18 13

14 40

17 38

20 36

l/s kPa dBA dBA

7.04 20

8.57 12

9.25

10.62 11

12.30

% kW kW

27.3 32.9 4.40 5.01 4.32

25 33.3 38.5 44.2 49.3 59.57 40.1 46.4 53.5 4.38 4.03 4.22 4.67 4.66 4.75 4.29 4.05 4.04 4.18 1,020x913x2,684 1,233 1,334 1,366 1,416 1,276 1,378 1,415 1,473

88.6 71.4

°CDB °CDB kg

18

mm inch Hz/V

2.5

20

33

34 1

36

250 256 305

280 285 340

310 330 310 334 377 405 Stepless

58.7 71.68 4.37 5.20 4.26

68.3 80.75 4.18 4.46 4.21

77 92.88 4.03 4.80 4.06

82.7 88.4 99.9 107 4.04 4.84 5.00 4.05 4.04

1,600 1,663

380 386 466

4 3~/50/400

400 416 499

450 464 554

12.5 98.6 108 113 119 131 3.91 4.22 4.30 4.79 5.17 5.27 4.12 4.19 4.22 2,000x913x2,684 2,782 2,832 3,016 2,888 2,946 3,136

1,607 2,668 2,700 2,732 1,675 2,755 2,792 2,830 Brazed plate, one per circuit 26 29 31 33 37 28 33 40 38 Double pass shell and tube 15.06 16.89 18.49 19.91 21.28 23.15 16 26 11 87.2 92.4 70.0 74.4 Semi-hermetic single screw compressor -10~15 23~60 R-134a 38 66 67 68 70 76.2

56

360 357 432

41

500 513 610

530 541 645

560 570 681

117 143 4.38 5.37 4.26

127 152 4.26 5.25 4.23

137 162 4.16 4.81 4.22

3,200 3,327

3,207 3,338

3,215 3,350

46

52

36 24.59

28 27.33

30.10

33 31.92

16

72 2

91.8 73.8

91.0 73.0

74

76

33.78 26



EWWD-G-SS

Water cooled chiller EWWD-G-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

High efficiency (XS) All models are PED pressure vessel approved Stepless single-screw compressor Optimised for use with R-134a EER range up to 4 (SS) , 4.73 (XS) 1-2 truly independent refrigerant circuits Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Heating only & Cooling only Capacity class Cooling capacity Heating capacity Capacity control Power input EER COP ESEER Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume evaporator Nominal water Cooling Total pressure drop Water heat Type exchanger Water flow rate Nom. condenser Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping Evaporator water inlet/outlet connections Condenser water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW

170 166 204

210 201 247

260 253 310

300 280 343

320 334 410

380 372 456

420 403 494

460 448 552

500 494 610

600 556 674

129 161 3.83 3.79 5.1

150 177 3.70 3.81 4.93

Stepless % kW kW

mm kg kg l kPa

l/s kPa

25 42.2 52.7 3.93 3.87 5.00

50.6 64.9 75.3 63.5 80.8 89.2 3.97 3.90 3.72 3.89 3.84 5.04 4.95 4.72 1,860x920x3,435 1,410 1,503 1,480 1,650

1,393 1,470 60

56

48

69

123 43

53

9.95

12.02

15.19

16.98

39

41

63

77

dBA dBA

93 117 4.00 3.91 5.33

2,687 2,697 2,840 2,850 Single pass shell and tube 118 113 64

63

168 54

24.08

41

68

26.90

29.77

33.73

57

60

75

90.2

69.7

71.7

50

55

Semi-hermetic single screw compressor -8~15 20~55 R-134a 110 50 Electronic expansion valve

1 mm inch Hz / V

2,762 2,970

173 72

Single pass shell and tube 19.99 22.22 40

12.5 101 115 127 144 3.97 3.89 3.89 3.84 5.29 5.19 1,880x860x4,305 2,702 2,757 2,860

87.7

°CDB °CDB kg

84.3 106 3.96 3.88 5.28

55

110

2

88.9

114.3 5 3~ / 50 / 400

58

139.7


EWWD-G-XS

High efficiency Standard sound

Heating only & Cooling only Capacity class Cooling capacity Heating capacity Capacity control Power input EER COP ESEER Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume evaporator Nominal water Cooling Total pressure drop Water heat Type exchanger Water flow rate Nom. condenser Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping Evaporator water inlet/outlet connections Condenser water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW

190 186 220

230 223 264

280 277 326

320 307 354

380 366 434

400 408 482

460 444 524

87.2 110 4.68

95.1 120 4.67

500 496 585

550 541 638

650 604 712

115 144 4.72 4.43 6.30

137 162 4.39 4.40 5.85

Stepless % kW kW

mm kg kg l kPa

l/s kPa dBA dBA

25 39.6 50.1 4.70 4.38 5.97 1,650 1,800 125

12.5

48.1 59.4 60.6 74.5 4.64 4.66 4.35 4.38 5.9 5.92 1,860x920x3,435 1,665 1,680 1,810 1,820 120

25

110 35

44

10.78

12.95

16.07

18.08

17

20

25

28

mm inch Hz / V

79.2 99.9 4.62 4.34 6.15

105 132 4.73 4.38 4.42 6.24 6.23 6.31 1,880x860x4,305 2,800 2,945 2,955 2,975 3,020 3,280 3,290 3,315 Single pass shell and tube 170 285 30

24

Single pass shell and tube 21.27 23.66

2,990 3,340 280

28

39

46

57

25.76

28.71

31.34

35.40

16

15

19

17

88.2

90.9

69.7

71.7 Semi-hermetic single screw compressor -8~15 20~55 R-134a 110 105 Electronic expansion valve

째CDB 째CDB kg

71.4 83.7 4.30 4.23 5.46

55 1 114.3

100 2

139.7 5 3~ / 50 / 400

59

168.3


EWWD-I-SS

Water cooled chiller EWWD-I-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

High efficiency (XS) All models are PED pressure vessel approved Stepless single-screw compressor Optimised for use with R-134a Cooling range: 333–1,510kW (SS) , 362-1.134kW (XS) EER range: 4.28 to 4.66 (SS) , 4.73 to 5.10 (XS) 1-2-3 truly independent refrigerant circuits Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Partial and total heat recovery option available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Heating only & Cooling only Capacity class Cooling capacity Heating capacity Capacity control Power input EER COP ESEER Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume evaporator Nominal water Cooling Heat exchanger pressure drop Water heat Type exchanger Water flow rate Nom. condenser Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Evaporator water inlet/outlet Piping connections Condenser water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW % kW kW

mm kg kg l kPa

l/s kPa dBA dBA

340 333 388.4

900 950 C10 C12 C13 C14 C15 C16 C17 910 986 1,027 1,155 1,204 1,274 1,346 1,401 1,455 1,072 1,161 1,217 1,363 1,427 1,507 1,227 1,661 1,730 Stepless 25 12.5 8.3 71.5 85.8 101 120 141 156 171 186 200 218 237 254 268 282 298 317 335 87.4 104 122 143 174 191 208 225 243 262 282 309 326 344 363 383 401 4.66 4.59 4.56 4.47 4.53 4.52 4.57 4.55 4.51 4.33 4.54 4.50 4.51 4.43 4.35 4.44 4.42 4.41 4.35 4.36 4.42 4.41 4.43 4.32 4.41 4.38 3.38 4.34 4.31 5.06 4.96 4.93 4.86 5.54 5.75 5.56 5.7 5.47 5.61 5.36 5.51 5.56 5.54 5.55 5.45 1,821x1,430x3,398 2,113x1,350x4,361 2,323x2,135x4,426 2,150 2,160 2,179 2,224 3,909 3,927 3,945 3,971 3,996 4,080 4,092 6,079 6,097 6,136 6,174 6,192 6,210 2,380 2,396 2,410 2,457 4,217 4,228 4,243 4,262 4,288 4,369 4,386 6,628 6,646 6,670 6,699 6,717 6,735 Single pass shell and tube 193 183 172 271 263 256 248 241 233 472 504 489 472 37

400 394 460

50

460 460 538

550 538 630

54

650 640 757

62

700 705 832

55

44

850 844 993

58

53

66

51

62

56

47

58

62

66

C18 1,510 1,790

353 420 4.28 4.26 5.27 6,228 6,761

71

Single pass shell and tube 19.33 22.92 26.80 31.44 37.31 41.14 45.53 49.21 53.03 57.52 60.39 67.32 70.33 74.34 78.55 82.08 85.52 89.01 26

28

93.7

96.6

30 96.7

26 96.9

25 97.3

97.8

28 98.9

99.8

100.4 100.8 101.2

103.0

75.2

76.2

78.2

77.8

78.2

78.7

79.8

80.7

80.4

80.8

81.2

83.0

Semi-hermetic single screw compressor -8~15 20~55 R-134a Electronic expansion valve 2 104 100 156

155

154

°CDB °CDB

1 kg mm inch Hz / V

800 782 919

54

52

51

50

108

106 168.3

26

23

5 3~ / 50 / 400

60

24

25

24

3 153 219.1

23

152

151

150


EWWD-I-XS

High efficiency Standard sound

Heating only & Cooling only Capacity class Cooling capacity Heating capacity Capacity control Power input EER COP ESEER Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Water volume evaporator Nominal water Cooling Heat exchanger pressure drop Water heat Type exchanger Water flow rate Nom. condenser Water flow Nom. rate 2 Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping Evaporator water inlet/outlet connections Condenser water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW % kW kW

mm kg kg l kPa

l/s l/min kPa dBA dBA

360 362 410.9

71 85.9 5.10 4.78 5.34 2,594 2,998

440 433 493

600 573 660

25 85.4 100 103 121 5.07 5.06 4.79 4.77 5.27 5.22 1,883x1,430x4,081 2,667 2,704 3,078 3,116

326

317

64

48

20.69

500 506 577

121 143 4.75 4.62 5.11

308 54

24.77

750 720 823

28.95

33.16

156 189 5.10 4.80 6.31

48

48

47 96.6

51 96.7

75.20

76.2

78.2

C10 976 1,126

47

C11 1,038 1,203

C12 1,134 1,313

219 263

240 285 4.73

4.57 6.05

504

50

72

46

52

23.31

28.07

27.10

32.82

28

28.07

33

32.82

24.75

96.9

97.3

97.8

98.9

99.8

77.8

78.2

78.7

79.8

80.7

2 172 219.1

170

48

47

50

65

Semi-hermetic single screw compressor -8~15 20~55 R-134a Electronic expansion valve 1 90

87

85

180

177

168.3 5 3~ / 50 / 400

61

174

4.61 5.67 5,132 5,741

24.98

66

째CDB 째CDB

kg mm inch Hz / V

950 933 1,069

170 206 5.08 4.81 6.01

Single pass shell and tube 20.58 20.44 24.75 20.58

93.7

850 866 990

12.5 185 199 223 240 5.05 4.9 4.79 4.69 6.14 5.9 2,245x1,350x4,769 4,964 4,997 5,049 5,073 5,097 5,582 5,615 5,671 5,695 5,729 Single pass shell and tube 539 528 141 172 5.09 4.78 6.13

68

-

800 795 908 Stepless


EWWD-H-XS

Water cooled chiller, high efficiency, standard sound EWWD-H-

MicroTech III

›› ›› ›› ›› ››

Cooling range: 369-1,215 kW Condenser leaving water temperatures (CLWT) up to 65°C (optional) Heat pump version available Flooded type heat exchangers MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

High efficiency Standard sound

Heating only & Cooling only Capacity class Cooling capacity Heating capacity Capacity control Power input EER ESEER COP Dimensions Weight

Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Water heat Type exchanger Water volume evaporator Nominal water pressure drop Cooling Heat exchanger Water heat Type exchanger Water flow rate Nom. condenser Nominal water pressure drop Cooling Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping Evaporator water inlet/outlet connections Condenser water inlet/outlet Power supply Phase/Frequency/Voltage

kW kW % kW kW

mm

370 369 419

450 445 505

62.8 84.5 5.88 6.44 4.96

75.4 101 5.90 6.47 4.98

530 521 589

610 608 687

2,121x1,353x3,341

87.0 101 117 136 5.99 6.02 6.56 6.57 5.03 5.06 2,121x1,353 2,048x1,384 x3,419 x3,417 3,603 3,781 3,870 4,163

3,089 3,250

3,370 3,588

l kPa

78 48

107 40

134 38

160 42

l/s kPa dBA dBA

20.63 35 96.7 78.0

24.86 30 97.7 79.0

29.05 32 98.7

33.87 28 99.1

210

190

180

80.0

°CDB °CDB

mm inch Hz/V

830 827 924 Stepless

930 932 1,036

980 978 1,093

125 159 5.98 7.16 5.28

138 175 5.99 7.23 5.27

151 192 6.17 7.32 5.40

12.5 163 206 6.00 7.37 5.30

25

kg kg

kg

750 748 837

168.3 6

62

210

2,048x1,689x3,609

C10 1,050 1,173

C11 1,133 1,265

C12 1,215 1,356

174 221

188 238

201 255 6.04 7.42 5.31

6.03 7.40 5.31

2,048x1,711x3,609

5,289 5,375 5,654 5,694 5,835 6,174 Flooded shell and tube 172 201 261 48 40 38 Flooded Shell & Tube 41.71 46.11 51.74 34 30 37 100.2 100.7 101.2 81.0 81.5 82.0 Semi-hermetic single screw compressor -8~15 18~65 R-134a 220 250 1 219.1 8 3~/50/400

7.43 5.32 2,161x1,711x3,509

5,707 6,262 272

6,066 6,709

6,105 6,773

6,156 6,859

295

310 37.0

327 40

63.12

67.65 35

35.0 54.52 35.0 101.7 82.5

300

58.48 33.0 102.2 83.0

102.7 83.5

330



EWWQ-B-SS

Water cooled chiller, standard efficiency, standard sound EWWQ-B-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ››

All models are PED pressure vessel approved 1 or 2 stepless single-screw compressors 1 or 2 truly independent refrigerant circuits Shell and tube heat exchanger Optimised for use with R-410A Standard electronic expansion valve Compact design Partial heat recovery available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight Water heat exchanger evaporator Water heat exchanger condenser Sound power level Sound pressure level Compressor Operation range Refrigerant

Refrigerant circuit Refrigerant circuit 2 Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Type Water volume Nominal water pressure drop Cooling Heat exchanger Type Water flow rate Nom. Nominal water pressure drop Cooling Nominal water pressure drop 2 Cooling Cooling Nom. Cooling Nom. Type Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Type Control Circuits Quantity Charge Charge Evaporator water inlet/outlet Condenser water inlet/outlet Phase/Frequency/Voltage

kW % kW

mm kg kg

380 380

460 464

560 562

640 637

800 796

25 85.6 104 128 144 166 172 4.44 4.46 4.40 4.41 4.37 4.64 5.16 5.21 5.22 4.95 5.64 1,849x1,140 2,001x1,276 1,848x1,314 2,158x1,350 x3,535 x5,020 x3,373 x3,454 1,933 1,967 2,283 2,332 2,407 3,921 2,135 2,169 2,543 2,628 2,777 4,422

l kPa

124 47

118 63

176 43

l/s kPa kPa dBA dBA

22.2 58

27.2 62

32.9 37.3 66 63 102.3 83.9

100.2 101.2 82.2 83.0

170 46

°CDB °CDB

1 kg kg mm inch Hz/V

730 727

80

90 -

152.4 5

6

860 862

870 872

960 C10 960 1,007 Stepless

C11 1,055

C12 1,185

C13 1,255

C14 1,325

12.5 190 209 240 232 256 274 290 4.59 4.60 4.19 4.55 4.62 4.59 4.56 5.63 5.59 4.76 5.6 5.61 5.62 5.55 2,158x1,350 1,848x1,314 2,378x1,350 2,455x1,350x5,070 x5,020 x2,001 x4,894 3,949 3,988 2,457 4,344 4,529 4,536 4,607 4,463 4,496 2,812 4,780 5,186 5,200 5,280 Shell and tube 274 344 266 344 325 251 325 538 53 52 48 62 57 55 67 43 48 53 Shell and tube 42.7 23.1 50.9 23.4 27.9 59.6 27.6 34.3 33.4 38.4 15 62 19 62 65 25 65 70 67 62 65 67 70 67 101.5 104.7 102.3 104.7 105.1 103.2 104.7 105.2 106.5 83.2 84 84.9 85.2 85 85.6 86 86.5 86.9 Semi-hermetic single screw compressor -4~10 25~45 R-410A 2 1 2 80 90 85 100 95 100 80 90 85 100 95 100 203.2 5 3~/50/400

64

202 4.26 4.83 1,848x1,314 x2,001 2,427 2,795

C15 1,460

C17 1,748

C19 1,888

C20 2,050

333 401 432 466 4.38 4.36 4.37 4.40 5.18 5.06 5.11 5.07 2,495x1,350 2,495x1,350 x4,892 x4,865 4,988 5,053 5,204 5,289 5,602 5,670 5,881 5,970 505 58

495 86

539 95

527 119

42.6

51 16

50.8

59.8 14

16 14 105.8 106.6 107.1 107.5 86.2 87.0 87.5 87.9

130 130


EWWQ-B-XS

Water cooled chiller, high efficiency, standard sound EWWQ-B-

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

High efficiency All models are PED pressure vessel approved 1 or 2 stepless single-screw compressors 1 or 2 truly independent refrigerant circuits Shell and tube heat exchanger Optimised for use with R-410A Standard electronic expansion valve Compact design Partial heat recovery available MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

High efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight Water heat exchanger evaporator Water heat exchanger condenser Sound power level Sound pressure level Compressor Operation range Refrigerant

Refrigerant circuit Refrigerant circuit 2 Piping connections Power supply

Nom. Method Minimum capacity Cooling Nom.

Unit

HeightxWidthxDepth

Unit Operation weight Type Water volume Nominal water pressure drop Cooling Heat exchanger Type Water flow rate Nom. Nominal water pressure drop Cooling Nominal water pressure drop 2 Cooling Cooling Nom. Cooling Nom. Type Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Type Control Circuits Quantity Charge Charge Evaporator water inlet/outlet Condenser water inlet/outlet Phase/Frequency/Voltage

kW % kW

mm kg kg l kPa l/s kPa kPa dBA dBA °CDB °CDB

kg kg mm inch Hz/V

420 422

520 516

640 639

730 725

800 801

970 973

25

C10 1,037

C12 C13 1,158 1,270 Stepless

C14 1,369

C15 1,449

C16 1,573

C17 1,733

C19 1,863

C20 2,020

C21 2,152

25 12.5 227 228 252 269 286 315 349 382 417 451 4.91 5.07 5.04 5.08 5.07 4.99 4.96 4.87 4.84 4.77 5.54 6.13 6.28 6.23 5.92 6 5.73 5.78 5.64 2,495x1,350 2,003x1,446 2,454x1,350x5,219 2,495x1,350x4,829 x4,865 x3,919 2,457 4,831 4,873 4,919 4,969 5,117 5,388 5,408 5,414 3,086 5,479 5,512 5,546 5,606 5,794 5,843 6,110 6,118 6,124 Shell and tube 220 213 200 334 325 538 587 538 575 563 551 495 484 535 527 57 70 73 65 58 55 70 65 56 68 76 71 91 93 115 129 Shell and tube 24.2 29.5 36.5 41.4 45.8 55.7 29.5 64.2 29.6 36.3 36.7 41.2 44.9 44.6 53.3 53.2 61.9 50 40 41 46 60 64 39 84 35 48 49 46 43 60 52 78 39 48 46 43 62 60 79 78 100.9 101.7 102.6 102.7 102.0 102.9 105.2 103.8 105.6 106.1 106.5 105.8 106.2 106.6 107.1 107.5 82.2 83.0 83.9 83.2 84.0 85.6 84.9 86.0 86.5 86.9 86.2 86.6 87.0 87.5 87.9 Semi-hermetic single screw compressor -4~10 25~45 R-410A 1 2 1 2 95 110 130 120 130 120 130 120 120 130 152.2 203.2 254 203.2 254 203.2 254 8 6 5 6 5 6 8 3~/50/400 84.9 4.97 5.86

102 5.03 5.88

126 5.09 5.97

143 5.07 5.95 2,001x1,268 2,001x1,276x3,863 x3,878 2,322 2,403 2,464 2,738 2,594 2,685 2,745 3,158

159 193 5.05 5.89 5.66 2,003x1,314 2,003x1,446 x3,878 x3,919 2,407 2,427 2,815 3,056

65

12.5 205 5.06 6.18 2,454x1,350 x5,219 4,775 5,431

C11 1,116


EWWD-FZXS

Water cooled chiller with centrifugal compressor high efficiency, standard sound EWWD640-C10FZXS

pCO2

›› ›› ›› ›› ››

Oil free compressor technology with magentic bearing Wide capacity range from 114 to 1,048 kW An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures Top seasonal efficiency (ESEER up to 9.60) Onboard digital electronics provide smart controls

High efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight

Min. Max. Method Cooling Cooling

Min. Max.

HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Nominal water Cooling Heat evaporator exchanger pressure drop Water heat Type exchanger Water flow rate Nom. condenser Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping Evaporator water inlet/outlet connections Condenser water inlet/outlet Power supply Phase / Frequency / Voltage

kW kW

320 114 317

430 128 429

kW kW

21.6 65.9

27.7 85.7

mm kg kg

5.40 8.60 1,823x1,276x3,254 2,360 2,416 2,520 2,634

kPa

30

31

520 640 172 114 521 635 Variable speed centrifugal compressor 33.1 21.6 104 132 6.00 5.40 9.40 8.80 1,823x1,276x3,419 1,755x1,790x3,441 2,546 3,709 2,812 4,074 Flooded shell and tube (2 passes) 23

860 128 856

C10 172 1,048

27.7 171 5.50 8.60 1,748x1,853x3,289 4,095 4,548

33.1 206 5.90 9.60 1,794x1,904x3,401 4,765 5,330

21

11

49.1

59.9

18

Flooded shell and tube (2 passes) 29.9 36.7

l/s kPa

18.3

24.6

24

25

28

24

25

29

dBA dBA

89.0

90.1

91.2

92.4

93.6

94.6

70.9

72.0

73.0

73.8

75.1

75.9

°CDB °CDB kg

mm mm Hz / V

210

190

168.3

Oil free centrifugal compressor with magnetic bearings 2~15 18~46 R-134a 180 220 Electronic expansion valve 1 219.1

168.3

273 219.1

3~ / 50 / 400

66

300



DWSC / DWDC

Water cooled chiller with centrifugal compressor

›› ›› ›› ››

Single compressor unit up to 4.5MW Dual compressor unit on single circuit up to 9MW Optional variable speed drives (VFD) for superior partload performance Compressor unloading down to 5% for dual compressor units and 10% for single compressor units without hot gas bypass ›› Control flexibility for easy integration into BMS

WIDE CHOICE OF CAPACITIES AND EFFICIENCIES Single compressor ›› DWSC: 300 kW - 4,500 kW - Approximately 1.1 million possible chiller offerings with combination options of motors, impellers, gears and vessels Dual compressor ›› DWDC: 600 kW - 9,000 kW - Approximately 0.75 million possible chiller offerings with combination options of motors, impellers, gears and vessels

VARIABLE FREQUENCY DRIVE OPTION (VFD) ›› Inverter technology greatly improving part load efficiency ›› Reducing annual energy costs HIGH EFFICIENCY ›› COP up to 7 at full load ›› COP up to 12 at partial load (when coupled with inverter VFD) POWER LOSS DAMAGE PROTECTION Power failures do not allow chillers to proceed through their normal shutdown sequence. Poor lubrication at this point can damage the bearings and reduce compressor life. The compressors are equipped with a lubricant reservoir and a Piston piston with a compressed spring that provides pressurized Lubricant reservoir lubricant to the bearings during the coast-down period. Also, the compressors decelerate quickly due to the low inertia. REFRIGERANT STORAGE CAPABILITY The condensers are sized to hold the entire chiller refrigerant charge and are provided with the necessary valves to isolate this charge. This feature eliminates the need for separate storage vessels in most applications. 68


UNMATCHED UNLOADING Unloading to 10% of full load for a DWSC single compressor chiller and 5% for a DWDC dual compressor unit, without using inefficient hot gas bypass. This unloading capability provides improved stability of the chilled water temperature and less harmful cycling of compressors. Movable discharge diffuser increases stability and reduces vibrations.

Moveable diffuser closing off impeller discharge area

LOW OPERATIONAL SOUND LEVEL Liquid Injection A small amount of liquid refrigerant is taken from the condenser and injected into the compressor discharge area. The liquid droplets absorb sound energy and reduce the compressor's overall operational sound level. The droplets evaporate and reduce discharge superheat. Quieter as chiller unloads Daikin’s design results in a reduction in sound levels at lower loads, where most chillers spend most of their operating hours.

ONE DWDC DUAL COMPRESSOR CHILLER VERSUS TWO SINGLE COMPRESSOR CHILLERS ›› Lower equipment costs than two separate chillers ›› Lower installation cost than two separate chillers ›› Lower annual operating cost than either one large or two small chillers ›› Less equipment room space required than for two separate chillers (smaller footprint) ›› Capacity reduction to 5% of design value ›› Standby redundancy for most of the cooling season options of motors, impellers, gears and vessels

EXCELLENT PART LOAD EFFICIENCY When one compressor is running, it is able to utilize the heat transfer area of the entire chiller, twice the amount found on a single compressor chiller. This huge amount of surface provides exceptional part load efficiency. The addition of VFDs to the dual compressor chiller produces a very high ARI certified Integrated Part Load Value (IPLV). PARTIAL LOADS EFFICIENCY FOR 2,000 kW CENTRIFUGAL UNIT 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 0.0

7.0

D

9.7

7.4

D

D

10.0

DWSC: single compressor DWDC: double compressor VFD: compressor inverter Specific selections can vary up or down from this example.

D

69


1. Temperature sensor 2. Filter 3. Shut-off valve 4. Pump 5. Pressure port 6. Flow switch 7. Air purge 8. Pressure gauge 9. Balancing valve 10. Drain valve 11. Charging valve 12. Safety valve

CONDENSERLESS 1

To condenser

3

2

5

4

5

Expansion vessel

Chillers

12

Evaporator

Gas

7

Buffer tank

To fan coil units

Liquid

1

6

5

8

11

9

70

10


Daikin offers you flexible condenserless chillers with remote condenser, which can be used to satisfy applications with special requirements in the field of available space, sound level or extreme operating conditions. In these exceptional cases, remote condenser solutions can be preferred over standard air-cooled or water-cooled solutions.

Condenserless chillers NEW

EWLP-KBW1N EWLD-J-SS EWLD-G-SS EWLD-I-SS

72 73 74 75

71


EWLP-KBW1N

Condenserless chiller EWLP012-030KBW1N

μC² SE

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Daikin scroll compressor Optimised for use with R-407C Low operating sound level Low energy consumption Compact dimensions and low refrigerant volume Easy installation and maintenance Stainless steel plate heat exchanger Compatible with hydraulic module Main switch, pressure ports, flow switch, filter, shutoff valves and air purge are standard included µC² SE DDC controller

Cooling only Capacity class Cooling capacity Power input EER Dimensions Weight Water heat exchanger evaporator

Nom. Cooling

Nom.

HeightxWidthxDepth Unit Unit Minimum water volume in the system Water flow rate Min. Nom. Max. Model Quantity Type Sound power level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Piping Evaporator water inlet/outlet connections Evaporator water drain Power supply Phase / Frequency / Voltage

kW kW

012 12.1 4.2 2.88

020 20.0 6.6 3.03

mm kg l

108

l/min l/min l/min

dBA

026 26.8 8.5 3.15

030 31.2 10.1 3.09

040 40.0 13.4 2.99

141

147

151

62

103

134

155

17 35 69

29 57 115

38 77 153

205

268

311

45 57 89 115 179 229 1 Brazed plate 71 Hermetically sealed scroll compressor -10~20 25~60 R-407C Thermostatic expansion valve

77 154 307

89 179 358

600x600x600

64

°CDB °CDB

mm

065 62.4 20.3 3.07

252

055 53.7 17.8 3.02 600x600x1,200 265

1 FBSP 25

72

74

2 FBSP 40 Field installation 3N~ / 50 / 400

Hz / V

67

274


EWLD-J-SS

Condenserless chiller standard efficiency, standard sound EWLD-J-

MicroTech III

›› ›› ›› ›› ›› ››

Compact design to allow easy indoor installation or retrofit operations Steples single screw compressor High efficiency at full and partial load Chilled water temperatures down to -10°C on standard unit Optimised for use with R-134a MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER Dimensions Weight Water heat exchanger evaporator Sound power level Sound pressure level Compressor Operation range Refrigerant Piping connections Power supply

Nom. Method/Minimum capacity Cooling Nom.

kW % kW

HeightxWidthxDepth Unit Unit Operation weight Nominal water pressure drop Cooling Total Type Cooling Nom. Cooling Nom. Type Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Type Circuits Quantity Evaporator water inlet/outlet Phase/Frequency/Voltage

mm kg kg kPa dBA dBA

110 110

130 128

30.9 3.55

38.0 3.36

1,124 1,138 14

1,141 1,159 12

145 143

165 195 164 192 Stepless/25 43.3 49.8 55.3 3.31 3.30 3.47 1,020x913x2,684 1,237 1,263 1,305 1,253 1,281 1,327 36 34 32 88.6 71.4

°CDB °CDB 1 inch Hz/V

73

235 237

265 265

290 286

310 307

330 328

360 390 430 356 383 429 Stepless/12.5 65.2 74.5 86.5 93.0 99.5 105 111 121 3.63 3.56 3.31 3.30 3.39 3.47 3.56 2,000x913x2,684 1,489 2,474 2,500 2,526 2,568 2,611 2,795 1,518 2,505 2,533 2,562 2,608 2,655 2,845 25 31 36 34 32 Brazed plate, one per circuit 87.2 92.4 91.8 70.0 74.4 73.8 Semi-hermetic single screw compressor -10~15 25~60 R-134a 2 3 3~/50/400

470 474

500 502

530 530

130 3.63

140 3.59

149 3.56

2,979 3,036 25

31 91.0 73.0


EWLD-G-SS

Condenserless chiller standard efficiency, standard sound EWLD-G-SS

MicroTech III

›› ›› ›› ›› ›› ›› ›› ›› ››

Cooling range: 161-526kW EER range: 3.48 to 3.70 Stepless single-screw compressor Optimised for use with R-134a 1 or 2 truly independent refrigerant circuits Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return All models are PED pressure vessel approved MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity steps Power input EER Dimensions Weight

Nom. Cooling

Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Minimum water volume in the exchanger system evaporator Water flow rate Min. Nom. Max. Nominal water Cooling Heat exchanger pressure drop Model Quantity Type Type Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage

kW % kW mm kg kg l l/min l/min l/min kPa

160 161

190 240 189 244 stepless 25 - 100 54.3 65.9 3.48 3.70 1,860x1,000x3,700

45.4 3.54 1,280 1,337

280 270

320 316

74.6 3.62

90.6 3.48

1,398 1,516

360 352

380 420 381 428 stepless 12.5 - 100 99.7 108.6 120 3.53 3.51 3.57 1,942x1,100x4,400 2,446 2,501 2,560

2,442

480 476

550 526

131.5 3.62

148 3.55 2,506

2,670

1,151

1,354

1,749

1,938

1,130

1,262

1,365

1,535

1,704

1,884

230.20 460.39 649.15

270.90 541.81 763.95

349.74 699.47 986.26

387.58 775.16 1,092.97

452.22 904.44 1,275.27

504.83 1,009.65 1,423.61

546.25 1,092.50 1,540.42

613.90 1,227.81 1,731.21

681.84 1,363.69 1,922.80

753.80 1,507.60 2,125.71

48

69

43

53

64

63

72

54

68

1 EV19270055 dBA dBA

EV27270066

EV27270077 EV27270088 Shell and tube - direct expansion

88

EV32270088

EV32270099

90.5

69.7

71.7 Semi-hermetic single screw compressor -8~15 25~60 R-134a

°CDB °CDB kg

5

10 Electronic expansion valve

1 mm Hz / V

2

88.9

114.3 3~ / 50 / 400

74

139.7


EWLD-I-SS

Condenserless chiller standard efficiency, standard sound EWLD-I-SS

MicroTech III

›› ›› ›› ›› ›› ›› ›› ››

Cooling range: 328–1,422kW EER range: 3.51 to 3.91 Stepless single-screw compressor Optimised for use with R-134a Standard electronic expansion valve DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return All models are PED pressure vessel approved MicroTech III controller for superior control logic and an easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications

Standard efficiency Standard sound

Cooling only Capacity class Cooling capacity Capacity control Power input EER Dimensions Weight

Nom. Method Minimum capacity Cooling Nom.

HeightxWidthxDepth Unit Unit Operation weight Water heat Water flow rate Nom. exchanger Nominal water Cooling Total evaporator pressure drop Type Sound power level Cooling Nom. Sound pressure Cooling Nom. level Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping Evaporator water inlet/outlet connections Power supply Phase / Frequency / Voltage

kW % kW mm kg kg l/min kPa

dBA dBA

320 328

400 391

420 428

500 504

25 83.8 100 116 137 3.91 3.9 3.7 3.67 1,899x1,464x3,114 1,861 1,869 1,884 2,054 2,052 2,056 940.2 1,120.8 1,227.0 1,444.8 34

47

600 596

650 657

165 3.61

181 3.63

3,331 3,339 3,602 1,708.8 1,883.4

54

49

39

750 730

800 788

900 950 C10 C11 C12 C13 C14 C15 C16 919 966 1,033 1,078 1,125 1,188 1,267 1,319 1,370 Stepless 12.5 8.3 198 214 231 252 271 279 296 312 329 347 366 386 3.69 3.67 3.65 3.56 3.59 3.64 3.60 3.61 3.65 3.60 3.55 2,325x1,464x4,391 2,415x2,135x4,426 3,347 3,356 3,364 3,412 5,146 5,167 5,188 5,208 3,603 3,604 3,605 3,645 5,667 5,671 5,677 5,680 2,092.8 2,259.0 2,436.6 2,634.6 2,769.0 2,961.0 3,090.0 3,225.0 3,405.6 3,631.8 3,781.2 3,927.6 52

850 850

47

45

52

46

49

41

51

55

59

C17 1,422

405 3.51

4,076.4 63

93.7

96.6

96.7

96.9

97.3

97.8

Single pass shell and tube 98.9 99.8 100.4 100.8 101.2 103 100.4 100.8 101.2 103

75.2

76.2

78.2

77.8

78.2

78.7

79.8

80.7

80.4

80.8

Semi-hermetic single screw compressor -8~15 25~60 R-134a 5 Electronic expansion valve 2

°CDB °CDB kg 1 mm

168.3

75

83

80.4

3 219.1

3~ / 50 / 400

Hz / V

81.2

80.8

81.2

83


D.I.C.N.

Daikin Integrated Chiller Network

APPLICABLE SERIES: ›› ››

EWAQ080-260DAYN (R-410A) EWYQ080-250DAYN (R-410A)

Daikin chillers can be equipped with DICN which allows the simultaneous operation of up to 4 chillers as if they were a single unit, in order to deliver the required cooling capacity. This results in precise and efficient capacity control and is also useful for back up purposes, ensuring that the necessary amount of cooling is available and guaranteeing reliable operation of the chiller plant. This function enables a Daikin chiller plant to be operated via a single controller. Please note that DICN is only possible within the same series.

76


EHMC/EKBT

Hydraulic Module / Buffer Tank EHMC10-15-30A10

mH2O 55 50 45

›› ›› ›› ›› ›› ››

3 models available 100 l tank for all sizes freeze up protection high static pump (option) standard drain kit (for indoor use) standard dual pressure ports (before & behind the pump)

40 35

LEGENDS Pump characteristics 1. EHMC30A80 2. EHMC10A80 & EHMC15A80 3. EHMC30A10 4. EHMC10A10 & EHMC15A10 Hydraulic module + filter pressures losses 5. EHMC15/30A10 & EHMC15/30A80 6. EHMC10A10 & EHMC10A80

30 25 20 15 10 5 0

0 20 40 60 80 100 120 140 160 180 200 220 240 260 ( l/min)

Water flow

HYDRAULIC MODULE 10

EHMC-AV Nominal flow Nominal External static pressure Nominal input Dimensions (HxWxD) Machine weight Sound power Sound pressure Power supply Operation range Water side Air side Piping connections Water inlet/outlet Drain connection

10 l/min mH2O W mm kg dBA dBA V1 °C °CDB inch inch

15 80

10

62 17 630

10

88 34 1,050

15 650

101

102

1,284x635x688 99

30 80 27 1,070

10 1,070

104

105

1,284x635x688

63 52

27 2,090 1,284x635x688

63 52 1~/230V/50Hz -10°C ~ 55°C -10°C ~ 43°C 2" BSPF 1/2"

1" BSPF

80 187

111 63 52

2-1/2" BSPF

BUFFER TANK MODEL

Description

Volume

Dimensions

Unit weight

EKBT

Buffer tank with cabinet

EKBT500C

Buffer tank with cabinet

200l

1,284x637x754

86.5

500l

1,200x1,200x1,950

EKBTC10C

160

Buffer tank with cabinet

1,000l

1,200x1,450x1,950

185

EKBT500N

Buffer tank

500l

710x1,670

70

EKBTC10N

Buffer tank

1,000l

860x2,020

100

77


Dry Coolers & Condensers

Duct type with centrifugal fan

V Shape type with axial fan

Horizontal or vertical type with axial fan

›› ›› ›› ›› ››

Single coil, both for vertical and horizontal installation, or double coil (V shape) For air conditioning and for industrial process cooling Extreme low noise and energy saving models available Factory engineered and mounted controls Capacities from 3 up to more than 2,400 kW

Cooling Towers

Radial fan type

›› ›› ›› ›› ›› ›› ›› ››

Axial fan type

Open circuit type Closed circuit type Evaporative condenser type Radial or axial fans Galvanized steel, Stainles steel or Fiberglass For air conditioning and for industrial process cooling Low noise and energy saving models available Capacities from 70 up to more than 9,200 kW

78


Ventilation Fan coil units Casette units FWC-BT/BF FWF-BT/BF FWC-AT/AF FWF-CT

80 81 81 82 83 84

Concealed ceiling units FWB-JT/JF FWB-BT

85 85 86

Wall mounted units FWT-BT

87 87

Flexi type units FWL-DT/DF FWM-DT/DF FWD-AT/AF

88 88 89 90

Floor standing units FWV-DT/DF

91 91

Air Coolers

92

Heat Reclaim Ventilation VAM-FA

93 93

Rooftops UATYQ-CY1 UATYP-AY1

94 94 95

Air handling units

96

PLUG and PLAY VRV速 connection AHU

100

For more information on Options & Accessories, please refer to page 107 of this catalogue. 79


Portfolio Fan coil units

FWV-DT/DF

FWD-AT/AF

FWM-DT/DF

FWL-DT/DF

FWT-BT

FWB-BT

FWB-JT/JF

FWF-CT

FWC-AT/AF

FWF-BT/BF

FWC-BT/BF

Reference 2-pipe

4-pipe

2-pipe

4-pipe

2-pipe

4-pipe

2-pipe

2-pipe

4-pipe

2-pipe

4-pipe

2-pipe

2-pipe

4-pipe

2-pipe

4-pipe

2-pipe

4-pipe

2-pipe

4-pipe

Page 1

2

3

4

5

cooling heating cooling

6

06

07

06

08

09

06

07

07

08

09

06

cooling

cooling

02

03

04

10

08

heating

02 02

03

04

cooling

0304

07

08

0203

08

10

11

12

08

02

02

06

06

heating

09

10 11 07 08

09

10 11

07

08

10 07

06 05

06

07

02 03

04

08

08 09

10 10 05

06

07

08

09

10

86 02 03 04

05

06

07

02 03 04 02 03

08

09

10

05 06 07

04

05

08 09 10

06

87 02

01

02

03 04

03

05

06

04 06

01 02

08

03

04

06

10 08

10

88 01 02

03

01 02 01

04 06 03

02

08 04

03

06

08

04 06

01 02

10

08

03

04

06

10

10 08

10

89 01 02

03

01 02

0406

08

03

10

04 06

08

04

06

08

04

10 10

06

12 08

16 12

10

18 16

18

90 04

06 04

cooling

cooling

08

03 04

heating

heating

07

06

03 04

cooling

cooling

04

04

030405

02

heating

heating

03

03 04 05 02

cooling

cooling

04 05 06

85

heating

heating

03

03 04 02

cooling

cooling

11 12

84

heating

heating

10

04 05 06 02

02 03 04

heating

22kW

09

07

83

cooling

cooling

20

05

07

02

cooling

18

05

heating

heating

16

05

02 03 04

cooling heating

12

09

heating

cooling

11

05

cooling

cooling

9

82

heating

heating

8

81

heating

heating

7

01

02 01

03 02

08

10

06

04 06 04

06

10 08

10

91 01

02 01 02

03

04 06 03

08 0406

80

10 08

10

16 12

10

08

03

12 08

18 16 18


FWC-BT/BF

Round flow cassette

FWC-BT/BF

›› ›› ›› ›› ›› ››

BRC315D7

BRC7E532F

360° air discharge ensures uniform air flow and temperature distribution Modern style decoration panel in white Possibility to shut 1 or 2 flaps for easy installation in corners Fresh air intake for healthy living Comfortable horizontal air discharge ensures draughtfree operation and prevents ceiling soiling Standard drain pump with 850mm lift

Indoor units Cooling capacity

2-PIPE

Total capacity Sensible capacity Heating capacity 2-Pipe 4-Pipe Power input High Dimensions Unit Weight Unit Water pressure Cooling drop Heating Fan Type Air flow rate Sound power level High Sound pressure level High Piping Water connections Power supply

High High High High HeightxWidthxDepth

High

Inlet Outlet Drain OD Phase/Frequency/Voltage

kW kW kW kW W mm kg kPa kPa m³/h dBA dBA inch inch mm Hz/V

FWC06BT 5.0 3.4 6.3

FWC07BT 5.6 4.0 7.1

4-PIPE FWC08BT 6.3 4.5 8.3

FWC09BT 7.2 5.3 9.5

40

46

58

76

FWC06BF 4.9 3.4

FWC07BF 5.6 3.9

6.2 41

6.8 47

1,062 36 24

19 19

7.8 59

8.8 77

25 38

32 47

288x840x840 29 26 26

Turbo fan 1,236 1,518 39 44 28 32 3/4” BSP (female thread) 3/4” BSP (female thread) VP25 (External dia. 32, Internal dia. 25) 1~/50/220-240

81

FWC09BF 7.2 5.2

-

288x840x840 26 15 15

FWC08BF 6.3 4.4

34 34

15 24

1,776 49 37

1,032 36 24

19 30

Turbo fan 1,200 1,476 39 44 28 32 3/4” BSP (female thread) 3/4” BSP (female thread) VP25 (External dia. 32, Internal dia. 25) 1~/50/220-240

1,746 49 37


FWF-BT/BF

4-way blow ceiling mounted cassette

FWF-BT/BF

›› ›› ›› ›› ›› ››

BRC315D7

BRC7E532F

Modern style decoration panel in white Compact casing (570mm in width and depth) enables unit to fit flush into ceilings and match standard architectural modules, without cutting ceiling tiles Comfortable horizontal auto swing ensures draughtfree operation and prevents ceiling soiling Possibility to shut 1 or 2 flaps for easy installation in corners Fresh air intake for healthy living Standard drain pump with 750mm lift

Indoor units Cooling capacity

2-PIPE

Total capacity Sensible capacity Heating capacity 2-Pipe 4-Pipe Power input High Dimensions Unit Weight Unit Water pressure Cooling drop Heating Fan Type Air flow rate Sound power level High Sound pressure level High Piping Water connections Power supply

High High High High HeightxWidthxDepth

kW kW kW kW W mm kg kPa kPa

FWF02BT 1.7 1.3 2.6

FWF03BT 2.8 1.7 3.4

4-PIPE FWF04BT 3.3 2.1 4.1

FWF05BT 4.0 2.7 5.3

67

70

19 19

Inlet Outlet Drain OD Phase/Frequency/Voltage

m³/h dBA dBA inch inch mm Hz/V

660 44 33 3/4” BSP (female thread) 3/4” BSP (female thread) VP20 (External dia. 26, Internal dia.20) 1~/50/220-440

82

FWF05BF 3.5 2.3

89

3.9 74

4.8 93

42 42

19 6 12

20 21 9

33 13

876 49 39

468 40 27

3.3 62 285x575x575

31 31

468 40 27

FWF04BF 2.8 1.7 -

Turbo fan High

FWF03BF 2.3 1.3

3.1 67

285x575x575 19 6 6

FWF02BF 1.7

13 6

Turbo fan 438 618 42 46 29 35 3/4” BSP (female thread) 3/4” BSP (female thread) VP20 (External dia. 26, Internal dia.20) 1~/50/220-440

822 51 41


FWC-AT/AF

4-way blow ceiling mounted cassette

FWC-AT/AF

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

MERCA

SRC-COA/HPA

WRC-COB/HPB

Wide operating range Easy installation and maintenance Flexibility (2-pipe or 4-pipe) 3-speed fan motor Double-intake centrifugal fans Air suction from underneath High power air flow Removable washable air filter (self-extinguishing class 1) Built-in high pressure drain pump with 700mm lift Infrared remote control as standard with decoration panel kit

Indoor units Cooling capacity

Total capacity High Sensible capacity High Heating capacity 2-Pipe High 4-Pipe High Power input High Current input High HeightxWidthxDepth Dimensions Unit Weight Unit Operation weight Heat exchanger Water volume Water flow Cooling Heating Water pressure Cooling drop Heating Fan Type Air flow rate High Sound power level High Sound pressure level High Piping connections Std. heat exchanger Drain OD Power supply Phase/Frequency/Voltage

kW kW kW kW W A mm kg kg l l/h l/h kPa kPa m³/h dBA dBA inch mm Hz/V

FWC07AT 6.63 4.90 8.40 127 0.52 31.0 34.0 1,140 1,140 24.8 21.4 1,310 52 42

2-PIPE FWC10AT FWC11AT 8.80 9.95 6.40 7.10 11.00 12.00 151 164 192 0.64 0.68 0.79 335x820x821 32.0 35.0 38.0 35.0 38.0 41.0 2.69 1,290 1,514 1,711 1,290 1,514 1,711 30.8 41.6 52.2 26.8 35.3 45.2 Direct drive turbo fan 1,380 1,560 1,740 55 60 61 45 49 51 3/4 19.05 1~/50/220-240

FWC08AT 7.50 5.40 9.50

83

FWC12AT 10.80 7.70 12.90

FWC02AF 3.81 3.40

253 1.06

10.55 122 0.53

40.0 43.0

31.0 34.0

1,858 1,858 69.3 64.1

655 907 3.56 4.8

1,840 64 53

1,310 52 42

4-PIPE FWC04AF FWC05AF 4.63 5.01 4.07 4.40 10.99 12.51 13.48 138 153 184 0.61 0.67 0.80 335x820x821 32.0 35.0 38.0 35.0 38.0 41.0 2.69 681 796 862 945 1,076 1,159 3.78 4.94 5.70 5.5 7.2 8.6 Direct drive turbo fan 1,380 1,560 1,740 55 60 61 45 49 51 3/4 19.05 1~/50/220-240

FWC03AF 3.96 3.52

FWC06AF 5.16 4.54 13.77 232 1.02 40.0 43.0 888 1,184 5.96 8.9 1,840 64 53


FWF-CT

4-way blow ceiling mounted cassette

FWF-CT

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

MERCA

SRC-COA/HPA

WRC-COB/HPB

4 way air discharge and air swing Compact casing (570mm in width and depth) enables unit to fit flush into ceilings and match standard architectural modules, without cutting ceiling tiles Wide operating range Air suction from underneath Easy installation and maintenance Built-in high pressure drain pump with 700mm lift Double-intake centrifugal fans High power air flow 3-speed fan motor Infrared remote control as standard with decoration panel kit

Indoor units Cooling capacity

Total capacity High Sensible capacity High Heating capacity 2-Pipe High 4-Pipe High Power input High Current input High HeightxWidthxDepth Dimensions Unit Weight Unit Operation weight Water pressure Cooling drop Heating Fan Type Air flow rate High Sound power level High Sound pressure level High Piping connections Std. heat exchanger Drain OD Power supply Phase/Frequency/Voltage

kW kW kW kW W A mm kg kg kPa kPa m³/h dBA dBA inch mm Hz/V

2-PIPE FWF03CT 4.10 2.93 4.69 64 0.28 250x570x570

FWF02CT 2.49 1.91 3.52 63 0.27 22 22 19.00 17.00

FWF04CT 4.54 3.37 5.28 79 0.34 23 23

27.00 24.00 Direct drive turbo fan 680 54 45 3/4 19.05 1~/50/220-440

646 52 42

84

29.00 27.00 748 56 48


FWB-JT/JF

Concealed ceiling unit

FWEC1, 2, 3A

FWB02JT/JF

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Wide operating range Quiet operation via enlarged fan wheels Easy maintenance: filter can be removed from both sides and beneath (maximum filter size is 400mm) Flexibility (2-pipe or 4-pipe) 4-speed fan motor Direct driven centrifugal fans Flexibility via interchangeable water connection side High power air flow Available static pressure of 30 Pa Extended drain pan as standard Standard Filter Insulated with self-extinguishing class 1 heat insulation Electronic room thermostat

Indoor units Cooling capacity Heating capacity Power input Current input Dimensions Weight

Total capacity Sensible capacity 2-Pipe 4-Pipe High High Unit

High High High High

HeightxWidthxDepth

Unit Operation weight Heat exchanger Water volume Water flow Cooling Heating Additional heat exchanger Water pressure Cooling drop Heating Additional heat exchanger Fan Type Air flow rate High Available pressure High Sound power level High Sound pressure level High Piping connections Std. heat exchanger Power supply Phase / Frequency / Voltage

kW kW kW kW W A mm kg kg l l/h l/h l/h kPa kPa kPa m³/h Pa dBA dBA inch Hz / V

2-PIPE 4-PIPE FWB02JT FWB03JT FWB04JT FWB05JT FWB06JT FWB07JT FWB08JT FWB09JT FWB10JT FWB11JT FWB02JF FWB03JF FWB04JF FWB06JF FWB07JF 1.64 2.67 2.99 3.34 4.81 5.31 6.16 7.26 8.49 8.99 1.67 2.67 3.03 4.88 5.33 0.94 1.88 1.95 2.07 3.40 4.15 4.39 5.06 6.37 6.41 0.97 1.83 1.93 3.41 4.01 2.16 3.62 3.97 4.11 6.30 7.47 8.09 9.64 11.57 11.71 2.12 3.69 3.87 6.40 7.52 2.49 3.92 4.43 6.70 8.16 34 53 57 54 86 121 117 134 164 166 34 51 54 84 117 0.15 0.24 0.26 0.25 0.39 0.55 0.53 0.61 0.75 0.15 0.23 0.25 0.38 0.53 251x814 251x984 251x1,314 251x1,664 251x814 251x984 251x1,114 251x1,314 251x1,564 251x1,114x590 251x1,564x590 251x1,924x590 x590 x590 x590 x590 x590 x590 x590 x590 x590 20.0 23.0 28.0 31.0 33.0 44.0 48.0 52.0 50.0 56.0 22.0 27.0 31.0 36.0 48.0 20.7 24.0 29.1 32.5 34.4 45.8 50.4 54.6 52.4 59.1 22.9 28.3 32.5 37.9 50.4 0.69 0.95 1.14 1.52 1.44 1.82 2.42 2.62 2.36 3.14 0.92 1.26 1.52 1.92 2.42 386 549 739 803 1,022 1,109 1,383 1,523 1,764 1,910 386 530 724 986 1,138 386 549 738 802 1,020 1,107 1,336 1,524 1,764 1,911 387 530 725 985 1,139 269 391 493 663 820 10.91 8.34 15.64 11.22 31.31 12.56 7.62 9.83 21.71 16.81 10.95 8.24 15.67 29.95 9.24 8.86 6.76 12.84 9.21 25.87 11.13 6.57 8.60 18.56 14.46 8.94 6.64 12.84 24.16 7.89 10.66 24.73 41.72 81.63 25.31 Direct driven centrifugal fan (forward-curved blades)hot-galvanised steel 262 428 431 428 757 945 950 1,066 1,463 1,341 220 424 437 747 898 30 30 47.5 52 49 50 52 55 55.5 56 47 52 50 52 35.5 40 37 38 40 39.5 43 43.5 44 35 40 38 40 39.5 3/4 3/4 1~ / 50 / 220-240 1~ / 50 / 220-240

85

FWB08JF 6.53 4.91 9.01 9.56 137 0.62 251x1,664 x590 52.0 54.6 2.62 1,296 1,299 924 12.49 9.67 31.33

FWB10JF 8.21 6.28 11.09 11.68 163 0.74 251x1,924 x590 56.0 59.1 3.14 1,660 1,660 1,142 19.38 16.50 50.03

1,112 1,385 55 43

56 44


FWB-BT

Concealed ceiling unit

FWEC1, 2, 3A

FWB04BT

›› ›› ›› ›› ›› ›› ››

Low sound power levels and electrical absorption thanks to plastic impeller, ABS winding staircase and improved electric motor Compact dimensions, can easily be mounted in a narrow ceiling void 3, 4 or 6 stage row cooling coil Drain pan to collect the condensate from: heat exchanger and regulating valves 7-speed electrical motors (with thermal protection on windings) All 7 speeds pre-wired in the factory in the terminal block of the switch box The air filter can easily be removed for cleaning

Indoor units Cooling capacity Heating capacity Power input Current input Dimensions Weight Heat exchanger Additional heat exchanger Water flow

Total capacity High Sensible capacity High 2-Pipe High 4-Pipe* High High High HeightxWidthxDepth Unit Unit Operation weight Water volume Water volume

Cooling Heating Additional heat exchanger Water pressure Cooling drop Heating Additional heat exchanger Fan Type Air flow rate High Available pressure High Sound power level High Sound pressure level High Piping connections Std. heat exchanger Add. heat exchanger Drain OD Power supply Phase / Frequency / Voltage

kW kW kW kW W A mm kg kg l l l/h l/h l/h kPa kPa kPa m³/h Pa dBA dBA inch inch mm Hz / V

FWB02BT 2.61 1.88 5.47

23 24 1.1

FWB03BT FWB04BT 3.14 3.49 2.16 2.34 6.01 6.47 3.14 79 0.36 239x1,039x609 24 26 26 28 1.5 2.2

FWB05BT 5.08 3.6 10.31

31 33 1.6

0.4 448 480 8 7

2-PIPE FWB06BT FWB07BT 5.45 6.47 3.87 4.4 11.39 12.28 5.99 154 0.73 239x1,389x609 33 35 35 38 2.1 3.2

FWB08BT 7.57 5.23 15.05

43 45 2.1

FWB09BT FWB10BT 8.67 10.34 5.96 6.9 16.85 18.78 12.8 294 1.28 239x1,739x609 45 48 48 52 2.8 4.2

0.6

539 527 275 14 10 3

598 567

936 1,111 1,299 999 1,077 1,319 526 11 15 8 14 8 12 7 10 16 5 Centrifugal - forward blades - directly coupled on fan motor 800 65 59 47.5 3/4 3/4 16 1~ / 50 / 230

400 71 56 44.5

*4-pipe = 2-pipe + option additional heat exchanger

86

1.7

873 904

1,488 1,479 1,123 21 15 8 1,200 59 69 57.5 1

1,774 1,647 26 18


FWT-BT

Wall mounted unit

FWT05, 06BT

›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››

MERCA

SRC-COA/HPA

WRC-COB/HPB

Wide operating range Easy installation and maintenance 3-speed fan motor Double-intake centrifugal fans Excellent air flow and air distribution Flexibility via interchangeable water connection side High power air flow Insulated with self-extinguishing class 1 heat insulation Removable washable air filter (self-extinguishing class 1) Slim and compact aesthetic design Wireless remote control up to 9m distance, availability of a wired or simplified controller LED indicator gives an indication on the (normal or wrong) operation of the unit

Indoor units Cooling capacity

Total capacity High Sensible capacity High Heating capacity 2-Pipe High Power input High Current input High HeightxWidthxDepth Dimensions Unit Weight Unit Operation weight Heat exchanger Water volume Water flow Cooling Heating Water pressure Cooling drop Heating Fan Type Air flow rate High Sound power level High Sound pressure level High Piping connections Std. heat exchanger Drain OD Power supply Phase / Frequency / Voltage

kW kW kW W A mm kg kg l l/h l/h kPa kPa m³/h dBA dBA inch mm Hz / V

FWT02BT 2.34 1.74 3.02 24

2-PIPE FWT04BT 3.22 2.35 4.10 29 0.13

FWT03BT 2.78 2.03 3.75 25 0.11

260x799x198 10 10 0.49 402 402 48.3 42

FWT05BT 4.54 3.65 6.01 66 0.29

260x899x198 12 13 0.57 478 478 64.7 58.6

467

510 53

40

39

554 554 69.3 60.6 Direct drive cross flow fan 586 55 42 1/2

16

304x1,062x222 16 17 0.85 781 781 50.3 50.6

908 908 69.3 70.6

1,070 61 49

1,121 64 50 20

1~ / 50 / 220-240

87

FWT06BT 5.28 4.33 6.74 69 0.30


FWL-DT/DF

Flexi type unit

FWL-DT/DF

›› ›› ›› ›› ›› ›› ›› ››

FWL-DT/DF

FWEC1, 2, 3A

ECFWMB6

Quick fixing system for wall or ceiling mounted installation Pre-assembled 3-way/4-port on/off valves are available Valve packages are insulated, no extra drain pan required Valve packages contain balancing valves and sensor pocket Fast-on connections for electrical options: no tools needed The air filter can easily be removed for cleaning Electric heater: no relay up to 2kW capacity Electric heater: equipped with two overheat cut-out thermostats

Indoor units Cooling capacity

Total capacity High Sensible capacity High Heating capacity 2-Pipe High 4-Pipe High Power input High Current input High HeightxWidthxDepth Dimensions Unit Weight Unit Heat exchanger Water volume Water flow Cooling Heating Water pressure Cooling drop Heating Fan Type Air flow rate High Sound power level High Piping connections Std. heat exchanger Power supply Phase/Frequency/Voltage

kW kW kW kW W A mm kg l l/h l/h kPa kPa m³/h dBA inch Hz/V

2-PIPE 4-PIPE FWL01DT FWL02DT FWL03DT FWL04DT FWL06DT FWL08DT FWL10DT FWL01DF FWL02DF FWL03DF FWL04DF FWL06DF FWL08DF FWL10DF 1.54 2.09 2.93 4.33 4.77 6.71 8.02 1.46 1.90 2.87 4.33 4.67 6.64 7.88 1.20 1.51 2.11 3.15 3.65 4.91 5.96 1.14 1.51 2.07 3.15 3.57 4.85 5.85 2.14 2.57 3.81 5.63 6.36 7.83 10.03 1.90 2.10 3.08 5.05 5.30 7.91 9.30 37 53 56 98 137 175 37 53 56 98 137 175 0.17 0.24 0.25 0.44 0.43 0.60 0.76 0.17 0.24 0.25 0.44 0.43 0.60 0.76 564x774x226 564x984x226 564x1,194x226 564x1,404x251 564x774x226 564x984x226 564x1,194x226 564x1,404x251 20 21 27 32 33 44 21 22 28 34 35 46 0.5 0.7 1 1.4 2.1 0.5 0.7 1 1.4 2.1 265 359 504 745 820 1,154 1,343 251 327 494 745 803 1,142 1,355 265 359 504 745 820 1,154 1,343 196 182 286 396 465 694 816 13 11 12 14 12 19 13 11 12 14 12 19 9 11 9 10 9 16 7 8 5 10 8 9 Centrifugal multi-blade, double suction Centrifugal multi-blade, double suction 319 344 442 706 785 1,011 1,393 307 327 431 690 763 998 1,362 45 50 47 52 56 58 64 45 50 47 52 56 58 64 1/2 3/4 1/2 3/4 1~/50/230 1~/50/230

88


FWM-DT/DF

Flexi type unit

FWM-DT/DF

›› ›› ›› ›› ›› ›› ›› ››

FWM-DT/DF

FWEC1, 2, 3A

Quick fixing system for wall or ceiling mounted installation Pre-assembled 3-way/4-port on/off valves are available Valve packages are insulated, no extra drain pan required Valve packages contain balancing valves and sensor pocket Fast-on connections for electrical options: no tools needed The air filter can easily be removed for cleaning Electric heater: no relay up to 2kW capacity Electric heater: equipped with two overheat cut-out thermostats

Indoor units Cooling capacity

Total capacity High Sensible capacity High Heating capacity 2-Pipe High 4-Pipe High Power input High Current input High HeightxWidthxDepth Dimensions Unit Weight Unit Heat exchanger Water volume Water flow Cooling Heating Water pressure Cooling drop Heating Fan Type Air flow rate High Sound power level High Piping connections Std. heat exchanger Drain OD Power supply Phase/Frequency/Voltage

kW kW kW kW W A mm kg l l/h l/h kPa kPa m³/h dBA inch mm Hz/V

2-PIPE 4-PIPE FWM01DT FWM02DT FWM03DT FWM04DT FWM06DT FWM08DT FWM10DT FWM01DF FWM02DF FWM03DF FWM04DF FWM06DF FWM08DF FWM10DF 1.54 2.09 2.93 4.33 4.77 6.71 8.02 1.46 1.90 2.87 4.33 4.67 6.64 7.88 1.20 1.51 2.11 3.15 3.65 4.91 5.96 1.14 1.51 2.07 3.15 3.57 4.85 5.85 2.14 2.57 3.81 5.63 6.36 7.83 10.03 1.90 2.10 3.08 5.05 5.30 7.91 9.30 37 53 56 98 137 175 37 53 56 98 137 175 0.17 0.24 0.25 0.44 0.43 0.60 0.76 0.17 0.24 0.25 0.44 0.43 0.60 0.76 535x584x224 535x794x224 535x1,004x224 535x1,214x249 535x584x224 535x794x224 535x1,004x224 535x1,214x249 14 15 19 23 32 15 16 20 25 34 0.5 0.7 1 1.4 2.1 0.5 0.7 1 1.4 2.1 265 359 504 745 820 1,154 1,343 251 327 494 745 803 1,142 1,355 265 359 504 745 820 1,154 1,343 196 182 286 396 465 694 816 13 11 12 14 12 19 13 11 12 14 12 19 9 11 9 10 9 16 7 8 5 10 8 9 Centrifugal multi-blade, double suction Centrifugal multi-blade, double suction 319 344 442 706 785 1,011 1,393 307 327 431 690 763 998 1,362 45 50 47 52 56 58 64 45 50 47 52 56 58 64 1/2 3/4 1/2 3/4 17 17 1~/50/230 1~/50/230

89


FWD-AT/AF

Flexi type unit

FWD04AT/AF

›› ›› ›› ››

FWEC1,2,3A

FWD04AT/AF

Quick fixing system for wall or ceiling mounted installation Straight duct connector is mounted to discharge side Electronic controller with water probe, available in standard, advanced and advanced plus version The air filter can easily be removed for cleaning

Indoor units Cooling capacity Heating capacity Power input Current input Dimensions Weight Heat exchanger Additional heat exchanger Water flow

Total capacity Sensible capacity 2-Pipe 4-Pipe High High Unit Unit Water volume Water volume

High High High High

HeightxWidthxDepth

Cooling Heating Water pressure Cooling drop Heating Fan Type Air flow rate High Available pressure High Sound power level High Piping connections Std. heat exchanger Drain OD Power supply Phase / Frequency / Voltage

kW kW kW kW W A mm kg l l

2-PIPE 4-PIPE FWD04AT FWD06AT FWD08AT FWD10AT FWD12AT FWD16AT FWD18AT FWD04AF FWD06AF FWD08AF FWD10AF FWD12AF 3.90 6.20 7.80 8.82 11.90 16.40 18.30 3.90 6.20 7.80 8.82 11.90 3.08 4.65 6.52 7.16 9.36 12.80 14.10 3.08 4.65 6.52 7.16 9.36 4.05 7.71 9.43 10.79 14.45 19.81 21.92 4.49 6.62 9.21 15.86 234 349 443 714 1,197 234 349 443 714 0.95 1.58 1.97 3.21 5.37 0.95 1.58 1.97 3.21 280x754x559 280x964x559 280x1,174x559 352x1,174x718 352x1,384x718 280x754x559 280x964x559 280x1,174x559 352x1,174x718 33 41 47 49 65 77 80 35 43 50 52 71 1.06 1.42 1.79 2.38 2.5 4.02 5.03 1.06 1.42 1.79 2.38 2.50 -

l/h l/h kPa kPa

674 674 17 14

m³/h Pa dBA inch mm Hz / V

800 66 66

1,064 1,064

1,339 1,339

1,514 2,056 2,833 3,140 1,514 2,056 2,833 3,140 24 16 26 34 45 20 13 21 28 37 Centrifugal multi-blade, double suction 1,250 1,600 2,200 3,000 58 68 64 97 145 134 69 72 74 78 3/4 1 16 1~ / 50 / 230

90

0.35

0.47

674 349 17 9

1,064 581

800 63 66

0.59 1,339

1,514

1.42

FWD16AF FWD18AF 16.40 18.30 12.80 14.10 21.15 1,197 5.37 352x1,384x718 83 86 4.02 5.03 1.72

2,056 2,833 3,140 808 1,392 1,856 24 16 26 34 45 15 13 12 16 Centrifugal multi-blade, double suction 1,250 1,600 2,200 3,000 53 63 59 92 138 128 69 72 74 78 3/4 1 16 1~ / 50 / 230


FWV-DT/DF

Floor standing unit

FWV-DT/DF

›› ›› ›› ›› ›› ›› ›› ››

FWEC1, 2, 3A

ECFWMB6

Quick fixing system for wall mounted installation Pre-assembled 3-way/4-port on/off valves are available Valve packages are insulated, no extra drain pan required Valve packages contain balancing valves and sensor pocket Fast-on connections for electrical options: no tools needed The air filter can easily be removed for cleaning Electric heater: no relay up to 2kW capacity Electric heater: equipped with two overheat cut-out thermostats

Indoor unit Cooling capacity

Total capacity High Sensible capacity High Heating capacity 2-Pipe High 4-Pipe High Power input High Current input High HeightxWidthxDepth Dimensions Unit Weight Unit Heat exchanger Water volume Water flow Cooling Heating Water pressure Cooling drop Heating Fan Type Air flow rate High Sound power level High Piping connections Std. heat exchanger Drain OD Power supply Phase/Frequency/Voltage

kW kW kW kW W A mm kg l l/h l/h kPa kPa m³/h dBA inch mm Hz/V

2-PIPE 4-PIPE FWV01DT FWV02DT FWV03DT FWV04DT FWV06DT FWV08DT FWV10DT FWV01DF FWV02DF FWV03DF FWV04DF FWV06DF FWV08DF FWV10DF 1.54 2.09 2.93 4.33 4.77 6.71 8.02 1.46 1.90 2.87 4.33 4.67 6.64 7.88 1.20 1.51 2.11 3.15 3.65 4.91 5.96 1.14 1.51 2.07 3.15 3.57 4.85 5.85 2.14 2.57 3.81 5.63 6.36 7.83 10.03 1.90 2.10 3.08 5.05 5.30 7.91 9.30 37 53 56 98 137 175 37 53 56 98 137 175 0.17 0.24 0.25 0.44 0.43 0.60 0.76 0.17 0.24 0.25 0.44 0.43 0.60 0.76 564x774x226 564x984x226 564x1,194x226 564x1,404x251 564x774x226 564x984x226 564x1,194x226 564x1,404x251 19 20 25 30 31 41 20 21 26 32 33 44 0.5 0.7 1 1.4 2.1 0.5 0.7 1 1.4 2.1 265 359 504 745 820 1,154 1,343 251 327 494 745 803 1,142 1,355 265 359 504 745 820 1,154 1,343 196 182 286 396 465 694 816 13 11 12 14 12 19 13 11 12 14 12 19 9 11 9 10 9 16 7 8 5 10 8 9 Centrifugal multi-blade, double suction Centrifugal multi-blade, double suction 319 344 442 706 785 1,011 1,393 307 327 431 690 763 998 1,362 45 50 47 52 56 58 64 45 50 47 52 56 58 64 1/2 3/4 1/2 3/4 16 16 1~/50/230 1~/50/230

91


Air Coolers

Air coolers for big storage,freezing and working cold rooms with positive and negative temperature for the industry. The heat exchanger of the air cooler is made of high efficiency copper tubes with internal special helical profile for the water/glycol solution. Several models available with different fin spacings and for capacities from 1 up to more than 160 kW.

NHIW / HILW

HDIW

CHSW

LHSW

S2HCW

S3HCW

SHDNW / SHDSW

SHAW

92


VAM-FA

Heat reclaim ventilation

Clean outdoor air Total heat exchanged foul air

Total heat exchanged clean air

Foul indoor air

The Daikin heat reclaim ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly. HRV units can be controlled individually or integral with the air conditioning system (Daikin VRV® or Sky Air series).

›› ›› ›› ›› ›› ›› ›› ››

Energy saving ventilation by recovery of indoor unit heat/cold Ideal solution for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings Free cooling when outdoor temperature is below indoor temperature (eg. during night time) Can be used as stand alone unit or integrated in the VRV® system Wide range of units: air flow rate from 150 up to 2,000 m³/h Specially developed heat exchange element with High Efficiency Paper (HEP) No drain piping needed Can operate in over- and under pressure

[iPU]

Ventilation Fan-Air flow rate

Heat exchange mode Ultra high Bypass mode Ultra high Fan-External static pressure Ultra high Heat exchange mode Ultra high Sound pressure level Bypass mode Ultra high Temperature exchange efficieny Ultra high Enthalpy exchange Cooling Ultra high efficieny Heating Ultra high Heat exchange mode Nom. Ultra high Power input Ultra high Bypass mode Nom. HeightxWidthxDepth Dimensions Unit Weight Unit Connection duct diameter Operation range Min. Max. Relative humidity Operation mode Heat exchange system Heat exchange element Power supply Phase/Frequency/Voltage Maximum Fuse Amps (MFA)

m³/h m³/h Pa dBA dBA % % % kW kW mm kg mm °CDB °CDB %

VAM150FA 150 150 69 27 / 28.5 27 / 28.5 74

VAM250FA 250 250 64 28 / 29 28 / 29 72 58 64

0.116 0.141 0.116 0.141 285x776x525 24 100

VAM350FA 350 350

VAM500FA 500 500

98 32 / 34 33 / 34.5 32 / 34 33.5 / 34.5 75 61 58 65 62 0.194 0.212 0.194 0.212 301x828x816 33 150 200

VAM650FA 650 650 93 34.5 / 35.5 34.5 / 35.5 74

VAM800FA 800 800 137 36 / 37 36 / 37

60 63 65 0.380 0.451 0.380 0.451 364x1,004x868 48

VAM1000FA 1,000 1,000 157 36 / 37 36 / 37

VAM1500FA VAM2000FA 1,500 2,000 1,500 2,000 137 39.5 / 41.5 40 / 42.5 40.5 / 41.5 40 / 42.5 75 61 66 0.469 0.864 0.953 0.469 0.864 0.953 364x1,004x1,156 726x1,514x868 726x1,514x1,156 61 132 158 250 350

-15 50 80% or less Heat exchange mode / Bypass mode / Fresh-up mode Air to air cross flow total heat (sensible + latent heat) exchange Specially processed non-flammable paper 1~/50/60/220-240/220 15

Hz/V A

93


UATYQ-CY1

Rooftop - heat pump

Remote Control

UATYQ-CY1

›› ›› ›› ›› ›› ›› ›› ›› ›› ››

Easy to install ‘plug and play’ concept plus single installation configuration; no additional piping is required since indoor and outdoor sides are pre-connected High efficiency and reliable scroll compressor Wide operating range Flat top unit design allows maximum use of warehouse and container space Free cooling and fresh air intake possible with optional economiser Convertible return and supply air: fan can be mounted in two directions Factory pre-charged refrigerant ensures clean and efficient operation Belt driven fan enables air volume and static pressure to be adjusted as required. Adjustable fan pulley as standard to meet a wide range of supply air volumes and external static pressures Anti-corrosion treated coil

Plug and play installation

Heating & Cooling Indoor unit Cooling capacity Heating capacity Power input

Nom. Nom. Cooling Heating

Nom. Nom.

EER COP Evaporator

Air flow rate Cooling External static pressure Evaporator piping Condensation OD connections drain size Condenser Dimensions Unit HxWxD Weight Unit Casing Colour Material Air flow rate Cooling Operation range Cooling Min.~Max. Heating Min.~Max. Sound power level Nom. Refrigerant Type Power supply Phase/Frequency/Voltage

UATYQ250CY1 27.340 24.910 8.140 7.330 3.36 3.40 1,560

UATYQ350CY1 35.580 34.790 10.780 10.840 3.30 3.21 2,030 147

mm kg

1,150x1,638x2,063 445

1,028x2,209x2,113 580

cfm °CDB °CDB dBA

8,230

12,000

kW kW kW kW

l/s Pa

82

Hz/V

Weight Packing Fan Option for

ECONO250AY1 Packed unit

Unit Weight Air flow rate

Height Width Depth

Cooling Nom.

mm mm mm kg kg l/s cfm

UATYQ550CY1 55,690.000 53.930 16.740 15.540 3.33 3.47 3,160

UATYQ600CY1 66.820 61.690 19.650 18.580 3.40 3.32 3,445 206

UATYQ700CY1 72.600 69.610 21.610 21.420 3.36 3.25 3,917

1,302x2,209x2,670 830

1,454x2,209x2,670 970

20,200

21,200

25.4

mm

Economiser option Indoor unit Dimensions

UATYQ450CY1 44.720 41.790 13.040 12.860 3.43 3.25 2,670

1,130x2,209x2,113 1,048x2,209x2,670 610 780 Light grey Electro-galvanised mild steel 12,100 12,900 0~52 -15~20 83 87 R-410A 3~/50/380-415

ECONO350AY1

ECONO450AY1

90

ECONO550AY1

ECONO600AY1

ECONO700AY1

53 165 3,160 6,700 UATYQ550CY1

1,458 1,564 54 166 3,445 7,300 UATYQ600CY1

69 181 3,917 8,300 UATYQ700CY1

534 1,440 1,144 51 152 1,560 3,300 UATYQ250CY1

1,430 1,124 42 140 2,030 4,300 UATYQ350CY1

94

43 141 2,670 5,650 UATYQ450CY1


UATYP-AY1

Rooftop - heat pump

Remote Control

UATYP-AY1

›› ›› ›› ›› ›› ››

Easy to install ‘plug and play’ concept plus single installation configuration; no additional piping is required since indoor and outdoor sides are pre-connected Factory pre-charged refrigerant ensures clean and efficient operation Belt driven fan enables air volume and static pressure to be adjusted as required. Flat top unit design allows maximum use of warehouse and container space High efficiency and reliable scroll compressor Anti-corrosion treated coil

Heating & Cooling Indoor unit Cooling capacity Heating capacity Power input EER COP Evaporator

Nom. Nom. Cooling Heating

Nom. Nom.

Air flow rate Cooling External static pressure Evaporator piping Condensation OD connections drain size Condenser Dimensions Unit HxWxD Weight Unit Casing Colour Material Air flow rate Cooling Operation range Cooling Min.~Max. Heating Min.~Max. Sound power level Nom. Refrigerant Type Power supply Phase/Frequency/Voltage

kW kW kW kW

m³/min Pa mm mm kg

UATYP700AMY1 67.406 74.733 29.200 26.220 2.31 2.85 226

UATYP850AMY1 82.939 92.317 38.160 34.780 2.17 2.65 263

UATYPC10AMY1 101.110 102.290 43.170 41.670 2.34 2.45 312

UATYPC12AMY1 109.609 126.314 48.200 46.800 2.27 2.70 354

294 25.4 1,735x2,250x2,800 1,200

1,974x2,252x3,180 1,350

1,510

cfm °CDB °CWB dBA

Light grey Electro-galvanised mild steel 20,000 20~46 -15~20 -

Hz/V

3~/50/380-415

95

1,600


Air handling units

RANGE A wide standard range covers air flow rates from 500 m3/h up to 124.000 m3/h, with the possibility to choose the most appropriate transverse velocity, depending on the treatment required. In addition, with the same air flow, the flow section (width x height) can be adapted to the dimensional constraints of the installation. All sizes are modularly constructed to facilitate transport and easy assembly on site. With the absence of any welding points the Air Handling Units, on request, can be supplied completely dismantled to allow assembly directly on site. ›› P re-defined sizes Twenty-seven (27) fixed sizes optimized to reach the best compromise between competitiveness and manufacturing standardization. ›› “Infinitely” variable sizes designed to overcome installation constraints where space requirements of the section “width x height” must adapt to the available space. The system gives the possibility to tailor the unit sizes through increments/decrements of 5 cm. CONTROL Upon request all units can be provided with a regulation and control system that can manage the unit independently, or communicate with the external supervision system. Control panel power section, inverters, microprocessor, sensors to measure temperature, humidity and air quality, regulation valves, damper actuators, safety devices and control are just some of the components that can be installed upon request on the machine in order to provide an even more comprehensive product and faster installation.

96


Technical choices All the units were developed by paying special attention to energy efficiency. Exchange surfaces, motor efficiency, filtration, isolation, friction reduction and pressure drop in the air flow inside the Air Handling Units are just some of the most important parameters considered in the development of the design. All of this provides a product ready to be easily inserted in the system and capable of contributing to overall energy savings.

Frame Structure with carrier chassis built with anodized aluminum (suitable for installation in a particularly aggressive atmosphere) or aluminum profiles of 40x40 or 60x60mm sections. There are solutions with thermal break (60x60mm section) or radial profile (suitable for applications in the food sector or in general, where a high level of hygiene is required). All profiles are double chamber type so that the fixing screws are totally concealed and there are no projections inside the Air Handling Units (in compliance with current accidentprevention regulations), and they are also fitted with a gasket to be inserted inside the profile, in a dovetail slot, to ensure maximum seal. The structure is completed with three way connecting, nylon loaded glass joints put on corners while the base, independent for each section, is in extruded aluminum with aluminum pressure diecast corners to facilitate lifting. Panels The closing panels are double sheets, box-folded and can be flat (25 and 46mm thickness) or step type (42 and 62mm thickness). The step panels permit a flat surface inside the unit, ensuring continuity between the panel and the profile. Insulation can be made of polyurethane foam (40 รท 50 kg/m3) or fibrous mineral wool, glued to the panel (90 kg/m3).

Flat panel

Polyurethane foam

Step panel

Aluminium profile with thermal break

Fan-Motor Assembly The Fan-Motor is made with a single structure comprising two aluminum profiles which help to absorb transmitted shock and a motor, mounted on a tensioning slide. The structure never touches on the bottom of the unit because through the aluminum profiles transfer the weight onto the structure of the AHU, ensuring the maximum vibration isolation. With this solution it can be sure that the AHU does not transmit vibrations to any flat surface on which is installed.

Base

Tensioning slide

Structure with two aluminium profiles

97

Corner


Fittings The fasteners are stainless steel, self-tapping screws, located in nylon bosses and retained in the panel with an external cap. This system completely hides the screws in the panel and thanks to the self-fastening and self-centering screws, the tightness over time is ensured. Doors The doors for inspection and internal service can be provided with outward opening or inward opening for pressurized sections. There are solutions with hinges to allow left or right openings, or even the total removal of the door. Portholes The portholes are double-wall type made of polycarbonate and with sealing gaskets. The fastening system that provides the locking screws only enter the polycarbonate structure (and therefore not into the sandwich panel) and the continuous internal-external gasket, prevents the formation of condensation and ensures maximum sealing. Filters Particular attention is paid, during the configuration of the unit, to the position of the filters in the airflow, in order to maximize their effectiveness. All filters are mounted on commercial frames, provided with a seal to ensure effective filtration efficiency. In addition, all units are designed to allow the extraction of the filters from the dirt side in order to avoid possible contamination with the air circuit during maintenance.

FITTINGS

DOORS

PORTHOLES

FILTERS

the fasteners are stainless steel, self-tapping screws, located in nylon bosses and retained in the panel with an external cap. this system completely hides the screws in the panel and thanks to the self-fastening and self-centering screws, the tightness over time is ensured.

the portholes are double-wall type made of polycarbonate and with sealing gaskets. the fastening system that provides the locking screws only enter the polycarbonate structure (and therefore not into the sandwich panel) and the continuous internal-external gasket, prevents the formation of condensation and ensures maximum sealing.

COMPONENTS FILTER • Synthetic pleated filter • Flat filter aluminum mesh / SST 304 • Rigid / Soft bag filter • High efficiency filter • Carbon absorption / deodorizing filter EXCHANGERS • Water coils • Steam coils • Superheated water coils • Direct expansion coil • Electric coils

Humidifiers ›› Surface evaporation humidifier-constant loss water ›› Surface evaporation humidifier with re-circulating pump ›› Water spray humidifier constant loss water ›› Water spray humidifier with re-circulating pump ›› Steam humidifier with network distribution ›› Steam humidifier with local distributor ›› Atomized water spray humidifier

HUMIDIFIERS • Surface evaporation humidifier - constant loss water • Surface evaporation humidifier with re-circulating pum • Water spray humidifier - constant loss water • Water spray humidifier with re-circulating pump • Steam humidifier with network distribution • Steam humidifier with local distributor • Atomized water spray humidifier FANS • Forward curved fan • Backward curved fan • Plug fan (also available with direct coupling) Fastening

system Internal-external gasket

Fans ›› Forward curved fan ›› Backward curved fan ›› Plug fan (Also available with direct coupling) HEAT RECOVERY SYSTEMS ›› Heat wheel, sensible or enthalpy type ›› Cross-flow heat cube ›› Run-around coils OTHER SECTIONS ›› Attenuator section ›› Mixing box section with actuator or manual dampers ›› Empty section ›› Gas burner section ›› Factory mounted controls incl. Inverters

« Offering a complete range: from standard model sizes to customised solutions. » 98

Particular a unit, to the maximize th all filters ar a seal to en all units are from the d with the air

Hinges (left or right openings, or even the total removal of the door)

Available Components Filter ›› Synthetic pleated filter ›› Flat filter aluminum mesh / stainless steel 304 ›› Rigid / Soft bag filter ›› High efficiency filter ›› Carbon absorption /  deodorizing filter Exchangers ›› Water coils ›› Steam coils ›› Superheated water coils ›› Direct expansion coil ›› Electric coils

the doors provided w pressurized allow left o the door.



PLUG and PLAY VRV® connection AHU

Air Handling Units for ›› VRV Indoor units and Air Handling Units on single VRV system ›› Monovalent cooling and heating for Air Handling Units ›› Air Handling Unit connection like standard VRV indoor unit ›› Factory engineered and mounted controls ›› Constant and comfortable supply air temperature control ›› Fast and easy installation ›› Standard DAIKIN warranty

With the new DAIKIN “PLUG and PLAY” VRV connection

In addition the Daikin Inverter technology for step-less

system VRV indoor units and Air Handling Units for

and efficient capacity control combined with the high-

fresh air treatment can be connected to the same re-

ly sophisticated factory engineered and mounted Air Han-

frigerant line, resulting in enhanced design flexibility

dling Unit controls are ensuring constant and comfort-

and increased energy efficiency. Both fresh air treat-

able supply air temperature.

ment and air conditioning can be achieved successfully

Last but not least not to forget about the business ad-

in a single direct-expansion system via DAIKIN VRV

vantages in which the DAIKIN “PLUG and PLAY” VRV con-

technology without the usual design problems of need-

nection will put you. The possibility of connecting the Air

ing VRV system for air conditioning and separate individ-

Handling Units together with the standard VRV indoor

ual heating and cooling systems just for the Air Handling

units in a monovalent heating and cooling VRV system

Units.

gives you the opportunity to completely get rid off the

The factory engineered and mounted controls package of

fossil fuel burning boilers, the chillers and the water piping

the Air Handling Units assures a fast and easy “PLUG and

from your projects and so reduce the total investment

PLAY” connection of the Air Handling Units just like a

cost significantly.

standard VRV indoor unit.

Altogether, the Daikin “PLUG and PLAY” VRV connection

This innovation brings a total monovalent direct-

system offers you the most efficient, easiest to install tech-

expansion solution to the heating, cooling and fresh

nology with lowest investment costs for the cooling and

air treatment demands of air conditioning applications.

heating needs of your air conditioning projects.

100


Factory engineered and mounted controls For all Air Handling Units of the “PLUG and PLAY” VRV connection system a factory engineered and factory mounted controls package is included.

This package consists of: ›› Expansion valve kits EKEXV which are already mounted inside the unit so that only the refrigerant piping has to be connected. ›› Factory mounted control equipment for the AHU like temperature-, pressure sensors, dampers … ›› Control panel to control the whole AHU based on supply temperature including EKEQMCB boxes. This assures a fast and easy “PLUG and PLAY” connection of the Air Handling Units to a VRV system just like a standard VRV indoor unit. The possibility of operating the Air Handling Unit by using standard DAIKIN remote control greatly simplifies overall system control. Using a centralized remote control enables the user to choose from a wide range of control systems that integrate air conditioning and ventilation in a single control system structure.

Standardized preconfigured Air Handling Units The following preconfigured Air Handling Units are especially designed to meet the requirements which go along with the “PLUG and PLAY” VRV connection system as well as to assure maximum energy efficiency and comfort level for standard air conditioning applications.

Preconfigured Air Handling Unit

+ 101

Factory mounted controls


Standard spec. supply air only units for cooling only applications These units are single air stream (Supply fan only) with integrated mixing box (0-100% fresh air) and can operate, if connected to DAIKIN VRV outdoor unit, in cooling mode only. Structure: Natural aluminum frame 40mm, Flat panel 25mm with foam insulation (40 ÷ 50 kg/m3), Skin material external Grey plastisol 0,7mm, Skin material internal galvanized 0,5mm Components in Order of the direction of air flow: 1) Mixing box with dampers including 1 x louver, 1 x flexible connection and factor fitted actuators, 2) F5 bag filter with factory mounted differential pressure gauge and hinged door, 3) Section for factory mounted expansion valve kits EKEXV 4) Direct expansion cooling coil with galvanized drain pan and droplet eliminator, 5) Supply fan (incl. hinged door, porthole, drive screen, mounted and wired light and on/off switch), 6) Flexible connection, 7) 150 mm base frame

Air flow m3/h Width Height Length Weight Cooling capacity total Cooling capacity sensible External static pressure Max. Power input fan

mm mm mm kg kW kW Pa kW

Included VRV connection kit Capacity index

2.000

3.000

4.000

6.000

8.000

10.000

12.000

950 800 3030 ~ 300 20,60 10,90 450 1,10

1000 930 3250 ~ 350 28,80 16,40 450 1,50

1150 950 3590 ~ 400 40,70 22,00 450 2,20

1350 1050 3360 ~ 470 58,70 32,90 450 3,00

1550 1050 3680 ~600 83,40 43,40 450 5,50

1550 1250 3950 ~700 100,30 55,20 450 5,50

1650 1300 4050 ~700 117,30 65,70 450 7,50

1 x EKEXV200 1 x EKEQMCB

1 x EKEXV250 1 x EKEQMCB

2 x EKEXV200 2 x EKEQMCB

2 x EKEXV250 2 x EKEQMCB

3 x EKEXV250 3 x EKEQMCB

4 x EKEXV200 4 x EKEQMCB

4 x EKEXV250 4 x EKEQMCB

1 x 184

1 x 257

2 x 182

2 x 262

3 x 248

4 x 224

4 x 262

Conditions: Outside air: Summer 35°C/50% r.H.; Supply air: Summer 19°C 1) Height including 150 mm Base frame 2) Width and Height without factory mounted control panel 3) EKEXVs mounted inside Air Handling unit. EKEQMCB mounted inside control panel 4) Maximum Connection Ratio (CR) of the total VRV system: 110% 5) Sum of Capacity Indexes of EKEXVs must not exceed 30% when used in a system with other indoor units

102


High spec. supply air only units for cooling only applications These units are single air stream (Supply fan only) with integrated mixing box (0-100% fresh air) and can operate, if connected to DAIKIN VRV outdoor unit, in cooling mode only. Structure: Natural aluminum frame 40mm, Step panel 42mm with mineral wool insulation (90 kg/m3), Skin material external Grey plastisol 0,7mm, Skin material internal galvanized 0,5mm Components in Order of the direction of air flow: 1) Mixing box with dampers including 1 x louver, 1 x flexible connection and factor fitted actuators, 2) Combined filter section G4 pre filter F7 bag filter with factory mounted differential pressure gauge and hinged door, 3) Section for factory mounted expansion valve kits EKEXV 4) Direct expansion cooling coil with galvanized drain pan and droplet eliminator, 5) Supply fan (incl. hinged door, porthole, drive screen, mounted and wired light and on/off switch), 6) Empty section, 7) Sound attenuator 500 mm, 8) F9 bag filter with factory mounted differential pressure gauge and hinged door, 9) Flexible connection, 10) 150 mm base frame

Air flow m3/h Width Height Length Weight Cooling capacity total Cooling capacity sensible External static pressure Max. Power input fan

mm mm mm kg kW kW Pa kW

Included VRV connection kit Capacity index

2.000

3.000

4.000

6.000

8.000

10.000

12.000

950 800 4820 ~ 500 20,6 10,9 450 1,50

1000 930 4980 ~ 570 28,8 16,4 450 2,20

1150 950 4970 ~ 650 40,7 22 450 3,00

1350 1050 5210 ~ 780 58,70 32,90 450 4,00

1550 1050 5310 ~ 860 83,40 43,40 450 5,50

1650 1250 5780 ~ 1080 100,30 55,20 450 7,50

1650 1300 5770 ~ 1170 117,30 65,70 450 11,00

1 x EKEXV200 1 x EKEQMCB

1 x EKEXV250 1 x EKEQMCB

2 x EKEXV200 2 x EKEQMCB

2 x EKEXV250 2 x EKEQMCB

3 x EKEXV250 3 x EKEQMCB

4 x EKEXV200 4 x EKEQMCB

4 x EKEXV250 4 x EKEQMCB

1 x 184

1 x 257

2 x 182

2 x 262

3 x 248

4 x 224

4 x 262

Conditions: Outside air: Summer 35째C/50% r.H.; Supply air: Summer 19째C 1) Height including 150 mm Base frame 2) Width and Height without factory mounted control panel 3) EKEXVs mounted inside Air Handling unit. EKEQMCB mounted inside control panel 4) Maximum Connection Ratio (CR) of the total VRV system: 110% 5) Sum of Capacity Indexes of EKEXVs must not exceed 30% when used in a system with other indoor units

103


Standard spec. supply and return air units for cooling / heating applications These units are double air stream (Supply and Return fan) with integrated mixing box (0-100% fresh air), heat recovery system (Pleat heat exchanger or rotary wheel) and can operate, if connected to DAIKIN VRV outdoor unit, in cooling and heating mode. Structure: Natural aluminum frame 40mm, Flat panel 25mm with foam insulation (40 ÷ 50 kg/m3), Skin material external Grey plastisol 0,7mm, Skin material internal galvanized 0,5mm Components in Order of the direction of air flow: Supply air stream: 1) Dampers section including 1 x louver, and factor fitted actuators, 2) F5 bag filter with factory mounted differential pressure gauge and hinged door, 3) Heat recovery system (Pleat heat exchanger or rotary wheel), 4) Mixing box with damper and factor fitted actuators, 5) Direct expansion cooling coil with galvanized drain pan and droplet eliminator, 6) Supply fan (incl. hinged door, porthole, drive screen, mounted and wired light and on/off switch), 7) Flexible connection, 8) 150 mm base frame Return air stream: 1) G4 flat filter with factory mounted differential pressure gauge and hinged door, 2) Return fan (incl. hinged door, porthole, drive screen, mounted and wired light and on/off switch), 3) Mixing box with damper and factor fitted actuators, 4) Heat recovery system (Pleat heat exchanger or rotary wheel), 5) Dampers section including 1 x louver, and factor fitted actuators

Air flow m3/h Width Height Length Weight Cooling capacity total Cooling capacity sensible Heating capacity total External static pressure Max. Power input supply fan Max. Power input return fan Included VRV connection kit Capacity index

mm mm mm kg kW kW kW Pa kW kW

2.000

3.000

4.000

6.000

8.000

10.000

12.000

950 1450 2960 ~ 550 20,6 10,9 11,25 450 1,10 1,10

1000 1710 3440 ~ 680 28,8 16,4 16,50 450 2,20 1,50

1150 1750 3190 ~ 700 40,7 22 21,30 450 2,20 2,20

1350 1950 3330 ~ 900 58,70 32,90 32,26 450 4,00 3,00

1550 1950 3730 ~ 1020 83,40 43,40 44,40 450 5,50 4,00

1650 2350 3700 ~ 1270 100,30 55,20 57,91 450 5,50 5,50

2000 2350 4020 ~ 1560 117,30 65,70 78,31 450 11,00 7,50

1 x EKEXV200 1 x EKEQMCB

1 x EKEXV250 1 x EKEQMCB

2 x EKEXV200 2 x EKEQMCB

2 x EKEXV250 2 x EKEQMCB

3 x EKEXV250 3 x EKEQMCB

4 x EKEXV200 4 x EKEQMCB

4 x EKEXV250 4 x EKEQMCB

1 x 184

1 x 257

2 x 182

2 x 262

3 x 248

4 x 224

4 x 262

Conditions: Outside air: Summer 35°C/50% r.H., Winter -15°C/90% r.H.; Supply air: Summer 19°C, Winter 26°C 1) Height including 150 mm Base frame 2) Width and Height without factory mounted control panel 3) EKEXVs mounted inside Air Handling unit. EKEQMCB 4) Maximum Connection Ratio (CR) of the total VRV system: 110% 5) Sum of Capacity Indexes of EKEXVs must not exceed 30% when used in a system with other indoor units

104


High spec. supply and return air units for cooling / heating applications These units are double air stream (Supply and Return fan) with integrated mixing box (0-100% fresh air), heat recovery system (Pleat heat exchanger or rotary wheel) and can operate, if connected to DAIKIN VRV outdoor unit, in cooling and heating mode. Structure: Natural aluminum frame 40mm, Step panel 42mm with mineral wool insulation (90 kg/m3), Skin material external Grey plastisol 0,7mm, Skin material internal galvanized 0,5mm Components in Order of the direction of air flow: Supply air stream: 1) Dampers section including 1 x louver, and factor fitted actuators, 2) Combined filter section G4 pre filter F7 bag filter with factory mounted differential pressure gauge and hinged door, 3) Heat recovery system (Pleat heat exchanger or rotary wheel), 4) Mixing box with damper and factor fitted actuators, 5) Direct expansion cooling coil with galvanized drain pan and droplet eliminator, 6) Supply fan (incl. hinged door, porthole, drive screen, mounted and wired light and on/off switch), 7) Empty section, 8) Sound attenuator 500 mm 9) F9 bag filter with factory mounted differential pressure gauge and hinged door 10) Flexible connection, 11) 150 mm base frame Return air stream: 1) F6 bag filter with factory mounted differential pressure gauge and hinged door, 2) Return fan (incl. hinged door, porthole, drive screen, mounted and wired light and on/off switch), 3) Mixing box with damper and factor fitted actuators, 4) Heat recovery system (Pleat heat exchanger or rotary wheel), 5) Dampers section including 1 x louver, and factor fitted actuators

Air flow m3/h Width Height Length Weight Cooling capacity total Cooling capacity sensible Heating capacity total External static pressure Max. Power input supply fan Max. Power input return fan Included VRV connection kit Capacity index

mm mm mm kg kW kW kW Pa kW kW

2.000

3.000

4.000

6.000

8.000

10.000

12.000

950 1450 4740 ~ 830 20,6 10,9 11,25 450 1,50 1,10

1000 1710 5170 ~ 990 28,8 16,4 16,50 450 2,20 1,50

1150 1750 4900 ~ 1070 40,7 22 21,30 450 3,00 2,20

1350 1950 5050 ~ 1301 58,70 32,90 32,26 450 4,00 3,00

1550 1950 5560 ~ 1520 83,40 43,40 44,40 450 5,50 4,00

1650 2350 5580 ~ 1835 100,30 55,20 57,91 450 7,50 5,50

1650 2350 5760 ~ 2230 117,30 65,70 78,31 450 11,00 7,50

1 x EKEXV200 1 x EKEQMCB

1 x EKEXV250 1 x EKEQMCB

2 x EKEXV200 2 x EKEQMCB

2 x EKEXV250 2 x EKEQMCB

3 x EKEXV250 3 x EKEQMCB

4 x EKEXV200 4 x EKEQMCB

4 x EKEXV250 4 x EKEQMCB

1 x 184

1 x 257

2 x 182

2 x 262

3 x 248

4 x 224

4 x 262

Conditions: Outside air: Summer 35°C/50% r.H., Winter -15°C/90% r.H.; Supply air: Summer 19°C, Winter 26°C 1) Height including 150 mm Base frame 2) Width and Height without factory mounted control panel 3) EKEXVs mounted inside Air Handling unit. EKEQMCB mounted inside control panel 4) Maximum Connection Ratio (CR) of the total VRV system: 110% 5) Sum of Capacity Indexes of EKEXVs must not exceed 30% when used in a system with other indoor units

105



OPTIONS & ACCESSORIES Chillers Fan coil units Ventilation

108 112 114

107


Options - chillers Integrated Hydronics Type

Compr.

Refr

SWING

R-410A

Air Cooled

R-410A

SCROLL R-407C

CondenWater serless Cooled chiller

R-410A

Mode

Reference

Products

EWAQ-ACV3 EWYQ-ACV3 EWAQ-ACV3 EWAQ-ACW1 EWYQ-ACV3 EWYQ-ACW1 EUWAC-FBZW1 EUWAN-KBZW1 EUWAP-KBZW1 EUWAB-KBZW1 EUWYN-KBZW1 EUWYP-KBZW1 EUWYB-KBZW1 EWAQ-DAYNN EWYQ-DAYNN

005-006-007 005-006-007 009-010-011 009-011-013 009-010-011 009-011-013 5-8-10 5-8-10-12-16-20-24 5-8-10-12-16-20-24 5-8-10-12-16-20-24 5-8-10-12-16-20-24 5-8-10-12-16-20-24 5-8-10-12-16-20-24 080-100-130-150-180-210-240-260 080-100-130-150-180-210-240-260

SCROLL

R-407C

EWWP-KBW1N

014-022-028-035-045-055-065

SCROLL

R-407C

EWLP-KBW1N

012-020-026-030-040-055-065

Nomenclature for air-cooled B and C series: E W A D 4 1 2 3 4 5

6 6

0 7

B 8

Z X S 9 10 11

9 Inverter -: non-inverter Z: inverter

Description

code

Total heat recovery Total heat recovery 1 circuit Partial heat recovery Direct on line starter Wye delta starter (y - d) Soft starter Heat pump version Brine version Double set point Compressor thermal relays Fans circuit breakers with thermal overload relays Phase monitor Inverter compressor starter Under / overvoltage control Energy meter Capacitors cosfi 0.9 Current limit - display Evaporator victaulic kit Evaporator flange kit Evaporator Marine WaterBox VICTAULIC (1 Pass) Evaporator marine waterbox victaulic (2 step) Evaporator marine waterbox victaulic (3 step) Evaporator Marine WaterBox FLANGED (1 Pass) Evaporator marine waterbox flanged (2 step) Evaporator marine waterbox flanged (3 step) Condenser double flanges kit Evaporator water side design pressure 10 bar Evaporator water side design pressure 25 bar 20 mm evaporator insulation Axial fans 100 pa lift Axial fans 250 pa lift 20mm condenser insulation Fan silent mode Fans speed control device (phase cut on fan) Condenser victaulic kit Condenser flange kit Condenser Marine WaterBox VICTAULIC (1 Pass) Condenser Marine WaterBox VICTAULIC (2 Passes) Condenser Marine WaterBox VICTAULIC (3 Passes) Condenser Marine WaterBox FLANGED (1 Pass) Condenser Marine WaterBox FLANGED (2 Passes) Condenser Marine WaterBox FLANGED (3 Passes) Speedtrol (fan speed control device - on/off - up to -18°c) Condenser coil guards Evaporator area guards Cu-cu condenser coil Cu-cu sn condenser coil Condenser water side design 16 bar Condenser water side design 21 bar Alucoat fins coil Cu-ni 90-10 condenser tubes

01 02 03 04 05 06 07 08 10 11 12 13 14 15 16 17 19 20 21 22a 22 23 24a 24 25 26 27 28 29 30 32 33 34 35 36 37 38a 38 39 40a 40 41

10 Efficiency level S: Standard X: High P: Premium

Twin pump contact

Single pump

Twin pump

High ESP pump

OPSC

OPTC

OPSP

OPTP

OPHP

STD STD STD STD STD STD

• •

• •

• •

• •

• • • •

• •

(s) OP12 & OP03 need to be added to meet Swedish national law 1992: 16 (1) Impossible option combination: OPZH+OPZL (2) Not available with option OPLN

11 Sound level S: Standard L: Low R: Reduced

EWAQ~BA EWAD-BZ EWWD~G-XS EWWD~I-XS EWWD-J-SS EWAD~CZ EWAD~CF EWWQ~B- EWAD~D- EWAD~E- ERAD~EEWLD~G-SS EWLD~I-SS EWWD~FZXS EWAD~CEWWD~HEWYQ~BA EWYD-BZ EWWD~G-SS EWWD~I-SS EWLD-J-SS Option Option Option

Option STD STD STD STD Option Option Option STD

Option

Option (1) Option Option (1) Option Option (1) Option

Option

Option

Option

Option

STD Option

STD Option

STD Option

STD Option

STD Option

Option STD STD

Option STD Option

Option STD Option

STD

STD

Option STD Option STD STD

Option STD Option STD STD

Option STD Option

STD STD Option Option

Option STD Option STD STD

STD Option Option Option STD Option STD

STD

Option

Option STD Option

Option

STD

Option Option Option Option

Option Option Option Option STD

STD

STD

STD (14) STD (15)

Option Option Option

Option

Option

Option Option Option Option

Option Option Option Option

Option Option Option Option STD (2) Option (2)

Option Option Option Option

Option Option Option Option

STD

Option Option (2) Option cf cf Option Option Option cf Option

1. Heat exchangers are placed in series 2. Please note the following option availability: - Group 1: EWAD180-200D-SL; EWAD180-190D-SR; EWAD210D-SX; EWAD200-210D-HS - Group 2: all other models Group 1 Group 2 Option 20 N/A STD Option 21 N/A Option Option 29 STD Option 3. Option 42 is ‘N/A’ for EWAD-D-SX version

Option

Option

Option

Option

Option

STD Option

STD Option Option Option STD

STD Option

STD Option

Option STD

STD

STD

Option STD Option STD STD

Option

Option STD

STD

Option

Option

Option

Option

Option Option Option Option STD

Option STD Option Option

Option Option Option Option STD

STD Option Option

Option STD STD Option Option Option Option Option Option Option Option STD Option STD

Option Option Option Option STD Option

STD

STD Option Option Option STD Option

STD CF Option Option Option Option STD

STD Option Option Option Option STD

Option Option Option Option STD

STD

STD

Option

Option

Option

Option

Option

STD Option Option Option Option Option Option Option

STD (17)

STD Option Option Option Option Option Option

Option

Option

Option

Option

Option Option

Option Option

Option Option

Option Option Option Option

Option

STD CF Option Option STD Option

Option

Option

STD

STD

STD Option

Option

Option

Option

Option

CF

STD (1)

STD

Option

4. Option 56 is ‘STD’ for EWAD180-200D-SL; EWAD180-190D-SR; EWAD200-210D-HS 5. One ‘High pressure side manometer’ per circuit 6. * Low lift 8m – high lift 12m (nominal condition) * Option 80/81 is ‘N/A’ for EWAD180-190D-SR; 78/79/80/81 is ‘N/A’ for EWAD-D-SX version 7. Option 99 is ‘STD’ for EWAD-D-SX version 8. Not available for 2 smallest models 9. Not available for high efficiency range 10. Tank delivered separately

108

Option Option Option Option STD

Option (3) Option

Option Option

Option Option Option Option STD

Option

STD Option

Option (9)

STD

STD

42 43 44 45 46 47 48 49 50

Single pump contact

Option

11. Not available for standard efficiency range 13. Only available for EWAD~BZ range 14. Fan silent mode is an option for EWYD~BZSS 15. Only for EWYD~BZSL, option for EWYD~BZSS 16. Not available for EWYD~BZ 17. Not available for condenserless range 18. Only available for condenserless range * Option 76 is standard available for the versions with reduced / extra low sound level


Noise & Head Pressure Control

LWE

Electrical

Buffer tank

Low noise

Inverter fans

High ESP fans

High Glycol

Low Glycol

Evaporator heater tape

OPBT

OPLN

OPIF

OPHF

OPZH

OPZL

OP10

Main switch

Refrigerant

Condenser

A / V meter

Dual pressure relief valve

Suction stop valve

Coil guards

OP52

OP57

OP03

OP12

OPCG

STD STD

• •

• •

•(s) •(s)

• •

STD STD STD STD STD STD • • • • • •

STD

STD • •

Description

• •

• • • • • • •

• • • • • • • • •

•(2) •(2)

code

• • • • • • • •

EWWD-J-SS EWAQ~BA EWAD-BZ EWWD~G-XS EWWD~I-XS EWLD~I-SS EWWD~FZXS EWAD~CEWWD~HEWAD~CZ EWAD~CF EWWQ~B- EWAD~D- EWAD~E- ERAD~EEWLD~G-SS EWYQ~BA EWYD-BZ EWWD~G-SS EWWD~I-SS EWLD-J-SS

Condenser 1 pass (dt 4-8 °c) 51 Condenser 2 passes (dt 4-8 °c) 52 Condenser 2 passes (dt 9-15 °c) 53 Condenser 3 passes 53b Condenser 4 passes 54 Water pressure differential switch on condenser 55 Water pressure differential switch on evaporator 56 Evaporator electric heater 57 Option STD STD Evaporator flow switch 58 Option Option Condenser flow switch 59 Electronic expansion device 60 STD STD Discharge line shut off valve 61 STD STD Suction line shut off valve 62 STD Option High pressure side manometers 63 Option Option Low pressure side manometers 64 STD Additional capacity reduction steps 65 Ambient outside temperature sensor 67 STD and set-point reset Hour run meter 68 STD STD General fault contactor 69 STD STD Container kit 71 Option Option Fork-lift kit 72 Wooden box packing 74 Rubber anti vibration mount 75 Option Option Sound proof system* 76 Spring anti vibration mount 77 Option Option One centrifugal pump (low lift) 78 Option Option One centrifugal pump (high lift) 79 Option Option Two centrifugal pumps (low lift) 80 Option Option Two centrifugal pumps (high lift) 81 Option Witness test 82 External tank without cabinet (500 l) 83 Option External tank without cabinet (1000 l) 84 Option External tank (500 l) with cabinet RAL7032 87 Option External tank (1000 l) with cabinet RAL7032 88 Option Acoustic test 89 Set-point reset, 90 Option STD demand limit and alarm from external device Double pressure relief valve with diverter 91 Option Option Low ambient kit for 1 circuit 93 Low ambient kit for 2 circuits 94 Compressor circuit breakers 95 Option Fans circuit breakers 96 STD Main switch interlock 97 STD (16) STD Emergency stop 98 Option Fan speed regulation 99 STD (16) Option Refrigerant recovery tank 100 Option Evaporator right water connection 101 Option Ground fault relay 102 Option Evaporator 1pass 103 Evaporator 2 passes 103a Evaporator 3 passes 103b Evaporator Double Flange Kit 104 Liquid receiver 105 Rapid restart 110 Option High temperature kit 111 Transport kit 112 Option Option Option Glycol function .. Option Optimized free cooling ..

STD (9) STD (11) Option (9)

Option (4) STD STD Option Option

Option

Option Option

STD STD Option Option Option

STD STD STD Option STD STD Option STD STD STD Option (5) Option STD

STD STD STD

Option

STD STD Option

Option Option

Option Option

Option Option Option

Option

STD

STD STD Option

STD STD Option

Option

Option

Option

STD STD (9)

STD STD

STD (17) STD Option

Option

Option Option STD Option Option STD

STD Option Option STD

STD STD (11) STD STD STD STD Option Option Option

STD STD Option

STD STD Option

Option

Option Option

STD STD Option

Option Option STD

Option

STD

Option

Option STD

STD

Option STD Option STD STD Option STD

STD STD STD STD STD Option

Option Option STD STD Option Option Option

STD

Option Option

Option Option

STD STD

STD STD Option

STD STD

STD STD Option

Option Option Option

Option Option

Option

Option Option

Option Option

CF

Option

CF

Option Option Option Option (6) Option (6) cf Option Option Option Option cf

CF

CF

CF

CF

CF

STD

STD

Option

STD

STD

STD

STD

STD

STD

STD

STD

Option

STD

Option

STD

Option

Option

Option

Option

Option

Option

Option

STD

Option

Option

Option

Option STD STD

Option STD STD

Option STD STD

Option

Option

Option

STD STD

STD STD

CF

Option Option STD Option Option

Option CF

Option STD STD STD Option

Option Option Option Option Option (8) Option (8) cf cf Option Option Option Option cf cf

Option

STD STD Option Option STD

Option STD

Option Option Option CF

CF

CF

CF

CF

CF

STD Option Option Option Option

Option (7)

Option Option STD

STD Option STD

Option

Option

Option

Option Option

Option

Option

Option

109

Option

Option

Option

Option

Option

Option

Option

Option

Option

Option Option


Accessories - chillers Air cooled chillers EWA/YQ009-011ACV3 EWA/YQ009-013ACW1 Panels EKDSSP EKDSSP-S*** EKDDSP EKPWPRO EKPWPROM Serial Cards & Comm. Modules EKAC10C EKACPG EKAC200A EKAC200J EKACBAC EKACLON EKACLONP EKACRS232 EKACWEB EKACBACMSTP EKACBACCERT EKCM200J EKCMLON EKCMBACMSTP EKCMBACIP LON Gateway EKLONPG Other Systems & Accessories EKCLWS EKCON EKCONUSB EKMODEM EKGSMOD EKRP1HB EKRUPCJ EKRUPCK EKRUPCS EKPV2J EKPWPROEXT EKGWWEB EKGWMODEM EKBNPG EKBMSBNA EKBMSMBA EKRUMCA EKRUPC EKRUPG EHMC*AV1010 EHMC*AV1080 EKRP1AHTA DTA104A62 EKRUAHTB Gauges EKGAU5/8KA EKGAU10/12KA EKGAU16KA EKGAU20/24KA BHGP26A1 Soft starter EKSS Buffer tank EKBT Waterpipe kit EKGN210

EUWAC-FBZW1

EUWA/Y*-KBZW1

EWA/YQ~BA*

EWAD~D-

EWA(Y)D~BZ

• •

EWAD~C-

• • • •

• • • •

• • • •

• • • • •

• •

• • •

• •

• • • • (5-8) • (10-12) • (16) • (20-24)

• • • (080-210) • (EWAQ240-260DAYN & EWYQ230-250DAYN)

EKGN260 * To install EKRUMCA => EKAC10C needs to be installed on the unit.

EWA/YQ-DAYN

* EKAC10C allows direct connection to MODBUS BMS system

110

* To install EKLONPG & EKBNPG => EKACPG needs to be installed on the unit.


Water cooled chillers EWAD~CZ

EWAD-CF

• •

• •

EWWP-KBW1N

EWLP-KBW1N

Centrifugals

EWW(L)D~G-

EWW(L)D~I-

EWWD~H-

EWWQ~B-

EWW(L)D~J-

EWWD~FZXS

• •

• •

• •

• •

• •

• • • •

• • • •

• • • •

• • • •

• • • •

• •

• (014-045)

• • •

• • • •

• • • •

• • • •

• • • • • • • •

• • • •

• • • •

• • • •

• • • •

• • • •

DWSC & DWDC

• (012-030)

111

• • •


Options - fan coil units Type: FWM-DT/DF, FWL-DT/DF, FWV-DT/DF Description Additional single row heat exchanger Electric heater 2-pipe 3-way valve 4-pipe 3-way valve Fan stop thermostat Air intake & discharge grille Supporting feet Supporting feet + grille Fresh air intake Rear panel Control electromechanical Electronic controller Master slave option Vertical drainpan Horizontal drainpan Temperature sensor kit Relative humidity sensor kit On board FCU controller installation kit Wall mounting kit (spacing collar) for FWEC*A

1

2

3

4

ESRH02A6 EEH01A6 EEH02A6 E2MV03A6 E4MV03A6

ESRH03A6 EEH03A6

EAIDF02A6

EAIDF03A6 ESFV06A6 ESFVG3A6 EFA3A6 ERPV3A6

ESFVG2A6 EFA2A6 ERPV2A6

Type: FWB-BT Description Additional heat exchanger 3-way valve add. h/e 3-way valve cooling h/e 2-way valve add. h/e 2-way valve cooling h/e Electric Heater Fan stop thermostat Master slave interface Electronic controller Temperature sensor kit Relative humidity sensor kit On board installation kit Wall mounting kit (spacing collar) for FWEC*A

6

10 ESRH10A6 EEH10A6 E2MV10A6 E4MV10A6 EAIDF10A6 ESFV10A6 ESFVG10A6 EFA10A6 ERPV10A6

ESFVG6A6 EFA6A6 ERPV6A6 ECFWMB6 FWEC1A, FWEC2A, FWEC3A EPIMSB6 EDPVA6 EDPHA6 FWTSKA FWHSKA FWECKA FWFCKA

FWV

FWL

FWM

x x x x x x x x x x x x x x x x x

x x x x x x x x x x x x x x x

x x x x x x x x x x x x x x x

2-4

5-7

8-10

EAH04A6

EAH07A6

EAH10A6 E2MV310A6

E2MV307A6 Factory mounted E2MV207A6

E2MV210A6 Factory mounted Factory mounted YFSTA6 EPIMSB6 FWEC1A, FWEC2A, FWEC2A FWTSKA FWHSKA FWECKA FWFCKA

Type: FWB-JT/JF Description 2-pipe 3-way valve 4-pipe 3-way valve Electronic controller

8

ESRH06A6 EEH06A6 E2MV06A6 E4MV06A6 YFSTA6 EAIDF06A6

02 - 11 MCWCN MCWHN (3)

FWEC1A, FWEC2A, FWEC3A

Master slave interface

EPIMSB6

Temperature sensor kit

FWTSKA

Relative humidity sensor kit

FWHSKA

Wall mounting kit (spacing collar) for FWEC*A

FWFCKA

Type: FWD-AT/AF Description Electric heater: small (1) Electric heater: big 2-pipe 3-way valve (2) 4-pipe 3-way valve Vertical Drainpan Horizontal Drainpan Fan stop thermostat Fresh air intake Electronic controller (3) Power interface Master slave interface Temperature sensor kit Relative humidity sensor kit Wall mounting kit (spacing collar) for FWEC*A

4

6

EDEH04A6 EDEH04A6 ED2MV04A6 ED4MV04A6

EDEHS06A6 EDEHB06A6

8

EDMFA04A6

EDMFA06A6

10

EDEHS10A6 EDEHB10A6 ED2MV10A6 ED4MV10A6 EDDPV10A6 EDDPH10A6

12 EDEHS12A6 EDEHB12A6 ED2MV12A6 2xED2MV12A6

YFSTA6 EDMFA10A6 EDMFA12A6 FWEC1A, FWEC2A, FWEC3A -

Requires electronic controller For FWD 12,16,18AT/AF only motor valve (piping not included) Water probe included Optional, electrical installation box with earth terminal KJB212A is required, if controller wires need to be installed in the wall. Requires electrical installation box with earth terminal KJB311A. Requires electrical installation box KJB411A. Requires installation box KRP1H98. (FWC) Requires installation box KRP1BA101 (FWF) Requires electrical installation box with earth terminal KJB212A, if built in the wall. Requires valve control PCB EKRP1C11 I-touch: • Not allowed to use the i-touch for an installation with both fan coils and VRV units. • Can not be used in combination with fan coil units, that use MOD bus communication. • No Airnet or telephone connection possible. 12. Only 1 of these 4 options can be installed on 1 indoor unit. 13. Max. 1 KRP1H98 box can be mounted on the unit. Max. 2 PCB’s can be mounted in 1 KRP1H98 box. (FWC) 14. Max. 2 KRP1BA101 boxes can be mounted on the unit. Max. 1PCB can be mounted in 1 KRP1BA101 box. (FWF)

112

18

EDEHS18A6 EDEHB18A6 ED2MV18A6 2 x ED2MV18A6 EDDPV18A6 EDDPH18A6 EDMFA18A6 EPIB6

EPIMSB6 FWTSKA FWHSKA FWFCKA

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.

16


TYPE Description Decoration Panel (RAL 9010 - grey sealings) 4-way blow Decoration Panel - Standard (RAL 9010 - grey sealings) Round flow Decoration Panel - White (RAL 9010 - white sealings) Round flow Sealing member of air discharge outlet Panel spacer Long-life filter Fresh air intake kit - Direct installation type Fresh air intake kit (20% fresh air) - Direct installation type Remote controller - Wireless - H/P Remote controller - Wireless - C/O Remote controller - Wired Central remote controller Electrical box with earth terminal (3 blocks) Unified on/off controller Electrical box with earth terminal (2 blocks) Schedule timer Wiring adapter for electrical appendices (1) Wiring adapter for electrical appendices (2) Installation box for adapter PCB Remote sensor Intelligent touch controller Electrical installation box Optional PCB for MOD-bus connection 2-way valve - On/Off 3-way valve - On/Off Valve control PCB Remote “On/Off” and “forced off” kit

Description Standard wired remote controller with LCD Simplified wired remote controller (cooling only) Simplified wired remote controller (heat pump) Wireless controller for cooling only Wireless controller for heat pump Decoration panel (600x600) including wireless controller H/P 2pipes Decoration panel (900x900 / 2-pipe) including wireless controller H/P 2pipes Decoration panel (900x900 / 4-pipe) including wireless controller H/P 4pipes 2-pipe 3-way valve 2-pipe 3-way valve 4-pipe 3-way valve

FWC-BT/BF

FWF-BT/BF

BYCQ140CW BYCQ140CW KDBHQ55C140 KAFP551K160 CE.KDDQ55C140 BRC7F532F (*18) BRC7F533F (*18)

BYFQ60B

KDBH44BA60 KDBQ44B60 KAFQ441BA60 KDDQ44XA60 BRC7E530 (*18) BRC7E531 (*18) BRC315D (*4) DCS302C51 (*5) KJB311A DCS301B51 (*9) KJB212A

DST301B51 (*6)(*9) KRP2A52 (*7) (*12) KRP4AA53 (*7) (*12) KRP1H98 (*13) KRCS01-4 DCS601C51(*6) (*11)

DST301B51 (*6)(*9) KRP2A52 (*9) (*12) KRP4AA53 (*9) (*12) KRP1BA101 (*14) KRCS01-1 DCS601C51 (*6) (*11) KJB411A

EKFCMBCB (*8) (*12) EKMV2C09B (*8) (*10) (*15) EKMV3C09B (*8) (*10) (*15)

EKFCMBCB (*8) (*12) EKMV2C09B (*8) (*10) (*16) EKMV3C09B (*8) (*10) (*16) EKRP1C11 EKRORO (*17)

material MERCA SRC-COA SRC-HPA WRC-COB WRC-HPB DCP600TB DCP900TB DCP900FB MCKAW2T3VN MCKCW2T3VN MCKAWH4T3VN

FWT-BT x x x x x -

FWF-CT x x x x x x x -

15. 2-pipe unit: 1 x valve kit + 1 x installation box for PCB KRP1H98 + 1 x valve control PCB EKRP1C11 4-pipe unit: 2 x valve kit + 1 x installation box for PCB KRP1H98 + 1 x valve control PCB EKRP1C 11 (FWC) 16. 2-pipe unit: 1 x valve kit + 1 x installation box for PCB KRP1BA101 + 1 x valve control PCB EKRP1C11 4-pipe unit: 2 x valve kit + 1 x installation box for PCB KRP1BA101 + 1 x valve control PCB EKRP1C11 (FWF)» 17. This option is needed to create T1 T2 wire. 18. It is possible to change the operation mode, but this will not have an impact on the water temperature. (No feed back to water source) It is not possible to select the “auto airflow” setting. Dry operation can be selected with this remote control, but this function is not available on the FWC model. 19. All options are supplied as kit. 20. Both parts of the fresh air intake are needed for each unit.

113

FWC-AT x x x x x x x -

FWC-AF x x x x x


Options & accessories - ventilation

OTHERS

ERQ100-125AV1

ERQ140AV1

Central drain pan Central drain plug

KKPJ5F180

VAM wired remote control

CENTRALISED CONTROL SYSTEMS

KWC26B280

KRC19-26A6

Fixing box

Wired remote control

ERQ200-250AW1

KWC26B160 KKPJ5F180

Cool/heat selector

INDIVIDUAL CONTROL SYSTEMS

ERQ125AW1

KJB111A

VAM-FA

EKEQFCB 2

EKEQDCB 2

EKEQMCB 2

BRC1E52A / BRC1D52

BRC1E52A / BRC1D52

BRC1E52A / BRC1D52

BRC1E52A / BRC1D52

EKEQFCB 2

EKEQDCB 2

EKEQMCB 2

EKEQFCB 2

EKEQDCB 2

EKEQMCB 2

BRC301B61

VAM-FA

Centralised remote control

DCS302C51

Unified ON/OFF control

DCS301B51

Schedule timer

DST301B51

OTHERS

VAM-FA

Wiring adapter for electrical appendices (control and monitoring F1 F2)

KRP2A61

Wiring adapter for electrical appendices (control and monitoring P1 P2)

KRP4A51

Adapter for humidifier (running ON signal output)

KRP50-2

Adapter for heater control kit

BRP4A50

Remote sensor

KRCS01-1

Notes (2) Do not connect the system to DIII-net devices (Intelligent controller, Intelligent Manager, LonWorks interface, BACnet interface‌).

114


POWER SUPPLY T1 = 3~, 220V, 50Hz V1 = 1~, 220-240V, 50Hz VE = 1~, 220-240V/220V, 50Hz/60Hz* V3 = 1~, 230V, 50Hz VM = 1~, 220~240V/220~230V, 50Hz/60Hz W1 = 3N~, 400V, 50Hz Y1 = 3~, 400V, 50Hz * For VE power supply only 1~, 220-240V, 50Hz data is displayed in this catalogue.

MEASURING CONDITIONS AIR CONDITIONING 1) nominal cooling capacities are based on: Indoor temperature Outdoor temperature Refrigerant piping length Level difference 2) nominal heating capacities are based on: Indoor temperature Outdoor temperature Refrigerant piping length Level difference

27°CDB/19°CWB 35°CDB 7.5m - 8/5m VRV 0m 20°CDB 7°CDB/6°CWB 7.5m - 8/5m VRV 0m

APPLIED SYSTEMS Air cooled

Cooling only Heat pump

Water cooled

Cooling only

Evaporator: 12°C/7°C Ambient: 35°CDB Evaporator: 12°C/7°C Ambient: 35°C Condenser: 40°C/45°C Ambient: 7°CDB/6°CWB Evaporator: 12°C/7°C Condenser: 30°C/35°C Evaporator: 12°C/7°C Condenser: 40°C/45°C Evaporator: 12°C/7°C Condensing temperature: 45°C / Subcooling: 5 K Room temperature: 27°C/19°C Entering water temperature: 7°C/12°C Room temperature: 20°C Water inlet temperature: 50°C (2-pipe)/70°C (4-pipe)

Heating only Condenserless chiller Fan coil units

Cooling Heating

The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment (for measuring conditions: please refer to the technical databooks). The sound power level is an absolute value indicating the “power” which a sound source generates. For more detailed information please consult our technical databooks. 115


Environmental awareness European Union’s

20-20-20 energy targets

In March 2007, after years of worldwide concern, the European heads of state endorsed “an integrated

approach to climate and energy policy that aims to combat climate change and increase the EU’s energy security while strengthening its competitiveness. They committed Europe to transforming itself into a highly energy-efficient, low carbon economy.” (http://ec.europa.eu) To turn this into a reality, a series of challenging climate and energy objectives were set and became known as the 20-20-20

energy targets, which are to be met by 2020 and these are:

C02 -20% CO2 emissions vs. 1990

-20%

+20% Share of

Primary energy use

renewable energy

vs. BAU* *Business As Usual

What this really

By the year

2020

means

In simple terms, the EU’s targets are aimed at reducing the amount of energy consumed, reducing the use of fossil and other natural mineral fuels used in the production of energy, and the reduction of the amount of greenhouse gases (particularly CO2 and water vapour) produced. And if we are to be successful in doing this, then new regulations, production and performance standards, and energy usage rules will be needed. The EU has not been slow in recognizing this need. New directives have been developed and issued on the subject of

› energy labelling of domestic appliances – this must show the true energy usage of equipment across the whole year: for air-conditioning equipment this includes the introduction of a Seasonal Energy Efficiency Rating (SEER and SCOP)

› energy efficiency in buildings to reduce their impact on the environment through improved insulation, improved heating and lighting systems and the increased use of renewable energy sources

› environmental performance of products throughout their life-cycle by the systematic integration of environmental aspects at a very early stage in the product

design

› fluorinated greenhouse gases (F-gas) and ozone depleting substances which aim to phase out certain refrigerants and tighten up on the checks needed to ensure that such gases are not being leaked into the atmosphere and contributing to the greenhouse effect.

116


Environmental awareness

The Daikin Response Heat pump technology

Daikin, always the leader in air conditioning technology, has embraced the challenges of the EU 20-20-20 declaration and Energy Efficiency Directives and has moved positively to take a market leadership position on many issues.

In many ways, it is with our advanced heat pump technology and heat recovery systems that we can do most to contribute towards the EU’s climate targets. Our use of heat pumps to extract heat from the ambient air (a renewable heat source referred to as aerothermal energy) is very well established and helps reduce the energy usage of whole buildings. In addition, however, heat pumps can be used to extract heat from the ground (geothermal energy) as well as rivers, lakes and ground water (hydrothermal energy). This renewable heat energy is then transferred to the refrigerant system to raise the temperature of the outflow water and thus effectively pre-heat it. This reduces the energy required to provide heating and the transferred heat is often enough to maintain domestic hot water tanks at the correct temperature. This remarkable technology will now be applied to small capacity units as we focus on total climate control in all its forms.

Many years ago, we developed the inverter technology that is now installed in all of our air conditioning units. The inverter system supplies full load power at start up but then monitors the actual heating or cooling demand and steadily reduces the power being used until the correct temperature is reach. It then effectively turns itself off until a change is noted at which point it applies sufficient power to bring the temperature back to the set point. This direct link between temperature control and energy usage means that inverter driven air conditioners are up to 30% more energy efficiency. The eco-design requirements are very ambitious and will in the end ban non-inverter technology.

Temperature / Power input

Heat pump or air conditioner without Inverter

Temperature remains stable

Quick start

Heat pump or air conditioner with Inverter

Set temp.

AEROTHERMAL HEAT PUMP

Time

HYDROTHERMAL HEAT PUMP

GEOTHERMAL HEAT PUMP

Seasonal efficiency

State-of-the-art control systems

Over the years we have been concerned about letting our clients know the true seasonal energy efficiency of our products, as the rating system then in place was misleading. Our vision on this has been vindicated and the introduction of seasonal performance will ensure a better understanding of the energy usage of all air conditioning systems. We have been designing and engineering our equipment to achieve marketleading SEERs and SCOPs and thus contributing to a reduction of energy used.

Our systems are all connected to advanced control systems that give room-by-room settings as well as integrated building control to ensure that the customer can maximise and optimise the use of their Daikin system as a total solution for their building: one that gives perfect climate control, reduced costs and reduced environmental impact.

The way

New refrigerants The regulation on ozone depleting substances and the fluorinated gas directive provide some special challenges. The phasing out of R-22 refrigerants and the concerns over the environmental impact of other refrigerants has led to pressure being brought to bear for the development of non-fluorinated, low GWP (global warming potential) and natural refrigerant gases. This in turn means that refrigerant systems will have to be re-designed and re-engineered – our engineers are already hard at work developing an alternative product line and trying innovative modifications to our current lines. As always, we are the innovation leaders!

forward

All in all, the European Union’s climate concerns have added a new urgency to our ongoing innovation and R&D – we are confident of our response and that it will deliver huge benefits to the customers in terms of more controllable solutions giving perfect comfort, reduced operating costs and a much lower ecological impact.

117


Daikin solutions to R-22 phase out What is R-22 and why is it to be phased-out in Europe? Due to ozone layer depletion, harmful ultraviolet rays reach the surface of the earth giving rise to a number of health and environmental issues. The international community therefore, signed the Montreal Protocol to phase out ozone depletion materials by 2030. The European Union, however, decided to ban R-22 already in 2015.

R-22 is a hydrochlorofluorocarbon (HCFC) which was commonly used in air conditioning systems. When R-22 is released into the air, the ultraviolet rays of the sun cause it to decompose and chlorine is released into the stratosphere. Chlorine reacts with ozone, reducing the amount of the ozone.

When will R-22 be banned in Europe?

2004

2005

2006

Ban of the sale of R-22 air conditioning equipment

1

2009

Daikin advises the replacement of your existing R-22 installation

2010

2011

Ban on the use of virgin R-22 for service & maintenance

2014

2015

Ban on the use of all R-22 for service & maintenance

Only reclaimed & recycled 1 R-22 allowed

Recycled: re-use of R-22 following a basic cleaning process. Recycled R-22 must be re-used by the same company that carried out the recovery (can be done by installer) Reclaimed: reprocessed R-22 in order to meet the equivalent performance of virgin R-22 (by specialized company)

The Daikin

solution

to upgrade R-22 and R-407C systems

Due to significant developments in heat pump technology, today’s air conditioning systems, running on R-410A refrigerant, offer better performances than R-22 and R-407C systems did in the past. Furthermore, R-22 will be soon unavailable in Europe. Already today, only reclaimed or recycled

R-22 can be used for servicing. To upgrade R-22 and R-407C systems as cost effectively as possible, Daikin units can be installed using existing pipe work. Al large scale of Replacment and Retrofit solutions are offered for Daikin equipment.

What is the impact on an R-22 installation? reclaimed or recycled to cover the demand. As a consequence, supply shortages and price increases are expected. If there is no reclaimed or recycled R-22 available, certain repairs (for example: compressor change) will no longer be possible and considerable air conditioning system downtime can occur.

The R-22 phase out regulation will impact on all currently operating R-22 systems, although reliable R-22 equipment does not need to be replaced immediately because maintenance can be carried out with recycled or reclaimed R-22 until 1st January 2015. However, not enough R-22 is currently

It is therefore worthwhile to consider a replacement system before 2015, especially for air conditioning systems with a large impact on the daily running of the business.

118



The

EWAD~C family

Non-inverter

All year round… Inverter A p p l i e d S y s t e m s C ATA LO G U E 2 0 12

… top efficiency, low sound levels and flexible solutions for a wide range of applications

Applied Systems

Catalogue ■

ALL SEASONS PERFECT C MFORT

Free cooling

The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

DAIKIN AIRCONDITIONING CENTRAL EUROPE HandelsgmbH campus 21, Europaring F12/402, A – 2345 Brunn/Gebirge Tel.: +43 / 22 36 / 3 25 57-0, Fax: +43 / 22 36 / 3 25 57-900 e-mail: office@daikin.at, www.daikin-ce.com

Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.euroventcertification.com or using: www.certiflash.com

Daikin products are distributed by:

ECPEN12_02_dace_AS • Copyright Daikin We reserve the right for printing errors and model changes.

Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.