www.lsis.biz
Super Solution
Air Circuit Breakers
ACB
Susol Air Circuit Breakers
LSIS Made It!
Super Solution
Overview
4
External configuration
14
Internal configuration
16
Ordering
18
Ratings
22
Trip relays
26
Accessories
52
Electrical diagram
80
Dimensions
82
Technical information
Contents
Insulation voltage Temperature derating Operating conditions Installation recommendation Protective coordination
104 105 106 107 113
Standards & Approval
119
Time chart
120
Ordering sheet
123
Premium Susol ACB meets your demands for high breaking capacity, fully line-up, and optimized panel size. Various accessories and connection methods realize user-friendly handling. Susol ACB provides you with total solutions with an advanced trip relay for measurement, diagnosis, analysis, and communication as well as protective functions for absolute protective coordination and electric power monitoring system.
LSIS Super Solution series
Susol series circuit breakers are suitable for Protection of power distribution Protection of motor & its control device Controlling and disconnecting circuits
Optimum technical support for (Cascading, Discrimination, Type 2 coordination) Selecting economical protection system Quarantee safety of the installation Reducing the stress on components and damage Guarantee service continuity
Susol Manual Motor Starters
Susol Air Circuit Breakers
Susol Molded Circuit Breakers
Susol Magnetic Contactors & Overload Relays
Full line-up & Compact Up to 6300A, Susol ACB provides fully lined-up 3 frame. For each frame, there is just one size, which is smaller and more compact.
H = 430mm
It makes it possible for you to design the optimized volume panel.
W = 334mm
85kA AH-06~20D 06 08 10 13 16 20
630AF 800AF 1000AF 1250AF 1600AF 2000AF
Icu=Ics=85kA/500Vac W=334(3p), 419(4p)mm
W = 412mm
100kA AH-06~40E 06 08 10 13 16
630AF 800AF 1000AF 1250AF 1600AF
Icu=Ics=100kA/500Vac W=412(3p), 527(4p)mm
20 25 32 40
2000AF 2500AF 3200AF 4000AF
m 5m 37 = D
W = 785mm
150kA AH-40~63G 40 50 63
4000AF 5000AF 6300AF
Icu=Ics=150kA/500Vac W=785(3p), 1015(4p)mm
Trip Relay (OCR)
Trip relays are classified according to function. Trip relays are classified according to their usages and functions to maximize customers’ satisfaction. Classified trip relays and easy installation. Protection: overload, short current, ground fault, earth leakage, under voltage, over voltage, under frequency, over frequency, reverse power, unbalance, etc Measurement: voltage, ampere, power, energy, frequency, power factor, Harmonics, etc. Event & fault recording: Max. 256 events & faults Communication: Modbus/RS-485, Profibus-DP
Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism. It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides advanced functions - measurement, diagnosis, analysis, and communication.
Susol ACB Trip relay N type
L/S/I/G/Thermal Self Power RTC Timer mounted Fault information (LED)
A type
P/S type
L/S/I/G/Thermal ZSI Remote Reset Modbus/RS-485 Profibus-DP Self Power AC/DC 100~250V DC 24~60V RTC Timer mounted Fault Recording (10EA)
L/S/ I/G/Thermal(Continuous) UV/OV/OF/UF/rP/Vun/Iun Measurement: V/A/W/Wh/F/PF Harmonics (63th), Waveform (S Type) ZSI Remote Reset Modbus/RS-485 Profibus-DP AC/DC 100~250V DC 24~60V RTC Timer mounted Event Recording (256EA) Fault Recording (256EA) Fault Wave (S Type)
Trip relays series N type
A type
N Type (Normal) Self-power + Current protection
A Type (Ammeter) Current Meter + Current protection + DO control + Communication
P type
S type
P Type (Power Meter) A type + Power Meter + Voltage / Frequency / Unbalance protection
S Type (Supreme) P type + Harmonics analysis (63 th) + Fault wave recording
Accessories
ACB Trip Relay (OCR)
Auxiliary Switch (AX)
Motor (M)
Key Lock (K1),
Closing Coil (CC)
Double Key Lock (K3)
Shunt Coil (SHT)
Counter (C)
Under Voltage Trip Device (UVT)
On/Off Button Lock (B)
Door Interlock (DI)
Miss Insertion Preventing Device (MIP)
MOC (Mechanically
Automatically Discharge
Operated Cell Switch)
Mechanism (ADM)
Mechanical Interlock (MI)
Manual Reset Button (MRB)
Cradle
Other
Safety Shutter (ST)
Mechanical Interlock (MI)
Condenser Trip Device (CTD)
Manual Connector
Miss Insertion Prevent Device (MIP)
Door Frame (DF)
Zero Arc Space (ZAS)
Body Supporter (BSP)
Dust Cover (DC)
Insulation Barrier (IB)
Shorting "b" Contact (SBC)
OCR Tester (OT)
Cell Switch (CEL)
Safety Control Cover (SC)
ATS Controller (ATS)
Door Interlock (DI)
Automatically Discharge
Lifting Hook (LH)
MOC (Mechanical
Mechanism.(ADM)
Dummy ACB
Operated Cell switch)
Racking Interlock (RI)
UVT Time Delay Controller (UDC)
Safety Shutter Lock (STL)
Profibus-DP Communication module Remote I/O Temperature Alarm
Connection and Installation
Diverisified terminal connection methods of the ACB main circuit for users.
Multiple connections Various installation methods Standard connection
Horizontal type
Vertical type
Front type
Mixed connection
Horizontal / Vertical type
Vertical / Horizontal type
Vertical / Front type
Front / Horizontal type
Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current.
Horizontal / Front type
Front / Vertical type
External configuration Fixed type ACB
Terms Trip relay Counter ON button OFF button Series name Charge handle Rated name plate Charge/Discharge indicator ON/OFF indicator Corporation logo Arc cover Terminal cover Cradle Draw-out handle Position indicator Handle storage space Pad lock button Arc chute Control cover Fixed type bracket
Draw-out ACB (Cradle)
14
Cradle (Internal)
Cradle (Rear)
Terms Terminal cover of control circuit
Handle storage space
Cradle finger (Line side)
Pad lock button
Cradle finger (Load side)
Connecting conductor (Line side)
Draw-out handle
Connecting conductor (Load side)
Position indicator
Main nameplate [Acronym explanation]
[Secondary nameplate] Explanation of terminologies
Ui: Rated insulation voltage Uimp: Impulse withstand voltage Ue: Rated operational voltage (AC base) Icu: Ultimate breaking capacity Ics: Service breaking capacity Icw: Short time withstand current MFG. Date: Manufacturing date
Motor charge Control power and Closing coil terminal No. Shunt tripping coil Auxiliary switches: Contact specification and terminal No. Under voltage trip: UVT terminal No. OCR control source: Trip relay control power Alarm switch: Alarm and terminal No. Digital trip relay: Switching diagram Z.S.I: Input/Output terminal No. Reset: LED/LCD reset Communication: Communication and terminal No. Voltage module: Phase voltage and symbol Earth/Leakage: Ground fault / Earth leakage input terminal No.
15
Internal configuration
Terms Arc chute Aux. switch control terminal Control power supply terminal Trip relay control terminal Carrying grip Trip coil or UVT coil Mechanism Main body Counter Trip coil Closing coil Motor Ass’y Aux. switch ON button OFF button MTD base Trip relay Front cover
16
Terms Control circuit terminal block Control terminal Auxiliary switches Closing, Trip, UVT coil Trip relay Front cover Mechanism Charge handle Trip spring Closing spring Draw-in/out device Arc extinguishing part Moving contact Fixed contact Conductor on line side Cradle finger Cradle Connecting conductor Power supply CT Conductor on load side
17
Ordering ACB & Accessories AH
10
D
3
Type
Ampere frame
Frame sizes & phase array
No. of pole
-
AH
3P/4P
AS 06
AN
630AF
D
Standard type
3
3P(D)
RST(N) AH
AN
AS
08
800AF
10
1000AF
13
1250AF
16
1600AF
20
2000AF
W
10
J
Rated current (CT Spec.) 00
Without OCR & CT
02
200A
04
400A
06
630A
04
400A
06
630A
Connections Draw-out type J A
Manual connection Automatic connection Fixed type
4P
08
800A
H
Horizontal type
Reverse
10
1000A
V
Vertical type
13
1250A
16
1600A
M
Line: Horizontal
20
2000A
phase type
4
4P(D, W)
NRST
Mixed type Load: Vertical Mixed type
E 20
2000AF
3P/4P
06
630A
Standard
08
800A
10
1000A
13
1250A
16
1600A
4P
20
2000A
Reverse
25
2500A
32
3200A
40
4000A
type
3
3P(E)
RST(N) AH AS 25
2500AF
X
32
3200AF
phase type
40
4000AF
NRST
4
4P(E, X)
3P/4P 40
4000AF
F
Standard
3
3P(F)
40
4000A
4
4P(F, Y)
50
5000A
3
3P(G)
40
4000A
50
5000A
63
6300A
type RST(N)
AS
4P Reverse 50
5000AF
Y
phase type NRST
AH AS
18
40
4000AF
50
5000AF
63
6300AF
3P/4P G
Standard type RST(N) 4P Reverse
Z
phase type NRST
4
4P(G, Z)
N
Line: Vertical Load: Horizontal
P
Front type
M1
D1
Motor rated voltage
D1
NG0
AX
Trip relay
Shunt coil rated voltage
MA
Without Motor
D0
Without Shunt coil
M1
AC/DC 100V~130V
D1
AC/DC 100V~130V
M2
AC/DC 200V~250V
D2
AC/DC 200V~250V
M3
DC 125V
D3
DC 125V
M4
DC 24V~30V
D4
DC 24V~30V
M5
DC 48V~60V
D5
DC 48V~60V
M6
AC 380V~415V
D6
AC 380V~480V
M7
AC 440V~480V
D7
AC 48V
M8
AC 48V
Closing coil rated voltage
AL
U1
Refer to 26page
UVT coil rated voltage
Aux.contact & charging types
D0
Without Closing coil
AX
Standard OFF-Charge 3a3b
U0
Without UVT coil
D1
AC/DC 100V~130V
AC
Standard ON-Charge 3a3b
U1
AC/DC 100V~130V
D2
AC/DC 200V~250V
BX
Standard OFF-Charge 5a5b
U2
AC/DC 200V~250V
D3
DC 125V
BC
Standard ON-Charge 5a5b
U3
DC 125V
D4
DC 24V~30V
HX
High capacity OFF-Charge 5a5b
U4
DC 24V~30V
D5
DC 48V~60V
HC
High capacity ON-Charge 5a5b
U5
DC 48V~60V
D6
AC 380V~480V
CC
Standard ON-Charge 6a6b
U6
AC 380V~480V
D7
AC 48V
JC
High capacity ON-Charge 6a6b
U7
AC 48V
3)
* UVT Delay module is available over AC / DC 48V
Option
Type name
Option
AL A1 A2
AL1+MRB AL1+MRB+RES (AC110~130V) AL1+AL2+MRB
*AC private use
A3
AL1+MRB+RES (DC110~125V)
*DC private use
A4
AL1+MRB+RES (AC200~250V)
*AC private use
A5
AL1+MRB+Auto reset
A6 A7
AL1+AL2+MRB+Auto reset AL1+MRB+RES (DC110~125V)+Auto reset
*DC private use
A8
AL1+MRB+RES (AC200~250V)+Auto reset
*AC private use
A9
AL1+MRB+RES (AC110~130V)+Auto reset
*AC private use
C
C
Counter
S 2)
CS2
Charge switch communication
B M
B MI
On/Off Button lock Mechanical interlock **AN typenot applied
D
Type name DI or MOC
Door Interlock or MOC (Mechanism operated cell switch)
K
K1
Key lock
K2 K3
K2 K3 RCS
Key Interlock set Key lock double Ready to close switch
TM
Temperature monitoring AC/DC 100~130V
R 2) T 3) H1 H2 H3 H4 H5 H6 H7
AC/DC 200~250V DC 125V 1)
SHT2
DC 24~30V DC 48~60V
Double shunt coil **At using UVT, not applied
AC 380~480V AC 48V
Note) 1. UVT and SHT2 are alternative. 2. CS2 and RCS are alternative. 3. TM and CC/JC(6a6b) are alternative. 4. Other accessories should be ordered seperately.
19
Ordering Cradle AL
LS ACB cradle
N16D
Rated current & frame N16D
AN-06~16D
S20D
AS-20D
3
J
No. of pole 3
3P
4
4P
H V
S25E
H
E
Connections
Safety shutter
Horizontal type (20D inapplicable) Vertical type
AS-20~25E
E F
N
Without safety shutter With safety shutter
Mixed type
20
S32E
AS-32E
S40E
AS-40E
S50F
AS-40~50F
S50G
AS-40~50G
S63G
AS-63G
H16D
AH-06~16D
H20D
AH-20D
H32E
AH-20~32E
H40E
AH-40E
H50G
AH-40~50G
H63G
AH-63G
Terminal connections J A
M
Line: Horizontal
Manual
(20D inapplicable)
connection
Mixed type
Automatic Connection
N
Line: Vertical Load: Horizontal (20D inapplicable) Front type
P
Arc cover
Load: Vertical
(20D, 40E, 50FG, 63G inapplicable)
N S
Without Arc cover With Arc cover
Trip relay N
G
0
Trip relay type
Communication & protection
Control voltage & frequency
G
0
000 Without trip relay N N
Normal
G
Without comm. + L/S/I/G
* L/S/I/G configuration as standard -with LED indicators -without output contacts * Ground fault system by vector sum
A A
Ammeter
0
Self-Power, 60Hz
5
Self-Power, 50Hz
G
0
G
Without comm.
0
Self-Power, 60Hz
Z
Without comm. + Earth leakage
1
AC/DC 100V~250V, 60Hz
E
Without comm. + Earth leakage
2
DC 24V~60V, 60Hz
C
Comm.
5
Self-Power, 50Hz
K
Comm. + Earth leakage
6
AC/DC 100V~250V, 50Hz
X
Comm. + Earth leakage
7
DC 24V~60V, 50Hz
* L/S/I/G configuration as standard * Ground fault system by vector sum(G,C) * Earth leakage system - Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - E,X: External CT - Private ZCT applied(faullt current >30A) * Comm. And output contacts DO NOT work under self-power condition. (Only checking LED available)
P P
Power meter
C
1
C
Comm.
1
AC/DC 100V~250V, 60Hz
K
Comm. + Earth leakage
2
DC 24V~60V, 60Hz
X
Comm. + Earth leakage
6
AC/DC 100V~250V, 50Hz
A
Comm. + Pre-trip alarm
7
DC 24V~60V, 50Hz
* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose * Comm. And output contacts DO NOT work under self-power condition. (Only checking LED available)
S S
Supreme meter
C
1
C
Comm.
1
AC/DC 100V~250V, 60Hz
K
Comm. + Earth leakage
2
DC 24V~60V, 60Hz
X
Comm. + Earth leakage
6
AC/DC 100V~250V, 50Hz
A
Comm. + Pre-trip alarm
7
DC 24V~60V, 50Hz
* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose * Comm. And output contacts DO NOT work under self-power condition. (Only checking LED available)
Note) 1. L/S/I/G configuration as standard 2. Ground fault, earth leakage and pre-trip alarm functions are alternative. 3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition. 4. Voltage module should be required for P and S types(supplied seperately)
21
Ratings
Type
AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D
Ampere frame
(AF)
Rated current(A)
(In max)
Setting current (A) *
Control trip relay ( ...
at 40
630 200 400 630
800 400 630 800
400 630
400 630 800
1250
1600
2000
1000
1250
1600
2000
1600
2000
(0.4 ~ 1.0)
In max)
Rated current of neutral pole (A)
1000
1000
In max 1250
Rated insulation voltage(V)
(Ui)
1000
Rated operating voltage(V)
(Ue)
690 12 50/60 3/4
Rated impulse withstand voltage (kV)(Uimp) Frequency(Hz) Number of poles (P) Rated breaking capacity (kA sym) AC 50/60Hz
(Icu)
Rated service breaking capacity (kA) (Ics) Rated making capacity (kA peak) AC 50/60Hz
85 85 65
220V/230V/380V/415V IEC 60947-2 460V/480V/500V KS C 4620 550V/600V/690V ... % Icu
100% 187 187
220V/230V/380V/415V IEC 60947-2 (Icm) 460V/480V/500V KS C 4620 550V/600V/690V
143
1sec
65
2 sec
60
3 sec
50
Operating time (ms)
Maximum total breaking time
40
Life cycle (time)
Mechanical
Maximum closing time Without maintenance
80 20,000
With maintenance Without maintenance
30,000
Electrical
With maintenance
10,000
Rated short-time withstand current (kA)
Connections
(Icw)
Draw-out / Fixed
**
5,000 -
Horizontal connection Vertical connection
Weight (kg)
Draw-out type
63/74
70/85
61/72
68/83
Cradle only
29/32
33/40
Motor charging type
34/44
38/47
Manual charging type
32/42
36/45
3P 4P
430 334 375 430 419 375
3P
300 300 295
4P
300 385 295 N, A, P, S type
Fixed type External dimensions (mm) (H W D)
Draw-out type
H D
Fixed type
W
Trip relay
KS / KEMA / KERI / GOST
Certificate & Approval
LR, ABS, DNV, KR, BV, GL, RINA, NK
Marine clasiflcation * Refer to trip relay specification.
22
-
(With cradle) Manual charging type
Main body
(3P/4P)
Front connection Mixed connection Motor charging type
**
: Standard,
: Option
AH-06E
AH-08E
AH-10E
AH-13E
AH-16E
AH-20E
AH-25E
AH-32E
AH-40E
AH-40G
AH-50G
AH-63G
630
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
630
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
(0.4 ~ 1.0) 630
800
1000
1250
In max
1600
2000
(0.4 ~ 1.0) 2500
3200
4000
4000
In max
5000
1,000
1,000
690
690
12 50/60
12 50/60
3/4 100
3/4 150
100
150
85
100
100%
100%
220 220 187
330 330 220
85
100
75
85
65
75
40
40
80 15,000
80 10,000
20,000
15,000
5,000
2,000
10,000
5,000
-
6300
-
87/103
107/139
181/223
186/230
85/101
102/145
179/221
184/228
44/55
65/85
97/117
102/124
44/55
61/81
98/123
103/130
42/53 430 412 375
60/80
96/121 460 785 375
101/128
-
430 527 375 300 378 295
460 1015 375 300 751 295
300 493 295
300 981 295
N, A, P, S type KS / KEMA / KERI / GOST
N, A, P, S type KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
LR, ABS, DNV, KR, BV, GL, RINA, NK
23
Ratings
Type
AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D (AF)
Ampere frame Rated current(A)
(In max)
Setting current (A) *
at 40
Control trip relay ( ...
630
800
200
400
400
630
630
800
400 630
400 630 800
1250
1600
2000
1000
1250
1600
2000
1600
2000
(0.4 ~ 1.0)
In max)
Rated current of neutral pole (A)
1000
1000
In max 1250
Rated insulation voltage(V)
(Ui)
1000
Rated operating voltage(V)
(Ue)
690 12 50/60
Rated impulse withstand voltage (kV)(Uimp) Frequency (Hz) Number of poles (P) Rated breaking capacity (kA sym) AC 50/60Hz
(Icu)
IEC 60947-2 460V/480V/500V KS C 4620 550V/600V/690V
Rated service breaking capacity (kA) (Ics) Rated making capacity (kA peak) AC 50/60Hz
(Icm)
IEC 60947-2 KS C 4620
(Icw)
Operating time (ms)
70
65
70 65
100% 143 143
100% 154 154
550V/600V/690V
105
143
1 sec
50
65
2 sec
42
55
3 sec
36
220V/230V/380V/415V 460V/480V/500V
50 40
Maximum total breaking time
Life cycle (time)
Connections
65 50
... % Icu
Rated short-time withstand current (kA)
3/4 220V/230V/380V/415V
Mechanical
Maximum closing time Without maintenance
80 20,000
With maintenance Without maintenance
30,000
Electrical
With maintenance
10,000
Draw-out / Fixed
**
5,000 -
Horizontal connection Vertical connection
Weight (kg)
Draw-out type
63/74
70/85
61/72
68/83
Cradle only
29/32
33/40
Motor charging type
34/44
38/47
Manual charging type
32/42
36/45
3P 4P 3P
430 334 375 430 419 375 300 300 295
4P
300 385 295
Fixed type External dimensions (mm) (H W D)
Draw-out type
H D
Fixed type
W
N, A, P type
Trip relay
KS / KEMA / KERI / GOST
Certificate & Approval
LR, ABS, DNV, KR, BV, GL, RINA, NK
Marine clasiflcation * Refer to trip relay specification.
24
-
(With cradle) Manual charging type
Main body
(3P/4P)
Front connection Mixed connection Motor charging type
**
: Standard,
: Option
Trip relays Event & fault recording (P, S type)
When there are events such as setting change, Info. change, error of self-diagnose, state change, P and S type record Max. up to 256 information of the events in accordance with time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults such as fault cause, fault phase, fault value and so on in accordance with time(ms).
Event information display Initial display
Setting display
1000 A R
S
T
M
N
100%
50%
Password input
1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]
1.Event 2.Clear All 3.Fault 4.Clear All
1. Event L 2007/05/15 20:29:41 Sta Change
10. Event L 2007/04/15 10:11:24 Cfg Change
Power On
Comm Set up
Fault information display Initial display
Setting display
1000 A R
S
T
M
N
100%
50%
Password input
1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]
1.Event 2.Clear All 3.Fault 4.Clear All
1. Trip 2007/04/26 08:35:52 OCR-Short
9. Trip 2007/04/11 09:11:32 UVR
Phase T
Phase R
930A
System information
P and S type can indicate information as followings with the information of the ACB. - Present time: year/month/date/hour/minute/ms - ACB current ratings - N-phase current ratings: 100% - Frequency information: 60Hz / 50Hz - Closing numbers of breaker: CB ON numbers - Trip relay operating time: OCR ON time - ON time of breaker: CB ON time - S/W ver. information
System information display Initial display
Setting display
1000 A R 100%
50%
50
S
T
N
M
1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]
Password input
System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR Freq 60 Hz CB ON# 23 Ver-Arm 1.41
System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR T-OPER 220 h T-CB ON 180 h Ver-Msp 1.01
OV
System block diagram
R
S
T
N ACB Trip
ACB Vcc/+9V/-9V
CN2-1 CN2-11
Filter Amp.
CN2-3 CN2-13
Signal CT
CN2-5 CN2-15
Vcc
CPU Output Power PCB Ass’y
+5V
+24V
Display (LED, LCD) Main PCB Ass’y
MTD CN2-6 Output CN2-8
Main PCB Ass’y
CN2-7 CN2-16 CN2-14
Setting part GND 24
CN2-4
Vcc
Self power
RY0 (K1) CN4-2 GTD contact
+24V GND+24V
Power CT Main PCB Ass’y
RY1 (K2) CN4-4 STD/INST contact
+5V RY2 (K3)
-5V
CN4-6 LTD contact
CN2-2
CN4-9
SMPS
CN4-10
Power PCB Ass’y
CN4-8 Common contact
Trip relay
Additional source AC/DC 100~250V DC 24~60V
CN1-1 ZSI output+ terminal CN1-2 ZSI output- terminal CN1-3 ZSI input+ terminal CN1-4 ZSI input- terminal
CN1-9
VDM
CN1-10 CN1-11 CN1-12
CN1-5 Remote reset+ terminal CN1-6 Remote reset- terminal
CN1-7
Earth
CN1-8
CN1-7 Earth leakage+ terminal
Input signal(R phase) CN3-2 Input signal S phase CN3-4
CN1-8 Earth leakage- terminal
Input signal T phase CN3-6 Input signal N phase CN3-8 DC 24V
CN3-5
UTXO
CN3-1
URXO
CN3-3
GND 24V
CN3-7/9
AD GND
CN3-10
Test
Main PCB Ass’y
Comm. Power PCB Ass’y
CN4-1 485+ terminal CN4-3 485- terminal
51
Accessories
Mounting
Accessories
Standard Option Standard Option Standard Option
Remark Page 54
SHT2 Double Shunt Coil
M
*
55
Closing Coil
*
56
Motor
*
57
Charge Switch
*
57
CS2
Charge Switch Communication
*
57
UVT
Under Voltage Trip Device
*
58
AL
Trip Alarm Contact
MRB Manual Reset Button RES
Remote Reset Switch
C AX
*
59
*
59
*
60
*
60
Counter
*
67
Auxiliary Switch
*
61
RCS Ready to Close Switch
TM
Temperature Alarm
*
78
K1
Key Lock
*
62
K2
Key Interlock Set
*
62
K3
Double Key Lock
*
63
On/Off Button lock
*
B LH CTD ATS DC
63
Lifting Hook
64
Condenser Trip Device
64
Automatic Transfer
65
Switch Controller Dust Cover
67
DF
Door Frame
71
OT
OCR Tester
66
J
Manual Connector
*
A
Automatic Connector
*
* Seperate purchasing is not allowed. Each item should be purchased with the main body.
52
AN
*
CS1
External
AS
SHT1 Shunt Coil
CC
Internal
AH
Mounting
Accessories N
Trip relay
AH
AS
AN
Standard Option Standard Option Standard Option
Remark Page
N type
*
28
A
A type
*
30
P
P type
*
32
S VM
S type
*
34
Voltage Module
**
38
ZCT ZCT for the earth leakage SBC
Cradle
Shorting "b" Contact
73
MI
Mechanical Interlock
ST
Safety Shutter
69
STL
Safety Shutter Lock
70
MIP
Miss Insertion Prevent Device
76
*
70
MOC Mechanical Operated Cell Switch
68
CEL
72
DI ZAS SC BSP
Cell Switch Door Interlock Zero Arc Space Safety Control Cover Body Supporter
69 *
73
***
74
*
74
RI
Racking Interlock
PL
Pad Lock/ Position Lock
*
75
IB
Insulation Barrier
*
71
UDC UVT Time Delay Controller ADP
75
77
Compatible Adapter
RPH Reverse Phase ACB DUM Dummy ACB Other
VAD
Various Connection Type
RCO Remote I/O PC
Profibus-DP comm. module
13 79 49
* Seperate purchasing is not allowed. Each item should be purchased with the main body. ** Voltage module should be purchased with P/S type trip relay. *** It is available only when the control block is in the mode of auto-connection.
53
Accessories Shunt Coil [SHT1]
SHT1 is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 200ms to coil terminals(C1, C2).
Shunt coil 1
When UVT coil is installed, its location is changed.
1. Rated voltage and characteristics of Trip coil Rated voltage [Vn] Opening order C1 SHT1 C2
* The dotted Userline to be made by the Wiring Diagram customer
Wiring Diagram
DC [V]
AC [V]
Power consumption (VA or W) Operating voltage range [V]
24~30
-
48~60
48
0.6~1.1 Vn
100~130
100~130
0.56~1.1 Vn
200~250
200~250
0.56~1.1 Vn
-
380~480
0.56~1.1 Vn
Inrush
Steady-state
200
5
Trip time [ms]
0.6~1.1 Vn Less than 40ms
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
Wire type Operating voltage
54
DC/AC 48 [V]
#14 AWG
Double Shunt Coil [SHT2]
Shunt coil 1
SHT2 is a control device which trips a circuit breaker doubly from the outside. When SHT1 doesn’t operate normally, it can trip a circuit breaker safely.
Shunt coil 2
Shunt coil 1: Install it at existing location. Shunt coil 2: Install it on the right side of the Shunt coil 1 It is not available with UVT coil when installing double shunt coil.
1. Rated voltage and characteristics of Trip coil Rated voltage [Vn] Opening order C11 SHT2
DC [V]
AC [V]
Power consumption (VA or W) Operating voltage range [V]
24~30
-
0.6~1.1 Vn
48~60
48
0.6~1.1 Vn
100~130
100~130
0.56~1.1 Vn
200~250
200~250
0.56~1.1 Vn
-
380~480
0.56~1.1 Vn
Inrush
Steady-state
200
5
Trip time [ms]
Less than 40ms
C12 Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
* The dotted line to be made by the customer
Wiring Diagram
2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
Wire type Operating voltage
DC/AC 48 [V]
#14 AWG
55
Accessories Closing Coil [CC]
It is a control device which closes a circuit breaker, when the voltage is applied continuously or instantaneously over 200ms to the coil terminals (A1, A2).
Closing coil
1. Rated voltage and characteristics of Closing coil Rated voltage [Vn] Closing order
A1 CC A2
* The dotted line to be made by the customer
Wiring Diagram
DC [V]
AC [V]
Power consumption (VA or W) Operating voltage range [V]
24~30
-
48~60
48
0.75~1.1 Vn
100~130
100~130
0.75~1.1 Vn
200~250
200~250
0.75~1.1 Vn
-
380~480
0.75~1.1 Vn
Inrush
Steady-state
200
5
Shunt time [ms]
0.75~1.1 Vn Less than 80ms
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
Wire type Operating voltage
56
DC/AC 48 [V]
#14 AWG
Motor [M]
Charge the closing spring of a circuit breaker by the external power source. Without the external power source, charge manually.
Motor
Operating voltage range(IEC 60947) 85%~110%Vn
Gear
Main axis
Fully charged contact
Charge switch
Input voltage(V) Load current(max.)
DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V 5A
3A
1A
0.5A
Starting current(Max.)
5 times of load current
Load rpm(Motor)
15000 ~ 19000 rpm
Charge time Dielectric strength Using temperature range Using humidity range Endurance Charge switch
AC 380V
AC 440~480V
0.3A
0.3A
Less than 5sec. 2kV/min -20 ~ 60 Max. RH 80% (No dew condensation) 15,000 cycle (Load connection, 2 times/min) 10A at 250VAC
Charge Switch [CS1] Charge Switch Communication [CS2]
It is a built-in contact which sends the signal to the outside, when motor charging is completed. (2a) It has a “1a” contact for communication and the other “1a” contact for complete charging. When using an extra communication module (Remote I/O), the state of contacts can be displayed through the network. 10A at 250VAC
57
Accessories Under Voltage Trip device [UVT]
UVT coil
If the voltage of the main or the control power is under voltage, UVT which is installed inside of the breaker breaks the circuit automatically. Please connect with UVT time-delay device in order to present the timedelay function because UVT is technically instantaneous type.
Shunt coil
The closing of a circuit breaker is impossible mechanically or electrically if control power not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied to both terminals of UVT coil (D1, D2).
Closing coil
When using UVT coil, the double trip coil can not be used, and the location of trip coil is changed.
1. Rated voltage and characteristics of UVT coil Rated voltage [Vn] DC [V]
AC [V]
24~30
-
48~60
48
100~130
100~130
200~250
200~250
-
380~480
Operating voltage range [V]
Power consumption (VA or W)
Pick up
Drop out
Inrush
Steady-state
0.65~0.85 Vn
0.4~0.6 Vn
200
5
Trip time [ms]
Less than 50ms
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
48.5m
30.5m
233.2m
143.9m
85%
13.4m
8.8m
62.5m
39.3m
Wire type Operating voltage
Note) In case of using UVT coil, the location of TC coil is changed.
58
DC/AC 48 [V]
#14 AWG
Trip Alarm Contact [AL]
AL1, 1a AL2, 1a
When a circuit breaker is tripped by OCR which operates against the fault current (Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from the mechanical indicator on main cover of main circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker) When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the main cover and the switch (AL) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. MRB and AL can be operated only when tripping by OCR, but doesn’t be operated by Off button and OFF operation of trip coil. To re-close a circuit breaker after a trip, press MRB to reset it for closing. 2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option) Trip alarm contact and MRB(Manual reset bottom) need to be purchased together. 1. Electrical characteristics of trip alarm contact Rated voltage [V]
Non-inductive load (A) Resistive load
Inductive load (A)
lamp load
Inductive load(A)
Motor load
8V DC
11
3
6
3
30V DC
10
3
6
3
125V DC
0.6
0.1
0.6
0.1
250V DC
0.3
0.05
0.3
0.05
250V AC
11
1.5
6
2
Inrush current
MAX. 24A
Manual Reset Button [MRB] It is a function which resets a circuit breaker manually when a circuit breaker is tripped by OCR. When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the main cover and the switch(SDE) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a circuit breaker after a trip, press MRB to reset it for closing.
Manual reset button Manual reset button
MRB reset lever Note) The manual reset button is protruded in the event of trip.
59
Accessories Remote Reset Switch [RES]
Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical indicator(MRB) and enables circuit breaker closing. Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load In case of auto reset type circuit breaker Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is no longer required to enable circuit breaker closing. The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset button is pressed. AL2 and RES are alternative. 1. Rated voltage and rated current of RES Rated voltage Reset order 183 RES
AC/DC 100~130V AC/DC 200~250V
Operating current(Max.) AC
6A
DC
5A
AC
3A
DC
2.5A
Operating time
Wire spec. #14 AWG (2.08 mm2)
Less 40ms #16 AWG (1.31 mm2)
Connect to inner micro switch
184 Connect to AL2 / RES
* The dotted line to be made by the customer
Wiring Diagram
Ready to Close Switch [RCS] It interlocks with mechanism of circuit breaker. It indicates the status that the circuit breaker is ready to do closing operation. Ready to close switch
“A” contact Contact part
60
When mechanism is in OFF position or in Charge, contact is output with “ON” and it indicates that mechanism can be closed.
Dimensions Draw-out type 2000AF (630~1600A: AH/AN/AS-06~16D) Front view
20
20
394
20
20
479
167
167
42.5
2-M12 Tap CMB-U/F
405 430
405 430
2-M12 Tap CMB-U/F
85
260 334
260 419
4P
3P
Vertical type
85
85
85
15
85
85
200
200
115
115
15
260 334
85
260 345
3P
4P
Disconnected & Test Connected
50 15
55
ARC Chute surface 90 (Insulation barrier)
35
97
41 18
2- 13
6
60 10
200 375 6- 13 Mounting hole
84
115 38.5
<Conductor>
50
133 350
25
270
50
15
Horizontal type
85
85
85
85
85
50
200
200
115
115
50
85
260 334
260 345
3P
4P
Disconnected & Test Connected 50 15
55
ARC Chute surface 90 (Insulation barrier)
35
350
133
270
50
25
15
15
2- 13
97
41 18
<Conductor>
6
60
200 375 4- 13 Mounting hole
10
85
38.5
85
85
85
85
50
200
200
115
115
50
260 334
85
260 345
3P
4P
Disconnected & Test Connected 50 15
ARC Chute surface
55
25
200
13.5
25
483
50
270
15
2- 13
200
41 18
<Conductor>
6
4- 13 Mounting hole 60 10
200 375
78
Front connection type
115
115 11.5
85
Dimensions Fixed type 2000AF (2000A: AH/AS-20D) Front view 300 280
385 280 150
150
165
12
Vertical type
165
270 12
12
250 439
3P
4P
85
85
85
85 15
20
20
165
165
25
25
45
45
15
4- 14 Mounting hole
4- 14 Mounting hole
330 354
415 439
3P
4P
15
90 (Insulation barrier)
35
75 25
133 67
75
58
25
270
75
30 15
20
165 295
3- 13
<Conductor>
45 32.5
29.5
65
86
12
165
354
85
320
35
300 20
20
35
270
Operating panel center
320
300
Operating panel center
Draw-out type 2000AF (2000A: AH/AS-20D) Front view 20
20
394
20
20
479 42.5
167
2-M12 Tap CMB-U/F
405 430
405 430
2-M12 Tap CMB-U/F
167
260
Vertical type
85
260
334
419
3P
4P
85
85
85
15
85
85
200
200
115
115
15
260
85
260 334
345
3P
4P
Disconnected & Test Connected
50 15
55
ARC Chute surface 90 (Insulation barrier)
35
75 133 350
25
270
75
25
15
97
41 18
3- 13
6
60 10
200 375
<Conductor>
115 38.5
6- 13 Mounting hole
87
Dimensions Fixed type 4000AF (2000~3200A: AH/AN/AS-20~32E) Front view 493
378 189
304
189
189 280
280
204
12
12
270 320
300 20
12
204
35
270 320
Operating panel center
35
20
300
Operating panel center
204
319
3P
Vertical type
115
4P
115
115
115
115
20
45 20
20
165
165
25
25
45
20
4- 14 Mounting hole
4- 14 Mounting hole
408 432
523 547
3P
4P
15
90 (Insulation barrier)
65
20
165 295
45 32.5
29.5
35
75 25
133 67
75
58
25
270
75
30 15
88
12
547
432
3- 13
<Conductor>
Horizontal type
115
115
115
115
115 75
165
20
20
165
25
25
45
45
75
4- 14 Mounting hole
4- 14 Mounting hole 523 547
408 432
3P
4P
15
90 (Insulation barrier)
75 25
133
32.5
115
115
115
115 75
45 20
20
165
165
25
25
45
75
5.5
115
4- 14 Mounting hole
4- 14 Mounting hole
408 432
523
3P
4P
547
25
212.5
15
55
19.5
25
483
75
270
25
15
3- 13
<Conductor>
108
212.5
35
Front connection type
<Conductor>
45
165 295
5.5
20
65
3- 13
67
35
57 20
113
25
270
20
30 15
65
20
165 295
45 5.5
89
Dimensions Draw-out type 4000AF (2000~3200A: AH/AN/AS-20~32E) Front view
20
20
472
20
20
206
2-M12 Tap CMB-U/F
405 430
405 430
2-M12 Tap CMB-U/F
20
587 57.5
206
115
260 412
260 375 527
3P
Vertical type
115
4P
115
115
20
115
115
200
200
115
115
20
115
260 412
260 375
3P
4P
Disconnected & Test Connected
50
15
55
ARC Chute surface 90
34
(Insulation barrier)
350
133
270
75
25
75
25
15
3- 13
97
41 18
<Conductor>
6
60 10
115
200 375
6- 13 Mounting hole
90
38.5
115
Horizontal type
115
115
115
115
75
200
200
115
115
75
260
260
115
412
375
3P
4P
Disconnected & Test Connected 50 15
55
ARC Chute surface 90 (Insulation barrier) 34
25
133 350
270
75
25
20
15
97
41 18
3- 13
<Conductor>
6
60
200
10
115 38.5
375 6- 13 Mounting hole
115
115
115
115
115 75
200
200
115
115
75
260 412
115
260 375
4P
3P Disconnected & Test Connected 50 15
ARC Chute surface 25
55 13.5
483
270
25
75
25
212.5
15
3- 13
212.5
41 18
<Conductor>
6
4- 13 Mounting hole 60 10
200 375
78
Front connection type
115 11.5
91
Dimensions Fixed type 4000AF (4000A: AH/AS-40E) Front view
378
493
189
304
189
189
280
280
204
204
300 20
270 320
270 320
35 319
12
3P
4P
150
150 17.5
10
150
150 17.5
15
10
15
165 20
20 4- 14 Mounting hole
408 432
3P
4- 14 Mounting hole
523 547
4P
15
90 (Insulation barrier)
20
165 295
45 112.5
4.5
35
25 25 125
67
25
125
33 158
270
25
125
34 15
65
92
15
25 165
25
45
15
12
204 547
150
Vertical type
12
432
45
12
Operating panel center
35
20
300
Operating panel center
5- 13
<Conductor>
Horizontal type
140
140
140
140
100
140 100
165
25
20
20
165
25
45
45
12.5
4- 14 Mounting hole
4- 14 Mounting hole
408 432
523
3P
4P
547
15
90 (Insulation barrier) 34
12.5
57 20
165 295
45 65.5
29.5
35 65
10 1010
25
55
25
100
98 153
25
270
55
12.5
15
4- 13
<Conductor>
93
Dimensions Draw-out type 4000AF (4000A: AH/AS-40E) Front view 20
20
472
20
206
2-M12 Tap CMB-U/F
405 430
405 430
2-M12 Tap CMB-U/F
20
587 57.5
206
260 412
115
260 375 527
3P 4P
Vertical type
150 17.5
150 15
150
150
10
40
15
150 40
200
200
115
115
10
115
260 412
3P
4P
ARC Chute surface
90 (Insulation barrier)
34 15
15 10 15
125 25
125
25
350
33
158
270
200 375 4- 13 Mounting hole
115 98.5
22
84.5
41 18 6
94
60 10
125*10t-3ea M12*80L bolt
25
125
25
Disconnected & Test Connected 50 15 55
260 375
5- 13
<Conductor>
Horizontal type
140
140
140
12.5
140
140
100
200
200
115
115
100
115
260 412
260 375
3P
4P
Disconnected & Test Connected 50 15
55
ARC Chute surface 90 (Insulation barrier)
34
10 1010
25
6
60 10
200 375 6- 13 Mounting hole
4- 13 87
59.5
41 18
55
12.5
25
350
98
153
270
100
55
25
12.5
15
<Conductor>
115 66.5
95
Dimensions Fixed type 5000AF (4000~5000A: AS-40~50F) Front view 765
595
280
280
150 Operating panel center
460
Vertical type
165
270 380
300
60 35 95 630
12
12
165
649
819
3P
4P
190
190
190 70
190
190
20
20
4- 14 Mounting hole
625
795
649
819
3P
4P
15
90 (Insulation barrier)
96
165 295
25 25 125 25
39.5 125 102
20.5
95
58 183
25
270
125
34 15
20
5- 13
45 67.5
20
20
165 20 4- 14 Mounting hole
65
70
165
45
20
12
45
12
80
80
60 35 95
380
300
270
150 Operating panel center
<Conductor>
Horizontal type
190
190
190
190
190
125
20
20
165
165
45
45
125
4- 14 Mounting hole
625 649
3P
4P
90 (Insulation barrier)
34 15
18
95
42 20 97
70
25
20
25 25 125
83 193
270
20
25
70
20
15
4- 14 Mounting hole
795 819
65
20
165 295
Door Frame: DF (AH-G, AS-F)
5- 13
45
<Conductor>
67.5
<Mounting hole>
<Side hole>
<Panel cutting >
Rear panel
Operating panel center 276
10- 5
315(Panel cutting size)
Door frame
Din. "W" 625 795 781 1011
<External size>
7 10
165
334
128
165 Cradle bottom
109
Cradle bottom
11.5
278 350
353(Panel cutting size)
39 21.5
200 120
352
266 388
120
W
F3 F4 G3 G4
Note) The dimensions are for drawout type.
97
Dimensions Draw-out type 5000AF (4000~5000A: AS-40~50F) Front view 20
20
689 147.5
20
20
859 232.5
Operating panel center
2-M12 Tap CMB-U/F
Operating panel center
435 460
435 460
2-M12 Tap CMB-U/F
295
205
260
260 629
799
3P
4P
190
190
190
Vertical type
70
190
20
115 200
200
295
260
260
3P
Disconnected & Test Connected 50 15 55
205
Arc chute surface
25
125
34 15
36 41 18
200
5- 13
<Conductor>
115
375 6- 13 Mounting hole
25
39.5 125 102
58 183 380
25 25 125
270
A
10
260
4P
90 (Insulation barrier)
98
190
20
115
20
260
53 .5
70
20
Horizontal type
190
190
190
190
190 125
200
200
115
115
125
295
260
260
3P
205
260
4P
Disconnected & Test Connected
50
15
Arc chute surface 55 90 (Insulation barrier)
25 5- 13
110
<Conductor>
42
97
36 41 18
25
20 83 193 380
25
270
A
125
70 110
25
20
34 15
200 10
115
375
63.5
6- 13 Mounting hole
99
Dimensions Fixed type 6300AF (4000A~6300A: AH/AS-40~50G) Front view 981
751 792
189
562
189 280
280
Operating panel center
577
204
270 380
300
12
12
60 35 95
80
12
60 35 95
80
380
300
270
Operating panel center
807
204
12
1035
805
4P
3P
4000A~5000A
6300A
34 15
25
25
25
25 25 125
25 150
25
25
25
34 15
6- 13
5- 13
<Conductor>
<Conductor>
Vertical type 244
244
244 70
244
244
20
20
20 4- 14 Mounting hole
1011
805
1035
3P
4P
4000A~5000A
6300A
90 (Insulation barrier)
165 295
100
45
70 65
67.5
42 20 97
18
95
20.5 20
39.5 125 102
20
83 193
58 183
270
20
70
125
20
15
15
90 (Insulation barrier)
270 95 65
20
165
165 20 4- 14 Mounting hole
781
70
45
45
20
20
165 295
45 67.5
Horizontal type 4000A~5000A 244
244
244
244
244
125
20
20
165
165
45
45
125
4- 14 Mounting hole
781
4- 14 Mounting hole
1011
805
1035
3P
4P
6300A 244
244
244
244
150
20
20
165
165
45
45
150
4- 14 Mounting hole
781
244
1011
805
1035
3P
4P
4- 14 Mounting hole
18
95
42 20 97
70
20
83 193
270
20
70
20
15
90 (Insulation barrier)
65
20
165 295
45 67.5
101
Dimensions Draw-out type 6300AF (4000A~6300A: AH/AS-40~50G) Front view 845
20
20 186.5
1075
20
20 301.5
Operating panel center
Operating panel center
435 460
435 460
2-M12 Tap CMB-U/F
2-M12 Tap CMB-U/F
260
113 785
343
260
260
260
1015
3P
4P
4000A~5000A
6300A
34 15
25
25
25
25 25 125
25 150
25
25
25
34 15
6- 13
5- 13
<Conductor>
<Conductor>
Vertical type 244
244
244 70
244
244
20
20
200
200
115
115
20
260
113
343
260
260
3P
260
4P
4000A~5000A
6300A
Disconnected & Test Connected 50 15 55
Disconnected & Test Connected 50 55 15
Arc chute surface
Arc chute surface 90 (Insulation barrier)
A
10
102
200 375
33 183 380 150 27
102
36 41 18
36 41 18
39.5 125 102
58 183 380
270
270
A
150
125
90 (Insulation barrier)
115
6- 13 Mounting hole
53.5
10
200 375
115
6- 13 Mounting hole
53.5
70
20
Horizontal type 4000A~5000A
244
244
244
244
244 125
200
200
115
115
125
260
113
260
260
6300A
260
343
3P
4P
244
244
244
244
244
150
200
200
115
115
150
113
260
260
260
3P
343
260
4P
Disconnected & Test Connected
50
15
55
Arc chute surface
70 20 110
90 (Insulation barrier)
42
97
36 41 18
110
83 193 380
270
20
A
10
200 375
115 63.5
6- 13 Mounting hole
103
Technical information Insulation voltage
OPEN
B (AN, AS)
B (AH)
You should keep the isolation distance between ACB and panel as below table.
CLOSE
000001
A
A
Type Fixed Draw out
A
B
AN/AS
50
150
AH
50
150
AN/AS
50
150
AH
50
0
Note) When drawing the distribution panel, it is available to use regardless of the distance between ACB and the wall of the panel because Susol ACB(draw-in/out type) extinguishes the arc in the Arc Chute and Arc Cover clearly.
Minimum isolation distance For the safety, all the electric charging parts need to be installed over minimum isolation distance.
Insulating voltage (Ui)
X
8 mm
1000V
14 mm
Bolt
Bolt
Washers 40-50Nm
Minimum isolation distance (X min)
600V
Bolt
Washers
Nut Busher 25
Screw type
104
Tightening torque Standard(kgf cm)
Tolerance
Standard(N.m)
Tolerance
M8
135
16
13.3
1.6
M10
270
32
26.5
3.2
M12
480
57
46.6
5.6
Temperature derating The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars. Circuit breakers with mixed connections have the same derating as horizontally connected breakers. For ambient temperatures greater than 60°C, consult us. Temperature inside the switchboard around the circuit breaker and its connection: Ti(IEC 60947-2)
Frame
Rated current
ACB terminal
Applicable busbar size
Horizontal type 1600AF AN-D AS-D AH-D
200A 400A
5t 50
630A 800A 1,000A
15t 50
1EA
1,250A
1,600A 2000AF AS/AH-D 3200AF AN-E AS-E AH-E
2,000A
15t 75
1EA
630A 800A 1,000A 1,250A 20t 75
1EA
1,600A
2,000A 2,500A 3,200A 4000AF AS/AH-E 5000AF AS-F 6300AF AS-G AH-G
4,000A 4,000A 5,000A 4,000A 5,000A 6,300A
10t 100 3EA 20t 125 2EA 20t 125 2EA 20t 150 2EA
5t 10t 6t 10t 8t 6t 8t 10t 6t 10t 8t 8t 10t 5t 10t 6t 10t 8t 6t 8t 10t 6t 10t 8t 8t 10t 10t 8t 10t 10t 10t 10t 10t 10t 10t 10t 10t
1EA
50 2EA 60 1EA 50 2EA 60 1EA 50 2EA 75 2EA 60 2EA 50 2EA 75 3EA 60 2EA 60 3EA 75 3EA 100 2EA 50 2EA 60 1EA 50 2EA 60 1EA 50 2EA 75 2EA 60 2EA 50 2EA 75 3EA 60 2EA 60 3EA 75 3EA 100 2EA 75 3EA 75 4EA 100 3EA 75 4EA 100 4EA 75 5EA 100 4EA 125 4EA 100 4EA 125 4EA 150 4EA
Vertical type
40°C
45°C
50°C
55°C
60°C
40°C
45°C
50°C
55°C
60°C
200A 400A
200A 400A
200A 400A
200A 400A
200A 400A
200A 400A
200A 400A
200A 400A
200A 400A
200A 400A
630A
630A
630A
630A
630A
630A
630A
630A
630A
630A
800A
800A
800A
800A
800A
800A
800A
800A
800A
800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A -
-
-
-
-
1600A 1600A 1520A 1480A 1420A
1600A 1600A 1580A 1550A 1500A
-
-
-
-
-
2000A 2000A 1940A 1860A 1780A
630A
630A
630A
630A
630A
630A
630A
630A
630A
630A
800A
800A
800A
800A
800A
800A
800A
800A
800A
800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A -
-
-
-
-
1600A 1600A 1600A 1600A 1600A
1600A 1600A 1600A 1600A 1600A
2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2500A 2500A 2500A 2400A 2300A 2500A 2500A 2500A 2500A 2400A 3200A 4000A 4000A 5000A 4000A 5000A 6300A
3200A 4000A 4000A 5000A 4000A 5000A 6300A
3100A 3900A 3920A 4900A 4000A 4900A 6170A
3000A 3800A 3860A 4800A 4000A 4820A 6040A
2900A 3640A 3800A 4700A 4000A 4750A 5900A
3200A 3200A 3120A 3050A 2950A 4000A 4000A 3950A 3800A 3680A 4000A 5000A 4000A 5000A 6300A
4000A 5000A 4000A 5000A 6300A
3960A 4950A 4000A 4950A 6220A
3900A 4900A 4000A 4870A 6160A
3880A 4850A 4000A 4850A 6100A
105