Susol ACB - Catalogo

Page 1

www.lsis.biz

Super Solution

Air Circuit Breakers


ACB

Susol Air Circuit Breakers

LSIS Made It!

Super Solution


Overview

4

External configuration

14

Internal configuration

16

Ordering

18

Ratings

22

Trip relays

26

Accessories

52

Electrical diagram

80

Dimensions

82

Technical information

Contents

Insulation voltage Temperature derating Operating conditions Installation recommendation Protective coordination

104 105 106 107 113

Standards & Approval

119

Time chart

120

Ordering sheet

123

Premium Susol ACB meets your demands for high breaking capacity, fully line-up, and optimized panel size. Various accessories and connection methods realize user-friendly handling. Susol ACB provides you with total solutions with an advanced trip relay for measurement, diagnosis, analysis, and communication as well as protective functions for absolute protective coordination and electric power monitoring system.


LSIS Super Solution series

Susol series circuit breakers are suitable for Protection of power distribution Protection of motor & its control device Controlling and disconnecting circuits

Optimum technical support for (Cascading, Discrimination, Type 2 coordination) Selecting economical protection system Quarantee safety of the installation Reducing the stress on components and damage Guarantee service continuity

Susol Manual Motor Starters


Susol Air Circuit Breakers

Susol Molded Circuit Breakers

Susol Magnetic Contactors & Overload Relays


Full line-up & Compact Up to 6300A, Susol ACB provides fully lined-up 3 frame. For each frame, there is just one size, which is smaller and more compact.

H = 430mm

It makes it possible for you to design the optimized volume panel.

W = 334mm

85kA AH-06~20D 06 08 10 13 16 20

630AF 800AF 1000AF 1250AF 1600AF 2000AF

Icu=Ics=85kA/500Vac W=334(3p), 419(4p)mm

W = 412mm

100kA AH-06~40E 06 08 10 13 16

630AF 800AF 1000AF 1250AF 1600AF

Icu=Ics=100kA/500Vac W=412(3p), 527(4p)mm

20 25 32 40

2000AF 2500AF 3200AF 4000AF


m 5m 37 = D

W = 785mm

150kA AH-40~63G 40 50 63

4000AF 5000AF 6300AF

Icu=Ics=150kA/500Vac W=785(3p), 1015(4p)mm


Trip Relay (OCR)

Trip relays are classified according to function. Trip relays are classified according to their usages and functions to maximize customers’ satisfaction. Classified trip relays and easy installation. Protection: overload, short current, ground fault, earth leakage, under voltage, over voltage, under frequency, over frequency, reverse power, unbalance, etc Measurement: voltage, ampere, power, energy, frequency, power factor, Harmonics, etc. Event & fault recording: Max. 256 events & faults Communication: Modbus/RS-485, Profibus-DP

Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism. It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides advanced functions - measurement, diagnosis, analysis, and communication.


Susol ACB Trip relay N type

L/S/I/G/Thermal Self Power RTC Timer mounted Fault information (LED)

A type

P/S type

L/S/I/G/Thermal ZSI Remote Reset Modbus/RS-485 Profibus-DP Self Power AC/DC 100~250V DC 24~60V RTC Timer mounted Fault Recording (10EA)

L/S/ I/G/Thermal(Continuous) UV/OV/OF/UF/rP/Vun/Iun Measurement: V/A/W/Wh/F/PF Harmonics (63th), Waveform (S Type) ZSI Remote Reset Modbus/RS-485 Profibus-DP AC/DC 100~250V DC 24~60V RTC Timer mounted Event Recording (256EA) Fault Recording (256EA) Fault Wave (S Type)

Trip relays series N type

A type

N Type (Normal) Self-power + Current protection

A Type (Ammeter) Current Meter + Current protection + DO control + Communication

P type

S type

P Type (Power Meter) A type + Power Meter + Voltage / Frequency / Unbalance protection

S Type (Supreme) P type + Harmonics analysis (63 th) + Fault wave recording


Accessories

ACB Trip Relay (OCR)

Auxiliary Switch (AX)

Motor (M)

Key Lock (K1),

Closing Coil (CC)

Double Key Lock (K3)

Shunt Coil (SHT)

Counter (C)

Under Voltage Trip Device (UVT)

On/Off Button Lock (B)

Door Interlock (DI)

Miss Insertion Preventing Device (MIP)

MOC (Mechanically

Automatically Discharge

Operated Cell Switch)

Mechanism (ADM)

Mechanical Interlock (MI)

Manual Reset Button (MRB)


Cradle

Other

Safety Shutter (ST)

Mechanical Interlock (MI)

Condenser Trip Device (CTD)

Manual Connector

Miss Insertion Prevent Device (MIP)

Door Frame (DF)

Zero Arc Space (ZAS)

Body Supporter (BSP)

Dust Cover (DC)

Insulation Barrier (IB)

Shorting "b" Contact (SBC)

OCR Tester (OT)

Cell Switch (CEL)

Safety Control Cover (SC)

ATS Controller (ATS)

Door Interlock (DI)

Automatically Discharge

Lifting Hook (LH)

MOC (Mechanical

Mechanism.(ADM)

Dummy ACB

Operated Cell switch)

Racking Interlock (RI)

UVT Time Delay Controller (UDC)

Safety Shutter Lock (STL)

Profibus-DP Communication module Remote I/O Temperature Alarm


Connection and Installation

Diverisified terminal connection methods of the ACB main circuit for users.


Multiple connections Various installation methods Standard connection

Horizontal type

Vertical type

Front type

Mixed connection

Horizontal / Vertical type

Vertical / Horizontal type

Vertical / Front type

Front / Horizontal type

Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current.

Horizontal / Front type

Front / Vertical type


External configuration Fixed type ACB

Terms Trip relay Counter ON button OFF button Series name Charge handle Rated name plate Charge/Discharge indicator ON/OFF indicator Corporation logo Arc cover Terminal cover Cradle Draw-out handle Position indicator Handle storage space Pad lock button Arc chute Control cover Fixed type bracket

Draw-out ACB (Cradle)

14


Cradle (Internal)

Cradle (Rear)

Terms Terminal cover of control circuit

Handle storage space

Cradle finger (Line side)

Pad lock button

Cradle finger (Load side)

Connecting conductor (Line side)

Draw-out handle

Connecting conductor (Load side)

Position indicator

Main nameplate [Acronym explanation]

[Secondary nameplate] Explanation of terminologies

Ui: Rated insulation voltage Uimp: Impulse withstand voltage Ue: Rated operational voltage (AC base) Icu: Ultimate breaking capacity Ics: Service breaking capacity Icw: Short time withstand current MFG. Date: Manufacturing date

Motor charge Control power and Closing coil terminal No. Shunt tripping coil Auxiliary switches: Contact specification and terminal No. Under voltage trip: UVT terminal No. OCR control source: Trip relay control power Alarm switch: Alarm and terminal No. Digital trip relay: Switching diagram Z.S.I: Input/Output terminal No. Reset: LED/LCD reset Communication: Communication and terminal No. Voltage module: Phase voltage and symbol Earth/Leakage: Ground fault / Earth leakage input terminal No.

15


Internal configuration

Terms Arc chute Aux. switch control terminal Control power supply terminal Trip relay control terminal Carrying grip Trip coil or UVT coil Mechanism Main body Counter Trip coil Closing coil Motor Ass’y Aux. switch ON button OFF button MTD base Trip relay Front cover

16


Terms Control circuit terminal block Control terminal Auxiliary switches Closing, Trip, UVT coil Trip relay Front cover Mechanism Charge handle Trip spring Closing spring Draw-in/out device Arc extinguishing part Moving contact Fixed contact Conductor on line side Cradle finger Cradle Connecting conductor Power supply CT Conductor on load side

17


Ordering ACB & Accessories AH

10

D

3

Type

Ampere frame

Frame sizes & phase array

No. of pole

-

AH

3P/4P

AS 06

AN

630AF

D

Standard type

3

3P(D)

RST(N) AH

AN

AS

08

800AF

10

1000AF

13

1250AF

16

1600AF

20

2000AF

W

10

J

Rated current (CT Spec.) 00

Without OCR & CT

02

200A

04

400A

06

630A

04

400A

06

630A

Connections Draw-out type J A

Manual connection Automatic connection Fixed type

4P

08

800A

H

Horizontal type

Reverse

10

1000A

V

Vertical type

13

1250A

16

1600A

M

Line: Horizontal

20

2000A

phase type

4

4P(D, W)

NRST

Mixed type Load: Vertical Mixed type

E 20

2000AF

3P/4P

06

630A

Standard

08

800A

10

1000A

13

1250A

16

1600A

4P

20

2000A

Reverse

25

2500A

32

3200A

40

4000A

type

3

3P(E)

RST(N) AH AS 25

2500AF

X

32

3200AF

phase type

40

4000AF

NRST

4

4P(E, X)

3P/4P 40

4000AF

F

Standard

3

3P(F)

40

4000A

4

4P(F, Y)

50

5000A

3

3P(G)

40

4000A

50

5000A

63

6300A

type RST(N)

AS

4P Reverse 50

5000AF

Y

phase type NRST

AH AS

18

40

4000AF

50

5000AF

63

6300AF

3P/4P G

Standard type RST(N) 4P Reverse

Z

phase type NRST

4

4P(G, Z)

N

Line: Vertical Load: Horizontal

P

Front type


M1

D1

Motor rated voltage

D1

NG0

AX

Trip relay

Shunt coil rated voltage

MA

Without Motor

D0

Without Shunt coil

M1

AC/DC 100V~130V

D1

AC/DC 100V~130V

M2

AC/DC 200V~250V

D2

AC/DC 200V~250V

M3

DC 125V

D3

DC 125V

M4

DC 24V~30V

D4

DC 24V~30V

M5

DC 48V~60V

D5

DC 48V~60V

M6

AC 380V~415V

D6

AC 380V~480V

M7

AC 440V~480V

D7

AC 48V

M8

AC 48V

Closing coil rated voltage

AL

U1

Refer to 26page

UVT coil rated voltage

Aux.contact & charging types

D0

Without Closing coil

AX

Standard OFF-Charge 3a3b

U0

Without UVT coil

D1

AC/DC 100V~130V

AC

Standard ON-Charge 3a3b

U1

AC/DC 100V~130V

D2

AC/DC 200V~250V

BX

Standard OFF-Charge 5a5b

U2

AC/DC 200V~250V

D3

DC 125V

BC

Standard ON-Charge 5a5b

U3

DC 125V

D4

DC 24V~30V

HX

High capacity OFF-Charge 5a5b

U4

DC 24V~30V

D5

DC 48V~60V

HC

High capacity ON-Charge 5a5b

U5

DC 48V~60V

D6

AC 380V~480V

CC

Standard ON-Charge 6a6b

U6

AC 380V~480V

D7

AC 48V

JC

High capacity ON-Charge 6a6b

U7

AC 48V

3)

* UVT Delay module is available over AC / DC 48V

Option

Type name

Option

AL A1 A2

AL1+MRB AL1+MRB+RES (AC110~130V) AL1+AL2+MRB

*AC private use

A3

AL1+MRB+RES (DC110~125V)

*DC private use

A4

AL1+MRB+RES (AC200~250V)

*AC private use

A5

AL1+MRB+Auto reset

A6 A7

AL1+AL2+MRB+Auto reset AL1+MRB+RES (DC110~125V)+Auto reset

*DC private use

A8

AL1+MRB+RES (AC200~250V)+Auto reset

*AC private use

A9

AL1+MRB+RES (AC110~130V)+Auto reset

*AC private use

C

C

Counter

S 2)

CS2

Charge switch communication

B M

B MI

On/Off Button lock Mechanical interlock **AN typenot applied

D

Type name DI or MOC

Door Interlock or MOC (Mechanism operated cell switch)

K

K1

Key lock

K2 K3

K2 K3 RCS

Key Interlock set Key lock double Ready to close switch

TM

Temperature monitoring AC/DC 100~130V

R 2) T 3) H1 H2 H3 H4 H5 H6 H7

AC/DC 200~250V DC 125V 1)

SHT2

DC 24~30V DC 48~60V

Double shunt coil **At using UVT, not applied

AC 380~480V AC 48V

Note) 1. UVT and SHT2 are alternative. 2. CS2 and RCS are alternative. 3. TM and CC/JC(6a6b) are alternative. 4. Other accessories should be ordered seperately.

19


Ordering Cradle AL

LS ACB cradle

N16D

Rated current & frame N16D

AN-06~16D

S20D

AS-20D

3

J

No. of pole 3

3P

4

4P

H V

S25E

H

E

Connections

Safety shutter

Horizontal type (20D inapplicable) Vertical type

AS-20~25E

E F

N

Without safety shutter With safety shutter

Mixed type

20

S32E

AS-32E

S40E

AS-40E

S50F

AS-40~50F

S50G

AS-40~50G

S63G

AS-63G

H16D

AH-06~16D

H20D

AH-20D

H32E

AH-20~32E

H40E

AH-40E

H50G

AH-40~50G

H63G

AH-63G

Terminal connections J A

M

Line: Horizontal

Manual

(20D inapplicable)

connection

Mixed type

Automatic Connection

N

Line: Vertical Load: Horizontal (20D inapplicable) Front type

P

Arc cover

Load: Vertical

(20D, 40E, 50FG, 63G inapplicable)

N S

Without Arc cover With Arc cover


Trip relay N

G

0

Trip relay type

Communication & protection

Control voltage & frequency

G

0

000 Without trip relay N N

Normal

G

Without comm. + L/S/I/G

* L/S/I/G configuration as standard -with LED indicators -without output contacts * Ground fault system by vector sum

A A

Ammeter

0

Self-Power, 60Hz

5

Self-Power, 50Hz

G

0

G

Without comm.

0

Self-Power, 60Hz

Z

Without comm. + Earth leakage

1

AC/DC 100V~250V, 60Hz

E

Without comm. + Earth leakage

2

DC 24V~60V, 60Hz

C

Comm.

5

Self-Power, 50Hz

K

Comm. + Earth leakage

6

AC/DC 100V~250V, 50Hz

X

Comm. + Earth leakage

7

DC 24V~60V, 50Hz

* L/S/I/G configuration as standard * Ground fault system by vector sum(G,C) * Earth leakage system - Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - E,X: External CT - Private ZCT applied(faullt current >30A) * Comm. And output contacts DO NOT work under self-power condition. (Only checking LED available)

P P

Power meter

C

1

C

Comm.

1

AC/DC 100V~250V, 60Hz

K

Comm. + Earth leakage

2

DC 24V~60V, 60Hz

X

Comm. + Earth leakage

6

AC/DC 100V~250V, 50Hz

A

Comm. + Pre-trip alarm

7

DC 24V~60V, 50Hz

* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose * Comm. And output contacts DO NOT work under self-power condition. (Only checking LED available)

S S

Supreme meter

C

1

C

Comm.

1

AC/DC 100V~250V, 60Hz

K

Comm. + Earth leakage

2

DC 24V~60V, 60Hz

X

Comm. + Earth leakage

6

AC/DC 100V~250V, 50Hz

A

Comm. + Pre-trip alarm

7

DC 24V~60V, 50Hz

* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose * Comm. And output contacts DO NOT work under self-power condition. (Only checking LED available)

Note) 1. L/S/I/G configuration as standard 2. Ground fault, earth leakage and pre-trip alarm functions are alternative. 3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition. 4. Voltage module should be required for P and S types(supplied seperately)

21


Ratings

Type

AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D

Ampere frame

(AF)

Rated current(A)

(In max)

Setting current (A) *

Control trip relay ( ...

at 40

630 200 400 630

800 400 630 800

400 630

400 630 800

1250

1600

2000

1000

1250

1600

2000

1600

2000

(0.4 ~ 1.0)

In max)

Rated current of neutral pole (A)

1000

1000

In max 1250

Rated insulation voltage(V)

(Ui)

1000

Rated operating voltage(V)

(Ue)

690 12 50/60 3/4

Rated impulse withstand voltage (kV)(Uimp) Frequency(Hz) Number of poles (P) Rated breaking capacity (kA sym) AC 50/60Hz

(Icu)

Rated service breaking capacity (kA) (Ics) Rated making capacity (kA peak) AC 50/60Hz

85 85 65

220V/230V/380V/415V IEC 60947-2 460V/480V/500V KS C 4620 550V/600V/690V ... % Icu

100% 187 187

220V/230V/380V/415V IEC 60947-2 (Icm) 460V/480V/500V KS C 4620 550V/600V/690V

143

1sec

65

2 sec

60

3 sec

50

Operating time (ms)

Maximum total breaking time

40

Life cycle (time)

Mechanical

Maximum closing time Without maintenance

80 20,000

With maintenance Without maintenance

30,000

Electrical

With maintenance

10,000

Rated short-time withstand current (kA)

Connections

(Icw)

Draw-out / Fixed

**

5,000 -

Horizontal connection Vertical connection

Weight (kg)

Draw-out type

63/74

70/85

61/72

68/83

Cradle only

29/32

33/40

Motor charging type

34/44

38/47

Manual charging type

32/42

36/45

3P 4P

430 334 375 430 419 375

3P

300 300 295

4P

300 385 295 N, A, P, S type

Fixed type External dimensions (mm) (H W D)

Draw-out type

H D

Fixed type

W

Trip relay

KS / KEMA / KERI / GOST

Certificate & Approval

LR, ABS, DNV, KR, BV, GL, RINA, NK

Marine clasiflcation * Refer to trip relay specification.

22

-

(With cradle) Manual charging type

Main body

(3P/4P)

Front connection Mixed connection Motor charging type

**

: Standard,

: Option


AH-06E

AH-08E

AH-10E

AH-13E

AH-16E

AH-20E

AH-25E

AH-32E

AH-40E

AH-40G

AH-50G

AH-63G

630

800

1000

1250

1600

2000

2500

3200

4000

4000

5000

6300

630

800

1000

1250

1600

2000

2500

3200

4000

4000

5000

6300

(0.4 ~ 1.0) 630

800

1000

1250

In max

1600

2000

(0.4 ~ 1.0) 2500

3200

4000

4000

In max

5000

1,000

1,000

690

690

12 50/60

12 50/60

3/4 100

3/4 150

100

150

85

100

100%

100%

220 220 187

330 330 220

85

100

75

85

65

75

40

40

80 15,000

80 10,000

20,000

15,000

5,000

2,000

10,000

5,000

-

6300

-

87/103

107/139

181/223

186/230

85/101

102/145

179/221

184/228

44/55

65/85

97/117

102/124

44/55

61/81

98/123

103/130

42/53 430 412 375

60/80

96/121 460 785 375

101/128

-

430 527 375 300 378 295

460 1015 375 300 751 295

300 493 295

300 981 295

N, A, P, S type KS / KEMA / KERI / GOST

N, A, P, S type KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK

LR, ABS, DNV, KR, BV, GL, RINA, NK

23


Ratings

Type

AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D (AF)

Ampere frame Rated current(A)

(In max)

Setting current (A) *

at 40

Control trip relay ( ...

630

800

200

400

400

630

630

800

400 630

400 630 800

1250

1600

2000

1000

1250

1600

2000

1600

2000

(0.4 ~ 1.0)

In max)

Rated current of neutral pole (A)

1000

1000

In max 1250

Rated insulation voltage(V)

(Ui)

1000

Rated operating voltage(V)

(Ue)

690 12 50/60

Rated impulse withstand voltage (kV)(Uimp) Frequency (Hz) Number of poles (P) Rated breaking capacity (kA sym) AC 50/60Hz

(Icu)

IEC 60947-2 460V/480V/500V KS C 4620 550V/600V/690V

Rated service breaking capacity (kA) (Ics) Rated making capacity (kA peak) AC 50/60Hz

(Icm)

IEC 60947-2 KS C 4620

(Icw)

Operating time (ms)

70

65

70 65

100% 143 143

100% 154 154

550V/600V/690V

105

143

1 sec

50

65

2 sec

42

55

3 sec

36

220V/230V/380V/415V 460V/480V/500V

50 40

Maximum total breaking time

Life cycle (time)

Connections

65 50

... % Icu

Rated short-time withstand current (kA)

3/4 220V/230V/380V/415V

Mechanical

Maximum closing time Without maintenance

80 20,000

With maintenance Without maintenance

30,000

Electrical

With maintenance

10,000

Draw-out / Fixed

**

5,000 -

Horizontal connection Vertical connection

Weight (kg)

Draw-out type

63/74

70/85

61/72

68/83

Cradle only

29/32

33/40

Motor charging type

34/44

38/47

Manual charging type

32/42

36/45

3P 4P 3P

430 334 375 430 419 375 300 300 295

4P

300 385 295

Fixed type External dimensions (mm) (H W D)

Draw-out type

H D

Fixed type

W

N, A, P type

Trip relay

KS / KEMA / KERI / GOST

Certificate & Approval

LR, ABS, DNV, KR, BV, GL, RINA, NK

Marine clasiflcation * Refer to trip relay specification.

24

-

(With cradle) Manual charging type

Main body

(3P/4P)

Front connection Mixed connection Motor charging type

**

: Standard,

: Option


Trip relays Event & fault recording (P, S type)

When there are events such as setting change, Info. change, error of self-diagnose, state change, P and S type record Max. up to 256 information of the events in accordance with time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults such as fault cause, fault phase, fault value and so on in accordance with time(ms).

Event information display Initial display

Setting display

1000 A R

S

T

M

N

100%

50%

Password input

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

1.Event 2.Clear All 3.Fault 4.Clear All

1. Event L 2007/05/15 20:29:41 Sta Change

10. Event L 2007/04/15 10:11:24 Cfg Change

Power On

Comm Set up

Fault information display Initial display

Setting display

1000 A R

S

T

M

N

100%

50%

Password input

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

1.Event 2.Clear All 3.Fault 4.Clear All

1. Trip 2007/04/26 08:35:52 OCR-Short

9. Trip 2007/04/11 09:11:32 UVR

Phase T

Phase R

930A

System information

P and S type can indicate information as followings with the information of the ACB. - Present time: year/month/date/hour/minute/ms - ACB current ratings - N-phase current ratings: 100% - Frequency information: 60Hz / 50Hz - Closing numbers of breaker: CB ON numbers - Trip relay operating time: OCR ON time - ON time of breaker: CB ON time - S/W ver. information

System information display Initial display

Setting display

1000 A R 100%

50%

50

S

T

N

M

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

Password input

System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR Freq 60 Hz CB ON# 23 Ver-Arm 1.41

System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR T-OPER 220 h T-CB ON 180 h Ver-Msp 1.01

OV


System block diagram

R

S

T

N ACB Trip

ACB Vcc/+9V/-9V

CN2-1 CN2-11

Filter Amp.

CN2-3 CN2-13

Signal CT

CN2-5 CN2-15

Vcc

CPU Output Power PCB Ass’y

+5V

+24V

Display (LED, LCD) Main PCB Ass’y

MTD CN2-6 Output CN2-8

Main PCB Ass’y

CN2-7 CN2-16 CN2-14

Setting part GND 24

CN2-4

Vcc

Self power

RY0 (K1) CN4-2 GTD contact

+24V GND+24V

Power CT Main PCB Ass’y

RY1 (K2) CN4-4 STD/INST contact

+5V RY2 (K3)

-5V

CN4-6 LTD contact

CN2-2

CN4-9

SMPS

CN4-10

Power PCB Ass’y

CN4-8 Common contact

Trip relay

Additional source AC/DC 100~250V DC 24~60V

CN1-1 ZSI output+ terminal CN1-2 ZSI output- terminal CN1-3 ZSI input+ terminal CN1-4 ZSI input- terminal

CN1-9

VDM

CN1-10 CN1-11 CN1-12

CN1-5 Remote reset+ terminal CN1-6 Remote reset- terminal

CN1-7

Earth

CN1-8

CN1-7 Earth leakage+ terminal

Input signal(R phase) CN3-2 Input signal S phase CN3-4

CN1-8 Earth leakage- terminal

Input signal T phase CN3-6 Input signal N phase CN3-8 DC 24V

CN3-5

UTXO

CN3-1

URXO

CN3-3

GND 24V

CN3-7/9

AD GND

CN3-10

Test

Main PCB Ass’y

Comm. Power PCB Ass’y

CN4-1 485+ terminal CN4-3 485- terminal

51


Accessories

Mounting

Accessories

Standard Option Standard Option Standard Option

Remark Page 54

SHT2 Double Shunt Coil

M

*

55

Closing Coil

*

56

Motor

*

57

Charge Switch

*

57

CS2

Charge Switch Communication

*

57

UVT

Under Voltage Trip Device

*

58

AL

Trip Alarm Contact

MRB Manual Reset Button RES

Remote Reset Switch

C AX

*

59

*

59

*

60

*

60

Counter

*

67

Auxiliary Switch

*

61

RCS Ready to Close Switch

TM

Temperature Alarm

*

78

K1

Key Lock

*

62

K2

Key Interlock Set

*

62

K3

Double Key Lock

*

63

On/Off Button lock

*

B LH CTD ATS DC

63

Lifting Hook

64

Condenser Trip Device

64

Automatic Transfer

65

Switch Controller Dust Cover

67

DF

Door Frame

71

OT

OCR Tester

66

J

Manual Connector

*

A

Automatic Connector

*

* Seperate purchasing is not allowed. Each item should be purchased with the main body.

52

AN

*

CS1

External

AS

SHT1 Shunt Coil

CC

Internal

AH


Mounting

Accessories N

Trip relay

AH

AS

AN

Standard Option Standard Option Standard Option

Remark Page

N type

*

28

A

A type

*

30

P

P type

*

32

S VM

S type

*

34

Voltage Module

**

38

ZCT ZCT for the earth leakage SBC

Cradle

Shorting "b" Contact

73

MI

Mechanical Interlock

ST

Safety Shutter

69

STL

Safety Shutter Lock

70

MIP

Miss Insertion Prevent Device

76

*

70

MOC Mechanical Operated Cell Switch

68

CEL

72

DI ZAS SC BSP

Cell Switch Door Interlock Zero Arc Space Safety Control Cover Body Supporter

69 *

73

***

74

*

74

RI

Racking Interlock

PL

Pad Lock/ Position Lock

*

75

IB

Insulation Barrier

*

71

UDC UVT Time Delay Controller ADP

75

77

Compatible Adapter

RPH Reverse Phase ACB DUM Dummy ACB Other

VAD

Various Connection Type

RCO Remote I/O PC

Profibus-DP comm. module

13 79 49

* Seperate purchasing is not allowed. Each item should be purchased with the main body. ** Voltage module should be purchased with P/S type trip relay. *** It is available only when the control block is in the mode of auto-connection.

53


Accessories Shunt Coil [SHT1]

SHT1 is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 200ms to coil terminals(C1, C2).

Shunt coil 1

When UVT coil is installed, its location is changed.

1. Rated voltage and characteristics of Trip coil Rated voltage [Vn] Opening order C1 SHT1 C2

* The dotted Userline to be made by the Wiring Diagram customer

Wiring Diagram

DC [V]

AC [V]

Power consumption (VA or W) Operating voltage range [V]

24~30

-

48~60

48

0.6~1.1 Vn

100~130

100~130

0.56~1.1 Vn

200~250

200~250

0.56~1.1 Vn

-

380~480

0.56~1.1 Vn

Inrush

Steady-state

200

5

Trip time [ms]

0.6~1.1 Vn Less than 40ms

Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG

#14 AWG

#16 AWG

(2.08mm2)

(1.31mm2)

(2.08mm2)

(1.31mm2)

100%

95.7m

61m

457.8m

287.7m

85%

62.5m

38.4m

291.7m

183.2m

Wire type Operating voltage

54

DC/AC 48 [V]

#14 AWG


Double Shunt Coil [SHT2]

Shunt coil 1

SHT2 is a control device which trips a circuit breaker doubly from the outside. When SHT1 doesn’t operate normally, it can trip a circuit breaker safely.

Shunt coil 2

Shunt coil 1: Install it at existing location. Shunt coil 2: Install it on the right side of the Shunt coil 1 It is not available with UVT coil when installing double shunt coil.

1. Rated voltage and characteristics of Trip coil Rated voltage [Vn] Opening order C11 SHT2

DC [V]

AC [V]

Power consumption (VA or W) Operating voltage range [V]

24~30

-

0.6~1.1 Vn

48~60

48

0.6~1.1 Vn

100~130

100~130

0.56~1.1 Vn

200~250

200~250

0.56~1.1 Vn

-

380~480

0.56~1.1 Vn

Inrush

Steady-state

200

5

Trip time [ms]

Less than 40ms

C12 Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).

* The dotted line to be made by the customer

Wiring Diagram

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG

#14 AWG

#16 AWG

(2.08mm2)

(1.31mm2)

(2.08mm2)

(1.31mm2)

100%

95.7m

61m

457.8m

287.7m

85%

62.5m

38.4m

291.7m

183.2m

Wire type Operating voltage

DC/AC 48 [V]

#14 AWG

55


Accessories Closing Coil [CC]

It is a control device which closes a circuit breaker, when the voltage is applied continuously or instantaneously over 200ms to the coil terminals (A1, A2).

Closing coil

1. Rated voltage and characteristics of Closing coil Rated voltage [Vn] Closing order

A1 CC A2

* The dotted line to be made by the customer

Wiring Diagram

DC [V]

AC [V]

Power consumption (VA or W) Operating voltage range [V]

24~30

-

48~60

48

0.75~1.1 Vn

100~130

100~130

0.75~1.1 Vn

200~250

200~250

0.75~1.1 Vn

-

380~480

0.75~1.1 Vn

Inrush

Steady-state

200

5

Shunt time [ms]

0.75~1.1 Vn Less than 80ms

Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG

#14 AWG

#16 AWG

(2.08mm2)

(1.31mm2)

(2.08mm2)

(1.31mm2)

100%

95.7m

61m

457.8m

287.7m

85%

62.5m

38.4m

291.7m

183.2m

Wire type Operating voltage

56

DC/AC 48 [V]

#14 AWG


Motor [M]

Charge the closing spring of a circuit breaker by the external power source. Without the external power source, charge manually.

Motor

Operating voltage range(IEC 60947) 85%~110%Vn

Gear

Main axis

Fully charged contact

Charge switch

Input voltage(V) Load current(max.)

DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V 5A

3A

1A

0.5A

Starting current(Max.)

5 times of load current

Load rpm(Motor)

15000 ~ 19000 rpm

Charge time Dielectric strength Using temperature range Using humidity range Endurance Charge switch

AC 380V

AC 440~480V

0.3A

0.3A

Less than 5sec. 2kV/min -20 ~ 60 Max. RH 80% (No dew condensation) 15,000 cycle (Load connection, 2 times/min) 10A at 250VAC

Charge Switch [CS1] Charge Switch Communication [CS2]

It is a built-in contact which sends the signal to the outside, when motor charging is completed. (2a) It has a “1a” contact for communication and the other “1a” contact for complete charging. When using an extra communication module (Remote I/O), the state of contacts can be displayed through the network. 10A at 250VAC

57


Accessories Under Voltage Trip device [UVT]

UVT coil

If the voltage of the main or the control power is under voltage, UVT which is installed inside of the breaker breaks the circuit automatically. Please connect with UVT time-delay device in order to present the timedelay function because UVT is technically instantaneous type.

Shunt coil

The closing of a circuit breaker is impossible mechanically or electrically if control power not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied to both terminals of UVT coil (D1, D2).

Closing coil

When using UVT coil, the double trip coil can not be used, and the location of trip coil is changed.

1. Rated voltage and characteristics of UVT coil Rated voltage [Vn] DC [V]

AC [V]

24~30

-

48~60

48

100~130

100~130

200~250

200~250

-

380~480

Operating voltage range [V]

Power consumption (VA or W)

Pick up

Drop out

Inrush

Steady-state

0.65~0.85 Vn

0.4~0.6 Vn

200

5

Trip time [ms]

Less than 50ms

Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG

#14 AWG

#16 AWG

(2.08mm2)

(1.31mm2)

(2.08mm2)

(1.31mm2)

100%

48.5m

30.5m

233.2m

143.9m

85%

13.4m

8.8m

62.5m

39.3m

Wire type Operating voltage

Note) In case of using UVT coil, the location of TC coil is changed.

58

DC/AC 48 [V]

#14 AWG


Trip Alarm Contact [AL]

AL1, 1a AL2, 1a

When a circuit breaker is tripped by OCR which operates against the fault current (Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from the mechanical indicator on main cover of main circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker) When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the main cover and the switch (AL) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. MRB and AL can be operated only when tripping by OCR, but doesn’t be operated by Off button and OFF operation of trip coil. To re-close a circuit breaker after a trip, press MRB to reset it for closing. 2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option) Trip alarm contact and MRB(Manual reset bottom) need to be purchased together. 1. Electrical characteristics of trip alarm contact Rated voltage [V]

Non-inductive load (A) Resistive load

Inductive load (A)

lamp load

Inductive load(A)

Motor load

8V DC

11

3

6

3

30V DC

10

3

6

3

125V DC

0.6

0.1

0.6

0.1

250V DC

0.3

0.05

0.3

0.05

250V AC

11

1.5

6

2

Inrush current

MAX. 24A

Manual Reset Button [MRB] It is a function which resets a circuit breaker manually when a circuit breaker is tripped by OCR. When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the main cover and the switch(SDE) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a circuit breaker after a trip, press MRB to reset it for closing.

Manual reset button Manual reset button

MRB reset lever Note) The manual reset button is protruded in the event of trip.

59


Accessories Remote Reset Switch [RES]

Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical indicator(MRB) and enables circuit breaker closing. Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load In case of auto reset type circuit breaker Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is no longer required to enable circuit breaker closing. The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset button is pressed. AL2 and RES are alternative. 1. Rated voltage and rated current of RES Rated voltage Reset order 183 RES

AC/DC 100~130V AC/DC 200~250V

Operating current(Max.) AC

6A

DC

5A

AC

3A

DC

2.5A

Operating time

Wire spec. #14 AWG (2.08 mm2)

Less 40ms #16 AWG (1.31 mm2)

Connect to inner micro switch

184 Connect to AL2 / RES

* The dotted line to be made by the customer

Wiring Diagram

Ready to Close Switch [RCS] It interlocks with mechanism of circuit breaker. It indicates the status that the circuit breaker is ready to do closing operation. Ready to close switch

“A” contact Contact part

60

When mechanism is in OFF position or in Charge, contact is output with “ON” and it indicates that mechanism can be closed.


Dimensions Draw-out type 2000AF (630~1600A: AH/AN/AS-06~16D) Front view

20

20

394

20

20

479

167

167

42.5

2-M12 Tap CMB-U/F

405 430

405 430

2-M12 Tap CMB-U/F

85

260 334

260 419

4P

3P

Vertical type

85

85

85

15

85

85

200

200

115

115

15

260 334

85

260 345

3P

4P

Disconnected & Test Connected

50 15

55

ARC Chute surface 90 (Insulation barrier)

35

97

41 18

2- 13

6

60 10

200 375 6- 13 Mounting hole

84

115 38.5

<Conductor>

50

133 350

25

270

50

15


Horizontal type

85

85

85

85

85

50

200

200

115

115

50

85

260 334

260 345

3P

4P

Disconnected & Test Connected 50 15

55

ARC Chute surface 90 (Insulation barrier)

35

350

133

270

50

25

15

15

2- 13

97

41 18

<Conductor>

6

60

200 375 4- 13 Mounting hole

10

85

38.5

85

85

85

85

50

200

200

115

115

50

260 334

85

260 345

3P

4P

Disconnected & Test Connected 50 15

ARC Chute surface

55

25

200

13.5

25

483

50

270

15

2- 13

200

41 18

<Conductor>

6

4- 13 Mounting hole 60 10

200 375

78

Front connection type

115

115 11.5

85


Dimensions Fixed type 2000AF (2000A: AH/AS-20D) Front view 300 280

385 280 150

150

165

12

Vertical type

165

270 12

12

250 439

3P

4P

85

85

85

85 15

20

20

165

165

25

25

45

45

15

4- 14 Mounting hole

4- 14 Mounting hole

330 354

415 439

3P

4P

15

90 (Insulation barrier)

35

75 25

133 67

75

58

25

270

75

30 15

20

165 295

3- 13

<Conductor>

45 32.5

29.5

65

86

12

165

354

85

320

35

300 20

20

35

270

Operating panel center

320

300

Operating panel center


Draw-out type 2000AF (2000A: AH/AS-20D) Front view 20

20

394

20

20

479 42.5

167

2-M12 Tap CMB-U/F

405 430

405 430

2-M12 Tap CMB-U/F

167

260

Vertical type

85

260

334

419

3P

4P

85

85

85

15

85

85

200

200

115

115

15

260

85

260 334

345

3P

4P

Disconnected & Test Connected

50 15

55

ARC Chute surface 90 (Insulation barrier)

35

75 133 350

25

270

75

25

15

97

41 18

3- 13

6

60 10

200 375

<Conductor>

115 38.5

6- 13 Mounting hole

87


Dimensions Fixed type 4000AF (2000~3200A: AH/AN/AS-20~32E) Front view 493

378 189

304

189

189 280

280

204

12

12

270 320

300 20

12

204

35

270 320

Operating panel center

35

20

300

Operating panel center

204

319

3P

Vertical type

115

4P

115

115

115

115

20

45 20

20

165

165

25

25

45

20

4- 14 Mounting hole

4- 14 Mounting hole

408 432

523 547

3P

4P

15

90 (Insulation barrier)

65

20

165 295

45 32.5

29.5

35

75 25

133 67

75

58

25

270

75

30 15

88

12

547

432

3- 13

<Conductor>


Horizontal type

115

115

115

115

115 75

165

20

20

165

25

25

45

45

75

4- 14 Mounting hole

4- 14 Mounting hole 523 547

408 432

3P

4P

15

90 (Insulation barrier)

75 25

133

32.5

115

115

115

115 75

45 20

20

165

165

25

25

45

75

5.5

115

4- 14 Mounting hole

4- 14 Mounting hole

408 432

523

3P

4P

547

25

212.5

15

55

19.5

25

483

75

270

25

15

3- 13

<Conductor>

108

212.5

35

Front connection type

<Conductor>

45

165 295

5.5

20

65

3- 13

67

35

57 20

113

25

270

20

30 15

65

20

165 295

45 5.5

89


Dimensions Draw-out type 4000AF (2000~3200A: AH/AN/AS-20~32E) Front view

20

20

472

20

20

206

2-M12 Tap CMB-U/F

405 430

405 430

2-M12 Tap CMB-U/F

20

587 57.5

206

115

260 412

260 375 527

3P

Vertical type

115

4P

115

115

20

115

115

200

200

115

115

20

115

260 412

260 375

3P

4P

Disconnected & Test Connected

50

15

55

ARC Chute surface 90

34

(Insulation barrier)

350

133

270

75

25

75

25

15

3- 13

97

41 18

<Conductor>

6

60 10

115

200 375

6- 13 Mounting hole

90

38.5


115

Horizontal type

115

115

115

115

75

200

200

115

115

75

260

260

115

412

375

3P

4P

Disconnected & Test Connected 50 15

55

ARC Chute surface 90 (Insulation barrier) 34

25

133 350

270

75

25

20

15

97

41 18

3- 13

<Conductor>

6

60

200

10

115 38.5

375 6- 13 Mounting hole

115

115

115

115

115 75

200

200

115

115

75

260 412

115

260 375

4P

3P Disconnected & Test Connected 50 15

ARC Chute surface 25

55 13.5

483

270

25

75

25

212.5

15

3- 13

212.5

41 18

<Conductor>

6

4- 13 Mounting hole 60 10

200 375

78

Front connection type

115 11.5

91


Dimensions Fixed type 4000AF (4000A: AH/AS-40E) Front view

378

493

189

304

189

189

280

280

204

204

300 20

270 320

270 320

35 319

12

3P

4P

150

150 17.5

10

150

150 17.5

15

10

15

165 20

20 4- 14 Mounting hole

408 432

3P

4- 14 Mounting hole

523 547

4P

15

90 (Insulation barrier)

20

165 295

45 112.5

4.5

35

25 25 125

67

25

125

33 158

270

25

125

34 15

65

92

15

25 165

25

45

15

12

204 547

150

Vertical type

12

432

45

12

Operating panel center

35

20

300

Operating panel center

5- 13

<Conductor>


Horizontal type

140

140

140

140

100

140 100

165

25

20

20

165

25

45

45

12.5

4- 14 Mounting hole

4- 14 Mounting hole

408 432

523

3P

4P

547

15

90 (Insulation barrier) 34

12.5

57 20

165 295

45 65.5

29.5

35 65

10 1010

25

55

25

100

98 153

25

270

55

12.5

15

4- 13

<Conductor>

93


Dimensions Draw-out type 4000AF (4000A: AH/AS-40E) Front view 20

20

472

20

206

2-M12 Tap CMB-U/F

405 430

405 430

2-M12 Tap CMB-U/F

20

587 57.5

206

260 412

115

260 375 527

3P 4P

Vertical type

150 17.5

150 15

150

150

10

40

15

150 40

200

200

115

115

10

115

260 412

3P

4P

ARC Chute surface

90 (Insulation barrier)

34 15

15 10 15

125 25

125

25

350

33

158

270

200 375 4- 13 Mounting hole

115 98.5

22

84.5

41 18 6

94

60 10

125*10t-3ea M12*80L bolt

25

125

25

Disconnected & Test Connected 50 15 55

260 375

5- 13

<Conductor>


Horizontal type

140

140

140

12.5

140

140

100

200

200

115

115

100

115

260 412

260 375

3P

4P

Disconnected & Test Connected 50 15

55

ARC Chute surface 90 (Insulation barrier)

34

10 1010

25

6

60 10

200 375 6- 13 Mounting hole

4- 13 87

59.5

41 18

55

12.5

25

350

98

153

270

100

55

25

12.5

15

<Conductor>

115 66.5

95


Dimensions Fixed type 5000AF (4000~5000A: AS-40~50F) Front view 765

595

280

280

150 Operating panel center

460

Vertical type

165

270 380

300

60 35 95 630

12

12

165

649

819

3P

4P

190

190

190 70

190

190

20

20

4- 14 Mounting hole

625

795

649

819

3P

4P

15

90 (Insulation barrier)

96

165 295

25 25 125 25

39.5 125 102

20.5

95

58 183

25

270

125

34 15

20

5- 13

45 67.5

20

20

165 20 4- 14 Mounting hole

65

70

165

45

20

12

45

12

80

80

60 35 95

380

300

270

150 Operating panel center

<Conductor>


Horizontal type

190

190

190

190

190

125

20

20

165

165

45

45

125

4- 14 Mounting hole

625 649

3P

4P

90 (Insulation barrier)

34 15

18

95

42 20 97

70

25

20

25 25 125

83 193

270

20

25

70

20

15

4- 14 Mounting hole

795 819

65

20

165 295

Door Frame: DF (AH-G, AS-F)

5- 13

45

<Conductor>

67.5

<Mounting hole>

<Side hole>

<Panel cutting >

Rear panel

Operating panel center 276

10- 5

315(Panel cutting size)

Door frame

Din. "W" 625 795 781 1011

<External size>

7 10

165

334

128

165 Cradle bottom

109

Cradle bottom

11.5

278 350

353(Panel cutting size)

39 21.5

200 120

352

266 388

120

W

F3 F4 G3 G4

Note) The dimensions are for drawout type.

97


Dimensions Draw-out type 5000AF (4000~5000A: AS-40~50F) Front view 20

20

689 147.5

20

20

859 232.5

Operating panel center

2-M12 Tap CMB-U/F

Operating panel center

435 460

435 460

2-M12 Tap CMB-U/F

295

205

260

260 629

799

3P

4P

190

190

190

Vertical type

70

190

20

115 200

200

295

260

260

3P

Disconnected & Test Connected 50 15 55

205

Arc chute surface

25

125

34 15

36 41 18

200

5- 13

<Conductor>

115

375 6- 13 Mounting hole

25

39.5 125 102

58 183 380

25 25 125

270

A

10

260

4P

90 (Insulation barrier)

98

190

20

115

20

260

53 .5

70

20


Horizontal type

190

190

190

190

190 125

200

200

115

115

125

295

260

260

3P

205

260

4P

Disconnected & Test Connected

50

15

Arc chute surface 55 90 (Insulation barrier)

25 5- 13

110

<Conductor>

42

97

36 41 18

25

20 83 193 380

25

270

A

125

70 110

25

20

34 15

200 10

115

375

63.5

6- 13 Mounting hole

99


Dimensions Fixed type 6300AF (4000A~6300A: AH/AS-40~50G) Front view 981

751 792

189

562

189 280

280

Operating panel center

577

204

270 380

300

12

12

60 35 95

80

12

60 35 95

80

380

300

270

Operating panel center

807

204

12

1035

805

4P

3P

4000A~5000A

6300A

34 15

25

25

25

25 25 125

25 150

25

25

25

34 15

6- 13

5- 13

<Conductor>

<Conductor>

Vertical type 244

244

244 70

244

244

20

20

20 4- 14 Mounting hole

1011

805

1035

3P

4P

4000A~5000A

6300A

90 (Insulation barrier)

165 295

100

45

70 65

67.5

42 20 97

18

95

20.5 20

39.5 125 102

20

83 193

58 183

270

20

70

125

20

15

15

90 (Insulation barrier)

270 95 65

20

165

165 20 4- 14 Mounting hole

781

70

45

45

20

20

165 295

45 67.5


Horizontal type 4000A~5000A 244

244

244

244

244

125

20

20

165

165

45

45

125

4- 14 Mounting hole

781

4- 14 Mounting hole

1011

805

1035

3P

4P

6300A 244

244

244

244

150

20

20

165

165

45

45

150

4- 14 Mounting hole

781

244

1011

805

1035

3P

4P

4- 14 Mounting hole

18

95

42 20 97

70

20

83 193

270

20

70

20

15

90 (Insulation barrier)

65

20

165 295

45 67.5

101


Dimensions Draw-out type 6300AF (4000A~6300A: AH/AS-40~50G) Front view 845

20

20 186.5

1075

20

20 301.5

Operating panel center

Operating panel center

435 460

435 460

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

260

113 785

343

260

260

260

1015

3P

4P

4000A~5000A

6300A

34 15

25

25

25

25 25 125

25 150

25

25

25

34 15

6- 13

5- 13

<Conductor>

<Conductor>

Vertical type 244

244

244 70

244

244

20

20

200

200

115

115

20

260

113

343

260

260

3P

260

4P

4000A~5000A

6300A

Disconnected & Test Connected 50 15 55

Disconnected & Test Connected 50 55 15

Arc chute surface

Arc chute surface 90 (Insulation barrier)

A

10

102

200 375

33 183 380 150 27

102

36 41 18

36 41 18

39.5 125 102

58 183 380

270

270

A

150

125

90 (Insulation barrier)

115

6- 13 Mounting hole

53.5

10

200 375

115

6- 13 Mounting hole

53.5

70

20


Horizontal type 4000A~5000A

244

244

244

244

244 125

200

200

115

115

125

260

113

260

260

6300A

260

343

3P

4P

244

244

244

244

244

150

200

200

115

115

150

113

260

260

260

3P

343

260

4P

Disconnected & Test Connected

50

15

55

Arc chute surface

70 20 110

90 (Insulation barrier)

42

97

36 41 18

110

83 193 380

270

20

A

10

200 375

115 63.5

6- 13 Mounting hole

103


Technical information Insulation voltage

OPEN

B (AN, AS)

B (AH)

You should keep the isolation distance between ACB and panel as below table.

CLOSE

000001

A

A

Type Fixed Draw out

A

B

AN/AS

50

150

AH

50

150

AN/AS

50

150

AH

50

0

Note) When drawing the distribution panel, it is available to use regardless of the distance between ACB and the wall of the panel because Susol ACB(draw-in/out type) extinguishes the arc in the Arc Chute and Arc Cover clearly.

Minimum isolation distance For the safety, all the electric charging parts need to be installed over minimum isolation distance.

Insulating voltage (Ui)

X

8 mm

1000V

14 mm

Bolt

Bolt

Washers 40-50Nm

Minimum isolation distance (X min)

600V

Bolt

Washers

Nut Busher 25

Screw type

104

Tightening torque Standard(kgf cm)

Tolerance

Standard(N.m)

Tolerance

M8

135

16

13.3

1.6

M10

270

32

26.5

3.2

M12

480

57

46.6

5.6


Temperature derating The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars. Circuit breakers with mixed connections have the same derating as horizontally connected breakers. For ambient temperatures greater than 60°C, consult us. Temperature inside the switchboard around the circuit breaker and its connection: Ti(IEC 60947-2)

Frame

Rated current

ACB terminal

Applicable busbar size

Horizontal type 1600AF AN-D AS-D AH-D

200A 400A

5t 50

630A 800A 1,000A

15t 50

1EA

1,250A

1,600A 2000AF AS/AH-D 3200AF AN-E AS-E AH-E

2,000A

15t 75

1EA

630A 800A 1,000A 1,250A 20t 75

1EA

1,600A

2,000A 2,500A 3,200A 4000AF AS/AH-E 5000AF AS-F 6300AF AS-G AH-G

4,000A 4,000A 5,000A 4,000A 5,000A 6,300A

10t 100 3EA 20t 125 2EA 20t 125 2EA 20t 150 2EA

5t 10t 6t 10t 8t 6t 8t 10t 6t 10t 8t 8t 10t 5t 10t 6t 10t 8t 6t 8t 10t 6t 10t 8t 8t 10t 10t 8t 10t 10t 10t 10t 10t 10t 10t 10t 10t

1EA

50 2EA 60 1EA 50 2EA 60 1EA 50 2EA 75 2EA 60 2EA 50 2EA 75 3EA 60 2EA 60 3EA 75 3EA 100 2EA 50 2EA 60 1EA 50 2EA 60 1EA 50 2EA 75 2EA 60 2EA 50 2EA 75 3EA 60 2EA 60 3EA 75 3EA 100 2EA 75 3EA 75 4EA 100 3EA 75 4EA 100 4EA 75 5EA 100 4EA 125 4EA 100 4EA 125 4EA 150 4EA

Vertical type

40°C

45°C

50°C

55°C

60°C

40°C

45°C

50°C

55°C

60°C

200A 400A

200A 400A

200A 400A

200A 400A

200A 400A

200A 400A

200A 400A

200A 400A

200A 400A

200A 400A

630A

630A

630A

630A

630A

630A

630A

630A

630A

630A

800A

800A

800A

800A

800A

800A

800A

800A

800A

800A

1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A -

-

-

-

-

1600A 1600A 1520A 1480A 1420A

1600A 1600A 1580A 1550A 1500A

-

-

-

-

-

2000A 2000A 1940A 1860A 1780A

630A

630A

630A

630A

630A

630A

630A

630A

630A

630A

800A

800A

800A

800A

800A

800A

800A

800A

800A

800A

1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A -

-

-

-

-

1600A 1600A 1600A 1600A 1600A

1600A 1600A 1600A 1600A 1600A

2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2500A 2500A 2500A 2400A 2300A 2500A 2500A 2500A 2500A 2400A 3200A 4000A 4000A 5000A 4000A 5000A 6300A

3200A 4000A 4000A 5000A 4000A 5000A 6300A

3100A 3900A 3920A 4900A 4000A 4900A 6170A

3000A 3800A 3860A 4800A 4000A 4820A 6040A

2900A 3640A 3800A 4700A 4000A 4750A 5900A

3200A 3200A 3120A 3050A 2950A 4000A 4000A 3950A 3800A 3680A 4000A 5000A 4000A 5000A 6300A

4000A 5000A 4000A 5000A 6300A

3960A 4950A 4000A 4950A 6220A

3900A 4900A 4000A 4870A 6160A

3880A 4850A 4000A 4850A 6100A

105