Industrial Inverter for Fan and Pump
STARVERT iP5A 0.75~30kW (1~40HP) 3Phase 200~230Volts 0.75~450kW (1~600HP) 3Phase 380~480Volts 5.5~110kW (7.5~150HP) 3Phase 525~600Volts
STARVERT iP5A LS Starvert SV-iP5A has been specifically designed and created to provide competitive solutions for fan and pump applications
2
Industrial Inverter for Fan and Pump STARVERT iP5A
Specialized Functions for Fan and Pump
Marine Type Certification From DNV
Energy Saving and High Efficiency
User-friendly Interface and Easy Maintenance
STARVERT
iP5A
Contents
4 8 9 13 17 19 22 23 24 37 39 45 50
Intelligent Control Mechanism
Overview Model & Type Standard Specifications Wiring Terminal Configurations (Power Circuit Terminal) Terminal Configurations (Control Circuit Terminal) Programming Keypad Programming Keypad (Parameter Navigation) Parameter Description Trial Run Dimensions DB (Dynamic Braking) Unit External DB Resistor / Peripheral Device
3
iP5A
Specialized Functions for Fan and Pump The iP5A, specifically designed for HVAC application, provides stable and cost-effective system performance.
PID Control In the centrifugal fan and pump field, PID control is provided as a standard function in order to maintain a constant control of pressure, flow and oil level. This function includes Pre-PID, Sleep and Wake up and output inverse subfunctions.
Dual PID Where external or cascaded PID control is required, the built-in dual PID algorithm of the iP5A can be utilized to satisfy various system requirements.
Multi Motor Control (0.75~450kW) The iP5A MMC function provides cost-effective, simultaneous control of up to eight motors, without requiring external controllers.
Marine Type Certification From DNV The iP5A has been tested and certified by DNV to comply with International Marine requirements
4
Industrial Inverter for Fan and Pump STARVERT iP5A
Energy Saving and High Efficiency The iP5A, specifically designed for fan and pump applications, guarantees energy savings by optimizing the system.
Sleep and Wake-up Function Energy savings are obtained through the Sleep and Wake-Up functions of the iP5A, which enable the drive to automatically switch off during user-programmed low-load conditions and then to start up again when process demand increases. Sleep mode Adjusting output with detecting load
Output frequency PID reference
(Energy saving)
Wake-up mode Returning to normal state
PID feedback
Run command
Pre Heating Function When using the inverter in damp conditions, this function protects both the motor and the inverter's output
Flying Start Function When 2 or more fans, or a high inertia load are connected to the inverter, the iP5A detects the motor speed after a momentary power failure, enabling the motors to be smoothly reaccelerated without mechanical and electrical shockloading to the system.
Automatic Energy Saving Load change may incur energy losses but the optimized flux control of iP5A results in more outstanding energy saving compared to previous models. Reduction percentage 0.75
600 RPM
Damper control Conventional inverter control
V/F 30% manual energy saving
0.50 0.40
Automatic energy saving
0.25
iP5A
0.20 0.10 0
10
20
30
40
50
60
70
Load %
5
iP5A
Intelligent Control Because of effectual functions and protection algorithms, the iP5A provides constant performance, in spite of external power fluctuations.
Constant and Stable Performance In spite of external voltage fluctuations and lightning surges, the iP5A optimizes motor performance.
Improved System Management during Power Dips and Momentary Power Outages During Power Dips or Momentary Power Outage, the inverter output can be maintained by utilizing the residual mechanical energy in the load as a regenerative source. The duration of the power-dip ride-through depends on the load characteristics.
Emitted energy
Power failure for 1 second
Power failure for 3 seconds
The mechanical energy stored during blackout can be used for inverter’s power. Mechanical energy
Mecha -nical energy
Load Consumed energy
Safety Stop During unexpected power failure conditions, the iP5A can bring the load to a controlled stop, by utilizing the inertial energy. This can prevent further process problems or accidents.
Current Leakage Reduction Algorithm Under damp conditions, leakage currents can occur when using inverters. These currents can cause a system failure. The iP5A low-leakage PWM algorithm reduces these leakage currents to ensure reliability of operation.
PWM
Zero vector
Valid vector
Zero vector
Valid vector
Flux Braking Algorithm This algorithm reduces deceleration time, thereby improving system efficiency.
Automatic Carrier Frequency Change By taking ambient temperature into account, the iP5A can automatically adjust the Carrier (Modulation) Frequency.
Protection The iP5A has optimized protective functions, such as safety stop and pre-excitation of the motor, amongst others.
6
Industrial Inverter for Fan and Pump STARVERT iP5A
User-friendly Keypad & Easy Maintenance The iP5A construction allows for easy maintenance, with ease-of-access to all components.
8
3
5
Easy Start When pushing‘STOP’key for 2~3 seconds in case inverter turns on, the inverter turns into ‘Easy Start Mode’with FWD, REV, and STOP command. ‘SHIFT/ESC’can return it to previous mode. Control method: V/F Control frequency: Jog
1 4 2 6
7 9
1
NPN/PNP Input
4
iP5A has both NPN and PNP input, and you can select one of them easily. 2
The built-In RS485 allows for communication without external option. However, the optional communication boards enable the iP5A to talk to BMS and most Industrial Systems
Abundant I/O Suggestion 5
iP5A serves abundant I/O. Digital Input/Output Analog Input (Voltage + Current)/Output Pulse Input NTC/PTC Input
3
Built-in RS485 and Optional Communication
8 points / 4 points (1+1) points /4 points 1 point 1 point
iP5A adopts long-life condenser and enables easy maintenance in simple framework. 6
Consumption Time Display iP5A displays consumption time of components so that users can replace them in time.
Various Units of I/O Display The iP5A display can be calibrated in many different types of process units.
Long-life Condenser and Simple Framework
7
Others •Removable terminal board •External fan available •Cooling fan on/off control
7
iP5A
Model & Type 380~480V Class (Classification)
525~600V Class
SV055iP5A-4NE
SV055iP5A-4NE (CLASS)
SV0055iP5A-6
SV075iP5A-4NE
SV075iP5A-4NE (CLASS)
SV0075iP5A-6
SV110iP5A-2NE
SV110iP5A-4NE
SV110iP5A-4NE (CLASS)
SV0110iP5A-6
15kW (20HP)
SV150iP5A-2NO
SV150iP5A-4NO
SV150iP5A-4NOL (CLASS)
SV0150iP5A-6
18.5kW (25HP)
SV185iP5A-2NO
SV185iP5A-4NO
SV185iP5A-4NOL (CLASS)
SV0185iP5A-6
22kW (30HP)
SV220iP5A-2NO
SV220iP5A-4NO
SV220iP5A-4NOL (CLASS)
SV0220iP5A-6
30kW (40HP)
SV300iP5A-2NO
SV300iP5A-4NO
SV300iP5A-4NOL (CLASS)
SV0300iP5A-6
37kW (50HP)
SV370iP5A-4O
SV370iP5A-4OL (CLASS)
SV0370iP5A 6
45kW (60HP)
SV450iP5A-4O
SV450iP5A-4OL (CLASS)
SV0450iP5A-6
Motor Rating
200~230V Class
380~480V Class
0.75kW (1HP)
SV008iP5A-2NE
SV008iP5A-4NE
1.5kW (2HP)
SV015iP5A-2NE
SV015iP5A-4NE
2.2kW (3HP)
SV022iP5A-2NE
SV022iP5A-4NE
3.7kW (5HP)
SV037iP5A-2NE
SV037iP5A-4NE
5.5kW (7.5HP)
SV055iP5A-2NE
7.5kW (10HP)
SV075iP5A-2NE
11kW (15HP)
55kW (75HP)
SV550iP5A-4O
SV550iP5A-4OL (CLASS)
SV0550iP5A-6
75kW (100HP)
SV750iP5A-4O
SV750iP5A-4OL (CLASS)
SV0750iP5A-6
90kW (125HP)
SV900iP5A-4O
SV900iP5A-4OL (CLASS)
SV0900iP5A-6
110kW (150HP)
SV1100iP5A-4OL
SV1100iP5A-4OL (CLASS)
SV1100iP5A-6
132kW (200HP)
SV1320iP5A-4OL
SV1320iP5A-4OL (CLASS)
160kW (250HP)
SV1600iP5A-4OL
SV1800iP5A-4OL (CLASS)
220kW (300HP)
SV2200iP5A-4OL
SV2200iP5A-4OL (CLASS)
280kW (350HP)
SV2800iP5A-4OL
SV2800iP5A-4OL (CLASS)
315kW (400HP)
SV3150iP5A-4O
SV3150iP5A-4O (CLASS)
375kW (500HP)
SV3750iP5A-4O
SV3750iP5A-4O (CLASS)
450kW (600HP)
SV4500iP5A-4O
SV4500iP5A-4O (CLASS)
2
NE
(CLASS)
N: No Keypad O: UL Open Type E: UL Enclosed Type 1 L: Built-in DC Reactor
Classification
SV
055
iP5A
Motor Rating
Series Name iP5A
055 900
5.5 kW 90 kW
--
Input Voltage 2 4 6
200-230V 380-480V 525-600V
(15~90kW : Option / 110~280kW : Standard)
SV055iP5A-2NE INPUT
200-230 V 3 Phase 25A 50/60HZ
OUTPUT 0-Input V 3 Phase 24A 0.01-120HZ 9.1KVA, Enclosed Type 1
Model Number Input Rating Output Rating Protection Degree Bar Cord Serial Number
8
Marine Approved Drives needs additional ordering.
Industrial Inverter for Fan and Pump STARVERT iP5A
Standard Specifications 200~230V Class (0.75~30kW / 1~40HP) ��� iP5A-2) Model Number (SV� Capacity [kVA]
Note1) Note2)
Fan or pump load Output ratings General load
Motor rating
(HP) (kW)
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]
008
015
022
037
1.9 1 0.75 5
3.0 2 1.5 8
4.6 3 2.2 12
6.1 5 3.7 16
055
075
110
150
185
220
300
9.1 12.2 17.5 22.9 28.2 33.5 43.8 7.5 10 15 20 25 30 40 5.5 7.5 11 15 18.5 22 30 24 32 46 60 74 88 115 110% 1 Minute (Normal Duty) 0.5 1 2 3 5.5 7.5 10 15 20 25 30 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 2.5 5 8 12 17 23 33 44 54 68 84 110% 1 Minute (Normal Duty) 150% 1 Minute (Heavy Duty) 0.01~120 Hz 200~230V Note3) 3∅200~230V (-15%~+10%) 50/60 Hz (± 5%) IP20 / UL Type1 IP00 / UL Open Note4) 4.1(9.0) 4.2(9.3) 4.2(9.3) 4.9(10.8) 4.9 (10.8) 6 (13.2) 6 (13.2) 13 (28.7) 13.5 (29.8) 20 (44.1) 20 (44,1)
380~480V Class (0.75~90kW / 1~125HP) ��� iP5A-4) Model Number (SV� Capacity [kVA]
Note1) Note2)
Fan or pump load Output ratings General load
Motor rating
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]
(HP) (kW)
Standard Type Built-in DCL Type
008 015
022
037
055
075
2.0 1 0.75 2.5
4.8 3 2.2 6
6.4 5 3.7 8
9.6 7.5 5.5 12
12.7 10 7.5 16
3.0 2 1.5 4
110
150
185
220
300
370
450
550
750
900
19.1 23.9 31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8 15 20 25 30 40 50 60 75 100 125 11 15 18.5 22 30 37 45 55 75 90 24 30 39 45 61 75 91 110 152 183 110% 1 Minute (Normal Duty) 0.5 1 2 3 5.5 7.5 10 15 20 25 30 40 50 60 75 100 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 1.25 2.5 4 6 8.8 12 16 22/24 28/30 34/39 44/45 110% 1 Minute (Normal Duty) 150% 1 Minute (Heavy Duty) 0.01~120 Hz 380~480V Note3) 3∅380~480V (-15%~+10%) 50/60 Hz (± 5%) IP20 / UL Type1 IP00 / UL Open Note4) 4.1(9.0) 4.2(9.3) 4.2(9.3) 4.9(10.8) 4.9 (10.8) 6 (13.2) 6 (13.2) 12.5 (27.6) 13 (28.7) 20 (44.1) 20 (44.1) 27 (59.5) 27 (59.5) 29 (64) 42 (92.6) 43 (94.8) - 19.5 (43.9) 19.5 (42.9)26.5 (58.3) 26.5 (58.3) 39 (86) 40 (88.2) 42 (92.6) 67 (147.4) 68 (149.9)
Note 1) Rated capacity (v 3×V×I) is based on 220V for 200V class and 460V for 400V class. 2) Indicates the maximum applicable capacity when using a 4-Pole LS motor. 3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary. 4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.
9
iP5A
Standard Specifications 380~480V Class (110~450kW / 50~125HP) ��� iP5A-4) Model Number (SV� Capacity [kVA]
Note1) Note2)
Fan or pump load Output ratings General load
Motor rating
(HP) (kW)
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
Frequency Voltage Input Voltage ratings Frequency Protection degree DCL Weight [kg (lbs.)]
1100
1320
1600
178 150 110 223
210 200 132 264
259 250 160 325
125 90 183
150 10 223
200 132 264
101 (222.7)
Built-in 101 (222.7) 114 (251.3)
2200
2800
3150
3750
4500
488 400 315 613
582 500 375 731
699 600 450 877
350 280 547
400 315 613
500 375 731
344 436 300 350 220 280 432 547 110% 1 Minute (Normal Duty) 250 300 160 220 325 432 150% 1 Minute (Heavy Duty) 0.01~120 Hz 380~480V Note3) 3∅380~480V (-15%~+10%) 50/60 Hz (± 5%) IP00 / UL Open Note4) 200 (441.9)
200 (441.9)
External Option 243 (535.7) 380 (837.7)
380 (837.7)
525~600V Class (5.5~110kW /7.5~150HP) ��� iP5A-6) Model Number (SV� Capacity [kVA] Fan or pump load Output ratings General load
Motor rating
(HP) (kW)
Current [A] (110% over current) (HP) Motor rating (kW) Current [A] (150% over current)
0055
0075
0110
0150
0185
9.6 7.5 5.5 9
12.7 10 7.5 12
19.1 15 11 17
23.9 20 15 23
31.1 25 18.5 27
5.5 3.7 6.1
7.5 5.5 9
10 7.5 12
15 11 17
6.5 (14.4)
7.0 (15.5)
7.0 (15.5)
11.7 (25.8)
Frequency Voltage Input Voltage ratings Frequency Protection degree Weight [kg (lbs.)]
Standard Type
0220
0300
0370
0450
Note 1) Rated capacity (v 3×V×I) is based on 220V for 200V class and 460V for 400V class. 2) Indicates the maximum applicable capacity when using a 4-Pole LS motor. 3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary. 4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.
10
0550
0750
0900
35.9 48.6 59.8 72.5 87.6 121.1 145.8 30 40 50 60 75 100 125 22 30 37 45 55 75 90 34 43 55 64 80 104 128 110% 1Minute (Normal Duty) 20 25 30 40 50 60 75 100 15 18.5 22 43 55 64 80 104 23 27 34 150% 1 Minute (Heavy Duty) 0.01 ~ 120 Hz 525 ~ 600V Note3) 3∅ 525 ~ 600V (-15% ~ +10 %) 50/60 Hz (±5 %) IP20 / UL Type1 IP00 / UL Open Note4) 11.7 18.9 18.9 32 32 32 46 46 (25.8) (41.7) (41.7) (70.65) (70.65) (70.65) (101.5) (101.5)
1100 178 150 110 150 125 128 -
101 (223)
Industrial Inverter for Fan and Pump STARVERT iP5A
Common Specifications Cooling method Control Method
Control
Frequency Setting Resolution Frequency Accuracy V/F Pattern Overload Capacity Torque Boost Operation Method
Input Signal Output signal
Operatio
Frequency Setting Start Signal Multi-Step Multi Step Accel/Decel Time Emergency Stop Jog Fault Reset Operating Status Fault Output Indicator
Forced air cooling (Self-cooling for below 1.5kW-2, 2.2kW-4) V/F, Sensorless Vector, Slip Compensation, Easy Start Selectable Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz) Analog Reference: 0.01 Hz / 60 Hz Digital : 0.01% of the max frequency Analog : 0.1% of the max frequency Linear, Squared Pattern, User V/F 110 % per 1 min, 120% per 1 min Note5) Manual Torque Boost (0 ~ 15 %), Auto Torque Boost Keypad / Terminal / Communication Operation Analog: 0 ~ 12V / -12V ~ 12V / 0~20mA/ Pulse / Ext-PID Digital: Keypad Forward, Reverse Up to 18 Speeds can be set including Jog (Use Programmable Digital Input Terminal,Including Jog/Dwell ) 0.1~ 6,000 sec, Max 4 types can be set via Multi- Function Terminal. Accel/Decel Pattern: Linear, U-Curve, S-Curve Selectable Interrupts the Output of Inverter Jog Operation Fault Reset Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Low Voltage, Inverter Overheating/ Running/ Stopping/ Const ant running, Inverter By-Pass, Speed Searching Contact Output (3A, 3C, 3B) - AC 250V 1A, DC 30V 1A Choose 2 from Output Frequency, Output Current, Output Voltage, DC Link Voltage (Output Voltage: 0 ~ 10V) DC Braking, Frequency Limit, Frequency Jump, 2nd Function, Slip Compensation, Reverse Rotation
Operation Function
Prevention, Auto Restart, Invert By-Pass Auto-Tuning PID Control Start Stop Braking leakage Pre-PID Dual-PID MMC Start Prer By Pass, Auto Tuning, Control, Flying Start, Safety Stop, Flux Braking, Over Voltage, Low Voltage, Over Current, Ground Fault, Inverter Overheat, Motor Overheat, Output Phase
Inverter Trip
Open, Overload Protection, External Fault 1, 2, Communication Error, Loss of Speed Command, Hardware Fault, Option Fault etc
Inverter Alarm Keypad
Display
Protection
Low leakage, Pre PID, Dual PID, MMC, Easy Start, e-heater
Operation Information
Stall Prevention, Overload Alarm, Thermal Sensor Fault Output Frequency, Output Current, Output Voltage, Frequency Set Value, Operating Speed, DC Voltage, Integrating Wattmeter, Fan ON time, Run-time, Last Trip Time Trips Indication when the Protection Function activates.
Trip Information
Max. 5 Faults are saved.
Environment
Last Trip Time.
Ambient Temperature Storage Temperature Ambient Humidity Altitude-Vibration Application Site
-10℃ ~ 50℃ (14° F ~ 122° F) Decrease 2% of rated current for every 1℃ increase in above 40℃ -20℃ ~ 65℃ (14° F~ 149° F) Below 90 % RH Max. (Non-Condensing) Below 1,000m (3,300ft), Below 5.9m/sec2 (0.6g) Pollution degree 2, No Corrosive Gas, Combustible Gas, Oil Mist, or Dust
(1) Rated capacity (√3×V×I) is based on 220V for 200V class and 460V for 400V class. (3) IP20 or UL Enclosed Type1 can be provided by the option. (5) Overload rating 120%, 1 min is based on ambient 25℃
(2) Indicates the maximum applicable capacity when using a 4-Pole standard motor. (4) IP20 or UL Enclosed Type1 is not provided.
11
iP5A
Standard Specifications Common Specifications (External) 32 character display
Keypad
LCD
Remote
Remote cable
All units keypad Download and Upload available 2m, 3m and 5m long keypad cable enables users Optional to control the inverter from a distant area To enhance the regenerative braking performance,
DB resistor it makes the inverter to accelerate/decelerate rapidly
Dynamic braking
capacity DB unit
If it need a regenerative braking, it is used with DB resistor
Conduit for
Conduit option
According to inverter
15~90kW Install it to fit for NEMA TYPE 1 Enclosure or IP20
NEMA TYPE 1
(20~125HP) All series
DEVICENET
DEVICENET optional communication card (Above S/W V10) All series
PROFIBUS
PROFIBUS optional communication card (Above S/W V10) All series
LS485/MODBUS_RTU
LS485/MODBUS_RTU optional communication card (Above S/W V10) All series
LonWorks
Lonworks optional communication card (Above S/W V10)
Communication
All series BACNet
BACNet optional communication card
option card
(Above S/W V10) All series MODBUS_TCP
MODBUS_TCP optional communication card (Above S/W V10) All series
Metasys_N2
Metasys_N2 optional communication card (Above S/W V10) All series
CCLink
CCLink optional communication card (Above S/W V10) All series
CANopen
CANopen optional communication card (Above S/W V10)
12
Industrial Inverter for Fan and Pump STARVERT iP5A
Wiring For 0.75~30kW (1~40HP) Main Power Circuit Dynamic Braking Unit (Optional)
DC Bus Choke (Optional)
DB Unit (Optional) DB Resistor
P N B1 B2 DC Bus Choke
DB Resistor P1 (+)
P2 (+) N (-)
MCCB (Option) 3∅ AC Input 50/60 Hz
R (L1)
U
S (L2)
V
T (L3)
W
Motor
G
Control Circuit Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST)
+ -
M1 M2
+ -
M3 M4
Inverter Disable (BX)
V+
Analog Power Source (+12V)
V1
Frequency Reference (0~12V, V1S: -12~12V)
5G
Frequency Reference Common Terminal
I
Frequency Reference (0~20mA or 4~20mA)
V-
Analog Power Source (-12V)
S0 S1 5G
Output Frequency Meter
M5
Jog Frequency Reference (JOG)
M6
Forward Run Command (FX)
M7
Reverse Run Command (RX)
M8
Common Terminal
Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
Output Voltage Meter Common for Output Meter Signal
CM
Programmable Digital Output
A1 C1 A2 C2 A3 C3 A4
3A 3C 3B
A0 B0 5G
Fault Contact Output less than AC250V (DC30V), 1A
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)
C4
RS485 Signal RS485 Common
CC+
NT 5G
External Motor Thermal Detection
CM
Note 1) 5G is Common Ground for Analog Input / Output. 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
13
iP5A
Wiring For 37~90kW (50~125HP) / 315~450kW (400~600HP) Main Power Circuit Dynamic Braking Unit (Optional)
DC Bus Choke (Optional )
DB Unit (Optional) DB Resistor
P N B1 B2 DC Bus Choke
DB Resistor P1 (+)
P2 (+) N (-)
MCCB (Option) 3∅ AC Input 50/60 Hz
R (L1)
U
S (L2)
V
T (L3)
W
Motor
G
Control Circuit Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST)
+ -
M1 M2
+ -
M3 M4
Inverter Disable (BX)
V+
Analog Power Source (+12V)
V1
Frequency Reference (0~12V, V1S: -12~12V)
CM
Frequency Reference Common Terminal
I
Frequency Reference (0~20mA or 4~20mA)
V-
Analog Power Source (-12V)
S0 S1 5G
Output Frequency Meter
M5
Jog Frequency Reference (JOG)
M6
Forward Run Command (FX)
M7
Reverse Run Command (RX)
M8
Common Terminal
Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
Output Voltage Meter Common for Output Meter Signal
CM
Programmable Digital Output
A1 C1 A2
3A 3C 3B
C2 A3
A0
C3 A4
B0 CM
Fault Contact Output less than AC250V (DC30V), 1A
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)
C4
RS485 Signal RS485 Common
CC+ CM
Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input. 3) DC Reactor is built basically in inverters for 15~280kW.
14
ET 5G
External Motor Thermal Detection
Industrial Inverter for Fan and Pump STARVERT iP5A
For 110~280kW (150~350HP) Main Power Circuit Dynamic Braking Unit (Optional)
DB Unit (Optional) DB Resistor
P N B1 B2 DB Resistor P2 (+) MCCB (Option) DC Reactor (Built-in) 3∅ AC Input 50/60 Hz
R (L1)
U
S (L2)
V
T (L3)
W
Motor
G
Control Circuit Programmable Digital Input 1 (Speed L) Programmable Digital Input 2 (Speed M) Programmable Digital Input 3 (Speed H) Fault Reset (RST)
+ -
M1 M2
+ -
M3 M4
Inverter Disable (BX)
V+
Analog Power Source (+12V)
V1
Frequency Reference (0~12V,V1S: -12~12V)
CM
Frequency Reference Common Terminal
I
Frequency Reference (0~20mA or 4~20mA)
V-
Analog Power Source (-12V)
S0 S1 5G
Output Frequency Meter
M5
Jog Frequency Reference (JOG)
M6
Forward Run Command (FX)
M7
Reverse Run Command (RX)
M8
Common Terminal
Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
Output Voltage Meter Common for Output Meter Signal
CM
Programmable Digital Output
A1 C1 A2
3A 3C 3B
C2 A3
A0
C3 A4
B0 CM
Fault Contact Output less than AC250V (DC30V), 1A
Frequency Reference (Pulse: 0~100kHz) Common for Frequency Reference (Pulse)
C4
RS485 Signal RS485 Common
CC+
ET 5G
External Motor Thermal Detection
CM
Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). 2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input. 3) DC Reactor is built basically in inverters for 15~280kW.
15
iP5A
Wiring For 15~30kW (20~40HP) Built-in DCL Type
P N B1 B2 DB Resistor P (+)
N (-)
DC Reactor
3∅ AC Input 50/60 Hz
R (L1)
U
S (L2)
V
T (L3)
W
Motor
G
For 37~90kW (50~125HP) Built-in DCL Type
P N B1 B2 DB Resistor P1 (+)
P2 (+)
N (-)
DC Reactor
3∅ AC Input 50/60 Hz
R (L1)
U
S (L2)
V
T (L3)
W
G
Note) P1 (+) is not provided for wiring.
16
Motor
Industrial Inverter for Fan and Pump STARVERT iP5A
Terminal Configurations (Power Circuit Terminal) 0.75~30kW (1~40HP) <200V/400V Class>
R(L1) S(L2) T(L3)
G
(+)
(+)
(--)
P1
P2
N
U
V
W
Jumper
〉 37~90kW (50~125HP) / 315~450kW (400~600HP)〈400V/600V Class〉
R(L1) S(L2) T(L3)
(+)
(+)
(--)
P1
P2
N
U
V
W
Jumper
〉 15~18.5kW (20~25HP)〈Built-in DC Reactor Type, 400V Class〉
G
R(L1) S(L2) T(L3)
(+)
(--)
P
N
U
V
W
G
〉 22~30kW (30~40HP)〈Built-in DC Reactor Type, 400V Class〉
R(L1) S(L2) T(L3)
(+)
(-)
P
N
U
V
W
〉 37~90kW (50~125HP) / 110 ~280kW (150~350HP)〈Built-in DC Reactor Type, 400V Class〉
R(L1) S(L2) T(L3)
(+)
(--)
P2
N
U
V
W
Note) P1 (+) is not provided for wiring.
Symbol
Description
R, S, T (L1, L2, L3)
AC Line Voltage Input
G
Earth Ground
P1 (+), P2 (+)
External DC Reactor [P1 (+)-P2 (+)] Connection Terminals (Jumper must be removed).
P2 (+), N (-) or P (+), N (-)
DB Unit [P2 (+)-N (-)] Connection Terminals
U, V, W
3 Phase Power Output Terminals to Motor
17
iP5A
Terminal Configurations (Power Circuit Terminal) Grounding Inverter Capacity kW HP 0.75 ~ 3.7 kW 1~5 5.5 ~ 7.5 7.5 ~ 10 11 ~ 15 15 ~ 20 18.5 ~ 30 25 ~ 40 37 ~ 55 50 ~ 75 75 ~ 90 100 ~ 125 110 ~ 132 150 ~ 200 160 ~ 280 250 ~ 350 315 ~ 375 400 ~ 600 450 700
Grounding wire Sizes, kcmil (mm2) 200V Class 4 6 16 25 -
400V Class 2.5 4 10 16 25 35 70 95 150 240
Wires & Terminal lugs Refer to below for wires, terminal lugs, and screws used to connect the inverter power input and output. Inverter capacity
Terminal screw size
200V Class
400V Class
600V Class
0.75kW(1HP) 1.5kW(2HP) 2.2kW(3HP) 3.7kW(5HP) 5.5kW(7.5HP) 7.5kW(10HP) 11kW(15HP) 15kW(20HP) 18.5kW(25HP) 22kW(30HP) 30kW(40HP) 0.75kW(1HP) 1.5kW(2HP) 2.2kW(3HP) 3.7kW(5HP) 5.5kW(7.5HP) 7.5Kw(10HP) 11 kW(15HP) 15 kW(20HP) 18.5kW(25HP) 22~30kW(30~40HP) 37~55kW(50~75HP) 75~90kW(100~125HP) 110~132kW(150~200HP) 160kW(250HP) 220kW(300HP) 280kW(350HP) 315kW(400HP) 375kW(500HP) 450kW(600HP) 5.5kW(7.5HP) 7.5Kw(10HP) 11 kW(15HP) 15 kW(20HP) 18.5kW(25HP) 22~30kW(30~40HP) 37~55kW(50~75HP)
M4 M4 M4 M4 M4 M5 M5 M6 M6 M8 M8 M4 M4 M4 M4 M4 M4 M4 M6 M6 M8 M8 M10 M12 M12 M12 M12 M12 M12 M12 M4 M4 M4 M6 M6 M8 M8
Screw torque
Wire size R(L1), S(L2), T(L3)
・cm Kgf・
・in Ib・
mm
7.1 ~12.2 7.1 ~12.2 7.1 ~12.2 7.1 ~12.2 7.1 ~12.2
6.2 ~10.6 6.2 ~10.6 6.2 ~10.6 6.2 ~10.6 6.2~10.6
24.5 ~31.8
21.2~27.6
30.6 ~38.2
26.6~33.2
61.2 ~91.8
53.1~79.7
7.1 ~12.2 7.1 ~12.2 7.1 ~12.2 7.1 ~12.2
6.2 ~10.6 6.2 ~10.6 6.2 ~10.6 6.2 ~10.6
7.1 ~12.2
6.2~10.6
30.6~38.2
26.6~33.2
61.2~91.8
53.1~79.7
89.7~122.0
77.9~105.9
182.4~215.0
158.3~186.6
7.1 ~12.2
6.2~10.6
30.6~38.2
26.6~33.2
61.2~91.8
53.1~79.7
2.5 2.5 2.5 4 5.5 8 14 22 38 38 60 2.5 2.5 2.5 2.5 3.5 3.5 5.5 8 14 22 38 60 100 150 200 250 325 2×200 2×250 3.5 3.5 5.5 8 14 22 38
2
AWG or kcmil
14 14 14 12 10 8 6 4 2 2 1/0 14 14 14 14 12 12 10 8 6 4 2 1/0 4/0 300 400 500 700 2×400 2×500 12 12 10 8 6 4 2
U, V, W mm
2
2.5 2.5 2.5 4 5.5 8 14 22 38 38 60 2.5 2.5 2.5 2.5 3.5 3.5 5.5 8 14 22 38 60 100 150 200 250 325 2×200 2×250 3.5 3.5 5.5 8 14 22 38
* Apply the rated torque to terminal screws. * Loose screws can cause of short circuit or malfunction. Tightening the screw too much can damage the terminals and cause a short circuit or malfunction. * Use copper wires only with 600V, 75℃ ratings. For 7.5~11kW 240V type inverters, R(L1), S(L2), T(L3) and U, V, W terminals are only for use with insulated ring type connector.
18
AWG or kcmil
14 14 14 12 10 8 6 4 2 2 1/0 14 14 14 14 12 12 10 8 6 4 2 1/0 4/0 300 400 500 700 2×400 2×500 12 12 10 8 6 4 2
Industrial Inverter for Fan and Pump STARVERT iP5A
Terminal Configurations (Control Circuit Terminal) 0.75~30kW / 1~40HP (200V/400V Class)
C+ CM C-
3A 3C 3B A1 C1
A2 C2 A3 C3 A4 C4
M6
24
M7 M8
A0
B0 5G 5G
M1 CM M2 M3
24
M4 M5
V+
V1 5G
C+ CM C-
M6
24
M7 M8
CM NC 5G 5G ET
S0
M1 CM M2 M3
24
M4 M5
V+
A0 B0
V-
S0
S1
I
NT
37~450 kW/50~600HP (400V Class)
3A 3C 3B A1 C1
A2 C2 A3 C3 A4 C4
V1 CM
V-
1
S1
19
iP5A
Terminal Configurations (Control Circuit Terminal)
Type
Symbol M1, M2, M3 FX [M7] RX [M8]
Starting
JOG [M6]
Name Defines programmable digital inputs
Digital Input 1, 2, 3
(Factory setting : Multi-step frequency 1,2,3)
Forward Run Command Reverse Run Command
Select
Forward run when closed and stopped when open Reverse run when closed and stopped when open
Jog Frequency
Runs at jog frequency when the jog signal is on.
Reference
The direction is set by the FX (or RX) signal
Contact Function
Description
Programmable
When the BX signal is ON, the output of the inverter is turned off. BX [M5]
Emergency Stop
RST [M4]
Fault Reset
When motor uses an electrical brake to stop, BX is used to turned off the output signal. Take caution when BX signal is off (Not turned off by latching) and FX signal (or RX signal) is on.
Input Signal
Under these conditions, the motor will run!
CM 24
V+, VV1 Analog Frequency
I
Setting A0, B0
External Motor Thermal Detection
Output Signal
.
Sequence Common
Common 24V terminal for PNP contact input.
(PNP)
Maximum output : +24V, 100mA
Analog Power Source
Power supply for analog frequency setting.
(+12V,-12V)
Maximum output : +12V, 100mA, -12V, 100mA
Frequency Reference
Used by a DC 0~12V or -12~12V input to set the frequency reference.
(Voltage)
(Input impedance is 20kâ&#x201E;Ś)
Frequency Reference
Used by a 0-20mA input to set the frequency reference.
(Current)
(Input impedance is 249â&#x201E;Ś)
Frequency Reference (Pulse)
Used by a pulse input to set the frequency reference.
Frequency Reference Common Terminal
NT (~30kW)
External Motor
Motor thermal sensor input. Used to prevent motor from overheating by using a NTC or
ET (37kW~)
Thermal Detection
PTC thermal sensor.
5G
CM S0, S1, 5G 3A, 3C, 3B Contact A1~4, C1~4
20
Common terminal for NPN contact
CM (37kW~)
Built-in RS485 Terminal
Note) NC terminal is unavailable
(NPN)
5G (~30kW)
C+, C-
Analog Output
Sequence Common
Used for fault reset.
Common for NT (or ET) RS485 signal High, Low RS485 common Programmable Voltage Output Analog Common Terminal Fault Contact Output
Common terminal for analog frequency reference signal
Common terminal for external motor thermal detection RS485 signal (See RS485 communication in manual for more details.) Common ground. Terminal for RS485 interface. Voltage output for one of the following : Output frequency, output current, output voltage, DC link voltage. Default is set to output frequency. (Maximum output voltage and output current are 0-12V and 1mA) Common terminal for analog output (S0, S1) Energizes when a fault is present. (AC250V, 1A; DC30V, 1A) Fault : 3A-3C closed (3B-3C open) Normal : 3B-3C Closed (3A-3C open)
Programmable
Defined by programmable digital output terminal settings
Digital Output
(AC250V, 1A or less; DC30V, 1A or less)
Industrial Inverter for Fan and Pump STARVERT iP5A
iP5A provides Sink/Source (NPN/PNP) modes for sequence input terminal on the control circuit. The logic of the input terminal is settable to Sink mode (NPN mode)/Source mode (NPN mode) by using the J1 switch. Connection method is shown below. Sink mode (NPN mode) �Put J1 switch down to set to Sink mode (NPN mode). CM terminal (24V GND) is common terminal for contact signal input. �The factory default is Sink mode (NPN mode).
Source mode (PNP mode) Internal Power Supply Used �Put J1 switch up to set to Source mode (PNP mode). Terminal 24 (24V Power Supply) is common terminal for contact input signal.
Source mode (PNP mode) External Power Supply Used �Put J1 switch up to set to Source mode (PNP mode). �To use external 24V Power Supply, make a sequence between external Power Supply (-) terminal and CM (24V GND) terminal.
21
iP5A
Programming Keypad LCD Loader
Data set up start
■
32 character, background light, LCD display. Background tone is adjustable.
Shift between function groups ■ Shifting from group code to the upper code ■
Shift to function code Shift to next function code ■ Data is increased in set up mode ■ ■
Reverse run command key Only available with loader operation ■ LED is turned ON with reverse run ■ Blinks during Acc/Deceleration of reverse run
22
■
Decimal point shift Only available in case of data setup
Forward run command key Only available with loader operation ■ LED is turned ON with forward run ■ Blinks during Acc/Deceleration of forward run ■
■
■
Shift to function code ■ Shift to previous code ■ Data is decreased in set up mode
Data set up completion
■
■
■
■
Stop command Available with the loader operation ■ LED is turned on when inverter stops its operation ■ Blinks when fault occurs ■ Reset ■ Fault reset ■ ■
Industrial Inverter for Fan and Pump STARVERT iP5A
Programming Keypad (Parameter Navigation) Parameter group moves directly to DRV group by pressing [SHIFT] key in any parameter code.
Drive Group
FU1 Group
FU2 Group
I/O Group
Note) This figure shows group and code navigation through LCD display keypad. It can be different from actual display due to the group addition or code change.
23
iP5A
Parameter Description DRV Group CODE
Comm. Addr
DRV-00 Note1)
9100
DRV-01
9101
DRV-02
9102
Description Command Frequency (Output Frequency during motor run, Reference Frequency during motor stop), Output Current (LCD) Acceleration 0.75~90kW (1~125HP) Time 110~450kW (150~600HP) Deceleration 0.75~90kW (1~125HP) Time 110~450kW (150~600HP)
LCD Keypad Display
Setting Range
Factory Default
Adj. During Run
Cmd. freq
0 to FU1-30[Hz]
0 [Hz]
○
Acc. Time
0 to 6000 [sec]
Dec. time
DRV-03
9103
Drive Mode (Run/Stop Method)
Drive mode
DRV-04
9104
Frequency Mode (Frequency setting method)
Freq mode
DRV-05 DRV-06 DRV-07 DRV-08 DRV-09 DRV-10
9105 9106 9107 9108 9109 910A
Step Frequency 1 Step Frequency 2 Step Frequency 3 Output Current Motor Speed DC link Voltage
Step freq-1 Step freq-2 Step freq-3 Current Speed DC link Vtg
DRV-11
910B
User Display Selection
User disp
DRV-12 DRV-14 Note2) DRV-15 Note2) DRV-16 DRV-18 Note2) DRV-19 DRV-20 Note3)
910C 910E 910F 9110 9112 9113 9114
Current Trip Display Target/Output Frequency Display Reference/Feedback Frequency Display Speed Unit Selection PID Parameter AD Parameter EXT-PID Parameter
Fault Tar. Out. Freq. Ref. Fbk. Freq. Hz/Rpm Disp RTFO V1 V2 V1S I RTFO
DRV-22
9116
Local/Remote Key
LocalRemKey
DRV-23
9117
Keypad Mode Key
Ref Mode
DRV-91 Note4)
915B
Drive mode 2
Drive mode2
DRV-92
915C
Frequency mode 2
Freq mode2
0 to 6000 [sec] 0 1 2 3 0 1 2 3 4 5 6 7 8
(Keypad) (Fx/Rx-1) (Fx/Rx-2) (Int. 485) (Keypad-1) (Keypad-2) (V1) (V1S) (I) (V1+I) (Pulse) (Int. 485) (Ext. PID) 0 to FU1-30[Hz] * [A] * [rpm] * [V]
1 2 3 4 5 6 1 2 3 4 5 6 0 1 2 0 1 2 3 4 5 6
* * [Hz] * [Hz] Hz or Rpm * [Hz] * % (Cntl&RefStop) (Control Stop) (Ref Only) (Cntl&Ref Run) (Control Run) (Disable) (Minimum Spd) (Last Spd) (Preset Spd 1) (Stop) (Fault) (Disable) (Keypad) (Fx/Rx-1) (Fx//Rx-2) (Keypad-1) (Keypad-2) (V1) (V1S) (I) V1+I) (Pulse)
20 [sec] 60 [sec] 30 [sec] 90 [sec]
○ ○
1 (Fx/Rx-1)
×
0 (Keypad-1)
×
10 [Hz] 20 [Hz] 30 [Hz] * [A] * [rpm] * [V] Output voltage [V] * * [Hz] * [Hz] Hz * [Hz] * %
○ ○ ○ * * *
Cntl&RefStop
○
Disable
○
1 (Fx/Rx-1)
×
0 (Keypad-1)
* * * * ○ × × ×
×
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 1) The speed unit is changed from [Hz] to [%] when DRV-16 is set to [Rpm]. Only User Unit will be displayed when APP-02 is set to [Yes] and when APP-06 is set to either I, V1 or Pulse and when one of I/O-86~ I/O-88 is set to either [Speed] (Hz or Rpm), [Percent], [Bar], [mBar], [kPa] or [Pa]. Output Frequency (Hz or Rpm; Unit of outupt speed) is displayed in DRV-00 during the Inverter is running. User Unit reference (Unit of PID controller selected) is displayed in DRV-00 during the Inverter is not running. 2) DRV-15, DRV-18 will appear when APP-02 [Process PI Mode] is set to “Yes”. Also User Unit is displayed when one of I/O-86~ I/O-88 is set to either [Speed](Hz or Rpm), [Percent], [Bar], [mBar], [kPa] or [Pa]. 3)DRV-20 will appear when APP-80 [ExtProcess PI Mode] is set to “Yes”. 4) DRV-91/92 will appear only when DRV-22 is set to [2nd Source].
24
Industrial Inverter for Fan and Pump STARVERT iP5A
FU1 GROUP CODE
Comm. Addr
FU1-00
9200
Jump to Desired Code #
Jump code
FU1-01
9201
Run Prevention
Run prevent
FU1-02
9202
Acceleration Pattern
Acc. Pattern
FU1-03
9203
Deceleration Pattern
Dec. Pattern
FU1-04 Note5)
9204
FU1-05
9205
FU1-10
920A
Pre-Heat
Pre-Heat mode
FU1-11 FU1-12
920B 920C
Pre-Heat Value Pre-Heat Duty
Pre Heat level Pre Heat Perc
FU1-20
9214
Start Mode
Start mode
FU1-21 Note6) FU1-22
9215 9216
Starting DC Injection Braking Time Starting DC Injection Braking Value
DcSt time DcSt value
Description
Start Curve for S-Curve Accel/Decel Pattern End Curve for S-Curve Accel/Decel Pattern
LCD Keypad Display
Setting Range
0 1 2 0 1 2 0 1 2
1 to 74 (Use Only LCD Keypad) (None) (Fwd prev) (Rev prev) (Linear) (S-curve) (U-curve) (Linear) (S-curve) (U-curve)
Factory Default
Adj. During Run
1
○
0 (None)
×
0 (Linear)
×
0 (Linear)
×
Start Curve
0 to 100[%]
50 [%]
×
End Curve
0 to 100[%]
50 [%]
×
0 (No)
×
30 (%) 50 (%)
× ×
0 (Accel)
×
0.1 [sec] 50 [%]
× ×
0 (Decel)
×
0.1 [sec] 5 [Hz] 1 [sec] 50 [%]
× × × ×
0 (No)
×
60.00 [Hz] 60.00 [Hz] 60.00 [Hz] 0.50 [Hz]
× × × ×
0 (No)
×
0.50 [Hz] 60.00 [Hz]
○ ×
0 (Linear)
×
FU1-23
9217
Stop Mode
Stop mode
FU1-24 Note7) FU1-25 FU1-26 FU1-27
9218 9219 921A 921B
DC Injection Braking On-delay Time DC Injection Braking Frequency DC Injection Braking Time DC Injection Braking Value
DcBlk Time DcBrk freq DcBr time DcBr value
FU1-28
921C
Safety Stop
Safety Stop
FU1-29 FU1-30 FU1-31 FU1-32
921D 921F 9220 9220
Power Source Freq Maximum Frequency Base Frequency Starting Frequency
Line Freq Max Freq Base Freq Start Freq
FU1-33
9221
Frequency Limit selection
Freq limit
FU1-34 Note8) FU1-35
9222 9223
Freq Lower Limit Freq Upper Limit
Lim Lo Freq Lim Hi Freq FU
FU1-40
9228
Volts/Hz Pattern
V/F Pattern
0 1
0 1 2
0 1 2 3
0 1
0 1
0 1 2
(No) (Yes) 1 to 50[%] 1 to 100 [%] (Accel) (Dc-start) (Flying-start) 0 to 60 [sec] 0 to 150 [%] (Decel) (Dc-brake) (Free-run) (Flux-brake) 0.1 to 60 [sec] 0.1 to 60 [Hz] 0 to 60 [sec] 0 to 200 [%] (No) (Yes) 40 to 120 [Hz] 40 to 120 [Hz] 30 to 120 [Hz] 0.01 to 10 [Hz] (No) (Yes) 0 - FU1-35 1-34 - FU1-30 (Linear) (Square) (User V/F)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 5) Only displayed when FU1-02, FU1-03 is set to [S-Curve]. 6) Only displayed when FU1-20 is set to [DC-start]. 7) Only displayed when FU1-23 is set to [DC-break]. 8) Only displayed when FU1-33 is set to [Yes].
25
iP5A
Parameter Description FU1 GROUP Comm. Addr
CODE FU1-41 FU1-42 FU1-43 FU1-44 FU1-45 FU1-46 FU1-47 FU1-48 FU1-49 FU1-50
Note9)
Description
9229 922A 922B 922C 922D 922E 922F 9230 9231 9232
User V/F–Frequency 1 User V/F–Voltage 1 User V/F–Frequency 2 User V/F–Voltage 2 User V/F–Frequency 3 User V/F–Voltage 3 User V/F –Frequency 4 User V/F–Voltage 4 Input voltage adjustment Motor Rated Voltage
User freq 1 User volt 1 User freq 2 User volt 2 User freq 3 User volt 3 User freq 4 User volt 4 VAC 380.0V Motor Volt
FU1-51
9233
Energy Save
Energy save
FU1-52 Note10) FU1-54 FU1-55 FU1-56
9234 9236 9237 9238
Energy Save % Integrating Wattmeter Inverter Temperature Motor Temperature
Manual save% KiloWattHour Inv. Temp. Motor Temp.
FU1-57
9239
No Motor Selection
No Motor Sel
FU1-58 FU1-59
923A 923B
Trip Current Level Trip Time Setting
No Motor Level No Motor Time
FU1-60
923C
Electronic Thermal Selection
ETH select
FU1-61 FU1-62
923D 923E
ETH 1min ETH Cont
FU1-63
923F
Motor type
FU1-64 FU1-65
9240 9241
Electronic Thermal Level for 1 Minute Electronic Thermal Level for Continuous Characteristic Selection (Motor Type) Overload Warning Level Overload Warning Time
FU1-66
9242
Overload Trip Selection
OLT select
FU1-67 Note11) FU1-68 FU1-69 FU1-70 FU1-71 FU1-72
9243 9244 9245 9246 9247 9248
OLT level OLT time Trip select Stall Mode. Stall level Acc/Dec ch F
FU1-73
9249
Overload Trip Level Overload Trip Delay Time Input/Output Phase Loss Protection Stall Prevention Selection Stall Prevention Level Accel/Decel Change Frequency Reference Frequency for Accel and Decel
FU1-74
924A
Accel/Decel Time Scale
Time scale
FU1-75
924B
Up Down Save Mode
UpDnSaveMode
FU1-76 Note31)
924C
Up Down Save Freq
UpDnSaveFreq
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 9) FU1-41~48 only displayed when FU1-40 is set to‘User V/F’. 10) Only displayed when FU1-51 is set to‘Manual’. 11) Only displayed when FU1-66 is set to‘Yes’. 31) Only displayed when FU1-75 is set to‘Yes’.
26
LCD Keypad Display
OL level OL time
Acc/Dec freq
Setting Range 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 0 to FU1-30 0 to 100 [%] 1 73 to 115.0 [%] 0 to 600 [V] 0 (None) 1 (Manual) 2 (Auto) 0 to 30 [%] M kWh 0 to 160 [degree] 0 to 160 [degree] 0 (No) 1 (Yes) 5 to 100 [%] 0.5 to 10.0 [sec] 0 (No) 1 (Yes) FU1-62 to 200 [%] 50 to FU1-61(Maximum 150%) 0 (Self-cool) 1 (Forced-cool) 30 to 110 [%] 0 to 30 [sec] 0 (No) 1 (Yes) 30 to 150 [%] 0 to 60 [sec] 000 to 111 (Bit Set) No/Yes 30 to 200 [%] 0 to FU1-30 0 (Max freq) 1 (Delta freq) 0 (0.01 sec) 1 (0.1 sec) 2 (1 sec) 0 (No) 1 (Yes) 0 to 120[Hz]
Factory Default
Adj. During Run
15.00 [Hz] 25 [%] 30.00 [Hz] 50 [%] 45.00 [Hz] 75 [%] 60.00 [Hz] 00[%] 86.4 [%] 380 [V]
× × × × × × × × × ×
0 (None)
×
0 [%] * * *
○ × × × ×
0 (No) 5 [%] 3.0 [sec] 1 (Yes) 150 [%] 120 [%] 0 (Self-cool) 110 [%] 10 [sec] 0 (No) 120[%] 60 [sec] 100 No 120[%] 0 [Hz] 0 (Max freq)
× × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○ × ×
1 (0.1 sec)
○
0 (No)
×
0.00Hz
○
Industrial Inverter for Fan and Pump STARVERT iP5A
FU2 GROUP CODE
Comm. Addr
FU2-00
9300
FU2-01 FU2-02 FU2-03 FU2-04 FU2-05
9301 9302 9303 9304 9305
FU2-06
9306
FU2-07 FU2-08 Note12)
9307 9308
FU2-10
930A
FU2-11 Note13) FU2-12 FU2-13 FU2-14 FU2-15 FU2-16
930B 930C 930D 930E 930F 9310
FU2-20
9314
FU2-21
9315
FU2-22
9316
FU2-23
9317
FU2-24
9318
FU2-25 FU2-26 Note15) FU2-27
9319 931A 931B
FU2-40
9328
FU2-41 FU2-42
9329 932A
FU2-43
932B
Description
LCD Keypad Display
Setting Range
1 to 95 (Use Only LCD Keypad) Last trip 1 Last trip-1 By pressing [ENTER] Last trip 2 Last trip-2 and [SEL] key, the Last trip 3 Last trip-3 frequency, current, Last trip 4 Last trip-4 and operational status Last trip 5 Last trip-5 at the time of fault can be seen. 0 (No) Erase trips Erase trips 1 (Yes) Dwell Frequency Dwell time 0 to 10 [sec] Dwell Frequency Dwell freq FU1-32 to FU1-30 0 (No) Frequency Jump Selection Jump Freq 1 (Yes) Jump Frequency 1 Low jump lo 1 0 to FU2-12 Jump Frequency 1 High jump Hi 1 FU2-11 to FU1-30 Jump Frequency 2 Low jump lo 2 0 to FU2-14 Jump Frequency 2 High jump Hi 2 FU2-13 to FU1-30 Jump Frequency 3 Low jump lo 3 0 to FU2-16 Jump Frequency 3 High jump Hi 3 FU2-15 to FU1-30 Power-on run 0 (No) Power ON Start Selection RST restart 1 (Yes) 0 (No) Restart after Fault Reset RST restart 1 (Yes) IPF Mode 0 (No) Start After Interrupt Power Fault Selection 1 (Yes) Estimated SS Speed Search Type Selection Search Type Real SS No Selection of Auto Retry Retry Mode Yes Number of Auto Retry Retry number 0 to 10 Delay Time Before Auto Retry Retry delay 0 to 60 [sec] Speed Search Current Limit Flying Perc 30 to 160 0 (0.75kW) 1 (1.5kW) 2 (2.2kW) 3 (3.7kW) 4 (5.5kW/) 5 (7.5kW/) 6 (11.0kW) 7 (15.0kW) 8 (18.5kW) 9 (22.0kW) 10 (30.0kW) Rated Motor Selection for Motor select 11 (37.0kW) inverter (0.75~450kW) 12 (45.0kW) 13 (55.0kW) 14 (75.0kW) 15 (90.0kW) 16 (110.0kW) 17 (132.0 kW) 18 (160.0 kW) 18 (220.0 kW) 20 (280.0 kW) 21 (315.0 kW) 22 (375.0 kW) 23 (450.0 kW) * A motor rating same as inverter capacity is automatically set. If different, set the correct value. Number of Motor Poles Pole number 2 to 12 Rated Motor Slip Rate-Slip 0 to 10 [Hz] Jump to desired code #
Rated Motor Current (RMS)
Jump code
Rated-Curr
1.0 to 999.9 [A]
Factory Default
Adj. During Run
40
○
0 (None) 0 (None) 0 (None) 0 (None) 0 (None)
× × × × ×
0 (No)
○
0 [sec] 5.00[Hz]
× ×
0 (No)
×
10.00[Hz] 15.00[Hz] 20.00[Hz] 25.00[Hz] 30.00[Hz] 35.00[Hz]
○ ○ ○ ○ ○ ○
0 (No)
○
0 (No)
○
0(No)
×
estmated SS
○
No
○
0 1 [sec] 70%
○ × ×
* Depending on the inverter capacity
×
4 Depending on the motor capacity
× × ×
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 12) Only displayed when FU2-07 is set to [1~10 sec]. 13) FU2-11 is displayed when FU2-10 is set to [Yes].. 14) FU2-26 is displayed when FU2-25 [Retry number] is set to [1~10]. 15) FU2-64 is displayed when FU2-60 is set to [Sensorless].
27
iP5A
Parameter Description FU2 GROUP CODE
Comm. Addr
Description
Setting Range
Factory Default
FU2-44
932C
No Load Motor Current(rms)
Noload-Curr
0.1 to 999.9 [A]
FU2-46 FU2-47
932E 932F
Load Inertia Gain for Motor Speed Display
Inertia rate RPM DisplayGn
FU2-48
9330
Carrier Frequency
Carrier freq
FU2-49
9331
PWM Type Selection
PWM Select
FU2-52 FU2-53
9334 9335
Safety Stop Dec. Rate Safety Stop Output Dec. Rate
Dec Rate safety_perc
FU2-60
933C
Control Mode Selection
Control Mode
FU2-61
933D
Auto Tuning Selection
Auto Tuning
FU2-62 FU2-63 FU2-64 Note16)
933E 933F 9340
%Rs %Lsigma PreEx time
FU2-67
9343
Stator Resistance of Motor Leakage Inductance of Motor Pre-excitation Time Manual/Auto Torque Boost Selection
FU2-68
9344
Torque Boost in Forward Direction
Fwd boost
FU2-69
9345
Torque Boost in Reverse Direction
Rev boost
FU2-80 FU2-81 FU2-82 FU2-83 FU2-84 FU2-85 FU2-87
9350 9351 9352 9353 9354 9355 9357
Power On display User Select Software Version Last Trip Time Power On Time Run-time Power Set
PowerOn Disp User Disp iP5A S/W Ver LastTripTime On-time Run-time Power Set
FU2-90
935A
Parameter Display
Para. disp
FU2-91
935B
Read Parameter
Para. Read
FU2-92
935C
Write Parameter
Para. Write
FU2-93
935D
Initialize Parameters
Para. Init
FU2-94
935E
Parameter Write Protection
Para. Lock
FU2-95
935F
Parameter Save
Para. Save
0 to 40 1 to 1000 [%] 0.75~22kW 0.7~15[kHz] 30kW 0.7~10[kHz] 37~75kW 0.7~4[kHz] 90~280kW 0.7~3[kHz] 315~450kW 0.7~2[kHz] 0 (Normal) 1 (Low leakage) 1.0 to 100.0 [sec] 2 to 500 0 (V/F) 1 (Slip compen) 2 (Sensorless) 0 (No) 1 (Static) 0.01 to 20 [%] 0.01 to 100 [%] 0 to 60 [sec] 0 (Manual) 1 (Auto) 0.75~90kW 0 to 15 [%] 110~450kW 0.75~90kW 0 to 15 [%] 110~450kW 0 to 12 Voltage Watt Ver X.X Ver X:XX:XX:XX:XX:X X:XX:XX:XX:XX:X X:XX:XX:XX:XX:X 0.01 to 400 [%] 0 Default 1 (All Para) 2 (Diff Para) 0 (No) 1 (Yes) 0 (No) 1 (Yes) 0 (No) 1 (All Groups) 2 (BAS) 3 (DRV) 4 (FU1) 5 (FU2) 6 (I/O) 7 (EXT) 8 (COM) 9 (APP) 0 to 9999 0 (No) 1 (Yes)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 16) FU2-64 is displayed when FU2-60 is set to [Sensorless]. Table 1) Switching frequency and fatory default value for each inverter capacity
28
LCD Keypad Display
Torque boost
Inverter Capacity 0.75 ~ 22 kW 30 kW 37 ~ 75 kW 90 ~ 280 kW 315 ~ 450 kW
Adj. During Run
Depending on the motor capacity 10 100 [%]
× × ○
5.0 [kHz] 4.0 [kHz] 3.0 [kHz] 2.0 [kHz]
○
0 (Normal )
×
100.0 [sec] 21 0 (V/F)
×
0 (No)
×
4[%] 12[%] 1 [sec]
× × ×
0 (Manual)
×
2.0 [%] 1.0 [%] 2.0 [%] 1.0 [%] 0 Voltage X.X * * * 100
× × ○ ○ * × × × ○
0 (Default)
○
0 (No)
×
0 (No)
×
0 (No)
×
0
○
0 (No)
×
Setting Range 0.7 ~ 15 [kHz] 0.7 ~ 10 [kHz] 0.7 ~ 4 [kHz] 0.7 ~ 3 [kHz] 0.7 ~ 2 [kHz]
Factory Default 5.0 [kHz] 4.0 [kHz] 3.0 [kHz] 2.0 [kHz]
Industrial Inverter for Fan and Pump STARVERT iP5A
I/O GROUP CODE I/O-00
Comm. Addr 9400
Description
LCD Keypad Display
Setting Range
Factory Default
Adj. During Run
Jump to Desired Code #
Jump code
1 to 98
1
○
V1 Filter
0 to 9999 [msec]
10 [msec]
○
0.00 [V]
○
0.00 [Hz]
○
10 [V]
○
60.00 [Hz]
○
10 [msec] 4 [mA]
○ ○
0.00 [Hz]
○
20 [mA]
○
60.00 [Hz]
○
1 (A)
○
10 [msec] 0 [kHz]
○ ○
0 [Hz]
○
10 [kHz]
○
60.00 [Hz]
○
0 (None)
○
0 (None)
○
1.0 [sec]
○
0 (Speed-L)
○
I/O-01 Note17)
9401
I/O-02
9402
I/O-03
9403
I/O-04
9404
Filtering Time Constant for V1 Signal Input V1 Input Minimum Voltage Frequency Corresponding to V1 Input Minimum Voltage V1 Input Minimum Voltage
I/O-05
9405
V1 Input Maximum Voltage
V1 Freq y2
I/O-06 I/O-07
9406 9407
I Filter I curr x1
I/O-08
9408
I/O-09
9409
I/O-10
940A
Filtering Time Constant for I Signal Input I Input Minimum Current Frequency Corresponding to I Input Minimum Current Filtering Time Constant for I Signal Input Frequency Corresponding to I Input Maximum Current
I/O-11
940B
Pulse Input Method
P Pulse set
I/O-12 I/O-13
940C 940D
P filter P pulse x1
I/O-14
940E
I/O-15
940F
I/O-16
9410
Pulse Input Filter Pulse Input Minimum Frequency Frequency Corresponding to I/O-13 Pulse Input Minimum Frequency Pulse Input Maximum Frequency Frequency Corresponding to I/O-15 Pulse Input Maximum Frequency
I/O-17
9411
Criteria for Analog Input Signal Loss
Wire broken
I/O-18
9412
Operating selection at Loss of Freq. Reference
Lost command
I/O-19
9413
Waiting Time after Loss of Freq. Reference
Time out
V1 volt x1 V1 Freq y1 V1 volt x2
I Freq y1 I curr x2 I Freq y2
P freq y1 P pulse x2 P freq y2
Programmable Digital Input Terminal I/O-20
9414
‘M1’ Define
0 1
M1 Define
0 1 2 0 1 2 3 0 1 2 3 4 5 6 7 8 9 10 11 13
0 to 12[V] 0 to FU1-30 [Hz] 0 to 100.00 [**] Note18) 0 to 12[V] 0 to FU1-30 [Hz] 0 to 100.00 [**] Note18) 0 to 9999 [msec] 0 to 20 [mA] 0 to FU1-30 [Hz] 0 to 100.00 [**] Note18) 0 to 20 [mA] 0 to FU1-30 [Hz] 0 to 100.00 [**] Note18) (A+B) (A) 0 to 9999 [msec] 0 to 10 [kHz] 0 to FU1-30 [Hz] 0 to 100.00 [**] Note18) 0 to 100 [kHz] 0 to FU1-30 [Hz] 0 to 100.00 [**] Note18) (None) (half of x1) (below x1) (None) (FreeRun) (Stop) (Protection) 0.1 to 120 [sec] (Speed-L) (Speed-M) (Speed-H) (XCEL-L) (XCEL-M) (XCEL-H) (Dc-brake) (2nd Func) (Exchange) (- Reserved -) ( Up) (Down) (Ext Trip)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 17) When DRV-04 is set to either V1, V1S, I or V1+I or Pulse, only selected item codes are displayed in I/O-1~I/O-19. 18) I/O-3,5,8,10,14,16 is displayed 0~100.00 [**] when App-02 is set to [proc PI mode] or APP-80 is set to [Ext PImode] and APP-06 PID Feedback Signal Selection is set to one of I, VI, Pulse, after then, one of I/O-86 ~I/O-88 is set to percentage, Bar, mBar, kPa, Pa except for Speed. Unit will be changed to selected unit. Only user unit displayed when APP-02 or APP-80 is set to [Yes], after APP-06 is set to one of I, V, Pulse, after then one of I/O-86 ~I/O-88 is set to either speed, percentage, Bar, mBar, kPa, Pa..
29
iP5A
Parameter Description I/O GROUP CODE
Comm. Addr
I/O-20
9414
I/O-21
9415
I/O-22
9416
I/O-23
9417
I/O-24
9418
I/O-25
9419
I/O-26
941A
I/O-27
941B
I/O-28
941C
I/O-29
941D
I/O-30 I/O-31 I/O-32 I/O-33 I/O-34 I/O-35 I/O-36 I/O-37 I/O-38
Note19)
941E 941F 9420 9421 9422 9423 9424 9425 9426
Description
Programmable Digital Input Terminal ‘M1’ Define
Programmable Digital Input Terminal ’M2’ Define Programmable Digital Input Terminal ’M3’ Define Programmable Digital Input Terminal ’M4’ Define Programmable Digital Input Terminal ’M5’ Define Programmable Digital Input Terminal ’M6’ Define Programmable Digital Input Terminal ’M7’ Define Programmable Digital Input Terminal ’M8’ Define Terminal Input Status Filtering Time Constant for Programmable Digital Input Terminals Jog Frequency Setting Step Frequency 4 Step Frequency 5 Step Frequency 6 Step Frequency 7 Step Frequency 8 Step Frequency 9 Step Frequency 10 Step Frequency 11
LCD Keypad Display
M1 Define
Setting Range 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
(Pre-Heat) (iTerm Clear) (Open-loop) (LOC/REM) (Analog hold) (XCEL stop) (P Gain2) -Reserved(Interlock1) (Interlock2) (Interlock3) (Interlock4) (Speed_X) (RST) (BX) (JOG) (FX) (RX) (ANA_CHG) (Pre-Excite) (Ext PID Run) (Up/Dn Clr)
Factory Default
○
0 (Speed-L)
M2 define
Same as I/O-20
1 (Speed-M)
○
M3 define
Same as I/O-20
2 (Speed-H)
○
M4 define
Same as I/O-20
27 (RST)
○
M5 define
Same as I/O-20
12 (Stop/3-wire )
○
M6 define
Same as I/O-20
29 (JOG)
○
M7 define
Same as I/O-20
30 (FX)
○
M8 define
Same as I/O-20
31 (RX)
○
In status
00000000000/11111111111
00000000000
*
Ti Filt Num
2 to 1000 [msec]
15
○
10 [Hz] 40 [Hz] 50 [Hz] 40 [Hz] 30 [Hz] 20 [Hz] 10 [Hz] 20 [Hz] 30 [Hz]
○ ○ ○ ○ ○ ○ ○ ○ ○
Jog Freq Step Freq-4 Step Freq-5 Step Freq -6 Step Freq-7 Step Freq -8 Step Freq -9 Step Freq -10 Step Freq -11
0 to FU1-30
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 19) I/O-30 ~ I/O-34 displayed only when one of I/O-20 ~ I/O-27 is set to either JOG, Speed_L, Speed_M, Speed_H. I/O-35 ~ I/O-42 displayed only when one of I/O-20 ~ I/O-27 is set to Speed_X.
30
Adj. During Run
Industrial Inverter for Fan and Pump STARVERT iP5A
CODE
Comm. Addr
I/O-39 I/O-40 I/O-41 I/O-42
9427 9428 9429 942A
I/O-50
9432
I/O-51
9433
I/O-52 Note20)
9434
I/O-53 I/O-54 I/O-55 I/O-56 I/O-57 I/O-58 I/O-59 I/O-60 I/O-61 I/O-62 I/O-63
9435 9436 9437 9438 9439 943A 943B 943C 943D 943E 943F
Description Step Frequency 12 Step Frequency 13 Step Frequency 14 Step Frequency 15 Acceleration Time 1 (for Step speed) Deceleration Time 1 (for Step speed) Acceleration Time 1 (for Step speed) Deceleration Time 2 Acceleration Time 3 Deceleration Time 3 Acceleration Time 4 Deceleration Time 4 Acceleration Time 5 Deceleration Time 5 Acceleration Time 6 Deceleration Time 6 Acceleration Time 7 Deceleration Time 7
LCD Keypad Display
Setting Range
Factory Default
Adj. During Run
Step Freq-12 Step Freq-13 Step Freq-14 Step Freq-15
0 to FU1-30
40 [Hz] 50 [Hz] 40 [Hz] 30 [Hz]
○ ○ ○ ○
Acc time-1
0 to 6000 [sec]
20 [sec]
○
Dec time-1
0 to 6000 [sec]
20 [sec]
○
Acc time-2
0 to 6000 [sec]
30 [sec]
○
Dec time-2 Acc time-3 Dec time-3 Acc time-4 Dec time-4 Acc time-5 Dec time-5 Acc time-6 Dec time-6 Acc time-7 Dec time-7
30 [sec] 40 [sec] 40 [sec] 50 [sec] 50 [sec] 40 [sec] 40 [sec] 30 [sec] 30 [sec] 20 [sec] 20 [sec]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
0 (Frequency)
○
100 [%] 2 (Voltage) 100 [%] 30.00 [Hz]
○ ○ ○ ○
10.00 [Hz]
○
0 (NONE)
○
I/O-70
9446
S0 Output Selection
S0 mode
I/O-71 I/O-72 I/O-73 I/O-74 Note21)
9447 9448 9449 944A
S0 adjust S1 mode S1 adjust FDT freq
I/O-75
944B
S0 Output Adjustment S1 Output Selection S1 Output Adjustment Frequency Detection Level Frequency Detection Bandwidth
0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] 0 to 6000 [sec] (Frequency) (Current) (Voltage) (DC link Vtg) (Ext PID Out) 10 to 200 [%] Same as I/O-70 10 to 200 [%] 0 to FU1-30 [Hz]
FDT band
0 to FU1-30 [Hz]
I/O-76
944C
Programmable Digital Output Terminal Define (Aux terminal)
Aux Mode1
0 1 2 3 4
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
(NONE) (FDT-1) (FDT-2) (FDT-3) (FDT-4) (FDT-5) (OL) (IOL) (Stall) (OV) (LV) (OH) (Lost Command) (Run) (Stop) (Steady)
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 20) I/O-52 ~ I/O-63 displayed only when one of I/O-20 ~ I/O-27 is set to either XCEL_L, XCEL_M, XCEL_H. 21) I/O-74 ~ I/O-75 displayed only when one of I/O-76 ~ I/O-79 is set to either FDT-1~FDT5
31
iP5A
Parameter Description I/O GROUP CODE
Comm. Addr
Description
Output Terminal Define
Setting Range
Factory Default
Adj. During Run
(INV line) (COMM line) (SpeedSearch) (Ready) (MMC) (CriticalTrip)
0 (NONE)
○
Aux mode2
Same as I/O-76
0 (NONE)
○
Aux mode3
Same as I/O-76
0 (NONE)
○
Aux mode4
Same as I/O-76
0 (NONE)
○
Relay mode
000 to 111 [bit]
010 [bit]
○
Out status
00000000/11111111
00000000
*
Relay On
0 to 9999
0
×
Relay Off
0 to 9999
0
×
0 (Power On Fan)
×
70 [℃]
○
0 (Percent)
×
100[%] 1
× ○
3 (9600 bps)
○
0 (None)
○
1.0 [sec]
○
I/O-76
944C
I/O-77
944D
I/O-78
944E
I/O-79
944F
I/O-80
9450
I/O-81
9451
I/O-82
9452
I/O-83
9453
I/O-84
9454
Fan Con Sel (37 ~ 90kW)
Fan Con. Sel
I/O-85
9455
Fan Temp (37 ~ 90kW)
Fan Temp
Programmable Digital Output Terminal Define Programmable Digital Output Terminal Define Programmable Digital Output Terminal Define Fault Output Relay Setting (3A, 3B, 3C) Terminal Output Status Waiting Time after Fault Output Relay On Waiting Time after Fault Output Relay Off
Aux Mode1
COM Time Out Delay Time
2 to 1000 [msec]
5 [msec]
○
In No/Nc Set In CheckTime OH Trip Sel MO Trip Temp
00000000000/11111111111 1 to 1000 000 to 111 [bit] 0 to 255 [℃]
00000000000 1 [msec] 010 [bit] 110 [℃]
× × × ×
9456
Input User Unit Selection
Unit Sel
I/O-87 I/O-90
9457 945A
Unit Maximum Selection Inverter Number
Unit Max Val Inv No.
I/O-91 Note22)
945B
Baud Rate Selection
Baud rate
I/O-92 Note23)
945C
Operating Method at Loss of Freq. Reference
COM Lost Cmd
I/O-93
945D
I/O-94
945E
I/O-95 I/O-96 I/O-97 I/O-98
945F 9460 9461 9462
Waiting Time after Loss of Freq. Reference Communication Response Delay time A or B contact Input time Overheat Trip Selection Motor Overheat Trip Temperature
16 17 18 19 20 21
(Power On Fan) (Run Fan) (Temper-Fan) 0 to 70 [℃] (Percent) (Bar) (mBar) (kPa) (PSI) (Pa) 1.0 to 999.9[%] 1 to 250 (1200 bps) (2400 bps) (4800 bps) (9600 bps) (19200 bps) (38400 bps) (None) (FreeRun) (Stop) 0.1 to 120 [sec]
I/O-86
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 22) 38400 bps can be set only when the external communication option card is installed. 23) Only I/O-92 ~ I/O-93 displayed when DRV-03/04 is set to [int485].
32
LCD Keypad Display
0 1 2 0 1 2 3 4 5
0 1 2 3 4 5 0 1 2
Industrial Inverter for Fan and Pump STARVERT iP5A
APP GROUP CODE APP-00 APP-01 APP-02 APP-03 APP-04
Note25) Note26)
Comm. Addr
Description
LCD Keypad Display
9700
Jump to Desired Code #
Jump code
9701
Application Mode Selection
App mode
9702
PID Operation Selection
Proc PI mode
9703
PID F Gain Selection PID Auxiliary Reference Mode Selection
PID F-Gain
9704
Aux Ref Enbl
APP-05 Note27)
9705
PID Auxiliary Reference Signal Selection
Aux Ref Sel
APP-06
9706
PID Feedback Signal Selection
PID F/B
APP-07 APP-08 APP-09 APP-11 APP-12 APP-13 APP-14 APP-15 APP-16 APP-17 APP-18
9707 9708 9709 970B 970C 970D 970E 970F 9710 9711 9712
Meter I Maximum Value Meter V Maximum Value Meter P Maximum Value P Gain for PID Control I Time for PID Control D Time for PID Control High Limit Frequency for PID Control Low Limit Frequency for PID Control PID Output Gain PID P2 Gain P Gain Scale
Meter I Max Meter V Max Meter P Max PID P Gain PID I Time PID D Time PID Hi Limit PID LowLimit PID OutScale PID P2 Gain P Gain Scale
APP-19
9713
PID Output Inverse
PID OutInv.
APP-20
9714
PID U Curve Feedback Select
PID U Fbk
APP-23 APP-24 APP-25
9717 9718 9719
PrePID Reference Frequency PrePID Exit Level PrePID Stop delay
PrePID Freq PrePID Exit PrePID Dly
APP-26
971A
Pipe Broken
Pipe Broken
APP-27 APP-28 APP-29 APP-30 Note28) APP-31 APP-32
971B 971C 971D 971E 971F 9720
Sleep Delay Time Sleep Frequency Wake-Up Level 2nd Acceleration Time 2nd Deceleration Time 2nd Base Frequency
Sleep Delay Sleep Freq WakeUp level 2nd Acc Time 2nd Dec Time 2nd BaseFreq
APP-33
9721
2nd V/F Pattern
2nd V/F
APP-34 APP-35 APP-36 APP-37
9722 9723 9724 9725
2nd Forward Torque Boost 2nd Reverse Torque Boost 2nd Stall Prevention Level 2nd Electronic Thermal Level for 1 Minute
2nd F-Boost 2nd R-Boost 2nd Stall 2nd ETH 1min
Setting Range 0 1 0 1 0 1 0 1 2 3 4 5 6 7 8 0 1 2
0 1 0 1
0 1
0 1 2
1 to 80 (None) (MMC) (No) (Yes) 0 to 999.9[%] (No) (Yes) (Keypad-1) (Keypad-2) (V1) (V1S) (I) (V1+I) (Pulse) (Int. 485) (Ext. PID) (I) (V1) (Pulse) 0 to 20.00 mA 0 to 12.00 V 0 to100.0kHz 0 to 999.9 [%] 0 to 32.0 [sec] 0 to100 [msec] 0.00 to FN1-30 FN1-32 to APP-10 0.0 to 999.9 [%] 0.0 to 999.9 [%] 0.0 to 100.0 [%] (No) (Yes) (No) (Yes) 0 to FU1-30 0 to 100.0% 0 to 9999 (No) (Yes) 0.0 to 9999 [sec] 0 to FU1-30 [Hz] 0.0 to 100.0 [%] 0 to 6000 [sec] 0 to 6000 [sec] 30 to FN1-30 [Hz] (Linear) (Square) (User V/F) 0.0 to 15.0 [%] 0.0 to 15.0 [%] 30 to 150 [%] FU2-28 to 200 [%]
Factory Default
Adj. During Run
1
○
0 (None)
×
0 (No)
×
0.0 [%]
○
0 (No)
×
2 (V1)
×
0 (I)
×
20.00 mA 10.00V 100.0kHz 1.0 [%] 10.0 [sec] 0.0 [msec] 60 .00[Hz] 0.5 [Hz] 100.0 [%] 100.0 [%] 100.0 [%]
○ ○ ○ ○ ○ ○ ○ ○ × × ×
0 (No)
×
0 (No)
×
0 0 600
○ ○ ○
0 (No)
×
60.0 [sec] 0.00 [Hz] 2 .0[%] 5 [sec] 10 [sec] 60 [Hz]
○ ○ ○ ○ ○ ×
0 (Linear)
×
2.0 [%] 2.0 [%] 100 [%] 130[%]
× × × ○
The gray highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 25) Only APP-03 ~ APP-17 displayed when APP-02 is set to [Yes]. Only APP-03 ~ APP-17 and APP-63 ~ APP-65 displayed when APP-2 is set to [Yes]. 26) If APP-04 Aux Ref Mode is no set, DRV-04 setting will be reference of process PID. And APP -05 setting will be ignored 27) If APP-04 is set, APP-04 will appear. And APP -05 setting value will be reference of process PID, DRV-04 setting will be ignored. 28) Only APP-20 ~ APP-29 displayed only when one of I/O-20 ~ I/O-27 is set to either“2nd Func”.
33
iP5A
Parameter Description APP GROUP Comm. Addr
Description
LCD Keypad Display
APP-38 APP-39 APP-40 Note29) APP-41 APP-42 APP-43
9726 9727 9728 9729 972A 972B
2nd Electronic Thermal Level for Continuous 2nd Rated Motor Current Number of Auxiliary Motor Run Display Aux. Motor Start Selection Operation Time Display on Auto Change The Number of Aux Motor
2nd ETH Cont 2nd R-Curr Aux Mot Run Starting Aux Auto Op Time Nbr Aux`s
APP-44
972C
Aux. Motor Stop Sequence
F-in L-Out
APP-45
972D
How to stop Aux. Motor
ALL Stop
APP-47 APP-48 APP-49 APP-50 APP-51 APP-52 APP-53 APP-54 APP-58 APP-59
972F 9730 9731 9732 9733 9734 9735 9736 973A 973B
Start freq 1 Start freq 2 Start freq 3 Start freq 4 Stop freq 1 Stop freq 2 Stop freq 3 Stop freq 4 Aux start DT Aux stop DT
APP-60
973C
APP-61
973D
Start Frequency of Aux. Motor 1 Start Frequency of Aux. Motor 2 Start Frequency of Aux. Motor 3 Start Frequency of Aux. Motor 4 Stop Frequency of Aux. Motor 1 Stop Frequency of Aux. Motor 2 Stop Frequency of Aux. Motor 3 Stop Frequency of Aux. Motor 4 Delay Time before Operating Aux Motor Delay Time before Stopping Aux Motor Accel Time when the Number of Pump Decreases Decel Time when the Number of Pump Increases
CODE
Adj. During Run
120[%] 3.6[A] * 1 * 4
○ × * ○ * ○
1 (Yes)
×
1 (Yes)
×
49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 49.99 [Hz] 20.00 [Hz] 20.00 [Hz] 20.00 [Hz] 20.00 [Hz] 5.0 [sec] 5.0 [sec]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Pid AccTime
0 to 600.0 [sec]
2.0 [sec]
○
0 to 600.0 [sec] (No) (Yes) (EXCH_NONE), (AUX_EXCH), (MAIN_ EXCH) 00:00 to 99:00 FN1-32 to FN1-30[Hz] 0 (No) 0 to100% 0 to100% (No) (Yes) (I) (V1) (Pulse) (Keypad) 0 to 100.00 [%] (I) (V1) (Pulse) 0 to 999.9 [%] 0 to 32.0 [sec] 0 to 2000 [msec] 0 to 100.00 [%] 0 to 30.00 [%] 0 to 999.9 0 to 999.9 0 to 100.0 0 to 999.9 [%] (No) (Yes) 50 to 200 [msec]
2.0 [sec]
○
0 (No)
×
0(EXCH_NONE)
○
72:00 20.0 [Hz] 0 (No) 2[%] 2[%]
○ ○ ○ ○ ○
0 (No)
×
3(Keypad)
×
50.00 [%]
×
0 (I)
×
1.0 [%] 10.0 [sec] 0 [msec] 100.00 [%] 0 [%] 100.0 [%] 100.0 [%] 100.0 [%] 0.0 [%]
× × × × × × × × ○
0 (No)
×
100 [msec]
×
973E
PID Bypass Selection
Regul Bypass
APP-66
9742
Auto Change Mode Selection
AutoCh_Mode
APP-67 APP-68 APP-69 APP-71 APP-72
9743 9744 9745 9747 9748
Auto Change Time Auto Change Freq Inter-Lock Selection Pressure difference for Aux motor Start Pressure difference for Aux motor Stop
AutoEx-intv AutoEx-Freq Inter-lock Aux Stt Diff Aux Stp Diff
APP-80
9750
Ext PID Operation Selection
Ext PI Mode
APP-81 Note30)
9751
Ext PID Reference Signal Selection
ExtPI RefSel
APP-82
9752
Ext PID Reference Level
Ext PI Ref %
APP-83
9753
Ext PID Feedback Signal Selection
ExtPI FbkSel
APP-85 APP-86 APP-87 APP-88 APP-89 APP-90 APP-91 APP-92 APP-93
9755 9756 9757 9758 9759 975A 975B 975C 975D
P Gain for ExtPID I Time for ExtPID D Time for ExtPID High Limit Frequency for ExtPID Control Low Limit Frequency for ExtPID Control ExtPID Output Scale ExtPID P2 Gain ExtPID P Gain Scale ExtPID F Gain
ExtPID Pgain ExtPID Itime ExtPID Dtime ExtPID Lmt-H ExtPID Lmt-L ExtPID Scale ExtPI P2Gain ExtPI PScale ExtPID F-gain
APP-95
975F
ExtPID Output Inverse
ExtPI OutInv
APP-97
9761
ExtPID Loop Time
ExtPI LoopTm
34
0 1 0 1
50 to FU2-27 (Max 150%) 1 to 200 [A] * 1 to 4 * 0 to 7 (No) (Yes) (No) (Yes) 0 to FU1-30 0 to FU1-30 0 to FU1-30 0 to FU1-30 0 to FU1-30 0 to FU1-30 0 to FU1-30 0 to FU1-30 0.0 to 999.9 [sec] 0.0 to 999.9 [sec]
Factory Default
Pid DecTime
APP-62
The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set. Note 29) Only APP-40 ~ APP-71 displayed when APP-01 is set to [MMC]. 30) Only APP-81 ~ APP-97 displayed when APP-80 Ext PI mode is set to [Yes].
Setting Range
0 1 0 1 2
0 1 0 1 2 3 0 1 2
0 1
Industrial Inverter for Fan and Pump STARVERT iP5A
EXT GROUP CODE
Comm. Addr
Description
LCD Keypad Display
Setting Range
Factory Default
Adj. During Run
1
○
*
*
Frequency
○
100 [%]
○
0 [%]
○
DC link Vtg
○
EXT-00
9500
Jump to Desired Code #
Jump code
1 to 45
EXT-01
9501
Type of SUB Board
Sub B/D
Frequency
Sub-E Current Voltage EXT-40
9528
Current Output Terminal 1(CO1) Selection
AM1 mode
DC link Vtg Ext PID Out
EXT-41
9529
Adjust Gain of Current Output Terminal 1(CO1)
AM1 adjust
10-200 [%] 0-100 [%]
EXT-42
952A
Adjust Offset of Current Output Terminal 1(CO1)
AM1 Offset
Frequency Current Voltage
EXT-43
952B
Current Output Terminal 2(CO2) Selection
AM2 mode
EXT-44
952C
Adjust Gain of Current Output Terminal 2(CO2)
AM2 adjust
10-200 [%]
100 [%]
○
EXT-45
952D
Adjust Offset of Current Output Terminal 2(CO2)
AM2 Offset
0-100 [%]
0 [%]
○
LCD Keypad Display
Setting Range
Factory Default
Adj. During Run
1 to 60
1
○
*
*
None
×
Ver X.X
*
70
×
DC link Vtg Ext PID Out
* Only the above EXT group displayed when the corresponding option board is installed. * Refer to the SUB board option manual for details.
COM GROUP CODE
Comm. Addr
Description
COM-00
9600
Jump to Desired Code #
Jump code
COM-01
9601
Type of SUB Board
Opt B/D
RS485 DeviceNet Profibus BACnet LonWork
COM-02
9602
Option Mode
Opt mode
None Command Freq Cmd + Freq
COM-03
9603
Option Version
Opt Version
Ver X.X
COM-13
960D
Device Net Input Instance
In Instance
70 71 110 111
COM-17
9611
PLC Station ID
Station ID
0 to 63
1
○
COM-20
9614
Profi MAC ID
Profi MAC ID
1 to 127
1
○
COM-30
961E
Output Num
Output Num
0 to 8
3
○
COM-31
961F
Output 1
Output 1
0000-FFFF (HEX)
000A(HEX)
○
35
iP5A
Parameter Description COM GROUP CODE
Comm. Addr
Description
LCD Keypad Display
Setting Range
Factory Default
Adj. During Run
COM-32
9620
Output 2
Output 2
0000-FFFF (HEX)
000E(HEX)
○
COM-33
9621
Output 3
Output 3
0000-FFFF (HEX)
000F(HEX)
○
COM-34
9622
Output 4
Output 4
0000-FFFF (HEX)
0000(HEX)
○
COM-35
9623
Output 5
Output 5
0000-FFFF (HEX)
0000(HEX)
○
COM-36
9624
Output 6
Output 6
0000-FFFF (HEX)
0000(HEX)
○
COM-37
9625
Output 7
Output 7
0000-FFFF (HEX)
0000(HEX)
○
COM-38
9626
Output 8
Output 8
0000-FFFF (HEX)
0000(HEX)
○
COM-40
9628
Input Num
Input Num
0-8
2
○
COM-41
9629
Input 1
Input 1
0000-FFFF (HEX)
0005(HEX)
○
COM-42
962A
Input 2
Input 2
0000-FFFF (HEX)
0006(HEX)
○
COM-43
962B
Input 3
Input 3
0000-FFFF (HEX)
0000(HEX)
○
COM-44
962C
Input 4
Input 4
0000-FFFF (HEX)
0000(HEX)
○
COM-45
962D
Input 5
Input 5
0000-FFFF (HEX)
0000(HEX)
○
COM-46
962E
Input 6
Input 6
0000-FFFF (HEX)
0000(HEX)
○
COM-47
962F
Input 7
Input 7
0000-FFFF (HEX)
0000(HEX)
○
COM-48
9630
Input 8
Input 8
0000-FFFF (HEX)
0000(HEX)
○
8None/1Stop
○
None/1Stop 8None/2Stop
COM-60
963C
Parity/Stop
Parity/Stop 8
COM-61
963D
Opt Para-1
Opt Para-1
0 to FFFF
0
○
COM-62
963E
Opt Para-2
Opt Para-2
0 to FFFF
0
○
COM-63
963F
Opt Para-3
Opt Para-3
0 to FFFF
0
○
COM-64
9640
Opt Para-4
Opt Para-4
0 to FFFF
0
○
COM-65
9641
Opt Para-5
Opt Para-5
0 to FFFF
0
○
COM-66
9742
Opt Para-6
Opt Para-6
0 to FFFF
0
○
0 (No)
×
8Even/1Stop 8Odd/1Stop
COM-67
9743
Comm UpDate
* Only the above COM group displayed when the corresponding option board is installed. * COM-61~66 parameter is used to LonWorks and BACnet communication.
36
Comm UpDate
0
(No)
1
(Yes)
Industrial Inverter for Fan and Pump STARVERT iP5A
Trial Run Operation Example (1)
Wiring
V/F Control + Analog Voltage Input (V1) + Operation via Terminal (FX/RX) 3P AC INPUT
Operation condition �Control mode: V/F control �Frequency command: 50 [Hz] analog input via V1 terminal �Accel/Decel time: Accel‐15 [sec], Decel‐25 [sec] �Drive mode: Run/Stop via FX/RX terminal, Control terminal: NPN mode
R (L1)
U
S (L2)
V
T (L3)
W
IM
G S0
S/W M8 (RX)
S1
M7 (FX) 5G
M6 M5 M4
3A
M3
3C
M2
3B
M1 CM Potentiometer 2 [kohm], 1/2W V+ V1 5G
Step
Parameter setting
Description
Code
1
Control Mode Selection
2
Drive Mode
DRV-3
Set it to Fx/Rx-1.
3
Frequency Mode
DRV-4
Set V1 Analog input value in frequency mode.
4 5
50 [Hz] Freq Command Setting Accel/Decel Time
FU2-60
DRV-0 DRV-1 DRV-2
Set it to 0 (V/F).
Set freq command 50 [Hz] via V1 (Potentiometer). Set Accel time to 15 [sec] in DRV-2. Set Decel time to 25 [sec] in DRV-3. Motor starts to rotate in forward direction at 50Hz with Accel time 15 [sec] when
6
Terminal FX
I/O-26
FX terminal is turned ON. Motor decelerates to stop with Decel time 25 [sec] when FX terminal is turned OFF. When RX terminal is turned ON motor starts to rotate in Reverse direction
7
Terminal RX
I/O-27
at 50 [Hz] with Accel time 15 [sec]. When it is OFF, motor decelerates to stop with Decel time 25 [sec].
37
iP5A
Trial Run Operation Example (2)
Wiring
V/F control + Analog input (V1S) + Operation via terminal FX/RX Operation condition �Control mode: V/F control �Frequency command: Setting 50 [Hz] via Analog input (V1S) �Accel/Decel time: Accel time 15 [sec], Decel time 25 [sec] �Drive mode: Run/Stop via FX/RX, Control terminal: NPN mode
3P AC INPUT R (L1)
U
S (L2)
V
T (L3)
W
IM
G S0
S/W M8 (RX)
S1
M7 (FX) 5G
M6 M5 M4
3A
M3
3C
M2
3B
M1 CM Potentiometer 2 [kohm], 1/2W V+ V1 V-
Step
Parameter setting
Description
Code
1
Control Mode Selection
FU2-60
Set it to 0 (V/F).
2
Drive Mode
DRV-3
Set it to 1 (Fx/Rx-1).
3
Frequency Mode
DRV-4
Set it to 3 (V1S).
DRV-0
Set 50 [Hz] via potentiometer (V1S).
DRV-1
Set accel time to 15 [sec] in DRV-1
DRV-2
with decal time to 25 [sec] in DRV-2.
4 5
Operating Frequency Command 50 [Hz] Setting Accel/Decel Time Setting
When FX terminal is turned ON, motor rotating in forward direction starts 6
FX Terminal (M7)
IO-26
running at 50 [Hz] for 15 [sec]. When FX terminal is turned OFF, motor decelerates to stop for 25 [sec]. When RX terminal is turned ON, motor rotating in reverse direction starts
7
RX Terminal (M8)
IO-27
running at 50 [Hz] for 15 [sec]. When RX terminal is turned OFF, motor decelerates to stop for 25 [sec].
38
Industrial Inverter for Fan and Pump STARVERT iP5A
Dimensions SV008~055iP5A (200/400V Class) & SV0055~0110iP5A (600V Class)
DRV
FU1
FU2
I/O
EXT
LE-200 LC-200 MODE
PROG
RUN SHIFT ENTER
ESC SHIFT
REV
FWD
C2
RUN
STOP
C3
RESET
6
W2 W1
6
7.5
H2 H1
RESET
C1
PROG ENT
STOP
D1
mm (inches)
Model SV008iP5A-2/4 SV015iP5A-2/4 SV022iP5A-2/4 SV037iP5A-2/4 SV055iP5A-2/4 SV0055iP5A-6 SV0075iP5A-6 SV0110iP5A-6
W1
W2
H1
H2
D1
C1
C2
C3
Enclosure Type
150 (5.91) 150 (5.91) 150 (5.91) 150 (5.91) 150 (5.91) 7.87(200) 7.87(200) 7.87(200)
130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 7.09(180) 7.09(180) 7.09(180)
284 (11.18) 284 (11.18) 284 (11.18) 284 (11.18) 284 (11.18) 13.98(355) 13.98(355) 13.98(355)
269 (10.69) 269 (10.69) 269 (10.69) 269 (10.69) 269 (10.69) 13.39(340) 13.39(340) 13.39(340)
156.5 (6.16) 156.5 (6.16) 156.5 (6.16) 156.5 (6.16) 156.5 (6.16) 7.19(182.5) 7.19(182.5) 7.19(182.5)
24 (0.98) 24 (0.98) 24 (0.98) 24 (0.98) 24 (0.98) 1.12(28.5) 1.12(28.5) 1.12(28.5)
24 (0.98) 24 (0.98) 24 (0.98) 24 (0.98) 24 (0.98) 0.94(24) 0.94(24) 0.94(24)
24 (0.98) 24 (0.98) 24 (0.98) 24 (0.98) 24 (0.98) 1.12(28.5) 1.12(28.5) 1.12(28.5)
IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP 20 UL Type 1 IP 20 UL Type 1 IP 20 UL Type 1
SV075~300iP5A (200/400V Class) & SV0150~0300iP5A (600V Class)
DRV
FU1
FU2
I/O
EXT
LE-200 LC-200 MODE
PROG
RUN SHIFT ENTER
SV150~300 iP5A-2/4
ESC SHIFT
PROG ENT
STOP REV
RESET
FWD
STOP
RUN
RESET
C2
H1 H2
C1
C3
7.5
SV075~110 iP5A-2/4 W3
W3
D1
W2 W1
mm (inches)
Model SV075iP5A-2/4 SV110iP5A-2/4 SV150iP5A-2/4/6 SV185iP5A-2/4/6 SV220iP5A-2/4/6 SV300iP5A-2/4/6
W1
W2
200 (7.87) 180 (7.09) 200 (7.87) 180 (7.09) 250 (9.84) 230 (9.06) 250 (9.84) 230 (9.06) 304 (11.97)284 (11.18) 304 (11.97)284 (11.18)
W3 6 (0.23) 6 (0.23) 9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)
H1
H2
D1
C1
C2
C3
284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37) 284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37) 385 (15.16)370 (14.57) 201 (7.91) 385 (15.16)370 (14.57) 201 (7.91) 460 (18.11)445 (17.52) 234 (9.21) 460 (18.11)445 (17.52) 234 (9.21) -
Enclosure Type IP20 UL Type 1 IP20 UL Type 1 IP00 UL Open IP00 UL Open IP00 UL Open IP00 UL Open
39
iP5A
Dimensions SV150~300iP5A (UL Type 1 or UL Open Type with Conduit Option used, 200V/400V Class) W1 W2
Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP FWD
RESET
D2
D1
H3
H2 H1
REV
9 7.5
9
W3
mm (inches)
Model SV150iP5A-2/4 SV185iP5A-2/4 SV220iP5A-2/4 SV300iP5A-2/4
W1
W2
H1
H2
H3
D1
D2
C3
Enclosure Type
250 (9.84) 250 (9.84) 304 (11.97) 304 (11.97)
230 (9.06) 230 (9.06) 284 (11.18) 284 (11.18)
200.8 (7.9) 200.8 (7.9) 236 (9.29) 236 (9.29)
385 (15.16) 385 (15.16) 460 (18.11) 460 (18.11)
370 (14.57) 370 (14.57) 445 (17.52) 445 (17.52)
454.2 (17.88) 454.2 (17.88) 599.2 (23.59) 599.2 (23.59)
201 (7.91) 201 (7.91) 234 (9.21) 234 (9.21)
146 (5.74) 146 (5.74) 177.5 (6.98) 177.5 (6.98)
IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1
-Built-in DCL Type SV150~SV300 iP5A (400V Class)D1
W1 W2
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP RESET
FWD
H1 H2
REV
W3
mm (inches)
Model SV150, 185iP5A-4L SV220, 300iP5A-4L
40
W1
W2
W3
H1
H2
D1
Enclosure Type
250 (9.84) 260 (10.23)
186 (7.32) 220 (8.66)
7 (0.28) 7 (0.28)
403.5 (15.88) 480 (18.89)
392 (15.43) 468.5 (18.44)
261.2 (10.28) 268.6 (10.57)
IP00 UL Type 1 IP20 UL Type 1
Industrial Inverter for Fan and Pump STARVERT iP5A
SV150~SV300 iP5A (Built-in DCL Type, UL Type 1 or UL Open Type with Conduit Option used, 400V Class) W1 W2
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP RESET
FWD
D2
D1
H1
H2
REV
W3
mm (inches)
Model SV150, 185iP5A-4L SV220, 300iP5A-4L
W1
W2
W3
250 (9.84) 260 (10.23)
186 (7.32) 220 (8.66)
7 (0.28) 7 (0.28)
H1
H2
D1
475.5 (18.72) 392 (15.43) 261.2 (10.28) 552 (21.73) 468.5 (18.44) 268.6 (10.57)
D2
Enclosure Type
188.4 (7.42) 188.8 (7.43)
IP20 UL Type 1 IP20 UL Type 1
SV370~SV550iP5A (400V Class) & SV0370~0550iP5A (600V Class)
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP RESET
FWD
H1 H2
REV
D1 W3
W3
mm (inches)
W2 W1
Model
W1
300 (11.81) SV370, 450iP5A-4 SV550iP5A-4, SV0370 300 (11.81) 0450, 0550iP5A-6 SV370, 450iP5A-4L 300 (11.81) (Built-in DCLType)
SV550iP5A-4L (Built-in DCL Type)
300 (11.81)
H2
D1
Enclosure Type
W2
W3
H1
190 (7.48)
9 (0.35)
534 (21.02)
515 (20.28) 265.6 (10.46)
IP00 UL Open
190 (7.48)
9 (0.35)
534 (21.02)
515 (20.28) 292.6 (11.52)
IP00 UL Open
190 (7.48)
9 (0.35)
684 (26.92)
665 (26.18) 265.6 (10.46)
IP00 UL Open
190 (7.48)
9 (0.35)
684 (26.92)
665 (26.18) 292.6 (11.52)
IP00 UL Open
41
iP5A
Dimensions SV370~550iP5A (UL Type 1 or UL Open Type with Conduit Option Used, 400V Class) W1 W2 Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP RESET
FWD
D2
D1
H1
H2
REV
W3
mm (inches)
Model SV370, 450iP5A-4 SV550iP5A-4 SV370, 450iP5A-4L SV550iP5A-4L
W1
W2
W3
H1
H2
D1
300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)
190 (7.48) 190 (7.48) 190 (7.48) 190 (7.48)
9 (0.35) 9 (0.35) 9 (0.35) 9 (0.35)
642 (25.28) 642 (25.28) 792 (31.18) 792 (31.18)
515 (20.28) 515 (20.28) 665 (26.18) 665 (26.18)
D2
265.6 (10.46) 163.4 (6.43) 292.6 (11.52) 190.4 (7.5) 265.6 (10.46) 163.4 (6.43) 292.6 (11.52) 190.4 (7.5)
Enclosure Type IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1 IP20 UL Type 1
SV750, 900iP5A (400V Class) & SV0750~0900iP5A (600V Class)
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP RESET
FWD
H1 H2
REV
W3
D1
W3 W2 W1
mm (inches)
Model SV750, 900iP5A-4 SV0750, 0900iP5A-6 SV750, 900iP5A-4L (Built-in DCL Type)
42
W1
W2
W3
H1
H2
D1
Enclosure Type
370 (14.57)
220 (8.66)
9 (0.35)
610 (24.02)
586.5 (23.09)
337.6 (13.29)
IP00 UL Open
370 (14.57)
220 (8.66)
9 (0.35)
760 (29.92)
736.6 (28.99)
337.6 (13.29)
IP00 UL Open
Industrial Inverter for Fan and Pump STARVERT iP5A
SV750, 900iP5A (UL Type 1 or UL Open Type with Conduit Option used, 400V Class) W1 W2
Note) Mounting NEMA 1 conduit option to the 15~90kW (20~125HP) Open Type meets NEMA 1 but does not comply with UL Enclosed Type 1. To that end, please purchase UL Type 1 product.
LC-200 MODE
PROG
ENTER
ESC SHIFT
STOP RESET
FWD
D2
D1
H1
H2
REV
W3
mm (inches)
Model SV750, 900iP5A-4 SV750, 900iP5A-4L (Built-in DCL Type)
W1
W2
W3
H1
H2
D1
D2
Enclosure Type
370 (14.57)
220 (8.66)
9 (0.35)
767.5 (30.22)
586.5 (23.09)
337.6 (13.29)
223.4 (8.8)
IP20 UL Type 1
370 (14.57)
220 (8.66)
9 (0.35)
917.5 (36.12)
736.5 (28.99)
337.6 (13.29)
223.4 (8.8)
IP20 UL Type 1
SV1100, 1600iP5A (400V Class) & SV1100iP5A (600V Class) W1 W2
H1 H2
D1
W3
W3
mm (inches)
Model SV1100, 1320iP5A-4L SV1100iP5A-6L SV1600iP5A-4L
W1
W2
W3
H1
H2
D1
Enclosure Type
510 (20.08)
381 (15.00)
11 (0.43)
783.5(30.85)
759(29.88)
422.6 (16.64)
IP00 UL Open
510 (20.08)
381 (15.00)
11 (0.43)
861(33.90)
836.5(32.93)
422.6 (16.64)
IP00 UL Open
43
iP5A
SV2200, 2800iP5A (400V Class)
D1
H1 H2
W1 W2
W3
W3
W3
mm (inches)
Model SV2200, 2800iP5A-4L
W1
W2
W3
H1
H2
D1
Enclosure Type
690 (27.17)
581 (22.87)
14 (0.55)
1063 (41.85)
1043.5 (41.08)
449.6 (17.70)
IP00 UL Open
SV3150, 4500iP5A (400V Class) D1
H1 H2
15
W1 W2
W3
W3
W3
W4
mm (inches)
Model SV3150, iP5A-4L SV3750, 4500iP5A-4L
44
W1
W2
W3
H1
H2
D1
Enclosure Type
772 (30.39)
500 (19.69)
13 (0.51)
1140.5 (44.90)
1110 (43.70)
442 (17.40)
IP00 UL Open
922 (36.30)
580 (22.83)
14 (0.55)
1302.5 (51.28) 1271.5 (50.06)
495 (19.49)
IP00 UL Open
Industrial Inverter for Fan and Pump STARVERT iP5A
DB (Dynamic Braking) Unit DBU Models UL
Inverter
Applicable motor rating
200V class
Non UL type 400V class
DB Unit
11~15 kW (15~20 HP)
SV150DBU-2
18.5~22 KW (25~30 HP)
SV220DBU-2
Dimension Group 1.
30~37 kW (40~50 HP)
SV037DBH-2
45~55 kW (60~75 HP)
SV037DBH-2, 2set
11~15 kW (15~20 HP)
SV150DBU-4
18.5~22 kW (25~30 HP)
SV220DBU-4
30~37 kW (40~50 HP)
SV037DBH-4
Group 1.
45~55 kW (60~75 HP)
Group 2. SV075DBH-4
75 kW (100 HP) 11~15 kW (15~20 HP) 200V class
UL type
SV150DBU-2U
18.5~22 kW (25~30 HP)
SV220DBU-2U
30~37 kW (40~50 HP)
SV370DBU-2U
45~55 kW (60~75 HP)
SV550DBU-2U
11~15 kW (15~20 HP)
SV150DBU-4U
18.5~22 kW (25~30 HP)
SV220DBU-4U
30~37 kW (40~50 HP)
SV370DBU-4U
45~55 kW (60~75 HP)
SV550DBU-4U
75 kW (100 HP)
400V class
Group 2.
Group 3.
SV750DBU-4U
90~110 kW (125~150 HP)
SV550DBU-4, 2set
132~160 kW (200~250 HP)
SV750DBU-4, 2set
220 kW (300 HP)
SV750DBU-4, 3set
280~315 kW (350~400 HP)
-
375~450 kW (500~600 HP)
-
-
Terminal Configuration �Group 1 -
CM
OH
�Group 2 -
G
N
B2
P/B1
�Group 3 -
P
N
G
B1
G
B2
B1
N
P
B2
Terminals
Description
Terminals
G
Ground terminal
N
Connect to inverter terminal N
B2
Connect to DB Resistor’s B2
P
Connect to inverter terminal P1
B1
Connect to DB Resistor’s B1
CM
OH common
N
Connect to inverter terminal N
P
Connect to inverter terminal P1
OH*
Description
Over Heat Trip output terminal (Open Collector output: 20mA, 27V DC)
45
iP5A
Wiring for DB unit and DB resistor (For 5.5~90kW/7.5~125HP inverters)
DB Resistor
DB Unit
TH2
B2
B2
G
TH1
B1
B1
N
Max distance between P & P2: 5m
P Short
P1 (+)
P2 (+)
N (-)
MCCB (Option) 3â&#x2C6;&#x2026; AC Input 50/60 Hz
R (L1)
U
S (L2)
V
T (L3)
W
Motor
G
Programmable Digital Input: Ext Trip
M1 M2
Max. output voltage: 12V Source max.: 30mA Sink max.: 20mA
S0 S1 5G
Output Frequency Meter Output Voltage Meter Common for output meter signal
M3 M4 M5
3A
M6
3C
M7
3B
Fault Contact Output less than AC250V (DC30V), 1A
M8
Common Terminal
CM
DB resistor terminal B1, B2
TH1, TH2
46
Description Wire terminal properly based on wiring block diagram. Connect a DB resistor to the DB Unitâ&#x20AC;&#x2122; s B1, B2 terminals. Thermal sensor terminal of DB resistor. Normal temperature (Ambient): Contact ON (TH1-TH2 closed) DB resistor overheated: Contact OFF (TH1-TH2 Open). Wire it to the inverter terminal defined as External Trip.
Industrial Inverter for Fan and Pump STARVERT iP5A
DB (Dynamic Braking) Unit Group 1 (Unit: mm)
4-M5 Mounting
Dynamic Braking Unit WIRING U R V S (P2) T W P N
B1 B2
IM
G B2 B1
12.5
POWER
125
172
RUN
12.5
3.5
OHT
192
185
N P
68.5
150
47
iP5A
Group 2 (Unit: mm)
80
Dynamic Braking Unit
RESET 231.5
OHT
258
RUN
245
POWER
12
OCT
5
5.5
15
80 123
27
75
130
48
Industrial Inverter for Fan and Pump STARVERT iP5A
DB (Dynamic Braking) Unit Group 3 (Unit: mm)
49
iP5A
External DB Resistor iP5A do not have built-in DB resistor on power stack as factory installation. External DB Unit and Resistor (Optional) should be installed. See the following table for more details (ED: 5%, Continuous Braking Time: 15 sec). If Enable duty (%ED) is increased to 10%, use external DB resistor having twice Wattage rating. Applied motor capacity (kW/HP)
200V
400V
0.75/1 1.5/2 2.2/3 3.7/5 5.5/7.5 7.5/10 11/15 15/20 18.5/25 22/30 30/40 0.75/1 1.5/2 2.2/3 3.7/5 5.5/7.5 7.5/10 11/15 15/20 18.5/25 22/30 30/40 37/50 45/60 55/75 75/100 90/125
Operating rate (ED/Continuous Braking Time)
[ohm]
[W]
Type
[ohm]
[W]
Type
5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 10%/6 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 5%/15 sec 10%/6 sec 10%/6 sec 10%/6 sec 10%/6 sec 10%/6 sec 10%/6 sec
200 100 60 40 30 20 15 11 9 8 4.2 900 450 300 200 120 90 60 45 35 30 16.9 16.9 11.4 11.4 8.4 8.4
100 200 300 500 700 1000 1400 2000 2400 2800 6400 100 200 300 500 700 1000 1400 2000 2400 2800 6400 6400 9600 9600 12800 12800
TYPE 1 TYPE 1 TYPE 1 TYPE 2 Type3 Type 3 Type 3 Type 3 Type 3 Type 3 TYPE 1 TYPE 1 TYPE 1 TYPE 2 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 -
150 60 50 33 20 15 10 8 5 5 600 300 200 130 85 60 40 30 20 20 -
150 300 400 600 800 1200 2400 2400 3600 3600 150 300 400 600 1000 1200 2000 2400 3600 3600 -
TYPE 1 TYPE 1 TYPE 1 TYPE 2 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 TYPE 1 TYPE 1 TYPE 1 TYPE 2 Type 3 Type 3 Type 3 Type 3 Type 3 Type 3 -
100 % Braking Torque
150% Braking Torque
Peripheral Device MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor) Voltage
200V Class
50
Motor [kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30
Inverter Model SV008iP5A-2 SV015iP5A-2 SV022iP5A-2 SV037iP5A-2 SV055iP5A-2 SV075iP5A-2 SV110iP5A-2 SV150iP5A-2 SV185iP5A-2 SV220iP5A-2 SV300iP5A-2
MCCB (LS Industrial Systems)
MC (LS Industrial Systems)
ABS53b/50A ABS63b/60A ABS103b/100A ABS103b/100A ABS203b/125A ABS203b/150A ABS203b/175A
GMC-40 GMC-40 GMC-50 GMC-85 GMC-100 GMC-100 GMC-150
Industrial Inverter for Fan and Pump STARVERT iP5A
Peripheral Device MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor) Voltage
400V Class
600V Class
Motor [kW]
Inverter Model
MCCB (LS Industrial Systems) -
MC (LS Industrial Systems)
0.75
SV008iP5A-4
-
1.5
SV015iP5A-4
-
-
2.2
SV022iP5A-4
-
-
3.7
SV037iP5A-4
-
-
5.5
SV055iP5A-4
ABS33b/30A
GMC-22
7.5
SV075iP5A-4
ABS33b/30A
GMC-22
11
SV110iP5A-4
ABS53b/50A
GMC-40
15
SV150iP5A-4
ABS63b/60A
GMC-50
18.5
SV185iP5A-4
ABS63b/60A
GMC-50
22
SV220iP5A-4
ABS103b/100A
GMC-65
30
SV300IP5A-4
ABS103b/100A
GMC-75
37
SV370iP5A-4
ABS203b/125A
GMC-100
45
SV450iP5A-4
ABS203b/150A
GMC-125
55
SV550iP5A-4
ABS203b/175A
GMC-150
75
SV750iP5A-4
ABS203b/225A
GMC-180
90
SV900iP5A-4
ABS403b/300A
GMC-220
110
SV1100iP5A-4
ABS403b/400A
GMC-300
132
SV1300iP5A-4
ABS603b/500A
GMC-300
160
SV1600iP5A-4
ABS603b/600A
GMC-400
220
SV2200iP5A-4
ABS803b/700A
GMC-600
280
SV2800iP5A-4
ABS803b/800A
GMC-600
315
SV3150iP5A-4
ABS1003/1000A
GMC-800
375
SV3750iP5A-4
ABS1203/1200A
900A
450
SV4500iP5A-4
ABS1203/1200A
1000A
5.5
SV055iP5A-4
ABS33b/30A
GMC-22
7.5
SV075iP5A-4
ABS33b/30A
GMC-22
11
SV110iP5A-4
ABS53b/50A
GMC-40
15
SV150iP5A-4
ABS63b/60A
GMC-50
18.5
SV185iP5A-4
ABS63b/60A
GMC-50
22
SV220iP5A-4
ABS103b/100A
GMC-65
30
SV300IP5A 4
ABS103b/100A
GMC 75
37
SV370iP5A-4
ABS203b/125A
GMC-100
45
SV450iP5A-4
ABS203b/150A
GMC-125
55
SV550iP5A-4
ABS203b/175A
GMC-150
75
SV750iP5A-4
ABS203b/225A
GMC-180
90
SV900iP5A-4
ABS403b/300A
GMC-220
51
iP5A
AC Input Fuse Voltage
200V Class
400V Class
52
AC Reactor
Motor [kW]
Inverter Model
AC Input Fuse [A]
[mH]
0.75
SV008iP5A-2
10
2.13
1.5
SV015iP5A-2
15
1.2
2.2
SV022iP5A-2
20
3.7
SV037iP5A-2
5.5 7.5
DC Reactor [A]
[mH]
[A]
5.7
-
-
10
-
-
0.88
14
-
-
30
0.56
20
-
-
SV055iP5A-2
40
0.39
30
1.37
29
SV075iP5A-2
60
0.28
40
1.05
38
11
SV110iP5A-2
80
0.20
59
0.74
56
15
SV150iP5A-2
100
0.15
75
0.57
71
18.5
SV185iP5A-2
125
0.12
96
0.49
91
22
SV220iP5A-2
150
0.10
112
0.42
107
30
SV300iP5A-2
200
0.07
160
0.34
152
0.75
SV008iP5A-4
10
8.63
2.8
-
-
1.5
SV015iP5A-4
10
4.81
4.8
-
-
2.2
SV022iP5A-4
10
3.23
7.5
-
-
3.7
SV037iP5A-4
15
2.34
10
-
-
5.5
SV055iP5A-4
20
1.22
15
5.34
14
7.5
SV075iP5A-4
30
1.14
20
4.04
19
11
SV110iP5A-4
40
0.81
30
2.76
29
15
SV150iP5A-4
60
0.61
38
2.18
36
18.5
SV185iP5A-4
70
0.45
50
1.79
48 55
22
SV220iP5A-4
80
0.39
58
1.54
30
SV300IP5A-4
100
0.287
80
1.191
76
37
SV370iP5A-4
125
0.232
98
0.975
93
45
SV450iP5A-4
150
0.195
118
0.886
112
55
SV550iP5A-4
175
0.157
142
0.753
135
75
SV750iP5A-4
250
0.122
196
0.436
187
90
SV900iP5A-4
300
0.096
237
0.352
110
SV1100iP5A-4
350
0.081
289
Built-in
132
SV1300iP5A-4
400
0.069
341
Built-in
160
SV1600iP5A-4
450
0.057
420
Built-in
220
SV2200iP5A-4
700
0.042
558
Built-in
280
SV2800iP5A-4
800
0.029
799
Built-in
315
SV3150iP5A-4
900
0.029
799
0.090
375
SV3750iP5A-4
1000
0.024
952
0.076
996
450
SV4500iP5A-4
1200
0.024
952
0.064
1195
225
836
Industrial Inverter for Fan and Pump STARVERT iP5A
iP5A
MEMO
53
iP5A
MEMO
54
Industrial Inverter for Fan and Pump STARVERT iP5A
53
• For your safety, please read user's manual thoroughly before operating. • Contact the nearest authorized service facility for examination, repair, or adjustment. • Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
• Any maintenance and inspection shall be performed by the personnel having expertise concerned.
ⓒ 2006.8 LSIS Co.,Ltd. All rights reserved.
HEAD OFFICE LS Tower, 127, LS-ro, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea EMEA
+82-2-2034-4901 / bonseongk@lsis.biz
Asia Pacific
+82-2-2034-4620 / mswoo@lsis.biz
Global Network •LSIS (Middle East) FZE
www.lsis.biz
Dubai, U.A.E.
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz
•Dalian LSIS Co., Ltd.
Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
•LSIS (Wuxi) Co., Ltd.
Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
•LSIS-VINA Co., Ltd.
Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com
•LSIS-VINA Co., Ltd.
Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com
•LSIS Shanghai Office
Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
•LSIS Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
•LSIS Guangzhou Office
Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz
•LSIS Chengdu Office
Chengdu, China
Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn
•LSIS Qingdao Office
Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn
•LSIS NETHERLANDS Co.Ltd
Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz