J&C Joel Acoustic Brochure

Page 1

Sage Music Centre, Gateshead

Since the late 1970s, J&C Joel has been supplying wool serges into performing arts spaces. As well as its blackout and masking properties, its durability, and its cost-effectiveness, the acoustic absorption properties have been an acknowledged asset. More recently we started to measure these qualities objectively, using third-party test facilities to reassure our customers that the drapes and banners they are purchasing from J&C Joel are independently verified to meet their performance requirements.

Over the years we have built up an impressive array of acoustic fabrics, including 7 different constructions of serge ranging from 420gsm to 1,000gsm, bonded wool serge, and heavyweight cotton and synthetic velours. As well as acoustic drapery we have developed different ‘banner’ mechanisms, to vertically deploy absorptive surfaces which allow a venue’s acoustic properties to be fine-tuned to suit the characteristics of the performance.

As well as absorption tests to measure the absorption coefficient, we have conducted insulation tests to measure the sound reduction index on multi-layered drapery. Now that we have around 100 test reports, we felt that it was time to compile them into a single document. We hope that this will prove to be a useful reference tool for acousticians, theatre consultants, venue managers, indeed anyone involved in performance spaces.

We have also included some reference guides on testing methodology and the materials being tested. As our range of fabrics and acoustic devices evolves, we intend to continue to add to this document. We welcome any feedback and suggestions on the range of data we are providing you with. After all, this has been created to assist people to understand more about the potential acoustic attributes of our range

www.jcjoel.com The Royal Birmingham Conservatoire, UK
Welcome June 2023

Contents

- Acoustic Test Report Explanation

- Acoustic Banners Absorption Reports

- Acoustic Drapery Absorption Reports

- Acoustic Drapery Insulation Reports

- Basic Acoustics

Acoustic Test Reports Explanation

Test Report No: C/24281/T01

Page 18 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

A collection of our products are tested for their acoustic properties. These tests produce a sound absorption coefficient classification, which helps us to objectively demonstrate their effectiveness and offer you the best product for the space you are wanting to improve. All of our acoustic reports are available for download on the J&C Joel website. All acoustic reports are available for download on the website, alternatively please contact one of our team for technical advice or information.

1 2

3 4

1. Test Conditions

The temperature, humidity and pressure of the room in which the test was conducted

2. Test Results

SAC results table, across the sound frequency spectrum

2a. T1 - reverberation time in an empty room

2b. T2 - reverberation time in a room with the drape

3. SAC Classification (at 1KHz)

The Sound Absorption Coefficient is the fraction of sound energy absorbed by a material expressed as a value between 1.0 (perfect absorption / no reflection) and 0 (zero absorption / total reflection)

4. Noise Reduction Coefficient

Similar to the sound absorption class but using an American test standard, according to ASTMC 423/01.

5. Sound Absorption Coefficient (SAC) Graph displaying results of sound absorbers into sound absorption class A-E, according to BS EN ISO 11654:1997, including frequencies

4
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.4 °C Humidity: 43 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.96 4.75 0.05 63* 5.39 4.91 0.10 n/a 80* 7.08 6.53 0.07 100 9.00 7.17 0.15 125 7.30 5.54 0.24 0.25 160 6.60 4.40 0.41 200 6.86 4.05 0.55 250 7.22 3.91 0.64 0.65 315 6.99 3.50 0.78 400 6.36 3.28 0.81 500 5.64 3.01 0.85 0.85 630 5.09 2.69 0.96 800 5.10 2.62 1.01 1000 5.74 2.77 1.01 1.00 1250 5.63 2.77 0.99 1600 5.18 2.58 1.04 2000 4.76 2.38 1.10 1.00 2500 4.22 2.21 1.11 3150 3.35 1.85 1.21 4000 2.59 1.54 1.26 1.00 5000 2.04 1.23 1.49 6300* 1.39 0.91 1.68 8000* 1.14 0.77 1.77 n/a 10000* 0.80 0.59 1.77 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 19/01/2019 Data Sheet 8 The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 Sample Area: Chamber Volume: Test 9 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Acoustic Molton - Single Layer - 50% fullness (Approx. weight 500g/m2) 350mm cavity from wall Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz Sound Absorption Coefficient 2a 2b
5

Sample Description Explanation

The layout of sample descriptions on acoustic reports:

(Fabric Type - Acoustic Layers - Fullness - (Weight) - Cavity From the Wall)

The ‘Fabric Type’ refers to the fabric that is being acoustically tested for this article.

‘Acoustic layers’ applies to the layers of the fabric examined in the report. For our Motorised Banners reports, multiple acoustic layers can be bonded & pressed to give the fabric, a larger acoustic absorption coefficient.

The ‘Fullness’ of a drape refers to the amount of fabric, used during manufacture to produce a pleated finish.

The ‘Weight’ stated on the reports refers to the approximate weight of the fabric per square meter.

‘Cavity From the Wall’ is the distance between the fabric and the back wall.

Differentiation of G-Value & Cavity From the Wall

Cavity From the Wall - The test specimen is hung parallel to the room surface. The suffix of the mounting type is the distance in millimetres from the back of the test specimen and the wall.

G-Value - The test specimen is hung parallel to the room surface. The suffix of the mounting type is the distance in millimetres from the face of the test specimen and the wall.

Please refer to the diagram below.

Banner Housing Within a Recess

Acoustic Banner Without a Recess Acoustic Banner Within a Recess

5

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Our acoustic testing laboratory experience shows that designs based on actual test data are much more likely to achieve the required performance without being excessively over or under-designed. Laboratory testing is usually completed to show compliance with building regulations, to investigate a problem or as part of the design process.

Our highly trained and experienced engineers perform a wide range of noise, vibration, airflow and rain noise measurements in our laboratory.

The layout of our permanent test facility is flexible. This allows us to accommodate a wide range of products and test set-ups. Samples can be readily installed and tested, which allows our clients to do several tests in a day, a unique and valuable aspect of our service.

Independent Testing

Testing is usually completed to obtain performance data for publications or as the starting point for further design work. We are a UKAS accredited testing laboratory No.0444. Building Control Authorities and Sustainability Assessors prefer that companies doing these tests are independently accredited by this service, and it is an accreditation that enables our clients to minimise their risk, enhance their reputation in the marketplace and save considerable amounts of money.

UKAS Accreditations

Our purpose-built laboratory is accredited for the following test standards:

•BS EN ISO 10140: Parts 1: 2016 – Laboratory Measurement of Sound Insulation of Building Elements (specific elements)

•BS EN ISO 10140: Parts 2: 2010 – Laboratory Measurement of Airborne Sound Insulation of Building Elements

•BS EN ISO 10140: Parts 3: 2010 – Laboratory Measurement of Impact Sound Insulation of Building Elements

•BS EN ISO 10140: Parts 4: 2010 – Laboratory Measurement of Sound Insulation of Building Elements (procedures and requirements)

•BS EN ISO 10140: Parts 5: 2010 – Laboratory Measurement of Sound Insulation of Building Elements (test facilities and equipment)

•BS EN ISO 10848-2:2006 – Ceilings Laboratory Measurement of Flanking Transmission of Airborne Sound between Adjoining Rooms

•BS EN ISO 354:2003 Laboratory Measurement of Sound Absorption Coefficient

•BS EN ISO 140-3:1995 Laboratory Measurement of Airborne Sound Insulation

•BS EN ISO 140-6:1998 Laboratory Measurement of Impact Sound Insulation

•BS EN ISO 140-8:1998 Laboratory Measurement of the Reduction of Transmitted Impact Noise

•BS EN ISO 140-18:2006 Laboratory Measurement of Sound Generated by Rainfall on Building Elements (Roofs)

•BS EN ISO 20140-9:1994 Measurement of Sound Insulation in buildings and building elements (suspended ceilings)

•BS EN ISO 717-1:2013 & BS EN ISO 717-2:2013 Rating of Sound Insulation in Buildings and Building Elements

•BS EN ISO 7235:2009 Laboratory measurement for ducted silencers and air-terminal units. Insertion loss, flow noise and total pressure loss

We are accredited for on-site pre-completion testing to the following standards under UK Building Regulations:

•Building Regulations 2010, Approved Document E (2003 incorporating 2004 & 2010 amendments) Sound Insulation Tests including Pre-completion testing for Dwellings and Rooms for Residential Purpose (RRP)

•BS EN ISO 140-4:1998 Field Measurement of Airborne Sound Insulation between Rooms

•BS EN ISO 140-7:1998 Field Measurement of Impact Sound Insulation of Floors

Our laboratory is also UKAS accredited for testing to the following EU Directives/Regulations:

•European Directive 2000/14/EC and its amendment 2005/88/EC Measurement of Airborne Noise Emitted by Outdoor Machines

•ISO 11094:1991 – Acoustics Test code for the measurement of airborne noise emitted by power lawn mowers, lawn tractors, lawn and garden tractors, professional mowers, and lawn and garden tractors with mowing attachments (including ISO 3744:1994)

6

Test Report No: 24752-SRL-RP-XT-001-P1

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Page 3 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Summary

Tests have been done in SRL's Laboratory at Holbrook House, Sudbury, Suffolk, to determine the random incidence sound absorption coefficient of various types of curtain in accordance with BS EN ISO 354:2003 in all ways apart for the sample areas There were 9m2 where the standard requires a minimum of 10m 2 , therefore these tests are not completely in accordance with the test standard.

From these measurements, the required results have been derived and are presented in both tabular and graphic form in Data Sheets 1 to 9.

The results are given in 1/3rd octave bands over the frequency range 50Hz to 10kHz, which is beyond that required by the test standard.

SRL Technical Services Limited

Tel: 01787 247595

Email: rcalvert@srltsl.com

Template Ref: Lab Edition 3 – 14/10/2019

7

Test Report No: 24752-SRL-RP-XT-001-P1

Page 7 of 23

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

2.0 Description of Test

2.1 Description of Sample

Tests were performed on various curtains which were hung parallel to the wall in the test chamber. The samples were mounted on a test frame simulating the final install conditions. Airspaces of 100mm, 190mm, 200mm, 260mm, 350mm and 450mm between the face of the curtain and the wall were tested The curtains measured 3m high by 3m wide and were suspended on a st eel pole frame system giving an area of 9m2.

Please note – The area of each test sample was below the minimum 10m2 required by the test standard and tests therefore do not completely comply with the test standard. All other elements of the tests are in accordance with the standard.

Mounting Method: G-100, G-190, G-200, G-260, G-350 and G-450

Sampling plan: Taken from top of pile.

Sample condition: New

Details supplied by: J & C Joel Ltd

Sample installed by: J & C Joel Ltd

2.2 Sample Delivery Date

15 October 2020

2.3 Test Procedures

The sample was mounted/located and tested in accordance with the relevant standard. The method and procedure are described in Appendix A. The measurement uncertainty is given in Appendix B. The method of mounting samples is given in Appendix C.

Template Ref: Lab Edition 3 – 14/10/2019

8

Test Report No: 24752-SRL-RP-XT-001-P1

Page 18 of 23

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Appendix A - Test Procedure

Measurements of Random Incidence Sound Absorption

Coefficients Generally to BS EN ISO 354:2003 - TP14 (Plane Absorbers)

In the laboratory, random incidence sound absorption coefficients are determined from the rate of decay of a sound field in a reverberation room, with and without a test sample installed. The rate of decay is described by the time a sound field takes to d ecay by 60dB, known as the reverberation time.

The reverberation room is constructed from 215mm brick, which is internally plastered with a reinforced concrete roof and floor. The reverberation room is rectangular, measuring 8.3 metres long, 6.7 metres wide and 5.4 metres high. The volume is 300m3, the total surface area, 275m2. From the ceiling hang 10 randomly positioned diffusers, with a total surface area (for one side) of 20m 2. The room is isolated from the surrounding structure by the use of resilient mountings and seals, ensuring good acoustic isolation.

Using at least two omnidirectional loudspeaker positions, broad band random noise is produced in the room using an electronic generator and power amplifier. When the amplification system is switched off, the decay of sound is filtered into one-third octave band widths and the reverberation times measured. This process is repeated for each of six microphone positions and the values arithmetically averaged to obtain a final value for each frequency.

The sample area should normally be between 10m 2 and 15.7m2. This may be larger if it is suspected that the absorption properties will be low. The sample in this instance has an area of 9m 2 and therefore tests are described as generally in accordance with the test standard. The sample is suspended from a pre -assembled rig positioned on the floor of the reverberation room close to one wall. The test rig provides a space between the sample and wall, the depth of which can be varied to simulate speci fic requirements. The procedure of measuring the reverberation times then repeated.

The sound absorption coefficients are calculated from the difference in decay rates for each frequency according to the formula:

s = AT S where

s is the random incidence absorption coefficient

AT is the increase in equivalent sound absorption area of the test specimen (m 2)

S is the area covered by the test specimen (m 2)

Template Ref: Lab Edition 3 – 14/10/2019

9

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

The equivalent absorption area of the test specimen is further defined as:

AT =55.3V ( 1 c2 T21 c1 T1 ) -4V(m2 -m1 ) where

Test Report No: 24752-SRL-RP-XT-001-P1

Test Report No: 24752-SRL-RP-XT-001-P1

Page 20 of 23

V is the volume of the empty reverberation room (m 3)

c1 is the speed of sound in the empty room (m/sec)

Date: 12/11/2020

Test Report No: 24752-SRL-RP-XT-001-P1

Page 20 of 23

T1 is the reverberation time in the empty room (sec)

Date: 12/11/2020

Page 20 of 23

Test Report No: 24752-SRL-RP-XT-001-P1

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

m1 is the power attenuation coefficient calculated according to ISO 9613 -1 using the climatic conditions that have been present in the empty room during the measurement.

Appendix B - Measurement Uncertainty

Date: 12/11/2020

Page 20 of 23

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Date: 12/11/2020

c2 , T2 and m2 have the same meanings as c1 , T1 and m1 but with the test specimen in the room.

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

It is occasionally found that the absorption coefficient derived in this manner reaches a value greater than unity. This is impossible, by definition, and investigation has shown that this anomaly is due to diffrac tion of the impinging sound waves at the edges of the sample. In practical terms this is insignificant.

Appendix

Appendix B - Measurement

BS EN ISO 354:2003 - TP14

Appendix B - Measurement Uncertainty

BS EN ISO 354:2003 - TP14

1. Introduction

BS EN ISO 354:2003 - TP14

BS EN ISO 354:2003 - TP14

1. Introduction

The estimated values of uncertainty are based on a standard uncertainty multiplied by a coverage factor of K = 2, which provides a level of confidence of approximately 95%.

1. Introduction

The estimated values of uncertainty are based on a standard uncertainty multiplied by a coverage factor of K = 2, which provides a level of confidence of approximately 95%. Table

1: Uncertainty For Equivalent Absorption Area Measurement

The estimated values of uncertainty are based on a standard uncertainty multiplied by a coverage factor of K = 2, which provides a level of confidence of approximately 95%.

The estimated values of uncertainty are based on a standard uncertainty multiplied by a coverage factor of K = 2, which provides a level of confidence of approximately 95%. Table

Template Ref: Lab Edition 3 – 14/10/2019

10 except in full, without written approval of SRL Technical Services Limited
Table 1: Uncertainty
Equivalent Absorption Area Measurement Frequency, Hz Expanded uncertainty K = 2, 95% % of A1 or A2 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 9.0 8.1 5.6 6.7 4.3 8.1 4.6 5.0 5.3 3.2 3.5 3.1 2.8 2.7 2.2 1.8 1.6
For
Uncertainty
Uncertainty
Frequency, Hz Expanded uncertainty K
% of
A2 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 9.0 8.1 5.6 6.7 4.3 8.1 4.6 5.0 5.3 3.2 3.5 3.1 2.8 2.7 2.2 1.8 1.6 1.6
1:
For Equivalent Absorption Area Measurement
= 2, 95%
A1 or
B - Measurement Uncertainty 1. Introduction
Frequency, Hz Expanded uncertainty K = 2, 95% % of A1 or A2 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 9.0 8.1 5.6 6.7 4.3 8.1 4.6 5.0 5.3 3.2 3.5 3.1 2.8 2.7 2.2 1.8 1.6 1.6
Table 1: Uncertainty For Equivalent Absorption Area Measurement
Frequency, Hz Expanded uncertainty K = 2, 95% % of A1 or A2 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 9.0 8.1 5.6 6.7 4.3 8.1 4.6 5.0 5.3 3.2 3.5 3.1 2.8 2.7 2.2 1.8 1.6 1.6

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

2. Estimation of Expanded Uncertainty For Sample Equivalent Sound Absorption Area

The expanded uncertainty, UA,m2 is estimated by using the following formulae:-

UA is the expanded uncertainty for the sample equivalent sound absorption area, for K = 2, 95%, m2

u is the estimated expanded uncertainty for the equivalent sound absorption area, taken from Table 1 above, K = 2, 95%, % of A1 or A2

A1 is the equivalent sound absorption area of the empty room, m 2

A2 is the equivalent sound absorption area of the room with the sample, m 2

3. Estimation of expanded Uncertainty For Sound Absorption Coefficients

The expanded uncertainty for sound absorption coefficients, Us , is estimated using the following formulae:-

Test Report No: 24752-SRL-RP-XT-001-P1

Page 22 of 23

Us is the expanded uncertainty for sound absorption coefficients, K=2, 95%

s is the sound absorption coefficient

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

UA is the expanded uncertainty for the sample equivalent sound absorption area, K=2, 95%, m2

A is the sample equivalent sound absorption area, m 2

Appendix C - Mounting Methods

Description of Test Specimen Mountings for Sound Absorption Tests

BS EN ISO 354:2003 describes various test specimen mountings. The methods of mounting used for these tests is briefly described as follows:

Template Ref: Lab Edition 3 – 14/10/2019

Type G Mounting

The test specimen, such as a curtain, is hung parallel to the room surface. The suffix of the mounting type (e.g. Type G-100) is the distance in mm from the room side outer face of the test specimen and room surface.

11 except in full, without written approval of SRL Technical Services Limited
UA =√(uA1 100 )2 + (uA2 100 )2
where
Us = s UA A where
12
from SRL
Procedure - 3rd Party Accredited Laboratory Confidential P:\C22000s - Tech Services\C22800\22807 - J&C Joel\SRL Corr Out\22807 - T07.docx ©SRL Technical Services Limited 8 December 2014 C/22807/T07 Page 12 of 17
Extract
Testing
1
Photograph

Showcase

SRL Acoustic Testing Site, Sudbury, UK 13

Acoustic Banners Absorption Reports

Single Layer Banner Page 20

Product

Double Layer Banner

Concertina Banner 42 28

Frequency Comparison Chart

16 Banner Type Pressed Coloured Wool Serge (100mm Cavity Between Material) 100mm Concertina Banner System 0.25 Concertina Banner System Pressed Wool Serge 800 350mm 0.35 Concertina Banner System Pressed Wool Serge 800 100mm 0.35 Pressed Tay Wool Serge - Enclosed (150mm Cavity Between Material) 350mm Concertina Banner System 0.75 Pressed Tay Wool Serge (150mm Cavity Between Material) Concertina Banner System 350mm 0.50 Pressed Tay Wool Serge - Enclosed (150mm Cavity Between Material) 100mm Concertina Banner System 0.75 Concertina Banner System 100mm Pressed Tay Wool Serge (150mm Cavity Between Material) 0.50 Pressed Tay Wool Serge - Enclosed (100mm Cavity Between Material) 350mm Concertina Banner System 0.65 Concertina Banner System 350mm Pressed Tay Wool Serge (100mm Cavity Between Material) 0.50 Pressed Tay Wool Serge - Enclosed (100mm Cavity Between Material) 100mm Concertina Banner System 0.75 Concertina Banner System 100mm Pressed Tay Wool Serge (100mm Cavity Between Material) 0.40 Pressed Wool Serge 565 (100mm Cavity Between Material) 350mm Concertina Banner System 0.35 Pressed Wool Serge 565 (100mm Cavity Between Material) 160mm Concertina Banner System 0.30 Pressed Wool Serge 565 (100mm Cavity Between Material) 100mm Concertina Banner System 0.25 Pressed Coloured Wool Serge (100mm Cavity Between Material) 350mm Concertina Banner System 0.35 Fabric Distance 125Hz Double Layer Banner System Bonded Coloured Wool Serge (100mm Cavity Between Material) Bonded Coloured Wool Serge (100mm Cavity Between Material) 100mm 350mm Double Layer Banner System Bonded Coloured Wool Serge - Enclosed Bonded Coloured Wool Serge - Enclosed 100mm 350mm Bonded Wool Serge 565 Bonded Wool Serge 565 Bonded Wool Serge 565 100mm 150mm 350mm Bonded Wool Serge 565 - Enclosed Bonded Wool Serge 565 - Enclosed 100mm 350mm Bonded Wool Serge 565 & Printed Theatre Canvas Bonded Wool Serge 565 & Printed Theatre Canvas - Enclosed 150mm 350mm Double Layer Banner System Double Layer Banner System Double Layer Banner System Double Layer Banner System Double Layer Banner System Double Layer Banner System Double Layer Banner System Double Layer Banner System Double Layer Banner System 0.30 0.30 0.40 0.35 0.30 0.30 0.40 0.40 0.35 0.70 0.30 0.10 0.30 0.25 0.25 Single Layer Banner System 0.10 0.25 Bonded Wool Serge 420 100mm Single Layer Banner System Bonded Wool Serge 420 350mm Single Layer Banner System Single Layer Banner System Single Layer Banner System Single Layer Banner System Bonded Wool Serge 565 100mm Bonded Wool Serge 565 150mm Bonded Wool Serge 565 350mm Bonded Coloured Wool Serge 150mm
17 0.60 1.00 1.00 0.95 1.00 0.65 1.00 1.00 1.00 1.00 0.65 1.00 1.00 1.00 1.00 0.95 1.00 1.00 1.00 1.00 0.80 1.00 1.00 1.00 1.00 0.95 1.00 0.90 0.90 0.95 0.80 1.00 0.95 0.95 1.00 0.85 1.00 1.00 0.95 0.95 0.70 1.00 1.00 1.00 1.00 0.90 1.00 0.95 0.85 0.90 0.80 1.00 1.00 0.90 0.95 0.60 0.95 1.00 1.00 1.00 0.65 1.00 1.00 1.00 1.00 0.60 1.00 1.00 1.00 1.00 0.65 0.95 1.00 1.00 1.00 250Hz 500Hz 2000Hz 1000Hz 4000Hz 0.50 0.80 0.90 0.80 0.90 0.50 0.90 1.00 0.95 1.00 0.85 1.00 0.95 0.85 0.85 0.85 1.00 1.00 1.00 1.00 0.70 1.00 1.00 1.00 1.00 0.65 0.95 1.00 1.00 1.00 0.70 1.00 1.00 1.00 1.00 0.75 0.95 0.85 0.85 0.85 0.80 1.00 1.00 1.00 1.00 0.80 0.90 0.85 0.95 0.95 0.75 1.00 1.00 1.00 1.00 0.40 0.75 0.90 0.80 0.95 0.85 0.95 0.80 0.75 0.75 0.65 0.75 0.85 0.85 1.00 0.85 0.95 0.85 0.80 0.85 0.40 0.75 0.85 0.75 0.85 0.65 0.70 0.80 0.80 0.95

Fabrics Used In Banners

Bonded Wool Serge 420

Two layers of our Wool Serge 420, bonded together for a more stable structure.

1

Bonded Coloured Wool Serge

Two layers of our Coloured Wool Serge, bonded together for a more stable structure.

Bonded Wool Serge 565

Two layers of our Wool Serge 565, bonded together for a more stable structure

1

18
Width: 150cm /59” FR Certification: BS5867 Weight: 840 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft Colour Available FR Rating: IFR
Black
Acoustic Width: 150cm /59” FR Certification: BS5867, NFPA 701, IMO, AS1530.2/3 Weight: 1130 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft Colour Available FR Rating: IFR
Black
Acoustic Original Grey Width: 150cm / 59” Fire Certification: BS5867, IMO Weight: 1000 g/m2 Custom Dye Available* Approx Roll Length: 57m / 187ft Colours Available Fire Rating: IFR 18 Plum Scarlet Ultra Blue Cognac Gold Mole Midnight Slate Natural Bottle Oxford Emerald Marine TV Blue *CUSTOM DYE price on application, 4 wk lead time *BONDING 3 wk lead time *DYE & BOND 7 wk lead time Chroma Key Blue Chroma Key Green Black
Acoustic Width: 500cm / 197” Fire Certification: BS5867, B1 Weight: 340 g/m2 Customised Digital Print Approx Roll Length: 30m / 98ft Customised Digital Print Fire Rating: NDFR + Printed Theatre Canvas CUSTOM

Fabrics Used In Banners

Pressed Tay Wool Serge

Our Tay Wool Serge, with a pressed finish, suitable for use on our concertina banners

2

Pressed Wool Serge 800

Our Wool Serge 800, with a pressed finish, suitable for use on our concertina banners

1

Black

19 Width: 150cm /59” FR Certification: BS5867 Weight: 800 g/m2 Custom Dye N/A Approx Roll Length: 38m / 125ft Colour Available FR Rating: IFR
Acoustic Blackout
J&C Joel Concertina Banner System in Testing Width: 300cm /118” FR Certification: BS5867, M1, B1 Weight: 500 g/m2 Custom Dye N/A Approx Bale Length: 30m / 98ft Colours Available FR Rating: NDFR
Black 150cm /59” FR Certification: BS5867 g/m Approx Roll Length: IFR Warm White Custom Dye Available*
Acoustic *CUSTOM DYE price on application, 4 wk lead time, MOQ 4 rolls

Single Layer Banner

Cadenza (Single Layer Banner)

The Cadenza Acoustic Banner is a budget-friendly option within the J&C Joel variable acoustic range. Deploying a single layer of Bonded Wool Serge it achieves a Class B acoustic absorption rating according to EN ISO 11654:1997.

The Cadenza can offer an absorbent area of up to 48m2. With 6m as the maximum width, and 10m as the maximum drop. Custom sizes are available on request.

Works with Bonded Wool Serge*, available in 1,130gsm, 1000gsm, or 840gsm to achieve different acoustic requirements. The standard fabric colour is black, with a range of 10 colours available on 1,000gsm, custom colours available subject to MOQ. *100% recycled wool product. Other fabrics are available for acoustic or decorative purposes.

The standard operating speed is around 140mm/s which enables a 5m tall banner to deploy in 35s.

Designed and Manufactured in the UK.

Features

• Tubular Motor (typically Becker)

• End of Travel & Ultimate Limit Switches

• Standard power requirement of 230v 13A power supply per banner location.

Control Option One

• Uses the JCJ Conductor Control System, enables advanced control over a number of options using a tablet interface.

• Requires a 300x300 enclosure for electronics. Can be mounted on the unit (shown below) or the wall.

• Allows preset positions, individual and group control of up to 100 banners, with movement based on meterage or percentage of travel.

• Absolute Encoder (optional extra, shown below)

• Secondary Brake (optional extra, shown below)

• E-Stops compliant with ISO 13850 & can interface with other stage engineering packages through a global e-stop system.

• Can integrate into a building management system.

Installation

• Mounting brackets provide a simple wall or ceiling fix. The same part is used for both scenarios. Once the brackets are fixed, the banner slots into place and is fixed with a bolt.

• J&C Joel can provide full installation services or supply mechanical and electrical drawings to aid your installation.

Control Option Two

• Uses the motor manufacturer’s propriety software, allows control of upto 100 units from a mobile device

• Can be integrated into a building management system (BMS).

• Control via radio frequency, with the motors providing positional feedback to the control and signal amplification

• Application allows multiple pre-set positions for banners based on percentage of deployment.

20

Technical Data

For use with Tay Wool Serge & Pressed Wool Serge, please see page 19.

21
Class B EN ISO 11654:1997 (SAC) Single Phase 240v NRC 0.75 ASTM C 423-01 (SAC) Drop up to 10m Width up to 6m 48m2 Absorbent Surface
Contents
Wall Cavity Class SAC Classification Page 150mm 100mm 350mm 100mm C B C B 0.80 0.70 0.80 0.70 Fabric
Wool Serge 565 Bonded Wool Serge 565
Wool Serge 420 Bonded Wool Serge 420 22 23 24 25 26 27 350mm B 0.85 Bonded Wool Serge 565 Bonded Coloured Wool Serge 150mm B 0.85 Fabric Fabric-Wall Distance mm Acoustic Absorption Co-efficient 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz Bonded Wool Serge 1130 gsm 100 0.10 0.40 0.75 0.90 0.80 0.95 150 0.26 0.90 0.98 0.81 0.77 0.79 350 0.25 0.65 0.75 0.85 0.85 1.00 Bonded Wool Serge 840 gsm 100 0.10 0.40 0.75 0.85 0.75 0.85 350 0.25 0.65 0.70 0.80 0.80 0.95 Bonded Coloured Wool Serge 1000 gsm 150 0.22 0.91 0.98 0.88 0.75 0.85
Bonded
Bonded

Acoustic Test Report - Absorption

Fabric:

Bonded Wool Serge 420

Fullness: Single Layer Banner System Cavity from Wall: 100mm

Data Sheet 1

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 12/04/2014

Empty Room:

Sample D escription: Single Roller Banner System - Bonded Wool Serge 420 (Approx. weight 840g/m² made up of 2 bonded layers of 420g/m² fabric) – 100mm cavity from wall

Single Layer Banner System - Bonded Wool Serge 420 (Approx. Weight 840g/m² Made up of 2 Bonded Layers of 420g/m² Fabric) - 100mm Cavity From Wall

Mounting Method: G-100

Area: 9 m2

Volume: 300 m3 Test



423-01

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

www.jcjoel.com 22 Confidential
Humidity:
Humidity:
Temperature: 17.0 °C
57 %RH Pressure: 1010mbar Room with Sample: Temperature: 16.9 °C
54 %RH Pressure: 1010mbar
2 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.075.15-0.02 63*4.604.580.01n/a 80*5.865.540.05 100 6.966.220.09 125 7.226.700.060.10 160 6.825.570.18 200 6.375.250.18 250 7.194.570.430.40 315 7.064.180.53 400 6.403.500.70 500 5.353.020.780.75 630 5.032.870.81 800 5.432.900.87 1000 5.963.020.880.85 1250 5.703.080.81 1600 5.083.020.72 2000 4.622.830.730.75 2500 4.172.570.79 3150 3.502.280.80 4000 2.851.950.830.85 5000 2.251.580.94 6300*1.661.240.98 8000*1.381.061.00n/a 10000*0.930.751.13
Sample
Chamber
0.70(H) Class C Calculated to EN ISO 11654:1997 NRC 0.70 Calculated to ASTM C
T1,
T2, room reverberation
with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
empty room reverberation time
time
Calculated to EN ISO 11654:1997
Absorption Class: C

Acoustic Test Report - Absorption

Absorption Class: B

Fabric:

Bonded Wool Serge 420

Fullness: Single Layer Banner System Cavity from Wall: 350mm

Data Sheet 2

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 12/04/2014

Sample D escription: Single Roller Banner System - Bonded Wool Serge 420 (Approx. weight 840g/m² made up of 2 bonded layers of 420g/m² fabric) – 350mm cavity from wall

Single Layer Banner System - Bonded Wool Serge 420 (Approx. Weight 840g/m² Made up of 2 Bonded Layers of 420g/m² Fabric) - 350mm Cavity From Wall

Mounting Method: G-350

Area: 9 m2

Volume: 300 m3

Test

C 423-01

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

23 www.jcjoel.com Confidential
Humidity:
Humidity:
Empty Room: Temperature: 17.0 °C
57 %RH Pressure: 1010mbar Room with Sample: Temperature: 16.9 °C
54 %RH Pressure: 1010mbar
Sample
Chamber
3 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.074.760.07 63*4.603.850.23n/a 80*5.865.000.16 100 6.965.260.25 125 7.225.930.160.25 160 6.824.790.34 200 6.373.990.51 250 7.193.910.630.65 315 7.063.580.74 400 6.403.500.70 500 5.353.220.670.70 630 5.033.020.72 800 5.433.040.78 1000 5.963.140.810.80 1250 5.703.100.79 1600 5.082.960.76 2000 4.622.750.790.80 2500 4.172.520.83 3150 3.502.190.89 4000 2.851.900.900.95 5000 2.251.531.05 6300*1.661.181.20 8000*1.381.031.15n/a 10000*0.930.751.13
Class B Calculated to EN ISO 11654:1997 NRC 0.75 Calculated to ASTM
 0.80(H)
T2, room reverberation
# Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
T1, empty room reverberation time
time with sample
Calculated to EN ISO
11654:1997

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric:

Bonded Wool Serge 565

Confidential

Fullness: Single Layer Banner System Cavity from Wall: 100mm

Data Sheet 1

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description: Single Roller Banner System - Bonded Wool Serge 565 (Approx. weight 1,130g/m² made up of 2 bonded layers of 565g/m² fabric) – 100mm cavity from wall

Single Layer Banner System - Bonded Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Bonded Layers of 565g/m² Fabric) - 100mm Cavity From Wall

Sound

www.jcjoel.com 24
Test
Empty Room: Temperature: 17.0 °C Humidity: 57 %RH Pressure: 1010 mbar Room with Sample: Temperature: 16.8 °C Humidity: 52 %RH Pressure: 1010 mbar
Mounting
G-
Sample
9
Chamber Volume: 300 m3 Test 6 Absorp Practical Freq T1 T2 Coeff Absorp Hz sec sec Coeff # 50* 5.075.19-0.02 63* 4.604.560.01n/a 80* 5.865.550.05 100 6.966.740.02 125 7.226.830.040.10 160 6.825.500.19 200 6.375.020.23 250 7.194.610.420.40 315 7.064.270.50 400 6.403.630.65 500 5.353.090.740.75 630 5.032.830.84 800 5.432.840.91 1000 5.962.910.950.90 1250 5.702.930.89 1600 5.082.890.80 2000 4.622.810.740.80 2500 4.172.490.84 3150 3.502.220.84 4000 2.851.870.910.95 5000 2.251.511.04 6300* 1.661.171.15 8000* 1.381.001.17n/a 10000* 0.930.731.14 
Class
Calculated
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient
Client: J&C Joel Ltd
Date: 12/04/2014
Method:
100
Area:
m2
0.70(H)
C Calculated to EN ISO 11654:1997 NRC 0.70
to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003
Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric:

Bonded Wool Serge 565

Fullness: Single Layer Banner System Cavity from Wall: 150mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 13 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

25
www.jcjoel.com

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric:

Bonded Wool Serge 565

Fullness: Single Layer Banner System Cavity from Wall: 350mm

Data Sheets 1 and 2

Area: 08/03/2019

Test Report No: 24281-SRL-RP-XT-004-P1

Supersedes C/24281/T03

Page 9 of 16

Date: 02/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

- 350 Sample Description: Absorp Coeff α s

Volume:

9

Single Roller Banner System – Bonded Wool Serge 565 (Approx. weight 1,130g/m2 made up of 2 bonded layers of 565g/m2 fabric) – 350mm cavity from wall T1 sec T2 sec Freq Hz

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

www.jcjoel.com 26
Template Ref: Lab Edition 3 – 14/10/2019
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 55 %RH Pressure: 1004 mbar 15.8 °C Humidity: 50 %RH Pressure: 1003 mbar 9m² 300 m³ Practical Absorp Coeff # 50* 4.904.480.10 63* 5.234.960.06n/a 80* 6.956.360.07 100 7.636.090.18 125 7.105.690.190.25 160 6.604.560.37 200 6.854.120.52 250 7.103.690.700.65 315 6.873.630.70 400 6.653.360.80 500 5.643.220.720.75 630 4.962.900.78 800 5.192.890.83 1000 5.673.000.850.85 1250 5.642.980.85 1600 5.322.900.84 2000 4.862.710.860.85 2500 4.142.450.87 3150 3.412.080.96 4000 2.751.790.971.00 5000 2.141.471.01 6300* 1.461.071.14 8000* 1.180.901.12n/a 10000* 0.830.671.13 0.85(H) Calculated to EN ISO 11654:1997 0.80 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC
Temperature:
Empty Room:
Room with Sample: Temperature:
G
Sample
Chamber
Test
Mounting Method: Class B
Data Sheet 1
Absorption Coefficient
The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003
Sound
Single Layer Banner System - Bonded Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Bonded Layers of 565g/m² Fabric) - 350mm Cavity From Wall

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Bonded Coloured Wool Serge

Fullness: Single Layer Banner System Cavity from Wall: 150mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 14 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

27
www.jcjoel.com

Double Layer Banner

Duet (Variable Layer Banner)

The Duet Acoustic Banner is the mid-tier of the J&C Joel variable acoustic range. Deploying two layers of Bonded Wool Serge it achieves a A acoustic absorption rating according to EN ISO 11654:1997.

The Duet can offer an absorbent area of up to 48m2. With 6m as the maximum width, and 10m as the maximum drop. Custom sizes are available on request.

Works with Bonded Wool Serge*, available in 1,130gsm, 1000gsm, or 840gsm to achieve different acoustic requirements. Standard fabric colour is black, with a range 10 colours available on 1,000gsm, custom colours available subject to MoQ. *100% recycled wool product. Other fabrics are available for acoustic or decorative purposes.

Standard operating speed is around 140mm/s which enables a 5m tall banner to deploy in 35s.

Designed and Manufactured in the UK.

*For use with Bonded Wool Serge, please see page 190.

28
Class A EN ISO 11654:1997 (SAC) Single Phase 240v NRC 1.00 ASTM C 423-01 (SAC) Drop up to 10m Width up to 6m 48m2 Absorbent Surface

Legato (Double Layer Banner)

The Legato Acoustic Banner is a budget-friendly option within the J&C Joel variable acoustic range. Deploying two layers of Bonded Wool Serge it achieves an EN ISO 11654:1997 Class A acoustic absorption rating.

The Legato can offer an absorbent area of up to 30m2 of double layered absorbent fabric. With 6m as the maximum width, and 5m as the maximum drop. Custom sizes are available on request. Works with Bonded Wool Serge*, available in 1,130gsm, 1000gsm, or 840gsm to achieve different acoustic requirements. Standard fabric colour is black, with a range 10 colours available on 1,000gsm, custom colours available subject to MOQ. *100% recycled wool product. Other fabrics available for acoustic & decorative purposes. Standard operating speed is around 80mm/s which enables a 5m tall banner to deploy in 60s.

Designed and Manufactured in the UK.

Bonded Coloured Wool Serge

Bonded Wool Serge 565

(100mm Cavity Between Material)

Bonded Wool Serge 565

(150mm Cavity Between Material)

Bonded Wool Serge 565

(100mm Cavity Between Material)

29
Wall Cavity Class SAC Classification Page 100mm 0.80 Fabric Bonded Coloured Wool Serge 30 Bonded & Theatre Canvas Contents 31 32 33 34 35 36 0.80 1.00 0.95 1.00 1.00 0.90 B B A A A A A 350mm 100mm 150mm 350mm 350mm 150mm
Bonded & Theatre Canvas
Class A EN ISO 11654:1997 (SAC) Single Phase 240v NRC 0.90 ASTM C 423-01 (SAC) Drop up to 5m Width up to 6m 30m2 Absorbent Surface 37 38 39 40 Bonded Coloured Wool Serge Bonded Coloured Wool Serge 0.95 1.00 A A 100mm 350mm Bonded Wool Serge 565 Bonded Wool Serge 565 0.90 1.00 A A 100mm 350mm

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric:

Bonded Coloured Wool Serge

Fullness: Double Layer Banner System Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 14 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description: Sample Area:

Roller Banner System (100mm Cavity Between Material) - Bonded Coloured Wool Serge (Approx Weight 1000g/m² Made up of 2 Bonded Layers of 500g/m² Fabric) - 100mm Cavity From Wall

Double Layer Banner System (100mm Cavity Between Material) - Bonded Coloured Wool Serge (Approx. Weight 1000g/m² Made up of 2 Bonded Layers of 500g/m² Fabric) - 100mm Cavity From Wall

www.jcjoel.com 30
Template Ref: Lab Edition 3 – 14/10/2019 DS5 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.8 °C Humidity: 56 %RH Pressure: 1015 mbar G - 200 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.77 0.08 63* 4.83 4.79 0.01 n/a 80* 7.33 6.36 0.11 100 7.42 5.88 0.19 125 7.17 5.20 0.29 0.30 160 6.75 4.67 0.36 200 6.77 4.61 0.38 250 6.80 4.05 0.54 0.50 315 6.65 3.70 0.65 400 6.46 3.35 0.78 500 5.63 3.08 0.80 0.80 630 5.00 2.77 0.88 800 5.22 2.77 0.92 1000 5.79 2.89 0.94 0.90 1250 5.75 3.03 0.85 1600 5.33 3.02 0.78 2000 4.93 2.83 0.81 0.80 2500 4.35 2.60 0.83 3150 3.55 2.27 0.84 4000 2.92 1.94 0.90 0.90 5000 2.34 1.62 0.97 6300* 1.60 1.23 0.92 8000* 1.30 1.01 1.06 n/a 10000* 0.93 0.76 1.11 0.80 Calculated to EN ISO 11654:1997 0.75 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Double
Method:
Chamber
Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Volume:
5
B
Data Sheet 5
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric:

Bonded Coloured Wool Serge

Fullness: Double Layer Banner System Cavity from Wall: 350mm

Page 15 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Roller Banner System (100mm Cavity Between Material) - Bonded Coloured Wool Serge (Approx Weight

Double Layer Banner System (100mm Cavity Between Material) - Bonded Coloured Wool Serge (Approx. Weight 1000g/m² Made up of 2 Bonded Layers of 500g/m² Fabric) - 350mm Cavity From Wall

Made up of 2 Bonded Layers of 500g/m² Fabric) - 350mm Cavity From Wall

Sound Absorption Coefficient

www.jcjoel.com 31
Test Report No: 24766-SRL-RP-XT-001-P1
Template Ref: Lab Edition 3 – 14/10/2019 DS6
C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1015 mbar G - 450 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.95 0.04 63* 4.83 4.70 0.03 n/a 80* 7.33 5.90 0.18 100 7.42 6.10 0.16 125 7.17 4.87 0.36 0.30 160 6.75 4.46 0.41 200 6.77 4.67 0.36 250 6.80 4.12 0.52 0.50 315 6.65 3.60 0.69 400 6.46 3.22 0.85 500 5.63 2.90 0.91 0.90 630 5.00 2.61 1.00 800 5.22 2.62 1.03 1000 5.79 2.80 1.00 1.00 1250 5.75 2.77 1.01 1600 5.33 2.76 0.95 2000 4.93 2.61 0.97 0.95 2500 4.35 2.45 0.95 3150 3.55 2.12 1.01 4000 2.92 1.85 1.03 1.00 5000 2.34 1.54 1.14 6300* 1.60 1.19 1.06 8000* 1.30 0.98 1.21 n/a 10000* 0.93 0.73 1.38 0.80(H) Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room
Temperature: Mounting
Double
Sample
Sample
Chamber
Test
Class B T1 sec T2 sec Freq Hz Absorp Coeff α s
Client: J &
with Sample:
Method:
1000g/m²
Description:
Area:
Volume:
6
30/11/2020 Data Sheet 6
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Bonded Coloured Wool Serge - Enclosed

Fullness: Double Layer Banner System

Cavity from Wall: 100mm

www.jcjoel.com 32 Test Report No: 80161-SRL-RP-XT-001-P1 Page 15 of 32

Test Report No: 80161-SRL-RP-XT-001-P1

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Bonded Coloured Wool Serge - Enclosed

Fullness: Double Layer Banner System

Cavity from Wall: 350mm

www.jcjoel.com 33
Page 16 of 32
SRL Technical Services Limited

Acoustic Test Report - Absorption

Absorption Class: A Calculated to EN ISO 11654:1997

Fabric:

Bonded Wool Serge 565

Fullness: Double Layer Banner System Cavity from Wall: 100mm

Test Report No: 24752-SRL-RP-XT-001-P1

Page 15 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 7

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

with Sample:

Sample Description:

Method:

Double Layer Banner System (100mm Cavity Between Material) - Bonded Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Bonded Layers of 565g/m² Fabric) - 100mm Cavity From Wall

Double Roller Banner System (100mm Cavity Between Material) - Bonded Wool Serge 565 (Approx Weight 1130g/² Made up of 2 Bonded Layers of 565g/m² Fabric) - 100mm Cavity From Wall

Sound Absorption Coefficient

34
www.jcjoel.com
Template Ref: Lab Edition 3 – 14/10/2019 DS7 Client: J & C Joel Ltd Test Date: 16.1 °C Humidity: 63 %RH Pressure: 1016 mbar 15.7 °C Humidity: 59 %RH Pressure: 1016 mbar G - 200 9 m² 300 m³ Practical Absorp Coeff # 50* 5.09 4.49 0.14 63* 4.76 4.57 0.05 n/a 80* 7.42 6.56 0.10 100 7.54 6.62 0.10 125 6.85 4.73 0.35 0.30 160 6.65 4.19 0.48 200 7.05 4.17 0.53 250 6.89 3.65 0.70 0.70 315 6.51 3.10 0.92 400 6.32 2.94 0.99 500 5.53 2.73 1.01 1.00 630 4.91 2.44 1.12 800 5.18 2.53 1.10 1000 5.65 2.60 1.13 1.00 1250 5.60 2.67 1.06 1600 5.16 2.64 1.00 2000 4.76 2.46 1.05 1.00 2500 4.28 2.30 1.07 3150 3.59 2.03 1.12 4000 2.91 1.76 1.15 1.00 5000 2.36 1.54 1.12 6300* 1.62 1.14 1.24 8000* 1.33 0.97 1.26 n/a 10000* 0.94 0.72 1.40 1.00 Calculated to EN ISO 11654:1997
Calculated to ASTM C 423-01 v5 15/10/2020
0.95
Sample Area: Chamber Volume: Test
Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Temperature: Mounting
7
Room:
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric:

Bonded Wool Serge 565

Fullness: Double Layer Banner System Cavity from Wall: 150mm

Data Sheet 1

Test Report No: 24581-SRL-RP-XT-001-P1

Page 9 of 15

Date: 29/01/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Method:

Double Layer Banner System (150mm Cavity Between Material) - Bonded Wool Serge 565 (Approx. Weight

Roller Banner System (150mm cavity between material) - Bonded Wool Serge 565 (Approx. weight

made up of 2 bonded layers of 565g/m² fabric) – 150mm cavity from wall

Made up of 2 Bonded Layers of 565g/m² Fabric) - 150mm Cavity From Wall

Test 2

Sound Absorption Coefficient

www.jcjoel.com 35
Template Ref: Lab Edition 3 – 14/10/2019
Client: J&C Joel Test Date: 15.1 °C Humidity: 54 %RH Pressure: 1028 mbar 15.1 °C Humidity: 54 %RH Pressure: 1028 mbar 9.3 m² 300 m³ Practical Absorp Coeff # 50* 5.675.250.07 63* 6.035.510.08n/a 80* 8.277.330.08 100 8.346.530.17 125 8.075.210.360.30 160 6.884.510.40 200 6.854.040.53 250 6.863.840.600.65 315 6.443.210.82 400 6.113.040.87 500 5.532.750.960.95 630 4.962.481.06 800 5.072.491.07 1000 5.552.681.011.00 1250 5.532.760.95 1600 5.182.630.98 2000 4.762.461.031.00 2500 4.152.261.06 3150 3.351.981.08 4000 2.691.711.121.00 5000 2.091.451.11 6300* 1.431.081.19 8000* 1.200.951.15n/a 10000* 0.840.721.04 0.95 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 22/01/2020
Data Sheet 1
Sample Area: Chamber Volume:
Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room
Sample: Temperature: Mounting
G -
Sample
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
with
Double
1,130g/m²
300
Description:
1130g/m²

Acoustic Test Report - Absorption

Absorption Class: A

Fabric:

Bonded Wool Serge 565

Fullness: Double Layer Banner System Cavity from Wall: 350mm

Test Report No: 24752-SRL-RP-XT-001-P1

Page 16 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 8

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description:

Double Layer Banner System (100mm Cavity Between Material) - Bonded Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Bonded Layers of 565g/m² Fabric) - 350mm Cavity From Wall

2 Bonded Layers of 565g/m² Fabric) - 350mm Cavity From Wall

Sample Area:

Volume: Test 8 Class A

Sound Absorption Coefficient

www.jcjoel.com 36
to EN ISO 11654:1997
Calculated
Template Ref: Lab Edition 3 – 14/10/2019 DS 8 Client: J & C Joel Ltd Test Date: 16.1 °C Humidity: 63 %RH Pressure: 1016 mbar 15.7 °C Humidity: 59 %RH Pressure: 1016 mbar G - 450 9 m² 300 m³ Practical Absorp Coeff # 50* 5.09 3.99 0.29 63* 4.76 4.47 0.07 n/a 80* 7.42 5.89 0.19 100 7.54 6.50 0.11 125 6.85 4.34 0.46 0.40 160 6.65 3.94 0.56 200 7.05 4.04 0.57 250 6.89 3.68 0.69 0.70 315 6.51 3.27 0.82 400 6.32 2.96 0.97 500 5.53 2.64 1.07 1.00 630 4.91 2.30 1.25 800 5.18 2.44 1.18 1000 5.65 2.54 1.18 1.00 1250 5.60 2.56 1.15 1600 5.16 2.44 1.17 2000 4.76 2.34 1.17 1.00 2500 4.28 2.17 1.21 3150 3.59 1.93 1.26 4000 2.91 1.66 1.34 1.00 5000 2.36 1.45 1.34 6300* 1.62 1.10 1.42 8000* 1.33 0.92 1.57 n/a 10000* 0.94 0.70 1.62 1.00 Calculated to EN ISO 11654:1997 1.05 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Double Roller
Wool Serge 565 (Approx Weight 1130g/² Made up of
Banner System (100mm Cavity Between Material) - Bonded
T1 sec T2 sec Freq Hz Absorp Coeff α s 15/10/2020
Chamber
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Bonded Wool Serge 565 - Enclosed

Fullness: Double Layer Banner System

Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 11 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 37

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Bonded Wool Serge 565 - Enclosed

Fullness: Double Layer Banner System

Cavity from Wall: 350mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 12 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

38
www.jcjoel.com

Test Report No: 24281-SRL-RP-XT-004-P1

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Bonded Wool Serge 565 & Printed Theatre Canvas

Fullness: Double Layer Banner System

Cavity from Wall: 350mm

cavity between material) – Bonded Wool Serge 565 (Approx. weight 1,130g/m2 made up of 2 bonded layers of 565g/m2 fabric) + Printed Theatre Canvas (Approx. weight 340g/m2) – 350mm cavity from wall

Double Layer Banner System (150mm Cavity Between Material) - Bonded Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Bonded Layers of 565g/m² Fabric) + Printed Theatre Canvas (Approx. Weight 340g/m²) - 350mm Cavity From Wall

Sound Absorption Coefficient

www.jcjoel.com 39
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 55 %RH Pressure: 1004 mbar 15.6 °C Humidity: 51 %RH Pressure: 1003 mbar 9 m² 300 m³ Practical Absorp Coeff # 50* 4.904.290.16 63* 5.234.950.06n/a 80* 6.955.990.12 100 7.635.860.21 125 7.105.370.250.30 160 6.604.280.44 200 6.853.940.58 250 7.103.440.810.75 315 6.873.270.87 400 6.653.000.99 500 5.642.751.011.00 630 4.962.371.19 800 5.192.501.12 1000 5.672.721.041.00 1250 5.642.711.03 1600 5.322.571.08 2000 4.862.431.101.00 2500 4.142.231.09 3150 3.411.901.21 4000 2.751.631.271.00 5000 2.141.401.21 6300* 1.461.021.41 8000* 1.180.871.36n/a 10000* 0.830.651.43 1.00 Calculated to EN ISO 11654:1997 1.00 Calculated to ASTM C 423-01 v5 08/03/2019 Data Sheet 2 The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 Sample Area: Chamber Volume:
10 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Double Roller Banner System (150mm
G
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Supersedes C/24281/T03 Page 10 of 16 SRL Technical Services Limited
Test
- 500 Sample Description:
Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Bonded Wool Serge 565 & Printed Theatre Canvas - Enclosed

Fullness: Double Layer Banner System

Cavity from Wall: 150mm

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

J & C Joel Ltd

Sample Description:

Roller Banner System (150mm cavity between material) - Bonded Wool Serge 565 (Approx. weight 1130g/m2 made up of 2 bonded layers of 565g/m2) + Printed Theatre Canvas (Approx. weight 340g/m2) - 150mm cavity from wall set within recess G - 300

Double Layer Banner System (150mm Cavity Between Material) - Bonded Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Bonded Layers of 565g/m² Fabric) + Printed Theatre Canvas (Approx. Weight 340g/m²) - 150mm Cavity From Wall, Enclosed Sides

G - 300

Sound Absorption Coefficient

www.jcjoel.com 40 Test Report No: C/24402/T01 Page 10 of 17 Ds 2 Client:
Test
17.0 °C Humidity: 61 %RH Pressure: 1009 mbar 17.3 °C Humidity: 60 %RH Pressure: 1009 mbar 9.3 m² 300 m³ Practical Absorp Coeff # 50* 4.943.560.41 63* 5.493.880.39n/a 80* 7.423.660.72 100 7.414.420.48 125 7.293.570.750.70 160 7.273.140.94 200 6.723.250.83 250 7.063.500.750.80 315 7.103.500.76 400 6.533.160.85 500 5.762.860.920.90 630 5.132.710.91 800 5.152.770.87 1000 5.823.020.830.85 1250 5.692.980.83 1600 5.422.690.98 2000 5.012.630.940.95 2500 4.432.420.98 3150 3.702.210.95 4000 2.981.910.980.95 5000 2.411.660.97 6300* 1.691.290.95 8000* 1.371.100.93n/a 10000* 0.980.840.87 0.90 Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 24/05/2019
Date:
Data Sheet 2
Sample Area: Chamber Volume: Test 3 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Sample: Temperature: Mounting
Double
Room:
with
Method:
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Calculated to EN ISO 11654:1997

Showcase

Sevenoaks School, UK - Double Roller Banners

Concertina Banner

Concerto

The preferred option when large-scale acoustic absorption performance is required. The absorption is achieved by two layers of Tay Wool Serge, held together at regular intervals by horizontal slats. This achieves a Class A acoustic absorption rating according to EN ISO 11654:1997. These keep the air gap between the layers constant and help the fabric stack neatly as it is raised.

The Concerto offers up to 50m2 of absorbent material, with a maximum width of 6m or a maximum drop of 20m. Standard operating speed is 100-150mm/s which enables a 6m banner to deploy in 60s. Designed and Manufactured in the UK.

Features

• NORD IE3 3 Phase Braked Geared Motor

• Localised NORD Inverter Drive

• Mayr ROBA Stop Stage Safety Brake

• TER Limit Switch - End of Travel & Ultimate

• Absolute Rotary Encoder

• Overheat prevention

• Requires a single phase 13 amp 230V power supply per banner.

• E-Stops compliant with ISO 13850

• Tay Wool Serge is our standard fabric which has tested acoustic reports. Other fabric options and colours are also available upon request for varying aesthetic and acoustic performance.

Installation

• Two Unistrut P1000 channels along the full length of the top of the banner enable simple mounting.

• J&C Joel can install the banners or can provide mechanical and electrical drawings to aid your installation.

42
2D Side View 2D Front View Retracting 2D Front View Retracting 2D Side Viev Retracting

Technical Data

For use with Tay Wool Serge & Pressed Wool Serge, please see page 19.

37
Class A EN ISO 11654:1997 (SAC) Single Phase 240v 13amp NRC 0.95 ASTM C 423-01 (SAC) Drop upto 20m Width 1.2m - 6m 50m² Absorbent Surface Fabric Fabric-Fabric Distance mm Fabric-Wall Distance mm Acoustic Absorption Co-efficient 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz Pressed Tay Wool SergeEnclosed 100 100 0.75 0.90 1.00 0.95 0.85 0.90 100 350 0.65 0.85 1.00 1.00 0.95 0.95 Pressed Tay Wool Serge 100 100 0.40 0.80 1.00 1.00 0.90 0.95 100 350 0.50 0.70 1.00 1.00 1.00 0.95
44 Contents Wall Cavity Class SAC Classification Page 160mm 100mm 350mm 100mm A A A A 0.95 0.90 0.95 0.90 Fabric Pressed Wool Serge 565 Pressed Wool Serge 565 Pressed Coloured Wool Serge Pressed Coloured Wool Serge 45 46 47 48 Pressed Wool Serge 800 Pressed Wool Serge 800 350mm 100mm A A 0.95 0.95 58 59 350mm A 0.90 Pressed Wool Serge 565 49 350mm 350mm 100mm 100mm A A A A 1.00 1.00 0.95 1.00 Pressed Tay Wool Serge (100mm Cavity Between Material, Enclosed) Pressed Tay Wool Serge (100mm Cavity Between Material) 50 51 52 53 100mm A 1.00 54 350mm 350mm 100mm A A A 1.00 1.00 0.95 55 56 57 Pressed Tay Wool Serge (100mm Cavity Between Material, Enclosed) Pressed Tay Wool Serge (100mm Cavity Between Material) Pressed Tay Wool Serge (150mm Cavity Between Material, Enclosed) Pressed Tay Wool Serge (150mm Cavity Between Material) Pressed Tay Wool Serge (150mm Cavity Between Material, Enclosed) Pressed Tay Wool Serge (150mm Cavity Between Material)

A

from

Wall: 100mm

Test Report No: 24694-SRL-RP-XT-001-P1

Page 19 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Empty Room:

Room with Sample:

Sample Description:

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Coloured Wool Serge (Approx. Weight 1000g/m² Made up of 2 Layers of 500g/m² Fabric)100mm Cavity From Wall

www.jcjoel.com 45
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.7 °C Humidity: 66 %RH Pressure: 997 mbar G - 200 9 m² 300 m³ Practical Absorp Coeff # 50* 4.835.00-0.04 63* 5.224.850.08n/a 80* 7.656.440.13 100 7.546.200.15 125 7.755.570.270.25 160 6.514.740.31 200 6.934.370.45 250 6.803.920.580.60 315 6.683.560.70 400 6.353.220.82 500 5.572.691.031.00 630 4.922.421.12 800 4.942.521.04 1000 5.402.661.021.00 1250 5.542.671.04 1600 5.122.680.95 2000 4.792.580.960.95 2500 4.392.430.98 3150 3.742.161.04 4000 3.171.931.081.00 5000 2.591.711.06 6300* 1.951.341.24 8000* 1.571.171.15n/a 10000* 1.110.920.98 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 21/08/2020 Data Sheet 10
The Laboratory Measurement
Sound Absorption generally to BS EN ISO 354:2003 Sample Area: Chamber Volume: Test 12 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s
See SRL report 24694-SRL-RP-XT-001-P1 for full details
of Random Incidence
Temperature:
Temperature:
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Mounting Method: Absorption
Sound
Coefficient
Absorption Class:
Calculated to EN ISO 11654:1997
Acoustic Test Report - Absorption
Fabric: Pressed Coloured Wool Serge Fullness: Concertina Banner System Cavity

Acoustic Test Report - Absorption

Absorption Class: A Calculated to

Fabric:

Pressed Coloured Wool Serge

Fullness: Concertina Banner System Cavity from Wall: 350mm

Test Report No: 24694-SRL-RP-XT-001-P1

Page 20 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 11

See SRL report 24694-SRL-RP-XT-001-P1 for full details

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Mounting Method:

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats)

- Pressed Coloured Wool Serge (Approx. Weight 1000g/m² Made up of 2 Layers of 500g/m² Fabric)350mm Cavity From Wall

Sound Absorption Coefficient

www.jcjoel.com 46
Template Ref: Lab Edition 3 – 14/10/2019 Client:
& C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.6 °C Humidity: 66 %RH Pressure: 997 mbar 9 m² 300 m³ Practical Absorp Coeff # 50* 4.834.640.05 63* 5.224.890.07n/a 80* 7.656.080.18 100 7.545.870.20 125 7.755.110.360.35 160 6.514.010.51 200 6.934.050.55 250 6.803.570.710.65 315 6.683.640.67 400 6.353.130.87 500 5.572.790.960.95 630 4.922.531.03 800 4.942.451.10 1000 5.402.591.081.00 1250 5.542.531.15 1600 5.122.511.09 2000 4.792.491.031.00 2500 4.392.331.08 3150 3.742.071.15 4000 3.171.861.191.00 5000 2.591.611.25 6300* 1.951.321.30 8000* 1.571.141.27n/a 10000* 1.110.871.30 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature:
J
G - 450 Sample Description: Sample Area: Chamber Volume: Test 13 Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 21/08/2020
A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
EN ISO
11654:1997

Acoustic Test Report - Absorption

11654:1997

EN ISO

Fabric: Pressed Wool Serge 565

Test Report No: 24752-SRL-RP-XT-001-P1

Page 10 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 2

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

15/10/2020

Wall T1 sec T2 sec Freq Hz

Absorp Coeff α s

Sound Absorption Coefficient

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats)Pressed Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Layers of 565g/m² Fabric) - 100mm Sample Description: Sample Area: Chamber Volume: Test 2 Class A

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

www.jcjoel.com 47
Template Ref: Lab Edition 3 – 14/10/2019 DS2 Client: J & C Joel Ltd Test Date: 16.1 °C Humidity: 63 %RH Pressure: 1016 mbar 15.9 °C Humidity: 62 %RH Pressure: 1016 mbar 9 m² 300 m³ Practical Absorp Coeff # 50* 5.094.620.11 63* 4.764.520.06n/a 80* 7.426.580.09 100 7.546.700.09 125 6.854.990.290.25 160 6.654.420.41 200 7.054.380.47 250 6.894.140.520.60 315 6.513.360.78 400 6.323.090.90 500 5.532.760.981.00 630 4.912.471.09 800 5.182.571.06 1000 5.652.631.101.00 1250 5.602.661.07 1600 5.162.650.99 2000 4.762.560.971.00 2500 4.282.381.00 3150 3.592.101.06 4000 2.911.841.061.00 5000 2.361.591.08 6300* 1.621.191.16 8000* 1.331.001.27n/a 10000* 0.940.781.08 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample:
Temperature:
Cavity From
Mounting Method: G - 200
Calculated
Absorption Class: A
to
Fullness: Concertina Banner System Cavity from Wall: 100mm

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Pressed Wool Serge 565

Fullness: Concertina Banner System

Cavity from Wall: 160mm

Data Sheets 1 to 9

Data Sheet 1

Test Report No: 24752-SRL-RP-XT-001-P1

Page 9 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Method:

Banner System - Two Layers of Pressed Wool Serge 565 (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 160mm Cavity From Wall

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Layers of 565g/m² Fabric) - 160mm Cavity From Wall

Sound Absorption Coefficient

www.jcjoel.com 48
Template Ref: Lab Edition 3 – 14/10/2019
Ds 1 Client: J & C Joel Ltd Test Date: 16.1 °C Humidity: 63 %RH Pressure: 1016 mbar 15.9 °C Humidity: 63 %RH Pressure: 1016 mbar G - 260 9 m² 300 m³ Practical Absorp Coeff # 50* 5.09 4.45 0.15 63* 4.76 4.50 0.07 n/a 80* 7.42 6.52 0.10 100 7.54 6.33 0.14 125 6.85 4.95 0.30 0.30 160 6.65 4.08 0.51 200 7.05 4.26 0.50 250 6.89 4.05 0.55 0.65 315 6.51 3.18 0.87 400 6.32 3.05 0.92 500 5.53 2.76 0.98 1.00 630 4.91 2.53 1.04 800 5.18 2.47 1.15 1000 5.65 2.58 1.14 1.00 1250 5.60 2.64 1.08 1600 5.16 2.59 1.04 2000 4.76 2.59 0.95 1.00 2500 4.28 2.34 1.05 3150 3.59 2.09 1.08 4000 2.91 1.80 1.14 1.00 5000 2.36 1.55 1.19 6300* 1.62 1.19 1.19 8000* 1.33 1.01 1.26 n/a 10000* 0.94 0.76 1.33 0.95 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room with Sample: Temperature: Mounting
Sample Description: Sample Area: Chamber Volume: Test
Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 15/10/2020
Room:
Concertina
1
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Pressed Wool Serge 565

Fullness: Concertina Banner System Cavity from Wall: 350mm

Test Report No: 24752-SRL-RP-XT-001-P1

Page 11 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 3

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Banner System - Two Layers of Pressed Wool Serge 565 (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 350mm Cavity From Wall

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Wool Serge 565 (Approx. Weight 1130g/m² Made up of 2 Layers of 565g/m² Fabric) - 350mm Cavity From Wall

3

Sound Absorption Coefficient

www.jcjoel.com 49
Template Ref: Lab Edition 3 – 14/10/2019 DS3 Client: J & C Joel Ltd Test Date: 16.1 °C Humidity: 63 %RH Pressure: 1016 mbar 15.9 °C Humidity: 62 %RH Pressure: 1016 mbar G - 450 9 m² 300 m³ Practical Absorp Coeff # 50* 5.09 4.08 0.26 63* 4.76 4.43 0.09 n/a 80* 7.42 6.03 0.17 100 7.54 6.60 0.10 125 6.85 4.63 0.38 0.35 160 6.65 3.97 0.55 200 7.05 4.21 0.52 250 6.89 4.02 0.56 0.60 315 6.51 3.37 0.78 400 6.32 3.24 0.81 500 5.53 2.87 0.91 0.95 630 4.91 2.51 1.06 800 5.18 2.47 1.15 1000 5.65 2.45 1.25 1.00 1250 5.60 2.54 1.17 1600 5.16 2.46 1.15 2000 4.76 2.44 1.08 1.00 2500 4.28 2.27 1.11 3150 3.59 1.99 1.20 4000 2.91 1.75 1.21 1.00 5000 2.36 1.53 1.21 6300* 1.62 1.16 1.28 8000* 1.33 0.97 1.44 n/a 10000* 0.94 0.74 1.45 0.90 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 15/10/2020
Sample
Chamber Volume:
T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room with Sample: Temperature: Mounting
Concertina
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Area:
Test
Class A
Room:
Method:
EN ISO
Calculated to
11654:1997

Acoustic Test Report - Absorption

Absorption Class: A Calculated to

Fabric:

Pressed Tay Wool Serge

Fullness: Concertina Banner System Cavity from Wall: 100mm

Data Sheets 1 to 20

Data Sheet 1

Test Report No: 24766-SRL-RP-XT-001-P1

Page 10 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description: Sample Area: Chamber Volume: Test 1 Class A

Method:

Concertina Banner System - Two Layers of Pressed Tay Wool Serge (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 100mm Cavity From Wall

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 100mm Cavity From Wall

www.jcjoel.com 50
EN ISO 11654:1997
Template Ref: Lab Edition 3 – 14/10/2019
Ds 1 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 16.1 °C Humidity: 57 %RH Pressure: 1015 mbar G - 200 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.97 0.04 63* 4.83 4.37 0.12 n/a 80* 7.33 5.46 0.25 100 7.42 5.22 0.31 125 7.17 4.47 0.46 0.40 160 6.75 4.17 0.50 200 6.77 3.72 0.66 250 6.80 3.42 0.79 0.80 315 6.65 3.12 0.92 400 6.46 2.95 1.00 500 5.63 2.77 0.99 1.00 630 5.00 2.55 1.04 800 5.22 2.63 1.02 1000 5.79 2.75 1.03 1.00 1250 5.75 2.84 0.97 1600 5.33 2.84 0.89 2000 4.93 2.71 0.90 0.90 2500 4.35 2.56 0.87 3150 3.55 2.25 0.88 4000 2.92 1.91 0.97 0.95 5000 2.34 1.65 0.95 6300* 1.60 1.24 0.95 8000* 1.30 1.03 1.05 n/a 10000* 0.93 0.77 1.15 1.00 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
T1 sec T2 sec Freq Hz Absorp Coeff α s
30/11/2020
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Class: A

Fabric: Pressed Tay Wool Serge - Enclosed

Fullness: Concertina Banner System Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 20 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description: Sample Area:

Method:

Volume:

Concertina Banner System - Two Layers of Pressed Tay Wool Serge (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 100mm Cavity From Wall, Enclosed Sides

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats)

- Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 100mm Cavity From Wall, Enclosed Sides

www.jcjoel.com 51
Absorption
Calculated to EN ISO 11654:1997
Template Ref: Lab Edition 3 – 14/10/2019 DS11 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.6 °C Humidity: 56 %RH Pressure: 1011 mbar G - 200 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 3.69 0.42 63* 4.83 3.75 0.32 n/a 80* 7.33 4.74 0.40 100 7.42 4.33 0.52 125 7.17 3.52 0.78 0.75 160 6.75 3.17 0.91 200 6.77 3.28 0.85 250 6.80 3.32 0.84 0.90 315 6.65 3.00 0.99 400 6.46 2.75 1.13 500 5.63 2.69 1.06 1.00 630 5.00 2.52 1.07 800 5.22 2.73 0.95 1000 5.79 2.86 0.96 0.95 1250 5.75 2.85 0.96 1600 5.33 2.91 0.84 2000 4.93 2.72 0.89 0.85 2500 4.35 2.52 0.89 3150 3.55 2.25 0.86 4000 2.92 1.91 0.94 0.90 5000 2.34 1.64 0.92 6300* 1.60 1.22 0.94 8000* 1.30 1.02 0.98 n/a 10000* 0.93 0.77 0.98 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Chamber
Test 11 Class A
Data Sheet 11
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: A Calculated to

Fabric:

Pressed Tay Wool Serge

Fullness: Concertina Banner System

Cavity from Wall: 350mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 11 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Banner System - Two Layers of Pressed Tay Wool Serge (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 350mm Cavity From Wall Sample Description: Sample Area:

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 350mm Cavity From Wall

www.jcjoel.com 52
EN ISO 11654:1997
Template Ref: Lab Edition 3 – 14/10/2019 DS2 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.9 °C Humidity: 57 %RH Pressure: 1016 mbar G - 450 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.59 0.13 63* 4.83 4.23 0.16 n/a 80* 7.33 4.87 0.37 100 7.42 5.01 0.35 125 7.17 4.24 0.52 0.50 160 6.75 3.95 0.57 200 6.77 4.03 0.54 250 6.80 3.62 0.70 0.70 315 6.65 3.26 0.85 400 6.46 2.91 1.02 500 5.63 2.58 1.14 1.00 630 5.00 2.31 1.26 800 5.22 2.43 1.19 1000 5.79 2.64 1.12 1.00 1250 5.75 2.65 1.10 1600 5.33 2.62 1.05 2000 4.93 2.52 1.05 1.00 2500 4.35 2.32 1.08 3150 3.55 2.08 1.07 4000 2.92 1.82 1.10 1.00 5000 2.34 1.55 1.15 6300* 1.60 1.19 1.12 8000* 1.30 0.98 1.29 n/a 10000* 0.93 0.75 1.30 1.00 Calculated to EN ISO 11654:1997 1.00 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Concertina
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020 Data
Method:
Chamber Volume: Test 2 Class A
Sheet 2
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: A Calculated to EN ISO 11654:1997

Fabric: Pressed Tay Wool Serge - Enclosed

Fullness: Concertina Banner System Cavity from Wall: 350mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 21 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description: Sample Area:

Concertina Banner System - Two Layers of Pressed Tay Wool Serge (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 350mm Cavity From Wall, Enclosed Sides

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats)

- Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 350mm Cavity From Wall, Enclosed Sides

www.jcjoel.com 53
Template Ref: Lab Edition 3 – 14/10/2019 DS12Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.6 °C Humidity: 56 %RH Pressure: 1011 mbar G - 450 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 3.35 0.57 63* 4.83 3.76 0.32 n/a 80* 7.33 4.62 0.43 100 7.42 4.52 0.47 125 7.17 3.54 0.78 0.65 160 6.75 3.49 0.75 200 6.77 3.22 0.88 250 6.80 3.51 0.75 0.85 315 6.65 3.04 0.97 400 6.46 2.71 1.16 500 5.63 2.59 1.13 1.00 630 5.00 2.44 1.14 800 5.22 2.60 1.05 1000 5.79 2.75 1.04 1.00 1250 5.75 2.79 1.00 1600 5.33 2.78 0.93 2000 4.93 2.64 0.95 0.95 2500 4.35 2.46 0.94 3150 3.55 2.18 0.93 4000 2.92 1.88 0.98 0.95 5000 2.34 1.60 1.00 6300* 1.60 1.18 1.09 8000* 1.30 0.99 1.14 n/a 10000* 0.93 0.75 1.17 1.00 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Method:
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Chamber Volume: Test 12 Class A
Data Sheet 12
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: A Calculated

Fabric:

Pressed Tay Wool Serge

Fullness: Concertina Banner System Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 12 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 3

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description:

Method:

Sample Area:

Banner System - Two Layers of Pressed Tay Wool Serge (150mm Cavity Between Material Using Lightweight Aluminium Slats) - 100mm Cavity From Wall

Concertina Banner System (150mm Cavity Between Material) (Including Lightweight Aluminium Slats)

- Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 100mm Cavity From Wall

Volume: Test 3 Class A

Sound Absorption Coefficient

www.jcjoel.com 54
ISO
to EN
11654:1997
Template Ref: Lab Edition 3 – 14/10/2019 DS3 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.8 °C Humidity: 56 %RH Pressure: 1016 mbar G - 250 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.62 0.12 63* 4.83 4.40 0.11 n/a 80* 7.33 5.32 0.28 100 7.42 4.89 0.38 125 7.17 4.26 0.52 0.50 160 6.75 3.92 0.58 200 6.77 3.52 0.74 250 6.80 3.44 0.78 0.80 315 6.65 3.15 0.91 400 6.46 2.83 1.08 500 5.63 2.71 1.04 1.00 630 5.00 2.50 1.09 800 5.22 2.62 1.03 1000 5.79 2.96 0.90 0.95 1250 5.75 2.86 0.95 1600 5.33 2.73 0.97 2000 4.93 2.67 0.92 0.95 2500 4.35 2.47 0.94 3150 3.55 2.19 0.93 4000 2.92 1.86 1.02 1.00 5000 2.34 1.61 0.99 6300* 1.60 1.21 1.00 8000* 1.30 1.00 1.11 n/a 10000* 0.93 0.74 1.30 1.00 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Concertina
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Chamber
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Pressed Tay Wool Serge - Enclosed

Fullness: Concertina Banner System Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 22 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Banner System - Two Layers of Pressed Tay Wool Serge (150mm Cavity Between Material Using Lightweight Aluminium Slats) - 100mm Cavity From Wall, Enclosed Sides

Concertina Banner System (150mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 100mm Cavity From Wall, Enclosed Sides

Sound Absorption Coefficient

www.jcjoel.com 55
Template Ref: Lab Edition 3 – 14/10/2019
13 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.9 °C Humidity: 56 %RH Pressure: 1011 mbar 9 m² 300 m³ Practical Absorp Coeff # 50* 5.153.410.54 63* 4.833.570.40n/a 80* 7.334.910.36 100 7.424.370.51 125 7.173.540.770.75 160 6.753.060.97 200 6.773.150.92 250 6.803.250.870.95 315 6.652.891.06 400 6.462.801.10 500 5.632.631.101.00 630 5.002.630.98 800 5.222.760.93 1000 5.792.980.880.90 1250 5.752.870.95 1600 5.332.800.92 2000 4.932.680.920.90 2500 4.352.510.90 3150 3.552.190.93 4000 2.921.920.930.95 5000 2.341.620.97 6300* 1.601.201.05 8000* 1.301.011.07n/a 10000* 0.930.761.13 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 30/11/2020 Data Sheet 13
DS
Sample
Chamber Volume: Test 13 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting
G - 250 Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Area:
Method: Concertina
G - 250

Acoustic Test Report - Absorption

Absorption Class: A Calculated to

Fabric:

Pressed Tay Wool Serge

Fullness: Concertina Banner System

Cavity from Wall: 350mm

Sheet 4

Test Report No: 24766-SRL-RP-XT-001-P1

Page 13 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Banner System - Two Layers of Pressed Tay Wool Serge (150mm Cavity Between Material Using Lightweight Aluminium Slats) - 350mm Cavity From Wall Sample Description: Sample Area:

Concertina Banner System (150mm Cavity Between Material) (Including Lightweight Aluminium Slats)

- Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 350mm Cavity From Wall

Class A

www.jcjoel.com 56
ISO
EN
11654:1997
Template Ref: Lab Edition 3 – 14/10/2019 DS4 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.6 °C Humidity: 56 %RH Pressure: 1016 mbar G - 500 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.61 0.12 63* 4.83 4.38 0.12 n/a 80* 7.33 5.44 0.26 100 7.42 4.98 0.36 125 7.17 4.24 0.52 0.50 160 6.75 3.78 0.63 200 6.77 3.68 0.67 250 6.80 3.38 0.81 0.80 315 6.65 3.14 0.91 400 6.46 2.77 1.12 500 5.63 2.53 1.18 1.00 630 5.00 2.40 1.18 800 5.22 2.55 1.09 1000 5.79 2.74 1.04 1.00 1250 5.75 2.70 1.07 1600 5.33 2.53 1.12 2000 4.93 2.41 1.14 1.00 2500 4.35 2.28 1.12 3150 3.55 2.01 1.14 4000 2.92 1.77 1.16 1.00 5000 2.34 1.52 1.18 6300* 1.60 1.13 1.30 8000* 1.30 0.96 1.31 n/a 10000* 0.93 0.71 1.57 1.00 Calculated to EN ISO 11654:1997 1.05 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Concertina
Method:
Chamber Volume: Test 4
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020 Data
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: A Calculated to

Fabric:

Pressed Tay Wool Serge - Enclosed

Fullness: Concertina Banner System Cavity from Wall: 350mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 23 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample Description: Sample Area:

Method:

Banner System - Two Layers of Pressed Tay Wool Serge (150mm Cavity Between Material Using Lightweight Aluminium Slats) - 350mm Cavity From Wall, Enclosed Sides

Concertina Banner System (150mm Cavity Between Material) (Including Lightweight Aluminium Slats) - Pressed Tay Wool Serge (Approx. Weight 1250g/m² Made up of 2 Layers of 625g/m² Fabric) - 350mm Cavity From Wall, Enclosed Sides

www.jcjoel.com 57
EN ISO 11654:1997
Template Ref: Lab Edition 3 – 14/10/2019 DS14 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1011 mbar G - 500 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 3.12 0.69 63* 4.83 3.58 0.39 n/a 80* 7.33 3.87 0.66 100 7.42 4.18 0.57 125 7.17 3.48 0.80 0.75 160 6.75 3.25 0.86 200 6.77 3.04 0.98 250 6.80 3.25 0.87 0.95 315 6.65 2.88 1.07 400 6.46 2.70 1.17 500 5.63 2.54 1.17 1.00 630 5.00 2.41 1.17 800 5.22 2.59 1.06 1000 5.79 2.89 0.94 1.00 1250 5.75 2.82 0.98 1600 5.33 2.63 1.04 2000 4.93 2.58 1.00 1.00 2500 4.35 2.41 0.99 3150 3.55 2.13 0.99 4000 2.92 1.89 0.97 1.00 5000 2.34 1.57 1.07 6300* 1.60 1.18 1.10 8000* 1.30 1.00 1.10 n/a 10000* 0.93 0.76 1.09 1.00 Calculated to EN ISO 11654:1997 1.00 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Concertina
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Chamber Volume: Test 14 Class A
Data Sheet 14
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Pressed Wool Serge 800

Fullness: Concertina Banner System Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 16 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 7

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Banner System - Two Layers of Pressed Wool Serge 800 (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 100mm Cavity From Wall

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats)Pressed Wool Serge 800 (Approx. Weight 1600g/m² Made up of 2 Layers of 800g/m² Fabric) - 100mm Cavity From Wall

Sound Absorption Coefficient

www.jcjoel.com 58
Template Ref: Lab Edition 3 – 14/10/2019 DS7 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1014 mbar G - 200 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 5.06 0.02 63* 4.83 4.73 0.02 n/a 80* 7.33 5.95 0.17 100 7.42 5.51 0.25 125 7.17 5.02 0.32 0.35 160 6.75 4.28 0.46 200 6.77 4.11 0.52 250 6.80 3.80 0.63 0.65 315 6.65 3.39 0.78 400 6.46 2.99 0.98 500 5.63 2.81 0.97 1.00 630 5.00 2.61 1.00 800 5.22 2.58 1.07 1000 5.79 2.66 1.10 1.00 1250 5.75 2.70 1.07 1600 5.33 2.64 1.03 2000 4.93 2.64 0.95 1.00 2500 4.35 2.45 0.95 3150 3.55 2.11 1.02 4000 2.92 1.81 1.10 1.00 5000 2.34 1.57 1.07 6300* 1.60 1.20 1.03 8000* 1.30 0.99 1.15 n/a 10000* 0.93 0.75 1.18 0.95 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Concertina
Sample Description: Sample Area: Chamber Volume: Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Method:
7
A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Pressed Wool Serge 800

Fullness: Concertina Banner System

Cavity from Wall: 350mm

Data Sheet 9

Test Report No: 24752-SRL-RP-XT-001-P1

Page 17 of 23

Date: 12/11/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Banner System - Two Layers of Pressed Wool Serge 800 (100mm Cavity Between Material Using Lightweight Aluminium Slats) - 350mm Cavity From Wall

Concertina Banner System (100mm Cavity Between Material) (Including Lightweight Aluminium Slats)Pressed Wool Serge 800 (Approx. Weight 1600g/m² Made up of 2 Layers of 800g/m² Fabric) - 350mm Cavity From Wall

9

www.jcjoel.com 59
Template Ref: Lab Edition 3 – 14/10/2019
Client: J & C Joel Ltd Test Date: 16.1 °C Humidity: 63 %RH Pressure: 1016 mbar 15.7 °C Humidity: 58 %RH Pressure: 1015 mbar G - 450 9 m² 300 m³ Practical Absorp Coeff # 50* 5.09 4.17 0.24 63* 4.76 4.41 0.09 n/a 80* 7.42 6.24 0.14 100 7.54 6.67 0.09 125 6.85 4.37 0.45 0.35 160 6.65 3.91 0.57 200 7.05 4.10 0.55 250 6.89 3.94 0.59 0.65 315 6.51 3.30 0.81 400 6.32 3.13 0.87 500 5.53 2.67 1.05 1.00 630 4.91 2.37 1.19 800 5.18 2.37 1.24 1000 5.65 2.40 1.30 1.00 1250 5.60 2.53 1.17 1600 5.16 2.40 1.20 2000 4.76 2.37 1.13 1.00 2500 4.28 2.23 1.14 3150 3.59 1.93 1.25 4000 2.91 1.67 1.30 1.00 5000 2.36 1.45 1.31 6300* 1.62 1.12 1.29 8000* 1.33 0.94 1.39 n/a 10000* 0.94 0.71 1.43 0.95 Calculated to EN ISO 11654:1997 1.00 Calculated to ASTM C 423-01 v5 15/10/2020
DS9
Sample
Chamber
T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting
Concertina
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Absorption Coefficient
Area:
Volume: Test
Class A
Method:
Sound
Calculated to EN ISO
11654:1997

Acoustic Drapery Absorption Reports

Product Wool Serge Page 62 Velvet Other Fabrics 146 116

Wool Serge

Product Wool Serge 420 Page 65 Wool Serge 565 72 Wool Serge 650 79 Wool Serge 800 86 Wool Serge 1000 93 Euro Wool Serge 104 Coloured Wool Serge 110 Wool Serge 1.8 100
Showcase Bonus Arena - Wool Serge 565 (WS090)

Wool Serge 420

A lightweight cost-effective IFR wool serge suitable for a variety of applications.

Cardinal Heenan Catholic High School, Liverpool - Wool Serge 420 (WS100)
100% 100% 50% Fullness Wall Cavity Class SAC Classification Page Flat 50% 350mm 100mm 350mm 100mm 350mm 100mm Flat D C C B B A 0.95 0.85 0.85 0.75 0.65 0.50 71 70 69 68 67 66 Width: 150cm /59” FR Certification: BS5867 Weight: 420 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft FR Rating: IFR Colour Available 1 WS100 Black Fabric Thickness: *1.35 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions

Acoustic Test Report - Absorption

Fabric: Wool Serge 420

Fullness: Flat Cavity from Wall: 100mm

Data Sheet 21

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014 Empty Room:

Sample D escription: Wool Serge 420 - Single Layer – Flat (Approx. weight 420g/m²) – 100mm cavity from wall Mounting Method: G-100

Test

23

Class D Calculated to EN ISO 11654:1997

0.55 Calculated to ASTM C 423-01

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

66 Confidential
www.jcjoel.com
Temperature:
Humidity:
%RH Pressure:
Room
Temperature:
Humidity:
%RH Pressure: 999mbar
19.0 °C
62
999mbar
with Sample:
18.9 °C
61
Sample
Chamber
Area: 9 m2
Volume: 300 m3
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.070.05 63*5.405.44-0.01n/a 80*6.566.540.00 100 7.576.940.06 125 7.116.720.040.05 160 6.425.940.07 200 7.125.830.17 250 7.075.890.150.20 315 6.844.880.32 400 6.464.320.41 500 5.453.530.540.55 630 4.963.020.70 800 5.473.130.74 1000 5.913.180.780.75 1250 5.593.050.80 1600 5.063.010.72 2000 4.752.950.690.70 2500 4.342.770.70 3150 3.642.480.69 4000 3.092.150.750.75 5000 2.441.800.76 6300*1.791.440.70 8000*1.511.230.76n/a 10000*1.060.880.96
 0.50(MH)
NRC
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Absorption
Calculated to EN ISO 11654:1997
Class: D

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Confidential

Fabric: Wool Serge 420

Fullness: Flat Cavity from Wall: 350mm

Data Sheet 22

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014

Sample D escription: Wool Serge 420 - Single Layer – Flat (Approx. weight 420g/m²) – 350mm cavity from wall Mounting Method: G-350

Area: 9 m2

Volume: 300 m3

Test 24

67 www.jcjoel.com
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 18.9 °C Humidity: 61 %RH Pressure: 999mbar
with Sample:
Sample
Chamber
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.200.03 63*5.404.600.17n/a 80*6.565.990.08 100 7.576.440.12 125 7.116.260.100.15 160 6.424.860.27 200 7.124.700.39 250 7.074.370.470.45 315 6.844.040.55 400 6.463.710.62 500 5.453.400.600.60 630 4.963.270.56 800 5.473.260.67 1000 5.913.330.710.70 1250 5.593.260.69 1600 5.063.090.68 2000 4.752.920.710.70 2500 4.342.720.74 3150 3.642.380.78 4000 3.092.140.760.75 5000 2.441.790.78 6300*1.791.400.81 8000*1.511.200.87n/a 10000*1.060.890.89  0.65 Class C
NRC 0.60
T1, empty room reverberation
T2, room reverberation
sample
absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Calculated to EN ISO 11654:1997
Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003
time
time with
# Practical

Acoustic Test Report - Absorption

Fabric: Wool Serge 420

Fullness: 50% Cavity from Wall: 100mm

Data Sheet 24

Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 Client: J&C Joel Ltd

The

Test 26

www.jcjoel.com 68 Confidential
Empty
Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Sample: Temperature: 18.9 °C Humidity: 61 %RH Pressure: 1000mbar
Mounting
Sample Area: 9 m2 Chamber Volume: 300 m3
Test Date: 20/05/2014
Room:
with
Sample D escription: Wool Serge 420 – Single Layer – 50% fullness (Approx. weight 420g/m²) – 100mm cavity from wall
Method: G-100
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.230.02 63*5.404.740.14n/a 80*6.565.880.09 100 7.577.390.02 125 7.115.710.190.15 160 6.424.980.24 200 7.124.800.37 250 7.074.620.400.45 315 6.843.830.62 400 6.463.460.72 500 5.453.010.800.80 630 4.962.790.85 800 5.472.840.91 1000 5.912.960.910.90 1250 5.592.970.85 1600 5.062.940.77 2000 4.752.750.820.80 2500 4.342.550.87 3150 3.642.290.87 4000 3.092.050.870.85 5000 2.441.740.87 6300*1.791.370.89 8000*1.511.170.98n/a 10000*1.060.841.25  0.75 Class C Calculated
EN ISO
NRC 0.75 Calculated
to
11654:1997
to ASTM C 423-01
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
* Denotes frequencies outside the range covered by BS EN ISO 354:2003
Absorption Class: C Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

B

Fabric: Wool Serge 420

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 23

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014

Sample D escription: Wool Serge 420 – Single Layer – 50% fullness (Approx. weight 420g/m²) – 350mm cavity from wall

Test

25

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

69 www.jcjoel.com Confidential
Temperature:
Humidity:
Pressure:
Room
Temperature:
Humidity:
%RH Pressure: 999mbar
Empty Room:
19.0 °C
62 %RH
999mbar
with Sample:
18.9 °C
61
Sample Area:
Chamber
Mounting Method: G-350
9 m2
Volume: 300 m3
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.390.22 63*5.404.790.13n/a 80*6.565.790.11 100 7.576.130.17 125 7.115.520.220.25 160 6.424.520.35 200 7.124.140.54 250 7.073.850.640.65 315 6.843.520.74 400 6.463.340.78 500 5.452.930.850.80 630 4.962.830.82 800 5.472.900.87 1000 5.912.970.900.90 1250 5.592.800.96 1600 5.062.750.89 2000 4.752.680.870.90 2500 4.342.500.91 3150 3.642.220.94 4000 3.092.010.920.95 5000 2.441.680.98 6300*1.791.340.98 8000*1.511.161.02n/a 10000*1.060.811.49  0.85
Class B Calculated to EN ISO 11654:1997 NRC 0.80 Calculated to ASTM C 423-01
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Calculated to EN ISO
Absorption Class:
11654:1997

Acoustic Test Report - Absorption

Fabric: Wool Serge 420

Fullness: 100% Cavity from Wall: 100mm

Data Sheet 25

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 Client: J&C Joel Ltd

D escription: Wool Serge 420 – Single Layer – 100% fullness (Approx. weight 420g/m²) – 100mm cavity from wall

Method: G-100

Test 27

70 Confidential
www.jcjoel.com
Empty
Temperature: 19.0
Humidity: 62 %RH Pressure: 999mbar Room
Sample: Temperature: 19.0
Humidity: 61 %RH Pressure: 1001mbar
Mounting
Sample
Chamber
Test Date: 20/05/2014
Room:
°C
with
°C
Sample
Area: 9 m2
Volume: 300 m3
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.430.21 63*5.404.610.17n/a 80*6.565.860.10 100 7.577.500.01 125 7.115.420.240.15 160 6.424.840.27 200 7.124.510.44 250 7.074.200.520.55 315 6.843.600.71 400 6.463.220.84 500 5.452.890.880.90 630 4.962.680.92 800 5.472.671.03 1000 5.912.880.961.00 1250 5.592.820.95 1600 5.062.740.90 2000 4.752.600.940.95 2500 4.342.450.95 3150 3.642.240.92 4000 3.091.960.991.00 5000 2.441.661.02 6300*1.791.350.95 8000*1.511.151.08n/a 10000*1.060.821.42
0.85(H)
Calculated to EN ISO 11654:1997 NRC 0.85 Calculated to ASTM C 423-01
Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t

Class B
*
Calculated to EN ISO 11654:1997
Absorption Class: B

Acoustic Test Report - Absorption

Fabric: Wool Serge 420

Fullness: 100% Cavity from Wall: 350mm

Data Sheet 26

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014 Empty Room:

Sample D escription: Wool Serge 420 – Single Layer – 100% fullness (Approx. weight 420g/m²) – 350mm cavity from wall Mounting Method: G-350

Area: 9 m2

Volume: 300 m3

Test 28

71 www.jcjoel.com Confidential
Temperature:
Humidity:
Pressure:
Room
Temperature:
Humidity:
Pressure:
Sample
Chamber
19.0 °C
62 %RH
999mbar
with Sample:
19.0 °C
60 %RH
1001mbar
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.600.16 63*5.404.500.20n/a 80*6.565.350.19 100 7.576.300.14 125 7.114.920.340.30 160 6.424.180.45 200 7.123.860.64 250 7.073.780.660.70 315 6.843.350.82 400 6.463.190.85 500 5.452.810.930.90 630 4.962.670.93 800 5.472.701.01 1000 5.912.781.031.00 1250 5.592.691.04 1600 5.062.611.00 2000 4.752.511.011.00 2500 4.342.361.03 3150 3.642.111.06 4000 3.091.891.091.00 5000 2.441.621.08 6300*1.791.301.08 8000*1.511.111.20n/a 10000*1.060.811.44  0.95 Class A Calculated to EN ISO 11654:1997 NRC 0.90 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Absorption Class: A Calculated to EN ISO 11654:1997

Wool Serge 565

The workhorse for on stage masking, perimeter and acoustic drapery in the entertainment and events industry.

Bonus Arena, Hull - Wool Serge 565 (WS090)
100% 100% 50% Fullness Wall Cavity Class SAC Classification Page Flat 50% 350mm 100mm 350mm 100mm 350mm 100mm Flat D C B B A A 0.90 0.90 0.85 0.80 0.70 0.55 78 77 76 75 74 73 Width: 150cm /59” FR Certification: BS5867, NFPA 701, IMO, AS1530.2/3 Weight: 565 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft FR Rating: IFR Colour Available 1 WS090 Black Fabric Thickness: *1.90 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions

Acoustic Test Report - Absorption

Fabric: Wool Serge 565

Fullness: Flat Cavity from Wall: 100mm

Data Sheet 9

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 12/04/2014 Empty Room:

Sample D escription: Wool Serge 565 - Single Layer – Flat (Approx. weight 565g/m²) – 100mm cavity from wall Mounting Method: G-100

Test

10

73
Confidential
www.jcjoel.com
Temperature:
Humidity:
Room
Temperature:
Humidity:
Pressure:
Sample
Chamber
17.0 °C
57 %RH Pressure: 1010mbar
with Sample:
16.7 °C
50 %RH
1009mbar
Area: 9 m2
Volume: 300 m3
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.075.34-0.05 63*4.604.75-0.04n/a 80*5.865.270.10 100 6.966.700.03 125 7.226.730.050.05 160 6.825.920.12 200 6.375.610.11 250 7.195.280.270.25 315 7.064.950.33 400 6.404.160.46 500 5.353.500.540.55 630 5.033.020.72 800 5.433.010.80 1000 5.963.060.860.80 1250 5.703.090.80 1600 5.082.980.74 2000 4.622.960.630.70 2500 4.172.610.73 3150 3.502.260.77 4000 2.851.900.820.85 5000 2.251.510.97 6300*1.661.161.09 8000*1.380.981.13n/a 10000*0.930.691.36
Calculated
EN ISO
NRC 0.60 Calculated
Denotes
by BS EN ISO
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
 0.55(MH) Class D
to
11654:1997
to ASTM C 423-01 *
frequencies outside the range covered
354:2003
Absorption Class: D Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Fabric: Wool Serge 565

Fullness: Flat Cavity from Wall: 350mm

The

Data Sheet 10

Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 12/04/2014 Empty Room:

Sample D escription: Wool Serge 565 - Single Layer – Flat (Approx. weight 565g/m²) – 350mm cavity from wall

Test

Class C Calculated to EN ISO 11654:1997

0.65 Calculated to ASTM C 423-01

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

74 Confidential
www.jcjoel.com
Temperature:
Humidity:
Pressure:
Room
Temperature:
Humidity:
%RH Pressure: 1009mbar
Sample
Chamber
17.0 °C
57 %RH
1010mbar
with Sample:
16.7 °C
50
Mounting Method: G-350
Area: 9 m2
Volume: 300 m3
11 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.074.920.03 63*4.603.970.19n/a 80*5.865.000.16 100 6.965.590.19 125 7.225.500.230.25 160 6.824.580.39 200 6.374.110.47 250 7.194.080.570.55 315 7.063.860.64 400 6.403.600.66 500 5.353.310.630.60 630 5.033.300.57 800 5.433.210.69 1000 5.963.370.700.70 1250 5.703.310.68 1600 5.083.020.71 2000 4.622.830.720.75 2500 4.172.570.76 3150 3.502.230.80 4000 2.851.850.900.90 5000 2.251.491.02 6300*1.661.161.09 8000*1.380.981.13n/a 10000*0.930.691.36  0.70(H)
NRC
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Absorption Class:
Calculated to EN ISO 11654:1997
C

Acoustic Test Report - Absorption

B

Fabric: Wool Serge 565

Fullness: 50% Cavity from Wall: 100mm

Data Sheet 13

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 12/04/2014

Sample D escription: Wool Serge 565 – Single Layer – 50% fullness (Approx. weight 565g/m²) – 100mm cavity from wall

75
Confidential
www.jcjoel.com
Temperature:
Humidity:
%RH Pressure: 1010mbar Room
Temperature:
Humidity:
%RH Pressure: 1009mbar
Sample
Chamber
14 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.075.19-0.02 63*4.604.160.12n/a 80*5.865.260.10 100 6.966.420.06 125 7.225.910.160.15 160 6.825.070.27 200 6.374.600.33 250 7.194.180.540.50 315 7.063.960.60 400 6.403.510.70 500 5.352.960.820.80 630 5.032.670.95 800 5.432.830.92 1000 5.962.990.900.90 1250 5.702.990.85 1600 5.082.800.85 2000 4.622.650.840.85 2500 4.172.390.91 3150 3.502.130.90 4000 2.851.810.941.00 5000 2.251.451.09 6300*1.661.111.25 8000*1.380.941.30n/a 10000*0.930.661.62
0.80(H)
Calculated to EN ISO 11654:1997 NRC 0.80 Calculated to ASTM C
Denotes frequencies outside the range
by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Empty Room:
17.0 °C
57
with Sample:
16.7 °C
49
Mounting Method: G-100
Area: 9 m2
Volume: 300 m3 Test

Class B
423-01 *
covered
Calculated to EN ISO 11654:1997
Absorption Class:

Acoustic Test Report - Absorption

Class: B

Fabric: Wool Serge 565

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 14

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 12/04/2014

Sample D escription: Wool Serge 565 – Single Layer – 50% fullness (Approx. weight 565g/m²) – 350mm cavity from wall

Test

B

0.80

to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003

76 Confidential
www.jcjoel.com
Temperature:
Humidity:
%RH Pressure: 1010mbar Room
Temperature:
Humidity: 49 %RH Pressure: 1009mbar
Mounting
Sample
Chamber
Empty Room:
17.0 °C
57
with Sample:
16.1 °C
Method: G-350
Area: 9 m2
Volume: 300 m3
15 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.074.880.04 63*4.604.170.12n/a 80*5.864.930.17 100 6.965.240.26 125 7.225.110.310.35 160 6.824.160.51 200 6.373.890.54 250 7.193.640.730.70 315 7.063.400.83 400 6.403.370.76 500 5.353.150.710.75 630 5.032.840.84 800 5.432.920.86 1000 5.962.990.900.90 1250 5.702.930.89 1600 5.082.760.88 2000 4.622.610.870.90 2500 4.172.330.96 3150 3.502.070.96 4000 2.851.761.001.00 5000 2.251.401.18 6300*1.661.081.32 8000*1.380.941.21n/a 10000*0.930.661.50
0.85(H)

NRC
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Class
Calculated to EN ISO 11654:1997
Calculated
Calculated to EN ISO 11654:1997
Absorption

Acoustic Test Report - Absorption

Fabric: Wool Serge 565

Fullness: 100% Cavity from Wall: 100mm

Data Sheet 16

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 12/04/2014

Sample D escription: Wool Serge 565 – Single Layer – 100% fullness (Approx. weight 565g/m²) – 100mm cavity from wall

Test

77 www.jcjoel.com Confidential
Temperature:
Humidity:
%RH Pressure: 1010mbar Room
Temperature:
Humidity: 49 %RH Pressure: 1009mbar
Sample
Chamber
Empty Room:
17.0 °C
57
with Sample:
16.7 °C
Mounting Method: G-100
Area: 9 m2
Volume: 300 m3
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.075.35-0.06 63*4.603.670.30n/a 80*5.865.360.09 100 6.966.570.05 125 7.225.260.280.20 160 6.824.850.32 200 6.374.320.40 250 7.193.850.650.60 315 7.063.710.69 400 6.403.250.82 500 5.352.910.850.90 630 5.032.611.00 800 5.432.780.95 1000 5.962.870.980.95 1250 5.702.820.96 1600 5.082.720.91 2000 4.622.580.900.90 2500 4.172.340.96 3150 3.502.090.95 4000 2.851.751.041.00 5000 2.251.431.14 6300*1.661.111.25 8000*1.380.951.24n/a 10000*0.930.671.50  0.90 Class A Calculated to EN ISO 11654:1997 NRC 0.85 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
17
Absorption Class: A Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Fabric: Wool Serge 565

Fullness: 100% Cavity from Wall: 350mm

Data Sheet 15

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sample D escription: Wool Serge 565 – Single Layer – 100% fullness (Approx. weight 565g/m²) – 350mm cavity from wall

Test

78 Confidential
www.jcjoel.com
Temperature:
Humidity:
%RH Pressure: 1010mbar Room
Temperature:
Humidity:
%RH Pressure: 1009mbar
Mounting
Sample
Chamber
Client: J&C Joel Ltd Test Date: 12/04/2014 Empty Room:
17.0 °C
57
with Sample:
16.7 °C
49
Method: G-350
Area: 9 m2
Volume: 300 m3
16 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.074.930.03 63*4.603.720.28n/a 80*5.865.220.11 100 6.965.480.21 125 7.225.020.330.35 160 6.824.330.45 200 6.373.890.54 250 7.193.600.750.70 315 7.063.430.81 400 6.403.340.78 500 5.353.090.740.80 630 5.032.760.89 800 5.432.711.00 1000 5.962.860.981.00 1250 5.702.780.99 1600 5.082.591.01 2000 4.622.490.971.00 2500 4.172.281.02 3150 3.502.001.07 4000 2.851.681.171.00 5000 2.251.381.28 6300*1.661.081.39 8000*1.380.931.36n/a 10000*0.930.671.50  0.90 Class A Calculated to EN ISO 11654:1997 NRC 0.85 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Absorption Class:
Calculated to EN ISO 11654:1997
A

Wool Serge 650

A heavy-duty fabric with excellent acoustic properties whether flat or sewn with fullness.

American School of Dubai, UAE - Wool Serge 650 (WS041)
100% 100% 50% Fullness Wall Cavity Class SAC Classification Page Flat 50% 350mm 100mm 350mm 100mm 350mm 100mm Flat C C B A A A 1.00 0.90 0.95 0.80 0.75 0.60 85 84 83 82 81 80 Width: 150cm /59” FR Certification: BS5867 Weight: 650 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft FR Rating: IFR Colour Available 1 WS041 Black Fabric Thickness: *2.00 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions

Calculated to EN ISO 11654:1997

Fabric: Wool Serge 650

Test Report No: 24694-SRL-RP-XT-001-P1

Page 18 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Empty Room: Temperature: Room with Sample: Temperature:

Sound Absorption Coefficient

1.10

1.00

0.90

0.80

0.70

0.60

0.50

0.40

0.30

0.20

0.10

Wool Serge 650 - Single Layer - Flat (Approx. Weight 650g/m²) - 100mm cavity from wall Sample Description: NRC

1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

Absorption Coefficient Frequency, Hz

0.00

www.jcjoel.com 80
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.2 °C Humidity: 67 %RH Pressure: 994 mbar 21.5 °C Humidity: 67 %RH Pressure: 996 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.504.83-0.08 63* 5.345.000.07n/a 80* 7.807.200.06 100 7.456.780.07 125 7.526.510.110.10 160 6.435.600.12 200 7.005.470.21 250 6.854.800.330.30 315 6.504.400.39 400 6.173.640.60 500 5.513.160.720.70 630 4.842.800.81 800 5.032.740.89 1000 5.392.830.900.90 1250 5.592.880.90 1600 5.173.050.72 2000 4.852.910.730.75 2500 4.422.690.78 3150 3.752.380.82 4000 3.162.150.800.80 5000 2.581.840.84 6300* 1.921.480.84 8000* 1.541.240.86n/a 10000* 1.120.960.83
Calculated to EN ISO 11654:1997 0.65 Calculated to ASTM C 423-01 v5 21/08/2020
Sheet 9
0.60(MH)
Data
Laboratory
BS EN ISO 354:2003 Sample Area: Chamber Volume: Test 10 Class C T1 sec T2 sec Freq Hz Absorp Coeff α s
See SRL report 24694-SRL-RP-XT-001-P1 for full details The
Measurement of Random Incidence Sound Absorption generally to
Mounting Method: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997
Acoustic Test Report - Absorption
Absorption Class: C
Fullness: Flat Cavity from Wall: 100mm

Acoustic Test Report - Absorption

Class: C

Fabric: Wool Serge 650 Fullness: Flat Cavity from Wall: 350mm

Page 24 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Sound Absorption Coefficient

81 www.jcjoel.com
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.7 °C Humidity: 43 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.720.06 63* 5.394.750.14n/a 80* 7.085.950.15 100 9.007.070.16 125 7.305.690.210.20 160 6.604.880.29 200 6.864.620.38 250 7.223.960.620.55 315 6.993.690.70 400 6.363.530.69 500 5.643.210.730.70 630 5.093.130.67 800 5.102.960.77 1000 5.743.070.820.80 1250 5.633.070.80 1600 5.182.840.85 2000 4.762.600.910.90 2500 4.222.370.95 3150 3.352.010.99 4000 2.591.631.081.00 5000 2.041.281.35 6300* 1.390.961.41 8000* 1.140.811.47n/a 10000* 0.800.591.83 0.75(H) Calculated to EN ISO 11654:1997 0.75 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Wool
Sample Description: Sample Area: Chamber Volume: Test
Class C T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet 14 The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Method:
Serge 650 - Single Layer - flat (Approx. weight 650g/m2) - 350mm cavity from wall
15
Absorption
Calculated to EN ISO 11654:1997

Class: B

Fabric: Wool Serge 650

Fullness: 50% Cavity from Wall: 100mm

report

Test Report No: 24694-SRL-RP-XT-001-P1

Page 17 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Wool Serge 650 - Single Layer - 50% Fullness (Approx. Weight 650g/m²) - 100mm cavity from wall

Sound

www.jcjoel.com 82
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.2 °C Humidity: 67 %RH Pressure: 994 mbar 21.5 °C Humidity: 67 %RH Pressure: 996 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.504.76-0.07 63* 5.344.960.08n/a 80* 7.806.830.10 100 7.456.580.09 125 7.525.940.190.20 160 6.434.700.31 200 7.004.620.39 250 6.854.090.530.50 315 6.503.990.52 400 6.173.310.75 500 5.512.850.910.85 630 4.842.600.95 800 5.032.591.00 1000 5.392.681.001.00 1250 5.592.711.02 1600 5.172.780.89 2000 4.852.660.910.90 2500 4.422.530.90 3150 3.752.290.91 4000 3.162.040.930.95 5000 2.581.780.94 6300* 1.921.421.00 8000* 1.541.240.86n/a 10000* 1.120.950.89 0.80(H) Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 21/08/2020
BS EN
Sample Area: Chamber Volume: Test 9 Class B T1 sec T2 sec Freq Hz Absorp Coeff α s
Data Sheet 8 See SRL
24694-SRL-RP-XT-001-P1 for full details The Laboratory Measurement of Random Incidence Sound Absorption generally to
ISO 354:2003
Empty Room: Temperature: Room with Sample: Temperature:
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Mounting Method: Absorption
Coefficient
Absorption
Calculated to EN ISO 11654:1997
Acoustic Test Report - Absorption

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Wool Serge 650

Fullness: 50% Cavity from Wall: 350mm

Page 23 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Serge 650 - Single Layer - 50% fullness (Approx. weight 650g/m2) - 350mm cavity from wall Sample Description:

Method:

Sound Absorption Coefficient

83 www.jcjoel.com
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.6 °C Humidity: 43 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.410.14 63* 5.394.470.21n/a 80* 7.085.550.21 100 9.007.050.17 125 7.305.580.230.25 160 6.604.520.38 200 6.864.220.50 250 7.223.690.720.70 315 6.993.390.83 400 6.363.170.86 500 5.643.010.850.90 630 5.092.621.01 800 5.102.670.97 1000 5.742.850.961.00 1250 5.632.661.07 1600 5.182.591.03 2000 4.762.451.041.00 2500 4.222.251.07 3150 3.351.861.20 4000 2.591.581.181.00 5000 2.041.261.41 6300* 1.390.921.64 8000* 1.140.791.63n/a 10000* 0.800.581.97 0.95 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room
Sample: Temperature: Mounting
Sample
Chamber
Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet 13
with
Wool
Area:
Volume:
14
A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Calculated
EN ISO 11654:1997
to

Acoustic Test Report - Absorption

Absorption

Fabric: Wool Serge 650

Test Report No: 24694-SRL-RP-XT-001-P1

Page 16 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Empty Room: Temperature: Room with Sample: Temperature:

Sound Absorption Coefficient

1.10

1.00

0.90

0.80

0.70

0.60

0.50

0.40

Sample Description: 0.00

0.30

0.20

Wool Serge 650 - Single Layer - 100% Fullness (Approx. Weight 650g/m²) - 100mm cavity from wall NRC

1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

Absorption Coefficient Frequency, Hz

0.10

www.jcjoel.com 84
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.2 °C Humidity: 67 %RH Pressure: 994 mbar 21.5 °C Humidity: 67 %RH Pressure: 995 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.504.59-0.02 63* 5.344.940.08n/a 80* 7.806.970.08 100 7.456.530.10 125 7.525.610.240.20 160 6.434.710.30 200 7.004.310.48 250 6.853.850.610.60 315 6.503.600.66 400 6.173.110.85 500 5.512.780.950.95 630 4.842.570.98 800 5.032.531.05 1000 5.392.661.021.00 1250 5.592.711.02 1600 5.172.710.94 2000 4.852.600.950.95 2500 4.422.421.00 3150 3.752.211.00 4000 3.162.010.971.00 5000 2.581.760.97 6300* 1.921.391.08 8000* 1.541.201.01n/a 10000* 1.120.911.14 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 21/08/2020 Data Sheet 7
SRL
24694-SRL-RP-XT-001-P1 for
The Laboratory Measurement
Incidence Sound Absorption generally to BS EN ISO 354:2003 Sample Area: Chamber Volume: Test 8 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s
See
report
full details
of Random
Mounting Method: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997
Calculated to EN ISO 11654:1997
Class:
A
Fullness: 100% Cavity from Wall: 100mm

Acoustic Test Report - Absorption

Class: A

Fabric: Wool Serge 650

Fullness: 100% Cavity from Wall: 350mm

Page 22 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS

Sample Description:

Method:

Serge 650 - Single Layer - 100% fullness (Approx. weight 650g/m2) - 350mm cavity from wall

Sound Absorption Coefficient

85 www.jcjoel.com
No: C/24281/T01
Test Report
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.5 °C Humidity: 43 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.410.14 63* 5.394.480.21n/a 80* 7.085.690.19 100 9.006.720.21 125 7.305.280.290.30 160 6.604.290.44 200 6.863.880.61 250 7.223.480.810.80 315 6.993.160.94 400 6.363.150.87 500 5.642.870.930.95 630 5.092.601.03 800 5.102.581.04 1000 5.742.771.011.00 1250 5.632.661.07 1600 5.182.541.07 2000 4.762.381.111.00 2500 4.222.171.15 3150 3.351.821.26 4000 2.591.541.271.00 5000 2.041.251.43 6300* 1.390.921.63 8000* 1.140.791.61n/a 10000* 0.800.581.95 1.00 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 19/01/2019 Data Sheet 12
Sample Area: Chamber Volume:
13 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Sample: Temperature: Mounting
EN ISO 354:2003
Test
Room:
with
Wool
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Absorption
Calculated to EN ISO 11654:1997

Wool Serge 800

A hard-wearing fabric perfect for creating a black box on stage or masking offstage areas and equipment.

QVC Studios, London - Wool Serge 800 (WS022)
100% 100% 50% Fullness Wall Cavity Class SAC Classification Page Flat 50% 350mm 100mm 350mm 100mm 350mm 100mm Flat C C B A A A 1.00 0.95 0.95 0.85 0.75 0.65 92 91 90 89 88 87 Width: 150cm /59” FR Certification: BS5867 Weight: 800 g/m2 Custom Dye N/A Approx Roll Length: 38m / 125ft FR Rating: IFR Colour Available 1 WS022 Black Fabric Thickness: *2.10 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions

Acoustic Test Report - Absorption

C

Fabric: Wool Serge 800

Fullness: Flat Cavity from Wall: 100mm

The

Data Sheet 11

Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Test

Class C Calculated to EN ISO 11654:1997

0.70 Calculated to ASTM C 423-01

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

87 www.jcjoel.com
Confidential
Room: Temperature: 17.0 °C Humidity: 57 %RH Pressure: 1010mbar Room
Sample: Temperature: 16.7 °C Humidity: 50 %RH Pressure: 1009mbar
Mounting
Sample Area: 9 m2 Chamber Volume: 300 m3
Client: J&C Joel Ltd Test Date: 12/04/2014 Empty
with
Sample D escription: Wool Serge 800 - Single Layer – Flat (Approx. weight 800g/m²) – 100mm cavity from wall
Method: G-100
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.075.33-0.05 63*4.604.050.16n/a 80*5.865.720.02 100 6.966.530.05 125 7.226.800.050.05 160 6.825.980.11 200 6.375.290.17 250 7.194.670.410.35 315 7.064.530.43 400 6.403.930.53 500 5.353.240.660.65 630 5.032.850.83 800 5.432.880.88 1000 5.962.980.910.90 1250 5.702.930.89 1600 5.082.840.83 2000 4.622.810.730.80 2500 4.172.560.77 3150 3.502.220.81 4000 2.851.860.880.90 5000 2.251.501.00 6300*1.661.121.26 8000*1.380.971.19n/a 10000*0.930.701.25
12
 0.65(MH)
NRC
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Calculated to EN ISO 11654:1997
Absorption Class:

Acoustic Test Report - Absorption

Class: C

Fabric: Wool Serge 800

Fullness: Flat Cavity from Wall: 350mm

Data Sheet 12

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 12/04/2014

Sample D escription: Wool Serge 800 - Single Layer – Flat (Approx. weight 800g/m²) – 350mm cavity from wall Mounting Method: G-350

Test

0.70 Calculated to ASTM C 423-01

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

www.jcjoel.com 88 Confidential
Humidity:
Humidity:
Pressure:
Empty Room: Temperature: 17.0 °C
57 %RH Pressure: 1010mbar Room with Sample: Temperature: 16.7 °C
50 %RH
1009mbar
Sample
Chamber
Area: 9 m2
Volume: 300 m3
13 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.075.010.01 63*4.604.100.14n/a 80*5.865.520.06 100 6.965.500.21 125 7.225.440.240.30 160 6.824.410.43 200 6.374.120.46 250 7.193.940.620.60 315 7.063.730.68 400 6.403.570.67 500 5.353.290.640.65 630 5.033.060.70 800 5.433.050.78 1000 5.963.240.760.75 1250 5.703.160.76 1600 5.082.890.79 2000 4.622.730.790.80 2500 4.172.510.81 3150 3.502.130.92 4000 2.851.810.961.00 5000 2.251.461.10 6300*1.661.141.17 8000*1.380.961.25n/a 10000*0.930.681.48
NRC
 0.75(H) Class C Calculated to EN ISO 11654:1997
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
Calculated to EN ISO 11654:1997
Absorption

Acoustic Test Report - Absorption

Absorption Class: B

Calculated

Fabric: Wool Serge 800

Test Report No: 24694-SRL-RP-XT-001-P1

Page 15 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

See SRL report 24694-SRL-RP-XT-001-P1 for full details

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS

Empty Room: Temperature: Room with Sample: Temperature:

Sound Absorption Coefficient

1.10

1.00

0.90

0.80

0.70

0.60

0.50

0.40

0.30

0.20

0.10

Wool Serge 800 - Single Layer - 50% Fullness (Approx. Weight 800g/m²) - 100mm cavity from wall Sample Description: NRC

1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

Absorption Coefficient Frequency, Hz

0.00

89 www.jcjoel.com
Template Ref: Lab Edition 3 – 14/10/2019
J & C Joel Test Date: 21.2 °C Humidity: 67 %RH Pressure: 994 mbar 21.5 °C Humidity: 68 %RH Pressure: 995 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.504.61-0.03 63* 5.344.670.14n/a 80* 7.806.690.11 100 7.456.450.11 125 7.525.680.230.25 160 6.434.560.34 200 7.004.640.39 250 6.853.800.630.55 315 6.503.730.61 400 6.173.280.76 500 5.512.810.930.90 630 4.842.590.96 800 5.032.501.08 1000 5.392.631.041.00 1250 5.592.671.05 1600 5.172.700.95 2000 4.852.690.890.90 2500 4.422.560.88 3150 3.752.260.95 4000 3.162.020.970.95 5000 2.581.760.98 6300* 1.921.450.94 8000* 1.541.201.04n/a 10000* 1.120.931.06 0.85 Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 21/08/2020
Client:
Data Sheet 6
Sample Area: Chamber Volume: Test 7 Class B T1 sec T2 sec Freq Hz Absorp Coeff α s
EN ISO 354:2003
Mounting Method: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997
to EN ISO 11654:1997
Fullness: 50% Cavity from Wall: 100mm

Acoustic Test Report - Absorption

Class: A

Fabric: Wool Serge 800

Fullness: 50% Cavity from Wall: 350mm

Page 31 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

- 50% fullness (Approx. weight 800g/m2) 350mm cavity from the wall Sample Description:

www.jcjoel.com 90
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 45 %RH Pressure: 1007 mbar 15.4 °C Humidity: 42 %RH Pressure: 1009 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.894.500.10 63* 5.294.910.08n/a 80* 7.175.970.15 100 8.746.820.17 125 7.195.480.230.30 160 6.814.200.49 200 6.803.980.56 250 6.893.790.640.70 315 6.813.330.83 400 6.463.090.92 500 5.522.880.900.90 630 5.092.710.94 800 5.132.601.03 1000 5.662.761.001.00 1250 5.452.750.97 1600 5.022.610.98 2000 4.542.371.071.00 2500 4.012.171.10 3150 3.161.841.16 4000 2.471.491.341.00 5000 1.891.221.41 6300* 1.260.901.49 8000* 1.050.751.75n/a 10000* 0.750.571.90 0.95 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Wool Serge
Sample
Chamber
Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 20/01/2019 Data Sheet 21
800 - Single Layer
Area:
Volume:
23
A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient
Calculated
EN ISO
Absorption
to
11654:1997

Absorption

Fullness: 100% Cavity from Wall: 100mm

Test Report No: 24694-SRL-RP-XT-001-P1

Page 14 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Sound Absorption Coefficient

1.10

1.00

0.90

0.80

0.70

0.60

0.50

0.40

Description: 0.00

0.30

0.20

Wool Serge 800 - Single Layer - 100% Fullness (Approx. Weight 800g/m²) - 100mm cavity from wall NRC

1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

Absorption Coefficient Frequency, Hz

0.10

91 www.jcjoel.com
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.2 °C Humidity: 67 %RH Pressure: 994 mbar 21.5 °C Humidity: 68 %RH Pressure: 995 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.504.55-0.01 63* 5.344.740.13n/a 80* 7.806.430.15 100 7.456.110.16 125 7.525.660.230.25 160 6.434.450.37 200 7.004.120.54 250 6.853.590.710.70 315 6.503.350.78 400 6.173.130.84 500 5.512.721.000.95 630 4.842.560.98 800 5.032.511.07 1000 5.392.671.011.00 1250 5.592.681.04 1600 5.172.680.96 2000 4.852.580.970.95 2500 4.422.450.97 3150 3.752.181.03 4000 3.161.951.061.00 5000 2.581.721.06 6300* 1.921.391.09 8000* 1.541.201.04n/a 10000* 1.120.921.12 0.95 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 21/08/2020
Sheet 5
Laboratory
Sound Absorption generally to BS EN ISO 354:2003 Sample Area: Chamber Volume: Test 6 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s
Data
See SRL report 24694-SRL-RP-XT-001-P1 for full details The
Measurement of Random Incidence
Empty Room: Temperature: Room with Sample: Temperature:
Sample
Mounting Method: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997
Calculated to EN ISO 11654:1997
Acoustic Test Report - Absorption
Class: A
Fabric: Wool Serge 800

Acoustic Test Report - Absorption

Class: A

Fabric: Wool Serge 800

Fullness: 100% Cavity from Wall: 350mm

Page 32 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

800 - Single Layer - 100% fullness (Approx. weight 800g/m2) 350mm cavity from the wall

www.jcjoel.com 92
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 45 %RH Pressure: 1007 mbar 15.3 °C Humidity: 42 %RH Pressure: 1009 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.894.550.08 63* 5.294.550.17n/a 80* 7.176.160.12 100 8.746.750.18 125 7.195.080.310.35 160 6.814.080.53 200 6.803.770.64 250 6.893.510.760.75 315 6.813.180.91 400 6.463.010.96 500 5.522.770.981.00 630 5.092.561.05 800 5.132.561.06 1000 5.662.691.051.00 1250 5.452.581.10 1600 5.022.491.08 2000 4.542.301.141.00 2500 4.012.111.17 3150 3.161.771.27 4000 2.471.461.401.00 5000 1.891.151.67 6300* 1.260.861.75 8000* 1.050.731.93n/a 10000* 0.750.542.41 1.00 Calculated to EN ISO 11654:1997 1.00 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Wool
Sample
Chamber
Test
Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 20/01/2019 Data Sheet 22
Serge
Sample Description:
Area:
Volume:
24
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient
Absorption
Calculated to EN ISO 11654:1997

Wool Serge 1000

The heavyweight of the Wool Serge world, offering the best acoustic properties whether flat or sewn with fullness.

Sample of Wool Serge 1000 (WS055)
100% 100% 50% Fullness Wall Cavity Class SAC Classification Page Flat 50% 350mm 100mm 350mm 100mm 350mm 100mm Flat B B A A A A 1.00 1.00 1.00 1.00 0.80 0.80 99 98 97 96 95 94 Width: 150cm /59” FR Certification: BS5867 Weight: 1000 g/m2 Custom Dye N/A Approx Roll Length: 35m / 115ft FR Rating: IFR Colour Available 1 WS055 Black Fabric Thickness: *3.00 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions

Acoustic Test Report - Absorption

Absorption Class: B Calculated to

Fabric: Wool Serge 1000

Fullness: Flat Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 19 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Sound Absorption Coefficient

www.jcjoel.com 94
Template Ref: Lab Edition 3 – 14/10/2019
DS10
Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.8 °C Humidity: 56 %RH Pressure: 1013 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 5.30 -0.03 63* 4.83 5.20 -0.08 n/a 80* 7.33 6.54 0.09 100 7.42 5.98 0.18 125 7.17 5.97 0.15 0.20 160 6.75 5.02 0.28 200 6.77 4.58 0.38 250 6.80 4.25 0.48 0.50 315 6.65 3.78 0.62 400 6.46 3.32 0.79 500 5.63 3.01 0.84 0.85 630 5.00 2.73 0.90 800 5.22 2.66 1.00 1000 5.79 3.00 0.87 0.90 1250 5.75 3.16 0.77 1600 5.33 2.99 0.79 2000 4.93 2.83 0.81 0.80 2500 4.35 2.63 0.80 3150 3.55 2.25 0.86 4000 2.92 1.92 0.93 0.90 5000 2.34 1.62 0.97 6300* 1.60 1.21 1.00 8000* 1.30 1.02 1.00 n/a 10000* 0.93 0.77 1.02 0.80 Calculated to EN ISO 11654:1997 0.75 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Wool Serge 1000 - Single Layer - Flat (Approx. Weight 1000g/m²) - 100mm Cavity From Wall Sample Description: Sample Area: Chamber Volume: Test 10 Class B T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020 Data Sheet 10 The Laboratory
Absorption generally to BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Client: J & C Joel Ltd
Measurement of Random Incidence Sound
EN ISO
11654:1997

Acoustic Test Report - Absorption

Class: B

Fabric: Wool Serge 1000

Fullness: Flat

Cavity from Wall: 350mm

Page 30 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Sound Absorption Coefficient

95 www.jcjoel.com
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 45 %RH Pressure: 1007 mbar 15.4 °C Humidity: 43 %RH Pressure: 1009 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.894.350.14 63* 5.294.840.10n/a 80* 7.176.410.09 100 8.746.590.20 125 7.195.640.210.30 160 6.814.430.43 200 6.804.380.44 250 6.893.740.660.60 315 6.813.500.75 400 6.463.360.78 500 5.523.320.650.75 630 5.092.930.79 800 5.132.850.85 1000 5.663.040.820.85 1250 5.452.910.86 1600 5.022.770.87 2000 4.542.560.910.90 2500 4.012.290.99 3150 3.161.901.09 4000 2.471.561.201.00 5000 1.891.251.35 6300* 1.260.911.49 8000* 1.050.771.65n/a 10000* 0.750.581.84 0.80(H) Calculated to EN ISO 11654:1997 0.75 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Wool Serge 1000 - Single Layer - flat (Approx. weight 1000g/m2) 350mm cavity from the wall Sample Description: Sample Area: Chamber Volume:
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 20/01/2019 Data Sheet 20 The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Test 22
B
Absorption
Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Wool Serge 1000

Fullness: 50% Cavity from Wall: 100mm

Data Sheet 9

Test Report No: 24766-SRL-RP-XT-001-P1

Page 18 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J & C Joel Ltd

Method:

Serge 1000 - Single Layer - 50% Fullness (Approx. Weight 1000g/m²) - 100mm Cavity From Wall

Sound Absorption Coefficient

www.jcjoel.com 96
Template Ref: Lab Edition 3 – 14/10/2019
DS9
Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.8 °C Humidity: 56 %RH Pressure: 1013 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.87 0.06 63* 4.83 4.80 0.01 n/a 80* 7.33 5.99 0.17 100 7.42 5.93 0.18 125 7.17 4.75 0.39 0.40 160 6.75 3.84 0.61 200 6.77 3.77 0.64 250 6.80 3.44 0.78 0.75 315 6.65 3.27 0.84 400 6.46 2.85 1.06 500 5.63 2.69 1.05 1.00 630 5.00 2.50 1.09 800 5.22 2.56 1.08 1000 5.79 2.73 1.05 1.00 1250 5.75 2.81 0.99 1600 5.33 2.71 0.98 2000 4.93 2.56 1.01 1.00 2500 4.35 2.40 1.00 3150 3.55 2.08 1.06 4000 2.92 1.82 1.08 1.00 5000 2.34 1.54 1.14 6300* 1.60 1.16 1.19 8000* 1.30 0.96 1.34 n/a 10000* 0.93 0.74 1.30 1.00 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature: Mounting
Sample Description: Sample Area: Chamber Volume: Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Room:
with Sample:
Wool
9
A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Class: A

Fabric: Wool Serge 1000 Fullness: 50% Cavity from Wall: 350mm

Page 26 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

weight 1000g/m2)

97 www.jcjoel.com
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.7 °C Humidity: 42 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.320.16 63* 5.394.280.26n/a 80* 7.085.640.20 100 9.006.640.21 125 7.305.320.280.35 160 6.604.120.49 200 6.863.830.63 250 7.223.310.890.85 315 6.993.070.99 400 6.362.911.02 500 5.642.761.011.00 630 5.092.591.03 800 5.102.541.07 1000 5.742.691.071.00 1250 5.632.631.09 1600 5.182.561.05 2000 4.762.381.101.00 2500 4.222.171.14 3150 3.351.811.26 4000 2.591.491.361.00 5000 2.041.221.51 6300* 1.390.911.65 8000* 1.140.771.73n/a 10000* 0.800.581.87 1.00 Calculated to EN ISO 11654:1997 1.00 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Wool Serge 1000 - Single Layer - 50% fullness (Approx.
Sample
Chamber
T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet
Sample Description:
Area:
Volume: Test 17 Class A
16
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
350mm cavity from wall
Sound Absorption Coefficient
Absorption
Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Wool Serge 1000

Fullness: 100% Cavity from Wall: 100mm

Data Sheet 8

DS 8

Test Report No: 24766-SRL-RP-XT-001-P1

Page 17 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J & C Joel Ltd

Serge 1000 - Single Layer - 100% Fullness (Approx. Weight 1000g/m²) - 100mm

Sound Absorption Coefficient

www.jcjoel.com 98
Template Ref: Lab Edition 3 – 14/10/2019
Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.9 °C Humidity: 56 %RH Pressure: 1013 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.86 0.06 63* 4.83 4.66 0.04 n/a 80* 7.33 6.04 0.16 100 7.42 5.68 0.22 125 7.17 4.71 0.39 0.40 160 6.75 3.86 0.60 200 6.77 3.71 0.66 250 6.80 3.37 0.81 0.80 315 6.65 3.10 0.93 400 6.46 2.77 1.12 500 5.63 2.56 1.16 1.00 630 5.00 2.41 1.17 800 5.22 2.57 1.07 1000 5.79 2.72 1.06 1.00 1250 5.75 2.74 1.04 1600 5.33 2.64 1.03 2000 4.93 2.48 1.08 1.00 2500 4.35 2.32 1.08 3150 3.55 2.03 1.12 4000 2.92 1.76 1.19 1.00 5000 2.34 1.53 1.17 6300* 1.60 1.15 1.24 8000* 1.30 0.98 1.24 n/a 10000* 0.93 0.73 1.42 1.00 Calculated to EN ISO 11654:1997 1.05 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature: Mounting
Wool
Cavity
Sample Description: Sample Area: Chamber Volume: Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Room:
with Sample:
Method:
From Wall
8
A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Class: A

Fabric: Wool Serge 1000 Fullness: 100% Cavity from Wall: 350mm

Page 25 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to

weight 1000g/m2)

99 www.jcjoel.com
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.7 °C Humidity: 43 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.430.13 63* 5.394.690.15n/a 80* 7.085.830.17 100 9.006.480.23 125 7.304.790.390.40 160 6.603.730.63 200 6.863.500.76 250 7.223.320.880.90 315 6.992.951.06 400 6.363.010.95 500 5.642.711.041.00 630 5.092.541.07 800 5.102.551.07 1000 5.742.671.091.00 1250 5.632.581.13 1600 5.182.471.13 2000 4.762.321.171.00 2500 4.222.101.24 3150 3.351.821.27 4000 2.591.501.371.00 5000 2.041.221.56 6300* 1.390.901.79 8000* 1.140.771.82n/a 10000* 0.800.572.15 1.00 Calculated to EN ISO 11654:1997 1.05 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Wool
Sample
Sample Area: Chamber Volume:
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet
Serge 1000 - Single Layer - 100% fullness (Approx.
Description:
Test 16
A
15
EN
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
350mm cavity from wall
BS
ISO 354:2003
Sound Absorption Coefficient
Absorption
Calculated to EN ISO 11654:1997

Wool Serge 1.8

A durable fabric ideal for theatrical application as well as being used for touring shows and hire drapes.

Fullness Wall Cavity Class SAC Classification Page 50% 100% 350mm 100mm 100mm 100% B A A 0.90 0.90 0.85 103 102 101 Width: 180cm /71” FR Certification: BS5867, IMO, AS1530.2/3 Weight: 500 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft FR Rating: IFR Colour Available 1 WS180 Black Fabric Thickness: *1.40 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions
Wool Serge 1.8 (WS180)

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Wool Serge 1.8

Fullness: 50% Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 19 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 101

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Wool Serge 1.8

Fullness: 100% Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 20 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 102

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:199

Fabric: Wool Serge 1.8

Fullness: 100% Cavity from Wall: 350mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 21 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 103

Euro Wool Serge

A hard-wearing fabric perfect for the touring market, manufactured specifically to meet B1 and M1 FR standards.

Sample of Euro Wool Serge (WS040)
100% 50% Fullness Wall Cavity Class SAC Classification Page 350mm 350mm B A 1.00 0.85 350mm Flat C 0.75 109 108 107 Width: 150cm /59” FR Certification: BS5867, M1, NFPA 701 Weight: 786 g/m2 Custom Dye N/A Approx Roll Length: 57m / 187ft FR Rating: DFR Colour Available 1 WS040 Black Fabric Thickness: *1.90 mm *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions 100mm 50% B 100% 100mm A 0.90 0.85 106 105

Acoustic Test Report - Absorption

Class: C

Fabric: Euro Wool Serge

Fullness: Flat

Cavity from Wall: 350mm

Page 27 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Method:

Wool Serge - Single Layer - flat (Approx. weight 786g/m2) 350mm cavity from wall

www.jcjoel.com 105
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 45 %RH Pressure: 1007 mbar 15.6 °C Humidity: 45 %RH Pressure: 1008 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.89 4.64 0.06 63* 5.29 4.33 0.23 n/a 80* 7.17 6.09 0.13 100 8.74 6.56 0.21 125 7.19 5.65 0.21 0.25 160 6.81 4.81 0.33 200 6.80 4.62 0.38 250 6.89 3.97 0.58 0.55 315 6.81 3.67 0.68 400 6.46 3.45 0.73 500 5.52 3.26 0.68 0.70 630 5.09 3.10 0.68 800 5.13 2.95 0.78 1000 5.66 3.16 0.76 0.75 1250 5.45 3.07 0.77 1600 5.02 2.92 0.78 2000 4.54 2.70 0.81 0.80 2500 4.01 2.49 0.82 3150 3.16 2.06 0.91 4000 2.47 1.73 0.93 0.95 5000 1.89 1.42 0.94 6300* 1.26 1.04 0.90 8000* 1.05 0.88 0.98 n/a 10000* 0.75 0.64 1.22 0.75(H) Calculated to EN ISO 11654:1997 0.70 Calculated to ASTM C 423-01 v5 20/01/2019
Data Sheet 17
Sample Area: Chamber Volume: Test
Class C T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Temperature: Mounting
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Absorption Coefficient
19
Room:
with Sample:
Euro
Sound
Absorption
Calculated
to EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Euro Wool Serge

Fullness: 50% Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 17 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 106

Acoustic Test Report - Absorption

Fabric: Euro Wool Serge

Fullness: 50% Cavity from Wall: 350mm

Page 28 of 38

Date: 13/02/2019

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Mounting Method: 20/01/2019

Empty Room: T1 sec T2 sec Freq Hz

Room with Sample: Absorp Coeff α s

Euro Wool Serge - Single Layer - 50% fullness (Approx. weight 786g/m2) 350mm cavity from wall

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

www.jcjoel.com 107
Report No: C/24281/T01
Test
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 45 %RH Pressure: 1007 mbar 15.6 °C Humidity: 45 %RH Pressure: 1008 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.89 4.51 0.09 63* 5.29 4.89 0.08 n/a 80* 7.17 6.36 0.10 100 8.74 7.08 0.15 125 7.19 5.56 0.22 0.30 160 6.81 4.33 0.46 200 6.80 3.96 0.57 250 6.89 3.78 0.65 0.65 315 6.81 3.42 0.79 400 6.46 3.33 0.79 500 5.52 3.02 0.81 0.80 630 5.09 2.83 0.85 800 5.13 2.72 0.94 1000 5.66 2.90 0.91 0.90 1250 5.45 2.86 0.90 1600 5.02 2.71 0.92 2000 4.54 2.55 0.93 0.95 2500 4.01 2.37 0.93 3150 3.16 2.02 0.96 4000 2.47 1.68 1.03 1.00 5000 1.89 1.38 1.05 6300* 1.26 1.01 1.05 8000* 1.05 0.85 1.20 n/a 10000* 0.75 0.64 1.22 0.85(H) Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC
Temperature:
Temperature:
Sample
This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited Sample Area: Chamber Volume: Test 20 Class B
Description:
Data Sheet 18
Sound Absorption Coefficient
Absorption Class: B Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Euro Wool Serge

Fullness: 100% Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 18 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 108

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Euro Wool Serge

Fullness: 100% Cavity from Wall: 350mm

Page 29 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS

Room:

Wool Serge - Single Layer - 100% fullness (Approx. weight 786g/m2) 350mm cavity from wall

Method:

Sound Absorption Coefficient

www.jcjoel.com 109 Test Report No: C/24281/T01
Client: J & C Joel Ltd Test Date: 15.7 °C Humidity: 45 %RH Pressure: 1007 mbar 15.4 °C Humidity: 44 %RH Pressure: 1009 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.89 4.53 0.09 63* 5.29 4.77 0.11 n/a 80* 7.17 6.18 0.12 100 8.74 6.85 0.17 125 7.19 5.37 0.26 0.30 160 6.81 4.19 0.50 200 6.80 3.97 0.57 250 6.89 3.55 0.74 0.75 315 6.81 3.14 0.93 400 6.46 3.07 0.93 500 5.52 2.82 0.94 0.95 630 5.09 2.62 1.00 800 5.13 2.55 1.07 1000 5.66 2.68 1.06 1.00 1250 5.45 2.65 1.05 1600 5.02 2.52 1.07 2000 4.54 2.32 1.13 1.00 2500 4.01 2.13 1.18 3150 3.16 1.79 1.28 4000 2.47 1.50 1.37 1.00 5000 1.89 1.23 1.47 6300* 1.26 0.90 1.62 8000* 1.05 0.76 1.83 n/a 10000* 0.75 0.58 1.95 1.00 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 20/01/2019
Data Sheet 19
Sample Area: Chamber Volume:
T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature:
Temperature: Mounting
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
EN ISO 354:2003
Test 21 Class A
Room with Sample:
Euro
Calculated
EN
to
ISO 11654:1997

Coloured Wool Serge

A popular fabric for perimeter and production drapes due to its wide range of colours and acoustic properties.

Brighton
UAE
Coloured Wool
College,
-
Serge (WS017)
Acoustic 100% 100% 50% Fullness Wall Cavity Class SAC Classification Page 50% 350mm 100mm 350mm 100mm B B A A 0.90 0.90 0.85 0.80 114 113 112 111 Width: 150cm /59” FR Certification: BS5867, IMO Weight: 500 g/m2 Custom Dye Available* Approx Roll Length: 57m / 187ft FR Rating: IFR Colours Available 17 WS006 WS008 WS005 WS007 WS011 WS016 WS010 WS017 WS019 WS012 WS009 WS056 WS018 WS013 WS020 WS015 WS014 Plum Scarlet Ultra Blue Cognac Gold Mole Midnight Original Grey Slate Natural Bottle Oxford Emerald Marine TV Blue *FABRIC THICKNESS Measured in-house with digital callipers, not under labatory conditions *CUSTOM DYE price on application, 4 wk lead time, MOQ 2 rolls Chroma Key Blue Chroma Key Green Fabric Thickness: *1.70 mm

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Coloured Wool Serge

Fullness: 50% Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 26 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

with Sample: 30/11/2020

Method:

17

Room: Absorp Coeff α s

Sound Absorption Coefficient

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

B

www.jcjoel.com 111
Template Ref: Lab Edition 3 – 14/10/2019 17
Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1010 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 5.21 -0.01 63* 4.83 5.31 -0.10 n/a 80* 7.33 7.00 0.04 100 7.42 6.33 0.13 125 7.17 5.52 0.23 0.20 160 6.75 4.96 0.29 200 6.77 4.62 0.37 250 6.80 4.23 0.49 0.50 315 6.65 3.66 0.67 400 6.46 3.23 0.84 500 5.63 2.87 0.93 0.95 630 5.00 2.58 1.02 800 5.22 2.72 0.96 1000 5.79 2.93 0.92 0.95 1250 5.75 2.94 0.90 1600 5.33 2.87 0.87 2000 4.93 2.72 0.89 0.90 2500 4.35 2.50 0.91 3150 3.55 2.17 0.95 4000 2.92 1.86 1.02 1.00 5000 2.34 1.60 1.00 6300* 1.60 1.17 1.14 8000* 1.30 1.01 1.04 n/a 10000* 0.93 0.74 1.28 0.80(H) Calculated to EN ISO 11654:1997 0.80 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature: Mounting
Sample Description: Sample
Chamber Volume: Test
Class
Client: J & C Joel Ltd T1 sec T2 sec Freq Hz
Coloured Wool Serge - Single Layer - 50% Fullness (Approx. Weight 500g/m²) - 100mm Cavity From Wall
Area:
Data Sheet 17
The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003
Acoustic Test Report - Absorption

Acoustic Test Report - Absorption

B

Fabric: Coloured Wool Serge

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 18

Test Report No: 24766-SRL-RP-XT-001-P1

Page 27 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sound Absorption Coefficient

112
www.jcjoel.com
Template Ref: Lab Edition 3 – 14/10/2019 18
Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1009 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.78 0.08 63* 4.83 4.91 -0.02 n/a 80* 7.33 6.13 0.15 100 7.42 5.95 0.18 125 7.17 4.91 0.35 0.30 160 6.75 4.40 0.43 200 6.77 4.32 0.45 250 6.80 3.83 0.62 0.60 315 6.65 3.52 0.73 400 6.46 3.25 0.83 500 5.63 3.10 0.79 0.80 630 5.00 2.83 0.83 800 5.22 2.83 0.88 1000 5.79 2.95 0.90 0.90 1250 5.75 2.90 0.93 1600 5.33 2.73 0.97 2000 4.93 2.66 0.93 0.95 2500 4.35 2.41 0.99 3150 3.55 2.12 1.01 4000 2.92 1.81 1.10 1.00 5000 2.34 1.54 1.14 6300* 1.60 1.14 1.26 8000* 1.30 0.98 1.21 n/a 10000* 0.93 0.72 1.49 0.85(H) Calculated to EN ISO 11654:1997 0.80 Calculated to ASTM C 423-01 v5 30/11/2020
Client: J & C Joel
Sample
Chamber Volume: Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting
Coloured
Fullness
Cavity
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Area:
18
B
Method:
Wool Serge - Single Layer - 50%
(Approx. Weight 500g/m²) - 350mm
From Wall
Absorption Class:
Calculated to EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Coloured Wool Serge

Fullness: 100% Cavity from Wall: 100mm

Data Sheet 15

Test Report No: 24766-SRL-RP-XT-001-P1

Page 24 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Wool Serge - Single Layer - 100% Fullness (Approx. Weight 500g/m²) - 100mm

Sound Absorption Coefficient

www.jcjoel.com 113
Template Ref: Lab Edition 3 – 14/10/2019 15
Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1011 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 5.05 0.02 63* 4.83 5.12 -0.06 n/a 80* 7.33 6.97 0.04 100 7.42 6.36 0.12 125 7.17 5.03 0.32 0.25 160 6.75 4.74 0.34 200 6.77 4.35 0.45 250 6.80 3.81 0.63 0.60 315 6.65 3.44 0.76 400 6.46 3.07 0.93 500 5.63 2.83 0.96 0.95 630 5.00 2.57 1.03 800 5.22 2.68 0.99 1000 5.79 2.92 0.92 0.95 1250 5.75 2.84 0.97 1600 5.33 2.70 0.99 2000 4.93 2.56 1.01 1.00 2500 4.35 2.42 0.98 3150 3.55 2.11 1.02 4000 2.92 1.83 1.06 1.00 5000 2.34 1.55 1.11 6300* 1.60 1.17 1.14 8000* 1.30 0.99 1.15 n/a 10000* 0.93 0.75 1.19 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature: Mounting
Coloured
Sample Description: Sample Area: Chamber Volume:
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Client: J & C Joel Ltd
Room:
with Sample:
Method:
Cavity From Wall
Test 15 Class A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

Acoustic Test Report - Absorption

Absorption Class: A

Fabric: Coloured Wool Serge

Fullness: 100% Cavity from Wall: 350mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 25 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J & C Joel Ltd

Sound Absorption Coefficient

www.jcjoel.com 114
Template Ref: Lab Edition 3 – 14/10/2019 16
Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 56 %RH Pressure: 1010 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 4.91 0.05 63* 4.83 4.95 -0.03 n/a 80* 7.33 6.01 0.16 100 7.42 5.88 0.19 125 7.17 4.69 0.40 0.35 160 6.75 4.42 0.42 200 6.77 4.01 0.55 250 6.80 3.80 0.63 0.65 315 6.65 3.42 0.77 400 6.46 3.25 0.83 500 5.63 3.02 0.83 0.90 630 5.00 2.63 0.98 800 5.22 2.72 0.96 1000 5.79 2.87 0.95 1.00 1250 5.75 2.72 1.05 1600 5.33 2.65 1.03 2000 4.93 2.55 1.02 1.00 2500 4.35 2.32 1.08 3150 3.55 2.01 1.15 4000 2.92 1.73 1.24 1.00 5000 2.34 1.50 1.23 6300* 1.60 1.14 1.26 8000* 1.30 0.95 1.38 n/a 10000* 0.93 0.72 1.49 0.90 Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Sample: Temperature: Mounting
Coloured
Sample Description: Sample Area: Chamber Volume: Test
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 30/11/2020
Room:
with
Method:
Wool Serge - Single Layer - 100% Fullness (Approx. Weight 500g/m²) - 350mm Cavity From Wall
16
A
Data Sheet 16
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Calculated to EN ISO 11654:1997

Showcase

FBN Rehearsal Studios - Wool Serge 565 (WS090) 115
Velvet
Product Countess Page 118 Duchess 123 Queen 129 Empress 132 Coliseum 137 Sowerby 142

Countess

Our most popular cotton velvet, manufactured using open-end pile yarn to create a hard-wearing fabric. DFR finish available upon request.

100% Fullness Wall Cavity Class SAC Classification Page 50% 100% 350mm 100mm 350mm 100mm 50% C C C C 0.75 0.70 0.75 0.60 122 121 120 119 VEL032 Holly Width: 122cm / 48” FR Certification: BS5867, M1, EN13773, NFPA 701, IMO Weight: 375 g/m2 Custom Dye Available* Approx Roll Length: 55m / 180ft FR Rating: NDFR Colours Available 35 VEL008 VEL027 VEL016 VEL007 VEL020 VEL026 VEL015 VEL003 VEL253 VEL028 VEL001 VEL006 VEL019 VEL033 VEL254 VEL002 VEL018 VEL031 VEL269 VEL034 VEL255 VEL025 VEL009 VEL030 VEL024 VEL004 VEL012 VEL029 VEL106 VEL011 VEL023 VEL022 VEL010 VEL017 Damson Sky Mocha Maroon Ginger Jade Fawn Plum Sunset Mallard Black Mulberry Amber New Bottle Graphite Port Gold Leaf Pewter Scarlet Aubergine Slate Purple Thyme Silver Raspberry Midnight Onyx Pearl White Oxford Chocolate Cognac Marine Mink *CUSTOM DYE price on application, 4 wk lead time, MOQ of 400m Fabric Thickness: 1.35 mm *APPROX PILE HEIGHT - 2.10mm

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Countess

Fullness: 50% Cavity from Wall: 100mm

Confidential

Data Sheet 28

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 20/05/2014

Sample D escription: Countess – Single Layer – 50% fullness (Approx. weight 375g/m²) – 100mm cavity from wall Mounting Method: G-100

Area: 9 m2

Volume: 300 m3

Test 30

www.jcjoel.com 119
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 19.1 °C Humidity: 60 %RH Pressure: 1001mbar
with Sample:
Sample
Chamber
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.70-0.07 63*5.404.730.14n/a 80*6.566.070.07 100 7.577.59-0.00 125 7.116.260.100.10 160 6.425.560.13 200 7.125.500.22 250 7.075.150.280.30 315 6.844.460.42 400 6.463.870.56 500 5.453.130.730.70 630 4.962.870.79 800 5.472.920.86 1000 5.913.090.830.85 1250 5.592.920.88 1600 5.062.890.80 2000 4.752.760.810.80 2500 4.342.630.80 3150 3.642.330.82 4000 3.092.020.900.85 5000 2.441.730.88 6300*1.791.380.85 8000*1.511.180.92n/a 10000*1.060.831.30
Class
Calculated to EN ISO
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
 0.60(MH)
C
11654:1997 NRC 0.65 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Countess

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 27

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014 Empty

Room with Sample:

Sample D escription: Countess – Single Layer – 50% fullness (Approx. weight 375g/m²) – 350mm cavity from wall

Mounting Method: G-350 Sample Area: 9 m2 Chamber Volume: 300 m3

Test 29

Calculated to EN ISO 11654:1997 NRC 0.75 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003

www.jcjoel.com 120
Confidential
Temperature: 19.0 °C Humidity:
%RH Pressure: 999mbar
Room:
62
Temperature:
°C Humidity:
Pressure:
19.1
60 %RH
1001mbar
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.73-0.07 63*5.404.450.21n/a 80*6.565.720.12 100 7.576.880.07 125 7.115.600.200.20 160 6.424.710.30 200 7.124.510.44 250 7.074.190.520.55 315 6.843.760.64 400 6.463.560.68 500 5.453.180.700.70 630 4.962.980.72 800 5.472.970.83 1000 5.913.030.870.85 1250 5.592.920.88 1600 5.062.820.84 2000 4.752.700.860.85 2500 4.342.540.87 3150 3.642.250.90 4000 3.092.030.890.90 5000 2.441.700.93 6300*1.791.330.99 8000*1.511.151.04n/a 10000*1.060.841.22
Class C
T1, empty
T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
 0.75(H)
room reverberation time

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Countess

Fullness: 100% Cavity from Wall: 100mm

Confidential

Data Sheet 29

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 20/05/2014

Sample D escription: Countess – Single Layer – 100% fullness (Approx. weight 375g/m²) – 100mm cavity from wall

Method: G-100

Area: 9 m2

Volume: 300 m3

Test 31

www.jcjoel.com 121
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 19.2 °C Humidity: 60 %RH Pressure: 1001mbar
Sample
Chamber
with Sample:
Mounting
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.59-0.05 63*5.404.510.20n/a 80*6.565.960.08 100 7.576.670.10 125 7.115.780.170.15 160 6.425.290.18 200 7.125.200.28 250 7.074.800.360.40 315 6.843.910.59 400 6.463.530.69 500 5.452.930.850.85 630 4.962.660.94 800 5.472.770.96 1000 5.912.940.920.95 1250 5.592.830.94 1600 5.062.770.88 2000 4.752.640.900.90 2500 4.342.480.92 3150 3.642.230.93 4000 3.091.960.990.95 5000 2.441.700.93 6300*1.791.360.91 8000*1.511.170.97n/a 10000*1.060.831.31
Class C Calculated to EN ISO 11654:1997 NRC 0.75 Calculated
C
Denotes
by BS EN ISO
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
 0.70(MH)
to ASTM
423-01 *
frequencies outside the range covered
354:2003

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Countess

Fullness: 100% Cavity from Wall: 350mm

Confidential

Data Sheet 30

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014

Sample D escription: Countess – Single Layer – 100% fullness (Approx. weight 375g/m²) – 350mm cavity from wall Mounting Method: G-350

Area: 9 m2

Volume: 300 m3

Test 32

www.jcjoel.com 122
Empty
Temperature: 19.0 °C Humidity:
%RH Pressure: 999mbar Room
Temperature: 19.2 °C Humidity:
%RH Pressure: 1001mbar
Room:
62
with Sample:
60
Sample
Chamber
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.990.07 63*5.404.630.17n/a 80*6.565.710.12 100 7.576.850.07 125 7.115.460.230.20 160 6.424.500.36 200 7.124.410.46 250 7.074.380.470.50 315 6.843.830.62 400 6.463.480.71 500 5.453.140.730.75 630 4.962.770.86 800 5.472.830.92 1000 5.912.910.940.95 1250 5.592.760.99 1600 5.062.730.91 2000 4.752.540.980.95 2500 4.342.410.99 3150 3.642.141.03 4000 3.091.891.091.00 5000 2.441.611.11 6300*1.791.340.97 8000*1.511.131.14n/a 10000*1.060.801.56
0.75(H) Class C Calculated to EN
NRC
Calculated
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t

ISO 11654:1997
0.80
to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003

Similar to Countess, Duchess is manufactured using open-end pile yarn, woven into a heavier, more robust cloth.

Duchess
100% Fullness Wall Cavity Class SAC Classification Page 50% 100% 350mm 100mm 350mm 100mm 50% C B B A 0.90 0.80 0.85 0.65 127 126 125 124 Royal Court Theatre, UK - Duchess (VELH005) Colours Available 10 VELH044 Claret VELH048 Navy Width: 140cm / 55” FR Certification: BS5867 Weight: 520 g/m2 Custom Dye Available* Approx Roll Length: 40m / 131ft FR Rating: NDFR *CUSTOM DYE price on application, 4 wk lead time, MOQ of 400m VELH045 VELH043 VELH049 VELH042 VELH040 VELH051 VELH046 VELH047 Brick Red Bottle True Gold Black Aubergine Purple Royal Fabric Thickness: 1.95 mm *APPROX PILE HEIGHT - 2.50mm

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Duchess

Fullness: 50% Cavity from Wall: 100mm

Confidential

Data Sheet 17

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014

Sample D escription: Duchess – Single Layer – 50% fullness (Approx. weight 520g/m²) – 100mm cavity from wall Mounting Method: G-100

Area: 9 m2

Volume: 300 m3

Test

124
www.jcjoel.com
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 18.9 °C Humidity:
%RH Pressure: 999mbar
Sample
Chamber
with Sample:
62
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.000.07 63*5.405.230.03n/a 80*6.566.030.07 100 7.576.940.06 125 7.116.370.090.10 160 6.425.530.14 200 7.125.420.24 250 7.074.890.340.35 315 6.844.060.54 400 6.463.530.69 500 5.452.970.830.80 630 4.962.720.89 800 5.472.790.95 1000 5.912.850.980.95 1250 5.592.900.89 1600 5.062.770.88 2000 4.752.650.900.90 2500 4.342.540.88 3150 3.642.260.90 4000 3.092.040.890.90 5000 2.441.720.92 6300*1.791.350.97 8000*1.511.171.03n/a 10000*1.060.861.17
T1, empty room reverberation
T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
19
 0.65(MH) Class C Calculated to EN ISO 11654:1997 NRC 0.75 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003
time

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Duchess

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 18

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 20/05/2014

Sample D escription: Duchess – Single Layer – 50% fullness (Approx. weight 520g/m²) – 350mm cavity from wall

Method: G-350

Area: 9 m2

Volume: 300 m3

Test

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

www.jcjoel.com 125
Confidential
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 18.9 °C Humidity: 62 %RH Pressure: 999mbar
Sample
Chamber
with Sample:
Mounting
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.900.09 63*5.405.100.06n/a 80*6.565.510.16 100 7.575.960.19 125 7.115.400.240.25 160 6.424.490.36 200 7.124.300.50 250 7.074.000.580.60 315 6.843.580.72 400 6.463.390.76 500 5.452.960.830.85 630 4.962.680.92 800 5.472.740.98 1000 5.912.850.980.95 1250 5.592.810.95 1600 5.062.720.92 2000 4.752.580.950.95 2500 4.342.450.96 3150 3.642.190.98 4000 3.091.941.031.00 5000 2.441.661.03 6300*1.791.311.10 8000*1.511.151.11n/a 10000*1.060.851.24
0.85(H)
20

Class B Calculated to EN ISO 11654:1997 NRC 0.85 Calculated to ASTM C 423-01
T1, empty
T2, room reverberation
sample
Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
room reverberation time
time with
#

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Duchess

Fullness: 100% Cavity from Wall: 100mm

Confidential

Data Sheet 20

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014

Sample D escription: Duchess – Single Layer – 100% fullness (Approx. weight 520g/m²) – 100mm cavity from wall Mounting Method: G-100

Area: 9 m2

Volume: 300 m3

Test 22

126
www.jcjoel.com
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 18.9 °C Humidity: 62 %RH Pressure: 999mbar
Sample
Chamber
with Sample:
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.335.41-0.01 63*5.405.040.07n/a 80*6.566.000.08 100 7.576.790.08 125 7.115.940.150.15 160 6.425.200.20 200 7.124.850.35 250 7.074.500.440.50 315 6.843.780.64 400 6.463.360.77 500 5.452.890.880.90 630 4.962.600.99 800 5.472.721.00 1000 5.912.910.941.00 1250 5.592.741.00 1600 5.062.700.93 2000 4.752.620.920.90 2500 4.342.500.91 3150 3.642.220.95 4000 3.091.990.960.95 5000 2.441.671.01 6300*1.791.350.97 8000*1.511.141.15n/a 10000*1.060.821.47
0.80(H) Class B
EN ISO
0.80
C 423-01
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t

Calculated to
11654:1997 NRC
Calculated to ASTM
* Denotes frequencies outside the range covered by BS EN ISO 354:2003

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Duchess

Fullness: 100% Cavity from Wall: 350mm

Confidential

Data Sheet 19

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 20/05/2014

D escription: Duchess – Single Layer – 100% fullness (Approx. weight 520g/m²) – 350mm cavity from wall

Method: G-350

Area: 9 m2

Volume: 300 m3

Test 21

www.jcjoel.com 127
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 18.9 °C Humidity: 62 %RH Pressure: 999mbar
Mounting
Sample
Chamber
with Sample:
Sample
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.870.10 63*5.404.940.09n/a 80*6.565.800.11 100 7.576.000.19 125 7.115.310.260.30 160 6.424.420.38 200 7.124.370.48 250 7.073.980.590.60 315 6.843.590.71 400 6.463.180.86 500 5.452.900.870.90 630 4.962.660.94 800 5.472.631.06 1000 5.912.771.031.00 1250 5.592.641.08 1600 5.062.551.05 2000 4.752.471.051.00 2500 4.342.341.06 3150 3.642.121.06 4000 3.091.931.051.00 5000 2.441.611.13 6300*1.791.281.19 8000*1.511.111.27n/a 10000*1.060.801.64  0.90 Class A Calculated to EN ISO 11654:1997 NRC 0.90 Calculated to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t

Showcase

128
Elizabeth Sneddon Theatre, South Africa - Duchess (VELH004)

High-end ring-spun yarns, woven into a luxurious velvet. Queen has the longest pile in our range which creates a bright and deep colour.

Queen
Fullness Wall Cavity Class SAC Classification Page 50% 350mm 350mm 100% B A 0.90 0.85 131 130 Width: 150cm / 59” FR Certification: BS5867, NFPA 701 Weight: 565 g/m2 Custom Dye Available* Approx Roll Length: 30m / 98ft FR Rating: NDFR Colours Available 8 *CUSTOM DYE price on application, 4 wk lead time, MOQ of 240m VEL165 VEL160 VEL164 VEL163 VEL162 VEL167 VEL168 VEL166 Wine Angel Flame Scarlet Gold Navy Royal Black Natural Fabric Thickness: 2.16 mm *APPROX PILE HEIGHT - 2.90mm
E-DA World Theme ParK, Taiwan - Queen (VEL160)

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Queen

Fullness: 50% Cavity from Wall: 350mm

Client:

Test

Report No:

Test Report No: C/24281/T01

Page 14 of 38

Date: 13/02/2019

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

J & C Joel Ltd

Method:

- Single Layer - 50% fullness (Approx. weight 565g/m2) 350mm cavity from wall

Sound Absorption Coefficient

B

www.jcjoel.com 130
Client:
Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.1 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.810.04 63* 5.395.040.07n/a 80* 7.086.400.08 100 9.007.590.11 125 7.305.850.190.25 160 6.604.500.39 200 6.864.060.55 250 7.223.900.640.65 315 6.993.510.77 400 6.363.340.78 500 5.643.070.810.80 630 5.092.920.80 800 5.102.720.94 1000 5.742.890.940.95 1250 5.632.810.97 1600 5.182.670.97 2000 4.762.501.011.00 2500 4.222.301.03 3150 3.351.931.11 4000 2.591.581.211.00 5000 2.041.271.42 6300* 1.390.931.65 8000* 1.140.801.63n/a 10000* 0.800.611.64 0.85(H) Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature:
Sample
Sample Area: Chamber Volume: Test 5 Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet
J & C
Room:
with Sample:
Mounting
Queen
Description:
4
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sound Absorption Coefficient C/24281/T01
Page 14 of 38
Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 15.1 °C Humidity: 45 %RH Pressure: 1002 G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.810.04 63* 5.395.040.07n/a 80* 7.086.400.08 100 9.007.590.11 125 7.305.850.190.25 160 6.604.500.39 200 6.864.060.55 250 7.223.900.640.65 315 6.993.510.77 400 6.363.340.78 500 5.643.070.810.80 630 5.092.920.80 800 5.102.720.94 1000 5.742.890.940.95 1250 5.632.810.97 1600 5.182.670.97 2000 4.762.501.011.00 2500 4.222.301.03 3150 3.351.931.11 4000 2.591.581.211.00 5000 2.041.271.42 6300* 1.390.931.65 8000* 1.140.801.63n/a 10000* 0.800.611.64 0.85(H) Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Queen
Sample Description: Sample Area: Chamber Volume: Test 5 Class B T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet 4 The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 200 315 400 500 630 1000 1250 1600 2000 2500 3150 5000 Absorption Coefficient Frequency, Hz
This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited
Method:
- Single Layer - 50% fullness (Approx. weight 565g/m2) 350mm cavity from wall

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Queen

Fullness: 100% Cavity from Wall: 350mm

Test Report No:

Test Report No: C/24281/T01

Page 13 of 38

Page 13 of 38

Date: 13/02/2019

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Mounting Method:

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

- Single Layer - 100% fullness (Approx. weight 565g/m2) 350mm cavity from wall

- Single Layer - 100% fullness (Approx. weight 565g/m2) 350mm cavity from wall

Sound Absorption Coefficient

Sound Absorption Coefficient

# Practical absorption coefficient, BS EN ISO 11654:1997

www.jcjoel.com 131
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.2 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.800.04 63* 5.394.940.09n/a 80* 7.086.560.06 100 9.006.680.21 125 7.305.490.250.30 160 6.604.400.41 200 6.864.080.54 250 7.223.840.660.65 315 6.993.430.81 400 6.363.220.84 500 5.642.960.880.90 630 5.092.750.91 800 5.102.621.01 1000 5.742.761.021.00 1250 5.632.711.04 1600 5.182.541.08 2000 4.762.341.161.00 2500 4.222.141.21 3150 3.351.831.27 4000 2.591.561.261.00 5000 2.041.281.39 6300* 1.390.921.72 8000* 1.140.791.74n/a 10000* 0.800.601.80 0.90 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature:
Queen
Sample
Sample Area: Chamber Volume: Test 4 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet 3
Room:
with Sample:
Mounting Method:
Description:
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
C/24281/T01
Client:
C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.2 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.800.04 63* 5.394.940.09n/a 80* 7.086.560.06 100 9.006.680.21 125 7.305.490.250.30 160 6.604.400.41 200 6.864.080.54 250 7.223.840.660.65 315 6.993.430.81 400 6.363.220.84 500 5.642.960.880.90 630 5.092.750.91 800 5.102.621.01 1000 5.742.761.021.00 1250 5.632.711.04 1600 5.182.541.08 2000 4.762.341.161.00 2500 4.222.141.21 3150 3.351.831.27 4000 2.591.561.261.00 5000 2.041.281.39 6300* 1.390.921.72 8000* 1.140.791.74n/a 10000* 0.800.601.80 0.90 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample
J &
NRC Empty Room: Temperature:
Temperature:
Sample Description: Sample Area: Chamber Volume: Test 4 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019
Sheet
Laboratory Measurement of
Incidence Sound Absorption
EN
354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Room with Sample:
Queen
Data
3 The
Random
generally to BS
ISO

Empress is our Queen velvet but with an M1 finish. It is manufactured using high-end, ring-spun yarns, which provide a vibrant and rich colour.

Empress
Manufacture of Box Pelmets - Peth Theatre, Scotland - Empress (VEL175) Fullness Wall Cavity Class SAC Classification Page 50% 100mm B 100mm 100% A 0.90 0.80 134 133 VEL172 Angel Flame Width: 150cm / 59” FR Certification: BS5867, M1 Weight: 620 g/m2 Custom Dye Available* Approx Roll Length: 30m / 98ft FR Rating: NDFR Colours Available 8 *CUSTOM DYE price on application, 4 wk lead time, MOQ of 240m VEL175 VEL174 VEL171 VEL173 VEL177 VEL178 VEL176 Wine Scarlet Gold Navy Royal Black Natural Fabric Thickness: 2.68 mm *APPROX PILE HEIGHT - 2.90mm 350mm 100% A 0.95 50% 350mm A 0.90 136 135

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: Empress

Fullness: 50% Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 10 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 133

Acoustic Test Report - Absorption

Absorption Class: A

Calculated

Fabric: Empress

Fullness: 50% Cavity from Wall: 350mm

Test Report No: C/24281/T01

Page 12 of 38

Page 12 of 38

Date: 13/02/2019

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Client:

with Sample: Data Sheet 2

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Room: 19/01/2019

Method:

J & Absorp Coeff α s

- Single Layer - 50% fullness (Approx. weight 620g/m2) 350mm cavity from wall

Sample Description: Sample Area: Chamber Volume: Test 3 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019 Data Sheet 2 The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz

www.jcjoel.com 134
to EN ISO 11654:1997
Client:
C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.3 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.720.06 63* 5.394.950.09n/a 80* 7.086.190.11 100 9.007.060.17 125 7.305.700.210.25 160 6.604.750.32 200 6.864.150.52 250 7.223.770.690.65 315 6.993.420.81 400 6.363.270.81 500 5.643.000.850.85 630 5.092.770.90 800 5.102.591.04 1000 5.742.840.971.00 1250 5.632.780.99 1600 5.182.601.03 2000 4.762.461.041.00 2500 4.222.251.08 3150 3.351.931.12 4000 2.591.591.201.00 5000 2.041.281.40 6300* 1.390.931.67 8000* 1.140.811.58n/a 10000* 0.800.601.82 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty
Temperature: Room
Temperature: Mounting
Sample
Sample Area: Chamber Volume: Test 3 Class
This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited T1 sec T2 sec Freq Hz
Empress - Single Layer - 50% fullness (Approx. weight 620g/m2) 350mm cavity from wall
Description:
A
Sound Absorption Coefficient
Test Report No:
C/24281/T01
Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.3 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.720.06 63* 5.394.950.09n/a 80* 7.086.190.11 100 9.007.060.17 125 7.305.700.210.25 160 6.604.750.32 200 6.864.150.52 250 7.223.770.690.65 315 6.993.420.81 400 6.363.270.81 500 5.643.000.850.85 630 5.092.770.90 800 5.102.591.04 1000 5.742.840.971.00 1250 5.632.780.99 1600 5.182.601.03 2000 4.762.461.041.00 2500 4.222.251.08 3150 3.351.931.12 4000 2.591.591.201.00 5000 2.041.281.40 6300* 1.390.931.67 8000* 1.140.811.58n/a 10000* 0.800.601.82 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
J & C
Method:
Empress
Sound Absorption Coefficient

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Empress

Fullness: 100% Cavity from Wall: 100mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 9 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 135

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Empress

Fullness: 100% Cavity from Wall: 350mm

Data Sheets 1 to 22

Data Sheet 1

Test Report No: C/24281/T01

Test Report No: C/24281/T01

Page 11 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Sample Area: Chamber Volume:

T1 sec T2 sec Freq Hz Absorp Coeff α s Empty

J & C Joel Ltd

Class

1.50

1.40

Description: 0.70

1.30

1.20

1.10

1.00

0.90

0.80

Sound Absorption Coefficient

Sound Absorption Coefficient

1.50

1.40

1.30

Room: 0.20

with Sample: 0.30

Method: 0.40

1.20

1.10

The Laboratory Measurement of Random Incidence Sound Absorption generally to NRC

Absorption Coefficient Frequency, Hz

1.00

0.90

Empress - Single Layer - 100% fullness (Approx. weight 620g/m2) 350mm cavity from wall 0.50

Absorption Coefficient Frequency, Hz

BS 0.00

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997

ISO 0.10

0.80

0.70

1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

0.60

www.jcjoel.com 136
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.5 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.640.08 63* 5.394.840.12n/a 80* 7.086.200.11 100 9.007.350.14 125 7.305.230.300.30 160 6.604.230.46 200 6.864.040.55 250 7.223.600.760.70 315 6.993.430.81 400 6.363.210.84 500 5.643.010.850.90 630 5.092.700.95 800 5.102.561.06 1000 5.742.681.081.00 1250 5.632.671.07 1600 5.182.451.16 2000 4.762.341.161.00 2500 4.222.151.20 3150 3.351.841.27 4000 2.591.521.371.00 5000 2.041.251.52 6300* 1.390.951.57 8000* 1.140.801.70n/a 10000* 0.800.601.86 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 19/01/2019 Data Sheet 1
EN
354:2003 Sample Area: Chamber Volume: Test 2 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Temperature: Mounting
Data Sheets 1 to 22 Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997
Page 11 of 38 Date: 13/02/2019
This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited
Client:
Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.5 °C Humidity: 45 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.964.640.08 63* 5.394.840.12n/a 80* 7.086.200.11 100 9.007.350.14 125 7.305.230.300.30 160 6.604.230.46 200 6.864.040.55 250 7.223.600.760.70 315 6.993.430.81 400 6.363.210.84 500 5.643.010.850.90 630 5.092.700.95 800 5.102.561.06 1000 5.742.681.081.00 1250 5.632.671.07 1600 5.182.451.16 2000 4.762.341.161.00 2500 4.222.151.20 3150 3.351.841.27 4000 2.591.521.371.00 5000 2.041.251.52 6300* 1.390.951.57 8000* 1.140.801.70n/a 10000* 0.800.601.86 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 19/01/2019
Temperature:
Sample
Test 2 NRC
A 0.00
Room: 0.10
Room 0.20
with Sample: 0.30
Temperature: 0.40
Mounting Method: 0.50
Empress - Single Layer - 100% fullness (Approx. weight 620g/m2) 350mm cavity from wall 0.60

The West End Collection - Coliseum

A knitted, synthetic based velvet collection that imitates traditional velvets. Developed to incorporate a longer pile, the West End velvets provide a rich sheen to enhance the colour and overall appearance, without compromising the hardwearing properties.

100% Fullness Wall Cavity Class SAC Classification Page 50% 100% 350mm 100mm 350mm 100mm 50% B B A A 0.90 0.90 0.85 0.80 127 126 125 124
-
Coliseum
VEL930/4 Plum VEL930/6 Bottle VEL930/2 VEL930/5 VEL930/8 VEL930/9 VEL930/3 VEL930/1 Burgundy Grey Gold Navy Royal Black Width: 150cm / 59” FR Certification: BS5867, NFPA 701, EN13773 Weight: 500 g/m2 Custom Dye Available* Approx Roll Length: 55m / 180ft FR Rating: IFR Colours Available 8 *MOQ of 400m Fabric Thickness: 1.71 mm
Thammasat University, Thailand
The West End Collection -
(VEL930/2)

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: The West End Collection - Coliseum

Fullness: 50% Cavity from Wall: 100mm

Data Sheet 13

Test Report No: 24694-SRL-RP-XT-001-P1

Page 22 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

See SRL report 24694-SRL-RP-XT-001-P1 for full details

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Test

Sound Absorption Coefficient

B

www.jcjoel.com 138
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.6 °C Humidity: 66 %RH Pressure: 997 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.834.89-0.01 63* 5.225.210.00n/a 80* 7.657.270.04 100 7.546.820.07 125 7.756.280.160.15 160 6.515.050.24 200 6.934.820.34 250 6.804.230.480.50 315 6.683.690.65 400 6.353.230.81 500 5.572.770.970.95 630 4.922.501.05 800 4.942.600.98 1000 5.402.760.950.95 1250 5.542.880.89 1600 5.122.770.89 2000 4.792.690.870.90 2500 4.392.480.94 3150 3.742.240.96 4000 3.172.010.970.95 5000 2.591.760.97 6300* 1.951.381.12 8000* 1.571.181.11n/a 10000* 1.110.911.03 0.80(H) Calculated to EN ISO 11654:1997 0.80 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: The
Sample Description: Sample Area: Chamber Volume:
T1 sec T2 sec Freq Hz Absorp Coeff α s 21/08/2020
West End Collection - Coliseum - Single Layer - 50% Fullness (Approx. Weight 500g/m²)
15 Class
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
100mm cavity from wall

Acoustic Test Report - Absorption

Absorption Class: B

Calculated to EN ISO 11654:1997

Fabric: The West End Collection - Coliseum

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 14

Test Report No: 24694-SRL-RP-XT-001-P1

Page 23 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

See SRL report 24694-SRL-RP-XT-001-P1 for full details

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sound Absorption Coefficient

www.jcjoel.com 139
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.6 °C Humidity: 66 %RH Pressure: 997 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.834.840.00 63* 5.224.890.07n/a 80* 7.656.610.11 100 7.546.580.10 125 7.755.170.340.30 160 6.514.310.42 200 6.934.200.50 250 6.803.760.640.60 315 6.683.600.69 400 6.353.310.77 500 5.573.100.770.80 630 4.922.740.87 800 4.942.610.97 1000 5.402.780.940.95 1250 5.542.760.97 1600 5.122.690.95 2000 4.792.560.970.95 2500 4.392.430.98 3150 3.742.181.02 4000 3.171.931.081.00 5000 2.591.691.09 6300* 1.951.381.12 8000* 1.571.171.15n/a 10000* 1.110.881.23 0.85(H) Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
The
Sample Description: Sample Area: Chamber Volume:
Class
T1 sec T2 sec Freq Hz Absorp Coeff α s 21/08/2020
Method:
West End Collection - Coliseum - Single Layer - 50% Fullness (Approx. Weight 500g/m²)
Test 16
B
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
350mm cavity from wall

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: The West End Collection - Coliseum

Fullness: 100% Cavity from Wall: 100mm

Data Sheet 15

Test Report No: 24694-SRL-RP-XT-001-P1

Page 24 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

See SRL report 24694-SRL-RP-XT-001-P1 for full details

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sound Absorption Coefficient

www.jcjoel.com 140
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.6 °C Humidity: 66 %RH Pressure: 997 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.834.90-0.02 63* 5.225.070.03n/a 80* 7.657.240.04 100 7.546.850.07 125 7.755.480.290.20 160 6.514.750.30 200 6.934.360.46 250 6.803.840.610.60 315 6.683.520.72 400 6.353.090.89 500 5.572.760.980.95 630 4.922.561.00 800 4.942.580.99 1000 5.402.790.930.95 1250 5.542.830.93 1600 5.122.770.89 2000 4.792.630.920.90 2500 4.392.460.96 3150 3.742.230.97 4000 3.171.981.011.00 5000 2.591.731.02 6300* 1.951.381.12 8000* 1.571.181.11n/a 10000* 1.110.930.90 0.90 Calculated to EN ISO 11654:1997 0.85 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: The
Sample Description: Sample Area: Chamber Volume:
West End Collection - Coliseum - Single Layer - 100% Fullness (Approx. Weight 500g/m²)
T1 sec T2 sec Freq Hz Absorp Coeff α s 21/08/2020
Test 17 Class A
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
100mm cavity from wall

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: The West End Collection - Coliseum

Fullness: 100% Cavity from Wall: 350mm

Data Sheet 16

Test Report No: 24694-SRL-RP-XT-001-P1

Page 25 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

See SRL report 24694-SRL-RP-XT-001-P1 for full details

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Sound Absorption Coefficient

www.jcjoel.com 141
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.6 °C Humidity: 66 %RH Pressure: 997 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.834.780.01 63* 5.224.970.05n/a 80* 7.656.360.14 100 7.546.480.12 125 7.755.210.340.30 160 6.514.400.39 200 6.934.200.50 250 6.803.680.670.65 315 6.683.440.76 400 6.353.260.80 500 5.572.940.860.85 630 4.922.680.91 800 4.942.580.99 1000 5.402.691.001.00 1250 5.542.671.04 1600 5.122.571.04 2000 4.792.451.071.00 2500 4.392.341.07 3150 3.742.101.12 4000 3.171.881.151.00 5000 2.591.671.13 6300* 1.951.361.18 8000* 1.571.141.27n/a 10000* 1.110.891.16 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 21/08/2020
Sample Area: Chamber Volume: Test 18 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room
Sample: Temperature:
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
with
Mounting Method: The West End Collection - Coliseum - Single Layer - 100% Fullness (Approx. Weight 500g/m²)
350mm cavity from wall

The Pennine Collection - Sowerby

A premier IFR velvet collection, manufactured using 100% Trevira CS yarns for both the base layer and pile. The velvets are first manufactured as a ‘V’ weave double-layered cloth, which is then cut to create the tightly packed, laid pile for creating superior fabrics.

Fullness Wall Cavity Class SAC Classification Page 50% 350mm 350mm 100% A A 0.95 0.95 130 129
Caudan Arts Centre, Mauritius - The Pennine Collection - Sowerby (Custom Dye)
Width: 140cm / 55” FR Certification: BS5867, M1, B1, IMO, EN13773 Weight: 550 g/m2 Custom Dye Available* Approx Roll Length: 30m / 98ft FR Rating: IFR Colours Available 10 Fabric Thickness: 2.51 mm VEL700/3 Plum VEL700/8 Bottle *CUSTOM DYE price on application, 4 wk lead time, MOQ 30m VEL700/13 VEL700/2 VEL700/6 VEL700/12 VEL700/5 VEL700/4 VEL700/7 VEL700/1 Burgundy Red Graphite Gold Slate Navy Royal Black *APPROX PILE HEIGHT - 2.70mm

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: The Pennine Collection - Sowerby

Fullness: 50% Cavity from Wall: 350mm

Sound

Test Report No: C/24281/T01

Page 16 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 143
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.4 °C Humidity: 44 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.96 4.76 0.05 63* 5.39 5.00 0.08 n/a 80* 7.08 6.22 0.11 100 9.00 7.29 0.14 125 7.30 5.48 0.25 0.30 160 6.60 4.30 0.44 200 6.86 3.81 0.63 250 7.22 3.63 0.75 0.75 315 6.99 3.36 0.84 400 6.36 3.20 0.85 500 5.64 3.06 0.82 0.85 630 5.09 2.70 0.95 800 5.10 2.64 1.00 1000 5.74 2.78 1.01 1.00 1250 5.63 2.74 1.01 1600 5.18 2.54 1.08 2000 4.76 2.37 1.12 1.00 2500 4.22 2.19 1.14 3150 3.35 1.85 1.23 4000 2.59 1.55 1.27 1.00 5000 2.04 1.25 1.47 6300* 1.39 0.92 1.68 8000* 1.14 0.78 1.77 n/a 10000* 0.80 0.58 2.04 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Sowerby
Sample Description: Sample Area: Chamber Volume: Test 7 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019
The Laboratory
BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Velvet - Single Layer - 50% fullness (Approx. weight 550g/m2) 350mm cavity from wall
Data Sheet 6
Measurement of Random Incidence Sound Absorption generally to
Absorption
Coefficient

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: The Pennine Collection - Sowerby

Fullness: 100% Cavity from Wall: 350mm

Test Report No: C/24281/T01

Page 15 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Laboratory Measurement of Random Incidence Sound Absorption generally to BS

Velvet - Single Layer- 100% fullness (Approx. weight 550g/m2) 350mm cavity from wall

Method:

Sound Absorption Coefficient

www.jcjoel.com 144
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.3 °C Humidity: 44 %RH Pressure: 1002 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.96 4.56 0.10 63* 5.39 5.02 0.08 n/a 80* 7.08 6.02 0.14 100 9.00 6.99 0.17 125 7.30 5.52 0.24 0.30 160 6.60 4.31 0.44 200 6.86 3.94 0.59 250 7.22 3.71 0.71 0.70 315 6.99 3.44 0.81 400 6.36 3.14 0.88 500 5.64 2.88 0.93 0.90 630 5.09 2.74 0.92 800 5.10 2.67 0.97 1000 5.74 2.74 1.04 1.00 1250 5.63 2.62 1.10 1600 5.18 2.49 1.12 2000 4.76 2.35 1.14 1.00 2500 4.22 2.14 1.20 3150 3.35 1.84 1.24 4000 2.59 1.52 1.33 1.00 5000 2.04 1.27 1.39 6300* 1.39 0.93 1.61 8000* 1.14 0.78 1.75 n/a 10000* 0.80 0.58 2.02 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting
Sample Description: Sample Area: Chamber Volume: Test 6 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s 19/01/2019
The
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Sowerby
Data Sheet 5
EN ISO 354:2003
Esplanade Theatre - Pennine Collection - Sowerby (VEL700/CUSTOM) 145
Showcase

Other Fabrics

Product Page 148 Acoustic Molton 154 158 Acoustic Transparent 160 Transition (Digital Print) 8pt Sharkstooth Gauze 162 Digifoam

Acoustic Molton

A Molton that combines great masking properties with excellent acoustic absorption, also known as Calmuc.

Width: 300cm /118” FR Certification: BS5867, M1, B1 Weight: 500 g/m2 Custom Dye N/A Approx Bale Length: 30m / 98ft Colours Available FR Rating: NDFR 2 MOL030 MOL031 Black Natural Fullness Wall Cavity Class SAC Classification Page Flat 50% 350mm 350mm 100mm Flat C C A 0.90 0.65 0.60 151 150 149 100% 350mm 100mm 100% A A 0.95 0.90 153 152
Sample of Acoustic Molton (MOL030)

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Acoustic Molton

Fullness: Flat Cavity from Wall: 100mm

Data Sheet 20

Test Report No: 24766-SRL-RP-XT-001-P1

Page 29 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Room:

Description:

Acoustic Molton - Single Layer - Flat (Approx. Weight 500g/m²) - 100mm Cavity From Wall

www.jcjoel.com 149
Template Ref: Lab Edition 3 – 14/10/2019 20 Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 55 %RH Pressure: 1009 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 5.23 -0.01 63* 4.83 5.51 -0.14 n/a 80* 7.33 7.60 -0.03 100 7.42 6.82 0.06 125 7.17 6.47 0.08 0.10 160 6.75 5.78 0.14 200 6.77 5.59 0.17 250 6.80 5.13 0.26 0.30 315 6.65 4.48 0.40 400 6.46 3.60 0.67 500 5.63 3.19 0.74 0.75 630 5.00 2.83 0.83 800 5.22 2.88 0.85 1000 5.79 3.04 0.85 0.85 1250 5.75 3.08 0.82 1600 5.33 3.00 0.79 2000 4.93 2.95 0.73 0.75 2500 4.35 2.70 0.74 3150 3.55 2.34 0.76 4000 2.92 1.96 0.85 0.80 5000 2.34 1.68 0.82 6300* 1.60 1.22 0.91 8000* 1.30 1.05 0.78 n/a 10000* 0.93 0.77 0.92
Calculated to EN ISO 11654:1997 0.65 Calculated to ASTM C 423-01 v5 30/11/2020
0.60(MH)
Sample Area: Chamber Volume: Test 20 Class C T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Temperature: Mounting
Sample
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 Absorption Coefficient
with Sample:
Method:
Sound

Acoustic Test Report - Absorption

Absorption Class: C

Calculated to EN ISO 11654:1997

Fabric: Acoustic Molton

Fullness: Flat Cavity from Wall: 350mm

Data Sheet 9

Test Report No: C/24281/T01

Page 19 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Room: NRC

Sound Absorption Coefficient

1.30

1.20

1.10

1.00

0.90

0.80

Description: 0.30

Acoustic Molton - Single Layer - flat (Approx. weight 500g/m2) 350mm cavity from wall 0.20

0.70

0.60

with 0.00

Method: 0.10

1.40 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

0.50

0.40

Absorption Coefficient Frequency, Hz

150
www.jcjoel.com
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.5 °C Humidity: 43 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.96 4.87 0.02 63* 5.39 5.02 0.08 n/a 80* 7.08 6.76 0.04 100 9.00 7.44 0.13 125 7.30 6.03 0.16 0.15 160 6.60 5.23 0.22 200 6.86 4.78 0.35 250 7.22 4.43 0.48 0.45 315 6.99 4.00 0.58 400 6.36 3.81 0.58 500 5.64 3.42 0.63 0.60 630 5.09 3.23 0.62 800 5.10 3.05 0.72 1000 5.74 3.14 0.78 0.75 1250 5.63 3.08 0.79 1600 5.18 2.86 0.83 2000 4.76 2.65 0.87 0.85 2500 4.22 2.43 0.89 3150 3.35 2.00 0.99 4000 2.59 1.62 1.09 1.00 5000 2.04 1.30 1.27 6300* 1.39 0.96 1.39 8000* 1.14 0.80 1.52 n/a 10000* 0.80 0.59 1.79 0.65(H) Calculated to EN ISO 11654:1997 0.70 Calculated to ASTM C 423-01 v5 19/01/2019
Sample Area: Chamber Volume: Test 10 Class C T1 sec T2 sec Freq Hz Absorp Coeff α s Empty
Temperature: Room
Sample: Temperature: Mounting
Sample
The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Acoustic Molton

Fullness: 50% Cavity from Wall: 350mm

Data Sheet 8

Test Report No: C/24281/T01

Page 18 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Method:

Molton - Single Layer - 50% fullness (Approx. weight 500g/m2) 350mm cavity from wall

www.jcjoel.com 151
Client:
C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.4 °C Humidity: 43 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.96 4.75 0.05 63* 5.39 4.91 0.10 n/a 80* 7.08 6.53 0.07 100 9.00 7.17 0.15 125 7.30 5.54 0.24 0.25 160 6.60 4.40 0.41 200 6.86 4.05 0.55 250 7.22 3.91 0.64 0.65 315 6.99 3.50 0.78 400 6.36 3.28 0.81 500 5.64 3.01 0.85 0.85 630 5.09 2.69 0.96 800 5.10 2.62 1.01 1000 5.74 2.77 1.01 1.00 1250 5.63 2.77 0.99 1600 5.18 2.58 1.04 2000 4.76 2.38 1.10 1.00 2500 4.22 2.21 1.11 3150 3.35 1.85 1.21 4000 2.59 1.54 1.26 1.00 5000 2.04 1.23 1.49 6300* 1.39 0.91 1.68 8000* 1.14 0.77 1.77 n/a 10000* 0.80 0.59 1.77 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 19/01/2019
J &
Sample Area: Chamber Volume:
Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting
Sample
α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Absorption
Test 9
Acoustic
Description:
Sound
Coefficient

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Acoustic Molton

Fullness: 100% Cavity from Wall: 100mm

Test Report No: 24766-SRL-RP-XT-001-P1

Page 28 of 35

Date: 02/12/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS

www.jcjoel.com 152
Template Ref: Lab Edition 3 – 14/10/2019
Client: J & C Joel Ltd Test Date: 16.4 °C Humidity: 57 %RH Pressure: 1016 mbar 15.7 °C Humidity: 55 %RH Pressure: 1009 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 5.15 5.18 0.00 63* 4.83 5.19 -0.08 n/a 80* 7.33 7.40 -0.01 100 7.42 6.58 0.09 125 7.17 5.33 0.26 0.20 160 6.75 4.99 0.28 200 6.77 4.49 0.41 250 6.80 3.99 0.56 0.60 315 6.65 3.45 0.76 400 6.46 2.84 1.07 500 5.63 2.72 1.03 1.00 630 5.00 2.49 1.10 800 5.22 2.59 1.06 1000 5.79 2.80 1.00 1.00 1250 5.75 2.82 0.98 1600 5.33 2.73 0.97 2000 4.93 2.60 0.98 1.00 2500 4.35 2.40 0.99 3150 3.55 2.14 0.97 4000 2.92 1.82 1.06 1.00 5000 2.34 1.55 1.09 6300* 1.60 1.18 1.06 8000* 1.30 1.00 1.04 n/a 10000* 0.93 0.76 1.01 0.90 Calculated to EN ISO 11654:1997 0.90 Calculated to ASTM C 423-01 v5 30/11/2020 Data
19
Sheet 19
Sample Area: Chamber Volume: Test 19 Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Acoustic Molton
Layer
Fullness (Approx.
500g/m²)
Cavity
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Absorption Coefficient
EN ISO 354:2003
- Single
- 100%
Weight
- 100mm
From Wall
Sound

Acoustic Test Report - Absorption

Absorption Class: A

Calculated to EN ISO 11654:1997

Fabric: Acoustic Molton

Fullness: 100% Cavity from Wall: 350mm

Data Sheet 7

Test Report No: C/24281/T01

Page 17 of 38

Date: 13/02/2019

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Molton - Single Layer - 100% fullness (Approx. weight 500 g/m2) 350mm cavity from wall

www.jcjoel.com 153
Client: J & C Joel Ltd Test Date: 17.0 °C Humidity: 46 %RH Pressure: 1002 mbar 15.4 °C Humidity: 44 %RH Pressure: 1001 mbar G - 350 9 m² 300 m³ Practical Absorp Coeff # 50* 4.96 4.66 0.07 63* 5.39 4.95 0.09 n/a 80* 7.08 6.47 0.07 100 9.00 7.41 0.13 125 7.30 5.44 0.26 0.30 160 6.60 4.19 0.47 200 6.86 4.09 0.54 250 7.22 3.73 0.71 0.70 315 6.99 3.49 0.78 400 6.36 3.14 0.88 500 5.64 2.90 0.92 0.95 630 5.09 2.64 1.00 800 5.10 2.56 1.06 1000 5.74 2.71 1.06 1.00 1250 5.63 2.69 1.05 1600 5.18 2.53 1.08 2000 4.76 2.39 1.10 1.00 2500 4.22 2.17 1.16 3150 3.35 1.87 1.20 4000 2.59 1.53 1.31 1.00 5000 2.04 1.24 1.50 6300* 1.39 0.91 1.75 8000* 1.14 0.78 1.77 n/a 10000* 0.80 0.58 2.04 0.95 Calculated to EN ISO 11654:1997 0.95 Calculated to ASTM C 423-01 v5 19/01/2019
Sample Area: Chamber Volume:
Class A T1 sec T2 sec Freq Hz Absorp Coeff α s Empty Room: Temperature: Room with Sample: Temperature: Mounting
Acoustic
Sample Description: α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
Test 8
Method:
Sound Absorption Coefficient

Acoustic Transparent

A fabric which allows sound to penetrate whilst masking visually, making it suitable for sub bass speaker openings in a stage.

Fullness Wall Cavity Class SAC Classification Page Flat 350mm 100mm Flat E E 0.25 0.25 156 155 Width: 260cm /102” FR Certification: BS5867, M1, B1, EN13773 Weight: 140 g/m2 Custom Dye N/A Approx Bale Length: 60m / 197ft Colour Available FR Rating: NDFR 1 ACT001 Black
Sample of Acoustic Transparent (ACT001)

Acoustic Test Report - Absorption

Absorption Class: E

Calculated to EN ISO 11654:1997

Fabric: Acoustic Transparent

Confidential

Fullness: Flat Cavity from Wall: 100mm

Data Sheet 32

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd

Test Date: 20/05/2014

Sample Description: Acoustic Transparent – Single Layer – Flat (Approx. weight 140g/m²) – 100mm cavity from wall Mounting Method: G-100

Area: 9 m2

Volume: 300 m3

* Denotes frequencies outside the range covered by BS EN ISO 354:2003

www.jcjoel.com 155
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 19.2 °C Humidity: 60 %RH Pressure: 1001mbar
with Sample:
Sample
Chamber
Test 34 Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.930.08 63*5.404.420.22n/a 80*6.566.340.03 100 7.577.88-0.03 125 7.117.020.01-0.00 160 6.426.49-0.01 200 7.126.590.06 250 7.076.680.040.05 315 6.846.040.10 400 6.465.620.12 500 5.454.620.180.15 630 4.964.190.20 800 5.474.250.28 1000 5.914.450.300.30 1250 5.594.450.25 1600 5.064.170.23 2000 4.753.940.230.25 2500 4.343.550.27 3150 3.643.080.26 4000 3.092.620.300.30 5000 2.442.090.34 6300*1.791.590.34 8000*1.511.320.45n/a 10000*1.060.940.56
0.25 Class E

Calculated to EN ISO 11654:1997 NRC 0.20 Calculated to ASTM C 423-01
T2, room reverberation
sample
absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
T1, empty room reverberation time
time with
# Practical

Acoustic Test Report - Absorption

Absorption Class: E

Calculated to EN ISO 11654:1997

Fabric: Acoustic Transparent

Confidential

Fullness: Flat Cavity from Wall: 350mm

Data Sheet 31

The Laboratory Measurement of Random Incidence Sound Absorption generally to BS EN ISO 354:2003

Client: J&C Joel Ltd Test Date: 20/05/2014

Sample Description: Acoustic Transparent – Single Layer – Flat (Approx. weight 140g/m²) – 350mm cavity from wall

Method: G-350

Area: 9 m2

Volume: 300 m3

Test 33

www.jcjoel.com 156
Empty Room: Temperature: 19.0 °C Humidity: 62 %RH Pressure: 999mbar Room
Temperature: 19.2 °C Humidity: 60 %RH Pressure: 1001mbar
Sample
Chamber
with Sample:
Mounting
Absorp Practical Freq T1T2 Coeff Absorp Hz secsec Coeff # 50*5.334.720.13 63*5.405.010.08n/a 80*6.565.810.11 100 7.577.73-0.02 125 7.116.170.110.10 160 6.425.510.14 200 7.125.660.19 250 7.075.740.180.20 315 6.845.290.23 400 6.465.120.22 500 5.454.600.180.20 630 4.964.360.15 800 5.474.360.25 1000 5.914.660.240.25 1250 5.594.590.21 1600 5.064.200.22 2000 4.753.840.270.25 2500 4.343.540.27 3150 3.643.020.29 4000 3.092.560.340.35 5000 2.442.070.37 6300*1.791.570.38 8000*1.511.330.42n/a 10000*1.060.930.62  0.25 Class E Calculated
EN ISO
NRC 0.20 Calculated
T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 v4.3 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F r e q u e n c y , H z 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 Absorption Coefficient S o u n d A b s o r p t i o n C o e f f i c i e n t
to
11654:1997
to ASTM C 423-01 * Denotes frequencies outside the range covered by BS EN ISO 354:2003

Showcase

BBC Hoddinott Hall, UK - Acoustic Transparent, covering acoustic duvets (ACT001)

8pt Sharkstooth Gauze

An industry staple 8pt cotton scrim, usually used for projection and lighting effects, 8pt Sharksooth is also effective as an acoustically transparent material. .

Cambridge University American Stage
&
FR Certification: BS5867, M1, B1, NFPA 701, AS1530.2/3 ST013 ST011 Red Black Width: 1097cm / 432” Weight: 100 g/m2 Custom Dye Available* Approx Bale Length: 58m / 190ft Colours Available FR Rating: NDFR 8 ST012 ST007 ST009 ST008 ST010 ST006 Navy Western Grey Sky Blue Eastern Grey Natural White *CUSTOM DYE price on application, 3 wk lead time, MOQ of 58m Fullness Wall Cavity Class SAC Classification Page Flat 100mm N/A 0.05 159
Tour (ST001
ST004)

Acoustic Test Report - Absorption

Absorption Class: Not Classified

Calculated to EN ISO 11654:1997

Fabric: 8pt Sharkstooth Gauze

Fullness: Flat Cavity from Wall: 100mm

Test Report No: C/23171/T02

Page 11 of 16

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 159

Transition (Digital Print)

A lightweight foldable fabric, printed with multiple images to allow the transition from day to night when lit from behind. Tested to prove absence of acoustic absorption.

Sample of Transition (PRT001) FR Certification: EN13501-1 Width: 500cm / 197” Weight: 190 g/m2 Custom Dye Print Approx Roll Length: 30m / 98ft FR Rating: NDFR Fullness Wall Cavity Class SAC Classification Page Flat 100mm N/A 0.05 161

Acoustic Test Report - Absorption

Absorption Class: Not Classified

Calculated to EN ISO 11654:1997

Fabric: Transition (Digital Print)

Fullness: Flat Cavity from Wall: 100mm

Data Sheet 12

Test Report No: 24694-SRL-RP-XT-001-P1

Page 21 of 35

Date: 11/09/2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

See SRL report 24694-SRL-RP-XT-001-P1 for full details

www.jcjoel.com 161
Template Ref: Lab Edition 3 – 14/10/2019 Client: J & C Joel Test Date: 21.5 °C Humidity: 67 %RH Pressure: 996 mbar 21.6 °C Humidity: 66 %RH Pressure: 997 mbar G - 100 9 m² 300 m³ Practical Absorp Coeff # 50* 4.83 4.98 -0.03 63* 5.22 5.38 -0.03 n/a 80* 7.65 7.89 -0.02 100 7.54 7.35 0.02 125 7.75 7.53 0.02 0.00 160 6.51 6.48 0.00 200 6.93 7.17 -0.03 250 6.80 6.69 0.01 0.00 315 6.68 6.47 0.03 400 6.35 6.13 0.03 500 5.57 5.50 0.01 0.05 630 4.92 4.69 0.05 800 4.94 4.79 0.03 1000 5.40 5.28 0.02 0.05 1250 5.54 5.29 0.05 1600 5.12 4.96 0.03 2000 4.79 4.65 0.03 0.05 2500 4.39 4.19 0.06 3150 3.74 3.61 0.05 4000 3.17 3.04 0.07 0.05 5000 2.59 2.50 0.07 6300* 1.95 1.88 0.09 8000* 1.57 1.48 0.19 n/a 10000* 1.11 1.09 0.05 0.05 Calculated to EN ISO 11654:1997 0.00 Calculated to ASTM C 423-01 v5 α w * Denotes frequencies outside the range covered by BS EN ISO 354:2003 T1, empty room reverberation time T2, room reverberation time with sample # Practical absorption coefficient, BS EN ISO 11654:1997 NRC Empty Room: Temperature: Room with Sample: Temperature: Mounting Method: Transition (Digital Print) - Single Layer - Flat (Approx. Weight 190g/m²) Sample Description: Sample Area: Chamber Volume: Test 14 Not Classified T1 sec T2 sec Freq Hz Absorp Coeff α s 21/08/2020
The Laboratory Measurement
Incidence Sound Absorption generally to BS EN ISO 354:2003 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Absorption Coefficient Frequency, Hz
of Random
Sound Absorption Coefficient

Digifoam

A loop Nylon foam backed fabric, ideal for large format blue or green screens for the film production industry.

FR Certification: BS5867 Width: 183cm / 72” Weight: 230 g/m2 Custom Dye N/A Approx Roll Length: 50m / 164ft Colours Available FR Rating: NDFR 2 Fullness Wall Cavity Class SAC Classification Page Flat 350mm 100mm Flat D D 0.40 0.45 164 163 DIG005 DIG004 Blue Green
Guardians of the Galaxy - Digifoam (DIG004)

Acoustic Test Report - Absorption

Absorption Class: D

Calculated to EN ISO 11654:1997

Fabric: Digifoam

Fullness: Flat Cavity from Wall: 100mm

Data Sheets 1 to 15

Page 7 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 163
Template Ref: Lab Edition 5 – Mar 2021 Return to Contents

Acoustic Test Report - Absorption

Absorption Class: D

Calculated to EN ISO 11654:1997

Fabric: Digifoam

Fullness: Flat Cavity from Wall: 350mm

Test Report No: 80161-SRL-RP-XT-001-P1

Page 8 of 32

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 164

Showcase

The Whitworth - Acoustic Panels (ACT001)

Acoustic Drapery Insulation Reports

Products PVC, Wool Serge 800, Wool Serge 565, PVC Page 174 Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 565 175 Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 565 176 Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 800 Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Bolton Twill 179 177 Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 800 178 Empress, PVC, Heavy Bump Interlining, PVC, Bolton Twill Wool Serge 565, Heavy Bump Interlining and PVC (X2) Heavy Bump Interlining, Bolton Twill Empress, Heavy Bump Interlining and PVC (X2) Heavy Bump Interlining, Bolton Twill 182 180 181 Wool Serge 565, PVC Screen, Wool Serge 565 183 Wool Serge 565, PVC Screen, Acoustic Molton, PVC Screen, Wool Sereg 565 Coliseum, PVC Screen, Acoustic Molton, PVC Screen, Coliseum Coliseum, PVC Screen, Coliseum 186 184 185
Products Page PVC Screen, Acoustic Molton, PVC Screen 187 Mercury, PVC Screen, Acoustic Molton, PVC Screen, Mercury 188 Mercury, Wool Serge 565, PVC Screen, Acoustic Molton, PVC Screen, Wool Serge 565, Mercury Acoustic Molton 191 189 PVC Screen 190 Wool Serge 565 PVC Screen, Wool Serge 1000, PVC Screen Coliseum 194 192 193 Coliseum, PVC Screen, Wool Serge 1000, PVC Screen, Coliseum 195 PVC Screen, Bonded Wool Serge, PVC Screen Wool Serge 565, PVC Screen, Bonded Wool Serge, PVC Screen, Wool Serge 565 196 197

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Quality Assurance

Project Title

Document Title

The Laboratory Measurement of Sound Reduction Index of Various Drapes

Technical Report

Client J & C Joel Ltd

Client Address

Summary

Corporation Mill

Corporation Street

Sowerby Bridge, Halifax

Test Report No: C/23171/T01

Page 3 of 25

HX6 2QQ

Date: 12/11/2015

Author Richard Calvert

Checker Richard Critchlow

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Report Number C/23171/T01

Tests have been done in SRL's Laboratory at Holbrook House, Sudbury, Suffolk, to determine the sound reduction index of various drapes in accordance with BS EN ISO 10140-2:2010

From these measurements the required results have been derived and are presented in both tabular and graphic form in Data Sheets 1 to 9.

The results are given in 1/3rd octave bands over the frequency range 50Hz to 10kHz, which is beyond that required by the test standard. Measurements outside the standard frequency range are not UKAS accredited.

Richard Calvert

Tester

For and on behalf of

Tel: 01787 247595

Email: rcalvert@srltsl.com

Richard Critchlow

Deputy Technical Manager

168
SRL Technical Services Limited
This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited London, Birmingham, Manchester, Sudbury SRL Technical Services Limited Registered office: Holbrook House, Little Waldingfield, Sudbury, Suffolk, CO10 0TF Registered in England No 907694

Page 6 of 25

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

1.5 Instrumentation and Apparatus Used

169
C/23171/T01
Test Report No:
Make Description Type E D I Microphone Multiplexer Microphone Power Supply Unit Norwegian Electronics Real Time Analyser 830 Rotating Microphone Boom 231 Brüel & Kjaer 12mm Condenser Microphones 4166 Windshields UA0237 Pre Amplifiers 2639, 2669C Microphone Calibrator 4231 Omnipower Sound Source 4296 Larson Davis 12mm Condenser Microphone 2560 Celestion Loudspeakers 100w Douglas Curtis Rotating Microphone Boom Oregon Scientific Temperature & Humidity & Probe THGR810 TOA Graphic Equalizer E-1231 QSC Audio Power Amplifier RMX 1450

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

1.6 References

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Test Report No: C/23171/T01

Page 8 of 25

BS EN ISO 717-1:2013 Rating of sound insulation in buildings and of building elements. Airborne Sound Insulation.

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

BS EN ISO 10140-2:2010 Laboratory measurement of sound insulation for building elements – Part 2: Measurement of airborne sound insulation.

2.0 Description of Test

2.1 Description of Sample

Various different drape materials were overlaid to build up different combinations. These were clamped to a wooden frame which was sealed to the test aperture. Descriptions are in the summary and data sheets. Drawing 1 shows a typical installation.

Sampling plan: Enough for test only

Sample condition: New

Details supplied by: J & C Joel Ltd

Sample installed by: J & C Joel Ltd

2.2 Sample Delivery date

18 September 2015

2.3 Test Procedures

The sample was mounted/located and tested in accordance with the relevant standard. The method and procedure is described in Appendix A. The measurement uncertainty is given in Appendix B.

170

Date: 12/11/2015

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Drawing 1

171 Page 21 of 25
NORTH ROOM REV ROOM Various Layers of Drape 4 x 2 Timber Frame

Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Appendix A -Test Method

Measurement of Sound Transmission in accordance with

BS EN ISO 10140-2: 2010 – TP33

In the laboratory, airborne sound transmission is determined from the difference in sound pressure levels measured across a test sample installed between two reverberant rooms. The difference in measured sound pressure levels is corrected for the amount of absorption in the receiving room. The test is done under conditions which restrict the transmission of sound by paths other than directly through the sample. The source sound field is randomly incident on the sample.

The test sample is located and sealed in an aperture within the brick dividing wall between the two rectangular reverberant or acoustically "live" rooms, both of which are constructed from 215mm brick with reinforced concrete floors and roofs. The brick wall has dimensions of 3.9m wide x 2.9m high and forms the whole of the common area between the two rooms.

One of the rooms termed the source room has a volume of 55 cubic metres and is isolated by the use of resilient mountings and seals, from the surrounding structure and the adjoining room. The adjoining receiving room has a volume of 50 cubic metres.

Broad band noise is produced in the source room from an electronic generator, power amplifier and loudspeaker. The resulting sound pressure levels in both rooms are sampled, filtered into one third octave band widths, integrated and averaged by means of a Real Time Analyser using a microphone on an oscillating microphone boom. The value obtained at any particular frequency is known as the equivalent sound pressure level for either source or receiving rooms. The change in level across the test sample is termed the equivalent sound pressure level difference, i.e.

D = L1 - L2

where

D is the equivalent sound pressure level difference in dB

L1 is the equivalent sound pressure level in the source room in dB

L2 is the equivalent sound pressure level in the receiving room in dB

172 Page 22 of 25 Date: 12/11/2015 This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

The Sound Reduction Index (R), also known by the American terminology Sound Transmission Loss, is defined as the number of decibels by which sound energy randomly incident on the test sample is reduced in transmitting through it and is given by the formula:

R = D + 10log10 S A ………..in decibels

Where

S is the area of the sample (m2)

A is the total absorption in the receiving room (m2)

both dimensions being in consistent units

The Sound Reduction Index is an expression of the laboratory sound transmission performance of a particular element or construction. It is a function of the mass, thickness, sealing, method of mounting etc., and is independent of the overall area of the sample.

However, when a sample is installed on site and forms part of an enclosure of building, the sound insulation obtained will be dependent upon its surface area, th e larger the area the greater the sound energy transmitted, as well as the absorption in the receiving area. In addition, the overall sound insulation of an enclosure is also determined by the sound transmission through other building elements, some of which may have an inferior performance to the sample. Because of this the potential Sound Reduction Index of a sample is not always fully realised in practice. A further consequence is that the Sound Reduction Index of a particular sample can only successfully be measured in a laboratory because only under such controlled conditions can the sound transmission path be limited to the sample under test.

Rw, C and Ctr have been calculated in accordance with the relevant section of BS EN ISO 717-1:1997 from the results of laboratory tests carried out in accordance with BS EN ISO 10140-2:2010.

173 Page 23 of 25 Date: 12/11/2015 This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited
Extract from SRL Testing Procedure - 3rd Party Accredited Laboratory

Acoustic Test Report - Insulation

Decibel Reduction: 13 dB

Fabrics: PVC, Wool Serge 800, Wool Serge 565, PVC

Test Report No: C/23171/T01

Page 12 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 1

Product PVC (flat)

Identification: Wool Serge 800 (flat)

Wool S erg e 565 (flat)

PVC (flat)

Rating according to BS EN ISO 717-1:2013

13

*shows measurement corrected for background

174
www.jcjoel.com
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test Room:SourceReceiving Client:
C Joel Ltd Air temperature: 16 °C16.1°C
Air humidity: 74 %74% Sample height: 2.2m Volume: 115 m3 300 m3
Air Pressure: 1002 mbar
Test Number : 2
J &
Test Date: 18/09/2015
Sample width: 2m Sample weight: 2.37kg/m2
Sound FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+9.3 63+7.98.1 80+7.3 1006.4 1256.16.7 1607.6 2006.7 2508.17.5 3158.0 4007.4 5007.17.4 6307.9 8009.4 100011.211.2 125014.4 160019.1 200023.322.0 250026.7 315028.3 400029.129.4 500031.5 6300+33.5
10000+33.1
8000+33.133.2
Average Version 100-315012.4v2.1
Rw(C;Ctr)=
(-1;-3) dB +shows frequency
and not UKAS accredited 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
beyond standard

Acoustic Test Report - Insulation

Decibel Reduction: 16 dB

Fabrics: Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 565

Test Report No: C/23171/T01

Page 13 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 2

Test Number : 3

Sample width: 2m

Sample weight: 2.83kg/m2

Product Wool S erg e 565 (50% fullness)

Identification: PVC (flat)

Heavy Bump Interlining (flat)

PVC (flat)

Wool S erg e 565 (flat) Sound

Rating according to BS EN ISO 717-1:2013

16

*shows measurement corrected for background

beyond

www.jcjoel.com 175
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test
Air temperature: 16 °C16.2°C
Air humidity: 74 %74%
Volume: 115 m3 300 m3
Room:SourceReceiving Client: J & C Joel Ltd
Test Date: 18/09/2015
Sample height: 2.2m
Air Pressure: 1002
mbar
FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+8.3 63+8.77.7 80+6.6 1007.7 1256.37.1 1607.5 2008.0 2508.78.5 3159.1 4009.7 50010.310.5 63011.5 80012.4 100015.414.9 125019.5 160024.5 200028.227.0 250030.7 315032.7 400034.834.6 500037.6 6300+39.1 8000+38.838.9 10000+38.8 Average Version 100-315015.1v2.1
Rw(C;Ctr)=
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
(-1;-3) dB +shows frequency
standard and not UKAS accredited

Acoustic Test Report - Insulation

Decibel Reduction: 18 dB

Fabrics: Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 565

Test Report No: C/23171/T01

Page 14 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 3

Test Number : 4

Client: J & C Joel Ltd

Test Date: 18/09/2015

Sample width: 2m

Sample weight: 3.11kg/m2

Product Wool S erg e 565 (50% fullness)

Identification: PVC (flat)

Heavy Bump Interlining (flat)

PVC (flat)

Wool S erg e 565 (50% fullness) Sound

Rating according to BS EN ISO 717-1:2013

*shows measurement corrected for background

18 (-1;-3) dB +shows frequency beyond standard and not

176
www.jcjoel.com
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test Room:SourceReceiving
Air
16.1
temperature:
°C16.3°C
Air humidity: 73 %74%
Volume: 115 m3 300 m3
Sample height: 2.2m
Air Pressure:
1002 mbar
fIndex, dB Hz1/3 Oct 1/1 Oct 50+8.2 63+8.38.0 80+7.6 1009.4 1258.49.1 1609.5 2009.1 25010.29.8 31510.4 40010.9 50011.912.0 63013.7 80014.4 100017.316.8 125021.2 160025.7 200029.428.3 250032.2 315034.6 400036.236.1 500038.0 6300+39.8 8000+39.339.3 10000+38.8 Average Version 100-315016.8v2.1
FreqReduction
Rw(C;Ctr)=
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
UKAS accredited

Acoustic Test Report - Insulation

Decibel Reduction: 16 dB

Fabrics: Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 800

Test Report No: C/23171/T01

Page 15 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 4

Test Number : 5

Test Date: 18/09/2015

Sample width: 2m

Sample weight: 3.06kg/m2

Product Wool S erg e 565 (50% fullness)

Identification: PVC (flat)

Heavy Bump Interlining (flat)

PVC (flat)

Wool S erge 800 (flat)

Rating according to BS EN ISO 717-1:2013

*shows measurement corrected for background

www.jcjoel.com 177
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test
Air temperature: 16.1 °C16.3°C
Air humidity: 73 %74%
Volume: 115 m3 300 m3
Room:SourceReceiving Client: J & C Joel Ltd
Sample height: 2.2m
Air Pressure: 1002 mbar
FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+6.9 63+7.36.5 80+5.6 1006.8 1256.37.0 1607.9 2008.1 2508.78.7 3159.4 4009.9 50010.810.7 63011.8 80013.0 100015.815.4 125020.0 160024.7 200028.527.3 250031.2 315033.0 400035.635.3 500039.6 6300+41.7 8000+41.240.6 10000+39.3 Average Version 100-315015.4v2.1
Sound
Rw(C;Ctr)=
+shows
UKAS
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
16 ( 0;-3) dB
frequency beyond standard and not
accredited

Acoustic Test Report - Insulation

Decibel Reduction: 17 dB

Fabrics: Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Wool Serge 800

Test Report No: C/23171/T01

Page 16 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 5

Test Number : 6

Test Date: 18/09/2015

Sample width: 2m

Sample weight: 3.46kg/m2

Product Wool S erg e 565 (50% fullness)

Identification: PVC (flat)

Heavy Bump Interlining (flat)

PVC (flat)

Wool S erge 800 (50% fullness)

Rating according to BS EN ISO 717-1:2013 *shows measurement corrected for background

17 (-1;-3) dB +shows frequency beyond standard and not

178
www.jcjoel.com
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test
Air temperature: 16.1 °C16.4°C
Air humidity: 73 %74%
Volume: 115 m3 300 m3
Room:SourceReceiving Client: J & C Joel Ltd
Sample height: 2.2m
Air Pressure: 1002 mbar
FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+9.0 63+9.48.1 80+6.5 1007.2 1256.06.8 1607.3 2007.9 2508.78.7 3159.6 40010.5 50012.011.7 63012.9 80014.1 100017.416.7 125021.3 160025.7 200028.727.9 250030.7 315032.7 400034.634.6 500038.1 6300+39.8 8000+39.839.9 10000+40.2 Average Version 100-315015.8v2.1
Sound
Rw(C;Ctr)=
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
UKAS accredited

Acoustic Test Report - Insulation

Decibel Reduction: 16 dB

Fabrics: Wool Serge 565, PVC, Heavy Bump Interlining, PVC, Bolton Twill

Test Report No: C/23171/T01

Page 17 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 6

Test Number : 7

Sample width: 2m

Sample weight: 2.64kg/m2

Product Wool S erg e 800 (50% fullness)

Identification: PVC (flat)

Heavy Bump Interlining (flat)

PVC (flat)

Bolton Twill (50% fullness)

Rating according to BS EN ISO 717-1:2013

16 (-1;-3) dB

*shows measurement corrected for background

beyond

and

www.jcjoel.com 179
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test
Air temperature: 16.1 °C16.4°C
Air humidity: 72 %74%
Volume: 115 m3 300 m3
Room:SourceReceiving Client: J & C Joel Ltd
Test Date: 18/09/2015
Sample height: 2.2m
Air Pressure: 1003 mbar
FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+8.0 63+8.87.3 80+5.7 1006.3 1256.36.5 1606.9 2007.2 2507.67.8 3158.5 4008.9 50010.310.2 63011.8 80013.3 100016.816.0 125021.3 160025.3 200027.326.9 250028.9 315030.8 400032.532.5 500035.3 6300+37.5 8000+37.637.6 10000+37.7 Average Version 100-315014.8v2.1
Sound
Rw(C;Ctr)=
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
+shows frequency
standard
not UKAS accredited

Acoustic Test Report - Insulation

Decibel Reduction: 16 dB

Fabrics: Empress, PVC, Heavy Bump Interlining, PVC, Bolton Twill

Test Report No: C/23171/T01

Page 18 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Data Sheet 7

Test Number : 8

Test Date: 18/09/2015

Sample width: 2m

Sample weight: 2.64kg/m2

Product Empress Velvet (50% fullness)

Identification: PVC (flat)

Heavy Bump Interlining (flat)

PVC (flat)

Bolton Twill (50% fullness)

according to BS EN ISO 717-1:2013

measurement corrected for background

180
www.jcjoel.com
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test
Air temperature: 16.1 °C16.4°C
Room:SourceReceiving Client: J & C Joel Ltd
Air humidity: 72 %74%
Volume: 115 m3 300 m3
Sample height: 2.2m
Air Pressure: 1004
mbar
Sound FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+7.7 63+7.77.2 80+6.3 1006.5 1255.86.4 1606.9 2007.3 2507.87.7 3158.0 4008.3 5009.19.3 63011.1 80013.0 100016.815.8 125020.9 160024.4 200025.725.7 250027.6 315029.1 400029.930.2 500032.0 6300+34.5 8000+33.833.9 10000+33.5 Average
100-315014.3v2.1
*shows
Rw(C;Ctr)=
+shows frequency
not UKAS accredited 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
Version
Rating
16 (-1;-4) dB
beyond standard and

Acoustic Test Report - Insulation

Decibel Reduction: 17 dB

Fabrics: Empress, Heavy Bump Interlining and PVC Heavy Bump Interlining and PVC Heavy Bump Interlining, Bolton Twill

Data Sheet 8

Test Report No: C/23171/T01

Page 19 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Test Number : 9

Client: J & C Joel Ltd

Test Date: 18/09/2015

Sample width: 2m

Sample weight: 3.54kg/m2

Product Empress Velvet (50% fullness)

Identification: Heavy Bump Interlining (flat) and PVC (flat)

Heavy Bump Interlining (flat) and PVC (flat)

Heavy Bump Interlining (flat)

Bolton Twill (50% fullness)

Rating according to BS EN ISO 717-1:2013 *shows measurement corrected for background

17 (-1;-4)

www.jcjoel.com 181
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test Room:SourceReceiving
Air
temperature: 16.3 °C16.5°C
Air
Volume: 115 m3 300 m3
humidity: 72 %76% Sample height: 2.2m
Air Pressure: 1005 mbar
FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+8.6 63+9.08.2 80+7.2 1007.4 1256.16.9 1607.3 2008.0 2508.18.1 3158.3 4008.5 5009.910.0 63012.5 80015.0 100019.318.0 125024.2 160028.6 200029.129.4 250030.7 315033.0 400035.034.7 500037.0 6300+38.7 8000+39.039.1 10000+39.6 Average Version 100-315016.0v2.1
Rw(C;Ctr)=
+shows frequency beyond standard and not UKAS accredited 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve
Sound
dB

Acoustic Test Report - Insulation

Decibel Reduction: 17 dB

Fabrics: Wool Serge 565, Heavy Bump Interlining and PVC

Heavy Bump Interlining and PVC Heavy Bump Interlining, Bolton Twill

Data Sheet 9

Test Report No: C/23171/T01

Page 20 of 25

Date: 12/11/2015

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Test Number : 10

Product

Wool S erg e 565 (50% fullness)

Identification: Heavy Bump Interlining (flat) and PVC (flat)

Heavy Bump Interlining (flat) and PVC (flat)

Heavy Bump Interlining (flat)

Bolton Twill (50% fullness)

Rating according to BS EN ISO 717-1:2013

17 (-1;-4)

*shows measurement corrected for background

182
www.jcjoel.com
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Test
Air temperature: 16.3 °C16.5°C
Air humidity: 72 %76% Sample height: 2.2m Volume: 115 m3 300 m3
Air Pressure: 1005 mbar
Room:SourceReceiving Client: J & C Joel Ltd
Test Date: 18/09/2015
Sample width: 2m Sample weight: 3.46kg/m2
Sound FreqReduction fIndex, dB Hz1/3 Oct 1/1 Oct 50+8.4 63+9.28.6 80+8.1 1007.2 1252.85.0 1606.2 2007.3 2508.48.0 3158.3 4009.4 50010.810.7 63012.2 80013.7 100018.416.8 125022.7 160026.9 200028.828.5 250030.2 315032.0 400033.233.2 500034.8 6300+36.7 8000+35.936.0 10000+35.4 Average Version 100-315015.3v2.1
Rw(C;Ctr)=
dB +shows frequency beyond standard and not UKAS accredited 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Frequency, Hz 0 10 20 30 40 50 60 Sound Reduction Index, dB Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Fabrics: Wool Serge 565, PVC Screen, Wool Serge 565

Dat a Sheets 1 to 15

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

www.jcjoel.com 183
Reduction:
dB (Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel
13
Test Report No: Page 7 of 29
13/04/2023
Template Ref: Mar 2021 Return to Contents
Date:
This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited
1 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 1.6 kg/m2 Octave 5.2 4.4 3.5 2.4 4.1 5.5 2.2 2.6 5.1 6.1 8.4 10.1 11.9 14.4 17.2 19.4 21.9 24.3 26.5 28.6 30.6 33.0 34.3 35.7
Rating according to BS EN ISO 717-1:2020 13 (-1;-3) dB 3150 28.2 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 34.2 8000+ 10000+ 11.4 400 7.9 500 630 1250 800 14.0 1000 1600 21.4 2000 2500 Product Identification: 1st Layer - Wool Serge 565g/m² at
Fullness
Fullness 3rd Layer – Wool Serge 565g/m²
50% Fullness 200 3.1 250 315 3.8 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 1 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1023 mbar 100 Air Temperature: 11.3 °C 15.4 °C Client: Sample Weight: 50+ 4.3 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
50%
2nd Layer – PVC Screen 500g/m² at 0%
at

Acoustic Test Report - Insulation

16

Fabrics: Wool Serge 565, PVC Screen, Acoustic Molton, PVC Screen, Wool Serge 565

Test Report No: 80161-SRL-RP-XT-002-P1

Page 8 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

to BS EN ISO

www.jcjoel.com 184
Reduction:
dB (Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel
Template Ref: Mar 2021 Return to Contents 2 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 2.6 kg/m2 Octave 6.2 6.4 5.2 3.0 5.9 7.0 4.3 4.9 8.2 9.1 11.8 13.7 14.6 16.3 18.5 20.7 24.3 28.5 32.1 34.4 36.3 36.9 37.3 37.5
Rating according
717-1:2020 16 (-1;-4) dB 3150 33.9 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 37.2 8000+ 10000+ 13.9 400 11.1 500 630 1250 800 16.2 1000 1600 23.4 2000 2500 Product Identification: 1st Layer - Wool Serge 565g/m² at 50% Fullness 4th Layer - PVC Screen 500g/m² at 0% Fullness 2nd Layer – PVC Screen 500g/m² at 0% Fullness 5th Layer – Wool Serge 565g/m² at 50% Fullness 3rd Layer – Acoustic Molton 500g/m² at 0% Fullness 200 5.5 250 315 5.0 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 2 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1023 mbar 100 Air Temperature: 11.3 °C 15.4 °C Client: Sample Weight: 50+ 5.9 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Fabrics: Coliseum, PVC Screen Coliseum

Test Report No: 80161-SRL-RP-XT-002-P1

Page 9 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021

2nd

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

according to BS EN ISO 717-1:2020

www.jcjoel.com 185
Reduction:
dB (Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel
13
Template Ref: Mar 2021 Return to Contents 3 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 1.5 kg/m2 Octave 5.2 4.3 3.0 2.2 3.8 4.9 1.9 2.4 5.3 5.8 8.5 10.0 11.9 14.5 17.5 19.3 21.4 23.6 25.5 27.6 29.6 32.0 33.8 35.3
Rating
13 (-1;-3) dB 3150 27.2 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 33.5 8000+ 10000+ 11.2 400 7.7 500 630 1250 800 14.1 1000 1600 21.1 2000 2500 Product Identification: 1st Layer – Coliseum Velvet 500g/m²
at 50% Fullness
Coliseum Velvet 500g/m²
200 3.0 250 315 3.5 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 3 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1023 mbar 100 Air Temperature: 11.3 °C 15.4 °C Client: Sample Weight: 50+ 4.1 63+ 80+ Air Pressure:
0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
Layer – PVC Screen 500g/m² at 0% Fullness 3rd Layer –
at 50% Fullness

Acoustic Test Report - Insulation

Decibel

Fabrics: Coliseum, PVC Screen, Acoustic Molton, PVC Screen, Coliseum

Test Report No: 80161-SRL-RP-XT-002-P1

Page 10 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

BS EN ISO

www.jcjoel.com 186
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Reduction: 15 dB
Template Ref: Mar 2021 Return to Contents 4 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 2.5 kg/m2 Octave 7.1 6.0 4.4 3.5 5.5 6.6 3.8 4.3 7.3 8.5 11.1 12.8 14.9 17.2 20.1 22.4 25.7 30.1 33.7 36.5 38.7 40.1 40.7 40.3
Rating according to
717-1:2020 15 (0;-3) dB 3150 35.8 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 40.4 8000+ 10000+ 14.2 400 10.4 500 630 1250 800 16.9 1000 1600 25.0 2000 2500 Product Identification: 1st Layer – Coliseum Velvet 500g/m² at 50% Fullness 4th Layer – PVC Screen 500g/m² at 0% Fullness 2nd Layer – PVC Screen 500g/m² at 0% Fullness 5th Layer – Coliseum Velvet 500g/m² at 50% Fullness 3rd Layer – Acoustic Molton 500g/m² at 0% Fullness 200 4.9 250 315 5.0 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 4 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 5.7 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Decibel Reduction: 11 dB

Fabrics: PVC Screen, Acoustic Molton, PVC Screen

Test Report No: 80161-SRL-RP-XT-002-P1

Page 11 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021

1st Layer – PVC Screen 500g/m² at 0% Fullness

2nd Layer – Acoustic Molton 500g/m² at 0% Fullness

3rd Layer – PVC Screen 500g/m² at 0% Fullness

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited Rating according to BS EN ISO 717-1:2020 11 (-1;-3)

www.jcjoel.com 187
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Template Ref: Mar 2021 Return to Contents 5 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 1.5 kg/m2 Octave 5.5 4.5 3.2 2.3 4.2 5.1 2.2 2.4 5.0 4.1 6.5 7.0 7.4 9.4 12.6 15.3 18.8 22.4 25.6 28.1 29.0 31.0 31.3 31.3
dB 3150 27.3 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 31.2 8000+ 10000+ 9.4 400 5.7 500 630 1250 800 9.3 1000 1600 17.9 2000 2500 Product Identification:
200 3.0 250 315 3.7 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 5 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 4.3 63+ 80+ Air Pressure:
0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Decibel

15

Fabrics: Mercury, PVC Screen, Acoustic Molton, PVC Screen, Mercury

Test Report No: 80161-SRL-RP-XT-002-P1

Page 12 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Layer – Mercury 255g/m² at 50% Fullness

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

to BS EN ISO

www.jcjoel.com 188
Reduction:
dB (Calculated in accordance with BS EN ISO 717-1 : 2013)
Template Ref: Mar 2021 Return to Contents 6 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 2.0 kg/m2 Octave 7.1 5.1 4.7 3.3 5.3 6.1 3.2 3.6 6.2 6.8 9.9 11.7 13.9 16.7 19.7 20.9 23.8 28.5 32.9 35.7 37.5 39.1 39.3 38.6
Rating
717-1:2020 15 (-1;-4) dB Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 5.5 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 Test Date: Sample Height: Sample Width: Data Sheet 6 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Product Identification: 1st
4th
2nd Layer –
Fullness 5th Layer – Mercury 255g/m² at 50% Fullness 3rd Layer
500g/m²
Fullness 200 4.1 250 315 4.7 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct 400 9.0 500 630 1250 800 16.1 1000 1600 23.4 2000 2500 3150 34.9 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 39.0 8000+ 10000+ 13.3 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
according
Layer – PVC Screen 500g/m² at 0% Fullness
PVC Screen 500g/m² at 0%
– Acoustic Molton
at 0%

Acoustic Test Report - Insulation

Decibel Reduction: 17 dB

Fabrics: Mercury, Wool Serge 565, PVC Screen, Acoustic Molton, PVC Screen, Wool Serge 565, Mercury

Test Report No: 80161-SRL-RP-XT-002-P1

Page 13 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

Rating according to BS EN ISO 717-1:2020 17 (-1;-4) dB

www.jcjoel.com 189
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Template Ref: Lab Edition 5 Mar 2021 Return to Contents 7 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 3.1 kg/m2 Octave 7.7 5.7 5.5 4.2 5.4 6.9 3.8 4.4 8.0 9.8 13.7 16.9 18.5 20.7 24.4 27.1 29.1 30.6 32.1 33.2 34.7 35.7 35.9 35.7
Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 6.2 63+ 80+ Air Pressure:
Test Date: Sample Height: Sample Width: Data Sheet 7 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Product Identification: 1st Layer
Fullness 5th Layer – PVC
500g/m² at 0% Fullness 2nd Layer – Wool Serge 565g/m²
Fullness 6th Layer – Wool Serge 565g/m² at 0% Fullness 3rd Layer
PVC Screen 500g/m²
Fullness 7th Layer – Mercury 255g/m² at 50% Fullness 4th Layer – Acoustic Molton 500g/m² at 0% Fullness 200 5.0 250 315 5.4 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct 400 12.5 500 630 1250 800 20.6 1000 1600 28.7 2000 2500 3150 33.2 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 35.8 8000+ 10000+ 16.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
– Mercury 255g/m² at 50%
Screen
at 50%
at 0%

Acoustic Test Report - Insulation

Fabrics: PVC Screen

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

Rating according to BS EN ISO 717-1:2020

Page 14 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

www.jcjoel.com 190
dB (Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel Reduction: 8
Test Report No: 80161-SRL-RP-XT-002-P1
Template Ref: Mar 2021 Return to Contents 8 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 0.5 kg/m2 Octave 3.6 2.3 0.9 1.0 2.0 2.4 -1.6 -0.7 1.8 2.2 4.3 5.3 6.4 7.8 9.5 10.7 12.3 13.6 15.1 16.8 18.2 19.7 20.4 21.6
(0;-3) dB 3150 16.5 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 20.5 8000+ 10000+ 5.8 400 3.7 500 630 1250 800 7.7 1000 1600 12.0 2000 2500 Product Identification: PVC Screen 500g/m² at 0% Fullness 200 -0.4 250 315 1.8 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 8 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 2.1 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 -10.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
8

Acoustic Test Report - Insulation

Page 15 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited Rating according to BS EN ISO 717-1:2020

www.jcjoel.com 191
Reduction:
dB (Calculated in accordance with BS EN ISO 717-1 : 2013) Fabrics: Acoustic Molton
Decibel
8
Test Report No: 80161-SRL-RP-XT-002-P1
Template Ref: Mar 2021 Return to Contents 9 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 0.5 kg/m2 Octave 2.8 1.1 1.7 1.7 1.4 4.2 0.8 1.7 3.8 4.7 5.9 6.5 7.6 8.6 9.3 9.5 9.7 9.7 9.5 9.6 9.6 9.7 9.8 9.4
8 (0;-1) dB 3150 9.6 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 9.6 8000+ 10000+ 5.9 400 5.6 500 630 1250 800 8.4 1000 1600 9.6 2000 2500 Product Identification: Acoustic Molton 500g/m² at 0% Fullness 200 1.9 250 315 2.3 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 9 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 1.8 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 -10.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Fabrics: Wool Serge 565

Test Report No: 80161-SRL-RP-XT-002-P1

Page 16 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

Rating according to BS EN ISO 717-1:2020

www.jcjoel.com 192
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel Reduction: 6 dB
Template Ref: Mar 2021 Return to Contents 10 J&C Joel Ltd 28/02/2023 2.20 m 2.00 m 0.6 kg/m2 Octave 3.2 2.7 1.0 1.5 1.8 3.1 -0.7 -0.5 1.7 1.8 4.1 4.2 4.8 6.0 6.8 7.3 7.8 7.7 7.6 7.8 7.7 7.7 7.8 7.5
dB 3150 7.7 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 7.6 8000+ 10000+ 4.1 400 3.2 500 630 1250 800 5.8 1000 1600 7.6 2000 2500 Product Identification: Wool Serge 565g/m² at 50% Fullness 200 0.0 250 315 2.1 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 10 Volume: 115 m³ 300.1 m³ Air Humidity: 53 % 46 % Test Room: Source Receiving Test Number: 1022 mbar 100 Air Temperature: 11.3 °C 15.6 °C Client: Sample Weight: 50+ 2.2 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 -10.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
6 (0;-2)

Acoustic Test Report - Insulation

Page 17 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited Rating according to BS EN ISO 717-1:2020

www.jcjoel.com 193
Reduction: 6 dB (Calculated in accordance with BS EN ISO 717-1 : 2013) Fabrics: Coliseum Velvet
Decibel
Test Report No: 80161-SRL-RP-XT-002-P1
Template Ref: Mar 2021 Return to Contents 11 J&C Joel Ltd 01/03/2023 2.20 m 2.00 m 0.5 kg/m2 Octave 3.1 1.3 2.0 0.8 0.4 4.4 1.3 0.9 2.4 2.9 4.5 4.1 4.6 5.7 6.2 6.5 6.7 7.0 7.0 7.1 7.4 7.2 7.3 7.0
6 (0;-1) dB 3150 7.2 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 7.2 8000+ 10000+ 4.1 400 3.8 500 630 1250 800 5.4 1000 1600 6.7 2000 2500 Product Identification: Coliseum Velvet 500g/m² at 50% Fullness 200 1.5 250 315 1.5 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 11 Volume: 115 m³ 300.1 m³ Air Humidity: 55 % 52 % Test Room: Source Receiving Test Number: 1021 mbar 100 Air Temperature: 10.5 °C 16.1 °C Client: Sample Weight: 50+ 2.1 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 -10.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Decibel Reduction: 12 dB

Fabrics: PVC Screen, Wool Serge 1000, PVC Screen

Test Report No: 80161-SRL-RP-XT-002-P1

Page 18 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021

1st Layer – PVC Screen 500g/m² at 0% Fullness

2nd Layer – Wool Serge 1000g/m² at 0% Fullness

3rd Layer – PVC Screen 500g/m² at 0% Fullness

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited Rating according to BS EN ISO 717-1:2020 12 (-1;-3)

www.jcjoel.com 194
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Template Ref: Mar 2021 Return to Contents 12 J&C Joel Ltd 01/03/2023 2.20 m 2.00 m 2.0 kg/m2 Octave 6.1 4.1 4.5 3.3 4.5 7.7 5.7 4.4 6.5 6.1 7.4 7.2 8.1 10.3 13.8 17.1 21.4 26.5 31.5 35.3 37.6 40.6 40.3 39.6
3150 34.1 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 40.1 8000+ 10000+ 11.3 400 6.9 500 630 1250 800 10.1 1000 1600 20.1 2000 2500 Product Identification:
dB
200 5.4 250 315 4.8 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 12 Volume: 115 m³ 300.1 m³ Air Humidity: 55 % 52 % Test Room: Source Receiving Test Number: 1021 mbar 100 Air Temperature: 10.5 °C 16.1 °C Client: Sample Weight: 50+ 4.8 63+ 80+ Air Pressure:
0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve

Acoustic Test Report - Insulation

Fabrics: Coliseum Velvet, PVC Screen, Wool Serge 1000, PVC Screen, Coliseum

Test Report No: 80161-SRL-RP-XT-002-P1

Page 19 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited

to BS EN ISO

www.jcjoel.com 195
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel Reduction: 16 dB
Template Ref: Mar 2021 Return to Contents 13 J&C Joel Ltd 01/03/2023 2.20 m 2.00 m 3.0 kg/m2 Octave 7.4 5.0 6.1 3.8 4.9 8.2 7.2 6.2 8.6 9.9 11.9 12.7 14.6 17.4 20.6 24.0 28.1 32.0 34.7 37.6 39.8 42.0 41.8 38.5
Rating
717-1:2020 16 (0;-3) dB 3150 36.9 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 40.4 8000+ 10000+ 15.3 400 11.3 500 630 1250 800 16.9 1000 1600 26.9 2000 2500 Product Identification:
– Coliseum Velvet 500g/m² at 50% Fullness 4th Layer – PVC Screen 500g/m² at 0% Fullness 2nd Layer - PVC Screen 500g/m² at 0% Fullness 5th Layer - Coliseum Velvet 500g/m² at 50% Fullness 3rd Layer - Wool Serge 1000g/m² at 0% Fullness 200 7.2 250 315 5.3 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct Test Date: Sample Height: Sample Width: Data Sheet 13 Volume: 115 m³ 300.1 m³ Air Humidity: 55 % 52 % Test Room: Source Receiving Test Number: 1021 mbar 100 Air Temperature: 10.5 °C 16.1 °C Client: Sample Weight: 50+ 6.1 63+ 80+ Air Pressure: Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
according
1st Layer

Acoustic Test Report - Insulation

Fabrics: PVC Screen, Bonded Wool Serge, PVC Screen

Test Report No: 80161-SRL-RP-XT-002-P1

Page 20 of 29

Date: 13/04/2023

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited

Laboratory Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021

Layer – PVC Screen 500g/m² at 0% Fullness

Layer – Bonded Wool Serge 1130g/m² at 0% Fullness

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited Rating according to BS EN ISO 717-1:2020 13 (0;-3)

196
www.jcjoel.com
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel Reduction: 13 dB
Template Ref: Lab Edition 5 – Mar 2021 Return to Contents 14 J&C Joel Ltd 01/03/2023 2.20 m 2.00 m 2.1 kg/m2 Octave 7.1 4.7 5.4 2.4 4.9 8.2 6.7 5.7 7.2 7.1 8.5 8.6 9.4 11.7 15.0 18.5 22.7 26.9 30.9 34.8 35.8 36.9 35.5 34.9
dB Test Number: 1021 mbar 100 Air Temperature: 10.5 °C 16.1 °C Client: Sample Weight: 50+ 5.6 63+ 80+ Air Pressure:
Test Date: Sample Height: Sample Width: Data Sheet
Volume: 115 m³ 300.1 m³ Air Humidity: 55 % 52 % Test Room: Source Receiving Product Identification:
2nd
3rd
200 6.5 250 315 4.6 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct 400 8.0 500 630 1250 800 11.5 1000 1600 21.4 2000 2500 3150 33.3 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 35.7 8000+ 10000+ 12.2 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
14
1st
Layer – PVC Screen 500g/m² at 0% Fullness

Acoustic Test Report - Insulation

Test Report No: 80161-SRL-RP-XT-002-P1

Page 21 of 29

Date: 13/04/2023

Fabrics: Wool Serge 565, PVC Screen, Bonded Wool Serge, PVC Screen, Wool Serge 565

Measurement of Sound Reduction Index to BS EN ISO 10140-2:2021

Layer - Wool Serge 565g/m² at 50% Fullness

Layer - PVC Screen 500g/m² at 0% Fullness

Layer - Wool Serge 565g/m² at 50% Fullness 3rd Layer - Bonded Wool Serge 1130g/m² at 0% Fullness

Layer - PVC Screen 500g/m² at 0% Fullness

* shows measurement corrected for background

> shows measurement limited by background

+ shows Frequency beyond standard and not UKAS accredited Rating according to BS EN ISO 717-1:2020

This report shall not be reproduced, except in full, without written approval of SRL Technical Services Limited Template Ref: Lab Edition 5

www.jcjoel.com 197
(Calculated in accordance with BS EN ISO 717-1 : 2013)
Decibel Reduction: 18 dB
– Mar
Return to Contents 15 J&C Joel Ltd 01/03/2023 2.20 m 2.00 m 3.3 kg/m2 Octave 8.3 5.2 6.5 4.1 5.2 9.0 7.7 7.7 10.1 11.7 14.0 14.4 16.4 19.4 22.1 25.5 30.3 35.2 38.9 40.7 41.7 43.9 42.5 35.5
2021
Test Number: 1021 mbar 100 Air Temperature: 10.5 °C 16.1 °C Client: Sample Weight: 50+ 6.5 63+ 80+ Air Pressure: Laboratory
Test Date: Sample Height: Sample Width: Data Sheet 15 Volume: 115 m³ 300.1 m³ Air Humidity: 55 % 52 % Test Room: Source Receiving Product
1st
4th
2nd
5th
200 8.4 250 315 5.6 125 160 Frequency Hz Sound Reduction Index, dB ⅓ Oct 400 13.2 500 630 1250 800 18.7 1000 1600 28.7 2000 2500 3150 40.3 4000 5000 Rw(C;Ctr)= Average 100-3150 SRL Version 1.1 6300+ 39.0 8000+ 10000+ 17.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 Sound Reduction Index, dB Frequency, Hz Sound Reduction Index Rw reference curve
18 (-1;-4) dB
Identification:

Basic Acoustics

Sound is made up of vibrations or sound waves, formed by objects shaking back and forth. These sound waves travel through air, water and solid objects. When they reach our ears, they make the delicate skin of the eardrums vibrate and translate into sounds we recognise.

The scientific study of sound waves is known as acoustics.

The following pages are designed to act as a guide to help you understand some of the key factors involved in acoustics. Our aim is to get you thinking about your space, the type of performance(s) you are wanting to stage and the problems you are seeking to overcome.

We would always advise you to seek input from a professional acoustician. Our expert team is always on hand to facilitate such a conversation, offering guidance and support as to which products are most suitable to meet your needs.

Decibels (dB)

The decibel (dB) is the unit used to measure the intensity of a sound. Your ears can hear everything from your fingertip brushing lightly over your skin to a loud jet engine.

The higher the decibel level, the louder the noise. On the decibel scale, the level increase of 10 means that a sound is actually 10 times more intense, or powerful

Typical Noise Levels

198
Breathing
Jet Engine Rock Concert
Rustling Leaves Whisper Library Home Office Conversation Piano Noisy Restaurant Television Lorry Applause Hair
Nightclub
Grenade Rocket Launch
Dryer French Horn
Bass Drum
Symphony Orchestra Police Siren

Frequency is the speed of the vibration and determines the pitch of the sound. Frequency is measured as the number of wave cycles that occur in one second, this unit is measured in Hertz (Hz). Humans can detect sound in a range of 20Hz to 20kHz.

Sound waves interact with objects in a room differently and can cause acoustic issues. Low frequencies are more difficult to control, due to short reverberation times and often full acoustic solutions are required to deal with these. Mid or high frequencies have a longer line of reverberation, so it’s important to understand the sound you are dealing with.

Reverberation Time

Sound in a room will repeatedly bounce off surfaces such as the walls, the ceiling and floor or other hard surfaces. When these reflections combine, a phenomenon known as reverberation is created. Reverberation reduces when the reflections hit absorptive surfaces such as curtains, soft furniture and even people.

The reverberation time of a room or space is defined as the time it takes for sound to reduce (or decay) by 60dB. For example, if the sound in a room took 5 seconds to decay from 90dB to 30dB, the reverberation time would be 5 seconds.

In order to enhance the experience for your audience, it is vital to understand the acoustic requirements of the performance as these need to be in harmony with the reverberation time of the space.

199
Frequency
Frequency1 wave per second = 1Hz Time (seconds) 1 Wave Length Amplitude Frequency3 waves per second = 3Hz Time (seconds) 1 Wave Length Amplitude Reverberation Time (seconds) 0.2 1.0 1.8 0.6 1.4 2.2 0.4 1.2 2.0 0.8 1.6 2.4 2.6 Speech Speech & Music Music Dead Space (Sound decays rapidly) Live Space (Sound persists) Symphonic Classical to Romantic Liturgical Orchestra, Chorus, Organ Secular Chorus Opera Recital and Chamber music Baroqué Semiclassical Concert using sound system Musical Comedies, Operettas Dance & Rock bands using sound system House of Worship Multipurpose Auditorium High school Auditorium Small Theatre Cinema Lecture / Conference Room Intimate Drama Primary School Classroom Recording & Broadcasting Studios Churches Cathedrals Optimal Level. Tolerance Level.

Sound Absorption and Insulation

There is a key difference between acoustic absorption and acoustic insulation. The graphics below are designed to show you this difference and help you achieve the perfect acoustics in your space.

Issue - Sound Transmission

Solution - Acoustically Insulating Drapes

Multilayered drapery can be installed in open office environments to create privacy and prevent sound transmission

Issue - Slapback Echo

Solution - Measured Absorption

Acoustic drapery, banners and panels can be used to absorb slapback echo within auditoriums and performance venues

Issue - Sound Dissipation

Solution - Positive Reflection

Acoustic shell systems can be installed on stage to reflect lost sound towards the audience.

200 - Direction of Sound - Reduced Sound - Audience (bottom images) - Multilayer Drape - Banner / Panel - Drape - Shell