PRAIRIE BAND CASINO BINGO & SLOT ADDITION MAYETTA, KANSAS 09.23.15
F
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
ISSUE DRAWINGS: 08.17.15 08.21.15 09.01.15 09.23.15
STRUCTURAL PACKAGE SEWER PACKAGE STRUCTURAL ADDENDUM SHELL PACKAGE
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
DRAWING INDEX:
B
CIVIL: C100 C120 C150 C200 C300 C301 C302 C303 C304
A
MAYETTA, KANSAS
PROJECT:
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
ARCHITECTURAL: DEMO PLAN SITE PLAN SITE PLAN GRADING PLAN UTILITY DETAILS PLAN SITE DETAILS PLAN UTILITY DETAILS PLAN UTILITY DETAILS PLAN SITE DETAILS PLAN
A100 A101 A102 A103 A201 A213 A214 A301 A302 A303 A311 A312 A313 A314 A401
COVER SHEET CODE FLOOR PLAN SITE PLAN REFERENCE FLOOR & CEILING PLAN DEMO OVERALL FLOOR & CEILING PLAN RCP DEMO PLAN PHASE ONE RCP DEMO PLAN PHASE TWO OVERALL FLOOR & CEILING PLAN OVERALL ROOF PLAN OVERALL WALKER DUCT PLAN FLOOR PLAN PHASE ONE FLOOR PLAN PHASE TWO RCP PHASE ONE RCP PHASE TWO EXTERIOR ELEVATIONS
A501 A502 A503 A504 A505 A506 A507 A511 A515 A601 A602 A603 A604 A801
WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS EXTERIOR WALL DETAILS EXTERIOR WALL DETAILS ENLARGED RESTROOM PLAN & ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS DOOR SCHEDULES & DETAILS
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
COVER SHEET
DATE:
09.23.15
JOB NO.:
1016
SHEET:
A100
9
F
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
LIGHTING DESIGNER:
MAYETTA, KANSAS
PROJECT:
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
Copyright 2015 H2B architect, inc. Original Size: 1 1 2 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
FOOTING & FOUNDATIONS SHEET TITLE:
J:\2015Proj\155130\DWGS\site plan.dwg, 9/22/2015 2:34:09 PM
DEMO PLAN
A DATE:
08.19.15
JOB NO.:
1016
SHEET:
C100
9
F
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
LIGHTING DESIGNER:
MAYETTA, KANSAS
PROJECT:
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
Copyright 2015 H2B architect, inc. Original Size: 1 1 2 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHEET TITLE:
J:\2015Proj\155130\DWGS\Ph 1 site.dwg, 9/22/2015 2:50:17 PM
SITE PLAN
A 09.02.15 JOB NO.: 1016 CFS JOB NO.: 15-5130 DATE:
SHEET:
C120
9
F
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
LIGHTING DESIGNER:
MAYETTA, KANSAS
PROJECT:
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
Copyright 2015 H2B architect, inc. Original Size: 1 1 2 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
FOOTING & FOUNDATIONS SHEET TITLE:
J:\2015Proj\155130\DWGS\site plan.dwg, 9/22/2015 2:52:57 PM
SITE PLAN
A DATE:
08.19.15
JOB NO.:
1016
SHEET:
C150
9
F
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
LIGHTING DESIGNER:
MAYETTA, KANSAS
PROJECT:
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
FOOTING & FOUNDATIONS SHEET TITLE:
J:\2015Proj\155130\DWGS\site plan.dwg, 9/22/2015 2:46:56 PM
GRADING PLAN
A DATE:
08.19.15
JOB NO.:
1016
SHEET:
C200
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F PLAN
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
SECTION - TYPE II-P INLET
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
TRENCHING DETAILS
PRECAST INLET BOX RISER SECTION - TYPE II-P INLET MANHOLE
NOTES:
LIGHTING DESIGNER:
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
STANDARDS FOR SETTING LINE AND GRADE FOR SEWER CONSTRUCTION:
WELD DETAILS (E) DETAIL PLAN A
C STANDARD METHODS FOR TRANSFERRING LINE AND GRADE TO SEWER TRENCH BOTTOM: A
SECTION A-A PLAN VIEW SECTION
GRATE FRAME
INLET GRATE WEIGHT: 140 LBS
II-P CURB INLET WEIGHT: 1,550 LBS
PROJECT:
(1, 2) INTEGRATED DUCTILE IRON FRAME & GRATE TO MATCH BASIN O.D. WITH PEDESTRIAN GRATE
MAYETTA, KANSAS
(C) DETAIL
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
INLET DETAILS
B
18" DRAIN BASIN Copyright 2015 H2B architect, inc.
(5) ADAPTER ANGLES
Original Size: 1 1 2 " - Drawing may have been reduced. 0" 1"
ACCORDING TO PLANS
J:\2015Proj\155130\DWGS\Site Details.dwg, 9/18/2015 11:14:54 AM
ISSUED FOR:
A
1 - GRATES/SOLID COVER SHALL BE DUCTILE IRON PER ASTM A536 GRADE 70-50-05. 2 - FRAMES SHALL BE DUCTILE IRON PER ASTM A536 GRADE 70-50-05. 3 - DRAIN BASIN TO BE CUSTOM MANUFACTURED ACCORDING TO PLAN DETAILS. RISERS ARE NEEDED FOR BASINS OVER 84" DUE TO SHIPPING RESTRICTIONS. SEE DRAWING NO. 7001-110-065. 4 - DRAINAGE CONNECTION STUB JOINT TIGHTNESS SHALL CONFORM TO ASTM D3212 FOR CORRUGATED HDPE (ADS N-12/HANCOR DUAL WALL), N-12 HP, & PVC SEWER.
SHEET TITLE:
SEWER CLEANOUT DETAIL
UTILITY DETAILS PLAN
REINFORCED CONCRETE COLLAR
ANGLE BETWEEN ADAPTERS SEE DRAWING NO. 7001-110-012. WATERTIGHT JOINT (CORRUGATED HDPE SHOWN) (4) VARIOUS TYPES OF INLET & OUTLET ADAPTERS AVAILABLE: 4" - 18" FOR CORRUGATED HDPE (ADS N-12/HANCOR DUAL WALL, ADS/HANCOR SINGLE WALL), N-12 HP, PVC SEWER (EX: SDR 35), PVC DWV (EX: SCH 40), PVC C900/C905, CORRUGATED & RIBBED PVC
FOOTING & FOUNDATIONS
THE BACKFILL MATERIAL SHALL BE CRUSHED STONE OR OTHER GRANULAR MATERIAL MEETING THE REQUIREMENTS OF CLASS I OR CLASS II MATERIAL AS DEFINED IN ASTM D2321. BEDDING & BACKFILL FOR SURFACE DRAINAGE INLETS SHALL BE PLACED & COMPACTED UNIFORMLY IN ACCORDANCE WITH ASTM D2321.
DATE:
08.19.15
JOB NO.:
1016
SHEET:
C300
8
7
6
5
4
3
2
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F DOME DETAIL B
SPECIAL REQUIREMENTS FOR WHEELCHAIR RAMP CONSTRUCTION
COMBINED CURB & GUTTER AT MAIN ENTRANCE
RUNNING BOND/PARALLEL ALIGNMENT AND JOINT DETAIL
E
1
SIDEWALK (RESIDENTIAL AND COMMERCIAL) CONSTRUCTION
B
9
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
Installation pattern for detectable warning paving bricks
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
SECTION B-B SIDEWALK RAMP DETAILS 3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
COMBINED CURB & GUTTER
LIGHTING DESIGNER:
ASPHALT PAVEMENT
C
PROJECT:
TYPICAL SECTION
MAYETTA, KANSAS
ARMOR-TILE CAST IN PLACE DETECTABLE WARNING SYSTEM
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHEET TITLE:
J:\2015Proj\155130\DWGS\Ph 1 details.dwg, 9/18/2015 11:15:03 AM
SITE DETAILS PLAN
A 09.02.15 JOB NO.: 1016 CFS JOB NO.: 15-5130 DATE:
SHEET:
C301
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
PLAN
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC
SECTION - TYPE II-P INLET
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
TRENCHING DETAILS
SECTION - TYPE II-P INLET MANHOLE
INLET DETAILS
STANDARDS FOR SETTING LINE AND GRADE FOR SEWER CONSTRUCTION:
(C) DETAIL
WELD DETAILS PLAN
(E) DETAIL
C
A
STANDARD METHODS FOR TRANSFERRING LINE AND GRADE TO SEWER TRENCH BOTTOM: A
SECTION A-A PLAN VIEW
SECTION
GRATE FRAME
INLET GRATE WEIGHT: 140 LBS
II-P CURB INLET WEIGHT: 1,550 LBS
PROJECT:
(1, 2) INTEGRATED DUCTILE IRON FRAME & GRATE TO MATCH BASIN O.D. WITH PEDESTRIAN GRATE
MAYETTA, KANSAS
D
PRAIRIE BAND CASINO AND RESORT
NOTES:
PRAIRIE BAND BINGO & SLOT EXPANSION
PRECAST INLET BOX RISER
LIGHTING DESIGNER:
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
18" DRAIN BASIN Copyright 2015 H2B architect, inc.
(5) ADAPTER ANGLES
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ACCORDING TO PLANS
J:\2015Proj\155130\DWGS\Ph 1 details.dwg, 9/18/2015 11:15:09 AM
ISSUED FOR:
A
THE BACKFILL MATERIAL SHALL BE CRUSHED STONE OR OTHER GRANULAR MATERIAL MEETING THE REQUIREMENTS OF CLASS I OR CLASS II MATERIAL AS DEFINED IN ASTM D2321. BEDDING & BACKFILL FOR SURFACE DRAINAGE INLETS SHALL BE PLACED & COMPACTED UNIFORMLY IN ACCORDANCE WITH ASTM D2321.
1 - GRATES/SOLID COVER SHALL BE DUCTILE IRON PER ASTM A536 GRADE 70-50-05. 2 - FRAMES SHALL BE DUCTILE IRON PER ASTM A536 GRADE 70-50-05. 3 - DRAIN BASIN TO BE CUSTOM MANUFACTURED ACCORDING TO PLAN DETAILS. RISERS ARE NEEDED FOR BASINS OVER 84" DUE TO SHIPPING RESTRICTIONS. SEE DRAWING NO. 7001-110-065. 4 - DRAINAGE CONNECTION STUB JOINT TIGHTNESS SHALL CONFORM TO ASTM D3212 FOR CORRUGATED HDPE (ADS N-12/HANCOR DUAL WALL), N-12 HP, & PVC SEWER.
UTILITY DETAILS PLAN
REINFORCED CONCRETE COLLAR
ANGLE BETWEEN ADAPTERS SEE DRAWING NO. 7001-110-012.
09.02.15 JOB NO.: 1016 CFS JOB NO.: 15-5130 DATE:
WATERTIGHT JOINT (CORRUGATED HDPE SHOWN) (4) VARIOUS TYPES OF INLET & OUTLET ADAPTERS AVAILABLE: 4" - 18" FOR CORRUGATED HDPE (ADS N-12/HANCOR DUAL WALL, ADS/HANCOR SINGLE WALL), N-12 HP, PVC SEWER (EX: SDR 35), PVC DWV (EX: SCH 40), PVC C900/C905, CORRUGATED & RIBBED PVC
SHEET TITLE:
SHEET:
C302
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
TRENCH DRAIN DETAIL
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
LIGHTING DESIGNER:
MAYETTA, KANSAS
PROJECT:
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHEET TITLE:
J:\2015Proj\155130\DWGS\Ph 1 details.dwg, 9/18/2015 11:15:14 AM
UTILITY DETAILS PLAN
A 09.02.15 JOB NO.: 1016 CFS JOB NO.: 15-5130 DATE:
INLET REPAIR DETAIL
SHEET:
C303
8
7
6
5
4
3
2
1
SIDEWALK (RESIDENTIAL AND COMMERCIAL) CONSTRUCTION
B
9
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F DOME DETAIL B
SPECIAL REQUIREMENTS FOR WHEELCHAIR RAMP CONSTRUCTION
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
HANDICAPPED PARKING SIGN
RUNNING BOND/PARALLEL ALIGNMENT AND JOINT DETAIL
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
MECHANICAL & PLUMBING ENGINEER:
Installation pattern for detectable warning paving bricks
FACILITY ENGINEERING AND CONSULTING, LLC
ELECTRICAL ENGINEER:
SECTION B-B SIDEWALK RAMP DETAILS 3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM CIVIL ENGINEER:
COMBINED CURB & GUTTER
LIGHTING DESIGNER:
ASPHALT PAVEMENT
C
PROJECT:
CC&G (MODIFIED)
MAYETTA, KANSAS
ARMOR-TILE CAST IN PLACE DETECTABLE WARNING SYSTEM
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LIGHTWORKS INC. 361B Main Weston, MO. 64098 816.640.9948
B
CONCRETE WHEEL STOP Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
FOOTING & FOUNDATIONS SHEET TITLE:
J:\2015Proj\155130\DWGS\Site Details.dwg, 9/18/2015 11:15:24 AM
SITE DETAILS PLAN
A DATE:
08.19.15
JOB NO.:
1016
SHEET:
C304
9
8
7
6
5
4
3
2
1
Design No. U419 October 27, 2005
Nonbearing Wall Ratings -- 1, 2, 3 or 4 Hr (See Items 3 & 4)
4
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F 1" 94
1" 74
1" 74
47 8"
1" 44
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
7
3
3A
4
2
1. Floor and Ceiling Runners -- (Not shown) -- Channel shaped, fabricated from min 25 MSG corrosion-protected steel, min width to accommodate stud size, with min 1 in. long legs, attached to floor and ceiling with fasteners 24 in. OC max. 2. Steel Studs -- Channel shaped, fabricated from min 25 MSG corrosion-protected steel, min width as indicated under Item 4, min 1-1/4 in. flanges and 1/4 in. return, spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than assembly height. 3. Batts and Blankets* -- (Required as indicated under Item 4) -- Mineral wool batts, friction fitted between studs and runners. Min nom thickness as indicated under Item 4. See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies. 3A. Batts and Blankets* -- (Optional) -- Placed in stud cavities, any glass fiber or mineral wool insulation bearing the UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance. See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies.
MECHANICAL & PLUMBING ENGINEER:
4. Gypsum Board* -- Gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Vertical joints in adjacent layers (multilayer systems) staggered one stud cavity. Horizontal joints need not be backed by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be staggered. Horizontal edge joints and horizontal butt joints in adjacent layers (multilayer systems) staggered a min of 12 in. The thickness and number of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
Wallboard Protection on Each Side of Wall Rating Min Stud Depth No. of Layers Min Thkns & Thkns of Insulation of Panel (Item 3) 1 3-1/2 1 layer, 5/8 in. thick Optional 1 2-1/2 1 layer, 1/2 in. thick 1-1/2 in. 1 1-5/8 1 layer, 3/4 in. thick Optional 2 1-5/8 2 layers, 1/2 in. thick Optional 2 1-5/8 2 layers, 5/8 in. thick Optional 2 3-1/2 1 layer, 3/4 in. thick 3 in. 3 1-5/8 3 layers, 1/2 in. thick Optional 3 1-5/8 2 layers, 3/4 in. thick Optional 3 1-5/8 3 layers, 5/8 in. thick Optional 4 1-5/8 4 layers, 5/8 in. thick Optional 4 1-5/8 4 layers, 1/2 in. thick Optional 4 2-1/2 2 layers, 3/4 in. thick 2 in.
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
3350
EGRESS CAPACITY
NEW
4A. Gypsum Board* -- (As an alternate to Item 4) -- 5/8 in. thick, 2 ft. wide, tongue and groove edge, applied horizontally as the outer layer to one side of the assembly. Secured as described in Item 5. Joint covering (Item 7) not required.
907
EXISTING 2 HOUR FIREWALL
FX
EDGE OF NEW CONSTRUCTION
EXISTING NEW
C
EXISTING 90 MIN. FIRE SHUTTER
550
F.D.
PAC INTERNATIONAL INC -- Type RSIC-1. 6B. Steel Framing Members (Optional, Not Shown)* -- As an alternate to Item 6, furring channels and Steel Framing Members on only one side of studs as described below: a. Furring Channels -- Formed of No. 25 MSG galv steel, spaced 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Batts and Blankets placed in stud cavity as described in Item 4. Two layers of gypsum board attached to furring channels as described in Item 4. Not for use with Item 4A. b. Steel Framing Members* -- Used to attach furring channels (Item 6Ba) to one side of studs (Item 2) only. Clips spaced 48 in. OC., and secured to studs with two No. 8 x 2-1/2 in. coarse drywall screws, one through the hole at each end of the clip. Furring channels are friction fitted into clips. KINETICS NOISE CONTROL INC -- Type Isomax 7. Joint Tape and Compound -- Vinyl or casein, dry or premixed joint compound applied in two coats to joints and screw heads of outer layers. Paper tape, nom 2 in. wide, embedded in first layer of compound over all joints of outer layer panels. Paper tape and joint compound may be omitted when gypsum panels are supplied with a square edge. 8. Siding, Brick or Stucco -- (Optional, not shown) -Aluminum, vinyl or steel siding, brick veneer or stucco, meeting the requirements of local code agencies, installed over gypsum panels. Brick veneer attached to studs with corrugated metal wall ties attached to each stud with steel screws, not more than each sixth course of brick.
A
9. Caulking and Sealants* -- (Optional, not shown) -- A bead of acoustical sealant applied around the partition perimeter for sound control. UNITED STATES GYPSUM CO -- Type AS *Bearing the UL Classification Mark
EDGE OF NEW CONSTRUCTION FX
FX 775
2 HOUR FIRE RATED WALL 225 453
CONCOURSE
450
1,080 SF @ 100/= 11 OCCUPANTS
453
BINGO ROOM 6,260 SF @15SF/ OCCUPT = 417 ACTUAL LOAD 432 OCCUPANTS + 1153 SF @ 100SF/ OCCUPT = 12 TOTAL OCCUPANT LOAD = 450
GIFT SHOP 268 SF @ 30/= 9 OCCUPANTS
1220 1360
B
680
90 MIN. DOOR
6. Furring Channels -- (Optional, not shown, for single or double layer systems) -- Resilient furring channels fabricated from min 25 MSG corrosion-protected steel, spaced vertically a max of 24 in. OC. Flange portion attached to each intersecting stud with 1/2 in. long Type S-12 steel screws. Not for use with Item 4A. 6A. Steel Framing Members (Not Shown)* -- (Optional on one or both sides, not shown, for single or double layer systems) -As an alternate to Item 6, furring channels and Steel Framing Members as described below: a. Furring Channels -- Formed of No. 25 MSG galv steel. 2-3/8 in. wide by 7/8 in. deep, spaced max. 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Gypsum board attached to furring channels as described in Item 5. Not for use with Item 4A. b. Steel Framing Members* -- Used to attach furring channels (Item 6Aa) to studs (Item 2). Clips spaced max. 48 in. OC., and secured to studs with No. 8 x 1-1/2 in. minimum self-drilling, S-12 steel screw through the center grommet. Furring channels are friction fitted into clips.
EGRESS CAPACITY
FX
HATCHED AREA INDICATES AREA OF SPRAY-ON FIRE PROOFING. 1-HR COLUMNS & 1-HR UNDER ROOF
CASINO WITH NEW ADDITION
BUILDING #3/ TYPE II-A EXISTING CASINO 15SF/PERSON USED ON GAMING FLOOR PER ORIGINAL CODE MODIFICATION. REFER TO ATTACHED SHEET G-LS-102 R1 BY HNEDAK BOBO GROUP. (SEE NOTE #1 ABOVE)
EXISTING CASINO = 55,489 GSF SLOTS ADDITION 5,475 NEW GSF @15SF/ OCCUPT = 365 NEW OCCUPANTS TOTAL 60,964 GSF
PREVIOUS EXITING OCCUPANTS FROM EAST SIDE OF EXISTING BUILDING - 1615 NEW OCCUPANTS ADDED FROM NEW ADDITION - 55 TOTAL EAST OCCUPANTS - 1670 NEW EAST EXITS PROVIDE EXITING FOR 1813 OCCUPANTS
450
OCCUPANT LOAD
906
# OF OCCUPANTS EGRESS CAPACITY PROVIDED FOR 225
837 NEW OCCUPANTS TOTAL IN ADDITIONS
CONSTRUCTION TYPE AND USE - IBC TABLE 503 SPRINKLERED - NFPA 13 CONSTRUCTION TYPE II-A OCCUPANCY GROUP A-2
AREA EXISTING CASINO = 55,489 GSF CASINO ADDITION = 5,475 GSF TOTAL = 60,964 GSF ALLOWABLE AREA BASIC ALLOWABLE BUILDING AREA, TABLE 503 = 15,500 SF FRONTAGE INCREASE, 506.2 If = [ F/P-.025 ] W/30 If = [ 773.25FT/1325.5FT - 0.25 ] 30/30 = .33 AUTOMATIC SPRINKLER SYSTEM INCREASE, 506.3 ONE-STORY SPRINKLER INCREASE ( Is ) = 300% = 3 AREA MODIFICATION, 506.1 Aa = {At+[ At x If ] + [ At x Is ] } Aa = { 15500 + [ 15500 x 0 ] + [ 15500 x 3 ] } = 62000 SF ALLOWABLE HEIGHT & STORIES - TABLE 503 ALLOWED = 65 FT ACTUAL = 25 FT ALLOWED = 3 STORIES ACTUAL = 1 STORY FIRE-RESISTIVE REQUIREMENTS - TABLE 601 TYPE II-B STRUCTURAL FRAME 1 HOURS BEARING WALLS, EXTERIOR 1 HOURS BEARING WALLS, INTERIOR 1 HOURS NON BEARING WALLS 0 HOURS FLOOR CONSTRUCTION 1 HOURS ROOF 1 HOURS
453
STORAGE 142 SF @ 300/= 1 OCCUPANTS
797
CODE ANALYSIS: PROJECT DESCRIPTION: NEW 1 STORY ADDITIONS TO EXISTING BUILDING LOCATION: PRAIRIE BAND CASINO & RESORT MAYETTA,KS
BUILDING: NEW COMMERCIAL · EXTERIOR WALLS - METAL STUDS W/ EIFS · FLOOR - SLAB ON GRADE. · STRUCTURE -STEEL - PROTECTED @ TYPE IIA · STRUCTURE -STEEL - UNPROTECTED @ TYPE IIB · ROOF - METAL DECKING ON STEEL JOIST - PROTECTED @ TYPE IIA · ROOF - METAL DECKING ON STEEL JOIST - UMPROTECTED @ TYPE IIB ARCHITECT: H2B ARCHITECTS 1800 BALTIMORE KANSAS CITY, MO. 64108 816.979.1800 www.h2barch.com APPLICABLE CODES: INTERNATIONAL BUILDING CODE (IBC), 2012 EDITION INTERNATIONAL MECHANICAL CODE (IMC), 2012 EDITION UNIFORM PLUMBING CODE (UPC), 2012 EDITION INTERNATIONAL FIRE CODE (IFC), 2012 EDITION NATIONAL ELECTRICAL CODE, 2011 EDITION INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2012 EDITION AMERICAN WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADDAAG) AMERICAN NATIONAL STANDARDS INSTITUTE STANDARDSICC/ANSI-A117.1 PROVIDING ACCESSIBILITY AND USABILITY FOR PHYSICALLY HANDICAPPED PEOPLE, 2009 EDITION
EVENT CENTER WITH NEW BINGO ADDITION
907
EXISTING EVENT CENTER = 30,994 GSF BINGO ADDITION 8,112 NEW GSF TOTAL 39,106 GSF OCCUPT = 472 NEW OCCUPANTS
EGRESS CAPACITY = PROVIDED SIZE. CALCULATED AT 0.15 INCH PER OCCUPANT
* EXISTING OCCUPANCY LOADS AND EGRESS CAPAICTIES BASED ON LIFE SAFETY PLAN PREPARED UNDER ARCHITECT OF RECORD-HNEDAK BOBO GROUP (SHEET G-LS-101 DATED 06.14.05) REFER TO THE SUPPLEMENTAL ORIGINAL CODE PLANS FOR MODIFICATIONS SUBMITTED AND APPROVED UNDER THE ORIGINAL HOTEL AND EVENT CENTER EXPANSION PROJECT.
PLUMBING REQUIREMENTS NEW ADDED OCCUPANTS CASINO/SLOTS = 365 BINGO = 451 TOTAL = 816 NEW OCCUPANTS / GENDER = 408 WC - 1 / 75 = 6 / GENDER LAV - 1 / 200 = 3 / GENDER DRINKING FOUNTAIN - 1 / 500 = .37 1 SERVICE SINK
CONSTRUCTION TYPE AND USE - IBC TABLE 503 SPRINKLERED - NFPA 13 CONSTRUCTION TYPE II-B OCCUPANCY GROUP A-2
PROJECT:
CANADIAN GYPSUM COMPANY -- Type SHX. UNITED STATES GYPSUM CO -- Type SHX. USG MEXICO S A DE C V -- Type SHX.
2040
680
EDGE OF NEW CONSTRUCTION
EXISTING
When Item 6B, Steel Framing Members*, is used, Nonbearing Wall Rating is limited to 1 Hr. Min. stud depth is 3-1/2 in., min. thickness of insulation (Item 3) is 3 in., and two layers of gypsum board panels (1/2 in. or 5/8 in. thick) shall be attached to furring channels as described in Item 5. One layer of gypsum board panels (1/2 in. or 5/8 in. thick) attached to opposite side of stud without furring channels as described in Item 5.
OCCUPANT LOAD
MAYETTA, KANSAS
OCCUPANT LOAD
1814
EXISTING
3012
J&S STRUCTURAL ENGINEERS
PRAIRIE BAND CASINO AND RESORT
BUILDING #3/ TYPE II-A EXISTING CASINO 15SF/PERSON USED ON GAMING FLOOR PER ORIGINAL CODE MODIFICATION. REFER TO ATTACHED SHEET G-LS-102 R1 BY HNEDAK BOBO GROUP. (SEE NOTE #1 ABOVE)
CANADIAN GYPSUM COMPANY -- 1/2 in. thick Type C, IP-X2 or IPC-AR; WRC, 5/8 in. thick Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRX or WRC; 3/4 in. thick Types IP-X3 or ULTRACODE UNITED STATES GYPSUM CO -- 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in.thick Type SCX, SHX, WRX, IP-X1, AR, C, WRC, FRX-G, IP-AR, IP-X2, IPC-AR ; 3/4 in. thick Types IP-X3 or ULTRACODE USG MEXICO S A DE C V -- 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in. thick Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRX, WRC or; 3/4 in. thick Types IP-X3 or ULTRACODE
5. Fasteners -- (Not shown) -- Type S or S-12 steel screws used to attach panels to studs (Item 2) or furring channels (Item 6). Single layer systems: 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for 3/4 in. thick panels, spaced 8 in. OC when panels are applied horizontally, or 8 in. OC along vertical and bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer systems: First layer- 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels or 2-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC with screws offset 8 in. from first layer. Three-layer systems: First layer- 1 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long for 1/2 in., 5/8 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below. Four-layer systems: First layer- 1 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long for 1/2 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 24 in. OC. Fourth layer- 2-5/8 in. long for 1/2 in. thick panels or 3 in. long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below.
BUILDING #4/ TYPE II-B EVENT CENTER NO MAIN EXIT-PER ORIGINAL CODE MODIFICATION REFER TO ATTACHED SHEET G-LS-102 R1 BY HNEDAK BOBO GROUP
NEW
D
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
PRAIRIE BAND BINGO & SLOT EXPANSION
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
AREA EXISTING EVENT CENTER = 30,994 GSF EXISTING EVENT CENTER = 8,112 GSF TOTAL = 39,106 GSF ALLOWABLE AREA BASIC ALLOWABLE BUILDING AREA, TABLE 503 = 9,500 SF FRONTAGE INCREASE, 506.2 If = [ F/P-.025 ] W/30 If = [ 651.5FT/904.5FT - 0.25 ] 30/30 = .47
Copyright 2015 H2B architect, inc.
AUTOMATIC SPRINKLER SYSTEM INCREASE, 506.3 ONE-STORY SPRINKLER INCREASE ( Is ) = 300% = 3
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
AREA MODIFICATION, 506.1 Aa = {At+[ At x If ] + [ At x Is ] } Aa = { 9500 + [ 9500 x .47 ] + [ 9500 x 3 ] } = 42,465 SF
ISSUED FOR:
SHELL PACKAGE
ALLOWABLE HEIGHT & STORIES - TABLE 503 ALLOWED = 55 FT ACTUAL = 25 FT ALLOWED = 2 STORIES ACTUAL = 1 STORY
SHEET TITLE:
FIRE-RESISTIVE REQUIREMENTS - TABLE 601 TYPE II-B STRUCTURAL FRAME 0 HOURS BEARING WALLS, EXTERIOR 0 HOURS BEARING WALLS, INTERIOR 0 HOURS NON BEARING WALLS 0 HOURS FLOOR CONSTRUCTION 0 HOURS ROOF 0 HOURS
CODE FLOOR PLAN 1/16"=1'-0"
A1
CODE FLOOR PLAN
DATE:
09.23.15
JOB NO.:
1016
SHEET:
PLAN NORTH
NORTH
A101
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS
PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
PROJECT:
C
MAYETTA, KANSAS
F.D.
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
B
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
SITE PLAN
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
SITE PLAN 1" = 20'-0"
A1
A102
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
S
FS
S
S
FS
S
FS S
S
EXISTING CONCOURSE S 104
FS
S
FS
S
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
S
T
S
S
EXIST SERVER 133
EXIST ELEC 129 MEN'S 127
HIGH LIMIT SLOTS 135
CONFERENCE ROOM 108
S S S
CONCOURSE 103
S S FS
STOR 105
STORAGE 112
S
OFFICE 110
OFFICE 111
STOR 109
S
ELEC 128
FS
S
S
S
ELEC 106
S
S
STOR 134
S S
E
S
S
S
FS S
MEN'S 126
S
S
T
S
S
S
S
STOR 107
GAMING 132
MOP 130
WOMEN'S 125 S S
S
S
S
FAMILY 131
S
WOMEN'S 124
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
CONCESS 114
S
S
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
DISPLAY 123
S
ELECTRICAL ENGINEER:
BINGO HALL 113
CALLER 115 3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CONCOURSE 102
STOR 116
CIVIL ENGINEER:
ENGINEERS
PRIVATE OFFICE 118
GIFT SHOP 122
cfse.com STRUCTURAL ENGINEER:
J&S STRUCTURAL ENGINEERS
BINGO CAGE 117
STOR 121
STOR 120
CEILING PLAN 3/32" = 1'-0"
D1
C EXISTING CONCOURSE 104
EXIST SERVER 133
EXIST ELEC 129 CONCOURSE 103
MEN'S 127
HIGH LIMIT SLOTS 135
CONFERENCE ROOM 108
STOR 105
STORAGE 112 OFFICE 110 STOR 109
ELEC 128
OFFICE 111
ELEC 106 CONCESS 114
STOR 134
PROJECT:
MEN'S 126 STOR 107
GAMING 132
MOP 130
WOMEN'S 125
B
S S
FAMILY 131
S
S
S
S WOMEN'S 124
MAYETTA, KANSAS
VESTIBULE 101
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
OFFICE 119
DISPLAY 123
S
BINGO HALL 113
CALLER 115
CONCOURSE 102
STOR 116 Copyright 2015 H2B architect, inc.
PRIVATE OFFICE 118
GIFT SHOP 122
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
BINGO CAGE 117
ISSUED FOR:
SHELL PACKAGE
OFFICE 119 VESTIBULE 101
SHEET TITLE:
REFERENCE FLOOR & CEILING PLAN
STOR 121
STOR 120
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
FLOOR PLAN 3/32" = 1'-0"
A1
A103
9
8
7
6
5
4
3
2
1
REMOVE, SALVAGE & REINSTALL EXISTING CEILING AS REQUIRED FOR NEW MECH. INSTALLATION
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
RESTRUCTURE STEEL SUPPORT FOR EXISTING LIGHT FIXTURE
F EXISTING CEILING TO REMAIN S
FS
S
S
FS
S
FS
FS
S
S
S
S
FS
EXISTING ENTRY CANOPY TO REMAIN
S
S
EXISTING CEILING TO REMAIN
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
EXISTING CEILING TO REMAIN
DEMO EXISTING GYP BOARD CEILING T
S
S FS
S
S S S
S S FS
EXISTING CEILING TO BE REMOVED
S
S
S
DEMO EXISTING GYP BOARD CEILING
S S
EXISTING CEILING TO REMAIN
S
S
E
DEMO EXISTING GYP BOARD CEILING
T
DEMO LAY-IN CEILING
S
S
S
S
FS
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
S S
S S
S
S
S
S
S
MECHANICAL & PLUMBING ENGINEER:
DEMO DUCTWORK REFER TO MEP DEMO LAY-IN CEILING
EXISTING CEILING TO REMAIN
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
DEMO EXISTING GYP BOARD CEILING
DEMO BEAMS
CEILING LEGEND HVAC DIFFUSER HVAC EXHUST
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
HVAC EXHUST
CIVIL ENGINEER:
LIGHT FIXTURE cfse.com STRUCTURAL ENGINEER:
D1
D
PLAN NORTH
C
EXISTING SUMP REFER TO MEP DWGS.
DEMO STUD WALL AND PRECAST WALL FOR NEW OPENING
EXISTING COLUMN TO REMAIN
SLOPED ROOF & STRUCTURE THIS AREA TO BE REMOVED
DEMO PRECAST OPENING FOR NEW DUCT WORK. REFER TO MEP DWGS FOR LOCATION AND SIZE
REMOVE CULTURED STONE ON FACE OF WALL TO REMAIN
SLOPED ROOF & STRUCTURE THIS AREA TO BE REMOVED
F.V.
EXISTING DECORATIVE COLUMN WRAP (CULTURED STONE & METAL STUDS) TO BE REMOVED. EXISTING STRUCTURAL STEEL COLUMN TO REMAIN.
REMOVE EXISTING CONC. FLOOR SLAB AS REQ'D FOR INSTALLATION OF NEW FTGS AT NEW COLUMNS. INSTALL NEW SLAB AS REQ'D. TYP. SEE STRUCT. DWGS.
DEMOLITION LEGEND 5.
1.
ALL BIDDERS SHALL VISIT AND TOUR BUILDING PRIOR TO BIDDING THE PROJECT.
6.
2.
COMPLETE ALL DEMOLITION WORK SHOWN AND SPECIFIED. SEE FLOOR PLANS FOR ADDITIONAL INFORMATION.
7.
3.
ALL DEMOLITION MATERIAL IS TO BE DISPOSED OF OFF SITE AS SPECIFIED UNLESS OTHERWISE NOTED. DEMOLITION CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTING DEMOLITION. ANY AND ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OWNER AND ARCHITECT.
EDGE OF SLAB TO REMAIN
EXISTING COLUMN TO BE REMOVED REFER TO STRUCTURAL DWGS
GENERAL DEMOLITION NOTES:
4.
PROJECT:
LINE OF ROOF AND ROOF STRUCTURE ABOVE TO BE REMOVED. ADJACENT EXISTING BEAM TO REMAIN. PROVIDE SHORING AS REQUIRED.
DEMO EXISTING CASEWORK
EDGE OF SLAB TO REMAIN
B
EXIST. ROOF TO REMAIN
EXIST. ROOF TO REMAIN
EXISTING ELECTRICAL ROOM & ELECTRICAL EQUIPMENT TO REMAIN AND REMAIN ACTIVE DURING ALL PHASES OF CONSTRUCTION. EXTREME CARE IS TO BE TAKEN TO PROTECT THIS AREA DURING REMOVAL OF THE ROOF ABOVE AND DURING DEMOLITION.
EXISTING ELECT. PANELS TO BE RELOCATED TO ADJCENT NEW WALL. SEE PLANS & ELECT. DWGS.
EXIST. ROOF TO BE REMOVED
LINE OF ROOF & ROOF STRUCTURE ABOVE TO BE REMOVED. ADJACENT EXISTING BEAM TO REMAIN.
EXIST. ROOF TO BE REMOVED
EXISTING SERVER ROOM & COMPUTER EQUIPMENT TO REMAIN AND REMAIN ACTIVE DURING ALL PHASES OF CONSTRUCTION. EXTREME CARE IS TO BE TAKEN TO PROTECT THIS AREA DURING REMOVAL OF THE ROOF ABOVE AND DURING DEMOLITION.
EXISTING COLUMNS TO REMAIN REFER TO STRUCTURAL
EXISTING RESTROOM TO REMAIN
EXIST. ROOF TO REMAIN
EXIST. ROOF TO REMAIN
REMOVE EXISTING CONC. FLOOR SLAB AS REQ'D FOR INSTALLATION OF NEW FTGS AT NEW COLUMNS. INSTALL NEW SLAB AS REQ'D. TYP. SEE STRUCT. DWGS.
NORTH
MAYETTA, KANSAS
3/32" = 1'-0"
J&S STRUCTURAL ENGINEERS
PRAIRIE BAND CASINO AND RESORT
DEMO CEILING PLAN
PRAIRIE BAND BINGO & SLOT EXPANSION
EL
ENGINEERS
CAN FIXTURE EXIT SIGN EMERGENCY LIGHT TRACK FIXTURE
8.
9.
COMPLY WITH ALL APPLICABLE CODES, REGULATIONS AND SAFETY GUIDELINES OF ALL PUBLIC AUTHORITIES HAVING JURISDICTION.
EXISTING WALL TO REMAIN
SEE MECHANICAL, PLUMBING & ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
EXISTING WALL TO BE REMOVED
Copyright 2015 H2B architect, inc.
THE CONTRACTOR SHALL PROVIDE PROPER SHORING TO SUPPORT ALL EXISTING WORK TO REMAIN DURING DEMOLITION. ALL SHORING IS TO BE LOCATED AND ENGINEERED BY THE CONTRACTOR.
EXISTING DOOR TO REMAIN
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
PROTECT ALL EXISTING STRUCTURE TO REMAIN AFFECTED BY THE DEMOLITION PROCESS. PATCH AND REPAIR ALL AREAS OF EXISTING CONSTRUCTION TO REMAIN,THAT ARE DAMAGED DURING DEMOLITION TO MATCH ADJACENT CONSTRUCTION, MATERIAL AND FINISH. NOT ALL DEMOLITION IS SHOWN. REMOVE EXISTING MATERIALS AS REQUIRED FOR INSTALLATION OF ALL MEP, ETC. REPAIR AS REQUIRED.
EXISTING DOOR & FRAME TO BE REMOVED ISSUED FOR:
SHELL PACKAGE
DEMO FLOOR PLAN 3/32" = 1'-0"
SHEET TITLE:
A1 PLAN NORTH
NORTH
DEMO OVERALL FLOOR & CEILING PLAN
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
A201
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS
PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
S
FS
S
S
FS
S
FS
FS S
S
FS
S
S
PROJECT:
S
S
S
S
B
FS S
MAYETTA, KANSAS
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
S
S S
S S FS
S
S
S S S
S
S S
S
S
S
FS
Copyright 2015 H2B architect, inc.
S
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
S S S
S
S
S
S S
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
RCP DEMO PLAN PHASE ONE
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
DEMO REFLECTED CEILING PLAN 1/8" = 1'-0"
A1
A213 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
S
FS
PROJECT:
T
S S
MAYETTA, KANSAS
C
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
S S FS
S
B
S
S
S
T
S
S Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
RCP DEMO PLAN PHASE TWO
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
DEMO REFLECTED CEILING PLAN 1/8" = 1'-0"
A1
A214 PLAN NORTH
NORTH
7
6
5
4
F
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
EXIST SOFFIT EL. +9'-5"
T
FS
FS S
S
S
FS
S
S
R54'-0"
S
S S
4'-1"
GYP CEILING EL. +9'-11 1/2"
LAY-IN CEILING EL. +11'-0"
FS
S
GYP CEILING EL. +8'-6"
GYP SOFFIT EL. +8'-0"
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +14'-0"
GYP CEILING EL. +10'-11 1/4" ±
LAY-IN CEILING EL. +15'-0"
S
GYP CEILING EL. +8'-0" GYP CEILING EL. +10'-0"
GYP CEILING EL. +8'-6"
LAY-IN CEILING EL. +10'-0"
S
S
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +10'-0"
S
S LAY-IN CEILING EL. +12'-0"
S
LAY-IN CEILING EL. +12'-0"
S
GYP CEILING EL. +15'-0"
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +10'-0"
GYP CEILING EL. +8'-6"
D SE BI HA P
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
GYP CEILING EL. +20'-0"
GYP CEILING EL. +8'-0" S HEADER EL. +8'-0"
MECHANICAL & PLUMBING ENGINEER:
GYP CEILING EL. +8'-6"
GYP CEILING EL. +10'-0"
GYP CEILING EL. +11'-0" LAY-IN CEILING EL. +12'-0"
C H LI A N 3 E A3 14 13
LAY-IN CEILING EL. +12'-6"
LAY-IN CEILING EL. +12'-6"
LAY-IN CEILING EL. +10'-0"
LAY-IN CEILING EL. +12'-0"
GYP CEILING EL. +10'-0"
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
2
M AT
LAY-IN CEILING EL. +14'-6"
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +10'-0"
LAY-IN CEILING EL. +10'-0"
R20'-0"
S
LAY-IN CEILING EL. +11'-4"
GYP CEILING EL. +20'-0"
LAY-IN CEILING EL. +13'-6"
LAY-IN CEILING EL. +12'-6"
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
S
S
E GYP CEILING EL. +12'-0"
S
S
GYP CEILING EL. +10'-0"
LAY-IN CEILING EL. +14'-6"
FS
S
LAY-IN CEILING EL. +12'-6"
LAY-IN CEILING EL. +13'-6"
S
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
LAY-IN CEILING EL. +10'-0"
R28'-0" LAY-IN CEILING EL. +13'-6"
1
EXIST GYP CEILING EL. +10'-11 1/2"
6'-0" 12'-0"
'-0" R 40
6'-0" 6'-0"
R18'-0 "
GYP CEILING EL. +13'-10"
LAY-IN CEILING EL. +14'-6"
S
EXIST GYP CEILING EL. +11'-0"
GYP CEILING EL. +10'-6"
LAY-IN CEILING EL. +13'-6"
FS
EXIST SOFFIT EL. +9'-5"
GYP CEILING EL. +12'-2"
LAY-IN CEILING EL. +15'-6"
S
S
MATCHLINE
EXIST SOFFIT EL. +9'-5"
4'-0"
EXIST SOFFIT EL. +9'-5"
2
BID PHASE 1
A314
BID PHASE 2
3 REMOVE, SALVAGE & REINSTALL EXISTING CEILING AS REQUIRED FOR NEW MECH. INSTALLATION RESTRUCTURE STEEL SUPPORT FOR EXISTING LIGHT FIXTURE
A313
8
MATCHLINE
9
D SE BI HA P
LAY-IN CEILING EL. +10'-0"
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
1
GYP CEILING EL. +10'-0"
LAY-IN CEILING EL. +10'-0"
CIVIL ENGINEER:
ENGINEERS
LAY-IN CEILING EL. +10'-0"
cfse.com
GYP CEILING EL. +9'-11-3/8"
STRUCTURAL ENGINEER:
J&S STRUCTURAL ENGINEERS
3/32" = 1'-0"
D1 PLAN NORTH
1" 3'-74
CONFERENCE ROOM 108
STOR 105
STORAGE 112 OFFICE 110 STOR 109
ELEC 128
OFFICE 111
B1/A401
105 128
1" 30'-92
CONCOURSE 103
MEN'S 127
A1 A502
HIGH LIMIT SLOTS 135
EXIST ELEC 129
A1 A507
106
ELEC 106
B 114
CONCESS 114
STOR 134
10'-83 4" 3'-5"
D 12'-11"
CALLER 115
20'-6"
CONCOURSE 102
STOR 116
122
A1 A504
GIFT SHOP 122
22'-27 8"
28'-0"
PRIVATE OFFICE 118
116
6'-2"
A1 A503
E
D1 A501
8
19'-23 4"
3'-11"
D1 A501 15'-9"
A
5'-0"
9
4'-0"
9.3 10
13.1 1" 16'-102
5'-0"
11
5'-8"
12 1" 44'-102
6'-3"
15.6
22'-0"
19'-23 4"
8'-4"
13
15'-10"
16.2
H.8 J
6'-2"
16.6
1'-4"
9.5
14
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
22'-0"
15.2 2'-0"
1" 12'-22
113B
A5 A507
61'-87 8"
A1/A401
1'-10" 6'-2"
101B
101A
J.2
H
SHELL PACKAGE
17.2
A1 A506
7
1
STOR 120 120
D2/A401
6 157'-07 8"
E
J
Copyright 2015 H2B architect, inc.
117
SHEET TITLE:
OVERALL FLOOR & CEILING PLAN
A4 A507
25'-0"
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
AS
G
119
A1 A505
5
32'-43 8"
101D
101C 121
A3 12 11 D5/A401
A3
H
LI
N
E
A1 A502
A4 A502
25'-0"
PH
F.7
OFFICE 119
STOR 121
M
AT C
H
F.1
BINGO CAGE 117
VESTIBULE 101
D
25'-0"
4
8.7
BI
3
2
2
15'-0"
D SE BI HA P
1" 6'-72
8.1
7.3
6.6
5.6
22'-0"
22'-0"
22'-0"
4.6
3.7
1.8 28'-1"
1
8.3
1 25'-216"
22'-0"
22'-0"
22'-0"
1.1
ANGLED GRIDLINE
C.2
10'-7"
113A
8"
2'-0"
S
BINGO HALL 113
B7/A401
B5/A401
FAMILY 131
S WOMEN'S 124
G ANGLED GRIDLINES
A1 A501
B8/A401
S
C
8'-0"
XX
YY
9'-2"
6'-2"
ZZ
B5/A401
F
132D
E.8
°
132C
132A
E.2
E.4 132B
88
3'-0"
5'-6"
E
S
2'-2"
1" 5'-82
D.4
S
DISPLAY 123
B2/A401
S S
D
B
WOMEN'S 125
A5 A503
14'-0"
A2 A501
130 MOP 130
131
STOR 107
118
C
107
A9 A504
GAMING 132
134
5'-10"
MEN'S 126
B.4
PROJECT:
A2 A507
64'-6"
EXIST SERVER 133
1" 3'-72 4'-8"
C
EXISTING GRIDLINE
1" 15'-92
EXISTING GRIDLINE
1" 6'-44
65'-35 8"
1'-10"
EXISTING CONCOURSE 104
1" 8'-32
32'-43 8"
25'-0"
10
112B
25'-0"
8
112A
25'-0"
7
111
15'-0"
6
109B
1'-10"
5
4
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
109A
1" 6'-72
28'-1"
A
3
2
BID PHASE 1
MATCHLINE
1
BID PHASE 2
A311
ELECT. ROOM EQUIPMENT TO REMAIN IN SERVICE DURING CONSTRUCTION. CONTRACTOR TO TAKE ALL NECESSARY MEANS TO PROTECT EQUIPMENT AND ENSURE SERVICE
A312
SERVERS TO REMAIN IN SERVICE DURING CONSTRUCTION. CONTRACTOR TO TAKE ALL NECESSARY MEANS TO PROTECT EQUIPMENT AND ENSURE SERVICE
NORTH
MAYETTA, KANSAS
CEILING PLAN
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
LAY-IN CEILING EL. +10'-0"
41'-8"
29'-8"
15
16
14'-5"
16.7
6'-2"
17
104'-113 4"
368'-8"
DATE:
09.23.15
JOB NO.:
1016
SHEET:
FLOOR PLAN 3/32" = 1'-0"
A1
A301 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
EXISTING BUILDING TO RECEIVE NEW MEMBRANE ROOFING AS REQUIRED DUE TO DEMOLITION, NEW CONSTRUCTION AND NEW DRAINAGE
E
MECHANICAL & PLUMBING ENGINEER:
HATCHED AREAS INDICATE NEW MEMBRANE ROOF AREAS TO RECEIVE RECOVERY BD.
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
NEW MEMBRANE ROOF
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
NEW MEMBRANE ROOF
CIVIL ENGINEER:
NEW MEMBRANE ROOF
ENGINEERS cfse.com
SKYLIGHT
STRUCTURAL ENGINEER:
SLOPED STANDING SEAM METAL ROOF
J&S STRUCTURAL ENGINEERS
D
MATCHLINE
3/64" = 1'-0"
7
8
10
NEW TAPERED ROOFING INSULATION TO SLOPE TO NEW ROOF DRAINS
EXISTING FALSE WALL TO REMAIN EXISTING ROOF TO REMAIN, NO WORK
7
8
C
LINE OF EXISTING ROOF TO BE REMOVED
SLOPE
R.T.U.
SLOPE
ALL ROOF TOP EQUIPMENT TO BE LOCATED A MIN. 10'-0" AWAY FROM PARAPET, TYP.
INSTALL TAPERED ROOFING CRICKET AT ALL CURBS, TYP.
9.3 10
ISSUED FOR:
SHELL PACKAGE
SLOPE
SLOPE
11
G
SHT. MTL. COPING TYP. AT PARAPETS
A5 A507
SHEET TITLE:
OVERALL ROOF PLAN
H.8 J
15.6
16.2
CURVED STANDING SEAM METAL ROOF
9.5
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
F.7
H
15.2
9
D
SLOPE
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON SLOPED METAL ROOF DECK.
SEAM METAL ROOF SLOPED OVERBUILD
J.2
PROJECT:
SLOPE
SLOPE SLOPE
73 8" 1" 47'-24
D5 A506
SLOPE SLOPE
MATCHLINE
B.4
16.6
SLOPED STANDING SEAM METAL ROOF
17.2
A1 A506
6
B
SLOPE
C.2
ROOF DRAIN & OVERFLOW DRAIN W/ CAST IRON STRAINER. OVERFLOW DRAIN INLET TO BE 2" HIGHER THAN PRIMARY ROOF DRAIN SEE PLUMBING DWGS. TYP.
J
A1 A505
5
1
4
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
KAWNEER, SERIES 1600 SLOPED GLAZING, 2-1/2"X"6 OR EQ. ANODIZED ALUM., W/ TINTED, INSULATED, LAMINATED GLAZING
5'-0" SQ. WALK PAD
ROOF STRUCTURE SLOPES APPROX. 1/4" PER FOOT
SLOPE
7'-73 8"
BI D
SLOPE
R.T.U.
N LI
H
SLOPE
F.1
SLOPE
A3
A4 A502
A1 A502
A1 A501
11
M
E
3
H
8.7
E1 A515
TAPERED ROOFING INSULATION CRICKETS TO SLOPE TO ROOF DRAINS
G
C T A
AS
2
E
PH
1
8.1
8.3
2
A
1.8
7.3
6.6
12 3 A
D SE BI HA P
1.1
ROOF DRAIN & OVERFLOW DRAIN W/ CAST IRON STRAINER. OVERFLOW DRAIN INLET TO BE 2" HIGHER THAN PRIMARY ROOF DRAIN SEE PLUMBING DWGS. TYP.
SLOPED STANDING SEAM METAL ROOF
5.6
4.6
SLOPE
PREFINISHED, INSULATED, 3'-0" X 3'-0" STEEL ROOF HATCH W/ MECHANICAL LIFT ASSIST, LOCKABLE LATCH, CURB AND FLASHING.
WALK THRU W/ PAINTED STEEL LADDER. MIN. 18" WIDE, 1 1/4" SERRATED RUNGS, 12" O.C.,
LINE OF EXISTING ROOF TO BE REMOVED SLOPE
A1 A504
SLOPE
ROOF DRAIN & OVERFLOW DRAIN W/ CAST IRON STRAINER. OVERFLOW DRAIN INLET TO BE 2" HIGHER THAN PRIMARY ROOF DRAIN SEE PLUMBING DWGS. TYP.
SLOPE
E
E.2
EXPANSION JT. COVER TYP. BETWEEN NEW & EXISTING BUILDING 4'-0" SLOPE
SLOPE
73 8"
SLOPE
E.4
XX
3.7
A9 3 15'-7 " A504 4
SLOPE
SLOPE
ZZ YY
73 8"
SLOPE
SLOPE
SLOPE
E.8
F
SLOPE
SLOPE
SLOPE
SLOPE
SLOPE
E1 A515
SLOPE
A1 A503
SLOPE
FLASH AROUND EXISTING COLUMNS TO REMAIN.
SLOPE
DATE:
09.23.15
JOB NO.:
1016
SHEET:
13.1
12
13
14
A4 A507
SLOPE
SLOPE
SLOPE
SLOPE SLOPE
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. (AT RATED ROOFS SEE SHT. A101 & D1/A302) ON SLOPED METAL ROOF DECK.
SLOPE
NEW ROOF DRAIN & OVERFLOW AT EXISTING DECK
SLOPE
D.4 SLOPE
SLOPE
5'-0" SQ. WALK PAD
TAPERED ROOFING INSULATION CRICKETS TO SLOPE TO ROOF DRAINS
SHT. MTL. COPING TYP. AT PARAPETS
SLOPE
EXISTING SLOPED ROOF TO REMAIN
SLOPE
A1 A501
E
PREFINISHED, INSULATED, 3'-0" X 3'-0" STEEL ROOF HATCH W/ MECHANICAL LIFT ASSIST, LOCKABLE LATCH, CURB AND FLASHING.
INSTALL TAPERED ROOFING CRICKET AT ALL CURBS
A5 A503
ALL ROOF TOP EQUIPMENT TO BE LOCATED A MIN. 10'-0" AWAY FROM PARAPET, TYP.
C
D
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. (AT RATED ROOFS SEE SHT. A101 & D1/A302) ON SLOPED METAL ROOF DECK.
SLOPE
EXPANSION JT. COVER TYP. BETWEEN NEW & EXISTING BUILDING
LINE OF EXISTING ROOF TO BE REMOVED
R.T.U.
ROOF STRUCTURE SLOPES APPROX. 1/4" PER FOOT, TYP.
A1 A507
SLOPE
A1 A502
R.T.U.
EXPANSION JT. COVER TYP. BETWEEN NEW & EXISTING BUILDING
SLOPE
EXPANSION JT. COVER TYP. BETWEEN NEW & EXISTING BUILDING
EXISTING SLOPED ROOF TO REMAIN
B
EXPANSION JT. COVER TYP. BETWEEN NEW & EXISTING BUILDING
SLOPE
5'-0" SQ. WALK PAD
A A2 A507
EXISTING FALSE WALL TO REMAIN
SLOPE
INSTALL TAPERED ROOFING CRICKET AT ALL CURBS, TYP.
NORTH
EXISTING SLOPED ROOF TO REMAIN
6
SLOPE
5
4
NEW TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON NEW 4" (MIN. R-24) RIGID ROOFING INSULATION ON EXISTING METAL ROOF DECK. INSTALL NEW FLASHINGS AT PERIMETER AS REQUIRED TO PROVIDE WEATHER TIGHT CONDITIONS. TYP.
BID PHASE 1
A311
3
2
A312
1
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
PLAN NORTH
EXISTING ROOF TO REMAIN, NO WORK
BID PHASE 2
C
D1
MAYETTA, KANSAS
ROOF DIAGRAM
PRAIRIE BAND CASINO AND RESORT
CURVED STANDING SEAM METAL ROOF
PRAIRIE BAND BINGO & SLOT EXPANSION
SLOPED STANDING SEAM METAL ROOF
15
16
ROOF PLAN 3/32" = 1'-0"
A1
A302
17 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
OUTLINE OF EXISTING SLAB ON GRADE
ACCESS PANEL INTO CLOSET FOR DATA & POWER
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
'-0 67 "
WALKER DUCT LAYOUT FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com
AREA OF NEW SLAB ON GRADE
STRUCTURAL ENGINEER:
OUTLINE OF EXISTING SLAB ON GRADE
'-0 " 49
"
33'-10"
38
'-0
" '-0
"
" '-0 18
'-0
"
-0
6'
10
14'-0"
"
58'-0"
-0 2' WALKER DUCT LAYOUT
OUTLINE OF NEW WALKER DUCT
65'-07 8"
"
"
"
" '-0
24 '-0
"
'-0
-0
27
26
35
" '-0 34
'-0
35 " 36 '-0
" '-0
2'
18
" -0
"
34
6'
'-0
" '-0
"
18'-0"
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
"
27 '-0
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
'-0 " -0
1" 31'-72
89'-0"
29
34
"
2'
"
"
-0
" -0
"
'-0
2'
37
" '-0
" '-0 17
-0 "
6'
-0 38
'-0 46
' 40
B
ACCESS PANEL INTO NEW ELECTRICAL ROOM FOR SLOT AREA
" 6'
1" 5'-72
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
OUTLINE OF EXISTING SLAB ON GRADE
ACCESS PANEL INTO CLOSET FOR DATA & POWER
-0 2'
6' -0
"
ACCESS PANEL INTO CLOSET FOR DATA
BID PHASE 1
PROJECT:
OUTLINE OF EXISTING WALKER DUCT. FIELD VERIFY EXISTING CONDITIONS
NORTH
5'-6"
SAW CUT EXISTING FLOOR AS NEEDED FOR NEW WALKERDUCT IN THIS AREA
PLAN NORTH
23'-43 4"
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
D1
A311
C
A312
BID PHASE 2
MATCHLINE
3/32" = 1'-0"
MAYETTA, KANSAS
(ALT.) WALKER DUCT FLOOR PLAN
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
AREA OF NEW SLAB ON GRADE
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
155'-7"
2 A
1 31
ISSUED FOR:
16'-2"
20'-10"
16'-0"
SHELL PACKAGE
16'-0"
OVERALL WALKER DUCT PLAN
8'-0"
AS
PH
E 1
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
SHEET TITLE:
AREA OF NEW SLAB ON GRADE
BI D
A
1'-0"
H AT C
2
8'-0"
M
B PH ID AS E
LI
N
E
1 A3
69'-0" 94'-13 8"
DATE:
09.23.15
JOB NO.:
1016
SHEET:
(BASE BID) WALKER DUCT FLOOR PLAN 3/32" = 1'-0"
A1
A303 PLAN NORTH
NORTH
9
8
7
6
5
4
3
GENERAL PLAN NOTES: 1.
ALL BIDDERS TO VISIT AND TOUR BUILDING PRIOR TO BIDDING THE PROJECT.
EXISTING WALL TO REMAIN
COMPLY WITH ALL APPLICABLE CODES, REGULATIONS, ADA / ACCESSIBILITY, LIFE SAFETY AND SAFETY GUIDELINES.
3.
ALL SUBCONTRACTORS SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH THE EXISTING BUILDING, CONDITIONS AND EXTENTS OF WORK PRIOR TO BIDDING.
4.
FIELD VERIFY EXISTING WALLS AND CONDITIONS.
5.
NOTIFY ARCHITECT OF ANY OF ANY DISCREPANCIES BETWEEN THE PROJECT DOCUMENTS AND EXISTING CONDITIONS.
NEW GYP. BD. WALL, SEE WALL TYPES.
7.
SEE STRUCTURAL, MECHANICAL, PLUMBING & ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
8.
ALL PENETRATIONS OF FIRE RATED FLOOR/CEILINGS AND WALLS TO BE PROPERLY FIRE STOPPED, FIRE CAULKED, DAMPERED, ETC. ARE REQUIRED TO MAINTAIN THE ASSEMBLIES FIRE-RATINGS.
NEW WALL TYPE
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
NEW DOOR
A
DO NOT SCALE DRAWINGS.
WINDOW TYPE DESIGNATION
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
EXISTING DOOR TO REMAIN
101A
6.
9.
1
PLAN LEGEND
2.
F
2
16.2
DOOR NUMBER RE: SCHEDULE
STRUCTURAL GRIDLINE REFERENCE ELEVATION REFERENCE
C1/A603
CAULK ALL JOINTS BETWEEN DISSIMILAR MATERIALS. PROVIDE WEATHERTIGHT, WATERTIGHT AND AIRTIGHT PERFORMANCE.
A9 A504
SECTION REFERENCE
10. PROVIDE MOISTURE RESISTANT TYPE 'X' GYP. BD. AT TOILET ROOMS, JANITOR CLOSETS, MOP ROOMS AND ALL WALLS WITH SINKS LOCATED ON THEM, EXCEPT FOR WALLS TO RECEIVE CERAMIC TILE WHICH ARE TO BE CEMENT BD. THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
11. PROVIDE 2 X SOLID FIRE TREATED WOOD BLOCKING IN WALLS AS REQUIRED FOR CASEWORK, CABINETRY, COUNTERTOPS AND TOILET ACCESSORIES.
E
12. REPLACE AND REPAIR WALL WALLS, FLOORS, CEILINGS, ROOFING & MATERIALS AS REQUIRED FOR INSTALLATION OF ALL MEP ITEMS ETC.
MECHANICAL & PLUMBING ENGINEER:
13. PLAN DIMENSIONS ARE FROM COLUMN GRID. INTERIOR WALLS ARE FROM FACE OF FINISH MATERIAL. EXTERIOR WALLS ARE DIMENSIONED FROM OUTSIDE FACE OF STUD.
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
A1/A401
6" 1'-4"
7'-0"
7'-0"
NEW CONC. SIDEWALK, TYP. AT NEW DOORS. SLOPE AWAY FROM BUILDING., SEE CIVIL
1'-4"
19'-23 4"
5'-8" 1'-4"
7'-0"
7'-0"
1'-4" 6"
DIMENSIONS OF CONC. FTG. SEE STRUCT. DWGS
3'-11" FULL HT. CULTURED STONE ON 6" STUD FURRING
4'-2"
22'-0"
15'-9"
15.2
DIMENSIONS OF CONC. FTG. SEE STRUCT. DWGS
6'-3"
15.6
13.1
MAYETTA, KANSAS
PROJECT:
PRAIRIE BAND CASINO AND RESORT
67'-2"
1" 12'-22
H 8'-0"
6'-2"
22'-0"
16.2
H.8
15'-10"
J
6'-2"
16.6
17.2
DIMENSION TO OUTSIDE FACE OF STUD TYP. FOR EXTERIOR WALL PLAN DIMENSIONS
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
CONC. BANNER TIEDOWN W/ S.S. EYE BOLT. TYP. SEE D1/A501
A1/A401
16'-8"
9.5
4'-2"
D1 A501
64'-6"
12'-11" 1" 8'-32
4'-8"
11'-0"
1'-10"
6'-2"
D2/A401
EIFS OVER CULTURED STONE WAINSCOT
PRAIRIE BAND BINGO & SLOT EXPANSION
1" 6'-44 10'-83 4" STRUCT. STL. CROSS BRACING. SEE STRUCT. DWGS
10'-7"
B2/A401
3'-5"
D5 A603 D1/A603 D6/A603
23'-6"
LOW WALL, 42" ABOVE RAISED FLOOR
A6/A603
9'-10" 11'-0"
1'-4"
112A
1 2"
109B
109A
1" 15'-92
ALIGN
111
ALIGN
ALIGN
E6/A602 A1/A603
20'-6"
A5 A507
5'-1"
STOR 1'-4" 120 120
1" 14'-22
16'-8"
BINGO CAGE 117
A1 A506
DIMENSION TO OUTSIDE FACE OF STUD FOR EXTERIOR WALL PLAN DIMENSIONS A1
G
1'-4"
7'-6"
41'-5"
101D
8'-0"
J.2
F.7
117
101B
2'-0"
A801
ISSUED FOR:
SHELL PACKAGE 5'-0"
9 1'-4"
4'-0"
9.3
1" 16'-102
5'-0"
10
11
5'-8"
12 1" 44'-102 1" 47'-62
A
119
D
F.1
NEW CONC. SIDEWALK, TYP. AT NEW DOORS. SLOPE AWAY FROM BUILDING., SEE CIVIL
INSTALL GYP. BD. CONTROL JTS. AS REQUIRED BY MFR. TYP. WALLS, CEILINGS & SOFFITS
C.2
A4 A507
61'-87 8"
STRUCT. STL. CROSS BRACING. SEE STRUCT. DWGS
OFFICE 119
SLOPE
1
FULL HT. CULTURED STONE ON 6" STUD FURRING
101C
STOR 121
EIFS OVER CULTURED STONE WAINSCOT
J
4'-0" 121
H
VESTIBULE 101
101A
A
STRUCT. STL. CROSS BRACING. SEE STRUCT. DWGS
C
STOR 116
RAISED PLATFORM. 2'-2" AFF. 3/4" TREATED PLY. WD. ON 6" COLD METAL JSTS. 16" O.C.
FURRING WALLS AT NON-FIRE PROOFED COLUMN, TO BE LOCATED TIGHT TO STRUCTURE.
A
A1 A505
M
C9/A602 D9/A602
12'-10"
TC
D SE BI HA P
8
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
H
FX CABINET
2'-8"
2
32'-43 8"
N LI
8.7
45°
B1/A603
1'-0"
4'-1"
116
10'-11"
CALLER 115
D3/A603
1" 23'-02 A
5'-1"
8.1
D SE BI HA P
22'-0"
2 A3 11 D5/A401
A3 1
E
C
10'-11"
23'-6"
13'-0" 5'-3"
A1/A602
PRIVATE OFFICE 118
D7/A602
G
5'-3"
1" 9'-32 11'-9"
23'-5"
122
1-1/2" DIA. PAINTED STEEL HANDRAIL. RETURN TO WALL. MOUNT TOP OF RAIL 36" ABOVE LANDINGS & NOSINGS
4'-1"
CONCRETE SLAB ON GRADE TYP., SEE WALKERDUCT PAN. SEE STRUCT. DWGS. FOR CONTROL JTS., REINF., THICKNESS, ETC. ALIGN TOP OF SLAB W./ EXISTING BUILDING
5'-3"
A3/A602
C1/A602
D5/A602 C5/A602
C7/A602
CONCOURSE 102
B.4
45°
BINGO HALL 113
6'-8" B
GIFT SHOP 122
22'-27 8"
CONCESS 114
3'-8" CLEAR
118
28'-0"
5'-3"
113A
13'-0"
20'-6"
A1 A504
PAINTED STEEL ROOF ACCESS LADDER. MIN. 18" WIDE, 1 1/4" SERRATED RUNGS, 12" O.C., MAINTAIN MIN. 8" CLEARANCE FROM WALL/COLUMN.
FX CABINET
C1/A603
B
C
2-HR FIRE RATED WALL
DIMENSIONS OF CONC. FTG. SEE STRUCT. DWGS
B 114
8"
6'-8"
A7/A602
A5 A503
5'-8"
8.3
B
EXISTING BM.
STOR 107
SKYLT ABOVE
2'-10"
B7/A401
A1 A503
5'-8" 6'-2"
8"
2'-0"
CONC. BANNER TIEDOWN W/ S.S. EYE BOLT. TYP. SEE D1/A501
DISPLAY 123 2-HR FIRE RATED WALL
1'-4"
B1/A401
1'-0"
LOW FURRING WALL BELOW COUNTERTOP
E
112B
1'-6" 9'-6"
A9 A504
OFFICE 111
14'-7"
2'-0"
WOMEN'S 124
FAMILY 131
FURRING WALLS AT NON-FIRE PROOFED COLUMN, TO BE LOCATED TIGHT TO STRUCTURE.
107
WOMEN'S 125
2'-2"
131
ELEC 106
1" 7'-92
1" 6'-112 5'-03 4"
1" 1'-72 130 MOP 130
D.4
106
9'-6"
MEN'S 126
A1 A601
C
STOR 109
105
ALIGN
RUNGS, 12" O.C., MAINTAIN
E4/A602
OFFICE 110
STORAGE 112
113B
ALIGN
MEN'S 127
STOR 105
128
ELEC 128
CONCOURSE 103
J&S STRUCTURAL ENGINEERS EXISTING GRIDLINE
5"
CONFERENCE ROOM 108
cfse.com STRUCTURAL ENGINEER:
4'-11"
E1/A602
5'-10"
E3/A602
EXIST ELEC 129
F1/A602
ENGINEERS
1" 3'-72
MATCHLINE
D
F1/A602
MATCH EXISTING WALL TYPE & THICKNESS AT DOOR INFILL
EXISTING SIDEWALK TO REMAIN. SEE CIVIL
RELOCATED DRINKING FOUNTAINS SEE PLUMBING DWGS.
1" 3'-74
65'-35 8"
1'-10"
EXISTING CONCOURSE 104
2'-10"
32'-43 8"
10
CIVIL ENGINEER:
SLOPE
8
A311
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
BID PHASE 1
A312
BID PHASE 2
19'-23 4"
8'-4"
13
14
41'-8"
29'-8"
15
16 104'-113 4"
14'-5"
16.7
6'-2"
SHEET TITLE:
FLOOR PLAN PHASE ONE
17 1'-4"
104'-113 4"
368'-8" 371'-4"
DATE:
09.23.15
JOB NO.:
1016
SHEET:
FLOOR PLAN 1/8" = 1'-0"
A1
A311 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
25'-0"
8 32'-43 8"
25'-0"
ALIGN 9"
5'-03 4"
9'-6"
D1/A604 GAMING 132
MEN'S 126
A1 A601
130 MOP 130
CONC. BANNER TIEDOWN W/ S.S. EYE BOLT. TYP. SEE D1/A501
2'-10" DIMENSIONS OF CONC. FTG. SEE STRUCT. DWGS
20'-6"
A1 A504 28'-0"
3
25'-0"
4
25'-0"
5
6
7
157'-07 8"
8
AT C H LI M
PROJECT:
4'-0" 12'-10"
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
2'-0"
2'-8"
32'-43 8"
25'-0"
STOR 121
J FULL HT. CULTURED STONE ON 6" STUD FURRING
1
2
15'-0"
H
E
1" 6'-72
28'-1"
C9/A602 D9/A602
STRUCT. STL. CROSS BRACING. SEE STRUCT. DWGS
121
1.1
A
8.7
EIFS OVER CULTURED STONE WAINSCOT
D S BI HA P
3.7
1.8
7.3
6.6
5.6
4.6
8.1
2
22'-0"
1
22'-0"
22'-0"
22'-0"
22'-0"
C
10'-11"
5'-1"
8.3
22'-0"
GIFT SHOP 122
22'-27 8"
G
NEW CONC. SIDEWALK, TYP. AT NEW DOORS. SLOPE AWAY FROM BUILDING., SEE CIVIL
1 25'-216"
122
CONCOURSE
D7/A602
D SE BI HA P
B
C7/A602 23'-5"
5'-8"
C
2-HR FIRE RATED WALL
A5 A503
A1 A503
5'-8" 6'-2"
8"
E
41'-5"
4'-2"
LOW FURRING WALL BELOW COUNTERTOP
2 A3 11 D5/A401
B5/A401
D1 A501
DIMENSIONS OF CONC. FTG. SEE STRUCT. DWGS
WOMEN'S 124
FAMILY 131
N E
A4 A502
ANGLED GRIDLINE
A1 A502
A1 A501
B8/A401
ANGLED GRIDLINES
132D
1 21'-016"
4'-2"
CONC. BANNER TIEDOWN W/ S.S. EYE BOLT. TYP. SEE D1/A501
9'-2"
B5/A401
4'-2"
XX
YY
4'-2" 4'-2"
ZZ
EQ.
EQ. 5'-9"
F
132C
E.8
E.2
E.4
19'-7"
2'-0"
19'-9"
132B
132A
D.4
SLOPE
88 °
NEW CONC. SIDEWALK, TYP. AT NEW DOORS. SLOPE AWAY FROM BUILDING., SEE CIVIL
3'-0"
SLOPE
INSTALL GYP. BD. CONTROL JTS. AS REQUIRED BY MFR. TYP. ALL NEW WALLS, CEILINGS & SOFFITS
6'-2"
5'-6"
E
1" 11'-58
1" 5'-82
D
DISPLAY 123 2-HR FIRE RATED WALL
D5/A602 C5/A602
131
WOMEN'S 125
2'-2"
14'-0"
CONCRETE SLAB ON GRADE TYP., SEE WALKERDUCT PAN. SEE STRUCT. DWGS. FOR CONTROL JTS., REINF., THICKNESS, ETC. ALIGN TOP OF SLAB W./ EXISTING BUILDING
A3 1
FX CABINET
B7/A401
A2 A501
C
C
A9 A504
1" 1'-72
134
PAINTED STEEL ROOF ACCESS LADDER. MIN. 18" WIDE, 1 1/4" SERRATED RUNGS, 12" O.C., MAINTAIN MIN. 8" CLEARANCE FROM WALL/COLUMN.
ALIGN
2-HR SPRAY ON FIRE PROOFING AT STRUCTURAL STEEL COLUMNS, BEAMS, JOISTS & DECKING. SEE A101 FOR EXTENTS.
CONCOURSE
MEN'S 127
ALIGN
B1/A604
F5/A604
E1/A604
E5/A604 5'-10"
EXTEND EXISTING WALLS UP TO BOTTOM OF NEW ROOF DECK
A1/A604
B4/A604
ELEC 128
ELECT. ROOM EQUIPMENT TO REMAIN IN SERVICE DURING CONSTRUCTION. CONTRACTOR TO TAKE ALL NECESSARY MEANS TO PROTECT EQUIPMENT AND ENSURE SERVICE
STOR 134
B7/A604
EXIST ELEC 129
A1 A507
EXTEND EXISTING WALLS UP TO BOTTOM OF NEW ROOF DECK
1" 30'-92
HIGH LIMIT SLOTS 135
A2 A507
J&S STRUCTURAL ENGINEERS
128
ALIGN
FX CABINET
ALIGN
EXIST SERVER 133
STRUCTURAL ENGINEER:
C1/A602
SERVERS TO REMAIN IN SERVICE DURING CONSTRUCTION. CONTRACTOR TO TAKE ALL NECESSARY MEANS TO PROTECT EQUIPMENT AND ENSURE SERVICE
A1 A502
1'-10"
EXISTING GRIDLINE
A
cfse.com
1" 3'-74
65'-35 8"
1'-10"
10
MAYETTA, KANSAS
25'-0"
7
ENGINEERS
PRAIRIE BAND CASINO AND RESORT
15'-0"
6
CIVIL ENGINEER:
PRAIRIE BAND BINGO & SLOT EXPANSION
5
4
1" 6'-72
28'-1"
D
3
2
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
BID PHASE 1
MATCHLINE
1
BID PHASE 2
A311
ELECT. ROOM EQUIPMENT TO REMAIN IN SERVICE DURING CONSTRUCTION. CONTRACTOR TO TAKE ALL NECESSARY MEANS TO PROTECT EQUIPMENT AND ENSURE SERVICE
A312
SERVERS TO REMAIN IN SERVICE DURING CONSTRUCTION. CONTRACTOR TO TAKE ALL NECESSARY MEANS TO PROTECT EQUIPMENT AND ENSURE SERVICE
61'-87 8"
A1/A401
A1/A401
J.2 Copyright 2015 H2B architect, inc.
DIMENSION TO OUTSIDE FACE OF STUD FOR EXTERIOR WALL PLAN DIMENSIONS A1
6" 1'-4"
7'-0"
7'-0" 16'-8"
9.5
A801 NEW CONC. SIDEWALK, TYP. AT NEW DOORS. SLOPE AWAY FROM BUILDING., SEE CIVIL
1'-4"
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHELL PACKAGE 5'-0"
9
4'-0"
9.3
5'-0"
10
SHEET TITLE:
FLOOR PLAN PHASE TWO
11
1'-4"
A
218'-93 4" 368'-8" 371'-4"
DATE:
09.23.15
JOB NO.:
1016
SHEET:
FLOOR PLAN 1/8" = 1'-0"
A1
A312 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
BID PHASE 1
S
S
FS
S
FS
FS
S
EXIST. CEILING TO REMAIN
S
S
S
FS
S
S
EXIST. CEILING TO REMAIN
EXIST. CEILING TO REMAIN EXIST GYP CEILING EL. +10'-11 1/2"
LAY-IN CEILING EL. +10'-0" S
EXIST GYP CEILING EL. +11'-0"
S
LAY-IN CEILING EL. +11'-0"
S S S
OPEN CEILING TO STRUCT
EXIST. CEILING TO REMAIN
GYP CEILING EL. +14'-0"
LAY-IN CEILING EL. +10'-0"
S
S LAY-IN CEILING EL. +12'-0"
S
GYP CEILING EL. +8'-0" S HEADER EL. +8'-0"
S
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +10'-0"
GYP CEILING EL. +15'-0"
GYP CEILING EL. +10'-0"
GYP CEILING EL. +11'-0" LAY-IN CEILING EL. +12'-0"
LAY-IN CEILING EL. +12'-0"
GYP CEILING EL. +10'-0"
H LI
OPEN TO SKYLIGHT
C
D SE BI HA P 2
D SE BI HA P
INSTALL CONTROL JOINTS IN GYP. BD. CEILINGS & SOFFITS, ETC. AS REQUIRED
GYP CEILING EL. +20'-0"
GYP CEILING EL. +8'-6"
N A3 E 1 4 A3 13
GYP CEILING EL. +8'-6"
LAY-IN CEILING EL. +10'-0" GYP CEILING EL. +10'-0"
GYP CEILING EL. +20'-0"
1
GYP HEADER EL. +21'-7"
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +10'-0"
LAY-IN CEILING EL. +12'-0"
GYP CEILING EL. +20'-0"
LAY-IN CEILING EL. +10'-0"
LAY-IN CEILING EL. +15'-0"
GYP CEILING EL. +8'-0" GYP CEILING EL. +10'-0"
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
B
GYP CEILING EL. +10'-11 1/4" ±
LAY-IN CEILING EL. +10'-0"
GYP CEILING EL. +20'-0"
GYP CEILING EL. +8'-6"
S
OPEN CEILING TO STRUCT
GYP CEILING EL. +10'-0"
AT
LAY-IN CEILING EL. +12'-6"
S
LAY-IN CEILING EL. +10'-0"
LAY-IN CEILING EL. +10'-0"
M
GYP SOFFIT EL. +8'-0"
S
S
NEW GYP. BD. CEILING TO ALIGN W/ EXISTING. OPEN GYP CEILING CEILING EL. +8'-6" TO STRUCT GYP CEILING EL. +10'-0"
FS
PROJECT:
R20'-0"
LAY-IN CEILING EL. +13'-6"
S
LAY-IN CEILING EL. +11'-4"
LAY-IN CEILING EL. +10'-0"
WOOD WRAPPED MTL. STUDS
4'-1"
GYP CEILING EL. +9'-11 1/2"
S
C
MATCHLINE
S
MAYETTA, KANSAS
FS
PRAIRIE BAND CASINO AND RESORT
S
J&S STRUCTURAL ENGINEERS
PRAIRIE BAND BINGO & SLOT EXPANSION
D
REMOVE, SALVAGE & REINSTALL EXISTING CEILING AS REQUIRED FOR NEW MECH. INSTALLATION RESTRUCTURE STEEL SUPPORT FOR EXISTING LIGHT FIXTURE
A313
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
A314
BID PHASE 2
MATCHLINE
ELECTRICAL ENGINEER:
LAY-IN CEILING EL. +10'-0" GYP CEILING EL. +9'-11-3/8"
CURVED GYP. BD.
Copyright 2015 H2B architect, inc.
LAY-IN CEILING EL. +10'-0"
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
INSTALL CONTROL JOINTS IN GYP. BD. CEILINGS & SOFFITS, ETC. AS REQUIRED
WOOD WRAPPED MTL. STUDS
T&G WOOD SOFFIT WOOD WRAPPED STEEL BEAM
WOOD WRAPPED MTL. STUDS
WOOD BRACKETS
WOOD WRAPPED STEEL BEAM
ISSUED FOR:
SHELL PACKAGE
T&G WOOD SOFFIT SHEET TITLE:
PAINTED STEEL TRUSS
A
RCP PHASE ONE
HIGH CONCOURSE CEILING ABOVE VESTIBULE
DATE:
09.23.15
JOB NO.:
1016
SHEET:
REFLECTED CEILING PLAN 1/8" = 1'-0"
A1
A313 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
R54'-0"
GYP CEILING EL. +10'-6"
S S
S S
6'-0"
OPEN CEILING TO STRUCT GYP CEILING EL. +12'-2"
R28'-0" LAY-IN CEILING EL. +14'-6"
LAY-IN CEILING EL. +13'-6"
GYP SOFFIT EL. +8'-0" LAY-IN CEILING EL. +12'-6"
LAY-IN CEILING EL. +12'-6"
S
GYP CEILING EL. +8'-0" GYP CEILING EL. +10'-0"
GYP CEILING EL. +8'-6"
S
LAY-IN CEILING EL. +12'-0"
S
GYP CEILING EL. +10'-0"
S
S LAY-IN CEILING EL. +12'-0"
GYP CEILING EL. +10'-0"
GYP CEILING EL. +8'-6"
2
T&G WOOD SOFFIT WOOD WRAPPED STEEL BEAM EIFS HEADER
INSTALL CONTROL JOINTS IN GYP. BD. CEILINGS & SOFFITS, ETC. AS REQUIRED
GYP CEILING EL. +11'-0" LAY-IN CEILING EL. +12'-0"
GYP CEILING EL. +10'-0"
1
T&G WOOD SOFFIT
WOOD WRAPPED MTL. STUDS
GYP CEILING EL. +15'-0"
GYP CEILING EL. +8'-6"
D SE BI HA P
B
S
LAY-IN CEILING EL. +10'-0"
D SE BI HA P
EIFS HEADER
GYP CEILING EL. +20'-0"
GYP CEILING EL. +8'-0" S HEADER EL. +8'-0"
LI A N 3 E A3 14 13
LAY-IN CEILING EL. +14'-6"
GYP CEILING EL. +10'-11 1/4" ±
S
NEW GYP. BD. CEILING TO ALIGN W/ EXISTING. OPEN GYP CEILING CEILING EL. +8'-6" TO STRUCT GYP CEILING EL. +10'-0"
S
AT C H
LAY-IN CEILING EL. +13'-6"
LAY-IN CEILING EL. +12'-6"
S
FS
M
LAY-IN CEILING EL. +13'-6"
S
R20'-0"
R18'-0
GYP CEILING EL. +13'-10"
EXIST. CEILING TO REMAIN
LAY-IN CEILING EL. +11'-4"
PROJECT:
4'-1"
GYP CEILING EL. +9'-11 1/2"
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
WOOD WRAPPED STEEL BEAM
FS
EXIST GYP CEILING EL. +11'-0"
"
OPEN CEILING TO STRUCT
12'-0"
6'-0"
R40
'-0"
4'-0"
ALIGN WITH EXISTING GYP BOARD HEIGHT
LAY-IN CEILING EL. +14'-6"
WOOD WRAPPED MTL. STUDS
S
EXIST SOFFIT EL. +9'-5"
T
LAY-IN CEILING EL. +12'-6"
T&G WOOD SOFFIT
BID PHASE 1
MAYETTA, KANSAS
EXIST SOFFIT EL. +9'-5"
LAY-IN CEILING EL. +13'-6"
GYP CEILING EL. +12'-0"
J&S STRUCTURAL ENGINEERS
EXIST. CEILING TO REMAIN
MATCHLINE
EXIST SOFFIT EL. +9'-5"
LAY-IN CEILING EL. +15'-6"
C
STRUCTURAL ENGINEER:
EXIST. CEILING TO REMAIN
6'-0"
EXIST SOFFIT EL. +9'-5"
cfse.com
PRAIRIE BAND CASINO AND RESORT
EXIST. CEILING TO REMAIN
ENGINEERS
PRAIRIE BAND BINGO & SLOT EXPANSION
BIDDERS ARE TO PROVIDE SEPARATE BIDS FOR EACH BID PHASE
CIVIL ENGINEER:
A313
D
A314
BID PHASE 2
MATCHLINE
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
EIFS HEADER
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
LAY-IN CEILING EL. +10'-0" ISSUED FOR:
SHELL PACKAGE T&G WOOD SOFFIT
SHEET TITLE:
RCP PHASE TWO
WOOD WRAPPED STEEL TRUSS
HIGH TRUSS CEILING
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
RCP 1/8" = 1'-0"
A1
A314 PLAN NORTH
NORTH
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
ENLARGED ELEVATION 1/4" = 1'-0"
E1
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
J&S STRUCTURAL ENGINEERS
D
J
J.2
E
E
J.2
T.O. WALL 131'-0" T.O. STUD 130'-9"
3/4" EXPAN. JT. IN EIFS, CAULK & BACKER ROD T.O. WALL 127'-0" T.O. STUD 126'-9"
J
H
T.O. WALL 131'-0" T.O. STUD 130'-9"
T.O. WALL 127'-0" T.O. STUD 126'-9"
PEFINISHED SHT. MTL. COPING TYP. 1" R.O. 13'-12
WOOD TRIM
1"R.O. 11'-42
KAWNEER, SERIES 1600 CURTAIN WALL SYSTEM, OR EQ. W/ STRUCTURAL SILICONE GLAZED INTERMEDIATE HORZONTALS W/ ALUM. CAP VERTICALS. ANODIZED ALUM., W/ TINTED, INSULATED, GLAZING
ANODIZED SHT. MTL. TRIM TO MATCH DOOR/ WINDOW COLOR CULTURED STONE OVER AIR BARRIER MEMBRANE
ELEVATION
C
3/32" = 1'-0"
ZZ
ZZ
XX
ELEVATION 3/32" = 1'-0"
A5 A507
A5 A507
A1 A504
SIGNAGE B.O. SEE ELECT. DWGS
D3
ELEVATION
D5
3/32" = 1'-0"
H
ZZ
F.1
C.2
D2
B
SHT. MTL. COPING
17
YY 3/4" EXPAN. JT. IN EIFS, CAULK & BACKER ROD
H.8
T.O. WALL 124'-3" T.O. STUD 124'-0"
T.O. WALL 124'-3" T.O. STUD 124'-0"
T.O. WALL 124'-3" T.O. STUD 124'-0"
T.O. SOG 100'-0"
T.O. SOG 100'-0"
T.O. SOG 100'-0"
EXPAN. JT. COVER
PROJECT:
YY
3/4" EXPAN. JT. IN EIFS
EXISTING
4'-0" TYP.
YY
NEW
MAYETTA, KANSAS
G
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
C
DECORATIVE BANNER ANCHORED TO BUILDING
B
ELEVATION 3/32" = 1'-0"
1
ELEVATION
B8
3/32" = 1'-0"
4
6
EXISTING TO REMAIN, BEYOND
ELEVATION
B7
3/32" = 1'-0"
7
3/4" EXPAN. JT. IN EIFS AT & BEHIND DECORATIVE COL. TYP., CAULK & BACKER ROD
EAST ELEVATION
B5
3/32" = 1'-0"
8
ELEVATION
B2
3/32" = 1'-0"
B1
9 14
EXISTING TO REMAIN, BEYOND
9.5
15
3/4" EXPAN. JT. IN EIFS AT & BEHIND DECORATIVE COL. TYP., CAULK & BACKER ROD
16 EXISTING TO REMAIN, BEYOND
13.1
17
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
12 4
PEFINISHED SHT. MTL. COPING TYP.
17.2
PEFINISHED SHT. MTL. COPING TYP.
T.O. WALL 124'-3" T.O. STUD 124'-0"
8.3
8.7
EXISTING TO REMAIN, BEYOND
T.O. WALL 124'-3" T.O. STUD 124'-0"
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
3'-0"
EXTERIOR ELEVATIONS
A T.O. SOG 100'-0"
WOOD WRAPPED STEEL BEAM & COLUMNS
D1 A501
DECORATIVE BANNER ANCHORED TO BUILDING
EAST ELEVATION 3/32" = 1'-0"
A1
A1 A506
A4 A507
WOOD WRAPPED EXPOSED STEEL STEEL TRUSS TRUSS, PAINTED.
A1 A505
CULTURED STONE OVER AIR BARRIER MEMBRANE
SIGNAGE, PROVIDE SOLID TREATED WOOD BLOCKING & POWER
A8 A503
D1 A501
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE
A5 A503
DECORATIVE BANNER ANCHORED TO BUILDING
A4 A502
A1 A502
A1 A501
DECORATIVE BANNER ANCHORED TO BUILDING
A1 A503
T.O. SOG 100'-0"
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE NEW CULTURED STONE TO MATCH EXISTING, TYP.
CULTURED STONE OVER AIR BARRIER MEMBRANE
DATE:
09.23.15
JOB NO.:
1016
SHEET:
A401
9
8
7
6
5
4
3
2
1
F STAINLESS STEEL EYE BOLT ANCHOR FOR DECORATIVE BANNER
1'-0" 45°
8X8 WOOD BRACKET, STAIN 1'-2" 1" 12
1 3"± 14"
1'-2"
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
T.O. STONE 111'-3"±
6"
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
1"
1"
B1 A511
EXISTING
EXISTING
H.2 C
H.9 C
H.9 C
1
DECORATIVE BANNER, (8) THUS SEE ELEVATIONS FOR LOCATIONS
E
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
12
11'-0"
EXISTING
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
EXISTING STRUCTURE & ROOF TO REMAIN
A1 A511
12X12 CONC. W/ STAINLESS STEEL EYE BOLT (2) PER BANNER
2'-1"
4"
4"
1"
STAINLESS STEEL EYE BOLT ON SOLID BLK'G ON COLD FORMED FRAMING
2'-1"
ELECTRICAL ENGINEER:
T.O. FTG 100'-0"
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
2'-4"
4'-2"
CIVIL ENGINEER:
ENGINEERS
8'-8" cfse.com
D1
J&S STRUCTURAL ENGINEERS
EXISTING
C
H.9A C
EXISTING
NEW
ZZ
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK.
EXISTING WALL & STRUCTURE TO REMAIN EXPANSION JT. COVER
YY B1 A515
1'-4"
PREFINISHED SHT MTL COPING
T.O. WALL 124'-3"
CAST IRON ROOF DRAIN, SEE ROOF PLAN. SEE PLUMBING DWGS. TYP. SLOPE
T.O. STUD 124'-0" SLOPE
T.O. BM 122'-1-1/4"
EXISTING TO BE REMOVED
T.O. BM 121'-7"
EXISTING ROOFS TO BE REMOVED
EIFS DRAINAGE TERMINATION
C1 A511
SHT. MTL. COUNTER FLASHING EXISTING TO REMAIN
EXISTING TO BE REMOVED
12 SPRAY-ON FIRE PROOFING AT STRUCTURAL STEEL. SEE SHT. A101.
EXISTING WALL & STRUCTURE TO REMAIN
C
STANDING SEAM METAL ROOF ON ICE & WATER SHIELD ON SHEATHING
3-3/4
D3 A511
COLD METAL FRAMING
SEE RCP FOR CEILING INFORMATION REWORK EXISTING MECH. SEE MECH. DWGS.
T.O. BM 115'-9"
1'-45 8"
EXISTING TO BE REMOVED
8'-2"
1'-4" 6'-2"
2'-6" 3'-45 8"
24'-0"
EXISTING TO BE REMOVED 5/8" DENSGLASS GOLD SHEATHING
COLD METAL FRAMING EXTERIOR WALLS, SIZE BY CONTRACTOR.
DECORATIVE COLUMN SEE D1/A501 ABOVE
5/8" GYP. BD.
PROJECT:
6" FOIL FACED BATT INSULATION
MAYETTA, KANSAS
D
1/2" = 1'-0"
PRAIRIE BAND CASINO AND RESORT
1'-0"
STRUCTURAL ENGINEER:
PRAIRIE BAND BINGO & SLOT EXPANSION
DECORATIVE COL. SECTION
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE. SEE A515 TYP.
B
EIFS TERMINATION SEE DETAIL
A6 A515 4"
SIMULATED STONE SILL WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING MORTAR SETTING BED
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
CONC. SLAB W/ WALKER DUCT, ON VAPOR BARRIER ON 4" CRUSHED ROCK. SEE STRUCTURAL DWGS.
3'-8"
2.5 GAL. METAL LATH EXISTING SLAB TO REMAIN
SCRATCH COAT CULTURED STONE VARIES THICKNESS FROM 1"-3"
ISSUED FOR:
SHELL PACKAGE
SHT. MTL. FLASHING SHEET TITLE:
T.O. SOG 100'-0"
2'-0" MIN.
WALL SECTIONS
A 2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP. REINF. CONC. FTGS & FOUNDATIONS, SEE STRUCT. DWGS., TYP.
DEMOLITION HIGH LIMIT SECTION 1/2" = 1'-0"
A2d
DEMOLITION HIGH LIMIT SECTION 1/2" = 1'-0"
A1d
HIGH LIMIT SECTION 1/2" = 1'-0"
A2
DATE:
09.23.15
JOB NO.:
1016
SHEET:
HIGH LIMIT SECTION 1/2" = 1'-0"
A1
A501
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
H.1 C
ZZ
H C
XX
A
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
1'-10"
9'-2"
CIVIL ENGINEER:
EXISTING
NEW
ENGINEERS
STANDING SEAM METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING ON COLD METAL FRAMING
cfse.com STRUCTURAL ENGINEER:
J&S STRUCTURAL ENGINEERS 1" 94
D5 A511 T.O. BM VARIES
1'-3"
D CARRY MEMBRANE UP PARAPET, TYP.
EXISTING TO BE REMOVED
TONGUE & GROOVE WOOD SOFFIT.ON 2X TREATED WOOD FURRING. TYP.
10 x 6 STEEL TUBE, SEE STRUCT. WRAPPED W/ 2X WD TRIM ON WD BLK'G
C5 A511
SLOPE
SLOPE
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE. SEE A515 TYP.
EXISTING TO BE REMOVED
EXPANSION JT. COVER KNEE WALL
EXISTING TO REMAIN
B1 A515 PREFINISHED SHT MTL COPING
T.O. WALL 124'-3"
T.O. BM 122'-9"
SLOPE
SLOPE
STANDING SEAM METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING ON COLD METAL FRAMING
A5 A511
T.O. BM 121'-7" EIFS DRAINAGE TERMINATION SHT. MTL. COUNTER FLASHING STEEL BEAM, SEE STRUCT.
STEEL BEAM, SEE STRUCT.
STEEL BEAM W/ SPRAY-ON FIRE PROOFING, SEE STRUCT.
EXISTING WALL TO REMAIN
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK.
YY
T.O. STUD 124'-0"
T. O. STL. 123'-1"
1'-6"
TPO ROOFING ON MIN 4" RIGID ROOFING INSULATION ON METAL DECKING ON STEEL JOISTS
ZZ
A8 A515
C
SPRAY-ON FIRE PROOFING AT STRUCTURAL STEEL. SEE SHT. A101.
C1 A511
D3 A511
EXISTING WALL TO REMAIN T.O. BM 115'-9"
SUSPENDED GYP. BD. CEILING, SEE RCP.
GYP. BD. SOFFIT ALIGN W/ & TIE INTO EXISTING SOFFIT
15'-9"
B
PROJECT:
22'-9" 19'-10"
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE. SEE A515 TYP.
24'-0"
SEE A1/A501
21'-10"
3'-0"
3'-0" AT CENTER ARCH
TONGUE & GROOVE WOOD SOFFIT.ON 2X TREATED WOOD FURRING. TYP.
MAYETTA, KANSAS
H C
EXISTING
PRAIRIE BAND CASINO AND RESORT
EXISTING
PRAIRIE BAND BINGO & SLOT EXPANSION
EXISTING
A6 A515 Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
NEW CONC. FOOTINGS AT NEW STEEL COLUMNS. SEE STRUCT DWGS.
SHELL PACKAGE SHEET TITLE:
T.O. SOG 100'-0"
2'-0" MIN.
A
WALL SECTIONS
CONC. SIDEWALK AT DOORS, SLOPE AWAY FROM BUILDING. TYP. ASPHALT IMPREGNATED FIBERBOARD CAPPED WITH ELECTROMETRIC POLYURETHANE CAULK EXPANSION JOINT. TYP. WHERE PAVING ABUTS BUILDING.
DEMOLITION CASINO SECTION 1/2" = 1'-0"
A2d DEMOLITION CASINO SECTION A1d 1/2" = 1'-0"
TYP. CASINO SECTION 1/2" = 1'-0"
DATE:
09.23.15
JOB NO.:
1016
SHEET:
A4
TYP. CASINO SECTION 1/2" = 1'-0"
A2
TYP. CASINO SECTION 1/2" = 1'-0"
A1
A502
9
8
7
6
5
4
3
EXISTING
EXISTING
H.1 C
H.1 C
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
C
D.4 10"
2'-0"
C
PREFINISHED SHT MTL FLASHING 1X10 WOOD TRIM 1" 94
PREFINISHED SHT MTL FLASHING MEMBRANE FLASHING ON 5/8" DENS GLASS SHEATHING
TONGUE & GROOVE 12x6 STEEL TUBE, SEE STRUCT. WRAPPED W/ 2X WD TRIM ON WD BLK'G
PREFINISHED SHT MTL FLASHING 1X10 WOOD TRIM
TONGUE & GROOVE
SEALANT
SLOPED STEEL TUBE, SEE STRUCT.
TERMINATION BAR
6X6 STEEL TUBE COLUMN, SEE STRUCT. SLOPE
COUNTER FLASHING MEMBRANE FLASHING
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK. SLOPE
EXISTING WALL
T.O. BM 116'-3-1/2"
SEALANT 1'-7"
1" 12
TERMINATION BAR
SEALANT
COUNTER FLASHING MEMBRANE FLASHING
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK.
T.O. STUD 119'-7"
MEMBRANE FLASHING
SLOPE
SLOPE
T.O. BM 116'-3-1/2"
BEARING 116'-0"
3/4" TREATED PLY. WD.
BEARING 116'-0"
T.O. STONE 115'-3"±
3"±
6"
SEALANT
12x6 STEEL TUBE, SEE STRUCT. WRAPPED W/ 2X WD TRIM ON WD BLK'G
SLOPE
T.O. WALL 119'-10"
SEALANT, BOTH SIDES
T. O. STL. 118'-8"
2X WOOD COLUMN TRIM
SLOPE
B1 A515
PREFINISHED SHT MTL COPING
1"
SHT. MTL. COUNTER FLASHING
EXISTING WALL
1'-6"
T.O. BM VARIES
3"
MEMBRANE FLASHING ON 5/8" DENS GLASS SHEATHING
EIFS DRAINAGE TERMINATION
8" MIN.
C
1" 94
PREFINISHED SHT MTL FLASHING
STANDING SEAM PREFINISHED METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING ON COLD METAL FRAMING
8" MIN.
STANDING SEAM PREFINISHED METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING ON 6" COLD METAL FRAMING
T.O. BM VARIES
1" SIMULATED STONE SILL WEATHER BARRIER 4" GALV. COLD METAL FRAMING
5/8" DENSGLASS GOLD SHEATHING 6" FOIL FACED BATT INSULATION
TREATED WD BLK'G FOR SIGNAGE. PROVIDE POWER. 19'-7"
1
15'-0"
B
SEE A1/A503 FOR WALL NOTES
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE. SEE A515 TYP.
16'-0"
EXISTING DECORATIVE COLUMN WRAP W/ CULTURED STONE ON METAL STUDS TO BE REMOVED. EXISTING STRUCTURAL STEEL COLUMN INSIDE WRAP TO REMAIN.
1" 16'-32
12
EXISTING WALL TO REMAIN. REMOVE EXISTING SURFACE APPLIED CULTURED STONE
A6 A515
A6 A515
COLD METAL FRAMING EXTERIOR WALLS, SIZE BY CONTRACTOR.
PROJECT:
CULTURED STONE
MAYETTA, KANSAS
D.4
STANDING SEAM PREFINISHED METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING ON 6" COLD METAL FRAMING
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
EIFS TERMINATION SEE DETAIL SIMULATED STONE SILL WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING
EXISTING WALL TO REMAIN. REMOVE EXISTING SURFACE APPLIED CULTURED STONE
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
MORTAR SETTING BED 2.5 GAL. METAL LATH SCRATCH COAT CULTURED STONE VARIES THICKNESS FROM 1"-3"
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
1"
2'-10"
T.O. FTG 100'-0"
T.O. SOG 100'-0"
2'-0" MIN.
T.O. SOG 100'-0"
2'-0" MIN.
WALL SECTIONS
FLASHING
A
CONC. FTG.
2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP.
SECTION AT PILASTER 1/2" = 1'-0"
A8
2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP.
SECTION AT NEW RESTROOMS 1/2" = 1'-0"
A5
DATE:
09.23.15
JOB NO.:
1016
SHEET:
SECTION AT NEW RESTROOMS 1/2" = 1'-0"
A1
A503
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
EXISTING 14 C
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
10
CIVIL ENGINEER:
11
11
12
ENGINEERS cfse.com
EXISTING WALL
EXPANSION JT. COVER
T.O. WALL 127'-0" T.O. STUD 126'-10-1/2" TAPERED ROOFING INSULATION SEE ROOF PLAN
T.O. WALL 127'-0" TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK. SLOPE
T.O. STUD 126'-10-1/2"
T.O. STUD 126'-10-1/2"
KAWNEER, SERIES 1600 SLOPED GLAZING, 2-1/2"X"6 OR EQ. ANODIZED ALUM., W/ TINTED, INSULATED, LAMINATED GLAZING
SLOPE
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK.
T.O. STL. 124'-0-1/2"
T.O. WALL 127'-0"
SEALANT, BOTH SIDES
T.O. STUD 126'-9"
MEMBRANE FLASHING SLOPE
T.O. STL. 124'-0-1/2"
T.O. STL. 123'-11-1/4"
PREFINISHED SHT MTL COPING
T.O. WALL 127'-0"
1" 15'-62
B1 A515
EIFS SYSTEM SLOPE
T.O. STL. 124'-0-1/2"
T.O. BM 123'-9" EIFS DRAINAGE TERMINATION SHT. MTL. COUNTER FLASHING 8"
MEMBRANE FLASHING
8"
8"
8"
T.O. STL. VARIES W/ ROOF SLOPE (120'-8" - 122'-0")
1" 16'-102
C
SEE RCP FOR CEILING MATERIAL & HT.
SEE RCP FOR CEILING MATERIAL & HT.
PROJECT:
5/8" DENSGLASS GOLD SHEATHING 6" FOIL FACED BATT INSULATION
MAYETTA, KANSAS
D
B1 A515
J&S STRUCTURAL ENGINEERS
PRAIRIE BAND CASINO AND RESORT
MEMBRANE FLASHING TURNED UP WALLS
14
PRAIRIE BAND BINGO & SLOT EXPANSION
9
15°
STRUCTURAL ENGINEER:
COLD METAL FRAMING EXTERIOR WALLS, SIZE BY CONTRACTOR.
B
5/8" GYP. BD. 2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE. SEE A515 TYP.
A6 A515
EIFS TERMINATION SEE DETAIL SIMULATED STONE SILL
Copyright 2015 H2B architect, inc.
WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
2.5 GAL. METAL LATH
4'-0"
MORTAR SETTING BED CONC. SLAB W/ WALKER DUCT AT BINGO HALL. ON VAPOR BARRIER ON 4" CRUSHED ROCK. SEE STRUCTURAL DWGS.
SCRATCH COAT CULTURED STONE VARIES THICKNESS FROM 1"-3"
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
T.O. SOG 100'-0"
T.O. SOG 100'-0"
WALL SECTIONS
A DATE:
09.23.15
JOB NO.:
1016
SHEET:
WALL SECTION 1/2" = 1'-0"
A9
SECTION AT NEW CONCOURSE 1/2" = 1'-0"
A1
A504
9
8
7
6
5
4
3
2
1
1" 42'-42
9.5
13.1 1" 15'-54
1" 15'-54
F
6'-115 8"
8"
6'-115 8"
8"
6" 6" T.O. TRUSS @ APEX 125'-1"
1'-4"
5'-9"
R70'-0"
4'-4"
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
WELDED STEEL CAP
8"
7'-0"
16X8 STEEL TUBE
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
8"
8X8 STEEL TUBE
45°
1'-4"
8"
WELDED STEEL END CAP 8X8 STEEL TUBE
R63'-0"
16X8 STEEL TUBE
E
PAINT ALL EXPOSED STEEL
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
12X12 STEEL TUBE COLUMN
MECHANICAL & PLUMBING ENGINEER:
CL
FACILITY ENGINEERING AND CONSULTING, LLC
A1 A505
TOPEKA, KS
PHONE: (785) 217-7670
TRUSS ELEVATION 1/2" = 1'-0"
B.4
D1 J
H C
A4 A507
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
J.2
CIVIL ENGINEER:
5'-0"
3'-0"
4'-0" ENGINEERS cfse.com
EXISTING
STRUCTURAL ENGINEER:
10 E
11 E
3'-6"
T.O. WALL 127'-0"
T.O. STUD 126'-9"
T.O. STUD 126'-10-1/2"
EIFS SYSTEM
10'-0"
TAPERED ROOFING INSULATION SEE ROOF PLAN
SEALANT
T.O. STL. 123'-9" T.O. STL. 123'-9"
T.O. STL. 123'-9"
T.O. STL. 124'-2-1/2"
T.O. STL. 123'-9"
1X10 WOOD TRIM 4'-0"
ANODIZED ALUM. SHT. MTL. ON WEATHER PROOFING MEMBRANE ON 5/8" DENS GLASS SHEATHING.
8"
EXPANSION JT. COVER
T.O. TRUSS @ APEX 125'-1" 1X6 WOOD TRIM
BOT.O. STL. 123'-4-1/2"
EIFS DRAINAGE TERMINATION SHT. MTL. COUNTER FLASHING
OVER-BUILD, METAL ROOFING SLOPE 1/4"/ FT.
T.O. TUBE 126'-10-1/2"
TONGUE & GROOVE
CURVED STEEL TRUSS
11'-4" R.O.
SEE RCP FOR CEILING MATERIAL & HT.
1" 12
KAWNEER, SERIES 1600 CURTAIN WALL SYSTEM, 2-1/2"X"6 OR EQ. W/ STRUCTURAL SILICONE GLAZED INTERMEDIATE HORIZONTALS W/ ALUM. CAP VERTICALS. ANODIZED ALUM., W/ TINTED, INSULATED, GLAZING
6"
3"±
C
1'-4"
8"
ANODIZED ALUM. SHT. MTL. ON WEATHER PROOFING MEMBRANE ON 5/8" DENS GLASS SHEATHING.
SIGN B.O.
10"
1" 12 1" 12
10"
T.O. STL. 110'-11-1/2"
PROJECT:
EXISTING WALL
23'-3"
EXISTING WALL TO REMAIN
BOT.O. STL. 110'-1-1/2"
MAYETTA, KANSAS
9 E
T.O. WALL 127'-0"
D1 A505
EXISTING
1" 1'-14
EXISTING
1'-4"
EXISTING
T.O. WALL 127'-0"
STANDING SEAM PREFINISHED METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING ON 10" DP COLD METAL FRAMING PREFINISHED SHT MTL FLASHING
4'-4"
D
PRAIRIE BAND CASINO AND RESORT
KAWNEER, SERIES 1600 SLOPED GLAZING, 2-1/2"X"6 OR EQ. ANODIZED ALUM., W/ TINTED, INSULATED, LAMINATED GLAZING
B3 A515
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
9 E
B
1" 10'-112
12'-0"
15'-0"
5/8" GYP. BD. ON COLD METAL JOISTS
3'-0"
3/4" TREATED PLY. WD. DECK
Copyright 2015 H2B architect, inc.
7'-0"
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
KAWNEER 451T, ANODIZED ALUM. STOREFRONT SYSTEM, W/ TINTED, INSULATED, SAFETY GLAZING
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
WALL SECTIONS 2'-10" T.O. SOG 100'-0"
2'-0" MIN.
A 2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP.
DEMOLITION SECTION 1/2" = 1'-0"
A1d
DATE:
09.23.15
JOB NO.:
1016
SHEET:
SECTION AT NEW CONCOURSE 1/2" = 1'-0"
A1
A505
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
B
SHT MTL EDGE FLASHING 3'-6"
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
TAPERED ROOFING INSULATION SEE ROOF PLAN
TAPERED ROOFING INSULATION SEE ROOF PLAN
1'-0" 1'-0"
STEEL ROOF LADDER
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
7" 1'-0"
1 1/4" SQ. STEEL SERRATED RUNGS W/ SLIP PROOF COATING
MECHANICAL & PLUMBING ENGINEER:
1'-2"
STEEL SIDE RAILS, SEE STRUCT. DWGS.
STEEL ANGLES TIED BACK TO STEEL, SEE STRUCT.
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
D B B3 A515
8 E
B1 A515
PREFINISHED SHT MTL COPING
T.O. WALL 124'-3"
PREFINISHED SHT MTL COPING
T.O. STUD 124'-0"
SEALANT, BOTH SIDES
T.O. WALL 124'-3"
SEALANT, BOTH SIDES TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON METAL ROOF DECK.
9 E
MEMBRANE FLASHING
T.O. STUD 124'-0" 2'-5"
EXISTING FALSE WALL TO REMAIN
H.8
H
EIFS SYSTEM
T.O. BM 121'-7"
EIFS DRAINAGE TERMINATION
NEW TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON EXISTING ROOF DECK.
C1 A511
T.O. BM 120'-3" SHT. MTL. COUNTER FLASHING
STEEL BEAM, SEE STRUCT.
EXPANSION JT. COVER
C
EXPANSION JT. COVER
NEW KNEE WALL.5/8" SHEATHING ON 6" MTL. STUDS W/ 6" INSULATION
EXISTING ROOF DECKING TO REMAIN EXISTING STEEL BEAM TO REMAIN
T.O. BM 115'-9"
PORTION OF EXISTING BUILDING TO BE REMOVED
NEW STEEL COLUMN, SEE STRUCT. STRUCT. BRACKET W/ SLOTTED CONNECTION TO EXISTING BEAM. SEE STRUCT. DWGS.
SEE A1/A501
SEE RCP FOR CEILING MATERIAL & HT.
B
PROJECT:
20'-3"
21'-7"
24'-0"
EXISTING ROOF DECK & STRUCTURE TO REMAIN
D3 A511
5/8" GYP. BD. ON INSULATED, 8" COLD METAL FRAMING W/ 5/8" DENSGLASS SHEATHING
MAYETTA, KANSAS
D5
PRAIRIE BAND CASINO AND RESORT
1/2" = 1'-0"
PRAIRIE BAND BINGO & SLOT EXPANSION
SECTION
J&S STRUCTURAL ENGINEERS
2" DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE CANVAS ART APPLIED TO WALL
A6 A515 Copyright 2015 H2B architect, inc.
4'-0"
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
ISSUED FOR:
SHELL PACKAGE 4" CONC. SLAB ON 4" CRUSHED ROCK
SHEET TITLE:
T.O. SOG 100'-0"
WALL SECTIONS
A 2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP.
DATE:
09.23.15
JOB NO.:
1016
SHEET:
SECTION AT NEW BINGO HALL 1/2" = 1'-0"
A1
A506
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
J 1'-4"
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
B6 A515
T.O. WALL 130'-0" SEALANT, BOTH SIDES
CIVIL ENGINEER:
T.O. WALL 130'-0" SEALANT, BOTH SIDES
T.O. STUD 130'-9"
MEMBRANE FLASHING
8
2
T.O. STUD 130'-9"
ENGINEERS cfse.com
MEMBRANE FLASHING
STRUCTURAL ENGINEER:
J&S STRUCTURAL ENGINEERS
EXISTING TO REMAIN
A8 A515
D
A8 A515
EXPANSION JT. COVER SEALANT
STEEL BEAM, SEE STRUCT.
SHT. MTL. FLASHING COUNTER FLASHING MEMBRANE FLASHING
T.O. BM VARIES
T.O. BM 123'-9"
1" 1'-14
T.O. BM VARIES
D3 A511
EXISTING TO REMAIN
TPO, 60 MIL MIN. FULLY ADHERED MEMBRANE ROOFING ON 1/2" COVER BD. ON 4" (MIN. R-24) RIGID ROOFING INSULATION ON 5/8" RECOVERY BD. ON METAL ROOF DECK.
EXPANSION JT. COVER
T.O. BM VARIES
SPRAY-ON FIRE PROOFING AT STRUCTURAL STEEL. SEE SHT. A101.
SEE A1/A505
SIMILAR 1'-45 8" 1'-4" 4'-0"
4'-0" CURVED STEEL TRUSS
EXISTING TO BE REMOVED
8"
C 30'-9"
FLASHING/ WEATHER BARRIER
3"±
1" 12 6"
30'-9"
1'-10"
1"
5/8" DENSGLASS GOLD SHEATHING
5/8" DENSGLASS GOLD SHEATHING
6" FOIL FACED BATT INSULATION
6" FOIL FACED BATT INSULATION
COLD METAL FRAMING EXTERIOR WALLS, SIZE BY CONTRACTOR.
COLD METAL FRAMING EXTERIOR WALLS, SIZE BY CONTRACTOR.
EXISTING WALL TO REMAIN AT ELECT. 129
12
5/8" GYP. BD.
6" METAL STUD ATTACHED TO STRUCT. STUD
15'-0"
B
EXISTING TO BE REMOVED
1
15'-0"
5/8" GYP. BD.
REMOVE EXISTING EXTERIOR METAL PANELS
PROJECT:
1'-105 8"
1'-7"
SHT. MTL FLASHING
MAYETTA, KANSAS
PREFINISHED SHT MTL COPING
PRAIRIE BAND CASINO AND RESORT
PREFINISHED SHT MTL COPING
B8 A515
6"
1'-4"
J.2
PRAIRIE BAND BINGO & SLOT EXPANSION
14
6" GALV. COLD METAL FRAMING WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING
CULTURED STONE VARIES THICKNESS FROM 1"-3"
MORTAR SETTING BED
SCRATCH COAT
2.5 GAL. METAL LATH
2.5 GAL. METAL LATH
SCRATCH COAT CULTURED STONE VARIES THICKNESS FROM 1"-3"
CONC. SLAB
T.O. SOG 100'-0"
2'-0" MIN.
2'-0" MIN.
2'-10"
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
MORTAR SETTING BED
ISSUED FOR:
WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING
SHELL PACKAGE SHEET TITLE:
WALL SECTIONS
T.O. SOG 100'-0"
1"
SHT. MTL. FLASHING
Copyright 2015 H2B architect, inc.
SHT. MTL. FLASHING
A
CONC. FTG. SEE STRUCT. 2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP.
2" RIGID POLY-ISO., 24" DP & 24" HORZ. CONT. AT EDGE OF BUILDING. TYP.
REINF. CONC. FTGS & FOUNDATIONS, SEE STRUCT. DWGS., TYP.
REINF. CONC. FTGS & FOUNDATIONS, SEE STRUCT. DWGS., TYP.
SECTION 1/2" = 1'-0"
A5
DATE:
09.23.15
JOB NO.:
1016
SHEET:
SECTION 1/2" = 1'-0"
A4
SECTIONS AT GAMING 1/2" = 1'-0"
A2
SECTIONS AT GAMING 1/2" = 1'-0"
A1
A507
9
8
7
6
5
4
3
2
1
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
F
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
E
MECHANICAL & PLUMBING ENGINEER:
FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS
PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
STANDING SEAM METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING
EIFS WALL SYSTEM DRAINAGE STRIP
1"
6" COLD METAL FRAMING 1X10 WOOD TRIM, STAIN
DETAIL MESH WRAP BOTTOM & BACK TO MIN. 2"
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
SHEET METAL COUNTER FLASHING
PREFINISHED SHT MTL FLASHING
ICE & WATER SHIELD TURN UP WALL
CIVIL ENGINEER:
SHEET MTL. FLASHING STANDING SEAM ROOFING
ENGINEERS cfse.com
SEALANT 1" 94
STRUCTURAL ENGINEER:
2'-0" 12 x 6 STEEL TUBE, SEE STRUCT.
DETAIL 1 1/2" = 1'-0"
1x6" TONGUE & GROOVE, STAIN
3-3/4
D3
COLD METAL FRAMING 1X10 WOOD TRIM, STAIN PREFINISHED SHT MTL FLASHING
2X WOOD TRIM, MITER CORNERS, STAIN
1 1/2" = 1'-0"
D5
SEALANT 1" 94
EAVE DETAIL
BOT. O. FRAMING T.O. STL.
1"
115'-9"
1'-03 4"
1'-3"
12 x 6 STEEL TUBE, SEE STRUCT.
2X TREADED WD NAILER / BLK'G
12 x 6 STEEL TUBE, SEE STRUCT. 2X WOOD TRIM, MITER CORNERS, STAIN
2'-6"
1'-0"
C2 A511
2X TREADED WD NAILER / BLK'G
FAUX BEAM DETAIL
1'-0"
1 1/2" = 1'-0"
BEAM DETAIL 1 1/2" = 1'-0"
2X NAILER
1x6" TONGUE & GROOVE, STAIN
2X WOOD TRIM, MITER CORNERS, STAIN
2X WOOD TRIM, STAIN
1'-0"
1'-6"
2X TREADED WD NAILER / BLK'G
COLD FORMED FRAMING
1" 1'-12
1'-3"
T.O. STL. 123'-1"
C
CONT. SOFFIT VENT W/ INSECT SCREEN
2X TREADED WD NAILER / BLK'G
1'-0"
C3
EAVE DETAIL
C5
1 1/2" = 1'-0"
C1
2X WOOD TRIM, MITER CORNERS STANDING SEAM METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING
2X TREADED WD NAILER / BLK'G 1'-2"
BACKER ROD & EXTERIOR ELECTROMETRIC SEALANT
1'-2" 1'-0"
COLD METAL FRAMING
WEATHER BARRIER TURNED UP COL. 8" & SEAL
T.O.FRAMING 111'-0"
1" 12 6"
T.O. WALL 119'-10"
3/4" TREATED PLY. WD. 1"
B
SEALANT
PROJECT:
1" 12
PREFINISHED SHT MTL FLASHING
MAYETTA, KANSAS
1'-3"
12 CONT. SOFFIT VENT W/ INSECT SCREEN
PRAIRIE BAND CASINO AND RESORT
2X TREADED WD NAILER / BLK'G
D
STANDING SEAM METAL ROOF ON ICE & WATER SHIELD ON FIRE RATED, NAILABLE SHEATHING
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
T.O. STL. VARIES
SIMULATED STONE SILL
WEATHER BARRIER
4" GALV. COLD METAL FRAMING
5/8" DENSGLASS GOLD SHEATHING
11'-0"
CULTURED STONE VARIES THICKNESS FROM 1"-3"
DECORATIVE COL. DETAIL 1 1/2" = 1'-0"
2" THK. DRAINAGE EIFS SYSTEM OVER AIR BARRIER MEMBRANE
B1
CULTURED STONE VARIES THICKNESS FROM 1"-3" SCRATCH COAT
Copyright 2015 H2B architect, inc. Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
2.5 GAL. METAL LATH CONT. SOFFIT VENT W/ INSECT SCREEN
MORTAR SETTING BED ISSUED FOR:
WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING
STEEL COL. SEE STRUCT.
1"
1x6" TONGUE & GROOVE, STAIN
A
2'-1"
2'-1"
6" GALV. COLD METAL FRAMING TOP OF FTG. ALIGNS W/ TOP OF SLAB T.O.FTG. 100'-0"
SHELL PACKAGE SHEET TITLE:
EXTERIOR WALL DETAILS
SHT. MTL. FLASHING CONC. FTG. SEE STRUCT.
4'-2"
3'-0"
DETAIL 1 1/2" = 1'-0"
A5
DATE:
09.23.15
JOB NO.:
1016
SHEET:
DECORATIVE COL. DETAIL 1 1/2" = 1'-0"
A1
A511
9
8
7
6
5
4
3
2
1
ROOF HATCH ROOF HATCH CURB
FASTEN 12" O.C.
THERMOPLASTIC MEMBRANE FLASHING
METAL CAP OR COUNTERFLASHING BONDING ADHESIVE
2x TREATED BLOCKING THERMOPLASTIC MEMBRANE ROOFING
REINFORCED TPO MEMBRANE SEAM FASTENING PLATE, 12" O. C. MAX.
F
7"
H2B architects, inc. 1800 Baltimore Ave #1 South Kansas City, MO 64108 816.979.1800 www.h2barch.com
AUTOMATIC HOLD-OPEN AND OPERATING ARMS, EACH SIDE
WALK PAD
MINIMUM 1-1/2" HOT AIR WELD
3'-0" CLEAR 1'-0"
CUT-EDGE SEALANT REINFORCED TPO MEMBRANE
METAL ROOF DECK
STEEL PERIMETER ANGLE
ARCHITECTURAL CORPORATION KANSAS LICENSE # 685
RIGID ROOFING INSULATION EXIST. BEAM AT HATCH IN STORAGE 112
USE ONE CONTINUOUS SHEET OF REINFORCED MEMBRANE TO WRAP AROUND CURB
NOTES: 1.
BONDING ADHESIVE IS NOT REQUIRED WHEN FLASHING HEIGHT IS 12" OR LESS AND MEMBRANE IS FASTENED "AS SHOWN" AT TOP OF CURB.
2.
FLASHING MEMBRANE FASTENED APPROXIMATELY 12" ON CENTER. IF FASTENER PENETRATES METAL COUNTERFLASHING, USE NEOPRENE WASHER OR APPLY WATER CUT-OFF MASTIC UNDER COUNTERFLASHING OR CAULK FASTENER HEAD.
3.
E
7" MIN.
EXTENSION OF EXIST. WALL AT HATCH AT ELEC 128
RIGID INSULATION
STEEL ROOF ACCESS LADDER
LOCATE ROOF HATCH & LADDER SO THAT CENTER OF RUNGS IS NO LESS THAN 7" FROM FACE OF WALL OR FLANGE EDGE OF BEAM, AS CONDITIONS DICTATE
1 1/4" SQ. STEEL SERRATED RUNGS WITH SLIP PROOF COATING
FACE OF WALL OR COLUMN. RE: FLOOR PLAN
STEEL SIDE RAILS, SEE STRUCT. DWGS.
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
APPROXIMATELY 1/8" BEAD OF CUT-EDGE SEALANT IS REQUIRED ON CUT EDGES OF MEMBRANE.
TYP. ROOF CURB DETAIL 1'-0" = 1'-0"
ACCESS LADDER SECTION
E4
1 1/2" = 1'-0"
MECHANICAL & PLUMBING ENGINEER:
E1 FACILITY ENGINEERING AND CONSULTING, LLC TOPEKA, KS PHONE: (785) 217-7670
ELECTRICAL ENGINEER:
3545 SOUTHWEST 6TH AVE. - TOPEKA KS 66606 PHONE 785.233.2213 - FAX 785.233.7066 WWW.TORGESONELECTRIC.COM
CIVIL ENGINEER:
ENGINEERS cfse.com STRUCTURAL ENGINEER:
6" 24 GA SHEET METAL CLEAT
C
24 GA SHEET METAL CLEAT 5"
6" METAL STUD ATTACHED TO STRUCT. STUD
24 GA SHEET METAL CLEAT
CONT. SEALANT
MEMBRANE FLASHING ON BACKSIDE OF PARAPET
COLD FORMED METAL STUD FRAMING, SIZE VARIES
CONT. SEALANT
CONT. SEALANT
CULTURED STONE VARIES THICKNESS FROM 1"-3"
BACKWRAPPED FOAM
SCRATCH COAT
ADHESIVE IN VERTICAL NOTCHED TROWEL CONFIGURATION
2.5 GAL. METAL LATH
1'-2"
CONT. SEALANT
COLD FORMED METAL STUD FRAMING, SIZE VARIES
MEMBRANE FLASHING ON BACKSIDE OF PARAPET
WATER RESISTIVE BARRIER COATING
MORTAR SETTING BED
5/8" DENS GLASS GOLD SHEATHING
CONT. SEALANT
WEATHER BARRIER ON 5/8" DENS GLASS GOLD SHEATHING
5/8" DENS GLASS GOLD SHEATHING
COLD FORMED METAL STUD FRAMING, SIZE VARIES
BACKWRAPPED FOAM 3"
COLD FORMED METAL STUD FRAMING, SIZE VARIES
CONT. SEALANT
2"
ADHESIVE IN VERTICAL NOTCHED TROWEL CONFIGURATION WATER RESISTIVE BARRIER COATING
1" 1"
5/8" DENS GLASS GOLD SHEATHING
5/8" DENS GLASS GOLD SHEATHING
SAME AS B6 EXCEPT AS NOTED
PARAPET DETAIL N.T.S.
B8
PARAPET DETAIL N.T.S.
B6
PARAPET DETAIL
WATER-RESISTIVE BARRIER COATING
N.T.S.
PARAPET DETAIL
B3
N.T.S.
B1
ADHESIVE IN VERTICAL NOTCHED TROWEL CONFIGURATION APPLIED TO BACK OF INSULATION BOARD
EXISTING WALL SEALANT
DENS GLASS GOLD SHEATHING PROJECT:
TERMINATION BAR COUNTER FLASHING
MAYETTA, KANSAS
TREATED WOOD BLOCKING SLOPE TOP
6"
CONT. SEALANT
24 GA PREFINISHED SHEET METAL COPING
3"
CONT. SEALANT 6"
24 GA PREFINISHED SHEET METAL COPING
SLOPE
1 2"
1 2"
24 GA PREFINISHED SHEET METAL COPING
6"
6"
1 2"
TREATED WOOD BLOCKING SLOPE TOP
6"
EXTEND MEMBRANE ROOFING OVER TOP OF PARAPET
SLOPE
SLOPE
6"
EXTEND MEMBRANE ROOFING OVER TOP OF PARAPET
SLOPE
PRAIRIE BAND CASINO AND RESORT
D
PRAIRIE BAND BINGO & SLOT EXPANSION
J&S STRUCTURAL ENGINEERS
B EXPANSION JT. COVER CARRY MEMBRANE OVER KNEE WALL 5/8" GYP. BD.
5/8" DENS GLASS SHEATHING
COLD FORMED FRAMING
WATER BARRIER
TREATED WOOD BLK'G
5/8" DENS GLASS SHEATHING ON 6" COLD FORMED FRAMING KNEE WALL 8" MIN.
2"
EIFS WALL SYSTEM
6" FOIL FACED BATT INSULATION
FINISH COAT
2'-0" MAX.
BASE COAT
MEMBRANE FLASHING
EPS INSULATION
ADHESIVE IN VERTICAL NOTCHED TROWEL CONFIGURATION
EPS INSULATION BD. TYP. 2" THK.
BASE, SEE FINISH SCHEDULE CONC. SLAB ON GRADE 1"
REINFORCING MESH EMBEDDED IN BASE COAT
A
GALV. STUDS
DRAINAGE STRIP
WATER-RESISTIVE BARRIER COATING
DETAIL MESH WRAP BOTTOM & BACK TO MIN. 2"
EPS INSULATION BOARD BASE COAT REINFORCING MESH
DETAIL MESH WRAPPED TO BACKSIDE OF EPS MIN. 2"
BASE COAT
BACKSTOP NT-TEXTURE OVER GRID TAPE™
FINISH
3" = 1'-0"
A8
3" = 1'-0"
A6
ISSUED FOR:
SHELL PACKAGE SHEET TITLE:
EXTERIOR WALL DETAILS
DRAINAGE STRIP
NORMAL IMPACT FINISH
SLOPE GRADE AWAY FROM FOUNDATION WALL
STONE SILL DETAIL
Original Size: 1 12 " - Drawing may have been reduced. 0" 1"
5/8" DENS GLASS GOLD SHEATHING
AQUAFLASH® SYSTEM
DRAINAGE STRIP ADHERED WITH DABS OF AP ADHESIVE. ENSURE BOTTOM EDGE IS FREE TO DRAIN.
EXPANSION JOINT DETAIL
Copyright 2015 H2B architect, inc.
DATE:
09.23.15
JOB NO.:
1016
SHEET:
BOTTOM OF. E.I.F.S. WALL DETAIL N.T.S.
A4
E.I.F.S. WALL SYSTEM N.T.S.
A1
A515