Lighting Design -Office

Page 1

辦公室照明規劃案

Date: 05.01.2006 Operator: lee jiunshian


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

Table of contents 辦公室照明規劃案 Project Cover Table of contents Fagerhult 76300 Pleiad Power 125 MR 1 x HIPAR 30 35 W Luminaire Data Sheet Fagerhult 62715 Icon 1 x TC-DEL 18 W Luminaire Data Sheet Fagerhult 3965 Pegasus 1 x TC-T 26 W Luminaire Data Sheet Fagerhult 26303-10 Ten°Wall Line 2 x TC-L 55 W Luminaire Data Sheet ERCO 88100023 Gimbal Directional spotlight for low-voltage halogen ... Luminaire Data Sheet ERCO 33200000 Parscoop I Wallwasher with mounting plate for tungste... Luminaire Data Sheet ERCO 33499000 Trion Ceiling washlight for tungsten halogen lamps Luminaire Data Sheet HOFFMEISTER 0.13950.44 Downlight 200 superflach, 1 TC-DEL 26W, EVG Luminaire Data Sheet 辦公室 Summary Luminaire parts list 3D Rendering Room Surfaces Working Plane Isolines (E) Greyscale (E) Value Chart (E) UGR 眩光計算面(主管) Isolines (UGR) Greyscale (UGR) Value Chart (UGR) Floor Isolines (E) Greyscale (E) Value Chart (E)

www.ceve.com.tw

1 2 3 4 5 6 7 8 9 10 11 13 15 16 17 18 19 20 21 22 23 24

Page 2


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

Fagerhult 76300 Pleiad Power 125 MR 1 x HIPAR 30 35 W / Luminaire Data Sheet Luminous emittance 1: 105

105

90

90

75

75

800

60

60

1200 45

45

1600 2000 2400

η = 96 %

cd/klm

30

15

0

C0-C180

Luminaire classification according to CIE: 100 CIE flux code: 97 99 99 100 97

30

15

C90-C270

Luminous emittance 1: Glare Evaluation According to UGR

Installation For recessed mounting in unventilated and ventilated ceilings. Fastening springs for quick installation are supplied. Connection Luminaire is fitted with 0,5 m connection cable 3x1,5mm ² and a "Weiland" snap-in terminal block for connection to ballast box. Design Assembly arms of natural aluzinc. White assembly ring of PC/ABS plastic, colour RAL 9010.

ρ Ceiling

70

70

50

50

30

70

70

50

50

30

ρ Walls

50

30

50

30

30

50

30

50

30

30

ρ Floor

20

20

20

20

20

20

20

20

20

20

Room Size Viewing direction at right angles X Y to lamp axis 2H

2H 3H 4H 6H 8H 12H

13.9 13.7 13.7 13.6 13.6 13.5

14.5 14.3 14.2 14.1 14.1 14.0

14.1 14.0 14.0 13.9 13.9 13.9

14.7 14.6 14.5 14.4 14.4 14.3

14.9 14.8 14.7 14.7 14.7 14.6

14.0 13.8 13.8 13.7 13.7 13.7

14.6 14.4 14.4 14.3 14.2 14.2

14.2 14.1 14.1 14.1 14.1 14.1

14.8 14.7 14.6 14.5 14.5 14.5

15.0 14.9 14.9 14.8 14.8 14.8

4H

2H 3H 4H 6H 8H 12H

13.7 13.5 13.5 13.5 13.5 13.5

14.2 14.0 13.9 13.8 13.8 13.7

14.0 13.9 13.9 13.9 13.9 13.9

14.5 14.3 14.2 14.2 14.1 14.1

14.8 14.6 14.6 14.5 14.5 14.5

13.8 13.7 13.6 13.6 13.6 13.7

14.4 14.1 14.0 13.9 13.9 13.9

14.1 14.0 14.0 14.0 14.0 14.1

14.6 14.4 14.4 14.3 14.3 14.3

14.9 14.7 14.7 14.7 14.7 14.7

8H

4H 6H 8H 12H

13.4 13.4 13.4 13.5

13.7 13.6 13.6 13.6

13.8 13.8 13.9 13.9

14.1 14.0 14.0 14.1

14.5 14.5 14.5 14.6

13.5 13.5 13.6 13.7

13.8 13.7 13.7 13.8

13.9 14.0 14.0 14.1

14.2 14.2 14.2 14.3

14.6 14.6 14.7 14.8

12H

4H 6H 8H

13.4 13.4 13.4

13.6 13.5 13.5

13.8 13.8 13.9

14.0 14.0 14.0

14.4 14.5 14.5

13.5 13.5 13.5

13.7 13.7 13.7

13.9 14.0 14.0

14.1 14.1 14.2

14.6 14.6 14.7

Reflector Smooth or elliptical patterned reflector made of anodized aluminium. Miscellaneous Pleiad Power 125 MR has to be connected to a separate ballast box, see accessories.

Viewing direction parallel to lamp axis

Variation of the observer position for the luminaire distances S

S=

Standard Table Correction Summand

1.0H 1.5H 2.0H

+4.5 / +7.2 / +9.2 /

-5.4 -7.8 -8.4

+4.4 / +7.0 / +9.0 /

-4.9 -7.1 -7.5

BK00

BK00

-4.8

-4.6

Corrected Glare Indices referring 3200lm to Total Luminous Flux

www.ceve.com.tw

Page 3


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

Fagerhult 62715 Icon 1 x TC-DEL 18 W / Luminaire Data Sheet Luminous emittance 1: 105

105

90

90

75

75

60

60

100

150 45

45

200

250 30

η = 29 %

cd/klm 15 C0-C180

Luminaire classification according to CIE: 100 CIE flux code: 31 65 90 100 29

0

30

15

C90-C270

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Installation Placed on a desk using the clamp or the base (accessory). Supplied with clamp. Connection The luminaire is supplied with a 2.0 m white screened mains cable and earthed plug. Design Counterbalance arm mainly of aluminium. The lamp housing is of enamelled polycarbonate, which is adjustable to give good flexibility with varying tasks, see measurement diagram. Enamelled in two matching colours similar to aluminium. Reflector Anodised aluminium with asymmetrical light distribution. Miscellaneous Icon is equipped with HF ballasts (std-start) as standard for compact fluorescent lamps FSQ-E . This means a flicker-free light and a long service life from the lamp. Lamp included. Designed by Olle Lundberg, Monitor.

www.ceve.com.tw

Page 4


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

Fagerhult 3965 Pegasus 1 x TC-T 26 W / Luminaire Data Sheet Luminous emittance 1: 135

135

60 45

120

120

30 105

105

90

90

75

75

60

60

45

η = 45 %

cd/klm 30 C0-C180

Luminaire classification according to CIE: 50 CIE flux code: 15 42 72 50 45

15

0

15

45

30

C90-C270

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Installation Wall bracket with two securing holes. Connection Two access holes. Snap-in terminal block 3x2.5 mm². Two access holes and knockouts for external mains cable. Opening for flush mains cable is placed in the centre. Design White enamell sheet steel (NCS 0500) with decorative rods in white enamell or matt brushed brass. Designed by Bengt Källgren.

www.ceve.com.tw

Page 5


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

Fagerhult 26303-10 Ten°Wall Line 2 x TC-L 55 W / Luminaire Data Sheet Luminous emittance 1: 150

150

160 135

135

120

80

120

120

105

105

90

90

η = 65 %

cd/klm

75

60

45

C0-C180

Luminaire classification according to CIE: 3 CIE flux code: 37 68 91 02 65

30 15 0 15 30

45

75

60

C90-C270

Luminous emittance 1: Glare Evaluation According to UGR

Installation On walls via the bracket (ordered separately). Two securing points on the brackets installation disc. Placement see dimension diagram. Connection 5-way terminal block and 30 mm cable entry for recessed installation. Knockouts in the top and underneath for a surface mounted mains cable. Snap-in connector between the wall bracket and luminaire. On request with switch fitted to the luminaire arm. Design Sheet steel luminaire body in white (NCS 0500 / RAL 9016) or alu -grey (RAL 9006) structured enamelled finish. A clear, shaped acrylic plastic diffuser covers the top of the luminaire. Louvre Line - A cone shaped opal louvre covers the light opening. The cone meets the acrylic diffuser on the top and creates a decorative light passage. Reflector Diffusing reflector to reduce the luminance on the opal louvre. Accessories Wall bracket purchased separately, see accessories. Miscellaneous Luminaires are available on request with HF ballasts for dimming.

www.ceve.com.tw

ρ Ceiling

70

70

50

50

30

70

70

50

50

30

ρ Walls

50

30

50

30

30

50

30

50

30

30

ρ Floor

20

20

20

20

20

20

20

20

20

20

Room Size Viewing direction at right angles X Y to lamp axis

Viewing direction parallel to lamp axis

2H

2H 3H 4H 6H 8H 12H

-4.2 -2.2 -1.5 -1.0 -0.9 -0.8

-3.7 -1.7 -1.0 -0.6 -0.5 -0.5

-3.0 -0.9 -0.2 0.3 0.4 0.5

-2.5 -0.5 0.2 0.7 0.8 0.8

-0.7 1.3 2.0 2.5 2.6 2.6

-6.8 -4.8 -4.0 -3.1 -2.7 -2.3

-6.2 -4.4 -3.5 -2.7 -2.3 -1.9

-5.5 -3.6 -2.7 -1.8 -1.4 -1.0

-5.0 -3.1 -2.3 -1.5 -1.1 -0.7

-3.2 -1.3 -0.4 0.4 0.8 1.2

4H

2H 3H 4H 6H 8H 12H

-3.7 -1.5 -0.6 0.0 0.2 0.2

-3.2 -1.1 -0.3 0.3 0.4 0.4

-2.4 -0.2 0.7 1.3 1.4 1.5

-2.0 0.1 1.0 1.6 1.7 1.7

-0.2 2.0 2.8 3.4 3.5 3.6

-5.4 -3.3 -2.2 -1.3 -0.8 -0.4

-5.0 -2.9 -1.9 -1.0 -0.6 -0.2

-4.1 -2.0 -0.9 0.0 0.5 0.9

-3.7 -1.7 -0.7 0.3 0.7 1.1

-1.9 0.2 1.2 2.1 2.5 3.0

8H

4H 6H 8H 12H

-0.3 0.5 0.7 0.8

-0.1 0.7 0.9 1.0

1.0 1.8 2.0 2.1

1.2 1.9 2.1 2.3

3.1 3.8 4.0 4.1

-1.6 -0.4 0.2 0.8

-1.4 -0.2 0.4 0.9

-0.3 0.9 1.5 2.1

-0.1 1.1 1.6 2.2

1.7 2.9 3.5 4.1

12H

4H 6H 8H

-0.3 0.5 0.8

-0.1 0.7 1.0

1.0 1.8 2.1

1.2 2.0 2.2

3.1 3.9 4.1

-1.6 -0.3 0.4

-1.4 -0.1 0.5

-0.3 1.0 1.7

-0.1 1.1 1.8

1.8 3.0 3.7

Variation of the observer position for the luminaire distances S

S=

1.0H 1.5H 2.0H

+0.1 / +0.1 / +0.4 /

-0.1 -0.2 -0.3

+0.1 / +0.2 / +0.3 /

-0.1 -0.2 -0.3

Standard Table

BK07

BK09

Correction Summand

-15.4

-15.8

Corrected Glare Indices referring 9600lm to Total Luminous Flux

Page 6


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

ERCO 88100023 Gimbal Directional spotlight for low-voltage halogen lamps /

Luminaire Data Sheet Luminous emittance 1: 105

105

90

90

75

75

60

60

6000

45

45

9000

12000

η = 75 %

cd/klm

30

15

0

C0-C180

Luminaire classification according to CIE: 100 CIE flux code: 97 100 100 99 92

30

15

C90-C270

Luminous emittance 1: Glare Evaluation According to UGR

Gimbal Directional spotlight for low-voltage halogen lamps Luminaire: cast aluminum, black powder-coated. Mounting ring: plastic, white (RAL9002), with multigroove baffle, cast aluminum, black powder-coated. Fixing springs. Cardanic suspension of the luminaire in the mounting ring. 0 °-40°tilt. Pivots are to be fixed. Mounting box for preinstallation with junction box for through -wiring, black powder-coated. Magnetic transformer 120/12V, 60Hz inside mounting box. Snap-in plug for connection between transformer and luminaire. Anti-glare ring as lamp retainer: plastic, black. Type Non IC luminaire. Insulation materials must be kept away from the luminaire by a minimum of 3". Thermally protected luminaire. Suitable for wet locations. Removal of luminaire allows access to transformer and junction box from below. Max. ceiling thickness 3/4".

ρ Ceiling

70

70

50

50

30

70

70

50

50

30

ρ Walls

50

30

50

30

30

50

30

50

30

30

ρ Floor

20

20

20

20

20

20

20

20

20

20

Room Size Viewing direction at right angles X Y to lamp axis

Viewing direction parallel to lamp axis

2H

2H 3H 4H 6H 8H 12H

9.8 9.7 9.6 9.5 9.5 9.4

10.4 10.0 10.3 9.9 10.2 9.9 10.0 9.8 10.0 9.8 9.9 9.8

10.6 10.5 10.4 10.3 10.3 10.2

10.8 10.7 10.7 10.6 10.6 10.5

9.8 9.7 9.6 9.5 9.5 9.4

10.4 10.0 10.3 9.9 10.2 9.9 10.0 9.8 10.0 9.8 9.9 9.8

10.6 10.5 10.4 10.3 10.3 10.2

10.8 10.7 10.7 10.6 10.6 10.5

4H

2H 3H 4H 6H 8H 12H

9.7 10.2 10.0 9.6 10.0 9.9 9.5 9.9 9.9 9.4 9.8 9.8 9.4 9.7 9.8 9.3 9.6 9.8

10.5 10.3 10.2 10.1 10.1 10.0

10.8 10.6 10.6 10.5 10.5 10.4

9.7 10.2 10.0 9.6 10.0 9.9 9.5 9.9 9.9 9.4 9.8 9.8 9.4 9.7 9.8 9.3 9.6 9.8

10.5 10.3 10.2 10.1 10.1 10.0

10.8 10.6 10.6 10.5 10.5 10.4

8H

4H 6H 8H 12H

9.4 9.3 9.2 9.2

9.7 9.5 9.4 9.3

9.8 10.1 9.7 9.9 9.7 9.9 9.7 9.8

10.5 10.4 10.3 10.3

9.4 9.3 9.2 9.2

9.7 9.5 9.4 9.3

9.8 10.1 9.7 9.9 9.7 9.9 9.7 9.8

10.5 10.4 10.3 10.3

12H

4H 6H 8H

9.3 9.2 9.2

9.6 9.4 9.3

9.8 10.0 10.4 9.7 9.9 10.3 9.7 9.8 10.3

9.3 9.2 9.2

9.6 9.4 9.3

9.8 10.0 10.4 9.7 9.9 10.3 9.7 9.8 10.3

Variation of the observer position for the luminaire distances S

S=

Standard Table Correction Summand

1.0H 1.5H 2.0H

+3.1 / +5.6 / +7.5 /

-4.2 -7.6 -16.9

+3.1 / +5.6 / +7.5 /

-4.2 -7.6 -16.9

BK00

BK00

-9.9

-9.9

Corrected Glare Indices referring 1000lm to Total Luminous Flux

www.ceve.com.tw

Page 7


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

ERCO 33200000 Parscoop I Wallwasher with mounting plate for tungsten halogen lamps / Luminaire Data Sheet Luminous emittance 1: 105

105

90

90

75

75

60

60

300

45

45

450

600

30

η = 59 %

cd/klm 15 C0-C180

Luminaire classification according to CIE: 98 CIE flux code: 49 79 95 97 58

0

30

15

C90-C270

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Parscoop I Wallwasher with mounting plate for tungsten halogen lamps Housing, hinge and mounting plate: corrosion-resistant cast aluminium, Norinse surface treatment. Double powder-coated. Optimised surface for reduced accumulation of dirt. Hinge with internal wiring, ± 90°tilt. Graduated disc: stainless steel. Mounting plate rotatable through 240 °. 2 cable entries. Through-wiring possible. 3-pole terminal block. Reflector: aluminium, silver anodised. Without spill light. Screw-mounted cover frame with safety glass: corrosion-resistant cast aluminium, double powder-coated. Hinge open for lamp replacement. Protection mode IP65: dust-proof and water jet-proof.

www.ceve.com.tw

Page 8


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

ERCO 33499000 Trion Ceiling washlight for tungsten halogen lamps / Luminaire

Data Sheet Luminous emittance 1: 150

150

400

300

135

135

200 120

120

105

105

90

75

90

η = 41 %

cd/klm 60 C0-C180

Luminaire classification according to CIE: 0 CIE flux code: 00 00 00 00 40

45

30 15 0 15 30

45

75

60

C90-C270

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

Trion Ceiling washlight for tungsten halogen lamps Housing and wall plate: cast aluminium, powder-coated. 2-pole terminal block. Reflector: aluminium, silver anodised. 2 cut-off shields: metal, black powder-coated. With max. wattage, the safety distance to the wall illuminated must not be less than 0.4m.

www.ceve.com.tw

Page 9


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

HOFFMEISTER 0.13950.44 Downlight 200 superflach, 1 TC-DEL 26W, EVG / Luminaire

Data Sheet Luminous emittance 1: 105

105

90

90

75

75

60

60

45

45

150

200

η = 60 %

cd/klm

30

15

0

C0-C180

Luminaire classification according to CIE: 100 CIE flux code: 46 88 100 99 60

30

15

C90-C270

Luminous emittance 1: Glare Evaluation According to UGR

Downlight 200 superflat, recess-mounted luminaire, TC-DEL 26 W, built-in electronic ballast, emergency light, IP 20, protection class I, rectangular ceiling trim thermoplastic, DA 214 / LH 80, 0.13950.44

ρ Ceiling

70

70

50

50

30

70

70

50

50

30

ρ Walls

50

30

50

30

30

50

30

50

30

30

ρ Floor

20

20

20

20

20

20

20

20

20

20

Room Size Viewing direction at right angles X Y to lamp axis

Viewing direction parallel to lamp axis

2H

2H 3H 4H 6H 8H 12H

21.3 21.8 21.7 21.6 21.6 21.6

22.6 23.0 22.8 22.6 22.6 22.5

21.6 22.1 22.1 22.0 22.0 21.9

22.9 23.2 23.1 22.9 22.9 22.8

23.1 23.5 23.4 23.2 23.2 23.1

21.3 21.8 21.7 21.6 21.6 21.6

22.6 23.0 22.8 22.6 22.6 22.5

21.6 22.1 22.1 22.0 22.0 21.9

22.9 23.2 23.1 22.9 22.9 22.8

23.1 23.5 23.4 23.2 23.2 23.1

4H

2H 3H 4H 6H 8H 12H

21.7 22.2 22.1 22.1 22.0 22.0

22.8 23.1 22.9 22.7 22.7 22.6

22.1 22.6 22.5 22.5 22.5 22.4

23.1 23.4 23.3 23.1 23.0 23.0

23.4 23.8 23.6 23.5 23.5 23.4

21.7 22.2 22.1 22.1 22.0 22.0

22.8 23.1 22.9 22.7 22.7 22.6

22.1 22.6 22.5 22.5 22.5 22.4

23.1 23.4 23.3 23.1 23.0 23.0

23.4 23.8 23.6 23.5 23.5 23.4

8H

4H 6H 8H 12H

22.1 22.0 22.0 21.9

22.7 22.5 22.4 22.3

22.5 22.4 22.4 22.4

23.1 22.9 22.8 22.8

23.5 23.4 23.3 23.3

22.1 22.0 22.0 21.9

22.7 22.5 22.4 22.3

22.5 22.4 22.4 22.4

23.1 22.9 22.8 22.8

23.5 23.4 23.3 23.3

12H

4H 6H 8H

22.0 22.0 21.9

22.6 22.4 22.3

22.5 22.4 22.4

23.0 22.8 22.8

23.4 23.3 23.3

22.0 22.0 21.9

22.6 22.4 22.3

22.5 22.4 22.4

23.0 22.8 22.8

23.4 23.3 23.3

Variation of the observer position for the luminaire distances S

S=

Standard Table Correction Summand

1.0H 1.5H 2.0H

+0.3 / +0.9 / +1.8 /

-0.3 -1.4 -3.5

+0.3 / +0.9 / +1.8 /

-0.3 -1.4 -3.5

BK01

BK01

2.3

2.3

Corrected Glare Indices referring 1800lm to Total Luminous Flux

www.ceve.com.tw

Page 10


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Summary 10.10 m 650

650

650

650

650

650

650

650

650 650

650

650

650

650 650

650 650

650

650

650

650

650

650

650

650

650

650

650

650

650

650

650

6.10 650

650

650

0.00 0.00

6.00

10.00

21.00 m

Height of Room: 2.800 m, Maintenance factor: 0.80 Surface Working Plane

ρ [%]

Eav [lx]

Values in Lux, Scale 1:149 Emin [lx]

Emax [lx]

Emin / E av

/

390

115

3302

0.30

Floors (6)

35

181

0.00

1198

/

Ceiling

70

225

82

3298

0.37

Walls (9)

69

125

11

3160

/

Working Plane: Height: Grid: Boundary Zone:

0.850 m 101 x 210 Points 0.000 m

Luminaire Parts List No.

Pieces

1

9

2

3

3

4

4

4

5

7

ERCO 33170000 Lucy Task light for low-voltage halogen lamps (1.000) ERCO 33200000 Parscoop I Wallwasher with mounting plate for tungste... (1.000) Fagerhult 26303-10 Ten° Wall Line 2 x TC-L 55 W (1.000) Fagerhult 53686 Ten°Circle 450 1 x (2x TC-TEL 32W + 2x TC-D 26 W) ... (1.000) Fagerhult 76300 Pleiad Power 125 MR 1 x HIPAR 30 35 W (1.000)

6

4

PHILIPS TBS 285 TBS285/236 M2 2xTL-D36W/830 (1.000)

www.ceve.com.tw

Designation (Correction Factor)

Φ [lm]

P [W]

930

58

2500

150

9600

58

8400

118

3200

10

6400

72

Page 11


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Summary Luminaire Parts List No.

Pieces

7

6

Designation (Correction Factor) PHILIPS TCS 630 TCS630/414 D7 4xTL5-14W/830 (1.000) total:

Φ [lm]

P [W]

4800

66

164670

2430

Specific connected load: 12.46 W/m² = 3.19 W/m²/100 lx (Area: 195.05 m²)

www.ceve.com.tw

Page 12


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Luminaire parts list 9 Pieces

3 Pieces

4 Pieces

4 Pieces

7 Pieces

ERCO 33170000 Lucy Task light for low-voltage halogen lamps Article No.: 33170000 Luminaire Luminous Flux: 930 lm Luminaire Wattage: 58 W Luminaire classification according to CIE: 100 CIE flux code: 75 92 99 100 62 Fitting: 1 x QT12-ax 50W (Correction Factor 1.000). ERCO 33200000 Parscoop I Wallwasher with mounting plate for tungsten halogen lamps Article No.: 33200000 Luminaire Luminous Flux: 2500 lm Luminaire Wattage: 150 W Luminaire classification according to CIE: 98 CIE flux code: 49 79 95 97 58 Fitting: 1 x QT-DE12 150W (Correction Factor 1.000). Fagerhult 26303-10 Ten° Wall Line 2 x TC-L 55 W Article No.: 26303-10 Luminaire Luminous Flux: 9600 lm Luminaire Wattage: 58 W Luminaire classification according to CIE: 3 CIE flux code: 37 68 91 02 65 Fitting: 2 x TC-L (Correction Factor 1.000). Fagerhult 53686 Ten° Circle 450 1 x (2x TC-TEL 32W + 2x TC-D 26 W) 118 W Article No.: 53686 Luminaire Luminous Flux: 8400 lm Luminaire Wattage: 118 W Luminaire classification according to CIE: 13 CIE flux code: 71 87 94 13 46 Fitting: 1 x (2x TC-TEL 32W + 2x TC-D 26 W) (Correction Factor 1.000). Fagerhult 76300 Pleiad Power 125 MR 1 x HIPAR 30 35 W Article No.: 76300 Luminaire Luminous Flux: 3200 lm Luminaire Wattage: 10 W Luminaire classification according to CIE: 100 CIE flux code: 97 99 99 100 97 Fitting: 1 x HIPAR 30 (Correction Factor 1.000).

www.ceve.com.tw

400

600

800

cd/klm

300

450

600

cd/klm

160

120

80

cd/klm

80 60 40

cd/klm

800 1200 1600 2000

2400 cd/klm

Page 13


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Luminaire parts list 4 Pieces

6 Pieces

PHILIPS TBS 285 TBS285/236 M2 2xTLD36W/830 Article No.: Luminaire Luminous Flux: 6400 lm Luminaire Wattage: 72 W Luminaire classification according to CIE: 100 CIE flux code: 61 93 99 100 68 Fitting: 2 x TL-D36W (Correction Factor 1.000). PHILIPS TCS 630 TCS630/414 D7 4xTL514W/830 Article No.: Luminaire Luminous Flux: 4800 lm Luminaire Wattage: 66 W Luminaire classification according to CIE: 100 CIE flux code: 74 99 100 99 82 Fitting: 4 x TL5-14W (Correction Factor 1.000).

www.ceve.com.tw

100 150 200

300 cd/klm

200

300

cd/klm

Page 14


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / 3D Rendering

www.ceve.com.tw

Page 15


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Working Plane / Isolines (E) 10.10 m 650

650

650

650

650

650

650

650

650 650

650

650

650

650 650

650 650

650

650

650

650

650

650

650

650

650

650

650

650

650

650

650

6.10 650

650

650

0.00 0.00

6.00

10.00

21.00 m

Values in Lux, Scale 1 : 149 Grid: 101 x 210 Points Eav [lx] 390

www.ceve.com.tw

Emin [lx] 115

Emax [lx] 3302

Emin / E av 0.30

Emin / E max 0.03

Page 16


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Working Plane / Greyscale (E) 10.10 m

6.10

0.00 0.00

6.00 650

10.00

21.00 m

1300

1950

lx

Scale 1 : 149 Grid: 101 x 210 Points Eav [lx] 390

www.ceve.com.tw

Emin [lx] 115

Emax [lx] 3302

Emin / E av 0.30

Emin / E max 0.03

Page 17


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Working Plane / Value Chart (E) 223

243

280

276 241

249

145

166 167 145

232

143

194

115

417 534 544

482 592 595

487 662 665

510 420 595 507 598 510

361 256 290

115 173 180

201 198 161 236 224 180 259 243 190

305 257 293

161 178 185

364 230 247

158 222 232

473 331

544 362

491

648 173 420

158 174 234

236 239 180 237 182 205 890 217 472

572 220 406

176 172 225

521 247 793

172 149 178

900 420

675 385

297 1915 267 932 291 533 273 430

686 399

289 1893 204 279 499 165

394 499

385 507

370 485

377 355 398 502 470 512

393 511

347 460

289 319

144 142

422 466 507 358 370 395 271 256 262

521 423 309

501 393 267

508 485 521 393 394 408 267 301 278

519 398 263

490 411 294

320 152 144

140 138 115

554 528 434 314 376 275 440 396 514 436 228 969 204 2001 364 993 778 331 1861 253 839 595 729 674 205 465 259 682 687 678 661 332 327 326 661 673 119 643 541 408 454 541 115 115 269 306 238 130 134 125

488 231 124

544 336 170

10.10 m

6.10

0.00 0.00

6.00

10.00

21.00 m

Values in Lux, Scale 1 : 149 Not all calculated values could be displayed. Grid: 101 x 210 Points Eav [lx] 390

www.ceve.com.tw

Emin [lx] 115

Emax [lx] 3302

Emin / E av 0.30

Emin / E max 0.03

Page 18


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / UGR 眩光計算面(主管) / Isolines (UGR) 2.10 m

10

10

15

15 20 25

25 30

0.00 0.00

3.00 m

Scale 1 : 22 Position of surface in room:

Grid: 3 x 2 Points Min <10

www.ceve.com.tw

Max 25

Page 19


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / UGR 眩光計算面(主管) / Greyscale (UGR) 2.10 m

0.00 0.00

3.00 m

10

15

20

25

30

Scale 1 : 22 Position of surface in room:

Grid: 3 x 2 Points Min <10

www.ceve.com.tw

Max 25

Page 20


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / UGR 眩光計算面(主管) / Value Chart (UGR) 2.10 m

<10

<10

<10

25

24

24

0.00 0.00

3.00 m

Scale 1 : 22 Position of surface in room:

Grid: 3 x 2 Points Min <10

www.ceve.com.tw

Max 25

Page 21


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Floor / Isolines (E) 10.10 m 9.30

400

400 400

400 400

400 200

200

200 400

600

400

400

400

600

400 800 400 400

6.10

400

400

400

400 400

400

4.08

200

200 200 200

200

0.79 0.00

0.00

5.99

10.00

21.00 m

Values in Lux, Scale 1 : 149 Position of surface in room:

Grid: 64 x 32 Points Eav [lx] 192

www.ceve.com.tw

Emin [lx] 70

Emax [lx] 1045

Emin / E av 0.36

Emin / E max 0.07

Page 22


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Floor / Greyscale (E) 10.10 m 9.30

6.10

4.08

0.79 0.00 0.00

5.99 200

10.00 400

21.00 m 600

800

lx

Scale 1 : 149 Position of surface in room:

Grid: 64 x 32 Points Eav [lx] 192

www.ceve.com.tw

Emin [lx] 70

Emax [lx] 1045

Emin / E av 0.36

Emin / E max 0.07

Page 23


辦公室照明規劃案 05.01.2006

DIALux Asia

Operator Telephone Fax e-Mail

lee jiunshian 04-23873177 04-23877199 club@dialux.cn

辦公室 / Floor / Value Chart (E) 70

70

70

70

70

70

70

70

70

90

132

91

135

90

114

109

113

70

70

70

70

70

151

165

156

167

159

157

141

147

70

70

70

70

70

95

173

99

177

94

154

121

141

181

240

217

192

246

156

244

152

363

647

670

351

963

271

960

226

334

416

448

251

608

274

637

193

315

354

243

211

264

248

269

149

325

205

70

108

70

91

249

141

302

319

308

293

325

253

97

128

70 70

70 70

70 70

81

70 70

408

70

70

70

70

70

70

70

70

70

70

70

70

70

70

70

70

463

204

443

987

283 1006

353

259

433

110

103

252

264

244

233

219

240

315

93

85

95

95

92

10.10 m

70

87

9.30

6.10

4.08

0.79 0.00

0.00

5.99

10.00

21.00 m

Values in Lux, Scale 1 : 149 Not all calculated values could be displayed. Position of surface in room:

Grid: 64 x 32 Points Eav [lx] 192

www.ceve.com.tw

Emin [lx] 70

Emax [lx] 1045

Emin / E av 0.36

Emin / E max 0.07

Page 24