ABBREVIATIONS
PLOT PLAN (NTS)
Architect:
TENANT SAFETY NOTES: RENOVATION IN RESIDENTIAL BUILDING:
3'-0" Min
W.169 STREET
1'-6"
3'-6" Min
1'-6"
2'-3" Max
4'-8" Min
4'-8" Min
5'-6" Min
FORT WASHINGTON AVE.
1'-6"
SIDE
1'-6"
2'-6" Min
3'-0" Min 1'-6"
SIDE
1. General: all work to be completed in accordance with the new york city building code, article 19, and regulations of all other agenies having jurisdiction. 2. Means of egress: all existing means of egress for tenants of the building to be maintained clear and free of all obstructions, such as building materials, tools, etc. 3. Fire safety: a. All building materials which are stored at the site or any area of the building are to be stored in a locked area. access to the area to be controlled by the owner, or the general contractor. b. All materials to be stored in a orderly fashion. c. All flammable materials to be kept tightly sealed in their respective manutacturers' containers. such materials are to be kept away from heat. d. All flammable materials to be used and stored in an adequately ventilated space. e. All electrical power to be shut off where there are exposed conduits. f. All electrical power in the construction area to be shut off after working hours. g. Contractor, at all times, to ensure there is no natural gas leakage in the buildings, or any flammable gas to be used during construction. 4. Dust control: a. Debris, dirt and dust to be kept to a minimum and confined to the immediate constuction area. b. Contractor to isolate construction area from occupied building area by means of temporary partitions or heavy weight drop cloths. c. Debris, dirt, and dust to be cleaned up and cleared from the building site periodically to avoid excessive accumulation. 5. Noise after hours: a. Construction operations will be confined to normal working hours, as stipulated in the alteration agreement. b. Contractor must obtain written permission from all affected parties to work other than regular hours. 6. Construction operations will not involve interruption of heating, water, or electrical services to other tenants. 7. Construction work will be confined to the apartment interior, and will not create dust, dirt, or other such inconveniences to the other apartment units within the building.
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Clear Floor Space
3'-0"
LAV Clear Floor Space
W.168 STREET
Mechanical Engineer:
Clear Floor Space
4'-0" Min
4'-0" Min
5'-0" Min
5'-0"
STANDARD SYMBOLS
SHOWER SIZES AND CLEARANCES
CLEAR FLOOR SPACE FOR ADAPTABLE BATHROOMS
Contractor:
4'-6" Min GENERAL NOTES:
1'-0" Max
1. The general conditions of the American Institute of Architects for the contract of the construction of interiors, latest edition, is hereby made a part of this contract as if they were printed herein in full. 2. The contractor shall provide owner with all applicable certificates of insurance, liability and workman's compensation as required by law and building regulations. 3. The contractor shall take all necessary precautions to protect the owner, tenants and job site from damage or fire. 4. The contractor shall inspect the job site to verify all conditions, measurements and job requirements and shall report any inconsistencies to the architect immediately. 5. The contractor shall furnish all labor, materials, equipment, and services required to perform a finished job and for the proper completion of all trades whether or not such items are expressly mentioned in the contract documents. 6. The contractor shall coordinate the work of all trades and cooperate with the the work of all trades whether or not part of this contract. 7. All work performed must comply with all current rules and regulations of all municipal agencies having jurisdiction over this work and with all department of building rules and the rules of the particular building in which the work is located. 8. The job site shall be kept broom clean at all times. upon completion of the work the contractor shall provide a broom clean space, free of all dust and debris. 9. The owner's signature must be obtained prior to ordering any materials or executing any work in excess of the original contract. 10. All work shall comply with current trade practices and conform to the standards of good workmanship. 11. The contractor shall cause the owner and architect and their agents to be held harmless from all liabilities resulting from any and all situations resulting from this work. 12. The contractor shall maintain a complete and up to date set of drawings on the job site at all times. 13. The contractor shall prepare and submit shop drawings to the architect for approval. Contractor shall inspect shop drawings prior to submission and no material shall be ordered prior to approval of shop drawings. 14. The contractor shall protect all property from damage. Any damage caused by the contractor's workmen or sub-contractor's workmen shall be repaired or replaced at no cost to the owner. 15. Contractor shall coordinate the work of all trades and shall cooperate with all trades not specifically part of this contract. 16. Contractor shall submit samples to the architect of all finishes of hardware, wood, switch plates, stone, tile, etc., for approval, prior to ordering. 17. Contractor shall be responsible for arranging with building management for elevators and/or other hoisting facilities for the handling of materials and shall bear all costs for same. 18. Tenant shall, through its building code consultant, arrange for drawings to be filed with the building department in the municipality having jurisdiction over the work, and for final sign-off. Contractor shall obtain permits and all other licenses and sign-offs required and shall bear all costs for same. 19. General contractor shall properly protect the owner and any adjacent property or work. Any damage to the same caused by contractor's workmen or subcontractor's workmen shall be repaired or replaced without delay. Patching and replacing of damaged work shall be done by general contractor. General contractor shall provide all necessary protection for the work until same is turned over to the client. 20. Shareholder is responsible for all elec. radiant heat 21. No solenoids or restrictions on the building HVAC/fan coil units. 22. All cabinetry to be removable
3'-6" Min
Note: Cross hatched areas to receive blocking for securing grab bars
3'-0" Max
INTERIOR ELEVATION
1'-0" 1'-0" Min Min
02
17" Min
19" Max
3
(B) BACK WALL
0000
TOILET PAPER DISPENSER LOCATION
INTERIOR ELEVATION
EXTERIOR ELEVATION
4'-0" Min NAME
(A) SIDE WALL
03
04
SPACE DESIGNATION
Legend:
CLEAR FLOOR SPACE AT LAVATORIES
REINFORCING AREAS FOR INSTALLATION OF GRAB BARS IN BATHROOMS
REVISION DESIGNATION
Notification:
X = 0"-25" Note: Dashed line indicates dimensional clearances of optional underlavatory enclosure
WINDOW DESIGNATION
3
0000
2'-6"
9" Min
4'-0"
27" Min
X 2'-1" Max
40" Max
1 29" Min
1. Provide selective demolition work as shown and as needed for a complete and proper installation of the work. 2. Contractor to perform selective demolition in a systematic manner. Use such methods as required to complete work indicated in accordance with demolition schedule and governing regulations; comply with new york city building code and regulations of the building. 3. Remove all items necessary to accommodate the new construction. 4. Remove salvageable items as noted for reuse with care to prevent damage. Store in a protected area where directed by the owner. 5. Repair and restore all permanent materials damaged during the demolition process or other construction activity. 6. Remove debris, rubbish and other non-salvageable materials resulting from demolition operations from the site. 7. Demolish and remove all existing partitions, doors, walls, floor coverings and ceilings as noted and/or keyed. 8. Demolish and remove all plumbing lines, fixtures and equipment as noted and/or keyed. All branchwork plumbing to be removed back to the riser. 9. Demolish and remove all existng electrical, telephone and computer wiring, devices, conduits and black boxes back to existing panels as noted and/or keyed. 10. Demolish all soffits, dropped ceilings including pencil rod and chicago bar or other furring materials. 11. Demolish all electrical points, including jboxes, terminations, cabling and switch controls. 12. Demolish all recessed light fixtures, sconces, cabinetry lighting and track lighting. 13. Demolish all air conditoning equipment including condensor units, air handlers, controls, and all duct work and grills. 14. All gas branch work to be demolished back to riser. New shut off valves to be installed. 15. All water, waste and venting branch work to be demolished back to riser locations. New shutoff valves to be installed throughout.
T-001.00
2'-6" Min
TP
1'-7" Min
3'-2" Max
2'-8" Min
01
Y = 48"
DEMOLITION NOTES
Key Plan:
2/A00.01
01 0.
AIR CONDITIONING ADJUSTABLE ABOVE FINISH FLOOR ALUMINUM AS NOTED ARCHITECT ACOUSTIC TILE CEILING BUILDING BY OTHERS BUILDING STANDARD CABINET CABINET CONTRACTOR CENTERLINE CLOSET CEILING COLUMN CONCRETE CONTINUOUS CARPET CERAMIC TILE DOWN DOOR DETAIL DRAWING ELEVATION ELECTRIC EQUAL EXISTING TO BE RELOCATED ELECTRIC WATER COOLER EXISTING FURNISH & INSTALL FINISH FULL HEIGHT FLOOR FINISH OPENING FIREPROOF FIREPROOF SELF CLOSING FIRE RATED FRAME FLUSH VALVE GAUGE GALVANIZED GENERAL CONTRACTOR GLASS GYPSUM WALL BOARD HOLLOW METAL HOLD OPEN HOUR HEIGHT HEATING/VENTILATION INSULATION INTERIOR INSTALL ONLY JANITOR CLOSET JUNCTION BOX JAMB OPENING JOINT LAVATORY LIGHTING MAXIMUM MINIMUM MECHANICAL MANUFACTURER MASONRY OPENING METAL NO HOLD OPENING NOT IN CONTRACT NUMBER NOT TO SCALE ON CENTER OPENING OPPOSITE PLATE PLASTIC LAMINATE PLUMBING PLYWOOD PANEL POLISHED PAIR PAINT QUARRY TILE RADIUS REFLECTED REINFORCE REQUIRED ROOM SEPARATE CIRCUIT SIMILAR STAINLESS STEEL SPECIFICATION SPEAKER SPRINKLER SQUARE STANDARD STEEL STRUCTURAL TELEPHONE TRIMMED OPENING TYPICAL UNLESS OTHERWISE NOTED VERIFY IN FIELD VINYL TILE WITH WOOD
THERE IS NO CHANGE OF USE, EGRESS, OR OCCUPANCY UNDER THIS APPLICATION
A0
A/C ADJ AFF ALUM AN ARCH ATC BLDG BO BS CAB CABC CL CLOS CLG COL CONC CONT CPT CT DN DR DTL DWG EL ELEC EQ ER EWC EXTG F/I FIN FH FLR FO FP FPSC FR FRM FV GA GALV GC GL GWB HM HO HR HT HVAC INSUL INT I/O JAN CL JB JO JT LAV LTG MAX MIN MECH MRF MO MTL NHO NIC NO NTS OC OPNG OPP PL PLLA PLMB PLY PNL POL PR PT QT RAD REF REINF REQ'D RM SC SIM STNSTL SPEC SPKR SPR SQ STD STL STR TEL TO TYP UON VIF VT W/ WD
GENERAL NOTES
DOOR DESIGNATION
DRAWING LABEL Scale: SCALE: ACTUAL SIZE
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
NO CHANGE OF USE, OCCUPANCY AND EGRESS
Z=X OR GREATER
PROPERTY IS NOT LOCATED IN SPECIAL FLOOD HAZARD AREA (SFHA)
Note: X = Reach Distance, Y = Maximum Height, Z = Clear Knee Space. Z is the clear space below the obstruction, which shall be at least as deep as the reach distance
MAXIMUM FORWARD REACH OVER AN OBSTRUCTION
LAVATORY CLEARANCES
SMOKE DETECTOR/CARBON MONOXIDE NOTES 1. Smoke/Carbon Monoxide detectors or devices shall be installed in ordinance with the Housing Maintenance Code, Multiple Dwelling Law the New York City Building Code the New York City Electrical Code and LL 7/04. 2. Smoke Detectors and Carbon Monoxide Detectors may be combined providing the devices comply with the provisions of title 27 of the administrative code of the city of New York and any applicable rules promulgated thereunder. 3. Each Smoke/Carbon Monoxide Detector shall be installed in accordance with Reference Standard 17-12 of the New York City Building Code. 4. Each Smoke/Carbon Monoxide Detector shall be installed outside of each sleeping room in the immediate vicinity or within 10-0" of the entrance to a sleeping room. 5. Each Smoke/Carbon Monoxide Detector shall be of a type that allows for readily testing of such device. 6. Duplex units shall have a device located on each level if only one means of egress is provided from each level. 7. Ceiling mounted devices shall be a minimum distance of 4" from any wall. 8. Wall mounted devices shall be a minimum of 4" to a maximum of 12" from the ceiling. 9. Each dwelling unit shall be equipped with an approved type smoke/carbon monoxide detector device receiving primary power from the building wiring with no switches in the circuit other than the over current device protecting the branch circuit as per New York City Building Code Sec. 27-980. 10. Existing buildings that are not equipped with hardwired connections shall be supplied with battery operated devices. 11. Such smoke/carbon monoxide detector must be either the ionization chamber type or the photoelectric detector type as per New York City Building Code Sec. 27-981, (b). 12. A "Certificate of Satisfactory Installation for Smoke/Carbon Monoxide Detectors" must be filed with the division of code enforcement H.P.D., 10 days after installation. 13. Written information of testing and maintenance of the devices shall be provided to the dwelling unit owner.
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
CONTROLLED INSPECTIONS TR1: FIRE STOP/DRAFT STOP/FIRE BLOCK FINAL ENERGY CODE COMPLIANCE TR8: LIGHTING AND DWELLING UNITS INTERIOR LIGHTING POWER LIGHTING CONTROLS
LIST OF DRAWINGS ARCHITECTURAL DRAWINGS: A-001.00 A-002.00 A-003.00 A-004.00 A-005.00 A-006.00 A-007.00 A-008.00 A-009.00 A-008.00
DEMO PLAN CONSTRUCTION PLAN WALL TYPES & DETAILS REFLECTED CEILING & POWER PLAN POWER PLAN ELEVATIONS ELEVATIONS ELEVATIONS ELEVATIONS ELEVATIONS
Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
T-001.00 File:
Architect:
GENERAL DEMOLITION NOTES:
LEGEND
VERIFY EXISTING CONDITIONS PRIOR TO THE COMMENCEMENT OF WORK AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES OR UNUSUAL CONDITIONS
EXISTING WALL TO REMAIN
PHASE ALL WORK TO ACHIEVE THE MINIMUM DISTURBANCE IN WORK AREAS; PROTECT UNAFFECTED AREAS FROM DUST DIRT AND NOISE
EXISTING WALL TO BE DEMOLISHED
REMOVE ALL DEBRIS FROM THE SITE AND DISPOSE OF IN A MANNER APPROVED BY ALL LOCAL, STATE, AND FEDERAL REGULATIONS. PERFORM ALL DEMOLITION AND CARTING IN ACCORDANCE WITH THE BUILDING RULES AND REGULATIONS. CARTING SHALL BE COORDINATED WITH THE BUILDING MANAGEMENT AND SUPERINTENDENT. BROOM SWEEP ALL PREMISES AND PUBLIC SPACES ON A DAILY BASIS, OR AS REQUIRED BY BUILDING MANAGEMENT.
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Mechanical Engineer:
SALVAGE EQUIPMENT, FIXTURES AND DOORS AS REQUIRED BY THE CONTRACT DOCUMENTS. REUSE AS DIRECTED ON DRAWINGS AND IN SCHEDULES.
Contractor:
SALVAGE SPECIFIED DOORS AND ATTACHED HARDWARE FOR COURSE OF JOB. REMOVE THOSE NOT REUSED AT END OF JOB AS DIRECTED BY OWNER. SEE DOOR SCHEDULE FOR THOSE SALVAGED AND RELOCATED.
Key Plan:
REMOVE ALL MISCELLANEOUS ATTACHMENTS TO WALLS, FLOORS, CEILINGS, WINDOWS, AND DOORS INCLUDING, BUT NOT LIMITED TO, NAILS, HOOKS, WIRES, DOORBELLS, AND STOPS. SHUT OFF ALL EXISTING PLUMBING HOOK-UPS IMMEDIATELY PRIOR TO DEMOLITION WORK AT EACH LOCATION. Legend:
REMOVE EXISTING FLOORING INCLUDING WOOD FLOOR, SADDLES, CARPET, TILE, STONE AND ALL SUB-FLOOR MATERIAL INCLUDING SLAB TOPPING. RESTORE TO VALUES SPECIFIED IN APPLICABLE CODES THE INTEGRITY OF EXISTING RATED PARTITIONS AND THE FIRE PROTECTION OF STRUCTURAL MEMBERS THAT ARE DAMAGED DURING CONSTRUCTION.
Notification: COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
PROVIDE A MINIMUM OF TWO (2) FIRE EXTINGUISHERS OR MORE AS REQUIRED BY NYC DOB. REMOVE ALL PARTITION WALLS, MILLWORK, DOORS, DOOR CASINGS, WINDOW CASINGS, DECORATIVE FINISHES, SHELVING AS INDICATED. REMOVE ALL EXISTING CONSTRUCTION LOCATED IN A MANNER SO AS NOT TO CONFLICT WITH WORK SHOWN ON OTHER DRAWINGS.
Issue Description
Date
Revision
Date
REMOVE AND REPLACE ANY OTHER CONSTRUCTION OUTSIDE LIMITS SHOWN, AS NECESSARY TO COMPLETE THE WORK. BRING ALL DEMOLITION AND REMOVAL TO A NATURAL STOPPING POINT. REPLACE ANY MATERIAL REMOVED BY MISTAKE OR IN EXCESS OF REQUIREMENTS.
REPAIR/ REPAINT (E) BRICK AS NECESSARY
WHERE ALTERATIONS OCCUR OR NEW AND OLD WORK JOIN, CUT, REMOVE, PATCH, REPAIR, OR REFINISH THE ADJACENT SURFACES, AND REMOVE EXISTING WORK TO PROFILES SHOWN FOR NEW WORK SO AS TO LEAVE IN AS GOOD A CONDITION AS EXISTED PRIOR TO COMMENCING OF WORK. PROTECT ALL FINISHES TO REMAIN. PROTECT PUBLIC CORRIDORS AND SPACES FROM DAMAGE. PROTECT ALL MATERIALS, SURFACES AND FINISHES TO REMAIN. SALVAGE ALL DOOR HARDWARE, LABEL AND BAG FOR RESTORATION AND REUSE. REMOVE ALL DROPPED CEILINGS, SOFFITS AND EXPOSED CONCRETE SLAB FOR INSPECTION AND PREPARATION FOR NEW FINISHES.
DEMOLITION PLAN 1 Scale: 1/4" = 1'0"
DEMOLISH & REPLACE (E) WINDOW
DISCONNECT AND REMOVE ALL EXISTING LIGHTING, ELECTRICAL BOXES, TELEPHONE EQUIPMENT, ELECTRICAL TERMINATIONS. SEE DEMOLITION AND ELECTRICAL NOTES FOR ADDITIONAL SAFETY REQUIREMENTS AND TEMPORARY LIGHTING REQUIREMENTS. REMOVE EXISTING RADIATOR ENCLOSURE AND HVAC EQUIPMENT INCLUDING ATTACHED DEVICES, DUCTING, GRILLS, CONDENSORS, AIR HANDLERS, PACKAGE UNITS DISCONNECT AND REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED BRANCH PIPING AND CAP AT PLUMBING STACK LOCATIONS. SEE PLUMBING NOTES FOR ADDITIONAL REQUIREMENTS REDUCE CHASE SIZE AT ALL LOCATION OF BUILDING PLUMBING RISERS TO A MINIMUM. EXPOSE ALL RISERS FOR INSPECTION BY ARCHITECT AND BUILDING MANAGEMENT DEMISING WALLS, STRUCTURAL ELEMENTS TO BE REDUCED TO THE MINIMUM DIMENSION WITHOUT UNDERMINING REQUIRED FIRE RATING. ALL WINDOWS TO BE DEMOLISHED
DEMOLISH & REPLACE (E) WINDOW
DEMOLISH & REPLACE (E) WINDOW
DEMOLISH & REPLACE (E) WINDOW
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
BUILDING NOTES: FEED BRANCH LINES MUST BE REPLACED BACK TO THE RISER. ALL RISERS MUST BE INSPECTED BY THE RESIDENT MANAGER UPON OPENING UP OF THE WALLS. IF ANY WORK IS REQUIRED THE RESIDENT MANAGER SHALL CONTACT THE BUILDING PLUMBER FOR FURTHER REVIEW. FEED BRANCH LINES MUST BE EQUIPPED WITH AN EMERGENCY SHUTOFF/CHECK VALVE AS CLOSE TO THE RISER AS POSSIBLE. THE VALVE MUST ALSO BE LOCATED OUTSIDE THE WALL OR IN A FIRE-RATED ACCESS PANEL. ALL BRANCH FEED PIPING MUST CONFORM TO LOCAL CODE REQUIREMENTS AND ONLY HIGH QUALITY COPPER PIPES SHALL BE USED. THE LOCATION OF ACCESS PANELS, VALVES AND NEW BRANCH LINE RUNS MUST BE SHOWN TO THE RESIDENT MANAGER DURING CONSTRUCTION. ALL EXPOSED AND NEW FEED PIPING SHALL BE INSULATED. ALL PIPE INSULATION MUST BE INSPECTED BY THE RESIDENT MANAGER PRIOR TO CLOSURE.
DEMOLITION PLAN Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
A-001.00 File:
Architect:
Restroom # 104 PROVIDE WATERPROOFING LATICRETE AT FLOOR AND EXTEND 4" UP ALL WALLS. PROVIDE DUROCK WALL BOARD IN ALL AREAS. INSTALL ALL TILE, MATERIAL TO BE PROVIDED BY CONTRACTOR. INSTALL PLUMBING FIXTURES, FITTING & ACCESSORIES PROVIDED BY CONTRACTOR. FURNISH & INSTALL ALL MILLWORK, MIRROR AND GLASS.
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Classroom # 100 FURNISH AND INSTALL NEW SUBFLOOR, UNDERLAYMAT, AS PER DETAILS SHEET A-003.00 FURNISH AND INSTALL NEW TERAZZO FLOOR, IN PATTERN SHOWN. SEE FINISH SHOWN.
Mechanical Engineer:
FURNISH AND INSTALL NEW BASE, DOORS, CASINGS, TRIM. FURNISH AND INSTALL NEW MILLWORK, BUILT CABINETS, SEE ELEVATIONS.
Contractor:
2 Key Plan:
4'-1112"
2
Legend: 714" 4'-09 16"
5'-75 16"
5'-55 8"
18'-2"
FLOOR FINISH F.2 IN PATTERN SHOWN
STORAGE Notification:
105
2
8'-1015 16"
RESTROOM
FLOOR FINISH F.10
10'-57 8"
1 A-007.00
01
02
104 5'-0" CLEAR
CLASSROOM 100
01
02
A-010.00
FLOOR FINISH F.1 IN PATTERN SHOWN
2
04
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
03
2'-97 8"
01
A-006.00
2
02
4'-65 8"
02
A-010.00
FLOOR FINISH F.1
STORAGE 106
01
7'-018"
17'-69 16"
7'-01116"
7'-114"
Break- out Space #101 FURNISH & INSTALL NEW SUBFLOOR, UNDERLAYMENT, AS PER DETAILS SHEET A003.00
03
A-008.00
04
2
2
5'-17 8"
2 02
FURNISH & INSTALL NEW TERAZZO FLOOR, IN PATTERN SHOWN. SEE FINISH SCHEDULE.
01
OFFICE
OFFICE
103
102
BREAK OUT SPACE
FURNISH & INSTALL NEW BASE, DOORS, CASINGS , TRIM & SLIDING PARTITION.
101
HVAC EQUIP.
2
6'-6"
HVAC EQUIP.
FURNISH & INSTALL NEW MILLWORK, BUILT-IN CABINETS, SEE ELEVATIONS.
Project Title: Office # 102 & 103 FURNISH & INSTALL NEW SUBFLOOR, UNDERLAYMENT, AS PER DETAILS SHEET A003.00 FURNISH & INSTALL NEW TERAZZO FLOOR, IN PATTERN SHOWN. SEE FINISH SCHEDULE. FURNISH & INSTALL NEW BASE, DOORS, CASINGS , TRIM , GLASS PARTITION AND DOOR. FURNISH & INSTALL NEW MILLWORK, BUILT-IN CABINETS, SEE ELEVATIONS.
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
CONSTRUCTION PLAN Seal & Signature:
Date: 11/18/2015 Project Number: Drawing:
7'-112"
5'-63 4"
19'-07 16"
Checked: Drawing Number:
A-002.00 File:
CONSTRUCTION PLAN 1 Scale: 3/8" = 1'0" FLOOR FINISH F.1
FLOOR FINISH F.2 IN PATTERN SHOWN
STC 56 BSA #301-60-SM
5
Architect:
STC 48 BSA #301-60-SM 618"
47 8"
35 8"
35 8"
5 8" 8"
5
5 8" 8"
5
8"
LATICRETE 9235 LIQUID MEMBRANE FILLET
214" 15 8" 5
5
8"
FINISH STONE/TILE
1 12" CR 16 GA STEEL SUSPENDED CHANNEL 475 POUNDS @ 4' O.C.
METAL STUD
STEEL FURRING CHANNEL
8"
LATICRETE 9235, LAP 12" MINIMUM @ FLOOR AND 6" MINIMUM UP WALL
UNDERSIDE OF SLAB
UNDERSIDE OF SLAB
PERIMETER SEALANT
STEEL TRACK
STEEL TRACK
3 5 8" BATT INSULATION
3 5 8" BATT INSULATION
1
4" DIAMETER GALVANIZED STEEL ROD CHEMICALLY FASTENED TO PLANK @ 4" O.C.
LATICRETE 9235 LIQUID MEMBRANE, TERMINATION AT SEAMS HYDROCUT 660 CREEP RESISTANT GEO COMPOSITE ECORE QT SOUNDPROOFING
STEEL TRACK 3 5 8" BATT INSULATION
GYPSUM WALL BOARD CEILING OR SOFFIT
EXTG. SLAB
UNDERSIDE OF SLAB
LATICRETE ABOVE GRADE WATERPROOFING MEMBRANE STONE/TILE METAL CORNER BEAD
EXTEND GWB TO UNDERSIDE OF SLAB, GROUT AND SEAL AT ENDS AS REQUIRED
EXTEND GWB TO UNDERSIDE OF SLAB, GROUT AND SEAL AT ENDS AS REQUIRED
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Mechanical Engineer:
EXTEND GWB TO UNDERSIDE OF SLAB, GROUT AND SEAL AT ENDS AS REQUIRED
Contractor:
Key Plan:
3 5 8" 18 GAUGE STEEL STUDS AT 16 INCHES ON CENTER
1 5 8" 18 GAUGE STEEL STUDS AT 16 INCHES ON CENTER
3 5 8" 18 GAUGE STEEL STUDS AT 16 INCHES ON CENTER
5
5
8" TYPE 'X' GWB BOTH SIDES, TAPE AND (3) COATS SPACKLE, USE GREENBOARDS AT ALL WET LOCATIONS
5 8" TYPE 'X' GWB BOTH SIDES, TAPE AND (3) COATS SPACKLE, USE GREENBOARDS AT ALL WET LOCATIONS
STEEL TRACK
STEEL TRACK
8" TYPE 'X' GWB BOTH SIDES, TAPE AND (3) COATS SPACKLE, USE GREENBOARDS AT ALL WET LOCATIONS
1
BITUTHENE WATER PROOFING Scale: 3" = 1'-0"
2
DROPPED AND FURRED CEILING DETAIL Scale: 1-1/2" = 1'-0"
5 8" TYP X GWB BOARD FRY REGLET REVEAL BASE DRMB-625-250 CLEAR ANODIZED
STEEL TRACK
LATICRETE 9235 WITH REINFORCEMENT FLEECE STONE/TILE ON THINSET
TERRAZZO
Legend:
METAL STUD UNDERLAYMENT
TYP. FLOOR CONSTRUCTION
Wall Type: 2 Hour Partition Scale: 3" = 1'0"
2
Wall Type: 1 Hour Partition Scale: 3" = 1'0"
3
Wall Type: Furring
212"
1
Scale: 3" = 1'0"
EXTG. SLAB
TYP. STONE/TILE FLOOR - ALL WET AREAS
3
FINISH SCHEDULE TAG
DESCRIPTION TERRAZZO - NTMA Specimen # EP-I-49 (WHITE WITH WHITE CHIPS) - PROVIDE 81" STAINLESS STEEL SPACER
SUBMIT SPEC FOR APPROVAL
F.2
TERRAZZO - NTMA Specimen # EP-II-65 (BLUE WITH WHITE CHIPS) - PROVIDE 81" STAINLESS STEEL SPACER
SUBMIT SPEC FOR APPROVAL
F.3
SOLID SURFACE: PORCELANOSA KRION - EXTREME LIGHT 4102 - THICKNESS AS SHOWN
SUBMIT SPEC FOR APPROVAL
F.4
SOLID SURFACE: PORCELANOSA KRION - NAVY BLUE 6704 - THICKNESS AS SHOWN
SUBMIT SPEC FOR APPROVAL
F.5
SOLID SURFACE: PORCELANOSA KRION - HAPPY RED 6405 - THICKNESS AS SHOWN
SUBMIT SPEC FOR APPROVAL
F.6
3FORM CHROMA RECYCLED ACRYLIC - 21" THICKNESS - COLOR:CRANBERRY
SUBMIT SPEC FOR APPROVAL
STAINLESS STEEL
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
EXTG. SLAB
Issue Description
Date
Revision
Date
TYP. TERRAZZO FLOOR
4
TYPICAL BASEBOARD DETAIL Scale: 3" = 1'0"
NOTES
F.1
F.7
FLOOR DETAILS Scale: 3" = 1'-0"
Notification:
SUBMIT SPEC FOR APPROVAL
F.8
ASH PLYWOOD
SUBMIT SPEC FOR APPROVAL
F.9
LONSEAL MOONWALK VINYL - NO. 345 - BLUE
SUBMIT SPEC FOR APPROVAL
F.10
CARTER GLASS CLASSIC SERIES GLASS TILE
SUBMIT SPEC FOR APPROVAL
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
WALL TYPES AND TYP DETAILS Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
GENERAL NOTES
A-003.00
1. Contractor to provide paint samples for review and approval for each room and selected colors prior to painting. All painting to be Level-3 paint finish. Assume Benjamin Moore paint.
File:
Architect:
ELECTRICAL NOTES
RCP LEGEND
CONTRACTOR TO VERIFY THAT ALL EQUIPMENT AND APPLIANCES ARE COMPATIBLE WITH EXISTING POWER. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL REQUIRED ADJUSTMENTS AND CHANGES.
New Secondary GWB Drop Ceiling: See Elevations for Heights.
GENERAL A). PROVIDE LOAD LETTER CONFIRMING THAT THE EXISTING ELECTRICAL SERVICE IS ADEQUATE FOR THE DEVICES, EQUIPMENT, AND FIXTURES SPECIFIED. CONTRACTOR TO EXTEND SERVICE FROM HALLWAY PANEL IF ADDITIONAL POWER IS REQUIRED, ACCORDING TO THE STANDARDS, SYSTEMS, AND SPECIFICATIONS OF THE BUILDING MANAGEMENT. RESTORE ALL EXISTING DISTURBED WORK TO ITS ORIGINAL CONDITION INCLUDING MAINTENANCE OF WIRING CONTINUITY AS REQUIRED. B). PROVIDE ALL FIXTURES, WIRING, AND ELECTRICAL OUTLETS, TELECOMMUNICATIONS WIRING, DEVICES, AND CATV AS INDICATED ON THE DRAWINGS. INSTALL ALL LIGHT FIXTURES PROVIDED BY OWNER. C). ALL WIRING DEVICES TO BE LUTRON ARCHITECTURAL STYLE. D). ELECTRICAL WORK TO INCLUDE IN-WALL TELEPHONE WIRING FROM THE NYNEX ENTRY TO ALL OUTLETS. WALL JACKS TO BE LEVITON TYPE 625. E). ELECTRICAL WORK TO INCLUDE IN-WALL WIRING FOR TV . OUTLETS TO BE DECORA TYPE. F). ELECTRICIAN TO BE RESPONSIBLE FOR DESIGN OF ALL CIRCUITS AND DISTRIBUTION AND FOR ALL REQUIRED PERMITS, INSPECTIONS AND APPROVALS FROM BOTH GOVERNMENT AGENCIES AND THE POWER UTILITY. G). REFER TO AV DRAWINGS FOR SCOPE OF WORK ALLOCATION H). PROVIDE GANG BOXES AND PLATES AS PER DIAGRAM. I). ALL SMOKE DETECTORS TO BE HARDWIRED. J). NO ALUMINUM WIRING PERMITTED. K). PROVIDE PIGTAILS AT ALL JUNCTION BOXES INDICATED ON DRAWINGS. INCLUDE INSTALLATION OF FIXTURES PROVIDED BY OWNER AT THOSE LOCATIONS. L). UNLESS OTHERWISE NOTED, LOCATE ALL CEILING BOXES ON THE CENTER LINE OF THE ROOM IN 2 DIRECTIONS AND LOCATE ALL WALL BOXES ON THE CENTER OF THAT WALL. CONFIRM LOCATION OF ALL BOXES WITH ARCHITECT. M). MOUNT ALL SWITCHES AT 4'-0" ABOVE FINISHED FLOOR.
FLUORESCENT LIGHT: NEO-RAY L1, L1.1 22DP-1T5-SC-4-1DB-?-EM-?-S92. COORDINATE SUSPENSION HEIGHT WITH ARCHITECT ON SITE.
ELECTRICAL SPECIFICATIONS NOTE: 1. SHOP DRAWINGS FOR ALL LIGHTING AND LOW VOLTAGE CONTROL SYSTEMS TO BE SUBMITTED TO THE ARCHITECT FOR REVIEW. MATERIALS: 1. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND IN GOOD CONDITION AND HAVE UNDERWRITER'S LABORATORIES LABELS. 2. ANY MATERIALS AND/OR EQUIPMENT WHICH THE DESIGNER AND ARCHITECT REGARDS AS UNSATISFACTORY SHALL NOT BE INSTALLED; OTHER MATERIALS OR EQUIPMENT SHALL BE SUBMITTED AND IF CONSIDERED NECESSARY TO REQUEST PARTICULAR ITEMS BY NAME AND/OR CATALOG NUMBER, SUCH REQUESTS SHALL BE COMPLIED WITH, WITHOUT ADDITIONAL CHARGE. 3. MATERIALS AND EQUIPMENT SHALL BE SPECIFIED IN OTHER PARAGRAPHS NOTED ON PLANS, OR SUBJECT TO APPROVAL, BASED UPON ADAPTABILITY FOR INTENDED USE. WORKMANSHIP: 1. INSTALL CONDUITS CAREFULLY AND PROTECT AGAINST DAMAGE, REMOVING ALL CRUSHED OR DAMAGED CONDUITS. CAP OR PLUG ENDS TO PROTECT AGAINST DIRT OR MOISTURE BEFORE PULLING WIRES. 2. ALL CONDUITS SHALL BE SUPPORTED WITH APPROPRIATE HANGERS AT NOT OVER 8 FOOT INTERVALS. RUN EXPOSED CONDUITS PARALLEL OR PERPENDICULAR TO WALLS. USE APPROPRIATE FITTINGS FOR ALL BENDS, ETC... 3. PROVIDE ALL LOCKNUTS AND BUSHINGS AS REQUIRED WHERE CONDUITS ENTER BOXES, CABINETS, ETC... 4. NOT MORE THAN THREE RIGHT-ANGLE BENDS, OR THEIR EQUIVALENT, SHALL BE MADE IN CONDUIT BETWEEN PULLBOXES. 5. LEAVE A DRAG WIRE IN EVERY SPARE OR EMPTY CONDUIT. 6. NOTHING SHALL BE DONE WHICH WILL IN ANY MANNER ENDANGER OR UNDERMINE THE STRUCTURE OR ANY PART THEREOF.
RECESSED FLUORESCENT LIGHT: NEO RAY 22DR-1T5-FSR-4-120-DB-?-EM-?-S92
L1.3
RECESSED FLUORESCENT LIGHT: NEO RAY
Mechanical Engineer: L3
IO LINE .75-WARM WHITE BY IO LIGHTING PRODCUTS. SEE www.iolighting.com
L4
Existing or Proposed Ceiling Clear Height. Coordinate with Elevations
L5
HALO POWER TRAC L642-P TRAC SYSTEM WITH HALO L761P-L265 LAMPHOLDER
EX/EM
L4
Contractor:
L4
S
LITE TOUCH METROPOLITAN KEYPAD, www.litetouch.com
Key Plan: Static Pressure Vent
L4
STORAGE
L4
L4 Ceiling Speaker
105 L1
L1
L1
L1 Smoke/CO Detector, refer to MEP drawings
RESTROOM
L4
104
L4
L4
CLASSROOM L1.3
L4
L1
L1
100
L4
L1
L1
L4
S
Legend:
L1.1 L1 L1 L1
STORAGE L4
L4
106
L4 L1
L1
L1
OFFICE
103
102
Notification:
ADDITIONAL NOTES 1 Locate Specialty Fixtures and Sconces On-Site with Architect as Shown. 2. Maximize Clear Ceiling Height Where Possible. Consult with Architect After Demolition.
S
OFFICE
BREAK OUT SPACE 101 L1
L1.1
L1
L1.1
S
L4
S
FEEDERS AND CIRCUITS: A). PROVIDE ANY AND ALL MATERIALS, EQUIPMENT. LABOR, ETC... NECESSARY FOR THE COMPLETE INSTALLATION OF ALL BRANCH CIRCUITS TO EQUIPMENT, RECEPTACLES AND LIGHTING OUTLETS, AND WIRING FOR CONTROL EQUIPMENT FURNISHED BY OTHERS, ETC... B). WHERE REQUIRED, FURNISH AND INSTALL SAFETY TYPE DISCONNECT SWITCHES, FUSED OR UNFUSED, WITH PROPER POLES AND NEUTRALS, AS EACH CASE REQUIRED, IF THE EQUIVALENT IS NOT EXISTING OR FURNISHED BY OTHERS, AND IS NECESSARY TO CONFORM TO CODE. C). PROVIDE MATCHING RECEPTACLES FOR ALL EQUIPMENT FURNISHED WITH CORD AND PLUG. D). MAKE DIRECT CONNECTIONS AS REQUIRED TO ALL EQUIPMENT NOT FURNISHED WITH CORD AND PLUG. CONDUITS: A). APARTMENT PANEL FEEDER SHALL BE HEAVY-WEIGHT, RIGID, GALVANIZED TYPE. B). GREENFIELD AND THINWALL TUBING MAY BE USED IN HUNG CEILING AND PARTITIONS AS PERMITTED BY CODE AND LABOR AGREEMENTS. C). NO EXPOSED CIRCUITING. DEMOLITION: A). DO ALL NECESSARY DEMOLITION AND REMOVAL OF EXISTING LIGHTING AND ELECTRICAL EQUIPMENT AS REQUIRED. B). REROUTE AND RECONNECT ALL CIRCUITING TO EXISTING LOADS WHICH ARE TO REMAIN IF SAME IS DISTURBED BY DEMOLITION WORK. PROVIDE NEW HOMERUNS, IF REQUIRED. C). CONDUITS COMING UP OUT OF FLOOR SLAB WHICH ARE TO BE REMOVED SHALL BE CUT BACK BELOW TOP OF FINISHED SLAB TO PERMIT PATCHING. D). DISCONNECT AND REMOVE ALL EXISTING WIRING AND EXPOSED CONDUITS NOT BEING RETAINED OR REUSED. E). INSTALL BLANK PLATES ON ALL EXISTING OUTLETS WHICH ARE TO REMAIN BUT HAVE NO DEVICES. F).PROVIDE EXTENSION COLLARS ON EXISTING OUTLETS WHERE EXISTING WALLS, COLUMNS, ETC... ARE BEING LAMINATED OR FURRED-OUT. G). RELOCATE EXISTING ACTIVE OUTLET BOXES, JUNCTION BOXES, ETC... WHICH ARE RENDERED INACCESSIBLE BY NEW CONSTRUCTION. TEMPORARY LIGHT AND POWER: A). POWER SHALL BE OBTAINED FROM THE EXISTING APARTMENT PANEL FEEDER. B). PROVIDE NECESSARY MATERIALS AND LABOR TO MAKE POWER CONNECTIONS FOR MACHINES, PORTABLE TOOLS, ETC... AS USED BY OTHER TRADES, REGARDLESS OF SIZE. C). FURNISH ALL LABOR NEEDED TO KEEP THIS TEMPORARY SYSTEM ENERGIZED DURING THE ENTIRE STANDARD PERIOD OF WORKING TIME OF ALL TRADES, PLUS 15 MINUTES BEFORE AND 15 MINUTES AFTER THIS TIME AND OVERTIME AS REQUIRED FOR ANY AND ALL TRADES. NEW LIGHTING AND APPLIANCE PANEL: A). FURNISH AND INSTALL LIGHTING AND APPLIANCE PANEL AS INDICATED ON PLANS, OF THE CIRCUIT BREAKER TYPE, CONSTRUCTED FOR A ONE (1) PHASE, THREE (3) WIRE, SOLID NEUTRAL, 120/208 VOLT SYSTEM. B). TIE-BARS SHALL NOT BE USED TO CREATE MULTI-POLE CIRCUITS. C). ONLY ONE WIRE SHALL BE INSTALLED UNDER EACH CIRCUIT BREAKER. D). PANELBOARD SHALL BE MOUNTED IN CODE GAUGE AND SIZE BOX(ES) FOR MOUNTING AS INDICATED ON PLANS, COMPLETE WITH TRIM AND DOOR. E). BRANCHES SHALL BE SINGLE POLE CIRCUIT BREAKERS IN GENERAL, AND SHALL BE 15 AMPERE FOR RECEPTACLE AND LIGHTING, 20 AMPERE FOR RECEPTACLES, AND OTHER SIZES AS NOTED ON PLANS. F). INSTALL ACCURATE DIRECTORY INSIDE PANEL DOOR. CATV / TELEPHONE SERVICE: A). PROVIDE ALL POWER SUPPLY OUTLETS AS NOTED AND REQUIRED BY THE TELEPHONE COMPANY FOR USE WITH ITS EQUIPMENT. B). PROVIDE ALL BUSHINGS ON EACH END OF TELEPHONE CONDUITS. C). EXACT EXTENT OF WORK REQUIRED SHALL BE DETERMINED FROM THE TELEPHONE COMPANY REPRESENTATIVE PRIOR TO COMMENCING WORK. D). ELECTRICAL WORK TO INCLUDE IN-WALL TELEPHONE AND CATV WIRING FROM THE UTILITY ENTRY TO APARTMENT TO ALL OUTLETS. WALL JACKS TO BE LEVITON TYPE 625 AND 406 81. WALL TELEPHONE OUTLET TO BE TYPE 630. ALL TELEPHONE LOCATIONS TO HAVE ACCESS TO 4 LINES. E). ALL CATV AND TELEPHONE OUTLETS TO HAVE HOMERUNS TO PANEL AT LOCATION INDICATED.
L1.2
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
L1
L1
HVAC EQUIP.
L1.1
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
HVAC EQUIP.
L1
1
L1
REFLECTED CEILING PLAN Scale: 1/4" = 1'0"
L1
PATCH AND REPAIR CEILING AS NECESSARY. PAINT ALL ABOVE +8'-2" IN ONE COLOR, TBD BY ARCHITECT
Project Title:
GROUNDING: 1. GROUNDING CONNECTIONS SHALL BE MADE TO THE NON-CONDUCTIVE CARRYING PARTS OF ALL ELECTRICAL EQUIPMENT AS REQUIRED. ELECTRICAL SERVICE: 1. EXISTING BUILDING INCOMING ELECTRIC SERVICE SHALL BE UTILIZED FOR THIS WORK. 2. MAKE ALL NECESSARY MODIFICATIONS, EXTENSIONS, ETC... AS NOTED ON PLANS AND/OR REQUIRED. 3. ENTIRE INSTALLATION SHALL BE IN FULL ACCORDANCE WITH ALL REQUIREMENTS OF THE CONSOLIDATED EDISON COMPANY AND THE SHERRY NETHRTLAND. CONDUCTORS: 1. ALL BRANCH CIRCUIT CONDUCTORS MAY BE TYPE TW FOR FIFTEEN AND TWENTY AMPERE CIRCUITS. ALL SIZES INDICATED ON PLANS ARE BASED UPON THW COPPER WIRE. 2. ALL CONDUCTORS #8 AND SMALLER SHALL BE SOLID, #6 AND LARGER SHALL BE STRANDED. PIPE SLEEVES, SUPPORTS AND INSERTS: 1. WHERE PIPES PASS THROUGH MASONRY, CONCRETE WALLS OR FLOORS, SET SUCH SLEEVES AS ARE NECESSARY FOR THE PASSAGE OF THE PIPES. 2. SLEEVES SHALL NOT BE USED IN ANY PORTION OF THE BUILDING WHERE THE USE OF SAME WOULD IMPAIR THE STRENGTH OF CONSTRUCTION FEATURES OF THE BUILDING. 3. SLEEVES PASSING THROUGH WALLS WHERE SUBJECT TO LEAKAGE SHALL BE CAULKED TO OBTAIN A WATER-TIGHT JOINT.
JOB CONDITIONS: A). WHERE EXISTING WIRING WHICH IS TO REMAIN IS LEFT EXPOSED BY THE DEMOLITION AND REMOVAL OF PARTITIONS AND/OR HUNG CEILINGS, REROUTE SUCH WIRING AS REQUIRED TO MAINTAIN THE CIRCUIT CONTINUITY. B). WHERE EXISTING WIRING WHICH IS TO REMAIN IS LEFT STUBBED UP FROM FLOOR BY THE DEMOLITION AND REMOVAL OF PARTITIONS RE-ROUTE SUCH WIRING AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY AND CUT BACK CONDUIT BELOW TOP OF FINISHED SLAB TO PERMIT PATCHING. C). WHERE EXISTING CIRCUITING IS BEING UTILIZED FOR CONNECTION OF NEW LOAD OR IS BEING RETAINED FOR EXISTING LOADS AND SUCH CIRCUITING IS NOT EXACTLY AS INDICATED ON PLANS, MAKE SUCH MODIFICATIONS AS MAY BE REQUIRED TO WIRING TO ACCOMPLISH THE DESIGN INTENT.
D). WHERE EXISTING LIGHTING, EQUIPMENT, WIRING, ETC... IS INDICATED AS REMAINING AND SUCH ITEMS INTERFERE WITH THE INSTALLATION OR DEMOLITION WORK OF OTHER TRADES, BUT WILL NOT CONFLICT WITH SAME AFTER WORK IS COMPLETED, DISCONNECT, REMOVE, RELOCATE TO AVOID CONFLICTS, REINSTALL AND RECONNECT SUCH ITEMS AS REQUIRED. E). WHERE EXISTING LIGHTING, EQUIPMENT, WIRING, ETC... IS TO REMAIN AND SUCH WIRING IS FOUND TO BE DEFECTIVE, MAKE ALL CORRECTIONS AND REPLACEMENTS NECESSARY TO ELIMINATE THE DEFECT AND PUT SUCH ITEMS IN SATISFACTORY OPERATING CONDITION. CUTTING AND PATCHING: A). DO ALL THE REQUIRED CUTTING OF THE STRUCTURE NECESSARY FOR THE INSTALLATION OF THIS WORK. NO CUTTING LIKELY TO WEAKEN THE STRUCTURE (OR ANY PART THEREOF) SHALL BE DONE WITHOUT THE WRITTEN APPROVAL OF THE OWNER. B). PATCHING SHALL BE DONE BY THE GENERAL CONTRACTOR.
MISC.NOTES: 1. 2. 3.
AT LOCATIONS SHOWING SWITCHPLATES WITH OUTLETS DIRECTLY ADJACENT IN PLAN, BOTH TO BE CENTERED VERTICALLY WITH RELATION TO EACH OTHER. ALL SWITCHPLATED TO BE 4'-0" AFF TO CENTER, THE FIRST SWITCHPLATE TO BE 4" AWAY FROM FINISHED DOOR CASING TO CENTER UNLESS OTHERWISE NOTED. ALL DIMENSIONS TO CENTERLINE OF FIXTURE.
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
RFELECTED CEILING PLAN Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
A-004.00 File:
Architect:
ELECTRICAL NOTES
POWER/ELEC. LEGEND
CONTRACTOR TO VERIFY THAT ALL EQUIPMENT AND APPLIANCES ARE COMPATIBLE WITH EXISTING POWER. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL REQUIRED ADJUSTMENTS AND CHANGES.
WIRE PLAN SYM SYM DESCRIPTION
GENERAL A). PROVIDE LOAD LETTER CONFIRMING THAT THE EXISTING ELECTRICAL SERVICE IS ADEQUATE FOR THE DEVICES, EQUIPMENT, AND FIXTURES SPECIFIED. CONTRACTOR TO EXTEND SERVICE FROM HALLWAY PANEL IF ADDITIONAL POWER IS REQUIRED, ACCORDING TO THE STANDARDS, SYSTEMS, AND SPECIFICATIONS OF THE BUILDING MANAGEMENT. RESTORE ALL EXISTING DISTURBED WORK TO ITS ORIGINAL CONDITION INCLUDING MAINTENANCE OF WIRING CONTINUITY AS REQUIRED. B). PROVIDE ALL FIXTURES, WIRING, AND ELECTRICAL OUTLETS, TELECOMMUNICATIONS WIRING, DEVICES, AND CATV AS INDICATED ON THE DRAWINGS. INSTALL ALL LIGHT FIXTURES PROVIDED BY OWNER. C). ALL WIRING DEVICES TO BE LUTRON ARCHITECTURAL STYLE. D). ELECTRICAL WORK TO INCLUDE IN-WALL TELEPHONE WIRING FROM THE NYNEX ENTRY TO ALL OUTLETS. WALL JACKS TO BE LEVITON TYPE 625. E). ELECTRICAL WORK TO INCLUDE IN-WALL WIRING FOR TV . OUTLETS TO BE DECORA TYPE. F). ELECTRICIAN TO BE RESPONSIBLE FOR DESIGN OF ALL CIRCUITS AND DISTRIBUTION AND FOR ALL REQUIRED PERMITS, INSPECTIONS AND APPROVALS FROM BOTH GOVERNMENT AGENCIES AND THE POWER UTILITY. G). REFER TO AV DRAWINGS FOR SCOPE OF WORK ALLOCATION H). PROVIDE GANG BOXES AND PLATES AS PER DIAGRAM. I). ALL SMOKE DETECTORS TO BE HARDWIRED. J). NO ALUMINUM WIRING PERMITTED. K). PROVIDE PIGTAILS AT ALL JUNCTION BOXES INDICATED ON DRAWINGS. INCLUDE INSTALLATION OF FIXTURES PROVIDED BY OWNER AT THOSE LOCATIONS. L). UNLESS OTHERWISE NOTED, LOCATE ALL CEILING BOXES ON THE CENTER LINE OF THE ROOM IN 2 DIRECTIONS AND LOCATE ALL WALL BOXES ON THE CENTER OF THAT WALL. CONFIRM LOCATION OF ALL BOXES WITH ARCHITECT. M). MOUNT ALL SWITCHES AT 4'-0" ABOVE FINISHED FLOOR.
GFI
Duplex Convenience Outlet, 15 amp DCTD
ELECTRICAL SPECIFICATIONS NOTE: 1. SHOP DRAWINGS FOR ALL LIGHTING AND LOW VOLTAGE CONTROL SYSTEMS TO BE SUBMITTED TO THE ARCHITECT FOR REVIEW. MATERIALS: 1. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND IN GOOD CONDITION AND HAVE UNDERWRITER'S LABORATORIES LABELS. 2. ANY MATERIALS AND/OR EQUIPMENT WHICH THE DESIGNER AND ARCHITECT REGARDS AS UNSATISFACTORY SHALL NOT BE INSTALLED; OTHER MATERIALS OR EQUIPMENT SHALL BE SUBMITTED AND IF CONSIDERED NECESSARY TO REQUEST PARTICULAR ITEMS BY NAME AND/OR CATALOG NUMBER, SUCH REQUESTS SHALL BE COMPLIED WITH, WITHOUT ADDITIONAL CHARGE. 3. MATERIALS AND EQUIPMENT SHALL BE SPECIFIED IN OTHER PARAGRAPHS NOTED ON PLANS, OR SUBJECT TO APPROVAL, BASED UPON ADAPTABILITY FOR INTENDED USE. WORKMANSHIP: 1. INSTALL CONDUITS CAREFULLY AND PROTECT AGAINST DAMAGE, REMOVING ALL CRUSHED OR DAMAGED CONDUITS. CAP OR PLUG ENDS TO PROTECT AGAINST DIRT OR MOISTURE BEFORE PULLING WIRES. 2. ALL CONDUITS SHALL BE SUPPORTED WITH APPROPRIATE HANGERS AT NOT OVER 8 FOOT INTERVALS. RUN EXPOSED CONDUITS PARALLEL OR PERPENDICULAR TO WALLS. USE APPROPRIATE FITTINGS FOR ALL BENDS, ETC... 3. PROVIDE ALL LOCKNUTS AND BUSHINGS AS REQUIRED WHERE CONDUITS ENTER BOXES, CABINETS, ETC... 4. NOT MORE THAN THREE RIGHT-ANGLE BENDS, OR THEIR EQUIVALENT, SHALL BE MADE IN CONDUIT BETWEEN PULLBOXES. 5. LEAVE A DRAG WIRE IN EVERY SPARE OR EMPTY CONDUIT. 6. NOTHING SHALL BE DONE WHICH WILL IN ANY MANNER ENDANGER OR UNDERMINE THE STRUCTURE OR ANY PART THEREOF.
Dedicated Duplex Appliance Outlet (consult appliance schedule and manufacture for electrical specifications)
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Mechanical Engineer:
Contractor:
Floor Outlet With Stainless Steel Cover Telephone / FAX STORAGE
Key Plan:
Computer
105 FEEDERS AND CIRCUITS: A). PROVIDE ANY AND ALL MATERIALS, EQUIPMENT. LABOR, ETC... NECESSARY FOR THE COMPLETE INSTALLATION OF ALL BRANCH CIRCUITS TO EQUIPMENT, RECEPTACLES AND LIGHTING OUTLETS, AND WIRING FOR CONTROL EQUIPMENT FURNISHED BY OTHERS, ETC... B). WHERE REQUIRED, FURNISH AND INSTALL SAFETY TYPE DISCONNECT SWITCHES, FUSED OR UNFUSED, WITH PROPER POLES AND NEUTRALS, AS EACH CASE REQUIRED, IF THE EQUIVALENT IS NOT EXISTING OR FURNISHED BY OTHERS, AND IS NECESSARY TO CONFORM TO CODE. C). PROVIDE MATCHING RECEPTACLES FOR ALL EQUIPMENT FURNISHED WITH CORD AND PLUG. D). MAKE DIRECT CONNECTIONS AS REQUIRED TO ALL EQUIPMENT NOT FURNISHED WITH CORD AND PLUG. CONDUITS: A). APARTMENT PANEL FEEDER SHALL BE HEAVY-WEIGHT, RIGID, GALVANIZED TYPE. B). GREENFIELD AND THINWALL TUBING MAY BE USED IN HUNG CEILING AND PARTITIONS AS PERMITTED BY CODE AND LABOR AGREEMENTS. C). NO EXPOSED CIRCUITING. DEMOLITION: A). DO ALL NECESSARY DEMOLITION AND REMOVAL OF EXISTING LIGHTING AND ELECTRICAL EQUIPMENT AS REQUIRED. B). REROUTE AND RECONNECT ALL CIRCUITING TO EXISTING LOADS WHICH ARE TO REMAIN IF SAME IS DISTURBED BY DEMOLITION WORK. PROVIDE NEW HOMERUNS, IF REQUIRED. C). CONDUITS COMING UP OUT OF FLOOR SLAB WHICH ARE TO BE REMOVED SHALL BE CUT BACK BELOW TOP OF FINISHED SLAB TO PERMIT PATCHING. D). DISCONNECT AND REMOVE ALL EXISTING WIRING AND EXPOSED CONDUITS NOT BEING RETAINED OR REUSED. E). INSTALL BLANK PLATES ON ALL EXISTING OUTLETS WHICH ARE TO REMAIN BUT HAVE NO DEVICES. F).PROVIDE EXTENSION COLLARS ON EXISTING OUTLETS WHERE EXISTING WALLS, COLUMNS, ETC... ARE BEING LAMINATED OR FURRED-OUT. G). RELOCATE EXISTING ACTIVE OUTLET BOXES, JUNCTION BOXES, ETC... WHICH ARE RENDERED INACCESSIBLE BY NEW CONSTRUCTION. TEMPORARY LIGHT AND POWER: A). POWER SHALL BE OBTAINED FROM THE EXISTING APARTMENT PANEL FEEDER. B). PROVIDE NECESSARY MATERIALS AND LABOR TO MAKE POWER CONNECTIONS FOR MACHINES, PORTABLE TOOLS, ETC... AS USED BY OTHER TRADES, REGARDLESS OF SIZE. C). FURNISH ALL LABOR NEEDED TO KEEP THIS TEMPORARY SYSTEM ENERGIZED DURING THE ENTIRE STANDARD PERIOD OF WORKING TIME OF ALL TRADES, PLUS 15 MINUTES BEFORE AND 15 MINUTES AFTER THIS TIME AND OVERTIME AS REQUIRED FOR ANY AND ALL TRADES. NEW LIGHTING AND APPLIANCE PANEL: A). FURNISH AND INSTALL LIGHTING AND APPLIANCE PANEL AS INDICATED ON PLANS, OF THE CIRCUIT BREAKER TYPE, CONSTRUCTED FOR A ONE (1) PHASE, THREE (3) WIRE, SOLID NEUTRAL, 120/208 VOLT SYSTEM. B). TIE-BARS SHALL NOT BE USED TO CREATE MULTI-POLE CIRCUITS. C). ONLY ONE WIRE SHALL BE INSTALLED UNDER EACH CIRCUIT BREAKER. D). PANELBOARD SHALL BE MOUNTED IN CODE GAUGE AND SIZE BOX(ES) FOR MOUNTING AS INDICATED ON PLANS, COMPLETE WITH TRIM AND DOOR. E). BRANCHES SHALL BE SINGLE POLE CIRCUIT BREAKERS IN GENERAL, AND SHALL BE 15 AMPERE FOR RECEPTACLE AND LIGHTING, 20 AMPERE FOR RECEPTACLES, AND OTHER SIZES AS NOTED ON PLANS. F). INSTALL ACCURATE DIRECTORY INSIDE PANEL DOOR. CATV / TELEPHONE SERVICE: A). PROVIDE ALL POWER SUPPLY OUTLETS AS NOTED AND REQUIRED BY THE TELEPHONE COMPANY FOR USE WITH ITS EQUIPMENT. B). PROVIDE ALL BUSHINGS ON EACH END OF TELEPHONE CONDUITS. C). EXACT EXTENT OF WORK REQUIRED SHALL BE DETERMINED FROM THE TELEPHONE COMPANY REPRESENTATIVE PRIOR TO COMMENCING WORK. D). ELECTRICAL WORK TO INCLUDE IN-WALL TELEPHONE AND CATV WIRING FROM THE UTILITY ENTRY TO APARTMENT TO ALL OUTLETS. WALL JACKS TO BE LEVITON TYPE 625 AND 406 81. WALL TELEPHONE OUTLET TO BE TYPE 630. ALL TELEPHONE LOCATIONS TO HAVE ACCESS TO 4 LINES. E). ALL CATV AND TELEPHONE OUTLETS TO HAVE HOMERUNS TO PANEL AT LOCATION INDICATED.
Duplex Ground Fault Interupt Convenience Outlet, 15 amp
RESTROOM
TV
Cable
104 CLASSROOM 100
Legend:
STORAGE 106
OFFICE
OFFICE
103
102
BREAK OUT SPACE 101
HVAC EQUIP.
Notification: COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
HVAC EQUIP.
1
POWER PLAN Scale: 1/4" = 1'0"
Project Title:
GROUNDING: 1. GROUNDING CONNECTIONS SHALL BE MADE TO THE NON-CONDUCTIVE CARRYING PARTS OF ALL ELECTRICAL EQUIPMENT AS REQUIRED. ELECTRICAL SERVICE: 1. EXISTING BUILDING INCOMING ELECTRIC SERVICE SHALL BE UTILIZED FOR THIS WORK. 2. MAKE ALL NECESSARY MODIFICATIONS, EXTENSIONS, ETC... AS NOTED ON PLANS AND/OR REQUIRED. 3. ENTIRE INSTALLATION SHALL BE IN FULL ACCORDANCE WITH ALL REQUIREMENTS OF THE CONSOLIDATED EDISON COMPANY AND THE SHERRY NETHRTLAND. CONDUCTORS: 1. ALL BRANCH CIRCUIT CONDUCTORS MAY BE TYPE TW FOR FIFTEEN AND TWENTY AMPERE CIRCUITS. ALL SIZES INDICATED ON PLANS ARE BASED UPON THW COPPER WIRE. 2. ALL CONDUCTORS #8 AND SMALLER SHALL BE SOLID, #6 AND LARGER SHALL BE STRANDED. PIPE SLEEVES, SUPPORTS AND INSERTS: 1. WHERE PIPES PASS THROUGH MASONRY, CONCRETE WALLS OR FLOORS, SET SUCH SLEEVES AS ARE NECESSARY FOR THE PASSAGE OF THE PIPES. 2. SLEEVES SHALL NOT BE USED IN ANY PORTION OF THE BUILDING WHERE THE USE OF SAME WOULD IMPAIR THE STRENGTH OF CONSTRUCTION FEATURES OF THE BUILDING. 3. SLEEVES PASSING THROUGH WALLS WHERE SUBJECT TO LEAKAGE SHALL BE CAULKED TO OBTAIN A WATER-TIGHT JOINT.
JOB CONDITIONS: A). WHERE EXISTING WIRING WHICH IS TO REMAIN IS LEFT EXPOSED BY THE DEMOLITION AND REMOVAL OF PARTITIONS AND/OR HUNG CEILINGS, REROUTE SUCH WIRING AS REQUIRED TO MAINTAIN THE CIRCUIT CONTINUITY. B). WHERE EXISTING WIRING WHICH IS TO REMAIN IS LEFT STUBBED UP FROM FLOOR BY THE DEMOLITION AND REMOVAL OF PARTITIONS RE-ROUTE SUCH WIRING AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY AND CUT BACK CONDUIT BELOW TOP OF FINISHED SLAB TO PERMIT PATCHING. C). WHERE EXISTING CIRCUITING IS BEING UTILIZED FOR CONNECTION OF NEW LOAD OR IS BEING RETAINED FOR EXISTING LOADS AND SUCH CIRCUITING IS NOT EXACTLY AS INDICATED ON PLANS, MAKE SUCH MODIFICATIONS AS MAY BE REQUIRED TO WIRING TO ACCOMPLISH THE DESIGN INTENT.
D). WHERE EXISTING LIGHTING, EQUIPMENT, WIRING, ETC... IS INDICATED AS REMAINING AND SUCH ITEMS INTERFERE WITH THE INSTALLATION OR DEMOLITION WORK OF OTHER TRADES, BUT WILL NOT CONFLICT WITH SAME AFTER WORK IS COMPLETED, DISCONNECT, REMOVE, RELOCATE TO AVOID CONFLICTS, REINSTALL AND RECONNECT SUCH ITEMS AS REQUIRED. E). WHERE EXISTING LIGHTING, EQUIPMENT, WIRING, ETC... IS TO REMAIN AND SUCH WIRING IS FOUND TO BE DEFECTIVE, MAKE ALL CORRECTIONS AND REPLACEMENTS NECESSARY TO ELIMINATE THE DEFECT AND PUT SUCH ITEMS IN SATISFACTORY OPERATING CONDITION. CUTTING AND PATCHING: A). DO ALL THE REQUIRED CUTTING OF THE STRUCTURE NECESSARY FOR THE INSTALLATION OF THIS WORK. NO CUTTING LIKELY TO WEAKEN THE STRUCTURE (OR ANY PART THEREOF) SHALL BE DONE WITHOUT THE WRITTEN APPROVAL OF THE OWNER. B). PATCHING SHALL BE DONE BY THE GENERAL CONTRACTOR.
MISC.NOTES: 1. 2. 3.
AT LOCATIONS SHOWING SWITCHPLATES WITH OUTLETS DIRECTLY ADJACENT IN PLAN, BOTH TO BE CENTERED VERTICALLY WITH RELATION TO EACH OTHER. ALL SWITCHPLATED TO BE 4'-0" AFF TO CENTER, THE FIRST SWITCHPLATE TO BE 4" AWAY FROM FINISHED DOOR CASING TO CENTER UNLESS OTHERWISE NOTED. ALL DIMENSIONS TO CENTERLINE OF FIXTURE.
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
POWER PLAN Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
A-005.00 File:
Architect: PROVIDE SAGATSUNE PIANO HINGE
WHITE BOARD
WHITE BOARD
PROVIDE SAGATSUNE PIANO HINGE
PROVIDE SAGATSUNE PIANO HINGE
WHITE BOARD
CEILING EL + 12'-4"
HAFELE COAT HOOK 842.01.233
PT FINISH F.5 1/2"
SOFFIT EL + 8'-2"
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Mechanical Engineer:
EXIT
Contractor: FINISH F.5
PT
FINISH F.5 3/4"
Key Plan:
03 A-006
FLOOR EL + 0'-0"
Legend: 4'-09 16"
5'-75 16"
EQ.
EQ.
FINISH F.5
EQ.
18'-2"
ELEVATION 01 Scale: 1/2" = 1'0"
Notification:
TEMPERED GLASS DOOR FINISH F.5
1'-512"
1
CEILING EL + 12'-4"
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
FINISH F.5 1 4"
212"
SOFFIT EL + 8'-2" 1'-618"
PT
MILLWORK DETAIL 3 Scale: 3" = 1'0"
PT
BLOCKING AS NECESSARY
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM
FLOOR EL + 0'-0"
DRAWING NAME:
2
ELEVATION 03 Scale: 1/2" = 1'0"
ELEVATIONS FINISH F.9
STAINLESS STEEL CORNER TRIM
REPAIR / REPRINT BRICK AS NECESSARY & PAINT
Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
A-006.00 File:
Architect: INTERIOR WINDOW FINISH F.5
CEILING EL + 12'-4"
STEEL SUBSTRUCTURE
DORMA G150 TRACK & PIVOT
PT
SOFFIT EL + 8'-2"
DORMA FSW-G RAIL & RAIL COVER
1 8"
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Mechanical Engineer:
3 FORM ARYLIC PANEL F.6
Contractor: PT
PT
OPEN
PT
Key Plan:
DORMA FSW-G RAIL & RAIL COVER
FLOOR EL + 0'-0"
Legend:
1
ELEVATION Scale: 1/2" = 1'0" FINISH F.3
FINISH F.5
FINISH F.3
Notification:
3
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
FOLDING SLIDING WALL DETAIL Scale: 3" = 1'0"
CEILING EL + 12'-4"
SOFFIT EL + 8'-2"
Issue Description
Date
Revision
Date
SOLID WOOD CASING
PT
2" X 2" STEEL FRAME
PT 3 4"
04 A-007
PLYWOOD
PT 1 4"
1 4"
DRY ERASE BOARD
STAINLESS STEEL FRAME
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM
1"
FLOOR EL + 0'-0"
DRAWING NAME:
ELEVATION 2 Scale: 1/2" = 1'0"
ELEVATIONS 1118"
03 A-007
TYPICAL BASE DETAIL
FINISH F.9
Seal & Signature:
Date: 11/18/2015 Project Number: Drawing:
STAINLESS STEEL CORNER TRIM
Checked: Drawing Number:
A-007.00 File:
4
DRY ERASE PANEL Scale: 3" = 1'0"
Architect:
REPAIR/ REPOINT BRICK AS NECESSARY, PAINT
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
PT
Mechanical Engineer:
2'-912"
PT
Contractor: PT
2'-63 16"
1'-115 16"
Key Plan:
05 A-008
1'-63 4"
ELEVATION Scale: 1/2" = 1'0"
2
ELEVATION Scale: 1/2" = 1'0"
Legend:
1'-6"
1 2"
3
TEMPERED GLASS PANEL
ELEVATION Scale: 1/2" = 1'0"
1 2"
TEMPERED GLASS DOOR
4
ELEVATION Scale: 1/2" = 1'0" Notification:
TYPICAL MILLWORK NOTES 1'-0"
1. FINISH F.8
FINISH F.3
FINISH F.4
ROLL OUT SHELVING AND DRAWERS TO BE INSTALLED ON DRAWER RUNNERS BY BLUM TANDEM PLUS RUNNER INTEGRATED WITH BLUMOTION.
2.
ALL CABINET DOORS TO BE INSTALLED WITH BLUM CLIPTOP CONCEALED HINGES AND BLUMOTION.
3.
APPLIANCES ARE OWNER FURNISHED CONTRACTOR INSTALL
4.
CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR ALL MILLWORK SCOPE FOR REVIEW AND APPROVAL BY ARCHITECT
5.
CABINETS AND DRAWERS TO BE LOCKABLE. ARCHITECT TO SPEC LOCK
6.
ALL ADJUSTABLE SHELVES TO BE FITTED WITH HAFELE METAL SHELF SUPPORT 282.04.739
7.
CONTRACTOR TO PROVIDE ALL FINISH SAMPLE FOR REVIEW AND APPROVAL.
8.
CONTRACTOR TO RECONFIRM ALL MATERIAL AND FINISH WITH ARCHITECT (STONE, SOLID SURFACE, ETC) PRIOR TO ORDERING & FABRICATION.
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
FINISH F.3
4"
FINISH F.3
8"
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM
1'-15 8"
DRAWING NAME:
ELEVATIONS Seal & Signature:
43 8"
1
2'-614"
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
1'-10"
A-008.00 File:
5
MILLWORK DETAIL Scale: 1 1/2" = 1'0"
Architect:
CEILING EL + 12'-4"
CEILING EL + 12'-4"
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
SOFFIT EL + 8'-2"
SOFFIT EL + 8'-2"
Mechanical Engineer:
FINISH F.3
PT FINISH F.3
FIXED TEMPERED GLASS PANEL
Contractor:
Key Plan: PROVIDE KNIFE EDGE PULL
PROVIDE KNIFE EDGE PULL
1 2
THK TEMPERED GLASS DOOR
FLOOR EL + 0'-0"
FLOOR EL + 0'-0"
Legend:
EQ 4'-01116"
3'-0"
3'-0"
ELEVATION Scale: 1/2" = 1'0"
1
EQ
EQ
EQ
14'-51116"
4'-018"
2
ELEVATION Scale: 1/2" = 1'0"
Notification:
FINISH F.3
TYPICAL MILLWORK NOTES
1.
ROLL OUT SHELVING AND DRAWERS TO BE INSTALLED ON DRAWER RUNNERS BY BLUM TANDEM PLUS RUNNER INTEGRATED WITH BLUMOTION.
2.
ALL CABINET DOORS TO BE INSTALLED WITH BLUM CLIPTOP CONCEALED HINGES AND BLUMOTION.
3.
APPLIANCES ARE OWNER FURNISHED CONTRACTOR INSTALL
4.
CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR ALL MILLWORK SCOPE FOR REVIEW AND APPROVAL BY ARCHITECT
5.
CABINETS AND DRAWERS TO BE LOCKABLE. ARCHITECT TO SPEC LOCK
6.
ALL ADJUSTABLE SHELVES TO BE FITTED WITH HAFELE METAL SHELF SUPPORT 282.04.739
7.
CONTRACTOR TO PROVIDE ALL FINISH SAMPLE FOR REVIEW AND APPROVAL.
8.
CONTRACTOR TO RECONFIRM ALL MATERIAL AND FINISH WITH ARCHITECT (STONE, SOLID SURFACE, ETC) PRIOR TO ORDERING & FABRICATION.
AJUSTABLE SHELVES
FINISH F.3 1 4"
8116"
FINISH F.8
COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
Project Title: FINISH F.8
FINISH F.3 1 4"
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
ELEVATIONS Seal & Signature:
Date: 11/18/2015
414"
Project Number: Drawing: Checked: Drawing Number:
A-009.00 File:
3
MILLWORK DETAIL Scale: 1/2" = 1'0"
Architect:
Nava Companies 31 Union Square West, Suite 2D New York, NY 10003, USA +1 212.365.1052 www.navacompanies.com
Mechanical Engineer:
FINISH F.10
FINISH F.10
FINISH F.10
FINISH F.10
Contractor:
Key Plan:
Legend:
1
ELEVATION Scale: 1/2" = 1'0"
2
ELEVATION Scale: 1/2" = 1'0"
3
ELEVATION Scale: 1/2" = 1'0"
4
ELEVATION Scale: 1/2" = 1'0"
Notification: COPYRIGHT NOTICE: THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER SECTION 102 OF THE COPYRIGHT ACT 17 U.S.O. AS MENTIONED DECEMBER 1990 AND KNOWN AS ARCHITECTURAL WORKS PROTECTION ACT OF 1990. THE PROTECTION INCLUDES BUT IS NOT LIMITED TO THE OVERALL FORM AS WELL AS THE ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE PLANS, WORK, OR BUILDING REPRESENTED CAN LEGALLY RESULT IN CESSATION OF CONSTRUCTION OR BUILDING BEING SEIZED AND/OR MONETARY COMPENSATION TO: NAVA COMPANIES LLC THIS PLAN IS SUBMITTED ONLY FOR WORK INDICATED ON THE APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OF OR IN ACCORDANCE WITH APPLICABLE CODES.
Issue Description
Date
Revision
Date
FIXTURE SCHEDULE LOCATION
TYPE
MFR
MODEL
FINISH
RESTROOM 104
ADA LAVATORY
1
AMERICAN STANDARD
STUDIO ABOVE-0621.001
WHITE VITREOUS CHINA
RESTROOM 104
ADA FAUCET
1
AMERICAN STANDARD
SERIN-2064.101
POLISHED CHROME
RESTROOM 104
TOILET
1
AMERICAN STANDARD
AFWALL 2257.103
WHITE VITREOUS CHINA
RESTROOM 104
TOILET SEAT
1
AMERICAN STANDARD
AFWALL 5905.110
WHITE PLASTIC
RESTROOM 104
TOILET FLUSH VALVE
1
SLOANE VALVE CO.
ROYAL FLUSHOMETER 111
SATIN STAINLESS STEEL
RESTROOM 104
ADA MIRROR
1
BOBRICK
B-290-2436
POLISHED CHROME
RESTROOM 104
ADA GRAB BAR
1
BOBRICK
CLASSIC B-68616
SATIN STAINLESS STEEL
RESTROOM 104
ADA SOAP DISPENSER
1
BOBRICK
CLASSIC B-2111
SATIN STAINLESS STEEL
SURFACE MOUNTED
RESTROOM 104
HAND DRYER
1
BOBRICK
CLASSIC B-708
WHITE VITREOUS ENAMEL
ELECTRIC DRYER
RESTROOM 104
TRASH RECEPTACLE
1
BOBRICK
CLASSIC B-3644
SATIN STAINLESS STEEL
RECESS MOUNTED
RESTROOM 104
TOILET PAPER HOLDER
1
BOBRICK
CLASSIC B-2892
SATIN STAINLESS STEEL
SURFACE MOUNTED
RESTROOM 104
NAPKIN DISPOSAL
1
BOBRICK
CLASSIC B-254
SATIN STAINLESS STEEL
SURFACE MOUNTED
NAPKIN VENDOR
1
BOBRICK
CLASSIC B-352-25
SATIN STAINLESS STEEL
SURFACE MOUNTED
RESTROOM 104
QUANTITY
NOTE
WALL MOUNTED
Project Title:
FORT WASHINGTON ARMORY - ACADEMY ROOM DRAWING NAME:
ELEVATIONS Seal & Signature:
Date: 11/18/2015 Project Number: Drawing: Checked: Drawing Number:
A-010.00 File: