New Life Safety Requirements from The Joint Commission - Business Occupancies

Page 1

New Life Safety Requirements from The Joint Commission Business Occupancies Effective: July 2021



New Life Safety Requirements from The Joint Commission Business Occupancies

There are five (5) new standards and twenty-nine (29) new elements of performance that addresses fire safety and means of egress during fire emergencies:

• Standard LS.05.01.10 – Building & fire protection elements • Standard LS.05.01.20 – Means of egress • Standard LS.05.01.30 – Building elements • Standard LS.05.01.34 – Fire alarm systems • Standard LS.05.01.35 – Fire extinguishing equipment & systems


The best recommendation that The Joint Commission is offering to tackle these new requirements is to create a Building Maintenance Program (BMP) that should be organized and planned to obtain successful compliance within Business Occupancies. The following elements need to be taken into consideration when addressing these new standards: • 18” or more of open space is kept below the sprinkler to the top of storage • 75’ or less is the travel distance from any point to the nearest fire extinguisher • Alcohol-based hand rubs (ABHR) are reserved and organized in accordance with NFPA 101-2012 • A one (1) hour fire resistance-rated barrier or a smoke resistive barrier and automatic sprinklers are needed for protection between hazardous areas and anywhere else » Self-closing or automatic closing doors are needed with latching hardware



• Assessments of fire barriers , fire-rated smoke barriers and fire-rated smoke partitions • Corridors or passageways must have a minimum 44” of clear width in occupancies that serve fifty (50) or more people • Dead-end corridors in existing facilities cannot be longer than 50’ and in new facilities the dead-end corridors cannot be longer than 20’ unless they are fully sprinklered • Decorations, coverings and other items should not be stuck to a door with a fire rating of forty-five (45) minutes or more » Informational signs are the exception as long as they are applied with an appropriate adhesive • Emergency powered lighting for existing construction is provided if the building is: » Three (3) or more stories high


» Filled with one hundred (100) or more occupants in the stories above or below the level of exit discharge » Filled with one thousand (1,000) or more total occupants • Emergency powered lighting for existing construction is provided if the building is: » Three (3) or more stories high » Filled with one hundred (100) or more occupants in the stories above or below the level of exit discharge » Filled with three-hundred (300) or more total occupants • Exits and exit access corridors for interior wall and ceiling finishes must be Class A or B » Everywhere else should be Class A, B or C • Exit’s travel distance must not be more than 200’ and can increase to 300’ if the space is fully sprinklered


• Fire alarm systems are needed for existing construction if the building is: » Three (3) or more stories high » Filled with one hundred (100) or more occupants above or below exit discharge level » Filled with one thousand (1,000) or more occupants • Fire alarm systems are needed for new construction if the building is: » Three (3) or more stories high » Filled with fifty (50) or more occupants above or below exit discharge level » Filled with three hundred (300) or more occupants •

If not greater than one (1) level below the street floor, interior open stairways and ramps are able to be part of the egress system

• Means of egress while occupied must be consistently illuminated by Emergency Powered Lighting




• Pipes, cables, conduits, bus ducts, wire, air ducts or pneumatic tubes passing through the floor or walls must be protected with approved fire-rated material » Polyurethane expanding foam that has not been approved is not an acceptable fire-rated material here • Protection of vertical openings » Opening below street level that has storage or communicates with another occupancy » New construction - enclosure services four (4) or more floors - 2 hour fire rating » New construction - enclosure services three (3) or more floors » Existing construction - 1/2 hour fire rating • Separation occurs between buildings and parking structures by a two (2) hour or more fire barrier


• Sprinklers must be not damaged; free of corrosion, paint and foreign materials; and have required escutcheon plates installed • Unless noted compliant, latches or locks that open with a tool or key are not permitted on doors in a means of egress » Compliant latch/lock systems include a delayed egress-locking system or an access-controlled egress door assembly *Note: TJC’s recommendation to create a BMP is not mandatory but just a suggestion



Have questions? Contact JPT Architects and MEP Engineers

Johnstown Office - 244 Walnut Street, Johnstown, PA 15901 - 814.536.5321 Hollidaysburg Office - 215 Allegheny Street, Suite 101, Hollidaysburg, PA 16648 - 814.695.1406 State College Office - 204 East Calder Way, Suite 305, State College, PA 16801 - 814.234.9470 www.JPTarchs.com