High-pressure cylinders
for maximum operating safety and flexibility
General Description The fire safety philosophy behind Fire Eater A/S fire extinguishing systems is based on three basic principles:
ffProtecting LIFE ffProtecting ASSETS ff Protecting ENVIRONMENT All of these are fully met by Fire Eater high-pressure cylinders.
Great flexibility means substantial savings Fire Eater cylinders are under a pressure of 300 bar. The high gas compression ratio means fewer cylinders and valves, resulting in cost and space savings. The cylinders may be placed either vertically or horizontally, maximising flexibility for the design of your premises and the installation of the cylinders.
Safe transport and operation High pressures mean rigorous safety requirements – and maximum safety is top priority for the Fire Eater team developing these cylinders. For greater ease of handling, the cylinders are equipped with standard threaded valves. For safety reasons, the cylinders feature valve caps. The cylinders’ valves have been impact tested, so they will not break if knocked over without the valve cap in place. All valves are fitted with a rupture seal to relieve the cylinder pressure in the event of exposure to intense heat or fire. Fire Eater cylinders are the only fire extinguishers with both cylinder and valves that are pi-marked and TPED approved. That means there is no restriction on transportation in the filled state. Type
Capacity
Diameter
Height
Weight
Volume coverage
[L/bar]
[m3]
[mm]
[mm]
when full
MDC 38.5
[Kg]
[m3]
2
5/200
1.1
140
465
11
10/200
2.1
140
815
18
4
20/200
4.2
204
815
38
8.5
30/300
8.7
229
970
60
18
50/200
10.5
229
1480
67
21
50/300
14.6
229
1520
85
30
80/200
16.8
267
1710
110
34
80/300
23.3
267
1780
140
48
140/200
29.4
360
1745
260
59.5
140/300
40.8
360
1745
260
84
General description INERGEN® for high-pressure equipment is supplied in stand-
ard pressurised cylinders in a range of different sizes
More information See reverse side for technical details of these high-pressure cylinders. To find out more about high-pressure cylinders or automatic extinguishing equipment in general, contact the Fire Eater sales department, or visit www.fire-eater.com.
Fire Eater A/S – Vølundsvej 17 – DK-3400 Hillerød – Tel: +45 7022 2769 Fax: +45 7023 2769 – info@fire-eater.com – www.fire-eater.com – CVR: 59538713 INDATBD_INERGEN Cylinders_UK.rev.4