December 7, 2021
TO: Plan Check and Inspection Unit Development Services Section Fire Prevention and Public Safety Bureau
FROM: Dwayne Laurent, Fire Captain II Fire Development Services
SUBJECT: ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER- EXEMPTIONS TO THE MINIMUM DIMENSIONS
It has been brought to our attention that new elevator cars intended to be used for emergency medical service are being manufactured to dimensions smaller than the minimum code required size set forth in the California Building Code (CBC) 3002.4.3a.
CBC 3002.4.3a states:
3002.4.3a Elevator entrance openings and car size. The elevator car shall be of such a size and arrangement to accommodate a 24-inch by 84-inch (610 mm by 2134 mm) ambulance gurney or stretcher with not less than 5-inch (127 mm) radius corners, in the horizontal, open position, shall be provided with a minimum clear distance between walls or between walls and door excluding return panels not less than 80 inches by 54 inches (2032 mm by 1372 mm), and a minimum distance from wall to return panel not less than 51 inches (1295 mm) with a 42-inch (1067 mm) side slide door.
Exception: The elevator car dimensions and/or the clear entrance opening dimensions may be altered where it can be demonstrated to the local jurisdictional authority’s satisfaction that the proposed configuration will handle the designated gurney or stretcher with equivalent ease. Documentation from the local authority shall be provided to the Occupational Safety and Health Standards Board.
The exception in CBC 3002.4.3a grants the local jurisdiction, in this case the Los Angeles Fire Department (LAFD), the authority to accept elevator car dimensions demonstrated by an elevator manufacturer to accommodate an ambulance gurney with surface extenders.
In an effort to assist elevator manufacturers, architects, engineers and developers in proposing alternate elevator car sizes to accommodate ambulance stretchers, the LAFD has established the following procedures for approval of a smaller medical emergency service elevator.
Page 2
December 7, 2021
1. The elevator manufacturer shall submit a request in writing to the LAFD Development Services Section (FDS) for approval at 201 N Figueroa St Suite 210 Los Angeles, CA 90012. Approval shall be in writing by the FDS Field Inspection Unit Commander. Said approval can be revoked at any time without prior notice.
2. Plans shall be prepared by the elevator manufacturer that show graphically that an ambulance stretcher with minimum dimensions of 24-inches by 84-inches (610 mm by 2134 mm) with not less than 5-inch (127 mm) radius corners and surface extenders with a dimension of 27-inches by 38-inches (605.6 mm x 965.2 mm) can be accommodated with similar ease as the code prescribed elevator car size See figure 1 for gurney specifications.
3. Plans shall also show that space will be provided for a minimum of two (2) LAFD emergency operations members in addition to the ambulance stretcher. Each LAFD members shall be shown graphically as a 21-inch (533.4 mm) diameter circle.
4. The minimum dimensions for the elevator car shall not be less than any other code required minimum, including but not limited to, those dimensions required by the American with Disabilities Act (ADA).
5. Approval shall be presented to the Los Angeles Department of Building and Safety (LADBS) for filing of approval to the Occupational Safety and Health Standards Board.
Dwayne LaurentPage 3
December 7, 2021
The following elevator cars have been reviewed and granted approval by FDS. The list will be amended as additional elevators are approved.
Delta - 2800, 88” X 52” Front Opening
Delta - 2800, 88” x 52” Front and Rear Opening
Delta - 2800, 58” x 80.5” Front Opening
Delta - 2800, 58” x 80.5” Rear Opening
Delta - 3500, 80” x 64” Front Opening
Delta - 3500, 80” x 64” Front and Rear Opening
Diamond Elevator - 2800, 88" x 51.5" Front and Rear Opening
Page 4
December 7, 2021
TRE 3500 88 X 52 Front opening
Modular Elevator Manufacturing - HOLE-LESS HW-2-3500G
OTIS – G2S, 3500# (6’-5 9/16” x 5’-5 9/16”) Side Slide
OTIS – G2S, 3500# (6’-6 3/4” x 5’-6 1/8”) Side Slide OTIS – Hydrofit,
9'-6"INSIDEPITDIMENSION
9'-41 4"OUTSIDEHOISTWAYDIMENSION(SHEATHING)
8'-6"INSIDEHOISTWAYDIMENSION
6'-101 2"PLATFORMDIMENSION
6'-8"INSIDECLEARDIMENSION
Ø21"
CARTOP REFUGESPACE 24"X47"
24"x84" GURNEY Ø21"
3500CAPACITY LEFTHANDED
PITSTOPSW. LIGHTSW. PITLIGHT PITLADDER HALLSTATION
TELESCOPICJACKSWILLNOT BEUSEDFORTHISMODELELEVATOR
HOLE-LESS HW-2-3500G
P.O.BOX3998 CHATSWORTH,CA.91313
3'-6"DOOROPENING
COMPLIANCE'S THISEQUIPMENTISDESIGNEDACCORDINGTO THEREQUIREMENTSOFANSIA17.1SAFETY CODEFORELEVATORS,ANDALLLOCALAND STATECODES.THEFEATURESFORTHEBENEFIT OFTHEHANDICAPPEDAREPROVIDEDAS REQUIREDBYTHE"AMERICANSWITH DISABILITIESACT".
PROJECTNUMBER:
DATE: FEB01,2022
SHEETNAME:
ELEVATOR
LAYOUT
PROJECTNAME:THISINFORMATIONISCONFIDENTIALAND REMAINSTHEPROPERTYOFMODULAR ELEVATORMANUFACTURING,INC.ITSUSE REPRODUCTIONOFDESSEMINATIONWITHOUT THEEXPRESSPERMISSIONOFMODULAR ELEVATORMANUFACTURING,INC.ISSTRICTLY PROHIBITED.
DRAWNBY: JF
SHEETNO:
818-509-8228 WWW.MODULARELEVATOR.NET HW-CL-35G
Surface extenders
24" Min Dia. for LAFD Personnel
Surface extenders
*LEFTHANDANDRIGHT HANDDOOR
CONFIGURATIONSARE SYMMETRIC
Schindler33003000#GP
FRONT/REAROPENING 2SSOLH/LHDOOR*
FRONTOPENING 2SSOLHDOOR*
Thisinstallationconformswith Section3002.4oftheCalifornia BuildingCodeasseeninthe diagram,includingthelargergurney sizerequiredtherein(seeabovefor dimensions).