Steinel Catalogue 2015

Page 1

STEINEL Lighting Controls Setting the Standard in Presence Detection

Presence Detectors, Occupancy Sensors, Power Packs, Wall Switches, High Bay Controls, Photocell Control, Fixture Integrated Controls & Outdoor Sensors


Control Pro Series High definition presence detection The Control Pro Series includes passive infrared, ultrasonic or dual technologies to detect the presence of a person in a space. Line voltage or low voltage sensors for use with power packs and building automation systems. Control options of an independently programed HVAC control output with normally open or normally closed contacts. 1-10V manual dimming or auto photo control dimming choices and dim before disconnect feature. Selectable auto ON or manual ON functions with either momentary or maintained switch inputs. The “COM-Link” feature allows multiple sensors to communicate together to achieve expanded detection zones. The control set up functions can be programed at one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience.


IR Quattro COM1-24 Presence Detectors Project Name: Location: 64410

65300

65320

65330

IR Quattro COM1-24 Specifications Item No. Accessories

Voltage Load Rating Sensing Technology

The IR Quattro COM1-24 is a low voltage passive infrared presence detector setting a new standard in lighting control with minimal movement required for human presence detection. It features a single pyroelectric detector with a high performance lens system creating 1,760 switching zones. Operational choices of manual on or auto on with either momentary or maintained switch options. Included light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the sensors detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available time saving wireless remote commissioning set up tool and the user / occupant wireless remote provides addition convenience. The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

control output - 1 A @ 30 VAC/VDC passive infrared (PIR)

Light Level Setting

10 - 1000 lux / 1 - 100 fc

Coverage at 9 ft

Sensors

IP20 rated, 0°C to +40°C, 32°F to +104°F 2.5 - 8 m / 8 - 26 ft 360º square mechanically scalable detection zones presence: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) radially: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) tangentially: max. 7.1 x 7.1 m (50.41 sq.m. ) max. 23 x 23 ft (529.00 sq.ft.) single infrared pyroelectric detector

Lens Design

13 detection levels, 1760 switching zones

Dimensions

4.72 x 4.72 x 3.03 in, 120 x 120 x 77 mm (LxWxD)

Warranty

5 years

Key Features: • • • • • • • • • •

The typical application is for offices, conference rooms, classrooms and other indoor public building spaces.

1 - 100 ffc

18 - 24 VDC/VAC (30 mA)

control output 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile)

Environment

15 x 15 Ft Presence 23 x 23 Ft Tangential

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Time Delay Setting

Installation Height

Applications

1760 PIR Detection Zones

64410 IR Quattro COM1-24

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system PIR Presence Detection Mechanical reach setting Square coverage pattern with 1760 switching zones Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficient daylight is present Mounts to a 4” Square box, 4” Octagon box, Round 3.0 MudRing or directly to the ceiling with quick mount spring tabs “COM-Link” communication allows for up to 10 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

18-24 VDC/VAC

30 Sec - 30 Min

www.steinel.net


IR Quattro COM1-24 Presence Detectors Wiring

Settings

Mechanical Scalability

Coverage

2

1

Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 13 ft. Maximum mounting height up to 26 ft. One Gridline = 0.5 m / 1.5 ft 5 m (16 ft) 4 m (13 ft)

4

1 - Tangential - motion perpendicular to the sensor 7.1 x 7.1 m (23 x 23 ft)

3 m (9.5 ft) 2 m (6.5 ft)

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Sensor DIP switch settings

1 m (3 ft) 1 0 m (0 ft) 2,3 1 m (3 ft) 2 m (6.5 ft) 3 m (9.5 ft) 4 m (13 ft)

4

4

3

NOT USED

NOT USED

2 - Radial - motion either directly toward or away from the sensor 4.7 x 4.7 m (15 x 15 ft)

5 m (16 ft)

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON‘ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 4.7 x 4.7 m (15 x 15 ft)

Mounting

120

120 61

Ceiling 6

26

46

61

Load module

120

IR Quattro

Sensor Module

120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring www.steinel.net

(800) 852-4343

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

120

120

Ø

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01106-2


IR Quattro COM2-24 Presence Detectors Project Name: Location: 64420

65300

65320

65330

IR Quattro COM2-24 Item No. Accessories

Voltage Load Rating Sensing Technology

The IR Quattro COM2-24 is a low voltage passive infrared presence detector setting a new standard in lighting and HVAC control with minimal movement required for human presence detection. Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output (isolated normally open and normally closed dry contacts) are signaled in relation to only the presence of motion. It features a single pyroelectric detector with a high performance lens system creating 1,760 switching zones. Operational choices of manual on or auto on with either momentary or maintained switch options. Included light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the sensors detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications The typical application is for offices, schools and other indoor public building spaces.

1760 PIR Detection Zones

15 x 15 Ft Presence 23 x 23 Ft Tangential

1 - 100 ffc

Time Delay Setting

Light Level Setting Environment Installation Height Coverage at 9 ft

Sensors

64420 IR Quattro COM2-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (34 mA) control output - 1 A @ 30 VAC/VDC HVAC dry contacts - 1 A @ 30 VAC/VDC passive infrared (PIR) control output - 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) HVAC dry contacts: 0 sec. - 10 min. switch ‘ON’ delay 1 min. - 2 hrs. stay ‘ON’ time auto-HVAC mode 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F 2.5 - 8 m / 8 - 26 ft 360º square mechanically scalable detection zones presence: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) radially: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) tangentially: max. 7.1 x 7.1 m (50.41 sq.m. ) max. 23 x 23 ft (529.00 sq.ft.) single infrared pyroelectric detector

Lens Design

13 detection levels, 1760 switching zones

Dimensions

4.72 x 4.72 x 3.03 in, 120 x 120 x 77 mm (LxWxD)

Warranty

5 years

Key Features: • • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Independent ON and OFF time settings for the HVAC (NO/NC) PIR Presence Detection with Mechanical reach setting Square coverage pattern with 1760 switching zones Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off with sufficient daylight “COM-Link communication allows for up to 10 sensors to be grouped together Auto-HVAC mode reduces presence detection sensitivity and requires additional detection verification before signaling the HVAC output.

18 - 24 VDC/VAC & HVAC

30 Sec - 30 Min

www.steinel.net


IR Quattro COM2-24 Presence Detectors Wiring

Coverage

Settings 2

1

3

Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 13 ft. Maximum mounting height up to 26 ft.

4

One Gridline = 0.5 m / 1.5 ft

Mechanical Scalability

5 m (16 ft)

1 - Light level setting 2 - Occupancy time delay setting 3 - HVAC stay-‘ON’ time 4 - HVAC switch-‘ON’ delay 5 - Reach setting 6 - Dip switch settings

4 m (13 ft)

4

3 m (9.5 ft) 2 m (6.5 ft) 1 m (3 ft) 1 0 m (0 ft) 2,3

3 m (9.5 ft) 4 m (13 ft)

4

6

NOT USED

5 m (16 ft)

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

NOT USED

2 - Radial - motion either directly toward or away from the sensor 4.7 x 4.7 m (15 x 15 ft)

1 m (3 ft) 2 m (6.5 ft)

5

1 - Tangential - motion perpendicular to the sensor 7.1 x 7.1 m (23 x 23 ft)

Mounting

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 4.7 x 4.7 m (15 x 15 ft)

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

Ceiling 120 61

61 26

120

120

Ø

46

120

6

120

Load module

IR Quattro 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

Sensor Module

M-01107-2


IR Quattro DIM-24 Presence Detectors Project Name: Location: 64430

65300

65320

65330

IR Quattro DIM-24 Specifications Item No. Accessories

The IR Quattro DIM-24 is a low voltage passive infrared presence detector setting a new standard in lighting and 1-10 volt dimming control with minimal movement required for human presence detection. Provides for superior presence detection, energy savings and occupant convenience. Lighting is controlled in relation to the presence of motion, the user selected dim level by remote or momentary switch and ambient light levels. As soon as occupancy is detected, the sensor goes to either the last selected electric light dim level (constant-lighting controller ‘OFF’) or adjusts to the last selected electric light + daylight brightness level (constant-lighting controller ‘ON’). The “force off” light level feature will turn lights off when sufficient daylight is present for additional energy savings. When no movement is detected and the occupancy time setting has elapsed, the sensor dims light levels back to basic brightness (1.6 volts), after the Stay ‘ON’ time DIM before ‘OFF’ delay has expired the light turns off. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the sensors detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning (HVAC) and lighting loads (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications The typical application is for offices, schools and other indoor public building spaces.

1760 PIR Detection Zones

15 x 15 Ft F Presence P 23 x 23 Ft Tangential

1 - 100 fc f

Voltage Load Rating

Sensing Technology Time Delay Setting Light Level Setting Environment Installation Height Coverage at 9 ft

Sensors Lens Design Dimensions Warranty Certifications

64430 IR Quattro DIM-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC 46mA control output (blue) 1 A @ 30 VAC/VDC 1 - 10 volt dimming output (purple & gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts) passive infrared (PIR) 30 sec. to 30 min., pulse mode (approx. 2 sec.) IQ mode (automatic adjustment to the usage profile) 10 - 1000 lux / 1 - 100 fc IP20 rated, 0°F to +40°F, 32°C to +104°C 2.5 - 8 m / 8 - 26 ft 360º square mechanically scalable detection zones presence: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) radially: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) tangentially: max. 7.1 x 7.1 m (50.41 sq.m. ) max. 23 x 23 ft (529.00 sq.ft.) single infrared pyroelectric detector 13 detection levels, 1760 switching zones 4.72 x 4.72 x 3.03 in, 120 x 120 x 77 mm (LxWxD) 5 years C-UL-US Listed, RoHS Compliant UL 2043 Plenum rated, CA Energy Code Compliant

Key Features: • • • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system 1-10 volt dimming Stay ‘ON’ time DIM before ‘OFF’ Constant light level DIM control option PIR Presence Detection Mechanical reach setting Square coverage pattern with 1760 switching zones Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching “COM-Link” communication allows for up to 10 sensors to be grouped together

18 - 24 VDC/VAC 1 - 10 Volt Dimming

30 Sec - 30 Min

www.steinel.net


IR Quattro DIM-24 Presence Detectors Wiring

Settings 1

2

Coverage

Mechanical Scalability

3

Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 13 ft. Maximum mounting height up to 26 ft. One Gridline = 0.5 m / 1.5 ft 5 m (16 ft)

1 - Light level setting 2 - Occupancy time delay setting 3 - Stay ‘ON’ time DIM before ‘OFF’ 4 - Reach setting 1 5 - Sensor DIP switch settings

4 m (13 ft)

4

1 - Tangential - motion perpendicular to the sensor 7.1 x 7.1 m (23 x 23 ft)

3 m (9.5 ft) 2 m (6.5 ft) 1 m (3 ft) 0 m (0 ft)

2,3

2 - Radial - motion either directly toward or away from the sensor 4.7 x 4.7 m (15 x 15 ft)

1 m (3 ft) 2 m (6.5 ft) 3 m (9.5 ft) 4 m (13 ft)

4

5

4

5 m (16 ft)

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Constant light level DIM control option

Ø

Mounting

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

Ceiling

120 61 26

120

120 61

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 4.7 x 4.7 m (15 x 15 ft)

6

120

46

120

Load module

IR Quattro 120

Sensor Module Mounts to a 4” Square box, 4” Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01108-2


IR Quattro COM1-WR Presence Detector Project Name: Location: 64440

65300

65320

65330

IR Quattro COM1-WR Item No.

64440 IR Quattro COM1-WR

Accessories

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage Load Rating Sensing Technology

The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

Light Level Setting

10 – 1000 lux / 1 – 100 fc

Coverage at 9 ft

Sensors

2.5 - 8 m / 8 - 26 ft 360º square mechanically scalable detection zones presence: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) radially: max. 4.7 x 4.7 m (22.09 sq.m.) max. 15 x 15 ft (225 sq.ft.) tangentially: max. 7.1 x 7.1 m (50.41 sq.m. ) max. 23 x 23 ft (529.00 sq.ft.) single infrared pyroelectric detector 13 detection levels, 1760 switching zones

Dimensions

4.72 x 4.72 x 3.03 in, 120 x 120 x 77 mm (LxWxD) 5 years

Key Features: • • • • • • • • • • •

The typical application is for offices, schools and other indoor public building spaces.

1 - 100 fc f

IP20 rated, 0° C to +40° C / 32° F to 104° F

Lens Design

Warranty

15 x 15 Ft Presence 23 x 23 Ft Tangential

passive infrared (PIR) 30 sec. – 30 min., pulse mode (approx. 2 sec.) IQ mode (automatic adjustment to the usage profile)

Installation Height

Applications

1760 PIR Detection Zones

120 VAC: 0-800 watt electronic ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt electronic ballast, 1/4hp

Time Delay Setting

Environment

The IR Quattro COM1-WR is a line voltage passive infrared presence detector setting a new standard in lighting control with minimal movement required for human presence detection. Features a single pyroelectric detector with a high performance lens system creating 1,760 switching zones. Operational choices of manual on or auto on with either momentary or maintained switch options. Included light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the sensors detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box or Round 3.0 Mud-Ring. The available time saving wireless remote commissioning set up tool and the user /occupant wireless remote provides addition convenience.

120/230/277 VAC, 50/60 Hz

Line voltage lighting control (120/230/277 VAC, 50/60 Hz) PIR Presence Detection 1760 switching zones Mechanical reach setting Square coverage pattern Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficiant daylight is present Mounts to a 4” Square box, 4” Octagon box or Round 3.0 Mud-Ring “COM-Link” communication allows for up to 10 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy habits

120 / 230 / 277 V

30 Sec - 30 Min

www.steinel.net


IR Quattro COM1-WR Presence Detector Wiring Master / Master - Occupancy is communicated to each sensor as group control but light level is independently controlled. Master / Slave - Occupancy is communicated to each sensor as group control but only light level of the master is used.

Settings Mechanical Scalability

2

1

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Dip switch settings

4

3

NOT USED

Mounting

NOT USED

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

Coverage Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 13 ft. Maximum mounting height up to 26 ft. One Gridline = 0.5 m / 1.5 ft

120

120

5 m (16 ft) 4 m (13 ft)

4

1 - Tangential - motion perpendicular to the sensor 7.1 x 7.1 m (23 x 23 ft)

3 m (9.5 ft) 2 m (6.5 ft)

120

120 61

1 m (3 ft) 1 0 m (0 ft) 2,3

26

46

61

1 m (3 ft)

6

IR Quattro

2 - Radial - motion either directly toward or away from the sensor 4.7 x 4.7 m (15 x 15 ft)

2 m (6.5 ft) 3 m (9.5 ft)

120

4 m (13 ft)

120

4

5 m (16 ft)

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 4.7 x 4.7 m (15 x 15 ft)

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01105-2


IR Quattro HD COM1-24 Presence Detectors Project Name: Location: 64460

65300

65320

65330

IR Quattro HD COM1-24 Specifications Item No. Accessories

Voltage Load Rating Sensing Technology

The IR Quattro HD COM1-24 is a low voltage, high definition, passive infrared presence detector setting a new standard in lighting control with minimal movement required for human presence detection. Features four pyroelectric detectors with a high performance lens system that creates a new global standard in detection with 4,800 switching zones. Operational choices of manual on or auto on with either momentary or maintained switch options. Included light level feature provides the option to turn lights off when sufficient daylight is present for additional energy saings. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the detection reach without compromising sensitivity providing precise presence detection in the desired detection zone. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available time saving wireless remote commissioning set up tool and the user /occupant wireless remote provides addition convenience. The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications

4800 PIR Detection Zones

26 x 26 Ft Presence 65 x 65 Ft Tangential

1 - 100 ffc

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18 - 24 VDC/VAC (32 mA) control output - 1 A @ 30 VAC/VDC passive infrared (PIR)

Time Delay Setting

control output 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile)

Light Level Setting

10 - 1000 lux / 1 - 100 fc

Environment Installation Height Coverage at 9 ft

Sensors

IP20 rated, 0°C to +40°C, 32°F to +104°F 2.5 - 10 m / 8 - 32 ft 360º square mechanically scalable detection zones presence: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) radially: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) tangentially: max. 20 x 20 m (400.0 sq.m. ) max. 65.5 x 65.5 ft (4,290.25 sq.ft.) 4 infrared pyroelectric detectors

Lens Design

13 detection levels, 4800 switching zones

Dimensions

4.72 x 4.72 x 2.83 in, 120 x 120 x 72 mm (LxWxD)

Warranty Certifications

5 years C-UL-US Listed, RoHS compliant, UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • • • • •

The typical application is for offices, conference rooms, classrooms and other indoor public building spaces.

64460 IR Quattro HD COM1-24

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Extremely High Definition PIR Presence Detection Mechanical reach setting Square coverage pattern with 4800 switching zones Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficient daylight is present Mounts to a 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs “COM-Link” communication allows for up to 10 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

18-24 VDC/VAC

30 sec - 30 min

www.steinel.net


IR Quattro HD COM1-24 Presence Detectors Wiring

Settings

Mechanical Scalability

Coverage

2

1

Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 26 ft. Maximum mounting height up to 32 ft. One Gridline = 1 m / 3 ft 0° -20°

-10°

10°

20°

-30°

14 m (46 ft)

30°

-40° -50°

10 m (33 ft)

50°

-60°

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Sensor DIP switch settings

12 m (39 ft)

40°

8 m (26 ft)

60° 70°

-70°

6 m (20 ft) 4 m (13 ft)

-80°

80°

-90°

90°

-100°

100°

1 2,3

2 m (7 ft) 0 m (0 ft)

110° 120°

-130°

4

3

10 m (33 ft)

140°

-150°

12 m (39 ft)

150° -160°

-170°

170°

6 m (20 ft) 8 m (26 ft)

130°

-140°

14 m (46 ft)

160°

180°

NOT USED

NOT USED

2 - Radial - motion either directly toward or away from the sensor 8 x 8 m (26.25 x 26.25 ft)

2 m (7 ft) 4 m (13 ft)

-110° -120°

1 - Tangential - motion perpendicular to the sensor 20 x 20 m (65.6 x 65.6 ft)

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not Used

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 8 x 8 m (26.25 x 26.25 ft)

Ø

Mounting

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

120

120

Ceiling

120 61

26

61

Load module

120

41

6

120

IR Quattro HD Sensor Module

120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01120-2


IR Quattro HD COM2-24 Presence Detectors Project Name: Location: 64470

65300

65320 653 0

65330

IR Quattro HD COM2-24 Item No. Accessories

Voltage Load Rating

The IR Quattro HD COM2-24 is a low voltage, high definition, passive infrared presence detector setting a new standard in lighting and HVAC control with minimal movement required for human presence detection. Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output (isolated normally open and normally closed dry contacts) are signaled in relation to only the presence of motion. Features four pyroelectric detectors with a high performance lens system that creates a new global standard in detection with 4,800 switching zones. Operational choices of manual on or auto on with either momentary or maintained switch options. Included light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the sensors detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications The typical application is for offices, schools and other indoor public building spaces.

4800 PIR Detection Zones

26 x 26 Ft Presence 65 x 65 Ft Tangential

1 - 100 ffc

Sensing Technology Time Delay Setting

Light Level Setting Environment Installation Height Coverage at 9 ft

Sensors

64470 IR Quattro HD COM2-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (34 mA) control output - 1 A @ 30 VAC/VDC HVAC dry contacts - 1 A @ 30 VAC/VDC passive infrared (PIR) control output - 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) HVAC dry contacts: 0 sec. - 10 min. switch ‘ON’ delay 1 min. - 2 hrs. stay ‘ON’ time auto-HVAC mode 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F 2.5 - 10 m / 8 - 32 ft 360º square mechanically scalable detection zones presence: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) radially: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) tangentially: max. 20 x 20 m (400.0 sq.m. ) max. 65.5 x 65.5 ft (4,290.25 sq.ft.) 4 infrared pyroelectric detectors

Lens Design

13 detection levels, 4800 switching zones

Dimensions

4.72 x 4.72 x 2.83 in, 120 x 120 x 72 mm (LxWxD)

Warranty

5 years

Key Features: • • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Independent ON and OFF time settings for the HVAC (NO/NC) High Definition Detection with adjustable reach setting Square coverage pattern with 4800 switching zones Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’&’OFF’ manual switching Light level feature turns lights off with sufficient daylight “COM-Link” allows up to 10 sensors to be grouped together Auto-HVAC mode reduces presence detection sensitivity and requires additional detection verification before signaling the HVAC output

18 - 24 VDC/VAC & HVAC

30 sec - 30 min

www.steinel.net


IR Quattro HD COM2-24 Presence Detectors Wiring

Settings

Mechanical Scalability 2

1

3

Coverage Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 26 ft. Maximum mounting height up to 32 ft.

4

One Gridline = 1 m / 3 ft 0° -20°

-10°

10°

20°

-30°

14 m (46 ft)

30°

-40° -50°

8 m (26 ft)

60° 70°

-70°

6 m (20 ft) 4 m (13 ft)

-80°

80°

-90°

90°

-100°

100°

1 2,3

2 m (7 ft) 0 m (0 ft)

110° 120°

-130°

6

10 m (33 ft)

140°

-150°

12 m (39 ft)

150° -160°

-170°

170°

6 m (20 ft) 8 m (26 ft)

130°

-140°

14 m (46 ft)

160°

180° NOT USED

NOT USED

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

120

Mounting

2 - Radial - motion either directly toward or away from the sensor 8 x 8 m (26.25 x 26.25 ft)

2 m (7 ft) 4 m (13 ft)

-110° -120°

5

10 m (33 ft)

50°

-60°

1 - Light level setting 2 - Occupancy time delay setting 3 - HVAC stay-‘ON’ time 4 - HVAC switch-‘ON’ delay 5 - Reach setting 6 - Dip switch settings

12 m (39 ft)

40°

1 - Tangential - motion perpendicular to the sensor 20 x 20 m (65.6 x 65.6 ft)

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 8 x 8 m (26.25 x 26.25 ft)

Ø

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

120

Ceiling

120 61

61 26

41

120

Load module

120

6

IR Quattro HD

Sensor Module

120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01121-2


IR Quattro HD DIM-24 Presence Detectors Project Name: Location: 64480

65300

65320

65330

IR Quattro HD DIM-24 Specifications

The IR Quattro HD DIM-24 is a low voltage, high definitio definition, passive infrared presence detector that is setting a new standard in lighting control. Featuring 1-10 volt dimming coupled with four pyroelectric detectors and a high performance lense system that creates 4,800 presence detection switching zones. Provides superior presence detection, energy savings and occupant convenience. Lighting is controlled in relation to the presence of motion, the user selected dim level by remote or momentary switch and ambient light levels. As soon as occupancy is detected, the sensor goes to either the last selected electric light dim level (constant-lighting controller ‘OFF’) or adjusts to the last selected electric light + daylight brightness level (constant-lighting controller ‘ON’). The “force off” light level feature will turn lights off when sufficient daylight is present for additional energy savings. When no movement is detected and the occupancy time setting has elapsed, the sensor dims light levels back to basic brightness (1.6 volts), after the Stay ‘ON’ time DIM before ‘OFF’ delay has expired the light turns off. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the sensors detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning (HVAC) and lighting loads (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications The typical application is for offices, schools and other indoor public building spaces.

4800 PIR Detection Zones

26 x 26 Ft F Presence P 65 x 65 Ft Tangential

1 - 100 ffc

Item No.

64480 IR Quattro HD DIM-24

Accessories

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage Load Rating

Sensing Technology Time Delay Setting Light Level Setting Environment Installation Height Coverage at 9 ft

Sensors Lens Design Dimensions Warranty Certifications

18-24 VDC/VAC 46mA control output (blue) 1 A @ 30 VAC/VDC 1 - 10 volt dimming output (purple & gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts) passive infrared (PIR) 30 sec. to 30 min., pulse mode (approx. 2 sec.), IQ mode (automatic adjustment to the usage profile) 10 - 1000 lux / 1 - 100 fc IP20 rated, 0°F to +40°F, 32°C to +104°C 2.5 - 10 m / 8 - 32 ft 360º square mechanically scalable detection zones presence: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) radially: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) tangentially: max. 20 x 20 m (400.0 sq.m. ) max. 65.5 x 65.5 ft (4,290.25 sq.ft.) 4 infrared pyroelectric detectors 13 detection levels, 4800 switching zones 4.72 x 4.72 x 2.83 in, 120 x 120 x 72 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant UL 2043 Plenum rated, CA Energy Code compliant

Key Features: • • • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system 1-10 volt dimming Stay ‘ON’ time DIM before ‘OFF’ Constant light level DIM control option 4 pyros (Infrared Pyroelectric Detectors) Mechanical reach setting Square coverage pattern with 4800 switching zones Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching “COM-Link” communication allows for up to 10 sensors to be grouped together

18 - 24 VDC/VAC 1 - 10 Volt Dimming

30 sec - 30 min

www.steinel.net


IR Quattro HD DIM-24 Presence Detectors Wiring

Settings 1

2

Coverage

Mechanical Scalability

3

Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 26 ft. Maximum mounting height up to 32 ft. One Gridline = 1 m / 3 ft 1 - Tangential - motion 0° -10° 10° perpendicular to the sensor -20° 20° 14 m (46 ft) -30° 30° 20 x 20 m (65.6 x 65.6 ft) 12 m (39 ft) -40° 40° -50°

1 - Light level setting 2 - Occupancy time delay setting 3 - Stay ‘ON’ time DIM before ‘OFF’ 2,3 4 - Reach setting 5 - Sensor DIP switch settings

-70°

6 m (20 ft)

70°

4 m (13 ft) -80°

80°

-90°

90°

-100°

100°

2 m (7 ft) 0 m (0 ft)

-110°

110°

6 m (20 ft)

120°

140°

-150°

12 m (39 ft)

150° -160°

-170°

170°

8 m (26 ft) 10 m (33 ft)

130°

-140°

14 m (46 ft)

160°

2 - Radial - motion either directly toward or away from the sensor 8 x 8 m (26.25 x 26.25 ft)

2 m (7 ft) 4 m (13 ft)

-130°

5

8 m (26 ft)

60°

-120°

4

10 m (33 ft)

50°

-60°

180°

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Constant light level DIM control option

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 8 x 8 m (26.25 x 26.25 ft)

Ø

Mounting

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

120

120

Ceiling

120 61

61 26

120

120

41

6

Load module

IR Quattro HD Sensor Module

120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01122-2


IR Quattro HD COM1-WR Presence Detector Project Name: Location: 64490

65300

65320

65330

IR Quattro HD COM1-WR Item No. Accessories

Voltage Load Rating Sensing Technology Time Delay Setting

The IR Quattro HD COM1-WR is a line voltage, high definition, passive infrared presence detector setting a new standard in lighting control with minimal movement required for human presence detection. Features four pyroelectric detectors with a high performance lens system that creates a new global standard in detection with 4,800 switching zones. Operational choices of manual on or auto on with either momentary or maintained switch options. Included light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The innovative mechanical reach setting enables the designer with a precise method of controlling lighting zones by means of optimizing the detection reach without compromising sensitivity providing true precise presence detection in the desired detection zone. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box or Round 3.0 Mud-Ring. The available time saving wireless remote commissioning set up tool and the user /occupant wireless remote provides addition convenience. The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications

Environment Installation Height Coverage at 9 ft

Sensors Lens Design

26 x 26 Ft Presence 65 x 65 Ft Tangential

1 - 100 fc f

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 120/230/277 VAC, 50/60 Hz 120 VAC: 0-800 watt electronic ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt electronic ballast, 1/4hp passive infrared (PIR) 30 sec. – 30 min., pulse mode (approx. 2 sec.), IQ mode (automatic adjustment to the usage profile) 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F 2.5 - 10 m / 8 - 32 ft 360º square mechanically scalable detection zones presence:max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) radially: max. 7.9 x 7.9 m (62.41 sq.m.) max. 25.5 x 25.5 ft (650.25 sq.ft.) tangentially: max. 20 x 20 m (400.0 sq.m. ) max. 65.5 x 65.5 ft (4,290.25 sq.ft.) 4 infrared pyroelectric detectors 13 detection levels, 4800 switching zones

Key Features: • • • • • • • • • • • • •

The typical application is for offices, schools and other indoor public building spaces.

4800 PIR Detection Zones

Light Level Setting

64490 IR Quattro HD COM1-WR

Line voltage lighting control (120/230/277 VAC, 50/60 Hz) Extremely High Definition PIR Presence Detection 4 pyros (Infrared Pyroelectric Detectors) 4800 switching zones Mechanical reach setting Square coverage pattern Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficiant daylight is present Mounts to a 4” Square box, 4” Octagon box or Round 3.0 Mud-Ring “COM-Link” communication allows for up to 10 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

120 / 230 / 277 V

30 Sec - 30 Min

www.steinel.net


IR Quattro HD COM1-WR Presence Detector Wiring Master / Master - Occupancy is communicated to each sensor as group control but light level is independently controlled. Master / Slave - Occupancy is communicated to each sensor as group control but only light level of the master is used.

Settings Mechanical Scalability

2

1

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Dip switch settings

4

3

NOT USED

Mounting

Coverage

NOT USED

Shown at 9 ft mounting height. Coverage will vary depending on mounting height. See pages 4 & 5 of the instruction manual for coverage at heights from 8 to 26 ft. Maximum mounting height up to 32 ft.

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

One Gridline = 1 m / 3 ft 0° -20°

-10°

10°

20°

-30°

14 m (46 ft)

30°

120

120

12 m (39 ft)

40°

-40°

10 m (33 ft)

50°

-50°

8 m (26 ft)

60°

-60°

70°

-70°

6 m (20 ft) 4 m (13 ft)

120

-80°

80°

-90°

90°

-100°

100°

1

120 61

2,3

26

41

61

IR Quattro HD

-110°

110° 120°

-130°

130°

-140°

140°

-150°

120

2 m (7 ft) 0 m (0 ft)

150° -160°

-170°

170° 180°

160°

2 - Radial - motion either directly toward or away from the sensor 8 x 8 m (26.25 x 26.25 ft)

2 m (7 ft) 4 m (13 ft)

-120°

1 - Tangential - motion perpendicular to the sensor 20 x 20 m (65.6 x 65.6 ft)

6 m (20 ft) 8 m (26 ft) 10 m (33 ft) 12 m (39 ft) 14 m (46 ft)

3 - Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection 8 x 8 m (26.25 x 26.25 ft)

120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01119-2


US Quattro COM1-24 Presence Detectors Project Name: Location: 64510

65300

65320

65330

US Quattro COM1-24 Specifications Item No.

64510 US Quattro COM1-24

Accessories

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage

18 - 24 VDC/VAC (30 mA) 50/60 Hz

Load Rating

control output - 1 A @ 30 VAC/VDC

Sensing Technology

The US Quattro COM1-24 is a low voltage (40 kHz) Ultrasonic Technology Presence Detector that utilizes STEINEL’s state of the art ultrasonic signal processing to providing superior stable volumetric omnidirectional detection. Ultrasonic is used for best practice in design and retrofit applications where the sensor will not have a clear line of site view of the occupants in the desired coverage area. Operational choices of manual on or auto on with either momentary or maintained switch options. The force off light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience.

Light Level Setting

10 - 1000 lux / 1 - 100 fc

Dimensions Warranty Certifications

IP20 rated, 0°C to +40°C, 32°F to +104°F presence: max. 6 x 6 m (36 sq.m.) max. 20 x 20 ft (400 sq.ft.) min. 2 x 2 (4 sq.m.) min. 6.5 x 6.5 ft (42.25 sq.ft.) radial / tangential: max. of up to 10 x 10 m (100 sq.m.) radial / tangential: max. of up to 32 x 32 ft (1000 sq.ft.) 4.72 x 4.72 x 2.68 in, 120 x 120 x 68 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant, UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: •

Applications

Typical applications are for large open areas with cubicals, work stations, conference rooms, bathrooms, storage areas with racking or applications requiring a volumetric pattern of detection.

1 - 100 ffc

control output 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile)

Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft)

• • • • • •

20 x 20 Ft Presence 32 x 32 Ft Max

Time Delay Setting

Environment

The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

Ultrasonic

ultrasonic (40 kHz)

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Omnidirectional ultrasonic (40 kHz) presence detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficient daylight is present Mounts to a 4” square box, 4” octagon box, round 3.0 mud-ring or directly to the ceiling with quick mount spring tabs IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

18-24 VDC/VAC

30 Sec - 30 Min

www.steinel.net


US Quattro COM1-24 Presence Detectors Wiring

Setting 1

2

3

Coverage Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft

m ft 6 19.7

4

5 16 4 13

Tangential - motion perpendicular to the sensor Radial - motion either directly toward or away from the sensor

3 9.5 2 6.5 1 3.3

Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection

0 0 1 3.3 2 6.5 3 9.5

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 / 6 / 7 / 8 - Not used

4 13 5 16

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Sensor DIP switch settings

6 19.7 6

5

4

3

2

1

0

1

2

3

4

5

6

Mounting 120

Ø

120

Ceiling

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120 61

26

61

6

120

36

120

Load module US Quattro

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01128-1


US Quattro COM2-24 Presence Detectors Project Name: Location: 64520

65300

65320

65330

US Quattro COM2-24 Item No. Accessories

Voltage Load Rating

The US Quattro COM2-24 is a low voltage (40 kHz) Ultrasonic Technology Presence Detector that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric omnidirectional detection for independent control of both lighting and HVAC. Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output (isolated normally open and normally closed dry contacts) are signaled in relation to only the presence of motion. The omnidirectional coverage pattern is ideal for those design and retrofit applications where the sensor will not have complete line of site view of the occupant and space. Operational choices of manual on or auto on with either momentary or maintained switch options. The included force off light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications The US Quattro COM2-24 is designed to be utilized in a multitude of applications and configurations: Large open areas where work stations or cubical furniture is used, bathrooms with stalls, storage areas with racking or any applications requiring a true omnidirectional volumetric pattern of detection and separate HVAC control output.

Ultrasonic

20 x 20 Ft Presence 32 x 32 Ft Max

1 - 100 ffc

Sensing Technology Time Delay Setting

Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft)

Sensors Dimensions Warranty Certifications

64520 US Quattro COM2-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 wire guard cage 18-24 VDC/VAC (34 mA) 50/60 Hz control output - 1 A @ 30 VAC/VDC HVAC dry contacts - 1 A @ 30 VAC/VDC ultrasonic (40 kHz) control output - 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) HVAC dry contacts: 0 sec. - 10 min. switch ‘ON’ delay 1 min. - 2 hrs. stay ‘ON’ time auto-HVAC mode 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F presence: max. 6 x 6 m (36 sq.m.) max. 20 x 20 ft (400 sq.ft.) min. 2 x 2 (4 sq.m.) min. 6.5 x 6.5 ft (42.25 sq.ft.) radial / tangential: max. of up to 10 x 10 m (100 sq.m.) radial / tangential: max. of up to 32 x 32 ft (1000 sq.ft.) 4 ultrasonic (40 kHz) transducers 4.72 x 4.72 x 2.68 in, 120 x 120 x 68 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Independent ON and OFF time settings for the HVAC (NO/NC) Omnidirectional ultrasonic (40 kHz) presence detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off with sufficient daylight IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Auto-HVAC mode reduces presence detection sensitivity and requires additional detection verification before signaling the HVAC output.

18 - 24 VDC/VAC & HVAC

30 Sec - 30 Min

www.steinel.net


US Quattro COM2-24 Presence Detectors Wiring

Coverage

Settings 1

2

3

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces.

5

4

One Gridline = 1 m / 3.3 ft

m ft 6 19.7 5 16

6

4 13

Tangential - motion perpendicular to the sensor Radial - motion either directly toward or away from the sensor

3 9.5 2 6.5 1 3.3

Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection

0 0 1 3.3 2 6.5

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Automatic mode (AUTO) Manual ON mode (MAN) / DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 / 6 / 7 / 8 - Not used

3 9.5 4 13

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - HVAC stay-‘ON’ time 5 - HVAC switch-‘ON’ delay 6 - Sensor DIP switch settings

5 16 6 19.7 6

5

4

3

2

1

0

1

2

3

4

5

6

Mounting 120

Ø

120

Ceiling

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120 61

26

61

6

120

36

120

Load module US Quattro

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01129-1


US Quattro DIM-24 Presence Detectors Project Name: Location: 64520

65300

65320

65330

US Quattro DIM-24 Specifications Item No. Accessories

Voltage Load Rating

The US Quattro DIM-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric omnidirectional detection and provides a 1-10 volt dimming output to control ballasts or driver lighting loads. Lighting is controlled in relation to the presence of motion, the user selected dim level by remote or momentary switch and ambient light levels. As soon as occupancy is detected, the sensor goes to either the last selected electric light dim level (constant-lighting controller ‘OFF’) or adjusts to the last selected electric light + daylight brightness level (constant-lighting controller ‘ON’). The “force off” light level feature will turn lights off when sufficient daylight is present for additional energy savings. When no movement is detected and the occupancy time setting has elapsed, the sensor dims light levels back to basic brightness (1.6 volts), after the Stay ‘ON’ time DIM before ‘OFF’ delay has expired the light turns off. The omnidirectional coverage pattern is ideal for those design and retrofit applications where the sensor will not have complete line of site view of the occupant and space. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning (HVAC) and lighting loads (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

Sensing Technology Time Delay Setting Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft)

Sensors Dimensions Warranty Certifications

64520 US Quattro DIM-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (46 mA) 50/60Hz control output (blue) 1 A @ 30 VAC/VDC 1 - 10 volt dimming output (purple & gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts) ultrasonic (40 kHz) 30 sec. to 30 min., pulse mode (approx. 2 sec.) IQ mode (automatic adjustment to the usage profile) 10 - 1000 lux / 1 - 100 fc IP20 rated, 0°F to +40°F, 32°C to +104°C presence: max. of 6 x 6 m (36 sq.m.) max. of 20 x 20 ft (400 sq.ft.) min. of 2 x 2 (4 sq.m.) min. of 6.5 x 6.5 ft (42.25 sq.ft.) radial / tangential: max. of up to 10 x 10 m (100 sq.m.) radial / tangential: max. of up to 32 x 32 ft (1000 sq.ft.) 4 ultrasonic (40 kHz) transducers 4.72 x 4.72 x 2.68 in, 120 x 120 x 68 mm (LxWxD) 5 years C-UL-US Listed, RoHS Compliant UL 2043 Plenum rated, CA Energy Code Compliant

Key Features: • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system 1-10 volt dimming Stay ‘ON’ time DIM before ‘OFF’ Constant light level DIM control option Ultrasonic (40 kHz) Presence Detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

Applications The typical application is for offices, schools and other indoor public building spaces.

Ultrasonic

20 x 20 Ft Presence 32 x 32 Ft Max

1 - 100 ffc

18 - 24 VDC/VAC 1 - 10 Volt Dimming

30 Sec - 30 Min

www.steinel.net


US Quattro DIM-24 Presence Detectors Wiring

Settings 1

2

3

4

Coverage Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft

5

Tangential - motion perpendicular to the sensor Radial - motion either directly toward or away from the sensor

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Constant light level DIM control option DIP 6 / 7 / 8 - Not used

Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Stay ‘ON’ time DIM before ‘OFF’ 5 - Sensor DIP switch settings

Mounting 120

Ø

120

Ceiling

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120 61

26

61

6

120

36

120

Load module US Quattro

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01130-1


US Hallway COM1-24 Occupancy Sensors Project Name: Location: 64550

65300

65320

65330

US Hallway COM1-24 Specifications Item No.

64550 US Hallway COM1-24

Accessories

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage

18 - 24 VDC/VAC (30 mA) 50/60 Hz

Load Rating

control output - 1 A @ 30 VAC/VDC

Sensing Technology Time Delay Setting

control output 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile)

Light Level Setting

10 - 1000 lux / 1 - 100 fc

Environment

The US Hallway COM1-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric bidirectional detection. The unique linear bidirectional coverage pattern is engineered specifically for hallways and applications requiring a true linear volumetric pattern of detection. This is an ideal hallway sensor for design and retrofit applications. Operational choices of manual on or auto on with either momentary or maintained switch options. Included force off light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

ultrasonic (40 kHz)

Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft) Dimensions Warranty Certifications

IP20 rated, 0°C to +40°C, 32°F to +104°F max. max. min. min.

2 x 20 m (40 sq.m.) 6.5 x 65 ft (422.5 sq.ft.) 2 x 5 m (10 sq.m.) 6.5 x 20 ft (130 sq.ft.)

4.72 x 4.72 x 2.87 in, 120 x 120 x 73 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant, UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Bidirectional ultrasonic (40 kHz) occupancy sensor Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficient daylight is present Mounts to a 4” square box, 4” octagon box, round 3.0 mudring or directly to the ceiling with quick mount spring tabs “COM-Link” communication allows for up to 10 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

Applications The typical best practice applications for the US Hallway sensors are: Hallways, tunnel walkways, sky walks, etc.

Ultrasonic

6.5 x 65 Ft Max

1 - 100 fc f

18-24 VDC/VAC

30 Sec - 30 Min

www.steinel.net


US Hallway COM1-24 Occupancy Sensors Wiring

Settings

2

1

3

Coverage Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft

m 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

4

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON‘ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Sensor DIP switch settings

Mounting 120

Ø

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120

Ceiling

ft 45.5 42.5 39 36 32.5 29.5 26 23 19.5 16.5 13 10 6.5 3.3 0 3.3 6.5 10 13 16.5 19.5 23 26 29.5 32.5 36 39 42.5 45.5

120 61

26

61

6

120

41

120

Load module US Hallway

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01142-1


US Hallway COM2-24 Occupancy Sensors Project Name: Location: 64560

65300

65320

65330

US Hallway COM2-24 Item No.

64560 US Hallway COM2-24

Accessories

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage Load Rating Sensing Technology

The US Hallway COM2-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric bidirectional detection for independent control of both lighting and HVAC. Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output (isolated normally open and normally closed dry contacts) are signaled in relation to only the presence of motion. The unique linear bidirectional coverage pattern is engineered specifically for hallways and applications requiring a true volumetric bidirectional linear pattern of detection. This is an ideal hallway sensor for design and retrofit applications. Operational choices of manual on or auto on with either momentary or maintained switch options. Included “force off” light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

Time Delay Setting

Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft) Dimensions Warranty Certifications

control output - 1 A @ 30 VAC/VDC HVAC dry contacts - 1 A @ 30 VAC/VDC ultrasonic (40 kHz) control output - 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) HVAC dry contacts: 0 sec. - 10 min. switch ‘ON’ delay 1 min. - 2 hrs. stay ‘ON’ time auto-HVAC mode 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F max. of 2 x 20 m (40 sq.m.) min. of 2 x 5 m (10 sq.m.) max. of 6.5 x 65 ft (422.5 sq.ft.) min. of 6.5 x 20 ft (130 sq.ft.) 4.72 x 4.72 x 2.87 in, 120 x 120 x 73 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • • • •

Applications

18-24 VDC/VAC (34 mA) 50/60 Hz

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Independent ON and OFF time settings for the HVAC (NO/NC) Ultrasonic (40 kHz) Occupancy Sensor Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off with sufficient daylight IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Auto-HVAC mode reduces presence detection sensitivity and requires additional detection verification before signaling the HVAC output.

The typical best practice applications for the US Hallway sensors are: Hallways, tunnel walkways, sky walks, etc.

Ultrasonic

6.5 x 65 Ft Max

1 - 100 ffc

18 - 24 VDC/VAC & HVAC

30 Sec - 30 Min

www.steinel.net


US Hallway COM2-24 Occupancy Sensors Wiring

Settings

Coverage 2

1

3

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces.

5

4

One Gridline = 1 m / 3.3 ft

m 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

6

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - HVAC stay-‘ON’ time 5 - HVAC switch-‘ON’ delay 6 - Sensor DIP switch settings

Mounting 120

Ø

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120

Ceiling

ft 46 42.7 39.4 36.1 32.8 29.5 26 23 19.7 16 13 9.5 6.5 3.3 0 3.3 6.5 9.5 13 16 19.7 23 26 29.5 32.8 36.1 39.4 42.7 46

120 61

26

61

6

120

41

120

Load module US Hallway

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01143-1


US Hallway DIM-24 Presence Detectors Project Name: Location: 64570

65300

65320

65330

US Hallway DIM-24 Specifications Item No. Accessories

Voltage

The US Hallway DIM-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric bidirectional detection and provides a 1-10 volt dimming output to control ballasts or driver lighting loads. Lighting is controlled in relation to the presence of motion, the user selected dim level by remote or momentary switch and ambient light levels. As soon as occupancy is detected, the sensor goes to either the last selected electric light dim level (constant-lighting controller ‘OFF’) or adjusts to the last selected electric light + daylight brightness level (constant-lighting controller ‘ON’). The “force off” light level feature will turn lights off when sufficient daylight is present for additional energy savings. When no movement is detected and the occupancy time setting has elapsed, the sensor dims light levels back to basic brightness (1.6 volts), after the Stay ‘ON’ time DIM before ‘OFF’ delay has expired the light turns off. The unique linear bidirectional coverage pattern is engineered specifically for hallways and applications requiring a true volumetric linear pattern of detection. This is an ideal hallway sensor for design and retrofit applications. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

Load Rating

Sensing Technology Time Delay Setting Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft) Dimensions Warranty Certifications

64570 US Hallway DIM-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (46 mA) 50/60 Hz control output (blue) 1 A @ 30 VAC/VDC 1 - 10 volt dimming output (purple & gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts) ultrasonic (40 kHz) 30 sec. to 30 min., pulse mode (approx. 2 sec.) IQ mode (automatic adjustment to the usage profile) 10 - 1000 lux / 1 - 100 fc IP20 rated, 0°F to +40°F, 32°C to +104°C max. of 2 x 20 m (40 sq.m.) min. of 2 x 5 m (10 sq.m.) max. of 6.5 x 65 ft (422.5 sq.ft.) min. of 6.5 x 20 ft (130 sq.ft.) 4.72 x 4.72 x 2.87 in, 120 x 120 x 73 mm (LxWxD) 5 years C-UL-US Listed, RoHS Compliant UL 2043 Plenum rated, CA Energy Code Compliant

Key Features: • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system 1-10 volt dimming Stay ‘ON’ time DIM before ‘OFF’ Constant light level DIM control option Ultrasonic (40 kHz) Presence Detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

Applications The typical best practice applications for the US Hallway sensors are: Hallways, tunnel walkways, sky walks, etc.

Ultrasonic

6.5 x 65 Ft Max

1 - 100 ffc

18 - 24 VDC/VAC 1 - 10 Volt Dimming

30 Sec - 30 Min

www.steinel.net


US Hallway DIM-24 Occupancy Sensors Wiring

Settings 1

2

3

Coverage

4

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft

m 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

5

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Constant light level DIM control option

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Stay ‘ON’ time DIM before ‘OFF’ 5 - Sensor DIP switch settings

Mounting 120

Ø

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120

Ceiling

ft 46 42.7 39.4 36.1 32.8 29.5 26 23 19.7 16 13 9.5 6.5 3.3 0 3.3 6.5 9.5 13 16 19.7 23 26 29.5 32.8 36.1 39.4 42.7 46

120 61

26

61

6

120

41

120

Load module US Hallway

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01144-1


US Oneway COM1-24 Occupancy Sensors Project Name: Location: 64600

65300

65320

65330

US Oneway COM1-24 Specifications Item No.

64600 US Oneway COM1-24

Accessories

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage

18 - 24 VDC/VAC (30 mA) 50/60 Hz

Load Rating

control output - 1 A @ 30 VAC/VDC

Sensing Technology

The US Oneway COM1-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to providing superior stable volumetric unidirectional detection. The unique linear unidirectional coverage pattern is engineered specifically for hallways and applications requiring a true volumetric linear pattern of detection. This is an ideal hallway sensor for design and retrofit applications where coverage is desired only in a single direction or small space applications where the sensor will not have a complete line of site view of the occupied space. Operational choices of manual on or auto on with either momentary or maintained switch options. Included force off light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of sensors are available in multiple technologies for the control of heating, ventilation and air conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

Time Delay Setting

control output 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile)

Light Level Setting

10 - 1000 lux / 1 - 100 fc

Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft) Dimensions Warranty Certifications

IP20 rated, 0°C to +40°C, 32°F to +104°F max. max. min. min.

2 x 10 m (20 sq.m.) 6.5 x 33 ft (214.5 sq.ft.) 2 x 2.5 m (5 sq.m.) 6.5 x 10 ft (65 sq.ft.)

4.72 x 4.72 x 2.87 in, 120 x 120 x 73 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant, UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • •

• Applications

ultrasonic (40 kHz)

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Unidirectional ultrasonic (40 kHz) occupancy sensor Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficient daylight is present Mounts to a 4” square box, 4” octagon box, round 3.0 mud-ring or directly to the ceiling with quick mount spring tabs IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

The typical best practice applications for the US Oneway sensors are: Hallways, underground walkways, sky walks, small offices and single stall bathrooms, small conference rooms, small kitchen or common areas, etc.

Ultrasonic

6.5 x 33 Ft Max

1 - 100 ffc

18-24 VDC/VAC

30 Sec - 30 Min

www.steinel.net


US Oneway COM1-24 Occupancy Sensors Wiring

Settings Setting

Coverage 2

1

3

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft m 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

4

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON‘ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Sensor DIP switch settings

Mounting 120

Ø

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120

Ceiling

ft 46 42.7 39.4 36.1 32.8 29.5 26 23 19.7 16 13 9.5 6.5 3.3 0 3.3 6.5 9.5 13 16 19.7 23 26 29.5 32.8 36.1 39.4 42.7 46

120 61

26

61

6

120

41

120

Load module US Oneway

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01135-1


US Oneway COM2-24 Occupancy Sensors Project Name: Location: 64610

65300

65320

65330

US Oneway COM2-24

The US Oneway COM2-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric unidirectional detection for independent control of both lighting and HVAC. Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output (isolated normally open and normally closed dry contacts) are signaled in relation to only the presence of motion. The unique linear unidirectional coverage pattern is engineered specifically for hallways and applications requiring a true volumetric linear pattern of detection. This is an ideal hallway sensor for design and retrofit applications where coverage is desired only in a single direction or small space applications where the sensor will not have a complete line of site view of the occupied space. Operational choices of manual on or auto on with either momentary or maintained switch options. Included “force off” light level feature provides the option to turn lights off when sufficient daylight is present for additional energy savings. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. Mounting options provide for 4” Square box, 4” Octagon box, Round 3.0 Mud-Ring or directly to the ceiling with quick mount spring tabs. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

6.5 x 33 Ft Max

1 - 100 ffc

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Load Rating Sensing Technology Time Delay Setting

Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft) Dimensions Warranty Certifications

18-24 VDC/VAC (34 mA) 50/60 Hz control output - 1 A @ 30 VAC/VDC HVAC dry contacts - 1 A @ 30 VAC/VDC ultrasonic (40 KHz) control output - 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) HVAC dry contacts: 0 sec. - 10 min. switch ‘ON’ delay 1 min. - 2 hrs. stay ‘ON’ time auto-HVAC mode 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F max. of 2 x 10 m (20 sq.m.) max. of 6.5 x 33 ft (214.5 sq.ft.) min. of 2 x 2.5 m (5 sq.m.) min. of 6.5 x 10 ft (65 sq.ft.) 120 x 120 x 73 mm, 4.72 x 4.72 x 2.87 in, (LxWxD) 5 years C-UL-US Listed, RoHS compliant UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • • • •

Ultrasonic

64610 US Oneway COM2-24

Voltage

Applications The typical application is for the US Quattro sensors are: Hallways, underground walkways, sky walks, small offices and single stall bathrooms, small conference rooms, small kitchen or common areas, etc.

Item No. Accessories

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Independent ON and OFF time settings for the HVAC (NO/NC) Ultrasonic (40 kHz) Occupancy Sensor Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off with sufficient daylight IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Auto-HVAC mode reduces presence detection sensitivity and requires additional detection verification before signaling the HVAC output.

18 - 24 VDC/VAC & HVAC

30 Sec - 30 Min

www.steinel.net


US Oneway COM2-24 Occupancy Sensors Wiring

Coverage

Settings 2

1

3

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft

5

4

m 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

6

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not Used

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - HVAC stay-‘ON’ time 5 - HVAC switch-‘ON’ delay 6 - Sensor DIP switch settings

Mounting 120

Ø

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120

Ceiling

ft 46 42.7 39.4 36.1 32.8 29.5 26 23 19.7 16 13 9.5 6.5 3.3 0 3.3 6.5 9.5 13 16 19.7 23 26 29.5 32.8 36.1 39.4 42.7 46

120 61

26

61

6

120

41

120

Load module US Oneway

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01136-1


US Oneway DIM-24 Occupancy Sensors Project Name: Location: 64620

65300

65320

65330

US Oneway DIM-24 Specifications Item No.

The US Oneway DIM-24 is a low voltage (40 kHz) Ultrasonic Technology Occupancy Sensor that utilizes STEINEL’s state of the art ultrasonic signal processing to provide superior stable volumetric unidirectional detection and provides a 1-10 volt dimming output to control ballasts or driver lighting loads. Lighting is controlled in relation to the presence of motion, the user selected dim level by remote or momentary switch and ambient light levels. As soon as occupancy is detected, the sensor goes to either the last selected electric light dim level (constant-lighting controller ‘OFF’) or adjusts to the last selected electric light + daylight brightness level (constant-lighting controller ‘ON’). The “force off” light level feature will turn lights off when sufficient daylight is present for additional energy savings. When no movement is detected and the occupancy time setting has elapsed, the sensor dims light levels back to basic brightness (1.6 volts), after the Stay ‘ON’ time DIM before ‘OFF’ delay has expired the light turns off. The unique linear unidirectional coverage pattern is engineered specifically for hallways and applications requiring a true volumetric linear pattern of detection. This is an ideal hallway sensor for design and retrofit applications where coverage is desired only in a single direction or small space applications where the sensor will not have a complete line of site view of the occupied space. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning as well as lighting (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications

Accessories

Voltage Load Rating

Sensing Technology Time Delay Setting Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft) Dimensions Warranty Certifications

64620 US Oneway DIM-24 65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (46 mA) 50/60 Hz control output (blue) 1 A @ 30 VAC/VDC 1 - 10 volt dimming output (purple & gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts) ultrasonic (40 kHz) 30 sec. to 30 min., pulse mode (approx. 2 sec.) IQ mode (automatic adjustment to the usage profile) 10 - 1000 lux / 1 - 100 fc IP20 rated, 0°F to +40°F, 32°C to +104°C max. of 2 x 10 m (20 sq.m.) min. of 2 x 2.5 m (5 sq.m.) max. of 6.5 x 33 ft (214.5 sq.ft.) min. of 6.5 x 10 ft (65 sq.ft.) 4.72 x 4.72 x 2.87 in, 120 x 120 x 73 mm (LxWxD) 5 years C-UL-US Listed, RoHS Compliant UL 2043 Plenum rated, CA Energy Code Compliant

Key Features: • • • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system 1-10 volt dimming Stay ‘ON’ time DIM before ‘OFF’ Constant light level DIM control option Ultrasonic (40 kHz) Occupancy Sensor Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

The typical application is fort he US Quattro sensors are: Hallways, underground walkways, sky walks, small offices and single stall bathrooms, small conference rooms, small kitchen or common areas, etc.

Ultrasonic

6.5 x 33 Ft Max

1 - 100 ffc

18 - 24 VDC/VAC 1 - 10 Volt Dimming

30 Sec - 30 Min

www.steinel.net


US Oneway DIM-24 Occupancy Sensors Wiring

Coverage

Setting 1

2

3

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft

4

m 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

5

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Constant light level DIM control option

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Stay ‘ON’ time DIM before ‘OFF’ 5 - Sensor DIP switch settings

Mounting 120

Ø

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120

Ceiling

ft 46 42.7 39.4 36.1 32.8 29.5 26 23 19.7 16 13 9.5 6.5 3.3 0 3.3 6.5 9.5 13 16 19.7 23 26 29.5 32.8 36.1 39.4 42.7 46

120 61

26

61

6

120

41

120

Load module US Oneway

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01137-1


DT Quattro COM1-24 Presence Detectors Project Name: Location: 64700

65300

65320

65330

DT Quattro COM1-24 Specifications Item No. Accessories

18 - 24 VDC/VAC (30 mA) 50/60 Hz

Load Rating

control output - 1 A @ 30 VAC/VDC

Time Delay Setting

Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft)

PIR Detection Zones:

Dimensions Warranty Certifications

Applications The typical application is for classrooms, conference rooms, computer rooms, storage rooms, workspaces, open office space with cubicles, general open areas, restrooms, stairwells, storage rooms, executive offices and private offices.

Passive Infrared Ultrasonic

20 x 20 Ft Presence 32 x 32 Ft Max

1 - 100 ffc

passive infrared (PIR), single pyro, 11 detection levels, 520 switching zones, ultrasonic 40 kHz control output 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) 10 - 1000 lux / 1 - 100 fc IP20 rated, 0°C to +40°C, 32°F to +104°F presence: max. 6 x 6 m (36 sq.m.) max. 20 x 20 ft (400 sq.ft.) min. 2 x 2 (4 sq.m.) min. 6.5 x 6.5 ft (42.25 sq.ft.) radial / tangential: max. of up to 10 x 10 m (100 sq.m.) radial / tangential: max. of up to 32 x 32 ft (1000 sq.ft.) presence: max. max. radially: max. tangentially: max.

3 x 3 m (9 sq.m.) 10 x 10 ft (100 sq.ft.) 4 x 4 m (13 x 13 ft) 8 x 8 m (26 x 26 ft )

4.72 x 4.72 x 2.68 in, 120 x 120 x 68 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant, UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: •

The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air conditioning (HVAC) and lighting loads (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage

Voltage

Sensing Technologies

The DT Quattro COM1-24 Dual Technology Presence Detector utilizes PIR and ultrasonic technologies to detect the presence or signature of a person in a space. The logic options for initial “ON” and “Maintained” state of occupancy gives design engineers and installation contractors the choice for proper control of lighting and building automation in difficult applications where detection options are needed in a single device. Lighting loads are controlled in relation to both presence detection and selectable ambient light levels with the integrated force off photocell to maximize energy savings. STEINEL’s world class PIR optics and ultrasonic signal processing provides unparalleled line of sight and volumetric presence detection. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with convenient control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience.

64700 DT Quattro COM1-24

• • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system PIR & ultrasonic (40 kHz) presence detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off when sufficient daylight is present Mounts to a 4” square box, 4” octagon box, round 3.0 mudring or directly to the ceiling with quick mount spring tabs IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

18-24 VDC/VAC

30 Sec - 30 Min

www.steinel.net


DT Quattro COM1-24 Presence Detectors Wiring

2

1

3

Settings 1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Sensor DIP switch settings 5 - Trigger mode

Coverage Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces.

4

One Gridline = 1 m / 3.3 ft

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used DIP 6/7/8 - Trigger mode 5 Initial Maintain Trigger Mode Options Occupancy Occupancy Option 1 Both Either Option 2 Both Both Option 3 PIR Either Option 4 US Either Option 5 Factory Setting Either Either Option 6 US US Option 7 PIR PIR Option 8 Either Both

m ft 6 19.7 5 16

Tangential - motion perpendicular to the sensor

4 13

Radial - motion either directly toward or away from the sensor

3 9.5 2 6.5 1 3.3 0 0

Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection

1 3.3

DIP 6 L OFF L OFF L OFF L OFF K ON K ON K ON K ON

DIP 7 L OFF L OFF K ON K ON L OFF L OFF K ON K ON

DIP 8 L OFF K ON L OFF K ON L OFF K ON L OFF K ON

2 6.5 3 9.5 4 13 5 16 6 19.7 6

5

4

3

2

1

0

1

2

3

4

5

6

The trigger mode enables the user to choose which sensing technologies should be used to initially turn the load on and which technologies are required to keep it on.

Mounting 120

Ø

120

Ceiling

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

120 61

26

61

6

120

36

120

Load module DT Quattro

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01149-1


DT Quattro COM2-24 Presence Detectors Project Name: Location: 64710

65300

65320

65330

DT Quattro COM2-24 Item No. Accessories

Voltage Load Rating Sensing Technology

The DT Quattro COM2-24 Dual Technology Presence Detector utilizes PIR and ultrasonic technologies to detect the presence or signature of a person in a space. The logic options for initial “ON” and “Maintained” state of occupancy gives design engineers and installation contractors the choice for proper control of lighting and HVAC in difficult applications where detection options are needed in a single device. Lighting loads are controlled in relation to both presence detection and selectable ambient light levels with the integrated force off photocell to maximize energy savings. The separate HVAC dry contact output is signaled only by presence detection and has a separate “ON/OFF” delay time feature set. STEINEL’s world class PIR optics and ultrasonic signal processing provides unparalleled line of sight and volumetric presence detection. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience. The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning (HVAC) and lighting loads (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions). Applications The typical application is for lighting and HVAC in classrooms, conference rooms, computer rooms, storage rooms, workspaces, open office space with cubicles, general open areas, restrooms, stairwells, storage rooms, executive offices and private offices.

Time Delay Setting

Light Level Setting Environment Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft)

PIR Detection Zones:

Dimensions Warranty Certifications

20 x 20 Ft Presence 32 x 32 Ft Max

1 - 100 ffc

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (34 mA) 50/60 Hz control output - 1 A @ 30 VAC/VDC HVAC dry contacts - 1 A @ 30 VAC/VDC passive infrared (PIR), single pyro, 11 detection levels, 520 switching zones, ultrasonic 40 kHz control output - 30 sec. - 30 min. pulse mode (approx. 2 sec. ‘ON’ 8 sec. ‘OFF’) IQ mode (automatic adjustment to the usage profile) HVAC dry contacts: 0 sec. - 10 min. switch ‘ON’ delay 1 min. - 2 hrs. stay ‘ON’ time, auto-HVAC mode 10 – 1000 lux / 1 – 100 fc IP20 rated, 0° C to +40° C / 32° F to 104° F presence: max. of 6 x 6 m (36 sq.m.) max. of 20 x 20 ft (400 sq.ft.) min. of 2 x 2 (4 sq.m.) min. of 6.5 x 6.5 ft (42.25 sq.ft.) radial / tangential: max. of up to 10 x 10 m (100 sq.m.) radial / tangential: max. of up to 32 x 32 ft (1000 sq.ft.) presence: max. max. radially: max. tangentially: max.

of of of of

3 x 3 m (9 sq.m.) 10 x 10 ft (100 sq.ft.) 4 x 4 m (13 x 13 ft) 8 x 8 m (26 x 26 ft )

4.72 x 4.72 x 2.68 in, 120 x 120 x 68 mm (LxWxD) 5 years C-UL-US Listed, RoHS compliant UL 2043 Plenum Rated, CA Energy Code compliant

Key Features: • • • • • • • • • •

Passive Infrared Ultrasonic

64710 DT Quattro COM2-24

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system Independent ON and OFF time settings for the HVAC (NO/NC) PIR & Ultrasonic (40 kHz) Presence Detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching Light level feature turns lights off with sufficient daylight IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Auto-HVAC mode

18 - 24 VDC/VAC & HVAC

30 Sec - 30 Min

www.steinel.net


DT Quattro COM2-24 Presence Detectors Wiring

Settings 1 - Light level setting 2 1 2 - Occupancy time delay setting 3 - Reach setting 4 - HVAC stay-‘ON’ time 6 5 - HVAC switch-‘ON’ delay 6 - Sensor DIP switch settings 7 - Trigger mode DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Not used DIP 6/7/8 - Trigger mode 7 Initial Maintain Trigger Mode Options Occupancy Occupancy Option 1 Both Either Option 2 Both Both Option 3 PIR Either Option 4 US Either Option 5 Factory Setting Either Either Option 6 US US Option 7 PIR PIR Option 8 Either Both

3

5

4

Coverage Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft m ft

6 19.7 5 16

Tangential - motion perpendicular to the sensor

4 13

Radial - motion either directly toward or away from the sensor

3 9.5 2 6.5 1 3.3 0 0

DIP 6 L OFF L OFF L OFF L OFF K ON K ON K ON K ON

DIP 7 L OFF L OFF K ON K ON L OFF L OFF K ON K ON

DIP 8 L OFF K ON L OFF K ON L OFF K ON L OFF K ON

Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection

1 3.3 2 6.5 3 9.5 4 13 5 16 6 19.7 6

5

4

3

2

1

0

1

2

3

4

5

6

The trigger mode enables the user to choose which sensing technologies should be used to initially turn the load on and which technologies are required to keep it on.

Mounting 120

Ø

120

Ceiling

min. 68 mm (2 11/16 in) max. 76 mm (3 in)

120 61

26

61

6

120

36

120

Load module DT Quattro

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01150-1


DT Quattro DIM-24 Presence Detectors Project Name: Location: 64720

65300

65320

65330

DT Quattro DIM-24 Specifications Item No. Accessories

The DT Quattro Q tt DIM DIM-24 24 D Duall T Technology h l P Presence Detector D utilizes PIR and ultrasonic technologies to detect the presence or signature of a person in a space. The logic options for initial “ON” and “Maintained” state of occupancy gives design engineers and installation contractors the choice for proper control of lighting and provides a 1-10 volt dimming output to control ballasts or driver lighting loads. Lighting is controlled in relation to the presence of motion, the user selected dim level by remote or momentary switch and ambient light levels. As soon as presence is detected, the sensor goes to either the last selected electric light dim level (constant-lighting controller ‘OFF’) or adjusts to the last selected electric light + daylight brightness level (constant-lighting controller ‘ON’). The “force off” light level feature will turn lights off when sufficient daylight is present for additional energy savings. When no movement is detected and the occupancy time setting has elapsed, the sensor dims light levels back to basic brightness (1.6 volts), after the Stay ‘ON’ time DIM before ‘OFF’ delay has expired the light turns off. STEINEL’s world class PIR optics and ultrasonic signal processing provides unparalleled line of sight and volumetric presence detection. Operational choices of auto on or manual on with a momentary or maintained switch input. The convenient “COM-Link” feature enables multiple sensors to link together via the communication link for pier to pier grouping achieving expanded detection zones with control set up functions set at only one primary sensor for the entire group. The available service and user wireless remotes provide simplified commissioning and occupant convenience.

Voltage

Applications The typical application is for classrooms, conference rooms, computer rooms, workspaces, open office space with cubicles, general open areas, restrooms, stairwells, storage rooms, executive offices and private offices.

Passive Infrared Ultrasonic

20 x 20 Ft Presence 32 x 32 Ft Max

1 - 100 ffc

65300 RC 3 service remote 65320 RC 4 user remote 65330 WGC wire guard cage 18-24 VDC/VAC (46mA) 50/60 Hz

Load Rating

control output (blue) 1 A @ 30 VAC/VDC 1 - 10 volt dimming output (purple & gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts)

Sensing Technology

passive infrared (PIR), single pyro, 11 detection levels, 520 switching zones, ultrasonic 40 kHz

Time Delay Setting

30 sec. to 30 min., pulse mode (approx. 2 sec.) IQ mode (automatic adjustment to the usage profile)

Light Level Setting

10 - 1000 lux / 1 - 100 fc

Environment

IP20 rated, 0°F to +40°F, 32°C to +104°C

Ultrasonic Detection Zones: (Coverage at 2.5 m / 9 ft)

presence: max. of 6 x 6 m (36 sq.m.) max. of 20 x 20 ft (400 sq.ft.) min. of 2 x 2 (4 sq.m.) min. of 6.5 x 6.5 ft (42.25 sq.ft.) radial / tangential: max. of up to 10 x 10 m (100 sq.m.) radial / tangential: max. of up to 32 x 32 ft (1000 sq.ft.)

PIR Detection Zones:

presence: max. of 3 x 3 m (9 sq.m.) max. of 10 x 10 ft (100 sq.ft.) radially: max. of 4 x 4 m (13 x 13 ft) tangentially: max. of 8 x 8 m (26 x 26 ft

Dimensions Warranty Certifications

4.72 x 4.72 x 2.68 in, 120 x 120 x 68 mm (LxWxD) 5 years C-UL-US Listed, RoHS Compliant UL 2043 Plenum rated, CA Energy Code Compliant

Key Features: •

The Control PRO group of presence detectors are available in multiple presence detection technologies for the control of heating, ventilation and air-conditioning (HVAC) and lighting loads (as in the COM2-24 versions) and optional 1-10 volt dimming and daylighting options (in the DIM-24 versions).

64720 DT Quattro DIM-24

• • • • • • • • •

Low voltage (18-24 VDC/VAC) sensor for use with a power pack or building automation system 1-10 volt dimming Stay ‘ON’ time DIM before ‘OFF’ Constant light level DIM control option PIR & Ultrasonic (40 kHz) Presence Detection Service and user wireless remotes available Manual ON mode (MAN) / Automatic mode (AUTO) Momentary / Maintained switch option ‘ON’ only / ‘ON’ & ‘OFF’ manual switching IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

18 - 24 VDC/VAC 1 - 10 Volt Dimming

30 Sec - 30 Min

www.steinel.net


DT Quattro DIM-24 Presence Detectors Wiring

Settings

2

1

1 - Light level setting 2 - Occupancy time delay setting 3 - Reach setting 4 - Stay ‘ON’ time DIM before ‘OFF’ 5 - Sensor DIP switch settings 6 - Trigger Mode

3

4

Coverage

5

Shown coverage diagram at 9 ft mounting height. Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces. One Gridline = 1 m / 3.3 ft m ft

DIP 1 - Normal mode / Test mode (NORM / TEST) DIP 2 - Manual ON mode (MAN) / Automatic mode (AUTO) DIP 3 - Momentary / Maintained switch option DIP 4 - ‘ON’ only / ‘ON’ & ‘OFF’ manual switching DIP 5 - Constant light level DIM control option DIP 6/7/8 - Trigger mode 6 Initial Maintain Trigger Mode Options Occupancy Occupancy Option 1 Both Either Option 2 Both Both Option 3 PIR Either Option 4 US Either Option 5 Factory Setting Either Either Option 6 US US Option 7 PIR PIR Option 8 Either Both

6 19.7 5 16

Tangential - motion perpendicular to the sensor

4 13

Radial - motion either directly toward or away from the sensor

3 9.5 2 6.5 1 3.3 0 0

Presence - minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection

1 3.3

DIP 6 L OFF L OFF L OFF L OFF K ON K ON K ON K ON

DIP 7 L OFF L OFF K ON K ON L OFF L OFF K ON K ON

DIP 8 L OFF K ON L OFF K ON L OFF K ON L OFF K ON

2 6.5 3 9.5 4 13 5 16 6 19.7 6

5

4

3

2

1

0

1

2

3

4

5

6

The trigger mode enables the user to choose which sensing technologies should be used to initially turn the load on and which technologies are required to keep it on.

Mounting 120

Ø

120

Ceiling

Min. 68 mm (2 11/16 in) Max. 76 mm (3 in)

120 61

26

61

6

120

36

120

Load module DT Quattro

Sensor Module 120

Mounts to a 4“ Square box, 4“ Octagon box or Round 3.0 Mud-Ring

www.steinel.net

(800) 852-4343

Mounts directly to ceiling with quick mount spring tabs

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01151-1


Wall Switch Sensors Occupancy controlled wall switches The STEINEL Wall Switch sensors are available in infrared, ultrasonic and dual tech versions. STENEL’s commercial switches feature all the sequence of operation settings that are needed for controlling a typical office or small conference room. The new innovative “SwitchLink” feature provides true multi-way switching and the ability to expand coverage in the desired control zone.


IR WLS 1 Passive Infrared Wall Switch Occupancy Sensor Project Name: Location: 66100

66110

IR WLS 1 Specifications ecification Item No. Voltage Mounting Load Rating

Sensing Technology Time Setting Light Level Setting Environment

The IR WLS 1 is a line voltage, single relay, Passive Infrared (PIR) wall switch occupancy sensor intended to control lighting in commercial spaces. PIR is used where the sensor will have a clear view of the occupants in the desired coverage area. The hold OFF photocell daylight option will keep the lighting load off if the light level is greater than the threshold level setting. The convenient “Switch Link” feature enables up to four sensors to link together for pier to pier grouping achieving expanded detection zones and multiway switching.

PIR Coverage at 1.2 m / 4 ft Mounting Height Dimensions Warranty Certifications

66100 IR WLS 1-W (white) 66110 IR WLS 1-LA (light almond) 120/230/277 VAC, 50/60 Hz single-gang NEMA-style switch box (standard switch box) & decorator-style wall plate by others 0-800 watts @ 120/230/277 VAC, 50/60 Hz tungsten, magnetic or electronic ballast • 1/6 hp 0-600 watts @ 120/230/277 VAC, 50/60 Hz CFL or LED electronic ballasts C d 132 μF max. passive infrared (PIR) IQ/Test, 5, 15, 30 minutes 80 - 2000 Lux / 8 - 200 fc IP20 rated, 0°C to +40°C, 32°F to +104°F minor motion: max. max. radially: max. tangentially: max.

6.5 x 5.5 m (36 sq.m.) 21 x 18 ft (378 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 20 m (628 sq.m.) 54 ft (4,500 sq.ft.)

105 x 44.1 x 45.1 mm, 4.13 x 1.74 x 1.78 in, (LxWxD) 5 years C-UL-US Listed, RoHS compliant, California Compliant

Applications The typical application is for small office, conference, storage closet and break rooms. For best performance use this sensor in enclosed spaces no larger than 18’ x 15’. Key Features: • • • • • • • •

PIR (passive infrared) wall switch occupancy sensor Line voltage lighting control (120/230/277 VAC, 50/60 Hz) 180° coverage pattern Manual ON or Automatic ON option Light level feature keeps lights OFF when sufficient daylight is present Mounts to a single-gang NEMA-style, standard switch box & decorator-style wall plate by others “Switch Link” communication allows for up to 4 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

Passive Infrared

21 Ft Minor Motion 54 Ft Tangential

8 - 200 ffc

• •

Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected Visible alert feature provides a momentary OFF/ON blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button

Line Voltage

IQ/Test, 5, 15, 30 Min

www.steinel.net


IR WLS 1 Passive Infrared Wall Switch Occupancy Sensor Wiring WLS 1 (Master / Master) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" WLS 1 Basic Wiring

Line Neutral

Line

Line (Black)

Neutral

Line (Black) Neutral (White)

Neutral (White) Red (Load)

Load

Line (Black) Neutral (White)

Red (Load)

Load

Red (Load)

Load Yellow (Switch Link)

Ground

Ground (Green)

Yellow (Switch Link)

Yellow Ground (Green)

Ground (Green) Ground

WLS 1 (Master / Slave) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link"

Components

Line Neutral

ON/OFF button

Line (Black) Neutral (White)

Line (Black) Neutral (White)

Red (Load)

Red (Load)

Load

Yellow (Switch Link) Ground (Green)

Yellow Ground (Green)

Ground

DIP switches

Audible Alert (ON)

Visible Alert (ON)

5

6

7

8

Visible Alert (OFF)

Service Mode (ON)

Walk Through (ON)

42 36 30

30

18

18

12

24

24

18

30

24

36

36

12

12

12

24

18

12

18

30

24

36

42

30

48

36

3

42

48

PIR Tangential Coverage PIR Radial Coverage PIR Minor Motion Coverage

9

10 Service Mode (OFF)

48

42

2

Relay 1 (Automatic ON)

54

48

42

4

ON OFF 1

48

Time Delay

Audible Alert (OFF)

Coverage

Relay 1 (Manual ON)

Not Used

Walk Through (OFF)

Setting

PIR lens

Time Delay

8

9

IQ / Test

OFF

OFF

5 Minutes

OFF

ON

15 Minutes

ON

OFF

30 Minutes

ON

ON

Ordering Information Color

Part #

Relays

IR WLS 1-W

Model

White

66100

1

IR WLS 1-LA

Light Almond

66110

1

IR WLS 2-W

White

66130

2

IR WLS 2-LA

Light Almond

66140

2

www.steinel.net

(800) 852-4343

Technology

Coverage

Voltage

PIR

180°

120/230/277 VAC

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01501-1


IR WLS 2 Passive Infrared Dual Relay Wall Switch Occupancy Sensor Project Name: Location: 66130

66140

IR WLS 2 Specifications ifi ti Item No. Voltage Mounting Load Rating (Per Relay)

Sensing Technology Time Setting Light Level Setting Environment

The IR WLS 2 is a line voltage, two relay, Passive Infrared (PIR) wall switch occupancy sensor intended to control bi-level lighting in commercial spaces. PIR is used where the sensor will have a clear view of the occupants in the desired coverage area. The hold off photocell daylight option will keep the lighting load OFF when the light level is greater than the threshold level setting. The convenient “Switch Link” feature enables up to four sensors to link together for pier to pier grouping achieving expanded detection zones and multiway switching.

PIR Coverage at 1.2 m / 4 ft Mounting Height Dimensions Warranty Certifications

66130 IR WLS 2-W (white) 66140 IR WLS 2-LA (light almond) 120/230/277 VAC, 50/60 Hz single-gang NEMA-style switch box (standard switch box) & decorator-style wall plate by others 0-800 watts @ 120/230/277 VAC, 50/60 Hz tungsten, magnetic or electronic ballast • 1/6 hp 0-600 watts @ 120/230/277 VAC, 50/60 Hz CFL or LED electronic ballasts C d 132 μF max. passive infrared (PIR) IQ/Test, 5, 15, 30 minutes 80 - 2000 Lux / 8 - 200 fc IP20 rated, 0°C to +40°C, 32°F to +104°F minor motion: max. max. radially: max. tangentially: max.

6.5 x 5.5 m (36 sq.m.) 21 x 18 ft (378 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 20 m (628 sq.m.) 54 ft (4,500 sq.ft.)

105 x 44.1 x 45.1 mm, 4.13 x 1.74 x 1.78 in, (LxWxD) 5 years C-UL-US Listed, RoHS compliant, California Compliant

Applications The typical application is for bi-level switching in small office, conference, and break rooms. For best performance use this sensor in enclosed spaces no larger than 18’ x 15’. Key Features: • • • • • • • •

PIR (passive infrared) wall switch occupancy sensor Bi-level load switching (2 relays) Line voltage lighting control (120/230/277 VAC, 50/60 Hz) 180° coverage pattern Manual ON or Automatic ON option Light level feature keeps lights OFF when sufficient daylight is present Mounts to a single-gang NEMA-style, standard switch box & decorator-style wall plate by others “Switch Link” communication allows for up to 4 sensors to be grouped together

Passive Infrared

21 Ft Minor Motion 54 Ft Tangential

8 - 200 ffc

• • •

IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected Visible alert feature provides a momentary OFF/ON blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button

LIne Voltage

IQ/Test, 5, 15, 30 Min

www.steinel.net


IR WLS 2 Passive Infrared Dual Relay Wall Switch Occupancy Sensor Wiring WLS 2 (Master / Master) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line

WLS 2 Basic Wiring

Neutral Line

Line 1 (Black) Line 2 (Blue) Neutral (White)

Neutral

Load

Red (Load 1)

Load

Load

Brown (Load 2)

Load Ground

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Ground (Green)

Load Load Yellow (Switch Link)

Ground (Green)

Yellow (Switch Link)

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2) Yellow Ground (Green)

Ground

WLS 2 (Master / Slave) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link"

Components

Line Neutral Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

ON/OFF button relay 1 ON/OFF button relay 2

Load Load

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2) Yellow (Switch Link)

Ground (Green)

Yellow Ground (Green)

Ground

DIP switches

Walk Through (ON)

Audible Alert (ON)

Visible Alert (ON)

4

5

6

7

Audible Alert (OFF)

Time Delay

Service Mode (ON)

Relay 1 (Manual ON)

3

Walk Through (OFF)

Not Used

Relay 2 (Manual ON)

PIR lens

Relay 1 (Automatic ON)

Setting

8

10

Coverage 54 48 42

24

24

18

18

12

30

30

18

36

36

24

42

42

30

48

36

48

12

12

12

12

18

24

18

30

24

36

42

30

48

36

42

48

PIR Tangential Coverage PIR Radial Coverage PIR Minor Motion Coverage

Model

Color

Part #

Relays

IR WLS 1-W

White

66100

1

IR WLS 1-LA

Light Almond

66110

1

IR WLS 2-W

White

66130

2

IR WLS 2-LA

Light Almond

66140

2

www.steinel.net

(800) 852-4343

9

Service Mode (OFF)

2

Relay 2 (Automatic ON)

1

Visible Alert (OFF)

ON OFF

Time Delay

8

9

IQ / Test

OFF

OFF

5 Minutes

OFF

ON

15 Minutes

ON

OFF

30 Minutes

ON

ON

Technology

Coverage

Voltage

PIR

180°

120/230/277 VAC

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01502-1


US WLS 1 Ultrasonic Wall Switch Occupancy Sensor Project Name: Location: 66160

66170

US S WLS S 1 Specifications Item No. Voltage Mounting Load Rating

Sensing Technology Time Setting Light Level Setting Environment

The US WLS 1 is a line voltage, single relay, Ultrasonic (40 kHz) wall switch occupancy sensor intended to control lighting in commercial spaces. Ultrasonic is used where the sensor will not have a clear line of site of the occupants in the desired coverage area. The hold OFF photocell daylight option will keep the lighting load off when the light level is greater than the threshold level setting. The convenient “Switch Link” feature enables up to four sensors to link together for pier to pier grouping achieving expanded detection zones and multiway switching.

Ultrasonic Coverage at 1.2 m / 4 ft Mounting Height Dimensions Warranty Certifications

66160 US WLS 1-W (white) 66170 US WLS 1-LA (light almond) 120/230/277 VAC, 50/60 Hz single-gang NEMA-style switch box (standard switch box) & decorator-style wall plate by others 0-800 watts @ 120/230/277 VAC, 50/60 Hz tungsten, magnetic or electronic ballast • 1/6 hp 0-600 watts @ 120/230/277 VAC, 50/60 Hz CFL or LED electronic ballasts C d 132 μF max. 40 kHz ultrasonic IQ/Test, 5, 15, 30 minutes 80 - 2000 lux / 8 - 200 fc IP20 rated, 0°C to +40°C, 32°F to +104°F minor motion: max. max. radially: max. tangentially: max.

8 x 8 m (64 sq.m.) 18 x 12 ft (216 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.)

105 x 44.1 x 45.1 mm, 4.13 x 1.74 x 1.78 in (LxWxD) 5 years C-UL-US Listed, RoHS compliant, California Compliant

Applications The typical application is for small offices, restrooms with two stalls and utility/storage rooms. For best performance use this sensor in enclosed spaces no larger than 15’ x 15’. Key Features: • • • • • • • • •

40 kHz ultrasonic wall switch occupancy sensor Adjustable ultrasonic reach setting from 25% to 100% Line voltage lighting control (120/230/277 VAC, 50/60 Hz) 180° coverage pattern Manual ON or Automatic ON option Light level feature keeps lights OFF when sufficient daylight is present Mounts to a single-gang NEMA-style, standard switch box & decorator-style wall plate by others “Switch Link” communication allows for up to 4 sensors to be grouped together IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy

Ultrasonic

18 Ft Minor Motion 24 Ft Tangential

8 - 200 ffc

• •

Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected Visible alert feature provides a momentary OFF/ON blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button

Line Voltage

IQ/Test, 5, 15, 30 Min

www.steinel.net


US WLS 1 Ultrasonic Wall Switch Occupancy Sensor Wiring WLS 1 (Master / Master) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line

WLS 1 Basic Wiring

Neutral

Line

Line (Black)

Neutral

Line (Black)

Line (Black)

Neutral (White)

Neutral (White)

Neutral (White)

Red (Load)

Load

Load

Red (Load)

Load

Red (Load)

Yellow (Switch Link) Ground (Green)

Yellow Ground (Green)

Ground Ground (Green)

Ground

Yellow (Switch Link) WLS 1 (Master / Slave) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line Neutral

Components

Line (Black) Neutral (White)

Line (Black) Neutral (White)

Red (Load)

Red (Load)

Load

Yellow (Switch Link) Ground (Green)

Yellow Ground (Green)

Ground

ON/OFF button

Time Delay

4

5

6

7

8

Service Mode (ON)

Visible Alert (ON)

Not Used

Audible Alert (ON)

Ultrasonic transducers

Walk Through (ON)

Ultrasonic sensitivity adjustment trimpot DIP switches

Relay 1 (Manual ON)

Setting

10 Service Mode (OFF)

Coverage

9

Visible Alert (OFF)

3

Audible Alert (OFF)

2

Relay 1 (Automatic ON)

1

Walk Through (OFF)

ON OFF

Time Delay

8

9

IQ / Test

OFF

OFF

5 Minutes

OFF

ON

15 Minutes

ON

OFF

30 Minutes

ON

ON

54 48 42

24

24

18

18

12

30

30

18

36

36

24

42

42

30

48

36

48

12

12

12

12

18

24

18

30

24

36

42

48

The sensors ultrasonic sensitivity and reach is adjusted with a trim potentiometer (dial). The left stop is minimum 25% (counter clockwise) the right stop is maximum 100% (clockwise). 30

36

42

48

Ultrasonic Tangential and Radial Coverage Ultrasonic Minor Motion Coverage

Ordering Information Color

Part #

Relays

US WLS 1-W

Model

White

66160

1

US WLS 1-LA

Light Almond

66170

1

US WLS 2-W

White

66190

2

US WLS 2-LA

Light Almond

66200

2

www.steinel.net

(800) 852-4343

Technology

Coverage

Voltage

40 kHz Ultrasonic

180°

120/230/277 VAC

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01503-1


US WLS 2 Ultrasonic Dual Relay Wall Switch Occupancy Sensor Project Name: Location: 66190

66200

US WLS 2 Specifications Item No. Voltage Mounting Load Rating (Per Relay)

Sensing Technology Time Setting Light Level Setting

The US WLS 2 is a line voltage, two relay, Ultrasonic (40 kHz) wall switch occupancy sensor intended to control bilevel lighting in commercial spaces. Ultrasonic is used where the sensor does not have a clear view of the occupants in the desired coverage area. The hold off photocell daylight option will keep the lighting load OFF when the light level is greater than the threshold level setting. The convenient “Switch Link” feature enables up to four sensors to link together for pier to pier grouping achieving expanded detection zones and multiway switching.

Environment Ultrasonic Coverage at 1.2 m / 4 ft Mounting Height Dimensions Warranty Certifications

66190 US WLS 2-W (white) 66200 US WLS 2-LA (light almond) 120/230/277 VAC, 50/60 Hz single-gang NEMA-style switch box (standard switch box) & decorator-style wall plate by others 0-800 watts @ 120/230/277 VAC, 50/60 Hz tungsten, magnetic or electronic ballast • 1/6 hp 0-600 watts @ 120/230/277 VAC, 50/60 Hz CFL or LED electronic ballasts C d 132 μF max. 40 kHz ultrasonic IQ/Test, 5, 15, 30 minutes 80 - 2000 lux / 8 - 200 fc IP20 rated, 0°C to +40°C, 32°F to +104°F minor motion: max. max. radially: max. tangentially: max.

8 x 8 m (64 sq.m.) 18 x 12 ft (216 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.)

105 x 44.1 x 45.1 mm, 4.13 x 1.74 x 1.78 in (LxWxD) 5 years C-UL-US Listed, RoHS compliant, California Compliant

Applications The typical application is for bi-level switching (lighting and/ or fan motor) in restrooms utility and storage rooms. For best performance use this sensor in enclosed spaces no larger than 15’ x 15’. Key Features: • • • • • • • • •

40 kHz ultrasonic wall switch occupancy sensor Adjustable ultrasonic reach setting from 25% to 100% Bi-level load switching (2 relays) Line voltage lighting control (120/230/277 VAC, 50/60 Hz) 180° coverage pattern Manual ON or Automatic ON option Light level feature keeps lights OFF when sufficient daylight is present Mounts to a single-gang NEMA-style, standard switch box & decorator-style wall plate by others “Switch Link” communication allows for up to 4 sensors to be grouped together

Ultrasonic

18 Ft Minor Motion 24 Ft Tangential

8 - 200 ffc

• • •

IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected Visible alert feature provides a momentary Off/On blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button

Line Voltage

IQ/Test, 5,15, 30 Min

www.steinel.net


US WLS 2 Ultrasonic Dual Relay Wall Switch Occupancy Sensor Wiring

WLS 2 (Master / Master) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link"

Line Neutral

WLS 2 Basic Wiring

Line

Line 1 (Black) Line 2 (Blue) Neutral (White)

Neutral

Load Load

Load Load

Yellow Ground (Green)

Ground (Green)

Brown (Load 2)

Load Ground

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Yellow (Switch Link)

Red (Load 1)

Load

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Ground

Ground (Green)

Yellow (Switch Link)

WLS 2 (Master / Slave) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line

Components

Neutral

ON/OFF button relay 1

Load Load

ON/OFF button relay 2

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2) Yellow

Yellow (Switch Link) Ground (Green)

Ground (Green)

Ground

Ultrasonic sensitivity adjustment trimpot DIP switches

Setting

Coverage

36 30 24

18

18

12

24

24

18

30

30

12

12

12

24

18

12

18

30

24

36

30

48

36

42

Service Mode (ON)

Audible Alert (ON)

Visible Alert (ON) 7 Visible Alert (OFF)

8

9

10

Time Delay

8

9

IQ / Test

OFF

OFF

5 Minutes

OFF

ON

15 Minutes

ON

OFF

30 Minutes

ON

ON

Service Mode (OFF)

6 Audible Alert (OFF)

5 Walk Through (OFF)

42

36

42

4 Relay 1 (Automatic ON)

48

36

42

3 Relay 2 (Automatic ON)

2

54

48

42

Time Delay

ON OFF 1

48

Walk Through (ON)

Not Used

Relay 1 (Manual ON)

Relay 2 (Manual ON)

Ultrasonic transducers

The sensors ultrasonic sensitivity and reach is adjusted with a trim potentiometer (dial). The left stop is minimum 25% (counter clockwise) the right stop is maximum 100% (clockwise).

48

Ultrasonic Tangential and Radial Coverage Ultrasonic Minor Motion Coverage

Ordering Information Color

Part #

Relays

US WLS 1-W

Model

White

66160

1

US WLS 1-LA

Light Almond

66170

1

US WLS 2-W

White

66190

2

US WLS 2-LA

Light Almond

66200

2

www.steinel.net

(800) 852-4343

Technology

Coverage

Voltage

40 kHz Ultrasonic

180°

120/230/277 VAC

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01504-1


DT WLS 1 Dual Technology Wall Switch Occupancy Sensor Project Name: Location: 66220

66230

DT WLS 1 Specifications ifi ti Item No. Voltage Mounting Load Rating

Sensing Technology Time Setting

The DT WLS 1 is a line voltage, single relay, Dual Technology (PIR & ultrasonic) wall switch occupancy sensor intended to control lighting in commercial spaces. The combination of both technologies enhances occupancy detection in difficult applications. DIP switch adjustable technology options to initiate the load ON and maintain the load ON with either or both technologies. The hold off photocell daylight option will keep the lighting load OFF when the light level is greater than the threshold level setting. The convenient “Switch Link” feature enables up to four sensors to link together for pier to pier grouping achieving expanded detection zones and multiway switching.

Light Level Setting Environment

120/230/277 VAC, 50/60 Hz single-gang NEMA-style switch box (standard switch box) & decorator-style wall plate by others 0-800 watts @ 120/230/277 VAC, 50/60 Hz tungsten, magnetic or electronic ballast • 1/6 hp 0-600 watts @ 120/230/277 VAC, 50/60 Hz CFL or LED electronic ballasts C d 132 μF max. 40 kHz ultrasonic & passive infrared IQ/Test, 5, 15, 30 minutes 80 - 2000 lux / 8 - 200 fc IP20 rated, 0°C to +40°C, 32°F to +104°F

Ultrasonic Coverage at 1.2 m / 4 ft Mounting Height

minor motion: max. max. radially: max. tangentially: max.

8 x 8 m (64 sq.m.) 18 x 12 ft (216 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.)

PIR Coverage at 1.2 m / 4 ft Mounting Height

minor motion: max. max. radially: max. tangentially: max.

6.5 x 5.5 m (36 sq.m.) 21 x 18 ft (378 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 20 m (628 sq.m.) 54 ft (4,500 sq.ft.)

Dimensions Warranty

Applications

66220 DT WLS 1-W (white) 66230 DT WLS 1-LA (light almond)

Certifications

105 x 44.1 x 45.1 mm, 4.13 x 1.74 x 1.78 in, (LxWxD) 5 years C-UL-US Listed, RoHS compliant, California Compliant

The typical application is for small offices, conference rooms and break rooms. For best performance use this sensor in enclosed spaces no larger than 20’ x 16’. Key Features: • •

• • • • • • •

PIR & 40 kHz ultrasonic wall switch occupancy sensor Trigger mode settings enable what sensing technologies are used to initially turn the load ON and what technologies are used to keep the load ON Adjustable ultrasonic reach setting from 25% to 100% Line voltage lighting control (120/230/277 VAC, 50/60 Hz) 180° coverage pattern Manual ON or Automatic ON option Light level feature keeps lights off when sufficient daylight is present Mounts to a single-gang NEMA-style, standard switch box & decorator-style wall plate by others “Switch Link” communication allows for up to 4 sensors to be grouped together

Passive Infrared Ultrasonic

21 Ft Minor Motion 54 Ft Tangential

8 - 200 ffc

• • •

IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected Visible alert feature provides a momentary OFF/ON blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button

Line Voltage

IQ/Test, 5, 15, 30 Min

www.steinel.net


DT WLS 1 Dual Technology Wall Switch Occupancy Sensor Wiring

WLS 1 (Master / Master) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line Neutral

WLS 1 Basic Wiring

Line (Black) Neutral (White) Line

Line (Black) Neutral (White)

Line (Black)

Neutral

Neutral (White) Red (Load)

Load

Load

Red (Load)

Yellow (Switch Link)

Yellow Ground (Green)

Red (Load)

Load

Ground (Green) Ground Ground (Green)

Ground

Yellow (Switch Link)

WLS 1 (Master / Slave) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line Neutral Line (Black) Neutral (White)

Line (Black) Neutral (White) Red (Load)

Red (Load)

Load

Yellow (Switch Link) Ground (Green)

Component

Yellow Ground (Green)

Ground

Service Mode (ON)

Visible Alert (ON)

Audible Alert (ON)

Walk Through (ON)

Not Used

Trigger Mode

Relay 1 (Manual ON)

Setting ON/OFF button

Time Delay

Trigger Mode Factory Setting

Ultrasonic transducers PIR lens

4

5

6

7

8

9

10 Service Mode (OFF)

3

Visible Alert (OFF)

2

Audible Alert (OFF)

1

Walk Through (OFF)

Ultrasonic sensitivity adjustment trimpot DIP switches

Relay 1 (Automatic ON)

ON OFF

1

2

Both

Either

Either

OFF

OFF

Option A

PIR

Either

Either

OFF

ON

Option B

PIR

PIR

PIR

ON

OFF

Option C

Both

Both

Both

ON

ON

Time Delay

8

9

IQ / Test

OFF

OFF

5 Minutes

OFF

ON

15 Minutes

ON

OFF

30 Minutes

ON

ON

The sensors ultrasonic sensitivity and reach is adjusted with a trim potentiometer (dial). The left stop is minimum 25% (counter clockwise) the right stop is maximum 100% (clockwise).

Coverage

54

54

48

48

42

42 12

18

24

30

36

42

48

48

42

36

30

30

24

24

18

18

12

12

36

18

12

24

36

42

24

18

12

18

30

48

48

30

18

12

24

24

18

30

30

42

36

36

24

36

42

30

42

36

48

48

Initial Maintain Retrigger Occupancy Occupancy Occupancy

12

12

12

12

18

24

18

30

24

36

42

30

48

36

42

48

Ultrasonic Tangential and Radial Coverage Ultrasonic Minor Motion Coverage

PIR Tangential Coverage PIR Radial Coverage PIR Minor Motion Coverage

Ordering Information Color

Part #

Relays

DT WLS 1-W

Model

White

66220

1

DT WLS 1-LA

Light Almond

66230

1

DT WLS 2-W

White

66250

2

DT WLS 2-LA

Light Almond

66260

2

www.steinel.net

(800) 852-4343

Technology

Coverage

Voltage

PIR & 40 kHz Ultrasonic

180°

120/230/277 VAC

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01505-1


DT WLS 2 Dual Technology Dual Relay Wall Switch Occupancy Sensor Project Name: Location: 66250

66260

DT WLS 2 Specifications ifi ti Item No. Voltage Mounting Load Rating (Per Relay)

Sensing Technology

The DT WLS 2 is a line voltage, two relay, Dual Technology (PIR & ultrasonic) wall switch occupancy sensor intended to control bi-level lighting in commercial spaces. The combination of both technologies enhances occupancy detection in difficult applications. DIP switch adjustable technology options to initiate the load ON and maintain the load ON with either or both technologies. The hold OFF photocell daylight option will keep the lighting load OFF when the light level is greater than the threshold level setting. The convenient “Switch Link” feature enables up to four sensors to link together for pier to pier grouping achieving expanded detection zones and multiway switching.

Time Setting Light Level Setting Environment

single-gang NEMA-style switch box (standard switch box) & decorator-style wall plate by others 0-800 watts @ 120/230/277 VAC, 50/60 Hz tungsten, magnetic or electronic ballast • 1/6 hp 0-600 watts @ 120/230/277 VAC, 50/60 Hz CFL or LED electronic ballasts C d 132 μF max. 40 kHz ultrasonic & passive infrared IQ/Test, 5, 15, 30 minutes 80 - 2000 lux / 8 - 200 fc IP20 rated, 0°C to +40°C, 32°F to +104°F minor motion: max. max. radially: max. tangentially: max.

8 x 8 m (64 sq.m.) 18 x 12 ft (216 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.)

PIR Coverage at 1.2 m / 4 ft Mounting Height

minor motion: max. max. radially: max. tangentially: max.

6.5 x 5.5 m (36 sq.m.) 21 x 18 ft (378 sq.ft.) 7 m (77 sq.m.) 24 ft (904 sq.ft.) 20 m (628 sq.m.) 54 ft (4,500 sq.ft.)

Warranty

The typical application is for bi-level switching in small offices, conference rooms or break rooms. For best performance use this sensor in enclosed spaces no larger than 20’ x 16’.

120/230/277 VAC, 50/60 Hz

Ultrasonic Coverage at 1.2 m / 4 ft Mounting Height

Dimensions

Applications

66250 DT WLS 2-W (white) 66260 DT WLS 2-LA (light almond)

Certifications

105 x 44.1 x 45.1 mm, 4.13 x 1.74 x 1.78 in (LxWxD) 5 years C-UL-US Listed, RoHS compliant, California Compliant

Key Features: • •

• • • • • • • •

PIR & 40 kHz ultrasonic wall switch occupancy sensor Trigger mode settings enable what sensing tecnolgies are used to initially turn the load ON and what technologies are used to keep the load ON Adjustable ultrasonic reach setting from 25% to 100% Bi-level load switching (2 relays) Line voltage lighting control (120/230/277 VAC, 50/60 Hz) 180° coverage pattern Manual ON or Automatic ON option Light level feature keeps lights OFF when sufficient daylight is present Mounts to a single-gang NEMA-style, standard switch box & decorator-style wall plate by others “Switch Link” communication allows for up to 4 sensors to be grouped together

Passive Infrared Ultrasonic

21 Ft Minor Motion 54 Ft Tangential

8 - 200 ffc

• • •

IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected Visible alert feature provides a momentary OFF/ON blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button

Line Voltage

IQ/Test, 5, 15, 30 Min

www.steinel.net


DT WLS 2 Dual Technology Dual Relay Wall Switch Occupancy Sensor Wiring

WLS 2 (Master / Master) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line Neutral

WLS 2 Basic Wiring Line Neutral

Line 1 (Black) Line 2 (Blue) Neutral (White)

Load

Red (Load 1)

Load

Load

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Brown (Load 2)

Load Ground

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Load Load Yellow (Switch Link)

Yellow Ground (Green)

Ground (Green)

Ground (Green)

Ground

Yellow (Switch Link)

WLS 2 (Master / Slave) Three-way Wiring - up to maximum 4 sensors can be grouped via "Switch Link" Line Neutral

Components

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2)

Load Load

Line 1 (Black) Line 2 (Blue) Neutral (White) Red (Load 1) Brown (Load 2) Yellow

Yellow (Switch Link) Ground (Green)

ON/OFF button relay 1

Ground (Green)

Ground

ON/OFF button relay 2

Time Delay

Service Mode (ON)

Visible Alert (ON)

Walk Through (ON)

Audible Alert (ON)

Ultrasonic sensitivity adjustment trimpot DIP switches

Relay 2 (Manual ON)

Trigger Mode

Relay 1 (Manual ON)

Setting Trigger Mode Factory Setting

4

5

6

7

Audible Alert (OFF)

Visible Alert (OFF)

8

9

10 Service Mode (OFF)

3

Walk Through (OFF)

PIR lens

2

Relay 2 (Automatic ON)

1

Ultrasonic transducers

Relay 1 (Automatic ON)

ON OFF

1

2 OFF

Both

Either

Either

OFF

Option A

PIR

Either

Either

OFF

ON

Option B

PIR

PIR

PIR

ON

OFF

Option C

Both

Both

Both

ON

ON

Time Delay

8

9

IQ / Test

OFF

OFF

5 Minutes

OFF

ON

15 Minutes

ON

OFF

30 Minutes

ON

ON

The sensors ultrasonic sensitivity and reach is adjusted with a trim potentiometer (dial). The left stop is minimum 25% (counter clockwise) the right stop is maximum 100% (clockwise).

Coverage

54

54

48

48 12

12

18

24

30

36

42

48

48

PIR Tangential Coverage PIR Radial Coverage PIR Minor Motion Coverage

42

36

30

30

24

24

18

18

12

12

24

36

18

18

12

18

36

42

24

18

12

24

24

30

48

48

30

30

18

30

24

36

42

36

42

30

36

36

42

42

42

48

48

Initial Maintain Retrigger Occupancy Occupancy Occupancy

12

12

12

12

18

24

18

30

24

36

42

30

48

36

42

48

Ultrasonic Tangential and Radial Coverage Ultrasonic Minor Motion Coverage

Ordering Information Color

Part #

Relays

DT WLS 1-W

Model

White

66220

1

DT WLS 1-LA

Light Almond

66230

1

DT WLS 2-W

White

66250

2

DT WLS 2-LA

Light Almond

66260

2

www.steinel.net

(800) 852-4343

Technology

Coverage

Voltage

PIR & 40 kHz Ultrasonic

180°

120/230/277 VAC

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01506-1


IS Series Ceiling & wall mount occupancy sensors The high performance IS Series commercial occupancy sensors utilize pasive infrared technology, with multiple pyro arrangements and unique lens design to provide up to 1416 switching zones. The application specific detection patterns provide 360°, 180° and linear (hallway) coverage capabilities.


IS 3360-24 Ceiling Mount Occupancy Sensor Project Name: Location:

IS 3360-24 Specifications Item No.

Voltage Mounting Sensing Technology

61133 white 61141 black decorative cover 61142 inox decorative cover 24 VDC, 12 mA ceiling passive infrared (PIR)

Time Delay Setting

5 seconds to 15 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors Lens Design

IP20 rated, -4°F to +122°F, -20°C to +50°C 360° horizontal, 180° vertical, up to 25 ft radial reach, up to 130 ft tangential reach 3 dual element infrared pyroelectric detectors 1416 switching zones, 11 detection levels

Dimensions 3.74 x 3.74 x 2.56 in, (LxWxD) 95 x 95 x 65 mm, Warranty Certifications

The IS 3360-24 is part of the STEINEL family of high performance commercial occupancy sensors. With 360° of uninterrupted coverage, the IS 3360-24 provides exceptional lighting control in a wide range of spaces.

Applications

C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features: • •

IS 3360-24 sensors are passive infrared and respond to heat radiated from human body motion. They mount on a ceiling and turn lighting ON either automatically with occupancy or manually using a low voltage wall switch and the manual on mode of a STEINEL power pack. After a period of time where no occupancy has been detected, the sensor switches lighting OFF.

5 years

• • •

360° coverage with up to 25 ft radial reach and 130 ft tangential reach Shrouds allow users to easily customize the coverage area; the moving lens (mechanical adjustment) fine tunes coverage even further 3 pyroelectric detectors with 1416 switching zones provides highly accurate small motion detection Automatically adjusts to temperature changes keeping sensitivity and coverage consistent The hold off light level feature allows lighting to remain off during daylight regardless of occupancy. User-friendly “teach mode” automatically sets the daylight level, saving time with commissioning.

Ceiling mount applications where 360° coverage is needed, open office spaces, conference rooms, lobbies.

Voltage

Passive Infrared Technology

360˚ Coverage Max 60 Ft

IP20 Rated

Mounting

www.steinel.net


IS 3360-24 Ceiling Mount Occupancy Sensor Coverage

NEUTRAL

8.2 ft 2.5 m

Wiring

LOAD LINE VOLTAGE SWITCH

HOT WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

65 ft 20 m 24VDC Occupancy Sensor BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

Model# TR100 Power Pack

65 ft 20 m

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

Momentary switch

The shaded area on the coverage pattern represents minor motion coverage. Minor motion coverage, typical for an ofďŹ ce environment, is 13 ft (4 m) radius.

Coverage Adjustment

Setting

Shrouds supplied with each unit allow users to adjust coverage as needed.

Mounting

.2-200 fc

5 sec.-15 min.

Threaded Nipple Locknut Ceiling Tile

Washer

Sensor

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01101-1


IS 3180-24 Wall Mount Occupancy Sensor Project Name: Location:

IS 3180-24 Specifications Item No.

Voltage Mounting Sensing Technology

61131 white 61141 black decorative cover 61142 inox decorative cover 61143 black corner wall bracket 61144 white corner wall bracket 24 VDC, 12 mA wall or ceiling passive infrared (PIR)

Time Delay Setting

5 seconds to 15 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors Lens Design

IP20 rated, -4°F to +122°F, -20°C to +50°C 180° horizontal, 90° vertical, up to 42 ft radial reach, up to 65 ft tangential reach 2 dual element infrared pyroelectric detectors 448 switching zones, 7 detection levels

Dimensions 3.74 x 3.74 x 2.56 in, (LxWxD) 95 x 95 x 65 mm, Warranty Certifications

The IS 3180-24 mounts on a wall and is designed to control a variety of building spaces. The sensor is part of the STEINEL family of high performance commercial occupancy sensors.

• • •

Applications Wall mount applications where 180° coverage is needed, classrooms, offices, conference rooms.

Voltage

Passive Infrared Technology

180° Coverage

C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features:

• IS 3180-24 sensors are passive infrared and respond to heat radiated from human body motion. They turn lighting ON either automatically with occupancy or manually using a low voltage wall switch and the manual on mode of a STEINEL power pack. After a period of time where no occupancy has been detected, the sensor switches lighting OFF.

5 years

180° coverage with up to 42 ft radial reach and up to 65 ft tangential reach Shrouds allow users to easily customize the coverage area; the moving lens (mechanical adjustment) fine tunes coverage even further 2 pyroelectric detectors with 448 switching zones provides sensitive motion detection Automatically adjusts to temperature changes keeping sensitivity and coverage consistent The hold off light level feature allows lighting to remain off during daylight regardless of occupancy. User-friendly “teach mode” automatically sets the daylight level, saving time with commissioning.

IP20 Rated

Mounting

www.steinel.net


IS 3180-24 Wall Mount Occupancy Sensor Wiring

Coverage

NEUTRAL

LOAD

66 ft 20 m

LINE VOLTAGE SWITCH HOT

6.6 ft 2m

24VDC Occupancy Sensor BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

20 m

20 m

6.5 ft 2m

Model# TR100 Power Pack

26-66 ft 8–20 m

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

26-66 ft 8-20 m

13-26 ft 4–8 m 8m

26 ft 8m

16 m

Momentary switch

The shaded area on the coverage pattern represents minor motion coverage with a 10 ft radius, typical for an office environment. The sensor has 2 coverage settings. The lens rotates to select the 8m max lens or the 20m max lens. There is additional adjustment by sliding the lens up or down.

Setting

Coverage Adjustment

.2-200 fc

5 sec.-15 min. Shrouds supplied with each unit allow users to adjust coverage as needed.

Wall or Ceiling Mount with Screws

Mounting Threaded Nipple Locknut Ceiling Tile

Washer

Sensor

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01102-1


IS 345-24 Corridor Occupancy Sensor Project Name: Location:

IS 345-24 Specifications Item No.

Voltage Mounting Sensing Technology

61134 white 61141 black decorative cover 61142 inox decorative cover 24 VDC, 12 mA ceiling passive infrared (PIR)

Time Delay Setting 5 seconds to 15 minutes Light Level Setting Environment Coverage Sensors Lens Design

.2-200 footcandles 2-2000 lux IP20 rated, -4°F to +122°F, -20°C to +50°C 180° horizontal, 45° vertical, up to 40 x 13 ft radial reach, up to 65 x 13 ft tangential reach 2 dual element infrared pyroelectric detectors 280 switching zones, 5 detection levels

Dimensions 3.74 x 3.74 x 2.56 in (LxWxD) 95 x 95 x 65 mm Warranty Certifications

With a unique, specially designed detection lens, the IS 345-24 occupancy sensor is ideal for controlling lights in long corridors or aisleways. The sensor is part of the STEINEL family of high performance commercial occupancy sensors. IS 345-24 sensors are passive infrared and respond to heat radiated from human body motion. They mount on a ceiling and turn lighting ON either automatically with occupancy or manually using a low voltage wall switch and the manual on mode of a STEINEL power pack. After a period of time where no occupancy has been detected, the sensor switches lighting OFF. Applications

5 years C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features: • •

• • •

Coverage up to 40 ft radial reach and 65 ft tangential reach Shrouds allow users to easily customize the coverage area; the moving lens (mechanical adjustment) fine tunes coverage even further 2 pyroelectric detectors with 280 switching zones provides sensitive motion detection for corridors Automatically adjusts to temperature changes keeping sensitivity and coverage consistent The hold off light level feature allows lighting to remain off during daylight regardless of occupancy. User-friendly “teach mode” automatically sets the daylight level, saving time with commissioning.

Corridors and ceiling mount applications where hallway coverage is needed.

Voltage

Passive Infrared Technology

Corridor Coverage

IP20

Mounting

www.steinel.net


IS 345-24 Corridor Occupancy Sensor Settings

Wiring

NEUTRAL

LOAD LINE VOLTAGE SWITCH

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

HOT

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

.2-200 fc

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

Model# TR100 Power Pack

24VDC Occupancy Sensor

5 sec.-15 min.

Mounting

Threaded Nipple Locknut Ceiling Tile

Momentary switch

Washer

Coverage

9.8 ft 3m

Sensor

33 ft 10 m

13 ft 4m

33 ft 10 m

Coverage Adjustment

Shrouds supplied with each unit allow users to adjust coverage as needed.

The shaded area on the coverage pattern represents radial coverage. Slight coverage adjustment to the left or right of the aisle is possible by sliding the lens in the direction that additional coverage is desired.

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01103-1


IS D360-24 Ceiling Mount Occupancy Sensor Project Name: Location:

IS D360-24 Specifications Item No. Voltage Mounting Sensing Technology

5 seconds to 20 minutes .2-200 footcandles 2-2000 lux

Sensors

IP20 rated, -4°F to +122°F, -20°C to +50°C 360° with 180° angle of aperture, up to 13 ft (4 m) radial reach, up to 26 ft (8 m) tangential reach 3 dual element infrared pyroelectric detectors

Lens Design

720 switching zones, 10 detection levels

Dimensions (LxWxD)

3.23 x 2.01 in 82 x 51 mm

Warranty Certifications

5 years C-UL-US Listed, RoHS Compliant UL 2043 Plenum Rated CA Compliant

Key Features: • • • • •

Applications

passive infrared (PIR)

Light Level Setting

Coverage

The sensor is passive infrared and responds to heat radiated from human body motion. They mount on a ceiling and turn lighting ON either automatically with occupancy or manually using a low voltage wall switch and the manual on mode of a STEINEL power pack. After a period of time where no occupancy has been detected, the sensor switches lighting OFF.

ceiling mounts to standard MR16 fitting frame

Time Delay Setting

Environment

The IS D360-24 is a highly sensitive ceiling mount occupancy sensor for indoor use.

61136 24 VDC, 19 mA

360° coverage with up to 13 ft (4 m) radial reach and 26 ft (8 m) tangential reach Snap-on shrouds allow users to easily customize the coverage area 3 pyroelectric detectors with 720 switching zones provides highly accurate small motion detection Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy

Architecturally pleasing recessed ceiling mount for offices, conference rooms, vestibules, break rooms and a plenum areas.

Voltage

Passive Infrared Technology

360° Coverage

IP20 Rated

Mounting

www.steinel.net


IS D360-24 Ceiling Mount Occupancy Sensor Coverage

Wiring NEUTRAL

26 ft

LOAD

26 ft

LINE VOLTAGE SWITCH HOT WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

26 ft

26 ft

Model# TR100 Power Pack

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

24VDC Occupancy Sensor

26 ft

With a mounting height of 8 ft (2.5 m), the maximum reach of the sensor is 26 ft (8 m). Minor motion coverage, typical for an office environment, is 13 ft (4 m) radius. Coverage may vary depending on mounting height and environmental conditions.

Coverage Adjustment 26 ft

26 ft

Momentary switch

Settings 13 ft

13 ft

13 ft 13 ft

Shrouds, supplied with each unit, snap in place, allowing users to adjust coverage as needed.

Mounting 1 - Fitting frame 2 - Catch 3 - Switching module 4 - Sensor module 5 - Shroud 6 - Securing spring 7 - Light level setting 8 - Time delay setting

Light level and time delay settings are under the sensor module.

1

1

1

3 8 2

6

7

.2 – 200 fc

1

4

1

4 1

5 4 5 approx. 5 sec. – 20 min.

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01104-1


Photocell Control Sight lighting controller The STEINEL NM 5000-2-24 controller is the ideal choice for controling site lighting including signage and entryway lighting without the additional need for timed control. The controller measures ambient brightness and automatically switch lights ON at dusk and OFF as selected by the night economy mode. The optional morning setting allows lights to turn on in the morning between approximately 4:00 and 5:00 am and remain on until the set brightness level is achieved.


NM 5000-2-24 Light Level Controller Project Name: Location:

NM 5000-2-24 Specifications Item No. Voltage Mounting Light Level Setting Environment

Dimensions (LxWxD) Warranty Certifications

The NM 5000-2-24 light level controller switches lighting on and off automatically based on light levels. The controller works with a STEINEL power pack and functions by measuring ambient brightness. It automatically switches lights ON at dusk and OFF as programmed with the various switching options.

24 VDC, 15 mA ceiling or wall .05-100 footcandles .5-1000 lux IP20 rated -4°F to +122°F -20°C to +50°C 3.74 x 3.74 x 1.64 in 95 x 95 x 41.5 mm 5 years C-UL-US Listed RoHS Compliant

Key Features: • • • •

Applications

62151 white 62155 black decorative cover

Easy pushbutton light level setting Night economy mode and morning ON/OFF setting ease product commissioning Night economy mode automatically turns lights off at times of night when lighting is not needed Morning setting allows lights to turn on in the morning between approximately 4:00 and 5:00 am and remain on until the set brightness level is achieved

Applications that include business signs, corridors, vestibules, office areas, entrances and garages.

Voltage

IP20 Rated

Mounting

Settings

0.05 - 100 fc

www.steinel.net


NM 5000-2-24 Light Level Controller Controls and Settings

Wiring

Neutral

Load Line Voltage Switch

White (Neutral) Black (Hot) Red (Relay) Red (Relay)

Hot

24 VDC

Model# TR100 Power Pack

Blue (Control) Black (-24VDC) Red (+24VDC) Gray (Momentary Switch)

Blue (Control) Black (-24VDC) Red (+24VDC)

NM 5000-2-24 Daylight Sensor

Momentary Switch

.05 - 100 fc (Load 1 controlled by occupancy sensor only) Neutral Load 1 Line Voltage Switch

24 VDC NM 5000-2-24 Daylight Sensor

Blue (Control) Black (-24VDC) Red (+24VDC) Gray (Momentary Switch) Yellow/Red (Normally Open) Yellow (Relay Common) Yellow/Black (Normally Closed) Orange (Override On) Brown (Override Off)

Model# TR150 Power Pack

Blue (Control) Black (-24VDC) Red (+24VDC)

24 VDC Occupancy Sensor Blue (Control) Black (-24VDC) Red (+24VDC)

White (Neutral) Black (Hot) Red (Relay) Red (Relay)

Hot

1 - Back housing 2 - Front housing 3 - Decorative cover 4 - Light level programming button 5 - Morning ON/OFF setting 6 - Night economy mode setting

Product Overview & Mounting

Threaded nipple Locknut Ceiling tile

Washer

(Load 2 controlled by occupancy and daylight sensors) Neutral

Load 2 Line Voltage Switch

White (Neutral) Black (Hot) Red (Relay) Red (Relay)

Hot

Model# TR150 Power Pack

www.steinel.net

Blue (Control) Black (-24VDC) Red (+24VDC) Gray (Momentary Switch) Yellow/Red (Normally Open) Yellow (Relay Common) Yellow/Black (Normally Closed) Orange (Override On) Brown (Override Off)

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-02101-1


Power Packs Lighting and receptical control The TR 100 and TR 150 are full-featured power packs that provide Class 2 power suitable for parallel connection to STEINEL low voltage sensors and other control devices. The power packs switch load(s) on and off in response to signals from controls and contain a Mode Switch to select either manual ON or automatic ON operation. In manual ON mode, occupants operate a low voltage momentary switch to turn lights ON. The TR 150 includes force ON and force OFF control inputs allowing for integration with a building automation system for time of day control or load shed applications and contains an isolated relay for use with HVAC controls and other low voltage devices.


TR 100 Power Pack Project Name: Location:

TR 100 Specifications Item No.

120/230/277 VAC, 50/60 Hz

Output

24 VDC +/- 5% 250 mA (class 2)

Load

Environment Dimensions (LxWxD) Threaded Nipple Dimensions Warranty Certifications

The TR 100 is a full featured power pack that provides power to STEINEL low voltage occupancy sensors and other control devides. They are Class 2 output power supplies, suitable for parallel interconnection. The power packs switch the load(s) ON and OFF in response to signals from the control devices. Each power pack contains a Mode Switch to select either manual ON or automatic ON operation. In manual ON mode, occupants operate a low voltage momentary switch to turn lights ON. All wires have UL Style 1659, 250°C, 600V insulation: • 18 AWG: Black for Line and White for Neutral • 12 AWG: two Red wires for normally open dry contact from the 20A relay • 22 AWG: 4 low voltage conductors: Red (+24VDC), Black (-24VDC), Blue (Control Input), Gray (Momentary Switch Input)

Voltage

UL 2043 Plenum Rated

IP 20 Rated

63101

Voltage

20 A @ 120/230/277 VAC 50/60 Hz - ballast and incandescent load 1 hp @ 120-240 VAC, 50/60 Hz 15 A @120 VAC, 50/60 Hz - receptacle load IP20 rated, -4°F to +130°F, -20°C to +55°C 2.4 x 3.2 x 1.5 in 60 x 81 x 39 mm .83 x .83 in 21 x 21 mm 5 years C-UL-US Listed RoHS Compliant, UL 2043 Plenum Rated

Key Features: • • • • • • •

Convenient mode switch selects either manual ON or automatic ON operation LED status indicator Switching is performed at, or close to, the zero-cross of the AC waveform in order to improve relay performance 1/2 inch threaded nipple and two lock nuts are used to secure to a standard 1/2” knockout Low voltage momentary switch input allows for manual control in automatic or manual mode Switching Power Supply provides up to 250mA of 24VDC to low voltage controls 15 A receptical load control rated

Load

Operating Modes

www.steinel.net


TR 100 Power Pack Low Voltage 3-Way Wiring

Wiring

NEUTRAL

NEUTRAL

LOAD

LOAD

Symbol List LINE VOLTAGE SWITCH

Normally Open Momentary Contact Switch

HOT WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

Model# TR100 Power Pack

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

24VDC Occupancy Sensor

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

24VDC Occupancy Sensor

Model# TR100 Power Pack

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

HOT

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

Momentary switch

Line Voltage 3-Way Wiring

Two Stage Multi Level 3-Way Switching

NEUTRAL

Load 1 - Auto ON by sensor / Auto OFF by sensor or switch NEUTRAL

LOAD

LOAD 1

Traveler Wires

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

Model# TR100 Power Pack

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

24VDC Occupancy Sensor

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

24VDC Occupancy Sensor

3-Way Switch

Model# TR100 Power Pack

3-Way Switch 24VDC Occupancy Sensor

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH)

GRAY (MOMENTARY SWITCH)

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

HOT HOT

Load 2 - Manual ON only by switch / Auto OFF by sensor or switch NEUTRAL

LOAD 2

Product Overview & Mounting RED (RELAY) RED (RELAY)

WHITE (NEUTRAL) BLACK (HOT)

HOT

Model# TR100 Power Pack

Two lock nuts

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

1/2 inch threaded chase nipples

GRAY (MOMENTARY SWITCH)

Upon occupancy, lights (Load 1) attached to Power Pack (set to Auto ON) will illuminate automatically while lights (Load 2) attached to Power Pack (set to Manual ON) require the occupant to turn the lights on manually by means of a low voltage switch. All lights can be turned off manually by a low voltage switch or automatically by an occupancy sensor(s).

www.steinel.net

The TR 100 power pack mounts to a junction box with 1/2 inch knockouts.

Line voltage wires

(800) 852-4343

Model# TR100 Power Pack

LED status indicator

9051 Lyndale Avenue South, Bloomington, MN 55420

Low voltage wires

Manual/automatic mode switch

M-03101-1


TR 150 Power Pack Project Name: Location:

TR 150 Specifications Item No.

120/230/277 VAC, 50/60 Hz

Output

24 VDC +/- 5% 250 mA (class 2)

Load

Isolated Relay Environment Dimensions (LxWxD) Threaded Nipple Dimensions Warranty Certifications

The TR 150 is a full featured power pack with an isolated relay that provides power to STEINEL low voltage occupancy sensors and other control devides. They are Class 2 output power supplies, suitable for parallel interconnection. The power packs switch the load(s) ON and OFF in response to signals from the control devices. Each power pack contains a Mode Switch to select either manual ON or automatic ON operation. In manual ON mode, occupants operate a low voltage momentary switch to turn lights ON.

Voltage

UL 2043 Plenum Rated

IP 20 Rated

20 A @ 120/230/277 VAC 50/60 Hz - ballast and incandescent load 1 hp @ 120-240 VAC, 50/60 Hz 15 A @120 VAC, 50/60 Hz - receptacle load Single pole, double-throw with NO, NC and common outputs; rated 1 A @ 30 VAC/VDC IP20 rated, -4°F to +130°F, -20°C to +55°C 3.2 x 2.4 x 1.5 in 81 x 60 x 39 mm .83 x .83 in 21 x 21 mm 5 years C-UL-US Listed, RoHS Compliant, UL 2043 Plenum Rated

Key Features: • • • •

• All wires have UL Style 1659, 250°C, 600V insulation: • 18 AWG: Black for Line and White for Neutral • 12 AWG: two Red wires for normally open dry contact from the 20A relay • 22 AWG: 9 low voltage conductors: Red (+24VDC), Black (-24 VDC), Blue (Control Input), Orange ( Force On), Brown (Force Off), Gray (Momentary Switch Input), Yellow (Isolated Relay Common), Yellow with Red Stripes (Normally Open Isolated Relay), Yellow with Black Stripes (Normally Closed Isolated Relay)

63205

Voltage

• • • •

Convenient mode switch selects either manual ON or automatic ON operation LED status indicator Built-in isolated relay for use with HVAC controls and other low voltage devices Force on and force off control inputs allow for integration with a building automation system for time of day control or load shed applications. Switching is performed at, or close to, the zero-cross of the AC waveform in order to improve relay performance 1/2 inch threaded nipple and two lock nuts are used to secure to a standard 1/2” knockout Low voltage momentary switch input allows for manual control in automatic or manual mode Switching Power Supply provides up to 250mA of 24VDC to low voltage controls 15 A receptical load control rated

Load

Isolated Relay

www.steinel.net


TR 150 Power Pack Low Voltage 3-Way Wiring

Wiring NEUTRAL

NEUTRAL

LOAD

LOAD

LINE VOLTAGE SWITCH HOT

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH) YELLOW/RED (NORMALLY OPEN)

Model# TR150 Power Pack

24VDC Occupancy Sensor

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

24VDC Sensor

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

HOT

BLUE (CONTROL) BLACK (-24VDC)

Model# TR150 Power Pack

Isolated Relay NORMALLY OPEN

YELLOW (RELAY COMMON) YELLOW/BLACK (NORMALLY CLOSED) ORANGE (OVERRIDE ON) BROWN (OVERRIDE OFF)

RED (+24VDC) GRAY (MOMENTARY SWITCH)

RELAY COMMON NORMALLY CLOSED

YELLOW/RED (NORMALLY OPEN) YELLOW (RELAY COMMON) YELLOW/BLACK (NORMALLY CLOSED) ORANGE (OVERRIDE ON) BROWN (OVERRIDE OFF)

Symbol List

Line Voltage 3-Way Wiring

Normally open momentary contact switch Building Management System

Maintained contact switch

NEUTRAL

LOAD

Two Stage Multi Level 3-Way Switching HOT

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

BLUE (CONTROL)

24VDC Occupancy Sensor

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

HOT

BLACK (-24VDC) RED (+24VDC)

Model# TR150 Power Pack

3-Way Switch

3-Way Switch

24VDC Occupancy Sensor BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC)

LOAD 1

24VDC Occupancy Sensor

Traveler Wires

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

NEUTRAL

BLUE (CONTROL) BLACK (-24VDC) RED (+24VDC) GRAY (MOMENTARY SWITCH) YELLOW/RED (NORMALLY OPEN)

Model# TR150 Power Pack

YELLOW (RELAY COMMON) YELLOW/BLACK (NORMALLY CLOSED) ORANGE (OVERRIDE ON) BROWN (OVERRIDE OFF)

GRAY (MOMENTARY SWITCH) YELLOW/RED (NORMALLY OPEN) YELLOW (RELAY COMMON) YELLOW/BLACK (NORMALLY CLOSED) ORANGE (OVERRIDE ON) BROWN (OVERRIDE OFF)

Product Overview & Mounting

Load 2 - Manual ON only by switch/ Auto OFF by sensor or switch

NEUTRAL

LOAD 2

WHITE (NEUTRAL) BLACK (HOT) RED (RELAY) RED (RELAY)

HOT

The TR 150 power pack mounts to a junction box with 1/2 inch knockouts.

Line voltage wires

BLUE (CONTROL) BLACK (-24VDC)

Model# TR150 Power Pack

Two lock nuts

RED (+24VDC) GRAY (MOMENTARY SWITCH) YELLOW/RED (NORMALLY OPEN) YELLOW (RELAY COMMON) YELLOW/BLACK (NORMALLY CLOSED) ORANGE (OVERRIDE ON) BROWN (OVERRIDE OFF)

Upon occupancy, lights (Load 1) attached to Power Pack (set to Auto ON) will illuminate automatically while lights (Load 2) attached to Power Pack (set to Manual ON) require the occupant to turn the lights on manually by means of a low voltage switch. All lights can be turned off manually by a low voltage switch or automatically by an occupancy sensor(s).

www.steinel.net

(800) 852-4343

1/2 inch threaded chase nipples

Model# TR100 TR 150 Power Pack

LED status indicator

9051 Lyndale Avenue South, Bloomington, MN 55420

Low voltage wires

Manual/automatic mode switch

M-03201-1


High Bay Sensors High / Low bay occupancy based lighting control STEINEL’s HBS series of occupancy sensors provide world class detection in high and low bay applications. They utilizing multiple Pyro configurations coupled with application specific lens designs that provide up to 1416 switching zones of detection. IP20 and IP65 versions available in 120/230/277VAC, 50/60Hz. IP20 versions available in 347/480VAC, 60Hz.


HBS 300 360° High Bay Occupancy Sensor Project Name: Location:

HBS 300 Specifications Item No. Accessories

Voltage Load Rating Sensing Technology

64131 (indv. packaged) 64130 (bulk) 64304 LC4, Reduced Range Lens Cover 64305 LC5, 180° Half Moon Lens Cover 64307 EM1, Extender Module 120/230/277 VAC, 50/60 Hz 120 VAC: 0-800 watt ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt ballast passive infrared (PIR)

Time Delay Setting

15 seconds to 30 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors Lens Design

IP20 rated, -4°F to +122°F, -20°C to +50°C 360° up to 22 ft (6.7 m) radial reach, up to 60 ft (18.2 m) tangential reach 3 dual element infrared pyroelectric detectors 1416 switching zones

Dimensions 3.9 x 3.9 x 2.6 in, 99 x 99 x 66 mm, (LxWxD) nipple length .62 in (15.75 mm) Warranty Certifications

The HBS 300 High Bay Occupancy Sensor provides 360 degrees of occupancy based lighting control in high bay open area applications. The sensor performs at a wide range of mounting heights, up to 45 ft. The EM1 Extendor Module mounts directly to a high bay lighting fixture or junction box. With three highly sensitive pyroelectric detectors and a multi-segmented lens, the HBS 300 is able to achieve 1416 switching zones.

C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features: • • • • • •

Applications

5 years

360° coverage with up to 60 ft tangential reach Coverage area may be adjusted with plastic lens covers that snap to the front of the sensor 3 pyroelectric detectors with 1416 switching zones Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy Built-in surge protection with auto-reset

High bay open areas where 360 degree coverage is desired, such as in warehouses, distribution centers, gymnasiums, and loading docks.

Voltage

Passive Infrared Technology

360˚ Coverage Max 60 Ft

Fixture or Junction Box Mounting

0.2 - 200 fc

www.steinel.net


HBS 300 360° High Bay Occupancy Sensor Coverage 10 20 30 40

40 ft

Wiring

50 40

35 ft 35 ft 22 ft 22 ft

40 50

Typical mounting height is 8 to 45 ft. Maximum reach is 22 ft radial and 60 ft tangential. Coverage may vary depending on mounting height and environmental conditions.

Coverage Adjustment

Setting

Lens covers can be used to adjust the HBS 300 coverage as needed. The covers are plastic and snap to the front of a sensor.

Detection lens

ON

30 ft 30 ft 22 ft 22 ft

10 20 30 40

40 ft

10 20 30 40

Light level setting

Time delay DIP switch

Time

LC5

High Low

1 2 3 4

40 ft

Time

LC4 ON

35 ft

40 50 60

22 ft

High Low

teach mode

1 2 3 4

Time Delay DIP Switch 1

2

3

4

Time

ON

ON

ON

OFF

15 sec 1 min

ON

OFF

OFF

OFF

OFF

ON

ON

OFF

5 min

ON

OFF

ON

OFF

10 min

ON

ON

OFF

OFF

15 min

OFF

ON

OFF

OFF

20 min

OFF

OFF

ON

OFF

25 min

OFF

OFF

OFF

OFF

30 min

N/A

N/A

N/A

ON

override

LC4 reduced range lens cover

LC5 180° half moon lens cover

Factory setting is 15 minutes.

Mounting EM1 EM1

www.steinel.net

(800) 852-4343

The HBS 300 is mounted directly to a lighting fixture. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

9051 Lyndale Avenue South, Bloomington, MN 55420

M-04101-2


HBS 200 High Bay Occupancy Sensor Project Name: Location:

HBS 200 Specifications Item No. Accessories Voltage Load Rating Sensing Technology

64121 (indv. packaged) 64120 (bulk) 64301 LC1, Aisle Starter Lens Cover 64307 EM1, Extender Module 120/230/277 VAC, 50/60 Hz 120 VAC: 0-800 watt ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt ballast passive infrared (PIR)

Time Delay Setting

15 seconds to 30 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors Lens Design

IP20 rated, -4°F to +122°F, -20°C to +50°C 100 x 13 ft (30.48 x 3.96 m) linear detection 2 dual element infrared pyroelectric detectors 104 switching zones

Dimensions 3.9 x 3.9 x 2.72 in, 99 x 99 x 69.1 mm, (LxWxD) nipple length .62 in (15.75 mm) Warranty Certifications

The HBS 200 High Bay Occupancy Sensor provides occupancy based lighting control in high bay aisleway applications. The sensor performs at a wide range of mounting heights, up to 45 feet. It mounts directly to a high bay lighting fixture or junction box. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

• • •

• •

High bay aisleway areas such as in warehouses and distribution centers.

Passive Infrared Technology

Aisleway Coverage

C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features:

Applications

Voltage

5 years

Aisleway coverage with up to 100 ft linear detection Coverage area may be adjusted with LC1 aisle starter lens cover that snap to the front of the sensor 2 pyroelectric detectors with 104 switching zones provides superior aisleway detection over other single pyroelectric linear coverage highbay sensors Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy Built-in surge protection with auto-reset

Fixture or Junction Box Mounting

0.2 - 200 fc

www.steinel.net


HBS 200 High Bay Occupancy Sensor Coverage

50 ft 50 ft 53 ft 53 ft

Coverage may vary depending on mounting height and environmental conditions.

13 ft

10 20 30 40

40 ft

Wiring

radial tangential

Coverage Adjustment

Setting

ON

High Low

1 2 3 4

Light level setting

Time

Time delay DIP switch ON

LC1

High

10 20 30 40

Low

Teach mode

1 2 3 4

2

3

4

Time

ON

ON

ON

OFF

15 sec

ON

OFF

OFF

OFF

1 min

OFF

ON

ON

OFF

5 min

ON

OFF

ON

OFF

10 min

ON

ON

OFF

OFF

15 min

OFF

ON

OFF

OFF

20 min

OFF

OFF

ON

OFF

25 min

OFF

OFF

OFF

OFF

30 min

N/A

N/A

N/A

ON

override

radial tangential

Factory setting is 15 minutes.

Mounting EM1

www.steinel.net

(800) 852-4343

50 ft 53 ft

13 ft

Time Delay DIP Switch 1

40 ft

Time

Detection lens

The HBS 200 is mounted directly to a lighting fixture. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

9051 Lyndale Avenue South, Bloomington, MN 55420

LC1 aisle starter cover for HBS 200

M-04103-2


HBS 200 (347-480V) High Bay Occupancy Sensor Project Name: Location:

HBS 200 (347-480V) Specifications Item No. Voltage Load Rating

64123 64122 (bulk) 347/480 VAC, 60 Hz 120 VAC: 0-800 watt ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt ballast

Sensing Technology

5A electronic ballast load

Time Delay Setting

15 seconds to 30 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors Lens Design

IP20 rated, -4°F to +122°F, -20°C to +50°C 100 x 13 ft (30.48 x 3.96 m) linear detection 2 dual element infrared pyroelectric detectors 104 switching zones

Dimensions 3.9 x 3.9 x 2.72 in, 99 x 99 x 69.1 mm, (LxWxD) nipple length .62 in (15.75 mm) Warranty Certifications

The HBS 200 (347-480V) High Bay Occupancy Sensor provides occupancy based lighting control in high bay aisleway applications. The sensor performs at a wide range of mounting heights, up to 45 ft. It mounts directly to a high bay lighting fixture or junction box. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

• • • •

• •

High bay aisleway areas such as in warehouses, distribution and centers.

• •

Passive Infrared Technology

Aisleway Coverage

C-UL-US Listed, RoHS Compliant

Key Features:

Applications

Voltage

5 years

Aisleway coverage with up to 100 ft linear detection Easily upgradable to wireless control with the MF1-UL module Coverage area may be adjusted with LC1 aisle starter lens cover that snaps to the front of the sensor 2 pyroelectric detectors with 104 switching zones provides superior aisleway detection over other single pyroelectric highbay sensors Precision molded lens Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy Built-in surge protection with auto-reset

Fixture or Junction Box Mounting

www.steinel.net


HBS 200 (347-480V) High Bay Occupancy Sensor Wiring

Coverage 10 20 30 40

40 ft

Setting

50 ft 50 ft 53 ft 53 ft

Time

13 ft

Detection lens ON

High

radial tangential

Low 1 2 3 4

Light level setting

Time delay DIP switch

High

ON

Low

Teach mode

Coverage Adjustment LC1

1 2 3 4

10 20 30 40

1

2

3

4

Time

ON

ON

ON

OFF

15 sec

ON

OFF

OFF

OFF

1 min

OFF

ON

ON

OFF

5 min

ON

OFF

ON

OFF

10 min

ON

ON

OFF

OFF

15 min

OFF

ON

OFF

OFF

20 min

OFF

OFF

ON

OFF

25 min

OFF

OFF

OFF

OFF

30 min

N/A

N/A

N/A

ON

override

50 ft 53 ft

13 ft

Time Delay DIP Switch

40 ft

Time

Typical mounting height is 8 to 45 feet. Maximum reach is 22 feet radial and 60 feet tangential. Coverage may vary depending on mounting height and environmental conditions.

radial tangential

LC1 aisle starter cover for HBS 200 (347-480V) Note: When used with the MF1-UL wireless control module the minimum time delay is 35 seconds

Mounting EM1 EM1

www.steinel.net

(800) 852-4343

The HBS 200 (347-480V) is mounted directly to a lighting fixture. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

9051 Lyndale Avenue South, Bloomington, MN 55420

M-04104-2


HBS 300 (347-480V) 360° High Bay Occupancy Sensor Project Name: Location:

HBS 300 (347-480V) Specifications Item No. Accessories

Voltage Load Rating Sensing Technology

64133 (indv. packaged) 64132 (bulk) 64304 LC4, Reduced Range Lens Cover 64305 LC5, 180° Half Moon Lens Cover 64307 EM1, Extender Module 347/480 VAC, 60 Hz 5A electronic ballast load passive infrared (PIR)

Time Delay Setting

15 seconds to 30 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors

IP20 rated, -4°F to +122°F, -20°C to +50°C 360°, up to 22 foot (6.7 m) radial reach, up to 60 ft (18.2 m) tangential reach 3 dual element infrared pyroelectric detectors

Dimensions 3.9 x 3.9 x 2.6 in, 99 x 99 x 66 mm, (LxWxD) nipple length .62 in (15.75 mm) Warranty Certifications

The HBS 300 (347-480V) High Bay Occupancy Sensor provides 360 degrees of occupancy based lighting control in 347/480 VAC, 60Hz high bay open area applications. The sensor performs at a wide range of mounting heights, up to 45 feet. It mounts directly to a high/low bay lighting fixture or junction box. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture. With three highly sensitive pyroelectric detectors and a multi-segmented lens, the HBS 300 (347-480V) is able to achieve 1416 switching zones.

C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features: • • • • • • •

Applications

5 years

360° coverage with up to 60 ft tangential reach Coverage area may be adjusted with plastic lens covers that snap to the front of the sensor 3 pyroelectric detectors with 1416 switching zones provides better detection for high bay applications Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy User-friendly “teach mode” automatically sets the daylight level, saving time with commissioning. Built-in surge protection with auto-reset

High bay open areas where 360 degree coverage is desired, such as in warehouses, distribution centers, gymnasiums, and loading docks.

Voltage

Passive Infrared Technology

360˚ Coverage Max 60 Ft

Fixture or Junction Box Mounting

0.2 - 200 fc

www.steinel.net


HBS 300 (347-480V) 360° High Bay Occupancy Sensor Coverage 10 20 30 40

40 ft

Wiring

50 40

35 ft 35 ft 22 ft 22 ft

Typical mounting height is 8 to 45 ft. Maximum reach is 22 feet radial and 60 feet tangential. Coverage may vary depending on mounting height and environmental conditions.

40 50

Coverage Adjustment

Setting

Lens covers can be used to adjust the HBS 300 (347480V) coverage as needed. The covers are plastic and snap to the front of a sensor.

High

LC4

Low 1 2 3 4

Light level setting

Time delay DIP switch

Time

10 20 30 40 High

ON

LC5

30 ft 30 ft 22 ft 22 ft

10 20 30 40

40 ft

ON

40 ft

Time

Detection lens

35 ft

40 50

22 ft

Low

teach mode 1 2 3 4

Time Delay DIP Switch 1

2

3

4

Time

ON

ON

ON

OFF

15 sec 1 min

ON

OFF

OFF

OFF

OFF

ON

ON

OFF

5 min

ON

OFF

ON

OFF

10 min

ON

ON

OFF

OFF

15 min

OFF

ON

OFF

OFF

20 min

OFF

OFF

ON

OFF

25 min

OFF

OFF

OFF

OFF

30 min

N/A

N/A

N/A

ON

override

LC4 reduced range lens cover

LC5 180° half moon lens cover

Factory setting is 15 minutes.

Mounting EM1 EM1

www.steinel.net

(800) 852-4343

The HBS 300 (347-480V) is mounted directly to a lighting fixture. The EM1 Extender Module is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

9051 Lyndale Avenue South, Bloomington, MN 55420

M-04105-1


HBS 200-WL IP65 Wet Location Aisle Occupancy Sensor Project Name: Location:

HBS 200-WL Specifications Item No. Accessories Voltage Load Rating Sensing Technology

64124 64307 EM1 extender module 120/230/277 VAC, 50/60 Hz 120 VAC: 0-800 watt ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt ballast passive infrared (PIR)

Time Delay Setting

15 seconds to 30 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Environment Coverage Sensors Lens Design

IP65 rated, -4°F to +122°F, -20°C to +50°C 100 x 13 ft (30.48 x 3.96 m) linear detection 2 dual element infrared pyroelectric detectors 104 switching zones

Dimensions 5.54 x 5.54 x 2.98 in, 115.3 x 115.3 x 75.8 mm, (LxWxD) nipple length .58 in, 14.7 mm Warranty Certifications

The HBS 200-WL sensor provides effective lighting control in damp or wet locations. Coverage specifically designed for aisle occupancy detection. Can be used in a wide range of applications that require an IP65 rating. Best practice for unconditioned storage areas, warehouse aisles or any spaces requiring linear detection pattern.

Key Features:

The sensor performs at a wide range of mounting heights, up to 45 feet. It mounts directly to a lighting fixture or junction box. The EM1 Extender Module is recommended if the knockout at the end of a fixture is located greater than 1/2” from the bottom edge of the fixture.

• •

• • •

• •

5 years C-UL-US Listed, RoHS Compliant, CA Compliant

Aisleway coverage with up to 100 ft linear detection IP65 Wet location rated 2 pyroelectric detectors with 104 switching zones provides superior aisleway detection over other single pyroelectric highbay sensors Linear coverage Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy Built-in surge protection with auto-reset

Applications High bay wet location aisle applications such as unconditioned storage warehouses.

Voltage

Wet Location Rated Passive Infrared Technology

Aisleway Coverage

Fixture or Junction Box Mounting

0.2 - 200 fc

www.steinel.net


HBS 200-WL IP65 Wet Location Aisle Occupancy Sensor Coverage

Neutral

10 20 30 40

Hot

40 ft

Wiring

50 ft 50 ft 53 ft 53 ft

Coverage may vary depending on mounting height and environmental conditions.

13 ft

Line (Black) Neutral (White) Load (Red)

radial tangential

Coverage Adjustment

Setting

The HBS 300-WL or HBS 200-WL typically mount to a 1/2” knockout at the end of a high/low bay water tight fixture using an EM1 extender module. The sensor’s lens should be mounted below the bottom edge of the fixture. Slotted Cable gasket

Detection lens

Rubber gasket Fixture

EM1

Light level setting

Time

Time delay DIP switch ON

Chase nipple

High Low

Teach mode

1 2 3 4

Sensor

Time Delay DIP Switch 1

2

3

4

Time

ON

ON

ON

OFF

15 sec

ON

OFF

OFF

OFF

1 min

OFF

ON

ON

OFF

5 min

ON

OFF

ON

OFF

10 min

ON

ON

OFF

OFF

15 min

OFF

ON

OFF

OFF

20 min

OFF

OFF

ON

OFF

25 min

OFF

OFF

OFF

OFF

30 min

N/A

N/A

N/A

ON

override

The EM1 Extender Module is recommended for use with the HBS 300-WL and HBS 200-WL if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture. Pull the slotted cable gasket through the provided chase nipple until it snaps in to place creating a water tight seal.

Factory setting is 15 minutes.

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-04106-1


HBS 300-WL IP65 Wet Location 360° Occupancy Sensor Project Name: Location:

HBS 300-WL Specifications Item No. Accessories Voltage Load Rating Sensing Technology

120 VAC: 0-800 watt ballast, tungsten, 1/4 hp 230/277 VAC: 0-1200 watt ballast passive infrared (PIR) 15 seconds to 30 minutes .2-200 footcandles 2-2000 lux

Sensors

IP65 rated, -4°F to +104°F, -20°C to +40°C 360° up to 22 ft (6.7 m) radial reach, up to 60 ft (18.2 m) tangential reach 3 dual element infrared pyroelectric detectors

Lens Design

1416 switching zones

Dimensions (LxWxD)

5.54 x 5.54 x 2.86 in, 115.3 x 115.3 x 72.7 mm, nipple length .58 in (14.7 mm)

Warranty Certifications

The HBS 300-WL sensor provides effective lighting control in areas requiring a 360 degree occupancy detection pattern. Best practice for high/low bay open areas requiring IP65 wet location rating. Ideal for warehouses and general damp or wet unconditioned storage areas.

Key Features:

The sensor performs at a wide range of mounting heights, up to 45 ft. The EM1 Extendor Module mounts directly to a lighting fixture or junction box. With three highly sensitive pyroelectric detectors and a multi-segmented lens, the HBS 300-WL is able to achieve 1416 switching zones with best in class radial and tangential detection.

120/230/277 VAC, 50/60 Hz

Light Level Setting

Coverage

64307 EM1 extender module

Time Delay Setting

Environment

• • •

64134

5 years C-UL-US Listed, RoHS Compliant, CA Compliant

360° coverage with up to 60 ft tangential reach IP65 Wet location rated 3 pyroelectric detectors with 1416 switching zones provides better detection for high bay applications Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Light level feature allows lighting to remain off during daylight regardless of occupancy Built-in surge protection with auto-reset

Applications Open area wet location where 360 coverage is needed, such as unconditioned storage warehouses.

Voltage

Wet Location Rated Passive Infrared Technology

360˚ Coverage Max 60 Ft

Fixture or Junction Box Mounting

0.2 - 200 fc

www.steinel.net


HBS 300-WL IP65 Wet Location 360° Occupancy Sensor Coverage

Neutral

10 20 30 40

Hot

40 ft

Wiring

50 40

35 ft 35 ft 22 ft 22 ft

40 50

Line (Black) Neutral (White)

Typical mounting height is 8 to 45 ft. Maximum reach is 22 ft radial and 60 ft tangential. Coverage may vary depending on mounting height and environmental conditions.

Load (Red)

Mounting

Setting

The HBS 300-WL or HBS 200-WL typically mount to a 1/2” knockout at the end of a high/low bay water tight fixture using an EM1 extender module. The sensor’s lens should be mounted below the bottom edge of the fixture. Slotted Cable gasket

Detection lens

Rubber gasket Fixture

EM1

Light level setting

Time

Time delay DIP switch ON

Chase nipple

High Low

Teach mode

1 2 3 4

Sensor

Time Delay DIP Switch 1

2

3

4

Time

ON

ON

ON

OFF

15 sec

ON

OFF

OFF

OFF

1 min

OFF

ON

ON

OFF

5 min

ON

OFF

ON

OFF

10 min

ON

ON

OFF

OFF

15 min

OFF

ON

OFF

OFF

20 min

OFF

OFF

ON

OFF

25 min

OFF

OFF

OFF

OFF

30 min

N/A

N/A

N/A

ON

override

The EM1 Extender Module is recommended for use with the HBS 300-WL and HBS 200-WL if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture. Pull the slotted cable gasket through the provided chase nipple until it snaps in to place creating a water tight seal.

Factory setting is 15 minutes.

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-04107-1


EM1 Extender Module Project Name: Location:

EM 1 Specifications Item No. Environment Dimensions (LxWxD) Warranty Certifications

64307 IP20 rated, -4°F to +122°F, -20°C to +50°C 5.93 x 1.74 x 1.01 in, 150.62 x 44.20 x 25.65 mm 5 years C-UL-US Listed, RoHS Compliant

Left

Front

The EM 1 Extender Module is used with STEINEL high bay occupancy sensors. It is recommended if the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

Right

J-Box

Fixture EM 1

EM 1

High Bay Sensor

High Bay Sensor

Example of the EM 1 used to mount the HBS 300 high bay occupancy sensor to a fixture. Here, the knockout at the end of the fixture is located greater than 1/2” from the bottom edge of the fixture.

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-04306-1 www.steinel.net

Back


Outdoor Sensors Outdoor sensors for residential and commercial use STEINEL’s wide range of outdoor sensors offer the highest level of reliability and durability in harsh outdoor environments with a proven track record here in the USA. For over 20 years we have been the choice of contractors, specifiers and facility managers who demand the best in outdoor lighting controls. Models are available with and without lampholders and in configurations for either soffit or wall mount.


IS 360 Ceiling Mount Outdoor Occupancy Sensor Project Name: Location:

IS 360 Specifications Item No. Voltage

0-600 watt tungsten 0-300 watt ballast

Sensing Technology

passive infrared (PIR)

Mounting Light Level Setting Environment Coverage Sensors

• • • • • • •

Interior applications that includes vestibules and garages. Exterior applications that includes entryways, carports, balconies, building soffits.

• •

Passive Infrared Technology

360° Coverage

360° up to 40 foot reach (12.2 m) 3 dual element infrared pyroelectric detectors

Dimensions (LxWxD)

4.7 x 4.7 x 3.9 in 120 x 120 x 100 mm 5 years C-UL-US Listed, CSA Approved RoHS Compliant

Key Features:

Applications

Voltage

.2-200 footcandles, 2-2000 lux IP54 raintight rated, -4°F to +122°F, -20°C to +50°C

720 switching zones, 10 levels

Warranty

For unmatched coverage, the IS 360 incorporates three highly sensitive pyroelectric sensors that provide reliable, uninterupted 360 coverage.

10 seconds to 15 minutes ceiling

Lens Design

Certifications

The sensors are passive infrared and respond to heat radiated from moving persons or other heat-emitting objects (such as vehicles). They automatically turn lights on when presence is detected and off when a space is left vacant.

120 VAC, 60 Hz

Maximum Wattage

Time Delay Setting

The STEINEL IS 360 occupancy sensor is raintight for safe reliable operation indoors and out.

60261 white 60251 black

360° coverage with up to 40 ft reach 720 switching zones for highly accurate small motion detection Coverage area may be customized with supplied snap-on shrouds and through fine-tune rotation adjustment Precision molded lens is distortion free and watertight Detects motion directly beneath sensor for immediate detection Light level feature allows lighting to remain off during daylight regardless of occupancy Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Built in surge protection with auto-reset Raintight IP54 rated; suitable for interior or exterior use

IP54 Rated

Mounting

www.steinel.net


IS 360 Ceiling Mount Outdoor Occupancy Sensor Coverage

Wiring

40 ft 40 ft

NEUTRAL HOT Local OFF Switch (optional)

L O A D LINE (BLACK) NEUTRAL (WHITE) LOAD (RED)

40 ft

40 ft

40 ft

Typical mounting height is 8 to 12 ft The IS 360’s unique 180° angle of aperture enables the sensor to see straight out for greater coverage

Coverage Adjustment Fine tune coverage adjustment is possible by rotating the sensor housing.

Settings Time Delay

Light Level

40 ft

40 ft

Thumbdial adjustments for time delay and light level are located beneath the decorative cover 15 ft

Shrouds, supplied with each unit, snap in place, allowing users to adjust coverage as needed.

15 ft

15 ft

Controls

15 ft

Mounting plate Housing cover

Mounting The IS 360 mounts to a NEMA 4 inch watertight round J-box outdoors and a standard octagon 4 inch J-box indoors

Sensor housing (rotates for coverage adjustment) Coverage shroud Decorative ring (adjustments beneath)

www.steinel.net

(800) 852-4343

Detection lens

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01601-1


IS 240-120 Wall Mount Outdoor Occupancy Sensor Project Name: Location:

IS 240-120 Specifications Item No. Voltage Maximum Wattage Sensing Technology Time Delay Setting Mounting Light Level Setting Environment Coverage Sensors Lens Design

61621 white 61622 black 120 VAC, 60 Hz 0-600 watt tungsten, 0-300 watt ballast passive infrared (PIR) 10 seconds to 15 minutes wall .2-200 footcandles 2-2000 lux IP54 raintight rated, -4°F to +122°F, -20°C to +50°C 240° up to 40 ft reach (12.2 m) 2 dual element infrared pyroelectric detectors 304 switching zones, 9 levels

Dimensions 3.75 x 2.33 x 3.33 in (LxWxD) 95.25 x 59.2 x 84.6 mm Warranty Certifications

The STEINEL IS 240-120 occupancy sensor is intended for vertical mounting to any 1/2” threaded cover plate or knockout and is raintight for safe reliable operation indoors and out. The sensors are passive infrared and respond to heat radiated from moving persons or other heat-emitting objects (such as vehicles). They automatically turn lights on when presence is detected and off when a space is left vacant.

• • • • • •

Voltage

Passive Infrared Technology

240° Coverage

C-UL-US Listed, RoHS Compliant

Key Features:

Applications Interior applications such as corridors, vestibules, garages. Exterior applications such as entryways, carports, balconies and porches.

5 years

• •

240° coverage with up to 40 ft reach 304 switching zones Coverage area may be customized with supplied snap-on shrouds and through fine-tune rotation adjustment Precision molded lens is distortion free and watertight Light level feature allows lighting to remain off during daylight regardless of occupancy Automatically adjusts to temperature changes keeping sensitivity and coverage consistent Built in surge protection with auto-reset Raintight IP54 rated; suitable for interior or exterior use

IP54 Raintight Rated

0.2 - 200 fc

www.steinel.net


IS 240-120 Wall Mount Outdoor Occupancy Sensor Wiring

Coverage NEUTRAL HOT

40 ft

Local OFF Switch (optional)

L O A D

Typical mounting height is 8 to 12 ft

LINE (BLACK) NEUTRAL (WHITE) LOAD (RED)

40 ft

NEUTRAL HOT L O A D

L O A D

Coverage Adjustment Fine tune coverage adjustment is possible by rotating the sensor housing.

LINE (BLACK) NEUTRAL (WHITE) LOAD (RED)

LINE (BLACK) NEUTRAL (WHITE) LOAD (RED)

Local OFF Switch (optional)

40 ft

40 ft

15 ft

Setting

15 ft

Shrouds, supplied with each unit, snap in place, allowing users to adjust coverage as needed.

15 ft

Time Delay

Light Level

Mounting .2-200 fc

Standard junction box Nut

Thumbdial adjustments for time delay and light level are located beneath the decorative cover

Cover plate with 1/2 inch knockouts Gasket

Standard box installation

Controls Mounting plate Sensor housing (rotates for ďŹ ne tune coverage adjustment)

Decorative ring (adjustments beneath)

Coverage shroud

Detection lens

www.steinel.net

(800) 852-4343

Gasket

Watertight threaded cover plate

Watertight box installation

4 inch watertight box

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01101-1


HS 150, HS 300 Halogen Outdoor Sensor Light Project Name: Location:

HS 150, HS 300 Specifications Item No.

Voltage Maximum Wattage Sensing Technology Time Delay Setting Mounting Light Level Setting Environment Coverage Sensors

• • • • • •

Exterior locations include entryways, driveways, carports, patios and balconies.

• •

Passive Infrared Technology

240° Coverage

passive infrared (PIR) 10 seconds to 15 minutes wall .2-200 footcandles, 2-2000 lux P44 raintight rated, -40°F to +120°F, -40°C to +49°C 240° up to 40 foot reach (12.2 m) 2 dual element infrared pyroelectric detectors

Dimensions (LxWxD)

HS 150 8.5 x 6.2 x 6.7 in, 215 x 155 x 170 mm HS 300 9.5 x 8.3 x 7.4 in, 240 x 210 x 180 mm 5 years C-UL-US Listed, CSA Approved, RoHS Compliant

Key Features:

Applications

Voltage

HS 150: 150 watts HS 300: 300 watts

304 switching zones, 9 levels

Warranty

The sensors are passive infrared and respond to heat radiated from moving persons or other heat-emitting objects (such as vehicles). They automatically turn lights on when presence is detected and off when a space is left vacant.

120 VAC, 60 Hz

Lens Design

Certifications

The STEINEL HS 150 and HS 300 occupancy sensors mount on a wall and are raintight for safe reliable operation indoors and out.

63311 HS 150 white 63301 HS 150 black 63331 HS 300 white 63321 HS 300 black

240° coverage with up to 40 ft reach Lens provides 304 switching zones The floodlight tilts and swivels within a range of 150° vertically and 80° horizontally to achieve desired illumination Coverage area may be customized with supplied snap-on shrouds and through fine-tune rotation adjustment Precision molded lens is distortion free and watertight Light level feature allows lighting to remain off during daylight regardless of occupancy Built in surge protection with auto-reset Override feature keeps lighting on for 4 hours regardless of occupancy, then resets to sensor mode

IP44 Rated

Mounting

www.steinel.net


HS 150, HS 300 Halogen Outdoor Sensor Light Coverage

Wiring

NEUTRAL 40 ft

HOT Local OFF Switch (optional) 40 ft

Typical mounting height is 8 to 12 ft

LINE (BLACK) NEUTRAL (WHITE)

Coverage Adjustment

Controls

Fastening screws for glass cover

40 ft 40 ft

20 ft

20 ft

20 ft

Detection lens

Shrouds, supplied with each unit, snap in place, allowing users to adjust coverage as needed.

Settings Time Delay

Backplate

Time delay and light level setting

Light Level

Halogen bulb Thumb dial adjustments for time delay and light level are located beneath the decorative cover

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-01607-1


FL 300 Outdoor Sensor with Dual Lampholders Project Name Location

FL 300 Specifications Item No. Voltage Maximum Wattage Sensing Technology Time Delay Setting Mounting Light Level Setting Environment Coverage Lamps Dimensions (LxWxD) Warranty Certifications

The STEINEL FL 300 Outdoor Sensor with dual PAR Lampholders convenient configuration enhances security and energy savings for outdoor lighting. The FL 300 is passive infrared and responds to moving persons or other heat-emitting objects (such as vehicles). Using a multi-segmented lens to view the controlled area, the sensors switch lighting ON upon occupancy and OFF after a period of time where no motion has been detected.

• • •

• • • • •

Voltage

Passive Infrared Technology

140° Coverage

120 VAC, 60 Hz 300 watts (two 150 watt lamps) passive infrared (PIR) 10 seconds to 15 minutes wall or soffit .2-200 footcandles 2-2000 lux IP54 raintight rated -40°F to +120°F, -40°C to +49°C 140°, up to 40 foot reach (12.2 m) Accepts type PAR 38, max two 150 watt Tungsten lamps (not included) 5 x 11.5 x 5 in 127 x 292 x 127 mm 5 years UL Listed, CSA Approved, RoHS Compliant

Key Features

Applications Low-rise residential exterior locations including entryways, carports, patios and balconies.

61801 white 61811 black

Fully adjustable 140° coverage with up to 40 foot reach Sensor head tilts and swivels within a range of 65° vertically and 130° horizontally Aim n’ Lock lampholders require no screws or tools to move and set lamp positions; the lamps are directed at areas of desired illumination and lock in place, avoiding post-installation problems Unique dual mounting system enables the FL 300 to mount either to a wall or ceiling under a building soffit Snap-on shrouds allow users to easily customize the coverage area Light level feature allows lighting to remain off during daylight regardless of occupancy Override feature keeps lighting on for 4 hours regardless of occupancy, then resets to sensor mode Raintight IP54 rated; suitable for interior or exterior use

IP54 Raintight Rated

Mounting

www.steinel.net


FL 300 Outdoor Sensor with Dual Lampholders Coverage Adjustment

Coverage

Typical mounting height is 8 to 12 feet

8 ft

max 40 ft

Narrow-alley zone

Left or right side only

Split zone

Mounting The FL 300 can mount to a wall or building soffit

Shrouds, supplied with each unit, snap in place, allowing users to adjust coverage as needed

Wiring NEUTRAL HOT Local OFF Switch (optional)

LINE (BLACK) NEUTRAL (WHITE)

Aim n’ Lock Lampholders Settings STEINEL’s unique Aim n’Lock lampholders do not require tools and ensure that lampholders remain locked in place without sagging over time. The lampholder arm rotates for vertical adjustment, and the lampholders can also swivel to aim lamps horizontally.

www.steinel.net

(800) 852-4343

Time delay: 10 seconds to 15 minutes

9051 Lyndale Avenue South, Bloomington, MN 55420

Light level: .2 (night) to 200 (day) fc

M-01611-1


Fixture Integrated Controls Individual lighting fixture controls STEINEL’s OEM fixture integrated sensors use PIR or High Frequency technologies with a built in daylight feature. They provide occupancy and daylight control to be easily incorporated in a variety of fixture types for many applications. The HF technology allows the sensor to be totally enclosed within the fixture. This is ideal for IP44 or greater fixture types.


IS D360-120 Fixture Mount Occupancy Sensor Project Name: Location:

IS D360-120 Specifications Item No.

120 VAC, 0-300 ballast or tungsten

Mounting

fixture mount or to listed enclosure

Sensing Technology

5 seconds to 20 minutes

Light Level Setting

.2-200 footcandles 2-2000 lux

Coverage Sensors

360° with 180° angle of aperture, up to 13 ft (4 m) radial reach, up to 26 ft (8 m) tangential reach 3 dual element infrared pyroelectric detectors 720 switching zones, 10 detection levels

Dimensions (LxWxD)

3.23 x 2.01 in 82 x 51 mm

Certifications

5 years C-UL-US Listed, RoHS Compliant, CA Compliant

Key Features: • • • • •

Applications

IP20 rated, -4°F to +122°F, -20°C to +50°C

Lens Design

Warranty

The sensor is passive infrared and responds to heat radiated from human body motion. They turn lighting ON automatically with occupancy or manually controlled using a wall switch. After a period of time where no occupancy has been detected, the sensor switches lighting OFF.

passive infrared (PIR)

Time Delay Setting

Environment

The IS D360-120 is a fixture mount occupancy sensor for indoor use. The sensor‘s dimensions are the same as those of a MR16 lamp and fit commercially available MR16 fitting frames.

65236

Voltage

360° coverage with up to 13 ft (4 m) radial reach and 26 ft (8m) tangential reach Snap-on shrouds allow users to easily customize the coverage area 3 pyroelectric detectors with 720 switching zones provides highly accurate small motion detection Automatically adjusts to temperature changes keeping sensitivity and coverage consistent The hold off light level feature allows lighting to remain off during daylight regardless of occupancy

Fixture integrated for interior spaces such as offices, conference rooms, vestibules, and break rooms.

Voltage

Passive Infrared Technology

Coverage

IP20 Rated

Mounting

www.steinel.net


IS D360-120 Fixture Mount Occupancy Sensor Coverage

Wiring

26 ft 26 ft

Neutral Hot L O A D

26 ft

Black (Line) Red (Relay) White (Neutral) Red (Relay)

26 ft

26 ft

With a mounting height of 8 ft (2.5 m), the maximum reach of the sensor is 26 ft (8 m). Minor motion coverage, typical for an office environment, is 13 ft (4 m) radius. Coverage may vary depending on mounting height and environmental conditions.

Coverage Adjustment 26 ft

Settings

26 ft

13 ft

13 ft

13 ft 13 ft

Mounting 1 - Fitting frame 2 - Catch 3 - Switching module 4 - Sensor module 5 - Shroud 6 - Securing spring 7 - Light level setting 8 - Time delay setting

Light level and time delay settings are under the sensor module.

1

1

1

3 8 2

6

7

.2 – 200 fc

1

4

1

4 1

5 4 5 approx. 5 sec. – 20 min.

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-05202-1


HFLUM2-WR Fixture Integrated Sensor Module Project Name: Location:

HFLUM2-WR Specifications Item No. Voltage Load Rating

Transmitter Power Power Consumption

1 mW < 0.5 W 30 seconds to 30 minutes

Light Level Setting

0.2-200 footcandles 2-2000 lux

Coverage Environment Dimensions (LxWxD) Warranty Certifications

The HFLUM2-WR uses STEINEL’s High Frequency (HF) technology to turn lights on and off based on occupancy. It works by emitting high frequency electromagnetic waves (5.8 GHz) into the controlled area. Movement in the area causes a change in the waves’ echo, resulting in occupancy detection. The sensor can detect motion through many materials including glass and the lens of a fixture, enabling the sensor to be hidden from view.

0-800 watts @ 120 VAC, 50/60 Hz incandescent, magnetic or electronic ballasts - 1/4 HP 0-1200 watts @ 230/277 VAC, 50/60 Hz magnetic or electronic ballasts 0-650 watts @ 120/230/277 VAC, 50/60 Hz LED

Time Delay Setting

HF System

The HFLUM2-WR is a line voltage occupancy sensor module that installs in a fixture, adding energy saving lighting control in each fixture location.

65122 120/230/277 VAC, 50/60 Hz

5.8 GHz 360° adjustable 3.3 to 26 ft reach (1 to 8 m) requires enclosure temperature -4° F - 185° F, -20° C - 85° C 4.2 x 1.7 x 1.8 in 107 x 42 x 44.5 mm 5 years C-UL-US Listed, RoHS Compliant, Contains: FCC ID - W8J-SIR13, IC - 8529A-SIR13

Key Features: • • • • • • •

360° coverage; reach is adjustable from 3.3 to 26 ft High frequency technology emits 5.8 GHz electromagnetic waves Built-in surge protection with auto-reset Lamp seasoning feature provides a simple and convenient 4 day burn in as recommended by lamp manufacturers Adjustable time delay and light level settings Light level feature allows lighting to remain off during daylight, regardless of occupancy (hold off) Wiring is streamlined with three terminals

Applications Mounted in either a ceiling or wall lighting fixture, the sensor module is suited to a wide variety of interior spaces including offices, conference rooms and damp or wet locations when mounted inside sealed and gasketed fluorescent IP65 type fixtures.

Line Voltage

High Frequency Technology

360˚ of Coverage

Fixture Integrated

0.2 - 200 fc

www.steinel.net


HFLUM2-WR Fixture Integrated Sensor Module Controls Photocell Sensitivity Sensor dome

Time delay

antenna Light Level Wire terminations Mounting tabs

Mounting

Coverage

3.3 - 13 ft 1-4m

44.5 mm 1.75”

Typical mounting height is 8 to 10 ft

Mounting screw holes are 3.8 inches (97 mm) apart

107 mm 4.2” 97 mm 3.8”

42 mm 1.65”

3.3 - 26 ft 1-8m

Wiring

Coverage Adjustments

Sensitivity: Adjusts coverage reach from approximately 3.3 feet to 26 feet

Time delay: 30 seconds to 30 minutes

Light level: .2 (night) to 200 (day) footcandles

NEUTRAL HOT LOAD

www.steinel.net

(800) 852-4343

9051 Lyndale Avenue South, Bloomington, MN 55420

M-05104-1


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.