COORDINATE THE LOCATION OF ALL DIFFUSER, REGISTER, GRILLES WITH THE ARCHITECTURAL PLAN.
7.
ALL SHEET METAL DUCTWORK SHALL BE NEW GALVANIZED SHEET METAL DUCT GAUGES, CONSTRUCTION, SUPPORT, AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE CALIFORNIA MECHANICAL CODE 2010
8.
9.
BALANCE AND ADJUST ALL DIFFUSERS, REGISTERS, ETC. FOR OPTIMUM AIRDISTRIBUTION AND MINIMUM NOISE. SUBMIT A CERTIFIED AIR BALANCE REPORTTO THE MECHANICAL ENGINEER FOR APPROVAL. BALANCING OF THE SYSTEMS SHALL BE PERFORMED BY AN INDEPENDENT CERTIFIED TEST AND BALANCING AGENCY WHIC SPECIALIZES IN THE BALANCING AND TESTING OF HEATING, VENTILATING ANDAIR CONDITIONING SYSTEMS.
HP
VOLT
PH
HZ
OPER. WEIGHT
1/2
208
1
60
170
CARRIER 58MVB-060-14
LOWER FLOOR
FAU 2
CARRIER 58MVB-060-14
MASTER BEDROOM
FAU 3
CARRIER 58MVB-080-20
MASTER BED, BEDROOM 4
1600
0.5
46.5
75
1
208
1
60
FAU 4
CARRIER 58MVB-080-20
KITCHEN, FAMILY ROOM
2000
0.5
56
75
1
208
1
60
FAU 5
CARRIER 58MVB-080-20
2ND FLR MAIN
1200 1200
2000
0.5 0.5
0.5
35
57
35
56
56
75
1/2
1
208
1
208
1
60
60
11. CEILING DIFFUSERS SHALL BE ANEMOSTAT RMD-S OR APPROVED EQUAL MODULAR WIH OBD.
UNIT
REMARKS
MANUFACTURER AMB. TEMP AND MODEL
COMPRESSOR NO
RLA
COND. COIL FACE ROW FPI (SQ.FT)
FAN MOTOR
COND. FAN
MCA NO.
RPM
FLA
HP
VOLT
PH
HZ
MOCP
OPER. WEIGHT
CU 1
CARRIER 24ANA136
95
1
16.7
22.63
25
1
1
800
1.2
1/12
208
1
60
22
35
191
16X25X3/4
CU 2
CARRIER 24ANA136
95
1
16.7
22.63
25
1
1
800
1.2
1/12
208
1
60
22
35
191
204
20X25X3/4
CU 3
CARRIER 24ANA148
95
1
21.8
25.15
25
1
1
800
1.2
1/4
208
1
60
28.4
40
231
204
20X25X3/4
PRIVDE CONDENSING PUMP
CU 4
CARRIER 24ANA160
95
1
26.4
25.15
20
2
1
800
1.2
1/4
208
1
60
34.2
50
272
20X25X3/4
PRIVDE CONDENSING PUMP
CU 5
CARRIER 24ANA160
170
204
16X25X3/4
PRIVDE CONDENSING PUMP
95
1
26.4
25.15
20
2
1
800
1.2
1/4
208
1
60
34.8
50
S
TEMPERATURE SENSOR
T
THERMOSTAT
REMARKS
UNIT
SERVICE
TYPE
CFM
ESP IN (WG)
FAN RPM
CAPACITY
CD
CEILING DIFFUSER
SECTION THRU RECTANGULAR SUPPLY DUCT
CFM
CUBIC FEET PER MINUTE
SECTION THRU RECTANGULAR RETURN DUCT
CG
CEILING GRILLE
CHS
CHILLED WATER SUPPLY
CHR
CHILLED WATER RETURN
CONC
CONCRETE
COND
CONDENSATE
DUCT DROP IN DIRECTION OF FLOW
CONN
CONNECTION
CEILING DIFFUSER W/DIRECTION OF THROW INDICATED, (3-WAY BLOW SHOWN)
CONT
CONTINUATION
CR
CEILING REGISTER
D
DRAIN
DB
DRY BULB
DL
DOOR LOUVER
STATIC PRESSURE DAMPER COMBINATION FIRE/SMOKE DAMPER
DN
DOWN
DTR
DOWN THRU ROOF
FLEXIBLE CONNECTION, (F.C.)
272
DUCT RISE IN DIRECTION OF FLOW
MOTOR VOLT
PH
HZ
BACKDRAFT DAMPER, (BDD)
REMARKS
EF 1
POWDER ROOMS AND BATHROOMS
LOREN COOK GC-162
CEILING
100
0.25
1,200
103
120
1
60
15
PROVIDE BACKDRAFT DAMPER
SOUND LINED (SL)DUCT W/INTERNAL INSULATION DUCT SIZES SHOWN ARE NET INSIDE DIMENSION.
EA
EXHAUST AIR
(E)
EXISTING
EF 2
MASTER BATHROOM
LOREN COOK GC-182
CEILING
200
0.25
1,400
185
120
1
60
16
PROVIDE BACKDRAFT DAMPER
SOUND TRAP (ST)
ENT
ENTERING
TURNING VANES
EXH
EXHAUST
F.A.
FACE AREA
F
FAHRENHEIT
FLA
FULL LOAD AMPS
FPI
FINS PER INCH
SINGLE LINE RIGID SHEET METAL DUCTWORK
FPM
FEET PER MINUTE
M
FURNISHED & INSTALLED BY MECH. CONTRACTOR
FLEX
FLEXIBLE
GALV.
GALVANIZED
E
FURNNISHED & INSTALLED BY ELECT. CONTRACTOR
GA
GAUGE
HWS
HOT WATER SUPPLY
12. SIDEWALL SUPPLY REGISTERS SHALL BE DOUBLE DEFLECTION GRILLE WITH OPOSED BLADE DAMPER ATTACHED, TWO SETS OF INDIVIDUALLY ADJUSTABLE LOUVER, ANEMOSTAT S2HO
FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER
13. EXHAUST AIR AND RETURN AIR REGISTERS SHALL BE ANEMOSTAT S3HOD, HORIZONTAL FACE BARS SET AN ANGLE OF 45-DEGREES WITH OBD AND FLEXIBLE DUCT ADAPTOR. 14. FLEXIBLE CONNECTION SHALL BE PROVIDED FOR ALL DUCT WORK ATTACHED TO AIR MOVING EQUIPMENT MOUNTED ON OR SUSPENDED FROM VIBRATION ISOLATIONS. FLEXIBLE CONNECTIONS SHALL BE CODE APPROVED NEOPRENE COATED GLASS TYPE FABRIC. 15. THE ELECTRICAL AND PLUMBING CONTRACTORS SHALL PROVIDE FLEXIBLE CONNECTIONS AT ALL MECHANICAL EQUIPMENT MOUNTED ON VIBRATION ISOLATORS AND OR SUSPENDED FROM VIBRATION HANGER.
BELOW
CAP
MODULATING DAMPER, (MOD)
HP (WATTS)
BEL
BRITISH THERMAL UNIT
AUTOMATIC FIRE DAMPER, (AFD)
WEIGHT (LBS)
ABOVE
BTU
SECTION THRU RECTANGULAR EXHAUST DUCT
EXHAUST FAN SCHEDULE MANUFACTURER AND MODEL
ABV
RECTANGULAR DUCT W/SIZE OF SIDE SHOWN INDICATED FIRST
MANUAL VOLUME DAMPER, (MVD)
AS-BUILT RECORD PRINTS MUST BE PROVIDED PRIOR TO JOB COMPLETION.
10. PROVIDE ALL TRANSITIONS AS REQUIRED FROM MAIN DUCT OR BRANCHES TO DIFFUSERS, REGISTERS, OR GRILLES. PROVIDE MVD FOR EACH BRANCH.
FILTER
ME
FURNISHED & INSTALLED BY MECH. CONTRACTOR, WIRED BY ELECT. CONTRACTOR
HWR
HOT WATER RETURN
EM
FURNISHED BY ELECT. CONTRACTOR, INSTALLED BY MECH. CONTRACTOR WIRED BY ELECT. CONTRACTOR
HP
HORSEPOWER
IN
INCH
ISOL
ISOLATOR
LBS
POUNDS
LVG
LEAVING
EMS
ENERGY MANAGEMENT SYSTEM
21. CONTRACTOR TO THOROUGHLY CLEAN ALL PORTIONS OF THEIR WORK, REMOVE ALL DEBRIS AND LEAVE INSTALLATION IN PERFECT CONDITION READY FOR USE.
M.A.
MIXED AIR
MAX
MAXIMUM
22. CONDENSER REFRIGERANT PIPING IN THE STRUCTURE SHALL BE INSTALLED SO AS NOT TOUCH STRUCTURE, FRAMING, OR WALL SURFACES. INSTALL FOAM RUBBER CUSHIONS AT PENETRATIONS TO SEPERATE PIPING FROM STRUCTURE.
MBH
1000 BTU'S PER HOUR
MIN
MINIMUM
MOD
MODULATING DAMPER
23. DUCT INSTALLATION: FOR THERMAL INSULATION, INSULATE ALL SUPPLY AND RETURN AIR DUCT WORK AND PLENUM WITH 2" THICK FIBERGLASS INSULATION WRAPPED AROUND WITH 2" OVERLAP AND WIRED ON #18 GALVANIZED WIRE @ 12" O.C. NRC RATING SHALL BE AT LEAST .80 AT FREQUENCIES ABOVE 1000. ALL DUCTS SHALL HAVE JOINTS AND SEAMS SEALED. FOR SOUND INSULLATION, INSULATE INTERIOR OF SUPPLY AND RETURN AIR PLENUMS WITH MIN. 1" THICK SOUND INTERIOR OF SUPPLY AND RETURN AIR PLENUMS WITH MIN. 1" THICK SOUND ABSORBING INSULATION TO REDUCE NOISE. INSTALL SOUND STRAPS IN PLENUM AND INSULATE BLOWER COMPARTMENT WHERE RETURN AIR REGISTERS ARE IN CLOSE PROXIMITY TO UNITS.
MVD
MANUAL VOLUME DAMPER
NTS
NOT TO SCALE
OPER. WT. OPERATING WEIGHT
24. LABEL ALL EQUIPMENT (AC) TO INDICATE THE SPACE NAME THAT IT IS SERVING.
16. ALL AIR CONDINTIONING FILTERS SHALL BE REPLACED PRIOR ON DAY OF BALANCING. 17. ALL EQUIPMENT TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTION 18. AFFIX MAINTENANCE LABELS TO MECHANICAL EQUIPMENT AND PROVIDE THE OWNER WITH MAINTENANCE AND PARTS MANUALS., LABEL ALL EQUIPMENT WITH THE NAME OF SPACE IT SERVES.
CC
CLOSING COIL IN MAGNETIC STARTER
19. SEAL ALL DUCT JOINTS WITH AN APPROVED TYPE MASTIC.
SW
SWITCH
20. ALL DUCTS PENETRATING THE ROOF SHALL HAVE APPROVED FLASHING AND COUNTER-FLASHING AND BE WEATHER PROOFED.
25. DUCT SYSTEM SHOWN ON THE PLANS ARE SIZED IN ACCORDANCE WITH ASHRAE EQUAL FRICTION METHOD (CHAPTER 35,2005 ASHRAE HANDBOOK). 26. DUCT MATERIAL AND GAGES, PER THE FOLLOWING TABLES: i. TABLE 6-6A & 6-6B DUCT INSTALLATION ii. TABLE 6-7 DUCT SUPPORT a. VERTICAL DUCTS b. HORIZONTAL DUCTS c. HORIZONTAL-DUCTS-TRAPEZE-TYPE SUPPORTS iii. TABLE 6-8 CONSTRUCTION DETAILS FOR ROUND & FLAT-OVAL DTUCTS (LOW, MED, & HI PRESSURE)
SD
SMOKE DETECTOR
OPG
OPENING
OSA
OUTSIDE AIR
PD
PRESSURE DROP
PH
PHASE
PRESS
PRESSURE
POC
POINT OF CONNECTION
PSI
POUNDS PER SQUARE INCH
RA
RETURN AIR
RAR
RETURN AIR REGISTER
REQ'D
REQUIRED
RL
REFRIGERATION LIQUID LINE
RLA
RATED LOAD AMPS
RPM
REVOLUTIONS PER MINUTE
RS
REFRIGERATION SUCTION LINE
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
6.
FAN MOTOR
ROUND DUCT SA
SUPPLY AIR
SP
STATIC PRESSURE
SF
SQUARE FEET
SWR
SIDEWALL REGISTER
SL
SOUND LINED
TEMP
TEMPERATURE
T'STAT
THERMOSTAT
TYP
TYPICAL
UTR
UP THRU ROOF
V
VOLT
W/
WITH
WB
WET BULB
W.G.
WATER GAUGE
(E)
EXISTING
(N)
NEW
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
5253 HORIZON DRIVE MALIBU, CA
COORDINATE THE SIZE, LOCATION, @ SERVICE REQUIREMENTS OF ALL MECHANICAL EQUIPMENT & DUCTWORK WITH THE GENERAL, PLUMBING, ELEC.CONTROL, & FIRE PROTECTION CONTRACTOR PRIOR TO THE START OF CONSTRUCTION. REPORT ALL UNRESOLVED CONFLICTS TO THE ARCHITECT.
COOLING HEATING ESP. (IN WG.) CAPACITY CAPACITY (MBH) (MBH)
CREATIVE DESIGN
5.
THE MECHANICAL CONTRACTOR SHALL OBTAIN & PAY FOR ALL PERMITS, LICENSES & INSPECTIONS REQUIRED TO COMPLETE THIS JOB.
CFM
OHANIAN RESIDENCE
4.
THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, APPARATUS, ACCESSORIES (I.E., THE ENTIRE INSTALLATION) AS FURNISHED BY HIM FOR A PERIOD OF ONE YEAR.
FAU 1
SERVICE
NOT FOR CONSTRUCTION USE
3.
THE INSTALLATION SHALL COMPLY WITH & BE INSTALLED IN ACCORDANCE WITH ALL LEGALLY CONSTITUTED AUTHORITIES & CODES HAVING JURISDICTION. ALSO ALL THE REQUIREMENTS OF LANDLORD.
MANUFACTURER AND MODEL
UNIT
JOB TITLE
2.
THE MECHANICAL CONTRACTOR SHALL FURNISH ALL MATERIAL, LABOR, EQUIPMENT APPURTENANCES, AND ALL CONTRACTUAL EXPENSES REQUIRED FOR THE COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM TO THE SATISFACTION OF THE OWNER, ARCHITECT, AND MECHANICAL ENGINEER.
OUTDOOR UNIT
INDOOR UNIT
LEGENDS, NOTES, AND SCHEDULES
1.
LEGEND & ABBREVIATIONS
SHEET TITLE
HVAC GENERAL NOTES
SPLIT SYSTEM COOLING UNIT SCHEDULE
Sheet
M-1
NOT FOR CONSTRUCTION USE
NUMBERED NOTES: 1
RL & 7 8" RS (INSULATED) UP TO 1ST FLOOR TO RELATED CONDENSING UNIT
2
2" COMBUSTION AIR AND 2" VENT UTR WITH RAIN CAP. (TERMINATE VENT MIN 3'-0" FROM AIR INTAKE)
8"
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
3
EF 1 8X312 EXHAUST DUCT UP TO 1ST FLOOR 26X6 SAR 380 CFM 8X8 CD 80 CFM
8X8 CD 80 CFM T
16X6 SAR 260 CFM
16X6
10X6
14X6
26X8 16X6
28X8 24X24 RAR 1,200 CFM 2 FAU 1
1
LOWER FLOOR PLAN SCALE: 1/4" = 1'-0"
1 M-2
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
5253 HORIZON DRIVE MALIBU, CA
OHANIAN RESIDENCE
JOB TITLE
LOWER FLOOR PLAN
SHEET TITLE
26X6 SAR 400 CFM
Sheet
M-2
NUMBERED NOTES:
1
3
3
2" COMBUSTION AIR AND 2" VENT UTR WITH RAIN CAP. (TERMINATE VENT MIN 3'-0" FROM AIR INTAKE)
FAU 4
1
36X10
T
8X8 CD 80 CFM
EF 1
14X6 SAR 220 CFM
EF 1
8X6 8X8 CD 80 CFM 26X10
8X8 CD 80 CFM
24X6 SAR 380 CFM
10X6 SAR 160 CFM
8X312 EXHAUST DUCT UP TO 1ST FLOOR
12X10
UTR TERMINATE WITH ROOF JACK
26X6 SAR 380 CFM 2
12X8 8X312 EXHAUST DUCT UP TO 2ND FLOOR AND DOWN TO LOWER FLOOR
16X6
12X10
20X10 EF 1
18X10
12X6 12X10
10X6
10X6 16X6 SAR 240 CFM
12X6
10X6 16X6 SAR 240 CFM
16X10
18X10 16X6 SAR 240 CFM
16X6 SAR 240 CFM 8X8 CD 80 CFM 24X6 SAR 340 CFM
24X10
24X36 RAR 2,000 CFM
T
3 FAU 5 26X12 26X12 1
8X8 CD 80 CFM
12X10
16X6 SAR 240 CFM 10X6
EF 1
2
14X6
24X6 SAR 320 CFM
SHEET TITLE
12X10
12X6 20X6 SAR 300 CFM
8X312 EXHAUST DUCT UP TO 2ND FLOOR AND DOWN TO LOWER FLOOR
1
24X36 RAR 2,000 CFM
12X6 20X6 SAR 300 CFM
2
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
1
RL & 7 8" RS (INSULATED) UP OFFSET ABOVE CEILING TO RELATED CONDENSING UNIT 8"
CREATIVE DESIGN
1
3
FIRST FLOOR PLAN SCALE: 1/4" = 1'-0"
1 M-3
FIRST FLOOR PLAN
1
1
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
M-3
5253 HORIZON DRIVE MALIBU, CA
CU 3
CU 5
OHANIAN RESIDENCE
CU 4
JOB TITLE
CU 2
NOT FOR CONSTRUCTION USE
CU 1
NOT FOR CONSTRUCTION USE
NUMBERED NOTES: 1
3
RL & 7 8" RS (INSULATED) DOWN IN WALL TO RELATED CONDENSING UNIT
2
8X312 EXHAUST DUCT UTR AND DOWN TO 1ST FLOOR
8"
3 4 2" COMBUSTION AIR AND 2" VENT UTR WITH RAIN CAP.
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
5
24X24 CR 1,600 CFM 12X6
T
22X12 12X6 16X6 SAR 220 CFM
12X6
2
2 10X6
FAU 3
8X8 CD 80 CFM
EF 1
1
10X8
2
20X6 SAR 260 CFM
5
14X14 CD 280 CFM 3
22X12 EF 1
3
8X8 CD 80 CFM 16X12 16X6 SAR 300 CFM 8X8 CD 160 CFM
18X12 22X22 CR 1,200 CFM 12X10
12X6
EF 1
1 5
FAU 2
EF 1
12X6
EF 1
3
18X12
3
8X8 CD 160 CFM
3 3 8X4
20X6 SAR 260 CFM
20X6 SAR 260 CFM 8X8 CD 180 CFM EF 1
SECOND FLOOR PLAN SCALE: 1/4" = 1'-0"
1 M-4
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
M-4
5253 HORIZON DRIVE MALIBU, CA
OHANIAN RESIDENCE
2
JOB TITLE
26X6 SAR 400 CFM
4
SECOND FLOOR PLAN
8X8 CD 80 CFM
SHEET TITLE
8X8 CD 80 CFM
EF 2
FIXTURE UNITS COUNT(WATER)
GENERAL NOTES
PLUMBING FIXTURE SCHEDULE
HOT AND COLD WATER CALCULATIONS
PLUMBING SYMBOLS LEGEND
CONNECTION SIZES
WC BD
4.
5.
6.
7. 8. 9.
IT SHALL BE THE GENERAL CONTRACTORS RESPONSIBILITY TO ARBITRATE ANY CONFLICTS WITH THE STRUCTURE AND/OR BETWEEN THE TRADES. PROVIDE TRAP PRIMERS, VACUUM BREAKERS AND BACKFLOW DEVICES AS REQUIRED BY THE OWNER THE LOCAL CODE OR AUTHORITY HAVING JURISDICTION. ALL WORKMANSHIP, EQUIPMENT FURNISHED, MATERIALS SYSTEM PROVIDED BY THIS CONTRACTOR SHALL BE GUARANTEED IN WRITING FOR A PERIOD OF ONE FULL YEAR FROM DATE OF FINAL ACCEPTANCE BY THE OWNER. INSULATE FIXTURE TRAPS AND HOT WATER RISERS TO MEET WITH ADA CODE REQUIREMENTS.
BT SH
QTY.
11
LAVATORY WATER CLOSET
11 1
BIDET
6
BATH TUB
2
SHOWER
(WATER) FIXTURE UNIT 1 2.5 1 4 2
(WATER) TOTAL FIXTURE UNIT 11 27.5 1 24 4
BS
BAR SINK
1
1
LS
LAUNDRY SINK
1
1.5
1.5
S
SINK
1
1.5
1.5
1
KS
KITCHEN SINK
1
1.5
1.5
DW
DISH WASHER
1
1.5
1.5
CLOTHES WASHER ASSEMBLY
1
4
PROVIDE LOW FLOW WATER CLOSETS (1.6 GPF).
11. CONTRACTOR SHALL PROVIDE THE NECESSARY MATERIALS FOR BUILDING SETTLEMENT FOR ALL PIPING. 12. CONTRACTOR SHALL ROUTE VENTS THRU ROOF AS NEEDED, AND SHALL MAKE ALL NECESSARY OFFSETS AS REQUIRED FOR INSTALLATION OF VENTS THRU ROOF. VENTS SHALL TERMINATE NOT LESS THAN 10 FEET FROM, OR AT LEAST 3 FEET ABOVE ANY OPERABLE WINDOW, DOOR, OPENING, AIR INTAKE, OR VENT SHAFT, NOR LESS THAN 3 FEET IN EVERY DIRECTION FROM ANY LOT LINE. PER 2010 UNIFORM PLUMBING CODE.
MAX 50 PSI, MIN 45 PSI
B. PRESSURE LOSSES FROM METER TO BOOSTER PUMP 1. LOSS THRU 2" METER (60 GPM): 2 PSI 2. LOSS THRU 2" BFP (WILKINS 375): 14 PSI 3. DEVELOP. LENGTH FROM METER TO BOOSTER PUMP 500 FT 20% FITTINGS 100 FT TOTAL DEVELOPED LENGTH= 600 FT LOSS THROUGH PIPE FRICTION 600' X 7/100 = 42 42 X 0.43 = 18 PSI PRESSURE LOSS BEFORE BOOSTER PUMP
34 PSI
4. PRESSURE LEFT TO BOOSTER PUMP: 45-34 = 5. BOOSTER PUMP DIFFERENTIAL PRESSURE: 75 - 11 =
11 PSI 64 PSI
C. PRESSURE LOSSES AFTER BOOSTER PUMP 1. LOSS DUE TO BUILDING HEIGHT 15 FT X 0.43=
CWA HB BS
4
HOSE BIBB FUTURE OUTDOOR BAR SINK
1
2.5 + 4 1
TOTAL
13. PLUMBING DRAWINGS ARE DIAGRAMATIC AND DO NOT SHOW ROUGH-IN HEIGHTS AND LOCATIONS. 14. INSTALL ALL PLUMBING IN CONFORMANCE WITH THE 2010 EDITION OF THE "UNIFORM PLUMBING CODE".
6 PSI
1
HW FU
1/2"
3
3
3/4"
11
9
1"
23
17
1-1/4"
54
29
1-1/2"
104
48
2"
260
120
2-1/2"
474
246
3"
747
412
4"
1743
851
FIXTURE
FIX ID
DRAIN
TRAP
VENT
COLD
HOT
WC-1
WATER CLOSET
3"
INTEGRAL
2"
1/2"
-
BD-1
BIDET
2"
INTEGRAL
1-1/2"
1/2"
-
L-1
LAVATORY
2"
BATHTUB
BT-1
1-1/4" X 1-1/2"
2"
1-1/2"
1-1/2"
1/2"
1/2"
3/4"
1-1/2"
SYMBOL
COMMENTS
3/4"
D. PRESSURE LEFT TO OVERCOME FRICTION 75 - 33 =
42 PSI
E. TOTAL DEVELOPED LENGTH= 20% FITTING ALLOWANCE = TOTAL DEVELOPED LENGTH
400 FT 80 FT 480 FT
F. AVAILABLE FRICTION HEAD LOSS PER 100FT 42 PSI X 100 FT= 480 FT
ABBREV.
SH-1
SHOWER
2"
2"
WASTE ABOVE FLOOR
W
WASTE BELOW FLOOR
SD
SD
STORM DRAIN ABOVE FLOOR
OD
OD
OVERFLOW DRAIN ABOVE GRADE
SD
SD
STORM DRAIN BELOW FLOOR
PIPE SIZED BASED ON 8 PSI DROP PER 100 FEET 2"
KITCHEN SINK
1-1/2"
1-1/2"
1/2"
-
1/2"
CW
COLD WATER
HW
HOT WATER
HWR DW-1
DISH WASHER
2"
1-1/2"
-
BS-1
BAR SINK
2"
1-1/2"
1-1/2"
1/2"
1/2"
1/2"
S-1
SINK
2"
1-1/2"
1-1/2"
1/2"
1/2"
LS-1
LAUNDRY SINK
2"
1-1/2"
1-1/2"
1/2"
1/2"
(E)
8.8 PSI
HB-1
CLOTHES WASHER ASSEMBLY
2"
2"
1-1/2"
3/4"
3/4"
HOSE BIBB
-
-
-
1/2"
-
G
ICW
ICW
INDUSTRIAL COLD WATER
CD
CD
CONDENSATE DRAIN
D
D (E)
RISER DRAIN EXISTING PIPING WITH SERVICE INDICATED SHUT OFF VALVE CHECK VALVE
CO
CLEANOUT FLOOR CLEANOUT PIPE DROP UNLESS OTHER WISE NOTED
60 GPM
GPM
GAS
CV
FCO
20 GPM
HOT WATER RETURN
G
SOV CWA-1
VENT
1/2"
1/2"
1-1/2"
DESCRIPTION
W
V
20 PSI 33 PSI
3. PRESSURE REQ MOST REMOTE OUTLET: TOTAL PRESSURE LOSSES:
40 GPM
LANDSCAPE
16. ISOLATE ALL WATER PIPING FROM STRUCTURE WITH FELT PADS OR TRISOLATORS.
6.5
CW (FT) FU
7 PSI
86 FU
GPM
15. PROVIDE WATER AND SHUT OFF VALVE AT ALL REFRIGERATORS FOR ICE MAKER CONNECTION. (FINAL CONNECTION BY OTHERS).
4
PIPE SIZE
KS-1
2. 2" PRV WILKINS 500
DOMESTIC WATER HEATER SHALL BE CALIFORNIA ENERGY COMMISSION (CEC) LISTED.
10. PROVIDE VACUUM BREAKERS ON ALL HOSE BIBBS.
A. STREET PRESSURE:
PIPE-UP UNLESS OTHER WISE NOTED 17. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL PLUMBING FIXTURES AND DRAINS.
WATER HEATER SCHEDULE GAS PIPE CALCULATION TYPICAL ALL 49 UNITS
19. BACKFLOW PREVENTION DEVICES FOR CROSS CONNECTION CONTROL SHALL BE INSTALLED TO COMPLY WITH SECTION 603 AND TABLE 6-1
21. SLOPE ALL WASTE PIPING AT 2% (1/4" PER FOOT) UNLESS IT IS IMPRACTICAL DUE TO THE DEPTH OF THE STREET SEWER OR BUILDING STRUCTURAL IMPEDIMENTS. PRIOR APPROVAL FROM THE BUILDING OFFICIAL MUST BE OBTAINED TO REDUCE SLOPE TO 1% (1/8" PER FOOT) FOR 4" DIAMETER AND LARGER PIPE. SEE SECTION 708, 2010 UNIFORM PLUMBING CODE. 22. PIPING PENETRATIONS OF FIRE RESISTANCE RATED WALLS, PARTITIONS, FLOOR, FLOOR/CEILING ASSEMBLIES AND ROOF/CEILING ASSEMBLIESSHALL BE PROTECTED BY AN APPROVED PENETRATION FIRE STOP SYSTEM. 23. LEAD FREE COMPLIANCE REQUIRED EFFECTIVE JANUARY 1, 2010 PER CALIFORNIA HEALTH & SAFETY CODE SEC. 116875
L WC
LAVATORY
11
1
11
WATER CLOSET
11
3
33
FIXTURE
WOOD SHRINKAGE THE CONTRACTOR SHALL ANTICIPATE THE NORMAL SHRINKAGE OF THE WOOD FRAMING DURING CONSTRUCTION AND FOR A PERIOD OF TIME THEREAFTER. IN ORDER TO PREVENT DAMAGE CAUSED BY SUCH SHRINKAGE, THE FOLLOWING MEASURES SHALL BE TAKEN DURING INSTALLATION OF PLUMBING LINES, GAS LINES AND OTHER ELEMENTS WHICH WOULD BE ADVERSELY AFFECTED BY SHRINKAGE: JOISTS AND PLATES SHALL BE TESTED FOR MOISTURE CONTENT DURING FRAMING (SEE STRUCTURAL DRAWINGS).
B.
PROVIDE SWING JOINTS ON BRANCHES CONNECTING TO RISERS.
C.
VALVED CONNECTIONS TO RISERS SHALL BE OF COPPER TUBING INSTALLED SO AS TO PERMIT MOVEMENT OF THE STRUCTURE.
D.
HOLES BORED IN STUDS TO PERMIT PASSAGE OF PIPING SHALL BE DRILLED 3/4-INCH OVERSIZE, AND PIPING INSTALLED IN THE BOTTOM OF THE HOLES.
ID
QUANTITY
CFH EACH
WATER HEATER
3
199
597
DRYER
1
35
35
EQUIPMENT
DESCRIPTION
CFH TOTAL
WH-1, WH-2 WH-3
TANKLESS WATER HEATER
BD
1
BIDET
2
2
BT
BATH TUB
6
2
12
SH
SHOWER
2
2
4
BS
BAR SINK
1
1
1
LAUNDRY SINK
1
2
2
S
SINK
1
2
2
KS
KITCHEN SINK
1
2
2
DW
DISH WASHER
1
2
2
CWA BS
CLOTHES WASHER ASSEMBLY FUTURE OUTDOOR BAR SINK TOTAL
1 1
3 1
3 1 75 FU
RANGE
1
65
F.
WHERE PLASTER, DRYWALL OR TILE IS INSTALLED AROUND HORIZONTAL PIPING, PROVIDE FOR MOVEMENT BY PROVIDING CLEARANCES BETWEEN FINISHES AND PIPE LINES.
RTGH-95DVLN
RHEEM
STORAGE CAPACITY
GAS BTU/H 199,000
RECOVERY RATE
OPERAT. WEIGHT 82 LBS
TANKLESS
PIPES TO BE REMOVED
REMARKS MUST BE CEC LISTED INSTALL PER MANUFACTURER INSTALLATION INSTRUCTION
POC
POINT OF CONNECTION
ABV
ABOVE
BEL
BELOW
BV
BALANCING VALVE
FIRE PLACE
4
65
260
PATIO HEATER
7
25
175
FIRE PIT
1
50
50
FAU-1, & 2
2
60
120
FAU-3, 4, & 5
3
80
240
POOL HEATER
1
400
400
FUTURE FIRE PLACE
1
65
1
40
TOTAL
DN
EQUIPMENT SCHEDULE
(E), EXIST EQUIP ID ET-1
DESCRIPTION EXPANSION TANK
CP-1
CIRCULATING PUMP
MANUFACTURER
MODEL NO.
BELL & GOSSETT
PT-5
BELL & GOSSETT
REMARKS 2 GALLON
65 DESCRIPTION
MANUFACTURER
MOTOR
CAPACITY
40 2047
SP 1
SUMP PUMP - PRE-ASSEMBLED DUPLEX SYSTEM
LIBERTY PUMP 1100 SERIES
40 GPM @ 16' HEAD
HP
VOLTS
PH
4/10
230
1
MAX TOTAL DEVELOPMENT LENGTH = 550'
BOOSTER PUMP SCHEDULE BP 1
BELL & GOSSETT
MODEL No. SERIES 80 112 X 112 X 7B
GPM
HEAD
HP
60
100'
3
RPM
3,500
VOLTS PHASE 230
EXISTING
ELEV
ELEVATION
FT
FOOT, FEET
FU
FIXTURE UNITS
FV
FLUSH VALVE
HDCP
HANDICAP
MTD
MOUNTED
REQ
REQUIRED
SGL
SINGLE
REMARKS
2" DISCHARGE
ST STL TYP
PUMP No. MANUFACTURER
DOWN
1/12 HP-120V, 1PH, 60HZ ALL BROZE
PL-30
SUMP PUMP SCHEDULE PUMP ID
FUTURE BBQ
CEILING
65
4" GAS METER REQUIRED
E.
MODEL NO.
MANUFACTURER
CLG
LS
A.
(WATER) TOTAL FIXTURE UNIT
SYMBOL
20. PROVIDE CLEANOUTS PER 2010 UNIFORM PLUMBING CODE.
REMARKS
STAINLESS STEEL TYPICAL
VB
VACUUM BREAKER
W/
WITH
3
VENTS SHALL BE INSTALLED WITH DOUBLE FLASHING WHICH WILL PERMIT MOVEMENT WITHOUT COMPROMISING WATER TIGHTNESS OF INSTALLATION.
NOTES: NO EXTRA WORK SHALL BE UNDERTAKEN WITHOUT THE WRITTEN APPROVAL OF THE OWNER OR HIS REPRESENTATIVE. THE CONTRACTOR SHALL FULLY DESCRIBE THE EXTRA WORK TO BE PERFORMED AND THE COST THEREOF.
PIPING MATERIALS WASTE, VENT AND STORM DRAINAGE PIPING:
CAST IRON.
DOMESTIC AND INDUSTRIAL WATER PIPING:
TYPE "L" COPPER PIPE.
NATURAL GAS PIPING:
SCHEDULE 40 BLACK STEEL.
LEGENDS, NOTES, AND SCHEDULES
1.
SHEET TITLE
1.
QTY.
(WATER) FIXTURE UNIT
HEATER
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
FIXTURE UNITS COUNT(WASTE)
DROP OR RISE
CREATIVE DESIGN
18. ALL HOT WATER PIPING SHALL BE INSULATED IN ACCORDANCE WITH THE LATEST EDITION OF THE ENERGY EFFICIENCY STANDARDS.
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
P-1
5253 HORIZON DRIVE MALIBU, CA
REVIEW ALL DRAWINGS IN THIS SET PRIOR TO STARTING WORK. NOTIFY THE GENERAL CONTRACTOR OF ANY FURRING OR SLEEVING REQUIREMENTS
L
FIXTURE
OHANIAN RESIDENCE
3.
VERIFY ALL INVERTS, ELEVATIONS, DIMENSIONS AND LOCATIONS PRIOR TO STARTING THIS PORTION OF THE WORK.
SYMBOL
NOT FOR CONSTRUCTION USE
2.
THIS CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED PERMITS AND INSPECTIONS REQUIRED FOR THIS PORTION OF THE WORK.
JOB TITLE
1.
PL
NOT FOR CONSTRUCTION USE
PL
PL
2" GAS FOR CONTINUATION SEE FLOOR PLAN
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
2" CW FOR CONTINUATION SEE FLOOR PLAN
4" GAS (1542 CFH) BELOW GRADE
1" GAS (50 CFH) FOR CONTINATION SEE FIRST FLOOR PLAN
1
2" CW & HW FOR CONTINUATION SEE FLOOR PLAN
4" GAS (1542 CFH) FOR CONTINUATION SEE 1ST FLOOR PLAN
PL
4" GAS (1942 CFH) BELOW GRADE
2" BFP WILKINS 975XL
2" WATER METER
2" WASTE BELOW GRADE TO SEPTIC TANK, FOR CONTINUATION SEE CIVIL DRAWINGS
2" WASTE CAPPED BELOW GRADE FOR FUTURE OUTDOOR BAR SINK
PL
PL
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
P-2
5253 HORIZON DRIVE MALIBU, CA
OHANIAN RESIDENCE
JOB TITLE
1 P-2
SITE PLAN
SCALE: 1/16" = 1'-0"
SHEET TITLE
SITE PLAN
NOT FOR CONSTRUCTION USE
NUMBERED NOTES: 3
4" PRIMARY COND. DRAIN DOWN IN WALL & CONNECT TO TAIL PIECE ADAPTER, 3 4" SECONDARY COND. DRAIN TERMINATED 1" BELOW CEILING WITH CHROME PLATE ESCUTCHEON
2
1" GAS UP TO 1ST FLOOR
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
1
3
CREATIVE DESIGN
4" CW & HW DOWN IN WALL TO SERVE BAR SINK
112" VENT UTR
BS-1
2" VENT UP TO 1ST FLOOR CONTROL PANEL
SP 1
2" SUMP DISCHARGE FCO ON 1ST FLOOR Y-CONNECTION WC-1
2" VENT UP TO 1ST FLOOR
2 L-1
1
3
4" CW & HW UP TO 1ST FLOOR
LOWER FLOOR PLAN SCALE: 1/4" = 1'-0"
1 P-3
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
P-3
5253 HORIZON DRIVE MALIBU, CA
JOB TITLE
LOWER FLOOR PLAN
SHEET TITLE
FAU 1
OHANIAN RESIDENCE
4" WASTE, FOR CONTINUATION SEE 1ST FLOOR PLAN
2" GAS (400 CFH) UP IN WALL TO POOL HEATER
1" CW TO POOL EQUIP 2" CW UP, AND DOWN IN WALL TO BOOSTER PUMP
2" PRV WILKINS 500
HB-1 1
NOT FOR CONSTRUCTION USE
11 4" CW TO LANDSCAPING
NUMBERED NOTES:
2" GAS (400 CFH) BELOW GRADE, FOR CONTINUATION SEE SITE PLAN 2" CW UP IN WALL TO BOOSTER PUMP AND 2" CW BELOW GRADE, DOWN OFFSET BELOW GRADE FOR CONTINUATION SEE SITE PLAN BP 1
1
4" WASTE BELOW GRADE TO SEPTIC TANK, FOR CONTINUATION SEE CIVIIL DRAWINGS
11
5"/3" CONCENTRIC VENT SYSTEM UP TO 2ND FLOOR, INSTALL PER MANUFACTURER INSTALLATION INSTRUCTION
2
2" WASTE UP OFFSET ABOVE CEILING AND DOWN IN WALL
12
3" VENT UP TO 2ND FLOOR
3
3" WASTE UP OFFSET ABOVE CEILING AND DOWN IN WALL
13
3
4
1
4" PRIMARY COND. DRAIN DOWN IN WALL & CONNECT TO TAIL PIECE ADAPTER, 3 4" SECONDARY COND. DRAIN TERMINATED 1" BELOW CEILING WITH CHROME PLATE ESCUTCHEON
5
3
4"
CW & 3" WASTE UP TO 2ND FLOOR
14
3" AD UP TO 2ND FLOOR AND DOWN IN WALL, SPILL 6" ABOVE GRADE
6
3
4"
CW & 2" WASTE UP TO 2ND FLOOR
15
3" AD UP TO 2ND FLOOR
7
112" CW DOWN IN WALL, RUN 11 4" CW TO EACH WATER HEATER
16
3" AD DOWN IN WALL, SPILL 6" ABOVE GRADE
8
112" HW & 3 4" HWR UP OFFSET ABOVE CEILING
9
112" HW & 3 4" HWR UP TO SECOND FLOOR
10
212" GAS (597 CFH) DOWN IN WALL, RUN 1 12" GAS TO EACH WATER HEATER
2"CW
CW & 2" WASTE UP TO 2ND FLOOR
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
2"CW
2"
112"VENT UP TO 2ND FLOOR AND DOWN TO LOWER FLOOR 3
11 4"GAS (80 CFH)
4" GAS (35 CFH) DOWN IN WALL TO DRYER HB-1
112"CW
7 8
CWA-1
WH-1
11 2" VENT UP TO 2ND FLOOR AND DOWN TO BASEMENT
9 2"CW
LS-1
11
1
1 4" GAS (115 CFH)
WH-3
11
2" WASTE FOR CONT SEE LOWER FLOOR PLAN
WH-2 13
L-1
12
FCO 10
1 4" GAS (80 CFH) UP TO 2ND FLR
12 S-1 5
4
WC-1
3 1 4" CW & 2HW DOWN TO BASEMENT
6
1
L-1
WC-1
WC-1
L-1
5
6
PIPING IN CEILING SPACE
G
GAS (25 CFH)
3" GAS (1112 CFH)
3" GAS (1172 CFH)
4" GAS (1312 CFH) G
11 4" GAS (140 CFH)
14
1" GAS (60 CFH) UP TO 2ND FLR G
112" GAS (230 CFH)
112" VENT UP TO 2ND FLOOR
BS-1
11 4" GAS (130 CFH)
112" VENT UP TO 2ND FLR
5
4" GAS (1372 CFH)
2
1" GAS (65 CFH) DOWN IN WALL TO FIRE PLACE
1" GAS (65 CFH) DOWN IN WALL TO FIRE PLACE
4"
CW DOWN IN WALL OFFSET BELOW FLOOR
PIPING IN CEILING SPACE HB-1
6 5 KS-1
6
4 5
11 4" GAS (80 CFH) PIPING IN CEILING SPACE
5
4
4
4" GAS (1452 CFH)
HB-1 11 4" GAS (100 CFH)
2% 4
3
1" GAS (50 CFH) DOWN IN WALL OFFSET BELOW GRADE
1" GAS (50 CFH)
11 4" GAS (75 CFH)
16
13
4
4" GAS (1517 CFH)
16
G
12
2%
2%
1" GAS (50 CFH) 3
4"
GAS (25 CFH)
3
4"
3
GAS (25 CFH)
4"
GAS (25 CFH)
3
4"
GAS (25 CFH)
PIPING IN CEILING SPACE
L-1 WC-1
FCO 3
4"
GAS (25 CFH)
4" GAS (1542 CFH) UP IN WALL OFFSET ABOVE CEILING
6 2
15
SH-1
1" GAS (65 CFH) UP TO 2ND FLOOR 2%
FCO
1" GAS (50 CFH) BELOW GRADE TO FIRE PIT 3 4" GAS (25 CFH) UP TO 2ND FLOOR
1 14 1
FIRST FLOOR PLAN SCALE: 1/4" = 1'-0"
2" CW & HW CAPPED BELOW GRADE FOR FUTURE OUTDOOR BAR SINK
1 P-4
14
SHEET TITLE
14
JOB TITLE
14
FIRST FLOOR PLAN
2%
6
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
P-4
5253 HORIZON DRIVE MALIBU, CA
15
4" GAS BELOW GRADE, FOR CONTINUATION SEE SITE PLAN
OHANIAN RESIDENCE
HB-1
G
3
4"
G
GAS (65 CFH)
PIPING BELOW FLOOR
HW DOWN IN WALL OFFSET BELOW FLOOR
3
14
DW-1
4"
G
2%
3
3" GAS (1087 CFH) 212" GAS (490 CFH)
PIPING IN CEILING SPACE
4"
1" GAS (65 CFH) DOWN IN WALL TO RANGE
2" VENT UP TO 2ND FLOOR AND DOWN TO BASEMENT
G 112" GAS (180 CFH)
3
4"
1" GAS (60 CFH) DOWN TO LOWER FLOOR
3
4
BT-1
3
2" VENT UP TO 2ND FLOOR 2%
4"
NOT FOR CONSTRUCTION USE
NUMBERED NOTES: 1
1
2
3
CW, & 3" WASTE DOWN TO 1ST FLOOR, 1 12" VENT UP OFFSET ABOVE CEILING
3
3 4" CW & 2" WASTE DOWN TO 1ST FLOOR, UP OFFSET ABOVE CEILING
4
1
5
112" HW & 3 4" HWR DOWN TO 1ST FLOOR
6
3
4"
GAS (40 CFH) DOWN TO 1ST FLOOR
7
3
4"
GAS (25 CFH) DOWN TO 1ST FLOOR
8
1" GAS (60 CFH) DOWN TO 1ST FLOOR
9
3
4" PRIMARY COND. DRAIN DOWN IN WALL & CONNECT TO TAIL PIECE ADAPTER, 3 4" SECONDARY COND. DRAIN TERMINATED 1" BELOW CEILING WITH CHROME PLATE ESCUTCHEON
10
5"/3" CONCENTRIC VENT SYSTEM UTR AND DOWN TO 1ST FLOOR, INSTALL PER MANUFACTURER INSTALLATION INSTRUCTION
11
3" AD DOWN TO 1ST FLOOR
2"
CW & 2" WASTE DOWN TO 1ST FLOOR, UP OFFSET ABOVE CEILING
1
2"
HW, & 112" VENT
4"
3
4"
HW, & 2" VENT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
1 2" CW, & 2" WASTE DOWN TO 1ST FLOOR, 1 2" VENT UP OFFSET ABOVE CEILING
112"VENT UTR AND DOWN TO 1ST FLOOR
10 5 2" VENT UTR AND DOWN TO 1ST FLOOR
10 10
3" VENT UTR 3
FAU 3
4" VENT UTR
BT-1
3" VENT UTR
2 2" VENT UTR AND DOWN IN WALL TO 1ST FLOOR
WC-1 3" VENT DOWN TO 1ST FLOOR
L-1
WC-1
2
BT-1
9
8
1
3
2" VENT UTR AND DOWN TO 1ST FLOOR L-1
1 11
AD-1
11
AD-1
8 1
1 2" VENT UP OFFSET ABOVE CEILING AND DOWN TO 1ST FLOOR 2 FAU 2 112" VENT DOWN TO 1ST FLOOR
WC-1 3
3" VENT UTR
3" VENT UTR 2
WC-1
BT-1 2
1
9
2
L-1 BD-1
WC-1
3" VENT UTR
WC-1 4
1
1
L-1
L-1
L-1
1 3" VENT UTR AND DOWN TO 1ST FLOOR
11 AD-1
BT-1
11 AD-1 11
6
AD-1
11
7 AD-1
11 AD-1
SECOND FLOOR PLAN SCALE: 1/4" = 1'-0"
1 P-5 11 AD-1
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
P-5
5253 HORIZON DRIVE MALIBU, CA
3
OHANIAN RESIDENCE
SH-1
JOB TITLE
3
SECOND FLOOR PLAN
BT-1
SHEET TITLE
3
3
3
4"HW(6)
1
4"HW(4)
1
2"HW(2)
3
4"HW(7)
1
2"HW(1)
3
4"HW(8)
1
2"HW(1)
1"HW(10)
4"HW(9)
3
2"HW(1)
4"HW(4)
1
1"HW(11)
1"HW(15)
3
2"HW(1)
11 4"HW(20)
1"HW(16)
1
4"HW(4)
3
2"HW(1)
3
4"HW(4)
11 4"HW(24)
11 4"HW(25)
1
4"HW(4)
2"HW(1) 3
BT 3
L
SH 1
4"CW(4)
2ND FLOOR
1
2"CW(2)
3
3
4"CW(7)
BD 1
2"CW(1)
L
WC 1
2"CW(1)
1
2"CW(2.5)
1
2"CW(1)
1"CW(13.5)
4"CW(11.5)
L
WC 3
2"CW(2.5)
1
4"CW(4.5) 1
1"CW(20)
1
BT
WC 1
2"CW(1)
3
2"CW(2.5)
L
4"CW(4)
1
BT
WC 1
2"CW(1)
3
2"CW(2.5)
L 1
4"CW(4)
BT
WC 1
2"CW(1)
2"CW(2.5)
3
BT 3
4"CW(4)
1
1
2"CW(2.5)
2"CW(1)
114"CW(39) 2"CW(73.5)
1
1 4"CW(24.5) 1 4"CW(28)
11 4"HW(25)
L
WC
4"CW(4)
4"HWR
1 4"CW(31.5)
2"CW(77)
11 4"HW(19)
1
1
2"HW(3)
3
2"HW(4)
3
4"CW(6.5)
3
4"HW(6)
1
1
1ST FLOOR
1
2"CW(1)
1
2"CW(2)
1
2"HW(1)
1
2"HW(2)
FUTURE BAR SINK
1
2"CW(2.5)
SH
1
2"CW(1)
2"CW(1)
1
2"CW(2)
2"HW(1)
1
2"HW(2)
HB
HB
1
2"CW(2.5)
BS
3
4"HW(8)
3
4"CW(4.5)
1"CW(12)
4"CW(9.5)
1"CW(17.5)
1"HW(11)
2"HW(1)
4"CW(7.5)
3
4"HW(5)
11 4"CW(25)
11 4"CW(27)
11 4"CW(30.5)
3
11 4"CW(34.5)
1
4"CW(3.5)
11 4"HW(23)
2"HW(1)
1
3
2"CW(2.5)
4"HWR
WH-2
2"CW(1)
1
2"CW(1.5)
1
2"CW(1)
1
2"HW(1)
1
2"HW(3)
1
2"HW(1)
L
2"CW(77)
2"CW(1)
1
WC
3
11 4"HW(18)
1
1
L
3
4"HW(7)
2"CW(1)
1
WC
3
4"CW(3.5)
HB
DW
KS
1
2"CW(2.5)
L
3
4"CW(4)
1
2"CW(2)
3
4"HW(4)
1
2"HW(2)
BT
WC
NOT FOR CONSTRUCTION USE
3
ROOF
1
2"CW(2.5)
S
1
2"CW(1)
3
4"CW(4)
1
2"HW(1)
3
4"HW(4)
L
WC
HB
1
2"CW(2)
1
2"HW(2)
CWA
2"CW(126)
112"CW(48)
WH-3
1
CP-1 (TYP)
WH-1
2"CW(1)
2" PRV WILKINS 500
SOV (TYP) LS
BP 1
HB
1
1 2"CW(48)
2" BFP WILKINS 975XL
114"CW(25) 3 1
ET-1 (TYP)
1" CW TO POOL EQUIP
4"CW(3.5)
11 4" CW TO LANDSCAPE
2"HW(1)
2" WATER METER
1
2"CW(2.5)
1
2"CW(1)
1
2"HW(1)
L
WC LOWER FLOOR
CW & HW RISER DIAGRAM
1 P-6
NOT TO SCALE
2" VTR
112" VTR
2" VTR
3" VTR
3" VTR
4" VTR
3" VTR
3" VTR
2" VTR
3" VTR
3" VTR
112"
2"
112"
3"
L
112"
112"
2"
L
2"(1) 2ND FLOOR
WC
2"(2)
112"
112"
112"
LS
112"
L
S
112"
BT
2"(2)
BT 3"(3)
2"(2) WC
3"(3)
2"(2)
WC
2"(3)
BT
KS
3"(3)
2"(2)
4"(14)
4"(19)
2"
L
DW
FCO
2"(1) WC
FCO
BT
2"(1)
2"(2)
112"
2"(2)
112"
2"
L
2"(1)
2"(1) WC
FCO 3"(3)
2"(1)
3"(10)
SH 3"(3)
3"(4)
3"(5)
3"(8)
4"(9)
4"(12)
4"(13)
4"(14)
2"(3)
3"(6)
4"(50)
4"(20) 4"(20)
112"
3"(3)
BS
2"(4)
3"(6) 4"(11)
SH
3"(6)
2"(1)
FCO
BD
112"
2"
L 3"(6)
3"(5)
3"(5)
112"
4"(22)
4"(28)
4"(34)
4"(44)
3"(8)
3"(10) 4"(50)
4"(50)
4"(14)
4"(24) 4"(74) 4" WASTE TO SEPTIC TANK
BS
LOWER FLOOR
2"(2)
4"(50)
112"
2"(1) WC
112"
3"
2"(1) WC
3"(3)
L
2"(1)
CWA
3"(3)
112"
L
WC
112"
3"(6)
112"
2"(1)
WC 2"(2)
112"
2"
L
2"(1)
WC 2"(2)
112"
2"
L
112"
2"
3"(6)
FCO
BT
3"(3)
2"
112"
2"
2"(1)
BT
3"(3)
112"
L
2"(1) WC
1ST FLOOR
112"
2"
CREATIVE DESIGN
112"
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
ROOF
2"(1)
3"(3)
SP 1 2" DISCHARGE
3"(5)
WASTE & VENT RISER DIAGRAM
2 P-6
NOT TO SCALE
ROOF FAU 3 (80 CFH)
FAU 2 (60 CFH) 11 4"(80)
2ND FLOOR
1"(60)
3
4"(25)
2"(260) 11 4"(115)
11 4"(180)
212"(490) 1"(50) 3
1"(65)
1
1 4"(80)
3
4"(35)
SPACE HEATER (25 CFH)
4"(25)
3
SPACE HEATER (25 CFH)
4"(25)
1
1 4"(130)
11 4"(100) 1"(50)
3"(1087)
112"(230)
RANGE (65 CFH)
FAU 4 (80 CFH)
DRYER (35 CFH)
FIRE PIT (50 CFH)
3"(1172) 1"(50) 3
1"(65)
1"(65)
FIRE PLACE (65 CFH)
112"(199)
WATER HEATER (199 CFH)
112"(199)
4"(1312)
212"(597)
2"(398)
WATER HEATER (199 CFH)
1ST FLOOR
SPACE HEATER (25 CFH)
WATER HEATER (199 CFH)
112"(199)
SPACE HEATER (25 CFH)
3
4"(25)
SPACE HEATER (25 CFH)
FIRE PLACE (65 CFH)
4"(25)
3
SPACE HEATER (25 CFH)
4"(25)
1"(75) 3
SPACE HEATER (25 CFH)
4"(1452)
4"(1542)
11 4"(140)
4"(25)
11 4"(80)
1"(65)
1"(65)
POOL HEATER (400 CFH)
FIRE PLACE (65 CFH)
FAU 5 (80 CFH)
FIRE PLACE (65 CFH)
11 4" GAS CAP FOR FUTURE BBQ AND FIRE PLACE
4" EARTHQUAKE SOV KOSO 316
2"(400) 114"(105) 4"(1942)
4"(2047)
4" GAS METER
1"(60)
Date
4/12/2013
Scale
AS NOTED
Drawn
PP
Job
7068
Sheet
P-6
5253 HORIZON DRIVE MALIBU, CA
NOT TO SCALE
3 P-6 SHEET TITLE
GAS RISER DIAGRAM
OHANIAN RESIDENCE
LOWER FLOOR
JOB TITLE
FAU 1 (60 CFH)
RISER DIAGRAMS
GAS SOV (TYP.)