COORDINATE THE LOCATION OF ALL DIFFUSER, REGISTER, GRILLES WITH THE ARCHITECTURAL PLAN.

7.

ALL SHEET METAL DUCTWORK SHALL BE NEW GALVANIZED SHEET METAL DUCT GAUGES, CONSTRUCTION, SUPPORT, AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE CALIFORNIA MECHANICAL CODE 2010

8.

9.

BALANCE AND ADJUST ALL DIFFUSERS, REGISTERS, ETC. FOR OPTIMUM AIRDISTRIBUTION AND MINIMUM NOISE. SUBMIT A CERTIFIED AIR BALANCE REPORTTO THE MECHANICAL ENGINEER FOR APPROVAL. BALANCING OF THE SYSTEMS SHALL BE PERFORMED BY AN INDEPENDENT CERTIFIED TEST AND BALANCING AGENCY WHIC SPECIALIZES IN THE BALANCING AND TESTING OF HEATING, VENTILATING ANDAIR CONDITIONING SYSTEMS.

HP

VOLT

PH

HZ

OPER. WEIGHT

1/2

208

1

60

170

CARRIER 58MVB-060-14

LOWER FLOOR

FAU 2

CARRIER 58MVB-060-14

MASTER BEDROOM

FAU 3

CARRIER 58MVB-080-20

MASTER BED, BEDROOM 4

1600

0.5

46.5

75

1

208

1

60

FAU 4

CARRIER 58MVB-080-20

KITCHEN, FAMILY ROOM

2000

0.5

56

75

1

208

1

60

FAU 5

CARRIER 58MVB-080-20

2ND FLR MAIN

1200 1200

2000

0.5 0.5

0.5

35

57

35

56

56

75

1/2

1

208

1

208

1

60

60

11. CEILING DIFFUSERS SHALL BE ANEMOSTAT RMD-S OR APPROVED EQUAL MODULAR WIH OBD.

UNIT

REMARKS

MANUFACTURER AMB. TEMP AND MODEL

COMPRESSOR NO

RLA

COND. COIL FACE ROW FPI (SQ.FT)

FAN MOTOR

COND. FAN

MCA NO.

RPM

FLA

HP

VOLT

PH

HZ

MOCP

OPER. WEIGHT

CU 1

CARRIER 24ANA136

95

1

16.7

22.63

25

1

1

800

1.2

1/12

208

1

60

22

35

191

16X25X3/4

CU 2

CARRIER 24ANA136

95

1

16.7

22.63

25

1

1

800

1.2

1/12

208

1

60

22

35

191

204

20X25X3/4

CU 3

CARRIER 24ANA148

95

1

21.8

25.15

25

1

1

800

1.2

1/4

208

1

60

28.4

40

231

204

20X25X3/4

PRIVDE CONDENSING PUMP

CU 4

CARRIER 24ANA160

95

1

26.4

25.15

20

2

1

800

1.2

1/4

208

1

60

34.2

50

272

20X25X3/4

PRIVDE CONDENSING PUMP

CU 5

CARRIER 24ANA160

170

204

16X25X3/4

PRIVDE CONDENSING PUMP

95

1

26.4

25.15

20

2

1

800

1.2

1/4

208

1

60

34.8

50

S

TEMPERATURE SENSOR

T

THERMOSTAT

REMARKS

UNIT

SERVICE

TYPE

CFM

ESP IN (WG)

FAN RPM

CAPACITY

CD

CEILING DIFFUSER

SECTION THRU RECTANGULAR SUPPLY DUCT

CFM

CUBIC FEET PER MINUTE

SECTION THRU RECTANGULAR RETURN DUCT

CG

CEILING GRILLE

CHS

CHILLED WATER SUPPLY

CHR

CHILLED WATER RETURN

CONC

CONCRETE

COND

CONDENSATE

DUCT DROP IN DIRECTION OF FLOW

CONN

CONNECTION

CEILING DIFFUSER W/DIRECTION OF THROW INDICATED, (3-WAY BLOW SHOWN)

CONT

CONTINUATION

CR

CEILING REGISTER

D

DRAIN

DB

DRY BULB

DL

DOOR LOUVER

STATIC PRESSURE DAMPER COMBINATION FIRE/SMOKE DAMPER

DN

DOWN

DTR

DOWN THRU ROOF

FLEXIBLE CONNECTION, (F.C.)

272

DUCT RISE IN DIRECTION OF FLOW

MOTOR VOLT

PH

HZ

BACKDRAFT DAMPER, (BDD)

REMARKS

EF 1

POWDER ROOMS AND BATHROOMS

LOREN COOK GC-162

CEILING

100

0.25

1,200

103

120

1

60

15

PROVIDE BACKDRAFT DAMPER

SOUND LINED (SL)DUCT W/INTERNAL INSULATION DUCT SIZES SHOWN ARE NET INSIDE DIMENSION.

EA

EXHAUST AIR

(E)

EXISTING

EF 2

MASTER BATHROOM

LOREN COOK GC-182

CEILING

200

0.25

1,400

185

120

1

60

16

PROVIDE BACKDRAFT DAMPER

SOUND TRAP (ST)

ENT

ENTERING

TURNING VANES

EXH

EXHAUST

F.A.

FACE AREA

F

FAHRENHEIT

FLA

FULL LOAD AMPS

FPI

FINS PER INCH

SINGLE LINE RIGID SHEET METAL DUCTWORK

FPM

FEET PER MINUTE

M

FURNISHED & INSTALLED BY MECH. CONTRACTOR

FLEX

FLEXIBLE

GALV.

GALVANIZED

E

FURNNISHED & INSTALLED BY ELECT. CONTRACTOR

GA

GAUGE

HWS

HOT WATER SUPPLY

12. SIDEWALL SUPPLY REGISTERS SHALL BE DOUBLE DEFLECTION GRILLE WITH OPOSED BLADE DAMPER ATTACHED, TWO SETS OF INDIVIDUALLY ADJUSTABLE LOUVER, ANEMOSTAT S2HO

FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER

13. EXHAUST AIR AND RETURN AIR REGISTERS SHALL BE ANEMOSTAT S3HOD, HORIZONTAL FACE BARS SET AN ANGLE OF 45-DEGREES WITH OBD AND FLEXIBLE DUCT ADAPTOR. 14. FLEXIBLE CONNECTION SHALL BE PROVIDED FOR ALL DUCT WORK ATTACHED TO AIR MOVING EQUIPMENT MOUNTED ON OR SUSPENDED FROM VIBRATION ISOLATIONS. FLEXIBLE CONNECTIONS SHALL BE CODE APPROVED NEOPRENE COATED GLASS TYPE FABRIC. 15. THE ELECTRICAL AND PLUMBING CONTRACTORS SHALL PROVIDE FLEXIBLE CONNECTIONS AT ALL MECHANICAL EQUIPMENT MOUNTED ON VIBRATION ISOLATORS AND OR SUSPENDED FROM VIBRATION HANGER.

BELOW

CAP

MODULATING DAMPER, (MOD)

HP (WATTS)

BEL

BRITISH THERMAL UNIT

AUTOMATIC FIRE DAMPER, (AFD)

WEIGHT (LBS)

ABOVE

BTU

SECTION THRU RECTANGULAR EXHAUST DUCT

EXHAUST FAN SCHEDULE MANUFACTURER AND MODEL

ABV

RECTANGULAR DUCT W/SIZE OF SIDE SHOWN INDICATED FIRST

MANUAL VOLUME DAMPER, (MVD)

AS-BUILT RECORD PRINTS MUST BE PROVIDED PRIOR TO JOB COMPLETION.

10. PROVIDE ALL TRANSITIONS AS REQUIRED FROM MAIN DUCT OR BRANCHES TO DIFFUSERS, REGISTERS, OR GRILLES. PROVIDE MVD FOR EACH BRANCH.

FILTER

ME

FURNISHED & INSTALLED BY MECH. CONTRACTOR, WIRED BY ELECT. CONTRACTOR

HWR

HOT WATER RETURN

EM

FURNISHED BY ELECT. CONTRACTOR, INSTALLED BY MECH. CONTRACTOR WIRED BY ELECT. CONTRACTOR

HP

HORSEPOWER

IN

INCH

ISOL

ISOLATOR

LBS

POUNDS

LVG

LEAVING

EMS

ENERGY MANAGEMENT SYSTEM

21. CONTRACTOR TO THOROUGHLY CLEAN ALL PORTIONS OF THEIR WORK, REMOVE ALL DEBRIS AND LEAVE INSTALLATION IN PERFECT CONDITION READY FOR USE.

M.A.

MIXED AIR

MAX

MAXIMUM

22. CONDENSER REFRIGERANT PIPING IN THE STRUCTURE SHALL BE INSTALLED SO AS NOT TOUCH STRUCTURE, FRAMING, OR WALL SURFACES. INSTALL FOAM RUBBER CUSHIONS AT PENETRATIONS TO SEPERATE PIPING FROM STRUCTURE.

MBH

1000 BTU'S PER HOUR

MIN

MINIMUM

MOD

MODULATING DAMPER

23. DUCT INSTALLATION: FOR THERMAL INSULATION, INSULATE ALL SUPPLY AND RETURN AIR DUCT WORK AND PLENUM WITH 2" THICK FIBERGLASS INSULATION WRAPPED AROUND WITH 2" OVERLAP AND WIRED ON #18 GALVANIZED WIRE @ 12" O.C. NRC RATING SHALL BE AT LEAST .80 AT FREQUENCIES ABOVE 1000. ALL DUCTS SHALL HAVE JOINTS AND SEAMS SEALED. FOR SOUND INSULLATION, INSULATE INTERIOR OF SUPPLY AND RETURN AIR PLENUMS WITH MIN. 1" THICK SOUND INTERIOR OF SUPPLY AND RETURN AIR PLENUMS WITH MIN. 1" THICK SOUND ABSORBING INSULATION TO REDUCE NOISE. INSTALL SOUND STRAPS IN PLENUM AND INSULATE BLOWER COMPARTMENT WHERE RETURN AIR REGISTERS ARE IN CLOSE PROXIMITY TO UNITS.

MVD

MANUAL VOLUME DAMPER

NTS

NOT TO SCALE

OPER. WT. OPERATING WEIGHT

24. LABEL ALL EQUIPMENT (AC) TO INDICATE THE SPACE NAME THAT IT IS SERVING.

16. ALL AIR CONDINTIONING FILTERS SHALL BE REPLACED PRIOR ON DAY OF BALANCING. 17. ALL EQUIPMENT TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTION 18. AFFIX MAINTENANCE LABELS TO MECHANICAL EQUIPMENT AND PROVIDE THE OWNER WITH MAINTENANCE AND PARTS MANUALS., LABEL ALL EQUIPMENT WITH THE NAME OF SPACE IT SERVES.

CC

CLOSING COIL IN MAGNETIC STARTER

19. SEAL ALL DUCT JOINTS WITH AN APPROVED TYPE MASTIC.

SW

SWITCH

20. ALL DUCTS PENETRATING THE ROOF SHALL HAVE APPROVED FLASHING AND COUNTER-FLASHING AND BE WEATHER PROOFED.

25. DUCT SYSTEM SHOWN ON THE PLANS ARE SIZED IN ACCORDANCE WITH ASHRAE EQUAL FRICTION METHOD (CHAPTER 35,2005 ASHRAE HANDBOOK). 26. DUCT MATERIAL AND GAGES, PER THE FOLLOWING TABLES: i. TABLE 6-6A & 6-6B DUCT INSTALLATION ii. TABLE 6-7 DUCT SUPPORT a. VERTICAL DUCTS b. HORIZONTAL DUCTS c. HORIZONTAL-DUCTS-TRAPEZE-TYPE SUPPORTS iii. TABLE 6-8 CONSTRUCTION DETAILS FOR ROUND & FLAT-OVAL DTUCTS (LOW, MED, & HI PRESSURE)

SD

SMOKE DETECTOR

OPG

OPENING

OSA

OUTSIDE AIR

PD

PRESSURE DROP

PH

PHASE

PRESS

PRESSURE

POC

POINT OF CONNECTION

PSI

POUNDS PER SQUARE INCH

RA

RETURN AIR

RAR

RETURN AIR REGISTER

REQ'D

REQUIRED

RL

REFRIGERATION LIQUID LINE

RLA

RATED LOAD AMPS

RPM

REVOLUTIONS PER MINUTE

RS

REFRIGERATION SUCTION LINE

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

6.

FAN MOTOR

ROUND DUCT SA

SUPPLY AIR

SP

STATIC PRESSURE

SF

SQUARE FEET

SWR

SIDEWALL REGISTER

SL

SOUND LINED

TEMP

TEMPERATURE

T'STAT

THERMOSTAT

TYP

TYPICAL

UTR

UP THRU ROOF

V

VOLT

W/

WITH

WB

WET BULB

W.G.

WATER GAUGE

(E)

EXISTING

(N)

NEW

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

5253 HORIZON DRIVE MALIBU, CA

COORDINATE THE SIZE, LOCATION, @ SERVICE REQUIREMENTS OF ALL MECHANICAL EQUIPMENT & DUCTWORK WITH THE GENERAL, PLUMBING, ELEC.CONTROL, & FIRE PROTECTION CONTRACTOR PRIOR TO THE START OF CONSTRUCTION. REPORT ALL UNRESOLVED CONFLICTS TO THE ARCHITECT.

COOLING HEATING ESP. (IN WG.) CAPACITY CAPACITY (MBH) (MBH)

CREATIVE DESIGN

5.

THE MECHANICAL CONTRACTOR SHALL OBTAIN & PAY FOR ALL PERMITS, LICENSES & INSPECTIONS REQUIRED TO COMPLETE THIS JOB.

CFM

OHANIAN RESIDENCE

4.

THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, APPARATUS, ACCESSORIES (I.E., THE ENTIRE INSTALLATION) AS FURNISHED BY HIM FOR A PERIOD OF ONE YEAR.

FAU 1

SERVICE

NOT FOR CONSTRUCTION USE

3.

THE INSTALLATION SHALL COMPLY WITH & BE INSTALLED IN ACCORDANCE WITH ALL LEGALLY CONSTITUTED AUTHORITIES & CODES HAVING JURISDICTION. ALSO ALL THE REQUIREMENTS OF LANDLORD.

MANUFACTURER AND MODEL

UNIT

JOB TITLE

2.

THE MECHANICAL CONTRACTOR SHALL FURNISH ALL MATERIAL, LABOR, EQUIPMENT APPURTENANCES, AND ALL CONTRACTUAL EXPENSES REQUIRED FOR THE COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM TO THE SATISFACTION OF THE OWNER, ARCHITECT, AND MECHANICAL ENGINEER.

OUTDOOR UNIT

INDOOR UNIT

LEGENDS, NOTES, AND SCHEDULES

1.

LEGEND & ABBREVIATIONS

SHEET TITLE

HVAC GENERAL NOTES

SPLIT SYSTEM COOLING UNIT SCHEDULE

Sheet

M-1


NOT FOR CONSTRUCTION USE

NUMBERED NOTES: 1

RL & 7 8" RS (INSULATED) UP TO 1ST FLOOR TO RELATED CONDENSING UNIT

2

2" COMBUSTION AIR AND 2" VENT UTR WITH RAIN CAP. (TERMINATE VENT MIN 3'-0" FROM AIR INTAKE)

8"

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

3

EF 1 8X312 EXHAUST DUCT UP TO 1ST FLOOR 26X6 SAR 380 CFM 8X8 CD 80 CFM

8X8 CD 80 CFM T

16X6 SAR 260 CFM

16X6

10X6

14X6

26X8 16X6

28X8 24X24 RAR 1,200 CFM 2 FAU 1

1

LOWER FLOOR PLAN SCALE: 1/4" = 1'-0"

1 M-2

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

5253 HORIZON DRIVE MALIBU, CA

OHANIAN RESIDENCE

JOB TITLE

LOWER FLOOR PLAN

SHEET TITLE

26X6 SAR 400 CFM

Sheet

M-2


NUMBERED NOTES:

1

3

3

2" COMBUSTION AIR AND 2" VENT UTR WITH RAIN CAP. (TERMINATE VENT MIN 3'-0" FROM AIR INTAKE)

FAU 4

1

36X10

T

8X8 CD 80 CFM

EF 1

14X6 SAR 220 CFM

EF 1

8X6 8X8 CD 80 CFM 26X10

8X8 CD 80 CFM

24X6 SAR 380 CFM

10X6 SAR 160 CFM

8X312 EXHAUST DUCT UP TO 1ST FLOOR

12X10

UTR TERMINATE WITH ROOF JACK

26X6 SAR 380 CFM 2

12X8 8X312 EXHAUST DUCT UP TO 2ND FLOOR AND DOWN TO LOWER FLOOR

16X6

12X10

20X10 EF 1

18X10

12X6 12X10

10X6

10X6 16X6 SAR 240 CFM

12X6

10X6 16X6 SAR 240 CFM

16X10

18X10 16X6 SAR 240 CFM

16X6 SAR 240 CFM 8X8 CD 80 CFM 24X6 SAR 340 CFM

24X10

24X36 RAR 2,000 CFM

T

3 FAU 5 26X12 26X12 1

8X8 CD 80 CFM

12X10

16X6 SAR 240 CFM 10X6

EF 1

2

14X6

24X6 SAR 320 CFM

SHEET TITLE

12X10

12X6 20X6 SAR 300 CFM

8X312 EXHAUST DUCT UP TO 2ND FLOOR AND DOWN TO LOWER FLOOR

1

24X36 RAR 2,000 CFM

12X6 20X6 SAR 300 CFM

2

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

1

RL & 7 8" RS (INSULATED) UP OFFSET ABOVE CEILING TO RELATED CONDENSING UNIT 8"

CREATIVE DESIGN

1

3

FIRST FLOOR PLAN SCALE: 1/4" = 1'-0"

1 M-3

FIRST FLOOR PLAN

1

1

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

M-3

5253 HORIZON DRIVE MALIBU, CA

CU 3

CU 5

OHANIAN RESIDENCE

CU 4

JOB TITLE

CU 2

NOT FOR CONSTRUCTION USE

CU 1


NOT FOR CONSTRUCTION USE

NUMBERED NOTES: 1

3

RL & 7 8" RS (INSULATED) DOWN IN WALL TO RELATED CONDENSING UNIT

2

8X312 EXHAUST DUCT UTR AND DOWN TO 1ST FLOOR

8"

3 4 2" COMBUSTION AIR AND 2" VENT UTR WITH RAIN CAP.

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

5

24X24 CR 1,600 CFM 12X6

T

22X12 12X6 16X6 SAR 220 CFM

12X6

2

2 10X6

FAU 3

8X8 CD 80 CFM

EF 1

1

10X8

2

20X6 SAR 260 CFM

5

14X14 CD 280 CFM 3

22X12 EF 1

3

8X8 CD 80 CFM 16X12 16X6 SAR 300 CFM 8X8 CD 160 CFM

18X12 22X22 CR 1,200 CFM 12X10

12X6

EF 1

1 5

FAU 2

EF 1

12X6

EF 1

3

18X12

3

8X8 CD 160 CFM

3 3 8X4

20X6 SAR 260 CFM

20X6 SAR 260 CFM 8X8 CD 180 CFM EF 1

SECOND FLOOR PLAN SCALE: 1/4" = 1'-0"

1 M-4

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

M-4

5253 HORIZON DRIVE MALIBU, CA

OHANIAN RESIDENCE

2

JOB TITLE

26X6 SAR 400 CFM

4

SECOND FLOOR PLAN

8X8 CD 80 CFM

SHEET TITLE

8X8 CD 80 CFM

EF 2


FIXTURE UNITS COUNT(WATER)

GENERAL NOTES

PLUMBING FIXTURE SCHEDULE

HOT AND COLD WATER CALCULATIONS

PLUMBING SYMBOLS LEGEND

CONNECTION SIZES

WC BD

4.

5.

6.

7. 8. 9.

IT SHALL BE THE GENERAL CONTRACTORS RESPONSIBILITY TO ARBITRATE ANY CONFLICTS WITH THE STRUCTURE AND/OR BETWEEN THE TRADES. PROVIDE TRAP PRIMERS, VACUUM BREAKERS AND BACKFLOW DEVICES AS REQUIRED BY THE OWNER THE LOCAL CODE OR AUTHORITY HAVING JURISDICTION. ALL WORKMANSHIP, EQUIPMENT FURNISHED, MATERIALS SYSTEM PROVIDED BY THIS CONTRACTOR SHALL BE GUARANTEED IN WRITING FOR A PERIOD OF ONE FULL YEAR FROM DATE OF FINAL ACCEPTANCE BY THE OWNER. INSULATE FIXTURE TRAPS AND HOT WATER RISERS TO MEET WITH ADA CODE REQUIREMENTS.

BT SH

QTY.

11

LAVATORY WATER CLOSET

11 1

BIDET

6

BATH TUB

2

SHOWER

(WATER) FIXTURE UNIT 1 2.5 1 4 2

(WATER) TOTAL FIXTURE UNIT 11 27.5 1 24 4

BS

BAR SINK

1

1

LS

LAUNDRY SINK

1

1.5

1.5

S

SINK

1

1.5

1.5

1

KS

KITCHEN SINK

1

1.5

1.5

DW

DISH WASHER

1

1.5

1.5

CLOTHES WASHER ASSEMBLY

1

4

PROVIDE LOW FLOW WATER CLOSETS (1.6 GPF).

11. CONTRACTOR SHALL PROVIDE THE NECESSARY MATERIALS FOR BUILDING SETTLEMENT FOR ALL PIPING. 12. CONTRACTOR SHALL ROUTE VENTS THRU ROOF AS NEEDED, AND SHALL MAKE ALL NECESSARY OFFSETS AS REQUIRED FOR INSTALLATION OF VENTS THRU ROOF. VENTS SHALL TERMINATE NOT LESS THAN 10 FEET FROM, OR AT LEAST 3 FEET ABOVE ANY OPERABLE WINDOW, DOOR, OPENING, AIR INTAKE, OR VENT SHAFT, NOR LESS THAN 3 FEET IN EVERY DIRECTION FROM ANY LOT LINE. PER 2010 UNIFORM PLUMBING CODE.

MAX 50 PSI, MIN 45 PSI

B. PRESSURE LOSSES FROM METER TO BOOSTER PUMP 1. LOSS THRU 2" METER (60 GPM): 2 PSI 2. LOSS THRU 2" BFP (WILKINS 375): 14 PSI 3. DEVELOP. LENGTH FROM METER TO BOOSTER PUMP 500 FT 20% FITTINGS 100 FT TOTAL DEVELOPED LENGTH= 600 FT LOSS THROUGH PIPE FRICTION 600' X 7/100 = 42 42 X 0.43 = 18 PSI PRESSURE LOSS BEFORE BOOSTER PUMP

34 PSI

4. PRESSURE LEFT TO BOOSTER PUMP: 45-34 = 5. BOOSTER PUMP DIFFERENTIAL PRESSURE: 75 - 11 =

11 PSI 64 PSI

C. PRESSURE LOSSES AFTER BOOSTER PUMP 1. LOSS DUE TO BUILDING HEIGHT 15 FT X 0.43=

CWA HB BS

4

HOSE BIBB FUTURE OUTDOOR BAR SINK

1

2.5 + 4 1

TOTAL

13. PLUMBING DRAWINGS ARE DIAGRAMATIC AND DO NOT SHOW ROUGH-IN HEIGHTS AND LOCATIONS. 14. INSTALL ALL PLUMBING IN CONFORMANCE WITH THE 2010 EDITION OF THE "UNIFORM PLUMBING CODE".

6 PSI

1

HW FU

1/2"

3

3

3/4"

11

9

1"

23

17

1-1/4"

54

29

1-1/2"

104

48

2"

260

120

2-1/2"

474

246

3"

747

412

4"

1743

851

FIXTURE

FIX ID

DRAIN

TRAP

VENT

COLD

HOT

WC-1

WATER CLOSET

3"

INTEGRAL

2"

1/2"

-

BD-1

BIDET

2"

INTEGRAL

1-1/2"

1/2"

-

L-1

LAVATORY

2"

BATHTUB

BT-1

1-1/4" X 1-1/2"

2"

1-1/2"

1-1/2"

1/2"

1/2"

3/4"

1-1/2"

SYMBOL

COMMENTS

3/4"

D. PRESSURE LEFT TO OVERCOME FRICTION 75 - 33 =

42 PSI

E. TOTAL DEVELOPED LENGTH= 20% FITTING ALLOWANCE = TOTAL DEVELOPED LENGTH

400 FT 80 FT 480 FT

F. AVAILABLE FRICTION HEAD LOSS PER 100FT 42 PSI X 100 FT= 480 FT

ABBREV.

SH-1

SHOWER

2"

2"

WASTE ABOVE FLOOR

W

WASTE BELOW FLOOR

SD

SD

STORM DRAIN ABOVE FLOOR

OD

OD

OVERFLOW DRAIN ABOVE GRADE

SD

SD

STORM DRAIN BELOW FLOOR

PIPE SIZED BASED ON 8 PSI DROP PER 100 FEET 2"

KITCHEN SINK

1-1/2"

1-1/2"

1/2"

-

1/2"

CW

COLD WATER

HW

HOT WATER

HWR DW-1

DISH WASHER

2"

1-1/2"

-

BS-1

BAR SINK

2"

1-1/2"

1-1/2"

1/2"

1/2"

1/2"

S-1

SINK

2"

1-1/2"

1-1/2"

1/2"

1/2"

LS-1

LAUNDRY SINK

2"

1-1/2"

1-1/2"

1/2"

1/2"

(E)

8.8 PSI

HB-1

CLOTHES WASHER ASSEMBLY

2"

2"

1-1/2"

3/4"

3/4"

HOSE BIBB

-

-

-

1/2"

-

G

ICW

ICW

INDUSTRIAL COLD WATER

CD

CD

CONDENSATE DRAIN

D

D (E)

RISER DRAIN EXISTING PIPING WITH SERVICE INDICATED SHUT OFF VALVE CHECK VALVE

CO

CLEANOUT FLOOR CLEANOUT PIPE DROP UNLESS OTHER WISE NOTED

60 GPM

GPM

GAS

CV

FCO

20 GPM

HOT WATER RETURN

G

SOV CWA-1

VENT

1/2"

1/2"

1-1/2"

DESCRIPTION

W

V

20 PSI 33 PSI

3. PRESSURE REQ MOST REMOTE OUTLET: TOTAL PRESSURE LOSSES:

40 GPM

LANDSCAPE

16. ISOLATE ALL WATER PIPING FROM STRUCTURE WITH FELT PADS OR TRISOLATORS.

6.5

CW (FT) FU

7 PSI

86 FU

GPM

15. PROVIDE WATER AND SHUT OFF VALVE AT ALL REFRIGERATORS FOR ICE MAKER CONNECTION. (FINAL CONNECTION BY OTHERS).

4

PIPE SIZE

KS-1

2. 2" PRV WILKINS 500

DOMESTIC WATER HEATER SHALL BE CALIFORNIA ENERGY COMMISSION (CEC) LISTED.

10. PROVIDE VACUUM BREAKERS ON ALL HOSE BIBBS.

A. STREET PRESSURE:

PIPE-UP UNLESS OTHER WISE NOTED 17. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL PLUMBING FIXTURES AND DRAINS.

WATER HEATER SCHEDULE GAS PIPE CALCULATION TYPICAL ALL 49 UNITS

19. BACKFLOW PREVENTION DEVICES FOR CROSS CONNECTION CONTROL SHALL BE INSTALLED TO COMPLY WITH SECTION 603 AND TABLE 6-1

21. SLOPE ALL WASTE PIPING AT 2% (1/4" PER FOOT) UNLESS IT IS IMPRACTICAL DUE TO THE DEPTH OF THE STREET SEWER OR BUILDING STRUCTURAL IMPEDIMENTS. PRIOR APPROVAL FROM THE BUILDING OFFICIAL MUST BE OBTAINED TO REDUCE SLOPE TO 1% (1/8" PER FOOT) FOR 4" DIAMETER AND LARGER PIPE. SEE SECTION 708, 2010 UNIFORM PLUMBING CODE. 22. PIPING PENETRATIONS OF FIRE RESISTANCE RATED WALLS, PARTITIONS, FLOOR, FLOOR/CEILING ASSEMBLIES AND ROOF/CEILING ASSEMBLIESSHALL BE PROTECTED BY AN APPROVED PENETRATION FIRE STOP SYSTEM. 23. LEAD FREE COMPLIANCE REQUIRED EFFECTIVE JANUARY 1, 2010 PER CALIFORNIA HEALTH & SAFETY CODE SEC. 116875

L WC

LAVATORY

11

1

11

WATER CLOSET

11

3

33

FIXTURE

WOOD SHRINKAGE THE CONTRACTOR SHALL ANTICIPATE THE NORMAL SHRINKAGE OF THE WOOD FRAMING DURING CONSTRUCTION AND FOR A PERIOD OF TIME THEREAFTER. IN ORDER TO PREVENT DAMAGE CAUSED BY SUCH SHRINKAGE, THE FOLLOWING MEASURES SHALL BE TAKEN DURING INSTALLATION OF PLUMBING LINES, GAS LINES AND OTHER ELEMENTS WHICH WOULD BE ADVERSELY AFFECTED BY SHRINKAGE: JOISTS AND PLATES SHALL BE TESTED FOR MOISTURE CONTENT DURING FRAMING (SEE STRUCTURAL DRAWINGS).

B.

PROVIDE SWING JOINTS ON BRANCHES CONNECTING TO RISERS.

C.

VALVED CONNECTIONS TO RISERS SHALL BE OF COPPER TUBING INSTALLED SO AS TO PERMIT MOVEMENT OF THE STRUCTURE.

D.

HOLES BORED IN STUDS TO PERMIT PASSAGE OF PIPING SHALL BE DRILLED 3/4-INCH OVERSIZE, AND PIPING INSTALLED IN THE BOTTOM OF THE HOLES.

ID

QUANTITY

CFH EACH

WATER HEATER

3

199

597

DRYER

1

35

35

EQUIPMENT

DESCRIPTION

CFH TOTAL

WH-1, WH-2 WH-3

TANKLESS WATER HEATER

BD

1

BIDET

2

2

BT

BATH TUB

6

2

12

SH

SHOWER

2

2

4

BS

BAR SINK

1

1

1

LAUNDRY SINK

1

2

2

S

SINK

1

2

2

KS

KITCHEN SINK

1

2

2

DW

DISH WASHER

1

2

2

CWA BS

CLOTHES WASHER ASSEMBLY FUTURE OUTDOOR BAR SINK TOTAL

1 1

3 1

3 1 75 FU

RANGE

1

65

F.

WHERE PLASTER, DRYWALL OR TILE IS INSTALLED AROUND HORIZONTAL PIPING, PROVIDE FOR MOVEMENT BY PROVIDING CLEARANCES BETWEEN FINISHES AND PIPE LINES.

RTGH-95DVLN

RHEEM

STORAGE CAPACITY

GAS BTU/H 199,000

RECOVERY RATE

OPERAT. WEIGHT 82 LBS

TANKLESS

PIPES TO BE REMOVED

REMARKS MUST BE CEC LISTED INSTALL PER MANUFACTURER INSTALLATION INSTRUCTION

POC

POINT OF CONNECTION

ABV

ABOVE

BEL

BELOW

BV

BALANCING VALVE

FIRE PLACE

4

65

260

PATIO HEATER

7

25

175

FIRE PIT

1

50

50

FAU-1, & 2

2

60

120

FAU-3, 4, & 5

3

80

240

POOL HEATER

1

400

400

FUTURE FIRE PLACE

1

65

1

40

TOTAL

DN

EQUIPMENT SCHEDULE

(E), EXIST EQUIP ID ET-1

DESCRIPTION EXPANSION TANK

CP-1

CIRCULATING PUMP

MANUFACTURER

MODEL NO.

BELL & GOSSETT

PT-5

BELL & GOSSETT

REMARKS 2 GALLON

65 DESCRIPTION

MANUFACTURER

MOTOR

CAPACITY

40 2047

SP 1

SUMP PUMP - PRE-ASSEMBLED DUPLEX SYSTEM

LIBERTY PUMP 1100 SERIES

40 GPM @ 16' HEAD

HP

VOLTS

PH

4/10

230

1

MAX TOTAL DEVELOPMENT LENGTH = 550'

BOOSTER PUMP SCHEDULE BP 1

BELL & GOSSETT

MODEL No. SERIES 80 112 X 112 X 7B

GPM

HEAD

HP

60

100'

3

RPM

3,500

VOLTS PHASE 230

EXISTING

ELEV

ELEVATION

FT

FOOT, FEET

FU

FIXTURE UNITS

FV

FLUSH VALVE

HDCP

HANDICAP

MTD

MOUNTED

REQ

REQUIRED

SGL

SINGLE

REMARKS

2" DISCHARGE

ST STL TYP

PUMP No. MANUFACTURER

DOWN

1/12 HP-120V, 1PH, 60HZ ALL BROZE

PL-30

SUMP PUMP SCHEDULE PUMP ID

FUTURE BBQ

CEILING

65

4" GAS METER REQUIRED

E.

MODEL NO.

MANUFACTURER

CLG

LS

A.

(WATER) TOTAL FIXTURE UNIT

SYMBOL

20. PROVIDE CLEANOUTS PER 2010 UNIFORM PLUMBING CODE.

REMARKS

STAINLESS STEEL TYPICAL

VB

VACUUM BREAKER

W/

WITH

3

VENTS SHALL BE INSTALLED WITH DOUBLE FLASHING WHICH WILL PERMIT MOVEMENT WITHOUT COMPROMISING WATER TIGHTNESS OF INSTALLATION.

NOTES: NO EXTRA WORK SHALL BE UNDERTAKEN WITHOUT THE WRITTEN APPROVAL OF THE OWNER OR HIS REPRESENTATIVE. THE CONTRACTOR SHALL FULLY DESCRIBE THE EXTRA WORK TO BE PERFORMED AND THE COST THEREOF.

PIPING MATERIALS WASTE, VENT AND STORM DRAINAGE PIPING:

CAST IRON.

DOMESTIC AND INDUSTRIAL WATER PIPING:

TYPE "L" COPPER PIPE.

NATURAL GAS PIPING:

SCHEDULE 40 BLACK STEEL.

LEGENDS, NOTES, AND SCHEDULES

1.

SHEET TITLE

1.

QTY.

(WATER) FIXTURE UNIT

HEATER

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

FIXTURE UNITS COUNT(WASTE)

DROP OR RISE

CREATIVE DESIGN

18. ALL HOT WATER PIPING SHALL BE INSULATED IN ACCORDANCE WITH THE LATEST EDITION OF THE ENERGY EFFICIENCY STANDARDS.

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

P-1

5253 HORIZON DRIVE MALIBU, CA

REVIEW ALL DRAWINGS IN THIS SET PRIOR TO STARTING WORK. NOTIFY THE GENERAL CONTRACTOR OF ANY FURRING OR SLEEVING REQUIREMENTS

L

FIXTURE

OHANIAN RESIDENCE

3.

VERIFY ALL INVERTS, ELEVATIONS, DIMENSIONS AND LOCATIONS PRIOR TO STARTING THIS PORTION OF THE WORK.

SYMBOL

NOT FOR CONSTRUCTION USE

2.

THIS CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED PERMITS AND INSPECTIONS REQUIRED FOR THIS PORTION OF THE WORK.

JOB TITLE

1.


PL

NOT FOR CONSTRUCTION USE

PL

PL

2" GAS FOR CONTINUATION SEE FLOOR PLAN

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

2" CW FOR CONTINUATION SEE FLOOR PLAN

4" GAS (1542 CFH) BELOW GRADE

1" GAS (50 CFH) FOR CONTINATION SEE FIRST FLOOR PLAN

1

2" CW & HW FOR CONTINUATION SEE FLOOR PLAN

4" GAS (1542 CFH) FOR CONTINUATION SEE 1ST FLOOR PLAN

PL

4" GAS (1942 CFH) BELOW GRADE

2" BFP WILKINS 975XL

2" WATER METER

2" WASTE BELOW GRADE TO SEPTIC TANK, FOR CONTINUATION SEE CIVIL DRAWINGS

2" WASTE CAPPED BELOW GRADE FOR FUTURE OUTDOOR BAR SINK

PL

PL

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

P-2

5253 HORIZON DRIVE MALIBU, CA

OHANIAN RESIDENCE

JOB TITLE

1 P-2

SITE PLAN

SCALE: 1/16" = 1'-0"

SHEET TITLE

SITE PLAN


NOT FOR CONSTRUCTION USE

NUMBERED NOTES: 3

4" PRIMARY COND. DRAIN DOWN IN WALL & CONNECT TO TAIL PIECE ADAPTER, 3 4" SECONDARY COND. DRAIN TERMINATED 1" BELOW CEILING WITH CHROME PLATE ESCUTCHEON

2

1" GAS UP TO 1ST FLOOR

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

1

3

CREATIVE DESIGN

4" CW & HW DOWN IN WALL TO SERVE BAR SINK

112" VENT UTR

BS-1

2" VENT UP TO 1ST FLOOR CONTROL PANEL

SP 1

2" SUMP DISCHARGE FCO ON 1ST FLOOR Y-CONNECTION WC-1

2" VENT UP TO 1ST FLOOR

2 L-1

1

3

4" CW & HW UP TO 1ST FLOOR

LOWER FLOOR PLAN SCALE: 1/4" = 1'-0"

1 P-3

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

P-3

5253 HORIZON DRIVE MALIBU, CA

JOB TITLE

LOWER FLOOR PLAN

SHEET TITLE

FAU 1

OHANIAN RESIDENCE

4" WASTE, FOR CONTINUATION SEE 1ST FLOOR PLAN


2" GAS (400 CFH) UP IN WALL TO POOL HEATER

1" CW TO POOL EQUIP 2" CW UP, AND DOWN IN WALL TO BOOSTER PUMP

2" PRV WILKINS 500

HB-1 1

NOT FOR CONSTRUCTION USE

11 4" CW TO LANDSCAPING

NUMBERED NOTES:

2" GAS (400 CFH) BELOW GRADE, FOR CONTINUATION SEE SITE PLAN 2" CW UP IN WALL TO BOOSTER PUMP AND 2" CW BELOW GRADE, DOWN OFFSET BELOW GRADE FOR CONTINUATION SEE SITE PLAN BP 1

1

4" WASTE BELOW GRADE TO SEPTIC TANK, FOR CONTINUATION SEE CIVIIL DRAWINGS

11

5"/3" CONCENTRIC VENT SYSTEM UP TO 2ND FLOOR, INSTALL PER MANUFACTURER INSTALLATION INSTRUCTION

2

2" WASTE UP OFFSET ABOVE CEILING AND DOWN IN WALL

12

3" VENT UP TO 2ND FLOOR

3

3" WASTE UP OFFSET ABOVE CEILING AND DOWN IN WALL

13

3

4

1

4" PRIMARY COND. DRAIN DOWN IN WALL & CONNECT TO TAIL PIECE ADAPTER, 3 4" SECONDARY COND. DRAIN TERMINATED 1" BELOW CEILING WITH CHROME PLATE ESCUTCHEON

5

3

4"

CW & 3" WASTE UP TO 2ND FLOOR

14

3" AD UP TO 2ND FLOOR AND DOWN IN WALL, SPILL 6" ABOVE GRADE

6

3

4"

CW & 2" WASTE UP TO 2ND FLOOR

15

3" AD UP TO 2ND FLOOR

7

112" CW DOWN IN WALL, RUN 11 4" CW TO EACH WATER HEATER

16

3" AD DOWN IN WALL, SPILL 6" ABOVE GRADE

8

112" HW & 3 4" HWR UP OFFSET ABOVE CEILING

9

112" HW & 3 4" HWR UP TO SECOND FLOOR

10

212" GAS (597 CFH) DOWN IN WALL, RUN 1 12" GAS TO EACH WATER HEATER

2"CW

CW & 2" WASTE UP TO 2ND FLOOR

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

2"CW

2"

112"VENT UP TO 2ND FLOOR AND DOWN TO LOWER FLOOR 3

11 4"GAS (80 CFH)

4" GAS (35 CFH) DOWN IN WALL TO DRYER HB-1

112"CW

7 8

CWA-1

WH-1

11 2" VENT UP TO 2ND FLOOR AND DOWN TO BASEMENT

9 2"CW

LS-1

11

1

1 4" GAS (115 CFH)

WH-3

11

2" WASTE FOR CONT SEE LOWER FLOOR PLAN

WH-2 13

L-1

12

FCO 10

1 4" GAS (80 CFH) UP TO 2ND FLR

12 S-1 5

4

WC-1

3 1 4" CW & 2HW DOWN TO BASEMENT

6

1

L-1

WC-1

WC-1

L-1

5

6

PIPING IN CEILING SPACE

G

GAS (25 CFH)

3" GAS (1112 CFH)

3" GAS (1172 CFH)

4" GAS (1312 CFH) G

11 4" GAS (140 CFH)

14

1" GAS (60 CFH) UP TO 2ND FLR G

112" GAS (230 CFH)

112" VENT UP TO 2ND FLOOR

BS-1

11 4" GAS (130 CFH)

112" VENT UP TO 2ND FLR

5

4" GAS (1372 CFH)

2

1" GAS (65 CFH) DOWN IN WALL TO FIRE PLACE

1" GAS (65 CFH) DOWN IN WALL TO FIRE PLACE

4"

CW DOWN IN WALL OFFSET BELOW FLOOR

PIPING IN CEILING SPACE HB-1

6 5 KS-1

6

4 5

11 4" GAS (80 CFH) PIPING IN CEILING SPACE

5

4

4

4" GAS (1452 CFH)

HB-1 11 4" GAS (100 CFH)

2% 4

3

1" GAS (50 CFH) DOWN IN WALL OFFSET BELOW GRADE

1" GAS (50 CFH)

11 4" GAS (75 CFH)

16

13

4

4" GAS (1517 CFH)

16

G

12

2%

2%

1" GAS (50 CFH) 3

4"

GAS (25 CFH)

3

4"

3

GAS (25 CFH)

4"

GAS (25 CFH)

3

4"

GAS (25 CFH)

PIPING IN CEILING SPACE

L-1 WC-1

FCO 3

4"

GAS (25 CFH)

4" GAS (1542 CFH) UP IN WALL OFFSET ABOVE CEILING

6 2

15

SH-1

1" GAS (65 CFH) UP TO 2ND FLOOR 2%

FCO

1" GAS (50 CFH) BELOW GRADE TO FIRE PIT 3 4" GAS (25 CFH) UP TO 2ND FLOOR

1 14 1

FIRST FLOOR PLAN SCALE: 1/4" = 1'-0"

2" CW & HW CAPPED BELOW GRADE FOR FUTURE OUTDOOR BAR SINK

1 P-4

14

SHEET TITLE

14

JOB TITLE

14

FIRST FLOOR PLAN

2%

6

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

P-4

5253 HORIZON DRIVE MALIBU, CA

15

4" GAS BELOW GRADE, FOR CONTINUATION SEE SITE PLAN

OHANIAN RESIDENCE

HB-1

G

3

4"

G

GAS (65 CFH)

PIPING BELOW FLOOR

HW DOWN IN WALL OFFSET BELOW FLOOR

3

14

DW-1

4"

G

2%

3

3" GAS (1087 CFH) 212" GAS (490 CFH)

PIPING IN CEILING SPACE

4"

1" GAS (65 CFH) DOWN IN WALL TO RANGE

2" VENT UP TO 2ND FLOOR AND DOWN TO BASEMENT

G 112" GAS (180 CFH)

3

4"

1" GAS (60 CFH) DOWN TO LOWER FLOOR

3

4

BT-1

3

2" VENT UP TO 2ND FLOOR 2%

4"


NOT FOR CONSTRUCTION USE

NUMBERED NOTES: 1

1

2

3

CW, & 3" WASTE DOWN TO 1ST FLOOR, 1 12" VENT UP OFFSET ABOVE CEILING

3

3 4" CW & 2" WASTE DOWN TO 1ST FLOOR, UP OFFSET ABOVE CEILING

4

1

5

112" HW & 3 4" HWR DOWN TO 1ST FLOOR

6

3

4"

GAS (40 CFH) DOWN TO 1ST FLOOR

7

3

4"

GAS (25 CFH) DOWN TO 1ST FLOOR

8

1" GAS (60 CFH) DOWN TO 1ST FLOOR

9

3

4" PRIMARY COND. DRAIN DOWN IN WALL & CONNECT TO TAIL PIECE ADAPTER, 3 4" SECONDARY COND. DRAIN TERMINATED 1" BELOW CEILING WITH CHROME PLATE ESCUTCHEON

10

5"/3" CONCENTRIC VENT SYSTEM UTR AND DOWN TO 1ST FLOOR, INSTALL PER MANUFACTURER INSTALLATION INSTRUCTION

11

3" AD DOWN TO 1ST FLOOR

2"

CW & 2" WASTE DOWN TO 1ST FLOOR, UP OFFSET ABOVE CEILING

1

2"

HW, & 112" VENT

4"

3

4"

HW, & 2" VENT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

1 2" CW, & 2" WASTE DOWN TO 1ST FLOOR, 1 2" VENT UP OFFSET ABOVE CEILING

112"VENT UTR AND DOWN TO 1ST FLOOR

10 5 2" VENT UTR AND DOWN TO 1ST FLOOR

10 10

3" VENT UTR 3

FAU 3

4" VENT UTR

BT-1

3" VENT UTR

2 2" VENT UTR AND DOWN IN WALL TO 1ST FLOOR

WC-1 3" VENT DOWN TO 1ST FLOOR

L-1

WC-1

2

BT-1

9

8

1

3

2" VENT UTR AND DOWN TO 1ST FLOOR L-1

1 11

AD-1

11

AD-1

8 1

1 2" VENT UP OFFSET ABOVE CEILING AND DOWN TO 1ST FLOOR 2 FAU 2 112" VENT DOWN TO 1ST FLOOR

WC-1 3

3" VENT UTR

3" VENT UTR 2

WC-1

BT-1 2

1

9

2

L-1 BD-1

WC-1

3" VENT UTR

WC-1 4

1

1

L-1

L-1

L-1

1 3" VENT UTR AND DOWN TO 1ST FLOOR

11 AD-1

BT-1

11 AD-1 11

6

AD-1

11

7 AD-1

11 AD-1

SECOND FLOOR PLAN SCALE: 1/4" = 1'-0"

1 P-5 11 AD-1

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

P-5

5253 HORIZON DRIVE MALIBU, CA

3

OHANIAN RESIDENCE

SH-1

JOB TITLE

3

SECOND FLOOR PLAN

BT-1

SHEET TITLE

3


3

3

4"HW(6)

1

4"HW(4)

1

2"HW(2)

3

4"HW(7)

1

2"HW(1)

3

4"HW(8)

1

2"HW(1)

1"HW(10)

4"HW(9)

3

2"HW(1)

4"HW(4)

1

1"HW(11)

1"HW(15)

3

2"HW(1)

11 4"HW(20)

1"HW(16)

1

4"HW(4)

3

2"HW(1)

3

4"HW(4)

11 4"HW(24)

11 4"HW(25)

1

4"HW(4)

2"HW(1) 3

BT 3

L

SH 1

4"CW(4)

2ND FLOOR

1

2"CW(2)

3

3

4"CW(7)

BD 1

2"CW(1)

L

WC 1

2"CW(1)

1

2"CW(2.5)

1

2"CW(1)

1"CW(13.5)

4"CW(11.5)

L

WC 3

2"CW(2.5)

1

4"CW(4.5) 1

1"CW(20)

1

BT

WC 1

2"CW(1)

3

2"CW(2.5)

L

4"CW(4)

1

BT

WC 1

2"CW(1)

3

2"CW(2.5)

L 1

4"CW(4)

BT

WC 1

2"CW(1)

2"CW(2.5)

3

BT 3

4"CW(4)

1

1

2"CW(2.5)

2"CW(1)

114"CW(39) 2"CW(73.5)

1

1 4"CW(24.5) 1 4"CW(28)

11 4"HW(25)

L

WC

4"CW(4)

4"HWR

1 4"CW(31.5)

2"CW(77)

11 4"HW(19)

1

1

2"HW(3)

3

2"HW(4)

3

4"CW(6.5)

3

4"HW(6)

1

1

1ST FLOOR

1

2"CW(1)

1

2"CW(2)

1

2"HW(1)

1

2"HW(2)

FUTURE BAR SINK

1

2"CW(2.5)

SH

1

2"CW(1)

2"CW(1)

1

2"CW(2)

2"HW(1)

1

2"HW(2)

HB

HB

1

2"CW(2.5)

BS

3

4"HW(8)

3

4"CW(4.5)

1"CW(12)

4"CW(9.5)

1"CW(17.5)

1"HW(11)

2"HW(1)

4"CW(7.5)

3

4"HW(5)

11 4"CW(25)

11 4"CW(27)

11 4"CW(30.5)

3

11 4"CW(34.5)

1

4"CW(3.5)

11 4"HW(23)

2"HW(1)

1

3

2"CW(2.5)

4"HWR

WH-2

2"CW(1)

1

2"CW(1.5)

1

2"CW(1)

1

2"HW(1)

1

2"HW(3)

1

2"HW(1)

L

2"CW(77)

2"CW(1)

1

WC

3

11 4"HW(18)

1

1

L

3

4"HW(7)

2"CW(1)

1

WC

3

4"CW(3.5)

HB

DW

KS

1

2"CW(2.5)

L

3

4"CW(4)

1

2"CW(2)

3

4"HW(4)

1

2"HW(2)

BT

WC

NOT FOR CONSTRUCTION USE

3

ROOF

1

2"CW(2.5)

S

1

2"CW(1)

3

4"CW(4)

1

2"HW(1)

3

4"HW(4)

L

WC

HB

1

2"CW(2)

1

2"HW(2)

CWA

2"CW(126)

112"CW(48)

WH-3

1

CP-1 (TYP)

WH-1

2"CW(1)

2" PRV WILKINS 500

SOV (TYP) LS

BP 1

HB

1

1 2"CW(48)

2" BFP WILKINS 975XL

114"CW(25) 3 1

ET-1 (TYP)

1" CW TO POOL EQUIP

4"CW(3.5)

11 4" CW TO LANDSCAPE

2"HW(1)

2" WATER METER

1

2"CW(2.5)

1

2"CW(1)

1

2"HW(1)

L

WC LOWER FLOOR

CW & HW RISER DIAGRAM

1 P-6

NOT TO SCALE

2" VTR

112" VTR

2" VTR

3" VTR

3" VTR

4" VTR

3" VTR

3" VTR

2" VTR

3" VTR

3" VTR

112"

2"

112"

3"

L

112"

112"

2"

L

2"(1) 2ND FLOOR

WC

2"(2)

112"

112"

112"

LS

112"

L

S

112"

BT

2"(2)

BT 3"(3)

2"(2) WC

3"(3)

2"(2)

WC

2"(3)

BT

KS

3"(3)

2"(2)

4"(14)

4"(19)

2"

L

DW

FCO

2"(1) WC

FCO

BT

2"(1)

2"(2)

112"

2"(2)

112"

2"

L

2"(1)

2"(1) WC

FCO 3"(3)

2"(1)

3"(10)

SH 3"(3)

3"(4)

3"(5)

3"(8)

4"(9)

4"(12)

4"(13)

4"(14)

2"(3)

3"(6)

4"(50)

4"(20) 4"(20)

112"

3"(3)

BS

2"(4)

3"(6) 4"(11)

SH

3"(6)

2"(1)

FCO

BD

112"

2"

L 3"(6)

3"(5)

3"(5)

112"

4"(22)

4"(28)

4"(34)

4"(44)

3"(8)

3"(10) 4"(50)

4"(50)

4"(14)

4"(24) 4"(74) 4" WASTE TO SEPTIC TANK

BS

LOWER FLOOR

2"(2)

4"(50)

112"

2"(1) WC

112"

3"

2"(1) WC

3"(3)

L

2"(1)

CWA

3"(3)

112"

L

WC

112"

3"(6)

112"

2"(1)

WC 2"(2)

112"

2"

L

2"(1)

WC 2"(2)

112"

2"

L

112"

2"

3"(6)

FCO

BT

3"(3)

2"

112"

2"

2"(1)

BT

3"(3)

112"

L

2"(1) WC

1ST FLOOR

112"

2"

CREATIVE DESIGN

112"

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

ROOF

2"(1)

3"(3)

SP 1 2" DISCHARGE

3"(5)

WASTE & VENT RISER DIAGRAM

2 P-6

NOT TO SCALE

ROOF FAU 3 (80 CFH)

FAU 2 (60 CFH) 11 4"(80)

2ND FLOOR

1"(60)

3

4"(25)

2"(260) 11 4"(115)

11 4"(180)

212"(490) 1"(50) 3

1"(65)

1

1 4"(80)

3

4"(35)

SPACE HEATER (25 CFH)

4"(25)

3

SPACE HEATER (25 CFH)

4"(25)

1

1 4"(130)

11 4"(100) 1"(50)

3"(1087)

112"(230)

RANGE (65 CFH)

FAU 4 (80 CFH)

DRYER (35 CFH)

FIRE PIT (50 CFH)

3"(1172) 1"(50) 3

1"(65)

1"(65)

FIRE PLACE (65 CFH)

112"(199)

WATER HEATER (199 CFH)

112"(199)

4"(1312)

212"(597)

2"(398)

WATER HEATER (199 CFH)

1ST FLOOR

SPACE HEATER (25 CFH)

WATER HEATER (199 CFH)

112"(199)

SPACE HEATER (25 CFH)

3

4"(25)

SPACE HEATER (25 CFH)

FIRE PLACE (65 CFH)

4"(25)

3

SPACE HEATER (25 CFH)

4"(25)

1"(75) 3

SPACE HEATER (25 CFH)

4"(1452)

4"(1542)

11 4"(140)

4"(25)

11 4"(80)

1"(65)

1"(65)

POOL HEATER (400 CFH)

FIRE PLACE (65 CFH)

FAU 5 (80 CFH)

FIRE PLACE (65 CFH)

11 4" GAS CAP FOR FUTURE BBQ AND FIRE PLACE

4" EARTHQUAKE SOV KOSO 316

2"(400) 114"(105) 4"(1942)

4"(2047)

4" GAS METER

1"(60)

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

Sheet

P-6

5253 HORIZON DRIVE MALIBU, CA

NOT TO SCALE

3 P-6 SHEET TITLE

GAS RISER DIAGRAM

OHANIAN RESIDENCE

LOWER FLOOR

JOB TITLE

FAU 1 (60 CFH)

RISER DIAGRAMS

GAS SOV (TYP.)