VVHS

Page 1

EXHAUST FAN SCHEDULE

SHEET INDEX MOTOR

MANUFACTURER AND MODEL

TYPE

CFM

ESP IN (WG)

FAN RPM

HP (WATTS)

VOLT

PH

HZ

WEIGHT (LBS)

ANCHOR. DETAIL

REMARKS

SHEET TITLE

M-001

LEGENDS, NOTES, AND SCHEDULES

EF 1

TOILET 159

LOREN COOK GC-160

CEILING

140

0.25

1,500

113

120

1

60

15

-

-

PROVIDE BACKDRAFT DAMPER

M-110

MECHANICAL FIRST FLOOR PLAN

EF 2

TOILET 207

LOREN COOK GC-160

CEILING

140

0.25

1,500

113

120

1

60

15

-

-

PROVIDE BACKDRAFT DAMPER

M-111

MECHANICAL SECOND FLOOR PLAN

EF 3

JANITOR 209

LOREN COOK GC-180

CEILING

200

0.25

1,500

192

120

1

60

16

-

-

EF 4

TOILETS 106, 108, 109

LOREN COOK 80C2B

ROOF VENTILATOR

400

0.5

1,260

1/6

120

1

60

30

12 M-500

EF 5

TOILETS 136, 137

LOREN COOK 80C2B

ROOF VENTILATOR

300

0.5

1,239

1/6

120

1

60

30

EF 6

MEN'S RESTROOM 133

LOREN COOK 120C2B

ROOF VENTILATOR

750

0.5

1,151

1/6

120

1

60

EF 7

WOMEN'S 134, 212 AND MEN'S RESTROOMS 211

LOREN COOK 180C3B

ROOF VENTILATOR

1,600

0.5

742

1/4

120

1

60

S

ON-OFF SWITCH

T

THERMOSTAT

ABV ABOVE BEL BELOW BTU BRITISH THERMAL UNIT CAP CAPACITY CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CG CEILING GRILLE CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CR CEILING REGISTER D DRAIN DB DRY BULB DL DOOR LOUVER DN DOWN DTR DOWN TRHU ROOF EA EXHAUST AIR (E) EXISTING ENT ENTERING F.A. FACE AREA F FARENHEIT FLA FULL LOAD AMPS FPI FINS PER INCH FPM FEET PER MINUTE FLEX FLEXIBLE GALV GALVANIZED GA GAUGE HP HORSEPOWER IN INCH ISOL ISOLATOR LBS POUNDS LVG LEAVING EMS ENERGY MANAGEMENT SYSTEM M.A. MIXED AIR MAX MAXIMUM MBH 1000 BTU'S PER HOUR (N) NEW MIN MINIMUM MOD MODULATING DAMPER MVD MANUAL VOLUME DAMPER NTS NOT TO SCALE OPER. WT. OPERATING WEIGHT OPG OPENING OSA OUTSIDE AIR PD PRESSURE DROP PH PHASE PRESS PRESSURE POC POINT OF CONNECTION PSI POUNDS PER SQUARE INCH RA RETURN AIR RAR RETURN AIR REGISTER REQ'D REQUIRED RLA RATED LOAD AMPS RPM REVOLUTIONS PER MINUTE Ø ROUND DUCT SA SUPPLY AIR SP STATIC PRESSURE SF SQUARE FEET SWR SIDEWALL REGISTER SL SOUND LINED TEMP TEMPERATURE T'STAT THERMOSTAT TYP TYPICAL UTR UP THRU ROOF V VOLT VTR VENT THRU ROOF W/ WITH WB WET BULB W.G. WATER GAUGE

SECTION THRU RECTANGULAR SUPPLY DUCT SECTION THRU RECTANGULAR RETURN DUCT SECTION THRU RECTANGULAR EXHAUST DUCT

PROVIDE BACKDRAFT DAMPER

M-130

MECHANICAL ROOF PLAN

10"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-310

BUILDING SECTIONS

12 M-500

10"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-500

DETAILS

55

12 M-500

10"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-510

VIBRATION ISOLATOR DETAILS

90

12 M-500

18"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-511

VIBRATION ISOLATOR DETAILS

M-520

EMS DIAGRAMS

FLEXIBLE CONNECTION R

SERVICE

SHEET NUMBER

DUCT RISE IN DIRECTION OF FLOW

D

UNIT

FAN WHEEL DIA. IN (MIN)

MECHANICAL LEGENDS & ABBREVIATIONS

DUCT DROP IN DIRECTION OF FLOW MANUAL VOLUME DAMPER (MVD) AUTOMACTIC FIRE DAMPER (AFD) MODULATING DAMPER (MOD) BACKDRAFT DAMPER (BDD) STATIC PRESSURE DAMPER

SOUND TRAP SCHEDULE DESIGNATION ST 1-1

MFG MODEL

UNIT SIZE (INCHES)

P.D. (IN. W.G.)

125

250

500

1000

2000

4000

8000

VEL. FPM

PRICE RLX60/2F

18x14

0.23

14

28

42

48

48

37

21

914

1,600

PRICE RMX60/4G

26X12

0.15

16

31

43

51

45

27

13

738

5

112

ON RETURN AIR DUCTWORK

CFM

ST 2-1

DECIBELS

1,600

LENGTH (FT)

OPER. WT. (LBS)

ST 2-2

ST 3-1

ST 4-1

ST 5-1

2,400

PRICE RMX60/4G

28x14

0.22

13

27

40

47

45

28

15

882

5

124

ON SUPPLY AIR DUCTWORK

ST 3-2

ST 4-2

ST 5-2

1,680

PRICE RMX60/1F

36X12

0.17

14

25

42

51

50

34

21

800

5

162

ON RETURN AIR DUCTWORK

3,000

PRICE RLX60/1F

36X14

0.35

14

32

45

50

51

46

26

857

5

176

ON RETURN AIR DUCTWORK

6,000

PRICE RLX60/1F

40X20

PRICE RLX60/1F

48X16

ST 9-1

ST 10-1

ST 9-2

6,000 ST 10-2

4,065

ST 10-3

1,875

PRICE RLX60/1F

36X18

PRICE RMX60/4G

24X16

0.79

11

0.79

14

1.5

14

1.5

13

26

33

32

27

41

45

46

51

51

45

51

50

40

51

47

45

48

45

46

28

30

5

1,260

25

26

ENERGY COMPLIANCE FORMS

SD SMOKE DETECTOR

M-531

ENERGY COMPLIANCE FORMS

BD

BYPASS DAMPER

SOUND LINED (SL) DUCT W/ INTERNAL INSULATION. DUCT SIZES SHOWN ARE NET INSIDE DIMENSION

MEP COMPONENT ANCHORAGE NOTE: ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 1615A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.

FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER

THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.

ON RETURN AIR DUCTWORK

124

COMBINATION FIRE/SMOKE DAMPER

SOUND TRAP

ON RETURN AIR DUCTWORK

162

5

738

M-530

ON SUPPLY AIR DUCTWORK

213

5

857

15

213

5

1,125

M

ON SUPPLY AIR DUCTWORK

ST 1-2

ST 6-1

EMS DIAGRAMS

REMARKS

110

5

M-521

ON RETURN AIR DUCTWORK

SINGLE LINE RIGID SHEET METAL DUCTWORK

A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.

NOTES: PROVIDE DUCT TRANSITION FROM SOUND TRAPS TO RELATED DUCTWORK AS NEEDED

FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE

M

FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR

E

FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR

ME

FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR

EM

FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR

CC

CLOSING COIL IN MAGNETIC STARTER

SW

SWITCH

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

ARCHITECT STAMP

CONSULTANT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22. THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PREAPPROVALS WITH AN OPA #, AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D.

FLS

AC DATE

ZONE

SS

AC NUMBER ZONE NUMBER

Z1-1 1000

ZONE CFM

COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.

BYPASS DAMPER

THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.

BD-1 1000

AC NUMBER

SCHOOL DISTRICT:

DAMPER CFM

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

SPLIT SYSTEM COOLING UNIT SCHEDULE INDOOR UNIT COOLING CAPACITY (MBH)

SEER

290

12

15.2

1

0.33

208

1

ELECTRICAL ROOM 107

570

24

17

1

0.36

208

ELECTRICAL ROOM 124

635

34.2

14

1

0.57

208

MANUFACTURER AND MODEL

SERVICE

FC 1

MITSUBISHI PKA-A12HA4

ELECTRICAL ROOM 155

FC 2

MITSUBISHI PKA-A24KA4

FC 3

MITSUBISHI PKA-A36KA4

UNIT

OUTDOOR UNIT

CFM

MCA

FLA

V

OPER. WEIGHT

ANCHOR. DETAIL

60

29

2 M-511

1

1

60

46

2 M-511

1

60

46

2 M-511

PH

HZ

OPER. WEIGHT

ANCHOR. DETAIL

60

82

1 M-511

1

60

165

1 M-511

1

60

165

1 M-511

MANUFACTURER AND MODEL

MCA

CU 1

MITSUBISHI PKY-A12NHA4

13

15

208

1

1

CU 2

MITSUBISHI PKA-A24NHA4

18

30

208

1

CU 3

MITSUBISHI PKA-A36NHA4

25

40

208

REMARKS

UNIT

MOCP

V

PH

HZ

REMARKS

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

NOTES: 1

PROVIDE WITH CONDENSING PUMP

PACKAGED AIR CONDITIONING UNIT SCHEDULE COOLING CAP UNIT

MANUFACTURER

SERVICE AREA

MODEL

CFM

HEATING CAPACITY

ESP IN (WG) TOTAL

SENSIBLE

EWB TEMP. ºF

ENT COND TEMP ºF

SEER

INDOOR FAN

CONDENSER COIL

EVAPORATOR COIL

OUTDOOR FAN

EER INPUT MBH OUT MBH

ROWS

FPI

FACE AREA

ROWS

FPI

FACE AREA

NO.

SIZE

RPM

BHP

NO.

SIZE

RPM

BHP

COMP NO.1 RLA

COMP NO.2 RLA

OFM (FLA) IFM (FLA) EACH EACH

FILTERS (INCHES)

V

PHASE

HZ

MCA

MOCP

OPER. WEIGHT INCLUD. CURB

ACCESSORIES INTEGRATED

REMARKS

ANCHORAGE

AC 1

CARRIER

CORRIDOR 217

48HCFD05

1,600

1.0

47.7

37

67º

105º

15.6

13

120

96

3

15

7.3

2

17

23.1

1

10X10

1,208

2.9

1

22"DIAM.

1,100

1/4

6.2

-

0.9

2.7

460

3

60

10.8

15

(4)16X20X2 (1)20X36X1

910

1

2

3

4

5

6

7

1 M-510

AC 2

CARRIER

TEXTBOOK 213

48HCFD05

1,600

1.0

47.7

37

67º

105º

15.6

13

120

96

3

15

7.3

2

17

23.1

1

10X10

1,208

2.9

1

22"DIAM.

1,100

1/4

6.2

-

0.9

2.7

460

3

60

10.8

15

(4)16X20X2 (1)20X36X1

910

1

2

3

4

5

6

7

1 M-510

AC 3

CARRIER

CLASSROOM 214

48HCFD07

2,400

1.0

71.2

55.3

67º

105º

-

12

150

120

3

15

8.9

2

17

20.5

1

15X15

949

2.9

2

22"DIAM.

1,100

1/4

9.7

9.7

0.8

3.4

460

3

60

13.1

15

(4)16X20X2 (1)20X36X1

1,275

1

2

3

4

5

6

7

2 M-510

AC 4

CARRIER

CLASSROOM 215

48HCFD07

2,400

1.0

71.2

55.3

67º

105º

-

12

150

120

3

15

8.9

2

17

20.5

1

15X15

949

2.9

2

22"DIAM.

1,100

1/4

9.7

9.7

0.8

3.4

460

3

60

13.1

15

(4)16X20X2 (1)20X36X1

1,275

1

2

3

4

5

6

7

2 M-510

AC 5

CARRIER

CLASSROOM 216

48HCFD07

2,400

1.0

71.2

55.3

67º

105º

-

12

150

120

3

15

8.9

2

17

20.5

1

15X15

949

2.9

2

22"DIAM.

1,100

1/4

9.7

9.7

0.8

3.4

460

3

60

13.1

15

(4)16X20X2 (1)20X36X1

1,275

1

2

3

4

5

6

7

2 M-510

AC 6

CARRIER

MUSEUM 100

48HCFD08

3,000

1.0

88.2

70.1

67º

105º

-

12

224

184

4

15

11.1

2

17

25.1

1

15X15

1,084

2.4

2

22"DIAM.

1,100

1/4

6.1

6.1

0.8

2.6

460

3

60

21.1

25

(4)20X20X2 (1)20X24X1

1,350

1

2

3

4

5

6

7

2 M-510

AC 7

AC 8

CARRIER

FIRST FLOOR NORTH OFFICES

48HCFD24

7,000

1.6

232.6

170.4

67º

105º

-

12

400

324

4

15

26

2

17

29.6

2

18X15 15X11

1,176

8.7

4

22"DIAM.

1,100

1/4

18.6

14.7

0.9

6.4

460

3

60

53.8

60

(9)16X25X2 (4)16X25X1

3,250

1

2

3

4

5

6

7

3 M-510

AC 9

AC 10

CARRIER

SECOND FLOOR LIBRARY

48HCFD24

7,000

1.6

232.6

170.4

67º

105º

-

12

400

324

4

15

26

2

17

29.6

2

18X15 15X11

1,176

8.7

4

22"DIAM.

1,100

1/4

18.6

14.7

0.9

6.4

460

3

60

53.8

60

(9)16X25X2 (4)16X25X1

3,250

1

2

3

4

5

6

7

3 M-510

CARRIER

FIRST FLOOR WEST OFFICES

2

18X15 15X11

60

(9)16X25X2 (4)16X25X1

7

4 M-510

AC 11

48HCFD28

9,000

1.6

284.4

210.8

67º

105º

-

11.2

400

324

4

15

26

2

17

34.3

1,010

8.7

6

ACCESSORIES NOTES: 1

ELECTRICAL

TIME GUARD II CONTROL CIRCUIT

2

100% DRY-BULB TYPE ECONOMIZER

3

100% BAROMETRIC RELIEF

4

MODULATING POWER EXHAUST

5

CO2 SENSOR

6

POWERED CONVENIENCE OUTLET

7

THE AIR-MOVING EQUIPMENT IS SERVED BY A TOTAL COVERAGE SMOKEDETECTION SYSTEM COMPLYING WITH THE CALIFORNIA FIRE CODE

22"DIAM.

1,100

1/4

18.6

18.6

0.9

9.7

460

3

60

63.6

3,470

1

2

3

4

5

6

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

LEGENDS, NOTES, AND SCHEDULES ORIGINAL SCALE 0

1"

JOB NO.: SHEET NUMBER:

M-001

2"


5.5 AC-7 ZONE DAMPER SCHEDULE DESIGNATION

CARRIER MODEL NUMBER

Z7-1

INLET SIZE

CFM

35JN1

1

7

DESIGNATION

2

CARRIER MODEL NUMBER

Z11-1

35JN1

1500

35

35

INLET SIZE

CFM

35

REMARKS

16"Ø

1

Z8-8 1050

4

2

10"ø

10"ø

32

J

10"ø

12"ø

12"ø

16"ø

35JN1

Z7-5

10"Ø

1200

35JN1

1

16"Ø

600

2

2

1

10"Ø

Z11-2

Z11-3

2

1

35JN1

35JN1

Z11-4

2

650

650

35JN1

Z11-5

12"Ø

12"Ø

600

35JN1

1

1

10"Ø

450

2

Z8-7 800

2

1

35JN1

Z7-7

600

35JN1

10"Ø

1300

1

16"Ø

2

1

Z11-6

2

35JN1

Z11-7

800

35JN1

14"Ø

400

2

40

(Z8-2) T

9"ø

24"x20" 10"Ø

1

Z11-8

2

PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK

35JN1

Z11-9

PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC

35JN1

Z11-10

Z8-1

500

35JN1

Z8-3

2

1

16"Ø

10"ø Z8-2 600 12"ø

2

1

10"ø

2

2

12"ø

PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC

14"Ø

500

10"Ø

DESIGNATION

CARRIER MODEL NUMBER

CFM

PASO-18

7,000

BD-7

2

1

BD-8

2

INLET SIZE

44 (Z8-1) T

REMARKS

PASO-18

7,000

1

22"X28"X18"

2

1

35JN1

1400

16"Ø

1

BD-11

2

PASO-24

9,000

22"X42"X18"

1

14 ATHLETIC DIRECTOR 126

35JN1

Z8-8 1 2

800

35JN1

12"Ø

1050

1

14"Ø

2

1

1

2

PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK

2

PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK

38"x20"

M

31

12"ø

17

20"x16"

PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC

12"ø

PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC

BDD 12"x8"

ASB / ACTIVITIES DIRECTOR 127(Z7-8) T

7"ø

24

10"x8" STAFF TOILET 109

Z7-2 700

14"ø

12"x8" 7"ø

51

6

COT 38"x20" 105

4

TOILET 106 8"ø 12"ø

8

CORRIDOR 130 Z7-1 1500

SICK ROOM 104

10"ø 8"ø 16"ø 12"ø

10"ø

DL 12"ø

24 18"ø

18"ø

Z7-3 500 42

16"ø

25

12"ø

ASB WORK & CONFERENCE ROOM 129

28

8 1

UP

C

3

N D 16

10"ø

TOILET 159

EF 1 6

9

STORAGE 158

32"x20"

12"ø

17 PRINCIPAL'S ASSISTANT 12"ø 157

8

8

AP CONFERENCE ROOM 156

M

36"x20"

A

10

OFFICE ASSISTANT 151A

T (Z11-4) T (FC-1)

10"ø 4 M

24"x20" 2

(Z11-3) T

15

14

AP OFFICE 151

9"ø

7

WAITING 150

15 7

9"ø

WAITING 149 12"ø

20

SRO OFFICE 138

48"x

STORAGE 142

(Z11-2) T 14

Z11-3 650

5

AP OFFICE 141 10"ø

Z11-2 650

24"x20"

27 T (Z7-6) M

RECORDS STORAGE 12"ø 101

2

" 20 x 4"

9"ø 8

9.5

53

53

10

UP 12"x8" 14"ø

T (Z11-1)

14"ø

10"ø

6

20 8"ø 10"x8"

STAFF TOILET 137

8"ø 21

3

STAFF TOILET 136 7"ø

6

8"X8" CD-3W, 100 CFM

7

10"x10" CD-4W, 250 CFM

8

12"x12" CD-4W, 300 CFM

9

14"x14" CD-4W, 450 CFM

10

16"x16" CD-4W, 550 CFM

11

10"x10" CR, 235 CFM

12

18"x18" CR, 800 CFM

13

18"x18" CR, 1000 CFM

14

12"x12" CR, 370 CFM

15

10"x10" CR, 220 CFM

16

16"x16" CR, 640 CFM

17

14"x14" CR, 420 CFM

18

16"x16" CR, 550 CFM

19

12"x12" CER, 300 CFM

20

8"X8" CER, 150 CFM

21

10"X8" EXHAUST DUCT UP TO SECOND FLOOR

22

14"X8" EXHAUST DUCT UP TO SECOND FLOOR

23

14"X14" CD-4W, 500 CFM

24

14"X14" CD-2W, 500 CFM

25

16"X16" CD-4W, 650 CFM

26

12"X12" CD-2W, 400 CFM

27

14"X14" CR, 545 CFM

28

18"X18" CR, 900 CFM

29

20"x20" CR, 1200 CFM

30

38"x20" SA (SL) UP TO SECOND FLOOR

31

38"x20" RA (SL) UP TO SECOND FLOOR

32

14"X14" CD-3W, 450 CFM

33

12"X12" CD-3W, 4300 CFM

34

10"X10" CD-3W, 200 CFM

35

12"X12" CD-3W, 350 CFM

36

10"X10" CD-2W, 250 CFM

SCHOOL DISTRICT:

37

12"X12" CD-2W, 300 CFM

38

14"X14" CR, 420 CFM

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

39

18"X18" CR, 755 CFM

40

12"X12" CR, 320 CFM

41

16"X16" CR, 615 CFM

42

12"X12" CR, 270 CFM

43

10"X10" CR, 170 CFM

44

14"X14" CR, 455 CFM

45

18"X18" CR, 1100 CFM

46

14"x6" SA DUCT COVERED WTIH 1/2" MEST SCREEN UP TO SECOND FLOOR

47

14"x6" EXHAUST DUCT UP TO SECOND FLOOR

48

10"x4" EXHAUST DUCT UP TO SECOND FLOOR

49

8"X8" CER, 120 CFM

50

12"X8" EXHAUST DUCT UP TO SECOND FLOOR

51

8"X8" CER, 160 CFM

52

TITUS LINEAR SUPPLY DIFFUSER MODEL MLR-39TZ, 1" SLOT, 4 SLOTS, 6'-0" LONG, 600 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL

53

TITUS LINEAR SUPPLY DIFFUSER MODEL MLR-39TZ, 1" SLOT, 3 SLOTS, 5'-0" LONG, 300 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL

54

36"x12" SA (SL) DUCT UP TO 2ND FLOOR

55

TITUS LINEAR RETURN DIFFUSER MODEL MLR-38TZ, 3/4" SLOT, 3 SLOTS, 5'-0" LONG, 375 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL

56

REFRIGERATION PIPING RL & SL (INSULATED) UP TO SECOND FLOOR

design@csdarchitects.com T:310.821.9200 F:310.821.9201

CONSULTANT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249 FLS

AC DATE

SS

16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

MECHANICAL FIRST FLOOR PLAN

9"ø

19

10"X10" CD-4W, 200 CFM

SHEET TITLE

WOMEN'S RESTROOM14"x8" 134

11

9"ø

6

5

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

COPYRIGHT: CSDA ARCHITECTS 2011

22

20"

12"X12" CD-4W, 400 CFM

27

12"x6"

CORRIDOR 132 53

55

8"ø

18"ø

9.3

7"ø

7"ø

42"x20"

T (Z7-5)

M

BD-11

DUCT SHAFT

M M 24 14"ø "x 14 "

7"ø

M

M

STORAGE 143

3

9"ø

M

4 12"ø

19

10"ø

9"ø 10"ø

36"x20"

2 M-511

DL

10"ø DL

12"ø Z11-4 600

JANITOR 139 16"ø

DL

DL

OFFICE ASSISTANT M 141A

9"ø

SERVER / ELECTRICAL ROOM 155 FC 1

1

40"x18"

STORAGE 152

18

9"ø

12"ø

12"ø

12"x6"

4

8

18"x6"

ELEVATOR 22 -

9"ø T (Z11-1O)

K

52

14"x8" MEN'S RESTROOM 133

SECURITY OFFICE 140 11

DL

CORRIDOR 162

DL

9"ø

10

10

16"ø

12"ø

DL Z11-5 450

TA WORKSPACE 151B

36"x18"

(Z11-5) T

8"ø

STORAGE Z11-11 2200 145 T (Z11-11) 5 18"ø OFFICE ASSISTANT STORAGE 146A 20"x18" 144

28"x18"

12"ø

ELEVATOR MACHINE ROOM 135

7

LOBBY 100

2" x1 " 20

19

13

DL

(Z11-6) T

8"ø

T (Z11-9)

9"ø 9"ø

OFFICE ASSISTANT 154A 12"ø 20"x18" TA WORKSPACE 16"ø 154B

Z11-10 450

9"ø

14 10"ø

13 Z11-6 800

14

9"ø 15 15

12"ø

48"x20"

7"ø

9"ø

10"ø (Z11-8) T

10

14"ø

12"ø

10"ø AP OFFICE 146

48"x20"

T (Z11-7)

14"ø

12"ø WAITING 147

7

36"x20"

3

WAITING 148

7

56 STORAGE 153

28"x18"

10"ø 10"ø PRINCIPAL'S CONFERENCE ROOM 161 10"ø PRINCIPAL'S OFFICE 14 160 10"ø

53

AP OFFICE 154 12"ø

Z11-7 400

4

28"x20"

3

18"x6"

12"x6"

24"x20"

28"x20"

" 12 x 6"

52

FULL LOUVER DOOR 4

4

B

12"x6"

24"x20"

12"X12" CD-4W, 350 CFM

16"ø

Z7-6 600 9"ø

M

53

M-310

48

REGISTRAR 102 9"ø

14"ø

(Z7-1) T

36"x12"

Z11-9 650

L

" 16 "x 22

M

Z11-8 650

9"ø

16"ø CORRIDOR 130

36"x12"

54

D

3

8

24

12"ø 25

E

Z7-5 600

12"ø 28 (Z7-4) T

REGISTRAR WAITING 102A

5

48"x20" RA (SL) DUCT UP TO 2ND FLOOR

34"x20"

16"ø

23

16"ø

4

2

29

Z7-7 1300

3

Z7-4 1200

ATTENDANCE 103

(Z7-7) T

2

F

T (Z7-3) 23

12"ø

1

7"ø 6

12"ø

23

G

49

38"x20"

ASSISTANT 126A

Z7-8 500

7"ø

7"ø

STORAGE 128 32"x20"

12"ø

6

49

2 M-511

12"ø

BD-7

10"ø

9

T ELECTRICAL (FC-2) 107

38"x20"

Z8-7

FC 3

12"ø

12"ø

STAFF TOILET 108 28"x20" 6

STORAGE 125

M

26

16"ø

BDD

2

14"ø

36"x20"

M

30

TEACHER WORKROOM / LOUNGE 110

FC 2 M 2 M-511 (FC-3)

DUCT SHAFT

28

9

16"ø

38"x20"

12"ø

2

14"ø

12"ø Z8-3 1350

38"x20"

BD-8

T (Z8-3)

41

Z8-4 900

41

M T 22"X28"X18"

32

9

ELECTRICAL ROOM 124

48"x20" SA (SL) DUCT UP TO 2ND FLOOR

ARCHITECT STAMP

14"ø

56

M

H

12"ø

33

9"ø

20"x16"

M

COUNSELOR 12"ø 112

9"ø

STORAGE 120

37

1

16"ø

12"ø

COUNSELOR 111 12"ø DL

24"x16"

24 BOOKSTORE 30 122 31 50 M

(Z7-2) T Z8-6

34

Z8-1 500

BYPASS DAMPER SCHEDULE

42

TESTING MATERIALS 8"ø 123

M

2

1

15

38

9"ø

42

COUNSELOR 119 9"ø 12"ø 8"ø Z8-5 500 8"ø

33

BOOK KEEPER 121

PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK

2

1

COUNSELOR 118

45

28"x16"

37

(Z8-6) T

20"x8"

35

2

1

16"Ø

900

35JN1

1

10"Ø

1350

35JN1

Z8-5

1

REMARKS

10"Ø

600

35JN1

Z8-4

1

10"Ø

2200

2

UP

35JN1

Z8-2

INLET SIZE

CFM

12"Ø

450

35JN1

1

36

AC-8 ZONE DAMPER SCHEDULE CARRIER MODEL NUMBER

12"Ø

650

35JN1

Z11-11

DESIGNATION

650

24"x20"

2

500

26"x20"

1

35JN1

32"x24"

Z7-8

24"x14"

38 12"ø

9"ø

16"øCORRIDOR 131

14"x8"

COUNSELOR 113 T (Z8-4)

10"ø

16"x14"

T (Z8-5)

40

COUNSELOR 114

T (Z8-8)

COUNSELOR 24 ASSISTANT 111A 12"ø

Z8-6 1400

40

COUNSELOR 115 10"ø

14"ø

2

1

40

10"ø

2

1

10"Ø

T (Z8-7)

4

39 Z7-6

16"ø COUNSELOR 116

COUNSELOR 14"ø CONFERENCE ROOM 117 10"ø

2

1

10"Ø

10"ø

18"ø

28"x20"

Z7-4

500

1

36"x20"

35JN1

12"Ø

34"x20"

Z7-3

700

24"x8"

35JN1

32"x20"

Z7-2

KEY NOTES

9

8

AC-11 ZONE DAMPER SCHEDULE

REMARKS

16"Ø

1500

6

19

6

ORIGINAL SCALE

20

0

Z11-1 1600

MECHANICAL FIRST FLOOR

F.S. CLOSET 136A

12

1/8" = 1'-0"

1

1"

JOB NO.: SHEET NUMBER:

M-110

2"


5.5

6

7 6

AC-10 ZONE DAMPER SCHEDULE DESIGNATION

Z10-1

Z10-2

CARRIER MODEL NUMBER

CFM

35JN1

2200

35JN1

INLET SIZE

REMARKS

16X12

1100

BYPASS DAMPER SCHEDULE

1

16"Ø

DESIGNATION

2

1

BD-10

CARRIER MODEL NUMBER

CFM

PASO-18

7,000

INLET SIZE

M-310

5

M-310

J

12"x8" (TYP.5) 1

2

2

1

2

2

1

1

2

Z10-4

35JN1

1200

16"Ø

1

2

Z10-5

35JN1

1850

20X14

1

2

PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK

2

2

2

PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK

2

BACK DRAFT DAMPER ST 10-3

PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC

(AC-9) T

H

24"x16"

PH

2

5

14"x12" 3

BD-10

2

12"x8" (TYP.11) 24"x14"

18"x16"

5 TYP. 12"x8"

ACCESS PANEL (TYP.)

5

5 6 Z10-1 2200

9"ø

OPEN

44

Z10-2 1100 12 AV STORAGE 203 M 40"x20"

OFFICE 204 12

12"ø (Z10-2) T

9"ø

M

2

2

28"x10"

13

45

5

14"ø M

CONFERENCE 12"ø ROOM 206 41 9 Z10-5 1850

EF 2

12"ø STAFF TOILET 207

7"ø

LINE OF ROOF ABOVE, SEE A-130

3

3

16

14"x8"

12"x8"

D

12"x8"

EXTERIOR BALCONY

14"ø

14"øCLASSROOM 215

20"x14"

10"ø

24

24

OPEN 46

28"x14"

14"ø

10"ø 36"x12" 24

20"x10" 24

20"x10"

20"x10"

M

47

10"ø 10"ø

8"x4"

24

ST 3-1 10"ø 14"ø

CLASSROOM 214 20"x14"

10"ø

20"x10" 24

21

21

36"x12"

49

PH

9

14"x14" CD-3W, 500 CFM

10

8"x8" CD-2W, 100 CFM

11

16"x16" CD-4W, 600 CFM

12

10"x10" CR, 220 CFM

13

8"x8" CR, 135 CFM

14

14"x14" CR, 420 CFM

15

14"x14" CR, 470 CFM

16

20"x20" CR, 1110 CFM

17

12"X12" C-2W, 300 CFM

18

36"x12" SA (SL) DUCT UTR & DOWN TO FIRST FLOOR

19

36"x12" RA (SL) DUCT THRU CONCRETE WALL, FOR CONTINUATION SEE ROOF PLAN

20

16"x16" CD-4W, 600 CFM

21

18"x18" CR, 840 CFM

22

28"x14" SA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT

23

36"x12" RA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT

24

12"x12" CD-4W 400 CFM

25

14"X14" CD-4W, 530 CFM

26

12"X12" CD-3W, 300 CFM

27

10"X10" CD-4W, 200 CFM

28

14"X14" CR, 500 CFM

29

18"X18" CR, 800 CFM

30

18"X14" SA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT

31

26"X12" RA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT

32

14"X8" EXHAUST DUCT TRANSITION AS REQUIRED UP TO ROOF TO EXHAUST FAN

ELECTRICAL 219 ST 3-2 34

M

49

CONSULTANT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

33

14"X8" EXHAUST DUCT DOWN TO FIRST FLOOR

34

10"X8" EXHAUST DUCT TRANSITION AS REQUIRED UP TO ROOF TO EXHAUST FAN & DOWN TO FIRST FLOOR

35

10"X6" EXHAUST DUCT UTR TERMINATE WITH ROOF JACK

36

12"X12" CER, 300 CFM

37

10"X10" CER, 200 CFM

38

18"X14" EXHAUST DUCT TRANSITION AS REQUIRED UP TO ROOF TO EXHAUST FAN, AND 14"X8" EXHAUST DUCT DOWN TO 1ST FLR.

39

10"X4" EXHAUST DUCT DOWN TO FIRST FLOOR AND UTR TERMINATE WITH ROOF JACK

40

NOT USE

41

8"Ø EXHAUST DUCT UTR TERMINATE WITH ROOF JACK

42

12"X8" EXHAUST DUCT DOWN TO FIRST FLOOR

43

12"X8" EXHAUST DUCT TRANSITION AS REQUIRED UTR TO EXHAUST FAN & DOWN TO FIRST FLOOR

44

38"X20" SA (SL) DUCT DOWN TO FIRST FLOOR AND UTR

45

38"X20" RA (SL) DUCT DOWN TO FIRST FLOOR AND UTR

46

48"X20" SA (SL) DUCT DOWN TO FIRST FLOOR AND UTR

47

48"X20" RA (SL) DUCT DOWN TO FIRST FLOOR AND UTR

48

REFRIGERATION RL & SL (INSULATED) UP THRU ROOF & DOWN TO FIRST FLOOR

49

6X6 CD-2W, 60 CFM

50

6X6 CR, 60 CFM

NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249 FLS

AC DATE

SS

SCHOOL DISTRICT:

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

2

CANOPY

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

T (AC-3)

26

9"ø

COPYRIGHT: CSDA ARCHITECTS 2011

38

SHEET TITLE

50

WOMEN'S RESTROOM 212 37

10"x4" STORAGE 220 50

20"x10"

ARCHITECT STAMP

2

27

M

M

24

12"x8"

8"ø

36"x12"

23

22

10"ø

ST 4-2

10"ø

10"x4"

24

10"ø

24

8"x8" CD-2W, 150 CFM

10

2

M

10"x4" 24

ST 4-1

36"x12"

24 10"ø

9"ø

23

22

28"x14"

10"ø

22

14"ø

DN

8" "x 2 1

12"ø

14"ø

18"x14"

CLOSET 218 10"x4"

28"x14"

24

A

12"ø

CORRIDOR 217

FIRE-RATED WALL (TYP.)

8

2 16"x6" 16"x6"

M

12"ø

T (AC-4)

36"x12"

21

17

9"ø 23

14"x14" CD-3W, 450 CFM

2

OPEN

DF2

32

12"ø

30

26"x12" 12"ø

ST 5-1

10"ø

31

7

design@csdarchitects.com T:310.821.9200 F:310.821.9201

16"x6"

ELEVATOR

CORRIDOR 210

ST 1-1

T (Z10-5) TYP.

12"ø

17

12"ø

31

8"x4"

ST 5-2

30 ST 1-2

2

16"x10"

25

26"x12"

9"ø

28"x14"

20

25

12"ø

ST 2-1

12"ø

36"x12" 21

33

25

T (AC-5)

20

12"ø

48

6

TITUS LINEAR SUPPLY DIFFUSER MODEL MLR-39TZ, 1" SLOT, 4 SLOTS, 5'-0" LONG, 550 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL 10"x10" CD-3W, 250 CFM

16"x6"

12"ø

36"x12"

20"x10"

ST 2-2

5

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

L1

(AC-6) T

16"x10" 16"x12"

12"x8"

BRIDGE

12"ø 12"ø

9.3

9.5

EF 3

10"x6"

SHEAR WALL

18"x14"

PH

2

36"x12"

JANITOR 209

35

14"ø

16"x14"

20"x10"

CLOSET 221

CLASSROOM 216

26"x12"

14"ø

12"ø

TEXTBOOK STORAGE 213

2

20"x8"

12"x8"

" 12 x " 36

12"x8"

T (AC-1)

29

12"ø

21

12"ø

B

28

29

12"x8"

2

19

24"x8" 30"x10"

24"x8"

20

20

OPEN

ST 9-2

12"x8"

2

PH

T (AC-2)

PH

14"x8"

20"x8" ST 6-1

2

28

M

PH

2 12"x8"

14"x8" (TYP.16)

48"x16"

5

M

OP EN

2

OPEN

E

M

M-310

39

40"x 20" RA DUCT (SL) TRANSITION AS REQUIRED UTR TO AC UNIT

2

16"x14"

5

18

4

K

2

20"x10"

4 1

1 40"x20"

WORK ROOM 208

11

L

2

3

14"ø M 20"x14" M

12"ø 16"ø 12"ø (Z10-4) T

M-310

2 ST 9-1

24"x18"

Z10-4 1200 11

5

M Z10-3 600

F

2

24"x10"

(Z10-3) T

14"ø

24"x10"

12"ø

2

LIBRARY 201

5

48"x16"

M

CIRCULATION DESK

12"ø

24"x8" 10

24"x18"

12"ø

15

40"x20"

8

SHEAR WALL

L2

2 38"x16"

OFFICE 205

24"x20"

OPEN

14

C

4

5

5

44

12"ø

2

5

18"x10" 7"ø 6

7"ø

FIRE-RATED WALL (TYP.)

M

G

2

5

30"x10"

7

2

5

14"ø

TECH STORAGE 20243

DN

40"x 20" SA DUCT(SL) TRANSITION AS REQUIRED UTR TO AC UNIT

2

ST 10-2

16"ø

45

ST 10-1

28"x16"

48

5

30"x20"

48

EXTERIOR BALCONY

22"x18"

SHEAR WALL

2

3

4

30"x10"

40"x20"

12"x8"

(Z10-1) T

40"x20"

2

5

DN

1

TITUS LINEAR RETURN DIFFUSER MODEL MLR-38TZ, 3/4" SLOT, 3 SLOTS, 5'-0" LONG, 375 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL

14"x12"

PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC

20"x12"

12"Ø

24"x12"

600

2

1

14"x12"

24"x16"

1

35JN1

18"x18" CD-4W, 750 CFM

M-310

REMARKS

22"X28"X18"

1

M-310 4

2 Z10-3

KEY NOTES

9

8

2

14"x12"

MEN'S 36 RESTROOM 211

11

9"ø 8"ø 8"ø

LINE OF ROOF ABOVE, SEE A-310

12"ø 9"ø

MECHANICAL SECOND FLOOR PLAN

36

ORIGINAL SCALE

37

0

SHEAR WALL

JOB NO.: SHEET NUMBER:

21

12

MECHANICAL SECOND FLOOR 1/8" = 1'-0"

1"

1

M-111

2"


6

5.5

M-310

6

2

7

5

9

8

M-310

KEY NOTES

M-310

4 M-310

J

1

38"X20" SA (SL) DUCT DOWN TO SECOND FLOOR

2

38"X20" RA (SL) DUCT DOWN TO SECOND FLOOR

3

48"X20" SA (SL) DUCT DOWN TO SECOND FLOOR

4

48"X20" RA (SL) DUCT DOWN TO SECOND FLOOR

5

36"X12" SA (SL) DUCT DOWN TO SECOND FLOOR

6

36"X12" RA (SL) DUCT THROUGH CONCRETE WALL

7

FLEXIBLE CONNECTION

8

DUCT SUPPORT ON ROOF

9

REFRIGERATION PIPING RL & SL (INSULATED) DOWN THRU ROOF

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

1 M-500

5 M-500

H ARCHITECT STAMP CU 1 M-511 2

AC 10

3 M-510

20 TONS 1 M-511

CU 3

10 P-500 PIPE SUPPORT (TYP.)

9 8

1

5 M-500

CONSULTANT

G

2 5 8 M-500 12 M-500

EF 4

7

AC 8

3 M-510

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

20 TONS 5 8 M-500

CONSULTANT STAMP

ROOF ACCESS 1

8

5 M-500

NOT FOR CONSTRUCTION USE

2

F AC 7

M

AUTHORITY APPROVAL

3 M-510

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

20 TONS

5 M-500 8 7

ROOF JACK

04-112249 FLS

AC DATE

AC 9

3 M-510 20 TONS

SCHOOL DISTRICT:

E 3

L

M-310

M-310

SCHOOL ADDRESS:

AC 6

5 7

8 6

D

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395

7 5 8 M-500

1

SS

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

2 M-510

7.5 TONS

9.3

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

5 M-500

K

KEY PLAN

ROOF JACK

C

9.5 ROOF JACK

AC 11

4 M-510

(25 TONS) CU 1 M-511 1

9 1 M-510

EF 12 M-500 6

AC 2

10

(4 TONS)

B

7 1 M-510 2 M-510

AC 1

5 8 M-500

(4 TONS)

AC 5

(6 TONS)

7

AC 4

2 M-510

3

(6 TONS)

4 ROOF ACCESS

EF 7

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

12 M-500

COPYRIGHT: CSDA ARCHITECTS 2011 2 M-510

AC 3

SHEET TITLE

MECHANICAL ROOF PLAN

(6 TONS)

11

EF 12 M-500 5

A

ORIGINAL SCALE 0

12

MECHANICAL ROOF PLAN 1/8" = 1'-0"

1

2

3

4

5

1

1"

JOB NO.: SHEET NUMBER:

M-130

2"


M

J

H

G

F

L

K

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

E

design@csdarchitects.com T:310.821.9200 F:310.821.9201

AC 9

6"x16"

10"x16" 36"x12"

10"x30" 20"x30"

20"x40"

18"x22"

12"x20" ST 9-1

ARCHITECT STAMP

20"x40"

20"x12"

6"x12"

CONSULTANT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

LIBRARY SECTION - LOOKING EAST - AC-9 SUPPLY 1/8" = 1'-0"

J

H

G

ENTRY/MUSEUM SECTION - AC-6 SUPPLY & RETURN

2

1

1/8" = 1'-0"

E

F

CONSULTANT STAMP

6

7

8

NOT FOR CONSTRUCTION USE

9

AUTHORITY APPROVAL AC 10

AC 8

AC 7

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

AC 6

AC 9

04-112249

ST 10-1

ST 9-2

FLS

AC DATE

SS

40"x20" 16"x48" 14"x24" Z10-1 2200

20"x40" SA TO ZONE 10-2

20"x24"

18"x24" SA TO ZONE 10-3

48"x16"

SCHOOL DISTRICT:

SA TO ZONE 10-4 & 10-5

ACCESS PANEL

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

LIBRARY 201

16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

CORRIDOR 131

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

LIBRARY SECTION - LOOKING EAST - AC10 SUPPLY 1/8" = 1'-0"

J

H

G

F

AC 8

E

AC 7

AC 6

20"x40"

10"x30"

10"x30"

10"x28"

10"x24"

10"x24"

H

G

CU 2

AC 10

3

1/8" = 1'-0"

J

9.3

AC 9

LIBRARY SECTION - LOOKING NORTH - AC-9 RETURN

4

CU 3

F

EF 4

8"x20"

ST 10-2

8"x12"

38"x20"

38"x20" 38"x20" 38"x20"

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

BUILDING SECTIONS ORIGINAL SCALE 0

LIBRARY SECTION - LOOKING EAST - AC10 RETURN 1/8" = 1'-0"

5

LIBRARY SECTION - DUCT SHAFT 1/8" = 1'-0"

1"

JOB NO.: SHEET NUMBER:

6

M-310

2"


(SUPPLY AIR OR RETURN AIR) ROUND OR RECTANGULAR MAIN DUCT. SEE PLAN FOR SIZES.

EXHAUST FAN

PROVIDE CONTINUOUS SEALANT ALL AROUND EXTERIOR

1 1/8" SHT. METAL HANGER STRAPS SECURED FROM STRUCTURE ABOVE. (TYP)

3'-0" MAX. (TYP.)

SECURE DUCT TO (N) CURB

SEAL WATERTIGHT

3/4" x 4" EMBEDMENT HILTI KB-TZ @ 16" O.C.

FLASHING & COUNTER FLASHING

#8 SHEET METAL SCREW

22 GA. GALV. HOOD @ 30% SLOPE

MY A T

ATTACH EXHAUST FAN TO CURB THRU MASTIC WITH #10 SCREWS @ 6" O.C.

TURN ROOFING & DUCT OVER CURB FLASHING & COUNTER FLASHING

DRAW BAND (TYP.)

MVD

PRE-FAB ROOF CURB

FLEX. DUCT. SEE PLAN FOR SIZES.

ROOFING

CEILING WIRE SUPPORT. (TYP.) CEILING DIFFUSER OR REGISTER

ROOF CONSTRUCTION

DUCT - SEE PLAN FOR SIZES

BACK DRAFT DAMPER

EXHAUST FAN DETAIL NOT TO SCALE

CANT STRIP

MY A T

DUCT -SEE MECHANICAL

CEILING

NOTES: 1.

DUCT ADAPTER SHALL BE SAME MANUFACTURER AS CEILING DIFFUSER OR REGISTER.

2.

FLEX DUCT SHALL BE INSTALLED PER SMACNA MANUAL USING DRAWBAND & INSULATION SHALL BE FITTED OVER THE CORE AND SUPPLEMENTARY SECURED WITH A DRAWBAND.

22"

ROOF DECK

SL DUCT

CEILING DIFFUSERS AND REGISTER SHALL MATCH CEILING.

FLEX DUCT TO CD OR CR

12

NOT TO SCALE

EXPANSIVE FOAM INSLULATION WITH CONT. CAULKING ON BOTH SIDES

DUCT THRU ROOF DETAIL

8

NOT TO SCALE

PIPE SEE PLANS FOR SIZE & CONT.

1-1/2 Hr. & 3 Hr. Rated Fire Damper for 1, 2, 3 & 4 Hr. fire partitions.

(TYPICAL)

3x3x1/4"x4"

LEAD FLASH (TYPICAL)

SEALED OFF FLANGE

POTTORFF MODEL FSD-142

NOT TO SCALE

CONSULTANT STAMP FOR CONNECTION TO STRUCTURAL MEMBER SEE 15 STRUCTURAL DRAWING S-12

NOT FOR CONSTRUCTION USE

4" X 4" X 12 GA. VERTICAL HANGER 1

DAMPER BLADE

ROOF DECK

SLEEVE THRU ROOF (TYPICAL)

BARE METAL DECK

NOT TO SCALE

DUCT SUPPORT ON ROOF DETAIL

9

NOT TO SCALE

ALL FIRE DAMPERS SHALL BE LABELED AND LISTED BY CALIFORNIA STATE FIRE MARSHAL AND/OR UNDERWRITERS LABORATORIES. ALL DAMPERS MUST ALSO BE LEAKAGE RATED AND LABLED UNDER UNDERWRITER LABORATORIES STD. 555S. WITH METAL SEALS ALLOWING NO MORE THAN 10 CFM/SQ.FT. AT 1" W.G. TO 250째 F FOR A FULL 30 MIN. CAN BE MOTOR OPERATED. TORQUE REQ'D. TO MAINTAIN LEAKAGE RATE NOT TO EXCEED 0 LBS. TORQUE. DAMPERS SHALL BE INSTALLED PER MANUFACTURERS INSTALLATION INSTRUCTIONS AND/OR STATE FIRE MARSHAL LISTING NO. 03225. POTTORFF COMPANY, INC. (NO RUBBER SEALS ALLOWED) (LISTING NO.03225:0368:110 AND 03230:0368:111) PROVIDE NON STALL SHUNT MOTOR , 23 VA. MAXIMUM. OR APPROVED EQUAL.

FOR CONNECTION TO STRUCTURAL MEMBER SEE STRUCTURAL DETAIL

PIPE CLAMP 5'-0" MAX. TO STRUCTURAL SUPPORTING MEMBER

VERTICAL RISER

COMBINATION FIRE/SMOKE DAMPER OPENING TO BE SINGLE HEADER FRAMING FOR WOOD OR STEEL. WOOD FRAMED OPENINGS MUST BE LINED WITH MINIMUM 5/8" TYPE X GYP. BOARD. LINING NOT REQUIRED AT STEEL STUD, CONCRETE, OR MASONRY. SUGGESTED CLEARANCE BETWEEN SLEEVE AND OPENING 1/8" FOR EACH 12" DAMPER WIDTH AND HEIGHT FOR EXPANSION. DAMPER TO BE HELD IN PLACE BY RETAINING ANGLES ATTACHED TO SLEEVE ON BOTH SIDES OF PARTITION, AND AROUND ENTIRE PERIMETER OF THE SLEEVE. ANGLES TO BE MIN. 16 GA. 1-1/2" X 1-1/2" OR LARGER AS REQUIRED TO PROVIDE A MIN. 1" OVERLAP OF THE OPENING. ANGLES MAY BE MITERED, BUTTED OR OVERLAPPED AT THE CORNERS. ATTACH ANGLES TO THE SLEEVE (NOT THE PARTITION) WITH SHEET METAL SCREWS, BOLTS OR WELDS AS PER MANUFACTURERS INSTRUCTIONS. CONNECT DUCT TO SLEEVE WITH "S" TYPE SLIP CONNECTIONS. DO NOT USE MECHANICAL FASTENERS.

PIPE CHASE

NEOPRENE PAD (TYP)

VERTICAL RISER PIPE CLAMP SPACER AS REQUIRED TO LIFT CLAMP ABOVE SLEEVE.

DUCT

1

3/ " 8

MACHINE BOLT 2-1/2"x12 GAUGE SHEET METAL STRAP

FLS

SS

DUCT

SOUND TRAP

SCHOOL DISTRICT:

7 M500

7 M500

5'-0" 6" MAX

6" MAX

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395

1 MIN. 2 MAX.

SCHOOL ADDRESS:

3"X3"X14 GA. "L" BRACING

CL OF BOLTS EQUAL CL OF ANGLE EQ.

NEOPRENE PAD (TYP)

5

15 S-12

3"X3"X14 GA. TRANSVERSE BRACE

W.P.

04-112249

INSULATION WHERE REQ'D

3"X3"X16 GA. VERTICAL HANGER

3/ " MACHINE 8 BOLT

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

AC DATE

LONGITUDINAL BRACE (SHOWN DOTTED)

SOUNDTRAP HANGER DETAIL

DUCT SIZE

PIPE THRU ROOF DETAIL DETAIL

1 MIN. 2 MAX.

LONGITUDINAL BRACE ONE EA. SIDE OF DUCT (SHOWN DOTTED) 6'-0" SPACING

3" X 3" X 16 GA.

22 S-12

AUTHORITY APPROVAL

1 1 MIN. 2 MAX.

FOR CONNECTION TO ROOF SEE STRUCTURAL DETAIL

FIRE/SMOKE DAMPER SPECIFICATIONS:

CONSULTANT

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

FLASHING COMPOUND

BLADE BRACKET

1

CREATIVE DESIGN

L 2X2X1/8" VERTICAL ANGLE

FLASHING & COUNTER FLASHING (TYPICAL)

ACCESS DOOR

DUCT THRU WALL DETAIL

1/4"THRU BOLT

1/4"

2.7" MAX.

3.750

5 M-500

UNISTRUT 1 5/8 CHANNEL SERIES P3000 WELDED TO VERTICAL ANGLE

1 1/2" X 1 1/2" X 1/8" ANGLE IRON CROSSBRACE. WELD TO VERTICAL ANGLE

DAMPER FRAME

ROOFING

#8 SHEET METAL SCREWS @ 12" O.C. ON BOT. & SIDES. MAKE WATERTIGHT W/ ELASTIC SEALANT.

TYP. (SL) DUCT

24 GA. GALV. STEEL PIPE FLASHING

FLASHING & COUNTER FLASHING

DUCT SUPPORT, SEE

2'-6"(MAX)

LEAD COLLAR

4

POUR IN PLACE CONCRETE

ARCHITECT STAMP

1/4"PL. CAP

42" O.C.

AIR-FLOW

design@csdarchitects.com T:310.821.9200 F:310.821.9201

NEW ROOFING

SQUARE TO ROUND ADAPTER. SECURED TO DIFFUSER NECK WITH SHEET METAL SCREWS. (SIZE AS REQ'D.)

3.

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

NOT TO SCALE

2

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

DUCT SIZE NOTE: SPACE HANGERS AND BRACES IN ACCORDANCE WITH MECHANICAL CODE AND SMACNA GUIDELINES. BRACE SPACING SHALL NOT EXCEED 20'-0"

PIPE SLEEVE (WHERE OCCURS)

STIFFENING REQUIREMENTS - THREADED ROD OPA-0485

HIGHEST OPERABLE PART OF THERMOSTAT OR CONTROLS AND TOP OF OUTLETS OR SWITCHES

13

46" MAX SIDE-APPROACH 44" MAX FRONT-APPROACH AT WORK STATION

HIGHEST OPERABLE PART OF THERMOSTAT OR CONTROLS AND TOP OF OUTLETS OR SWITCHES

48" MAX.

24" MAX.

BOTTOM OF OUTLETS OR SWITCHES

NOT TO SCALE

10

STANDARD WEIGHT STEEL PIPE SLEEVE OF SIZE TO FIT PIPE AND INSULATION.

SEAL WITH DOWCORNING 700, UL QMFZ2, SMOKE TIGHT MANNER

PIPE AND INSULATION TO BE CENTERED IN SLEEVE - DO NOT SUPPORT PIPE FROM SLEEVE. FINISHED WALL SURFACE

FOR CONNECTION TO STRUCTURAL MEMBER SEE STRUCTURAL DETAIL

FINISHED ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING.

INTERIOR WALL

1" SEALING AND ANCHORING COLLAR SEAL SLEEVE WITH TIGHTLY PACKED SILICON COMPOUND.

1/4" 1"

34" MAX.

EXTERIOR WALL

TIGHTEN TILL SNUG

15 S-12 MAXIMUM 6" (152 mm) 1

1/2" CLEAR MAX.

4" X 4" X 12 GA. VERTICAL HANGER HORIZONTAL BRACE

EQ.

LONGITUDINAL BRACE ONE EA. SIDE OF DUCT (SHOWN DOTTED)

1 MIN. 2 MAX.

3" X 3" X 16 GA.

OUTSIDE

2"MAXIMUM (51 mm)

2"MINIMUM (51 mm)

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

RC-1 ROD STIFFENER (1/2" ROD DIAMETER) (13 mm)

INSULATION WHERE REQ'D

CL OF BOLTS EQUAL CL OF ANGLE EQ.

2"MAXIMUM (51 mm)

MAXIMUM SPACING BETWEEN ROD STIFFNER CLIPS DIM. "B"

TIGHTEN TILL SNUG DUCT

12 ga. CHANNEL 1-5/8"X 1-5/8" MAXIMUM LENGTH 9'-0" (2.7 m)

DUCT SIZE THREADED ROD DIAMETER 1/2"(13)

DETAILS

DIM."A" DIM."B" MAXIMUM MAXIMUM ROD LENGTH SPACING WITHOUT BETWEEN STIFFENER ROD STIFFENRES 22"(559)

18"(457)

NOTICE:ROD STIFFENING REQUIRED ONLY FOR HANGER RODS TO WHICH SEISMIC BRACING HAS BEEN INSTALLED.

ORIGINAL SCALE 0

FINISHED FLOOR

THERMOSTAT MOUNTING HEIGHT DETAIL NOT TO SCALE

PIPE SLEEVE THRU WALL DETAIL 14

COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

ROD STIFFENER CHART

#10 SELF-TAPPING SHEET METAL DUCT SIZE SCREWS EQUALLY SPACED (18" O.C MAXIMUM.) NOTE: SPACE HANGERS AND BRACES IN ACCORDANCE WITH MECHANICAL CODE AND SMACNA GUIDELINES. BRACE SPACING SHALL NOT EXCEED 20'-0"

FINISHED WALL SURFACE

SEAL WATERTIGHT

6

FOR CONNECTION TO STRUCTURAL MEMBER SEE STRUCTURAL 18 DETAIL S-12

TRANSVERSE BRACE 3" X 3" X 16 GA.

COAT EXTERIOR SURFACES WITH TAR COMPOUND.

15" MIN.

NOT TO SCALE

TERMINATE SLEEVE FLUSH WITH FINISHED WALL SURFACES.

2"

FINISHED FLOOR

SINGLE HANGER BRACING FOR ROUND DUCT DETAIL

10' MAX. TO STRUCTURAL SUPPORTING MEMBER

NOT TO SCALE

PIPE SUPPORT - VERTICAL RISER DETAIL

TYPICAL 4 SIDES

COMBINATION FIRE SMOKE DAMPER DETAIL

MAXIMUM 6" (152 mm)

NOT TO SCALE

11

CENTER BRACING FOR RECTANGULAR DUCT DETAIL NOT TO SCALE

7

PIPE SUPPORT DETAIL NOT TO SCALE

3

1"

JOB NO.: SHEET NUMBER:

M-500

2"


3

4

5

6

7

FORM NO.: ________

8

1

WELDING DETAIL

80.375 TOP O.D.

2-6

135.375 TOP O.D.

1.250

1.424

40.688 TOP O.D.

E

70.875 TOP O.D. 37.188 I.D.

1.000 TYP.

ISOLATOR

5.000 TYP x 8

SECURE MICROHOLD (6) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)

69.438

FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL 9 DETAIL S-8

82.875 BOTTOM O.D.

62.438 TYP x 2

18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE

C:sers\jdetweiler\Desktop\Calculations\Isocurbs\HE4F\0403-HE4FD\0403-HE4FD

10"

137.875 BOTTOM O.D.

C

16 GA MICROHOLD ATTACH TO UNIT USING (6) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)

FULL PERIMETER WOOD NAILER

OPA# 0070 14 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT ISOCURB

14 GA CURB

DETAIL

NUMBER OF SPRING PER SHORT SIDE = 2

THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES

MicroMetl Corporation

C

C

9 S-8

D

MICROHOLD

WELDING DETAIL

DETAIL

SECURE MICROHOLD (4) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)

73.375 BASE O.D.

" 10

43.188 BASE O.D.

5.000 TYP x 4

ARCHITECT STAMP

16 GA MICROHOLD ATTACH TO UNIT USING (4) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)

18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE

C

FULL PERIMETER WOOD NAILER

16 GA CURB B

B

ISOCURB DETAIL THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES

NUMBER OF SPRING PER LONG SIDE = 2

MicroMetl Corporation

PAGE 1 of 2

B

CONSULTANT

STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB

0403-372D-08B 18" TALL 0403-372D 21" TALL 0403-372D-14B 24" TALL

CREATIVE DESIGN

PAGE 1 of 2

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

Indianapolis, IN. : (800) 662-4822 Sparks, NV. (800) 884-4662

Sparks, NV. (800) 884-4662

CONSULTANT STAMP

Longview, TX. (903) 248-4800

Longview, TX. (903) 248-4800 A

WEIGHT: 670/700/730 DRAWN BY: JD

1.000 TYP.

ISOLATOR

16 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT

Indianapolis, IN. : (800) 662-4822

DATE: 01/17/2011

MEETS SEISMIC REQUIREMENTS FOR 2010 CBC & 2009 IBC

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 2 3 4 1

5

6

7

WEIGHT: 325/340/355 LBS. DRAWN BY: JD

PRINTED: 11/29/2011

A

2.920

OPA# 0070

STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB

0403-HE4FD-08B 18" TALL 0403-HE4FD 21" TALL 0403-HE4FD-14B 24" TALL

13.875

DATE: 01/01/2011 MEETS SEISMIC

PRINTED: 8/10/2011

B

NUMBER OF SPRING PER LONG SIDE = 5

FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL DETAIL

design@csdarchitects.com T:310.821.9200 F:310.821.9201

1.298

LY P P SU

DETAIL

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

1/8

D

MICROHOLD

WELDING DETAIL

SEAM WELD TOP AND SIDES (TYP. 4 CORNERS)

6.000

32.063

RET URN

20.250

D

2-6

1.250

2.983

22.188

8

4.684 13.625

25.938

0.134

67.375 I.D.

27.875

RN U T RE

7

WELDING DETAIL

1/8

LY 63.875 P P SU

6

1.000

4.684

131.875 I.D.

D

5

10 GA SUPPORT

6.000 SEAM WELD TOP AND SIDES (TYP. 4 CORNERS)

76.875 I.D.

4

.750 Created: 1/18/2011 9:14:11 AM

E

3

FORM NO.: ________

10 GA SUPPORT 0.134

2

Created: 1/2/2011 7:33:37 AM

2

T:\Solidwrk\ISOCURB\372\0403-372D\0403-372D

1

REQUIREMENTS FOR 2010 CBC & 2009 IBC THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 2 3 4 1

8

5

6

7

NOT FOR CONSTRUCTION USE

8

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

3

2

3

4

5

6

FORM NO.: ________

7

8

1

WELDING DETAIL

Created: 1/18/2011 10:14:11 AM

SEAM WELD TOP AND SIDES (TYP. 4 CORNERS) 1.250

4.684

151.625 TOP O.D. 148.125 I.D.

1.424

E

53.500 TOP O.D. 50.000 I.D.

2.983

5.000 TYP x 8

22.188

81.750 TOP O.D. 78.250 I.D.

154.125 BOTTOM O.D. 48.708 TYP x 2

FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL 9 DETAIL S-8

82.875 BOTTOM O.D.

18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE

14 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT ISOCURB

B

NUMBER OF SPRING PER LONG SIDE = 5

MicroMetl Corporation

14 GA CURB

DETAIL

NUMBER OF SPRING PER SHORT SIDE = 2

THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES

FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL DETAIL

C

C

9 S-8

40.063 2.919 1.000 TYP.

ISOLATOR

D

MICROHOLD

WELDING DETAIL

16 GA MICROHOLD ATTACH TO UNIT USING (6) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)

" 10

56.000 BASE O.D. 18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE

16 GA CURB ISOCURB

B

NUMBER OF SPRING PER LONG SIDE = 4

MicroMetl Corporation

PAGE 1 of 2

Longview, TX. (903) 248-4800 A

PRINTED: 8/10/2011

DATE: 01/17/2011

MEETS SEISMIC REQUIREMENTS FOR 2010 CBC & 2009 IBC

5

6

7

8

WEIGHT: xxxx/xxxx/xxxx DRAWN BY: JD

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

DETAIL THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES 0403-972D-08B 18" TALL 0403-972D 21" TALL 0403-972D-14B 24" TALL

C

B

STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB PAGE 1 of 2

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

Indianapolis, IN. : (800) 662-4822

Longview, TX. (903) 248-4800

SCHOOL ADDRESS:

KEY PLAN

DETAIL

16 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT

B

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

SECURE MICROHOLD (6) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)

84.250 BASE O.D.

5.000 TYP

OPA# 0070

Sparks, NV. (800) 884-4662

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 1 2 3 4

1.172

LY P P SU

Sparks, NV. (800) 884-4662

WEIGHT: 820/850/890 DRAWN BY: JD

4.684

FULL PERIMETER WOOD NAILER

Indianapolis, IN. : (800) 662-4822

A

1.250

15.688

STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB

0403-HE6FD-08B 18" TALL 0403-HE6FD 21" TALL 0403-HE6FD-14B 24" TALL

RET URN

DETAIL

FULL PERIMETER WOOD NAILER

OPA# 0070

SEAM WELD TOP AND SIDES (TYP. 4 CORNERS)

1/8

MICROHOLD

16 GA MICROHOLD ATTACH TO UNIT USING (5) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)

" 10

.750

D

SECURE MICROHOLD (5) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)

N 69.438 R U RET C

D

WELDING DETAIL

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

31.375

C:sers\jdetweiler\Desktop\Calculations\Isocurbs\HE6F\0403-HE6FD\0403-HE6FD

LY 63.875 P P SU

1.000 TYP.

2-6

COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

DATE: 01/07/2011

MEETS SEISMIC REQUIREMENTS FOR 2010 CBC & 2009 IBC

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 1 2 3 4

5

6

7

8

VIBRATION ISOLATOR DETAILS ORIGINAL SCALE 0

VIBRATION ISOLATOR DETAIL (AC-11) NOT TO SCALE

4

SS

SCHOOL DISTRICT:

8

6.000

15.313

ISOLATOR

7

WELDING DETAIL

1/8

25.938

6

10 GA SUPPORT

27.875

D

5

0.134

6.000

E

76.875 I.D.

4

.750

2-6

80.375 TOP O.D.

3

FORM NO.: ________

10 GA SUPPORT 0.134

2

FLS

AC DATE

PRINTED: 8/10/2011

1

1

NOT TO SCALE

Created: 1/7/2011 10:50:04 AM

NOT TO SCALE

04-112249

VIBRATION ISOLATOR DETAIL (AC-1 & AC-2)

C:sers\jdetweiler\Desktop\Calculations\Isocurbs\972\0403-972\0403-972

VIBRATION ISOLATOR DETAIL (AC-7 THRU AC-10)

VIBRATION ISOLATOR DETAIL (AC-3 THRU AC-6) NOT TO SCALE

2

1"

JOB NO.: SHEET NUMBER:

M-510

2"


15 1-3/4 TYP.

ISOLATOR/RESTRAINTS ARE OSHPD PRE-APPROVED #OPA-0029

12

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

6

5

1/2 x 1-1/2" LONG STUD

2-1/2

2-1/2

10 7-3/4

1-1/8 ARCHITECT STAMP

1/4"

1/4"

RIBBED NEOPRENE PAD

7-1/4" OPER HT. VERTICAL LIMIT STOP CONSULTANT

5

5

5

FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL DETAIL DRAWING

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

10 S-8

CONSULTANT STAMP

NOT FOR CONSTRUCTION USE

M.W. SAUSSE' & CO., INC. VALENCIA, CALIFORNIA 91355

V IBREX TYPE RMLS-EQ-3

JOB NAME: CUST.: CUST. P.O.: MECH. ENGR .: MARK:

--

REVISIONS:

DRN:

DATE: DEC, 19, 2011 SHEET NO.:

-CONDENSING UNIT

A: B: C: D:

JO

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249

E1

VIBRATION ISOLATOR DETAIL (CU-1, CU-2 & CU-3) NOT TO SCALE

FLS

AC DATE

SS

1

SCHOOL DISTRICT:

FC -

WALL BRACKET BY MANUFACTURER

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

#8 METAL SCREWS, 3/4 "LONG, (2) EACH SIDE. SCREWS MUST BE INSERTED INTO METAL STUDS.

16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

FC UNIT MOUNTING DETAIL (FC-1, FC-2 & FC-3) NOT TO SCALE

2

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

VIBRATION ISOLATOR DETAILS ORIGINAL SCALE 0

1"

JOB NO.: SHEET NUMBER:

M-511

2"


AC Unit w/Power Exhaust Typical of (6) - AC-1, AC-2, AC-3, AC-4, AC-5, AC-6 & AC-9 CONTROL PANEL #

5A Ckt Bkr

LABEL DESCRIPTION:

AC - FILTER STATUS - DI

TB-PWR

TCP-

H

Panel Rm Location:

G

AC - SUPPLY AIR TEMPERATURE - AI

3

2

Unit Power

N

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

TX-1

TX PROVIDED BY SUNBELT CONTROLS

50va

NEMA 1 12HX12W SCREW COVER

design@csdarchitects.com T:310.821.9200 F:310.821.9201

X1+

X1-

GAS

REC

TB-1 24VAC Power to below

OSA

TB-PWR

N.C.

HI

SF

DX

LO

10A

H N G

ON

1

50VA

24VAC

R

AC - SUPPLY FAN STATUS - DI

AC - SUPPLY FAN START/STOP - DO AC - COOLING STAGE-1 ENABLE - DO AC - COOLING STAGE-2 ENABLE - DO AC- HEATING STAGE-1 ENABLE - DO AC - HEATING STAGE-2 ENABLE - DO

G Y1

OFF

Y2 W1 W2

R

AUTOMATEDLOGIC

VA

20

CORPORATION

Gnd 24Vac Lstat

PROGRAM/ FB NAME(S)

Rx

Net +

Tx

IN-1

Thermistor/dry contact 0-5Vdc On

1

Rnet

MSTP ARC156

9600

Inputs: 5V Max

76.8k

Poly tubing from space static tip to AC unit mfr power exhaust transducer, provide by unit mfr. (Typical)

Gnd

Terminal Setting

Point Addr. & Type

IN-2 Gnd

IN-3 AO-1 Gnd

Universal Input Verification Checklist:

AO-01

DO-3

DO-1

Power for D.O.'s

BUSS

®

BACnet

Room Temp Sensor T-STAT LOCKING COVER

COOLER

AC/RTU - HEATING STAGE-2 ENABLE - DO AC/RTU - HEATING STAGE-1 ENABLE - DO

DO-3

DO-04

DO-2

AUTOMATED LOGIC

Y1 3/8" Pneumatic Tubing

AC/RTU - SUPPLY FAN START/STOP - DO

G

24VAC POWER

DO-1 BUSS

CONSULTANT

RSPLUS

RA

Y2

AC/RTU - COOLING STAGE-1 ENABLE - DO

DO-03

OCCUPIED

W1

DO-4

DO-05

MANUAL ON

W2

DO-5

AC/RTU - COOLING STAGE-2 ENABLE - DO

UI-04

SA

WARMER

Point Addr. & Type

Off

Offset (if appl)

Actual Fld. Measured Value

Input Value Reading

Date Verified

DO-4

DO-2

CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

GND AO-1

DI-03

Gnd IN-4 IN-5 LED

Note: Economizer w/Power Exhaust

DO-5

Class 2 24 Vac, 50-60 Hz 20VA, 0.83A 24Vdc, 0.2A, 5W Use Copper Conductors Only

IN-4

AI-02

IN-3 Gnd

AC/RTU - FILTER STATUS - DI

By Tech Initials

DI-01

On

AC/RTU - SUPPLY AIR TEMPERATURE - AI

IN-2 Gnd

Digital Date Verified

IN-1 Gnd

N.O.

Digital Output Verification Checklist: By Tech Initials

AC/RTU - SUPPLY FAN STATUS - DI

Check’d

Point Addr. & Input #

Room Temp Sensor

CONTROLLER

Gnd

LED

AUTOMATED LOGIC

ZN551

CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

IN-5

3

38.4k

MSTP Baud

Gnd

100

75

50

25

0

Rnet

Date Verified

By Tech Initials

Analog Out %

Gnd Rnet+ Rnet+12V

MANUAL ON

2

19.2k

IN-1

Grn Wht Blk Red

OCCUPIED

1

3

2 3

COOLER

Gnd Rnet+ Rnet+12V

2

2

Communications Selection

+12V

1 2 3 4

4

3

Gnd Gnd Rnet + Rnet -

WARMER

ARCHITECT STAMP

4

Rnet+

Analog Output Verification Checklist:

N.C.

EA

Thermistor/dry contact 0-5Vdc

IN-2

+12V Rnet-

1

5 6

Tens

4

5 6 4

CR 2032

Sense

2 3

4

0 1

9 0 1

9

5 6

2 3

2 3

7 8

24 Vac Pwr

+ Err

Ones

5 6 4

0 1 7 8

Jumper: Gain1

Run

7 8

7 8

.equipment

Term

Rnet

Format

Batt

-

9 0 1

ZN551

BT485

W2

C

Ground

Net Shield

OR

T-STAT LOCKING COVER

Bias

CMnet

ADDRESS

9

Comm from previous & to next control module (See network riser diagram)

CONTROL MODULE

Arc156

Net + Net Shield

Y2 W1

O N

ALC Controller Checklist:

Wire to factory provided power exhaust transducer

Units with factory provided and controlled power exhaust with vfd.

G Y1

R

CREATIVE DESIGN

DO-02

UI-05

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

DO-01 DP-TIP-S HIGH

CONSULTANT STAMP

AH Space Static Tip NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

AC RTU MODULE DETAIL NOT TO SCALE

AC RTU CONTROL SCHEMATIC

2

NOT TO SCALE

04-112249

1

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

NEMA 1 12HX12W SCREW COVER AC - FILTER STATUS - DI

CONTROL PANEL #

5A Ckt Bkr

LABEL DESCRIPTION:

H

TCP-

N

Panel Rm Location:

G

Unit Power

3

TB-PWR 10A

50va

50VA

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

GAS

X1+

X1-

OFF

REC

OSA

TB-1 24VAC Power to below

N.C.

HI

Bias

Rx

Net +

Tx

SF

DX

LO

CS

CMnet

Net -

Thermistor/dry contact 0-5Vdc

W1

IN-2 Thermistor/dry contact 0-5Vdc

+12V

2

2 3

2 3

Gnd

AUTOMATEDLOGIC

ALC Controller Checklist:

20

CORPORATION

Comm from previous & to next control module (See network riser diagram)

CONTROL MODULE

Arc156

Net + Net Shield

ADDRESS

Communications Selection

Rnet

MSTP

VA

19.2k

38.4k

76.8k

IN-1 Inputs: 5V Max

Gnd

MSTP Baud

IN-2 Gnd

WIRE TO FACTORY PROVIDED POWER EXHAUST TRANDUCER

Gnd

IN-3 AO-1 Gnd

PROGRAM/ FB NAME(S)

CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

ZN551 CONTROLLER

DO-5

Class 2 24 Vac, 50-60 Hz 20VA, 0.83A 24Vdc, 0.2A, 5W Use Copper Conductors Only

DO-4

DO-2

IN-4

ZN551

IN-5 LED

.equipment

EA

DO-3

Gnd

BT485

C

UNIT WITH FACTORY PROVIDED AND CONTROLLED POWER EXHAUST

ARC156

9600

+12V

Gnd 24Vac

O N

1

Rnet -

W2

4

3

3

4

Gnd

Rnet +

KEY PLAN

W1

On

RnetRnet+

R

Y2

AC - HEATING STAGE-1 ENABLE - DO

IN-1

2

5 6

Tens

CR 2032

Sense

1

4

4

5 6 4

0 1

0 1

Ones

9

9

5 6

2 3

2 3

7 8

4

Err 0 1

0 1 7 8

Y2

+

Y1

AC - COOLING STAGE-2 ENABLE - DO

Pwr Run

9

9

5 6

7 8

Y1

24 Vac

Batt

-

7 8

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

G

AC - COOLING STAGE-1 ENABLE - DO

Format

Jumper: Gain1

R

AC - SUPPLY FAN START/STOP - DO

G

Rnet

Ground

Shield

24VAC

R

AC - SUPPLY FAN STATUS - DI

2 Lstat

16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

H N G

ON

TX-1

AC - SUPPLY AIR TEMPERATURE - AI

5

TB-PWR

SS

SCHOOL DISTRICT:

VVT AC Unit w/Power Exhaust Typical of (4) - AC-7, AC-8, AC-10 & AC-11

VVT AC Unit w/Power Exhaust Typical of (4) - AC-7, AC-8, AC-10 & AC-11

FLS

AC DATE

DO-1 CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

Power for D.O.'s

BACnet

N.C.

BUSS

®

OR

Term

2 3

IN-3 Gnd

Offset (if appl)

Actual Fld. Measured Value

Input Value Reading

Date Verified

By Tech Initials

Point Addr. & Type

AC - SUPPLY AIR TEMPERATURE - AI

On

IN-2 Gnd

5

AC - RETURN AIR TEMPERATURE - AI AC - FILTER STATUS - DI

Gnd IN-4 IN-5 LED

AC - HEATING STAGE-1 ENABLE - DO DO-4

AC - COOLING STAGE-2 ENABLE - DO DO-05

DO-3

DO-04

DO-2

AC - COOLING STAGE-1 ENABLE - DO AC - SUPPLY FAN START/STOP - DO

DO-1 BUSS

24VAC

2

3

W1 Y2 Y1 LO

G R

DO-02 AC - RETURN AIR TEMPERATURE - AI

UI-05

81

24VAC+

1

DO-5

DI-03

UI-04

AC - BYPASS DAMPER CONTROL - AO HIGH

AC Space Static Tip

AI-02

DO-03 4

GND AO-1

24VAC-

Digital Off

AC - SUPPLY FAN STATUS - DI

DI-01

1/4" Pneumatic Tubing

Digital Output Verification Checklist: Date Verified

IN-1 Gnd

AO-01

By Tech Initials

1

AC - DUCT STATIC PRESSURE - AI

Check’d

Point Addr. & Input #

Universal Input Verification Checklist:

Note: Economizer w/Power Exhaust

Terminal Setting

100

75

50

25

0

Date Verified

By Tech Initials

Rnet

Point Addr. & Type

N.O.

Analog Out %

81

Gnd Rnet+ Rnet+12V

Analog Output Verification Checklist:

DO-01

4

1

AC - DUCT STATIC PRESSURE - AI

24VAC+

+ S

24VAC-

-

HI

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

RA

SA

EMS DIAGRAMS ORIGINAL SCALE 0

VVT AC UNIT MODULE DETAIL NOT TO SCALE

4

VVT AC UNIT NOT TO SCALE

3

1"

JOB NO.: SHEET NUMBER:

M-520

2"


Exhaust Fans

5A Ckt Bkr

LABEL DESCRIPTION:

To ZN-Card controller (HI & LO)

TB-PWR

TCP-EF

H

Panel Rm Location:

G

POWER CIRCUIT FROM:

N

PNL #:

TX-1

TX PROVIDED BY SUNBELT CONTROLS

X1+

X1-

VOLT: TB-1 24VAC Power to below

Zone Box Typical of: AC-7 - (8) Zones AC-8 - (8) Zones AC-10 - (5) Zones AC-11 - (11) Zones

H N G

ON

50VA R

OFF

20

CORPORATION Arc156

Red Stripe =

Gnd 24Vac

FILTER

PROGRAM/ FB NAME(S)

.equipment

Lstat

OR

Bias

Rx

Net +

Tx

CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

Rnet

Rnet LogiStat

Format

Ground

Net -

CR 2032

Made in USA

IN-1 Thermistor/dry contact 0-5Vdc

IN-2

Sense +12V

3

2

O N

LStat =

2 3

Communications Selection

or IN-3 =

Rnet

MSTP ARC156

2 3

+12V

9600

19.2k

38.4k

76.8k

IN-1 Inputs: 5V Max

ARC156

Batt

Gnd

Gnd

MSTP

CR2032

IN-3 AO-1

10's

MSTP Baud

BUSS

On

®

2 3

19.2k

38.4k

76.8k

CMnet

4 3 2

Local

24V ac

Ground

Shield

Net +

BT485

Access +12V

Gnd

Rnet -

CCW

Rnet +

IN-4

Power

Rnet

Motor CW

LED

IN-3

Rnet+ Gnd

Conductors Only

Port Gnd

+12V Rnet-

Power

1

26Vdc, 0.1A, 3W Use Copper

LStat/ZASF

Inputs

Sense

Run

O N

Tx

Net -

0-5V, therm, dry

IN-1

Gnd

DO-3

AO-1

DO-2

Rx

Therm, dry

Gnd

Analog

Inputs 1 & 2

IN-2

5mA Max

Error

14VA, 0.58A

Inputs 3 & 4

Gnd

Power for D.O.s

Class 2 24Vac, 50-60 Hz

LogiStat/IN3 & 4 ZASF

1A Max

DO-1

BUS

1

BACnet AO: 0-10 Vdc

3 2

Outputs 24V Max,

9 0 1

4

9600

Point Addr. & Type

Off

On

Date Verified

By Tech Initials

Offset (if appl)

Actual Fld. Measured Value

Input Value Reading

Date Verified

By Tech Initials

Power for D.O.'s

BACnet

5 6

Check’d

2 3

4 6

4

Point Addr. & Input #

7

51

DO-1 BUSS

AI-02

8

6

5

9

Output

EF-x - EXHAUST FAN START/STOP - DO

3

DO-1

®

DO-02

7

2

0

DO-2

CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

DO-2

AI-01

1

8

5 6

IN-5

1's

DO-3

IN-4

5

9

ZN341v+

DO-4

Gnd

LED

Digital

CONTROLLER

DO-5

Class 2 24 Vac, 50-60 Hz 20VA, 0.83A 24Vdc, 0.2A, 5W Use Copper Conductors Only

4

4

Digital Output Verification Checklist:

ZN551

3

0

-

+ CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

2

1

Gnd

9 0 1

IN-2

Input Output Verification Checklist:

CAUTION: The modules are Class 2 devices (less than 30 VAC). Take appropriate isolation measures when mounting a module in a control panel where Class 1 devices or wiring are present.

MSTP Baud

Gnd

IN-2 Gnd

ARCHITECT STAMP

Format Short pins

4

3

1

IN-1 Gnd

LO

0-5Vdc Therm/dry

4

Gnd

Rnet

IN-1

On

Rnet-

Gnd

Rnet -

Green Stripe =

0-5Vdc Therm/dry

Thermistor/dry contact 0-5Vdc

Rnet+

Rnet +

CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

U.S. Patent No. 6,715,690 B2

2

5 6

Tens

4

5 6 4

0 1

5 6

2 3

2 3 9

9 0 1

Ones

5 6 4

0 1 7 8

IN-2

Pwr + Err

9

7 8

4

-

7 8 9 0 1

Gnd Rnet+ Rnet+12V

24 Vac

Batt

Run

Shield

7 8

Jumper: Gain1

1

Term

EF-x - EXHAUST FAN STATUS - DI

To VVT Box Flow Sensing Device (LO & HI)

Flow Low

ZN220

BT485

CONSULTANT

DO-01 6

7 8

4

3

2

1

1

2

3

1

2 DISCONNECT SWITCH

1 2 3 4

1

HI

High

CMnet

Net + Net Shield

ADDRESS

Install Air Filter (shipped loose)

7 8

CMnet from PREVIOUS & to NEXT ALC CONTROL MODULE (SEE NETWORK RISER DIAGRAM)

CONTROL MODULE

VA

design@csdarchitects.com T:310.821.9200 F:310.821.9201

NEMA 1 12HX12W SCREW COVER

TB-PWR

ALC Controller Checklist:

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

SA

120VAC

10A

AUTOMATEDLOGIC

LO

CKT #:

50va

REC

HI

7 8

CONTROL PANEL #

120 VAC

24 VAC

120 VAC (Provided & Wired by others)

CREATIVE DESIGN

Transformer (50 VA) mounted at each VVT Box to power ZN341v+.

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

CMnet daisy chained from previous / to next control module. (See riser detail)

Room Temp Sensor RSPLUS

NOT FOR CONSTRUCTION USE

WARMER

4 3 2 1

EF-x – EXHAUST FAN WIRING DETAIL 460 VAC/3PH/60HZ

Status EF-x - EXHAUST FAN STATUS - DI

1

COOLER

MANUAL ON OCCUPIED

MCC Starter

AUTHORITY APPROVAL

AUTOMATED LOGIC

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

CS H O A

EF-x - EXHAUST FAN START/STOP - DO

51

R-AC

04-112249

R^

EXHAUST FAN MODULE DETAIL NOT TO SCALE

ZONE BOX DETAIL

2

NOT TO SCALE

Administration Building and Library Network Architecture Layout AC-1 N1 12X12 LOCATE INSIDE UNIT

AC-2 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER ZN551

FLS

AC DATE

SS

SCHOOL DISTRICT: AC-3 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER ZN551

1

AC-4 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER

AC-5 N1 12X12 LOCATE INSIDE UNIT

AC-6 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER

ZN551

ZN551

UNIT POWER ZN551

AC-7 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER

AC-8 N1 12X12 LOCATE INSIDE UNIT

AC-9 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER

ZN551

ZN551

UNIT POWER ZN551

AC-10 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER

UNIT POWER

ZN551

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

AC-10 N1 12X12 LOCATE INSIDE UNIT

UNIT POWER ZN551

ZN551

16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

EXHAUST FANS N1 12X12

ZONE BOX Z10-1

120VAC ZN551

ZONE BOX Z10-2

120VAC

E

120VAC

E

ZN341V+

ZONE BOX Z10-3

120VAC

E

ZN341V+

ZONE BOX Z10-4

ZONE BOX Z10-5

120VAC

E

ZN341V+

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

E

ZN341V+

KEY PLAN

120VAC

E

ZN341V+

22/2 SHLD (Cmnet, Orange)

ZONE BOX Z11-1

ZONE BOX Z11-2

120VAC

120VAC

E

ZN341V+

ZONE BOX Z11-3

ZONE BOX Z7-1

120VAC

E

ZN341V+

ZONE BOX Z7-2

120VAC ZN341V+

ZONE BOX Z7-3

ZN341V+

ZONE BOX Z7-4

ZN341V+

ZONE BOX Z7-5

ZN341V+

ZONE BOX Z7-6

ZN341V+

ZONE BOX Z7-7

ZN341V+

ZONE BOX Z11-10

120VAC

E

ZN341V+

ZN341V+

ZONE BOX Z11-11

120VAC

E

ZN341V+

120VAC

E

ZN341V+

E

ZONE BOX Z7-8

120VAC

E

ZONE BOX Z11-9

120VAC

E

ZN341V+

120VAC

E

ZONE BOX Z11-8

120VAC

E

ZN341V+

120VAC

E

ZONE BOX Z11-7

120VAC

E

ZN341V+

120VAC

E

ZONE BOX Z11-6

120VAC

E

ZN341V+

120VAC

E

ZONE BOX Z11-5

120VAC

E

ZN341V+

120VAC

E

ZONE BOX Z11-4

120VAC

E

ZN341V+

E

ZN341V+

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

22/2 SHLD (Cmnet, Orange)

HIGH PERFORMANCE BACnet ROUTER w/GATEWAY 120vac HUB

E

ZONE BOX Z8-1

LGR25

DEV:01

ZONE BOX Z8-2

120VAC ZN341V+

ZONE BOX Z8-3

120VAC

E

ZN341V+

ZONE BOX Z8-4

120VAC

E

ZN341V+

ZONE BOX Z8-5

120VAC

E

ZN341V+

ZONE BOX Z8-6

120VAC

E

ZN341V+

ZONE BOX Z8-7

120VAC

E

ZN341V+

120VAC

E

ZN341V+

COPYRIGHT: CSDA ARCHITECTS 2011

ZONE BOX Z8-8

SHEET TITLE

120VAC

E

ZN341V+

E

EMS DIAGRAMS

BT D

TCP-01, BLDG PANEL

ORIGINAL SCALE 0

ETHERNET- CUSTOMERS WIDE AREA NETWORK CAT5e (BY OTHERS)

NETWORK RISER DIAGRAM NOT TO SCALE

3

1"

JOB NO.: SHEET NUMBER:

M-521

2"


PLUMBING SHEET INDEX

WATER HEATER SCHEDULE WATER HEATER ID WH-1

DESCRIPTION

SERVICE AREA

MANUFACTURER & MODEL

GAS INPUT

STORAGE CAPACITY

RECOVERY RATE IN GPH

WATER HEATER

NEW ADMINISTRATION BUILDING

A.O. SMITH BTH-150

150,000

100 GALLONS

173 GPH @ 100° RISE

REMARKS

SHEET NUMBER

MUST BE CEC APPROVED

EQUIPMENT SCHEDULE

PLUMBING SYMBOLS LEGEND

SHEET TITLE

P-001

LEGENDS, NOTES, AND SCHEDULES

P-100

PLUMBING SITE PLAN

P-110

PLUMBING FIRST FLOOR PLAN

P-111

PLUMBING SECOND FLOOR PLAN

SYMBOL

ABBREV. W

WASTE ABOVE FLOOR

W

WASTE BELOW FLOOR

SD

SD

STORM DRAIN ABOVE FLOOR

OD

OD

OVERFLOW DRAIN ABOVE GRADE

SD

SD

STORM DRAIN BELOW FLOOR

V EQUIP ID

ET-1

CP-1

DESCRIPTION

EXPANSION TANK CIRCULATING PUMP

MANUFACTURER & MODEL NUMBER

SERVICE

BELL & GOSSETT PT-12

WH-1

BELL & GOSSETT PL-30

WH-1

REMARKS 4 GALLON

P-130

PLUMBING ROOF PLAN

P-410

ENLARGED PLUMBING PLAN

P-420

3D RISER DIAGRAMS

P-500

DETAILS

(E)

COLD WATER

HW

HOT WATER

PLUMBING FIXTURE SCHEDULE FIXTURE ID

CONNECTION SIZE FIXTURE

TRAP

WASTE

VENT

COLD

COMMENTS

HOT

WC-1

WATER CLOSET

INTEGRAL

4"

2"

1"

-

SEE SPECIFICATION

WC-2

WATER CLOSET (ACCESSIBLE)

INTEGRAL

4"

2"

1"

-

SEE SPECIFICATION

INTEGRAL

2"

1-1/2"

-

-

SEE SPECIFICATION

UR-1

UR-2

L-1

URINAL URINAL (WATERLESS, ACCESSIBLE) LAVATORY

G

ICW

ICW

INDUSTRIAL COLD WATER

CD

CD

CONDENSATE DRAIN

D

D

SOV

INTEGRAL

1-1/4"

2"

2"

1-1/2"

1-1/2"

-

-

1/2"

1/2"

2"

1-1/2"

1/2"

1/2"

SEE SPECIFICATION

SS-1

SERVICE SINK

3"

3"

2"

3/4"

3/4"

SEE SPECIFICATION

CHECK VALVE

CO

CLEANOUT

FCO

FLOOR CLEANOUT

PIPE-UP UNLESS OTHER WISE NOTED

POC

POINT OF CONNECTION

ABV

ABOVE

BEL

BELOW

BV

BALANCING VALVE

CLG

FIXTURE ID

FIXTURE

QUANTITY

FIXTURE UNIT (FU)

WC

WATER CLOSET (115 FU FOR 5 WC) + (10 FU X 19 WC)

24

115 + 190

L

LAVATORY

17

SS

SERVICE SINK

DF

DRINKING FOUNTAIN HI-LO

2"

2"

1-1/2"

-

FLOOR DRAIN

-

DF-1

DRINKING FOUNTAIN HI-LO

2"

1-1/2"

1-1/2"

3/4"

-

SEE SPECIFICATION

TP-1

TRAP PRIMER

-

-

-

1/2"

-

SEE SPECIFICATION

HB-1

HOSE BIBB (WALL)

-

-

-

3/4"

-

SEE SPECIFICATION

RHB-1

RECESSED HOSE BIBB NON-FREEZE

-

-

-

3/4"

-

SEE SPECIFICATION

RD-1

ROOF DRAIN

SEE SPECIFICATION, SEE ROOF PLAN FOR SIZES

OD-1

OVERFLOW DRAIN

SEE SPECIFICATION, SEE ROOF PLAN FOR SIZES

SEE SPECIFICATION, SEE PLAN FOR SIZES

FIXTURE ID

305

WC

1

17

2

3

2

1

FIXTURE

GAS PIPING CALCULATION

QUANTITY

FIXTURE UNIT

TOTAL

QUANTITY

CFH (EACH)

CFH (TOTAL)

AC-1 & AC-2

2

120

240

AC-3 THRU AC-5

3

150

450

EQUIPMENT

24

6

144

L

LAVATORY

17

1

17

6

SS

SERVICE SINK

2

3

6

AC-6

1

224

224

2

DF

DRINKING FOUNTAIN HI-LO

2

1

2

AC-7 THRU AC-10

4

400

1600

HOSE BIBB (WALL)

4

3

12

RHB

RECESSED HOSE BIBB

6

3

18

UR

URINAL

TOTAL

TOTAL

360

GPM

110

EXISTING

ELEV

ELEVATION

FT

FOOT, FEET

FU

FIXTURE UNITS

FV

FLUSH VALVE

HDCP

HANDICAP

MTD

MOUNTED

REQ

REQUIRED

SGL

SINGLE

ST STL

5

5

25

AC-11

1

400

400

WH-1

1

150

150

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

DOWN

NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249 FLS

AC DATE

SS

STAINLESS STEEL

TYP

TYPICAL

VB

VACUUM BREAKER

W/

WITH

MEP COMPONENT ANCHORAGE NOTE:

WATER CLOSET

HB

CONSULTANT

CEILING

SEE SPECIFICATION, SEE PLAN FOR SIZES, PROVIDE WITH 1/2" MAX GRATE OPENING IN ALL DIRECTIONS

FIXTURE UNIT (WASTE) TOTAL

(E), EXIST

PROVIDE WITH 1/2" MAX GRATE OPENING IN ALL DIRECTIONS

FD-1

FIXTURE UNIT (WATER)

EXISTING PIPING WITH SERVICE INDICATED SHUT OFF VALVE

CV

DN

AREA DRAIN GRATE

RISER DRAIN

SEE SPECIFICATION

1-1/4"

AD-2

ARCHITECT STAMP

PIPE DROP UNLESS OTHER WISE NOTED

SEE SPECIFICATION

LAVATORY (ACCESSIBLE)

AREA DRAIN

GAS

DROP OR RISE

L-2

AD-1

design@csdarchitects.com T:310.821.9200 F:310.821.9201

HOT WATER RETURN

G

(E)

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

VENT

CW

HWR 1/6 HP-120V, 1Ø, 60HZ ALL BRONZE

DESCRIPTION

ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 1615A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS. THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY STTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.

SCHOOL DISTRICT:

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL. FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER

194

TOTAL

MAXIMUM DEVELOPMENT LENGTH

SIZE OF GAS METER

3064

350 FT

4"

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22. THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PREAPPROVALS WITH AN OPA #, AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D. COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

LEGENDS, NOTES, AND SCHEDULES ORIGINAL SCALE 0

1"

JOB NO.: SHEET NUMBER:

P-001

2"


KEY NOTES

2 GPL

1

4" SEWER LINE EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

2

3" CW LINE EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

3

6" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

4

PROPOSED NEW GAS METER ASSEMBLY, COORDINATE & PAY ALL REQUIRED INSPECTION AND INSTALLATION FEES.

5

MEDIUM PRESSURE GAS PIPING BELOW GRADE, VERIFY PIPE SIZE WITH GAS COMPANY

6

MEDIUM PRESSURE GAS PIPING CONNECT TO EXISTING PIPING SERVING ALL OTHER BUILDINGS, VERIFY EXACT LOCATION AND SIZE ON SITE.

7

4" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

8

3" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

9

2" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

ARCHITECT STAMP

LIMIT OF WORK

CONSULTANT

6

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

LIMIT OF WORK

CONSULTANT STAMP

3 NOT FOR CONSTRUCTION USE

1

9 9

3

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

1

04-112249 FLS

AC DATE

SS

3

3 9

SCHOOL DISTRICT:

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

LIM IT OF WO RK

N D

(N) ADMINSTRATION BUILDING

16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

9

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

9 8

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

1

2

1

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

OF LIMIT

PLUMBING SITE PLAN

K WOR

ORIGINAL SCALE 0

PLUMBING SITE PLAN 1" = 20'-0"

1"

JOB NO.: SHEET NUMBER:

1

P-100

2"


5.5

6

7

KEY NOTES

9

8

ELECTRICAL 152

9

J

1

2-1/2" CW TERMINATE 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

2

2-1/2" SOV IN YARD BOX

3

4" WASTE LINE, TERMINATE 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

4

2' MPG, FOR CONTINUATION SEE SITE PLAN, P-100

5

GAS REGULATOR

6

4" EARTHQUAKE SEISMIC SOV

7

4" WASTE UP TO SECOND FLOOR

8

1-1/2" CW & 3/4" HW UP TO SECOND FLOOR

9

3/4" CW DOWN IN WALL TO SERVE HOSE BIB

10

4" GAS OFFSET ABOVE CEILING

11

4" GAS UP TO SECOND FLOOR

12

2-1/2" CW IN YARD BOX

13

6" SD DOWN UP TO 2ND FLOOR, AND DOWN OFFSET BELOW GRADE

14

6" SD BELOW GRADE, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

15

6" OD DOWN UP TO 2ND FLOOR, AND DOWN OFFSET & SPILL ON GRADE AT 6" ABOVE FINISHED FLOOR

16

3" SD DOWN FROM 2ND FLOOR, OFFSET BELOW GRADE

17

3" SD BELOW GRADE, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

18

4" SD DOWN FROM 2ND FLOOR, OFFSET BELOW GRADE

19

4" SD BELOW GRADE, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

20

4" OD DOWN FROM 2ND FLOOR, OFFSET & SPILL ON GRADE AT 6" ABOVE FINISHED FLOOR

21

3/4" COND. DRAIN DN IN WALL & CONNECT TO TAIL PIECE ADAPTER

22

3/4" SECONDARY COND. DRAIN TERMINATE 1" BELOW CEILING WITH CHROM PLATE ESCHACHEON

23

2" SD BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

RHB-1

COUNSELOR 116

COUNSELOR CONFERENCE ROOM 117

COUNSELOR 115

COUNSELOR 113

COUNSELOR 114

COUNSELOR ASSISTANT 111A CORRIDOR 131

COUNSELOR 111

COUNSELOR 112

H

STORAGE 120 COUNSELOR 118

BOOK KEEPER 121 15 SD

14

UP

COUNSELOR 119

TEACHER WORKROOM / LOUNGE 110

TESTING MATERIALS 123

13

OD

STAFF TOILET 21 108 10

ELECTRICAL ROOM 124

BOOKSTORE 122

6

5

9

CD

FC 3 M-511 3

VENTED PIPE SLEEVE 4

RHB-1

G

G

ELECTRICAL 107

11 AD-2

3

FC 2

23

STAFF TOILET 109 3 M-511

23

1" CD UP TO 2ND FLOOR

ASSISTANT 126A

13

14

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

AUTHORITY APPROVAL

SICK ROOM 104

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

G

15

CREATIVE DESIGN

TOILET 106

F

CORRIDOR 130

CONSULTANT

NOT FOR CONSTRUCTION USE

M

COT 105

ARCHITECT STAMP

CONSULTANT STAMP

2 P-410

AD-2

STORAGE 125 4" V UP TO 2ND FLOOR ATHLETIC DIRECTOR 126

INVERT ELEVATION 4'-0" BELOW GRADE

design@csdarchitects.com T:310.821.9200 F:310.821.9201

04-112249

ASB / ACTIVITIES DIRECTOR 127

3

STORAGE 128 7

WCO

INVERT ELEVATION 4'-0" BELOW GRADE

GENERAL NOTES 1. 2.

E ASB WORK & CONFERENCE ROOM 129

1

2

3

REGISTRAR 102

REGISTRAR WAITING 102A

5

4

3. 4. 5.

L G

9

RECORDS STORAGE 101

SD

C

OD 13

N D

13 9 RHB-1

AP OFFICE 154

WAITING 148

STORAGE 153

PRINCIPAL'S CONFERENCE ROOM 161

STORAGE 145

PRINCIPAL'S OFFICE 160

OFFICE ASSISTANT 154A

B

OFFICE ASSISTANT 146A

STORAGE 144

SECURITY OFFICE 140

RHB-1

MEN'S RESTROOM 133

ELEVATOR -

GAS

CORRIDOR 132

23 16

CORRIDOR 162

UP AD-2

TA WORKSPACE 151B

22

TOILET 21 159

PRINCIPAL'S ASSISTANT 157

STORAGE 143

3" GAS UP TO 2ND FLOOR

SRO OFFICE 138

COPYRIGHT: CSDA ARCHITECTS 2011 STORAGE 142 STAFF TOILET 137

3 M-511

AP OFFICE 151

CD

2%

AP CONFERENCE ROOM 156

A

OFFICE ASSISTANT 141A

STORAGE 152

FC 1

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

23

17

OFFICE ASSISTANT 151A

STORAGE 158

10

AD-2

JANITOR 139

TA WORKSPACE 154B

3 P-410

9.5

9

ELEVATOR MACHINE ROOM 135

RHB-1

2" V UP TO 2ND FLOOR

LOBBY 100

15

AD-2

AP OFFICE 146

WAITING 147

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

KEY PLAN

14

23

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

14

15

SCHOOL DISTRICT:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

K

9.3

UP

PIPE LOCATIONS SHOWN ARE ONLY SCHEMATIC. MASONRY WALL PENETRATIONS OR FOUNDATION PENETRATIONS ARE NOT ALLOWED. PIPES MAY BE RUN BELOW OR ABOVE WALL FOOTINGS. PIPES MAY BE RUN ABOVE COLUMN FOOTINGS, BUT ARE NOT ALLOWED BELOW COLUMNS. SEE DETAIL 4 ON SHEET S-6 FOR DETAIL BELOW WALL FOOTINGS.

SCHOOL ADDRESS:

CORRIDOR 130

D

WAITING 150

WAITING 149

WOMEN'S RESTROOM 134

SHEET TITLE

1 P-410

2

AP OFFICE 141

SERVER / ELECTRICAL ROOM 155

STAFF TOILET 136

FIRST FLOOR PLUMBING PLAN

11 12

ORIGINAL SCALE 0

RHB-1 3 INVERT ELEVATION 4'-0" BELOW GRADE

SS

4" ATTENDANCE 103

8

RHB-1

FLS

AC DATE

CO

F.S. CLOSET 136A

3

INVERT ELEVATION 4'-0" BELOW GRADE

PLUMBING FIRST FLOOR PLAN

1

12

1/8" = 1'-0"

1

1"

JOB NO.: SHEET NUMBER:

P-110

2"


5.5

6

7

KEY NOTES

9

8

J

2%

1

3/4" CD UP THRU ROOF TO AC UNIT

2

2" GAS UP THRU ROOF TO AC UNIT

3

1-1/4" GAS UP THRU ROOF TO AC UNIT

4

4" GAS DOWN TO FIRST FLOOR

5

1-1/4" CONDENSATE DRAIN DOWN IN WALL AND SPILL INTO SERVICE SINK

6

1-1/2" GAS DOWN TO WATER HEATER, PROVIDE SOV

7

3" PVC SUPPLY AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH

8

3" PVC VENT AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH

9

6" SD & OD DOWNSPOUTS FROM ROOF

10

6" SD & OD DOWN TO 1ST FLOOR

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

9

2%

H 2%

ARCHITECT STAMP DN

1

2

2%

CO 3/4"

CONSULTANT 2%

10

G

CD

AV STORAGE 203 4

CREATIVE DESIGN

TECH STORAGE 202 4"V DOWN TO 1ST FLR

OFFICE 204 1"

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

M

1

CONSULTANT STAMP

2

1" CD DN TO 1ST FLR

4" V UP TO ROOF 10

NOT FOR CONSTRUCTION USE OFFICE 205

2

2%

9

F

AUTHORITY APPROVAL

LIBRARY 201

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

1 2%

04-112249

CONFERENCE ROOM 206

STAFF TOILET 207 4 P-410 2%

FLS

AC DATE

L

SS

CO

K

2

SCHOOL DISTRICT: 1

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

E

1

2

3

2%

WORK ROOM 208

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

3

SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

4 CO 1

9.3

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

D DN 10 10

C TEXTBOOK STORAGE 213

OD

JANITOR 209

SD

8

9.5

SS-1

WH-1

5

SD

CLOSET 221 OD

7

6 2 1 1/4" 1

3

2" V UP TO ROOF & DN TO 1ST FLR 6 P500

B

6 P500

3/4" CO

2%

CD

1

2% G

6 P500

2" CLOSET 218

3 3

2 1/2"

6 P500

1 3

2" V UTR & DN TO 1ST FLR

1"

G 1 1/2"

6 P500

DN

1 1/4"

3" SD DOWN TO FIRST FLOOR

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

CD CO

3"

3" GAS DOWN TO 1ST FLOOR AD-1

1

1

ELECTRICAL 219

COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

3 3" V UTR & DN TO 1ST FLR

CLASSROOM 215

10 CORRIDOR 210

9

9 1 CORRIDOR 217

1" 2%

CLASSROOM 216

WOMEN'S RESTROOM 212

CLASSROOM 214

STORAGE 220

SECOND FLOOR PLUMBING PLAN

AD-1

MEN'S RESTROOM 211

11 5 P-410

A

ORIGINAL SCALE 0

12

PLUMBING SECOND FLOORPLAN 1/8" = 1'-0"

1

1"

JOB NO.: SHEET NUMBER:

P-111

2"


5.5 5.5

6

M

7

6

7

KEY NOTES

9

8

8

J

E 8

L

7

K

2

2" GAS DOWN THRU ROOF

3

1-1/4" GAS DOWN THRU ROOF

4

4" SD UP TO UPPER ROOF AND DOWN SPILL ONTO LOWER ROOF

5

3" SUPPLY AIR DOWN THRU ROOF

6

3" VENT AIR DOWN THRU ROOF

7

4" SD DOWNSPOUT FROM UPPER ROOF

8

4" SD DOWN TO LOWER ROOF

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

H

9.3

ARCHITECT STAMP

9.5

7

3/4" CD DOWN THRU ROOF

6" OD 6" SD 3600 S.F.

D

1

10 PIPE SUPPORT (TYP.) P-500

8

1

2

C 1.3

CONSULTANT

G 10

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

2

1

1.2

B

CONSULTANT STAMP

ROOF ACCESS

LOWER ROOF

NOT FOR CONSTRUCTION USE

4" V DOWN THRU ROOF

F

6" SD

2

1

6" OD 5293 S.F.

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

M

11

04-112249 ROOF JACK FLS

AC DATE

2" V DOWN THRU ROOF

SS

2

5

12

1

PLUMBING UPPER ROOF PLAN 1/8" = 1'-0"

SCHOOL DISTRICT:

E

2 4

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

L

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

3

SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

1

9.3

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

D

K 4

KEY PLAN

OPEN

ROOF JACK

C

9.5 2" V DTR. ROOF JACK 6

10 PIPE SUPPORT (TYP.) P-500

5 4" V DTR.

2 1

OPEN

3

2" V DTR.

10

6" OD 6" SD 3653 S.F.

LOWER ROOF

B 6" OD 6" SD 3570 S.F.

2" V DTR.

1

1

LOWER ROOF

3

3 3

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

ROOF ACCESS

1

3 4" V DTR

1

1

COPYRIGHT: CSDA ARCHITECTS 2011

3" V DTR.

SHEET TITLE

PLUMBING ROOF PLAN

11

A

ORIGINAL SCALE 0

12 1

2

3

4

5

PLUMBING ROOF PLAN 1/8" = 1'-0"

1

1"

JOB NO.: SHEET NUMBER:

P-130

2"


KEY NOTES 4 1

7 RHB-1 3" WASTE UP TO 2ND FLOOR

HB-1 10

FCO

FCO STAFF TOILET 207

WC-2

L-2

4

TP WC-2

2"V

L-2

11

4"

4" W

4" V DN IN WALL

24

12

11

WC-1 10 2" V UTR

23

4" 2"

2%

WC-2

FCO 2"V UP TO 2ND FLR

3

1/4" = 1'-0"

MEN'S RESTROOM 133

3

B

4

4" 4" 8

L C

2%

2" 9

WOMEN'S RESTROOM 134 4"

WC-2

FD-1

FD-1

FD-1

32

TP

STAFF TOILET 137

2" VTR

FCO

WC-2

L-2

WC-1

WC-1

2

15

8 P-500

WH-1

2%

WC-1

16

TP

TP

3" V UP TO 2ND FLR

2"

26

L-1

11 2%

WCO

1 1/2"

29

4

2-1/2" CW UP TO 2ND FLOOR

5

2" HW UP TO 2ND FLOOR

6

3/4" CW DN IN WALL TO DF

7

3/4" CW AND 3/4" HW DN IN WALL TO SERVE SERVICE SINK

8

3/4" CW AND 3/4" HW DN IN WALL TO SERVE LAV AND HB

9

1-1/2" CW, 3/4" HW DOWN IN WALL, PROVIDE SOV AND ACCESS PANEL, RUN 1-1/2" CW TO WC, 3/4" CW & HW TO LAV AND 1/2" CW TO TRAP PRIMER

10

1-1/2" CW DN IN WALL TO WC, PROVIDE SOV AND ACCESS PANEL, RUN 1-1/2" CW TO WC & 1/2" CW TO TRAP PRIMER

11

4" VENT UP TO 2ND FLOOR

12

3/4" CW, 3/4" HW DOWN IN WALL TO SERVE LAV

13

1-1/4" CONDENSATE DRAIN DOWN IN WALL AND CONNECT TO TAILPIECE ADAPTER

14

1" CONDENSATE DRAIN DOWN IN WALL CONNECT TO TAILPIECE ADAPTER

15

3/4" HW DOWN IN WALL TO SERVE LAV

16

4" WASTE DOWN FROM 2ND FLOOR

17

4" GAS UP IN WALL, OFFSET ABOVE CEILING

18

EARTHQUAKE SOV

19

GAS PRESSURE REGULATING VALVE

20

4" GAS BELOW GRADE, FOR CONTINUATION SEE SITE PLAN

21

4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING

22

1" CONDENSATE DRAIN DOWN IN WALL CONNECT TO TAILPIECE ADAPTER

23

1-1/4" CONDENSATE DRAIN DOWN IN WALL CONNECT TO TAILPIECE ADAPTER

24

1-1/2" CW & 3/4" HW DOWN TO FIRST FLOOR

25

4" WASTE DOWN TO FIRST FLOOR

26

2" HW DOWN TO FIRST FLOOR

27

2-1/2" CW UP FROM FIRST FLOOR

28

4" VENT DN TO FIRST FLOOR AND UP THRU ROOF

29

3" WASTE DOWN TO FIRST FLOOR

30

1-1/2" CW & HW DN TO WH

31

3" PVC SUPPLY AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH

32

3" PVC VENT AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

ARCHITECT STAMP

CONSULTANT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

WC-1

WC-2

NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249 FLS

AC DATE

SS

L-2

27

31

STAFF TOILET 136

2 1/2"

11

2 1/2"

3

15 10

TP

SCHOOL DISTRICT:

2%

2-1/2" SOV IN YARD BOX 2%

WC-2

A

12

4" V DN IN WALL

FD-1

28

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

A 4"

4"

DF-1 CO

2"W DN TO 1ST FLR

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

21

SCHOOL ADDRESS:

1

B

FIRST FLOOR RESTROOM 133, 134 2 1/2"

2-1/2" CW DOWN IN WALL TO 2-1/2" CW HEADER, RUN 1-1/2" CW TO EACH WC & 1/2" TO TRAP PRIMER, PROVIDE SOV AND ACCESS PANEL

HB-1

L-2

30

3

DF-1

1" HW UP TO 2ND FLR

SS-1

2-1/2" CW UP IN WALL, OFFSET ABOVE CEILING

6 2%

7 SECOND FLOOR RESTROOM 207

2

TP

7 SS-1

1/4" = 1'-0"

2"W UP TO 2ND FLR

FD-1 12

2-1/2" CW BELOW GRADE, TERMINATE 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING

L-1

25

FCO

FIRST FLOOR RESTROOM 159

8

L-2

UR-2

FD-1

TOILET 159

5

UR-1

TP FD-1

4"

1

4

8

3/4" HWR

1/4" = 1'-0"

1

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

1" HW DN. TO 1ST FLR

G

15

22

10

10

15 TP

TP

L-2

20

G WC-2

17

21

2%

FCO 8

FD-1

L-1

L

FD-1

TP

L-1

TP

3

WC-2

STAFF TOILET 108

L-2

4"

FD-1 STAFF TOILET 4" 109

L-1

FCO 4" V UTR & DN TO 1ST FLR

CD

FD-1

L-1

3

1"CD

WOMEN'S RESTROOM 212

HB-1

WC-1 UR2

2%

HB-1

G

19

RHB-1

8

L-2

18

L-2 MEN'S RESTROOM 211

WC-1 WC-1

4" W DOWN TO FIRST FLOOR

UR-1

WC-1

UR1

WC-1

FD-1

TP

FCO

L-2

FD-1

15

WC-2

TP

TP

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

12

COPYRIGHT: CSDA ARCHITECTS 2011

FD-1

SHEET TITLE

STAFF TOILET 106 WC-2

WC-2

A

WCO

F

ENLARGED PLUMBING PLAN ORIGINAL SCALE 0

8

4

SECOND FLOOR RESTROOM 211, 212 1/4" = 1'-0"

5

JOB NO.: SHEET NUMBER:

9

FIRST FLOOR RESTROOM 106, 108, 109 1/4" = 1'-0"

1"

2

P-410

2"


2" VTR 4" VTR

2" VTR

AC-10 2" (400 CFH)

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

4" VTR AC-8

3" (3)

2" (400 CFH)

design@csdarchitects.com T:310.821.9200 F:310.821.9201

SS 4" V UTR

AC-7

3" (1424 CFH)

2" (400 CFH)

DF SINK

AC-9 2" (400 CFH)

3" (1024 CFH) 4" (1824 CFH)

3" (4)

2" (1)

AC-6 2" V UTR

2-1/2" (624 CFH) LAV

1-1/2" (224 CFH) 4" (3064 CFH)

LAV

2" VTR

EARTHQUAKE SOV

3" (1240 CFH)

LAV FD

LAV

GAS PRESSURE REGULATOR

LAV

WC

LAV

3" (6)

2" (3) 4" (63)

UR 4" GAS BELOW GRADE, FOR CONTINUATION SEE SITE PLAN

WC

FD

UR

2" (3)

4"V UR

FCO

FD

WC WC

FD

4" (29) WC

2" (1) 4" (24)

WC

3" (10)

SS

AC-11

1-1/4" (120 CFH)

LAV

LAV

2" (400 CFH)

AC-2

1-1/4" (150 CFH)

4" (31)

4" (29)

2" 1-1/2" AC-5

3" (1090 CFH)

AC-4

LAV

WC

AC-3

2-1/2" (690 CFH) 1-1/4" (150 CFH) 1-1/2" (300 CFH) 1-1/4" (150 CFH)

WH

LAV

3" (1240 CFH)

FCO

4" (6)

WC

3D RISER - GAS

3D RISER - WASTE & VENT - TOILET 159

5

4" (145)

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

WCO

4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING

WC

FD

4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING

4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING

SINK

4" (24) 4" (6)

4" (7)

1-1/4" (150 CFH)

CONSULTANT

4" (7)

4" (6)

4" (9) 2" (1)

2"

2" (1) 4" (6)

WC

WC

FD

2" (540 CFH)

2" (1) FD

WC

WC

LAV

FD

WC

FCO

WC

WC

2"V

LAV

4" (6)

FD

FD

4" (6)

1-1/2"V

FCO

3" (3)

AC-1

FD

1-1/2"V

4" (7)

2"

WC

2"

4" (6)

FD

WC

LAV

2"V

4"

WC

FD

FCO

WCO FCO

ARCHITECT STAMP

4" (21)

WC

LAV

WC

DF

2"V LAV

FCO

FD

WC

3"V

LAV

UR

UR FCO

LAV

4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING

CO

CONSULTANT STAMP

4" (17)

3D RISER - WASTE & VENT - WEST SIDE

4

3D RISER - WASTE & VENT - NORTH SIDE

3

2

NOT FOR CONSTRUCTION USE

SINK

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249

3/4"CW (3)

RHB

.

1"HW (7)

LAV

WC

LAV

FD

WC FIXTURE UNIT COUNT

LAV

WC

PIPE

CW - FV (FU)

HW (FU)

WC

FIXTURE UNIT

1/2"

1

0

1

1ST

40

SCHOOL ADDRESS:

.. .

FD WC

6

2ND

2"CW (41) 3/4"HW (1)

1"

13

0

13

3RD

20

1-1/4"

24

0

24

4TH

15

.

2-1/2"CW (105)

..

.

10

47

5TH OR MORE

158

64

10

3/4"HWR

WH-1

120

245

.

246 .

3"

691

630

..

. . DF

1"HW (10) 1"HW (6)

.

RHB

3/4"CW (6) 3/4"HW (3)

1-1/4"HW (20)

412

2-1/2"CW (111)

3/4"HW (3)

SS

. 380

KEY PLAN

2-1/2"CW (147)

3/4"HW (6) 2-1/2"

1"HW (10)

3/4"CW (3)

. 2"

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

.

. 47

3/4"CW (1)

3/4"CW (3)

2-1/2"CW (150)

1-1/2"

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

LAV

FD

3/4"CW(3) 3/4"HW(3)

1-1/2"CW (23) 1-1/2"HW (23) 1-1/2"CW (26) HWR

30

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

2"CW (41)

FD

CW - FT (FU)

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

3/4"HW (1) RHB

WC

0

.

. .

2"CW (98)

6

SCHOOL DISTRICT:

2-1/2"CW (75) 3/4"CW (1) 3/4"HW (1)

2"CW (95)

3/4"

2-1/2"CW (135)

3/4"HW (6) BASED ON 3 PPSI PER 100 FEET LOSS

1-1/4"HW (18) .

2-1/2" CW (102)

.

2-1/2"CW (178)

.

2" CW (47)

RHB HB LAV WC

2" CW (44)

. .

.

1-1/4"HW (14) 1-1/4"HW (15) 2-1/2"CW (70) SS

2" CW (41) 1-1/4"HW (15)

.

LAV

WC WC FD

3"CW (267)

.

.

LAV

WC

LAV

HB

TP WC

WC

2-1/2"CW (112) 1"HW (10)

WC

WC

FD

.

FD

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

TP TP

WC

3/4"CW (5) 3/4"HW (2)

DF

FD

3"CW (272) TP

COPYRIGHT: CSDA ARCHITECTS 2011

HB

2-1/2"CW (75) 3/4"HW (2)

. . .

. LAV

. .

FD

TP . .

3/4"CW (6) 3/4"HW (3)

LAV LAV HB LAV . .

2-1/2" CW (99)

.

RHB

1"CW (8) 3/4"HW (2)

2-1/2"CW (158)

3/4"CW (3)

SS

3/4"HW (1) 2"CW (44)

2"CW (40)

CW & HW PIPE SIZING

FLS

AC DATE

3/4"HW (2) 2"CW (41)

2-1/2"CW (125)

RHB WC LAV

WC

WC FD

LAV

TP

SHEET TITLE

LAV

LAV

WC

WC WC

3D RISER DIAGRAMS

WC FD

TP

TP

2" CW (40) 3/4"CW (1) 3/4"HW (1)

FD

TP FD

WC

3"CW SOV IN YARD BOX 3"CW, FOR CONTINUATION, SEE CIVIL DRAWING

ORIGINAL SCALE 0

3"CW (360) RHB

LAV

FD

WC

TP

3D RISER - CW & HW

1

1"

JOB NO.: SHEET NUMBER:

P-420

2"


1-1/4" GAS SUPPLY 1-1/2" COLD WATER SUPPLY 3/4" HOT WATER RETURN 10'-0" CLAMP-ON AQUASTAT FOR PUMP CONTROL SHUT-OFF VALVE (TYP.) 3" PVC VENT UTR 3" PVC INTAKE AIR UTR

CP 1

CLEANOUT IN YARDBOX

12" SQ.x6" DEEP CONCRETE PAD

CLEANOUT IN YARDBOX

TRENCH EXCAVATION

CONCRETE

BACKFILL AS PER SPECIFICATONS

9"

BLACKTOP PAVING

GROUND LINE

THE SLOPE OF THIS LINE MUST BE APPROVED BY THE STRUCTURAL ENGINEER

2"

CHECK VALVE UNION (TYP.)

1"

1'-6" MIN. PRESSURE & TEMPERATURE RELIEF VALVE D

4"

TRENCH EXCAVATIONS

3/4" DRAIN SPILL TO EXIST. FLOOR SINK

1" 4"

4"

4"

G

NOTE: FOR PIPES MORE THAN 3'-0" BELOW BOTTOM OF FOOTING STEP AS REQUIRED

NOT PARALLEL TO FOOTING

DRAIN VALVE 2"x2"x1" ANGLE IRON CLIP (TYP. FOR 3) 1/2" X 2" EMBEDMENT HILTI KB-TZ (TYP.)

WATER HEATER DETAIL NOT TO SCALE

TYPICAL EXTERIOR CLEAN OUT DETAIL

8

COMPACTED FILL OF INUNDATED SAND MAY BE USED IN WELL DRAINED SANDY OR GRAVELLY SOIL 90% DENSITY

2"

1/2" BOLT WITH WASHER INTO BACKING (TYP. 4 PLACES). FOR BACKING SEE DETAIL 2Q ON SHEET S8.1 PROVIDE 2"x12 GAUGE GALV. STEEL STRAP AROUND WATER HEATER WITH 1/2" NUT & BOLT WITH WASHER (TYP. 2 PLACES)

1-1/2" HOT WATER SUPPLY

NOT TO SCALE

ALL PIPE SLEEVES 2" MIN. LARGER THAN PIPE 3" MIN.

SECTION 4

NO PIPES ALLOWED IN FOOTING

3" MIN.

3" MIN.

6" MIN. 3'-0" MAX.

PIPE SLEEVE DIA. PLACE CONC. FILL AROUND SLEEVES BEFORE POURING FOOTING

6" MIN.

PIPE AT FOOTING DETAIL

4" LONG FLEXIBLE HOSE STAINLESS STEEL HOSE CLAMPS TYPICAL UNIT

NOT TO SCALE

1"

MINERAL WOOL INSULATION MIN 1" DEEP (TYP)

PIPE SLEEVE

3M FIRE BARRIER ¼" BEAD CP25 CAULK (TYP)

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

FOR USE WITH THE FOLLOWING TYPES OF HINGE ARRANGEMENTS

"I" OR "WF" BEAM CLAMP 2 3/8" - 7" FLANGES 1365# MAX

3" MIN TRAP

CREATIVE DESIGN

PIPE HANGER

"I" BEAM CLAMP 2' 6 1/2" FLANGES 540# MAX

ADJUSTABLE SWIVEL COUPLINGS <2300#

INSULATION

CONSULTANT STAMP

LINKED EYE RODS

NOT FOR CONSTRUCTION USE

CHANNEL CLAMP 1740# MAX

PIPE

NOTES:

1

U.L. LISTED SYSTEM CAJ5001

1. CONDENSATE DRAIN PIPING SHALL BE TYPE "M" COPPER.

1. DETAIL SIMILAR FOR UNINSULATED PIPE.

CONDENSATE DRAIN EQUIPMENT CONNECTION DETAIL

9

NOT TO SCALE

SWIVEL HANGER PLANGE

PIPE THRU CONCRETE FLOOR OR WALL DETAIL NOT TO SCALE

AUTHORITY APPROVAL

ADJUSTABLE SWIVEL HANGAR FLANGE

CONCRETE INSERT

NOTES:

IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249

PIPE HANGARS FOR OTHER THAN ADJUSTABLE WROUGHT IRON

CONCRETE INSERTS

5

TYP. PIPE W/ ALUMINUM JACKET & INSULATION

ANNULAR SPACE SPACE SHALL BE ¼" TO 3/8"

FOR THREADED ROD

UNISTRUT 1 5/8 CHANNEL SERIES P3000 WELDED TO 1 1/4" SCHEDULE 40 PIPE

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT

RING

VERTICAL PIPE SUPPORT AT EACH FLOOR EXTENSION CALMED WITH TEFLON OR LEAD LINER WHEN USE COPPER PIPE.

PIPE

LEAD FLASH (TYPICAL)

16350 MOJAVE DRIVE VICTORVILLE, CA 92395

CONC. FL.

SCHOOL ADDRESS:

SUBMERGED GALV. SUPPORT PIPE

1 1/4" PIPE (TYP.)

FLASHING & COUNTER FLASHING (TYPICAL)

CLEVIS RING

FOR THREADED PIPE AS HANGAR ROD

UNISTRUT PIPE CLAMP

ELASTOMERIC WRAP STRIP WITH FOIL FACE 2 IN. WIDE BIND W/ STEEL WIRE OR ALUMINUM FOIL TAPE 3M TYPE FS-195 OR EQUAL.

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

ALL PIPES AND DUCTS SHALL BE SUPPORTED AND BRACED PER "SMACNA" GUIDELINES OSHPD PRE-APPROVAL NO. R.0010

INSULATION

SS

SCHOOL DISTRICT:

WOOD CEILINGS, BEAMS, OR JOISTS

3M FIRE BARRIER BEAD CP25 CAULK (TYP)

FLS

AC DATE

4 WEDGE TYPE

INSULATION SHIELD REQUIRED FOR INSULATED PIPE

CONSULTANT

GROUT

6" MAX

SEE PLAN FOR SIZE

ARCHITECT STAMP

2" CEM. DRYPACK IF PLACED UNDER EXISTING FOOTING

ALL PIPE SLEEVES 2" MIN. LARGER THAN PIPE

d + 1'-6"

SLOPE DOWN TOWARDS APPROVED RECEPTOR @ 1/8" PER LINEAR FOOT.

design@csdarchitects.com T:310.821.9200 F:310.821.9201

NO PIPE TRENCH PARALLEL TO FOOTING BELOW THESE LINES

4"

4" WH 1

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292

PIPE HANGING COMPONENT DETAIL

3/4"+

NOT TO SCALE

RATED WALL

2

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

U.L. LISTED SYSTEM WL-5001

NOTES:

BARE METAL DECK

1. FOR UNINSULATED PIPE WRAP STRIP MAY BE ELIMINATED AND ANNULAR SPACE SHALL BE 0-3/16 INCH, WITH CAULK ONLY.

6 4"C O.

4"

33" APPROX.

C.I. NT VE

SEALED OFF FLANGE

.I. C ENT V

O. 4"C

ROOFING

4"C.I.

(TYPICAL) 12" LONG BRAIDED FLEX CONN BRASS THREADED ENDS

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO

30" APPROX.

COUPLING

24 GA. GALV. STEEL PIPE FLASHING

FIG. NO. 1

4"C.I.

FLASHING & COUNTER FLASHING

FIG. NO. 2C

C.I. VENT

AC UNIT

T EN

PIPE SEE PLANS FOR SIZE & CONT.

I. V C.

LEAD COLLAR

4"C.I.

FIG. NO. 3

34 1/2" MAX 23 1/2" MIN

NOT TO SCALE

28" APPROX.

10

24"APPROX.

PIPE THRU FIRE WALL DETAIL

C.I. VENT

NOT TO SCALE

2. OTHER U.L. LISTED SYSTEMS MAY BE USED, SUBMIT FOR REVIEW.

21"APPROX.

PIPE SUPPORT ON ROOF DETAIL

22 S-12

C.I. VENT

FOR CONNECTION TO ROOF SEE STRUCTURAL DETAIL

COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

4"CO.

SEE DRAWING FOR CONT

FIG. NO. 2A

GAS STOP - IRON BODY W/BRONZE PLUG & WASHER

FLASHING COMPOUND

ROOF DECK

ALTERNATE POSITION OF CO. LINE

FIG. NO. 2

NOTE: FOOTINGS MUST BE LOWERED TO SUIT THE INSTALLATION OF CLEAN-OUT LINES IN FIGURES HR2, 2A, 2B, 2C & 3

SLEEVE THRU ROOF (TYPICAL)

DETAILS

4"

4"

ALTERNATE POSITION OF 4" COMB. FITTING W/ RUN COMING TOWARD OBSERVER & 4" CO ON OPPOSITE END.

FIG. NO. 2B

ORIGINAL SCALE 0

GAS TO EQUIPMENT CONNECTION DETAIL NOT TO SCALE

PIPE THRU ROOF DETAIL 11

NOT TO SCALE

7

WATER CLOSET SOIL PIPE CONNECTION DETAIL NOT TO SCALE

3

1"

JOB NO.: SHEET NUMBER:

P-500

2"


REVISIONS

BY

KEY NOTE: ROOF 3" GAS TO EXISTING 3" GAS LINE ON ROOF

1

AMERICAN METER GAS REGULATOR, 15 PSI, 2" INLET, MODEL 1803.

2

AMERICAN METER GAS REGULATOR, 15 PSI, 1-1/2" INLET, MODEL 1803.

3

4" GAS BELOW GRADE CONNECT TO EXISTING GAS TO WEST CAMPUS, VERIFY EXACT LOCATION ON SITE

4

6" GAS BELOW GRADE CONNECT TO EXISTING GAS TO EAST CAMPUS, VERIFY EXACT LOCATION ON SITE

5

REMOVE EXISTING GAS PIPING INCLUDING PIPING ON ROOF OF EXISTING ELECTRICAL ROOM

6

GAS SHUT OFF VALVE

7

6" GAS UP OFFSET ON ROOF

8

POINT OF CONNECTION TO EXISTING 6" GAS ON ROOF

9

EXISTING 6" GAS ON ROOF, VERIFY EXACT LOCATION ON SITE

10

3" GAS UP OFFSET ON ROOF

11

POINT OF CONNECTION TO EXISTING 6" GAS ON ROOF

12

EXISTING 3" GAS ON ROOF, VERIFY EXACT LOCATION ON SITE

13

4" GAS BELOW GRADE CONNECT TO EXISTING GAS TO POOL, VERIFY EXACT LOCATION ON SITE

14

6" GAS OFFSET BELOW GRADE

15

6" GAS MANIFOLD, OFFSET (4) GAS PIPES BELOW GRADE: 4" GAS TO WEST CAMPUS, 2" GAS TO OLD GYM, 6" GAS TO EAST CAMPUS, AND 4" GAS TO POOL.

16

THE GRAVITY LINES SHOULD BE PLACED FIRST TO ALLOW ENOUGH CLEARANCE BETWEEN ALL PIPING BELOW GRADE

17

6" GAS BELOW GRADE CONNECT TO EXISTING GAS TO NEW GYM, VERIFY EXACT LOCATION ON SITE

18

2" GAS BELOW GRADE CONNECT TO EXISTING GAS TO OLD GYM, VERIFY EXACT LOCATION ON SITE

6" GAS TO EXISTING 6" GAS LINE ON ROOF

6

UNION (TYP.)

2

15

1

1 6

1

FLOOR

6

TEST PORT (TYP.) 6

TEST PORT (TYP.) 1-1/2" MPG

6

2" MPG

2" MPG 6" GAS TO NEW GYM 2" MPG 4" GAS TO WEST CAMPUS 2" GAS TO OLD GYM 6" GAS TO EAST CAMPUS 4" GAS TO POOL

SECTION DIAGRAM NOT TO SCALE

2

GENERAL NOTE: PROVIDE EARTHQUAKE SHUT OFF VALVE AT EACH EXISTING BUILDING IF IT IS NOT ALREADY INSTEALLED.

2

11

1-1/2" MPG

3

9

10

2

13

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 (818) 507-7522

12

CREATIVE DESIGN

GPL

CAP (TYP.) 8

7 1 6

5

15

5

1

4

6 14

3" MPG 2"MPG 4"MPG 2"MPG 4"MPG

1 6 6"

2"

18 16

4" MPG

6"

17

16

16

16

G

4" MPG

4" MPG

MPG

4 1-1/2" MPG 6

2

MPG 16

4", 5 PSI GAS PRESSURE BELOW GRADE 4", 5 PSI MEDIUM GAS LINE DOWN TO BELOW GRADE GAS METER ASSEMBLY HIGH PRESSURE GAS PIPING TO BELOW GRADE BY GAS COMPANY

TO MAIN GAS LINE BY GAS COMPANY

16500 MOJAVE DRIVE VICTORVILLE, CA 92395

JOB TITLE

GAS PIPING LAYOUT

SHEET TITLE

N D

VVHS - GAS PIPING LAYOUT

(N) ADMINSTRATION BUILDING

PROJECT # DATE

07/26/2012

DRAWN BY

PP

CHECKED BY

VO

SHEET NUMBER

GAS PIPING LAYOUT 1" = 20'-0"

1

GPL