EXHAUST FAN SCHEDULE
SHEET INDEX MOTOR
MANUFACTURER AND MODEL
TYPE
CFM
ESP IN (WG)
FAN RPM
HP (WATTS)
VOLT
PH
HZ
WEIGHT (LBS)
ANCHOR. DETAIL
REMARKS
SHEET TITLE
M-001
LEGENDS, NOTES, AND SCHEDULES
EF 1
TOILET 159
LOREN COOK GC-160
CEILING
140
0.25
1,500
113
120
1
60
15
-
-
PROVIDE BACKDRAFT DAMPER
M-110
MECHANICAL FIRST FLOOR PLAN
EF 2
TOILET 207
LOREN COOK GC-160
CEILING
140
0.25
1,500
113
120
1
60
15
-
-
PROVIDE BACKDRAFT DAMPER
M-111
MECHANICAL SECOND FLOOR PLAN
EF 3
JANITOR 209
LOREN COOK GC-180
CEILING
200
0.25
1,500
192
120
1
60
16
-
-
EF 4
TOILETS 106, 108, 109
LOREN COOK 80C2B
ROOF VENTILATOR
400
0.5
1,260
1/6
120
1
60
30
12 M-500
EF 5
TOILETS 136, 137
LOREN COOK 80C2B
ROOF VENTILATOR
300
0.5
1,239
1/6
120
1
60
30
EF 6
MEN'S RESTROOM 133
LOREN COOK 120C2B
ROOF VENTILATOR
750
0.5
1,151
1/6
120
1
60
EF 7
WOMEN'S 134, 212 AND MEN'S RESTROOMS 211
LOREN COOK 180C3B
ROOF VENTILATOR
1,600
0.5
742
1/4
120
1
60
S
ON-OFF SWITCH
T
THERMOSTAT
ABV ABOVE BEL BELOW BTU BRITISH THERMAL UNIT CAP CAPACITY CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CG CEILING GRILLE CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CR CEILING REGISTER D DRAIN DB DRY BULB DL DOOR LOUVER DN DOWN DTR DOWN TRHU ROOF EA EXHAUST AIR (E) EXISTING ENT ENTERING F.A. FACE AREA F FARENHEIT FLA FULL LOAD AMPS FPI FINS PER INCH FPM FEET PER MINUTE FLEX FLEXIBLE GALV GALVANIZED GA GAUGE HP HORSEPOWER IN INCH ISOL ISOLATOR LBS POUNDS LVG LEAVING EMS ENERGY MANAGEMENT SYSTEM M.A. MIXED AIR MAX MAXIMUM MBH 1000 BTU'S PER HOUR (N) NEW MIN MINIMUM MOD MODULATING DAMPER MVD MANUAL VOLUME DAMPER NTS NOT TO SCALE OPER. WT. OPERATING WEIGHT OPG OPENING OSA OUTSIDE AIR PD PRESSURE DROP PH PHASE PRESS PRESSURE POC POINT OF CONNECTION PSI POUNDS PER SQUARE INCH RA RETURN AIR RAR RETURN AIR REGISTER REQ'D REQUIRED RLA RATED LOAD AMPS RPM REVOLUTIONS PER MINUTE Ø ROUND DUCT SA SUPPLY AIR SP STATIC PRESSURE SF SQUARE FEET SWR SIDEWALL REGISTER SL SOUND LINED TEMP TEMPERATURE T'STAT THERMOSTAT TYP TYPICAL UTR UP THRU ROOF V VOLT VTR VENT THRU ROOF W/ WITH WB WET BULB W.G. WATER GAUGE
SECTION THRU RECTANGULAR SUPPLY DUCT SECTION THRU RECTANGULAR RETURN DUCT SECTION THRU RECTANGULAR EXHAUST DUCT
PROVIDE BACKDRAFT DAMPER
M-130
MECHANICAL ROOF PLAN
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-310
BUILDING SECTIONS
12 M-500
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-500
DETAILS
55
12 M-500
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-510
VIBRATION ISOLATOR DETAILS
90
12 M-500
18"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-511
VIBRATION ISOLATOR DETAILS
M-520
EMS DIAGRAMS
FLEXIBLE CONNECTION R
SERVICE
SHEET NUMBER
DUCT RISE IN DIRECTION OF FLOW
D
UNIT
FAN WHEEL DIA. IN (MIN)
MECHANICAL LEGENDS & ABBREVIATIONS
DUCT DROP IN DIRECTION OF FLOW MANUAL VOLUME DAMPER (MVD) AUTOMACTIC FIRE DAMPER (AFD) MODULATING DAMPER (MOD) BACKDRAFT DAMPER (BDD) STATIC PRESSURE DAMPER
SOUND TRAP SCHEDULE DESIGNATION ST 1-1
MFG MODEL
UNIT SIZE (INCHES)
P.D. (IN. W.G.)
125
250
500
1000
2000
4000
8000
VEL. FPM
PRICE RLX60/2F
18x14
0.23
14
28
42
48
48
37
21
914
1,600
PRICE RMX60/4G
26X12
0.15
16
31
43
51
45
27
13
738
5
112
ON RETURN AIR DUCTWORK
CFM
ST 2-1
DECIBELS
1,600
LENGTH (FT)
OPER. WT. (LBS)
ST 2-2
ST 3-1
ST 4-1
ST 5-1
2,400
PRICE RMX60/4G
28x14
0.22
13
27
40
47
45
28
15
882
5
124
ON SUPPLY AIR DUCTWORK
ST 3-2
ST 4-2
ST 5-2
1,680
PRICE RMX60/1F
36X12
0.17
14
25
42
51
50
34
21
800
5
162
ON RETURN AIR DUCTWORK
3,000
PRICE RLX60/1F
36X14
0.35
14
32
45
50
51
46
26
857
5
176
ON RETURN AIR DUCTWORK
6,000
PRICE RLX60/1F
40X20
PRICE RLX60/1F
48X16
ST 9-1
ST 10-1
ST 9-2
6,000 ST 10-2
4,065
ST 10-3
1,875
PRICE RLX60/1F
36X18
PRICE RMX60/4G
24X16
0.79
11
0.79
14
1.5
14
1.5
13
26
33
32
27
41
45
46
51
51
45
51
50
40
51
47
45
48
45
46
28
30
5
1,260
25
26
ENERGY COMPLIANCE FORMS
SD SMOKE DETECTOR
M-531
ENERGY COMPLIANCE FORMS
BD
BYPASS DAMPER
SOUND LINED (SL) DUCT W/ INTERNAL INSULATION. DUCT SIZES SHOWN ARE NET INSIDE DIMENSION
MEP COMPONENT ANCHORAGE NOTE: ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 1615A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
ON RETURN AIR DUCTWORK
124
COMBINATION FIRE/SMOKE DAMPER
SOUND TRAP
ON RETURN AIR DUCTWORK
162
5
738
M-530
ON SUPPLY AIR DUCTWORK
213
5
857
15
213
5
1,125
M
ON SUPPLY AIR DUCTWORK
ST 1-2
ST 6-1
EMS DIAGRAMS
REMARKS
110
5
M-521
ON RETURN AIR DUCTWORK
SINGLE LINE RIGID SHEET METAL DUCTWORK
A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
NOTES: PROVIDE DUCT TRANSITION FROM SOUND TRAPS TO RELATED DUCTWORK AS NEEDED
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
M
FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR
E
FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR
ME
FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR
EM
FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR
CC
CLOSING COIL IN MAGNETIC STARTER
SW
SWITCH
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
ARCHITECT STAMP
CONSULTANT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22. THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PREAPPROVALS WITH AN OPA #, AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D.
FLS
AC DATE
ZONE
SS
AC NUMBER ZONE NUMBER
Z1-1 1000
ZONE CFM
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.
BYPASS DAMPER
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
BD-1 1000
AC NUMBER
SCHOOL DISTRICT:
DAMPER CFM
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
SPLIT SYSTEM COOLING UNIT SCHEDULE INDOOR UNIT COOLING CAPACITY (MBH)
SEER
290
12
15.2
1
0.33
208
1
ELECTRICAL ROOM 107
570
24
17
1
0.36
208
ELECTRICAL ROOM 124
635
34.2
14
1
0.57
208
MANUFACTURER AND MODEL
SERVICE
FC 1
MITSUBISHI PKA-A12HA4
ELECTRICAL ROOM 155
FC 2
MITSUBISHI PKA-A24KA4
FC 3
MITSUBISHI PKA-A36KA4
UNIT
OUTDOOR UNIT
CFM
MCA
FLA
V
OPER. WEIGHT
ANCHOR. DETAIL
60
29
2 M-511
1
1
60
46
2 M-511
1
60
46
2 M-511
PH
HZ
OPER. WEIGHT
ANCHOR. DETAIL
60
82
1 M-511
1
60
165
1 M-511
1
60
165
1 M-511
MANUFACTURER AND MODEL
MCA
CU 1
MITSUBISHI PKY-A12NHA4
13
15
208
1
1
CU 2
MITSUBISHI PKA-A24NHA4
18
30
208
1
CU 3
MITSUBISHI PKA-A36NHA4
25
40
208
REMARKS
UNIT
MOCP
V
PH
HZ
REMARKS
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
NOTES: 1
PROVIDE WITH CONDENSING PUMP
PACKAGED AIR CONDITIONING UNIT SCHEDULE COOLING CAP UNIT
MANUFACTURER
SERVICE AREA
MODEL
CFM
HEATING CAPACITY
ESP IN (WG) TOTAL
SENSIBLE
EWB TEMP. ºF
ENT COND TEMP ºF
SEER
INDOOR FAN
CONDENSER COIL
EVAPORATOR COIL
OUTDOOR FAN
EER INPUT MBH OUT MBH
ROWS
FPI
FACE AREA
ROWS
FPI
FACE AREA
NO.
SIZE
RPM
BHP
NO.
SIZE
RPM
BHP
COMP NO.1 RLA
COMP NO.2 RLA
OFM (FLA) IFM (FLA) EACH EACH
FILTERS (INCHES)
V
PHASE
HZ
MCA
MOCP
OPER. WEIGHT INCLUD. CURB
ACCESSORIES INTEGRATED
REMARKS
ANCHORAGE
AC 1
CARRIER
CORRIDOR 217
48HCFD05
1,600
1.0
47.7
37
67º
105º
15.6
13
120
96
3
15
7.3
2
17
23.1
1
10X10
1,208
2.9
1
22"DIAM.
1,100
1/4
6.2
-
0.9
2.7
460
3
60
10.8
15
(4)16X20X2 (1)20X36X1
910
1
2
3
4
5
6
7
1 M-510
AC 2
CARRIER
TEXTBOOK 213
48HCFD05
1,600
1.0
47.7
37
67º
105º
15.6
13
120
96
3
15
7.3
2
17
23.1
1
10X10
1,208
2.9
1
22"DIAM.
1,100
1/4
6.2
-
0.9
2.7
460
3
60
10.8
15
(4)16X20X2 (1)20X36X1
910
1
2
3
4
5
6
7
1 M-510
AC 3
CARRIER
CLASSROOM 214
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
2.9
2
22"DIAM.
1,100
1/4
9.7
9.7
0.8
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
5
6
7
2 M-510
AC 4
CARRIER
CLASSROOM 215
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
2.9
2
22"DIAM.
1,100
1/4
9.7
9.7
0.8
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
5
6
7
2 M-510
AC 5
CARRIER
CLASSROOM 216
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
2.9
2
22"DIAM.
1,100
1/4
9.7
9.7
0.8
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
5
6
7
2 M-510
AC 6
CARRIER
MUSEUM 100
48HCFD08
3,000
1.0
88.2
70.1
67º
105º
-
12
224
184
4
15
11.1
2
17
25.1
1
15X15
1,084
2.4
2
22"DIAM.
1,100
1/4
6.1
6.1
0.8
2.6
460
3
60
21.1
25
(4)20X20X2 (1)20X24X1
1,350
1
2
3
4
5
6
7
2 M-510
AC 7
AC 8
CARRIER
FIRST FLOOR NORTH OFFICES
48HCFD24
7,000
1.6
232.6
170.4
67º
105º
-
12
400
324
4
15
26
2
17
29.6
2
18X15 15X11
1,176
8.7
4
22"DIAM.
1,100
1/4
18.6
14.7
0.9
6.4
460
3
60
53.8
60
(9)16X25X2 (4)16X25X1
3,250
1
2
3
4
5
6
7
3 M-510
AC 9
AC 10
CARRIER
SECOND FLOOR LIBRARY
48HCFD24
7,000
1.6
232.6
170.4
67º
105º
-
12
400
324
4
15
26
2
17
29.6
2
18X15 15X11
1,176
8.7
4
22"DIAM.
1,100
1/4
18.6
14.7
0.9
6.4
460
3
60
53.8
60
(9)16X25X2 (4)16X25X1
3,250
1
2
3
4
5
6
7
3 M-510
CARRIER
FIRST FLOOR WEST OFFICES
2
18X15 15X11
60
(9)16X25X2 (4)16X25X1
7
4 M-510
AC 11
48HCFD28
9,000
1.6
284.4
210.8
67º
105º
-
11.2
400
324
4
15
26
2
17
34.3
1,010
8.7
6
ACCESSORIES NOTES: 1
ELECTRICAL
TIME GUARD II CONTROL CIRCUIT
2
100% DRY-BULB TYPE ECONOMIZER
3
100% BAROMETRIC RELIEF
4
MODULATING POWER EXHAUST
5
CO2 SENSOR
6
POWERED CONVENIENCE OUTLET
7
THE AIR-MOVING EQUIPMENT IS SERVED BY A TOTAL COVERAGE SMOKEDETECTION SYSTEM COMPLYING WITH THE CALIFORNIA FIRE CODE
22"DIAM.
1,100
1/4
18.6
18.6
0.9
9.7
460
3
60
63.6
3,470
1
2
3
4
5
6
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
LEGENDS, NOTES, AND SCHEDULES ORIGINAL SCALE 0
1"
JOB NO.: SHEET NUMBER:
M-001
2"
5.5 AC-7 ZONE DAMPER SCHEDULE DESIGNATION
CARRIER MODEL NUMBER
Z7-1
INLET SIZE
CFM
35JN1
1
7
DESIGNATION
2
CARRIER MODEL NUMBER
Z11-1
35JN1
1500
35
35
INLET SIZE
CFM
35
REMARKS
16"Ø
1
Z8-8 1050
4
2
10"ø
10"ø
32
J
10"ø
12"ø
12"ø
16"ø
35JN1
Z7-5
10"Ø
1200
35JN1
1
16"Ø
600
2
2
1
10"Ø
Z11-2
Z11-3
2
1
35JN1
35JN1
Z11-4
2
650
650
35JN1
Z11-5
12"Ø
12"Ø
600
35JN1
1
1
10"Ø
450
2
Z8-7 800
2
1
35JN1
Z7-7
600
35JN1
10"Ø
1300
1
16"Ø
2
1
Z11-6
2
35JN1
Z11-7
800
35JN1
14"Ø
400
2
40
(Z8-2) T
9"ø
24"x20" 10"Ø
1
Z11-8
2
PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK
35JN1
Z11-9
PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC
35JN1
Z11-10
Z8-1
500
35JN1
Z8-3
2
1
16"Ø
10"ø Z8-2 600 12"ø
2
1
10"ø
2
2
12"ø
PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC
14"Ø
500
10"Ø
DESIGNATION
CARRIER MODEL NUMBER
CFM
PASO-18
7,000
BD-7
2
1
BD-8
2
INLET SIZE
44 (Z8-1) T
REMARKS
PASO-18
7,000
1
22"X28"X18"
2
1
35JN1
1400
16"Ø
1
BD-11
2
PASO-24
9,000
22"X42"X18"
1
14 ATHLETIC DIRECTOR 126
35JN1
Z8-8 1 2
800
35JN1
12"Ø
1050
1
14"Ø
2
1
1
2
PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK
2
PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK
38"x20"
M
31
12"ø
17
20"x16"
PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC
12"ø
PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC
BDD 12"x8"
ASB / ACTIVITIES DIRECTOR 127(Z7-8) T
7"ø
24
10"x8" STAFF TOILET 109
Z7-2 700
14"ø
12"x8" 7"ø
51
6
COT 38"x20" 105
4
TOILET 106 8"ø 12"ø
8
CORRIDOR 130 Z7-1 1500
SICK ROOM 104
10"ø 8"ø 16"ø 12"ø
10"ø
DL 12"ø
24 18"ø
18"ø
Z7-3 500 42
16"ø
25
12"ø
ASB WORK & CONFERENCE ROOM 129
28
8 1
UP
C
3
N D 16
10"ø
TOILET 159
EF 1 6
9
STORAGE 158
32"x20"
12"ø
17 PRINCIPAL'S ASSISTANT 12"ø 157
8
8
AP CONFERENCE ROOM 156
M
36"x20"
A
10
OFFICE ASSISTANT 151A
T (Z11-4) T (FC-1)
10"ø 4 M
24"x20" 2
(Z11-3) T
15
14
AP OFFICE 151
9"ø
7
WAITING 150
15 7
9"ø
WAITING 149 12"ø
20
SRO OFFICE 138
48"x
STORAGE 142
(Z11-2) T 14
Z11-3 650
5
AP OFFICE 141 10"ø
Z11-2 650
24"x20"
27 T (Z7-6) M
RECORDS STORAGE 12"ø 101
2
" 20 x 4"
9"ø 8
9.5
53
53
10
UP 12"x8" 14"ø
T (Z11-1)
14"ø
10"ø
6
20 8"ø 10"x8"
STAFF TOILET 137
8"ø 21
3
STAFF TOILET 136 7"ø
6
8"X8" CD-3W, 100 CFM
7
10"x10" CD-4W, 250 CFM
8
12"x12" CD-4W, 300 CFM
9
14"x14" CD-4W, 450 CFM
10
16"x16" CD-4W, 550 CFM
11
10"x10" CR, 235 CFM
12
18"x18" CR, 800 CFM
13
18"x18" CR, 1000 CFM
14
12"x12" CR, 370 CFM
15
10"x10" CR, 220 CFM
16
16"x16" CR, 640 CFM
17
14"x14" CR, 420 CFM
18
16"x16" CR, 550 CFM
19
12"x12" CER, 300 CFM
20
8"X8" CER, 150 CFM
21
10"X8" EXHAUST DUCT UP TO SECOND FLOOR
22
14"X8" EXHAUST DUCT UP TO SECOND FLOOR
23
14"X14" CD-4W, 500 CFM
24
14"X14" CD-2W, 500 CFM
25
16"X16" CD-4W, 650 CFM
26
12"X12" CD-2W, 400 CFM
27
14"X14" CR, 545 CFM
28
18"X18" CR, 900 CFM
29
20"x20" CR, 1200 CFM
30
38"x20" SA (SL) UP TO SECOND FLOOR
31
38"x20" RA (SL) UP TO SECOND FLOOR
32
14"X14" CD-3W, 450 CFM
33
12"X12" CD-3W, 4300 CFM
34
10"X10" CD-3W, 200 CFM
35
12"X12" CD-3W, 350 CFM
36
10"X10" CD-2W, 250 CFM
SCHOOL DISTRICT:
37
12"X12" CD-2W, 300 CFM
38
14"X14" CR, 420 CFM
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
39
18"X18" CR, 755 CFM
40
12"X12" CR, 320 CFM
41
16"X16" CR, 615 CFM
42
12"X12" CR, 270 CFM
43
10"X10" CR, 170 CFM
44
14"X14" CR, 455 CFM
45
18"X18" CR, 1100 CFM
46
14"x6" SA DUCT COVERED WTIH 1/2" MEST SCREEN UP TO SECOND FLOOR
47
14"x6" EXHAUST DUCT UP TO SECOND FLOOR
48
10"x4" EXHAUST DUCT UP TO SECOND FLOOR
49
8"X8" CER, 120 CFM
50
12"X8" EXHAUST DUCT UP TO SECOND FLOOR
51
8"X8" CER, 160 CFM
52
TITUS LINEAR SUPPLY DIFFUSER MODEL MLR-39TZ, 1" SLOT, 4 SLOTS, 6'-0" LONG, 600 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL
53
TITUS LINEAR SUPPLY DIFFUSER MODEL MLR-39TZ, 1" SLOT, 3 SLOTS, 5'-0" LONG, 300 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL
54
36"x12" SA (SL) DUCT UP TO 2ND FLOOR
55
TITUS LINEAR RETURN DIFFUSER MODEL MLR-38TZ, 3/4" SLOT, 3 SLOTS, 5'-0" LONG, 375 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL
56
REFRIGERATION PIPING RL & SL (INSULATED) UP TO SECOND FLOOR
design@csdarchitects.com T:310.821.9200 F:310.821.9201
CONSULTANT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249 FLS
AC DATE
SS
16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
MECHANICAL FIRST FLOOR PLAN
9"ø
19
10"X10" CD-4W, 200 CFM
SHEET TITLE
WOMEN'S RESTROOM14"x8" 134
11
9"ø
6
5
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
COPYRIGHT: CSDA ARCHITECTS 2011
22
20"
12"X12" CD-4W, 400 CFM
27
12"x6"
CORRIDOR 132 53
55
8"ø
18"ø
9.3
7"ø
7"ø
42"x20"
T (Z7-5)
M
BD-11
DUCT SHAFT
M M 24 14"ø "x 14 "
7"ø
M
M
STORAGE 143
3
9"ø
M
4 12"ø
19
10"ø
9"ø 10"ø
36"x20"
2 M-511
DL
10"ø DL
12"ø Z11-4 600
JANITOR 139 16"ø
DL
DL
OFFICE ASSISTANT M 141A
9"ø
SERVER / ELECTRICAL ROOM 155 FC 1
1
40"x18"
STORAGE 152
18
9"ø
12"ø
12"ø
12"x6"
4
8
18"x6"
ELEVATOR 22 -
9"ø T (Z11-1O)
K
52
14"x8" MEN'S RESTROOM 133
SECURITY OFFICE 140 11
DL
CORRIDOR 162
DL
9"ø
10
10
16"ø
12"ø
DL Z11-5 450
TA WORKSPACE 151B
36"x18"
(Z11-5) T
8"ø
STORAGE Z11-11 2200 145 T (Z11-11) 5 18"ø OFFICE ASSISTANT STORAGE 146A 20"x18" 144
28"x18"
12"ø
ELEVATOR MACHINE ROOM 135
7
LOBBY 100
2" x1 " 20
19
13
DL
(Z11-6) T
8"ø
T (Z11-9)
9"ø 9"ø
OFFICE ASSISTANT 154A 12"ø 20"x18" TA WORKSPACE 16"ø 154B
Z11-10 450
9"ø
14 10"ø
13 Z11-6 800
14
9"ø 15 15
12"ø
48"x20"
7"ø
9"ø
10"ø (Z11-8) T
10
14"ø
12"ø
10"ø AP OFFICE 146
48"x20"
T (Z11-7)
14"ø
12"ø WAITING 147
7
36"x20"
3
WAITING 148
7
56 STORAGE 153
28"x18"
10"ø 10"ø PRINCIPAL'S CONFERENCE ROOM 161 10"ø PRINCIPAL'S OFFICE 14 160 10"ø
53
AP OFFICE 154 12"ø
Z11-7 400
4
28"x20"
3
18"x6"
12"x6"
24"x20"
28"x20"
" 12 x 6"
52
FULL LOUVER DOOR 4
4
B
12"x6"
24"x20"
12"X12" CD-4W, 350 CFM
16"ø
Z7-6 600 9"ø
M
53
M-310
48
REGISTRAR 102 9"ø
14"ø
(Z7-1) T
36"x12"
Z11-9 650
L
" 16 "x 22
M
Z11-8 650
9"ø
16"ø CORRIDOR 130
36"x12"
54
D
3
8
24
12"ø 25
E
Z7-5 600
12"ø 28 (Z7-4) T
REGISTRAR WAITING 102A
5
48"x20" RA (SL) DUCT UP TO 2ND FLOOR
34"x20"
16"ø
23
16"ø
4
2
29
Z7-7 1300
3
Z7-4 1200
ATTENDANCE 103
(Z7-7) T
2
F
T (Z7-3) 23
12"ø
1
7"ø 6
12"ø
23
G
49
38"x20"
ASSISTANT 126A
Z7-8 500
7"ø
7"ø
STORAGE 128 32"x20"
12"ø
6
49
2 M-511
12"ø
BD-7
10"ø
9
T ELECTRICAL (FC-2) 107
38"x20"
Z8-7
FC 3
12"ø
12"ø
STAFF TOILET 108 28"x20" 6
STORAGE 125
M
26
16"ø
BDD
2
14"ø
36"x20"
M
30
TEACHER WORKROOM / LOUNGE 110
FC 2 M 2 M-511 (FC-3)
DUCT SHAFT
28
9
16"ø
38"x20"
12"ø
2
14"ø
12"ø Z8-3 1350
38"x20"
BD-8
T (Z8-3)
41
Z8-4 900
41
M T 22"X28"X18"
32
9
ELECTRICAL ROOM 124
48"x20" SA (SL) DUCT UP TO 2ND FLOOR
ARCHITECT STAMP
14"ø
56
M
H
12"ø
33
9"ø
20"x16"
M
COUNSELOR 12"ø 112
9"ø
STORAGE 120
37
1
16"ø
12"ø
COUNSELOR 111 12"ø DL
24"x16"
24 BOOKSTORE 30 122 31 50 M
(Z7-2) T Z8-6
34
Z8-1 500
BYPASS DAMPER SCHEDULE
42
TESTING MATERIALS 8"ø 123
M
2
1
15
38
9"ø
42
COUNSELOR 119 9"ø 12"ø 8"ø Z8-5 500 8"ø
33
BOOK KEEPER 121
PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK
2
1
COUNSELOR 118
45
28"x16"
37
(Z8-6) T
20"x8"
35
2
1
16"Ø
900
35JN1
1
10"Ø
1350
35JN1
Z8-5
1
REMARKS
10"Ø
600
35JN1
Z8-4
1
10"Ø
2200
2
UP
35JN1
Z8-2
INLET SIZE
CFM
12"Ø
450
35JN1
1
36
AC-8 ZONE DAMPER SCHEDULE CARRIER MODEL NUMBER
12"Ø
650
35JN1
Z11-11
DESIGNATION
650
24"x20"
2
500
26"x20"
1
35JN1
32"x24"
Z7-8
24"x14"
38 12"ø
9"ø
16"øCORRIDOR 131
14"x8"
COUNSELOR 113 T (Z8-4)
10"ø
16"x14"
T (Z8-5)
40
COUNSELOR 114
T (Z8-8)
COUNSELOR 24 ASSISTANT 111A 12"ø
Z8-6 1400
40
COUNSELOR 115 10"ø
14"ø
2
1
40
10"ø
2
1
10"Ø
T (Z8-7)
4
39 Z7-6
16"ø COUNSELOR 116
COUNSELOR 14"ø CONFERENCE ROOM 117 10"ø
2
1
10"Ø
10"ø
18"ø
28"x20"
Z7-4
500
1
36"x20"
35JN1
12"Ø
34"x20"
Z7-3
700
24"x8"
35JN1
32"x20"
Z7-2
KEY NOTES
9
8
AC-11 ZONE DAMPER SCHEDULE
REMARKS
16"Ø
1500
6
19
6
ORIGINAL SCALE
20
0
Z11-1 1600
MECHANICAL FIRST FLOOR
F.S. CLOSET 136A
12
1/8" = 1'-0"
1
1"
JOB NO.: SHEET NUMBER:
M-110
2"
5.5
6
7 6
AC-10 ZONE DAMPER SCHEDULE DESIGNATION
Z10-1
Z10-2
CARRIER MODEL NUMBER
CFM
35JN1
2200
35JN1
INLET SIZE
REMARKS
16X12
1100
BYPASS DAMPER SCHEDULE
1
16"Ø
DESIGNATION
2
1
BD-10
CARRIER MODEL NUMBER
CFM
PASO-18
7,000
INLET SIZE
M-310
5
M-310
J
12"x8" (TYP.5) 1
2
2
1
2
2
1
1
2
Z10-4
35JN1
1200
16"Ø
1
2
Z10-5
35JN1
1850
20X14
1
2
PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK
2
2
2
PROVIDE DUCT TRANSITION ON INLET AND OUTLET SIDE OF DAMPER TO MAIN AND BRANCH DUCTWORK
2
BACK DRAFT DAMPER ST 10-3
PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC
(AC-9) T
H
24"x16"
PH
2
5
14"x12" 3
BD-10
2
12"x8" (TYP.11) 24"x14"
18"x16"
5 TYP. 12"x8"
ACCESS PANEL (TYP.)
5
5 6 Z10-1 2200
9"ø
OPEN
44
Z10-2 1100 12 AV STORAGE 203 M 40"x20"
OFFICE 204 12
12"ø (Z10-2) T
9"ø
M
2
2
28"x10"
13
45
5
14"ø M
CONFERENCE 12"ø ROOM 206 41 9 Z10-5 1850
EF 2
12"ø STAFF TOILET 207
7"ø
LINE OF ROOF ABOVE, SEE A-130
3
3
16
14"x8"
12"x8"
D
12"x8"
EXTERIOR BALCONY
14"ø
14"øCLASSROOM 215
20"x14"
10"ø
24
24
OPEN 46
28"x14"
14"ø
10"ø 36"x12" 24
20"x10" 24
20"x10"
20"x10"
M
47
10"ø 10"ø
8"x4"
24
ST 3-1 10"ø 14"ø
CLASSROOM 214 20"x14"
10"ø
20"x10" 24
21
21
36"x12"
49
PH
9
14"x14" CD-3W, 500 CFM
10
8"x8" CD-2W, 100 CFM
11
16"x16" CD-4W, 600 CFM
12
10"x10" CR, 220 CFM
13
8"x8" CR, 135 CFM
14
14"x14" CR, 420 CFM
15
14"x14" CR, 470 CFM
16
20"x20" CR, 1110 CFM
17
12"X12" C-2W, 300 CFM
18
36"x12" SA (SL) DUCT UTR & DOWN TO FIRST FLOOR
19
36"x12" RA (SL) DUCT THRU CONCRETE WALL, FOR CONTINUATION SEE ROOF PLAN
20
16"x16" CD-4W, 600 CFM
21
18"x18" CR, 840 CFM
22
28"x14" SA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT
23
36"x12" RA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT
24
12"x12" CD-4W 400 CFM
25
14"X14" CD-4W, 530 CFM
26
12"X12" CD-3W, 300 CFM
27
10"X10" CD-4W, 200 CFM
28
14"X14" CR, 500 CFM
29
18"X18" CR, 800 CFM
30
18"X14" SA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT
31
26"X12" RA (SL) DUCT TRANSITION AS REQUIRED UTR TO AC UNIT
32
14"X8" EXHAUST DUCT TRANSITION AS REQUIRED UP TO ROOF TO EXHAUST FAN
ELECTRICAL 219 ST 3-2 34
M
49
CONSULTANT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
33
14"X8" EXHAUST DUCT DOWN TO FIRST FLOOR
34
10"X8" EXHAUST DUCT TRANSITION AS REQUIRED UP TO ROOF TO EXHAUST FAN & DOWN TO FIRST FLOOR
35
10"X6" EXHAUST DUCT UTR TERMINATE WITH ROOF JACK
36
12"X12" CER, 300 CFM
37
10"X10" CER, 200 CFM
38
18"X14" EXHAUST DUCT TRANSITION AS REQUIRED UP TO ROOF TO EXHAUST FAN, AND 14"X8" EXHAUST DUCT DOWN TO 1ST FLR.
39
10"X4" EXHAUST DUCT DOWN TO FIRST FLOOR AND UTR TERMINATE WITH ROOF JACK
40
NOT USE
41
8"Ø EXHAUST DUCT UTR TERMINATE WITH ROOF JACK
42
12"X8" EXHAUST DUCT DOWN TO FIRST FLOOR
43
12"X8" EXHAUST DUCT TRANSITION AS REQUIRED UTR TO EXHAUST FAN & DOWN TO FIRST FLOOR
44
38"X20" SA (SL) DUCT DOWN TO FIRST FLOOR AND UTR
45
38"X20" RA (SL) DUCT DOWN TO FIRST FLOOR AND UTR
46
48"X20" SA (SL) DUCT DOWN TO FIRST FLOOR AND UTR
47
48"X20" RA (SL) DUCT DOWN TO FIRST FLOOR AND UTR
48
REFRIGERATION RL & SL (INSULATED) UP THRU ROOF & DOWN TO FIRST FLOOR
49
6X6 CD-2W, 60 CFM
50
6X6 CR, 60 CFM
NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249 FLS
AC DATE
SS
SCHOOL DISTRICT:
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
2
CANOPY
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
T (AC-3)
26
9"ø
COPYRIGHT: CSDA ARCHITECTS 2011
38
SHEET TITLE
50
WOMEN'S RESTROOM 212 37
10"x4" STORAGE 220 50
20"x10"
ARCHITECT STAMP
2
27
M
M
24
12"x8"
8"ø
36"x12"
23
22
10"ø
ST 4-2
10"ø
10"x4"
24
10"ø
24
8"x8" CD-2W, 150 CFM
10
2
M
10"x4" 24
ST 4-1
36"x12"
24 10"ø
9"ø
23
22
28"x14"
10"ø
22
14"ø
DN
8" "x 2 1
12"ø
14"ø
18"x14"
CLOSET 218 10"x4"
28"x14"
24
A
12"ø
CORRIDOR 217
FIRE-RATED WALL (TYP.)
8
2 16"x6" 16"x6"
M
12"ø
T (AC-4)
36"x12"
21
17
9"ø 23
14"x14" CD-3W, 450 CFM
2
OPEN
DF2
32
12"ø
30
26"x12" 12"ø
ST 5-1
10"ø
31
7
design@csdarchitects.com T:310.821.9200 F:310.821.9201
16"x6"
ELEVATOR
CORRIDOR 210
ST 1-1
T (Z10-5) TYP.
12"ø
17
12"ø
31
8"x4"
ST 5-2
30 ST 1-2
2
16"x10"
25
26"x12"
9"ø
28"x14"
20
25
12"ø
ST 2-1
12"ø
36"x12" 21
33
25
T (AC-5)
20
12"ø
48
6
TITUS LINEAR SUPPLY DIFFUSER MODEL MLR-39TZ, 1" SLOT, 4 SLOTS, 5'-0" LONG, 550 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL 10"x10" CD-3W, 250 CFM
16"x6"
12"ø
36"x12"
20"x10"
ST 2-2
5
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
L1
(AC-6) T
16"x10" 16"x12"
12"x8"
BRIDGE
12"ø 12"ø
9.3
9.5
EF 3
10"x6"
SHEAR WALL
18"x14"
PH
2
36"x12"
JANITOR 209
35
14"ø
16"x14"
20"x10"
CLOSET 221
CLASSROOM 216
26"x12"
14"ø
12"ø
TEXTBOOK STORAGE 213
2
20"x8"
12"x8"
" 12 x " 36
12"x8"
T (AC-1)
29
12"ø
21
12"ø
B
28
29
12"x8"
2
19
24"x8" 30"x10"
24"x8"
20
20
OPEN
ST 9-2
12"x8"
2
PH
T (AC-2)
PH
14"x8"
20"x8" ST 6-1
2
28
M
PH
2 12"x8"
14"x8" (TYP.16)
48"x16"
5
M
OP EN
2
OPEN
E
M
M-310
39
40"x 20" RA DUCT (SL) TRANSITION AS REQUIRED UTR TO AC UNIT
2
16"x14"
5
18
4
K
2
20"x10"
4 1
1 40"x20"
WORK ROOM 208
11
L
2
3
14"ø M 20"x14" M
12"ø 16"ø 12"ø (Z10-4) T
M-310
2 ST 9-1
24"x18"
Z10-4 1200 11
5
M Z10-3 600
F
2
24"x10"
(Z10-3) T
14"ø
24"x10"
12"ø
2
LIBRARY 201
5
48"x16"
M
CIRCULATION DESK
12"ø
24"x8" 10
24"x18"
12"ø
15
40"x20"
8
SHEAR WALL
L2
2 38"x16"
OFFICE 205
24"x20"
OPEN
14
C
4
5
5
44
12"ø
2
5
18"x10" 7"ø 6
7"ø
FIRE-RATED WALL (TYP.)
M
G
2
5
30"x10"
7
2
5
14"ø
TECH STORAGE 20243
DN
40"x 20" SA DUCT(SL) TRANSITION AS REQUIRED UTR TO AC UNIT
2
ST 10-2
16"ø
45
ST 10-1
28"x16"
48
5
30"x20"
48
EXTERIOR BALCONY
22"x18"
SHEAR WALL
2
3
4
30"x10"
40"x20"
12"x8"
(Z10-1) T
40"x20"
2
5
DN
1
TITUS LINEAR RETURN DIFFUSER MODEL MLR-38TZ, 3/4" SLOT, 3 SLOTS, 5'-0" LONG, 375 CFM. INSTALL PER ARMSTRONG CEILING INSTALLATION MANUAL
14"x12"
PROVIDE 36" CLEARANCE FOR ELECTRICAL ENCLOSURE PER NEC
20"x12"
12"Ø
24"x12"
600
2
1
14"x12"
24"x16"
1
35JN1
18"x18" CD-4W, 750 CFM
M-310
REMARKS
22"X28"X18"
1
M-310 4
2 Z10-3
KEY NOTES
9
8
2
14"x12"
MEN'S 36 RESTROOM 211
11
9"ø 8"ø 8"ø
LINE OF ROOF ABOVE, SEE A-310
12"ø 9"ø
MECHANICAL SECOND FLOOR PLAN
36
ORIGINAL SCALE
37
0
SHEAR WALL
JOB NO.: SHEET NUMBER:
21
12
MECHANICAL SECOND FLOOR 1/8" = 1'-0"
1"
1
M-111
2"
6
5.5
M-310
6
2
7
5
9
8
M-310
KEY NOTES
M-310
4 M-310
J
1
38"X20" SA (SL) DUCT DOWN TO SECOND FLOOR
2
38"X20" RA (SL) DUCT DOWN TO SECOND FLOOR
3
48"X20" SA (SL) DUCT DOWN TO SECOND FLOOR
4
48"X20" RA (SL) DUCT DOWN TO SECOND FLOOR
5
36"X12" SA (SL) DUCT DOWN TO SECOND FLOOR
6
36"X12" RA (SL) DUCT THROUGH CONCRETE WALL
7
FLEXIBLE CONNECTION
8
DUCT SUPPORT ON ROOF
9
REFRIGERATION PIPING RL & SL (INSULATED) DOWN THRU ROOF
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
1 M-500
5 M-500
H ARCHITECT STAMP CU 1 M-511 2
AC 10
3 M-510
20 TONS 1 M-511
CU 3
10 P-500 PIPE SUPPORT (TYP.)
9 8
1
5 M-500
CONSULTANT
G
2 5 8 M-500 12 M-500
EF 4
7
AC 8
3 M-510
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
20 TONS 5 8 M-500
CONSULTANT STAMP
ROOF ACCESS 1
8
5 M-500
NOT FOR CONSTRUCTION USE
2
F AC 7
M
AUTHORITY APPROVAL
3 M-510
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
20 TONS
5 M-500 8 7
ROOF JACK
04-112249 FLS
AC DATE
AC 9
3 M-510 20 TONS
SCHOOL DISTRICT:
E 3
L
M-310
M-310
SCHOOL ADDRESS:
AC 6
5 7
8 6
D
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395
7 5 8 M-500
1
SS
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
2 M-510
7.5 TONS
9.3
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
5 M-500
K
KEY PLAN
ROOF JACK
C
9.5 ROOF JACK
AC 11
4 M-510
(25 TONS) CU 1 M-511 1
9 1 M-510
EF 12 M-500 6
AC 2
10
(4 TONS)
B
7 1 M-510 2 M-510
AC 1
5 8 M-500
(4 TONS)
AC 5
(6 TONS)
7
AC 4
2 M-510
3
(6 TONS)
4 ROOF ACCESS
EF 7
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
12 M-500
COPYRIGHT: CSDA ARCHITECTS 2011 2 M-510
AC 3
SHEET TITLE
MECHANICAL ROOF PLAN
(6 TONS)
11
EF 12 M-500 5
A
ORIGINAL SCALE 0
12
MECHANICAL ROOF PLAN 1/8" = 1'-0"
1
2
3
4
5
1
1"
JOB NO.: SHEET NUMBER:
M-130
2"
M
J
H
G
F
L
K
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
E
design@csdarchitects.com T:310.821.9200 F:310.821.9201
AC 9
6"x16"
10"x16" 36"x12"
10"x30" 20"x30"
20"x40"
18"x22"
12"x20" ST 9-1
ARCHITECT STAMP
20"x40"
20"x12"
6"x12"
CONSULTANT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
LIBRARY SECTION - LOOKING EAST - AC-9 SUPPLY 1/8" = 1'-0"
J
H
G
ENTRY/MUSEUM SECTION - AC-6 SUPPLY & RETURN
2
1
1/8" = 1'-0"
E
F
CONSULTANT STAMP
6
7
8
NOT FOR CONSTRUCTION USE
9
AUTHORITY APPROVAL AC 10
AC 8
AC 7
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
AC 6
AC 9
04-112249
ST 10-1
ST 9-2
FLS
AC DATE
SS
40"x20" 16"x48" 14"x24" Z10-1 2200
20"x40" SA TO ZONE 10-2
20"x24"
18"x24" SA TO ZONE 10-3
48"x16"
SCHOOL DISTRICT:
SA TO ZONE 10-4 & 10-5
ACCESS PANEL
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
LIBRARY 201
16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
CORRIDOR 131
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
LIBRARY SECTION - LOOKING EAST - AC10 SUPPLY 1/8" = 1'-0"
J
H
G
F
AC 8
E
AC 7
AC 6
20"x40"
10"x30"
10"x30"
10"x28"
10"x24"
10"x24"
H
G
CU 2
AC 10
3
1/8" = 1'-0"
J
9.3
AC 9
LIBRARY SECTION - LOOKING NORTH - AC-9 RETURN
4
CU 3
F
EF 4
8"x20"
ST 10-2
8"x12"
38"x20"
38"x20" 38"x20" 38"x20"
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
BUILDING SECTIONS ORIGINAL SCALE 0
LIBRARY SECTION - LOOKING EAST - AC10 RETURN 1/8" = 1'-0"
5
LIBRARY SECTION - DUCT SHAFT 1/8" = 1'-0"
1"
JOB NO.: SHEET NUMBER:
6
M-310
2"
(SUPPLY AIR OR RETURN AIR) ROUND OR RECTANGULAR MAIN DUCT. SEE PLAN FOR SIZES.
EXHAUST FAN
PROVIDE CONTINUOUS SEALANT ALL AROUND EXTERIOR
1 1/8" SHT. METAL HANGER STRAPS SECURED FROM STRUCTURE ABOVE. (TYP)
3'-0" MAX. (TYP.)
SECURE DUCT TO (N) CURB
SEAL WATERTIGHT
3/4" x 4" EMBEDMENT HILTI KB-TZ @ 16" O.C.
FLASHING & COUNTER FLASHING
#8 SHEET METAL SCREW
22 GA. GALV. HOOD @ 30% SLOPE
MY A T
ATTACH EXHAUST FAN TO CURB THRU MASTIC WITH #10 SCREWS @ 6" O.C.
TURN ROOFING & DUCT OVER CURB FLASHING & COUNTER FLASHING
DRAW BAND (TYP.)
MVD
PRE-FAB ROOF CURB
FLEX. DUCT. SEE PLAN FOR SIZES.
ROOFING
CEILING WIRE SUPPORT. (TYP.) CEILING DIFFUSER OR REGISTER
ROOF CONSTRUCTION
DUCT - SEE PLAN FOR SIZES
BACK DRAFT DAMPER
EXHAUST FAN DETAIL NOT TO SCALE
CANT STRIP
MY A T
DUCT -SEE MECHANICAL
CEILING
NOTES: 1.
DUCT ADAPTER SHALL BE SAME MANUFACTURER AS CEILING DIFFUSER OR REGISTER.
2.
FLEX DUCT SHALL BE INSTALLED PER SMACNA MANUAL USING DRAWBAND & INSULATION SHALL BE FITTED OVER THE CORE AND SUPPLEMENTARY SECURED WITH A DRAWBAND.
22"
ROOF DECK
SL DUCT
CEILING DIFFUSERS AND REGISTER SHALL MATCH CEILING.
FLEX DUCT TO CD OR CR
12
NOT TO SCALE
EXPANSIVE FOAM INSLULATION WITH CONT. CAULKING ON BOTH SIDES
DUCT THRU ROOF DETAIL
8
NOT TO SCALE
PIPE SEE PLANS FOR SIZE & CONT.
1-1/2 Hr. & 3 Hr. Rated Fire Damper for 1, 2, 3 & 4 Hr. fire partitions.
(TYPICAL)
3x3x1/4"x4"
LEAD FLASH (TYPICAL)
SEALED OFF FLANGE
POTTORFF MODEL FSD-142
NOT TO SCALE
CONSULTANT STAMP FOR CONNECTION TO STRUCTURAL MEMBER SEE 15 STRUCTURAL DRAWING S-12
NOT FOR CONSTRUCTION USE
4" X 4" X 12 GA. VERTICAL HANGER 1
DAMPER BLADE
ROOF DECK
SLEEVE THRU ROOF (TYPICAL)
BARE METAL DECK
NOT TO SCALE
DUCT SUPPORT ON ROOF DETAIL
9
NOT TO SCALE
ALL FIRE DAMPERS SHALL BE LABELED AND LISTED BY CALIFORNIA STATE FIRE MARSHAL AND/OR UNDERWRITERS LABORATORIES. ALL DAMPERS MUST ALSO BE LEAKAGE RATED AND LABLED UNDER UNDERWRITER LABORATORIES STD. 555S. WITH METAL SEALS ALLOWING NO MORE THAN 10 CFM/SQ.FT. AT 1" W.G. TO 250째 F FOR A FULL 30 MIN. CAN BE MOTOR OPERATED. TORQUE REQ'D. TO MAINTAIN LEAKAGE RATE NOT TO EXCEED 0 LBS. TORQUE. DAMPERS SHALL BE INSTALLED PER MANUFACTURERS INSTALLATION INSTRUCTIONS AND/OR STATE FIRE MARSHAL LISTING NO. 03225. POTTORFF COMPANY, INC. (NO RUBBER SEALS ALLOWED) (LISTING NO.03225:0368:110 AND 03230:0368:111) PROVIDE NON STALL SHUNT MOTOR , 23 VA. MAXIMUM. OR APPROVED EQUAL.
FOR CONNECTION TO STRUCTURAL MEMBER SEE STRUCTURAL DETAIL
PIPE CLAMP 5'-0" MAX. TO STRUCTURAL SUPPORTING MEMBER
VERTICAL RISER
COMBINATION FIRE/SMOKE DAMPER OPENING TO BE SINGLE HEADER FRAMING FOR WOOD OR STEEL. WOOD FRAMED OPENINGS MUST BE LINED WITH MINIMUM 5/8" TYPE X GYP. BOARD. LINING NOT REQUIRED AT STEEL STUD, CONCRETE, OR MASONRY. SUGGESTED CLEARANCE BETWEEN SLEEVE AND OPENING 1/8" FOR EACH 12" DAMPER WIDTH AND HEIGHT FOR EXPANSION. DAMPER TO BE HELD IN PLACE BY RETAINING ANGLES ATTACHED TO SLEEVE ON BOTH SIDES OF PARTITION, AND AROUND ENTIRE PERIMETER OF THE SLEEVE. ANGLES TO BE MIN. 16 GA. 1-1/2" X 1-1/2" OR LARGER AS REQUIRED TO PROVIDE A MIN. 1" OVERLAP OF THE OPENING. ANGLES MAY BE MITERED, BUTTED OR OVERLAPPED AT THE CORNERS. ATTACH ANGLES TO THE SLEEVE (NOT THE PARTITION) WITH SHEET METAL SCREWS, BOLTS OR WELDS AS PER MANUFACTURERS INSTRUCTIONS. CONNECT DUCT TO SLEEVE WITH "S" TYPE SLIP CONNECTIONS. DO NOT USE MECHANICAL FASTENERS.
PIPE CHASE
NEOPRENE PAD (TYP)
VERTICAL RISER PIPE CLAMP SPACER AS REQUIRED TO LIFT CLAMP ABOVE SLEEVE.
DUCT
1
3/ " 8
MACHINE BOLT 2-1/2"x12 GAUGE SHEET METAL STRAP
FLS
SS
DUCT
SOUND TRAP
SCHOOL DISTRICT:
7 M500
7 M500
5'-0" 6" MAX
6" MAX
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395
1 MIN. 2 MAX.
SCHOOL ADDRESS:
3"X3"X14 GA. "L" BRACING
CL OF BOLTS EQUAL CL OF ANGLE EQ.
NEOPRENE PAD (TYP)
5
15 S-12
3"X3"X14 GA. TRANSVERSE BRACE
W.P.
04-112249
INSULATION WHERE REQ'D
3"X3"X16 GA. VERTICAL HANGER
3/ " MACHINE 8 BOLT
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
AC DATE
LONGITUDINAL BRACE (SHOWN DOTTED)
SOUNDTRAP HANGER DETAIL
DUCT SIZE
PIPE THRU ROOF DETAIL DETAIL
1 MIN. 2 MAX.
LONGITUDINAL BRACE ONE EA. SIDE OF DUCT (SHOWN DOTTED) 6'-0" SPACING
3" X 3" X 16 GA.
22 S-12
AUTHORITY APPROVAL
1 1 MIN. 2 MAX.
FOR CONNECTION TO ROOF SEE STRUCTURAL DETAIL
FIRE/SMOKE DAMPER SPECIFICATIONS:
CONSULTANT
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
FLASHING COMPOUND
BLADE BRACKET
1
CREATIVE DESIGN
L 2X2X1/8" VERTICAL ANGLE
FLASHING & COUNTER FLASHING (TYPICAL)
ACCESS DOOR
DUCT THRU WALL DETAIL
1/4"THRU BOLT
1/4"
2.7" MAX.
3.750
5 M-500
UNISTRUT 1 5/8 CHANNEL SERIES P3000 WELDED TO VERTICAL ANGLE
1 1/2" X 1 1/2" X 1/8" ANGLE IRON CROSSBRACE. WELD TO VERTICAL ANGLE
DAMPER FRAME
ROOFING
#8 SHEET METAL SCREWS @ 12" O.C. ON BOT. & SIDES. MAKE WATERTIGHT W/ ELASTIC SEALANT.
TYP. (SL) DUCT
24 GA. GALV. STEEL PIPE FLASHING
FLASHING & COUNTER FLASHING
DUCT SUPPORT, SEE
2'-6"(MAX)
LEAD COLLAR
4
POUR IN PLACE CONCRETE
ARCHITECT STAMP
1/4"PL. CAP
42" O.C.
AIR-FLOW
design@csdarchitects.com T:310.821.9200 F:310.821.9201
NEW ROOFING
SQUARE TO ROUND ADAPTER. SECURED TO DIFFUSER NECK WITH SHEET METAL SCREWS. (SIZE AS REQ'D.)
3.
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
NOT TO SCALE
2
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
DUCT SIZE NOTE: SPACE HANGERS AND BRACES IN ACCORDANCE WITH MECHANICAL CODE AND SMACNA GUIDELINES. BRACE SPACING SHALL NOT EXCEED 20'-0"
PIPE SLEEVE (WHERE OCCURS)
STIFFENING REQUIREMENTS - THREADED ROD OPA-0485
HIGHEST OPERABLE PART OF THERMOSTAT OR CONTROLS AND TOP OF OUTLETS OR SWITCHES
13
46" MAX SIDE-APPROACH 44" MAX FRONT-APPROACH AT WORK STATION
HIGHEST OPERABLE PART OF THERMOSTAT OR CONTROLS AND TOP OF OUTLETS OR SWITCHES
48" MAX.
24" MAX.
BOTTOM OF OUTLETS OR SWITCHES
NOT TO SCALE
10
STANDARD WEIGHT STEEL PIPE SLEEVE OF SIZE TO FIT PIPE AND INSULATION.
SEAL WITH DOWCORNING 700, UL QMFZ2, SMOKE TIGHT MANNER
PIPE AND INSULATION TO BE CENTERED IN SLEEVE - DO NOT SUPPORT PIPE FROM SLEEVE. FINISHED WALL SURFACE
FOR CONNECTION TO STRUCTURAL MEMBER SEE STRUCTURAL DETAIL
FINISHED ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING.
INTERIOR WALL
1" SEALING AND ANCHORING COLLAR SEAL SLEEVE WITH TIGHTLY PACKED SILICON COMPOUND.
1/4" 1"
34" MAX.
EXTERIOR WALL
TIGHTEN TILL SNUG
15 S-12 MAXIMUM 6" (152 mm) 1
1/2" CLEAR MAX.
4" X 4" X 12 GA. VERTICAL HANGER HORIZONTAL BRACE
EQ.
LONGITUDINAL BRACE ONE EA. SIDE OF DUCT (SHOWN DOTTED)
1 MIN. 2 MAX.
3" X 3" X 16 GA.
OUTSIDE
2"MAXIMUM (51 mm)
2"MINIMUM (51 mm)
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
RC-1 ROD STIFFENER (1/2" ROD DIAMETER) (13 mm)
INSULATION WHERE REQ'D
CL OF BOLTS EQUAL CL OF ANGLE EQ.
2"MAXIMUM (51 mm)
MAXIMUM SPACING BETWEEN ROD STIFFNER CLIPS DIM. "B"
TIGHTEN TILL SNUG DUCT
12 ga. CHANNEL 1-5/8"X 1-5/8" MAXIMUM LENGTH 9'-0" (2.7 m)
DUCT SIZE THREADED ROD DIAMETER 1/2"(13)
DETAILS
DIM."A" DIM."B" MAXIMUM MAXIMUM ROD LENGTH SPACING WITHOUT BETWEEN STIFFENER ROD STIFFENRES 22"(559)
18"(457)
NOTICE:ROD STIFFENING REQUIRED ONLY FOR HANGER RODS TO WHICH SEISMIC BRACING HAS BEEN INSTALLED.
ORIGINAL SCALE 0
FINISHED FLOOR
THERMOSTAT MOUNTING HEIGHT DETAIL NOT TO SCALE
PIPE SLEEVE THRU WALL DETAIL 14
COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
ROD STIFFENER CHART
#10 SELF-TAPPING SHEET METAL DUCT SIZE SCREWS EQUALLY SPACED (18" O.C MAXIMUM.) NOTE: SPACE HANGERS AND BRACES IN ACCORDANCE WITH MECHANICAL CODE AND SMACNA GUIDELINES. BRACE SPACING SHALL NOT EXCEED 20'-0"
FINISHED WALL SURFACE
SEAL WATERTIGHT
6
FOR CONNECTION TO STRUCTURAL MEMBER SEE STRUCTURAL 18 DETAIL S-12
TRANSVERSE BRACE 3" X 3" X 16 GA.
COAT EXTERIOR SURFACES WITH TAR COMPOUND.
15" MIN.
NOT TO SCALE
TERMINATE SLEEVE FLUSH WITH FINISHED WALL SURFACES.
2"
FINISHED FLOOR
SINGLE HANGER BRACING FOR ROUND DUCT DETAIL
10' MAX. TO STRUCTURAL SUPPORTING MEMBER
NOT TO SCALE
PIPE SUPPORT - VERTICAL RISER DETAIL
TYPICAL 4 SIDES
COMBINATION FIRE SMOKE DAMPER DETAIL
MAXIMUM 6" (152 mm)
NOT TO SCALE
11
CENTER BRACING FOR RECTANGULAR DUCT DETAIL NOT TO SCALE
7
PIPE SUPPORT DETAIL NOT TO SCALE
3
1"
JOB NO.: SHEET NUMBER:
M-500
2"
3
4
5
6
7
FORM NO.: ________
8
1
WELDING DETAIL
80.375 TOP O.D.
2-6
135.375 TOP O.D.
1.250
1.424
40.688 TOP O.D.
E
70.875 TOP O.D. 37.188 I.D.
1.000 TYP.
ISOLATOR
5.000 TYP x 8
SECURE MICROHOLD (6) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)
69.438
FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL 9 DETAIL S-8
82.875 BOTTOM O.D.
62.438 TYP x 2
18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE
C:sers\jdetweiler\Desktop\Calculations\Isocurbs\HE4F\0403-HE4FD\0403-HE4FD
10"
137.875 BOTTOM O.D.
C
16 GA MICROHOLD ATTACH TO UNIT USING (6) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)
FULL PERIMETER WOOD NAILER
OPA# 0070 14 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT ISOCURB
14 GA CURB
DETAIL
NUMBER OF SPRING PER SHORT SIDE = 2
THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES
MicroMetl Corporation
C
C
9 S-8
D
MICROHOLD
WELDING DETAIL
DETAIL
SECURE MICROHOLD (4) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)
73.375 BASE O.D.
" 10
43.188 BASE O.D.
5.000 TYP x 4
ARCHITECT STAMP
16 GA MICROHOLD ATTACH TO UNIT USING (4) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)
18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE
C
FULL PERIMETER WOOD NAILER
16 GA CURB B
B
ISOCURB DETAIL THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES
NUMBER OF SPRING PER LONG SIDE = 2
MicroMetl Corporation
PAGE 1 of 2
B
CONSULTANT
STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB
0403-372D-08B 18" TALL 0403-372D 21" TALL 0403-372D-14B 24" TALL
CREATIVE DESIGN
PAGE 1 of 2
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
Indianapolis, IN. : (800) 662-4822 Sparks, NV. (800) 884-4662
Sparks, NV. (800) 884-4662
CONSULTANT STAMP
Longview, TX. (903) 248-4800
Longview, TX. (903) 248-4800 A
WEIGHT: 670/700/730 DRAWN BY: JD
1.000 TYP.
ISOLATOR
16 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT
Indianapolis, IN. : (800) 662-4822
DATE: 01/17/2011
MEETS SEISMIC REQUIREMENTS FOR 2010 CBC & 2009 IBC
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 2 3 4 1
5
6
7
WEIGHT: 325/340/355 LBS. DRAWN BY: JD
PRINTED: 11/29/2011
A
2.920
OPA# 0070
STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB
0403-HE4FD-08B 18" TALL 0403-HE4FD 21" TALL 0403-HE4FD-14B 24" TALL
13.875
DATE: 01/01/2011 MEETS SEISMIC
PRINTED: 8/10/2011
B
NUMBER OF SPRING PER LONG SIDE = 5
FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL DETAIL
design@csdarchitects.com T:310.821.9200 F:310.821.9201
1.298
LY P P SU
DETAIL
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
1/8
D
MICROHOLD
WELDING DETAIL
SEAM WELD TOP AND SIDES (TYP. 4 CORNERS)
6.000
32.063
RET URN
20.250
D
2-6
1.250
2.983
22.188
8
4.684 13.625
25.938
0.134
67.375 I.D.
27.875
RN U T RE
7
WELDING DETAIL
1/8
LY 63.875 P P SU
6
1.000
4.684
131.875 I.D.
D
5
10 GA SUPPORT
6.000 SEAM WELD TOP AND SIDES (TYP. 4 CORNERS)
76.875 I.D.
4
.750 Created: 1/18/2011 9:14:11 AM
E
3
FORM NO.: ________
10 GA SUPPORT 0.134
2
Created: 1/2/2011 7:33:37 AM
2
T:\Solidwrk\ISOCURB\372\0403-372D\0403-372D
1
REQUIREMENTS FOR 2010 CBC & 2009 IBC THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 2 3 4 1
8
5
6
7
NOT FOR CONSTRUCTION USE
8
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
3
2
3
4
5
6
FORM NO.: ________
7
8
1
WELDING DETAIL
Created: 1/18/2011 10:14:11 AM
SEAM WELD TOP AND SIDES (TYP. 4 CORNERS) 1.250
4.684
151.625 TOP O.D. 148.125 I.D.
1.424
E
53.500 TOP O.D. 50.000 I.D.
2.983
5.000 TYP x 8
22.188
81.750 TOP O.D. 78.250 I.D.
154.125 BOTTOM O.D. 48.708 TYP x 2
FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL 9 DETAIL S-8
82.875 BOTTOM O.D.
18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE
14 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT ISOCURB
B
NUMBER OF SPRING PER LONG SIDE = 5
MicroMetl Corporation
14 GA CURB
DETAIL
NUMBER OF SPRING PER SHORT SIDE = 2
THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES
FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL DETAIL
C
C
9 S-8
40.063 2.919 1.000 TYP.
ISOLATOR
D
MICROHOLD
WELDING DETAIL
16 GA MICROHOLD ATTACH TO UNIT USING (6) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)
" 10
56.000 BASE O.D. 18" MIN HEIGHT, 24" MAX HEIGHT PER ROOF SLOPE
16 GA CURB ISOCURB
B
NUMBER OF SPRING PER LONG SIDE = 4
MicroMetl Corporation
PAGE 1 of 2
Longview, TX. (903) 248-4800 A
PRINTED: 8/10/2011
DATE: 01/17/2011
MEETS SEISMIC REQUIREMENTS FOR 2010 CBC & 2009 IBC
5
6
7
8
WEIGHT: xxxx/xxxx/xxxx DRAWN BY: JD
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
DETAIL THE STANDARD PRODUCT DOES NOT INCLUDE THROUGH THE SIDE SERVICE HOLES 0403-972D-08B 18" TALL 0403-972D 21" TALL 0403-972D-14B 24" TALL
C
B
STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB PAGE 1 of 2
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
Indianapolis, IN. : (800) 662-4822
Longview, TX. (903) 248-4800
SCHOOL ADDRESS:
KEY PLAN
DETAIL
16 GA STIFFENER 1-1/2" x 7" x BASE HEIGHT
B
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
SECURE MICROHOLD (6) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)
84.250 BASE O.D.
5.000 TYP
OPA# 0070
Sparks, NV. (800) 884-4662
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 1 2 3 4
1.172
LY P P SU
Sparks, NV. (800) 884-4662
WEIGHT: 820/850/890 DRAWN BY: JD
4.684
FULL PERIMETER WOOD NAILER
Indianapolis, IN. : (800) 662-4822
A
1.250
15.688
STRUCTURALLY CALCULATED VIBRATION ISOLATION CURB
0403-HE6FD-08B 18" TALL 0403-HE6FD 21" TALL 0403-HE6FD-14B 24" TALL
RET URN
DETAIL
FULL PERIMETER WOOD NAILER
OPA# 0070
SEAM WELD TOP AND SIDES (TYP. 4 CORNERS)
1/8
MICROHOLD
16 GA MICROHOLD ATTACH TO UNIT USING (5) #12 x 1-1/2" TEK SCREWS (TYP. EACH HOLD)
" 10
.750
D
SECURE MICROHOLD (5) #10 x 1/2" TEK SCREWS (TYP. EACH HOLD)
N 69.438 R U RET C
D
WELDING DETAIL
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
31.375
C:sers\jdetweiler\Desktop\Calculations\Isocurbs\HE6F\0403-HE6FD\0403-HE6FD
LY 63.875 P P SU
1.000 TYP.
2-6
COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
DATE: 01/07/2011
MEETS SEISMIC REQUIREMENTS FOR 2010 CBC & 2009 IBC
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MICROMETL CORPORATION. ANY REPRODUCTION IN PART OR WHOLE WITHOUT THE WRITTEN PERMISSION OF MICROMETL CORPORATION. IS PROHIBITED. ENGS03A 1 2 3 4
5
6
7
8
VIBRATION ISOLATOR DETAILS ORIGINAL SCALE 0
VIBRATION ISOLATOR DETAIL (AC-11) NOT TO SCALE
4
SS
SCHOOL DISTRICT:
8
6.000
15.313
ISOLATOR
7
WELDING DETAIL
1/8
25.938
6
10 GA SUPPORT
27.875
D
5
0.134
6.000
E
76.875 I.D.
4
.750
2-6
80.375 TOP O.D.
3
FORM NO.: ________
10 GA SUPPORT 0.134
2
FLS
AC DATE
PRINTED: 8/10/2011
1
1
NOT TO SCALE
Created: 1/7/2011 10:50:04 AM
NOT TO SCALE
04-112249
VIBRATION ISOLATOR DETAIL (AC-1 & AC-2)
C:sers\jdetweiler\Desktop\Calculations\Isocurbs\972\0403-972\0403-972
VIBRATION ISOLATOR DETAIL (AC-7 THRU AC-10)
VIBRATION ISOLATOR DETAIL (AC-3 THRU AC-6) NOT TO SCALE
2
1"
JOB NO.: SHEET NUMBER:
M-510
2"
15 1-3/4 TYP.
ISOLATOR/RESTRAINTS ARE OSHPD PRE-APPROVED #OPA-0029
12
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
6
5
1/2 x 1-1/2" LONG STUD
2-1/2
2-1/2
10 7-3/4
1-1/8 ARCHITECT STAMP
1/4"
1/4"
RIBBED NEOPRENE PAD
7-1/4" OPER HT. VERTICAL LIMIT STOP CONSULTANT
5
5
5
FOR ANCHORAGE TO ROOF STRUCTURE, SEE STRUCTURAL DETAIL DRAWING
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
10 S-8
CONSULTANT STAMP
NOT FOR CONSTRUCTION USE
M.W. SAUSSE' & CO., INC. VALENCIA, CALIFORNIA 91355
V IBREX TYPE RMLS-EQ-3
JOB NAME: CUST.: CUST. P.O.: MECH. ENGR .: MARK:
--
REVISIONS:
DRN:
DATE: DEC, 19, 2011 SHEET NO.:
-CONDENSING UNIT
A: B: C: D:
JO
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249
E1
VIBRATION ISOLATOR DETAIL (CU-1, CU-2 & CU-3) NOT TO SCALE
FLS
AC DATE
SS
1
SCHOOL DISTRICT:
FC -
WALL BRACKET BY MANUFACTURER
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
#8 METAL SCREWS, 3/4 "LONG, (2) EACH SIDE. SCREWS MUST BE INSERTED INTO METAL STUDS.
16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
FC UNIT MOUNTING DETAIL (FC-1, FC-2 & FC-3) NOT TO SCALE
2
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
VIBRATION ISOLATOR DETAILS ORIGINAL SCALE 0
1"
JOB NO.: SHEET NUMBER:
M-511
2"
AC Unit w/Power Exhaust Typical of (6) - AC-1, AC-2, AC-3, AC-4, AC-5, AC-6 & AC-9 CONTROL PANEL #
5A Ckt Bkr
LABEL DESCRIPTION:
AC - FILTER STATUS - DI
TB-PWR
TCP-
H
Panel Rm Location:
G
AC - SUPPLY AIR TEMPERATURE - AI
3
2
Unit Power
N
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
TX-1
TX PROVIDED BY SUNBELT CONTROLS
50va
NEMA 1 12HX12W SCREW COVER
design@csdarchitects.com T:310.821.9200 F:310.821.9201
X1+
X1-
GAS
REC
TB-1 24VAC Power to below
OSA
TB-PWR
N.C.
HI
SF
DX
LO
10A
H N G
ON
1
50VA
24VAC
R
AC - SUPPLY FAN STATUS - DI
AC - SUPPLY FAN START/STOP - DO AC - COOLING STAGE-1 ENABLE - DO AC - COOLING STAGE-2 ENABLE - DO AC- HEATING STAGE-1 ENABLE - DO AC - HEATING STAGE-2 ENABLE - DO
G Y1
OFF
Y2 W1 W2
R
AUTOMATEDLOGIC
VA
20
CORPORATION
Gnd 24Vac Lstat
PROGRAM/ FB NAME(S)
Rx
Net +
Tx
IN-1
Thermistor/dry contact 0-5Vdc On
1
Rnet
MSTP ARC156
9600
Inputs: 5V Max
76.8k
Poly tubing from space static tip to AC unit mfr power exhaust transducer, provide by unit mfr. (Typical)
Gnd
Terminal Setting
Point Addr. & Type
IN-2 Gnd
IN-3 AO-1 Gnd
Universal Input Verification Checklist:
AO-01
DO-3
DO-1
Power for D.O.'s
BUSS
®
BACnet
Room Temp Sensor T-STAT LOCKING COVER
COOLER
AC/RTU - HEATING STAGE-2 ENABLE - DO AC/RTU - HEATING STAGE-1 ENABLE - DO
DO-3
DO-04
DO-2
AUTOMATED LOGIC
Y1 3/8" Pneumatic Tubing
AC/RTU - SUPPLY FAN START/STOP - DO
G
24VAC POWER
DO-1 BUSS
CONSULTANT
RSPLUS
RA
Y2
AC/RTU - COOLING STAGE-1 ENABLE - DO
DO-03
OCCUPIED
W1
DO-4
DO-05
MANUAL ON
W2
DO-5
AC/RTU - COOLING STAGE-2 ENABLE - DO
UI-04
SA
WARMER
Point Addr. & Type
Off
Offset (if appl)
Actual Fld. Measured Value
Input Value Reading
Date Verified
DO-4
DO-2
CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
GND AO-1
DI-03
Gnd IN-4 IN-5 LED
Note: Economizer w/Power Exhaust
DO-5
Class 2 24 Vac, 50-60 Hz 20VA, 0.83A 24Vdc, 0.2A, 5W Use Copper Conductors Only
IN-4
AI-02
IN-3 Gnd
AC/RTU - FILTER STATUS - DI
By Tech Initials
DI-01
On
AC/RTU - SUPPLY AIR TEMPERATURE - AI
IN-2 Gnd
Digital Date Verified
IN-1 Gnd
N.O.
Digital Output Verification Checklist: By Tech Initials
AC/RTU - SUPPLY FAN STATUS - DI
Check’d
Point Addr. & Input #
Room Temp Sensor
CONTROLLER
Gnd
LED
AUTOMATED LOGIC
ZN551
CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
IN-5
3
38.4k
MSTP Baud
Gnd
100
75
50
25
0
Rnet
Date Verified
By Tech Initials
Analog Out %
Gnd Rnet+ Rnet+12V
MANUAL ON
2
19.2k
IN-1
Grn Wht Blk Red
OCCUPIED
1
3
2 3
COOLER
Gnd Rnet+ Rnet+12V
2
2
Communications Selection
+12V
1 2 3 4
4
3
Gnd Gnd Rnet + Rnet -
WARMER
ARCHITECT STAMP
4
Rnet+
Analog Output Verification Checklist:
N.C.
EA
Thermistor/dry contact 0-5Vdc
IN-2
+12V Rnet-
1
5 6
Tens
4
5 6 4
CR 2032
Sense
2 3
4
0 1
9 0 1
9
5 6
2 3
2 3
7 8
24 Vac Pwr
+ Err
Ones
5 6 4
0 1 7 8
Jumper: Gain1
Run
7 8
7 8
.equipment
Term
Rnet
Format
Batt
-
9 0 1
ZN551
BT485
W2
C
Ground
Net Shield
OR
T-STAT LOCKING COVER
Bias
CMnet
ADDRESS
9
Comm from previous & to next control module (See network riser diagram)
CONTROL MODULE
Arc156
Net + Net Shield
Y2 W1
O N
ALC Controller Checklist:
Wire to factory provided power exhaust transducer
Units with factory provided and controlled power exhaust with vfd.
G Y1
R
CREATIVE DESIGN
DO-02
UI-05
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
DO-01 DP-TIP-S HIGH
CONSULTANT STAMP
AH Space Static Tip NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
AC RTU MODULE DETAIL NOT TO SCALE
AC RTU CONTROL SCHEMATIC
2
NOT TO SCALE
04-112249
1
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
NEMA 1 12HX12W SCREW COVER AC - FILTER STATUS - DI
CONTROL PANEL #
5A Ckt Bkr
LABEL DESCRIPTION:
H
TCP-
N
Panel Rm Location:
G
Unit Power
3
TB-PWR 10A
50va
50VA
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
GAS
X1+
X1-
OFF
REC
OSA
TB-1 24VAC Power to below
N.C.
HI
Bias
Rx
Net +
Tx
SF
DX
LO
CS
CMnet
Net -
Thermistor/dry contact 0-5Vdc
W1
IN-2 Thermistor/dry contact 0-5Vdc
+12V
2
2 3
2 3
Gnd
AUTOMATEDLOGIC
ALC Controller Checklist:
20
CORPORATION
Comm from previous & to next control module (See network riser diagram)
CONTROL MODULE
Arc156
Net + Net Shield
ADDRESS
Communications Selection
Rnet
MSTP
VA
19.2k
38.4k
76.8k
IN-1 Inputs: 5V Max
Gnd
MSTP Baud
IN-2 Gnd
WIRE TO FACTORY PROVIDED POWER EXHAUST TRANDUCER
Gnd
IN-3 AO-1 Gnd
PROGRAM/ FB NAME(S)
CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
ZN551 CONTROLLER
DO-5
Class 2 24 Vac, 50-60 Hz 20VA, 0.83A 24Vdc, 0.2A, 5W Use Copper Conductors Only
DO-4
DO-2
IN-4
ZN551
IN-5 LED
.equipment
EA
DO-3
Gnd
BT485
C
UNIT WITH FACTORY PROVIDED AND CONTROLLED POWER EXHAUST
ARC156
9600
+12V
Gnd 24Vac
O N
1
Rnet -
W2
4
3
3
4
Gnd
Rnet +
KEY PLAN
W1
On
RnetRnet+
R
Y2
AC - HEATING STAGE-1 ENABLE - DO
IN-1
2
5 6
Tens
CR 2032
Sense
1
4
4
5 6 4
0 1
0 1
Ones
9
9
5 6
2 3
2 3
7 8
4
Err 0 1
0 1 7 8
Y2
+
Y1
AC - COOLING STAGE-2 ENABLE - DO
Pwr Run
9
9
5 6
7 8
Y1
24 Vac
Batt
-
7 8
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
G
AC - COOLING STAGE-1 ENABLE - DO
Format
Jumper: Gain1
R
AC - SUPPLY FAN START/STOP - DO
G
Rnet
Ground
Shield
24VAC
R
AC - SUPPLY FAN STATUS - DI
2 Lstat
16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
H N G
ON
TX-1
AC - SUPPLY AIR TEMPERATURE - AI
5
TB-PWR
SS
SCHOOL DISTRICT:
VVT AC Unit w/Power Exhaust Typical of (4) - AC-7, AC-8, AC-10 & AC-11
VVT AC Unit w/Power Exhaust Typical of (4) - AC-7, AC-8, AC-10 & AC-11
FLS
AC DATE
DO-1 CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
Power for D.O.'s
BACnet
N.C.
BUSS
®
OR
Term
2 3
IN-3 Gnd
Offset (if appl)
Actual Fld. Measured Value
Input Value Reading
Date Verified
By Tech Initials
Point Addr. & Type
AC - SUPPLY AIR TEMPERATURE - AI
On
IN-2 Gnd
5
AC - RETURN AIR TEMPERATURE - AI AC - FILTER STATUS - DI
Gnd IN-4 IN-5 LED
AC - HEATING STAGE-1 ENABLE - DO DO-4
AC - COOLING STAGE-2 ENABLE - DO DO-05
DO-3
DO-04
DO-2
AC - COOLING STAGE-1 ENABLE - DO AC - SUPPLY FAN START/STOP - DO
DO-1 BUSS
24VAC
2
3
W1 Y2 Y1 LO
G R
DO-02 AC - RETURN AIR TEMPERATURE - AI
UI-05
81
24VAC+
1
DO-5
DI-03
UI-04
AC - BYPASS DAMPER CONTROL - AO HIGH
AC Space Static Tip
AI-02
DO-03 4
GND AO-1
24VAC-
Digital Off
AC - SUPPLY FAN STATUS - DI
DI-01
1/4" Pneumatic Tubing
Digital Output Verification Checklist: Date Verified
IN-1 Gnd
AO-01
By Tech Initials
1
AC - DUCT STATIC PRESSURE - AI
Check’d
Point Addr. & Input #
Universal Input Verification Checklist:
Note: Economizer w/Power Exhaust
Terminal Setting
100
75
50
25
0
Date Verified
By Tech Initials
Rnet
Point Addr. & Type
N.O.
Analog Out %
81
Gnd Rnet+ Rnet+12V
Analog Output Verification Checklist:
DO-01
4
1
AC - DUCT STATIC PRESSURE - AI
24VAC+
+ S
24VAC-
-
HI
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
RA
SA
EMS DIAGRAMS ORIGINAL SCALE 0
VVT AC UNIT MODULE DETAIL NOT TO SCALE
4
VVT AC UNIT NOT TO SCALE
3
1"
JOB NO.: SHEET NUMBER:
M-520
2"
Exhaust Fans
5A Ckt Bkr
LABEL DESCRIPTION:
To ZN-Card controller (HI & LO)
TB-PWR
TCP-EF
H
Panel Rm Location:
G
POWER CIRCUIT FROM:
N
PNL #:
TX-1
TX PROVIDED BY SUNBELT CONTROLS
X1+
X1-
VOLT: TB-1 24VAC Power to below
Zone Box Typical of: AC-7 - (8) Zones AC-8 - (8) Zones AC-10 - (5) Zones AC-11 - (11) Zones
H N G
ON
50VA R
OFF
20
CORPORATION Arc156
Red Stripe =
Gnd 24Vac
FILTER
PROGRAM/ FB NAME(S)
.equipment
Lstat
OR
Bias
Rx
Net +
Tx
CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
Rnet
Rnet LogiStat
Format
Ground
Net -
CR 2032
Made in USA
IN-1 Thermistor/dry contact 0-5Vdc
IN-2
Sense +12V
3
2
O N
LStat =
2 3
Communications Selection
or IN-3 =
Rnet
MSTP ARC156
2 3
+12V
9600
19.2k
38.4k
76.8k
IN-1 Inputs: 5V Max
ARC156
Batt
Gnd
Gnd
MSTP
CR2032
IN-3 AO-1
10's
MSTP Baud
BUSS
On
®
2 3
19.2k
38.4k
76.8k
CMnet
4 3 2
Local
24V ac
Ground
Shield
Net +
BT485
Access +12V
Gnd
Rnet -
CCW
Rnet +
IN-4
Power
Rnet
Motor CW
LED
IN-3
Rnet+ Gnd
Conductors Only
Port Gnd
+12V Rnet-
Power
1
26Vdc, 0.1A, 3W Use Copper
LStat/ZASF
Inputs
Sense
Run
O N
Tx
Net -
0-5V, therm, dry
IN-1
Gnd
DO-3
AO-1
DO-2
Rx
Therm, dry
Gnd
Analog
Inputs 1 & 2
IN-2
5mA Max
Error
14VA, 0.58A
Inputs 3 & 4
Gnd
Power for D.O.s
Class 2 24Vac, 50-60 Hz
LogiStat/IN3 & 4 ZASF
1A Max
DO-1
BUS
1
BACnet AO: 0-10 Vdc
3 2
Outputs 24V Max,
9 0 1
4
9600
Point Addr. & Type
Off
On
Date Verified
By Tech Initials
Offset (if appl)
Actual Fld. Measured Value
Input Value Reading
Date Verified
By Tech Initials
Power for D.O.'s
BACnet
5 6
Check’d
2 3
4 6
4
Point Addr. & Input #
7
51
DO-1 BUSS
AI-02
8
6
5
9
Output
EF-x - EXHAUST FAN START/STOP - DO
3
DO-1
®
DO-02
7
2
0
DO-2
CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
DO-2
AI-01
1
8
5 6
IN-5
1's
DO-3
IN-4
5
9
ZN341v+
DO-4
Gnd
LED
Digital
CONTROLLER
DO-5
Class 2 24 Vac, 50-60 Hz 20VA, 0.83A 24Vdc, 0.2A, 5W Use Copper Conductors Only
4
4
Digital Output Verification Checklist:
ZN551
3
0
-
+ CAUTION : To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
2
1
Gnd
9 0 1
IN-2
Input Output Verification Checklist:
CAUTION: The modules are Class 2 devices (less than 30 VAC). Take appropriate isolation measures when mounting a module in a control panel where Class 1 devices or wiring are present.
MSTP Baud
Gnd
IN-2 Gnd
ARCHITECT STAMP
Format Short pins
4
3
1
IN-1 Gnd
LO
0-5Vdc Therm/dry
4
Gnd
Rnet
IN-1
On
Rnet-
Gnd
Rnet -
Green Stripe =
0-5Vdc Therm/dry
Thermistor/dry contact 0-5Vdc
Rnet+
Rnet +
CAUTION : This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
U.S. Patent No. 6,715,690 B2
2
5 6
Tens
4
5 6 4
0 1
5 6
2 3
2 3 9
9 0 1
Ones
5 6 4
0 1 7 8
IN-2
Pwr + Err
9
7 8
4
-
7 8 9 0 1
Gnd Rnet+ Rnet+12V
24 Vac
Batt
Run
Shield
7 8
Jumper: Gain1
1
Term
EF-x - EXHAUST FAN STATUS - DI
To VVT Box Flow Sensing Device (LO & HI)
Flow Low
ZN220
BT485
CONSULTANT
DO-01 6
7 8
4
3
2
1
1
2
3
1
2 DISCONNECT SWITCH
1 2 3 4
1
HI
High
CMnet
Net + Net Shield
ADDRESS
Install Air Filter (shipped loose)
7 8
CMnet from PREVIOUS & to NEXT ALC CONTROL MODULE (SEE NETWORK RISER DIAGRAM)
CONTROL MODULE
VA
design@csdarchitects.com T:310.821.9200 F:310.821.9201
NEMA 1 12HX12W SCREW COVER
TB-PWR
ALC Controller Checklist:
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
SA
120VAC
10A
AUTOMATEDLOGIC
LO
CKT #:
50va
REC
HI
7 8
CONTROL PANEL #
120 VAC
24 VAC
120 VAC (Provided & Wired by others)
CREATIVE DESIGN
Transformer (50 VA) mounted at each VVT Box to power ZN341v+.
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
CMnet daisy chained from previous / to next control module. (See riser detail)
Room Temp Sensor RSPLUS
NOT FOR CONSTRUCTION USE
WARMER
4 3 2 1
EF-x – EXHAUST FAN WIRING DETAIL 460 VAC/3PH/60HZ
Status EF-x - EXHAUST FAN STATUS - DI
1
COOLER
MANUAL ON OCCUPIED
MCC Starter
AUTHORITY APPROVAL
AUTOMATED LOGIC
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
CS H O A
EF-x - EXHAUST FAN START/STOP - DO
51
R-AC
04-112249
R^
EXHAUST FAN MODULE DETAIL NOT TO SCALE
ZONE BOX DETAIL
2
NOT TO SCALE
Administration Building and Library Network Architecture Layout AC-1 N1 12X12 LOCATE INSIDE UNIT
AC-2 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER ZN551
FLS
AC DATE
SS
SCHOOL DISTRICT: AC-3 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER ZN551
1
AC-4 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER
AC-5 N1 12X12 LOCATE INSIDE UNIT
AC-6 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER
ZN551
ZN551
UNIT POWER ZN551
AC-7 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER
AC-8 N1 12X12 LOCATE INSIDE UNIT
AC-9 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER
ZN551
ZN551
UNIT POWER ZN551
AC-10 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER
UNIT POWER
ZN551
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
AC-10 N1 12X12 LOCATE INSIDE UNIT
UNIT POWER ZN551
ZN551
16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
EXHAUST FANS N1 12X12
ZONE BOX Z10-1
120VAC ZN551
ZONE BOX Z10-2
120VAC
E
120VAC
E
ZN341V+
ZONE BOX Z10-3
120VAC
E
ZN341V+
ZONE BOX Z10-4
ZONE BOX Z10-5
120VAC
E
ZN341V+
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
E
ZN341V+
KEY PLAN
120VAC
E
ZN341V+
22/2 SHLD (Cmnet, Orange)
ZONE BOX Z11-1
ZONE BOX Z11-2
120VAC
120VAC
E
ZN341V+
ZONE BOX Z11-3
ZONE BOX Z7-1
120VAC
E
ZN341V+
ZONE BOX Z7-2
120VAC ZN341V+
ZONE BOX Z7-3
ZN341V+
ZONE BOX Z7-4
ZN341V+
ZONE BOX Z7-5
ZN341V+
ZONE BOX Z7-6
ZN341V+
ZONE BOX Z7-7
ZN341V+
ZONE BOX Z11-10
120VAC
E
ZN341V+
ZN341V+
ZONE BOX Z11-11
120VAC
E
ZN341V+
120VAC
E
ZN341V+
E
ZONE BOX Z7-8
120VAC
E
ZONE BOX Z11-9
120VAC
E
ZN341V+
120VAC
E
ZONE BOX Z11-8
120VAC
E
ZN341V+
120VAC
E
ZONE BOX Z11-7
120VAC
E
ZN341V+
120VAC
E
ZONE BOX Z11-6
120VAC
E
ZN341V+
120VAC
E
ZONE BOX Z11-5
120VAC
E
ZN341V+
120VAC
E
ZONE BOX Z11-4
120VAC
E
ZN341V+
E
ZN341V+
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
22/2 SHLD (Cmnet, Orange)
HIGH PERFORMANCE BACnet ROUTER w/GATEWAY 120vac HUB
E
ZONE BOX Z8-1
LGR25
DEV:01
ZONE BOX Z8-2
120VAC ZN341V+
ZONE BOX Z8-3
120VAC
E
ZN341V+
ZONE BOX Z8-4
120VAC
E
ZN341V+
ZONE BOX Z8-5
120VAC
E
ZN341V+
ZONE BOX Z8-6
120VAC
E
ZN341V+
ZONE BOX Z8-7
120VAC
E
ZN341V+
120VAC
E
ZN341V+
COPYRIGHT: CSDA ARCHITECTS 2011
ZONE BOX Z8-8
SHEET TITLE
120VAC
E
ZN341V+
E
EMS DIAGRAMS
BT D
TCP-01, BLDG PANEL
ORIGINAL SCALE 0
ETHERNET- CUSTOMERS WIDE AREA NETWORK CAT5e (BY OTHERS)
NETWORK RISER DIAGRAM NOT TO SCALE
3
1"
JOB NO.: SHEET NUMBER:
M-521
2"
PLUMBING SHEET INDEX
WATER HEATER SCHEDULE WATER HEATER ID WH-1
DESCRIPTION
SERVICE AREA
MANUFACTURER & MODEL
GAS INPUT
STORAGE CAPACITY
RECOVERY RATE IN GPH
WATER HEATER
NEW ADMINISTRATION BUILDING
A.O. SMITH BTH-150
150,000
100 GALLONS
173 GPH @ 100° RISE
REMARKS
SHEET NUMBER
MUST BE CEC APPROVED
EQUIPMENT SCHEDULE
PLUMBING SYMBOLS LEGEND
SHEET TITLE
P-001
LEGENDS, NOTES, AND SCHEDULES
P-100
PLUMBING SITE PLAN
P-110
PLUMBING FIRST FLOOR PLAN
P-111
PLUMBING SECOND FLOOR PLAN
SYMBOL
ABBREV. W
WASTE ABOVE FLOOR
W
WASTE BELOW FLOOR
SD
SD
STORM DRAIN ABOVE FLOOR
OD
OD
OVERFLOW DRAIN ABOVE GRADE
SD
SD
STORM DRAIN BELOW FLOOR
V EQUIP ID
ET-1
CP-1
DESCRIPTION
EXPANSION TANK CIRCULATING PUMP
MANUFACTURER & MODEL NUMBER
SERVICE
BELL & GOSSETT PT-12
WH-1
BELL & GOSSETT PL-30
WH-1
REMARKS 4 GALLON
P-130
PLUMBING ROOF PLAN
P-410
ENLARGED PLUMBING PLAN
P-420
3D RISER DIAGRAMS
P-500
DETAILS
(E)
COLD WATER
HW
HOT WATER
PLUMBING FIXTURE SCHEDULE FIXTURE ID
CONNECTION SIZE FIXTURE
TRAP
WASTE
VENT
COLD
COMMENTS
HOT
WC-1
WATER CLOSET
INTEGRAL
4"
2"
1"
-
SEE SPECIFICATION
WC-2
WATER CLOSET (ACCESSIBLE)
INTEGRAL
4"
2"
1"
-
SEE SPECIFICATION
INTEGRAL
2"
1-1/2"
-
-
SEE SPECIFICATION
UR-1
UR-2
L-1
URINAL URINAL (WATERLESS, ACCESSIBLE) LAVATORY
G
ICW
ICW
INDUSTRIAL COLD WATER
CD
CD
CONDENSATE DRAIN
D
D
SOV
INTEGRAL
1-1/4"
2"
2"
1-1/2"
1-1/2"
-
-
1/2"
1/2"
2"
1-1/2"
1/2"
1/2"
SEE SPECIFICATION
SS-1
SERVICE SINK
3"
3"
2"
3/4"
3/4"
SEE SPECIFICATION
CHECK VALVE
CO
CLEANOUT
FCO
FLOOR CLEANOUT
PIPE-UP UNLESS OTHER WISE NOTED
POC
POINT OF CONNECTION
ABV
ABOVE
BEL
BELOW
BV
BALANCING VALVE
CLG
FIXTURE ID
FIXTURE
QUANTITY
FIXTURE UNIT (FU)
WC
WATER CLOSET (115 FU FOR 5 WC) + (10 FU X 19 WC)
24
115 + 190
L
LAVATORY
17
SS
SERVICE SINK
DF
DRINKING FOUNTAIN HI-LO
2"
2"
1-1/2"
-
FLOOR DRAIN
-
DF-1
DRINKING FOUNTAIN HI-LO
2"
1-1/2"
1-1/2"
3/4"
-
SEE SPECIFICATION
TP-1
TRAP PRIMER
-
-
-
1/2"
-
SEE SPECIFICATION
HB-1
HOSE BIBB (WALL)
-
-
-
3/4"
-
SEE SPECIFICATION
RHB-1
RECESSED HOSE BIBB NON-FREEZE
-
-
-
3/4"
-
SEE SPECIFICATION
RD-1
ROOF DRAIN
SEE SPECIFICATION, SEE ROOF PLAN FOR SIZES
OD-1
OVERFLOW DRAIN
SEE SPECIFICATION, SEE ROOF PLAN FOR SIZES
SEE SPECIFICATION, SEE PLAN FOR SIZES
FIXTURE ID
305
WC
1
17
2
3
2
1
FIXTURE
GAS PIPING CALCULATION
QUANTITY
FIXTURE UNIT
TOTAL
QUANTITY
CFH (EACH)
CFH (TOTAL)
AC-1 & AC-2
2
120
240
AC-3 THRU AC-5
3
150
450
EQUIPMENT
24
6
144
L
LAVATORY
17
1
17
6
SS
SERVICE SINK
2
3
6
AC-6
1
224
224
2
DF
DRINKING FOUNTAIN HI-LO
2
1
2
AC-7 THRU AC-10
4
400
1600
HOSE BIBB (WALL)
4
3
12
RHB
RECESSED HOSE BIBB
6
3
18
UR
URINAL
TOTAL
TOTAL
360
GPM
110
EXISTING
ELEV
ELEVATION
FT
FOOT, FEET
FU
FIXTURE UNITS
FV
FLUSH VALVE
HDCP
HANDICAP
MTD
MOUNTED
REQ
REQUIRED
SGL
SINGLE
ST STL
5
5
25
AC-11
1
400
400
WH-1
1
150
150
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
DOWN
NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249 FLS
AC DATE
SS
STAINLESS STEEL
TYP
TYPICAL
VB
VACUUM BREAKER
W/
WITH
MEP COMPONENT ANCHORAGE NOTE:
WATER CLOSET
HB
CONSULTANT
CEILING
SEE SPECIFICATION, SEE PLAN FOR SIZES, PROVIDE WITH 1/2" MAX GRATE OPENING IN ALL DIRECTIONS
FIXTURE UNIT (WASTE) TOTAL
(E), EXIST
PROVIDE WITH 1/2" MAX GRATE OPENING IN ALL DIRECTIONS
FD-1
FIXTURE UNIT (WATER)
EXISTING PIPING WITH SERVICE INDICATED SHUT OFF VALVE
CV
DN
AREA DRAIN GRATE
RISER DRAIN
SEE SPECIFICATION
1-1/4"
AD-2
ARCHITECT STAMP
PIPE DROP UNLESS OTHER WISE NOTED
SEE SPECIFICATION
LAVATORY (ACCESSIBLE)
AREA DRAIN
GAS
DROP OR RISE
L-2
AD-1
design@csdarchitects.com T:310.821.9200 F:310.821.9201
HOT WATER RETURN
G
(E)
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
VENT
CW
HWR 1/6 HP-120V, 1Ø, 60HZ ALL BRONZE
DESCRIPTION
ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 1615A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS. THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY STTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
SCHOOL DISTRICT:
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL. FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER
194
TOTAL
MAXIMUM DEVELOPMENT LENGTH
SIZE OF GAS METER
3064
350 FT
4"
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22. THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PREAPPROVALS WITH AN OPA #, AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D. COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
LEGENDS, NOTES, AND SCHEDULES ORIGINAL SCALE 0
1"
JOB NO.: SHEET NUMBER:
P-001
2"
KEY NOTES
2 GPL
1
4" SEWER LINE EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
2
3" CW LINE EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
3
6" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
4
PROPOSED NEW GAS METER ASSEMBLY, COORDINATE & PAY ALL REQUIRED INSPECTION AND INSTALLATION FEES.
5
MEDIUM PRESSURE GAS PIPING BELOW GRADE, VERIFY PIPE SIZE WITH GAS COMPANY
6
MEDIUM PRESSURE GAS PIPING CONNECT TO EXISTING PIPING SERVING ALL OTHER BUILDINGS, VERIFY EXACT LOCATION AND SIZE ON SITE.
7
4" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
8
3" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
9
2" STORM DRAIN, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
ARCHITECT STAMP
LIMIT OF WORK
CONSULTANT
6
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
LIMIT OF WORK
CONSULTANT STAMP
3 NOT FOR CONSTRUCTION USE
1
9 9
3
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
1
04-112249 FLS
AC DATE
SS
3
3 9
SCHOOL DISTRICT:
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
LIM IT OF WO RK
N D
(N) ADMINSTRATION BUILDING
16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
9
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
9 8
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
1
2
1
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
OF LIMIT
PLUMBING SITE PLAN
K WOR
ORIGINAL SCALE 0
PLUMBING SITE PLAN 1" = 20'-0"
1"
JOB NO.: SHEET NUMBER:
1
P-100
2"
5.5
6
7
KEY NOTES
9
8
ELECTRICAL 152
9
J
1
2-1/2" CW TERMINATE 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
2
2-1/2" SOV IN YARD BOX
3
4" WASTE LINE, TERMINATE 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
4
2' MPG, FOR CONTINUATION SEE SITE PLAN, P-100
5
GAS REGULATOR
6
4" EARTHQUAKE SEISMIC SOV
7
4" WASTE UP TO SECOND FLOOR
8
1-1/2" CW & 3/4" HW UP TO SECOND FLOOR
9
3/4" CW DOWN IN WALL TO SERVE HOSE BIB
10
4" GAS OFFSET ABOVE CEILING
11
4" GAS UP TO SECOND FLOOR
12
2-1/2" CW IN YARD BOX
13
6" SD DOWN UP TO 2ND FLOOR, AND DOWN OFFSET BELOW GRADE
14
6" SD BELOW GRADE, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
15
6" OD DOWN UP TO 2ND FLOOR, AND DOWN OFFSET & SPILL ON GRADE AT 6" ABOVE FINISHED FLOOR
16
3" SD DOWN FROM 2ND FLOOR, OFFSET BELOW GRADE
17
3" SD BELOW GRADE, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
18
4" SD DOWN FROM 2ND FLOOR, OFFSET BELOW GRADE
19
4" SD BELOW GRADE, EXTEND 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
20
4" OD DOWN FROM 2ND FLOOR, OFFSET & SPILL ON GRADE AT 6" ABOVE FINISHED FLOOR
21
3/4" COND. DRAIN DN IN WALL & CONNECT TO TAIL PIECE ADAPTER
22
3/4" SECONDARY COND. DRAIN TERMINATE 1" BELOW CEILING WITH CHROM PLATE ESCHACHEON
23
2" SD BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
RHB-1
COUNSELOR 116
COUNSELOR CONFERENCE ROOM 117
COUNSELOR 115
COUNSELOR 113
COUNSELOR 114
COUNSELOR ASSISTANT 111A CORRIDOR 131
COUNSELOR 111
COUNSELOR 112
H
STORAGE 120 COUNSELOR 118
BOOK KEEPER 121 15 SD
14
UP
COUNSELOR 119
TEACHER WORKROOM / LOUNGE 110
TESTING MATERIALS 123
13
OD
STAFF TOILET 21 108 10
ELECTRICAL ROOM 124
BOOKSTORE 122
6
5
9
CD
FC 3 M-511 3
VENTED PIPE SLEEVE 4
RHB-1
G
G
ELECTRICAL 107
11 AD-2
3
FC 2
23
STAFF TOILET 109 3 M-511
23
1" CD UP TO 2ND FLOOR
ASSISTANT 126A
13
14
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
AUTHORITY APPROVAL
SICK ROOM 104
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
G
15
CREATIVE DESIGN
TOILET 106
F
CORRIDOR 130
CONSULTANT
NOT FOR CONSTRUCTION USE
M
COT 105
ARCHITECT STAMP
CONSULTANT STAMP
2 P-410
AD-2
STORAGE 125 4" V UP TO 2ND FLOOR ATHLETIC DIRECTOR 126
INVERT ELEVATION 4'-0" BELOW GRADE
design@csdarchitects.com T:310.821.9200 F:310.821.9201
04-112249
ASB / ACTIVITIES DIRECTOR 127
3
STORAGE 128 7
WCO
INVERT ELEVATION 4'-0" BELOW GRADE
GENERAL NOTES 1. 2.
E ASB WORK & CONFERENCE ROOM 129
1
2
3
REGISTRAR 102
REGISTRAR WAITING 102A
5
4
3. 4. 5.
L G
9
RECORDS STORAGE 101
SD
C
OD 13
N D
13 9 RHB-1
AP OFFICE 154
WAITING 148
STORAGE 153
PRINCIPAL'S CONFERENCE ROOM 161
STORAGE 145
PRINCIPAL'S OFFICE 160
OFFICE ASSISTANT 154A
B
OFFICE ASSISTANT 146A
STORAGE 144
SECURITY OFFICE 140
RHB-1
MEN'S RESTROOM 133
ELEVATOR -
GAS
CORRIDOR 132
23 16
CORRIDOR 162
UP AD-2
TA WORKSPACE 151B
22
TOILET 21 159
PRINCIPAL'S ASSISTANT 157
STORAGE 143
3" GAS UP TO 2ND FLOOR
SRO OFFICE 138
COPYRIGHT: CSDA ARCHITECTS 2011 STORAGE 142 STAFF TOILET 137
3 M-511
AP OFFICE 151
CD
2%
AP CONFERENCE ROOM 156
A
OFFICE ASSISTANT 141A
STORAGE 152
FC 1
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
23
17
OFFICE ASSISTANT 151A
STORAGE 158
10
AD-2
JANITOR 139
TA WORKSPACE 154B
3 P-410
9.5
9
ELEVATOR MACHINE ROOM 135
RHB-1
2" V UP TO 2ND FLOOR
LOBBY 100
15
AD-2
AP OFFICE 146
WAITING 147
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
KEY PLAN
14
23
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
14
15
SCHOOL DISTRICT:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
K
9.3
UP
PIPE LOCATIONS SHOWN ARE ONLY SCHEMATIC. MASONRY WALL PENETRATIONS OR FOUNDATION PENETRATIONS ARE NOT ALLOWED. PIPES MAY BE RUN BELOW OR ABOVE WALL FOOTINGS. PIPES MAY BE RUN ABOVE COLUMN FOOTINGS, BUT ARE NOT ALLOWED BELOW COLUMNS. SEE DETAIL 4 ON SHEET S-6 FOR DETAIL BELOW WALL FOOTINGS.
SCHOOL ADDRESS:
CORRIDOR 130
D
WAITING 150
WAITING 149
WOMEN'S RESTROOM 134
SHEET TITLE
1 P-410
2
AP OFFICE 141
SERVER / ELECTRICAL ROOM 155
STAFF TOILET 136
FIRST FLOOR PLUMBING PLAN
11 12
ORIGINAL SCALE 0
RHB-1 3 INVERT ELEVATION 4'-0" BELOW GRADE
SS
4" ATTENDANCE 103
8
RHB-1
FLS
AC DATE
CO
F.S. CLOSET 136A
3
INVERT ELEVATION 4'-0" BELOW GRADE
PLUMBING FIRST FLOOR PLAN
1
12
1/8" = 1'-0"
1
1"
JOB NO.: SHEET NUMBER:
P-110
2"
5.5
6
7
KEY NOTES
9
8
J
2%
1
3/4" CD UP THRU ROOF TO AC UNIT
2
2" GAS UP THRU ROOF TO AC UNIT
3
1-1/4" GAS UP THRU ROOF TO AC UNIT
4
4" GAS DOWN TO FIRST FLOOR
5
1-1/4" CONDENSATE DRAIN DOWN IN WALL AND SPILL INTO SERVICE SINK
6
1-1/2" GAS DOWN TO WATER HEATER, PROVIDE SOV
7
3" PVC SUPPLY AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH
8
3" PVC VENT AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH
9
6" SD & OD DOWNSPOUTS FROM ROOF
10
6" SD & OD DOWN TO 1ST FLOOR
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
9
2%
H 2%
ARCHITECT STAMP DN
1
2
2%
CO 3/4"
CONSULTANT 2%
10
G
CD
AV STORAGE 203 4
CREATIVE DESIGN
TECH STORAGE 202 4"V DOWN TO 1ST FLR
OFFICE 204 1"
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
M
1
CONSULTANT STAMP
2
1" CD DN TO 1ST FLR
4" V UP TO ROOF 10
NOT FOR CONSTRUCTION USE OFFICE 205
2
2%
9
F
AUTHORITY APPROVAL
LIBRARY 201
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
1 2%
04-112249
CONFERENCE ROOM 206
STAFF TOILET 207 4 P-410 2%
FLS
AC DATE
L
SS
CO
K
2
SCHOOL DISTRICT: 1
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
E
1
2
3
2%
WORK ROOM 208
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
3
SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
4 CO 1
9.3
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
D DN 10 10
C TEXTBOOK STORAGE 213
OD
JANITOR 209
SD
8
9.5
SS-1
WH-1
5
SD
CLOSET 221 OD
7
6 2 1 1/4" 1
3
2" V UP TO ROOF & DN TO 1ST FLR 6 P500
B
6 P500
3/4" CO
2%
CD
1
2% G
6 P500
2" CLOSET 218
3 3
2 1/2"
6 P500
1 3
2" V UTR & DN TO 1ST FLR
1"
G 1 1/2"
6 P500
DN
1 1/4"
3" SD DOWN TO FIRST FLOOR
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
CD CO
3"
3" GAS DOWN TO 1ST FLOOR AD-1
1
1
ELECTRICAL 219
COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
3 3" V UTR & DN TO 1ST FLR
CLASSROOM 215
10 CORRIDOR 210
9
9 1 CORRIDOR 217
1" 2%
CLASSROOM 216
WOMEN'S RESTROOM 212
CLASSROOM 214
STORAGE 220
SECOND FLOOR PLUMBING PLAN
AD-1
MEN'S RESTROOM 211
11 5 P-410
A
ORIGINAL SCALE 0
12
PLUMBING SECOND FLOORPLAN 1/8" = 1'-0"
1
1"
JOB NO.: SHEET NUMBER:
P-111
2"
5.5 5.5
6
M
7
6
7
KEY NOTES
9
8
8
J
E 8
L
7
K
2
2" GAS DOWN THRU ROOF
3
1-1/4" GAS DOWN THRU ROOF
4
4" SD UP TO UPPER ROOF AND DOWN SPILL ONTO LOWER ROOF
5
3" SUPPLY AIR DOWN THRU ROOF
6
3" VENT AIR DOWN THRU ROOF
7
4" SD DOWNSPOUT FROM UPPER ROOF
8
4" SD DOWN TO LOWER ROOF
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
H
9.3
ARCHITECT STAMP
9.5
7
3/4" CD DOWN THRU ROOF
6" OD 6" SD 3600 S.F.
D
1
10 PIPE SUPPORT (TYP.) P-500
8
1
2
C 1.3
CONSULTANT
G 10
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
2
1
1.2
B
CONSULTANT STAMP
ROOF ACCESS
LOWER ROOF
NOT FOR CONSTRUCTION USE
4" V DOWN THRU ROOF
F
6" SD
2
1
6" OD 5293 S.F.
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
M
11
04-112249 ROOF JACK FLS
AC DATE
2" V DOWN THRU ROOF
SS
2
5
12
1
PLUMBING UPPER ROOF PLAN 1/8" = 1'-0"
SCHOOL DISTRICT:
E
2 4
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
L
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
3
SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
1
9.3
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
D
K 4
KEY PLAN
OPEN
ROOF JACK
C
9.5 2" V DTR. ROOF JACK 6
10 PIPE SUPPORT (TYP.) P-500
5 4" V DTR.
2 1
OPEN
3
2" V DTR.
10
6" OD 6" SD 3653 S.F.
LOWER ROOF
B 6" OD 6" SD 3570 S.F.
2" V DTR.
1
1
LOWER ROOF
3
3 3
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
ROOF ACCESS
1
3 4" V DTR
1
1
COPYRIGHT: CSDA ARCHITECTS 2011
3" V DTR.
SHEET TITLE
PLUMBING ROOF PLAN
11
A
ORIGINAL SCALE 0
12 1
2
3
4
5
PLUMBING ROOF PLAN 1/8" = 1'-0"
1
1"
JOB NO.: SHEET NUMBER:
P-130
2"
KEY NOTES 4 1
7 RHB-1 3" WASTE UP TO 2ND FLOOR
HB-1 10
FCO
FCO STAFF TOILET 207
WC-2
L-2
4
TP WC-2
2"V
L-2
11
4"
4" W
4" V DN IN WALL
24
12
11
WC-1 10 2" V UTR
23
4" 2"
2%
WC-2
FCO 2"V UP TO 2ND FLR
3
1/4" = 1'-0"
MEN'S RESTROOM 133
3
B
4
4" 4" 8
L C
2%
2" 9
WOMEN'S RESTROOM 134 4"
WC-2
FD-1
FD-1
FD-1
32
TP
STAFF TOILET 137
2" VTR
FCO
WC-2
L-2
WC-1
WC-1
2
15
8 P-500
WH-1
2%
WC-1
16
TP
TP
3" V UP TO 2ND FLR
2"
26
L-1
11 2%
WCO
1 1/2"
29
4
2-1/2" CW UP TO 2ND FLOOR
5
2" HW UP TO 2ND FLOOR
6
3/4" CW DN IN WALL TO DF
7
3/4" CW AND 3/4" HW DN IN WALL TO SERVE SERVICE SINK
8
3/4" CW AND 3/4" HW DN IN WALL TO SERVE LAV AND HB
9
1-1/2" CW, 3/4" HW DOWN IN WALL, PROVIDE SOV AND ACCESS PANEL, RUN 1-1/2" CW TO WC, 3/4" CW & HW TO LAV AND 1/2" CW TO TRAP PRIMER
10
1-1/2" CW DN IN WALL TO WC, PROVIDE SOV AND ACCESS PANEL, RUN 1-1/2" CW TO WC & 1/2" CW TO TRAP PRIMER
11
4" VENT UP TO 2ND FLOOR
12
3/4" CW, 3/4" HW DOWN IN WALL TO SERVE LAV
13
1-1/4" CONDENSATE DRAIN DOWN IN WALL AND CONNECT TO TAILPIECE ADAPTER
14
1" CONDENSATE DRAIN DOWN IN WALL CONNECT TO TAILPIECE ADAPTER
15
3/4" HW DOWN IN WALL TO SERVE LAV
16
4" WASTE DOWN FROM 2ND FLOOR
17
4" GAS UP IN WALL, OFFSET ABOVE CEILING
18
EARTHQUAKE SOV
19
GAS PRESSURE REGULATING VALVE
20
4" GAS BELOW GRADE, FOR CONTINUATION SEE SITE PLAN
21
4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING
22
1" CONDENSATE DRAIN DOWN IN WALL CONNECT TO TAILPIECE ADAPTER
23
1-1/4" CONDENSATE DRAIN DOWN IN WALL CONNECT TO TAILPIECE ADAPTER
24
1-1/2" CW & 3/4" HW DOWN TO FIRST FLOOR
25
4" WASTE DOWN TO FIRST FLOOR
26
2" HW DOWN TO FIRST FLOOR
27
2-1/2" CW UP FROM FIRST FLOOR
28
4" VENT DN TO FIRST FLOOR AND UP THRU ROOF
29
3" WASTE DOWN TO FIRST FLOOR
30
1-1/2" CW & HW DN TO WH
31
3" PVC SUPPLY AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH
32
3" PVC VENT AIR UP THRU ROOF TERMINATE WITH RAIN CAP AND DOWN TO WH
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
ARCHITECT STAMP
CONSULTANT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
WC-1
WC-2
NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249 FLS
AC DATE
SS
L-2
27
31
STAFF TOILET 136
2 1/2"
11
2 1/2"
3
15 10
TP
SCHOOL DISTRICT:
2%
2-1/2" SOV IN YARD BOX 2%
WC-2
A
12
4" V DN IN WALL
FD-1
28
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
A 4"
4"
DF-1 CO
2"W DN TO 1ST FLR
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
21
SCHOOL ADDRESS:
1
B
FIRST FLOOR RESTROOM 133, 134 2 1/2"
2-1/2" CW DOWN IN WALL TO 2-1/2" CW HEADER, RUN 1-1/2" CW TO EACH WC & 1/2" TO TRAP PRIMER, PROVIDE SOV AND ACCESS PANEL
HB-1
L-2
30
3
DF-1
1" HW UP TO 2ND FLR
SS-1
2-1/2" CW UP IN WALL, OFFSET ABOVE CEILING
6 2%
7 SECOND FLOOR RESTROOM 207
2
TP
7 SS-1
1/4" = 1'-0"
2"W UP TO 2ND FLR
FD-1 12
2-1/2" CW BELOW GRADE, TERMINATE 5'-0" FROM EXTERIOR WALL, FOR CONTINUATION SEE CIVIL DRAWING
L-1
25
FCO
FIRST FLOOR RESTROOM 159
8
L-2
UR-2
FD-1
TOILET 159
5
UR-1
TP FD-1
4"
1
4
8
3/4" HWR
1/4" = 1'-0"
1
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
1" HW DN. TO 1ST FLR
G
15
22
10
10
15 TP
TP
L-2
20
G WC-2
17
21
2%
FCO 8
FD-1
L-1
L
FD-1
TP
L-1
TP
3
WC-2
STAFF TOILET 108
L-2
4"
FD-1 STAFF TOILET 4" 109
L-1
FCO 4" V UTR & DN TO 1ST FLR
CD
FD-1
L-1
3
1"CD
WOMEN'S RESTROOM 212
HB-1
WC-1 UR2
2%
HB-1
G
19
RHB-1
8
L-2
18
L-2 MEN'S RESTROOM 211
WC-1 WC-1
4" W DOWN TO FIRST FLOOR
UR-1
WC-1
UR1
WC-1
FD-1
TP
FCO
L-2
FD-1
15
WC-2
TP
TP
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
12
COPYRIGHT: CSDA ARCHITECTS 2011
FD-1
SHEET TITLE
STAFF TOILET 106 WC-2
WC-2
A
WCO
F
ENLARGED PLUMBING PLAN ORIGINAL SCALE 0
8
4
SECOND FLOOR RESTROOM 211, 212 1/4" = 1'-0"
5
JOB NO.: SHEET NUMBER:
9
FIRST FLOOR RESTROOM 106, 108, 109 1/4" = 1'-0"
1"
2
P-410
2"
2" VTR 4" VTR
2" VTR
AC-10 2" (400 CFH)
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
4" VTR AC-8
3" (3)
2" (400 CFH)
design@csdarchitects.com T:310.821.9200 F:310.821.9201
SS 4" V UTR
AC-7
3" (1424 CFH)
2" (400 CFH)
DF SINK
AC-9 2" (400 CFH)
3" (1024 CFH) 4" (1824 CFH)
3" (4)
2" (1)
AC-6 2" V UTR
2-1/2" (624 CFH) LAV
1-1/2" (224 CFH) 4" (3064 CFH)
LAV
2" VTR
EARTHQUAKE SOV
3" (1240 CFH)
LAV FD
LAV
GAS PRESSURE REGULATOR
LAV
WC
LAV
3" (6)
2" (3) 4" (63)
UR 4" GAS BELOW GRADE, FOR CONTINUATION SEE SITE PLAN
WC
FD
UR
2" (3)
4"V UR
FCO
FD
WC WC
FD
4" (29) WC
2" (1) 4" (24)
WC
3" (10)
SS
AC-11
1-1/4" (120 CFH)
LAV
LAV
2" (400 CFH)
AC-2
1-1/4" (150 CFH)
4" (31)
4" (29)
2" 1-1/2" AC-5
3" (1090 CFH)
AC-4
LAV
WC
AC-3
2-1/2" (690 CFH) 1-1/4" (150 CFH) 1-1/2" (300 CFH) 1-1/4" (150 CFH)
WH
LAV
3" (1240 CFH)
FCO
4" (6)
WC
3D RISER - GAS
3D RISER - WASTE & VENT - TOILET 159
5
4" (145)
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
WCO
4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING
WC
FD
4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING
4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING
SINK
4" (24) 4" (6)
4" (7)
1-1/4" (150 CFH)
CONSULTANT
4" (7)
4" (6)
4" (9) 2" (1)
2"
2" (1) 4" (6)
WC
WC
FD
2" (540 CFH)
2" (1) FD
WC
WC
LAV
FD
WC
FCO
WC
WC
2"V
LAV
4" (6)
FD
FD
4" (6)
1-1/2"V
FCO
3" (3)
AC-1
FD
1-1/2"V
4" (7)
2"
WC
2"
4" (6)
FD
WC
LAV
2"V
4"
WC
FD
FCO
WCO FCO
ARCHITECT STAMP
4" (21)
WC
LAV
WC
DF
2"V LAV
FCO
FD
WC
3"V
LAV
UR
UR FCO
LAV
4" WASTE BELOW GRADE, FOR CONTINUATION SEE CIVIL DRAWING
CO
CONSULTANT STAMP
4" (17)
3D RISER - WASTE & VENT - WEST SIDE
4
3D RISER - WASTE & VENT - NORTH SIDE
3
2
NOT FOR CONSTRUCTION USE
SINK
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249
3/4"CW (3)
RHB
.
1"HW (7)
LAV
WC
LAV
FD
WC FIXTURE UNIT COUNT
LAV
WC
PIPE
CW - FV (FU)
HW (FU)
WC
FIXTURE UNIT
1/2"
1
0
1
1ST
40
SCHOOL ADDRESS:
.. .
FD WC
6
2ND
2"CW (41) 3/4"HW (1)
1"
13
0
13
3RD
20
1-1/4"
24
0
24
4TH
15
.
2-1/2"CW (105)
..
.
10
47
5TH OR MORE
158
64
10
3/4"HWR
WH-1
120
245
.
246 .
3"
691
630
..
. . DF
1"HW (10) 1"HW (6)
.
RHB
3/4"CW (6) 3/4"HW (3)
1-1/4"HW (20)
412
2-1/2"CW (111)
3/4"HW (3)
SS
. 380
KEY PLAN
2-1/2"CW (147)
3/4"HW (6) 2-1/2"
1"HW (10)
3/4"CW (3)
. 2"
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
.
. 47
3/4"CW (1)
3/4"CW (3)
2-1/2"CW (150)
1-1/2"
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
LAV
FD
3/4"CW(3) 3/4"HW(3)
1-1/2"CW (23) 1-1/2"HW (23) 1-1/2"CW (26) HWR
30
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
2"CW (41)
FD
CW - FT (FU)
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
3/4"HW (1) RHB
WC
0
.
. .
2"CW (98)
6
SCHOOL DISTRICT:
2-1/2"CW (75) 3/4"CW (1) 3/4"HW (1)
2"CW (95)
3/4"
2-1/2"CW (135)
3/4"HW (6) BASED ON 3 PPSI PER 100 FEET LOSS
1-1/4"HW (18) .
2-1/2" CW (102)
.
2-1/2"CW (178)
.
2" CW (47)
RHB HB LAV WC
2" CW (44)
. .
.
1-1/4"HW (14) 1-1/4"HW (15) 2-1/2"CW (70) SS
2" CW (41) 1-1/4"HW (15)
.
LAV
WC WC FD
3"CW (267)
.
.
LAV
WC
LAV
HB
TP WC
WC
2-1/2"CW (112) 1"HW (10)
WC
WC
FD
.
FD
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
TP TP
WC
3/4"CW (5) 3/4"HW (2)
DF
FD
3"CW (272) TP
COPYRIGHT: CSDA ARCHITECTS 2011
HB
2-1/2"CW (75) 3/4"HW (2)
. . .
. LAV
. .
FD
TP . .
3/4"CW (6) 3/4"HW (3)
LAV LAV HB LAV . .
2-1/2" CW (99)
.
RHB
1"CW (8) 3/4"HW (2)
2-1/2"CW (158)
3/4"CW (3)
SS
3/4"HW (1) 2"CW (44)
2"CW (40)
CW & HW PIPE SIZING
FLS
AC DATE
3/4"HW (2) 2"CW (41)
2-1/2"CW (125)
RHB WC LAV
WC
WC FD
LAV
TP
SHEET TITLE
LAV
LAV
WC
WC WC
3D RISER DIAGRAMS
WC FD
TP
TP
2" CW (40) 3/4"CW (1) 3/4"HW (1)
FD
TP FD
WC
3"CW SOV IN YARD BOX 3"CW, FOR CONTINUATION, SEE CIVIL DRAWING
ORIGINAL SCALE 0
3"CW (360) RHB
LAV
FD
WC
TP
3D RISER - CW & HW
1
1"
JOB NO.: SHEET NUMBER:
P-420
2"
1-1/4" GAS SUPPLY 1-1/2" COLD WATER SUPPLY 3/4" HOT WATER RETURN 10'-0" CLAMP-ON AQUASTAT FOR PUMP CONTROL SHUT-OFF VALVE (TYP.) 3" PVC VENT UTR 3" PVC INTAKE AIR UTR
CP 1
CLEANOUT IN YARDBOX
12" SQ.x6" DEEP CONCRETE PAD
CLEANOUT IN YARDBOX
TRENCH EXCAVATION
CONCRETE
BACKFILL AS PER SPECIFICATONS
9"
BLACKTOP PAVING
GROUND LINE
THE SLOPE OF THIS LINE MUST BE APPROVED BY THE STRUCTURAL ENGINEER
2"
CHECK VALVE UNION (TYP.)
1"
1'-6" MIN. PRESSURE & TEMPERATURE RELIEF VALVE D
4"
TRENCH EXCAVATIONS
3/4" DRAIN SPILL TO EXIST. FLOOR SINK
1" 4"
4"
4"
G
NOTE: FOR PIPES MORE THAN 3'-0" BELOW BOTTOM OF FOOTING STEP AS REQUIRED
NOT PARALLEL TO FOOTING
DRAIN VALVE 2"x2"x1" ANGLE IRON CLIP (TYP. FOR 3) 1/2" X 2" EMBEDMENT HILTI KB-TZ (TYP.)
WATER HEATER DETAIL NOT TO SCALE
TYPICAL EXTERIOR CLEAN OUT DETAIL
8
COMPACTED FILL OF INUNDATED SAND MAY BE USED IN WELL DRAINED SANDY OR GRAVELLY SOIL 90% DENSITY
2"
1/2" BOLT WITH WASHER INTO BACKING (TYP. 4 PLACES). FOR BACKING SEE DETAIL 2Q ON SHEET S8.1 PROVIDE 2"x12 GAUGE GALV. STEEL STRAP AROUND WATER HEATER WITH 1/2" NUT & BOLT WITH WASHER (TYP. 2 PLACES)
1-1/2" HOT WATER SUPPLY
NOT TO SCALE
ALL PIPE SLEEVES 2" MIN. LARGER THAN PIPE 3" MIN.
SECTION 4
NO PIPES ALLOWED IN FOOTING
3" MIN.
3" MIN.
6" MIN. 3'-0" MAX.
PIPE SLEEVE DIA. PLACE CONC. FILL AROUND SLEEVES BEFORE POURING FOOTING
6" MIN.
PIPE AT FOOTING DETAIL
4" LONG FLEXIBLE HOSE STAINLESS STEEL HOSE CLAMPS TYPICAL UNIT
NOT TO SCALE
1"
MINERAL WOOL INSULATION MIN 1" DEEP (TYP)
PIPE SLEEVE
3M FIRE BARRIER ¼" BEAD CP25 CAULK (TYP)
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
FOR USE WITH THE FOLLOWING TYPES OF HINGE ARRANGEMENTS
"I" OR "WF" BEAM CLAMP 2 3/8" - 7" FLANGES 1365# MAX
3" MIN TRAP
CREATIVE DESIGN
PIPE HANGER
"I" BEAM CLAMP 2' 6 1/2" FLANGES 540# MAX
ADJUSTABLE SWIVEL COUPLINGS <2300#
INSULATION
CONSULTANT STAMP
LINKED EYE RODS
NOT FOR CONSTRUCTION USE
CHANNEL CLAMP 1740# MAX
PIPE
NOTES:
1
U.L. LISTED SYSTEM CAJ5001
1. CONDENSATE DRAIN PIPING SHALL BE TYPE "M" COPPER.
1. DETAIL SIMILAR FOR UNINSULATED PIPE.
CONDENSATE DRAIN EQUIPMENT CONNECTION DETAIL
9
NOT TO SCALE
SWIVEL HANGER PLANGE
PIPE THRU CONCRETE FLOOR OR WALL DETAIL NOT TO SCALE
AUTHORITY APPROVAL
ADJUSTABLE SWIVEL HANGAR FLANGE
CONCRETE INSERT
NOTES:
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249
PIPE HANGARS FOR OTHER THAN ADJUSTABLE WROUGHT IRON
CONCRETE INSERTS
5
TYP. PIPE W/ ALUMINUM JACKET & INSULATION
ANNULAR SPACE SPACE SHALL BE ¼" TO 3/8"
FOR THREADED ROD
UNISTRUT 1 5/8 CHANNEL SERIES P3000 WELDED TO 1 1/4" SCHEDULE 40 PIPE
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT
RING
VERTICAL PIPE SUPPORT AT EACH FLOOR EXTENSION CALMED WITH TEFLON OR LEAD LINER WHEN USE COPPER PIPE.
PIPE
LEAD FLASH (TYPICAL)
16350 MOJAVE DRIVE VICTORVILLE, CA 92395
CONC. FL.
SCHOOL ADDRESS:
SUBMERGED GALV. SUPPORT PIPE
1 1/4" PIPE (TYP.)
FLASHING & COUNTER FLASHING (TYPICAL)
CLEVIS RING
FOR THREADED PIPE AS HANGAR ROD
UNISTRUT PIPE CLAMP
ELASTOMERIC WRAP STRIP WITH FOIL FACE 2 IN. WIDE BIND W/ STEEL WIRE OR ALUMINUM FOIL TAPE 3M TYPE FS-195 OR EQUAL.
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
ALL PIPES AND DUCTS SHALL BE SUPPORTED AND BRACED PER "SMACNA" GUIDELINES OSHPD PRE-APPROVAL NO. R.0010
INSULATION
SS
SCHOOL DISTRICT:
WOOD CEILINGS, BEAMS, OR JOISTS
3M FIRE BARRIER BEAD CP25 CAULK (TYP)
FLS
AC DATE
4 WEDGE TYPE
INSULATION SHIELD REQUIRED FOR INSULATED PIPE
CONSULTANT
GROUT
6" MAX
SEE PLAN FOR SIZE
ARCHITECT STAMP
2" CEM. DRYPACK IF PLACED UNDER EXISTING FOOTING
ALL PIPE SLEEVES 2" MIN. LARGER THAN PIPE
d + 1'-6"
SLOPE DOWN TOWARDS APPROVED RECEPTOR @ 1/8" PER LINEAR FOOT.
design@csdarchitects.com T:310.821.9200 F:310.821.9201
NO PIPE TRENCH PARALLEL TO FOOTING BELOW THESE LINES
4"
4" WH 1
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
PIPE HANGING COMPONENT DETAIL
3/4"+
NOT TO SCALE
RATED WALL
2
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
U.L. LISTED SYSTEM WL-5001
NOTES:
BARE METAL DECK
1. FOR UNINSULATED PIPE WRAP STRIP MAY BE ELIMINATED AND ANNULAR SPACE SHALL BE 0-3/16 INCH, WITH CAULK ONLY.
6 4"C O.
4"
33" APPROX.
C.I. NT VE
SEALED OFF FLANGE
.I. C ENT V
O. 4"C
ROOFING
4"C.I.
(TYPICAL) 12" LONG BRAIDED FLEX CONN BRASS THREADED ENDS
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO
30" APPROX.
COUPLING
24 GA. GALV. STEEL PIPE FLASHING
FIG. NO. 1
4"C.I.
FLASHING & COUNTER FLASHING
FIG. NO. 2C
C.I. VENT
AC UNIT
T EN
PIPE SEE PLANS FOR SIZE & CONT.
I. V C.
LEAD COLLAR
4"C.I.
FIG. NO. 3
34 1/2" MAX 23 1/2" MIN
NOT TO SCALE
28" APPROX.
10
24"APPROX.
PIPE THRU FIRE WALL DETAIL
C.I. VENT
NOT TO SCALE
2. OTHER U.L. LISTED SYSTEMS MAY BE USED, SUBMIT FOR REVIEW.
21"APPROX.
PIPE SUPPORT ON ROOF DETAIL
22 S-12
C.I. VENT
FOR CONNECTION TO ROOF SEE STRUCTURAL DETAIL
COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
4"CO.
SEE DRAWING FOR CONT
FIG. NO. 2A
GAS STOP - IRON BODY W/BRONZE PLUG & WASHER
FLASHING COMPOUND
ROOF DECK
ALTERNATE POSITION OF CO. LINE
FIG. NO. 2
NOTE: FOOTINGS MUST BE LOWERED TO SUIT THE INSTALLATION OF CLEAN-OUT LINES IN FIGURES HR2, 2A, 2B, 2C & 3
SLEEVE THRU ROOF (TYPICAL)
DETAILS
4"
4"
ALTERNATE POSITION OF 4" COMB. FITTING W/ RUN COMING TOWARD OBSERVER & 4" CO ON OPPOSITE END.
FIG. NO. 2B
ORIGINAL SCALE 0
GAS TO EQUIPMENT CONNECTION DETAIL NOT TO SCALE
PIPE THRU ROOF DETAIL 11
NOT TO SCALE
7
WATER CLOSET SOIL PIPE CONNECTION DETAIL NOT TO SCALE
3
1"
JOB NO.: SHEET NUMBER:
P-500
2"
REVISIONS
BY
KEY NOTE: ROOF 3" GAS TO EXISTING 3" GAS LINE ON ROOF
1
AMERICAN METER GAS REGULATOR, 15 PSI, 2" INLET, MODEL 1803.
2
AMERICAN METER GAS REGULATOR, 15 PSI, 1-1/2" INLET, MODEL 1803.
3
4" GAS BELOW GRADE CONNECT TO EXISTING GAS TO WEST CAMPUS, VERIFY EXACT LOCATION ON SITE
4
6" GAS BELOW GRADE CONNECT TO EXISTING GAS TO EAST CAMPUS, VERIFY EXACT LOCATION ON SITE
5
REMOVE EXISTING GAS PIPING INCLUDING PIPING ON ROOF OF EXISTING ELECTRICAL ROOM
6
GAS SHUT OFF VALVE
7
6" GAS UP OFFSET ON ROOF
8
POINT OF CONNECTION TO EXISTING 6" GAS ON ROOF
9
EXISTING 6" GAS ON ROOF, VERIFY EXACT LOCATION ON SITE
10
3" GAS UP OFFSET ON ROOF
11
POINT OF CONNECTION TO EXISTING 6" GAS ON ROOF
12
EXISTING 3" GAS ON ROOF, VERIFY EXACT LOCATION ON SITE
13
4" GAS BELOW GRADE CONNECT TO EXISTING GAS TO POOL, VERIFY EXACT LOCATION ON SITE
14
6" GAS OFFSET BELOW GRADE
15
6" GAS MANIFOLD, OFFSET (4) GAS PIPES BELOW GRADE: 4" GAS TO WEST CAMPUS, 2" GAS TO OLD GYM, 6" GAS TO EAST CAMPUS, AND 4" GAS TO POOL.
16
THE GRAVITY LINES SHOULD BE PLACED FIRST TO ALLOW ENOUGH CLEARANCE BETWEEN ALL PIPING BELOW GRADE
17
6" GAS BELOW GRADE CONNECT TO EXISTING GAS TO NEW GYM, VERIFY EXACT LOCATION ON SITE
18
2" GAS BELOW GRADE CONNECT TO EXISTING GAS TO OLD GYM, VERIFY EXACT LOCATION ON SITE
6" GAS TO EXISTING 6" GAS LINE ON ROOF
6
UNION (TYP.)
2
15
1
1 6
1
FLOOR
6
TEST PORT (TYP.) 6
TEST PORT (TYP.) 1-1/2" MPG
6
2" MPG
2" MPG 6" GAS TO NEW GYM 2" MPG 4" GAS TO WEST CAMPUS 2" GAS TO OLD GYM 6" GAS TO EAST CAMPUS 4" GAS TO POOL
SECTION DIAGRAM NOT TO SCALE
2
GENERAL NOTE: PROVIDE EARTHQUAKE SHUT OFF VALVE AT EACH EXISTING BUILDING IF IT IS NOT ALREADY INSTEALLED.
2
11
1-1/2" MPG
3
9
10
2
13
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 (818) 507-7522
12
CREATIVE DESIGN
GPL
CAP (TYP.) 8
7 1 6
5
15
5
1
4
6 14
3" MPG 2"MPG 4"MPG 2"MPG 4"MPG
1 6 6"
2"
18 16
4" MPG
6"
17
16
16
16
G
4" MPG
4" MPG
MPG
4 1-1/2" MPG 6
2
MPG 16
4", 5 PSI GAS PRESSURE BELOW GRADE 4", 5 PSI MEDIUM GAS LINE DOWN TO BELOW GRADE GAS METER ASSEMBLY HIGH PRESSURE GAS PIPING TO BELOW GRADE BY GAS COMPANY
TO MAIN GAS LINE BY GAS COMPANY
16500 MOJAVE DRIVE VICTORVILLE, CA 92395
JOB TITLE
GAS PIPING LAYOUT
SHEET TITLE
N D
VVHS - GAS PIPING LAYOUT
(N) ADMINSTRATION BUILDING
PROJECT # DATE
07/26/2012
DRAWN BY
PP
CHECKED BY
VO
SHEET NUMBER
GAS PIPING LAYOUT 1" = 20'-0"
1
GPL