Asbestos Re-Inspection Report A Building, A Hospital Site, Any Town Hospital NHS Trust
Prepared for: Mr A N Other Project Manager Any Town Hospital NHS Trust A Hospital Any Town AN1 0WQ
February 2010
Prepared by: Mr Kevin Hume Oakleaf Technical Services Ltd. 7 Brookfield Moulton Park Northampton NN3 6WL
Oakleaf Technical Services Ltd. 0845 293 7571
Issue 2
Contents Item
Page
Introduction
3
Method of Survey
4
Risk Assessment
5
Survey Information
6
Section 1 Asbestos Material Risk Summary Report Section 2 Asbestos Register Sheets Section 3 No Access Report Section 4 Site Drawings Section 5 Removal and Clearance Information
A Building, A Hospital February 2010
Asbestos Survey Page 2 of 7
Oakleaf Technical Services Ltd. 0845 293 7571
Issue 2
Introduction Further to a request made by Mr A N Other of Any Town Hospital NHS Trust, Oakleaf Technical Services Ltd has completed a re-inspection of previously identified asbestos materials (ACMs) in A Block. A survey report (produced by Aspect Contracts Ltd) was provided by the Trust and used as the base for the re-inspections. All asbestos information has been checked and updated to provide the Trust with accurate and compliant risk assessments. Any caveats from the original reports are still important and should be considered when managing asbestos on the site. The inspections were completed in August of 2010. At the time of the survey, the building was occupied and fully functional. Access to the site was arranged by Mr A N Other who coordinated with local building users and the Estates team. For details of the asbestos contained within this building, see section 1 and 2 of this report.
A Building, A Hospital February 2010
Asbestos Survey Page 3 of 7
Oakleaf Technical Services Ltd. 0845 293 7571
Issue 2
Method of Survey The building was inspected in a professional and methodical manner, using the drawings and existing survey reports provided by the Trust. Access to the site was arranged through Mr A N Other. The survey was carried out in accordance with the Oakleaf Technical Services Ltd in house asbestos survey procedure. This procedure is based upon and meets the requirements of HSG 264 Asbestos: The survey guide. Where possible, all areas of asbestos identified in the previous report have been accessed and their current condition recorded. Material risk assessments for all asbestos containing materials (ACMs) have been produced, to show current levels of damage and subsequent treatments. Recommendations of future actions for each asbestos containing material (ACM) have been provided. Any actions taken must be in full accordance with the Control of Asbestos Regulations 2006 (CAR 2006).
A Building, A Hospital February 2010
Asbestos Survey Page 4 of 7
Oakleaf Technical Services Ltd. 0845 293 7571
Issue 2
Risk Assessment The risk assessment method used is the HSE approved ‘materials risk assessment’, as described in the HSE document HSG 264. This is used to assess all ACMs on a like for like basis, using an algorithm that for each ACM looks at:
Product type – Cement roof sheets or gaskets etc. Extent of damage/deterioration – High or low etc. Surface treatment – Painted, exposed etc. Asbestos type – Chrysotile etc.
Each of these parameters is awarded a score, with the scores then combined to give the final material risk assessment score of between 2 and 12. Materials that do not contain asbestos are not given a score. ACMs with a score of 10 or more should be regarded as high risk with a significant potential to release fibres if disturbed. ACMs with a score between 7 and 9 are regarded as medium risk items. ACMs with a score between 5 and 6 are regarded as low risk items. ACMs with a score of 4 and below are regarded as very low risk items.
A Building, A Hospital February 2010
Asbestos Survey Page 5 of 7
Oakleaf Technical Services Ltd. 0845 293 7571
Issue 2
Survey Information Sealed voids; partitions; cavity walls; behind cladding; behind Asbestos Containing Materials (ACMs); under floorboards; safes/fire cabinets; plant and equipment; above solid ceilings, where to gain access would have caused destruction, have not been surveyed. The extent of the survey did not include items on the surface of or within the ground beneath or adjacent to the survey area. The grounds of the building and inaccessible areas such as under floor ducts, tunnels and sewers have not been assessed. Confined spaces of any kind will not have been accessed. This is not a contaminated land survey. This also applies for re-locatable items held in storage facilities (for example, asbestos gloves in boxes or draws). Representative checks will have been made above suspended ceiling grids where access is available, i.e. where the ceiling tiles were not sealed with paint or fixed with screws/nails. Loft and roof spaces will have only been surveyed where safe access was available. If crawl boards or secure flooring were not present, the area would have been deemed to be unsafe. Flooded basements, pipe runs, troughs or other areas that were covered with water could not be fully assessed. These areas may contain asbestos that is not identified in the survey. Fuse boxes will not have been opened up as they remain ‘live’ and would constitute a safety hazard. Some older type fuse boxes have been known to contain chrysotile asbestos rope used as fuse insulation. It will be necessary to presume that these contain asbestos and investigate the areas with the help of an electrician before any future works are carried out. Fixed items of plant, heaters, services or equipment will not have been surveyed internally, as surveyors are not qualified to shut down, dismantle and restart these items. The survey was limited to the accessible external casings of these items. Oakleaf Technical Services Ltd make every effort to fully survey buildings and rooms, but cannot be held responsible for asbestos products located behind or underneath stored items. This is particularly important in areas of excessive or untidy storage. As a qualified engineer was not present on site, the lift shafts have not been fully inspected. The inspection will have been limited to gaps in-between the lift doors and the lift shaft were lifts are present. Within a survey, Oakleaf Technical Services Ltd will not have removed insulation or its coverings, such as metal or plaster cladding. The inspection will have been carried out where the underlying pipe was visible (normally at areas of damage, flanges or gaskets) and the outer casing of boilers, pipes and other plant machinery.
A Building, A Hospital February 2010
Asbestos Survey Page 6 of 7
Oakleaf Technical Services Ltd. 0845 293 7571
Issue 2
General Comments: Where drawings have been provided by the client, Oakleaf Technical Services Ltd does not accept liability for recording errors due to inaccurate drawings. The results in the survey report relate to prevailing conditions on site at the time of survey. Alterations to the building or to its use and occupancy may affect the accessibility of ACMs contained within. In these circumstances, the report should be reviewed in accordance with HSG227 ‘A comprehensive guide to Managing Asbestos in Premises’. Due to the limitations described above, the survey information should not therefore be solely relied on when undertaking building works. Before any building works, refurbishment or re-wiring etc are undertaken a fully invasive demolition or refurbishment survey must be carried out in the location of the works to ensure that workers are not put at risk.
A Building, A Hospital February 2010
Asbestos Survey Page 7 of 7
Section 1: Asbestos Material Risk Summary Report
Section 1 Oakleaf Technical Services 0845 293 7571
Asbestos Material Risk Summary Report Site: A Hospital Site Block: A Building Accessibility Score
Qty
Materials Risk Score
1
1
3 m2
2 (Very Low)
Chrysotile
1
2
<1 m2
2 (Very Low)
0
Chrysotile
1
1
3 m2
2 (Very Low)
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
1
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
1
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
Floor tiles - Floor
1
0
0
Chrysotile
1
1
4 m2
2 (Very Low)
1/Villa 3 - R14
Floor tiles - Floor
1
0
0
Chrysotile
1
1
4 m2
2 (Very Low)
Identified
1/Villa 3 - R18
Floor tiles - Floor
1
0
0
Chrysotile
1
1
4 m2
2 (Very Low)
Identified
0/Villa 3 - R18
Floor tiles - Floor
1
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
Sample Ref
Inspection
9
Identified
0/Villa 1 - R11
Floor tiles - Floor
1
0
0
Chrysotile
10
Identified
0/Villa 1 - R16
Floor tiles - Floor
1
0
0
9
Identified
0/Villa 1 - R17
Floor tiles - Floor
1
0
9
Identified
0/Villa 1 - R21
Floor tiles - Floor
1
9
Identified
0/Villa 1 - R5
Floor tiles - Floor
5
Identified
0/Villa Floor tiles - Floor 3Cupboar d4
4
Identified
1/Villa 3 - R13
4
Identified
4 5
Section 1 Oakleaf Technical Services 0845 293 7571
Flr/Room Description
Product Damage Treatmt
1651/9
Asbestos Type
Priotity Risk Score
Section 1: Page 2 of 4
Asbestos Material Risk Summary Report Site: A Hospital Site Block: A Building Accessibility Score
Qty
Materials Risk Score
1
1
4 m2
2 (Very Low)
Chrysotile
1
1
3 m2
2 (Very Low)
0
Chrysotile
1
1
4 m2
2 (Very Low)
0
0
Chrysotile
1
1
4 m2
2 (Very Low)
1
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
Floor tiles - Floor
1
0
0
Chrysotile
1
1
4 m2
2 (Very Low)
0/Villa 3 - R8
Floor tiles - Floor
1
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
Identified
1/Villa 3 - R9
Floor tiles - Floor
1
0
0
Chrysotile
1
1
4 m2
2 (Very Low)
5
Identified
0/Villa 3 - R9
Floor tiles - Floor
1
0
0
Chrysotile
1
1
3 m2
2 (Very Low)
8
Identified
0/Villa 1 - Ext
Cement boarding Canopy
1
0
1
Chrysotile
1
1
6 m2
3 (Very Low)
11
Identified
0/Villa 1 - R8
Cistern - Toilet cistern
1
0
0
Amosite
2
2
1 m2
3 (Very Low)
Sample Ref
Inspection
4
Identified
1/Villa 3 - R19
Floor tiles - Floor
1
0
0
Chrysotile
5
Identified
0/Villa 3 - R2
Floor tiles - Floor
1
0
0
4
Identified
1/Villa 3 - R4
Floor tiles - Floor
1
0
4
Identified
1/Villa 3 - R5
Floor tiles - Floor
1
5
Identified
0/Villa 3 - R6
Floor tiles - Floor
4
Identified
1/Villa 3 - R8
5
Identified
4
Section 1 Oakleaf Technical Services 0845 293 7571
Flr/Room Description
Product Damage Treatmt
1651/9
Asbestos Type
Priotity Risk Score
Section 1: Page 3 of 4
Asbestos Material Risk Summary Report Site: A Hospital Site Block: A Building Sample Ref
Inspection
Flr/Room Description
7
Identified
0/Villa 2 - Ext
13
Identified
14
Asbestos Type
Accessibility Score
Qty
Materials Risk Score
1
0
1
Chrysotile
1
1
4 m2
3 (Very Low)
0/Pigger Cement sheeting - Roof y
1
1
1
Chrysotile
1
1
45 m2
4 (Very Low)
Strongly presumed
1/Villa 1 - Ext
Cement Cowl - Roof
1
1
1
Chrysotile
1
0
<1 m2
4 (Very Low)
3
Identified
1/Villa 1 -Loft
Insulation - Insulation on tank
3
2
2
Amosite
2
3
3 m2
9 (Medium)
1
Identified
1/Villa 1 -Loft
Insulation - Residue on tank
2
3
2
Amosite
2
3
4 m2
9 (Medium)
2
Identified
1/Villa 1 -Loft
Debris - Debris on floor
3
3
3
Amosite
2
2
80 m2
11 (High)
Section 1 Oakleaf Technical Services 0845 293 7571
Cement boarding Canopy
Product Damage Treatmt
1651/9
Priotity Risk Score
Section 1: Page 4 of 4
Section 2: Asbestos Register Sheets
Section 2 Oakleaf Technical Services 0845 293 7571
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
12
Floor:
0
RoomNo:
Kitchen
No Photo Available
Description: Bitumen Pad - Under sink Extent: Inspection:
Identified
Last Inspection Date:
08/09/2010
Next Inspection Date:
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
0
Normal Occupant Activity
Damage:
0
Likelihood of Disturbance
Treatment:
0
Human Exposure Potential
Asbestos Type:
0
Maintenance Activity
Material Risk Score:
0
Priority Risk Score:
0
Recommendation No action required. Comments
No Asbestos Detected. No Action Required.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 1 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
6
Floor:
1
RoomNo:
Loft
No Photo Available
Description: Debris - Debris inside tank Extent: Inspection:
Identified
Last Inspection Date:
08/09/2010
Next Inspection Date:
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
0
Normal Occupant Activity
Damage:
0
Likelihood of Disturbance
Treatment:
0
Human Exposure Potential
Asbestos Type:
0
Maintenance Activity
Material Risk Score:
0
Priority Risk Score:
0
Recommendation No action required. Comments
No Asbestos Detected. No Action Required.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 2 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
13
Floor:
0
RoomNo:
Piggery
No Photo Available
Description: Cement sheeting - Roof 45 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Cement
Normal Occupant Activity
Damage:
1
Low Damage
Likelihood of Disturbance
Treatment:
1
Asbestos Cement
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
4
Very Low
Priority Risk Score:
0
Recommendation Remove and Clean. Comments Little used building to the rear of the site.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 3 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
8
Floor:
0
RoomNo:
Villa 1 - Ext
No Photo Available
Description: Cement boarding - Canopy 6 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Cement
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
1
Asbestos Cement
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
3
Very Low
Priority Risk Score:
0
Recommendation Label and Manage. Comments Soffits above entrance to Villa 1.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 4 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
14
Floor:
1
RoomNo:
Villa 1 - Ext
No Photo Available
Description: Cement Cowl - Roof <1 m2
Extent: Inspection:
Strongly presumed
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Cement
Normal Occupant Activity
Damage:
1
Low Damage
Likelihood of Disturbance
Treatment:
1
Asbestos Cement
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
4
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments High level cowl on roof.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 5 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
9
Floor:
0
RoomNo:
Villa 1 - R11
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 6 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
10
Floor:
0
RoomNo:
Villa 1 - R16
No Photo Available
Description: Floor tiles - Floor <1 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 7 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
9
Floor:
0
RoomNo:
Villa 1 - R17
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 8 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
9
Floor:
0
RoomNo:
Villa 1 - R21
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 9 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
9
Floor:
0
RoomNo:
Villa 1 - R5
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 10 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
11
Floor:
0
RoomNo:
Villa 1 - R8
No Photo Available
Description: Cistern - Toilet cistern 1 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
2
Amosite
Maintenance Activity
Material Risk Score:
3
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Low level toilet cistern.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 11 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
1
Floor:
1
RoomNo:
Villa 1 -Loft
No Photo Available
Description: Insulation - Residue on tank 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
2
Insulation Board
Normal Occupant Activity
Damage:
3
High Damage
Likelihood of Disturbance
Treatment:
2
Unsealed AIB/Encapsul
Human Exposure Potential
Asbestos Type:
2
Amosite
Maintenance Activity
Material Risk Score:
9
Medium
Priority Risk Score:
0
Recommendation Remove and Clean. Comments Asbestos debris found on water tank. Access to this area must be prohibited until clearance certificates are available.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 12 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
2
Floor:
1
RoomNo:
Villa 1 -Loft
No Photo Available
Description: Debris - Debris on floor 80 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
3
Thermal Insulation
Normal Occupant Activity
Damage:
3
High Damage
Likelihood of Disturbance
Treatment:
3
Unsealed Lagging and
Human Exposure Potential
Asbestos Type:
2
Amosite
Maintenance Activity
Material Risk Score:
11
High
Priority Risk Score:
0
Recommendation Remove and Clean. Comments Insulation debris found within the lift space. Access to this area must be prohibited until clearance certificates are available.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 13 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
3
Floor:
1
RoomNo:
Villa 1 -Loft
No Photo Available
Description: Insulation - Insulation on tank 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
3
Thermal Insulation
Normal Occupant Activity
Damage:
2
Medium Damage
Likelihood of Disturbance
Treatment:
2
Unsealed AIB/Encapsul
Human Exposure Potential
Asbestos Type:
2
Amosite
Maintenance Activity
Material Risk Score:
9
Medium
Priority Risk Score:
0
Recommendation Remove and Clean. Comments Asbestos insulation has been applied to the water tank. Access to this area must be prohibited until clearance certificates are available.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 14 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
7
Floor:
0
RoomNo:
Villa 2 - Ext
No Photo Available
Description: Cement boarding - Canopy 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Cement
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
1
Asbestos Cement
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
3
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Soffits above entrance to Villa 2 have been painted and labelled.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 15 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
5
Floor:
0
RoomNo: Villa 3 - Cupboard 4
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 16 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R13
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 17 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R14
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 18 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
5
Floor:
0
RoomNo:
Villa 3 - R18
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 19 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R18
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 20 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R19
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 21 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
5
Floor:
0
RoomNo:
Villa 3 - R2
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 22 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R4
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 23 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R5
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 24 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
5
Floor:
0
RoomNo:
Villa 3 - R6
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 25 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
5
Floor:
0
RoomNo:
Villa 3 - R8
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 26 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R8
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 27 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
5
Floor:
0
RoomNo:
Villa 3 - R9
No Photo Available
Description: Floor tiles - Floor 3 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 28 of 29
Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:
4
Floor:
1
RoomNo:
Villa 3 - R9
No Photo Available
Description: Floor tiles - Floor 4 m2
Extent: Inspection:
Identified
Last Inspection Date:
30/06/2010
Next Inspection Date:
30/06/2011
Asbestos Risk Assessment Material Score
Priority Score
Product Type:
1
Reinforced Composite
Normal Occupant Activity
Damage:
0
Good Condition
Likelihood of Disturbance
Treatment:
0
Composite Material
Human Exposure Potential
Asbestos Type:
1
Chrysotile
Maintenance Activity
Material Risk Score:
2
Very Low
Priority Risk Score:
0
Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.
Section 2 Oakleaf Technical Services 0845 293 7571
Report Number: 1651/9 Section 2: Page 29 of 29
Section 3: No Access Areas Report
Section 3 Oakleaf Technical Services 0845 293 7571
Asbestos No Access Areas Report Site: A Hospital Site Block: A Building Floor:
RoomNo:
Comments:
Recommendations:
Ext
High level access.
Further Investigation.
0
Villa 1 R7
Access could still not be gained into the cupboard.
Further Investigation.
1
Loft Villa 3
Limited access; loft space.
Further Investigation.
Section 3 Oakleaf Technical Services 0845 293 7571
Section 3: Page 2 of 2