Ventilation in balance TECHNICAL DATA AM: 100 · 300 · 500 · 800 · 900 · 1200
CV: 80
INTELLIGENT VENTILATION
4
Different needs
6
Supply air
8
The correct position
12
Construction and design
14
CONTROLS
Network
16
Features and controls
18
Control processes
22
Our philosophy is that our products should be the most energy efficient on the market.
INTELLIGENT VENTILATION
CONTENTS
EFFICIENT COOLING
Dedicated cooling unit
28
CC 300
29
CC 500
30
CC 800
31
PRODUCT INFORMATION
AM 100
2
32
AM 300
38
AM 500
44
AM 800
50
AM 900
56
AM 1200
64
CV 80
76
CV components
87
Roof penetration ducting and fittings
88
TECHNICAL DATA SUMMARY
92
3
INTELLIGENT VENTILATION VENTILATION IN BALANCE
HIGH HEAT RECOVERY
Fresh air is a human right. It is with this in mind
We use highly efficient countercurrent heat exchan-
that Airmaster has developed the market’s most
gers and is tested to European standard DS/EN3081,
energy-efficient low-noise decentralised ventilation
which is a dry effect under conditions where con-
solutions with heat recovery – ventilation solutions
densation from the exhaust air does not occur. Air-
that can be used in all types of rooms or buildings.
master’s countercurrent heat exchangers perform
INTELLIGENT VENTILATION
With Airmaster, you are not only choosing a responsible solution. You are also choosing a solution for the future.
up to approx. 85% measured as dry effect according Airmaster’s decentralised ventilation solutions
to EN308 and up to approx. 95% if condensation is
keep the energy consumption for ventilation in the
included.
building to a minimum. Ventilation is only activated in those rooms where it is required – when
MAJOR BENEFITS IN AIRMASTER SOLUTIONS
it is required. No wasted energy for unnecessary
• Energy-efficient
ventilation.
• Low noise levels 30 dB(A) • Cost-effective
LOW ENERGY CONSUMPTION
• Quick and easy to install
WITH HIGH RATE OF HEAT RECOVERY
• Efficient cooling unit available as optional extra
The decentralised heat recovery unit is placed in the room, close to an external wall. Very low energy consumption is achieved using a short distance for the external air to travel and the position of the heat exchanger. No need for long ventilation ducts – no additional energy consumption. Decentralised ventilation takes into account the requirements of each room saving on demanding complicated and costly installation. EFFICIENT EC MOTOR TECHNOLOGY
Airmaster uses energy-efficient EC motors ensuring low energy consumption, good regulation options and low-noise operation.
1
Testing conditions: Ambient temperature Room exhaust temperature Airflow test range Internal or external leakage
5°C 25°C 50-150% of nominal airflow <3% of nominal airflow. Supply and exhaust air is in balance. 5 5
CHOOSE THE RIGHT UNIT
WALL-MOUNTED UNITS
Airmaster products come in a wide range of diffe-
Airmasterâ&#x20AC;&#x2122;s wall-mounted units are available
rent variations and a range of intelligent controllers
in different models:
that respond to actual demands, making daily operation easier and reducing ventilation costs. Correct dimensioning of the system minimises energy consumption, while optimum control constantly
AM 100
100 m3/h at 35 dB(A) 75 m3/h at 30 dB(A) AM 300
300 m3/h at 35 dB(A) 240 m3/h at 30 dB(A) AM 500
550 m3/h at 35 dB(A) 430 m3/h at 30 dB(A) AM 800
725 m3/h at 35 dB(A) FLOOR MODEL (AM 900)
is located on the floor and
650 m3/h at 30 dB(A)
supplies air either at floor
AM 900
or ceiling level. Available
830 m3/h at 35 dB(A)
where supply and exhaust
690 m3/h at 30 dB(A)
is led horizontally through
monitors the need for ventilation.
CHOOSE THE RIGHT CAPACITY
INTELLIGENT VENTILATION
DIFFERENT NEEDS DIFFERENT UNITS
Whether you position a unit under the ceiling or standing on the floor, the same criteria apply: quick, flexible installation which can be adapted to the roomâ&#x20AC;&#x2122;s purpose, location and design.
the wall or vertically up
AM 1200
through the roof.
1310 m3/h at 35 dB(A) 1050 m3/h at 30 dB(A)
CV 80
85 m3/h at 30 dB(A)
HORIZONTAL MODEL Supply and exhaust is led
VERTICAL MODEL Supply and exhaust is led up
horizontally out through the wall on which the unit
vertically out through the roof. It is finished off on
is installed. The external wall is finished off with
the outside with roof caps and flashing.
louvered grilles.
6
Both horizontal and vertical models are available
FULLY DUCTED MODEL Supply air, extraction,
FLOOR MODEL (AM 1200) can be placed
with supply air in the middle or lower panel. This
intake and exhaust are ducted. Intake and exhaust
along the wall, against a wall or be free-
means that up to 2/3 of the unit can be integrated
can be placed in three different places on either
standing, e.g. as room divider.
in the ceiling.
the right or left side.
7
INTELLIGENT VENTILATION
SUPPLY AIR WITH COANDA EFFECT Correct selection and location of the unit ensures optimum supply air.
Cold air ‘sticks’ to the ceiling before it slowly descends – which is known as the Coanda effect. The Coanda effect means that the cooler fresh air is mixed with the surrounding air and then slowly descends in the room. THE SUPPLY AIR
The fresh air is supplied at relatively high speed, which grips the air in the room, and this ensures efficient mixing of the fresh air and the air in the room. This method ensures uniform air quality in the room while the supply air speed is reduced. This means that draughts do not occur.
Wall-mounted Airmaster ventilation
SUPPLY AIR FOR WALL-MOUNTED UNITS AM 100, 300, 500 and 800 are all wall-mounted units. The wall-mounted units all ventilate using the mixing principle where fresh air is supplied into the room near the ceiling using the Coanda effect.
Wall-mounted Airmaster ventilation with side view of supply air.
8
9
INTELLIGENT VENTILATION
SUPPLY AIR FOR FLOOR-MOUNTED UNITS The mixing principle is also used in Airmaster’s floor-mounted models (AM 900, AM 1200) where fresh air is supplied upwards in order to achieve the coanda effect. ADJUSTABLE SUPPLY
The floor-mounted models, AM 900 and AM 1200,
Floor-mounted AM 900 – mixing ventilation.
are equipped with adjustable grilles. The grilles can be adjusted as required to ensure the right throw, depending on the size of the room. The throw can easily be adjusted by changing the grilles area/ direction. THE DISPLACEMENT PRINCIPLE
If the unit should need to be moved to another
Floor-mounted AM 900 – displacement ventilation.
Airmaster’s floor-mounted model AM 900 is also
room, the grilles can simply be adjusted to the new
available in a displacement model. With the dis-
room. The depth of the room determines how much
placement principle, the fresh air is supplied into
the grilles needs to be adjusted.
the room at low speed at floor level and a couple of degrees lower than the temperature of the room. This means that the fresh air is distributed over the entire floor due to the difference in density between the cool and warm air. The low supply speed ensures that draughts do not occur. Floor-mounted AM 1200 placed perpendicular to the wall and used as a room divider. Airflow/direction is set using adjustable grilles.
The illustration shows two floor-mounted AM 1200s, one placed against the wall and the other placed perpendicular to the wall. The supply air viewed from the side.
10
Floor-mounted AM 900 – displacement ventilation.
11
3
such as light fittings installed directly in the ceiling, should be avoided. Light fittings should be lowered so that the supply air has free access to the room.
To get the full benefit of the Airmaster units, the units must be located correctly according to the physical geometry of the room.
4 1 2
Where people will be located in close physical proximity to a unit, it is important to use wallmounted or floor-mounted models using the mixing principle as this avoids the occurrence of draughts.
In a small, narrow room where the throw is too short lengthwise,
but too large the other way, two smaller units with shorter throw are a better option.
5
In a room with high or sloping ceilings,
If the room has ceiling
the units should be
beams that may obstruct
installed as high up
the airflow, a floor-mounted
as possible.
unit that ventilates using the
12
INTELLIGENT VENTILATION
THE CORRECT POSITION OF THE AM RANGE
To achieve the most efficient supply conditions, objects,
displacement principle (AM 900) or a wall-mounted unit that ventilates along the room should be chosen.
13
INTELLIGENT VENTILATION
CONSTRUCTION AND DESIGN
EPP is an abbreviation of expanded polypropylene. This material is a central part of several of Airmaster’s ventilation units such as AM 100 and CV 80.
Airmaster’s ventilation systems are well constructed, designed, and functional.
FLEXIBLE CONNECTION CUBE
Airmaster has developed two ventilation units (AM 100 and CV 80) which have been designed in an EPP construction. A complete EPP construction comprises three sections – a filter section, a motor section and an exchanger section. These can be combined in either a right or a left model. All unit parts and components are installed in or on the moulded EPP
MOTORISED BYPASS DAMPER
sections which are finally assembled into one tight and closed unit. Due to the excellent insulation properties of the material, undesirable heat transfer between airflows in the unit is minimized. This means, for example, that ‘thermal bridges’ and unwanted condensation do not occur in the construction. This ensures the desired heat transfer is concentrated between the airflows in the heat exchanger under controlled conditions.
HEAT EXCHANGER AND CONDENSATE TROUGH with float switch.
EPP – Expanded polypropylene We use a plastic foam material whose proper-
During the moulding of the parts, emphasis is
ties make it an extremely good material for use
on installation flexibility, compact design and
in ventilation systems.
optimisation of the airflows in the unit. The latter reduces the internal pressure loss in the
EPP is produced according to environmentally
unit and thereby also energy consumption for
friendly methods and is labelled for recycling.
air transport. The density of the material also
The sections are moulded into special moulds
contributes to ensuring that each EPP section
using compressed air and water vapour.
remains light. AM 100 ventilation units with EPP construction which include all components and which insulate perfectly against unwanted heat loss.
14
EC-MOTOR-POWERED FAN
15
CONTROLS
NETWORK WITH AIRMASTER
The figure shows a Master/Slave System with a central control panel and two sensors, e.g. PIR and CO2 sensors, in each room.
N
BMS SYSTEM
Network control can be carried out using Airmaster’s BMS system (Master/Slave) where up to 16 units can be controlled from a single control panel. BMS is an abbreviation of Building Management System.
With a BMS network all the advantages of
Airmaster’s functionality in an existing BMS
decentralised ventilation can be retained. At
system:
the same time, the administrative benefits of
• Unit start/stop
centralised control can be utilised. Airmaster
• Adjusting set points for supply tempera-
supports various types of BMS system:
ture and air volume • Releasing night cooling
• KNX® • BACnetTM/IP • BACnet
TM
MS/TP
• LON® • MODBUS® RTU RS485
• Reading of temperature sensor data, including room and supply temperatures • Bypass position; if the unit is equipped with automatic modulating bypass, readings can be taken of its position
In order to utilise the various BMS systems,
• Alarm (e.g. filter alarm)
all Airmaster units must be equipped with or
• Monitoring of cooling unit (if installed)
ordered with a plug-in module for the BMS
• Unit status
system concerned. Different types of units
• CO2 sensor, including reading CO2 levels
are available and are installed individually according to local requirements. The units control themselves within the programme framework – depending on local operating conditions.
AIRMASTER BMS
from a connected CO2 sensor • PIR sensor, including reading PIR signal from a connected PIR sensor • Remote diagnosis using detailed operational data for each unit via the BMS system – and thereby reducing service costs
Airmaster ventilation products can be easily controlled from a PC and integrated with the
Flexibility is key in Airmaster’s newly developed
Division of the system into groups with one or more
rest of the building automation system. A
BMS system.
units with shared controls optimises the use of unit
local computer can be used to retain a full
size and sensors.
overview of operations and temperature
Our system controls and monitors up to 16 different
N
and provides the option of programming the
ventilation units using a single control panel. Diffe-
Controlling the system using a single sensor (e.g.
rent types of unit with various kinds of accessories
CO2 sensor) or a combination (e.g. a PIR and a CO2
can be controlled by this panel. Cooling units can
sensor) is also an option. By using sensors, it is en-
also be connected to any of the units as required.
sured that the basic operating parameters for each
These flexible options mean that units with diffe-
unit, group or system can be overridden.
rent outputs and equipment can be linked to form a single system while individual requirements in each
Individual control, monitoring and programming as
room can still be catered for.
well as programming of common parameters are
units based on the purpose of the rooms.
The figure shows a generic BMS system with a central BMS computer which is linked to all Airmaster units and sensors.
carried out from a single control panel. Connection to a building network (BMS system) is, of course, also possible.
16
17
The fully automated intelligent control software
Airmaster’s ventilation system can be optimised
used in Airmaster’s ventilation units allows the
for local operating conditions using the features
units to be used immediately after installation;
below:
CONTROLS
BASIC FEATURES AND CONTROLS
Control panel Airmaster supplies units with control panels as standard. The control panel is used for daily operation and for programming the unit.
all basic features are pre-programmed from the factory.
• Manual start and stop via the control panel • Automatic operation using programmed weekly
The control software is capable of automatically counteracting both high and low supply temperatures to ensure the desired room temperature.
schedule • Background ventilation as constant basic ventilation with reduced minimum airflow
Effective protection features prevent the freezing of
• Free night cooling
the heat exchanger, removes condensate and auto-
• Automatic bypass control
matically stops the unit, if required. This prevents
• Start and stop using external switches such as
unnecessary damage to the unit.
thermostat and hygrostat • Start and stop using motion (PIR) sensor
Customised requests from the customer or local conditions can easily be set in the controls and programmed immediately. If required, the software
• CO2 sensor either to start and stop the unit or control the airflow • Automatic operation using a BMS system
controls the installed option automatically, such as bypass, heating surface, condensate pump, cooling unit and various sensors (CO2, humidity, motion etc.).
NEWS NEW CONTROL PANELS We will be introducing two new control panels in the autumn of 2012
18
19
CONTROLS
Airmasterâ&#x20AC;&#x2122;s CO2 sensors adapt ventilation to CO2 levels in the room. This saves both energy and operating hours in rooms, e.g. in schools.
PIR/MOTION SENSOR Ensures that energy consumption is as low as possible by only starting up the ventilation if there is movement in the room. The unit will run until a delay has elapsed. This can be set in the controller.
HUMIDITY SENSOR Ensures that the indoor humidity is under control. Is supplied as an option for either wall mount or all ready installed in the unit.
START, STOP AND CONTROL
START, STOP AND CONTROL
START, STOP AND CONTROL
USING A CO2 SENSOR
USING A MOTION SENSOR (PIR)
USING AN HUMIDITY SENSOR
The CO2-sensor is used to start and stop the unit, as
The ventilation unit has been set to start/stop via a
A hygrostat registers the relative humidity of the air
well as controlling the accurate airflow needed to
signal from a PIR sensor. When a signal is received
and then sends a start/stop signal to the ventilation
secure the optimum air quality as discribed in the
from the PIR sensor, i.e. movement in the sensorâ&#x20AC;&#x2122;s
system. The humidity level of the sensor can be
measurement area, the unit will start. The system
preset. The hygrostat contains artificial hygrosco-
will start in standard operation with the associated
pic fibres whose length depend on the relative hu-
The Airmaster unit starts with the programmed
programmed airflow and supply temperature.
midity of the air. When the required relative humi-
minimum airflow (min) when the CO2 level exceeds
When the signal stops, the unit will stop after the
dity is exceeded/not reached, the humidity sensor
the programmed lower limit plus 10% (A+10%). The
end of the pre-programmed timer delay (factory-set
sends a start/stop signal to the ventilation unit. This
at 30 minutes). PIR control is often used to activate
is often used to activate full operation on systems
mum (max) at the upper limit of CO2 (B) and above.
full operation on systems running basic ventilation
running basic ventilation when the required relative
If the CO2 level drops back below the programmed
when no one is present in the building.
humidity is exceeded.
CO2 SENSOR - WALL-MOUNTED Is used to secure energy efficient ventilation on demand, which automatically adjust the airflow to suit the desired air-quality in each room.
figures below.
CO2 SENSOR - INTEGRATED Is supplied as an option to be installed in the unit.
FIGURE 1
max
min
unit then increases the airflow linearly to the maxi-
0
lower limit (A), the unit will stop automatically
0
A A+10%
0
A
B
(Figure 1). When the system runs on a reduced airflow (basic
FIGURE 2
max
ventilation), the control software is able to adapt the airflow. When the lower limit of CO2 (A) is exceeded, the airflow is increased linearly to the maximum (max). If the CO2 level drops back below the
min
programmed lower limit (A), the control software will return to the programmed basic ventilation (Figure 2).
0
B
All the above parameters can be adapted and programmed in the control software.
20
21
CONTROLS
IMPORTANT CONTROL PROCESSES
Programming of Airmaster’s products builds on many years’ experience of control and regulation of highly efficient decentralised ventilation units.
We supply units across Europe. We know that our
heat exchanger. The condensate is captured in a
FROST PROTECTION
the heat exchanger. To maintain balanced ventila-
units have to be able to work effectively under very
condensate trough. A float automatically registers
When the outdoor temperature approaches fre-
tion the control software monitors the temperature
different outside temperatures – outdoor tempe-
high condensate levels in the trough. The controls
ezing, the exhaust temperature behind the counter-
conditions in the unit. This takes place by activating
ratures from around -25°C up to around 35°C. A
stop the supply and increase extraction whereby
current heat exchanger drops. This may result in
the preheating surfaces, if required.
combination of humid air and frost and changing
the condensate evaporates and is emitted with the
the condensate freezing inside the heat exchan-
weather conditions are often regular occurrences.
exhaust air. Alternatively, a drain can be connected
ger. The control software efficiently prevents the
to the condensate trough to lead condensate away
formation of ice by increasing the exhaust air and
WITH ELECTRICAL COMFORT HEATING SURFACE
from the unit.
reducing the supply air. The exhaust temperature
In units CV 80, AM 100 and AM 300, ice formation
then rises again. If this process is not sufficient to
protection is carried out using a high-capacity elec-
The various fully automatically control processes are described below.
FROST PROTECTION USING VIRTUAL PREHEAT
CONDENSATE PUMP
prevent the formation of ice in the heat exchanger,
trical comfort heating surface. By using the bypass
CONDENSATE
The ventilation unit can be equipped with a con-
the control software is able to protect the unit by
damper, some of the outdoor air is made to bypass
With a high rate of heat recovery of up to 95%,
densate pump that pumps away the condensate be-
stopping operation.
the countercurrent heat exchanger. The outdoor air
the exhaust air is cooled down significantly in the
fore the control software increases exhaust air and
countercurrent heat exchanger. This means that the
stops further supply. A condensate pump is always
FROST PROTECTION WITH
to the required supply temperature. The exhaust
humidity in the exhaust air can condensate in the
recommended for a cooling unit.
ELECTRICAL PREHEATING SURFACE
air is cooled less in the heat exchanger and the
Ventilation units AM 500, AM 800, AM 900 and AM
formation of ice in the heat exchanger is prevented.
1200 can be equipped with an electrical preheating
In AM 300, this function can also be carried out by
surface. This preheating surface warms up the out-
a water heating surface. Find out more about com-
side air before it is supplied into the countercurrent
fort heating surfaces in the following sections.
is then warmed up by the comfort heating surface
heat exchanger to prevent the formation of ice in
FLOAT Integrated float warning of condensate forming and not being drained off.
22
CONDENSATE PUMP Integrated condensate pump option – factory-fitted
ELECTRICAL PREHEATING SURFACE Preheating surface option for use in very cold areas.
SAFETY Thermostats automatically disconnect power at excessively high temperatures.
23
CONTROLS
IMPORTANT CONTROL PROCESSES LOW SUPPLY TEMPERATURE,
ELECTRICAL COMFORT HEATING SURFACE
WATER HEATING SURFACE
COMFORT HEATING SURFACE
The electrical comfort heating surface for AM 500,
A water heating surface can be installed on units
FROST PROTECTION OF WATER HEATING SURFACE
To achieve optimum heat recovery Airmasterâ&#x20AC;&#x2122;s
AM 800, AM 900 and AM 1200 warms up the intake
AM 300, AM 500, AM 800, AM 900 and AM 1200
The water heating surface is equipped with a sepa-
ventilation units are equipped with highly efficient
air after the countercurrent heat exchanger to the
as an alternative to an electrical comfort heating
rate, self-controlling heating valve from the factory
countercurrent heat exchangers. Comfort heating
set supply temperature, if required. The control
surface. This also ensures the required supply tem-
to ensure a minimum temperature even when the
surfaces, which are available for all Airmaster units,
software regulates the temperature in the unit
perature. The large surface of the heating surface
ventilation unit is switched off. To frost-proof the
are therefore only used to replace the minimum
and automatically activates the comfort heating
ensures excellent transfer of heat energy to the
heating surface all nominal values are pre-pro-
heat loss during ventilation. Balanced ventilation
surface, if required. In units CV 80, AM 100 and
intake air.
grammed in the control software. This means that
is maintained as standard as long as the supply
AM 300 a high-capacity comfort heating surface is
temperature stays within acceptable limits.
used. This simultaneously takes over the function
The control software starts and stops the heating
of the preheating surface. See also Frost Protection
surface using a motor-powered valve. The heating
Without comfort heating surface: If the required
using Virtual Preheat with Electrical Comfort Heat-
surface settings are programmed when the ventila-
supply temperature cannot be maintained, the
ing Surface on page 23.
tion unit is put into service. The heating surfaces is
the heating surface is protected against frost and is
controls will reduce the intake airflow and increase
supplied with the ventilation unit as a fully inte-
extraction. This compensates for a low outdoor
grated unit. This means that connection to the local
temperature. This function is also activated if the
heating system is simple and quick.
always in working order.
capacity of the comfort heating surface is being fully utilised. To increase comfort, a comfort heating surface can be used to maintain the balance between intake and exhaust â&#x20AC;&#x201C; even in extremely low outdoor temperatures.
ELECTRICAL COMFORT HEATING SURFACE
24
WATER HEATING SURFACE Reversible comfort heating surface available as an optional extra.
WATER HEATING SURFACE in copper and aluminium to ensure good heat transfer and durability.
THERMOSTAT VALVE AND THERMO ACTUATOR The thermo actuator regulates the amount of water in steps according to supply temperature. The thermostat valve works as frost protection.
25
CONTROLS
IMPORTANT CONTROL PROCESSES
Airmaster’s comfort cooling unit (CC) for the AM product range completes the market’s most flexible ventilation system.
AUTOMATIC BYPASS
If the supply temperature exceeds the required level, the control software activates the bypass, in the ventilation unit, in steps. This means the cooler outdoor air bypasses the countercurrent heat exchanger (in unit AM 800 warmer exhaust air bypasses the exchanger). The required supply temperature is thus maintained. If the room temperature rises, e.g. during direct sun, above the required maximum supply temperature, the bypass is likewise activated automatically. The control software can also be set to a new supply temperature to achieve a higher cooling effect. If a cooling unit has been installed in the ventilation unit and cooling with outdoor air is not sufficient, the control software automatically activates the cooling unit. During operation of the cooling unit, the bypass is still used to regulate the supply temperature. NIGHT-TIME COOLING
CC COOLING UNIT
If the automatic bypass function is not sufficient
CC Cooling unit
to keep the supply or room temperature at the
If the room temperature exceeds the required maxi-
required level, efficient temperature reduction can
mum level during the day, all Airmaster ventilation
be achieved by installing a cooling unit. The control
units are automatically able to cool the room using
software activates the cooling unit automatically
the cooler night air. This function is called ‘nighttime cooling’. Should it be required, the function uses both the bypass damper and the cooling unit to achieve the required cooling effect. The building and its fittings are cooled, and the room temperature will rise less on the following
when required. The self-regulating cooling unit AM ventilation unit
reduces the temperature of the outside air by up to 15°C before the air is supplied into the ventilation unit. The supply temperature is also regulated using the automatic bypass function. See also the section on cooling units on page 28.
day. All associated parameters are factory-set, but can be adapted.
26
27
CC 300 COOLING CAPACITY (W)
TECHNICAL DATA
2400
Maximum cooling capacity
2314 W
Refrigerant
R134a
2000
Filling
0,310 kg
1800
Operating current
3,6 A
Airmaster's dedicated cooling units (CC) are com-
The cooling unit is designed to reduce the tempe-
Power consumption
868 W
patible with the full range of Airmaster's horizontal
rature of the fresh air by up to 15°C. The units are
Electrical connection
1x230 V AC 50 Hz
models, LON®, MODBUS® RTU RS485, BACnetTM
dimensioned for European conditions (outdoor
Duct connection
Ø200 mm
MS/TP, BACnetTM/IP, KNX® and the individual
temperature of 35°C, 40% relative humidity) based
Condensate drain
Ø16 mm
control panels, which together make Airmaster ven-
on standard DS/EN 14511-2. The cooling unit is ex-
De-icing interval
2h
tilation systems an efficient, economic and future-
cluded from the Pressure Equipment Directive (PED)
De-icing period
5°C or 10 min.
proof solution.
under the terms of Article 1 3.6.
Net weight
55 kg
COP value
2,6
Leakage current
<– 2 mA
Condensate pumps are available for all cooling units.
COMFORT COOLING
DEDICATED COOLING UNITS
2200
1600 1400 1200 1000 18
20
22
24
26
28
30
32
34
36
Outdoor temperature(°C)
Panels, front
AM 300 H (HORIZONTAL) WITH CC 300 AM ventilation unit
CC Cooling unit Panels, side
Wall frame
28
29
Maximum cooling capacity
4065 W
Refrigerant
R407c
Filling
0,700 kg
Operating current
4,4 A
Power consumption
1033 W
COOLING CAPACITY (W)
TECHNICAL DATA
4500 4000 3500 3000 2500 2000 1500 1000 500
Maximum cooling capacity
5622 W
Refrigerant
R407c
Filling
0,950 kg
Operating current
10,8 A
Power consumption
1991 W
Electrical connection
1x230 V AC 50 Hz
Duct connection
Ø315 mm
Condensate drain
Ø16 mm
Electrical connection
1x230 V AC 50 Hz
Duct connection
Ø250 mm
Condensate drain
Ø16 mm
De-icing interval
2h
De-icing interval
2h
De-icing period
5°C or 10 min.
De-icing period
5°C or 10 min.
Net weight
71,4 kg
Net weight
86 kg
COP value
4,2
COP value
2,82
Leakage current
<– 2 mA
Leakage current
<– 2 mA
AM 500 H (HORIZONTAL) WITH CC 500
30
CC 800 COOLING CAPACITY (W)
TECHNICAL DATA
COMFORT COOLING
CC 500
0 15
20
25
30
Outdoor temperature °C
35
40
6000 5000 4000 3000 2000 1000 0 15
20
25
30
35
40
Outdoor temperature °C
AM 800 H (HORIZONTAL) WITH CC 800
31
The ideal unit for small rooms such as offices for one or two people etc. The low noise level ensures that the unit is not noticeable.
75 m³/h
Maximum capacity at 35 dB(A)
100 m³/h
Throw (0,2 m/s)
3.5 m. at 75 m³/h
the newest of our decentra-
5.5 m. at 100 m³/h
lised ventilation units with heat recovery. AM 100 is dimensioned for an airflow of up to ap-
Electrical connection
1 ~ 230 V + N + PE / 50 Hz
prox. 100 m3/h at a noise level
Duct connections
Ø125 mm
of only 35 dB(A) at a distance
Condensate drain
Ø16 mm
of 1 metre and is thus perfect
Weight
42 kg
Heat exchanger
Countercurrent heat exchanger (aluminium)
Filter
F5 Standard, F7 Optional
Colour
Panels RAL 9010 (white)
AM 100 is also available with
Current
0.15 A
an F7 intake air filter. With
Supply cable
1.5 mm²
an F7 intake air filter and
Maximum power consumption by 30 dB(A)
21 W
Maximum power consumption by 35 dB(A)
27.5 W
Leakage current
<– 1 mA
for ventilation in smaller rooms such as offices etc.
parameter adjustment, the unit provides balanced ventilation. With an F7 intake air filter, the maximum air volume is reduced by approx. 5%.
ELECTRICAL HEATING SURFACE (OPTIONAL) Heating element
1 x 230 V
Heating capacity
500 W
Thermal cut-out, automatic reset
70°C
Thermal cut-out, manual reset
120°C
STANDARD & OPTIONAL FEATURES
VERTICAL MODEL
HORIZONTAL MODEL
Bypass
x
x
Electrical heating surface (preheating)
–
–
Electrical heating surface (comfort heating)
•
•
Water heating surface (comfort heating)
–
–
CO2 sensor (wall-mounted)
Condensate pump
• • • • • •
• • • • • •
Cooling unit
–
–
Motorised exhaust damper
x
x
Motorised main damper
x
x
Countercurrent heat exchanger (aluminium)
x
x
CO2 sensor (integrated) PIR/motion sensor Humidity sensor Thermostat
x : standard
32
AM 100 is the smallest and also
Maximum capacity at 30 dB(A)
PRODUCT INFORMATION AM 100
AM 100
TECHNICAL DATA
• : optional
– : not available
33
AM 100 SCHEMATIC DIAGRAM - LEFT
AM 100 SOUND PRESSURE LEVEL (dB(A))
100
35
90
33
80 70
INTAKE
31
35 dBA
EXHAUST
29
60
27
30 dBA
50
25
40
23
30
21
20
19
10 20
30
40
50
60
70
80
90
OT
17
100
30
40
50
Airflow (m3/h)
60
70
80
90
100
BP
Airflow (m3/h)
AM 100 POWER CONSUMPTION (W)
ET HE
MD
IF
AM 100 SFP W/(m3/s)
FT
1300
28 26 24
1200
CT
22 20
1100
18 16
1000
14
900
30
40
50
60
70
80
90
30
100
40
50
AM 100 TEMPERATURE EFFICIENCY (%)
25
30
35
40 45
50
55
60 65
70
80
90
100
MD IT
EXTRACTION
70
F1
CH*
AM 100 EXTERNAL PRESSURE DROP (Pa)
91 90 89 88 87 86 85 84 83 82 81 80 20
60
CP*
BP
Airflow (m3/h)
Airflow (m3/h)
15
RT FL
EF
12 10
F2
PRODUCT INFORMATION AM 100
AM 100 CAPACITY (%)
75
120 110 100 90 80 70 60 50 40 30 20 10 0
80 85 90 95 100 105
35 dBA 30 dBA
INLET 30
Airflow (m3/h)
40
50
60
70
80
90
100
110
Airflow (m3/h)
AM 100 THROW (0.2 m/s) 0m
10m
The Airmaster units provide different air throw lengths depending on supply air volume. The blue tones on the illustration on the left show the airflow at different throws.
1
1
AM 100
2
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) BP Bypass damper
HE CT CP FT RT/FL OT
Countercurrent heat exchanger Condensate tray Condensate pump Float Room temperature sensor/flow sensor Outdoor temperature sensor
ET CH IT
Exhaust temperature sensor Comfort heating surface Inlet temperature sensor
Throw viewed from above Throw viewed from the side
2
75 m3/h 100 m3/h
34
35
AM 100 V (VERTICAL) - RIGHT
AM 100 H (HORIZONTAL) - LEFT
AM 100 V (VERTICAL) - LEFT
PRODUCT INFORMATION AM 100
36
AM 100 H (HORIZONTAL) - RIGHT
37
On the AM 300, the electrical
Maximum capacity at 30 dB(A)
240 m³/h
Maximum capacity at 35 dB(A)
300 m³/h
Throw (0.15 m/s)
4.8 m. at 160 m³/h
heating surface can be used as a Virtual Preheater (VPH). With the help of a bypass, a VPH
5.7 m. at 220 m³/h
allows some of the cold fresh
6.5 m. at 300 m³/h
air to be guided around the
Electrical connection
1 ~ 230 V + N + PE / 50 Hz
heat exchanger directly into the
Duct connections
Ø200 mm
heating element. This protects
Condensate drain
Ø16 mm
Weight
49.8 kg
Heat exchanger
Countercurrent heat exchanger (aluminium)
Filter
F5 Standard, F7 Optional
Colour
Panels RAL 9010 (white)
Current
0.6 A
Supply cable
1.5 mm²
Maximum power consumption
100 W
Leakage current
<– 3 mA
PRODUCT INFORMATION AM 300
AM 300
TECHNICAL DATA
the unit against icing up, even at very low outside temperatures.
WATER HEATING SURFACE (OPTIONAL)
Once the temperature and CO2 level of the room become too high, the sense of well-being decreases and productivity drops. There is also an increased risk of absence through illness.
Maximum operating temperature
90°C
Maximum operating pressure
10 bar
Heating capacity
400 W*
Pipe connection
3/8" (DN 10)
Material of pipes/louvres
copper/aluminium
Opening/closing time of motorised valve
< 60 s
* Capacity at flow/return water temperature of 70/40°C, Qw = 15 l/h
ELECTRICAL HEATING SURFACE (OPTIONAL) Heating elements
1 x 230 V
Heating capacity
1500 W
Thermal cut-out, automatic reset
70°C
Thermal cut-out, manual reset
120°C
STANDARD & OPTIONAL FEATURES
VERTICAL MODEL
HORIZONTAL MODEL
Automatic bypass (past heat exchanger)
•
•
Electrical heating surface (preheating)
–
–
Electrical heating surface (comfort heating) VPH
Condensate pump
• • • • • • • •
Cooling unit
–
• • • • • • • • •
Motorised exhaust damper
–
–
Motorised main damper
x
x
Countercurrent heat exchanger (aluminium)
x
x
Water heating surface (comfort heating) CO2 sensor (wall-mounted) CO2 sensor (integrated) PIR/motion sensor Humidity sensor Thermostat
x : standard 38
• : optional
– : not available 39
AM 300 SOUND PRESSURE LEVEL (dB(A))
PRODUCT INFORMATION AM 300
AM 300 CAPACITY (%)
AM 300 SCHEMATIC DIAGRAM
40
100 30 dBA
80
35
35 dBA
T=0,9 s
60 30
40
35 dBA: the same with cooling unit
20
25
PI
ED
20
0 60
100
140
180
220
260
INTAKE
EXHAUST
T=0,6 s
140
300
160
180
200
220
240
260
280
300
Airflow (m3/h)
Airflow (m3/h)
OT
PE
FI
F2 AM 300 POWER CONSUMPTION (W)
AM 300 SFP W/(m3/s)
140
1600
120
1400 1200
100 with cooling unit
MD
ET
with cooling unit
1000
80
IF
800
60
EF
BP
HE
EXTRACTION
600
40
400
20
200
0
0 60
100
140
180
220
260
300
RT FL 60
100
140
Airflow (m3/h)
180
220
260
300
Airflow (m3/h)
CT
FT
CP AM 300 TEMPERATURE EFFICIENCY (%)
AM 300 EXTERNAL PRESSURE DROP (Pa)
88
200
+
87
IT
150
86 85
CH
100
84 83
INLET
50
82 81
0 60
100
140
180
220
260
140
300
Airflow (m3/h)
160
180
200
220
240
260
280
300
Airflow (m3/h)
AM 300 THROW (0.15 m/s) 0m
10m
The Airmaster units provide different air throw lengths depending on supply air volume. The blue tones on the illustration on the left show the airflow at different throws.
1
1
AM 300
2
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) ED Exhaust damper (overpressure)
BP HE CT CP FT RT/FL OT
Bypass damper Countercurrent heat exchanger Condensate tray Condensate pump Float Room temperature sensor/flow sensor Outdoor temperature sensor
ET PI PE CH IT
Exhaust temperature sensor Connection for pressure gauge for airflow-measurement, inlet Connection for pressure gauge for airflow-measurement, extraction Comfort heating surface Inlet temperature sensor
Throw viewed from above Throw viewed from the side
2
160m3/h 220m3/h 300m3/h
40
41
AM 300 V (VERTICAL)
PRODUCT INFORMATION AM 300
AM 300 H (HORIZONTAL)
AM 300 HB (HORIZONTAL) - INLET BOTTOM If the unit is to be installed in a room where air humidity level is high, we recommend connecting the unitâ&#x20AC;&#x2122;s integrated condensate drain or adding a condensate pump (se page 22). It is also possible to connect ductwork to either supply or extract or both.
42
43
The AM 500 is designed
Maximum capacity at 30 dB(A)
430 m³/h
Maximum capacity at 35 dB(A)
550 m³/h
Throw (0.15 m/s)
5 m. at 350 m³/h
for medium-sized rooms. A horizontal or vertical model is installed, depending on the
5.9 m. at 450 m³/h
type of room and the posi-
7.5 m. at 550 m³/h
tioning of the unit. The unit is
Electrical connection
1 ~ 230 V + N + PE / 50 Hz
available with the Airmaster
Duct connections
Ø250 mm
control panel, but it can also be
Condensate drain
Ø16 mm
Weight
100.6 kg
Heat exchanger
Countercurrent heat exchanger (aluminium)
Filter
F5 Standard, F7 Optional
Colour
Panels RAL 9010 (white)
Current
1.1 A
Supply cable
1.5 mm²
Maximum power consumption
132 W
Leakage current
<– 6 mA
PRODUCT INFORMATION AM 500
AM 500
TECHNICAL DATA
connected to a BMS system. The CC module is a often used option. (optional item – for more information, see pages 28-31).
WATER HEATING SURFACE (OPTIONAL)
Investigations repeatedly confirm that poor indoor climate inhibits learning – as do noisy ventilation systems.
Maximum operating temperature
90°C
Maximum operating pressure
10 bar
Heating capacity
800 W*
Pipe connection
3/8" (DN 10)
Material of pipes/louvres
copper/aluminium
Opening/closing time of motorised valve
< 60 s
* Capacity at: flow/return temperature of 70/40°C, volume of water 25 l/h
ELECTRICAL HEATING SURFACE (OPTIONAL) Heating element
PREHEATING
COMFORT HEATING
1 x 230 V
1 x 230 V
Heating capacity
1000 W
630 W
Thermal cut-out, automatic reset
70°C
70°C
Thermal cut-out, manual reset
120°C
120°C
STANDARD & OPTIONAL FEATURES
VERTICAL MODEL
HORIZONTAL MODEL
Bypass
Condensate pump
• • • • • • • • • •
Cooling unit
–
Motorised exhaust damper
•
• • • • • • • • • • • •
Motorised main damper
x
x
Auto close for motorised main damper
•
•
Countercurrent heat exchanger (aluminium) x
x
Electrical heating surface (preheating) Electrical heating surface (comfort heating) Water heating surface (comfort heating) CO2 sensor (wall-mounted) CO2 sensor (integrated) PIR/motion sensor Humidity sensor Thermostat
x : standard 44
• : optional
– : not available 45
AM 500 SOUND PRESSURE LEVEL (dB(A))
100
PRODUCT INFORMATION AM 500
AM 500 CAPACITY (%)
AM 500 SCHEMATIC DIAGRAM
40
80
35
35 dBA with cooling unit
30 dBA
60
INTAKE
EXHAUST
T=0,9 s
35 dBA
30
40
T=0,6 s
PI
25
20
50
100
150
200
250
300
350
400
450
500
200
550
OT
ED
20
0
250
300
350
400
450
500
550
PE
PH
Airflow (m3/h)
Airflow (m3/h)
FI
F2 AM 500 POWER CONSUMPTION (W)
IF
AM 500 SFP W/(m3/s)
160
1600
140
1400
with cooling unit
120
ET
1200
100
1000
80
800
60
600
40
400
20
200
0 50
150
250
350
450
MD
HE
with cooling unit
RT FL 50
150
250
Airflow (m3/h)
350
450
550
Airflow (m3/h)
FT
CT CP
AM 500 EXTERNAL PRESSURE DROP (Pa)
94
EXTRACTION
0
550
AM 500 TEMPERATURE EFFICIENCY (%)
EF
BP
CH
+
200
IT
92
150
90 88
100
86 84
INLET
50
82
0
80 50
100
150
200
250
300
350
400
450
500
50
550
100
150
200
250
300
350
400
450
500
550
Airflow (m3/h)
Airflow (m3/h)
AM 500 THROW (0.15 m/s) 0m
10m
The Airmaster units provide different air throw lengths depending on supply air volume. The blue tones on the illustration on the left show the airflow at different throws.
1
1
AM 500
2
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) ED Exhaust damper (overpressure)
BP HE CT CP FT RT/FL OT
Bypass damper Countercurrent heat exchanger Condensate tray Condensate pump Float Room temperature sensor/flow sensor Outdoor temperature sensor
ET PI PE CH PH IT
Exhaust temperature sensor Connection for pressure gauge for airflow-measurement, inlet Connection for pressure gauge for airflow-measurement, extraction Comfort heating surface Preheating surface (optional) Inlet temperature sensor
Throw viewed from above Throw viewed from the side
2
350m3/h 450m3/h 550m3/h
46
47
AM 500 V (VERTICAL)
If the unit is to be installed in a room where air humidity level is high, we
AM 500 HB (HORIZONTAL) - INLET BOTTOM
PRODUCT INFORMATION AM 500
AM 500 H (HORIZONTAL)
recommend connecting the unitâ&#x20AC;&#x2122;s integrated condensate drain or adding a condensate pump (se page 22). It is also possible to connect ductwork to either supply or extract or both.
48
49
Human beings are sensitive to changes in the air: There has to be a natural equilibrium between the temperature, oxygen and CO2 content for us to feel comfortable.
AM 800 is designed for larger
Maximum capacity at 30 dB(A)
650 m³/h
Maximum capacity at 35 dB(A)
725 m³/h
Throw (0.15 m/s)
6.5 m at 500 m³/h
rooms involving moderate demand, and is therefore the perfect choice for classrooms.
7.4 m at 600 m³/h
A horizontal or vertical model
8.1 m at 700 m³/h
is installed, depending on the
Electrical connection
1 ~ 230 V + N + PE / 50 Hz
type of room and the posi-
Duct connections
Ø315 mm
tioning of the unit. The unit is
Condensate drain
Ø16 mm
Weight
131.2 kg
Heat exchanger
2 countercurrent exchangers (aluminium)
Filter
F5 Standard, F7 Optional
Colour
Paneler RAL 9010 (white)
Current
1.0 A
Supply cable
1.5 mm²
Maximum power consumption
156 W
Leakage current
<– 6 mA
available with the Airmaster control panel, but it can also be
PRODUCT INFORMATION AM 800
AM 800
TECHNICAL DATA
connected to a BMS system. The CC module is an often used option. (optional item – for more information, see page 28-31).
WATER HEATING SURFACE (OPTIONAL) Maximum operating temperature
90°C
Maximum operating pressure
10 bar
Heating capacity
1100 W*
Pipe connection
1/2" (DN 15)
Material of pipes/louvres
copper/aluminium
Opening/closing time of motorised valve
< 60 s
* Capacity at: delivery/return temperature of 70/40°C, volume of water 32 l/h
ELECTRICAL HEATING SURFACE (OPTIONAL) Heating element
PREHEATING
COMFORT HEATING
1 x 230 V
1 x 230 V
Heating capacity
1500 W
1000 W
Thermal cut-out, automatic reset
70°C
70°C
Thermal cut-out, manual reset
120°C
120°C
STANDARD & OPTIONAL FEATURES
VERTICAL MODEL
HORIZONTAL MODEL
Bypass
Condensate pump
• • • • • • • • • •
Cooling unit
–
Motorised exhaust damper
x
• • • • • • • • • • • •
Electrical heating surface (preheating) Electrical heating surface (comfort heating) Water heating surface (comfort heating) CO2 sensor (wall-mounted) CO2 sensor (integrated) PIR/motion sensor Humidity sensor Thermostat
x (w. cooling unit) Returnfunction for motorised main damper
•
•
Motorised main damper
x
x
Countercurrent heat exchanger (aluminium) x
x
x : standard
50
• : optional
– : not available
51
PRODUCT INFORMATION AM 800
AM 800 CAPACITY (%)
AM 800 SCHEMATIC DIAGRAM
AM 800 SOUND PRESSURE LEVEL (dB(A)) 40
100 35 dBA with cooling unit
80
35
35 dBA
60
30 dBA
T=0,9 s
INTAKE
EXHAUST
30 T=0,6 s
40 25
20
150
200
250
300
350
400
450
500
550
600
650
700
750
400
450
500
550
Airflow (m3/h)
600
650
700
120
600
CT
FT
400
40
HE
200 0
0 150
250
350
450
550
650
150
750
250
350
450
550
650
AM 800 TEMPERATURE EFFICIENCY (%)
180
90
160
89
140
BP
EXTRACTION
AM 800 EXTERNAL PRESSURE DROP (Pa)
91
CP
EF
750
Airflow (m3/h)
Airflow (m3/h)
F2
PI
with cooling unit
800
80
BP
F1
1000
with cooling unit
PE
MD
1200
160
ET
IF
AM 800 SFP W/(m3/s)
200
ED
750
Airflow (m3/h)
AM 800 POWER CONSUMPTION (W)
OT
PH
20
0
RT FL
CH IT
120
88
100
87
80
86
60
85
40
84
20
83
INLET
0 150
200
250
300
350
400
450
500
550
600
650
700
150
750
Airflow (m3/h)
250
350
450
550
650
750
Airflow (m3/h)
AM 800 THROW (0.15 m/s) 0m
10m
The Airmaster units distribute the supply air to different degrees, depending on the given airflow. The blue tones on the illustration on the left show the airflow at different throws.
1
AM 800
1 2
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) ED Exhaust damper (overpressure)
BP HE CT CP FT RT/FL OT
Bypass damper Countercurrent heat exchanger Condensate tray Condensate pump Float Room temperature sensor/flow sensor Outdoor temperature sensor
ET PI PE PH CH IT
Exhaust temperature sensor Connection for pressure gauge for airflow-measurement, inlet Connection for pressure gauge for airflow-measurement, extraction Preheating surface (optional) Comfort heating surface Inlet temperature sensor
Throw viewed from above Throw viewed from the side
2
500m3/h 600m3/h 700m3/h
52
53
AM 800 V (VERTICAL)
If the unit is to be installed in a room where air humidity level is high, we
AM 800 HB (HORIZONTAL) - INLET BOTTOM
PRODUCT INFORMATION AM 800
AM 800 H (HORIZONTAL)
recommend connecting the unitâ&#x20AC;&#x2122;s integrated condensate drain or adding a condensate pump (se page 22). It is also possible to connect ductwork to either supply or extract or both.
54
55
Normal capacity, mixing
AM 900 is available in two
830 m³/h at 35 dB(A)
models, which can either be
690 m³/h at 30 dB(A) Normal capacity, displacement
positioned free-standing on
800 m³/h at 35 dB(A)
the floor or discreetly between
650 m³/h at 30 dB(A) Mixing, throw (0.15 m/s)
Displacement, near zone (0.15 m/s)
cupboards to form an integrat-
Adjustable grille, 1/1, 7 m at 830 m³/h
ed part of the room. The unit
Adjustable grille, 1/1, 6 m at 700 m³/h
has been developed so that it
Adjustable grille, 2/3, 12 m at 850 m³/h
can function either as mixing
Adjustable grille, 2/3, 9 m at 700 m³/h
ventilation or as displacement
Adjustable grille, 1/2, 12 m at 700 m³/h
ventilation, depending on room
Near zone from fitting, approx. 1.5 m at 800 m³/h
layout and use.
Near zone from fitting, approx. 1.2 m at 650 m³/h Electrical connection
1 ~ 230 V, 50 Hz, N + PE
Duct connections
Ø315 mm
Condensate drain (optional)
Ø16 mm
Weight
180 kg
Heat exchanger
3 countercurrent exchangers (plastic)
Filters
F5 standard
Colour
Ral 9010 (white)
Current
1.8 A
Supply cable
1.5 mm²
Maximum power consumption
240 W
Leakage current
<– 6 mA
PRODUCT INFORMATION AM 900
AM 900
TECHNICAL DATA
AM 900 is designed for larger rooms such as, e.g. classrooms, meeting rooms and office areas.
WATER HEATING SURFACE (OPTIONAL) Maximum operating temperature
90°C
Maximum operating pressure
10 bar
Heating capacity
1156 W*
Connection dimension
1/2" (DN 15)
Material of pipes/louvres
copper/aluminium
Opening/closing time of motorised valve < 60 s * Capacity at: flow/return temperature of 70/40°C, volume of water 33 l/h
ELECTRICAL HEATING SURFACE (optional)
PREHEATING
COMFORT HEATING
Heating element
1 x 230 V
1 x 230 V
Heating capacity
1500 W
1050 W
Thermal cut-out, automatic reset
70°C
70°C
Thermal cut-out, manual reset
120°C
120°C
Decentralised ventilation gives you the freedom to change your mind. The ventilation can be easily reconfigured if the rooms are to be used for a different purpose.
56
57
MIXING DISPLACEMENT HORIZONTAL MODEL VERTICAL MODEL
DISPLACEMENT HORIZONTAL MODEL
Condensate pump
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
Cooling unit
–
–
–
–
Motorised exhaust damper
x
–
x
–
Motorised main damper
x
x
x
x
Countercurrent heat exchanger (plastic) x
x
x
x
Bypass Electrical heating surface (preheating) Electrical heating surface (comfort heating) Water heating surface (comfort heating) CO2 sensor (wall-mounted) CO2 sensor (integrated) PIR/motion sensor Humidity sensor Thermostat
• : optional
x : standard
AM 900 SCHEMATIC DIAGRAM - MIXING
INTAKE
EXHAUST
PH
ED
IF
ET
OT
F2
F1 MD
PE
PI
HE
EF
FT
– : not available
EXTRACTION
BP
CT
CH
CP
RT FL
IT
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) ED Exhaust damper (overpressure) BP Bypass damper HE Countercurrent heat exchanger CT Condensate tray CP Condensate pump FT Float RT/FL Room temperature sensor/flow sensor OT Outdoor temperature sensor ET Exhaust temperature sensor PI Connection for pressure gauge for airflow-measurement, inlet PE Connection for pressure gauge for airflow-measurement, extraction PH Preheating surface (optional) CH Comfort heating surface IT Inlet temperature sensor
PRODUCT INFORMATION AM 900
STANDARD & OPTIONAL FEATURES MIXING VERTICAL MODEL
INLET
AM 900 MIXING - CAPACITY (%) 100 90 80 70 60 50 40 30 20 10 0
AM 900 MIXING - SOUND PRESSURE LEVEL (dB(A)) 40 38 36
30 dBA
AM 900 SCHEMATIC DIAGRAM - DISPLACEMENT
34 32 30 28 26
35 dBA
T=0,9 s T=0,6 s
INTAKE
EXHAUST
24 22 20
100
200
300
400
500
600
700
800
900
500
550
600
Airflow (m3/h)
650
700
750
800
850
PH
ED
Airflow (m3/h)
IF
AM 900 MIXING - POWER CONSUMPTION (W)
AM 900 MIXING - SFP W/(m /s)
100
200
300
400
500
600
700
800
EF CP
200
300
400
500
600
700
800
EXTRACTION
900
RT FL
CH IT
AM 900 MIXING - EXTERNAL PRESSURE DROP (Pa)
100 98 96 94 92 90 88 86 84 82 80
BP
CT
Airflow (m3/h)
AM 900 MIXING - TEMPERATURE EFFICIENCY (%)
PI HE
FT
100
900
F1 MD
PE
Airflow (m3/h)
250 35 dB(A)
200
30 dB(A)
INLET
150 100 50 0 100
200
300
400
500
Airflow (m3/h)
58
F2
1000 900 800 700 600 500 400 300 200 100 0
240 220 200 180 160 140 120 100 80 60 40 20 0
OT
ET
3
600
700
800
900
100
200
300
400
500
600
700
800
900
Airflow (m3/h)
59
AM 900 H (HORIZONTAL) - DISPLACEMENT
AM 900 V (VERTICAL) - MIXING
AM 900 V (VERTICAL) - DISPLACEMENT
PRODUCT INFORMATION AM 900
60
AM 900 H (HORIZONTAL) - MIXING
61
AM 900 ROOF CAP
0m
12m The Airmaster units provide different air throw lengths depending on supply air volume. The blue tones on the illustration on the left show the airflow at different throws. 1
Throw viewed from above
PRODUCT INFORMATION AM 900
AM 900 THROW - MIXING (0.15 m/s)
AM 900
The throw and distribution of the supply air in the room can be adapted to the geometry of the room by adjusting the supply opening.
min. 7 m
max. 12 m
1
AM 900 THROW - DISPLACEMENT (0.15 M/S)
0m
3m The result applies to an supply air temperature deficit of 3-5째C. Throw viewed from above
AM 900
2
2
62
650m3/h 800m3/h
63
FUNCTION AND DESIGN A PRIORITY
AM 1200 is a floor-mounted unit available in a horizon-
Ventilation should not just be seen as a technical com-
tal and vertical model. The unit can be placed against a
ponent: it also plays an active role in a roomâ&#x20AC;&#x2122;s function.
wall (right/left variant) or free-standing (centre variant).
In the field of decentralised ventilation, the AM 1200 is
With the various types of panel design, the surface
a byword for combining fresh air and elegant design. It
can be used as a notice board, mirror or equipped with
has a lot more uses than you might think.
acoustic boards â&#x20AC;&#x201C; the sky is the limit.
PRODUCT INFORMATION AM 1200
AM 1200
THE MANY POSSIBILITIES WITH AM 1200
AIRMASTER VISUALIZER Design your own AM 1200 with Airmaster VISUALISER at www.airmaster.dk With Airmaster, you are not only choosing a responsible solution. You are also choosing a solution for the future. 64
Visit www.airmaster.dk to design, choose, save and print your very own design.
65
35 DB(A)
30 DB(A)
right/left
1180 m /h
centre
1310 m /h
3
3
90° C
930 m /h
Maximum operating pressure
10 bar
1050 m /h
Heating capacity
2240 W*
Connection dimension
3/4" (DN 20)
Material of pipes/louvres
copper/aluminium
3
3
Vertical, Ø400 mm right/left centre
1130 m3/h 1260 m3/h
870 m3/h 980 m3/h
right/left
1060 m3/h
820 m3/h
centre
1170 m /h
920 m3/h
3
TECHNICAL DATA
Throw (0.15 m/s) – right/left
Opening/closing time of motorised valve <60 s * Capacity at: flow/return temperature of 65/35°, volume of water 72 l/h
Vertical, Ø315 mm
Throw (0.15 m/s) - centre
WATER HEATING SURFACE (OPTIONAL) Maximum operating temperature
Horizontal
PRODUCT INFORMATION AM 1200
CAPACITY
ELECTRICAL HEATING SURFACE (OPTIONAL)
PREHEATING
COMFORT HEATING
Min. 4.5 m at 1000 m3/h
Heating element
1 x 230 V
1 x 230 V
Max. 5.5 m at 1000 m3/h
Heating capacity
2500 W
1670 W
Min. 5.5 m at 1300 m3/h
Thermal cut-out, automatic reset
70°
70°
Max. 7.0 m at 1300 m3/h
Thermal cut-out, manual reset
120°
120°
Min. 6.5 m at 1000 m3/h Max. 7.5 m at 1000 m3/h Min. 7.5 m at 1300 m3/h Max. 9.5 m at 1300 m3/h
Electrical connection – with preheating surface
3~230 V + N + PE/50 Hz (note: preheating surface to be provided with a dedicated phase)
Electrical connection
1~230 V + N + PE/50 Hz
Duct connection
Ø400 mm
Condensate drain Weight
STANDARD & OPTIONAL FEATURES
VERTICAL MODEL CENTRE
VERTICAL MODEL RIGHT/LEFT
HORIZONTAL MODEL HORIZONTAL MODEL CENTRE RIGHT/LEFT
Ø16 mm
Bypass
x
x
x
x
Centre model 630 kg
Electrical heating surface (preheating)
Right-/left model 545 kg
Electrical heating surface (comfort heating)
Heat exchanger
4 countercurrent exchangers (aluminium)
Water heating surface (comfort heating)
Filter
F5 standard, F7 for fresh air optional item
CO2 sensor (wall-mounted)
Current
Unit without electrical heating surface 1.4 A
CO2 sensor (integrated)
Electrical preheating surface 10.9 A
PIR/motion sensor
Electrical comfort heating surface 7.3 A
Humidity sensor
Supply cable
1.5 mm2
Thermostat
Maximum power consumption
254 W
Condensate pump
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
Leakage current
<– 9 mA
Cooling unit
–
–
–
–
Spring-return actuator on main damper (for fresh air and exhaust air)
x
x
x
x
Countercurrent heat exchanger (aluminium)
x
x
x
x
x : standard
66
• : optional
– : not available
67
Horizontal model
AM 1200 SCHEMATIC DIAGRAM
Centre*
EXHAUST
Right
INTAKE
Left Vertical model
PRODUCT INFORMATION AM 1200
INSTALLATION POSITION
MODEL
PI
4
3
Centre*
MD
MD
Right
PH
Left
PE
IF
* If the centre model is required to be of freestanding type, a back panel is fitted to finish it off (option).
FI
F2
BP
ET
1
EF
BP
HE
EXTRACTION
2
1: Right and left (mounting in the corner) 2: Right and left (mounting along the wall)
OT
RT FL
FT
CT
3: Centre (mounting against the wall)
CP
4: Centre (mounting as free-standing)
CH
+ IT
INLET
AM 1200 PANEL DESIGNS
COLOURS
SIZE
Chipboard with melamine
White
600x500
Chipboard with melamine
Black
600x500
MDF
Lacquered (all colours)
600x500
MDF
Lacquered (all colours)
1200x1000
MDF with whiteboard laminate
White
MDF with notice board surface
Black
1200x1000
Mirror bonded to MDF
Mirror
1200x1000
Sound-absorbing wood (Acoustic Lightboard)
White
1200x1000
White
1200x1000
Sound-absorbing foam, printed/unprinted
1200x1000
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) BP Bypass damper HE Countercurrent heat exchanger
CT CP FT RT/FL OT ET
Condensate tray Condensate pump Float Room temperature sensor/flow sensor Outdoor temperature sensor Exhaust temperature sensor
PI PE PH CH IT
Connection for pressure gauge for airflow-measurement, inlet Connection for pressure gauge for airflow-measurement, extraction Preheating surface (optional) Comfort heating surface Inlet temperature sensor
AM 1200 has a spring-return actuator on the main dampers as standard, both on the intake and exhaust.
AM 1200 COLOUR OPTIONS Lacquered MDF boards are supplied in the standard colours shown, but all RAL colours are available at an additional cost.
68
69
AM 1200 V CAPACITY (%) - Ø400 MM
100
100
90
90
80
80
70
70
60
Right/left 35 dBA
40
Centre 30 dBA
30
Right/left 30 dBA
20 300
60
Centre 35 dBA
50
400
500
600
700
800
900
1000
1100
1200
1300
Centre 35 dBA
50
Right/left 35 dBA
40
Centre 30 dBA
30 20 300
Right/left 30 dBA 400
500
600
100 90 80 70 60
Centre 35 dBA
50
Right/left 35 dBA
40
Centre 30 dBA
30
Right/left 30 dBA
20 500
600
700
800
900
1000
1100
1200
1300
40 38 36 34 32 30 28 26 24 22 20 500
350
38
300
36 34
250
32
200
30 28 24 22 900
1300
600
700
800
1000
1100
1200
1300
1100
1200
1300
500
1400
70 60 50
120
Centre, 30 dBA Right/left, 35 dBA Right/left, 30 dBA
100
900
1000
1100
1200
1300
1400
900
1100
1200
1300
1100
1200
1300
1400
Centre, 35 dBA Centre, 30 dBA Right/left, 35 dBA Right/left, 30 dBA
0
500
600
700
800
900
1000
1100
1200
1300
500
1400
600
700
800
900
1000
1100
1200
1300
1400
Airflow (m3/h)
AM 1200 V EXTERNAL PRESSURE DROP (Pa) – Ø315MM - FRESH AIR
1000
1000
Roof cap Ø400 mm
Airflow (m3/h)
Vertical Ø400 mm
900
20
100 90 80 70 60 50 40 30 20 10 0 800
800
60
10
Horizontal
700
700
40
20
Vertical Ø315 mm
600
600
80
0 800
Centre, 30 dBA Right/left, 35 dBA Right/left, 30 dBA
140
Centre, 35 dBA
30
Centre Right/left 700
Centre, 35 dBA
AM 1200 V EXTERNAL PRESSURE DROP (Pa) – Ø400 MM - EXHAUST
40
600
Wall grille
Airflow (m3/h)
Roof cap Ø400 mm
AM 1200 V EXTERNAL PRESSURE DROP (Pa) – Ø315MM - EXHAUST 140
Roof cap Ø315 mm Centre, 35 dBA
120
Centre, 30 dBA Right/left, 35 dBA Right/left, 30 dBA
100
Roof cap Ø315 mm Centre, 35 dBA Centre, 30 dBA Right/left, 35 dBA Right/left, 30 dBA
80 60 40 20
500
600
Airflow (m3/h)
AM 1200 SFP W/(m3/s)
1000
90
50
1400
900
AM 1200 V EXTERNAL PRESSURE DROP (Pa) – Ø400 MM -FRESH AIR
100
0 500
100 90 80 70 60 50 40 30 20 10 0
Airflow (m3/h)
80
Airflow (m3/h)
1000 900 800 700 600 500 400 300 200 100 0 500
1200
150
Ø315 mm centre Ø315 mm right/left Ø400 mm centre Ø400 mm right/left
26
800
1100
AM 1200 POWER CONSUMPTION (W)
40
700
1000
Airflow (m3/h)
AM 1200 V SOUND PRESSURE LEVEL (dB(A))
600
900
AM 1200 H EXTERNAL PRESSURE DROP (Pa) – EXHAUST AIR
Wall grille Centre, 35 dBA Centre, 30 dBA Right/left, 35 dBA Right/left, 30 dBA
100
Airflow (m3/h)
20 500
800
AM 1200 H SOUND PRESSURE LEVEL (dB(A))
AM 1200 V CAPACITY (%) - Ø315 MM
400
700
120 110 100 90 80 70 60 50 40 30 20 10 0 500
Airflow (m3/h)
Airflow (m3/h)
300
AM 1200 H EXTERNAL PRESSURE DROP (Pa) – FRESH AIR
PRODUCT INFORMATION AM 1200
AM 1200 H CAPACITY (%)
700
800
900
1000
1100
1200
1300
0 500
1400
600
700
800
900
1000
1100
1200
1300
1400
Airflow (m3/h)
Airflow (m3/h)
AM 1200 TEMPERATURE EFFICIENCY (%) 88 87
AM 1200 THROW (0.15 m/s)
86
0m
85
Vertical Ø315 mm Horizontal Vertical Ø400 mm 600
700
800
900
Airflow (m3/h)
1000
1100
1200
1300
11m
1
84 83 82 500
600
700
800
900
1000
1100
1200
1300 m3/h Max. Min. 1000 m3/h Max. Min.
1300
Airflow (m3/h)
AM 1200
The Airmaster units provide different air throw lengths depending on supply air volume. The blue tones on the illustration on the left show the airflow at different throws.
AM 1200
2
70
1 2
Throw viewed from above Throw viewed from the side
71
AM 1200 H (HORIZONTAL) - RIGHT
PRODUCT INFORMATION AM 1200
AM 1200 H (HORIZONTAL) - CENTRE
AM 1200 H (HORIZONTAL) - LEFT
72
73
AM 1200 V (VERTICAL) - RIGHT
AM 1200 V (VERTICAL) - LEFT
AM 1200 ROOF CAP UNIT Ø315
PRODUCT INFORMATION AM 1200
AM 1200 V (VERTICAL) - CENTRE
A panel box is available for the roof cover module to cover intake and exhaust. White as standard.
74
75
CV 80 equals low energy con-
Maximum capacity at 30 dB(A)
80 m³/h
Electrical connection
1 ~ 230 V + N + PE / 50 Hz
Duct connections
Ø125 mm
Condensate drain
Ø16 mm
The unit has been designed
Weight
30 kg
to use a limited duct system
Heat exchanger
countercurrent exchangers (aluminium)
for ventilation as CV 80 is part
Filter
F5 Standard, F7 Optional
usually supplied into living
Colour
Black
areas, and extraction used in
Current
0.16 A
bathrooms and kitchens/open-
Supply cable
1.5 mm²
Maximum power consumption
22 W
Leakage current
<– 1 mA
ELECTRICAL HEATING SURFACE (OPTIONAL) Heating element
1 x 230 V
Heating capacity
500 W
Thermal cut-out, automatic reset
70°C
Thermal cut-out, manual reset
120°C
sumption, low noise levels and high heat rate of recovery.
of the ducting. Intake air is
PRODUCT INFORMATION CV 80
CV 80
TECHNICAL DATA
plan kitchens.
CV 80 is also available with an F7 intake air filter. With an F7 intake air filter and parameter adjustment, the unit provides balanced ventilation. With an F7 intake air filter, the maximum air volume is reduced by
STANDARD & OPTIONAL FEATURES Bypass
VERTICAL MODEL x
HORIZONTAL MODEL x
Electrical heating surface (preheating)
•
•
Electrical heating surface (comfort heating)
–
–
Water heating surface (comfort heating)
–
–
CO2 sensor (wall-mounted)
Thermostat
• • • • •
• • • • •
Condensate pump
x
x
Cooling unit
–
–
Motorised exhaust damper
x
x
Motorised main damper
x
x
Countercurrent heat exchanger (aluminium)
x
x
CO2 sensor (integrated) PIR/motion sensor Humidity sensor
x : standard
• : optional
approx. 4%.
– : not available
Ventilation in apartments and multi-storey buildings that complies with the most recent energy standards. 76
77
STANDARD FLOW 80 m3/h 32 Pa back pressure
Average frequency (Hz)
LWA
LpA/ 1 m distance
CV 80 CAPACITY (m3/h)
CV 80 SOUND PRESSURE LEVEL (dB(A))
80 70
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
Case*
28
31
32
25
27.4
21.4
19.6
18.5
36.7
29.8
Inlet**
45
49
49
39
41.6
31.1
23
16.4
53.3
40
Extraction**
36
42
42
36
29
12.1
0.1
-6.8
45.9
30
Intake**
43
48
48
33
26.1
12.3
6.63
4.02
51.8
Exhaust**
39
50
52
46
47.7
39.8
31.5
20.5
55.7
Case*
27
33
36
30
31
25.8
21.5
19.3
39.6
Inlet**
49
54
55
45
45.1
37.2
31.4
23.1
58.8
60 50
20 10 20
30
40
50
60
70
80
90
100%
32 30 28 26 24 22 20 18 16 14 12 30
40
50
60
70
80
90
70
80
90
Airflow (m3/h)
MAXIMUM FLOW 90 m3/h 42 Pa back pressure
32.7
Extraction**
38
45
46
40
31.6
16.7
4.73
-4.7
49.3
Intake**
46
52
52
38
28.7
16.6
10.7
7.88
55.6
25
Exhaust**
42
52
57
50
49.2
44.4
37
27.3
59.4
23
CV 80 POWER CONSUMPTION (W)
CV 80 SFP W/(m3/s) 1200
21
*
PRODUCT INFORMATION CV 80
NOISE EFFECT LEVEL CV80
Noise effect level (A weighted average) for emissions from the case, measured in accordance with EN/ISO 3744
1100
19
** Noise effect level (A weighted average) for emissions to duct, measured in accordance with EN/ISO 5136
17
Note: Sound data are not sensitive to changes in back pressure. Data for 1/3 octave bands can be obtained from Airmaster A/S.
15
1000
13 11
900
30
40
50
60
70
80
30
90
40
50
CV 80 SCHEMATIC DIAGRAM
CV 80 TEMPERATURE EFFICIENCY (%)*
CV 80 EXTERNAL PRESSURE DROP (Pa) 120 110 100 90 80 70 60 50 40 30 20 10 0
91
INTAKE
EXHAUST
89 87 85 83 81 15
30
45
60
Airflow (m3/h)
Airflow (m3/h)
60
75
90
1
6 5 2 4 3
30
40
60
70
80
90
100
Airflow (m3/h)
Airflow (m3/h)
* measured without condensation, if condensation is included, efficiency rises up to 95%.
50
1: CV 80 (30 dB(A)
4: 1000 Ws/m3
2: CV 80 ducts
5: 1200 Ws/m3
3: Wall grille
6: 1400 Ws/m3
EXTRACTION
INLET
Name of component F1 Inlet fan F2 Exhaust fan IF Fresh air filter EF Exhaust air filter MD Main damper (motorised) BP Bypass damper 78
HE CT CP FT RT/FL OT
Countercurrent heat exchanger Condensate tray Condensate pump Float Room temperature sensor/flow sensor Outdoor temperature sensor
ET CH IT
Exhaust temperature sensor Comfort heating surface Inlet temperature sensor
79
INSTALLATION
TWO BEDROOM APARTMENT
The CV 80 is installed above the ceiling in the bathroom.
EXAMPLES FOR CV
Bathroom
Projekteringsforslag
Living room
Intake
Fresh air
Exhaust
Exhaust air
Entrance
Bedroom
Intake and exhaust through the wall grille in the exterior wall.
PRODUCT INFORMATION CV 80
vindue ind her
Living room
Kitchen
Kitchen
ONE BEDROOM APARTMENT
Balcony
The CV 80 is installed above the ceiling in the bathroom. Bathroom
THREE-STOREY RESIDENTIAL BUILDING
CV on 2nd floor installed with intake
Intake and exhaust through the wall grille in the exterior wall.
Living room
Roof
through facade grilles in external wall and exhaust through the roof. vindue ind her Living room
CV with intake and exhaust through facade
Bathroom
ONE BEDROOM APARTMENTS
grilles in external wall on 1st and ground floors.
2. floor
in the bathroom.
suspended ceilings with ducting for supply Kitchen
Entrance
Supply and extraction are located in the rooms that require ventilation.
Kitchen
Bathroom
Kitchen
The CV 80 is installed above the ceiling
The ventilation units are installed above and extraction.
Bathroom
Bathroom
vindue ind her
Intake and exhaust through the wall grille in the exterior wall. NB: Option for an inverted unit.
1. floor
Living room Bathroom
Bedroom
Ground floor
80
81
FOR ORDERING
3
PRODUCT INFORMATION CV 80
GUIDE See drawings page 84
2 1
EPPCONSTRUCTION
TYPE
FLOW
CV
80
EXTRACTION
INTAKE
R
B
(right side)
(rear)
L
T
(left side)
(top)
FLEXIBLE LOCATION OF INTAKE AND EXHAUST
sections – a filter section (1), an exchanger sec-
The ventilation unit is part of the ducting. The
tion (2) and a motor section (3). All unit parts and
exchanger section includes inlet, extraction and
components are installed in or on the moulded
intake. The intake can be placed in three different
EPP sections which are finally assembled into one
places on either the right or left side.
tight and closed unit.
GRILLE
G0
B
(standard) 2 x Ø125
(rear)
G1
T
(extraction grille) Ø125 + grille
(top)
One option from each column S
can be selected. A complete EPP construction comprises three
EXHAUST
(side)
G2
S
(inlet airflow grille) Grille + Ø125
(side)
FOR EXAMPLE:
A CV 80 is required with extraction from the room to the right, intake of fresh air through the wall behind the system and exhaust leading above the ceiling, ducts for both exhaust air and fresh air. Product name = CV 80 R B T G0
The exhaust is always located in the motor section where there are also three different location options.
EXAMPLE 33 PA PRESSURE DROP – Ø125 / Ø100
INTAKE Airmaster wall grille
CV 80 L - left model
Ø100 on
cti
du
Re
EXTRACTION 2 Check valve
EXHAUST Airmaster wall grille
ipe
Tp
CV 80
90° Ø125 EXTRACTION 1 Check valve
EXTRACTION 1 Duct length: 7,25 m Airflow: 54,0 m3/h Pressure drop:
18,1 Pa
EXTRACTION 2 Duct length: 10,0 m Airflow: 80,0 m3/h Pressure drop:
— — — —
82
Inlet Extraction Exhaust (three different location options) Intake (three different location options)
18,1 Pa
Ø125
INTAKE Duct length: Airflow: Pressure drop:
6,0 m 80,0 m3/h 14,1 Pa
EXHAUST Duct length: Airflow:
6,0 m 80,0 m3/h
Pressure drop:
14,1 Pa
INLET Check valve
INLET Duct length: Airflow:
6,0 m 80,0 m3/h
Pressure drop:
18,1 Pa
CV 80 R - right model The demand for the energy consumption of transporting the air in the system must be low, which requires correctly dimensioning of the ducting.
83
CV 80 RTT EXTRACTION RIGHT - INTAKE TOP - EXHAUST TOP
CV 80 LBB EXTRACTION LEFT - INTAKE BACK - EXHAUST BACK
CV 80 LTT EXTRACTION LEFT - INTAKE TOP - EXHAUST TOP
PRODUCT INFORMATION CV 80
84
CV 80 RBB EXTRACTION RIGHT - INTAKE BACK - EXHAUST BACK
85
COMPONENTS
FOR THE CV RANGE
PRODUCT INFORMATION CV 80
CV 80 RSS EXTRACTION RIGHT - INTAKE SIDE - EXHAUST SIDE
STANDARD:
EC MOTORS built-in to the EPP construction. Efficient
COUNTERCURRENT HEAT EXCHANGER with
EC motors help to deliver a total energy consumption
documented efficiency of up to approx. 85% according
(SFP) < approx. 950 W/(m3/s) including duct counter-
to EN308 and up to 95% with condensation.
pressure.
CV 80 LSS EXTRACTION LEFT - INTAKE SIDE - EXHAUST SIDE BYPASS with automatic regulation of 0-100% air flow
TEMPERATURE SENSORS on exhaust, intake, extrac-
around heat exchangers, depending on temperatures
tion and supply ensures correct operation in synergy
and setpoints. Also used for automatic night time
with the advanced programming of the Airmaster
cooling.
controller.
DOUBLE MOTORISED MAIN DAMPER ensures that no
FILTERS on both extraction and exhaust air protect the
air penetrates the system when it is not in operation.
ventilators and heat exchanger from dirt. F5 filter as standard and optional F7 filter. Easily change the filter by removing the filter cassette.
CONDENSATION TROUGH WITH FLOAT stops the sys-
CONDENSATION PUMP with a lifting height of up to
tem if the condensation pump fails or the condensa-
six metres as standard.
tion pumpâ&#x20AC;&#x2122;s feed/outlet becomes clogged. 86
87
Ød
ROOF FLASHING
Ød
Ød AM 100/CV 80
250
AM 300
315
AM 500
355
AM 800/AM 900/AM 1200
450
AM 1200
500
PRODUCT INFORMATION AM RANGE
ROOF PENETRATION SHEATHING AND FITTINGS
Ød = internal diameter Roof flashing is available in galvanised metal or as grey Perform sheeting; both come with a galvanised metal pipe collar Also available in black, at extra charge.
FACADE GRILLES supplied with built-in birds net to protect against heavy rain.
SOUND ABSORBER used if there are special requirements for sound-proofing, e.g. in residential areas.
INSULATED PENETRATION DUCTING
CEILING BRACKETS to secure unit directly on the ceiling as support if the unit cannot be placed on the wall alone.
VAPOUR BARRIER MEMBRANE used around pipes for wall or roof ducts. Ensures tight vapour membrane after ducting.
ADJUSTABLE CEILING BRACKETS which is height-adjustable.
ØD
AM 100/CV 80
125
250
AM 300
200
315
AM 500
250
355
AM 800/AM 900/AM 1200
315
450
AM 1200
400
500
L = 900 / 1200 depending on pitch
Ød
Ød
ØD
WALL COVER for AM 900. Used when intake and exhaust need to be located close together and ensures against external short circuiting.
Ød = internal diameter · ØD = external diameter The insulated penetration ducting has a minimum of 50 mm insulation. The length of the penetration ducting depends on the pitch of the roof: Pitch 0°-30° = length 900 mm · Pitch 31°-45° = length 1200 mm Also available in black, at extra charge.
88
89
H
ROOF PENETRATION KIT
Ød ØD
Ød
ØD
H
AM 100/CV 80
125
250
230
AM 300
200
315
380
AM 500
250
355
437
AM 800/AM 900/AM 1200
315
450
540
AM 1200
400
500
700
A full roof penetration kit consists of 2 pieces of insulated penetration ducting, 2 roof flashing items, 1 exhaust cap, 1 louvred cap, 2 connectors and 3 metres of spiral pipe.
Ød = internal diameter · ØD = external diameter H = height NB: The height dimensions indicated are to the upper edge of the lowest hole. The exhaust cap has the same external dimensions as Airmaster’s insulated pipework, providing an optimum fit. Also available in black, at extra charge.
LOUVRED CAP
PRODUCT INFORMATION AM RANGE
EXHAUST CAP
ROOF CAP UNIT ØD
ØD
H
AM 100/CV 80
125
250
130
AM 300
200
315
160
AM 500
250
355
191
AM 800/AM 900/AM 1200
315
450
222
AM 1200
400
500
284
Ød = internal diameter · ØD = external diameter H = height The louvred cap has the same external dimensions as Airmaster’s insulated pipework, providing an optimum fit. Also available in black, at extra charge.
90
AM 900/AM 1200
Ød
ØD
H
Exhaust cap
315
450
540
Louvred cap
315
450
540
Roof flashing
-
-
1000x950x500 (H x B x D)
H
Ød
Ød
Insulated penetration sheathing 2 x 315
-
1000x950x500 (H x B x D)
Internal damper (AM 1200)
-
320
-
On roofing felt with a pitch of 0-30°, a so-called roof cap unit should be used for the AM 900 vertical model and AM 1200 vertical model. Here the pipe, caps and roof flashing are integrated in a box. Remember to specify the roof pitch when ordering.
91
AM
AM
100
300
500
900
1200
Maximum capacity at 35 dB(A)
m 3/h
725
830
1310
Maximum capacity at 30 dB(A)
m 3/h
650
690
1050
Throw (max.)
m
8.1
12
9.5
Maximum capacity at 35 dB(A)
m 3/h
100
300
550
Weight (ventilation units without optionals)
kg
147
180
450
Maximum capacity at 30 dB(A)
m /h
75
240
430
Dimensions for designpanels
mm
-
-
600x500 or 1200x1000
Throw (max.)
m
5.5
6.5
7.5
Colour, panels
RAL
9010
9010
9010
Weight (ventilation units without options)
kg
42
49.8
100.6
Colour, case
RAL
9010
9010
-
Colour, panels
RAL
9010
9010
9010
Dimensions (L/H/D)
mm
1910/467/833
800/2323/588
2427/2098/496
Colour, case
RAL
7024
7024
7024
Min. room height for horizontal intake/exhaust
mm
-
2400
2400
Dimensions (L/H/D)
mm
1170/246/571
1275/327/578
1600/432/729
Min. room height for vertical intake/exhaust
mm
-
2400
2500
Voltage (unit)
V
1~230
1~230
1~230
Voltage (unit)
V
1~230
1~230
1~230/ 3~230
Frequency
Hz
50
50
50
Frequency
Hz
50
50
50
Power consumption (max.)
W
27.5
100
132
Power consumption (max.)
W
156
240
254
Current
A
A
1.1
1.8
1.4
0.56
0.60
0.60
3
Power factor
0.2
0.6
1.1
Current
0.54
0.56
0.58
Power factor
Leakage current (max.)
mA
≤1
≤3
≤6
Leakage current (max.)
mA
≤6
≤6
≤9
Fuse rating (max.)
A
20
20
20
Fuse rating (max.)
A
20
20
20/3x20
CC COOLING UNIT
CC COOLING UNIT
Cooling capacity
W
-
2314
4065
Cooling capacity
W
5622
-
-
Power consumption
W
-
868
1033
Power consumption
W
1991
-
-
Current
A
-
3.6
4.4
Current
A
10.8
-
-
Leakage current (max.)
mA
-
≤2
≤2
Leakage current (max.)
mA
≤2
-
-
Weight
kg
-
55
71.4
Weight
kg
86
-
-
ELECTRICAL HEATING SURFACE
ELECTRICAL HEATING SURFACE
Thermal cut-out, automatic reset
°C
70
70
70
Thermal cut-out, automatic reset
°C
70
70
70
Thermal cut-out, manual reset
°C
120
120
120
Thermal cut-out, manual reset
°C
120
120
120
Electrical heating surface (comfort heating)
W
500
1500
630
Electrical heating surface (comfort heating)
W
1000
1050
1670
A
2.2
6.5
2.6
A
4.4
4.4
7.3
W
-
-
1000
W
1500
1500
-/ 2500
A
-
-
4.4
A
6.5
6.5
-/10.9
Current Electrical heating surface (preheating) Current WATER HEATING SURFACE
Current Electrical heating surface (preheating) Current WATER HEATING SURFACE
Capacity at flow/return temperature of 70/40°C
W
-
400
800
Capacity at flow/return temperature of 65/35°C
W
1100
1156
2240
Operating Temperature (max.)
°C
-
90
90
Operating Temperature (max.)
°C
90
90
90
Operating pressure (max.)
bar
bar
-
10
10
Operating pressure (max.)
10
10
10
Connection dimension
-
3/8”/DN10
3/8”/DN10
Connection dimension
1/2" (DN 15)
1/2" (DN 15)
3/4”(DN 20)
Material
-
Copper /
Copper /
Material
Copper /
Copper /
Copper /
Aluminium
Aluminium
Aluminium
Aluminium
Aluminium
60
60
s
60
60
60
Opening/closing time of motorised valve
s
-
CONDENSATE PUMP
92
800
PRODUCT INFORMATION
TECHNICAL DATA SUMMARY
Opening/closing time of motorised valve CONDENSATE PUMP
Output
l/h
10
10
10
Output
l/h
10
10
10
Pump head
m
6
6
6
Pump head
m
6
6
6
93
CV
PRODUCT INFORMATION
TECHNICAL DATA SUMMARY 80
Maximum capacity at 30 dB(A)
m 3/h
80
Weight (ventilation units without options)
kg
30
Colour, case
RAL
black
Dimensions (L/H/D)
mm
1170x275x560
Voltage (unit)
V
1~230
Frequency
Hz
50
Power consumption (max.)
W
22
Current
A
0.16 0.60
Power factor Leakage current (max.)
mA
≤1
Fuse rating (max.)
A
20
Thermal cut-out, automatic reset
°C
70
Thermal cut-out, manual reset
°C
120
Electrical heating surface (comfort heating)
W
500
Current
A
2.2
Output
l/h
10
Pump head
m
6
ELECTRICAL HEATING SURFACE
CONDENSATE PUMP
CC COOLING UNIT Cooling capacity (max.)
W
Refrigerant
500
800
2314
4065
5622
R134a
R407c
R407c
Charge
kg
0.310
0.700
0.950
Amperage
A
3.6
4.4
10.8
Power consumption
W
868
1033
1991
Duct connections
mm
Ø200
Ø250
Ø315
Condensate drain
mm
Ø16
Ø16
Ø16
Defrost interval
h
Defrost time Weight
kg
COP value Leakage current
94
300
mA
2
2
2
5°C or 10 minutes
5°C or 10 minutes
5°C or 10 minutes
55
71.4
86
2.6
4.2
2.82
<– 2
<– 2
< –2
95
Tel.
+45 98 62 48 22
DK - 9600 Aars
Fax.
+45 98 62 57 77
Denmark
info@airmaster.dk
Airmaster Applied
PO Box 6102
CV34 9PF
Solutions Ltd.
Innovation Centre
United Kingdom
Gallows Hill
Phone +44 (0)8448 099 993
Warwick
Fax
+44 (0)1926 797 001
www.airmaster.dk
www.airmaster-as.com
We are not liable for any errors and reserve the right to make changes. See www.airmaster.dk for updated documentation.
Industrivej 59