Connection of TSX SUP 1011/1021 power supplies

Connection of TSX SUP 1011/1021 power supplies

Illustration Connection diagram:

Advertisement

Connection rules Primary:if the module is supplied with a 100/240VAC power supply, it is necessary to observe wiring requirements for the phase and neutral when connecting the module. However, if the module is powered by a 125VDC supply, it is not necessary to respect the polarities.  an operating voltage ≥ 600VAC with a cross-section of 1.5mm2 (14AWG) for connection to the mains,

The power supply terminal is protected by a flap which allows access to the wiring terminals. The wires come vertically out of the power supply at its base. These wires can be kept in place with a cable-clip. Secondary: to comply with isolation requirements (EN60950) for a 24V SELV isolated voltage, the following wiring is used:  an operating voltage ≥ 300VAC with a cross-section of 2.5mm2 (12AWG) for the 24V outputs and the ground.

DANGER

ELECTRIC SHOCK

Connect the module grounding terminal to the protective ground, using a green/yellow wire. Failure to follow these instructions will result in death or serious injury.