HITACHI AIR-COOLED WATER CHILLERS
– ATHYZ1 SERIES – HITACHI Nominal Capacity Range 35℃ Condenser Air Inlet Temperature R22: 116kW to 1,146kW R407C: 110kW to 1,089kW 46℃ Condenser Air Inlet Temperature R22: 104kW to 1,007kW R407C: 98kW to 957 kW
Ambient temperature up to 52℃
New Series! This requirements of
Technical Catalog I Design Information Model:
R22 RCU40ATHYZ1 RCU50ATHYZ1 RCU60ATHYZ1 RCU75ATHYZ1 RCU100ATHYZ1 RCU120ATHYZ1 RCU150ATHYZ1 RCU160ATHYZ1 RCU180ATHYZ1 RCU200ATHYZ1 RCU240ATHYZ1 RCU270ATHYZ1 RCU300ATHYZ1 RCU330ATHYZ1 RCU350ATHYZ1 RCU360ATHYZ1 RCU380ATHYZ1 RCU400ATHYZ1
R407C RCUG40ATHYZ1 RCUG50ATHYZ1 RCUG60ATHYZ1 RCUG75ATHYZ1 RCUG100ATHYZ1 RCUG120ATHYZ1 RCUG150ATHYZ1 RCUG160ATHYZ1 RCUG180ATHYZ1 RCUG200ATHYZ1 RCUG240ATHYZ1 RCUG270ATHYZ1 RCUG300ATHYZ1 RCUG330ATHYZ1 RCUG350ATHYZ1 RCUG360ATHYZ1 RCUG380ATHYZ1 RCUG400ATHYZ1
series of HITACHI air-cooled water chillers up to 400HP has been developed for various
air-conditioning systems and industrial chilled water systems, where these equipment are operated under high
ambient temperatures of 52 ℃,Therefore, the units can be utilized under a wide temperature range. These water chillers are equipped with newly model-changed semi-hermetic HITACHI A-type screw compressors, featuring high reliability, low noise and low vibration, and highly efficient air-cooled condenser, resulting in compact design. The unit is composed of compressors, air-cooled condensers, shell-tube type water coolers, and other auxiliary and control devices, compactly packaged in a weather-proof cabinet which is constructed of galvanized steel plates processed with specially baked resin paint.
FEATURE
NEW HITACHI AIR-COOLED WATER CHILLERS… THAT’S THE ACHIEVEMENT OF TOTAL HITACHI TECHNOLOGY… ● The most reliable semi-hermetic screw type compressor
Adopting new profile screw rotors, HITACHI have developed the higher performance screw type compressor to obtain a higher reliability and durability of the unit operation. In this new century when people pay more attention to the change of the environment, HITACHI semi-hermetic screw type compressors ,which use the R407C refrigerant directly, and reduce the refrigerant leak greatly, have been sold 140,000 in the world ! Discharge Outlet
1. Efficiency is improved by using the highly precision rotors. 2. Separation efficiency is enhanced greatly by changing the oil separation mode.
Motor for Compressor
Slide Valve
Suction Inlet
Bearing ●Highly
Efficiency Operation
The appropriate combination of the air side heat exchangers with high performance SLIT fins, highly efficient screw compressors and water side heat exchangers has achieved this high efficiency of operation. Heat-Exchanger(ATHYZ1) Air side heat-exchanger using the converse M-type distributing resulting in an equality distribution of the air velocity, achieves highly heat exchange efficiency.
1.Improve the air heat exchanger configuration. 2.Adopt high heat exchange efficiency inner thread tube 3.Improve air velocity distribution to enhance efficiency.
●Smaller
Vibration and Lower Operation Sound
Due to the combination of the HITACHI semi-hermetic screw compressors and smooth-air-flow propeller fans for air side heat exchangers, smaller vibration and lower sound operation has been achieved, therefore, in most cases, special vibration absorbing curbs are not required by utilizing factory-supplied rubber mats.
1
FEATURE
Capacity Control Continuous Capacity Control z z
Chilled water outlet temperature can be controlled precisely within ±0.5℃ of the setting temperature. This control is performed by applying a micro-computer to the continuous capacity control type screw compressor. This precise temperature control is not only suitable for air conditioning, but also for industrial Load-up signal When there is a big use. 12sec.
difference between set temperature and actual temperature
60sec.
Load-up signal
Start 2sec.
Inlet water temperature
Outlet water temperature
≈
Outlet water temperature
Inlet water temperature 60sec.
≈
8
Neutral zone standard
6 4
(Set temperature:5℃)
Stop
Stop temperature standard
Lapsed time Load-down signal A given load status is maintained.
2sec.
60sec.
The inlet water temperature is detected at a stop, and it is restarted by a raise in inlet water temperature
-Principle of Continuous Capacity ControlContinuous capacity control is performed by adjusting the slide valve position as shown below. The slide position can be changed freely between 100% and 15% in accordance with cooling load.
Load-up
Pd: Discharge Pressure,
Load-down
Ps: Suction Pressure
Hold
S1,2,3 :Solenoid Valve
Other Option The following specifications are available on order basis. Please contact local Hitachi’s distributors if required. z G/W communication adapter or RS485 physics connector z High static pressure fan (Max. outside static pressure:150Pa) z Remote control box z Liquid crystal touch panel with big screen(Independent Box) z HITACHI water chillers group control system
Micro-Processor Control for Various Functions z Alarm Indication for each cycle by 7-Segment z Rotating control of compressor starting order z Current limitation control z Automatic start after instantaneous power failure Complete Standard Accessory z Water connection companion flange z Vibration-proof Mat z Foundation Bolt, Nut, Washer and Bushing z Spreader bar for rigging z Acoustic panel for compressor z Protection net for condenser 2
GENERAL DATA
General Data(R22) Model
R22
*1
Nominal Cooling Capacity
Nominal Cooling Capacity*2
Capacity Control
Outer Dimension
116
143
179
191
286
358
382
429
537
573
99,760
122,980
153,940
164,230
245,916
307,825
328,461
368,874
461,737
492,691
122.0
152.7
163.0
RT
33.0
40.7
50.9
54.3
81.3
101.8
108.6
kW
104
126
157
168
251
315
336
kcal/h
89,440
108,360
135,020
144,454
215,821
270,851
288,908
RT
29.6
35.8
44.6
47.8
71.4
89.6
95.6
377
472
504
324,220
405,847
433,362
107.2
134.2
143.3
Continuous Capacity Control
─
*3
*3
100~15,0
100~15(7.5) ,0
Depth
mm
2,390
4,490
6,590
Width
mm
1,940
1,940
1,940
Height
mm kg
Standard
—
Flow Control
—
Number of Circuit
—
Compressor
Type
─
Model
─
2,170 1,906
1,946
2,057
3,822
4,103
5,103
5,688
5,827
R22 Thermal Expansion Valve 1
2
3
Semi-Hermetic Screw Type 40ASCC-Z
50ASCC-Z
60ASCC-Z
60ASCC-Z
50ASCC-Z
60ASCC-Z
─ ─
Cross Fin Type
─
Direct drive Propeller Fan
1
60ASCC-Z
50ASCC-Z
60ASCC-Z
2
60ASCC-Z
3
kW
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
─
4
4
4
4
8
8
8
12
12
12
930
930
930
930
1,860
1,860
1,860
2,790
2,790
2,790
3
Air Discharge m /min Evaporator
2,170
4,017
Condenser
Fan Power Input Motor Quantity
100~15(5) ,0
2,170 2,014
Quantity
Condenser Fan HeatExchanger
kW kcal/h
%
Net Weight
Refrigerant
RCU40ATHY RCU50ATHY RCU60ATHY RCU75ATHY RCU100ATHY RCU120ATHY RCU150ATH RCU160ATH RCU180ATH RCU200ATH Z1 Z1 Z1 Z1 Z1 Z1 YZ1 YZ1 YZ1 YZ1
─
Shell and Tube Type
Safety Devices
─
Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
Piping Connections for Water-Side Heat Exchanger(In/Outlet)
─
Connection Hole
Main Power (square orifice)
mm
Circuit
mm
*4
With φ142 Inner Diameter Companion Flange
500×200 2×φ64.5;φ102; φ52
3×φ64.5;φ102;φ52
4×φ64.5;φ102;φ52
kg
2,166
2,206
2,274
2,317
4,282
4,477
4,563
5,763
6,348
6,487
Depth
mm
2,600
2,600
2,600
2,600
4,700
4,700
4,700
6,800
6,800
6,800
Width
mm
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2,190
Height
mm
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
Shipping Weight Shipping Dimension
With φ90 Inner Diameter Companion Flange
NOTE: 1. The nominal cooling capacities are based on the standard
4. Water Flow
GB/T 18430.1-2001:
1) RCU240, 300,360,400ATHYZ1
*1Chilled Water Inlet/Outlet Temperature:12/7℃
It is necessary to control the common water flow volume to each cooler.
Condenser Air Inlet Temperature:35℃(DB)
2) RCU270, 330,350,380ATHYZ1
*2Chilled Water Inlet/Outlet Temperature 12℃/7℃ Condenser Air Inlet Temperature 46℃ (DB)
Because the chilled water flow rate is different between No.1 and No.2 units. It is necessary to control the water flow volume of each unit with
2. Applicable Power Supply Main Power Source(AC3φ)
Control Power Source(AC1φ)
380V, 50HZ
220V,50HZ
415V, 50HZ
240V,50HZ
adjusting valves (Filed-Supplied). 5. It is required to connect electrical control wires between No.1 and No.2 units for the unit greater than 240ATHYZ1including 240ATHYZ1. 6. ( ) marked with *3 is available by selection switch.
3.The units greater than 240ATHYZ1 including 240ATHYZ1 consist of two modules and are separately shipped(*4). The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.
Working Range
Item Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB)
Standard 5~10℃ 5~52℃ 3
GENERAL DATA
General Data(R22) Model
R22
Nominal Cooling Capacity
Nominal Cooling Capacity
*1
*2
kW
716
740
764
919
955
1,074
1,110
1,146
kcal/h
615,649
636,285
656,922
790,198
821,152
923,474
954,428
985,383 325.9
RT
203.6
210.5
217.3
261.4
271.6
305.5
315.7
kW
630
651
672
808
840
944
976
1,007
kcal/h
541,702
559,759
577,816
694,755
722,270
811,694
839,209
865,864
RT
179.2
185.2
191.1
229.8
238.9
268.5
277.6
286.4 *3
100~15(6) ,0
100~15(7.5) ,0
9,080(Minimum)
11,180(Minimum)
13,280(Minimum)
Width
mm
1,940
1,940
1,940
Height
mm
2,170
2,170
2,170
kg —
Flow Control
—
Number of Circuit
—
Type
─
2×4,017
4,103+4,017
2×4,103
5,688+4,103
5,827+4,103
5
6
─
Condenser
─
Cross Fin Type
─
Direct Drive Propeller Fan
Air Discharge
2×5,827
Semi-Hermetic Screw Type
─
60ASCC-Z
60ASCC-Z
60ASCC-Z
60ASCC-Z
4
60ASCC-Z
60ASCC-Z
60ASCC-Z
5
60ASCC-Z
6
kW
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
─
2×8
8+8
2×8
12+8
12+8
2×12
12+12
2×12
3,720
3,720
3,720
4,650
4,650
5,580
5,580
5,580
3
m /min
Evaporator
5,827+5,688
Thermal Expansion Valve 4
Model
Fan Power Input Motor Quantity
2×5,688
R22
Quantity
Condenser Fan HeatExchanger
*3
100~15(7.5) ,0
mm
Standard
Compressor
*3
%
Depth
Net Weight
Refrigerant
Continuous Capacity Control
─
Capacity Control
Outer Dimension
RCU240ATHYZ1 RCU270ATHYZ1 RCU300ATHYZ1 RCU330ATHYZ1 RCU350ATHYZ1 RCU360ATHYZ1 RCU380ATHYZ1 RCU400ATHYZ1
─
Shell and Tube Type
Safety Devices
─
Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
Piping Connections for Water-Side Heat Exchanger(In/Outlet)
─
With φ142 Inner Diameter Companion Flange
Main Power (square orifice)
mm
2×500×200
Circuit
mm
Connection Hole
Shipping Dimension
*4
6×φ64.5;2×φ102;2×φ52
7×φ64.5;2×φ102;2×φ52
8×φ64.5;2×φ102;2×φ52
kg
2×4,477
4,563+4,477
2×4,563
6,348+4,563
6,487+4,563
2×6,348
6,487+6,348
2×6,487
Depth
mm
2×4,700
2×4,700
2×4,700
6,800+4,700
6,800+4,700
2×6,800
2×6,800
2×6,800
Width
mm
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2190
Height
mm
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
Shipping Weight
NOTE: 1. The nominal cooling capacities are based on the standard
4. Water Flow
GB/T 18430.1-2001:
1) RCU240, 300,360,400ATHYZ1
*1Chilled Water Inlet/Outlet Temperature:12/7℃
It is necessary to control the common water flow volume to each cooler.
Condenser Air Inlet Temperature:35℃(DB)
2) RCU270, 330,350,380ATHYZ1
*2Chilled Water Inlet/Outlet Temperature 12℃/7℃ Condenser Air Inlet Temperature 46℃ (DB)
Because the chilled water flow rate is different between No.1 and No.2 units. It is necessary to control the water flow volume of each unit with
2. Applicable Power Supply Main Power Source(AC3φ)
Control Power Source(AC1φ)
380V, 50HZ
220V,50HZ
415V, 50HZ
240V,50HZ
adjusting valves (Filed-Supplied). 5. It is required to connect electrical control wires between No.1 and No.2 units for the unit greater than 240ATHYZ1including 240ATHYZ1. 6. ( ) marked with *3 is available by selection switch.
3.The units greater than 240ATHYZ1 including 240ATHYZ1 consist of two modules and are separately shipped(*4). The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.
Working Range
Item Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB) 4
Standard 5~10℃ 5~52℃
GENERAL DATA
General Data(R407C) Model
R407C
Nominal Cooling Capacity
*1
Nominal Cooling Capacity*2
110
136
170
181
272
340
363
408
510
544
94,600
116,960
146,200
156,019
233,620
292,433
312,038
350,430
438,650
468,057 154.8
RT
31.3
38.7
48.4
51.6
77.3
96.7
103.2
115.9
145.1
kW
98
119
150
160
239
299
319
358
449
479
kcal/h
84,280
102,340
129,000
137,575
205,503
257,094
274,291
307,880
386,071
411,866
RT
28
34
43
46
68
85
91
102
128
136
*3
*3
%
100~15,0
100~15(7.5) ,0
100~15(5) ,0
mm
2,390
4,490
6,590
Width
mm
1,940
1,940
1,940
Height
mm
2,170
2,170
kg
Standard
—
Flow Control
—
Number of Circuit
—
Type
─
Compressor
Continuous Capacity Control
Depth
Net Weight
Refrigerant
kW kcal/h
─
Capacity Control
Outer Dimension
RCUG40AT RCUG50AT RCUG60AT RCUG75AT RCUG100AT RCUG120AT RCUG150AT RCUG160AT RCUG180AT RCUG200AT HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1
1,906
1,946
2,014
2,057
3,822
5,827
3
2
─
Condenser
─
Cross Fin Type
─
Direct drive Propeller Fan
Evaporator
5,688
Semi-Hermetic Screw Type
─
Air Discharge
5,103
Thermal Expansion Valve 1
Model
Power Input HeatFan Motor Exchanger Quantity
4,103
R407C
Quantity
Condenser Fan
2,170
4,017
40ASCC-Z
50ASCC-Z
60ASCC-Z
60ASCC-Z
50ASCC-Z
1
60ASCC-Z
60ASCC-Z
50ASCC-Z
60ASCC-Z
2
60ASCC-Z
3
kW
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
─
4
4
4
4
8
8
8
12
12
12
930
930
930
930
1,860
1,860
1,860
2,790
2,790
2,790
3
m /min
1.1
─
Shell and Tube Type
Safety Devices
─
Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
Piping Connections for Water-Side Heat Exchanger(In/Outlet)
─
With φ90 Inner Diameter Companion Flange
Connection Hole
Main Power (square orifice)
mm
Circuit
mm
500×200 2×φ64.5;φ102; φ52
3×φ64.5;φ102;φ52
4×φ64.5;φ102;φ52
kg
2,166
2,206
2,274
2,317
4,282
4,477
4,563
5,763
6,348
6,487
Depth
mm
2,600
2,600
2,600
2,600
4,700
4,700
4,700
6,800
6,800
6,800
Width
mm
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2,190
Height
mm
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
Shipping Weight Shipping Dimension
*4
With φ142 Inner Diameter Companion Flange
NOTE: 1. The nominal cooling capacities are based on the standard
4. Water Flow
GB/T 18430.1-2001:
1) RCUG240, 300,360,400ATHYZ1
*1Chilled Water Inlet/Outlet Temperature:12/7℃
It is necessary to control the common water flow volume to each cooler.
Condenser Air Inlet Temperature:35℃(DB)
2) RCUG270, 330,350,380ATHYZ1
*2Chilled Water Inlet/Outlet Temperature 12℃/7℃ Condenser Air Inlet Temperature 46℃ (DB)
Because the chilled water flow rate is different between No.1 and No.2 units. It is necessary to control the water flow volume of each unit with
2. Applicable Power Supply Main Power Source(AC3φ)
Control Power Source(AC1φ)
380V, 50HZ
220V,50HZ
415V, 50HZ
240V,50HZ
adjusting valves (Filed-Supplied). 5. It is required to connect electrical control wires between No.1 and No.2 units for the unit greater than 240ATHYZ1including 240ATHYZ1. 6. ( ) marked with *3 is available by selection switch.
3.The units greater than 240ATHYZ1 including 240ATHYZ1 consist of two modules and are separately shipped(*4). The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.
Working Range
Item Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB)
Standard 5~10℃ 5~52℃ 5
GENERAL DATA
General Data(R407C) RCUG240ATHY RCUG270ATHY RCUG300ATH RCUG330ATHY RCUG350ATHY RCUG360ATHY RCUG380ATHY RCUG400ATH R407C Z1 Z1 YZ1 Z1 Z1 Z1 Z1 YZ1
Model
Nominal Cooling Capacity
Nominal Cooling Capacity
*1
*2
726
873
907
1,020
1,055
1,089
624,076
750,688
780,095
877,300
906,707
936,113 309.6
RT
193.4
199.9
206.4
248.2
258.0
290.1
299.8
kW
598
618
638
768
798
897
927
957
kcal/h
514,187
531,384
548,581
660,361
686,156
771,281
797,077
822,872
RT
170
176
181
218
227
255
264
272
%
100~15(7.5)*3,0
100~15(6) ,0
100~15(7.5) ,0
9,080(Minimum)
11,180(Minimum)
13,280(Minimum)
Width
mm
1,940
1,940
1,940
Height
mm
2,170
2,170
2,170
kg —
Flow Control
—
Number of Circuit
—
Type
─
Model
─
Quantity
─
Condenser
Fan Motor
Continuous Capacity Control
mm
Standard
Compressor
HeatExchanger
703 604,471
Depth
Net Weight
Refrigerant
680 584,867
─
Capacity Control
Outer Dimension
kW kcal/h
2×4,017
4,103+4,017
*3
2×4,103
5,688+4,103
5,827+4,103
*3
2×5,688
5,827+5,688
2×5,827
R407C Thermal Expansion Valve 4
5
6
Semi-Hermetic Screw Type 60ASCC-Z
60ASCC-Z
60ASCC-Z
60ASCC-Z
60ASCC-Z
4
60ASCC-Z
5
60ASCC-Z
60ASCC-Z
6
─
Cross Fin Type
Condenser Fan
─
Direct Drive Propeller Fan
Power Input
kW
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
Quantity
─
2×8
8+8
2×8
12+8
12+8
2×12
12+12
2×12
3,720
3,720
3,720
4,650
4,650
5,580
5,580
5,580
Air Discharge Evaporator
3
m /min ─
Shell and Tube Type
Safety Devices
─
Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
Piping Connections for Water-Side Heat Exchanger(In/Outlet)
─
With φ142 Inner Diameter Companion Flange
Connection Hole
Main Power (square orifice)
mm
Circuit
mm
7×φ64.5;2×φ102;2×φ52
8×φ64.5;2×φ102;2×φ52
kg
2×4,477
4,563+4,477
2×4,563
6,348+4,563
6,487+4,563
2×6,348
6,487+6,348
2×6,487
Depth
mm
2×4,700
2×4,700
2×4,700
6,800+4,700
6,800+4,700
2×6,800
2×6,800
2×6,800
Width
mm
2,190
2,190
2,190
2,190
2,190
2,190
2,190
2190
Height
mm
2,510
2,510
2,510
2,510
2,510
2,510
2,510
2,510
Shipping Weight Shipping Dimension
*4
2×500×200 6×φ64.5;2×φ102;2×φ52
NOTE: 1. The nominal cooling capacities are based on the standard
4. Water Flow
GB/T 18430.1-2001:
1) RCUG240, 300,360,400ATHYZ1
*1Chilled Water Inlet/Outlet Temperature:12/7℃
It is necessary to control the common water flow volume to each cooler.
Condenser Air Inlet Temperature:35℃(DB)
2) RCUG270, 330,350,380ATHYZ1
*2Chilled Water Inlet/Outlet Temperature 12℃/7℃ Condenser Air Inlet Temperature 46℃ (DB)
Because the chilled water flow rate is different between No.1 and No.2 units. It is necessary to control the water flow volume of each unit with
2. Applicable Power Supply Main Power Source(AC3φ)
Control Power Source(AC1φ)
380V, 50HZ
220V,50HZ
415V, 50HZ
240V,50HZ
adjusting valves (Filed-Supplied). 5. It is required to connect electrical control wires between No.1 and No.2 units for the unit greater than 240ATHYZ1including 240ATHYZ1. 6. ( ) marked with *3 is available by selection switch.
3.The units greater than 240ATHYZ1 including 240ATHYZ1 consist of two modules and are separately shipped(*4). The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.
Working Range
Item Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB)
Standard 5~10℃ 5~52℃
6
DIMENSION DATA
Unit Dimensions RCU(G)40ATHYZ1, RCU(G)50ATHYZ1, RCU(G)60ATHYZ1,RCU(G)75TATHYZ1 Air Discharge Air Side Heat-Exchanger
Air Inlet
Air Inlet
Rigging holes(4-φ50)
Mounting Holes(4-φ26) Earth Connection Terminal
Screw Type Compressor
NOTE: Fan
1.It should surpport the water pipings properly to avoid its weight press on the unit directly. Wiring Hole for Power Supply
2.Water connection flanges( 90mm inner diameter )are supplied by factory with the unit.
RCU(G)100ATHYZ1, RCU(G)120ATHYZ1 and RCU(G)150ATHYZ1
Air Discharge Air Side Heat-Exchanger
Air Inlet
Air Inlet
Rigging Holes(4-φ50)
Earth Connection Terminal
Mounting Holes(6-φ26)
Screw Type Compressor
Fan Wiring Hole for Power Supply
NOTE: 1.It should surpport the water pipings properly to avoid its weight press on the unit directly. 2.Water connection flanges( 142mm inner diameter)are supplied by factory with the unit.
7
DIMENSION DATA
Unit Dimensions CU(G)160ATHYZ1,RCU(G)180ATHYZ1,and RCU(G)200ATHYZ1
Air Discharge
Air Side Heat-Exchanger
Air Inlet
Air Inlet
Rigging Holes (4-φ50) Mounting Holes (8-φ26)
Screw Type Compressor
Earth Connection Terminal
Fan
NOTE:
Wiring Hole for Power Supply
1.It should surpport the water pipings properly to avoid its weight press on the unit directly. 2.Water connection flanges( 142mm inner diameter ) are supplied by factory with the unit.
RCU(G)240ATHYZ1、RCU(G)270ATHYZ1 and RCU(G)300ATHYZ1
Minimum)
Air Discharge
Air Side Heat-Exchanger
Air Side Heat-Exchanger
Air Inlet
Air Inlet
Rigging Holes(8-φ50) Earth Connection Terminal
Screw Type Compressor
No.1 Water Outlet
Screw Type Compressor
No.1 Water Inlet
Earth Connection Terminal
Mounting Holes(12-φ26)
Screw Type Compressor
Screw Type Compressor
No.2 Water Outlet
No.2 Water Inlet
Wiring Hole for Power Supply
NOTES:
Fan Wiring Hole for Power Supply
8
1.This chiller consists of unit No.1 and No.2 and should be separately shipped. 2.Support the water pipes with stay not to give the weight of water pipes directly to the unit. 3.Provide a field-supplied common water piping at the water coolers to connect unit No.1 and No.2. Furthermore,for RCU240,300ATHYZ1:as the No.1 unit and No.2 unit have a same water flow rate, it just needs to control the common water volume to the chiller;for RCU270ATHYZ1:because the chilled water flow rate between No.1and No.2 unit is different, It is necessary to control the water volume of each unit with adjusting valves. 4.It needs to field-connect the control wiring between the No.1 unit and No. 2 unit.
DIMENSION DATA
Unit Dimensions RCU(G)330ATHYZ1 and RCU(G)350ATHYZ1
Air Discharge
(Minimum) Air Side Heat-Exchanger
Air Side Heat-Exchanger
Air Inlet
Air Inlet
Rigging Holes(8-φ50) P Mounting Holes(14- φ26) Screw Type Compressor
Earth Connection Terminal
No.1Water Outlet
Earth Connection Terminal
No.1WaterInlet
Screw Type Compressor
Screw Type Compressor
No.2WaterInlet
No.2Water Outlet
NOTES:
Wiring Hole for Power Supply
1.This chiller consists of unit No.1 and No.2 and should be separately shipped. 2.Support the water pipes with stay not to give the weight of water pipes directly to the unit. 3.Provide a field-supplied common water piping at the water coolers to connect unit No.1 and No.2. Furthermore,for RCU330,350ATHYZ1,because the chilled water flow rate between No.1and No.2 unit is different,It is necessary to control the water volume of each unit with adjusting valves. 4.It needs to field-connect the control wiring between the No.1 unit and No. 2 unit. 5.The dimension of No.2 unit marked with P is 300mm.
Fan
RCU(G)360ATHYZ1, RCU(G)380ATHYZ1 and RCU(G)400ATHYZ1
(Minimum)
Air Discharge
Air Side Heat-Exchanger
Air Side Heat-Exchanger
Air Inlet
Air Inlet
Rigging Holes(8- φ50) Mounting Holes(16-φ26)
Screw Type Compressor
Earth Connection Terminal
No.1 Water Outlet
Screw Type Compressor
Earth Connection Terminal
No.2 Water Outlet
No.1 Water Inlet
Wiring Hole for Power Supply
No.2 Water Inlet
NOTES:
Fan
9
1.This chiller consists of unit No.1 and No.2 and should be separately shipped. 2.Support the water pipes with stay not to give the weight of water pipes directly to the unit. 3.Provide a field-supplied common water piping at the water coolers to connect unit No.1 and No.2. Furthermore,for RCU360,400ATHYZ1:as the No.1 unit and No.2 unit have a same water flow rate, it just needs to control the common water volume to the chiller;for RCU380ATHYZ1:because the chilled water flow rate between No.1and No.2 unit is different, It is necessary to control the water volume of each unit with adjusting valves. 4.It needs to field-connect the control wiring between the No.1 unit and No. 2 unit.
PREPARATION
Operation Space h1≤h2
h1≤h2
For Models:
RCU(G)40ATHYZ1, RCU(G)50ATHYZ1
For Models: RCU(G)240ATHYZ1,RCU(G)270ATHYZ1, RCU(G)300ATHYZ1, RCU(G)330ATHYZ1, RCU(G)350ATHYZ1, RCU(G)360ATHYZ1, RCU(G)380ATHYZ1,RCU(G)400ATHYZ1
RCU(G)60ATHYZ1,RCU(G)75ATHYZ1, RCU(G)100ATHYZ1,RCU(G)120ATHYZ1, RCU(G)150ATHYZ1,RCU(G)160ATHYZ1 RCU(G)180ATHYZ1,RCU(G)200ATHYZ1.
Maximum Foundation Gradient Refer to C,D E
Refer to C,D F 30mmm
Refer to C,D 15mm
G
Model
Maintain Space (mm)
Air Inlet Space (mm)
A
B
C
D
E
F
G
RCU(G)40ATHYZ1
2,100
1,200
100
900
1,200
2,000
1,200
RCU(G)50ATHYZ1
2,100
1,200
100
900
1,200
2,000
1,200
RCU(G)60ATHYZ1
2,100
1,200
100
900
1,200
2,000
1,200
RCU(G)75ATHYZ1
2,100
1,200
100
900
1,200
2,000
1,200
RCU(G)100ATHYZ1
4,200
1,200
100
900
1,200
2,000
1,200
RCU(G)120ATHYZ1
4,200
1,200
100
900
1,200
2,000
1,200
RCU(G)150ATHYZ1
4,200
1,200
100
900
1,200
2,000
1,200
RCU(G)160ATHYZ1
6,300
1,200
100
900
1,200
2,000
1,200
RCU(G)180ATHYZ1
6,300
1,200
100
900
1,200
2,000
1,200
RCU(G)200ATHYZ1
6,300
1,200
100
900
1,200
2,000
1,200
RCU(G)240ATHYZ1
8,500(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)270ATHYZ1
8,500(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)300ATHYZ1
8,500(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)330ATHYZ1
10,600(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)350ATHYZ1
10,600(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)360ATHYZ1
12,700(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)380ATHYZ1
12,700(Minimum)
1,200
900
900
1,200
2,000
1,200
RCU(G)400ATHYZ1
12,700(Minimum)
1,200
900
900
1,200
2,000
1,200
10
PREPARATION
Center of Gravity Center of Gravity
Model
X 975 975 975 975 2,035 2,055 2,065 3,550 3,550 3,570 2,055 2,065 2,055 2,065 3,570 2,065 3,570 2,065 3,550 3,570 3,550 3,570
RCU(G)40ATHYZ1 RCU(G)50ATHYZ1 RCU(G)60ATHYZ1 RCU(G)75ATHYZ1 RCU(G)100ATHYZ1 RCU(G)120ATHYZ1 RCU(G)150ATHYZ1 RCU(G)160ATHYZ1 RCU(G)180ATHYZ1 RCU(G)200ATHYZ1 RCU(G)240ATHYZ1-1,2 RCU(G)270ATHYZ1-1 RCU(G)270ATHYZ1-2 RCU(G)300ATHYZ1-1,2 RCU(G)330ATHYZ-1 RCU(G)330ATHYZ-2 RCU(G)350ATHYZ-1 RCU(G)350ATHYZ-2 RCU(G)360ATHYZ-1,2 RCU(G)380ATHYZ-1 RCU(G)380ATHYZ-2 RCU(G)400ATHYZ-1,2
Operation Weight(kg)
Y 830 830 830 830 805 805 835 805 805 835 805 835 805 835 835 835 835 835 805 835 805 835
2156 2206 2279 2,332 4,112 4,312 4,403 5,413 6,006 6,152 4,312 4,403 4,312 4,403 6,006 4,403 6,152 4,403 6,006 6,152 6,006 6,152
Weight Balance Model RCU(G)40ATHYZ1 RCU(G)50ATHYZ1 RCU(G)60ATHYZ1 RCU(G)75ATHYZ1
Model RCU(G)100ATHYZ1 RCU(G)120ATHYZ1 RCU(G)150ATHYZ1 RCU(G)240ATHYZ1-1,2 RCU(G)270ATHYZ1-1 RCU(G)270ATHYZ1-2 RCU(G)300ATHYZ1-1
Model RCU(G)160ATHYZ1 RCU(G)180ATHYZ1 RCU(G)200ATHYZ1 RCU(G)330ATHYZ1-1 RCU(G)330ATHYZ1-2 RCU(G)350ATHYZ1-1 RCU(G)350ATHYZ1-2 RCU(G)360ATHYZ1-1,2 RCU(G)380ATHYZ1-1 RCU(G)380ATHYZ1-2 RCU(G)400ATHYZ1-1,2
Weight Destribution (kg) 1 520 532 550 563
2 469 480 496 508
3 612 626 646 662
4 555 568 587 601
1 655 651 688 651 688 651 688
Weight Destribution (kg) 2 3 4 5 610 590 756 756 643 628 817 799 665 651 807 800 643 628 817 799 665 651 807 800 643 628 817 799 665 651 807 800
1 590 654 688 654 688 688 688 654 688 654 688
2 605 671 696 671 665 696 665 671 696 671 696
6 745 776 794 776 794 776 794
Weight Destribution (kg) 3 4 5 6 608 605 744 754 674 671 825 836 707 696 842 850 674 671 825 836 651 807 800 794 707 696 842 850 651 807 800 794 674 671 825 836 707 696 842 850 674 671 825 836 707 696 842 850
11
7 757 840 837 840
8 751 833 834 833
837
834
840 837 840 837
833 834 833 834
SELECTION DATA
Selection Example
Cooling Capacity and Compressor Input When the fouling factor is different
Determination the System Requirements: Condenser Air Inlet Temperature: 40℃ Chilled Water Outlet Temperature 7℃ Chilled Water Inlet Temperature 12℃ Cooling Load 453kW Power Source Frequency: 50Hz
-4
0.86×10 m .℃/w, the cooling capacity or the compressor input will be corrected utilizing follow formulas:
Correction
Corrected
From the cooling capacity table, model RCU180ATHYZ1 can be selected with the following performance: Cooling Capacity: 507.5kW Chilled Water Flow Rate: 87.3m3/h Water Cooler Pressure Drop: 69.7kPa Compressor Input Power: 173.2kW
Cooling Capacity
Corrected
The water flow rate in the cooling capacity table is
Correction
the chilled water inlet and outlet temperature, if the
Factor
Capacity
Indicated in Table
Correction
Compressor
= Factor
×
Input
indicated in Table
Factor
for
Cooling
Capacity
and
Compressor Input Regarding Fouling Factor
5 ℃ , correct the
water flow rater of the water cooler utilizing follow formulas. Flow Rate
Rate
Cooling
×
Input
based on the 5 ℃ temperature difference between
Corrected Flow =
=
and
Compressor
temperature difference is not
from
2
Fouling
Cooling
Compressor
Factor
Capacity
Input
2
m . ℃/W
5℃ × From the Table (CFR)
Water
Given Temperature
Cooler
0(0) -4
0.86×10
1.02
1.00
1.00
1.00
Difference (℃)
0.0001m2h℃/kcal=0.086m2℃/kW
The corrected chilled water flow rate must be confirmed to be within the working range described on pages 24
Water Cooler Pressure Drop(kPa)
1、RCU(G)40ATHYZ1 2、RCU(G)50ATHYZ1 3、RCU(G)60ATHYZ1 RCU(G)75ATHYZ1 4、RCU(G)100ATHYZ1 5、RCU(G)120ATHYZ1 RCU(G)150ATHYZ1 RCU(G)240ATHYZ1-1 RCU(G)240ATHYZ1-2 RCU(G)270ATHYZ1-1 RCU(G)270ATHYZ1-2 RCU(G)300ATHYZ1-1 RCU(G)300ATHYZ1-2 RCU(G)330ATHYZ1-2 RCU(G)350ATHYZ1-2 6、RCU(G)160ATHYZ1 RCU(G)180ATHYZ1 RCU(G)200ATHYZ1 RCU(G)330ATHYZ1-1 RCU(G)350ATHYZ1-1 RCU(G)360ATHYZ1-1 RCU(G)360ATHYZ1-2 RCU(G)380ATHYZ1-1 RCU(G)380ATHYZ1-2 RCU(G)400ATHYZ1-1 RCU(G)400ATHYZ1-2 3
Chilled Water Flow Rate of Each Water Cooler(m /h) (Total Flow Rate /Number of Cooler )
NOTE: The flow rate of each model is not different; please refer to the chilled water flow rate on the pages13 to 18. 12
SELECTION DATA
Cooling Capacities(R22) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq
-50HzABT CLOT
25
30
35
40
46
48
52
5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
ABT CLOT
25
30
35
40
46
48
52
5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
CCAP 120.5 124.6 128.7 132.7 136.7 140.7 114.4 118.4 122.3 126.2 130.1 133.9 108.3 112.1 115.9 119.7 123.5 127.1 102.2 105.9 109.5 113.2 116.8 120.3 96.4 100.0 103.6 107.2 110.6 114.1 93.9 97.5 101.0 104.5 107.9 111.3 89.0 92.5 95.9 99.2 102.5 105.8
RCU40ATHYZ1 CFR CPD 20.7 38.2 21.4 40.7 22.1 43.2 22.8 45.7 23.5 48.3 24.2 50.9 19.7 34.7 20.4 37.0 21.0 39.3 21.7 41.7 22.4 44.0 23.0 46.4 18.6 31.4 19.3 33.5 19.9 35.6 20.6 37.8 21.2 40.0 21.9 42.2 17.6 28.2 18.2 30.1 18.8 32.1 19.5 34.1 20.1 36.1 20.7 38.1 16.6 25.3 17.2 27.1 17.8 28.9 18.4 30.8 19.0 32.7 19.6 34.6 16.2 24.1 16.8 25.9 17.4 27.6 18.0 29.4 18.6 31.2 19.1 33.0 15.3 21.8 15.9 23.4 16.5 25.1 17.1 26.7 17.6 28.4 18.2 30.1
IPT 27.2 27.5 27.7 27.9 28.2 28.4 30.6 30.9 31.1 31.4 31.7 31.9 34.0 34.3 34.6 34.9 35.1 35.4 37.4 37.7 38.0 38.3 38.6 38.9 41.5 41.8 42.1 42.4 42.8 43.1 42.9 43.1 43.5 43.8 44.2 44.5 45.6 45.9 46.3 46.6 47.0 47.4
CCAP 148.7 153.7 158.7 163.7 168.7 173.5 141.1 146.0 150.9 155.7 160.5 165.2 133.6 138.3 143.0 147.7 152.3 156.8 126.0 130.6 135.1 139.6 144.1 148.5 117.0 121.3 125.7 129.9 134.2 138.5 114.0 118.3 122.6 126.7 130.9 135.1 107.9 112.1 116.3 120.3 124.3 128.5
CCAP 372.1 384.8 397.4 409.9 422.2 434.4 353.3 365.5 377.7 389.8 401.7 413.4 334.5 346.2 358.0 369.7 381.2 392.6 315.6 327.0 338.4 349.6 360.7 371.7 292.9 303.9 314.8 325.6 336.1 346.5 285.4 296.3 306.9 317.5 327.9 338.2 270.3 280.9 291.2 301.5 311.5 321.4
RCU120ATHYZ1 CFR CPD 64.0 66.2 66.2 70.9 68.3 75.7 70.5 80.7 72.6 85.8 74.7 90.9 60.8 59.5 62.9 63.8 65.0 68.2 67.0 72.8 69.1 77.4 71.1 82.2 57.5 53.1 59.5 57.0 61.6 61.1 63.6 65.3 65.6 69.5 67.5 73.9 54.3 47.1 56.2 50.7 58.2 54.4 60.1 58.2 62.0 62.1 63.9 66.0 50.4 40.5 52.3 43.6 54.1 46.9 56.0 50.3 57.8 53.7 59.6 57.2 49.1 38.3 50.9 41.4 52.8 44.5 54.6 47.8 56.4 51.0 58.2 54.3 46.5 34.3 48.3 37.1 50.1 40.0 51.8 42.9 53.6 45.9 55.3 49.0
IPT 82.6 83.4 84.1 84.9 85.6 86.4 93.0 93.8 94.5 95.4 96.2 97.0 103.3 104.1 105.0 105.9 106.7 107.6 113.6 114.5 115.5 116.3 117.3 118.3 126.1 126.9 128.0 128.9 130.0 131.1 130.2 131.1 132.2 133.1 134.2 135.3 138.5 139.4 140.6 141.4 142.6 143.8
CCAP 397.0 410.6 424.0 437.4 450.6 463.6 377.0 390.0 403.0 416.0 428.6 441.2 356.8 369.4 382.0 394.4 406.8 418.8 336.8 348.8 361.0 373.0 385.0 396.6 312.8 324.1 335.8 347.3 358.8 370.0 304.8 315.8 327.4 338.8 350.1 361.1 288.8 299.4 310.6 321.6 332.7 343.3
RCU50ATHYZ1 CFR CPD 25.6 41.3 26.4 43.9 27.3 46.6 28.2 49.3 29.0 52.1 29.8 54.9 24.3 37.5 25.1 39.9 25.9 42.4 26.8 44.9 27.6 47.5 28.4 50.1 23.0 33.9 23.8 36.1 24.6 38.4 25.4 40.8 26.2 43.1 27.0 45.5 21.7 30.4 22.5 32.5 23.2 34.6 24.0 36.8 24.8 38.9 25.5 41.2 20.1 26.5 20.9 28.4 21.6 30.3 22.3 32.2 23.1 34.2 23.8 36.2 19.6 25.3 20.3 27.0 21.1 28.9 21.8 30.7 22.5 32.6 23.2 34.6 18.6 22.8 19.3 24.5 20.0 26.2 20.7 27.9 21.4 29.7 22.1 31.5
IPT 33.1 33.4 33.7 34.0 34.4 34.6 37.3 37.7 38.0 38.4 38.7 39.0 41.6 42.0 42.3 42.6 43.0 43.4 45.8 46.2 46.6 47.0 47.4 47.8 50.9 51.3 51.7 52.2 52.6 53.0 52.6 53.0 53.5 53.9 54.3 54.8 56.0 56.4 56.9 57.4 57.8 58.3
RCU150ATHYZ1 IPT CFR CPD 88.0 68.3 75.6 88.7 70.6 81.0 89.5 72.9 86.5 90.3 75.2 92.2 91.0 77.5 98.1 92.0 79.7 104.0 98.8 64.8 68.0 99.8 67.1 72.9 100.6 69.3 77.9 101.5 71.5 83.2 102.3 73.7 88.5 103.2 75.9 93.9 109.7 61.4 60.7 110.6 63.5 65.2 111.6 65.7 69.8 112.6 67.8 74.6 113.5 70.0 79.5 114.3 72.0 84.4 120.7 57.9 53.9 121.7 60.0 57.9 122.6 62.1 62.2 123.6 64.1 66.5 124.6 66.2 71.0 125.5 68.2 75.4 53.8 46.3 134.0 55.7 49.8 134.9 57.7 53.6 135.9 59.7 57.4 136.9 61.7 61.4 137.8 63.6 65.4 139.0 52.4 43.9 138.4 54.3 47.2 139.4 56.3 50.9 140.3 58.3 54.5 141.3 60.2 58.4 142.2 62.1 62.2 143.5 49.7 39.3 147.3 51.5 42.3 148.2 53.4 45.6 149.2 55.3 49.0 150.1 57.2 52.6 151.1 59.0 56.1 152.5
ABT:Condensate Air Inlet Temperature(℃)
CCAP 186.1 192.4 198.7 204.9 211.1 217.2 176.7 182.7 188.9 194.9 200.9 206.7 167.2 173.1 179.0 184.9 190.6 196.3 157.8 163.5 169.2 174.8 180.4 185.8 146.5 152.0 157.4 162.8 168.1 173.3 142.7 148.1 153.5 158.8 164.0 169.1 135.1 140.4 145.6 150.7 155.8 160.7
RCU60ATHYZ1 CFR CPD 32.0 44.8 33.1 47.8 34.2 50.9 35.2 54.0 36.3 57.1 37.3 60.3 30.4 40.6 31.4 43.3 32.5 46.1 33.5 49.0 34.5 51.9 35.5 54.9 28.8 36.5 29.8 39.0 30.8 41.6 31.8 44.3 32.8 47.0 33.8 49.7 27.1 32.7 28.1 35.0 29.1 37.4 30.1 39.8 31.0 42.2 32.0 44.7 25.2 28.4 26.1 30.4 27.1 32.5 28.0 34.7 28.9 36.9 29.8 39.1 24.5 27.0 25.5 29.0 26.4 31.0 27.3 33.1 28.2 35.2 29.1 37.3 23.2 24.3 24.2 26.2 25.0 28.0 25.9 30.0 26.8 31.9 27.6 33.9
IPT 41.3 41.7 42.0 42.4 42.8 43.2 46.5 46.9 47.3 47.7 48.1 48.5 51.6 52.1 52.5 52.9 53.4 53.8 56.8 57.2 57.7 58.2 58.7 59.1 63.0 63.5 64.0 64.4 65.0 65.5 65.1 65.5 66.1 66.5 67.1 67.7 69.2 69.7 70.3 70.7 71.3 71.9
CCAP 198.5 205.3 212.0 218.7 225.3 231.8 188.5 195.0 201.5 208.0 214.3 220.6 178.4 184.7 191.0 197.2 203.4 209.4 168.4 174.4 180.5 186.5 192.5 198.3 156.4 162.0 167.9 173.7 179.4 185.0 152.4 157.9 163.7 169.4 175.1 180.5 144.4 149.7 155.3 160.8 166.3 171.7
RCU75ATHYZ1 CFR CPD 34.1 50.8 35.3 54.1 36.5 57.6 37.6 61.1 38.7 64.7 39.9 68.3 32.4 46.0 33.5 49.1 34.7 52.2 35.8 55.5 36.9 58.8 37.9 62.1 30.7 41.4 31.8 44.2 32.8 47.1 33.9 50.1 35.0 53.2 36.0 56.2 29.0 37.0 30.0 39.6 31.0 42.3 32.1 45.0 33.1 47.9 34.1 50.7 26.9 32.1 27.9 34.4 28.9 36.8 29.9 39.3 30.9 41.8 31.8 44.3 26.2 30.6 27.2 32.8 28.2 35.1 29.1 37.5 30.1 39.9 31.0 42.3 24.8 27.6 25.7 29.6 26.7 31.7 27.7 33.9 28.6 36.2 29.5 38.4
IPT 44.0 44.4 44.8 45.1 45.5 46.0 49.4 49.9 50.3 50.8 51.1 51.6 54.8 55.3 55.8 56.3 56.8 57.1 60.4 60.8 61.3 61.8 62.3 62.8 67.0 67.5 68.0 68.4 68.9 69.5 69.2 69.7 70.2 70.6 71.1 71.7 73.6 74.1 74.6 75.1 75.5 76.2
CCAP 297.3 307.3 317.5 327.5 337.4 347.1 282.2 292.0 301.7 311.4 320.9 330.3 267.2 276.6 286.0 295.4 304.6 313.6 252.1 261.2 270.3 279.3 288.1 296.9 233.9 242.7 251.4 259.9 268.4 277.0 227.9 236.5 245.1 253.4 261.8 270.3 215.8 224.2 232.5 240.5 248.7 257.0
RCU100ATHYZ1 CFR CPD 51.1 55.7 52.9 59.3 54.6 62.9 56.3 66.6 58.0 70.4 59.7 74.1 48.5 50.6 50.2 53.9 51.9 57.3 53.6 60.7 55.2 64.2 56.8 67.7 46.0 45.8 47.6 48.8 49.2 51.9 50.8 55.1 52.4 58.3 53.9 61.5 43.4 41.1 44.9 43.9 46.5 46.8 48.0 49.7 49.6 52.6 51.1 55.6 40.2 35.8 41.7 38.3 43.2 40.9 44.7 43.5 46.2 46.2 47.6 48.9 39.2 34.2 40.7 36.6 42.1 39.1 43.6 41.5 45.0 44.1 46.5 46.8 37.1 30.9 38.5 33.1 40.0 35.4 41.4 37.7 42.8 40.1 44.2 42.6
IPT 66.3 66.9 67.4 68.0 68.7 69.3 74.7 75.3 76.0 76.7 77.4 78.1 83.1 83.9 84.6 85.3 86.1 86.7 91.6 92.4 93.2 94.0 94.7 95.5 101.8 102.6 103.5 104.4 105.1 106.0 105.2 106.0 106.9 107.8 108.6 109.6 112.0 112.7 113.8 114.8 115.6 116.6
CCAP 446.0 461.0 476.2 491.2 506.1 520.6 423.3 438.0 452.6 467.2 481.4 495.5 400.8 414.9 429.0 443.1 456.9 470.4 378.1 391.8 405.4 418.9 432.2 445.4 350.9 364.0 377.1 389.8 402.6 415.4 341.9 354.8 367.7 380.2 392.7 405.4 323.7 336.2 348.8 360.8 373.0 385.5
RCU160ATHYZ1 CFR CPD 76.7 55.8 79.3 59.4 81.9 63.3 84.5 67.1 87.0 71.1 89.5 75.1 72.8 50.5 75.3 53.9 77.8 57.4 80.3 61.0 82.8 64.6 85.2 68.3 68.9 45.4 71.4 48.5 73.8 51.8 76.2 55.1 78.6 58.4 80.9 61.8 65.0 40.6 67.4 43.5 69.7 46.4 72.0 49.4 74.3 52.5 76.6 55.6 60.3 35.2 62.6 37.7 64.8 40.4 67.0 43.1 69.2 45.8 71.4 48.7 58.8 33.5 61.0 35.9 63.2 38.5 65.4 41.0 67.5 43.7 69.7 46.4 55.7 30.1 57.8 32.4 60.0 34.8 62.0 37.1 64.1 39.6 66.3 42.1
IPT 99.4 100.3 101.2 102.0 103.1 103.9 112.0 113.0 114.0 115.1 116.1 117.1 124.7 125.9 126.9 127.9 129.1 130.1 137.4 138.6 139.8 140.9 142.1 143.3 152.7 153.9 155.2 156.5 157.7 159.1 157.8 158.9 160.4 161.8 162.9 164.3 168.0 169.1 170.6 172.2 173.3 174.9
CCAP 558.2 577.2 596.1 614.8 633.3 651.6 530.0 548.2 566.6 584.7 602.6 620.2 501.7 519.3 537.0 554.6 571.8 588.9 473.4 490.5 507.5 524.5 541.1 557.5 439.4 455.9 472.2 488.3 504.2 519.8 428.1 444.4 460.4 476.3 491.9 507.3 405.4 421.3 436.9 452.2 467.3 482.1
RCU180ATHYZ1 CFR CPD 96.0 83.6 99.3 89.2 102.5 94.9 105.7 100.7 108.9 106.6 112.0 112.6 91.1 75.7 94.3 80.8 97.4 86.1 100.5 91.4 103.6 96.9 106.6 102.4 86.3 68.1 89.3 72.8 92.3 77.6 95.4 82.6 98.3 87.6 101.3 92.7 81.4 60.9 84.3 65.2 87.3 69.7 90.2 74.2 93.0 78.8 95.9 83.4 75.6 52.8 78.4 56.7 81.2 60.6 84.0 64.7 86.7 68.8 89.4 72.9 73.6 50.2 76.4 53.9 79.2 57.8 81.9 61.6 84.6 65.6 87.2 69.6 69.7 45.2 72.5 48.7 75.1 52.2 77.8 55.8 80.4 59.4 82.9 63.1
IPT 123.9 125.1 126.1 127.3 128.4 129.6 139.5 140.6 141.8 143.1 144.3 145.4 154.9 156.2 157.5 158.8 160.1 161.4 170.4 171.7 173.2 174.5 176.0 177.4 189.1 190.4 192.0 193.3 195.0 196.6 195.3 196.6 198.3 199.6 201.3 203.0 207.7 209.1 210.9 212.2 214.0 215.8
CCAP 595.5 615.9 636.0 656.1 675.9 695.4 565.5 585.0 604.5 624.0 642.9 661.8 535.2 554.1 573.0 591.6 610.2 628.2 505.2 523.2 541.5 559.5 577.5 594.9 469.2 486.1 503.7 521.0 538.3 554.9 457.2 473.8 491.1 508.1 525.2 541.6 433.2 449.0 465.9 482.5 499.0 515.0
RCU200ATHYZ1 CFR CPD 102.4 94.7 105.9 101.1 109.4 107.5 112.8 114.1 116.2 120.8 119.6 127.6 97.2 85.8 100.6 91.5 104.0 97.5 107.3 103.6 110.6 109.8 113.8 116.0 92.0 77.1 95.3 82.5 98.5 88.0 101.7 93.5 104.9 99.3 108.0 105.0 86.9 69.0 90.0 73.9 93.1 78.9 96.2 84.0 99.3 89.3 102.3 94.5 80.7 59.9 83.6 64.1 86.6 68.6 89.6 73.2 92.6 78.0 95.4 82.7 78.6 57.0 81.5 61.0 84.5 65.4 87.4 69.8 90.3 74.4 93.1 78.9 74.5 51.4 77.2 55.0 80.1 59.1 83.0 63.2 85.8 67.4 88.6 71.6
IPT 132.0 133.1 134.3 135.4 136.5 138.0 148.3 149.7 150.8 152.3 153.4 154.8 164.5 166.0 167.4 168.8 170.3 171.4 181.1 182.5 184.0 185.4 186.8 188.3 201.0 202.4 203.9 205.3 206.7 208.5 207.6 209.1 210.5 211.9 213.3 215.2 220.9 222.3 223.7 225.2 226.6 228.7
CCAP:Cooling Capacity(kW)
CLOT:Chilled Water Outlet Temperature(℃) CFR:Chilled Water Flow Rate at 5℃ Difference Between Inlet and Outlet Temperature(m3/h)
CPD:Water Cooler Pressure Drop(kPa)
IPT:Input Power for Compressor(kW)
13
SELECTION DATA
Cooling Capacities(R22) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq
-50HzABT
25
30
35
40
46
48
52
ABT
25
30
35
40
46
48
52
CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
CCAP 744.2 769.6 794.8 819.7 844.4 868.7 706.7 731.0 755.5 779.6 803.4 826.9 668.9 692.4 716.0 739.4 762.4 785.2 631.2 653.9 676.7 699.3 721.4 743.3 585.9 607.9 629.6 651.1 672.2 693.1 570.8 592.5 613.9 635.1 655.8 676.3 540.6 561.8 582.5 603.0 623.0 642.8
CFR1 64.0 66.2 68.3 70.5 72.6 74.7 60.8 62.9 65.0 67.0 69.1 71.1 57.5 59.5 61.6 63.6 65.6 67.5 54.3 56.2 58.2 60.1 62.0 63.9 50.4 52.3 54.1 56.0 57.8 59.6 49.1 50.9 52.8 54.6 56.4 58.2 46.5 48.3 50.1 51.8 53.6 55.3
RCU240ATHYZ1 CFR2 CPD1 64.0 66.2 66.2 70.9 68.3 75.7 70.5 80.7 72.6 85.8 74.7 90.9 60.8 59.5 62.9 63.8 65.0 68.2 67.0 72.8 69.1 77.4 71.1 82.2 57.5 53.1 59.5 57.0 61.6 61.1 63.6 65.3 65.6 69.5 67.5 73.9 54.3 47.1 56.2 50.7 58.2 54.4 60.1 58.2 62.0 62.1 63.9 66.0 50.4 40.5 52.3 43.6 54.1 46.9 56.0 50.3 57.8 53.7 59.6 57.2 49.1 38.3 50.9 41.4 52.8 44.5 54.6 47.8 56.4 51.0 58.2 54.3 46.5 34.3 48.3 37.1 50.1 40.0 51.8 42.9 53.6 45.9 55.3 49.0
CPD2 66.2 70.9 75.7 80.7 85.8 90.9 59.5 63.8 68.2 72.8 77.4 82.2 53.1 57.0 61.1 65.3 69.5 73.9 47.1 50.7 54.4 58.2 62.1 66.0 40.5 43.6 46.9 50.3 53.7 57.2 38.3 41.4 44.5 47.8 51.0 54.3 34.3 37.1 40.0 42.9 45.9 49.0
IPT 165.2 166.8 168.2 169.7 171.3 172.8 186.0 187.5 189.1 190.8 192.4 193.9 206.5 208.3 210.0 211.7 213.5 215.2 227.2 229.0 230.9 232.7 234.6 236.5 252.1 253.9 256.0 257.8 259.9 262.1 260.4 262.2 264.4 266.1 268.4 270.6 277.0 278.7 281.1 282.9 285.3 287.7
CCAP 769.1 795.4 821.4 847.3 872.8 898.0 730.3 755.5 780.7 805.8 830.3 854.6 691.3 715.6 740.0 764.1 788.0 811.4 652.4 675.8 699.4 722.6 745.7 768.3 605.7 628.0 650.6 672.9 694.9 716.5 590.2 612.1 634.3 656.3 678.0 699.2 559.1 580.2 601.8 623.1 644.2 664.7
CFR1 68.3 70.6 72.9 75.2 77.5 79.7 64.8 67.1 69.3 71.5 73.7 75.9 61.4 63.5 65.7 67.8 70.0 72.0 57.9 60.0 62.1 64.1 66.2 68.2 53.8 55.7 57.7 59.7 61.7 63.6 52.4 54.3 56.3 58.3 60.2 62.1 49.7 51.5 53.4 55.3 57.2 59.0
RCU270ATHYZ1 CFR2 CPD1 64.0 75.6 66.2 81.0 68.3 86.5 70.5 92.2 72.6 98.1 74.7 104.0 60.8 68.0 62.9 72.9 65.0 77.9 67.0 83.2 69.1 88.5 71.1 93.9 57.5 60.7 59.5 65.2 61.6 69.8 63.6 74.6 65.6 79.5 67.5 84.4 54.3 53.9 56.2 57.9 58.2 62.2 60.1 66.5 62.0 71.0 63.9 75.4 50.4 46.3 52.3 49.8 54.1 53.6 56.0 57.4 57.8 61.4 59.6 65.4 49.1 43.9 50.9 47.2 52.8 50.9 54.6 54.5 56.4 58.4 58.2 62.2 46.5 39.3 48.3 42.3 50.1 45.6 51.8 49.0 53.6 52.6 55.3 56.1
CPD2 66.2 70.9 75.7 80.7 85.8 90.9 59.5 63.8 68.2 72.8 77.4 82.2 53.1 57.0 61.1 65.3 69.5 73.9 47.1 50.7 54.4 58.2 62.1 66.0 40.5 43.6 46.9 50.3 53.7 57.2 38.3 41.4 44.5 47.8 51.0 54.3 34.3 37.1 40.0 42.9 45.9 49.0
IPT 170.6 172.1 173.6 175.1 176.7 178.4 191.8 193.6 195.1 196.9 198.5 200.2 213.0 214.8 216.6 218.4 220.2 221.9 234.4 236.2 238.1 239.9 241.9 243.8 260.1 261.9 263.9 265.7 267.8 270.0 268.6 270.4 272.5 274.3 276.4 278.8 285.7 287.6 289.7 291.5 293.7 296.3
CCAP 794.0 821.2 848.0 874.8 901.2 927.2 754.0 780.0 806.0 832.0 857.2 882.4 713.6 738.8 764.0 788.8 813.6 837.6 673.6 697.6 722.0 746.0 770.0 793.2 625.6 648.2 671.6 694.6 717.7 739.9 609.6 631.7 654.8 677.5 700.2 722.2 577.6 598.7 621.2 643.3 665.4 686.6
CFR1 68.3 70.6 72.9 75.2 77.5 79.7 64.8 67.1 69.3 71.5 73.7 75.9 61.4 63.5 65.7 67.8 70.0 72.0 57.9 60.0 62.1 64.1 66.2 68.2 53.8 55.7 57.7 59.7 61.7 63.6 52.4 54.3 56.3 58.3 60.2 62.1 49.7 51.5 53.4 55.3 57.2 59.0
RCU300ATHYZ1 CFR2 CPD1 68.3 75.6 70.6 81.0 72.9 86.5 75.2 92.2 77.5 98.1 79.7 104.0 64.8 68.0 67.1 72.9 69.3 77.9 71.5 83.2 73.7 88.5 75.9 93.9 61.4 60.7 63.5 65.2 65.7 69.8 67.8 74.6 70.0 79.5 72.0 84.4 57.9 53.9 60.0 57.9 62.1 62.2 64.1 66.5 66.2 71.0 68.2 75.4 53.8 46.3 55.7 49.8 57.7 53.6 59.7 57.4 61.7 61.4 63.6 65.4 52.4 43.9 54.3 47.2 56.3 50.9 58.3 54.5 60.2 58.4 62.1 62.2 49.7 39.3 51.5 42.3 53.4 45.6 55.3 49.0 57.2 52.6 59.0 56.1
CPD2 75.6 81.0 86.5 92.2 98.1 104.0 68.0 72.9 77.9 83.2 88.5 93.9 60.7 65.2 69.8 74.6 79.5 84.4 53.9 57.9 62.2 66.5 71.0 75.4 46.3 49.8 53.6 57.4 61.4 65.4 43.9 47.2 50.9 54.5 58.4 62.2 39.3 42.3 45.6 49.0 52.6 56.1
IPT 176.0 177.5 179.0 180.5 182.1 184.0 197.7 199.6 201.1 203.0 204.5 206.4 219.4 221.3 223.2 225.1 227.0 228.5 241.5 243.4 245.3 247.2 249.1 251.0 268.0 269.9 271.8 273.7 275.6 278.0 276.8 278.7 280.6 282.5 284.4 287.0 294.5 296.4 298.3 300.2 302.1 304.9
CCAP 955.2 987.8 1020.1 1052.2 1083.9 1115.2 907.0 938.2 969.6 1000.7 1031.2 1061.4 858.5 888.7 919.0 949.0 978.6 1007.7 810.2 839.3 868.5 897.5 926.1 954.1 752.2 780.0 808.0 835.7 863.0 889.8 732.9 760.2 787.8 815.1 842.0 868.3 694.2 720.7 747.5 773.9 799.9 825.4
CFR1 96.0 99.3 102.5 105.7 108.9 112.0 91.1 94.3 97.4 100.5 103.6 106.6 86.3 89.3 92.3 95.4 98.3 101.3 81.4 84.3 87.3 90.2 93.0 95.9 75.6 78.4 81.2 84.0 86.7 89.4 73.6 76.4 79.2 81.9 84.6 87.2 69.7 72.5 75.1 77.8 80.4 82.9
RCU330ATHYZ1 CFR2 CPD1 68.3 83.6 70.6 89.2 72.9 94.9 75.2 100.7 77.5 106.6 79.7 112.6 64.8 75.7 67.1 80.8 69.3 86.1 71.5 91.4 73.7 96.9 75.9 102.4 61.4 68.1 63.5 72.8 65.7 77.6 67.8 82.6 70.0 87.6 72.0 92.7 57.9 60.9 60.0 65.2 62.1 69.7 64.1 74.2 66.2 78.8 68.2 83.4 53.8 52.8 55.7 56.7 57.7 60.6 59.7 64.7 61.7 68.8 63.6 72.9 52.4 50.2 54.3 53.9 56.3 57.8 58.3 61.6 60.2 65.6 62.1 69.6 49.7 45.2 51.5 48.7 53.4 52.2 55.3 55.8 57.2 59.4 59.0 63.1
CPD2 75.6 81.0 86.5 92.2 98.1 104.0 68.0 72.9 77.9 83.2 88.5 93.9 60.7 65.2 69.8 74.6 79.5 84.4 53.9 57.9 62.2 66.5 71.0 75.4 46.3 49.8 53.6 57.4 61.4 65.4 43.9 47.2 50.9 54.5 58.4 62.2 39.3 42.3 45.6 49.0 52.6 56.1
IPT 211.9 213.8 215.6 217.5 219.5 221.6 238.3 240.4 242.4 244.6 246.5 248.7 264.6 266.8 269.1 271.4 273.6 275.7 291.2 293.4 295.8 298.1 300.5 302.9 323.1 325.3 327.9 330.2 332.8 335.6 333.7 336.0 338.6 340.9 343.5 346.5 355.0 357.3 360.0 362.3 365.0 368.2
ABT:Condensate Air Inlet Temperature(℃) CCAP:Cooling Capacity(kW)
CLOT:Chilled Water Outlet Temperature(℃)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h). CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa)
14
IPT:Input Power for Compressor(kW)
SELECTION DATA
Cooling Capacities(R22) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq
-50HzABT
25
30
35
40
46
48
52
ABT
25
30
35
40
46
48
52
CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
CCAP 992.5 1026.5 1060.0 1093.5 1126.5 1159.0 942.5 975.0 1007.5 1040.0 1071.5 1103.0 892.0 923.5 955.0 986.0 1017.0 1047.0 842.0 872.0 902.5 932.5 962.5 991.5 782.0 810.2 839.5 868.3 897.1 924.9 762.0 789.6 818.5 846.9 875.3 902.7 722.0 748.4 776.5 804.1 831.7 858.3
CFR1 102.4 105.9 109.4 112.8 116.2 119.6 97.2 100.6 104.0 107.3 110.6 113.8 92.0 95.3 98.5 101.7 104.9 108.0 86.9 90.0 93.1 96.2 99.3 102.3 80.7 83.6 86.6 89.6 92.6 95.4 78.6 81.5 84.5 87.4 90.3 93.1 74.5 77.2 80.1 83.0 85.8 88.6
RCU350ATHYZ1 CFR2 CPD1 68.3 94.7 70.6 101.1 72.9 107.5 75.2 114.1 77.5 120.8 79.7 127.6 64.8 85.8 67.1 91.5 69.3 97.5 71.5 103.6 73.7 109.8 75.9 116.0 61.4 77.1 63.5 82.5 65.7 88.0 67.8 93.5 70.0 99.3 72.0 105.0 57.9 69.0 60.0 73.9 62.1 78.9 64.1 84.0 66.2 89.3 68.2 94.5 53.8 59.9 55.7 64.1 57.7 68.6 59.7 73.2 61.7 78.0 63.6 82.7 52.4 57.0 54.3 61.0 56.3 65.4 58.3 69.8 60.2 74.4 62.1 78.9 49.7 51.4 51.5 55.0 53.4 59.1 55.3 63.2 57.2 67.4 59.0 71.6
CPD2 75.6 81.0 86.5 92.2 98.1 104.0 68.0 72.9 77.9 83.2 88.5 93.9 60.7 65.2 69.8 74.6 79.5 84.4 53.9 57.9 62.2 66.5 71.0 75.4 46.3 49.8 53.6 57.4 61.4 65.4 43.9 47.2 50.9 54.5 58.4 62.2 39.3 42.3 45.6 49.0 52.6 56.1
IPT 220.0 221.9 223.8 225.7 227.6 230.0 247.1 249.5 251.4 253.8 255.7 258.1 274.2 276.6 279.0 281.4 283.8 285.7 301.9 304.2 306.6 309.0 311.4 313.8 335.0 337.4 339.8 342.1 344.5 347.5 346.0 348.4 350.8 353.2 355.6 358.7 368.1 370.5 372.9 375.3 377.6 381.2
CCAP 1116.3 1154.4 1192.1 1229.6 1266.7 1303.1 1060.0 1096.5 1133.2 1169.4 1205.2 1240.3 1003.4 1038.5 1074.0 1109.1 1143.6 1177.8 946.7 980.9 1015.1 1048.9 1082.1 1115.0 878.8 911.8 944.4 976.7 1008.3 1039.6 856.1 888.8 920.8 952.6 983.7 1014.5 810.8 842.7 873.7 904.4 934.5 964.3
CFR1 96.0 99.3 102.5 105.7 108.9 112.0 91.1 94.3 97.4 100.5 103.6 106.6 86.3 89.3 92.3 95.4 98.3 101.3 81.4 84.3 87.3 90.2 93.0 95.9 75.6 78.4 81.2 84.0 86.7 89.4 73.6 76.4 79.2 81.9 84.6 87.2 69.7 72.5 75.1 77.8 80.4 82.9
RCU360ATHYZ1 CFR2 CPD1 96.0 83.6 99.3 89.2 102.5 94.9 105.7 100.7 108.9 106.6 112.0 112.6 91.1 75.7 94.3 80.8 97.4 86.1 100.5 91.4 103.6 96.9 106.6 102.4 86.3 68.1 89.3 72.8 92.3 77.6 95.4 82.6 98.3 87.6 101.3 92.7 81.4 60.9 84.3 65.2 87.3 69.7 90.2 74.2 93.0 78.8 95.9 83.4 75.6 52.8 78.4 56.7 81.2 60.6 84.0 64.7 86.7 68.8 89.4 72.9 73.6 50.2 76.4 53.9 79.2 57.8 81.9 61.6 84.6 65.6 87.2 69.6 69.7 45.2 72.5 48.7 75.1 52.2 77.8 55.8 80.4 59.4 82.9 63.1
CPD2 83.6 89.2 94.9 100.7 106.6 112.6 75.7 80.8 86.1 91.4 96.9 102.4 68.1 72.8 77.6 82.6 87.6 92.7 60.9 65.2 69.7 74.2 78.8 83.4 52.8 56.7 60.6 64.7 68.8 72.9 50.2 53.9 57.8 61.6 65.6 69.6 45.2 48.7 52.2 55.8 59.4 63.1
IPT 247.9 250.2 252.2 254.6 256.9 259.2 279.0 281.3 283.6 286.2 288.6 290.9 309.8 312.4 315.0 317.6 320.2 322.8 340.9 343.5 346.4 349.0 351.9 354.8 378.2 380.8 384.0 386.7 389.9 393.2 390.6 393.2 396.6 399.2 402.6 406.0 415.5 418.1 421.7 424.3 427.9 431.5
CCAP 1153.7 1193.1 1232.1 1270.9 1309.2 1347.0 1095.5 1133.2 1171.1 1208.7 1245.5 1282.0 1036.9 1073.4 1110.0 1146.2 1182.0 1217.1 978.6 1013.7 1049.0 1084.0 1118.6 1152.4 908.6 942.0 975.9 1009.3 1042.4 1074.8 885.3 918.1 951.5 984.4 1017.0 1048.9 838.6 870.4 902.8 934.7 966.3 997.1
CFR1 102.4 105.9 109.4 112.8 116.2 119.6 97.2 100.6 104.0 107.3 110.6 113.8 92.0 95.3 98.5 101.7 104.9 108.0 86.9 90.0 93.1 96.2 99.3 102.3 80.7 83.6 86.6 89.6 92.6 95.4 78.6 81.5 84.5 87.4 90.3 93.1 74.5 77.2 80.1 83.0 85.8 88.6
RCU380ATHYZ1 CFR2 CPD1 96.0 94.7 99.3 101.1 102.5 107.5 105.7 114.1 108.9 120.8 112.0 127.6 91.1 85.8 94.3 91.5 97.4 97.5 100.5 103.6 103.6 109.8 106.6 116.0 86.3 77.1 89.3 82.5 92.3 88.0 95.4 93.5 98.3 99.3 101.3 105.0 81.4 69.0 84.3 73.9 87.3 78.9 90.2 84.0 93.0 89.3 95.9 94.5 75.6 59.9 78.4 64.1 81.2 68.6 84.0 73.2 86.7 78.0 89.4 82.7 73.6 57.0 76.4 61.0 79.2 65.4 81.9 69.8 84.6 74.4 87.2 78.9 69.7 51.4 72.5 55.0 75.1 59.1 77.8 63.2 80.4 67.4 82.9 71.6
CPD2 83.6 89.2 94.9 100.7 106.6 112.6 75.7 80.8 86.1 91.4 96.9 102.4 68.1 72.8 77.6 82.6 87.6 92.7 60.9 65.2 69.7 74.2 78.8 83.4 52.8 56.7 60.6 64.7 68.8 72.9 50.2 53.9 57.8 61.6 65.6 69.6 45.2 48.7 52.2 55.8 59.4 63.1
IPT 255.9 258.2 260.4 262.7 265.0 267.6 287.7 290.3 292.6 295.4 297.7 300.3 319.4 322.2 324.9 327.6 330.4 332.8 351.5 354.3 357.2 359.9 362.8 365.7 390.1 392.8 395.9 398.6 401.7 405.1 402.9 405.7 408.8 411.5 414.6 418.2 428.6 431.4 434.6 437.3 440.6 444.5
CCAP 1191.0 1231.8 1272.0 1312.2 1351.8 1390.8 1131.0 1170.0 1209.0 1248.0 1285.8 1323.6 1070.4 1108.2 1146.0 1183.2 1220.4 1256.4 1010.4 1046.4 1083.0 1119.0 1155.0 1189.8 938.4 972.2 1007.4 1042.0 1076.5 1109.9 914.4 947.5 982.2 1016.3 1050.4 1083.2 866.4 898.1 931.8 964.9 998.0 1030.0
CFR1 102.4 105.9 109.4 112.8 116.2 119.6 97.2 100.6 104.0 107.3 110.6 113.8 92.0 95.3 98.5 101.7 104.9 108.0 86.9 90.0 93.1 96.2 99.3 102.3 80.7 83.6 86.6 89.6 92.6 95.4 78.6 81.5 84.5 87.4 90.3 93.1 74.5 77.2 80.1 83.0 85.8 88.6
RCU400ATHYZ1 CFR2 CPD1 102.4 94.7 105.9 101.1 109.4 107.5 112.8 114.1 116.2 120.8 119.6 127.6 97.2 85.8 100.6 91.5 104.0 97.5 107.3 103.6 110.6 109.8 113.8 116.0 92.0 77.1 95.3 82.5 98.5 88.0 101.7 93.5 104.9 99.3 108.0 105.0 86.9 69.0 90.0 73.9 93.1 78.9 96.2 84.0 99.3 89.3 102.3 94.5 80.7 59.9 83.6 64.1 86.6 68.6 89.6 73.2 92.6 78.0 95.4 82.7 78.6 57.0 81.5 61.0 84.5 65.4 87.4 69.8 90.3 74.4 93.1 78.9 74.5 51.4 77.2 55.0 80.1 59.1 83.0 63.2 85.8 67.4 88.6 71.6
CPD2 94.7 101.1 107.5 114.1 120.8 127.6 85.8 91.5 97.5 103.6 109.8 116.0 77.1 82.5 88.0 93.5 99.3 105.0 69.0 73.9 78.9 84.0 89.3 94.5 59.9 64.1 68.6 73.2 78.0 82.7 57.0 61.0 65.4 69.8 74.4 78.9 51.4 55.0 59.1 63.2 67.4 71.6
IPT 264.0 266.2 268.5 270.8 273.1 276.0 296.5 299.4 301.7 304.5 306.8 309.7 329.1 331.9 334.8 337.7 340.5 342.8 362.2 365.1 367.9 370.8 373.7 376.5 402.0 404.8 407.7 410.6 413.4 417.0 415.2 418.1 421.0 423.8 426.7 430.4 441.8 444.6 447.5 450.3 453.2 457.4
ABT:Condensate Air Inlet Temperature(℃) CCAP:Cooling Capacity(kW)
CLOT:Chilled Water Outlet Temperature(℃)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h). CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa)
15
IPT:Input Power for Compressor(kW)
SELECTION DATA
Cooling Capacities (R407C) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq
-50HzABT CLOT
25
30
35
40
46
48
52
5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
ABT CLOT
25
30
35
40
46
48
52
5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
CCAP 114.5 118.3 122.2 126.1 129.9 133.6 108.7 112.4 116.2 119.9 123.6 127.2 102.9 106.5 110.1 113.7 117.3 120.7 97.1 100.6 104.1 107.5 110.9 114.3 91.6 95.0 98.4 101.8 105.1 108.3 89.2 92.6 96.0 99.3 102.5 105.7 84.5 87.8 91.0 94.3 97.4 100.5
RCUG40ATHYZ1 CFR CPD 19.7 34.8 20.4 37.0 21.0 39.3 21.7 41.6 22.3 43.9 23.0 46.3 18.7 31.6 19.3 33.6 20.0 35.7 20.6 37.9 21.3 40.1 21.9 42.2 17.7 28.6 18.3 30.4 18.9 32.4 19.6 34.4 20.2 36.4 20.8 38.4 16.7 25.6 17.3 27.4 17.9 29.2 18.5 31.0 19.1 32.8 19.7 34.7 15.7 23.0 16.3 24.7 16.9 26.3 17.5 28.0 18.1 29.7 18.6 31.4 15.3 22.0 15.9 23.5 16.5 25.1 17.1 26.7 17.6 28.4 18.2 30.0 14.5 19.9 15.1 21.3 15.7 22.8 16.2 24.3 16.7 25.8 17.3 27.3
IPT 29.1 29.4 29.6 29.9 30.2 30.4 32.8 33.0 33.3 33.6 33.9 34.2 36.4 36.7 37.0 37.3 37.6 37.9 40.0 40.3 40.7 41.0 41.3 41.7 44.4 44.7 45.1 45.4 45.8 46.2 45.9 46.2 46.6 46.9 47.3 47.7 48.8 49.1 49.5 49.8 50.2 50.7
CCAP 141.2 146.0 150.8 155.5 160.3 164.9 134.1 138.7 143.3 147.9 152.4 156.9 126.9 131.4 135.9 140.3 144.7 148.9 119.7 124.1 128.4 132.6 136.9 141.0 111.1 115.3 119.4 123.4 127.5 131.6 108.3 112.3 116.4 120.4 124.4 128.4 102.5 106.5 110.4 114.2 118.1 122.1
CCAP 353.4 365.4 377.4 389.2 401.0 412.5 335.6 347.1 358.8 370.2 381.5 392.6 317.6 328.8 340.0 351.1 362.0 372.9 299.7 310.5 321.4 332.1 342.6 353.0 278.2 288.6 299.0 309.2 319.2 329.1 271.0 281.4 291.5 301.6 311.4 321.2 256.7 266.8 276.6 286.3 295.8 305.3
RCUG120ATHYZ1 CFR CPD IPT 60.8 88.4 59.5 62.8 89.2 63.7 64.9 90.0 68.1 66.9 90.8 72.6 69.0 91.6 77.2 70.9 92.5 81.8 57.7 99.5 53.5 59.7 100.3 57.3 61.7 101.2 61.4 63.7 102.1 65.5 65.6 102.9 69.6 67.5 103.7 73.9 54.6 110.5 47.8 56.5 111.4 51.3 58.5 112.4 55.0 60.4 113.3 58.7 62.3 114.2 62.5 64.1 115.1 66.4 51.5 121.6 42.4 53.4 122.5 45.6 55.3 123.5 48.9 57.1 124.5 52.4 58.9 125.5 55.8 60.7 126.5 59.4 47.8 36.4 134.9 49.6 39.2 135.8 51.4 42.2 137.0 53.2 45.2 137.9 54.9 48.3 139.1 56.6 51.4 140.2 46.6 34.5 139.3 48.4 37.2 140.3 50.1 40.1 141.5 51.9 42.9 142.4 53.6 45.9 143.6 55.2 48.9 144.8 44.1 30.8 148.2 45.9 33.4 149.1 47.6 36.0 150.4 49.2 38.6 151.3 50.9 41.3 152.6 52.5 44.0 153.9
CCAP 377.2 390.1 402.8 415.5 428.1 440.4 358.2 370.5 382.9 395.2 407.2 419.1 339.0 350.9 362.9 374.7 386.5 397.9 320.0 331.4 343.0 354.4 365.8 376.8 297.2 307.9 319.0 330.0 340.9 351.5 289.6 300.0 311.0 321.8 332.6 343.0 274.4 284.4 295.1 305.6 316.0 326.2
RCUG50ATHYZ1 CFR CPD 24.3 37.5 25.1 39.9 25.9 42.4 26.7 44.9 27.6 47.4 28.4 49.9 23.1 34.1 23.9 36.3 24.6 38.6 25.4 40.9 26.2 43.2 27.0 45.6 21.8 30.8 22.6 32.8 23.4 34.9 24.1 37.1 24.9 39.2 25.6 41.4 20.6 27.7 21.3 29.5 22.1 31.5 22.8 33.4 23.5 35.4 24.3 37.4 19.1 24.1 19.8 25.8 20.5 27.5 21.2 29.3 21.9 31.1 22.6 32.9 18.6 23.0 19.3 24.6 20.0 26.3 20.7 28.0 21.4 29.7 22.1 31.5 17.6 20.8 18.3 22.3 19.0 23.8 19.6 25.4 20.3 27.0 21.0 28.7
IPT 35.5 35.8 36.1 36.4 36.8 37.1 39.9 40.3 40.7 41.0 41.4 41.8 44.5 44.9 45.3 45.6 46.0 46.4 49.0 49.4 49.8 50.3 50.7 51.1 54.5 54.9 55.4 55.8 56.3 56.7 56.3 56.7 57.2 57.7 58.1 58.6 59.9 60.3 60.9 61.4 61.8 62.4
RCUG150ATHYZ1 CFR CPD IPT 64.9 68.0 94.1 67.1 72.9 95.0 69.3 77.9 95.8 71.5 83.0 96.6 73.6 88.2 97.4 75.7 93.6 98.4 61.6 61.2 105.8 63.7 65.6 106.8 65.8 70.1 107.6 68.0 74.9 108.6 70.0 79.6 109.4 72.1 84.5 110.4 58.3 54.6 117.4 60.3 58.7 118.4 62.4 62.8 119.4 64.4 67.1 120.4 66.5 71.5 121.4 68.4 75.9 122.3 55.0 48.5 129.2 57.0 52.1 130.2 59.0 55.9 131.2 60.9 59.8 132.2 62.9 63.9 133.3 64.8 67.9 134.3 51.1 41.7 143.4 52.9 44.8 144.4 54.9 48.2 145.4 56.7 51.7 146.4 58.6 55.3 147.5 60.4 58.8 148.7 49.8 39.5 148.1 51.6 42.5 149.1 53.5 45.8 150.1 55.3 49.1 151.2 57.2 52.5 152.2 59.0 56.0 153.5 47.2 35.4 157.6 48.9 38.1 158.6 50.7 41.1 159.6 52.5 44.1 160.6 54.4 47.3 161.6 56.1 50.5 163.1
ABT:Condensate Air Inlet Temperature(℃)
CCAP 176.7 182.7 188.7 194.6 200.5 206.3 167.8 173.6 179.4 185.1 190.8 196.3 158.8 164.4 170.0 175.6 181.0 186.4 149.9 155.3 160.7 166.0 171.3 176.5 139.1 144.3 149.5 154.6 159.6 164.6 135.5 140.7 145.8 150.8 155.7 160.6 128.3 133.4 138.3 143.2 147.9 152.6
RCUG60ATHYZ1 CFR CPD 30.4 40.6 31.4 43.3 32.5 46.1 33.5 48.9 34.5 51.7 35.5 54.6 28.9 36.8 29.8 39.2 30.8 41.8 31.8 44.4 32.8 47.0 33.8 49.7 27.3 33.1 28.3 35.4 29.2 37.7 30.2 40.1 31.1 42.5 32.1 45.0 25.8 29.6 26.7 31.7 27.6 33.9 28.6 36.1 29.5 38.3 30.4 40.5 23.9 25.7 24.8 27.6 25.7 29.5 26.6 31.4 27.4 33.4 28.3 35.4 23.3 24.4 24.2 26.2 25.1 28.1 25.9 30.0 26.8 31.9 27.6 33.8 22.1 22.0 22.9 23.7 23.8 25.4 24.6 27.1 25.4 28.9 26.2 30.7
IPT 44.2 44.6 45.0 45.4 45.8 46.2 49.7 50.2 50.6 51.0 51.5 51.9 55.2 55.7 56.2 56.6 57.1 57.6 60.8 61.3 61.8 62.2 62.8 63.3 67.4 67.9 68.5 69.0 69.5 70.1 69.7 70.1 70.7 71.2 71.8 72.4 74.1 74.6 75.2 75.7 76.3 77.0
CCAP 188.6 195.0 201.4 207.8 214.0 220.2 179.1 185.3 191.4 197.6 203.6 209.6 169.5 175.5 181.5 187.3 193.2 198.9 160.0 165.7 171.5 177.2 182.9 188.4 148.6 153.9 159.5 165.0 170.4 175.7 144.8 150.0 155.5 160.9 166.3 171.5 137.2 142.2 147.5 152.8 158.0 163.1
RCUG75ATHYZ1 CFR CPD 32.4 46.0 33.5 49.1 34.6 52.2 35.7 55.4 36.8 58.6 37.9 61.9 30.8 41.7 31.9 44.5 32.9 47.4 34.0 50.3 35.0 53.3 36.0 56.3 29.1 37.5 30.2 40.1 31.2 42.7 32.2 45.4 33.2 48.2 34.2 51.0 27.5 33.6 28.5 35.9 29.5 38.3 30.5 40.8 31.4 43.4 32.4 45.9 25.6 29.1 26.5 31.2 27.4 33.4 28.4 35.6 29.3 37.9 30.2 40.2 24.9 27.7 25.8 29.7 26.7 31.8 27.7 33.9 28.6 36.2 29.5 38.4 23.6 25.0 24.5 26.8 25.4 28.7 26.3 30.7 27.2 32.8 28.0 34.8
IPT 47.1 47.5 47.9 48.3 48.7 49.2 52.9 53.4 53.8 54.3 54.7 55.2 58.7 59.2 59.7 60.2 60.7 61.1 64.6 65.1 65.6 66.1 66.6 67.1 71.7 72.2 72.7 73.2 73.7 74.4 74.1 74.6 75.1 75.6 76.1 76.8 78.8 79.3 79.8 80.3 80.8 81.6
CCAP 282.5 292.0 301.6 311.1 320.5 329.7 268.1 277.4 286.6 295.9 304.9 313.8 253.8 262.8 271.7 280.6 289.4 297.9 239.5 248.1 256.8 265.3 273.7 282.1 222.3 230.5 238.8 246.9 255.0 263.1 216.5 224.7 232.8 240.8 248.7 256.8 205.0 213.0 220.9 228.5 236.2 244.1
RCUG100ATHYZ1 CFR CPD IPT 48.6 70.9 50.7 50.2 71.5 53.9 51.9 72.2 57.2 53.5 72.8 60.6 55.1 73.5 64.0 56.7 74.1 67.4 46.1 79.9 46.1 47.7 80.6 49.1 49.3 81.3 52.1 50.9 82.1 55.2 52.4 82.8 58.4 54.0 83.5 61.6 43.7 89.0 41.7 45.2 89.8 44.4 46.7 90.5 47.2 48.3 91.3 50.1 49.8 92.1 53.0 51.2 92.8 55.9 41.2 98.0 37.4 42.7 98.9 39.9 44.2 99.7 42.5 45.6 100.5 45.2 47.1 101.4 47.9 48.5 102.2 50.6 38.2 32.6 108.9 39.6 34.9 109.8 41.1 37.2 110.7 42.5 39.6 111.7 43.9 42.0 112.5 45.2 44.5 113.5 37.2 31.1 112.5 38.6 33.3 113.4 40.0 35.5 114.4 41.4 37.8 115.4 42.8 40.1 116.2 44.2 42.5 117.2 35.3 28.1 119.8 36.6 30.1 120.6 38.0 32.2 121.7 39.3 34.3 122.8 40.6 36.5 123.6 42.0 38.8 124.7
CCAP 423.7 438.0 452.4 466.6 480.8 494.6 402.2 416.1 430.0 443.8 457.3 470.7 380.8 394.2 407.6 420.9 434.0 446.8 359.2 372.2 385.1 397.9 410.6 423.1 333.4 345.8 358.2 370.3 382.5 394.7 324.8 337.0 349.3 361.1 373.1 385.2 307.5 319.4 331.3 342.7 354.4 366.2
RCUG160ATHYZ1 CFR CPD IPT 72.9 50.5 106.4 75.3 53.9 107.3 77.8 57.3 108.3 80.2 60.8 109.2 82.7 64.4 110.3 85.1 68.0 111.2 69.2 45.7 119.8 71.6 48.8 120.9 73.9 52.0 122.0 76.3 55.2 123.1 78.6 58.5 124.2 80.9 61.9 125.3 65.5 41.2 133.4 67.8 44.0 134.7 70.1 46.9 135.8 72.4 49.9 136.9 74.6 52.9 138.1 76.8 56.0 139.2 61.8 36.8 147.0 64.0 39.4 148.3 66.2 42.1 149.5 68.4 44.8 150.8 70.6 47.6 152.1 72.8 50.4 153.3 57.3 31.9 163.4 59.5 34.2 164.6 61.6 36.6 166.1 63.7 39.0 167.5 65.8 41.5 168.8 67.9 44.1 170.2 55.8 30.3 168.8 58.0 32.5 170.1 60.1 34.9 171.6 62.1 37.2 173.1 64.2 39.6 174.3 66.2 42.1 175.8 52.9 27.3 179.7 54.9 29.4 181.0 57.0 31.5 182.6 58.9 33.6 184.2 60.9 35.8 185.5 63.0 38.2 187.1
CCAP 530.1 548.2 566.1 583.9 601.5 618.8 503.4 520.7 538.1 555.3 572.3 589.0 476.5 493.2 510.0 526.7 543.1 559.3 449.6 465.8 482.0 498.1 513.9 529.5 417.3 433.0 448.5 463.8 478.8 493.7 406.5 422.0 437.3 452.4 467.1 481.7 385.0 400.1 414.9 429.5 443.8 457.9
RCUG180ATHYZ1 CFR CPD IPT 91.2 132.6 75.7 94.3 133.9 80.8 97.4 134.9 85.9 100.4 136.2 91.2 103.4 137.4 96.6 106.4 102.0 138.7 86.6 149.2 68.6 89.5 150.5 73.2 92.5 151.7 78.0 95.5 153.1 82.8 98.4 154.4 87.7 101.3 155.6 92.7 81.9 165.7 61.7 84.8 167.1 65.9 87.7 168.5 70.3 90.6 169.9 74.8 93.4 171.3 79.3 96.2 172.7 84.0 77.3 182.4 55.2 80.1 183.8 59.1 82.9 185.3 63.1 85.7 186.7 67.2 88.4 188.3 71.3 91.1 189.8 75.6 71.8 47.8 202.3 74.5 51.3 203.7 77.1 54.9 205.5 79.8 58.6 206.9 82.3 62.3 208.6 84.9 66.0 210.3 69.9 45.5 209.0 72.6 48.9 210.4 75.2 52.3 212.2 77.8 55.8 213.6 80.3 59.4 215.4 82.8 63.0 217.2 66.2 41.0 222.3 68.8 44.1 223.7 71.3 47.3 225.6 73.9 50.5 227.0 76.3 53.8 228.9 78.7 57.1 230.9
CCAP 565.7 585.1 604.2 623.3 642.1 660.6 537.2 555.8 574.3 592.8 610.8 628.7 508.4 526.4 544.4 562.0 579.7 596.8 479.9 497.0 514.4 531.5 548.6 565.2 445.7 461.8 478.5 494.9 511.3 527.2 434.3 450.1 466.5 482.7 498.9 514.5 411.5 426.6 442.6 458.3 474.1 489.2
RCUG200ATHYZ1 CFR CPD IPT 97.3 141.2 85.8 100.6 142.4 91.6 103.9 143.7 97.4 107.2 103.4 144.9 110.4 109.5 146.1 113.6 115.6 147.6 92.4 158.6 77.7 95.6 160.2 82.9 98.8 161.4 88.3 101.9 162.9 93.9 105.0 164.1 99.4 108.1 105.1 165.7 87.4 176.1 69.9 90.5 177.6 74.7 93.6 179.1 79.7 96.7 180.6 84.7 99.7 182.2 89.9 102.6 183.4 95.1 82.5 193.8 62.6 85.5 195.3 66.9 88.5 196.8 71.5 91.4 198.4 76.1 94.3 199.9 80.9 97.2 201.4 85.7 76.7 54.3 215.1 79.4 58.1 216.6 82.3 62.2 218.1 85.1 66.4 219.6 87.9 70.7 221.2 90.7 74.9 223.1 74.7 51.6 222.2 77.4 55.3 223.7 80.2 59.2 225.2 83.0 63.3 226.7 85.8 67.4 228.3 88.5 71.5 230.3 70.8 46.5 236.3 73.4 49.9 237.9 76.1 53.5 239.4 78.8 57.3 240.9 81.5 61.1 242.5 84.1 64.9 244.7
CCAP:Cooling Capacity(kW)
CLOT:Chilled Water Outlet Temperature(℃) CFR:Chilled Water Flow Rate at 5℃ Difference Between Inlet and Outlet Temperature(m3/h)
CPD:Water Cooler Pressure Drop(kPa)
IPT:Input Power for Compressor(kW)
16
SELECTION DATA
Cooling Capacities (R407C) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq
-50HzABT
25
30
35
40
46
48
52
ABT
25
30
35
40
46
48
52
CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
CCAP 706.8 730.9 754.8 778.5 802.0 825.1 671.1 694.2 717.5 740.4 763.0 785.3 635.3 657.5 680.0 702.3 724.1 745.7 599.4 621.1 642.7 664.1 685.2 706.0 556.4 577.3 597.9 618.4 638.4 658.2 542.1 562.7 583.0 603.1 622.8 642.3 513.4 533.5 553.2 572.6 591.7 610.5
CFR1 60.8 62.8 64.9 66.9 69.0 70.9 57.7 59.7 61.7 63.7 65.6 67.5 54.6 56.5 58.5 60.4 62.3 64.1 51.5 53.4 55.3 57.1 58.9 60.7 47.8 49.6 51.4 53.2 54.9 56.6 46.6 48.4 50.1 51.9 53.6 55.2 44.1 45.9 47.6 49.2 50.9 52.5
RCUG240ATHYZ1 CFR2 CPD1 60.8 59.5 62.8 63.7 64.9 68.1 66.9 72.6 69.0 77.2 70.9 81.8 57.7 53.5 59.7 57.3 61.7 61.4 63.7 65.5 65.6 69.6 67.5 73.9 54.6 47.8 56.5 51.3 58.5 55.0 60.4 58.7 62.3 62.5 64.1 66.4 51.5 42.4 53.4 45.6 55.3 48.9 57.1 52.4 58.9 55.8 60.7 59.4 47.8 36.4 49.6 39.2 51.4 42.2 53.2 45.2 54.9 48.3 56.6 51.4 46.6 34.5 48.4 37.2 50.1 40.1 51.9 42.9 53.6 45.9 55.2 48.9 44.1 30.8 45.9 33.4 47.6 36.0 49.2 38.6 50.9 41.3 52.5 44.0
CPD2 59.5 63.7 68.1 72.6 77.2 81.8 53.5 57.3 61.4 65.5 69.6 73.9 47.8 51.3 55.0 58.7 62.5 66.4 42.4 45.6 48.9 52.4 55.8 59.4 36.4 39.2 42.2 45.2 48.3 51.4 34.5 37.2 40.1 42.9 45.9 48.9 30.8 33.4 36.0 38.6 41.3 44.0
IPT 176.8 178.5 179.9 181.6 183.2 184.9 199.0 200.7 202.3 204.2 205.8 207.5 221.0 222.8 224.7 226.6 228.4 230.3 243.1 245.0 247.1 249.0 251.0 253.1 269.8 271.6 274.0 275.8 278.1 280.5 278.6 280.5 282.9 284.8 287.2 289.6 296.4 298.2 300.8 302.7 305.3 307.8
CCAP 730.5 755.5 780.2 804.8 829.1 853.0 693.7 717.6 741.6 765.4 788.7 811.8 656.6 679.7 702.9 725.8 748.5 770.7 619.7 641.9 664.3 686.4 708.3 729.8 575.4 596.5 618.0 639.1 660.1 680.6 560.6 581.4 602.5 623.4 644.0 664.2 531.0 551.2 571.7 591.9 611.9 631.4
CFR1 64.9 67.1 69.3 71.5 73.6 75.7 61.6 63.7 65.8 68.0 70.0 72.1 58.3 60.3 62.4 64.4 66.5 68.4 55.0 57.0 59.0 60.9 62.9 64.8 51.1 52.9 54.9 56.7 58.6 60.4 49.8 51.6 53.5 55.3 57.2 59.0 47.2 48.9 50.7 52.5 54.4 56.1
RCUG270ATHYZ1 CFR2 CPD1 60.8 68.0 62.8 72.9 64.9 77.9 66.9 83.0 69.0 88.2 70.9 93.6 57.7 61.2 59.7 65.6 61.7 70.1 63.7 74.9 65.6 79.6 67.5 84.5 54.6 54.6 56.5 58.7 58.5 62.8 60.4 67.1 62.3 71.5 64.1 75.9 51.5 48.5 53.4 52.1 55.3 55.9 57.1 59.8 58.9 63.9 60.7 67.9 47.8 41.7 49.6 44.8 51.4 48.2 53.2 51.7 54.9 55.3 56.6 58.8 46.6 39.5 48.4 42.5 50.1 45.8 51.9 49.1 53.6 52.5 55.2 56.0 44.1 35.4 45.9 38.1 47.6 41.1 49.2 44.1 50.9 47.3 52.5 50.5
CPD2 59.5 63.7 68.1 72.6 77.2 81.8 53.5 57.3 61.4 65.5 69.6 73.9 47.8 51.3 55.0 58.7 62.5 66.4 42.4 45.6 48.9 52.4 55.8 59.4 36.4 39.2 42.2 45.2 48.3 51.4 34.5 37.2 40.1 42.9 45.9 48.9 30.8 33.4 36.0 38.6 41.3 44.0
IPT 182.6 184.2 185.7 187.4 189.0 190.9 205.3 207.1 208.7 210.7 212.3 214.2 227.9 229.8 231.8 233.7 235.7 237.4 250.8 252.7 254.8 256.7 258.8 260.8 278.3 280.2 282.4 284.3 286.5 288.9 287.4 289.4 291.6 293.5 295.8 298.3 305.7 307.7 310.0 312.0 314.3 317.1
CCAP 754.3 780.1 805.6 831.1 856.1 880.8 716.3 741.0 765.7 790.4 814.3 838.3 677.9 701.9 725.8 749.4 772.9 795.7 639.9 662.7 685.9 708.7 731.5 753.5 594.3 615.8 638.0 659.9 681.8 702.9 579.1 600.1 622.1 643.6 665.2 686.1 548.7 568.8 590.1 611.1 632.1 652.3
CFR1 64.9 67.1 69.3 71.5 73.6 75.7 61.6 63.7 65.8 68.0 70.0 72.1 58.3 60.3 62.4 64.4 66.5 68.4 55.0 57.0 59.0 60.9 62.9 64.8 51.1 52.9 54.9 56.7 58.6 60.4 49.8 51.6 53.5 55.3 57.2 59.0 47.2 48.9 50.7 52.5 54.4 56.1
RCUG300ATHYZ1 CFR2 CPD1 64.9 68.0 67.1 72.9 69.3 77.9 71.5 83.0 73.6 88.2 75.7 93.6 61.6 61.2 63.7 65.6 65.8 70.1 68.0 74.9 70.0 79.6 72.1 84.5 58.3 54.6 60.3 58.7 62.4 62.8 64.4 67.1 66.5 71.5 68.4 75.9 55.0 48.5 57.0 52.1 59.0 55.9 60.9 59.8 62.9 63.9 64.8 67.9 51.1 41.7 52.9 44.8 54.9 48.2 56.7 51.7 58.6 55.3 60.4 58.8 49.8 39.5 51.6 42.5 53.5 45.8 55.3 49.1 57.2 52.5 59.0 56.0 47.2 35.4 48.9 38.1 50.7 41.1 52.5 44.1 54.4 47.3 56.1 50.5
CPD2 68.0 72.9 77.9 83.0 88.2 93.6 61.2 65.6 70.1 74.9 79.6 84.5 54.6 58.7 62.8 67.1 71.5 75.9 48.5 52.1 55.9 59.8 63.9 67.9 41.7 44.8 48.2 51.7 55.3 58.8 39.5 42.5 45.8 49.1 52.5 56.0 35.4 38.1 41.1 44.1 47.3 50.5
IPT 188.3 189.9 191.5 193.2 194.8 196.8 211.5 213.6 215.2 217.2 218.9 220.9 234.7 236.8 238.8 240.9 242.9 244.5 258.4 260.4 262.5 264.5 266.5 268.6 286.8 288.8 290.8 292.9 294.9 297.4 296.2 298.2 300.3 302.3 304.4 307.0 315.1 317.2 319.2 321.2 323.3 326.3
CCAP 907.2 938.2 968.9 999.4 1029.6 1059.2 861.5 891.2 921.0 950.5 979.5 1008.1 815.4 844.1 872.9 901.4 929.5 957.2 769.5 797.2 825.0 852.5 879.6 906.2 714.5 740.9 767.5 793.7 819.7 845.1 696.1 722.1 748.3 774.2 799.7 824.8 659.4 684.5 710.0 735.0 759.8 784.0
CFR1 91.2 94.3 97.4 100.4 103.4 106.4 86.6 89.5 92.5 95.5 98.4 101.3 81.9 84.8 87.7 90.6 93.4 96.2 77.3 80.1 82.9 85.7 88.4 91.1 71.8 74.5 77.1 79.8 82.3 84.9 69.9 72.6 75.2 77.8 80.3 82.8 66.2 68.8 71.3 73.9 76.3 78.7
RCUG330ATHYZ1 CFR2 CPD1 64.9 75.7 67.1 80.8 69.3 85.9 71.5 91.2 73.6 96.6 75.7 102.0 61.6 68.6 63.7 73.2 65.8 78.0 68.0 82.8 70.0 87.7 72.1 92.7 58.3 61.7 60.3 65.9 62.4 70.3 64.4 74.8 66.5 79.3 68.4 84.0 55.0 55.2 57.0 59.1 59.0 63.1 60.9 67.2 62.9 71.3 64.8 75.6 51.1 47.8 52.9 51.3 54.9 54.9 56.7 58.6 58.6 62.3 60.4 66.0 49.8 45.5 51.6 48.9 53.5 52.3 55.3 55.8 57.2 59.4 59.0 63.0 47.2 41.0 48.9 44.1 50.7 47.3 52.5 50.5 54.4 53.8 56.1 57.1
CPD2 68.0 72.9 77.9 83.0 88.2 93.6 61.2 65.6 70.1 74.9 79.6 84.5 54.6 58.7 62.8 67.1 71.5 75.9 48.5 52.1 55.9 59.8 63.9 67.9 41.7 44.8 48.2 51.7 55.3 58.8 39.5 42.5 45.8 49.1 52.5 56.0 35.4 38.1 41.1 44.1 47.3 50.5
IPT 226.8 228.8 230.7 232.8 234.8 237.1 255.0 257.3 259.3 261.7 263.8 266.1 283.1 285.5 287.9 290.4 292.8 295.0 311.6 314.0 316.5 319.0 321.5 324.1 345.7 348.1 350.9 353.3 356.1 359.1 357.1 359.5 362.3 364.7 367.6 370.7 379.8 382.3 385.2 387.6 390.6 394.0
ABT:Condensate Air Inlet Temperature(℃)
CLOT:Chilled Water Outlet Temperature(℃)
CCAP:Cooling Capacity(kW) CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h). CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa)
17
IPT:Input Power for Compressor(kW)
SELECTION DATA
Cooling Capacities (R407C) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq
-50HzABT
25
30
35
40
46
48
52
ABT
25
30
35
40
46
48
52
CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 CLOT 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10 5 6 7 8 9 10
CCAP 942.9 975.2 1007.0 1038.8 1070.2 1101.1 895.4 926.3 957.1 988.0 1017.9 1047.9 847.4 877.3 907.3 936.7 966.2 994.7 799.9 828.4 857.4 885.9 914.4 941.9 742.9 769.7 797.5 824.9 852.2 878.7 723.9 750.1 777.6 804.6 831.5 857.6 685.9 711.0 737.7 763.9 790.1 815.4
CFR1 97.3 100.6 103.9 107.2 110.4 113.6 92.4 95.6 98.8 101.9 105.0 108.1 87.4 90.5 93.6 96.7 99.7 102.6 82.5 85.5 88.5 91.4 94.3 97.2 76.7 79.4 82.3 85.1 87.9 90.7 74.7 77.4 80.2 83.0 85.8 88.5 70.8 73.4 76.1 78.8 81.5 84.1
RCUG350ATHYZ1 CFR2 CPD1 85.8 64.9 91.6 67.1 97.4 69.3 103.4 71.5 109.5 73.6 115.6 75.7 77.7 61.6 82.9 63.7 88.3 65.8 93.9 68.0 99.4 70.0 105.1 72.1 69.9 58.3 74.7 60.3 79.7 62.4 84.7 64.4 89.9 66.5 95.1 68.4 62.6 55.0 66.9 57.0 71.5 59.0 76.1 60.9 80.9 62.9 85.7 64.8 51.1 54.3 52.9 58.1 54.9 62.2 56.7 66.4 58.6 70.7 60.4 74.9 49.8 51.6 51.6 55.3 53.5 59.2 55.3 63.3 57.2 67.4 59.0 71.5 47.2 46.5 48.9 49.9 50.7 53.5 52.5 57.3 54.4 61.1 56.1 64.9
CPD2 68.0 72.9 77.9 83.0 88.2 93.6 61.2 65.6 70.1 74.9 79.6 84.5 54.6 58.7 62.8 67.1 71.5 75.9 48.5 52.1 55.9 59.8 63.9 67.9 41.7 44.8 48.2 51.7 55.3 58.8 39.5 42.5 45.8 49.1 52.5 56.0 35.4 38.1 41.1 44.1 47.3 50.5
IPT 235.4 237.4 239.4 241.5 243.5 246.1 264.4 266.9 269.0 271.5 273.6 276.1 293.4 296.0 298.5 301.1 303.6 305.7 323.0 325.5 328.1 330.6 333.2 335.7 358.4 361.0 363.5 366.1 368.6 371.8 370.3 372.8 375.4 377.9 380.4 383.8 393.9 396.4 399.0 401.5 404.1 407.9
CCAP 1060.2 1096.3 1132.2 1167.7 1203.0 1237.6 1006.7 1041.3 1076.3 1110.6 1144.6 1177.9 952.9 986.3 1020.0 1053.4 1086.1 1118.6 899.1 931.6 964.1 996.2 1027.7 1058.9 834.6 865.9 896.9 927.6 957.6 987.4 813.1 844.1 874.5 904.7 934.3 963.5 770.1 800.3 829.8 859.0 887.5 915.8
CFR1 91.2 94.3 97.4 100.4 103.4 106.4 86.6 89.5 92.5 95.5 98.4 101.3 81.9 84.8 87.7 90.6 93.4 96.2 77.3 80.1 82.9 85.7 88.4 91.1 71.8 74.5 77.1 79.8 82.3 84.9 69.9 72.6 75.2 77.8 80.3 82.8 66.2 68.8 71.3 73.9 76.3 78.7
RCUG360ATHYZ1 CFR2 CPD1 91.2 75.7 94.3 80.8 97.4 85.9 100.4 91.2 103.4 96.6 106.4 102.0 86.6 68.6 89.5 73.2 92.5 78.0 95.5 82.8 98.4 87.7 101.3 92.7 81.9 61.7 84.8 65.9 87.7 70.3 90.6 74.8 93.4 79.3 96.2 84.0 77.3 55.2 80.1 59.1 82.9 63.1 85.7 67.2 88.4 71.3 91.1 75.6 71.8 47.8 74.5 51.3 77.1 54.9 79.8 58.6 82.3 62.3 84.9 66.0 69.9 45.5 72.6 48.9 75.2 52.3 77.8 55.8 80.3 59.4 82.8 63.0 66.2 41.0 68.8 44.1 71.3 47.3 73.9 50.5 76.3 53.8 78.7 57.1
CPD2 75.7 80.8 85.9 91.2 96.6 102.0 68.6 73.2 78.0 82.8 87.7 92.7 61.7 65.9 70.3 74.8 79.3 84.0 55.2 59.1 63.1 67.2 71.3 75.6 47.8 51.3 54.9 58.6 62.3 66.0 45.5 48.9 52.3 55.8 59.4 63.0 41.0 44.1 47.3 50.5 53.8 57.1
IPT 265.2 267.7 269.9 272.4 274.9 277.4 298.5 301.0 303.5 306.3 308.8 311.2 331.5 334.3 337.1 339.8 342.6 345.4 364.7 367.5 370.6 373.4 376.5 379.6 404.6 407.4 410.9 413.7 417.2 420.7 418.0 420.8 424.4 427.2 430.8 434.4 444.6 447.4 451.2 454.0 457.9 461.7
CCAP 1095.8 1133.3 1170.3 1207.2 1243.6 1279.4 1040.6 1076.4 1112.4 1148.1 1183.0 1217.7 984.9 1019.5 1054.4 1088.7 1122.8 1156.1 929.5 962.8 996.5 1029.6 1062.5 1094.6 863.0 894.8 927.0 958.7 990.2 1020.9 840.9 872.1 903.8 935.1 966.1 996.3 796.6 826.7 857.5 887.8 917.8 947.1
CFR1 97.3 100.6 103.9 107.2 110.4 113.6 92.4 95.6 98.8 101.9 105.0 108.1 87.4 90.5 93.6 96.7 99.7 102.6 82.5 85.5 88.5 91.4 94.3 97.2 76.7 79.4 82.3 85.1 87.9 90.7 74.7 77.4 80.2 83.0 85.8 88.5 70.8 73.4 76.1 78.8 81.5 84.1
RCUG380ATHYZ1 CFR2 CPD1 91.2 85.8 94.3 91.6 97.4 97.4 100.4 103.4 103.4 109.5 106.4 115.6 86.6 77.7 89.5 82.9 92.5 88.3 95.5 93.9 98.4 99.4 101.3 105.1 81.9 69.9 84.8 74.7 87.7 79.7 90.6 84.7 93.4 89.9 96.2 95.1 77.3 62.6 80.1 66.9 82.9 71.5 85.7 76.1 88.4 80.9 91.1 85.7 71.8 54.3 74.5 58.1 77.1 62.2 79.8 66.4 82.3 70.7 84.9 74.9 69.9 51.6 72.6 55.3 75.2 59.2 77.8 63.3 80.3 67.4 82.8 71.5 66.2 46.5 68.8 49.9 71.3 53.5 73.9 57.3 76.3 61.1 78.7 64.9
CPD2 75.7 80.8 85.9 91.2 96.6 102.0 68.6 73.2 78.0 82.8 87.7 92.7 61.7 65.9 70.3 74.8 79.3 84.0 55.2 59.1 63.1 67.2 71.3 75.6 47.8 51.3 54.9 58.6 62.3 66.0 45.5 48.9 52.3 55.8 59.4 63.0 41.0 44.1 47.3 50.5 53.8 57.1
IPT 273.8 276.3 278.6 281.1 283.5 286.3 307.9 310.7 313.1 316.1 318.5 321.3 341.8 344.7 347.6 350.6 353.5 356.1 376.2 379.1 382.2 385.1 388.2 391.3 417.4 420.3 423.6 426.5 429.8 433.4 431.1 434.1 437.4 440.3 443.7 447.5 458.6 461.6 465.0 467.9 471.4 475.6
CCAP 1131.5 1170.2 1208.4 1246.6 1284.2 1321.3 1074.5 1111.5 1148.6 1185.6 1221.5 1257.4 1016.9 1052.8 1088.7 1124.0 1159.4 1193.6 959.9 994.1 1028.9 1063.1 1097.3 1130.3 891.5 923.6 957.0 989.9 1022.7 1054.4 868.7 900.1 933.1 965.5 997.8 1029.1 823.1 853.2 885.2 916.7 948.1 978.5
CFR1 97.3 100.6 103.9 107.2 110.4 113.6 92.4 95.6 98.8 101.9 105.0 108.1 87.4 90.5 93.6 96.7 99.7 102.6 82.5 85.5 88.5 91.4 94.3 97.2 76.7 79.4 82.3 85.1 87.9 90.7 74.7 77.4 80.2 83.0 85.8 88.5 70.8 73.4 76.1 78.8 81.5 84.1
RCUG400ATHYZ1 CFR2 CPD1 97.3 85.8 100.6 91.6 103.9 97.4 107.2 103.4 110.4 109.5 113.6 115.6 92.4 77.7 95.6 82.9 98.8 88.3 101.9 93.9 105.0 99.4 108.1 105.1 87.4 69.9 90.5 74.7 93.6 79.7 96.7 84.7 99.7 89.9 102.6 95.1 82.5 62.6 85.5 66.9 88.5 71.5 91.4 76.1 94.3 80.9 97.2 85.7 76.7 54.3 79.4 58.1 82.3 62.2 85.1 66.4 87.9 70.7 90.7 74.9 74.7 51.6 77.4 55.3 80.2 59.2 83.0 63.3 85.8 67.4 88.5 71.5 70.8 46.5 73.4 49.9 76.1 53.5 78.8 57.3 81.5 61.1 84.1 64.9
CPD2 85.8 91.6 97.4 103.4 109.5 115.6 77.7 82.9 88.3 93.9 99.4 105.1 69.9 74.7 79.7 84.7 89.9 95.1 62.6 66.9 71.5 76.1 80.9 85.7 54.3 58.1 62.2 66.4 70.7 74.9 51.6 55.3 59.2 63.3 67.4 71.5 46.5 49.9 53.5 57.3 61.1 64.9
IPT 282.4 284.9 287.3 289.8 292.2 295.3 317.3 320.3 322.8 325.8 328.3 331.3 352.1 355.2 358.2 361.3 364.3 366.8 387.6 390.6 393.7 396.7 399.8 402.9 430.1 433.2 436.2 439.3 442.4 446.1 444.3 447.4 450.4 453.5 456.5 460.6 472.7 475.7 478.8 481.8 484.9 489.4
ABT:Condensate Air Inlet Temperature(℃) CCAP:Cooling Capacity(kW)
CLOT:Chilled Water Outlet Temperature(℃)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h). CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa)
18
IPT:Input Power for Compressor(kW)
SELECTION DATA
Electric Data (Voltage:380V) 35℃ Condenser Air Inlet Temperature Model
Unit Main Power Voltage
RCU40ATHYZ1 RCU50ATHYZ1 RCU60ATHYZ1 RCU75ATHYZ1 RCU100ATHYZ1 RCU120ATHYZ1 RCU150ATHYZ1 RCU160ATHYZ1 RCU180ATHYZ1 RCU200ATHYZ1 RCU240ATHYZ1 RCU270ATHYZ1 RCU300ATHYZ1 RCU330ATHYZ1 RCU350ATHYZ1 RCU360ATHYZ1 RCU380ATHYZ1 RCU400ATHYZ1 RCUG40ATHYZ1 RCUG50ATHYZ1 RCUG60ATHYZ1 RCUG75ATHYZ1 RCUG100ATHYZ1 RCUG120ATHYZ1 RCUG150ATHYZ1 RCUG160ATHYZ1 RCUG180ATHYZ1 RCUG200ATHYZ1 RCUG240ATHYZ1 RCUG270ATHYZ1 RCUG300ATHYZ1 RCUG330ATHYZ1 RCUG350ATHYZ1 RCUG360ATHYZ1 RCUG380ATHYZ1 RCUG400ATHYZ1
380
RNC:Running Current
Hz
50
Application Voltage(V) Max.
Min.
418
Compressor(Three Phases) STC(A)
342
114 148 178 178 148 178 178 148 178 178 178 178 178 178 178 178 178 178 114 148 178 178 148 178 178 148 178 178 178 178 178 178 178 178 178 178
Refrigeration RNC(A) 58 75 95 100 2×75 2×95 2×100 3×75 3×95 3×100 4×95 2×100+2×95 4×100 3×95+2×100 5×100 6×95 3×100+3×95 6×100 64 81 102 107 2×81 2×102 2×107 3×81 3×102 3×107 4×102 2×107+2×102 4×107 3×102+2×107 5×107 6×102 3×107+3×102 6×107
IPT (kW) 34.6 42.3 52.5 55.8 2×42.3 2×52.5 2×55.8 3×42.3 3×52.5 3×55.8 4×52.5 2×55.8+2×52.5 4×55.8 3×52.5+2×55.8 5×55.8 6×52.5 3×55.8+3×52.5 6×55.8 36.6 45.3 56.2 59.7 2×45.3 2×56.2 2×59.7 3×45.3 3×56.2 3×59.7 4×56.2 2×59.7+2×56.2 4×59.7 3×56.2+2×59.7 5×59.7 6×56.2 3×59.7+3×56.2 6×59.7
Motor for Condenser Fan RNC(A) 4×2.7 4×2.7 4×2.7 4×2.7 8×2.7 8×2.7 8×2.7 12×2.7 12×2.7 12×2.7 16×2.7 16×2.7 16×2.7 20×2.7 20×2.7 24×2.7 24×2.7 24×2.7 4×2.7 4×2.7 4×2.7 4×2.7 8×2.7 8×2.7 8×2.7 12×2.7 12×2.7 12×2.7 16×2.7 16×2.7 16×2.7 20×2.7 20×2.7 24×2.7 24×2.7 24×2.7
IPT (kW) 4×1.1 4×1.1 4×1.1 4×1.1 8×1.1 8×1.1 8×1.1 12×1.1 12×1.1 12×1.1 16×1.1 16×1.1 16×1.1 20×1.1 20×1.1 24×1.1 24×1.1 24×1.1 4×1.1 4×1.1 4×1.1 4×1.1 8×1.1 8×1.1 8×1.1 12×1.1 12×1.1 12×1.1 16×1.1 16×1.1 16×1.1 20×1.1 20×1.1 24×1.1 24×1.1 24×1.1
Maximum Unit Current(A) 77 99 125 132 198 251 264 297 376 396 502 515 528 640 660 752 772 792 84 107 135 141 214 269 282 321 404 424 539 552 565 686 706 808 828 847
IPT:Power Input
1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit General Data. 2. The starting current is indicated for each compressor. 3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the maximum current within the unit working range. Supplied Voltage: Rated Voltage×0.9 Condenser Air Inlet Temperature: 43 ℃ Chilled Water Outlet Temperature: 10℃ Capacity Control: 100% Therefore, the size of wiring and fuses must be determined according to applicable national and local codes. 4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below. One-Compressor Maximum Instantaneous
STC
Current 5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan motor above. 19
SELECTION DATA
Electric Data (Voltage:415V) 35℃ Condenser Air Inlet Temperature Unit Main Power
Model
Voltage
Max.
Min.
Compressor(Three Phases) STC(A)
Motor for Condenser Fan
Refrigeration
Maximum Unit Current(A)
RNC(A)
IPT (kW)
RNC(A)
IPT (kW)
RCU40ATHYZ1
125
53
34.6
4×2.7
4×1.1
RCU50ATHYZ1
161
69
42.3
4×2.7
4×1.1
91
RCU60ATHYZ1
195
87
52.5
4×2.7
4×1.1
115
RCU75ATHYZ1
195
92
55.8
4×2.7
4×1.1
121
RCU100ATHYZ1
161
2×69
2×42.3
8×2.7
8×1.1
181
RCU120ATHYZ1
195
2×87
2×52.5
8×2.7
8×1.1
230
RCU150ATHYZ1
195
2×92
2×55.8
8×2.7
8×1.1
242
RCU160ATHYZ1
161
3×69
3×42.3
12×2.7
12×1.1
272
RCU180ATHYZ1
195
3×87
3×52.5
12×2.7
12×1.1
344
RCU200ATHYZ1
195
3×92
3×55.8
12×2.7
12×1.1
363
RCU240ATHYZ1
195
4×87
4×52.5
16×2.7
16×1.1
459
RCU270ATHYZ1
195
2×92+2×87
2×55.8+2×52.5
16×2.7
16×1.1
471
RCU300ATHYZ1
195
4×92
4×55.8
16×2.7
16×1.1
483
RCU330ATHYZ1
195
3×87+2×92
3×52.5+2×55.8
20×2.7
20×1.1
586
RCU350ATHYZ1
195
5×92
5×55.8
20×2.7
20×1.1
604
RCU360ATHYZ1
195
6×87
6×52.5
24×2.7
24×1.1
689
RCU380ATHYZ1
195
3×92+3×87
3×55.8+3×52.5
24×2.7
24×1.1
707
RCU400ATHYZ1
Hz
Application Voltage(V)
70
195
6×92
6×55.8
24×2.7
24×1.1
725
125
59
36.6
4×2.7
4×1.1
77
RCUG50ATHYZ1
161
74
45.3
4×2.7
4×1.1
98
RCUG60ATHYZ1
195
93
56.2
4×2.7
4×1.1
123
RCUG40ATHYZ1
415
50
456
374
RCUG75ATHYZ1
195
98
59.7
4×2.7
4×1.1
129
RCUG100ATHYZ1
161
2×74
2×45.3
8×2.7
8×1.1
196
RCUG120ATHYZ1
195
2×93
2×56.2
8×2.7
8×1.1
247
RCUG150ATHYZ1
195
2×98
2×59.7
8×2.7
8×1.1
259
RCUG160ATHYZ1
161
3×74
3×45.3
12×2.7
12×1.1
294
RCUG180ATHYZ1
195
3×93
3×56.2
12×2.7
12×1.1
370
RCUG200ATHYZ1
195
3×98
3×59.7
12×2.7
12×1.1
388
RCUG240ATHYZ1
195
4×93
4×56.2
16×2.7
16×1.1
493
RCUG270ATHYZ1
195
2×98+2×93
2×59.7+2×56.2
16×2.7
16×1.1
505
RCUG300ATHYZ1
195
4×98
4×59.7
16×2.7
16×1.1
517
RCUG330ATHYZ1
195
3×93+2×98
3×56.2+2×59.7
20×2.7
20×1.1
629
RCUG350ATHYZ1
195
5×98
5×59.7
20×2.7
20×1.1
647
RCUG360ATHYZ1
195
6×93
6×56.2
24×2.7
24×1.1
740
RCUG380ATHYZ1
195
3×98+3×93
3×59.7+3×56.2
24×2.7
24×1.1
758
195
6×98
6×59.7
24×2.7
24×1.1
776
RCUG400ATHYZ1
RNC:Running Current
IPT:Power Input
1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit General Data. 2. The starting current is indicated for each compressor. 3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the maximum current within the unit working range. Supplied Voltage: Rated Voltage×0.9 Condenser Air Inlet Temperature: 43℃ Chilled Water Outlet Temperature: 10℃ Capacity Control: 100% Therefore, the size of wiring and fuses must be determined according to applicable national and local codes. 4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below. One-Compressor Maximum Instantaneous
STC
Current 5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan motor above.
20
SELECTION DATA
Electric Data (Voltage:380V) 46℃ Condenser Air Inlet Temperature Model
Unit Main Power Voltage
RCU40ATHYZ1 RCU50ATHYZ1 RCU60ATHYZ1 RCU75ATHYZ1 RCU100ATHYZ1 RCU120ATHYZ1 RCU150ATHYZ1 RCU160ATHYZ1 RCU180ATHYZ1 RCU200ATHYZ1 RCU240ATHYZ1 RCU270ATHYZ1 RCU300ATHYZ1 RCU330ATHYZ1 RCU350ATHYZ1 RCU360ATHYZ1 RCU380ATHYZ1 RCU400ATHYZ1 RCUG40ATHYZ1 RCUG50ATHYZ1 RCUG60ATHYZ1 RCUG75ATHYZ1 RCUG100ATHYZ1 RCUG120ATHYZ1 RCUG150ATHYZ1 RCUG160ATHYZ1 RCUG180ATHYZ1 RCUG200ATHYZ1 RCUG240ATHYZ1 RCUG270ATHYZ1 RCUG300ATHYZ1 RCUG330ATHYZ1 RCUG350ATHYZ1 RCUG360ATHYZ1 RCUG380ATHYZ1 RCUG400ATHYZ1
380
RNC:Running Current
Hz
50
Application Voltage (V) Max.
418
Min.
342
Compressor(Three Phases) STC(A) 114 148 178 178 148 178 178 148 178 178 178 178 178 178 178 178 178 178 114 148 178 178 148 178 178 148 178 178 178 178 178 178 178 178 178 178
Refrigeration RNC(A) 71 92 116 122 2×92 2×116 2×122 3×92 3×116 3×122 4×116 2×122+2×116 4×122 3×116+2×122 5×122 6×116 3×122+3×116 6×122
IPT (kW) 42.1 51.7 64.0 68.0 2×51.7 2×64 2×68 3×51.7 3×64 3×68 4×64 2×68+2×64 4×68 3×64+2×68 5×68 6×64 3×68+3×64 6×68
79 99 124 130
45.1 55.4 68.5 72.7 2×55.4 2×68.5 2×72.7 3×55.4 3×68.5 3×72.7 4×68.5 2×72.7+2×68.5 4×72.7 3×68.5+2×72.7 5×72.7 6×68.5 3×72.7+3×68.5 6×72.7
2×99 2×124 2×130 3×99 3×124 3×130 4×124 2×130+2×124 4×130 3×124+2×130 5×130 6×124 3×130+3×124 6×130
Motor for Condenser Fan RNC(A) 4×2.7 4×2.7 4×2.7 4×2.7 8×2.7 8×2.7 8×2.7 12×2.7 12×2.7 12×2.7 16×2.7 16×2.7 16×2.7 20×2.7 20×2.7 24×2.7 24×2.7 24×2.7 4×2.7 4×2.7 4×2.7 4×2.7 8×2.7 8×2.7 8×2.7 12×2.7 12×2.7 12×2.7 16×2.7 16×2.7 16×2.7 20×2.7 20×2.7 24×2.7 24×2.7 24×2.7
IPT (kW) 4×1.1 4×1.1 4×1.1 4×1.1 8×1.1 8×1.1 8×1.1 12×1.1 12×1.1 12×1.1 16×1.1 16×1.1 16×1.1 20×1.1 20×1.1 24×1.1 24×1.1 24×1.1 4×1.1 4×1.1 4×1.1 4×1.1 8×1.1 8×1.1 8×1.1 12×1.1 12×1.1 12×1.1 16×1.1 16×1.1 16×1.1 20×1.1 20×1.1 24×1.1 24×1.1 24×1.1
Maximum Unit Current(A) 88 115 145 153 230 290 305 345 435 458 580 595 610 740 763 870 893 915 98 124 155 163 248 310 325 371 465 488 620 635 650 790 813 930 953 975
IPT:Power Input
1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit General Data. 2. The starting current is indicated for each compressor. 3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the maximum current within the unit working range. Supplied Voltage: Rated Voltage×0.9 Condenser Air Inlet Temperature: 52 ℃ Chilled Water Outlet Temperature: 10℃ Capacity Control: 100% Therefore, the size of wiring and fuses must be determined according to applicable national and local codes. 4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below. One-Compressor Maximum Instantaneous
STC
Current 5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan motor above. 21
SELECTION DATA
Electric Data (Voltage:415V) 46℃ Condenser Air Inlet Temperature Unit Main Power
Model
Voltage
Max.
Min.
Compressor(Three Phases) STC(A)
Refrigeration
Motor for Condenser Fan
Maximum Unit Current(A)
RNC(A)
IPT (kW)
RNC(A)
IPT (kW)
RCU40ATHYZ1
125
65
42.1
4×2.7
4×1.1
81
RCU50ATHYZ1
161
84
51.7
4×2.7
4×1.1
105
RCU60ATHYZ1
195
106
64.0
4×2.7
4×1.1
133
RCU75ATHYZ1
195
112
68.0
4×2.7
4×1.1
140
RCU100ATHYZ1
161
2×84
2×51.7
8×2.7
8×1.1
210
RCU120ATHYZ1
195
2×106
2×64
8×2.7
8×1.1
265
RCU150ATHYZ1
195
2×112
2×68
8×2.7
8×1.1
280
RCU160ATHYZ1
161
3×84
3×51.7
12×2.7
12×1.1
315
RCU180ATHYZ1
195
3×106
3×64
12×2.7
12×1.1
398
RCU200ATHYZ1
195
3×112
3×68
12×2.7
12×1.1
420
RCU240ATHYZ1
195
4×106
4×64
16×2.7
16×1.1
530
RCU270ATHYZ1
195
2×112+2×106
2×68+2×64
16×2.7
16×1.1
545
RCU300ATHYZ1
195
4×112
4×68
16×2.7
16×1.1
560
RCU330ATHYZ1
195
3×106+2×112
3×64+2×68
20×2.7
20×1.1
678
RCU350ATHYZ1
195
5×112
5×68
20×2.7
20×1.1
700
RCU360ATHYZ1
195
6×106
6×64
24×2.7
24×1.1
795
RCU380ATHYZ1
195
3×112+3×106
3×68+3×64
24×2.7
24×1.1
818 840
RCU400ATHYZ1
Hz
Application Voltage(V)
195
6×112
6×68
24×2.7
24×1.1
125
72
45.1
4×2.7
4×1.1
90
RCUG50ATHYZ1
161
91
55.4
4×2.7
4×1.1
114
RCUG60ATHYZ1
195
114
68.5
4×2.7
4×1.1
143
RCUG75ATHYZ1
195
119
72.7
4×2.7
4×1.1
149
RCUG100ATHYZ1
161
2×91
2×55.4
8×2.7
8×1.1
228
RCUG120ATHYZ1
195
2×114
2×68.5
8×2.7
8×1.1
286
RCUG150ATHYZ1
195
2×119
2×72.7
8×2.7
8×1.1
298
RCUG160ATHYZ1
161
3×91
3×55.4
12×2.7
12×1.1
342
RCUG180ATHYZ1
195
3×114
3×68.5
12×2.7
12×1.1
429
RCUG200ATHYZ1
195
3×119
3×72.7
12×2.7
12×1.1
446
RCUG240ATHYZ1
195
4×114
4×68.5
16×2.7
16×1.1
572
RCUG270ATHYZ1
195
2×119+2×114
2×72.7+2×68.5
16×2.7
16×1.1
583
RCUG40ATHYZ1
415
50
456
374
RCUG300ATHYZ1
195
4×119
4×72.7
16×2.7
16×1.1
595
RCUG330ATHYZ1
195
3×114+2×119
3×68.5+2×72.7
20×2.7
20×1.1
726
RCUG350ATHYZ1
195
5×119
5×72.7
20×2.7
20×1.1
744
RCUG360ATHYZ1
195
6×114
6×68.5
24×2.7
24×1.1
858
RCUG380ATHYZ1
195
3×119+3×114
3×72.7+3×68.5
24×2.7
24×1.1
875
RCUG400ATHYZ1
195
6×119
6×72.7
24×2.7
24×1.1
893
RNC:Running Current
IPT:Power Input
1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit General Data. 2. The starting current is indicated for each compressor. 3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the maximum current within the unit working range. Supplied Voltage: Rated Voltage×0.9 Condenser Air Inlet Temperature: 52℃ Chilled Water Outlet Temperature: 10℃ Capacity Control: 100% Therefore, the size of wiring and fuses must be determined according to applicable national and local codes. 4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below. One-Compressor Maximum Instantaneous
STC
Current 5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan motor above. 22
SOUND DATA
Sound Data Unit Power Frequency :50Hz Model
RCU40ATHYZ1 RCUG40ATHYZ1 RCU50ATHYZ1 RCUG50ATHYZ1 RCU60ATHYZ1 RCUG60ATHYZ1 RCU75ATHYZ1 RCUG75ATHYZ1 RCU100ATHYZ1 RCUG100ATHYZ1 RCU120ATHYZ1 RCUG120ATHYZ1 RCU150ATHYZ1 RCUG150ATHYZ1 RCU160ATHYZ1 RCUG160ATHYZ1 RCU180ATHYZ1 RCUG180ATHYZ1 RCU200ATHYZ1 RCUG200ATHYZ1 RCU240ATHYZ1 RCUG240ATHYZ1 RCU270ATHYZ1 RCUG270ATHYZ1 RCU300ATHYZ1 RCUG300ATHYZ1 RCU330ATHYZ1 RCUG330ATHYZ1 RCU350ATHYZ1 RCUG350ATHYZ1 RCU360ATHYZ1 RCUG360ATHYZ1 RCU380ATHYZ1 RCUG380ATHYZ1 RCU400ATHYZ1 RCUG400ATHYZ1
Frequency Band(Hz) 45~90
90~180
180~355
355~710
710~1400
1400~2800
2800~5600
5600~11200
Overall
49.6
54.4
62.4
65.2
66.5
60.9
44.3
38.9
69.0
49.9
54.8
63.0
65.8
67.0
61.2
44.7
39.1
69.5
51.1
55.2
63.4
66.4
67.2
61.5
44.9
39.3
69.8
51.5
55.8
63.8
66.7
67.4
61.8
45.3
39.8
70.1
52.4
56.5
64.7
66.3
67.4
66.5
46.2
41.5
71.4
52.8
57.2
65.4
66.5
67.8
66.9
46.7
42.2
71.8
52.8
57.3
65.5
66.8
68.1
66.9
46.8
42.3
72.0
53.0
57.3
66.2
67.2
68.5
67.0
47.1
42.5
72.3
53.1
57.5
66.4
67.3
68.7
67.2
47.2
42.6
72.5
53.1
57.7
66.7
67.6
68.8
67.5
47.2
42.6
72.7
53.3
57.9
66.8
68.1
69.3
67.8
47.3
43.1
73.1
53.3
57.9
66.8
68.3
69.4
67.9
47.3
43.1
73.2
53.3
57.9
66.8
68.4
69.5
67.9
47.3
43.1
73.3
53.5
58.1
67.3
68.8
70.1
68.2
47.6
43.4
73.7
53.5
58.1
67.3
69.1
70.3
68.4
47.6
43.4
73.9
54.7
58.6
67.9
69.5
70.9
69.2
49.4
44.5
74.6
54.7
58.6
67.9
69.7
71.1
69.4
49.4
44.5
74.8
55.2
58.5
68.1
69.9
71.4
69.7
49.6
44.9
75.0
SPL-A: A Scale Sound Pressure Level (dB) Notes: 1. The measuring point is 1.0 meter from the center of the unit surface and 1.5 meter from the floor level. 2. The units are operating under the standard working condition for cooling operation. 3. The above data was measured on a flat ground, Therefore, reflected sounds should be taken into consideration when the unit is surrounded by walls, etc.
23
WOKING RANGE
Working Range Power Supply: Working Voltage :90%-100% Rating Voltage Unbalanced Voltage :Within ±3% Deviation from Each Voltage at Compressor Terminals Start Voltage:Higher than 85% of the Rated Voltage Maximum Water Flow Rate and Minimum Water Flow Rate Max.Flow Rate Min.Flow Rate (No.1) (No.1)
Model RCU40ATHYZ1, RCUG40ATHYZ1 RCU50ATHYZ1, RCUG50ATHYZ1 RCU60ATHYZ1, RCUG60ATHYZ1 RCU75ATHYZ1, RCUG75ATHYZ1 RCU100ATHYZ1, RCUG100ATHYZ1 RCU120ATHYZ1, RCUG120ATHYZ1 RCU150ATHYZ1, RCUG150ATHYZ1 RCU160ATHYZ1, RCUG160ATHYZ1 RCU180ATHYZ1, RCUG180ATHYZ1
41.0 50.5 63.3 67.5 76.4 98.3 135.0 151.6 152.2
12.8 15.7 19.7 21.0 28.6 35.2 42.0 47.2 53.4
Max.Flow Rate Min.Flow Rate (No.1/No.2) (No.1/No.2)
Model RCU200ATHYZ1, RCUG200ATHYZ1 RCU240ATHYZ1, RCUG240ATHYZ1 RCU270ATHYZ1, RCUG270ATHYZ1 RCU300ATHYZ1, RCUG300ATHYZ1 RCU330ATHYZ1, RCUG330ATHYZ1 RCU350ATHYZ1, RCUG350ATHYZ1 RCU360ATHYZ1, RCUG360ATHYZ1 RCU380ATHYZ1, RCUG380ATHYZ1 RCU400ATHYZ1, RCUG400ATHYZ1
159.4 98.3/98.3 135/98.3 135/135 152.2/135 159.4/135 152.2/152.2 159.4/152.2 159.4/159.4
57.1 35.2/35.2 42/35.2 42/42 53.4/42 57.1/42 53.4/53.4 57.1/53.4 57.1/57.1
Internal Water Volume in Water Cooler Model
Volume(No.1)
Model
Volume(No.1/No.2)
RCU40ATHYZ1, RCUG40ATHYZ1
0.08
RCU200ATHYZ1, RCUG200ATHYZ1
0.21
RCU50ATHYZ1, RCUG50ATHYZ1
0.07
RCU240ATHYZ1, RCUG240ATHYZ1
0.14/0.14
RCU60ATHYZ1, RCUG60ATHYZ1
0.07
RCU270ATHYZ1, RCUG270ATHYZ1
0.14/0.14
RCU75ATHYZ1, RCUG75ATHYZ1
0.07
RCU300ATHYZ1, RCUG300ATHYZ1
0.14/0.14
RCU100ATHYZ1, RCUG100ATHYZ1
0.14
RCU330ATHYZ1, RCUG330ATHYZ1
0.21/0.14
RCU120ATHYZ1, RCUG120ATHYZ1
0.14
RCU350ATHYZ1, RCUG350ATHYZ1
0.21/0.14
RCU150ATHYZ1, RCUG150ATHYZ1
0.14
RCU360ATHYZ1, RCUG360ATHYZ1
0.21/0.21
RCU160ATHYZ1, RCUG160ATHYZ1
0.21
RCU380ATHYZ1, RCUG380ATHYZ1
0.21/0.21
RCU180ATHYZ1, RCUG180ATHYZ1
0.21
RCU400ATHYZ1, RCUG400ATHYZ1
0.21/0.21
Minimum Internal System Water Volume Model Volume (m3) Model Volume (m3)
RCU40ATHYZ1
RCU50ATHYZ1
RCU60ATHYZ1
RCU75ATHYZ1
RCU100ATHYZ1
RCU120ATHYZ1
RCU150ATHYZ1
RCU160ATHYZ1
RCU180ATHYZ1
RCUG40ATHYZ1 RCUG50ATHYZ1 RCUG60ATHYZ1 RCUG75ATHYZ1 RCUG100ATHYZ1 RCUG120ATHYZ1 RCUG150ATHYZ1 RCUG160ATHYZ1 RCUG180ATHYZ1
0.42
0.51
0.64
RCU200ATHYZ1
RCU240ATHYZ1
RCU270ATHYZ1
0.68
1.02
1.28
RCU300ATHYZ1 RCU330ATHYZ1 RCU350ATHYZ1
1.37
1.54
1.92
RCU360ATHYZ1
RCU380ATHYZ1
RCU400ATHYZ1
RCUG200ATHYZ1 RCUG240ATHYZ1 RCUG270ATHYZ1 RCUG300ATHYZ1 RCUG330ATHYZ1 RCUG350ATHYZ1 RCUG360ATHYZ1 RCUG380ATHYZ1 RCUG400ATHYZ1
2.05
2.57
2.65
2.74
3.29
3.42
3.85
3.98
4.11
Note: Minimum internal system water volume in the above table is setting according to standard ON/OFF differential. In case of changing ON/OFF differential, minimum internal system water volume shall be increased as follows. The Switch ON/OFF of Temperature Difference
Minimum Water Volume in System
2℃(Standard)
100%
1.5℃
130%
1℃
200%
Temperature Range The temperature range is given in the following table. Item Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB)
Standard 5~10℃ 5~52℃
24
COMPONENT DATA
Component Detailed Data(R22 and R407C) Compressor Model
—
Compressor Type
—
Revolution Displacement Capacity Control Air Tight Pressure
Motor
Oil
40ASCC-Z
50ASCC-Z
60ASCC-Z
Semi-Hermetic
50Hz 50Hz Continuous Control Type
r/min m3/h
2,880 169.5
%
100~15, 0
Discharge
MPa
3.0
Suction Type Starting Method Poles Insulation Name Charge
MPa — — — — — Liters
2.0 Special Squirrel Cage, Three-Phase Motor Star-Delta Starting 2 F ICEMATIC UX300 6
137.4
208.7
Condenser and Condenser Fan RCU40ATHY RCU50ATHY RCU60ATHY RCU75ATHY RCU100ATHY RCU120ATHY RCU150ATHY RCU160ATHY RCU180ATHY Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1
R22
Model
RCUG40AT RCUG50AT RCUG60AT RCUG75AT RCUG100ATH RCUG120ATH RCUG150ATH RCUG160ATH RCUG180ATH HYZ1 HYZ1 HYZ1 HYZ1 YZ1 YZ1 YZ1 YZ1 YZ1
R407C Condenser Type Condenser Piping
Multi-Pass Cross Finned Tube
—
Material
—
Outer Diameter
mm
9.53
9.53
9.53
9.53
Copper Tube 9.53
9.53
9.53
9.53
9.53
Tube Thickness(mean)
mm
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Fin Material
—
Maximum Operation Pressure
MPa
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
Number of Condenser/unit(s)
—
4
4
4
4
8
8
8
12
12
8 710 960
12 710 960
12 710 960
0.9
0.9
0.9
Condeser Fan
Condenser Fan Motor
Type
—
Number/Unit Outer Diameter Revolution
— mm r/min
Type
—
Starting Method
—
Nominal Output
kW
Quantity Insulation Class Poles
— — —
R22
Model
R407C Condenser Type Condenser Piping
—
Aluminum
Direct-Drive Propeller Fan 4 710 960
4 710 960
4 710 960
4 710 960
8 710 960
8 710 960
Drip-Proof Enclosure Direct-On-Line Starting 0.9
0.9
0.9
0.9
0.9
0.9
4 4 4 4 8 8 8 12 12 E E E E E E E E E 6 6 6 6 6 6 6 6 6 RCU200ATH RCU240ATH RCU270ATH RCU300ATH RCU330ATHY RCU350ATHY RCU360ATHY RCU380ATHY RCU400ATHY YZ1 YZ1 YZ1 YZ1 Z1 Z1 Z1 Z1 Z1 RCUG200AT RCUG240AT RCUG270AT RCUG300AT RCUG330ATH RCUG350ATH RCUG360ATH RCUG380ATH RCUG400ATH HYZ1 HYZ1 HYZ1 HYZ1 YZ1 YZ1 YZ1 YZ1 YZ1 Multi-Pass Cross Finned Tube
Material
—
Outer Diameter
mm
9.53
9.53
9.53
9.53
9.53
Copper Tube 9.53
9.53
9.53
9.53
Tube Thickness(mean)
mm
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Fin Material
—
Maximum Operation Pressure
MPa
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
Number of Condenser/unit(s)
—
12
2×8
2×8
2×8
20
20
2×12
2×12
2×12
12 710 960
2×8 710 960
2×8 710 960
2×8 710 960
20 710 960
2×12 710 960
2×12 710 960
Condeser Fan
Condenser Fan Motor
Type
—
Number/Unit Outer Diameter Revolution
— mm r/min
Aluminum
Direct-Drive Propeller Fan 20 710 960
2×12 710 960
Type
—
Drip-Proof Enclosure
Starting Method
—
Direct-On-Line Starting
Nominal Output
kW
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
Quantity Insulation Class Poles
— — —
12 E 6
2×8 E 6
2×8 E 6
2×8 E 6
20 E 6
20 E 6
2×12 E 6
2×12 E 6
2×12 E 6
25
COMPONENT DATA
Water Cooler RCU(G)40 RCU(G)50 RCU(G)60 RCU(G)75A RCU(G)100 RCU(G)120 RCU(G)150 RCU(G)160 RCU(G)180 ATHYZ1 ATHYZ1 ATHYZ1 THYZ1 ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1
Model
Steel
Shell Material Water Side
Outer Diameter
356.2
356.2
356.2
356.2
356.2
356.2
356.2
431.8
431.8
Length
1,276
1,276
1,276
1,276
2,296
2,296
2,296
2,400
2,400
Steel
Shell Material
Shell Refrigerant Side
Outer Diameter
420
420
420
420
420
420
420
500
500
Length
101
101
101
101
101
101
101
101
101
Thickness
10
10
10
10
10
10
10
12
12 12.7 437 2
Material Tube
Maximum Pemissable Pressure
Copper
Outer Diameter Quantity Number of Pass
12.7 220 4
12.7 272 4
12.7 310 4
12.7 310 4
12.7 272 2
12.7 310 2
12.7 310 2
12.7 408 2
Refrigerant Side
R22
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
R407C
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.05
1.05
1.05
1.05
1.05
1.05
1.05
1.05
1.05
Water Side Insulation
Polyethylene(25mm)
Model
RCU(G)200 RCU(G)24 RCU(G)270 RCU(G)300 RCU(G)330 RCU(G)350 RCU(G)360 RCU(G)380 RCU(G)400 ATHYZ1 0ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1 ATHYZ1 Steel
Shell Material Water Side Shell
Tube
Maximum Pemissable Pressure
Outer Diameter
431.8
356.2
356.2
356.2
431.8+356.2 431.8+356.2
431.8
431.8
431.8
Length
2,400
2,296
2,296
2,296
2,400+2,296 2,400+2,296 Steel
2,400
2,400
2,400
500 101 12
420 101 10
420 101 10
420 101 10
500+420 101 12+10
500+420 101 12+10 Copper
500 101 12
500 101 12
500 101 12
12.7 437 2 1.3 1.6
12.7 310 2 1.3 1.6
12.7 310 2 1.3 1.6
12.7 310 2 1.3 1.6
12.7 437+310 2 1.3 1.6
12.7 437+310 2 1.3 1.6
12.7 437 2 1.3 1.6
12.7 437 2 1.3 1.6
12.7 437 2 1.3 1.6
1.05
1.05
1.05
1.05
1.05
1.05
1.05
1.05
1.05
Shell Material Refrigerant Outer Diameter Side Length Thickness Material Outer Diameter Quantity Number of Pass Refrigerant Side
R22 R407C
Water Side Insulation
Polyethylene(25mm)
Note: the data above is indicated for each water cooler, as these units greater than 240ATHYZ1 including 240ATHYZ1 consist of two water coolers for two modules, in the case the data for the two water coolers are different, it is showed as no.1water cooler data + no.2 water cooler data.
26
CONTROL SYSTEM
Refrigerant System In addition to the basic air-cooled water chiller components (compressor, condenser, thermal expansion valves and water cooler), the following components are equipped in each refrigerant cycle: Stop Valve for Compressor Discharge Line and Liquid Line: These stop valves are equipped at the liquid line, and facilitate easy compressor service without appreciable leakage of refrigerant.
Capacity Control All models are equipped with an unloading system for each compressor, in order to adjust the cooling capacity and provide precise temperature control for the chilled water, coupled with electric thermostat.
Electric Operation Control Electrical Operation Control advanced HITACHI Water Chillers are as follows.
Control Panel ON switch, OFF switch, Power Supply Lamp, Operation Lamp, Alarm Lamp, Operation/Alarm Indicator for each refrigerant cycle and check switch are mounted in the Control Panel. The Control Panel is located at a position where easy access is available. Operation/Alarm indicator can display individual alarm codes such as High-Cut, Low-Cut etc. This function is very useful for detecting what alarm has occurred. Check switches are for checking chilled water temperature and alarm occurrence data. Chilled water temperature setting switches, ON/OFF Differential Setting Switches, Remote-Local Switch and so on are located at the rear side of Control Panel, in order not to access during operation.
Operation Hour Meter This hour-meter indicates the sum of the compressor operation.
Screw Compressor Cycling Protection Circuit The electric timer of the screw compressor cycling protection (CCP ) connected in the compressor control circuit delays the screw compressor restarting period for approximately three (3) minutes for No.1 compressor, four (4) minutes for No.2 compressor, five (5) minutes for No.3 compressor and six (6) minutes for No.4 compressor after the electronic thermostat calls for the cooling operation or automatic resetting of the protection devices, thereby preventing harmful screw compressor cycling operation.
Electronic Thermostat Circuit The electronic thermostat senses chilled water temperatures at the water cooler outlet, and operates solenoid valves for HITACHI screw compressor capacity control.
Screw Compressor Reversing Protection Circuit This circuit is composed of a reverse-phase protection devices, preventing reverse operation of the screw compressor, because the screw compressor definitely cannot be operated in the wrong direction as the misconnection of the main power phases.
Rotation of Compressor Operation Rotation of compressor operation order is available in order to balance operation hours of compressors. This function extends machine life.
Restart after Short Period Power-Failure In the case that a power failure shorter than 2 seconds occurred, compressors can be restarted automatically within 3 minutes after power supply.
27
CONTROL SYSTEM
Refrigerant Charge
R22 RCU40A THYZ1
RCU50A THYZ1
RCU60AT HYZ1
RCU75AT HYZ1
RCU100AT HYZ1
RCU120ATH YZ1
RCU150ATH YZ1
RCU160ATH YZ1
RCU180ATH YZ1
Model
RCU200 ATHYZ1
RCU240 ATHYZ1
RCU270AT HYZ1
RCU300AT HYZ1
2× RCU330AT HYZ1
2× RCU350ATH YZ1
2× RCU360ATH YZ1
3× RCU380ATH YZ1
3× RCU400ATH YZ1
Charge
3×
2×+ 2×
4×
3×+2x
5×
6×
3×+3×
6×
Model Charge
4×
R407C RCUG40 ATHYZ1
RCUG50 ATHYZ1
RCUG60A THYZ1
RCUG75A THYZ1
RCUG100 ATHYZ1
RCUG120AT HYZ1
RCUG150AT HYZ1
RCUG160AT HYZ1
RCUG180AT HYZ1
Model
RCUG200 ATHYZ1
RCUG240 ATHYZ1
RCUG270 ATHYZ1
RCUG300 ATHYZ1
2× RCUG330 ATHYZ1
2× RCUG350AT HYZ1
2× RCUG360AT HYZ1
3× RCUG380AT HYZ1
RCUG400AT HYZ1
Charge
3×
4×
2×+ 2×
4×
3×+2×
3×+2×
6×
3×+3×
6×
Model Charge
Note: for the details of the blank places, please contact HITACHI or Hitachi’s distributors.
Protection and Safety Control The safety and protective devices are equipped in the unit to ensure dependable and long life operation. Their functions should be carefully noted, and field adjustment is not recommended, if the setting is maintained at the point listed in the table.
Compressor Protection 1、The high pressure switch and the low pressure control protect against excessive discharge pressure and exceedingly low suction pressure. The switch and control cut out compressor operation when the discharge pressure exceeds the setting or when the suction pressure decrease below the setting. 2、Overcurrent relays equipped in the magnetic switch box cut out each compressor operation when the current to the compressor exceeds the setting. 3、The internal thermostat embedded in the compressor motor winding cuts out each operations, when the temperature of the motor winding exceeds the setting. 4、An oil heater in the compressor prevents from oil foaming during cold starting. Energize this heater to warm the oil, while the compressor is stopped.
Fan Motor Protection The thermal overcurrent relays for the condenser fan motors cut out fan operation and compressor operation, when the current to the fan motor exceeds the setting.
Refrigerant Cycle 1、The fusible plug is equipped on the liquid line. When refrigerant temperature exceeds the melting point, and the plug melts and purges the refrigerant gas, in order to avoid explosion of the condenser. 2、The freeze protection control, for which the sensor is located in the water outlet near the water cooler, cuts out the compressor operation, when the water outlet temperature decreases below the setting.
28
CONTROL SYSTEM
Safety and Control Device Setting (R22) 35℃ Condenser Air Inlet Temperature RCU40ATH RCU50ATH RCU60ATHY RCU75ATH RCU100ATH RCU120ATH RCU150ATH RCU160ATH RCU180ATH YZ1 YZ1 Z1 YZ1 YZ1 YZ1 YZ1 YZ1 YZ1
Model High pressure control
For Compressor
Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Cut Off Low pressure control
MPa
2.98
2.98
Cut Off Internal Thermostat
MPa
0.05
0.05
Cut Off
℃
115
115
Cut In Overcurrent Relay*1
℃
93
93
2.98
2.98
0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
0.05
115
2.98
115
2.98 2.98 Control by Micro-Processor
115
115
2.98
115
115
115
93
93
76
57
72
70
52
66
150
150
150
93 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor)
380V
50Hz
A
44
57
72
415V
50Hz
A
40
52
66
W
150
150
150
150 70
Oil Heater Capacity Discharged Gas Thermostat
76
57
72
70 52 66 One Oil Heater for Each Compressor Motor 150 150 (One for Each Circuit)
Cut Off
℃
70
70
70
70
70
70
Cut In CCP Calculagraph
℃
100
100
100 100 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor)
100
100
Setting Time
s
180
180
180
180
180
180
180
180
180
Star-Delta Starting
s
5
5
5
5
5
5
5
5
5
s
30
30
30
30
30
30
30
30
30
A
6
6
6
6
6
6
6
6
6
℃
72
72
72
72
72
72
72
72
72
℃
2
2
2
2
2
2
2
2
2
℃
140
140
140
140
380V 50Hz
A
3.3
3.3
3.3
3.3
415V 50Hz
A
3.3
3.3
3.3
3.3
3.13
3.13
3.13
3.13
From Start to Load-up Control Circuit
2.98
Fuse Capacity(220V/240V) Fusible Plug
Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off
70
70
(One for Each Circuit)
Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan
140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
Discharged valve of pressure Starting to Open
MPa
High pressure control Cut Off Low pressure control
MPa
2.98
2.98
Cut Off Internal Thermostat
MPa
0.05
0.05
Cut Off
℃
115
115
Cut In Overcurrent Relay*1
℃
93
93
2.98
3.3
3.3
3.3
3.3
3.3
3.3
3.13
3.13
3.13
3.13
3.13
2.98
2.98
0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
0.05
115
2.98
115
2.98 2.98 Control by Micro-Processor
115
115
2.98
115
115
115
93
93
72
76/72
76
66
70/66
70
150
150
150
93 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor)
380V
50Hz
A
76
72
76/72
415V
50Hz
A
70
66
70/66
W
150
150
150
150 70
Oil Heater Capacity Discharged Gas Thermostat
76
72/76
76
70 66/70 70 One Oil Heater for Each Compressor Motor 150 150 (One for Each Circuit)
Cut Off
℃
70
70
70
70
70
70
Cut In CCP Calculagraph
℃
100
100
100 100 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor)
100
100
Setting Time
s
180
180
180
180
180
180
180
180
180
Star-Delta Starting
s
5
5
5
5
5
5
5
5
5
s
30
30
30
30
30
30
30
30
30
A
6
6
6
6
6
6
6
6
6
℃
72
72
72
72
72
72
72
72
72
℃
2
2
2
2
2
2
2
2
2
℃
140
140
140
140
380V 50Hz
A
3.3
3.3
3.3
3.3
415V 50Hz
A
3.3
3.3
3.3
3.3
MPa
3.13
3.13
3.13
3.13
From Start to Load-up Control Circuit
3.3
3.3 3.3 (One for Each Compressor)
RCU200AT RCU240AT RCU270ATH RCU300AT RCU330ATH RCU350ATH RCU360ATH RCU380ATH RCU400ATH HYZ1 HYZ1 YZ1 HYZ1 YZ1 YZ1 YZ1 YZ1 YZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Model
For Compressor
3.3
Fuse Capacity(220V/240V) Fusible Plug
Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off
70
70
(One for Each Circuit)
Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan
140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
Discharged valve of pressure Starting to Open
3.3
3.3
3.3
3.3
3.3
3.3 3.3 (One for Each Compressor)
3.3
3.3
3.3
3.13
3.13
3.13
3.13
3.13
Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used, for these chillers greater than 240ATHYZ1 including 240ATHYZ1 which consist of two modules, when the data for the compressors in the two modules are different, it is showed as data for one of the compressor in the no.1 module / data for one of the compressor in the no.2 module. 29
CONTROL SYSTEM
Safety and Control Device Setting (R407C) 35℃ Condenser Air Inlet Temperature Model High pressure control Cut Off Low pressure control Cut Off Internal Thermostat Cut Off Cut In Overcurrent Relay*1 For Compressor
380V
50Hz
415V
50Hz
Oil Heater Capacity Discharged Gas Thermostat Cut Off Cut In CCP Calculagraph Setting Time Star-Delta Starting From Start to Load-up
Control Circuit
Refrigerant Circuit
Fuse Capacity(220V/240V) Fusible Plug
RCUG40A RCUG50A RCUG60AT RCUG75A RCUG100AT RCUG120A RCUG150A RCUG160A RCUG180A THYZ1 THYZ1 HYZ1 THYZ1 HYZ1 THYZ1 THYZ1 THYZ1 THYZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor) MPa 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 Control by Micro-Processor MPa 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor) 115 115 115 115 115 115 115 115 115 ℃ 93 93 93 93 93 93 93 93 93 ℃ Manual Reset Adjustable (One Switch for Each Compressor Motor) A 49 62 78 82 62 78 82 62 78 A 45 57 71 75 57 71 75 57 71 One Oil Heater for Each Compressor Motor W 150 150 150 150 150 150 150 150 150 (One for Each Circuit) 60 60 60 60 60 60 60 60 60 ℃ 90 90 90 90 90 90 90 90 90 ℃ Non-Adjustable (One Timer for Each Compressor Motor) s 180 180 180 180 180 180 180 180 180 s 5 5 5 5 5 5 5 5 5 s 30 30 30 30 30 30 30 30 30 A
6
6
6
6
℃
72
72
72
72
℃
2
2
2
2
℃
140
140
380V 50Hz
A
415V 50Hz
A
3.3 3.3
3.3 3.3
Starting to Open
MPa
3.13
3.13
Melt Temperature Frost-Proof Protection Cut Off
6
6
6
6
(One for Each Circuit) 72 72
6
72
72
72
2
2
2
2
2
Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan
Discharged valve of pressure
Model High pressure control
For Compressor
Cut Off Low pressure control
MPa
Cut Off Internal Thermostat
MPa
Cut Off
℃
Cut In Overcurrent Relay*1
℃
380V
50Hz
A
415V
50Hz
A
Oil Heater Capacity
W
Discharged Gas Thermostat Cut Off
℃
Cut In CCP Calculagraph
℃
Setting Time Star-Delta Starting From Start to Load-up Control Circuit
Fuse
s s s
140 140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor) 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13 3.13 3.13 3.13 3.13 3.13
6
6
6
6
℃
72
72
72
72
℃
2
2
2
2
℃
140
140
380V 50Hz
A
415V 50Hz
A
3.3 3.3
3.3 3.3
Starting to Open
MPa
3.13
3.13
Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off
3.3 3.3 3.13
RCUG200 RCUG240 RCUG270A RCUG300 RCUG330AT RCUG350A RCUG360A RCUG380A RCUG400A ATHYZ1 ATHYZ1 THYZ1 ATHYZ1 HYZ1 THYZ1 THYZ1 THYZ1 THYZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor) 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 Control by Micro-Processor 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor) 115 115 115 115 115 115 115 115 115 93 93 93 93 93 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor) 82 78 82/78 82 78/82 82 78 82/78 82 75 71 75/71 75 71/75 75 71 75/71 75 One Oil Heater for Each Compressor Motor 150 150 150 150 150 150 150 150 150 (One for Each Circuit) 60 60 60 60 60 60 60 60 60 90 90 90 90 90 90 90 90 90 Non-Adjustable (One Timer for Each Compressor Motor) 180 180 180 180 180 180 180 180 180 5 5 5 5 5 5 5 5 5 30 30 30 30 30 30 30 30 30
A
Capacity(220V/240V) Fusible Plug
140
6
6
6
6
(One for Each Circuit) 72 72
72
72
72
2
2
2
6
2
2
Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan
Discharged valve of pressure
140 140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor) 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13 3.13 3.13 3.13 3.13 3.13
140 3.3 3.3 3.13
Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used, for these chillers greater than 240ATHYZ1 including 240ATHYZ1 which consist of two modules, when the data for the compressors in the two modules are different, it is showed as data for one of the compressor in the no.1 module / data for one of the compressor in the no.2 module. 30
CONTROL SYSTEM
Safety and Control Device Setting (R22) 46℃ Condenser Air Inlet Temperature RCU40ATH RCU50ATH RCU60ATHY RCU75ATH RCU100ATH RCU120ATH RCU150ATH RCU160ATH RCU180ATH YZ1 YZ1 Z1 YZ1 YZ1 YZ1 YZ1 YZ1 YZ1
Model High pressure control
For Compressor
Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Cut Off Low pressure control
MPa
2.98
2.98
Cut Off Internal Thermostat
MPa
0.05
0.05
Cut Off
℃
115
115
Cut In Overcurrent Relay*1
℃
93
93
2.98
2.98
0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
0.05
115
2.98
115
50Hz
A
51
66
84
415V
50Hz
A
47
61
77
W
150
150
150
150 70
Oil Heater
115
115
115
115
93
93
88
66
84
81 61 77 One Oil Heater for Each Compressor Motor
88
66
84
81
61
77
150 150 (One for Each Circuit)
150
150
150
℃
70
70
70
70
70
70
Cut In CCP Calculagraph
℃
100
100
100 100 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor)
100
100
Setting Time
s
180
180
180
180
180
180
180
180
180
Star-Delta Starting
s
5
5
5
5
5
5
5
5
5
s
30
30
30
30
30
30
30
30
30
A
6
6
6
6
6
6
6
6
6
Fuse Capacity(220V/240V) Fusible Plug
Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off Control of Exhaust Temperature
70
70
(One for Each Circuit) ℃
72
72
72
72
72
72
72
72
72
℃
2
2
2
2
2
2
2
2
2
℃
140
140
140
140
380V 50Hz
A
3.3
3.3
3.3
3.3
415V 50Hz
A
3.3
3.3
3.3
3.3
3.13
3.13
3.13
3.13
Cut Off Overcurrent relay for motor of fan
140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
Discharged valve of pressure Starting to Open
MPa
3.3
3.3
3.3
3.3
3.3
3.3 3.3 (One for Each Compressor)
3.3
3.3
3.3
3.13
3.13
3.13
3.13
3.13
RCU200AT RCU240AT RCU270ATH RCU300AT RCU330ATH RCU350ATH RCU360ATH RCU380ATH RCU400ATH HYZ1 HYZ1 YZ1 HYZ1 YZ1 YZ1 YZ1 YZ1 YZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Model High pressure control Cut Off Low pressure control
MPa
2.98
2.98
Cut Off Internal Thermostat
MPa
0.05
0.05
Cut Off
℃
115
115
Cut In Overcurrent Relay*1
℃
93
93
2.98
2.98
2.98
0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
0.05
115
2.98
115
2.98 2.98 Control by Micro-Processor
115
115
2.98
115
115
115
93
93
84
88/84
88
77
81/77
81
150
150
150
93 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor)
380V
50Hz
A
88
84
88/84
415V
50Hz
A
81
77
81/77
W
150
150
150
150 70
Oil Heater Capacity Discharged Gas Thermostat
88
84/88
88
81 77/81 81 One Oil Heater for Each Compressor Motor 150 150 (One for Each Circuit)
Cut Off
℃
70
70
70
70
70
70
Cut In CCP Calculagraph
℃
100
100
100 100 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor)
100
100
Setting Time
s
180
180
180
180
180
180
180
180
180
Star-Delta Starting
s
5
5
5
5
5
5
5
5
5
s
30
30
30
30
30
30
30
30
30
A
6
6
6
6
6
6
6
6
6
From Start to Load-up Control Circuit
115
2.98
Cut Off
From Start to Load-up
For Compressor
2.98 2.98 Control by Micro-Processor
93 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor)
380V
Capacity Discharged Gas Thermostat
Control Circuit
2.98
Fuse Capacity(220V/240V) Fusible Plug
70
70
(One for Each Circuit)
Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off Control of Exhaust Temperature
℃
72
72
72
72
72
72
72
72
72
℃
2
2
2
2
2
2
2
2
2
Cut Off
℃
140
140
140
140
380V 50Hz
A
3.3
3.3
3.3
3.3
415V 50Hz
A
3.3
3.3
3.3
3.3
MPa
3.13
3.13
3.13
3.13
Overcurrent relay for motor of fan
140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
Discharged valve of pressure Starting to Open
3.3
3.3
3.3
3.3
3.3
3.3 3.3 (One for Each Compressor)
3.3
3.3
3.3
3.13
3.13
3.13
3.13
3.13
Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used, for these chillers greater than 240ATHYZ1 including 240ATHYZ1 which consist of two modules, when the data for the compressors in the two modules are different, it is showed as data for one of the compressor in the no.1 module / data for one of the compressor in the no.2 module. 31
Safety and Control Device Setting (R407C)
CONTROL SYSTEM
46℃ Condenser Air Inlet Temperature Model High pressure control Cut Off Low pressure control Cut Off Internal Thermostat Cut Off Cut In Overcurrent Relay*1 For Compressor
380V
50Hz
415V
50Hz
Oil Heater Capacity Discharged Gas Thermostat Cut Off Cut In CCP Calculagraph Setting Time Star-Delta Starting From Start to Load-up
Control Circuit
Refrigerant Circuit
Fuse Capacity(220V/240V) Fusible Plug
RCUG40A RCUG50A RCUG60AT RCUG75A RCUG100AT RCUG120A RCUG150A RCUG160A RCUG180A THYZ1 THYZ1 HYZ1 THYZ1 HYZ1 THYZ1 THYZ1 THYZ1 THYZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor) MPa 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 Control by Micro-Processor MPa 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor) 115 115 115 115 115 115 115 115 115 ℃ 93 93 93 93 93 93 93 93 93 ℃ Manual Reset Adjustable (One Switch for Each Compressor Motor) A 57 71 89 94 71 89 94 71 89 A 52 66 83 86 66 83 86 66 83 One Oil Heater for Each Compressor Motor W 150 150 150 150 150 150 150 150 150 (One for Each Circuit) 60 60 60 60 60 60 60 60 60 ℃ 90 90 90 90 90 90 90 90 90 ℃ Non-Adjustable (One Timer for Each Compressor Motor) s 180 180 180 180 180 180 180 180 180 s 5 5 5 5 5 5 5 5 5 s 30 30 30 30 30 30 30 30 30 A
6
6
6
6
℃
72
72
72
72
℃
2
2
2
2
℃
140
140
380V 50Hz
A
415V 50Hz
A
3.3 3.3
3.3 3.3
Starting to Open
MPa
3.13
3.13
Melt Temperature Frost-Proof Protection Cut Off
6
6
6
6
(One for Each Circuit) 72 72
6
72
72
72
2
2
2
2
2
Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan
Discharged valve of pressure
Model High pressure control
For Compressor
Cut Off Low pressure control
MPa
Cut Off Internal Thermostat
MPa
Cut Off
℃
Cut In Overcurrent Relay*1
℃
380V
50Hz
A
415V
50Hz
A
Oil Heater Capacity
W
Discharged Gas Thermostat Cut Off
℃
Cut In CCP Calculagraph
℃
Setting Time Star-Delta Starting From Start to Load-up Control Circuit
Fuse Capacity(220V/240V) Fusible Plug
s s s A
140 140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor) 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13 3.13 3.13 3.13 3.13 3.13
3.3 3.3 3.13
RCUG200 RCUG240 RCUG270A RCUG300 RCUG330AT RCUG350A RCUG360A RCUG380A RCUG400A ATHYZ1 ATHYZ1 THYZ1 ATHYZ1 HYZ1 THYZ1 THYZ1 THYZ1 THYZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor) 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 Control by Micro-Processor 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor) 115 115 115 115 115 115 115 115 115 93 93 93 93 93 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor) 94 89 94/89 94 89/94 94 89 94/89 94 86 83 86/83 86 83/86 86 83 86/83 86 One Oil Heater for Each Compressor Motor 150 150 150 150 150 150 150 150 150 (One for Each Circuit) 60 60 60 60 60 60 60 60 60 90 90 90 90 90 90 90 90 90 Non-Adjustable (One Timer for Each Compressor Motor) 180 180 180 180 180 180 180 180 180 5 5 5 5 5 5 5 5 5 30 30 30 30 30 30 30 30 30 6
6
6
6
℃
72
72
72
72
℃
2
2
2
2
℃
140
140
380V 50Hz
A
415V 50Hz
A
3.3 3.3
3.3 3.3
Starting to Open
MPa
3.13
3.13
Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off
140
6
6
6
6
(One for Each Circuit) 72 72
6
72
72
72
2
2
2
2
2
Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan
Discharged valve of pressure
140 140 140 140 140 140 Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor) 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13 3.13 3.13 3.13 3.13 3.13
140 3.3 3.3 3.13
Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used, for these chillers greater than 240ATHYZ1 including 240ATHYZ1 which consist of two modules, when the data for the compressors in the two modules are different, it is showed as data for one of the compressor in the no.1 module / data for one of the compressor in the no.2 module.
32
INSTALLATION DATA
Recommended Concrete Curbs RCU(G)40、50、60、75ATHYZ1
Drain Ditch
6-Vibration Proof Rubber Mat
[Tubing Side]
Foundation Bolt
(4-M20×300)
☆Foundation Bolt 3
☆Nut ☆Washer ☆Bushing ☆Vibration Proof Rubber Mat
Steel Plate(1mm)
[Compressor Side] ☆:Supplied by Factory Steel Plate(1mm): Field Supply
Concrete
Mortar Cement
Drain Ditch
RCU(G)100ATHYZ1、RCU(G)120ATHYZ1 and RCU(G)150ATHYZ1
Drain Ditch
10-Vibration Proof Rubber Mat
Foundation Bolt (6-M20×300)
☆Foundation Bolt ☆Nut ☆Washer ☆Bushing ☆Vibration Proof Rubber Mat
Steel Plate(1mm)
☆:Supplied by Factory Steel Plate(1mm) : Field Supply
Drain Ditch
Concrete
33
Mortar Cement
INSTALLATION DATA
Recommended Concrete Curbs RCU(G)160ATHYZ1、RCU(G)180ATHYZ1 and RCU(G)200ATHYZ1
Drain Ditch
14-Vibration Proof Rubber Mat
[Tubing Side]
Foundation Bolt
☆Foundation Bolt ☆Nut ☆Washer ☆Bushing ☆Vibration Proof Rubber Mat Steel Plate(1mm)
☆:Supplied by Factory
Steel Plate(1mm) : Field Supply
Compressor Side
Concrete
Drain Ditch
Mortar Cement
RCU(G)240ATHYZ1、RCU(G)270ATHYZ1 and RCU(G)300ATHYZ1
Drain Ditch
10-Vibration Proof Rubber Mat
10-Vibration Proof Rubber Mat
[Tubing Side]
[Tubing Side]
Foundation Bolt (6-M20×300)
Foundation Bolt (6-M20×300)
[Compressor Side]
[Compressor Side]
Concrete
Drain Ditch
☆Foundation Bolt ☆Nut ☆Washer ☆Bushing ☆Vibration Proof Rubber Mat
Steel Plate(1mm)
☆:Supplied by Factory Steel Plate(1mm) : Field Supply
34
Mortar Cement
INSTALLATION DATA
Recommended Concrete Curbs
RCU(G)330ATHYZ1 and RCU(G)350ATHYZ1
Drain Ditch
14-Vibration Proof Rubber Mat
10-Vibration Proof Rubber Mat
[Tubing Side]
Foundation Bolt
[Tubing Side]
Foundation Bolt (6-M20×300)
[Compressor Side]
[Compressor Side]
Concrete
Drain Ditch
Mortar Cement
☆Foundation Bolt ☆Nut ☆Washer ☆Bushing ☆Vibration Proof Rubber Mat Steel Plate(1mm)
☆:Supplied by Factory
Steel Plate(1mm): Field Supply
RCU(G)360ATHYZ1、RCU(G)380ATHYZ1 and RCU(G)400ATHYZ1
Drain Ditch
14-Vibration Proof Rubber Mat
14-Vibration Proof Rubber Mat
[Tubing Side]
Foundation Bolt
[Tubing Side]
Foundation Bolt
Compressor Side
Compressor Side
Concrete
Drain Ditch
☆Foundation Bolt ☆Nut ☆Washer ☆Bushing ☆Vibration Proof Rubber Mat
Steel Plate(1mm)
☆:Supplied by Factory Steel Plate(1mm) : Field Supply
35
Mortar Cement
CONTROL SYSTEM
36
CONTROL SYSTEM
37
CONTROL SYSTEM
38
CONTROL SYSTEM
39
CONTROL SYSTEM
40
CONTROL SYSTEM
DIP SWITCH SETTING MODELS: :RCU(G)40ATHYZ1~RCU(G)400ATHYZ1
41
Standard Specifications Unit − The unit shall be an air-cooled screw type water chiller with R22 or R407C refrigerant, and shall be factory-completed with screw-type compressors, refrigeration cycle(s), air-cooled condensers, shell-and-tube water coolers, condenser fan motors, a star-delta starter, protective and safety devices, thermal expansion valves and compressor discharge stop valves, and shall be factory-assembled, piped, internal wired and charged with R22 or R407C refrigerant. The unit shall be completely weather-proofed for outdoor installation. The unit shall comply with Chinese Industrial Standards and other Chinese Industrial Standardization statutes, including safety codes.
SPECIFICATIONS
Compressor − The compressor shall be a semi-hermetic compressor from the same manufacturer. The compressor shall be serviceable type. The compressor protection system shall include an overcurrent relay, a pressure switch, a timer relays and an internal thermostat embedded in the motor winding. Water-Cooler-the water cooler shall be the dry expansion type with a horizontal welded steel construction shell, containing inside tubes. The refrigerant side of the water cooler shall be cleaned, dehydrated and tested for leakage at the maximum permissible working pressure of _ MPa.The water side of the water cooler shall be cleaned and performed water pressure test at_ MPa.
Capacity − The cooling capacity of the unit shall kW or greater under the following be conditions: m3/h chilled water flow rate, ℃chilled water inlet temperature, ℃chilled water outlet temperature, m2.℃/W fouling factor for the water-side heat exchanger or greater. The water-side heat exchanger pressure decrease kPa. shall not exceed The compressor power input shall not exceed kW under the prescribed conditions.
Air-Side Heat Exchanger Fan and Fan Motor − The fan shall be the propeller type directly driven by a kW motor. The motor shall be thermally protected from overloaded conditions with a thermal overcurrent relay and shall be permanently lubricated, The winding and bearing of the condenser fan motor shall be weather-proof construction. Condenser-The condenser shall be the multi-pass, cross-finned tube type, equipped with aluminum slit fins, mechanically bonded to seamless, oxygen-free copper tubes. The condenser shall be cleaned, dehydrated and tested for leakage at the maximum MPa. permissible working pressure of
V, Power Supply − The unit shall operate on ___Hz, three-phase current, and shall be capable to V and minimum operate within maximum V. Dimensions and Weight − The height of the unit mm, the width shall be mm, and shall be mm. The weight of the the depth shall be kg. unit shall not exceed
Accessories-Standard accessories shall include vibration-proof mats, foundation bolts
Cabinet − The cabinet shall be constructed of galvanized steel, baked with synthetic resin paint. The service panels shall be easily removable for service access to the electrical components such as magnetic switches and electrical devices.
42
Hitachi Appliances , Inc.
Distributed By:
Air Conditioning Division URL: http://www.hitachiacs.co.jp Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to their customers.
Printed in china
43
No:Z0011631-VIII-A