Engineering Product Data
Ceiling Cassette (50Hz/R22)
5CST2-06A Replace 5CST2-05A
Ceiling Cassette Introduction
Part 1 General information 1. Model line up ....................................................................................10 1.1 Indoor units............................................................................................................10 2.2 Outdoor units.........................................................................................................11
2. Nomenclature ...................................................................................12 3. Appearance.......................................................................................13 4. List of functions ...............................................................................14 5. Features ............................................................................................15 6. Control system(accessory) .............................................................17 6.1 Individual control system .......................................................................................17 6.2 Central control system...........................................................................................17 6.3 Control device........................................................................................................18
2
Ceiling Cassette
Part 2 Product data 1. Indoor units.......................................................................................20 1.1 Ceiling cassette 4-way............................................................................................20
2. Outdoor units....................................................................................44 2.1 Single piping type ...................................................................................................44
Ceiling Cassette
3
Part 3 Design and installation 1. General installation guidelines .......................................................80 1.1 Installation process & guidelines ...................................................................80 1.2 Checking the drawing.....................................................................................81 1.3 Application guidelines ....................................................................................82
2. Guideline for each installation process .........................................85 2.1 Sleeve and inserting work ..............................................................................85 2.2 Refrigerant piping work ..................................................................................88 2.3 Drain piping work ..........................................................................................97 2.4 Insulation work .............................................................................................103 2.5 Electrical work..............................................................................................107 2.6 Air tight test ..................................................................................................109 2.7 Vacuum drying .............................................................................................112 2.8 Trial test run operation .................................................................................117
3. Installation of indoor unit .............................................................119 3.1 Safety precautions .......................................................................................119 3.2 Ceiling cassette 4-way .................................................................................124
4. Installation of outdoor Unit ..........................................................132 4.1 Safety precautions .......................................................................................132 4.2 Introduction ..................................................................................................138 4.3 Foundation ...................................................................................................139 4.4 Settlement of the outdoor unit ......................................................................140 4.5 Selection of the best location .......................................................................141 4.6 Clearance space ..........................................................................................142 4.7 Outdoor unit piping.......................................................................................145 4.8 Outdoor unit installation requirements .........................................................146 4.9 Outdoor unit cabin........................................................................................149
4
Ceiling Cassette
Part 4 Special Guide 1. Installation guide at the seaside ...................................................152
Ceiling Cassette
5
Introduction
5CST2-06A
Introduction Preface New era brings more sophisticated and advanced buildings which in turn demands for specialized and optimized direct expansion air conditioning systems. Also energy efficiency, environment friendliness, low noise and low maintenance are the features which are essential for these systems. As a part of vertical integration LG makes all the key components in house, which gives us an edge to make better and latest technology products with best quality in optimized time. Ceiling cassette installed in the ceiling is popularly used for various places. It has nice outlook and is equipped with many special features. This engineering product data book incorporates information about the product itself, and installation, designing for ceiling cassette. The comprehensive study of this book will improve your knowledge about the system and its application in detail.
LG Electronics Inc. Air Conditioning Division
General information
Ceiling Cassette
6
5CST2-06A
Introduction
Publication history Pub. No. Frequency Category
Type
Product name
Refrigerant
5CST2-03B
Models
Notes
Published in
All models
New models edition
Jun.2005
5CST2-04A
New edition of EPDB LT-H548DLE1 - Engineering data addition - Design and installation guideline addition
5CST2-04B
LT-H246HLE1
Addition of new models
Dec.2006
5CST2-04D
LT-C246HLE1 LT-C548DLE1 LT-C548DLE2 LT-H548DLE2
Addition of new models
Jan.2007
5CST2-05A
LT-C286HLE1 LT-C368DLE1 LT-H286HLE1 LT-H368DLE1
Addition of new models
Apr.2007
5CST2-06A
LT-H186ELE1 LT-H186ELF1 LT-C186ELE1 LT-C186ELF1
Addition of new models
May.2007
50Hz
General information
CAC
Single
Ceiling cassette
R22
Ceiling Cassette
Agu.2006
7
Introduction
5CST2-06A
Step by step air conditioner selection process (reference) (1)
Calculate or obtain the maximum heat load for the area(s) to be air conditioned
Indoor unit specifications .......................................................................................p. 28
(2)
Outdoor unit specifications ....................................................................................p. 46 Capacity coefficient factor ......................................................................................p. 73 Air flow and temperature distribution....................................................................p. 41
Selection of the control system Control wiring method
(3)
Description of devices â?ˆ Make referene to the Multi PDB (P/No. 3828A20576B)
Electrical wiring Electrical characteristics .....................................................................................p. 44
(4)
Field wiring................................................................................................p. 131, 148
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
8
Ceiling Cassette
General information
Part 1 General information 1. Model line up .........................................................................................10 1.1 Indoor units .................................................................................................................10 2.2 Outdoor units...............................................................................................................11
2. Nomenclature ........................................................................................12 3. Appearance ...........................................................................................13 4. List of functions ....................................................................................14 5. Features .................................................................................................15 6. Control system(accessory)..................................................................17 6.1 Individual control system.............................................................................................17 6.2 Central control system ................................................................................................17 6.3 Control device .............................................................................................................18
General information
Ceiling Cassette
9
Model line up
5CST2-06A
1. Model line up 1.1 Indoor units Category
Type
Ceiling cassette
4-way
Category
Type
Ceiling cassette
Model names Capacity, kW(kBtu/h)
Chassis
TD
15.82(54.0)
14.0(47.8)
10.5(35.8)
LT-C548DLE1 LT-C548DLE2 LT-H548DLE1 LT-H548DLE2
LT-C488DLE1 LT-H488DLE1
LT-C368DLE1 LT-H368DLE1
Model names Capacity, kW(kBtu/h)
Chassis
4-way
TH
8.2(28.0)
7.0(23.8)
5.27(18.0)
LT-C286HLE1 LT-H286HLE1
LT-C246HLE1 LT-H246HLE1
LT-H186ELE1 LT-H186ELF1 LT-C186ELE1 LT-C186ELF1
1.2 Outdoor units LT-H548DLE1
LT-H548DLE2
LT-H488DLE1
LT-H246HLE1
1
1
1
1
kW
15.82/17.29
15.82/17.29
14/15.2
7.0/7.0
kBtu/h
54/59
54/59
47.7/51.8
23.8/23.8
Heat Pump No. of connectable indoor units Total capacity index of connectable indoor units(Cooling/Heating) Power supply
3Ø, 380-415V, 50Hz 3Ø, 380-415V, 50Hz 3Ø, 380-415V, 50Hz 1Ø, 220-240V, 50Hz
Chassis
LT-C548DLE1
LT-C548DLE2
LT-C488DLE1
LT-C246HLE1
1
1
1
1
kW
15.82/-
15.82/-
14/-
7.0/-
kBtu/h
54/-
54/-
47.7/-
23.8/-
Cooling Only No. of connectable indoor units Total capacity index of connectable indoor units(Cooling) Power supply
3Ø, 380-415V, 50Hz 3Ø, 380-415V, 50Hz 3Ø, 380-415V, 50Hz 1Ø, 220-240V, 50Hz
Chassis
10
Ceiling Cassette
General information
5CST2-06A
Model line up
LT-H186ELF1 LT-H186ELE1
LT-H286HLE1
LT-H368DLE1
1
1
1
kW
5.27/5.53
8.2/8.8
10.5/11.2
kBtu/h
18.0/18.9
28.0/30.0
35.8/38.2
1Ø, 220-240V, 50Hz
1Ø, 220-240V, 50Hz
3Ø, 380-415V, 50Hz
LT-C186ELF1 LT-C186ELE1
LT-C286HLE1
LT-C368DLE1
1
1
1
kW
5.27/-
8.2/-
10.5/-
kBtu/h
18.0/-
28.0/-
35.8/-
1Ø, 220-240V, 50Hz
1Ø, 220-240V, 50Hz
3Ø, 380-415V, 50Hz
Heat Pump No. of connectable indoor units Total capacity index of connectable indoor units(Cooling/Heating) Power supply
Chassis
Cooling Only No. of connectable indoor units Total capacity index of connectable indoor units(Cooling) Power supply
Chassis
General information
Ceiling Cassette
11
Nomenclature
5CST2-06A
2. Nomenclature L T
- H 5 4 8 D L E 1 Development Sequence Function A : Basic E : Elevation Grille
C : Plasma Air Purifying F : Elevation Grille + Plasma Air Purifying
Decoration Panel Information L : Basic Panel
Chassis Type C : C Chassis E : E Chassis F : F Chassis D : D Chassis H : H Chassis
Electric Standard (Volts / Freq. / Phase) 6 : 220-240V, 50Hz, 1Ø
8 : 380-415V, 50Hz, 3Ø
Nominal Cooling Capacity Ex) 54 ➔ 54,000 Btu/h
Model Type C : Cooling Only
H : Heat Pump
Type of Air Conditioner LT : LG Ceiling Cassette Type Air Conditioner, R22 Ref.
P T
- H D A 1 Development Sequence Function A : Basic E : Elevation Grille
C : Plasma Air Purifying. F : Elevation Grille + Plasma Air Purifying
Indoor Unit Chassis D: D Chassis
E: E Chassis
F: F Chassis
Model Type C : Cooling Only
H : Heat Pump
Decoration Panel of Ceiling Cassette Type Indoor Unit
12
Ceiling Cassette
General information
5CST2-06A
Appearance
3. Appearance Model
Outdoor unit
Indoor unit
LT-H548DLE1 LT-H548DLE2 LT-C548DLE1 LT-C548DLE2 LT-H488DLE1 LT-C488DLE1
LT-H368DLE1 LT-C368DLE1
LT-H286HLE1 LT-C286HLE1
LT-H246HLE1 LT-C246HLE1
LT-H186ELE1 LT-H186ELF1 LT-C186ELE1 LT-C186ELF1
General information
Ceiling Cassette
13
List of functions
5CST2-06A
4. List of functions Category
Ceiling Cassette 4-way
Function
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Air flow Airflow steps(fan / cool / heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Air purifying Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Installation Electric heater(operation) High ceiling operation Hot start Reliability Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Convenience Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Individual Simple wired remote controller control Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control General central control(Non LGAP) Dry contact CAC network Simple central control(LGAP) function PDI(power distribution indicator) PI 485 CTIE Special function kit Zone control Others Thermistor
4 X Auto X O 4/5/4 X O O O X Option O O O O(Heat Pump Only) O O O(Heat Pump Only) X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
*Some of functions are slightly different depending upon models, refer individual function table on "indoor units of PART 2". O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. 14
Ceiling Cassette
General information
5CST2-06A
Features
5. Features Ceiling Cassette 4-way ■ Compact design and easy installation ■ Low noise ■ Hygienic and easy-to-clean filter ■ 2-thermistor(unit body and remote controller) ■ Jet cool ■ Plasma air purifying system(option) ■ High head drain pump(700mm) ■ High-ceiling corresponding operation ■ LCD wired remote controller ■ Wireless remote controller(accessory)
840mm
Compact design and easy installation (For TH Chassis)
840mm
Only about 225mm height of the ceiling is sufficient for installation space. A smaller size than a textile(840 x 840) is very convenient for installation.
225mm
Low noise The most advanced low-noise design. The adoption of turbo-fan and round type heat exchanger provides the quietest operation.
Hygienic and easy to clean filter Washable filter is adopted. It is easy to open grille and clean filter.
General information
Ceiling Cassette
15
Features
5CST2-06A
Plasma air purifying system The plasma air purifying function not only removes microscopic contaminants and dust, but also removes house mites, pollen, pet fur etc. which helps to prevent allergic diseases like asthma. Dust electrode discharge Dust particles
Ionizer
Photo-catalyst coated mesh
+4.8KV discharge
Polluted air
+ +
+
Purified fresh air
+
Generating plasma
Odour Odour molecule
High head drain pump(700mm)
300mm or less
A standard drain-head height of up to 700 mm is possible, providing an ideal solution for perfect water drainage.
Max. 700mm
Built-in drain pump drains out water automatically. PVC elbow
PVC
PVC Flexible hose Common drain pipe
Drain pump
installation on the higher ceiling
High-ceiling corresponding operation
Installation on the normal-height ceiling
According to the height of the installation, it provides variability of indoor fan motor rpm. If the height of installation is low then you can adjust low rpm of indoor fan motor. On the other hand if the height of the installation is high you can adjust high rpm of indoor fan motor. Selection of speed can be done by slide switch at the back of the LCD wired remote controller.
16
Ceiling Cassette
General information
5CST2-06A
Control system(accessory)
6. Control system(accessory) 6.1 Individual control system Not available
6.2 Central control system Item
Central controller
Model name
Simple central controller
PQCSA101S0
Simple central controller (function controller available)
PQCSB101S0
Function controller
PQCSC101S0
Image
Applicable model
Ceiling cassette
Deluxe central controller (without schedule function)
PQCSW501A0
Deluxe central controller (with schedule function)
PQCSW502A0
PC based central controller (without schedule function)
PQCSS501A0
PC based central controller (with schedule function)
PQCSS502A0
â?ˆ Please refer to Multi F/FDX PDB (P/No.3828A20576B) for detail information.
General information
Ceiling Cassette
17
Combination
5CST2-06A
6.3 Control device Item
BNU_LW
Model name
LonWorks for BMS
Image
Application model
PQNFB16A0
PDI (Power distributor indicator)
PQNUD1S00
PI485
PMNFP14A0 Ceiling cassette
Product interface units
PQNFG00A0
CNU
PQDSA Dry_contact PQDSB
â?ˆ Please refer to Multi F/FDX PDB (P/No.3828A20576B) for detail information.
18
Ceiling Cassette
General information
Part 2 Product data 1. Indoor units............................................................................................20 1.1 Ceiling cassette 4-way.................................................................................................20
2. Outdoor units.........................................................................................44 2.1 Single piping type ........................................................................................................44
Product data
Ceiling Cassette
19
Features
5CST2-06A
1. Indoor unit 1.1 Ceiling cassette 4-way 1.1.1 Features Models : LT-H548DLE1, LT-C548DLE1, LT-H548DLE2, LT-C548DLE2, LT-H488DLE1, LT-C488DLE1, LT-H368DLE1, LT-C368DLE1, LT-C286HLE1, LT-C286HLE1, LT-H246HLE1, LT-C246HLE1, LT-H186ELF1, LT-C186ELF1, LT-C186ELE1, LT-H186ELE1
• PLASMA air purifying system
• Group control
The PLASMA air purifying system developed uniquely by LG not only removes microscopic contaminants and dust, but also removes house mites, pollen, and pet fur to help prevent allergic diseases like asthma. With a filter that can be used over and over again by simply washing with water, you can enjoy clean fresh air.
1) Operation summary
Dust electrode discharge Dust particles
Photo-Catalyst Coated Mesh
Ionizer +4.8KV discharge
Polluted Air
+
+ + Purified fresh Air
+ +
Generating plasma
Odour Odour molecule
Dust free! Odor free! Anti-allergy !
- Where several products are linked, one specific control device can control a specific number of products. 2) Specific operation - Connecting line is linked to each of the indoor equipments for communication. A specific control device is connected to each of them and this control device can control the same function. - Group control function is enabled by cutting an optional jump wire in the wired remote controller. At this time, the main system will not respond in order to prevent data collision. - While executing group control command, use the random data(0-3minutes) in the main body of indoor equipment for limiting starting current. - Control device can control up to 16 indoor equipments. 1
2
16
Remote Controller
20
Ceiling Cassette
Ceiling cassette 4 – way
5CST2-06A
Features
Zero power consumption in standby mode by adopting SMPS (Switching mode power supply)
• High ceiling operation
• Power waste due to standby mode - Power is wasted if a plug is connected to an outlet even though the appliance is turned off.
If the height of installation is low then you can adjust low rpm of indoor fan motor. On the other hand if the height of the installation is high you can adjust high speed of indoor fan motor. Selection of speed can be done by slide switch at the back of the LCD wired remote controller.
• Development of super power-saving SMPS (Switching Mode Power Supply) - Zero standby power by reducing 90% of standby power. - No need to pull out every plug when system is not in use.
Low noise with 3-dimensional turbo fan
According to the height of the installation, it provides variability of indoor fan motor speed.
ex: If ceiling height of 2.7-3m(taken as standard for the product) is exceeded, then the slide switch is iperated in the high mode discharging air at a high volume rate and when below 2.7m, the switch is adjusted to discharge at a lower volume rate.
The most advanced low-noise design.The adoption of turbo-fan and round type give the most quiet operation.
Air velocity distribution Noise output measured in anechoic test room
Built-in drain pump A standard drain-head height of up to 700mm is possible, creating the ideal solution for perfect water drainage.
Ceiling cassette 4 – way
Ceiling Cassette
21
List of functions
5CST2-06A
1.1.2 List of functions Category
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
CAC Network Function
Special Function Kit Others
LT-H548DLE1
Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor
LT-H548DLE2
LT-H488DLE1
4 4 4 X X X Auto Auto Auto X X X O O O 4/5/4 4/5/4 4/5/4 X X X O O O O O O O O O X X X Option Option Option O O O O O O O O O O O O O O O O O O O O O X X X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X Accessory(PQWRHSF0) Accessory(PQWRHSF0) Accessory(PQWRHSF0) X X X Option Option Option O O O X X X Option Option Option X X X X X X -
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
22
Ceiling Cassette
Ceiling cassette 4 – way
5CST2-06A
List of functions
Category
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
CAC Network Function
Special Function Kit Others
LT-H368DLE1
Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor
LT-H286HLE1
LT-H246HLE1
4 4 4 X X X Auto Auto Auto X X X O O O 4/5/4 4/5/4 4/5/4 X X X O O O O O O O O O X X X Option Option Option O O O O O O O O O O O O O O O O O O O O O X X X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X Accessory(PQWRHSF0) Accessory(PQWRHSF0) Accessory(PQWRHSF0) X X X Option Option Option O O O X X X Option Option Option X X X X X X -
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling cassette 4 – way
Ceiling Cassette
23
List of functions
Category
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
CAC Network Function
Special Function Kit Others
5CST2-06A
Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor
LT-H186ELE1
LT-H186ELF1
4 X Auto X O 4/5/4 X O O O X X O O O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
4 X Auto X O 4/5/4 X O O O X O O O O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
24
Ceiling Cassette
Ceiling cassette 4 – way
5CST2-06A
List of functions
Category
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
CAC Network Function
Special Function Kit Others
Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor
LT-C548DLE1
LT-C548DLE2
LT-C488DLE1
4 X Auto X O 4/5/X O O O X Option O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
4 X Auto X O 4/5/X O O O X Option O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
4 X Auto X O 4/5/X O O O X Option O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling cassette 4 – way
Ceiling Cassette
25
List of functions
Category
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
CAC Network Function
Special Function Kit Others
5CST2-06A
Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor
LT-C368DLE1
LT-C286HLE1
LT-C246HLE1
4 X Auto X O 4/5/X O O O X Option O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
4 X Auto X O 4/5/X O O O X Option O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
4 X Auto X O 4/5/X O O O X Option O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
26
Ceiling Cassette
Ceiling cassette 4 – way
5CST2-06A
List of functions
Category
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
CAC Network Function
Special Function Kit Others
Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor
LT-C186ELE1
LT-C186ELF1
4 X Auto X O 4/5/X O O O X X O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
4 X Auto X O 4/5/X O O O X O O O O O O X O O O O O O O O O O X X X X Accessory(PQWRHSF0) X Option O X Option X X -
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling cassette 4 – way
Ceiling Cassette
27
Specifications
5CST2-06A
1.1.3 Specifications Indoor unit type
Ceilling Cassette - 4way
Model Power supply
Phase/Volts/Hz
Cooling capacity Heating capacity Current
Nominal running current
Fan
Motor Type
LT-H488DLE1
3 / 380-415 / 50
3 / 380-415 / 50
3 / 380-415 / 50
kW
15.82
15.82
14
54,000
54,000
47,770
kW
17.29
17.29
15.2
Btu/h
59,000
59,000
51,865
A
Motor Output(W) * number of units
Capacitor
LT-H548DLE2
Btu/h
Fan Type Air flow rate (H/M/L)
LT-H548DLE1
0.4
0.4
0.4
BLDC
BLDC
BLDC
Turbo Fan
Turbo Fan
Turbo Fan
124*1
124*1
124*1
CMM
37 / 35 / 31
37 / 35 / 31
31 / 29 / 27
CFM
1300 / 1240 / 1090
1300 / 1240 / 1090
1094 / 1024 / 953
µF/Vac
680 / 400
680 / 400
680 / 400
Direct
Direct
Direct
2R*12C*19
2R*12C*19
2R*12C*19
Drive Coil
Row * Column * FPI
Dimensions
Body
mm(inch)
840*840*288(331/16*331/16*111/3) 840*840*288(331/16*331/16*111/3) 840*840*288(331/16*331/16*111/3)
(W*D*H)
Decorative Panel
mm(inch)
950*950*30(3713/32*3713/32*13/16)
950*950*30(3713/32*3713/32*13/16)
950*950*30(3713/32*3713/32*13/16)
Weight
Body
kg(lbs)
31(68.3)
31(68.3)
31(68.3)
Decorative Panel
kg(lbs)
Air filter
5(11)
5(11)
5(11)
Long Life filter
Long Life filter
Long Life filter
Sound Level (H/M/L)
dB(A)+3
48 / 46 / 44
48 / 46 / 44
45 / 44 / 42
Piping Connections Liquid
mm(inch)
9.52(3/8)
9.52(3/8)
9.52(3/8)
mm(inch)
19.05(3/4)
19.05(3/4)
19.05(3/4)
mm
32 / 25
32 / 25
32 / 25
Gas Drain
OD/ID
Dehumidification rate
l/h
Safety Devices Temperature sensor Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable
No. * mm2
6.3
6.3
6.3
Fuse, Thermal Protector
Fuse, Thermal Protector
Fuse, Thermal Protector
Thermistor
Thermistor
Thermistor
R22
R22
R22
Capillary
Capillary
Capillary
LTUH548DLE1
LTUH548DLE2
LTUH488DLE1
5*3.5(5*0.75)
5*3.5(5*0.75)
5*3.5 (5*0.75)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
28
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
Ceiling cassette 4 – way
5CST2-06A
Specifications
Indoor unit type
Ceilling Cassette - 4way
Model Power supply
Phase/Volts/Hz
Cooling capacity Heating capacity Current
Nominal running current
Fan
Motor Type
LT-H246HLE1
3 / 380-415 / 50
1 / 220-240 / 50
1/220~240/50
kW
10.5
8.2
7.0
35,830
27,982
23,885
kW
11.2
8.8
7.0
Btu/h
38,220
30,030
23,885
A
Motor Output(W) * number of units
Capacitor
LT-H286HLE1
Btu/h
Fan Type Air flow rate (H/M/L)
LT-H368DLE1
0.4
0.3
0.3
BLDC
BLDC
BLDC
Turbo Fan
Turbo Fan
Turbo Fan
124*1
100*1
100*1
CMM
24 / 21 / 19
20/17/14
17 / 15 / 13
CFM
848 / 742 / 671
706 / 600 / 494
600/530/460
µF/Vac
680 / 400
220/450
220 / 450
Direct
Direct
Direct
2R*12C*19
2R*9C*18
2R*9C*18
Drive Coil
Row * Column * FPI
Dimensions
Body
mm(inch)
840*840*288(33.1*33.1*11.3) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9)
(W*D*H)
Decorative Panel
mm(inch)
950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2)
Weight
Body
kg(lbs)
Decorative Panel
kg(lbs)
Air filter
31(68.3)
28.5(62.8)
27(59.5)
5(11)
5(11)
5(11)
Long Life Filter
Long Life Filter
Long Life Filter
Sound Level (H/M/L)
dB(A)+3
41/38/35
38/33/30
36 / 33 / 30
Piping Connections Liquid
mm(inch)
6.35(1/4)
6.35(1/4)
6.35(1/4)
mm(inch)
15.88(5/8)
15.88(5/8)
15.88(5/8)
mm
32/25
32/25
32 / 25
Gas Drain
OD/ID
Dehumidification rate
l/h
Safety Devices Temperature sensor Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable
No. * mm2
3
2.4
2.4
Fuse,Thermal Protector
Fuse,Thermal Protector
Fuse, Thermal Protector
Thermistor
Thermistor
Thermistor
R22
R22
R22
Capillary
Capillary
Capillary
LTUH368DLE1
LTUH286HLE1
LTUH246HLE1
5*1.25(5*0.75)
3*2.5(5*0.75)
3*2.5(5*0.75)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
Ceiling cassette 4 – way
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
29
Specifications
5CST2-06A
Indoor unit type
Ceilling Cassette - 4way
Model Power supply
Phase/Volts/Hz
Cooling capacity Heating capacity Current
Nominal running current
Fan
Motor Type
LT-H186ELE1
LT-H186ELF1
1/220~240/50
1/220~240/50
kW
5.27
5.27
Btu/h
18,000
18,000
kW
5.53
5.53
Btu/h
18,900
18,900
A
Fan Type
0.3
0.3
BLDC
BLDC
Turbo Fan
Turbo Fan
100*1
100*1
Motor Output(W) * number of units Air flow rate (H/M/L) Capacitor
CMM
11/10/9
11/10/9
CFM
388/353/317
388/353/317
µF/Vac
220 / 450
220 / 450
Direct
Direct
Drive Coil
Row * Column * FPI
2R*11C*18
2R*11C*18
Dimensions
Body
mm(inch)
570*570*269(22.4*22.4*10.6)
570*570*269(22.4*22.4*10.6)
(W*D*H)
Decorative Panel
mm(inch)
650*650*30(25.6*25.6*1.2)
650*650*30(25.6*25.6*1.2)
Weight
Body
kg(lbs)
19(41.8)
19(41.8)
Decorative Panel
kg(lbs)
Air filter
3(6.6)
3(6.6)
Long Life Filter
Long Life Filter
Sound Level (H/M/L)
dB(A)+3
41/39/37
41/39/37
Piping Connections Liquid
mm(inch)
6.35(1/4)
6.35(1/4)
mm(inch)
12.7(1/2)
12.7(1/2)
mm
32 / 25
32 / 25
Gas Drain
OD/ID
Dehumidification rate
l/h
Safety Devices Temperature sensor
2.4
2.4
Fuse, Thermal Protector
Fuse, Thermal Protector
Thermistor
Thermistor
R22
R22
Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable
No. * mm2
Capillary
Capillary
LTUH186ELE1
LTUH186ELF1
3*2.5(5*0.75)
3*2.5(5*0.75)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
30
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
Ceiling cassette 4 – way
5CST2-06A
Specifications
Indoor unit type
Ceilling Cassette - 4way
Model Power supply
Phase/Volts/Hz
Cooling capacity Heating capacity Current
Nominal running current
Fan
Motor Type
LT-C488DLE1
3 / 380-415 / 50
3 / 380-415 / 50
3 / 380-415 / 50
kW
15.82
15.82
14
54,000
54,000
47,770
kW
-
-
-
Btu/h
-
-
-
A
Motor Output(W) * number of units
Capacitor
LT-C548DLE2
Btu/h
Fan Type Air flow rate (H/M/L)
LT-C548DLE1
0.4
0.4
0.4
BLDC
BLDC
BLDC
Turbo Fan
Turbo Fan
Turbo Fan
124*1
124*1
124*1
CMM
37 / 35 / 31
37 / 35 / 31
31 / 29 / 27
CFM
1300 / 1240 / 1090
1300 / 1240 / 1090
1094 / 1024 / 953
µF/Vac
680 / 450
680 / 450
680 / 400
Direct
Direct
Direct
2R*12C*19
2R*12C*19
2R*12C*19
Drive Coil
Row * Column * FPI
Dimensions
Body
mm(inch)
840*840*288(331/16*331/16*111/3) 840*840*288(331/16*331/16*111/3) 840*840*288(331/16*331/16*111/3)
(W*D*H)
Decorative Panel
mm(inch)
950*950*30(3713/32*3713/32*13/16) 950*950*30(3713/32*3713/32*13/16) 950*950*30(3713/32*3713/32*13/16)
Weight
Body
kg(lbs)
Decorative Panel
kg(lbs)
Air filter
31(68.3)
31(68.3)
31(68.3)
5(11)
5(11)
5(11)
Long Life filter
Long Life filter
Long Life filter
Sound Level (H/M/L)
dB(A)+3
48 / 46 / 44
48 / 46 / 44
45 / 44 / 42
Piping Connections Liquid
mm(inch)
9.52(3/8)
9.52(3/8)
9.52(3/8)
mm(inch)
19.05(3/4)
19.05(3/4)
19.05(3/4)
mm
32 / 25
32 / 25
32 / 25
6.3
6.3
Gas Drain
OD/ID
Dehumidification rate
l/h
Safety Devices Temperature sensor Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable
No. * mm2
Fuse, Thermal Protector
Thermistor
Thermistor
Thermistor
R22
R22
R22
Capillary
Capillary
Capillary
LTUC548DLE1
LTUC548DLE2
LTUC488DLE1
5*1.25(4*0.75)
5*1.25(4*0.75)
5*3.5 (4*0.75)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
Ceiling cassette 4 – way
6.3
Fuse, Thermal Protector Fuse, Thermal Protector
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
31
Specifications
5CST2-06A
Indoor unit type
Ceilling Cassette - 4way
Model Power supply
Phase/Volts/Hz
Cooling capacity Heating capacity Current
Nominal running current
Fan
Motor Type
LT-C246HLE1
3 / 380-415 / 50
1 / 220-240 / 50
1/220~240/50
kW
10.5
8.2
7.0
35,830
27,982
23,885
kW
-
-
-
Btu/h
-
-
-
A
Motor Output(W) * number of units
Capacitor
LT-C286HLE1
Btu/h
Fan Type Air flow rate (H/M/L)
LT-C368DLE1
0.4
0.3
0.3
BLDC
BLDC
BLDC
Turbo Fan
Turbo Fan
Turbo Fan
124*1
100*1
100*1
CMM
24 / 21 / 19
20/17/14
17 / 15 / 13
CFM
848 / 742 / 671
706 / 600 / 494
600/530/460
µF/Vac
680 / 400
220/450
220 / 450
Direct
Direct
Direct
2R*12C*19
2R*9C*18
2R*9C*18
Drive Coil
Row * Column * FPI
Dimensions
Body
mm(inch)
(W*D*H)
Decorative Panel
mm(inch)
950*950*30(37.4*37.4*1.2)
950*950*30(37.4*37.4*1.2)
950*950*30(37.4*37.4*1.2)
Weight
Body
kg(lbs)
31(68.3)
28.5(62.8)
27(59.5)
Decorative Panel
kg(lbs)
Air filter
840*840*288(33.1*33.1*11.3) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9)
5(11)
5(11)
5(11)
Long Life Filter
Long Life Filter
Long Life Filter
Sound Level (H/M/L)
dB(A)+3
41/38/35
38/33/30
36 / 33 / 30
Piping Connections Liquid
mm(inch)
6.35(1/4)
6.35(1/4)
6.35(1/4)
mm(inch)
15.88(5/8)
15.88(5/8)
15.88(5/8)
mm
32/25
32/25
32 / 25
Gas Drain
OD/ID
Dehumidification rate
l/h
Safety Devices Temperature sensor Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable
No. * mm2
3
2.4
2.4
Fuse,Thermal Protector
Fuse,Thermal Protector
Fuse, Thermal Protector
Thermistor
Thermistor
Thermistor
R22
R22
R22
Capillary
Capillary
Capillary
LTUC368DLE1
LTUC286HLE1
LTUC246HLE1
5*1.25(4*0.75)
3*2.5(4*0.75)
3*2.5(4*0.75)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
32
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
Ceiling cassette 4 – way
5CST2-06A
Specifications
Indoor unit type
Ceilling Cassette - 4way
Model Power supply
Phase/Volts/Hz
Cooling capacity Heating capacity Current
Nominal running current
Fan
Motor Type
LT-C186ELF1
LT-C186ELE1
1/220~240/50
1/220~240/50
kW
5.27
5.27
Btu/h
18,000
18,000
kW
-
-
Btu/h
-
-
0.3
0.3
BLDC
BLDC
Turbo Fan
Turbo Fan
100*1
100*1
A
Fan Type Motor Output(W) * number of units Air flow rate (H/M/L) Capacitor
CMM
11/10/9
11/10/9
CFM
388/353/317
388/353/317
µF/Vac
220 / 450
220 / 450
Direct
Direct
Drive Coil
Row * Column * FPI
2R*11C*18
2R*11C*18
Dimensions
Body
mm(inch)
570*570*269(22.4*22.4*10.6)
570*570*269(22.4*22.4*10.6)
(W*D*H)
Decorative Panel
mm(inch)
650*650*30(25.6*25.6*1.2)
650*650*30(25.6*25.6*1.2)
Weight
Body
kg(lbs)
19(41.8)
19(41.8)
Decorative Panel
kg(lbs)
Air filter
3(6.6)
3(6.6)
Long Life Filter
Long Life Filter
Sound Level (H/M/L)
dB(A)+3
41/39/37
41/39/37
Piping Connections Liquid
mm(inch)
6.35(1/4)
6.35(1/4)
mm(inch)
12.7(1/2)
12.7(1/2)
mm
32 / 25
32 / 25
Gas Drain
OD/ID
Dehumidification rate
l/h
Safety Devices Temperature sensor
2.4
2.4
Fuse, Thermal Protector
Fuse, Thermal Protector
Thermistor
Thermistor
R22
R22
Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable
No. * mm2
Capillary
Capillary
LTUC186ELF1
LTUC186ELE1
3*2.5(5*0.75)
3*2.5(5*0.75)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
Ceiling cassette 4 – way
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
33
30
950
225 70.4 30 47
Ceiling Cassette
40
TH
950
45
840
785
288 140 30 52
40
110
TD
110
678
840
840 Unit size 90
840 Unit size
90
785(Hanging bolt) 45
875 (Ceiling opening)
Unit:mm
101.5 672 (Hanging bolt) 101.5 152
34 210.5
875 (Ceiling opening)
mm
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lge.com/airconditioner
CHASSIS CODE: TD, TH
3. The Unit is powered from the outdoor unit. Therefore power cable should be connected with the outdoor unit.
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
32/25
15.88(5/8) 32/25
15.88(5/8) 32/25
19.05(3/4) 32/25
19.05(3/4) 32/25
19.05(3/4) 32/25
19.05(3/4)
6.35(1/4)
6.35(1/4) 9.52(3/8) 9.52(3/8)
9.52(3/8)
-
7.0 23,800
15.2 51,865
17.29 59,000
kW Btu/h
9.52(3/8)
7.0 23,800
7.0 23,800
14 47,770
14 47,770
15.82 54,000
15.82 54,000
kW Btu/h
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Drain(OD/ID)
LT-H548DLE1/2 LT-C548DLE1/2 LT-H488DLE1 LT-C488DLE1 LT-H246HLE1 LT-C246HLE1
Remark
+ PT-HDA1 + PT-HDC1 + PT-CDA1 + PT-CDC1
Ø / V / Hz 3/380~415/50 3/380~415/50 3/380~415/50 3/380~415/50 1/220~240/50 1/220~240/50
Model
Liquid(Ø) mm(inch) Piping Connections Gas(Ø) mm(inch)
Heating Capacity
Cooling Capacity
Power supply
Technical Specification
Power supply connection
Liquid pipe connection
7
Gas pipe connection
5
Drain pipe connection
Air discharge grille
4
6
Air suction grille
3
Decoration panel
Part Name
2
1
No.
Heat Pump Heat Pump(Plasma) Cooling Only Cooling Only(Plasma)
Ceiling Cassette 4-way + Decoration Panel
Dimensions 5CST2-06A
1.1.4 Dimensions
Ceiling cassette 4 – way 139.8
84
30
950
225 70.4 30 47
Ceiling Cassette
40
TH
950
45
840
785
288 140 30 52
40
110
TD
110
678
840
840 Unit size 90
840 Unit size
90
785(Hanging bolt) 45
875 (Ceiling opening)
Unit:mm
101.5 672 (Hanging bolt) 101.5 152
Ceiling cassette 4 – way 210.5
875 (Ceiling opening)
Part Name
mm
32/25
15.88(5/8) 32/25
15.88(5/8) 32/25
15.88(5/8) 32/25
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lge.com/airconditioner
CHASSIS CODE: TD, TH
3. The Unit is powered from the outdoor unit. Therefore power cable should be connected with the outdoor unit.
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Drain(OD/ID)
15.88(5/8)
6.35(1/4)
-
6.35(1/4)
-
8.8 30,030
11.2 38,220
kW Btu/h
6.35(1/4)
8.2 27,982
27,982 35,830 35,830 Btu/h
6.35(1/4)
1/220-240/50 8.2 10.5 10.5 kW
LT-C286HLE1 1/220-240/50
LT-H286HLE1 3/380-415/50
LT-C368DLE1 3/380-415/50
LT-H368DLE1
Remark
+ PT-HDA1 + PT-HDC1 + PT-CDA1 + PT-CDC1
Ø / V / Hz
Model
Liquid(Ø) mm(inch) Piping Connections Gas(Ø) mm(inch)
Heating Capacity
Cooling Capacity
Power supply
Technical Specification
Power supply connection
Liquid pipe connection
7
Gas pipe connection
5
Drain pipe connection
Air discharge grille
4
6
Air suction grille
3
Decoration panel
2
1
No.
Heat Pump Heat Pump(Plasma) Cooling Only Cooling Only(Plasma)
Ceiling Cassette 4-way + Decoration Panel
5CST2-06A Dimensions
35
139.8
84
670
30
Ceiling Cassette
670
2
3
1
4
5
60
450
570
6
450(Hanging bolt)
7
60 25 521(Hanging bolt) 25 521 52 120
600(Ceiling opening) 570
36 269
600(Ceiling opening)
Air discharge grille Gas pipe connection Liquid pipe connection Drain pipe connection Power supply connection
4 5 6 7
Model
mm
32/25
12.7(/2) 32/25
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lge.com/airconditioner
CHASSIS CODE: TE1
3. The Unit is powered from the outdoor unit. Therefore power cable should be connected with the outdoor unit.
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Drain(OD/ID)
12.7(/2)
6.35(1/4)
-
5.53 18,900
kW Btu/h
6.35(1/4)
5.27 18,000
18,000 Btu/h
1/220-240/50 5.27 kW
LT-C186ELE1/LT-C186ELF1 1/220-240/50
Ø / V / Hz
Liquid(Ø) mm(inch) Piping Connections Gas(Ø) mm(inch)
Heating Capacity
Cooling Capacity
Power supply
Remark
+ PT-HEA1 + PT-HEC1 + PT-CEA1 + PT-CEC1
LT-H186ELE1/LT-H186ELF1
Air suction grille
3
Technical Specification
Decoration panel
2
Part Name
1
No.
Heat pump Heat pump (Plasma) Cooling Cooling (Plasma)
Ceiling Cassette 4-way + Decoration Panel
5CST2-06A
5 R3
Ceiling cassette 4 – way
190
160
5CST2-06A
Piping diagrams
1.1.5 Piping diagrams Gas pipe connection port (flare connection)
Heat exchanger Th2
Turbo fan
Th1
Liquid pipe connection port (flare connection) Heating
Capillary tube
Cooling
■ Refrigerant pipe connection port diameters
(mm)
Model
Gas
Liquid
LT-H548DLE1/2
Ø 19.05
Ø 9.52
LT-C548DLE1/2
Ø 19.05
Ø 9.52
LT-H488DLE1
Ø 19.05
Ø 9.52
LT-C488DLE1
Ø 19.05
Ø 9.52
LT-H368DLE1
Ø 15.88
Ø 6.35
LT-C368DLE1
Ø 15.88
Ø 6.35
LT-H286HLE1
Ø 15.88
Ø 6.35
LT-C286HLE1
Ø 15.88
Ø 6.35
LT-H246HLE1
Ø 15.88
Ø 6.35
LT-C246HLE1
Ø 15.88
Ø 6.35
LT-H186ELF1
Ø12.7
Ø 6.35
LT-C186ELE1
Ø12.7
Ø 6.35
LT-H186ELE1
Ø12.7
Ø6.35
LT-C186ELF1
Ø12.7
Ø6.35
Ceiling cassette 4 – way
Ceiling Cassette
37
Wiring diagrams
5CST2-06A
1.1.6 Wiring diagrams 1) Wiring diagrams Models : LT-H548DLE1, LT-H548DLE2, LT-H488DLE1
Models :LT-H368DLE1, LT-H246HLE1, LT-H286HLE1
Connector Number CN-POWER CN-MOTOR CN-DPUMP CN-DISP CN-FLOAT CN-REMO CN-CC CN-ROOM CN-PIPE1 CN-GRILL CN-PTC CN-HVB
38
Location AC power supply BLDC fan motor output Drain pump output Display Float switch input Remote control Dry-contact Room sensor In-pipe thermistor Elevation grille PTC Heater HVB Ass'y (Air cleaner)
Ceiling Cassette
Ceiling cassette 4 – way
5CST2-06A
Wiring diagrams
Models : LT-C548DLE1, LT-C548DLE2, LT-C488DLE1
Models : LT-C368DLE1, LT-C246HLE1, LT-C286HLE1
Connector Number CN-POWER CN-MOTOR CN-DPUMP CN-DISP CN-FLOAT CN-REMO CN-CC CN-ROOM CN-PIPE1 CN-GRILL CN-PTC CN-HVB
Ceiling cassette 4 – way
Location AC power supply BLDC fan motor output Drain pump output Display Float switch input Remote control Dry-contact Room sensor In-pipe thermistor Elevation grille PTC Heater HVB Ass'y (Air cleaner)
Ceiling Cassette
39
Wiring diagrams
5CST2-06A
Models : LT-C186ELE1, LT-C186ELF1, LT-H186ELE1, LT-H186ELF1
Connector Number CN-POWER CN-MOTOR CN-DPUMP CN-DISP CN-FLOAT CN-REMO CN-CC CN-ROOM CN-PIPE1 CN-GRILL CN-PTC CN-HVB
Location AC power supply BLDC fan motor output Drain pump output Display Float switch input Remote control Dry-contact Room sensor In-pipe thermistor Elevation grille PTC Heater HVB Ass'y (Air cleaner)
2) PCB CN- DPUMP
CN- MOTOR 2
CN- FLOAT
CN- ROOM CN- POWER
CN- PIPE CN- REMO
CN- VANE 2
CN- DISP
CN- VANE 1
40
Ceiling Cassette
CN- HVB (PLASMA FILTER)
Ceiling cassette 4 – way
5CST2-06A
Air flow and temperature distributions (reference data)
1.1.7 Air flow and temperature distribution (reference data) Model : 24kBtu/h Cooling
Heating
Air velocity [m/s]
Air velocity [m/s] 2.7m 2.0
2.0
1.5
2.7m 2.0
2.0
1.5
1.5
2m
1.5
1.0
1.0
0.5
1.0 0.5
1m
0.5
2m 1.0 0.5
1m
0m 4m
3m
2m
1m
0m
1m
2m
3m
4m
0m 4m
Temperature [˚C]
3m
2m
1m
0m
1m
2m
3m
4m
Temperature [˚C] 2.7m 18 20
18 20
22
33
2m
2.7m
33
30
2m
30
21
22
24
1m 24
21 27 24
27
1m
24 0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
0m 4m
3m
2m
1m
0m
1m
2m
3m
4m
Model : 54kBtu/h Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m 2.0
2m 2.0
2.0
1.5 0.5 4m
3m
1.5
1.5
1.0
1.0
2m
1m
0m
1m
2.0
2m
1m
3m
0m 4m
1.5
1.0 0.5
0.5 4m
3m
2m
2m 1m
1.0 0.5
1m
0m
1m
2m
0m 4m
3m
Temperature [˚C]
Temperature [˚C]
2.7m
2.7m 33 20
3m
30
21 1m
22
24 4m
2m
2m
20
22
33
24
30
27
21 1m
24
27
24 2m
1m
0m
Ceiling cassette 4 – way
1m
2m
3m
0m 4m
4m
3m
Ceiling Cassette
2m
1m
0m
1m
2m
3m
0m 4m
41
Sound levels
5CST2-06A
1.1.8 Sound levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20µPa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
Ceiling 1.5m
Sound pressure level LT-H548DLE1 / LT-H548DLE2 LT-C548DLE1 / LT-C548DLE2
LT-H488DLE1/LT-C488DLE1 80
LT-H246HLE1 / LT-C246HLE1 80
High Middle Low
70
70
NC-65
60
NC-65
60 NC-60
NC-60 NC-55
NC-55
50
50 NC-50
NC-50
NC-45
NC-45
40
40 NC-40
NC-40
NC-35
NC-35
30
30 NC-30
NC-30
NC-25
NC-25
20
Approximate He aring Thres hold
NC-20
LT-H368DLE1 / LT-C368DLE1
125
250
500
1000
2000
4000
High Middle Low
70
NC-55
NC-55
NC-50
NC-50
NC-45
NC-45 NC-40
NC-35
NC-35
NC-30
NC-30
NC-25
NC-25
20
Approximate Hearing Threshold
NC-20 NC-15
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
4000
8000
LT-H186ELE1 / LT-H186ELF1 LT-C186ELE1 / LT-C186ELF1 High Middle Low
NC-65
NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30
NC-25
20
Approximate He aring Thres hold
NC-20 NC-15
10
125
2000
30
30
63
1000
40
40 NC-40
10
500
50
50
Approximate He aring Thres hold
250
60 NC-60
20
125
NC-65
60
30
63
70
NC-60
40
NC-15
80 High Middle Low
NC-65
50
NC-20
10
LT-H286HLE1 / LT-C286HLE1
70
60
42
8000
80
80
Approximate He aring Thres hold
NC-15
10 63
20
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
Ceiling Cassette
8000
63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
Ceiling cassette 4 – way
5CST2-06A
Controller
1.1.9 Controller 1) Wired remote controller
AUTO SWING
OPERATION
SET TEMP Room Temp
2ndF
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4
Time
Operation unit No Func Program set
On Off Set no. Time 01
03
05
07
09
11
13
15
17
19
21
23
5
14 2 3 4
SUB FUNCTION
HI MED LO
1 Timer
FAN SPEED
6 7 Timer
Cancel
2ndF
Program
Week
Holiday PLASMA
Set/Clr Hour
Min
RESET
8 9 10 11 12 13
1. Operation indication screen
10. Horizontal/Vertical air flow direction button
2. Swirl button
11. Room temperature / Filter sign release button
3. 2nd F button 4. Timer set/cancel Program/Week/Holiday Hour/Min/SET/Clr/Ventilator
12. Plasma/Heater button(Option)
5. Set temperature button
14. Operation lamp
13. Time reset button
6. ON/OFF button 7. Fan operation 8. Operation mode selection button 9. Fan speed button
Ceiling cassette 4 – way
Ceiling Cassette
43
Power supplys
5CST2-06A
2. Outdoor units 2.1 Single piping type 2.1.1. Power supply Type
Heat Pump
Cooling Only
Outdoor unit
Capacity [kBtu/h(kW)]
Circuit breaker capacity
Power supply
LT-H548DLE1/2
54(15.82)/59(17.29)
40A
3Ø, 380-415V, 50Hz
LT-H488DLE1
47.7(14.0)/51.8(15.2)
40A
3Ø, 380-415V, 50Hz
LT-H368DLE1
35.8(10.5)/38.2(11.2)
30A
3Ø, 380-415V, 50Hz
LT-H286HLE1
28.0(8.2)/30.0(8.8)
30A
1Ø, 220-240V, 50Hz
LT-H246HLE1
23.8(7.0)/23.8(7.0)
30A
1Ø, 220-240V, 50Hz
LT-H186ELF1/LT-H186ELE1
18(5.27)/18.9(5.53)
30A
1Ø, 220-240V,50Hz
LT-C548DLE1/2
54(15.82)/-
40A
3Ø, 380-415V, 50Hz
LT-C488DLE1
47.7(14.0)/-
40A
3Ø, 380-415V, 50Hz
LT-C368DLE1
35.8(10.5)/-
30A
3Ø, 380-415V, 50Hz
LT-C286HLE1
28.0(8.2)/-
30A
1Ø, 220-240V, 50Hz
LT-C246HLE1
23.8(7.0)/-
30A
1Ø, 220-240V, 50Hz
LT-C186ELE1/LT-C186ELF1
18(5.27)/-
30A
1Ø, 220-240V,50Hz
Power supply
Circuit breaker
Earth wire
44
Outdoor unit
Indoor unit
Ceiling Cassette
Outdoor unit
5CST2-06A
List of function
2.1.2 List of functions Category
LT-H548DLE1, LT-H548DLE2 O O X X O O X O O O O X Option Accessory -
LT-C548DLE1, LT-C548DLE2 O X X O O X O O O X Option Accessory -
Category
LT-H488DLE1, LT-H368DLE1 O O X O O O X O O O O X Option Accessory -
LT-C488DLE1, LT-C368DLE1 O X O O O X O O O X Option Accessory -
Category
LT-H286HE1, LT-H246HLE1, LT-H186ELF1, LT-H186ELE1 O O X O O X O O O O X Option X -
LT-C286HLE1, LT-C246HLE1, LT-C186ELE1, LT-C186ELF1 O X O O X O O O X Option X -
Function Defrost / Deicing High Pressure Switch Low Pressure Switch Phase protection Reliability Restart Delay (3-minutes) Self Diagnosis Soft Start Test Function Auto Changeover Convenience Auto Restart Operation Central control(LGAP) CAC Network PDI(Power Distribution Indicator) Function PI485 Special Function Kit Low Ambient Kit Thermistor Others Function Defrost / Deicing High Pressure Switch Low Pressure Switch Phase protection Reliability Restart Delay (3-minutes) Self Diagnosis Soft Start Test Function Auto Changeover Convenience Auto Restart Operation Central control(LGAP) CAC Network PDI(Power Distribution Indicator) Function PI485 Special Function Kit Low Ambient Kit Thermistor Others Function Defrost / Deicing High Pressure Switch Low Pressure Switch Phase protection Reliability Restart Delay (3-minutes) Self Diagnosis Soft Start Test Function Auto Changeover Convenience Auto Restart Operation Central control(LGAP) CAC Network PDI(Power Distribution Indicator) Function PI485 Special Function Kit Low Ambient Kit Thermistor Others
Note : O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. Outdoor unit
Ceiling Cassette
45
Specifications
5CST2-06A
2.1.3 Specifications Outdoor Unit Rated Capacity
Cooling
LT-H548DLE1
LT-H548DLE2
kW Btu/h kW Btu/h kW kW
LT-H488DLE1
15.82 15.82 54,000 54,000 Heating 17.29 17.29 59,000 59,000 Rated Input Cooling 5.6 5.6 Heating 6.6 6.6 Energy Label Testing combination Running current Cooling A 10.0 10.0 Heating A 11.5 11.5 Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz 3 / 380-415 / 50 3 / 380-415 / 50 Power supply Cable(outdoor) No. * mm*mm 5 * 3.5 5 * 3.5 Power and transmission cable No. * mm*mm 5 * 0.75(Including Earth) 5 * 0.75(Including Earth) Dimensions W*H*D mm(inch) 900 * 1060 * 370(35.4*41.7*14.6) 900 * 1060 * 370(35.4*41.7*14.6) Net weight kg(lbs) 105(231.5) 105(231.5) Maximum number of connectable unit 1 1 Compressor Type Scroll Scroll (constant) Qty * model SR073YAA SR073YAA Motor Type Induction Induction Oil charge volume cc 1,800 1,800 Oil type SUNISO 4GSI SUNISO 4GSI Refrigerant Charge(at 7.5m) g(oz) 3,750(132) 3,750(132) Type R22 R22 Control CAPILLARY CAPILLARY Heat Exchanger Rows * Column * FPI (2R *22C* 18 FPI)*2 (2R *22C* 18 FPI)*2 Defrosting method Reversing Cycle Reversing Cycle Fan Capacitor µF/Vac 6 / 370 6 / 370 Drive Direct Direct Discharge Direction Side / Top Side Side Air flow rate CMM(CFM) 105(3708) 105(3708) Noise level(H) Sound press dB(A) + 3 58 58 Piping connections Liquid mm(inch) 9.52(3/8) 9.52(3/8) Gas mm(inch) 19.05(3/4) 19.05(3/4) Max. piping length Main piping m 50 50 Max. elevation Indoor unit - Outdoor unit m 30 30 Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
46
Ceiling Cassette
14 47,770 4.90 51,865 4.9 5.3 8.5 8.7 3 / 380-415 / 50 5 * 3.5 5 * 0.75(Including Earth) 900 * 1060 * 370(35.4*41.7*14.6) 105(231.5) 1 Scroll SB061YAA Induction 1650 SUNISO 4GSI 3,700(130.5) R22 CAPILLARY (2R *22C* 18 FPI)*2 Reversing Cycle 6 / 370 Direct Side 105(3708) 59 9.52(3/8) 19.05(3/4) 50 30
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
Outdoor unit
5CST2-06A
Specifications
Outdoor Unit Rated Capacity
Cooling
LT-H368DLE1 kW Btu/h kW Btu/h kW kW
10.5 35,830 Heating 11.2 38,220 Rated Input Cooling 4.0 Heating 4.0 Energy Label Testing combination Running current Cooling A 7.0 Heating A 7.0 Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz 3 / 380-415 / 50 Power supply Cable(outdoor) No. * mm*mm 5*1.25 Power and transmission cable No. * mm*mm 5*0.75(Including Earth) Dimensions W*H*D mm(inch) 870*1060*320(34.3*41.7*12.6) Net weight kg(lbs) 88(194) Maximum number of connectable unit 1 Compressor Type Scroll (constant) Qty * model 1*SR049YAA Motor Type Induction Oil charge volume cc 1,800 Oil type SUNISO 4GSI Refrigerant Charge(at 7.5m) g(oz) 2,450(86.4) Type R22 Control CAPILLARY Heat Exchanger Rows * Column * FPI (2R*24C*18)*2 Defrosting method Reversing Cycle Fan Capacitor µF/Vac 2/400 Drive Direct Discharge Direction Side / Top Side Air flow rate CMM(CFM) 65(2295) Noise level(H) Sound press dB(A) + 3 60 Piping connections Liquid mm(inch) 6.35(1/4) Gas mm(inch) 15.88(5/8) Max. piping length Main piping m 50 Max. elevation Indoor unit - Outdoor unit m 30
LT-H286HLE1
LT-H246HLE1
8.2 27,982 8.8 30,030 2.9 2.9 13.7 13.7 1 / 220-240 / 50 3*2.5 5*0.75(Including Earth) 870*808*320(34.3*31.8*12.6) 68(149.9) 1 Twin Rotary(tropical) 1*QPT488PCA Induction 1,200 NM56 & 4GSI 2,250(79.4) R22 CAPILLARY (2R*36C*18)*1 Reversing Cycle 6/370-400 Direct Side 52(1836) 58 6.35(1/4) 15.88(5/8) 50 30
7.00 23,885 7.00 23,885 2.67 2.45 12.5 11.5 1 / 220~240 / 50 3*2.5 5*0.75(Including Earth) 870*655*320(34.3*25.8*12.6) 64(141.1) 1 Rotary(tropical) 1*QP442PBA Induction 700 SUNISO 4GSI 1,650(58.2) R22 CAPILLARY (2R*28C*18FPI)*1 Reversing Cycle 6/370 Direct Side 52(1,836.5)*1 56 6.35(1/4) 15.88(5/8) 50 30
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
Outdoor unit
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
47
Specifications
5CST2-06A
Outdoor Unit Rated Capacity
Cooling Heating
Rated Input
Cooling Heating
kW Btu/h kW Btu/h kW kW
Energy Label Testing combination Running current Cooling A Heating A Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz Power supply Cable(outdoor) No. * mm*mm Power and transmission cable No. * mm*mm Dimensions W*H*D mm(inch) Net weight kg(lbs) Maximum number of connectable unit Compressor Type (constant) Qty * model Motor Type Oil charge volume cc Oil type Refrigerant Charge(at 7.5m) g(oz) Type Control Heat Exchanger Rows * Column * FPI Defrosting method Fan Capacitor µF/Vac Drive Discharge Direction Side / Top Air flow rate CMM(CFM) Noise level(H) Sound press dB(A) + 3 Piping connections Liquid mm(inch) Gas mm(inch) Max. piping length Main piping m Max. elevation Indoor unit - Outdoor unit m
LT-H186ELE1
LT-H186ELF1
5.27 18,000 5.53 18,900 1.95 1.95 10 10 1 / 220~240 / 50 3*2.5 5*0.75(Including Earth) 840*575*275(33.1*22.6*10.8) 51(112.4) 1 Rotary(tropical) 1*QP325PCB Induction 700 SUNISO 4GSI 1,200(42.3) R22 CAPILLARY (2R*26C*18FPI)*1 Reversing Cycle 6/370 Direct Side 52(1,836)*1 55 6.35(1/4) 12.7(1/2) 30 20
5.27 18,000 5.53 18,900 1.95 1.95 10 10 1 / 220~240 / 50 3*2.5 5*0.75(Including Earth) 840*575*275(33.1*22.6*10.8) 51(112.4) 1 Rotary(tropical) 1*QP325PCB Induction 700 SUNISO 4GSI 1,200(42.3) R22 CAPILLARY (2R*26C*18FPI)*1 Reversing Cycle 6/370 Direct Side 52(1,836)*1 55 6.35(1/4) 12.7(1/2) 30 20
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
48
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
Outdoor unit
5CST2-06A
Specifications
Outdoor Unit Rated Capacity
Cooling
LT-C548DLE1
LT-C548DLE2
LT-C488DLE1
kW Btu/h kW Btu/h kW kW
15.82 15.82 14 54,000 54,000 47,770 Heating Rated Input Cooling 5.6 5.6 4.9 Heating Energy Label Testing combination Running current Cooling A 10.0 10.0 8.5 Heating A Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz 3 / 380-415 / 50 3 / 380-415 / 50 3 / 380-415 / 50 Power supply Cable(outdoor) No. * mm*mm 5 * 3.5 5 * 3.5 5 * 3.5 Power and transmission cable No. * mm*mm 4*0.75(Including Earth) 4*0.75(Including Earth) 4*0.75 (Including earth) Dimensions W*H*D mm(inch) 900*1160*370(35.4*45.6*14.6) 900*1160*370(35.4*45.6*14.6) 900*1160*370(35.4*45.6*14.6) Net weight kg(lbs) 105(231.5) 105(231.5) 105(231.5) Maximum number of connectable unit 1 1 1 Compressor Type Scroll Scroll Scroll (constant) Qty * model SR073YAA SR073YAA SB061YAA Motor Type Induction Induction Induction Oil charge volume cc 1,800 1,800 1650 Oil type SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI Refrigerant Charge(at 7.5m) g(oz) 3,750(132) 3,750(132) 3,700(130.5) Type R22 R22 R22 Control CAPILLARY CAPILLARY CAPILLARY Heat Exchanger Rows * Column * FPI (2R *22C* 18 FPI)*2 (2R *22C* 18 FPI)*2 (2R *22C* 18 FPI)*2 Defrosting method Fan Capacitor µF/Vac 6 / 370 6 / 370 6 / 370 Drive Direct Direct Direct Discharge Direction Side / Top Side Side Side Air flow rate CMM(CFM) 105(3708) 105(3708) 105(3708) Noise level(H) Sound press dB(A) + 3 58 58 59 Piping connections Liquid mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) Gas mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) Max. piping length Main piping m 50 50 50 Max. elevation Indoor unit - Outdoor unit m 30 30 30 Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
Outdoor unit
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
49
Specifications
5CST2-06A
Outdoor Unit Rated Capacity
Cooling
LT-C368DLE1 kW Btu/h kW Btu/h kW kW
10.5 35,830 Heating Rated Input Cooling 4.0 Heating Energy Label Testing combination Running current Cooling A 7.0 Heating A Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz 3 / 380-415 / 50 Power supply Cable(outdoor) No. * mm*mm 5*1.25 Power and transmission cable No. * mm*mm 4*0.75(Including Earth) Dimensions W*H*D mm(inch) 870*1060*320(34.3*41.7*12.6) Net weight kg(lbs) 88(194) Maximum number of connectable unit 1 Compressor Type Scroll (constant) Qty * model 1*SR049YAA Motor Type Induction Oil charge volume cc 1,800 Oil type SUNISO 4GSI Refrigerant Charge(at 7.5m) g(oz) 2,450(86.4) Type R22 Control CAPILLARY Heat Exchanger Rows * Column * FPI (2R*24C*18)*2 Defrosting method Fan Capacitor µF/Vac 2/400 Drive Direct Discharge Direction Side / Top Side Air flow rate CMM(CFM) 65(2295) Noise level(H) Sound press dB(A) + 3 60 Piping connections Liquid mm(inch) 6.35(1/4) Gas mm(inch) 15.88(5/8) Max. piping length Main piping m 50 Max. elevation Indoor unit - Outdoor unit m 30
LT-C286HLE1
LT-C246HLE1
8.2 27,982 2.9 13.7 1 / 220-240 / 50 3*2.5 4*0.75(Including Earth) 870*808*320(34.3*31.8*12.6) 68(149.9) 1 Twin Rotary(tropical) 1*QPT488PCA Induction 1,200 NM56 & 4GSI 2,250(79.4) R22 CAPILLARY (2R*36C*18)*1 6/370-400 Direct Side 52(1836) 58 6.35(1/4) 15.88(5/8) 50 30
7.00 23,885 2.67 12.5 1 / 220~240 / 50 3*2.5 4*0.75(Including Earth) 870*655*320(34.3*25.8*12.6) 64(141.1) 1 Rotary(tropical) 1*QP442PBA Induction 700 SUNISO 4GSI 1,650(58.2) R22 CAPILLARY (2R*28C*18FPI)*1 6/370 Direct Side 52(1,836.5)*1 56 6.35(1/4) 15.88(5/8) 50 30
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
50
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
Outdoor unit
5CST2-06A
Specifications
Outdoor Unit Rated Capacity
Cooling Heating
Rated Input
Cooling Heating
kW Btu/h kW Btu/h kW kW
Energy Label Testing combination Running current Cooling A Heating A Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz Power supply Cable(outdoor) No. * mm*mm Power and transmission cable No. * mm*mm Dimensions W*H*D mm(inch) Net weight kg(lbs) Maximum number of connectable unit Compressor Type (constant) Qty * model Motor Type Oil charge volume cc Oil type Refrigerant Charge(at 7.5m) g(oz) Type Control Heat Exchanger Rows * Column * FPI Defrosting method Fan Capacitor µF/Vac Drive Discharge Direction Side / Top Air flow rate CMM(CFM) Noise level(H) Sound press dB(A) + 3 Piping connections Liquid mm(inch) Gas mm(inch) Max. piping length Main piping m Max. elevation Indoor unit - Outdoor unit m
LT-C186ELE1
LT-C186ELF1
5.27 18,000 1.95 10 1 / 220~240 / 50 3*2.5 5*0.75(Including Earth) 840*575*275(33.1*22.6*10.8) 51(112.4) 1 Rotary(tropical) 1*QP325PCB Induction 700 SUNISO 4GSI 1,200(42.3) R22 CAPILLARY (2R*26C*18FPI)*1 6/370 Direct Side 52(1,836)*1 55 6.35(1/4) 12.7(1/2) 30 20
5.27 18,000 1.95 10 1 / 220~240 / 50 3*2.5 5*0.75(Including Earth) 840*575*275(33.1*22.6*10.8) 51(112.4) 1 Rotary(tropical) 1*QP325PCB Induction 700 SUNISO 4GSI 1,200(42.3) R22 CAPILLARY (2R*26C*18FPI)*1 6/370 Direct Side 52(1,836)*1 55 6.35(1/4) 12.7(1/2) 30 20
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB / 19°C(66.2°F) WB - Outdoor Temperature 35°C(95°F) DB / 24°C(75.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero. 2. The specification may be subject to change without prior notice for purpose of improvement.
Outdoor unit
Ceiling Cassette
Conversion Formula kW = Btu/h × 0.0002931 CFM = CMM × 35.3
51
175
550
900
175
112
1
370 45
410
1130
4-hole for anchor bolts
460 120 83
52
Ceiling Cassette
30
4
2
3
MODEL
LT-H548DLE1/2 LT-C548DLE1/2 LT-H488DLE1 LT-C488DLE1 3 / 380-415 / 50 3 / 380-415 / 50 3 / 380-415 / 50 3 / 380-415 / 50 15.82 15.82 14.0 14.0 54,000 47,770 47,770 54,000 15.2 17.29 59,000 51,865 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
LT-H548DLE1/2, LT-H488DLE1 LT-C548DLE1/2, LT-C488DLE1
Dimensions 5CST2-06A
2.1.4 Dimensions
Outdoor unit
1160
Outdoor unit MODEL
LT-H368DLE1 3 / 380-415 / 50 10.5 35,830 11.2 38,220 6.35(1/4) 15.88(5/8)
LT-C368DLE1 3 / 380-415 / 50 10.5 35,830 6.35(1/4) 15.88(5/8)
LT-H368DLE1, LT-C368DLE1
5CST2-06A Dimensions
Ceiling Cassette
53
54 Model
6.35(1/4) 15.88(5/8)
6.35(1/4) 15.88(5/8)
30,030
8.8
8.2 27,982
8.2 27,982
LT-C286HLE1 1 / 220-240 / 50
LT-H286HLE1 1 / 220-240 / 50
LT-H286HLE1, LT-C286HLE1
Dimensions 5CST2-06A
Ceiling Cassette
Outdoor unit
1
Model
Outdoor unit 6.35(1/4) 15.88(5/8)
6.35(1/4) 15.88(5/8)
23,800
7.0
7.0 23,800
7.0 23,800
LT-C246HLE1 1 / 220-240 / 50
LT-H246HLE1 1 / 220-240 / 50
LT-H246HLE1 LT-C246HLE1
5CST2-06A Dimensions
Ceiling Cassette
55
299.8
639.4
840
71
1
336.4 577
840
276 62
Ceiling Cassette 70
56 16.4
5
276
3
2
4
Model
6.35(1/4) 12.7(1/2)
6.35(1/4) 12.7(1/2)
18,900
5.53
5.27 18,000
1 / 220-240 / 50 5.27
LT-C186ELF1 1 / 220-240 / 50
LT-H186ELF1
18,000
LT-C186ELE1
LT-H186ELE1
LT-C(H)186ELE1 LT-C(H)186ELF1
Dimensions 5CST2-06A
Outdoor unit
每4
86
290.3
508.5
321.8
5CST2-06A
Piping siagrams
2.1.5 Piping diagrams Models : LT-H548DLE1 OUTDOOR UNIT CAPILLARY TUBE LIQUID SIDE
HEAT EXCHANGER
Th3
GAS SIDE REVERSING VALVE HIGH PRESSURE S/W
ACCUMULATOR
COOLING HEATING
COMPRESSOR
Models : LT-H548DLE2 OUTDOOR UNIT CAPILLARY TUBE LIQUID SIDE
CAPILLARY TUBE
2-WAY VALVE
HEAT EXCHANGER (Condenser)
GAS SIDE 3-WAY VALVE
CAPILLARY TUBE
ACCUMULATOR
Outdoor unit
REVERSING VALVE
COMPRESSOR
Ceiling Cassette
COOLING HEATING
57
Piping siagrams
5CST2-06A
Models : LT-C548DLE1 OUTDOOR UNIT CAPILLARY TUBE LIQUID SIDE
HEAT EXCHANGER
GAS SIDE REVERSING VALVE HIGH PRESSURE S/W
ACCUMULATOR
COOLING
COMPRESSOR
Models : LT-C548DLE2 OUTDOOR UNIT CAPILLARY TUBE LIQUID SIDE
CAPILLARY TUBE
2-WAY VALVE
HEAT EXCHANGER (Condenser)
GAS SIDE 3-WAY VALVE
CAPILLARY TUBE
ACCUMULATOR
58
REVERSING VALVE
COMPRESSOR
Ceiling Cassette
COOLING
Outdoor unit
5CST2-06A
Piping siagrams
Models : LT-H488DLE1 Outdoor Unit
Liquid Side
Capillary Tube
3-Way Valve
Heat Exchanger (Condenser)
Th3
Gas Side Reversing Valve
3-Way Valve
High Pressure S/W Cooling Heating
Compressor
Models : LT-C488DLE1 OUTDOOR UNIT
LIQUID SIDE
CAPILLARY TUBE
3-WAY VALVE
Heat Exchanger (Condenser)
GAS SIDE
COMPRESSOR
3-WAY VALVE
Outdoor unit
Ceiling Cassette
59
Piping siagrams
5CST2-06A
Models : LT-H246HLE1, LT-H286HLE1, LT-H368DLE1 OUTDOOR UNIT CAPILLARY TUBE LIQUID SIDE
CAPILLARY TUBE
2-WAY VALVE
HEAT EXCHANGER (Condenser)
Th3
GAS SIDE REVERSING VALVE
3-WAY VALVE
HIGH PRESSURE S/W ACCUMULATOR
COOLING HEATING
COMPRESSOR
Models : LT-C246HLE1, LT-C286HLE1, LT-C368DLE1 OUTDOOR UNIT CAPILLARY TUBE LIQUID SIDE
CAPILLARY TUBE
2-WAY VALVE
HEAT EXCHANGER (Condenser)
GAS SIDE REVERSING VALVE
3-WAY VALVE
HIGH PRESSURE S/W ACCUMULATOR
60
COMPRESSOR
Ceiling Cassette
COOLING
Outdoor unit
5CST2-06A
Piping siagrams
Model : LT-H186ELE1, LT-H186ELF1 Outdoor Unit
Liquid Side
Capillary Tube
2-Way Valve
Heat Exchanger (Condenser)
Th3
Gas Side Reversing Valve
3-Way Valve
High Pressure S/W Cooling Heating
Compressor
Model : LT-C186ELF1, LT-C186ELE1 OUTDOOR UNIT
LIQUID SIDE
CAPILLARY TUBE
2-Way Valve
Heat Exchanger (Condenser)
GAS SIDE
COMPRESSOR
3Way Valve
Outdoor unit
Ceiling Cassette
61
Wiring diagrams
5CST2-06A
2.1.6 Wiring diagrams Models : LT-H548DLE1
Models : LT-H548DLE2
62
Ceiling Cassette
Outdoor unit
5CST2-06A
Wiring diagrams
Models : LT-C548DLE1
Models : LT-C548DLE2
Outdoor unit
Ceiling Cassette
63
Wiring diagrams
5CST2-06A
Models : LT-H488DLE1
Models : LT-C488DLE1
64
Ceiling Cassette
Outdoor unit
5CST2-06A
Wiring diagrams
Models : LT-H368DLE1
Models : LT-C368DLE1
Outdoor unit
Ceiling Cassette
65
Wiring diagrams
5CST2-06A
Models : LT-H246HLE1, LT-H286HLE1
Models : LT-C246HLE1, LT-C286HLE1
66
Ceiling Cassette
Outdoor unit
5CST2-06A
Wiring diagrams
Model : LT-H186ELE1, LT-H186ELF1
Model : LT-C186ELF1, LT-C186ELE1
Outdoor unit
Ceiling Cassette
67
Capacity tables
5CST2-06A
2.1.7 Capacity tables [Cooling capacity] Model No.: LT-H548DLE1/2, LT-C548DLE1/2 Outdoor Air Temperature : °CDB
Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20 22 25 27 30 32
20 TC 12.8 15.0 16.7 17.5 19.2 19.9
SHC 9.3 10.6 11.5 11.9 12.6 12.8
25 PI 3.67 3.73 3.78 3.85 3.9 4.0
TC 12.6 14.7 16.4 17.1 18.8 19.5
SHC 9.2 10.5 11.4 11.7 12.4 12.6
32 PI 4.3 4.4 4.5 4.6 4.6 4.7
TC 12.0 14.0 15.6 16.3 17.9 18.6
SHC 9.0 10.2 11.0 11.4 12.0 12.2
35 PI 5.1 5.1 5.2 5.3 5.4 5.5
TC SHC 11.6 8.8 13.6 9.9 15.1 10.8 15.8 11.1 17.4 11.7 18.0 11.9
40 PI 5.3 5.4 5.5 5.6 5.7 5.8
TC 11.2 13.0 14.6 15.2 16.7 17.4
SHC 8.6 9.7 10.5 10.8 11.4 11.6
43 PI 5.7 5.8 5.9 6.0 6.0 6.1
TC SHC 10.9 8.5 12.7 9.6 14.2 10.3 14.9 10.7 16.3 11.2 17.0 11.3
PI 5.9 6.0 6.1 6.2 6.2 6.3
Model No.: LT-H488DLE1, LT-C488DLE1 Outdoor Air Temperature : °CDB
Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20 22 25 27 30 32
20 TC 11.4 13.2 14.8 15.5 17.0 17.6
SHC 9.1 10.4 11.3 11.7 12.4 12.6
25 PI TC SHC 3.21 11.1 9.0 3.26 13.0 10.3 3.31 14.5 11.1 3.37 15.1 11.5 3.4 16.6 12.2 3.5 17.2 12.4
32 PI 3.8 3.9 3.9 4.0 4.0 4.1
TC 10.6 12.4 13.8 14.4 15.8 16.4
SHC 8.8 10.0 10.8 11.2 11.8 12.0
35 PI 4.4 4.5 4.6 4.7 4.7 4.8
TC SHC 10.3 8.6 12.0 9.7 13.4 10.6 14.0 10.9 15.4 11.5 15.9 11.7
40 PI 4.7 4.7 4.8 4.9 5.0 5.0
TC 9.9 11.5 12.9 13.5 14.8 15.4
SHC 8.4 9.5 10.3 10.6 11.2 11.3
43 PI 5.0 5.0 5.1 5.2 5.3 5.4
TC SHC 9.7 8.3 11.3 9.4 12.6 10.1 13.2 10.4 14.5 11.0 15.0 11.1
PI 5.1 5.2 5.3 5.4 5.5 5.5
Model No.: LT-H368DLE1, LT-C368DLE1 Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20 22 25 27 30 32
Outdoor Air Temperature : °CDB 20
25
TC SHC PI TC SHC 8.5 6.9 2.62 8.3 6.8 9.9 7.8 2.66 9.7 7.7 11.1 8.5 2.70 10.9 8.4 11.6 8.8 2.75 11.4 8.7 12.7 9.3 2.8 12.5 9.2 13.2 9.5 2.8 12.9 9.3
32 PI 3.1 3.2 3.2 3.3 3.3 3.3
TC SHC 7.9 6.6 9.3 7.5 10.3 8.1 10.8 8.4 11.9 8.9 12.3 9.0
35 PI 3.6 3.7 3.7 3.8 3.8 3.9
TC SHC 7.7 6.5 9.0 7.3 10.0 7.9 10.5 8.2 11.5 8.7 12.0 8.8
40 PI 3.8 3.9 3.9 4.0 4.1 4.1
TC SHC 7.4 6.3 8.7 7.2 9.7 7.7 10.1 8.0 11.1 8.4 11.5 8.5
43 PI 4.1 4.1 4.2 4.3 4.3 4.4
TC SHC 7.2 6.3 8.5 7.1 9.4 7.6 9.9 7.9 10.8 8.3 11.2 8.4
PI 2.9 3.0 3.0 3.1 3.1 3.2
TC 5.7 6.6 7.4 7.7 8.5 8.8
PI 4.2 4.3 4.3 4.4 4.5 4.5
Model No.: LT-H286HLE1, LT-C286HLE1 Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20 22 25 27 30 32
Outdoor Air Temperature : °CDB 20 TC SHC PI 6.7 5.5 1.90 7.8 6.2 1.93 8.7 6.7 1.96 9.1 7.0 1.99 9.9 7.4 2.0 10.3 7.5 2.0
25 TC SHC 6.5 5.4 7.6 6.1 8.5 6.7 8.9 6.9 9.7 7.3 10.1 7.4
32 PI 2.3 2.3 2.3 2.4 2.4 2.4
TC 6.2 7.2 8.1 8.5 9.3 9.6
SHC 5.3 6.0 6.5 6.7 7.1 7.2
35 PI 2.6 2.7 2.7 2.8 2.8 2.8
TC 6.0 7.0 7.8 8.2 9.0 9.3
SHC 5.2 5.8 6.3 6.5 6.9 7.0
40 PI 2.8 2.8 2.9 2.9 2.9 3.0
TC 5.8 6.8 7.5 7.9 8.7 9.0
SHC 5.0 5.7 6.2 6.4 6.7 6.8
43 SHC 5.0 5.6 6.1 6.2 6.6 6.7
PI 3.0 3.1 3.1 3.2 3.2 3.3
Notes: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. TC : Total Capacity (kW) PI : Power Input (kW) SHC : Sensible Heat Capacity (kW)
68
Ceiling Cassette
Outdoor unit
5CST2-06A
Capacity tables
Model No.: LT-H246HLE1, LT-C246HLE1 Outdoor Air Temperature : °CDB
Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20 22 25 27 30 32
20 TC 5.7 6.6 7.4 7.7 8.5 8.8
SHC 4.1 4.7 5.1 5.2 5.6 5.6
25 PI 1.75 1.78 1.80 1.83 1.9 1.9
TC 5.6 6.5 7.2 7.6 8.3 8.6
SHC 4.1 4.6 5.0 5.2 5.5 5.6
32 PI 2.1 2.1 2.1 2.2 2.2 2.2
TC 5.3 6.2 6.9 7.2 7.9 8.2
SHC 4.0 4.5 4.9 5.0 5.3 5.4
35 PI 2.4 2.5 2.5 2.5 2.6 2.6
TC 5.1 6.0 6.7 7.0 7.7 8.0
SHC 3.9 4.4 4.7 4.9 5.2 5.2
40 PI 2.5 2.6 2.6 2.7 2.7 2.7
TC 4.9 5.8 6.4 6.7 7.4 7.7
SHC 3.8 4.3 4.6 4.8 5.0 5.1
43 PI 2.7 2.8 2.8 2.8 2.9 2.9
TC 4.8 5.6 6.3 6.6 7.2 7.5
SHC 3.7 4.2 4.6 4.7 4.9 5.0
PI 2.8 2.8 2.9 2.9 3.0 3.0
Model No.: LT-C186ELE1, LT-H186ELE1, LT-C186ELF1, LT-H186ELF1 Outdoor Air Temperature : °CDB
Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20 22 25 27 30 32
20 TC 4.3 5.0 5.6 5.8 6.4 6.6
SHC 3.3 3.7 4.0 4.2 4.4 4.5
25 PI 1.28 1.30 1.32 1.34 1.4 1.4
TC 4.2 4.9 5.5 5.7 6.3 6.5
SHC 3.2 3.7 4.0 4.1 4.4 4.4
32 PI 1.5 1.5 1.6 1.6 1.6 1.6
TC 4.0 4.7 5.2 5.4 6.0 6.2
SHC 3.1 3.6 3.9 4.0 4.2 4.3
35 PI 1.8 1.8 1.8 1.9 1.9 1.9
TC 3.9 4.5 5.0 5.3 5.8 6.0
SHC 3.1 3.5 3.8 3.9 4.1 4.2
40 PI 1.9 1.9 1.9 2.0 2.0 2.0
TC 3.7 4.3 4.9 5.1 5.6 5.8
SHC 3.0 3.4 3.7 3.8 4.0 4.0
43 PI 2.0 2.0 2.0 2.1 2.1 2.1
TC 3.6 4.2 4.7 5.0 5.4 5.7
SHC 3.0 3.3 3.6 3.7 3.9 4.0
PI 2.0 2.1 2.1 2.1 2.2 2.2
Notes: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. TC : Total Capacity (kW) PI : Power Input (kW) SHC : Sensible Heat Capacity (kW)
Outdoor unit
Ceiling Cassette
69
Capacity tables
5CST2-06A
[Heating capacity] Model No.: LT-H548DLE1/2 Indoor Air Temperature ˚CDB 16 18 20 22 24
-10 TC 11.7 11.3 11.0 10.6 10.2
-5 PI 4.8 5.0 5.1 5.3 5.5
TC 13.8 13.3 12.9 12.5 12.0
PI 5.7 5.9 6.1 6.3 6.5
Outdoor Air Temperature : °CWB 2 4 TC PI TC PI 16.7 5.9 17.5 6.1 16.2 6.1 17.0 6.3 15.7 6.3 16.5 6.5 15.1 6.5 15.9 6.7 14.6 6.7 15.3 6.9
PI 3.7 3.9 4.0 4.1 4.2
Outdoor Air Temperature : °CWB 2 4 TC PI TC PI 14.7 3.8 15.4 4.0 14.2 4.0 14.9 4.1 13.8 4.1 14.5 4.2 13.3 4.2 13.9 4.4 12.8 4.4 13.5 4.5
PI 3.5 3.6 3.7 3.8 3.9
Outdoor Air Temperature : °CWB 2 4 TC PI TC PI 10.8 3.6 11.3 3.7 10.5 3.7 11.0 3.8 10.2 3.8 10.7 3.9 9.8 3.9 10.3 4.1 9.5 4.1 9.9 4.2
PI 2.5 2.6 2.7 2.8 2.9
Outdoor Air Temperature : °CWB 2 4 TC PI TC PI 8.5 2.6 8.9 2.7 8.2 2.7 8.6 2.8 8.0 2.8 8.4 2.9 7.7 2.9 8.1 2.9 7.4 2.9 7.8 3.0
0 PI 5.3 5.4 5.6 5.8 6.0
TC 15.9 15.4 14.9 14.4 13.9
6 TC 18.5 17.9 17.3 16.8 16.2
10 PI 6.2 6.4 6.6 6.8 7.0
TC 20.0 19.4 18.8 18.1 17.5
15 PI 6.5 6.7 7.0 7.2 7.4
TC 22.1 21.4 20.8 20.0 19.3
PI 7.0 7.2 7.4 7.7 7.9
Model No.: LT-H488DLE1 Indoor Air Temperature ˚CDB 16 18 20 22 24
-10 TC 10.3 9.9 9.6 9.3 9.0
-5 PI 3.1 3.2 3.3 3.5 3.6
TC 12.1 11.7 11.4 10.9 10.6
0 PI 3.4 3.5 3.7 3.8 3.9
TC 14.0 13.5 13.1 12.7 12.2
6 TC 16.3 15.8 15.2 14.7 14.2
10 PI 4.0 4.2 4.3 4.4 4.6
TC 17.6 17.0 16.5 15.9 15.4
15 PI 4.2 4.4 4.5 4.7 4.8
TC 19.4 18.8 18.3 17.6 17.0
PI 4.5 4.7 4.9 5.0 5.2
Model No.: LT-H368DLE1 Indoor Air Temperature ˚CDB 16 18 20 22 24
-10 TC 7.6 7.3 7.1 6.8 6.6
-5 PI 2.9 3.0 3.1 3.2 3.3
TC 8.9 8.6 8.4 8.1 7.8
0 PI 3.2 3.3 3.4 3.5 3.6
TC 10.3 10.0 9.7 9.3 9.0
6 TC 12.0 11.6 11.2 10.9 10.5
10 PI 3.7 3.9 4.0 4.1 4.3
TC 13.0 12.6 12.2 11.7 11.3
15 PI 3.9 4.1 4.2 4.3 4.5
TC 14.3 13.9 13.5 13.0 12.5
PI 4.2 4.4 4.5 4.7 4.8
Model No.: LT-H286HLE1 Indoor Air Temperature ˚CDB 16 18 20 22 24
-10 TC 5.9 5.8 5.6 5.4 5.2
-5 PI 2.1 2.2 2.3 2.3 2.4
TC 7.0 6.8 6.6 6.3 6.1
0 PI 2.3 2.4 2.5 2.5 2.6
TC 8.1 7.8 7.6 7.3 7.1
6 TC 9.4 9.1 8.8 8.5 8.2
10 PI 2.7 2.8 2.9 3.0 3.1
TC 10.2 9.9 9.6 9.2 8.9
15 PI 2.9 3.0 3.1 3.2 3.2
TC 11.3 10.9 10.6 10.2 9.8
PI 3.1 3.2 3.3 3.4 3.5
Notes: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. TC PI
70
: Total Capacity (kW) : Power Input (kW)
Ceiling Cassette
Outdoor unit
5CST2-06A
Capacity tables
Model No.: LT-H246HLE1 Indoor Air Temperature ˚CDB 16 18 20 22 24
-10 TC 4.7 4.6 4.4 4.3 4.1
-5 PI 1.8 1.8 1.9 2.0 2.0
TC 5.6 5.4 5.2 5.0 4.9
PI 2.1 2.2 2.3 2.3 2.4
Outdoor Air Temperature : °CWB 2 4 TC PI TC PI 6.8 2.2 7.1 2.3 6.6 2.3 6.9 2.3 6.4 2.3 6.7 2.4 6.1 2.4 6.4 2.5 5.9 2.5 6.2 2.6
TC 7.5 7.3 7.0 6.8 6.6
PI 1.7 1.8 1.8 1.9 1.9
Outdoor Air Temperature : °CWB 2 4 TC PI TC PI 5.4 1.7 5.6 1.8 5.2 1.8 5.4 1.9 5.0 1.9 5.3 1.9 4.8 1.9 5.1 2.0 4.7 2.0 4.9 2.0
TC 5.9 5.7 5.5 5.4 5.2
0 PI 2.0 2.0 2.1 2.2 2.2
TC 6.4 6.2 6.1 5.8 5.6
6
10 PI 2.3 2.4 2.5 2.5 2.6
TC 8.1 7.9 7.6 7.3 7.1
PI 1.8 1.9 2.0 2.0 2.1
TC 6.4 6.2 6.0 5.8 5.6
15 PI 2.4 2.5 2.6 2.7 2.7
TC 9.0 8.7 8.4 8.1 7.8
PI 1.9 2.0 2.1 2.1 2.2
TC 7.1 6.9 6.7 6.4 6.2
PI 2.6 2.7 2.8 2.9 2.9
Model No.: LT-H186ELE1, LT-H186ELF1 Indoor Air Temperature ˚CDB 16 18 20 22 24
-10 TC 3.7 3.6 3.5 3.4 3.3
-5 PI 1.4 1.5 1.5 1.6 1.6
TC 4.4 4.3 4.1 4.0 3.9
0 PI 1.6 1.6 1.7 1.7 1.8
TC 5.1 4.9 4.8 4.6 4.5
6
10
15 PI 2.1 2.1 2.2 2.3 2.3
Notes: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. TC PI
: Total Capacity (kW) : Power Input (kW)
Outdoor unit
Ceiling Cassette
71
Operation range
5CST2-06A
2.1.8 Operation range Model No.: LT-H548DLE1, LT-C548DLE1 Cooling
Heating(Heat Pump Only)
Continuous operation
21
24
-7
Warning up period
Outdoor temperature (°C DB)
Outdoor temperature (°C DB)
48
Continuous operation
Operative
-10
-5 C
18
16
32
Indoor temperature (°C DB)
30
Indoor temperature (°C DB)
Operative: Intermittent operation due to the operational conditions(indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrese.
Model No.: LT-H548DLE2, LT-C548DLE2, LT-H488DLE1, LT-C488DLE1, LT-H368DLE1, LT-C368DLE1, LT-H286HLE1, LT-C286HLE1, LT-H246HLE1, LT-C246HLE1, LT-(C)H186ELE1, LT-C(H)186ELF1 Cooling
Heating(Heat Pump Only)
Continuous operation
21
24
-7
Warning up period
Outdoor temperature (°C DB)
Outdoor temperature (°C DB)
54
Continuous operation
Operative
-10
-5 C
18
32
Indoor temperature (°C DB)
16
30
Indoor temperature (°C DB)
Operative: Intermittent operation due to the operational conditions(indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrese.
72
Ceiling Cassette
Outdoor unit
5CST2-06A
Capacity coefficient factor
2.1.9 Capacity coefficient factor Models: LT-H548DLE1, LT-H548DLE2, LT-C548DLE1, LT-C548DLE2, LT-H488DLE1, LT-C488DLE1 Cooling Main piping length(m)
Model
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
54k
100.0
98.5
96.0
93.4
90.5
88.1
48k
100.0
99.4
96.8
94.2
91.6
89.0
Main piping length(m)
Model
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
54k
100.0
99.3
97.8
96.1
94.7
93.2
48k
100.0
99.9
99.6
99.2
98.8
98.5
Heating(Heat Pump Only)
100
Capacity(%)
Cooling
90
48k 54k
80
70 7.5
10
20
30
40
50
Total Pipe Length(m) 100 Heating (Heat Pump Only)
48k
Capacity(%)
54k 90
80
70 7.5
10
20
30
40
50
Total Pipe Length(m) Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model. Outdoor unit
Ceiling Cassette
73
Capacity coefficient factor
5CST2-06A
Models: LT-H368DLE1, LT-C368DLE1 Cooling Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
98.9
94.4
89.9
85.5
81.0
Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.8
99.1
98.4
97.7
97.0
Heating(Heat Pump Only)
100
Capacity(%)
Cooling
90
36k
80
70 7.5
10
20
30
40
50
Total Pipe Length(m)
Capacity(%)
Heating 100 (Heat Pump Only)
36k
90
80
70 7.5
10
20
30
40
50
Total Pipe Length(m) Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model. 74
Ceiling Cassette
Outdoor unit
5CST2-06A
Capacity coefficient factor
Models: LT-H286HLE1, LT-C286HLE1 Cooling Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.1
95.6
92.1
88.5
85.0
Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.4
97.0
94.7
92.3
89.9
Heating(Heat Pump Only)
100
Capacity(%)
Cooling
90 28k 80
70 7.5
10
20
30
40
50
Total Pipe Length(m)
Capacity(%)
Heating 100 (Heat Pump Only)
28k
90
80
70 7.5
10
20
30
40
50
Total Pipe Length(m) Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model. Outdoor unit
Ceiling Cassette
75
Capacity coefficient factor
5CST2-06A
Models: LT-H246HLE1, LT-C246HLE1 Cooling Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.2
96.1
93.1
90.0
86.9
Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.2
96.2
93.2
90.1
87.1
Heating(Heat Pump Only)
100
Capacity(%)
Cooling
90 24k
80
70 7.5
10
20
30
40
50
Total Pipe Length(m)
Capacity(%)
Heating 100 (Heat Pump Only)
90 24k
80
70 7.5
10
20
30
40
50
Total Pipe Length(m) Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model. 76
Ceiling Cassette
Outdoor unit
5CST2-06A
Capacity coefficient factor
Models: LT-C186ELE1, LT-H186ELE1, LT-C186ELF1, LT-H186ELF1 Cooling Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.2
95.9
92.6
89.3
86.0
Main piping length(m)
7.5
10
20
30
40
50
Rate of change in cooling capacity(%)
100.0
99.3
96.6
94.0
91.3
88.6
Heating(Heat Pump Only)
100
Capacity(%)
Cooling
90 18k 80
70 7.5
10
20
30
Total Pipe Length(m)
Capacity(%)
Heating 100 (Heat Pump Only)
90 18k
80
70 7.5
10
20
30
40
50
Total Pipe Length(m) Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model. Outdoor unit
Ceiling Cassette
77
Sound levels
5CST2-06A
2.1.10 Sound levels Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20ÂľPa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
1m Microphone
1m
Sound pressure level LT-H548DLE1 / LT-H548DLE2 LT-C548DLE1 / LT-C548DLE2
LT-H246HLE1 / LT-C246HLE1
LT-H488DLE1 / LT-C488DLE1
80
80
80
70
70
70
NC-65
60
NC-60
NC-60
NC-55
NC-55
50
50
30
30
NC-25
20 NC-20
Approximate Hearing Threshold
NC-15
500
1000
2000
4000
8000
63
LT-H368DLE1 / LT-C368DLE1
NC-25
20
Approximate Hearing Threshold
NC-20 NC-15
10 250
NC-30
NC-30
NC-25
125
NC-35
NC-35
NC-30
63
NC-40
NC-40
NC-35
10
NC-45
40
NC-40
Approximate Hearing Threshold
NC-50
NC-45
40
20
NC-55
NC-50
NC-45
30
NC-60
50
NC-50
40
NC-65
NC-65
60
60
125
250
500
1000
2000
4000
63
80
70
70
70
NC-60
NC-55
NC-55
NC-50
NC-50
NC-45
NC-45
NC-40
NC-40
NC-35
NC-35
Approximate Hearing Threshold
125
250
500
1000
2000
4000
8000
NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30
NC-25
20
Approximate Hearing Threshold
NC-20 NC-15
10
63
78
NC-25
20
NC-15
8000
NC-65
NC-30
NC-20
10
4000
30
30 NC-30
NC-25
2000
40
40
Approximate Hearing Threshold
1000
50
50
20
500
60
60 NC-60
30
250
NC-65
NC-65
40
125
LT-H186ELE1 / LT-H186ELF1 LT-C186ELE1 / LT-C186ELF1
LT-H286HLE1 / LT-C286HLE1 80
50
NC-15
10
8000
80
60
NC-20
NC-20 NC-15
10 63
125
250
500
1000
2000
Ceiling Cassette
4000
8000
63
125
250
500
1000
2000
4000
8000
Outdoor unit
Part 3 Design and installation 1. General installation guidelines ..........................................................80 1.1 Installation process & guidelines ......................................................................80 1.2 Checking the drawing ........................................................................................81 1.3 Application guidelines........................................................................................82
2. Guideline for each installation process ............................................85 2.1 Sleeve and inserting work..................................................................................85 2.2 Refrigerant piping work......................................................................................88 2.3 Drain piping work ..............................................................................................97 2.4 Insulation work.................................................................................................103 2.5 Electrical work .................................................................................................107 2.6 Air tight test......................................................................................................109 2.7 Vacuum drying.................................................................................................102 2.8 Trial test run operation .....................................................................................117
3. Installation of indoor unit ................................................................119 3.1 Safety precautions ...........................................................................................119 3.2 Ceiling cassette 4-way.....................................................................................124
4. Installation of outdoor Unit .............................................................132 4.1 Safety precautions ...........................................................................................132 4.2 Introduction......................................................................................................138 4.3 Foundation.......................................................................................................139 4.4 Settlement of the outdoor unit .........................................................................140 4.5 Selection of the best location...........................................................................141 4.6 Clearance space..............................................................................................142 4.7 Outdoor unit piping ..........................................................................................145 4.8 Outdoor unit installation requirements .............................................................146 4.9 Outdoor unit cabin ...........................................................................................149
Design and installation
Ceiling Cassette
79
Installation process & Guidelines
5CST2-06A
1. General installation guidelines 1.1 Installation process & Guidelines Striking a balance between system installation & General construction work. Construction work
Air conditioning work Setting sleeve and insert work details
Preparation of contract drawing
Fitting of steel sleeves
Moulding box and reinforcement work
Sleeve and insert work
Removal of moulding boxes
Installation of indoor unit Refrigerant piping work Drain piping work Duct work Insulation work Electrical work
Ceiling preparations Building rooftop Outdoor unit foundation work Installation of outdoor unit Air tight test Vacuum drying Additional charge of refrigerant Fit decoration panels Cleaning inside and outside
Test run T.A.B and final report Transfer to customer with explanation
Energization
1. The division of the work should be thoroughly clarified. 2. keep a constant check on the progress of the construction work to avoid deviations from the air conditioning work schedule. 80
Ceiling Cassette
General installation guidelines
5CST2-06A
Checking the drawing
1.2 Checking the drawing Installation procedure
Remarks
Determination of work scope
Check and confirm required load calculation, model selection, drawings etc.
Preparation of contract drawings
Make relationships between outdoor ,indoor controller and option connection clear. (prepare control circuit diagram)
Sleeve and insert works
Determine sleeve position, size and counts as required
Installation of indoor units
Check model name to make sure the fitting is made correctly
Refrigerant piping works
Special attention to dryness , cleanliness and tightness
Drain pipe works
Make sure that the drain pipe diameter is big enough and adjust it to downward gradient Make sure airflow is sufficient
Duct works
Make sure no gap is left where the insulating materials are joined
Insulation works Electrical work
Multiple core cable must not be used (suitable cable should be selected) The foundation must be vibration proof and levelled Avoid airflow short circuit and ensure sufficient space is allowed for servicing
Outdoor unit foundation works Installation of outdoor units
For 24 hours at 3.8MPa(R410a) or 2.8MPa(R22) there must be no drop in pressure
Air tight test Vacuum drying
Less than 5 Torr (At least more than 1hr) Charge the refrigerant accurately by using a charging cylinder
Additional charge of refrigerant
Make sure there are no gaps left between facing materials used on the ceiling
Fit decoration panels Test run
Follow the testing operation check sheet Explain to customer or operator the manual etc
Transfer to customer with explanation
General installation guidelines
Ceiling Cassette
81
Application guidelines
5CST2-06A
1.3 Application guidelines
1.3.1 Restaurant - Load characteristics Extremely variable loads with high peaks, in many cases, occurring twice daily High sensible and latent heat gains because of gas, steam, electric appliances, people, and food (sensible and latent loads are not always coincident) Large quantities of makeup air normally required. Unbalanced conditions in restaurant areas adjacent to kitchens which, although not part of the conditioned space still require special attention. Heavy infiltration of outside air through doors during rush hour. Smoking versus nonsmoking areas. - Design concepts High concentrations of food, body, and tobacco-smoke odors require adequate ventilation with exhaust facilities. Step control of refrigeration plants gives satisfactory and economical operation under reduced loads. Mechanical humidification is typically not provided because of high internal latent loads.
1.3.2 Office buildings - Load characteristics Peripheral zone have variable loads because of changing sun position and weather. - Design concepts Office buildings have allowed the use of almost every available air conditioning system. Built in system flexibility is essential for office building design. Stores, banks, restaurants, and entertainment facilities should have their own air distribution systems. - Special consideration Elevator, refrigeration, plumbing, mechanical equipment rooms, electrical switchgear, and telephone closets may require air conditioning units for spot cooling. Tall buildings in cold climates experience severe stack effect. - Revolving doors or vestibules, pressurized lobbies or lower floors - Automatic dampers on elevator shaft vents, tight construction of the exterior skin - Tight closure and seals on all dampers opening to the exterior
82
Ceiling Cassette
General installation guidelines
5CST2-06A
Application guidelines
1.3.3 Bowling centers - Load characteristics Bowling center generally have little fenestration, solar load may not be important. It is necessary to compare the day load and its high outside solar load and off peak people load with the evening peak people load and zero solar load. The proper heat gain should be applied for each person to avoid too large a design heat load - Design concepts As other building types all air systems are generally the most suitable for bowling alley areas. Temp. may be graded down to the pin area – Unit heaters are often used at this location. Bowling areas must be well shielded from entrances so that no cold drafts are created in these areas - Maintaining a positive pressure in the space when outside air pressurization is taken into consideration. The return and exhaust air systems should have a large number of small registers uniformly located at high points, or pockets, to draw off the hot, smoky, and foul air. It may be desirable to use all outside air to cool during intermediate seasons. - Special consideration A large number of people concentrated in a relatively small area of a very large room. A major portion of the floor area is unoccupied. Heavy smoking, high physical activity, and high latent heat load. Greatest use from about 6:00 P.M. to midnight
1.3.4 Comunication centers - Load characteristics Human occupancy is limited in telephone terminal rooms, so the load is primarily equipment heat load. TV studio have very high lighting capacities, and the load may fluctuate in intensity over short periods. The A/C system must be capable of handling wide load variations quickly, accurately, and efficiently. Completely shielded from external noise and thermal environments. - Design concepts TV studio – Each rooms should have its own air distribution system separate from studio system. Simultaneous heating and cooling cannot occur unless heating is as achieved solely by heat recovery Studio should have its own refrigeration system in case of emergency. Required a remote location so that machine noise is isolated from the studio. - Special consideration On camera studio – Duct work must be planned carefully to avoid interference with proper studio operation. Control room – The large number of necessary air changes and the low sound level must be maintained Noise control – Air outlets or returns should be located away from areas where microphones are used Air distribution – No rough edges, poor turns, or improperly installed damper to cause turbulence Piping distribution – All piping in the studio should be supported by suitable vibration isolation hangers Mechanical equipment room – Located far from the studio as possible. (noise) Office and dressing room – Such rooms are treated as separate zones, with their own controls. Air return – The largest portion of studio air should be returned over the banks of lights.
General installation guidelines
Ceiling Cassette
83
Application guidelines
5CST2-06A
1.3.5 Hotel - Load characteristics The hours for which each public area is used varies widely. In many cases the load is due to internal sources from people, lights, and equipment. The main lobby normally is operational 24 hours per day. Areas like restaurants, meeting rooms and retail areas have intermittent use, so the load changes frequently. HVAC systems that respond effectively and economically must be selected for these areas. - Design concepts Year round availability of heating and cooling Independent unit for each main public area Economical and satisfactory operation at part-load and low-load conditions Coordination with adjacent back of the house (BOTH) areas to ensure proper air pressurization - Special consideration Unitary refrigerant system – PAC, Air to air pump Selection of particular system should be based on – first cost, economical operation, maintenance
1.3.6 Warehouses - Load characteristics Internal loads from lighting, people, and miscellaneous sources are generally low. Most load is thermal transmission and infiltration. - Design concepts Most warehouses are only heated and ventilated. (located near heat entrances and work areas) Necessary to keep the temperature above 4°C to protect sprinkler piping or stored materials from freezing. If the stored product requires defined inside conditions, and a/c system must be added. - Special consideration Forklifts and trucks powered by gasoline, propane, and other fuels are often used inside warehouses. Proper ventilation is necessary to alleviate the buildup of CO and other noxious fumes. Proper ventilation of battery – charging rooms for electrically powered forklifts and trucks is also required.
1.3.7 Convention and exhibition centers - Load characteristics The main exhibition room is subject to a variety of loads, depending on the type of activity in progress. Alternative loads that are very different in character may be encountered. (Multi speed fans may provide a better balance of load during these high latent, low sensible periods of use.) - System application The main exhibition hall is normally handled by one or mail all air system. Smaller meeting rooms are best conditioned either with individual room air handlers, or with variable volume central systems, because these rooms have high individual peak loads but are not used frequently. Offices and restaurants often operate for many more hours than the meeting areas or exhibition areas and should be served separately.
84
Ceiling Cassette
General installation guidelines
5CST2-06A
Sleeve and inserting work
2. Guideline for each installation process 2.1 Sleeve and insert work 2.1.1 Positioning of the pipe holes 1. The through holes for the drain piping should be positioned such that pipes have a downward gradient (the gradient must be at least 1/100.The thickness of the insulating materials must also be taken into consideration.) 2. The diameter of the through holes for the refrigerant piping should include an allowance for the thickness of the heat insulation materials. 3. Attention should be paid to the construction of the beam themselves since there are parts of the beam which cannot be used to accommodate through holes at times.
2.1.2 Selection of sleeve 1. Sleeve work should be performed to make space for passing pipe and wire through the wall or ground under construction. Sleeve Power cable Gas pipe Liquid pipe Insulation Insulation Transmission cable
For example if gas pipe and liquid pipe is 12.7mm , 6.35mm the sleeve diameter is minimum 79.05mm . Gas pipe diameter Liquid pipe diameter Insulation thickness(gas pipe) Insulation thickness(liquid pipe) 20mm surplus Total sleeve diameter
12.7mm 6.35mm 10mm x 2 10mm x 2 20mm 79.05mm
* Assumption : Gas pipe insulation thickness and liquid pipe insulation thickness is 10mm and 10mm respectively NOTE
Use of shielded transmission cable is recommended to avoid the problem of electrical noise.
Guidelines for each installation process
Ceiling Cassette
85
Sleeve and inserting work
5CST2-06A
2.1.3 Sleeve type Sleeve Insulation Pipe
NOTE
Sleeve type should be considered as per local & laws (rules & regulations). CAUTION
1. In high voltage generation places, water-proof flexible conduit should be used. (in substation room, in elevator room) 2. Conduit should be chosen in accordance with electrical installation regulation.
NOTE
Cable conduit should be considered under the local laws (rules & regulations).
2.1.4 Insert work and support work An insert is a metal tool which is inserted into a floor or beam before the concrete is set such that fittings such as duct , pipes or suspension bolts for hanging units can be fitted into the place later. The positioning of the inserts must be decided early. 1) Insert work
Embedding depth h
Example : Through holes in a reinforced concrete beam
Polyblock Nail securing molding box
Molding box
86
Suspension bolt
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Sleeve and inserting work
2) Support work. Insulated U-bolt type supporting
Insulated O-ring band type supporting Bolt
Foam resin Bolt 1.5t plate PVC PVC
Saddle supporting Supporting interval 1.5~2.0m
CAUTION
During saddle supporting work, insulation should not be pressed by saddle as this can lead to tearing of insulation and thus falling of condensed water during product operation. a) Supporting with insulated pipe U-bolt supporting
0-ring band supporting
To prevent Insulation from pressing, and lagging, cover can be used.
O-ring band
Sheathing pipe
lags Sheathing pipe
B) Down stopper supporting One point supporter (200kg) O-ring band Welding Plate nut
Down stopper
Welding Insulated Supporting band
Insulated Supporting band
Hexagonal nut Refrigerant pipe
Guidelines for each installation process
Ceiling Cassette
87
Refrigerant piping work
5CST2-06A
2.2 Refrigerant piping work 2.2.1 Principles of refrigerant piping The “ principles of refrigerant piping “ must be strictly observed. Cause of problem
Dry
Clean
Action to avoid problem
-Rainwater, work water, etc gets into pipes from outside -Moisture generated inside pipe due to condensation
Flushing
-Formation of oxides inside pipes during soldering
Replace Nitrogen
-Dirt,dust or other extraneous material gets into pipes from outside
Pipe covering
Flushing
Vacuum drying
Pipe covering
Pipe covering
Use the proper materials -Leak from soldered area Air tight
Adhere strictly to standard soldering work practice.
-Leak from flared area -Leak from flange area
Adhere strictly to standard flaring work practice. Adhere strictly to standard flaring connection work practice.
• The end of all copper pipes should be capped to protect them from dust or water particles while safe keeping
The 3 princples of refrigerant piping work Dry
Clean
Make sure there is no moisture inside the pipes
Air tight
Make sure there is no dirt inside the pipes
Make sure the refrigerant does not leak out.
Leak Moisture
88
Dirt
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Refrigerant piping work
2.2.2 Flaring work Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable. Copper tube
Use the piping kit accessory or the pipes purchased locally.
Slanted Uneven Rough
90°
Measure the distance between the indoor and the outdoor unit. Cut the pipes a little longer than measured distance. Pipe
Cut the cable 1.5m longer than the pipe length.
Reamer
2) Burrs removal Point down
Completely remove all burrs from the cut cross section of pipe/tube. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping of burrs into the tubing.
Flare nut
3) Putting nut on Copper tube
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.(not possible to put them on after flaring work)
4) Flaring work Carry out flaring work using flaring tool as shown below.
Handle
Firmly hold copper pipe in a die in the dimension shown in the table below. Outer diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4
Bar
Bar
"A"
Yoke Cone
A mm 1.1~1.3 1.5~1.7 1.6~1.8 1.6~1.8 1.9~2.1
Copper pipe Clamp handle
Red arrow mark
Smooth all round Inside is shining without scratches
5) Check after flaring
= Improper flaring =
Compare the flared work with figure on right side. If flare is found to be defective, cut off the flared section and do flaring work again. Even length all round
Guidelines for each installation process
Ceiling Cassette
Inclined Surface Cracked Uneven damaged thickness
89
Refrigerant piping work
NOTE
5CST2-06A
Choice of material for refrigerant piping Copper pipe selection a. The wall thickness of the refrigerant piping should comply with relevant local and national regulation for R410A the design pressure is 3.8MPa.(38.7kgf/cm2) b. If not, we recommend use of phosphorus deoxidized copper type c. Generally used copper pipe specifications as follows; Thickness Size(ø)mm
R22
R410A
6.35
0.7
0.8
9.52
0.8
0.8
12.70
0.8
0.8
15.88
1.0
1.0
19.05
1.0
1.0
* Never use the pipe which is mixed scrap or a pipe used somewhere else The method how to distinguish the pipe mixed scarp : check the oxidization evidence after leaving the pipe for 24hour. CAUTION
Flare connection and procedure 1. Stiffened pipe must always be annealed at least once prior to the flaring work. 2. A pipe cutter must be used to cut the pipe. (A large pipe cutter must be used where the pipe has a large diameter. When cutting a pipe which is too big for the pipe cutter a metal saw may be used but care must be taken to ensure that the debris from sawing does not get into the pipe.)
A
3. Set the flaring tool to make sure the flare size remains within the prescribed limits. 4. Coat the inner and outer surface of the flare with refrigerator oil (Ester or ether oil). (this ensures that the flare nut passes smoothly, preventing the pipe Oil from twisting.) Do not use SUNISO-4GS oil.
Oil
D
External diameter of pipe D (in) (mm) 1/4 6.35 3/8 9.52 1/2 12.7 5/8 15.88 3/4 19.05
Pipe widening dimension A 8.6~9.0 12.6~13.0 15.8~16.2 19.0~19.4 22.9~23.3
CAUTION
1. Burrs should be carefully removed. 2. 2 spanners should be used to grip the pipe. 3. The flare nut must be inserted before starting the flaring operation. 4. The appropriate amount of torque should be used to tighten the flare nut. 5. Check that there is no superficial damage to the surface of the flare.
90
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Refrigerant piping work
NOTE
Flange connection and procedure 1) Cut the pipe using a pipe cutter.
7) Apply refrigerant oil on the inside and outside of the flared section. (Do not apply SUNISO oil) (Be careful to keep dust away)
2) The cut edge has burrs. (the amount of burrs becomes larger when pipe wall is thick) 8) Tighten the flare nut. (Use a torque wrench to apply the proper tightening force)
3) Remove the burrs using a reamer (Be careful not to let particles enter the pipe. Point the pipe end downward during cutting)
4) Clean the inside of the pipe (use a thin stick with a cloth wrapped around it)
9) • Check for gas leaks. (Check at the threaded section of the flare nut for gas leak) • Spay –type gas leak detecting products are available on the market. • Soap water may be used to check for leaks , but use only neutral soap to prevent corrosion of the flare nut. • Be sure to wipe the nut area clean after the gas leak check.
5) Before flaring , clean the corn section of the flaring tool.
Corn section
6) Flare the pipe. Rotate the flaring tool 3 or 4 turns after a clicking sound is produced. this results in a clean flared surface
Guidelines for each installation process
Ceiling Cassette
91
Refrigerant piping work
5CST2-06A
2.2.3 Pipe connection flaring NOTE
CAUTION
1. After installation completion make sure to open the valve. operating the unit with the valve shut off will destroy the compressor (Refer to the additional refrigerant charge detail information) 2. Use R22 to add refrigerant. All field piping must be installed by a licensed refrigeration technician 3. Must comply with local and national standard regulations.
Improper piping and flaring can lead to leakage of refrigerant
NOTE
For flaring work of the piping, follow the instructions in the installation manual to each unit.
1) Connecting the piping to the indoor unit and drain hose to drain pipe Align the center of the piping and sufficiently tighten the flare nut by hand. Indoor unit tubing
Tighten the flare nut with a wrench. Wrap the insulation material around the connecting portion. Outside diameter(Ă˜) mm inch 6.35 1/4 9.52 3/8 12.7 1/2 15.88 5/8 19.05 3/4
Torque kg.f.m 1.80~2.50 3.40~4.20 5.50~6.60 6.30~8.20 9.90~12.1
Flare nut
Pipes
Open-end wrench (fixed) Flare nut Wrench
2) Wrap the insulation material around the connecting portion. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. Wrap the area which accommodates the rear piping housing section with vinyl tape.
Connection pipe
Indoor unit tubing
Wrap with vinyl tape Vinyl tape (wide) Connecting cable Pipe
When the piping is passed through a tray, duct work or a sleeve the insulation wrapping on the pipe is not required.
3) Close up a socket out of use with a brass cap. Align the center of the piping and sufficiently tighten the brass cap by hand.
Indoor unit pipe
Connection pipe
Vinyl tape(narrow)
CAUTION
Never use the plastic cap during closing.
Tighten the brass cap with a wrench. Wrap the area contacted with insulation. CAUTION
Over tightening of the flare nuts in the pipes may cause nuts to crack or the refrigerant to leak.
92
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Refrigerant piping work
2.2.4 Brazing work CAUTION
Brazing of refrigerant piping : The following precaution should be taken. 1. Do not use flux when brazing copper to copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)
If brazing work is carried out without passing nitrogen gas through the pipes then it allows the formation of oxidation bubbles on the inside surface of the pipes. These oxidation bubbles are then carried along inside the pipes to cause damage to various members of the system such as valve or compressors and the system ceases to function properly. In order to avoid this problem nitrogen is passed through the pipe while the soldering work is being carried out. This operation work is known as nitrogen replacement.(Air is replaced by nitrogen) This is standard work during all brazing works.
CAUTION
1) Niorogen flushing method (During brazing)
Brazing section Copper pipe 1/4 Pressure regulator
Water enters
Packless valve Taping Nitrogen cylinder
High pressure hose
Outdoor unit
Packless valve
Pipe
Plaster enters
Make sure to keep the connecting piping dry (away from water) , clean (away from dust) , and air tight (avoid refrigerant leakage)
CAUTION Hose
Pressure regulator
Nitrogen cylinder
Pipe bending Annealed copper pipe with small diameter (Ă˜6.35 or Ă˜9.52) can be easily bent manually. In this case, secure large R (radius) for the bend section and gradually bend pipe. If annealed copper pipe is large in diameter (Ă˜15.88 or over), bend pipe with bender. Use bender appropriate for the pipe diameter.
CAUTION
Nitrogen brazing
(Direction of nitrogen gas.)
a. This procedure is designed to prevent formation of oxidation film by filling piping with inert gas. Note that excessive gas pressure will generate pinholes at brazed points. (Nitrogen gas: Supply pressure 0.05~0.1kg/cm2G) b. When supplying inert gas, be sure to open one end of piping.
Guidelines for each installation process
Ceiling Cassette
N2 Nitrogen brazing
93
Refrigerant piping work
5CST2-06A
Brazing work should be carried out either downwards or sideways. An upward direction should be avoided wherever possible(to prevent leakage).
over 10mm
over 10mm
N2
N2
(Expanding pipe brazing)
(Pipe brazing with socket)
N2
N2
(Flare part brazing)
(Butt-brazing)
Table 1: Correlation of nozzle tip and size of refrigeration piping Brazing filler diameter Ă˜
Nozzle tip No. # 200
# 225
# 250
# 315
# 400
# 450
# 500
1.6
2.4
3.2
6.35 9.52
Piping size
12.7 15.9 19.1 22.2 25.4 31.8 38.1 44.5
CAUTION
1. Generally expanding pipe brazing is performed with pan-coil type copper pipe, and socket blazing is performed with straight copper pipe. 2. Do not perform flare part brazing or butt-brazing. 3. Brazing should be performed on welding table. 4. No dust particles should enter the pipe while brazing. 5. Distance of copper pipe support spacing is within 1~2m 6. The copper pipe should not be secured directly by metal brackets.
94
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Refrigerant piping work
2.2.5 Refrigerant pipe flushing Flushing is a method of cleaning extraneous matter out of pipes using pressurized gas. NOTE
Refrigerant pipe flushing of 3 major effects 1. Removal of oxidation bubbles formed inside copper pipes when “nitrogen replacement is insufficient� during soldering work 2. Removal of extraneous material and moisture from pipes when covering has been insufficient 3. Checks connections in pipes linking outdoor and indoor units (Both liquid and gas pipes)
Set pressure regulator on nitrogen cylinder. Connect the charge hose from pressure regulator to service port on the liquid pipe side of the outdoor unit before its connection to B/D unit or indoor unit. Open the main valve on the nitrogen cylinder and set the pressure regulator to 0.5MPa.
Lo
Pressure regulator
Hi
Nitrogen
Primary side Lo
Ensure that nitrogen is flowing through the pipe properly.
For flushing block the end of the pipe with wood insulation block.
Hi
Secondary side 0.5 MPa
Nitrogen
When the pressure becomes great remove the block quickly. Do step 6 & 7 repeatedly till cleanness is ensured. Gas pressure of 0.5 MPa
Connect the charge hose from pressure regulator to service port on the gas pipe side of outdoor unit before its connection to B/D unit or indoor unit.
Wood
Insulation
Flow the steps 3, 4, 5, 6, 7. In case of BD unit system, before connecting to indoor units, each pipe should be flushed individually. Flow the steps 3, 4, 5, 6, 7.
CAUTION
Lo
Hi
Taping Nitrogen
After welding the pipe, nitrogen flushing is strongly recommended.
Guidelines for each installation process
Ceiling Cassette
95
Refrigerant piping work
5CST2-06A
2.2.6 Necessity of an oil trap Ceiling cassette has oil seperator or oil return function in their outdoor unit hence they don't need any oil trap within 24m elevation. But after 24m of vertical height, 1 oil trap is required. Outdoor unit
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping.
Gas pipe Oil trap Indoor unit Liquid pipe
Capacity is based on standard length and maximum allowance length is taken on the basis of reliability.
1) When outdoor unit is at higher elevation than the indoor units 1
Outdoor unit
2
2) When indoor units are at higher elevation than the outdoor unit
Outdoor unit Indoor unit
24m or more No oil trap
Oil trap
Less than 24m
Oil Indoor unit
Indoor unit Oil Outdoor unit
• Oil trap need not be installed
96
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Drain piping work
2.3 Drain piping work The purpose of drain piping is to prevent damage of product and ceiling materials by proper draining of dew condensate which is generated from the evaporator of indoor unit when the hot vapors come in contact with the evaporator. 1) Application Pipes for draining water generated from indoor unit on cooling operation
Specification for drain piping
Type
Single CAC
Cassette 4 way
Drain pipe diameter (External/ Internal)
Drain pump
32/25mm
Standard
Drain pump discharge head (mm)
Drain amount (at 10mm height) cm3/min (lpm)
700
400 (0.4)
[Reference Table] Drain amount per capacity kW
Air flow rate (CMH)
Drain amount (lpm)
2.04
8
0.128
2.33
8.5
0.137
2.91
10.5
0.169
4.36
11.5
0.185
Indoor temp. : 26째C DB
5.82
17
0.273
Indoor humidity RH : 85%
7.28
19
0.305
8.73
21
0.337
10.2
23
0.369
11.6
25
0.402
14.6
34
0.546
Guidelines for each installation process
Ceiling Cassette
Remark
Outlet temp. :14째C DB Outlet temp. RH: 50%
97
Drain piping work
5CST2-06A
2.3.1 Drain pipe slope and support • Slope gradient for drain should be 1/50~1/100mm and PVC pipes should be used. • Support hanger should be at 1~1.5m interval to prevent from loosening and dropping. • Drain pipe insulation : The inside temperature of drain pipe is about 10°C. When high temperature and humid air touches the surface of pipe, dew forms. To prevent that, drain pipe keeps warm using insulation with polyethylene 10mm thickness.
Indoor unit Gradient of at least 1 / 50 ~ 1 / 100
1) Application Refrigerant pipe length contracts and expands on heating and cooling repeatedly. So supporting work is needed not to hinder each copper pipe connection part. 2) Supporting distance for common drain pipe [Table]The interval of the supporting hanger for drainage pipe Pipe diameter (mm) Max. interval(m)
Ø20~40
Ø40~50
Ø65~125
Below 1.0
Below 1.2
Below 1.5
3) Anchor bolt supporting work Anchor bolt supporting work should be used for supporting a heavy indoor unit to ceiling. Clamp hanger supporting work is for hanging refrigerant pipe, drain pipe and cables. It can prevent vibrating noise from passing through pipe. We recommend set anchor bolt for supporting indoor unit and strong anchor bolt for supporting pipes and cables
98
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Drain piping work
2.3.2 Drain pipe trap (only for high static duct)
A ≥ 50mm B ≥ 4 x SP SP = External Pressure (mmAq)
B U-Trap
Ex) External Pressure = 10mmAq A ≥ 50mm B ≥ 40mm
A
<U-trap size calculations>
Indoor unit
Plug
- In case of duct high static pressure, the U trap maintains a positive pressure on the indoor side of the unit. 1) Models with drain pump 300mm or less
PVC elbow
PVC 1/50~1/100 slope
Max. 700
PVC Flexible hose Drain pump
[Unit : mm]
Common drain pipe
Polyethylene insulation 10t PVC drain pipe
2) Models without drain pump Metal clamp Flexible drain hose Thermal insulation (drain pipe area)
Drain pan
Guidelines for each installation process
Thermal insulation(bend area)
Ceiling Cassette
99
Drain piping work
5CST2-06A
2.3.3 Grouped drain pipes It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible. The diameter of ventilation pipe should be same or larger than drain pipe diameter. 45~60째
45~60째 angle connection against overflow
45~60째 Face the vent pipe mouth downward to keep foreign matter from penentrating the system
45~60째
slop e1 /50
Sharing horizontal pipe
~1 /1 0 0
700mm maxinmum Common drain pipe
Trap in the end
NOTE
1. Trap is required if the pipe is open towards sewage to prevent bad smell from coming to indoor. 2. Do not connect drain pipe with building common drain pipe in heavy snow area. It might block the pipe with ice and remaining collected water can get back to indoor unit. Provide seperate air conditioner drain pipe. Grouped drain piping standard - For drain pipe diameter selection, refer to the following table. - The drainpipe should be used for only air conditioners. If you share it for rainwater drain, you should be careful of a back flow, leakage, bad odor and so on. - Use separate drain pipe for polluted water or wasted water [Table] Drain pipe diameter selection standard Sum of the capacity of indoor units (Btu/h)
~80,000
Internal diameter (External)
25(32)
~200,000
~400,000
~600,000
32(40)
40(50)
50(60)
~1000,000 65(75)
NOTE
Select the diameter of the horizontal pipe bigger than vertical.
100
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Drain piping work
2.3.4 Caution for drain piping work 1) Notice on drain working Flexible tube should not be crooked sharply. The tube can be broken by continuous vibration for a long time.
Sharp crook Sh Sharp crook
CAUTION
Flexible tube should be connected with clamp concentrically. If not, water will leak from the connection.
<clamp connection>
No reverse slope for drain connection
Water flow
<Reverse slope>
Guidelines for each installation process
Ceiling Cassette
101
Drain piping work
5CST2-06A
2) Drain pipe insulation - Drain pipe should be insulated all connected joints and ends.
Insulation not required
Insulation required
Loose fitting wrong insulation
Fitting insulation
- Do not use the loose fitting insulation. 3) Drain water leakage test - Water leakage test should be performed 24 hours later after drain work finishing. - In the test, only water should be used. Other liquids are unacceptable.
102
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Insulation work
2.4 Insulation work 2.4.1 Insulation
1) Operational steps
1
EPDM length should be more than pipe length. Do not extend EPDM by force.
2
Put the pipe in EPDM insulation carefully so that the pipe will not get damaged with EPDM.
3
Apply bond on both side of cut surfaces of move sure to use the correct type of bond for EPDM cut surface attaching.
3
Bond both sides of the surface of EPDM and press them together for long lasting bonding.
3
Apply bond the both cutting sides of fitting cover.
4
Dry it until it becomes thick, sticky and does not get detached.
2) Bending vertical side of insulation
1
Use the original uncut insulation material.
2
Only in specialcase is the vertical cutting of the insulation allowed.
4
Dry it until it becomes thick and sticky.
3) 'L' Fitting connection part insulation
1
All of the fitting connecting parts should be insulated. Bring face to face the each end of EPDM on fitting connection part.
2
Make fitting cover to fit the EPDM insulation fitting cover should be overlapped with insulation min 1 inch (2.5cm).
Guidelines for each installation process
Ceiling Cassette
103
Insulation work
5CST2-06A
2.4.2 Forming the piping 1) Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape. â&#x20AC;˘ If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately. 2) In cases where the outdoor unit is installed below the indoor unit perform the following. Tape the piping, drain hose and transmission cable from down to up. Secure the tapped piping along the exterior wall using saddle or equivalent.
The cable is required to prevent rain water from entering into electrical parts of outdoor unit.
104
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Insulation work
2.4.3 Essential points of thermal insulation 1) Thermal insulation of refrigerant piping
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant insulation materials, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation drip, etc. pay special attention to insulation work to ceiling plenum. • Do not insulate gas or low pressure pipe and liquid or high pressure pipe together.
B Wrong method
• Be sure to fully insulate connecting portion.
A Liquid pipe
A
A
B Gas pipe
C
C Power cable D Insulation
D D E
Correct method
A These parts are not insulated.
A Liquid pipe
E
B Gas pipe
A
B
C Power cable D Transmission cable E Insulation
C
2. Penetrations 2) Caution during insulation work Outer wall Inner wall (concealed)
Outer wall (exposed)
Sleeve
D line and transmission line should be separated Heat insulating material • To avoid electrical noise, the power from each other.
• In case the cables are installed in the conduit, a finishing tape is not required. • Defect and insufficient insulation can cause condensation drops. • Binding the insulation too tight may result in dew drops. • Be sure not to tie rap the insulation but put special taping or the clamp at the connecting portion. • The insulation overlapping part at the piping connection must be a distance from the flaring part at the pipe connection.
Guidelines for each installation process
Ceiling Cassette
105
Insulation work
5CST2-06A
3) Insulation tube thickness Thickness of insulation tube is decided considering the following factors : • Insulation material: EPDM or polyethylene foam • Thermal conductivity 0.035 kcal~0.040kcal/mh°C • Heat resistance=85°C(Cooling only) or more 100°C(Heat pump) or over The thickness of the thermal insulation material must be determined in the light of the pipe sizes. Pipe size
Thickness of insulation material (normal)
6.35 ~ 25.4 mm
13mm or more
25.4 ~
19mm or more
It will be necessary to increase the thickness of insulation in the above table when conditions are hot and humid. Where a customer supplies his own specifications then these must be adhered to. CAUTION
Outdoor temperature and humidity around the cooling piping might exceed 30°C and RH80%, reinforce the insulation on the cooling piping (at least 20mm thick)
106
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Electrical work
2.5 Electrical work 2.5.1 Precautions CAUTION
When knocking out knock holes • To punch a knock hole, hit it with a hammer. • After knocking out the holes, we recommend you paint the edges and areas around it to prevent rusting. • When passing electrical wiring through the knock holes, remove any burrs from the knock holes and wrap the wiring with a protective tape to prevent damage.
Burr
If there are any possibilities that small animals or insects enter the system through the knock holes, plug the holes with packing materials (to be prepared onsite).
Use a conduit for the cable • Outside the unit, make sure the thin signal cable (i.e. for the remote control, between units, etc.) and the thick electric wiring do not pass near each other, and the shield signal cable, is recommended. Otherwise, the outdoor unit may be affected by electrical noise (external noise), and malfunction or fail. • Secure the wiring with the accessory clamps so that it does not touch the piping. • Make sure the wiring and the electric parts box cover do not stick up above the structure, and close the cover firmly.
CAUTION
Do not operate the air conditioner until the refrigerant piping work is completed. (Operating the air conditioner before the refrigerant piping work is completed may damage the compressor.) • Install an earth leakage circuit breaker. Since this is a inverter air conditioner. In order to prevent malfunction of the earth leakage breaker itself, use a breaker resistant to higher harmonics. • After finishing the electric work, confirm that each electric part and terminal inside the electric parts box is connected securely.
NOTE
• Only professional electricians having sufficient knowledge should perform the electrical wiring work. Perform the electrical wiring work in accordance with the electrical wiring diagram. Make sure to set OFF the branch switch and over current breaker before starting the work. • Install an earth leakage breaker. • Perform grounding to the indoor units and outdoor units. • Do not connect the ground wire to gas pipes, sewage pipes, lightning rods telephone ground wires. • Gas pipes ···· Can explode or catch fire if gas leaks. • Sewage pipes···· Provides no grounding effect if hard plastic pipes are used. • Telephone ground wires and lightening rods ···· dangerous when struck by lightening due to abnormal rise in the ele trical potential in the ground.
Guidelines for each installation process
Ceiling Cassette
107
Electrical work
5CST2-06A
• Use only copper wires. • Make sure to shut down the power before starting the electric wiring work. Do not switch ON any switch until the work is completed. • The outdoor unit has an inverter compresser which generates noise and charges the outer casing with the leakag current. The outdoor unit should be grounded so that the effect of the generated noise on to the equipment can be reduced, and that the outer casing can be discharged. • Never install a phase advancing capacitor for power factor improvement. (Even if it is installed, the power factor is not improved. And if it is installed, the outdoor unit is abnormally overheated.) • Use specified electric wires in the wiring, and connect them securely. Fix them in such a way that external force is not applied at the terminals (transmission wiring in the local field and ground terminal). • Never push excessive electric wires into the units. • Protect electric wires with conduit tubes or other proper tubes so that they will not be damaged by edges of knock holes. • Do not use multi conductor cable which have more than 5 wires in one core.
108
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Air tight test
2.6. Air tight test 2.6.1 Air purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Pressure in the system rises. Operating current rises. Cooling (or heating) efficiency drops. Moisture in the refrigerant circuit may freeze and block capillary tubing. Water may lead to corrosion of parts in the refrigeration system. Therefore, the indoor/outdoor unit and connecting tube must be checked for leakage, and vacuumed to remove incondensable gas and moisture in the system.
1)Checking method
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position. 1. Do a leakage test of all joints of the Tubing (both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth. 2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Preparation â&#x20AC;˘ Check that each pipe (both liquid and gas side pipes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage. Leakage test â&#x20AC;˘ Connect the manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
Gas pipe
Liquid Liquid Pipe pipe
Manifold valve Pressure gauge Lo Hi
Manifold gauge hose
Charge hose
Outdoor unit
Nitrogen gas cylinder(in vertical standing position)
Guidelines for each installation process
Ceiling Cassette
109
Air tight test
5CST2-06A
2.6.2 Essential points of testing The key to successful testing is strict adherence to the following procedure: 1) The liquid and gas piping in each refrigerant system should be pressurized in turns in accordance with the following steps. (Nitrogen gas must be used.) Step 1: increase pressure to 0.3MPa for 3 minutes or more Major leaks indicate Step 2: increase pressure to 1.5MPa for 3 minutes or more Minor leaks indicate
Step 3: increase pressure to 3.8MPa for approxmate 24 hours
Increasing the system pressure to 3.8MPa does not guarantee the identification of minor leaks if pressure is maintained for only a short time. It is therefore recommended that the system remain pressurized in accordance with Step 3 above for at least 24 hours. NOTE
Piping should not be pressured more than 3.8MPa. 2) Check for pressure drop If there is no drop in pressure then the test is deemed a success. If the pressure drops then the leak must be located. See following page. However, if there is a change in the ambient temperature between the pressurizing stage and the time when you check for a drop in pressure then you will have to adjust your calculations accordingly since a change of 1°C can account for a pressure change of approximately 0.01MPa. Compensating adjustment value: (temperature at time of pressurizing – temperature at time of checking)
0.01
Example: During of pressurizing: 3.8MPa 25˚C 24 hours later: 3.75MPa 20˚C Although the gauge pressure is dropped from 3.8MPa to 3.75MPa, it can be safely assumed that there is no leakage because the gauge pressure can also drop due to the change in outdoor temperature. (MPa) 3.8
3.8MPa x 24min
Step 3 3.75
3.5 Outdoor te mperature (℃ ( )
3.0
25℃ 20℃
2.5
15℃
2.0 1.5MPa x 5min
1.5
Step 2
1.0 0.5
0.3MPa x 3min
Step 1
0 24 hours
(Time)
5 minutes 3 minutes
110
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Air tight test
2.6.3 Checking for leakage [Check 1] (Where pressure falls while carrying out Steps 1 to 3 described on previous page) Check by measure gage......Gas detector. Check by ear......Listen for the sound of a major leakage. Check by hand......Check for leak by feeling around jointed sections with hand. Bubble check ......Bubbles will reveal the presence of a leakage. [Check 2] (When searching for a minor leak or when there has been a fall in pressure while the system has been fully pressurized but the source of the leak cannot be traced.) Release the nitrogen until the pressure reaches 0.3MPa. Increase pressure to 1.5MPa using gaseous refrigerant(R22). Search for the source of the leakage using a leakage detector such as a halide torch or a propane or electrronic detector. If the source of the leakage still cannot be traced then repressurize with nitrogen up to 3.8MPa and check again. (The pressure must not be increased to more than 3.8MPa.) (System sample)
Do not open the service valve during the airtight test.
(R22 gas) Liquid Pipe Liquid Pipe
Vacuum pump Nitrogen gas
Gauge
Important points Where the lengths of piping involved are particularly long then the air tight test should be carried out block by block. - Indoor side - Indoor side + vertical pipes - Indoor side + vertical pipes + outdoor side
Liquid side
CAUTION
Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. 3. To open the 2-way valve turn the valve stem counterclockwise approximately 90째, wait for about 2~3 sec, and close it. 4. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. 5. If bubbles appear then those points have leakage.
Guidelines for each installation process
Gas side 2-way valve (Open) 3-way valve (Close)
Ceiling Cassette
Hexagonal wrench
Cap
111
Vacuum drying
5CST2-06A
2.7. Vacuum drying work 2.7.1 What is Vacuum drying? Vacuum drying is : The use of a vacuum pump to vaporize(gasify) the moisture (liquid) inside the pipe and expel it leaving the pipes completely dry inside. At 1 atm(760mmHg) the boiling point (evaporating temperature) of water is 100째C but if a vacuum is created inside the pipes using a vacuum pump then the boiling point is rapidly reduced as the degree of the vacuum is increased. If the boiling point is reduced to a level below that of the ambient temperature then the moisture in the pipes will evaporate.
Example When outside temperature is 11.7째C as shown in the table on the right , the degree of vacuum must be lowered below -750mmHg
Boilng point of water(째C)
mmHg
Pa
Torr
The evacuation of air conditioner piping provides the following effects.
40 30 26.7 24.4 22.2 20.6 17.8 15.0 11.7 7.2 0
-705 -724 -735 -738 -740 -742 -745 -747 -750 -752 -755
7333 4800 3333 3066 2666 2400 2000 1733 1333 1066 667
55 36 25 22 20 18 15 13 10 8 5
- Vaccum drying - Removes air and nitrogen(used in air-tightness test) from the inside of pipes.
NOTE
Key point: Maintain a vacuum level of -755mmHg
0 60 160 260
760mmHg 700 600 500
360
400
460
300
560
200
660 670 680 690 700
100 90
710
70 60 50
720
40
730
30
740
20
3.8MPa
10
Required degree of vaccum
Evaporation point
755
Absolute pressure (mmHg)
Gauge pressure (kg/cm2)
Therefore , it is necessary to ensure that both purposes have been achieved in the vacuum drying operation.
Gauge pressure
5
Outside temperature range
mmHg 760 -20 -10
0
10
20
30
Temperature
112
Ceiling Cassette
40
50
60
70
x
0 mmHg
(째C)
Guidelines for each installation process
5CST2-06A
Vacuum drying
2.7.2 Evacuation Connect the manifold hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Gas Gas pipe Pipe
pipe Liquid Pipe
Manifold gauge
Outdoor unit
Manifold valve Pressure gauge
Lo
Hi
Open
Close
Vacuum pump (0.5 ~ 1HP)
CAUTION
Finishing the job 1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve. 2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve. 3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose. 4. Replace the flare nut and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system. 5. Replace the valve caps at both gas and liquid side service valves and fasten them tight. This completes air purging with a vacuum pump. The air conditioner is now ready for test run.
Guidelines for each installation process
Ceiling Cassette
113
Vacuum drying
5CST2-06A
2.7.3 Choosing a vacuum pump The necessity for counter flow prevention After the vacuum process of the refrigerant cycle, the inside of the hose will be vacuumed but after stopping the vacuum pump, the oil of vacuumpump may flow back. Moreover, if the vacuum pump may stop during the operation for some reason. Therefore, in order to prevent the counter flow from the vacuum pump, a check valve is reguired.
1) Vacuum pump performance The 2 most important things for determining vacuum pump performance are as follows: Exhaust velocity Degree of vacuum Exhaust velocity Exhaust volume is usually expressed as l/min or m3/hr. The larger the number, the faster the vacuum is achieved. Generally speaking, the faster the exhaust velocity, the larger and heavier the vacuum pump is. Commercially available vacuum pumps (exhaust velocity of 20 - 30 l/min) usually take an extremely long time to achieve vacuum. (We recommend a vacuum pump of approx. 60 - 100 l/min.) Degree of vacuum Ultimate vacuum varies largely according to use of the vacuum pump. Vacuum pumps used for vacuum forming cannot be used for vacuum drying. (A vacuum pump with a high degree of vacuum is required.) When selecting a vacuum, you should select one which is capable of achieving 0.2 Torr of ultimate vacuum. Degree of vacuum is expressed in Torr, micron, mmHg, and Pascal (Pa). The units correlate as follows:
Unit
Standard atmospheric pressure
Perfect vacuum
0
-1.033
Gauge pressure
kg/cm
Absolute pressure
kg/cm abs
1.033
0
Torr
Torr
760
0
Micron
Micron
760000
0
mmHg
mmHg
0
760
Pa
Pa
1013.33
0
2
2
Degree of vacuum must be within the range expressed by
0 Torr
5 Torr
760 Torr
0 Pa
667 Pa
1013.33 hPa
760 mmHg
755 cmHg
0 mmHg
Perfect vacuum
Vacuum target value
Standard atmospheric pressure
114
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Vacuum drying
2) Vacuum pump maintenance Because of their nature, most vacuum pumps contain large amounts of oil which lubricate bearings, etc., and function to enhance airtightness of pistons. When using a vacuum pump to discharge air from refrigerant piping, moisture in the air tends to get mixed in with the oil. You must therefore change oil periodically and make sure that proper oil level is maintained. (Perform periodic inspections in accordance with the operating instructions.)
3) Degree of vacuum measurement An extremely accurate vacuum gauge is required to test degree of vacuum. You cannot accurately measure degree of vacuum with the compound gauge on the gauge manifold. A Pirani vacuum gauge is required to measure degree of vacuum accurately. Because Pirani gauges are very sensitive and require extreme care when using, they are not very suitable for use in the field. You should therefore use the Pirani gauge to calibrate the attached vacuum gauge on the gauge manifold and the degree of vacuum of the vacuum pump.
4) Calibration method Connect a Pirani vacuum gauge and the gauge manifold vacuum gauge (760 mmHg) to the vacuum pump at the same time, and run the pump for about 3 minutes. Make sure the reading of the Pirani vacuum gauge is 5 Torr (667 Pa ) or less. The reading of conventional vacuum pumps lowers to about 0.2 Torr. If the reading is not 5 Torr or less, check the vacuum pump oil. (Oil is low in many cases.) Check the attached gauge on the gauge manifold. Adjust the gauge if the reading is not exactly correct. Adjust the gauge manifold valve so that the Pirani vacuum gauge reads 5 Torr. Mark the position indicated by the gauge manifold gauge with an oil based ink pen. Use the mark of the gauge manifold as a target when vacuuming in the field. Gauge manifold
Pressure detection section
Indicator Vacuum pump
(Reference) Types of vacuum pump with respect to maximum degree of vacuum Type Oil rotary (Oil using)
Maximum degree of vacuum Expulsion capacity
Vacuum drying
Air expulsion
100 l/min
Suitable
Suitable
50 l/min
Unsuitable
Suitable
Suitable
Suitable
0.02 mmHg 10 mmHg
Oilless rotary (No need of oil)
0.02 mmHg 40 l/min
Guidelines for each installation process
Use
Ceiling Cassette
Many handy pumps fall into this category
115
Vacuum drying
5CST2-06A
2.7.4 Vacuum drying procedure There are two vacuum drying methods and the appropriate one should always be chosen to confirm with individual local conditions. [Normal vacuum drying]........The standard method
[Operational steps] Vacuum drying (1st time): Connect a manifold gauge to the service port of the liquid or gas pipe and operate the vacuum pump for at least 2 hours. (The degree of vacuum produced should be in excess of 5 Torr) If after 2 hours the vacuum produced has not exceeded 5 Torr then either there is moisture in the pipe or there is a leak. Operate the vacuum pump for further one more hour. If, even after 3 hours, the vacuum has not reached 5 Torr then check the system for a leak. Carry out vacuum test. Produce a vacuum in excess of 5 Torr and do not release it for an hour or more. Check the vacuum gauge to make sure that it has not risen. (If the gauge rise then there is still moisture in the pipe or there is a leak somewhere.) Additional charge of refrigerant. Connect the charging cylinder to the liquid pipe service port and charge with the required amount of refrigerant. Open stop valve to the full. Open the stop valve on the liquid and the gas pipes to the full.
NOTE
Vacuum should be produced in both the liquid and the gas pipes. (Because there is a large number of functional components in the indoor unit which cut off the vacuum mid-way through)
+0.05MPa Rising pressure
0 MPa
(Atmospheric pressure) 0 MPa -200 mmHg
Falling pressure -400 mmHg (vacuum)
-600 mmHg
-700 mmHg
-755 mmHg (5 Torr)
Time.
-760 mmHg
Additional refrigerant Vacuum Maintaining charge drying vacuum test (2 hours) (1 hours) Time required: approximately 3 hours.
116
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Trial test run operation
2.8 Trial test run operation 2.8.1 Test run procedure Check the following before turning power on
Wrong power wiring , loose screws Wrong control transmission wiring , loose screws Piping size , presence of thermal insulation Use a mega-tester
Measurement of main power circuit insulation
Be sure to record the additional quantity of refrigerant
Addition of refrigerant if required Fully open respective stop valves on liquid, gas Turn on outdoor unit power
2.8.2 Evaluation of performance Evaluation of performance Operate unit for 15~20 minutes, then check the system refrigerant charge: Measure the pressure of the gas side service valve. Measure the temperature of the intake and discharge of air. Ensure the difference between the intake temperature and the discharge is more than 8°C Intake temperature
Discharge temperature
Discharge air
For reference, the gas side pressure of optimum condition is as below. (Cooling)
R22
Outside ambient Temp. 35°C (95°F)
The pressure of the gas side service valve.(Low Pressure) 5.0~7.0kg/cm2G
R410A
35°C (95°F)
8.0~10.0kg/cm2G
Refrigerant
NOTE
: If the actual pressure is higher than shown, the system is most likely overcharged so extra refrigerant should be removed. If the actual pressure is lower than shown, the system is most likely undercharged so extra refrigerant should be added. The air conditioner is now ready for use. Guidelines for each installation process
Ceiling Cassette
117
Trial test run operation
5CST2-06A
2.8.3 Transfer to customer with explanation Operational step
Complete test run
Make final report (test run inspection sheet)
Explain how to operate and maintain equipment
Hand over relevant printed materials
The measurements taken during the test run should be recorded and kept on a test run inspection sheet. Do not forget to record the length of the refrigerant piping and the refrigerant additional charging volume on the plate on the back of the outdoor unit external notice board, as this information will be required for servicing the system. Explain the customer how to operate and maintain the equipment and let him try it. Assemble all the relevant diagrams and other printed matter which is required to operate the system and hand over to the customer (on the spot) and request him to keep it handy. Service contact address.
List of equipment which has been delivered
Installation drawing
It is essential to prepare a control wiring diagram which clarifies the refrigerant system and the control system.
1 set of operation manuals
Names of those responsible for the work (emergency contact address)
Equipment guarantees.
118
Ceiling Cassette
Guidelines for each installation process
5CST2-06A
Safety precautions
3. Installation of indoor unit 3.1 Safety precautions Please strictly follow the instructions given in the Installation manual .Improper installation by ignoring the instructions can lead to damage of life and property. Make sure to read the following safety instructions very carefully and throughly .
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage to properties only.
■ The meaning of the symbols used in this manual are as shown below.
Be sure not to do. Be sure to follow the instruction.
WARNING Do not use a defective or underrated circuit breaker. • There is risk of fire or electric shock. Always use this appliance on a dedicated circuit breaker. • Otherwise it can cause electric shock or fire. For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service center. Do not disassemble or repair the product by yourself. • There is risk of fire or electric shock. Always ground the product as per the field wiring diagram. Do not connect the ground wire to gas or water pipes lightening rod or telephone ground wire. • There is risk of fire or electric shock. Install the panel and the cover of control box securely. • There is risk of fire or electric shock due to dust , water etc. Use the correctly rated breaker or fuse. • There is risk of fire or electric shock. Do not modify or extend the power cable. If the power cable or cord has scratches or skin peeled off or then immediately replace it. • There is risk of fire or electric shock. For installation, removal or reinstall, always contact the dealer or an Authorized Service Center. • There is risk of fire, electric shock, explosion, or injury. Do not install the product on a defective installation foundation. Be sure that the installation area does not deteriorate with age. • If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury. When the product is soaked (flooded or submerged) in water, contact an Authorized Service Center for repair before using it again. • There is risk of fire or eletric shock. In outdoor unit the step-up capacitor supplies high voltage electlicity to the electricity components. Be sure to discharge the capacitor completely before conducting the repair work. • An charged capacitor can cause electrical shock. Be sure to use only those parts which are listed in the service parts list. Never attempt to modify the equipment. • The use of inappropriate parts can cause an electrical shock, excessive heat generation or fire. Indoor/outdoor wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable at the connection terminals. • Improper or loose connections can cause excessive heat generation or fire.
Installation of indoor unit
Ceiling Cassette
119
Safety precautions
5CST2-06A
Safely dispose off the packing materials. • Things like screws, nails, batteries, broken things etc. after installation or service can cause injury to small kids. Tear and throw away the plastic packaging bags so that children do not play with them. During svc be sure to check the refrigerant to the used. • Incorrect refrigerant used can prevent the normal operation of the unit. When installing the unit, use the installation kit provided with the product. • Otherwise the unit may fall and cause severe injury . Do not touch, operate, or repair the product with wet hands. • There is risk of electric shock or fire. Do not place a heater or other appliances near the power cable. • There is risk of fire and electric shock. Do not allow water to run into electric parts. Install the unit away from water sources • There is risk of fire, failure of the product, or electric shock. Do not store or use or even allow flammable gas or combustibles near the product. • There is risk of fire or failure of product. Do not use the product in a tightly closed space for a long time. Perform ventilation regularly. • Oxygen deficiency could occur and hence harm your health. If strange sounds, smell or smoke comes out from product, immediately turn the breaker off or disconnect the power supply cable. • There is risk of electric shock or fire. When installing the unit, use the installation kit provided with the product. • Otherwise the unit may fall and cause severe injury. Do not open the front grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) • There is risk of physical injury, electric shock or product failure. Ventilate the product room from time to time when operating it together with a stove, or heating element etc. • Oxygen deficiency can occur and hence harm your health. Turn off when cleaning or repairing the product. • There is risk of electric shock. When the product is not to be used for a long time, shut off the circuit breaker. • There is risk of product damage or failure or unintended operation.
120
Ceiling Cassette
Installation of indoor unit
5CST2-06A
Safety precautions
CAUTION Use two or more people to lift and transport the product. • Avoid personal injury. Do not install the product where it exposed to sea wind (salt spray) directly. • It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation. Install the drain hose to ensure that water is drained away properly. • A bad connection may cause water leakage. Keep level even when installing the product. • To avoid vibration or noise. Always check for gas (refrigerant) leakage after installation or repair of product. • Low pressure levels may cause failure of product. Do not block the inlet or outlet of air flow. • It may cause product failure. Use a soft cloth to clean. Do not use harsh detergents, solvents or splashing water etc . • There is risk of fire, electric shock, or damage to the plastic parts of the product. Do not step on or put anyting on the product. (outdoor units) • There is risk of personal injury and failure of product. Do not insert hands or other objects through the air inlet or outlet while the product is operating. • There are sharp and moving parts that could cause personal injury. Be cautious when unpacking and installing the product. • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator. If the refrigerant gas leaks during the repair, do not touch the leaking refrigerant gas. • The refrigerant gas can cause frostbite (cold burn). Do not tilt the unit when removing or uninstalling it. • The condensed water inside can cause spill and wet the furniture and the floor. Do not mix air or gas other than the specified refrigerant used in the system. • If air enters the refrigerant system, an excessively high pressure results, causing equipment damage or injury. Replace the old batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries. • There is risk of fire or explosion. If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked. • The chemicals in batteries could cause burns or other health hazards. Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system. • There is risk of damage or loss of property. Do not touch the metal parts of the product when removing the air filter. • There is risk of personal injury. If the refrigerant gas leaks during the installation or operation ventilate the area immediately. • Otherwise it can be harmful to your health. Do not turn off the power immediately after stopping the operation. • Always wait for 5 minutes before turning off the power otherwise water leakage and troubles can occur. Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open. • Moisture may condense and wet or damage furniture. Do not expose your skin or kids or plants to the cool or hot air draft. • This could harm your health. Do not drink the water drained from the product. • It is not hygienic and could cause serious health issues. Use a firm stool or ladder when cleaning, maintaining or repairing the product at an height. • Be careful and avoid personal injury. Dismantling the unit , treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards. Do not recharge or disassemble the batteries. Do not dispose off batteries in fire. • They may burn or explode.
Installation of indoor unit
Ceiling Cassette
121
Safety precautions
5CST2-06A
3.1.1 Points for explanation about operations The items with WARNING and CAUTION marks in the operation manual are the items pertaining to possibillties for body injury and material damage in addition to the general usage of the product. Accordingly, it is necessary that you make a full explanation about the described contents and also ask your customers to read the owner's manual.
NOTE
to the installer
Be sure to instruct customers how to properly operate the unit (especially cleaning filters, different operating functions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.
3.1.2 Selecting installation site for indoor units 1) Select an installation site where the following conditions are fulfilled and that meets your customer s approval. Location strong enough to bear the weight of the unit. Location accessible and having enough clearance for inspection and service in the future. Location allowing easy condensate drainage and suitable gradient of the unit and the drain pipe. Piping between the indoor and outdoor unit is possible within the allowable limits. Location free from electrical noise. Location allowing optimum air distribution without any blocking to air flow. Location having no risk of flammable gas leakage. Location free from mineral oil mist or an oil spray or vapor example in kitchen .It could result in leakage . Location free from corrosive gases such as sulphurous acid gas because it corrodes the copper pipes or soldered parts resulting in leakage . Location free from any machinery emitting electromagnetic waves which may disturb the control system thus causing malfunction of the unit . Location free from flammable gases , carbon fibre , or ignitable dust suspensions in the air or where volatile flames are handled like gasoline or thinner. Operating in such conditions may result in fire . Install the indoor and outdoor units, power supply wiring and connecting wires at least 1m away from television or radio in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1m. may not be sufficient enough to eliminate the noise.) Consider whether the place where the unit will be installed can support the full weight of the unit, and reinforce it with boards and beams, etc. If needed before proceeding with the installation. Reinforce the place to prevent vibration and noise before installing. Obey the local and national regulations and limits regarding airconditioner installation.
122
Ceiling Cassette
Installation of indoor unit
5CST2-06A
Safety precautions
2) For the following items, take special care during construction and check after installation is finished Items to be checked after completion of installation work Items to be checked
If not properly done, what is likely to occur
Are the indoor and outdoor unit fixed firmly?
The units may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling or heating.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the name plate?
The unit may malfunction or the components burn out.
Are wiring and piping correct?
The unit may malfunction or the components burn out.
Is the unit safely grounded?
It may be dangerous during electric leakage.
Is wiring size correct according to specifications?
The unit may malfunction or the components burn out.
Is there something blocking the air outlet or inlet of either the indoor or outdoor units?
It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge noted down?
The refrigerant charge in the system is not clear.
Check
3.1.3 Before installation During product unpacking and removing it from the packing case, be sure to lift it without exerting any pressure on other parts, especially, horizontal flaps, the refrigerant piping, drain piping, and other resin parts. • The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them! • Decide upon a line of transport. • Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit. • When using the wireless remote controller, refer to the installation manual attached to the wireless remote controller.
NOTE
• Be sure to read this manual before installing the indoor unit. • Entrust installation to the place of purchase or an authorized serviceman. Improper installation could lead to leaks and in worst cases, electric shock or fire. • Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could cause the unit to fall out of place, or could lead to leaks and in the worst cases, electric shock or fire.
Installation of indoor unit
Ceiling Cassette
123
Ceiling cassette 4-way
5CST2-06A
3.2 Ceiling cassette 4-way • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Long life filter Air return Air supply
3.2.1 Accessories Check whether the following accessories are included with your unit.
1) Standard accessories Name
Drain hose
Clamp metal
Quantity
1 EA
1 EA
Washer for hanging backet 8 EA
Shape
Clamp
Insulation for fitting
8 EA
1 SET
for gas pipe
(Other)
• Paper pattern for installation • Owner's manual • Installation manual
for liquid pipe
124
Ceiling Cassette
Installation of indoor unit
5CST2-06A
Ceiling cassette 4-way
3.2.2 Selection of the best location • There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • There should be provision of easy condensate drain. • Taking into account the noise prevention criteria, spot the installation location. • Do not install the unit near the door way. • Keep proper distances, of the unit, from ceiling, fence, floor, walls and other obstacles as shown in figure. • The indoor unit must have sufficient maintenance space.
3.2.3 Precautions regarding cassette indoor unit installation 1) Main points about the indoor installation - In case of high height ceiling In general commercial places and offices though the height of the ceiling is 2.7 m, the ceiling height can be 3 m. In such cases because of the temperature difference with the floor the heating effect can fall down.
Discharge Suction High elevation of the ceiling
Hot air
50 or more
Above 250 400 or less
100 or more
Ceiling Ceiling Board
Ceiling Board 30 or less
30 or more
Cold air
50 or more
Unit:cm
Outdoor side (Entering of air by frequent opening and closing of door)
- Countermeasure method Air conditioner must be able to operate in high ceiling rooms. Plan to install the circulator. The air discharge port is made to give more airflow to the down wood directions.
Floor
The gate or exit of the building is protected by dual door system. NOTE
Above figure means minimum value. Please keep these value at least. If H is 2700~3300: High ceiling operation control required If H is ~2700: Normal operation
2) In case the floor or surfaces of the place to be air conditioned is in direct contact with the outdoor air - The floor of the heating room in direct contact with the storeroom, garage or the outside air receives the cold air at the floor and the floor temperature decreases and the person will feel cold at the feet. Indoor
1500 or more 1500 or more
Low temperature of the floor
1500 or more
Outdoor side
Outdoor side Garage
(50~100mm Insulation required) Outdoor side
1500 or more
Unit:mm
Installation of indoor unit
In such places where the feet comes in direct contact with floors will give a cold feeling to the person.
Ceiling Cassette
125
Ceiling cassette 4-way
5CST2-06A
- Countermeasure: • Use the carpet on the floor (compared to the tiles, the carpet over it will have a 3 degree rise in temperature)
• Refrigerant piping: Increase the piping insulation thickness above 20 mm. Refrigerant piping
• Insulating the floor. • Floor heating
CAUTION
• Case of cold air intake: The duct surface will have dew drops so an insulation material on the duct is a must.(Insulation material: a glass wool of thickness 25 mm will be appropriate.)
• Others: Inside the ceiling near th air tight seal places (To escape of the humidity inside false ceiling)
3) In case of high temperature or high humidity between the false ceiling and ceiling slab(near by the sea, river, lake, spa) - In case of temperature of 30 degree and humidity above 80%, the units body as well as the piping insulation should be strengthened. Refer to the picture given below. Psychrometric chart
Enhance additional insulation required area
Grill for ventilation
4) In case of multiple indoor cassette units (recommended) Indoor unit
Indoor unit Ventilator Lighting
Relative humidity
30˚C 1500mm or more 2000mm or more
- Places having the temperature and humidity of the surrounding water sources(sea, river etc.)
3000mm or more
In case, steam is generated between the false ceiling and the ceiling slab Due to some nearby steam source. • Indoor unit: Insulate the unit body with some insulation material like glass wool of at least 10 mm thickness.
Additional insulation required
126
Ceiling Cassette
Installation of indoor unit
5CST2-06A
Ceiling cassette 4-way
3.2.4 Ceiling opening dimensions and hanging bolt location The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions. Select and mark the position for fixing bolts and piping hole.
1) Install the suspension bolts. (Use either a W3/8â&#x20AC;? or M10 size bolt) Use a hole-in anchor for existing ceilings, and a sunken insert, sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit. Adjust clearance from the ceiling before proceeding further.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Ceiling Anchor Long nut or turn-buckle
Drill the hole for anchor bolt on the wall.
Suspension bolt
TD, TH Model 810 785
False ceiling
30 30
30
NOTE
840
810
672
840
All the above parts are field supplied.
3.3.5 Indoor unit installation â&#x20AC;˘ Installation of the accessories (except for the decoration panel) before installing the indoor unit is easier.
30
Indoor
Unit:mm
TE1 Model
1) Install the indoor unit. â&#x20AC;˘ Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and washer from the upper and lower sides of the hanger bracket.
570 521 Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)
Flat washer for M10 (accessory)
450 570
Spring washer (M10) Flat washer for M10 (accessory) Nut (W3/8 or M10)
Keep the length of the bolt from the bracket to 40mm Air Conditioner body
150mm
Ceiling
Unit:mm
Ceiling board
Ceiling board Keep the length of 15~18mm between the air conditioner bottom surface and the ceiling surface
Set screw of paper model (4 pieces) Paper model for installation
Installation of indoor unit
Ceiling Cassette
Open the ceiling board along the outer edge of the paper model
127
Ceiling cassette 4-way
5CST2-06A
3.2.6 Connecting pipes to the indoor unit
• The following parts are locally purchased. - Hanging Bolt
- W 3/8 or M10
- Nut
- W 3/8 or M10
1) Refrigerant piping work
- Spring Washer - M10
please refer “REFRIGERANT PIPING WORK”.
- Plate Washer - M10
2) Piping insulation
2) For new ceilings Refer to the paper pattern for ceiling opening dimension. • The center of the ceiling opening is indicated on the paper pattern for installation. The center of the unit is indicated on the label attached to the unit and on the paper pattern for installation. • First remove paper packaging material from the 4 corners of the paper pattern for installation , fix the paper pattern to the unit with screws. • Ceiling height is shown on the side of the paper pattern for installation. Adjust the height of the unit according to this indication.
Perform heat insulation work completely on both gas and the liquid pipe. Because improper insulation will result in condensate formation over pipe. Use the heat insulation material for refrigerant piping which has an excellent heat resistance (over 120°C). Precautions in high humidity circumstance: Refer to insulation work
CAUTION
• Make sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause condensation or burns if touched.
<Ceiling work> Adjust the unit to the right position for installation. Assure that the unit is horizontal. • The indoor unit is equipped with a built-in drain pump and float switch. At each of the unit's 3 corners, verify that it is levelled by using awater-level or a water-filled vinyl tube. (Otherwise it will result in the malfunctioning of unit and cause water to drip.) Remove the washer fixing plate used for preventing the washer from falling and tighten the upper nut.
3) Indoor unit drain piping • Drain piping must have downward slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reverse flow. • During drain piping connection, be careful not to exert extra force on the drain port of the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings
5) Remove the paper pattern for installation
2) For existing ceilings Adjust the height and position of the unit. Perform steps 3 and 4 in "2) For new ceilings".
128
Ceiling Cassette
1/50~ 1/100
Upward routing not allowed
MAX 700mm
Installation of indoor unit
5CST2-06A
Ceiling cassette 4-way
• Be sure to install heat insulation on the drain piping. Heat insulation material: Polyethylene foam with thickness more than 10 mm.
Flexible drain hose (Accessory) Main drain pipe
Drain pump
NOTE
• The decoration panel has its installation direction. • Before installing the decoration panel, always remove the paper template.
4) Drain test
Feed water
3.2.7 Installation of decoration panel
Drain port
Glue the joint
Drain hose connection use the clip (Accessory)
Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included with the indoor unit box. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. Tighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
Drain pan
Connect the louver motor connector and display connector. After tightening these screws, install the air inlet grille (including the air filter).
Flexible drain hose Piping side
Air conditioner unit
Decorative panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)
Control box cover
Decorative panel Key holes Lead wire for louver motor and display
Decorative panel fixing screws (Hexagon M5 screw)
Inlet Grille
Installation of indoor unit
Ceiling Cassette
129
Ceiling cassette 4-way
5CST2-06A
2) Wiring Connection CAUTION
â&#x20AC;˘ Properly install decoration panel because any slit or gap between unit and decoration panel will result cool air leakage which may responsible for water driblling.
Open the control box cover and connect the Remote controller cord and Indoor power wires.
Air conditioner unit
False ceiling
Indoor power cord
Decoration panel Fit the insulation (this part) and be careful for cool air leakage
Fire prevention cover Remote controller cord Connector cover Fire prevention cover bolt
Air conditioner unit Air
Cool air leakage(no good)
False ceiling Decoration panel
3.2.8 Electric wiring work Code clip
1) General instructions All field supplied parts and materials, electric works must conform to local codes. Use copper wire only. Follow the "WIRING DIAGRAMâ&#x20AC;? attached to the unit body to wire the outdoor unit, indoor units and the remote controller. All wiring must be performed by an authorized electrician. This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and make sure the terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the outdoor unit and an indoor units are mismatched, the system may a malfunction. A circuit breaker capable of shutting down the power supply to the entire system must be installed.
130
Ceiling Cassette
Installation of indoor unit
5CST2-06A
Ceiling cassette 4-way
3Phase 36k/48k/54kBtu/h Heat Pump Model. R
S
T
NOTE
N
POWER INPUT
Terminal Block of Indoor Unit 1(L) 2(N) 3 4 5
Terminal Block of Outdoor Unit 1(L) 2(N) 3 4 5
1. Use round crimp-style terminals for connecting wires to the power supply terminal block. If unavailable, observe the following points when wiring. • Do not connect wires of different gauge to the same power supply terminal. (Loose connection may cause overheating.) • Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without applying excessive force to the terminal.
1Phase 18k/24k/28kBtu/h Heat Pump Model.
Attach insulation sleeve
Terminal Block of Indoor Unit 1(L) 2(N) 3 4 5
Terminal Block of Outdoor Unit 1(L) 2(N) 1(L) 2(N) 3 4
Round crimp-style terminal POWER INPUT
Electricwire
3Phase 36k/48k/54kBtu/h Cooling Model. R
S
T
N
Terminal Block of Outdoor Unit 1(L) 2(N) 3
Terminal Block of Indoor Unit 1(L) 2(N) 3 4 5
POWER INPUT
1Phase 18k/24k/28kBtu/h Cooling Model. Terminal Block of Outdoor Unit 1(L) 2(N) 1(L) 2(N) 3 4
Connect wires of the same gauge to both sides Terminal Block of Indoor Unit 1(L) 2(N) 3 4 5
2. Tightening torque for the terminal screws.
POWER INPUT
Make sure to attach the sealing material (field supplied) to hole of wiring to prevent the infiltration of foreign particle from outside. Otherwise a short-circuit may occur inside the electric parts box When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts box cover, make sure no wires get caught in the edges. Pass wiring through the holes to prevent damage. Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the same locations outside the unit, separating them properly, otherwise electrical noise (external static) could cause product malfunction. WARNING
• Make sure that the screws of the terminal are not loose.
Installation of indoor unit
• Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the head of the screw might be damaged, and the screw will not be properly tightened. • If the terminal screws are tightened too hard, screws might be damaged. 3. Do not connect wires of different gauge to the same grounding terminal. Loose connection may deteriorate protection. 4. At the unit, keep proper distance between transmisson and power supply wiring. The equipment may malfunction if subjected to electrical (external) noise. 5. Never connect power supply wiring to the terminal block for remote controller wiring. A mistake of this sort could damage the entire system. 6. Use only specified wire and tightly connect wires to terminals. Be careful that wires should not place external stress on terminals. Keep wiring in neat order and so as not to obstruct other equipment such as popping open the electric parts box cover. Make sure the cover closes tight. Incomplete connections could result in overheating, and in worst case, electric shock or fire.
Ceiling Cassette
131
Safety precautions
5CST2-06A
4. Installation of outdoor unit 4.1 Safety precautions Please strictly follow the instructions given in the Installation manual .Improper installation by ignoring the instructions can lead to damage of life and property. Make sure to read the following safety instructions very carefully and throughly .
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage to properties.
■ The meanings of the symbols used in this manual are as shown below.
Be sure not to do. Be sure to follow the instructions.
WARNING Do not use a defective or underrated circuit breaker. • There is risk of fire or electric shock. Do not use a multi consent. Always use this appliance on a dedicated circuit and breaker. • Otherwise it can cause electric shock or fire. For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service center. Do not disassemble or repair the product by yourself. • There is risk of fire or electric shock. Always ground the product as per the wiring diagram. Do not connect the ground wire to gas or water pipes lightening rod or telephone ground wire. • There is risk of fire or electric shock. Install the panel and the cover of control box securely. • There is risk of fire or electric shock due to dust , water etc. Use the correctly rated breaker or fuse. • There is risk of fire or electric shock. If the power cable or cord has scratches or skin peeled off or deterioted then immediately replace it. • There is risk of fire or electric shock. For installation, removal or reinstall, always contact the dealer or an authorized service center. • There is risk of fire, electric shock, explosion, or injury. Do not install the product on a defective foundation. Be sure that the installation area does not deteriorate with age. • If the foundation collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury. Never install the outdoor unit at a place from where it can fall down. • The falling outdoor unit can cause damage or injury or even death of a person and also damage or malfunctioning of the product itself. When the product is soaked (flooded or submerged) in water, contact an authorized service center for repair before using it again. • There is risk of fire or electric shock. In outdoor units the step up capacitor supplies high voltage electricity to the electrical components. Be sure to discharge the capacitor completely before conducting the repair work. • A charged capacitor can cause electrical shock.
132
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Safety precautions
Be sure to use only those parts which are listed in the svc parts list. Never attempt to modify the equipment. • The use of inappropriate parts can cause an electrical shock, excessive heat generation or fire. Indoor/outdoor wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable at the connection terminals. • Improper or loose connections can cause excessive heat heat generation or fire. Safely dispose off the packing materials. • Things like screws, nails, batteries, broken things etc after installation or svc can cause injury to small kids. Tear away and throw away the plastic packaging bags so that children will not play with them. Make sure to check that the power cable plug is not dirty, loose or broken, then only insert the plug completely. • Dirty,loose or broken power plug can cause electric shock or fire. During svc be sure to check the refrigerant to be used. • Incorrect refrigerant used can prevent the normal operation of the unit. When installing the unit, use the installation kit provided with the product. • Otherwise the unit may fall and cause severe injury . Do not touch, operate, or repair the product with wet hands. • There is risk of electric shock or fire. Do not place a heater or other appliances near the power cable. • There is risk of fire and electric shock. Do not allow water to run into electric parts. Install the unit away from water sources • There is risk of fire, failure of the product, or electric shock. Do not store or use or even allow flammable gas or combustibles near the product. • There is risk of fire or failure of product. If strange sounds, smell or smoke comes out from the product, immediately turn the breaker off or disconnect the power supply cable. • There is risk of electric shock or fire. Do not open the front grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) • There is risk of physical injury, electric shock, or product failure. Turn the main power off when cleaning or repairing the product. • There is risk of electric shock. When the product is not to be used for a long time, turn off the circuit breaker. • There is risk of product damage or failure, or unintended operation. Take care to ensure that nobody especially kids could step on or fall onto the outdoor unit. • This could result in personal injury and product damage.
Installation of outdoor unit
Ceiling Cassette
133
Safety precautions
5CST2-06A
CAUTION Use two or more people to lift and transport the product. • Avoid personal injury. Do not install the product where it is exposed to sea wind (salt spray) directly. • It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation. Keep level even when installing the product. • To avoid vibration or noise. Do not install the product where noise or hot air from the outdoor unit could damage or disturb the neighborhood. • It may cause a problem for your neighbors and hence dispute. Always check for gas (refrigerant) leakage after installation or repair of product. • Low refrigerant levels may cause failure of product. Do not block the inlet or outlet of air flow. • It may cause product failure. Do not step on or put anyting on the product. • There is risk of personal injury and failure of product. Do not insert hands or other objects through the air inlet or outlet while the product is operating. • There are sharp and moving parts that could cause personal injury. Be cautious when unpacking and installing the product. • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator. If the refrigerant gas leaks during the repair, do not touch the leaking refrigerant gas. • The refrigerant gas can cause frostbite (cold burn). Do not tilt the unit when removing or uninstalling it. • The condensed water inside can cause spill and wet the furniture and the floor. Do not mix air or gas other than the specified refrigerant used in the system. • If air enters the refrigerant system, an excessively high pressure results, causing equipment damage or injury. If the refrigerant gas leaks during the installation or operation, ventilate the area immediately. • Otherwise it can be harmful to your health. Do not expose your skin or kids or plants to the cool or hot air draft. • This could harm your health. Use a firm stool or ladder when cleaning, maintaining or repairing the product at a height. • Be careful and avoid personal injury. Dismantling the unit , treatment of the refrigerant oil, oil and eventual parts should be done in accordance with local and national standards.
134
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Safety precautions
4.1.1 Points for explanation about operation The items with WARNING and CAUTION marks in the operation manual are the items pertaining to possibillties for bodily injury and material damage in addition to the general usage of the product. Accordingly, it is necessary that you make a full explanation about the described contents and also ask your customers to read the operation manual.
4.1.2 Note to the installer Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different functions, and adjusting the temperature) by having them carry out operations themselves by looking at the manual.
4.1.3 Selecting installation site for outdoor units Select an installation site where the following conditions are fulfilled and that meets with your customer s approval. Location strong enough to bear the weight of the unit. Location accessible and having enough clearance for inspection and service in the future. Location allowing easy condensate drainage suitable gradient of the unit and the drain pipe. Piping between the indoor and outdoor unit is possible within the allowable limits. Location free from electrical noise. Location allowing optimum air distribution without any blocking to air flow. Location having no risk of flammable gas leakage. Location free from mineral oil mist or an oil spray or vapor eg in kitchen .It could result in leakage . Location free from corrosive gases such as sulphurous acid gas because it corrodes the copper pipes or soldered parts resulting in leakage . Location free from any machinery emitting electromagnetic waves which may disturb the control system thus causing malfunction of the unit . Location free from flammable gases , carbon fibre , or ignitable dust suspensions in the air or where volatile flames are handled like gasoline or thinner. Operating in such conditions may result in fire . Install the indoor and outdoor units, power supply wiring and connecting wires at least 1m. away from televisions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1m. may not be sufficient enough to eliminate the noise.) Consider whether the place where the unit will be installed can support the full weight of the unit, and reinforce it with boards and beams, etc. if needed before proceeding with the installation. Also, reinforce the place to prevent vibration and noise before installing. (The installation pitch can be found on the paper pattern for installation (3), so refer to it when considering the necessity for reinforcing the location.) Obey the local and national regulations and limits regarding airconditioner installation. Location free from lavatory (NH3.etc.). NH3 gas will cause corrosion of outdoor unit metallic parts.
Installation of outdoor unit
Ceiling Cassette
135
Safety precautions
5CST2-06A
4.1.4 For the following items, take special care during construction and check after installation is finished 1. Items to be checked after completion of work Unit
Items to be checked
If not properly done, what is likely to occur
Are the indoor and outdoor unit fixed firmly?
The units may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the name plate?
The unit may malfunction or the components burn out.
Are wiring and piping correct?
The unit may malfunction or the components burn out.
Is the unit safely grounded?
It may be dangerous at electric leakage.
Is wiring size according to specifications?
The unit may malfunction or the components burn out.
Is something blocking the air outlet or inlet of either the indoor or outdoor units?
It may result in insufficient cooling.
Are refrigerant piping length and additional refrigerant charge noted down?
The refrigerant charge in the system is not clear.
Check
CAUTION
• Be very careful about product transportation. Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous. • Safely dispose of the packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
NOTE
• Install the indoor and outdoor units, power supply wiring and connecting wires at least 1m. away from televisions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1m. may not be sufficient enough to eliminate the noise.)
136
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Safety precautions
4.1.5 Before installation • During product unpacking and removing it from the packing case, be sure to lift it without exerting any pressure on other parts, especially, horizontal flaps, the refrigerant piping, drain piping, and other resin parts. • Be sure to remove a cushion (corrugated paper) located between the heat exchanger and the right air filter. • Be sure to check the type of R22 refrigerant to be used before installing the unit. (Using an incorrect refrigerant will prevent normal operation of the unit.) • The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them! • Decide upon a line of transport. • Leave the unit inside its packaging while moving, until it reaches the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit. • For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit. • When using the wireless remote controller, refer to the installation manual attached to the wireless remote controller. • Entrust installation to the place of purchase or an authorized serviceman. Improper installation could lead to leaks and in worst cases, electric shock of fire. • Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could cause the unit to fall out of place, or could lead to leaks and, in the worst cases, electric shock or fire.
Installation of outdoor unit
Ceiling Cassette
137
Safety precautions
5CST2-06A
4.2 Introduction This installation guidance describes the procedures for outdoor unit installation, piping, wiring, and control between outdoor units, indoor units and controller. Installation of the indoor units is not described in this part. Please refer to the installation guidance manual which is supplied with indoor units for their respective installation.
4.2.1 Lifting method Always lift the unit with ropes attached at four points so that impact is not applied to the unit. Attach the ropes to the unit at an angle of 40째 or less. Use two ropes at least 7 m long.
4.2.2 Inspecting and handling the unit At the time of delivery, the package should be checked for any damage from out side and inside, If damaged then it should be reported to the carrier claims agent immediately . When handling the unit refer to following cautions: Handle the unit with care. Keep the unit upright in order to avoid inside components damage.
CAUTION
Be very careful when carrying the product. PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous. Do not touch heat exchanger fins with your bare hands. Otherwise you may get cut. Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
If a forklift is to be used it should pass the forklift arms through the openings at the bottom of the unit. If a crane is used, lift the unit preferably with 2 ropes of at least 7m length. When lifting the unit with a crane, always use protectors to prevent belt damage and pay attention to the position of the unit's center of gravity. Bring the unit in original package to prevent damage during local transport.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it.
138
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Foundation
4.3 Foundation LT-H548DLE1, LT-H548DLE2, LT-C548DLE1, LT-C548DLE2, LT-H488DLE1, LT-C488DLE1 <Basic intensity> Bolt Factor Concrete height Bolt inserted depth
M10-J type 100mm or more 70mm or more
460mm or more
550mm
LT-H368DLE1, LT-C368DLE1 <Basic intensity> Bolt Factor Concrete height Bolt inserted depth
M10-J type 100mm or more 70mm or more
100mm or more
550mm
360mm or more
546mm
370mm or more
LT-H286HLE1, LT-C286HLE1 <Basic intensity> Bolt Factor Concrete height Bolt inserted depth
M10-J type 100mm or more 70mm or more 100mm or more
LT-H246HLE1, LT-C246HLE1 <Basic intensity> Bolt Factor Concrete height Bolt inserted depth
M10-J type 100mm or more 70mm or more 100mm
546mm
370mm or more
639mm
322mm or more
LT-H186ELE1, LT-C186ELF1 LT-H186ELF1, LT-C186ELE1 <Basic intensity> Bolt Factor Concrete height Bolt inserted depth
M10-J type 100mm or more 70mm or more 100mm
Installation of outdoor unit
Ceiling Cassette
139
Settlement of the outdoor unit
5CST2-06A
4.4 Settlement of the outdoor unit Anchor the outdoor unit with a bolt and nut tightly and horizontally on a concrete or rigid mount. When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake. In the case when the vibration of the unit is conveyed to the house, secure the unit with an anti-vibration rubber.
Bolt construction work Mechanical anchor bolt
Foundation bolt
M10
Nut
Size M10 Count 4EA
75
60~120
Frame
Settlement draw of outdoor units
Bolt
Tubing connection
CAUTION
• The ingredients of foundation : Cement : Sand : Gravel for the concrete should 1 : 2 : 4 ratio • The foundation surface should be finished with mortar. • The edges of foundation should be rounded. • A drain passage should be made around the foundation to thoroughly drain water away from the equipment installation area. • If installing the outdoor units on the roof, the roof's strength have to be checked. • Care should be taken for weather - proofing • Blocking all gaps of outdoor unit, for passing piping and wiring, using sealing material (Field supply) (Animals and bugs might enter the machine.)
140
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Selection of the best location
4.5 Selection of the best location This unit is suitable for installation in a residential and commercial environment situation. If installed near a household appliance it can cause electromagnetic interference. The units should be installed in a location that meets the following requirements: A robust and strong base which can support the weight of the unit and will not degrade easily If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that the discharge air of the condenser is not restricted. It is recommended that the outdoor unit should be fenced to avoid animals or plants being exposed in the direct path of the discharged air . Ensure proper spaces between the unit and its surrounding as given in the figure. Ensure that the water shall not cause any damage by overflowing in case of water condensation The noise, vibration and hot discharged air of the outdoor unit should not annoy the surrounding environment. Ensure that there is no damage to the pipes in the long run as it may cause refrigerant leakage. In case the outdoor may have heavy snow : a. Make foundation at a suitable height. b. Fit a suitable hood or a awning over the unit. Rooftop Installations : If the outdoor unit is installed on a roof, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Installation of outdoor unit
Ceiling Cassette
141
Clearance space
5CST2-06A
4.6 Clearance space 4.6.1 Clearance around outdoor unit
300 mm or more
300 mm or more 300 mm or more
Su
nro
of
Fe ob nce sta or cle s
300 100 mm or more
More than 50cm (Service space)
500 mm or more (Service space)
â&#x20AC;˘ Ensure that the space around the back is more than 300 mm on the opposite to the PCB side and secure 500 mm space near the compressor and PCB side of the airconditioner for service.
142
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Clearance space
Clearance of side discharge unit (Unit:mm) 1) Where there is an obstacle on the air intake side: ■ No obstacle above • Obstacle on the suction side only
• Obstacle on both the sides
30
0o
ore rm 0o 10
rm
ore 60
0o
■ Obstacle above, too • Obstacle on the air intake side, too
rm
ore
or
ss
s les
1000 or more
r le
0o
1000 or more
• Obstacle on the air intake side, and both sides 500
50
ore
rm
0o
10
30
0o
rm
ore
0 10
ore
m or
60
0o
rm
0o
rm
ore
15
ore
2) Where there is an obstacle on the discharge side:
s les
■ Obstacle above, too
ore
rm
0o
50
1000 or more
■ No obstacle above
or
0 50
3) Where there are obstacles on both suction and discharge sides:
0 50
or
re
mo
■ Where the obstacles on the discharge side is higher than the unit: • No obstacle above
ore
rm
0o
ore
rm
0o
50
• Obstacle above, too The relations between H, A and L are as follows: 0 < L ≤ 1/2H
750
1/2H < L
1000
ss
or le
1000 or more
A
500
L
L≤H
L
10
Set the stand as: L ≤ H
Close the bottom of the installation frame to prevent the discharged air from being bypassed.
Installation of outdoor unit
Ceiling Cassette
ore
rm
0o
20
H
H<L
A
143
Clearance space
5CST2-06A
■ Where the obstacles on the discharge side is lower than the unit: • No obstacle above
ore
rm
0o
• Obstacle above, too The relations between H, A and L are as follows: 0 < L ≤ 1/2H
100
1/2H < L
200
H<L
ss
r le
0o
50
1000 or more
A
Set the stand as: L ≤ H
H
L≤H
L
ore
rm
0o
50
10
L
Close the bottom of the installation frame to prevent the discharged air from being bypassed. ore
A
rm
o 00
5
4) Series installation
0 10 00
10
0 50
or
or
or
re
mo
re
mo
re
mo
[Example]
4.6.2 Air guide work In case the out door unit is located in the outdoor cabin of apartment or flats, then the efficiency may drop and system pressure increases thus finally damaging the compressor or other components in the system by heat short circuit.
4.6.3 Lightning safety zone 1) To protect outdoor unit from lightning, it should be placed within lightning safety zone.
<Without air guide> Safety dorice activation Lightning rod
<With air guide> Normal operation
Lightning rod Protection Angle (25˚~55˚)
Safety zone
1.5m
Building Height [m]
20
30
45
60
Protection Angle [˚]
55
45
35
25
Regarding the safety from atmosphere electricity, follow the local or national regulations
2) Power cable and communication cable should be 1.5m away from lightning rod. 3) High resistance grounded system should be performed against induced lightning or indirect stroke. 4) If the building has no lightning protection, outdoor unit may be damaged from lightning. This should be informed to customer or building owner in advance.
Safe zone
Ground
144
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Outdoor unit piping
4.7 Outdoor unit piping 4.7.1 Outdoor unit piping Required tools
Screw Driver
Drill M/C f 3.5/F14.5
Measuring Tape, Blade
Core drill
Spanner
Torque Wrench
Soap Foam
Thermometer
Hook Meter
Multi Tester
Flare Set
Hexagonal wrench(4mm, 5mm)
4.7.2 Connecting piping 1) Align the center of the pipings and sufficiently tighten the flare out by hand.
2) Finally, tighten the flare nut with torque wrench until the wrench clicks. â&#x20AC;˘ When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Outdoor unit Gas pipe
Liquid pipe
Torque wrench
Installation of outdoor unit
Ceiling Cassette
145
Outdoor unit installation requirements
5CST2-06A
4.8 Outdoor unit installation requirements 4.8.1 Piping elevation and length
Max. 30m
Installaton irrespective of indoor, outdoor elevation
Model [Outdoor unit]
Max total piping length(m)
Standard length(m)
LT-H548DLE1, LT-H548DLE2 LT-C548DLE1, LT-C548DLE2
7.5
50
LT-H488DLE1, LT-C488DLE1
7.5
50
LT-H368DLE1, LT-C368DLE1
7.5
50
LT-H286HLE1, LT-C286HLE1
7.5
50
LT-H246HLE1, LT-C246HLE1
7.5
50
LT-H186ELE1, LT-C186ELF1 LT-H186ELF1, LT-C186ELE1
7.5
30
Refrigerant charge Indoor unit capacity (Btu/h)
Pipe size Liquid
Rated length
Additional refrigerant
Gas
54k
3/4"(19.05mm)
3/8"(9.52mm)
7.5m
60g/m
48k
3/4"(19.05mm)
3/8"(9.52mm)
7.5m
45g/m
36k
5/8"(15.88mm)
1/4"(6.35mm)
7.5m
50g/m
28k
5/8"(15.88mm)
1/4"(6.35mm)
7.5m
35g/m
24k
5/8"(15.88mm)
1/4"(6.35mm)
7.5m
35g/m
18k
1/2"(12.7mm)
1/4"(6.35mm)
7.5m
20g/m
CAUTION
Extra refrigerant = (Extended length - rated length) x additional refrigerant If total additional charge value after calculation comes out to be negative, then do not consider additional charge.
146
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Outdoor unit installation requirements
CAUTION
1. Regulation for refrigerant leakage : the amount of refrigerant leakage should satisfy the following equation for human safety. Total amount of refrigerant in the system
0.3 ( kg / m3 )
Volume of the room at which indoor unit of the least capacity is installed 2. If the above equation can not be satisfied, then follow the following steps. Selection of air conditioning system: select one of the followings. • Effective opening part Installation • Reconfirmation of outdoor unit capacity and piping length • Reduction of the amount or refrigerant • 2 or more security device installation of alarm for gas leakage Change indoor unit type : installation position should be over 2m from the floor Adoption of ventilation system : choose ordinary ventilation system or building ventilation system Limitation in piping work : design for earthquake-proof and prevention against thermal stress
Installation of outdoor unit
Ceiling Cassette
147
Outdoor unit installation requirements
5CST2-06A
4.8.2 Transmission and power cable connection 1) Example for the connection of transmission and power cable - No need of independent power supply for the indoor units. Power supply
Circuit breaker
Earth wire
Outdoor unit
Indoor unit
NOTE
*
148
: The 4 slashed lines represent 2 power line, 1 earth line and 1 transmission cable.
Ceiling Cassette
Installation of outdoor unit
5CST2-06A
Outdoor unit cabin
4.9 Outdoor unit cabin 4.9.1 Outdoor cabin louver requirement 1. Outdoor cabin type : Manual door open type 2. Louver angle : less than 15° on the horizontal base
Max15° (Recommended)
3. Louver interval: over 100mm (recommend) 4. Louver shape : wing type or plane type Louver
Over 100mm (Recommended)
Section CAUTION
• Opening rate and suction should be considered for louvered outdoor room. • Do not use 'S' type louver.
Outside
Noise can occur due to backward flow of the air passing through the louver blade
Inside
NOTE
The problem in case the louver opening rate is small. 1. Noise can occur due to increased velocity of the air passing through louver blade. 2. Noise can occur due to the louver blade vibrations. 3. Drop in outdoor fan performance (Excess static pressure damage can cause drop in the performance as well as outdoor heat exchange efficiency). 4. In case the louver opening rate is small or there is insufficient air flow exchange, it might stop the air conditioner.
Opening rate by louver radian W
h ho H
≤ 15° ho = h * COS Total face area(A) = H * W Number of open space (N) = (number of louver - 1) Effective face area(Af) = ho * W * N Louver opening rate (n) = Af/A Af = A * n Effective face area of cross section
Installation of outdoor unit
[Side view]
Ceiling Cassette
[Front view]
149
Outdoor unit cabin
5CST2-06A
4.9.2 Air flow rate confirmation Example. 1 ■ Application Model : AT-H126CLC0 [T11AHP SC0] Air flow rate 25CMM [Total opening rate] 1400mm 1200mm
1900mm
■ Case : velocity of discharging air: 5m/s, velocity of suction air: 2.5m/s
Air guide duct
540 mm
■ Openness rate = 80% or more ✻ Openness rate =
Effective face area(Af) Total face area(A)
■ Air guide of discharging air part should be equipped. 770mm
■ Louver total dimension (excluding frame) ■ Louver shielding dimension by product ■ Suction able louver dimension ■ Equivalent suction dimension (Opening rate 80%) ■ Equivalent suction air volume ■ Required air volume / equivalent voloume
(A) = 1.2 m x 1.9 m = 2.28 m2 (B) =0.77 m x 0.54 m = 0.42 m2 (A-B) = 1.86m2 = 1.86 m2 x 0.8 = 1.49 m2 = 1.49 m2 x 2.5 m/s x 60s/m = 223.5 CMM = 223.5 CMM / 25 CMM(product airflow rate) = 894 %
➡ OK
150
Ceiling Cassette
Installation of outdoor unit
Part 4 Spcial Guide 1. Installation guide at the seaside ......................................................152
Special guide
Ceiling Cassette
151
Installation guide at the seaside
5CST2-06A
1. Installation guide at the seaside CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit) 1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
Sea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
• It should be strong enough like concrete to prevent the sea wind from the sea. • The height and width should be more than 150% of the outdoor unit.
Sea wind
• It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
152
Ceiling Cassette
Special guide
P/No.: MFL33061302
Head Office: 20 Yoidodong, Youngdungpogu, Yoido P.O.Box 355 Seoul 150-721, Korea Phone:82-2-3777-7985
Changwon Office: 76 Seongsandong, Changwon, Gyeongnam 641-713, Korea Phone: 82-55-269-3506 http://www.lge.com/airconditioner All rights reserved Printed in Korea June/2007 The specifications, designs, and information in this brochure are subject to change without notice.
File No. : A8974 Volume:1
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 Certificate No. : certificate for environmental E00626/1 management system.