SPLIT SYSTEM RILE A - SAKB SERIES HIGH EFFICIENCY DUCTED SPLIT SYSTEM AIR CONDITIONERS HEAVY DUTY 50 HERTZ
The RILE A series is the latest introduction in the range of RHEEM's split airconditioners with the most reliable unit design available. All air handler models are only 11 - 19
• EXPANSION DEVICE - Capillary / Flow check orifice. • FILTERS - woven synthetic / Half inch aluminium(optional) permanent washable filters are standard on all units.
inches high. These units can be matched with all • INSULATION -
RHEEM condensing units.
5mm thick irradiated grade EPE, fire
retardent. Engineering Features • EVAPORATOR COIL Air Handler
grooved copper tubes and aluminium fins mechanically
• CABINET - Made from heavy gauge galvanized steel, and powder coated by electrostatic painting process. • MOT OR -
Coils are constructed with inner
Permanently
lubricated with
bonded to the tubes for maximum heat transfer capabilities. •
thermal
overload protection & ventilated type motors are mounted inside of insulated cabinet to reduce motor noise and provide a neat looking installation. • BLOWER - Double inlet, double width, forward curved aluminum/GI construction dynamically balanced for low noise & high performance.
REFRIGERANT
CONNECTIONS
-
Field
piping
connections, RILE 018 A to 030 A flare & RILE 036 A to 072 A sweat type, are made through side of the unit. • DRAIN PAN -
Insulated galvanized steel drain pan is
designed to trap condensate drain. • SE RVICE ACCESS- For RILE 036A to 072A removable panels at the bottom of the unit, can be easily removed for access to motor & blowers. For RILE 018A to 030A entire fan &
• LOW PROFILE - Allow for horizontal installation in most
motor section can be separated from the coil section by wing
standard drop ceiling application, and the movement of units
nuts for servicing and maintenance.
through most standard doorways for addition or replacement work.
• TESTING - All units are run tested at the factory prior to shipment.
Engineering Features Condensing Units
• Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.
The RHEEM Classic X High Efficiency SAKB -Condensing Unit was designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi-family and light commercial applications. The RHEEM Classic X SAKB - Condensing Units are the result of an ongoing development program for improved efficiencies. With SEER's ranging to 10.50, these units continue a tradition of high efficiency.
• Compressors have an internal pressure-relief assembly to protect against excessive pressure differential. • All refrigerant connections are on the exterior of the units, located close to the ground for neat appearing installations. • Cabinet is constructed of powder painted galvanized steel. The full wrap around louvered grille protects the coil from damage.This cabinet is also able to with stand 1000 hours of salt spray test.
• Attractive, louvered wrap-around jacket protects the coil from yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for all-weather protection.
• Copper Tube - Aluminium Fin coils are used on all models.
• Air is discharged upward away from bushes and shrubs. The discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.
• The control box is located in the top corner of the cabinet providing for easy access through a service panel. • Service valves are standard on all models.
• Exclusive Combination Grille/Motor Mount secures the motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.
• Power and control wiring are kept separate. • Every unit is factory charged and tested.
• All controls are accessible by removing one service panel. Removable top grille provides access to the condenser fan motor and condenser coil. • Single speed motor is designed for low speed, quiet energysaving operation. • All Units tested in accordance with A.R.I. standard
• Separate compressor compartment for easy service access. • Drawn, painted base pan for extra corrosion resistance and sound reduction. • H.P. Cutout safety control is a standard feature on all the models.
no.2-10-81-360-86
CONDENSING UNITS SAKB SERIES
DIMENSIONS AND OPERATING WEIGHT
AIR HANDLING UNITS RILE A SERIES
RILE - 018A/024A/030A
CONTROL BOX (RILE 018A&024A)
CONTROL BOX (RILE 030A)
C1
DRAIN
B
HEIGHT
DEPTH AIR DISCHARGE ALLOW 60º[1524 mm] CLEARANCE
C2 WIDTH (30 A) WIDTH (18A & 24A ONLY) ACCESS PANEL
RILE - 036A/042A/048A/060A/072A DEPTH A CONTROL BOX
HEIGHT
C1
B
ALLOW 24º[610 mm] ACCESS CLEARANCE
AIR INLETS (LOUVERS) ALLOW 12º[305 mm] MIN. CLEARANCE 3 SIDES
C2
FRONT VIEW
CONDENSING UNITS
Model
SAKB 018 SAKB 024 SAKB 030 SAKB 036 SAKB 042 SAKB 048 SAKB 060 SAKB 065
Height H (Inches) 17.0 17.0 19.0 19.0 19.0 23.0 23.0 23.0
DRAIN
C3 SIDE VIEW
AIR HANDLING UNITS
Length L (Inches) 36.0 36.0 36.0 41.0 41.0 44.0 44.0 44.0
Width W (Inches) 23.0 23.0 23.0 27.0 27.0 31.0 31.0 31.0
Weight (Lbs)
Model
Height
Depth
Width
A
B
C1
C2
C3
130 135 145 170 180 200 230 230
RILE 018A
11.0
21.0
47.0
33.0
4.7
1.40
1.00
--
65
RILE 024A
11.0
21.0
47.0
33.0
4.7
1.40
1.00
--
66
RILE 030A
12.0
26.5
41.0
34.0
6.6
1.40
1.00
--
68
RILE 036A
15.0
34.0
30.0
10.6
9.6
1.25
1.25
5.60
85
RILE 042A
17.5
34.0
30.0
13.5
11.0
1.00
1.60
4.40
90
RILE 048A
17.5
34.0
30.0
13.5
11.0
1.00
1.60
4.40
90
RILE 060A
19.0
33.0
30.0
12.6
11.8
0.73
2.00
4.90
110
RILE 072A
19.0
37.0
30.0
13.5
12.5
3.75
2.00
2.65
115
(Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches)
Weight (Lbs)
EVAPORATOR AIR ENTERING AIR TEMP
AMBIENT TEMP : 115 deg F
724
Note:
* **
FULL LOAD CURRENT
CIRCUIT BREAKER SIZE
For shipping weight, add 10 Lbs to net weight Power supply : 1-50-220/240 & 3-50-380/415
NET WEIGHT (Lbs)*
NUMBER OF FANS
COIL FACE AREA
ELECTRICAL DATA
POWER INPUT
**POWER SUPPLY
EXPANSION DEVICE
1.5
AIR HANDLING UNIT
2
AIR HANDLING UNIT
LBS 130
AIR HANDLING UNIT
CONDENSING UNIT
1 65
CONDENSING UNIT
NOS.
5.0
CONDENSING UNIT
SQ.FT
7.9
CONDENSING UNIT
AMPS
20 1.3
15
AIR HANDLING UNIT
AMPS
CONDENSING UNIT
AIR HANDLING UNIT
1.60
0.26 KW
AIR HANDLING UNIT
CONDENSING UNIT
1-50-220
1-50-220
CONDENSING UNIT
AIR HANDLING UNIT
1
47
45
43
0.10
130
66
1
2
5.0
1.8
7.9
1.3
20
15
1.60
0.26
1-50-220
1-50-220
1
1
48
46
44
0.10
800
559 600
665
11.40
14.40
12.40
15.40
12.50
16.30
13.60
17.40
SAKB 018
RILE 024A
523
1
PH-HZ-VOLTS
dbA
INCHES OF WC
CFM
11.10
13.20
TMBH SMBH
10.30
14.20
TMBH SMBH
11.50
SMBH
TMBH
NUMBER OF CIRCUITS FOR THE AIR HANDLING UNIT
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
76DB / 63 WB Deg F
80DB / 67 WB Deg F
76DB / 63 WB Deg F
11.60 15.00
SMBH
16.10
NUMBER OF COMPRESSORS
NOISE LEVEL(AHU)
ESP
AIR FLOW PERFORMANCE
EVAPORATOR AIR ENTERING AIR TEMP
AMBIENT TEMP : 95 deg F
TMBH
SAKB 018
80DB / 67 WB Deg F
RILE 018A
CONDENSING UNIT MODEL
135
66
1
2
6.1
1.8
10.0
1.3
20
15
2.00
0.26
1-50-220
1-50-220
1
1
48
46
44
0.10
800
724
665
15.30
18.20
15.70
19.50
16.70
20.60
17.20
22.00
SAKB 024
RILE 024A
145
68
1
2
9.1
2.4
11.9
1.3
25
15
2.40
0.26
1-50-220
1-50-220
1
1
49
47
45
0.10
1000
905
835
17.00
21.20
17.60
22.70
18.20
24.00
19.70
25.80
SAKB 030
RILE 030A
145
85
1
1
9.1
2.4
11.9
2.0
25
15
2.40
0.4
1-50-220
1-50-220
1
1
50
48
46
0.10
1200
1088
1029
17.80
22.40
19.40
23.90
19.70
25.40
22.00
27.10
SAKB 030
RILE 036A
TABLE FOR TECHNICAL DATA
AIR HANDLING UNIT MODEL
170
85
1
1
11.0
2.4
14.3
2.0
30
15
2.80
0.4
1-50-220
1-50-220
CAPILLARY
1
1
50
48
46
0.10
1200
1088
1029
22.40
26.80
23.30
28.80
24.80
29.50
25.70
32.50
SAKB 036
RILE 036A
170
90
1
1
11.0
4.7
14.3
2.5
30
15
2.80
0.5
1-50-220
1-50-220
1
1
51
49
47
0.20
1380
1265
1112
23.10
28.40
25.00
30.30
25.90
32.20
26.40
34.30
SAKB 036
RILE 042A
180
90
1
1
11.0
4.7
6.6
2.5
15
15
3.90
0.5
3-50-380
1-50-220
1
1
51
49
47
0.20
1380
1265
1112
24.90
29.60
25.40
32.00
26.40
34.20
27.10
36.70
SAKB 042
RILE 042A
180
90
1
1
11.0
4.7
6.6
2.5
15
15
3.90
0.5
3-50-380
1-50-220
1
1
53
51
49
0.20
1600
1441
1265
25.80
31.90
27.20
34.20
28.80
36.10
30.00
38.60
SAKB 042
RILE 048A
200
90
1
1
15.8
4.7
7.5
2.5
15
15
4.40
0.5
3-50-380
1-50-220
1
1
53
51
49
0.20
1600
1441
1265
29.50
35.50
30.30
37.90
32.30
40.20
33.10
42.90
SAKB 048
RILE 048A
230
110
1
1
15.8
7.5
8.8
2.5
15
15
5.20
0.5
3-50-380
1-50-220
1
1
55
53
51
0.20
2000
1930
1865
36.70
44.20
40.20
47.20
42.00
50.10
43.50
53.40
SAKB 060
RILE 060A
230
115
1
1
15.8
7.5
11.0
5
20
15
6.50
1.1
3-50-380
1-50-220
ORIFICE
1
1
58
56
53
0.20
2400
2335
2223
46.70
55.80
51.50
59.50
54.20
63.30
55.80
67.50
SAKB 065
RILE 072A
Condensing Unit Refrigerant Line Size Information Liquid Line Size System
Line
Model
Size
Numbers
(inch O.D.)
Outdoor Unit Below Indoor Coil
Total Length - Feet (m) 25 [7.26]
50 [15.24]
[mm] 018
Liquid Line Size
Outdoor Unit Above Indoor Coil
1/4* [6.35]
Total Length - Feet (m)
100 [30.48] 125 [38.10] 150 [45.72]
25 [7.62]
50 [15.24]
Vertical Separation - Feet [m] 25 [7.62]
50 [15.24]
5/16 [7.94] 1/4* [6.35]
75 [22.86]
25 [7.62]
75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]
Vertical Separation - Feet [m]
70 [21.34]
25 [7.62]
36 [10.97] 42 [12.80]
48 [14.63] 54 [16.46]
34 [10.36] 44 [13.41]
54 [16.46] 64 [19.51]
50 [15.24]
25 [7.62]
23 [7.01]
8[2.44] 36 [10.97]
30 [9.14]
24 [7.32]
18 [5.49]
38 [11.58]
28 [8.53]
18 [5.49]
8 [2.44]
39 [11.89]
25 [7.62]
11 [3.35]
23 [7.01]
024 5/16 [7.94] 1/4* [6.35] 030
24 [7.32] 25 [7.62]
5/16 [7.94]
50 [15.24] 19 [5.79]
25 [7.62] 33 [10.06] 47 [14.33]
3/8 [9.53] 5/16* [7.94]
48 [14.63]
61 [18.59]
50 [15.24]
11 [3.35] 25 [7.62]
50 [15.24]
70 [21.34]
25 [7.62]
50 [15.24]
75 [22.86]
25 [7.62]
44 [13.41]
53 [16.15] 61 [18.59]
23 [7.01]
15 [4.57]
57 [17.37] 25 [7.62]
23 [7.01]
25 [7.62]
23 [7.01]
25 [7.62]
28 [8.53]
9 [2.74]
036 3/8 [9.53] 5/16* [7.94]
34 [10.36] 40 [12.19]
46 [14.02] 52 [15.85]
38 [11.58]
32 [9.75]
26 [7.92]
20 [6.10]
40 [12.19] 33 [10.66]
26 [7.92]
19 [5.79]
9 [2.74]
042 3/8 [9.53] 3/8* [9.53]
32 [9.75]
39 [11.89]
46 [14.02] 53 [16.15] 70 [21.34]
19 [5.79]
11 [3.35]
3 [.91]
048 1/2 [12.7] 060
3/8* [9.53]
065
1/2* [12.7]
25 [7.62]
48 [14.63]
37 [11.28]
39 [11.89]
38 [11.58]
41 [12.50]
61 [18.59] 72 [21.95] 35 [10.67]
35 [10.67] 33 [10.06] 25 [7.62]
23 [7.01]
11 [3.35]
3 [.91] 37 [11.28] 34 [10.36] 31 [9.45]
*Standard line size
NOTES :
NOTES
1. This chart is applicable for condensing units. Example 1:A 2.5 ton [nom.] condensing unit with a total line length of 75 feet [22.86m] with a vertical separation of 30 feet [9.14m] requires a liquid line size of 5/16 [7.94mm]. 2. This chart may also be used to size horizontal runs. Example 2: A 5 ton [nom.] condensing unit may have a total horizontal run of 100 feet [30.48m] if using the 3/8 [9.53mm] liquid line. The total horizontal run of using 1/2 [12.7mm] liquid line size will be 150 feet [45.72m]. 3. Do not exceed vertical separation as indicated on the chart. 4. Always use the smallest liquid line possible to minimize system charge. 5. No changes required for flow-check pistons or expansion valve coils.
1. This chart is applicable for condensing units. 2. Do not exceed 120 feet [36.58m] maximum vertical separation, 3. No changes required for expansion valve coils. 4. Coils with flow-check pistons may require change of piston size,only incase of longer pipe lengths 5. Do not exceed table values for capillary tube coils. 6. Always use the smallest liquid line possible to minimize system charge. 7. Chart may be used to size horizontal runs.
Vapor Line Length / Size versus Capacity Multiplier System Model Numbers
018
024
-5/ " 8
Vapor Line Run-feet [m]
25' [7.62]
50' [15.24]
100' [30.48]
150' [45.72]
Optional Standard Optional Optional Standard Optional Optional Standard Optional Optional Standard Optional
[15.88 mm] O.D. Standard 3/ " [19.05mm] 4 O.D. Optional 1.00 1.01 .98 1.00 .96 .99 .97 .98
.98 1.00 1.01 .96 .99 1.00 .93 .98 .99 .97 .98
030
036
042
048
060/065
5/ " 8
[15.88mm] O.D Optional
7/ " 8
[22.23 mm] O.D. Optional
3/ " 4
[19.05mm] O.D. Standard
11 / " 8
[28.58mm] O.D. Standard
7/ " 8
[22.23 mm] O.D. Optional
13/ " 8
[34.94mm] O.D. Optional
1.00 1.01 .99 1.00 .97 .99 .95 .97
1.00 1.01 .98 1.00 .96 .99 .93 .97
1.00 1.01 .97 1.00 .94 .98 .90 .96
.99 1.00 1.01 .97 1.00 1.01 .96 .99 1.00 .93 .99 1.00
.98 1.00 1.01 .97 .99 1.01 .95 .99 1.00 .91 .98 .99
NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity. [ ] Designates Metric Conversions Additional compressor oil is not required for runs up to 150 feet [45.72 m]. Oil traps in vertical runs are not required for any height up to 100 feet [30.48 m]. See Liquid Line chart for Vertical Separat ion Requirements and Limitations.
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
RHEEM AIRCONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.
" In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice. "
FORM NO. M2-06-B3
SPLIT SYSTEM RIZE - SAKB SERIES DUCTED SPLIT SYSTEM AIR CONDITIONERS HEAVY DUTY 50 HERTZ
The RIZE Series is the latest introduction in the range of
• FILTERS - Woven synthetic, permanent washable filters are
RHEEM split airconditioners with the most reliable unit design
standard on all units. Optional - half inch aluminium washable
available. All air handler models are only 11 - 18 inches high.
filters.
These units can be matched with all the RHEEM's condensing units.
• INSULATION - 5mm thick irradiated grade EPE, fire retardent.
Engineering Features Air Handler
• EVAPORATOR COIL - Coils are constructed with inner grooved copper tubes and aluminium fins mechanically
• CABINET - Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are
bonded to the tubes for maximum heat transfer capabilities.
available optionally for use when units are to be installed
• REFRIGERANT
within conditioned space.
connections, sweat type, are made through side of the unit.
• MOTOR - Inherently protected, mounted on resilient
• DRAIN PAN - Insulated galvanized steel drain pan is
neoprene rubber mountings, to reduce noise level.
designed to trap condensate drain. The drain connections are
• BLOWER - Centrifugal, forward curved, double inlet double width type, made from heavy duty aluminium sheet.
• LOW PROFILE - Allow for horizontal installation in most standard drop ceiling application, and the movement of units through most standard doorways for addition or replacement work.
• EXPANSION DEVICE - Capillary
CONNECTIONS
-
Field
piping
on two sides of the unit to facilitate the site conditions for the convenience of installation.
• SERVICE ACCESS - Removable panels at the bottom of the unit, can be easily removed for access to motor & blowers. The entire fan and motor section can be separated from the coil section for servicing and maintenace.
• TESTING - All units are run tested at the factory prior to shipment.
Engineering Features Condensing Units
• Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.
The RHEEM Classic X High Efficiency SAKB -Condensing Unit was designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi-family and light commercial applications. The RHEEM Classic X SAKB - Condensing Units are the result of an ongoing development program for improved efficiencies. With SEER's ranging to 10.50, these units continue a tradition of high efficiency.
• Compressors have an internal pressure-relief assembly to protect against excessive pressure differential. • All refrigerant connections are on the exterior of the units, located close to the ground for neat appearing installations. • Cabinet is constructed of powder painted galvanized steel. The full wrap around louvered grille protects the coil from damage.This cabinet is also able to with stand 1008 hours of salt spray test.
• Attractive, louvered wrap-around jacket protects the coil from yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for all-weather protection.
• Copper Tube - Aluminium Fin coils are used on all models.
• Air is discharged upward away from bushes and shrubs. The discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.
• The control box is located in the top corner of the cabinet providing for easy access through a service panel. • Service valves are standard on all models.
• Exclusive Combination Grille/Motor Mount secures the motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.
• Power and control wiring are kept separate. • Every unit is factory charged and tested.
• All controls are accessible by removing one service panel. Removable top grille provides access to the condenser fan motor and condenser coil. • Single speed motor is designed for low speed, quiet energysaving operation. • All Units tested in accordanc with A.R.I. standard
• Separate compressor compartment for easy service access. • Drawn, painted base pan for extra corrosion resistance and sound reduction. • H.P. Cutout safety control is a standard feature on all the models.
no.2-10-81-360-86
DIMENSIONS AND OPERATING WEIGHT
AIR DISCHARGE ALLOW 60º[1524 mm] CLEARANCE
CONDENSING UNITS
Model
ACCESS PANEL
ALLOW 24º[610 mm] ACCESS CLEARANCE
AIR INLETS (LOUVERS) ALLOW 12º[305 mm] MIN. CLEARANCE 3 SIDES
SAKB 018 SAKB 024 SAKB 030 SAKB 036 SAKB 042 SAKB 048 SAKB 060 SAKB 065
Height H (Inches) 17.0 17.0 19.0 19.0 19.0 23.0 23.0 23.0
Length L (Inches) 36.0 36.0 36.0 41.0 41.0 44.0 44.0 44.0
Width W (Inches) 23.0 23.0 23.0 27.0 27.0 31.0 31.0 31.0
Weight (Lbs)
130 135 145 170 180 200 230 230
AIR HANDLING UNITS Model C E
AUXILIARY DRAIN PIPE
DRAIN PIPE G D
REFRIGERANT PIPE CONNECTIONS
PLAN
A
F
ELEVATION
B
R H SIDE VIEW
RIZE RIZE RIZE RIZE RIZE RIZE RIZE RIZE
018 024 030 036 042 048 060 A 072 A
A
B
C
D
E
F
G
(Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches)
35.9 35.9 35.9 42.6 42.6 42.6 44.0 44.0
10.9 10.9 10.9 15.0 15.0 15.0 18.0 18.0
24.7 24.7 24.7 28.9 28.9 28.9 28.9 30.9
34.8 34.8 34.8 41.4 41.4 41.4 42.8 42.8
9.7 9.7 9.7 10.4 10.4 10.4 10.4 10.4
7.5 7.5 7.5 9.4 9.4 9.4 9.4 9.4
33.3 33.3 33.3 40.1 40.1 40.1 41.1 41.1
Weight (Lbs) 49 50 51 92 95 97 113 114
RIZE 018/024/030/036/042/048/060A/072A
EVAPORATOR ENTERING AIR TEMP.
AMBIENT TEMP. 115 F 18.0
CIRCUIT BREAKER SIZE
POWER INPUT
FULL LOAD CURRENT
2
2
CONDENSING UNIT
LBS
130
130
1 50
1 49
CONDENSING UNIT
AIRHANDLING UNIT
NOS.
5.0
5.0
CONDENSING UNIT
AIRHANDLING UNIT
SQ. FT
7.9 1.5
7.9 1.5
0.6
0.6
15 20
15 20
CONDENSING UNIT
AMPS.
AMPS.
AIRHANDLING UNIT
AIRHANDLING UNIT
CONDENSING UNIT
AIRHANDLING UNIT
1.60
0.12
1.60
0.12
KW
AIRHANDLING UNIT
CONDENSING UNIT
1-50-220
1-50-220
1-50-220
1-50-220
CONDENSING UNIT
AIRHANDLING UNIT
* Optional power supply : 3-50-380/415 available.
NET WEIGHT
NUMBER OF FANS
COIL FACE AREA
DATA
ELECTRICAL
** POWER SUPPLY
EXPANSION DEVICE
PH - HZ - VOLTS
145
51
1
2
9.1
1.8
11.9
0.6
25
15
2.60
0.12
1-50-220
1-50-220
1
1
46
44
42
0.1
1000
905
835
14.9
20.8
15.4
22.3
16.0
23.9
16.6
25.2
SAKB 030
RIZE 030
145
92
1
2
9.1
2.9
11.9
2.0
25
15
2.60
0.40
1-50-220
170
92
1
2
11.0
2.9
14.3
2.0
30
15
2.83
0.40
1-50-220*
1-50-220
1
1
47
45
43
0.1
1200
1088
1029
20.5
26.3
21.3
28.5
22.6
30.2
23.5
32.3
SAKB 036
RIZE 036
CAPILLARY
1-50-220
1
1
47
45
43
0.1
1200
1088
1029
16.3
22.2
17.8
23.7
18.0
25.2
20.0
26.8
SAKB 030
RIZE 036
** Power Supply : 1-50-220/240 & 3-50-380/415
135
50
1
2
6.1
1.5
10.0
0.6
20
15
2.10
0.12
1-50-220
1-50-220
1 1
1 1
1 1
HIGH
MEDIUM
NUMBER OF COMPRESSORS
NOISE LEVEL (AHU)
NUMBER OF CIRCUITS FOR THE AIRHANDLING UNIT
41
41
40 43
0.1
0.1
0.1
45
800
800
600
43
665 724
665 724
523 559
45
dbA
INCHES WC.
CFM
13.9
14.3 10.4
10.0
13.1
SMBH
TMBH
19.3 14.5
11.3
14.2
9.4
14.1
TMBH
SMBH
15.6
11.5
10.5
SMBH
TMBH
42
LOW
SELECTED
HIGH
MEDIUM
LOW
76DB / 63WB F
80DB / 67WB F
76DB / 63WB F
16.0 21.3
12.4 16.1
10.6 14.9
SMBH
44
EXTERNAL STATIC PRESSURE
AIR FLOW PERFORMANCE
EVAPORATOR ENTERING AIR TEMP.
AMBIENT TEMP. 95 F
21.8
17.2
15.9
80DB / 67WB F
SAKB 024
SAKB 018
SAKB 018
TMBH
CONDENSING UNIT MODEL
RIZE 024
RIZE 024
RIZE 018
AIR HANDLING UNIT MODEL
TABLE FOR TECHNICAL DATA
170
95
1
2
11.0
3.1
14.3
2.4
30
15
2.83
0.48
1-50-220*
1-50-220
1
1
48
46
44
0.25
1350
1265
1112
22.2
28.8
22.9
30.7
23.7
31.7
25.8
33.8
SAKB 036
RIZE 042
180
95
1
2
11.0
3.1
6.6
2.4
15
15
3.90
0.48
3-50-380
1-50-220
1
1
48
46
44
0.2
1350
1265
1112
22.8
29.3
23.2
31.7
24.2
33.9
24.8
36.3
SAKB 042
RIZE 042
180
97
1
2
11.0
3.5
6.6
2.6
15
15
3.90
0.52
3-50-380
1-50-220
1
1
50
48
46
0.2
1650
1585
1490
23.8
31.6
25.0
33.8
26.6
37.3
27.5
38.2
SAKB 042
RIZE 048
200
97
1
2
15.8
3.5
7.5
2.6
15
15
4.40
0.52
3-50-380
1-50-220
1
1
50
48
46
0.2
1650
1585
1490
27.0
35.1
27.7
37.5
29.6
39.2
30.5
42.5
SAKB 048
RIZE 048
0.62
15
230
113
1
2
15.8
4.3
8.8
3.0
20
230
114
1
2
15.8
4.8
11.0
3.0
20
15
6.52
0.62 5.20
3-50-380
1-50-220
1
1
55
53
49
0.2
2420
2335
2223
42.7
55.2
47.1
58.9
49.6
62.7
51.1
66.8
SAKB 065
RIZE 072 A
3-50-380
1-50-220
1
1
52
50
48
0.2
2018
1930
1865
33.8
44.0
37.1
46.9
38.4
49.6
39.8
52.9
SAKB 060
RIZE 060 A
Condensing Unit Refrigerant Line Size Information Liquid Line Size System
Line
Liquid Line Size
Outdoor Unit Above Indoor Coil
Model
Size
Numbers
(inch O.D.)
SAKB
[mm]
Outdoor Unit Below Indoor Coil
Total Length - Feet (m)
1/4* [6.35]
25 [7.26]
50 [15.24]
75 [22.86]
Total Length - Feet (m)
100 [30.48] 125 [38.10] 150 [45.72]
25 [7.62]
50 [15.24]
Vertical Separation - Feet [m] 25 [7.62]
50 [15.24]
75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]
Vertical Separation - Feet [m]
70 [21.34]
25 [7.62]
23 [7.01]
8[2.44]
018 5/16 [7.94] 024
1/4* [6.35]
25 [7.62]
5/16 [7.94] 1/4* [6.35] 030
36 [10.97] 42 [12.80]
48 [14.63] 54 [16.46]
34 [10.36] 44 [13.41]
54 [16.46] 64 [19.51]
19 [5.79]
33 [10.06] 47 [14.33]
61 [18.59]
50 [15.24]
70 [21.34]
50 [15.24] 24 [7.32]
25 [7.62]
5/16 [7.94]
25 [7.62]
50 [15.24]
11 [3.35] 25 [7.62]
30 [9.14]
24 [7.32]
18 [5.49]
38 [11.58]
28 [8.53]
18 [5.49]
8 [2.44]
50 [15.24]
39 [11.89]
25 [7.62]
11 [3.35]
23 [7.01]
9 [2.74]
23 [7.01] 48 [14.63]
25 [7.62]
3/8 [9.53] 5/16* [7.94]
36 [10.97]
23 [7.01]
15 [4.57]
57 [17.37] 25 [7.62]
036 3/8 [9.53] 5/16* [7.94] 042
34 [10.36] 40 [12.19] 25 [7.62]
50 [15.24]
3/8 [9.53] 3/8* [9.53]
75 [22.86] 32 [9.75]
25 [7.62]
44 [13.41]
46 [14.02] 52 [15.85]
38 [11.58] 25 [7.62]
39 [11.89]
53 [16.15] 61 [18.59]
25 [7.62]
26 [7.92]
20 [6.10]
40 [12.19] 33 [10.66]
26 [7.92]
19 [5.79]
23 [7.01]
46 [14.02] 53 [16.15] 70 [21.34]
32 [9.75]
9 [2.74]
28 [8.53]
19 [5.79]
11 [3.35]
3 [.91]
048 1/2 [12.7] 060
3/8* [9.53]
065
1/2* [12.7]
25 [7.62]
48 [14.63]
37 [11.28]
39 [11.89]
38 [11.58]
41 [12.50]
61 [18.59] 72 [21.95] 35 [10.67]
35 [10.67] 33 [10.06] 25 [7.62]
23 [7.01]
11 [3.35]
3 [.91] 37 [11.28] 34 [10.36] 31 [9.45]
*Standard line size
NOTES :
NOTES
1. This chart is applicable for condensing units. Example 1:A 2.5 ton [8.79kW] condensing unit with a total line length of 75 feet [22.86m] with a vertical separation of 30 feet [9.14m] requires a liquid line size of 5/16 [7.94mm]. 2. This chart may also be used to size horizontal runs. Example 2: A 5 ton [17.58kW] condensing unit may have a total horizontal run of 100 feet [30.48m] if using the 3/8 [9.53mm] liquid line. The total horizontal run of using 1/2 [12.7mm] liquid line size will be 150 feet [45.72m]. 3. Do not exceed vertical separation as indicated on the chart. 4. Always use the smallest liquid line possible to minimize system charge. 5. No changes required for flow-check pistons or expansion valve coils.
1. This chart is applicable for condensing units. 2. Do not exceed 120 feet [36.58m] maximum vertical separation, 3. No changes required for expansion valve coils. 4. Coils with flow-check pistons may require change of piston size,only incase of longer pipe lengths 5. Do not exceed table values for capillary tube coils. 6. Always use the smallest liquid line possible to minimize system charge. 7. Chart may be used to size horizontal runs.
Vapor Line Length / Size versus Capacity Multiplier SAKB-
018
024
-5/ " 8
Vapor Line Run-feet [m]
25' [7.62]
50' [15.24]
100' [30.48]
150' [45.72]
Optional Standard Optional Optional Standard Optional Optional Standard Optional Optional Standard Optional
[15.88 mm] O.D. Standard 3/ " [19.05mm] 4 O.D. Optional 1.00 1.01 .98 1.00 .96 .99 .97 .98
.98 1.00 1.01 .96 .99 1.00 .93 .98 .99 .97 .98
030
036
042
048
060/065
5/ " 8
[15.88mm] O.D Optional
7/ " 8
[22.23 mm] O.D. Optional
3/ " 4
[19.05mm] O.D. Standard
11 / " 8
[28.58mm] O.D. Standard
7/ " 8
[22.23 mm] O.D. Optional
13/ " 8
[34.94mm] O.D. Optional
1.00 1.01 .99 1.00 .97 .99 .95 .97
1.00 1.01 .98 1.00 .96 .99 .93 .97
1.00 1.01 .97 1.00 .94 .98 .90 .96
.99 1.00 1.01 .97 1.00 1.01 .96 .99 1.00 .93 .99 1.00
.98 1.00 1.01 .97 .99 1.01 .95 .99 1.00 .91 .98 .99
NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity. [ ] Designates Metric Conversions Additional compressor oil is not required for runs up to 150 feet [45.72 m]. Oil traps in vertical runs are not required for any height up to 100 feet [30.48 m]. See Liquid Line chart for Vertical Separat ion Requirements and Limitations.
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
RHEEM AIRCONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.
" In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice"
FORM NO. R/S3-0106
RILE A - RAAB SERIES RILE A - SARB SERIES
HIGH EFFICIENCY,HIGH STATIC, DUCTED SPLIT SYSTEM AIR CONDITIONERS COOLING ONLY, HEAVYDUTY 50 HERTZ The RILE A Series is the latest introduction in the range of RHEEM split airconditioners with the most reliable unit design available. All air handler models are only 11 - 19 inches high. These units can be matched with all the RHEEM's condensing units.
Engineering Features Air Handler
• CABINET - Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are
• EXPANSION DEVICE - Capillary / Flow check orifice. • FILTERS - Woven synthetic, permanent washable filters are standard on all units. Optional - half inch aluminium washable filters.
• EVAPORATOR COIL- Coils are constructed with inner grooved copper tubes and aluminium fins mechanically bonded to the tubes for maximum heat transfer capabilities.
• REFRIGERANT CONNECTIONS - Field piping connections, sweat type, are made through side of the unit.
available optionally for use when units are to be installed within conditioned space.
• DRAIN PAN - Insulated galvanized steel drain pan is
• MOTOR - Inherently protected motors are mounted inside
designed to trap condensate drain.
of insulated cabinet to reduce motor noise and provide a neat
• SERVICE ACCESS - For RILE 036 A to 072 A removable
looking installation.
panels at the bottom of the unit, can be easily removed for
• LOW PROFILE - Allow for horizontal installation in most
access to motor & blowers. For RILE 018 A to 030 A entire fan
standard drop ceiling application, and the movement of units
and motor section can be separated from the coil section by
through most standard doorways for addition or replacement
wing nuts at four corners of the unit for maintenance.
work.
• TESTING - All units are run tested at the factory prior to shipment.
Engineering Features Condensing Units
• All refrigerant connection are on the exterior of the units, located close to the ground for neat appearing installation.
• Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor winding. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.
• Cabinet is constructed of galvanised steel with polyester powder coating for U.V radiation protection.
• Compressor has an internal pressure - relief assembly to protect against excessive pressure differential.
• The compressor and the control panel is located in separate compartment of the cabinet providing for easy access through service panels.
• Condenser fan motor, inherently protected and permanently lubricated type.
• Service valves are standard on all models.
• Metallic Condenser fan blades ensure safety & durability.
• Every unit is factory charged and tested.
• New design SARB version of low height condensing units for models 060 and 072 allow installation of units in the upper area of a balcony in any apartment. This gives clear space for normal use of the balcony
• H.P. & L.P. Safety controls are standard feature on all the models.
• Internally Grooved Copper Tube (IGT) - Aluminium Fin coils are used on all models.
• Heat Pump Optional, available under "UPAB" Model number.
DIMENSIONS AND OPERATING WEIGHT SARB 060 / 072
RAAB 018 / 024 / 030 / 036 / 042 / 048
RAAB 060 / 072 W
W
W D D
D PLAN PLAN PLAN
H H H
ELEVATION
ELEVATION
ELEVATION
RILE 018 A / 024 A / 030 A
RILE 036 A / 042 A / 048 A / 060 A / 072 A
CONTROL BOX (RILE 018 A & 024 A)
WIDTH
A
DEPTH
HEIGHT
B
DRAIN
A
DEPTH
C1
CONTROL BOX
HEIGHT
C1 (RILE 030 A)
B
C2 WIDTH (30 A)
WIDTH (18 A & 24 A ONLY)
C2
DRAIN
C3
FRONT VIEW
SIDE VIEW
CONDENSING UNITS
FRONT VIEW
SIDE VIEW
AIR HANDLING UNITS C3
RAAB 018 RAAB 024 RAAB 030 RAAB 036 RAAB 042 RAAB 048 RAAB 060 RAAB 072 SARB 060 SARB 072
21.0 21.0 21.0 27.0 27.0 27.0 50.0 50.0 32.0 32.0
13.0 13.0 13.0 16.0 16.0 16.0 16.0 16.0 30.0 30.0
33.0 33.0 33.0 40.0 40.0 40.0 40.0 40.0 44.0 44.0
RILE 018 A RILE 024 A RILE 030 A RILE 036 A RILE 042 A RILE 048 A RILE 060 A RILE 072 A RILE 060 A RILE 072 A
11.0 11.0 12.0 15.0 17.5 17.5 19.0 19.0 19.0 19.0
21.0 21.0 26.5 34.0 34.0 34.0 33.0 37.0 33.0 37.0
47.0 47.0 41.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0
33.0 33.0 34.0 10.6 13.5 13.5 12.6 13.5 12.6 13.5
4.7 4.7 6.6 9.6 11.0 11.0 11.8 12.5 11.8 12.5
1.40 1.40 1.40 1.25 1.00 1.00 0.73 3.75 0.73 3.75
1.00 1.00 1.00 1.25 1.60 1.60 2.00 2.00 2.00 2.00
---5.60 4.40 4.40 4.90 2.65 4.90 2.65
65 66 68 85 90 90 110 115 110 115
EVAPORATOR AIR ENTERING TEMP
AMBIENT TEMP : 115 deg F
15.26 11.83 12.86
11.57 13.50 10.29 11.38 9.88
SMBH TMBH SMBH TMBH SMBH
Note:
FULL LOAD CURRENT
CIRCUIT BREAKER SIZE
134
65 LBS
AIR HANDLING UNIT CONDENSING UNIT
1
2
AIR HANDLING UNIT
NOS.
CONDENSING UNIT CONDENSING UNIT
3.1x1.5R
1.5
AIR HANDLING UNIT SQ.FT
7.6
CONDENSING UNIT
AMPS
20 1.3
CONDENSING UNIT AIR HANDLING UNIT
15 AMPS
1.6
AIR HANDLING UNIT
134
66
1
2
3.1x1.5R
1.8
7.6
1.3
20
15
1.6
AIR HANDLING UNIT CONDENSING UNIT
0.26
0.26 KW
1-50-220
1-50-220
1-50-220
1-50-220
CONDENSING UNIT
* For shipping weight, add 10 Lbs to net weight ** Power supply : 1-50-220/240 & 3-50-380/415
NET WEIGHT (Lbs)*
NUMBER OF FANS
COIL FACE AREA
ELECTRICAL DATA
POWER INPUT
**POWER SUPPLY
AIR HANDLING UNIT
NUMBER OF CIRCUITS FOR THE AIR HANDLING UNIT
EXPANSION DEVICE
1
1
NUMBER OF COMPRESSORS
46
1
45
143
66
1
2
3.1x1.5R
1.8
10.5
1.3
20
15
2
0.26
1-50-220
1-50-220
1
1
48
46
150
68
1
2
3.1x2R
2.4
12.8
1.3
25
15
2.4
0.26
1-50-220
1-50-220
1
1
49
47
150
85
1
1
3.1x2R
2.4
12.9
2.0
25
15
2.4
0.4
1-50-220
1-50-220
1
1
50
48
179
85
1
1
6.2x1.5R
2.4
15.6
2.0
30
15
2.8
0.4
1-50-220
1-50-220
CAPILLARY
1
1
50
48
179
90
1
1
6.2x1.5R
4.7
15.8
2.5
30
15
183
90
1
1
6.2x2R
4.7
17.4
2.5
30
15
3.9
0.5
0.5 2.8
1-50-220
1-50-220
1
1
51
49
1-50-220
1-50-220
1
1
51
49
183
90
1
1
6.2x2R
4.7
17.8
2.5
30
15
3.9
0.5
1-50-220
1-50-220
1
1
53
51
185
90
1
1
6.2x2R
4.7
10.2
2.5
15
15
4.4
0.5
3-50-380
1-50-220
1
1
53
51
240/243
110
2
1
12.9x1.5R
7.5
11.7
2.5
15
15
5.2
0.5
3-50-380
1-50-220
1
1
55
53
51
0.2 49
0.2 49
0.2 47
0.2 47
0.2 46
0.10
46
0.10
45
0.10
44
0.10
44
0.10
43
0.10
1930 2000
1600
1441
1865
31.84
41.65
37.90
46.80
35.65
47.17
42.43
53.00
244/247
115
2
1
12.9x2R
7.5
12.7
5
20
15
6.5
1.1
3-50-380
1-50-220
ORIFICE
1
1
58
56
53
0.2
2400
2335
2223
40.07
49.47
45.10
55.40
42.35
55.96
50.15
62.70
RAAB 060/ RAAB 072/ SARB 060 SARB 072
1600
1441
1265
25.65
33.55
30.53
37.70
28.23
37.38
33.60
42.00
RAAB 048
1380
1265
1265
24.79
31.88
29.52
35.82
27.83
36.21
33.12
40.68
RAAB 042
1380
1265
1112
21.56
28.21
25.67
31.70
24.20
32.04
28.80
36.00
RAAB 042
1200
1088
1112
21.13
27.15
25.15
30.51
23.69
30.77
28.21
34.58
RAAB 036
1200
1088
1029
18.37
24.03
21.87
27.00
20.60
27.23
24.53
30.60
RAAB 036
1000
905
1029
17.84
22.92
21.24
25.03
19.78
25.64
23.55
28.82
RAAB 030
800
724
835
15.51
20.28
18.47
22.15
17.20
22.69
20.48
25.50
RAAB 030
800
724
665
12.25
16.02
14.57
18.00
13.83
18.24
16.46
20.50
RAAB 024
600
559
665
1
PH-HZ-VOLTS
dbA
INCHES OF WC
CFM
13.31
13.61
TMBH
523
14.75 15.38
12.83
SMBH
11.36
17.29
15.30
TMBH
48
HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
76DB / 63 WB Deg F
80DB / 67 WB Deg F
76DB / 63 WB Deg F
RAAB 018
RAAB 018
RILE 018A RILE 024A RILE 024A RILE 030A RILE 036A RILE 036A RILE 042A RILE 042A RILE 048A RILE 048A RILE 060A RILE 072A
47
NOISE LEVEL(AHU)
ESP
AIR FLOW PERFORMANCE
EVAPORATOR AIR ENTERING TEMP
AMBIENT TEMP : 95 deg F
80DB / 67 WB Deg F
CONDENSING UNIT MODEL
AIR HANDLING MODEL
TABLE FOR TECHNICAL DATA
System Model Numbers
018
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
024
030
036
042
048
060/072
5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.
" In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice. "
FORM NO. R/Z1-0601
SPLIT SYSTEM RIZE - RAAB SERIES RIZE - SARB SERIES DUCTED SPLIT SYSTEM AIR CONDITIONERS HEAVY DUTY 50 HERTZ
The RIZE Series is the latest introduction in the range of
• FILTERS - Woven synthetic, permanent washable filters are
RHEEM split airconditioners with the most reliable unit design
standard on all units. Optional - half inch aluminium washable
available. All air handler models are only 11 - 18 inches high.
filters.
These units can be matched with all the RHEEM's condensing units.
Engineering Features Air Handler
• CABINET - Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are available optionally for use when units are to be installed
• INSULATION - 5mm thick irradiated grade EPE, fire retardent. • EVAPORATOR COIL - Coils are constructed with inner grooved copper tubes and aluminium fins mechanically bonded to the tubes for maximum heat transfer capabilities.
• REFRIGERANT
CONNECTIONS
-
Field
piping
connections, sweat type, are made through side of the unit.
within conditioned space.
• DRAIN PAN - Insulated galvanized steel drain pan is • MOTOR - Inherently protected, mounted on resilient
designed to trap condensate drain. The drain connections are
neoprene rubber mountings, to reduce noise level.
on two sides of the unit to facilitate the site conditions for the
• BLOWER - Centrifugal, forward curved, double inlet double
convenience of installation.
width type, made from heavy duty aluminium sheet.
• SERVICE ACCESS - Removable panels at the bottom of
• LOW PROFILE - Allow for horizontal installation in most
the unit, can be easily removed for access to motor & blowers.
standard drop ceiling application, and the movement of units
The entire fan and motor section can be separated from the
through most standard doorways for addition or replacement
coil section for servicing and maintenace.
work.
• TESTING - All units are run tested at the factory prior to
• EXPANSION DEVICE - Capillary
shipment.
• New design SARB version of low height condensing units for models 060 and 072 allow installation of units in the upper area of a balcony in any apartment. This gives clear space for normal use of the balcony.
Engineering Features Condensing Units • Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor winding . It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.
• Cabinet is constructed of galvanised steel with polyester powder coating for U.V radiation protection. • Internally Grooved Copper Tube (IGT) - Aluminium Fin coils are used on all models.
• Compressor has an internal pressure - relief assembly to protect against excessive pressure differential.
• The compressor and the control box is located in separate compartment of the cabinet providing for easy access through service panels.
• Condenser fan motor, inherently protected and permanently lubricated type. • Metallic Condenser fan blades ensure safety & durability. • All refrigerant connection are on the exterior of the units, located close to the ground for neat appearing installation.
• Service valves are standard on all models.
• HP and LP controls are a standard feature on all the models
• Heat Pump Optional, available under 'RPAB' Model number.
• Every unit is factory charged and tested.
DIMENSIONS AND OPERATING WEIGHT RAAB 018 / 024 / 030 / 036 / 042 / 048
SARB 060 / 072
RAAB 060 / 072
W
W
W
D D
D
PLAN PLAN PLAN
H
H H ELEVATION
CONDENSING UNITS Model RAAB 018 RAAB 024 RAAB 030 RAAB 036 RAAB 042 RAAB 048 RAAB 060 RAAB 072 SARB 060 SARB 072
Height 'H' (Inches) 21 21 21 27 27 27 50 50 32 32
ELEVATION
Depth 'D' (Inches) 13 13 13 16 16 16 16 16 30 30
Width 'W' (Inches) 33 33 33 40 40 40 40 40 44 44
Weight (Lbs) 134 143 150 179 183 185 240 244 243 247
C E
AUXILIARY DRAIN PIPE
DRAIN PIPE G D
ELEVATION
AIR HANDLING UNITS Model RIZE RIZE RIZE RIZE RIZE RIZE RIZE RIZE
018 024 030 036 042 048 060 A 072 A
A
B
C
D
E
F
G
(Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches)
35.9 35.9 35.9 42.6 42.6 42.6 44.0 44.0
10.9 10.9 10.9 15.0 15.0 15.0 18.0 18.0
24.7 24.7 24.7 28.9 28.9 28.9 28.9 30.9
34.8 34.8 34.8 41.4 41.4 41.4 42.8 42.8
9.7 9.7 9.7 10.4 10.4 10.4 10.4 10.4
7.5 7.5 7.5 9.4 9.4 9.4 9.4 9.4
33.3 33.3 33.3 40.1 40.1 40.1 41.1 41.1
Weight (Lbs) 49 50 51 92 95 97 113 114
REFRIGERANT PIPE CONNECTIONS
PLAN
A
RIZE 018/024/030/036/042/048/060A/072A
F
ELEVATION
B
R H SIDE VIEW
EVAPORATOR ENTERING AIR TEMP.
AMBIENT TEMP. 115 F
FULL LOAD CURRENT
CIRCUIT BREAKER SIZE
1.5
1.5
2
2
AIRHANDLING UNIT
CONDENSING UNIT
LBS 134
** Power Supply : 1-50-220/240 & 3-50-380/415
134
1
50
1
49
CONDENSING UNIT
AIRHANDLING UNIT
NOS.
3.1x1R
3.1x1R
CONDENSING UNIT
SQ. FT
AIRHANDLING UNIT
0.6
0.6 7.6
20
20
15
1.60
7.6
AMPS.
AMPS.
15
1.60
CONDENSING UNIT
AIRHANDLING UNIT
CONDENSING UNIT
AIRHANDLING UNIT
CONDENSING UNIT
0.12
0.12
KW
1-50-220
1-50-220
CONDENSING UNIT
1-50-220
AIRHANDLING UNIT
PH - HZ - VOLTS
1-50-220
1
1
45
41
0.1
800
724
665
10.45
12.49
10.89
14.82
12.24
14.94
44
* Refer to installations and operation instructions for the full Air Flow Performance Data
NET WEIGHT ****
NUMBER OF FANS
COIL FACE AREA ***
DATA
ELECTRICAL
POWER INPUT
** POWER SUPPLY
AIRHANDLING UNIT
16.79 13.43
43
1
EXPANSION DEVICE
RIZE 024
RAAB 018
42
40
0.1
600
559
523
9.09
NUMBER OF CIRCUITS FOR THE AIRHANDLING UNIT
dbA
INCHES WC.
CFM
SMBH
9.47 11.15
TMBH
13.23
TMBH
SMBH
10.64
SMBH
13.34
TMBH
14.99 11.66
TMBH
SMBH
1
HIGH
MEDIUM
LOW
SELECTED
HIGH
MEDIUM
LOW
76DB / 63WB F
80DB / 67WB F
76DB / 63WB F
80DB / 67WB F
NUMBER OF COMPRESSORS
NOISE LEVEL (AHU)
EXTERNAL STATIC PRESSURE
*AIR FLOW PERFORMANCE
EVAPORATOR ENTERING AIR TEMP.
CONDENSING UNIT MODEL
AMBIENT TEMP. 95 F
RIZE 018
RAAB 018
AIR HANDLING UNIT MODEL RIZE 030
150
51
1
2
3.1x2R
1.8
12.8
0.6
25
15
2.40
0.12
1-50-220
1-50-220
1
1
46
44
42
0.1
1000
905
835
14.27
19.87
16.99
21.71
15.82
22.24
18.64
24.99
RAAB 030
RIZE 036
6.2x2R
2.9
12.9
2.0
25
15
2.40
0.40
1-50-220
150
92
1
2
RIZE 036
179
92
1
2
6.2x2R
2.9
15.6
2.0
30
15
2.80
0.40
1-50-220
1-50-220
1
1
47
45
43
0.1
1200
1088
1029
16.90
23.55
20.12
26.46
18.95
26.69
22.32
29.99
RAAB 036
CAPILLARY 1-50-220
1
1
47
45
43
0.1
1200
1088
1029
16.41
22.26
19.54
24.31
18.20
24.90
21.43
27.99
RAAB 030
*** Condr. Coil face area = 1R/1.5R/2R=No of rows
143
50
1
2
3.1x1.5R
1.5
10.5
0.6
20
15
2.00
0.12
1-50-220
1-50-220
1
1
45
43
41
0.1
800
724
665
11.27
15.70
13.40
17.64
12.72
17.88
14.98
20.09
RAAB 024
RIZE 024
TABLE FOR TECHNICAL DATA RIZE 042
179
95
1
2
6.2x2R
3.1
15.9
2.4
30
15
2.80
0.48
1-50-220
1-50-220
1
1
48
46
44
0.2
1350
1265
1112
19.44
26.38
23.14
29.64
21.79
29.89
25.67
33.59
RAAB 036
RIZE 042
183
95
1
2
6.2x2R
3.1
17.4
2.4
30
15
3.90
0.48
1-50-220
1-50-220
1
1
48
46
44
0.2
1350
1265
1112
19.84
27.65
23.62
31.07
22.26
31.40
26.21
35.28
RAAB 042
RIZE 048
RIZE 048
185
97
1
2
6.2x2R
3.5
10.2
2.6
15
15
4.40
0.52
3-50-380
1-50-220
1
1
50
48
46
0.2
1650
1585
1490
23.60
32.88
28.09
36.95
25.97
36.63
30.58
41.16
RAAB 048
240/243
113
2
2
12.9x1.5R
4.3
12.7
3.0
15
15
5.20
0.62
3-50-380
1-50-220
1
1
52
50
48
0.2
2018
1930
1865
29.29
40.82
34.87
45.86
32.80
46.23
38.61
51.94
244/247
114
2
2
12.9x2R
4.8
11.7
3.0
20
15
6.50
0.62
3-50-380
1-50-220
1
1
55
53
49
0.2
2420
2335
2223
38.85
48.51
41.57
54.32
39.07
54.87
45.76
61.48
RIZE 072 A
RAAB 072 / SARB 072
RIZE 060 A
RAAB 060 / SARB 060
**** For Shipping weight, add 10 lbs to the net weight
183
97
1
2
6.2x2R
3.5
17.8
2.6
30
15
3.90
0.52
1-50-220
1-50-220
1
1
50
48
46
0.2
1650
1585
1490
22.81
30.96
27.16
34.79
25.60
35.17
30.14
39.51
RAAB 042
Condensing Unit Refrigerant Line Size Information System
Line
Model
Size
Numbers
(inch O.D.)
018 018 024 024
Liquid Line Size Outdoor Unit Below Indoor Coil
Total Length - Feet (m) 25 [7.26]
50 [15.24]
25 [7.62]
50 [15.24]
25 [7.62]
50 [15.24]
[mm]
RAAB/SARB
Liquid Line Size Outdoor Unit Above Indoor Coil
75 [22.86]
5/16 [7.94] 1/4* [6.35]
030
1/4* [6.35]
030
5/16 [7.94]
50 [15.24]
25 [7.62]
23 [7.01]
36 [10.97] 42 [12.80]
25 [7.62]
23 [7.01]
24 [7.32] 25 [7.62]
5/16* [7.94]
34 [10.36] 44 [13.41]
54 [16.46] 64 [19.51]
33 [10.06] 47 [14.33]
61 [18.59]
25 [7.62]
50 [15.24]
50 [15.24]
048 048
3/8* [9.53]
060
3/8* [9.53]
072
1/2* [12.7]
32 [9.75] 44 [13.41]
53 [16.15] 61 [18.59]
25 [7.62]
48 [14.63]
61 [18.59] 72 [21.95]
1/2 [12.7]
18 [5.49]
38 [11.58]
28 [8.53]
18 [5.49]
8 [2.44]
39 [11.89]
25 [7.62]
11 [3.35]
70 [21.34]
38 [11.58]
9 [2.74] 38 [11.58]
32 [9.75]
26 [7.92]
20 [6.10]
40 [12.19] 33 [10.66]
26 [7.92]
19 [5.79]
23 [7.01]
46 [14.02] 53 [16.15]
37 [11.28]
35 [10.67]
24 [7.32]
23 [7.01]
46 [14.02] 52 [15.85] 25 [7.62]
25 [7.62]
30 [9.14]
57 [17.37] 25 [7.62]
39 [11.89]
36 [10.97]
15 [4.57]
75 [22.86]
3/8 [9.53]
8[2.44]
23 [7.01] 50 [15.24]
70 [21.34] 34 [10.36] 40 [12.19]
25 [7.62]
48 [14.63] 25 [7.62]
11 [3.35]
3/8 [9.53] 5/16* [7.94]
48 [14.63] 54 [16.46]
50 [15.24] 19 [5.79]
75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]
Vertical Separation - Feet [m]
70 [21.34]
3/8 [9.53]
042 042
25 [7.62]
Vertical Separation - Feet [m]
1/4* [6.35]
5/16 [7.94]
036 036
Total Length - Feet (m)
100 [30.48] 125 [38.10] 150 [45.72]
9 [2.74]
25 [7.62]
28 [8.53]
19 [5.79]
11 [3.35]
25 [7.62]
23 [7.01]
11 [3.35]
3 [.91]
39 [11.89]
3 [.91] 35 [10.67] 33 [10.06]
41 [12.50]
37 [11.28] 34 [10.36] 31 [9.45]
*Standard line size
NOTES :
NOTES :
1. This chart is applicable for condensing units. Example 1:A 2.5 ton [8.79kW] condensing unit with a total line length of 75 feet [22.86m] with a vertical separation of 30 feet [9.14m] requires a liquid line size of 5/16 [7.94mm]. 2. This chart may also be used to size horizontal runs. Example 2: A 5 ton [17.58kW] condensing unit may have a total horizontal run of 100 feet [30.48m] if using the 3/8 [9.53mm] liquid line. The total horizontal run of using 1/2 [12.7mm] liquid line size will be 150 feet [45.72m]. 3. Do not exceed vertical separation as indicated on the chart. 4. Always use the smallest liquid line possible to minimize system charge.
1. This chart is applicable for condensing units. 2. Do not exceed 120 feet [36.58m] maximum vertical separation, 3. No changes are required for expansion valve coils. 4. Do not exceed table values for capillary tube coils. 5. Always use the smallest liquid line possible to minimize system charge. 6. Chart may be used to size horizontal runs.
Vapor Line Length / Size versus Capacity Multiplier RAAB/SARB
018
024
-5/ ' 8
Vapor Line Run-feet [m]
25 ' [7.62]
50 ' [15.24]
100' [30.48]
150 ' [45.72]
Optional Standard Optional Optional Standard Optional Optional Standard Optional Optional Standard Optional
[15.88 mm] O.D. Standard 3/ ' [19.05mm] 4 O.D. Optional 1.00 1.01 .98 1.00 .96 .99 .97 .98
.98 1.00 1.01 .96 .99 1.00 .93 .98 .99 .97 .98
030
036
042
048
060/072
5/ ' 8
[15.88mm] O.D Optional
7/ ' 8
[22.23 mm] O.D. Optional
3/ ' 4
[19.05mm] O.D. Standard
11 / ' 8
[28.58mm] O.D. Standard
7/ ' 8
[22.23 mm] O.D. Optional
13/ ' 8
[34.94mm] O.D. Optional
1.00 1.01 .99 1.00 .97 .99 .95 .97
NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity.
1.00 1.01 .98 1.00 .96 .99 .93 .97
1.00 1.01 .97 1.00 .94 .98 .90 .96
.99 1.00 1.01 .97 1.00 1.01 .96 .99 1.00 .93 .99 1.00
.98 1.00 1.01 .97 .99 1.01 .95 .99 1.00 .91 .98 .99
[ ] Designates Metric Conversions
Additional compressor oil is not required for runs up to 150 feet [45.72 m]. Oil traps in vertical runs are not required for any height up to 100 feet [30.48 m]. See Liquid Line chart for Vertical Separat ion Requirements and Limitations.
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
RHEEM AIRCONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.
' In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice'
FORM NO. R-OS 9-05-A1
SPLIT SYSTEM RITD-OS,RAAB-OS SERIES 50 HERTZ DUCTED SPLIT SYSTEM AIR CONDITIONERS WITH CENTRIFUGAL OIL SEPARATOR
Engineering Features Condensing Units
Fan grille is steel reinforced for extra strength. Cabinet is powder painted for all-weather protection.
Copper Tube - Aluminium Fin coils are used on all models.
All controls are accessible by removing one service panel. Removable top grille provides access to the condenser fan motor and condenser coil.
Optional-Condenser coil fins from aluminium precoated corrosion resistant hydrophilic blue colour material for long life of condenser coil.
Single speed motor is designed for low speed, quiet energy-saving operation.
All refrigerant connections are on the exterior of the units, located close to the ground for neat appearing installations.
Compressor have an internal pressure-relief assembly to protect against excessive pressure differential. Compressor is hermetically sealed and incorporates internal high temperature motor overload protecion, and durable insulation on the motor windings. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise
Oil Separator
Services valves are standard on all models. Controls, HP cutout & LP cutouts are standard features. Power and control wiring are kept separate. Every unit is factory charged and tested.
Integral part of unit to suit high rise application
High efficiency (95%) centrifugal separation.
Internal oil collection screen.
Maximum working pressure, 450 psig
Hermetic welded or accessible bolted flange construction.
U.L. listed (file #5168)
Solid copper connection. Corrosion resistant paint.
C.S.A. listed (LR 100624)
Rated Capacity AIR HANDLING UNIT MODEL
RIZE*
018
CONDENSING UNIT MODEL RITD-OS/RAAB-OS O
AMBIENT AIR EVAPORATOR AIR ENTERING TEMP. O TEMP. 95 F
80DB / 67WB F O
76DB / 63 WB F O
AMBIENT AIR EVAPORATOR AIR ENTERING TEMP. O TEMP. 115 F
80DB / 67 WB F O
76DB / 63 WB F
TMBH SMBH TMBH SMBH TMBH SMBH TMBH SMBH
018 14.99 11.66 13.34 10.64 13.23 9.47 11.15 9.09
030
024 024 20.09 14.98 17.88 12.72 17.64 13.40 15.70 11.27
030 24.99 18.64 22.24 15.82 21.71 16.99 19.87 14.27
036
042
042
048
042
048
060
072
081
094
036 33.59 25.67 29.89 21.79 29.64 23.14 26.38 19.44
042
042 39.51 30.14 35.17 25.60 34.79 27.16 30.96 22.81
048 40.13 29.82 35.71 25.32 36.03 27.39 32.06 23.01
048 41.16 30.58 36.63 25.97 36.95 28.09 32.88 23.60
060 51.94 38.61 46.23 32.80 45.86 34.87 40.82 29.29
072 61.48 45.76 54.87 39.07 54.32 41.57 48.51 38.85
081 69.17 51.48 61.73 43.95 61.11 46.77 54.57 43.71
094 80.27 59.74 71.64 51.01 70.92 54.27 63.33 50.72
036
030 27.99 21.43 24.90 18.20 24.31 19.54 22.26 16.41
036 29.99 22.32 26.69 18.95 26.46 20.12 23.55 16.90
35.28 26.21 31.40 22.26 31.07 23.62 27.65 19.84
Condensing Unit Refrigerant Line Size Information System Model Numbers RITD-OS/RAAB-OS
50ft [15.24m] SL LL
Vapor line (SL) Size & Liquid Line (LL) Size 100ft [30.48m] 150ft [45.72m] 200ft [60.9m] SL LL SL LL SL LL
3/8"
5/8"
3/8"
3/4"
3/8"
3/4"
250ft [76.2m] SL LL
1/2"
7/8"
1/2"
300ft [91.44m] SL LL
018
5/8"
7/8"
1/2"
024
5/8"
3/8"
5/8"
3/8"
3/4"
3/8"
3/4"
1/2"
7/8"
1/2"
7/8"
1/2"
030
5/8"
3/8"
5/8"
3/8"
7/8"
3/8"
7/8"
1/2"
1 1/8"
1/2"
1 1/8"
1/2"
036
5/8"
3/8"
5/8"
3/8"
7/8"
3/8"
7/8"
1/2"
1 1/8"
1/2"
1 1/8"
1/2"
042
3/4"
3/8"
3/4"
3/8"
1 1/8"
5 /8"
1 1/8"
5/8"
1 1/8"
5/8"
1 1/8"
5/8"
048
7/8"
3/8"
7/8"
3/8"
1 1/8"
5 /8"
1 1/8"
5/8"
1 3/8"
5/8"
1 3/8"
5/8"
060
7/8"
3/8"
7/8"
3/8"
1 1/8"
3/4"
1 3/8"
3/4"
1 3/8"
3/4"
1 3/8"
3/4"
072
7/8"
3/8"
7/8"
3/8"
1 1/8"
3/4"
1 3/8"
3/4"
1 3/8"
3/4"
1 3/8"
3/4"
081
7/8"
5/8"
7/8"
5/8"
1 1/8"
3/4"
1 3/8"
3/4"
1 3/8"
3/4"
1 3/8"
3/4"
094
1 1/8"
3/4"
1 1/8"
3/4"
1 3/8"
3/4"
1 5/8"
3/4"
1 5/8"
3/4"
1 5/8"
3/4"
Capacity Multiplier 0.98
018 024
0.97 0.98 0.97 0.97 0.97 0.97 0.97
030 036 042 048
0.97 0.98 0.97 0.97 0.98 0.99
0.98 0.97 0.97 0.97 0.98 0.99
0.98 0.97 0.98 0.97 0.97 0.97
0.97 0.97 0.98 0.98 0.97 0.97
0.98 0.98 0.98 0.98
0.99 0.99 0.99 0.99
0.97 0.97 0.97 0.97
0.97 0.97 0.97 0.97
0.97 0.97 0.98 0.97 0.97 0.97
0.97 0.97 0.97 0.97 081 0.97 094 0.97 1. For condensing unit below the air handling unit, provide one inverted 'U' trap at the evaporator outlet in order to prevent liquid refrigerant going back to compressor during off cycle. 2. However it is recommended to provide 'U' trap after every 10 meter of pipe rise in case of condensing unit is above the evaporator 3. In case any pipe size not available it is recommended to use next higher pipe size. 060 072
DIMENSIONS AND OPERATING WEIGHT
H
W
CONDENSING UNITS RAAB-OS
CONDENSING UNITS RITD-OS
Model W Weight H D RAAB-OS (Inches) (Inches) (Inches) (Lbs)
Weight Model D W H RITD-OS (Inches) (Inches) (Inches) (Lbs.)
018 024 030 036 042 048 060 072
21 21 21 27 27 27 50 50
D
13 13 13 16 16 16 16 16
33 33 33 40 40 40 40 40
144 153 160 189 195 297 255 259
018 024 030 036 042 048 060 072 081 094
25.7 25.7 25.7 27.7 27.7 27.7 29.7 29.7 31.7 31.7
22.5 22.5 22.5 22.5 22.5 22.5 30.0 30.0 30.0 30.0
22.5 22.5 22.5 22.5 22.5 22.5 30.0 30.0 30.0 30.0
125 125 127 142 165 165 199 205 218 248
H
D
W
NOTES: Other air handlers RILE, RICD and SBHC can be used with these condensing units Capacity Multiplier x Rated Capacity = Actual Capacity.
Before proceeding with installation, refer RHEEM to installation instructions packaged with AIRCONDITIONING each model, as well as complying with DIVISION all Federal, State, Provincial, and Local codes, regulations, and practices. 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A. " In Keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice"