Heat Recovery Ventilator
0CZH9-02F(Replaces 0CZH9-02E)
General Description Ventilation is a process by which one can exchange indoor air to outdoor air in order to improve the air quality and to maintain environmental temperature conditions. LG’s heat recovery ventilation system, , modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly. can be controlled individually or integral with the air conditioning system. provides efficiency, cost savings, superior performance, compact & light design, linear E.S.P control ensuring vaious design of duct system and easy maintenance. Units are ideal for hotels, dormitories, restaurants, hospitals, retail establishments, theaters, schools, and office buildings. A lot of information regarding the design & installation of this system is provided in this publication. The new products series contains data on the same pattern. Please utilize all the information for conducting your business efficiently. Make sure the specification, dimension or others technical data are same as provided in engineering data book before you start the project. We look forward to your continuing support.
LG Electronics Inc. Air Conditioning Division
1
2
LG Airconditioners Product Data
Table of contents Table of contents
Page
1. Models List ...........................................................................................4 2. Model Number Nomenclature ...............................................................5 3. Feature & Benefits.................................................................................6 4. Specifications ......................................................................................14 5. Characteristic Curve............................................................................19 6. Dimensional Drawings.........................................................................24 7. Wiring Diagrams ..................................................................................29 8. External Static Pressure Settings........................................................33 9. Sound Pressure Level .........................................................................35 10. Installation .........................................................................................37 11. LCD Wired Remote Control(AZLRAD) ..............................................44
3
1. Models List 1.1 Total Heat Recovery Ventilator [50Hz] Nominal Capacity
Model Name
CMH(CFM)
Power Supply Ø,V,Hz
100(59)
LZ-H0106BA0
150(88)
LZ-H0156BA0
250(147)
LZ-H0256BA0
350(206)
LZ-H0356BA0
500(294)
LZ-H0506BA0
800(471)
LZ-H0806BA0
1000(589)
LZ-H1006BA0
1500(883)
LZ-H1506BA0
2000(1177)
LZ-H2006BA0
1Ø, 220-240V, 50Hz
[60Hz] Nominal Capacity
Model Name
CMH(CFM)
4
Power Supply Ø,V,Hz
150(88)
LZ-H0152BA0
500(294)
LZ-H0502BA0
800(471)
LZ-H0802BA0
1000(589)
LZ-H1002BA0
1500(883)
LZ-H1502BA0
2000(1177)
LZ-H2002BA0
1Ø, 220V, 60Hz
2. Model Number Nomenclature L Z - H 0 8 0 2 B A 0 Development Sequence Function A : Basic
Model Type B : Ceiling Concealed Type
Electric Standard (Volts / Freq. / Phase) 2 : 220V,60Hz,1Ø
6 : 220-240V,50Hz,1Ø
Capacity Ex) 080 -> 800 CMH 100 -> 1000 CMH
Heat Exchange Type H : Total Heat Recovery T : Sensible Heat Recovery
Indicates that this is LG’s
system
5
3. Features & Benefits The LG heat recovery ventilation system, improving your indoor air quality.
, is the solution for
Ventilation is a process by which one can exchange indoor air to outdoor air in order to improve the air quality and to maintain environmental temperature conditions. With today’s concern for a healthy indoor environment, is an integral component of HVAC system. Using in the HVAC system allows contaminants to be removed quickly and effectively from the airconditioned space. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load on the air conditioning system to be reduced significantly. Low-noise Design
Energy Savings
is accoustically engineered and tested for quiet operation. (ensuring comfort to be felt, not heard.)
The indoor air is passed through the heat exchanger to prewarm or precool the incoming outside air, saving energy and money.
Air Purifying
Easy Maintenance
Removing common pollutants from home which create an unhealthy environment.
The briefcase-style latches allows easy filter replacement and heat exchanger cleaning.
Efficiency & Comfort exhaust the polluted indoor air to outdoor and supply the fresh outdoor air to indoor in order to maintain the resident’s healthy and comfortable indoor environment.
6
3. Features & Benefits Healthy and Fresh Indoor Environmental Maintenance : Case of the window ventilation
(Indoor) 30˚C 26˚C
(Outdoor) EA
o
30 C
OA
In order to ventilate the indoor air is to open the window in summer. While opening the window, the conditioned indoor air goes out. Indoor air has to be cooling again.
Case of Enthalpy heat exchange ventilation
(Indoor) SA EA 27˚C
(Outdoor) o
30 C
25% Saving Energy
26˚C
When using the enthalpy heat exchanger,it maintains the temperature and humidity of the indoor and changes the polluted indoor air to the fresh outdoor air.
• Comparing to Enthalpy heat exchange ventilation with the window ventilation,Enthalpy heat exchange enables to economize a electric bill.It also helps the environmental protection due to saving energy.
Enthalpy Heat and Sensible Heat Exchangers Comparisons : • Enthalpy Heat Exchanger = Temperature heat (temperatures) + Latentheat (humidity)
• Sensible Heat Exchanger = Temperature heat (temperatures)
• The Enthalpy Heat Exchanger consists of Mechanism which is exchanged to the temperature heat (temperatures)as well as the latent heat (moisture heat capacity).When it calculates at the electric heat frequency quantity,it has an energy recovery effect above 3 times than the temperature heat.
7
3. Features & Benefits Reclaimed Energy Comparisons in Psychrometric Chart : Enthalpy heat exchanger
EA(Exhaust Air) OA(Outdoor Air) SA(Supply Air) RA(Return Air)
Temperature heat efficiency
Enthalpy heat efficiency
Latent heat efficiency
Temperature heat exchanger EA(Exhaust Air) OA(Outdoor Air) SA(Supply Air) RA(Return Air)
Enthalpy heat efficiency
Temperature heat efficiency
Latent heat efficiency
• Like appearing from the picture of the case only of the temperature heat exchange,the efficiency is high. But when it calculates at enthalpy heat frequency quantity,it has a difference above 3 times.
Zero Standby Power Consumption :
5~6W
- Due to SMPS (Switching Modulation Power Supply) technology, there is almost zero power consumption in the standby mode. It saves energy and cost.
0.5W Others
8
LG
3. Features & Benefits High Efficiency Heat Exchanger : - Cross flow heat exchanger ensure no mixing of the stale air with the fresh air. Efficiency and comfort is ensured by the high-efficiency energy recovery central core which recovers energy from the indoor air and transfers it to the fresh incoming air without mixing airstreams.The heat exchanger also helps to remove unwanted humidity from air inside your home during winter, and removes the humidity from the outside air before it enters your home in the summer.
Supply Air
Exhaust Air
Deodorization Filter
(Option)
High performance Filter Outdoor Air
Air Filter
Indoor Air
Air Filter
:(External Static Pressure Control) E.S.P Control M
H
L Air volume
- Individual air volume control (Supply&Exhaust). Generally, when External Static Pressure increases air volume decreases. But by controlling the phase of motor E.S.P. is controlled linearly. E.S.P. control provides required constant air volume irrespective of E.S.P. change. Desired E.S.P. can also be set through LCD wired remote. Setting of the desired E.S.P. gives required combination of ESP and airflow. So, air volume is kept constant for various duct work system. All units feature Phase control of Motor.
H M L
Air volume at 10 mmAq.
Air volume at 2 mmAq. 2
4
6
8
10
12
9
3. Features & Benefits Auto Operation : - Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the operating status of the air conditioner. • Total Heat Exchange Mode (Cooling operation in summer/ heating operation in winter)
• Bypass Mode (Intermediate season)
Damper Exhaust air
Return air
Outdoor air intake
Supply air
Damper Return air
Exhaust air
Supply air
Outdoor air intake
Flexibility of Installation : - Possibility of opposite installation of up and lower part Case of the installation of 2 units, generally it is necessary to two maintenance spaces. If it is installed opposite one unit of up and lower part, it is necessary to one maintencnce space. (1500/2000 CMH models are not available.) Maintenance space
Installation of 2 units
Top
Low
Low
Top
Opposite installation of up and lower part
Opposite Installation of up and lower part of one unit
Auto Restart Operation : - When there’s Electricity failure to the unit. After resumption of the Power, It starts in the same mode as prior to the power failure. This is as per the memorized condition. Any change will be memorized automatically to the MICOM & it takes about 2 secs to keep it.
Interlocking with Air Conditioning System : - It is able to install the ventilation system being interlocking with the air conditioning /heating system. It can be also controlled individually or integral with the air conditioning /heating system.
10
3. Features & Benefits Excellent Sound Arresting Blocking Effect : - The enthalpy heat exchanger element is difficult to convey the vibration of air with structure and it has a function of absorbing sounds.if it is installed a building in a serious noise place,it will be much more effective.
88.2dB(A)
42.9dB(A)
(45.3dB(A) Sound arresting blocking effect)
Collection Efficiency(%)
Air Filter : 100 80 60 40
Polyethylene
20 0
0
10
20
30
40
50
60
70
80
Dust Feed(g)
- Air filter has sufficient effects with collection efficiency above 80%, which is 0.3Âľm sample particle smaller than tobacco of smoke. It is even against floating particle from yellow sand. - Few pressure loss in the static pressure plan. - Excellent washing characteristic and durability.
External static pressure[pa]
High Efficiency Filter(Option) : 250 200 150 100 50 0 600
700
800
900
1000
1100
3
Air Volume[m /h]
Media : Poly propylene Frame : Paper
- Collection efficiency over 99%of an adopted law standard - Low-noise and reduction of power supplying cost - More multi-wind quantity than validity area - Not-melting processing with media pleated filter uniform
11
3. Features & Benefits LCD Wired Remote Control : (Accessory) EXTERNAL
- It can control all the functions of the unit. You can check and change operation mode, set timer & also diagnose the error of the unit. It also has the option of weekly program.
PLASMA
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH PLASMA
e-SAVER
fresh
Auto Lo
Auto Auto
Normal
Delay Time
Timer
SHi
Timer
Cancel
Week
fresh
OPERATION
SET TEMP Room Temp
Auto
Holiday Plasma
Min
Terminal block
Filter Time
Program set
Timer
Cancel
Program
Week
Hour
ZONE 1234
Sun Mon Tue Wed Thu
Fri
Sat
Auto
Holiday
FAN SPEED HI MED LO
Time
ZONE
TIME RESET
Min
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door 1 2 3 4
Operation unit No Func Program set 03
05
07
Timer
Cancel
2ndF
Program
Week
Holiday
Hour
Min
09
11
13
15
17
19
21
23
PLASMA
Set/Clr Hour
Heater Preheat Defrost Humidify
Plasma
On Off Set no. Time 01
Program
SHi
Set no. Timer
2ndF Timer
Sat
SUB FUNCTION Hi
Fan Speed
Set/Clr
ZONE 1234 Fri
Normal
Delay Time
fresh
Timer
Heater Preheat Defrost Humidify
Sun Mon Tue Wed Thu
Auto
fresh
AUTO SWING
SUB FUNCTION Hi
Fan Speed Filter Time
Program set
On Off Set no. Timer
e-SAVER
Auto Lo
Auto
On Off
- Built-in battery keeps user’s operating setup information for 2 hours when the main power line to the wired remote controller is disconnected due to power outage as well. - It can be installed with air conditioner remote controller, and each controller can control Ventilation and Air conditioner simultaneously. EXTERNAL
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH
Set/Clr
TIME RESET
Ventilation remote controller (PZRCUSB0)
AUTO SWING
RESET
OPERATION
SET TEMP Room Temp
2ndF Timer
FAN SPEED HI MED LO
Time
ZONE
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door 1 2 3 4
Operation unit No Func Program set
On Off Set no. Time 01
03
05
07
Timer
Cancel
2ndF
Program
Week
Holiday
Hour
Min
09
11
13
15
17
19
21
23
PLASMA
Set/Clr
AUTO SWING
RESET
OPERATION
SET TEMP Room Temp
2ndF Timer
FAN SPEED HI MED LO
Time
ZONE
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door 1 2 3 4
Operation unit No Func Program set
On Off Set no. Time 01
03
05
07
Timer
Cancel
2ndF
Program
Week
Holiday
Hour
Min
09
11
13
15
17
19
21
23
PLASMA
Set/Clr
AUTO SWING
RESET
OPERATION
SET TEMP Room Temp
2ndF Timer
FAN SPEED HI MED LO
Time
ZONE
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door 1 2 3 4
Operation unit No Func Program set
On Off Set no. Time 01
03
05
07
Timer
Cancel
2ndF
Program
Week
Holiday
Hour
Min
09
11
13
15
17
19
21
23
Maximum 8 connections are possible
PLASMA
Set/Clr RESET
Airconditioner remote controller (PCRCUSZ0/PDRCUSZ0)
Group Control :
1
2
- It operate maximum 16unit by only one wired remote controller and each units start sequentially to prevent overcurrent. All the units will follow same setting mode & other sub functions.
........
16
........ EXTERNAL
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH PLASMA
e-SAVER
fresh
Auto Lo
Auto Auto
Normal
SUB FUNCTION Hi
SHi
Heater Preheat Defrost Humidify
Fan Speed Filter Time
Delay Time
Timer
Program set
Sun Mon Tue Wed Thu
ZONE 1234 Fri
Sat
On Off Set no. Timer
Timer
Cancel
Program
Week
fresh
Auto
Holiday Plasma
Set/Clr Hour
Central Control : (Accessory) - It enables to control 16 x 8 = 128 units with the help of 8 controllers. All units can be put on and off from one Central Room. For Setting Temperature, Fan speed and other sub functions, access the LCD wired remote controller of each unit.
Min
Main PCB
Controller #1
12
TIME RESET
M 1
M 2
M 16
M 17
M 18
M 128
Sub 1
Sub 2
Sub 16
Sub 17
Sub 18
Sub 128
Controller #2
Controller #8
3. Features & Benefits Ventilation System + Multi V :
Indoor / Outdoor Communication Line Wired Remote Controller Line Ventilation Connected Control Line Central Control Line
Ethernet Remote Controller
LGAP Central Control System
Remote Controller
13
4. Specifications 4.1 50Hz Item Nominal Capacity Power Supply Step
eco-V Mode
Current
SH/H/L
LZ-H0106BA0
LZ-H0156BA0
LZ-H0256BA0
CMH(CFM)
100(59)
150(88)
250(147)
Ø,V,Hz
1, 220~240, 50
1, 220~240, 50
1, 220~240, 50
-
S-HIGH / HIGH / LOW
S-HIGH / HIGH / LOW
S-HIGH / HIGH / LOW
Amps
0.32/0.3/0.28
0.36/0.36/0.35
0.55/0.5/0.34
68/60/50
83/80/78
130/115/80
Power Input
SH/H/L
W
Air Flow
SH/H/L
CMH(CFM)
100/100/90(59/59/53)
150/150/100(88/88/59)
250/250/180(147/147/106)
External Static Pressure
SH/H/L
Pa(in.wg)
40/35/30(0.16/0.14/0.12)
70/55/45(0.28/0.22/0.18)
65/50/40(0.26/0.20/0.16)
%
78/78/80
75/75/79
80/80/85
%
68/68/70
62/62/69
70/70/78
Temperature Exchange Efficiency SH/H/L Enthalpy Exchange Efficiency Heating(SH/H/L) Cooling(SH/H/L) Noise Level(Sound Level, 1.5m) SH/H/L Step
Bypass Mode
Unit
%
58/58/60
55/55/59
64/64/68
dB(A)+3
28/26/20
32/30/22
32/28/21
-
-/-/-
-/-/-
-/-/-
Amps
-/-/-
-/-/-
-/-/-
Current
SH/H/L
Power Input
SH/H/L
W
-/-/-
-/-/-
-/-/-
Air Flow
SH/H/L
CMH(CFM)
-/-/-
-/-/-
-/-/-
External Static Pressure
SH/H/L
Pa(in.wg)
-/-/-
-/-/-
-/-/-
Temperature Exchange Efficiency SH/H/L
%
-/-/-
-/-/-
-/-/-
Enthalpy Exchange Efficiency
Heating(SH/H/L)
%
-/-/-
-/-/-
-/-/-
Cooling(SH/H/L)
%
-/-/-
-/-/-
-/-/-
dB(A)+3
-/-/-
-/-/-
-/-/-
-
Crossflow
Crossflow
Crossflow
Noise Level(Sound Level, 1.5m) SH/H/L Heat Exchanger
Type
Weight Dimension
W*H*D
Duct work*
Qty Size(Ø)
Supply Air Fan Exhaust Air Fan Filters
kg(lb)
23(50.70)
23(50.70)
24(52.91)
mm(inch)
590*204*590(23.23*8.03*23.23)
590*204*590(23.23*8.03*23.23)
596*320*640(23.46*12.60*25.20)
EA
4
4
4
mm(inch)
Ø100(Ø3.94)
Ø100(Ø3.94)
Ø150(Ø5.91)
Qty
EA
1
1
1
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
1
1
1
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
2
2
2
Type
-
Cleanable
Cleanable
Cleanable
Size(W*H*D) Packing Dimension
W*H*D
Stuffing Quantity
Without S/Parts
mm(inch)
580*10*113(22.83*0.39*4.45)
580*10*113(22.83*0.39*4.45)
590*10*175(23.23*0.39*6.89)
mm(inch)
850*280*760(33.46*11.02*29.92)
850*280*760(33.46*11.02*29.92)
850*405*760((33.46*15.94*29.92)
20/40ft
160/336
160/336
100/210
Notes: 1. eco-V mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.
14
4. Specifications Item Nominal Capacity Power Supply
eco-V Mode
Step
LZ-H0356BA0
LZ-H0506BA0
LZ-H0806BA0
350(206)
500(294)
800(470)
Ø,V,Hz
1, 220~240, 50
1, 220~240, 50
1, 220~240, 50
-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Current
SH/H/L
Amps
1.40/1.33/0.9
1.51/1.39/1.06
2.8/2.7/2.6
Power Input
SH/H/L
W
205/195/170
260/225/200
405/360/320
Air Flow
SH/H/L
CMH(CFM)
350/350/210(206/206/124)
500/500/320(294/294/124)
800/800/660(470/470/388)
External Static Pressure
SH/H/L
Pa(in.wg)
170/88/40(0.68/0.35/0.16)
150/60/28(0.60/0.24/0.11)
200/110/60(0.80/0.44/0.24)
Temperature Exchange Efficiency SH/H/L
%
83/83/87
75/75/79
79/79/82
Enthalpy Exchange Efficiency Heating(SH/H/L)
%
80/80/85
75/75/80
70/70/75 65/65/70
Cooling(SH/H/L) Noise Level(Sound Level, 1.5m) SH/H/L Step
Bypass Mode
Unit CMH(CFM)
%
78/78/83
70/70/75
dB(A)+3
33/28/23
34/32/25
36/34/30
-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Amps
1.40/1.33/0.9
1.51/1.39/1.06
2.8/2.7/2.6
Current
SH/H/L
Power Input
SH/H/L
W
205/195/170
260/225/200
405/360/320
Air Flow
SH/H/L
CMH(CFM)
350/350/210(206/206/124)
500/500/320(294/294/124)
800/800/660(470/470/388)
External Static Pressure
SH/H/L
Pa(in.wg)
170/88/40(0.68/0.35/0.16)
150/60/28(0.60/0.24/0.11)
200/110/60(0.80/0.44/0.24)
Temperature Exchange Efficiency SH/H/L
%
-
-/-/-
-/-/-
Enthalpy Exchange Efficiency
Heating(SH/H/L)
%
-
-/-/-
-/-/-
Cooling(SH/H/L)
%
-
-/-/-
-/-/-
dB(A)+3
33/28/23
34/32/25
36/34/30
-
Crossflow
Crossflow
Crossflow
Noise Level(Sound Level, 1.5m) SH/H/L Heat Exchanger
Type
Weight Dimension Duct work*
W*H*D Qty Size(Ø)
Supply Air Fan Exhaust Air Fan Filters
kg(lb)
38(83.8)
45(99.2)
63(139)
mm(inch)
988*273*1014(38.9*10.75*39.92)
988*273*1014(38.9*10.75*39.92)
1062*365*1140(41.9*14.4*44.9)
EA
4
4
4
mm(inch)
Ø200(7.87)
Ø200(Ø7.87)
Ø250(Ø9.54)
Qty
EA
1
1
1
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
1
1
1
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
2
2
2
Type
-
Cleanable
Cleanable
Cleanable
855*10*166(33.66*0.39*6.54)
855*10*166(33.66*0.39*6.54)
1056*10*212.5(41.57*0.39*8.37)
Size(W*H*D)
mm(inch)
Packing Dimension
W*H*D
mm(inch)
Stuffing Quantity
Without S/Parts
20/40ft
1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20) 1320*450*1350(51.97*17.72*53.15) 48/108
48 / 108
24 / 45
Notes: 1. eco-V mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.
15
4. Specifications Item Nominal Capacity Power Supply
eco-V Mode
Step
LZ-H1006BA0
LZ-H1506BA0
1000(588)
1500(882)
LZ-H2006BA0 2000(1177)
Ø,V,Hz
1, 220~240, 50
1, 220~240, 50
1, 220~240, 50
-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Current
SH/H/L
Amps
3.0/2.9/2.6
5.6/5.4/5.2
6.0/5.8/5.2
Power Input
SH/H/L
W
560/540/470
950/925/795
1020/970/860
Air Flow
SH/H/L
CMH(CFM)
1000/1000/800(588/588/470)
1500/1500/1200(882/882/706)
2000/2000/1600(1177/1177/941)
Pa(in.wg)
160/90/50(0.80/0.44/0.24)
200/110/60(0.80/0.44/0.24)
160/90/50(0.80/0.44/0.24)
Temperature Exchange Efficiency SH/H/L
%
75/75/78
79/79/82
75/75/78
Enthalpy Exchange Efficiency Heating(SH/H/L)
%
66/66/71
70/70/75
66/66/71
Cooling(SH/H/L)
%
61/61/66
65/65/70
61/61/66
dB(A)+3
37/35/31
39/37/33
39/37/33 SUPER-HIGH / HIGH / LOW
External Static Pressure
SH/H/L
Noise Level(Sound Level, 1.5m) SH/H/L
-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Current
SH/H/L
Amps
2.8/2.7/2.4
5.6/5.4/5.2
5.6/5.4/4.8
Power Input
SH/H/L
W
560/540/470
950/925/795
1020/970/860
Air Flow
SH/H/L
CMH(CFM)
1000/1000/800(588/588/470)
1500/1500/1200(882/882/706)
2000/2000/1600(1177/1177/941)
External Static Pressure
SH/H/L
Step
Bypass Mode
Unit CMH(CFM)
Pa(in.wg)
160/90/50(0.80/0.44/0.24)
200/110/60(0.80/0.44/0.24)
160/90/50(0.80/0.44/0.24)
Temperature Exchange Efficiency SH/H/L
%
-/-/-
-/-/-
-/-/-
Enthalpy Exchange Efficiency
%
-/-/-
-/-/-
-/-/-
%
-/-/-
-/-/-
-/-/-
Heating(SH/H/L) Cooling(SH/H/L)
Noise Level(Sound Level, 1.5m) SH/H/L Heat Exchanger
Type
Weight Dimension
W*H*D
Duct work*
Qty Size(Ø)
Supply Air Fan Exhaust Air Fan Filters
dB(A)+3
37/35/31
37/35/31
37/35/31
-
Crossflow
Crossflow
Crossflow
kg(lb)
63(139)
138(305)
138(305)
mm(inch)
1062*365*1140(41.9*14.4*44.9)
1313*737*1140(51.7*28.8*44.9)
1313*737*1140(51.7*28.8*44.9)
EA
4
4+2
4+2
mm(inch)
Ø250(Ø9.54)
Ø250(Ø9.54)+Ø350(Ø13.77)
Ø250(Ø9.54)+Ø350(Ø13.77)
EA
1
2
2
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
1
2
2
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
2
4
4
-
Cleanable
Cleanable
Cleanable
1056*10*212.5(41.57*0.39*8.37)
1056*10*212.5(41.57*0.39*8.37)
Qty
Type Size(W*H*D)
mm(inch)
1056*10*212.5(41.57*0.39*8.37)
Packing Dimension
W*H*D
mm(inch)
1320*450*1350(51.97*17.72*53.15) 1630*900*1330(64.17*35.43*52.36) 1630*900*1330(64.17*35.43*52.36)
Stuffing Quantity
Without S/Parts
20/40ft
24 / 45
8 / 18
8 / 18
Notes: 1. eco-V mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.
16
4. Specifications 4.2 60Hz Item Nominal Capacity Power Supply Step
eco-V Mode
Current
SH/H/L
LZ-H0152BA0
LZ-H0502BA0
LZ-H0802BA0
CMH(CFM)
150(88)
500(294)
800(470)
Ø,V,Hz
1, 220, 60
1, 220, 60
1, 220, 60
-
S-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Amps
0.5/0.48/0.42
1.25/1.07/0.9
3.1/3.0/2.5
100/95/77
258/235/195
585/555/470
Power Input
SH/H/L
W
Air Flow
SH/H/L
CMH(CFM)
150/150/90(88/88/53)
500/500/320(294/294/124)
800/800/660(470/470/388)
External Static Pressure
SH/H/L
Pa(in.wg)
70/50/25(0.281/0.200/0.100)
200/70/28(0.80/0.28/0.11)
200/110/60(0.80/0.44/0.24)
%
75/75/79
82/82/86
79/79/82
%
62/62/69
79/79/83
70/70/75 65/65/70
Temperature Exchange Efficiency SH/H/L Enthalpy Exchange Efficiency Heating(SH/H/L) Cooling(SH/H/L) Noise Level(Sound Level, 1.5m) SH/H/L Step
Bypass Mode
Unit
%
55/55/59
76/76/80
dB(A)+3
32/30/22
34/32/25
36/34/30
-
-/-/-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Amps
-/-/-
1.25/1.07/0.9
3.1/3.0/2.5
Current
SH/H/L
Power Input
SH/H/L
W
-/-/-
258/235/195
585/555/470
Air Flow
SH/H/L
CMH(CFM)
-/-/-
500/500/320(294/294/124)
800/800/660(470/470/388)
External Static Pressure
SH/H/L
Pa(in.wg)
-/-/-
200/70/28(0.80/0.28/0.11)
200/110/60(0.80/0.44/0.24)
Temperature Exchange Efficiency SH/H/L
%
-/-/-
-/-/-
-/-/-
Enthalpy Exchange Efficiency
Heating(SH/H/L)
%
-/-/-
-/-/-
-/-/-
Cooling(SH/H/L)
%
-/-/-
-/-/-
-/-/-
dB(A)+3
-/-/-
34/32/25
36/34/30
-
Crossflow
Crossflow
Crossflow
Noise Level(Sound Level, 1.5m) SH/H/L Heat Exchanger
Type
Weight Dimension
W*H*D
Duct work*
Qty Size(Ø)
Supply Air Fan Exhaust Air Fan Filters
kg(lb)
23(50.70)
45(99.2)
63(139)
mm(inch)
590*204*590(23.23*8.03*23.23)
988*273*1014(38.9*10.75*39.92)
1062*365*1140(41.9*14.4*44.9)
EA
4
4
4
mm(inch)
Ø100(Ø3.94)
Ø200(Ø7.87)
Ø250(Ø9.54)
Qty
EA
1
1
1
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
1
1
1
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
2
2
2
Type
-
Cleanable
Cleanable
Cleanable
855*10*166(33.66*0.39*6.54)
1056*10*212.5(41.57*0.39*8.37)
Size(W*H*D) Packing Dimension
W*H*D
Stuffing Quantity
Without S/Parts
mm(inch)
580*10*113(22.83*0.39*4.45)
mm(inch)
850*280*760(33.46*11.02*29.92)
20/40ft
160/336
1160*360*1275(45.67*14.17*50.20) 1320*450*1350(51.97*17.72*53.15) 48 / 108
24 / 45
Notes: 1. eco-V mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.
17
4. Specifications
Item Nominal Capacity Power Supply
eco-V Mode
Step
LZ-H1002BA0
LZ-H1502BA0
LZ-H2002BA0
CMH(CFM)
1000(588)
1500(882)
2000(1177)
Ø,V,Hz
1, 220, 60
1, 220, 60
1, 220, 60
-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Amps
3.5/3.4/2.9
6.2/6.0/5.0
7.0/6.8/5.8
Current
SH/H/L
Power Input
SH/H/L
W
660/500/400
1190/1151/960
1344/1306/1122
Air Flow
SH/H/L
CMH(CFM)
1000/1000/800(588/588/470)
1500/1500/1200(882/882/706)
2000/2000/1600(1177/1177/941)
External Static Pressure
SH/H/L
Pa(in.wg)
200/110/60(0.80/0.44/0.24)
200/110/70(0.80/0.44/0.28)
200/110/70(0.80/0.44/0.28)
%
75/75/78
75/75/78
75/75/78
Enthalpy Exchange Efficiency Heating(SH/H/L)
%
66/66/71
66/66/71
66/66/71
Cooling(SH/H/L)
%
61/61/66
61/61/66
61/61/66
dB(A)+3
37/35/31
39/37/33
42/38/33
-
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
SUPER-HIGH / HIGH / LOW
Temperature Exchange Efficiency SH/H/L
Noise Level(Sound Level, 1.5m) SH/H/L Step
Bypass Mode
Unit
Current
SH/H/L
Amps
3.5/3.4/2.9
6.2/6.0/5.0
7.0/6.8/5.8
Power Input
SH/H/L
W
660/500/400
1190/1151/960
1344/1306/1122
Air Flow
SH/H/L
CMH(CFM)
1000/1000/800(588/588/470)
1500/1500/1200(882/882/706)
2000/2000/1600(1177/1177/941)
External Static Pressure
SH/H/L
Pa(in.wg)
200/110/60(0.80/0.44/0.24)
200/110/70(0.80/0.44/0.28)
200/110/70(0.80/0.44/0.28)
Temperature Exchange Efficiency SH/H/L
%
-/-/-
-/-/-
-/-/-
Enthalpy Exchange Efficiency
Heating(SH/H/L)
%
-/-/-
-/-/-
-/-/-
Cooling(SH/H/L)
%
-/-/-
-/-/-
-/-/-
dB(A)+3
37/35/31
39/37/33
42/38/33 Crossflow
Noise Level(Sound Level, 1.5m) SH/H/L Heat Exchanger
Type
Weight Dimension
W*H*D
Duct work*
Qty
-
Crossflow
Crossflow
kg(lb)
63(139)
138(305)
138(305)
mm(inch)
1062*365*1140(41.9*14.4*44.9)
1313*737*1140(51.7*28.8*44.9)
1313*737*1140(51.7*28.8*44.9)
EA
4
4+2
4+2 Ø250(Ø9.54)+Ø350(Ø13.77)
mm(inch)
Ø250(Ø9.54)
Ø250(Ø9.54)+Ø350(Ø13.77)
Qty
EA
1
2
2
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
1
2
2
Type
-
Direct-Drive
Direct-Drive
Direct-Drive
Qty
EA
2
4
4
Type
-
Cleanable
Cleanable
Cleanable
Size(W*H*D)
mm(inch)
1056*10*212.5(41.57*0.39*8.37)
1056*10*212.5(41.57*0.39*8.37)
1056*10*212.5(41.57*0.39*8.37)
Packing Dimension
W*H*D
mm(inch)
1320*450*1350(51.97*17.72*53.15)
1630*900*1330(64.17*35.43*52.36) 1630*900*1330(64.17*35.43*52.36)
Stuffing Quantity
Without S/Parts
20/40ft
24 / 45
Size(Ø) Supply Air Fan Exhaust Air Fan Filters
8 / 18
8 / 18
Notes: 1. eco-V mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.
18
5. Characteristic Curve Model No. : LZ-H0106BA0 [Ventilation]
[Efficiency] 90 Exchange efficiency[%]
External static pressure[Pa]
150
100
High
Super-High
50
Temperature exchanger efficiency (Sensible Efficiency)
80
Enthalpy exchanger efficiency (Sensible Efficiency Heating)
70
60
Low
Enthalpy exchanger efficiency (Total Efficiency Cooling) 0
0
50
100
50
150
0
20
40
60
Air Volume[m3/h]
80
100
120
140
160
180
200
Air Volume[m3/h]
Model No. : LZ-H0152BA0 [Ventilation]
[Efficiency] 90 Exchange efficiency[%]
External static pressure[Pa]
200
150 Super-High 100 High
Enthalpy exchanger efficiency (Sensible Efficiency Heating)
70
60
Low
50
Temperature exchanger efficiency (Sensible Efficiency)
80
Enthalpy exchanger efficiency (Total Efficiency Cooling) 50
0 0
50
100
150
0
200
20
40
60
Air Volume[m3/h]
80 100 120 Air Volume[m3/h]
140
160
180
200
Model No. : LZ-H0156BA0 [Ventilation]
[Efficiency] 90
150
Exchange efficiency[%]
External static pressure[Pa]
200
Super-High High
100
Enthalpy exchanger efficiency (Sensible Efficiency Heating)
70
60
Low
50
Temperature exchanger efficiency (Sensible Efficiency)
80
Enthalpy exchanger efficiency (Total Efficiency Cooling) 50
0 0
50
100 Air Volume[m3/h]
150
200
0
20
40
60
80
100
120
140
160
180
200
Air Volume[m3/h]
19
5. Characteristic Curve Model No. : LZ-H0256BA0 [Ventilation]
[Efficiency] 100
250
Exchange efficiency[%]
External static pressure[Pa]
300
200 150 100 Super-High 50
Low
Temperature exchanger efficiency (Sensible Efficiency)
90
80
Enthalpy exchanger efficiency (Sensible Efficiency Heating)
70 Enthalpy exchanger efficiency (Total Efficiency Cooling)
60
High 50
0 0
50
100
150
200
250
300
350
0
400
50
100
150
200
250
300
350
400
Air Volume[m3/h]
Air Volume[m3/h]
Model No. : LZ-H0356BA0 [Ventilation]
[Efficiency]
400
90 Tem p efficie erature exch ncy a
Exchange efficiency[%]
External static pressure[Pa]
350 300 250
Super High
200 150
High 100
80
Enth
alpy
Enth
alpy
70
nge
exch
ange
exch
ange
efficie
ncy(H
eatin
efficie
g)
ncy(C
oolin
g)
60
Low 50 0 0
100
200 Air
300
400
500
50
600
0
100
200
300
Volume[m3/h]
400
500
600
700
Air Volume[m3/h]
Model No. : LZ-H0502BA0 [Ventilation]
[Efficiency]
400
90
300
Exchange efficiency[%]
External static pressure[Pa]
350 Super High
250
High
200 Low
150 100
80
Tem p efficie erature exch ncy a
nge
Enth
alpy
Enth
alpy
70
exch
exch
ange
ange
efficie
ncy(H
efficie
eatin
ncy(C
g)
oolin
g)
60
50 0 0
100
200
300
400
Air Volume[m3/h]
20
500
600
700
50 0
100
200
300
400
Air Volume[m3/h]
500
600
700
5. Characteristic Curve Model No. : LZ-H0506BA0 [Ventilation]
[Efficiency]
400
90 Exchange efficiency[%]
External static pressure[Pa]
350 300 250 Super High 200 150
High
Low
100
Tem effic perature ienc exch y
80
ange
Enth
alpy
Enth
alpy
70
exch
ange
exch
ange
efficie
ncy(H
effic
eatin
ienc
g)
y(Co
oling
)
60
50 0
50 0
100
200
300
400
500
600
0
700
100
200
300
Air Volume[m3/h]
400
500
600
700
Air Volume[m3/h]
Model No. : LZ-H0802BA0 / LZ-H0806BA0 [Ventilation]
[Efficiency] 90
Exchange efficiency[%]
External static pressure[Pa]
500
400
Super High
300
High
Low 200
Tem p effic erature ienc exch y an
tha
lpy
80
ge
exc
han
ge
En
effi
cie
tha
70
lpy
0
200
400
600
800
1000
1200
ncy
(He
exc
ha
atin
ng
g)
ee
ffic
ien
cy(
Co
60
100
0
En
olin
g)
50 0
200
400
600
800
1000
1200
Air Volume[m3/h]
Air Volume[m3/h]
Model No. : LZ-H1002BA0 [Ventilation]
[Efficiency] 90 Exchange efficiency[%]
External static pressure[Pa]
500
400 Super High 300
High Low
200
En
Tem effic peratur ienc e ex y cha
nge
tha
80
lpy
exc
han
ge
effi
cie
En
70
tha
lpy
ncy
(He
atin
g)
exc
han
ge
effi
cie
60
ncy
100
(Co
olin
g)
50
0 0
200
400
600 Air
800
Volume[m3/h]
1000
1200
1400
0
200
400
600
800
1000
1200
1400
Air Volume[m3/h]
21
5. Characteristic Curve Model No. : LZ-H1006BA0 [Ventilation]
[Efficiency] 90 Exchange efficiency[%]
500
External static pressure[Pa]
400 Super High 300
High Low
200
En
Tem effic peratu re e ienc xcha y
nge
tha
80
lpy
exc
han
ge
70
lpy
atin
g)
exc
ge
effi
cie
60
0 200
400
600
800
1000
1200
ncy
(He
tha
han
100
0
effi
cie
En
ncy (Co
olin
g)
50
1400
0
200
400
600
Air Volume[m3/h]
800
1000
1200
1400
Air Volume[m3/h]
Model No. : LZ-H1502BA0 / LZ-H1506BA0 [Ventilation]
[Efficiency]
500 Exchange efficiency[%]
90
External static pressure[Pa]
400
300 Super High
??
200
High ?
100
En
Tem effic peratu ienc re e xch y a
nge
tha
80
lpy
exc
ha
En
70
ng
ee
0
500
1000
1500
2000
cy(
He
atin
g)
xch
ang
ee
ffic
ien
cy(
?
0
ien
lpy e
60
Low
ffic
tha
Co
olin g)
50
2500
0
500
1000
1500
2000
2500
Air Volume[m3/h]
Air Volume[m3/h]
Model No. : LZ-H2006BA0 [Ventilation]
[Efficiency] 90
400
Exchange efficiency[%]
External static pressure[Pa]
500
Super High 300 High 200
Low
100
80
Ent
Tem p effic erature ienc exch y ang
e
halp
y ex
cha
70
nge
effic
ienc
En
y(H
tha
lpy
exc han g
ee
60
ffic
ien
cy(
eat
ing)
Co
olin
g)
0
50 0
500
1000
1500
Air Volume[m3/h]
22
2000
2500
0
500
1000
1500
Air Volume[m3/h]
2000
2500
5. Characteristic Curve Model No. : LZ-H2002BA0 [Ventilation]
[Efficiency] 90 Exchange efficiency[%]
External static pressure[Pa]
500
400 Super High 300 High 200 Low
80
Tem effic peratur e ex ienc chan y
ge
Ent
halp
70
En
ye
xch
ang
ee
fficie
ncy
tha
lpy
(He
atin
exc
han ge
effi
g)
cie
60 100
ncy
(Co
olin g
)
0
0
500
1000
1500
Air Volume[m3/h]
2000
2500
50 0
500
1000
1500
2000
2500
Air Volume[m3/h]
23
6. Dimensional Drawings Model No. : LZ-H0152BA0 / LZ-H0106BA0 / LZ-H0156BA0
G
H
J
A
Suspension Fixture Blower for supplying air L
Control Box
EA
SA Total Heat Exchanger K B E
Air Filter Blower for Exhausting Air
RA
OA
F
D
C
Unit: mm Model
LZ-H0106BA0 LZ-H0152BA0 LZ-H0156BA0
24
Pitch of Suspension Fixture
Figure A
B
C
D
E
F
590
590
204
504
624.2
64
Nominal Diameter
100
Duct Connection Flange
Duct Pitch
Weight
G
H
J
K
L
(kg)
97.5
160
90
402
93
23
6. Dimensional Drawings Model No. : LZ-H0256BA0
A
H
G
Air Filter
J
Total Heat Exchanger
Maintenance Cover
Control Box
Suspension Fixture
L
Blower for supplying air
K
Blower for Exhausting Air
E
RA
B
EA
SA
OA
C
D
F
Unit: mm Model
LZ-H0256BA0
Pitch of Suspension Fixture
Figure A
B
C
D
E
F
640
596
320
568
636.2
55
Nominal Diameter 150
Duct Connection Flange
Duct Pitch
Weight
G
H
J
K
L
(kg)
140
160
70
430
84
24
25
6. Dimensional Drawings Model No. : LZ-H0356BA0 / LZ-H0506BA0 / LZ-H0502BA0
Blower for Exhausting Air
Suspension Fixture
RA
OA
SA 50
EA
600
150~250
Blower for supplying air Control Box
Total Heat Exchanger Air Filter High Efficiency Filter Blower Maintenance space
Maintenance Cover
Maintenance space
Total Heat Exchanger
Suspension Fixture
Air Filter
Unit: mm Model A LZ-H0356BA0
26
Pitch of Suspension Fixture
Figure B
C
D
E
F
Nominal Diameter
Duct Connection Flange
Duct Pitch
Weight
G
H
J
K
L
(kg)
1013.6 988.2
271.6
938.8 1024.8
5.8
200
194
252
95.8
590
198
38
LZ-H0506BA0 1013.6 988.2 LZ-H0502BA0
271.6
938.8 1024.8
5.8
200
194
252
95.8
590
198
45
6. Dimensional Drawings Model No. : LZ-H0802BA0 / LZ-H1002BA0 / LZ-H0806BA0 / LZ-H1006BA0
Blower for Exhausting Air
Suspension Fixture
RA
EA SA Blower for supplying air
Total Heat Exchanger Air Filter High Efficiency Filter Blower Maintenance space
Longer than 600
OA
Control Box Maintenance Cover
Maintenance space
Total Heat Exchanger
Suspension Fixture
Air Filter Unit: mm Model LZ-H0802BA0 A LZ-H1002BA0 LZ-H0806BA0 1062 LZ-H1006BA0
Pitch of Suspension Fixture
Figure B
C
D
E
F
1140
365
987
1176
52
Nominal Diameter 250
Duct Connection Flange
Duct Pitch
Weight
G
H
J
K
L
(kg)
242
253
98
513
481
63
27
6. Dimensional Drawings Model No. : LZ-H1502BA0 / LZ-H2002BA0 / LZ-H1506BA0 / LZ-H2006BA0
D
O
RA
E
B
EA N
SA
OA
Control Box Maintenance Cover
Total Heat Exchanger Air Filter High Efficiency Filter Blower Maintenance space
Maintenance space
A
J
F
L K
C
H2
Unit: mm Model LZ-H1502BA0 LZ-H2002BA0 LZ-H1506BA0 LZ-H2006BA0
28
Pitch of Suspension Fixture
Figure
Duct Connection Flange
Weight
A
B
C
D
E
F
G
H
J
K
L
(kg)
1312
1140
730
987
1176
52
242
253
98
340
350
138
7. Wiring Diagrams Model No. : LZ-H0152BA0 / LZ-H0106BA0 / LZ-H0156BA0 / LZ-H0256BA0
29
7. Wiring Diagrams Model No. : LZ-H0502BA0 / LZ-H0356BA0 / LZ-H0506BA0
30
7. Wiring Diagrams Model No. : LZ-H0802BA0 / LZ-H1002BA0 / LZ-H0806BA0 / LZ-H1006BA0
31
7. Wiring Diagrams Model No. : LZ-H1502BA0 / LZ-H2002BA0 / LZ-H1506BA0 / LZ-H2006BA0
32
8. External Static Pressure Settings Setting up Air Volume By setting a phase value of motor, you can control the air volume.
Setting up the air volume of SA EXTERNAL
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH PLASMA
e-SAVER
fresh
Auto Lo
Auto Auto
Normal
Hi
SHi
Heater Preheat Defrost Humidify
Fan Speed Filter Time
Delay Time
Timer
SUB FUNCTION
Program set
Sun Mon Tue Wed Thu
ZONE 1234 Fri
Sat
On Off Set no. Timer
1. If you simultaneously press [timer, ] button for more than 3 seconds, the current phase value is displayed at the display window as right Figure shows. 2. Select the Air volume mode which you want by pressing [ ] button.
Timer
Cancel
fresh Program
Week
Auto
Holiday Plasma
Set/Clr Hour
Min
3. Set up the phase value by pressing [ comes to the target value.
] button until it
4. If you simultaneously press [timer, ] button for more than 3 seconds again, setting up completes.
TIME RESET
EXTERNAL
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH
Cover open status
PLASMA
fresh
e-SAVER
Auto Lo
Auto Auto
SHi
Heater Preheat Defrost Humidify
Fan Speed
Normal
ZONE
Filter Time
Delay Time
Timer
SUB FUNCTION Hi
Program set
Sun Mon Tue Wed Thu
Fri
Sat
On Off Set no. Timer
Phase value
Cipher Supply air
Setting up the air volume of EA 1. If you simultaneously press [timer, ] button for more than 3 seconds, the current phase mvalue is displayed at the display window as right Figure shows.
EXTERNAL
PLASMA
2. Select the Air volume mode which you want by pressing [ button. 3. Set up the phase value by pressing [ comes to the target value.
]
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH Timer
e-SAVER
fresh
Auto Lo
Auto Auto
SHi
Heater Preheat Defrost Humidify
Fan Speed
Normal
Delay Time
SUB FUNCTION Hi
ZONE
Filter Time
Program set
Sun Mon Tue Wed Thu
Fri
Sat
On Off Set no. Timer
] button until it
Phase value
Cipher Exhaust air
4. If you simultaneously press [timer, ] button for more than 3 seconds again, setting up completes.
You can set up the air volume at all air volume mode according to installation circumstances. The phase value can range from 00 to 254. As the value is low, the air volume increases. As making a shipment from the factory, the initial setting up value is “00”. * For more information of setting up the phase value, refer to the external static pressure value table.
33
8. External Static Pressure Settings ESP Data Table External static pressure Pa(in.wg)
Model
0(0)
50(0.2)
100(0.4)
150(0.6)
200(0.8)
253 253 254 235 235 253 200 200 240 160 160 200 248 248 225 162 162 226 110 110 170 107 107 180 40 40 100 205 205 246 88 88 177
247 247 250 230 230 250 192 192 232 155 155 192 232 232 216 151 151 206 108 108 130 96 96 114 24 24 75 172 172 208 65 65 148
237 237 220 220 245 180 180 222 140 140 180 193 193 209 140 140 189 75 75 82 82 10 10 152 152 185 39 39 128
1 1 1 1 240 170 170 215 120 120 170 180 180 201 130 130 177 56 56 75 75 2 2 133 133 166 2 2 109
160 160 205 1 1 160 167 167 192 50 50 163 1 57 1 110 110 145 1 1 83
Mode LZ-H0356BA0
LZ-H0506BA0
LZ-H0806BA0
LZ-H1006BA0
LZ-H1506BA0
LZ-H2006BA0
LZ-H0502BA0
LZ-H0802BA0
LZ-H1002BA0
LZ-H1502BA0
LZ-H2002BA0
34
Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low Super High High Low
9. Sound Pressure Level Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20µPa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
1.5m
Sound levels[dB(A)] S/H H 28 26 32 30 32 30 32 28 34 32 34 32 34 32 36 34 36 34
Model LZ-H0106BA0 LZ-H0152BA0 LZ-H0156BA0 LZ-H0256BA0 LZ-H0356BA0 LZ-H0502BA0 LZ-H0506BA0 LZ-H0802BA0 LZ-H0806BA0
Model
L 20 22 22 21 25 25 25 30 30
LZ-H1002BA0 LZ-H1006BA0 LZ-H1502BA0 LZ-H1506BA0 LZ-H2002BA0 LZ-H2006BA0
Sound levels[dB(A)] S/H H 37 35 37 35 39 37 37 35 42 38 37 35
L 31 31 33 31 33 31
Sound pressure level LZ-H0106BA0
LZ-H0152BA0
LZ-H0156BA0
80
80
80
S/High
S/High
NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30
NC-25 Approximate Hearing Threshold
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15
10 125
250
500
1000
2000
4000
8000
LZ-H0256BA0
125
250
500
1000
2000
NC-35 30 NC-30
4000
8000
63
NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 Approximate Hearing Threshold
NC-15 4000
Octave Band Center Frequency (Hz)
NC-15 125
250
500
1000
2000
4000
8000
8000
LZ-H0506BA0 80 S/High High
Low
70
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
NC-20
10
NC-20
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB re 20µPa )
NC-60
Octave Band Sound Pressure Level (dB re 20µPa )
NC-65
20
NC-25 Approximate Hearing Threshold
High
60
2000
NC-40
S/High
Low
1000
NC-45
LZ-H0502BA0 High
500
NC-50
40
NC-15
S/High
250
NC-55 50
NC-20
80
125
NC-60
Octave Band Center Frequency (Hz)
80
63
NC-65 60
10 63
Octave Band Center Frequency (Hz)
70
Low
70
20
10 63
Octave Band Sound Pressure Level (dB re 20µPa )
High
Low
70
Octave Band Sound Pressure Level (dB re 20µPa )
NC-65 60
20
S/High
High
Low
Octave Band Sound Pressure Level (dB re 20µPa )
Octave Band Sound Pressure Level (dB re 20µPa )
High
70
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15
10
Low
70
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
35
9. Sound Pressure Level
LZ-H0356BA0
LZ-H0802BA0
LZ-H0806BA0
80
80
80
S/High
S/High
S/High
High
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15
10
High
Low
70
Octave Band Sound Pressure Level (dB re 20µPa )
Low
Octave Band Sound Pressure Level (dB re 20µPa )
Octave Band Sound Pressure Level (dB re 20µPa )
High
70
125
250
500
1000
2000
4000
8000
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15
10
63
Low
70
125
250
500
1000
2000
4000
8000
63
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
LZ-H1002BA0
NC-15
10 63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
LZ-H1006BA0
LZ-H1502BA0
80
80
NC-20
80 S/High
High
High
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold 63
250
500
1000
2000
4000
NC-65 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-15 125
10
NC-25 Approximate Hearing Threshold 63
8000
Octave Band Center Frequency (Hz)
LZ-H1506BA0
250
500
1000
2000
4000
NC-45 40 NC-40 NC-35 30 NC-30
Low
63
50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 Approximate Hearing Threshold
NC-65 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
20 Approximate Hearing Threshold
4000
Octave Band Center Frequency (Hz)
8000
1000
2000
4000
8000
63
70
NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30
NC-15 125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-25
20 Approximate Hearing Threshold
NC-20
10 2000
500
Low
60
NC-15
10
250
High
70
NC-20
NC-15 125
S/High
Octave Band Sound Pressure Level (dB re 20µPa )
NC-55
NC-20
10
LZ-H2006BA0 High
20
NC-25 Approximate Hearing Threshold
80 S/High
NC-60
1000
NC-50
Octave Band Center Frequency (Hz)
Low
Octave Band Sound Pressure Level (dB re 20µPa )
Octave Band Sound Pressure Level (dB re 20µPa )
125
High
NC-65
500
NC-55 50
20
NC-15 8000
S/High
60
250
NC-60
LZ-H2002BA0
70
125
NC-65 60
NC-20
80
63
70
Octave Band Center Frequency (Hz)
80
36
Low
60
NC-20
10
High
Low
70
Octave Band Sound Pressure Level (dB re 20µPa )
Low
70
Octave Band Sound Pressure Level (dB re 20µPa )
Octave Band Sound Pressure Level (dB re 20µPa )
S/High S/High
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
10. Installation 10.1 Typical Installation Map Model No.: LZ-H0152BA0 / LZ-H0106BA0 / LZ-H0156BA0
Air return grille Air return system A
OA B
(Fresh air outlet)
Air supply grille
EA (Exaust air outlet)
Control Box
Duct slope: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
Duct
Inspection part
Ceiling Fixing Bolt (user-supplied)
New hood (preventing penetration of rain water)
C
C
Air return system
EA (Exaust air outlet)
OA (Fresh air outlet)
Inspection part
SA
RA
(Supply air)
(Return air) Air return grille
Air supply grille
[Unit : mm]
LZ-H0152BA0 LZ-H0106BA0 LZ-H0156BA0
A
B
C
504
624.2
100
37
10. Installation Model No.: LZ-H0256BA0
Air supply grille Air return system A
OA Air return system
B
(Fresh air outlet)
EA
Air return grille
(Exaust air outlet)
Inspection part
Duct slope: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
Duct
Ceiling Fixing Bolt (user-supplied)
New hood (preventing penetration of rain water)
C
C
Air return system
EA (Exaust air outlet)
OA (Fresh air outlet)
Inspection part
SA
RA
(Supply air)
(Return air) Air return grille
Air supply grille
[Unit : mm]
LZ-H0256BA0
38
A
B
C
568
636.2
150
10. Installation Model No.: LZ-H0502BA0 / LZ-H0356BA0 / LZ-H0506BA0
Ceiling suspension bolts position
EA (Exaust air outlet) Air return grille (user-supplied)
OA
Min.600
150~250
(Fresh air outlet)
Inspection part 450 ( 600)
Air supply grille (user-supplied)
(
Maintenance space Total heat Exchanger Air Filter
)
Ceiling Fixing Bolt (user-supplied)
C
C
Duct normal diameter Ă˜C(user-supplied)
EA (Exaust air outlet)
OA
Inspection part 450( 600)
(Fresh air outlet)
Duct slope: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
RA SA (Return air)
Air supply grille Air return grille
(Supply air)
[Unit : mm]
LZ-H0502BA0 LZ-H0356BA0 LZ-H0506BA0
A
B
C
938.8
1024.8
200
39
10. Installation Model No.: LZ-H0802BA0 / LZ-H1002BA0 / LZ-H0806BA0 / LZ-H1006BA0
Air supply grille (user-supplied)
Ceiling suspension bolts position Air return grille (user-supplied)
EA (Exaust air outlet)
OA (Fresh air outlet)
Min.600 150~250
Y duct connecting (user-supplied) Inspection part 450 ( 600)
Maintenance space Exchanger ( Total heat ) Air Filter
Ceiling Fixing Bolt (user-supplied)
C
C
Duct normal diameter Ă˜C(user-supplied)
EA (Exaust air outlet)
OA
Inspection part 450( 600)
(Fresh air outlet)
Air supply grille
Air return grille
RA (Return air) Duct slope: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
SA
SA
(Supply air)
(Supply air)
[Unit : mm]
LZ-H0802BA0 LZ-H0806BA0 LZ-H1002BA0 LZ-H1006BA0
40
A
B
C
987
1176
250
10. Installation Model No.: LZ-H1502BA0 / LZ-H2002BA0 / LZ-H1506BA0 / LZ-H2006BA0
Air return grille (user-supplied) Air supply grille (user-supplied)
Ceiling suspension bolts position A
Air return grille (user-supplied) D
Air supply grille (user-supplied)
D
C
B
EA (Exaust air outlet)
OA (Fresh air outlet) Min.60 150~2
Y duct connecting (user-supplied) Inspection port 450 ( 600)
Air supply grille (user-supplied) Air supply grille (user-supplied) Maintenance space Total Heat Exchanger Air Filter
Duct normal diameter Ă˜ C (user-supplied)
Ceiling Fixing Bolt (user-supplied)
New Type Hood (Preventing Penetration of Rain Water)
EA
(Exaust air outlet)
OA
(Fresh air outlet) Inspection port 450 ( 600)
Air return grille
Duct slope : More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
RA (Return air)
SA RA (Supply air) (Return air)
Air supply grille SA (Supply air)
SA SA (Supply air) (Supply air)
[Unit : mm]
LZ-H1502BA0 LZ-H1506BA0 LZ-H2002BA0 LZ-H2006BA0
A
B
C
D
987
1176
350
250
41
10. Installation 10.2 Installation Installation of Main Body Assembly of Washer, Nut Ceiling Fixing Bolt (M10~12)
Tighten the commercial washer nut (more than 21mm for the outside diameter of M10, to the commercial ceiling fixing bolt (M10) as shown in the left figure.
Nut Washer, Spring Lock
• For the ceiling fixing bolt, perform work less than 50mm under the ceil fixing bracket.
Washer, Plain Nut
Connection of Duct 1. After securely connect the duct with the duct connection flange, wrap it with a commercial aluminium tape so that air cannot be leaked.
Duct
2. Adjust the duct from the ceiling so that no force is applied to the main body of the ventilation system. 3. Always use two ducts at the outdoor with the heat insulating material for prevention of dewing.
Taping Duct
CAUTION: • Check that there are no foreign materials (paper, vinyl, etc) or cutoff powders in the duct before connecting the duct. • Take care so that shock may not be applied to the damper plate within the main body when performing the duct connection work.
Taping
• It is recommended to perform adiabatic treatment even to the duct pipe at the indoor side where ambient temperature is expected when the main body of the ventilation system for cooling in summer. • Take care so that work may not be performed as in the left figure. Otherwise, it may cause reduction of air volume or abnormal noise.
Heat Insulating Material Aluminium
Main Body Duct to OA Duct Connection Flange
Rapid Bending
42
Excessive Bending
Too Close Bending to Outlet
Rapid Reduction of Duct Diameter
10. Installation 10.3 Wiring Connection Method to Connect Power Cord 1. Release two screws and then open the cover of the control box. • With reference to the above wiring diagram, accurately connect the main power cords into the terminal block. Cover of Control Box Cover of Control Box
Screw
Screw
2. After inserting the power cord into the bushing, fully insert it into the terminal block for connection. • Fix the power cords with the clamp. • Make sure that the power cords may not be removed by pulling them.
Bushing
Bushing GN/YL GND
GN/YL GND
BL BR Power
Cord Clamp
BL BR Power
Cord Clamp
43
11. LCD Wired Remote Control(PZRCUSB0) LCD Remote Control (Ventilation System Remote Control PZRCUSB0)
EXTERNAL
1
VENTILATOR OPERATION
Linked Run Dual Remote Central Run Heat XCH PLASMA
e-SAVER
fresh
Auto Lo
Auto Auto
Normal
Delay Time
Timer
SUB FUNCTION Hi
SHi
Heater Preheat Defrost Humidify
Fan Speed Filter Time
Program set
ZONE 1234
Sun Mon Tue Wed Thu
Fri
Sat
On Off Set no. Timer
13 10 Timer
Cancel
fresh Program
Week
2
Auto
Holiday Plasma
Set/Clr Hour
Min
3 4 5 6 7 11
TIME RESET
8 12
9
Cover open status
1. Display Window
6. Ventilation Mode Button
2. Execute/Cancel of Time Reservation,Weekly Reservation/Weed Day Select/Holiday Select Button
7. Air volume Select Button
3. Operation/Stop Button 4. Delay Time Button 5. Rapid Ventilation Button
8. Power Saving/Filter Cleaning Button 9. Time Reset Button 10. Heater Button 11. Humidification Button 12. Plasma Button 13. Operation Lamp
44
P/No.: 3828A20428T
Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com
All rights reserved Printed in Korea Aug./2008 The specifications, designs, and information in this brochure are subject to change without notice.
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.