Multi-V Plus II Tropical(R410a) - Indoor Units, 09.06.11

Page 1

Indoor unit

0CVP0-02B(Replaces:0CVP0-02A)


LG Airconditioners Product Data

(R410A)

• Introduction • General Information • Indoor Units


Introduction 1. Preface R410A Model is the most favored choice when there is a need for precise air conditioning of relatively big projects extending from Multi-Room structure to big commercial places. We have a big line up, that offers wider flexibility of model selection. Equipped with inverter technology and long piping installation, the product matches well if one talk about optimum power consumption in high rise buildings. Add on capacity feature makes it easy to upgrade the existing capacity at any time. With the growing concern about environment preservation, comes with R410A refrigerant which is environment friendly and thus our system is a high technology and environment friendly product.

Unique refrigerant flow and electronic circuit control gives this system an unique capability to work in extreme/abnormal working conditions making our customer feel great about their decision of selecting LG as their first choice. This publication provides a detailed and in depth information about the design and installation of . We hope that with this information you would become an expert of your

system.

Air-Conditioning Company


2. Step by Step (1)

(2)

System Selection Process

Calculate or obtain the maximum heat load for the area(s) to be air conditioned

Decide the indoor unit specifications Decide the outdoor unit specifications Capacity coefficient factor Decide the air velocity and temperature distributions

(3)

(4)

Selection of refrigerant pipe joints and headers

Selection of the control system Control wiring method Description of devices

(5)

Electrical wiring Electric characteristics Field wiring

Caution 1. Air conditioners should not be installed in areas where corrosive gases such as acid gas or alkaline gas is produced. 2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.


General Information 1. Model Names 2. External Appearance 3. Nomenclature 4. Indoor Unit Capacity Index

General information


1. Model Names Category

Capacity(Btu/h(kW))

Chassis Name

5k (1.6)

9k (2.8)

12k (3.6)

15k (4.5)

Mirror

ARNU18 ARNU24 GS8*2 GS8*2

S8 SF

1 Way

TJ

2 Way

TL TR

Ceiling

ARNU07 ARNU09 ARNU12 GSF*2 GSF*2 GSF*2 ARNU07 ARNU09 ARNU12 GTJ*2 GTJ*2 GTJ*2 ARNU18 ARNU24 GTL*2 GTL*2 ARNU05 ARNU07 ARNU09 ARNU12 GTR*2 GTR*2 GTR*2 GTR*2 ARNU15 ARNU18 GTQ*2 GTQ*2

TQ

Cassette 4 Way

ARNU24 ARNU28 GTP*2 GTP*2

TP

ARNU36 GTN*2

TN

ARNU42 ARNU48 GTM*2 GTM*2

TM BH High Static Ceiling Concealed Duct

ARNU07 ARNU09 ARNU12 ARNU15 ARNU18 ARNU24 GBHA2 GBHA2 GBHA2 GBHA2 GBHA2 GBHA2 ARNU28 ARNU36 ARNU42 GBGA2 GBGA2 GBGA2

BG

ARNU48 GBRA2

BR

URNU76 URNU96 GB8A2 GB8A2

B8 B1 Low Static

ARNU07 ARNU09 ARNU12 ARNU15 GB1G2 GB1G2 GB1G2 GB1G2 ARNU18 ARNU24 GB2G2 GB2G2

B2 B3 Built In

ARNU07 ARNU09 ARNU12 ARNU15 GB3G2 GB3G2 GB3G2 GB3G2

B4

Ceiling & Floor

VE

Ceiling Suspended

VJ CE

With Case

ARNU18 ARNU24 GB4G2 GB4G2 ARNU09 ARNU12 GVEA2 GVEA2 ARNU18 ARNU24 GVJA2 GVJA2 ARNU07 ARNU09 ARNU12 ARNU15 GCEA2 GCEA2 GCEA2 GCEA2 ARNU18 ARNU24 GCFA2 GCFA2

CF

Floor Standing Without Case

28k 36k 42k 48k 76k 96k (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)

ARNU07 ARNU09 ARNU12 ARNU15 GSE*2 GSE*2 GSE*2 GSE*2

SE

Gallery

24k (7.1)

ARNU18 ARNU24 GS5*2 GS5*2

S5

ART COOL

18k (5.6)

ARNU07 ARNU09 ARNU12 ARNU15 GSE*2 GSE*2 GSE*2 GSE*2

SE

Wall Mounted (General)

7k (2.2)

CE

ARNU07 ARNU09 ARNU12 ARNU15 GCEU2 GCEU2 GCEU2 GCEU2

CF

ARNU18 ARNU24 GCFU2 GCFU2

❈ *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable)) *Wall Mounted- A: Basic, L:Plasma *Ceiling Cassette- A: Basic, C:Plasma

General information

1


2. External Appearance Ceiling Cassette- 1Way

Ceiling Cassette -2Way

ARNU07GTJ*2 ARNU09GTJ*2 ARNU12GTJ*2

ARNU18GTL*2 ARNU24GTL*2

* A:Basic, C:Plasma

* A:Basic, C:Plasma

Ceiling Cassette- 4Way

Ceiling Concealed Duct - High Static

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2

ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2

ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2

ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 URNU76GB8A2 URNU96GB8A2

* A:Basic, C:Plasma

Ceiling Concealed Duct - Low Static

Wall Mounted

ARNU07GB1G2 ARNU15GB1G2 ARNU09GB1G2 ARNU18GB2G2 ARNU12GB1G2 ARNU24GB2G2

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2

ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 * A:Basic, L:Plasma

Ceiling Concealed Duct – Built-in

ART COOL Gallery

ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2

ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 * E:Red V:Silver G:Gold 1: Kiss (Photo changeable)

ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2

ART COOL Mirror ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2

*R:Mirror V:Silver B:Blue

Ceiling & Floor ARNU09GVEA2 ARNU12GVEA2

Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2

2

Floor Standing With case ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2

Without case ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2

General information


3. Nomenclature ARN

U

07

G

TJ

A

2 Serial Number Combinations of functions A:Basic function L:Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) G: Low Static U : Floor Standing without Case ART COOL Type Panel Color SE/S8 - R:Mirror V:Silver B:Blue SF - E:Red V:Silver G:Gold 1: Kiss (Photo changeable) Chassis Name Electrical Ratings 1:1Ø, 115V, 60Hz 2: 1Ø, 220V, 60Hz 6:1Ø, 220 ~ 240V, 50Hz 7: 1Ø, 100V, 50/60Hz G:1Ø, 220 ~ 240V, 50Hz / 220V 60Hz Total Cooling Capacity in Btu/h EX) 5,000 Btu/h➞'05' 18,000 Btu/h➞'18' Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O System with Indoor Unit using R410A ❈ LGETA:U Ex) URN

General information

3


4. Indoor Unit Capacity Index INDOOR UNIT CAPACITY INDEX Unit Capacity (Btu/h)

5k

7k

9k

12k

15k

18k

24k

28k

36k

42k

48k

76k

96k

Capacity Index

1.6

2.2

2.8

3.6

4.5

5.6

7.1

8.2

10.6

12.3

14.1

22.4

28

â?ˆ Capacity Index is same as the capacity(kW).

4

General information


Indoor Units

Ceiling Cassette 2-Way Ceiling Cassette 4-way Ceiling Concealed Duct(High Static) Ceiling Concealed Duct(Low Static) Ceiling Concealed Duct(Built in) Wall Mounted ART COOL Mirror ART COOL Gallery Ceiling & Floor/Ceiling Suspended Floor Standing

Cassette 1-way

Ceiling Cassette 1-Way


Cassette 1-way

Ceiling Cassette 1-Way

1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Ceiling Cassette 1-way


1. List of Functions Category

Air flow

Installation

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GTJ*2, ARNU09GTJ*2, ARNU12GTJ*2 1 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

Cassette 1-way

Air purifying

Function

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Cassette 1-way

1-1


2. Specifications

Cassette 1-way

* Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Acc'y)

Ø, V, Hz

1Way Ceiling Cassette ARNU07GTJ*2 ARNU09GTJ*2 ARNU12GTJ*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 860x410x138 860x410x138 860x410x138 33.8x16.1x5.4 33.8x16.1x5.4 33.8x16.1x5.4 1,070x480x20 1,070x480x20 1,070x480x20 42.1x18.9x0.8 42.1x18.9x0.8 42.1x18.9x0.8 2x9x21 2x9x21 2x9x21 0.13 0.13 0.13 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20.0 20.0 20.0 0.20 0.20 0.20 7.5/6.5/6 7.5/6.5/6 8/7/6 265/229/212 265/229/212 283/247/212 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25.0 25.0 25.0 11.5(25.4) 11.5(25.4) 11.5(25.4) 40/38/37 40/38/37 41/39/37 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog Morning fog PT-HJ*

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

1-2

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 1-way


138

83

19.1 16.5

198.8

131

16.4

32.8

410 344.4

939

1070

Branch Duct Connection

961.2 860

2

4

3

1

30 36 50 83

Liquid pipe connection Gas pipe connection Air suction grill Air discharge grill

1 2 3 4

Unit size(7k, 9k, 12k):ø12.7

Unit size(7k, 9k, 12k):ø6.35

Descripition

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: TJ

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

Number

ARNU07GTJ*2 ARNU09GTJ*2 ARNU12GTJ*2

Cassette 1-way

Ceiling Cassette 1-way

480

Ceiling Cassette 1-way

3. Dimensions

110

1-3

173 151 100 56

242.5


Cassette 1-way

4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 C.F.F.

Filter Th1

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

Model

Gas

Liquid

Ø12.7(1/2)

Ø6.35(1/4)

ARNU07GTJ*2 ARNU09GTJ*2 ARNU12GTJ*2

1-4

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Cassette 1-way


5. Wiring Diagrams TJ Chassis

Cassette 1-way

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 1-way

1-5


6. Capacity Tables

Cassette 1-way

6.1 Cooling Capacity

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.2

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.2 2.1 2.0

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.0

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

1-6

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 1-way


6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

2.8

3.6

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7 2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2 2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Cassette 1-way

2.2

Heating capacity

Notes: TC: Total Capacity(kW)

Ceiling Cassette 1-way

1-7


7. Air Velocity and Temperature Distribution(Reference Data)

Cassette 1-way

ARNU07GTJ*2 Cooling

Heating

Discharge angle: 45°

Discharge angle: 60°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m 2.0 1.5

2m

2.0

2m

1.0 1.5

1m

1m 0.5

1.0 0.5 5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

5m

4m

3m

2m

0m 0m

1m

Temperature [°C] 2.7m

2.7m 33 30

18 2m

20

2m 24

22

21

18

1m

1m

27

24 5m

4m

3m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

ARNU09GTJ*2 Heating

Cooling Discharge angle: 45°

Discharge angle: 60° Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0 1.5

2m

2m

2.0 1.0 1.5

1m

1m 0.5

1.0 0.5 5m

4m

3m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 33

18 20

2m

30

21

1m

22

24 4m

3m

2m

1m

0m 0m

5m

4m

1m

27

18

5m

2m

24

3m

2m

1m

0m 0m

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

1-8

Ceiling Cassette 1-way


ARNU12GTJ*2 Cooling

Heating Discharge angle: 60째

Discharge angle: 45째

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2m 2.0

1m 1.0

1.0

0.5

0.5 4m

3m

Cassette 1-way

1.5 1m

1.5

5m

2m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

Temperature [째C]

Temperature [째C]

2.7m

2.7m 18 20

33 2m

30

21

22

2m

1m

1m 24

27

24 5m

4m

3m

2m

1m

0m 0m

5m

4m

3m

2m

1m

0m 0m

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

Ceiling Cassette 1-way

1-9


8. Electric Characteristics

Cassette 1-way

Units Model

Type

ARNU07GTJ*2

TJ

ARNU09GTJ*2

TJ

ARNU12GTJ*2

TJ

ARNU07GTJ*2

TJ

ARNU09GTJ*2

TJ

ARNU12GTJ*2

TJ

Power Supply Hz 50

60

Volts 220~240

220

Voltage Range MCA Max:264 Min:198 Max:242 Min:198

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

1.29

15

0.02

0.23

40

40

1.29

15

0.02

0.23

40

40

1.29

15

0.02

0.23

40

40

1.29

15

0.02

0.23

40

40

1.29

15

0.02

0.23

40

40

1.29

15

0.02

0.23

40

40

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes( see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA + 1 MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

1-10

Ceiling Cassette 1-way


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m

Cassette 1-way

Microphone

Sound Levels dB(A) H M L

Model ARNU07GTJ*2 ARNU09GTJ*2 ARNU12GTJ*2

40 40 41

38 38 39

37 37 37

Sound Pressure Level ARNU07GTJ*2

ARNU09GTJ*2 80

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

70

NC-65 60 NC-60

NC-50

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 1-way

NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-15 125

NC-55

50

NC-20

10

80

70

NC-65 60 NC-60

NC-50

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-15 125

NC-55

50

NC-20

10 63

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

80

ARNU12GTJ*2

NC-20 NC-15

10 63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

1-11


• Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Anti-bacteria filter

Air Outlet

Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

TEMP

Remote Controller

Air Intake

Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

10.1 Selection of the best location

1-12

Ceiling board

50 or more

Ceiling board

50 or more

30 or less

20 or more

Ceiling

Above 250 330 or less

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

100 or more

Cassette 1-way

10. Installation

Unit:cm Floor

Ceiling Cassette 1-way


10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.

1,030 (Ceiling opening)

53

50

344(Hanging bolt) 53

Level gauge

923 (Hanging bolt) 860

Cassette 1-way

Ceiling

450 (Ceiling opening) 410

57

CAUTION (unit: mm)

• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires. • Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

Ceiling board

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Ceiling Cassette 1-way

1-13


Nut (W3/8 or M10)

55mm

Cassette 1-way

Ceiling Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Flat washer for M10 (accessory) Ceiling board

Spring washer (M10)

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Air Conditioner body

Set screw of paper pattern (4 pieces)

Paper pattern for installation

Open the ceiling board along the outer edge of the paper pattern

Adjust the same height

• The following parts are locally purchased. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10

Ceiling board

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

1-14

Ceiling Cassette 1-way


10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

Air conditioner unit

Decorative panel fixing screws (hexagon M6 screws) Temporarily fitting at 2 poles (Tightening about 10mm)

Piping side

Control box cover Cover

Plasma filter

Key holes

Louver motor

Decorative panel fixing screws (Hexagon M6 screw)

Decorative panel

Push

Ratch pull

Inlet Grille

CAUTION Install the decoration panel otherwise cool air leakage causes condensation. Water drops fall.

Correct method

Wrong method Air conditioner unit Cool air leakage (no good) Ceiling board Decoration panel

Air conditioner unit Ceiling board Decoration panel

Fit the insulator (this part) and be careful for cool air leakage

Ceiling Cassette 1-way

1-15

Cassette 1-way

1. Temporarily fix two decoration panel fixing screws (hexagon M6 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M6 screw) are included in the Indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector and room temp. thermistor connector. 6. After tightening these screws, install the air inlet grille (including the air filter) and push middle point of inlet grille. 7. Assemble the cover display and the cover.


• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping. 1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

Drain pan

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp Flexible drain hose

Max 700mm

Cassette 1-way

10.5 Indoor Unit Drain Piping

Insulation

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

1-16

Ceiling Cassette 1-way


CAUTION

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet (1.5meters)

TEMP

Controller Remote

no

no

Fig.1 Typical locations for remote controller

Ceiling Cassette 1-way

1-17

Cassette 1-way

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.


11. Accessories

Cassette 1-way

Standard Accessories Name

Clamp metal

Drain hose

Insulation for fitting

Quantity

2 EA

1 EA

1 set

Washer for hanging bracket 8 EA

Clamp (Tie Wrap)

Bolt

4 EA

4 EA

Screw

(Other)

3 EA • Paper pattern for installation • Owner's manual • Installation manual

Shape

for gas pipe

for liquid pipe • Screws for fixing panels are attached to decoration panel.

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

1-18

Ceiling Cassette 1-way


1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Ceiling Cassette 2-way

Cassette 2-way

Ceiling Cassette 2-Way


1. List of Functions

Cassette 2-way

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU18GTL*2, ARNU24GTL*2 2 Auto O 4/5/4 X O O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

2-1

Ceiling Cassette 2-way


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity Casing Body Dimensions (WxDxH) Front Panel Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Acc'y)

Ø, V, Hz

2Way Ceiling Cassette ARNU18GTL*2 5.6 4,800 19,100 6.3 5,400 21,500 Galvanized Steel Plate 830x550x225 32.6x21.6x8.9 1,050x640x28.5 41.3x25.2x1.1 2x11x20 0.13 Cross Flow Fan 20x2 0.18x2 13/12/10 459/424/353 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25.0 22(48.5) 40/35/30 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C Morning fog PT-HL*

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Ceiling Cassette 2-way

Cassette 2-way

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

2-2


Cassette 2-way

* Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Acc'y)

Ø, V, Hz

2Way Ceiling Cassette ARNU24GTL*2 7.1 6,100 24,200 8.0 6,900 27,300 Galvanized Steel Plate 830x550x225 32.6x21.6x8.9 1,050x640x28.5 41.3x25.2x1.1 2x11x20 0.13 Cross Flow Fan 20x2 0.18x2 17/15/13 601/530/459 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø9.52(3/8) Ø15.88(5/8) 25.0 22(48.5) 42/37/32 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C Morning fog PT-HL*

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

2-3

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 2-way


3

4

1050

889.2

830

2

1

B

28.5

225 126.5

A

TL

A B 47.9

Air suction grill Air discharge grill

3 4

Unit size(24k):ø15.88

Unit size(18k):ø12.7

Unit size(24k):ø9.52

Unit size(18k):ø6.35

Descripition

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: TL

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection

Liquid pipe connection

Name

2

1

Number

ARNU18GTL*2 ARNU24GTL*2

Cassette 2-way

Ceiling Cassette 2-way 275 69.5

Ceiling Cassette 2-way

3. Dimensions

2-4

640

550


Cassette 2-way

4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 C.F.F.

Filter Th1

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

2-5

Model

Gas

Liquid

ARNU18GTL*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GTL*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Cassette 2-way


5. Wiring Diagrams TL Chassis

Cassette 2-way

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO

SPEC AC Power supply Fan motor output Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

DESCRIPTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 2-way

2-6


6. Capacity Tables

Cassette 2-way

6.1 Cooling Capacity

Capacity Index

5.6

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

3.8

7.2

4.1

12

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

3.8

7.1

4.0

14

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

3.8

7.1

4.0

16

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

3.8

7.0

4.0

18

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.6

3.8

6.9

3.9

20

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.5

3.7

6.8

3.9

21

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.5

3.7

6.8

3.9

23

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.5

3.7

6.7

3.8

25

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

3.6

6.6

3.7

27

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.3

3.6

6.5

3.7

29

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.3

3.5

6.4

3.6

31

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.9

4.0

6.2

3.5

6.3

3.6

33

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.8

3.9

6.1

3.5

6.2

3.5

35

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.8

3.9

6.0

3.4

6.1

3.5

37

3.8

3.2

4.5

3.6

5.2

3.9

5.5

3.9

5.7

3.8

5.9

3.3

6.0

3.4

39

3.8

3.2

4.5

3.6

5.2

3.9

5.5

3.8

5.6

3.8

5.8

3.3

5.9

3.4

42

3.8

3.2

4.5

3.6

5.2

3.9

5.4

3.8

5.5

3.7

5.7

3.2

5.8

3.3

44

3.8

3.2

4.5

3.6

5.2

3.8

5.3

3.7

5.4

3.7

5.6

3.2

5.7

3.2

46

3.8

3.2

4.5

3.6

4.9

3.6

5.0

3.5

5.1

3.4

5.1

2.9

5.2

2.9

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

2-7

Cooling capacity

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 2-way


Cooling capacity

Capacity Index

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

4.8

9.1

5.2

12

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

4.8

9.0

5.1

14

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

4.8

8.9

5.1

16

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

4.8

8.8

5.0

18

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.4

4.8

8.8

5.0

20

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.3

4.7

8.7

4.9

21

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.3

4.7

8.6

4.9

23

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.2

4.6

8.5

4.8

25

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.1

4.6

8.4

4.8

27

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.0

4.6

8.3

4.7

29

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.5

5.1

7.9

4.5

8.1

4.6

31

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.5

5.1

7.8

4.4

8.0

4.5

33

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.4

5.0

7.7

4.4

7.9

4.5

35

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.3

4.9

7.6

4.3

7.8

4.4

37

4.8

4.1

5.7

4.5

6.6

4.9

7.0

4.9

7.2

4.9

7.5

4.2

7.6

4.3

39

4.8

4.1

5.7

4.5

6.6

4.9

6.9

4.9

7.1

4.8

7.4

4.2

7.5

4.3

42

4.8

4.1

5.7

4.5

6.6

4.9

6.8

4.8

7.0

4.7

7.2

4.1

7.3

4.2

44

4.8

4.1

5.7

4.5

6.5

4.8

6.7

4.7

6.9

4.7

7.1

4.0

7.2

4.1

46

4.8

4.1

5.7

4.5

6.3

4.6

6.3

4.4

6.5

4.4

6.5

3.7

6.6

3.7

Notes: TC: Total Capacity(kW)

Ceiling Cassette 2-way

SHC: Sensible Heat Capacity(kW)

2-8

Cassette 2-way

7.1

20 14 TC SHC kW kW

Outdoor air temp. (DB, 째C)


Cassette 2-way

6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

5.6

Heating capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW 4.2

kW 4.2

kW 4.2

kW 4.2

kW 4.2

kW 4.2

-18.8 -19.0

4.3

4.3

4.3

4.3

4.3

4.3

-16.7 -17.0

4.6

4.6

4.6

4.6

4.6

4.5

-14.7 -15.0

4.9

4.8

4.3

4.8

4.8

4.8

-12.6 -13.0

5.1

5.1

4.5

5.0

5.0

5.0

-10.5 -11.0

5.4

5.4

4.8

5.4

5.3

5.3

-9.5 -10.0

5.4

5.4

4.9

5.4

5.4

5.4

-8.5

-9.1

5.5

5.5

5.0

5.5

5.5

5.4

-7.0

-7.6

5.7

5.7

5.1

5.6

5.6

5.5

-5.0

-5.6

6.0

6.0

5.4

5.8

5.8

5.5

-3.0

-3.7

6.2

6.2

5.5

6.1

5.9

5.5

0.0

-0.7

6.6

6.6

5.8

6.1

5.9

5.5

3.0

2.2

7.0

6.7

6.2

6.1

5.9

5.5

5.0

4.1

7.1

6.7

6.3

6.1

5.9

5.5

7.0

6.0

7.2

6.7

6.3

6.1

5.9

5.5

9.0

7.9

7.2

6.7

6.3

6.1

5.9

5.5

11.0

9.8

7.2

6.7

6.3

6.1

5.9

5.5

13.0 11.8

7.2

6.7

6.3

6.1

5.9

5.5

15.0 13.7

7.2

6.7

6.3

6.1

5.9

5.5

Notes: TC: Total Capacity(kW)

2-9

Ceiling Cassette 2-way


Heating capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW 5.4

kW 5.4

kW 5.4

kW 5.3

kW 5.3

kW 5.3

-18.8 -19.0

5.5

5.5

5.5

5.5

5.4

5.4

-16.7 -17.0

5.8

5.8

5.8

5.8

5.8

5.8

-14.7 -15.0

6.2

6.1

5.5

6.1

6.1

6.1

-12.6 -13.0

6.5

6.5

5.8

6.4

6.4

6.4

-10.5 -11.0

6.8

6.8

6.0

6.8

6.7

6.7

-9.5 -10.0

6.9

6.9

6.2

6.9

6.9

6.8

-8.5

-9.1

7.0

7.0

6.3

7.0

7.0

6.8

-7.0

-7.6

7.3

7.3

6.5

7.1

7.1

7.0

-5.0

-5.6

7.6

7.6

6.8

7.4

7.4

7.0

-3.0

-3.7

7.9

7.9

7.0

7.7

7.5

7.0

0.0

-0.7

8.4

8.4

7.4

7.8

7.5

7.0

3.0

2.2

8.9

8.6

7.8

7.8

7.5

7.0

5.0

4.1

9.0

8.6

8.0

7.8

7.5

7.0

7.0

6.0

9.2

8.6

8.0

7.8

7.5

7.0

9.0

7.9

9.2

8.6

8.0

7.8

7.5

7.0

11.0

9.8

9.2

8.6

8.0

7.8

7.5

7.0

13.0 11.8

9.2

8.6

8.0

7.8

7.5

7.0

15.0 13.7

9.2

8.6

8.0

7.8

7.5

7.0

Notes: TC: Total Capacity(kW)

Ceiling Cassette 2-way

2-10

Cassette 2-way

7.1

Indoor air temp. (DB, 째C)


7. Air Velocity and Temperature Distribution(Reference Data)

Cassette 2-way

ARNU24GTL*2 Cooling

Heating

Discharge angle: 40째

Discharge angle: 60째

Air velocity [m/s]

Air velocity [m/s]

22

21

20

20

2.7m 21

22

23

32 31

2m

23

30

24

24

1m

28 26

4m

3m

2m

1m

0m

1m

2m

0m 4m

3m

Temperature [째C]

4m

29

27

3m

2m

2m

30 27

28

1m

2.7m

32 31

29 28

0m

1m

28 27

1m

26

2m

3m

Temperature [째C]

2.7m 2.0

2.5

3.0

3.0

2.5

1.5

1.5

1.0

2-11

2.7m 2.5 2.0

2m

2.0 1.0

0.5

4m

2m

1m

0m

1m

2m

3m

0m 4m

2.5 2.0

1.5

1m

3m

2m

1m

1.0

0.5

4m

2m

1.5

1.0

0.5

3m

0m 4m

0.5

1m

0m

1m

2m

3m

0m 4m

Ceiling Cassette 2-way


8. Electric Characteristics Units Model

Type

ARNU18GTL*2

TL

ARNU24GTL*2

TL

ARNU18GTL*2

TL

ARNU24GTL*2

TL

Power Supply Hz

Volts

50

220~240

60

220

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

Max:264

1.52

15

0.04

0.41

70

70

Min:198

1.52

15

0.04

0.41

70

70

Max:242

1.52

15

0.04

0.41

70

70

Min:198

1.52

15

0.04

0.41

70

70 Cassette 2-way

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes( see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA + 1 MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

Ceiling Cassette 2-way

2-12


9. Sound Levels

Cassette 2-way

Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m Microphone

Sound Levels dB(A)

Model

H

M

L

ARNU18GTL*2

40

35

30

ARNU24GTL*2

42

37

32

Sound Pressure Level ARNU18GTL*2

ARNU24GTL*2 80

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

NC-65 60 NC-60

125

250

500

NC-15 1000 2000 4000 8000

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20

Octave Band Center Frequency (Hz)

2-13

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

80

NC-20 NC-15

10 63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 2-way


10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Cassette 2-way

Anti-bacteria filter TEMP

Remote Controller

Air Intake Air Outlet

Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

Ceiling Cassette 2-way

Ceiling Board

50 or more

30 or less

50 or more

Above 250 330 or less

Ceiling Ceiling Board

100 or more

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

20 or more

10.1 Selection of the best location

Unit:cm Floor

2-14


Cassette 2-way

10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions. Ceiling board

Ceiling Level gauge

CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

2-15

Ceiling Cassette 2-way


Ceiling

Nut (W3/8 or M10)

90mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Flat washer for M10 False (accessory) ceiling board

Spring washer (M10)

Air Conditioner body

Set screw of paper pattern (4 pieces)

Paper pattern for installation

Open the ceiling board along the outer edge of the paper pattern

Adjust the same height

• The following parts are locally purchased. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10

Cassette 2-way

Flat washer for M10 (accessory) Nut (W3/8 or M10)

False ceiling board

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

Ceiling Cassette 2-way

2-16


Cassette 2-way

10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Air conditioner unit Decorative panel fixing screws (hexagon M6 screws) Temporary fitting at 2 poles (Tightening about 10mm)

Piping side

Control box cover Cover

Plasma filter

Louver motor

Key holes

Decorative panel fixing screws (Hexagon M6 screw)

Decorative panel Push

Ratch pull

Inlet Grille

CAUTION Install the decoration panel otherwise cool air leakage causes condensation. Water drops fall.

Correct method

Wrong method Air conditioner unit Cool air leakage (no good) Ceiling board Decoration panel

Air conditioner unit Ceiling board Decoration panel

Fit the insulator (this part) and be careful for cool air leakage

2-17

Ceiling Cassette 2-way


10.5 Indoor Unit Drain Piping

Upward routing not allowed

Pipe clamp

• Drain piping must have down-slope (1/50 to 1/100): Make sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Indoor unit

Maintenance drain port

1/50~1/100

• Make sure to install heat insulation on the drain piping.

MAX 700mm

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Make sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

Max 300mm

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Hanger distance 1~15m

Metal clamp Flexible drain hose

Hanger Bracket 1/50~1/100 slope Max 700mm

CAUTION

Insulation

Ceiling Cassette 2-way

2-18

Cassette 2-way

Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings


Cassette 2-way

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

2-19

Ceiling Cassette 2-way


11. Accessories Standard Accessories Name

Clamp metal

Drain hose

Insulation for fitting

Quantity

2 EA

1 EA

1 set

Washer for hanging bracket 8 EA

Clamp (Tie Wrap) 4 EA

Bolt

(Other)

4 EA

Shape

for gas pipe

for liquid pipe • Screws for fixing panels are attached to decoration panel.

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 2-way

2-20

Cassette 2-way

• Paper pattern for installation • Owner's manual • Installation manual


Cassette 4-way

Ceiling Cassette 4-way

1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Ceiling Cassette 4-way


1. List of Functions Category

Air flow

Installation

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Elevation Grill Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2, ARNU12GTR*2 ARNU15GTQ*2, ARNU18GTQ*2, ARNU24GTP*2, ARNU28GTP*2 ARNU36GTN*2, ARNU42GTM*2, ARNU48GTM*2 4 Auto O 4/5/4 X O O O X Option O O X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory (TM,TN,TP only) Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Cassette 4-way

3-1

Cassette 4-way

Air purifying

Function


2. Specifications

Cassette 4-way

* Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions(WxDxH) Front Panel Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch mm inch m2 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz mm2 mm2

ARNU05GTR*2 1.6 1,400 5,500 1.8 1,500 6,100 Galvanized Steel Plate 570x570x214 22.4x22.4x8.4 700x700x30 27.5x27.5x1.2 1x8x18 0.21 Turbo Fan 43x1 0.2 7.5/7.0/6.6 265/247/212 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25 13.1(28.9) 15.4(33.9) 36/35/33 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C Morning fog

4 Way Ceiling Cassette ARNU07GTR*2 ARNU09GTR*2 2.2 2.8 1,900 2,400 7,500 9,600 2.5 3.2 2,200 2,800 8,500 10,900 Galvanized Steel Plate Galvanized Steel Plate 570x570x214 570x570x214 22.4x22.4x8.4 22.4x22.4x8.4 700x700x30 700x700x30 27.5x27.5x1.2 27.5x27.5x1.2 1x8x18 2x8x18 0.21 0.21 Turbo Fan Turbo Fan 43x1 43x1 0.2 0.2 7.5/7.0/6.6 8.0/7.5/7.1 265/247/212 283/265/251 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25 25 13.1(28.9) 14.2(31.3) 15.4(33.9) 16.5(36.3) 36/35/33 36/35/34 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog PT-UQC

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

3-2

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 4-way


* Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity Casing Body Dimensions(WxDxH) Front Panel Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch mm inch m2 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz mm2 mm2

ARNU12GTR*2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 570x570x214 22.4x22.4x8.4 700x700x30 27.5x27.5x1.2 2x8x18 0.21 Turbo Fan 43x1 0.2 8.7/8.0/7.0 307/283/247 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25 14.2(31.3) 16.5(36.3) 36/35/34 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C Morning fog

4 Way Ceiling Cassette ARNU15GTQ*2 ARNU18GTQ*2 4.5 5.6 3,900 4,800 15,400 19,100 5.0 6.3 4,300 5,400 17,100 21,500 Galvanized Steel Plate Galvanized Steel Plate 570x570x256 570x570x256 22.4x22.4x10.1 22.4x22.4x10.1 700x700x30 700x700x30 27.5x27.5x1.2 27.5x27.5x1.2 2x10x18 2x10x18 0.27 0.27 Turbo Fan Turbo Fan 43x1 43x1 0.2 0.2 11.0/10.0/9.3 11.2/11.0/10.0 388/353/328 396/388/353 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25 25 15.5(34.2) 15.5(34.2) 18.0(39.7) 18.0(39.7) 37/36/35 38/37/36 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog PT-UQC

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Ceiling Cassette 4-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

3-3

Cassette 4-way

Unit kW kcal/h Btu/h kW kcal/h Btu/h


Cassette 4-way

* Model Name A:Basic, C:Plasma 4 Way Ceiling Cassette ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 7.1 8.2 10.6 Cooling Capacity 6,100 7,100 9,100 24,200 28,000 36,200 8.0 9.2 11.9 Heating Capacity 6,900 8,000 10,200 27,300 31,500 40,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Casing 840 x 840 x 204 840 x 840 x 204 840 x 840 x 246 Dimensions Body mm 33.0x33.0x8.0 33.0x33.0x8.0 33.0x33.0x9.7 (WxDxH) inch 950 x 950 x 25 950 x 950 x 25 950 x 950 x 25 Front Panel mm 37.4 x 37.4 x 1 37.4 x 37.4 x 1 37.4 x 37.4 x 1 inch 2 x 8 x 19 2 x 8 x 19 2x10x19 Coil Rows x Columns x FPI 0.40 0.40 0.57 Face Area m2 Turbo Fan Turbo Fan Turbo Fan Fan Type 30 30 135 Motor Outputx Number W 0.15 0.15 0.56 Running Current A 17/15/13 19/16/14 25/21/19 Air Flow Rate(H/M/L) CMM 600/529/459 671/565/494 883/742/671 cfm Direct Direct Direct Drive BLDC BLDC BLDC Motor type Microprocessor, Thermostat for cooling and heating Temperature Control Foamed polystrene Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Fuse Fuse Fuse Safety Device Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Pipe Liquid Side mm(inch) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Connections Gas Side mm(inch) 25.0 25.0 25.0 Drain Pipe(Internal Dia.) mm 20.8(45.8) 20.8(45.8) 23.5(51.8) Net Weight Body kg(lbs) 36/34/31 39/35/33 43/40/37 Noise Level (Sound Press, 1.5m, H/M/L) dB(A) 1, 220~240, 50 1, 220~240, 50 1, 220~240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV Refrigerant Control CV2.0 X 3C CV2.0 X 3C CV2.0 X 3C Power cord CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C Transmission cable Morning fog Morning fog Morning fog Panel Color PT-UMC Panel Name(Accessory) PTEGM0 Elevation Grill(Accessory) Type Model

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

3-4

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 4-way


* Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Body Front Panel

Coil Fan

Rows x Columns x FPI Face Area Type Motor Outputx Number Running Current Air Flow Rate(H/M/L)

mm inch mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight Body kg(lbs) Noise Level (Sound Press, 1.5m, H/M/L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cord Transmission cable Panel Color Panel Name(Accessory) Elevation Grill(Accessory)

4 Way Ceiling Cassette ARNU42GTM*2 ARNU48GTM*2 12.3 14.1 10,600 12,100 42,000 48,100 13.8 15.9 11,000 13,200 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate 840x840x288 840x840x288 33.0x33.0x11.3 33.0x33.0x11.3 950 x 950 x 25 950 x 950 x 25 37.4 x 37.4 x 1 37.4 x 37.4 x 1 2 x 12 x 19 2 x 12 x 19 0.57 0.57 Turbo Fan Turbo Fan 135 135 0.56 0.56 30/27/24 31/29/27 1,059/954/848 1,059/1,024/954 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) 25.0 25.0 25.6(56.4) 25.6(56.4) 44/41/38 46/43/41 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 EEV EEV CV2.0 X 3C CV2.0 X 3C CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C Morning fog Morning fog PT-UMC PTEGM0

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Ceiling Cassette 4-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

3-5

Cassette 4-way

Casing Dimensions (WxDxH)

Unit kW kcal/h Btu/h kW kcal/h Btu/h


6

5

55

380(Air outlet hole) 473 700

172

4-R 2

0 378.6 380(Air outlet hole) 700 22.5

378.6 4

523 59.5 84.5 30 19 142.5

2 1

3

79 53 48

128 570

165

461 570

517

5

(unit : mm)

Unit size(5k, 7k, 9k, 12k):ø12.7

Unit size(5k, 7k, 9k, 12k):ø6.35

Descripition

CHASSIS CODE: TR

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill

6

4

Air discharge grill

Power supply connection

3 5

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

1

Number

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

63

69

517 214

3-6 34.5

R3

570

Cassette 4-way

3. Dimensions

Ceiling Cassette 4-way


6

5

55

380(Air outlet hole) 473 700

4

30 19 142.5

2 1

3

570

165

461 570

517

5

174

R3

570

Air discharge grill Air suction grill

5 6

Unit size(15k, 18k):Ă˜12.7

Unit size(15k, 18k):Ă˜6.35

Descripition

(unit : mm)

CHASSIS CODE: TQ

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Drain pipe connection Power supply connection

4

Gas pipe connection

3

Liquid pipe connection

1

Name

ARNU15GTQ*2 ARNU18GTQ*2

2

Number

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

63

68

76 94

0 4-R 2 378.6 380(Air outlet hole) 700 22.5

378.6

523 59.5 125 95.5

172

79 48

517 256

Ceiling Cassette 4-way

Cassette 4-way

Ceiling Cassette 4-way

3-7


54

500(Air outlet hole) 734 950

4-

5

R2

0

6

500(Air outlet hole) 618 950

25

292

671

2

108 60

1

204 154

65 40

618

79 41.5

350

840

165

840

787

787

804

53.5

4

62

3

R35

Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air suction grill

3 4 5 6

Unit size(24k, 28k):ø15.88

Unit size(24k, 28k):ø9.52

Descripition

(unit : mm)

CHASSIS CODE: TP

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Liquid pipe connection

2

Name

ARNU24GTP*2 ARNU28GTP*2

1

Number

Cassette 4-way

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

80

A

204

3-8 684 840

A direction View

60 82 99

126

Ceiling Cassette 4-way


3-9

5

6

246 195

2 110

1

60 840

165

840

40

350

80

103 141

246

3

4

62

Power supply connection Air discharge grill Air suction grill

4 5 6

(unit : mm)

Unit size(36k):ø15.88

Unit size(36k):ø9.52

Descripition

CHASSIS CODE: TN

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection Drain pipe connection

2 3

Liquid pipe connection

Name

1

Number

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

53.5

A

ARNU36GTN*2

Ceiling Cassette 4-way

Cassette 4-way

Ceiling Cassette 4-way 107

126

78

A direction View

100 52

R35

25


5

6

2

1 165

840

350

53.5

3-10 100 84

3

4

A direction View 126

288

237

25

Power supply connection Air discharge grill Air suction grill

3 4 5 6

(unit : mm)

Unit size(42k, 48k):ø15.88

Unit size(42k, 48k):ø9.52

Descripition

CHASSIS CODE: TM

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

ARNU42GTM*2 ARNU48GTM*2

1

Number

Cassette 4-way

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

A

109

R35

Ceiling Cassette 4-way


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter

Th3

Th2 Turbo Fan

Th1

Cassette 4-way

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

Model

Gas

Liquid

ARNU05GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU07GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GTQ*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GTQ*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GTP*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU28GTP*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU36GTN*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU42GTM*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU48GTM*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Cassette 4-way

3-11


5. Wiring Diagrams

Cassette 4-way

TR/TQ Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

3-12

Ceiling Cassette 4-way


TM/TN/TP Chassis

Cassette 4-way

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE1 / VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 4-way

3-13


6. Capacity Tables

Cassette 4-way

6.1 Cooling Capacity

Capacity Index

1.6

2.2

2.8

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 1.6 1.5 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.8 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.2 1.1

2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.5 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.8 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.7

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.6 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.6 1.5

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

3-14

Cooling capacity

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way


Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, 째C)

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.3

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.2

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 2.0 1.9

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 1.9

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.6

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.8 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.7 3.5

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.8 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.4

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1 6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.1 3.1 3.1 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.3 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.5 3.5 3.4 3.3 3.3 3.2 3.2 2.9

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2 7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

3.3 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.8 2.7 2.6 2.6 2.4 4.1 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.3 3.2 2.9

5.6

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way

SHC: Sensible Heat Capacity(kW)

3-15

Cassette 4-way

4.5

32 24 TC SHC kW kW


Cassette 4-way

Cooling capacity

Capacity Index

7.1

8.2

10.6

Outdoor air temp. (DB, 째C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

Notes: TC: Total Capacity(kW)

3-16

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6 7.6 7.2 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.8 9.3

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5 9.8 9.8 9.8 9.8 9.7 9.6 9.5 9.4 9.4 9.3 9.2 9.0 8.9 8.8 8.6 8.5 8.3 8.1 7.5 12.7 12.7 12.7 12.6 12.5 12.4 12.3 12.2 12.1 12.0 11.8 11.7 11.5 11.3 11.2 11.0 10.7 10.5 9.7

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6 10.5 10.4 10.3 10.2 10.1 10.0 9.9 9.8 9.7 9.5 9.4 9.2 9.1 9.0 8.8 8.7 8.5 8.3 7.6 13.6 13.5 13.3 13.2 13.1 12.9 12.9 12.7 12.5 12.3 12.1 12.0 11.8 11.6 11.4 11.2 11.0 10.8 9.8

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.4 7.1

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 8.0 7.9 7.8 7.3 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.5 10.4 10.2 10.0 9.5

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.9 4.8 4.6 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.7 5.6 5.3 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.3 7.2 6.8

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.6 8.5 8.4 8.3 8.2 8.1 7.9 7.5 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.1 11.0 10.9 10.8 10.6 10.5 10.3 9.6

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.5 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 5.9 5.9 5.8 5.7 5.6 5.5 5.2 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.8 7.8 7.7 7.6 7.5 7.4 7.3 7.2 6.7

5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.2 4.1 3.8 5.7 5.7 5.7 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.8 4.8 4.4 7.4 7.4 7.4 7.4 7.3 7.2 7.2 7.1 7.1 7.0 6.9 6.8 6.7 6.6 6.5 6.4 6.3 6.2 5.7

5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.6 4.5 4.5 4.4 4.3 4.2 3.8 6.1 6.1 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.6 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.4 7.9 7.9 7.8 7.7 7.6 7.6 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.4 6.3 5.7

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way


Cooling capacity

Capacity Index

14.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4

11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.3 10.8 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.1 13.0 12.4

14.7 14.7 14.7 14.7 14.5 14.4 14.3 14.2 14.0 13.9 13.7 13.6 13.4 13.2 12.9 12.7 12.4 12.2 11.3 16.8 16.8 16.8 16.8 16.7 16.5 16.4 16.2 16.1 15.9 15.7 15.6 15.3 15.1 14.8 14.6 14.2 14.0 12.9

15.8 15.6 15.5 15.3 15.2 15.0 14.9 14.7 14.5 14.3 14.1 13.9 13.7 13.5 13.2 13.0 12.7 12.5 11.4 18.1 17.9 17.8 17.6 17.4 17.2 17.1 16.8 16.6 16.4 16.1 15.9 15.7 15.4 15.2 14.9 14.6 14.4 13.1

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way

7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.6 8.2 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.9 9.4

12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.2 12.0 11.8 11.7 11.0 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 13.9 13.8 13.5 13.4 12.6

8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.8 8.7 8.5 8.4 7.9 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.0 9.9 9.7 9.6 9.1

13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.9 12.8 12.6 12.5 12.3 12.1 11.9 11.2 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.8 14.6 14.5 14.3 14.2 13.9 13.7 12.8

9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.0 8.9 8.8 8.7 8.6 8.4 8.3 7.8 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.4 10.3 10.2 10.1 10.0 9.9 9.7 9.5 8.9

8.6 8.6 8.6 8.6 8.5 8.4 8.4 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.4 7.3 7.1 6.6 9.8 9.8 9.8 9.8 9.7 9.6 9.6 9.5 9.4 9.3 9.2 9.1 8.9 8.8 8.7 8.5 8.3 8.2 7.6

9.2 9.1 9.0 9.0 8.9 8.8 8.7 8.6 8.5 8.3 8.2 8.1 8.0 7.9 7.7 7.6 7.4 7.3 6.7 10.6 10.5 10.4 10.3 10.2 10.1 10.0 9.8 9.7 9.6 9.4 9.3 9.1 9.0 8.9 8.7 8.5 8.4 7.6

SHC: Sensible Heat Capacity(kW)

3-17

Cassette 4-way

12.3

Outdoor air temp. (DB, 째C)


Cassette 4-way

6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

1.6

2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Heating capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.9 1.9 2.0 2.0 2.0 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.9 1.9 1.9 1.9 1.9 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

Notes: TC: Total Capacity(kW)

3-18

Ceiling Cassette 4-way


Heating capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

4.5

5.6

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6 3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0 3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Cassette 4-way

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Indoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way

3-19


Cassette 4-way

Heating capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

7.1

8.2

10.6

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2 6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6 6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0 6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7

8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7

8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9

7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4

Notes: TC: Total Capacity(kW)

3-20

Ceiling Cassette 4-way


Heating capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

12.3

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9

9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8

9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8

9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4

9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0

9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

14.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3

10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0

10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9

10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4

10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9

10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way

3-21

Cassette 4-way

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


7. Air Velocity and Temperature Distribution(Reference Data) ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2 Cassette 4-way

Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m 2.0

2.0

2.0

1.5 1.0

1.5 1.0

2m

2.0 1.5

1.5 1.0

2.5m

1.5m

0m

1.5m

0m 2.5m

1.0 0.5

0.5

1m

0.5

0.5

2.5m

2m

1.5m

1m

0m

1.5m

0m 2.5m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 33

2m

18

18 20

20

22

21

21 2m 27

18

24

27

18 24

24

1m

22

33

1m

24

2.5m

1.5m

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

1.5m

0m 2.5m

ARNU12GTR*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s] 2.7m 2.0

2.7m 2.0 1.5

2.0

2m 1.5

2.0 1.5

1.0 1.0

1.0

0.5

2.5m

2m

1.5 1.0

0.5

1m

0.5

1m

0.5

1.5m

0m

1.5m

0m 2.5m

Temperature [°C]

2.5m

1.5m

0m

0m 2.5m

1.5m

Temperature [°C] 2.7m 18

2.7m 33

18

20

2m

20

22

33

30 24

22

2m

30

27

27

24

21

21

1m 24

2.5m

3-22

1.5m

1m

24

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

1.5m

0m 2.5m

Ceiling Cassette 4-way


ARNU15GTQ*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2.0 1.5

1m 0.5

1m

0m

1m

0.5

0.5

2m

3m

4m

0m

4m

3m

2m

1m

1.0

1.0

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18

18 20

20

33

33

2m

2m 22

22

21

24

24

1m

27

24

24

3m

21

1m 27

4m

0m

2m

1m

0m

1m

2m

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m

ARNU18GTQ*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2.0

1.5

2m

1.0

4m

3m

2m

1.5

1.5 1m

1.0

0.5 0m

1m

3m

4m

0m

4m

3m

2m

1m

1.0

0.5

2m

2m

1.5

1.0

0.5 1m

2.0

0.5

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18 20

18

22

33

20

2m

30

22

24

3m

2m

33

2m

30

21

1m

4m

0m

21 24

27

27

1m

24

24

1m

0m

Ceiling Cassette 4-way

1m

2m

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m

3-23

Cassette 4-way

1.0

2m

1.5

1.5

0.5 3m

2m

2m 1.5

1.0

4m

2.0


ARNU24GTP*2 Cassette 4-way

Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2m

2m 2.0

1.5

3m

1.0

1.0

1.0 4m

1m

1.5

2m

1m

0m

1m

3m

4m

0m

4m

2m

0.5

1m

0m

1m

2m

3m

4m

0m

Temperature [°C]

18 20 22

2.7m

2.7m

18 20 22

2m

23

24

2m

1m

0m

1m

2m

3m

4m

0m

4m

30

2m 22

22

3m

1m

24

24

27

23

24

33

33 30

1m

3m

3m

1m

1.0

0.5

2m

Temperature [°C]

4m

2.0

2m

1m

27

0m

1m

2m

3m

4m

0m

ARNU28GTP*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m 2.0

2m

2.0

1.0

1.0

1.0

2m

2m 1.5

1m

1.5

1.0 3m

2.7m

3.0 2.0

1.5

1m

1.5

4m

3.0 2.0

2.5

2.5

1m

0m

1m

2m

3m

4m

0m

0.5

4m

3m

2m

0.5

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18

33

18

33

2m

2m 21 22

22 23

4m

3-24

3m

2m

0m

23

1m

0m

24

1m

1m

2m

3m

4m

0m

30

30

1m

27

4m

3m

2m

21

24

1m

0m

27 1m

2m

3m

4m

0m

Ceiling Cassette 4-way


ARNU36GTN*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

3.0 2.5 2.0

2.7m

3.0 2.5 2.0

2m

1.0 5m

4m

3m

1m

0m

1m

2m

4m

0m 5m

3m

2m

1.0

1m

2.7m

0m

1m

2m

3m

4m

0m 5m

22

23

1m

0m

2m

1m

2m

3m

4m

0m 5m

30

24 22

1m 23

2m

33

2m

20

22

2.7m

33

18

20

3m

4m

1m

Temperature [°C]

18

4m

5m

2m

2.0

1.0

3m

Temperature [°C]

5m

2.0

1.0 1m

2m

2.7m

3.5 3.0 2.5

30

27

5m

4m

3m

2m

1m

24 22

1m

4m

0m 5m

27

0m

1m

2m

3m

ARNU42GTM*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

3.2m

3.2m 4.0

4.0

4.0 3.0

3.0

3.0

2m

3.0

4.0

2m

1m

5m

4m

3m

1m 2.0

2.0 1.0

2.0 1.0 1m

2m

0m

1m

2m

2.0

1.0

3m

4m

0m 5m

5m

4m

3m

2m

1.0

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C] 3.2m

3.2m

18

18

2m

20

22

22

4m

3m

2m

1m

0m

Ceiling Cassette 4-way

1m

2m

3m

33

30

30

4m

0m 5m

22

5m

4m

2m

24 22 27

24

24

33

24

20

1m

5m

0m 5m

3m

2m

1m

1m

27

0m

1m

2m

3m

4m

0m 5m

3-25

Cassette 4-way

1.5

1.5

3.5 3.0 2.5


ARNU48GTM*2 Cassette 4-way

Cooling

Heating

Discharge angle: 40째

Discharge angle: 50째

Air velocity [m/s]

Air velocity [m/s]

3.2m 4.0

1.0 4m

3m

2m

1m

0m

1m

2m

2m

3.0

3.0

1m

2.0 1.0

2.0

4.0

2m

3.0

3.0

5m

3.2m 4.0

4.0

1m 2.0

2.0

1.0

3m

4m

0m 5m

5m

4m

3m

2m

1m

1.0

0m

1m

2m

3m

4m

0m 5m

Temperature [째C]

Temperature [째C] 3.2m

3.2m 33

18

18

2m

20

20

33

2m 22

24

22

24

1m 22 24

5m

4m

3-26

24

3m

2m

1m

1m

0m

1m

2m

3m

30

30 27

22

4m

0m 5m

5m

4m

3m

2m

1m

27

0m

1m

2m

3m

4m

0m 5m

Ceiling Cassette 4-way


8. Electric Characteristicss Units Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

TR

1.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

1.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

1.25

15

0.043

0.2

30

30

1.22

15

0.03

0.17

33

33

50

220~240

MAX : 264 MIN:198

ARNU24GTP*2

TP

ARNU28GTP*2

TP

1.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

1.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

1.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

1.81

15

0.135

0.64

144

144

ARNU05GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

1.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

1.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

1.25

15

0.043

0.2

30

30

ARNU24GTP*2

TP

1.22

15

0.03

0.17

33

33

ARNU28GTP*2

TP

1.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

1.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

1.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

1.81

15

0.135

0.64

144

144

60

220

MAX : 242 MIN:198

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes( see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA + 1 MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

Ceiling Cassette 4-way

3-27

Cassette 4-way

ARNU05GTR*2


9. Sound Levels

Cassette 4-way

Overall Notes: - Sound measured at 1.5m below the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Ceiling 1.5m

Model H 29 29 30 32 36 37

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2

Sound Level dB(A) L M 26 27 26 27 27 29 27 30 32 34 34 35

Sound Level dB(A) L M 34 31 35 33 40 37 41 38 43 41

Model H 36 39 43 44 46

ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2

Sound Pressure Level ARNU07GTR*2

ARNU09GTR*2 80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

3-28

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20µPa )

80

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU05GTR*2 80

NC-60

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20 NC-15 8000

NC-65

60

10

Approximate Hearing Threshold 63

NC-20

125

250

500

1000

2000

4000

NC-15 8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 4-way


ARNU15GTQ*2 70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-60 50

NC-50

125

250

500

1000

2000

4000

NC-45

40

NC-40 NC-35

30

NC-30

NC-20

63

NC-55

10

NC-15 8000

NC-25 Approximate Hearing Threshold 63

125

ARNU24GTP*2

NC-55 NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

NC-65 NC-60

2000

4000

NC-15 8000

250

500

NC-45

40

NC-40 NC-35

30

NC-30 NC-25

10

Approximate Hearing Threshold 63

NC-15 1000 2000 4000 8000

125

250

500

1000

2000

4000

NC-15 8000

ARNU36GTN*2

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

10

NC-20

Octave Band Center Frequency (Hz)

70

NC-20

125

NC-50

80

NC-25 Approximate Hearing Threshold 63

250

500

NC-15 1000 2000 4000 8000

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

125

NC-20

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

ARNU42GTM*2

70

NC-20

125

Octave Band Center Frequency (Hz)

ARNU48GTM*2

80

80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

1000

20

NC-25 Approximate Hearing Threshold 63

10

500

NC-55

50

ARNU28GTP*2

70

50

NC-60

20

80

80

10

250

NC-65

60

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

60

70

NC-20

Octave Band Sound Pressure Level (dB re 20µPa )

10

Approximate Hearing Threshold

NC-65

60

20

NC-25

20

ARNU18GTQ*2 80

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

80

70

NC-60

125

250

500

Octave Band Center Frequency (Hz)

Ceiling Cassette 4-way

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 1000 2000 4000 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

125

NC-20

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

3-29

Cassette 4-way

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU12GTR*2 80


• Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Anti-bacteria filter

Air Intake

TEM

Remote Controll er

P

Air Outlet Wired Remote Controller(Optional)

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

3-30

50 or more

Ceiling Board

50 or more

30 or less

Ceiling Ceiling Board

Above 250 360 or less

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

30 or more

10.1 Selection of the best location

100 or more

Cassette 4-way

10. Installation

Unit:cm Floor

Ceiling Cassette 4-way


10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.

Ceiling Ceiling board

Level gauge

TM/TN/TP Chassis 875(Ceiling opening)

517

461

CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

875(Ceiling opening)

517

Unit:mm

684(Hanging bolt)

840 Unit size 840 Unit size

671

319

570

585~660(Ceiling opening)

787(Hanging bolt)

570 523

Cassette 4-way

TQ/TR Chassis 585~660(Ceiling opening)

Unit:mm

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Ceiling Cassette 4-way

3-31


Ceiling

Cassette 4-way

Nut (W3/8 or M10)

Flat washer for M10 (accessory) Ceiling board

150mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Air Conditioner body

Ceiling board Keep the length of 15~18mm between the air conditioner bottom surface and the ceiling surface

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Set screw of paper model (4 pieces) Paper model for installation

• The following parts are locally purchased. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10

Open the ceiling board along the outer edge of the paper model

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. Indoor cord Remote control cord power cord

• TR/TQ Chassis Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

INTERNET DRY1 DRY2 GND 12V

IDU

A

-

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

• TM/TN/TP Chassis Terminal Block Indoor

Terminal Block Indoor

SODU

1(L) 2(N) 3(L) 4(N)

5(A) 5(B) RD

B

POWER INPUT

YL BK

A

IDU B

INTERNET DRY1 DRY2 GND 12V A

B

A

-

-

-

-

Outdoor Unit

TO AIR FRESH KIT

WARNING Make sure that the screws of the terminal are not loose.

3-32

Ceiling Cassette 4-way


10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

Piping side Air conditioner unit

Control box cover Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)

Louver motor

Decoration panel

Display Lead wire for louver motor and display

Decoration panel fixing screws (Hexagon M5 screw)

CAUTION Inlet Grille

Install certainly the decoration panel. Cool air leakage causes sweating.

Good example

Bad example Air conditioner unit

Air conditioner unit Air

Cool air leakage (no good)

Water drops fall. Ceiling board Decoration panel Fit the insulator (this part) and be careful for cool air leakage

Ceiling Cassette 4-way

Ceiling board Decoration panel

3-33

Cassette 4-way

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter).


• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose

Hanger Bracket 1/50~1/100 slope Max 700mm

Cassette 4-way

10.5 Indoor Unit Drain Piping

Insulation

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

3-34

Ceiling Cassette 4-way


WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

TEMP

Cassette 4-way

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Cassette 4-way

3-35


11. Accessories

Cassette 4-way

Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Shape

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

for gas pipe

Bolt

(Other)

4 EA • Paper pattern for installation • Owner's manual • Installation manual

for liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

3-36

Ceiling Cassette 4-way


1. List of Functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure(E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Ceiling Concealed Duct - High Static

Ceiling Concealed Duct- High Static

Ceiling Concealed Duct (High Static)


Ceiling Concealed Duct- High Static

1. List of Functions Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2, ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2, ARNU28GBGA2 , ARNU36GBGA2, ARNU42GBGA2, ARNU48GBRA2, URNU76GB8A2, URNU96GB8A2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O X O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

4-1

Ceiling Concealed Duct - High Static


2. Specifications Type Model

Heating Capacity Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m2 Type Motor Output x Number W Running Current A Air Flow Rate(H/M/L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H/M/L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU07GBHA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 882x450x260 34.7x17.7x10.2 2x10x21 0.15 Sirocco Fan 118 0.92 8.5/7.5/6 300/265/212 8(78) 8.5/8/7.5 300/282/265 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25.0 26(57.4) 34/33/32 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Ceiling Concealed Duct -High Static ARNU09GBHA2 ARNU12GBHA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate 882x450x260 882x450x260 34.7x17.7x10.2 34.7x17.7x10.2 2x10x21 2x10x21 0.15 0.15 Sirocco Fan Sirocco Fan 118 118 0.92 0.92 10/8.5/7.5 12/10/8.5 353/300/265 424/353/300 8(78) 8(78) 8.5/8/7.5 11/8.5/7.5 300/282/265 388/300/265 6(59) 6(59) Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25.0 25.0 26(57.4) 26(57.4) 35/34/33 37/35/34 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))

Ceiling Concealed Duct - High Static

ARNU15GBHA2 4.5 3,900 15,400 5.0 4,300 17,100 Galvanized Steel Plate 882x450x260 34.7x17.7x10.2 2x10x21 0.15 Sirocco Fan 118 0.92 13.5/12/8.5 477/424/300 8(78) 13.5/12/11 477/424/388 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25.0 26(57.4) 39/38/37 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

4-2

Ceiling Concealed Duct- High Static

Cooling Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h


Ceiling Concealed Duct- High Static

Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m2 Type Motor Output x Number W Running Current A Air Flow Rate(H/M/L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H/M/L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Ceiling Concealed Duct(High Static) ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2 5.6 7.1 8.2 4,800 6,100 7,100 19,100 24,200 28,000 6.3 8.0 9.2 5,400 6,900 8,000 21,500 27,300 31,500 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 882x450x260 882x450x260 1,182x450x298 34.7x17.7x10.2 34.7x17.7x10.2 46.5x17.7x11.7 3x10x21 3x10x21 3x12x21 0.15 0.15 0.26 Sirocco Fan Sirocco Fan Sirocco Fan 118 118 390 0.92 0.92 2.30 15.5/13.5/12.4 18.3/16.9/15.5 25.9/24.1/21.8 547/477/438 646/597/547 915/851/770 8(78) 8(78) 10(98) 15.3/13.6/10.3 19/16.4/14.5 25.3/21.8/17.6 540/480/364 671/579/512 893/770/622 6(59) 6(59) 8(78) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) 25.0 25.0 25.0 26.5(58.4) 26.5(58.4) 38(83.8) 42.5/41/37 45/43/41 44/42/40 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))

4-3

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct - High Static


Cooling Capacity

Heating Capacity

Ceiling Concealed Duct(High Static) Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m2 Type Motor Output x Number W Running Current A Air Flow Rate(H/M/L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H/M/L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 10.6 12.3 14.1 9,100 10,600 12,100 36,200 42,000 48,100 11.9 13.8 15.9 10,200 11,000 13,200 40,600 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 1,182x450x298 1,182x450x298 1,230x590x380 46.5x17.7x11.7 46.5x17.7x11.7 48.4x23.2x15.0 3x12x21 3x12x21 3x13x19 0.26 0.26 0.38 Sirocco Fan Sirocco Fan Sirocco Fan 390 390 390 2.30 2.30 2.40 32.3/29/25.3 34.5/32.3/30.7 44.8/40.6/33.3 1,141/1,024/894 1,218/1,141/1,084 1,582/1,434/1,176 10(98) 10(98) 14(137) 28.4/25.3/21.8 32/28.4/27.2 44.4/39.5/33.5 1,003/893/770 1,130/1,003/961 1,568/1,395/1,183 8(78) 8(78) 10(98) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) 25.0 25.0 25.0 38(83.8) 38(83.8) 53(117) 46/44/42 48/46/45 45/43/41 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))

Ceiling Concealed Duct - High Static

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

4-4

Ceiling Concealed Duct- High Static

Type Model


Ceiling Concealed Duct- High Static

Ceiling Concealed Duct(High Static) URNU76GB8A2 URNU96GB8A2 22.4 28.0 19,300 24,100 Cooling Capacity 76,400 95,900 25.2 31.5 21,700 27,100 Heating Capacity 86,000 107,500 Galvanized Steel Plate Galvanized Steel Plate Casing 1,562x688x460 1,562x688x460 mm Dimensions(WxDxH) Body 61.5x27.1x18.1 61.5x27.1x18.1 inch 3x21x19 3x21x19 Rows x Columns x FPI Coil 0.59 0.59 Face Area m2 Sirocco Fan Sirocco Fan Type 375x2 375x2 Motor Output x Number W 4.50 4.50 Running Current A 60/50/50 72/64/64 Air Flow Rate(H/M/L) CMM 2,119/1,766/1,766 2,542/2,260/2,260 (High Mode-factory set) cfm 22(216) 22(216) Fan External Static Pressure mmAq(Pa) 64/50/50 76/64/64 Air Flow Rate(H/M/L) CMM 2,260/1,766/1,766 2,684/2,260/2,260 (Standard Mode) cfm 15(147) 15(147) External Static Pressure mmAq(Pa) Direct Direct Drive BLDC BLDC Motor type Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Temperature Control Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Air Filter Fuse Fuse Safety Device Ø9.52(3/8) Ø9.52(3/8) Liquid Side mm(inch) Ø19.05(3/4) Ø22.2(7/8) Pipe Connections Gas Side mm(inch) 25.0 25.0 Drain Pipe(Internal Dia.) mm 87(192) 87(192) Net Weight kg(lbs) 50/48/48 52/50/50 Noise Level(Sound Press, 1.5m, H/M/L) dB(A) 1, 220 ~ 240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 EEV EEV Refrigerant Control CV1.5 x 3C CV1.5 x 3C Power cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Transmission cable mm2 Type Model

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))

4-5

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct - High Static


R3

7. 5

60

114

450

260

47

20

175

75

21

49

64

24

243

5

428

6

882

212

882

87 750

932

243

119

65

108

30

115

4

450 47

133 127 106

355

158

450

219 119

Ceiling Concealed Duct - High Static 1 2

100

50

70

260

29

51

3

123 140

48 52 165

31

Air suction

6

Unit size(7k, 9k, 12k, 15k, 18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k, 9k, 12k, 15k, 18k):ø12.7 Unit size(24k):ø15.88

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BH

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air discharge

5

Drain pipe connection Power supply connection

3 4

Gas pipe connection

Liquid pipe connection

Name

2

1

Number

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

101

ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2

Ceiling Concealed Duct (High Static)

Ceiling Concealed Duct- High Static

745

3. Dimensions & Gravity point

4-6

355

224


ø1 0

0

60

152

20

298

220

23

186

450

232

49

565

243

5

6

1,182

232

1,182

87 830

1,230

1,043

243

232

115

108

29

75

4

87

355 450 158 113

219 136

4-7

Ceiling Concealed Duct - High Static

224

1

100

50

2 261

165

3

122 140

47 53

32

Unit size(28k,36k,42k):ø15.88

Unit size(28k,36k,42k):ø9.52

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BG

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction

Air discharge

5 6

Power supply connection

4

Drain pipe connection

Gas pipe connection

3

2

Name Liquid pipe connection

1

Number

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

102 51

ARNU28GBGA2 ARNU36GBGA2 ARNU42GBGA2

Ceiling Concealed Duct (High Static)

Ceiling Concealed Duct- High Static


0

R6

60

198

312

380

25

303

32

140

590

50

215

5

621

279

6

1,230

241

118 1,004

1,284 1,230

1,092

279 215

120

114

4

477 590 56 168 185 174

2

90

1

135 190 260

115

101 83

Air suction

6

(unit : mm)

Unit size(48k):ø15.88

Unit size(48k):ø9.52

Descripition

Gravity point

CHASSIS CODE: BR

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air discharge

5

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

3

Drain pipe connection Power supply connection

4

Gas pipe connection

3

Liquid pipe connection

2

Name

1

Number

ARNU48GBRA2

Ceiling Concealed Duct (High Static)

26

122 144

72 123 221

Ceiling Concealed Duct- High Static

Ceiling Concealed Duct - High Static

4-8

302


460

460

688

20

440

318

293

5

329

819

6

1,562

320

1,220

1,562

1,622

1,396

329

115

4

688 30

222

560 64

290 161

4-9

Ceiling Concealed Duct - High Static

358

68

18

109

58

122 60 70 64

397

Gas pipe connection Drain pipe connection Power supply connection Air discharge Air suction

2 3 5 6

(unit : mm)

Unit size(76k):ø19.05 Unit size(96k):ø22.2

Unit size(76k,96k):ø9.52

Descripition

Gravity point

CHASSIS CODE: B8

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

4

Liquid pipe connection

Name

1

Number

3

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

1

40 99 1

70 120

2

URNU76GB8A2 URNU96GB8A2

Ceiling Concealed Duct (High Static)

Ceiling Concealed Duct- High Static


4. Piping Diagrams

:Cooling :Heating

EEV Filter

Th3

Ceiling Concealed Duct- High Static

Heat Exchanger Th2 Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GBHA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU28GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU36GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU42GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU48GBRA2

Ø15.88(5/8)

Ø9.52(3/8)

URNU76GB8A2

Ø19.05(3/4)

Ø9.52(3/8)

URNU96GB8A2

Ø22.2(7/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Concealed Duct - High Static

4-10


5. Wiring Diagrams Ceiling Concealed Duct- High Static

BH Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

4-11

Ceiling Concealed Duct - High Static


BG Chassis Ceiling Concealed Duct- High Static

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC

LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct - High Static

4-12


Ceiling Concealed Duct- High Static

BR Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC

LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

4-13

Ceiling Concealed Duct - High Static


B8 Chassis Ceiling Concealed Duct- High Static

CONNECTOR NUMBER CN-POWER CN-MOTOR1, CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-DISPLAY CN-OPTION CN-ZONE

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact RF Remocon Option PCB Zone controller

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC Output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Dry contact line RF Remocon receiver Option PCB connector Zone controller line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct - High Static

4-14


6. Capacity Tables 6.1 Cooling Capacity Ceiling Concealed Duct- High Static

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, 째C)

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.5

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.3

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 1.9

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 1.9

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.6

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.6

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.5

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.4

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.1

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.1

Notes: TC: Total Capacity(kW)

4-15

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct - High Static


Cooling capacity

23 16 TC SHC kW kW

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.2

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.1

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.2 3.0

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1

3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.8 2.8 2.6

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.7

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.6

6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 3.3 3.1

7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.4 3.1

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.8

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 4.9 4.6

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1 5.1 5.0 4.9 4.9 4.6

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.2 4.2 3.9

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.6 4.5 4.5 4.3 4.3 3.9

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - High Static

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

4-16

Ceiling Concealed Duct- High Static

20 14 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW


Ceiling Concealed Duct- High Static

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

8.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6 7.6 7.2

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.6

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 8.0 7.9 7.8 7.3

6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 5.9 5.8 5.8 5.4

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.6 8.5 8.4 8.3 8.2 8.1 7.9 7.5

6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2 6.2 6.1 6.0 6.0 5.9 5.8 5.7 5.3

9.8 9.8 9.8 9.8 9.7 9.6 9.5 9.4 9.4 9.3 9.2 9.0 8.9 8.8 8.6 8.5 8.3 8.1 7.5

5.9 5.9 5.9 5.9 5.8 5.7 5.7 5.7 5.6 5.6 5.5 5.4 5.3 5.3 5.2 5.1 5.0 4.9 4.5

10.5 10.4 10.3 10.2 10.1 10.0 9.9 9.8 9.7 9.5 9.4 9.2 9.1 9.0 8.8 8.7 8.5 8.3 7.6

6.3 6.3 6.2 6.1 6.1 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.2 5.1 5.0 4.6

10.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2

6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.8 9.3

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.6 7.3

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.5 10.4 10.2 10.0 9.5

7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.7 7.5 7.4 7.0

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.1 11.0 10.9 10.8 10.6 10.5 10.3 9.6

8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 6.9

12.7 12.7 12.7 12.6 12.5 12.4 12.3 12.2 12.1 12.0 11.8 11.7 11.5 11.3 11.2 11.0 10.7 10.5 9.7

7.6 7.6 7.6 7.6 7.5 7.4 7.4 7.3 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.4 6.3 5.8

13.6 13.5 13.3 13.2 13.1 12.9 12.9 12.7 12.5 12.3 12.1 12.0 11.8 11.6 11.4 11.2 11.0 10.8 9.8

8.2 8.1 8.0 7.9 7.9 7.8 7.7 7.6 7.5 7.4 7.3 7.2 7.1 7.0 6.8 6.7 6.6 6.5 5.9

12.3

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9

8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.3 10.8

9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9 8.8 8.5

12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.2 12.0 11.8 11.7 11.0

9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.0 8.9 8.7 8.6 8.1

13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.9 12.8 12.6 12.5 12.3 12.1 11.9 11.2

9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.1 9.0 8.9 8.8 8.7 8.5 8.0

14.7 14.7 14.7 14.7 14.5 14.4 14.3 14.2 14.0 13.9 13.7 13.6 13.4 13.2 12.9 12.7 12.4 12.2 11.3

8.8 8.8 8.8 8.8 8.7 8.6 8.6 8.5 8.4 8.3 8.2 8.1 8.0 7.9 7.8 7.6 7.5 7.3 6.8

15.8 15.6 15.5 15.3 15.2 15.0 14.9 14.7 14.5 14.3 14.1 13.9 13.7 13.5 13.2 13.0 12.7 12.5 11.4

9.5 9.4 9.3 9.2 9.1 9.0 9.0 8.8 8.7 8.6 8.5 8.3 8.2 8.1 7.9 7.8 7.6 7.5 6.8

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

4-17

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct - High Static


Cooling capacity

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

Capacity Index

14.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5

8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5

13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.1 13.0 12.4

10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.1 9.7

14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 13.9 13.8 13.5 13.4 12.6

10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.3 10.2 10.0 9.9 9.3

15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.8 14.6 14.5 14.3 14.2 13.9 13.7 12.8

10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.7 10.6 10.5 10.4 10.2 10.1 10.0 9.8 9.2

16.8 16.8 16.8 16.8 16.7 16.5 16.4 16.2 16.1 15.9 15.7 15.6 15.3 15.1 14.8 14.6 14.2 14.0 12.9

10.1 10.1 10.1 10.1 10.0 9.9 9.8 9.7 9.7 9.6 9.4 9.3 9.2 9.1 8.9 8.8 8.6 8.4 7.8

18.1 17.9 17.8 17.6 17.4 17.2 17.1 16.8 16.6 16.4 16.1 15.9 15.7 15.4 15.2 14.9 14.6 14.4 13.1

10.8 10.8 10.7 10.5 10.4 10.3 10.3 10.1 10.0 9.8 9.7 9.5 9.4 9.3 9.1 9.0 8.8 8.6 7.8

22.4

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1

12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3

20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.9 20.6 19.7

15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.4 15.2 14.6

22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.1 21.9 21.5 21.2 20.0

15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.5 15.3 15.0 14.9 14.0

23.9 23.9 23.9 23.9 23.9 23.9 23.9 23.9 23.9 23.9 23.8 23.5 23.3 23.0 22.7 22.5 22.1 21.7 20.4

16.2 16.2 16.2 16.2 16.2 16.2 16.2 16.2 16.2 16.2 16.1 15.9 15.7 15.6 15.4 15.2 15.0 14.7 13.8

26.8 26.8 26.8 26.7 26.5 26.2 26.1 25.8 25.5 25.3 25.0 24.7 24.3 24.0 23.6 23.2 22.6 22.3 20.6

15.2 15.2 15.2 15.2 15.0 14.9 14.8 14.6 14.5 14.4 14.2 14.0 13.8 13.6 13.4 13.2 12.9 12.6 11.7

28.7 28.5 28.2 27.9 27.7 27.3 27.2 26.8 26.4 26.0 25.7 25.3 24.9 24.5 24.1 23.7 23.2 22.8 20.8

16.3 16.2 16.0 15.8 15.7 15.5 15.4 15.2 15.0 14.8 14.6 14.3 14.1 13.9 13.7 13.5 13.2 12.9 11.8

28.0

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9

16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1

22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5

17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8

26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.1 25.8 24.7

19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.0 18.2

28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 27.7 27.4 26.9 26.5 25.0

19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.4 19.2 18.8 18.6 17.5

29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.4 29.1 28.8 28.4 28.1 27.6 27.1 25.5

20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.1 19.9 19.7 19.5 19.2 19.0 18.7 18.4 17.2

33.5 33.5 33.5 33.4 33.1 32.7 32.6 32.3 31.9 31.6 31.3 30.9 30.4 30.0 29.5 29.0 28.3 27.8 25.7

19.0 19.0 19.0 19.0 18.8 18.6 18.5 18.3 18.1 17.9 17.7 17.5 17.3 17.0 16.7 16.5 16.1 15.8 14.6

35.9 35.6 35.3 34.9 34.6 34.2 34.0 33.5 33.0 32.5 32.1 31.6 31.1 30.6 30.1 29.7 29.0 28.5 26.0

20.4 20.2 20.0 19.8 19.6 19.4 19.3 19.0 18.7 18.5 18.2 17.9 17.7 17.4 17.1 16.9 16.4 16.2 14.7

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - High Static

SHC: Sensible Heat Capacity(kW)

4-18

Ceiling Concealed Duct- High Static

20 14 TC SHC kW kW

Outdoor air temp. (DB, 째C)


Ceiling Concealed Duct- High Static

6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating capacity

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

4-19

Ceiling Concealed Duct - High Static


Heating capacity

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - High Static

4-20

Ceiling Concealed Duct- High Static

Outdoor air temp. Capacity Index DB(째C) WB(째C)


Ceiling Concealed Duct- High Static

Heating capacity

Outdoor air temp. Capacity Index DB(째C) WB(째C)

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

8.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6

6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8

6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2

6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9

6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

10.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7

8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7

8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9

7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4

12.3

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9

9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8

9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8

9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4

9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0

9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

Notes: TC: Total Capacity(kW)

4-21

Ceiling Concealed Duct - High Static


Heating capacity

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

14.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3

10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0

10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9

10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4

10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9

10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

22.4

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

16.9 17.4 18.4 19.4 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 28.0 28.4 29.0 29.0 29.0 29.0 29.0

16.9 17.4 18.4 19.2 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 27.0 27.0 27.0 27.0 27.0 27.0 27.0

16.9 17.4 18.4 17.3 18.2 19.1 19.5 19.9 20.6 21.5 22.1 23.4 24.6 25.2 25.2 25.2 25.2 25.2 25.2

16.6 17.4 18.4 19.2 20.2 21.4 21.7 22.2 22.4 23.3 24.3 24.4 24.4 24.4 24.4 24.4 24.4 24.4 24.4

16.6 17.1 18.4 19.2 20.2 21.2 21.7 22.2 22.4 23.3 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7

16.6 17.1 18.1 19.2 20.2 21.2 21.4 21.6 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0

28.0

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

21.1 21.7 23.0 24.3 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 35.0 35.4 36.2 36.2 36.2 36.2 36.2

21.1 21.7 23.0 23.9 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 33.7 33.7 33.7 33.7 33.7 33.7 33.7

21.1 21.7 23.0 21.6 22.7 23.8 24.4 24.9 25.7 26.8 27.6 29.2 30.8 31.5 31.5 31.5 31.5 31.5 31.5

20.8 21.7 23.0 23.9 25.2 26.8 27.1 27.7 28.0 29.1 30.3 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

20.8 21.4 23.0 23.9 25.2 26.5 27.1 27.7 28.0 29.1 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6

20.8 21.4 22.7 24.0 25.2 26.5 26.8 27.0 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - High Static

4-22

Ceiling Concealed Duct- High Static

Outdoor air temp. Capacity Index DB(째C) WB(째C)


Ceiling Concealed Duct- High Static

7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Setting Value 70 80 90 100 110 120 130 140 145 150

(Unit: CMM)

Static Pressure(mmAq(Pa)) 3(29) 4.1 7.6 10.7 13.4 15.9 18.6 19.8 22.3 23.2 24.3

4(39) 8.1 11.2 13.2 16.2 18.8 21.1 22.2 23.1

5(49) 6.3 9.6 12.6 15.2 18.0 20.3 21.4 22.3

6(59) 4.9 7.5 10.3 12.8 15.3 17.7 19.1 21.1

7(69) 4.0 7.7 11.1 14.2 17.1 18.4 19.8

8(78) 5.5 9.1 12.4 15.5 16.9 18.3

9(88) 6.7 10.4 13.7 15.3 16.8

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2 Setting Value 70 80 90 100 110 120 130 140 143 150 160

91 96 101 106 111 116 121 126

12(118) 5.7 9.7 11.8 13.0

(Unit: CMM)

Static Pressure(mmAq(Pa)) 5(49) 4.0 12.1 17.0 21.4 25.8 30.0 36.0 37.5 41.0 42.4

6(59) 6.9 15.5 19.6 24.0 28.5 32.1 33.9 38.0 41.6

7(69) 4.13 11.01 17.53 21.8 26.93 30.41 32.1 36.0 38.2

8(78) 6.2 14.0 19.8 25.3 29.0 30.7 34.5 36.1

9(88) 4.2 11.6 17.9 23.4 27.4 28.8 32.1 35

10(98) 6.6 14.6 21.8 25.9 27.2 30.1 34.6

ARNU48GBRA2 Setting Value

10(98) 5.3 8.8 12.6 13.8 15.2

12(118) 12.1 18.1 21.6 23.0 26.3 31.1

14(137) 14.6 17.8 20.1 22.4 26.8

16(157) 11.3 14.5 16.8 18.2 23.3

(Unit: CMM) Static Pressure(mmAq(Pa))

5(49) 46.5 49.9 52.1 51.4 53.6 62.3 67.0 68.2

6(59) 43.7 46.1 50.2 51.2 53.7 61.0 64.8 67.5

8(78) 38.2 43.0 47.9 50.4 52.9 60.3 64.1 66.2

10(98) 12(118) 14(137) 15(147) 16(157) 17(168) 18(176) 20(196) 31.3 23.2 14.0 9.0 3.7 33.5 31.1 18.4 13.7 9.0 2.6 39.5 37.4 27.3 25.2 17.8 8.9 6.1 44.4 43.1 33.3 32.1 28.9 21.0 17.9 8.3 49.9 48.3 40.6 40.2 32.8 31.5 27.2 17.5 55.7 50.8 44.8 42.6 40.1 37.6 32.5 27.6 58.2 52.2 50.8 50.3 45.7 44.6 38.8 32.2 65.1 64.3 57.4 54.4 51.2 50.4 46.0 43.5

Note: 1. The above table shows the correlation between the air rates and E.S.P.

4-23

Ceiling Concealed Duct - High Static


URNU76GB8A2, URNU96GB8A2 Static Pressure(mmAq) 6(59)

9(88)

12(118)

15(147)

18(177)

20(196)

22(216)

23(226)

25(245)

60

40.5

-

-

-

-

-

-

-

-

65

52.7

-

-

-

-

-

-

-

-

70

63.7

47.1

-

-

-

-

-

-

-

75

71.1

56.9

44.7

-

-

-

-

-

-

80

76.3

69.7

55.2

-

-

-

-

-

-

85

83.3

78.6

67.4

55.9

-

-

-

-

-

91

89.7

87.1

78.9

67.6

54.2

-

-

-

-

95

93.4

91.4

86.1

77.0

66.4

50.6

30.0

-

-

100

93.4

91.4

88.3

84.9

75.9

69.5

60.8

43.1

-

105

93.2

91.3

88.3

84.9

81.1

77.4

69.2

67.9

51.3

Note: 1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct - High Static

4-24

Ceiling Concealed Duct- High Static

Setting Value

(Unit: CMM)


Ceiling Concealed Duct- High Static

ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Capacity

High 7k Standard High 9k Standard High 12k Standard High 15k Standard High (factory set) 18k Standard

24k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

120 117 115 110 107 105 125 120 117 110 107 105 130 125 120 115 110 105 135 130 120 123 120 115 140 135 130 130 125 110 150 145 140 145 135 128

8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59)

CMM 8.5 7.5 6 8.5 8 7.5 10 8.5 7.5 8.5 8 7.5 12 10 8.5 11 8.5 7.5 13.5 12 8.5 13.5 12 11 15.5 13.5 12.4 15.3 13.6 10.3 18.3 16.9 15.5 19 16.4 14.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2 Capacity

28k

High (factory set) Standard

36k

High (factory set) Standard High (factory set)

42k Standard

4-25

Standard Set value ESP(mmAq(Pa))

Mode HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

140 136 130 130 124 116 151 145 139 138 130 124 157 154 151 145 138 134

10(98) 8(78) 10(98) 8(78) 10(98) 8(78)

CMM 25.9 24.1 21.8 25.3 21.8 17.6 32.3 29 25.3 28.4 25.3 21.8 34.5 32.3 30.7 32 28.4 27.2

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

8(78)

16(157)

6(59)

10(98)

8(78)

14(137)

6(59)

10(98)

8(78)

12(118)

6(59)

10(98)

Ceiling Concealed Duct - High Static


ARNU48GBRA2 Standard Set value ESP(mmAq(Pa))

Mode High (factory set)

48k Standard

HI Mid Low HI Mid Low

116 111 106 106 101 96

14(137) 10(98)

CMM 44.8 40.6 33.3 44.4 39.5 33.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

10(98)

20(196)

7(67)

14(137)

URNU76GB8A2, URNU96GB8A2 Capacity

Standard Set value ESP(mmAq(Pa))

Mode High

76k Standard High 96k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

Ceiling Concealed Duct - High Static

102 98 98 86 83 83 105 102 102 94 89 89

22(216) 15(147) 22(216) 15(147)

CMM 60 50 50 64 50 50 72 64 64 76 64 64

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)

4-26

Ceiling Concealed Duct- High Static

Capacity


8. Electric Characteristics Ceiling Concealed Duct- High Static

Units

Power Supply

Input(W)

MFA

kW

FLA

2.32

15

0.118

1.06

150

150

BH

2.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:264

2.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

4.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

4.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

4.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

4.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

7.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

7.47

15

0.75

5.18

800

800

ARNU07GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU09GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

2.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:242

2.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

4.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

4.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

4.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

4.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

7.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

7.47

15

0.75

5.18

800

800

Model

Type

ARNU07GBHA2

BH

ARNU09GBHA2

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(Notes) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor

Hz

50

60

Volts

220~ 240

220

Voltage Range MCA

IFM

Cooling Heating

Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA + 1 MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

4-27

Ceiling Concealed Duct - High Static


9. Sound Levels Overall SUCTION

DUCT

DUCT 1.5m

2m

Model

1m 1m

Sound Level dB(A)

Ceiling Concealed Duct- High Static

DISCHARGE

Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Sound Level dB(A)

Model

ARNU07GBHA2

H 34

M 33

L 32

ARNU28GBGA2

H 44

M 42

L 40

ARNU09GBHA2

35

34

33

ARNU36GBGA2

46

44

42

ARNU12GBHA2

37

35

34

ARNU42GBGA2

48

46

45

ARNU15GBHA2

39

38

37

ARNU48GBRA2

45

43

41

ARNU18GBHA2

42.5

41

37

URNU76GB8A2

50

48

48

ARNU24GBHA2

45

43

41

URNU96GB8A2

52

50

50

Sound Pressure Level ARNU09GBHA2

ARNU12GBHA2 80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

Ceiling Concealed Duct - High Static

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20µPa )

80

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU07GBHA2 80

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

4-28


ARNU18GBHA2 70

NC-65 NC-60 NC-55 NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

NC-60

250

500

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20

125

NC-65

60

NC-15 1000 2000 4000 8000

10

Approximate Hearing Threshold 63

250

500

NC-15 1000 2000 4000 8000

NC-60

NC-50

NC-40

NC-30 20

10

NC-55 NC-50 NC-45 NC-40 NC-35 NC-30

20

10

NC-25 Approximate Hearing Threshold 63

NC-60

NC-50

250

500

NC-15 1000 2000 4000 8000

NC-45

40

NC-40 NC-35

30

NC-30

10

Approximate Hearing Threshold 63

ARNU48GBRA2

80

70

70

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

NC-15 1000 2000 4000 8000

NC-15 1000 2000 4000 8000

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

10

NC-25 Approximate Hearing Threshold 63

125

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

125

250

500

Octave Band Center Frequency (Hz)

500

NC-15 1000 2000 4000 8000

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20 NC-15 1000 2000 4000 8000

250

URNU96GB8A2

80

NC-65

NC-20

Octave Band Center Frequency (Hz)

URNU76GB8A2

60

NC-20

Octave Band Center Frequency (Hz)

4-29

Octave Band Sound Pressure Level (dB re 20µPa )

80

NC-65

500

NC-15 1000 2000 4000 8000

NC-65

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

60

250

500

60

NC-20

125

250

20

NC-25

20

NC-20

125

NC-55

50

Octave Band Sound Pressure Level (dB re 20µPa )

NC-60

NC-65

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

70

60

125

ARNU42GBGA2

ARNU36GBGA2

NC-65

NC-20

Octave Band Center Frequency (Hz)

70

30

NC-25 Approximate Hearing Threshold 63

80

40

NC-35

30

80

50

NC-45

40

80

60

NC-55

50

Octave Band Center Frequency (Hz)

ARNU28GBGA2

NC-65

60

NC-20

125

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

80

50

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU24GBHA2

80

60

Octave Band Sound Pressure Level (dB re 20µPa )

Ceiling Concealed Duct- High Static

ARNU15GBHA2 80

10

Approximate Hearing Threshold 63

NC-20

125

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct - High Static


10. Installation

Air outlet vents

Ceiling Concealed Duct- High Static

• Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air filters

Air intake vents TEMP

Wired LCD Remote Control

Remote Controller

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product • The selection of the servicing hole should be approved by the customer

Ceiling Concealed Duct - High Static

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 100cm

2

20cm to 100cm

Hole size should be more than the size of IDU.

Less than 20cm

Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.

4-30


BH/BG/BR Chassis

A B

■ Installation of Unit Install the unit above the ceiling correctly.

C E

CASE 1

D

POSITION OF SUSPENSION BOLT

(G)

F

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. • Refer to the Dimensions. (Unit:mm)

I

Ceiling Concealed Duct- High Static

10.2 Ceiling dimension and hanging bolt location

Dimension

A

B

C

D

E

F

(G)

H

I

932

882

355

47

450

30

87

750

158

BG

1232

1182

355

47

450

30

87

830

186

BR

1282 1230

477

56

590

30

H

Chassis

BH

120 1006 294

Drainage hole

B8 Chassis

(Unit:mm) Dimension

A

B

C

D

E

F

G

H

I

J

K

L

Chassis

B8

1680 1565 1160 330 460 580 700 1400 1635 390 445 15

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

M10 Nut

X4 (Local M10 SP. washer X 4 supply) M10 washer X4

M10 washer

X4

(Local M10 SP. washer X 4 supply) M10 Nut X4

4-31

Ceiling Concealed Duct - High Static


NOTE:

• Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

Old building

New building

1 Set anchor 2 Plate washer 3 Spring washer 4 Nut

CAUTION

5 Suspension bolts

Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables between Indoor Unit and Outdoor Unit Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

Ceiling Concealed Duct - High Static

4-32

Ceiling Concealed Duct- High Static

• Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators.


Ceiling Concealed Duct- High Static

THERMAL INSULATION

All thermal insulation must comply with local requirement.

INDOOR UNIT BH/BG/BR Chassis

Union for liquid pipe

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Refrigerant pipe and thermal insulator(Local supply) Hose clamp for thermal insulator (Local supply)

B8

Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe

Overlap with thermal insulator for piping. Hose clamp for thermal insulator(Local supply) Make sure that there is no clearance here.

Union for gas pipe Thermal insulator for refrigerant pipe (Local supply) Hose crip for thermal insulator (Local supply) Refrigerant pipe and therma insulator(Local supply)

Union for liquid pipe

10.4 Checking the Drainage 1) Checking the Drainage

BH/BG/BR Chassis

1. Remove the Air Filter.

B8

2. Check the drainage. • Spray one or two glasses of water on the evaporator. • Ensure that water flows through drain hose of indoor unit without any leakage.

4-33

Ceiling Concealed Duct - High Static


10.5 Indoor Unit Drain Piping

Indoor unit

Maintenance drain port

Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings • Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water

Drain Pump

Flexible drain hose (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Main drain pipe • Feed water to the flexible drain hose and check the piping for leakage. Drain • Be sure to check the drain pump for normal operation and port Glue the joint noise when electrical wiring is complete. Drain hose connection Use the clip (accessory) • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp

Max 700mm

CAUTION

Max 300mm

Flexible drain hose Insulation

Flexible drain hose Flexible drain hose Flexible drain hose

Ceiling Concealed Duct - High Static

4-34

Ceiling Concealed Duct- High Static

• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Upward routing not allowed

Pipe clamp


Ceiling Concealed Duct- High Static

10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.

Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward Vent pipe

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain. Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp Thermal insulation(bend area) Drain pan

â?ˆ Important points - The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.

4-35

Ceiling Concealed Duct - High Static


WIRED REMOTE CONTROLLER INSTALLATION

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Concealed Duct - High Static

4-36

Ceiling Concealed Duct- High Static

• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.


11. Accessories Ceiling Concealed Duct- High Static

Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

1 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

(Other)

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

4-37

Ceiling Concealed Duct - High Static


1. List of Functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Ceiling Concealed Duct - Low Static

Ceiling Concealed Duct- Low Static

Ceiling Concealed Duct (Low Static)


Ceiling Concealed Duct- Low Static

1. List of Functions Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2, ARNU18GB2G2, ARNU24GB2G2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O X O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

5-1

Ceiling Concealed Duct - Low Static


2. Specifications

Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m2 Type Motor Output x Number W Running Current A Air Flow Rate(H/M/L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H/M/L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Ceiling Concealed Duct (Low Static) ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 2x11x21 2x11x21 2x11x21 0.16 0.16 0.16 Sirocco Fan Sirocco Fan Sirocco Fan 28 28 28 0.15 0.15 0.15 8.5/7.5/6.5 9.5/8.5/7.5 10.5/9.5/8.5 300/265/229 335/300/265 371/335/300 2(20) 2(20) 2(20) 8.5/7.5/6.5 9.5/8.5/7.5 10.5/9.5/8.5 300/265/229 335/300/265 371/335/300 0(0) 0(0) 0(0) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuser Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25.4 25.4 25.4 21(46.3) 21(46.3) 21(46.3) 35/33/31 36/35/33 37/36/35 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))

Ceiling Concealed Duct - Low Static

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

5-2

Ceiling Concealed Duct- Low Static

Type Model


Ceiling Concealed Duct (Low Static) ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2 4.5 5.6 7.1 3,900 4,800 6,100 Cooling Capacity 15,400 19,100 24,200 5.0 6.3 8.0 4,300 5,400 6,900 Heating Capacity 17,100 21,500 27,300 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Casing 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 mm Dimensions(WxDxH) Body 32.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 inch 2x11x21 3x10x18 3x10x18 Rows x Columns x FPI Coil 0.16 0.23 0.23 Face Area m2 Sirocco Fan Sirocco Fan Sirocco Fan Type 28 76 76 Motor Output x Number W 0.15 0.38 0.38 Running Current A 11.5/10.5/9.5 16/14/12 19/17/15 Air Flow Rate(H/M/L) CMM 406/371/335 565/494/424 671/600/530 (High Mode-factory set) cfm 2(20) 2(20) 2(20) Fan External Static Pressure mmAq(Pa) 11.5/10.5/9.5 16/14/12 19/17/15 Air Flow Rate(H/M/L) CMM 406/371/335 565/494/424 671/600/530 (Standard Mode) cfm 0(0) 0(0) 0(0) External Static Pressure mmAq(Pa) Direct Direct Direct Drive BLDC BLDC BLDC Motor type Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Temperature Control Foamed polystrene Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Air Filter Fuser Fuse Fuse Safety Device Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Liquid Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Pipe Connections Gas Side mm(inch) 25.4 25.4 25.4 Drain Pipe(Internal Dia.) mm 21(46.3) 26(57.3) 26(57.3) Net Weight kg(lbs) 38/37/36 40/37/34 43/40/37 Noise Level(Sound Press, 1.5m, H/M/L) dB(A) 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV Refrigerant Control CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Power cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Transmission cable mm2

Ceiling Concealed Duct- Low Static

Type Model

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))

5-3

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct - Low Static


575

18

154

383

18

B1 : 448 B2 : 573

D

B A

C

6

5 13

161 14 B1 : 186 B2 : 175 B1 : 73 B2 : 81

4

3

65 60

190

2

1

Gas pipe connection Drain pipe connection Power supply connection Air discharge Air suction

2 3 4 5 6

1072

Descripition

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: B1/B2

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

Gravity point

794

D

(unit : mm)

1131

856

C

Unit size(7k, 9k, 12k, 15k, 18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k, 9k, 12k, 15k, 18k):ø12.7 Unit size(24k):ø15.88

1008

728

B

(unit: mm)

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Liquid pipe connection

Name

1100

820

A

1

Number

ARNU18GB2G2 ARNU24GB2G2

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2

Ceiling Concealed Duct- Low Static

Ceiling Concealed Duct - Low Static 216 24

Ceiling Concealed Duct (Low Static)

3. Dimensions & Gravity point

5-4

277

190


Ceiling Concealed Duct- Low Static

4. Piping Diagrams

Heat Exchanger

EEV Filter

Th3

:Cooling :Heating

Th2 Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

5-5

MODEL

GAS

LIQUID

ARNU07GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GB2G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GB2G2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Concealed Duct - Low Static


5. Wiring Diagrams B1/B2 Chassis Ceiling Concealed Duct- Low Static

CONNECTOR NUMBER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC

SPEC. Fan motor output Fan motor output Discharge pipe thermistor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

DESCRIPTION Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct - Low Static

5-6


6. Capacity Tables Ceiling Concealed Duct- Low Static

6.1 Cooling Capacity

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.2

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.2 2.1 2.0

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.0

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

5-7

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct - Low Static


Cooling capacity

23 16 TC SHC kW kW

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 2.9

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 2.9

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1

3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.7 2.6 2.4

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2

3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.7 2.5

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.6

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.5

6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.2 3.0

7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.0

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.7

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.8 4.8 4.5

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.4

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

4.9 4.9 4.9 4.9 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.2 4.1 4.1 3.8

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.2 5.2 5.1 5.1 5.0 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.5 4.5 4.4 4.3 4.2 4.2 3.8

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - Low Static

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

5-8

Ceiling Concealed Duct- Low Static

20 14 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW


Ceiling Concealed Duct- Low Static

6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

5-9

Ceiling Concealed Duct - Low Static


Heating capacity

4.5

5.6

7.1

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - Low Static

5-10

Ceiling Concealed Duct- Low Static

Outdoor air temp. Capacity Index DB(째C) WB(째C)


7. External Static Pressure (E.S.P) & Air Flow Ceiling Concealed Duct- Low Static

ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Setting Value 60 65 70 75 80 85 90 95 100 105 110 115

Static Pressure(mmAq(Pa)) 0(0) 6.02 6.95 7.69 8.46 9.5 10.35 10.81 11.57 12.58 13.31 14.2 14.82

1(10) 2.25 3.32 5.16 6.93 7.37 8.72 9.66 10.31 11.22 12.27 13.24 13.92

2(20)

3(29)

4(39)

0.61 0.73 1.19 2.42 3.4 5.33 6.75 8.56 9.75 10.89 12.15 12.64

0.54 0.65 0.77 0.87 1.35 3.15 4.73 7.46 8.64 10.49 11.16

0.48 0.56 0.63 0.72 0.88 0.98 1.03 2.31 5.01 7.7 9.48

ARNU18GB2G2, ARNU24GB2G2 Setting Value 65 70 75 80 85 90 95 100 105 110 115 120 125 130

(Unit: CMM)

(Unit: CMM) Static Pressure(mmAq(Pa))

0(0)

1(10)

2(20)

3(29)

4(39)

10.07 11.39 12.01 13.21 14.24 15.04 16.02 17.11 17.99 19.04 19.77 20.94 21.97 22.83

6.9 8.49 9.79 11.03 12.36 13.34 14.63 15.56 16.53 17.71 18.62 19.92 20.56 21.98

0.82 2.2 4.2 5.92 9.41 10.8 12.5 13.66 15.17 16.22 17.1 18.56 19.25 20.75

0.92 2.1 5.29 7.59 11.53 12.35 14.23 15.23 16.98 17.68 19.32

1.01 1.34 5.35 7.67 10.45 13.25 14.66 16.06 17.73

Note : 1. The above table shows the correlation between the air rates and E.S.P.

5-11

Ceiling Concealed Duct - Low Static


ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2

7k

High (factory set) Standard

9k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard High (factory set)

12k Standard High (factory set) 15k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

94 92 86 75 69 62 99 94 92 82 75 69 103 99 94 89 80 75 107 105 99 95 89 82

2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)

CMM 8.5 7.5 6.5 8.5 7.5 6.5 9.5 8.5 7.5 9.5 8.5 7.5 10.5 9.5 8.5 10.5 9.5 8.5 11.5 10.5 9.5 11.5 10.5 9.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

ARNU18GB2G2, ARNU24GB2G2 Capacity

18k

High (factory set) Standard

24k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

Ceiling Concealed Duct - Low Static

110 101 93 95 84 75 125 115 105 110 100 90

2(20) 0(0) 2(20) 0(0)

CMM 16 14 12 16 14 12 19 17 15 19 17 15

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

5-12

Ceiling Concealed Duct- Low Static

Capacity


8. Electric Characteristics Units Ceiling Concealed Duct- Low Static

Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

ARNU07GB1G2

B1

1.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

1.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:264

1.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

1.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

1.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

1.55

15

0.076

0.44

80

80

ARNU07GB1G2

B1

1.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

1.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:242

1.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

1.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

1.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

1.55

15

0.076

0.44

80

80

50

60

220~240

220

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(Notes) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA + 1 MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

5-13

Ceiling Concealed Duct - Low Static


9. Sound Levels Overall

1.5m

Ceiling 2.0m

Ceiling Concealed Duct- Low Static

Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Microphone

Model Name ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2

Sound Levels dB(A) H M 35 33 36 35 37 36 38 37 40 37 43 40

L 31 33 35 36 34 37

Sound Pressure Level ARNU09GB1G2

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-20 10

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

63

NC-55

50

NC-25 Approximate Hearing Threshold 63

ARNU15GB1G2

250

500

NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

NC-15 1000 2000 4000 8000

NC-45 NC-40 NC-35

30

NC-30

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU24GB2G2 80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

Ceiling Concealed Duct - Low Static

Octave Band Sound Pressure Level (dB re 20µPa )

NC-65

40

NC-50

ARNU18GB2G2

70

50

NC-55

40

NC-20

80

60

NC-60 50

Octave Band Center Frequency (Hz)

80

10

125

NC-65

60

20

10 63

Octave Band Sound Pressure Level (dB re 20µPa )

10

NC-60

20

NC-25 Approximate Hearing Threshold

NC-65

60

Octave Band Sound Pressure Level (dB re 20µPa )

80

20

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU12GB1G2

80

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU07GB1G2 80

70

NC-60

125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20 NC-15

NC-65

60

10

Approximate Hearing Threshold 63

NC-20 NC-15

125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

5-14


Ceiling Concealed Duct- Low Static

10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight. • The place shall be able to inspect the unit as given in the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product. • The selection of the servicing hole should be approved by the customer.

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 100cm

2

20cm to 100cm

Hole size should be more than the size of IDU.

Less than 20cm

Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.

Inspection hole (600X600) Control box

Top view (unit: mm)

600

600

Front view

H

5-15

Ceiling Concealed Duct - Low Static


Ceiling Concealed Duct- Low Static

10.2 Ceiling dimension and hanging bolt location ■ Installation of Unit Install the unit above the ceiling correctly.

CASE 1 POSITION OF SUSPENSION BOLT

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators.

Ceiling Concealed Duct - Low Static

5-16


• Spray one or two glasses of water on the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

10.4 Indoor Unit Drain Piping Upward routing not allowed

• Drain piping must have down-slope (1/50 to 1/100): be sure not to pro- Pipe clamp vide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the Indoor unit drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings

Maintenance drain port

• Be sure to install heat insulation on the drain piping. 1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose

Hanger Bracket 1/50~1/100 slope Max 700mm

Ceiling Concealed Duct- Low Static

10.3 Checking the Drainage

Insulation

5-17

Flexible drain hose

Ceiling Concealed Duct Flexible drain hose Flexible drain hose - Low Static


10.5 Ground drain piping

Face the vent pipe mouth downward to keep foreign matter from penetrating the system Face piping downward Vent pipe

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

10.6 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain. Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp Thermal insulation(bend area) Drain pan

â?ˆ Important points - The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.

Ceiling Concealed Duct - Low Static

5-18

Ceiling Concealed Duct- Low Static

a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.


Ceiling Concealed Duct- Low Static

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

5-19

Ceiling Concealed Duct - Low Static


11. Accessories Standard Accessories Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

(Other)

1 SET

4 EA

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Concealed Duct - Low Static

5-20

Ceiling Concealed Duct- Low Static

Name


Ceiling Concealed Duct- Built in

6

Ceiling Concealed Duct (Built in) 1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Ceiling Concealed Duct - Built in


1. List of Functions

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

Ceiling Concealed Duct- Built in

Function

Category

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O X O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Concealed Duct - Built in

6-1


Ceiling Concealed Duct- Built in

2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB30/PBSC30 PBSGB30/PBSC30 Unit ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2 kW 2.2 2.8 3.6 Cooling Capacity kcal/h 1,900 2,400 3,100 Btu/h 7,500 9,600 12,300 kW 2.5 3.2 4.0 Heating Capacity kcal/h 2,200 2,800 3,400 Btu/h 8,500 10,900 13,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 Dimensions(WxDxH) Body inch 32.3x22.6x7.5 32.3x22.6x7.5 32.3x22.6x7.5 Rows x Columns x FPI 2x11x21 2x11x21 2x11x21 Coil Face Area m2 0.16 0.16 0.16 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 30 30 Running Current A 0.15 0.15 0.15 Air Flow Rate(H/M/L) CMM 8/6.5/5.5 9/7/6 10/8/6.5 (High Mode-factor set) cfm 283/229/194 318/247/212 353/283/229 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H/M/L) CMM 8/6.5/5.5 9/7/6 10/8/6.5 (Standard Mode) cfm 283/229/194 318/247/212 353/283/229 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm 25.4 25.4 25.4 Net Weight kg(lbs) 21(46.3) 21(46.3) 21(46.3) Noise Level(Sound Press, 1m, H/M/L) dB(A) 37/34/33 39/35/34 40/37/34 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Type Accessory Model

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models

6-2

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct - Built in


Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models

Ceiling Concealed Duct - Built in

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

6-3

Ceiling Concealed Duct- Built in

Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB40/PBSC40 PBSGB40/PBSC40 Unit ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2 kW 4.5 5.6 7.1 Cooling Capacity kcal/h 3,900 4,800 6,100 Btu/h 15,400 19,100 24,200 kW 5.0 6.3 8.0 Heating Capacity kcal/h 4,300 5,400 6,900 Btu/h 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3x22.6x7.5 32.3x22.6x7.5 32.3x22.6x7.5 Rows x Columns x FPI 2x11x21 3x10x18 3x10x18 Coil Face Area m2 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 80 80 Running Current A 0.15 0.38 0.38 Air Flow Rate(H/M/L) CMM 11/10/8 14/12/10 17/15/10 (High Mode-factor set) cfm 388/353/283 494/424/353 600/530/353 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H/M/L) CMM 11/10/8 14/12/10 17/15/10 (Standard Mode) cfm 388/353/283 494/424/353 600/530/353 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm 25.4 25.4 25.4 Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1m, H/M/L) dB(A) 41/40/37 43/40/37 46/43/37 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Type Accessory Model


A

A

B

C

B

C

With Suction Grille & Suction Canvas

575

A

B3/B4

With Suction Grille & Suction Canvas

250

618

388

PBSC30 PBSC40

PBSGB30 PBSGB40

E 821 1100

D 56 56 F G 274 42~250 274 42~250

C 359 359

A 820 1100

B 910 1188

Btu/h 7k,9k,12k,15k 18,24k

With Suction Grille

6

1

4

5

Name

2

Air discharge Air suction

6

(unit : mm) Unit size(7k, 9k, 12k, 15k, 18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k, 9k, 12k, 15k, 18k):ø12.7 Unit size(24k):ø15.88

Descripition

CHASSIS CODE: B3/B4

Drain pipe connection Power supply connection

Gas pipe connection

Liquid pipe connection

60

190

5

3 4

2

1

Number

3

65

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ceiling Concealed Duct (Built in)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

500(Max)

277

With Suction Grille

388 190

216 24

6-4 190

Ceiling Concealed Duct- Built in

3. Dimensions

Ceiling Concealed Duct - Built in


4. Piping Diagrams

EEV Filter

Ceiling Concealed Duct- Built in

Heat Exchanger

:Cooling :Heating

Th2

Th3 Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Concealed Duct - Built in

6-5


5. Wiring Diagrams

Ceiling Concealed Duct- Built in

B3/B4 Chassis

CONNECTOR NUMBER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC

SPEC.

DESCRIPTION

Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEVv output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact

Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

6-6

Ceiling Concealed Duct - Built in


6. Capacity Tables 6.1 Cooling Capacity

Cooling capacity

23 16 TC SHC kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.2

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.2 2.1 2.0

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.0

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - Built in

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

6-7

Ceiling Concealed Duct- Built in

20 14 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW


Ceiling Concealed Duct- Built in

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 2.9

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 2.9

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1

3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.7 2.6 2.4

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2

3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.7 2.5

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.6

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.5

6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.2 3.0

7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.0

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.7

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.8 4.8 4.5

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.4

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

4.9 4.9 4.9 4.9 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.2 4.1 4.1 3.8

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.2 5.2 5.1 5.1 5.0 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.5 4.5 4.4 4.3 4.2 4.2 3.8

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

6-8

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct - Built in


6.2 Heating Capacity Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Ceiling Concealed Duct- Built in

Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating capacity

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct - Built in

6-9


Ceiling Concealed Duct- Built in

Heating capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

4.5

5.6

7.1

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

6-10

Ceiling Concealed Duct - Built in


7. External Static Pressure (E.S.P) & Air Flow

Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa)) 0(0)

1(10)

2(20)

3(29)

4(39)

60

6.29

3.03

0.93

-

-

65

6.61

4.84

1.52

-

-

70

7.69

5.64

2.18

0.79

-

75

8.19

6.28

2.81

0.85

-

80

8.91

7.43

4.96

1.58

-

85

9.51

8.14

5.91

2.75

0.95

90

10.21

8.76

6.79

3.41

1.36

95

10.83

9.62

8.11

5.48

2.61

100

11.31

10.55

9.02

6.12

3.31

105

11.84

11.19

9.99

8.28

5.32

110

12.68

11.88

10.38

9.16

6.92

115

13.19

12.22

11.55

10.21

8.23

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa)) 0(0)

1(10)

2(20)

3(29)

4(39)

75

10.32

7.68

3.55

-

-

80

11.06

8.77

4.71

1.38

-

85

11.84

10.02

6.95

2.16

-

90

12.73

10.74

8.26

4.73

1.25

95

13.47

12.13

9.93

6.74

2.73

100

14.16

13.25

10.51

8.41

3.65

105

15.29

14.11

12.31

9.83

6.21

110

16.09

14.77

13.49

10.39

8.32

115

16.91

15.88

14.48

12.77

9.92

120

17.81

16.88

15.15

13.98

10.85

125

18.55

17.84

16.12

15.13

12.97

130

19.01

18.55

17.33

16.28

14.59

Note : 1. The above table shows the correlation between the air rates and E.S.P. 2. E.S.P. is given after subtracting coil losses motor step factory installed 3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.

Ceiling Concealed Duct - Built in

6-11

Ceiling Concealed Duct- Built in

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)


Ceiling Concealed Duct- Built in

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) Capacity

7k

High (factory set) Standard

9k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard High (factory set)

12k Standard High (factory set) 15k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

94 88 83 74 62 56 99 89 85 82 66 58 105 94 88 90 74 62 110 105 94 96 90 74

2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)

CMM 8 6.5 5.5 8 6.5 5.5 9 7 6 9 7 6 10 8 6.5 10 8 6.5 11 10 8 11 10 8

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Capacity

18k

High (factory set) Standard

24k

High (factory set) Standard

6-12

Standard Set value ESP(mmAq(Pa))

Mode HI Mid Low HI Mid Low HI Mid Low HI Mid Low

115 103 93 100 86 74 128 118 93 116 104 74

2(20) 0(0) 2(20) 0(0)

CMM 14 12 10 14 12 10 17 15 10 17 15 10

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

Ceiling Concealed Duct - Built in


8. Electric Characteristics Units

Power Supply

Input(W)

kW

FLA

1.22

15

0.028

0.17

30

30

1.22

15

0.028

0.17

30

30

Max:264

1.22

15

0.028

0.17

30

30

Min:198

1.22

15

0.028

0.17

30

30

B4

1.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

1.55

15

0.076

0.44

80

80

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

1.22

15

0.028

0.17

30

30

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

1.22

15

0.028

0.17

30

30

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Max:242

1.22

15

0.028

0.17

30

30

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Min:198

1.22

15

0.028

0.17

30

30

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

1.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

1.55

15

0.076

0.44

80

80

Type

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Hz

50

60

220~240

220

Cooling Heating

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(Notes) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFA : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA + 1 MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use circuit breaker.

Ceiling Concealed Duct - Built in

6-13

Ceiling Concealed Duct- Built in

MFA

Model

Volts Voltage Range MCA

IFM


9. Sound Levels

Ceiling Concealed Duct- Built in

Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m

Ceiling 2.0m Microphone

Sound Levels dB(A) H M 37 34 39 35 40 37 41 40 43 40 46 43

Model Name ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

L 33 34 34 37 37 37

Sound Pressure Level

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

63

80

70

70

NC-60

250

500

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-20

125

NC-65

60

20

NC-25 Approximate Hearing Threshold

80

NC-15 1000 2000 4000 8000

10

NC-25 Approximate Hearing Threshold 63

Octave Band Center Frequency (Hz)

70

70

NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

250

500

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-15 1000 2000 4000 8000

NC-20

125

250

NC-15 1000 2000 4000 8000

500

Octave Band Center Frequency (Hz)

ARNU24GB4G2+ PBSGB40(Acc'y), PBSC40(Acc'y) 80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

NC-25

20

NC-20

Octave Band Center Frequency (Hz)

6-14

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

80

40

125

NC-55

50

ARNU18GB4G2+ PBSGB40(Acc'y), PBSC40(Acc'y)

80

50

NC-60

NC-20 NC-15 1000 2000 4000 8000

NC-65

60

Octave Band Center Frequency (Hz)

ARNU15GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

60

Octave Band Sound Pressure Level (dB re 20µPa )

NC-65

60

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

70

ARNU12GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

Octave Band Sound Pressure Level (dB re 20µPa )

80

ARNU09GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

ARNU07GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

10

Approximate Hearing Threshold 63

Approximate Hearing Threshold

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-15 8000

NC-20 NC-15

10 63

125

250

500

1000 2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct - Built in


10. Installation

Suction Grille TEMP

Remote Controller

Suction Grille + Suction Canvas

TEMP

Remote Controller

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose (Inner Dia ....................................25mm)

• Level • Screw driver • Electric drill • Hole core drill (ø70mm) • Flaring Tools set • Torque Wrenches • Hexagonal Wrench (4mm, 5mm) • Gas-leak detector • Owner’s Manual • Thermometer

Ceiling Concealed Duct - Built in

6-15

Ceiling Concealed Duct- Built in

• Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.


Install the air conditioner in the location that satisfies the following conditions.

Top view (unit:mm) Airflow

• The place shall easily bear a load exceeding four times the indoor unit’s weight.

Inspection hole (600 x 600)

• The place shall be able to inspect the unit as the figure.

Control box

• The place where the unit shall be leveled. • The place shall easily connect with the outdoor unit. 600

• The place where the unit is not affected by an electrical noise.

600

• There should not be any heat source or steam near the unit Confirm the positional relationship between the unit and suspension bolts.

270 or more

• The place where air circulation in the room will be good .

• Installation the ceiling opening to clean the filter or service under the product.

(unit : mm) Chassis

A

B

B3

600

900

B4

600

1100

520 or more

Ceiling Concealed Duct- Built in

10.1 Selection of the best location

• Refer to Suction grille and Suction canvas installation manual for detail installation of Built-in duct type

A(Min)

B3/B4 Series : Built-in Duct type

B(Min)

Ceiling Service Space

A

B

6-16

Ceiling Concealed Duct - Built in


10.2 Ceiling dimension and hanging bolt location Ceiling Concealed Duct- Built in

Installation of Unit B A J

Install the unit above the ceiling correctly.

CASE 1

C D

POSITION OF SUSPENSION BOLT

E

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. G

• Apply a filter Accessory at air return hole. (Unit:mm)

I F

Dimension

A

D

E

F

850 900 383 575 1130 1180 383 575

93 93

190 190

Chassis

B3 B4

B

C

G

H

I

J

H 21 795 163 820 21 1065 163 1100

Drainage hole

Drain Pump use

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

CASE 2 • Install the unit leaning to a drainage hole side as a figure for easy water drainage.

POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

Ceiling Concealed Duct - Built in

6-17


• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

Ceiling Concealed Duct- Built in

• Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

Old building

New building

1 Set anchor 2 Plate washer 3 Spring washer 4 Nut

CAUTION

5 Suspension bolts

Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not from loose.

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

6-18

Ceiling Concealed Duct - Built in


10.4 Part name and functions Ceiling Concealed Duct- Built in

Air outlet

Air outlet

Suction Grille Suction Grille Suction Canvas

• Buit-in duct type with Suction Grille

• Buit-in duct type with Suction Grille and Suction Canvas

■ B3/B4 Series : Built-in Duct type Control Box service

Ceiling Concealed Duct - Built in

6-19


Ceiling Concealed Duct- Built in

INSULATION, OTHERS THERMAL INSULATION

Insulate the joint and tubes completely.

All thermal insulation must comply with local requirement.

INDOOR UNIT Union for gas pipe

Refrigerant pipe and thermal insulator(Local supply)

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Hose clip for thermal insulator (Local supply) Overlap with thermal insulator for piping. Hose clip for thermal insulator(Local supply) Make sure that there is no clearance here.

Thermal insulator for refrigerant pipe (Local supply) Union for liquid pipe

Felt

Cabinet

Rubber

Insulation No clearance

TEST AND CHECK

■ After all workings are finished, check the working and operation. • Air distribution ............... Is the air circulation good? • Drain ............................. Is the drainage smoothly and no sweating? • Gas leakage ................. Is the piping connection correctly? • Wiring ........................... Is the wiring connection correctly? • Lock-bolt ....................... Is the lock-bolt of compressor loosened? • Insulation Is the unit fully insulated? • Ground Is the unit safely grounded?

10.5 Checking the Drainage 1. Remove the Air Filter.

6-20

2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

Ceiling Concealed Duct - Built in


CAUTION Ceiling Concealed Duct- Built in

1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 19mm.

Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling Drainage hole

Drain Pump use

10.6 Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Pipe clamp Indoor unit

Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings

Upward routing not allowed

Maintenance drain port

• Be sure to install heat insulation on the drain piping. Heat insulation material: Polyethylene foam with thickness more than 8 mm.

1/50~1/100 MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

Ceiling Concealed Duct - Built in

6-21


Max 300mm

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp Flexible drain hose

Max 700mm

Ceiling Concealed Duct- Built in

CAUTION : The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Insulation

CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) Flexible drain hose 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

6-22

Ceiling Concealed Duct - Built in


WIRED REMOTE CONTROLLER INSTALLATION

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Concealed Duct - Built in

6-23

Ceiling Concealed Duct- Built in

• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.


11. Accessories

Ceiling Concealed Duct- Built in

Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

(Other)

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specilications.

6-24

Ceiling Concealed Duct - Built in


7

1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Wall Mounted

Wall Mounted

Wall Mounted


1. List of Functions

Wall Mounted

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2 ARNU15GSE*2, ARNU18GS5*2, ARNU24GS5*2 1 SE Manual / S5 Auto Auto SE Manual / S5 Auto X 3/4/3 O O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

7-1

Wall Mounted


2. Specifications * Model Name A:Basic L:Plasma Type Model Cooling Capacity

Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Wall Mounted ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 895x165x282 895x165x282 895x165x282 35.2x6.5x11.1 35.2x6.5x11.1 35.2x6.5x11.1 2x15x18 2x15x18 2x15x18 0.21 0.21 0.21 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20 20 20 0.20 0.20 0.20 5.6/5/4.6 7/ 6.5 /6 9.5/ 9/8.5 198/177/162.5 247/230/212 336/318/300 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 16 16 16 9(19.8) 9(19.8) 9(19.8) 37/33/23 39/35/25 41/36/27 1, 220 ~ 240, 50 1, 220 ~240, 50 1, 220 ~240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Wall Mounted

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

7-2

Wall Mounted

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch


Wall Mounted

* Model Name A:Basic L:Plasma Type Model Cooling Capacity

Heating Capacity Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Wall Mounted ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 4.5 5.6 7.1 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 4,300 5,400 6,900 17,100 21,500 27,300 895x165x282 1,090x178x300 1,090x178x300 35.2x6.5x11.1 42.9x7x11.8 42.9x7x11.8 2x15x18 2x15x20 2x15x20 0.21 0.26 0.26 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20 20 20 0.20 0.20 0.20 10.5/9/8.5 12/10.5/9 14/13/10 371/318/300 424/371/318 494/459/353 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) 16 16 16 9(19.8) 12(26.5) 12(26.5) 42/36/27 44/40/36 46/41/38 1, 220 ~240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

7-3

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Wall Mounted


567

895

2

1

Air discharge grill Air suction grill

1 2

282

H

Descripition

(unit : mm)

165

D

(unit : mm)

282

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: SE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

895

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

Number

W

Wall Mounted

Wall Mounted Model

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

Wall Mounted

3. Dimensions

7-4

265

165


7-5

Wall Mounted

804

1,090

2

1

281

300

Air discharge grill Air suction grill

1 2

300

H

Descripition

(unit : mm)

178

D

(unit : mm)

CHASSIS CODE: S5

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

1090

ARNU18GS5*2 ARNU24GS5*2

Number

W

Model

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

178

ARNU18GS5*2 ARNU24GS5*2

Wall Mounted

Wall Mounted


4. Piping Diagrams

Heat Exchanger

EEV Filter

Th3

:Cooling :Heating

Th2

C.F.F

Wall Mounted

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

Wall Mounted

MODEL

GAS

LIQUID

ARNU07GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GS5*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GS5*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

7-6


5. Wiring Diagrams

Wall Mounted

SE Chassis

S5 Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-COM CN-DISP1 CN-DISP2 CN-EEV CN-U/D CN-TH1 CN-REMO CN-CC CN-HVB

7-7

LOCATION POINT AC Power supply Fan motor output Communication Display Display EEV output Step motor Room/pipe sensor Remote controller Dry contact Air clean

FUNCTION AC Power line input for indoor controller Motor output of BLDC Connection between indoor and outdoor Display of indoor status Display of indoor status EEV control output Step motor output Room and pipe thermistor Remote control line Dry contact line Air clean control

Wall Mounted


6. Capacity Tables 6.1 Cooling Capacity

Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, 째C)

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.2

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.8

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.7

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.2

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.1 1.9

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1 2.1 1.9

Wall Mounted

SHC: Sensible Heat Capacity(kW)

7-8

Wall Mounted

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW


Wall Mounted

Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.0

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 2.9

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.8

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1

3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.4

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2

3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.7 2.7 2.4

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.7

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.6

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 4.0 4.0 3.9 3.8 3.8 3.5

6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.4 3.4 3.3 3.2 3.0

7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

4.2 4.2 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.3 3.0

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.9 4.8 4.6

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.5

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.2 4.1 3.8

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.6 4.5 4.5 4.4 4.3 4.2 3.8

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

7-9

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Wall Mounted


6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating Capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Wall Mounted

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

Wall Mounted

7-10


Wall Mounted

Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

7-11

Wall Mounted


7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GSE*2 Cooling

Heating Discharge angle:50°

Discharge angle:45° Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m 0.5

1.5

1.0

1m

Wall Mounted

2.0 1.5

1m

1.0 0.5

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

5m

4m

3m

2m

0m 0m

1m

Temperature [°C] 2.7m

2.7m

2m

2m 21

24

18 20

33 30

1m

1m

27 22

24

5m

4m

3m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

ARNU09GSE*2 Cooling

Heating Discharge angle:50°

Discharge angle:45°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m 2.0 1.5

1.5

1m

1m

1.0 0.5

1.0 0.5

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

5m

4m

3m

2m

0m 0m

1m

Temperature [°C] 2.7m

2.7m

2m

2m 33

18 21 20

24

30

1m

1m

27 22

24

5m

4m

Wall Mounted

3m

2m

1m

0m 0m

5m

4m

3m

2m

1m

0m 0m

7-12


ARNU12GSE*2 Cooling

Heating Discharge angle:50°

Wall Mounted

Discharge angle:45°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m

2.0

2.0

1m

1m

1.5 0.5

5m

4m

3m

2m

1.0

1.0

0.5

0m 0m

1m

5m

Temperature [°C]

4m

1.5

3m

2m

0m 0m

1m

Temperature [°C] 2.7m

2.7m

2m

2m 33

18

21 30

1m

20

1m

27 24

5m

4m

24

22

3m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

ARNU18GS5*2 Cooling

Heating Discharge angle:50°

Discharge angle:45°

Air velocity [m/s]

Air velocity [m/s]

2.5 0.5

8m

7m

6m

5m

4m

3m

2.7m

2.7m

2m

2m

1m

1.5

1.0

2m

0.5

0m 0m

1m

Temperature [°C]

1m

2.0 1.0

8m

7m

6m

5m

4m

3m

2m

1.5

0m 0m

1m

Temperature [°C] 2.7m

2.7m

2m

2m 33

18 20

7m

7-13

6m

5m

4m

30

21

3m

2m

1m

0m 0m

8m

7m

6m

5m

4m

3m

1m

27

24

22

24

8m

1m

2m

1m

0m 0m

Wall Mounted


8. Electric Characteristics Units

Power Supply

Input(W)

kW

FLA

1.29

15

0.02

0.23

40

40

1.29

15

0.02

0.23

40

40

Max:264

1.29

15

0.02

0.23

40

40

Min:198

1.29

15

0.02

0.23

40

40

S5

1.29

15

0.02

0.23

40

40

ARNU24GS5*2

S5

1.29

15

0.02

0.23

40

40

ARNU07GSE*2

SE

1.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

1.29

15

0.02

0.23

40

40

ARNU12GSE*2

SE

Max:242

1.29

15

0.02

0.23

40

40

ARNU15GSE*2

SE

Min:198

1.29

15

0.02

0.23

40

40

ARNU18GS5*2

S5

1.29

15

0.02

0.23

40

40

ARNU24GS5*2

S5

1.29

15

0.02

0.23

40

40

Type

ARNU07GSE*2

SE

ARNU09GSE*2

SE

ARNU12GSE*2

SE

ARNU15GSE*2

SE

ARNU18GS5*2

Hz

50

60

Volts

220 ~ 240

220

Cooling Heating

Symbols: MCA :Min, Circuit Amps(A) MFA:Max. Fuse Amps(Notes) kW:Fan Motor Rated Output(kW) FLA:Full Load Amps(A) IFM:Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA + 1 MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

Wall Mounted

7-14

Wall Mounted

MFA

Model

Voltage Range MCA

IFM


9. Sound Levels

Wall Mounted

Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m 1m Microphone Sound Levels dB(A) H M 37 33 39 35 41 36 42 36 44 40 46 41

Model ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2

L 23 25 27 27 36 38

Sound Pressure Level

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

10

NC-25 Approximate Hearing Threshold 63

NC-60

250

500

1000

2000

4000

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

NC-65

60

NC-15 8000

10

NC-25 Approximate Hearing Threshold 63

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20µPa )

80

20

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-15 8000

NC-60

NC-50

NC-40

NC-30

10

ARNU18GS5*2

NC-55 NC-50 NC-45 NC-40 NC-35 NC-30

10

NC-25

63

7-15

NC-65 60 NC-60 50

NC-50

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20 NC-15 8000

NC-55

10 63

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20µPa )

NC-60

Octave Band Sound Pressure Level (dB re 20µPa )

NC-65

NC-20

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-15 8000

ARNU24GS5*2 70

Approximate Hearing Threshold

Approximate Hearing Threshold 63

70

20

NC-25

20

70

30

NC-35

30

80

40

NC-45

40

80

50

NC-55

50

80

60

NC-65

60

NC-20

ARNU15GSE*2

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU12GSE*2

ARNU09GSE*2 80

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU07GSE*2 80

NC-65 60 NC-60

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20 NC-15 8000

NC-55

50

NC-20 NC-15

10 63

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

8000

Wall Mounted


10. Installation • Please read the instruction sheetss completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided Wall Mounted

1. Type "A" screw 2. Installation Plate

Required Parts

Required Tools

❏ Installation plate ❏ Four type "A" screws ❏ Connecting cable

❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill

❏ Pipes: Gas side Liquid side ❏ Insulation materials ❏ Additional drain pipe

❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer

Wall Mounted

7-16


10.1 Selection of the best location

Front

Wall Mounted

• There should not be any heat source or steam near

the unit. • There should not be any obstacles to prevent air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

Left Rear left Down right Right

Rear right

More than 100mm

More than 200mm

More than 100mm More than 2300mm

The mounting wall should be strong and solid enough to protect it from vibration. 1. Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of thread and a level.

S5 chassis Installation Plate Chassis Hook

Type “A”

SE chassis Installation Plate

Chassis Hook

Type “A”

7-17

Wall Mounted


Preparing work for installation ■ Preparing the indoor unit's piping and drain hose for installation through the wall. ■ Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. ■ Replace the plastic tubing holder in the original position.

3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Wall Mounted

Loop

Tubing holder

Connecting cable Drain hose

To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.

2 Pull 1 Press

CAUTION While installing, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.

For left rear piping

Gas side piping Liquid side piping

NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. 4. Indoor unit installation ■ Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

1. Route the indoor tubing and the drain hose in the direction of rear left.

Connecting cable

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound). Drain hose

2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. ■ Do not connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

5. Connecting the pipings to the indoor unit and drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Wall Mounted

Flare nut

Pipings

7-18


■ Tighten the flare nut with a wrench.

Wall Mounted

Spanner (fixed) Flare nut Connection pipe

Torque wrench

■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Wrap with vinyl tape

Connection pipe Vinyl tape (wide)

Connecting cable

Indoor unit tubing

Pipe

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Vinyl tape(narrow)

■ Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape

Indoor unit drain hose Vinyl tape(narrow)

Pipe

Adhesive

Vinyl tape(wide) Drain hose

6. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands

For right rear piping 1. Route the indoor tubing and the drain hose to the required piping hole position.

Insulation material

2. Insert the piping, drain hose and the connecting cable into the piping hole. Connecting cable

Drain pipe

7-19

Wall Mounted


3. Insert the connecting cable into the indoor unit. ■ Don't connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

4. Tape the drain hose and the connecting cable. • Connecting cable Indoor unit drain hose

7. Wrap the insulation material around the connecting portion. ■ Overlap the connecting pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. 5. Indoor unit installation ■ Hang the indoor unit from the hooks at the top of the installation plate. ■ Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.

Plastic bands

Insulation material

■ Wrap the area which accommodates the rear piping housing section with vinyl tape.

Indoor unit Spacer

Connection pipe

Installation plate

Vinyl tape (wide)

8cm

6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Indoor unit piping Wrap with vinyl tape Pipe

Connecting cable

Vinyl tape (narrow)

Pipings

■ Tighten the flare nut with a wrench. Spanner (fixed)

Torque wrench

Flare nut Connection pipe

Indoor unit tubing

Wall Mounted

7-20

Wall Mounted

Vinyl tape(narrow) Adhesive


Wall Mounted

■ Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.

10. Indoor unit installation ■ Remove the spacer. ■ Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Pipe Drain hose

Vinyl tape (narrow)

Connecting cable

Wrap with vinyl tape(wide)

8. Reroute the pipings and the drain hose across the back of the chassis.

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Piping for passage through piping hole

9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. ■ Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Tubing holder 1 Hook

2 Push

7-21

Wall Mounted


10.2 Connection of Pipings 2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Wall Mounted

1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off. (2.1/7, 2.6/9, 3.5/12 kW/Btu models: 2EA, 3.5/18 kW/Btu models: 3EA)

Pull the right and the left side.

Screw

10.3 Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Remote control co cord

Connecting cable

Wall Mounted

7-22


Terminal Block Indoor

Wall Mounted

1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it is back in place.

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Confirm the specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between the cable length and thickness.) 7) In a wet or moist area, always install an earth leakage circuit breaker. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

7-23

Wall Mounted


WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

TEMP

Wall Mounted

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Wall Mounted

7-24


11. Accessories

Wall Mounted

Standard Accessories Name

Installation panel

Type "A" screw

Quantity

1 set

SE: 6 EA S5: 8 EA

(Other) • Owner's manual • Installation manual

SE

Shape S5

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

7-25

Wall Mounted


8

1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

ART COOL Mirror

ART COOL Mirror

ART COOL Mirror


ART COOL Mirror

1. List of Functions Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2 ARNU15GSE*2, ARNU18GS8*2, ARNU24GS8*2 1 Auto Auto Auto X 3/4/3 O O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

8-1

ART COOL Mirror


2. Specifications

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

ART COOL Mirror

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

8-2

ART COOL Mirror

ART COOL Mirror ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 2.2 2.8 3.6 1,900 2,400 3,100 Cooling Capacity 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 Heating Capacity 8,500 10,900 13,600 915x169x282 915x169x282 915x169x282 Dimensions(WxDxH) Body 36.0x6.5x11.1 36.0x6.5x11.1 36.0x6.5x11.1 2x15x18 2x15x18 2x15x18 Rows x Columns x FPI Coil 0.21 0.21 0.21 Face Area m2 Cross Flow Fan Cross Flow Fan Cross Flow Fan Type 20 20 20 Motor Output x Number W 0.20 0.20 0.20 Running Current A 7/6/4 8/7/5 10/8/6 Fan Air Flow Rate(H/M/L) CMM 247/212/141 282/247/177 353/283/212 cfm Direct Direct Direct Drive BLDC BLDC BLDC Motor type Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Temperature Control Foamed polystrene Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Resin Net(washable) Resin Net(washable) Resin Net(washable) Air Filter Fuse Fuse Fuse Safety Device Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Liquid Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Pipe Connections Gas Side mm(inch) 16 16 16 Drain Pipe(Internal Dia.) mm 11.2(24.7) 11.2(24.7) 11.2(24.7) Net Weight kg(lbs) 37/33/23 39/35/25 41/36/27 Noise Level(Sound Press, 1m, H/M/L) dB(A) 1, 220 ~ 240, 50 1, 220 ~240, 50 1, 220 ~240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV Refrigerant Control CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Power cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Transmission cable mm2 R:Mirror V:Silver B:Blue Front Panel('*' Position) Type Model


ART COOL Mirror

ART COOL Mirror ARNU15GSE*2 ARNU18GS8*2 4.5 5.6 3,900 4,800 Cooling Capacity 15,400 19,100 5.0 6.3 4,300 5,400 Heating Capacity 17,100 21,500 915x169x282 1,107x200x299 Dimensions(WxDxH) Body 36.0x6.5x11.1 43.9x7.9x11.8 2x15x18 2x15x20 Rows x Columns x FPI Coil 0.21 0.26 Face Area m2 Cross Flow Fan Cross Flow Fan Type 20 20 Motor Output x Number W 0.20 0.20 Running Current A 10.5/8/6 14.4/13/11 Fan Air Flow Rate(H/M/L) CMM 371/283/212 508/459/388 cfm Direct Direct Drive BLDC BLDC Motor type Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Temperature Control Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Resin Net(washable) Resin Net(washable) Air Filter Fuse Fuse Safety Device Ø6.35(1/4) Ø6.35(1/4) Liquid Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Pipe Connections Gas Side mm(inch) 16 16 Drain Pipe(Internal Dia.) mm 11.2(24.7) 15(33.1) Net Weight kg(lbs) 42/36/27 37/34/31 Noise Level(Sound Press, 1m, H/M/L) dB(A) 1, 220 ~240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 EEV EEV Refrigerant Control CV1.5 x 3C CV1.5 x 3C Power cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Transmission cable mm2 R:Mirror V:Silver B:Blue Front Panel('*' Position) Type Model

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

8-3

ARNU24GS8*2 7.1 6,100 24,200 8.0 6,900 27,300 1,107x200x299 43.9x7.9x11.8 2x15x20 0.26 Cross Flow Fan 20 0.20 17.9/14.4/12 632/508/424 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø9.52(3/8) Ø15.88(5/8) 16 15(33.1) 43/37/32 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

ART COOL Mirror


567

915

W

165

282

169

1

51

2

282

D

Note

282

H

Descripition

(unit : mm)

169

D

(unit : mm)

CHASSIS CODE: SE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Air suction grill

Air discharge grill

1 2

Name

915

W

Number

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

Model

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

ART COOL Mirror

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

53

ART COOL Mirror ART COOL Mirror

H

3. Dimensions

8-4

265


804

1107

1

72 58 122

2

281

93

3

200

53

4

10 63

8-5

ART COOL Mirror

48

299

Knockout hole

4

Note

Remark

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: S8

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Installation plate

Air suction grille

3

5

Display & signal receiver

2

Part Name Front panel

1

No.

ARNU18GS8*2 ARNU24GS8*2

ART COOL Mirror

ART COOL Mirror


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter Th2

Th3

C.F.F

ART COOL Mirror

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GS8*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GS8*2

Ø15.88(5/8)

Ø9.52(3/8)

*Panel Color (SE/S8 chassis) : R(Mirror),V(Silver), B(Blue) LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

ART COOL Mirror

PCB Connector CN-TH1 CN-TH2

8-6


5. Wiring Diagrams ART COOL Mirror

SE/S8 Chassis

CONNECTOR NUMBER

LOCATION POINT

FUNCTION

CN-MOTOR1

Fan motor output

Motor output of BLDC

CN-COM

Communication

Communication between indoor and outdoor

CN-EEV

EEV output

EEV control output

CN-L/R

Step motor

Step motor output for left/right

CN-U/D

Step motor

Step motor output

CN-TH1

Room/pipe sensor

Room & pipe thermistor

CN-TH2

Discharge pipe sensor

Discharge pipe thermistor

CN-SUC

Step motor(front)

Front panel step motor

CN-HVB

Air purifier

Air purifier output

CN-VFD

Display

Display of indoor status

CN-12V

Safety connection

Safety of indoor status

CN-REMO

Remote controller

Remote control line

CN-CC

Dry contact

Dry contact line

CN-HVB

Air clean

Air clean control

8-7

ART COOL Mirror


6. Capacity Tables 6.1 Cooling Capacity

Cooling Capacity

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.2

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 1.9

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1 1.9

Notes: TC: Total Capacity(kW)

ART COOL Mirror

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

8-8

ART COOL Mirror

20 14 TC SHC kW kW

Outdoor air temp. (DB, 째C)


ART COOL Mirror

Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, 째C)

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.0

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 2.9

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.8

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1

3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.4

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2

3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.7 2.7 2.4

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.7

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.6

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 4.0 4.0 3.9 3.8 3.8 3.5

6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.4 3.4 3.3 3.2 3.0

7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

4.2 4.2 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.3 3.0

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.8

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 4.9 4.6

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1 5.1 5.0 4.9 4.9 4.6

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.2 4.2 3.9

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.6 4.5 4.5 4.3 4.3 3.9

Notes: TC: Total Capacity(kW)

8-9

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

ART COOL Mirror


6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating Capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

ART COOL Mirror

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

ART COOL Mirror

8-10


ART COOL Mirror

Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

8-11

ART COOL Mirror


7. Air Velocity and Temperature Distribution ARNU07GSE*2 Cooling

Heating

Discharge angle:45°

Discharge angle:60° Air velocity [m/s]

Air velocity [m/s]

2.7m

2m

2m

2.0

2.0

1.5

1m

1m 1.5 1.0

0.5

0.5

5m

4m

3m

2m

0m 0m

1m

5m

4m

1.0

3m

2m

0m 0m

1m

Temperature [°C]

Temperature [°C]

2.7m

2.7m

2m

2m 33

18 30 20

1m

1m 24

22

21

24

5m

4m

3m

2m

1m

0m 0m

5m

4m

27

3m

2m

0m 0m

1m

ARNU12GSE*2 Cooling

Heating

Discharge angle:45°

Discharge angle:60° Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m 2.0

2.0 1.5

1m

1.5

0.5 0.5

5m

4m

3m

1m

1.0

1.0

2m

1m

0m 0m

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

Temperature [°C] 2.7m

2.7m

2m

2m 33

18

30

1m

21

1m 20 24

5m

4m

3m

ART COOL Mirror

24

27

22

2m

1m

0m 0m

5m

4m

3m

2m

1m

0m 0m

8-12

ART COOL Mirror

2.7m


8. Electric Characteristics Units ART COOL Mirror

Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

ARNU07GSE*2

SE

1.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

1.29

15

0.02

0.23

40

40

ARNU12GSE*2

SE

Max:264

1.29

15

0.02

0.23

40

40

ARNU15GSE*2

SE

Min:198

1.29

15

0.02

0.23

40

40

ARNU18GS8*2

S8

1.29

15

0.02

0.23

35

35

ARNU24GS8*2

S8

1.29

15

0.02

0.23

35

35

ARNU07GSE*2

SE

1.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

ARNU12GSE*2

SE

ARNU15GSE*2

SE

ARNU18GS8*2 ARNU24GS8*2

50

220 ~ 240

1.29

15

0.02

0.23

40

40

Max:242

1.29

15

0.02

0.23

40

40

Min:198

1.29

15

0.02

0.23

40

40

S8

1.29

15

0.02

0.23

35

35

S8

1.29

15

0.02

0.23

35

35

60

220

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA + 1 MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA.

8-13

ART COOL Mirror


9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m 1m

ART COOL Mirror

Microphone Sound Levels dB(A)

Model

H 37 39 41 42 37 43

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2

M 33 35 36 36 34 37

L 23 25 27 27 31 32

Sound Pressure Level ARNU07GSE*2

80

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

63

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-25 Approximate Hearing Threshold

70

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

10

Octave Band Sound Pressure Level (dB re 20µPa )

NC-60

Octave Band Sound Pressure Level (dB re 20µPa )

Approximate Hearing Threshold 63

NC-60

NC-50

NC-40

NC-30

10

ARNU24GS8*2 70

NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

Octave Band Sound Pressure Level (dB re 20µPa )

70

NC-65

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

ART COOL Mirror

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

ARNU18GS8*2

70

30

NC-25 Approximate Hearing Threshold 63

80

40

NC-35

30

80

50

NC-45

40

80

60

NC-55

50

20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

ARNU15GSE*2

NC-65

60

NC-20

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

NC-65

60

20

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU12GSE*2 80

70

70

10

ARNU09GSE*2

80

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-25

20

10

Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

8-14


ART COOL Mirror

10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Type "A" screw 2. Installation Plate

Required Parts

Required Tools

❏ Installation plate ❏ Four type "A" screws ❏ Connecting cable

❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill

❏ Pipes: Gas side Liquid side ❏ Insulation materials ❏ Additional drain pipe

❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer

8-15

ART COOL Mirror


10.1 Selection of the best location

More than 100mm

More than 200mm

• There should not be any heat source or steam near the

More than 100mm More than 2300mm

S8 chassis Installation Plate

Chassis Hook

The mounting wall should be strong and solid enough to protect it from the vibration. Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of the thread and a level.

ART COOL Mirror

unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

Type “A”

SE chassis Installation Plate

Chassis Hook

Type “A”

The lower left and the right side of Installation Plate

S8 chassis

Installation plate 133mm

100mm

Installation plate

110mm

Ø70mm

Ø70mm

Ø70mm

Ø70mm

85mm

Left rear piping

Right rear piping

110mm

SE chassis

Left rear piping

65mm

Right rear piping

CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.

ART COOL Mirror

8-16


ART COOL Mirror

Preparing work for installation ■ Preparing the indoor unit's piping and drain hose for installation through the wall. ■ Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. ■ Replace the plastic tubing holder in the original position.

3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Tape Connecting pipe Drain hose

Connecting cable

NOTICE : If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.

For right rear piping

*Foamed polyethylene or equivalent is recommended.

1. Route the indoor tubing and the drain hose in the direction of rear left.

4. Indoor unit installation ■ Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Drain hose

Connecting cable

Drain hose

2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. ■ Do not connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

8-17

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

ART COOL Mirror


5. Connecting the pipings to the indoor unit and drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Wrap with vinyl tape

Connection pipe Vinyl tape (wide)

Connecting cable

Indoor unit tubing

Flare nut

Pipings Vinyl tape(narrow)

■ Tighten the flare nut with a wrench. Spanner (fixed) Flare nut Connection pipe

Torque wrench

■ Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape Pipe

Indoor unit tubing

■ Mount the clamp on the boss with a type "B" screw.(optional)

Type "B" screw

Drain hose

Clamp Boss

Vinyl tape(wide) Drain hose

For left rear piping 1. Route the indoor tubing and the drain hose to the required piping hole position.

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Indoor unit drain hose Vinyl tape(narrow) Adhesive

6. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. Plastic bands

ART COOL Mirror

2. Insert the piping, drain hose and the connecting cable into the piping hole.

Connecting cable Drain pipe

Insulation material

8-18

ART COOL Mirror

Pipe


ART COOL Mirror

3. Insert the connecting cable into the indoor unit. ■ Don't connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

4. Tape the drain hose and the connecting cable. • Connecting cable Indoor unit drain hose Vinyl tape(narrow) Adhesive

5. Indoor unit installation ■ Hang the indoor unit from the hooks at the top of the installation plate. ■ Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.

Indoor unit Spacer

Plastic bands

Insulation material

■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Connection pipe

Installation plate 80mm

Vinyl tape (wide)

6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

7. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.

Flare nut

Indoor unit piping Wrap with vinyl tape Pipe

Connecting cable

Vinyl tape (narrow)

Pipings

■ Tighten the flare nut with a wrench.

Spanner (fixed)

Torque wrench

Flare nut Connection pipe

Indoor unit tubing

8-19

ART COOL Mirror


■ Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.

9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. ■ Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Pipe Drain hose

Wrap with vinyl tape(wide)

8. Reroute the pipings and the drain hose across the back of the chassis.

ART COOL Mirror

Vinyl tape (narrow)

Tubing holder

10. Indoor unit installation ■ Remove the spacer. ■ Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting cable

Piping for passage through piping hole

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

ART COOL Mirror

8-20


ART COOL Mirror

10.2 Connection of Pipings 1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.

2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Connecting area drain hose

Leakage checking Drain pan

Drain hose Leakage checking

Front panel

■ The drain hose should point downward for easy drain flow. Downward slope

■ Do not make drain piping. Accumulated drain water Air

Do not raise

Water leakage

Water leakage

Waving

Tip of drain hose dipped in water Water leakage

Less than 50mm gap

Ditch

10.3 Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Remote control co cord

Connecting cable

8-21

ART COOL Mirror


SODU

Terminal Block Indoor 1(L1) 2(L2)

3

4

B

A

IDU -

-

INTERNET DRY1 DRY2 GND 12V Outdoor unit B A -

INDOOR POWER INPUT

ART COOL Mirror

2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it is back into its original place.

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.) 7) Always install an earth leakage circuit breaker in a wet or moist area. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

ART COOL Mirror

8-22


ART COOL Mirror

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

8-23

ART COOL Mirror


11. Accessories Standard Accessories Name

Installation panel

Type "A" screws and plastic anchors

Quantity

1 set

4 set

(Other)

SE

Shape

S8

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

ART COOL Mirror

8-24

ART COOL Mirror

• Owner's manual • Installation manual


ART COOL Gallery

9

ART COOL Gallery ART COOL Panel 1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Electric Characteristics 8. Sound Levels 9. Installation 10. Accessories

ART COOL Gallery


1. List of Functions Category

Air flow

Installation

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GSF*2, ARNU09GSF*2, ARNU12GSF*2 3 X Auto X O 3/4/3 X O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory Accessory -

ART COOL Gallery

Air purifying

Function

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

ART COOL Gallery

9-1


ART COOL Gallery

2. Specifications

Type Model Cooling Capacity

Heating Capacity Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Front Panel('*' Position)

Ø, V, Hz mm2 mm2

ART COOL Gallery ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 600x146x600 600x146x600 600x146x600 23.6x5.7x23.6 23.6x5.7x23.6 23.6x5.7x23.6 2x20x21 2x20x21 2x20x21 0.18 0.18 0.18 Turbo Fan Turbo Fan Turbo Fan 30 30 30 0.16 0.16 0.16 8.1/6.3/4.2 8.1/6.3/4.2 9.3/7.7/6.0 286/222/148 286/222/148 328/272/212 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 12.2 12.2 12.2 15(33.1) 15(33.1) 15(33.1) 38/32/27 38/32/27 44/38/32 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C E:Red, V:Silver, G:Gold, 1: Kiss (Photo changeable)

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

9-2

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

ART COOL Gallery


ART COOL Gallery

1

Fix Hole

500

Pipe Hole

W

Hanger Hole

1

H

D

1

Air discharge grill Air suction grill

1 2

600

H

Descripition

(unit : mm)

146

D

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: SF

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

600

W

Number

ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2

Model

ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2

ART COOL Gallery

ART COOL Gallery

2

3. Dimensions

9-3

525


ART COOL Gallery

4. Piping Diagrams

Heat Exchanger Th3

EEV

:Cooling :Heating

Filter

Th2

Turbo Fan

Filter

Th1

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

Model

Gas

Liquid

ARNU07GSF*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GSF*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GSF*2

Ø12.7(1/2)

Ø6.35(1/4)

* Panel color:E(Red), V(Silver), G(Gold), 1(Kiss (Photo changeable))

9-4

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

PCB Connector CN-TH1 CN-TH1

ART COOL Gallery


5. Wiring Diagrams SF Chassis

ART COOL Gallery

CONNECTOR NUMBER CN-MOTOR1 CN-COM CN-EEV CN-D1 CN-LR1 CN-LR2 CN-UD CN-TH1 CN-TH2 CN-REMO CN-CC CN-HVB

ART COOL Gallery

LOCATION POINT Fan motor output Communication EEV output Display Step motor Step motor Step motor Room/pipe sensor Discharge pipe sensor Remote controller Dry contact Air clean

FUNCTION Motor output of BLDC Communication between indoor and outdoor EEV control output Display of indoor status Step motor output for left/right Step motor output for left/right Step motor output Room and pipe thermistor Discharge pipe thermistor Remote control line Dry contact line Air clean control

9-5


6. Capacity Tables ART COOL Gallery

6.1 Cooling Capacity Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, 째C)

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.2

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 1.9

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1 1.9

Notes: TC: Total Capacity(kW)

9-6

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

ART COOL Gallery


6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating Capacity

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

ART COOL Gallery

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

ART COOL Gallery

9-7


7. Electric Characteristics ART COOL Gallery

Units Model

Type

ARNU07GSF*2

SF

ARNU09GSF*2

SF

ARNU12GSF*2

SF

ARNU07GSF*2

SF

ARNU09GSF*2

SF

ARNU12GSF*2

SF

Power Supply Hz 50

Volts 220 ~ 240

60

220

Voltage Range MCA Max:264 Min:198

Max:242 Min:198

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

1.23

15

0.024

0.18

35

35

1.23

15

0.024

0.18

35

35

1.23

15

0.024

0.18

35

35

1.23

15

0.024

0.18

35

35

1.23

15

0.024

0.18

35

35

1.23

15

0.024

0.18

35

35

Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes( see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA + 1 MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.

9-8

ART COOL Gallery


8. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m

ART COOL Gallery

0.8m Microphone Sound Levels dB(A)

Model

H

M

L

ARNU07GSF*2

38

32

27

ARNU09GSF*2

38

32

27

ARNU12GSF*2

44

38

32

Sound Pressure Level ARNU07GSF*2 ARNU09GSF*2

ARNU12GSF*2 80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20

NC-20

Approximate Hearing Threshold

NC-15

10 63

NC-25

20

Approximate Hearing Threshold 125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ART COOL Gallery

NC-20 NC-15

10 63

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

9-9


ART COOL Gallery

9. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Installation guide map

2. Type "A" screw and plastic anchors

Required Parts

Required Tools

❏ Four type "A" screws ❏ Connecting cable ❏ Pipes: Gas side Liquid side

❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill ❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer

❏ Insulation materials ❏ Additional drain pipe

9.1 Selection of the best location • Do not have any heat or steam near the unit. • Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 500mm. The unit should be installed as high on the wall as possible, allowing a minimum of 200mm from ceiling. • Use a stud finder to locate studs to prevent unnecessary damage to the wall.

9-10

More than 200mm More than 500mm

More than 500mm More than 1500mm

ART COOL Gallery


9.2 Preparing Work for Installation Open panel front 1. Pull the upper part of the front panel. 2. Lift up the panel. 3. To detach the front panel, remove the two screws at the lower part. 4. Detach the front panel from the body. ART COOL Gallery

5. To detach the panel, disconnect the connector at the upper part.

Panel Front Connector

Cover pipe and cover side remove 1. Please remove the screw of the center tuning cover. 2. Pull up the side cover of desired connecting direction, then cover side is separated. 3. Pick the pipe hole of the side cover.

CAUTION: After removing the pipe hole, cut the burr for safety.

Pipe hole Side cover

NOTICE

When making pipe path through rear wall, you don’t need to pick the pipe hole.

Drain hose junction 1. Remove the rubber stopple in the desired drain direction. 2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by. Adhesive

Onlythe the Only desired desireddirection direction

Connecting part Drain hose

ART COOL Gallery

rubber cap

9-11


ART COOL Gallery

9.3 Fixing Indoor Unit 1. Attach an Installation guide map on the desired surface. INSTALLATION GUIDE MAP

2. Look at suited horizon by horizontal meter on the horizontal setting line, and fix lightly the map by adhesive tape. Horizontality

3. Make a hole with a diameter of 6mm and depth of 30-35mm by piercing a screw point. IN ST AII AT IO N

IN ST AL LA TIO N

GU ID EM AP

4. Drill the pierted part as a diameter of 50mm for connecting piping. (In case of piercing rear surface)

GU ID EM AP

5. Drive the fore plastic anchors into drilled points. IN ST AL LA TIO N

6. First, Drive the two points of the upper parts by screws. (Leave 10mm for hanging the product)

GU ID EM AP

mm

10

Plastic anchors

7. Hang the hole of product at the upper screws, and remove the map. (Falling attention) INS TAL LAT ION GUID EM AP

IN ST AL LA TIO N

GU

8. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws. Plastic anchors

Hanger hole (Rear side of the product)

9. Check the fixed product with light power.

9-12

10. In case of nothing wrong, connect the pipe and the wire. (Refer to installation manual)

ART COOL Gallery


9.4 Connecting the Piping Preparing the indoor unit's piping and drain hose for installation through the wall. 1. Route the indoor tubing and the drain hose in the direction of rear left or right

3. Connecting the pipings to the in door unit and drain hose to drain pipe ❏ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Flare nut

ART COOL Gallery

Indoor unit tubing

Pipings

❏ Tighten the flare nut with a wrench.

Drain hose

Spanner (fixed) Flare nut

2. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Torque wrench

Connection pipe

Indoor unit tubing

❏ When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Loop

Connecting cable

Gas side piping Liquid side piping

Drain hose

CAUTION: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.

ART COOL Gallery

Indoor unit drain hose Adhesive

Vinyl tape(narrow)

4. Wrap the insulation material around the connecting portion. ❏ Overlap the connecting pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands Insulation material

9-13


ART COOL Gallery

CAUTION: Installation Information For right piping. Follow the instruction below. Good case • Press on the upper side of clamp and unfold the tubing to downward slowly.

Bad case • Following bending type from left to right may cause damage to the turbing.

9.5 Drain Piping 1) To check the drainage. • Pour a glass of water on the evaporator. • Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

2) Drain piping • The drain hose should point downward for easy drain flow. Downward slope

• Do not make drain piping. Do not raise

Accumulated drain water

Tip of drain hose dipped in water Less than 50mm gap

Air

Water leakage

9-14

Water leakage

Waving

Water leakage

Ditch

ART COOL Gallery


9.6 Panel Front Assembly 1. First, Check the side cover assembly exactly, and fix the power cord in the bottom groove of cover side left.

ART COOL Gallery

2. Assemble connecting lead wire with controller, fix the upper part of panel front, and match the lower part of panel front. Panel Front Connector

3. Screw up panel front, and suspend the hook of panel front in the groove.

ART COOL Gallery

9-15


ART COOL Gallery

9.7 Connect the cable to the Indoor unit. • Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) The earth wire should be longer than the common wires. Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

CAUTION • When installing, refer to the circuit diagram on the Control Box of Indoor Unit. • When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.

CAUTION • The above circuit diagram is subject to change without notice. • Be sure to connect wires according to the wiring diagram. • Connect the wires firmly, so that not to be pulled out easily. • Connect the wires according to color codes by referring the wiring diagram.

9-16

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power circuit specifically for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Confirm the specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. 7) Always install an earth leakage circuit breaker in a wet or moist area. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

ART COOL Gallery


WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

TEMP

ART COOL Gallery

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

ART COOL Gallery

9-17


10. Accessories ART COOL Gallery

Standard Accessories Name

Installation guide map

Quantity

1 EA

Type "A" screws and plastic anchors

(Other)

4 SET

• Owner's manual • Installation manual Shape

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

9-18

ART COOL Gallery


Ceiling & Floor Ceiling Suspended 1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Electric Characteristics 8. Sound Levels 9. Installation 10. Accessories

Ceiling & Floor Ceiling Suspended

Ceiling & Floor/Ceiling Suspended

10


1. List of Functions

Ceiling & Floor/Ceiling Suspended

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU09GVEA2, ARNU12GVEA2 ARNU18GVJA2, ARNU24GVJA2 1 Manual Auto X O 3/4/3 X O O X X O X X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

10-1

Ceiling & Floor Ceiling Suspended


2. Specifications

Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Ceiling & Floor ARNU09GVEA2 ARNU12GVEA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 900x200x490 900x200x490 35.4x7.9x19.3 35.4x7.9x19.3 2x12x20 2x12x20 0.10 0.10 Cross Flow Fan Cross Flow Fan 27 27 0.15 0.15 7.6/6.9/6.2 9.2/7.6/6.9 268/243/219 325/268/244 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 16 16 13.7(30.2) 13.7(30.2) 36/32/28 38/36/30 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Ceiling & Floor Ceiling Suspended

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

10-2

Ceiling & Floor/Ceiling Suspended

Type Model


Ceiling & Floor/Ceiling Suspended

Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch m2 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2 5.6 7.1 4,800 6,100 19,100 24,200 6.3 8.0 5,400 6,900 21,500 27,300 Galvanized Steel Plate+Painting Galvanized Steel Plate+Painting 950x220x650 950x220x650 37.4x8.7x25.6 37.4x8.7x25.6 3x14x19 3x14x19 0.23 0.23 Sirocco Fan Sirocco Fan 60 60 0.30 0.30 16/ 14 /12 18/16/14 565/495/424 636/565/495 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) 16 16 24.6(54.2) 24.6(54.2) 42/40/37 43/41/39 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

10-3

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling & Floor Ceiling Suspended


Air suction grill

587

<Ceiling Installation>

Air discharge grill

900 1

24 2

490

Air discharge grill Air suction grill

1 2

490

H

Descripition

(unit : mm)

200

D

(unit : mm)

CHASSIS CODE: VE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

900

ARNU09GVEA2 ARNU12GVEA2

Number

W

ARNU09GVEA2 ARNU12GVEA2

Ceiling & Floor

Model

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

<Floor Installation>

200

Signal receiver & Operation indicator

273

Ceiling & Floor Ceiling Suspended

10-4

Ceiling & Floor/Ceiling Suspended

879

3. Dimensions


950

800

1

2

41

650

10-5

Ceiling & Floor Ceiling Suspended

Note

650

H

Descripition

(unit : mm)

220

D

(unit : mm)

CHASSIS CODE: VJ

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Air suction grill

1 2

Name Air discharge grill

Number

950

ARNU18GVJA2 ARNU24GVJA2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Ceiling Suspended type)

220

W

Model

ARNU18GVJA2 ARNU24GVJA2

Ceiling Suspended

Ceiling & Floor/Ceiling Suspended


4. Piping Diagrams VE

Th3

EEV

:Cooling :Heating

Filter

Th2 C.F.F.

Th1

Filter

lndoor unit

VJ Heat Exchanger

EEV

:Cooling :Heating

Filter

Th2

Th3 Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

Model

Gas

Liquid

ARNU09GVEA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GVEA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GVJA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GVJA2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling & Floor Ceiling Suspended

10-6

Ceiling & Floor/Ceiling Suspended

Heat Exchanger


5. Wiring Diagrams

Ceiling & Floor/Ceiling Suspended

VE Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-DISPLAY CN-DOOR CN-CC

SPEC.

DESCRIPTION

AC power supply Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Option pwb. Communication Drain pump output AC power supply Display wire Door lock switch Dry contact

AC power line input for indoor controller Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV Control output Communication between main and option Communication between indoor and outdoor AC Output for drain pump AC Power line input for indoor controller Display wire line Door lock switch line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

10-7

Ceiling & Floor Ceiling Suspended


VJ Chassis Ceiling & Floor/Ceiling Suspended

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-DISPLAY CN-DOOR CN-CC

SPEC.

DESCRIPTION

AC power supply Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Option pwb. Communication Drain pump output AC power supply Display wire Door lock switch Dry contact

AC power line input for indoor controller Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV Control output Communication between main and option Communication between indoor and outdoor AC Output for drain pump AC Power line input for indoor controller Display wire line Door lock switch line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling & Floor Ceiling Suspended

10-8


6. Capacity Tables

Ceiling & Floor/Ceiling Suspended

6.1 Cooling Capacity

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 1.5

3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.5

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.3

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 1.9

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1 1.9

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.7

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.6

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 4.0 4.0 3.9 3.8 3.8 3.5

6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.4 3.4 3.3 3.2 3.0

7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

4.2 4.2 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.3 3.0

Capacity Index

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

10-9

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling & Floor Ceiling Suspended


Cooling capacity

Outdoor air temp. (DB, 째C)

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

Notes: TC: Total Capacity(kW)

Ceiling & Floor Ceiling Suspended

20 14 TC SHC kW kW

23 16 TC SHC kW kW

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 4.9 4.8 4.6

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.5

30 22 TC SHC kW kW 8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.2 4.1 3.8

32 24 TC SHC kW kW 9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.6 4.5 4.5 4.4 4.3 4.2 3.8

SHC: Sensible Heat Capacity(kW)

10-10

Ceiling & Floor/Ceiling Suspended

Capacity Index

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW


Ceiling & Floor/Ceiling Suspended

6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Notes: TC: Total Capacity(kW)

10-11

Ceiling & Floor Ceiling Suspended


Heating capacity

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Ceiling & Floor Ceiling Suspended

10-12

Ceiling & Floor/Ceiling Suspended

Outdoor air temp. Capacity Index DB(째C) WB(째C)


7. Electric Characteristics Units Ceiling & Floor/Ceiling Suspended

Model

Type

ARNU09GVEA2 ARNU12GVEA2 ARNU18GVJA2 ARNU24GVJA2

VE VE VJ VJ

ARNU09GVEA2 ARNU12GVEA2 ARNU18GVJA2 ARNU24GVJA2

VE VE VJ VJ

Power Supply Hz

50

Volts

220 ~ 240

60

220

Voltage Range MCA Max:264 Min:198

Max:242 Min:198

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

1.22 1.22

15 15

0.027 0.027

0.17 0.17

30 30

30 30

1.43 1.43

15 15

0.060 0.060

0.35 0.35

63 63

63 63

1.22 1.22 1.43 1.43

15 15 15 15

0.027 0.027 0.060 0.060

0.17 0.17 0.35 0.35

30 30 63 63

30 30 63 63

Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes( see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA + 1 MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.

10-13

Ceiling & Floor Ceiling Suspended


8. Sound Levels Overall

1m

1m Microphone

Model

H

Sound Levels dB(A) M L

Model

H

Ceiling & Floor/Ceiling Suspended

Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Sound Levels dB(A) M L

ARNU09GVEA2

36

32

28

ARNU18GVJA2

42

40

37

ARNU12GVEA2

38

36

30

ARNU24GVJA2

43

41

39

Sound Pressure Level ARNU18GVJA2

ARNU12GVEA2 80

70

70

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45 40 NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-60

NC-50 NC-45 40 NC-40

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-15 125

NC-55

50

NC-20

10 63

NC-65 60

NC-65 60 NC-60

NC-15 125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-55

50

NC-50 NC-45 40 NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-20

10 63

Octave Band Sound Pressure Level (dB re 20µPa )

80

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU09GVEA2 80

NC-20 NC-15

10 63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

ARNU24GVJA2 80

Octave Band Sound Pressure Level (dB re 20µPa )

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

NC-20 NC-15 125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling & Floor Ceiling Suspended

10-14


Ceiling & Floor/Ceiling Suspended

9. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

9.1 Features 9.1.1 VE Chassis

Vertical louver

Horizontal louver Air outlet vent

Air filters (behind front panel) Air inlet vent

10-15

Ceiling & Floor Ceiling Suspended


9.1.2 VJ Chassis Ceiling & Floor/Ceiling Suspended

Air Discharge

Right Side Cover

Signal Receptor

Air Filter

Left Side Cover

Inlet Grill

Drain hose

Ceiling & Floor Ceiling Suspended

10-16


Ceiling & Floor/Ceiling Suspended

VE Chassis 9.2 Installation Map NOTICE

Installation parts you should purchase.

There should be no gap between the ceiling and the unit.

Ceiling Mounting

Sleeve Bushing-Sleeve Putty(Gum Type Sealer) More than 200mm (Left and right are identical)

More than 50mm

Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.

Wall Mounting

More than 200mm (Left and right are identical)

Vinyl tape (Wide) • To carry out the drainage test, remove the air filters and pour water into the heat exchanger. • Apply after carrying out a drainage test.

More than 50mm

Saddle

10-17

Ceiling & Floor Ceiling Suspended


9.3 Select the best Location More than 200mm

1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit.

More than 200mm

3. Make sure that condensation drainage can be conveniently routed away. More than 500mm

4. Do not install near a doorway. 5. Ensure that the interval between a wall and the left (or right) of the unit is more than 200mm. The unit should be installed as low as possible on the wall, allowing a minimum of 500mm from floor.

More than 200mm

6. Use a stud finder to locate studs to prevent unnecessary damage to the wall. More than 500mm

More than 200mm

9.4 Preparing Work for Installation Open panel front 1. Remove the five screws. 2. Release the claws in the 3 places indicated. 3. Pull up the Front Panel.

2 Claw

Cover pipe and cover side remove 1. Pull up the side cover of desired connecting direction, then cover side is separated. 2. Pick the pipe hole of the side cover.

1

3

CAUTION: After removing the pipe hole, cut the burr for safety. NOTICE

When making pipe path through rear wall, you don’t need to pick the pipe hole.

Drain hose junction 1. Remove the rubber stopple in the desired drain direction. 2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure as shown on the right.

Ceiling & Floor Ceiling Suspended

10-18

Ceiling & Floor/Ceiling Suspended

Indoor unit


Ceiling & Floor/Ceiling Suspended

9.5 Mounting the installation plate(Wall Mounting) The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with type "A" screws. While mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level.

2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.

Installation Plate

Type "A" screw

70

70 Installation plate

Ă˜70mm

120

Ă˜70mm

more than 2000 Left rear piping

Right rear piping Floor

10-19

Ceiling & Floor Ceiling Suspended


9.6 Mounting the anchor Nut & Bolt(Ceiling Mounting) • Measure and mark the position for the Suspension bolts and the piping hole. • Drill the hole for anchor nut on the ceiling.

Anchor nut Ceiling Nut

Washer

Suspension bolts

• Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.

40

235 820

Suspension bolt

50 100

• Mount the suspension bolts to the anchor-nuts firmly. • Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers.

Reference of piping hole (Ø45)

piping hole (Ø45)

• Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts. • Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be inclined to the bottomside so as to drain well.

: Tighten the nut and bolt to prevent unit falling.

Suspension bolts Spring washer Hangen Max. 12mm

Nut

Washer

Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)

Flat washer for M10 (accessory)

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Ceiling & Floor Ceiling Suspended

10-20

Ceiling & Floor/Ceiling Suspended

• Prepare 4 suspension bolts. (Each bolts length should be same.)


Ceiling & Floor/Ceiling Suspended

: Installation Information For right piping. Follow the instruction below.

Good case

Bad case

For left piping. Follow the instruction below.

1. Following bending type from right to left could cause problem of pipe damage.

1. Press on the upper side of clamp. ( ) 2. Unfold the tubing downward slowly. ( ) 3. Bend the tubing to the left side of chassis.

10-21

Ceiling & Floor Ceiling Suspended


9.7 Checking the Drainage Ceiling & Floor/Ceiling Suspended

1. Set the air direction louvers up-and-down to the position(horizontally) by hand.

To check the drainage. 1. Pour a glass of water on the evaporator using a kettle. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. ■ Checking the Drainage 1. Remove the Air Filter. • To remove air filter, take hold of tab and pull slightly upwards. 2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

Drain piping

Downward slope

1. The drain hose should point downward for easy drain flow. 2. Do not make drain piping like the following.

Accumulated drain water Air

Do not raise

Water leakage

Water leakage

Waving

Less than 50mm gap

Tip of drain hose dipped in water Water leakage

Ditch

9.8 Panel Front Assembly 1. Suspend the hook of panel front in the groove. 2. Press the panel front.

1

3. Screw up panel front. 3 2

Ceiling & Floor Ceiling Suspended

10-22


Ceiling & Floor/Ceiling Suspended

VJ Chassis 9.9 Select the best Location Indoor unit 1. Do not have any heat or steam near the unit.

More than 700mm

2. Select a place where there are no obstacles in front of the unit. 3. Make sure that condensation drainage can be conveniently routed away. 4. Do not install near a doorway. 5. Ensure that the interval between a wall and the left (or right) of the unit is more than 700mm. 6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.

More than 700mm

More than 300mm

: In case that the unit is installed near the sea, the installation parts may be cor-

roded by salt. The installation parts (and the unit) should be treated with appropriate anti-corrosion measures.

10-23

Ceiling & Floor Ceiling Suspended


9.10 Preparing Work for Installation

2. Unlock side-cover from side panel by slightly pulling the edge of side cover. 3. Tap the side-cover with your palm on the backside.(Inlet grill side.) 4. Hold the side-cover with other hand while tapping to prevent it to fall down.

2 Edge part

1

5. Remove the rubber stopple in the desired drain direction. 6. Knock out the pipe hole from the left side-cover with the help or nipper/plier. 7. Knock hole on right side-cover only if right side is selected for water drain.

Ceiling & Floor Ceiling Suspended

10-24

Ceiling & Floor/Ceiling Suspended

Open side cover 1. Remove two screws from side-cover as shown in fig.


• Prepare 4 suspension bolts. (Each bolts length should be same.)

(Unit: mm) DIM. MODEL VJ

• Measure and mark the position for the Suspension bolts and the piping hole.

A

B

855

320

• Drill the hole for anchor nut on the ceiling. • Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the anchor-nuts firmly.

Anchor nut

B

A

Ceiling

Suspension bolt Nut

Washer

Suspension bolts

• Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers. • Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts. Suspension bolts

• Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be inclined to the bottomside so as to drain well.

Spring washer Hangen

Nut

Max. 12mm

: Tighten the nut and bolt to prevent unit falling.

Washer

Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)

Flat washer for M10 (accessory)

Spring washer (M10) Flat washer for M10 (accessory) Nut (W3/8 or M10)

DRILL A HOLE IN THE WALL.

WALL Indoor

Outdoor

10-25

(3/16"~5/16")

• Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.

5-7mm

Ceiling & Floor/Ceiling Suspended

MOUNTING THE ANCHOR NUT AND BOLT

Ceiling & Floor Ceiling Suspended


9.11 Indoor unit installation

: Installation Information For Declination

1. Inclination of the indoor unit is very important for drain purposes in the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 10mm. 3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.

Front of view • The unit must be horizontal or inclined at angle. • The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain direction as shown in fig. Ceiling 10~20mm

Side of view • The unit must be inclined to the bottomside of the unit when finished installation. Ceiling 5~10mm

Ceiling & Floor Ceiling Suspended

10-26

Ceiling & Floor/Ceiling Suspended

Hang the Indoor unit on suspension bolt as per following guidelines: 1. Lift the indoor unit to sufficient height. 2. Insert the suspended part of four suspension bolt in the four hangers provided on the side of main body one by one. 3. Lower the indoor unit till the hangers rest on their respective flat washer. 4. Adjust the level in the top down direction by adjusting the suspension bolts. Inclined the indoor unit as per direction provided in the fig


Ceiling & Floor/Ceiling Suspended

9.12 Checking the Drainage 1. Set the air direction louvers up-and-down to the position(horizontally) by hand.

To check the drainage. 1. Pour a glass of water on the evaporator using a kettle. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Drain piping Downward slope

1. The drain hose should point downward for easy drain flow.

2. Do not make drain piping like the following. Accumulated drain water Air

Do not raise

Water leakage

10-27

Water leakage

Waving

Tip of drain hose dipped in water Water leakage

Less than 50mm gap

Ditch

Ceiling & Floor Ceiling Suspended


9.13 Wiring Connection

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING : Make sure that the screws of the terminal are free from looseness.

Ceiling & Floor Ceiling Suspended

10-28

Ceiling & Floor/Ceiling Suspended

Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.


Ceiling & Floor/Ceiling Suspended

CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have a separate power circuit specially for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.

10-29

Ceiling & Floor Ceiling Suspended


WIRED REMOTE CONTROLLER INSTALLATION

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling & Floor Ceiling Suspended

10-30

Ceiling & Floor/Ceiling Suspended

• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.


10. Accessories

Ceiling & Floor/Ceiling Suspended

Standard Accessories Name

Installation plate

Type "A" screw and plastic anchor

Quantity

1EA

4EA

(Other)

• Owner's manual • Installation manual Shape

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

10-31

Ceiling & Floor Ceiling Suspended


11

1. List of Functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories

Floor Standing

Floor Standing

Floor Standing


1. List of Functions

Floor Standing

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GCEA2, ARNU09GCEA2, ARNU12GCEA2 ARNU15GCEA2, ARNU18GCFA2, ARNU24GCFA2 ARNU07GCEU2, ARNU09GCEU2, ARNU12GCEU2 ARNU15GCEU2, ARNU18GCFU2, ARNU24GCFU2 1 3/3/3 X X O X O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O X O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

11-1

Floor Standing


2. Specification Type Model Cooling Capacity

Heating Capacity Casing Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch m2 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU07GCEA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 1,067x203x635 42.2x8.0x25.0 2x12x19 0.16 Sirocco Fan 28 0.15 8.5/7.5/6.5 300/265/229 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12 27(59.5) 35/33/31 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Floor Standing ARNU09GCEA2 2.8 2,400 9,600 3.2 2,800 10,900 Galvanized Steel Plate 1,067x203x635 42.2x8.0x25.0 2x12x19 0.16 Sirocco Fan 28 0.15 9.5/8.5/7.5 335/300/265 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12 27(59.5) 36/34/32 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Floor Standing

ARNU12GCEA2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 1,067x203x635 42.2x8.0x25.0 2x12x19 0.16 Sirocco Fan 28 0.15 10.5/9.5/8.5 371/335/300 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12 27(59.5) 37/35/33 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

11-2

Floor Standing

Unit kW kcal/h Btu/h kW kcal/h Btu/h


Floor Standing

Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

mm inch m2 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm Net Weight kg(lbs) Noise Level(Sound Press, 1m, H/M/L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU07GCEU2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 978x190x639 38.5x7.5x25.2 2x12x19 0.16 Sirocco Fan 28 0.15 8.5/7.5/6.5 300/265/229 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12 20(44.1) 35/33/31 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Floor Standing ARNU09GCEU2 2.8 2,400 9,600 3.2 2,800 10,900 Galvanized Steel Plate 978x190x639 38.5x7.5x25.2 2x12x19 0.16 Sirocco Fan 28 0.15 9.5/8.5/7.5 335/300/265 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12 20(44.1) 36/34/32 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

11-3

ARNU12GCEU2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 978x190x639 38.5x7.5x25.2 2x12x19 0.16 Sirocco Fan 28 0.15 10.5/9.5/8.5 371/335/300 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12 20(44.1) 37/35/33 1, 220 ~ 240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.25 x 2C Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Floor Standing


Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

Floor Standing

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

11-4

Floor Standing

Floor Standing ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2 4.5 5.6 7.1 3,900 4,800 6,100 Cooling Capacity 15,400 19,100 24,200 5.0 6.3 8.0 4,300 5,400 6,900 Heating Capacity 17,100 21,500 27,300 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Casing 1,067x203x635 1,345x203x635 1,345x203x635 mm Dimensions(WxDxH) Body 42.2x8.0x25.0 52.9x8.0x25.0 52.9x8.0x25.0 inch 2x12x19 3x11x19 3x11x19 Rows x Columns x FPI Coil 0.16 0.23 0.23 Face Area m2 Sirocco Fan Sirocco Fan Sirocco Fan Type 28 76 76 Motor Output x Number W 0.15 0.38 0.38 Running Current A 11.5/10/9.5 16/14/12 18/16/14 Fan Air Flow Rate(H/M/L) CMM 406/353/335 565/494/424 635/565/494 cfm Direct Direct Direct Drive BLDC BLDC BLDC Motor type Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat Temperature Control for cooling and heating for cooling and heating for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Resin Net(washable) Resin Net(washable) Resin Net(washable) Air Filter Fuse Fuse Fuse Safety Device Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Liquid Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Pipe Connections Gas Side mm(inch) 12 12 12 Drain Pipe(Internal Dia.) mm 27(59.5) 34(75.0) 34(75.0) Net Weight kg(lbs) 38/37/35 40/37/34 43/40/37 Noise Level(Sound Press, 1m, H/M/L) dB(A) 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV Refrigerant Control CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Power cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Transmission cable mm2 Type Model


Floor Standing ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2 4.5 5.6 7.1 3,900 4,800 6,100 Cooling Capacity 15,400 19,100 24,200 5.0 6.3 8.0 4,300 5,400 6,900 Heating Capacity 17,100 21,500 27,300 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Casing 978x190x639 1,256x190x639 1,256x190x639 mm Dimensions(WxDxH) Body 38.5x7.5x25.2 49.5x7.5x25.2 49.5x7.5x25.2 inch 2x12x19 3x11x19 3x11x19 Rows x Columns x FPI Coil 0.16 0.23 0.23 Face Area m2 Sirocco Fan Sirocco Fan Sirocco Fan Type 28 76 76 Motor Output x Number W 0.15 0.38 0.38 Running Current A 11.5/10/9.5 16/14/12 18/16/14 Fan Air Flow Rate(H/M/L) CMM 406/353/335 565/494/424 635/565/494 cfm Direct Direct Direct Drive BLDC BLDC BLDC Motor type Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat Temperature Control for cooling and heating for cooling and heating for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Sound Absorbing Thermal Insulation Material Resin Net(washable) Resin Net(washable) Resin Net(washable) Air Filter Fuse Fuse Fuse Safety Device Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Liquid Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Pipe Connections Gas Side mm(inch) 12 12 12 Drain Pipe(Internal Dia.) mm 20(44.1) 27(59.5) 27(59.5) Net Weight kg(lbs) 38/37/35 40/37/34 43/40/37 Noise Level(Sound Press, 1m, H/M/L) dB(A) 1, 220 ~ 240, 50 1, 220 ~ 240, 50 1, 220 ~ 240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV Refrigerant Control CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Power cable mm2 CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C Transmission cable mm2

Floor Standing

Type Model

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve

11-5

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Floor Standing


148.3

<Without Case>

978 794

<With Case> 2

1067

13

148.3

1

635 70 20.4 62.8

Floor Standing

11-6

190 161

203

14

Air discharge grill Air suction grill

1 2

639

635

H

Descripition

(unit : mm)

190

203

D

(unit : mm)

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: CE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

978

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2

Number

1067

W

ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2

Model

ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2

Floor Standing

Floor Standing

1067

3. Dimensions

49

639


148.3

70

21.4

639

<Without Case>

1256 1098 1072

<With Case>

1048.4

1345

2

203 635 109.8 30

148.3

70 81.4 145

11-7

Floor Standing

49.4

1

190 161

203

14

Air discharge grill Air suction grill

1 2

639

635

H

Descripition

(unit : mm)

190

203

D

(unit : mm)

ARNU18GCFU2 ARNU24GCFU2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: CF

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

Number

1256

1345

ARNU18GCFA2 ARNU24GCFA2 ARNU18GCFU2 ARNU24GCFU2

W

Model

ARNU18GCFA2 ARNU24GCFA2

Floor Standing

Floor Standing


4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 Sirroco Fan

Floor Standing

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [unit: mm(inch)]

Model ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2

Floor Standing

Gas

Liquid

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

11-8


5. Wiring Diagrams

Floor Standing

CE/CF Chassis

CONNECTOR NUMBER

CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COMM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-OPTION CN-ZONE CN-DISPLAY CN-CC

LOCATION POINT

FUNCTION

AC power supply Fan motor output Fan motor output Drain pump output Communication EEV output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Option PCB Zone controller RF Remote controller Dry contact

AC Power line input for indoor controller Motor output of bldc Motor output of bldC AC Output for drain pump Communication between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Communication between main and option Zone control line RF Remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

11-9

Floor Standing


6. Capacity Tables 6.1 Cooling Capacity Capacity Index

2.8

3.6

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.5

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.5

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.8 2.6

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.2 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 1.5

2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.0 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.6

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.2 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.2

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.4

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.3

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.3

4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.6 3.3

2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1 2.0

4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.7 3.3

2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.0

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

Floor Standing

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

11-10

Floor Standing

2.2

Cooling capacity


Floor Standing

Cooling capacity

Capacity Index

4.5

5.6

7.1

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 4.9

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.1 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.7

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.0 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.0

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.6

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.1 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.1

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 2.9 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.5

5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.7 4.5 4.5 4.1 6.7 6.7 6.7 6.7 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.6 5.1

3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8 2.7 2.7 2.5 3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.2 3.0

5.8 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.2 7.2 7.1 7.1 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.2

3.5 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.5 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.0

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.7

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.8 6.7 6.3

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.8 4.8 4.5

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0 6.9 6.5

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.4

8.5 8.5 8.5 8.5 8.4 8.3 8.3 8.2 8.1 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.2 7.1 6.5

4.9 4.9 4.9 4.9 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.2 4.1 4.1 3.8

9.1 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 7.2 6.6

5.2 5.2 5.1 5.1 5.0 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.5 4.5 4.4 4.3 4.2 4.2 3.8

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

11-11

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Floor Standing


6.2 Heating Capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

Heating capacity Indoor air temp. (DB, 째C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW) Capacity

Floor Standing

11-12

Floor Standing

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


Floor Standing

Heating capacity Outdoor air temp. Capacity Index DB(째C) WB(째C)

4.5

5.6

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, 째C) 16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2 5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3 5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

11-13

Floor Standing


7. Air velocity and Temperature Distribution(Reference Data) ARNU24GCFA2- Installation on floor or wall Cooling

Heating

Discharge angle:45°

Discharge angle:60°

Air velocity [m/s]

Air velocity [m/s] • 2.7m

• 2.7m 0.5 0.75

0.75

• 2m

• 2m

1.0

1.0

• 1m

• 1m

• 8m

• 7m

• 6m

• 5m

• 4m

• 3m

• 2m

•• 0m 0m

• 1m

• 8m

• 7m

• 6m

• 5m

• 4m

• 3m

• 2m

•• 0m 0m

• 1m

Temperature [°C]

Temperature [°C]

• 2.7m

• 2.7m 24

29 30

• 2m 25 23

• 8m

• 7m

• 6m

Floor Standing

• 5m

• 4m

• 3m

• 2m

• 1m

• 2m

28 • 1m

•• 0m 0m

31

• 8m

• 7m

• 6m

• 5m

• 4m

• 3m

• 2m

• 1m

• 1m

•• 0m 0m

11-14

Floor Standing

1.25

1.25


8. Electric Characteristics Units Floor Standing

Model ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2 ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2

Type

Power Supply Hz

Volts Voltage Range MCA

CE CE CE

MAX.264 50

220~240

60

220

MIN.198

CE CF CF CE CE CE

MAX.242 MIN.198

CE CF CF

1.22 1.22 1.22 1.22 1.22 1.22 1.22 1.22 1.55 1.55 1.55 1.55 1.22 1.22 1.22 1.22 1.22 1.22 1.22 1.22 1.55 1.55 1.55 1.55

IFM

Input(W)

MFA

kW

FLA

15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.076 0.076 0.076 0.076 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.076 0.076 0.076 0.076

0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.44 0.44 0.44 0.44 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.44 0.44 0.44 0.44

Cooling Heating 30 30 30 30 30 30 30 30 80 80 80 80 30 30 30 30 30 30 30 30 80 80 80 80

30 30 30 30 30 30 30 30 80 80 80 80 30 30 30 30 30 30 30 30 80 80 80 80

Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes( see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.

11-15

Floor Standing


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Microphone

With Case

1.5m

E

Du

1.5m

ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2

Floor Standing

Model

(Fie

Sound Levels dB(A) H L M 35 33 31 36 34 32 37 35 33 38 37 35 40 37 34 43 40 37

Sound Pressure Level ARNU07GCEA2 ARNU07GCEU2

ARNU09GCEA2 ARNU09GCEU2 70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

250

500

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

NC-15 1000 2000 4000 8000

10

63

NC-60

250

500

NC-50

NC-40

NC-30

NC-15 1000 2000 4000 8000

10

NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30

10

NC-25

63

NC-60

125

250

500

Octave Band Center Frequency (Hz)

Floor Standing

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 1000 2000 4000 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

70

Approximate Hearing Threshold

125

250

500

1000

2000

4000

500

1000 2000

NC-15 4000 8000

NC-15 8000

Octave Band Center Frequency (Hz)

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

250

ARNU24GCFA2 ARNU24GCFU2

ARNU18GCFA2 ARNU18GCFU2

70

20

NC-20

Octave Band Center Frequency (Hz)

80

30

NC-25 Approximate Hearing Threshold 63

80

40

NC-35

30

80

50

NC-45

40

Octave Band Center Frequency (Hz)

ARNU15GCEA2 ARNU15GCEU2

60

NC-55

50

NC-20

125

NC-65

60

20

NC-25 Approximate Hearing Threshold

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20µPa )

80

Octave Band Sound Pressure Level (dB re 20µPa )

70

Octave Band Sound Pressure Level (dB re 20µPa )

80

Octave Band Sound Pressure Level (dB re 20µPa )

80

ARNU12GCEA2 ARNU12GCEU2

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

1000

2000

4000

NC-15 8000

Octave Band Center Frequency (Hz)

11-16


Floor Standing

10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

10.1 Features

[CEA/CFA Type]

Control panel

Air Outlet Remote Controller Control panel TEMP

Remote Controller

Air Filter Air Inlet

[CEU/CFU Type]

Air Inlet Air filter (At Air Inlet)

11-17

Floor Standing


10.2 Selection of the best location Indoor unit Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight. Floor Standing

• Sufficient space should be available to inspect the unit as in the figure shown on the right.

Window

• The place where the unit is installed shall be leveled. • The place shall be suitable for easy connection of the indoor unit with the outdoor unit. • The place where the unit is installed should not be affected by electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit Select an installation site where the following conditions are satisfied and that meets your customer's approval. • Where the floor is strong enough to bear the indoor unit weight. • Where the floor is not significantly inclined. • Where nothing blocks the air passage. • Where condensate can be properly drained.

20 or more

Service space

Air flow direction Front side

100 or more

175 or more

100 or more

1000 or more

Air inlet direction

• Where sufficient clearance for installation and maintenance can be ensured.

Base

• Where there is no possibility of flammable gas leakage. • Where optimum air distribution can be ensured. • Where piping between indoor and outdoor units is possible within the allowable limit (Refer to the installation manual of the outdoor unit.) 80 or more

654

• Keep the indoor and outdoor unit, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static.(Depending on the type and source of the electrical waves, static may be heard even when more than 1 m away.)

Window

Ma

(Unit: mm) Type

A

B

CEU Type

788

1080

CFU Type

1066

1358

Floor Standing

inte

nan

ce

are

a

Ao

[IMPORTANT] Leave sufficient clearance for air inlet and maintenance.

rm ore Bo rm ore

11-18


A

• Positioning of holes for fastening to the wall

Type

A

CEA, CEU CFA, CFU

858 1136

1. Use the installationmount for installation. Check whether the wall is strong enough to bear the weight of the unit or not. if there is a risk, reinforce the wall before installing the unit. 2. The unit requires a minimum 100 mm clearance below the unit for air intake. Also, ensure the unit is leveled when installed so that drainage flows smoothly. If inclined, water can leak. 3. Depending upon the shape and nature of the wall surface, operating sound may become bigger.

198

(Unit:mm)

270

Floor Standing

Bolt pitch

How to open/close front panel

(1)

• How to open/close the front panel (2)

(1) Open the lid of control panel(Both left and right) (2) Remove screws(Both left and right) (3) Lift the front panel of the unit • To close, perform the procedure in opposite order.

11-19

(2) (3)

(1)

Floor Standing


10.3 Drain piping work • Drain piping must have downward slope(1/50 to 1/100): be sure not to provide up-and-down slope to prevent reverse flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection to the indoor unit is 21mm. Floor Standing

Piping material: Polyvinyl chloride pipe 25mm and pipe fittings • Be sure to install heat insulation on the drain piping Heat insulation material: Polyethylene foam with thickness more than 10 mm. • If converging multiple drain pipes, install according to the procedure shown below.

Slope downwards at a gradient of at least 1/100 • After piping work is finished, check for drainage. • Be sure to insulate all indoor units.

10.4 How to connect wirings Remove the electric parts Box cover and connect the wiring

Fasten with clamp

Fasten with accessory clamp

Floor Standing

Power Supply wiring ground wiring (Field wiring)

Power supply wiring ground wiring Transmission wiring (Field wiring)

Transmission wiring

11-20


Floor Standing

10.5 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING : Make sure that the screws of the terminal are free from looseness. CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have a separate power circuit specifically for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.) 7) In a wet or moist area, always install an earth leakage circuit breaker. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

11-21

Floor Standing


WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: Floor Standing

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Floor Standing

11-22


11. Accessories

Floor Standing

Standard Accessories Name

Dran hose

Level adjustment screw

Insulation for fitting

Clamp (Tie Wrap)

Quantity

1 EA

4

1 each.

8 pcs.

(1) For gas pipe Shape

[Other]

• Operation manual • Installation manual

(2) For liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

11-23

Floor Standing


P/No.: MFL42059206

Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com

All rights reserved Printed in Korea April/2009 The specifications, designs, and information in this brochure are subject to change without notice.

File No. : A8974 Volume:1

Certificate No. : E00626/1

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.