ADPF Dedicated Downflow Three-Speed Air Handler 1½ to 5 Tons Standard Features
• Suitable for use with refrigerants R-410A & R-22 • Check flowrater expansion device • Direct-drive, multi-speed motor • Transformer and blower time-delay on all units • Dedicated downflow requires no modification in the field • AHRI Certified • ETL Listed
Cabinet Features
• Fully insulated, painted steel cabinet with attractive Architectural Gray finish • Built-in coil has downflow drain pan with secondary drain connections • Power supply entry at top • Low-voltage entry on left side and top
Accessories
• 3 kW to 21 kW electric heat kits available as field-installed options
Contents
Nomenclature........................................................................2 Product Specifications...........................................................3 Dimensions............................................................................4 Airflow Data...........................................................................5 Wiring Diagrams...............................................................................6 Accessories........................................................................................7
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.
SS-GADPF
www.goodmanmfg.com
5/10A
Supersedes 5/10
Product Specifications
Nomenclature A 1
D 2
P 3
F 4
3642 5,6,7,8
1 9
6 10
Brand A Single-piece Air Handler
Engineering * Major/ Minor Revisions * Not used for inventory management
Unit Application C Ceiling Mount PSC Motor D Downflow PSC Motor E Multi-Position Variable-Speed Motor R Multi-Position PSC Motor S Multi-Position EEM Motor W Wall Mount PSC Motor Cabinet Finish U Unpainted P Painted N Uncased Expansion Device F Flowrater T Expansion Valve
2
AA 11,12
Refrigerant Charge No Digit = R-22 only 6 = R-410A or R-22 Electrical 1 208/240 V, 1 Phase, 60 Hz Nominal Capacity Range @ 13 SEER Multi-Position & Downflow Applications 3642 3-3½ Tons 1830 1½-3½ Tons 1729 1½ to 2½ Tons (for Export Systems) Ceiling Mount & Wall Mount Applications (Nominal Cooling Capacity/ Electric Heat kW) 1805 1½ Tons Cooling/ 5 kW Electric Heat 2405 2 Tons Cooling/ 5 kW Electric Heat 3608 3 Tons Cooling/ 8 kW Electric Heat
www.goodmanmfg.com
SS-GADPF
Product Specifications
Specifications ADPF 182416
ADPF 304216
ADPF 486016
Nominal Ratings Cooling (BTU/h)
18,000-24,000
30,000-42,000
48,000-60,000
1,025/ 790/ 570
1,645/ 1,440/ 1,275
1,985/ 1,875/ 1,650
9½”
10⅝”
10⅝”
Width
6”
8”
10⅝”
Coil Drain Connection FPT
¾”
¾”
¾”
Liquid
⅜”
⅜”
⅜”
Suction
¾”
⅞”
⅞”
Voltage
208/240
208/240
208/240
Min Circuit Ampacity
2.1/2.1
3.7/3.7
5.4/5.4
CFM (High/ Med/ Low) Blower Diameter
Service Valve
Electrical Data
Max. Overcurrent Device (amps) Min./Max. VAC
15/15
15/15
15/15
197/253
197/253
197/253
Blower Motor FLA
1.7
2.95
4.3
HP
⅓
½
¾
Ship Weight (lbs)
96
131
151
* Maximum Overcurrent Protection Device
SS-GADPF
www.goodmanmfg.com
3
Product Specifications
Dimensions 13/16”
13/16”
2 ⅞”
13/16”
3¼”
Model
4
A
B
C
D
E
F
G
H
I
L
M
ADPF182416
42⅛”
22”
13½”
15½”
10”
3½”
6¹/₁₆”
13⅛”
17¹⁵/₁₆”
15½”
15⁵/₁₆”
ADPF304216
53¼”
24”
20”
22”
12”
9¼”
11¹³/₁₆”
19⅝”
19¹⁵/₁₆” 21⁷/₁₆”
21¼”
ADPF486016
53¼”
24”
20”
22”
12”
9¼”
11¹³/₁₆”
19⅝”
19¹⁵/₁₆” 21⁷/₁₆”
21¼”
www.goodmanmfg.com
SS-GADPF
Product Specifications
Airflow Data Model
Speed High
ADPF182416
ADPF304216
ADPF486016
CFM delivered against External Static Pressure 0.1”
0.2”
0.3”
0.4”
0.5”
1,155
1,090
1,025
950
895
Med
940
890
860
815
755
Low
695
665
650
610
550
High
1,700
1,660
1,625
1,545
1,505
Med
1,500
1,440
1,400
1,350
1,345
Low
1,370
1,300
1,250
1,230
1,220
High
2,150
2,120
2,070
2,000
1,940
Med
1,940
1,930
1,905
1,860
1,790
Low
1,610
1,600
1,590
1,575
1,550
Note: Assumes dry coil with filter in place; SCFM correction for wet coil = 4% (208V / 240V
SS-GADPF
www.goodmanmfg.com
5
Product Specifications 6 ADPF Wiring Diagram
7
5
4
3
BK
PU BL
R
3
WH
R
BK
BK
8
RD
BL
5
M4
PU
3
RD BL
R2
RD
6
1
BL
M3
M2
2
M4
M5
M7
M6
M8
R1
WH
6
RD
3
RD BL
R2
BK
4
BR
BK RD
WH
5
6
7
7
BK RD
7
YL
8
9
RD
8
YL
BK 9
RD
9
L1
BK
PU
BK RD M1
YL
RD
5
BR
BK
BK
BL
4
M2
R1
PLM
BL
2
M1
M4
YL
HTR4 TL
1
YL
M3
M2
RD
HTR3 TL
FL
PLM
RD
M1
4
WH
7
RD
3
M3
M2
6
BK
YL
BL M1
RD
BK
2
PU
BK RD
5
A
BK
HTR2 TL
FL
HTR3 TL
1
RD
4
M1 M2
BK
BK
BK
HTR2 TL
FL
PLM
BK
2
RD BK
RD
1
HTR1 TL
FL
HTR1 TL
FL HTR1 TL
PLM BK
FL
HTR2 TL
FL
HTR1 TL
REV
FL
FL
FL
ECN 1004553
BL BK
8
9
L2 L1
ONE (1) ELEMENT ROWS
L2
L1
TWO (2) ELEMENT ROWS
L2
L1
L2
THREE (3) ELEMENT ROWS
L1
L2
L1
L2
FOUR (4) ELEMENT ROWS
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE. MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED. TERMINAL BLOCK SHOWN FOR 50HZ MODELS ONLY BL RD GR WH
L2
L1
BR
BK
SR
EQUIPMENT GROUND USE COPPER OR ALUMINUM WIRE
208/240 VOLTS
GRD
RD
L1
PLM
1
2
3
4
5
6
7
8
9
PLF
1
2
3
4
5
6
7
8
9
BK
RD
PU
BL
BR
WH
L2
1
PLM
1
PLF
PLM 2
HI
BR
LO
WH
2
EM
RC
SEE NOTE 4
SEE NOTE 2
PLF
3
1
2
3
4
24V
5
M1
NC
NO EBTDR
M2
COM
SEE NOTE 1
TR
EBTDR R GR RD G
BL
COM
K1
C
BL
SPEEDUP
RD
NO
K1
C
2
RD
240
3
TR 24V
5
NC M1
6
SEE NOTE 1 1
RD
PU
4
BK RD YL BL
BL
BL
M2
RD
PU RD (M1) RD
IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, USE WIRE THAT CONFORMS TO THE NATIONAL ELECTRIC CODE.
BK
LOW
(M2) BL
MEDIUM
(COM) BK (TR 1)
RC
HIGH PU
PU
BR
BR EM 3 SPEED
GR GREEN BLACK PU PURPLE RED YELLOW BR BROWN WH WHITE BLUE
COMPONENT CODE
SEE NOTE 3
THREE SPEED MOTOR WIRING (SELECT MODELS ONLY) SEE NOTE 3
5
BR
EM
RC
EM RC SR R EBTDR
EBTDR
G
4 PLF
BL
WH BR COLOR CODE
BK
COPPER OR ALUMINUM POWER SUPPLY (SEE RATING PLATE) USE MIN. 75°C FIELD WIRE
C
RD
PU
EBTDR
R XFMR-R XFMR-C
RD
BK
SEE NOTE 5
GR
WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE NOTE 2
EVAPORATOR MOTOR TR RUN CAPACITOR PLF STRAIN RELIEF PLM FL RELAY TL ELECTRONIC BLOWER TIME DELAY RELAY HTR
TRANSFORMER FEMALE PLUG CONNECTOR MALE PLUG CONNECTOR FUSE LINK THERMAL LIMIT HEAT ELEMENTS
Notes: 1) Red wires to be on transformer terminal "3" for 240 volts and on terminal "2" for 208 volts. 2) See composite wiring diagrams in installation instructions for proper low voltage wiring connections. 3) Confirm speed tap selected is appropriate for application. If speed tap needs to be changed, connect appropriate motor wire (Red for low, Blue for medium, and Black for high speed) on "COM" connection of the EBTDR. Inactive motor wires should be connected to "M1 or M2" on EBTDR. 4) Brown and white wires are used with Heat Kits only. 5) EBTDR has a 7 second ondelay when "G" is energized and a 65 second off delay when "G" is de-energized.
0140M00170 REV A
RESSURE SENSITIVE S4900061, TYPE A. ROUND.
THE Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
L CHARACTERISTIC
7
SC
= SIGNIFICANT CHARACTERISTIC 6
6
⚠
W
⚡
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power arning sources may be present. Failure to do so may cause property damage, personal injury, or death. COMPONENTS AND MATERIALS SPECIFIED HEREIN WILL ALSO CONFORM TO THE APPLICABLE SECTION OF GOODMAN MSP 824.01 WORKMANSHIP STANDARD FOR FIT, FEEL AND FINISH. CONFIDENTIAL PROPERTY OF THE GOODMAN MANUFACTURING COMPANY, L.P. NOT TO BE DISCLOSED TO OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAND, ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT.
5
www.goodmanmfg.com
4
3
SS-GADPF
DRAWIN ACCORD
DIME UNLE T A
HO TUBE
Product Specifications
Accessories Expansion Valve Kits for Air Conditioning and Heat Pump Applications For R-22 Systems
For R-410A Systems
Valve
Description
Used with Outdoor Units below
Valve
Description
Used with Outdoor Units below
TX3N2
Non-bleed valve
3 Ton > Air Conditioner & Heat Pump
TX3N4
Non-bleed valve
3 Ton > Air Conditioner & Heat Pump
TX5N2
Non-bleed valve
3½ Ton < Air Conditioner & Heat Pump
TX5N4
Non-bleed valve
3½ Ton < Air Conditioner & Heat Pump
Heat Kit Selection
Single Point Kit ** ADPF 182416
ADPF 304216
ADPF 486016
HKR-03*
X
X
X
HKR-05*, HKR-05C*
X
X
X
HKR-06*
X
X
X
HKR-08*, HKR-08C*
X¹
X
X
HKR-10*, HKR-10C*
X¹
X
X
HKR-15C*
X²
X³
X
HKR-20C*
X³
X
HKR-21C*
X³
X
^ HKR3-15*
X³
X
^ HKR3-20*
X³
X
Model SPW-01
HKR-15C
HKR-20C
HKR-21C
X
X
X
** Must be installed along with any of the above compatible heat kits. This kit will fit any ADPF air handler as long as a compatible heat kit is installed in the unit.
Notes: * Revision level that may or may not be designated C Circuit breaker option ^ Heat kit requires three-phase power supply ¹ Air handler must either be on medium or high speed ² Air handler must be on high speed ³ For static pressure of 0.6 or higher, air handler must be on medium or high speed
Filters ADPF
Filter #
Qty Required
1824
FIL 18-32
1
3042
FIL 48-61
1
4860
FIL 48-61
1
SS-GADPF
www.goodmanmfg.com
7
Product Specifications
Notes
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2010 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
8
www.goodmanmfg.com
SS-GADPF