1. Models Line up .......................................................................................4 2. Nomenclature..........................................................................................5 3. Features & Benefits................................................................................7 4. Specifications ........................................................................................15 5. Dimensional Drawings ..........................................................................18 6. Wiring Diagrams ................................................................................... 22 7. Refrigerant Cycle Diagram................................................................... 28 8. Capacity Tables.................................................................................... .30 9. Capacity coefficient factor....................................................................35 10. Operation Range..................................................................................39 11. Controller..............................................................................................41 12. Installation guide at the seaside ........................................................45

2008 Product Data

1


Test condition of international standard

CLASSIFICATION

Indoor Cooling Capacity

Outdoor

Indoor Heating Capacity

Maximum

Outdoor

Indoor

Cooling Operating

Outdoor

Maximum

Indoor

Heating Operating Enclosure

Outdoor

Indoor

Sweat / Condensate

Outdoor

Disposal Freeze-up/

Indoor

Low Temperature Outdoor

KSC 9306

ISO 5151

ARI 210/240

AHAM

AS 1861.1

SSA 385

DB°C(°F)

27.0

27.0

26.7(80)

26.7(80)

27.0

29.0

WB°C(°F)

19.5

19.0

19.4(67)

19.4(67)

19.0

19.0

DB°C(°F)

35.0

35.0

35.0(95)

35.0(95)

35.0

46.0

WB°C(°F)

24.0

24.0

23.9(75)

23.9(75)

24.0

24.0

DB°C(°F)

20.0

20.0

21.1(70)

21.1(70)

21.0

21.0

WB°C(°F)

15.0

15.0

15.6(60)

15.6(60)

15.0

15.5

DB°C(°F)

7.0

7.0

8.3(47)

8.3(47)

7.0

7.0

WB°C(°F)

6.0

6.0

6.1(43)

6.1(43)

6.0

6.0

DB°C(°F)

32.0

32.0

26.7(80)

32.2(90)

32.0

29.0

WB°C(°F)

23.0

23.0

19.4(67)

22.8(73)

23.0

19.0

DB°C(°F)

43.0

43.0

46.1(115)

43.3(110)

43.0

54.0

WB°C(°F)

26.0

26.0

23.9(75)

25.6(78)

26.0

24.0

DB°C(°F)

27.0

27.0

26.7(80)

26.7(80)

-

-

WB°C(°F)

19.0

19.0

19.4(67)

22.8(73)

-

-

DB°C(°F)

21.0

24.0

23.9(75)

23.9(75)

-

-

WB°C(°F)

15.0

18.0

18.3(65)

18.3(65)

-

-

DB°C(°F)

27.0

27.0

26.7(80)

26.7(80)

27.0

27.0

WB°C(°F)

24.0

24.0

23.9(75)

23.9(75)

24.0

24.0

DB°C(°F)

27.0

27.0

26.7(80)

26.7(80)

27.0

27.0

WB°C(°F)

24.0

24.0

23.9(75)

23.9(75)

24.0

24.0

DB°C(°F)

21.0

21.0

19.4(67)

21.1(70)

21.0

21.0

WB°C(°F)

15.0

15.0

13.9(57)

15.6(60)

16.0

16.0

DB°C(°F)

21.0

21.0

19.4(67)

21.1(70)

21.0

21.0

WB°C(°F)

15.0

15.0

13.9(57)

15.6(60)

16.0

16.0

KS : Korea Standard ISO : International Standard Organization ARI : Airconditioning and Refrigeration Institute AHAM : Association of Home Appliance Manufacturers

2

2008 Product Data

AS : Australia Standard SSA : Saudi Arabian Standard


General Description

Split type of Air Conditioners are known by the category name of Wall Mounted Type of units.These units can be easily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,it ensures a pleasant air conditioned environment. LG Offers various types of units to its customers to suit for the best application and requirement.The following are the important categories offered by LG : 1) General Wall Mounted Type Units : Units with Simplicity in design. 2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning. 3) New Gas Models : These models uses HCFC free refrigerant to provide a healthy environment to the world. Some of the Important Features of these units are listed below : 1) Providing Health to the Customers : By having Filters such as Plasma Filter which is capable of removing Micro Organisms up to 0.1 microns. 2) Long Term Money Saving : By providing Features such as Gold Fin,Plasma Fin, Auto Clean etc. to maintain the same performance for years. 3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc. These Units are available with many standard and optional features which gives our Customers the choice to select the unit of their own desire.For details refer to the Detailed specification followed after this description.

LG Electronics Inc. Air Conditioning Division

2008 Product Data

3


1. Models Line up General Wall Mounted Capacity

4

Chassis

9k

S4

12k

S4

18k

S5

26k

S5

2008 Product Data

Type C/O H/P C/O H/P C/O C/O H/P C/O H/P

Refrigerant R22 R22 R22 R22 R22 R22 R22 R22 R22

Model HS-C0964DA6 HS-H0964D71 HS-C1264DA3 HS-H1264D71 HS-C1865DB5 HS-C1865DB6 HS-H1865D70 HS-C2665DB1 HS-H2665D70


2. Nomenclature • Identification Rule 1:

Code

L

S

1

2

-

T

1

8

6

A

B

L

3

4

5

6

7

8

9

Type

Code of Model

Meaning

1, 2

Type of Airconditioner

A~Z

LS: LG Split Type Airconditioner

3

Chassis

A~Z

Name of tool of Unit Ex. LS-N ➔ SN Chassis

4, 5

Capacity

0~9

Cooling/Heating Capacity Ex. "09" ➔ 9,000Btu/h

6

Electric Range

1~9

Electric Standard 1: 115V/60Hz, 2: 220V/60Hz 3: 208-230V/60Hz 5: 200-220V/50Hz

7

Function

0~9 A~Z

8

9

Cooling/Heating

LG/OEM Brand

A~Z

A~Z

A A B C D E F G H I J K L M N P Q R S 4 8

0 0 1 2 3 5 6 7 8 9 Z Y X W V U T

6: 220-240V/50Hz 7: 110V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz

Basic Basic+4 Way Plasma Filter Plasma Filter+4 Way Tele + LED Tele + LCD Plasma F+4 Way+Tele+LCD Low A+A/change Low A+A/change+Plasma F Tele +LED+Plasma F Internet 4 way+Plasma F+ Oxygen generator 4 way+Soft Start 4 way+Star Rating 4 way+Star Rating +Plasma F 4 way+Soft S+Star Rating 4 way+Soft S+Star Rating 4+Plasma F 4 way+Tele+LCD 4 way+Tele+LCD+Soft Start 4 way+Mult Tele+LCD+Plasma F Wired remote controller

C: Cooling only H: Heat pump V: Inverter Cooling only N: Inverter Heat pump D: Gold fin(Outdoor) + Plasma + C/O

X: Cooling + E/Heater

L: LG Brand G: 2nd LG Brand

M: 1st OEM Brand N: 2nd OEM Brand

F: Cooling (New Ref.) R: Heat pump(New Ref.) E: Gold fin(Outdoor) + Plasma + H/P

Note: • Identification Rule 1 is old one. • Identification Rule 2 is new one.

2008 Product Data 5


2. Nomenclature • Identification Rule 2:

Code

L

S

1

2

-

C

1

8

6

T

L

B

3

4

5

6

7

8

9

Type

Code of Model

10

Meaning

1

Production Center, Refrigerant

A~Z

2 3

Product Type Cooling/Heating/Inverter

A~Z A~Z

4, 5

Capacity

0~9

6

Electric Range

1~9 A~Z

7

Chassis

A~Z

Name of Chassis of Unit

8

Look

A~Z

Looks : D – Look (Panel Type), G – Look (Grille Type) Glory Look :- (a) F –Look (Blue Color) (b) H – Look (Gold) (c) J – Look (Silver)

9

Function

A~Z

10

Serial No.

1~9

Note: • Identification Rule 1 is old one. • Identification Rule 2 is new one.

6

1

2008 Product Data

L: Chang-won R22 A: Chang-won R410A H: Thailand S: Split Type Air Conditioner C: Cooling only H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P Cooling/Heating Capacity Ex. "09" 9,000 Btu/h 1: 115V/60Hz, 2: 220V/60Hz 3: 208-230V/60Hz 5: 200-220V/50Hz 6: 220-240V/50Hz 7: 110V, 50/60Hz

A B C D E F G H I J K L M N P Q R S T U V W Y 7

Basic Basic+4Way Plasma Filter Plasma Filter+4 Way Tele+LCD Tele+LCD+Nano plasma+4Way NBF F+(A/changeover)+A/clean+Low A NBF F+(A/changeover)+A/clean+4way+Low A Tele+LED+4way Internet Plasma F+4Way+Oxygen generator NBF F+(A/changeover)+A/clean NBF F+(A/changeover)+A/clean+4way NBF F+(A/changeover)+A/clean+PTC NBF F+(A/changeover)+Autoclean+4way+PTC NBF F+(A/changeover)+A/clean+4way+Low A+PTC Negative ion+A/Clean (Nano)Plasma+Negative ion+A/Clean 4way+(Nano)Plasma F+Negative ion+A/Clean Nano Plasma F+4Way+(A/changeover)+A/clean+Oxygen generator 4way+(Nano)Plasma F+Negative ion+A/Clean+Oxygen generator Dry contact Basic+Low A NBF F+(A/changeover)+A/Clean+4Way(Thailand only)

LG Model Development Serial No.


3. Features & Benefits

NEO-Plasma Air Purifying System LG Electronics’ unique neo-plasma air purifying system, equipped with 12-level bio-enzyme filters, has further enhanced its sterilization power. While air passes each level of filters, the system powerfully eliminates household's fine dust and molds ordinary odor food smell and cigar smoke, as well as can destroy bacteria's cell walls to completely kill them. It has strong sterilization power.

Have you ever experienced these symptoms? Though the industrial development has enhanced people's quality of life and their satisfaction in living, it is increasingly creating various kinds of pollution, hazardous substances and viruses. In particular, substances (household tick dust, molds, etc.) that create allergies give rise to respiratory and atopic diseases. Harmful gases, the prime cause of 'new house syndromes,’ create chronic headache.

Whenever seasons change, You have runny nose

Asthma, and Continuous cough.

The skin is itchy without knowing reasons,

Frequent headache, and chronic fatigue...

You scratch it again and again...

1

First antibiotic

Allergy

2

Fishy smell

Foot stink

3

Animal smell

Odor of food garbage

Chemical substance

4

Influenza

Virus

Mite

5

Micro dust

Deodorize

Mold Smoke

Allergy Mold

Mite

Big dust

Odor of construction ingredient

Blanket dust Odor of food garbage

Chemical substance

Pollutant

2008 Product Data 7


3. Features & Benefits Plasma Filter

Nano Bio Fusion Filter

Nano bio fusion filters allow their nano-size bio enzymes to directly penetrate through cell walls of bacteria and allergen to decompose

The PLASMA Air Purifying System developed uniquely by LG not only removes microscopic contaminants and dust, but also removes house mites, pollen, and pet fur to prevent allergic diseases like asthma.

its cell nuclei and kill them.While conventional methods merely inactivate bacteria or destroy external cell walls, this innovative sterilization method can completely decompose bacteria's cell nuclei and kill them.

5

Bacteria, Virus

Bio Active Site Nano Particle

Nano Particle

Nano Particle

Active State

Bacteria Selective Capture

Bacteriolysis

Nano Particle

Polluted Air

Regeneration (Active State)

Distinctions from Conventional Filters Conventional

4 Simply inactivate bacteria

Destroy bacteria but allow part of them to survive

Nano Bio Fusion Filter

The bio enzyme destroys cell walls and nuclei of bacteria and allergens, thus completely kills bacteria

3

Nano-size carbon filters catch fine odorous particles again, and doubly and completely remove odors from the household, thus offering a pleasant environment.

What is Nano Carbon Ball?

2 Clean Air

Nano Carbon Filter

Nano(1/1Bil) ball structure,consisting of Nano carbon, is adopted as deodorizing material first in the world

200~500nm

Kitasato Research Center of Environmental Sciences - Inactivating Germs Test Result 99.9% Performance (No. 16_0113_1,2,3) Japan Food Research Laboratories - Inactivating Germs Test Result 99.9% Performance (No. 104093863-001,2,3,4,5) - Killing Virus (No. 204031236-001,2,3) Japan Spinners Inspecting Foundation (No. 624217, 019355-13) - NCB Deodorizing 4 Type Test Result 78%~98% Security

Pre Filter The antibacterial pre-filters primarily remove large dusts, molds, and quilt dusts.

8 2008 Product Data

Triple Filter

FITI Korea Consumer Science Center (No. 513104-195-A-01) - Killing bacteria, fungi Test Result 99.9% Security ITS(International Technical Standard Center) (No. IL26937-A,B) - Inactivating bacteria Test Result 99.9% Security

The triple filters consist of various organic-compound filter to eliminate displeasure and pain in the eyes and necks with various organic compounds. It also has a formaldehyde filter to cut off formaldehyde, a prime cause of new-house syndromes, and prevents symptoms such as dermatitis, vomiting and pneumonia. And lastly, it has a filter to remove ordinary odor that causes migraine and chronic fatigue.


3. Features & Benefits Healthy Dehumidification LG Wall Mounted Split models feature a Dehumidification mode to remove uncomfortable humidity from the room without over cooling.

Indoor Temperature Distribution Chart

Conventional Since the surrounding temperature is measured after the air from the unit is widely distributed, an accurate assessment of the air is not possible.

Healthy Dehumidification By increasing the Vane Angle, a better assessment of the actual temperature is possible to prevent over cooling.

Auto Clean The main cause of air conditioner's odor is molds that breed in the heatexchanger. If you turn off the air conditioner as it is, molds and bacteria will breed in the wet heat exchanger. The automatic cleaning function will dry the wet heat exchanger to prevent molds and bacteria from breeding. It will eliminate air conditioner's odor and save you time and frequent cleaning efforts.

When you press "Auto Clean�, Auto clean starts after cooling operation.

In 30 minutes, Auto clean" dries the inner part of Air conditioner.

1STEP : Dries the evaporator with super-weak, lownoise air blowing, and removes remaining moisture.

2STEP : Fundamentally removes the sources of molds once again through the neo plasma system.

2008 Product Data 9


Ultra Silent The indoor equipment, which adopts optimum fan and motor, implements a lowest-noise of 23db in the sleep mode. It offers you a quieter and more convenient sleeping environment and helps you concentrate when you work. In addition, the vibration and noise of the outdoor equipment has been reduced drastically so that it does not disturb your neighbours.

Indoor

Empty Studio

Outdoor

23dB

[Indoor equipment] 1. Uses low-noise motor and fan 2. Shuts off noise with an all-side panel design

Empty Concert Hall

45dB

[Outdoor equipment] 1. Low-noise compressor and lownoise fan 2. Designed for optimizing compressor vibration

Anti Rust Gold Fin™ LG's Heat exchanger surface is coated with an anticorrosive, gold on aluminum. This ensures their surface always free of corrosion and helps them perform like new one. Salt Spray Test for 15 Days

After 15 Days

LG Gold Fin™ Corrosion Free

Gold Coated Aluminum

After 15 Days

Uncoated Aluminum

• Gold Fin is long lasting, durable and makes the Outdoor Unit look prestigious.

10 2008 Product Data

LG Indoor

Conventional Starting to corrode

Low Noise Compressor

Quiet Libraryy

Hotel Lobby


3. Features & Benefits Auto Changeover

Low Ambient

With heat pump model,cooling and heating operation is changed automatically on the basis of setting temperature.

Cools the room as is necessary, even in winter. - In case you hold a party indoors in winter, you need to operate equipment in the computer server room for long hours, or you cannot open windows for security's sake, you can cool the room using the Inverter air conditioner. Under such circumstances, ordinary conventional air conditioners may have heat exchangers in indoor equipment frozen, thus not properly cooling the room. However, in the case of inverter air conditioners, you can adjust the speed of compressors and outdoor equipment's fan to prevent heat exchangers in indoor equipment from being frozen, thus cooling the room more easily.

• Initial Setting Temp:18˚C Memorize final setting temp.

Auto Restart Function

Hot Start Function

In case of a sudden power failure, It automatically sets the A/C to settings before the power failure when power returns.

When starting the unit in the heating mode this function prevents cold air blowing from the unit. It starts the indoor fan only after indoor unit pipe temperature reaches a preset value (28˚C).

Sleep Mode Auto Control

When indoor unit pipe temperature reaches 28˚C, then for initial 1 minute the indoor fan runs at a low speed and after that at the setting speed.

it automatically programs the Air Conditioning Unit to turn off, controls the fan speed and adjusts the set temperature for a more comfortable sleep.

With one touch of the Sleep mode button,

2008 Product Data 11


Heating mode

Cooling mode

New Chaos Swing The most comfortable airflow for the human body can be found in nature. After countless analysis, LG has applied the scientific chaos theory to its Air Conditioning range, which effectively produces a natural, fresh breeze.

Cooling mode

0.5hr

1hr

Heating mode

2hr

0.5hr

1hr

2hr

The chaos theory is a technology that recreates the flow of natural air by controlling the angle speed of the movement of the air vane. Chaos Swing technology also minimizes the temperature difference between high and low places in the room, creating a more comfortable and cooler environment.

LG

Co., A

Co., B

Up speed :12ms(Slow) Down speed :6ms(fast) Wind-up Effects: The Wind-up Effect is controlled by the Vane Angle Control to evenly distribute nature-like air throughout the room.

6ms

12ms

It swings at an angle twice wider than that of the existing Chaos swing, thus minimizing the difference in indoor temperatures and allowing air in every corner of the room.

32ยบ The angle is twice wider.

12 2008 Product Data


3. Features & Benefits Indoor Temperature Distribution Chart

4 Way Auto Swing LG Air Conditioning units can now automatically distribute the air 4-ways.

This effectively eliminates hot and cold patches, keeping the room at a more stable temperature. Chaos Swing

Auto Swing

Chaos Swing Effect

ARTCOOL_MIRROR TYPE

Jet Cool TM The Jet cool function allows quick cooling.

A little interior accent for the modern you. The romantic pastel colors, subdued luster,modern texture and the super slim design of LG ARTCOOL Mirror are the answers to your unique mood and personality.

In this mode, strong, cool air is blown at high speed for 30 minutes, until the room temperature reaches 18ËšC.

ARTCOOL_PANEL TYPE LG's unique frame-style of ARTCOOL panel type. Its super-slim and sensory design satisfies your sense.

10m It can cool the spot ten meters away in 3 minutes.

ARTCOOL_WIDE TYPE LG ARTCOOL Wide is a cool addition to your work-space. Like a piece of modern art, the golden-section design and the simple and modern design of LG Artcool Wide is an attractive, efficient and cool addition to your room.

2008 Product Data 13


Modern & Luxury Design

Gallery In My Room

Its premium designs match well with any part of the household.

Your room will shine chicly with a famous painting or a beautiful photo (showcased in the product). LG ARTCOOL will convert your room into a gallery. Do you like Western paintings, Oriental paintings, or photos? The product features your desired style of famous paintings.

THE STARRY NIGHT (1889) - VINCENT VAN GOGH

ALLEE DES MARRONIERS(1878) - SiISLEY, ALFRED

Ez-Replaceable Color Panel

Digital Air Flow Control

The ARTCOOL chameleon panel enables you to change the air conditioner color according to background colors, the first of its kind in the world. When you want to change interior designs (wallpaper colors, furniture, etc.) or you want to change the air conditioner designs after you are bored with them. You can only change the panel.

You feel more comfortable and convenient by controlling air flow.

Normal

Jet Cool

Sleep Mode

Fast & Even Widely

Speedy & Powerful

Indirectly & Softly

3 Dimensional Air Flow Designed like a work of art, and the new concept of 3 dimensional air flow. It gives even cooling as well as quick cooling from front and bothsides making the space evenly cool.

Ultra Thin Technology mixed with sense of art result in the super slim design which is 129mm depth.

The slimmest in the world!!!

129mm 14 2008 Product Data


4.Specifications GeneralWall Mounted Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Circulation Moisture Removal Noise Level (Sound Pressure,1m)

Cooling Heating Cooling Heating Cooling Heating

Indoor,Max Outdoor,Max

GeneralWall Mounted s106DC

Unit kcal/h.(W) Btu/h. kcal/h.(W) Btu/h. W W A A A A kcal/h.W(W/W) Btu/h.W W/W Ø,V,Hz % m 3/min(CFM) m 3/min(CFM) l/h.(pts/h.) dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3

s106DQ

s136DC

s136DQ

HS-C0964DA6 HS-H0964D71 HS-C1264DA3 HS-H1264D71 2,521 (2,930) 3,278(3809) 3,278(3809) 2,269(2,637) 10,000 13,000 9,000 13,000 3,326(3866) 2,521 (2,930) 13,200 10,000 950 1,300 1,300 950 900 1,250 6.0 4.2 6.0 4.1 4.8 4.0 2.52 (2.92) 2.39 (2.78) 2.65 (3.08) 2.52 (2.92) 9.5 10.5 10.0 10.0 3.09 3.08 1,220-240,50 1,220-240,50 1,220-240,50 1,220-240,50 98 94 98 94 8.8(311) 8.8(311) 6.8(240) 6.8(240) 23(812) 23(812) 23(812) 23(812) 1.5(3.20) 1.5(3.20) 1.2(2.56) 1.2(2.56) 37 37 32 32 33 33 29 29 30 30 24 24 49 49 47 47 Thermistor Thermistor Thermistor Thermistor Yes Yes Yes Yes Yes Yes Yes Yes 4-Way 2-Way 2-Way 4-Way 3/4 3/4 3/4 3/4 Auto Auto Auto Auto Auto Manual Auto Manual Wireless-LCD Wireless-LCD Wireless-LCD Wireless-LCD 18 - 30 18 - 30 18 - 30 18 - 30 16 - 30 16 - 30 1 1 1 1 Yes Yes Yes Yes Yes Yes Yes Yes 24h, On/Off 24h, On/Off 24h, On/Off 24h, On/Off Yes Yes Yes Yes Yes Yes Yes Yes 3 3 3 3 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 720(25.4) 800(28.2) 830(29.3) 830(29.3) Rotary Rotary Rotary Rotary QK164PDJ QK222PBA QK222PBA QK164PDJ LG LG LG LG 9350/9450 13100/13200 13100/13200 9350/9450 Single-Phase-Induction-Moto r Single-Phase-Induction-Moto Single-Phase-Induction-Moto Single-Phase-Induction-Moto 886/913 1254/1375 1254/1375 886/913 SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI 350 380 380 350 MRA12176 -12026 MRA12155 -12027 MRA12155 -12027 MRA12176 -12026 34.3 27.6 34.3 27.6 15.1 7.8 15.1 7.8 YDK23-6P YDK23-6P YDK23-6P YDK23-6P AC INDUCTION AC INDUCTION AC INDUCTION AC INDUCTION 63.2 63.2 63.2 63.2 25 25 25 25 15 15 15 15 18:3*0.75 18:3*0.75 16:3*1.0 16:3*1.0 16:3*1.0 16:3*1.0+18:2*0.75 16:3*1.0 16:3*1.0+18:2*0.75 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 9.52(3/8) 9.52(3/8) 7.5(295) 7.5(295) 7.5(295) 7.5(295) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 840*270*153 840*270*153 840*270*153 840*270*153 33.1*10.6*6.1 33.1*10.6*6.1 33.1*10.6*6.1 33.1*10.6*6.1 770*245*540 770*245*540 770*245*540 770*245*540 30.3*9.6*21.3 30.3*9.6*21.3 30.3*9.6*21.3 30.3*9.6*21.3 7(15.4) 7(15.4) 7(15.4) 7(15.4) 25(55) 25(55) 25(55) 25(55) 117/237 117/237 117/237 117/237

Indoor,High Med Low Outdoor,Max Features Temperature Control Plasma Filter Deodorizing Filter CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Optional) Steps, Fan/Cool Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature Range Cool Heat Temperature Increment Auto Operation (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Soft Start Hot Start Auto Changeover(only H/P model) Auto Clean Jet Cool Refrigerant(R22)Charge g(oz) Compressor Type Model Maker Capacity Btu/h Motor Type Motor Input W Oil Type Oil Charge cc O.L.P Name Blower Motor Input W Output W Fan Motor Model Motor Type Motor Input W Motor Output W Circuit Breaker A Power Cord AWG#:P*mm2 Connecting Cable AWG#:P*mm2 Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in) Length,std m(in) Drain Hose (O.D , I.D) mm(in) Dimension Indoor mm inch Outdoor mm inch Net Weight Indoor kg(lbs) Outdoor kg(lbs) Stuffing With S/Parts 20/40ft Quantity Without S/Parts 20/40ft * Filters are optional for some specific areas. * For circuit breaker rating,please conform to local standards wherever necessary.

2008 Product Data 15


4.Specifications GeneralWall Mounted Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Circulation Moisture Removal Noise Level (Sound Pressure,1m)

Cooling Heating Cooling Heating Cooling Heating

Indoor,Max Outdoor,Max

s196DC Unit kcal/h.(W) Btu/h. kcal/h.(W) Btu/h. W W A A A A kcal/h.W(W/W) Btu/h.W W/W Ø,V,Hz % m 3/min(CFM) m 3/min(CFM) l/h.(pts/h.) dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3

s196DQ

s276DC

HS-C1864DB5 HS-C1865DB6 HS-H1865D70 HS-C2665DB1 4,787 (5,564) 4,787(5,564) 6,803(7,907) 4,787(5,564) 19,000 27,000 19,000 19,000 4,787(5,564) 19,000 1,950 2,700 1,990 2,050 1,840 9.2 8.5 12.6 9.7 8.4 2.52 (2.92) 2.34 (2.71) 2.45 (2.85) 2.41 (2.80) 9.27 9.74 9.55 10.0 3.02 1,220-240,50 1,220-240,50 1,220-240,50 1,220-240,50 99 94 91 93 12.5(442) 14.0(495) 12.5(442) 12.5(442) 42(1,483) 42(1,483) 42(1,483) 42(1,483) 1.8(383) 1.8(3.83) 2.8(5.95) 1.8(383) 40 46 40 40 37 43 37 37 33 39 30 33 56 56 56 56 Thermistor Thermistor Thermistor Thermistor Yes Yes Yes Yes Yes Yes 4-Way 4-Way 4-Way 4-Way 3/4 3/4 3/4 3/4 Auto Auto Auto Auto Auto Auto Auto Auto Wireless-LCD Wireless-LCD Wireless-LCD Wireless-LCD 18 - 30 18 - 30 18 - 30 18 - 30 16 - 30 1 1 1 1 Yes Yes Yes Yes Yes Yes Yes Yes 24h, On/Off 24h, On/Off 24h, On/Off 24h, On/Off Yes Yes Yes Yes Yes Yes Yes Yes 3 3 3 3 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 1100(38.8) 1070(37.7) 1300(45.8) 1170(41.2) Rotary Rotary Rotary Rotary QP325PBA QP348PBC QP464PAA 2KS324D5BD04 LG LG LG MATSUSHITA 19200/19300 20500/20600 27600/27700 18950/19052 Single-Phase-Induction-Moto r Single-Phase-Induction-Moto Single-Phase-Induction-Moto Single-Phase-Induction-Moto 1778/1856 1884/1967 2654/2870 1865/2055 SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI 700 700 700 450 Internal Internal Internal Internal 50 50 58 50 19 19 25.6 19 YDK80-6Q YDK80-6Q YDK80-6Q YDK80-6Q AC INDUCTION AC INDUCTION AC INDUCTION AC INDUCTION 145 145 145 145 74 74 74 74 20 20 20 20 14:3*1.5 14:3*1.5 14:3*2.5 14:3*1.5 14:3*1.5+18:2*0.75 14:3*2.5 14:3*1.5 14:3*1.5 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/4) 12.7(1/2) 15.88(5/8) 12.7(1/2) 12.7(1/2) 7.5(295) 7.5(295) 7.5(295) 7.5(295) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 1090*300*180 1090*300*180 1090*300*180 1090*300*180 42.9*11.8*7.1 42.9*11.8*7.1 42.9*11.8*7.1 42.9*11.8*7.1 870*655*320 870*655*320 870*655*320 870*655*320 34.3*25.8*12.6 34.3*25.8*12.6 34.3*25.8*12.6 34.3*25.8*12.6 13.5(29.7) 13.5(29.7) 13.5(29.7) 13.5(29.7) 50(110.2) 50(110.2) 50(110.2) 60(110.2) 60/129 60/129 60/129 60/129

Indoor,High Med Low Outdoor,Max Features Temperature Control Plasma Filter Deodorizing Filter CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Optional) Steps, Fan/Cool Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature Range Cool Heat Temperature Increment Auto Operation (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Soft Start Hot Start Auto Changeover(only H/P model) Auto Clean Jet Cool Refrigerant(R22)Charge g(oz) Compressor Type Model Maker Capacity Btu/h. Motor Type Motor Input W Oil Type Oil Charge cc O.L.P Name Blower Motor Input W Output W Fan Motor Model Motor Type Motor Input W Motor Output W Circuit Breaker A Power Cord AWG#:P*mm2 Connecting Cable AWG#:P*mm2 Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in) Length,std m(in) Drain Hose (O.D , I.D) mm(in) Dimension Indoor mm inch Outdoor mm inch Net Weight Indoor kg(lbs) Outdoor kg(lbs) Stuffing With S/Parts 20/40ft Quantity Without S/Parts 20/40ft * Filters are optional for some specific areas. * For circuit breaker rating,please conform to local standards wherever necessary.

16 2008 Product Data

GeneralWall Mounted


4.Specifications GeneralWall Mounted Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Circulation Moisture Removal Noise Level (Sound Pressure,1m)

Cooling Heating Cooling Heating Cooling Heating

Indoor,Max Outdoor,Max

GeneralWall Mounted s276DQ

Unit kcal/h.(W) Btu/h. kcal/h.(W) Btu/h. W W A A A A kcal/h.W(W/W) Btu/h.W W/W Ø,V,Hz % m 3/min(CFM) m 3/min(CFM) l/h.(pts/h.) dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3

HS-H2665D70 HS-C1264DA3 HS-H1264D71 3,278(3809) 3,278(3809) 6,804(7,908) 13,000 27,000 13,000 3,278(3809) 6,804(7,908) 13,000 27,000 1,300 1,300 2,700 2,770 1,250 12.6 6.0 6.0 12.6 4.8 2.52 (2.92) 2.52 (2.99) 2.52 (2.92) 10.0 10.0 10.0 2.85 3.05 1,220-240,50 1,220-240,50 1,220-240,50 95 93 95 8.8(311) 8.8(311) 14.0(495) 6.8(240) 23(812) 23(812) 23(812) 42(1,483) 1.5(3.20) 1.5(3.20) 2.8(5.95) 1.2(2.56) 37 37 46 32 33 33 43 29 30 30 39 24 49 49 56 47 Thermistor Thermistor Thermistor Thermistor Yes Yes Yes Yes Yes Yes Yes Yes 4-Way 2-Way 4-Way 4-Way 3/4 3/4 3/4 3/4 Auto Auto Auto Auto Auto Manual Auto Wireless-LCD Wireless-LCD Wireless-LCD Wireless-LCD 18 - 30 18 - 30 18 - 30 18 - 30 16 - 30 16 - 30 1 1 1 1 Yes Yes Yes Yes Yes Yes Yes Yes 24h, On/Off 24h, On/Off 24h, On/Off 24h, On/Off Yes Yes Yes Yes Yes Yes Yes Yes 3 3 3 3 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 1400(49.3) 800(28.2) 830(29.3) 830(29.3) Rotary Rotary Rotary Rotary QK164PDJ QK222PCC QK222PCC QP464PAA LG LG LG LG (9350/9450) (12900/13100) (12900/13100) 27600/27700 Single-Phase-Induction-Moto r Single-Phase-Induction-Moto Single-Phase-Induction-Moto Single-Phase-Induction-Moto 886/913 1230/1300 1230/1300 2654/2870 SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI SUNISO 4GSI 350 380 380 700 MRA12176 -12026 MRA98990 -12027 MRA98990 -12027 Internal 34.3 58 34.3 27.6 15.1 25.6 15.1 7.8 YDK23-6P YDK23-6P YDK23-6P YDK80-6Q AC INDUCTION AC INDUCTION AC INDUCTION AC INDUCTION 63.2 63.2 63.2 145 25 25 25 74 15 15 15 15 18:3*0.75 14:3*2.5 16:3*1.0 16:3*1.0 14:3*2.5+18:2*0.75 9.52(3/8) 6.35(1/4) 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 15.88(5/8) 9.52(3/8) 7.5(295) 7.5(295) 7.5(295) 7.5(295) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 26.5,12.2(1.04,0.48) 940*270*150 940*270*150 1090*300*180 940*270*150 33.1*10.6*6.0 33.1*10.6*6.0 42.9*11.8*7.1 33.1*10.6*6.0 717*498*228 717*498*228 870*655*320 717*498*228 28.2*19.6*9.0 28.2*19.6*9.0 34.3*25.8*12.6 28.2*19.6*9.0 13.5(29.7) 7(15.4) 7(15.4) 7(15.4) 60(110.2) 25(55) 25(55) 25(55) 128/277 128/277 128/277 130/280 130/280 130/280 60/129

Indoor,High Med Low Outdoor,Max Features Temperature Control Plasma Filter Deodorizing Filter CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Optional) Steps, Fan/Cool Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature Range Cool Heat Temperature Increment Auto Operation (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Soft Start Hot Start Auto Changeover(only H/P model) Auto Clean Jet Cool Refrigerant(R22)Charge g(oz) Compressor Type Model Maker Capacity Btu/h. Motor Type Motor Input W Oil Type Oil Charge cc O.L.P Name Blower Motor Input W Output W Fan Motor Model Motor Type Motor Input W Motor Output W Circuit Breaker A Power Cord AWG#:P*mm2 Connecting Cable AWG#:P*mm2 Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in) Length,std m(in) Drain Hose (O.D , I.D) mm(in) Dimension Indoor mm inch Outdoor mm inch Net Weight Indoor kg(lbs) Outdoor kg(lbs) Stuffing With S/Parts 20/40ft Quantity Without S/Parts 20/40ft * Filters are optional for some specific areas. * For circuit breaker rating,please conform to local standards wherever necessary.

2008 Product Data 17


5. Dimensional Drawings

18 2008 Product Data

Indoor Units


5. Dimensional Drawings

Right rear piping

Ø70mm

240mm

Left rear piping

5

100mm

Ø70mm

Indoor Units

2008 Product Data

19


5. Dimensional Drawings

1

Outdoor Units

20 2008 Product Data


5. Dimensional Drawings

1

Outdoor Units

2008 Product Data 21


6. Wiring Diagrams 6.1 Indoor Units Models: HS-H0964D71 HS-H1264D71 HS-H1865D70 HS-H2665D70

Models: HS-C0964DA6 HS-C1264DA3 HS-C1865DB5 HS-C1865DB6 HS-C2665DB1

22

2008 Product Data

Indoor Units


6. Wiring Diagram

Indoor Units

6.1 Indoor Units

RY-COMP3 FUSE

CN-L/R(BL) CN-HVB(BL) CN-U/D(WH)

RY-COMP4 CN-DISP2(BL)

CN-N1 CN-DISP1(WH) CN-MOTOR

CN-TH1(WH) CN-12V(YL)

CN-4WAY

CN-OPTION

2008 Product Data

23


6. Wiring Diagram 6.2 Outdoor Units

Models: HS-C0964DA6 HS-C1264DA3 HS-C1865DB5 HS-C1865DB6 HS-C2665DB1

Models: HS-H1264D71 HS-H0964D71

24

2008 Product Data

Outdoor Units


6. Wiring Diagram

Outdoor Units

6.2 Outdoor Units

Capacitor

Terminal Block

2008 Product Data

25


6. Wiring Diagram 6.2 Outdoor Units

Models: HS-H2665D70 HS-H1865D70

26

2008 Product Data

Outdoor Units


6. Wiring Diagram

Outdoor Units

6.2 Outdoor Units

Terminal Block

Capacitor

Terminal Block

2008 Product Data

27


7. Refrigerant Cycle Diagram For Cooling Only models, Indoor Unit

Outdoor Unit Liquid Side

Capillary Tube

Th3 Th1

Heat Exchanger (Condenser)

Heat Exchanger (Evaporator)

Gas Side

Compressor

Cooling

For Heat Pump models, Outdoor Unit

Indoor Unit Liquid Side Th3

Check Valve (Heating Model only)

3-Way Valve

Capillary Tube

Th1

Heat Exchanger (Evaporator)

Heat Exchanger (Condenser)

Th2*

Gas Side 3-Way Valve

Reversing Valve (Heating Model Only)

Accumulator

Compressor

N.B. :Th1 = thermistor for sensing Indoor air temperature. Th2* = thermistor for sensing Outdoor air temperature(used only in very special cases) Th3 = thermistor for sensing Evaporating temperature. = direction of refrigerant flow in cooling mode. = direction of refrigerant flow in Heating mode.

28

2008 Product Data

Cooling Heating


7. Refrigerant Cycle Diagram For Cooling Only models, Indoor Unit

Outdoor Unit Capillary Tube

Liquid Side Th2

2-Way Valve

Th1

Heat Exchanger (Evaporator)

Heat Exchanger (Condenser)

Compressor

Gas Side 3-Way Valve

Accumulator

High Pressure S/W Cooling

For Heat Pump models, Indoor Unit

Outdoor Unit Liquid Side

Th2

Capillary Tube

2-Way Valve

Th1

Heat Exchanger (Evaporator)

Heat Exchanger (Condenser)

Gas Side

Reversing Valve High Pressure S/W

3-Way Valve

Accumulator

Compressor

Cooling Heating

N.B. :Th1 = thermistor for sensing Indoor air temperature. Th2* = thermistor for sensing Outdoor air temperature(used only in very special cases) Th3 = thermistor for sensing Evaporating temperature. = direction of refrigerant flow in cooling mode. = direction of refrigerant flow in Heating mode.

2008 Product Data

29


8. Capacity Tables

Cooling

Cooling capacity HS-C0964DA6 Outdoor DB( C ) Indoor WB( C ) 16.1 TC SHC Indoor DB( C ) PI TC 23.9 2.5 2.1 0.86 2.7

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 1.6 0.89 2.9 0.7 0.90 2.4 2.2 0.95 2.6

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 1.6 0.98 2.8 0.7 1.00 2.3 2.1 1.02 2.6

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 1.6 1.05 2.7 0.7 1.07 2.2 2.1 1.07 2.4

46.1 19.4 22.8 SHC PI TC SHC PI 1.6 1.11 2.6 0.7 1.13

26.7

2.6 2.4 0.86 2.8 2.0 0.89 2.9 1.3 0.91 2.5 2.5 0.95 2.7 2.1 0.98 2.8 1.3 1.00 2.4 2.4 1.02 2.6 2.0 1.05 2.7 1.3 1.07 2.3 2.3 1.08 2.4 2.0 1.11 2.6 1.3 1.13

29.4

2.7 2.7 0.86 2.8 2.4 0.89 2.9 1.8 0.91 2.6 2.6 0.96 2.7 2.5 0.99 2.8 1.9 1.00 2.5 2.5 1.02 2.6 2.4 1.05 2.7 1.8 1.07 2.4 2.4 1.08 2.5 2.3 1.12 2.6 1.8 1.14

32.2

2.8 2.8 0.87 2.9 2.7 0.89 2.9 2.2 0.91 2.7 2.7 0.96 2.8 2.8 0.99 2.8 2.3 1.01 2.6 2.6 1.03 2.7 2.7 1.06 2.7 2.2 1.08 2.4 2.4 1.08 2.5 2.5 1.12 2.6 2.2 1.14

HS-C1264DA3 Outdoor DB( Indoor WB( Indoor DB( 23.9

C) 16.1 C) C) TC SHC PI TC 3.4 2.7 1.18 3.7

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.0 1.22 4.0 0.9 1.24 3.3 2.7 1.30 3.6

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.1 1.34 3.9 0.9 1.37 3.1 2.7 1.39 3.5

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.0 1.44 3.7 0.9 1.46 3.0 2.6 1.47 3.3

46.1 19.4 22.8 SHC PI TC SHC PI 2.0 1.52 3.5 0.9 1.55

26.7

3.5 3.1 1.18 3.8 2.5 1.22 4.0 1.7 1.24 3.4 3.1 1.31 3.7 2.6 1.35 3.9 1.7 1.37 3.3 3.0 1.40 3.5 2.5 1.44 3.7 1.6 1.47 3.1 3.0 1.48 3.3 2.5 1.53 3.5 1.6 1.55

29.4

3.7 3.4 1.19 3.9 3.1 1.22 4.0 2.3 1.25 3.5 3.4 1.31 3.7 3.1 1.35 3.9 2.3 1.38 3.4 3.3 1.40 3.6 3.0 1.45 3.7 2.3 1.47 3.2 3.2 1.48 3.4 3.0 1.53 3.5 2.2 1.56

32.2

3.8 3.5 1.19 3.9 3.4 1.23 4.0 2.8 1.25 3.6 3.6 1.31 3.8 3.5 1.36 3.8 2.9 1.38 3.5 3.5 1.41 3.6 3.4 1.45 3.7 2.8 1.48 3.3 3.3 1.49 3.4 3.3 1.53 3.5 2.7 1.56

HS-C1865DB5 Outdoor DB( C ) Indoor WB( C) 16.1 TC SHC DB( ) C Indoor PI TC 23.9 5.0 4.0 1.87 5.5

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.0 1.92 5.9 1.3 1.96 4.8 4.1 2.06 5.3

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.1 2.13 5.7 1.4 2.17 4.6 4.0 2.21 5.1

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.0 2.28 5.5 1.3 2.32 4.4 3.9 2.33 4.8

46.1 19.4 22.8 SHC PI TC SHC PI 2.9 2.41 5.2 1.3 2.45

26.7

5.2 4.6 1.87 5.6 3.8 1.93 5.9 2.5 1.97 5.0 4.7 2.07 5.4 3.9 2.13 5.7 2.5 2.17 4.8 4.6 2.21 5.2 3.8 2.28 5.5 2.5 2.33 4.6 4.4 2.34 4.9 3.7 2.41 5.2 2.4 2.46

29.4

5.4 5.0 1.88 5.7 4.6 1.94 5.9 3.4 1.97 5.2 5.1 2.07 5.5 4.7 2.14 5.7 3.5 2.18 5.0 5.0 2.22 5.3 4.5 2.29 5.5 3.4 2.33 4.7 4.7 2.35 5.0 4.4 2.42 5.2 3.3 2.47

32.2

5.6 5.3 1.88 5.7 5.1 1.94 5.9 4.2 1.98 5.4 5.4 2.08 5.5 5.2 2.15 5.7 4.3 2.19 5.2 5.2 2.23 5.3 5.0 2.30 5.5 4.2 2.34 4.9 4.9 2.35 5.0 4.9 2.43 5.1 4.0 2.47

• Symbol

• Notes

DB : Dry bulb temperature

[°C]

WB : Wet bulb temperature

[°C]

1. All capacites are net, evaporator fan motor heat is deducted.

TC : Total capacity

[kW]

2.

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

PI : Power Input [kW] (Comp.+ indoor fan motor+outdoor fan motor)

30

2008 Product Data

Indicates nominal capacity.

4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.


8. Capacity Tables

Cooling

HS-C1865DB6 Outdoor DB( C ) Indoor WB( C ) 16.1 Indoor DB( C ) TC SHC PI TC 23.9 4.6 3.7 1.72 5.1

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.8 1.78 5.4 1.3 1.81 4.4 3.8 1.90 4.9

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.9 1.96 5.2 1.3 2.00 4.3 3.7 2.04 4.7

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.8 2.10 5.1 1.2 2.14 4.0 3.6 2.15 4.4

46.1 19.4 22.8 SHC PI TC SHC PI 2.7 2.22 4.8 1.2 2.26

26.7

4.8 4.3 1.73 5.1 3.6 1.78 5.4 2.3 1.81 4.6 4.4 1.91 5.0 3.6 1.97 5.2 2.4 2.00 4.4 4.3 2.04 4.8 3.5 2.11 5.1 2.3 2.15 4.2 4.2 2.16 4.5 3.4 2.23 4.8 2.2 2.27

29.4

5.0 4.7 1.73 5.2 4.3 1.79 5.4 3.2 1.82 4.8 4.8 1.91 5.0 4.4 1.97 5.2 3.3 2.01 4.6 4.6 2.05 4.9 4.3 2.11 5.1 3.2 2.15 4.4 4.4 2.17 4.6 4.1 2.23 4.8 3.1 2.28

32.2

5.1 5.0 1.74 5.3 4.8 1.79 5.4 3.9 1.82 4.9 4.9 1.92 5.1 4.8 1.98 5.2 4.0 2.02 4.8 4.8 2.05 4.9 4.7 2.12 5.0 3.9 2.16 4.5 4.5 2.17 4.6 4.6 2.24 4.7 3.8 2.28

HS-C2665DB1 Outdoor DB( C ) Indoor WB( C ) 16.1 Indoor DB( C ) TC SHC PI TC 23.9 6.3 4.8 2.41 7.0

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.6 2.49 7.5 1.6 2.53 6.1 4.9 2.66 6.7

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.7 2.75 7.2 1.6 2.80 5.9 4.8 2.85 6.5

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.6 2.94 7.0 1.6 3.00 5.5 4.7 3.01 6.1

46.1 19.4 22.8 SHC PI TC SHC PI 3.5 3.11 6.6 1.6 3.17

26.7

6.6 5.5 2.42 7.1 4.6 2.49 7.5 3.0 2.54 6.3 5.6 2.67 6.8 4.7 2.76 7.2 3.1 2.81 6.1 5.5 2.86 6.6 4.5 2.95 7.0 3.0 3.00 5.8 5.3 3.02 6.2 4.4 3.12 6.6 2.9 3.18

29.4

6.8 6.1 2.42 7.2 5.5 2.50 7.5 4.1 2.55 6.6 6.2 2.68 6.9 5.6 2.76 7.2 4.2 2.82 6.4 6.0 2.87 6.7 5.5 2.96 7.0 4.1 3.01 6.0 5.9 3.03 6.3 5.3 3.13 6.6 4.0 3.19

32.2

7.1 6.4 2.43 7.3 6.1 2.51 7.4 5.0 2.55 6.8 6.5 2.69 7.0 6.2 2.77 7.2 5.1 2.82 6.6 6.3 2.88 6.8 6.1 2.97 6.9 5.0 3.02 6.2 6.2 3.04 6.4 5.9 3.14 6.5 4.9 3.20

HS-H0964D71 Outdoor DB( Indoor WB( Indoor DB( 23.9 26.7 29.4 32.2

C) C) C ) TC 2.5 2.7 2.8 2.9

16.1 SHC PI TC 2.2 0.89 2.8 2.5 0.89 2.9 2.7 0.90 2.9 2.9 0.90 2.9

29.4 19.4 SHC PI TC 1.6 0.92 3.0 2.0 0.92 3.0 2.5 0.92 3.0 2.7 0.93 3.0

22.8 SHC PI TC 0.7 0.94 2.5 1.3 0.94 2.6 1.9 0.94 2.7 2.3 0.94 2.7

16.1 SHC PI TC 2.2 0.98 2.7 2.5 0.99 2.8 2.7 0.99 2.8 2.7 0.99 2.8

35.0 19.4 SHC PI TC 1.7 1.02 2.9 2.1 1.02 2.9 2.5 1.02 2.9 2.8 1.03 2.9

• Symbol DB : Dry bulb temperature

22.8 SHC PI TC 0.7 1.03 2.4 1.4 1.04 2.5 1.9 1.04 2.6 2.3 1.04 2.7

16.1 SHC PI TC 2.1 1.05 2.6 2.5 1.06 2.7 2.6 1.06 2.7 2.7 1.06 2.7

40.6 19.4 SHC PI TC 1.6 1.09 2.8 2.0 1.09 2.8 2.4 1.09 2.8 2.7 1.10 2.8

22.8 SHC PI TC 0.7 1.11 2.2 1.3 1.11 2.3 1.8 1.11 2.4 2.2 1.12 2.5

16.1 SHC PI TC 2.1 1.11 2.5 2.3 1.12 2.5 2.4 1.12 2.6 2.5 1.12 2.6

46.1 19.4 SHC PI TC 1.6 1.15 2.7 2.0 1.15 2.7 2.4 1.16 2.7 2.6 1.16 2.6

22.8 SHC PI 0.7 1.17 1.3 1.17 1.8 1.18 2.2 1.18

• Notes [°C]

WB : Wet bulb temperature

[°C]

1. All capacites are net, evaporator fan motor heat is deducted.

TC : Total capacity

[kW]

2.

SHC : Sensible capacity

[kW]

3. Direct interpolation is permissible. Do not extrapolate

PI : Power Input [kW] (Comp.+ indoor fan motor+outdoor fan motor)

Indicates nominal capacity.

4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.

2008 Product Data 31


8. Capacity Tables

Cooling

HS-H1264D71 Outdoor DB( C ) Indoor WB( C ) 16.1 Indoor DB( C ) TC SHC PI TC 23.9 3.5 2.9 1.21 3.9

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.2 1.25 4.2 1.0 1.27 3.4 2.9 1.34 3.8

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.2 1.38 4.0 1.0 1.40 3.3 2.8 1.43 3.6

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.1 1.48 3.9 0.9 1.50 3.1 2.8 1.51 3.4

46.1 19.4 22.8 SHC PI TC SHC PI 2.1 1.56 3.7 0.9 1.59

26.7

3.7 3.3 1.21 4.0 2.7 1.25 4.2 1.8 1.27 3.5 3.3 1.34 3.8 2.8 1.38 4.0 1.8 1.41 3.4 3.3 1.44 3.7 2.7 1.48 3.9 1.8 1.51 3.2 3.2 1.52 3.5 2.6 1.57 3.7 1.7 1.59

29.4

3.8 3.6 1.22 4.0 3.3 1.26 4.2 2.4 1.28 3.7 3.7 1.35 3.9 3.3 1.39 4.0 2.5 1.41 3.5 3.5 1.44 3.7 3.2 1.49 3.9 2.4 1.51 3.3 3.3 1.52 3.5 3.1 1.57 3.7 2.4 1.60

32.2

3.9 3.8 1.22 4.1 3.6 1.26 4.1 3.0 1.28 3.8 3.8 1.35 3.9 3.7 1.39 4.0 3.0 1.42 3.7 3.7 1.44 3.8 3.6 1.49 3.9 3.0 1.52 3.5 3.5 1.53 3.6 3.5 1.58 3.6 2.9 1.60

HS-H1865D70 Outdoor DB( C ) Indoor WB( C ) 16.1 Indoor DB( C ) TC SHC PI TC 23.9 4.7 3.8 1.72 5.2

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.9 1.77 5.6 1.3 1.80 4.6 3.9 1.90 5.1

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.0 1.96 5.4 1.3 1.99 4.4 3.8 2.03 4.9

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 2.9 2.10 5.3 1.3 2.13 4.2 3.7 2.15 4.6

46.1 19.4 22.8 SHC PI TC SHC PI 2.8 2.22 5.0 1.2 2.26

26.7

5.0 4.4 1.72 5.3 3.6 1.78 5.6 2.4 1.81 4.8 4.5 1.90 5.2 3.7 1.96 5.4 2.4 2.00 4.6 4.4 2.04 5.0 3.6 2.10 5.3 2.4 2.14 4.4 4.2 2.15 4.7 3.5 2.22 5.0 2.3 2.26

29.4

5.1 4.8 1.73 5.4 4.4 1.78 5.6 3.3 1.81 5.0 4.9 1.91 5.2 4.5 1.97 5.4 3.3 2.01 4.8 4.8 2.04 5.0 4.3 2.11 5.2 3.3 2.15 4.5 4.5 2.16 4.8 4.2 2.23 4.9 3.2 2.27

32.2

5.3 5.1 1.73 5.5 4.9 1.79 5.6 4.0 1.82 5.1 5.1 1.91 5.3 4.9 1.98 5.4 4.1 2.01 4.9 4.9 2.05 5.1 4.8 2.11 5.2 4.0 2.15 4.7 4.7 2.17 4.8 4.7 2.24 4.9 3.9 2.28

HS-H2665D70 Outdoor DB( C ) Indoor WB( C ) 16.1 Indoor DB( C ) TC SHC PI TC 23.9 6.3 4.8 2.51 6.9

29.4 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.6 2.59 7.4 1.6 2.64 6.0 4.9 2.78 6.7

35.0 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.7 2.86 7.2 1.6 2.92 5.8 4.7 2.97 6.4

40.6 19.4 22.8 16.1 SHC PI TC SHC PI TC SHC PI TC 3.6 3.07 6.9 1.6 3.12 5.5 4.6 3.14 6.1

46.1 19.4 22.8 SHC PI TC SHC PI 3.5 3.24 6.5 1.5 3.30

26.7

6.5 5.5 2.52 7.0 4.5 2.60 7.4 3.0 2.65 6.3 5.6 2.79 6.8 4.6 2.87 7.2 3.0 2.93 6.1 5.4 2.98 6.6 4.5 3.08 6.9 2.9 3.13 5.7 5.3 3.15 6.2 4.4 3.25 6.5 2.9 3.31

29.4

6.8 6.0 2.53 7.1 5.4 2.61 7.4 4.1 2.65 6.5 6.1 2.79 6.9 5.5 2.88 7.2 4.2 2.93 6.3 5.9 2.99 6.7 5.4 3.08 6.9 4.1 3.14 6.0 5.8 3.16 6.3 5.3 3.26 6.5 4.0 3.32

32.2

7.0 6.3 2.53 7.2 6.0 2.61 7.4 5.0 2.66 6.8 6.4 2.80 7.0 6.2 2.89 7.1 5.1 2.94 6.5 6.3 3.00 6.7 6.0 3.09 6.9 4.9 3.15 6.2 6.1 3.17 6.3 5.8 3.27 6.5 4.8 3.33

• Symbol

• Notes

DB : Dry bulb temperature

[°C]

WB : Wet bulb temperature

[°C]

1. All capacites are net, evaporator fan motor heat is deducted.

TC : Total capacity

[kW]

2.

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

PI : Power Input [kW] (Comp.+ indoor fan motor+outdoor fan motor)

32

2008 Product Data

Indicates nominal capacity.

4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.


8. Capacity Tables

Heating

Heating capacity HS-H0964D71 Indoor Air Temperature ℃DB 16 18 20 22 24

-10 TC 1.8 1.7 1.7 1.6 1.6

-5 PI 0.6 0.7 0.7 0.7 0.7

TC 2.1 2.1 2.0 1.9 1.9

PI 0.8 0.8 0.8 0.8 0.9

Outdoor Air Temperature : ℃WB 2 4 TC PI TC PI 2.6 0.8 2.7 0.8 2.5 0.8 2.6 0.8 2.4 0.8 2.5 0.9 2.3 0.9 2.5 0.9 2.3 0.9 2.4 0.9

TC 2.9 2.8 2.7 2.6 2.5

PI 1.1 1.2 1.2 1.2 1.3

Outdoor Air Temperature : ℃WB 2 4 TC PI TC PI 3.7 1.1 3.8 1.2 3.5 1.2 3.7 1.2 3.4 1.2 3.6 1.3 3.3 1.3 3.5 1.3 3.2 1.3 3.3 1.3

TC 4.0 3.9 3.8 3.7 3.5

PI 1.6 1.7 1.7 1.8 1.9

Outdoor Air Temperature : ℃WB 2 4 TC PI TC PI 5.3 1.7 5.6 1.7 5.1 1.7 5.4 1.8 5.0 1.8 5.2 1.8 4.8 1.9 5.0 1.9 4.6 1.9 4.9 2.0

TC 5.9 5.7 5.5 5.3 5.1

0 PI 0.7 0.7 0.7 0.8 0.8

TC 2.5 2.4 2.3 2.2 2.2

6

10 PI 0.8 0.8 0.9 0.9 0.9

TC 3.1 3.0 2.9 2.8 2.7

PI 1.2 1.2 1.3 1.3 1.4

TC 4.4 4.2 4.1 4.0 3.8

PI 1.8 1.8 1.9 1.9 2.0

TC 6.3 6.1 6.0 5.7 5.6

15 PI 0.9 0.9 0.9 0.9 1.0

TC 3.4 3.3 3.2 3.1 3.0

PI 1.3 1.3 1.4 1.4 1.4

TC 4.8 4.7 4.5 4.4 4.2

PI 1.9 1.9 2.0 2.0 2.1

TC 7.0 6.8 6.6 6.3 6.1

PI 0.9 1.0 1.0 1.0 1.0

HS-H1264D71 Indoor Air Temperature ℃DB 16 18 20 22 24

-10

-5

TC 2.6 2.5 2.4 2.3 2.2

PI 0.9 1.0 1.0 1.0 1.1

TC 3.0 2.9 2.8 2.7 2.6

0 PI 1.0 1.1 1.1 1.1 1.2

TC 3.5 3.4 3.3 3.1 3.0

6

10

15 PI 1.4 1.4 1.4 1.5 1.5

HS-H1865D70 Indoor Air Temperature ℃DB 16 18 20 22 24

-10 TC 3.7 3.6 3.5 3.4 3.2

-5 PI 1.4 1.4 1.5 1.5 1.6

TC 4.4 4.2 4.1 3.9 3.8

0 PI 1.5 1.5 1.6 1.7 1.7

TC 5.0 4.9 4.7 4.6 4.4

• Symbol

6

10

15

• Notes

DB : Dry bulb temperature

[°C]

WB : Wet bulb temperature

[°C]

1. All capacites are net, evaporator fan motor heat is deducted.

TC : Total capacity

[kW]

2.

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

PI : Power Input [kW] (Comp.+ indoor fan motor+outdoor fan motor)

Indicates nominal capacity.

4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.

2008 Product Data

33

PI 2.0 2.1 2.1 2.2 2.3


8. Capacity Tables

Heating

HS-H2665D70 Indoor Air Temperature ℃DB 16 18 20 22 24

-10 TC 4.8 4.6 4.5 4.3 4.2

-5 PI 2.0 2.1 2.2 2.2 2.3

TC 5.6 5.4 5.3 5.1 4.9

0 PI 2.2 2.3 2.4 2.4 2.5

TC 6.5 6.3 6.1 5.9 5.7

PI 2.4 2.5 2.6 2.7 2.7

• Symbol DB : Dry bulb temperature

Outdoor Air Temperature : ℃WB 2 4 TC PI TC PI 6.8 2.5 7.1 2.6 6.6 2.6 6.9 2.7 6.4 2.7 6.7 2.7 6.2 2.7 6.5 2.8 5.9 2.8 6.2 2.9

6 TC 7.5 7.3 7.0 6.8 6.6

10 PI 2.6 2.7 2.8 2.9 3.0

TC 8.2 7.9 7.7 7.4 7.1

15 PI 2.7 2.8 2.9 3.0 3.1

TC 9.0 8.7 8.5 8.1 7.9

• Notes

WB : Wet bulb temperature

[°C]

1. All capacites are net, evaporator fan motor heat is deducted.

TC : Total capacity

[kW]

2.

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

[°C]

PI : Power Input [kW] (Comp.+ indoor fan motor+outdoor fan motor)

34 2008 Product Data

Indicates nominal capacity.

4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.

PI 2.9 3.0 3.1 3.2 3.3


9. Capacity Coefficient factor • Model: 5 kBtu/h ~ 26 kBtu/h Cooling Only

Classification

Outdoor (A) Indoor Indoor (A) Outdoor

Capacity Coefficient factor Total Pipe Length(m)

Height (A)

5

7.5

10

12.5

15

10

-

-

-

(0.94)

(0.93)

7

-

0.97

0.96

(0.95)

(0.94)

5

0.99

0.98

0.97

(0.96)

(0.95)

0

1.0

0.99

0.98

(0.97)

(0.96)

0

1.0

0.99

0.98

(0.97)

(0.96)

5

0.99

0.98

0.97

(0.96)

(0.95)

7

-

0.97

0.96

(0.95)

(0.94)

10

-

-

-

(0.94)

(0.93)

The values in parentheses are valid only for 18~24kBtu models.

• Model: 5 kBtu/h ~ 14 kBtu/h Heat Pump Classification

Outdoor (A) Indoor Indoor (A) Outdoor

Capacity Coefficient factor Total Pipe Length(m)

Height (A) 5

7.5

10

12.5

15

10

-

-

-

-

-

7

-

0.97

0.97

-

-

5

0.99

0.98

0.97

-

-

0

1.0

0.99

0.98

-

-

0

1.0

0.99

0.98

-

-

5

0.99

0.98

0.97

-

-

7

-

0.97

0.97

-

-

10

-

-

-

-

-

2008 Product Data

35


9. Capacity Coefficient factor

• Model: 18 kBtu/h ~ 26 kBtu/h Heat Pump Capacity Coefficient factor Total Pipe Length(m)

Height

Classification

(A)

5

7.5

10

12.5

15

10

-

-

-

0.94

0.93

7

-

0.97

0.96

0.95

0.94

5

0.99

0.98

0.97

0.96

0.95

0

1.0

0.99

0.98

0.97

0.96

Indoor

0

1.0

0.99

0.98

0.97

0.96

(A)

5

0.99

0.98

0.97

0.96

0.95

7

-

0.97

0.96

0.95

0.94

10

-

-

-

0.94

0.93

Outdoor (A) Indoor

Outdoor

Piping length and elevation

7k~12k

18k~24k

30k~36k

Max. Length A (m)

Additional Refrigerant (g/m)

Gas

Liquid

3/8"(Ø9.52)

1/4"(Ø6.35)

7.5

7

15

20

1/2"(Ø12.7)

1/4"(Ø6.35)

7.5

7

15

20

1/2"(Ø12.7)

1/4"(Ø6.35)

7.5

15

30

20

5/8"(Ø15.88)

1/4"(Ø6.35)

7.5

15

30

20

5/8"(Ø15.88)

3/8"(Ø9.52)

7.5

15

30

30

5/8"(Ø15.88)

3/8"(Ø9.52)

7.5

15

30

30

3/4"(Ø19.05)

3/8"(Ø9.52)

7.5

15

30

50

Indoor unit

Outdoor unit

A B

Max. Elevation B (m)

Standard Length (m)

Pipe Size

Capacity (Btu/h)

A Outdoor unit

Indoor unit

Outdoor unit

Oil trap

B

Indoor unit

A

B

If piping length is more than 5m

Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters.

36

2008 Product Data


9. Capacity Coefficient factor

Cooling

Capacity(%)

100 30k

90

80

70

15

Total Pipe Length(m)

30

100 30k

Capacity(%)

Heating

7.5

90

80

70

7.5

15

Total Pipe Length(m)

30

2008 Product Data

37


9. Capacity Coefficient factor Piping length and elevation

HS-C0964DA6 HS-H0964D71 HS-C1264DA3 HS-C1865DB5 HS-C1865DB6 HS-H1264D71 HS-H1865D70 HS-C2665DB1 HS-H2665D70

Max. Elevation B (m)

Max. Length A (m)

Additional Refrigerant (g/m)

Gas

Liquid

Standard Length (m)

3/8"(Ø9.52)

1/4"(Ø6.35)

7.5

7

15

20

1/2"(Ø12.7)

1/4"(Ø6.35)

7.5

7

15

20

5/8"(Ø15.88)

3/8"(Ø9.52)

7.5

15

30

30

Pipe Size

Models

Indoor unit

Outdoor unit

A B

A Outdoor unit

Indoor unit

Outdoor unit

Oil trap

B

Indoor unit

A

B

If piping length is more than 5m

Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters.

38 2008 Product Data


10. Operation Range Without Low Ambient Kit Cooling 46

24 Outdoor Unit [°C DB]

Continuous operation

21 Operative

-5 18

Warming up Operation

Operative

43 Outdoor Unit [°C DB]

Heating

Standard operation

-5

Operative

-10 16

32 Indoor Unit [°C DB]

30 Indoor Unit [°C DB]

Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease

With Low Ambient Kit Heating

Cooling 46

Outdoor Unit [°C DB]

Outdoor Unit [°C DB]

24 Continuous operation

21

-5 18

32 Indoor Unit [°C DB]

If outdoor temperature falls below 0˚C, the cooling capacity and operating characteristics could be different than rated.

Warming up Operation

Operative

43

Standard operation

-5

Operative

-10 16

30 Indoor Unit [°C DB]

Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease

2008 Product Data

39


10. Operation Range Tropical Model only Cooling

Heating

Continuous operation

21

18

32

Indoor Unit [°C DB] • Although low ambient kit is installed, in case outdoor temperature goes below 0°C, the cooling capacity can be dropped and operation characteristics can be slightly different.

40 2008 Product Data

24 Operation Warming up

Outdoor Unit [°C DB]

Outdoor Unit [°C DB]

54

Continuous operation

0

Operative

-5 16

30

Indoor Unit [°C DB] Operative: Intermittent operation according to operation condition (indoor/outdoor temperature, humidity, and load) the heating capacity can be drop


11. Controller Type 1 (Wireless LCD) The controls will look like the following. Signal transmitter

5

1

6

3 4 2 7 11 8 13

10

CANCEL ON

OFF

9 12 17 19 18 14

SET AUTO CLEAN

15

16

Flip-up door (opened)

Operation Mode Operation Mode

Cooling Operation

Auto Operation or Auto Changeover Healthy Dehumidification Operation Heating Operation

• Cooling Model(

), Heat Pump Model(

)

1. START/STOP BUTTON Used to turn off/on the unit. 2. OPERATION MODE SELECTION BUTTON Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4. INDOOR FAN SPEED SELECTOR BUTTON Used to select fan speed in four steps low, medium, high and CHAOS. 5. JET COOL BUTTON Used to start or stop the speed cooling. (It operates fan in super high speed in cooling mode) 6. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction. 7. ON/OFF TIMER BUTTONS Used to set the time of starting and stopping operation. 8. TIME SETTING BUTTONS Used to adjust the time. 9. TIMER SET/CANCEL BUTTON Used to set and to cancel the timer operation. 10. SLEEP MODE AUTO BUTTON Used to set sleep mode auto operation. 11. AIR CIRCULATION BUTTON Used to circulate the room air without cooling or heating. ENERGY-SAVING COOLING MODE BUTTON (OPTIONAL) For inverter type models 12. ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 13. PLASMA BUTTON(OPTIONAL) Used to start or stop the plasma-purification function. 14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL) Used to set the desired horizontal airflow direction. 15. RESET BUTTON Used prior to resetting time. 16. 2nd F BUTTON Used prior to using modes printed in blue at the bottom of buttons. 17. AUTO CLEAN BUTTON(OPTIONAL) Used to set auto clean mode. In some models this button has a 2nd function of LED luminosity control. 18. HEATER BUTTON(OPTIONAL) (Not available in all models) 19. LCD LUMINOSITY BUTTON(OPTIONAL) Used to adjust LCD luminosity.

NOTE To use the functions printed in blue at the bottom of the buttons press 2nd F button first and then the required function button. Pressing the 2nd F button activates the blue printed function of the respective button. To cancel the function press the 2nd F button again else it will automatically cancel if remains idle after 10 seconds.

2008 Product Data

41


11. Controller Type 2 (Wireless LCD)

Signal transmitter

5

6

4

1

7 8 9

ON

OFF

SET

CANCEL

1

START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again.

2

OPERATION MODE SELECTION BUTTON Used to select the operation mode.

3

ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature.

4

INDOOR FAN SPEED SELECTOR Used to select fan speed in four steps low, medium, high and CHAOS.

5

3 10

JET COOL Used to start or stop the speed cooling. (Speed cooling operates super high fan speed in cooling mode.)

6

CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction.

7

ON/OFF TIMER BUTTONS Used to set the time of starting and stopping operation.

8

TIME SETTING BUTTONS Used to adjust the time.

9

TIMER SET/CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation.

10

SLEEP MODE AUTO BUTTON Used to set Sleep Mode Auto operation.

Cooling Operation

11

AIR CIRCULATION BUTTON Used to circulate the room air without cooling or heating.

Auto Operation

12

ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature.

Healthy Dehumidification Operation

13

PLASMA(OPTION) Used to start or stop the plasma-purification function.

Heating Operation

14

HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON ALL MODELS) Used to set the desired horizontal airflow direction.

15

RESET BUTTON Used prior to resetting time or after replacing batteries.

11 12 PLASMA

2

13

14

15

Flip-up door (opened)

Operation Mode

• Cooling Model(

), Heat Pump Model(

42 2008 Product Data

)


11. Controller Type 3. (Wireless Simple) The remote control transmits the signals to the system.

1 TEMP. OFF

TIME

hr.

1

3

4

8

2

7

5

2

OPERATION DISPLAY Displays the operation conditions. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction.

3

OPERATION MODE SELECTION BUTTON Used to select the operation mode.

4

OFF TIMER BUTTON Used to set the time of stopping operation.

5

START/STOP BUTTON Operation starts when this button is pressed, and stops when the button is pressed again.

6

ROOM TEMPERATURE SETTING BUTTONS

6

7 8

INDOOR FAN SPEED SELECTION BUTTON JET COOL Used to start or stop the speed cooling. (Speed cooling operates super high fan speed in cooling mode.)

(1) Operation Mode Cooling Operation

Cooling Operation Healthy Dehumidifacation Operation

Healthy Dehumidifacation Operation

Heating Operation

(Cooling Model)

(Heat pump Model)

(2) Operation PROCEDURE

1st

Start/Stop Button

TEMP. OFF

2nd

Operation Mode Selection Button

3rd

Room Temperature Setting Button

4th

hr.

2

4

Indoor Fan speed Selection Button

TIME

1 3

2008 Product Data

43


11. Controller Type 4. (Wireless Simple) The remote control transmits the signals to the system.

TEMP. OFF

TIME

hr.

1 4

1

OPERATION DISPLAY Displays the operation conditions.

2

CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction.

3

OPERATION MODE SELECTION BUTTON Used to select the operation mode.

3

2

4

OFF TIMER BUTTON Used to set the time of stopping operation.

7

5

5

START/STOP BUTTON Operation starts when this button is pressed, and stops when the button is pressed again.

6

ROOM TEMPERATURE SETTING BUTTONS

7

INDOOR FAN SPEED SELECTION BUTTON

6

(1) Operation Mode Cooling Operation

Cooling Operation Healthy Dehumidifacation Operation

Healthy Dehumidifacation Operation

Heating Operation

(Cooling Model)

(Heat pump Model)

(2) Operation PROCEDURE

1st

Start/Stop Button

TEMP. OFF

2nd

Operation Mode Selection Button

3rd

Room Temperature Setting Button

4th

Indoor Fan speed Selection Button

hr.

2

4

44 2008 Product Data

TIME

1 3


12. Installation Guide at the Seaside

CAUTION 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.

Selecting the location(Outdoor Unit) 1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.

Sea wind

Sea wind

2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak

• It should be strong enough like concrete to prevent the sea wind from the sea. • The height and width should be more than 150% of the outdoor unit.

Sea wind

• It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.

3) Select a well-drained place.  1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water

2008 Product Data

45


P/No.: MFL42689107


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.