Z0011121-VII-B

Page 1

HITACHI AIR-COOLED WATER CHILLERS

– SCREW TYPE – HITACHI Nominal Capacity Range R407C: 181kW to 1,089kW

156,000kcal/h to 936,100kcal/h 52 RT to 310 RT R22: 191kW to 1,146kW 164,230kcal/h to 985,400kcal/h 54RT to 336 RT

Technical Catalog I Design Information Model:

R22 RCU75AHYZ1 RCU100AHYZ1 RCU120AHYZ1 RCU150AHYZ1 RCU180AHYZ1 RCU200AHYZ1 RCU240AHYZ1 RCU270AHYZ1 RCU300AHYZ1 RCU330AHYZ1 RCU350AHYZ1 RCU360AHYZ1 RCU380AHYZ1 RCU400AHYZ1

R407C RCUG75AHYZ1 RCUG100AHYZ1 RCUG120AHYZ1 RCUG150AHYZ1 RCUG180AHYZ1 RCUG200AHYZ1 RCUG240AHYZ1 RCUG270AHYZ1 RCUG300AHYZ1 RCUG330AHYZ1 RCUG350AHYZ1 RCUG360AHYZ1 RCUG380AHYZ1 RCUG400AHYZ1

New Series!HITACHI H Series air-cooled water chillers which achieve to 400HP, are designed for all the conveniences of chilled water air-conditioning systems and modern manufacturing industries,these chillers can operate normally even at 43 of the outdoor air temperature,that is why the chillers can apply for larger temperature range。 HITACHI air-cooled water chillers are equipped with newly-developed HITACHI A type semi-hermetic screw compressors which features are lower noise and vibration, reliable long period operation and used the higher performance air-cooled condenser that result in compact structure。 The units are composed of a compressor(s), a air-cooled condenser(s), a shell-tube type evaporator and auxiliary and control equipment, these parts are equipped in the metal cabinet for avoiding the climate influence,the shell plate is used the galvanize steel with oleoresin paint。


FEATURE

New HITACHI AIR-COOLED WATER CHILLERS… THAT’S THE ACHIEVEMENT OF TOTAL HITACHI TECHNOLOGE… ● Reliable semi-hermetic screw type compressor

Adopting new screw rotor outline , HITACHI have developed the higher performance screw type compressor to improve the operation reliable and durable. In this new century, people pay more attention to the change of the environment… HITACHI semi-hermetic screw type compressor ,which use the R407C directly, reduce the refrigerant leak greatly, and have been sold 140,000 in the world ! Discharge Outlet

1. Efficiency is improved by using the highly precision rotors. 2 . Separating efficiency enhanced greatly by changing the oil separate mode.

Motor for Compressor

Slide Valve

Suction Inlet

Bearing ●Highly Efficiency Operation

To combine highly performance fins in the air side heat exchanger,efficiently screw type compressor and water side heat exchanger together properly can achieve high efficiency operation. Heat-Exchanger(AHYZ1) Air

side

heat-exchanger

used

the

converse M type distribution that the air velocity

distribute

equally

,

highly

efficiency heat exchange is achieved, and improve defrost performance.

1.Improve the air heat exchanger configure. 2.Adopt highly efficiency inner thread tube 3.Improve Air velocity distribution to enhance efficiency and defrost performance

●Smaller Vibration and Lower Operation Sound

Due to the combination of the HITACHI semi-hermetic screw compressors and smooth-air-flow propeller fans for air side heat exchangers, smaller vibration and lower sound operation has been achieved, Therefore, in most cases, special vibration absorbing curbs are not required by utilizing factory-supplied rubber mats.


FEATURE

Capacity Control Continuous Capacity Control Chilled water outlet temperature can be controlled precisely within ±0.5 of the setting temperature. This control is performed by applying a micro-computer to the continuous capacity control type screw compressor. This precise temperature control is not only suitable for air conditioning, but also for industrial Load-up signal When there is a big use. 12sec.

difference between set temperature and actual temperature

60sec.

Load-up signal

Start 2sec.

Inlet water temperature

60sec.

Outlet water temperature

Outlet water temperature

Inlet water temperature

8

Neutral zone standard

6 4

(Set temperature:5℃)

Stop

Stop temperature standard

Lapsed time Load-down signal A given load status is maintained.

2sec.

60sec.

The inlet water temperature is detected at a stop, and it is restarted by a raise in inlet water temperature

-Principle of Continuous Capacity ControlContinuous capacity control is performed by adjusting the slide valve position as shown below. The slide position can be changed freely between 100% and 15% in accordance with cooling load.

Load-up

Pd: Discharge Pressure,

Load-down

Ps: Suction Pressure

Micro-Processor Control for Various Functions Alarm Indication for each cycle by 7-Segment Rotating control of compressor starting order Current limitation control Automatic start after instantaneous power failure Complete Standard Accessory Water connection companion flange Vibration-proof Mat Foundation Bolt, Nut, Washer and Bushing Spreader bar for rigging Noise-proof pan for compressor

Hold

S1,2,3 :Solenoid Valve

Other Option The following specifications are available on order basis. Please contact local Hitachi’s distributors if required. G/W communication adapter or RS485 physics connector. High static pressure fan (Outside static pressure:150Pa) Remote control box Liquid crystal touch panel with big screen HITACHI water chillers group control system

1


GENERAL DATA

General Data(R22 and R407C) Model

Nominal Cooling Capacity *1

R22

Nominal Cooling Capacity *1

R407C

RCU120AHY Z1

RCU150AHY Z1

RCU180AHY Z1

RCU200AHY Z1

RCU240AHY Z1

RCUG120AHY Z1

RCUG150AHY Z1

RCUG180AHY Z1

RCUG200AHY Z1

RCUG240AHY Z1

kW

191

286

358

382

537

573

716

kcal/h

164,230

245,916

307,825

328,461

461,737

492,691

615,649 203.6

RT

54.3

81.3

101.8

108.6

152.7

163.0

kW

181

272

340

363

510

544

680

kcal/h

156,019

233,620

292,433

312,038

438,650

468,057

584866.7

RT

51.6

77.3

96.7

103.2

145.1

154.8

193.4

Continuous Capacity Control

%

100~15,0

mm

2,390

4,490

4,490

4,490

6,590

6,590

9,080(Minimum)

Depth

mm

1,940

1,940

1,940

1,940

1,940

1,940

1,940

Height

mm

2,170

2,170

2,170

2,170

2,170

2,170

2,170

kg

2,057

3,822

4,017

4,103

5,688

5,827

2×4,017

100~15(5)*2,0

100~15(7.5)*2,0

Standard

R22

R407C

R407C

Flow Control

Number of Circuit

Ty pe

Compressor

60ASCC-Z

1

Condenser

Air Discharge Ev aporator

3

2

4

Semi-Hermetic Screw Ty pe

Model

Fan Power Input Motor Quantity

100~15(7.5)*2,0

Thermal Expansion Valv e 1

Quantity Condenser Fan HeatExchanger

RCU100AHY Z1 RCUG100AHY Z1

Width

Net Weight

Ref rigerant

RCU75AHY Z1 RCUG75AHY Z1

Capacity Control

Outer Dimension

R22 R407C

50ASCC-Z

60ASCC-Z

60ASCC-Z

60ASCC-Z

2

60ASCC-Z 3

60ASCC-Z 4

Cross Fin Ty pe Direct driv e Propeller Fan

─ kW

1.1

1.1

1.1

1.1

1.1

1.1

1.1

4

8

8

8

12

12

2×8

m 3/min

930

1,860

1,860

1,860

2,790

2,790

3,720

Shell and Tube Ty pe

Saf ety Dev ices

Ov ercurrent Relay f or Compressor , Internal Thermostat f or Compressor, Rev erse Phase Protection Dev ice f or Compressor,Thermal Ov ercurrent Relay f or Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse f or Control Circuit and Pressure Relief Valv e

Piping Connections f or Water-Side Heat Exchanger(In/Outlet)

With φ90 Inner Diameter Companion Flange

Main Power (square orif ice)

mm

Circuit

mm

2×φ64.5;φ102; φ 52

Connection Hole

2×500×200

500×200 3×φ64.5;φ102;φ52

4×φ64.5;φ102;φ52

6×φ64.5;2×φ102;2 ×φ52

*3

kg

2,524

4,442

4,635

4,745

6,813

6,956

2×4,635

Width

mm

2,600

4,700

4,700

4,700

6,800

6,800

2×4,700

Depth

mm

2,190

2,190

2,190

2,190

2,190

2,190

2,190

Height

mm

2,510

2,510

2,510

2,510

2,510

2,510

2,510

Shipping Weight Shipping Dimension

With φ142 Inner Diameter Companion Flange

NOTE: 1. The nominal cooling capacities are based on GB/T 18430.1-2001(*1) Chilled Water Inlet/Outlet Temperature:12/7℃ Condensate Air Inlet Temperature:35℃(DB) 2. Applicable Power Supply Main Power Source(AC3φ) 380V,50HZ Control Power Source(AC1φ)220V,50HZ 3.The units greater than 240AHYZ1 including 240AHYZ1 consist of two modules and are separately shipped.(*3).

The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.

4. Water Flow 1) RCU(G)240,300,360,400AHYZ1 It is necessary to control the same water quantity to each cooler. 2) RCU(G)270,330,350,380AHYZ1 The chilled water flow rate is different between No.1 & No.2 units. It is necessary to control the water quantity of each unit with adjusting valves(Filed-Supplied). 5. It is required to connect electrical control wires between No.1 and No.2 units for the unit greater than 240AHYZ1including 240AHYZ1. 6. ( ) marked with *2 is available by selection switch.

Working Range

Standard 5~15℃ 5~43℃

I t em Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB)

2


GENERAL DATA

General Data(R22 and R407C) Model

Nominal Cooling Capacity*1

R22

Nominal Cooling Capacity*1

R407C

RCU330AHYZ1

RCU350AHYZ1

RCU380AHYZ1

RCU400AHYZ1

RCUG330AHYZ1

RCUG350AHYZ1 RCUG360AHYZ1 RCUG380AHYZ1

RCUG400AHYZ1

RCU360AHYZ1

kW

740

764

919

955

1,074

1,110

1,146

kcal/h

636,285

656,922

790,198

821,152

923,474

954,428

985,383 325.9

RT

210.5

217.3

261.4

271.6

305.5

315.7

kW

703

726

873

907

1,020

1,055

1,089

kcal/h

604,471

624,076

750,688

780,095

877,300

906,707

936,113

RT

199.9

206.4

248.2

258.0

290.1

299.8

309.6

Continuous Capacity Control

%

100~15(7.5)*2,0

100~15(6)*2,0

100~15(7.5)*2,0

mm

9,080(Minimum)

9,080(Minimum)

11,180(Minimum)

Depth

mm

1,940

1,940

1,940

1,940

1,940

1,940

Height

mm

2,170

2,170

2,170

2,170

2,170

2,170

2,170

kg

4,103+4,017

2×4,103

5,688+4,103

5,827+4,103

2×5,688

5,827+5,688

2×5,827

11,180(Minimum) 13,280(Minimum) 13,280(Minimum)

Standard

R22

R407C

R407C

Flow Control

Number of Circuit

Type

Model

Quantity

Compressor

HeatExchanger

RCU300AHYZ1 RCUG300AHYZ1

Width

Net Weight

Refrigerant

RCU270AHYZ1 RCUG270AHYZ1

Capacity Control

Outer Dimension

R22 R407C

Condenser Condenser Fan Power Input Fan Motor Quantity Air Discharge

13,280(Minimum) 1,940

Thermal Expansion Valve 4

6

5 Semi-Hermetic Screw Type

60ASCC-Z

60ASCC-Z

60ASCC-Z

4

60ASCC-Z

60ASCC-Z

5

60ASCC-Z

60ASCC-Z

6

Cross Fin Type

Direct Drive Propeller Fan

kW

1.1

1.1

1.1

1.1

1.1

1.1

1.1

8+8

2×8

12+8

12+8

2×12

12+12

2×12

m3/min

3,720

3,720

4,650

4,650

5,580

5,580

5,580

Shell and Tube Type

Safety Devices

Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve

Piping Connections for Water-Side Heat Exchanger(In/Outlet)

With φ142 Inner Diameter Companion Flange

Main Power (square orifice)

mm

2×500×200

Circuit

mm

2×φ102 2×φ52 6×φ64.5; ;

kg

4,745+4,635

2×4,745

6,813+4,745

6,956+4,745

2×6,813

6,956+6,813

2×6,956

Width

mm

2×4,700

2×4,700

6,800+4,700

6,800+4,700

2×6,800

2×6,800

2×6,800

Depth Height

mm mm

2,190 2,510

2,190 2,510

2,190 2,510

2,190 2,510

2,190 2,510

2,190 2,510

2190 2,510

Evaporator

Connection Hole

Shipping Weight*3 Shipping Dimension

NOTE: 1. The nominal cooling capacities are based on GB/T 18430.1-2001(*1) Chilled Water Inlet/Outlet Temperature:12/7℃ Condensate Air Inlet Temperature:35℃(DB) 2. Applicable Power Supply Main Power Source(AC3φ) 380V,50HZ Control Power Source(AC1φ)220V,50HZ 3.The units greater than 240AHYZ1 including 240AHYZ1 consist of two modules and are separately shipped.(*3). The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.

7×φ64.5;2×φ102;2×φ52

8×φ64.5;2×φ102;2×φ52

4. Water Flow 1) RCU(G)240,300,360,400AHYZ1 It is necessary to control the same water quantity to each cooler. 2) RCU(G)270,330,350,380AHYZ1 The chilled water flow rate is different between No.1 & No.2 units. It is necessary to control the water quantity of each unit with adjusting valves (Filed-Supplied) . 5. It is required to connect electrical control wires between No.1 and No.2 units for the unit greater than 240AHYZ1including 240AHYZ1. 6. ( ) marked with *2 is available by selection switch.

Working Range

Item Chilled Water Outlet Temperature Condenser Air Inlet Temperature(DB) 3

Standard 5~15℃ 5~43℃


DIMENSION DATA

Unit Dimensions RCU(G)75AHYZ1

RCU(G)100AHYZ1, RCU(G)120AHYZ1 and RCU(G)150AHYZ1

4


DIMENSION DATA

Unit Dimensions RCU(G)180AHYZ1 and RCU(G)200AHYZ1

RCU(G)240AHYZ1、RCU(G)270AHYZ1 and RCU(G)300AHYZ1

5


DIMENSION DATA

Unit Dimensions RCU(G)330AHYZ1 and RCU(G)350AHYZ1

RCU(G)360AHYZ1, RCU(G)380AHYZ1 and RCU(G)400AHYZ1

6


PREPARATION

Operation Space h1≤h2

h1≤h2 For Models: RCU(G)240AHYZ1,RCU(G)270AHYZ1, RCU(G)300AHYZ1, RCU(G)330AHYZ1, RCU(G)350AHYZ1, RCU(G)360AHYZ1, RCU(G)380AHYZ1,RCU(G)400AHYZ1

For Models: RCU(G)75AHYZ1, RCU(G)100AHYZ1, RCU(G)120AHYZ1,RCU(G)150AHYZ1, RCU(G)180AHYZ1,RCU(G)200AHYZ1.

Maximum Foundation Gradient Refer to C,D E

Refer to C,D F 30mmm

Refer to C,D 15mm

G

Model

Maintain Space (mm)

Air Inlet Space (mm)

A

B

C

D

E

F

G

RCU(G)75AHYZ1

2,100

1,200

100

900

1,200

2,000

1,200

RCU(G)100AHYZ1

4,200

1,200

100

900

1,200

2,000

1,200

RCU(G)120AHYZ1

4,200

1,200

100

900

1,200

2,000

1,200

RCU(G)150AHYZ1

4,200

1,200

100

900

1,200

2,000

1,200

RCU(G)180AHYZ1

6,300

1,200

100

900

1,200

2,000

1,200

RCU(G)200AHYZ1

6,300

1,200

100

900

1,200

2,000

1,200

RCU(G)240AHYZ1

9,300(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)270AHYZ1

9,300(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)300AHYZ1

9,300(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)330AHYZ1

11,400(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)350AHYZ1

11,400(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)360AHYZ1

13,500(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)380AHYZ1

13,500(Minimum)

1,200

900

900

1,200

2,000

1,200

RCU(G)400AHYZ1

13,500 (Minimum

1,200

900

900

1,200

2,000

1,200

7


PREPARATION

Center of Gravity Model RCU(G)75AHYZ1 RCU(G)100AHYZ1 RCU(G)120AHYZ1 RCU(G)150AHYZ1 RCU(G)180AHYZ1 RCU(G)200AHYZ1 RCU(G)240AHYZ1-1,2 RCU(G)270AHYZ1-1 RCU(G)270AHYZ1-2 RCU(G)300AHYZ1-1,2 RCU(G)330AHYZ-1 RCU(G)330AHYZ-2 RCU(G)350AHYZ-1 RCU(G)350AHYZ-2 RCU(G)360AHYZ-1,2 RCU(G)380AHYZ-1 RCU(G)380AHYZ-2 RCU(G)400AHYZ-1,2

Center of Gravity X 975 2,035 2,055 2,065 3,550 3,570 2,055 2,065 2,055 2,065 3,570 2,065 3,570 2,065 3,550 3,570 3,550 3,570

Operation Weight(kg)

Y 830 805 805 835 805 835 805 835 805 835 835 835 835 835 805 835 805 835

2,332 4,112 4,312 4,403 6,006 6,152 4,312 4,403 4,312 4,403 6,006 4,403 6,152 4,403 6,006 6,152 6,006 6,152

Weight Balance Model RCU(G)75AHYZ1

Model RCU(G)100AHYZ1 RCU(G)120AHYZ1 RCU(G)150AHYZ1 RCU(G)240AHYZ1-1,2 RCU(G)270AHYZ1-1 RCU(G)270AHYZ1-2 RCU(G)300AHYZ1-1

Model RCU(G)180AHYZ1 RCU(G)200AHYZ1 RCU(G)330AHYZ1-1 RCU(G)330AHYZ1-2 RCU(G)350AHYZ1-1 RCU(G)350AHYZ1-2 RCU(G)360AHYZ1-1,2 RCU(G)380AHYZ1-1 RCU(G)380AHYZ1-2 RCU(G)400AHYZ1-1,2

Weight Destribution (kg) 1 563

2 508

3 662

4 601

1 655 651 688 651 688 651 688

Weight Destribution (kg) 2 3 4 5 610 590 756 756 643 628 817 799 665 651 807 800 643 628 817 799 665 651 807 800 643 628 817 799 665 651 807 800

1 654 688 654 688 688 688 654 688 654 688

2 671 696 671 665 696 665 671 696 671 696

6 745 776 794 776 794 776 794

Weight Destribution (kg) 3 4 5 6 674 671 825 836 707 696 842 850 674 671 825 836 651 807 800 794 707 696 842 850 651 807 800 794 674 671 825 836 707 696 842 850 674 671 825 836 707 696 842 850

8

7 840 837 840

8 833 834 833

837

834

840 837 840 837

833 834 833 834


SELECTION DATA

Selection Example Determination the System Requirements: Condenser Air Inlet Temperature: 40 Chilled Water Outlet Temperature 7 Chilled Water Inlet Temperature 12 Cooling Load 453kW Power Source Frequency: 50Hz

Cooling Capacity and Compressor Input When the fouling factor is different -4

2

0.86×10 m . /w,

the

cooling

capacity

from

or

compressor input will be corrected utilizing follow formulas:

Corrected Cooling

From the cooling capacity table, model RCU180AHYZ1 can be selected with the following performance: Cooling Capacity: 511kW Chilled Water Flow Rate: 87.1m3/h Water Cooler Pressure Drop: 31.3kPa Compressor Input Power: 184.6kW

Corrected

The water flow rate in the cooling capacity table is

Compressor

based on the 5

Input

Capacity

Correction = Factor ×

Cooling

Capacity

Indicated in Table

and

temperature difference between

Correction = Factor

Compressor

Input

× indicated in Table

the chilled water inlet and outlet temperature, if the

Correction

temperature difference is not

Compressor Input Regarding Fouling Factor

5

the

, correct the

Factor

for

Cooling

Capacity

water flow rater of the water cooler utilizing follow formulas. Flow Rate Corrected Flow = Rate

5

× From the Table (CFR)

Fouling

Cooling

Compressor

Factor

Capacity

Input

2

m.

Given Temperature

Water

Difference ( )

Cooler

/W

0(0) 0.86×10

-4

1.02

1.00

1.00

1.00

0.0001m2h /kcal=0.086m2 /kW

The corrected chilled water flow rate must be confirmed to be within the working range described on pages 17

Flow Rate (m3/h) NOTE: The flow rate of each model is not different, please refer the chilled water flow rate to the page 17 in TCI. 9

and


SELECTION DATA

Cooling Capacities(R22) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq

-50HzABT

25

30

35

40

ABT

25

30

35

40

CLOT

RCU75AHYZ1

RCU100AHYZ1

RCU120AHYZ1

RCU150AHYZ1

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

CCAP

CFR

5

198.5

34.1

42.2

44.0

297.3

51.1

55.7

66.3

372.1

64.0

66.2

82.6

397.0

68.3

CPD 75.6

88.0

IPT

6

205.3

35.3

44.8

44.4

307.3

52.9

59.3

66.9

384.8

66.2

70.9

83.4

410.6

70.6

81.0

88.7

7

212.0

36.5

47.4

44.8

317.5

54.6

62.9

67.4

397.4

68.3

75.7

84.1

424.0

72.9

86.5

89.5

8

218.7

37.6

50.1

45.1

327.5

56.3

66.6

68.0

409.9

70.5

80.7

84.9

437.4

75.2

92.2

90.3

9

225.3

38.7

52.8

45.5

337.4

58.0

70.4

68.7

422.2

72.6

85.8

85.6

450.6

77.5

98.1

91.0

10

231.8

39.9

55.5

46.0

347.1

59.7

74.1

69.3

434.4

74.7

90.9

86.4

463.6

79.7

104.0

92.0

5

188.5

32.4

38.5

49.4

282.2

48.5

50.6

74.7

353.3

60.8

59.5

93.0

377.0

64.8

68.0

98.8

6

195.0

33.5

40.9

49.9

292.0

50.2

53.9

75.3

365.5

62.9

63.8

93.8

390.0

67.1

72.9

99.8

7

201.5

34.7

43.3

50.3

301.7

51.9

57.3

76.0

377.7

65.0

68.2

94.5

403.0

69.3

77.9

100.6

8

208.0

35.8

45.8

50.8

311.4

53.6

60.7

76.7

389.8

67.0

72.8

95.4

416.0

71.5

83.2

101.5

9

214.3

36.9

48.3

51.1

320.9

55.2

64.2

77.4

401.7

69.1

77.4

96.2

428.6

73.7

88.5

102.3

10

220.6

37.9

50.8

51.6

330.3

56.8

67.7

78.1

413.4

71.1

82.2

97.0

441.2

75.9

93.9

103.2

5

178.4

30.7

34.9

54.8

267.2

46.0

45.8

83.1

334.5

57.5

53.1

103.3

356.8

61.4

60.7

109.7

6

184.7

31.8

37.1

55.3

276.6

47.6

48.8

83.9

346.2

59.5

57.0

104.1

369.4

63.5

65.2

110.6

7

191.0

32.8

39.4

55.8

286.0

49.2

51.9

84.6

358.0

61.6

61.1

105.0

382.0

65.7

69.8

111.6

8

197.2

33.9

41.7

56.3

295.4

50.8

55.1

85.3

369.7

63.6

65.3

105.9

394.4

67.8

74.6

112.6

9

203.4

35.0

44.0

56.8

304.6

52.4

58.3

86.1

381.2

65.6

69.5

106.7

406.8

70.0

79.5

113.5

10

209.4

36.0

46.4

57.1

313.6

53.9

61.5

86.7

392.6

67.5

73.9

107.6

418.8

72.0

84.4

114.3

5

168.4

29.0

31.6

60.4

252.1

43.4

41.1

91.6

315.6

54.3

47.1

113.6

336.8

57.9

53.9

120.7

6

174.4

30.0

33.6

60.8

261.2

44.9

43.9

92.4

327.0

56.2

50.7

114.5

348.8

60.0

57.9

121.7

7

180.5

31.0

35.7

61.3

270.3

46.5

46.8

93.2

338.4

58.2

54.4

115.5

361.0

62.1

62.2

122.6

8

186.5

32.1

37.8

61.8

279.3

48.0

49.7

94.0

349.6

60.1

58.2

116.3

373.0

64.1

66.5

123.6

9

192.5

33.1

40.0

62.3

288.1

49.6

52.6

94.7

360.7

62.0

62.1

117.3

385.0

66.2

71.0

124.6

10

198.3

34.1

42.1

62.8

296.9

51.1

55.6

95.5

371.7

63.9

66.0

118.3

396.6

68.2

75.4

125.5

CLOT

RCU180AHYZ1

RCU200AHYZ1

RCU240AHYZ1

RCU270AHYZ1

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

CCAP

CFR1,2

CPD1,2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

5

558.2

96.0

83.6

123.9

595.5

102.4

94.7

132.0

744.2

64.0

66.2

165.2

769.1

68.3

64.0

75.6

66.2

170.6

6

577.2

99.3

89.2

125.1

615.9

105.9

101.1

133.1

769.6

66.2

70.9

166.8

795.4

70.6

66.2

81.0

70.9

172.1

7

596.1

102.5

94.9

126.1

636.0

109.4

107.5

134.3

794.8

68.3

75.7

168.2

821.4

72.9

68.3

86.5

75.7

173.6

8

614.8

105.7

100.7

127.3

656.1

112.8

114.1

135.4

819.7

70.5

80.7

169.7

847.3

75.2

70.5

92.2

80.7

175.1

9

633.3

108.9

106.6

128.4

675.9

116.2

120.8

136.5

844.4

72.6

85.8

171.3

872.8

77.5

72.6

98.1

85.8

176.7

10

651.6

112.0

112.6

129.6

695.4

119.6

127.6

138.0

868.7

74.7

90.9

172.8

898.0

79.7

74.7

104.0

90.9

178.4

5

530.0

91.1

75.7

139.5

565.5

97.2

85.8

148.3

706.7

60.8

59.5

186.0

730.3

64.8

60.8

68.0

59.5

191.8

6

548.2

94.3

80.8

140.6

585.0

100.6

91.5

149.7

731.0

62.9

63.8

187.5

755.5

67.1

62.9

72.9

63.8

193.6

7

566.6

97.4

86.1

141.8

604.5

104.0

97.5

150.8

755.5

65.0

68.2

189.1

780.7

69.3

65.0

77.9

68.2

195.1

8

584.7

100.5

91.4

143.1

624.0

107.3

103.6

152.3

779.6

67.0

72.8

190.8

805.8

71.5

67.0

83.2

72.8

196.9

9

602.6

103.6

96.9

144.3

642.9

110.6

109.8

153.4

803.4

69.1

77.4

192.4

830.3

73.7

69.1

88.5

77.4

198.5

10

620.2

106.6

102.4

145.4

661.8

113.8

116.0

154.8

826.9

71.1

82.2

193.9

854.6

75.9

71.1

93.9

82.2

200.2

5

501.7

86.3

68.1

154.9

535.2

92.0

77.1

164.5

668.9

57.5

53.1

206.5

691.3

61.4

57.5

60.7

53.1

213.0

6

519.3

89.3

72.8

156.2

554.1

95.3

82.5

166.0

692.4

59.5

57.0

208.3

715.6

63.5

59.5

65.2

57.0

214.8

7

537.0

92.3

77.6

157.5

573.0

98.5

88.0

167.4

716.0

61.6

61.1

210.0

740.0

65.7

61.6

69.8

61.1

216.6

8

554.6

95.4

82.6

158.8

591.6

101.7

93.5

168.8

739.4

63.6

65.3

211.7

764.1

67.8

63.6

74.6

65.3

218.4

9

571.8

98.3

87.6

160.1

610.2

104.9

99.3

170.3

762.4

65.6

69.5

213.5

788.0

70.0

65.6

79.5

69.5

220.2

10

588.9

101.3

92.7

161.4

628.2

108.0

105.0

171.4

785.2

67.5

73.9

215.2

811.4

72.0

67.5

84.4

73.9

221.9

5

473.4

81.4

60.9

170.4

505.2

86.9

69.0

181.1

631.2

54.3

47.1

227.2

652.4

57.9

54.3

53.9

47.1

234.4

6

490.5

84.3

65.2

171.7

523.2

90.0

73.9

182.5

653.9

56.2

50.7

229.0

675.8

60.0

56.2

57.9

50.7

236.2

7

507.5

87.3

69.7

173.2

541.5

93.1

78.9

184.0

676.7

58.2

54.4

230.9

699.4

62.1

58.2

62.2

54.4

238.1

8

524.5

90.2

74.2

174.5

559.5

96.2

84.0

185.4

699.3

60.1

58.2

232.7

722.6

64.1

60.1

66.5

58.2

239.9

9

541.1

93.0

78.8

176.0

577.5

99.3

89.3

186.8

721.4

62.0

62.1

234.6

745.7

66.2

62.0

71.0

62.1

241.9

10

557.5

95.9

83.4

177.4

594.9

102.3

94.5

188.3

743.3

63.9

66.0

236.5

768.3

68.2

63.9

75.4

66.0

243.8

ABT:Condensate Air Inlet Temperature(℃)

CLOT:Chilled Water Outlet Temperature(℃)

CCAP:Cooling Capacity(kW)

CFR:Chilled Water Flow Rate at 5℃ Difference Between Inlet and Outlet Temperature(m3/h)

CPD:Water Cooler Pressure Drop(kPa)

IPT:Input Power(kW)

10


SELECTION DATA

Cooling Capacities(R22) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq

-50HzABT

25

30

35

40

ABT

25

30

35

40

CLOT

RCU300AHYZ1

RCU330AHYZ1

RCU350AHYZ1

CCAP

CFR1,2

CPD1,2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

5

794.0

68.3

75.6

176.0

955.2

93.3

68.3

83.5

75.6

211.9

992.5

102.3

68.3

94.7

75.6

220.0

6

821.2

70.6

81.0

177.5

987.8

96.5

70.6

89.1

81.0

213.8

1026.5

105.7

70.6

101.1

81.0

221.9

7

848.0

72.9

86.5

179.0

1020.1

99.6

72.9

94.8

86.5

215.6

1060.0

109.2

72.9

107.5

86.5

223.8

8

874.8

75.2

92.2

180.5

1052.2

102.8

75.2

100.7

92.2

217.5

1093.5

112.6

75.2

114.1

92.2

225.7

9

901.2

77.5

98.1

182.1

1083.9

105.9

77.5

106.6

98.1

219.5

1126.5

116.0

77.5

120.8

98.1

227.6

10

927.2

79.7

104.0

184.0

1115.2

108.9

79.7

112.6

104.0

221.6

1159.0

119.4

79.7

127.6

104.0

230.0

5

754.0

64.8

68.0

197.7

907.0

88.6

64.8

75.6

68.0

238.3

942.5

97.1

64.8

85.8

68.0

247.1

6

780.0

67.1

72.9

199.6

938.2

91.6

67.1

80.7

72.9

240.4

975.0

100.4

67.1

91.5

72.9

249.5

7

806.0

69.3

77.9

201.1

969.6

94.7

69.3

86.0

77.9

242.4

1007.5

103.8

69.3

97.5

77.9

251.4

8

832.0

71.5

83.2

203.0

1000.7

97.7

71.5

91.4

83.2

244.6

1040.0

107.1

71.5

103.6

83.2

253.8

9

857.2

73.7

88.5

204.5

1031.2

100.7

73.7

96.8

88.5

246.5

1071.5

110.4

73.7

109.8

88.5

255.7

10

882.4

75.9

93.9

206.4

1061.4

103.7

75.9

102.4

93.9

248.7

1103.0

113.6

75.9

116.0

93.9

258.1

5

713.6

61.4

60.7

219.4

858.5

83.9

61.4

68.0

60.7

264.6

892.0

91.9

61.4

77.1

60.7

274.2

6

738.8

63.5

65.2

221.3

888.7

86.8

63.5

72.6

65.2

266.8

923.5

95.1

63.5

82.5

65.2

276.6

7

764.0

65.7

69.8

223.2

919.0

89.8

65.7

77.5

69.8

269.1

955.0

98.4

65.7

88.0

69.8

279.0

8

788.8

67.8

74.6

225.1

949.0

92.7

67.8

82.5

74.6

271.4

986.0

101.6

67.8

93.5

74.6

281.4

9

813.6

70.0

79.5

227.0

978.6

95.6

70.0

87.5

79.5

273.6

1017.0

104.8

70.0

99.3

79.5

283.8

10

837.6

72.0

84.4

228.5

1007.7

98.4

72.0

92.6

84.4

275.7

1047.0

107.9

72.0

105.0

84.4

285.7

5

673.6

57.9

53.9

241.5

810.2

79.1

57.9

60.7

53.9

291.2

842.0

86.7

57.9

69.0

53.9

301.9

6

697.6

60.0

57.9

243.4

839.3

82.0

60.0

65.0

57.9

293.4

872.0

89.8

60.0

73.9

57.9

304.2

7

722.0

62.1

62.2

245.3

868.5

84.8

62.1

69.5

62.2

295.8

902.5

93.0

62.1

78.9

62.2

306.6

8

746.0

64.1

66.5

247.2

897.5

87.7

64.1

74.0

66.5

298.1

932.5

96.0

64.1

84.0

66.5

309.0

9

770.0

66.2

71.0

249.1

926.1

90.4

66.2

78.6

71.0

300.5

962.5

99.1

66.2

89.3

71.0

311.4

10

793.2

68.2

75.4

251.0

954.1

93.2

68.2

83.3

75.4

302.9

991.5

102.1

68.2

94.5

75.4

313.8

CCAP

CFR1,2

CPD1,2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

CCAP

CFR1,2

CPD1,2

IPT

5

1116.3

96.0

83.5

247.9

1153.7

102.3

93.3

94.7

83.5

255.9

1191.0

102.4

94.7

264.0

6

1154.4

99.3

89.1

250.2

1193.1

105.7

96.5

101.1

89.1

258.2

1231.8

105.9

101.1

266.2

7

1192.1

102.5

94.8

252.2

1232.1

109.2

99.6

107.5

94.8

260.4

1272.0

109.4

107.5

268.5

8

1229.6

105.7

100.7

254.6

1270.9

112.6

102.8

114.1

100.7

262.7

1312.2

112.8

114.1

270.8

CLOT

RCU360AHYZ1

RCU380AHYZ1

RCU400AHYZ1

9

1266.7

108.9

106.6

256.9

1309.2

116.0

105.9

120.8

106.6

265.0

1351.8

116.2

120.8

273.1

10

1303.1

112.0

112.6

259.2

1347.0

119.4

108.9

127.6

112.6

267.6

1390.8

119.6

127.6

276.0

5

1060.0

91.1

75.6

279.0

1095.5

97.1

88.6

85.8

75.6

287.7

1131.0

97.2

85.8

296.5

6

1096.5

94.3

80.7

281.3

1133.2

100.4

91.6

91.5

80.7

290.3

1170.0

100.6

91.5

299.4

7

1133.2

97.4

86.0

283.6

1171.1

103.8

94.7

97.5

86.0

292.6

1209.0

104.0

97.5

301.7

8

1169.4

100.5

91.4

286.2

1208.7

107.1

97.7

103.6

91.4

295.4

1248.0

107.3

103.6

304.5

9

1205.2

103.6

96.8

288.6

1245.5

110.4

100.7

109.8

96.8

297.7

1285.8

110.6

109.8

306.8

10

1240.3

106.6

102.4

290.9

1282.0

113.6

103.7

116.0

102.4

300.3

1323.6

113.8

116.0

309.7

5

1003.4

86.3

68.0

309.8

1036.9

91.9

83.9

77.1

68.0

319.4

1070.4

92.0

77.1

329.1

6

1038.5

89.3

72.6

312.4

1073.4

95.1

86.8

82.5

72.6

322.2

1108.2

95.3

82.5

331.9

7

1074.0

92.3

77.5

315.0

1110.0

98.4

89.8

88.0

77.5

324.9

1146.0

98.5

88.0

334.8

8

1109.1

95.4

82.5

317.6

1146.2

101.6

92.7

93.5

82.5

327.6

1183.2

101.7

93.5

337.7

9

1143.6

98.3

87.5

320.2

1182.0

104.8

95.6

99.3

87.5

330.4

1220.4

104.9

99.3

340.5

10

1177.8

101.3

92.6

322.8

1217.1

107.9

98.4

105.0

92.6

332.8

1256.4

108.0

105.0

342.8

5

946.7

81.4

60.7

340.9

978.6

86.7

79.1

69.0

60.7

351.5

1010.4

86.9

69.0

362.2

6

980.9

84.3

65.0

343.5

1013.7

89.8

82.0

73.9

65.0

354.3

1046.4

90.0

73.9

365.1

7

1015.1

87.3

69.5

346.4

1049.0

93.0

84.8

78.9

69.5

357.2

1083.0

93.1

78.9

367.9

8

1048.9

90.2

74.0

349.0

1084.0

96.0

87.7

84.0

74.0

359.9

1119.0

96.2

84.0

370.8

9

1082.1

93.0

78.6

351.9

1118.6

99.1

90.4

89.3

78.6

362.8

1155.0

99.3

89.3

373.7

10

1115.0

95.9

83.3

354.8

1152.4

102.1

93.2

94.5

83.3

365.7

1189.8

102.3

94.5

376.5

ABT:Condensate Air Inlet Temperature( )

CLOT:Chilled Water Outlet Temperature( )

CCAP:Cooling Capacity(kW)

CFR:Chilled Water Flow Rate at 5

CPD:Water Cooler Pressure Drop(kPa)

IPT:Input Power(kW)

11

Difference Between Inlet and Outlet Temperature(m3/h)


SECTION DATA

Cooling Capacities (R407C) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq

-50HzABT

25

30

35

40

ABT

25

30

35

40

CLOT

RCUG75AHYZ1

RCUG100AHYZ1

RCUG120AHYZ1

RCUG150AHYZ1

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

5

188.6

32.4

38.5

47.1

282.5

48.6

50.7

70.9

353.4

60.8

59.5

88.4

377.2

64.9

68.0

94.1

6

195.0

33.5

40.9

47.5

292.0

50.2

53.9

71.5

365.4

62.8

63.7

89.2

390.1

67.1

72.9

95.0

7

201.4

34.6

43.3

47.9

301.6

51.9

57.2

72.2

377.4

64.9

68.1

90.0

402.8

69.3

77.9

95.8

8

207.8

35.7

45.7

48.3

311.1

53.5

60.6

72.8

389.2

66.9

72.6

90.8

415.5

71.5

83.0

96.6

9

214.0

36.8

48.2

48.7

320.5

55.1

64.0

73.5

401.0

69.0

77.2

91.6

428.1

73.6

88.2

97.4

10

220.2

37.9

50.7

49.2

329.7

56.7

67.4

74.1

412.5

70.9

81.8

92.5

440.4

75.7

93.6

98.4

5

179.1

30.8

35.2

52.9

268.1

46.1

46.1

79.9

335.6

57.7

53.5

99.5

358.2

61.6

61.2

105.8

6

185.3

31.9

37.3

53.4

277.4

47.7

49.1

80.6

347.1

59.7

57.3

100.3

370.5

63.7

65.6

106.8

7

191.4

32.9

39.6

53.8

286.6

49.3

52.1

81.3

358.8

61.7

61.4

101.2

382.9

65.8

70.1

107.6

8

197.6

34.0

41.8

54.3

295.9

50.9

55.2

82.1

370.2

63.7

65.5

102.1

395.2

68.0

74.9

108.6

9

203.6

35.0

44.1

54.7

304.9

52.4

58.4

82.8

381.5

65.6

69.6

102.9

407.2

70.0

79.6

109.4

10

209.6

36.0

46.4

55.2

313.8

54.0

61.6

83.5

392.6

67.5

73.9

103.7

419.1

72.1

84.5

110.4

5

169.5

29.1

31.9

58.7

253.8

43.7

41.7

89.0

317.6

54.6

47.8

110.5

339.0

58.3

54.6

117.4

6

175.5

30.2

33.9

59.2

262.8

45.2

44.4

89.8

328.8

56.5

51.3

111.4

350.9

60.3

58.7

118.4

7

181.5

31.2

36.0

59.7

271.7

46.7

47.2

90.5

340.0

58.5

55.0

112.4

362.9

62.4

62.8

119.4

8

187.3

32.2

38.1

60.2

280.6

48.3

50.1

91.3

351.1

60.4

58.7

113.3

374.7

64.4

67.1

120.4

9

193.2

33.2

40.2

60.7

289.4

49.8

53.0

92.1

362.0

62.3

62.5

114.2

386.5

66.5

71.5

121.4

10

198.9

34.2

42.3

61.1

297.9

51.2

55.9

92.8

372.9

64.1

66.4

115.1

397.9

68.4

75.9

122.3

5

160.0

27.5

28.8

64.6

239.5

41.2

37.4

98.0

299.7

51.5

42.4

121.6

320.0

55.0

48.5

129.2

6

165.7

28.5

30.7

65.1

248.1

42.7

39.9

98.9

310.5

53.4

45.6

122.5

331.4

57.0

52.1

130.2

7

171.5

29.5

32.6

65.6

256.8

44.2

42.5

99.7

321.4

55.3

48.9

123.5

343.0

59.0

55.9

131.2

8

177.2

30.5

34.5

66.1

265.3

45.6

45.2

100.5

332.1

57.1

52.4

124.5

354.4

60.9

59.8

132.2

9

182.9

31.4

36.5

66.6

273.7

47.1

47.9

101.4

342.6

58.9

55.8

125.5

365.8

62.9

63.9

133.3

10

188.4

32.4

38.5

67.1

282.1

48.5

50.6

102.2

353.0

60.7

59.4

126.5

376.8

64.8

67.9

134.3

CLOT

RCUG180AHYZ1

RCUG200AHYZ1

RCUG240AHYZ1

RCUG270AHYZ1

CCAP

CFR

CPD

IPT

CCAP

CFR

CPD

IPT

CCAP

CFR1,2

CPD1,2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

5

530.1

91.2

75.7

132.6

565.7

97.3

85.8

141.2

706.8

60.8

59.5

176.8

730.5

64.9

59.1

68.0

59.5

182.6

6

548.2

94.3

80.8

133.9

585.1

100.6

91.6

142.4

730.9

62.8

63.7

178.5

755.5

67.1

61.1

72.9

63.7

184.2

7

566.1

97.4

85.9

134.9

604.2

103.9

97.4

143.7

754.8

64.9

68.1

179.9

780.2

69.3

63.1

77.9

68.1

185.7

8

583.9

100.4

91.2

136.2

623.3

107.2

103.4

144.9

778.5

66.9

72.6

181.6

804.8

71.5

65.1

83.0

72.6

187.4

9

601.5

103.4

96.6

137.4

642.1

110.4

109.5

146.1

802.0

69.0

77.2

183.2

829.1

73.6

67.1

88.2

77.2

189.0

10

618.8

106.4

102.0

138.7

660.6

113.6

115.6

147.6

825.1

70.9

81.8

184.9

853.0

75.7

69.0

93.6

81.8

190.9

5

503.4

86.6

68.6

149.2

537.2

92.4

77.7

158.6

671.1

57.7

53.5

199.0

693.7

61.6

56.1

61.2

53.5

205.3

6

520.7

89.5

73.2

150.5

555.8

95.6

82.9

160.2

694.2

59.7

57.3

200.7

717.6

63.7

58.0

65.6

57.3

207.1

7

538.1

92.5

78.0

151.7

574.3

98.8

88.3

161.4

717.5

61.7

61.4

202.3

741.6

65.8

60.0

70.1

61.4

208.7

8

555.3

95.5

82.8

153.1

592.8

101.9

93.9

162.9

740.4

63.7

65.5

204.2

765.4

68.0

61.9

74.9

65.5

210.7

9

572.3

98.4

87.7

154.4

610.8

105.0

99.4

164.1

763.0

65.6

69.6

205.8

788.7

70.0

63.8

79.6

69.6

212.3

10

589.0

101.3

92.7

155.6

628.7

108.1

105.1

165.7

785.3

67.5

73.9

207.5

811.8

72.1

65.7

84.5

73.9

214.2

5

476.5

81.9

61.7

165.7

508.4

87.4

69.9

176.1

635.3

54.6

47.8

221.0

656.6

58.3

53.1

54.6

47.8

227.9

6

493.2

84.8

65.9

167.1

526.4

90.5

74.7

177.6

657.5

56.5

51.3

222.8

679.7

60.3

55.0

58.7

51.3

229.8

7

510.0

87.7

70.3

168.5

544.4

93.6

79.7

179.1

680.0

58.5

55.0

224.7

702.9

62.4

56.9

62.8

55.0

231.8

8

526.7

90.6

74.8

169.9

562.0

96.7

84.7

180.6

702.3

60.4

58.7

226.6

725.8

64.4

58.7

67.1

58.7

233.7

9

543.1

93.4

79.3

171.3

579.7

99.7

89.9

182.2

724.1

62.3

62.5

228.4

748.5

66.5

60.5

71.5

62.5

235.7

10

559.3

96.2

84.0

172.7

596.8

102.6

95.1

183.4

745.7

64.1

66.4

230.3

770.7

68.4

62.3

75.9

66.4

237.4

5

449.6

77.3

55.2

182.4

479.9

82.5

62.6

193.8

599.4

51.5

42.4

243.1

619.7

55.0

50.1

48.5

42.4

250.8

6

465.8

80.1

59.1

183.8

497.0

85.5

66.9

195.3

621.1

53.4

45.6

245.0

641.9

57.0

51.9

52.1

45.6

252.7

7

482.0

82.9

63.1

185.3

514.4

88.5

71.5

196.8

642.7

55.3

48.9

247.1

664.3

59.0

53.7

55.9

48.9

254.8

8

498.1

85.7

67.2

186.7

531.5

91.4

76.1

198.4

664.1

57.1

52.4

249.0

686.4

60.9

55.5

59.8

52.4

256.7

9

513.9

88.4

71.3

188.3

548.6

94.3

80.9

199.9

685.2

58.9

55.8

251.0

708.3

62.9

57.3

63.9

55.8

258.8

10

529.5

91.1

75.6

189.8

565.2

97.2

85.7

201.4

706.0

60.7

59.4

253.1

729.8

64.8

59.0

67.9

59.4

260.8

ABT:Condensate Air Inlet Temperature( )

CLOT:Chilled Water Outlet Temperature( )

CCAP:Cooling Capacity(kW)

CFR:Chilled Water Flow Rate at 5

CPD:Water Cooler Pressure Drop(kPa)

IPT:Input Power(kW)

12

Difference Between Inlet and Outlet Temperature(m3/h)


SECTION DATA

Cooling Capacities (R407C) Conversion Multiplier:1kW=860kcal/h =3412Btu/h 1kPa=0.102mAq

-50HzABT

25

30

35

40

ABT

25

30

35

40

CLOT

RCUG300AHYZ1

RCUG330AHYZ1

RCUG350AHYZ1

CCAP

CFR1,2

CPD1,2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

5

754.3

64.9

68.0

188.3

907.2

91.2

64.9

75.7

68.0

226.8

942.9

97.3

64.9

85.8

68.0

235.4

6

780.1

67.1

72.9

189.9

938.2

94.3

67.1

80.8

72.9

228.8

975.2

100.6

67.1

91.6

72.9

237.4

7

805.6

69.3

77.9

191.5

968.9

97.4

69.3

85.9

77.9

230.7

1007.0

103.9

69.3

97.4

77.9

239.4

8

831.1

71.5

83.0

193.2

999.4

100.4

71.5

91.2

83.0

232.8

1038.8

107.2

71.5

103.4

83.0

241.5

9

856.1

73.6

88.2

194.8

1029.6

103.4

73.6

96.6

88.2

234.8

1070.2

110.4

73.6

109.5

88.2

243.5

10

880.8

75.7

93.6

196.8

1059.2

106.4

75.7

102.0

93.6

237.1

1101.1

113.6

75.7

115.6

93.6

246.1

5

716.3

61.6

61.2

211.5

861.5

86.6

61.6

68.6

61.2

255.0

895.4

92.4

61.6

77.7

61.2

264.4

6

741.0

63.7

65.6

213.6

891.2

89.5

63.7

73.2

65.6

257.3

926.3

95.6

63.7

82.9

65.6

266.9

7

765.7

65.8

70.1

215.2

921.0

92.5

65.8

78.0

70.1

259.3

957.1

98.8

65.8

88.3

70.1

269.0

8

790.4

68.0

74.9

217.2

950.5

95.5

68.0

82.8

74.9

261.7

988.0

101.9

68.0

93.9

74.9

271.5

9

814.3

70.0

79.6

218.9

979.5

98.4

70.0

87.7

79.6

263.8

1017.9

105.0

70.0

99.4

79.6

273.6

10

838.3

72.1

84.5

220.9

1008.1

101.3

72.1

92.7

84.5

266.1

1047.9

108.1

72.1

105.1

84.5

276.1

5

677.9

58.3

54.6

234.7

815.4

81.9

58.3

61.7

54.6

283.1

847.4

87.4

58.3

69.9

54.6

293.4

6

701.9

60.3

58.7

236.8

844.1

84.8

60.3

65.9

58.7

285.5

877.3

90.5

60.3

74.7

58.7

296.0

7

725.8

62.4

62.8

238.8

872.9

87.7

62.4

70.3

62.8

287.9

907.3

93.6

62.4

79.7

62.8

298.5

8

749.4

64.4

67.1

240.9

901.4

90.6

64.4

74.8

67.1

290.4

936.7

96.7

64.4

84.7

67.1

301.1

9

772.9

66.5

71.5

242.9

929.5

93.4

66.5

79.3

71.5

292.8

966.2

99.7

66.5

89.9

71.5

303.6

10

795.7

68.4

75.9

244.5

957.2

96.2

68.4

84.0

75.9

295.0

994.7

102.6

68.4

95.1

75.9

305.7

5

639.9

55.0

48.5

258.4

769.5

77.3

55.0

55.2

48.5

311.6

799.9

82.5

55.0

62.6

48.5

323.0

6

662.7

57.0

52.1

260.4

797.2

80.1

57.0

59.1

52.1

314.0

828.4

85.5

57.0

66.9

52.1

325.5

7

685.9

59.0

55.9

262.5

825.0

82.9

59.0

63.1

55.9

316.5

857.4

88.5

59.0

71.5

55.9

328.1

8

708.7

60.9

59.8

264.5

852.5

85.7

60.9

67.2

59.8

319.0

885.9

91.4

60.9

76.1

59.8

330.6

9

731.5

62.9

63.9

266.5

879.6

88.4

62.9

71.3

63.9

321.5

914.4

94.3

62.9

80.9

63.9

333.2

10

753.5

64.8

67.9

268.6

906.2

91.1

64.8

75.6

67.9

324.1

941.9

97.2

64.8

85.7

67.9

335.7

CCAP

CFR1,2

CPD1,2

IPT

CCAP

CFR1

CFR2

CPD1

CPD2

IPT

CCAP

CFR1,2

CPD1,2

IPT

5

1060.2

91.2

75.7

265.2

1095.8

97.3

91.2

85.8

75.7

273.8

1131.5

97.3

85.8

282.4

6

1096.3

94.3

80.8

267.7

1133.3

100.6

94.3

91.6

80.8

276.3

1170.2

100.6

91.6

284.9

7

1132.2

97.4

85.9

269.9

1170.3

103.9

97.4

97.4

85.9

278.6

1208.4

103.9

97.4

287.3

8

1167.7

100.4

91.2

272.4

1207.2

107.2

100.4

103.4

91.2

281.1

1246.6

107.2

103.4

289.8

CLOT

RCUG360AHYZ1

RCUG380AHYZ1

RCUG400AHYZ1

9

1203.0

103.4

96.6

274.9

1243.6

110.4

103.4

109.5

96.6

283.5

1284.2

110.4

109.5

292.2

10

1237.6

106.4

102.0

277.4

1279.4

113.6

106.4

115.6

102.0

286.3

1321.3

113.6

115.6

295.3

5

1006.7

86.6

68.6

298.5

1040.6

92.4

86.6

77.7

68.6

307.9

1074.5

92.4

77.7

317.3

6

1041.3

89.5

73.2

301.0

1076.4

95.6

89.5

82.9

73.2

310.7

1111.5

95.6

82.9

320.3

7

1076.3

92.5

78.0

303.5

1112.4

98.8

92.5

88.3

78.0

313.1

1148.6

98.8

88.3

322.8

8

1110.6

95.5

82.8

306.3

1148.1

101.9

95.5

93.9

82.8

316.1

1185.6

101.9

93.9

325.8

9

1144.6

98.4

87.7

308.8

1183.0

105.0

98.4

99.4

87.7

318.5

1221.5

105.0

99.4

328.3

10

1177.9

101.3

92.7

311.2

1217.7

108.1

101.3

105.1

92.7

321.3

1257.4

108.1

105.1

331.3

5

952.9

81.9

61.7

331.5

984.9

87.4

81.9

69.9

61.7

341.8

1016.9

87.4

69.9

352.1

6

986.3

84.8

65.9

334.3

1019.5

90.5

84.8

74.7

65.9

344.7

1052.8

90.5

74.7

355.2

7

1020.0

87.7

70.3

337.1

1054.4

93.6

87.7

79.7

70.3

347.6

1088.7

93.6

79.7

358.2

8

1053.4

90.6

74.8

339.8

1088.7

96.7

90.6

84.7

74.8

350.6

1124.0

96.7

84.7

361.3

9

1086.1

93.4

79.3

342.6

1122.8

99.7

93.4

89.9

79.3

353.5

1159.4

99.7

89.9

364.3

10

1118.6

96.2

84.0

345.4

1156.1

102.6

96.2

95.1

84.0

356.1

1193.6

102.6

95.1

366.8

5

899.1

77.3

55.2

364.7

929.5

82.5

77.3

62.6

55.2

376.2

959.9

82.5

62.6

387.6

6

931.6

80.1

59.1

367.5

962.8

85.5

80.1

66.9

59.1

379.1

994.1

85.5

66.9

390.6

7

964.1

82.9

63.1

370.6

996.5

88.5

82.9

71.5

63.1

382.2

1028.9

88.5

71.5

393.7

8

996.2

85.7

67.2

373.4

1029.6

91.4

85.7

76.1

67.2

385.1

1063.1

91.4

76.1

396.7

9

1027.7

88.4

71.3

376.5

1062.5

94.3

88.4

80.9

71.3

388.2

1097.3

94.3

80.9

399.8

10

1058.9

91.1

75.6

379.6

1094.6

97.2

91.1

85.7

75.6

391.3

1130.3

97.2

85.7

402.9

ABT:Condensate Air Inlet Temperature( )

CLOT:Chilled Water Outlet Temperature( )

CCAP:Cooling Capacity(kW)

CFR:Chilled Water Flow Rate at 5

CPD:Water Cooler Pressure Drop(kPa)

IPT:Input Power(kW)

13

Difference Between Inlet and Outlet Temperature(m3/h)


SECTION DATA

Electric Data (Voltage:380V) Unit Main Power

Application Voltage(V)

Voltage

Max.

Model Hz

Min.

Compressor(Three Phases) Refrigeration STC(A)

Motor for Condenser Fan

RNC(A)

IPT (kW)

RNC(A)

IPT (kW)

Maximum Unit Current(A)

RCU75AHYZ1

178

94

55.8

4×2.7

4×1.1

151

RCU100AHYZ1

148

2×69

2×42.3

8×2.7

8×1.1

243

RCU120AHYZ1

178

2×87

2×52.5

8×2.7

8×1.1

283

RCU150AHYZ1

178

2×94

2×55.8

8×2.7

8×1.1

302

RCU180AHYZ1

178

3×87

3×52.5

12×2.7

12×1.1

424.5

RCU200AHYZ1

178

3×94

3×55.8

12×2.7

12×1.1

453

RCU240AHYZ1

178

4×87

4×52.5

16×2.7

16×1.1

566

RCU270AHYZ1

178

2×94+2×87

2×55.8+2×52.5

16×2.7

16×1.1

585

RCU300AHYZ1

178

4×94

4×55.8

16×2.7

16×1.1

604

RCU330AHYZ1

178

3×87+2×94

3×52.5+2×55.8

20×2.7

20×1.1

726.5

RCU350AHYZ1

178

5×94

5×55.8

20×2.7

20×1.1

755

RCU360AHYZ1

178

6×87

6×52.5

24×2.7

24×1.1

849

RCU380AHYZ1

178

3×94+3×87

3×55.8+3×52.5

24×2.7

24×1.1

877.5

RCU400AHYZ1

178

6×94

6×55.8

24×2.7

24×1.1

906

RCUG75AHYZ1

380

50

418

342

178

99

59.7

4×2.7

4×1.1

157

RCUG100AHYZ1

148

2×79

2×45.3

8×2.7

8×1.1

233

RCUG120AHYZ1

178

2×94

2×56.2

8×2.7

8×1.1

275

RCUG150AHYZ1

178

2×99

2×59.7

8×2.7

8×1.1

314

RCUG180AHYZ1

178

3×94

3×56.2

12×2.7

12×1.1

412.5

RCUG200AHYZ1

178

3×99

3×59.7

12×2.7

12×1.1

471

RCUG240AHYZ1

178

4×94

4×56.2

16×2.7

16×1.1

550

RCUG270AHYZ1

178

2×99+2×94

2×59.7+2×56.2

16×2.7

16×1.1

589

RCUG300AHYZ1

178

4×99

4×59.7

16×2.7

16×1.1

628

RCUG330AHYZ1

178

3×94+2×99

3×56.2+2×59.7

20×2.7

20×1.1

726.5

RCUG350AHYZ1

178

5×99

5×59.7

20×2.7

20×1.1

785

RCUG360AHYZ1

178

6×94

6×56.2

24×2.7

24×1.1

825

RCUG380AHYZ1

178

3×99+3×94

3×59.7+3×56.2

24×2.7

24×1.1

883.5

RCUG400AHYZ1

178

6×99

6×59.7

24×2.7

24×1.1

942

1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit General Data. 2. The starting current is indicated for each compressor. 3. The “Maximum Unit Current” is the total running of the unit under the following conditions, which consume the maximum current within the unit working range. Supplied Voltage: Rated Voltage×0.9 Condenser Water Inlet Temperature: 43 Chilled Water Outlet Temperature: 15 Capacity Control: 100% Therefore, the size of wiring and fuses must be determined according to applicable national and local codes. 4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below. One-Compressor Maximum Instantaneous

STC

Current 5. The unit power input can be estimated from the compressor in the Cooling Capacity Table and the condenser fan motor.

14


SECTION DATA

Electric Data Unit Main Power

Application Voltage(V)

Voltage

Max.

Model Hz

Min.

(Voltage:415V) Compressor(Three Phases) Refrigeration

STC(A)

Motor for Condenser Fan

RNC(A)

IPT (kW)

RNC(A)

IPT (kW)

Maximum Unit Current(A)

RCU75AHYZ1

195

86

55.8

4×2.7

4×1.1

133.3

RCU100AHYZ1

162

2×63

2×42.3

8×2.7

8×1.1

195.3

RCU120AHYZ1

195

2×80

2×52.5

8×2.7

8×1.1

248.0

RCU150AHYZ1

195

2×86

2×55.8

8×2.7

8×1.1

266.6

RCU180AHYZ1

195

3×80

3×52.5

12×2.7

12×1.1

372.0

RCU200AHYZ1

195

3×86

3×55.8

12×2.7

12×1.1

399.9

RCU240AHYZ1

195

4×80

4×52.5

16×2.7

16×1.1

496.0

RCU270AHYZ1

195

2×86+2×80

2×55.8+2×52.5

16×2.7

16×1.1

514.6

RCU300AHYZ1

195

4×86

4×55.8

16×2.7

16×1.1

533.2

RCU330AHYZ1

195

3×80+2×86

3×52.5+2×55.8

20×2.7

20×1.1

638.6

RCU350AHYZ1

195

5×86

5×55.8

20×2.7

20×1.1

666.5

RCU360AHYZ1

195

6×80

6×52.5

24×2.7

24×1.1

744.0

RCU380AHYZ1

195

3×86+3×80

3×55.8+3×52.5

24×2.7

24×1.1

771.9

RCU400AHYZ1

195

6×86

6×55.8

24×2.7

24×1.1

799.8

RCUG75AHYZ1

415

50

456

374

195

91

59.7

4×2.7

4×1.1

141.1

RCUG100AHYZ1

162

2×72

2×45.3

8×2.7

8×1.1

223.2

RCUG120AHYZ1

195

2×86

2×56.2

8×2.7

8×1.1

266.6

RCUG150AHYZ1

195

2×91

2×59.7

8×2.7

8×1.1

282.1

RCUG180AHYZ1

195

3×86

3×56.2

12×2.7

12×1.1

399.9

RCUG200AHYZ1

195

3×91

3×59.7

12×2.7

12×1.1

423.2

RCUG240AHYZ1

195

4×86

4×56.2

16×2.7

16×1.1

533.2

RCUG270AHYZ1

195

2×91+2×86

2×59.7+2×56.2

16×2.7

16×1.1

548.7

RCUG300AHYZ1

195

4×91

4×59.7

16×2.7

16×1.1

564.2

RCUG330AHYZ1

195

3×86+2×91

3×56.2+2×59.7

20×2.7

20×1.1

666.5

RCUG350AHYZ1

195

5×91

5×59.7

20×2.7

20×1.1

705.3

RCUG360AHYZ1

195

6×86

6×56.2

24×2.7

24×1.1

799.8

RCUG380AHYZ1

195

3×91+3×86

3×59.7+3×56.2

24×2.7

24×1.1

823.1

RCUG400AHYZ1

195

6×91

6×59.7

24×2.7

24×1.1

846.3

1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit General Data. 2. The starting current is indicated for each compressor. 3. The “Maximum Unit Current” is the total running of the unit under the following conditions, which consume the maximum current within the unit working range. Supplied Voltage: Rated Voltage×0.9 Condenser Water Inlet Temperature: 43 Chilled Water Outlet Temperature: 15 Capacity Control: 100% Therefore, the size of wiring and fuses must be determined according to applicable national and local codes. 4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below. One-Compressor Maximum Instantaneous

STC

Current 5. The unit power input can be estimated from the compressor in the Cooling Capacity Table and the condenser fan motor. 15


SOUND DATA

Sound Data Model

RCU75AHYZ1 RCUG75AHYZ1 RCU100AHYZ1 RCUG100AHYZ1 RCU120AHYZ1 RCUG120AHYZ1 RCU150AHYZ1 RCUG150AHYZ1 RCU180AHYZ1 RCUG180AHYZ1 RCU200AHYZ1 RCUG200AHYZ1 RCU240AHYZ1 RCUG240AHYZ1 RCU270AHYZ1 RCUG270AHYZ1 RCU300AHYZ1 RCUG300AHYZ1 RCU330AHYZ1 RCUG330AHYZ1 RCU350AHYZ1 RCUG350AHYZ1 RCU360AHYZ1 RCUG360AHYZ1 RCU380AHYZ1 RCUG380AHYZ1 RCU400AHYZ1 RCUG400AHYZ1

Unit Power Frequency :50Hz Frequency Band(Hz) 355~710 710~1400 1400~2800 2800~5600

45~90

90~180

180~355

5600~ 11200

Overall

51.5

55.8

63.8

66.7

67.4

61.8

45.3

39.8

70.1

52.4

56.5

64.7

66.3

67.4

66.5

46.2

41.5

71.4

52.8

57.2

65.4

66.5

67.8

66.9

46.7

42.2

71.8

52.8

57.3

65.5

66.8

68.1

66.9

46.8

42.3

72.0

53.1

57.5

66.4

67.3

68.7

67.2

47.2

42.6

72.5

53.1

57.7

66.7

67.6

68.8

67.5

47.2

42.6

72.7

53.3

57.9

66.8

68.1

69.3

67.8

47.3

43.1

73.1

53.3

57.9

66.8

68.3

69.4

67.9

47.3

43.1

73.2

53.3

57.9

66.8

68.4

69.5

67.9

47.3

43.1

73.3

53.5

58.1

67.3

68.8

70.1

68.2

47.6

43.4

73.7

53.5

58.1

67.3

69.1

70.3

68.4

47.6

43.4

73.9

54.7

58.6

67.9

69.5

70.9

69.2

49.4

44.5

74.6

54.7

58.6

67.9

69.7

71.1

69.4

49.4

44.5

74.8

55.2

58.5

68.1

69.9

71.4

69.7

49.6

44.9

75.0

SPL-A: A Scale Sound Pressure Level (dB) Notes: 1. The measuring point is 1.0 meter from the center of the unit surface and 1.5 meter from the floor level. 2. The units are operating under the standard working condition for cooling operation. 3. The above data was measured on a flat ground, Therefore, reflected sounds should be taken into consideration when the unit is

16


WOKING RANGE

Working Range Power Supply: Working Voltage :90%-100% Rating Voltage Unbalanced Voltage :Within ±3% Deviation from Each Voltage at Compressor Terminals Start Voltage:Higher than 85% of the Rated Voltage Maximum Water Flow Rate and Minimum Water Flow Rate (m3/h)

Model

Max.Flow Rate Min.Flow Rate

RCU75AHYZ1, RCUG75AHYZ1 RCU100AHYZ1, RCUG100AHYZ1 RCU120AHYZ1, RCUG120AHYZ1 RCU150AHYZ1, RCUG150AHYZ1 RCU180AHYZ1, RCUG180AHYZ1 RCU200AHYZ1, RCUG200AHYZ1 RCU240AHYZ1, RCUG240AHYZ1

67.5 76.4 98.3 135.0 152.2 159.4 196.6

21.0 28.6 35.2 42.0 53.4 57.1 70.4

Model

Max.Flow Rate Min.Flow Rate

RCU270AHYZ1, RCUG270AHYZ1 RCU300AHYZ1, RCUG300AHYZ1 RCU330AHYZ1, RCUG330AHYZ1 RCU350AHYZ1, RCUG350AHYZ1 RCU360AHYZ1, RCUG360AHYZ1 RCU380AHYZ1, RCUG380AHYZ1 RCU400AHYZ1, RCUG400AHYZ1

77.2 84.0 95.4 99.1 106.8 110.5 114.2 3

(m ) Volume

Internal Water Volume in Water Cooler

Model

233.3 270.0 287.2 294.4 304.4 311.6 318.8

Volume

Model

RCU75AHYZ1, RCUG75AHYZ1

0.07

RCU270AHYZ1, RCUG270AHYZ1

0.28

RCU100AHYZ1, RCUG100AHYZ1

0.14

RCU300AHYZ1, RCUG300AHYZ1

0.28

RCU120AHYZ1, RCUG120AHYZ1

0.14

RCU330AHYZ1, RCUG330AHYZ1

0.35

RCU150AHYZ1, RCUG150AHYZ1

0.14

RCU350AHYZ1, RCUG350AHYZ1

0.35

RCU180AHYZ1, RCUG180AHYZ1

0.21

RCU360AHYZ1, RCUG360AHYZ1

0.42

RCU200AHYZ1, RCUG200AHYZ1

0.21

RCU380AHYZ1, RCUG380AHYZ1

0.42

RCU240AHYZ1, RCUG240AHYZ1

0.28

RCU400AHYZ1, RCUG400AHYZ1

0.42

(m3)

Minimum Internal System Water Volume Model

RCU75AHYZ1

RCU100AHYZ1

RCU120AHYZ1

RCU150AHYZ1

RCU180AHYZ1

RCU200AHYZ1

RCU240AHYZ1

RCUG75AHYZ1

RCUG100AHYZ1

RCUG120AHYZ1

RCUG150AHYZ1

RCUG180AHYZ1

RCUG200AHYZ1

RCUG240AHYZ1

0.75

1.35

1.50

1.50

2.25

2.25

3.00

Volume(m3) Model

RCU270AHYZ1

RCU300AHYZ1

RCU330AHYZ1

RCU350AHYZ1

RCU360AHYZ1

RCU380AHYZ1

RCU400AHYZ1

RCUG270AHYZ1

RCUG300AHYZ1

RCUG330AHYZ1

RCUG350AHYZ1

RCUG360AHYZ1

RCUG380AHYZ1

RCUG400AHYZ1

3.00

3.00

3.75

3.75

4.50

4.50

4.50

Volume(m3)

Note: Minimum internal system water volume in the above table is setting according to standard ON/OFF differential. In case of changing ON/OFF differential, minimum internal system water volume shall be increased as follows. The Switch ON/OFF of Temperature Difference

Minimum Water Volume in System

2℃(Standard)

100%

1.5℃

130%

1℃

200%

Temperature Range The temperature range is given in the following table.

Standard 5~15℃ 5~43℃

I t em Chilled Water Outlet Temperature Condensate Air Inlet Temperature(DB) 17


COMPONENT DATA

Component Detailed Data(R22 and R407C) Compressor Compressor Type Revolution Displacement Capacity Control Air Tight Pressure

Motor

Oil

Model

50Hz 50Hz Continuous Control Type Discharge Suction Type Starting Method Poles Insulation Name Charge

— r/min m3/h % MPa MPa — — — — — Liters

50ASCC-Z

60ASCC-Z Semi-Hermetic 2,880

169.5

208.7 100~15, 0 3.0 2.0 Special Squirrel Cage, Three-Phase Motor Star-Delta Starting 2 F ICEMATIC UX300 6

Condenser and Condenser Fan RCU75 AHYZ1 RCUG75 AHYZ1

R22

Model R407C

Condenser Type

Material Condenser Outer Diameter Piping Tube Thickness(mean) Fin Material Maximum Operation Pressure Number of Condenser/unit(s) Type Number/Unit Condenser Fan Outer Diameter Revolution Type Starting Method Nominal Output Condenser Fan Motor Quantity Insulation Class Poles

— mm mm — MPa — — — mm r/min — — kW — — —

R22

Model R407C Condenser Type Material Condenser Outer Diameter Piping Tube Thickness(mean) Fin Material Maximum Operation Pressure Number of Condenser/unit(s) Type Number/Unit Condenser Fan Outer Diameter Revolution Type Starting Method Nominal Output Condenser Fan Motor Quantity Insulation Class Poles

— — mm mm — MPa — — — mm r/min — — kW — — —

RCU100 AHYZ1 RCUG100 AHYZ1

RCU120 AHYZ1 RCUG120 AHYZ1

RCU150 AHYZ1 RCUG150 AHYZ1

RCU180 AHYZ1 RCUG180 AHYZ1

RCU200 AHYZ1 RCUG200 AHYZ1

RCU240 AHYZ1 RCUG240 AHYZ1

9.53 0.4

9.53 0.4

9.53 0.4

3.0 12

3.0 12

3.0 2×8

12 710 960

12 710 960

2×8 710 960

0.9 12

0.9 12

0.9 2×8

Multi-Pass Cross Finned Tube 9.53 0.4

9.53 0.4

9.53 0.4

3.0 4

3.0 8

3.0 8

4 710 960

8 710 960

8 710 960

0.9 4

0.9 8

0.9 8

Copper Tube 9.53 0.4

Aluminum 3.0 8 Direct-Drive Propeller Fan 8 710 960 Drip-Proof Enclosure Direct-On-Line Starting 0.9 8 E 6

6

6

6

RCU270 AHYZ1 RCUG270 AHYZ1

RCU300 AHYZ1 RCUG300 AHYZ1

RCU330 AHYZ1 RCUG330 AHYZ1

RCU350 AHYZ1 RCUG350 AHYZ1

6

6

6

RCU360 AHYZ1 RCUG360 AHYZ1

RCU380 AHYZ1 RCUG380 AHYZ1

RCU400 AHYZ1 RCUG400 AHYZ1

9.53 0.4

9.53 0.4

9.53 0.4

3.0 2×12

3.0 2×12

3.0 2×12

2×12 710 960

2×12 710 960

2×12 710 960

0.9 2×12

0.9 2×12

0.9 2×12

6

6

6

Multi-Pass Cross Finned Tube Copper Tube 9.53 0.4

9.53 0.4

9.53 0.4

3.0 2×8

3.0 2×8

3.0 20

2×8 710 960

2×8 710 960

20 710 960

9.53 0.4

Aluminum 3.0 20

Direct-Drive Propeller Fan 20 710 960

Drip-Proof Enclosure Direct-On-Line Starting 0.9 2×8

0.9 2×8

0.9 20

6

6

6

18

0.9 20 E 6


COMPONENT DATA

Water Cooler Model Water Side

RCU(G)75 AHYZ1

RCU(G)100 AHYZ1

RCU(G)120 AHYZ1

RCU(G)150 AHYZ1 Steel

RCU(G)180 AHYZ1

RCU(G)200 AHYZ1

RCU(G)240 AHYZ1

356.2

356.2

356.2

356.2

431.8

431.8

356.2

1,276

2,296

2,296

2,296

2,400

2,400

2,296

Shell

Steel Refrigerant Side Material Outer Diameter Quantity

Tube

420

420

420

435

435

420

101

101

101

101

139

139

101

10

10

10

10

8

8

10

Copper 12.7

12.7

12.7

12.7

12.7

12.7

12.7

312

272

310

310

437

437

310×2

4

2

2

2

2

2

2+2

Refrigerant Side

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.6

1.6

1.6

1.6

1.6

1.6

1.6

Water Side

1.05

1.05

1.05

1.05

1.05

1.05

1.05

Number of Pass Maximum Pernissible Pressure

420

Insulation

Model

Polyethylene(25mm) RCU(G)270

RCU(G)300

RCU(G)330

RCU(G)350

RCU(G)360

RCU(G)380

RCU(G)400

AHYZ1

AHYZ1

AHYZ1

AHYZ1

AHYZ1

AHYZ1

AHYZ1

Steel Water Side

356.2

356.2

431.8+356.2

431.8+356.2

431.8

431.8

431.8

2,296

2,296

2,400+2,296

2,400+2,296

2,400

2,400

2,400

Shell

Steel Refrigerant Side

Tube

Material Outer Diameter Quantity

420

435+420

435+420

435

435

435

101

101

139+101

139+101

139

139

139

10

10

8+10

8+10

8

8

8

Copper 12.7

12.7

12.7

12.7

12.7

12.7

12.7

310×2

310×2

437+310

437+310

437×2

437×2

437×2

2+2

2+2

2+2

2+2

2+2

2+2

2+2

Refrigerant Side

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.6

1.6

1.6

1.6

1.6

1.6

1.6

Water Side

1.05

1.05

1.05

1.05

1.05

1.05

1.05

Number of Pass

Maximum Permissible Pressure

420

Insulation

Polyethylene(25mm)

19


CONTROL SYSTEM

Refrigerant System In addition to the basic air-cooled water chiller components (compressor, condenser, thermal expansion valves and water cooler), the following components are equipped in each refrigerant cycle: Stop Valve for Compressor Discharge Line and Liquid Line: These stop valves are equipped at the compressor discharge line and liquid line, and facilitate easy compressor service without appreciable leakage of refrigerant.

Capacity Control All models are equipped with an unloading system for each compressor, in order to adjust the cooling capacity and provide precise temperature control for the chilled water, coupled with electric thermostat.

Electric Operation Control Electrical Operation Control advanced HITACHI Water Chillers are as follows.

Control Panel ON switch, OFF switch, Power Supply Lamp, Operation Lamp, Alarm Lamp, Operation/Alarm Indicator for each refrigerant cycle and check switch are mounted in the Control Panel. The Control Panel is located at a position where easy access is available. Operation/Alarm indicator can display individual alarm codes such as High-Cut, Low-Cut etc. This function is very useful for detecting what alarm has occurred. Check switches are for checking chilled water temperature and alarm occurrence data. Chilled water temperature setting switches, ON/OFF Differential Setting Switches, Remote-Local Switch and so on are located at the rear side of Control Panel, in order not to access during operation.

Operation Hour Meter This hour-meter indicates the sum of the compressor operation.

Screw Compressor Cycling Protection Circuit The electric timer of the screw compressor cycling protection (CCP ) connected in the compressor control circuit delays the screw compressor restarting period for approximately three (3) minutes for No.1 compressor, four (4) minutes for No.2 compressor, five (5) minutes for No.3 compressor and six (6) minutes for No.4 compressor after the electronic thermostat calls for the cooling operation or automatic resetting of the protection devices, thereby preventing harmful screw compressor cycling operation.

Electronic Thermostat Circuit The electronic thermostat senses chilled water temperatures at the water cooler outlet, and operates solenoid valves for HITACHI screw compressor capacity control.

Screw Compressor Reversing Protection Circuit This circuit is composed of a reverse-phase protection devices, preventing reverse operation of the screw compressor, because the screw compressor definitely cannot be operated in the wrong direction as the misconnection of the main power phases.

Rotation of Compressor Operation Rotation of compressor operation order is available in order to balance operation hours of compressors. extends machine life.

This function

Restart after Short Period Power-Failure In the case that a power failure shorter than 2 seconds occurred, compressors can be restarted automatically within 3 minutes after power supply.

20


CONTROL SYSTEM

Refrigerant Charge R22 Model Charge Model Charge

RCU75AHYZ1

RCU100AHYZ1

RCU120AHYZ1

RCU150AHYZ1

RCU180AHYZ1

RCU200AHYZ1

RCU240AHYZ1

RCU270AHYZ1

RCU300AHYZ1

RCU330AHYZ1

RCU350AHYZ1

RCU360AHYZ1

RCU380AHYZ1

RCU400AHYZ1

2×+ 2×

3×+2X

3×+3×

R407C Model Charge Model Charge

RCUG75AHYZ1

RCUG100AHYZ1

RCUG120AHYZ1

RCUG150AHYZ1

RCUG180AHYZ1

RCUG200AHYZ1

RCUG240AHYZ1

RCUG270AHYZ1

RCUG300AHYZ1

RCUG330AHYZ1

RCUG350AHYZ1

RCUG360AHYZ1

RCUG380AHYZ1

RCUG400AHYZ1

2×+ 2×

3×+2×

3×+3×

Note : The blank part in above table would be supplied next.

Protection and Safety Control The safety and protective devices are equipped in the unit to ensure dependable and long life operation. Their functions should be carefully noted, and field adjustment is not recommended, if the setting is maintained at the point listed in the table.

Compressor Protection 1、The high pressure switch and the low pressure control protect against excessive discharge pressure and exceedingly low suction pressure. The switch and control cut out compressor operation when the discharge pressure exceeds the setting or when the suction pressure decrease below the setting. 2、Overcurrent relays equipped the magnetic switch box cut out each compressor operation when the current to the compressor exceeds the setting. 3、The internal thermostat embedded in the compressor motor winding cuts out each operations, when the temperature of the motor winding exceeds the setting. 4、An oil heater in the compressor prevents from oil foaming during cold starting. This heater warms the oil, while the compressor is stopped.

Fan Motor Protection The thermal overcurrent relays for the condenser fan motors cut out fan operation and compressor operation, when the current to the fan motor exceeds the setting.

Refrigerant Cycle 1、The fusible plug is equipped on the liquid line. When refrigerant temperature exceeds the melting point, and the plug melts and purges the refrigerant gas, in order to avoid explosion of the condenser. 2、The freeze protection control, for which the sensor is located in the water outlet near the water cooler, cuts out the compressor operation, when the water outlet temperature decreases below the setting.

21


CONTROL SYSTEM Safety and Control Device Setting (R22) Model High pressure control

RCU75AHYZ1

RCU100AHYZ1 RCU120AHYZ1 RCU150AHYZ1 RCU180AHYZ1 RCU200AHYZ1 RCU240AHYZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor)

Cut Off

MPa

2.98

2.98

2.98

2.98

2.98

Cut Off

MPa

0.05

0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)

0.05

Cut Off Cut In

℃ ℃

115 93

115 93

115 93

115 93

50Hz 50Hz

A A

88 88

67 67

88 88

80 80

Capacity Discharged Gas Thermostat

W

150

150

150

150

Cut Off Cut In

℃ ℃

70 100

70 100

70 100

70 100

s s s

180 5 30

180 5 30

180 5 30

180 5 30

180 5 30

180 5 30

180 5 30

A

6

6

6

6

6

6

6

72

72

72

72

72

72

72

2

2

2

2

2

2

2

140

140

140

140

140

140

140

A A

3.3 3.3

3.3 3.3

3.3 3.3

MPa

3.13

3.13

3.13

Low pressure control Internal Thermostat

Overcurrent Relay 380V For 415V Compressor Oil Heater

CCP Calculagraph Setting Time Star-Delta Starting From Start to Load-up Control Circuit

Fuse

Capacity(220V/240V) Fusible Plug Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan 380V 50Hz 415V 50Hz Pressure Relief Valve Starting to Open

115 93

115 93

115 93

80 88 80 80 88 80 One Oil Heater for Each Compressor Motor 150

150 (One for Each Unit)

150

70 70 70 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor)

(One for Each Circuit)

Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)

Model High pressure control

3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13

3.13

3.3 3.3

3.3 3.3

3.13

3.13

RCU270AHYZ1 RCU300AHYZ1 RCU330AHYZ1 RCU350AHYZ1 RCU360AHYZ1 RCU380AHYZ1 RCU400AHYZ1 Manual Reset, Adjustable(One Switch for Each Compressor Motor)

Cut Off

MPa

2.98

2.98

2.98

2.98

2.98

Cut Off

MPa

0.05

0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)

0.05

Cut Off Cut In

℃ ℃

115 93

115 93

115 93

115 93

A A

88\80 88\80

88 88

88\80 88\80

88 88

Capacity Discharged Gas Thermostat

W

150

150

150

150

Cut Off Cut In

℃ ℃

70 100

70 100

70 100

70 100

s s s

180 5 30

180 5 30

180 5 30

180 5 30

180 5 30

180 5 30

180 5 30

A

6

6

6

6

6

6

6

72

72

72

72

72

72

72

2

2

2

2

2

2

2

140

140

140

140

140

140

140

Low pressure control Internal Thermostat

Overcurrent Relay 380V 50Hz For 415V 50Hz Compressor Oil Heater

CCP Calculagraph Setting Time Star-Delta Starting From Start to Load-up Control Circuit

2.98 2.98 Control by Micro-Processor

Fuse

Capacity(220V/240V) Fusible Plug Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan 380V 50Hz 415V 50Hz Pressure Relief Valve Starting to Open

115 93

2.98 2.98 Control by Micro-Processor

115 93

115 93

80\88 88 80 80\88 88 80 One Oil Heater for Each Compressor Motor 150

150 (One for Each Circuit)

150

70 70 70 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor)

(One for Each Circuit)

Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor) A A

3.3 3.3

3.3 3.3

3.3 3.3

MPa

3.13

3.13

3.13

22

3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13

3.13

3.3 3.3

3.3 3.3

3.13

3.13


CONTROL SYSTEM Safety and Control Device Setting (R407C) RCUG75AHYZ1 RCUG100AHYZ1 RCUG120AHYZ1 RCUG150AHYZ1

Model

Cut Off

MPa

2.98

2.98

2.98

MPa

0.05

0.05

0.05

0.05

0.05

0.05

0.05

115

115

115

115

115

115

115

93

93

93

93

93

93

93

Manual Reset Adjustable (One Switch for Each Compressor Motor)

380V

50Hz

A

92

72

85

92

85

92

85

415V

50Hz

A

92

72

85

92

85

92

85

150

150

One Oil Heater for Each Compressor Motor Capacity

W

150

150

150

150

150

(One for Each Circuit)

Discharged Gas Thermostat Cut Off

70

70

70

70

70

70

70

Cut In

100

100

100

100

100

100

100

Setting Time

s

180

180

180

180

180

180

180

Star-Delta Starti

s

5

5

5

5

5

5

5

From Start to Load-up

s

30

30

30

30

30

30

30

A

6

6

6

6

6

6

6

72

72

72

72

72

72

72

2

2

2

2

2

2

2

140

140

140

140

140

140

140

380V 50Hz

A

3.3

3.3

3.3

3.3

3.3

3.3

3.3

415V 50Hz

A

3.3

3.3

3.3

3.3

3.3

3.3

3.3

3.13

3.13

3.13

Non-Adjustable (One Timer for Each Compressor Motor)

CCP Calculagraph

Fuse Capacity(220V/240V

(One for Each Circuit)

Fusible Plug Melt Temperature Frost-Proof Protection Cut Off Control of Exhaust Temperature Cut Off

Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)

Overcurrent relay for motor of fan

(One for Each Compressor)

Discharged valve of pressure Starting to Open

MPa

3.13

3.13

3.13

3.13

RCUG270AHYZ1 RCUG300AHYZ1 RCUG330AHYZ1 RCUG350AHYZ1

Model

Cut Off

MPa

2.98

2.98

2.98

2.98

2.98

2.98

2.98

Control by Micro-Processor

Low pressure control MPa

0.05

0.05 0.05 0.05 0.05 0.05 Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)

0.05

Cut Off

Cut In

115 93

115 93

115 93

Cut Off Internal Thermostat

Overcurrent Relay For Compressor

RCUG360AHYZ1 RCUG380AHYZ1 RCUG400AHYZ1

Manual Reset, Adjustable(One Switch for Each Compressor Motor)

High pressure control

380V

50Hz

A

415V

50Hz

A

92\85 92\85

92 92

W

150

150

Cut Off

Cut In

70 100

70 100 180 5 30 6

Oil Heater Capacity Discharged Gas Thermostat

CCP Calculagraph

Control Circuit

2.98

Cut In

Oil Heater

Refrigerant Circuit

2.98

Cut Off

Overcurrent Relay

Control Circuit

2.98

Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)

Internal Thermostat

For Compressor

2.98 Control by Micro-Processor

Low pressure control Cut Off

RCUG180AHYZ1 RCUG200AHYZ1 RCUG240AHYZ1

Manual Reset, Adjustable(One Switch for Each Compressor Motor)

High pressure control

Setting Time

s

Star-Delta Starting

s

From Start to Load-up

s

180 5 30

A

6

Fuse Capacity(220V/240V

115 115 115 115 93 93 93 93 Manual Reset Adjustable (One Switch for Each Compressor Motor) 85\92 92 85 85\92 92 85 One Oil Heater for Each Compressor Motor 150 150 150 (One for Each Circuit) 70 70 70 100 100 100 Non-Adjustable (One Timer for Each Compressor Motor) 180 180 180 5 5 5 30 30 30

92\85 92\85

92 92

150

150

70 100

70 100

180 5 30

180 5 30

6

6

6

6

6

72

72

72

72

72

72

(One for Each Circuit) 72

2

2

2

2

2

2

2

140

140

140

140

140

140

140

380V 50Hz

A

415V 50Hz

A

3.3 3.3

3.3 3.3

MPa

3.13

3.13

Fusible Plug Melt Temperature Refrigerant Frost-Proof Protection Circuit Cut Off Control of Exhaust Temperature Cut Off Overcurrent relay for motor of fan

Discharged valve of pressure Starting to Open

Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor) 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 (One for Each Compressor) 3.13 3.13 3.13 3.13

23

3.3 3.3 3.13


INSTALLATION DATA

Recommended Concrete Curbs RCU(G)75AHYZ1

Steel Plate: Field-Supplied

RCU(G)100AHYZ1、RCU(G)120AHYZ1 and RCU(G)150AHYZ1

Steel Plate: Field-Supplied

24


INSTALLATION DATA

Recommended Concrete Curbs RCU(G)180AHYZ1 and RCU(G)200AHYZ1

Steel Plate: Field-Supplied

RCU(G)240AHYZ1,RCU(G)270AHYZ1 and

RCU(G)300AHYZ1

Steel Plate: Field-Supplied

25


INSTALLATION DATA

Recommended Concrete Curbs RCU(G)330AHYZ1 and RCU(G)350AHYZ1

Steel Plate: Field-Supplied

RCU(G)360AHYZ1,RCU(G)380AHYZ1 and RCU(G)400AHYZ1

Steel Plate: Field-Supplied

26


CONTROL SYSTEM

27


CONTROL SYSTEM

28


CONTROL SYSTEM

29


CONTROL SYSTEM

30


CONTROL SYSTEM

31


CONTROL SYSTEM

32


SPECIFICATIONS

Standard Specifications Unit - The unit shall be an air-cooled screw type water chiller with R22 or R407C refrigerant, and shall be factory-completed with screw-type compressors, refrigeration cycle(s), air-cooled condensers, shell-and-tube water coolers, condenser fan motors, a star-delta starter, protective and safety devices, thermal expansion valves and compressor discharge stop valves, and shall be factory-assembled, piped, internal wired and charged with R22 or R407C refrigerant. The unit shall be completely weather-proofed for outdoor installation. The unit shall comply with Japanese Industrial Standards and other Chinese Industrial Standardization statues, including safety codes.

Compressor - The compressor shall be a semi-hermetic compressor from the same manufacturer. The compressor shall be serviceable type. The compressor protection system shall include an overcurrent relay, a pressure switch, a timer relays and an internal thermostat embedded in the motor winding. Water-Cooler-the water cooler shall be the dry expansion type with a horizontal welded steel construction shell, containing inside tubes. The seamless copper tube shall be the thermo fin cargated tube, in order to obtain the optimum heat transfer coefficient. The water side and the refrigerant side of the water cooler shall be tested for leakage. End plates shall be removable for maintenance.

Capacity - The cooling capacity of the unit shall kW or greater under the following be conditions: m3/h chilled water flow rate, chilled water inlet temperature, chilled water outlet temperature, m2. /W fouling factor for the water-side heat exchanger or greater. The water-side heat exchanger pressure decrease kPa. shall not exceed The compressor power input shall not exceed kW under the prescribed conditions. Power Supply - The unit shall operate on Hz, three-phase current, and shall be capable to V and minimum operate within maximum V.

Air-Side Heat Exchanger Fan and Fan Motor - The fan shall be the propeller type directly driven by a kW motor. The motor shall be thematically protected from overloaded conditions with a thermal overcurrent relay and shall be permanently lubricated, The winding and bearing of the condenser fan motor shall be weather-proof construction. Condenser-The condenser shall be the multi-pass, cross-finned tube type equipped with aluminum slit fins, mechanically bonded to seamless, oxygen-free copper tubes. The coil shall be cleaned, dehydrated and tested for leakage at the maximum permissible MPa. working pressure of

V,

Dimensions and Weight - The height of the unit mm, the width shall be mm, and shall be mm. The weight of the the depth shall be kg. unit shall not exceed

Accessories-Standard accessories shall include vibration-proof mates , foundation bolts and water side heat exchanger.

Cabinet - The cabinet shall be constructed of galvanized steel, baked with synthetic resin paint. The service panels shall be easily removable for service access to the electrical components, including magnetic switches and electrical devices.

33


Hitachi Appliances , Inc.

Distributed By:

Air Conditioning Division URL: http://www.hitachiacs.co.jp Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to their customers.

Printed in china

34