Ask the experts/Technical
Fully charged An introduction to the requirements for auxiliary circuits This article is the first of two dealing with auxiliary circuits. Whereas this article aims to provide a broad overview of use of auxiliary circuits, the second article will focus on the particular requirements of auxiliary circuits used in conjunction with instrument transformers.
A
lthough Section 557 – Auxiliary Circuits is introduced by Amendment 3 of BS 7671 as a separate section, the topic is not completely new. In previous editions of BS 7671, auxiliary circuits were referred to as ‘control circuits’ and were the subject of Regulation 537.5.3 (now deleted). Part 2 of BS 7671 defines auxiliary circuits as circuits for the transmission of signals intended for the detection, supervision or control of the functional status of a main circuit, such as circuits for control, signalling and measurement. The circuits used by a building management system (BMS) to monitor temperature and humidity at various points within a building are an example of auxiliary circuits. Regulation 557.1 makes it clear that Section 557 only applies to auxiliary circuits not covered by other product or system standards such as the construction of assemblies of electrical equipment to the appropriate part of the IEC 61439 series. However, as with many other standards, such as BS 5839 dealing with Fire Detection and Alarm Systems, it is a requirement of the standard that the installation of wiring associated with the alarm system complies with the requirements of BS 7671. Rather than being concerned with the operational characteristics of the equipment supplied by the auxiliary circuit, Section 557 is concerned with ensuring that the power supply is safe, reliable and does not impact upon the functionality of the equipment supplied by the auxiliary circuit. Broadly speaking, the contents of Section 557 cover the following areas:
52
1. The electrical supply to the auxiliary circuit and the associated protective measures (see Regulation Group 557.3). 2. The minimum cross-sectional area of the cables used for the auxiliary circuit (see Regulation Group 557.4). 3. The special requirements of auxiliary circuits used for measurement (see Regulation Group 557.5). 4. Measures required to avoid loss of functionality in the auxiliary circuit (see Regulation Group 557.6). Where the auxiliary circuit is a control circuit, Regulation 557.3.201 requires that the circuit should be designed, arranged and protected so that a fault between the circuit and other conductive parts is not liable to cause the equipment being controlled to malfunction, i.e. not operate as intended. The auxiliary circuits described in Section 557 may operate using an a.c. or d.c. supply which can either be obtained by either a connection to the main power circuit or from an independent source such as a battery. Section 557 includes requirements for the electrical protection provided for auxiliary circuits and the method used will depend upon whether the auxiliary circuits are earthed or unearthed. Rather than being permanently connected to the power supply some auxiliary circuits are connected via a switching device and Regulation 557.6.5.1 contains requirements for auxiliary circuits without a direct connection to a main circuit. Power supplies for auxiliary circuits dependent on the main a.c. circuit are detailed in Regulation 557.3.2.1. The recognised methods of connecting the auxiliary circuit are: 1. direct connection to the main a.c. supply (as shown by Fig 1), 2. via a rectifier (as shown by Fig 2), and 3. via a transformer providing simple separation between the main and auxiliary circuits (as shown by Fig 3). Regulation 557.3.2.1 recommends that where auxiliary circuits primarily supply electronic equipment or systems, then rather than being supplied directly (as shown in Fig 1) there should be, at least, simple separation from the main circuit. It should be noted, however, that rather than being a requirement this is a recommendation. Auxiliary circuits do not necessarily operate at extra-low voltages and the maximum preferred values of the nominal voltage for auxiliary circuits used for control purposes is as shown in Table 1 (Regulations 557.3.5.3 and 557.3.5.4.1 refer):
Spring 2015 Connections
44-68_technicals.FINAL.indd 52
02/04/2015 14:19